Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 08:56:28
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31084.06 | 671.07 | 671.07 |
Net Site Energy | 30547.56 | 659.48 | 659.48 |
Total Source Energy | 97246.45 | 2099.43 | 2099.43 |
Net Source Energy | 95547.36 | 2062.75 | 2062.75 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7019.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1712.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 263.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2726.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 903.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1993.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23218.79 |
Humidification | 10.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 574.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 30509.52 | 574.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25503.04 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 7019.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1712.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 263.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1144.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 4.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2726.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 903.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1993.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23218.79 |
Humidification | General | 10.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 574.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 7019.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1712.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 263.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2726.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 903.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1993.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23218.79 |
Humidification | Unassigned | 10.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 574.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 273.18 | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Other | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 658.66 | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 273.18 | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Other | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 658.66 | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 559.880 | 1.84 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -23.38 | -0.1 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 536.498 | 1.76 |
Electricity Coming From Utility | 29973.022 | 98.24 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 29973.022 | 98.24 |
Total On-Site and Utility Electric Sources | 30509.520 | 100.00 |
Total Electricity End Uses | 30509.520 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 25503.04 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 25503.04 | 100.00 |
Total Water End Uses | 25503.04 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1177.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.7776 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.7776 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.7776 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.7776 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.7776 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.7776 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.7776 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.7810 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:30 | 11-JAN-12:20 | - | - | - | - | - | - | - | - | - | - | 28-APR-11:00 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 644365.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 52589.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 243891.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 52932.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 84672.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 69577.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2002811.35 | 69577.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 644365.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3359.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 49008.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 221.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 243891.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 52932.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 84672.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 69577.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22230.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5422.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 834.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3812.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8633.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2862.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 6312.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 34.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 622.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 96623.65 | 622.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 479.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 186.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 61.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 136.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2085.99 | 13.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 479.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 186.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 61.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 136.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2085.99 | 13.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.29 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.467752 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.46 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.450459 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.37 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.73 | 0.331908 | 0.282000 | 1.62 | 0.885087 | 0.500000 | 0.001148 | 0.000356 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 54.67 | 0.347942 | 0.296000 | 16.18 | 0.927845 | 0.500000 | 0.001095 | 0.007072 | 16.18 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.52 | 0.344399 | 0.293000 | 1.62 | 0.918397 | 0.500000 | 0.001106 | 0.000988 | 1.62 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.27 | 0.187422 | 0.159000 | 0.202604 | 0.499793 | 0.500000 | 0.002033 | 0.000049 | 0.202604 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.07 | 0.144215 | 0.123000 | 0.131265 | 0.384573 | 0.500000 | 0.002642 | 0.000039 | 0.131265 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.43 | 0.167196 | 0.142000 | 0.202836 | 0.445856 | 0.500000 | 0.002279 | 0.000088 | 0.202836 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.40 | 0.110231 | 0.094000 | 0.131244 | 0.300000 | 0.500000 | 0.003456 | 0.000029 | 0.131244 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 13.03 | 0.183217 | 0.156000 | 2.03 | 0.488577 | 0.500000 | 0.002080 | 0.002310 | 3.14 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 11.38 | 0.360596 | 0.500000 | 0.002818 | 0.001540 | 2.10 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 14.56 | 0.164084 | 0.139000 | 2.02 | 0.437557 | 0.500000 | 0.002322 | 0.002307 | 3.14 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 12.64 | 0.121786 | 0.104000 | 1.31 | 0.324763 | 0.500000 | 0.003128 | 0.001297 | 1.76 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.45 | 0.164591 | 0.140000 | 0.203140 | 0.438908 | 0.500000 | 0.002315 | 0.000292 | 0.397463 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.18 | 0.130834 | 0.111000 | 0.130574 | 0.348890 | 0.500000 | 0.002912 | 0.000193 | 0.262951 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.60 | 0.149612 | 0.127000 | 0.202730 | 0.398966 | 0.500000 | 0.002547 | 0.000291 | 0.396826 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.36 | 0.113212 | 0.096000 | 0.130506 | 0.301899 | 0.500000 | 0.003365 | 0.000170 | 0.231439 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 16263.87 | 0.000356 | 453.93 |
CORE_MID VAV BOX REHEAT COIL | 323272.96 | 0.007072 | 10222.73 |
CORE_TOP VAV BOX REHEAT COIL | 45153.22 | 0.000988 | 1591.97 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 2249.00 | 0.000049 | 63.81 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 1767.27 | 0.000039 | 52.13 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 4008.05 | 0.000088 | 126.42 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 1320.84 | 0.000029 | 36.86 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 105602.83 | 0.002310 | 4110.77 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 70390.67 | 0.001540 | 2739.78 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 105464.42 | 0.002307 | 4105.40 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 59299.84 | 0.001297 | 2309.55 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 13341.24 | 0.000292 | 519.01 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 8825.48 | 0.000193 | 343.31 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 13319.92 | 0.000291 | 518.18 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7771.33 | 0.000170 | 302.40 |
VAV_BOT WITH REHEAT HEATING COIL | 9211.81 | 0.000202 | 217.99 |
VAV_MID WITH REHEAT HEATING COIL | 0.000000 | 0.000000 | 1.00 |
VAV_TOP WITH REHEAT HEATING COIL | 0.000000 | 0.000000 | 1.00 |
CAV_BAS HEATING COIL | 237422.88 | 0.005194 | 7867.64 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.45 | 2.28 | 10.90 | 2.28 | 9.91 | 9.91 | 0.300000 | 0.230466 | 9.91 |
VAV_MID WITH REHEAT | 53.14 | 22.86 | 106.27 | 22.86 | 93.75 | 93.75 | 0.300000 | 0.243841 | 93.75 |
VAV_TOP WITH REHEAT | 5.55 | 2.29 | 11.11 | 2.51 | 10.81 | 10.81 | 0.300000 | 0.231868 | 10.81 |
CAV_BAS | 5.29 | 5.29 | 5.29 | 5.29 | 5.29 | 5.29 | 1.00 | 1.00 | 5.29 |
AIRLOOP DATACENTER BASEMENT | 21.37 | 21.37 | 21.37 | 21.37 | 21.37 | 21.37 | 1.00 | 0.999991 | 21.37 |
AIRLOOP DATACENTER BOT | 0.467752 | 0.467752 | 0.467752 | 0.467752 | 0.467752 | 0.467752 | 1.00 | 1.00 | 0.467752 |
AIRLOOP DATACENTER MID | 4.46 | 4.46 | 4.46 | 4.46 | 4.46 | 4.46 | 1.00 | 1.00 | 4.46 |
AIRLOOP DATACENTER TOP | 0.450459 | 0.450459 | 0.450459 | 0.450459 | 0.450459 | 0.450459 | 1.00 | 1.00 | 0.450459 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.91 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 93.75 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.81 | |
CAV_BAS_OA_CONTROLLER | 5.29 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.37 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.467752 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.46 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.450459 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 27.85 | 6.67 | 11.04 | 0.008051 | 0.007000 | 236140.28 | 0.006754 | 9.91 |
VAV_MID WITH REHEAT COOLING COIL | 28.08 | 6.67 | 11.04 | 0.008142 | 0.007000 | 2285622.36 | 0.065369 | 93.75 |
VAV_TOP WITH REHEAT COOLING COIL | 27.54 | 6.67 | 11.05 | 0.008016 | 0.007000 | 252139.55 | 0.007211 | 10.81 |
CAV_BAS COOLING COIL | 28.43 | 6.67 | 11.42 | 0.008342 | 0.007000 | 132024.97 | 0.003776 | 5.29 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.91 |
VAV_MID WITH REHEAT FAN | 93.75 |
VAV_TOP WITH REHEAT FAN | 10.81 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006754 | 0.000071 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000202 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.065369 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.000000 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007211 | 0.000066 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000000 | |
CAV_BAS_COOLC_CONTROLLER | 0.003776 | 0.000126 |
CAV_BAS_HEATC_CONTROLLER | 0.005194 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.29 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.37 | 449431.10 | 286355.97 | 0.011007 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.467752 | 9869.68 | 6265.67 | 0.000242 |
AIRLOOP DATACENTER MID COOLING COIL | 4.46 | 94238.31 | 59804.86 | 0.002308 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.450459 | 9515.50 | 6037.40 | 0.000233 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.37 | 21.37 | 21.37 | 21.37 | 449431.10 | 449431.10 | 11172.98 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.467752 | 0.467752 | 0.467752 | 0.467752 | 9869.68 | 9869.68 | 516.15 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.46 | 4.46 | 4.46 | 4.46 | 94238.31 | 94238.31 | 5161.45 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.450459 | 0.450459 | 0.450459 | 0.450459 | 9515.50 | 9515.50 | 516.15 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.37 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.467752 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.46 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.450459 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.37 | 449431.10 | 0.011007 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.467752 | 9869.68 | 0.000242 |
AIRLOOP DATACENTER MID HEATING COIL | 4.46 | 94238.31 | 0.002308 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.450459 | 9515.50 | 0.000233 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 11172.98 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 516.15 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 5161.45 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 516.15 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000022 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.083109 | 13434.84 | |
HEATSYS1 PUMP | 0.022415 | 6683.59 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.083109 | 9.97 |
HEATSYS1 | 0.022415 | 2.69 |
COOLSYS1_SUPPLY | 0.083109 | 9.97 |
SINGLE WATER PLANT LOOP | 0.013789 | 1.65 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.083109 | 0.083109 | 348850.80 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1024685.60 | 1024685.60 | 0.022415 |
CENTRAL BOILER | 567995.62 | 557162.07 | 0.013789 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.041555 | 4650.70 |
COOLSYS1 CHILLER2 PUMP | 0.041555 | 4650.70 |
PLANT CIRC PUMP | 0.013789 | 3482.11 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.083109 | 0.041949 | 1470366.54 | 1477341.52 | 0.072630 |
COOLSYS1 CHILLER2 | 0.083109 | 0.041949 | 1470366.54 | 1477341.52 | 0.072630 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013789 | 139666.47 | 57442.41 | 69833.23 | 7004.20 | 21228.60 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.145260 | 17.43 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.145260 | 35607.07 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 53.84 | 1752856.88 | 10.77 | 219107.11 |
TOWERWATERSYS COOLTOWER 2 | 53.84 | 1752856.88 | 10.77 | 219107.11 |
Design Water Flow Rate [m3/s] Equipment # 45 | |
WSHPPLANT OPERATION SCHEME | 0.075938 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.778 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.619 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.778 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.201 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16058.301 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16058.301 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4527.754 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4527.754 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
51 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
52 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
53 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
54 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
55 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
56 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
57 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
58 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
59 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
60 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
61 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
62 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
63 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
64 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
65 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
66 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
67 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
68 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
69 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
70 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
71 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
72 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
73 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
74 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
75 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
76 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
77 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
78 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
79 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 35 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 36 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
3 | WINDOW_U_0.504_SHGC_WEST_0.219 | 37 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
4 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 38 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1309E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1321E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2756E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2766E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5896E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5903E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5426E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5431E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1580E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2332E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2977E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3606E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6066E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6560E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5556E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5883E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6239E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0110E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2576E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1206E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2225E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2224E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7703E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.6101E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1630E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2571E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3030E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3860E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6116E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6751E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5560E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5892E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1308E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1322E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2755E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2767E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5896E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5904E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5426E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5430E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3510E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4698E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1851E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3048E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0297E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0949E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6379E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6605E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7168E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7424E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4614E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5672E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5307E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4151E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8851E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.0771E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3252E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3782E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1533E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1922E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0104E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0266E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6380E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6608E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4920E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4932E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2886E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2896E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1402E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1409E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5426E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5431E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5197E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5879E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3112E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3654E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1575E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1953E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5560E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5893E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2700E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1690E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7659E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.9711E-003 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5501E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.0381E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7703E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.6072E-003 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5177E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5850E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3088E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3605E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1536E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1834E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5557E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5883E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4919E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4931E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2885E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2894E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1401E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1406E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5426E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5431E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9101E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9651E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6550E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6949E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6076E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6224E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6381E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6609E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0075E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4827E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6194E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2600E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8049E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1457E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8851E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.0771E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9312E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0285E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6814E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7753E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6258E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6839E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6379E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6604E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.0793E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.4954E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.5602E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.6640E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.9294E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4364E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.3990E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6803E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4413E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5383E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1569E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3241E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.2109E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1313E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.4843E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.6997E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.8655E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8859E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2913E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5116E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0465E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.1378E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3990E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6800E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6364E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1762E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2002E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8941E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3942E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7652E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.4843E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6997E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.0903E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.5049E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.5734E-002 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.6745E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.9427E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.4449E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.4063E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6840E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4457E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5423E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1618E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3279E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.2183E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1358E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.4917E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7034E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.8661E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8880E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2920E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5133E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0498E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.1398E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4063E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6837E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6391E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1793E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2031E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8969E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3999E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7687E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.4917E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7034E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 73238.61157 | 73238.61157 | 5.28874 | 5.28874 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 12.70000 | 9.15345E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 79353.24617 | 79353.24617 | 5.73064 | 5.73064 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 757127.54868 | 757127.54868 | 54.66557 | 54.66557 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 160426.92456 | 160426.92456 | 6.70499 | 10.77825 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 76488.67828 | 76488.67828 | 5.52280 | 5.52280 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 28867.83045 | 28867.83045 | 1.21801 | 1.21801 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 17481.46271 | 17481.46271 | 1.27424 | 1.27424 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 42.80000 | 1.07818E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 206.67511 | 206.67511 | 8.84845E-003 | 0.13533 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14640.99542 | 14640.99542 | 1.06719 | 1.06719 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 39.35650 | 1.07759E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 444.64758 | 444.64758 | 1.89597E-002 | 8.72129E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 19596.72594 | 19596.72594 | 1.42842 | 1.42842 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 1965.00048 | 1965.00048 | 8.29513E-002 | 0.13533 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 19154.92312 | 19154.92312 | 1.39621 | 1.39621 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 0.00000 | 0.00000 | 0.00000 | 8.72129E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 | |
17 | PERIMETER_MID_ZN_3 | Cooling | 178819.95481 | 178819.95481 | 13.03488 | 13.03488 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 73954.43019 | 73954.43019 | 3.14310 | 3.14310 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 156138.79286 | 156138.79286 | 11.38153 | 11.38153 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 39.59900 | 1.07763E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 49291.74581 | 49291.74581 | 2.09542 | 2.09542 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 199675.65865 | 199675.65865 | 14.55511 | 14.55511 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 42.80000 | 1.07818E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 73857.64790 | 73857.64790 | 3.13896 | 3.13896 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 173367.00468 | 173367.00468 | 12.63733 | 12.63733 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 41.83000 | 1.07801E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 41540.30297 | 41540.30297 | 1.76356 | 1.76356 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 19905.33018 | 19905.33018 | 1.45100 | 1.45100 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 42.60600 | 1.07815E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 9339.53575 | 9339.53575 | 0.39746 | 0.39746 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 16137.46668 | 16137.46668 | 1.17634 | 1.17634 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 39.84150 | 1.07767E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 6178.06950 | 6178.06950 | 0.26295 | 0.26295 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 21898.64594 | 21898.64594 | 1.59630 | 1.59630 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 42.80000 | 1.07818E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 9324.62611 | 9324.62611 | 0.39683 | 0.39683 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 18649.36160 | 18649.36160 | 1.35944 | 1.35944 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 5440.96491 | 5440.96491 | 0.23144 | 0.23144 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8137.08575 | 8137.08575 | 0.46775 | 0.46775 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 33.16467 | 1.07653E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 77654.19731 | 77654.19731 | 4.46387 | 4.46387 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 33.16467 | 1.07653E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7835.34461 | 7835.34461 | 0.45046 | 0.45046 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 40.63367 | 1.07781E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371752.60789 | 371752.60789 | 21.37181 | 21.37181 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 33.97300 | 1.07667E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 12.70000 | 9.15345E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 180335.17 | 9.91029 | 9.91029 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 184.19 | 1.52292 | 1.52292 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1730073.44 | 93.75290 | 93.75290 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 2452.33 | 20.91929 | 20.91929 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 192170.45 | 10.81081 | 10.81081 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 245.38 | 2.50668 | 2.50668 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
7 | CAV_BAS | Cooling | Sensible | 89797.17 | 5.28874 | 5.28874 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 39626.51 | 1.20016 | 1.20016 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 373005.54 | 21.37200 | 21.37200 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 11172.98 | 0.33839 | 0.33839 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8175.81 | 0.46775 | 0.46775 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 516.15 | 1.56323E-002 | 1.56323E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78067.29 | 4.46387 | 4.46387 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 5161.45 | 0.15632 | 0.15632 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8008.04 | 0.45046 | 0.45046 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 516.15 | 1.56323E-002 | 1.56323E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.28874 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.73064 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33191 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28200 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61604 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88509 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14791E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.55773E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61604 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16263.87207 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.55773E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 453.92630 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 54.66557 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34794 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29600 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.18101 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92784 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09501E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.07160E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.18101 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 323272.95525 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.07160E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10222.73468 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.52280 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34440 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29300 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61818 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91840 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10628E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.87728E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61818 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 45153.21981 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.87728E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1591.96975 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.27424 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18742 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15900 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20260 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49979 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.03284E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.91970E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20260 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2249.00471 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.91970E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 63.81223 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06719 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14421 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12300 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13126 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38457 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.64189E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.86590E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13126 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1767.26525 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.86590E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 52.13184 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.42842 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16720 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14200 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20284 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44586 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.27876E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.76762E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20284 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4008.05122 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.76762E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 126.41585 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39621 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11023 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.40000E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13124 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.45638E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.88934E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13124 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1320.83777 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.88934E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.86471 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.03488 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18322 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15600 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03344 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48858 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.07951E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.31006E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.14310 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 105602.82521 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.31006E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4110.76906 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.38153 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36060 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.81756E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.53980E-003 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.09542 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 70390.66537 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.53980E-003 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2739.77739 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.55511 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16408 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13900 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02316 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43756 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.32198E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.30704E-003 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.13896 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 105464.41661 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.30704E-003 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4105.39766 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.63733 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12179 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10400 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.31428 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32476 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.12844E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.29719E-003 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.76356 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 59299.83617 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.29719E-003 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2309.54896 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.45100 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16459 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14000 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20314 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43891 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.31484E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.91840E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39746 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13341.23809 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.91840E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 519.00668 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.17634 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13083 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11100 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13057 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34889 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.91209E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.93058E-004 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26295 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8825.47513 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.93058E-004 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 343.31376 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.59630 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14961 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12700 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20273 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39897 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54658E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.91374E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39683 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13319.92442 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.91374E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 518.17901 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.35944 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11321 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.60000E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13051 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30190 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.36536E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69998E-004 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23144 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7771.32784 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69998E-004 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 302.39558 |
209 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46775 |
210 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.46387 |
211 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45046 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.37181 |
213 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.44835 |
214 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28399 |
215 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.89670 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28399 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.91029 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.91029 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.23047 |
221 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 53.13721 |
222 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.86077 |
223 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 106.27442 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 22.86077 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 93.75290 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 93.75290 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.24384 |
229 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.55294 |
230 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28513 |
231 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.10587 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.50668 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.81081 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.81081 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.23187 |
237 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.28874 |
238 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.28874 |
239 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.28874 |
240 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.28874 |
241 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.28874 |
242 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.28874 |
243 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.37181 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.37181 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.37181 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.37181 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.37200 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.37200 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46775 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46775 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46775 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46775 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46775 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.46775 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.46387 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.46387 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.46387 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.46387 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.46387 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.46387 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45046 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45046 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45046 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45046 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45046 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45046 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.91029 |
278 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 93.75290 |
279 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.81081 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.28874 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.37200 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.46775 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.46387 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45046 |
285 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.91029 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.85263 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.03946 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.05137E-003 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 236140.28139 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.75358E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.91029 |
294 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 9211.80612 |
295 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.01509E-004 |
296 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 217.99368 |
297 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.91029 |
298 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.75358E-003 |
299 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.05093E-005 |
300 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.01509E-004 |
301 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 93.75290 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.07528 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.03975 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.14200E-003 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2285622.36037 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.53685E-002 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 93.75290 |
310 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 0.00000 |
311 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 0.00000 |
312 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1.00000 |
313 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 93.75290 |
314 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.53685E-002 |
315 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.28471E-006 |
316 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.00000 |
317 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.81081 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.53986 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04870 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.01567E-003 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 252139.54769 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.21116E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.81081 |
326 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 0.00000 |
327 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 0.00000 |
328 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1.00000 |
329 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.81081 |
330 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.21116E-003 |
331 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.60352E-005 |
332 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.00000 |
333 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.28874 |
334 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.43034 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
337 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.41927 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.34151E-003 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 132024.97187 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.77590E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.28874 |
343 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 237422.88179 |
344 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.19363E-003 |
345 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7867.64282 |
346 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.28874 |
347 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.77590E-003 |
348 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.26113E-004 |
349 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.19363E-003 |
350 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.37200 |
351 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
352 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.37200 |
353 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 449431.09831 |
354 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 286355.96505 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.10065E-002 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.37200 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.37200 |
358 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.37200 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.37200 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 449431.09831 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 449431.09831 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 11172.98038 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
364 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.37200 |
365 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.37200 |
366 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 449431.09831 |
367 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.10065E-002 |
368 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 11172.98038 |
369 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.23019E-005 |
370 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
371 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
373 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46775 |
374 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
375 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46775 |
376 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9869.68060 |
377 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6265.66846 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.41708E-004 |
379 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46775 |
380 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46775 |
381 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46775 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46775 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9869.68060 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9869.68060 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 516.14541 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
387 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46775 |
388 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46775 |
389 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9869.68060 |
390 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.41708E-004 |
391 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 516.14541 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.46387 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
394 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.46387 |
395 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 94238.30612 |
396 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 59804.86169 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.30789E-003 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.46387 |
399 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.46387 |
400 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.46387 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.46387 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 94238.30612 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 94238.30612 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 5161.45407 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
406 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.46387 |
407 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.46387 |
408 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 94238.30612 |
409 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.30789E-003 |
410 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 5161.45407 |
411 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45046 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
413 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45046 |
414 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9515.50400 |
415 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6037.39735 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.33034E-004 |
417 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45046 |
418 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45046 |
419 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45046 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45046 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9515.50400 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9515.50400 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 516.14541 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
425 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45046 |
426 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45046 |
427 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9515.50400 |
428 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.33034E-004 |
429 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 516.14541 |
430 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 8.31091E-002 |
431 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 13434.83613 |
432 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 8.31091E-002 |
433 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 9.97310 |
434 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 8.31091E-002 |
435 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 8.31091E-002 |
436 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 348850.79968 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
438 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.24150E-002 |
439 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.68980 |
440 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.24150E-002 |
441 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 6683.58563 |
442 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
443 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1024685.60283 |
444 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1024685.60000 |
445 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.24150E-002 |
446 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 8.31091E-002 |
447 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 9.97310 |
448 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 4.15546E-002 |
449 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4650.69506 |
450 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 4.15546E-002 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4650.69506 |
452 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.31091E-002 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.19493E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1470366.54386 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1477341.52000 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.26300E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.31091E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.19493E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1470366.54386 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1477341.52000 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.26300E-002 |
462 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.37892E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.65470 |
464 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.37892E-002 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3482.10701 |
466 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.37892E-002 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 57442.40802 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21228.59580 |
472 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 567995.61537 |
473 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 557162.07000 |
474 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.37892E-002 |
475 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
476 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
477 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
479 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
480 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.14526 |
481 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 17.43119 |
482 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.14526 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 35607.06685 |
484 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 53.84305 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1752856.87500 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.76861 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 219107.10938 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 53.84305 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1752856.87500 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.76861 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 219107.10938 |
492 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 7.59375E-002 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 7.59375E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 22640.54 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 450435.55 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 62867.72 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 3130.46 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 2461.70 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5584.75 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 1838.71 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 146952.69 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 97952.89 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 146760.08 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 82519.12 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 18565.18 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12281.21 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 18535.52 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10814.29 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 12170.28 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 0.00 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 0.00 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 272563.32 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 284071.63 | 192156.05 | 91915.58 | 0.68 | 63246.92 | 641.49 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2709184.99 | 1827113.54 | 882071.46 | 0.67 | 592623.24 | 6010.71 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 307584.83 | 208642.23 | 98942.60 | 0.68 | 69805.09 | 708.00 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 152106.76 | 102728.87 | 49377.89 | 0.68 | 30862.26 | 313.02 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.80 | 23.21 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.80 | 23.21 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2907433582 | 0.2226791721 | Pass | Pass | 1.1788491638 | 3.3588883145 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 7.5730596744E-002 | 0.1644973698 | Pass | Pass | 8.4693612772E-002 | 0.2772391316 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.3464287627E-003 | 5.5058577003E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.7447245311E-002 | 1.1426707445E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.7904121913E-002 | 0.1270962480 | Pass | Pass | 8.4532480767E-002 | 0.2773373759 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.2057215950E-002 | 0.1281453182 | Pass | Pass | 8.4583588677E-002 | 0.2774452552 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1050352421 | 0.1473924034 | Pass | Pass | 8.4695896944E-002 | 0.2775492312 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.6420854897E-002 | 0.1421043595 | Pass | Pass | 8.3646521844E-002 | 0.2759482509 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.0545048486E-002 | 2.4031287984E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.4328749759E-002 | 2.3581672429E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.1201686907E-002 | 5.4059971694E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.0629777718E-002 | 3.9211320255E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.0276296236E-002 | 2.9605409250E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.2714926719E-002 | 2.8298737769E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.8629753452E-002 | 5.8305067138E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.9349275093E-002 | 4.2195884438E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.2931763765E-002 | 2.0779653749E-002 | Pass | Pass | 0.1699814199 | 0.7256957437 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.7898588591E-003 | 6.2724737685E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.0478344712E-002 | 3.5467017821E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.2863755037E-004 | 1.4523103603E-004 | Pass | Pass | 1.7810725984E-003 | 1.3841048966E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 9.2196946476E-005 | 1.0055259178E-004 | Pass | Pass | 6.6458548612E-003 | 3.3243181877E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.4277026669E-005 | 8.7669657921E-005 | Pass | Pass | 2.1906436808E-002 | 1.0049238490E-002 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.2428531686E-004 | 5.0422824134E-004 | Pass | Pass | 8.5322179912E-005 | 1.1996708428E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3631.43 | -133.3 | 0.00 | -8806.9 | 46856.96 | 41548.20 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.504_SHGC_EAST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.504_SHGC_EAST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.504_SHGC_WEST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.504_SHGC_WEST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.504_SHGC_WEST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
North Total or Average | 1390.74 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.865 | 0.220 | 0.242 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.7776 | 2779.43 | 16058.30 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 116.04 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.7776 | 24961.20 | 144214.83 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 1042.11 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.93 | 0.0000 | Y | 7.45 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.88 | 0.0000 | Y | 4.79 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.74 | 0.0000 | Y | 7.39 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.85 | 0.0000 | Y | 4.79 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.7776 | 3134.13 | 18107.61 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.90 | 0.0000 | Y | 74.43 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.86 | 0.0000 | Y | 47.88 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.7776 | 3134.20 | 18108.01 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.73 | 0.0000 | Y | 73.85 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.82 | 0.0000 | Y | 47.80 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.90 | 0.0000 | Y | 7.44 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.86 | 0.0000 | Y | 4.79 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.73 | 0.0000 | Y | 7.38 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.82 | 0.0000 | Y | 4.78 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.7776 | 783.68 | 4527.75 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.66 | 0.0000 | Y | 32.85 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 7.1736 | 362.03 | 2597.04 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 16.76 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
Interior Lighting Total | 5.7907 | 46320.38 | 268225.21 | 539.77 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12952.94 | AstronomicalClock | - | 41.85 | 41.85 | 101.76 | |
EXTERIOR_LIGHTS_B | 919.74 | AstronomicalClock | - | 83.85 | 62.85 | 10.85 | |
EXTERIOR_LIGHTS_C | 17215.91 | AstronomicalClock | - | 83.85 | 46.68 | 150.86 | |
Exterior Lighting Total | 31088.59 | 263.47 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2896976.65 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1024685.60 | 0.90 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1477341.52 | 6.59 | 1295965.10 | 5.87 | 6.80 | 23.21 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1477341.52 | 6.59 | 1295965.10 | 5.87 | 6.80 | 23.21 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 557162.07 | 0.90 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1752856.88 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1752856.88 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 236140.28 | 284071.63 | 192156.05 | 91915.58 | 0.68 | - | 63246.92 | 641.49 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2285622.36 | 2709184.99 | 1827113.54 | 882071.46 | 0.67 | - | 592623.24 | 6010.71 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 252139.55 | 307584.83 | 208642.23 | 98942.60 | 0.68 | - | 69805.09 | 708.00 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 132024.97 | 152106.76 | 102728.87 | 49377.89 | 0.68 | - | 30862.26 | 313.02 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 449431.10 | 286355.97 | 163075.13 | 0.64 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9869.68 | 6265.67 | 3604.01 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 94238.31 | 59804.86 | 34433.44 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9515.50 | 6037.40 | 3478.11 | 0.63 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 16263.87 | 22640.54 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 323272.96 | 450435.55 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 45153.22 | 62867.72 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 2249.00 | 3130.46 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 1767.27 | 2461.70 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4008.05 | 5584.75 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 1320.84 | 1838.71 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 105602.83 | 146952.69 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 70390.67 | 97952.89 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 105464.42 | 146760.08 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 59299.84 | 82519.12 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 13341.24 | 18565.18 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 8825.48 | 12281.21 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13319.92 | 18535.52 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 7771.33 | 10814.29 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 9211.81 | 12170.28 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 0.00 | 0.00 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 0.00 | 0.00 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 237422.88 | 272563.32 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 449431.10 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9869.68 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 94238.31 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9515.50 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 11172.98 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 516.15 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 5161.45 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 516.15 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.91 | 21415.62 | 2160.95 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 93.75 | 202595.02 | 2160.95 | 1.00 | 1.08 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.81 | 23237.45 | 2149.46 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.29 | 8967.88 | 1695.65 | 1.00 | 1.16 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.37 | 35434.20 | 1657.97 | 1.00 | 1.13 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 523.93 | 1120.11 | 1.00 | 1.64 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.46 | 5000.01 | 1120.11 | 1.00 | 1.16 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 504.56 | 1120.11 | 1.00 | 1.65 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.083109 | 13434.84 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.022415 | 6683.59 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.041555 | 4650.70 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.041555 | 4650.70 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013789 | 3482.11 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.145260 | 35607.07 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 73238.61 | 73238.61 | 26.35 | 5.289 | 5.289 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00748 | 35.62 | 0.01077 | 1.200 | 0.00 |
CORE_BOTTOM | 79353.25 | 79353.25 | 31.79 | 5.731 | 5.731 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00739 | 35.62 | 0.01077 | 1.078 | 0.00 |
CORE_MID | 757127.55 | 757127.55 | 303.32 | 54.666 | 54.666 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00741 | 35.62 | 0.01077 | 10.778 | 0.00 |
CORE_TOP | 76488.68 | 76488.68 | 30.64 | 5.523 | 5.523 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00741 | 35.62 | 0.01077 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 17481.46 | 17481.46 | 55.78 | 1.274 | 1.274 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00729 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14641.00 | 14641.00 | 72.49 | 1.067 | 1.067 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 24.00 | 24.00 | 0.00723 | 39.36 | 0.01078 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 19596.73 | 19596.73 | 62.53 | 1.428 | 1.428 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00726 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 19154.92 | 19154.92 | 94.84 | 1.396 | 1.396 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00717 | 41.96 | 0.01078 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 178819.95 | 178819.95 | 570.56 | 13.035 | 13.035 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00738 | 42.70 | 0.01078 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 156138.79 | 156138.79 | 773.06 | 11.382 | 11.382 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 24.00 | 24.00 | 0.00729 | 39.60 | 0.01078 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 199675.66 | 199675.66 | 637.09 | 14.555 | 14.555 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00734 | 42.80 | 0.01078 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 173367.00 | 173367.00 | 858.36 | 12.637 | 12.637 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00726 | 41.83 | 0.01078 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 19905.33 | 19905.33 | 63.51 | 1.451 | 1.451 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00738 | 42.61 | 0.01078 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16137.47 | 16137.47 | 79.90 | 1.176 | 1.176 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 24.00 | 24.00 | 0.00731 | 39.84 | 0.01078 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 21898.65 | 21898.65 | 69.87 | 1.596 | 1.596 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00734 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18649.36 | 18649.36 | 92.33 | 1.359 | 1.359 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00727 | 41.96 | 0.01078 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8137.09 | 8137.09 | 224.76 | 0.468 | 0.468 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 33.16 | 0.01077 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 77654.20 | 77654.20 | 2144.98 | 4.464 | 4.464 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 33.16 | 0.01077 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7835.34 | 7835.34 | 216.43 | 0.450 | 0.450 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 27.00 | 27.00 | 0.00709 | 40.63 | 0.01078 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371752.61 | 371752.61 | 474.37 | 21.372 | 21.372 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 33.97 | 0.01077 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 26.43 | 0.00915 | 12.70 | 0.00915 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 23.79 | 0.00915 | 12.70 | 0.00915 | 1.078 | 0.00 | |
CORE_MID | 160426.92 | 160426.92 | 64.27 | 6.705 | 10.778 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 10.778 | 0.00 |
CORE_TOP | 28867.83 | 28867.83 | 11.57 | 1.218 | 1.218 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 206.68 | 206.68 | 0.66 | 0.009 | 0.135 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00889 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 444.65 | 444.65 | 2.20 | 0.019 | 0.087 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00864 | 12.70 | 0.00915 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 1965.00 | 1965.00 | 6.27 | 0.083 | 0.135 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00844 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 0.00 | 0.000 | 0.087 | 00:10:00 | 15.60 | 21.54 | 0.00915 | 12.70 | 0.00915 | 0.087 | 0.00 | |
PERIMETER_MID_ZN_3 | 73954.43 | 73954.43 | 235.96 | 3.143 | 3.143 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00824 | 12.70 | 0.00915 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 49291.75 | 49291.75 | 244.05 | 2.095 | 2.095 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00824 | 12.70 | 0.00915 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 73857.65 | 73857.65 | 235.65 | 3.139 | 3.139 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00824 | 12.70 | 0.00915 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 41540.30 | 41540.30 | 205.67 | 1.764 | 1.764 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00830 | 12.70 | 0.00915 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 9339.54 | 9339.54 | 29.80 | 0.397 | 0.397 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00819 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 6178.07 | 6178.07 | 30.59 | 0.263 | 0.263 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00818 | 12.70 | 0.00915 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 9324.63 | 9324.63 | 29.75 | 0.397 | 0.397 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00819 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 5440.96 | 5440.96 | 26.94 | 0.231 | 0.231 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00823 | 12.70 | 0.00915 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 12.70 | 0.00915 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 25.29 | 0.00702 | 12.70 | 0.00915 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.78 | 0.00833 | 12.70 | 0.00915 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 12.70 | 0.00915 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.91 | 9.91 | 1.52 | 1.52 | 9.9103 | 2.2840 | 9.9103 | 0.2305 | 0.3000 |
VAV_MID WITH REHEAT | 93.75 | 93.75 | 20.92 | 20.92 | 93.7529 | 22.8608 | 93.7529 | 0.2438 | 0.3000 |
VAV_TOP WITH REHEAT | 10.81 | 10.81 | 2.51 | 2.51 | 10.8108 | 2.5067 | 10.8108 | 0.2319 | 0.3000 |
CAV_BAS | 5.29 | 5.29 | 1.20 | 1.20 | 5.2887 | 5.2887 | 5.2887 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.37 | 21.37 | 0.34 | 0.34 | 21.3720 | 21.3718 | 21.3720 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.47 | 0.47 | 0.02 | 0.02 | 0.4678 | 0.4678 | 0.4678 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.46 | 4.46 | 0.16 | 0.16 | 4.4639 | 4.4639 | 4.4639 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.45 | 0.45 | 0.02 | 0.02 | 0.4505 | 0.4505 | 0.4505 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 16263.872 | 16263.872 | 1.616041 | 0.00035577 | 453.926 | 1/21 00:10:00 | 1/21 00:10:00 | 16263.87 | 16263.87 | 1.616041 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 16291.79 | 16291.79 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 323272.955 | 323272.955 | 16.181008 | 0.00707160 | 10222.735 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 323272.96 | 323272.96 | 16.181008 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 160426.92 | 0.00 | 324114.44 | 324114.44 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 45153.220 | 45153.220 | 1.618179 | 0.00098773 | 1591.970 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 45153.22 | 45153.22 | 1.618179 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 28867.83 | 0.00 | 45257.66 | 45257.66 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 2249.005 | 2249.005 | 0.202604 | 0.00004920 | 63.812 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2249.00 | 2249.00 | 0.202604 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00888907 | 57.3565 | 206.68 | 0.00 | 2252.78 | 2252.78 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 1767.265 | 1767.265 | 0.131265 | 0.00003866 | 52.132 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1767.27 | 1767.27 | 0.131265 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00864167 | 55.7817 | 444.65 | 0.00 | 1770.69 | 1770.69 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 4008.051 | 4008.051 | 0.202836 | 0.00008768 | 126.416 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4008.05 | 4008.05 | 0.202836 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00844177 | 54.5082 | 1965.00 | 0.00 | 4018.50 | 4018.50 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 1320.838 | 1320.838 | 0.131244 | 0.00002889 | 36.865 | 1/21 00:10:00 | 1/21 00:10:00 | 1320.84 | 1320.84 | 0.131244 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 1323.10 | 1323.10 | ||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 105602.825 | 105602.825 | 3.143104 | 0.00231006 | 4110.769 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 105602.83 | 105602.83 | 3.143104 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00824047 | 53.2244 | 73954.43 | 0.00 | 105827.65 | 105827.65 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 70390.665 | 70390.665 | 2.095420 | 0.00153980 | 2739.777 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 70390.67 | 70390.67 | 2.095420 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00823540 | 53.1920 | 49291.75 | 0.00 | 70540.53 | 70540.53 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 105464.417 | 105464.417 | 3.138965 | 0.00230704 | 4105.398 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 105464.42 | 105464.42 | 3.138965 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00824121 | 53.2291 | 73857.65 | 0.00 | 105688.95 | 105688.95 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 59299.836 | 59299.836 | 1.763556 | 0.00129719 | 2309.549 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 59299.84 | 59299.84 | 1.763556 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00829904 | 53.5975 | 41540.30 | 0.00 | 59426.07 | 59426.07 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 13341.238 | 13341.238 | 0.397463 | 0.00029184 | 519.007 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13341.24 | 13341.24 | 0.397463 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00818639 | 52.8797 | 9339.54 | 0.00 | 13369.65 | 13369.65 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 8825.475 | 8825.475 | 0.262951 | 0.00019306 | 343.314 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8825.48 | 8825.48 | 0.262951 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00818289 | 52.8574 | 6178.07 | 0.00 | 8844.27 | 8844.27 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 13319.924 | 13319.924 | 0.396826 | 0.00029137 | 518.179 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13319.92 | 13319.92 | 0.396826 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00818718 | 52.8848 | 9324.63 | 0.00 | 13348.29 | 13348.29 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 7771.328 | 7771.328 | 0.231439 | 0.00017000 | 302.396 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7771.33 | 7771.33 | 0.231439 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00823064 | 53.1616 | 5440.96 | 0.00 | 7787.87 | 7787.87 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 236140.281 | -999.000 | 9.910293 | 0.00675358 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 236140.28 | 207531.16 | 9.910293 | 27.85 | 17.35 | 0.00805137 | 11.04 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 20.4888 | 24.00 | 0.00734736 | 39.6083 | 135898.20 | 0.00 | 236456.30 | 219874.03 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 9211.806 | 9211.806 | 2.973088 | 0.00020151 | 217.994 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9211.81 | 9211.81 | 2.973088 | 10.24 | 10.24 | 0.00910772 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 68.2960 | 21.44 | 0.00878190 | 55.1720 | 0.00 | 0.00 | 10609.51 | 10609.51 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2285622.360 | -999.000 | 93.752900 | 0.06536851 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 2285622.36 | 1990892.59 | 93.752900 | 28.08 | 17.50 | 0.00814200 | 11.04 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 21.6591 | 24.00 | 0.00741110 | 39.9485 | 1284726.66 | 0.00 | 2288622.09 | 2105913.79 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 0.000 | 0.000 | 28.125870 | 0.00000000 | 1.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 28.125870 | 15.01 | 13.34 | 0.00885586 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 72.1969 | 21.00 | 0.00810865 | 52.3850 | 361679.65 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 252139.548 | -999.000 | 10.810811 | 0.00721116 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 252139.55 | 222079.52 | 10.810811 | 27.54 | 17.21 | 0.00801567 | 11.05 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 18.7821 | 24.00 | 0.00737371 | 39.7495 | 147885.73 | 0.00 | 252484.67 | 235646.59 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 0.000 | 0.000 | 3.243243 | 0.00000000 | 1.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 3.243243 | 15.80 | 13.54 | 0.00874394 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 62.6071 | 21.00 | 0.00806688 | 52.1190 | 41245.59 | 0.00 | 0.00 | 0.00 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 132024.972 | -999.000 | 5.288741 | 0.00377590 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 132024.97 | 112763.57 | 5.288741 | 28.43 | 17.78 | 0.00834151 | 11.42 | 9.94 | 0.00700000 | 41.54 | 0.01077963 | 23.52 | 22.6927 | 24.00 | 0.00751725 | 40.5131 | 66568.85 | 0.00 | 132186.98 | 120006.02 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 237422.882 | 237422.882 | 5.288741 | 0.00519363 | 7867.643 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 237422.88 | 237422.88 | 5.288741 | 2.88 | 2.88 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 22.6927 | 26.43 | 0.00915345 | 42.5676 | 0.00 | 0.00 | 196520.58 | 196520.58 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 449431.098 | 286355.965 | 21.371997 | 0.01100654 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 406852.04 | 401719.75 | -999.0 | 28.65 | 16.82 | 0.00710144 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | -999.0000 | 27.00 | 0.00704216 | 31.7851 | 371277.85 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9869.681 | 6265.668 | 0.467752 | 0.00024171 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 8941.14 | 8702.26 | -999.0 | 28.45 | 16.85 | 0.00721576 | 12.80 | 10.55 | 0.00700000 | 41.70 | 0.01077992 | 23.56 | -999.0000 | 27.00 | 0.00709036 | 31.9984 | 7999.97 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 94238.306 | 59804.862 | 4.463868 | 0.00230789 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 85379.56 | 82997.03 | -999.0 | 28.43 | 16.85 | 0.00722546 | 12.80 | 10.55 | 0.00700000 | 40.63 | 0.01077808 | 23.27 | -999.0000 | 27.00 | 0.00709447 | 32.0170 | 76465.49 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9515.504 | 6037.397 | 0.450459 | 0.00023303 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 8622.15 | 8387.11 | -999.0 | 28.46 | 16.86 | 0.00722038 | 12.80 | 10.55 | 0.00700000 | 41.70 | 0.01077992 | 23.56 | -999.0000 | 27.00 | 0.00709232 | 32.0072 | 7830.03 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 449431.098 | 449431.098 | 21.371997 | 0.01100654 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 449431.10 | 449431.10 | 21.371997 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 1.5833 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9869.681 | 9869.681 | 0.467752 | 0.00024171 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9869.68 | 9869.68 | 0.467752 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.3420 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 94238.306 | 94238.306 | 4.463868 | 0.00230789 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 94238.31 | 94238.31 | 4.463868 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.5020 | 25.29 | 0.00701680 | 35.0378 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9515.504 | 9515.504 | 0.450459 | 0.00023303 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9515.50 | 9515.50 | 0.450459 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.4703 | 24.78 | 0.00833028 | 42.7848 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 11172.980 | 11172.980 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 11172.98 | 11172.98 | 21.371997 | 0.20 | 0.20 | 0.00703410 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 1.5833 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 516.15 | 516.15 | 0.467752 | 0.42 | 0.42 | 0.00707197 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.3420 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 5161.454 | 5161.454 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 5161.45 | 5161.45 | 4.463868 | 0.44 | 0.44 | 0.00709162 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.5020 | 25.29 | 0.00701680 | 35.0378 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 516.15 | 516.15 | 0.450459 | 0.44 | 0.44 | 0.00835885 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.4703 | 24.78 | 0.00833028 | 42.7848 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 16263.872 | 16263.872 | 1.616041 | 0.00035577 | 453.926 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 1.5559 | 1.587206 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 16263.87 | 16263.87 | 1.0000 | 1.94505881 | 1.616041 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.35573636 | 60.00 | 48.89 | 11.11 | 0.000 | 16263.87 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 16291.79 | 16291.79 | 1.94505881 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 323272.955 | 323272.955 | 16.181008 | 0.00707160 | 10222.735 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 30.9261 | 31.548502 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 323272.96 | 323272.96 | 1.0000 | 19.47537999 | 16.181008 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 7.07088350 | 60.00 | 48.89 | 11.11 | 0.000 | 323272.96 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.59 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 160426.92 | 0.00 | 324114.44 | 324114.44 | 19.47537999 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.12 | 17.74 | 0.00800000 | 49702.1 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 45153.220 | 45153.220 | 1.618179 | 0.00098773 | 1591.970 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 4.3196 | 4.406544 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 45153.22 | 45153.22 | 1.0000 | 1.94763215 | 1.618179 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.98762718 | 60.00 | 48.89 | 11.11 | 0.000 | 45153.22 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 28867.83 | 0.00 | 45257.66 | 45257.66 | 1.94763215 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.59 | 19.84 | 0.00800000 | 56297.1 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2249.005 | 2249.005 | 0.202604 | 0.00004920 | 63.812 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 0.2152 | 0.219482 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2249.00 | 2249.00 | 1.0000 | 0.24385304 | 0.202604 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.04919202 | 60.00 | 48.89 | 11.11 | 0.000 | 2249.00 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.99 | 0.00888907 | 21.00 | 0.00888907 | 57.3565 | 206.68 | 0.00 | 2252.78 | 2252.78 | 0.24385304 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.86 | 15.17 | 0.00800000 | 42298.1 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1767.265 | 1767.265 | 0.131265 | 0.00003866 | 52.132 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 0.1691 | 0.172469 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1767.27 | 1767.27 | 1.0000 | 0.15798940 | 0.131265 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.03865503 | 60.00 | 48.89 | 11.11 | 0.000 | 1767.27 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.97 | 0.00864167 | 21.00 | 0.00864167 | 55.7817 | 444.65 | 0.00 | 1770.69 | 1770.69 | 0.15798940 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 23.79 | 15.88 | 0.00800000 | 44267.5 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4008.051 | 4008.051 | 0.202836 | 0.00008768 | 126.416 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 0.3834 | 0.391149 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4008.05 | 4008.05 | 1.0000 | 0.24413186 | 0.202836 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.08766729 | 60.00 | 48.89 | 11.11 | 0.000 | 4008.05 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.90 | 0.00844177 | 21.00 | 0.00844177 | 54.5082 | 1965.00 | 0.00 | 4018.50 | 4018.50 | 0.24413186 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.94 | 17.68 | 0.00800000 | 49520.2 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1320.838 | 1320.838 | 0.131244 | 0.00002889 | 36.865 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 0.1264 | 0.128902 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 1320.84 | 1320.84 | 1.0000 | 0.15796405 | 0.131244 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02889042 | 60.00 | 48.89 | 11.11 | 0.000 | 1320.84 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 1323.10 | 1323.10 | 0.15796405 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 105602.825 | 105602.825 | 3.143104 | 0.00231006 | 4110.769 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 10.1026 | 10.305876 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 105602.83 | 105602.83 | 1.0000 | 3.78302391 | 3.143104 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 2.30982909 | 60.00 | 48.89 | 11.11 | 0.000 | 105602.83 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00824047 | 21.00 | 0.00824047 | 53.2244 | 73954.43 | 0.00 | 105827.65 | 105827.65 | 3.78302391 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61034.2 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 70390.665 | 70390.665 | 2.095420 | 0.00153980 | 2739.777 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 6.7340 | 6.869489 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 70390.67 | 70390.67 | 1.0000 | 2.52203697 | 2.095420 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 1.53964069 | 60.00 | 48.89 | 11.11 | 0.000 | 70390.67 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00823540 | 21.00 | 0.00823540 | 53.1920 | 49291.75 | 0.00 | 70540.53 | 70540.53 | 2.52203697 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61029.5 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 105464.417 | 105464.417 | 3.138965 | 0.00230704 | 4105.398 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 10.0893 | 10.292368 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 105464.42 | 105464.42 | 1.0000 | 3.77804247 | 3.138965 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 2.30680170 | 60.00 | 48.89 | 11.11 | 0.000 | 105464.42 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00824121 | 21.00 | 0.00824121 | 53.2291 | 73857.65 | 0.00 | 105688.95 | 105688.95 | 3.77804247 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61034.4 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 59299.836 | 59299.836 | 1.763556 | 0.00129719 | 2309.549 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 5.6730 | 5.787125 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 59299.84 | 59299.84 | 1.0000 | 2.12260655 | 1.763556 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 1.29705324 | 60.00 | 48.89 | 11.11 | 0.000 | 59299.84 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.92 | 0.00829904 | 21.00 | 0.00829904 | 53.5975 | 41540.30 | 0.00 | 59426.07 | 59426.07 | 2.12260655 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.26 | 21.26 | 0.00800000 | 61056.6 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13341.238 | 13341.238 | 0.397463 | 0.00029184 | 519.007 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 1.2763 | 1.301984 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13341.24 | 13341.24 | 1.0000 | 0.47838397 | 0.397463 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.29181018 | 60.00 | 48.89 | 11.11 | 0.000 | 13341.24 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00818639 | 21.00 | 0.00818639 | 52.8797 | 9339.54 | 0.00 | 13369.65 | 13369.65 | 0.47838397 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61007.3 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8825.475 | 8825.475 | 0.262951 | 0.00019306 | 343.314 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 0.8443 | 0.861286 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8825.48 | 8825.48 | 1.0000 | 0.31648645 | 0.262951 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.19303782 | 60.00 | 48.89 | 11.11 | 0.000 | 8825.48 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00818289 | 21.00 | 0.00818289 | 52.8574 | 6178.07 | 0.00 | 8844.27 | 8844.27 | 0.31648645 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61005.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13319.924 | 13319.924 | 0.396826 | 0.00029137 | 518.179 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 1.2743 | 1.299904 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13319.92 | 13319.92 | 1.0000 | 0.47761761 | 0.396826 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.29134399 | 60.00 | 48.89 | 11.11 | 0.000 | 13319.92 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00818718 | 21.00 | 0.00818718 | 52.8848 | 9324.63 | 0.00 | 13348.29 | 13348.29 | 0.47761761 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61007.5 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7771.328 | 7771.328 | 0.231439 | 0.00017000 | 302.396 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 0.7434 | 0.758411 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7771.33 | 7771.33 | 1.0000 | 0.27855848 | 0.231439 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.16998067 | 60.00 | 48.89 | 11.11 | 0.000 | 7771.33 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00823064 | 21.00 | 0.00823064 | 53.1616 | 5440.96 | 0.00 | 7787.87 | 7787.87 | 0.27855848 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61017.6 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 236140.281 | -999.000 | 9.910293 | 0.00675358 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8071 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.910293 | 11.92797938 | 4197.9300 | 999.8980 | 83.10067097 | 15.00 | 6.67 | 8.33 | 2905927.16 | 8.1262 | 8.126160 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 236140.28 | 207531.16 | 1.0000 | 11.92797938 | 9.910293 | 27.85 | 17.35 | 0.00805137 | 48540.3 | 11.04 | 9.78 | 0.00700000 | 28743.1 | 6.75289322 | 6.67 | 15.00 | 8.33 | 21415.616 | 214724.67 | 42.80 | 0.01078182 | 23.86 | 2.03050000 | 20.4888 | 24.00 | 0.00734736 | 24.00 | 0.00734736 | 39.6083 | 135898.20 | 0.00 | 236456.30 | 219874.03 | 11.92797938 | 27.85 | 17.35 | 0.00805137 | 48540.3 | 9.78 | 9.76 | 0.00749951 | 28716.6 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 9211.806 | 9211.806 | 2.973088 | 0.00020151 | 217.994 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.910293 | 11.92797938 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 0.8813 | 0.898989 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9211.81 | 9211.81 | 1.0000 | 3.57839382 | 2.973088 | 10.24 | 10.24 | 0.00910772 | 33238.9 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.20148796 | 60.00 | 48.89 | 11.11 | 0.000 | 9211.81 | 12.70 | 0.00915345 | 12.70 | 2.03050000 | 68.2960 | 4.93 | 0.00900923 | 21.44 | 0.00878190 | 55.1720 | 0.00 | 0.00 | 10609.51 | 10609.51 | 3.57839382 | 2.80 | 2.80 | 0.00910772 | 25638.8 | 5.70 | 5.70 | 0.00910772 | 28603.7 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2285622.360 | -999.000 | 93.752900 | 0.06536851 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9756 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 93.752900 | 112.84051945 | 4197.9300 | 999.8980 | 83.10067097 | 15.00 | 6.67 | 8.33 | 2905927.16 | 78.6538 | 78.653808 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 2285622.36 | 1990892.59 | 1.0000 | 112.84051945 | 93.752900 | 28.08 | 17.50 | 0.00814200 | 48998.8 | 11.04 | 9.78 | 0.00700000 | 28743.4 | 65.36184191 | 6.67 | 15.00 | 8.33 | 202595.023 | 2083027.34 | 42.80 | 0.01078182 | 23.86 | 20.30600000 | 21.6591 | 24.00 | 0.00741110 | 24.00 | 0.00741110 | 39.9485 | 1284726.66 | 0.00 | 2288622.09 | 2105913.79 | 112.84051945 | 28.08 | 17.50 | 0.00814200 | 48998.8 | 9.78 | 9.76 | 0.00749925 | 28716.8 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 0.000 | 0.000 | 28.125870 | 0.00000000 | 1.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 93.752900 | 112.84051945 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 0.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 33.85215584 | 28.125870 | 15.01 | 13.34 | 0.00885586 | 37475.4 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.00000000 | 60.00 | 48.89 | 11.11 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 20.30600000 | 72.1969 | 21.00 | 0.00808311 | 21.00 | 0.00810865 | 52.3850 | 361679.65 | 0.00 | 0.00 | 0.00 | 33.85215584 | 2.80 | 2.80 | 0.00885586 | 25007.6 | 2.80 | 2.80 | 0.00885586 | 25007.6 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 252139.548 | -999.000 | 10.810811 | 0.00721116 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7407 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.810811 | 13.01183752 | 4197.9300 | 999.8980 | 83.10067097 | 15.00 | 6.67 | 8.33 | 2905927.16 | 8.6767 | 8.676733 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | Sensible | 252139.55 | 222079.52 | 1.0000 | 13.01183752 | 10.810811 | 27.54 | 17.21 | 0.00801567 | 48130.2 | 11.05 | 9.78 | 0.00700000 | 28752.5 | 7.21042353 | 6.67 | 15.00 | 8.33 | 23237.455 | 228902.09 | 42.80 | 0.01078182 | 23.86 | 2.03050000 | 18.7821 | 24.00 | 0.00737371 | 24.00 | 0.00737371 | 39.7495 | 147885.73 | 0.00 | 252484.67 | 235646.59 | 13.01183752 | 27.54 | 17.22 | 0.00801567 | 48130.2 | 9.78 | 9.76 | 0.00750198 | 28726.0 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 0.000 | 0.000 | 3.243243 | 0.00000000 | 1.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.810811 | 13.01183752 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 0.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 3.90355125 | 3.243243 | 15.80 | 13.54 | 0.00874394 | 38005.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.00000000 | 60.00 | 48.89 | 11.11 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 2.03050000 | 62.6071 | 21.00 | 0.00805831 | 21.00 | 0.00806688 | 52.1190 | 41245.59 | 0.00 | 0.00 | 0.00 | 3.90355125 | 2.80 | 2.80 | 0.00874394 | 24727.1 | 2.80 | 2.80 | 0.00874394 | 24727.1 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 132024.972 | -999.000 | 5.288741 | 0.00377590 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3464 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.288741 | 6.36550243 | 4197.9300 | 999.8980 | 83.10067097 | 15.00 | 6.67 | 8.33 | 2905927.16 | 4.5433 | 4.543299 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 132024.97 | 112763.57 | 1.0000 | 6.36550243 | 5.288741 | 28.43 | 17.78 | 0.00834151 | 49870.4 | 11.42 | 9.94 | 0.00700000 | 29129.7 | 3.77551230 | 6.67 | 15.00 | 8.33 | 8967.877 | 123057.09 | 41.54 | 0.01077963 | 23.52 | 1.20015641 | 22.6927 | 24.00 | 0.00751725 | 24.00 | 0.00751725 | 40.5131 | 66568.85 | 0.00 | 132186.98 | 120006.02 | 6.36550243 | 28.43 | 17.79 | 0.00834151 | 49870.4 | 9.95 | 9.93 | 0.00758198 | 29104.3 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 237422.882 | 237422.882 | 5.288741 | 0.00519363 | 7867.643 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.288741 | 6.36550243 | 4197.9300 | 999.8980 | 22.41273947 | 48.89 | 60.00 | 11.11 | 1045307.81 | 22.7132 | 23.170315 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 237422.88 | 237422.88 | 1.0000 | 6.36550243 | 5.288741 | 2.88 | 2.88 | 0.00915345 | 25837.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 5.19310233 | 60.00 | 48.89 | 11.11 | 0.000 | 237422.88 | 12.70 | 0.00915345 | 12.70 | 1.20015641 | 22.6927 | 0.00 | 0.00915345 | 26.43 | 0.00915345 | 42.5676 | 0.00 | 0.00 | 196520.58 | 196520.58 | 6.36550243 | 12.80 | 12.75 | 0.00915345 | 35972.0 | 43.01 | 22.85 | 0.00915345 | 66844.7 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 449431.098 | 286355.965 | 21.371997 | 0.01100654 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0412 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 406852.04 | 401719.75 | 0.9053 | -999.0 | -999.0 | 28.65 | 16.82 | 0.00710144 | 46927.5 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 406852.04 | 42.80 | 0.01078182 | 23.86 | 0.33839277 | -999.0000 | 27.00 | 0.00704216 | 27.00 | 0.00704216 | 31.7851 | 371277.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9869.681 | 6265.668 | 0.467752 | 0.00024171 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.2537 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | Sensible | 8941.14 | 8702.26 | 0.9059 | -999.0 | -999.0 | 28.45 | 16.85 | 0.00721576 | 47011.7 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8941.14 | 41.70 | 0.01077992 | 23.56 | 0.01563234 | -999.0000 | 27.00 | 0.00709036 | 27.00 | 0.00709036 | 31.9984 | 7999.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 94238.306 | 59804.862 | 4.463868 | 0.00230789 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.2718 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | Sensible | 85379.56 | 82997.03 | 0.9060 | -999.0 | -999.0 | 28.43 | 16.85 | 0.00722546 | 47021.2 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85379.56 | 40.63 | 0.01077808 | 23.27 | 0.15632344 | -999.0000 | 27.00 | 0.00709447 | 27.00 | 0.00709447 | 32.0170 | 76465.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9515.504 | 6037.397 | 0.450459 | 0.00023303 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.2623 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | Sensible | 8622.15 | 8387.11 | 0.9061 | -999.0 | -999.0 | 28.46 | 16.86 | 0.00722038 | 47034.5 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8622.15 | 41.70 | 0.01077992 | 23.56 | 0.01563234 | -999.0000 | 27.00 | 0.00709232 | 27.00 | 0.00709232 | 32.0072 | 7830.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 449431.098 | 449431.098 | 21.371997 | 0.01100654 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 449431.10 | 449431.10 | 1.0000 | 25.72322854 | 21.371997 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 449431.10 | 12.70 | 0.00915345 | 12.70 | 0.33839277 | 1.5833 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9869.681 | 9869.681 | 0.467752 | 0.00024171 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9869.68 | 9869.68 | 1.0000 | 0.56298346 | 0.467752 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9869.68 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.3420 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 94238.306 | 94238.306 | 4.463868 | 0.00230789 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 94238.31 | 94238.31 | 1.0000 | 5.37268871 | 4.463868 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 94238.31 | 12.70 | 0.00915345 | 12.70 | 0.15632344 | 3.5020 | 0.00 | 0.00701680 | 25.29 | 0.00701680 | 35.0378 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9515.504 | 9515.504 | 0.450459 | 0.00023303 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9515.50 | 9515.50 | 1.0000 | 0.54217025 | 0.450459 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9515.50 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.4703 | 0.00 | 0.00833028 | 24.78 | 0.00833028 | 42.7848 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11172.980 | 11172.980 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.371997 | 25.72322854 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 11172.98 | 11172.98 | 1.0000 | 25.72322854 | 21.371997 | 0.20 | 0.20 | 0.00703410 | 17796.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11172.98 | 12.70 | 0.00915345 | 12.70 | 0.33839277 | 1.5833 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.467752 | 0.56298346 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 516.15 | 516.15 | 1.0000 | 0.56298346 | 0.467752 | 0.42 | 0.42 | 0.00707197 | 18118.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 516.15 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.3420 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5161.454 | 5161.454 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.463868 | 5.37268871 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 5161.45 | 5161.45 | 1.0000 | 5.37268871 | 4.463868 | 0.44 | 0.44 | 0.00709162 | 18188.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5161.45 | 12.70 | 0.00915345 | 12.70 | 0.15632344 | 3.5020 | 0.00 | 0.00701680 | 25.29 | 0.00701680 | 35.0378 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.450459 | 0.54217025 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 516.15 | 516.15 | 1.0000 | 0.54217025 | 0.450459 | 0.44 | 0.44 | 0.00835885 | 21354.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 516.15 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.4703 | 0.00 | 0.00833028 | 24.78 | 0.00833028 | 42.7848 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5683.33 | 2011.00 | 2011.00 |
CORE_BOTTOM | 5712.33 | 0.17 | 0.17 |
CORE_MID | 5364.17 | 78.33 | 13.50 |
CORE_TOP | 5102.33 | 343.33 | 13.83 |
PERIMETER_BOT_ZN_3 | 5422.33 | 495.00 | 347.00 |
PERIMETER_BOT_ZN_2 | 5512.17 | 554.33 | 429.17 |
PERIMETER_BOT_ZN_1 | 5669.67 | 603.50 | 521.17 |
PERIMETER_BOT_ZN_4 | 5819.50 | 930.50 | 920.83 |
PERIMETER_MID_ZN_3 | 4846.17 | 1082.17 | 417.17 |
PERIMETER_MID_ZN_2 | 4388.17 | 860.00 | 548.83 |
PERIMETER_MID_ZN_1 | 5494.17 | 789.17 | 584.50 |
PERIMETER_MID_ZN_4 | 5329.50 | 936.00 | 637.00 |
PERIMETER_TOP_ZN_3 | 4708.67 | 1339.00 | 477.17 |
PERIMETER_TOP_ZN_2 | 5075.00 | 1085.83 | 587.50 |
PERIMETER_TOP_ZN_1 | 5354.67 | 958.50 | 619.33 |
PERIMETER_TOP_ZN_4 | 5170.17 | 1130.50 | 668.33 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1261.83 | 1261.83 |
DATACENTER_MID_ZN_6 | 5943.00 | 533.17 | 533.17 |
DATACENTER_TOP_ZN_6 | 5943.00 | 703.83 | 703.83 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 101.83 | 0.00 | 10.67 |
CORE_BOTTOM | 0.00 | 13.83 | 0.00 | 0.50 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 1.50 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 181.17 | 0.00 | 70.17 |
PERIMETER_BOT_ZN_2 | 0.00 | 192.83 | 0.00 | 92.50 |
PERIMETER_BOT_ZN_1 | 0.00 | 246.50 | 0.00 | 114.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 536.17 | 0.00 | 174.33 |
PERIMETER_MID_ZN_3 | 0.00 | 158.67 | 0.00 | 63.17 |
PERIMETER_MID_ZN_2 | 0.00 | 234.17 | 0.00 | 100.17 |
PERIMETER_MID_ZN_1 | 0.00 | 219.00 | 0.00 | 101.50 |
PERIMETER_MID_ZN_4 | 0.00 | 315.33 | 0.00 | 101.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 198.33 | 0.00 | 73.50 |
PERIMETER_TOP_ZN_2 | 0.00 | 265.67 | 0.00 | 105.33 |
PERIMETER_TOP_ZN_1 | 0.00 | 252.00 | 0.00 | 105.50 |
PERIMETER_TOP_ZN_4 | 0.00 | 333.17 | 0.00 | 106.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 745.50 | 0.00 | 516.67 |
DATACENTER_MID_ZN_6 | 0.00 | 659.83 | 0.00 | 454.17 |
DATACENTER_TOP_ZN_6 | 0.00 | 639.50 | 0.00 | 442.17 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 1228.67 | 0.00 | 926.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 1951.83 | 0.00 | 1177.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.64 | 149.60 | 6779.02 | 0.536 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.26 | 134.35 | 6849.35 | 0.473 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.26 | 134.35 | 6849.35 | 0.453 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.26 | 134.35 | 6849.35 | 0.447 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.06 | 16.87 | 860.00 | 0.683 | 0.037 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.55 | 10.87 | 554.22 | 0.787 | 0.038 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.06 | 16.87 | 860.02 | 0.845 | 0.037 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.55 | 10.87 | 554.22 | 1.183 | 0.038 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.06 | 16.87 | 860.00 | 0.739 | 0.087 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.98 | 10.87 | 554.22 | 0.910 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.06 | 16.87 | 860.02 | 0.965 | 0.087 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.55 | 10.87 | 554.22 | 1.003 | 0.090 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.06 | 16.87 | 860.00 | 0.714 | 0.108 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.55 | 10.87 | 554.22 | 0.912 | 0.112 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.06 | 16.87 | 860.02 | 0.925 | 0.108 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.55 | 10.87 | 554.22 | 0.953 | 0.112 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.82 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.82 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.82 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.66 | 42.18 | 1911.37 | 0.664 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.64 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.26 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.26 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.26 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.06 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.55 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.06 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.55 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.06 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.98 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.06 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.55 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.06 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.55 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.06 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.55 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.82 | 1.95 | 99.34 | 0.576 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.82 | 1.95 | 99.34 | 0.576 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.82 | 1.95 | 99.34 | 0.576 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.66 | 42.18 | 1911.37 | 0.648 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.64 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 56.26 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 56.26 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 56.26 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.06 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.55 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.06 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.55 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.06 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.98 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.06 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.55 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.06 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.55 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.06 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.55 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.82 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.82 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.82 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.66 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1038.25 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 23845732.91 | 0.00 | 23845732.91 | 0.00 | 23845732.91 | 37848132.68 | 3240.87 | 5519.13 | 0.00 | 698.28 |
CORE_BOTTOM | 24388099.99 | 0.00 | 24388099.99 | 0.00 | 24388099.99 | 33990283.35 | 7096.55 | 976.21 | 687.24 | 1545.64 |
CORE_MID | 0.22E+09 | 0.00 | 0.22E+09 | 0.00 | 0.22E+09 | 0.34E+09 | 7090.08 | 1050.12 | 619.79 | 1071.65 |
CORE_TOP | 21460788.21 | 0.00 | 21460788.21 | 0.00 | 21460788.21 | 33990283.35 | 7172.00 | 1157.19 | 430.82 | 1052.53 |
PERIMETER_BOT_ZN_3 | 4171464.96 | 0.00 | 4171464.96 | 322129.40 | 4493594.36 | 4267819.30 | 4053.17 | 962.10 | 3744.73 | 1545.64 |
PERIMETER_BOT_ZN_2 | 3018567.28 | 0.00 | 3018567.28 | 214752.79 | 3233320.07 | 2750345.05 | 3415.25 | 1130.06 | 4214.69 | 1545.64 |
PERIMETER_BOT_ZN_1 | 4997791.41 | 0.00 | 4997791.41 | 322129.40 | 5319920.82 | 4267912.63 | 2984.51 | 932.64 | 4842.85 | 1545.64 |
PERIMETER_BOT_ZN_4 | 4638779.81 | 0.00 | 4638779.81 | 214752.79 | 4853532.60 | 2750345.05 | 1986.13 | 860.59 | 5913.28 | 1545.64 |
PERIMETER_MID_ZN_3 | 42228838.50 | 0.00 | 42228838.50 | 755463.31 | 42984301.81 | 42678193.03 | 3998.66 | 1097.39 | 3663.95 | 1071.65 |
PERIMETER_MID_ZN_2 | 33056127.16 | 0.00 | 33056127.16 | 503641.86 | 33559769.02 | 27503450.52 | 3329.97 | 1017.16 | 4412.87 | 1966.32 |
PERIMETER_MID_ZN_1 | 53749721.22 | 0.00 | 53749721.22 | 755463.31 | 54505184.53 | 42679126.28 | 3353.96 | 651.94 | 4754.10 | 1071.65 |
PERIMETER_MID_ZN_4 | 36769061.05 | 0.00 | 36769061.05 | 503641.86 | 37272702.91 | 27503450.52 | 2858.18 | 916.61 | 4985.21 | 1071.65 |
PERIMETER_TOP_ZN_3 | 4118754.76 | 0.00 | 4118754.76 | 937962.89 | 5056717.64 | 4267819.30 | 3992.31 | 1141.08 | 3626.61 | 1052.53 |
PERIMETER_TOP_ZN_2 | 3318019.95 | 0.00 | 3318019.95 | 625308.16 | 3943328.12 | 2750345.05 | 3277.62 | 923.01 | 4559.37 | 1052.53 |
PERIMETER_TOP_ZN_1 | 5198717.13 | 0.00 | 5198717.13 | 937962.89 | 6136680.02 | 4267912.63 | 3181.92 | 869.74 | 4708.34 | 1052.53 |
PERIMETER_TOP_ZN_4 | 3531017.85 | 0.00 | 3531017.85 | 625308.16 | 4156326.02 | 2750345.05 | 3075.80 | 874.81 | 4809.39 | 1052.53 |
DATACENTER_BOT_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929815.99 | 0.00 | 4929815.99 | 0.00 | 4929815.99 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 10671554.30 | 0.00 | 10671554.30 | 0.00 | 10671554.30 | 10671554.30 | 0.00 | 8760.00 | 0.00 | 2817.00 |
Total Facility | 0.40E+10 | 0.00 | 0.40E+10 | 29382409.93 | 0.40E+10 | 0.50E+10 | 8708.93 | 8760.00 | 6346.38 | 3711.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9735 | 0.0000 | 0.9735 | 0.0000 | 0.9735 | 1.2002 | 1122.15 | 4820.85 | 0.00 |
CORE_BOTTOM | 0.8710 | 0.0000 | 0.8710 | 0.0000 | 0.8710 | 1.0778 | 4941.40 | 333.23 | 668.37 |
CORE_MID | 8.3367 | 0.0000 | 8.3367 | 0.0000 | 8.3367 | 10.7782 | 4825.40 | 502.96 | 614.64 |
CORE_TOP | 0.8233 | 0.0000 | 0.8233 | 0.0000 | 0.8233 | 1.0778 | 4840.18 | 674.02 | 428.80 |
PERIMETER_BOT_ZN_3 | 0.1573 | 0.0000 | 0.1573 | 0.0086 | 0.1659 | 0.1353 | 2055.46 | 359.30 | 3528.24 |
PERIMETER_BOT_ZN_2 | 0.1169 | 0.0000 | 0.1169 | 0.0057 | 0.1226 | 0.0872 | 1567.87 | 370.71 | 4004.42 |
PERIMETER_BOT_ZN_1 | 0.1949 | 0.0000 | 0.1949 | 0.0086 | 0.2035 | 0.1353 | 1066.23 | 292.80 | 4583.96 |
PERIMETER_BOT_ZN_4 | 0.1757 | 0.0000 | 0.1757 | 0.0057 | 0.1814 | 0.0872 | 645.50 | 254.52 | 5042.98 |
PERIMETER_MID_ZN_3 | 1.7014 | 0.0000 | 1.7014 | 0.0201 | 1.7214 | 1.3533 | 1958.23 | 501.51 | 3483.26 |
PERIMETER_MID_ZN_2 | 1.3505 | 0.0000 | 1.3505 | 0.0141 | 1.3646 | 0.8721 | 1131.76 | 466.67 | 3435.57 |
PERIMETER_MID_ZN_1 | 2.2270 | 0.0000 | 2.2270 | 0.0201 | 2.2471 | 1.3533 | 1102.40 | 329.43 | 4511.17 |
PERIMETER_MID_ZN_4 | 1.4884 | 0.0000 | 1.4884 | 0.0134 | 1.5018 | 0.8721 | 1056.15 | 370.82 | 4516.03 |
PERIMETER_TOP_ZN_3 | 0.1644 | 0.0000 | 0.1644 | 0.0249 | 0.1893 | 0.1353 | 1874.44 | 680.05 | 3388.51 |
PERIMETER_TOP_ZN_2 | 0.1355 | 0.0000 | 0.1355 | 0.0166 | 0.1521 | 0.0872 | 1123.16 | 588.83 | 4231.01 |
PERIMETER_TOP_ZN_1 | 0.2135 | 0.0000 | 0.2135 | 0.0249 | 0.2384 | 0.1353 | 1008.86 | 526.69 | 4407.45 |
PERIMETER_TOP_ZN_4 | 0.1415 | 0.0000 | 0.1415 | 0.0166 | 0.1581 | 0.0872 | 1075.15 | 567.17 | 4300.68 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.3384 | 0.0000 | 0.3384 | 0.0000 | 0.3384 | 0.3384 | 0.00 | 5943.00 | 0.00 |
Total Facility | 156.9402 | 0.0000 | 156.9402 | 0.7874 | 157.7276 | 158.4706 | 5917.54 | 5943.00 | 5266.60 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 59705320.71 | 0.00 | 59705320.71 | 48026705.38 | 1890.34 | 4.16 | 6865.50 | 1545.64 |
VAV_MID WITH REHEAT | 0.56E+09 | 0.00 | 0.56E+09 | 0.48E+09 | 2519.25 | 2.24 | 6238.50 | 1071.65 |
VAV_TOP WITH REHEAT | 54508444.04 | 0.00 | 54508444.04 | 48026705.38 | 2556.24 | 2.77 | 6200.99 | 1052.53 |
CAV_BAS | 34543903.50 | 0.00 | 34543903.50 | 37848132.68 | 3240.87 | 0.00 | 5519.13 | 698.28 |
AIRLOOP DATACENTER BASEMENT | 15459249.82 | 0.00 | 15459249.82 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 7141532.97 | 0.00 | 7141532.97 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.1960 | 0.0000 | 2.1960 | 1.5229 | 584.46 | 2.26 | 5356.27 |
VAV_MID WITH REHEAT | 21.8876 | 0.0000 | 21.8876 | 15.2292 | 748.05 | 1.15 | 5193.80 |
VAV_TOP WITH REHEAT | 2.1413 | 0.0000 | 2.1413 | 1.5229 | 761.46 | 1.36 | 5180.19 |
CAV_BAS | 1.4103 | 0.0000 | 1.4103 | 1.2002 | 1122.15 | 0.00 | 4820.85 |
AIRLOOP DATACENTER BASEMENT | 0.4902 | 0.0000 | 0.4902 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2265 | 0.0000 | 0.2265 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 327.10 | 0.00 | 0.00 | 0.00 | 0.00 | 6610.17 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 553.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5740.65 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 295.85 | 0.00 | 0.00 | 0.00 | 0.00 | 5965.49 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 5519.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.3530 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.4240 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 26.4831 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 24.7466 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.3647 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.4470 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7389 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4902 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2265 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1519 |
Defaulted Fields | 1187 |
Fields with Defaults | 3885 |
Autosized Fields | 333 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 30509.52 | 334859.09 | 21-JAN-04:00 | 2002811.35 | 10-AUG-15:30 |
Electricity:Building | 16388.72 | 215366.33 | 21-MAY-17:10 | 940052.87 | 15-DEC-17:00 |
Electricity:Zone:BASEMENT | 540.44 | 14022.76 | 01-JAN-00:10 | 23631.68 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16388.72 | 215366.33 | 21-MAY-17:10 | 940052.87 | 15-DEC-17:00 |
InteriorLights:Electricity | 1712.33 | 8110.17 | 01-JAN-09:30 | 164979.26 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1712.33 | 8110.17 | 01-JAN-09:30 | 164979.26 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity | 1712.33 | 8110.17 | 01-JAN-09:30 | 164979.26 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1712.33 | 8110.17 | 01-JAN-09:30 | 164979.26 | 15-MAR-07:10 |
Electricity:Zone:CORE_BOTTOM | 393.83 | 4960.84 | 01-JAN-00:10 | 26343.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 3938.24 | 49608.19 | 01-JAN-00:10 | 263436.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 393.82 | 4960.82 | 01-JAN-00:10 | 26343.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 43.82 | 589.50 | 26-MAR-17:10 | 3191.87 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.45 | 30.32 | 01-JAN-09:30 | 1031.32 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.45 | 30.32 | 01-JAN-09:30 | 1031.32 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 28.23 | 379.89 | 21-MAY-17:10 | 2047.26 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.79 | 19.54 | 01-JAN-08:00 | 654.92 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.79 | 19.54 | 01-JAN-08:00 | 654.92 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 43.76 | 589.50 | 12-MAR-17:10 | 3189.58 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.39 | 30.33 | 01-JAN-08:00 | 1029.00 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.39 | 30.33 | 01-JAN-08:00 | 1029.00 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 28.22 | 379.89 | 12-MAR-17:10 | 2061.19 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.79 | 19.54 | 01-JAN-09:30 | 668.86 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.79 | 19.54 | 01-JAN-09:30 | 668.86 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 438.08 | 5894.96 | 19-MAR-17:10 | 31905.48 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 74.43 | 303.25 | 01-JAN-09:20 | 10299.96 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 74.43 | 303.25 | 01-JAN-09:20 | 10299.96 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 282.24 | 3798.93 | 21-MAY-17:10 | 20453.46 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 47.88 | 195.42 | 01-JAN-08:00 | 6530.04 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 47.88 | 195.42 | 01-JAN-08:00 | 6530.04 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 437.51 | 5895.05 | 12-MAR-17:10 | 31882.50 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 73.85 | 303.26 | 01-JAN-08:00 | 10276.65 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 73.85 | 303.26 | 01-JAN-08:00 | 10276.65 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 282.15 | 3798.91 | 12-MAR-17:10 | 20593.44 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 47.80 | 195.42 | 01-JAN-09:30 | 6670.11 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 47.80 | 195.42 | 01-JAN-09:30 | 6670.11 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 43.81 | 589.50 | 19-MAR-17:10 | 3190.31 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.44 | 30.32 | 01-JAN-09:20 | 1029.75 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.44 | 30.32 | 01-JAN-09:20 | 1029.75 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 28.22 | 379.89 | 21-MAY-17:10 | 2045.18 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.79 | 19.54 | 01-JAN-08:00 | 652.84 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.79 | 19.54 | 01-JAN-08:00 | 652.84 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 43.75 | 589.50 | 12-MAR-17:10 | 3188.00 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.38 | 30.33 | 01-JAN-08:00 | 1027.42 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.38 | 30.33 | 01-JAN-08:00 | 1027.42 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 28.22 | 379.89 | 12-MAR-17:10 | 2059.20 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.78 | 19.54 | 01-JAN-09:30 | 666.86 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.78 | 19.54 | 01-JAN-09:30 | 666.86 | 14-MAR-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7527.71 | 95067.50 | 01-JAN-00:10 | 382501.19 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1555.56 | 19567.35 | 01-JAN-00:10 | 79407.42 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 6729.78 | 11112.55 | 20-JAN-05:50 | 588814.77 | 10-AUG-15:30 |
HeatRejection:Electricity | 1993.27 | 7490.51 | 20-JAN-07:00 | 84672.71 | 30-APR-15:10 |
General:HeatRejection:Electricity | 1993.27 | 7490.51 | 20-JAN-07:00 | 84672.71 | 30-APR-15:10 |
ElectricityProduced:Facility | 536.50 | -0.00 | 18-AUG-18:40 | 80415.16 | 21-MAY-12:30 |
ElectricityProduced:Plant | 536.50 | -0.00 | 18-AUG-18:40 | 80415.16 | 21-MAY-12:30 |
Photovoltaic:ElectricityProduced | 559.88 | 0.00 | 01-JAN-00:10 | 83680.20 | 21-MAY-12:30 |
PowerConversion:ElectricityProduced | -23.38 | -3265.05 | 21-MAY-12:30 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 5978.21 | 74582.39 | 10-JAN-02:30 | 447821.04 | 04-AUG-12:50 |
ExteriorEquipment:Electricity | 1203.69 | 17814.45 | 01-JAN-00:10 | 73698.15 | 15-MAR-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.35 | 979.82 | 01-JAN-00:10 | 3369.55 | 15-MAR-07:20 |
ElectricityPurchased:Facility | 29973.02 | 333425.05 | 21-MAY-12:30 | 1958546.36 | 10-AUG-15:30 |
ElectricityPurchased:Plant | 29973.02 | 333425.05 | 21-MAY-12:30 | 1958546.36 | 10-AUG-15:30 |
Cogeneration:ElectricityPurchased | 29973.02 | 333425.05 | 21-MAY-12:30 | 1958546.36 | 10-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 29973.02 | 333425.05 | 21-MAY-12:30 | 1958546.36 | 10-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 29973.02 | 333425.05 | 21-MAY-12:30 | 1958546.36 | 10-AUG-15:30 |
ElectricityNet:Plant | 29973.02 | 333425.05 | 21-MAY-12:30 | 1958546.36 | 10-AUG-15:30 |
Cogeneration:ElectricityNet | 29973.02 | 333425.05 | 21-MAY-12:30 | 1958546.36 | 10-AUG-15:30 |
General:Cogeneration:ElectricityNet | 29973.02 | 333425.05 | 21-MAY-12:30 | 1958546.36 | 10-AUG-15:30 |
Fans:Electricity | 2726.13 | 41462.71 | 13-MAY-23:40 | 258011.30 | 05-SEP-15:50 |
General:Fans:Electricity | 2726.13 | 41462.71 | 13-MAY-23:40 | 258011.30 | 05-SEP-15:50 |
ExteriorLights:Electricity | 263.47 | 0.00 | 01-JAN-07:10 | 31088.59 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 263.47 | 0.00 | 01-JAN-07:10 | 31088.59 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1144.44 | 16803.04 | 01-JAN-00:10 | 70012.65 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 4.90 | 31.59 | 01-JAN-00:10 | 315.94 | 01-JAN-07:10 |
Cooling:Electricity | 7019.55 | 30294.24 | 21-JAN-05:50 | 644365.65 | 10-AUG-15:30 |
General:Cooling:Electricity | 7019.55 | 30294.24 | 21-JAN-05:50 | 644365.65 | 10-AUG-15:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 10.96 | 0.00 | 01-JAN-12:00 | 14347.79 | 26-APR-10:10 |
General:Humidifier:Electricity | 10.96 | 0.00 | 01-JAN-12:00 | 14347.79 | 26-APR-10:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 903.72 | 3482.11 | 01-JAN-00:20 | 54068.20 | 05-JUL-05:10 |
General:Pumps:Electricity | 903.72 | 3482.11 | 01-JAN-00:20 | 54068.20 | 05-JUL-05:10 |
WIRED_LTG_ELECTRICITY | 48.12 | 0.00 | 01-JAN-00:10 | 4635.92 | 15-MAR-07:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 574.54 | 7280.88 | 21-MAY-15:10 | 69577.63 | 11-JAN-12:20 |
NaturalGas:Plant | 574.54 | 7280.88 | 21-MAY-15:10 | 69577.63 | 11-JAN-12:20 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 92.32 | 19-JAN-06:40 |
Boiler:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 92.32 | 19-JAN-06:40 |
WaterSystems:NaturalGas | 574.54 | 7280.88 | 21-MAY-15:10 | 69577.63 | 11-JAN-12:20 |
Water Heater:WaterSystems:NaturalGas | 574.54 | 7280.88 | 21-MAY-15:10 | 69577.63 | 11-JAN-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 39946.08 | 166838.49 | 21-JAN-05:50 | 3695456.38 | 10-AUG-16:00 |
PlantLoopCoolingDemand:HVAC | 39946.08 | 166838.49 | 21-JAN-05:50 | 3695456.38 | 10-AUG-16:00 |
CoolingCoils:PlantLoopCoolingDemand | 39946.08 | 166838.49 | 21-JAN-05:50 | 3695456.38 | 10-AUG-16:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 25503.04 | 0.00 | 09-JAN-00:10 | 0.00 | 28-APR-12:00 |
Water:HVAC | 4.08 | 0.00 | 01-JAN-12:00 | 0.00 | 26-APR-10:10 |
Humidifier:Water | 4.08 | 0.00 | 01-JAN-12:00 | 0.00 | 26-APR-10:10 |
General:Humidifier:Water | 4.08 | 0.00 | 01-JAN-12:00 | 0.00 | 26-APR-10:10 |
MainsWater:Facility | 25503.04 | 0.00 | 09-JAN-00:10 | 0.00 | 28-APR-12:00 |
MainsWater:HVAC | 4.08 | 0.00 | 01-JAN-12:00 | 0.00 | 26-APR-10:10 |
Humidifier:MainsWater | 4.08 | 0.00 | 01-JAN-12:00 | 0.00 | 26-APR-10:10 |
General:Humidifier:MainsWater | 4.08 | 0.00 | 01-JAN-12:00 | 0.00 | 26-APR-10:10 |
Water:Plant | 25498.96 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-12:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 25498.96 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-12:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 23218.79 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-10:50 |
General:HeatRejection:Water | 23218.79 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-10:50 |
HeatRejection:MainsWater | 23218.79 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-10:50 |
General:HeatRejection:MainsWater | 23218.79 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-10:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 144968.77 | 236976.12 | 21-JAN-05:50 | 14597165.36 | 10-AUG-16:00 |
EnergyTransfer:Building | 24073.24 | 100431.87 | 21-JAN-05:50 | 1797980.76 | 07-AUG-15:40 |
EnergyTransfer:Zone:BASEMENT | 734.20 | 0.00 | 01-JAN-00:40 | 75521.70 | 10-OCT-05:10 |
Heating:EnergyTransfer | 12.54 | 0.00 | 01-JAN-00:10 | 29926.05 | 29-JUL-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 5.58 | 0.00 | 01-JAN-00:10 | 29926.05 | 29-JUL-16:10 |
General:Heating:EnergyTransfer | 12.54 | 0.00 | 01-JAN-00:10 | 29926.05 | 29-JUL-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 5.58 | 0.00 | 01-JAN-00:10 | 29926.05 | 29-JUL-16:10 |
Cooling:EnergyTransfer | 24060.69 | 100431.87 | 21-JAN-05:50 | 1797980.76 | 07-AUG-15:40 |
Cooling:EnergyTransfer:Zone:BASEMENT | 728.61 | 0.00 | 01-JAN-00:40 | 75521.70 | 10-OCT-05:10 |
General:Cooling:EnergyTransfer | 24060.69 | 100431.87 | 21-JAN-05:50 | 1797980.76 | 07-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 728.61 | 0.00 | 01-JAN-00:40 | 75521.70 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 747.53 | 0.00 | 01-JAN-00:10 | 64947.73 | 07-AUG-05:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 747.53 | 0.00 | 01-JAN-00:10 | 64947.73 | 07-AUG-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 747.53 | 0.00 | 01-JAN-00:10 | 64947.73 | 07-AUG-05:10 |
EnergyTransfer:Zone:CORE_MID | 5697.45 | 0.00 | 01-JAN-00:10 | 437442.49 | 27-NOV-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5697.45 | 0.00 | 01-JAN-00:10 | 437442.49 | 27-NOV-06:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5697.45 | 0.00 | 01-JAN-00:10 | 437442.49 | 27-NOV-06:10 |
EnergyTransfer:Zone:CORE_TOP | 593.19 | 0.00 | 01-JAN-00:10 | 53145.48 | 07-AUG-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 593.19 | 0.00 | 01-JAN-00:10 | 53145.48 | 07-AUG-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 593.19 | 0.00 | 01-JAN-00:10 | 53145.48 | 07-AUG-05:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 142.07 | 0.00 | 01-JAN-00:10 | 14715.32 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 142.07 | 0.00 | 01-JAN-00:10 | 14715.32 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 142.07 | 0.00 | 01-JAN-00:10 | 14715.32 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 104.69 | 0.00 | 01-JAN-00:10 | 12263.47 | 31-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 104.69 | 0.00 | 01-JAN-00:10 | 12263.47 | 31-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 104.69 | 0.00 | 01-JAN-00:10 | 12263.47 | 31-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 171.44 | 0.00 | 01-JAN-00:10 | 16788.00 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 171.44 | 0.00 | 01-JAN-00:10 | 16788.00 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 171.44 | 0.00 | 01-JAN-00:10 | 16788.00 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 156.11 | 0.00 | 01-JAN-00:10 | 17086.73 | 10-AUG-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 156.11 | 0.00 | 01-JAN-00:10 | 17086.73 | 10-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 156.11 | 0.00 | 01-JAN-00:10 | 17086.73 | 10-AUG-15:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1242.57 | 0.00 | 01-JAN-00:10 | 143149.12 | 21-JUL-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1242.57 | 0.00 | 01-JAN-00:10 | 143149.12 | 21-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1242.57 | 0.00 | 01-JAN-00:10 | 143149.12 | 21-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 996.73 | 0.00 | 01-JAN-00:10 | 130765.63 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 996.73 | 0.00 | 01-JAN-00:10 | 130765.63 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 996.73 | 0.00 | 01-JAN-00:10 | 130765.63 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1573.90 | 0.00 | 01-JAN-00:10 | 167820.27 | 05-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1573.90 | 0.00 | 01-JAN-00:10 | 167820.27 | 05-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1573.90 | 0.00 | 01-JAN-00:10 | 167820.27 | 05-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1084.76 | 0.00 | 01-JAN-00:10 | 133671.67 | 10-AUG-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1084.76 | 0.00 | 01-JAN-00:10 | 133671.67 | 10-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1084.76 | 0.00 | 01-JAN-00:10 | 133671.67 | 10-AUG-15:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 129.10 | 0.00 | 01-JAN-00:10 | 15496.19 | 21-JUL-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 543.83 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 543.83 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 129.10 | 0.00 | 01-JAN-00:10 | 15496.19 | 21-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 129.10 | 0.00 | 01-JAN-00:10 | 15496.19 | 21-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 105.54 | 0.00 | 01-JAN-00:10 | 13154.80 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 266.17 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 266.17 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 105.54 | 0.00 | 01-JAN-00:10 | 13154.80 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 105.54 | 0.00 | 01-JAN-00:10 | 13154.80 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 161.09 | 0.00 | 01-JAN-00:10 | 17614.66 | 05-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 161.09 | 0.00 | 01-JAN-00:10 | 17614.66 | 05-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 161.09 | 0.00 | 01-JAN-00:10 | 17614.66 | 05-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 111.24 | 0.00 | 01-JAN-00:10 | 14093.39 | 10-AUG-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 111.24 | 0.00 | 01-JAN-00:10 | 14093.39 | 10-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 111.24 | 0.00 | 01-JAN-00:10 | 14093.39 | 10-AUG-15:50 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 149.66 | 0.00 | 01-JAN-00:10 | 21610.30 | 07-AUG-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.67 | 0.00 | 01-JAN-00:10 | 2963.71 | 12-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.67 | 0.00 | 01-JAN-00:10 | 2963.71 | 12-FEB-11:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 148.99 | 0.00 | 01-JAN-00:10 | 21610.30 | 07-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 148.99 | 0.00 | 01-JAN-00:10 | 21610.30 | 07-AUG-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1205.30 | 0.00 | 01-JAN-00:10 | 154768.67 | 07-AUG-05:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.48 | 0.00 | 01-JAN-00:10 | 22680.15 | 15-JAN-12:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.48 | 0.00 | 01-JAN-00:10 | 22680.15 | 15-JAN-12:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1200.82 | 0.00 | 01-JAN-00:10 | 154768.67 | 07-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1200.82 | 0.00 | 01-JAN-00:10 | 154768.67 | 07-AUG-05:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 175.79 | 0.00 | 01-JAN-00:10 | 27354.24 | 16-AUG-13:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.81 | 0.00 | 01-JAN-00:10 | 5158.48 | 21-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.81 | 0.00 | 01-JAN-00:10 | 5158.48 | 21-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 173.97 | 0.00 | 01-JAN-00:10 | 27354.24 | 16-AUG-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 173.97 | 0.00 | 01-JAN-00:10 | 27354.24 | 16-AUG-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.05 | 1243.94 | 21-JAN-08:00 | 7808.09 | 02-APR-16:30 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.05 | 1243.94 | 21-JAN-08:00 | 7808.09 | 02-APR-16:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.05 | 1243.94 | 21-JAN-08:00 | 7808.09 | 02-APR-16:30 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1337.60 | 7918.88 | 21-JAN-08:00 | 73748.00 | 23-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1337.60 | 7918.88 | 21-JAN-08:00 | 73748.00 | 23-APR-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1337.60 | 7918.88 | 21-JAN-08:00 | 73748.00 | 23-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.41 | 255.29 | 01-JAN-08:40 | 7536.64 | 02-APR-16:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.41 | 255.29 | 01-JAN-08:40 | 7536.64 | 02-APR-16:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.41 | 255.29 | 01-JAN-08:40 | 7536.64 | 02-APR-16:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7176.83 | 88838.34 | 06-MAY-16:20 | 368901.20 | 30-APR-03:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7176.83 | 88838.34 | 06-MAY-16:20 | 368901.20 | 30-APR-03:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7176.83 | 88838.34 | 06-MAY-16:20 | 368901.20 | 30-APR-03:10 |
PlantLoopHeatingDemand:Facility | 265.50 | 0.00 | 01-JAN-00:10 | 36118.00 | 06-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 265.45 | 0.00 | 01-JAN-00:10 | 35984.89 | 12-JAN-13:00 |
WaterSystems:PlantLoopHeatingDemand | 265.45 | 0.00 | 01-JAN-00:10 | 35984.89 | 12-JAN-13:00 |
General:WaterSystems:PlantLoopHeatingDemand | 265.45 | 0.00 | 01-JAN-00:10 | 35984.89 | 12-JAN-13:00 |
EnergyTransfer:HVAC | 36759.37 | 136544.25 | 21-JAN-05:50 | 3502969.05 | 10-AUG-16:00 |
HeatingCoils:EnergyTransfer | 0.05 | 0.00 | 01-JAN-00:10 | 2757.38 | 02-JAN-06:50 |
PlantLoopHeatingDemand:HVAC | 0.05 | 0.00 | 01-JAN-00:10 | 2757.38 | 02-JAN-06:50 |
HeatingCoils:PlantLoopHeatingDemand | 0.05 | 0.00 | 01-JAN-00:10 | 2757.38 | 02-JAN-06:50 |
CoolingCoils:EnergyTransfer | 36759.32 | 136544.25 | 21-JAN-05:50 | 3502969.05 | 10-AUG-16:00 |
EnergyTransfer:Plant | 84136.17 | 0.00 | 01-JAN-00:20 | 9342984.87 | 03-AUG-14:10 |
LoopToLoop:EnergyTransfer | 26857.92 | 0.00 | 01-JAN-00:20 | 2977871.01 | 03-AUG-14:10 |
WaterSystems:EnergyTransfer | 265.45 | 0.00 | 01-JAN-00:10 | 35984.89 | 12-JAN-13:00 |
WaterUse:WaterSystems:EnergyTransfer | 265.45 | 0.00 | 01-JAN-00:10 | 35984.89 | 12-JAN-13:00 |
Boilers:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 76.67 | 19-JAN-06:40 |
Chillers:EnergyTransfer | 26590.00 | 0.00 | 01-JAN-00:20 | 2954683.04 | 03-AUG-14:10 |
HeatRejection:EnergyTransfer | 30422.80 | 0.00 | 01-JAN-00:20 | 3405448.61 | 10-AUG-15:30 |
General:HeatRejection:EnergyTransfer | 30422.80 | 0.00 | 01-JAN-00:20 | 3405448.61 | 10-AUG-15:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 5.585 | -728.609 | 0.000 | 0.000 | 92.662 | 116.039 | 424.397 | 0.000 | 0.000 | 0.000 | 89.925 | 0.000 | 0.000 | 0.000 | 0.000 | -0.009 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -747.529 | 0.000 | 0.000 | 83.418 | 104.212 | 289.614 | 0.000 | 0.000 | 0.000 | 270.285 | 0.000 | 0.000 | 0.000 | 0.000 | -0.004 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5697.464 | 0.000 | 0.000 | 835.136 | 1042.115 | 2896.128 | 0.000 | 0.000 | 0.000 | 924.085 | 0.000 | 0.000 | 0.000 | 0.000 | -0.010 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -593.189 | 0.000 | 0.000 | 83.617 | 104.212 | 289.613 | 0.000 | 0.000 | 0.000 | 115.747 | 0.000 | 0.000 | 0.000 | 0.000 | -0.006 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -142.075 | 0.000 | 0.000 | 10.469 | 7.454 | 36.365 | 63.161 | 0.000 | 1.743 | 39.490 | 0.000 | -16.061 | 0.000 | -0.546 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -104.685 | 0.000 | 0.000 | 6.743 | 4.794 | 23.435 | 64.759 | 0.000 | 1.156 | 13.976 | 0.000 | -9.817 | 0.000 | -0.361 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -171.443 | 0.000 | 0.000 | 10.457 | 7.391 | 36.366 | 100.878 | 0.000 | 1.716 | 31.338 | 0.000 | -16.098 | 0.000 | -0.604 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -156.115 | 0.000 | 0.000 | 6.729 | 4.787 | 23.435 | 63.178 | 0.000 | 1.105 | 70.643 | 0.000 | -13.281 | 0.000 | -0.480 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -1242.559 | 0.000 | 0.000 | 105.150 | 74.430 | 363.654 | 646.226 | 0.000 | 40.234 | 171.222 | 0.000 | -146.809 | 0.000 | -11.549 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -996.721 | 0.000 | 0.000 | 49.429 | 47.884 | 234.352 | 644.036 | 0.000 | 26.028 | 100.212 | 0.000 | -96.693 | 0.000 | -8.527 | -0.001 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -1573.889 | 0.000 | 0.000 | 104.666 | 73.850 | 363.660 | 1012.967 | 0.000 | 39.373 | 150.942 | 0.000 | -157.288 | 0.000 | -14.281 | -0.007 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -1084.757 | 0.000 | 0.000 | 67.526 | 47.803 | 234.351 | 652.129 | 0.000 | 25.872 | 176.737 | 0.000 | -110.450 | 0.000 | -9.210 | -0.004 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.001 | -129.096 | 0.000 | 0.000 | 10.555 | 7.443 | 36.365 | 64.046 | 0.000 | 4.875 | 21.353 | 0.000 | -14.181 | 0.000 | -1.361 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -105.539 | 0.000 | 0.000 | 6.762 | 4.788 | 23.435 | 64.252 | 0.000 | 3.184 | 13.497 | 0.000 | -9.375 | 0.000 | -1.006 | -0.001 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -161.084 | 0.000 | 0.000 | 10.486 | 7.385 | 36.366 | 100.582 | 0.000 | 4.781 | 18.495 | 0.000 | -15.301 | 0.000 | -1.709 | -0.001 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -111.236 | 0.000 | 0.000 | 6.770 | 4.780 | 23.435 | 64.748 | 0.000 | 3.150 | 20.208 | 0.000 | -10.749 | 0.000 | -1.106 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -143.047 | 0.000 | 0.000 | 0.934 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -13.443 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1337.604 | 0.000 | 0.000 | 9.372 | 16.758 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -227.332 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.000 | -133.414 | 0.000 | 0.000 | 0.937 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -23.080 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7176.846 | 0.000 | 0.000 | 19.195 | 32.854 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -370.061 |
GROUNDFLOOR_PLENUM | 0.665 | -148.995 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.201 | 146.387 | 0.000 | 0.000 | 0.000 | -1.258 | 0.000 |
MIDFLOOR_PLENUM | 4.479 | -1200.817 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 58.401 | 1159.212 | 0.000 | 0.000 | 0.000 | -21.276 | 0.000 |
TOPFLOOR_PLENUM | 1.814 | -173.971 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.265 | 168.139 | 0.000 | 0.000 | 0.000 | -2.248 | 0.000 |
Total Facility | 6.958 | -1523.783 | 5.586 | -22536.901 | 0.000 | 0.000 | 1521.013 | 1712.328 | 14676.396 | 3540.961 | 0.000 | 221.085 | 3701.895 | 0.000 | -616.103 | 0.000 | -75.520 | -633.958 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 13-FEB-05:12 | 0.00 | 0.00 | 0.00 | -104096.45 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 90040.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 21-FEB-05:11 | 0.00 | 0.00 | 0.00 | -97140.91 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 90665.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 27-NOV-05:11 | 0.00 | 0.00 | 0.00 | -844233.34 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 779483.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-AUG-05:04 | 0.00 | 0.00 | 0.00 | -84953.32 | 0.00 | 0.00 | 800.75 | 537.36 | 7647.36 | 0.00 | 0.00 | 0.00 | 75967.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-JUL-15:51 | 0.00 | 0.00 | 0.00 | -23704.98 | 0.00 | 0.00 | 37.14 | 30.32 | 720.18 | 6156.30 | 0.00 | 389.53 | 16371.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-15:11 | 0.00 | 0.00 | 0.00 | -19801.51 | 0.00 | 0.00 | 23.34 | 19.54 | 464.11 | 4097.50 | 0.00 | 249.91 | 14947.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 05-NOV-12:12 | 0.00 | 0.00 | 0.00 | -26521.40 | 0.00 | 0.00 | 35.25 | 30.33 | 720.19 | 15348.11 | 0.00 | 113.49 | 10274.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-JUL-15:51 | 0.00 | 0.00 | 0.00 | -27991.60 | 0.00 | 0.00 | 18.24 | 19.54 | 464.11 | 8510.25 | 0.00 | 229.79 | 18749.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 03-SEP-16:51 | 0.00 | 0.00 | 0.00 | -237248.74 | 0.00 | 0.00 | 381.68 | 303.25 | 7201.84 | 36085.30 | 0.00 | 9934.35 | 183342.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-SEP-10:11 | 0.00 | 0.00 | 0.00 | -216336.22 | 0.00 | 0.00 | 208.53 | 195.42 | 4641.14 | 82154.34 | 0.00 | 4499.83 | 124636.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-13:31 | 0.00 | 0.00 | 0.00 | -281509.85 | 0.00 | 0.00 | 320.99 | 303.26 | 7201.95 | 127838.21 | 0.00 | 6933.23 | 138912.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 03-SEP-16:51 | 0.00 | 0.00 | 0.00 | -245063.41 | 0.00 | 0.00 | 199.74 | 195.42 | 4641.11 | 61724.12 | 0.00 | 5879.32 | 172423.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 21-MAY-13:12 | 0.00 | 0.00 | 0.00 | -26284.77 | 0.00 | 0.00 | 32.29 | 30.32 | 720.18 | 6036.99 | 0.00 | 4065.19 | 15399.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 21-MAY-13:12 | 0.00 | 0.00 | 0.00 | -21459.68 | 0.00 | 0.00 | 18.97 | 19.54 | 464.11 | 3908.72 | 0.00 | 2682.20 | 14366.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-12:41 | 0.00 | 0.00 | 0.00 | -31083.29 | 0.00 | 0.00 | 31.22 | 30.33 | 720.19 | 13897.61 | 0.00 | 682.43 | 15721.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 06-AUG-15:41 | 0.00 | 0.00 | 0.00 | -25499.83 | 0.00 | 0.00 | 15.81 | 19.54 | 464.11 | 9986.09 | 0.00 | 713.34 | 14300.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 02-APR-16:31 | 0.00 | 0.00 | 0.00 | -7809.27 | 0.00 | 0.00 | 5.28 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 1.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 23-APR-17:46 | 0.00 | 0.00 | 0.00 | -73765.08 | 0.00 | 0.00 | 0.00 | 81.29 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4260.43 |
DATACENTER_TOP_ZN_6 | 02-APR-16:31 | 0.00 | 0.00 | 0.00 | -7540.38 | 0.00 | 0.00 | 5.25 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -267.42 |
DATACENTER_BASEMENT_ZN_6 | 30-APR-03:07 | 0.00 | 0.00 | 0.00 | -369201.75 | 0.00 | 0.00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10590.13 |
GROUNDFLOOR_PLENUM | 07-AUG-05:13 | 0.00 | -23916.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.39 | 23877.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 07-AUG-05:13 | 0.00 | -214563.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 752.20 | 213811.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 16-AUG-13:50 | 0.00 | -27353.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.17 | 26727.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:01 | 0.00 | -149304.11 | 0.00 | -2349545.72 | 0.00 | 0.00 | 14778.24 | 10223.35 | 616289.16 | 30406.85 | 0.00 | 2850.74 | 1824301.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-JUL-11:33 | 0.00 | 0.00 | 34414.97 | 0.00 | 0.00 | 0.00 | 399.40 | 565.21 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -48837.13 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JAN-06:02 | 0.00 | 0.00 | 2275.83 | 0.00 | 0.00 | 0.00 | 140.52 | 67.47 | 960.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2695.53 | 0.00 | -44.51 | -704.03 |
PERIMETER_TOP_ZN_2 | 02-JAN-06:02 | 0.00 | 0.00 | 1138.65 | 0.00 | 0.00 | 0.00 | 90.43 | 43.48 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1815.34 | 0.00 | -29.67 | -46.37 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 18-DEC-05:12 | 11105.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -355.39 | -10749.67 |
MIDFLOOR_PLENUM | 26-MAR-14:52 | 73386.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8411.37 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -81797.93 |
TOPFLOOR_PLENUM | 01-FEB-06:02 | 14314.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -71.63 | -14242.63 |
Total Facility | 21-FEB-05:11 | -1155309.13 | 1237628.51 | 0.00 | -1237628.51 | 0.00 | 0.00 | 0.00 | 10223.35 | 350716.63 | 0.00 | 0.00 | 0.00 | 935298.21 | 0.00 | -111421.72 | 0.00 | -29507.34 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.8967 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.9103 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 106.2744 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 93.7529 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.1059 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.8108 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.2887 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.2887 | 0.2269 | 1.0000 | Not calculated | 1.2002 | 0.2269 | ||
AIRLOOP DATACENTER BASEMENT | 21.3718 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.3720 | 0.0158 | 1.0000 | Not calculated | 0.3384 | 0.0158 | ||
AIRLOOP DATACENTER BOT | 0.4678 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4678 | 0.0334 | 1.0000 | Not calculated | 0.0156 | 0.0334 | ||
AIRLOOP DATACENTER MID | 4.4639 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4639 | 0.0350 | 1.0000 | Not calculated | 0.1563 | 0.0350 | ||
AIRLOOP DATACENTER TOP | 0.4505 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4505 | 0.0347 | 1.0000 | Not calculated | 0.0156 | 0.0347 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.4483 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2840 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 53.1372 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8608 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.5529 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2851 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.2887 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.2887 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2269 | ||
AIRLOOP DATACENTER BASEMENT | 21.3718 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.3718 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0158 | ||
AIRLOOP DATACENTER BOT | 0.4678 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4678 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0334 | ||
AIRLOOP DATACENTER MID | 4.4639 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4639 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0350 | ||
AIRLOOP DATACENTER TOP | 0.4505 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4505 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0347 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.2887 | 5.2887 | 5.2887 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7306 | 5.7306 | 1.6160 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 54.6656 | 54.6656 | 16.1810 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5228 | 5.5228 | 1.6182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2742 | 1.2742 | 0.2026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0672 | 1.0672 | 0.1313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4284 | 1.4284 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3962 | 1.3962 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.0349 | 13.0349 | 2.0334 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.3815 | 11.3815 | 1.3089 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.5551 | 14.5551 | 2.0232 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.6373 | 12.6373 | 1.3143 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4510 | 1.4510 | 0.2031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1763 | 1.1763 | 0.1306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5963 | 1.5963 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3594 | 1.3594 | 0.1305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4678 | 0.4678 | 0.4678 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4639 | 4.4639 | 4.4639 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4505 | 0.4505 | 0.4505 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.3718 | 21.3718 | 21.3718 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.8967 | 9.9103 | 10.8967 | 2.2840 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 106.2744 | 93.7529 | 106.2744 | 22.8608 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.1059 | 10.8108 | 11.1059 | 2.2851 | 0.0000 | 1.0000 |
CAV_BAS | 5.2887 | 5.2887 | 5.2887 | 5.2887 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.3718 | 21.3720 | 21.3718 | 21.3718 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4678 | 0.4678 | 0.4678 | 0.4678 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4639 | 4.4639 | 4.4639 | 4.4639 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4505 | 0.4505 | 0.4505 | 0.4505 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.2887 | 5.2887 | 5.2887 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8653 | 2.8653 | 1.6160 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 27.3328 | 27.3328 | 16.1810 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7614 | 2.7614 | 1.6182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6371 | 0.6371 | 0.2026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5336 | 0.5336 | 0.1313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7142 | 0.7142 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6981 | 0.6981 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.5174 | 6.5174 | 2.0334 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6908 | 5.6908 | 1.3089 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.2776 | 7.2776 | 2.0232 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3187 | 6.3187 | 1.3143 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7255 | 0.7255 | 0.2031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5882 | 0.5882 | 0.1306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7981 | 0.7981 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6797 | 0.6797 | 0.1305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4678 | 0.4678 | 0.4678 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4639 | 4.4639 | 4.4639 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4505 | 0.4505 | 0.4505 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.3718 | 21.3718 | 21.3718 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.4483 | 2.2840 | 2.2840 | 2.2840 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 53.1372 | 22.8608 | 22.8608 | 22.8608 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.5529 | 2.2851 | 2.2851 | 2.2851 | 0.0000 | 1.0000 |
CAV_BAS | 5.2887 | 5.2887 | 5.2887 | 5.2887 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.3718 | 21.3718 | 21.3718 | 21.3718 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4678 | 0.4678 | 0.4678 | 0.4678 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4639 | 4.4639 | 4.4639 | 4.4639 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4505 | 0.4505 | 0.4505 | 0.4505 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1177.33 |
Number of hours not met | 1177.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 0.00 | 92.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 7019.55 | 644365.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1712.33 | 164979.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 263.47 | 31088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.35 | 3369.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1144.44 | 70012.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 4.90 | 315.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2726.13 | 258011.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 903.72 | 54068.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1993.27 | 84672.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 10.96 | 14347.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 574.54 | 69577.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 30509.52 |
Natural Gas | 0.00 | 574.54 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 31084.06 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 559.88 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 36.97 |
Space Heating | 0.00 |
Space Cooling | 151.54 |
Fans (All) | 58.85 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 658.66 |
Subtotal | 658.66 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 12.40 |
Miscellaneous (All) | 12.40 |
Subtotal | 12.40 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.51 |
Space Heating | 0.00 |
Space Cooling | 22.58 |
Fans (All) | 8.77 |
Service Water Heating | 1.85 |
Receptacle Equipment | 47.22 |
Miscellaneous | 14.08 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2069. | 8760. |
LTG_SCH_DATACENTER | 1840. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 900. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7108.00 | 1652.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8695.00 | 65.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8254.83 | 505.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8204.00 | 556.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8086.17 | 673.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6729.50 | 2030.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8203.50 | 556.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7808.67 | 951.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7783.33 | 976.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7403.67 | 1356.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8039.00 | 721.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7702.83 | 1057.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7666.50 | 1093.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7347.67 | 1412.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 5839.50 | 2920.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 5722.33 | 3037.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 5767.83 | 2992.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6720.00 | 1922.50 | 117.50 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8110.50 | 649.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8509.83 | 250.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7749.00 | 1011.00 | 0.00 | 0.00 | 0.00 |
Min | 5722.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 3037.67 | 117.50 | 0.00 | 0.00 |
Average | 7607.46 | 1147.43 | 5.11 | 0.00 | 0.00 |
Sum | 174971.67 | 26390.83 | 117.50 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 364246.83 | 4369.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330711.00 | 102.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1353.50 | 914.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1325.67 | 942.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1330.83 | 937.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 72121.83 | 28233.17 | 3040.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 364246.83 | 28233.17 | 3040.00 | 0.00 | 0.00 |
Average | 78659.33 | 1543.41 | 132.17 | 0.00 | 0.00 |
Sum | 1809164.67 | 35498.33 | 3040.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 3802.00 | 4958.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 6722.50 | 2037.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7420.00 | 1340.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 6999.33 | 1760.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6145.83 | 2614.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6209.50 | 2550.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5798.00 | 2962.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 5354.50 | 3405.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6050.00 | 2710.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 5874.00 | 2886.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 5737.50 | 3022.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 5759.17 | 3000.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6078.67 | 2681.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 5923.83 | 2836.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 5794.00 | 2966.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 5810.00 | 2950.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6875.83 | 1884.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6797.83 | 1962.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6856.17 | 1903.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7536.00 | 1224.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 3448.33 | 5311.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3111.17 | 5648.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3196.67 | 5563.33 | 0.00 | 0.00 | 0.00 |
Min | 3111.17 | 1224.00 | 0.00 | 0.00 | 0.00 |
Max | 7536.00 | 5648.83 | 0.00 | 0.00 | 0.00 |
Average | 5795.69 | 2964.31 | 0.00 | 0.00 | 0.00 |
Sum | 133300.83 | 68179.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 286655.00 | 81961.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 326911.00 | 3902.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 328598.67 | 2214.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 325277.83 | 5535.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38898.33 | 26.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18347.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38922.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24907.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38821.67 | 103.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24883.00 | 26.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38878.50 | 46.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24892.67 | 16.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1664.33 | 603.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1627.00 | 641.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1637.33 | 630.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 85519.33 | 17875.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 328598.67 | 81961.00 | 0.00 | 0.00 | 0.00 |
Average | 75396.09 | 4938.83 | 0.00 | 0.00 | 0.00 |
Sum | 1734110.00 | 113593.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:28
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.578115E+11 | 101139.44 | 02-JAN-05:12 | 13.67 | 11.10 | 0.567059E+10 | 7499.22 | 12-JAN-10:20 | 20.87 | 17.11 |
February | 0.512805E+11 | 104102.18 | 13-FEB-05:12 | 13.00 | 10.82 | 0.514296E+10 | 7499.57 | 15-FEB-14:20 | 25.33 | 18.17 |
March | 0.576486E+11 | 102406.89 | 06-MAR-05:11 | 16.67 | 12.96 | 0.613541E+10 | 7499.56 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.535063E+11 | 98746.84 | 24-APR-04:21 | 22.75 | 14.38 | 0.545190E+10 | 7499.98 | 25-APR-09:39 | 31.00 | 20.82 |
May | 0.571828E+11 | 89870.23 | 10-MAY-04:03 | 29.83 | 16.21 | 0.590337E+10 | 7499.79 | 08-MAY-13:39 | 29.83 | 16.21 |
June | 0.590431E+11 | 81633.35 | 30-JUN-03:02 | 26.88 | 20.77 | 0.588397E+10 | 7499.74 | 02-JUN-13:20 | 26.88 | 20.77 |
July | 0.625109E+11 | 95194.62 | 03-JUL-03:02 | 29.83 | 17.19 | 0.547599E+10 | 7500.17 | 21-JUL-13:09 | 42.25 | 27.34 |
August | 0.746749E+11 | 88885.22 | 06-AUG-10:58 | 40.00 | 24.45 | 0.613925E+10 | 7498.93 | 24-AUG-13:20 | 38.00 | 27.21 |
September | 0.619727E+11 | 85608.02 | 26-SEP-03:02 | 26.18 | 20.93 | 0.545505E+10 | 7499.19 | 26-SEP-13:00 | 39.00 | 23.79 |
October | 0.664109E+11 | 101039.83 | 29-OCT-13:46 | 34.18 | 18.90 | 0.567416E+10 | 7499.31 | 27-OCT-13:09 | 34.18 | 18.90 |
November | 0.645564E+11 | 98863.50 | 05-NOV-11:50 | 33.72 | 17.44 | 0.561783E+10 | 7499.11 | 17-NOV-14:20 | 29.00 | 19.48 |
December | 0.620122E+11 | 101702.37 | 18-DEC-05:12 | 13.00 | 10.66 | 0.547485E+10 | 7499.23 | 01-DEC-14:20 | 13.00 | 10.66 |
Annual Sum or Average | 0.728611E+12 | 0.680253E+11 | ||||||||
Minimum of Months | 0.512805E+11 | 81633.35 | 13.00 | 10.66 | 0.514296E+10 | 7498.93 | 13.00 | 10.66 | ||
Maximum of Months | 0.746749E+11 | 104102.18 | 40.00 | 24.45 | 0.613925E+10 | 7500.17 | 42.25 | 27.34 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.450661E+11 | 96024.33 | 02-JAN-05:12 | 13.67 | 11.10 | 0.507929E+10 | 6734.85 | 09-JAN-10:20 | 16.40 | 15.51 |
February | 0.447972E+11 | 97158.39 | 21-FEB-05:11 | 14.67 | 13.69 | 0.460835E+10 | 6734.92 | 15-FEB-14:09 | 14.67 | 13.69 |
March | 0.593707E+11 | 93657.41 | 06-MAR-05:11 | 16.67 | 12.96 | 0.549863E+10 | 6735.15 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.646188E+11 | 89107.26 | 05-APR-04:13 | 17.07 | 15.11 | 0.487763E+10 | 6735.18 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.638252E+11 | 84745.54 | 01-MAY-05:05 | 20.98 | 20.98 | 0.528171E+10 | 6735.03 | 08-MAY-13:30 | 35.75 | 23.54 |
June | 0.669787E+11 | 84718.29 | 05-JUN-05:03 | 29.00 | 23.92 | 0.526691E+10 | 6734.88 | 02-JUN-13:09 | 29.00 | 23.92 |
July | 0.708205E+11 | 86720.14 | 31-JUL-05:05 | 30.83 | 27.07 | 0.489582E+10 | 6735.17 | 03-JUL-09:09 | 30.83 | 27.07 |
August | 0.828842E+11 | 88513.52 | 07-AUG-05:05 | 32.82 | 23.16 | 0.550289E+10 | 6780.33 | 07-AUG-09:39 | 38.13 | 24.34 |
September | 0.634468E+11 | 84560.77 | 01-SEP-05:05 | 29.75 | 23.78 | 0.487780E+10 | 6734.76 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.659882E+11 | 85706.30 | 10-OCT-05:03 | 26.83 | 24.08 | 0.507310E+10 | 6734.73 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.619079E+11 | 95040.14 | 27-NOV-05:13 | 18.00 | 16.14 | 0.502704E+10 | 6734.77 | 22-NOV-10:20 | 18.00 | 16.14 |
December | 0.578220E+11 | 93894.01 | 18-DEC-05:12 | 13.00 | 10.66 | 0.490115E+10 | 6734.81 | 20-DEC-10:20 | 21.60 | 16.49 |
Annual Sum or Average | 0.747526E+12 | 0.608903E+11 | ||||||||
Minimum of Months | 0.447972E+11 | 84560.77 | 13.00 | 10.66 | 0.460835E+10 | 6734.73 | 14.67 | 13.69 | ||
Maximum of Months | 0.828842E+11 | 97158.39 | 32.82 | 27.07 | 0.550289E+10 | 6780.33 | 38.13 | 27.07 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.338306E+11 | 81097.61 | 02-JAN-06:02 | 13.00 | 10.83 | 0.505735E+10 | 6734.84 | 09-JAN-10:20 | 16.40 | 15.51 |
February | 0.331084E+11 | 82689.96 | 21-FEB-05:11 | 14.67 | 13.69 | 0.459658E+10 | 6734.97 | 15-FEB-14:09 | 14.67 | 13.69 |
March | 0.427869E+11 | 83884.77 | 06-MAR-05:11 | 16.67 | 12.96 | 0.549472E+10 | 6735.16 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.448661E+11 | 83367.08 | 05-APR-04:11 | 17.07 | 15.11 | 0.487753E+10 | 6735.19 | 28-APR-13:39 | 35.57 | 23.16 |
May | 0.546643E+11 | 78219.88 | 04-MAY-04:13 | 23.53 | 18.44 | 0.527826E+10 | 6735.07 | 08-MAY-13:30 | 35.75 | 23.54 |
June | 0.560162E+11 | 65245.88 | 26-JUN-05:02 | 29.00 | 25.21 | 0.526081E+10 | 6734.93 | 02-JUN-13:09 | 29.00 | 25.21 |
July | 0.571688E+11 | 68209.13 | 10-JUL-05:02 | 32.00 | 25.13 | 0.488555E+10 | 6735.20 | 03-JUL-09:09 | 32.00 | 25.13 |
August | 0.610372E+11 | 74170.61 | 07-AUG-05:04 | 32.82 | 23.16 | 0.548850E+10 | 6734.72 | 04-AUG-13:20 | 32.82 | 23.16 |
September | 0.538033E+11 | 74173.71 | 05-SEP-05:03 | 30.17 | 24.66 | 0.487310E+10 | 6734.76 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.515972E+11 | 77375.74 | 21-OCT-04:12 | 22.40 | 15.15 | 0.507107E+10 | 6734.73 | 20-OCT-09:20 | 22.40 | 15.15 |
November | 0.441090E+11 | 84435.26 | 27-NOV-05:11 | 18.00 | 16.14 | 0.502419E+10 | 6734.77 | 22-NOV-10:20 | 18.00 | 16.14 |
December | 0.367572E+11 | 83088.23 | 04-DEC-05:11 | 17.77 | 16.55 | 0.488722E+10 | 6734.81 | 01-DEC-14:20 | 17.77 | 16.55 |
Annual Sum or Average | 0.569745E+12 | 0.607949E+11 | ||||||||
Minimum of Months | 0.331084E+11 | 65245.88 | 13.00 | 10.83 | 0.459658E+10 | 6734.72 | 14.67 | 13.69 | ||
Maximum of Months | 0.610372E+11 | 84435.26 | 32.82 | 25.21 | 0.549472E+10 | 6735.20 | 35.75 | 25.21 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.295710E+11 | 79048.14 | 30-JAN-06:02 | 20.03 | 17.43 | 0.499897E+10 | 6734.80 | 17-JAN-10:20 | 20.03 | 17.43 |
February | 0.306082E+11 | 82719.51 | 08-FEB-05:12 | 22.00 | 18.65 | 0.456691E+10 | 6734.93 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.417563E+11 | 83418.98 | 24-MAR-04:11 | 20.07 | 19.04 | 0.548236E+10 | 6735.16 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.464114E+11 | 83654.06 | 10-APR-04:12 | 21.80 | 19.33 | 0.487814E+10 | 6735.18 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.600169E+11 | 79953.82 | 03-MAY-04:12 | 23.10 | 18.53 | 0.528308E+10 | 6735.03 | 08-MAY-13:30 | 35.75 | 23.54 |
June | 0.624399E+11 | 77506.76 | 19-JUN-05:03 | 28.00 | 25.66 | 0.526543E+10 | 6734.95 | 02-JUN-13:09 | 28.00 | 25.66 |
July | 0.649154E+11 | 83597.62 | 17-JUL-05:05 | 31.00 | 26.53 | 0.489342E+10 | 6735.19 | 03-JUL-09:09 | 31.00 | 26.53 |
August | 0.686213E+11 | 84971.98 | 07-AUG-05:04 | 32.82 | 23.16 | 0.549423E+10 | 6734.67 | 21-AUG-09:20 | 32.67 | 28.09 |
September | 0.587068E+11 | 83754.61 | 05-SEP-05:03 | 30.17 | 24.66 | 0.487773E+10 | 6734.75 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.539738E+11 | 81191.16 | 20-OCT-04:12 | 22.60 | 16.22 | 0.507415E+10 | 6734.73 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.429468E+11 | 84586.75 | 13-NOV-05:12 | 21.00 | 17.39 | 0.502189E+10 | 6734.74 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.332205E+11 | 83716.49 | 11-DEC-05:12 | 22.00 | 18.87 | 0.485498E+10 | 6734.79 | 01-DEC-14:20 | 22.00 | 18.87 |
Annual Sum or Average | 0.593188E+12 | 0.606913E+11 | ||||||||
Minimum of Months | 0.295710E+11 | 77506.76 | 20.03 | 16.22 | 0.456691E+10 | 6734.67 | 20.03 | 17.19 | ||
Maximum of Months | 0.686213E+11 | 84971.98 | 32.82 | 26.53 | 0.549423E+10 | 6735.19 | 35.75 | 28.09 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.469252E+10 | 13702.69 | 30-JAN-06:02 | 20.03 | 17.43 | 0.631645E+09 | 845.63 | 17-JAN-14:20 | 20.03 | 17.43 |
February | 0.544895E+10 | 14667.75 | 09-FEB-05:12 | 23.00 | 19.02 | 0.576211E+09 | 845.66 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.868956E+10 | 18792.81 | 26-MAR-14:52 | 32.60 | 18.60 | 0.689848E+09 | 845.68 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.112325E+11 | 16761.57 | 24-APR-04:21 | 22.75 | 14.38 | 0.613613E+09 | 845.69 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.145606E+11 | 21718.72 | 21-MAY-13:12 | 38.00 | 22.80 | 0.665638E+09 | 845.68 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.164951E+11 | 23234.86 | 11-JUN-15:01 | 36.90 | 27.61 | 0.663659E+09 | 845.64 | 02-JUN-13:09 | 36.90 | 27.61 |
July | 0.180188E+11 | 23711.19 | 04-JUL-15:51 | 38.40 | 27.76 | 0.617843E+09 | 845.70 | 21-JUL-13:09 | 42.25 | 27.34 |
August | 0.201237E+11 | 22688.63 | 06-AUG-15:01 | 40.85 | 24.99 | 0.693335E+09 | 854.24 | 07-AUG-09:39 | 38.13 | 24.34 |
September | 0.141906E+11 | 22293.72 | 10-SEP-16:21 | 34.55 | 29.54 | 0.614774E+09 | 845.63 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.123966E+11 | 19652.71 | 22-OCT-14:32 | 32.00 | 23.06 | 0.638765E+09 | 845.62 | 20-OCT-09:20 | 32.00 | 23.06 |
November | 0.940772E+10 | 17803.47 | 05-NOV-14:52 | 32.00 | 20.75 | 0.631575E+09 | 845.62 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.681812E+10 | 13820.86 | 12-DEC-06:02 | 23.03 | 17.89 | 0.613713E+09 | 845.63 | 01-DEC-14:20 | 23.03 | 17.89 |
Annual Sum or Average | 0.142075E+12 | 0.765062E+10 | ||||||||
Minimum of Months | 0.469252E+10 | 13702.69 | 20.03 | 14.38 | 0.576211E+09 | 845.62 | 20.03 | 17.19 | ||
Maximum of Months | 0.201237E+11 | 23711.19 | 40.85 | 29.54 | 0.693335E+09 | 854.24 | 42.25 | 27.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371845E+10 | 9324.60 | 30-JAN-06:02 | 20.03 | 17.43 | 0.408952E+09 | 544.96 | 24-JAN-10:00 | 20.03 | 17.43 |
February | 0.412945E+10 | 8288.44 | 06-FEB-06:03 | 21.88 | 19.06 | 0.371896E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.630744E+10 | 15934.54 | 26-MAR-14:52 | 32.60 | 18.60 | 0.444565E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.820607E+10 | 18408.53 | 30-APR-11:02 | 34.50 | 21.63 | 0.395539E+09 | 545.01 | 25-APR-09:09 | 34.50 | 21.63 |
May | 0.114306E+11 | 18743.82 | 14-MAY-09:12 | 31.53 | 22.33 | 0.429203E+09 | 545.28 | 22-MAY-09:00 | 36.70 | 22.71 |
June | 0.121268E+11 | 19408.12 | 11-JUN-15:01 | 36.90 | 27.61 | 0.427755E+09 | 544.96 | 02-JUN-13:09 | 36.90 | 27.61 |
July | 0.129182E+11 | 19808.48 | 04-JUL-15:11 | 39.47 | 27.45 | 0.398247E+09 | 545.07 | 31-JUL-09:00 | 39.90 | 23.78 |
August | 0.139543E+11 | 18709.05 | 06-AUG-15:01 | 40.85 | 24.99 | 0.446809E+09 | 551.99 | 07-AUG-09:39 | 38.13 | 24.34 |
September | 0.110204E+11 | 18649.95 | 10-SEP-16:21 | 34.55 | 29.54 | 0.396425E+09 | 545.02 | 05-SEP-09:00 | 34.55 | 29.54 |
October | 0.946481E+10 | 18150.59 | 09-OCT-09:02 | 30.55 | 27.53 | 0.411928E+09 | 544.95 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.682531E+10 | 14732.45 | 05-NOV-14:52 | 32.00 | 20.75 | 0.407298E+09 | 544.95 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.458374E+10 | 5745.99 | 04-DEC-10:10 | 24.67 | 20.70 | 0.395279E+09 | 544.96 | 01-DEC-14:20 | 24.67 | 20.70 |
Annual Sum or Average | 0.104686E+12 | 0.493390E+10 | ||||||||
Minimum of Months | 0.371845E+10 | 5745.99 | 20.03 | 17.43 | 0.371896E+09 | 544.95 | 20.03 | 17.19 | ||
Maximum of Months | 0.139543E+11 | 19808.48 | 40.85 | 29.54 | 0.446809E+09 | 551.99 | 39.90 | 29.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.843548E+10 | 19282.14 | 30-JAN-05:12 | 20.00 | 17.44 | 0.636048E+09 | 845.66 | 24-JAN-10:00 | 20.00 | 17.44 |
February | 0.883209E+10 | 24993.42 | 05-FEB-12:23 | 31.05 | 19.28 | 0.577928E+09 | 845.70 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.115914E+11 | 25222.92 | 26-MAR-14:52 | 32.60 | 18.60 | 0.690654E+09 | 845.90 | 27-MAR-13:00 | 35.00 | 19.40 |
April | 0.126153E+11 | 24155.11 | 30-APR-11:02 | 34.50 | 21.63 | 0.614005E+09 | 845.71 | 25-APR-09:09 | 34.50 | 21.63 |
May | 0.146333E+11 | 24330.67 | 21-MAY-13:12 | 38.00 | 22.80 | 0.665641E+09 | 845.70 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.157115E+11 | 25748.94 | 11-JUN-15:01 | 36.90 | 27.61 | 0.663537E+09 | 845.66 | 02-JUN-13:09 | 36.90 | 27.61 |
July | 0.177262E+11 | 26294.89 | 04-JUL-15:11 | 39.47 | 27.45 | 0.617789E+09 | 845.71 | 03-JUL-09:09 | 39.47 | 27.45 |
August | 0.210930E+11 | 25448.41 | 06-AUG-15:01 | 40.85 | 24.99 | 0.693434E+09 | 854.29 | 07-AUG-09:39 | 38.13 | 24.34 |
September | 0.172984E+11 | 26014.88 | 10-SEP-13:42 | 35.07 | 29.55 | 0.615262E+09 | 846.01 | 28-SEP-13:50 | 35.10 | 25.53 |
October | 0.175377E+11 | 25926.74 | 22-OCT-14:32 | 32.00 | 23.06 | 0.639813E+09 | 846.18 | 20-OCT-13:00 | 32.00 | 23.06 |
November | 0.147997E+11 | 26522.38 | 05-NOV-12:12 | 33.80 | 18.48 | 0.633086E+09 | 846.27 | 13-NOV-14:09 | 33.00 | 16.45 |
December | 0.111693E+11 | 26170.58 | 03-DEC-12:52 | 29.80 | 17.63 | 0.615783E+09 | 845.71 | 04-DEC-14:09 | 27.00 | 21.00 |
Annual Sum or Average | 0.171443E+12 | 0.766298E+10 | ||||||||
Minimum of Months | 0.843548E+10 | 19282.14 | 20.00 | 17.44 | 0.577928E+09 | 845.66 | 20.00 | 16.45 | ||
Maximum of Months | 0.210930E+11 | 26522.38 | 40.85 | 29.55 | 0.693434E+09 | 854.29 | 39.47 | 27.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.521438E+10 | 18391.63 | 30-JAN-05:12 | 20.00 | 17.44 | 0.410991E+09 | 544.96 | 17-JAN-14:20 | 20.00 | 17.44 |
February | 0.667948E+10 | 20390.53 | 27-FEB-05:12 | 18.00 | 16.52 | 0.373688E+09 | 544.99 | 15-FEB-14:09 | 18.00 | 16.52 |
March | 0.108468E+11 | 25143.01 | 26-MAR-14:52 | 32.60 | 18.60 | 0.446331E+09 | 545.00 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.140980E+11 | 24621.73 | 23-APR-16:22 | 31.75 | 18.84 | 0.396838E+09 | 545.01 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.137035E+11 | 24455.53 | 14-MAY-17:52 | 33.00 | 21.47 | 0.429608E+09 | 545.00 | 04-MAY-13:00 | 33.00 | 21.47 |
June | 0.161047E+11 | 27017.70 | 11-JUN-15:01 | 36.90 | 27.61 | 0.428178E+09 | 544.97 | 02-JUN-13:09 | 36.90 | 27.61 |
July | 0.182716E+11 | 28003.13 | 04-JUL-15:51 | 38.40 | 27.76 | 0.398709E+09 | 545.00 | 03-JUL-09:09 | 38.40 | 27.76 |
August | 0.239525E+11 | 26770.34 | 06-AUG-15:41 | 40.25 | 25.55 | 0.447569E+09 | 552.47 | 07-AUG-09:39 | 38.13 | 24.34 |
September | 0.135988E+11 | 25809.81 | 10-SEP-16:21 | 34.55 | 29.54 | 0.396826E+09 | 544.95 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.130538E+11 | 24953.49 | 22-OCT-14:32 | 32.00 | 23.06 | 0.412679E+09 | 544.95 | 20-OCT-09:20 | 32.00 | 23.06 |
November | 0.110969E+11 | 25282.40 | 05-NOV-15:32 | 31.60 | 21.44 | 0.408553E+09 | 544.96 | 16-NOV-14:30 | 30.50 | 19.19 |
December | 0.949387E+10 | 23754.03 | 03-DEC-14:12 | 27.00 | 20.88 | 0.398089E+09 | 544.96 | 01-DEC-14:09 | 27.00 | 20.88 |
Annual Sum or Average | 0.156114E+12 | 0.494806E+10 | ||||||||
Minimum of Months | 0.521438E+10 | 18391.63 | 18.00 | 16.52 | 0.373688E+09 | 544.95 | 18.00 | 16.52 | ||
Maximum of Months | 0.239525E+11 | 28003.13 | 40.25 | 29.54 | 0.447569E+09 | 552.47 | 38.40 | 27.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333861E+10 | 5025.98 | 23-JAN-14:10 | 27.50 | 16.66 | 0.612075E+09 | 845.63 | 17-JAN-14:20 | 27.50 | 16.66 |
February | 0.392361E+10 | 10306.06 | 09-FEB-06:03 | 22.92 | 19.06 | 0.565822E+09 | 845.66 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.647768E+10 | 16046.75 | 26-MAR-14:52 | 32.60 | 18.60 | 0.685730E+09 | 845.68 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.872458E+10 | 17750.13 | 23-APR-15:31 | 32.33 | 18.32 | 0.613292E+09 | 845.69 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.142419E+11 | 23075.50 | 21-MAY-13:12 | 38.00 | 22.80 | 0.665921E+09 | 845.68 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.160051E+11 | 22384.54 | 11-JUN-15:12 | 36.80 | 27.45 | 0.663733E+09 | 845.64 | 02-JUN-13:09 | 36.80 | 27.45 |
July | 0.173043E+11 | 23091.14 | 30-JUL-14:22 | 42.50 | 25.87 | 0.617821E+09 | 846.75 | 21-JUL-13:20 | 42.50 | 25.87 |
August | 0.180998E+11 | 22969.61 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692560E+09 | 846.84 | 04-AUG-13:20 | 40.85 | 24.99 |
September | 0.139268E+11 | 23726.29 | 03-SEP-16:51 | 36.70 | 26.63 | 0.614997E+09 | 845.63 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.109645E+11 | 23051.56 | 09-OCT-14:51 | 37.00 | 20.70 | 0.639075E+09 | 845.62 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.708756E+10 | 14233.36 | 20-NOV-06:02 | 25.85 | 18.49 | 0.630589E+09 | 845.62 | 16-NOV-14:20 | 25.85 | 18.49 |
December | 0.416219E+10 | 11328.71 | 12-DEC-06:02 | 23.03 | 17.89 | 0.602783E+09 | 845.63 | 01-DEC-14:20 | 23.03 | 17.89 |
Annual Sum or Average | 0.124257E+12 | 0.760440E+10 | ||||||||
Minimum of Months | 0.333861E+10 | 5025.98 | 22.92 | 16.66 | 0.565822E+09 | 845.62 | 23.03 | 16.66 | ||
Maximum of Months | 0.180998E+11 | 23726.29 | 42.50 | 27.45 | 0.692560E+09 | 846.84 | 42.50 | 27.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267922E+10 | 6230.59 | 24-JAN-11:05 | 24.00 | 18.08 | 0.297896E+09 | 548.51 | 24-JAN-11:09 | 24.00 | 18.08 |
February | 0.324334E+10 | 11466.08 | 05-FEB-14:52 | 32.00 | 19.39 | 0.272685E+09 | 548.51 | 16-FEB-15:09 | 24.78 | 18.41 |
March | 0.535591E+10 | 18955.03 | 26-MAR-14:52 | 32.60 | 18.60 | 0.327009E+09 | 548.54 | 28-MAR-10:09 | 27.17 | 20.40 |
April | 0.749866E+10 | 20228.74 | 23-APR-10:12 | 32.80 | 16.75 | 0.292792E+09 | 548.53 | 28-APR-14:09 | 35.00 | 23.22 |
May | 0.116222E+11 | 20235.10 | 28-MAY-09:32 | 32.53 | 25.25 | 0.317474E+09 | 548.56 | 11-MAY-12:09 | 32.53 | 25.25 |
June | 0.123544E+11 | 19633.35 | 11-JUN-09:52 | 38.00 | 26.72 | 0.315921E+09 | 548.52 | 02-JUN-12:09 | 38.00 | 26.72 |
July | 0.132450E+11 | 20393.33 | 30-JUL-09:42 | 41.80 | 21.60 | 0.295180E+09 | 548.49 | 03-JUL-10:09 | 41.80 | 21.60 |
August | 0.142093E+11 | 19998.99 | 06-AUG-15:01 | 40.85 | 24.99 | 0.329638E+09 | 548.49 | 24-AUG-12:09 | 37.25 | 26.69 |
September | 0.112728E+11 | 21645.37 | 04-SEP-10:11 | 38.00 | 23.07 | 0.293444E+09 | 548.49 | 26-SEP-14:09 | 39.00 | 24.02 |
October | 0.909372E+10 | 20355.19 | 09-OCT-14:51 | 37.00 | 20.70 | 0.305273E+09 | 548.50 | 10-OCT-14:09 | 34.58 | 20.06 |
November | 0.585863E+10 | 14053.38 | 05-NOV-10:32 | 31.33 | 19.23 | 0.301373E+09 | 548.49 | 06-NOV-15:09 | 31.90 | 21.82 |
December | 0.323949E+10 | 7642.41 | 12-DEC-06:02 | 23.03 | 17.89 | 0.290126E+09 | 548.50 | 01-DEC-13:09 | 23.03 | 17.89 |
Annual Sum or Average | 0.996726E+11 | 0.363881E+10 | ||||||||
Minimum of Months | 0.267922E+10 | 6230.59 | 23.03 | 16.75 | 0.272685E+09 | 548.49 | 23.03 | 17.89 | ||
Maximum of Months | 0.142093E+11 | 21645.37 | 41.80 | 26.72 | 0.329638E+09 | 548.56 | 41.80 | 26.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.740944E+10 | 17122.49 | 30-JAN-06:02 | 20.03 | 17.43 | 0.632213E+09 | 845.66 | 24-JAN-10:00 | 20.03 | 17.43 |
February | 0.769431E+10 | 26560.00 | 05-FEB-13:32 | 31.43 | 19.44 | 0.575115E+09 | 845.71 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.979011E+10 | 25828.85 | 26-MAR-13:32 | 33.67 | 18.36 | 0.689125E+09 | 846.80 | 27-MAR-13:20 | 35.67 | 19.65 |
April | 0.103300E+11 | 24209.22 | 23-APR-15:31 | 32.33 | 18.32 | 0.614011E+09 | 845.71 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.142955E+11 | 25708.17 | 21-MAY-13:12 | 38.00 | 22.80 | 0.665921E+09 | 845.71 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.151958E+11 | 24663.89 | 11-JUN-15:12 | 36.80 | 27.45 | 0.663601E+09 | 845.66 | 02-JUN-13:09 | 36.80 | 27.45 |
July | 0.170370E+11 | 25786.62 | 30-JUL-14:22 | 42.50 | 25.87 | 0.617775E+09 | 845.72 | 03-JUL-09:09 | 42.50 | 25.87 |
August | 0.193541E+11 | 25689.22 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692718E+09 | 846.94 | 16-AUG-13:20 | 44.13 | 25.65 |
September | 0.174123E+11 | 27091.81 | 03-SEP-16:51 | 36.70 | 26.63 | 0.615528E+09 | 846.84 | 01-SEP-13:20 | 36.70 | 26.63 |
October | 0.167981E+11 | 28153.27 | 09-OCT-13:31 | 37.20 | 20.23 | 0.640348E+09 | 846.74 | 16-OCT-13:20 | 32.93 | 25.16 |
November | 0.131694E+11 | 26717.40 | 12-NOV-13:22 | 29.65 | 18.98 | 0.633209E+09 | 846.70 | 03-NOV-13:20 | 29.65 | 18.98 |
December | 0.890385E+10 | 25385.95 | 25-DEC-14:53 | 27.00 | 16.24 | 0.613609E+09 | 845.66 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.157390E+12 | 0.765317E+10 | ||||||||
Minimum of Months | 0.740944E+10 | 17122.49 | 20.03 | 16.24 | 0.575115E+09 | 845.66 | 20.03 | 17.31 | ||
Maximum of Months | 0.193541E+11 | 28153.27 | 42.50 | 27.45 | 0.692718E+09 | 846.94 | 44.13 | 27.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308141E+10 | 9069.63 | 30-JAN-06:02 | 20.03 | 17.43 | 0.401570E+09 | 544.96 | 17-JAN-14:20 | 20.03 | 17.43 |
February | 0.381421E+10 | 19122.42 | 05-FEB-15:32 | 32.00 | 19.08 | 0.368937E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.630980E+10 | 21985.03 | 26-MAR-14:52 | 32.60 | 18.60 | 0.444451E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.810064E+10 | 21977.28 | 23-APR-16:11 | 32.00 | 18.66 | 0.396247E+09 | 545.00 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.120304E+11 | 23541.98 | 28-MAY-16:51 | 35.00 | 23.19 | 0.429568E+09 | 545.00 | 04-MAY-13:00 | 35.00 | 23.19 |
June | 0.132035E+11 | 22253.56 | 18-JUN-16:02 | 35.98 | 27.42 | 0.428051E+09 | 544.96 | 02-JUN-13:09 | 35.98 | 27.42 |
July | 0.141387E+11 | 22797.09 | 30-JUL-15:02 | 40.45 | 27.73 | 0.398457E+09 | 545.01 | 03-JUL-09:09 | 40.45 | 27.73 |
August | 0.154665E+11 | 23119.44 | 06-AUG-15:01 | 40.85 | 24.99 | 0.446659E+09 | 544.95 | 04-AUG-13:20 | 40.85 | 24.99 |
September | 0.119803E+11 | 24511.51 | 03-SEP-16:51 | 36.70 | 26.63 | 0.396779E+09 | 544.95 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.975720E+10 | 23885.91 | 09-OCT-15:31 | 36.87 | 19.42 | 0.412513E+09 | 544.95 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.658969E+10 | 18760.19 | 19-NOV-14:32 | 30.33 | 18.36 | 0.407535E+09 | 544.95 | 16-NOV-14:20 | 30.33 | 18.36 |
December | 0.400391E+10 | 10931.91 | 12-DEC-06:02 | 23.03 | 17.89 | 0.393428E+09 | 544.96 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.108476E+12 | 0.492419E+10 | ||||||||
Minimum of Months | 0.308141E+10 | 9069.63 | 20.03 | 17.43 | 0.368937E+09 | 544.95 | 20.03 | 17.31 | ||
Maximum of Months | 0.154665E+11 | 24511.51 | 40.85 | 27.73 | 0.446659E+09 | 545.01 | 40.85 | 27.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304011E+10 | 5231.47 | 23-JAN-14:10 | 27.50 | 16.66 | 0.595813E+09 | 845.63 | 17-JAN-14:20 | 27.50 | 16.66 |
February | 0.374490E+10 | 10343.72 | 06-FEB-06:03 | 21.88 | 19.06 | 0.556673E+09 | 845.66 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.642008E+10 | 17879.02 | 28-MAR-05:02 | 25.67 | 14.74 | 0.681451E+09 | 845.68 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.896399E+10 | 24367.57 | 30-APR-16:11 | 31.33 | 25.55 | 0.612567E+09 | 845.69 | 25-APR-09:09 | 31.33 | 25.55 |
May | 0.150487E+11 | 26291.72 | 21-MAY-13:12 | 38.00 | 22.80 | 0.666027E+09 | 845.68 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.170168E+11 | 25324.60 | 11-JUN-15:12 | 36.80 | 27.45 | 0.663838E+09 | 845.65 | 02-JUN-13:09 | 36.80 | 27.45 |
July | 0.186166E+11 | 26247.00 | 30-JUL-14:22 | 42.50 | 25.87 | 0.618004E+09 | 845.75 | 21-JUL-13:39 | 42.50 | 25.87 |
August | 0.193380E+11 | 26166.06 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692713E+09 | 845.86 | 16-AUG-13:00 | 44.00 | 25.56 |
September | 0.146910E+11 | 25666.96 | 04-SEP-15:02 | 40.95 | 24.20 | 0.615109E+09 | 845.63 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.113471E+11 | 25627.89 | 09-OCT-12:41 | 37.67 | 19.87 | 0.639159E+09 | 845.63 | 11-OCT-13:39 | 35.37 | 21.08 |
November | 0.699937E+10 | 22457.13 | 05-NOV-15:02 | 31.90 | 20.93 | 0.629467E+09 | 845.62 | 16-NOV-14:20 | 30.67 | 19.24 |
December | 0.387024E+10 | 9344.02 | 11-DEC-06:03 | 21.90 | 19.23 | 0.593713E+09 | 845.63 | 01-DEC-14:20 | 21.90 | 19.23 |
Annual Sum or Average | 0.129097E+12 | 0.756454E+10 | ||||||||
Minimum of Months | 0.304011E+10 | 5231.47 | 21.88 | 14.74 | 0.556673E+09 | 845.62 | 21.90 | 16.66 | ||
Maximum of Months | 0.193380E+11 | 26291.72 | 42.50 | 27.45 | 0.692713E+09 | 845.86 | 44.00 | 27.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261108E+10 | 5279.03 | 30-JAN-06:02 | 20.03 | 17.43 | 0.399752E+09 | 544.97 | 24-JAN-10:00 | 20.03 | 17.43 |
February | 0.327507E+10 | 13317.71 | 05-FEB-15:22 | 32.00 | 19.15 | 0.367312E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.553116E+10 | 14177.58 | 27-MAR-04:12 | 22.43 | 13.90 | 0.442684E+09 | 545.00 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.787449E+10 | 20898.28 | 30-APR-10:52 | 34.00 | 21.75 | 0.395770E+09 | 545.02 | 25-APR-09:09 | 34.00 | 21.75 |
May | 0.124122E+11 | 21466.77 | 21-MAY-13:12 | 38.00 | 22.80 | 0.429525E+09 | 544.99 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.132955E+11 | 20471.58 | 11-JUN-09:52 | 38.00 | 26.72 | 0.427973E+09 | 544.97 | 02-JUN-13:09 | 38.00 | 26.72 |
July | 0.143839E+11 | 21409.21 | 30-JUL-14:22 | 42.50 | 25.87 | 0.398492E+09 | 545.05 | 31-JUL-09:00 | 39.90 | 23.78 |
August | 0.153218E+11 | 21230.23 | 06-AUG-15:01 | 40.85 | 24.99 | 0.446612E+09 | 545.14 | 03-AUG-09:50 | 40.85 | 24.99 |
September | 0.120166E+11 | 20997.06 | 17-SEP-09:42 | 33.75 | 23.36 | 0.396703E+09 | 544.96 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.958584E+10 | 21257.98 | 09-OCT-12:41 | 37.67 | 19.87 | 0.412399E+09 | 544.96 | 11-OCT-13:39 | 35.37 | 21.08 |
November | 0.602347E+10 | 19831.46 | 05-NOV-15:02 | 31.90 | 20.93 | 0.407160E+09 | 544.95 | 16-NOV-14:20 | 30.67 | 19.24 |
December | 0.320823E+10 | 7194.85 | 11-DEC-06:03 | 21.90 | 19.23 | 0.390566E+09 | 544.96 | 01-DEC-14:09 | 21.90 | 19.23 |
Annual Sum or Average | 0.105539E+12 | 0.491495E+10 | ||||||||
Minimum of Months | 0.261108E+10 | 5279.03 | 20.03 | 13.90 | 0.367312E+09 | 544.95 | 20.03 | 17.43 | ||
Maximum of Months | 0.153218E+11 | 21466.77 | 42.50 | 26.72 | 0.446612E+09 | 545.14 | 40.85 | 26.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.675134E+10 | 17554.60 | 30-JAN-06:02 | 20.03 | 17.43 | 0.624424E+09 | 845.67 | 24-JAN-10:00 | 20.03 | 17.43 |
February | 0.730617E+10 | 29040.37 | 05-FEB-14:02 | 31.67 | 19.34 | 0.570404E+09 | 845.71 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.961174E+10 | 27557.32 | 26-MAR-12:23 | 34.50 | 17.70 | 0.686478E+09 | 845.71 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.105441E+11 | 27698.55 | 30-APR-12:12 | 37.03 | 20.80 | 0.613358E+09 | 845.72 | 25-APR-09:09 | 37.03 | 20.80 |
May | 0.150991E+11 | 28862.94 | 21-MAY-13:12 | 38.00 | 22.80 | 0.666023E+09 | 845.70 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.161996E+11 | 27512.71 | 11-JUN-15:12 | 36.80 | 27.45 | 0.663732E+09 | 845.67 | 02-JUN-13:09 | 36.80 | 27.45 |
July | 0.183498E+11 | 28884.30 | 30-JUL-14:22 | 42.50 | 25.87 | 0.617971E+09 | 845.71 | 03-JUL-09:09 | 42.50 | 25.87 |
August | 0.205989E+11 | 28871.69 | 13-AUG-14:21 | 40.00 | 25.61 | 0.692849E+09 | 845.75 | 16-AUG-13:50 | 44.03 | 25.58 |
September | 0.181710E+11 | 29101.07 | 04-SEP-14:22 | 41.00 | 24.70 | 0.615565E+09 | 845.97 | 28-SEP-13:50 | 35.10 | 25.53 |
October | 0.171267E+11 | 31081.45 | 09-OCT-12:41 | 37.67 | 19.87 | 0.640316E+09 | 846.07 | 10-OCT-13:00 | 34.50 | 20.13 |
November | 0.130249E+11 | 30099.24 | 05-NOV-12:22 | 33.70 | 19.11 | 0.632764E+09 | 845.67 | 06-NOV-14:09 | 32.83 | 20.61 |
December | 0.830211E+10 | 29055.55 | 03-DEC-13:02 | 29.33 | 18.32 | 0.610049E+09 | 845.66 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.161085E+12 | 0.763393E+10 | ||||||||
Minimum of Months | 0.675134E+10 | 17554.60 | 20.03 | 17.43 | 0.570404E+09 | 845.66 | 20.03 | 17.31 | ||
Maximum of Months | 0.205989E+11 | 31081.45 | 42.50 | 27.45 | 0.692849E+09 | 846.07 | 44.03 | 27.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286078E+10 | 9294.26 | 30-JAN-06:02 | 20.03 | 17.43 | 0.393604E+09 | 544.96 | 17-JAN-14:20 | 20.03 | 17.43 |
February | 0.365847E+10 | 20527.41 | 05-FEB-15:22 | 32.00 | 19.15 | 0.364794E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.621377E+10 | 18885.09 | 27-MAR-04:12 | 22.43 | 13.90 | 0.442973E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.821259E+10 | 23602.03 | 30-APR-16:11 | 31.33 | 25.55 | 0.396028E+09 | 545.00 | 25-APR-09:09 | 31.33 | 25.55 |
May | 0.125162E+11 | 24407.58 | 21-MAY-15:52 | 37.50 | 23.27 | 0.429602E+09 | 544.99 | 04-MAY-13:00 | 37.50 | 23.27 |
June | 0.138378E+11 | 24207.31 | 18-JUN-16:02 | 35.98 | 27.42 | 0.428077E+09 | 544.97 | 02-JUN-13:09 | 35.98 | 27.42 |
July | 0.149831E+11 | 24965.51 | 30-JUL-15:02 | 40.45 | 27.73 | 0.398533E+09 | 545.00 | 03-JUL-09:09 | 40.45 | 27.73 |
August | 0.162658E+11 | 25509.31 | 06-AUG-15:41 | 40.25 | 25.55 | 0.446712E+09 | 544.94 | 15-AUG-13:20 | 39.87 | 23.44 |
September | 0.124437E+11 | 24900.80 | 04-SEP-15:42 | 40.75 | 24.06 | 0.396794E+09 | 544.95 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.997626E+10 | 25501.85 | 01-OCT-15:41 | 33.75 | 26.68 | 0.412515E+09 | 544.96 | 11-OCT-13:39 | 35.37 | 21.08 |
November | 0.651639E+10 | 23961.05 | 05-NOV-15:02 | 31.90 | 20.93 | 0.407199E+09 | 544.95 | 16-NOV-14:20 | 30.67 | 19.24 |
December | 0.375192E+10 | 9997.30 | 11-DEC-06:03 | 21.90 | 19.23 | 0.389801E+09 | 544.96 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.111237E+12 | 0.490663E+10 | ||||||||
Minimum of Months | 0.286078E+10 | 9294.26 | 20.03 | 13.90 | 0.364794E+09 | 544.94 | 20.03 | 17.31 | ||
Maximum of Months | 0.162658E+11 | 25509.31 | 40.75 | 27.73 | 0.446712E+09 | 545.00 | 40.45 | 27.73 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.446241E+10 | 8859.21 | 30-JAN-06:15 | 20.07 | 17.42 | 0.00 | 0.00 | 01-JAN-00:10 | 20.07 | 17.42 |
February | 0.539961E+10 | 10228.45 | 06-FEB-06:03 | 21.88 | 19.06 | 0.00 | 0.00 | 01-FEB-00:10 | 21.88 | 19.06 |
March | 0.839485E+10 | 12592.14 | 27-MAR-05:15 | 21.93 | 13.41 | 0.00 | 0.00 | 01-MAR-00:10 | 21.93 | 13.41 |
April | 0.107539E+11 | 14821.81 | 24-APR-05:15 | 21.67 | 13.88 | 0.00 | 0.00 | 01-APR-00:10 | 21.67 | 13.88 |
May | 0.147870E+11 | 19038.92 | 30-MAY-05:15 | 27.00 | 24.83 | 0.00 | 0.00 | 01-MAY-00:10 | 27.00 | 24.83 |
June | 0.168054E+11 | 20467.83 | 12-JUN-05:15 | 29.13 | 24.04 | 0.00 | 0.00 | 01-JUN-00:10 | 29.13 | 24.04 |
July | 0.192988E+11 | 22083.26 | 24-JUL-05:15 | 32.67 | 27.85 | 0.00 | 0.00 | 01-JUL-00:10 | 32.67 | 27.85 |
August | 0.227877E+11 | 23919.31 | 07-AUG-05:13 | 32.63 | 23.12 | 0.00 | 0.00 | 01-AUG-00:10 | 32.63 | 23.12 |
September | 0.157268E+11 | 23085.54 | 05-SEP-05:15 | 30.33 | 24.49 | 0.00 | 0.00 | 01-SEP-00:10 | 30.33 | 24.49 |
October | 0.137381E+11 | 17810.79 | 10-OCT-05:25 | 26.50 | 24.00 | 0.00 | 0.00 | 01-OCT-00:10 | 26.50 | 24.00 |
November | 0.101005E+11 | 13839.17 | 13-NOV-06:15 | 20.83 | 17.71 | 0.00 | 0.00 | 01-NOV-00:10 | 20.83 | 17.71 |
December | 0.673976E+10 | 10343.44 | 11-DEC-06:13 | 21.80 | 19.16 | 0.00 | 0.00 | 01-DEC-00:10 | 21.80 | 19.16 |
Annual Sum or Average | 0.148995E+12 | 0.00 | ||||||||
Minimum of Months | 0.446241E+10 | 8859.21 | 20.07 | 13.41 | 0.00 | 0.00 | 20.07 | 13.41 | ||
Maximum of Months | 0.227877E+11 | 23919.31 | 32.67 | 27.85 | 0.00 | 0.00 | 32.67 | 27.85 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233192E+10 | 3716.05 | 30-JAN-06:15 | 20.07 | 17.42 | 0.00 | 0.00 | 01-JAN-00:10 | 20.07 | 17.42 |
February | 0.324148E+10 | 6335.25 | 06-FEB-15:30 | 31.95 | 17.43 | 0.00 | 0.00 | 01-FEB-00:10 | 31.95 | 17.43 |
March | 0.583101E+10 | 9348.26 | 27-MAR-16:00 | 35.00 | 18.85 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 18.85 |
April | 0.804448E+10 | 10365.48 | 24-APR-05:02 | 21.83 | 13.96 | 0.00 | 0.00 | 01-APR-00:10 | 21.83 | 13.96 |
May | 0.132905E+11 | 12875.15 | 30-MAY-05:03 | 27.00 | 24.83 | 0.00 | 0.00 | 01-MAY-00:10 | 27.00 | 24.83 |
June | 0.148950E+11 | 14181.69 | 09-JUN-05:03 | 32.00 | 26.79 | 0.00 | 0.00 | 01-JUN-00:10 | 32.00 | 26.79 |
July | 0.168527E+11 | 18493.94 | 17-JUL-05:15 | 31.00 | 26.67 | 0.00 | 0.00 | 01-JUL-00:10 | 31.00 | 26.67 |
August | 0.185332E+11 | 21458.83 | 07-AUG-05:13 | 32.63 | 23.12 | 0.00 | 0.00 | 01-AUG-00:10 | 32.63 | 23.12 |
September | 0.140899E+11 | 20036.36 | 05-SEP-05:15 | 30.33 | 24.49 | 0.00 | 0.00 | 01-SEP-00:10 | 30.33 | 24.49 |
October | 0.115552E+11 | 14319.53 | 10-OCT-05:02 | 26.83 | 24.08 | 0.00 | 0.00 | 01-OCT-00:10 | 26.83 | 24.08 |
November | 0.764427E+10 | 10224.13 | 06-NOV-06:02 | 20.02 | 17.47 | 0.00 | 0.00 | 01-NOV-00:10 | 20.02 | 17.47 |
December | 0.377239E+10 | 7119.10 | 11-DEC-06:13 | 21.80 | 19.16 | 0.00 | 0.00 | 01-DEC-00:10 | 21.80 | 19.16 |
Annual Sum or Average | 0.120082E+12 | 0.00 | ||||||||
Minimum of Months | 0.233192E+10 | 3716.05 | 20.02 | 13.96 | 0.00 | 0.00 | 20.02 | 13.96 | ||
Maximum of Months | 0.185332E+11 | 21458.83 | 35.00 | 26.79 | 0.00 | 0.00 | 35.00 | 26.79 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281959E+10 | 7903.56 | 23-JAN-14:10 | 27.50 | 16.66 | 0.00 | 0.00 | 01-JAN-00:10 | 27.50 | 16.66 |
February | 0.436955E+10 | 13158.22 | 06-FEB-15:00 | 32.50 | 17.28 | 0.00 | 0.00 | 01-FEB-00:10 | 32.50 | 17.28 |
March | 0.812920E+10 | 18765.54 | 27-MAR-14:30 | 35.00 | 19.13 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 19.13 |
April | 0.118786E+11 | 20935.77 | 28-APR-13:05 | 36.42 | 23.03 | 0.00 | 0.00 | 01-APR-00:10 | 36.42 | 23.03 |
May | 0.203501E+11 | 23611.83 | 10-MAY-14:40 | 40.00 | 20.07 | 0.00 | 0.00 | 01-MAY-00:10 | 40.00 | 20.07 |
June | 0.229620E+11 | 24692.12 | 09-JUN-15:00 | 42.00 | 24.89 | 0.00 | 0.00 | 01-JUN-00:10 | 42.00 | 24.89 |
July | 0.262366E+11 | 26997.24 | 21-JUL-13:05 | 42.25 | 27.34 | 0.00 | 0.00 | 01-JUL-00:10 | 42.25 | 27.34 |
August | 0.280496E+11 | 27354.24 | 16-AUG-13:50 | 44.03 | 25.58 | 0.00 | 0.00 | 01-AUG-00:10 | 44.03 | 25.58 |
September | 0.205354E+11 | 24691.65 | 05-SEP-14:20 | 39.67 | 25.10 | 0.00 | 0.00 | 01-SEP-00:10 | 39.67 | 25.10 |
October | 0.154055E+11 | 19481.68 | 05-OCT-14:40 | 36.00 | 22.65 | 0.00 | 0.00 | 01-OCT-00:10 | 36.00 | 22.65 |
November | 0.908314E+10 | 15335.18 | 01-NOV-14:00 | 33.00 | 26.24 | 0.00 | 0.00 | 01-NOV-00:10 | 33.00 | 26.24 |
December | 0.415228E+10 | 10395.44 | 04-DEC-14:05 | 27.00 | 21.00 | 0.00 | 0.00 | 01-DEC-00:10 | 27.00 | 21.00 |
Annual Sum or Average | 0.173971E+12 | 0.00 | ||||||||
Minimum of Months | 0.281959E+10 | 7903.56 | 27.00 | 16.66 | 0.00 | 0.00 | 27.00 | 16.66 | ||
Maximum of Months | 0.280496E+11 | 27354.24 | 44.03 | 27.34 | 0.00 | 0.00 | 44.03 | 27.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.416874E+10 | 1886.41 | 29-JAN-17:35 | 24.33 | 19.64 | 95237203.21 | 126.85 | 17-JAN-14:00 | 24.33 | 19.64 |
February | 0.849036E+10 | 3828.57 | 05-FEB-17:17 | 31.00 | 18.60 | 86408389.88 | 126.85 | 09-FEB-10:09 | 23.92 | 19.44 |
March | 0.145362E+11 | 7194.04 | 31-MAR-24:00 | 22.30 | 20.22 | 0.103244E+09 | 126.85 | 02-MAR-14:09 | 22.30 | 20.22 |
April | 0.190862E+11 | 7809.23 | 02-APR-16:31 | 30.13 | 18.26 | 92425130.17 | 143.50 | 26-APR-13:09 | 37.33 | 19.85 |
May | 0.471681E+10 | 3580.63 | 31-MAY-23:57 | 32.70 | 23.39 | 99238368.43 | 126.85 | 15-MAY-09:00 | 32.70 | 23.39 |
June | 0.950946E+10 | 5416.55 | 30-JUN-23:55 | 31.70 | 26.86 | 98978761.55 | 126.88 | 20-JUN-09:09 | 31.70 | 26.86 |
July | 0.150138E+11 | 7205.06 | 31-JUL-23:57 | 33.30 | 28.31 | 91890771.59 | 126.85 | 26-JUL-09:09 | 33.30 | 28.31 |
August | 0.193881E+11 | 7625.44 | 14-AUG-03:20 | 31.00 | 24.35 | 0.118371E+09 | 157.30 | 10-AUG-13:00 | 31.00 | 24.35 |
September | 0.464715E+10 | 3533.64 | 30-SEP-24:00 | 29.00 | 26.44 | 91606437.11 | 126.85 | 05-SEP-13:00 | 29.00 | 26.44 |
October | 0.975007E+10 | 5390.62 | 31-OCT-24:00 | 27.40 | 21.22 | 95250742.03 | 126.87 | 06-OCT-09:50 | 27.40 | 21.22 |
November | 0.141892E+11 | 5924.59 | 12-NOV-17:03 | 28.83 | 17.83 | 94311124.48 | 126.85 | 01-NOV-09:09 | 28.83 | 17.83 |
December | 0.195507E+11 | 7691.27 | 25-DEC-16:55 | 24.00 | 19.34 | 91883770.16 | 126.83 | 15-DEC-10:09 | 24.00 | 19.34 |
Annual Sum or Average | 0.143047E+12 | 0.115885E+10 | ||||||||
Minimum of Months | 0.416874E+10 | 1886.41 | 22.30 | 17.83 | 86408389.88 | 126.83 | 22.30 | 17.83 | ||
Maximum of Months | 0.195507E+11 | 7809.23 | 33.30 | 28.31 | 0.118371E+09 | 157.30 | 37.33 | 28.31 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328052E+10 | 1617.57 | 29-JAN-17:50 | 24.17 | 19.49 | 95233491.51 | 126.84 | 25-JAN-14:00 | 24.17 | 19.49 |
February | 0.765024E+10 | 3520.85 | 05-FEB-17:15 | 31.00 | 18.60 | 86407759.41 | 126.85 | 09-FEB-10:09 | 23.92 | 19.44 |
March | 0.136641E+11 | 6914.89 | 31-MAR-24:00 | 22.30 | 20.22 | 0.103244E+09 | 126.84 | 02-MAR-14:09 | 22.30 | 20.22 |
April | 0.181198E+11 | 7376.55 | 23-APR-17:46 | 30.17 | 19.07 | 92308827.74 | 142.00 | 26-APR-13:09 | 37.33 | 19.85 |
May | 0.439951E+10 | 3458.82 | 31-MAY-23:57 | 32.70 | 23.39 | 99237065.26 | 126.85 | 22-MAY-13:00 | 32.70 | 23.39 |
June | 0.899558E+10 | 5216.28 | 30-JUN-23:55 | 31.70 | 26.86 | 98977970.40 | 126.87 | 20-JUN-09:09 | 31.70 | 26.86 |
July | 0.142276E+11 | 6881.40 | 31-JUL-23:23 | 33.50 | 28.49 | 91891393.86 | 126.85 | 18-JUL-09:09 | 33.50 | 28.49 |
August | 0.182655E+11 | 7133.64 | 14-AUG-03:23 | 31.00 | 24.29 | 0.115402E+09 | 153.19 | 10-AUG-13:00 | 31.00 | 24.29 |
September | 0.428515E+10 | 3399.86 | 30-SEP-23:40 | 29.00 | 26.39 | 91605880.31 | 126.85 | 05-SEP-13:39 | 29.00 | 26.39 |
October | 0.920832E+10 | 5215.74 | 31-OCT-24:00 | 27.40 | 21.22 | 95249717.63 | 126.87 | 17-OCT-09:09 | 27.40 | 21.22 |
November | 0.134116E+11 | 5527.88 | 12-NOV-17:03 | 28.83 | 17.83 | 94310635.87 | 126.84 | 01-NOV-09:09 | 28.83 | 17.83 |
December | 0.182523E+11 | 7135.77 | 03-DEC-17:07 | 25.17 | 21.34 | 91883760.62 | 126.83 | 15-DEC-10:09 | 19.67 | 18.50 |
Annual Sum or Average | 0.133760E+12 | 0.115575E+10 | ||||||||
Minimum of Months | 0.328052E+10 | 1617.57 | 22.30 | 17.83 | 86407759.41 | 126.83 | 19.67 | 17.83 | ||
Maximum of Months | 0.182655E+11 | 7376.55 | 33.50 | 28.49 | 0.115402E+09 | 153.19 | 37.33 | 28.49 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279354E+10 | 1673.99 | 29-JAN-17:35 | 24.33 | 19.64 | 95233157.86 | 126.84 | 31-JAN-14:09 | 23.00 | 16.33 |
February | 0.737890E+10 | 3642.51 | 05-FEB-17:05 | 31.00 | 18.53 | 86407922.01 | 126.85 | 07-FEB-14:00 | 28.00 | 22.41 |
March | 0.135396E+11 | 6858.79 | 31-MAR-24:00 | 22.30 | 20.22 | 0.103244E+09 | 126.84 | 02-MAR-14:09 | 22.30 | 20.22 |
April | 0.181423E+11 | 7540.34 | 02-APR-16:31 | 30.13 | 18.26 | 92294620.84 | 142.66 | 26-APR-13:09 | 37.33 | 19.85 |
May | 0.453761E+10 | 3514.71 | 31-MAY-23:57 | 32.70 | 23.39 | 99237717.80 | 126.85 | 11-MAY-13:50 | 32.70 | 23.39 |
June | 0.914272E+10 | 5233.30 | 30-JUN-23:55 | 31.70 | 26.86 | 98978447.60 | 126.87 | 08-JUN-13:09 | 31.70 | 26.86 |
July | 0.144481E+11 | 6945.20 | 31-JUL-23:42 | 33.37 | 28.37 | 91891425.80 | 126.85 | 05-JUL-09:09 | 33.37 | 28.37 |
August | 0.184611E+11 | 7234.48 | 14-AUG-03:01 | 31.00 | 24.41 | 0.115369E+09 | 154.67 | 10-AUG-13:00 | 31.00 | 24.41 |
September | 0.441822E+10 | 3440.90 | 30-SEP-24:00 | 29.00 | 26.44 | 91606230.18 | 126.85 | 05-SEP-13:00 | 29.00 | 26.44 |
October | 0.927193E+10 | 5211.87 | 31-OCT-24:00 | 27.40 | 21.22 | 95250063.93 | 126.87 | 17-OCT-13:09 | 27.40 | 21.22 |
November | 0.133362E+11 | 5685.46 | 05-NOV-16:42 | 31.07 | 21.51 | 94310924.28 | 126.84 | 01-NOV-09:09 | 31.07 | 21.51 |
December | 0.179436E+11 | 7178.41 | 03-DEC-17:07 | 25.17 | 21.34 | 91884087.61 | 126.83 | 15-DEC-10:09 | 19.67 | 18.50 |
Annual Sum or Average | 0.133414E+12 | 0.115571E+10 | ||||||||
Minimum of Months | 0.279354E+10 | 1673.99 | 22.30 | 18.26 | 86407922.01 | 126.83 | 19.67 | 16.33 | ||
Maximum of Months | 0.184611E+11 | 7540.34 | 33.37 | 28.37 | 0.115369E+09 | 154.67 | 37.33 | 28.37 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242303E+12 | 92806.15 | 02-JAN-17:00 | 21.00 | 13.15 | 0.206201E+10 | 2747.73 | 20-JAN-10:09 | 17.42 | 12.06 |
February | 0.438796E+12 | 183758.50 | 06-FEB-17:00 | 26.00 | 21.11 | 0.187066E+10 | 2746.81 | 13-FEB-10:09 | 19.50 | 13.91 |
March | 0.730349E+12 | 359085.17 | 31-MAR-24:00 | 22.30 | 20.22 | 0.223503E+10 | 2746.01 | 16-MAR-09:09 | 22.30 | 20.22 |
April | 0.938246E+12 | 369213.88 | 30-APR-03:07 | 21.82 | 21.19 | 0.225186E+10 | 4095.33 | 28-APR-12:20 | 21.82 | 21.19 |
May | 0.242168E+12 | 176389.21 | 31-MAY-23:57 | 32.70 | 23.39 | 0.214869E+10 | 2747.15 | 30-MAY-09:09 | 32.70 | 23.39 |
June | 0.471172E+12 | 267950.75 | 30-JUN-23:55 | 31.70 | 26.86 | 0.214269E+10 | 2746.77 | 20-JUN-09:09 | 31.70 | 26.86 |
July | 0.733783E+12 | 353031.08 | 31-JUL-23:23 | 33.50 | 28.49 | 0.198916E+10 | 2745.86 | 26-JUL-09:09 | 33.50 | 28.49 |
August | 0.959794E+12 | 366441.34 | 15-AUG-07:10 | 29.58 | 21.34 | 0.329434E+10 | 4614.69 | 16-AUG-13:00 | 44.00 | 25.56 |
September | 0.238640E+12 | 177397.18 | 30-SEP-24:00 | 29.00 | 26.44 | 0.198367E+10 | 2747.24 | 22-SEP-09:09 | 29.00 | 26.44 |
October | 0.490637E+12 | 269497.22 | 31-OCT-24:00 | 27.40 | 21.22 | 0.206198E+10 | 2746.67 | 17-OCT-09:09 | 27.40 | 21.22 |
November | 0.711874E+12 | 277056.10 | 13-NOV-15:00 | 33.00 | 18.63 | 0.204154E+10 | 2745.81 | 01-NOV-09:09 | 33.00 | 18.63 |
December | 0.979072E+12 | 368803.88 | 06-DEC-22:02 | 22.25 | 18.77 | 0.202982E+10 | 3065.56 | 04-DEC-14:09 | 22.25 | 18.77 |
Annual Sum or Average | 0.717683E+13 | 0.261114E+11 | ||||||||
Minimum of Months | 0.238640E+12 | 92806.15 | 21.00 | 13.15 | 0.187066E+10 | 2745.81 | 17.42 | 12.06 | ||
Maximum of Months | 0.979072E+12 | 369213.88 | 33.50 | 28.49 | 0.329434E+10 | 4614.69 | 44.00 | 28.49 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101574E+09 | 7879.40 | 16-JAN-12:37 | 25.50 |
February | 0.102257E+09 | 12473.07 | 04-FEB-17:03 | 27.83 |
March | 0.157882E+09 | 15220.83 | 02-MAR-04:04 | 29.10 |
April | 0.380442E+09 | 24361.94 | 29-APR-16:01 | 35.33 |
May | 0.601510E+09 | 25287.31 | 20-MAY-16:01 | 36.17 |
June | 0.622740E+09 | 26827.43 | 03-JUN-16:01 | 37.08 |
July | 0.899309E+09 | 34419.05 | 30-JUL-11:33 | 43.67 |
August | 0.611597E+09 | 31260.62 | 05-AUG-16:01 | 40.08 |
September | 0.729122E+09 | 29898.58 | 04-SEP-14:03 | 41.00 |
October | 0.730544E+09 | 22670.40 | 07-OCT-16:01 | 34.33 |
November | 0.425532E+09 | 20260.25 | 05-NOV-12:30 | 33.70 |
December | 0.222285E+09 | 15343.64 | 03-DEC-12:22 | 28.90 |
Annual Sum or Average | 0.558479E+10 | |||
Minimum of Months | 0.101574E+09 | 7879.40 | 25.50 | |
Maximum of Months | 0.899309E+09 | 34419.05 | 43.67 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 812117.54 | 2275.88 | 02-JAN-06:02 | 13.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 812117.54 | |||
Minimum of Months | 0.00 | 0.00 | 13.00 | |
Maximum of Months | 812117.54 | 2275.88 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 392127.78 | 1138.68 | 02-JAN-06:02 | 13.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 392127.78 | |||
Minimum of Months | 0.00 | 0.00 | 13.00 | |
Maximum of Months | 392127.78 | 1138.68 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 83526558.20 | 8225.02 | 17-JAN-05:12 | 16.67 |
February | 74307155.96 | 9727.51 | 21-FEB-05:11 | 14.67 |
March | 66521585.51 | 10751.58 | 06-MAR-05:11 | 16.67 |
April | 51899210.65 | 7519.13 | 05-APR-04:11 | 17.07 |
May | 27451301.93 | 5249.03 | 14-MAY-15:11 | 34.67 |
June | 22938692.55 | 4972.53 | 04-JUN-13:41 | 37.92 |
July | 36886349.90 | 5609.88 | 30-JUL-11:02 | 44.67 |
August | 39301679.79 | 5297.93 | 27-AUG-11:02 | 37.83 |
September | 25110927.03 | 4889.49 | 03-SEP-14:22 | 39.00 |
October | 38746185.27 | 5909.91 | 22-OCT-14:32 | 32.00 |
November | 67823151.19 | 7819.29 | 30-NOV-05:12 | 19.67 |
December | 0.130536E+09 | 11105.20 | 18-DEC-05:12 | 13.00 |
Annual Sum or Average | 0.665049E+09 | |||
Minimum of Months | 22938692.55 | 4889.49 | 13.00 | |
Maximum of Months | 0.130536E+09 | 11105.20 | 44.67 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44774634.12 | 6678.61 | 02-JAN-06:02 | 13.00 |
February | 37821207.90 | 7258.23 | 21-FEB-05:11 | 14.67 |
March | 31671273.77 | 7338.66 | 26-MAR-14:52 | 32.60 |
April | 37377092.73 | 7057.53 | 02-APR-14:42 | 33.17 |
May | 37064386.09 | 6020.98 | 07-MAY-13:52 | 37.00 |
June | 29016675.99 | 5412.69 | 18-JUN-15:22 | 36.05 |
July | 42842410.87 | 6389.95 | 30-JUL-11:02 | 44.67 |
August | 28061622.64 | 5771.10 | 27-AUG-14:22 | 37.00 |
September | 32187050.10 | 6387.43 | 03-SEP-14:11 | 39.33 |
October | 43977036.60 | 6767.24 | 29-OCT-13:51 | 34.00 |
November | 39722786.46 | 4633.40 | 19-NOV-14:32 | 30.33 |
December | 43367725.80 | 5725.10 | 18-DEC-06:03 | 13.17 |
Annual Sum or Average | 0.447884E+09 | |||
Minimum of Months | 28061622.64 | 4633.40 | 13.00 | |
Maximum of Months | 44774634.12 | 7338.66 | 44.67 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.655550E+09 | 12905.19 | 12-JAN-06:02 | 13.93 |
February | 0.378245E+09 | 14313.79 | 01-FEB-06:02 | 13.02 |
March | 0.230051E+09 | 13302.45 | 06-MAR-06:03 | 15.97 |
April | 64022217.22 | 11415.31 | 05-APR-05:03 | 17.00 |
May | 10133222.03 | 7691.26 | 04-MAY-04:12 | 23.53 |
June | 1669536.24 | 3925.85 | 30-JUN-03:02 | 26.88 |
July | 321201.58 | 873.07 | 30-JUL-08:23 | 36.90 |
August | 12844.48 | 107.04 | 27-AUG-09:02 | 35.25 |
September | 2264636.60 | 3865.03 | 26-SEP-03:02 | 26.18 |
October | 20430550.25 | 10455.72 | 30-OCT-04:12 | 22.40 |
November | 72765995.12 | 11634.99 | 22-NOV-06:03 | 16.98 |
December | 0.378447E+09 | 12610.75 | 22-DEC-06:02 | 15.83 |
Annual Sum or Average | 0.181391E+10 | |||
Minimum of Months | 12844.48 | 107.04 | 13.02 | |
Maximum of Months | 0.655550E+09 | 14313.79 | 36.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.968216E+10 | 10174.14 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.878253E+10 | 10174.14 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.104353E+11 | 10174.14 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.932187E+10 | 10174.14 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.100587E+11 | 10174.14 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.100099E+11 | 10174.14 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.937071E+10 | 10174.14 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.104353E+11 | 10174.14 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.932187E+10 | 10174.14 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.968216E+10 | 10174.14 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.956821E+10 | 10174.14 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.937071E+10 | 10174.14 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.116039E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.878253E+10 | 10174.14 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.104353E+11 | 10174.14 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.660438E+09 | 854.72 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.579779E+09 | 880.50 | 09-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.671216E+09 | 1031.32 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.586417E+09 | 848.40 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.615151E+09 | 545.86 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.605754E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.577587E+09 | 637.35 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.645153E+09 | 600.46 | 29-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.590454E+09 | 616.14 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.629103E+09 | 761.09 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.644693E+09 | 957.43 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.648232E+09 | 983.36 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.745398E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.577587E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.671216E+09 | 1031.32 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.420959E+09 | 579.47 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.371987E+09 | 580.65 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.430908E+09 | 654.92 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.377893E+09 | 496.80 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.398732E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.393067E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.373749E+09 | 395.91 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.416599E+09 | 351.77 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.380264E+09 | 351.77 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.402569E+09 | 381.17 | 27-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.413951E+09 | 634.58 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.413020E+09 | 642.41 | 14-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.479370E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.371987E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.430908E+09 | 654.92 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.640116E+09 | 754.37 | 23-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.569703E+09 | 833.30 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.667275E+09 | 1029.00 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.587600E+09 | 854.35 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.620847E+09 | 582.86 | 23-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.611845E+09 | 593.66 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.582355E+09 | 750.07 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.647834E+09 | 596.39 | 29-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.589654E+09 | 613.16 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.622058E+09 | 608.81 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.627209E+09 | 830.74 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.624412E+09 | 919.89 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.739091E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.569703E+09 | 582.86 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.667275E+09 | 1029.00 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.417813E+09 | 548.11 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.369581E+09 | 519.61 | 09-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.433246E+09 | 668.86 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.379620E+09 | 573.64 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.399680E+09 | 396.88 | 23-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.393078E+09 | 398.63 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.375326E+09 | 516.87 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.418008E+09 | 410.79 | 29-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.381058E+09 | 485.89 | 06-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.405014E+09 | 531.73 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.407195E+09 | 533.33 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.407261E+09 | 612.61 | 15-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.478688E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.369581E+09 | 396.88 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.433246E+09 | 668.86 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.658713E+09 | 850.09 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.578462E+09 | 877.19 | 09-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.670290E+09 | 1030.00 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.585880E+09 | 844.72 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.614864E+09 | 545.86 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.605052E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.577252E+09 | 633.52 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.644765E+09 | 594.54 | 29-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.589828E+09 | 611.10 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.628170E+09 | 754.73 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.643321E+09 | 954.76 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.646435E+09 | 981.28 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.744303E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.577252E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.670290E+09 | 1030.00 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.420084E+09 | 575.48 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.371413E+09 | 576.48 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.430335E+09 | 653.00 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.377598E+09 | 492.27 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.398474E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.392792E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.373512E+09 | 393.23 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.416304E+09 | 351.77 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.379998E+09 | 351.77 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.402239E+09 | 377.22 | 27-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.413375E+09 | 631.87 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.412241E+09 | 639.90 | 14-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.478837E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.371413E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.430335E+09 | 653.00 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.639770E+09 | 750.12 | 23-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.569302E+09 | 829.74 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.666645E+09 | 1027.67 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.587084E+09 | 850.71 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.620401E+09 | 545.88 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.611340E+09 | 587.20 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.581787E+09 | 744.62 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.647347E+09 | 590.25 | 29-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.589118E+09 | 607.99 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.621256E+09 | 602.83 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.626912E+09 | 826.78 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.624035E+09 | 917.17 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.738500E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.569302E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.666645E+09 | 1027.67 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.417160E+09 | 543.12 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.368990E+09 | 513.79 | 09-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.432539E+09 | 667.01 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.378958E+09 | 569.25 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.399198E+09 | 393.62 | 23-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.392610E+09 | 395.48 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.374784E+09 | 510.95 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.417560E+09 | 408.35 | 29-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.380691E+09 | 478.80 | 06-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.404553E+09 | 526.96 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.406739E+09 | 528.71 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.406467E+09 | 609.30 | 15-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.478025E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.368990E+09 | 393.62 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.432539E+09 | 667.01 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.658632E+09 | 849.64 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.578391E+09 | 876.65 | 09-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.670238E+09 | 1029.75 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.585864E+09 | 844.12 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.614855E+09 | 545.86 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.605040E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.577236E+09 | 633.36 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.644742E+09 | 594.31 | 29-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.589811E+09 | 610.91 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.628128E+09 | 754.20 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.643287E+09 | 954.43 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.646385E+09 | 980.97 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.744261E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.577236E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.670238E+09 | 1029.75 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.420065E+09 | 575.24 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.371397E+09 | 576.16 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.430319E+09 | 652.84 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.377589E+09 | 491.83 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.398456E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.392783E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.373500E+09 | 393.10 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.416280E+09 | 351.77 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.379990E+09 | 351.77 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.402212E+09 | 377.11 | 27-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.413358E+09 | 631.69 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.412185E+09 | 639.71 | 14-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.478813E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.371397E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.430319E+09 | 652.84 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.639759E+09 | 749.42 | 23-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.569284E+09 | 829.14 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.666619E+09 | 1027.42 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.587066E+09 | 850.12 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.620372E+09 | 545.88 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.611313E+09 | 586.96 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.581758E+09 | 743.84 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.647322E+09 | 590.02 | 29-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.589096E+09 | 607.78 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.621246E+09 | 602.63 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.626905E+09 | 826.34 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.624023E+09 | 916.80 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.738476E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.569284E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.666619E+09 | 1027.42 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.417130E+09 | 542.75 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.368975E+09 | 513.36 | 09-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.432584E+09 | 666.86 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.378945E+09 | 568.90 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.399187E+09 | 393.51 | 23-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.392585E+09 | 395.37 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.374764E+09 | 510.50 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.417535E+09 | 408.26 | 29-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.380659E+09 | 478.34 | 06-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.404539E+09 | 526.69 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.406731E+09 | 528.46 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.406418E+09 | 609.04 | 15-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.478005E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.368975E+09 | 393.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.432584E+09 | 666.86 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.274130E+10 | 2868.67 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.248656E+10 | 2868.67 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.295472E+10 | 2868.67 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.263917E+10 | 2868.67 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.284801E+10 | 2868.67 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.283424E+10 | 2868.67 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.265294E+10 | 2868.67 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.295472E+10 | 2868.67 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.263917E+10 | 2868.67 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.274130E+10 | 2868.67 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.270917E+10 | 2868.67 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.265294E+10 | 2868.67 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.328542E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.248656E+10 | 2868.67 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.295472E+10 | 2868.67 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.100587E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.100099E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.956821E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.116039E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.660438E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1318327.33 | 0.147380E+09 |
February | 0.136985E+10 | 0.579779E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13064595.05 | 0.146481E+09 |
March | 0.163685E+10 | 0.671216E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34529725.83 | 76988678.95 |
April | 0.145243E+10 | 0.586417E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81341182.19 | 28748577.45 |
May | 0.157338E+10 | 0.615151E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204780E+09 | 2365802.86 |
June | 0.156900E+10 | 0.605754E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255835E+09 | 101743.73 |
July | 0.145680E+10 | 0.577587E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357264E+09 | 0.00 |
August | 0.163685E+10 | 0.645153E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338819E+09 | 0.00 |
September | 0.145243E+10 | 0.590454E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247521E+09 | 247637.26 |
October | 0.150991E+10 | 0.629103E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142453E+09 | 3101586.08 |
November | 0.149516E+10 | 0.644693E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57541469.76 | 33312737.58 |
December | 0.145680E+10 | 0.648232E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8391262.87 | 0.106972E+09 |
Annual Sum or Average | 0.181194E+11 | 0.745398E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174286E+10 | 0.545700E+09 |
Minimum of Months | 0.136985E+10 | 0.577587E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1318327.33 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.671216E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357264E+09 | 0.147380E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.420959E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 579618.30 | 0.101077E+09 |
February | 0.882782E+09 | 0.371987E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7959029.39 | 97714808.07 |
March | 0.105485E+10 | 0.430908E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22927894.00 | 50018610.69 |
April | 0.936002E+09 | 0.377893E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53666471.84 | 17983753.94 |
May | 0.101394E+10 | 0.398732E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135030E+09 | 1627998.60 |
June | 0.101113E+10 | 0.393067E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170648E+09 | 77014.84 |
July | 0.938820E+09 | 0.373749E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238422E+09 | 0.00 |
August | 0.105485E+10 | 0.416599E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226948E+09 | 0.00 |
September | 0.936002E+09 | 0.380264E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163212E+09 | 182291.60 |
October | 0.973041E+09 | 0.402569E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93684316.08 | 2131151.24 |
November | 0.963541E+09 | 0.413951E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37211759.02 | 21908436.71 |
December | 0.938820E+09 | 0.413020E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5551055.76 | 67798943.26 |
Annual Sum or Average | 0.116768E+11 | 0.479370E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115584E+10 | 0.360520E+09 |
Minimum of Months | 0.882782E+09 | 0.371987E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 579618.30 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.430908E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238422E+09 | 0.101077E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.640116E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 727862.70 | 0.164248E+09 |
February | 0.136988E+10 | 0.569703E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11399761.87 | 0.159071E+09 |
March | 0.163688E+10 | 0.667275E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33039971.89 | 83656717.12 |
April | 0.145246E+10 | 0.587600E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79008888.91 | 30509077.84 |
May | 0.157341E+10 | 0.620847E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204626E+09 | 2428739.93 |
June | 0.156904E+10 | 0.611845E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257243E+09 | 83463.77 |
July | 0.145684E+10 | 0.582355E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358069E+09 | 0.00 |
August | 0.163688E+10 | 0.647834E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338348E+09 | 0.00 |
September | 0.145246E+10 | 0.589654E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242365E+09 | 322743.48 |
October | 0.150994E+10 | 0.622058E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134336E+09 | 4722909.21 |
November | 0.149520E+10 | 0.627209E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50270826.19 | 40350711.40 |
December | 0.145684E+10 | 0.624412E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6776328.00 | 0.118992E+09 |
Annual Sum or Average | 0.181198E+11 | 0.739091E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171621E+10 | 0.604385E+09 |
Minimum of Months | 0.136988E+10 | 0.569703E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 727862.70 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.667275E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358069E+09 | 0.164248E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.417813E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 541063.16 | 0.115419E+09 |
February | 0.882782E+09 | 0.369581E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7661857.97 | 0.120846E+09 |
March | 0.105485E+10 | 0.433246E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21079525.44 | 71547279.75 |
April | 0.936002E+09 | 0.379620E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49669674.24 | 32176268.58 |
May | 0.101394E+10 | 0.399680E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130521E+09 | 2760529.08 |
June | 0.101113E+10 | 0.393078E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163869E+09 | 221392.63 |
July | 0.938820E+09 | 0.375326E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231771E+09 | 0.00 |
August | 0.105485E+10 | 0.418008E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219690E+09 | 0.00 |
September | 0.936002E+09 | 0.381058E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156823E+09 | 346044.65 |
October | 0.973041E+09 | 0.405014E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86176570.35 | 4893176.66 |
November | 0.963541E+09 | 0.407195E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32541515.32 | 35121117.69 |
December | 0.938820E+09 | 0.407261E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4381355.41 | 96935826.17 |
Annual Sum or Average | 0.116768E+11 | 0.478688E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110472E+10 | 0.480267E+09 |
Minimum of Months | 0.882782E+09 | 0.369581E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 541063.16 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.433246E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231771E+09 | 0.120846E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.658713E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5535403.19 | 0.287305E+09 |
February | 0.136985E+10 | 0.578462E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32619835.42 | 0.296324E+09 |
March | 0.163685E+10 | 0.670290E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77976536.22 | 0.169191E+09 |
April | 0.145243E+10 | 0.585880E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187911E+09 | 81524956.41 |
May | 0.157338E+10 | 0.614864E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467237E+09 | 7736506.77 |
June | 0.156900E+10 | 0.605052E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588036E+09 | 374902.25 |
July | 0.145680E+10 | 0.577252E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828721E+09 | 0.00 |
August | 0.163685E+10 | 0.644765E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792303E+09 | 0.00 |
September | 0.145243E+10 | 0.589828E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565975E+09 | 917818.44 |
October | 0.150991E+10 | 0.628170E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319917E+09 | 12204882.13 |
November | 0.149516E+10 | 0.643321E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134892E+09 | 83539487.27 |
December | 0.145680E+10 | 0.646435E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22321837.48 | 0.215739E+09 |
Annual Sum or Average | 0.181194E+11 | 0.744303E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402345E+10 | 0.115486E+10 |
Minimum of Months | 0.136985E+10 | 0.577252E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5535403.19 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.670290E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828721E+09 | 0.296324E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.420084E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1377211.05 | 0.214006E+09 |
February | 0.649041E+09 | 0.371413E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17556049.46 | 0.216414E+09 |
March | 0.773965E+09 | 0.430335E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48228416.00 | 0.124412E+09 |
April | 0.688021E+09 | 0.377598E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117027E+09 | 60335693.93 |
May | 0.744847E+09 | 0.398474E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304018E+09 | 6052132.80 |
June | 0.742030E+09 | 0.392792E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385744E+09 | 344557.53 |
July | 0.690839E+09 | 0.373512E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545838E+09 | 0.00 |
August | 0.773965E+09 | 0.416304E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521500E+09 | 0.00 |
September | 0.688021E+09 | 0.379998E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367675E+09 | 755874.32 |
October | 0.715730E+09 | 0.402239E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203706E+09 | 10276791.92 |
November | 0.708685E+09 | 0.413375E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78807019.21 | 63099910.14 |
December | 0.690839E+09 | 0.412241E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11340589.48 | 0.156985E+09 |
Annual Sum or Average | 0.858171E+10 | 0.478837E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260282E+10 | 0.852682E+09 |
Minimum of Months | 0.649041E+09 | 0.371413E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1377211.05 | 0.00 |
Maximum of Months | 0.773965E+09 | 0.430335E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545838E+09 | 0.216414E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.639770E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1564124.36 | 0.368971E+09 |
February | 0.136988E+10 | 0.569302E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25780756.90 | 0.356644E+09 |
March | 0.163688E+10 | 0.666645E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72958196.38 | 0.199149E+09 |
April | 0.145246E+10 | 0.587084E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180568E+09 | 88608369.75 |
May | 0.157341E+10 | 0.620401E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467254E+09 | 7958397.47 |
June | 0.156904E+10 | 0.611340E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591499E+09 | 319102.21 |
July | 0.145684E+10 | 0.581787E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830318E+09 | 0.00 |
August | 0.163688E+10 | 0.647347E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789295E+09 | 0.00 |
September | 0.145246E+10 | 0.589118E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552977E+09 | 1191506.86 |
October | 0.150994E+10 | 0.621256E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299270E+09 | 19101681.02 |
November | 0.149520E+10 | 0.626912E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111155E+09 | 0.110492E+09 |
December | 0.145684E+10 | 0.624035E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14663491.41 | 0.275637E+09 |
Annual Sum or Average | 0.181198E+11 | 0.738500E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393730E+10 | 0.142807E+10 |
Minimum of Months | 0.136988E+10 | 0.569302E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1564124.36 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.666645E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830318E+09 | 0.368971E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.417160E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1953343.69 | 0.222846E+09 |
February | 0.882782E+09 | 0.368990E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18897226.31 | 0.228682E+09 |
March | 0.105485E+10 | 0.432539E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48669942.69 | 0.138155E+09 |
April | 0.936002E+09 | 0.378958E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116752E+09 | 68585491.10 |
May | 0.101394E+10 | 0.399198E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302299E+09 | 7164194.01 |
June | 0.101113E+10 | 0.392610E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382219E+09 | 441314.51 |
July | 0.938820E+09 | 0.374784E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543453E+09 | 0.00 |
August | 0.105485E+10 | 0.417560E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519378E+09 | 0.00 |
September | 0.936002E+09 | 0.380691E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364138E+09 | 940061.67 |
October | 0.973041E+09 | 0.404553E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200293E+09 | 12684313.05 |
November | 0.963541E+09 | 0.406739E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77881696.21 | 69609615.11 |
December | 0.938820E+09 | 0.406467E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11225639.18 | 0.171914E+09 |
Annual Sum or Average | 0.116768E+11 | 0.478025E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258716E+10 | 0.921022E+09 |
Minimum of Months | 0.882782E+09 | 0.368990E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1953343.69 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.432539E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543453E+09 | 0.228682E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.658632E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7050738.03 | 0.325562E+09 |
February | 0.136985E+10 | 0.578391E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38458442.38 | 0.348502E+09 |
March | 0.163685E+10 | 0.670238E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93149519.79 | 0.204687E+09 |
April | 0.145243E+10 | 0.585864E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223337E+09 | 0.102111E+09 |
May | 0.157338E+10 | 0.614855E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566133E+09 | 10402347.58 |
June | 0.156900E+10 | 0.605040E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714656E+09 | 638561.41 |
July | 0.145680E+10 | 0.577236E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100890E+10 | 0.00 |
August | 0.163685E+10 | 0.644742E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.966584E+09 | 0.00 |
September | 0.145243E+10 | 0.589811E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686157E+09 | 1255277.62 |
October | 0.150991E+10 | 0.628128E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384810E+09 | 16179643.68 |
November | 0.149516E+10 | 0.643287E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159062E+09 | 0.100960E+09 |
December | 0.145680E+10 | 0.646385E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27048887.58 | 0.250664E+09 |
Annual Sum or Average | 0.181194E+11 | 0.744261E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487535E+10 | 0.136096E+10 |
Minimum of Months | 0.136985E+10 | 0.577236E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7050738.03 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.670238E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100890E+10 | 0.348502E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.420065E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1913487.68 | 0.244252E+09 |
February | 0.882782E+09 | 0.371397E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21441654.83 | 0.254780E+09 |
March | 0.105485E+10 | 0.430319E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59580983.10 | 0.150044E+09 |
April | 0.936002E+09 | 0.377589E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142784E+09 | 75155686.61 |
May | 0.101394E+10 | 0.398456E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371499E+09 | 8067853.34 |
June | 0.101113E+10 | 0.392783E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472193E+09 | 539530.84 |
July | 0.938820E+09 | 0.373500E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667721E+09 | 0.00 |
August | 0.105485E+10 | 0.416280E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639699E+09 | 0.00 |
September | 0.936002E+09 | 0.379990E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449110E+09 | 1012304.77 |
October | 0.973041E+09 | 0.402212E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248168E+09 | 13397291.03 |
November | 0.963541E+09 | 0.413358E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96047998.13 | 76270085.80 |
December | 0.938820E+09 | 0.412185E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14208957.83 | 0.182567E+09 |
Annual Sum or Average | 0.116768E+11 | 0.478813E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318437E+10 | 0.100609E+10 |
Minimum of Months | 0.882782E+09 | 0.371397E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1913487.68 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.430319E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667721E+09 | 0.254780E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.639759E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1767004.76 | 0.430844E+09 |
February | 0.136988E+10 | 0.569284E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30807255.94 | 0.425426E+09 |
March | 0.163688E+10 | 0.666619E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87849363.33 | 0.241749E+09 |
April | 0.145246E+10 | 0.587066E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216541E+09 | 0.110785E+09 |
May | 0.157341E+10 | 0.620372E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566225E+09 | 10663670.84 |
June | 0.156904E+10 | 0.611313E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718069E+09 | 551909.35 |
July | 0.145684E+10 | 0.581758E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101044E+10 | 0.00 |
August | 0.163688E+10 | 0.647322E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963551E+09 | 0.00 |
September | 0.145246E+10 | 0.589096E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672345E+09 | 1599025.46 |
October | 0.150994E+10 | 0.621246E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362684E+09 | 24829348.41 |
November | 0.149520E+10 | 0.626905E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133266E+09 | 0.134083E+09 |
December | 0.145684E+10 | 0.624023E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17092596.19 | 0.328274E+09 |
Annual Sum or Average | 0.181198E+11 | 0.738476E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478064E+10 | 0.170880E+10 |
Minimum of Months | 0.136988E+10 | 0.569284E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1767004.76 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.666619E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101044E+10 | 0.430844E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.417130E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2367779.51 | 0.260853E+09 |
February | 0.882782E+09 | 0.368975E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22611112.78 | 0.273849E+09 |
March | 0.105485E+10 | 0.432584E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58629260.65 | 0.168372E+09 |
April | 0.936002E+09 | 0.378945E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140740E+09 | 85513139.27 |
May | 0.101394E+10 | 0.399187E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367716E+09 | 9444649.85 |
June | 0.101113E+10 | 0.392585E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466032E+09 | 691490.86 |
July | 0.938820E+09 | 0.374764E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663731E+09 | 0.00 |
August | 0.105485E+10 | 0.417535E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635322E+09 | 0.00 |
September | 0.936002E+09 | 0.380659E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443409E+09 | 1249533.35 |
October | 0.973041E+09 | 0.404539E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242786E+09 | 16481193.82 |
November | 0.963541E+09 | 0.406731E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93559058.52 | 84768089.06 |
December | 0.938820E+09 | 0.406418E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13223591.51 | 0.204771E+09 |
Annual Sum or Average | 0.116768E+11 | 0.478005E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315013E+10 | 0.110599E+10 |
Minimum of Months | 0.882782E+09 | 0.368975E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2367779.51 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.432584E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663731E+09 | 0.273849E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.274130E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.248656E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.295472E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.263917E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.284801E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.283424E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.265294E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.295472E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.263917E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.274130E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.270917E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.265294E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.328542E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.248656E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.295472E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1795065.67 | 0.329697E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22992357.99 | 0.324274E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57462389.57 | 0.177692E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147211E+09 | 74466362.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382431E+09 | 7310024.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472562E+09 | 634574.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672691E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628731E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454298E+09 | 966091.42 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252451E+09 | 12083574.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95505807.92 | 84972085.21 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12480099.31 | 0.245773E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320061E+10 | 0.125787E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1795065.67 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672691E+09 | 0.329697E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5372947.57 | 0.539858E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44660627.75 | 0.543594E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104563E+09 | 0.305009E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267385E+09 | 0.138768E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688918E+09 | 13544216.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859710E+09 | 1142627.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123217E+10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116105E+10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822300E+09 | 1751211.17 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453388E+09 | 24405158.13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174967E+09 | 0.152604E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25635747.29 | 0.406891E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584012E+10 | 0.212757E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5372947.57 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123217E+10 | 0.543594E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3095971.22 | 0.562248E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41085105.67 | 0.583827E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102720E+09 | 0.339314E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249933E+09 | 0.149734E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726850E+09 | 14398194.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938162E+09 | 1154353.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134261E+10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128667E+10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895513E+09 | 1850009.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484632E+09 | 24974220.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173693E+09 | 0.148857E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20507085.24 | 0.421427E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626547E+10 | 0.224778E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3095971.22 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134261E+10 | 0.583827E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 10174.14 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 10174.14 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 10174.14 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 10174.14 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 10174.14 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 10174.14 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 10174.14 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 10174.14 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 10174.14 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 10174.14 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 10174.14 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 10174.14 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 854.72 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.11 | 29-JAN-11:50 | 389.74 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 880.50 | 09-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 288.68 | 05-FEB-14:50 | 325.20 | 13-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1031.32 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 266.04 | 02-MAR-04:00 | 271.24 | 06-MAR-05:55 |
April | 2010.79 | 03-APR-09:09 | 848.40 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.97 | 30-APR-13:04 | 205.81 | 05-APR-04:00 |
May | 2010.79 | 01-MAY-09:09 | 545.86 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2080.88 | 21-MAY-13:00 | 63.96 | 01-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 507.42 | 11-JUN-15:04 | 32.97 | 07-JUN-04:30 |
July | 2010.79 | 03-JUL-09:09 | 637.35 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 778.45 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.79 | 01-AUG-09:09 | 600.46 | 29-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 727.74 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.79 | 01-SEP-09:09 | 616.14 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 562.62 | 03-SEP-15:43 | 29.90 | 25-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 761.09 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 481.89 | 09-OCT-15:04 | 91.24 | 20-OCT-04:00 |
November | 2010.79 | 01-NOV-09:09 | 957.43 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 283.44 | 19-NOV-13:52 | 167.45 | 22-NOV-05:55 |
December | 2010.79 | 01-DEC-10:09 | 983.36 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 122.03 | 10-DEC-12:10 | 252.23 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 87.11 | 0.00 | |||||
Maximum of Months | 2010.79 | 1031.32 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2080.88 | 389.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 579.47 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.76 | 23-JAN-13:00 | 259.24 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 580.65 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.14 | 05-FEB-15:08 | 214.96 | 13-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 654.92 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 188.18 | 02-MAR-04:00 | 172.22 | 06-MAR-05:55 |
April | 1295.83 | 03-APR-09:09 | 496.80 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.10 | 30-APR-13:04 | 130.39 | 05-APR-04:00 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1387.26 | 21-MAY-13:00 | 41.73 | 01-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 336.18 | 11-JUN-15:04 | 20.62 | 07-JUN-04:30 |
July | 1295.83 | 03-JUL-09:09 | 395.91 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 518.97 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 351.77 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 485.15 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 351.77 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.55 | 03-SEP-15:43 | 19.93 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 381.17 | 27-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.81 | 09-OCT-15:04 | 59.03 | 20-OCT-04:00 |
November | 1295.83 | 01-NOV-09:09 | 634.58 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.23 | 05-NOV-14:55 | 106.56 | 22-NOV-05:55 |
December | 1295.83 | 01-DEC-10:09 | 642.41 | 14-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.09 | 10-DEC-12:50 | 156.87 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 24.76 | 0.00 | |||||
Maximum of Months | 1295.83 | 654.92 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1387.26 | 259.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 754.37 | 23-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.14 | 23-JAN-13:00 | 407.65 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 833.30 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 271.80 | 05-FEB-15:05 | 343.51 | 10-FEB-23:20 |
March | 2010.83 | 01-MAR-10:09 | 1029.00 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 247.60 | 26-MAR-14:00 | 287.71 | 17-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 854.35 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.62 | 30-APR-13:04 | 206.36 | 05-APR-04:00 |
May | 2010.83 | 01-MAY-09:09 | 582.86 | 23-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2080.88 | 21-MAY-13:00 | 64.30 | 01-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 593.66 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 503.97 | 11-JUN-15:04 | 31.82 | 07-JUN-04:30 |
July | 2010.83 | 03-JUL-09:09 | 750.07 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 778.45 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.83 | 01-AUG-09:09 | 596.39 | 29-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 727.73 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.83 | 01-SEP-09:09 | 613.16 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 555.83 | 03-SEP-16:00 | 29.90 | 25-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 608.81 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 467.33 | 09-OCT-15:10 | 104.86 | 20-OCT-04:00 |
November | 2010.83 | 01-NOV-09:09 | 830.74 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.39 | 05-NOV-14:55 | 169.51 | 22-NOV-05:55 |
December | 2010.83 | 01-DEC-10:09 | 919.89 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 99.57 | 10-DEC-12:37 | 245.74 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 582.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 37.14 | 0.00 | |||||
Maximum of Months | 2010.83 | 1029.00 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2080.88 | 407.65 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 548.11 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.12 | 29-JAN-11:50 | 298.64 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 519.61 | 09-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.10 | 05-FEB-15:05 | 264.37 | 10-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 668.86 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 165.07 | 26-MAR-14:00 | 242.57 | 17-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 573.64 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.31 | 30-APR-13:04 | 181.00 | 05-APR-01:10 |
May | 1295.83 | 01-MAY-09:09 | 396.88 | 23-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1387.25 | 21-MAY-13:00 | 55.18 | 01-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 398.63 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.83 | 11-JUN-15:04 | 37.05 | 07-JUN-04:30 |
July | 1295.83 | 03-JUL-09:09 | 516.87 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 518.97 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 410.79 | 29-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 485.15 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 485.89 | 06-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 370.55 | 03-SEP-16:00 | 21.14 | 25-SEP-04:30 |
October | 1295.83 | 02-OCT-09:09 | 531.73 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.50 | 09-OCT-15:04 | 88.62 | 20-OCT-04:00 |
November | 1295.83 | 01-NOV-09:09 | 533.33 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.05 | 19-NOV-14:05 | 135.24 | 22-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 612.61 | 15-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 10-DEC-12:37 | 207.47 | 16-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 396.88 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 27.12 | 0.00 | |||||
Maximum of Months | 1295.83 | 668.86 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1387.25 | 298.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 850.09 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 286.77 | 29-JAN-12:00 | 733.21 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 877.19 | 09-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 705.26 | 05-FEB-14:40 | 640.88 | 13-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1030.00 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 595.47 | 26-MAR-14:00 | 604.50 | 05-MAR-14:55 |
April | 2010.79 | 03-APR-09:09 | 844.72 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 833.70 | 30-APR-12:53 | 456.71 | 05-APR-00:55 |
May | 2010.79 | 01-MAY-09:09 | 545.86 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4832.96 | 21-MAY-13:00 | 135.59 | 02-MAY-02:55 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.37 | 11-JUN-13:14 | 98.72 | 07-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 633.52 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1812.19 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.79 | 01-AUG-09:09 | 594.54 | 29-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1692.72 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.79 | 01-SEP-09:09 | 611.10 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1299.06 | 04-SEP-16:53 | 83.87 | 25-SEP-04:50 |
October | 2010.79 | 02-OCT-09:09 | 754.73 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1111.95 | 09-OCT-14:54 | 245.35 | 20-OCT-04:05 |
November | 2010.79 | 01-NOV-09:09 | 954.76 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 672.29 | 19-NOV-14:00 | 362.58 | 22-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 981.28 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 319.53 | 10-DEC-12:00 | 494.30 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 286.77 | 0.00 | |||||
Maximum of Months | 2010.79 | 1030.00 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4832.96 | 733.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 575.48 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 75.86 | 29-JAN-12:00 | 514.17 | 18-JAN-04:00 |
February | 1239.33 | 01-FEB-08:09 | 576.48 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 452.42 | 05-FEB-14:56 | 443.18 | 13-FEB-04:00 |
March | 1239.33 | 01-MAR-08:09 | 653.00 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 395.70 | 02-MAR-04:06 | 420.55 | 05-MAR-14:55 |
April | 1239.33 | 03-APR-07:10 | 492.27 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 555.79 | 30-APR-12:52 | 316.53 | 05-APR-00:55 |
May | 1239.33 | 01-MAY-07:10 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3221.96 | 21-MAY-13:00 | 97.33 | 02-MAY-02:55 |
June | 1239.33 | 01-JUN-07:10 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 789.39 | 11-JUN-13:14 | 68.91 | 07-JUN-05:00 |
July | 1239.33 | 03-JUL-07:10 | 393.23 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.13 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1239.33 | 01-AUG-07:10 | 351.77 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1128.47 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1239.33 | 01-SEP-07:10 | 351.77 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 861.36 | 04-SEP-16:53 | 59.50 | 25-SEP-04:50 |
October | 1239.33 | 02-OCT-07:10 | 377.22 | 27-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 739.42 | 09-OCT-14:54 | 172.82 | 20-OCT-04:05 |
November | 1239.33 | 01-NOV-07:10 | 631.87 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 458.13 | 19-NOV-13:56 | 244.10 | 22-NOV-06:00 |
December | 1239.33 | 01-DEC-08:09 | 639.90 | 14-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 181.26 | 10-DEC-12:30 | 327.77 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 75.86 | 0.00 | |||||
Maximum of Months | 1239.33 | 653.00 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 3221.96 | 514.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 750.12 | 23-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 84.30 | 23-JAN-13:00 | 842.38 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 829.74 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 611.93 | 05-FEB-14:56 | 734.91 | 10-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 1027.67 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 585.16 | 02-MAR-04:06 | 721.10 | 05-MAR-14:55 |
April | 2010.83 | 03-APR-09:09 | 850.71 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 833.70 | 30-APR-12:52 | 473.15 | 05-APR-00:55 |
May | 2010.83 | 01-MAY-09:09 | 545.88 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4832.95 | 21-MAY-13:00 | 138.91 | 02-MAY-02:55 |
June | 2010.83 | 01-JUN-09:09 | 587.20 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1184.43 | 11-JUN-13:14 | 97.04 | 07-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 744.62 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1812.19 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.83 | 01-AUG-09:09 | 590.25 | 29-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1692.72 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.83 | 01-SEP-09:09 | 607.99 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1302.75 | 04-SEP-16:53 | 90.99 | 25-SEP-04:50 |
October | 2010.83 | 02-OCT-09:09 | 602.83 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1088.06 | 09-OCT-15:00 | 281.81 | 20-OCT-04:05 |
November | 2010.83 | 01-NOV-09:09 | 826.78 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 609.37 | 19-NOV-13:56 | 384.89 | 22-NOV-06:00 |
December | 2010.83 | 01-DEC-10:09 | 917.17 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 229.18 | 10-DEC-12:25 | 501.99 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 84.30 | 0.00 | |||||
Maximum of Months | 2010.83 | 1027.67 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4832.95 | 842.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 543.12 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.05 | 29-JAN-12:00 | 536.76 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 513.79 | 09-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 452.46 | 05-FEB-14:56 | 478.81 | 10-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 667.01 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 404.58 | 02-MAR-04:06 | 480.77 | 05-MAR-14:55 |
April | 1295.83 | 03-APR-09:09 | 569.25 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 555.80 | 30-APR-12:52 | 342.64 | 05-APR-00:55 |
May | 1295.83 | 01-MAY-09:09 | 393.62 | 23-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3221.94 | 21-MAY-13:00 | 107.51 | 02-MAY-02:55 |
June | 1295.83 | 01-JUN-09:09 | 395.48 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 787.38 | 11-JUN-13:14 | 76.69 | 07-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 510.95 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.13 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 408.35 | 29-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1128.47 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 478.80 | 06-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 869.54 | 04-SEP-16:53 | 64.22 | 25-SEP-04:50 |
October | 1295.83 | 02-OCT-09:09 | 526.96 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 749.05 | 09-OCT-14:54 | 192.34 | 20-OCT-04:05 |
November | 1295.83 | 01-NOV-09:09 | 528.71 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 456.71 | 19-NOV-13:56 | 258.46 | 22-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 609.30 | 15-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 191.96 | 10-DEC-12:00 | 344.26 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 393.62 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 151.05 | 0.00 | |||||
Maximum of Months | 1295.83 | 667.01 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 3221.94 | 536.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 849.64 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 361.96 | 29-JAN-11:45 | 826.01 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 876.65 | 09-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 832.41 | 05-FEB-15:00 | 728.65 | 10-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 1029.75 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 733.24 | 26-MAR-14:00 | 732.14 | 05-MAR-15:10 |
April | 2010.79 | 03-APR-09:09 | 844.12 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.37 | 30-APR-12:53 | 546.70 | 05-APR-00:55 |
May | 2010.79 | 01-MAY-09:09 | 545.86 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5941.98 | 21-MAY-13:00 | 166.11 | 02-MAY-02:55 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.66 | 11-JUN-13:14 | 127.63 | 07-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 633.36 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2233.26 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.79 | 01-AUG-09:09 | 594.31 | 29-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2084.26 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.79 | 01-SEP-09:09 | 610.91 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1585.54 | 03-SEP-16:00 | 92.03 | 25-SEP-04:40 |
October | 2010.79 | 02-OCT-09:09 | 754.20 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1336.44 | 09-OCT-15:00 | 304.79 | 20-OCT-04:05 |
November | 2010.79 | 01-NOV-09:09 | 954.43 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 803.68 | 19-NOV-14:00 | 423.88 | 22-NOV-05:55 |
December | 2010.79 | 01-DEC-10:09 | 980.97 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 394.98 | 10-DEC-12:10 | 564.31 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 361.96 | 0.00 | |||||
Maximum of Months | 2010.79 | 1029.75 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5941.98 | 826.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 575.24 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 90.61 | 29-JAN-11:50 | 580.30 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 576.16 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 546.40 | 05-FEB-14:46 | 512.05 | 10-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 652.84 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 464.07 | 26-MAR-14:00 | 507.34 | 05-MAR-14:55 |
April | 1295.83 | 03-APR-09:09 | 491.83 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 709.17 | 30-APR-12:53 | 378.12 | 05-APR-00:55 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3961.30 | 21-MAY-13:00 | 118.49 | 02-MAY-02:55 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 972.45 | 11-JUN-13:14 | 88.59 | 07-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 393.10 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.84 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 351.77 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1389.50 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 351.77 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1057.03 | 03-SEP-16:00 | 64.94 | 25-SEP-04:40 |
October | 1295.83 | 02-OCT-09:09 | 377.11 | 27-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 893.49 | 09-OCT-15:23 | 213.27 | 20-OCT-04:05 |
November | 1295.83 | 01-NOV-09:09 | 631.69 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 525.68 | 05-NOV-15:05 | 285.33 | 22-NOV-05:55 |
December | 1295.83 | 01-DEC-10:09 | 639.71 | 14-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 224.70 | 10-DEC-12:50 | 373.44 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 90.61 | 0.00 | |||||
Maximum of Months | 1295.83 | 652.84 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 3961.30 | 580.30 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 749.42 | 23-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 101.20 | 23-JAN-13:00 | 961.99 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 829.14 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 738.83 | 05-FEB-15:00 | 864.52 | 10-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 1027.42 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 696.02 | 26-MAR-14:00 | 870.74 | 05-MAR-14:55 |
April | 2010.83 | 03-APR-09:09 | 850.12 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.52 | 30-APR-12:53 | 566.03 | 05-APR-00:55 |
May | 2010.83 | 01-MAY-09:09 | 545.88 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5941.97 | 21-MAY-13:00 | 170.33 | 01-MAY-04:50 |
June | 2010.83 | 01-JUN-09:09 | 586.96 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1462.26 | 11-JUN-13:14 | 124.85 | 07-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 743.84 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2233.26 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.83 | 01-AUG-09:09 | 590.02 | 29-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2084.25 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.83 | 01-SEP-09:09 | 607.78 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1585.54 | 03-SEP-16:00 | 99.28 | 25-SEP-04:40 |
October | 2010.83 | 02-OCT-09:09 | 602.63 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1336.44 | 09-OCT-15:00 | 347.75 | 20-OCT-04:05 |
November | 2010.83 | 01-NOV-09:09 | 826.34 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 728.74 | 19-NOV-13:44 | 452.35 | 22-NOV-05:55 |
December | 2010.83 | 01-DEC-10:09 | 916.80 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 270.26 | 10-DEC-12:37 | 599.38 | 17-DEC-14:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 101.20 | 0.00 | |||||
Maximum of Months | 2010.83 | 1027.42 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5941.97 | 961.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 542.75 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 185.47 | 29-JAN-11:45 | 615.59 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 513.36 | 09-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 544.43 | 05-FEB-14:44 | 563.65 | 10-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 666.86 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 464.03 | 26-MAR-14:00 | 585.44 | 05-MAR-14:55 |
April | 1295.83 | 03-APR-09:09 | 568.90 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 706.67 | 30-APR-12:53 | 411.21 | 05-APR-00:55 |
May | 1295.83 | 01-MAY-09:09 | 393.51 | 23-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3961.28 | 21-MAY-13:00 | 130.77 | 02-MAY-02:55 |
June | 1295.83 | 01-JUN-09:09 | 395.37 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 970.86 | 11-JUN-13:14 | 98.06 | 07-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 510.50 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.84 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 408.26 | 29-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1389.49 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 478.34 | 06-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1057.03 | 03-SEP-16:00 | 69.62 | 25-SEP-04:40 |
October | 1295.83 | 02-OCT-09:09 | 526.69 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 890.96 | 09-OCT-15:00 | 237.67 | 20-OCT-04:05 |
November | 1295.83 | 01-NOV-09:09 | 528.46 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 492.87 | 19-NOV-13:44 | 305.84 | 22-NOV-05:55 |
December | 1295.83 | 01-DEC-10:09 | 609.04 | 15-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 236.34 | 10-DEC-12:10 | 398.39 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 393.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 185.47 | 0.00 | |||||
Maximum of Months | 1295.83 | 666.86 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 3961.28 | 615.59 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 2868.67 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 2868.67 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 2868.67 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 2868.67 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 2868.67 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 2868.67 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 2868.67 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 2868.67 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 2868.67 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 2868.67 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 2868.67 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 2868.67 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.60 | 29-JAN-11:53 | 858.65 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.22 | 05-FEB-14:52 | 707.62 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.96 | 26-MAR-14:00 | 619.55 | 06-MAR-05:55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 728.29 | 30-APR-12:52 | 441.41 | 05-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4136.18 | 21-MAY-13:00 | 136.28 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 982.59 | 11-JUN-12:52 | 89.88 | 07-JUN-04:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1504.28 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1370.73 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1068.23 | 03-SEP-16:00 | 90.09 | 25-SEP-04:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 896.79 | 09-OCT-14:51 | 204.97 | 20-OCT-04:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 591.10 | 19-NOV-13:52 | 380.93 | 22-NOV-05:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.93 | 10-DEC-13:00 | 533.45 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.60 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4136.18 | 858.65 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.96 | 29-JAN-12:00 | 1393.51 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1139.36 | 05-FEB-14:42 | 1189.63 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 996.19 | 26-MAR-14:00 | 1061.28 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.78 | 30-APR-13:00 | 788.69 | 05-APR-00:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7394.35 | 21-MAY-13:00 | 226.48 | 01-MAY-04:52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1808.97 | 11-JUN-13:00 | 173.06 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2755.72 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2565.09 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1962.55 | 03-SEP-16:00 | 157.12 | 25-SEP-04:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1647.05 | 09-OCT-15:20 | 397.41 | 20-OCT-04:12 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1057.40 | 19-NOV-14:00 | 668.65 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.77 | 10-DEC-12:50 | 907.88 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.96 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7394.35 | 1393.51 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.37 | 29-JAN-11:53 | 1385.70 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1021.18 | 05-FEB-15:00 | 1161.76 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 854.46 | 26-MAR-14:00 | 1253.02 | 05-MAR-15:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1276.07 | 30-APR-13:00 | 820.24 | 05-APR-00:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7281.27 | 21-MAY-13:00 | 259.57 | 01-MAY-04:52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1741.61 | 11-JUN-13:00 | 172.55 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2829.34 | 30-JUL-14:10 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2556.23 | 13-AUG-14:10 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1934.67 | 04-SEP-14:00 | 174.31 | 25-SEP-04:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1657.75 | 09-OCT-15:00 | 457.63 | 20-OCT-04:14 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 948.15 | 19-NOV-14:00 | 641.28 | 22-NOV-05:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.85 | 10-DEC-12:13 | 898.70 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.37 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7281.27 | 1385.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 101139.44 | 02-JAN-05:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 104102.18 | 13-FEB-05:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 102406.89 | 06-MAR-05:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 98746.84 | 24-APR-04:21 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89870.23 | 10-MAY-04:03 | 0.00 | 4521.71 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 81633.35 | 30-JUN-03:02 | 0.00 | 2826.07 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 95194.62 | 03-JUL-03:02 | 0.00 | 3391.28 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88885.22 | 06-AUG-10:58 | 7180.90 | 4521.71 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85608.02 | 26-SEP-03:02 | 0.00 | 2826.07 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 101039.83 | 29-OCT-13:46 | 6283.29 | 3956.50 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98863.50 | 05-NOV-11:50 | 5385.68 | 3391.28 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 101702.37 | 18-DEC-05:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 81633.35 | 0.00 | 2826.07 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 104102.18 | 7180.90 | 4521.71 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 96024.33 | 02-JAN-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 97158.39 | 21-FEB-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 93657.41 | 06-MAR-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89107.26 | 05-APR-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84745.54 | 01-MAY-05:05 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84718.29 | 05-JUN-05:03 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 86720.14 | 31-JUL-05:05 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88513.52 | 07-AUG-05:05 | 12897.91 | 4298.88 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84560.77 | 01-SEP-05:05 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 85706.30 | 10-OCT-05:03 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 95040.14 | 27-NOV-05:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 93894.01 | 18-DEC-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 84560.77 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 97158.39 | 12897.91 | 4298.88 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 81097.61 | 02-JAN-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82689.96 | 21-FEB-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 83884.77 | 06-MAR-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 83367.08 | 05-APR-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78219.88 | 04-MAY-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 65245.88 | 26-JUN-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 68209.13 | 10-JUL-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 74170.61 | 07-AUG-05:04 | 12897.91 | 4298.88 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74173.71 | 05-SEP-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 77375.74 | 21-OCT-04:12 | 0.00 | 3045.61 | 26719.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84435.26 | 27-NOV-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 83088.23 | 04-DEC-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 65245.88 | 0.00 | 2686.80 | 26719.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84435.26 | 12897.91 | 4298.88 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 79048.14 | 30-JAN-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82719.51 | 08-FEB-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 83418.98 | 24-MAR-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 83654.06 | 10-APR-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79953.82 | 03-MAY-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 77506.76 | 19-JUN-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83597.62 | 17-JUL-05:05 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84971.98 | 07-AUG-05:04 | 12897.91 | 4298.88 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83754.61 | 05-SEP-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 81191.16 | 20-OCT-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84586.75 | 13-NOV-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 83716.49 | 11-DEC-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 77506.76 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84971.98 | 12897.91 | 4298.88 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13702.69 | 30-JAN-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.91 |
February | 14667.75 | 09-FEB-05:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.21 |
March | 18792.81 | 26-MAR-14:52 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.68 | 0.00 |
April | 16761.57 | 24-APR-04:21 | 0.00 | 472.30 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 |
May | 21718.72 | 21-MAY-13:12 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1522.64 | 0.00 |
June | 23234.86 | 11-JUN-15:01 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 430.70 | 0.00 |
July | 23711.19 | 04-JUL-15:51 | 910.95 | 272.92 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 389.53 | 0.00 |
August | 22688.63 | 06-AUG-15:01 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 446.45 | 0.00 |
September | 22293.72 | 10-SEP-16:21 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 304.34 | 0.00 |
October | 19652.71 | 22-OCT-14:32 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.66 | 0.00 |
November | 17803.47 | 05-NOV-14:52 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.55 | 0.00 |
December | 13820.86 | 12-DEC-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13702.69 | 0.00 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23711.19 | 1012.16 | 472.30 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 1522.64 | 60.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9324.60 | 30-JAN-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.28 |
February | 8288.44 | 06-FEB-06:03 | 521.82 | 173.92 | 2475.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 |
March | 15934.54 | 26-MAR-14:52 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 142.46 | 0.00 |
April | 18408.53 | 30-APR-11:02 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 84.35 | 0.00 |
May | 18743.82 | 14-MAY-09:12 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 79.72 | 0.00 |
June | 19408.12 | 11-JUN-15:01 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 288.31 | 0.00 |
July | 19808.48 | 04-JUL-15:11 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 249.91 | 0.00 |
August | 18709.05 | 06-AUG-15:01 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 302.54 | 0.00 |
September | 18649.95 | 10-SEP-16:21 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 203.25 | 0.00 |
October | 18150.59 | 09-OCT-09:02 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 22.72 | 0.00 |
November | 14732.45 | 05-NOV-14:52 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 162.97 | 0.00 |
December | 5745.99 | 04-DEC-10:10 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5745.99 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19808.48 | 2591.66 | 703.55 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 302.54 | 12.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19282.14 | 30-JAN-05:12 | 0.00 | 404.83 | 4473.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.88 |
February | 24993.42 | 05-FEB-12:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 177.68 | 0.00 |
March | 25222.92 | 26-MAR-14:52 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 184.07 | 0.00 |
April | 24155.11 | 30-APR-11:02 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 131.31 | 0.00 |
May | 24330.67 | 21-MAY-13:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1523.99 | 0.00 |
June | 25748.94 | 11-JUN-15:01 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 438.78 | 0.00 |
July | 26294.89 | 04-JUL-15:11 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 378.96 | 0.00 |
August | 25448.41 | 06-AUG-15:01 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 446.16 | 0.00 |
September | 26014.88 | 10-SEP-13:42 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 272.40 | 0.00 |
October | 25926.74 | 22-OCT-14:32 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 162.67 | 0.00 |
November | 26522.38 | 05-NOV-12:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 113.49 | 0.00 |
December | 26170.58 | 03-DEC-12:52 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 14.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19282.14 | 0.00 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26522.38 | 910.97 | 404.83 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1523.99 | 42.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18391.63 | 30-JAN-05:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.10 |
February | 20390.53 | 27-FEB-05:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.17 |
March | 25143.01 | 26-MAR-14:52 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 115.78 | 0.00 |
April | 24621.73 | 23-APR-16:22 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 125.47 | 0.00 |
May | 24455.53 | 14-MAY-17:52 | 0.00 | 117.25 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 129.98 | 0.00 |
June | 27017.70 | 11-JUN-15:01 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 258.01 | 0.00 |
July | 28003.13 | 04-JUL-15:51 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.79 | 0.00 |
August | 26770.34 | 06-AUG-15:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 242.50 | 0.00 |
September | 25809.81 | 10-SEP-16:21 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 179.98 | 0.00 |
October | 24953.49 | 22-OCT-14:32 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 114.39 | 0.00 |
November | 25282.40 | 05-NOV-15:32 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 117.96 | 0.00 |
December | 23754.03 | 03-DEC-14:12 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18391.63 | 0.00 | 97.71 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28003.13 | 587.05 | 260.89 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.01 | 65.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5025.98 | 23-JAN-14:10 | 4021.58 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.59 | 0.00 |
February | 10306.06 | 09-FEB-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.10 |
March | 16046.75 | 26-MAR-14:52 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 495.24 | 0.00 |
April | 17750.13 | 23-APR-15:31 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 564.67 | 0.00 |
May | 23075.50 | 21-MAY-13:12 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 3392.12 | 0.00 |
June | 22384.54 | 11-JUN-15:12 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.31 | 0.00 |
July | 23091.14 | 30-JUL-14:22 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1726.08 | 0.00 |
August | 22969.61 | 06-AUG-15:01 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1041.29 | 0.00 |
September | 23726.29 | 03-SEP-16:51 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 993.44 | 0.00 |
October | 23051.56 | 09-OCT-14:51 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 996.60 | 0.00 |
November | 14233.36 | 20-NOV-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 34.48 | 0.00 |
December | 11328.71 | 12-DEC-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5025.98 | 607.30 | 181.95 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23726.29 | 4021.58 | 1091.73 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 3392.12 | 21.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6230.59 | 24-JAN-11:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 |
February | 11466.08 | 05-FEB-14:52 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 402.12 | 0.00 |
March | 18955.03 | 26-MAR-14:52 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 325.87 | 0.00 |
April | 20228.74 | 23-APR-10:12 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 158.11 | 0.00 |
May | 20235.10 | 28-MAY-09:32 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 113.39 | 0.00 |
June | 19633.35 | 11-JUN-09:52 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 584.55 | 0.00 |
July | 20393.33 | 30-JUL-09:42 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 517.70 | 0.00 |
August | 19998.99 | 06-AUG-15:01 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 696.20 | 0.00 |
September | 21645.37 | 04-SEP-10:11 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 449.98 | 0.00 |
October | 20355.19 | 09-OCT-14:51 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 652.71 | 0.00 |
November | 14053.38 | 05-NOV-10:32 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 119.48 | 0.00 |
December | 7642.41 | 12-DEC-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6230.59 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21645.37 | 2478.65 | 703.55 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 696.20 | 14.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17122.49 | 30-JAN-06:02 | 1012.19 | 337.36 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.54 |
February | 26560.00 | 05-FEB-13:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 405.71 | 0.00 |
March | 25828.85 | 26-MAR-13:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 436.18 | 0.00 |
April | 24209.22 | 23-APR-15:31 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 561.11 | 0.00 |
May | 25708.17 | 21-MAY-13:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 3402.65 | 0.00 |
June | 24663.89 | 11-JUN-15:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1090.80 | 0.00 |
July | 25786.62 | 30-JUL-14:22 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1725.99 | 0.00 |
August | 25689.22 | 06-AUG-15:01 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.43 | 0.00 |
September | 27091.81 | 03-SEP-16:51 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 954.88 | 0.00 |
October | 28153.27 | 09-OCT-13:31 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 693.32 | 0.00 |
November | 26717.40 | 12-NOV-13:22 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 149.27 | 0.00 |
December | 25385.95 | 25-DEC-14:53 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17122.49 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28153.27 | 1012.19 | 337.36 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 3402.65 | 26.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9069.63 | 30-JAN-06:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.56 |
February | 19122.42 | 05-FEB-15:32 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 378.01 | 0.00 |
March | 21985.03 | 26-MAR-14:52 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 291.36 | 0.00 |
April | 21977.28 | 23-APR-16:11 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 310.89 | 0.00 |
May | 23541.98 | 28-MAY-16:51 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 319.60 | 0.00 |
June | 22253.56 | 18-JUN-16:02 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 541.62 | 0.00 |
July | 22797.09 | 30-JUL-15:02 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1078.99 | 0.00 |
August | 23119.44 | 06-AUG-15:01 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 665.58 | 0.00 |
September | 24511.51 | 03-SEP-16:51 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 587.93 | 0.00 |
October | 23885.91 | 09-OCT-15:31 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 582.97 | 0.00 |
November | 18760.19 | 19-NOV-14:32 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 287.54 | 0.00 |
December | 10931.91 | 12-DEC-06:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9069.63 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24511.51 | 652.28 | 217.40 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1078.99 | 17.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5231.47 | 23-JAN-14:10 | 4021.58 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.82 | 0.00 |
February | 10343.72 | 06-FEB-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.58 |
March | 17879.02 | 28-MAR-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 | 0.00 |
April | 24367.57 | 30-APR-16:11 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 539.65 | 0.00 |
May | 26291.72 | 21-MAY-13:12 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 4065.19 | 0.00 |
June | 25324.60 | 11-JUN-15:12 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1292.93 | 0.00 |
July | 26247.00 | 30-JUL-14:22 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 2092.76 | 0.00 |
August | 26166.06 | 06-AUG-15:01 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1261.51 | 0.00 |
September | 25666.96 | 04-SEP-15:02 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1323.10 | 0.00 |
October | 25627.89 | 09-OCT-12:41 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 802.22 | 0.00 |
November | 22457.13 | 05-NOV-15:02 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 669.25 | 0.00 |
December | 9344.02 | 11-DEC-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5231.47 | 607.30 | 181.95 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26291.72 | 4021.58 | 1091.73 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 4065.19 | 73.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5279.03 | 30-JAN-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 |
February | 13317.71 | 05-FEB-15:22 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 470.12 | 0.00 |
March | 14177.58 | 27-MAR-04:12 | 0.00 | 260.89 | 2882.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 |
April | 20898.28 | 30-APR-10:52 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 222.45 | 0.00 |
May | 21466.77 | 21-MAY-13:12 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 2682.20 | 0.00 |
June | 20471.58 | 11-JUN-09:52 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 712.83 | 0.00 |
July | 21409.21 | 30-JUL-14:22 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 1386.75 | 0.00 |
August | 21230.23 | 06-AUG-15:01 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 840.14 | 0.00 |
September | 20997.06 | 17-SEP-09:42 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 416.23 | 0.00 |
October | 21257.98 | 09-OCT-12:41 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 516.34 | 0.00 |
November | 19831.46 | 05-NOV-15:02 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 437.67 | 0.00 |
December | 7194.85 | 11-DEC-06:03 | 521.82 | 173.92 | 2475.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5279.03 | 0.00 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21466.77 | 652.28 | 260.89 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 2682.20 | 49.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17554.60 | 30-JAN-06:02 | 1012.19 | 337.36 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.80 |
February | 29040.37 | 05-FEB-14:02 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 535.05 | 0.00 |
March | 27557.32 | 26-MAR-12:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 262.42 | 0.00 |
April | 27698.55 | 30-APR-12:12 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 587.55 | 0.00 |
May | 28862.94 | 21-MAY-13:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.70 | 0.00 |
June | 27512.71 | 11-JUN-15:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1317.27 | 0.00 |
July | 28884.30 | 30-JUL-14:22 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 2092.17 | 0.00 |
August | 28871.69 | 13-AUG-14:21 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1865.58 | 0.00 |
September | 29101.07 | 04-SEP-14:22 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1361.33 | 0.00 |
October | 31081.45 | 09-OCT-12:41 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 682.43 | 0.00 |
November | 30099.24 | 05-NOV-12:22 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 344.78 | 0.00 |
December | 29055.55 | 03-DEC-13:02 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 55.25 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17554.60 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31081.45 | 1012.19 | 337.36 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.70 | 33.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9294.26 | 30-JAN-06:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.38 |
February | 20527.41 | 05-FEB-15:22 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 462.98 | 0.00 |
March | 18885.09 | 27-MAR-04:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.97 |
April | 23602.03 | 30-APR-16:11 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 320.91 | 0.00 |
May | 24407.58 | 21-MAY-15:52 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 910.94 | 0.00 |
June | 24207.31 | 18-JUN-16:02 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 655.69 | 0.00 |
July | 24965.51 | 30-JUL-15:02 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1307.09 | 0.00 |
August | 25509.31 | 06-AUG-15:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 713.34 | 0.00 |
September | 24900.80 | 04-SEP-15:42 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 835.34 | 0.00 |
October | 25501.85 | 01-OCT-15:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 312.12 | 0.00 |
November | 23961.05 | 05-NOV-15:02 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 381.61 | 0.00 |
December | 9997.30 | 11-DEC-06:03 | 521.82 | 173.92 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9294.26 | 0.00 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25509.31 | 652.28 | 260.89 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1307.09 | 50.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8859.21 | 30-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.63 |
February | 10228.45 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.14 |
March | 12592.14 | 27-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 |
April | 14821.81 | 24-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 |
May | 19038.92 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.80 | 0.00 |
June | 20467.83 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.48 | 0.00 |
July | 22083.26 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.22 | 0.00 |
August | 23919.31 | 07-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.39 | 0.00 |
September | 23085.54 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.05 | 0.00 |
October | 17810.79 | 10-OCT-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.40 | 0.00 |
November | 13839.17 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.29 |
December | 10343.44 | 11-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8859.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23919.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.39 | 65.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3716.05 | 30-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.53 |
February | 6335.25 | 06-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.15 | 0.00 |
March | 9348.26 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.76 | 0.00 |
April | 10365.48 | 24-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.05 |
May | 12875.15 | 30-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 | 0.00 |
June | 14181.69 | 09-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.32 | 0.00 |
July | 18493.94 | 17-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.19 | 0.00 |
August | 21458.83 | 07-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.22 | 0.00 |
September | 20036.36 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.56 | 0.00 |
October | 14319.53 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.08 | 0.00 |
November | 10224.13 | 06-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.38 |
December | 7119.10 | 11-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3716.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21458.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.76 | 116.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7903.56 | 23-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.21 | 0.00 |
February | 13158.22 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.72 | 0.00 |
March | 18765.54 | 27-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.12 | 0.00 |
April | 20935.77 | 28-APR-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 843.48 | 0.00 |
May | 23611.83 | 10-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.25 | 0.00 |
June | 24692.12 | 09-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 934.71 | 0.00 |
July | 26997.24 | 21-JUL-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 687.55 | 0.00 |
August | 27354.24 | 16-AUG-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.17 | 0.00 |
September | 24691.65 | 05-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 625.03 | 0.00 |
October | 19481.68 | 05-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.15 | 0.00 |
November | 15335.18 | 01-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.70 | 0.00 |
December | 10395.44 | 04-DEC-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7903.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.54 | 0.00 | |
Maximum of Months | 27354.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 934.71 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1886.41 | 29-JAN-17:35 | 23.38 | 16.26 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3828.57 | 05-FEB-17:17 | 46.77 | 32.52 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7194.04 | 31-MAR-24:00 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7809.23 | 02-APR-16:31 | 81.84 | 56.91 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3580.63 | 31-MAY-23:57 | 0.00 | 24.39 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5416.55 | 30-JUN-23:55 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7205.06 | 31-JUL-23:57 | 0.00 | 24.39 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7625.44 | 14-AUG-03:20 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3533.64 | 30-SEP-24:00 | 0.00 | 16.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5390.62 | 31-OCT-24:00 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5924.59 | 12-NOV-17:03 | 46.77 | 32.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7691.27 | 25-DEC-16:55 | 23.38 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1886.41 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7809.23 | 81.84 | 56.91 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1617.57 | 29-JAN-17:50 | 23.38 | 16.26 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3520.85 | 05-FEB-17:15 | 46.77 | 32.52 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6914.89 | 31-MAR-24:00 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7376.55 | 23-APR-17:46 | 0.00 | 40.65 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3458.82 | 31-MAY-23:57 | 0.00 | 24.39 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5216.28 | 30-JUN-23:55 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6881.40 | 31-JUL-23:23 | 0.00 | 24.39 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7133.64 | 14-AUG-03:23 | 0.00 | 24.39 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3399.86 | 30-SEP-23:40 | 0.00 | 16.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5215.74 | 31-OCT-24:00 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5527.88 | 12-NOV-17:03 | 46.77 | 32.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7135.77 | 03-DEC-17:07 | 35.07 | 24.39 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1617.57 | 0.00 | 16.26 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7376.55 | 46.77 | 40.65 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1673.99 | 29-JAN-17:35 | 23.38 | 16.26 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3642.51 | 05-FEB-17:05 | 46.77 | 32.52 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6858.79 | 31-MAR-24:00 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7540.34 | 02-APR-16:31 | 81.84 | 56.91 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3514.71 | 31-MAY-23:57 | 0.00 | 24.39 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5233.30 | 30-JUN-23:55 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6945.20 | 31-JUL-23:42 | 0.00 | 32.52 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7234.48 | 14-AUG-03:01 | 0.00 | 56.91 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3440.90 | 30-SEP-24:00 | 0.00 | 16.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5211.87 | 31-OCT-24:00 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5685.46 | 05-NOV-16:42 | 58.46 | 40.65 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7178.41 | 03-DEC-17:07 | 35.07 | 24.39 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1673.99 | 0.00 | 16.26 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7540.34 | 81.84 | 56.91 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92806.15 | 02-JAN-17:00 | 4808.68 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183758.50 | 06-FEB-17:00 | 4808.68 | 2868.67 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 359085.17 | 31-MAR-24:00 | 0.00 | 318.73 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 369213.88 | 30-APR-03:07 | 0.00 | 478.10 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176389.21 | 31-MAY-23:57 | 0.00 | 478.10 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267950.75 | 30-JUN-23:55 | 0.00 | 318.73 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 353031.08 | 31-JUL-23:23 | 0.00 | 478.10 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366441.34 | 15-AUG-07:10 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 177397.18 | 30-SEP-24:00 | 0.00 | 318.73 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269497.22 | 31-OCT-24:00 | 0.00 | 318.73 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277056.10 | 13-NOV-15:00 | 5027.92 | 2868.67 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 368803.88 | 06-DEC-22:02 | 1265.44 | 1593.66 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92806.15 | 0.00 | 318.73 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369213.88 | 5027.92 | 2868.67 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.156270E+13 | 1020199.40 | 30-JAN-13:00 | 0.544821E+11 | 69577.63 | 11-JAN-12:20 |
February | 0.181915E+13 | 1313186.38 | 07-FEB-16:10 | 0.485290E+11 | 69095.45 | 01-FEB-12:00 |
March | 0.252705E+13 | 1547152.06 | 27-MAR-15:20 | 0.533263E+11 | 65768.90 | 08-MAR-12:20 |
April | 0.293998E+13 | 1733120.64 | 28-APR-15:09 | 0.466078E+11 | 60171.21 | 07-APR-11:39 |
May | 0.207448E+13 | 1390458.22 | 31-MAY-15:00 | 0.459692E+11 | 54891.65 | 02-MAY-11:50 |
June | 0.261448E+13 | 1587689.60 | 12-JUN-15:09 | 0.428170E+11 | 47876.32 | 01-JUN-11:30 |
July | 0.320772E+13 | 1827780.65 | 19-JUL-15:09 | 0.416918E+11 | 43817.85 | 31-JUL-11:20 |
August | 0.372766E+13 | 2002811.35 | 10-AUG-15:30 | 0.447405E+11 | 49017.41 | 31-AUG-11:50 |
September | 0.219624E+13 | 1452654.05 | 07-SEP-15:20 | 0.441656E+11 | 56034.90 | 29-SEP-11:50 |
October | 0.246340E+13 | 1503228.66 | 06-OCT-15:39 | 0.487171E+11 | 62818.11 | 31-OCT-11:00 |
November | 0.255908E+13 | 1604613.97 | 01-NOV-15:09 | 0.504490E+11 | 67131.77 | 29-NOV-12:30 |
December | 0.281756E+13 | 1612410.93 | 05-DEC-16:40 | 0.530437E+11 | 68858.43 | 19-DEC-12:39 |
Annual Sum or Average | 0.305095E+14 | 0.574539E+12 | ||||
Minimum of Months | 0.156270E+13 | 1020199.40 | 0.416918E+11 | 43817.85 | ||
Maximum of Months | 0.372766E+13 | 2002811.35 | 0.544821E+11 | 69577.63 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.316604E+11 | 53648.50 | 28-JAN-12:30 | 0.00 | 0.00 |
February | 0.341585E+11 | 61428.35 | 23-FEB-13:30 | 0.00 | 0.00 |
March | 0.445117E+11 | 67873.92 | 31-MAR-11:30 | 0.00 | 0.00 |
April | 0.497739E+11 | 74992.41 | 30-APR-11:30 | 0.00 | 0.00 |
May | 0.565893E+11 | 80415.16 | 21-MAY-12:30 | 0.00 | 0.00 |
June | 0.567342E+11 | 73565.29 | 27-JUN-11:30 | 0.00 | 0.00 |
July | 0.562590E+11 | 76566.42 | 20-JUL-13:30 | 0.00 | 0.00 |
August | 0.539527E+11 | 72892.98 | 16-AUG-11:30 | 0.00 | 0.00 |
September | 0.476698E+11 | 64853.47 | 06-SEP-12:30 | 0.00 | 0.00 |
October | 0.422390E+11 | 60230.35 | 19-OCT-12:09 | 0.00 | 0.00 |
November | 0.336438E+11 | 51917.63 | 04-NOV-12:09 | 0.00 | 0.00 |
December | 0.293056E+11 | 51568.47 | 25-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.536498E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.293056E+11 | 51568.47 | 0.00 | 0.00 | |
Maximum of Months | 0.567342E+11 | 80415.16 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.144077E+12 | 0.268047E+11 | 0.766053E+12 | 0.102194E+12 | 0.169447E+12 | 0.457331E+11 | 0.00 | 0.199575E+12 | 0.106090E+12 | 0.273129E+10 | 0.00 | 0.00 | 0.00 |
February | 0.130100E+12 | 0.225596E+11 | 0.978954E+12 | 0.923108E+11 | 0.162016E+12 | 0.431985E+11 | 0.00 | 0.276404E+12 | 0.111029E+12 | 0.258314E+10 | 0.00 | 0.00 | 0.00 |
March | 0.154058E+12 | 0.227874E+11 | 0.141687E+13 | 0.102362E+12 | 0.198587E+12 | 0.573159E+11 | 0.00 | 0.442411E+12 | 0.131004E+12 | 0.165203E+10 | 0.00 | 0.00 | 0.00 |
April | 0.137193E+12 | 0.197952E+11 | 0.165903E+13 | 0.988820E+11 | 0.208856E+12 | 0.683848E+11 | 0.00 | 0.599827E+12 | 0.147370E+12 | 0.648728E+09 | 0.00 | 0.00 | 0.00 |
May | 0.147448E+12 | 0.186136E+11 | 0.774844E+12 | 0.102278E+12 | 0.253287E+12 | 0.844493E+11 | 0.00 | 0.508355E+12 | 0.185203E+12 | 6496020.80 | 0.00 | 0.00 | 0.00 |
June | 0.146477E+12 | 0.172664E+11 | 0.106252E+13 | 0.990391E+11 | 0.262995E+12 | 0.948128E+11 | 0.00 | 0.726608E+12 | 0.204762E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137524E+12 | 0.181963E+11 | 0.139340E+13 | 0.102120E+12 | 0.279431E+12 | 0.102265E+12 | 0.00 | 0.960983E+12 | 0.213796E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153171E+12 | 0.197205E+11 | 0.173200E+13 | 0.102362E+12 | 0.307118E+12 | 0.107500E+12 | 0.00 | 0.108503E+13 | 0.220751E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137314E+12 | 0.209526E+11 | 0.740713E+12 | 0.988811E+11 | 0.254718E+12 | 0.948873E+11 | 0.00 | 0.642086E+12 | 0.206687E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143121E+12 | 0.239508E+11 | 0.108340E+13 | 0.102194E+12 | 0.241280E+12 | 0.843565E+11 | 0.00 | 0.595258E+12 | 0.189769E+12 | 72223549.65 | 0.00 | 0.00 | 0.00 |
November | 0.142137E+12 | 0.253648E+11 | 0.135889E+13 | 0.989454E+11 | 0.207835E+12 | 0.665635E+11 | 0.00 | 0.510751E+12 | 0.148404E+12 | 0.193092E+09 | 0.00 | 0.00 | 0.00 |
December | 0.139708E+12 | 0.274576E+11 | 0.170972E+13 | 0.102120E+12 | 0.180561E+12 | 0.542577E+11 | 0.00 | 0.472259E+12 | 0.128402E+12 | 0.307726E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171233E+13 | 0.263470E+12 | 0.146764E+14 | 0.120369E+13 | 0.272613E+13 | 0.903725E+12 | 0.00 | 0.701955E+13 | 0.199327E+13 | 0.109643E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130100E+12 | 0.172664E+11 | 0.740713E+12 | 0.923108E+11 | 0.162016E+12 | 0.431985E+11 | 0.00 | 0.199575E+12 | 0.106090E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154058E+12 | 0.274576E+11 | 0.173200E+13 | 0.102362E+12 | 0.307118E+12 | 0.107500E+12 | 0.00 | 0.108503E+13 | 0.220751E+12 | 0.307726E+10 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 341130.67 | 0.00 | 0.544817E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 110665.30 | 0.00 | 0.485289E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.533263E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.466078E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.459692E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.428170E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.416918E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.447405E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.441656E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.487171E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 3307.88 | 0.00 | 0.504490E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 127659.05 | 0.00 | 0.530436E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 582762.90 | 0.00 | 0.574539E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.416918E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 341130.67 | 0.00 | 0.544817E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 155162.26 | 23-JAN-16:00 | 31088.59 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 73692.02 | 09-JAN-08:20 | 115520.13 | 23-JAN-13:30 | 27533.32 | 30-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 157827.72 | 09-FEB-16:00 | 31088.59 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 73691.29 | 09-FEB-08:20 | 157638.18 | 06-FEB-15:09 | 50170.52 | 06-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 164979.26 | 15-MAR-07:10 | 31088.59 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 73698.15 | 15-MAR-07:19 | 199222.94 | 27-MAR-14:50 | 52104.53 | 23-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 157541.36 | 18-APR-07:10 | 31088.59 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 73694.25 | 18-APR-07:19 | 201110.61 | 28-APR-15:20 | 51938.83 | 24-APR-15:50 | 0.00 | 01-APR-00:10 |
May | 146529.51 | 23-MAY-07:10 | 31088.59 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 73688.47 | 23-MAY-07:19 | 221798.95 | 30-MAY-15:30 | 53721.81 | 11-MAY-09:20 | 0.00 | 01-MAY-00:10 |
June | 147016.92 | 08-JUN-07:10 | 31088.59 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 73688.73 | 08-JUN-07:19 | 232113.40 | 09-JUN-15:20 | 52063.19 | 15-JUN-16:40 | 0.00 | 01-JUN-00:10 |
July | 151847.86 | 20-JUL-07:10 | 31088.59 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 73691.26 | 20-JUL-07:19 | 255231.12 | 31-JUL-15:39 | 54068.20 | 05-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 147796.69 | 29-AUG-07:10 | 31088.59 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 73689.14 | 29-AUG-07:19 | 253808.05 | 07-AUG-15:20 | 54043.61 | 07-AUG-05:19 | 0.00 | 01-AUG-00:10 |
September | 149056.15 | 06-SEP-07:10 | 31088.59 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 73689.80 | 06-SEP-07:19 | 258011.30 | 05-SEP-15:50 | 53687.48 | 05-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 150606.23 | 31-OCT-07:10 | 31088.59 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 73690.61 | 31-OCT-07:19 | 212281.76 | 10-OCT-15:20 | 52460.54 | 20-OCT-13:50 | 0.00 | 01-OCT-00:10 |
November | 159193.86 | 29-NOV-16:00 | 31088.59 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 73690.81 | 29-NOV-08:20 | 182337.39 | 06-NOV-15:09 | 50505.74 | 01-NOV-14:09 | 0.00 | 01-NOV-00:10 |
December | 161681.18 | 15-DEC-16:00 | 31088.59 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 73696.03 | 15-DEC-08:20 | 144246.44 | 04-DEC-13:50 | 49671.87 | 04-DEC-11:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 146529.51 | 31088.59 | 423497.50 | 73688.47 | 115520.13 | 27533.32 | 0.00 | |||||||
Maximum of Months | 164979.26 | 31088.59 | 778371.69 | 73698.15 | 258011.30 | 54068.20 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 209477.32 | 30-JAN-13:00 | 84672.71 | 30-JAN-13:50 | 5534.88 | 01-JAN-05:00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 318428.02 | 07-FEB-13:30 | 84672.71 | 06-FEB-11:30 | 7073.18 | 15-FEB-05:00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 386311.43 | 27-MAR-12:09 | 84672.71 | 01-MAR-13:20 | 9848.97 | 08-MAR-05:00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 424458.88 | 26-APR-12:09 | 84672.71 | 30-APR-15:09 | 14347.79 | 26-APR-10:09 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 425230.12 | 31-MAY-15:00 | 84672.71 | 21-MAY-18:40 | 1440.04 | 07-MAY-10:00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 491527.73 | 12-JUN-14:09 | 84672.71 | 03-JUN-16:19 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 609238.14 | 19-JUL-14:00 | 84672.71 | 01-JUL-03:09 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 644365.65 | 10-AUG-15:30 | 84672.71 | 01-AUG-04:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 490129.85 | 07-SEP-14:09 | 84672.71 | 02-SEP-16:19 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 436325.39 | 06-OCT-15:00 | 84672.71 | 01-OCT-10:20 | 4480.72 | 29-OCT-12:00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 448313.51 | 01-NOV-14:09 | 84672.71 | 01-NOV-05:40 | 4195.02 | 22-NOV-06:00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 374675.99 | 05-DEC-16:40 | 84672.71 | 04-DEC-09:30 | 13671.17 | 18-DEC-05:00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 209477.32 | 84672.71 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Maximum of Months | 644365.65 | 84672.71 | 14347.79 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1020199.40 | 30-JAN-13:00 | 145987.23 | 423497.50 | 0.00 | 24458.17 | 105401.97 | 26704.51 | 0.00 | 209477.32 | 84672.71 |
February | 1313186.38 | 07-FEB-16:10 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 137944.04 | 49382.32 | 0.00 | 300821.59 | 84672.71 |
March | 1547152.06 | 27-MAR-15:20 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 198961.89 | 49989.88 | 0.00 | 354870.46 | 84672.71 |
April | 1733120.64 | 28-APR-15:09 | 145987.23 | 778371.69 | 0.00 | 52589.61 | 200560.35 | 49965.21 | 0.00 | 420973.86 | 84672.71 |
May | 1390458.22 | 31-MAY-15:00 | 145987.23 | 423497.50 | 0.00 | 52589.61 | 207356.12 | 51124.94 | 0.00 | 425230.12 | 84672.71 |
June | 1587689.60 | 12-JUN-15:09 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 225720.42 | 51509.06 | 0.00 | 485421.69 | 84672.71 |
July | 1827780.65 | 19-JUL-15:09 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 223625.16 | 52626.05 | 0.00 | 608199.61 | 84672.71 |
August | 2002811.35 | 10-AUG-15:30 | 145987.23 | 778371.69 | 0.00 | 52589.61 | 243891.57 | 52932.90 | 0.00 | 644365.65 | 84672.71 |
September | 1452654.05 | 07-SEP-15:20 | 145987.23 | 423497.50 | 0.00 | 52589.61 | 212857.39 | 51944.98 | 0.00 | 481104.64 | 84672.71 |
October | 1503228.66 | 06-OCT-15:39 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 192799.65 | 50719.30 | 0.00 | 434671.28 | 84672.71 |
November | 1604613.97 | 01-NOV-15:09 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 175676.78 | 50335.60 | 0.00 | 435271.76 | 84672.71 |
December | 1612410.93 | 05-DEC-16:40 | 148581.73 | 778371.69 | 0.00 | 52590.38 | 124197.58 | 49320.85 | 0.00 | 374675.99 | 84672.71 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1020199.40 | 145987.23 | 423497.50 | 0.00 | 24458.17 | 105401.97 | 26704.51 | 0.00 | 209477.32 | 84672.71 | |
Maximum of Months | 2002811.35 | 148581.73 | 778371.69 | 0.00 | 52590.38 | 243891.57 | 52932.90 | 0.00 | 644365.65 | 84672.71 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 92.32 | 19-JAN-06:40 | 0.00 | 69577.63 | 11-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 65.24 | 13-FEB-06:19 | 0.00 | 69095.45 | 01-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 65768.90 | 08-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 60171.21 | 07-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 54891.65 | 02-MAY-11:50 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 47876.32 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 43817.85 | 31-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 49017.41 | 31-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 56034.90 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 62818.11 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 5.51 | 21-NOV-08:39 | 0.00 | 67131.77 | 29-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 58.47 | 18-DEC-06:49 | 0.00 | 68858.43 | 19-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 43817.85 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 92.32 | 0.00 | 69577.63 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.23 | 2.00 | 27.25 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.18 | 2.33 | 27.17 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.70 | 0.00 | 26.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.85 | 0.00 | 26.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.50 | 0.17 | 26.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.05 | 0.00 | 26.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.22 | 0.67 | 26.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 25.79 | 0.83 | 25.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.32 | 0.33 | 26.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 26.39 | 0.00 | 26.39 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 26.86 | 0.67 | 26.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.16 | 3.67 | 27.17 |
Annual Sum or Average | 0.00 | 0.00 | 101.83 | 26.68 | 10.67 | 26.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 25.79 | 0.00 | 25.78 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.23 | 3.67 | 27.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 25.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 25.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.69 | 0.00 | 25.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.75 | 0.00 | 25.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.60 | 0.00 | 25.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.74 | 0.00 | 25.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 25.66 | 0.50 | 25.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.68 | 0.00 | 25.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.63 | 0.00 | 25.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.63 | 0.00 | 25.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
Annual Sum or Average | 0.00 | 0.00 | 13.83 | 25.66 | 0.50 | 25.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 25.75 | 0.50 | 25.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.64 | 0.00 | 25.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.60 | 0.00 | 25.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.63 | 0.00 | 25.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.66 | 0.00 | 25.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.50 | 25.63 | 0.00 | 25.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.66 | 0.00 | 25.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.62 | 0.00 | 25.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.14 | 3.33 | 27.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.22 | 9.00 | 27.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 27.09 | 9.67 | 27.25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 47.17 | 27.33 | 16.33 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 56.83 | 27.27 | 16.00 | 27.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.14 | 9.50 | 27.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.14 | 6.33 | 27.28 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 181.17 | 27.23 | 70.17 | 27.35 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 56.83 | 27.33 | 16.33 | 27.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.33 | 0.67 | 27.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.43 | 2.00 | 27.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.48 | 8.67 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 27.49 | 12.00 | 27.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 27.26 | 10.83 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 27.45 | 16.83 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 41.33 | 27.28 | 12.83 | 27.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 27.39 | 12.50 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.48 | 13.33 | 27.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.35 | 2.83 | 27.35 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 192.83 | 27.39 | 92.50 | 27.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 27.49 | 16.83 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.38 | 4.67 | 27.38 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.57 | 4.50 | 27.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.32 | 3.67 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.32 | 8.00 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.25 | 8.83 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 27.05 | 9.00 | 27.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 45.17 | 27.32 | 15.33 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 60.17 | 27.32 | 17.00 | 27.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 29.17 | 27.30 | 11.17 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 27.47 | 12.83 | 27.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.68 | 12.00 | 27.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.63 | 7.83 | 27.63 |
Annual Sum or Average | 0.00 | 0.00 | 246.50 | 27.34 | 114.83 | 27.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.05 | 3.67 | 27.23 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 60.17 | 27.68 | 17.00 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.45 | 1.50 | 27.45 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.31 | 4.00 | 27.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 27.17 | 7.33 | 27.33 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 56.33 | 27.61 | 18.50 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 | 27.40 | 14.17 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 75.33 | 27.54 | 19.83 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 88.00 | 27.92 | 26.00 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 82.83 | 28.28 | 25.00 | 28.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 57.00 | 27.46 | 16.50 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 51.50 | 27.39 | 15.83 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 27.34 | 14.33 | 27.48 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 27.23 | 11.33 | 27.38 |
Annual Sum or Average | 0.00 | 0.00 | 536.17 | 27.65 | 174.33 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.17 | 1.50 | 27.33 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 88.00 | 28.28 | 26.00 | 28.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.38 | 2.50 | 27.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.31 | 9.17 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 27.09 | 9.00 | 27.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 27.33 | 15.67 | 27.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 | 27.19 | 11.00 | 27.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 27.18 | 9.67 | 27.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.28 | 6.17 | 27.37 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 158.67 | 27.24 | 63.17 | 27.38 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 27.38 | 15.67 | 27.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.29 | 0.67 | 27.29 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.41 | 2.00 | 27.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.62 | 10.83 | 27.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 27.49 | 12.83 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 27.28 | 10.83 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 54.67 | 27.54 | 17.67 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 48.83 | 27.39 | 13.50 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 27.38 | 12.67 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.49 | 13.67 | 27.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.39 | 5.50 | 27.39 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 234.17 | 27.44 | 100.17 | 27.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 54.67 | 27.62 | 17.67 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.40 | 2.83 | 27.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.67 | 3.17 | 27.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.43 | 3.17 | 27.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.50 | 7.00 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.32 | 9.00 | 27.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 27.05 | 8.33 | 27.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 27.31 | 14.50 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 | 27.26 | 11.50 | 27.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 27.29 | 11.67 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.47 | 12.67 | 27.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.78 | 11.67 | 27.83 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.61 | 6.00 | 27.61 |
Annual Sum or Average | 0.00 | 0.00 | 219.00 | 27.35 | 101.50 | 27.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.05 | 2.83 | 27.24 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 27.78 | 14.50 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.59 | 1.00 | 27.59 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.25 | 2.17 | 27.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.50 | 7.33 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 | 27.38 | 11.50 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 | 27.35 | 10.83 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 72.67 | 27.59 | 21.17 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 69.50 | 27.55 | 18.17 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 | 27.37 | 12.33 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.26 | 10.17 | 27.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.53 | 6.00 | 27.58 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
Annual Sum or Average | 0.00 | 0.00 | 315.33 | 27.46 | 101.00 | 27.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 72.67 | 27.59 | 21.17 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.99 | 0.67 | 27.13 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.51 | 3.83 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 27.50 | 10.33 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 27.29 | 9.50 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 55.67 | 27.49 | 17.17 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 27.37 | 12.17 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 27.39 | 10.50 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.44 | 8.50 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.33 | 0.83 | 27.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 198.33 | 27.41 | 73.50 | 27.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 55.67 | 27.51 | 17.17 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.36 | 0.83 | 27.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.40 | 2.00 | 27.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.70 | 10.83 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 27.64 | 13.00 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 34.83 | 27.43 | 10.83 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 62.83 | 27.67 | 19.50 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 58.00 | 27.51 | 15.33 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 | 27.54 | 13.17 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 27.61 | 13.67 | 27.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.42 | 6.17 | 27.42 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 265.67 | 27.57 | 105.33 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 62.83 | 27.70 | 19.50 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.40 | 2.00 | 27.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.76 | 2.67 | 27.78 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.52 | 3.17 | 27.60 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.62 | 8.00 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 27.48 | 10.17 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 27.27 | 8.83 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 27.48 | 16.67 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 | 27.41 | 13.17 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 34.83 | 27.46 | 11.67 | 27.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 27.59 | 13.17 | 27.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.86 | 11.17 | 27.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.62 | 4.83 | 27.62 |
Annual Sum or Average | 0.00 | 0.00 | 252.00 | 27.49 | 105.50 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.27 | 2.00 | 27.40 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 27.86 | 16.67 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.67 | 1.17 | 27.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.36 | 2.50 | 27.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.58 | 8.00 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 37.83 | 27.55 | 12.50 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 45.33 | 27.46 | 11.17 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 76.00 | 27.71 | 21.50 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 71.50 | 27.66 | 19.00 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 27.48 | 13.17 | 27.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 27.45 | 10.67 | 27.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.63 | 6.50 | 27.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
Annual Sum or Average | 0.00 | 0.00 | 333.17 | 27.58 | 106.50 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 76.00 | 27.71 | 21.50 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 28.01 | 24.00 | 28.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.72 | 0.00 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 718.33 | 28.61 | 492.67 | 28.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 745.50 | 28.59 | 516.67 | 28.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 718.33 | 28.61 | 492.67 | 28.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 27.93 | 20.50 | 27.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.80 | 0.00 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 636.83 | 28.32 | 433.67 | 28.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 659.83 | 28.30 | 454.17 | 28.36 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 636.83 | 28.32 | 433.67 | 28.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 27.98 | 21.67 | 27.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.76 | 0.00 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 614.67 | 28.39 | 420.50 | 28.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 639.50 | 28.37 | 442.17 | 28.42 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 614.67 | 28.39 | 420.50 | 28.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 397.83 | 28.85 | 327.33 | 28.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 29.13 | 0.00 | 29.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 31.82 | 514.00 | 31.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 86.67 | 27.93 | 84.83 | 27.93 |
Annual Sum or Average | 0.00 | 0.00 | 1228.67 | 30.58 | 926.17 | 30.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 31.82 | 514.00 | 31.93 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.50 | 24.00 | 432.00 | 24.66 | 10.50 | 24.65 |
February | 74.33 | 24.69 | 430.33 | 24.61 | 74.33 | 24.62 |
March | 101.17 | 24.32 | 463.00 | 24.46 | 101.17 | 24.44 |
April | 181.33 | 24.78 | 439.67 | 24.65 | 181.33 | 24.68 |
May | 211.00 | 24.57 | 476.17 | 24.56 | 211.00 | 24.56 |
June | 353.33 | 24.68 | 493.33 | 24.56 | 353.33 | 24.60 |
July | 287.17 | 24.86 | 497.00 | 24.71 | 287.17 | 24.75 |
August | 206.00 | 25.13 | 514.00 | 24.67 | 206.00 | 24.77 |
September | 264.83 | 25.05 | 485.00 | 24.74 | 264.83 | 24.82 |
October | 144.00 | 25.21 | 489.17 | 24.77 | 144.00 | 24.85 |
November | 93.83 | 25.06 | 483.83 | 24.71 | 93.83 | 24.75 |
December | 83.50 | 25.73 | 479.83 | 24.81 | 83.50 | 24.93 |
Annual Sum or Average | 2011.00 | 24.88 | 5683.33 | 24.66 | 2011.00 | 24.70 |
Minimum of Months | 10.50 | 24.00 | 430.33 | 24.46 | 10.50 | 24.44 |
Maximum of Months | 353.33 | 25.73 | 514.00 | 24.81 | 353.33 | 24.93 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 412.33 | 24.45 | 0.00 | 24.45 |
February | 0.17 | 27.06 | 428.33 | 24.40 | 0.17 | 24.40 |
March | 0.00 | 0.00 | 474.17 | 24.29 | 0.00 | 24.29 |
April | 0.00 | 0.00 | 466.83 | 24.22 | 0.00 | 24.22 |
May | 0.00 | 0.00 | 488.00 | 24.20 | 0.00 | 24.20 |
June | 0.00 | 0.00 | 496.00 | 24.20 | 0.00 | 24.20 |
July | 0.00 | 0.00 | 497.00 | 24.27 | 0.00 | 24.27 |
August | 0.00 | 0.00 | 514.00 | 24.28 | 0.00 | 24.28 |
September | 0.00 | 0.00 | 485.00 | 24.22 | 0.00 | 24.22 |
October | 0.00 | 0.00 | 490.67 | 24.27 | 0.00 | 24.27 |
November | 0.00 | 0.00 | 483.17 | 24.33 | 0.00 | 24.33 |
December | 0.00 | 0.00 | 476.83 | 24.38 | 0.00 | 24.38 |
Annual Sum or Average | 0.17 | 27.06 | 5712.33 | 24.29 | 0.17 | 24.29 |
Minimum of Months | 0.00 | 0.00 | 412.33 | 24.20 | 0.00 | 24.20 |
Maximum of Months | 0.17 | 27.06 | 514.00 | 24.45 | 0.17 | 24.45 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.17 | 23.96 | 307.00 | 24.22 | 13.50 | 24.26 |
February | 8.17 | 23.60 | 372.00 | 24.26 | 0.00 | 24.26 |
March | 1.50 | 23.59 | 406.83 | 24.28 | 0.00 | 24.28 |
April | 2.83 | 23.82 | 433.67 | 24.25 | 0.00 | 24.25 |
May | 0.00 | 0.00 | 475.67 | 24.15 | 0.00 | 24.15 |
June | 0.00 | 0.00 | 493.67 | 24.09 | 0.00 | 24.09 |
July | 0.00 | 0.00 | 496.50 | 24.10 | 0.00 | 24.10 |
August | 0.00 | 0.00 | 514.00 | 24.10 | 0.00 | 24.10 |
September | 0.00 | 0.00 | 485.00 | 24.14 | 0.00 | 24.14 |
October | 0.00 | 0.00 | 485.17 | 24.24 | 0.00 | 24.24 |
November | 0.00 | 0.00 | 481.17 | 24.29 | 0.00 | 24.29 |
December | 11.67 | 23.51 | 413.50 | 24.23 | 0.00 | 24.23 |
Annual Sum or Average | 78.33 | 23.84 | 5364.17 | 24.19 | 13.50 | 24.19 |
Minimum of Months | 0.00 | 0.00 | 307.00 | 24.09 | 0.00 | 24.09 |
Maximum of Months | 54.17 | 23.96 | 514.00 | 24.29 | 13.50 | 24.29 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 172.67 | 23.32 | 206.17 | 23.72 | 13.33 | 23.71 |
February | 73.67 | 23.34 | 301.00 | 24.03 | 0.00 | 24.03 |
March | 23.33 | 23.46 | 385.67 | 24.21 | 0.00 | 24.21 |
April | 0.00 | 0.00 | 434.83 | 24.28 | 0.00 | 24.28 |
May | 0.00 | 0.00 | 485.50 | 24.23 | 0.00 | 24.23 |
June | 0.00 | 0.00 | 496.00 | 24.17 | 0.00 | 24.17 |
July | 0.00 | 0.00 | 497.00 | 24.23 | 0.00 | 24.23 |
August | 0.17 | 26.59 | 514.00 | 24.19 | 0.17 | 24.19 |
September | 0.33 | 26.63 | 485.00 | 24.23 | 0.33 | 24.23 |
October | 0.00 | 0.00 | 488.17 | 24.29 | 0.00 | 24.29 |
November | 0.00 | 0.00 | 474.50 | 24.27 | 0.00 | 24.27 |
December | 73.17 | 23.33 | 334.50 | 24.01 | 0.00 | 24.01 |
Annual Sum or Average | 343.33 | 23.34 | 5102.33 | 24.17 | 13.83 | 24.17 |
Minimum of Months | 0.00 | 0.00 | 206.17 | 23.72 | 0.00 | 23.71 |
Maximum of Months | 172.67 | 26.63 | 514.00 | 24.29 | 13.33 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 93.67 | 23.38 | 258.00 | 24.02 | 0.00 | 24.02 |
February | 31.17 | 23.38 | 357.50 | 24.22 | 0.00 | 24.22 |
March | 8.33 | 23.76 | 441.50 | 24.27 | 0.50 | 24.27 |
April | 15.50 | 26.83 | 470.50 | 24.47 | 15.50 | 24.54 |
May | 40.00 | 26.86 | 506.50 | 24.67 | 40.00 | 24.82 |
June | 45.00 | 26.89 | 496.00 | 24.69 | 45.00 | 24.86 |
July | 84.00 | 26.89 | 497.00 | 24.98 | 84.00 | 25.22 |
August | 80.50 | 26.90 | 514.00 | 24.86 | 80.50 | 25.10 |
September | 46.33 | 26.85 | 485.00 | 24.72 | 46.33 | 24.89 |
October | 33.67 | 26.81 | 496.50 | 24.64 | 33.67 | 24.77 |
November | 1.50 | 27.04 | 483.50 | 24.39 | 1.50 | 24.40 |
December | 15.33 | 23.58 | 416.33 | 24.26 | 0.00 | 24.26 |
Annual Sum or Average | 495.00 | 25.84 | 5422.33 | 24.56 | 347.00 | 24.68 |
Minimum of Months | 1.50 | 23.38 | 258.00 | 24.02 | 0.00 | 24.02 |
Maximum of Months | 93.67 | 27.04 | 514.00 | 24.98 | 84.00 | 25.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 66.33 | 23.43 | 316.83 | 24.20 | 1.00 | 24.21 |
February | 29.00 | 23.77 | 384.83 | 24.31 | 3.67 | 24.33 |
March | 17.17 | 24.41 | 447.00 | 24.31 | 4.67 | 24.33 |
April | 37.17 | 26.86 | 467.83 | 24.60 | 37.17 | 24.76 |
May | 54.50 | 26.95 | 507.83 | 24.77 | 54.50 | 24.97 |
June | 47.83 | 26.96 | 496.00 | 24.72 | 47.83 | 24.90 |
July | 82.17 | 26.97 | 497.00 | 24.99 | 82.17 | 25.24 |
August | 71.67 | 26.94 | 514.00 | 24.83 | 71.67 | 25.06 |
September | 55.67 | 26.96 | 485.00 | 24.81 | 55.67 | 25.01 |
October | 53.00 | 26.90 | 499.33 | 24.77 | 53.00 | 24.95 |
November | 17.83 | 26.81 | 485.17 | 24.53 | 17.83 | 24.61 |
December | 22.00 | 23.32 | 411.33 | 24.23 | 0.00 | 24.23 |
Annual Sum or Average | 554.33 | 26.13 | 5512.17 | 24.62 | 429.17 | 24.77 |
Minimum of Months | 17.17 | 23.32 | 316.83 | 24.20 | 0.00 | 24.21 |
Maximum of Months | 82.17 | 26.97 | 514.00 | 24.99 | 82.17 | 25.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 59.00 | 24.22 | 374.67 | 24.46 | 15.00 | 24.54 |
February | 39.67 | 24.94 | 402.33 | 24.50 | 17.33 | 24.59 |
March | 23.00 | 25.76 | 465.33 | 24.43 | 15.17 | 24.51 |
April | 32.67 | 26.87 | 473.67 | 24.59 | 32.67 | 24.73 |
May | 38.83 | 26.88 | 506.33 | 24.67 | 38.83 | 24.82 |
June | 40.50 | 26.88 | 496.00 | 24.66 | 40.50 | 24.81 |
July | 78.17 | 26.89 | 497.00 | 24.95 | 78.17 | 25.18 |
August | 83.33 | 26.91 | 514.00 | 24.88 | 83.33 | 25.13 |
September | 55.17 | 26.95 | 485.00 | 24.82 | 55.17 | 25.02 |
October | 57.17 | 27.00 | 502.00 | 24.85 | 57.17 | 25.05 |
November | 51.83 | 26.95 | 488.33 | 24.79 | 51.83 | 24.98 |
December | 44.17 | 26.26 | 465.00 | 24.64 | 36.00 | 24.78 |
Annual Sum or Average | 603.50 | 26.43 | 5669.67 | 24.70 | 521.17 | 24.87 |
Minimum of Months | 23.00 | 24.22 | 374.67 | 24.43 | 15.00 | 24.51 |
Maximum of Months | 83.33 | 27.00 | 514.00 | 24.95 | 83.33 | 25.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.50 | 25.09 | 401.50 | 24.54 | 7.83 | 24.59 |
February | 23.67 | 26.93 | 439.83 | 24.69 | 23.67 | 24.80 |
March | 40.00 | 26.97 | 507.17 | 24.72 | 40.00 | 24.87 |
April | 95.50 | 26.93 | 485.00 | 25.02 | 95.50 | 25.29 |
May | 91.83 | 26.90 | 508.00 | 24.97 | 91.83 | 25.22 |
June | 96.33 | 26.91 | 496.00 | 24.96 | 96.33 | 25.23 |
July | 118.83 | 27.03 | 497.00 | 25.18 | 118.83 | 25.48 |
August | 102.67 | 27.14 | 514.00 | 25.05 | 102.67 | 25.35 |
September | 102.83 | 26.89 | 485.00 | 25.04 | 102.83 | 25.31 |
October | 103.67 | 26.90 | 502.00 | 25.06 | 103.67 | 25.33 |
November | 77.67 | 26.94 | 489.00 | 24.99 | 77.67 | 25.22 |
December | 60.00 | 26.94 | 495.00 | 24.91 | 60.00 | 25.11 |
Annual Sum or Average | 930.50 | 26.92 | 5819.50 | 24.94 | 920.83 | 25.19 |
Minimum of Months | 17.50 | 25.09 | 401.50 | 24.54 | 7.83 | 24.59 |
Maximum of Months | 118.83 | 27.14 | 514.00 | 25.18 | 118.83 | 25.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 301.17 | 22.99 | 111.83 | 23.28 | 0.00 | 23.28 |
February | 136.83 | 23.08 | 211.67 | 23.73 | 1.50 | 23.73 |
March | 65.00 | 23.25 | 355.67 | 24.09 | 0.00 | 24.09 |
April | 30.50 | 25.62 | 449.17 | 24.51 | 26.50 | 24.59 |
May | 44.33 | 26.84 | 506.50 | 24.72 | 44.33 | 24.88 |
June | 57.50 | 26.73 | 496.00 | 24.73 | 57.50 | 24.92 |
July | 89.00 | 26.83 | 497.00 | 24.98 | 89.00 | 25.23 |
August | 70.00 | 26.79 | 514.00 | 24.78 | 70.00 | 25.00 |
September | 65.00 | 26.67 | 485.00 | 24.80 | 65.00 | 24.99 |
October | 50.17 | 26.44 | 495.00 | 24.71 | 50.17 | 24.85 |
November | 7.33 | 24.47 | 460.33 | 24.35 | 3.33 | 24.36 |
December | 165.33 | 23.14 | 264.00 | 23.74 | 9.83 | 23.74 |
Annual Sum or Average | 1082.17 | 24.42 | 4846.17 | 24.44 | 417.17 | 24.58 |
Minimum of Months | 7.33 | 22.99 | 111.83 | 23.28 | 0.00 | 23.28 |
Maximum of Months | 301.17 | 26.84 | 514.00 | 24.98 | 89.00 | 25.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 144.67 | 23.06 | 166.00 | 23.72 | 0.17 | 23.72 |
February | 61.17 | 23.18 | 263.33 | 24.13 | 2.83 | 24.15 |
March | 41.50 | 23.97 | 338.67 | 24.37 | 8.33 | 24.43 |
April | 57.33 | 26.62 | 394.17 | 24.89 | 55.17 | 25.09 |
May | 63.67 | 26.96 | 430.00 | 24.99 | 63.67 | 25.22 |
June | 62.67 | 26.88 | 418.00 | 24.93 | 62.67 | 25.15 |
July | 97.83 | 26.95 | 422.00 | 25.22 | 97.83 | 25.49 |
August | 82.50 | 26.90 | 433.00 | 25.01 | 82.50 | 25.27 |
September | 72.00 | 26.91 | 410.00 | 25.05 | 72.00 | 25.29 |
October | 67.17 | 26.83 | 426.33 | 25.02 | 67.17 | 25.23 |
November | 27.50 | 26.66 | 408.50 | 24.72 | 26.50 | 24.84 |
December | 82.00 | 23.29 | 278.17 | 24.07 | 10.00 | 24.08 |
Annual Sum or Average | 860.00 | 25.48 | 4388.17 | 24.75 | 548.83 | 24.95 |
Minimum of Months | 27.50 | 23.06 | 166.00 | 23.72 | 0.17 | 23.72 |
Maximum of Months | 144.67 | 26.96 | 433.00 | 25.22 | 97.83 | 25.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 101.33 | 23.61 | 337.00 | 24.27 | 13.67 | 24.35 |
February | 63.83 | 24.07 | 371.33 | 24.35 | 17.33 | 24.45 |
March | 40.67 | 24.38 | 424.00 | 24.38 | 12.50 | 24.45 |
April | 45.50 | 26.33 | 459.67 | 24.66 | 43.83 | 24.80 |
May | 42.33 | 26.85 | 506.33 | 24.71 | 42.33 | 24.86 |
June | 53.00 | 26.66 | 496.00 | 24.69 | 53.00 | 24.86 |
July | 87.17 | 26.81 | 497.00 | 24.97 | 87.17 | 25.21 |
August | 76.00 | 26.83 | 514.00 | 24.82 | 76.00 | 25.05 |
September | 74.00 | 26.85 | 485.00 | 24.90 | 74.00 | 25.13 |
October | 75.67 | 26.93 | 502.00 | 24.96 | 75.67 | 25.19 |
November | 53.67 | 26.91 | 487.00 | 24.82 | 52.83 | 25.01 |
December | 76.00 | 24.83 | 414.83 | 24.53 | 36.17 | 24.68 |
Annual Sum or Average | 789.17 | 25.85 | 5494.17 | 24.70 | 584.50 | 24.87 |
Minimum of Months | 40.67 | 23.61 | 337.00 | 24.27 | 12.50 | 24.35 |
Maximum of Months | 101.33 | 26.93 | 514.00 | 24.97 | 87.17 | 25.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 157.83 | 23.13 | 238.50 | 23.81 | 2.00 | 23.83 |
February | 66.33 | 23.35 | 334.67 | 24.15 | 4.83 | 24.18 |
March | 31.17 | 24.52 | 431.00 | 24.40 | 10.50 | 24.45 |
April | 48.17 | 26.67 | 474.00 | 24.76 | 48.17 | 24.92 |
May | 72.67 | 26.95 | 507.33 | 24.90 | 72.67 | 25.13 |
June | 85.17 | 26.87 | 496.00 | 24.90 | 85.17 | 25.15 |
July | 113.17 | 26.92 | 497.00 | 25.12 | 113.17 | 25.40 |
August | 97.33 | 26.92 | 514.00 | 24.94 | 97.33 | 25.22 |
September | 90.50 | 26.89 | 485.00 | 24.99 | 90.50 | 25.24 |
October | 71.17 | 26.85 | 499.00 | 24.92 | 71.17 | 25.14 |
November | 29.83 | 26.71 | 485.50 | 24.63 | 28.33 | 24.75 |
December | 72.67 | 23.53 | 367.50 | 24.19 | 13.17 | 24.22 |
Annual Sum or Average | 936.00 | 25.65 | 5329.50 | 24.70 | 637.00 | 24.90 |
Minimum of Months | 29.83 | 23.13 | 238.50 | 23.81 | 2.00 | 23.83 |
Maximum of Months | 157.83 | 26.95 | 514.00 | 25.12 | 113.17 | 25.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 347.33 | 22.61 | 92.33 | 22.91 | 0.00 | 22.91 |
February | 191.67 | 22.82 | 187.00 | 23.47 | 1.67 | 23.48 |
March | 94.17 | 23.07 | 334.00 | 23.98 | 1.67 | 23.98 |
April | 52.67 | 25.28 | 435.83 | 24.54 | 38.33 | 24.65 |
May | 52.33 | 26.85 | 505.17 | 24.76 | 52.33 | 24.94 |
June | 62.00 | 26.73 | 496.00 | 24.76 | 62.00 | 24.96 |
July | 95.17 | 26.89 | 497.00 | 25.03 | 95.17 | 25.28 |
August | 77.83 | 26.82 | 514.00 | 24.83 | 77.83 | 25.06 |
September | 72.33 | 26.67 | 485.00 | 24.83 | 72.33 | 25.05 |
October | 54.17 | 26.50 | 492.17 | 24.74 | 54.17 | 24.90 |
November | 27.17 | 23.93 | 443.67 | 24.32 | 8.00 | 24.34 |
December | 212.17 | 22.80 | 226.50 | 23.45 | 13.67 | 23.45 |
Annual Sum or Average | 1339.00 | 24.12 | 4708.67 | 24.38 | 477.17 | 24.54 |
Minimum of Months | 27.17 | 22.61 | 92.33 | 22.91 | 0.00 | 22.91 |
Maximum of Months | 347.33 | 26.89 | 514.00 | 25.03 | 95.17 | 25.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 210.33 | 22.79 | 173.00 | 23.41 | 0.00 | 23.41 |
February | 100.67 | 22.96 | 275.00 | 23.92 | 4.67 | 23.94 |
March | 66.50 | 23.61 | 391.17 | 24.22 | 9.33 | 24.27 |
April | 64.67 | 26.22 | 463.17 | 24.74 | 55.67 | 24.93 |
May | 67.33 | 26.98 | 507.83 | 24.88 | 67.33 | 25.10 |
June | 68.50 | 26.86 | 496.00 | 24.82 | 68.50 | 25.04 |
July | 104.50 | 26.99 | 497.00 | 25.10 | 104.50 | 25.38 |
August | 85.17 | 26.94 | 514.00 | 24.90 | 85.17 | 25.15 |
September | 77.00 | 26.90 | 485.00 | 24.93 | 77.00 | 25.16 |
October | 70.00 | 26.82 | 500.83 | 24.89 | 70.00 | 25.10 |
November | 37.67 | 25.99 | 469.83 | 24.59 | 31.00 | 24.71 |
December | 133.50 | 23.05 | 302.17 | 23.84 | 14.33 | 23.84 |
Annual Sum or Average | 1085.83 | 25.00 | 5075.00 | 24.59 | 587.50 | 24.79 |
Minimum of Months | 37.67 | 22.79 | 173.00 | 23.41 | 0.00 | 23.41 |
Maximum of Months | 210.33 | 26.99 | 514.00 | 25.10 | 104.50 | 25.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 140.00 | 23.03 | 301.33 | 23.98 | 10.67 | 24.05 |
February | 88.50 | 23.45 | 347.00 | 24.17 | 15.83 | 24.27 |
March | 70.17 | 23.85 | 402.33 | 24.29 | 13.83 | 24.36 |
April | 60.50 | 25.78 | 447.83 | 24.65 | 48.33 | 24.81 |
May | 51.17 | 26.85 | 504.00 | 24.76 | 51.17 | 24.94 |
June | 59.33 | 26.66 | 496.00 | 24.73 | 59.33 | 24.92 |
July | 93.83 | 26.87 | 497.00 | 25.01 | 93.83 | 25.27 |
August | 82.50 | 26.85 | 514.00 | 24.86 | 82.50 | 25.10 |
September | 79.83 | 26.85 | 485.00 | 24.93 | 79.83 | 25.17 |
October | 76.50 | 26.92 | 502.00 | 24.96 | 76.50 | 25.19 |
November | 54.83 | 26.74 | 478.00 | 24.79 | 52.50 | 24.98 |
December | 101.33 | 24.05 | 380.17 | 24.36 | 35.00 | 24.49 |
Annual Sum or Average | 958.50 | 25.38 | 5354.67 | 24.66 | 619.33 | 24.85 |
Minimum of Months | 51.17 | 23.03 | 301.33 | 23.98 | 10.67 | 24.05 |
Maximum of Months | 140.00 | 26.92 | 514.00 | 25.01 | 93.83 | 25.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 212.83 | 22.79 | 198.33 | 23.49 | 2.50 | 23.51 |
February | 103.83 | 23.06 | 308.67 | 23.97 | 5.83 | 24.01 |
March | 57.50 | 23.92 | 403.17 | 24.32 | 11.17 | 24.38 |
April | 54.83 | 26.50 | 462.83 | 24.77 | 52.67 | 24.94 |
May | 75.83 | 26.97 | 506.83 | 24.92 | 75.83 | 25.16 |
June | 89.83 | 26.87 | 496.00 | 24.92 | 89.83 | 25.18 |
July | 115.00 | 26.96 | 497.00 | 25.14 | 115.00 | 25.43 |
August | 97.33 | 26.96 | 514.00 | 24.96 | 97.33 | 25.23 |
September | 95.00 | 26.89 | 485.00 | 25.00 | 95.00 | 25.27 |
October | 73.00 | 26.84 | 497.50 | 24.93 | 73.00 | 25.15 |
November | 36.33 | 26.34 | 472.67 | 24.62 | 32.00 | 24.74 |
December | 119.17 | 23.25 | 328.17 | 24.01 | 18.17 | 24.05 |
Annual Sum or Average | 1130.50 | 25.21 | 5170.17 | 24.65 | 668.33 | 24.86 |
Minimum of Months | 36.33 | 22.79 | 198.33 | 23.49 | 2.50 | 23.51 |
Maximum of Months | 212.83 | 26.97 | 514.00 | 25.14 | 115.00 | 25.43 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.17 | 27.00 | 454.00 | 27.00 | 0.17 | 27.00 |
March | 8.67 | 27.00 | 514.00 | 27.00 | 8.67 | 27.00 |
April | 170.50 | 27.22 | 485.00 | 27.12 | 170.50 | 27.14 |
May | 13.00 | 27.00 | 508.00 | 27.00 | 13.00 | 27.00 |
June | 67.17 | 27.00 | 496.00 | 27.00 | 67.17 | 27.00 |
July | 327.17 | 27.00 | 497.00 | 27.00 | 327.17 | 27.00 |
August | 514.00 | 28.63 | 514.00 | 28.63 | 514.00 | 28.63 |
September | 45.83 | 27.00 | 485.00 | 27.00 | 45.83 | 27.00 |
October | 34.00 | 27.00 | 502.00 | 27.00 | 34.00 | 27.00 |
November | 35.67 | 27.00 | 489.00 | 27.00 | 35.67 | 27.00 |
December | 45.67 | 27.00 | 497.00 | 27.00 | 45.67 | 27.00 |
Annual Sum or Average | 1261.83 | 27.69 | 5943.00 | 27.24 | 1261.83 | 27.31 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 514.00 | 28.63 | 514.00 | 28.63 | 514.00 | 28.63 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 29.00 | 27.76 | 485.00 | 27.10 | 29.00 | 27.13 |
May | 2.83 | 27.00 | 508.00 | 27.00 | 2.83 | 27.00 |
June | 10.00 | 27.00 | 496.00 | 27.00 | 10.00 | 27.00 |
July | 24.00 | 27.00 | 497.00 | 27.00 | 24.00 | 27.00 |
August | 454.33 | 28.41 | 514.00 | 28.34 | 454.33 | 28.36 |
September | 11.33 | 27.00 | 485.00 | 27.00 | 11.33 | 27.00 |
October | 1.67 | 27.00 | 502.00 | 27.00 | 1.67 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 533.17 | 28.24 | 5943.00 | 27.21 | 533.17 | 27.29 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 454.33 | 28.41 | 514.00 | 28.34 | 454.33 | 28.36 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 1.50 | 27.00 | 514.00 | 27.00 | 1.50 | 27.00 |
April | 48.17 | 27.59 | 485.00 | 27.11 | 48.17 | 27.15 |
May | 21.33 | 27.00 | 508.00 | 27.00 | 21.33 | 27.00 |
June | 28.00 | 27.00 | 496.00 | 27.00 | 28.00 | 27.00 |
July | 98.50 | 27.00 | 497.00 | 27.00 | 98.50 | 27.00 |
August | 447.67 | 28.45 | 514.00 | 28.36 | 447.67 | 28.39 |
September | 32.00 | 27.00 | 485.00 | 27.00 | 32.00 | 27.00 |
October | 20.50 | 27.00 | 502.00 | 27.00 | 20.50 | 27.00 |
November | 6.17 | 27.00 | 489.00 | 27.00 | 6.17 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 703.83 | 27.96 | 5943.00 | 27.21 | 703.83 | 27.28 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 447.67 | 28.45 | 514.00 | 28.36 | 447.67 | 28.39 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 28.38 | 485.00 | 28.38 | 485.00 | 28.38 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 32.08 | 514.00 | 32.08 | 514.00 | 32.08 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.20 | 497.00 | 27.20 | 497.00 | 27.20 |
Annual Sum or Average | 5943.00 | 27.57 | 5943.00 | 27.57 | 5943.00 | 27.57 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 32.08 | 514.00 | 32.08 | 514.00 | 32.08 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00087 | 31.73758 | 0.88584 | 21.59239 |
February | 454.00000 | 27.00151 | 31.36009 | 0.92560 | 23.11682 |
March | 514.00000 | 27.00086 | 31.25653 | 0.96376 | 24.63806 |
April | 485.00000 | 27.07838 | 32.10226 | 1.03354 | 27.62486 |
May | 508.00000 | 27.00055 | 36.80236 | 0.31383 | 7.09732 |
June | 496.00000 | 27.00252 | 37.02285 | 0.37153 | 7.91224 |
July | 497.00000 | 27.00119 | 36.82012 | 0.43010 | 8.89868 |
August | 514.00000 | 28.62688 | 35.35099 | 0.90830 | 23.06578 |
September | 485.00000 | 27.00015 | 40.53598 | 0.35550 | 7.67501 |
October | 502.00000 | 27.00228 | 35.11675 | 0.99104 | 25.76785 |
November | 489.00000 | 27.00121 | 32.68063 | 0.98980 | 25.71305 |
December | 497.00000 | 27.00036 | 30.81313 | 0.98740 | 25.61408 |
Annual Sum or Average | 5943.00000 | 27.14806 | 34.31224 | 0.76233 | 19.04198 |
Minimum of Months | 454.00000 | 27.00015 | 30.81313 | 0.31383 | 7.09732 |
Maximum of Months | 514.00000 | 28.62688 | 40.53598 | 1.03354 | 27.62486 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00039 | 32.17561 | 0.82718 | 19.47477 |
February | 454.00000 | 27.00144 | 31.51383 | 0.85487 | 20.45278 |
March | 514.00000 | 27.00081 | 31.29964 | 0.88829 | 21.68691 |
April | 485.00000 | 27.05951 | 32.15286 | 0.94390 | 23.88038 |
May | 508.00000 | 27.00043 | 37.03867 | 0.26918 | 6.55140 |
June | 496.00000 | 27.00244 | 37.19281 | 0.30125 | 6.92195 |
July | 497.00000 | 27.00126 | 36.93808 | 0.33528 | 7.37551 |
August | 514.00000 | 28.27463 | 35.69183 | 0.66426 | 14.97292 |
September | 485.00000 | 27.00008 | 40.97639 | 0.30605 | 6.98876 |
October | 502.00000 | 27.00218 | 35.27380 | 0.93986 | 23.68041 |
November | 489.00000 | 27.00115 | 32.75235 | 0.91663 | 22.76770 |
December | 497.00000 | 27.00036 | 30.85014 | 0.87950 | 21.35871 |
Annual Sum or Average | 5943.00000 | 27.11597 | 34.50077 | 0.67601 | 16.31160 |
Minimum of Months | 454.00000 | 27.00008 | 30.85014 | 0.26918 | 6.55140 |
Maximum of Months | 514.00000 | 28.27463 | 40.97639 | 0.94390 | 23.88038 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00033 | 32.46250 | 0.80530 | 18.76178 |
February | 454.00000 | 27.00145 | 31.56417 | 0.84092 | 19.98970 |
March | 514.00000 | 27.00083 | 31.30080 | 0.88435 | 21.56935 |
April | 485.00000 | 27.06572 | 32.13749 | 0.95052 | 24.18713 |
May | 508.00000 | 27.00049 | 36.95299 | 0.28978 | 6.83826 |
June | 496.00000 | 27.00250 | 37.13245 | 0.32487 | 7.27484 |
July | 497.00000 | 27.00126 | 36.89561 | 0.36559 | 7.86791 |
August | 514.00000 | 28.28422 | 35.64984 | 0.69111 | 16.06532 |
September | 485.00000 | 27.00013 | 40.83936 | 0.32518 | 7.28520 |
October | 502.00000 | 27.00221 | 35.25459 | 0.94754 | 24.00592 |
November | 489.00000 | 27.00118 | 32.75562 | 0.91430 | 22.69801 |
December | 497.00000 | 27.00040 | 30.86128 | 0.86264 | 20.77079 |
Annual Sum or Average | 5943.00000 | 27.11733 | 34.49655 | 0.68250 | 16.41729 |
Minimum of Months | 454.00000 | 27.00013 | 30.86128 | 0.28978 | 6.83826 |
Maximum of Months | 514.00000 | 28.28422 | 40.83936 | 0.95052 | 24.18713 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00350 | 30.98672 | 1.10614 | 30.80048 |
February | 454.00000 | 27.00333 | 31.15667 | 1.24996 | 37.72804 |
March | 514.00000 | 27.00189 | 31.57765 | 1.38401 | 44.66334 |
April | 485.00000 | 28.38147 | 31.61225 | 1.78947 | 65.74609 |
May | 508.00000 | 27.00317 | 34.92546 | 0.54952 | 11.37704 |
June | 496.00000 | 27.00307 | 35.60037 | 0.77313 | 17.60627 |
July | 497.00000 | 27.00118 | 35.94508 | 0.99193 | 25.79151 |
August | 514.00000 | 32.08219 | 32.84351 | 2.69036 | 95.45706 |
September | 485.00000 | 27.00382 | 36.93914 | 0.62803 | 13.34655 |
October | 502.00000 | 27.00283 | 34.03383 | 1.31159 | 40.87014 |
November | 489.00000 | 27.00133 | 32.46635 | 1.43322 | 47.29152 |
December | 497.00000 | 27.20117 | 31.07617 | 1.57828 | 55.14718 |
Annual Sum or Average | 5943.00000 | 27.57111 | 33.27122 | 1.29375 | 40.61136 |
Minimum of Months | 454.00000 | 27.00118 | 30.98672 | 0.54952 | 11.37704 |
Maximum of Months | 514.00000 | 32.08219 | 36.93914 | 2.69036 | 95.45706 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.58650 | 49.13032 | 0.58382 | 12.77693 |
February | 454.00000 | 24.56031 | 54.24956 | 0.61258 | 13.50707 |
March | 514.00000 | 24.44527 | 52.74021 | 0.57430 | 12.43608 |
April | 485.00000 | 24.53734 | 56.42425 | 0.62002 | 13.79491 |
May | 508.00000 | 24.51602 | 58.13913 | -0.2216 | 7.26826 |
June | 496.00000 | 24.48204 | 63.04667 | -0.1882 | 7.07721 |
July | 497.00000 | 24.63025 | 61.96858 | -0.1375 | 7.10671 |
August | 514.00000 | 24.48654 | 61.29314 | -0.1593 | 6.96859 |
September | 485.00000 | 24.57294 | 63.15210 | -0.1433 | 7.12446 |
October | 502.00000 | 24.62577 | 58.51065 | 0.67684 | 15.55723 |
November | 489.00000 | 24.63022 | 57.09974 | 0.66706 | 14.99962 |
December | 497.00000 | 24.62392 | 54.71922 | 0.64280 | 14.47001 |
Annual Sum or Average | 5943.00000 | 24.55748 | 57.54571 | 0.29057 | 11.06123 |
Minimum of Months | 454.00000 | 24.44527 | 49.13032 | -0.2216 | 6.96859 |
Maximum of Months | 514.00000 | 24.63025 | 63.15210 | 0.67684 | 15.55723 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.36919 | 50.10178 | 0.53696 | 11.37771 |
February | 454.00000 | 24.37585 | 53.55003 | 0.57314 | 12.23226 |
March | 514.00000 | 24.26602 | 51.32811 | 0.54383 | 11.40268 |
April | 485.00000 | 24.21706 | 53.03680 | 0.55781 | 11.65906 |
May | 508.00000 | 24.19275 | 54.63630 | -0.3090 | 7.20279 |
June | 496.00000 | 24.19675 | 56.53094 | -0.2810 | 6.85089 |
July | 497.00000 | 24.26772 | 55.76440 | -0.2477 | 6.57384 |
August | 514.00000 | 24.28228 | 55.17064 | -0.2169 | 6.42779 |
September | 485.00000 | 24.22097 | 56.91433 | -0.2760 | 6.83670 |
October | 502.00000 | 24.26353 | 55.31397 | 0.58456 | 12.32825 |
November | 489.00000 | 24.32991 | 56.00790 | 0.60135 | 12.78888 |
December | 497.00000 | 24.37016 | 53.79641 | 0.58695 | 12.50973 |
Annual Sum or Average | 5943.00000 | 24.27871 | 54.33809 | 0.21778 | 9.82408 |
Minimum of Months | 454.00000 | 24.19275 | 50.10178 | -0.3090 | 6.42779 |
Maximum of Months | 514.00000 | 24.37585 | 56.91433 | 0.60135 | 12.78888 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.11847 | 52.30768 | 0.46055 | 9.77421 |
February | 454.00000 | 24.20095 | 54.41622 | 0.50320 | 10.49866 |
March | 514.00000 | 24.21287 | 51.91907 | 0.50117 | 10.44410 |
April | 485.00000 | 24.22278 | 53.77496 | 0.52731 | 11.00900 |
May | 508.00000 | 24.13694 | 54.98648 | -0.3535 | 7.74427 |
June | 496.00000 | 24.09314 | 57.31248 | -0.3466 | 7.55367 |
July | 497.00000 | 24.09715 | 57.01796 | -0.3427 | 7.49109 |
August | 514.00000 | 24.09603 | 57.52349 | -0.3333 | 7.36226 |
September | 485.00000 | 24.14400 | 57.55989 | -0.3312 | 7.38867 |
October | 502.00000 | 24.23169 | 55.89407 | 0.55257 | 11.53575 |
November | 489.00000 | 24.28234 | 56.74308 | 0.56237 | 11.79738 |
December | 497.00000 | 24.18027 | 55.09598 | 0.50565 | 10.55236 |
Annual Sum or Average | 5943.00000 | 24.16749 | 55.37628 | 0.15530 | 9.41554 |
Minimum of Months | 454.00000 | 24.09314 | 51.91907 | -0.3535 | 7.36226 |
Maximum of Months | 514.00000 | 24.28234 | 57.55989 | 0.56237 | 11.79738 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.78854 | 53.85895 | 0.37418 | 8.33091 |
February | 454.00000 | 24.00828 | 55.39285 | 0.45375 | 9.59072 |
March | 514.00000 | 24.14451 | 52.41743 | 0.48616 | 10.14720 |
April | 485.00000 | 24.25349 | 53.81903 | 0.54145 | 11.34818 |
May | 508.00000 | 24.21870 | 54.80048 | -0.3039 | 7.23860 |
June | 496.00000 | 24.17351 | 57.08544 | -0.2937 | 7.01385 |
July | 497.00000 | 24.23028 | 56.56918 | -0.2679 | 6.82297 |
August | 514.00000 | 24.18745 | 57.26984 | -0.2732 | 6.82108 |
September | 485.00000 | 24.22364 | 57.40200 | -0.2832 | 6.99374 |
October | 502.00000 | 24.28296 | 55.97228 | 0.57349 | 12.08455 |
November | 489.00000 | 24.26126 | 57.21036 | 0.55780 | 11.65896 |
December | 497.00000 | 23.96209 | 56.17699 | 0.44870 | 9.52471 |
Annual Sum or Average | 5943.00000 | 24.14508 | 55.65688 | 0.16473 | 8.95211 |
Minimum of Months | 454.00000 | 23.78854 | 52.41743 | -0.3039 | 6.82108 |
Maximum of Months | 514.00000 | 24.28296 | 57.40200 | 0.57349 | 12.08455 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.00767 | 50.48315 | 0.41974 | 9.05034 |
February | 454.00000 | 24.18709 | 53.39082 | 0.50648 | 10.69087 |
March | 514.00000 | 24.23039 | 50.64733 | 0.53163 | 11.16738 |
April | 485.00000 | 24.37808 | 51.93014 | 0.61879 | 13.52107 |
May | 508.00000 | 24.49884 | 52.76685 | -0.1094 | 6.54094 |
June | 496.00000 | 24.49080 | 54.95805 | -0.0563 | 6.41053 |
July | 497.00000 | 24.65400 | 54.06794 | 0.01860 | 6.84094 |
August | 514.00000 | 24.54201 | 53.89752 | 0.00532 | 6.61121 |
September | 485.00000 | 24.51999 | 55.50621 | -0.0792 | 6.55354 |
October | 502.00000 | 24.48832 | 54.05514 | 0.67329 | 15.12312 |
November | 489.00000 | 24.38120 | 55.14680 | 0.61508 | 13.25953 |
December | 497.00000 | 24.21835 | 53.82852 | 0.52391 | 11.01681 |
Annual Sum or Average | 5943.00000 | 24.38420 | 53.37648 | 0.30343 | 9.71307 |
Minimum of Months | 454.00000 | 24.00767 | 50.48315 | -0.1094 | 6.41053 |
Maximum of Months | 514.00000 | 24.65400 | 55.50621 | 0.67329 | 15.12312 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.13770 | 49.84999 | 0.46749 | 10.08042 |
February | 454.00000 | 24.24986 | 53.01714 | 0.53814 | 11.53568 |
March | 514.00000 | 24.24499 | 50.48477 | 0.55132 | 11.76463 |
April | 485.00000 | 24.40463 | 51.70839 | 0.64745 | 14.46122 |
May | 508.00000 | 24.53840 | 52.44544 | -0.0400 | 6.62548 |
June | 496.00000 | 24.50016 | 54.78566 | -0.0124 | 6.48416 |
July | 497.00000 | 24.66330 | 53.94611 | 0.05794 | 7.12813 |
August | 514.00000 | 24.53271 | 53.83728 | 0.03166 | 6.66024 |
September | 485.00000 | 24.56170 | 55.14214 | -0.0116 | 6.74467 |
October | 502.00000 | 24.53695 | 53.62975 | 0.71489 | 16.50160 |
November | 489.00000 | 24.44025 | 54.83572 | 0.64679 | 14.28421 |
December | 497.00000 | 24.18848 | 53.88685 | 0.52486 | 11.11618 |
Annual Sum or Average | 5943.00000 | 24.41742 | 53.11867 | 0.34080 | 10.25928 |
Minimum of Months | 454.00000 | 24.13770 | 49.84999 | -0.0400 | 6.48416 |
Maximum of Months | 514.00000 | 24.66330 | 55.14214 | 0.71489 | 16.50160 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.32172 | 48.95094 | 0.54771 | 12.13673 |
February | 454.00000 | 24.36821 | 52.38475 | 0.60315 | 13.30622 |
March | 514.00000 | 24.32168 | 50.11032 | 0.59281 | 12.85142 |
April | 485.00000 | 24.42337 | 51.69328 | 0.64900 | 14.46433 |
May | 508.00000 | 24.49668 | 52.77445 | -0.1092 | 6.56308 |
June | 496.00000 | 24.47406 | 55.06155 | -0.0763 | 6.41216 |
July | 497.00000 | 24.64504 | 54.10527 | 0.01022 | 6.81235 |
August | 514.00000 | 24.54856 | 53.83026 | 0.02333 | 6.67602 |
September | 485.00000 | 24.57618 | 55.11975 | -0.0033 | 6.76396 |
October | 502.00000 | 24.60614 | 53.33355 | 0.76670 | 18.25927 |
November | 489.00000 | 24.56215 | 54.17480 | 0.73362 | 17.10104 |
December | 497.00000 | 24.44131 | 52.65316 | 0.63918 | 14.35728 |
Annual Sum or Average | 5943.00000 | 24.48247 | 52.84026 | 0.36206 | 11.27896 |
Minimum of Months | 454.00000 | 24.32168 | 48.95094 | -0.1092 | 6.41216 |
Maximum of Months | 514.00000 | 24.64504 | 55.11975 | 0.76670 | 18.25927 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.40584 | 48.72407 | 0.56082 | 12.15493 |
February | 454.00000 | 24.54935 | 51.66299 | 0.66620 | 15.02987 |
March | 514.00000 | 24.53365 | 49.21811 | 0.70484 | 16.19764 |
April | 485.00000 | 24.64593 | 50.64688 | 0.80881 | 19.77973 |
May | 508.00000 | 24.61586 | 52.19611 | 0.03808 | 6.96978 |
June | 496.00000 | 24.58025 | 54.36537 | 0.10466 | 7.15819 |
July | 497.00000 | 24.74031 | 53.47172 | 0.19986 | 8.31233 |
August | 514.00000 | 24.63466 | 53.22191 | 0.26584 | 8.81740 |
September | 485.00000 | 24.64238 | 54.75386 | 0.07758 | 7.20929 |
October | 502.00000 | 24.68137 | 53.05789 | 0.81016 | 19.79277 |
November | 489.00000 | 24.67676 | 53.76338 | 0.78503 | 18.82724 |
December | 497.00000 | 24.66294 | 51.76984 | 0.73183 | 17.17506 |
Annual Sum or Average | 5943.00000 | 24.61409 | 52.22939 | 0.47749 | 13.08658 |
Minimum of Months | 454.00000 | 24.40584 | 48.72407 | 0.03808 | 6.96978 |
Maximum of Months | 514.00000 | 24.74031 | 54.75386 | 0.81016 | 19.79277 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.38082 | 52.31237 | 0.25315 | 7.10668 |
February | 454.00000 | 23.75545 | 54.97461 | 0.38278 | 8.64361 |
March | 514.00000 | 24.06527 | 51.35717 | 0.46656 | 9.96029 |
April | 485.00000 | 24.39007 | 52.98860 | 0.59879 | 13.07032 |
May | 508.00000 | 24.53184 | 52.96308 | -0.1065 | 6.70062 |
June | 496.00000 | 24.49921 | 55.80013 | -0.0602 | 6.52859 |
July | 497.00000 | 24.65136 | 55.19048 | 0.00666 | 6.90462 |
August | 514.00000 | 24.51255 | 56.13263 | -0.0296 | 6.53786 |
September | 485.00000 | 24.54710 | 56.57467 | -0.0753 | 6.73316 |
October | 502.00000 | 24.52578 | 55.05129 | 0.67121 | 15.15053 |
November | 489.00000 | 24.31096 | 56.13096 | 0.57628 | 12.25882 |
December | 497.00000 | 23.74494 | 56.09763 | 0.38582 | 8.70829 |
Annual Sum or Average | 5943.00000 | 24.24574 | 54.61607 | 0.25395 | 9.01537 |
Minimum of Months | 454.00000 | 23.38082 | 51.35717 | -0.1065 | 6.52859 |
Maximum of Months | 514.00000 | 24.65136 | 56.57467 | 0.67121 | 15.15053 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.78558 | 50.33565 | 0.35854 | 8.50108 |
February | 385.00000 | 24.07481 | 53.44021 | 0.47250 | 10.37495 |
March | 433.00000 | 24.26810 | 50.24995 | 0.53293 | 11.59579 |
April | 410.00000 | 24.60799 | 52.22026 | 0.68389 | 15.80994 |
May | 430.00000 | 24.69739 | 52.43387 | 0.00436 | 7.13830 |
June | 418.00000 | 24.63338 | 55.39265 | 0.02826 | 6.99042 |
July | 422.00000 | 24.81510 | 54.51568 | 0.10414 | 7.85056 |
August | 433.00000 | 24.65302 | 55.57048 | 0.06822 | 7.15353 |
September | 410.00000 | 24.72065 | 55.83811 | 0.03454 | 7.37193 |
October | 427.00000 | 24.73046 | 54.14817 | 0.75242 | 17.95524 |
November | 417.00000 | 24.57177 | 54.89655 | 0.65936 | 14.81260 |
December | 422.00000 | 24.03099 | 54.68550 | 0.46394 | 10.15425 |
Annual Sum or Average | 5034.00000 | 24.46739 | 53.63304 | 0.34555 | 10.46495 |
Minimum of Months | 385.00000 | 23.78558 | 50.24995 | 0.00436 | 6.99042 |
Maximum of Months | 433.00000 | 24.81510 | 55.83811 | 0.75242 | 17.95524 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.16180 | 49.11945 | 0.49487 | 11.26649 |
February | 454.00000 | 24.22797 | 52.76564 | 0.55385 | 12.30927 |
March | 514.00000 | 24.26866 | 50.32398 | 0.56046 | 12.21019 |
April | 485.00000 | 24.46016 | 52.57158 | 0.63851 | 14.27286 |
May | 508.00000 | 24.52928 | 52.97131 | -0.1066 | 6.70463 |
June | 496.00000 | 24.48115 | 55.93832 | -0.0809 | 6.51866 |
July | 497.00000 | 24.64388 | 55.23203 | -0.0006 | 6.87709 |
August | 514.00000 | 24.52709 | 55.97477 | -0.0039 | 6.61679 |
September | 485.00000 | 24.60575 | 56.01810 | 0.00725 | 6.98193 |
October | 502.00000 | 24.66711 | 54.01318 | 0.77776 | 18.77448 |
November | 489.00000 | 24.58594 | 54.61570 | 0.72758 | 17.00944 |
December | 497.00000 | 24.32434 | 53.37774 | 0.59015 | 13.34267 |
Annual Sum or Average | 5943.00000 | 24.45782 | 53.57104 | 0.34395 | 11.04840 |
Minimum of Months | 454.00000 | 24.16180 | 49.11945 | -0.1066 | 6.51866 |
Maximum of Months | 514.00000 | 24.66711 | 56.01810 | 0.77776 | 18.77448 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.83529 | 50.52740 | 0.38016 | 8.86688 |
February | 454.00000 | 24.10324 | 53.42622 | 0.49613 | 10.80585 |
March | 514.00000 | 24.29330 | 50.28065 | 0.56550 | 12.29367 |
April | 485.00000 | 24.54703 | 52.14732 | 0.68775 | 15.84634 |
May | 508.00000 | 24.60649 | 52.54151 | -0.0098 | 7.03072 |
June | 496.00000 | 24.55792 | 55.33671 | 0.03043 | 6.93767 |
July | 497.00000 | 24.70602 | 54.73675 | 0.09815 | 7.58653 |
August | 514.00000 | 24.57029 | 55.58636 | 0.08002 | 7.14226 |
September | 485.00000 | 24.63019 | 55.85923 | 0.03008 | 7.22160 |
October | 502.00000 | 24.64697 | 54.29877 | 0.75070 | 17.85056 |
November | 489.00000 | 24.49518 | 55.16446 | 0.66474 | 14.90790 |
December | 497.00000 | 24.13492 | 54.35016 | 0.50661 | 11.03638 |
Annual Sum or Average | 5943.00000 | 24.42886 | 53.67773 | 0.35481 | 10.60984 |
Minimum of Months | 454.00000 | 23.83529 | 50.28065 | -0.0098 | 6.93767 |
Maximum of Months | 514.00000 | 24.70602 | 55.85923 | 0.75070 | 17.85056 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.02536 | 53.42182 | 0.16459 | 6.93935 |
February | 454.00000 | 23.52649 | 55.78841 | 0.32694 | 8.29014 |
March | 514.00000 | 23.96459 | 51.84975 | 0.44436 | 9.78406 |
April | 485.00000 | 24.37174 | 53.28792 | 0.60168 | 13.28328 |
May | 508.00000 | 24.54524 | 53.18109 | -0.0825 | 6.84483 |
June | 496.00000 | 24.51173 | 56.08806 | -0.0337 | 6.68064 |
July | 497.00000 | 24.67134 | 55.45242 | 0.04080 | 7.24767 |
August | 514.00000 | 24.52789 | 56.46515 | 0.00091 | 6.75773 |
September | 485.00000 | 24.56028 | 56.93224 | -0.0509 | 6.91169 |
October | 502.00000 | 24.53597 | 55.48851 | 0.68311 | 15.58738 |
November | 489.00000 | 24.27026 | 56.67565 | 0.56796 | 12.18347 |
December | 497.00000 | 23.50813 | 57.09580 | 0.32728 | 8.28319 |
Annual Sum or Average | 5943.00000 | 24.17199 | 55.12672 | 0.24769 | 9.05881 |
Minimum of Months | 454.00000 | 23.02536 | 51.84975 | -0.0825 | 6.68064 |
Maximum of Months | 514.00000 | 24.67134 | 57.09580 | 0.68311 | 15.58738 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.53862 | 51.52469 | 0.30003 | 8.12277 |
February | 454.00000 | 23.88325 | 54.22661 | 0.43240 | 9.85642 |
March | 514.00000 | 24.14670 | 50.93627 | 0.51735 | 11.34898 |
April | 485.00000 | 24.49436 | 52.43498 | 0.67585 | 15.54678 |
May | 508.00000 | 24.59645 | 52.73902 | 0.00855 | 7.06622 |
June | 496.00000 | 24.53951 | 55.70885 | 0.03747 | 6.90149 |
July | 497.00000 | 24.70579 | 55.11337 | 0.11425 | 7.84571 |
August | 514.00000 | 24.55878 | 56.05333 | 0.08166 | 7.11340 |
September | 485.00000 | 24.61342 | 56.32997 | 0.03739 | 7.26263 |
October | 502.00000 | 24.62293 | 54.66263 | 0.74836 | 17.77360 |
November | 489.00000 | 24.44630 | 55.70941 | 0.64333 | 14.32719 |
December | 497.00000 | 23.84139 | 55.67219 | 0.42162 | 9.59081 |
Annual Sum or Average | 5943.00000 | 24.33464 | 54.24767 | 0.33321 | 10.21567 |
Minimum of Months | 454.00000 | 23.53862 | 50.93627 | 0.00855 | 6.90149 |
Maximum of Months | 514.00000 | 24.70579 | 56.32997 | 0.74836 | 17.77360 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.91777 | 49.92459 | 0.42766 | 10.53781 |
February | 454.00000 | 24.06566 | 53.39234 | 0.51030 | 11.74786 |
March | 514.00000 | 24.18571 | 50.78923 | 0.54129 | 11.98688 |
April | 485.00000 | 24.43839 | 52.88078 | 0.64022 | 14.44395 |
May | 508.00000 | 24.54228 | 53.19158 | -0.0828 | 6.85497 |
June | 496.00000 | 24.49691 | 56.21786 | -0.0532 | 6.65981 |
July | 497.00000 | 24.66487 | 55.49264 | 0.03397 | 7.21708 |
August | 514.00000 | 24.54057 | 56.31637 | 0.02566 | 6.86898 |
September | 485.00000 | 24.61212 | 56.40511 | 0.02853 | 7.24069 |
October | 502.00000 | 24.66594 | 54.47886 | 0.78613 | 19.12966 |
November | 489.00000 | 24.54912 | 55.09581 | 0.71907 | 16.81673 |
December | 497.00000 | 24.17877 | 54.07070 | 0.54840 | 12.66746 |
Annual Sum or Average | 5943.00000 | 24.40643 | 54.01427 | 0.34147 | 10.99228 |
Minimum of Months | 454.00000 | 23.91777 | 49.92459 | -0.0828 | 6.65981 |
Maximum of Months | 514.00000 | 24.66594 | 56.40511 | 0.78613 | 19.12966 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.55661 | 51.41045 | 0.30938 | 8.43718 |
February | 454.00000 | 23.93274 | 54.06990 | 0.45296 | 10.35328 |
March | 514.00000 | 24.21864 | 50.71774 | 0.54855 | 12.07772 |
April | 485.00000 | 24.52839 | 52.43249 | 0.68945 | 15.98876 |
May | 508.00000 | 24.61440 | 52.78354 | 0.01024 | 7.26058 |
June | 496.00000 | 24.56263 | 55.65440 | 0.05258 | 7.16005 |
July | 497.00000 | 24.71729 | 55.03006 | 0.12686 | 7.99422 |
August | 514.00000 | 24.57775 | 55.94266 | 0.10533 | 7.45053 |
September | 485.00000 | 24.63467 | 56.26002 | 0.04964 | 7.47308 |
October | 502.00000 | 24.64692 | 54.76181 | 0.75933 | 18.20075 |
November | 489.00000 | 24.45733 | 55.66050 | 0.65696 | 14.76015 |
December | 497.00000 | 23.96755 | 55.12607 | 0.46292 | 10.49625 |
Annual Sum or Average | 5943.00000 | 24.37023 | 54.14264 | 0.35039 | 10.62366 |
Minimum of Months | 454.00000 | 23.55661 | 50.71774 | 0.01024 | 7.16005 |
Maximum of Months | 514.00000 | 24.71729 | 56.26002 | 0.75933 | 18.20075 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.102802E+12 | 165732.59 | 30-JAN-14:00 | 448.39 | 0.646183E+12 | 0.00 | 0.748984E+12 | 3.50 | 7.93 | 30-JAN-06:04 | 0.00 | 0.00 |
February | 0.113556E+12 | 192756.83 | 07-FEB-16:30 | 420.06 | 0.768454E+12 | 0.00 | 0.882010E+12 | 3.89 | 7.95 | 06-FEB-15:40 | 0.00 | 0.00 |
March | 0.160507E+12 | 191919.56 | 28-MAR-15:20 | 558.67 | 0.113014E+13 | 0.00 | 0.129064E+13 | 4.79 | 7.95 | 31-MAR-05:04 | 0.00 | 0.00 |
April | 0.201843E+12 | 195401.75 | 03-APR-10:50 | 652.12 | 0.145037E+13 | 0.00 | 0.165221E+13 | 5.85 | 7.95 | 14-APR-12:40 | 0.00 | 0.00 |
May | 0.269466E+12 | 216073.72 | 29-MAY-14:09 | 687.79 | 0.192089E+13 | 0.00 | 0.219036E+13 | 6.33 | 7.95 | 10-MAY-07:20 | 0.00 | 0.00 |
June | 0.312629E+12 | 218453.30 | 19-JUN-05:03 | 691.08 | 0.217067E+13 | 0.00 | 0.248330E+13 | 6.53 | 7.95 | 02-JUN-08:70 | 0.00 | 0.00 |
July | 0.351992E+12 | 225176.24 | 19-JUL-15:00 | 692.86 | 0.241011E+13 | 0.00 | 0.276210E+13 | 6.31 | 7.95 | 03-JUL-05:05 | 0.00 | 0.00 |
August | 0.377183E+12 | 225604.58 | 10-AUG-15:30 | 721.80 | 0.256537E+13 | 0.00 | 0.294255E+13 | 6.50 | 7.86 | 05-AUG-17:42 | 0.00 | 0.00 |
September | 0.317966E+12 | 218768.70 | 09-SEP-17:42 | 682.45 | 0.219096E+13 | 0.00 | 0.250892E+13 | 6.38 | 7.95 | 26-SEP-05:04 | 0.00 | 0.00 |
October | 0.263808E+12 | 213573.72 | 01-OCT-16:34 | 688.84 | 0.186146E+13 | 0.00 | 0.212527E+13 | 6.16 | 7.95 | 14-OCT-05:04 | 0.00 | 0.00 |
November | 0.186736E+12 | 202737.37 | 02-NOV-20:00 | 601.53 | 0.133024E+13 | 0.00 | 0.151697E+13 | 5.39 | 7.95 | 06-NOV-05:14 | 0.00 | 0.00 |
December | 0.134219E+12 | 195894.49 | 05-DEC-13:40 | 542.49 | 0.911374E+12 | 0.00 | 0.104559E+13 | 4.43 | 7.94 | 04-DEC-06:04 | 0.00 | 0.00 |
Annual Sum or Average | 0.279271E+13 | 7388.07 | 0.193562E+14 | 0.00 | 0.221489E+14 | 5.51 | 0.00 | 0.00 | ||||
Minimum of Months | 0.102802E+12 | 165732.59 | 420.06 | 0.646183E+12 | 0.00 | 0.748984E+12 | 3.50 | 7.86 | 0.00 | 0.00 | ||
Maximum of Months | 0.377183E+12 | 225604.58 | 721.80 | 0.256537E+13 | 0.00 | 0.294255E+13 | 6.53 | 7.95 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.207854E+10 | 127269.98 | 08-FEB-15:05 | 5.58 | 0.152149E+11 | 0.00 | 0.172934E+11 | 0.06 | 7.70 | 06-FEB-13:05 | 0.00 | 0.00 |
March | 0.839662E+10 | 133086.10 | 29-MAR-12:05 | 23.42 | 0.621584E+11 | 0.00 | 0.705550E+11 | 0.23 | 7.80 | 23-MAR-11:05 | 0.00 | 0.00 |
April | 0.247917E+11 | 145171.15 | 10-APR-12:05 | 65.67 | 0.182147E+12 | 0.00 | 0.206939E+12 | 0.66 | 7.90 | 27-APR-08:55 | 0.00 | 0.00 |
May | 0.895752E+11 | 210853.24 | 30-MAY-05:03 | 213.78 | 0.641369E+12 | 0.00 | 0.730944E+12 | 2.05 | 7.78 | 09-MAY-09:05 | 0.00 | 0.00 |
June | 0.157213E+12 | 218453.30 | 19-JUN-05:03 | 337.38 | 0.109853E+13 | 0.00 | 0.125574E+13 | 3.27 | 7.67 | 16-JUN-09:05 | 0.00 | 0.00 |
July | 0.215172E+12 | 225176.24 | 19-JUL-15:00 | 409.32 | 0.147276E+13 | 0.00 | 0.168793E+13 | 3.76 | 7.80 | 30-JUL-13:42 | 0.00 | 0.00 |
August | 0.243709E+12 | 225604.58 | 10-AUG-15:30 | 438.94 | 0.166250E+13 | 0.00 | 0.190621E+13 | 4.02 | 7.86 | 05-AUG-17:42 | 0.00 | 0.00 |
September | 0.168289E+12 | 218768.70 | 09-SEP-17:42 | 345.05 | 0.116361E+13 | 0.00 | 0.133190E+13 | 3.31 | 7.67 | 05-SEP-05:03 | 0.00 | 0.00 |
October | 0.913976E+11 | 206168.87 | 02-OCT-05:02 | 213.39 | 0.651232E+12 | 0.00 | 0.742629E+12 | 2.04 | 7.79 | 20-OCT-13:05 | 0.00 | 0.00 |
November | 0.363053E+11 | 166047.37 | 08-NOV-06:04 | 91.20 | 0.261461E+12 | 0.00 | 0.297766E+12 | 0.91 | 7.87 | 08-NOV-06:02 | 0.00 | 0.00 |
December | 0.315643E+10 | 131347.20 | 06-DEC-15:05 | 8.58 | 0.228143E+11 | 0.00 | 0.259708E+11 | 0.08 | 7.62 | 06-DEC-15:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.104008E+13 | 2152.32 | 0.723379E+13 | 0.00 | 0.827387E+13 | 1.71 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.243709E+12 | 225604.58 | 438.94 | 0.166250E+13 | 0.00 | 0.190621E+13 | 4.02 | 7.90 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.103361E+12 | 744.00 | 43776.24 | 01-JAN-09:40 | 218083.05 | 23-JAN-14:05 | 25.23 | 21.55 | 14.69 |
February | 0.104373E+12 | 672.00 | 43776.24 | 01-FEB-00:10 | 385146.38 | 07-FEB-14:05 | 30.60 | 24.04 | 14.69 |
March | 0.117250E+12 | 744.00 | 43776.24 | 01-MAR-00:10 | 634441.57 | 31-MAR-23:25 | 37.26 | 27.79 | 14.69 |
April | 0.113468E+12 | 720.00 | 43776.24 | 01-APR-00:05 | 698822.55 | 28-APR-12:45 | 45.13 | 32.69 | 14.69 |
May | 0.117250E+12 | 744.00 | 43776.24 | 01-MAY-00:05 | 378877.63 | 31-MAY-23:35 | 37.86 | 33.51 | 14.69 |
June | 0.113468E+12 | 720.00 | 43776.24 | 01-JUN-00:10 | 537780.95 | 30-JUN-23:20 | 44.22 | 36.71 | 14.69 |
July | 0.117250E+12 | 744.00 | 43776.24 | 01-JUL-00:05 | 675403.24 | 31-JUL-23:53 | 51.14 | 40.46 | 14.69 |
August | 0.117250E+12 | 744.00 | 43776.24 | 01-AUG-00:03 | 726916.02 | 04-AUG-14:00 | 55.00 | 41.93 | 14.69 |
September | 0.113468E+12 | 720.00 | 43776.24 | 01-SEP-00:05 | 386118.44 | 30-SEP-23:15 | 39.41 | 34.78 | 14.69 |
October | 0.117250E+12 | 744.00 | 43776.24 | 01-OCT-00:05 | 509700.35 | 31-OCT-23:35 | 40.41 | 33.13 | 14.69 |
November | 0.113468E+12 | 720.00 | 43776.24 | 01-NOV-00:05 | 558343.59 | 01-NOV-14:05 | 40.13 | 30.36 | 14.69 |
December | 0.117250E+12 | 744.00 | 43776.24 | 01-DEC-00:10 | 667536.64 | 03-DEC-13:42 | 39.24 | 27.11 | 14.69 |
Annual Sum or Average | 0.136511E+13 | 8760.00 | 40.53 | 32.05 | 14.69 | ||||
Minimum of Months | 0.103361E+12 | 672.00 | 43776.24 | 218083.05 | 25.23 | 21.55 | 14.69 | ||
Maximum of Months | 0.117250E+12 | 744.00 | 43776.24 | 726916.02 | 55.00 | 41.93 | 14.69 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.265493E+10 | 392.28 | 20448.23 | 09-JAN-13:10 | 1371949.78 | 30-JAN-15:00 | 22.38 | 21.42 | 42.12 |
February | 0.614876E+10 | 384.77 | 20448.23 | 02-FEB-12:00 | 1610154.72 | 08-FEB-14:00 | 22.81 | 21.57 | 44.04 |
March | 0.116429E+11 | 496.34 | 20448.23 | 01-MAR-06:04 | 1616448.61 | 23-MAR-12:00 | 23.15 | 21.51 | 51.49 |
April | 0.260907E+11 | 599.85 | 20448.23 | 03-APR-05:02 | 1600440.78 | 06-APR-12:20 | 24.22 | 22.07 | 60.86 |
May | 0.432392E+11 | 685.21 | 20448.23 | 01-MAY-00:05 | 1626955.62 | 20-MAY-10:50 | 26.80 | 24.07 | 60.67 |
June | 0.497805E+11 | 691.08 | 20448.23 | 01-JUN-00:10 | 1583453.91 | 19-JUN-05:03 | 29.62 | 26.42 | 58.00 |
July | 0.499318E+11 | 692.86 | 20448.23 | 01-JUL-00:05 | 1713957.80 | 19-JUL-15:10 | 31.04 | 27.61 | 56.62 |
August | 0.531284E+11 | 721.80 | 20448.23 | 01-AUG-00:03 | 1717411.02 | 03-AUG-14:40 | 31.56 | 27.90 | 58.46 |
September | 0.500209E+11 | 682.45 | 20448.23 | 01-SEP-00:05 | 1610119.74 | 07-SEP-14:05 | 30.30 | 27.07 | 56.49 |
October | 0.452189E+11 | 679.87 | 20448.23 | 01-OCT-00:05 | 1579070.92 | 20-OCT-10:00 | 27.10 | 24.44 | 58.95 |
November | 0.252819E+11 | 540.88 | 20448.23 | 01-NOV-03:02 | 1602819.41 | 13-NOV-13:50 | 24.26 | 22.30 | 56.68 |
December | 0.100051E+11 | 468.60 | 20448.23 | 01-DEC-13:05 | 1474261.04 | 26-DEC-15:40 | 22.80 | 21.47 | 50.07 |
Annual Sum or Average | 0.373144E+12 | 7035.98 | 26.36 | 24.00 | 54.59 | ||||
Minimum of Months | 0.265493E+10 | 384.77 | 20448.23 | 1371949.78 | 22.38 | 21.42 | 42.12 | ||
Maximum of Months | 0.531284E+11 | 721.80 | 20448.23 | 1717411.02 | 31.56 | 27.90 | 60.86 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 73613643.11 | 1.00 | 20448.23 | 30-JAN-13:50 | 715038.59 | 30-JAN-14:50 | 22.38 | 22.37 | 0.05 |
February | 0.506526E+09 | 7.38 | 20448.23 | 06-FEB-11:30 | 1368247.97 | 06-FEB-15:05 | 22.81 | 22.77 | 0.65 |
March | 0.211046E+10 | 30.04 | 20448.23 | 01-MAR-13:05 | 1425322.81 | 23-MAR-15:50 | 23.15 | 22.99 | 2.37 |
April | 0.781137E+10 | 109.22 | 20448.23 | 03-APR-07:10 | 1425852.54 | 28-APR-08:30 | 24.22 | 23.65 | 8.54 |
May | 0.247136E+11 | 337.08 | 20448.23 | 01-MAY-04:15 | 1513381.44 | 30-MAY-05:03 | 26.80 | 25.20 | 26.64 |
June | 0.415134E+11 | 564.08 | 20448.23 | 01-JUN-07:10 | 1583453.91 | 19-JUN-05:03 | 29.62 | 26.82 | 45.24 |
July | 0.466141E+11 | 633.23 | 20448.23 | 01-JUL-00:05 | 1713957.80 | 19-JUL-15:10 | 31.04 | 27.80 | 50.82 |
August | 0.503722E+11 | 684.28 | 20448.23 | 01-AUG-00:03 | 1717411.02 | 03-AUG-14:40 | 31.56 | 28.00 | 54.81 |
September | 0.431980E+11 | 586.82 | 20448.23 | 01-SEP-00:05 | 1610119.74 | 07-SEP-14:05 | 30.30 | 27.33 | 46.88 |
October | 0.273002E+11 | 371.74 | 20448.23 | 01-OCT-00:05 | 1401484.69 | 02-OCT-05:04 | 27.10 | 25.32 | 28.33 |
November | 0.965366E+10 | 131.37 | 20448.23 | 01-NOV-04:13 | 1356988.61 | 13-NOV-14:05 | 24.26 | 23.61 | 11.09 |
December | 0.114715E+10 | 15.58 | 20448.23 | 04-DEC-09:30 | 1112086.38 | 05-DEC-13:05 | 22.80 | 22.72 | 1.17 |
Annual Sum or Average | 0.255014E+12 | 3471.82 | 26.36 | 24.89 | 23.18 | ||||
Minimum of Months | 73613643.11 | 1.00 | 20448.23 | 715038.59 | 22.38 | 22.37 | 0.05 | ||
Maximum of Months | 0.503722E+11 | 684.28 | 20448.23 | 1717411.02 | 31.56 | 28.00 | 54.81 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 284528.98 | 0.00 | 2.28 | 245.18 | 21-JAN-06:08 | 0.00 | 54.61 | 54.63 | 0.00 | 0.00 | 0.00 | 0.00 | 21-JAN-06:08 |
February | 93050.20 | 0.00 | 0.46 | 132.73 | 13-FEB-06:10 | 0.00 | 51.95 | 51.95 | 0.00 | 0.00 | 0.00 | 0.00 | 13-FEB-06:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 51.76 | 51.76 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 51.76 | 51.76 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 51.76 | 51.76 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 51.76 | 51.76 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 51.76 | 51.76 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 51.76 | 51.76 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 51.76 | 51.76 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 51.76 | 51.76 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 2785.70 | 0.00 | 0.17 | 4.64 | 21-NOV-08:40 | 0.00 | 51.75 | 51.76 | 0.00 | 0.00 | 0.00 | 0.00 | 21-NOV-08:40 |
December | 107526.23 | 0.00 | 1.50 | 49.24 | 18-DEC-06:50 | 0.00 | 51.71 | 51.73 | 0.00 | 0.00 | 0.00 | 0.00 | 18-DEC-06:50 |
Annual Sum or Average | 487891.11 | 0.00 | 4.41 | 0.00 | 52.01 | 52.01 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.71 | 51.73 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 284528.98 | 0.00 | 2.28 | 245.18 | 0.00 | 54.61 | 54.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 25.23 | 25.23 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 30.60 | 30.60 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 37.26 | 37.26 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 45.13 | 45.13 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 37.86 | 37.86 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 44.22 | 44.22 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 51.14 | 51.14 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 55.00 | 55.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 39.41 | 39.41 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 40.41 | 40.41 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 40.13 | 40.13 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 39.24 | 39.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 40.53 | 40.53 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.23 | 25.23 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.00 | 55.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.651972E+11 | 0.00 | 428.33 | 0.624692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 225927.31 | 30-JAN-05:12 | 156303.73 | 30-JAN-05:12 | 0.00 | 0.00 | 0.00 |
February | 0.784781E+11 | 0.00 | 404.67 | 0.726475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 252274.18 | 09-FEB-05:12 | 161004.95 | 09-FEB-05:12 | 0.00 | 0.00 | 0.00 |
March | 0.118595E+12 | 0.00 | 543.42 | 0.110487E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 213410.55 | 01-MAR-06:02 | 170348.34 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.159900E+12 | 0.00 | 621.54 | 0.139984E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 225489.81 | 03-APR-05:02 | 176186.61 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.212938E+12 | 0.00 | 638.28 | 0.175015E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 292801.46 | 30-MAY-05:03 | 179245.41 | 30-MAY-05:03 | 0.00 | 0.00 | 0.00 |
June | 0.274267E+12 | 0.00 | 638.14 | 0.195119E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 301380.47 | 26-JUN-05:02 | 191457.41 | 12-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.328088E+12 | 0.00 | 652.36 | 0.220575E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 327065.80 | 30-JUL-16:22 | 198586.62 | 22-JUL-05:03 | 0.00 | 0.00 | 0.00 |
August | 0.375313E+12 | 0.00 | 659.27 | 0.255580E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 327602.30 | 08-AUG-04:22 | 208091.81 | 07-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.277106E+12 | 0.00 | 626.05 | 0.182094E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 311350.84 | 10-SEP-16:21 | 194394.88 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.222875E+12 | 0.00 | 636.17 | 0.165268E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 294375.71 | 02-OCT-05:02 | 188056.98 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.154149E+12 | 0.00 | 568.39 | 0.128767E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 238049.33 | 02-NOV-04:22 | 169091.00 | 20-NOV-05:23 | 0.00 | 0.00 | 0.00 |
December | 0.104852E+12 | 0.00 | 520.67 | 0.933286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 205346.81 | 05-DEC-06:02 | 149898.78 | 12-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237176E+13 | 0.00 | 6937.28 | 0.180133E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.651972E+11 | 0.00 | 404.67 | 0.624692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 205346.81 | 149898.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.375313E+12 | 0.00 | 659.27 | 0.255580E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 327602.30 | 208091.81 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.464965E+12 | 0.00 | 407.50 | 0.443006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1708069.13 | 30-JAN-06:02 | 1105844.68 | 30-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.572156E+12 | 0.00 | 377.75 | 0.524039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1967881.49 | 09-FEB-06:03 | 1330978.26 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.879033E+12 | 0.00 | 459.79 | 0.813624E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2091481.17 | 29-MAR-04:12 | 1640652.65 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.120270E+13 | 0.00 | 484.14 | 0.104972E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2171283.39 | 20-APR-04:12 | 1576613.49 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.198307E+13 | 0.00 | 605.70 | 0.161559E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2389777.67 | 29-MAY-15:12 | 1627305.14 | 11-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.257284E+13 | 0.00 | 625.56 | 0.177402E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2947600.71 | 04-JUN-15:52 | 1736669.62 | 26-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.307335E+13 | 0.00 | 648.51 | 0.197392E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3353179.96 | 30-JUL-16:22 | 1828145.50 | 10-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.333305E+13 | 0.00 | 656.65 | 0.212224E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3242923.35 | 08-AUG-05:01 | 1926610.60 | 07-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.264104E+13 | 0.00 | 604.99 | 0.168598E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3303784.78 | 10-SEP-16:52 | 1806277.74 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.192896E+13 | 0.00 | 552.89 | 0.140598E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2906987.34 | 07-OCT-05:02 | 1663852.07 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.119750E+13 | 0.00 | 451.15 | 0.979541E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2484144.44 | 08-NOV-06:02 | 1523301.01 | 08-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.668091E+12 | 0.00 | 419.58 | 0.585479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1959414.10 | 12-DEC-06:02 | 1373580.04 | 12-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205168E+14 | 0.00 | 6294.22 | 0.149731E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.464965E+12 | 0.00 | 377.75 | 0.443006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1708069.13 | 1105844.68 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.333305E+13 | 0.00 | 656.65 | 0.212224E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3353179.96 | 1926610.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.421379E+11 | 0.00 | 400.78 | 0.399627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 165439.16 | 30-JAN-06:02 | 104544.66 | 30-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.552846E+11 | 0.00 | 371.36 | 0.505000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 201933.07 | 06-FEB-06:03 | 134489.82 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.886150E+11 | 0.00 | 451.11 | 0.820652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 197270.31 | 01-MAR-06:02 | 178101.62 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.125291E+12 | 0.00 | 481.81 | 0.109884E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 272656.97 | 30-APR-14:51 | 175073.17 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.211513E+12 | 0.00 | 606.92 | 0.174606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 328448.27 | 30-MAY-04:12 | 193045.10 | 30-MAY-04:12 | 0.00 | 0.00 | 0.00 |
June | 0.273363E+12 | 0.00 | 627.59 | 0.193075E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 330916.39 | 19-JUN-05:02 | 199654.41 | 26-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.326336E+12 | 0.00 | 649.01 | 0.216191E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 367282.66 | 30-JUL-16:22 | 210075.87 | 10-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.351826E+12 | 0.00 | 657.39 | 0.230792E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 364978.13 | 08-AUG-05:01 | 219178.58 | 07-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.276407E+12 | 0.00 | 607.68 | 0.180525E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 338121.08 | 10-SEP-15:52 | 206839.70 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.199382E+12 | 0.00 | 553.36 | 0.146676E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 326448.71 | 02-OCT-05:02 | 191636.28 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.118858E+12 | 0.00 | 445.79 | 0.971751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 243066.27 | 01-NOV-04:11 | 167530.48 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.626771E+11 | 0.00 | 408.53 | 0.546337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 210822.28 | 11-DEC-06:03 | 129895.44 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213169E+13 | 0.00 | 6261.34 | 0.157609E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.421379E+11 | 0.00 | 371.36 | 0.399627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 165439.16 | 104544.66 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.351826E+12 | 0.00 | 657.39 | 0.230792E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 367282.66 | 219178.58 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.629367E+11 | 0.00 | 409.74 | 0.615589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149790.86 | 30-JAN-05:12 | 97683.91 | 18-JAN-05:12 | 0.00 | 0.00 | 0.00 |
February | 0.603465E+11 | 0.00 | 371.96 | 0.584681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153579.85 | 07-FEB-05:12 | 100305.07 | 11-FEB-05:12 | 0.00 | 0.00 | 0.00 |
March | 0.742216E+11 | 0.00 | 436.01 | 0.718839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 161288.87 | 30-MAR-04:12 | 106586.20 | 02-MAR-05:03 | 0.00 | 0.00 | 0.00 |
April | 0.787885E+11 | 0.00 | 411.08 | 0.742291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 181471.36 | 30-APR-16:40 | 106871.44 | 03-APR-03:13 | 0.00 | 0.00 | 0.00 |
May | 0.103816E+12 | 0.00 | 454.93 | 0.913715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 217508.30 | 30-MAY-03:02 | 114297.02 | 29-MAY-10:50 | 0.00 | 0.00 | 0.00 |
June | 0.125317E+12 | 0.00 | 458.55 | 0.974899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 228628.13 | 18-JUN-22:00 | 104569.88 | 04-JUN-15:41 | 0.00 | 0.00 | 0.00 |
July | 0.149808E+12 | 0.00 | 464.01 | 0.105897E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 234620.75 | 30-JUL-22:20 | 127769.72 | 30-JUL-11:31 | 0.00 | 0.00 | 0.00 |
August | 0.176606E+12 | 0.00 | 510.51 | 0.123259E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 231345.31 | 20-AUG-21:31 | 118788.10 | 06-AUG-10:58 | 0.00 | 0.00 | 0.00 |
September | 0.136824E+12 | 0.00 | 462.71 | 0.991216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 239395.72 | 10-SEP-18:26 | 116244.31 | 04-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.120332E+12 | 0.00 | 476.06 | 0.969576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 226528.18 | 01-OCT-19:30 | 123178.11 | 29-OCT-13:46 | 0.00 | 0.00 | 0.00 |
November | 0.966197E+11 | 0.00 | 444.51 | 0.842663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 169829.78 | 03-NOV-03:02 | 120604.76 | 05-NOV-11:50 | 0.00 | 0.00 | 0.00 |
December | 0.751853E+11 | 0.00 | 431.27 | 0.708384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155914.51 | 06-DEC-05:11 | 99664.95 | 03-DEC-13:06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126080E+13 | 0.00 | 5331.35 | 0.103534E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.603465E+11 | 0.00 | 371.96 | 0.584681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149790.86 | 97683.91 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.176606E+12 | 0.00 | 510.51 | 0.123259E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 239395.72 | 127769.72 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.339644E+12 | 0.831406E+11 | 744.00 | 0.328785E+12 | 0.108587E+11 | 0.00 | 0.37 | 23-JAN-14:00 | 0.32 | 21-JAN-05:55 | 137130.25 | 30-JAN-15:00 | 128316.47 | 23-JAN-14:00 | 11041.02 | 30-JAN-15:00 | 40796.71 | 23-JAN-14:00 | 0.00 |
February | 0.531444E+12 | 0.133527E+12 | 672.00 | 0.518447E+12 | 0.129971E+11 | 0.00 | 0.62 | 06-FEB-15:00 | 0.53 | 01-FEB-05:00 | 231326.11 | 07-FEB-16:10 | 221426.78 | 06-FEB-15:00 | 11782.96 | 07-FEB-16:10 | 77558.47 | 06-FEB-15:00 | 0.00 |
March | 0.833206E+12 | 0.224349E+12 | 744.00 | 0.821093E+12 | 0.121133E+11 | 0.00 | 0.98 | 31-MAR-23:15 | 0.74 | 08-MAR-06:00 | 402265.84 | 31-MAR-23:05 | 392623.23 | 31-MAR-24:00 | 11962.01 | 28-MAR-16:00 | 126313.61 | 27-MAR-11:00 | 0.00 |
April | 0.104090E+13 | 0.302996E+12 | 720.00 | 0.102843E+13 | 0.124766E+11 | 0.00 | 1.00 | 01-APR-09:50 | 0.42 | 30-APR-23:20 | 419476.59 | 10-APR-09:50 | 404651.18 | 27-APR-03:45 | 17480.17 | 10-APR-10:00 | 154239.72 | 28-APR-12:00 | 0.00 |
May | 0.360181E+12 | 0.122547E+12 | 744.00 | 0.342108E+12 | 0.180727E+11 | 0.00 | 0.61 | 31-MAY-23:13 | 0.34 | 03-MAY-06:00 | 224407.54 | 31-MAY-23:03 | 214285.53 | 31-MAY-23:57 | 15774.47 | 30-MAY-00:53 | 77732.30 | 31-MAY-23:13 | 0.00 |
June | 0.597576E+12 | 0.208681E+12 | 720.00 | 0.569761E+12 | 0.278145E+11 | 0.00 | 0.84 | 30-JUN-24:00 | 0.58 | 07-JUN-05:20 | 322674.87 | 30-JUN-23:03 | 305504.36 | 30-JUN-23:55 | 18825.83 | 08-JUN-13:00 | 107095.64 | 30-JUN-24:00 | 0.00 |
July | 0.871066E+12 | 0.319054E+12 | 744.00 | 0.838103E+12 | 0.329630E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.81 | 03-JUL-06:00 | 398439.66 | 31-JUL-24:00 | 386336.81 | 31-JUL-24:00 | 22105.15 | 20-JUL-11:00 | 152047.99 | 21-JUL-12:00 | 0.00 |
August | 0.108902E+13 | 0.373178E+12 | 744.00 | 0.105868E+13 | 0.303381E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.46 | 31-AUG-24:00 | 421416.30 | 04-AUG-14:00 | 401839.88 | 15-AUG-07:00 | 23676.72 | 31-AUG-23:13 | 164173.94 | 16-AUG-12:00 | 0.00 |
September | 0.367461E+12 | 0.127236E+12 | 720.00 | 0.336754E+12 | 0.307075E+11 | 0.00 | 0.62 | 30-SEP-23:05 | 0.36 | 26-SEP-06:00 | 235796.57 | 30-SEP-23:05 | 213816.56 | 30-SEP-24:00 | 22710.37 | 30-SEP-23:05 | 72448.00 | 30-SEP-23:15 | 0.00 |
October | 0.612845E+12 | 0.196043E+12 | 744.00 | 0.588588E+12 | 0.242565E+11 | 0.00 | 0.81 | 31-OCT-23:15 | 0.56 | 29-OCT-07:00 | 312873.49 | 31-OCT-23:10 | 305161.99 | 31-OCT-24:00 | 19207.94 | 07-OCT-10:10 | 94284.91 | 31-OCT-23:30 | 0.00 |
November | 0.819101E+12 | 0.235334E+12 | 720.00 | 0.802275E+12 | 0.168268E+11 | 0.00 | 0.87 | 01-NOV-14:00 | 0.75 | 26-NOV-05:10 | 328346.44 | 01-NOV-15:00 | 314981.26 | 13-NOV-15:00 | 15362.52 | 01-NOV-15:00 | 113457.28 | 01-NOV-14:00 | 0.00 |
December | 0.108215E+13 | 0.274445E+12 | 744.00 | 0.106754E+13 | 0.146048E+11 | 0.00 | 1.00 | 01-DEC-09:40 | 0.94 | 30-DEC-06:00 | 412267.48 | 05-DEC-22:00 | 403838.01 | 06-DEC-22:02 | 13079.89 | 18-DEC-05:00 | 125770.49 | 10-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.854460E+13 | 0.260053E+13 | 8760.00 | 0.830057E+13 | 0.244030E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.339644E+12 | 0.831406E+11 | 672.00 | 0.328785E+12 | 0.108587E+11 | 0.00 | 0.37 | 0.32 | 137130.25 | 128316.47 | 11041.02 | 40796.71 | 0.00 | ||||||
Maximum of Months | 0.108902E+13 | 0.373178E+12 | 744.00 | 0.106754E+13 | 0.329630E+11 | 0.00 | 1.00 | 0.94 | 421416.30 | 404651.18 | 23676.72 | 164173.94 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.551516E+10 | 0.134824E+10 | 744.00 | 0.517618E+10 | 0.338979E+09 | 0.00 | 0.32 | 29-JAN-17:35 | 0.19 | 21-JAN-07:50 | 2624.64 | 29-JAN-17:35 | 2361.35 | 29-JAN-17:35 | 418.48 | 30-JAN-15:05 | 732.25 | 23-JAN-14:00 | 0.00 |
February | 0.992132E+10 | 0.246809E+10 | 672.00 | 0.947093E+10 | 0.450381E+09 | 0.00 | 0.57 | 05-FEB-15:52 | 0.42 | 01-FEB-07:00 | 4722.88 | 07-FEB-16:10 | 4429.85 | 05-FEB-17:17 | 488.50 | 07-FEB-16:10 | 1508.22 | 05-FEB-15:52 | 0.00 |
March | 0.162045E+11 | 0.431848E+10 | 744.00 | 0.157433E+11 | 0.461171E+09 | 0.00 | 0.91 | 31-MAR-23:05 | 0.63 | 08-MAR-07:00 | 8086.57 | 31-MAR-23:05 | 7630.39 | 31-MAR-24:00 | 489.28 | 28-MAR-16:10 | 2473.86 | 27-MAR-11:00 | 0.00 |
April | 0.210031E+11 | 0.611956E+10 | 720.00 | 0.204204E+11 | 0.582716E+09 | 0.00 | 1.00 | 02-APR-10:13 | 0.39 | 30-APR-23:42 | 8727.72 | 30-APR-21:55 | 8401.51 | 02-APR-16:30 | 584.52 | 29-APR-19:55 | 3262.37 | 28-APR-12:00 | 0.00 |
May | 0.708486E+10 | 0.234426E+10 | 744.00 | 0.635248E+10 | 0.732383E+09 | 0.00 | 0.58 | 31-MAY-23:13 | 0.27 | 03-MAY-07:00 | 4633.16 | 31-MAY-23:03 | 4218.18 | 31-MAY-23:57 | 654.14 | 30-MAY-02:00 | 1553.88 | 31-MAY-23:13 | 0.00 |
June | 0.123721E+11 | 0.418562E+10 | 720.00 | 0.111786E+11 | 0.119354E+10 | 0.00 | 0.80 | 30-JUN-23:03 | 0.52 | 03-JUN-06:40 | 6793.06 | 30-JUN-23:03 | 6038.24 | 30-JUN-24:00 | 797.31 | 30-JUN-23:03 | 2165.07 | 30-JUN-24:00 | 0.00 |
July | 0.183288E+11 | 0.650562E+10 | 744.00 | 0.168523E+11 | 0.147653E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.74 | 03-JUL-06:30 | 8518.00 | 31-JUL-24:00 | 7838.26 | 31-JUL-24:00 | 955.25 | 20-JUL-14:00 | 3046.09 | 30-JUL-13:55 | 0.00 |
August | 0.226745E+11 | 0.790612E+10 | 744.00 | 0.211559E+11 | 0.151859E+10 | 0.00 | 1.00 | 01-AUG-00:03 | 0.39 | 31-AUG-23:05 | 8828.76 | 08-AUG-03:55 | 8213.07 | 14-AUG-03:23 | 947.88 | 30-AUG-20:00 | 3475.99 | 16-AUG-12:00 | 0.00 |
September | 0.756274E+10 | 0.251413E+10 | 720.00 | 0.629374E+10 | 0.126900E+10 | 0.00 | 0.59 | 30-SEP-23:05 | 0.29 | 26-SEP-07:00 | 5074.05 | 30-SEP-23:05 | 4102.64 | 30-SEP-24:00 | 997.33 | 30-SEP-23:05 | 1478.46 | 30-SEP-23:15 | 0.00 |
October | 0.123209E+11 | 0.384176E+10 | 744.00 | 0.112935E+11 | 0.102739E+10 | 0.00 | 0.74 | 31-OCT-23:15 | 0.48 | 21-OCT-07:00 | 6267.10 | 31-OCT-23:10 | 5925.20 | 31-OCT-24:00 | 848.72 | 07-OCT-10:10 | 1847.25 | 31-OCT-23:20 | 0.00 |
November | 0.162031E+11 | 0.458045E+10 | 720.00 | 0.154801E+11 | 0.723012E+09 | 0.00 | 0.83 | 01-NOV-14:05 | 0.66 | 22-NOV-07:00 | 6860.66 | 01-NOV-16:00 | 6484.26 | 12-NOV-17:08 | 666.22 | 01-NOV-15:00 | 2290.37 | 01-NOV-14:00 | 0.00 |
December | 0.212104E+11 | 0.534004E+10 | 744.00 | 0.206562E+11 | 0.554175E+09 | 0.00 | 0.98 | 05-DEC-17:00 | 0.81 | 30-DEC-07:40 | 8575.04 | 05-DEC-17:00 | 8165.62 | 03-DEC-17:07 | 567.17 | 05-DEC-17:00 | 2583.27 | 10-DEC-12:53 | 0.00 |
Annual Sum or Average | 0.170401E+12 | 0.514724E+11 | 8760.00 | 0.160074E+12 | 0.103279E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.551516E+10 | 0.134824E+10 | 672.00 | 0.517618E+10 | 0.338979E+09 | 0.00 | 0.32 | 0.19 | 2624.64 | 2361.35 | 418.48 | 732.25 | 0.00 | ||||||
Maximum of Months | 0.226745E+11 | 0.790612E+10 | 744.00 | 0.211559E+11 | 0.151859E+10 | 0.00 | 1.00 | 0.81 | 8828.76 | 8401.51 | 997.33 | 3475.99 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.454724E+11 | 0.112641E+11 | 744.00 | 0.422358E+11 | 0.323663E+10 | 0.00 | 0.30 | 29-JAN-17:23 | 0.14 | 21-JAN-08:00 | 23476.49 | 30-JAN-15:00 | 20681.55 | 29-JAN-17:35 | 4080.24 | 30-JAN-15:05 | 6600.81 | 23-JAN-14:00 | 0.00 |
February | 0.901720E+11 | 0.225690E+11 | 672.00 | 0.857289E+11 | 0.444314E+10 | 0.00 | 0.57 | 07-FEB-16:10 | 0.38 | 13-FEB-07:00 | 44997.22 | 07-FEB-16:10 | 40981.91 | 05-FEB-17:15 | 4851.18 | 07-FEB-16:10 | 14243.06 | 06-FEB-15:00 | 0.00 |
March | 0.152657E+12 | 0.407784E+11 | 744.00 | 0.148072E+12 | 0.458503E+10 | 0.00 | 0.91 | 31-MAR-23:15 | 0.60 | 08-MAR-07:00 | 77708.23 | 31-MAR-23:05 | 73273.03 | 31-MAR-24:00 | 4868.23 | 28-MAR-16:10 | 23616.70 | 27-MAR-11:00 | 0.00 |
April | 0.199747E+12 | 0.582333E+11 | 720.00 | 0.193927E+12 | 0.582026E+10 | 0.00 | 1.00 | 02-APR-10:42 | 0.33 | 30-APR-23:42 | 82880.72 | 30-APR-17:55 | 79537.13 | 23-APR-16:45 | 5811.65 | 30-APR-15:00 | 31145.30 | 28-APR-12:00 | 0.00 |
May | 0.669432E+11 | 0.221552E+11 | 744.00 | 0.597086E+11 | 0.723459E+10 | 0.00 | 0.59 | 31-MAY-23:13 | 0.26 | 03-MAY-07:00 | 44948.20 | 31-MAY-23:03 | 40724.31 | 31-MAY-23:57 | 6451.06 | 30-MAY-02:00 | 15025.47 | 31-MAY-23:13 | 0.00 |
June | 0.117891E+12 | 0.398574E+11 | 720.00 | 0.106026E+12 | 0.118653E+11 | 0.00 | 0.81 | 30-JUN-23:03 | 0.51 | 03-JUN-06:50 | 65838.35 | 30-JUN-23:03 | 58139.89 | 30-JUN-24:00 | 8052.79 | 30-JUN-23:03 | 20871.35 | 30-JUN-24:00 | 0.00 |
July | 0.174738E+12 | 0.619783E+11 | 744.00 | 0.160019E+12 | 0.147186E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.73 | 03-JUL-06:00 | 81595.75 | 31-JUL-24:00 | 74841.97 | 31-JUL-24:00 | 9520.73 | 20-JUL-14:00 | 28935.57 | 21-JUL-12:00 | 0.00 |
August | 0.215187E+12 | 0.754417E+11 | 744.00 | 0.199897E+12 | 0.152899E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.34 | 31-AUG-23:05 | 83763.74 | 08-AUG-04:53 | 77407.28 | 06-AUG-05:00 | 9503.34 | 30-AUG-20:00 | 33179.17 | 16-AUG-12:00 | 0.00 |
September | 0.712369E+11 | 0.236623E+11 | 720.00 | 0.586946E+11 | 0.125424E+11 | 0.00 | 0.60 | 30-SEP-23:05 | 0.28 | 26-SEP-07:00 | 49351.90 | 30-SEP-23:05 | 39447.46 | 30-SEP-23:40 | 10142.41 | 30-SEP-23:05 | 14305.17 | 30-SEP-23:15 | 0.00 |
October | 0.117082E+12 | 0.364902E+11 | 744.00 | 0.106876E+12 | 0.102062E+11 | 0.00 | 0.75 | 31-OCT-23:45 | 0.47 | 21-OCT-07:00 | 60581.82 | 31-OCT-23:10 | 57263.88 | 31-OCT-24:00 | 8439.53 | 07-OCT-10:10 | 17827.23 | 31-OCT-23:30 | 0.00 |
November | 0.153600E+12 | 0.434563E+11 | 720.00 | 0.146405E+12 | 0.719537E+10 | 0.00 | 0.83 | 01-NOV-14:00 | 0.64 | 22-NOV-07:00 | 65968.60 | 01-NOV-16:00 | 61058.50 | 05-NOV-16:54 | 6636.86 | 01-NOV-15:00 | 21999.61 | 01-NOV-14:00 | 0.00 |
December | 0.198465E+12 | 0.501380E+11 | 744.00 | 0.192937E+12 | 0.552846E+10 | 0.00 | 0.97 | 05-DEC-17:00 | 0.78 | 30-DEC-07:50 | 81735.52 | 05-DEC-17:00 | 76100.32 | 04-DEC-17:00 | 5659.07 | 05-DEC-17:00 | 24206.20 | 10-DEC-12:10 | 0.00 |
Annual Sum or Average | 0.160319E+13 | 0.486024E+12 | 8760.00 | 0.150053E+13 | 0.102666E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.454724E+11 | 0.112641E+11 | 672.00 | 0.422358E+11 | 0.323663E+10 | 0.00 | 0.30 | 0.14 | 23476.49 | 20681.55 | 4080.24 | 6600.81 | 0.00 | ||||||
Maximum of Months | 0.215187E+12 | 0.754417E+11 | 744.00 | 0.199897E+12 | 0.152899E+11 | 0.00 | 1.00 | 0.78 | 83763.74 | 79537.13 | 10142.41 | 33179.17 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.406309E+10 | 0.102087E+10 | 744.00 | 0.374875E+10 | 0.314332E+09 | 0.00 | 0.31 | 29-JAN-17:35 | 0.07 | 01-JAN-08:00 | 2387.53 | 29-JAN-17:35 | 2129.50 | 29-JAN-17:35 | 411.08 | 30-JAN-15:05 | 677.06 | 23-JAN-14:00 | 0.00 |
February | 0.875514E+10 | 0.220466E+10 | 672.00 | 0.831257E+10 | 0.442572E+09 | 0.00 | 0.57 | 07-FEB-16:10 | 0.33 | 13-FEB-08:00 | 4557.45 | 07-FEB-16:10 | 4224.39 | 05-FEB-17:05 | 486.12 | 07-FEB-16:10 | 1445.43 | 06-FEB-15:00 | 0.00 |
March | 0.151531E+11 | 0.406118E+10 | 744.00 | 0.146949E+11 | 0.458267E+09 | 0.00 | 0.90 | 31-MAR-23:15 | 0.57 | 08-MAR-07:00 | 7725.16 | 31-MAR-23:05 | 7275.77 | 31-MAR-24:00 | 487.26 | 28-MAR-16:10 | 2375.22 | 27-MAR-11:00 | 0.00 |
April | 0.200087E+11 | 0.584302E+10 | 720.00 | 0.194267E+11 | 0.582048E+09 | 0.00 | 1.00 | 02-APR-10:53 | 0.34 | 30-APR-23:25 | 8407.67 | 30-APR-17:55 | 8105.86 | 02-APR-16:30 | 582.56 | 29-APR-19:55 | 3144.92 | 28-APR-12:00 | 0.00 |
May | 0.684854E+10 | 0.226796E+10 | 744.00 | 0.612129E+10 | 0.727249E+09 | 0.00 | 0.59 | 31-MAY-23:13 | 0.25 | 03-MAY-07:00 | 4547.91 | 31-MAY-23:03 | 4132.89 | 31-MAY-23:57 | 649.97 | 30-MAY-02:00 | 1521.51 | 31-MAY-23:13 | 0.00 |
June | 0.119506E+11 | 0.404184E+10 | 720.00 | 0.107616E+11 | 0.118900E+10 | 0.00 | 0.81 | 30-JUN-23:03 | 0.50 | 03-JUN-06:50 | 6603.63 | 30-JUN-23:03 | 5835.59 | 30-JUN-24:00 | 804.17 | 30-JUN-23:03 | 2096.27 | 30-JUN-24:00 | 0.00 |
July | 0.177082E+11 | 0.628135E+10 | 744.00 | 0.162346E+11 | 0.147362E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.73 | 03-JUL-06:50 | 8231.73 | 31-JUL-24:00 | 7555.28 | 31-JUL-24:00 | 954.14 | 20-JUL-14:00 | 3006.06 | 30-JUL-13:55 | 0.00 |
August | 0.217255E+11 | 0.761658E+10 | 744.00 | 0.201965E+11 | 0.152900E+10 | 0.00 | 1.00 | 01-AUG-00:03 | 0.35 | 31-AUG-23:05 | 8447.88 | 20-AUG-21:04 | 7830.47 | 06-AUG-05:00 | 955.67 | 30-AUG-20:00 | 3350.35 | 16-AUG-12:00 | 0.00 |
September | 0.727408E+10 | 0.241804E+10 | 720.00 | 0.601446E+10 | 0.125962E+10 | 0.00 | 0.60 | 30-SEP-23:05 | 0.27 | 26-SEP-07:00 | 4985.78 | 30-SEP-23:05 | 3990.48 | 30-SEP-24:00 | 1003.26 | 30-SEP-23:05 | 1446.17 | 30-SEP-23:10 | 0.00 |
October | 0.117850E+11 | 0.367727E+10 | 744.00 | 0.107634E+11 | 0.102157E+10 | 0.00 | 0.75 | 31-OCT-23:55 | 0.46 | 21-OCT-07:00 | 6055.23 | 31-OCT-23:10 | 5727.08 | 31-OCT-24:00 | 846.59 | 07-OCT-10:10 | 1787.83 | 09-OCT-15:02 | 0.00 |
November | 0.152961E+11 | 0.433841E+10 | 720.00 | 0.145768E+11 | 0.719238E+09 | 0.00 | 0.83 | 01-NOV-14:05 | 0.61 | 22-NOV-07:30 | 6649.41 | 01-NOV-15:00 | 6270.86 | 05-NOV-16:42 | 664.55 | 01-NOV-15:00 | 2217.01 | 01-NOV-14:00 | 0.00 |
December | 0.195495E+11 | 0.496020E+10 | 744.00 | 0.189972E+11 | 0.552367E+09 | 0.00 | 0.97 | 05-DEC-17:00 | 0.73 | 31-DEC-07:30 | 8199.30 | 05-DEC-17:00 | 7652.99 | 03-DEC-16:42 | 565.82 | 05-DEC-17:00 | 2430.57 | 10-DEC-12:53 | 0.00 |
Annual Sum or Average | 0.160118E+12 | 0.487314E+11 | 8760.00 | 0.149849E+12 | 0.102689E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.406309E+10 | 0.102087E+10 | 672.00 | 0.374875E+10 | 0.314332E+09 | 0.00 | 0.31 | 0.07 | 2387.53 | 2129.50 | 411.08 | 677.06 | 0.00 | ||||||
Maximum of Months | 0.217255E+11 | 0.761658E+10 | 744.00 | 0.201965E+11 | 0.152900E+10 | 0.00 | 1.00 | 0.73 | 8447.88 | 8105.86 | 1003.26 | 3350.35 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 120.39 | 277.05 | 0.00 | 0.00 | 0.00 |
February | 128.47 | 0.00 | 128.47 | 169.83 | 233.15 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 249.29 | 174.55 | 0.00 | 0.00 | 0.00 |
April | 166.26 | 0.34 | 165.91 | 363.29 | 106.66 | 0.00 | 0.00 | 0.00 |
May | 187.14 | 5.49 | 181.65 | 558.60 | 24.96 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.24 | 642.13 | 6.42 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.56 | 712.04 | 0.26 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.74 | 691.82 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.89 | 532.39 | 8.68 | 0.00 | 0.00 | 0.00 |
October | 138.21 | 0.00 | 138.21 | 378.47 | 42.49 | 0.00 | 0.00 | 0.00 |
November | 118.65 | 0.00 | 118.65 | 236.93 | 124.38 | 0.00 | 0.00 | 0.00 |
December | 104.61 | 0.00 | 104.61 | 134.87 | 231.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 400.57 | 101.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 0.00 | 104.61 | 120.39 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.24 | 712.04 | 277.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 120.39 | 277.05 | 0.00 | 0.00 | 0.00 |
February | 128.47 | 0.00 | 128.47 | 169.83 | 233.15 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 249.29 | 174.55 | 0.00 | 0.00 | 0.00 |
April | 166.26 | 0.34 | 165.91 | 363.29 | 106.66 | 0.00 | 0.00 | 0.00 |
May | 187.14 | 5.49 | 181.65 | 558.60 | 24.96 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.24 | 642.13 | 6.42 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.56 | 712.04 | 0.26 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.74 | 691.82 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.89 | 532.39 | 8.68 | 0.00 | 0.00 | 0.00 |
October | 138.21 | 0.00 | 138.21 | 378.47 | 42.49 | 0.00 | 0.00 | 0.00 |
November | 118.65 | 0.00 | 118.65 | 236.93 | 124.38 | 0.00 | 0.00 | 0.00 |
December | 104.61 | 0.00 | 104.61 | 134.87 | 231.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 400.57 | 101.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 0.00 | 104.61 | 120.39 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.24 | 712.04 | 277.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 120.39 | 277.05 | 0.00 | 0.00 | 0.00 |
February | 128.47 | 0.00 | 128.47 | 169.83 | 233.15 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 249.29 | 174.55 | 0.00 | 0.00 | 0.00 |
April | 166.26 | 0.34 | 165.91 | 363.29 | 106.66 | 0.00 | 0.00 | 0.00 |
May | 187.14 | 5.49 | 181.65 | 558.60 | 24.96 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.24 | 642.13 | 6.42 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.56 | 712.04 | 0.26 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.74 | 691.82 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.89 | 532.39 | 8.68 | 0.00 | 0.00 | 0.00 |
October | 138.21 | 0.00 | 138.21 | 378.47 | 42.49 | 0.00 | 0.00 | 0.00 |
November | 118.65 | 0.00 | 118.65 | 236.93 | 124.38 | 0.00 | 0.00 | 0.00 |
December | 104.61 | 0.00 | 104.61 | 134.87 | 231.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 400.57 | 101.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 0.00 | 104.61 | 120.39 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.24 | 712.04 | 277.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 120.39 | 277.05 | 0.00 | 0.00 | 0.00 |
February | 128.47 | 0.00 | 128.47 | 169.83 | 233.15 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 249.29 | 174.55 | 0.00 | 0.00 | 0.00 |
April | 166.26 | 0.34 | 165.91 | 363.29 | 106.66 | 0.00 | 0.00 | 0.00 |
May | 187.14 | 5.49 | 181.65 | 558.60 | 24.96 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.24 | 642.13 | 6.42 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.56 | 712.04 | 0.26 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.74 | 691.82 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.89 | 532.39 | 8.68 | 0.00 | 0.00 | 0.00 |
October | 138.21 | 0.00 | 138.21 | 378.47 | 42.49 | 0.00 | 0.00 | 0.00 |
November | 118.65 | 0.00 | 118.65 | 236.93 | 124.38 | 0.00 | 0.00 | 0.00 |
December | 104.61 | 0.00 | 104.61 | 134.87 | 231.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 400.57 | 101.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 0.00 | 104.61 | 120.39 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.24 | 712.04 | 277.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 120.38 | 277.03 | 0.00 | 0.00 | 0.00 |
February | 128.46 | 0.00 | 128.46 | 169.82 | 233.14 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 249.28 | 174.55 | 0.00 | 0.00 | 0.00 |
April | 166.25 | 0.34 | 165.91 | 363.28 | 106.65 | 0.00 | 0.00 | 0.00 |
May | 187.13 | 5.49 | 181.64 | 558.58 | 24.96 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.23 | 642.11 | 6.42 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.55 | 712.01 | 0.26 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.73 | 691.79 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.88 | 532.36 | 8.67 | 0.00 | 0.00 | 0.00 |
October | 138.20 | 0.00 | 138.20 | 378.45 | 42.49 | 0.00 | 0.00 | 0.00 |
November | 118.64 | 0.00 | 118.64 | 236.92 | 124.37 | 0.00 | 0.00 | 0.00 |
December | 104.60 | 0.00 | 104.60 | 134.86 | 231.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 400.55 | 101.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.60 | 0.00 | 104.60 | 120.38 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.23 | 712.01 | 277.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 225.26 | 68.15 | 157.11 | 300.43 | 285.26 | 0.00 | 0.00 | 0.00 |
February | 245.49 | 66.53 | 178.96 | 368.35 | 239.80 | 0.00 | 0.00 | 0.00 |
March | 271.17 | 66.83 | 204.33 | 474.85 | 178.96 | 0.00 | 0.00 | 0.00 |
April | 330.15 | 96.20 | 233.96 | 682.08 | 108.21 | 0.00 | 0.00 | 0.00 |
May | 368.96 | 117.55 | 251.41 | 923.39 | 26.65 | 0.00 | 0.00 | 0.00 |
June | 361.34 | 110.50 | 250.84 | 973.70 | 5.81 | 0.00 | 0.00 | 0.00 |
July | 337.25 | 97.23 | 240.02 | 1048.60 | 0.18 | 0.00 | 0.00 | 0.00 |
August | 345.34 | 105.99 | 239.35 | 1078.88 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 324.66 | 100.35 | 224.31 | 880.72 | 8.71 | 0.00 | 0.00 | 0.00 |
October | 294.60 | 96.24 | 198.35 | 688.60 | 42.40 | 0.00 | 0.00 | 0.00 |
November | 246.87 | 78.20 | 168.68 | 476.24 | 125.72 | 0.00 | 0.00 | 0.00 |
December | 199.82 | 54.82 | 145.00 | 296.42 | 231.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 296.11 | 88.31 | 207.80 | 684.50 | 103.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.82 | 54.82 | 145.00 | 296.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 368.96 | 117.55 | 251.41 | 1078.88 | 285.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 225.26 | 68.15 | 157.11 | 300.43 | 285.26 | 0.00 | 0.00 | 0.00 |
February | 245.49 | 66.53 | 178.96 | 368.35 | 239.80 | 0.00 | 0.00 | 0.00 |
March | 271.17 | 66.83 | 204.33 | 474.85 | 178.96 | 0.00 | 0.00 | 0.00 |
April | 330.15 | 96.20 | 233.96 | 682.08 | 108.21 | 0.00 | 0.00 | 0.00 |
May | 368.96 | 117.55 | 251.41 | 923.39 | 26.65 | 0.00 | 0.00 | 0.00 |
June | 361.34 | 110.50 | 250.84 | 973.70 | 5.81 | 0.00 | 0.00 | 0.00 |
July | 337.25 | 97.23 | 240.02 | 1048.60 | 0.18 | 0.00 | 0.00 | 0.00 |
August | 345.34 | 105.99 | 239.35 | 1078.88 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 324.66 | 100.35 | 224.31 | 880.72 | 8.71 | 0.00 | 0.00 | 0.00 |
October | 294.60 | 96.24 | 198.35 | 688.60 | 42.40 | 0.00 | 0.00 | 0.00 |
November | 246.87 | 78.20 | 168.68 | 476.24 | 125.72 | 0.00 | 0.00 | 0.00 |
December | 199.82 | 54.82 | 145.00 | 296.42 | 231.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 296.11 | 88.31 | 207.80 | 684.50 | 103.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.82 | 54.82 | 145.00 | 296.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 368.96 | 117.55 | 251.41 | 1078.88 | 285.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 225.26 | 68.15 | 157.11 | 300.42 | 285.25 | 0.00 | 0.00 | 0.00 |
February | 245.48 | 66.53 | 178.96 | 368.34 | 239.80 | 0.00 | 0.00 | 0.00 |
March | 271.16 | 66.83 | 204.33 | 474.84 | 178.96 | 0.00 | 0.00 | 0.00 |
April | 330.15 | 96.19 | 233.95 | 682.07 | 108.21 | 0.00 | 0.00 | 0.00 |
May | 368.95 | 117.55 | 251.40 | 923.37 | 26.65 | 0.00 | 0.00 | 0.00 |
June | 361.33 | 110.50 | 250.83 | 973.69 | 5.81 | 0.00 | 0.00 | 0.00 |
July | 337.25 | 97.23 | 240.02 | 1048.58 | 0.18 | 0.00 | 0.00 | 0.00 |
August | 345.33 | 105.99 | 239.35 | 1078.86 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 324.65 | 100.35 | 224.31 | 880.70 | 8.71 | 0.00 | 0.00 | 0.00 |
October | 294.59 | 96.24 | 198.35 | 688.59 | 42.40 | 0.00 | 0.00 | 0.00 |
November | 246.87 | 78.20 | 168.67 | 476.23 | 125.72 | 0.00 | 0.00 | 0.00 |
December | 199.82 | 54.82 | 144.99 | 296.42 | 231.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 296.10 | 88.30 | 207.80 | 684.49 | 103.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.82 | 54.82 | 144.99 | 296.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 368.95 | 117.55 | 251.40 | 1078.86 | 285.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.21 | 170.29 | 191.92 | 567.60 | 267.05 | 0.00 | 0.00 | 0.00 |
February | 340.13 | 139.13 | 201.00 | 568.15 | 231.26 | 0.00 | 0.00 | 0.00 |
March | 279.94 | 76.00 | 203.94 | 523.99 | 179.27 | 0.00 | 0.00 | 0.00 |
April | 220.06 | 23.33 | 196.73 | 487.66 | 111.13 | 0.00 | 0.00 | 0.00 |
May | 186.41 | 2.85 | 183.55 | 556.82 | 25.70 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.34 | 588.30 | 5.07 | 0.00 | 0.00 | 0.00 |
July | 175.55 | 1.49 | 174.06 | 691.04 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 203.62 | 14.43 | 189.19 | 766.27 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 268.48 | 61.53 | 206.95 | 772.41 | 9.71 | 0.00 | 0.00 | 0.00 |
October | 351.49 | 139.74 | 211.75 | 802.95 | 47.11 | 0.00 | 0.00 | 0.00 |
November | 387.76 | 186.93 | 200.83 | 745.79 | 129.15 | 0.00 | 0.00 | 0.00 |
December | 359.96 | 177.81 | 182.15 | 600.43 | 227.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.55 | 82.51 | 193.03 | 639.77 | 102.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.55 | 0.22 | 174.06 | 487.66 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.76 | 186.93 | 211.75 | 802.95 | 267.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.21 | 170.29 | 191.92 | 567.60 | 267.05 | 0.00 | 0.00 | 0.00 |
February | 340.13 | 139.13 | 201.00 | 568.15 | 231.26 | 0.00 | 0.00 | 0.00 |
March | 279.94 | 76.00 | 203.94 | 523.99 | 179.27 | 0.00 | 0.00 | 0.00 |
April | 220.06 | 23.33 | 196.73 | 487.66 | 111.13 | 0.00 | 0.00 | 0.00 |
May | 186.41 | 2.85 | 183.55 | 556.82 | 25.70 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.34 | 588.30 | 5.07 | 0.00 | 0.00 | 0.00 |
July | 175.55 | 1.49 | 174.06 | 691.04 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 203.62 | 14.43 | 189.19 | 766.27 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 268.48 | 61.53 | 206.95 | 772.41 | 9.71 | 0.00 | 0.00 | 0.00 |
October | 351.49 | 139.74 | 211.75 | 802.95 | 47.11 | 0.00 | 0.00 | 0.00 |
November | 387.76 | 186.93 | 200.83 | 745.78 | 129.15 | 0.00 | 0.00 | 0.00 |
December | 359.96 | 177.81 | 182.15 | 600.43 | 227.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.54 | 82.51 | 193.03 | 639.77 | 102.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.55 | 0.22 | 174.06 | 487.66 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.76 | 186.93 | 211.75 | 802.95 | 267.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.21 | 170.29 | 191.92 | 567.60 | 267.05 | 0.00 | 0.00 | 0.00 |
February | 340.13 | 139.13 | 201.00 | 568.15 | 231.26 | 0.00 | 0.00 | 0.00 |
March | 279.94 | 76.00 | 203.94 | 523.99 | 179.27 | 0.00 | 0.00 | 0.00 |
April | 220.06 | 23.33 | 196.73 | 487.66 | 111.13 | 0.00 | 0.00 | 0.00 |
May | 186.41 | 2.85 | 183.55 | 556.82 | 25.70 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.34 | 588.30 | 5.07 | 0.00 | 0.00 | 0.00 |
July | 175.55 | 1.49 | 174.06 | 691.04 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 203.62 | 14.43 | 189.19 | 766.27 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 268.48 | 61.53 | 206.95 | 772.41 | 9.71 | 0.00 | 0.00 | 0.00 |
October | 351.49 | 139.74 | 211.75 | 802.95 | 47.11 | 0.00 | 0.00 | 0.00 |
November | 387.76 | 186.93 | 200.83 | 745.79 | 129.15 | 0.00 | 0.00 | 0.00 |
December | 359.96 | 177.81 | 182.15 | 600.43 | 227.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.55 | 82.51 | 193.03 | 639.77 | 102.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.55 | 0.22 | 174.06 | 487.66 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.76 | 186.93 | 211.75 | 802.95 | 267.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.21 | 170.29 | 191.92 | 567.60 | 267.05 | 0.00 | 0.00 | 0.00 |
February | 340.13 | 139.13 | 201.00 | 568.15 | 231.26 | 0.00 | 0.00 | 0.00 |
March | 279.94 | 76.00 | 203.94 | 523.99 | 179.27 | 0.00 | 0.00 | 0.00 |
April | 220.06 | 23.33 | 196.73 | 487.66 | 111.13 | 0.00 | 0.00 | 0.00 |
May | 186.41 | 2.85 | 183.55 | 556.82 | 25.70 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.34 | 588.30 | 5.07 | 0.00 | 0.00 | 0.00 |
July | 175.55 | 1.49 | 174.06 | 691.04 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 203.62 | 14.43 | 189.19 | 766.27 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 268.48 | 61.53 | 206.95 | 772.41 | 9.71 | 0.00 | 0.00 | 0.00 |
October | 351.49 | 139.74 | 211.75 | 802.95 | 47.11 | 0.00 | 0.00 | 0.00 |
November | 387.76 | 186.93 | 200.83 | 745.78 | 129.15 | 0.00 | 0.00 | 0.00 |
December | 359.96 | 177.81 | 182.15 | 600.43 | 227.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.54 | 82.51 | 193.03 | 639.77 | 102.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.55 | 0.22 | 174.06 | 487.66 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.76 | 186.93 | 211.75 | 802.95 | 267.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.20 | 170.29 | 191.91 | 567.58 | 267.04 | 0.00 | 0.00 | 0.00 |
February | 340.12 | 139.12 | 200.99 | 568.13 | 231.25 | 0.00 | 0.00 | 0.00 |
March | 279.93 | 76.00 | 203.93 | 523.97 | 179.27 | 0.00 | 0.00 | 0.00 |
April | 220.05 | 23.33 | 196.72 | 487.64 | 111.13 | 0.00 | 0.00 | 0.00 |
May | 186.40 | 2.85 | 183.55 | 556.80 | 25.69 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.33 | 588.28 | 5.07 | 0.00 | 0.00 | 0.00 |
July | 175.54 | 1.49 | 174.05 | 691.01 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 203.61 | 14.43 | 189.19 | 766.24 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 268.47 | 61.53 | 206.94 | 772.38 | 9.70 | 0.00 | 0.00 | 0.00 |
October | 351.48 | 139.73 | 211.74 | 802.92 | 47.11 | 0.00 | 0.00 | 0.00 |
November | 387.75 | 186.92 | 200.83 | 745.76 | 129.14 | 0.00 | 0.00 | 0.00 |
December | 359.95 | 177.80 | 182.14 | 600.41 | 227.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.53 | 82.51 | 193.03 | 639.74 | 102.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.54 | 0.22 | 174.05 | 487.64 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.75 | 186.92 | 211.74 | 802.92 | 267.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 220.91 | 63.45 | 157.46 | 301.05 | 337.66 | 0.00 | 0.00 | 0.00 |
February | 252.26 | 71.93 | 180.33 | 379.62 | 298.17 | 0.00 | 0.00 | 0.00 |
March | 298.81 | 88.46 | 210.35 | 513.36 | 239.64 | 0.00 | 0.00 | 0.00 |
April | 326.55 | 91.74 | 234.81 | 649.32 | 167.93 | 0.00 | 0.00 | 0.00 |
May | 355.45 | 106.40 | 249.05 | 882.38 | 42.77 | 0.00 | 0.00 | 0.00 |
June | 367.32 | 115.79 | 251.53 | 956.34 | 15.57 | 0.00 | 0.00 | 0.00 |
July | 336.98 | 96.40 | 240.58 | 999.00 | 1.43 | 0.00 | 0.00 | 0.00 |
August | 345.70 | 105.11 | 240.59 | 999.99 | 1.53 | 0.00 | 0.00 | 0.00 |
September | 328.85 | 103.32 | 225.54 | 863.33 | 17.77 | 0.00 | 0.00 | 0.00 |
October | 292.25 | 94.41 | 197.85 | 666.04 | 73.52 | 0.00 | 0.00 | 0.00 |
November | 251.16 | 82.14 | 169.02 | 475.11 | 182.32 | 0.00 | 0.00 | 0.00 |
December | 210.26 | 63.56 | 146.70 | 308.87 | 315.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 299.04 | 90.29 | 208.76 | 667.79 | 140.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 210.26 | 63.45 | 146.70 | 301.05 | 1.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.32 | 115.79 | 251.53 | 999.99 | 337.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 220.91 | 63.45 | 157.46 | 301.05 | 337.66 | 0.00 | 0.00 | 0.00 |
February | 252.26 | 71.93 | 180.33 | 379.62 | 298.17 | 0.00 | 0.00 | 0.00 |
March | 298.81 | 88.46 | 210.35 | 513.36 | 239.64 | 0.00 | 0.00 | 0.00 |
April | 326.55 | 91.74 | 234.81 | 649.32 | 167.93 | 0.00 | 0.00 | 0.00 |
May | 355.45 | 106.40 | 249.05 | 882.38 | 42.77 | 0.00 | 0.00 | 0.00 |
June | 367.32 | 115.79 | 251.53 | 956.34 | 15.57 | 0.00 | 0.00 | 0.00 |
July | 336.98 | 96.40 | 240.58 | 999.00 | 1.43 | 0.00 | 0.00 | 0.00 |
August | 345.70 | 105.11 | 240.59 | 999.99 | 1.53 | 0.00 | 0.00 | 0.00 |
September | 328.85 | 103.32 | 225.54 | 863.33 | 17.77 | 0.00 | 0.00 | 0.00 |
October | 292.25 | 94.41 | 197.85 | 666.04 | 73.52 | 0.00 | 0.00 | 0.00 |
November | 251.16 | 82.14 | 169.02 | 475.11 | 182.32 | 0.00 | 0.00 | 0.00 |
December | 210.26 | 63.56 | 146.70 | 308.87 | 315.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 299.04 | 90.29 | 208.76 | 667.79 | 140.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 210.26 | 63.45 | 146.70 | 301.05 | 1.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.32 | 115.79 | 251.53 | 999.99 | 337.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 220.91 | 63.45 | 157.46 | 301.05 | 337.65 | 0.00 | 0.00 | 0.00 |
February | 252.26 | 71.93 | 180.32 | 379.62 | 298.17 | 0.00 | 0.00 | 0.00 |
March | 298.80 | 88.46 | 210.34 | 513.35 | 239.63 | 0.00 | 0.00 | 0.00 |
April | 326.54 | 91.74 | 234.80 | 649.31 | 167.92 | 0.00 | 0.00 | 0.00 |
May | 355.44 | 106.40 | 249.04 | 882.36 | 42.77 | 0.00 | 0.00 | 0.00 |
June | 367.32 | 115.79 | 251.53 | 956.32 | 15.57 | 0.00 | 0.00 | 0.00 |
July | 336.97 | 96.40 | 240.57 | 998.98 | 1.43 | 0.00 | 0.00 | 0.00 |
August | 345.70 | 105.11 | 240.59 | 999.97 | 1.53 | 0.00 | 0.00 | 0.00 |
September | 328.85 | 103.31 | 225.53 | 863.31 | 17.77 | 0.00 | 0.00 | 0.00 |
October | 292.25 | 94.40 | 197.84 | 666.03 | 73.52 | 0.00 | 0.00 | 0.00 |
November | 251.15 | 82.13 | 169.02 | 475.10 | 182.31 | 0.00 | 0.00 | 0.00 |
December | 210.25 | 63.56 | 146.70 | 308.86 | 315.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 299.04 | 90.29 | 208.75 | 667.78 | 140.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 210.25 | 63.45 | 146.70 | 301.05 | 1.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.32 | 115.79 | 251.53 | 999.97 | 337.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 560.36 | 0.00 | 560.36 | 653.71 | 1226.92 | 0.00 | 0.00 | 0.00 |
February | 642.34 | 0.00 | 642.34 | 891.05 | 1041.48 | 0.00 | 0.00 | 0.00 |
March | 737.81 | 0.00 | 737.81 | 1275.22 | 810.05 | 0.00 | 0.00 | 0.00 |
April | 831.27 | 1.71 | 829.56 | 1847.30 | 518.92 | 0.00 | 0.00 | 0.00 |
May | 935.67 | 27.44 | 908.23 | 2813.11 | 128.56 | 0.00 | 0.00 | 0.00 |
June | 1001.81 | 55.62 | 946.19 | 3249.73 | 30.70 | 0.00 | 0.00 | 0.00 |
July | 919.26 | 26.49 | 892.77 | 3624.91 | 0.77 | 0.00 | 0.00 | 0.00 |
August | 855.75 | 7.08 | 848.67 | 3571.97 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 779.51 | 0.09 | 779.42 | 2700.28 | 43.28 | 0.00 | 0.00 | 0.00 |
October | 691.02 | 0.00 | 691.02 | 1930.17 | 213.18 | 0.00 | 0.00 | 0.00 |
November | 593.23 | 0.00 | 593.23 | 1221.65 | 587.63 | 0.00 | 0.00 | 0.00 |
December | 523.03 | 0.00 | 523.03 | 725.38 | 1018.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.36 | 9.90 | 746.46 | 2049.17 | 465.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 523.03 | 0.00 | 523.03 | 653.71 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1001.81 | 55.62 | 946.19 | 3624.91 | 1226.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 675.79 | 204.46 | 471.33 | 911.18 | 797.31 | 0.00 | 0.00 | 0.00 |
February | 736.45 | 199.58 | 536.87 | 1103.56 | 682.84 | 0.00 | 0.00 | 0.00 |
March | 813.49 | 200.49 | 612.99 | 1410.42 | 534.69 | 0.00 | 0.00 | 0.00 |
April | 990.45 | 288.59 | 701.87 | 2021.50 | 351.81 | 0.00 | 0.00 | 0.00 |
May | 1106.86 | 352.65 | 754.21 | 2745.78 | 88.68 | 0.00 | 0.00 | 0.00 |
June | 1084.00 | 331.50 | 752.50 | 2902.41 | 20.38 | 0.00 | 0.00 | 0.00 |
July | 1011.74 | 291.68 | 720.06 | 3133.98 | 0.48 | 0.00 | 0.00 | 0.00 |
August | 1036.01 | 317.97 | 718.04 | 3234.96 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 973.97 | 301.04 | 672.93 | 2624.31 | 29.01 | 0.00 | 0.00 | 0.00 |
October | 883.78 | 288.73 | 595.05 | 2048.64 | 142.67 | 0.00 | 0.00 | 0.00 |
November | 740.61 | 234.59 | 506.02 | 1413.85 | 388.55 | 0.00 | 0.00 | 0.00 |
December | 599.45 | 164.47 | 434.99 | 890.85 | 665.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 888.31 | 264.91 | 623.39 | 2042.23 | 306.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.45 | 164.47 | 434.99 | 890.85 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1106.86 | 352.65 | 754.21 | 3234.96 | 797.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1811.03 | 851.45 | 959.59 | 2820.64 | 1293.20 | 0.00 | 0.00 | 0.00 |
February | 1700.64 | 695.64 | 1005.00 | 2825.30 | 1111.03 | 0.00 | 0.00 | 0.00 |
March | 1399.70 | 380.01 | 1019.69 | 2612.42 | 871.95 | 0.00 | 0.00 | 0.00 |
April | 1100.27 | 116.65 | 983.62 | 2448.55 | 551.98 | 0.00 | 0.00 | 0.00 |
May | 932.02 | 14.27 | 917.75 | 2802.99 | 130.65 | 0.00 | 0.00 | 0.00 |
June | 877.75 | 1.09 | 876.67 | 2988.94 | 22.88 | 0.00 | 0.00 | 0.00 |
July | 877.73 | 7.46 | 870.27 | 3515.48 | 0.31 | 0.00 | 0.00 | 0.00 |
August | 1018.10 | 72.14 | 945.96 | 3923.88 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 1342.37 | 307.64 | 1034.73 | 3869.71 | 50.12 | 0.00 | 0.00 | 0.00 |
October | 1757.43 | 698.68 | 1058.75 | 4004.72 | 246.96 | 0.00 | 0.00 | 0.00 |
November | 1938.80 | 934.65 | 1004.15 | 3707.27 | 648.77 | 0.00 | 0.00 | 0.00 |
December | 1799.79 | 889.04 | 910.75 | 2993.20 | 1093.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1377.71 | 412.56 | 965.15 | 3212.10 | 498.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 877.73 | 1.09 | 870.27 | 2448.55 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1938.80 | 934.65 | 1058.75 | 4004.72 | 1293.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 662.73 | 190.34 | 472.39 | 939.50 | 883.70 | 0.00 | 0.00 | 0.00 |
February | 756.77 | 215.80 | 540.97 | 1179.47 | 755.69 | 0.00 | 0.00 | 0.00 |
March | 896.42 | 265.39 | 631.03 | 1581.98 | 604.10 | 0.00 | 0.00 | 0.00 |
April | 979.63 | 275.22 | 704.41 | 2005.88 | 410.83 | 0.00 | 0.00 | 0.00 |
May | 1066.33 | 319.19 | 747.13 | 2676.09 | 113.81 | 0.00 | 0.00 | 0.00 |
June | 1101.96 | 347.37 | 754.59 | 2934.57 | 29.28 | 0.00 | 0.00 | 0.00 |
July | 1010.93 | 289.21 | 721.72 | 3105.40 | 1.17 | 0.00 | 0.00 | 0.00 |
August | 1037.10 | 315.32 | 721.78 | 3189.56 | 0.40 | 0.00 | 0.00 | 0.00 |
September | 986.55 | 309.95 | 676.60 | 2634.41 | 42.60 | 0.00 | 0.00 | 0.00 |
October | 876.75 | 283.22 | 593.54 | 2043.93 | 183.38 | 0.00 | 0.00 | 0.00 |
November | 753.46 | 246.41 | 507.05 | 1473.33 | 450.37 | 0.00 | 0.00 | 0.00 |
December | 630.76 | 190.67 | 440.10 | 989.61 | 751.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 897.12 | 270.86 | 626.26 | 2067.89 | 350.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 630.76 | 190.34 | 440.10 | 939.50 | 0.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1101.96 | 347.37 | 754.59 | 3189.56 | 883.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 560.36 | 0.00 | 560.36 | 678.45 | 1148.89 | 0.00 | 0.00 | 0.00 |
February | 642.34 | 0.00 | 642.34 | 902.03 | 992.61 | 0.00 | 0.00 | 0.00 |
March | 737.81 | 0.00 | 737.81 | 1269.59 | 788.95 | 0.00 | 0.00 | 0.00 |
April | 831.27 | 1.71 | 829.56 | 1827.25 | 521.62 | 0.00 | 0.00 | 0.00 |
May | 935.67 | 27.44 | 908.23 | 2777.62 | 135.33 | 0.00 | 0.00 | 0.00 |
June | 1001.81 | 55.62 | 946.19 | 3210.20 | 34.25 | 0.00 | 0.00 | 0.00 |
July | 919.26 | 26.49 | 892.77 | 3571.73 | 1.22 | 0.00 | 0.00 | 0.00 |
August | 855.75 | 7.08 | 848.67 | 3524.52 | 0.11 | 0.00 | 0.00 | 0.00 |
September | 779.51 | 0.09 | 779.42 | 2662.82 | 45.84 | 0.00 | 0.00 | 0.00 |
October | 691.02 | 0.00 | 691.02 | 1908.28 | 218.95 | 0.00 | 0.00 | 0.00 |
November | 593.23 | 0.00 | 593.23 | 1215.07 | 574.66 | 0.00 | 0.00 | 0.00 |
December | 523.03 | 0.00 | 523.03 | 739.31 | 966.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.36 | 9.90 | 746.46 | 2030.88 | 449.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 523.03 | 0.00 | 523.03 | 678.45 | 0.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1001.81 | 55.62 | 946.19 | 3571.73 | 1148.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 675.79 | 204.46 | 471.33 | 935.14 | 753.89 | 0.00 | 0.00 | 0.00 |
February | 736.45 | 199.58 | 536.87 | 1117.26 | 654.97 | 0.00 | 0.00 | 0.00 |
March | 813.49 | 200.49 | 612.99 | 1413.63 | 521.97 | 0.00 | 0.00 | 0.00 |
April | 990.45 | 288.59 | 701.87 | 2015.44 | 352.26 | 0.00 | 0.00 | 0.00 |
May | 1106.86 | 352.65 | 754.21 | 2729.58 | 92.21 | 0.00 | 0.00 | 0.00 |
June | 1084.00 | 331.50 | 752.50 | 2884.13 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 1011.74 | 291.68 | 720.06 | 3106.85 | 0.71 | 0.00 | 0.00 | 0.00 |
August | 1036.01 | 317.97 | 718.04 | 3212.35 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 973.97 | 301.04 | 672.93 | 2607.25 | 30.20 | 0.00 | 0.00 | 0.00 |
October | 883.78 | 288.73 | 595.05 | 2040.77 | 144.87 | 0.00 | 0.00 | 0.00 |
November | 740.61 | 234.59 | 506.02 | 1415.97 | 380.14 | 0.00 | 0.00 | 0.00 |
December | 599.45 | 164.47 | 434.99 | 906.60 | 635.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 888.31 | 264.91 | 623.39 | 2037.42 | 297.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.45 | 164.47 | 434.99 | 906.60 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1106.86 | 352.65 | 754.21 | 3212.35 | 753.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1811.03 | 851.45 | 959.59 | 2835.70 | 1229.66 | 0.00 | 0.00 | 0.00 |
February | 1700.64 | 695.64 | 1005.00 | 2825.99 | 1068.80 | 0.00 | 0.00 | 0.00 |
March | 1399.70 | 380.01 | 1019.69 | 2600.96 | 851.50 | 0.00 | 0.00 | 0.00 |
April | 1100.27 | 116.65 | 983.62 | 2427.19 | 552.98 | 0.00 | 0.00 | 0.00 |
May | 932.02 | 14.27 | 917.75 | 2767.26 | 136.74 | 0.00 | 0.00 | 0.00 |
June | 877.75 | 1.09 | 876.67 | 2948.72 | 25.42 | 0.00 | 0.00 | 0.00 |
July | 877.73 | 7.46 | 870.27 | 3461.30 | 0.56 | 0.00 | 0.00 | 0.00 |
August | 1018.10 | 72.14 | 945.96 | 3876.22 | 0.09 | 0.00 | 0.00 | 0.00 |
September | 1342.37 | 307.64 | 1034.73 | 3831.10 | 52.50 | 0.00 | 0.00 | 0.00 |
October | 1757.43 | 698.68 | 1058.75 | 3978.26 | 250.83 | 0.00 | 0.00 | 0.00 |
November | 1938.80 | 934.65 | 1004.15 | 3692.89 | 636.07 | 0.00 | 0.00 | 0.00 |
December | 1799.79 | 889.04 | 910.75 | 2996.89 | 1051.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1377.71 | 412.56 | 965.15 | 3189.42 | 485.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 877.73 | 1.09 | 870.27 | 2427.19 | 0.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1938.80 | 934.65 | 1058.75 | 3978.26 | 1229.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 662.73 | 190.34 | 472.39 | 946.63 | 839.90 | 0.00 | 0.00 | 0.00 |
February | 756.77 | 215.80 | 540.97 | 1178.99 | 727.83 | 0.00 | 0.00 | 0.00 |
March | 896.42 | 265.39 | 631.03 | 1572.39 | 590.88 | 0.00 | 0.00 | 0.00 |
April | 979.63 | 275.22 | 704.41 | 1989.54 | 410.21 | 0.00 | 0.00 | 0.00 |
May | 1066.33 | 319.19 | 747.13 | 2652.49 | 117.28 | 0.00 | 0.00 | 0.00 |
June | 1101.96 | 347.37 | 754.59 | 2909.46 | 31.18 | 0.00 | 0.00 | 0.00 |
July | 1010.93 | 289.21 | 721.72 | 3072.84 | 1.56 | 0.00 | 0.00 | 0.00 |
August | 1037.10 | 315.32 | 721.78 | 3159.42 | 0.51 | 0.00 | 0.00 | 0.00 |
September | 986.55 | 309.95 | 676.60 | 2610.94 | 44.53 | 0.00 | 0.00 | 0.00 |
October | 876.75 | 283.22 | 593.54 | 2028.55 | 185.86 | 0.00 | 0.00 | 0.00 |
November | 753.46 | 246.41 | 507.05 | 1465.38 | 441.43 | 0.00 | 0.00 | 0.00 |
December | 630.76 | 190.67 | 440.10 | 991.07 | 722.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 897.12 | 270.86 | 626.26 | 2053.14 | 340.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 630.76 | 190.34 | 440.10 | 946.63 | 0.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1101.96 | 347.37 | 754.59 | 3159.42 | 839.90 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300179E+09 | 0.00 | 0.300179E+09 | 0.322450E+09 | 0.742040E+09 |
February | 0.310792E+09 | 0.00 | 0.310792E+09 | 0.410843E+09 | 0.564033E+09 |
March | 0.395235E+09 | 0.00 | 0.395235E+09 | 0.667695E+09 | 0.467526E+09 |
April | 0.430936E+09 | 887921.69 | 0.430048E+09 | 0.941653E+09 | 0.276453E+09 |
May | 0.501225E+09 | 14700635.90 | 0.486525E+09 | 0.149616E+10 | 66844122.99 |
June | 0.519345E+09 | 28832482.11 | 0.490513E+09 | 0.166440E+10 | 16646351.14 |
July | 0.492435E+09 | 14188242.10 | 0.478247E+09 | 0.190712E+10 | 683743.26 |
August | 0.458415E+09 | 3791545.17 | 0.454623E+09 | 0.185297E+10 | 175672.49 |
September | 0.404104E+09 | 46306.58 | 0.404057E+09 | 0.137994E+10 | 22486075.36 |
October | 0.370170E+09 | 0.00 | 0.370170E+09 | 0.101369E+10 | 0.113803E+09 |
November | 0.307532E+09 | 0.00 | 0.307532E+09 | 0.614118E+09 | 0.322383E+09 |
December | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.361230E+09 | 0.619190E+09 |
Annual Sum or Average | 0.477055E+10 | 62447133.55 | 0.470810E+10 | 0.126323E+11 | 0.321226E+10 |
Minimum of Months | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.322450E+09 | 175672.49 |
Maximum of Months | 0.519345E+09 | 28832482.11 | 0.490513E+09 | 0.190712E+10 | 0.742040E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300179E+09 | 0.00 | 0.300179E+09 | 0.322450E+09 | 0.742040E+09 |
February | 0.310792E+09 | 0.00 | 0.310792E+09 | 0.410843E+09 | 0.564033E+09 |
March | 0.395234E+09 | 0.00 | 0.395234E+09 | 0.667695E+09 | 0.467526E+09 |
April | 0.430936E+09 | 887920.63 | 0.430048E+09 | 0.941653E+09 | 0.276453E+09 |
May | 0.501225E+09 | 14700618.26 | 0.486524E+09 | 0.149616E+10 | 66844031.32 |
June | 0.519345E+09 | 28832447.51 | 0.490512E+09 | 0.166440E+10 | 16646302.24 |
July | 0.492435E+09 | 14188225.07 | 0.478246E+09 | 0.190712E+10 | 683738.55 |
August | 0.458414E+09 | 3791540.62 | 0.454623E+09 | 0.185297E+10 | 175670.77 |
September | 0.404103E+09 | 46306.53 | 0.404057E+09 | 0.137994E+10 | 22486031.32 |
October | 0.370170E+09 | 0.00 | 0.370170E+09 | 0.101369E+10 | 0.113803E+09 |
November | 0.307532E+09 | 0.00 | 0.307532E+09 | 0.614118E+09 | 0.322382E+09 |
December | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.361230E+09 | 0.619190E+09 |
Annual Sum or Average | 0.477054E+10 | 62447058.62 | 0.470809E+10 | 0.126323E+11 | 0.321226E+10 |
Minimum of Months | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.322450E+09 | 175670.77 |
Maximum of Months | 0.519345E+09 | 28832447.51 | 0.490512E+09 | 0.190712E+10 | 0.742040E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300179E+09 | 0.00 | 0.300179E+09 | 0.322450E+09 | 0.742040E+09 |
February | 0.310792E+09 | 0.00 | 0.310792E+09 | 0.410843E+09 | 0.564033E+09 |
March | 0.395235E+09 | 0.00 | 0.395235E+09 | 0.667695E+09 | 0.467526E+09 |
April | 0.430936E+09 | 887921.69 | 0.430048E+09 | 0.941653E+09 | 0.276453E+09 |
May | 0.501225E+09 | 14700635.90 | 0.486525E+09 | 0.149616E+10 | 66844122.99 |
June | 0.519345E+09 | 28832482.11 | 0.490513E+09 | 0.166440E+10 | 16646351.14 |
July | 0.492435E+09 | 14188242.10 | 0.478247E+09 | 0.190712E+10 | 683743.26 |
August | 0.458415E+09 | 3791545.17 | 0.454623E+09 | 0.185297E+10 | 175672.49 |
September | 0.404104E+09 | 46306.58 | 0.404057E+09 | 0.137994E+10 | 22486075.36 |
October | 0.370170E+09 | 0.00 | 0.370170E+09 | 0.101369E+10 | 0.113803E+09 |
November | 0.307532E+09 | 0.00 | 0.307532E+09 | 0.614118E+09 | 0.322383E+09 |
December | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.361230E+09 | 0.619190E+09 |
Annual Sum or Average | 0.477055E+10 | 62447133.55 | 0.470810E+10 | 0.126323E+11 | 0.321226E+10 |
Minimum of Months | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.322450E+09 | 175672.49 |
Maximum of Months | 0.519345E+09 | 28832482.11 | 0.490513E+09 | 0.190712E+10 | 0.742040E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300179E+09 | 0.00 | 0.300179E+09 | 0.322450E+09 | 0.742040E+09 |
February | 0.310792E+09 | 0.00 | 0.310792E+09 | 0.410843E+09 | 0.564033E+09 |
March | 0.395234E+09 | 0.00 | 0.395234E+09 | 0.667695E+09 | 0.467526E+09 |
April | 0.430936E+09 | 887920.63 | 0.430048E+09 | 0.941653E+09 | 0.276453E+09 |
May | 0.501225E+09 | 14700618.26 | 0.486524E+09 | 0.149616E+10 | 66844031.32 |
June | 0.519345E+09 | 28832447.51 | 0.490512E+09 | 0.166440E+10 | 16646302.24 |
July | 0.492435E+09 | 14188225.07 | 0.478246E+09 | 0.190712E+10 | 683738.55 |
August | 0.458414E+09 | 3791540.62 | 0.454623E+09 | 0.185297E+10 | 175670.77 |
September | 0.404103E+09 | 46306.53 | 0.404057E+09 | 0.137994E+10 | 22486031.32 |
October | 0.370170E+09 | 0.00 | 0.370170E+09 | 0.101369E+10 | 0.113803E+09 |
November | 0.307532E+09 | 0.00 | 0.307532E+09 | 0.614118E+09 | 0.322382E+09 |
December | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.361230E+09 | 0.619190E+09 |
Annual Sum or Average | 0.477054E+10 | 62447058.62 | 0.470809E+10 | 0.126323E+11 | 0.321226E+10 |
Minimum of Months | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.322450E+09 | 175670.77 |
Maximum of Months | 0.519345E+09 | 28832447.51 | 0.490512E+09 | 0.190712E+10 | 0.742040E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300167E+09 | 0.00 | 0.300167E+09 | 0.322437E+09 | 0.742010E+09 |
February | 0.310779E+09 | 0.00 | 0.310779E+09 | 0.410827E+09 | 0.564010E+09 |
March | 0.395219E+09 | 0.00 | 0.395219E+09 | 0.667668E+09 | 0.467507E+09 |
April | 0.430919E+09 | 887885.91 | 0.430031E+09 | 0.941615E+09 | 0.276442E+09 |
May | 0.501205E+09 | 14700043.40 | 0.486505E+09 | 0.149610E+10 | 66841428.88 |
June | 0.519324E+09 | 28831320.03 | 0.490493E+09 | 0.166434E+10 | 16645680.22 |
July | 0.492415E+09 | 14187670.25 | 0.478227E+09 | 0.190705E+10 | 683715.70 |
August | 0.458396E+09 | 3791392.35 | 0.454605E+09 | 0.185289E+10 | 175665.41 |
September | 0.404087E+09 | 46304.72 | 0.404041E+09 | 0.137989E+10 | 22485169.07 |
October | 0.370155E+09 | 0.00 | 0.370155E+09 | 0.101365E+10 | 0.113799E+09 |
November | 0.307520E+09 | 0.00 | 0.307520E+09 | 0.614093E+09 | 0.322370E+09 |
December | 0.280167E+09 | 0.00 | 0.280167E+09 | 0.361216E+09 | 0.619165E+09 |
Annual Sum or Average | 0.477035E+10 | 62444616.66 | 0.470791E+10 | 0.126318E+11 | 0.321214E+10 |
Minimum of Months | 0.280167E+09 | 0.00 | 0.280167E+09 | 0.322437E+09 | 175665.41 |
Maximum of Months | 0.519324E+09 | 28831320.03 | 0.490493E+09 | 0.190705E+10 | 0.742010E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.603349E+09 | 0.182543E+09 | 0.420806E+09 | 0.804665E+09 | 0.764036E+09 |
February | 0.593881E+09 | 0.160945E+09 | 0.432936E+09 | 0.891110E+09 | 0.580132E+09 |
March | 0.726289E+09 | 0.179004E+09 | 0.547285E+09 | 0.127183E+10 | 0.479337E+09 |
April | 0.855761E+09 | 0.249341E+09 | 0.606421E+09 | 0.176796E+10 | 0.280474E+09 |
May | 0.988214E+09 | 0.314850E+09 | 0.673364E+09 | 0.247321E+10 | 71387040.17 |
June | 0.936584E+09 | 0.286418E+09 | 0.650166E+09 | 0.252384E+10 | 15068513.08 |
July | 0.903295E+09 | 0.260418E+09 | 0.642877E+09 | 0.280857E+10 | 479931.68 |
August | 0.924959E+09 | 0.283882E+09 | 0.641076E+09 | 0.288967E+10 | 13049.98 |
September | 0.841518E+09 | 0.260103E+09 | 0.581415E+09 | 0.228281E+10 | 22584038.80 |
October | 0.789047E+09 | 0.257782E+09 | 0.531265E+09 | 0.184435E+10 | 0.113554E+09 |
November | 0.639894E+09 | 0.202686E+09 | 0.437208E+09 | 0.123441E+10 | 0.325873E+09 |
December | 0.535197E+09 | 0.146836E+09 | 0.388361E+09 | 0.793942E+09 | 0.619279E+09 |
Annual Sum or Average | 0.933799E+10 | 0.278481E+10 | 0.655318E+10 | 0.215864E+11 | 0.327222E+10 |
Minimum of Months | 0.535197E+09 | 0.146836E+09 | 0.388361E+09 | 0.793942E+09 | 13049.98 |
Maximum of Months | 0.988214E+09 | 0.314850E+09 | 0.673364E+09 | 0.288967E+10 | 0.764036E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.603349E+09 | 0.182543E+09 | 0.420806E+09 | 0.804665E+09 | 0.764036E+09 |
February | 0.593881E+09 | 0.160945E+09 | 0.432936E+09 | 0.891110E+09 | 0.580132E+09 |
March | 0.726289E+09 | 0.179004E+09 | 0.547285E+09 | 0.127183E+10 | 0.479337E+09 |
April | 0.855761E+09 | 0.249341E+09 | 0.606421E+09 | 0.176796E+10 | 0.280474E+09 |
May | 0.988214E+09 | 0.314850E+09 | 0.673364E+09 | 0.247321E+10 | 71387040.17 |
June | 0.936584E+09 | 0.286418E+09 | 0.650166E+09 | 0.252384E+10 | 15068513.08 |
July | 0.903295E+09 | 0.260418E+09 | 0.642877E+09 | 0.280857E+10 | 479931.68 |
August | 0.924959E+09 | 0.283882E+09 | 0.641076E+09 | 0.288967E+10 | 13049.98 |
September | 0.841518E+09 | 0.260103E+09 | 0.581415E+09 | 0.228281E+10 | 22584038.80 |
October | 0.789047E+09 | 0.257782E+09 | 0.531265E+09 | 0.184435E+10 | 0.113554E+09 |
November | 0.639894E+09 | 0.202686E+09 | 0.437208E+09 | 0.123441E+10 | 0.325873E+09 |
December | 0.535197E+09 | 0.146836E+09 | 0.388361E+09 | 0.793942E+09 | 0.619279E+09 |
Annual Sum or Average | 0.933799E+10 | 0.278481E+10 | 0.655318E+10 | 0.215864E+11 | 0.327222E+10 |
Minimum of Months | 0.535197E+09 | 0.146836E+09 | 0.388361E+09 | 0.793942E+09 | 13049.98 |
Maximum of Months | 0.988214E+09 | 0.314850E+09 | 0.673364E+09 | 0.288967E+10 | 0.764036E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.603338E+09 | 0.182539E+09 | 0.420799E+09 | 0.804650E+09 | 0.764022E+09 |
February | 0.593870E+09 | 0.160942E+09 | 0.432929E+09 | 0.891094E+09 | 0.580121E+09 |
March | 0.726276E+09 | 0.179000E+09 | 0.547275E+09 | 0.127181E+10 | 0.479328E+09 |
April | 0.855746E+09 | 0.249336E+09 | 0.606409E+09 | 0.176793E+10 | 0.280469E+09 |
May | 0.988196E+09 | 0.314844E+09 | 0.673351E+09 | 0.247317E+10 | 71385735.77 |
June | 0.936567E+09 | 0.286413E+09 | 0.650155E+09 | 0.252380E+10 | 15068237.74 |
July | 0.903278E+09 | 0.260414E+09 | 0.642865E+09 | 0.280852E+10 | 479922.91 |
August | 0.924942E+09 | 0.283877E+09 | 0.641065E+09 | 0.288962E+10 | 13049.75 |
September | 0.841503E+09 | 0.260099E+09 | 0.581404E+09 | 0.228277E+10 | 22583626.14 |
October | 0.789033E+09 | 0.257777E+09 | 0.531255E+09 | 0.184431E+10 | 0.113552E+09 |
November | 0.639882E+09 | 0.202682E+09 | 0.437200E+09 | 0.123439E+10 | 0.325867E+09 |
December | 0.535187E+09 | 0.146834E+09 | 0.388353E+09 | 0.793927E+09 | 0.619268E+09 |
Annual Sum or Average | 0.933782E+10 | 0.278476E+10 | 0.655306E+10 | 0.215860E+11 | 0.327216E+10 |
Minimum of Months | 0.535187E+09 | 0.146834E+09 | 0.388353E+09 | 0.793927E+09 | 13049.75 |
Maximum of Months | 0.988196E+09 | 0.314844E+09 | 0.673351E+09 | 0.288962E+10 | 0.764022E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970147E+09 | 0.456110E+09 | 0.514037E+09 | 0.152027E+10 | 0.715269E+09 |
February | 0.822847E+09 | 0.336580E+09 | 0.486266E+09 | 0.137448E+10 | 0.559464E+09 |
March | 0.749801E+09 | 0.203567E+09 | 0.546234E+09 | 0.140344E+10 | 0.480163E+09 |
April | 0.570387E+09 | 60471832.51 | 0.509915E+09 | 0.126402E+10 | 0.288062E+09 |
May | 0.499273E+09 | 7645866.55 | 0.491627E+09 | 0.149139E+10 | 68822846.04 |
June | 0.455032E+09 | 563119.71 | 0.454469E+09 | 0.152488E+10 | 13153878.31 |
July | 0.470187E+09 | 3995158.92 | 0.466192E+09 | 0.185088E+10 | 390683.16 |
August | 0.545380E+09 | 38642379.00 | 0.506738E+09 | 0.205239E+10 | 134270.66 |
September | 0.695894E+09 | 0.159484E+09 | 0.536409E+09 | 0.200209E+10 | 25156088.83 |
October | 0.941430E+09 | 0.374271E+09 | 0.567158E+09 | 0.215063E+10 | 0.126182E+09 |
November | 0.100509E+10 | 0.484526E+09 | 0.520559E+09 | 0.193308E+10 | 0.334750E+09 |
December | 0.964125E+09 | 0.476248E+09 | 0.487876E+09 | 0.160820E+10 | 0.608023E+09 |
Annual Sum or Average | 0.868959E+10 | 0.260211E+10 | 0.608748E+10 | 0.201757E+11 | 0.321957E+10 |
Minimum of Months | 0.455032E+09 | 563119.71 | 0.454469E+09 | 0.126402E+10 | 134270.66 |
Maximum of Months | 0.100509E+10 | 0.484526E+09 | 0.567158E+09 | 0.215063E+10 | 0.715269E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970145E+09 | 0.456109E+09 | 0.514036E+09 | 0.152026E+10 | 0.715268E+09 |
February | 0.822846E+09 | 0.336580E+09 | 0.486266E+09 | 0.137448E+10 | 0.559464E+09 |
March | 0.749801E+09 | 0.203567E+09 | 0.546234E+09 | 0.140344E+10 | 0.480163E+09 |
April | 0.570387E+09 | 60471759.95 | 0.509915E+09 | 0.126402E+10 | 0.288061E+09 |
May | 0.499272E+09 | 7645857.37 | 0.491627E+09 | 0.149139E+10 | 68822755.24 |
June | 0.455032E+09 | 563119.04 | 0.454469E+09 | 0.152488E+10 | 13153839.28 |
July | 0.470187E+09 | 3995154.13 | 0.466192E+09 | 0.185088E+10 | 390680.06 |
August | 0.545380E+09 | 38642332.63 | 0.506737E+09 | 0.205239E+10 | 134269.19 |
September | 0.695893E+09 | 0.159484E+09 | 0.536409E+09 | 0.200209E+10 | 25156040.79 |
October | 0.941429E+09 | 0.374271E+09 | 0.567158E+09 | 0.215063E+10 | 0.126182E+09 |
November | 0.100508E+10 | 0.484525E+09 | 0.520559E+09 | 0.193307E+10 | 0.334750E+09 |
December | 0.964123E+09 | 0.476248E+09 | 0.487876E+09 | 0.160820E+10 | 0.608023E+09 |
Annual Sum or Average | 0.868958E+10 | 0.260210E+10 | 0.608748E+10 | 0.201757E+11 | 0.321957E+10 |
Minimum of Months | 0.455032E+09 | 563119.04 | 0.454469E+09 | 0.126402E+10 | 134269.19 |
Maximum of Months | 0.100508E+10 | 0.484525E+09 | 0.567158E+09 | 0.215063E+10 | 0.715268E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970147E+09 | 0.456110E+09 | 0.514037E+09 | 0.152027E+10 | 0.715269E+09 |
February | 0.822847E+09 | 0.336580E+09 | 0.486266E+09 | 0.137448E+10 | 0.559464E+09 |
March | 0.749801E+09 | 0.203567E+09 | 0.546234E+09 | 0.140344E+10 | 0.480163E+09 |
April | 0.570387E+09 | 60471832.51 | 0.509915E+09 | 0.126402E+10 | 0.288062E+09 |
May | 0.499273E+09 | 7645866.55 | 0.491627E+09 | 0.149139E+10 | 68822846.04 |
June | 0.455032E+09 | 563119.71 | 0.454469E+09 | 0.152488E+10 | 13153878.31 |
July | 0.470187E+09 | 3995158.92 | 0.466192E+09 | 0.185088E+10 | 390683.16 |
August | 0.545380E+09 | 38642379.00 | 0.506738E+09 | 0.205239E+10 | 134270.66 |
September | 0.695894E+09 | 0.159484E+09 | 0.536409E+09 | 0.200209E+10 | 25156088.83 |
October | 0.941430E+09 | 0.374271E+09 | 0.567158E+09 | 0.215063E+10 | 0.126182E+09 |
November | 0.100509E+10 | 0.484526E+09 | 0.520559E+09 | 0.193308E+10 | 0.334750E+09 |
December | 0.964125E+09 | 0.476248E+09 | 0.487876E+09 | 0.160820E+10 | 0.608023E+09 |
Annual Sum or Average | 0.868959E+10 | 0.260211E+10 | 0.608748E+10 | 0.201757E+11 | 0.321957E+10 |
Minimum of Months | 0.455032E+09 | 563119.71 | 0.454469E+09 | 0.126402E+10 | 134270.66 |
Maximum of Months | 0.100509E+10 | 0.484526E+09 | 0.567158E+09 | 0.215063E+10 | 0.715269E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970145E+09 | 0.456109E+09 | 0.514036E+09 | 0.152026E+10 | 0.715268E+09 |
February | 0.822846E+09 | 0.336580E+09 | 0.486266E+09 | 0.137448E+10 | 0.559464E+09 |
March | 0.749801E+09 | 0.203567E+09 | 0.546234E+09 | 0.140344E+10 | 0.480163E+09 |
April | 0.570387E+09 | 60471759.95 | 0.509915E+09 | 0.126402E+10 | 0.288061E+09 |
May | 0.499272E+09 | 7645857.37 | 0.491627E+09 | 0.149139E+10 | 68822755.24 |
June | 0.455032E+09 | 563119.04 | 0.454469E+09 | 0.152488E+10 | 13153839.28 |
July | 0.470187E+09 | 3995154.13 | 0.466192E+09 | 0.185088E+10 | 390680.06 |
August | 0.545380E+09 | 38642332.63 | 0.506737E+09 | 0.205239E+10 | 134269.19 |
September | 0.695893E+09 | 0.159484E+09 | 0.536409E+09 | 0.200209E+10 | 25156040.79 |
October | 0.941429E+09 | 0.374271E+09 | 0.567158E+09 | 0.215063E+10 | 0.126182E+09 |
November | 0.100508E+10 | 0.484525E+09 | 0.520559E+09 | 0.193307E+10 | 0.334750E+09 |
December | 0.964123E+09 | 0.476248E+09 | 0.487876E+09 | 0.160820E+10 | 0.608023E+09 |
Annual Sum or Average | 0.868958E+10 | 0.260210E+10 | 0.608748E+10 | 0.201757E+11 | 0.321957E+10 |
Minimum of Months | 0.455032E+09 | 563119.04 | 0.454469E+09 | 0.126402E+10 | 134269.19 |
Maximum of Months | 0.100508E+10 | 0.484525E+09 | 0.567158E+09 | 0.215063E+10 | 0.715268E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970107E+09 | 0.456091E+09 | 0.514016E+09 | 0.152020E+10 | 0.715240E+09 |
February | 0.822813E+09 | 0.336567E+09 | 0.486247E+09 | 0.137442E+10 | 0.559442E+09 |
March | 0.749771E+09 | 0.203559E+09 | 0.546212E+09 | 0.140339E+10 | 0.480144E+09 |
April | 0.570364E+09 | 60469395.23 | 0.509895E+09 | 0.126397E+10 | 0.288050E+09 |
May | 0.499253E+09 | 7645558.38 | 0.491607E+09 | 0.149133E+10 | 68820072.17 |
June | 0.455014E+09 | 563097.02 | 0.454451E+09 | 0.152481E+10 | 13153348.16 |
July | 0.470168E+09 | 3994997.90 | 0.466173E+09 | 0.185080E+10 | 390667.41 |
August | 0.545358E+09 | 38640821.54 | 0.506717E+09 | 0.205230E+10 | 134265.25 |
September | 0.695866E+09 | 0.159478E+09 | 0.536388E+09 | 0.200201E+10 | 25155074.93 |
October | 0.941392E+09 | 0.374256E+09 | 0.567135E+09 | 0.215055E+10 | 0.126177E+09 |
November | 0.100504E+10 | 0.484506E+09 | 0.520538E+09 | 0.193300E+10 | 0.334737E+09 |
December | 0.964086E+09 | 0.476229E+09 | 0.487857E+09 | 0.160813E+10 | 0.607999E+09 |
Annual Sum or Average | 0.868924E+10 | 0.260200E+10 | 0.608724E+10 | 0.201749E+11 | 0.321944E+10 |
Minimum of Months | 0.455014E+09 | 563097.02 | 0.454451E+09 | 0.126397E+10 | 134265.25 |
Maximum of Months | 0.100504E+10 | 0.484506E+09 | 0.567135E+09 | 0.215055E+10 | 0.715240E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.591693E+09 | 0.169939E+09 | 0.421754E+09 | 0.806345E+09 | 0.904385E+09 |
February | 0.610267E+09 | 0.174024E+09 | 0.436243E+09 | 0.918384E+09 | 0.721343E+09 |
March | 0.800331E+09 | 0.236940E+09 | 0.563391E+09 | 0.137499E+10 | 0.641848E+09 |
April | 0.846411E+09 | 0.237796E+09 | 0.608615E+09 | 0.168303E+10 | 0.435267E+09 |
May | 0.952025E+09 | 0.284979E+09 | 0.667045E+09 | 0.236336E+10 | 0.114551E+09 |
June | 0.952101E+09 | 0.300128E+09 | 0.651974E+09 | 0.247884E+10 | 40347844.76 |
July | 0.902565E+09 | 0.258206E+09 | 0.644359E+09 | 0.267571E+10 | 3837473.85 |
August | 0.925932E+09 | 0.281523E+09 | 0.644409E+09 | 0.267837E+10 | 4097079.92 |
September | 0.852387E+09 | 0.267796E+09 | 0.584591E+09 | 0.223775E+10 | 46050119.86 |
October | 0.782772E+09 | 0.252857E+09 | 0.529915E+09 | 0.178392E+10 | 0.196929E+09 |
November | 0.650996E+09 | 0.212897E+09 | 0.438100E+09 | 0.123149E+10 | 0.472566E+09 |
December | 0.563152E+09 | 0.170231E+09 | 0.392921E+09 | 0.827265E+09 | 0.845898E+09 |
Annual Sum or Average | 0.943063E+10 | 0.284732E+10 | 0.658332E+10 | 0.210595E+11 | 0.442712E+10 |
Minimum of Months | 0.563152E+09 | 0.169939E+09 | 0.392921E+09 | 0.806345E+09 | 3837473.85 |
Maximum of Months | 0.952101E+09 | 0.300128E+09 | 0.667045E+09 | 0.267837E+10 | 0.904385E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.591693E+09 | 0.169939E+09 | 0.421754E+09 | 0.806345E+09 | 0.904385E+09 |
February | 0.610267E+09 | 0.174024E+09 | 0.436243E+09 | 0.918384E+09 | 0.721343E+09 |
March | 0.800331E+09 | 0.236940E+09 | 0.563391E+09 | 0.137499E+10 | 0.641848E+09 |
April | 0.846411E+09 | 0.237796E+09 | 0.608615E+09 | 0.168303E+10 | 0.435267E+09 |
May | 0.952025E+09 | 0.284979E+09 | 0.667045E+09 | 0.236336E+10 | 0.114551E+09 |
June | 0.952101E+09 | 0.300128E+09 | 0.651974E+09 | 0.247884E+10 | 40347844.76 |
July | 0.902565E+09 | 0.258206E+09 | 0.644359E+09 | 0.267571E+10 | 3837473.85 |
August | 0.925932E+09 | 0.281523E+09 | 0.644409E+09 | 0.267837E+10 | 4097079.92 |
September | 0.852387E+09 | 0.267796E+09 | 0.584591E+09 | 0.223775E+10 | 46050119.86 |
October | 0.782772E+09 | 0.252857E+09 | 0.529915E+09 | 0.178392E+10 | 0.196929E+09 |
November | 0.650996E+09 | 0.212897E+09 | 0.438100E+09 | 0.123149E+10 | 0.472566E+09 |
December | 0.563152E+09 | 0.170231E+09 | 0.392921E+09 | 0.827265E+09 | 0.845898E+09 |
Annual Sum or Average | 0.943063E+10 | 0.284732E+10 | 0.658332E+10 | 0.210595E+11 | 0.442712E+10 |
Minimum of Months | 0.563152E+09 | 0.169939E+09 | 0.392921E+09 | 0.806345E+09 | 3837473.85 |
Maximum of Months | 0.952101E+09 | 0.300128E+09 | 0.667045E+09 | 0.267837E+10 | 0.904385E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.591682E+09 | 0.169936E+09 | 0.421746E+09 | 0.806330E+09 | 0.904369E+09 |
February | 0.610256E+09 | 0.174020E+09 | 0.436235E+09 | 0.918367E+09 | 0.721330E+09 |
March | 0.800316E+09 | 0.236936E+09 | 0.563381E+09 | 0.137496E+10 | 0.641837E+09 |
April | 0.846395E+09 | 0.237792E+09 | 0.608604E+09 | 0.168300E+10 | 0.435259E+09 |
May | 0.952007E+09 | 0.284974E+09 | 0.667033E+09 | 0.236332E+10 | 0.114548E+09 |
June | 0.952084E+09 | 0.300122E+09 | 0.651962E+09 | 0.247879E+10 | 40347107.52 |
July | 0.902549E+09 | 0.258201E+09 | 0.644348E+09 | 0.267566E+10 | 3837403.73 |
August | 0.925915E+09 | 0.281518E+09 | 0.644397E+09 | 0.267832E+10 | 4097005.05 |
September | 0.852371E+09 | 0.267791E+09 | 0.584581E+09 | 0.223771E+10 | 46049278.42 |
October | 0.782758E+09 | 0.252852E+09 | 0.529905E+09 | 0.178389E+10 | 0.196925E+09 |
November | 0.650984E+09 | 0.212893E+09 | 0.438092E+09 | 0.123147E+10 | 0.472557E+09 |
December | 0.563141E+09 | 0.170228E+09 | 0.392914E+09 | 0.827250E+09 | 0.845883E+09 |
Annual Sum or Average | 0.943046E+10 | 0.284726E+10 | 0.658320E+10 | 0.210591E+11 | 0.442704E+10 |
Minimum of Months | 0.563141E+09 | 0.169936E+09 | 0.392914E+09 | 0.806330E+09 | 3837403.73 |
Maximum of Months | 0.952084E+09 | 0.300122E+09 | 0.667033E+09 | 0.267832E+10 | 0.904369E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.175091E+10 | 0.328619E+10 |
February | 0.155394E+10 | 0.00 | 0.155394E+10 | 0.215563E+10 | 0.251954E+10 |
March | 0.197615E+10 | 0.00 | 0.197615E+10 | 0.341555E+10 | 0.216964E+10 |
April | 0.215465E+10 | 4439554.79 | 0.215021E+10 | 0.478819E+10 | 0.134505E+10 |
May | 0.250610E+10 | 73502290.71 | 0.243259E+10 | 0.753462E+10 | 0.344326E+09 |
June | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.842330E+10 | 79571884.77 |
July | 0.246214E+10 | 70940352.69 | 0.239120E+10 | 0.970897E+10 | 2051556.75 |
August | 0.229205E+10 | 18957496.60 | 0.227309E+10 | 0.956715E+10 | 136758.93 |
September | 0.202049E+10 | 231530.12 | 0.202026E+10 | 0.699912E+10 | 0.112191E+09 |
October | 0.185083E+10 | 0.00 | 0.185083E+10 | 0.516977E+10 | 0.570992E+09 |
November | 0.153764E+10 | 0.00 | 0.153764E+10 | 0.316652E+10 | 0.152312E+10 |
December | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.194285E+10 | 0.272810E+10 |
Annual Sum or Average | 0.238524E+11 | 0.312232E+09 | 0.235402E+11 | 0.646226E+11 | 0.146809E+11 |
Minimum of Months | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.175091E+10 | 136758.93 |
Maximum of Months | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.970897E+10 | 0.328619E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181003E+10 | 0.547622E+09 | 0.126241E+10 | 0.244050E+10 | 0.213552E+10 |
February | 0.178163E+10 | 0.482829E+09 | 0.129880E+10 | 0.266974E+10 | 0.165193E+10 |
March | 0.217884E+10 | 0.537005E+09 | 0.164184E+10 | 0.377767E+10 | 0.143210E+10 |
April | 0.256726E+10 | 0.748014E+09 | 0.181924E+10 | 0.523973E+10 | 0.911899E+09 |
May | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.735431E+10 | 0.237523E+09 |
June | 0.280972E+10 | 0.859245E+09 | 0.195048E+10 | 0.752304E+10 | 52819681.86 |
July | 0.270986E+10 | 0.781247E+09 | 0.192861E+10 | 0.839405E+10 | 1285483.01 |
August | 0.277485E+10 | 0.851639E+09 | 0.192321E+10 | 0.866451E+10 | 81335.86 |
September | 0.252453E+10 | 0.780302E+09 | 0.174423E+10 | 0.680222E+10 | 75186139.38 |
October | 0.236712E+10 | 0.773339E+09 | 0.159378E+10 | 0.548707E+10 | 0.382140E+09 |
November | 0.191966E+10 | 0.608051E+09 | 0.131161E+10 | 0.366470E+10 | 0.100713E+10 |
December | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.238606E+10 | 0.178172E+10 |
Annual Sum or Average | 0.280137E+11 | 0.835434E+10 | 0.196593E+11 | 0.644036E+11 | 0.966933E+10 |
Minimum of Months | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.238606E+10 | 81335.86 |
Maximum of Months | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.866451E+10 | 0.213552E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.485067E+10 | 0.228052E+10 | 0.257015E+10 | 0.755480E+10 | 0.346371E+10 |
February | 0.411418E+10 | 0.168288E+10 | 0.243130E+10 | 0.683497E+10 | 0.268780E+10 |
March | 0.374896E+10 | 0.101782E+10 | 0.273114E+10 | 0.699709E+10 | 0.233544E+10 |
April | 0.285190E+10 | 0.302356E+09 | 0.254955E+10 | 0.634663E+10 | 0.143074E+10 |
May | 0.249633E+10 | 38228870.47 | 0.245811E+10 | 0.750752E+10 | 0.349920E+09 |
June | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.774733E+10 | 59297791.82 |
July | 0.235091E+10 | 19975553.05 | 0.233093E+10 | 0.941587E+10 | 821349.26 |
August | 0.272687E+10 | 0.193210E+09 | 0.253366E+10 | 0.105097E+11 | 106273.23 |
September | 0.347943E+10 | 0.797412E+09 | 0.268201E+10 | 0.100303E+11 | 0.129919E+09 |
October | 0.470709E+10 | 0.187133E+10 | 0.283576E+10 | 0.107262E+11 | 0.661468E+09 |
November | 0.502537E+10 | 0.242260E+10 | 0.260277E+10 | 0.960925E+10 | 0.168160E+10 |
December | 0.482056E+10 | 0.238121E+10 | 0.243935E+10 | 0.801699E+10 | 0.292793E+10 |
Annual Sum or Average | 0.434474E+11 | 0.130104E+11 | 0.304370E+11 | 0.101297E+12 | 0.157288E+11 |
Minimum of Months | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.634663E+10 | 106273.23 |
Maximum of Months | 0.502537E+10 | 0.242260E+10 | 0.283576E+10 | 0.107262E+11 | 0.346371E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.177506E+10 | 0.509812E+09 | 0.126525E+10 | 0.251636E+10 | 0.236691E+10 |
February | 0.183078E+10 | 0.522065E+09 | 0.130872E+10 | 0.285336E+10 | 0.182817E+10 |
March | 0.240097E+10 | 0.710813E+09 | 0.169016E+10 | 0.423719E+10 | 0.161802E+10 |
April | 0.253921E+10 | 0.713381E+09 | 0.182583E+10 | 0.519924E+10 | 0.106488E+10 |
May | 0.285604E+10 | 0.854929E+09 | 0.200112E+10 | 0.716763E+10 | 0.304841E+09 |
June | 0.285628E+10 | 0.900374E+09 | 0.195590E+10 | 0.760642E+10 | 75896897.06 |
July | 0.270767E+10 | 0.774611E+09 | 0.193306E+10 | 0.831750E+10 | 3122994.84 |
August | 0.277777E+10 | 0.844560E+09 | 0.193321E+10 | 0.854293E+10 | 1069178.14 |
September | 0.255713E+10 | 0.803378E+09 | 0.175376E+10 | 0.682838E+10 | 0.110431E+09 |
October | 0.234829E+10 | 0.758564E+09 | 0.158973E+10 | 0.547446E+10 | 0.491170E+09 |
November | 0.195297E+10 | 0.638684E+09 | 0.131429E+10 | 0.381887E+10 | 0.116736E+10 |
December | 0.168944E+10 | 0.510687E+09 | 0.117875E+10 | 0.265056E+10 | 0.201311E+10 |
Annual Sum or Average | 0.282916E+11 | 0.854186E+10 | 0.197498E+11 | 0.652129E+11 | 0.110450E+11 |
Minimum of Months | 0.168944E+10 | 0.509812E+09 | 0.117875E+10 | 0.251636E+10 | 1069178.14 |
Maximum of Months | 0.285628E+10 | 0.900374E+09 | 0.200112E+10 | 0.854293E+10 | 0.236691E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.181716E+10 | 0.307719E+10 |
February | 0.155394E+10 | 0.00 | 0.155394E+10 | 0.218219E+10 | 0.240132E+10 |
March | 0.197615E+10 | 0.00 | 0.197615E+10 | 0.340047E+10 | 0.211313E+10 |
April | 0.215465E+10 | 4439554.79 | 0.215021E+10 | 0.473624E+10 | 0.135204E+10 |
May | 0.250610E+10 | 73502290.71 | 0.243259E+10 | 0.743958E+10 | 0.362480E+09 |
June | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.832083E+10 | 88772557.41 |
July | 0.246214E+10 | 70940352.69 | 0.239120E+10 | 0.956653E+10 | 3254980.47 |
August | 0.229205E+10 | 18957496.60 | 0.227309E+10 | 0.944007E+10 | 304355.24 |
September | 0.202049E+10 | 231530.12 | 0.202026E+10 | 0.690202E+10 | 0.118816E+09 |
October | 0.185083E+10 | 0.00 | 0.185083E+10 | 0.511115E+10 | 0.586443E+09 |
November | 0.153764E+10 | 0.00 | 0.153764E+10 | 0.314946E+10 | 0.148953E+10 |
December | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.198018E+10 | 0.258774E+10 |
Annual Sum or Average | 0.238524E+11 | 0.312232E+09 | 0.235402E+11 | 0.640459E+11 | 0.141810E+11 |
Minimum of Months | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.181716E+10 | 304355.24 |
Maximum of Months | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.956653E+10 | 0.307719E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181003E+10 | 0.547622E+09 | 0.126241E+10 | 0.250469E+10 | 0.201922E+10 |
February | 0.178163E+10 | 0.482829E+09 | 0.129880E+10 | 0.270287E+10 | 0.158451E+10 |
March | 0.217884E+10 | 0.537005E+09 | 0.164184E+10 | 0.378628E+10 | 0.139805E+10 |
April | 0.256726E+10 | 0.748014E+09 | 0.181924E+10 | 0.522403E+10 | 0.913052E+09 |
May | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.731091E+10 | 0.246962E+09 |
June | 0.280972E+10 | 0.859245E+09 | 0.195048E+10 | 0.747568E+10 | 57685508.29 |
July | 0.270986E+10 | 0.781247E+09 | 0.192861E+10 | 0.832137E+10 | 1907077.04 |
August | 0.277485E+10 | 0.851639E+09 | 0.192321E+10 | 0.860396E+10 | 160553.26 |
September | 0.252453E+10 | 0.780302E+09 | 0.174423E+10 | 0.675800E+10 | 78279485.32 |
October | 0.236712E+10 | 0.773339E+09 | 0.159378E+10 | 0.546600E+10 | 0.388021E+09 |
November | 0.191966E+10 | 0.608051E+09 | 0.131161E+10 | 0.367018E+10 | 0.985331E+09 |
December | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.242825E+10 | 0.170175E+10 |
Annual Sum or Average | 0.280137E+11 | 0.835434E+10 | 0.196593E+11 | 0.642522E+11 | 0.937492E+10 |
Minimum of Months | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.242825E+10 | 160553.26 |
Maximum of Months | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.860396E+10 | 0.201922E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.485067E+10 | 0.228052E+10 | 0.257015E+10 | 0.759514E+10 | 0.329353E+10 |
February | 0.411418E+10 | 0.168288E+10 | 0.243130E+10 | 0.683664E+10 | 0.258564E+10 |
March | 0.374896E+10 | 0.101782E+10 | 0.273114E+10 | 0.696641E+10 | 0.228067E+10 |
April | 0.285190E+10 | 0.302356E+09 | 0.254955E+10 | 0.629128E+10 | 0.143333E+10 |
May | 0.249633E+10 | 38228870.47 | 0.245811E+10 | 0.741183E+10 | 0.366242E+09 |
June | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.764309E+10 | 65885610.36 |
July | 0.235091E+10 | 19975553.05 | 0.233093E+10 | 0.927074E+10 | 1504190.32 |
August | 0.272687E+10 | 0.193210E+09 | 0.253366E+10 | 0.103821E+11 | 238120.32 |
September | 0.347943E+10 | 0.797412E+09 | 0.268201E+10 | 0.993022E+10 | 0.136081E+09 |
October | 0.470709E+10 | 0.187133E+10 | 0.283576E+10 | 0.106554E+11 | 0.671836E+09 |
November | 0.502537E+10 | 0.242260E+10 | 0.260277E+10 | 0.957198E+10 | 0.164871E+10 |
December | 0.482056E+10 | 0.238121E+10 | 0.243935E+10 | 0.802687E+10 | 0.281709E+10 |
Annual Sum or Average | 0.434474E+11 | 0.130104E+11 | 0.304370E+11 | 0.100582E+12 | 0.153008E+11 |
Minimum of Months | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.629128E+10 | 238120.32 |
Maximum of Months | 0.502537E+10 | 0.242260E+10 | 0.283576E+10 | 0.106554E+11 | 0.329353E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.177506E+10 | 0.509812E+09 | 0.126525E+10 | 0.253547E+10 | 0.224959E+10 |
February | 0.183078E+10 | 0.522065E+09 | 0.130872E+10 | 0.285222E+10 | 0.176078E+10 |
March | 0.240097E+10 | 0.710813E+09 | 0.169016E+10 | 0.421149E+10 | 0.158260E+10 |
April | 0.253921E+10 | 0.713381E+09 | 0.182583E+10 | 0.515689E+10 | 0.106327E+10 |
May | 0.285604E+10 | 0.854929E+09 | 0.200112E+10 | 0.710443E+10 | 0.314127E+09 |
June | 0.285628E+10 | 0.900374E+09 | 0.195590E+10 | 0.754132E+10 | 80814388.19 |
July | 0.270767E+10 | 0.774611E+09 | 0.193306E+10 | 0.823030E+10 | 4185017.53 |
August | 0.277777E+10 | 0.844560E+09 | 0.193321E+10 | 0.846219E+10 | 1356284.19 |
September | 0.255713E+10 | 0.803378E+09 | 0.175376E+10 | 0.676755E+10 | 0.115415E+09 |
October | 0.234829E+10 | 0.758564E+09 | 0.158973E+10 | 0.543326E+10 | 0.497817E+09 |
November | 0.195297E+10 | 0.638684E+09 | 0.131429E+10 | 0.379826E+10 | 0.114417E+10 |
December | 0.168944E+10 | 0.510687E+09 | 0.117875E+10 | 0.265447E+10 | 0.193511E+10 |
Annual Sum or Average | 0.282916E+11 | 0.854186E+10 | 0.197498E+11 | 0.647479E+11 | 0.107492E+11 |
Minimum of Months | 0.168944E+10 | 0.509812E+09 | 0.117875E+10 | 0.253547E+10 | 1356284.19 |
Maximum of Months | 0.285628E+10 | 0.900374E+09 | 0.200112E+10 | 0.846219E+10 | 0.224959E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 601.94 | 1385.22 | 560.37 | 0.00 | 560.37 | 0.00 | 0.00 |
February | 849.12 | 1165.73 | 642.34 | 0.00 | 642.34 | 0.00 | 0.00 |
March | 1246.43 | 872.76 | 737.81 | 0.00 | 737.81 | 0.00 | 0.00 |
April | 1816.45 | 533.28 | 831.27 | 1.71 | 829.56 | 0.00 | 0.00 |
May | 2792.98 | 124.78 | 935.67 | 27.44 | 908.23 | 0.00 | 0.00 |
June | 3210.63 | 32.11 | 1001.81 | 55.62 | 946.20 | 0.00 | 0.00 |
July | 3560.16 | 1.28 | 919.26 | 26.49 | 892.78 | 0.00 | 0.00 |
August | 3459.07 | 0.33 | 855.76 | 7.08 | 848.68 | 0.00 | 0.00 |
September | 2661.91 | 43.38 | 779.51 | 0.09 | 779.43 | 0.00 | 0.00 |
October | 1892.33 | 212.44 | 691.02 | 0.00 | 691.02 | 0.00 | 0.00 |
November | 1184.63 | 621.88 | 593.23 | 0.00 | 593.23 | 0.00 | 0.00 |
December | 674.33 | 1155.89 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Annual Sum or Average | 2002.82 | 509.30 | 756.36 | 9.90 | 746.46 | 0.00 | 0.00 |
Minimum of Months | 601.94 | 0.33 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Maximum of Months | 3560.16 | 1385.22 | 1001.81 | 55.62 | 946.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 901.28 | 855.77 | 675.79 | 204.46 | 471.33 | 0.00 | 0.00 |
February | 1105.04 | 719.41 | 736.46 | 199.58 | 536.87 | 0.00 | 0.00 |
March | 1424.53 | 536.89 | 813.49 | 200.50 | 612.99 | 0.00 | 0.00 |
April | 2046.24 | 324.62 | 990.46 | 288.59 | 701.87 | 0.00 | 0.00 |
May | 2770.16 | 79.96 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
June | 2921.10 | 17.44 | 1084.00 | 331.50 | 752.50 | 0.00 | 0.00 |
July | 3145.78 | 0.54 | 1011.75 | 291.69 | 720.06 | 0.00 | 0.00 |
August | 3236.62 | 0.01 | 1036.01 | 317.97 | 718.05 | 0.00 | 0.00 |
September | 2642.13 | 26.14 | 973.97 | 301.04 | 672.93 | 0.00 | 0.00 |
October | 2065.79 | 127.19 | 883.78 | 288.73 | 595.05 | 0.00 | 0.00 |
November | 1428.71 | 377.17 | 740.61 | 234.59 | 506.03 | 0.00 | 0.00 |
December | 889.27 | 693.63 | 599.46 | 164.47 | 434.99 | 0.00 | 0.00 |
Annual Sum or Average | 2053.49 | 311.28 | 888.31 | 264.92 | 623.40 | 0.00 | 0.00 |
Minimum of Months | 889.27 | 0.01 | 599.46 | 164.47 | 434.99 | 0.00 | 0.00 |
Maximum of Months | 3236.62 | 855.77 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2837.99 | 1335.24 | 1811.04 | 851.45 | 959.59 | 0.00 | 0.00 |
February | 2840.75 | 1156.29 | 1700.64 | 695.64 | 1005.01 | 0.00 | 0.00 |
March | 2619.91 | 896.35 | 1399.71 | 380.01 | 1019.69 | 0.00 | 0.00 |
April | 2438.29 | 555.67 | 1100.27 | 116.65 | 983.62 | 0.00 | 0.00 |
May | 2784.08 | 128.48 | 932.03 | 14.27 | 917.75 | 0.00 | 0.00 |
June | 2941.48 | 25.37 | 877.76 | 1.09 | 876.67 | 0.00 | 0.00 |
July | 3455.16 | 0.73 | 877.73 | 7.46 | 870.27 | 0.00 | 0.00 |
August | 3831.33 | 0.25 | 1018.10 | 72.14 | 945.96 | 0.00 | 0.00 |
September | 3862.03 | 48.53 | 1342.38 | 307.64 | 1034.73 | 0.00 | 0.00 |
October | 4014.74 | 235.55 | 1757.43 | 698.68 | 1058.75 | 0.00 | 0.00 |
November | 3728.90 | 645.73 | 1938.81 | 934.65 | 1004.16 | 0.00 | 0.00 |
December | 3002.14 | 1135.04 | 1799.80 | 889.05 | 910.75 | 0.00 | 0.00 |
Annual Sum or Average | 3198.82 | 510.46 | 1377.71 | 412.56 | 965.16 | 0.00 | 0.00 |
Minimum of Months | 2438.29 | 0.25 | 877.73 | 1.09 | 870.27 | 0.00 | 0.00 |
Maximum of Months | 4014.74 | 1335.24 | 1938.81 | 934.65 | 1058.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 903.16 | 1012.97 | 662.73 | 190.34 | 472.39 | 0.00 | 0.00 |
February | 1138.86 | 894.52 | 756.77 | 215.80 | 540.97 | 0.00 | 0.00 |
March | 1540.07 | 718.91 | 896.42 | 265.39 | 631.03 | 0.00 | 0.00 |
April | 1947.94 | 503.78 | 979.64 | 275.23 | 704.41 | 0.00 | 0.00 |
May | 2647.12 | 128.30 | 1066.33 | 319.20 | 747.13 | 0.00 | 0.00 |
June | 2869.01 | 46.70 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
July | 2996.97 | 4.30 | 1010.93 | 289.21 | 721.72 | 0.00 | 0.00 |
August | 2999.95 | 4.59 | 1037.10 | 315.32 | 721.78 | 0.00 | 0.00 |
September | 2589.97 | 53.30 | 986.55 | 309.95 | 676.61 | 0.00 | 0.00 |
October | 1998.11 | 220.57 | 876.76 | 283.22 | 593.54 | 0.00 | 0.00 |
November | 1425.33 | 546.95 | 753.46 | 246.41 | 507.06 | 0.00 | 0.00 |
December | 926.59 | 947.46 | 630.77 | 190.67 | 440.10 | 0.00 | 0.00 |
Annual Sum or Average | 2003.36 | 421.15 | 897.12 | 270.86 | 626.26 | 0.00 | 0.00 |
Minimum of Months | 903.16 | 4.30 | 630.77 | 190.34 | 440.10 | 0.00 | 0.00 |
Maximum of Months | 2999.95 | 1012.97 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 653.71 | 1226.92 | 560.36 | 0.00 | 560.36 | 0.00 | 0.00 |
February | 891.05 | 1041.48 | 642.34 | 0.00 | 642.34 | 0.00 | 0.00 |
March | 1275.22 | 810.05 | 737.81 | 0.00 | 737.81 | 0.00 | 0.00 |
April | 1847.30 | 518.92 | 831.27 | 1.71 | 829.56 | 0.00 | 0.00 |
May | 2813.11 | 128.56 | 935.67 | 27.44 | 908.23 | 0.00 | 0.00 |
June | 3249.73 | 30.70 | 1001.81 | 55.62 | 946.19 | 0.00 | 0.00 |
July | 3624.91 | 0.77 | 919.26 | 26.49 | 892.77 | 0.00 | 0.00 |
August | 3571.97 | 0.05 | 855.75 | 7.08 | 848.67 | 0.00 | 0.00 |
September | 2700.28 | 43.28 | 779.51 | 0.09 | 779.42 | 0.00 | 0.00 |
October | 1930.17 | 213.18 | 691.02 | 0.00 | 691.02 | 0.00 | 0.00 |
November | 1221.65 | 587.63 | 593.23 | 0.00 | 593.23 | 0.00 | 0.00 |
December | 725.38 | 1018.56 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Annual Sum or Average | 2049.17 | 465.53 | 756.36 | 9.90 | 746.46 | 0.00 | 0.00 |
Minimum of Months | 653.71 | 0.05 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Maximum of Months | 3624.91 | 1226.92 | 1001.81 | 55.62 | 946.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 911.18 | 797.31 | 675.79 | 204.46 | 471.33 | 0.00 | 0.00 |
February | 1103.56 | 682.84 | 736.45 | 199.58 | 536.87 | 0.00 | 0.00 |
March | 1410.42 | 534.69 | 813.49 | 200.49 | 612.99 | 0.00 | 0.00 |
April | 2021.50 | 351.81 | 990.45 | 288.59 | 701.87 | 0.00 | 0.00 |
May | 2745.78 | 88.68 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
June | 2902.41 | 20.38 | 1084.00 | 331.50 | 752.50 | 0.00 | 0.00 |
July | 3133.98 | 0.48 | 1011.74 | 291.68 | 720.06 | 0.00 | 0.00 |
August | 3234.96 | 0.03 | 1036.01 | 317.97 | 718.04 | 0.00 | 0.00 |
September | 2624.31 | 29.01 | 973.97 | 301.04 | 672.93 | 0.00 | 0.00 |
October | 2048.64 | 142.67 | 883.78 | 288.73 | 595.05 | 0.00 | 0.00 |
November | 1413.85 | 388.55 | 740.61 | 234.59 | 506.02 | 0.00 | 0.00 |
December | 890.85 | 665.22 | 599.45 | 164.47 | 434.99 | 0.00 | 0.00 |
Annual Sum or Average | 2042.23 | 306.61 | 888.31 | 264.91 | 623.39 | 0.00 | 0.00 |
Minimum of Months | 890.85 | 0.03 | 599.45 | 164.47 | 434.99 | 0.00 | 0.00 |
Maximum of Months | 3234.96 | 797.31 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2820.64 | 1293.20 | 1811.03 | 851.45 | 959.59 | 0.00 | 0.00 |
February | 2825.30 | 1111.03 | 1700.64 | 695.64 | 1005.00 | 0.00 | 0.00 |
March | 2612.42 | 871.95 | 1399.70 | 380.01 | 1019.69 | 0.00 | 0.00 |
April | 2448.55 | 551.98 | 1100.27 | 116.65 | 983.62 | 0.00 | 0.00 |
May | 2802.99 | 130.65 | 932.02 | 14.27 | 917.75 | 0.00 | 0.00 |
June | 2988.94 | 22.88 | 877.75 | 1.09 | 876.67 | 0.00 | 0.00 |
July | 3515.48 | 0.31 | 877.73 | 7.46 | 870.27 | 0.00 | 0.00 |
August | 3923.88 | 0.04 | 1018.10 | 72.14 | 945.96 | 0.00 | 0.00 |
September | 3869.71 | 50.12 | 1342.37 | 307.64 | 1034.73 | 0.00 | 0.00 |
October | 4004.72 | 246.96 | 1757.43 | 698.68 | 1058.75 | 0.00 | 0.00 |
November | 3707.27 | 648.77 | 1938.80 | 934.65 | 1004.15 | 0.00 | 0.00 |
December | 2993.20 | 1093.16 | 1799.79 | 889.04 | 910.75 | 0.00 | 0.00 |
Annual Sum or Average | 3212.10 | 498.76 | 1377.71 | 412.56 | 965.15 | 0.00 | 0.00 |
Minimum of Months | 2448.55 | 0.04 | 877.73 | 1.09 | 870.27 | 0.00 | 0.00 |
Maximum of Months | 4004.72 | 1293.20 | 1938.80 | 934.65 | 1058.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 939.50 | 883.70 | 662.73 | 190.34 | 472.39 | 0.00 | 0.00 |
February | 1179.47 | 755.69 | 756.77 | 215.80 | 540.97 | 0.00 | 0.00 |
March | 1581.98 | 604.10 | 896.42 | 265.39 | 631.03 | 0.00 | 0.00 |
April | 2005.88 | 410.83 | 979.63 | 275.22 | 704.41 | 0.00 | 0.00 |
May | 2676.09 | 113.81 | 1066.33 | 319.19 | 747.13 | 0.00 | 0.00 |
June | 2934.57 | 29.28 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
July | 3105.40 | 1.17 | 1010.93 | 289.21 | 721.72 | 0.00 | 0.00 |
August | 3189.56 | 0.40 | 1037.10 | 315.32 | 721.78 | 0.00 | 0.00 |
September | 2634.41 | 42.60 | 986.55 | 309.95 | 676.60 | 0.00 | 0.00 |
October | 2043.93 | 183.38 | 876.75 | 283.22 | 593.54 | 0.00 | 0.00 |
November | 1473.33 | 450.37 | 753.46 | 246.41 | 507.05 | 0.00 | 0.00 |
December | 989.61 | 751.61 | 630.76 | 190.67 | 440.10 | 0.00 | 0.00 |
Annual Sum or Average | 2067.89 | 350.23 | 897.12 | 270.86 | 626.26 | 0.00 | 0.00 |
Minimum of Months | 939.50 | 0.40 | 630.76 | 190.34 | 440.10 | 0.00 | 0.00 |
Maximum of Months | 3189.56 | 883.70 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 678.45 | 1148.89 | 560.36 | 0.00 | 560.36 | 0.00 | 0.00 |
February | 902.03 | 992.61 | 642.34 | 0.00 | 642.34 | 0.00 | 0.00 |
March | 1269.59 | 788.95 | 737.81 | 0.00 | 737.81 | 0.00 | 0.00 |
April | 1827.25 | 521.62 | 831.27 | 1.71 | 829.56 | 0.00 | 0.00 |
May | 2777.62 | 135.33 | 935.67 | 27.44 | 908.23 | 0.00 | 0.00 |
June | 3210.20 | 34.25 | 1001.81 | 55.62 | 946.19 | 0.00 | 0.00 |
July | 3571.73 | 1.22 | 919.26 | 26.49 | 892.77 | 0.00 | 0.00 |
August | 3524.52 | 0.11 | 855.75 | 7.08 | 848.67 | 0.00 | 0.00 |
September | 2662.82 | 45.84 | 779.51 | 0.09 | 779.42 | 0.00 | 0.00 |
October | 1908.28 | 218.95 | 691.02 | 0.00 | 691.02 | 0.00 | 0.00 |
November | 1215.07 | 574.66 | 593.23 | 0.00 | 593.23 | 0.00 | 0.00 |
December | 739.31 | 966.15 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Annual Sum or Average | 2030.88 | 449.68 | 756.36 | 9.90 | 746.46 | 0.00 | 0.00 |
Minimum of Months | 678.45 | 0.11 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Maximum of Months | 3571.73 | 1148.89 | 1001.81 | 55.62 | 946.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 935.14 | 753.89 | 675.79 | 204.46 | 471.33 | 0.00 | 0.00 |
February | 1117.26 | 654.97 | 736.45 | 199.58 | 536.87 | 0.00 | 0.00 |
March | 1413.63 | 521.97 | 813.49 | 200.49 | 612.99 | 0.00 | 0.00 |
April | 2015.44 | 352.26 | 990.45 | 288.59 | 701.87 | 0.00 | 0.00 |
May | 2729.58 | 92.21 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
June | 2884.13 | 22.26 | 1084.00 | 331.50 | 752.50 | 0.00 | 0.00 |
July | 3106.85 | 0.71 | 1011.74 | 291.68 | 720.06 | 0.00 | 0.00 |
August | 3212.35 | 0.06 | 1036.01 | 317.97 | 718.04 | 0.00 | 0.00 |
September | 2607.25 | 30.20 | 973.97 | 301.04 | 672.93 | 0.00 | 0.00 |
October | 2040.77 | 144.87 | 883.78 | 288.73 | 595.05 | 0.00 | 0.00 |
November | 1415.97 | 380.14 | 740.61 | 234.59 | 506.02 | 0.00 | 0.00 |
December | 906.60 | 635.36 | 599.45 | 164.47 | 434.99 | 0.00 | 0.00 |
Annual Sum or Average | 2037.42 | 297.28 | 888.31 | 264.91 | 623.39 | 0.00 | 0.00 |
Minimum of Months | 906.60 | 0.06 | 599.45 | 164.47 | 434.99 | 0.00 | 0.00 |
Maximum of Months | 3212.35 | 753.89 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2835.70 | 1229.66 | 1811.03 | 851.45 | 959.59 | 0.00 | 0.00 |
February | 2825.99 | 1068.80 | 1700.64 | 695.64 | 1005.00 | 0.00 | 0.00 |
March | 2600.96 | 851.50 | 1399.70 | 380.01 | 1019.69 | 0.00 | 0.00 |
April | 2427.19 | 552.98 | 1100.27 | 116.65 | 983.62 | 0.00 | 0.00 |
May | 2767.26 | 136.74 | 932.02 | 14.27 | 917.75 | 0.00 | 0.00 |
June | 2948.72 | 25.42 | 877.75 | 1.09 | 876.67 | 0.00 | 0.00 |
July | 3461.30 | 0.56 | 877.73 | 7.46 | 870.27 | 0.00 | 0.00 |
August | 3876.22 | 0.09 | 1018.10 | 72.14 | 945.96 | 0.00 | 0.00 |
September | 3831.10 | 52.50 | 1342.37 | 307.64 | 1034.73 | 0.00 | 0.00 |
October | 3978.26 | 250.83 | 1757.43 | 698.68 | 1058.75 | 0.00 | 0.00 |
November | 3692.89 | 636.07 | 1938.80 | 934.65 | 1004.15 | 0.00 | 0.00 |
December | 2996.89 | 1051.78 | 1799.79 | 889.04 | 910.75 | 0.00 | 0.00 |
Annual Sum or Average | 3189.42 | 485.18 | 1377.71 | 412.56 | 965.15 | 0.00 | 0.00 |
Minimum of Months | 2427.19 | 0.09 | 877.73 | 1.09 | 870.27 | 0.00 | 0.00 |
Maximum of Months | 3978.26 | 1229.66 | 1938.80 | 934.65 | 1058.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 946.63 | 839.90 | 662.73 | 190.34 | 472.39 | 0.00 | 0.00 |
February | 1178.99 | 727.83 | 756.77 | 215.80 | 540.97 | 0.00 | 0.00 |
March | 1572.39 | 590.88 | 896.42 | 265.39 | 631.03 | 0.00 | 0.00 |
April | 1989.54 | 410.21 | 979.63 | 275.22 | 704.41 | 0.00 | 0.00 |
May | 2652.49 | 117.28 | 1066.33 | 319.19 | 747.13 | 0.00 | 0.00 |
June | 2909.46 | 31.18 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
July | 3072.84 | 1.56 | 1010.93 | 289.21 | 721.72 | 0.00 | 0.00 |
August | 3159.42 | 0.51 | 1037.10 | 315.32 | 721.78 | 0.00 | 0.00 |
September | 2610.94 | 44.53 | 986.55 | 309.95 | 676.60 | 0.00 | 0.00 |
October | 2028.55 | 185.86 | 876.75 | 283.22 | 593.54 | 0.00 | 0.00 |
November | 1465.38 | 441.43 | 753.46 | 246.41 | 507.05 | 0.00 | 0.00 |
December | 991.07 | 722.49 | 630.76 | 190.67 | 440.10 | 0.00 | 0.00 |
Annual Sum or Average | 2053.14 | 340.86 | 897.12 | 270.86 | 626.26 | 0.00 | 0.00 |
Minimum of Months | 946.63 | 0.51 | 630.76 | 190.34 | 440.10 | 0.00 | 0.00 |
Maximum of Months | 3159.42 | 839.90 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.161224E+10 | 0.371017E+10 | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.00 | 0.00 |
February | 0.205420E+10 | 0.282014E+10 | 0.155395E+10 | 0.00 | 0.155395E+10 | 0.00 | 0.00 |
March | 0.333845E+10 | 0.233761E+10 | 0.197616E+10 | 0.00 | 0.197616E+10 | 0.00 | 0.00 |
April | 0.470823E+10 | 0.138226E+10 | 0.215466E+10 | 4439570.55 | 0.215022E+10 | 0.00 | 0.00 |
May | 0.748072E+10 | 0.334218E+09 | 0.250611E+10 | 73502551.72 | 0.243260E+10 | 0.00 | 0.00 |
June | 0.832195E+10 | 83230986.98 | 0.259670E+10 | 0.144161E+09 | 0.245254E+10 | 0.00 | 0.00 |
July | 0.953554E+10 | 3418679.31 | 0.246215E+10 | 70940604.60 | 0.239121E+10 | 0.00 | 0.00 |
August | 0.926477E+10 | 878351.92 | 0.229205E+10 | 18957563.92 | 0.227310E+10 | 0.00 | 0.00 |
September | 0.689966E+10 | 0.112429E+09 | 0.202050E+10 | 231530.94 | 0.202027E+10 | 0.00 | 0.00 |
October | 0.506843E+10 | 0.569011E+09 | 0.185084E+10 | 0.00 | 0.185084E+10 | 0.00 | 0.00 |
November | 0.307056E+10 | 0.161190E+10 | 0.153765E+10 | 0.00 | 0.153765E+10 | 0.00 | 0.00 |
December | 0.180614E+10 | 0.309592E+10 | 0.140088E+10 | 0.00 | 0.140088E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.631609E+11 | 0.160612E+11 | 0.238525E+11 | 0.312233E+09 | 0.235403E+11 | 0.00 | 0.00 |
Minimum of Months | 0.161224E+10 | 878351.92 | 0.140088E+10 | 0.00 | 0.140088E+10 | 0.00 | 0.00 |
Maximum of Months | 0.953554E+10 | 0.371017E+10 | 0.259670E+10 | 0.144161E+09 | 0.245254E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.241398E+10 | 0.229209E+10 | 0.181004E+10 | 0.547624E+09 | 0.126241E+10 | 0.00 | 0.00 |
February | 0.267331E+10 | 0.174039E+10 | 0.178163E+10 | 0.482831E+09 | 0.129880E+10 | 0.00 | 0.00 |
March | 0.381547E+10 | 0.143800E+10 | 0.217885E+10 | 0.537008E+09 | 0.164185E+10 | 0.00 | 0.00 |
April | 0.530386E+10 | 0.841417E+09 | 0.256727E+10 | 0.748018E+09 | 0.181925E+10 | 0.00 | 0.00 |
May | 0.741959E+10 | 0.214160E+09 | 0.296462E+10 | 0.944545E+09 | 0.202008E+10 | 0.00 | 0.00 |
June | 0.757148E+10 | 45205263.90 | 0.280974E+10 | 0.859248E+09 | 0.195049E+10 | 0.00 | 0.00 |
July | 0.842566E+10 | 1439786.26 | 0.270987E+10 | 0.781250E+09 | 0.192862E+10 | 0.00 | 0.00 |
August | 0.866897E+10 | 39149.71 | 0.277486E+10 | 0.851642E+09 | 0.192322E+10 | 0.00 | 0.00 |
September | 0.684840E+10 | 67751703.75 | 0.252454E+10 | 0.780305E+09 | 0.174423E+10 | 0.00 | 0.00 |
October | 0.553301E+10 | 0.340659E+09 | 0.236713E+10 | 0.773342E+09 | 0.159379E+10 | 0.00 | 0.00 |
November | 0.370322E+10 | 0.977614E+09 | 0.191967E+10 | 0.608054E+09 | 0.131162E+10 | 0.00 | 0.00 |
December | 0.238181E+10 | 0.185783E+10 | 0.160558E+10 | 0.440507E+09 | 0.116507E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.647588E+11 | 0.981659E+10 | 0.280138E+11 | 0.835437E+10 | 0.196594E+11 | 0.00 | 0.00 |
Minimum of Months | 0.238181E+10 | 39149.71 | 0.160558E+10 | 0.440507E+09 | 0.116507E+10 | 0.00 | 0.00 |
Maximum of Months | 0.866897E+10 | 0.229209E+10 | 0.296462E+10 | 0.944545E+09 | 0.202008E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.760126E+10 | 0.357631E+10 | 0.485069E+10 | 0.228053E+10 | 0.257016E+10 | 0.00 | 0.00 |
February | 0.687234E+10 | 0.279730E+10 | 0.411420E+10 | 0.168289E+10 | 0.243131E+10 | 0.00 | 0.00 |
March | 0.701717E+10 | 0.240080E+10 | 0.374897E+10 | 0.101783E+10 | 0.273115E+10 | 0.00 | 0.00 |
April | 0.632005E+10 | 0.144030E+10 | 0.285191E+10 | 0.302357E+09 | 0.254956E+10 | 0.00 | 0.00 |
May | 0.745687E+10 | 0.344111E+09 | 0.249634E+10 | 38229006.22 | 0.245811E+10 | 0.00 | 0.00 |
June | 0.762432E+10 | 65768783.34 | 0.227514E+10 | 2815574.52 | 0.227233E+10 | 0.00 | 0.00 |
July | 0.925431E+10 | 1953393.86 | 0.235092E+10 | 19975623.99 | 0.233094E+10 | 0.00 | 0.00 |
August | 0.102618E+11 | 671344.94 | 0.272688E+10 | 0.193210E+09 | 0.253367E+10 | 0.00 | 0.00 |
September | 0.100104E+11 | 0.125779E+09 | 0.347944E+10 | 0.797415E+09 | 0.268202E+10 | 0.00 | 0.00 |
October | 0.107531E+11 | 0.630906E+09 | 0.470711E+10 | 0.187134E+10 | 0.283577E+10 | 0.00 | 0.00 |
November | 0.966530E+10 | 0.167374E+10 | 0.502538E+10 | 0.242261E+10 | 0.260278E+10 | 0.00 | 0.00 |
December | 0.804093E+10 | 0.304009E+10 | 0.482058E+10 | 0.238122E+10 | 0.243936E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100878E+12 | 0.160977E+11 | 0.434476E+11 | 0.130104E+11 | 0.304372E+11 | 0.00 | 0.00 |
Minimum of Months | 0.632005E+10 | 671344.94 | 0.227514E+10 | 2815574.52 | 0.227233E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107531E+11 | 0.357631E+10 | 0.502538E+10 | 0.242261E+10 | 0.283577E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.241902E+10 | 0.271314E+10 | 0.177507E+10 | 0.509815E+09 | 0.126525E+10 | 0.00 | 0.00 |
February | 0.275513E+10 | 0.216402E+10 | 0.183079E+10 | 0.522068E+09 | 0.130872E+10 | 0.00 | 0.00 |
March | 0.412493E+10 | 0.192553E+10 | 0.240098E+10 | 0.710816E+09 | 0.169016E+10 | 0.00 | 0.00 |
April | 0.504907E+10 | 0.130579E+10 | 0.253922E+10 | 0.713384E+09 | 0.182583E+10 | 0.00 | 0.00 |
May | 0.709005E+10 | 0.343649E+09 | 0.285606E+10 | 0.854933E+09 | 0.200112E+10 | 0.00 | 0.00 |
June | 0.743647E+10 | 0.121043E+09 | 0.285629E+10 | 0.900378E+09 | 0.195591E+10 | 0.00 | 0.00 |
July | 0.802708E+10 | 11512351.44 | 0.270768E+10 | 0.774614E+09 | 0.193307E+10 | 0.00 | 0.00 |
August | 0.803507E+10 | 12291164.88 | 0.277778E+10 | 0.844564E+09 | 0.193322E+10 | 0.00 | 0.00 |
September | 0.671320E+10 | 0.138150E+09 | 0.255715E+10 | 0.803382E+09 | 0.175376E+10 | 0.00 | 0.00 |
October | 0.535174E+10 | 0.590783E+09 | 0.234830E+10 | 0.758567E+09 | 0.158974E+10 | 0.00 | 0.00 |
November | 0.369446E+10 | 0.141769E+10 | 0.195298E+10 | 0.638686E+09 | 0.131429E+10 | 0.00 | 0.00 |
December | 0.248178E+10 | 0.253768E+10 | 0.168944E+10 | 0.510689E+09 | 0.117876E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.631780E+11 | 0.132813E+11 | 0.282917E+11 | 0.854189E+10 | 0.197498E+11 | 0.00 | 0.00 |
Minimum of Months | 0.241902E+10 | 11512351.44 | 0.168944E+10 | 0.509815E+09 | 0.117876E+10 | 0.00 | 0.00 |
Maximum of Months | 0.803507E+10 | 0.271314E+10 | 0.285629E+10 | 0.900378E+09 | 0.200112E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.175091E+10 | 0.328619E+10 | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.00 | 0.00 |
February | 0.215563E+10 | 0.251954E+10 | 0.155394E+10 | 0.00 | 0.155394E+10 | 0.00 | 0.00 |
March | 0.341555E+10 | 0.216964E+10 | 0.197615E+10 | 0.00 | 0.197615E+10 | 0.00 | 0.00 |
April | 0.478819E+10 | 0.134505E+10 | 0.215465E+10 | 4439554.79 | 0.215021E+10 | 0.00 | 0.00 |
May | 0.753462E+10 | 0.344326E+09 | 0.250610E+10 | 73502290.71 | 0.243259E+10 | 0.00 | 0.00 |
June | 0.842330E+10 | 79571884.77 | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.00 | 0.00 |
July | 0.970897E+10 | 2051556.75 | 0.246214E+10 | 70940352.69 | 0.239120E+10 | 0.00 | 0.00 |
August | 0.956715E+10 | 136758.93 | 0.229205E+10 | 18957496.60 | 0.227309E+10 | 0.00 | 0.00 |
September | 0.699912E+10 | 0.112191E+09 | 0.202049E+10 | 231530.12 | 0.202026E+10 | 0.00 | 0.00 |
October | 0.516977E+10 | 0.570992E+09 | 0.185083E+10 | 0.00 | 0.185083E+10 | 0.00 | 0.00 |
November | 0.316652E+10 | 0.152312E+10 | 0.153764E+10 | 0.00 | 0.153764E+10 | 0.00 | 0.00 |
December | 0.194285E+10 | 0.272810E+10 | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.646226E+11 | 0.146809E+11 | 0.238524E+11 | 0.312232E+09 | 0.235402E+11 | 0.00 | 0.00 |
Minimum of Months | 0.175091E+10 | 136758.93 | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.00 | 0.00 |
Maximum of Months | 0.970897E+10 | 0.328619E+10 | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244050E+10 | 0.213552E+10 | 0.181003E+10 | 0.547622E+09 | 0.126241E+10 | 0.00 | 0.00 |
February | 0.266974E+10 | 0.165193E+10 | 0.178163E+10 | 0.482829E+09 | 0.129880E+10 | 0.00 | 0.00 |
March | 0.377767E+10 | 0.143210E+10 | 0.217884E+10 | 0.537005E+09 | 0.164184E+10 | 0.00 | 0.00 |
April | 0.523973E+10 | 0.911899E+09 | 0.256726E+10 | 0.748014E+09 | 0.181924E+10 | 0.00 | 0.00 |
May | 0.735431E+10 | 0.237523E+09 | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.00 | 0.00 |
June | 0.752304E+10 | 52819681.86 | 0.280972E+10 | 0.859245E+09 | 0.195048E+10 | 0.00 | 0.00 |
July | 0.839405E+10 | 1285483.01 | 0.270986E+10 | 0.781247E+09 | 0.192861E+10 | 0.00 | 0.00 |
August | 0.866451E+10 | 81335.86 | 0.277485E+10 | 0.851639E+09 | 0.192321E+10 | 0.00 | 0.00 |
September | 0.680222E+10 | 75186139.38 | 0.252453E+10 | 0.780302E+09 | 0.174423E+10 | 0.00 | 0.00 |
October | 0.548707E+10 | 0.382140E+09 | 0.236712E+10 | 0.773339E+09 | 0.159378E+10 | 0.00 | 0.00 |
November | 0.366470E+10 | 0.100713E+10 | 0.191966E+10 | 0.608051E+09 | 0.131161E+10 | 0.00 | 0.00 |
December | 0.238606E+10 | 0.178172E+10 | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.644036E+11 | 0.966933E+10 | 0.280137E+11 | 0.835434E+10 | 0.196593E+11 | 0.00 | 0.00 |
Minimum of Months | 0.238606E+10 | 81335.86 | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.00 | 0.00 |
Maximum of Months | 0.866451E+10 | 0.213552E+10 | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.755480E+10 | 0.346371E+10 | 0.485067E+10 | 0.228052E+10 | 0.257015E+10 | 0.00 | 0.00 |
February | 0.683497E+10 | 0.268780E+10 | 0.411418E+10 | 0.168288E+10 | 0.243130E+10 | 0.00 | 0.00 |
March | 0.699709E+10 | 0.233544E+10 | 0.374896E+10 | 0.101782E+10 | 0.273114E+10 | 0.00 | 0.00 |
April | 0.634663E+10 | 0.143074E+10 | 0.285190E+10 | 0.302356E+09 | 0.254955E+10 | 0.00 | 0.00 |
May | 0.750752E+10 | 0.349920E+09 | 0.249633E+10 | 38228870.47 | 0.245811E+10 | 0.00 | 0.00 |
June | 0.774733E+10 | 59297791.82 | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.00 | 0.00 |
July | 0.941587E+10 | 821349.26 | 0.235091E+10 | 19975553.05 | 0.233093E+10 | 0.00 | 0.00 |
August | 0.105097E+11 | 106273.23 | 0.272687E+10 | 0.193210E+09 | 0.253366E+10 | 0.00 | 0.00 |
September | 0.100303E+11 | 0.129919E+09 | 0.347943E+10 | 0.797412E+09 | 0.268201E+10 | 0.00 | 0.00 |
October | 0.107262E+11 | 0.661468E+09 | 0.470709E+10 | 0.187133E+10 | 0.283576E+10 | 0.00 | 0.00 |
November | 0.960925E+10 | 0.168160E+10 | 0.502537E+10 | 0.242260E+10 | 0.260277E+10 | 0.00 | 0.00 |
December | 0.801699E+10 | 0.292793E+10 | 0.482056E+10 | 0.238121E+10 | 0.243935E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.101297E+12 | 0.157288E+11 | 0.434474E+11 | 0.130104E+11 | 0.304370E+11 | 0.00 | 0.00 |
Minimum of Months | 0.634663E+10 | 106273.23 | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107262E+11 | 0.346371E+10 | 0.502537E+10 | 0.242260E+10 | 0.283576E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.251636E+10 | 0.236691E+10 | 0.177506E+10 | 0.509812E+09 | 0.126525E+10 | 0.00 | 0.00 |
February | 0.285336E+10 | 0.182817E+10 | 0.183078E+10 | 0.522065E+09 | 0.130872E+10 | 0.00 | 0.00 |
March | 0.423719E+10 | 0.161802E+10 | 0.240097E+10 | 0.710813E+09 | 0.169016E+10 | 0.00 | 0.00 |
April | 0.519924E+10 | 0.106488E+10 | 0.253921E+10 | 0.713381E+09 | 0.182583E+10 | 0.00 | 0.00 |
May | 0.716763E+10 | 0.304841E+09 | 0.285604E+10 | 0.854929E+09 | 0.200112E+10 | 0.00 | 0.00 |
June | 0.760642E+10 | 75896897.06 | 0.285628E+10 | 0.900374E+09 | 0.195590E+10 | 0.00 | 0.00 |
July | 0.831750E+10 | 3122994.84 | 0.270767E+10 | 0.774611E+09 | 0.193306E+10 | 0.00 | 0.00 |
August | 0.854293E+10 | 1069178.14 | 0.277777E+10 | 0.844560E+09 | 0.193321E+10 | 0.00 | 0.00 |
September | 0.682838E+10 | 0.110431E+09 | 0.255713E+10 | 0.803378E+09 | 0.175376E+10 | 0.00 | 0.00 |
October | 0.547446E+10 | 0.491170E+09 | 0.234829E+10 | 0.758564E+09 | 0.158973E+10 | 0.00 | 0.00 |
November | 0.381887E+10 | 0.116736E+10 | 0.195297E+10 | 0.638684E+09 | 0.131429E+10 | 0.00 | 0.00 |
December | 0.265056E+10 | 0.201311E+10 | 0.168944E+10 | 0.510687E+09 | 0.117875E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.652129E+11 | 0.110450E+11 | 0.282916E+11 | 0.854186E+10 | 0.197498E+11 | 0.00 | 0.00 |
Minimum of Months | 0.251636E+10 | 1069178.14 | 0.168944E+10 | 0.509812E+09 | 0.117875E+10 | 0.00 | 0.00 |
Maximum of Months | 0.854293E+10 | 0.236691E+10 | 0.285628E+10 | 0.900374E+09 | 0.200112E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.181716E+10 | 0.307719E+10 | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.00 | 0.00 |
February | 0.218219E+10 | 0.240132E+10 | 0.155394E+10 | 0.00 | 0.155394E+10 | 0.00 | 0.00 |
March | 0.340047E+10 | 0.211313E+10 | 0.197615E+10 | 0.00 | 0.197615E+10 | 0.00 | 0.00 |
April | 0.473624E+10 | 0.135204E+10 | 0.215465E+10 | 4439554.79 | 0.215021E+10 | 0.00 | 0.00 |
May | 0.743958E+10 | 0.362480E+09 | 0.250610E+10 | 73502290.71 | 0.243259E+10 | 0.00 | 0.00 |
June | 0.832083E+10 | 88772557.41 | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.00 | 0.00 |
July | 0.956653E+10 | 3254980.47 | 0.246214E+10 | 70940352.69 | 0.239120E+10 | 0.00 | 0.00 |
August | 0.944007E+10 | 304355.24 | 0.229205E+10 | 18957496.60 | 0.227309E+10 | 0.00 | 0.00 |
September | 0.690202E+10 | 0.118816E+09 | 0.202049E+10 | 231530.12 | 0.202026E+10 | 0.00 | 0.00 |
October | 0.511115E+10 | 0.586443E+09 | 0.185083E+10 | 0.00 | 0.185083E+10 | 0.00 | 0.00 |
November | 0.314946E+10 | 0.148953E+10 | 0.153764E+10 | 0.00 | 0.153764E+10 | 0.00 | 0.00 |
December | 0.198018E+10 | 0.258774E+10 | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.640459E+11 | 0.141810E+11 | 0.238524E+11 | 0.312232E+09 | 0.235402E+11 | 0.00 | 0.00 |
Minimum of Months | 0.181716E+10 | 304355.24 | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.00 | 0.00 |
Maximum of Months | 0.956653E+10 | 0.307719E+10 | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.250469E+10 | 0.201922E+10 | 0.181003E+10 | 0.547622E+09 | 0.126241E+10 | 0.00 | 0.00 |
February | 0.270287E+10 | 0.158451E+10 | 0.178163E+10 | 0.482829E+09 | 0.129880E+10 | 0.00 | 0.00 |
March | 0.378628E+10 | 0.139805E+10 | 0.217884E+10 | 0.537005E+09 | 0.164184E+10 | 0.00 | 0.00 |
April | 0.522403E+10 | 0.913052E+09 | 0.256726E+10 | 0.748014E+09 | 0.181924E+10 | 0.00 | 0.00 |
May | 0.731091E+10 | 0.246962E+09 | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.00 | 0.00 |
June | 0.747568E+10 | 57685508.29 | 0.280972E+10 | 0.859245E+09 | 0.195048E+10 | 0.00 | 0.00 |
July | 0.832137E+10 | 1907077.04 | 0.270986E+10 | 0.781247E+09 | 0.192861E+10 | 0.00 | 0.00 |
August | 0.860396E+10 | 160553.26 | 0.277485E+10 | 0.851639E+09 | 0.192321E+10 | 0.00 | 0.00 |
September | 0.675800E+10 | 78279485.32 | 0.252453E+10 | 0.780302E+09 | 0.174423E+10 | 0.00 | 0.00 |
October | 0.546600E+10 | 0.388021E+09 | 0.236712E+10 | 0.773339E+09 | 0.159378E+10 | 0.00 | 0.00 |
November | 0.367018E+10 | 0.985331E+09 | 0.191966E+10 | 0.608051E+09 | 0.131161E+10 | 0.00 | 0.00 |
December | 0.242825E+10 | 0.170175E+10 | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.642522E+11 | 0.937492E+10 | 0.280137E+11 | 0.835434E+10 | 0.196593E+11 | 0.00 | 0.00 |
Minimum of Months | 0.242825E+10 | 160553.26 | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.00 | 0.00 |
Maximum of Months | 0.860396E+10 | 0.201922E+10 | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.759514E+10 | 0.329353E+10 | 0.485067E+10 | 0.228052E+10 | 0.257015E+10 | 0.00 | 0.00 |
February | 0.683664E+10 | 0.258564E+10 | 0.411418E+10 | 0.168288E+10 | 0.243130E+10 | 0.00 | 0.00 |
March | 0.696641E+10 | 0.228067E+10 | 0.374896E+10 | 0.101782E+10 | 0.273114E+10 | 0.00 | 0.00 |
April | 0.629128E+10 | 0.143333E+10 | 0.285190E+10 | 0.302356E+09 | 0.254955E+10 | 0.00 | 0.00 |
May | 0.741183E+10 | 0.366242E+09 | 0.249633E+10 | 38228870.47 | 0.245811E+10 | 0.00 | 0.00 |
June | 0.764309E+10 | 65885610.36 | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.00 | 0.00 |
July | 0.927074E+10 | 1504190.32 | 0.235091E+10 | 19975553.05 | 0.233093E+10 | 0.00 | 0.00 |
August | 0.103821E+11 | 238120.32 | 0.272687E+10 | 0.193210E+09 | 0.253366E+10 | 0.00 | 0.00 |
September | 0.993022E+10 | 0.136081E+09 | 0.347943E+10 | 0.797412E+09 | 0.268201E+10 | 0.00 | 0.00 |
October | 0.106554E+11 | 0.671836E+09 | 0.470709E+10 | 0.187133E+10 | 0.283576E+10 | 0.00 | 0.00 |
November | 0.957198E+10 | 0.164871E+10 | 0.502537E+10 | 0.242260E+10 | 0.260277E+10 | 0.00 | 0.00 |
December | 0.802687E+10 | 0.281709E+10 | 0.482056E+10 | 0.238121E+10 | 0.243935E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100582E+12 | 0.153008E+11 | 0.434474E+11 | 0.130104E+11 | 0.304370E+11 | 0.00 | 0.00 |
Minimum of Months | 0.629128E+10 | 238120.32 | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106554E+11 | 0.329353E+10 | 0.502537E+10 | 0.242260E+10 | 0.283576E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.253547E+10 | 0.224959E+10 | 0.177506E+10 | 0.509812E+09 | 0.126525E+10 | 0.00 | 0.00 |
February | 0.285222E+10 | 0.176078E+10 | 0.183078E+10 | 0.522065E+09 | 0.130872E+10 | 0.00 | 0.00 |
March | 0.421149E+10 | 0.158260E+10 | 0.240097E+10 | 0.710813E+09 | 0.169016E+10 | 0.00 | 0.00 |
April | 0.515689E+10 | 0.106327E+10 | 0.253921E+10 | 0.713381E+09 | 0.182583E+10 | 0.00 | 0.00 |
May | 0.710443E+10 | 0.314127E+09 | 0.285604E+10 | 0.854929E+09 | 0.200112E+10 | 0.00 | 0.00 |
June | 0.754132E+10 | 80814388.19 | 0.285628E+10 | 0.900374E+09 | 0.195590E+10 | 0.00 | 0.00 |
July | 0.823030E+10 | 4185017.53 | 0.270767E+10 | 0.774611E+09 | 0.193306E+10 | 0.00 | 0.00 |
August | 0.846219E+10 | 1356284.19 | 0.277777E+10 | 0.844560E+09 | 0.193321E+10 | 0.00 | 0.00 |
September | 0.676755E+10 | 0.115415E+09 | 0.255713E+10 | 0.803378E+09 | 0.175376E+10 | 0.00 | 0.00 |
October | 0.543326E+10 | 0.497817E+09 | 0.234829E+10 | 0.758564E+09 | 0.158973E+10 | 0.00 | 0.00 |
November | 0.379826E+10 | 0.114417E+10 | 0.195297E+10 | 0.638684E+09 | 0.131429E+10 | 0.00 | 0.00 |
December | 0.265447E+10 | 0.193511E+10 | 0.168944E+10 | 0.510687E+09 | 0.117875E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.647479E+11 | 0.107492E+11 | 0.282916E+11 | 0.854186E+10 | 0.197498E+11 | 0.00 | 0.00 |
Minimum of Months | 0.253547E+10 | 1356284.19 | 0.168944E+10 | 0.509812E+09 | 0.117875E+10 | 0.00 | 0.00 |
Maximum of Months | 0.846219E+10 | 0.224959E+10 | 0.285628E+10 | 0.900374E+09 | 0.200112E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.281220E+11 | -0.271030E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101898E+10 | 58.97 | 0.00 | 0.00 |
February | 0.248598E+11 | -0.239385E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -921272599.1 | 58.97 | 0.00 | 0.00 |
March | 0.271895E+11 | -0.261653E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102415E+10 | 58.97 | 0.00 | 0.00 |
April | 0.222936E+11 | -0.213060E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987632773.6 | 58.96 | 0.00 | 0.00 |
May | 0.212804E+11 | -0.202582E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102221E+10 | 58.97 | 0.00 | 0.00 |
June | 0.192544E+11 | -0.182641E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990360415.1 | 58.96 | 0.00 | 0.00 |
July | 0.178317E+11 | -0.168136E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101808E+10 | 58.97 | 0.00 | 0.00 |
August | 0.202911E+11 | -0.192697E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102139E+10 | 58.96 | 0.00 | 0.00 |
September | 0.203398E+11 | -0.193533E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986455639.8 | 58.96 | 0.00 | 0.00 |
October | 0.234804E+11 | -0.224625E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101796E+10 | 58.97 | 0.00 | 0.00 |
November | 0.253894E+11 | -0.244050E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -984324806.9 | 58.97 | 0.00 | 0.00 |
December | 0.269669E+11 | -0.259498E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101704E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.277299E+12 | -0.265289E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120099E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.178317E+11 | -0.271030E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102415E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.281220E+11 | -0.168136E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -921272599.1 | 58.97 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4187.85 | 34.38 | 311.00 | 293.00 | 1081.44 | 25.75 | 306.67 | 280.33 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-08:09 | 2168.98 | 26.03 | 160.50 | 274.83 | 966.54 | 21.70 | 215.67 | 244.00 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1604.46 | 20.06 | 41.33 | 314.33 | 827.56 | 21.23 | 242.50 | 277.17 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 1258.39 | 18.99 | 0.67 | 322.83 | 663.56 | 20.27 | 226.17 | 284.67 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1073.66 | 18.93 | 0.00 | 349.67 | 586.61 | 20.25 | 186.33 | 304.17 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:10 | 1029.03 | 18.86 | 0.00 | 344.33 | 571.46 | 20.21 | 187.33 | 298.67 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:10 | 1080.69 | 18.79 | 0.00 | 345.17 | 592.75 | 20.13 | 219.83 | 304.00 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:10 | 1265.49 | 19.26 | 13.67 | 343.17 | 675.68 | 20.59 | 261.50 | 304.00 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 1577.57 | 20.02 | 71.00 | 318.67 | 826.79 | 21.36 | 258.00 | 284.83 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:19 | 2096.10 | 21.89 | 116.83 | 316.67 | 992.90 | 22.22 | 272.33 | 287.83 |
November | 318.83 | 0.49 | 0.48 | 01-NOV-07:10 | 3529.96 | 32.29 | 257.33 | 298.17 | 1121.01 | 25.39 | 312.67 | 281.83 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:19 | 4175.93 | 34.74 | 308.17 | 289.00 | 1154.67 | 26.89 | 301.00 | 275.17 |
Annual Sum or Average | 4323.33 | 0.51 | 1994.77 | 23.19 | 1280.50 | 3809.83 | 819.08 | 21.99 | 2990.00 | 3426.67 | ||
Minimum of Months | 308.33 | 0.49 | 0.48 | 1029.03 | 18.79 | 0.00 | 274.83 | 571.46 | 20.13 | 186.33 | 244.00 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 4187.85 | 34.74 | 311.00 | 349.67 | 1154.67 | 26.89 | 312.67 | 304.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-07:00 | 1543.18 | 23.78 | 112.00 | 275.33 | 805.53 | 23.84 | 173.00 | 236.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-07:40 | 1668.33 | 23.48 | 102.67 | 263.33 | 715.93 | 22.41 | 155.00 | 227.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-07:00 | 1572.14 | 22.75 | 97.50 | 309.17 | 797.96 | 23.01 | 167.50 | 271.33 |
April | 375.00 | 0.52 | 0.48 | 01-APR-06:00 | 1825.70 | 22.64 | 109.33 | 320.50 | 929.51 | 22.97 | 150.83 | 284.33 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:19 | 2071.31 | 23.40 | 129.50 | 359.00 | 877.24 | 22.68 | 159.00 | 321.33 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:10 | 1995.88 | 23.32 | 126.50 | 353.33 | 866.27 | 22.77 | 164.67 | 318.33 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:30 | 1880.79 | 23.06 | 123.67 | 348.33 | 828.03 | 22.45 | 167.33 | 312.83 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1928.76 | 22.77 | 114.17 | 341.50 | 860.57 | 22.16 | 173.50 | 307.50 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1926.22 | 23.59 | 107.00 | 311.50 | 986.87 | 23.89 | 183.67 | 285.50 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-06:49 | 1793.52 | 23.59 | 107.00 | 305.33 | 921.91 | 23.79 | 194.17 | 275.50 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1550.71 | 23.61 | 93.83 | 279.17 | 794.12 | 23.73 | 179.17 | 244.50 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1276.48 | 22.56 | 86.00 | 269.33 | 660.28 | 22.67 | 161.33 | 225.33 |
Annual Sum or Average | 4323.33 | 0.52 | 1770.70 | 23.20 | 1309.17 | 3735.83 | 841.75 | 23.01 | 2029.17 | 3310.50 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1276.48 | 22.56 | 86.00 | 263.33 | 660.28 | 22.16 | 150.83 | 225.33 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 2071.31 | 23.78 | 129.50 | 359.00 | 986.87 | 23.89 | 194.17 | 321.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-09:30 | 604.68 | 16.87 | 0.00 | 260.33 | 347.02 | 18.18 | 0.00 | 179.83 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-08:50 | 687.65 | 17.71 | 0.00 | 253.33 | 393.69 | 19.02 | 0.00 | 192.67 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:39 | 801.27 | 18.34 | 0.00 | 306.17 | 452.43 | 19.60 | 1.50 | 254.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 917.28 | 18.58 | 0.00 | 327.00 | 510.74 | 19.81 | 75.83 | 286.50 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:49 | 1080.04 | 19.60 | 3.50 | 368.50 | 592.15 | 20.81 | 186.00 | 333.50 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:40 | 1193.52 | 22.45 | 96.17 | 366.00 | 641.39 | 21.25 | 236.00 | 332.17 |
July | 405.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1154.75 | 20.50 | 41.00 | 358.50 | 625.87 | 21.84 | 252.83 | 327.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:00 | 1047.22 | 19.26 | 0.17 | 350.17 | 581.18 | 20.57 | 187.00 | 315.67 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 915.14 | 18.96 | 0.00 | 317.00 | 520.50 | 20.27 | 69.67 | 275.33 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:40 | 758.30 | 18.10 | 0.00 | 300.00 | 441.46 | 19.43 | 1.50 | 247.50 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-07:00 | 656.68 | 17.78 | 0.00 | 262.33 | 383.67 | 19.16 | 0.00 | 198.67 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:39 | 586.35 | 16.99 | 0.00 | 250.00 | 336.97 | 18.33 | 0.00 | 160.17 |
Annual Sum or Average | 4323.33 | 0.52 | 886.27 | 18.88 | 140.83 | 3719.33 | 495.31 | 19.95 | 1010.33 | 3104.00 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 586.35 | 16.87 | 0.00 | 250.00 | 336.97 | 18.18 | 0.00 | 160.17 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1193.52 | 22.45 | 96.17 | 368.50 | 641.39 | 21.84 | 252.83 | 333.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-09:30 | 1497.00 | 23.48 | 108.17 | 274.33 | 774.48 | 23.58 | 175.50 | 235.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:00 | 1468.10 | 22.28 | 76.33 | 262.33 | 736.75 | 22.43 | 159.00 | 223.83 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:00 | 1683.72 | 22.95 | 96.67 | 309.83 | 849.71 | 23.13 | 176.00 | 273.17 |
April | 375.00 | 0.52 | 0.48 | 01-APR-08:20 | 1701.17 | 19.62 | 55.00 | 324.67 | 878.74 | 19.49 | 116.83 | 288.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:40 | 1784.67 | 17.87 | 0.00 | 350.17 | 921.79 | 19.83 | 119.50 | 315.50 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:30 | 1898.82 | 18.06 | 0.00 | 345.83 | 974.28 | 20.01 | 130.00 | 313.00 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:40 | 1818.30 | 18.03 | 3.67 | 348.17 | 822.90 | 19.77 | 130.50 | 310.33 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1856.27 | 20.11 | 59.83 | 342.67 | 953.72 | 20.16 | 142.83 | 309.33 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:49 | 1797.39 | 22.21 | 87.17 | 318.17 | 920.63 | 22.58 | 174.33 | 287.17 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:00 | 1856.26 | 23.81 | 110.33 | 303.33 | 954.88 | 24.01 | 192.50 | 273.83 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-08:09 | 1614.74 | 24.02 | 99.50 | 278.33 | 828.72 | 24.12 | 180.83 | 245.33 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:39 | 1411.20 | 23.62 | 101.83 | 269.67 | 723.64 | 23.69 | 172.67 | 227.83 |
Annual Sum or Average | 4323.33 | 0.52 | 1712.02 | 21.14 | 798.50 | 3727.50 | 867.49 | 21.75 | 1870.50 | 3303.17 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1411.20 | 17.87 | 0.00 | 262.33 | 723.64 | 19.49 | 116.83 | 223.83 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 1898.82 | 24.02 | 110.33 | 350.17 | 974.28 | 24.12 | 192.50 | 315.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4207.91 | 33.84 | 310.17 | 293.00 | 1147.14 | 21.84 | 91.50 | 280.83 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-07:00 | 2187.98 | 22.15 | 140.67 | 274.83 | 1028.84 | 16.93 | 0.00 | 246.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1621.56 | 13.67 | 5.00 | 315.00 | 880.29 | 16.86 | 0.00 | 280.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 1273.61 | 13.01 | 0.00 | 323.50 | 705.34 | 16.29 | 0.00 | 289.83 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1088.63 | 13.09 | 0.00 | 350.00 | 623.76 | 16.45 | 0.00 | 310.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:00 | 1044.00 | 12.93 | 0.00 | 344.33 | 607.73 | 16.34 | 0.00 | 304.33 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:10 | 1095.74 | 12.76 | 0.00 | 345.17 | 630.14 | 16.11 | 0.00 | 308.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:10 | 1281.34 | 13.32 | 0.00 | 343.83 | 718.02 | 16.66 | 0.00 | 308.33 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1597.22 | 13.91 | 0.00 | 318.83 | 879.22 | 17.30 | 0.00 | 289.50 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:10 | 2125.39 | 15.99 | 34.50 | 317.50 | 1057.25 | 18.02 | 10.50 | 291.17 |
November | 318.83 | 0.49 | 0.48 | 01-NOV-07:10 | 3549.26 | 30.55 | 255.33 | 298.33 | 1191.68 | 21.59 | 76.33 | 283.67 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:19 | 4186.97 | 34.28 | 305.83 | 289.50 | 1220.80 | 23.26 | 113.00 | 276.50 |
Annual Sum or Average | 4323.33 | 0.51 | 2012.28 | 18.47 | 1051.50 | 3813.83 | 870.36 | 17.97 | 291.33 | 3469.83 | ||
Minimum of Months | 308.33 | 0.49 | 0.48 | 1044.00 | 12.76 | 0.00 | 274.83 | 607.73 | 16.11 | 0.00 | 246.67 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 4207.91 | 34.28 | 310.17 | 350.00 | 1220.80 | 23.26 | 113.00 | 310.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-07:00 | 1568.52 | 21.25 | 111.83 | 276.17 | 840.23 | 21.89 | 80.67 | 241.00 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-07:40 | 1697.93 | 20.78 | 102.33 | 263.67 | 753.19 | 20.04 | 47.17 | 231.00 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-07:00 | 1609.16 | 19.71 | 97.33 | 310.33 | 838.78 | 20.65 | 66.00 | 275.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-06:00 | 1848.78 | 19.73 | 109.33 | 321.17 | 973.06 | 20.70 | 79.67 | 288.67 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:19 | 2087.84 | 19.65 | 119.33 | 359.83 | 924.35 | 20.19 | 67.83 | 325.83 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:10 | 2026.25 | 20.36 | 125.83 | 354.50 | 912.39 | 20.26 | 66.67 | 321.83 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:30 | 1904.55 | 19.24 | 114.17 | 348.83 | 873.59 | 19.89 | 61.83 | 315.67 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1948.28 | 19.86 | 113.67 | 342.33 | 907.08 | 19.63 | 56.00 | 311.17 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1959.49 | 20.70 | 106.83 | 311.83 | 1033.19 | 21.66 | 77.33 | 288.17 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-06:49 | 1830.29 | 20.66 | 104.67 | 306.33 | 964.93 | 21.65 | 75.83 | 278.67 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1567.55 | 19.85 | 84.33 | 279.33 | 832.76 | 21.60 | 63.00 | 249.00 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1298.71 | 19.72 | 85.17 | 270.67 | 692.34 | 20.52 | 55.67 | 231.50 |
Annual Sum or Average | 4323.33 | 0.52 | 1796.81 | 20.10 | 1274.83 | 3745.00 | 883.97 | 20.69 | 797.67 | 3358.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1298.71 | 19.24 | 84.33 | 263.67 | 692.34 | 19.63 | 47.17 | 231.00 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 2087.84 | 21.25 | 125.83 | 359.83 | 1033.19 | 21.89 | 80.67 | 325.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-09:20 | 614.13 | 11.11 | 0.00 | 260.50 | 368.96 | 14.50 | 0.00 | 193.17 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:39 | 698.63 | 11.86 | 0.00 | 253.67 | 418.67 | 15.30 | 0.00 | 201.00 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:39 | 814.23 | 12.56 | 0.00 | 306.50 | 481.19 | 15.93 | 0.00 | 260.50 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 931.92 | 12.94 | 0.00 | 327.33 | 543.18 | 16.24 | 0.00 | 291.17 |
May | 405.33 | 0.50 | 0.48 | 01-MAY-06:40 | 1097.14 | 13.76 | 2.83 | 368.67 | 629.82 | 17.15 | 1.17 | 339.00 |
June | 403.50 | 0.50 | 0.48 | 01-JUN-06:19 | 1211.82 | 17.75 | 77.33 | 366.33 | 685.81 | 18.84 | 34.17 | 339.17 |
July | 405.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1172.02 | 14.89 | 26.83 | 359.00 | 665.11 | 18.16 | 27.17 | 331.00 |
August | 395.83 | 0.51 | 0.48 | 01-AUG-06:00 | 1063.49 | 13.49 | 0.00 | 350.50 | 617.87 | 16.89 | 0.00 | 319.50 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 929.92 | 13.46 | 0.00 | 317.33 | 553.57 | 16.82 | 0.00 | 280.67 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 770.75 | 12.66 | 0.00 | 300.67 | 469.62 | 16.06 | 0.00 | 253.50 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-07:49 | 667.01 | 12.11 | 0.00 | 263.17 | 408.02 | 15.62 | 0.00 | 209.67 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:30 | 595.17 | 11.06 | 0.00 | 251.00 | 358.19 | 14.54 | 0.00 | 174.33 |
Annual Sum or Average | 4323.33 | 0.52 | 900.17 | 13.27 | 107.00 | 3724.67 | 527.04 | 16.45 | 62.50 | 3192.67 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 595.17 | 11.06 | 0.00 | 251.00 | 358.19 | 14.50 | 0.00 | 174.33 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1211.82 | 17.75 | 77.33 | 368.67 | 685.81 | 18.84 | 34.17 | 339.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-09:30 | 1522.02 | 20.93 | 108.17 | 275.83 | 808.86 | 21.62 | 77.17 | 240.83 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:00 | 1498.38 | 19.17 | 76.33 | 263.00 | 774.95 | 20.04 | 48.33 | 227.83 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:50 | 1723.73 | 19.87 | 96.67 | 311.17 | 893.37 | 20.74 | 65.67 | 277.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-08:09 | 1722.67 | 15.98 | 55.00 | 325.67 | 921.42 | 16.37 | 0.00 | 292.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:30 | 1808.02 | 13.42 | 0.00 | 351.00 | 967.92 | 16.65 | 0.00 | 320.67 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-07:19 | 1930.46 | 13.59 | 0.00 | 346.50 | 1020.90 | 16.84 | 0.00 | 317.00 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:30 | 1844.22 | 13.63 | 3.67 | 349.33 | 868.43 | 16.63 | 0.00 | 314.83 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1874.15 | 16.45 | 59.83 | 342.83 | 1000.35 | 17.08 | 5.50 | 312.50 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:49 | 1823.98 | 19.10 | 86.83 | 318.00 | 966.96 | 20.14 | 57.33 | 289.67 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:49 | 1894.84 | 21.12 | 110.33 | 304.50 | 997.79 | 21.90 | 79.33 | 277.50 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-07:00 | 1642.75 | 21.30 | 98.67 | 279.00 | 867.81 | 22.05 | 69.00 | 249.50 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:30 | 1434.89 | 20.94 | 101.83 | 270.17 | 757.06 | 21.66 | 71.00 | 233.67 |
Annual Sum or Average | 4323.33 | 0.52 | 1739.59 | 17.70 | 797.33 | 3737.00 | 910.00 | 19.12 | 473.33 | 3354.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1434.89 | 13.42 | 0.00 | 263.00 | 757.06 | 16.37 | 0.00 | 227.83 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 1930.46 | 21.30 | 110.33 | 351.00 | 1020.90 | 22.05 | 79.33 | 320.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4210.55 | 33.83 | 310.17 | 293.00 | 1149.14 | 21.83 | 91.50 | 280.83 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-07:00 | 2190.99 | 22.13 | 140.67 | 274.83 | 1030.70 | 16.91 | 0.00 | 246.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1624.28 | 13.64 | 5.00 | 315.00 | 881.86 | 16.84 | 0.00 | 281.00 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 1275.69 | 12.98 | 0.00 | 323.50 | 706.54 | 16.28 | 0.00 | 289.83 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1090.23 | 13.06 | 0.00 | 350.17 | 624.74 | 16.43 | 0.00 | 310.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:00 | 1045.45 | 12.90 | 0.00 | 344.33 | 608.65 | 16.33 | 0.00 | 304.50 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:10 | 1097.32 | 12.73 | 0.00 | 345.33 | 631.12 | 16.09 | 0.00 | 308.50 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:10 | 1283.33 | 13.29 | 0.00 | 343.83 | 719.21 | 16.64 | 0.00 | 308.50 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1599.80 | 13.88 | 0.00 | 318.83 | 880.74 | 17.29 | 0.00 | 289.50 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:10 | 2128.39 | 15.96 | 34.50 | 317.50 | 1059.10 | 18.01 | 10.50 | 291.50 |
November | 318.83 | 0.49 | 0.48 | 01-NOV-07:10 | 3552.16 | 30.54 | 255.33 | 298.33 | 1193.74 | 21.58 | 76.33 | 283.67 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:19 | 4189.43 | 34.27 | 305.83 | 289.50 | 1222.82 | 23.25 | 113.00 | 276.50 |
Annual Sum or Average | 4323.33 | 0.51 | 2014.57 | 18.44 | 1051.50 | 3814.17 | 871.84 | 17.95 | 291.33 | 3471.00 | ||
Minimum of Months | 308.33 | 0.49 | 0.48 | 1045.45 | 12.73 | 0.00 | 274.83 | 608.65 | 16.09 | 0.00 | 246.67 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 4210.55 | 34.27 | 310.17 | 350.17 | 1222.82 | 23.25 | 113.00 | 310.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-07:00 | 1569.87 | 21.22 | 111.83 | 276.17 | 841.33 | 21.88 | 80.67 | 241.00 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-07:40 | 1699.51 | 20.75 | 102.33 | 263.67 | 754.37 | 20.03 | 47.17 | 231.33 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-07:00 | 1611.04 | 19.68 | 97.33 | 310.33 | 840.02 | 20.64 | 66.00 | 275.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-06:00 | 1850.67 | 19.70 | 109.33 | 321.17 | 974.33 | 20.68 | 79.67 | 288.67 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:19 | 2089.68 | 19.62 | 119.33 | 359.83 | 925.65 | 20.18 | 67.83 | 325.83 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:10 | 2028.13 | 20.33 | 125.83 | 354.50 | 913.70 | 20.24 | 66.67 | 321.83 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:30 | 1906.50 | 19.22 | 114.17 | 348.83 | 874.91 | 19.88 | 61.83 | 316.00 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1950.27 | 19.83 | 113.67 | 342.33 | 908.46 | 19.62 | 56.00 | 311.17 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1961.44 | 20.68 | 106.83 | 312.00 | 1034.60 | 21.65 | 77.33 | 288.17 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-06:49 | 1831.86 | 20.63 | 104.67 | 306.33 | 966.24 | 21.64 | 75.83 | 278.83 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1568.95 | 19.83 | 84.33 | 279.33 | 833.93 | 21.59 | 63.00 | 249.00 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1299.98 | 19.70 | 85.17 | 270.67 | 693.38 | 20.50 | 55.67 | 231.67 |
Annual Sum or Average | 4323.33 | 0.52 | 1798.54 | 20.07 | 1274.83 | 3745.17 | 885.23 | 20.67 | 797.67 | 3359.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1299.98 | 19.22 | 84.33 | 263.67 | 693.38 | 19.62 | 47.17 | 231.33 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 2089.68 | 21.22 | 125.83 | 359.83 | 1034.60 | 21.88 | 80.67 | 325.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-09:20 | 614.83 | 11.08 | 0.00 | 260.50 | 369.50 | 14.48 | 0.00 | 193.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:39 | 699.46 | 11.83 | 0.00 | 253.67 | 419.29 | 15.28 | 0.00 | 201.33 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:39 | 815.27 | 12.53 | 0.00 | 306.67 | 481.92 | 15.92 | 0.00 | 260.67 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 933.17 | 12.91 | 0.00 | 327.33 | 544.02 | 16.23 | 0.00 | 291.50 |
May | 405.33 | 0.50 | 0.48 | 01-MAY-06:40 | 1098.62 | 13.73 | 2.83 | 368.67 | 630.80 | 17.14 | 1.17 | 339.00 |
June | 403.50 | 0.50 | 0.48 | 01-JUN-06:19 | 1213.48 | 17.72 | 77.33 | 366.33 | 686.90 | 18.82 | 34.17 | 339.17 |
July | 405.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1173.65 | 14.86 | 26.83 | 359.00 | 666.18 | 18.15 | 27.17 | 331.17 |
August | 395.83 | 0.51 | 0.48 | 01-AUG-06:00 | 1064.89 | 13.46 | 0.00 | 350.50 | 618.83 | 16.87 | 0.00 | 319.67 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 931.04 | 13.43 | 0.00 | 317.33 | 554.39 | 16.80 | 0.00 | 280.83 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 771.59 | 12.63 | 0.00 | 300.67 | 470.28 | 16.05 | 0.00 | 253.50 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-07:49 | 667.71 | 12.08 | 0.00 | 263.17 | 408.59 | 15.61 | 0.00 | 209.83 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:30 | 595.84 | 11.03 | 0.00 | 251.00 | 358.72 | 14.52 | 0.00 | 174.83 |
Annual Sum or Average | 4323.33 | 0.52 | 901.32 | 13.24 | 107.00 | 3724.83 | 527.85 | 16.43 | 62.50 | 3194.83 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 595.84 | 11.03 | 0.00 | 251.00 | 358.72 | 14.48 | 0.00 | 174.83 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1213.48 | 17.72 | 77.33 | 368.67 | 686.90 | 18.82 | 34.17 | 339.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-09:30 | 1523.37 | 20.91 | 108.17 | 276.00 | 809.96 | 21.61 | 77.17 | 240.83 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:00 | 1499.99 | 19.14 | 76.33 | 263.00 | 776.15 | 20.03 | 48.33 | 227.83 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:50 | 1715.05 | 18.72 | 85.83 | 310.17 | 894.66 | 20.72 | 65.67 | 278.17 |
April | 375.00 | 0.52 | 0.48 | 01-APR-08:09 | 1724.59 | 15.95 | 55.00 | 326.00 | 922.72 | 16.36 | 0.00 | 292.67 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:30 | 1809.90 | 13.39 | 0.00 | 351.00 | 969.23 | 16.64 | 0.00 | 320.83 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-07:19 | 1932.40 | 13.56 | 0.00 | 346.83 | 1022.24 | 16.82 | 0.00 | 317.00 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:30 | 1846.21 | 13.60 | 3.67 | 349.33 | 869.78 | 16.61 | 0.00 | 314.83 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1876.18 | 16.42 | 59.83 | 343.00 | 1001.77 | 17.06 | 5.50 | 312.67 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:49 | 1826.01 | 19.07 | 86.83 | 318.17 | 968.39 | 20.13 | 57.33 | 289.83 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:49 | 1896.53 | 21.09 | 110.33 | 304.50 | 999.08 | 21.89 | 79.33 | 277.50 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-07:00 | 1644.13 | 21.27 | 98.67 | 279.17 | 868.98 | 22.04 | 69.00 | 249.50 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:30 | 1436.18 | 20.92 | 101.83 | 270.17 | 758.12 | 21.65 | 71.00 | 233.67 |
Annual Sum or Average | 4323.33 | 0.52 | 1740.49 | 17.58 | 786.50 | 3737.33 | 911.28 | 19.10 | 473.33 | 3355.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1436.18 | 13.39 | 0.00 | 263.00 | 758.12 | 16.36 | 0.00 | 227.83 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 1932.40 | 21.27 | 110.33 | 351.00 | 1022.24 | 22.04 | 79.33 | 320.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 324387.89 | 324.08 | 06-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13486.29 | 22.48 | 21-NOV-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 337874.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 324387.89 | 324.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 38888402.99 | 3616.54 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2999558.39 | 647.57 | 13-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 608362.17 | 240.91 | 18-DEC-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42496323.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38888402.99 | 3616.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 9009674.36 | 2001.05 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22464.06 | 37.44 | 13-FEB-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 9032138.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9009674.36 | 2001.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 667285.05 | 321.65 | 02-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 667285.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 667285.05 | 321.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 276377.74 | 148.91 | 20-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 276377.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 276377.74 | 148.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.651972E+11 | 0.624692E+11 | 225927.31 | 30-JAN-05:12 | 156303.73 | 0.56 |
February | 0.00 | 0.00 | 0.784781E+11 | 0.726475E+11 | 252274.18 | 09-FEB-05:12 | 161004.95 | 0.60 |
March | 0.00 | 0.00 | 0.118595E+12 | 0.110487E+12 | 213410.55 | 01-MAR-06:02 | 149100.18 | 0.70 |
April | 0.00 | 0.00 | 0.159900E+12 | 0.139984E+12 | 225489.81 | 03-APR-05:02 | 176186.61 | 0.84 |
May | 0.00 | 0.00 | 0.212938E+12 | 0.175015E+12 | 292801.46 | 30-MAY-05:03 | 179245.41 | 0.85 |
June | 0.00 | 0.00 | 0.274267E+12 | 0.195119E+12 | 301380.47 | 26-JUN-05:02 | 188894.60 | 0.89 |
July | 0.00 | 0.00 | 0.328088E+12 | 0.220575E+12 | 327065.80 | 30-JUL-16:22 | 161929.80 | 0.88 |
August | 0.00 | 0.00 | 0.375313E+12 | 0.255580E+12 | 327602.30 | 08-AUG-04:22 | 185586.36 | 0.89 |
September | 0.00 | 0.00 | 0.277106E+12 | 0.182094E+12 | 311350.84 | 10-SEP-16:21 | 150616.68 | 0.87 |
October | 0.00 | 0.00 | 0.222875E+12 | 0.165268E+12 | 294375.71 | 02-OCT-05:02 | 179931.82 | 0.84 |
November | 0.00 | 0.00 | 0.154149E+12 | 0.128767E+12 | 238049.33 | 02-NOV-04:22 | 154614.21 | 0.79 |
December | 0.00 | 0.00 | 0.104852E+12 | 0.933286E+11 | 205346.81 | 05-DEC-06:02 | 128139.60 | 0.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.237176E+13 | 0.180133E+13 | 0.78 | |||
Minimum of Months | 0.00 | 0.00 | 0.651972E+11 | 0.624692E+11 | 205346.81 | 128139.60 | 0.56 | |
Maximum of Months | 0.00 | 0.00 | 0.375313E+12 | 0.255580E+12 | 327602.30 | 188894.60 | 0.89 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.464965E+12 | 0.443006E+12 | 1708069.13 | 30-JAN-06:02 | 1105844.68 | 0.53 |
February | 0.00 | 0.00 | 0.572156E+12 | 0.524039E+12 | 1967881.49 | 09-FEB-06:03 | 1292678.44 | 0.56 |
March | 0.00 | 0.00 | 0.879033E+12 | 0.813624E+12 | 2091481.17 | 29-MAR-04:12 | 1295879.00 | 0.60 |
April | 0.00 | 0.00 | 0.120270E+13 | 0.104972E+13 | 2171283.39 | 20-APR-04:12 | 1354563.38 | 0.66 |
May | 0.00 | 0.00 | 0.198307E+13 | 0.161559E+13 | 2389777.67 | 29-MAY-15:12 | 1298046.26 | 0.81 |
June | 0.00 | 0.00 | 0.257284E+13 | 0.177402E+13 | 2947600.71 | 04-JUN-15:52 | 1542797.43 | 0.87 |
July | 0.00 | 0.00 | 0.307335E+13 | 0.197392E+13 | 3353179.96 | 30-JUL-16:22 | 1608491.07 | 0.87 |
August | 0.00 | 0.00 | 0.333305E+13 | 0.212224E+13 | 3242923.35 | 08-AUG-05:01 | 1666068.75 | 0.88 |
September | 0.00 | 0.00 | 0.264104E+13 | 0.168598E+13 | 3303784.78 | 10-SEP-16:52 | 1483074.12 | 0.84 |
October | 0.00 | 0.00 | 0.192896E+13 | 0.140598E+13 | 2906987.34 | 07-OCT-05:02 | 1621712.20 | 0.73 |
November | 0.00 | 0.00 | 0.119750E+13 | 0.979541E+12 | 2484144.44 | 08-NOV-06:02 | 1523301.01 | 0.62 |
December | 0.00 | 0.00 | 0.668091E+12 | 0.585479E+12 | 1959414.10 | 12-DEC-06:02 | 1373580.04 | 0.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.205168E+14 | 0.149731E+14 | 0.71 | |||
Minimum of Months | 0.00 | 0.00 | 0.464965E+12 | 0.443006E+12 | 1708069.13 | 1105844.68 | 0.53 | |
Maximum of Months | 0.00 | 0.00 | 0.333305E+13 | 0.212224E+13 | 3353179.96 | 1666068.75 | 0.88 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.421379E+11 | 0.399627E+11 | 165439.16 | 30-JAN-06:02 | 104544.66 | 0.53 |
February | 0.00 | 0.00 | 0.552846E+11 | 0.505000E+11 | 201933.07 | 06-FEB-06:03 | 134489.82 | 0.55 |
March | 0.00 | 0.00 | 0.886150E+11 | 0.820652E+11 | 197270.31 | 01-MAR-06:02 | 126117.90 | 0.59 |
April | 0.00 | 0.00 | 0.125291E+12 | 0.109884E+12 | 272656.97 | 30-APR-14:51 | 152665.39 | 0.65 |
May | 0.00 | 0.00 | 0.211513E+12 | 0.174606E+12 | 328448.27 | 30-MAY-04:12 | 193045.10 | 0.81 |
June | 0.00 | 0.00 | 0.273363E+12 | 0.193075E+12 | 330916.39 | 19-JUN-05:02 | 188898.78 | 0.87 |
July | 0.00 | 0.00 | 0.326336E+12 | 0.216191E+12 | 367282.66 | 30-JUL-16:22 | 182934.52 | 0.87 |
August | 0.00 | 0.00 | 0.351826E+12 | 0.230792E+12 | 364978.13 | 08-AUG-05:01 | 188707.84 | 0.88 |
September | 0.00 | 0.00 | 0.276407E+12 | 0.180525E+12 | 338121.08 | 10-SEP-15:52 | 171200.53 | 0.84 |
October | 0.00 | 0.00 | 0.199382E+12 | 0.146676E+12 | 326448.71 | 02-OCT-05:02 | 187932.03 | 0.73 |
November | 0.00 | 0.00 | 0.118858E+12 | 0.971751E+11 | 243066.27 | 01-NOV-04:11 | 152616.58 | 0.61 |
December | 0.00 | 0.00 | 0.626771E+11 | 0.546337E+11 | 210822.28 | 11-DEC-06:03 | 129895.44 | 0.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.213169E+13 | 0.157609E+13 | 0.71 | |||
Minimum of Months | 0.00 | 0.00 | 0.421379E+11 | 0.399627E+11 | 165439.16 | 104544.66 | 0.53 | |
Maximum of Months | 0.00 | 0.00 | 0.351826E+12 | 0.230792E+12 | 367282.66 | 193045.10 | 0.88 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.629367E+11 | 0.615589E+11 | 149790.86 | 30-JAN-05:12 | 92496.97 | 0.54 |
February | 0.00 | 0.00 | 0.603465E+11 | 0.584681E+11 | 153579.85 | 07-FEB-05:12 | 88466.69 | 0.55 |
March | 0.00 | 0.00 | 0.742216E+11 | 0.718839E+11 | 161288.87 | 30-MAR-04:12 | 86143.75 | 0.57 |
April | 0.00 | 0.00 | 0.787885E+11 | 0.742291E+11 | 181471.36 | 30-APR-16:40 | 102787.11 | 0.55 |
May | 0.00 | 0.00 | 0.103816E+12 | 0.913715E+11 | 217508.30 | 30-MAY-03:02 | 84387.73 | 0.61 |
June | 0.00 | 0.00 | 0.125317E+12 | 0.974899E+11 | 228628.13 | 18-JUN-22:00 | 89366.99 | 0.64 |
July | 0.00 | 0.00 | 0.149808E+12 | 0.105897E+12 | 234620.75 | 30-JUL-22:20 | 92622.25 | 0.62 |
August | 0.00 | 0.00 | 0.176606E+12 | 0.123259E+12 | 231345.31 | 20-AUG-21:31 | 89287.10 | 0.69 |
September | 0.00 | 0.00 | 0.136824E+12 | 0.991216E+11 | 239395.72 | 10-SEP-18:26 | 90289.66 | 0.64 |
October | 0.00 | 0.00 | 0.120332E+12 | 0.969576E+11 | 226528.18 | 01-OCT-19:30 | 92269.18 | 0.63 |
November | 0.00 | 0.00 | 0.966197E+11 | 0.842663E+11 | 169829.78 | 03-NOV-03:02 | 92374.49 | 0.61 |
December | 0.00 | 0.00 | 0.751853E+11 | 0.708384E+11 | 155914.51 | 06-DEC-05:11 | 87301.74 | 0.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.126080E+13 | 0.103534E+13 | 0.60 | |||
Minimum of Months | 0.00 | 0.00 | 0.603465E+11 | 0.584681E+11 | 149790.86 | 84387.73 | 0.54 | |
Maximum of Months | 0.00 | 0.00 | 0.176606E+12 | 0.123259E+12 | 239395.72 | 102787.11 | 0.69 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.339644E+12 | 0.328785E+12 | 137130.25 | 30-JAN-15:00 | 126089.23 | 0.00 |
February | 0.00 | 0.00 | 0.531444E+12 | 0.518447E+12 | 231326.11 | 07-FEB-16:10 | 219543.16 | 0.00 |
March | 0.00 | 0.00 | 0.833206E+12 | 0.821093E+12 | 402265.84 | 31-MAR-23:05 | 392023.95 | 0.00 |
April | 0.00 | 0.00 | 0.104090E+13 | 0.102843E+13 | 419476.59 | 10-APR-09:50 | 403270.35 | 0.00 |
May | 0.00 | 0.00 | 0.360181E+12 | 0.342108E+12 | 224407.54 | 31-MAY-23:03 | 213817.59 | 0.00 |
June | 0.00 | 0.00 | 0.597576E+12 | 0.569761E+12 | 322674.87 | 30-JUN-23:03 | 304682.96 | 0.00 |
July | 0.00 | 0.00 | 0.871066E+12 | 0.838103E+12 | 398439.66 | 31-JUL-24:00 | 386336.81 | 0.00 |
August | 0.00 | 0.00 | 0.108902E+13 | 0.105868E+13 | 421416.30 | 04-AUG-14:00 | 398362.67 | 0.00 |
September | 0.00 | 0.00 | 0.367461E+12 | 0.336754E+12 | 235796.57 | 30-SEP-23:05 | 213086.19 | 0.00 |
October | 0.00 | 0.00 | 0.612845E+12 | 0.588588E+12 | 312873.49 | 31-OCT-23:10 | 304495.13 | 0.00 |
November | 0.00 | 0.00 | 0.819101E+12 | 0.802275E+12 | 328346.44 | 01-NOV-15:00 | 312983.92 | 0.00 |
December | 0.00 | 0.00 | 0.108215E+13 | 0.106754E+13 | 412267.48 | 05-DEC-22:00 | 402098.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.854460E+13 | 0.830057E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.339644E+12 | 0.328785E+12 | 137130.25 | 126089.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108902E+13 | 0.106754E+13 | 421416.30 | 403270.35 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.551516E+10 | 0.517618E+10 | 2624.64 | 29-JAN-17:35 | 2361.35 | 0.00 |
February | 0.00 | 0.00 | 0.992132E+10 | 0.947093E+10 | 4722.88 | 07-FEB-16:10 | 4234.38 | 0.00 |
March | 0.00 | 0.00 | 0.162045E+11 | 0.157433E+11 | 8086.57 | 31-MAR-23:05 | 7614.44 | 0.00 |
April | 0.00 | 0.00 | 0.210031E+11 | 0.204204E+11 | 8727.72 | 30-APR-21:55 | 8283.55 | 0.00 |
May | 0.00 | 0.00 | 0.708486E+10 | 0.635248E+10 | 4633.16 | 31-MAY-23:03 | 4188.76 | 0.00 |
June | 0.00 | 0.00 | 0.123721E+11 | 0.111786E+11 | 6793.06 | 30-JUN-23:03 | 5995.75 | 0.00 |
July | 0.00 | 0.00 | 0.183288E+11 | 0.168523E+11 | 8518.00 | 31-JUL-24:00 | 7838.26 | 0.00 |
August | 0.00 | 0.00 | 0.226745E+11 | 0.211559E+11 | 8828.76 | 08-AUG-03:55 | 7975.58 | 0.00 |
September | 0.00 | 0.00 | 0.756274E+10 | 0.629374E+10 | 5074.05 | 30-SEP-23:05 | 4076.72 | 0.00 |
October | 0.00 | 0.00 | 0.123209E+11 | 0.112935E+11 | 6267.10 | 31-OCT-23:10 | 5890.70 | 0.00 |
November | 0.00 | 0.00 | 0.162031E+11 | 0.154801E+11 | 6860.66 | 01-NOV-16:00 | 6215.85 | 0.00 |
December | 0.00 | 0.00 | 0.212104E+11 | 0.206562E+11 | 8575.04 | 05-DEC-17:00 | 8007.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.170401E+12 | 0.160074E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.551516E+10 | 0.517618E+10 | 2624.64 | 2361.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.226745E+11 | 0.211559E+11 | 8828.76 | 8283.55 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.454724E+11 | 0.422358E+11 | 23476.49 | 30-JAN-15:00 | 19403.49 | 0.00 |
February | 0.00 | 0.00 | 0.901720E+11 | 0.857289E+11 | 44997.22 | 07-FEB-16:10 | 40146.04 | 0.00 |
March | 0.00 | 0.00 | 0.152657E+12 | 0.148072E+12 | 77708.23 | 31-MAR-23:05 | 72933.57 | 0.00 |
April | 0.00 | 0.00 | 0.199747E+12 | 0.193927E+12 | 82880.72 | 30-APR-17:55 | 77421.09 | 0.00 |
May | 0.00 | 0.00 | 0.669432E+11 | 0.597086E+11 | 44948.20 | 31-MAY-23:03 | 40465.71 | 0.00 |
June | 0.00 | 0.00 | 0.117891E+12 | 0.106026E+12 | 65838.35 | 30-JUN-23:03 | 57785.57 | 0.00 |
July | 0.00 | 0.00 | 0.174738E+12 | 0.160019E+12 | 81595.75 | 31-JUL-24:00 | 74841.97 | 0.00 |
August | 0.00 | 0.00 | 0.215187E+12 | 0.199897E+12 | 83763.74 | 08-AUG-04:53 | 75139.42 | 0.00 |
September | 0.00 | 0.00 | 0.712369E+11 | 0.586946E+11 | 49351.90 | 30-SEP-23:05 | 39209.49 | 0.00 |
October | 0.00 | 0.00 | 0.117082E+12 | 0.106876E+12 | 60581.82 | 31-OCT-23:10 | 56758.97 | 0.00 |
November | 0.00 | 0.00 | 0.153600E+12 | 0.146405E+12 | 65968.60 | 01-NOV-16:00 | 59538.87 | 0.00 |
December | 0.00 | 0.00 | 0.198465E+12 | 0.192937E+12 | 81735.52 | 05-DEC-17:00 | 76076.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160319E+13 | 0.150053E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.454724E+11 | 0.422358E+11 | 23476.49 | 19403.49 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.215187E+12 | 0.199897E+12 | 83763.74 | 77421.09 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.406309E+10 | 0.374875E+10 | 2387.53 | 29-JAN-17:35 | 2129.50 | 0.00 |
February | 0.00 | 0.00 | 0.875514E+10 | 0.831257E+10 | 4557.45 | 07-FEB-16:10 | 4071.33 | 0.00 |
March | 0.00 | 0.00 | 0.151531E+11 | 0.146949E+11 | 7725.16 | 31-MAR-23:05 | 7247.39 | 0.00 |
April | 0.00 | 0.00 | 0.200087E+11 | 0.194267E+11 | 8407.67 | 30-APR-17:55 | 7865.74 | 0.00 |
May | 0.00 | 0.00 | 0.684854E+10 | 0.612129E+10 | 4547.91 | 31-MAY-23:03 | 4100.94 | 0.00 |
June | 0.00 | 0.00 | 0.119506E+11 | 0.107616E+11 | 6603.63 | 30-JUN-23:03 | 5799.46 | 0.00 |
July | 0.00 | 0.00 | 0.177082E+11 | 0.162346E+11 | 8231.73 | 31-JUL-24:00 | 7555.28 | 0.00 |
August | 0.00 | 0.00 | 0.217255E+11 | 0.201965E+11 | 8447.88 | 20-AUG-21:04 | 7611.77 | 0.00 |
September | 0.00 | 0.00 | 0.727408E+10 | 0.601446E+10 | 4985.78 | 30-SEP-23:05 | 3982.52 | 0.00 |
October | 0.00 | 0.00 | 0.117850E+11 | 0.107634E+11 | 6055.23 | 31-OCT-23:10 | 5672.60 | 0.00 |
November | 0.00 | 0.00 | 0.152961E+11 | 0.145768E+11 | 6649.41 | 01-NOV-15:00 | 5984.86 | 0.00 |
December | 0.00 | 0.00 | 0.195495E+11 | 0.189972E+11 | 8199.30 | 05-DEC-17:00 | 7633.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160118E+12 | 0.149849E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.406309E+10 | 0.374875E+10 | 2387.53 | 2129.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.217255E+11 | 0.201965E+11 | 8447.88 | 7865.74 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3.34 | 2348.98 | 02-JAN-06:02 | 0.11 | 245.18 | 21-JAN-06:08 |
February | 0.06 | 48.07 | 13-FEB-07:00 | 0.04 | 132.73 | 13-FEB-06:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 4.64 | 21-NOV-08:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.04 | 49.24 | 18-DEC-06:50 |
Annual Sum or Average | 0.29 | 0.02 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 3.34 | 2348.98 | 0.11 | 245.18 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 241256.94 | 1259226.39 | 30-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 328143.32 | 1936742.49 | 08-FEB-15:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 457735.82 | 2033204.10 | 29-MAR-12:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 648608.88 | 2248639.52 | 27-APR-08:55 | 0.00 | 0.00 | 01-APR-00:05 |
May | 982599.44 | 2917032.35 | 30-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1284695.59 | 3466959.21 | 09-JUN-05:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1486311.20 | 4247724.45 | 20-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1608017.52 | 4112278.83 | 05-AUG-17:42 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1317564.93 | 3983241.45 | 08-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 962932.10 | 3143961.29 | 02-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 646972.40 | 2598945.81 | 08-NOV-06:02 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 353568.05 | 2002195.26 | 06-DEC-15:05 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 862981.70 | 0.00 | ||||
Minimum of Months | 241256.94 | 1259226.39 | 0.00 | 0.00 | ||
Maximum of Months | 1608017.52 | 4247724.45 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 239012.55 | 2868496.52 | 30-JAN-06:02 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 325706.67 | 3959160.83 | 09-FEB-06:03 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 454885.12 | 3910098.01 | 29-MAR-05:03 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 645537.11 | 4075973.71 | 12-APR-05:02 | 0.00 | 0.00 | 01-APR-00:05 |
May | 978589.34 | 4519219.57 | 24-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1278703.03 | 4636637.55 | 20-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1475529.46 | 4944784.75 | 25-JUL-03:12 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1600796.61 | 4940901.92 | 19-AUG-03:01 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1310940.87 | 4723931.97 | 05-SEP-03:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 957779.49 | 4458977.76 | 06-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 643040.09 | 4320987.18 | 01-NOV-04:11 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 350616.93 | 3813898.80 | 12-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 858191.55 | 0.00 | ||||
Minimum of Months | 239012.55 | 2868496.52 | 0.00 | 0.00 | ||
Maximum of Months | 1600796.61 | 4944784.75 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 353621.79 | 811899.50 | 23-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 632442.54 | 1299278.79 | 06-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 981394.34 | 1856041.95 | 27-MAR-11:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1399572.88 | 2265256.02 | 28-APR-12:00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1013132.24 | 1606153.62 | 31-MAY-19:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1350676.93 | 1931344.88 | 12-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1722087.46 | 2355652.37 | 21-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1931577.06 | 2513549.41 | 16-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1094589.62 | 1569740.40 | 04-SEP-14:40 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1147789.37 | 1619085.03 | 04-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 1132958.04 | 1616425.80 | 05-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1085475.18 | 1591054.70 | 10-DEC-12:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1157067.71 | 0.00 | ||||
Minimum of Months | 353621.79 | 811899.50 | 0.00 | 0.00 | ||
Maximum of Months | 1931577.06 | 2513549.41 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 11546.12 | 37766.61 | 13-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11321.05 | 37352.10 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11194.82 | 35673.09 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:05 | 9653.10 | 32359.67 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 9004.47 | 29207.27 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 8485.50 | 26263.30 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 7725.08 | 24935.30 | 31-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 8629.99 | 26749.83 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8903.35 | 29621.87 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 9815.09 | 33198.38 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10840.79 | 36038.98 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 11114.68 | 37566.59 | 29-DEC-12:50 |
Annual Sum or Average | 0.00 | 9844.96 | ||||
Minimum of Months | 0.00 | 0.00 | 7725.08 | 24935.30 | ||
Maximum of Months | 0.00 | 0.00 | 11546.12 | 37766.61 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 293231.71 | 2244530.26 | 30-JAN-14:00 | 425.87 | 98234.34 | 21-JAN-05:40 |
February | 419206.07 | 4112576.77 | 07-FEB-16:00 | 180.57 | 58141.62 | 15-FEB-05:40 |
March | 609705.34 | 3942363.49 | 29-MAR-10:05 | 553.35 | 73164.53 | 23-MAR-03:20 |
April | 1060036.90 | 4775162.22 | 10-APR-12:05 | 433.04 | 65558.89 | 26-APR-04:10 |
May | 2242926.89 | 7478631.49 | 31-MAY-16:00 | 4.39 | 7271.54 | 07-MAY-04:35 |
June | 3759151.77 | 7699838.21 | 12-JUN-14:40 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 4580879.33 | 8396168.15 | 19-JUL-15:10 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 5067513.96 | 8406014.69 | 03-AUG-14:40 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 4082611.33 | 8098612.67 | 07-SEP-14:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 2412374.48 | 7398494.20 | 01-OCT-15:52 | 28.07 | 33644.99 | 20-OCT-04:10 |
November | 1152387.51 | 6764171.90 | 01-NOV-14:05 | 151.60 | 39152.50 | 05-NOV-06:20 |
December | 478228.05 | 4500068.96 | 05-DEC-13:05 | 374.61 | 69597.17 | 18-DEC-00:40 |
Annual Sum or Average | 2190668.62 | 179.65 | ||||
Minimum of Months | 293231.71 | 2244530.26 | 0.00 | 0.00 | ||
Maximum of Months | 5067513.96 | 8406014.69 | 553.35 | 98234.34 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146732E+11 | 0.84 | 8967.88 | 01-JAN-00:05 | 1.38 |
February | 0.129622E+11 | 0.82 | 8967.88 | 01-FEB-05:12 | 1.38 |
March | 0.145123E+11 | 0.83 | 8967.88 | 01-MAR-04:02 | 1.38 |
April | 0.135921E+11 | 0.80 | 8967.88 | 01-APR-04:12 | 1.38 |
May | 0.149528E+11 | 0.86 | 8967.88 | 01-MAY-00:10 | 1.36 |
June | 0.149961E+11 | 0.88 | 8967.88 | 01-JUN-03:03 | 1.37 |
July | 0.151934E+11 | 0.87 | 8967.88 | 01-JUL-03:02 | 1.38 |
August | 0.166197E+11 | 0.95 | 8967.88 | 01-AUG-03:02 | 1.38 |
September | 0.151857E+11 | 0.90 | 8967.88 | 01-SEP-03:02 | 1.38 |
October | 0.157410E+11 | 0.90 | 8967.88 | 01-OCT-11:32 | 1.38 |
November | 0.148921E+11 | 0.88 | 8967.88 | 01-NOV-03:02 | 1.38 |
December | 0.148607E+11 | 0.85 | 8967.88 | 01-DEC-05:12 | 1.38 |
Annual Sum or Average | 0.178181E+12 | 0.87 | |||
Minimum of Months | 0.129622E+11 | 0.80 | 8967.88 | 1.36 | |
Maximum of Months | 0.166197E+11 | 0.95 | 8967.88 | 1.38 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.530626E+10 | 0.36 | 20954.51 | 30-JAN-05:12 | 1.73 |
February | 0.602779E+10 | 0.41 | 21407.05 | 08-FEB-05:12 | 1.76 |
March | 0.888120E+10 | 0.52 | 21407.05 | 28-MAR-05:02 | 1.77 |
April | 0.108776E+11 | 0.64 | 21407.05 | 17-APR-05:02 | 1.76 |
May | 0.119078E+11 | 0.65 | 21407.05 | 01-MAY-04:21 | 1.76 |
June | 0.139512E+11 | 0.72 | 21407.05 | 01-JUN-05:03 | 1.75 |
July | 0.162741E+11 | 0.76 | 21407.05 | 03-JUL-05:02 | 1.76 |
August | 0.218640E+11 | 0.89 | 21407.05 | 01-AUG-04:22 | 1.76 |
September | 0.125611E+11 | 0.68 | 21407.05 | 01-SEP-05:02 | 1.75 |
October | 0.119259E+11 | 0.65 | 21407.05 | 02-OCT-03:12 | 1.76 |
November | 0.101658E+11 | 0.59 | 21407.05 | 01-NOV-04:11 | 1.76 |
December | 0.798516E+10 | 0.48 | 21407.05 | 12-DEC-06:02 | 1.76 |
Annual Sum or Average | 0.137728E+12 | 0.61 | |||
Minimum of Months | 0.530626E+10 | 0.36 | 20954.51 | 1.73 | |
Maximum of Months | 0.218640E+11 | 0.89 | 21407.05 | 1.77 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.352849E+11 | 0.31 | 134329.72 | 30-JAN-06:02 | 1.36 |
February | 0.391860E+11 | 0.34 | 202513.99 | 06-FEB-06:03 | 1.76 |
March | 0.587043E+11 | 0.40 | 202513.99 | 02-MAR-06:02 | 1.76 |
April | 0.701166E+11 | 0.46 | 202513.99 | 03-APR-05:02 | 1.76 |
May | 0.104632E+12 | 0.60 | 202513.99 | 01-MAY-04:12 | 1.76 |
June | 0.114617E+12 | 0.66 | 202513.99 | 03-JUN-05:02 | 1.76 |
July | 0.123758E+12 | 0.68 | 202513.99 | 03-JUL-05:02 | 1.76 |
August | 0.142765E+12 | 0.73 | 202513.99 | 01-AUG-05:02 | 1.76 |
September | 0.108501E+12 | 0.63 | 202513.99 | 01-SEP-05:02 | 1.75 |
October | 0.935151E+11 | 0.54 | 202513.99 | 02-OCT-05:02 | 1.76 |
November | 0.691679E+11 | 0.44 | 202513.99 | 01-NOV-04:11 | 1.76 |
December | 0.429154E+11 | 0.34 | 197959.60 | 12-DEC-06:02 | 1.73 |
Annual Sum or Average | 0.100316E+13 | 0.51 | |||
Minimum of Months | 0.352849E+11 | 0.31 | 134329.72 | 1.36 | |
Maximum of Months | 0.142765E+12 | 0.73 | 202513.99 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.312872E+10 | 0.31 | 10841.07 | 30-JAN-06:02 | 1.09 |
February | 0.353336E+10 | 0.32 | 16515.48 | 06-FEB-06:03 | 1.41 |
March | 0.543534E+10 | 0.37 | 23202.31 | 28-MAR-05:02 | 1.75 |
April | 0.679851E+10 | 0.44 | 23228.16 | 03-APR-05:02 | 1.75 |
May | 0.107398E+11 | 0.59 | 23228.16 | 01-MAY-04:12 | 1.75 |
June | 0.119598E+11 | 0.65 | 23228.16 | 06-JUN-05:02 | 1.74 |
July | 0.131525E+11 | 0.67 | 23228.16 | 03-JUL-05:02 | 1.75 |
August | 0.148157E+11 | 0.71 | 23228.16 | 01-AUG-05:02 | 1.75 |
September | 0.109984E+11 | 0.61 | 23228.16 | 01-SEP-05:02 | 1.74 |
October | 0.904403E+10 | 0.51 | 23228.16 | 02-OCT-05:02 | 1.75 |
November | 0.613746E+10 | 0.40 | 23155.57 | 20-NOV-06:02 | 1.74 |
December | 0.374581E+10 | 0.32 | 12735.12 | 11-DEC-06:03 | 1.20 |
Annual Sum or Average | 0.994894E+11 | 0.49 | |||
Minimum of Months | 0.312872E+10 | 0.31 | 10841.07 | 1.09 | |
Maximum of Months | 0.148157E+11 | 0.71 | 23228.16 | 1.75 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.949070E+11 | 1.35 | 35434.20 | 01-JAN-00:05 | 1.35 |
February | 0.857224E+11 | 1.35 | 35434.20 | 01-FEB-00:20 | 1.35 |
March | 0.949070E+11 | 1.35 | 35434.20 | 01-MAR-00:10 | 1.35 |
April | 0.918454E+11 | 1.35 | 35434.20 | 01-APR-00:05 | 1.35 |
May | 0.949070E+11 | 1.35 | 35434.20 | 01-MAY-00:05 | 1.35 |
June | 0.918454E+11 | 1.35 | 35434.20 | 01-JUN-00:10 | 1.35 |
July | 0.949070E+11 | 1.35 | 35434.20 | 01-JUL-00:15 | 1.35 |
August | 0.949070E+11 | 1.35 | 35434.20 | 01-AUG-00:03 | 1.35 |
September | 0.918454E+11 | 1.35 | 35434.20 | 01-SEP-00:10 | 1.35 |
October | 0.949070E+11 | 1.35 | 35434.20 | 01-OCT-00:05 | 1.35 |
November | 0.918454E+11 | 1.35 | 35434.20 | 01-NOV-00:05 | 1.35 |
December | 0.949070E+11 | 1.35 | 35434.20 | 01-DEC-00:10 | 1.35 |
Annual Sum or Average | 0.111745E+13 | 1.35 | |||
Minimum of Months | 0.857224E+11 | 1.35 | 35434.20 | 1.35 | |
Maximum of Months | 0.949070E+11 | 1.35 | 35434.20 | 1.35 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140330E+10 | 0.91 | 523.93 | 01-JAN-00:05 | 0.92 |
February | 0.126750E+10 | 0.91 | 523.93 | 01-FEB-00:10 | 0.91 |
March | 0.140330E+10 | 0.91 | 523.93 | 01-MAR-00:10 | 0.91 |
April | 0.135803E+10 | 0.91 | 523.93 | 01-APR-00:05 | 0.91 |
May | 0.140330E+10 | 0.91 | 523.93 | 01-MAY-00:05 | 0.91 |
June | 0.135803E+10 | 0.91 | 523.93 | 01-JUN-00:10 | 0.91 |
July | 0.140330E+10 | 0.91 | 523.93 | 01-JUL-00:05 | 0.91 |
August | 0.140330E+10 | 0.91 | 523.93 | 01-AUG-00:03 | 0.91 |
September | 0.135803E+10 | 0.91 | 523.93 | 01-SEP-00:05 | 0.91 |
October | 0.140330E+10 | 0.91 | 523.93 | 01-OCT-00:05 | 0.91 |
November | 0.135803E+10 | 0.91 | 523.93 | 01-NOV-00:05 | 0.91 |
December | 0.140330E+10 | 0.91 | 523.93 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.165227E+11 | 0.91 | |||
Minimum of Months | 0.126750E+10 | 0.91 | 523.93 | 0.91 | |
Maximum of Months | 0.140330E+10 | 0.91 | 523.93 | 0.92 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133920E+11 | 0.91 | 5000.01 | 01-JAN-00:05 | 0.91 |
February | 0.120960E+11 | 0.91 | 5000.01 | 01-FEB-00:10 | 0.91 |
March | 0.133920E+11 | 0.91 | 5000.01 | 01-MAR-00:10 | 0.91 |
April | 0.129600E+11 | 0.91 | 5000.01 | 01-APR-00:05 | 0.91 |
May | 0.133920E+11 | 0.91 | 5000.01 | 01-MAY-00:05 | 0.91 |
June | 0.129600E+11 | 0.91 | 5000.01 | 01-JUN-00:10 | 0.91 |
July | 0.133920E+11 | 0.91 | 5000.01 | 01-JUL-00:05 | 0.91 |
August | 0.133920E+11 | 0.91 | 5000.01 | 01-AUG-00:03 | 0.91 |
September | 0.129600E+11 | 0.91 | 5000.01 | 01-SEP-00:05 | 0.91 |
October | 0.133920E+11 | 0.91 | 5000.01 | 01-OCT-00:05 | 0.91 |
November | 0.129600E+11 | 0.91 | 5000.01 | 01-NOV-00:05 | 0.91 |
December | 0.133920E+11 | 0.91 | 5000.01 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.157680E+12 | 0.91 | |||
Minimum of Months | 0.120960E+11 | 0.91 | 5000.01 | 0.91 | |
Maximum of Months | 0.133920E+11 | 0.91 | 5000.01 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135142E+10 | 0.91 | 504.56 | 01-JAN-00:05 | 0.91 |
February | 0.122064E+10 | 0.91 | 504.56 | 01-FEB-00:10 | 0.91 |
March | 0.135142E+10 | 0.91 | 504.56 | 01-MAR-00:10 | 0.91 |
April | 0.130783E+10 | 0.91 | 504.56 | 01-APR-00:05 | 0.91 |
May | 0.135142E+10 | 0.91 | 504.56 | 01-MAY-00:05 | 0.91 |
June | 0.130783E+10 | 0.91 | 504.56 | 01-JUN-00:10 | 0.91 |
July | 0.135142E+10 | 0.91 | 504.56 | 01-JUL-00:05 | 0.91 |
August | 0.135142E+10 | 0.91 | 504.56 | 01-AUG-00:03 | 0.91 |
September | 0.130783E+10 | 0.91 | 504.56 | 01-SEP-00:05 | 0.91 |
October | 0.135142E+10 | 0.91 | 504.56 | 01-OCT-00:05 | 0.91 |
November | 0.130783E+10 | 0.91 | 504.56 | 01-NOV-00:05 | 0.91 |
December | 0.135142E+10 | 0.91 | 504.56 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.159119E+11 | 0.91 | |||
Minimum of Months | 0.122064E+10 | 0.91 | 504.56 | 0.91 | |
Maximum of Months | 0.135142E+10 | 0.91 | 504.56 | 0.91 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 314506.97 | 285886.84 | 50.51 | 02-JAN-06:02 | 45.91 | 45.91 | 59.94 | 0.05 |
February | 18168.41 | 16515.09 | 3.98 | 13-FEB-06:10 | 3.62 | 3.62 | 52.18 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 51.76 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 51.76 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 51.76 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 51.76 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 51.76 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 51.76 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 51.76 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 51.76 | 0.00 |
November | 79.27 | 72.06 | 0.13 | 21-NOV-08:40 | 0.12 | 0.12 | 51.75 | 0.00 |
December | 3459.90 | 3145.05 | 1.40 | 18-DEC-06:50 | 1.27 | 1.27 | 51.74 | 0.00 |
Annual Sum or Average | 336214.55 | 305619.03 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.74 | 0.00 | |
Maximum of Months | 314506.97 | 285886.84 | 50.51 | 45.91 | 45.91 | 59.94 | 0.05 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.226578E+09 | 0.205959E+09 | 7041.76 | 30-JAN-06:02 | 6400.96 | 6400.96 | 8.55 | 64.11 |
February | 0.330599E+09 | 0.300514E+09 | 13514.10 | 06-FEB-06:03 | 12284.32 | 12284.32 | 10.29 | 83.10 |
March | 0.681355E+09 | 0.619352E+09 | 13514.10 | 24-MAR-05:03 | 12284.32 | 12284.32 | 10.18 | 83.10 |
April | 0.100712E+10 | 0.915476E+09 | 13514.10 | 08-APR-05:02 | 12284.32 | 12284.32 | 9.91 | 83.10 |
May | 0.167431E+10 | 0.152194E+10 | 13514.10 | 01-MAY-05:02 | 12284.32 | 12284.32 | 9.76 | 83.10 |
June | 0.218521E+10 | 0.198636E+10 | 13514.10 | 06-JUN-05:02 | 12284.32 | 12284.32 | 10.20 | 83.10 |
July | 0.296710E+10 | 0.269709E+10 | 13514.10 | 03-JUL-05:03 | 12284.32 | 12284.32 | 10.94 | 83.10 |
August | 0.352060E+10 | 0.320023E+10 | 13514.10 | 01-AUG-05:02 | 12284.32 | 12284.32 | 6.88 | 83.10 |
September | 0.231040E+10 | 0.210015E+10 | 13514.10 | 01-SEP-05:02 | 12284.32 | 12284.32 | 10.05 | 83.10 |
October | 0.159240E+10 | 0.144750E+10 | 13514.10 | 03-OCT-05:02 | 12284.32 | 12284.32 | 10.24 | 83.10 |
November | 0.963831E+09 | 0.876123E+09 | 13514.10 | 01-NOV-04:11 | 12284.32 | 12284.32 | 9.65 | 83.10 |
December | 0.383340E+09 | 0.348456E+09 | 13315.58 | 12-DEC-06:02 | 12103.86 | 12103.86 | 9.82 | 82.60 |
Annual Sum or Average | 0.178428E+11 | 0.162191E+11 | ||||||
Minimum of Months | 0.226578E+09 | 0.205959E+09 | 7041.76 | 6400.96 | 6400.96 | 6.88 | 64.11 | |
Maximum of Months | 0.352060E+10 | 0.320023E+10 | 13514.10 | 12284.32 | 12284.32 | 10.94 | 83.10 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.750715E+10 | 0.682400E+10 | 4650.70 | 01-JAN-00:05 | 4227.48 | 4227.48 | 6.88 | 41.55 |
February | 0.703278E+10 | 0.639280E+10 | 4650.70 | 01-FEB-05:12 | 4227.48 | 4227.48 | 8.81 | 41.55 |
March | 0.935348E+10 | 0.850231E+10 | 4650.70 | 01-MAR-04:02 | 4227.48 | 4227.48 | 8.62 | 41.55 |
April | 0.109182E+11 | 0.992464E+10 | 4650.70 | 01-APR-00:05 | 4227.48 | 4227.48 | 6.95 | 41.55 |
May | 0.115154E+11 | 0.104675E+11 | 4650.70 | 01-MAY-00:05 | 4227.48 | 4227.48 | 10.97 | 41.55 |
June | 0.115705E+11 | 0.105176E+11 | 4650.70 | 01-JUN-00:10 | 4227.48 | 4227.48 | 10.94 | 41.55 |
July | 0.116002E+11 | 0.105445E+11 | 4650.70 | 01-JUL-00:05 | 4227.48 | 4227.48 | 9.40 | 41.55 |
August | 0.120847E+11 | 0.109850E+11 | 4650.70 | 01-AUG-00:03 | 4227.48 | 4227.48 | 12.70 | 41.55 |
September | 0.114259E+11 | 0.103862E+11 | 4650.70 | 01-SEP-00:05 | 4227.48 | 4227.48 | 9.08 | 41.55 |
October | 0.115329E+11 | 0.104834E+11 | 4650.70 | 01-OCT-00:05 | 4227.48 | 4227.48 | 12.91 | 41.55 |
November | 0.100711E+11 | 0.915461E+10 | 4650.70 | 01-NOV-00:05 | 4227.48 | 4227.48 | 6.98 | 41.55 |
December | 0.908257E+10 | 0.825606E+10 | 4650.70 | 01-DEC-05:12 | 4227.48 | 4227.48 | 10.33 | 41.55 |
Annual Sum or Average | 0.123695E+12 | 0.112438E+12 | ||||||
Minimum of Months | 0.703278E+10 | 0.639280E+10 | 4650.70 | 4227.48 | 4227.48 | 6.88 | 41.55 | |
Maximum of Months | 0.120847E+11 | 0.109850E+11 | 4650.70 | 4227.48 | 4227.48 | 12.91 | 41.55 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.88 | 0.00 |
February | 0.170913E+09 | 0.155360E+09 | 4650.70 | 06-FEB-06:05 | 4227.48 | 4227.48 | 15.60 | 20.78 |
March | 0.633425E+09 | 0.575783E+09 | 4650.70 | 01-MAR-13:05 | 4227.48 | 4227.48 | 11.32 | 41.55 |
April | 0.145395E+10 | 0.132164E+10 | 4650.70 | 03-APR-07:20 | 4227.48 | 4227.48 | 14.92 | 20.78 |
May | 0.406459E+10 | 0.369472E+10 | 4650.70 | 01-MAY-04:13 | 4227.48 | 4227.48 | 15.35 | 20.78 |
June | 0.607502E+10 | 0.552219E+10 | 4650.70 | 01-JUN-07:20 | 4227.48 | 4227.48 | 14.60 | 20.78 |
July | 0.749221E+10 | 0.681042E+10 | 4650.70 | 01-JUL-03:02 | 4227.48 | 4227.48 | 16.10 | 20.78 |
August | 0.789821E+10 | 0.717947E+10 | 4650.70 | 01-AUG-01:03 | 4227.48 | 4227.48 | 11.57 | 41.55 |
September | 0.617833E+10 | 0.561610E+10 | 4650.70 | 01-SEP-05:03 | 4227.48 | 4227.48 | 16.83 | 20.78 |
October | 0.403438E+10 | 0.366726E+10 | 4650.70 | 01-OCT-15:52 | 4227.48 | 4227.48 | 12.77 | 41.55 |
November | 0.217286E+10 | 0.197513E+10 | 4650.70 | 01-NOV-04:13 | 4227.48 | 4227.48 | 15.64 | 20.78 |
December | 0.238581E+09 | 0.216870E+09 | 4650.70 | 04-DEC-10:40 | 4227.48 | 4227.48 | 14.84 | 20.78 |
Annual Sum or Average | 0.404125E+11 | 0.367349E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 | 0.00 | |
Maximum of Months | 0.789821E+10 | 0.717947E+10 | 4650.70 | 4227.48 | 4227.48 | 16.83 | 41.55 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.932648E+10 | 0.847777E+10 | 3482.11 | 01-JAN-00:05 | 3165.24 | 3165.24 | 21.85 | 14.69 |
February | 0.842391E+10 | 0.765734E+10 | 3482.11 | 01-FEB-00:10 | 3165.24 | 3165.24 | 25.78 | 14.69 |
March | 0.932648E+10 | 0.847777E+10 | 3482.11 | 01-MAR-00:10 | 3165.24 | 3165.24 | 36.01 | 14.69 |
April | 0.902562E+10 | 0.820429E+10 | 3482.11 | 01-APR-00:05 | 3165.24 | 3165.24 | 40.35 | 14.69 |
May | 0.932648E+10 | 0.847777E+10 | 3482.11 | 01-MAY-00:05 | 3165.24 | 3165.24 | 34.07 | 14.69 |
June | 0.902562E+10 | 0.820429E+10 | 3482.11 | 01-JUN-00:10 | 3165.24 | 3165.24 | 43.47 | 14.69 |
July | 0.932648E+10 | 0.847777E+10 | 3482.11 | 01-JUL-00:05 | 3165.24 | 3165.24 | 47.15 | 14.69 |
August | 0.932648E+10 | 0.847777E+10 | 3482.11 | 01-AUG-00:03 | 3165.24 | 3165.24 | 52.59 | 14.69 |
September | 0.902562E+10 | 0.820429E+10 | 3482.11 | 01-SEP-00:05 | 3165.24 | 3165.24 | 39.78 | 14.69 |
October | 0.932648E+10 | 0.847777E+10 | 3482.11 | 01-OCT-00:05 | 3165.24 | 3165.24 | 39.91 | 14.69 |
November | 0.902562E+10 | 0.820429E+10 | 3482.11 | 01-NOV-00:05 | 3165.24 | 3165.24 | 41.87 | 14.69 |
December | 0.932648E+10 | 0.847777E+10 | 3482.11 | 01-DEC-00:10 | 3165.24 | 3165.24 | 38.26 | 14.69 |
Annual Sum or Average | 0.109812E+12 | 0.998189E+11 | ||||||
Minimum of Months | 0.842391E+10 | 0.765734E+10 | 3482.11 | 3165.24 | 3165.24 | 21.85 | 14.69 | |
Maximum of Months | 0.932648E+10 | 0.847777E+10 | 3482.11 | 3165.24 | 3165.24 | 52.59 | 14.69 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 56.33 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 56.38 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 56.72 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 57.71 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 56.83 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 58.19 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.24 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 56.85 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 57.90 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:03 | 16.86 | 16.86 | 56.92 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 56.64 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 56.93 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.33 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 58.19 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.285596E+11 | 0.259607E+11 | 17774.37 | 30-JAN-14:00 | 16156.91 | 16156.91 | 28.52 | 72.33 |
February | 0.271383E+11 | 0.246687E+11 | 35530.17 | 07-FEB-16:00 | 32296.92 | 32296.92 | 27.90 | 144.67 |
March | 0.372082E+11 | 0.338223E+11 | 35521.77 | 29-MAR-10:05 | 32289.29 | 32289.29 | 27.62 | 144.67 |
April | 0.458707E+11 | 0.416964E+11 | 35557.22 | 10-APR-12:05 | 32321.51 | 32321.51 | 29.00 | 144.67 |
May | 0.577556E+11 | 0.524999E+11 | 35557.22 | 03-MAY-13:00 | 32321.51 | 32321.51 | 29.07 | 144.67 |
June | 0.658472E+11 | 0.598551E+11 | 35557.22 | 01-JUN-15:50 | 32321.51 | 32321.51 | 28.88 | 144.67 |
July | 0.707665E+11 | 0.643267E+11 | 35557.22 | 01-JUL-03:02 | 32321.51 | 32321.51 | 30.34 | 144.67 |
August | 0.745576E+11 | 0.677728E+11 | 35557.22 | 01-AUG-01:03 | 32321.51 | 32321.51 | 32.18 | 144.67 |
September | 0.658378E+11 | 0.598465E+11 | 35557.22 | 01-SEP-05:05 | 32321.51 | 32321.51 | 29.75 | 144.67 |
October | 0.577574E+11 | 0.525015E+11 | 35557.22 | 01-OCT-15:52 | 32321.51 | 32321.51 | 33.33 | 144.67 |
November | 0.442208E+11 | 0.401967E+11 | 35557.22 | 01-NOV-09:30 | 32321.51 | 32321.51 | 28.93 | 144.67 |
December | 0.351138E+11 | 0.319185E+11 | 35549.29 | 05-DEC-13:05 | 32314.31 | 32314.31 | 28.54 | 144.67 |
Annual Sum or Average | 0.610634E+12 | 0.555066E+12 | ||||||
Minimum of Months | 0.271383E+11 | 0.246687E+11 | 17774.37 | 16156.91 | 16156.91 | 27.62 | 72.33 | |
Maximum of Months | 0.745576E+11 | 0.677728E+11 | 35557.22 | 32321.51 | 32321.51 | 33.33 | 144.67 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3.34 | 2348.98 | 02-JAN-06:02 | 59.94 | 59.94 | 0.11 | 245.18 | 21-JAN-06:08 |
February | 0.06 | 48.07 | 13-FEB-07:00 | 51.99 | 51.99 | 0.04 | 132.73 | 13-FEB-06:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 51.76 | 51.76 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 01-APR-00:05 | 51.76 | 51.76 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 51.76 | 51.76 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 51.76 | 51.76 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 51.76 | 51.76 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 51.76 | 51.76 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 51.76 | 51.76 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 51.76 | 51.76 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 51.76 | 51.76 | 0.00 | 4.64 | 21-NOV-08:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 51.75 | 51.75 | 0.04 | 49.24 | 18-DEC-06:50 |
Annual Sum or Average | 0.29 | 0.02 | ||||||
Minimum of Months | 0.00 | 0.00 | 51.75 | 51.75 | 0.00 | 0.00 | ||
Maximum of Months | 3.34 | 2348.98 | 59.94 | 59.94 | 0.11 | 245.18 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 241256.94 | 1259226.39 | 30-JAN-14:00 | 13.94 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 328143.32 | 1936742.49 | 08-FEB-15:05 | 12.26 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 457735.82 | 2033204.10 | 29-MAR-12:05 | 12.54 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 648608.88 | 2248639.52 | 27-APR-08:55 | 13.16 | 6.70 | 0.00 | 0.00 | 01-APR-00:05 |
May | 982599.44 | 2917032.35 | 30-MAY-05:03 | 15.09 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1284695.59 | 3466959.21 | 09-JUN-05:03 | 16.67 | 8.17 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1486311.20 | 4247724.45 | 20-JUL-05:03 | 18.92 | 10.42 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1608017.52 | 4112278.83 | 05-AUG-17:42 | 18.53 | 10.03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1317564.93 | 3983241.45 | 08-SEP-05:03 | 18.16 | 9.66 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 962932.10 | 3143961.29 | 02-OCT-05:02 | 15.74 | 7.24 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 646972.40 | 2598945.81 | 08-NOV-06:02 | 14.17 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 353568.05 | 2002195.26 | 06-DEC-15:05 | 12.45 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 862981.70 | 0.00 | ||||||
Minimum of Months | 241256.94 | 1259226.39 | 12.26 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1608017.52 | 4247724.45 | 18.92 | 10.42 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 239012.55 | 2868496.52 | 30-JAN-06:02 | 17.40 | 10.44 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 325706.67 | 3959160.83 | 09-FEB-06:03 | 18.09 | 12.38 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 454885.12 | 3910098.01 | 29-MAR-05:03 | 17.95 | 12.31 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 645537.11 | 4075973.71 | 12-APR-05:02 | 18.43 | 12.55 | 0.00 | 0.00 | 01-APR-00:05 |
May | 978589.34 | 4519219.57 | 24-MAY-05:02 | 19.71 | 13.18 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1278703.03 | 4636637.55 | 20-JUN-05:02 | 20.05 | 13.35 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1475529.46 | 4944784.75 | 25-JUL-03:12 | 21.16 | 13.79 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1600796.61 | 4940901.92 | 19-AUG-03:01 | 20.92 | 13.79 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1310940.87 | 4723931.97 | 05-SEP-03:02 | 20.30 | 13.47 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 957779.49 | 4458977.76 | 06-OCT-05:02 | 19.53 | 13.09 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 643040.09 | 4320987.18 | 01-NOV-04:11 | 19.13 | 12.90 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 350616.93 | 3813898.80 | 12-DEC-06:02 | 17.74 | 12.17 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 858191.55 | 0.00 | ||||||
Minimum of Months | 239012.55 | 2868496.52 | 17.40 | 10.44 | 0.00 | 0.00 | ||
Maximum of Months | 1600796.61 | 4944784.75 | 21.16 | 13.79 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 353621.79 | 811899.50 | 23-JAN-14:00 | 34.06 | 29.99 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 632442.54 | 1299278.79 | 06-FEB-15:00 | 43.27 | 36.08 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 981394.34 | 1856041.95 | 27-MAR-11:05 | 53.62 | 43.16 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1399572.88 | 2265256.02 | 28-APR-12:00 | 61.10 | 48.46 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1013132.24 | 1606153.62 | 31-MAY-19:00 | 49.00 | 44.40 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1350676.93 | 1931344.88 | 12-JUN-12:00 | 55.01 | 47.03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1722087.46 | 2355652.37 | 21-JUL-12:00 | 62.74 | 51.67 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1931577.06 | 2513549.41 | 16-AUG-12:00 | 65.59 | 52.65 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1094589.62 | 1569740.40 | 04-SEP-14:40 | 48.32 | 43.44 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1147789.37 | 1619085.03 | 04-OCT-12:00 | 49.24 | 41.75 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 1132958.04 | 1616425.80 | 05-NOV-12:00 | 49.19 | 39.07 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1085475.18 | 1591054.70 | 10-DEC-12:00 | 48.72 | 36.25 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1157067.71 | 0.00 | ||||||
Minimum of Months | 353621.79 | 811899.50 | 34.06 | 29.99 | 0.00 | 0.00 | ||
Maximum of Months | 1931577.06 | 2513549.41 | 65.59 | 52.65 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.20 | 57.20 | 11546.12 | 37766.61 | 13-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.87 | 56.87 | 11321.05 | 37352.10 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.09 | 57.09 | 11194.82 | 35673.09 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:05 | 58.05 | 58.05 | 9653.10 | 32359.67 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 57.17 | 57.17 | 9004.47 | 29207.27 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.42 | 58.42 | 8485.50 | 26263.30 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 57.50 | 57.50 | 7725.08 | 24935.30 | 31-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.03 | 57.03 | 8629.99 | 26749.83 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 58.59 | 58.59 | 8903.35 | 29621.87 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 57.23 | 57.23 | 9815.09 | 33198.38 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 57.39 | 57.39 | 10840.79 | 36038.98 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.35 | 57.35 | 11114.68 | 37566.59 | 29-DEC-12:50 |
Annual Sum or Average | 0.00 | 9844.96 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.87 | 56.87 | 7725.08 | 24935.30 | ||
Maximum of Months | 0.00 | 0.00 | 58.59 | 58.59 | 11546.12 | 37766.61 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 293231.71 | 2244530.26 | 30-JAN-14:00 | 28.52 | 23.82 | 425.87 | 98234.34 | 21-JAN-05:40 |
February | 419206.07 | 4112576.77 | 07-FEB-16:00 | 27.90 | 24.92 | 180.57 | 58141.62 | 15-FEB-05:40 |
March | 609705.34 | 3942363.49 | 29-MAR-10:05 | 27.62 | 24.22 | 553.35 | 73164.53 | 23-MAR-03:20 |
April | 1060036.90 | 4775162.22 | 10-APR-12:05 | 29.00 | 25.16 | 433.04 | 65558.89 | 26-APR-04:10 |
May | 2242926.89 | 7478631.49 | 31-MAY-16:00 | 33.47 | 28.85 | 4.39 | 7271.54 | 07-MAY-04:35 |
June | 3759151.77 | 7699838.21 | 12-JUN-14:40 | 33.83 | 28.96 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 4580879.33 | 8396168.15 | 19-JUL-15:10 | 34.98 | 29.32 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 5067513.96 | 8406014.69 | 03-AUG-14:40 | 35.00 | 29.32 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 4082611.33 | 8098612.67 | 07-SEP-14:05 | 34.49 | 29.17 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 2412374.48 | 7398494.20 | 01-OCT-15:52 | 33.33 | 28.80 | 28.07 | 33644.99 | 20-OCT-04:10 |
November | 1152387.51 | 6764171.90 | 01-NOV-14:05 | 32.29 | 28.20 | 151.60 | 39152.50 | 05-NOV-06:20 |
December | 478228.05 | 4500068.96 | 05-DEC-13:05 | 28.54 | 24.86 | 374.61 | 69597.17 | 18-DEC-00:40 |
Annual Sum or Average | 2190668.62 | 179.65 | ||||||
Minimum of Months | 293231.71 | 2244530.26 | 27.62 | 23.82 | 0.00 | 0.00 | ||
Maximum of Months | 5067513.96 | 8406014.69 | 35.00 | 29.32 | 553.35 | 98234.34 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 324387.89 | 0.00 | 0.651972E+11 | 0.530626E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.784781E+11 | 0.602779E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.118595E+12 | 0.888120E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.159900E+12 | 0.108776E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.212938E+12 | 0.119078E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.274267E+12 | 0.139512E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.328088E+12 | 0.162741E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.375313E+12 | 0.218640E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.277106E+12 | 0.125611E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.222875E+12 | 0.119259E+11 | 0.00 | 0.00 |
November | 13486.29 | 0.00 | 0.154149E+12 | 0.101658E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.104852E+12 | 0.798516E+10 | 0.00 | 0.00 |
Annual Sum or Average | 337874.18 | 0.00 | 0.237176E+13 | 0.137728E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.651972E+11 | 0.530626E+10 | 0.00 | 0.00 |
Maximum of Months | 324387.89 | 0.00 | 0.375313E+12 | 0.218640E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.464965E+12 | 0.352849E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.572156E+12 | 0.391860E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.879033E+12 | 0.587043E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.120270E+13 | 0.701166E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.198307E+13 | 0.104632E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.257284E+13 | 0.114617E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.307335E+13 | 0.123758E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.333305E+13 | 0.142765E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.264104E+13 | 0.108501E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.192896E+13 | 0.935151E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.119750E+13 | 0.691679E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.668091E+12 | 0.429154E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.205168E+14 | 0.100316E+13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.464965E+12 | 0.352849E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.333305E+13 | 0.142765E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 48841740.14 | 0.00 | 0.421379E+11 | 0.312872E+10 | 0.00 | 0.00 |
February | 3022022.46 | 0.00 | 0.552846E+11 | 0.353336E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.886150E+11 | 0.543534E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.125291E+12 | 0.679851E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.211513E+12 | 0.107398E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.273363E+12 | 0.119598E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.326336E+12 | 0.131525E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.351826E+12 | 0.148157E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.276407E+12 | 0.109984E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.199382E+12 | 0.904403E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.118858E+12 | 0.613746E+10 | 0.00 | 0.00 |
December | 608362.17 | 0.00 | 0.626771E+11 | 0.374581E+10 | 0.00 | 0.00 |
Annual Sum or Average | 52472124.76 | 0.00 | 0.213169E+13 | 0.994894E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.421379E+11 | 0.312872E+10 | 0.00 | 0.00 |
Maximum of Months | 48841740.14 | 0.00 | 0.351826E+12 | 0.148157E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.629367E+11 | 0.146732E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.603465E+11 | 0.129622E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.742216E+11 | 0.145123E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.787885E+11 | 0.135921E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.103816E+12 | 0.149528E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.125317E+12 | 0.149961E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.149808E+12 | 0.151934E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.176606E+12 | 0.166197E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.136824E+12 | 0.151857E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.120332E+12 | 0.157410E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.966197E+11 | 0.148921E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.751853E+11 | 0.148607E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126080E+13 | 0.178181E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.603465E+11 | 0.129622E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.176606E+12 | 0.166197E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.422785E+12 | 0.180779E+12 | 0.00 | 1.02 |
February | 0.00 | 0.00 | 0.664971E+12 | 0.221833E+12 | 0.00 | 0.96 |
March | 0.00 | 0.00 | 0.105756E+13 | 0.320908E+12 | 0.00 | 0.61 |
April | 0.00 | 0.00 | 0.134390E+13 | 0.395490E+12 | 0.00 | 0.24 |
May | 0.00 | 0.00 | 0.482728E+12 | 0.217461E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.806257E+12 | 0.300526E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.119012E+13 | 0.413961E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.146220E+13 | 0.468085E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.494698E+12 | 0.219082E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.808888E+12 | 0.291022E+12 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.105444E+13 | 0.327373E+12 | 0.00 | 0.07 |
December | 0.00 | 0.00 | 0.135659E+13 | 0.372429E+12 | 0.00 | 1.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.111451E+14 | 0.372895E+13 | 0.00 | 4.08 |
Minimum of Months | 0.00 | 0.00 | 0.422785E+12 | 0.180779E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.146220E+13 | 0.468085E+12 | 0.00 | 1.14 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.686340E+10 | 0.275154E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.123894E+11 | 0.373559E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.205230E+11 | 0.572178E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.271226E+11 | 0.747759E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.942912E+10 | 0.374756E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.165577E+11 | 0.554365E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.248344E+11 | 0.790892E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.305807E+11 | 0.930943E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.100769E+11 | 0.387216E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.161626E+11 | 0.524506E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.207835E+11 | 0.593848E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.265504E+11 | 0.674334E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.221874E+12 | 0.679951E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.686340E+10 | 0.275154E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.305807E+11 | 0.930943E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.567365E+11 | 0.246562E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.112741E+12 | 0.346650E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.193435E+12 | 0.541704E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.257980E+12 | 0.711934E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.890985E+11 | 0.355473E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.157748E+12 | 0.528175E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.236716E+12 | 0.753703E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.290629E+12 | 0.888337E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.948992E+11 | 0.366223E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.153572E+12 | 0.498823E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.197056E+12 | 0.564164E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.248603E+12 | 0.635301E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.208922E+13 | 0.643705E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.567365E+11 | 0.246562E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.290629E+12 | 0.888337E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.508395E+10 | 0.237229E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.109598E+11 | 0.342530E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.192143E+11 | 0.541260E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.258518E+11 | 0.715085E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.911650E+10 | 0.361938E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.159924E+11 | 0.534967E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.239896E+11 | 0.763278E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.293421E+11 | 0.896800E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.969212E+10 | 0.372586E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.154623E+11 | 0.502869E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.196345E+11 | 0.564624E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.245097E+11 | 0.631162E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.208849E+12 | 0.646433E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.508395E+10 | 0.237229E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.293421E+11 | 0.896800E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.530626E+10 | 0.651972E+11 | 324387.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.602779E+10 | 0.784781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.888120E+10 | 0.118595E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108776E+11 | 0.159900E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119078E+11 | 0.212938E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139512E+11 | 0.274267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162741E+11 | 0.328088E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.218640E+11 | 0.375313E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125611E+11 | 0.277106E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119259E+11 | 0.222875E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101658E+11 | 0.154149E+12 | 13486.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.798516E+10 | 0.104852E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137728E+12 | 0.237176E+13 | 337874.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530626E+10 | 0.651972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.218640E+11 | 0.375313E+12 | 324387.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.352849E+11 | 0.464965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.391860E+11 | 0.572156E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587043E+11 | 0.879033E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.701166E+11 | 0.120270E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104632E+12 | 0.198307E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114617E+12 | 0.257284E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123758E+12 | 0.307335E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142765E+12 | 0.333305E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108501E+12 | 0.264104E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.935151E+11 | 0.192896E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.691679E+11 | 0.119750E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.429154E+11 | 0.668091E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100316E+13 | 0.205168E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.352849E+11 | 0.464965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142765E+12 | 0.333305E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.312872E+10 | 0.421379E+11 | 48841740.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.353336E+10 | 0.552846E+11 | 3022022.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.543534E+10 | 0.886150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.679851E+10 | 0.125291E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107398E+11 | 0.211513E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119598E+11 | 0.273363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131525E+11 | 0.326336E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148157E+11 | 0.351826E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109984E+11 | 0.276407E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.904403E+10 | 0.199382E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.613746E+10 | 0.118858E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.374581E+10 | 0.626771E+11 | 608362.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.994894E+11 | 0.213169E+13 | 52472124.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.312872E+10 | 0.421379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148157E+11 | 0.351826E+12 | 48841740.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146732E+11 | 0.629367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129622E+11 | 0.603465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145123E+11 | 0.742216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135921E+11 | 0.787885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149528E+11 | 0.103816E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149961E+11 | 0.125317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151934E+11 | 0.149808E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166197E+11 | 0.176606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151857E+11 | 0.136824E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157410E+11 | 0.120332E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148921E+11 | 0.966197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148607E+11 | 0.751853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178181E+12 | 0.126080E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129622E+11 | 0.603465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166197E+11 | 0.176606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.949070E+11 | 0.339644E+12 | 0.00 | 0.00 | 0.00 | 0.271905E+10 | 0.00 | 0.00 |
February | 0.857224E+11 | 0.531444E+12 | 0.00 | 0.00 | 0.00 | 0.257157E+10 | 0.00 | 0.00 |
March | 0.949070E+11 | 0.833206E+12 | 0.00 | 0.00 | 0.00 | 0.164463E+10 | 0.00 | 0.00 |
April | 0.918454E+11 | 0.104090E+13 | 0.00 | 0.00 | 0.00 | 0.645821E+09 | 0.00 | 0.00 |
May | 0.949070E+11 | 0.360181E+12 | 0.00 | 0.00 | 0.00 | 6466910.62 | 0.00 | 0.00 |
June | 0.918454E+11 | 0.597576E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.949070E+11 | 0.871066E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.949070E+11 | 0.108902E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.918454E+11 | 0.367461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.949070E+11 | 0.612845E+12 | 0.00 | 0.00 | 0.00 | 71899899.06 | 0.00 | 0.00 |
November | 0.918454E+11 | 0.819101E+12 | 0.00 | 0.00 | 0.00 | 0.192226E+09 | 0.00 | 0.00 |
December | 0.949070E+11 | 0.108215E+13 | 0.00 | 0.00 | 0.00 | 0.306347E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.111745E+13 | 0.854460E+13 | 0.00 | 0.00 | 0.00 | 0.109151E+11 | 0.00 | 0.00 |
Minimum of Months | 0.857224E+11 | 0.339644E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.949070E+11 | 0.108902E+13 | 0.00 | 0.00 | 0.00 | 0.306347E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140330E+10 | 0.551516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126750E+10 | 0.992132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140330E+10 | 0.162045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135803E+10 | 0.210031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140330E+10 | 0.708486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135803E+10 | 0.123721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140330E+10 | 0.183288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140330E+10 | 0.226745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135803E+10 | 0.756274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140330E+10 | 0.123209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135803E+10 | 0.162031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140330E+10 | 0.212104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165227E+11 | 0.170401E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126750E+10 | 0.551516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140330E+10 | 0.226745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.133920E+11 | 0.454724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120960E+11 | 0.901720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133920E+11 | 0.152657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129600E+11 | 0.199747E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133920E+11 | 0.669432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129600E+11 | 0.117891E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133920E+11 | 0.174738E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133920E+11 | 0.215187E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129600E+11 | 0.712369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133920E+11 | 0.117082E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129600E+11 | 0.153600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133920E+11 | 0.198465E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157680E+12 | 0.160319E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120960E+11 | 0.454724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133920E+11 | 0.215187E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135142E+10 | 0.406309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122064E+10 | 0.875514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135142E+10 | 0.151531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130783E+10 | 0.200087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135142E+10 | 0.684854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130783E+10 | 0.119506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135142E+10 | 0.177082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135142E+10 | 0.217255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130783E+10 | 0.727408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135142E+10 | 0.117850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130783E+10 | 0.152961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135142E+10 | 0.195495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159119E+11 | 0.160118E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122064E+10 | 0.406309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135142E+10 | 0.217255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.530626E+10 | 324387.89 | 0.651972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.602779E+10 | 0.00 | 0.784781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.888120E+10 | 0.00 | 0.118595E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108776E+11 | 0.00 | 0.159900E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119078E+11 | 0.00 | 0.212938E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139512E+11 | 0.00 | 0.274267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162741E+11 | 0.00 | 0.328088E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.218640E+11 | 0.00 | 0.375313E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125611E+11 | 0.00 | 0.277106E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119259E+11 | 0.00 | 0.222875E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101658E+11 | 13486.29 | 0.154149E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.798516E+10 | 0.00 | 0.104852E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137728E+12 | 337874.18 | 0.237176E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530626E+10 | 0.00 | 0.651972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.218640E+11 | 324387.89 | 0.375313E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.352849E+11 | 0.00 | 0.464965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.391860E+11 | 0.00 | 0.572156E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587043E+11 | 0.00 | 0.879033E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.701166E+11 | 0.00 | 0.120270E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104632E+12 | 0.00 | 0.198307E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114617E+12 | 0.00 | 0.257284E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123758E+12 | 0.00 | 0.307335E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142765E+12 | 0.00 | 0.333305E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108501E+12 | 0.00 | 0.264104E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.935151E+11 | 0.00 | 0.192896E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.691679E+11 | 0.00 | 0.119750E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.429154E+11 | 0.00 | 0.668091E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100316E+13 | 0.00 | 0.205168E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.352849E+11 | 0.00 | 0.464965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142765E+12 | 0.00 | 0.333305E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.312872E+10 | 48841740.14 | 0.421379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.353336E+10 | 3022022.46 | 0.552846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.543534E+10 | 0.00 | 0.886150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.679851E+10 | 0.00 | 0.125291E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107398E+11 | 0.00 | 0.211513E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119598E+11 | 0.00 | 0.273363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131525E+11 | 0.00 | 0.326336E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148157E+11 | 0.00 | 0.351826E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109984E+11 | 0.00 | 0.276407E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.904403E+10 | 0.00 | 0.199382E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.613746E+10 | 0.00 | 0.118858E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.374581E+10 | 608362.17 | 0.626771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.994894E+11 | 52472124.76 | 0.213169E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.312872E+10 | 0.00 | 0.421379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148157E+11 | 48841740.14 | 0.351826E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146732E+11 | 0.00 | 0.629367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129622E+11 | 0.00 | 0.603465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145123E+11 | 0.00 | 0.742216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135921E+11 | 0.00 | 0.787885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149528E+11 | 0.00 | 0.103816E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149961E+11 | 0.00 | 0.125317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151934E+11 | 0.00 | 0.149808E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166197E+11 | 0.00 | 0.176606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151857E+11 | 0.00 | 0.136824E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157410E+11 | 0.00 | 0.120332E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148921E+11 | 0.00 | 0.966197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148607E+11 | 0.00 | 0.751853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178181E+12 | 0.00 | 0.126080E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129622E+11 | 0.00 | 0.603465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166197E+11 | 0.00 | 0.176606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.949070E+11 | 0.00 | 0.422785E+12 | 0.00 | 0.831406E+11 | 0.00 | 0.00 | 0.00 | 0.273129E+10 | 0.00 | 0.00 | 0.00 |
February | 0.857224E+11 | 0.00 | 0.664971E+12 | 0.00 | 0.133527E+12 | 0.00 | 0.00 | 0.00 | 0.258314E+10 | 0.00 | 0.00 | 0.00 |
March | 0.949070E+11 | 0.00 | 0.105756E+13 | 0.00 | 0.224349E+12 | 0.00 | 0.00 | 0.00 | 0.165203E+10 | 0.00 | 0.00 | 0.00 |
April | 0.918454E+11 | 0.00 | 0.134390E+13 | 0.00 | 0.302996E+12 | 0.00 | 0.00 | 0.00 | 0.648728E+09 | 0.00 | 0.00 | 0.00 |
May | 0.949070E+11 | 0.00 | 0.482728E+12 | 0.00 | 0.122547E+12 | 0.00 | 0.00 | 0.00 | 6496020.80 | 0.00 | 0.00 | 0.00 |
June | 0.918454E+11 | 0.00 | 0.806257E+12 | 0.00 | 0.208681E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.949070E+11 | 0.00 | 0.119012E+13 | 0.00 | 0.319054E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.949070E+11 | 0.00 | 0.146220E+13 | 0.00 | 0.373178E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.918454E+11 | 0.00 | 0.494698E+12 | 0.00 | 0.127236E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.949070E+11 | 0.00 | 0.808888E+12 | 0.00 | 0.196043E+12 | 0.00 | 0.00 | 0.00 | 72223549.65 | 0.00 | 0.00 | 0.00 |
November | 0.918454E+11 | 0.00 | 0.105444E+13 | 0.00 | 0.235334E+12 | 0.00 | 0.00 | 0.00 | 0.193092E+09 | 0.00 | 0.00 | 0.00 |
December | 0.949070E+11 | 0.00 | 0.135659E+13 | 0.00 | 0.274445E+12 | 0.00 | 0.00 | 0.00 | 0.307726E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111745E+13 | 0.00 | 0.111451E+14 | 0.00 | 0.260053E+13 | 0.00 | 0.00 | 0.00 | 0.109643E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.857224E+11 | 0.00 | 0.422785E+12 | 0.00 | 0.831406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.949070E+11 | 0.00 | 0.146220E+13 | 0.00 | 0.373178E+12 | 0.00 | 0.00 | 0.00 | 0.307726E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140330E+10 | 0.00 | 0.686340E+10 | 0.00 | 0.134824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126750E+10 | 0.00 | 0.123894E+11 | 0.00 | 0.246809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140330E+10 | 0.00 | 0.205230E+11 | 0.00 | 0.431848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135803E+10 | 0.00 | 0.271226E+11 | 0.00 | 0.611956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140330E+10 | 0.00 | 0.942912E+10 | 0.00 | 0.234426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135803E+10 | 0.00 | 0.165577E+11 | 0.00 | 0.418562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140330E+10 | 0.00 | 0.248344E+11 | 0.00 | 0.650562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140330E+10 | 0.00 | 0.305807E+11 | 0.00 | 0.790612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135803E+10 | 0.00 | 0.100769E+11 | 0.00 | 0.251413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140330E+10 | 0.00 | 0.161626E+11 | 0.00 | 0.384176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135803E+10 | 0.00 | 0.207835E+11 | 0.00 | 0.458045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140330E+10 | 0.00 | 0.265504E+11 | 0.00 | 0.534004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165227E+11 | 0.00 | 0.221874E+12 | 0.00 | 0.514724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126750E+10 | 0.00 | 0.686340E+10 | 0.00 | 0.134824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140330E+10 | 0.00 | 0.305807E+11 | 0.00 | 0.790612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.133920E+11 | 0.00 | 0.567365E+11 | 0.00 | 0.112641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120960E+11 | 0.00 | 0.112741E+12 | 0.00 | 0.225690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133920E+11 | 0.00 | 0.193435E+12 | 0.00 | 0.407784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129600E+11 | 0.00 | 0.257980E+12 | 0.00 | 0.582333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133920E+11 | 0.00 | 0.890985E+11 | 0.00 | 0.221552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129600E+11 | 0.00 | 0.157748E+12 | 0.00 | 0.398574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133920E+11 | 0.00 | 0.236716E+12 | 0.00 | 0.619783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133920E+11 | 0.00 | 0.290629E+12 | 0.00 | 0.754417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129600E+11 | 0.00 | 0.948992E+11 | 0.00 | 0.236623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133920E+11 | 0.00 | 0.153572E+12 | 0.00 | 0.364902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129600E+11 | 0.00 | 0.197056E+12 | 0.00 | 0.434563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133920E+11 | 0.00 | 0.248603E+12 | 0.00 | 0.501380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157680E+12 | 0.00 | 0.208922E+13 | 0.00 | 0.486024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120960E+11 | 0.00 | 0.567365E+11 | 0.00 | 0.112641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133920E+11 | 0.00 | 0.290629E+12 | 0.00 | 0.754417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135142E+10 | 0.00 | 0.508395E+10 | 0.00 | 0.102087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122064E+10 | 0.00 | 0.109598E+11 | 0.00 | 0.220466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135142E+10 | 0.00 | 0.192143E+11 | 0.00 | 0.406118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130783E+10 | 0.00 | 0.258518E+11 | 0.00 | 0.584302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135142E+10 | 0.00 | 0.911650E+10 | 0.00 | 0.226796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130783E+10 | 0.00 | 0.159924E+11 | 0.00 | 0.404184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135142E+10 | 0.00 | 0.239896E+11 | 0.00 | 0.628135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135142E+10 | 0.00 | 0.293421E+11 | 0.00 | 0.761658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130783E+10 | 0.00 | 0.969212E+10 | 0.00 | 0.241804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135142E+10 | 0.00 | 0.154623E+11 | 0.00 | 0.367727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130783E+10 | 0.00 | 0.196345E+11 | 0.00 | 0.433841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135142E+10 | 0.00 | 0.245097E+11 | 0.00 | 0.496020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159119E+11 | 0.00 | 0.208849E+12 | 0.00 | 0.487314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122064E+10 | 0.00 | 0.508395E+10 | 0.00 | 0.102087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135142E+10 | 0.00 | 0.293421E+11 | 0.00 | 0.761658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101920E+10 | 0.459253E+09 | 0.00 | 0.117464E+09 | 12136909.78 | 0.00 | 0.147983E+11 | 0.00 | 0.40 |
February | 0.969621E+09 | 0.117622E+10 | 0.00 | 93987463.16 | 29878670.64 | 0.00 | 0.938023E+10 | 0.00 | 0.39 |
March | 0.349937E+09 | 0.344311E+10 | 0.00 | 82453787.69 | 27643256.96 | 0.00 | 0.711424E+10 | 0.00 | 0.40 |
April | 0.226224E+09 | 0.960072E+10 | 0.00 | 45385474.49 | 0.170999E+09 | 0.00 | 0.292216E+10 | 0.00 | 0.39 |
May | 38637138.15 | 0.264728E+11 | 0.00 | 14299834.64 | 0.644562E+09 | 0.00 | 0.465940E+09 | 0.00 | 0.41 |
June | 7110425.03 | 0.461319E+11 | 0.00 | 2636505.78 | 0.967146E+09 | 0.00 | 68160501.14 | 0.00 | 0.43 |
July | 6568698.22 | 0.673796E+11 | 0.00 | 2757178.81 | 0.161980E+10 | 0.00 | 43724638.89 | 0.00 | 0.42 |
August | 440069.39 | 0.801609E+11 | 0.00 | 74611.33 | 0.127203E+10 | 0.00 | 5279823.50 | 0.00 | 0.46 |
September | 585413.13 | 0.550146E+11 | 0.00 | 1213707.57 | 0.133544E+10 | 0.00 | 12259409.53 | 0.00 | 0.43 |
October | 36879131.12 | 0.332748E+11 | 0.00 | 11072135.11 | 0.851861E+09 | 0.00 | 0.419889E+09 | 0.00 | 0.43 |
November | 0.168777E+09 | 0.137564E+11 | 0.00 | 44932697.85 | 0.146585E+09 | 0.00 | 0.166476E+10 | 0.00 | 0.42 |
December | 0.698590E+09 | 0.263202E+10 | 0.00 | 0.111834E+09 | 39194698.99 | 0.00 | 0.925260E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.352257E+10 | 0.339502E+12 | 0.00 | 0.528112E+09 | 0.711727E+10 | 0.00 | 0.461475E+11 | 0.00 | 0.42 |
Minimum of Months | 440069.39 | 0.459253E+09 | 0.00 | 74611.33 | 12136909.78 | 0.00 | 5279823.50 | 0.00 | 0.39 |
Maximum of Months | 0.101920E+10 | 0.801609E+11 | 0.00 | 0.117464E+09 | 0.161980E+10 | 0.00 | 0.147983E+11 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.986492E+09 | 0.302742E+09 | 0.00 | 81393589.50 | 0.160385E+09 | 0.00 | 0.138360E+11 | 0.00 | 0.36 |
February | 0.743818E+09 | 0.124700E+10 | 0.00 | 69271000.23 | 0.325958E+09 | 0.00 | 0.876862E+10 | 0.00 | 0.36 |
March | 0.169675E+10 | 0.331743E+10 | 0.00 | 64633257.44 | 0.800650E+09 | 0.00 | 0.679846E+10 | 0.00 | 0.41 |
April | 0.163030E+10 | 0.816748E+10 | 0.00 | 25394395.17 | 0.522475E+10 | 0.00 | 0.192220E+10 | 0.00 | 0.46 |
May | 0.224482E+09 | 0.191748E+11 | 0.00 | 7345530.13 | 0.132306E+11 | 0.00 | 0.306556E+09 | 0.00 | 0.43 |
June | 26262381.57 | 0.328172E+11 | 0.00 | 929442.65 | 0.238056E+11 | 0.00 | 18517851.67 | 0.00 | 0.44 |
July | 94484103.87 | 0.443018E+11 | 0.00 | 1622751.96 | 0.324297E+11 | 0.00 | 24071048.70 | 0.00 | 0.43 |
August | 0.00 | 0.526975E+11 | 0.00 | 0.00 | 0.290331E+11 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 282007.38 | 0.370581E+11 | 0.00 | 913559.70 | 0.278867E+11 | 0.00 | 16430401.67 | 0.00 | 0.44 |
October | 0.269496E+09 | 0.225873E+11 | 0.00 | 5471260.34 | 0.170131E+11 | 0.00 | 0.277871E+09 | 0.00 | 0.44 |
November | 0.943390E+09 | 0.106364E+11 | 0.00 | 23336768.87 | 0.276933E+10 | 0.00 | 0.109182E+10 | 0.00 | 0.42 |
December | 0.152773E+10 | 0.226223E+10 | 0.00 | 77120796.28 | 0.101436E+10 | 0.00 | 0.828925E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.814350E+10 | 0.234570E+12 | 0.00 | 0.357432E+09 | 0.153694E+12 | 0.00 | 0.413498E+11 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.302742E+09 | 0.00 | 0.00 | 0.160385E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.169675E+10 | 0.526975E+11 | 0.00 | 81393589.50 | 0.324297E+11 | 0.00 | 0.138360E+11 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.774513E+10 | 0.223488E+10 | 0.00 | 0.528448E+09 | 0.247112E+10 | 0.00 | 0.123144E+12 | 0.00 | 0.35 |
February | 0.485418E+10 | 0.117980E+11 | 0.00 | 0.471456E+09 | 0.276678E+10 | 0.00 | 0.772872E+11 | 0.00 | 0.33 |
March | 0.750632E+10 | 0.321763E+11 | 0.00 | 0.469347E+09 | 0.326926E+10 | 0.00 | 0.625772E+11 | 0.00 | 0.35 |
April | 0.564549E+10 | 0.779184E+11 | 0.00 | 0.222986E+09 | 0.317127E+11 | 0.00 | 0.209265E+11 | 0.00 | 0.35 |
May | 0.215400E+10 | 0.184740E+12 | 0.00 | 54523815.77 | 0.115682E+12 | 0.00 | 0.283202E+10 | 0.00 | 0.40 |
June | 0.246221E+09 | 0.307804E+12 | 0.00 | 6455562.53 | 0.231871E+12 | 0.00 | 0.213202E+09 | 0.00 | 0.43 |
July | 0.913444E+09 | 0.404126E+12 | 0.00 | 5440406.14 | 0.334571E+12 | 0.00 | 0.103925E+09 | 0.00 | 0.42 |
August | 0.00 | 0.470483E+12 | 0.00 | 0.00 | 0.314258E+12 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 2753451.39 | 0.350392E+12 | 0.00 | 6470608.16 | 0.251714E+12 | 0.00 | 0.159046E+09 | 0.00 | 0.41 |
October | 0.168822E+10 | 0.213100E+12 | 0.00 | 48907246.08 | 0.125711E+12 | 0.00 | 0.318343E+10 | 0.00 | 0.37 |
November | 0.161023E+10 | 0.101598E+12 | 0.00 | 0.199169E+09 | 0.131051E+11 | 0.00 | 0.112374E+11 | 0.00 | 0.33 |
December | 0.609670E+10 | 0.210234E+11 | 0.00 | 0.485902E+09 | 0.572469E+10 | 0.00 | 0.725946E+11 | 0.00 | 0.34 |
Annual Sum or Average | 0.384627E+11 | 0.217739E+13 | 0.00 | 0.249911E+10 | 0.143286E+13 | 0.00 | 0.374258E+12 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.223488E+10 | 0.00 | 0.00 | 0.247112E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.774513E+10 | 0.470483E+12 | 0.00 | 0.528448E+09 | 0.334571E+12 | 0.00 | 0.123144E+12 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.424020E+10 | 0.185182E+09 | 0.00 | 35027643.10 | 0.199800E+09 | 0.00 | 0.732219E+10 | 0.00 | 0.32 |
February | 0.229823E+10 | 0.106787E+10 | 0.00 | 34444953.00 | 0.261513E+09 | 0.00 | 0.508174E+10 | 0.00 | 0.32 |
March | 0.107909E+10 | 0.290579E+10 | 0.00 | 39106645.18 | 0.255203E+09 | 0.00 | 0.519168E+10 | 0.00 | 0.33 |
April | 0.505442E+09 | 0.733662E+10 | 0.00 | 20403666.84 | 0.281409E+10 | 0.00 | 0.183761E+10 | 0.00 | 0.35 |
May | 0.193005E+09 | 0.180647E+11 | 0.00 | 5320465.06 | 0.107908E+11 | 0.00 | 0.249672E+09 | 0.00 | 0.41 |
June | 27040745.87 | 0.306514E+11 | 0.00 | 736220.45 | 0.220394E+11 | 0.00 | 22197247.43 | 0.00 | 0.43 |
July | 91671842.52 | 0.408363E+11 | 0.00 | 929193.12 | 0.313036E+11 | 0.00 | 11073502.31 | 0.00 | 0.42 |
August | 0.00 | 0.473724E+11 | 0.00 | 0.00 | 0.297056E+11 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.350606E+11 | 0.00 | 571462.97 | 0.242267E+11 | 0.00 | 10054030.91 | 0.00 | 0.41 |
October | 0.167410E+09 | 0.209272E+11 | 0.00 | 4754054.06 | 0.121696E+11 | 0.00 | 0.288673E+09 | 0.00 | 0.37 |
November | 0.158050E+09 | 0.978736E+10 | 0.00 | 15705836.82 | 0.115352E+10 | 0.00 | 0.895913E+09 | 0.00 | 0.33 |
December | 0.200457E+10 | 0.180764E+10 | 0.00 | 34223912.65 | 0.657818E+09 | 0.00 | 0.485428E+10 | 0.00 | 0.32 |
Annual Sum or Average | 0.107647E+11 | 0.216003E+12 | 0.00 | 0.191224E+09 | 0.135578E+12 | 0.00 | 0.257651E+11 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.185182E+09 | 0.00 | 0.00 | 0.199800E+09 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.424020E+10 | 0.473724E+11 | 0.00 | 39106645.18 | 0.313036E+11 | 0.00 | 0.732219E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.568383E+09 | 43533714.42 | 0.00 | 5918786.70 | 20107503.85 | 0.00 | 0.867943E+09 | 0.00 | 0.30 |
February | 0.313141E+09 | 0.196106E+09 | 0.00 | 6221226.45 | 40705622.71 | 0.00 | 0.650050E+09 | 0.00 | 0.33 |
March | 0.296935E+09 | 0.621381E+09 | 0.00 | 7083002.93 | 91661665.23 | 0.00 | 0.649651E+09 | 0.00 | 0.45 |
April | 0.209264E+09 | 0.185818E+10 | 0.00 | 3384273.44 | 0.537627E+09 | 0.00 | 0.229071E+09 | 0.00 | 0.59 |
May | 24138452.27 | 0.580904E+10 | 0.00 | 1630642.82 | 0.111649E+10 | 0.00 | 62440516.57 | 0.00 | 0.71 |
June | 2924700.56 | 0.110055E+11 | 0.00 | 276972.04 | 0.170980E+10 | 0.00 | 4600821.23 | 0.00 | 0.78 |
July | 6767349.94 | 0.160948E+11 | 0.00 | 414927.34 | 0.145398E+10 | 0.00 | 10866752.15 | 0.00 | 0.78 |
August | 0.00 | 0.174269E+11 | 0.00 | 0.00 | 0.943738E+09 | 0.00 | 0.00 | 0.00 | 0.76 |
September | 35355.41 | 0.108158E+11 | 0.00 | 149498.60 | 0.246088E+10 | 0.00 | 2764946.19 | 0.00 | 0.70 |
October | 33077292.54 | 0.513905E+10 | 0.00 | 850044.69 | 0.177174E+10 | 0.00 | 41340814.35 | 0.00 | 0.60 |
November | 0.127436E+09 | 0.183797E+10 | 0.00 | 2381224.80 | 0.340419E+09 | 0.00 | 0.108323E+09 | 0.00 | 0.49 |
December | 0.345908E+09 | 0.324822E+09 | 0.00 | 6775641.85 | 0.127211E+09 | 0.00 | 0.633024E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.192801E+10 | 0.711730E+11 | 0.00 | 35086241.66 | 0.106144E+11 | 0.00 | 0.326008E+10 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 43533714.42 | 0.00 | 0.00 | 20107503.85 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.568383E+09 | 0.174269E+11 | 0.00 | 7083002.93 | 0.246088E+10 | 0.00 | 0.867943E+09 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.300049E+09 | 33927988.06 | 0.00 | 5339248.48 | 11814154.45 | 0.00 | 0.806204E+09 | 0.00 | 0.36 |
February | 0.185133E+09 | 0.141753E+09 | 0.00 | 5084868.99 | 19103992.73 | 0.00 | 0.546916E+09 | 0.00 | 0.39 |
March | 0.202859E+09 | 0.455235E+09 | 0.00 | 5208561.62 | 56995625.45 | 0.00 | 0.458113E+09 | 0.00 | 0.50 |
April | 0.147182E+09 | 0.138979E+10 | 0.00 | 2521617.25 | 0.310552E+09 | 0.00 | 0.159575E+09 | 0.00 | 0.65 |
May | 12155127.52 | 0.454684E+10 | 0.00 | 1381841.23 | 0.643741E+09 | 0.00 | 54607383.28 | 0.00 | 0.85 |
June | 1903615.56 | 0.800203E+10 | 0.00 | 194655.43 | 0.110106E+10 | 0.00 | 3227803.39 | 0.00 | 0.87 |
July | 5071466.36 | 0.111460E+11 | 0.00 | 235552.94 | 0.109924E+10 | 0.00 | 6046802.98 | 0.00 | 0.86 |
August | 0.00 | 0.113739E+11 | 0.00 | 0.00 | 0.970565E+09 | 0.00 | 0.00 | 0.00 | 0.80 |
September | 22906.34 | 0.852648E+10 | 0.00 | 115475.41 | 0.142297E+10 | 0.00 | 2150020.79 | 0.00 | 0.82 |
October | 14285307.81 | 0.412704E+10 | 0.00 | 960653.06 | 0.103341E+10 | 0.00 | 45956213.78 | 0.00 | 0.70 |
November | 77766082.10 | 0.133973E+10 | 0.00 | 1815862.33 | 0.211672E+09 | 0.00 | 87385359.13 | 0.00 | 0.53 |
December | 0.241079E+09 | 0.210732E+09 | 0.00 | 4557386.31 | 82340201.73 | 0.00 | 0.426261E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.118751E+10 | 0.512934E+11 | 0.00 | 27415723.07 | 0.696348E+10 | 0.00 | 0.259644E+10 | 0.00 | 0.64 |
Minimum of Months | 0.00 | 33927988.06 | 0.00 | 0.00 | 11814154.45 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.300049E+09 | 0.113739E+11 | 0.00 | 5339248.48 | 0.142297E+10 | 0.00 | 0.806204E+09 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.385888E+09 | 99660759.46 | 0.00 | 13584188.04 | 7239122.27 | 0.00 | 0.184810E+10 | 0.00 | 0.51 |
February | 0.274055E+09 | 0.347032E+09 | 0.00 | 11513090.95 | 16154569.01 | 0.00 | 0.112313E+10 | 0.00 | 0.52 |
March | 0.275630E+09 | 0.868880E+09 | 0.00 | 10154190.73 | 77565945.17 | 0.00 | 0.877608E+09 | 0.00 | 0.58 |
April | 0.207698E+09 | 0.225929E+10 | 0.00 | 3780597.08 | 0.456617E+09 | 0.00 | 0.245498E+09 | 0.00 | 0.65 |
May | 24072464.94 | 0.581944E+10 | 0.00 | 1599697.25 | 0.112454E+10 | 0.00 | 60492907.27 | 0.00 | 0.71 |
June | 2928044.70 | 0.102964E+11 | 0.00 | 256551.60 | 0.184728E+10 | 0.00 | 4212192.05 | 0.00 | 0.74 |
July | 7676936.13 | 0.156538E+11 | 0.00 | 378281.27 | 0.163357E+10 | 0.00 | 9531825.74 | 0.00 | 0.77 |
August | 0.00 | 0.183280E+11 | 0.00 | 0.00 | 0.881542E+09 | 0.00 | 0.00 | 0.00 | 0.79 |
September | 35395.84 | 0.140578E+11 | 0.00 | 164338.17 | 0.184163E+10 | 0.00 | 3030011.56 | 0.00 | 0.84 |
October | 21230009.08 | 0.820041E+10 | 0.00 | 1981660.06 | 0.117895E+10 | 0.00 | 77999644.45 | 0.00 | 0.82 |
November | 0.112504E+09 | 0.308458E+10 | 0.00 | 4893716.15 | 0.245988E+09 | 0.00 | 0.188755E+09 | 0.00 | 0.72 |
December | 0.269971E+09 | 0.663332E+09 | 0.00 | 13294920.84 | 76704815.78 | 0.00 | 0.114670E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.158169E+10 | 0.796786E+11 | 0.00 | 61601232.15 | 0.938778E+10 | 0.00 | 0.558505E+10 | 0.00 | 0.69 |
Minimum of Months | 0.00 | 99660759.46 | 0.00 | 0.00 | 7239122.27 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.385888E+09 | 0.183280E+11 | 0.00 | 13584188.04 | 0.184728E+10 | 0.00 | 0.184810E+10 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123001E+09 | 59924509.70 | 0.00 | 8490913.34 | 7091218.13 | 0.00 | 0.133898E+10 | 0.00 | 0.50 |
February | 52970894.47 | 0.268390E+09 | 0.00 | 9476975.60 | 6716669.15 | 0.00 | 0.110995E+10 | 0.00 | 0.64 |
March | 69758145.56 | 0.839190E+09 | 0.00 | 12043612.37 | 19222618.22 | 0.00 | 0.117898E+10 | 0.00 | 0.87 |
April | 36779719.00 | 0.304974E+10 | 0.00 | 6949053.27 | 27767228.36 | 0.00 | 0.521618E+09 | 0.00 | 1.13 |
May | 6457198.30 | 0.645797E+10 | 0.00 | 1953848.61 | 0.206026E+09 | 0.00 | 72546620.82 | 0.00 | 1.05 |
June | 82234.05 | 0.126049E+11 | 0.00 | 319863.77 | 0.236759E+09 | 0.00 | 7104916.82 | 0.00 | 1.21 |
July | 857152.71 | 0.182976E+11 | 0.00 | 558084.34 | 0.142687E+09 | 0.00 | 19402319.84 | 0.00 | 1.28 |
August | 0.00 | 0.233171E+11 | 0.00 | 0.00 | 62637299.04 | 0.00 | 0.00 | 0.00 | 1.51 |
September | 22902.66 | 0.125648E+11 | 0.00 | 142705.66 | 0.350397E+09 | 0.00 | 2645772.20 | 0.00 | 1.04 |
October | 10078058.39 | 0.704419E+10 | 0.00 | 1376349.15 | 0.224551E+09 | 0.00 | 65835107.68 | 0.00 | 0.98 |
November | 38871922.36 | 0.245484E+10 | 0.00 | 4910470.68 | 60507138.23 | 0.00 | 0.222841E+09 | 0.00 | 0.87 |
December | 78383857.28 | 0.572961E+09 | 0.00 | 13253878.48 | 19512609.61 | 0.00 | 0.134275E+10 | 0.00 | 0.80 |
Annual Sum or Average | 0.417263E+09 | 0.875316E+11 | 0.00 | 59475755.27 | 0.136388E+10 | 0.00 | 0.588266E+10 | 0.00 | 0.99 |
Minimum of Months | 0.00 | 59924509.70 | 0.00 | 0.00 | 6716669.15 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.123001E+09 | 0.233171E+11 | 0.00 | 13253878.48 | 0.350397E+09 | 0.00 | 0.134275E+10 | 0.00 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.970449E+10 | 0.356448E+09 | 0.00 | 25222659.30 | 0.245152E+09 | 0.00 | 0.391871E+10 | 0.00 | 0.29 |
February | 0.521120E+10 | 0.183325E+10 | 0.00 | 32244352.95 | 0.435516E+09 | 0.00 | 0.377271E+10 | 0.00 | 0.32 |
March | 0.343652E+10 | 0.645553E+10 | 0.00 | 45446520.55 | 0.353605E+09 | 0.00 | 0.461681E+10 | 0.00 | 0.40 |
April | 0.114368E+10 | 0.196739E+11 | 0.00 | 26921821.57 | 0.322550E+10 | 0.00 | 0.215657E+10 | 0.00 | 0.52 |
May | 0.195378E+09 | 0.656424E+11 | 0.00 | 15570789.04 | 0.819278E+10 | 0.00 | 0.714763E+09 | 0.00 | 0.76 |
June | 21933634.92 | 0.124004E+12 | 0.00 | 2987951.39 | 0.147662E+11 | 0.00 | 71842397.26 | 0.00 | 0.86 |
July | 75790092.50 | 0.179675E+12 | 0.00 | 3121064.33 | 0.158819E+11 | 0.00 | 85650121.25 | 0.00 | 0.89 |
August | 0.00 | 0.189254E+12 | 0.00 | 0.00 | 0.186730E+11 | 0.00 | 0.00 | 0.00 | 0.88 |
September | 39419.59 | 0.122203E+12 | 0.00 | 1280807.38 | 0.199617E+11 | 0.00 | 30518985.76 | 0.00 | 0.76 |
October | 0.210177E+09 | 0.549885E+11 | 0.00 | 7942226.65 | 0.122772E+11 | 0.00 | 0.469843E+09 | 0.00 | 0.58 |
November | 0.548280E+09 | 0.186060E+11 | 0.00 | 16778594.32 | 0.164360E+10 | 0.00 | 0.879413E+09 | 0.00 | 0.41 |
December | 0.516194E+10 | 0.287695E+10 | 0.00 | 31350225.37 | 0.732409E+09 | 0.00 | 0.334356E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.257094E+11 | 0.785569E+12 | 0.00 | 0.208867E+09 | 0.963886E+11 | 0.00 | 0.200604E+11 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.356448E+09 | 0.00 | 0.00 | 0.245152E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.970449E+10 | 0.189254E+12 | 0.00 | 45446520.55 | 0.199617E+11 | 0.00 | 0.461681E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.412500E+10 | 0.294025E+09 | 0.00 | 32743283.81 | 0.129964E+09 | 0.00 | 0.573825E+10 | 0.00 | 0.34 |
February | 0.227739E+10 | 0.152210E+10 | 0.00 | 36510152.01 | 0.143148E+09 | 0.00 | 0.479420E+10 | 0.00 | 0.39 |
March | 0.166520E+10 | 0.526713E+10 | 0.00 | 44374224.77 | 0.170729E+09 | 0.00 | 0.464224E+10 | 0.00 | 0.50 |
April | 0.535455E+09 | 0.175687E+11 | 0.00 | 29969177.81 | 0.122529E+10 | 0.00 | 0.233730E+10 | 0.00 | 0.67 |
May | 70197634.71 | 0.535062E+11 | 0.00 | 14961977.33 | 0.376775E+10 | 0.00 | 0.695017E+09 | 0.00 | 0.94 |
June | 11431871.48 | 0.963092E+11 | 0.00 | 2408765.38 | 0.773518E+10 | 0.00 | 57616164.25 | 0.00 | 1.01 |
July | 37331355.43 | 0.138830E+12 | 0.00 | 2189312.05 | 0.636226E+10 | 0.00 | 71143025.29 | 0.00 | 1.04 |
August | 0.00 | 0.150627E+12 | 0.00 | 0.00 | 0.754456E+10 | 0.00 | 0.00 | 0.00 | 1.05 |
September | 107118.12 | 0.102326E+12 | 0.00 | 1074259.01 | 0.860424E+10 | 0.00 | 25483768.93 | 0.00 | 0.93 |
October | 44464715.07 | 0.489289E+11 | 0.00 | 11790438.15 | 0.526679E+10 | 0.00 | 0.644067E+09 | 0.00 | 0.73 |
November | 0.207265E+09 | 0.152531E+11 | 0.00 | 18637098.51 | 0.783925E+09 | 0.00 | 0.100283E+10 | 0.00 | 0.51 |
December | 0.227401E+10 | 0.228139E+10 | 0.00 | 31677707.67 | 0.422157E+09 | 0.00 | 0.387051E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.112479E+11 | 0.632713E+12 | 0.00 | 0.226336E+09 | 0.421560E+11 | 0.00 | 0.238787E+11 | 0.00 | 0.71 |
Minimum of Months | 0.00 | 0.294025E+09 | 0.00 | 0.00 | 0.129964E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.412500E+10 | 0.150627E+12 | 0.00 | 44374224.77 | 0.860424E+10 | 0.00 | 0.573825E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.448670E+10 | 0.113489E+10 | 0.00 | 0.116291E+09 | 68202999.10 | 0.00 | 0.189377E+11 | 0.00 | 0.57 |
February | 0.305514E+10 | 0.394701E+10 | 0.00 | 97744796.30 | 87578486.15 | 0.00 | 0.116387E+11 | 0.00 | 0.57 |
March | 0.237551E+10 | 0.981557E+10 | 0.00 | 83634329.20 | 0.190175E+09 | 0.00 | 0.854591E+10 | 0.00 | 0.59 |
April | 0.923150E+09 | 0.250046E+11 | 0.00 | 33698159.65 | 0.232603E+10 | 0.00 | 0.267595E+10 | 0.00 | 0.61 |
May | 0.194723E+09 | 0.654610E+11 | 0.00 | 15484649.76 | 0.826739E+10 | 0.00 | 0.696446E+09 | 0.00 | 0.76 |
June | 21495550.68 | 0.115310E+12 | 0.00 | 2787372.69 | 0.164624E+11 | 0.00 | 67435793.08 | 0.00 | 0.82 |
July | 78482191.75 | 0.175643E+12 | 0.00 | 2929670.47 | 0.168749E+11 | 0.00 | 81184028.08 | 0.00 | 0.87 |
August | 0.00 | 0.205871E+12 | 0.00 | 0.00 | 0.155787E+11 | 0.00 | 0.00 | 0.00 | 0.93 |
September | 165574.92 | 0.162077E+12 | 0.00 | 1505893.18 | 0.125527E+11 | 0.00 | 34976718.68 | 0.00 | 0.93 |
October | 67022131.21 | 0.930692E+11 | 0.00 | 22662680.52 | 0.584651E+10 | 0.00 | 0.100887E+10 | 0.00 | 0.87 |
November | 0.265193E+09 | 0.351367E+11 | 0.00 | 45581295.34 | 0.523084E+09 | 0.00 | 0.202519E+10 | 0.00 | 0.74 |
December | 0.255524E+10 | 0.767085E+10 | 0.00 | 0.107174E+09 | 0.234718E+09 | 0.00 | 0.118282E+11 | 0.00 | 0.61 |
Annual Sum or Average | 0.140228E+11 | 0.900141E+12 | 0.00 | 0.529494E+09 | 0.790123E+11 | 0.00 | 0.575406E+11 | 0.00 | 0.74 |
Minimum of Months | 0.00 | 0.113489E+10 | 0.00 | 0.00 | 68202999.10 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.448670E+10 | 0.205871E+12 | 0.00 | 0.116291E+09 | 0.168749E+11 | 0.00 | 0.189377E+11 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.424118E+10 | 0.429195E+09 | 0.00 | 37890660.02 | 0.116180E+09 | 0.00 | 0.641721E+10 | 0.00 | 0.38 |
February | 0.230223E+10 | 0.201766E+10 | 0.00 | 42930547.71 | 0.147289E+09 | 0.00 | 0.529020E+10 | 0.00 | 0.45 |
March | 0.128960E+10 | 0.671385E+10 | 0.00 | 53301416.71 | 66499500.34 | 0.00 | 0.587333E+10 | 0.00 | 0.60 |
April | 0.342770E+09 | 0.215753E+11 | 0.00 | 28826946.13 | 0.750917E+09 | 0.00 | 0.240235E+10 | 0.00 | 0.75 |
May | 64382150.53 | 0.619490E+11 | 0.00 | 14725979.07 | 0.236123E+10 | 0.00 | 0.647267E+09 | 0.00 | 1.00 |
June | 9916198.89 | 0.113214E+12 | 0.00 | 2516471.03 | 0.351223E+10 | 0.00 | 62598971.63 | 0.00 | 1.11 |
July | 11567673.16 | 0.158449E+12 | 0.00 | 3021226.86 | 0.271949E+10 | 0.00 | 0.109147E+09 | 0.00 | 1.13 |
August | 0.00 | 0.176565E+12 | 0.00 | 0.00 | 0.398539E+10 | 0.00 | 0.00 | 0.00 | 1.18 |
September | 13433.22 | 0.119077E+12 | 0.00 | 1035163.23 | 0.529359E+10 | 0.00 | 25063556.13 | 0.00 | 1.01 |
October | 97524863.93 | 0.559487E+11 | 0.00 | 8311966.16 | 0.404036E+10 | 0.00 | 0.457750E+09 | 0.00 | 0.80 |
November | 0.225684E+09 | 0.182393E+11 | 0.00 | 20199220.69 | 0.549276E+09 | 0.00 | 0.991880E+09 | 0.00 | 0.58 |
December | 0.210000E+10 | 0.332687E+10 | 0.00 | 40211827.10 | 0.359746E+09 | 0.00 | 0.479353E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.106849E+11 | 0.737506E+12 | 0.00 | 0.252971E+09 | 0.239022E+11 | 0.00 | 0.270703E+11 | 0.00 | 0.79 |
Minimum of Months | 0.00 | 0.429195E+09 | 0.00 | 0.00 | 66499500.34 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.424118E+10 | 0.176565E+12 | 0.00 | 53301416.71 | 0.529359E+10 | 0.00 | 0.641721E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.951437E+09 | 23387540.10 | 0.00 | 2025937.45 | 25082033.98 | 9423675.51 | 0.350035E+09 | 0.00 | 0.29 |
February | 0.510031E+09 | 0.159825E+09 | 0.00 | 2934238.17 | 42739079.71 | 0.00 | 0.356135E+09 | 0.00 | 0.31 |
March | 0.334347E+09 | 0.557578E+09 | 0.00 | 4325994.91 | 30257750.13 | 0.00 | 0.434766E+09 | 0.00 | 0.39 |
April | 0.136586E+09 | 0.178896E+10 | 0.00 | 2774392.20 | 0.257100E+09 | 0.00 | 0.177373E+09 | 0.00 | 0.50 |
May | 17752645.82 | 0.611525E+10 | 0.00 | 1488241.93 | 0.694392E+09 | 0.00 | 61437225.34 | 0.00 | 0.73 |
June | 2980133.76 | 0.117259E+11 | 0.00 | 278283.13 | 0.130043E+10 | 0.00 | 6658260.73 | 0.00 | 0.83 |
July | 7006156.35 | 0.172209E+11 | 0.00 | 351509.32 | 0.120051E+10 | 0.00 | 8884387.21 | 0.00 | 0.86 |
August | 0.00 | 0.181327E+11 | 0.00 | 0.00 | 0.148616E+10 | 0.00 | 0.00 | 0.00 | 0.85 |
September | 39073.87 | 0.118848E+11 | 0.00 | 107212.59 | 0.168007E+10 | 0.00 | 1898408.27 | 0.00 | 0.74 |
October | 22004322.24 | 0.537231E+10 | 0.00 | 854811.43 | 0.109741E+10 | 0.00 | 43171325.74 | 0.00 | 0.58 |
November | 61686050.29 | 0.176418E+10 | 0.00 | 1659960.33 | 0.139198E+09 | 0.00 | 71459728.76 | 0.00 | 0.40 |
December | 0.476480E+09 | 0.250034E+09 | 0.00 | 2655114.21 | 75960746.15 | 0.00 | 0.312667E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.252035E+10 | 0.749959E+11 | 0.00 | 19455695.67 | 0.802931E+10 | 9423675.51 | 0.182448E+10 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 23387540.10 | 0.00 | 0.00 | 25082033.98 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.951437E+09 | 0.181327E+11 | 0.00 | 4325994.91 | 0.168007E+10 | 9423675.51 | 0.434766E+09 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.436173E+09 | 28180215.75 | 0.00 | 3056366.59 | 9840190.52 | 5336599.81 | 0.548387E+09 | 0.00 | 0.35 |
February | 0.225162E+09 | 0.139783E+09 | 0.00 | 3694329.54 | 14926534.89 | 0.00 | 0.491199E+09 | 0.00 | 0.40 |
March | 0.162796E+09 | 0.480101E+09 | 0.00 | 4567267.60 | 13263411.45 | 0.00 | 0.466497E+09 | 0.00 | 0.51 |
April | 68455996.04 | 0.162313E+10 | 0.00 | 3175668.84 | 0.103246E+09 | 0.00 | 0.215081E+09 | 0.00 | 0.68 |
May | 5507173.62 | 0.505433E+10 | 0.00 | 1474194.16 | 0.311484E+09 | 0.00 | 62269469.45 | 0.00 | 0.93 |
June | 1919090.60 | 0.928114E+10 | 0.00 | 230153.65 | 0.656560E+09 | 0.00 | 5402394.52 | 0.00 | 1.00 |
July | 3153084.38 | 0.134691E+11 | 0.00 | 248191.00 | 0.430375E+09 | 0.00 | 7518766.34 | 0.00 | 1.02 |
August | 0.00 | 0.145541E+11 | 0.00 | 0.00 | 0.598013E+09 | 0.00 | 0.00 | 0.00 | 1.03 |
September | 25115.81 | 0.100253E+11 | 0.00 | 91531.77 | 0.718595E+09 | 0.00 | 1563727.32 | 0.00 | 0.93 |
October | 3715953.87 | 0.487013E+10 | 0.00 | 1261202.41 | 0.485353E+09 | 0.00 | 62206068.45 | 0.00 | 0.74 |
November | 21705807.67 | 0.151799E+10 | 0.00 | 1985245.55 | 73710855.46 | 0.00 | 89675146.00 | 0.00 | 0.53 |
December | 0.224739E+09 | 0.227509E+09 | 0.00 | 2983521.70 | 35446632.47 | 0.00 | 0.372138E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.115335E+10 | 0.612708E+11 | 0.00 | 22767672.82 | 0.345081E+10 | 5336599.81 | 0.232194E+10 | 0.00 | 0.71 |
Minimum of Months | 0.00 | 28180215.75 | 0.00 | 0.00 | 9840190.52 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.436173E+09 | 0.145541E+11 | 0.00 | 4567267.60 | 0.718595E+09 | 5336599.81 | 0.548387E+09 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.494073E+09 | 92540012.33 | 0.00 | 10256583.16 | 5722802.36 | 0.00 | 0.178889E+10 | 0.00 | 0.55 |
February | 0.296179E+09 | 0.339100E+09 | 0.00 | 9287815.22 | 8005528.85 | 0.00 | 0.116622E+10 | 0.00 | 0.55 |
March | 0.245071E+09 | 0.823356E+09 | 0.00 | 8272233.12 | 15731126.54 | 0.00 | 0.818434E+09 | 0.00 | 0.56 |
April | 0.121038E+09 | 0.222461E+10 | 0.00 | 3512973.93 | 0.188242E+09 | 0.00 | 0.224323E+09 | 0.00 | 0.58 |
May | 17964271.44 | 0.607786E+10 | 0.00 | 1485894.07 | 0.709817E+09 | 0.00 | 59786436.29 | 0.00 | 0.73 |
June | 2983267.66 | 0.109736E+11 | 0.00 | 259155.65 | 0.141765E+10 | 0.00 | 6195646.14 | 0.00 | 0.79 |
July | 7124559.30 | 0.168852E+11 | 0.00 | 328232.17 | 0.126210E+10 | 0.00 | 8553314.29 | 0.00 | 0.85 |
August | 0.00 | 0.196244E+11 | 0.00 | 0.00 | 0.117889E+10 | 0.00 | 0.00 | 0.00 | 0.90 |
September | 13127.93 | 0.153999E+11 | 0.00 | 130796.70 | 0.105201E+10 | 0.00 | 2222784.67 | 0.00 | 0.90 |
October | 5501721.46 | 0.878775E+10 | 0.00 | 2356235.34 | 0.541947E+09 | 0.00 | 97884758.31 | 0.00 | 0.85 |
November | 25623290.38 | 0.325205E+10 | 0.00 | 5338778.65 | 52596536.78 | 0.00 | 0.191788E+09 | 0.00 | 0.72 |
December | 0.252894E+09 | 0.686911E+09 | 0.00 | 9744423.22 | 22161628.28 | 0.00 | 0.111999E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.146847E+10 | 0.851672E+11 | 0.00 | 50973121.25 | 0.645488E+10 | 0.00 | 0.548429E+10 | 0.00 | 0.72 |
Minimum of Months | 0.00 | 92540012.33 | 0.00 | 0.00 | 5722802.36 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.494073E+09 | 0.196244E+11 | 0.00 | 10256583.16 | 0.141765E+10 | 0.00 | 0.178889E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.462928E+09 | 36329952.92 | 0.00 | 3273375.67 | 8192401.32 | 0.00 | 0.577613E+09 | 0.00 | 0.37 |
February | 0.231128E+09 | 0.179092E+09 | 0.00 | 4050005.11 | 11623006.06 | 0.00 | 0.514077E+09 | 0.00 | 0.43 |
March | 0.144242E+09 | 0.566091E+09 | 0.00 | 5232808.19 | 4589885.03 | 0.00 | 0.545098E+09 | 0.00 | 0.57 |
April | 45765007.67 | 0.188574E+10 | 0.00 | 2966422.44 | 66423931.88 | 0.00 | 0.209274E+09 | 0.00 | 0.71 |
May | 5272314.08 | 0.558787E+10 | 0.00 | 1402774.07 | 0.210907E+09 | 0.00 | 56243564.00 | 0.00 | 0.95 |
June | 716972.52 | 0.104305E+11 | 0.00 | 230319.75 | 0.314163E+09 | 0.00 | 6334265.71 | 0.00 | 1.06 |
July | 765860.29 | 0.146977E+11 | 0.00 | 318144.43 | 0.250922E+09 | 0.00 | 11088087.99 | 0.00 | 1.08 |
August | 0.00 | 0.164234E+11 | 0.00 | 0.00 | 0.331564E+09 | 0.00 | 0.00 | 0.00 | 1.12 |
September | 17813.67 | 0.111866E+11 | 0.00 | 89659.65 | 0.464007E+09 | 0.00 | 1591172.49 | 0.00 | 0.97 |
October | 9918057.21 | 0.531539E+10 | 0.00 | 888185.74 | 0.358104E+09 | 0.00 | 42823938.87 | 0.00 | 0.78 |
November | 23433813.79 | 0.170404E+10 | 0.00 | 2143012.45 | 51866673.45 | 0.00 | 88272116.80 | 0.00 | 0.57 |
December | 0.215213E+09 | 0.302081E+09 | 0.00 | 3530940.73 | 31722655.69 | 0.00 | 0.433161E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.113940E+10 | 0.683148E+11 | 0.00 | 24125648.24 | 0.210409E+10 | 0.00 | 0.248557E+10 | 0.00 | 0.76 |
Minimum of Months | 0.00 | 36329952.92 | 0.00 | 0.00 | 4589885.03 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.462928E+09 | 0.164234E+11 | 0.00 | 5232808.19 | 0.464007E+09 | 0.00 | 0.577613E+09 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 48963212.04 | 0.00 | 6149850.87 | 0.00 | 0.00 | 0.212628E+09 | 0.00 | 0.58 |
February | 0.00 | 0.133490E+09 | 0.00 | 7634008.02 | 0.00 | 0.00 | 74737335.84 | 0.00 | 0.58 |
March | 0.00 | 0.204060E+09 | 0.00 | 12646135.78 | 0.00 | 0.00 | 57551271.17 | 0.00 | 0.59 |
April | 0.00 | 0.482599E+09 | 0.00 | 5306941.35 | 0.00 | 0.00 | 10213457.91 | 0.00 | 0.59 |
May | 0.00 | 0.834383E+09 | 0.00 | 122105.11 | 0.00 | 0.00 | 664376.41 | 0.00 | 0.59 |
June | 0.00 | 0.136880E+10 | 0.00 | 7297.98 | 0.00 | 0.00 | 1621.01 | 0.00 | 0.60 |
July | 0.00 | 0.180211E+10 | 0.00 | 12615.93 | 0.00 | 0.00 | 1717.49 | 0.00 | 0.60 |
August | 0.00 | 0.177062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.143732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.103135E+10 | 0.00 | 370489.57 | 0.00 | 0.00 | 915151.35 | 0.00 | 0.59 |
November | 0.00 | 0.533669E+09 | 0.00 | 1153739.98 | 0.00 | 0.00 | 1939828.68 | 0.00 | 0.58 |
December | 0.00 | 0.231974E+09 | 0.00 | 14611079.52 | 0.00 | 0.00 | 57517332.60 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.987934E+10 | 0.00 | 48014264.12 | 0.00 | 0.00 | 0.416170E+09 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 48963212.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.180211E+10 | 0.00 | 14611079.52 | 0.00 | 0.00 | 0.212628E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.445704E+09 | 0.00 | 47795298.37 | 0.00 | 0.00 | 0.222696E+10 | 0.00 | 0.58 |
February | 0.00 | 0.130953E+10 | 0.00 | 68282043.42 | 0.00 | 0.00 | 0.771734E+09 | 0.00 | 0.58 |
March | 0.00 | 0.203127E+10 | 0.00 | 0.118802E+09 | 0.00 | 0.00 | 0.584801E+09 | 0.00 | 0.59 |
April | 0.00 | 0.482941E+10 | 0.00 | 50832883.49 | 0.00 | 0.00 | 0.103827E+09 | 0.00 | 0.59 |
May | 0.00 | 0.827145E+10 | 0.00 | 1157517.81 | 0.00 | 0.00 | 6810406.30 | 0.00 | 0.59 |
June | 0.00 | 0.136357E+11 | 0.00 | 69059.90 | 0.00 | 0.00 | 24536.08 | 0.00 | 0.60 |
July | 0.00 | 0.179823E+11 | 0.00 | 120841.23 | 0.00 | 0.00 | 20355.55 | 0.00 | 0.60 |
August | 0.00 | 0.180457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.142437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.102674E+11 | 0.00 | 3518871.78 | 0.00 | 0.00 | 9359274.78 | 0.00 | 0.59 |
November | 0.00 | 0.531885E+10 | 0.00 | 10892992.50 | 0.00 | 0.00 | 20408172.11 | 0.00 | 0.58 |
December | 0.00 | 0.231101E+10 | 0.00 | 0.136406E+09 | 0.00 | 0.00 | 0.586183E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.986920E+11 | 0.00 | 0.437877E+09 | 0.00 | 0.00 | 0.431013E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.445704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.180457E+11 | 0.00 | 0.136406E+09 | 0.00 | 0.00 | 0.222696E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 43181680.22 | 0.00 | 3864139.65 | 0.00 | 0.00 | 0.231048E+09 | 0.00 | 0.58 |
February | 0.00 | 0.130436E+09 | 0.00 | 6419449.63 | 0.00 | 0.00 | 78657497.24 | 0.00 | 0.58 |
March | 0.00 | 0.203142E+09 | 0.00 | 11653145.76 | 0.00 | 0.00 | 58866269.22 | 0.00 | 0.59 |
April | 0.00 | 0.482626E+09 | 0.00 | 5056088.19 | 0.00 | 0.00 | 10407929.24 | 0.00 | 0.59 |
May | 0.00 | 0.830209E+09 | 0.00 | 113972.92 | 0.00 | 0.00 | 680269.30 | 0.00 | 0.59 |
June | 0.00 | 0.136556E+10 | 0.00 | 6956.81 | 0.00 | 0.00 | 2250.15 | 0.00 | 0.60 |
July | 0.00 | 0.179979E+10 | 0.00 | 11898.74 | 0.00 | 0.00 | 1921.54 | 0.00 | 0.60 |
August | 0.00 | 0.180359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.142910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.102749E+10 | 0.00 | 346719.04 | 0.00 | 0.00 | 944892.74 | 0.00 | 0.59 |
November | 0.00 | 0.531741E+09 | 0.00 | 1065022.47 | 0.00 | 0.00 | 2103691.30 | 0.00 | 0.58 |
December | 0.00 | 0.230837E+09 | 0.00 | 13306492.30 | 0.00 | 0.00 | 59110895.81 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.987770E+10 | 0.00 | 41843885.51 | 0.00 | 0.00 | 0.441824E+09 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 43181680.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.180359E+10 | 0.00 | 13306492.30 | 0.00 | 0.00 | 0.231048E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.140361E+10 | 0.00 | 0.335699E+09 | 0.00 | 0.00 | 0.443348E+10 | 0.00 | 0.66 |
February | 0.00 | 0.305897E+10 | 0.00 | 0.379925E+09 | 0.00 | 0.00 | 0.156036E+10 | 0.00 | 0.66 |
March | 0.00 | 0.440402E+10 | 0.00 | 0.598880E+09 | 0.00 | 0.00 | 0.118028E+10 | 0.00 | 0.66 |
April | 0.00 | 0.858888E+10 | 0.00 | 0.343138E+09 | 0.00 | 0.00 | 0.263835E+09 | 0.00 | 0.66 |
May | 0.00 | 0.193054E+11 | 0.00 | 5892718.61 | 0.00 | 0.00 | 14028774.03 | 0.00 | 0.66 |
June | 0.00 | 0.305325E+11 | 0.00 | 179190.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.395632E+11 | 0.00 | 929409.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.316242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 0.00 | 0.333476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 0.00 | 0.230441E+11 | 0.00 | 20788519.23 | 0.00 | 0.00 | 16258270.94 | 0.00 | 0.66 |
November | 0.00 | 0.116522E+11 | 0.00 | 53675870.64 | 0.00 | 0.00 | 33419042.16 | 0.00 | 0.66 |
December | 0.00 | 0.466786E+10 | 0.00 | 0.687086E+09 | 0.00 | 0.00 | 0.110602E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.211193E+12 | 0.00 | 0.242619E+10 | 0.00 | 0.00 | 0.860768E+10 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.140361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.395632E+11 | 0.00 | 0.687086E+09 | 0.00 | 0.00 | 0.443348E+10 | 0.00 | 0.68 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:56:28
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.254425E+12 | 0.506831E+10 | 0.00 | 0.451970E+12 | 0.138725E+13 |
February | 0.287001E+12 | 0.412120E+10 | 0.00 | 0.277455E+12 | 0.185183E+13 |
March | 0.352024E+12 | 0.182758E+10 | 0.00 | 0.152571E+12 | 0.283687E+13 |
April | 0.370350E+12 | -0.404765E+10 | 0.00 | -0.233145E+12 | 0.373333E+13 |
May | 0.376525E+12 | -0.122576E+11 | 0.00 | -0.854822E+12 | 0.375691E+13 |
June | 0.358330E+12 | -0.240750E+11 | 0.00 | -0.151385E+13 | 0.501397E+13 |
July | 0.348726E+12 | -0.328132E+11 | 0.00 | -0.208821E+13 | 0.622742E+13 |
August | 0.332050E+12 | -0.325188E+11 | 0.00 | -0.222950E+13 | 0.698283E+13 |
September | 0.290165E+12 | -0.254577E+11 | 0.00 | -0.173301E+13 | 0.472693E+13 |
October | 0.245310E+12 | -0.129908E+11 | 0.00 | -0.996307E+12 | 0.411837E+13 |
November | 0.201595E+12 | -0.275730E+10 | 0.00 | -0.261421E+12 | 0.330662E+13 |
December | 0.214930E+12 | 0.256933E+10 | 0.00 | 0.221324E+12 | 0.291457E+13 |
Annual Sum or Average | 0.363143E+13 | -0.133332E+12 | 0.00 | -0.880694E+13 | 0.468569E+14 |
Minimum of Months | 0.201595E+12 | -0.328132E+11 | 0.00 | -0.222950E+13 | 0.138725E+13 |
Maximum of Months | 0.376525E+12 | 0.506831E+10 | 0.00 | 0.451970E+12 | 0.698283E+13 |