Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 08:56:56
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 24374.61 | 526.22 | 526.22 |
Net Site Energy | 23980.28 | 517.70 | 517.70 |
Total Source Energy | 73405.09 | 1584.73 | 1584.73 |
Net Source Energy | 72156.24 | 1557.76 | 1557.76 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1047.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 958.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1721.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 268.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2089.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 249.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 360.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1721.45 |
Humidification | 1026.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.92 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 771.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 22555.46 | 1819.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4383.53 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1047.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 958.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1721.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 268.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1144.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 4.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2089.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 249.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 360.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1721.45 |
Humidification | General | 1026.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.92 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 771.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1047.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 958.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1721.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 268.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2089.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 249.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 360.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1721.45 |
Humidification | Unassigned | 1026.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.92 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 771.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 101.14 | 39.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
Other | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 486.94 | 39.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 101.14 | 39.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
Other | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 486.94 | 39.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 413.650 | 1.83 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -19.32 | -0.1 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 394.333 | 1.75 |
Electricity Coming From Utility | 22161.122 | 98.25 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 22161.122 | 98.25 |
Total On-Site and Utility Electric Sources | 22555.455 | 100.00 |
Total Electricity End Uses | 22555.455 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 4383.53 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 4383.53 | 100.00 |
Total Water End Uses | 4383.53 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 22.33 |
Time Setpoint Not Met During Occupied Cooling | 192.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5934.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.7776 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.7776 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.7776 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.7776 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.7776 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.7776 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.7776 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.7810 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-AUG-15:09 | 02-JAN-05:19 | - | - | - | - | - | - | - | - | - | - | 10-AUG-15:00 |
Heating | 0.00 | 1264816.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 364461.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 52589.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 245279.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 35877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 70839.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7280.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1693406.60 | 1272096.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1264816.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 364461.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3359.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 49008.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 221.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 245279.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 35877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 70839.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 7280.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1135.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3035.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 851.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3812.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6618.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 790.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1140.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 3251.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 836.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 71433.13 | 1971.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 24.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 65.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 142.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 24.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 70.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1542.15 | 42.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 24.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 65.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 142.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 24.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 70.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1542.15 | 42.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 4.91 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.499730 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.80 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.487107 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.53 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.27 | 0.360606 | 0.307000 | 1.62 | 0.961616 | 0.500000 | 0.001057 | 0.000352 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 49.20 | 0.386620 | 0.329000 | 16.19 | 1.00 | 0.500000 | 0.000985 | 0.008265 | 16.19 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 4.73 | 0.402440 | 0.342000 | 1.62 | 1.00 | 0.500000 | 0.000947 | 0.001576 | 2.17 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.815884 | 0.292714 | 0.249000 | 0.203155 | 0.780570 | 0.500000 | 0.001302 | 0.000183 | 0.252930 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.25 | 0.122857 | 0.104000 | 0.130282 | 0.327619 | 0.500000 | 0.003101 | 0.000133 | 0.183478 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.74 | 0.137044 | 0.116000 | 0.202152 | 0.365452 | 0.500000 | 0.002780 | 0.000234 | 0.323732 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.52 | 0.101533 | 0.086000 | 0.130360 | 0.300000 | 0.500000 | 0.003752 | 0.000085 | 0.130360 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.52 | 0.317471 | 0.270000 | 2.03 | 0.846589 | 0.500000 | 0.001200 | 0.004231 | 5.85 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 13.14 | 0.312223 | 0.500000 | 0.003254 | 0.002808 | 3.88 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 18.15 | 0.131598 | 0.112000 | 2.03 | 0.350927 | 0.500000 | 0.002895 | 0.004199 | 5.81 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 13.92 | 0.110563 | 0.094000 | 1.31 | 0.300000 | 0.500000 | 0.003446 | 0.002618 | 3.62 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.852206 | 0.280238 | 0.238000 | 0.202825 | 0.747302 | 0.500000 | 0.001360 | 0.000537 | 0.743420 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.30 | 0.118053 | 0.100000 | 0.130369 | 0.314809 | 0.500000 | 0.003227 | 0.000355 | 0.490846 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.91 | 0.124826 | 0.106000 | 0.202806 | 0.332870 | 0.500000 | 0.003052 | 0.000534 | 0.738758 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.46 | 0.105531 | 0.090000 | 0.131255 | 0.300000 | 0.500000 | 0.003610 | 0.000338 | 0.467872 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 16071.79 | 0.000352 | 448.57 |
CORE_MID VAV BOX REHEAT COIL | 377839.33 | 0.008265 | 12523.87 |
CORE_TOP VAV BOX REHEAT COIL | 72026.27 | 0.001576 | 2805.01 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8385.23 | 0.000183 | 326.52 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6078.76 | 0.000133 | 236.61 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10719.71 | 0.000234 | 417.10 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3887.42 | 0.000085 | 142.39 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 193409.92 | 0.004231 | 7516.91 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 128378.78 | 0.002808 | 4989.24 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 191970.79 | 0.004199 | 7461.06 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 119658.58 | 0.002618 | 4650.76 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 24561.10 | 0.000537 | 954.27 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 16215.77 | 0.000355 | 630.01 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 24407.32 | 0.000534 | 948.30 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15457.90 | 0.000338 | 600.59 |
VAV_BOT WITH REHEAT HEATING COIL | 43649.76 | 0.000955 | 943.36 |
VAV_MID WITH REHEAT HEATING COIL | 382353.36 | 0.008364 | 8325.32 |
VAV_TOP WITH REHEAT HEATING COIL | 36953.93 | 0.000808 | 825.92 |
CAV_BAS HEATING COIL | 240224.13 | 0.005255 | 7653.16 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.30 | 2.29 | 10.60 | 2.29 | 8.77 | 8.77 | 0.300000 | 0.260468 | 8.77 |
VAV_MID WITH REHEAT | 50.97 | 22.87 | 101.93 | 29.94 | 80.33 | 80.33 | 0.300000 | 0.372712 | 80.33 |
VAV_TOP WITH REHEAT | 5.13 | 2.28 | 10.25 | 4.61 | 9.13 | 9.13 | 0.300000 | 0.505463 | 9.13 |
CAV_BAS | 4.91 | 4.91 | 4.91 | 4.91 | 4.91 | 4.91 | 1.00 | 1.00 | 4.91 |
AIRLOOP DATACENTER BASEMENT | 21.53 | 21.53 | 21.53 | 21.53 | 21.53 | 21.53 | 1.00 | 0.999996 | 21.53 |
AIRLOOP DATACENTER BOT | 0.499730 | 0.499730 | 0.499730 | 0.499730 | 0.499730 | 0.499730 | 1.00 | 1.00 | 0.499730 |
AIRLOOP DATACENTER MID | 4.80 | 4.80 | 4.80 | 4.80 | 4.80 | 4.80 | 1.00 | 1.00 | 4.80 |
AIRLOOP DATACENTER TOP | 0.487107 | 0.487107 | 0.487107 | 0.487107 | 0.487107 | 0.487107 | 1.00 | 1.00 | 0.487107 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.77 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 80.33 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.13 | |
CAV_BAS_OA_CONTROLLER | 4.91 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.53 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.499730 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.80 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.487107 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.25 | 6.67 | 11.02 | 0.008852 | 0.008500 | 160611.33 | 0.004593 | 8.77 |
VAV_MID WITH REHEAT COOLING COIL | 25.36 | 6.67 | 11.02 | 0.008877 | 0.008500 | 1487739.83 | 0.042549 | 80.33 |
VAV_TOP WITH REHEAT COOLING COIL | 25.20 | 6.67 | 11.02 | 0.008843 | 0.008500 | 166291.99 | 0.004756 | 9.13 |
CAV_BAS COOLING COIL | 25.34 | 6.67 | 11.40 | 0.009002 | 0.008500 | 90364.07 | 0.002584 | 4.91 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.77 |
VAV_MID WITH REHEAT FAN | 80.33 |
VAV_TOP WITH REHEAT FAN | 9.13 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.004593 | 0.000104 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000955 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.042549 | 0.000011 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.008364 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.004756 | 0.000100 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000808 | |
CAV_BAS_COOLC_CONTROLLER | 0.002584 | 0.000184 |
CAV_BAS_HEATC_CONTROLLER | 0.005255 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 4.91 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.53 | 426032.26 | 305087.74 | 0.010434 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.499730 | 9658.70 | 6998.44 | 0.000237 |
AIRLOOP DATACENTER MID COOLING COIL | 4.80 | 92787.13 | 67215.49 | 0.002272 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.487107 | 9421.01 | 6823.74 | 0.000231 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.53 | 21.53 | 21.53 | 21.53 | 426032.26 | 426032.26 | 17840.03 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.499730 | 0.499730 | 0.499730 | 0.499730 | 9658.70 | 9658.70 | 824.14 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.80 | 4.80 | 4.80 | 4.80 | 92787.13 | 92787.13 | 8241.36 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.487107 | 0.487107 | 0.487107 | 0.487107 | 9421.01 | 9421.01 | 824.14 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.53 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.499730 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.80 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.487107 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.53 | 426032.26 | 0.010434 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.499730 | 9658.70 | 0.000237 |
AIRLOOP DATACENTER MID HEATING COIL | 4.80 | 92787.13 | 0.002272 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.487107 | 9421.01 | 0.000231 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 17840.03 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 824.14 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8241.36 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 824.14 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000143 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.054483 | 8807.33 | |
HEATSYS1 PUMP | 0.041831 | 12472.79 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.054483 | 6.54 |
HEATSYS1 | 0.041831 | 5.02 |
COOLSYS1_SUPPLY | 0.054483 | 6.54 |
SINGLE WATER PLANT LOOP | 0.013173 | 1.58 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.054483 | 0.054483 | 228692.34 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1912249.86 | 1912249.86 | 0.041831 |
CENTRAL BOILER | 542619.38 | 531823.91 | 0.013173 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.027241 | 3048.81 |
COOLSYS1 CHILLER2 PUMP | 0.027241 | 3048.81 |
PLANT CIRC PUMP | 0.013173 | 3326.54 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.054483 | 0.027583 | 965512.75 | 971389.37 | 0.048877 |
COOLSYS1 CHILLER2 | 0.054483 | 0.027583 | 965512.75 | 971389.37 | 0.048877 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013173 | 139666.47 | 59768.41 | 69833.23 | 7004.20 | 21463.30 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.097754 | 11.73 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.097754 | 23962.05 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 36.13 | 1153971.56 | 7.23 | 144246.44 |
TOWERWATERSYS COOLTOWER 2 | 36.13 | 1153971.56 | 7.23 | 144246.44 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.049930 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.778 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.619 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.778 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.201 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16058.301 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16058.301 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4527.754 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4527.754 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.9398 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.9084 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8967 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9335 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8058 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.29018797E-14 | 0.36812723E-16 | -0.14924019E-09 | 0.48847313E-16 |
51 | 8 | 0.21807402E-07 | 0.12652057E-12 | 0.37708831E-03 | -0.24795767E-09 |
52 | 7 | -0.12220551E-01 | 0.65729479E-08 | -0.23055577E-01 | 0.13895212E-03 |
53 | 6 | 0.40477966 | 0.22909352E-05 | 0.47160541 | -0.47410351E-02 |
54 | 5 | -5.1849947 | 0.85678555E-04 | -4.4375337 | 0.63114796E-01 |
55 | 4 | 32.978226 | 0.70190469E-03 | 21.425779 | -0.42179587 |
56 | 3 | -111.17384 | 0.15317614E-02 | -55.595241 | 1.5144378 |
57 | 2 | 197.07933 | 0.86263138E-03 | 77.848428 | -2.8998938 |
58 | 1 | -171.14541 | 0.92189209E-04 | -55.246988 | 2.7452524 |
59 | 0 | 57.057407 | 0.52547460E-06 | 15.559906 | |
60 | 9 | -0.29188985E-14 | 0.30841220E-16 | -0.15071594E-09 | 0.45756810E-16 |
61 | 8 | 0.22014798E-07 | 0.12246996E-12 | 0.37926559E-03 | -0.25031584E-09 |
62 | 7 | -0.12285514E-01 | 0.63488536E-08 | -0.23149110E-01 | 0.13969077E-03 |
63 | 6 | 0.40654483 | 0.22108485E-05 | 0.47310859 | -0.47618422E-02 |
64 | 5 | -5.2022205 | 0.82619656E-04 | -4.4490782 | 0.63328388E-01 |
65 | 4 | 33.054419 | 0.67637415E-03 | 21.470902 | -0.42280751 |
66 | 3 | -111.33595 | 0.14751306E-02 | -55.684449 | 1.5167798 |
67 | 2 | 197.23999 | 0.83027991E-03 | 77.930247 | -2.9024452 |
68 | 1 | -171.20475 | 0.88686394E-04 | -55.270783 | 2.7462925 |
69 | 0 | 57.057407 | 0.50524406E-06 | 15.555978 | |
70 | 9 | -0.57207635E-15 | 0.35733182E-16 | -0.14510758E-09 | 0.92780423E-20 |
71 | 8 | 0.21226260E-07 | 0.13767829E-12 | 0.37094976E-03 | -0.24134990E-09 |
72 | 7 | -0.12037268E-01 | 0.71989887E-08 | -0.22791647E-01 | 0.13686812E-03 |
73 | 6 | 0.39979937 | 0.25155658E-05 | 0.46736115 | -0.46823295E-02 |
74 | 5 | -5.1363910 | 0.94286903E-04 | -4.4049234 | 0.62512134E-01 |
75 | 4 | 32.763227 | 0.77396227E-03 | 21.298286 | -0.41894130 |
76 | 3 | -110.71637 | 0.16919998E-02 | -55.343173 | 1.5078286 |
77 | 2 | 196.62589 | 0.95437189E-03 | 77.617295 | -2.8926932 |
78 | 1 | -170.97790 | 0.10214201E-03 | -55.179873 | 2.7423166 |
79 | 0 | 57.057407 | 0.58311013E-06 | 15.571069 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.1581E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1604E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.0740E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.0760E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4338E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4353E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4917E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4924E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2102E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3666E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1190E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2595E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4714E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5818E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5122E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5645E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1656 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.4328E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1907 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1105 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1057 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4306E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5025E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5661E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2131E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3810E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1221E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2747E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4737E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5906E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5127E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5660E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.1578E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1602E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.0737E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.0758E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4336E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4352E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4916E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4923E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8123E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.2136E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5904E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.0559E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0969E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.2306E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2602E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2962E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4527E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2086E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0695E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9501E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1274E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5728E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6880E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7537E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6597E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.7745E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3865E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4705E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0538E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0850E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2603E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2968E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7919E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7941E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3600E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3618E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0538E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0551E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4917E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4925E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8407E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9685E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4004E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5030E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0861E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1585E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5127E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5660E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6691E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4699E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5878E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8765E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1795E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2296E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5025E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5656E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8394E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9661E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3990E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4998E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0842E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1529E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5122E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5645E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7918E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7939E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3599E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3617E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0537E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0549E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4916E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4923E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4935E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6096E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1706E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2553E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9426E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9730E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2604E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2969E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1654E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0876E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6984E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7932E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9224E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4878E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6880E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7537E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6324E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.9942E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3565E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7699E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9846E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.1141E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2601E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2961E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1623 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1238 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1806 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1426 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1183 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.4902E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.5140E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7277E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.6832E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.6077E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.2581E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.3012E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.2604E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.7796E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.6552E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7590E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.7396E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.8170E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.5184E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0086E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0755E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1989E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.5140E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7273E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.3573E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.4395E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8368E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0827E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.0308E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6676E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.6552E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7590E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1623 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1240 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1806 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1428 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1185 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5053E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.5258E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.7338E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.6874E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.6146E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.2629E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.3078E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.2712E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.7876E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.6670E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7650E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.7399E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.8215E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.5191E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0121E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0821E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2031E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.5258E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7333E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.3611E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.4460E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8411E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0889E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.0413E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6752E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.6670E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7650E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 67245.00600 | 67245.00600 | 4.90904 | 4.90904 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | -4.20000 | 2.69032E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 72249.91527 | 72249.91527 | 5.27457 | 5.27457 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 674105.27737 | 674105.27737 | 49.19669 | 49.19669 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 217193.08715 | 217193.08715 | 9.27342 | 10.77825 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 64768.94700 | 64768.94700 | 4.72628 | 4.72628 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 50466.44377 | 50466.44377 | 2.17223 | 2.17223 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 11069.35530 | 11069.35530 | 0.81588 | 0.81588 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 5880.70546 | 5880.70546 | 0.25293 | 0.25293 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 16996.16185 | 16996.16185 | 1.25272 | 1.25272 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 23.02133 | 8.81136E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 4261.41098 | 4261.41098 | 0.18348 | 0.18348 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 23643.81052 | 23643.81052 | 1.74269 | 1.74269 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 28.96667 | 8.82080E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 7511.77572 | 7511.77572 | 0.32373 | 0.32373 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 20565.76177 | 20565.76177 | 1.51581 | 1.51581 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 2598.38456 | 2598.38456 | 0.11136 | 0.11136 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 102061.42584 | 102061.42584 | 7.52260 | 7.52260 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 135409.14819 | 135409.14819 | 5.85133 | 5.85133 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 178342.64594 | 178342.64594 | 13.14490 | 13.14490 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 89877.19793 | 89877.19793 | 3.88418 | 3.88418 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 246223.91524 | 246223.91524 | 18.14818 | 18.14818 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 134403.07787 | 134403.07787 | 5.80770 | 5.80770 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 188860.96253 | 188860.96253 | 13.92016 | 13.92016 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 27.77067 | 8.81889E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 83780.78223 | 83780.78223 | 3.61984 | 3.61984 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 11562.15175 | 11562.15175 | 0.85221 | 0.85221 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 17191.82694 | 17191.82694 | 0.74342 | 0.74342 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 17687.74789 | 17687.74789 | 1.30369 | 1.30369 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 11350.25325 | 11350.25325 | 0.49085 | 0.49085 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 25958.09061 | 25958.09061 | 1.91327 | 1.91327 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 17084.31212 | 17084.31212 | 0.73876 | 0.73876 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 19786.55299 | 19786.55299 | 1.45839 | 1.45839 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 10820.34201 | 10820.34201 | 0.46787 | 0.46787 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8596.01012 | 8596.01012 | 0.49973 | 0.49973 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 25.60400 | 8.81543E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 82543.91375 | 82543.91375 | 4.79872 | 4.79872 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 25.60400 | 8.81543E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8378.85739 | 8378.85739 | 0.48711 | 0.48711 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.81585E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370366.08158 | 370366.08158 | 21.53098 | 21.53098 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 19.93600 | 8.80655E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 01:00:00 | -4.20000 | 2.69032E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 130274.06 | 8.77360 | 8.77360 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 39526.27 | 1.94933 | 1.94933 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1203868.57 | 80.33354 | 80.33354 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 409001.61 | 29.94130 | 29.94130 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 134973.18 | 9.12655 | 9.12655 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 41060.18 | 4.61313 | 4.61313 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 |
7 | CAV_BAS | Cooling | Sensible | 65237.35 | 4.90904 | 4.90904 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 63272.12 | 1.20016 | 1.20016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 365282.86 | 21.53107 | 21.53107 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 17840.03 | 0.33839 | 0.33839 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8437.09 | 0.49973 | 0.49973 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 824.14 | 1.56323E-002 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 81007.52 | 4.79872 | 4.79872 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8241.36 | 0.15632 | 0.15632 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8228.14 | 0.48711 | 0.48711 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 824.14 | 1.56323E-002 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.90904 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.27457 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36061 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30700 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61929 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96162 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05655E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.51571E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61929 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16071.79484 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.51571E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 448.56540 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 49.19669 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38662 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32900 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.18571 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.85463E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.26525E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.18571 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 377839.32595 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.26525E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 12523.86545 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.72628 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.40244 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34200 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61639 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.46726E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.57558E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.17223 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 72026.27126 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.57558E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2805.00681 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81588 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29271 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24900 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20316 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78057 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.30161E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.83427E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25293 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8385.22840 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.83427E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 326.52201 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.25272 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12286 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10400 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13028 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32762 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.10116E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.32973E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.18348 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6078.76333 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.32973E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 236.60727 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.74269 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13704 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11600 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20215 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36545 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.78012E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.34494E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32373 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10719.71376 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.34494E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 417.10451 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.51581 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10153 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.60000E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13036 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.75247E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.50373E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13036 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3887.41589 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.50373E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 142.38581 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.52260 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31747 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03110 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84659 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20011E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.23085E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.85133 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 193409.92029 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.23085E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7516.90830 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.14490 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31222 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.25409E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.80829E-003 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.88418 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 128378.78127 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.80829E-003 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4989.23853 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.14818 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13160 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11200 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03260 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35093 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.89519E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.19937E-003 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.80770 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 191970.79442 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.19937E-003 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7461.05517 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.92016 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11056 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.40000E-002 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30850 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.44601E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.61753E-003 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.61984 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 119658.57691 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.61753E-003 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4650.76240 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85221 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28024 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23800 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20282 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74730 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.35956E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.37275E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.74342 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24561.09675 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.37275E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 954.27236 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30369 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11805 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10000 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13037 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31481 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.22736E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.54720E-004 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.49085 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16215.77119 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.54720E-004 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 630.01197 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.91327 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12483 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10600 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20281 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33287 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.05224E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.33911E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.73876 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24407.32019 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.33911E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 948.30432 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.45839 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10553 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.00000E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13125 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.61031E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.38142E-004 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.46787 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15457.90176 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.38142E-004 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 600.59477 |
209 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49973 |
210 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.79872 |
211 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48711 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.53098 |
213 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.30084 |
214 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28524 |
215 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.60168 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28524 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.77360 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.77360 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.26047 |
221 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 50.96626 |
222 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.87239 |
223 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 101.93252 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 29.94130 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 80.33354 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 80.33354 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.37271 |
229 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.12692 |
230 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28364 |
231 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.25383 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.61313 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.12655 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.12655 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50546 |
237 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.90904 |
238 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.90904 |
239 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.90904 |
240 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 4.90904 |
241 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.90904 |
242 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 4.90904 |
243 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.53098 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.53098 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.53098 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.53098 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.53107 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.53107 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49973 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49973 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49973 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49973 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49973 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.49973 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.79872 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.79872 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.79872 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.79872 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.79872 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.79872 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48711 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48711 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48711 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48711 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48711 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.48711 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.77360 |
278 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 80.33354 |
279 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.12655 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 4.90904 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.53107 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.49973 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.79872 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.48711 |
285 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.77360 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.24882 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.01744 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.85215E-003 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 160611.33209 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.59346E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.77360 |
294 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 43649.75788 |
295 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.54840E-004 |
296 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 943.35935 |
297 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.77360 |
298 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.59346E-003 |
299 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.03667E-004 |
300 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.54840E-004 |
301 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 80.33354 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.36406 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.01751 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.87652E-003 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1487739.83054 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.25492E-002 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 80.33354 |
310 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 382353.36360 |
311 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.36399E-003 |
312 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 8325.32397 |
313 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 80.33354 |
314 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.25492E-002 |
315 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.11915E-005 |
316 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.36399E-003 |
317 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.12655 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.20062 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.01741 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.84318E-003 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 166291.99278 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.75593E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.12655 |
326 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 36953.92972 |
327 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.08368E-004 |
328 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 825.91910 |
329 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.12655 |
330 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.75593E-003 |
331 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.00126E-004 |
332 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.08368E-004 |
333 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.90904 |
334 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.34204 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
337 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.40164 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.00223E-003 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 90364.07453 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.58440E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 4.90904 |
343 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 240224.13486 |
344 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.25491E-003 |
345 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7653.15735 |
346 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 4.90904 |
347 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.58440E-003 |
348 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.84256E-004 |
349 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.25491E-003 |
350 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.53107 |
351 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
352 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.53107 |
353 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 426032.26046 |
354 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 305087.74336 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.04335E-002 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.53107 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.53107 |
358 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.53107 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.53107 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 426032.26046 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 426032.26046 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 17840.03233 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
364 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.53107 |
365 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.53107 |
366 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 426032.26046 |
367 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.04335E-002 |
368 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 17840.03233 |
369 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.43036E-004 |
370 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
371 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
373 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49973 |
374 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
375 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49973 |
376 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9658.70103 |
377 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6998.43946 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.36541E-004 |
379 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49973 |
380 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49973 |
381 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49973 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49973 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9658.70103 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9658.70103 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.13559 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
387 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49973 |
388 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49973 |
389 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9658.70103 |
390 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.36541E-004 |
391 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 824.13559 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.79872 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
394 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.79872 |
395 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 92787.13080 |
396 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 67215.48688 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.27235E-003 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.79872 |
399 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.79872 |
400 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.79872 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.79872 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 92787.13080 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 92787.13080 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8241.35587 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
406 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.79872 |
407 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.79872 |
408 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 92787.13080 |
409 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.27235E-003 |
410 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8241.35587 |
411 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48711 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
413 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48711 |
414 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9421.00603 |
415 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6823.73781 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.30720E-004 |
417 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48711 |
418 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48711 |
419 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48711 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48711 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9421.00603 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9421.00603 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.13559 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
425 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48711 |
426 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48711 |
427 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9421.00603 |
428 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.30720E-004 |
429 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 824.13559 |
430 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.44830E-002 |
431 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 8807.33017 |
432 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 5.44830E-002 |
433 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 6.53796 |
434 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 5.44830E-002 |
435 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 5.44830E-002 |
436 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 228692.34453 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
438 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.18305E-002 |
439 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 5.01966 |
440 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.18305E-002 |
441 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 12472.78743 |
442 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
443 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1912249.86227 |
444 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1912249.86000 |
445 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.18305E-002 |
446 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 5.44830E-002 |
447 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 6.53796 |
448 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 2.72415E-002 |
449 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3048.80585 |
450 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 2.72415E-002 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3048.80585 |
452 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.44830E-002 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.75827E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 965512.74703 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 971389.37000 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 4.88769E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.44830E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.75827E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 965512.74703 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 971389.37000 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 4.88769E-002 |
462 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.31731E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.58077 |
464 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.31731E-002 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3326.53753 |
466 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.31731E-002 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 59768.41082 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21463.29602 |
472 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 542619.37532 |
473 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 531823.91000 |
474 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.31731E-002 |
475 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
476 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
477 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
479 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
480 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 9.77538E-002 |
481 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 11.73045 |
482 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 9.77538E-002 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 23962.05450 |
484 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 36.12941 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1153971.55758 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 7.22588 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 144246.44470 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 36.12941 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1153971.55758 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 7.22588 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 144246.44470 |
492 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 4.99300E-002 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 4.99300E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 22373.57 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 526306.78 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 100233.99 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 11669.15 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8459.41 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 14917.94 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5411.61 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 269157.33 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 178657.31 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 267154.57 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 166521.85 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 34180.29 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 22566.57 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 33966.29 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 21511.89 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 47011.74 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 415892.04 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 41564.58 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 259373.21 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 201803.85 | 147053.46 | 54750.39 | 0.73 | 33794.79 | 342.77 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1857714.06 | 1350359.81 | 507354.25 | 0.73 | 308991.62 | 3133.96 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 209468.19 | 152792.08 | 56676.11 | 0.73 | 35178.89 | 356.80 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 111816.05 | 81687.75 | 30128.30 | 0.73 | 17875.41 | 181.30 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.90 | 23.54 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.90 | 23.54 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 6.4145188471E-002 | 0.1298292626 | Pass | Pass | 0.4329160839 | 2.4477706305 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.8936114970E-003 | 6.0534656684E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.1801734827E-002 | 3.1170048254E-002 | Pass | Pass | 0.3400584348 | 0.4731733837 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.0826765627E-002 | 1.0245249595E-002 | Pass | Pass | 0.6324746630 | 1.7164067340 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.6481183810E-002 | 1.5217817519E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.7771735876E-002 | 1.6668495949E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.6294922165E-002 | 1.7209210409E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.7005294574E-002 | 1.5565374770E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1546031542 | 0.1797068495 | Pass | Pass | 2.9981593664 | 14.5586121118 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1656558306 | 0.1931610570 | Pass | Pass | 3.0128057223 | 14.9374541508 | Fail | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1481982983 | 0.1742224058 | Pass | Pass | 3.0678228295 | 14.2688509911 | Fail | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.2344596957E-002 | 7.6935890802E-002 | Pass | Pass | 6.2236231243 | 41.1713888058 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2803705667 | 0.2754359147 | Pass | Pass | 19.5999306511 | 80.5298369541 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2998515868 | 0.2909756594 | Pass | Pass | 19.3035628914 | 67.6751335490 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2823446867 | 0.2780555009 | Pass | Pass | 26.3665597619 | 109.1622246396 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1821701513 | 0.1973068238 | Pass | Pass | 55.0901701814 | 263.7527139855 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.2102228519E-003 | 4.6287860001E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.0471121441E-002 | 2.2960811111E-002 | Pass | Pass | 0.3368595509 | 0.4481172459 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.2739204743E-002 | 4.6565226506E-002 | Pass | Pass | 0.4532959273 | 0.4789692027 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.2225685609E-006 | 6.7946467661E-006 | Pass | Pass | 1.7870391929E-003 | 1.4427657550E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.8297020149E-003 | 3.8124498488E-003 | Pass | Pass | 1.2761369992E-003 | 1.0185285217E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.8881505413E-003 | 4.2442568666E-003 | Pass | Pass | 1.7216874912E-003 | 1.3731866800E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.9178240682E-006 | 2.0393062593E-006 | Pass | Pass | 3.0102828436E-005 | 1.0887054917E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5699.61 | 194.87 | 0.00 | 28596.26 | 6617.25 | 41108.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
North Total or Average | 1390.74 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.062 | 0.360 | 0.396 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.7776 | 2779.43 | 16058.30 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 116.04 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.7776 | 24961.20 | 144214.83 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 1042.11 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.78 | 0.0000 | Y | 7.74 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.57 | 0.0000 | Y | 4.94 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.37 | 0.0000 | Y | 7.60 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.53 | 0.0000 | Y | 4.93 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.7776 | 3134.13 | 18107.61 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.73 | 0.0000 | Y | 77.27 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.54 | 0.0000 | Y | 49.37 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.7776 | 3134.20 | 18108.01 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.35 | 0.0000 | Y | 75.98 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.49 | 0.0000 | Y | 49.26 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.73 | 0.0000 | Y | 7.73 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.54 | 0.0000 | Y | 4.94 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.35 | 0.0000 | Y | 7.60 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.49 | 0.0000 | Y | 4.93 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.7776 | 783.68 | 4527.75 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.66 | 0.0000 | Y | 32.85 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 7.1736 | 362.03 | 2597.04 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 16.76 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
Interior Lighting Total | 5.7907 | 46320.38 | 268225.21 | 542.16 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12952.94 | AstronomicalClock | - | 42.59 | 42.59 | 103.56 | |
EXTERIOR_LIGHTS_B | 919.74 | AstronomicalClock | - | 83.55 | 63.07 | 10.89 | |
EXTERIOR_LIGHTS_C | 17215.91 | AstronomicalClock | - | 83.55 | 47.80 | 154.47 | |
Exterior Lighting Total | 31088.59 | 268.92 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 1899139.64 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1912249.86 | 0.94 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 971389.37 | 5.60 | 941158.61 | 4.71 | 6.90 | 23.54 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 971389.37 | 5.60 | 941158.61 | 4.71 | 6.90 | 23.54 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 531823.91 | 0.94 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1153971.56 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1153971.56 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 160611.33 | 201803.85 | 147053.46 | 54750.39 | 0.73 | - | 33794.79 | 342.77 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1487739.83 | 1857714.06 | 1350359.81 | 507354.25 | 0.73 | - | 308991.62 | 3133.96 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 166291.99 | 209468.19 | 152792.08 | 56676.11 | 0.73 | - | 35178.89 | 356.80 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 90364.07 | 111816.05 | 81687.75 | 30128.30 | 0.73 | - | 17875.41 | 181.30 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 426032.26 | 305087.74 | 120944.52 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9658.70 | 6998.44 | 2660.26 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 92787.13 | 67215.49 | 25571.64 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9421.01 | 6823.74 | 2597.27 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 16071.79 | 22373.57 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 377839.33 | 526306.78 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 72026.27 | 100233.99 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 8385.23 | 11669.15 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 6078.76 | 8459.41 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10719.71 | 14917.94 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3887.42 | 5411.61 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 193409.92 | 269157.33 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 128378.78 | 178657.31 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 191970.79 | 267154.57 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 119658.58 | 166521.85 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 24561.10 | 34180.29 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 16215.77 | 22566.57 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 24407.32 | 33966.29 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 15457.90 | 21511.89 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 43649.76 | 47011.74 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 382353.36 | 415892.04 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 36953.93 | 41564.58 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 240224.13 | 259373.21 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 426032.26 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9658.70 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 92787.13 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9421.01 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 17840.03 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 824.14 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8241.36 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 824.14 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.77 | 18959.27 | 2160.95 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 80.33 | 173596.50 | 2160.95 | 1.00 | 1.08 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.13 | 19721.98 | 2160.95 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 4.91 | 8324.04 | 1695.65 | 1.00 | 1.16 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.53 | 35697.93 | 1657.97 | 1.00 | 1.13 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 559.75 | 1120.11 | 1.00 | 1.61 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.80 | 5375.09 | 1120.11 | 1.00 | 1.16 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 545.61 | 1120.11 | 1.00 | 1.62 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.054483 | 8807.33 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.041831 | 12472.79 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.027241 | 3048.81 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.027241 | 3048.81 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013173 | 3326.54 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.097754 | 23962.05 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 67245.01 | 67245.01 | 24.19 | 4.909 | 4.909 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00902 | 21.70 | 0.00881 | 1.200 | 0.00 |
CORE_BOTTOM | 72249.92 | 72249.92 | 28.94 | 5.275 | 5.275 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 21.70 | 0.00881 | 1.078 | 0.00 |
CORE_MID | 674105.28 | 674105.28 | 270.06 | 49.197 | 49.197 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 21.70 | 0.00881 | 10.778 | 0.00 |
CORE_TOP | 64768.95 | 64768.95 | 25.95 | 4.726 | 4.726 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00898 | 21.70 | 0.00881 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11069.36 | 11069.36 | 35.32 | 0.816 | 0.816 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00884 | 29.40 | 0.00882 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 16996.16 | 16996.16 | 84.15 | 1.253 | 1.253 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00865 | 23.02 | 0.00881 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 23643.81 | 23643.81 | 75.44 | 1.743 | 1.743 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00866 | 28.97 | 0.00882 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 20565.76 | 20565.76 | 101.82 | 1.516 | 1.516 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00862 | 27.94 | 0.00882 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 102061.43 | 102061.43 | 325.65 | 7.523 | 7.523 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00887 | 29.40 | 0.00882 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 178342.65 | 178342.65 | 882.99 | 13.145 | 13.145 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00864 | 23.68 | 0.00881 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 246223.92 | 246223.92 | 785.60 | 18.148 | 18.148 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00866 | 29.14 | 0.00882 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 188860.96 | 188860.96 | 935.07 | 13.920 | 13.920 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00864 | 27.77 | 0.00882 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 11562.15 | 11562.15 | 36.89 | 0.852 | 0.852 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00883 | 29.40 | 0.00882 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 17687.75 | 17687.75 | 87.57 | 1.304 | 1.304 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00864 | 23.68 | 0.00881 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 25958.09 | 25958.09 | 82.82 | 1.913 | 1.913 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00865 | 29.14 | 0.00882 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 19786.55 | 19786.55 | 97.97 | 1.458 | 1.458 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00863 | 27.94 | 0.00882 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8596.01 | 8596.01 | 237.44 | 0.500 | 0.500 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00858 | 25.60 | 0.00882 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 82543.91 | 82543.91 | 2280.05 | 4.799 | 4.799 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 25.60 | 0.00882 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8378.86 | 8378.86 | 231.44 | 0.487 | 0.487 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 25.86 | 0.00882 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370366.08 | 370366.08 | 472.60 | 21.531 | 21.531 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 19.94 | 0.00881 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | 21.00 | 24.53 | 0.00269 | -4.20 | 0.00269 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | 19.60 | 22.17 | 0.00269 | -4.20 | 0.00269 | 1.078 | 0.00 |
CORE_MID | 217193.09 | 217193.09 | 87.01 | 9.273 | 10.778 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 10.778 | 0.00 |
CORE_TOP | 50466.44 | 50466.44 | 20.22 | 2.172 | 2.172 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 5880.71 | 5880.71 | 18.76 | 0.253 | 0.253 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00688 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 4261.41 | 4261.41 | 21.10 | 0.183 | 0.183 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00703 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 7511.78 | 7511.78 | 23.97 | 0.324 | 0.324 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00725 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 2598.38 | 2598.38 | 12.86 | 0.111 | 0.111 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00613 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 135409.15 | 135409.15 | 432.05 | 5.851 | 5.851 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00744 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 89877.20 | 89877.20 | 444.99 | 3.884 | 3.884 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00744 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 134403.08 | 134403.08 | 428.83 | 5.808 | 5.808 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00743 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 83780.78 | 83780.78 | 414.81 | 3.620 | 3.620 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00739 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 17191.83 | 17191.83 | 54.85 | 0.743 | 0.743 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00747 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 11350.25 | 11350.25 | 56.20 | 0.491 | 0.491 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00747 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 17084.31 | 17084.31 | 54.51 | 0.739 | 0.739 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00747 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 10820.34 | 10820.34 | 53.57 | 0.468 | 0.468 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00744 | -4.20 | 0.00269 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 18.00 | 26.68 | 0.00850 | -4.20 | 0.00269 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 23.34 | 0.00490 | -4.20 | 0.00269 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 21.76 | 0.00310 | -4.20 | 0.00269 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 01:00:00 | 18.00 | 27.00 | 0.00850 | -4.20 | 0.00269 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 8.77 | 8.77 | 1.95 | 1.95 | 8.7736 | 2.2852 | 8.7736 | 0.2605 | 0.3000 |
VAV_MID WITH REHEAT | 80.33 | 80.33 | 29.94 | 29.94 | 80.3335 | 29.9413 | 80.3335 | 0.3727 | 0.3000 |
VAV_TOP WITH REHEAT | 9.13 | 9.13 | 4.61 | 4.61 | 9.1265 | 4.6131 | 9.1265 | 0.5055 | 0.3000 |
CAV_BAS | 4.91 | 4.91 | 1.20 | 1.20 | 4.9090 | 4.9090 | 4.9090 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.53 | 21.53 | 0.34 | 0.34 | 21.5311 | 21.5310 | 21.5311 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.50 | 0.50 | 0.02 | 0.02 | 0.4997 | 0.4997 | 0.4997 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.80 | 4.80 | 0.16 | 0.16 | 4.7987 | 4.7987 | 4.7987 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.49 | 0.49 | 0.02 | 0.02 | 0.4871 | 0.4871 | 0.4871 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 16071.795 | 16071.795 | 1.619294 | 0.00035157 | 448.565 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | 16071.79 | 16071.79 | 1.619294 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 16099.38 | 16099.38 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 377839.326 | 377839.326 | 16.185710 | 0.00826525 | 12523.865 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 377839.33 | 377839.33 | 16.185710 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 217193.09 | 0.00 | 378775.06 | 378775.06 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 72026.271 | 72026.271 | 2.172235 | 0.00157558 | 2805.007 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 72026.27 | 72026.27 | 2.172235 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 50466.44 | 0.00 | 72179.60 | 72179.60 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 8385.228 | 8385.228 | 0.252930 | 0.00018343 | 326.522 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8385.23 | 8385.23 | 0.252930 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00687641 | 43.9043 | 5880.71 | 0.00 | 8403.08 | 8403.08 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6078.763 | 6078.763 | 0.183478 | 0.00013297 | 236.607 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6078.76 | 6078.76 | 0.183478 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00703356 | 44.8961 | 4261.41 | 0.00 | 6091.71 | 6091.71 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 10719.714 | 10719.714 | 0.323732 | 0.00023449 | 417.105 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10719.71 | 10719.71 | 0.323732 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00724625 | 46.2372 | 7511.78 | 0.00 | 10742.54 | 10742.54 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3887.416 | 3887.416 | 0.130360 | 0.00008504 | 142.386 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3887.42 | 3887.42 | 0.130360 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00612662 | 39.1642 | 2598.38 | 0.00 | 3896.13 | 3896.13 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 193409.920 | 193409.920 | 5.851334 | 0.00423085 | 7516.908 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 193409.92 | 193409.92 | 5.851334 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00743762 | 47.4446 | 135409.15 | 0.00 | 193821.83 | 193821.83 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 128378.781 | 128378.781 | 3.884181 | 0.00280829 | 4989.239 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 128378.78 | 128378.78 | 3.884181 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00743971 | 47.4578 | 89877.20 | 0.00 | 128652.20 | 128652.20 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 191970.794 | 191970.794 | 5.807700 | 0.00419937 | 7461.055 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 191970.79 | 191970.79 | 5.807700 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00743282 | 47.4143 | 134403.08 | 0.00 | 192379.64 | 192379.64 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 119658.577 | 119658.577 | 3.619839 | 0.00261753 | 4650.762 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 119658.58 | 119658.58 | 3.619839 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00739147 | 47.1540 | 83780.78 | 0.00 | 119913.42 | 119913.42 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 24561.097 | 24561.097 | 0.743420 | 0.00053727 | 954.272 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24561.10 | 24561.10 | 0.743420 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00746934 | 47.6453 | 17191.83 | 0.00 | 24613.41 | 24613.41 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 16215.771 | 16215.771 | 0.490846 | 0.00035472 | 630.012 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16215.77 | 16215.77 | 0.490846 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00746540 | 47.6206 | 11350.25 | 0.00 | 16250.31 | 16250.31 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 24407.320 | 24407.320 | 0.738758 | 0.00053391 | 948.304 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24407.32 | 24407.32 | 0.738758 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00746616 | 47.6252 | 17084.31 | 0.00 | 24459.31 | 24459.31 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 15457.902 | 15457.902 | 0.467872 | 0.00033814 | 600.595 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15457.90 | 15457.90 | 0.467872 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00744006 | 47.4610 | 10820.34 | 0.00 | 15490.83 | 15490.83 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 160611.332 | -999.000 | 8.773595 | 0.00459346 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 160611.33 | 151036.61 | 8.773595 | 25.25 | 16.98 | 0.00885215 | 11.02 | 11.02 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 23.1433 | 24.00 | 0.00886138 | 46.9976 | 119033.57 | 0.00 | 162552.62 | 147208.66 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 43649.758 | 43649.758 | 2.632079 | 0.00095484 | 943.359 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 43649.76 | 43649.76 | 2.632079 | -1.10 | -1.68 | 0.00312569 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 77.1444 | 21.42 | 0.00548528 | 34.2102 | 20252.28 | 0.00 | 40951.51 | 40951.51 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1487739.831 | -999.000 | 80.333540 | 0.04254917 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 1487739.83 | 1394022.94 | 80.333540 | 25.36 | 17.04 | 0.00887652 | 11.02 | 11.02 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 25.2771 | 24.00 | 0.00889514 | 47.1742 | 1089903.92 | 0.00 | 1505520.59 | 1359031.53 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 382353.364 | 382353.364 | 24.100062 | 0.00836399 | 8325.324 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 382353.36 | 382353.36 | 24.100062 | -0.50 | -0.87 | 0.00343043 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 84.2570 | 19.60 | 0.00683535 | 47.5751 | 283404.11 | 0.00 | 362304.04 | 362304.04 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 166291.993 | -999.000 | 9.126548 | 0.00475593 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 166291.99 | 156585.09 | 9.126548 | 25.20 | 16.95 | 0.00884318 | 11.02 | 11.02 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 22.2483 | 24.00 | 0.00884938 | 46.9349 | 123806.49 | 0.00 | 168311.31 | 152602.27 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 36953.930 | 36953.930 | 2.737964 | 0.00080837 | 825.919 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 36953.93 | 36953.93 | 2.737964 | 1.48 | 0.97 | 0.00389886 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 74.1609 | 17.60 | 0.00686021 | 54.1387 | 31634.91 | 0.00 | 36212.77 | 36212.77 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 90364.075 | -999.000 | 4.909040 | 0.00258440 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 90364.07 | 82917.09 | 4.909040 | 25.34 | 17.13 | 0.00900223 | 11.40 | 11.39 | 0.00850000 | 28.88 | 0.00882066 | 18.17 | 24.4479 | 24.00 | 0.00907118 | 48.0947 | 59164.59 | 0.00 | 91440.92 | 81808.49 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 240224.135 | 240224.135 | 4.909040 | 0.00525491 | 7653.157 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 240224.13 | 240224.13 | 4.909040 | -1.03 | -2.32 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 24.4479 | 24.58 | 0.00269032 | 13.9122 | 0.00 | 0.00 | 186078.06 | 186078.06 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 426032.260 | 305087.743 | 21.531067 | 0.01043350 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 396346.04 | 393646.07 | -999.0 | 28.46 | 17.81 | 0.00854680 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | -999.0000 | 27.00 | 0.00854241 | 37.9343 | 370035.08 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9658.701 | 6998.439 | 0.499730 | 0.00023654 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 8950.16 | 8828.03 | -999.0 | 27.91 | 17.67 | 0.00859145 | 12.80 | 11.97 | 0.00850000 | 25.60 | 0.00881543 | 17.07 | -999.0000 | 27.00 | 0.00858421 | 38.1149 | 8596.01 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92787.131 | 67215.487 | 4.798721 | 0.00227235 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 85986.07 | 84766.15 | -999.0 | 27.91 | 17.67 | 0.00859512 | 12.80 | 11.97 | 0.00850000 | 25.60 | 0.00881543 | 17.07 | -999.0000 | 27.00 | 0.00858770 | 38.1303 | 82543.91 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9421.006 | 6823.738 | 0.487107 | 0.00023072 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 8730.88 | 8609.14 | -999.0 | 27.92 | 17.67 | 0.00859351 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00881585 | 17.16 | -999.0000 | 27.00 | 0.00858614 | 38.1234 | 8378.86 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 426032.260 | 426032.260 | 21.531067 | 0.01043350 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 426032.26 | 426032.26 | 21.531067 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5716 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9658.701 | 9658.701 | 0.499730 | 0.00023654 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9658.70 | 9658.70 | 0.499730 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1282 | 26.95 | 0.00850000 | 37.8463 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92787.131 | 92787.131 | 4.798721 | 0.00227235 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 92787.13 | 92787.13 | 4.798721 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2576 | 24.52 | 0.00490429 | 25.3700 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9421.006 | 9421.006 | 0.487107 | 0.00023072 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9421.01 | 9421.01 | 0.487107 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2092 | 23.52 | 0.00310462 | 17.1052 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 17840.032 | 17840.032 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17840.03 | 17840.03 | 21.531067 | -0.07 | -0.07 | 0.00840869 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5716 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.14 | 824.14 | 0.499730 | -0.13 | -0.13 | 0.00831826 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1282 | 26.95 | 0.00850000 | 37.8463 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8241.356 | 8241.356 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8241.36 | 8241.36 | 4.798721 | -0.14 | -0.14 | 0.00483217 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2576 | 24.52 | 0.00490429 | 25.3700 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.14 | 824.14 | 0.487107 | -0.13 | -1.19 | 0.00309132 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2092 | 23.52 | 0.00310462 | 17.1052 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 16071.795 | 16071.795 | 1.619294 | 0.00035157 | 448.565 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 0.8239 | 0.840465 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | Sensible | 16071.79 | 16071.79 | 1.0000 | 1.92208756 | 1.619294 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.35153509 | 60.00 | 48.89 | 11.11 | 0.000 | 16071.79 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 16099.38 | 16099.38 | 1.92208756 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 377839.326 | 377839.326 | 16.185710 | 0.00826525 | 12523.865 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 19.3691 | 19.758889 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 377839.33 | 377839.33 | 1.0000 | 19.21228818 | 16.185710 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 8.26440261 | 60.00 | 48.89 | 11.11 | 0.000 | 377839.33 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.89 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 217193.09 | 0.00 | 378775.06 | 378775.06 | 19.21228818 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.13 | 18.74 | 0.00800000 | 52775.1 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 72026.271 | 72026.271 | 2.172235 | 0.00157558 | 2805.007 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 3.6923 | 3.766572 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 72026.27 | 72026.27 | 1.0000 | 2.57842242 | 2.172235 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 1.57541596 | 60.00 | 48.89 | 11.11 | 0.000 | 72026.27 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 50466.44 | 0.00 | 72179.60 | 72179.60 | 2.57842242 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.26 | 0.00800000 | 61053.5 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8385.228 | 8385.228 | 0.252930 | 0.00018343 | 326.522 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 0.4298 | 0.438501 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8385.23 | 8385.23 | 1.0000 | 0.30022566 | 0.252930 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.18340839 | 60.00 | 48.89 | 11.11 | 0.000 | 8385.23 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.92 | 0.00687641 | 21.00 | 0.00687641 | 43.9043 | 5880.71 | 0.00 | 8403.08 | 8403.08 | 0.30022566 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.26 | 0.00800000 | 61049.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6078.763 | 6078.763 | 0.183478 | 0.00013297 | 236.607 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 0.3116 | 0.317885 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6078.76 | 6078.76 | 1.0000 | 0.21778710 | 0.183478 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.13295955 | 60.00 | 48.89 | 11.11 | 0.000 | 6078.76 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00703356 | 21.00 | 0.00703356 | 44.8961 | 4261.41 | 0.00 | 6091.71 | 6091.71 | 0.21778710 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61030.7 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10719.714 | 10719.714 | 0.323732 | 0.00023449 | 417.105 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 0.5495 | 0.560581 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10719.71 | 10719.71 | 1.0000 | 0.38426678 | 0.323732 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.23447012 | 60.00 | 48.89 | 11.11 | 0.000 | 10719.71 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00724625 | 21.00 | 0.00724625 | 46.2372 | 7511.78 | 0.00 | 10742.54 | 10742.54 | 0.38426678 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61015.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3887.416 | 3887.416 | 0.130360 | 0.00008504 | 142.386 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 0.1993 | 0.203290 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 3887.42 | 3887.42 | 1.0000 | 0.15473602 | 0.130360 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08502866 | 60.00 | 48.89 | 11.11 | 0.000 | 3887.42 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.87 | 0.00612662 | 21.00 | 0.00612662 | 39.1642 | 2598.38 | 0.00 | 3896.13 | 3896.13 | 0.15473602 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.49 | 20.43 | 0.00800000 | 58239.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 193409.920 | 193409.920 | 5.851334 | 0.00423085 | 7516.908 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 9.9147 | 10.114260 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 193409.92 | 193409.92 | 1.0000 | 6.94547906 | 5.851334 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 4.23041579 | 60.00 | 48.89 | 11.11 | 0.000 | 193409.92 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00743762 | 21.00 | 0.00743762 | 47.4446 | 135409.15 | 0.00 | 193821.83 | 193821.83 | 6.94547906 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60966.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 128378.781 | 128378.781 | 3.884181 | 0.00280829 | 4989.239 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 6.5810 | 6.713494 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 128378.78 | 128378.78 | 1.0000 | 4.61048763 | 3.884181 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 2.80800293 | 60.00 | 48.89 | 11.11 | 0.000 | 128378.78 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00743971 | 21.00 | 0.00743971 | 47.4578 | 89877.20 | 0.00 | 128652.20 | 128652.20 | 4.61048763 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60964.1 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 191970.794 | 191970.794 | 5.807700 | 0.00419937 | 7461.055 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 9.8409 | 10.039002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 191970.79 | 191970.79 | 1.0000 | 6.89368654 | 5.807700 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 4.19893808 | 60.00 | 48.89 | 11.11 | 0.000 | 191970.79 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00743282 | 21.00 | 0.00743282 | 47.4143 | 134403.08 | 0.00 | 192379.64 | 192379.64 | 6.89368654 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60966.5 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 119658.577 | 119658.577 | 3.619839 | 0.00261753 | 4650.762 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 6.1340 | 6.257476 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 119658.58 | 119658.58 | 1.0000 | 4.29671594 | 3.619839 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 2.61726768 | 60.00 | 48.89 | 11.11 | 0.000 | 119658.58 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00739147 | 21.00 | 0.00739147 | 47.1540 | 83780.78 | 0.00 | 119913.42 | 119913.42 | 4.29671594 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60968.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24561.097 | 24561.097 | 0.743420 | 0.00053727 | 954.272 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 1.2591 | 1.284408 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 24561.10 | 24561.10 | 1.0000 | 0.88243276 | 0.743420 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.53721987 | 60.00 | 48.89 | 11.11 | 0.000 | 24561.10 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00746934 | 21.00 | 0.00746934 | 47.6453 | 17191.83 | 0.00 | 24613.41 | 24613.41 | 0.88243276 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60952.5 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16215.771 | 16215.771 | 0.490846 | 0.00035472 | 630.012 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 0.8313 | 0.847994 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16215.77 | 16215.77 | 1.0000 | 0.58262917 | 0.490846 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.35468426 | 60.00 | 48.89 | 11.11 | 0.000 | 16215.77 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00746540 | 21.00 | 0.00746540 | 47.6206 | 11350.25 | 0.00 | 16250.31 | 16250.31 | 0.58262917 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60951.2 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24407.320 | 24407.320 | 0.738758 | 0.00053391 | 948.304 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 1.2512 | 1.276367 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 24407.32 | 24407.32 | 1.0000 | 0.87689835 | 0.738758 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.53385634 | 60.00 | 48.89 | 11.11 | 0.000 | 24407.32 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00746616 | 21.00 | 0.00746616 | 47.6252 | 17084.31 | 0.00 | 24459.31 | 24459.31 | 0.87689835 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60952.8 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15457.902 | 15457.902 | 0.467872 | 0.00033814 | 600.595 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 0.7924 | 0.808362 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15457.90 | 15457.90 | 1.0000 | 0.55535984 | 0.467872 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.33810754 | 60.00 | 48.89 | 11.11 | 0.000 | 15457.90 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00744006 | 21.00 | 0.00744006 | 47.4610 | 10820.34 | 0.00 | 15490.83 | 15490.83 | 0.55535984 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60953.1 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 160611.332 | -999.000 | 8.773595 | 0.00459346 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2957 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.773595 | 10.41417661 | 4197.9300 | 999.8980 | 54.47740780 | 15.00 | 6.67 | 8.33 | 1905007.23 | 8.4310 | 8.431009 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 160611.33 | 151036.61 | 1.0000 | 10.41417661 | 8.773595 | 25.25 | 16.98 | 0.00885215 | 47925.2 | 11.02 | 11.02 | 0.00850000 | 32502.8 | 4.59299519 | 6.67 | 15.00 | 8.33 | 18959.272 | 141652.06 | 29.40 | 0.00882150 | 18.34 | 2.03050000 | 23.1433 | 24.00 | 0.00886138 | 24.00 | 0.00886138 | 46.9976 | 119033.57 | 0.00 | 162552.62 | 147208.66 | 10.41417661 | 25.25 | 17.13 | 0.00885215 | 47925.2 | 11.41 | 11.28 | 0.00826798 | 32316.4 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 43649.758 | 43649.758 | 2.632079 | 0.00095484 | 943.359 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.773595 | 10.41417661 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 2.2376 | 2.282639 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 43649.76 | 43649.76 | 1.0000 | 3.12425298 | 2.632079 | -1.10 | -1.68 | 0.00312569 | 6701.7 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.95474226 | 60.00 | 48.89 | 11.11 | 0.000 | 43649.76 | -4.20 | 0.00269032 | -4.20 | 2.03050000 | 77.1444 | 9.35 | 0.00459521 | 21.42 | 0.00548528 | 34.2102 | 20252.28 | 0.00 | 40951.51 | 40951.51 | 3.12425298 | 2.80 | 0.71 | 0.00312569 | 10647.0 | 15.77 | 7.58 | 0.00312569 | 23754.6 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1487739.831 | -999.000 | 80.333540 | 0.04254917 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3410 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 80.333540 | 95.35517214 | 4197.9300 | 999.8980 | 54.47740780 | 15.00 | 6.67 | 8.33 | 1905007.23 | 78.0963 | 78.096283 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 1487739.83 | 1394022.94 | 1.0000 | 95.35517214 | 80.333540 | 25.36 | 17.04 | 0.00887652 | 48105.0 | 11.02 | 11.02 | 0.00850000 | 32502.9 | 42.54483037 | 6.67 | 15.00 | 8.33 | 173596.503 | 1314143.33 | 29.40 | 0.00882150 | 18.34 | 20.30600000 | 25.2771 | 24.00 | 0.00889514 | 24.00 | 0.00889514 | 47.1742 | 1089903.92 | 0.00 | 1505520.59 | 1359031.53 | 95.35517214 | 25.36 | 17.19 | 0.00887652 | 48105.0 | 11.41 | 11.28 | 0.00826742 | 32316.4 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 382353.364 | 382353.364 | 24.100062 | 0.00836399 | 8325.324 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 80.333540 | 95.35517214 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 19.6005 | 19.994948 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 382353.36 | 382353.36 | 1.0000 | 28.60655164 | 24.100062 | -0.50 | -0.87 | 0.00343043 | 8072.4 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 8.36313724 | 60.00 | 48.89 | 11.11 | 0.000 | 382353.36 | -4.20 | 0.00269032 | -4.20 | 20.30600000 | 84.2570 | 19.29 | 0.00739155 | 19.60 | 0.00683535 | 47.5751 | 283404.11 | 0.00 | 362304.04 | 362304.04 | 28.60655164 | 2.80 | 1.14 | 0.00343043 | 11410.7 | 15.32 | 7.72 | 0.00343043 | 24075.8 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 166291.993 | -999.000 | 9.126548 | 0.00475593 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2790 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.126548 | 10.83312852 | 4197.9300 | 999.8980 | 54.47740780 | 15.00 | 6.67 | 8.33 | 1905007.23 | 8.7292 | 8.729205 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 166291.99 | 156585.09 | 1.0000 | 10.83312852 | 9.126548 | 25.20 | 16.95 | 0.00884318 | 47853.1 | 11.02 | 11.02 | 0.00850000 | 32502.8 | 4.75544479 | 6.67 | 15.00 | 8.33 | 19721.984 | 146570.01 | 29.40 | 0.00882150 | 18.34 | 2.03050000 | 22.2483 | 24.00 | 0.00884938 | 24.00 | 0.00884938 | 46.9349 | 123806.49 | 0.00 | 168311.31 | 152602.27 | 10.83312852 | 25.20 | 17.10 | 0.00884318 | 47853.1 | 11.41 | 11.28 | 0.00826824 | 32316.4 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 36953.930 | 36953.930 | 2.737964 | 0.00080837 | 825.919 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.126548 | 10.83312852 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 1.8944 | 1.932484 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 36953.93 | 36953.93 | 1.0000 | 3.24993855 | 2.737964 | 1.48 | 0.97 | 0.00389886 | 11253.1 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.80828578 | 60.00 | 48.89 | 11.11 | 0.000 | 36953.93 | -4.20 | 0.00269032 | -4.20 | 2.03050000 | 74.1609 | 17.80 | 0.00736751 | 17.60 | 0.00686021 | 54.1387 | 31634.91 | 0.00 | 36212.77 | 36212.77 | 3.24993855 | 2.80 | 1.80 | 0.00389886 | 12584.7 | 13.81 | 7.55 | 0.00389886 | 23727.3 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 90364.075 | -999.000 | 4.909040 | 0.00258440 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5747 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:ConstantVolume | 4.909040 | 5.82698536 | 4197.9300 | 999.8980 | 54.47740780 | 15.00 | 6.67 | 8.33 | 1905007.23 | 4.7435 | 4.743503 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 90364.07 | 82917.09 | 1.0000 | 5.82698536 | 4.909040 | 25.34 | 17.13 | 0.00900223 | 48402.8 | 11.40 | 11.39 | 0.00850000 | 32895.0 | 2.58413746 | 6.67 | 15.00 | 8.33 | 8324.035 | 82040.04 | 28.88 | 0.00882066 | 18.17 | 1.20015641 | 24.4479 | 24.00 | 0.00907118 | 24.00 | 0.00907118 | 48.0947 | 59164.59 | 0.00 | 91440.92 | 81808.49 | 5.82698536 | 25.34 | 17.28 | 0.00900223 | 48402.8 | 11.60 | 11.44 | 0.00834690 | 32710.2 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 240224.135 | 240224.135 | 4.909040 | 0.00525491 | 7653.157 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:ConstantVolume | 4.909040 | 5.82698536 | 4197.9300 | 999.8980 | 41.82625173 | 48.89 | 60.00 | 11.11 | 1950734.65 | 12.3145 | 12.562382 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 240224.13 | 240224.13 | 1.0000 | 5.82698536 | 4.909040 | -1.03 | -2.32 | 0.00269032 | 5691.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 5.25437357 | 60.00 | 48.89 | 11.11 | 0.000 | 240224.13 | -4.20 | 0.00269032 | -4.20 | 1.20015641 | 24.4479 | 0.00 | 0.00269032 | 24.58 | 0.00269032 | 13.9122 | 0.00 | 0.00 | 186078.06 | 186078.06 | 5.82698536 | 12.80 | 5.58 | 0.00269032 | 19654.3 | 44.42 | 18.50 | 0.00269032 | 51588.1 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 426032.260 | 305087.743 | 21.531067 | 0.01043350 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7281 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 396346.04 | 393646.07 | 0.9303 | -999.0 | -999.0 | 28.46 | 17.81 | 0.00854680 | 50420.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 396346.04 | 29.40 | 0.00882150 | 18.34 | 0.33839277 | -999.0000 | 27.00 | 0.00854241 | 27.00 | 0.00854241 | 37.9343 | 370035.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9658.701 | 6998.439 | 0.499730 | 0.00023654 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8111 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 8950.16 | 8828.03 | 0.9266 | -999.0 | -999.0 | 27.91 | 17.67 | 0.00859145 | 49981.9 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8950.16 | 25.60 | 0.00881543 | 17.07 | 0.01563234 | -999.0000 | 27.00 | 0.00858421 | 27.00 | 0.00858421 | 38.1149 | 8596.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 92787.131 | 67215.487 | 4.798721 | 0.00227235 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8179 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 85986.07 | 84766.15 | 0.9267 | -999.0 | -999.0 | 27.91 | 17.67 | 0.00859512 | 49989.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85986.07 | 25.60 | 0.00881543 | 17.07 | 0.15632344 | -999.0000 | 27.00 | 0.00858770 | 27.00 | 0.00858770 | 38.1303 | 82543.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9421.006 | 6823.738 | 0.487107 | 0.00023072 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8149 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 8730.88 | 8609.14 | 0.9267 | -999.0 | -999.0 | 27.92 | 17.67 | 0.00859351 | 49994.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8730.88 | 25.86 | 0.00881585 | 17.16 | 0.01563234 | -999.0000 | 27.00 | 0.00858614 | 27.00 | 0.00858614 | 38.1234 | 8378.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 426032.260 | 426032.260 | 21.531067 | 0.01043350 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 426032.26 | 426032.26 | 1.0000 | 25.55717770 | 21.531067 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 426032.26 | -4.20 | 0.00269032 | -4.20 | 0.33839277 | 1.5716 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9658.701 | 9658.701 | 0.499730 | 0.00023654 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9658.70 | 9658.70 | 1.0000 | 0.59317464 | 0.499730 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9658.70 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.1282 | 0.00 | 0.00850000 | 26.95 | 0.00850000 | 37.8463 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 92787.131 | 92787.131 | 4.798721 | 0.00227235 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 92787.13 | 92787.13 | 1.0000 | 5.69603818 | 4.798721 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92787.13 | -4.20 | 0.00269032 | -4.20 | 0.15632344 | 3.2576 | 0.00 | 0.00490429 | 24.52 | 0.00490429 | 25.3700 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9421.006 | 9421.006 | 0.487107 | 0.00023072 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9421.01 | 9421.01 | 1.0000 | 0.57819186 | 0.487107 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9421.01 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.2092 | 0.00 | 0.00310462 | 23.52 | 0.00310462 | 17.1052 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17840.032 | 17840.032 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.531067 | 25.55717770 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 17840.03 | 17840.03 | 1.0000 | 25.55717770 | 21.531067 | -0.07 | -0.07 | 0.00840869 | 20962.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17840.03 | -4.20 | 0.00269032 | -4.20 | 0.33839277 | 1.5716 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.499730 | 0.59317464 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 824.14 | 824.14 | 1.0000 | 0.59317464 | 0.499730 | -0.13 | -0.13 | 0.00831826 | 20669.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.14 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.1282 | 0.00 | 0.00850000 | 26.95 | 0.00850000 | 37.8463 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8241.356 | 8241.356 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.798721 | 5.69603818 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8241.36 | 8241.36 | 1.0000 | 5.69603818 | 4.798721 | -0.14 | -0.14 | 0.00483217 | 11946.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8241.36 | -4.20 | 0.00269032 | -4.20 | 0.15632344 | 3.2576 | 0.00 | 0.00490429 | 24.52 | 0.00490429 | 25.3700 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.487107 | 0.57819186 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 824.14 | 824.14 | 1.0000 | 0.57819186 | 0.487107 | -0.13 | -1.19 | 0.00309132 | 7595.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.14 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.2092 | 0.00 | 0.00310462 | 23.52 | 0.00310462 | 17.1052 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.77 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 80.33 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.13 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 4.91 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 21.53 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2270.00 | 396.67 | 0.17 |
CORE_BOTTOM | 2288.17 | 582.83 | 13.00 |
CORE_MID | 1189.50 | 2854.83 | 26.67 |
CORE_TOP | 1404.33 | 3817.00 | 471.67 |
PERIMETER_BOT_ZN_3 | 1396.33 | 3036.17 | 30.67 |
PERIMETER_BOT_ZN_2 | 1730.67 | 3004.67 | 93.83 |
PERIMETER_BOT_ZN_1 | 2134.50 | 2733.83 | 166.00 |
PERIMETER_BOT_ZN_4 | 2985.50 | 1316.83 | 214.83 |
PERIMETER_MID_ZN_3 | 1767.83 | 4240.50 | 986.33 |
PERIMETER_MID_ZN_2 | 1949.00 | 3243.83 | 871.67 |
PERIMETER_MID_ZN_1 | 2323.67 | 3377.33 | 676.50 |
PERIMETER_MID_ZN_4 | 2218.33 | 3547.83 | 726.67 |
PERIMETER_TOP_ZN_3 | 2416.67 | 4508.50 | 1693.33 |
PERIMETER_TOP_ZN_2 | 2770.83 | 3953.00 | 1532.00 |
PERIMETER_TOP_ZN_1 | 2663.50 | 3741.00 | 1213.50 |
PERIMETER_TOP_ZN_4 | 2632.67 | 3930.50 | 1300.00 |
DATACENTER_BOT_ZN_6 | 5943.00 | 554.83 | 554.83 |
DATACENTER_MID_ZN_6 | 5804.17 | 117.67 | 93.00 |
DATACENTER_TOP_ZN_6 | 5423.83 | 304.50 | 152.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5592.00 | 5592.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5934.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 41.83 | 0.00 | 3.50 |
CORE_BOTTOM | 0.00 | 0.67 | 0.00 | 0.00 |
CORE_MID | 1.83 | 0.00 | 1.17 | 0.00 |
CORE_TOP | 5.83 | 0.00 | 1.33 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 16.33 | 0.00 | 16.33 |
PERIMETER_BOT_ZN_1 | 0.00 | 30.17 | 0.00 | 29.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 81.17 | 0.00 | 46.17 |
PERIMETER_MID_ZN_3 | 9.33 | 0.00 | 1.83 | 0.00 |
PERIMETER_MID_ZN_2 | 13.17 | 16.00 | 0.33 | 16.00 |
PERIMETER_MID_ZN_1 | 4.33 | 25.67 | 0.00 | 25.17 |
PERIMETER_MID_ZN_4 | 3.00 | 29.67 | 0.00 | 17.50 |
PERIMETER_TOP_ZN_3 | 82.83 | 0.00 | 21.33 | 0.00 |
PERIMETER_TOP_ZN_2 | 46.67 | 16.83 | 4.50 | 16.50 |
PERIMETER_TOP_ZN_1 | 32.00 | 21.50 | 1.50 | 20.17 |
PERIMETER_TOP_ZN_4 | 21.17 | 28.50 | 1.50 | 16.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 73.67 | 0.00 | 72.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 93.17 | 278.67 | 22.33 | 192.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 1.272 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.945 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.687 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.658 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.876 | 0.041 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 1.200 | 0.042 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 1.375 | 0.041 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 1.885 | 0.042 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.685 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.996 | 0.105 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 1.235 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 1.138 | 0.099 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.690 | 0.118 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 1.091 | 0.122 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 1.237 | 0.118 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 1.161 | 0.122 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 27.371 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.20 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 51423644.60 | 0.00 | 51423644.60 | 0.00 | 51423644.60 | 37848132.68 | 4015.46 | 328.07 | 4416.46 | 217.49 |
CORE_BOTTOM | 39529781.99 | 0.00 | 39529781.99 | 0.00 | 39529781.99 | 33990283.35 | 3859.98 | 158.04 | 4741.99 | 347.62 |
CORE_MID | 0.28E+09 | 0.00 | 0.28E+09 | 0.00 | 0.28E+09 | 0.34E+09 | 4433.56 | 822.87 | 3503.57 | 156.32 |
CORE_TOP | 26774166.76 | 0.00 | 26774166.76 | 0.00 | 26774166.76 | 33990283.35 | 4554.59 | 1235.37 | 2970.04 | 222.01 |
PERIMETER_BOT_ZN_3 | 4602330.26 | 0.00 | 4602330.26 | 420131.66 | 5022461.92 | 4267819.30 | 5003.64 | 282.62 | 3473.74 | 347.62 |
PERIMETER_BOT_ZN_2 | 4010710.22 | 0.00 | 4010710.22 | 280087.58 | 4290797.80 | 2750345.05 | 4925.74 | 306.91 | 3527.35 | 347.62 |
PERIMETER_BOT_ZN_1 | 7100968.27 | 0.00 | 7100968.27 | 420131.66 | 7521099.93 | 4267912.63 | 4785.72 | 304.47 | 3669.80 | 347.62 |
PERIMETER_BOT_ZN_4 | 6309991.36 | 0.00 | 6309991.36 | 280087.58 | 6590078.94 | 2750345.05 | 3995.80 | 230.64 | 4533.56 | 347.62 |
PERIMETER_MID_ZN_3 | 35131736.83 | 0.00 | 35131736.83 | 985321.86 | 36117058.68 | 42678193.03 | 4659.42 | 898.18 | 3202.40 | 156.32 |
PERIMETER_MID_ZN_2 | 33373335.77 | 0.00 | 33373335.77 | 656880.79 | 34030216.55 | 27503450.52 | 4860.74 | 624.44 | 3274.83 | 661.96 |
PERIMETER_MID_ZN_1 | 62607747.42 | 0.00 | 62607747.42 | 985321.86 | 63593069.27 | 42679126.28 | 4303.10 | 799.32 | 3657.58 | 156.32 |
PERIMETER_MID_ZN_4 | 37562214.32 | 0.00 | 37562214.32 | 656880.79 | 38219095.11 | 27503450.52 | 4484.49 | 899.41 | 3376.10 | 156.32 |
PERIMETER_TOP_ZN_3 | 3532586.80 | 0.00 | 3532586.80 | 1223376.39 | 4755963.19 | 4267819.30 | 4392.91 | 1268.23 | 3098.87 | 222.01 |
PERIMETER_TOP_ZN_2 | 3568842.52 | 0.00 | 3568842.52 | 815583.70 | 4384426.23 | 2750345.05 | 4374.85 | 1390.91 | 2994.24 | 222.01 |
PERIMETER_TOP_ZN_1 | 6270269.46 | 0.00 | 6270269.46 | 1223376.39 | 7493645.86 | 4267912.63 | 4230.33 | 1253.33 | 3276.34 | 222.01 |
PERIMETER_TOP_ZN_4 | 3833174.50 | 0.00 | 3833174.50 | 815583.70 | 4648758.20 | 2750345.05 | 4343.78 | 946.62 | 3469.60 | 222.01 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.43E+09 | 0.00 | 0.43E+09 | 0.00 | 0.43E+09 | 10671554.30 | 5.33 | 33.00 | 8721.67 | 2817.00 |
Total Facility | 0.51E+10 | 0.00 | 0.51E+10 | 38322411.53 | 0.51E+10 | 0.50E+10 | 6406.89 | 4375.09 | 8757.10 | 3322.64 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.3424 | 0.0000 | 2.3424 | 0.0000 | 2.3424 | 1.2002 | 1314.14 | 326.66 | 4302.20 |
CORE_BOTTOM | 1.7584 | 0.0000 | 1.7584 | 0.0000 | 1.7584 | 1.0778 | 1332.28 | 154.47 | 4456.25 |
CORE_MID | 12.7829 | 0.0000 | 12.7829 | 0.0000 | 12.7829 | 10.7782 | 1703.23 | 822.72 | 3417.05 |
CORE_TOP | 1.2277 | 0.0000 | 1.2277 | 0.0000 | 1.2277 | 1.0778 | 1795.80 | 1235.37 | 2911.83 |
PERIMETER_BOT_ZN_3 | 0.2049 | 0.0000 | 0.2049 | 0.0095 | 0.2145 | 0.1353 | 2470.04 | 278.72 | 3194.24 |
PERIMETER_BOT_ZN_2 | 0.1809 | 0.0000 | 0.1809 | 0.0064 | 0.1873 | 0.0872 | 2391.17 | 302.71 | 3249.12 |
PERIMETER_BOT_ZN_1 | 0.3217 | 0.0000 | 0.3217 | 0.0095 | 0.3313 | 0.1353 | 2251.20 | 300.25 | 3391.55 |
PERIMETER_BOT_ZN_4 | 0.2839 | 0.0000 | 0.2839 | 0.0064 | 0.2902 | 0.0872 | 1465.74 | 227.19 | 4250.08 |
PERIMETER_MID_ZN_3 | 1.6058 | 0.0000 | 1.6058 | 0.0224 | 1.6282 | 1.3533 | 1931.54 | 897.63 | 3113.83 |
PERIMETER_MID_ZN_2 | 1.5026 | 0.0000 | 1.5026 | 0.0159 | 1.5185 | 0.8721 | 1627.84 | 623.15 | 2783.01 |
PERIMETER_MID_ZN_1 | 2.8898 | 0.0000 | 2.8898 | 0.0224 | 2.9122 | 1.3533 | 1575.72 | 799.13 | 3568.16 |
PERIMETER_MID_ZN_4 | 1.7162 | 0.0000 | 1.7162 | 0.0149 | 1.7311 | 0.8721 | 1756.24 | 899.27 | 3287.50 |
PERIMETER_TOP_ZN_3 | 0.1618 | 0.0000 | 0.1618 | 0.0278 | 0.1896 | 0.1353 | 1637.49 | 1267.96 | 3037.55 |
PERIMETER_TOP_ZN_2 | 0.1646 | 0.0000 | 0.1646 | 0.0185 | 0.1831 | 0.0872 | 1625.87 | 1390.53 | 2926.59 |
PERIMETER_TOP_ZN_1 | 0.2897 | 0.0000 | 0.2897 | 0.0278 | 0.3175 | 0.1353 | 1478.58 | 1253.13 | 3211.29 |
PERIMETER_TOP_ZN_4 | 0.1751 | 0.0000 | 0.1751 | 0.0185 | 0.1936 | 0.0872 | 1590.05 | 946.43 | 3406.51 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 14.0767 | 0.0000 | 14.0767 | 0.0000 | 14.0767 | 0.3384 | 5.33 | 33.00 | 5904.67 |
Total Facility | 227.3253 | 0.0000 | 227.3253 | 0.8803 | 228.2056 | 158.4706 | 3589.89 | 4366.27 | 5940.10 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 86726028.15 | 0.00 | 86726028.15 | 48026705.38 | 3565.73 | 8.82 | 5185.44 | 347.62 |
VAV_MID WITH REHEAT | 0.63E+09 | 0.00 | 0.63E+09 | 0.48E+09 | 3971.93 | 7.10 | 4780.97 | 156.32 |
VAV_TOP WITH REHEAT | 61964142.32 | 0.00 | 61964142.32 | 48026705.38 | 4066.12 | 5.77 | 4688.11 | 222.01 |
CAV_BAS | 72453195.95 | 0.00 | 72453195.95 | 37848132.68 | 3967.38 | 1.79 | 4790.82 | 217.49 |
AIRLOOP DATACENTER BASEMENT | 0.61E+09 | 0.00 | 0.61E+09 | 10671554.30 | 5.33 | 0.00 | 8754.67 | 2817.00 |
AIRLOOP DATACENTER BOT | 344200.17 | 0.00 | 344200.17 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3442001.72 | 0.00 | 3442001.72 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 344200.17 | 0.00 | 344200.17 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.8744 | 0.0000 | 3.8744 | 1.5229 | 1079.99 | 6.04 | 4856.97 |
VAV_MID WITH REHEAT | 28.9265 | 0.0000 | 28.9265 | 15.2292 | 1248.32 | 6.98 | 4687.70 |
VAV_TOP WITH REHEAT | 2.8445 | 0.0000 | 2.8445 | 1.5229 | 1316.86 | 4.20 | 4621.94 |
CAV_BAS | 3.3003 | 0.0000 | 3.3003 | 1.2002 | 1299.07 | 0.43 | 4643.50 |
AIRLOOP DATACENTER BASEMENT | 19.8334 | 0.0000 | 19.8334 | 0.3384 | 5.33 | 0.00 | 5937.67 |
AIRLOOP DATACENTER BOT | 0.0161 | 0.0000 | 0.0161 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1609 | 0.0000 | 0.1609 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0161 | 0.0000 | 0.0161 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 521.09 | 3797.70 | 0.00 | 0.00 | 0.00 | 937.43 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 283.57 | 3253.80 | 0.00 | 0.00 | 0.00 | 1413.97 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 26.77 | 3006.04 | 0.00 | 0.00 | 0.00 | 1992.56 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 322.42 | 4554.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 33.00 | 8721.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.8513 | 5.5985 | 0.0000 | 0.0000 | 0.0000 | 2.3779 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 28.4736 | 42.7226 | 0.0000 | 0.0000 | 0.0000 | 22.3214 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.8532 | 4.4736 | 0.0000 | 0.0000 | 0.0000 | 2.1968 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6931 | 4.3977 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4768 | 19.9617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2203 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1519 |
Defaulted Fields | 1187 |
Fields with Defaults | 3885 |
Autosized Fields | 333 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 22555.46 | 294542.75 | 29-MAY-04:00 | 1693406.60 | 29-AUG-15:10 |
Electricity:Building | 16398.23 | 215366.33 | 07-MAY-17:10 | 948093.84 | 01-DEC-16:20 |
Electricity:Zone:BASEMENT | 540.44 | 14022.76 | 01-JAN-00:10 | 23631.68 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16398.23 | 215366.33 | 07-MAY-17:10 | 948093.84 | 01-DEC-16:20 |
InteriorLights:Electricity | 1721.84 | 8110.17 | 08-JAN-10:20 | 169722.15 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1721.84 | 8110.17 | 08-JAN-10:20 | 169722.15 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 1721.84 | 8110.17 | 08-JAN-10:20 | 169722.15 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1721.84 | 8110.17 | 08-JAN-10:20 | 169722.15 | 02-JAN-16:30 |
Electricity:Zone:CORE_BOTTOM | 393.83 | 4960.84 | 01-JAN-00:10 | 26343.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 3938.24 | 49608.19 | 01-JAN-00:10 | 263436.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 393.82 | 4960.82 | 01-JAN-00:10 | 26343.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 44.11 | 589.50 | 19-MAR-17:10 | 3307.80 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.74 | 30.32 | 08-JAN-10:20 | 1147.25 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.74 | 30.32 | 08-JAN-10:20 | 1147.25 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 28.38 | 379.89 | 09-APR-17:10 | 2131.68 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.94 | 19.54 | 01-JAN-09:50 | 739.33 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.94 | 19.54 | 01-JAN-09:50 | 739.33 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 43.97 | 589.50 | 19-MAR-17:10 | 3307.86 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.61 | 30.33 | 01-JAN-09:40 | 1147.28 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.61 | 30.33 | 01-JAN-09:40 | 1147.28 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 28.37 | 379.89 | 19-MAR-17:10 | 2131.67 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.93 | 19.54 | 01-JAN-10:30 | 739.33 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.93 | 19.54 | 01-JAN-10:30 | 739.33 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 440.92 | 5894.96 | 19-MAR-17:10 | 33078.05 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 77.27 | 303.25 | 08-JAN-10:10 | 11472.53 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 77.27 | 303.25 | 08-JAN-10:10 | 11472.53 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 283.72 | 3798.93 | 09-APR-17:10 | 21316.76 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 49.37 | 195.42 | 01-JAN-09:50 | 7393.34 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 49.37 | 195.42 | 01-JAN-09:50 | 7393.34 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 439.64 | 5895.05 | 19-MAR-17:10 | 33078.63 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 75.98 | 303.26 | 01-JAN-09:40 | 11472.78 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 75.98 | 303.26 | 01-JAN-09:40 | 11472.78 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 283.61 | 3798.91 | 19-MAR-17:10 | 21316.66 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 49.26 | 195.42 | 01-JAN-10:20 | 7393.34 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 49.26 | 195.42 | 01-JAN-10:20 | 7393.34 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 44.09 | 589.50 | 19-MAR-17:10 | 3307.80 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.73 | 30.32 | 08-JAN-10:10 | 1147.25 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.73 | 30.32 | 08-JAN-10:10 | 1147.25 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 28.37 | 379.89 | 09-APR-17:10 | 2131.68 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.94 | 19.54 | 01-JAN-09:50 | 739.33 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.94 | 19.54 | 01-JAN-09:50 | 739.33 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 43.96 | 589.50 | 19-MAR-17:10 | 3307.86 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.60 | 30.33 | 01-JAN-09:40 | 1147.28 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.60 | 30.33 | 01-JAN-09:40 | 1147.28 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 28.36 | 379.89 | 19-MAR-17:10 | 2131.67 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.93 | 19.54 | 01-JAN-10:20 | 739.33 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.93 | 19.54 | 01-JAN-10:20 | 739.33 | 02-JAN-16:30 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7527.71 | 95067.50 | 01-JAN-00:10 | 382501.19 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1555.56 | 19567.35 | 01-JAN-00:10 | 79407.42 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 938.14 | 3484.14 | 16-JAN-06:00 | 337330.45 | 29-AUG-14:30 |
HeatRejection:Electricity | 360.06 | 131.57 | 07-JAN-08:00 | 70839.74 | 27-APR-12:20 |
General:HeatRejection:Electricity | 360.06 | 131.57 | 07-JAN-08:00 | 70839.74 | 27-APR-12:20 |
ElectricityProduced:Facility | 394.33 | -0.00 | 31-MAR-18:30 | 89495.83 | 10-MAY-11:30 |
ElectricityProduced:Plant | 394.33 | -0.00 | 31-MAR-18:30 | 89495.83 | 10-MAY-11:30 |
Photovoltaic:ElectricityProduced | 413.65 | 0.00 | 01-JAN-00:10 | 96313.32 | 18-MAY-11:30 |
PowerConversion:ElectricityProduced | -19.32 | -6817.48 | 18-MAY-11:30 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 3800.83 | 46602.52 | 12-JAN-02:20 | 398934.72 | 29-AUG-15:10 |
ExteriorEquipment:Electricity | 1203.69 | 17814.45 | 01-JAN-00:10 | 73700.33 | 28-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.36 | 979.82 | 01-JAN-00:10 | 3372.05 | 01-DEC-16:30 |
ElectricityPurchased:Facility | 22161.12 | 233301.62 | 29-MAY-12:30 | 1649918.28 | 29-AUG-15:30 |
ElectricityPurchased:Plant | 22161.12 | 233301.62 | 29-MAY-12:30 | 1649918.28 | 29-AUG-15:30 |
Cogeneration:ElectricityPurchased | 22161.12 | 233301.62 | 29-MAY-12:30 | 1649918.28 | 29-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 22161.12 | 233301.62 | 29-MAY-12:30 | 1649918.28 | 29-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 22161.12 | 233301.62 | 29-MAY-12:30 | 1649918.28 | 29-AUG-15:30 |
ElectricityNet:Plant | 22161.12 | 233301.62 | 29-MAY-12:30 | 1649918.28 | 29-AUG-15:30 |
Cogeneration:ElectricityNet | 22161.12 | 233301.62 | 29-MAY-12:30 | 1649918.28 | 29-AUG-15:30 |
General:Cogeneration:ElectricityNet | 22161.12 | 233301.62 | 29-MAY-12:30 | 1649918.28 | 29-AUG-15:30 |
Fans:Electricity | 2089.94 | 42178.38 | 03-JAN-04:40 | 262695.26 | 11-SEP-14:30 |
General:Fans:Electricity | 2089.94 | 42178.38 | 03-JAN-04:40 | 262695.26 | 11-SEP-14:30 |
ExteriorLights:Electricity | 268.92 | 0.00 | 01-JAN-08:10 | 31088.59 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 268.92 | 0.00 | 01-JAN-08:10 | 31088.59 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1144.44 | 16803.04 | 01-JAN-00:10 | 70012.65 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 4.90 | 31.59 | 01-JAN-00:10 | 315.94 | 01-JAN-07:10 |
Cooling:Electricity | 958.49 | 1279.53 | 03-JAN-08:10 | 378173.61 | 29-AUG-14:30 |
General:Cooling:Electricity | 958.49 | 1279.53 | 03-JAN-08:10 | 378173.61 | 29-AUG-14:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1026.66 | 0.00 | 11-JAN-20:10 | 100000.00 | 11-FEB-17:10 |
General:Humidifier:Electricity | 1026.66 | 0.00 | 11-JAN-20:10 | 100000.00 | 11-FEB-17:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 249.48 | 3326.54 | 03-JAN-00:10 | 39118.35 | 30-AUG-15:50 |
General:Pumps:Electricity | 249.48 | 3326.54 | 03-JAN-00:10 | 39118.35 | 30-AUG-15:50 |
WIRED_LTG_ELECTRICITY | 48.38 | 0.00 | 01-JAN-00:10 | 4769.19 | 02-JAN-16:40 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1819.15 | 7280.88 | 07-MAY-16:10 | 1272096.88 | 02-JAN-05:20 |
NaturalGas:Plant | 1819.15 | 7280.88 | 07-MAY-16:10 | 1272096.88 | 02-JAN-05:20 |
Heating:NaturalGas | 1047.77 | 0.00 | 01-JAN-09:20 | 1264816.00 | 02-JAN-05:20 |
Boiler:Heating:NaturalGas | 1047.77 | 0.00 | 01-JAN-09:20 | 1264816.00 | 02-JAN-05:20 |
WaterSystems:NaturalGas | 771.38 | 7280.88 | 02-JAN-05:20 | 82993.97 | 13-FEB-13:00 |
Water Heater:WaterSystems:NaturalGas | 771.38 | 7280.88 | 02-JAN-05:20 | 82993.97 | 13-FEB-13:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 5568.44 | 3353.79 | 03-JAN-08:10 | 2238321.31 | 29-AUG-14:30 |
PlantLoopCoolingDemand:HVAC | 5568.44 | 3353.79 | 03-JAN-08:10 | 2238321.31 | 29-AUG-14:30 |
CoolingCoils:PlantLoopCoolingDemand | 5568.44 | 3353.79 | 03-JAN-08:10 | 2238321.31 | 29-AUG-14:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 4383.53 | 0.00 | 12-JAN-01:20 | 0.00 | 10-AUG-16:00 |
Water:HVAC | 381.92 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
Humidifier:Water | 381.92 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
General:Humidifier:Water | 381.92 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
MainsWater:Facility | 4383.53 | 0.00 | 12-JAN-01:20 | 0.00 | 10-AUG-16:00 |
MainsWater:HVAC | 381.92 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
Humidifier:MainsWater | 381.92 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
General:Humidifier:MainsWater | 381.92 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
Water:Plant | 4001.62 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 4001.62 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 1721.45 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
General:HeatRejection:Water | 1721.45 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
HeatRejection:MainsWater | 1721.45 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
General:HeatRejection:MainsWater | 1721.45 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 31084.55 | 96216.24 | 22-JAN-06:00 | 8646798.33 | 29-AUG-14:30 |
EnergyTransfer:Building | 16454.29 | 88379.86 | 14-JAN-19:30 | 1547497.47 | 10-AUG-15:10 |
EnergyTransfer:Zone:BASEMENT | 583.87 | 0.00 | 01-JAN-00:10 | 69824.80 | 10-OCT-05:10 |
Heating:EnergyTransfer | 295.85 | 0.00 | 11-JAN-22:10 | 996645.44 | 02-JAN-05:50 |
Heating:EnergyTransfer:Zone:BASEMENT | 1.84 | 0.00 | 01-JAN-00:10 | 10866.80 | 01-APR-16:10 |
General:Heating:EnergyTransfer | 295.85 | 0.00 | 11-JAN-22:10 | 996645.44 | 02-JAN-05:50 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 1.84 | 0.00 | 01-JAN-00:10 | 10866.80 | 01-APR-16:10 |
Cooling:EnergyTransfer | 16158.43 | 86938.47 | 16-JAN-06:00 | 1547497.47 | 10-AUG-15:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 582.03 | 0.00 | 01-JAN-00:10 | 69824.80 | 10-OCT-05:10 |
General:Cooling:EnergyTransfer | 16158.43 | 86938.47 | 16-JAN-06:00 | 1547497.47 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 582.03 | 0.00 | 01-JAN-00:10 | 69824.80 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 529.56 | 0.00 | 01-JAN-00:10 | 49457.84 | 10-OCT-05:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 529.56 | 0.00 | 01-JAN-00:10 | 49457.84 | 10-OCT-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 529.56 | 0.00 | 01-JAN-00:10 | 49457.84 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_MID | 3530.16 | 0.00 | 01-JAN-00:10 | 378711.12 | 15-JUL-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 5.04 | 0.00 | 01-JAN-00:10 | 361892.84 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 5.04 | 0.00 | 01-JAN-00:10 | 361892.84 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3525.12 | 0.00 | 01-JAN-00:10 | 378711.12 | 15-JUL-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3525.12 | 0.00 | 01-JAN-00:10 | 378711.12 | 15-JUL-05:10 |
EnergyTransfer:Zone:CORE_TOP | 307.91 | 0.00 | 01-JAN-00:40 | 63442.77 | 02-JAN-05:30 |
Heating:EnergyTransfer:Zone:CORE_TOP | 6.73 | 0.00 | 01-JAN-00:20 | 63442.77 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 6.73 | 0.00 | 01-JAN-00:20 | 63442.77 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 301.18 | 0.00 | 01-JAN-00:10 | 42358.15 | 10-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 301.18 | 0.00 | 01-JAN-00:10 | 42358.15 | 10-AUG-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 56.64 | 0.00 | 01-JAN-00:10 | 9330.46 | 24-JUL-14:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 925.16 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 925.16 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 56.63 | 0.00 | 01-JAN-00:10 | 9330.46 | 24-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 56.63 | 0.00 | 01-JAN-00:10 | 9330.46 | 24-JUL-14:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 48.83 | 0.00 | 01-JAN-00:10 | 14997.73 | 31-JUL-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 984.08 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 984.08 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 48.83 | 0.00 | 01-JAN-00:10 | 14997.73 | 31-JUL-08:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 48.83 | 0.00 | 01-JAN-00:10 | 14997.73 | 31-JUL-08:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 89.48 | 0.00 | 01-JAN-00:10 | 23082.05 | 04-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.08 | 0.00 | 01-JAN-00:10 | 4636.30 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.08 | 0.00 | 01-JAN-00:10 | 4636.30 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 89.40 | 0.00 | 01-JAN-00:10 | 23082.05 | 04-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 89.40 | 0.00 | 01-JAN-00:10 | 23082.05 | 04-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 81.91 | 0.00 | 01-JAN-00:10 | 18872.40 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 81.91 | 0.00 | 01-JAN-00:10 | 18872.40 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 81.91 | 0.00 | 01-JAN-00:10 | 18872.40 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 399.87 | 0.00 | 01-JAN-00:10 | 101735.61 | 02-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 46.37 | 0.00 | 01-JAN-00:10 | 101735.61 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 46.37 | 0.00 | 01-JAN-00:10 | 101735.61 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 353.49 | 0.00 | 01-JAN-00:10 | 81884.41 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 353.49 | 0.00 | 01-JAN-00:10 | 81884.41 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 400.86 | 0.00 | 01-JAN-00:10 | 152987.75 | 31-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 28.76 | 0.00 | 01-JAN-00:10 | 97333.98 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 28.76 | 0.00 | 01-JAN-00:10 | 97333.98 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 372.10 | 0.00 | 01-JAN-00:10 | 152987.75 | 31-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 372.10 | 0.00 | 01-JAN-00:10 | 152987.75 | 31-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 788.84 | 0.00 | 01-JAN-00:10 | 247703.03 | 04-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 30.06 | 0.00 | 01-JAN-00:10 | 145851.90 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 30.06 | 0.00 | 01-JAN-00:10 | 145851.90 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 758.78 | 0.00 | 01-JAN-00:10 | 247703.03 | 04-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 758.78 | 0.00 | 01-JAN-00:10 | 247703.03 | 04-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 460.46 | 0.00 | 01-JAN-00:10 | 167395.58 | 10-AUG-16:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 15.95 | 0.00 | 01-JAN-00:10 | 85517.46 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 15.95 | 0.00 | 01-JAN-00:10 | 85517.46 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 444.50 | 0.00 | 01-JAN-00:10 | 167395.58 | 10-AUG-16:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 444.50 | 0.00 | 01-JAN-00:10 | 167395.58 | 10-AUG-16:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.26 | 0.00 | 01-JAN-00:40 | 11807.37 | 02-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 15.80 | 0.00 | 01-JAN-00:40 | 11807.37 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 15.80 | 0.00 | 01-JAN-00:40 | 11807.37 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.46 | 0.00 | 01-JAN-00:10 | 9180.62 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.46 | 0.00 | 01-JAN-00:10 | 9180.62 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 45.22 | 0.00 | 01-JAN-00:40 | 15260.38 | 31-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 9.41 | 0.00 | 01-JAN-00:40 | 13142.05 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 9.41 | 0.00 | 01-JAN-00:40 | 13142.05 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 35.80 | 0.00 | 01-JAN-00:10 | 15260.38 | 31-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 35.80 | 0.00 | 01-JAN-00:10 | 15260.38 | 31-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 78.93 | 0.00 | 01-JAN-00:40 | 25049.21 | 04-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 10.94 | 0.00 | 01-JAN-00:40 | 19629.67 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 10.94 | 0.00 | 01-JAN-00:40 | 19629.67 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 67.99 | 0.00 | 01-JAN-00:10 | 25049.21 | 04-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 67.99 | 0.00 | 01-JAN-00:10 | 25049.21 | 04-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 47.02 | 0.00 | 01-JAN-00:40 | 17348.53 | 10-AUG-16:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.99 | 0.00 | 01-JAN-00:40 | 12028.10 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.99 | 0.00 | 01-JAN-00:40 | 12028.10 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 41.03 | 0.00 | 01-JAN-00:10 | 17348.53 | 10-AUG-16:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 41.03 | 0.00 | 01-JAN-00:10 | 17348.53 | 10-AUG-16:40 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 43.86 | 0.00 | 01-JAN-00:10 | 8285.82 | 14-AUG-14:00 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.64 | 0.00 | 01-JAN-00:10 | 3948.65 | 19-FEB-12:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.64 | 0.00 | 01-JAN-00:10 | 3948.65 | 19-FEB-12:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 42.22 | 0.00 | 01-JAN-00:10 | 8285.82 | 14-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 42.22 | 0.00 | 01-JAN-00:10 | 8285.82 | 14-AUG-14:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 290.67 | 0.00 | 01-JAN-00:10 | 130203.97 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 84.51 | 0.00 | 01-JAN-00:10 | 130203.97 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 84.51 | 0.00 | 01-JAN-00:10 | 130203.97 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 206.16 | 0.00 | 01-JAN-00:10 | 60251.43 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 206.16 | 0.00 | 01-JAN-00:10 | 60251.43 | 10-AUG-15:10 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 63.19 | 0.00 | 01-JAN-00:40 | 19699.94 | 17-JAN-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 28.22 | 0.00 | 01-JAN-00:40 | 19699.94 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 28.22 | 0.00 | 01-JAN-00:40 | 19699.94 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 34.97 | 0.00 | 01-JAN-00:10 | 17637.62 | 10-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 34.97 | 0.00 | 01-JAN-00:10 | 17637.62 | 10-AUG-14:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.84 | 675.98 | 16-JAN-06:00 | 8588.05 | 06-AUG-19:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.84 | 675.98 | 16-JAN-06:00 | 8588.05 | 06-AUG-19:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.84 | 675.98 | 16-JAN-06:00 | 8588.05 | 06-AUG-19:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1166.55 | 5.97 | 21-JAN-17:50 | 81320.35 | 06-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 3.65 | 0.00 | 03-JAN-13:20 | 5500.59 | 03-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 3.65 | 0.00 | 03-JAN-13:20 | 5500.59 | 03-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1162.89 | 0.00 | 01-JAN-00:10 | 81320.35 | 06-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1162.89 | 0.00 | 01-JAN-00:10 | 81320.35 | 06-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 106.71 | 1.07 | 25-JAN-19:50 | 8287.37 | 06-AUG-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.82 | 0.00 | 03-JAN-11:30 | 594.68 | 08-JAN-17:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.82 | 0.00 | 03-JAN-11:30 | 594.68 | 08-JAN-17:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.89 | 0.00 | 01-JAN-00:10 | 8287.37 | 06-AUG-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.89 | 0.00 | 01-JAN-00:10 | 8287.37 | 06-AUG-18:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7150.65 | 86234.66 | 17-JAN-05:00 | 368024.36 | 10-AUG-21:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7150.65 | 86234.66 | 17-JAN-05:00 | 368024.36 | 10-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7150.65 | 86234.66 | 17-JAN-05:00 | 368024.36 | 10-AUG-21:10 |
PlantLoopHeatingDemand:Facility | 1405.67 | 0.00 | 03-JAN-00:10 | 1101299.34 | 02-JAN-06:10 |
PlantLoopHeatingDemand:Plant | 423.42 | 0.00 | 01-JAN-00:10 | 50358.97 | 09-FEB-12:40 |
WaterSystems:PlantLoopHeatingDemand | 423.42 | 0.00 | 01-JAN-00:10 | 50358.97 | 09-FEB-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 423.42 | 0.00 | 01-JAN-00:10 | 50358.97 | 09-FEB-12:40 |
EnergyTransfer:HVAC | 5920.81 | 2129.74 | 03-JAN-05:50 | 2090176.83 | 29-AUG-14:30 |
HeatingCoils:EnergyTransfer | 982.25 | 0.00 | 01-JAN-09:20 | 1095312.02 | 02-JAN-06:10 |
PlantLoopHeatingDemand:HVAC | 982.25 | 0.00 | 01-JAN-09:20 | 1095312.02 | 02-JAN-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 982.25 | 0.00 | 01-JAN-09:20 | 1095312.02 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 4938.56 | 2074.26 | 03-JAN-08:10 | 2090176.83 | 29-AUG-14:30 |
EnergyTransfer:Plant | 8709.45 | 0.00 | 03-JAN-00:10 | 5028657.74 | 29-AUG-14:30 |
LoopToLoop:EnergyTransfer | 2319.29 | 0.00 | 01-JAN-00:10 | 1592597.69 | 29-AUG-14:30 |
WaterSystems:EnergyTransfer | 423.42 | 0.00 | 01-JAN-00:10 | 50358.97 | 09-FEB-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 423.42 | 0.00 | 01-JAN-00:10 | 50358.97 | 09-FEB-12:40 |
Boilers:EnergyTransfer | 980.89 | 0.00 | 01-JAN-09:20 | 1142206.05 | 02-JAN-05:20 |
Chillers:EnergyTransfer | 2328.62 | 0.00 | 01-JAN-00:10 | 1590549.41 | 29-AUG-14:30 |
HeatRejection:EnergyTransfer | 2657.23 | 0.00 | 01-JAN-00:10 | 1820578.54 | 29-AUG-14:30 |
General:HeatRejection:EnergyTransfer | 2657.23 | 0.00 | 01-JAN-00:10 | 1820578.54 | 29-AUG-14:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 1.844 | -582.026 | 0.000 | 0.000 | 92.750 | 116.039 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -53.005 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -529.562 | 0.000 | 0.000 | 83.440 | 104.212 | 289.614 | 0.000 | 0.000 | 0.000 | 52.297 | 0.000 | 0.000 | 0.000 | 0.000 | -0.004 |
CORE_MID | 0.000 | 0.000 | 5.041 | -3525.105 | 0.000 | 0.000 | 850.263 | 1042.115 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1268.442 |
CORE_TOP | 0.000 | 0.000 | 6.728 | -301.181 | 0.000 | 0.000 | 88.165 | 104.212 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -187.535 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.001 | -56.634 | 0.000 | 0.000 | 10.734 | 7.744 | 36.365 | 22.835 | 0.000 | 0.014 | 46.099 | 0.000 | -60.628 | 0.000 | -6.532 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.005 | -48.830 | 0.000 | 0.000 | 6.927 | 4.945 | 23.435 | 45.455 | 0.000 | 0.009 | 10.378 | 0.000 | -38.028 | 0.000 | -4.295 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.085 | -89.396 | 0.000 | 0.000 | 10.739 | 7.605 | 36.366 | 99.069 | 0.000 | 0.012 | 0.001 | 0.000 | -56.877 | 0.000 | -6.496 | -1.108 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -81.905 | 0.000 | 0.000 | 6.769 | 4.934 | 23.435 | 48.094 | 0.000 | 0.008 | 47.720 | 0.000 | -44.213 | 0.000 | -4.842 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 46.374 | -353.493 | 0.000 | 0.000 | 113.607 | 77.268 | 363.654 | 240.370 | 0.000 | 0.370 | 173.388 | 0.000 | -528.896 | 0.000 | -132.642 | -0.006 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 28.765 | -372.099 | 0.000 | 0.000 | 52.904 | 49.370 | 234.352 | 456.176 | 0.000 | 0.183 | 0.011 | 0.000 | -345.295 | 0.000 | -90.839 | -13.518 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 30.062 | -758.775 | 0.000 | 0.000 | 110.310 | 75.980 | 363.660 | 990.714 | 0.000 | 0.273 | 0.018 | 0.000 | -535.703 | 0.000 | -141.317 | -135.204 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 15.953 | -444.497 | 0.000 | 0.000 | 71.892 | 49.262 | 234.351 | 492.203 | 0.000 | 0.180 | 44.762 | 0.000 | -369.358 | 0.000 | -94.749 | -0.010 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 15.798 | -30.458 | 0.000 | 0.000 | 11.578 | 7.726 | 36.365 | 24.693 | 0.000 | 0.041 | 0.000 | 0.000 | -49.132 | 0.000 | -15.341 | -1.270 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 9.415 | -35.803 | 0.000 | 0.000 | 7.325 | 4.937 | 23.435 | 46.244 | 0.000 | 0.022 | 0.000 | 0.000 | -32.135 | 0.000 | -10.502 | -12.938 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 10.941 | -67.990 | 0.000 | 0.000 | 11.245 | 7.598 | 36.366 | 99.822 | 0.000 | 0.032 | 0.000 | 0.000 | -49.992 | 0.000 | -16.375 | -31.647 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 5.990 | -41.029 | 0.000 | 0.000 | 7.325 | 4.926 | 23.435 | 49.504 | 0.000 | 0.021 | 0.001 | 0.000 | -34.725 | 0.000 | -11.082 | -4.365 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -136.836 | 0.000 | 0.000 | 0.950 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -19.671 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 3.655 | -1162.892 | 0.000 | 0.000 | 9.508 | 16.758 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -405.834 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.824 | -105.889 | 0.000 | 0.000 | 0.953 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -51.445 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7150.647 | 0.000 | 0.000 | 20.505 | 32.854 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -397.569 |
GROUNDFLOOR_PLENUM | 1.645 | -42.218 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.023 | 54.470 | 0.000 | 0.000 | 0.000 | -13.920 | 0.000 |
MIDFLOOR_PLENUM | 84.511 | -206.162 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.461 | 352.329 | 0.000 | 0.000 | 0.000 | -231.139 | -0.015 |
TOPFLOOR_PLENUM | 28.220 | -34.968 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.025 | 30.957 | 0.000 | 0.000 | 0.000 | -24.234 | -0.001 |
Total Facility | 114.376 | -283.348 | 181.482 | -15875.046 | 0.000 | 0.000 | 1567.890 | 1721.836 | 14676.396 | 2615.179 | 0.000 | 1.674 | 812.432 | 0.000 | -2144.982 | 0.000 | -804.304 | -2583.587 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 11-SEP-04:11 | 0.00 | 0.00 | 0.00 | -100865.11 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 86809.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 12-JUN-04:12 | 0.00 | 0.00 | 0.00 | -88547.06 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 82072.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 28-AUG-04:12 | 0.00 | 0.00 | 0.00 | -736098.22 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 671348.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 12-JUN-04:11 | 0.00 | 0.00 | 0.00 | -70549.54 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 64074.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 12-JUN-04:11 | 0.00 | 0.00 | 0.00 | -10995.56 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 12582.18 | 0.00 | -2120.61 | 0.00 | -279.05 | 0.00 |
PERIMETER_BOT_ZN_2 | 30-JUL-08:31 | 0.00 | 0.00 | 0.00 | -24435.50 | 0.00 | 0.00 | 19.87 | 19.54 | 464.11 | 19314.97 | 0.00 | 0.00 | 4723.40 | 0.00 | -0.00 | 0.00 | -106.39 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-13:11 | 0.00 | 0.00 | 0.00 | -33847.60 | 0.00 | 0.00 | 31.11 | 30.33 | 720.19 | 25654.54 | 0.00 | 0.00 | 7578.28 | 0.00 | -0.00 | 0.00 | -166.85 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-JUL-16:31 | 0.00 | 0.00 | 0.00 | -32064.56 | 0.00 | 0.00 | 14.10 | 19.54 | 464.11 | 21712.71 | 0.00 | 0.00 | 9945.56 | 0.00 | -0.00 | 0.00 | -91.47 | 0.00 |
PERIMETER_MID_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -81882.35 | 0.00 | 0.00 | 11143.83 | 5458.63 | 21605.52 | 63676.11 | 0.00 | 810.55 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -20812.29 |
PERIMETER_MID_ZN_2 | 13-AUG-08:51 | 0.00 | 0.00 | 0.00 | -259644.53 | 0.00 | 0.00 | 190.84 | 195.42 | 4641.14 | 183107.52 | 0.00 | 0.00 | 76335.00 | 0.00 | -0.00 | 0.00 | -4825.39 | 0.00 |
PERIMETER_MID_ZN_1 | 13-AUG-12:11 | 0.00 | 0.00 | 0.00 | -342839.14 | 0.00 | 0.00 | 324.59 | 303.26 | 7201.95 | 236543.93 | 0.00 | 0.00 | 100347.90 | 0.00 | -0.00 | 0.00 | -1882.48 | 0.00 |
PERIMETER_MID_ZN_4 | 23-JUL-17:21 | 0.00 | 0.00 | 0.00 | -290020.80 | 0.00 | 0.00 | 0.00 | 195.42 | 3603.49 | 199475.47 | 0.00 | 0.00 | 89248.39 | 0.00 | -0.00 | 0.00 | -2501.97 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -9180.49 | 0.00 | 0.00 | 1114.38 | 545.86 | 2160.55 | 6308.96 | 0.00 | 98.95 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1048.21 |
PERIMETER_TOP_ZN_2 | 06-AUG-09:21 | 0.00 | 0.00 | 0.00 | -24591.66 | 0.00 | 0.00 | 21.10 | 19.54 | 464.11 | 16187.72 | 0.00 | 0.00 | 8398.44 | 0.00 | -0.00 | 0.00 | -499.26 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:11 | 0.00 | 0.00 | 0.00 | -38438.26 | 0.00 | 0.00 | 28.50 | 30.33 | 720.19 | 25391.22 | 0.00 | 0.00 | 12791.43 | 0.00 | -0.00 | 0.00 | -523.41 | 0.00 |
PERIMETER_TOP_ZN_4 | 30-JUL-17:01 | 0.00 | 0.00 | 0.00 | -30509.06 | 0.00 | 0.00 | 0.00 | 19.54 | 360.35 | 21107.84 | 0.00 | 0.00 | 9305.00 | 0.00 | -0.00 | 0.00 | -283.67 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-19:06 | 0.00 | 0.00 | 0.00 | -8601.39 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 798.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 06-AUG-18:32 | 0.00 | 0.00 | 0.00 | -81320.35 | 0.00 | 0.00 | 0.00 | 81.29 | 77944.22 | 0.00 | 0.00 | 0.00 | 3294.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 06-AUG-18:32 | 0.00 | 0.00 | 0.00 | -8303.82 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 501.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 13-AUG-18:42 | 0.00 | 0.00 | 0.00 | -371686.88 | 0.00 | 0.00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8105.00 |
GROUNDFLOOR_PLENUM | 14-AUG-05:10 | 0.00 | -10047.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10107.56 | 0.00 | -0.00 | 0.00 | -59.85 | 0.00 |
MIDFLOOR_PLENUM | 14-JAN-05:11 | 0.00 | -74138.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101534.43 | 0.00 | -0.00 | 0.00 | -27395.82 | 0.00 |
TOPFLOOR_PLENUM | 10-AUG-14:30 | 0.00 | -17637.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.59 | 17570.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-AUG-05:03 | 0.00 | -21349.59 | 0.00 | -1721422.81 | 0.00 | 0.00 | 16095.14 | 10223.35 | 616289.16 | 20328.85 | 0.00 | 0.00 | 1134963.54 | 0.00 | -51407.58 | 0.00 | -3720.06 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 01-APR-16:01 | 0.00 | 0.00 | 11969.66 | 0.00 | 0.00 | 0.00 | 520.13 | 565.21 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26512.55 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-05:11 | 0.00 | 0.00 | 395673.36 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -460423.19 |
CORE_TOP | 02-JAN-05:21 | 0.00 | 0.00 | 68232.80 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -74707.78 |
PERIMETER_BOT_ZN_3 | 17-JAN-06:01 | 0.00 | 0.00 | 7810.34 | 0.00 | 0.00 | 0.00 | 142.77 | 67.47 | 960.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4049.10 | 0.00 | -92.07 | -4839.66 |
PERIMETER_BOT_ZN_2 | 17-JAN-06:01 | 0.00 | 0.00 | 6711.38 | 0.00 | 0.00 | 0.00 | 93.20 | 43.48 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2711.71 | 0.00 | -60.74 | -4694.44 |
PERIMETER_BOT_ZN_1 | 17-JAN-05:01 | 0.00 | 0.00 | 12471.14 | 0.00 | 0.00 | 0.00 | 0.00 | 127.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3636.93 | 0.00 | -305.29 | -9401.97 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 109005.86 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19774.36 | 0.00 | -9923.41 | -87438.41 |
PERIMETER_MID_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 158138.76 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13152.45 | 0.00 | -6882.94 | -143342.86 |
PERIMETER_MID_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 227861.47 | 0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20289.87 | 0.00 | -10278.40 | -205423.65 |
PERIMETER_MID_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 156398.60 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14006.19 | 0.00 | -6883.03 | -140748.83 |
PERIMETER_TOP_ZN_3 | 02-JAN-05:21 | 0.00 | 0.00 | 12886.05 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1852.49 | 0.00 | -1167.87 | -10678.71 |
PERIMETER_TOP_ZN_2 | 02-JAN-05:21 | 0.00 | 0.00 | 18380.17 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1268.55 | 0.00 | -816.27 | -16819.30 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:21 | 0.00 | 0.00 | 27274.93 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1900.60 | 0.00 | -1223.92 | -24963.45 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:21 | 0.00 | 0.00 | 18807.80 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1324.55 | 0.00 | -847.17 | -17160.03 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 03-JAN-00:10 | 0.00 | 0.00 | 5500.60 | 0.00 | 0.00 | 0.00 | 0.00 | 81.29 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25067.95 |
DATACENTER_TOP_ZN_6 | 08-JAN-17:35 | 0.00 | 0.00 | 602.32 | 0.00 | 0.00 | 0.00 | 5.81 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2564.87 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 13-AUG-14:11 | 11781.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.29 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -11862.06 |
MIDFLOOR_PLENUM | 02-JAN-06:02 | 151345.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4937.07 | -146408.21 |
TOPFLOOR_PLENUM | 17-JAN-06:12 | 22399.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -287.47 | -22111.58 |
Total Facility | 02-JAN-05:31 | 554.70 | 109296.31 | 1075087.70 | -109296.31 | 0.00 | 0.00 | 0.00 | 10223.35 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -91607.11 | 0.00 | -73364.63 | -1153319.24 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.6017 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.7736 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 101.9325 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 80.3335 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.2538 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.1265 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 4.9090 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 4.9090 | 0.2445 | 1.0000 | Not calculated | 1.2002 | 0.2445 | ||
AIRLOOP DATACENTER BASEMENT | 21.5310 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.5311 | 0.0157 | 1.0000 | Not calculated | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.4997 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4997 | 0.0313 | 1.0000 | Not calculated | 0.0156 | 0.0313 | ||
AIRLOOP DATACENTER MID | 4.7987 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.7987 | 0.0326 | 1.0000 | Not calculated | 0.1563 | 0.0326 | ||
AIRLOOP DATACENTER TOP | 0.4871 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4871 | 0.0321 | 1.0000 | Not calculated | 0.0156 | 0.0321 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.3008 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2852 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 50.9663 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8724 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.1269 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2836 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 4.9090 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 4.9090 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2445 | ||
AIRLOOP DATACENTER BASEMENT | 21.5310 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.5310 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.4997 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4997 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0313 | ||
AIRLOOP DATACENTER MID | 4.7987 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.7987 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0326 | ||
AIRLOOP DATACENTER TOP | 0.4871 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4871 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0321 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9090 | 4.9090 | 4.9090 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2746 | 5.2746 | 1.6193 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 49.1967 | 49.1967 | 16.1857 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7263 | 4.7263 | 1.6164 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8159 | 0.8159 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2527 | 1.2527 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7427 | 1.7427 | 0.2022 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5158 | 1.5158 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.5226 | 7.5226 | 2.0311 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.1449 | 13.1449 | 1.3145 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.1482 | 18.1482 | 2.0326 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.9202 | 13.9202 | 1.3085 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8522 | 0.8522 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3037 | 1.3037 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9133 | 1.9133 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4584 | 1.4584 | 0.1313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4997 | 0.4997 | 0.4997 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7987 | 4.7987 | 4.7987 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4871 | 0.4871 | 0.4871 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.5310 | 21.5310 | 21.5310 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.6017 | 8.7736 | 10.6017 | 2.2852 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 101.9325 | 80.3335 | 101.9325 | 22.8724 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.2538 | 9.1265 | 10.2538 | 2.2836 | 0.0000 | 1.0000 |
CAV_BAS | 4.9090 | 4.9090 | 4.9090 | 4.9090 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5310 | 21.5311 | 21.5310 | 21.5310 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4997 | 0.4997 | 0.4997 | 0.4997 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.7987 | 4.7987 | 4.7987 | 4.7987 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4871 | 0.4871 | 0.4871 | 0.4871 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9090 | 4.9090 | 4.9090 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6373 | 2.6373 | 1.6193 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 24.5983 | 24.5983 | 16.1857 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3631 | 2.3631 | 1.6164 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4079 | 0.4079 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6264 | 0.6264 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8713 | 0.8713 | 0.2022 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7579 | 0.7579 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7613 | 3.7613 | 2.0311 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.5724 | 6.5724 | 1.3145 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.0741 | 9.0741 | 2.0326 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.9601 | 6.9601 | 1.3085 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4261 | 0.4261 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6518 | 0.6518 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9566 | 0.9566 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7292 | 0.7292 | 0.1313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4997 | 0.4997 | 0.4997 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7987 | 4.7987 | 4.7987 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4871 | 0.4871 | 0.4871 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.5310 | 21.5310 | 21.5310 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.3008 | 2.2852 | 2.2852 | 2.2852 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 50.9663 | 22.8724 | 22.8724 | 22.8724 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.1269 | 2.2836 | 2.2836 | 2.2836 | 0.0000 | 1.0000 |
CAV_BAS | 4.9090 | 4.9090 | 4.9090 | 4.9090 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5310 | 21.5310 | 21.5310 | 21.5310 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4997 | 0.4997 | 0.4997 | 0.4997 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.7987 | 4.7987 | 4.7987 | 4.7987 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4871 | 0.4871 | 0.4871 | 0.4871 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 22.33 |
Number of hours cooling loads not met | 192.00 |
Number of hours not met | 214.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1047.77 | 1264816.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 958.49 | 378173.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1721.84 | 169722.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 268.92 | 31088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.36 | 3372.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1144.44 | 70012.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 4.90 | 315.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2089.94 | 262695.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 249.48 | 39118.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 360.06 | 70839.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1026.66 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 771.38 | 82993.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 22555.46 |
Natural Gas | 0.00 | 1819.15 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 24374.61 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 413.65 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 37.17 |
Space Heating | 0.00 |
Space Cooling | 20.69 |
Fans (All) | 45.12 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 486.94 |
Subtotal | 486.94 |
Natural Gas [MJ/m2] | |
Space Heating | 22.62 |
Service Water Heating | 16.65 |
Miscellaneous (All) | 39.27 |
Subtotal | 39.27 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.06 |
Space Heating | 4.30 |
Space Cooling | 3.93 |
Fans (All) | 8.57 |
Service Water Heating | 3.16 |
Receptacle Equipment | 60.21 |
Miscellaneous | 12.75 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2069. | 8760. |
LTG_SCH_DATACENTER | 1840. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 782. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8509.83 | 250.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8733.00 | 27.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8732.67 | 27.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8722.50 | 37.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8474.17 | 285.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8733.00 | 27.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8723.17 | 36.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8701.83 | 58.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8734.17 | 25.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8724.33 | 35.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8701.33 | 58.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7813.67 | 946.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7774.00 | 986.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7749.50 | 1010.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7495.67 | 1264.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8736.67 | 23.33 | 0.00 | 0.00 | 0.00 |
Min | 7495.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1264.33 | 0.00 | 0.00 | 0.00 |
Average | 8538.19 | 221.81 | 0.00 | 0.00 | 0.00 |
Sum | 196378.33 | 5101.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368175.00 | 441.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330744.00 | 69.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1707.50 | 560.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1675.00 | 593.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1659.83 | 608.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 87701.17 | 15693.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368175.00 | 15693.83 | 0.00 | 0.00 | 0.00 |
Average | 79553.80 | 781.11 | 0.00 | 0.00 | 0.00 |
Sum | 1829737.50 | 17965.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8336.67 | 423.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8550.50 | 209.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8623.33 | 136.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8675.83 | 84.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8749.17 | 10.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8728.17 | 31.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8704.67 | 55.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8413.33 | 346.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8725.00 | 35.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8699.67 | 60.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8663.83 | 96.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8727.33 | 32.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8706.83 | 53.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8673.33 | 86.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8454.83 | 305.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8435.00 | 325.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8426.83 | 333.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7923.00 | 837.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8729.17 | 30.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8627.83 | 132.17 | 0.00 | 0.00 | 0.00 |
Min | 7923.00 | 1.33 | 0.00 | 0.00 | 0.00 |
Max | 8758.67 | 837.00 | 0.00 | 0.00 | 0.00 |
Average | 8601.96 | 158.04 | 0.00 | 0.00 | 0.00 |
Sum | 197845.17 | 3634.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 367749.17 | 866.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330466.00 | 347.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330547.00 | 266.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330635.00 | 178.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2056.83 | 211.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2041.00 | 227.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2035.83 | 232.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 92353.17 | 11041.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367749.17 | 11041.83 | 0.00 | 0.00 | 0.00 |
Average | 79753.61 | 581.30 | 0.00 | 0.00 | 0.00 |
Sum | 1834333.00 | 13370.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:56
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.396452E+11 | 99865.00 | 02-JAN-05:11 | 6.10 | 5.29 | 0.565165E+10 | 7499.17 | 20-JAN-10:09 | 4.18 | 2.79 |
February | 0.387299E+11 | 96303.84 | 27-FEB-05:11 | 6.50 | 5.53 | 0.513146E+10 | 7499.16 | 08-FEB-10:09 | 6.50 | 5.53 |
March | 0.493092E+11 | 96834.85 | 13-MAR-04:11 | 6.30 | 5.39 | 0.612991E+10 | 7499.16 | 02-MAR-10:20 | 6.30 | 5.39 |
April | 0.479977E+11 | 97446.96 | 03-APR-04:12 | 10.60 | 9.99 | 0.544764E+10 | 7499.25 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.493473E+11 | 97330.08 | 08-MAY-04:12 | 9.07 | 8.85 | 0.589886E+10 | 7499.23 | 05-MAY-09:20 | 9.07 | 8.85 |
June | 0.516768E+11 | 99943.06 | 05-JUN-04:11 | 10.60 | 9.38 | 0.587987E+10 | 7499.22 | 09-JUN-13:20 | 21.87 | 13.52 |
July | 0.531174E+11 | 98341.35 | 05-JUL-04:12 | 11.30 | 8.18 | 0.547080E+10 | 7499.19 | 11-JUL-09:20 | 16.13 | 15.49 |
August | 0.580406E+11 | 95877.59 | 07-AUG-04:12 | 12.53 | 11.52 | 0.613508E+10 | 7513.24 | 15-AUG-13:09 | 24.25 | 15.86 |
September | 0.500590E+11 | 100873.07 | 11-SEP-04:11 | 12.93 | 11.13 | 0.545031E+10 | 7499.19 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.508049E+11 | 97888.69 | 16-OCT-04:11 | 7.20 | 6.13 | 0.566635E+10 | 7499.10 | 25-OCT-13:20 | 13.50 | 10.37 |
November | 0.478190E+11 | 97846.73 | 20-NOV-05:11 | 8.13 | 6.37 | 0.561014E+10 | 7499.14 | 02-NOV-09:20 | 8.13 | 6.37 |
December | 0.454801E+11 | 98217.40 | 26-DEC-04:01 | -1.0 | -1.0 | 0.546476E+10 | 7499.24 | 13-DEC-14:20 | -1.0 | -1.0 |
Annual Sum or Average | 0.582027E+12 | 0.679368E+11 | ||||||||
Minimum of Months | 0.387299E+11 | 95877.59 | -1.0 | -1.0 | 0.513146E+10 | 7499.10 | -1.0 | -1.0 | ||
Maximum of Months | 0.580406E+11 | 100873.07 | 12.93 | 11.52 | 0.613508E+10 | 7513.24 | 26.10 | 16.46 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.299951E+11 | 78473.24 | 02-JAN-05:11 | 6.10 | 5.29 | 0.504678E+10 | 6734.78 | 20-JAN-10:09 | 4.18 | 2.79 |
February | 0.317535E+11 | 79323.05 | 27-FEB-05:11 | 6.50 | 5.53 | 0.459620E+10 | 6734.79 | 08-FEB-10:09 | 6.50 | 5.53 |
March | 0.445261E+11 | 81047.58 | 27-MAR-04:11 | 4.80 | 3.63 | 0.549985E+10 | 6734.79 | 02-MAR-10:20 | 4.80 | 3.63 |
April | 0.481879E+11 | 82299.67 | 17-APR-04:12 | 6.10 | 5.14 | 0.488280E+10 | 6734.78 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.448970E+11 | 82860.35 | 01-MAY-04:12 | 12.20 | 10.35 | 0.528631E+10 | 6734.82 | 05-MAY-09:20 | 16.33 | 13.64 |
June | 0.493402E+11 | 88547.76 | 12-JUN-04:12 | 14.80 | 13.61 | 0.527096E+10 | 6734.83 | 05-JUN-09:00 | 14.80 | 13.61 |
July | 0.546833E+11 | 84581.08 | 17-JUL-04:11 | 14.23 | 12.63 | 0.489780E+10 | 6734.77 | 18-JUL-09:20 | 17.43 | 12.11 |
August | 0.626009E+11 | 82372.59 | 29-AUG-04:13 | 15.40 | 14.08 | 0.549654E+10 | 6739.32 | 15-AUG-13:09 | 15.40 | 14.08 |
September | 0.432425E+11 | 85882.18 | 05-SEP-04:12 | 11.33 | 9.63 | 0.488490E+10 | 6734.81 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.425380E+11 | 86008.88 | 10-OCT-04:12 | 12.20 | 11.04 | 0.507807E+10 | 6734.80 | 12-OCT-09:09 | 9.18 | 7.86 |
November | 0.394959E+11 | 84404.74 | 06-NOV-05:12 | 10.77 | 8.10 | 0.502875E+10 | 6734.76 | 02-NOV-09:20 | 10.77 | 8.10 |
December | 0.383024E+11 | 81452.58 | 04-DEC-05:12 | 3.70 | 1.47 | 0.489950E+10 | 6734.79 | 12-DEC-10:09 | 3.58 | 3.51 |
Annual Sum or Average | 0.529563E+12 | 0.608685E+11 | ||||||||
Minimum of Months | 0.299951E+11 | 78473.24 | 3.70 | 1.47 | 0.459620E+10 | 6734.76 | 3.58 | 2.79 | ||
Maximum of Months | 0.626009E+11 | 88547.76 | 15.40 | 14.08 | 0.549985E+10 | 6739.32 | 26.10 | 16.46 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186082E+11 | 17327.80 | 12-JAN-17:00 | 7.20 | 5.41 | 0.448343E+10 | 6696.13 | 12-JAN-14:00 | 7.20 | 5.41 |
February | 0.197486E+11 | 29539.50 | 28-FEB-06:03 | 10.60 | 9.74 | 0.433362E+10 | 6734.74 | 09-FEB-10:09 | 10.60 | 9.74 |
March | 0.274833E+11 | 65478.56 | 03-MAR-06:02 | 6.60 | 6.18 | 0.541353E+10 | 6734.78 | 02-MAR-10:20 | 6.60 | 6.18 |
April | 0.287844E+11 | 70367.27 | 28-APR-04:12 | 11.50 | 10.06 | 0.483961E+10 | 6734.80 | 14-APR-09:20 | 11.50 | 10.06 |
May | 0.350914E+11 | 72050.18 | 09-MAY-05:02 | 11.10 | 9.86 | 0.526486E+10 | 6734.82 | 05-MAY-09:20 | 11.10 | 9.86 |
June | 0.372840E+11 | 73444.02 | 12-JUN-04:11 | 14.80 | 13.61 | 0.525936E+10 | 6734.81 | 12-JUN-13:20 | 16.70 | 15.00 |
July | 0.381341E+11 | 73593.71 | 17-JUL-04:11 | 14.23 | 12.63 | 0.489010E+10 | 6734.81 | 25-JUL-09:20 | 16.67 | 14.02 |
August | 0.414311E+11 | 73622.42 | 28-AUG-04:12 | 15.40 | 14.02 | 0.549164E+10 | 6735.03 | 09-AUG-09:00 | 15.40 | 14.02 |
September | 0.342731E+11 | 71853.63 | 08-SEP-05:02 | 10.18 | 9.80 | 0.486932E+10 | 6734.81 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.285667E+11 | 71800.06 | 10-OCT-05:02 | 12.20 | 11.22 | 0.502264E+10 | 6734.78 | 12-OCT-09:09 | 9.18 | 7.86 |
November | 0.225710E+11 | 64836.87 | 07-NOV-06:02 | 12.12 | 9.85 | 0.485869E+10 | 6734.76 | 02-NOV-09:20 | 12.12 | 9.85 |
December | 0.205360E+11 | 21676.89 | 06-DEC-16:20 | 2.57 | 2.27 | 0.455535E+10 | 6734.64 | 13-DEC-14:39 | 6.50 | 4.91 |
Annual Sum or Average | 0.352512E+12 | 0.592822E+11 | ||||||||
Minimum of Months | 0.186082E+11 | 17327.80 | 2.57 | 2.27 | 0.433362E+10 | 6696.13 | 6.50 | 4.91 | ||
Maximum of Months | 0.414311E+11 | 73622.42 | 15.40 | 14.02 | 0.549164E+10 | 6735.03 | 17.38 | 15.51 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135992E+11 | 15126.17 | 11-JAN-17:00 | 12.20 | 9.27 | 0.406919E+10 | 6209.69 | 11-JAN-14:00 | 12.20 | 9.27 |
February | 0.150375E+11 | 21555.77 | 28-FEB-17:00 | 14.40 | 10.82 | 0.386866E+10 | 6734.57 | 28-FEB-14:30 | 14.40 | 10.82 |
March | 0.212622E+11 | 24478.63 | 15-MAR-16:00 | 11.10 | 7.72 | 0.497914E+10 | 6734.65 | 02-MAR-14:20 | 11.10 | 7.72 |
April | 0.242313E+11 | 63316.64 | 28-APR-05:03 | 11.10 | 9.92 | 0.464576E+10 | 6734.80 | 14-APR-09:20 | 11.10 | 9.92 |
May | 0.315027E+11 | 65662.75 | 05-MAY-05:02 | 12.98 | 10.75 | 0.519394E+10 | 6734.81 | 05-MAY-09:20 | 16.33 | 13.64 |
June | 0.357589E+11 | 70547.25 | 12-JUN-04:11 | 14.80 | 13.61 | 0.523326E+10 | 6734.80 | 09-JUN-13:09 | 14.80 | 13.61 |
July | 0.378901E+11 | 68773.36 | 10-JUL-05:02 | 13.22 | 11.65 | 0.487607E+10 | 6734.81 | 11-JUL-09:20 | 16.13 | 15.49 |
August | 0.402759E+11 | 69509.22 | 28-AUG-05:02 | 14.83 | 13.93 | 0.547503E+10 | 6735.01 | 09-AUG-09:00 | 14.83 | 13.93 |
September | 0.296120E+11 | 65069.01 | 14-SEP-05:03 | 12.62 | 12.25 | 0.480089E+10 | 6734.79 | 14-SEP-09:20 | 17.57 | 15.54 |
October | 0.217481E+11 | 32378.53 | 04-OCT-15:50 | 21.20 | 11.42 | 0.472180E+10 | 6734.71 | 05-OCT-09:20 | 12.43 | 7.97 |
November | 0.162516E+11 | 17992.08 | 03-NOV-16:00 | 13.30 | 12.93 | 0.430284E+10 | 6689.13 | 03-NOV-13:00 | 13.30 | 12.93 |
December | 0.140142E+11 | 15121.85 | 06-DEC-16:25 | 2.20 | 1.95 | 0.397736E+10 | 6279.67 | 06-DEC-14:00 | 2.20 | 1.95 |
Annual Sum or Average | 0.301184E+12 | 0.561439E+11 | ||||||||
Minimum of Months | 0.135992E+11 | 15121.85 | 2.20 | 1.95 | 0.386866E+10 | 6209.69 | 2.20 | 1.95 | ||
Maximum of Months | 0.402759E+11 | 70547.25 | 21.20 | 13.93 | 0.547503E+10 | 6735.01 | 17.57 | 15.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221142E+10 | 2273.52 | 11-JAN-06:03 | 9.90 | 7.47 | 0.554658E+09 | 832.05 | 11-JAN-14:39 | 14.40 | 10.49 |
February | 0.240288E+10 | 4354.36 | 27-FEB-15:30 | 19.70 | 12.30 | 0.530536E+09 | 845.62 | 27-FEB-10:20 | 19.70 | 12.30 |
March | 0.364014E+10 | 4783.43 | 10-MAR-14:20 | 16.50 | 11.85 | 0.670229E+09 | 845.63 | 09-MAR-14:09 | 16.50 | 11.85 |
April | 0.491691E+10 | 7161.72 | 27-APR-15:20 | 27.20 | 17.16 | 0.606052E+09 | 845.63 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.568096E+10 | 7229.42 | 15-MAY-13:50 | 23.22 | 13.56 | 0.658947E+09 | 845.63 | 05-MAY-09:09 | 23.22 | 13.56 |
June | 0.691550E+10 | 10995.53 | 12-JUN-04:11 | 14.80 | 13.61 | 0.660636E+09 | 845.64 | 09-JUN-13:09 | 14.80 | 13.61 |
July | 0.814309E+10 | 10933.48 | 24-JUL-05:03 | 15.87 | 13.15 | 0.614640E+09 | 845.76 | 03-JUL-13:30 | 15.87 | 13.15 |
August | 0.882320E+10 | 10299.69 | 14-AUG-05:03 | 15.37 | 13.48 | 0.689687E+09 | 847.19 | 15-AUG-13:09 | 24.25 | 15.86 |
September | 0.489211E+10 | 7907.98 | 11-SEP-15:35 | 23.30 | 16.04 | 0.608457E+09 | 845.63 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.366238E+10 | 5037.16 | 10-OCT-12:10 | 13.30 | 8.88 | 0.623375E+09 | 845.63 | 12-OCT-09:20 | 9.47 | 7.95 |
November | 0.282954E+10 | 4282.60 | 06-NOV-11:40 | 13.70 | 9.94 | 0.602014E+09 | 845.62 | 10-NOV-14:09 | 10.00 | 6.84 |
December | 0.251582E+10 | 2550.46 | 04-DEC-05:12 | 3.70 | 1.47 | 0.566043E+09 | 845.61 | 04-DEC-14:09 | 8.90 | 5.70 |
Annual Sum or Average | 0.566339E+11 | 0.738527E+10 | ||||||||
Minimum of Months | 0.221142E+10 | 2273.52 | 3.70 | 1.47 | 0.530536E+09 | 832.05 | 8.90 | 5.70 | ||
Maximum of Months | 0.882320E+10 | 10995.53 | 27.20 | 17.16 | 0.689687E+09 | 847.19 | 27.20 | 17.16 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139743E+10 | 2598.83 | 05-JAN-09:25 | 1.10 | 0.98 | 0.358794E+09 | 544.95 | 20-JAN-10:09 | 4.18 | 2.79 |
February | 0.167543E+10 | 4667.30 | 08-FEB-09:45 | 1.93 | 0.91 | 0.345380E+09 | 544.95 | 08-FEB-10:09 | 2.48 | 1.47 |
March | 0.297280E+10 | 9110.69 | 14-MAR-08:55 | 7.80 | 5.89 | 0.432115E+09 | 544.96 | 02-MAR-10:09 | 7.80 | 5.89 |
April | 0.454157E+10 | 12244.39 | 27-APR-08:30 | 16.95 | 12.18 | 0.390811E+09 | 544.96 | 20-APR-09:00 | 16.95 | 12.18 |
May | 0.526255E+10 | 19047.32 | 14-MAY-08:42 | 16.32 | 11.34 | 0.425184E+09 | 544.97 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.666159E+10 | 20832.42 | 25-JUN-08:32 | 16.33 | 11.87 | 0.426002E+09 | 544.97 | 09-JUN-13:09 | 16.33 | 11.87 |
July | 0.713399E+10 | 24438.94 | 30-JUL-08:31 | 19.83 | 15.43 | 0.396350E+09 | 546.36 | 31-JUL-09:50 | 23.12 | 17.56 |
August | 0.785318E+10 | 24191.92 | 13-AUG-08:51 | 20.90 | 15.90 | 0.444339E+09 | 546.34 | 10-AUG-09:50 | 20.90 | 15.90 |
September | 0.483857E+10 | 23534.31 | 10-SEP-08:31 | 15.53 | 13.26 | 0.392859E+09 | 544.97 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.311323E+10 | 10019.88 | 04-OCT-08:50 | 15.32 | 10.37 | 0.400889E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.180668E+10 | 4128.74 | 15-NOV-09:05 | 6.78 | 5.27 | 0.382467E+09 | 544.95 | 15-NOV-10:20 | 7.40 | 5.77 |
December | 0.157251E+10 | 3538.67 | 05-DEC-09:55 | 6.70 | 5.10 | 0.354419E+09 | 544.95 | 12-DEC-10:20 | 3.87 | 3.71 |
Annual Sum or Average | 0.488295E+11 | 0.474961E+10 | ||||||||
Minimum of Months | 0.139743E+10 | 2598.83 | 1.10 | 0.91 | 0.345380E+09 | 544.95 | 2.48 | 1.47 | ||
Maximum of Months | 0.785318E+10 | 24438.94 | 20.90 | 15.90 | 0.444339E+09 | 546.36 | 23.12 | 17.56 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281906E+10 | 16025.89 | 20-JAN-13:05 | 6.70 | 4.72 | 0.560447E+09 | 845.64 | 20-JAN-10:09 | 6.70 | 4.72 |
February | 0.429041E+10 | 20179.74 | 12-FEB-13:23 | 6.40 | 1.13 | 0.538232E+09 | 846.56 | 27-FEB-14:50 | 19.72 | 12.05 |
March | 0.698979E+10 | 19703.06 | 01-MAR-13:25 | 11.15 | 5.98 | 0.667791E+09 | 846.79 | 01-MAR-14:50 | 13.03 | 7.20 |
April | 0.829551E+10 | 28183.54 | 02-APR-11:32 | 16.67 | 10.75 | 0.604171E+09 | 846.59 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.822009E+10 | 29049.15 | 07-MAY-15:41 | 22.12 | 16.33 | 0.657565E+09 | 845.67 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.885022E+10 | 27262.22 | 11-JUN-12:53 | 21.70 | 15.29 | 0.660256E+09 | 845.68 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.111245E+11 | 32392.57 | 30-JUL-13:11 | 26.30 | 17.73 | 0.615177E+09 | 846.62 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.132677E+11 | 32478.48 | 13-AUG-12:11 | 26.23 | 18.19 | 0.690177E+09 | 851.00 | 15-AUG-13:09 | 24.25 | 15.86 |
September | 0.100145E+11 | 33847.39 | 10-SEP-13:11 | 21.13 | 14.29 | 0.610054E+09 | 929.27 | 11-SEP-14:39 | 23.13 | 15.81 |
October | 0.764167E+10 | 30456.90 | 29-OCT-12:22 | 10.85 | 7.74 | 0.621986E+09 | 846.54 | 02-OCT-13:39 | 10.85 | 7.74 |
November | 0.399655E+10 | 20195.58 | 11-NOV-12:23 | 5.85 | 4.72 | 0.594747E+09 | 845.64 | 02-NOV-09:20 | 5.85 | 4.72 |
December | 0.388640E+10 | 27188.98 | 03-DEC-13:32 | 12.20 | 6.14 | 0.559977E+09 | 845.64 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.893964E+11 | 0.738058E+10 | ||||||||
Minimum of Months | 0.281906E+10 | 16025.89 | 5.85 | 1.13 | 0.538232E+09 | 845.64 | 5.85 | 4.72 | ||
Maximum of Months | 0.132677E+11 | 33847.39 | 26.30 | 18.19 | 0.690177E+09 | 929.27 | 28.30 | 18.92 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185930E+10 | 5384.57 | 05-JAN-15:30 | 6.40 | 4.89 | 0.389376E+09 | 544.95 | 27-JAN-14:09 | 9.72 | 8.09 |
February | 0.294031E+10 | 11562.93 | 26-FEB-15:23 | 14.40 | 10.39 | 0.368339E+09 | 544.95 | 08-FEB-10:09 | 14.40 | 10.39 |
March | 0.587568E+10 | 16766.97 | 09-MAR-06:02 | 10.68 | 9.15 | 0.444871E+09 | 544.96 | 09-MAR-14:09 | 14.90 | 12.35 |
April | 0.861347E+10 | 26107.99 | 02-APR-15:32 | 20.60 | 11.94 | 0.396191E+09 | 544.96 | 27-APR-13:39 | 26.10 | 16.65 |
May | 0.754126E+10 | 30378.30 | 07-MAY-16:21 | 21.95 | 16.24 | 0.428089E+09 | 544.96 | 05-MAY-09:09 | 21.95 | 16.24 |
June | 0.921400E+10 | 27002.84 | 18-JUN-16:52 | 17.20 | 12.22 | 0.427485E+09 | 544.97 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.124281E+11 | 32064.62 | 30-JUL-16:31 | 27.07 | 18.02 | 0.398178E+09 | 544.97 | 28-JUL-13:50 | 27.07 | 18.02 |
August | 0.136578E+11 | 32027.98 | 06-AUG-16:51 | 23.40 | 15.11 | 0.446423E+09 | 546.23 | 15-AUG-13:09 | 24.25 | 15.86 |
September | 0.694846E+10 | 29983.02 | 10-SEP-16:31 | 22.20 | 14.28 | 0.395859E+09 | 575.88 | 11-SEP-15:30 | 23.30 | 15.99 |
October | 0.510135E+10 | 17514.09 | 01-OCT-15:53 | 16.70 | 13.67 | 0.410844E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.388165E+10 | 12321.51 | 07-NOV-06:02 | 12.12 | 9.85 | 0.406405E+09 | 544.95 | 02-NOV-09:20 | 12.12 | 9.85 |
December | 0.384393E+10 | 14043.78 | 04-DEC-05:11 | 3.70 | 1.47 | 0.395984E+09 | 544.96 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.819053E+11 | 0.490804E+10 | ||||||||
Minimum of Months | 0.185930E+10 | 5384.57 | 3.70 | 1.47 | 0.368339E+09 | 544.95 | 7.10 | 5.11 | ||
Maximum of Months | 0.136578E+11 | 32064.62 | 27.07 | 18.02 | 0.446423E+09 | 575.88 | 27.07 | 18.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.500298E+09 | 1586.08 | 11-JAN-16:10 | 14.03 | 10.30 | 0.469388E+09 | 697.64 | 11-JAN-14:00 | 14.03 | 10.30 |
February | 0.996625E+09 | 1998.88 | 28-FEB-15:10 | 13.90 | 10.77 | 0.445132E+09 | 821.90 | 28-FEB-14:00 | 13.90 | 10.77 |
March | 0.211344E+10 | 2375.10 | 10-MAR-14:30 | 16.40 | 11.76 | 0.583849E+09 | 845.60 | 10-MAR-14:30 | 16.40 | 11.76 |
April | 0.270588E+10 | 5795.82 | 27-APR-15:20 | 27.20 | 17.16 | 0.559903E+09 | 845.63 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.419175E+10 | 6421.01 | 05-MAY-13:30 | 23.85 | 16.52 | 0.642470E+09 | 845.63 | 22-MAY-13:20 | 16.10 | 10.37 |
June | 0.508481E+10 | 6975.47 | 21-JUN-15:30 | 24.70 | 15.68 | 0.653704E+09 | 845.64 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.579068E+10 | 8188.44 | 24-JUL-15:00 | 30.60 | 18.78 | 0.610652E+09 | 846.34 | 24-JUL-13:20 | 30.60 | 18.78 |
August | 0.589997E+10 | 7728.81 | 25-AUG-14:00 | 27.40 | 18.74 | 0.684515E+09 | 845.67 | 09-AUG-09:00 | 27.40 | 18.74 |
September | 0.368000E+10 | 6147.01 | 11-SEP-15:30 | 23.30 | 15.99 | 0.592854E+09 | 845.63 | 05-SEP-13:20 | 23.30 | 15.99 |
October | 0.232738E+10 | 3350.58 | 06-OCT-14:40 | 17.20 | 12.13 | 0.561617E+09 | 845.62 | 02-OCT-13:20 | 17.20 | 12.13 |
November | 0.137535E+10 | 1948.23 | 07-NOV-06:02 | 12.12 | 9.85 | 0.497859E+09 | 791.41 | 02-NOV-13:00 | 12.12 | 9.85 |
December | 0.683264E+09 | 1494.08 | 29-DEC-15:10 | 10.60 | 8.76 | 0.456726E+09 | 673.81 | 05-DEC-14:39 | 10.60 | 8.76 |
Annual Sum or Average | 0.353494E+11 | 0.675867E+10 | ||||||||
Minimum of Months | 0.500298E+09 | 1494.08 | 10.60 | 8.76 | 0.445132E+09 | 673.81 | 10.60 | 8.76 | ||
Maximum of Months | 0.589997E+10 | 8188.44 | 30.60 | 18.78 | 0.684515E+09 | 846.34 | 30.60 | 18.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.302425E+09 | 1182.15 | 20-JAN-11:10 | 5.60 | 3.32 | 0.224394E+09 | 488.76 | 20-JAN-11:09 | 5.60 | 3.32 |
February | 0.646634E+09 | 3916.75 | 08-FEB-11:05 | 4.08 | 2.58 | 0.223586E+09 | 548.49 | 08-FEB-11:09 | 4.08 | 2.58 |
March | 0.173276E+10 | 9053.65 | 14-MAR-10:05 | 10.28 | 7.92 | 0.295457E+09 | 548.50 | 14-MAR-10:09 | 10.28 | 7.92 |
April | 0.329374E+10 | 13048.07 | 27-APR-10:05 | 19.27 | 13.13 | 0.279303E+09 | 548.51 | 20-APR-10:09 | 19.27 | 13.13 |
May | 0.446283E+10 | 20507.73 | 14-MAY-09:22 | 17.80 | 11.88 | 0.308270E+09 | 548.52 | 15-MAY-10:09 | 19.18 | 13.24 |
June | 0.602990E+10 | 24700.55 | 25-JUN-08:21 | 16.15 | 11.79 | 0.312228E+09 | 548.51 | 07-JUN-10:09 | 16.15 | 11.79 |
July | 0.637026E+10 | 25886.91 | 23-JUL-08:41 | 18.72 | 13.76 | 0.292080E+09 | 548.51 | 07-JUL-12:09 | 18.72 | 13.76 |
August | 0.693331E+10 | 25968.52 | 13-AUG-08:51 | 20.90 | 15.90 | 0.326535E+09 | 548.58 | 09-AUG-10:09 | 20.90 | 15.90 |
September | 0.419238E+10 | 21163.75 | 10-SEP-08:42 | 15.82 | 13.36 | 0.285415E+09 | 548.50 | 11-SEP-10:09 | 19.08 | 14.37 |
October | 0.207853E+10 | 10045.98 | 04-OCT-10:05 | 17.48 | 10.97 | 0.277815E+09 | 548.51 | 05-OCT-10:09 | 14.08 | 9.36 |
November | 0.760753E+09 | 4473.56 | 04-NOV-10:05 | 16.38 | 13.96 | 0.243984E+09 | 548.49 | 02-NOV-12:09 | 16.38 | 13.96 |
December | 0.406143E+09 | 1312.62 | 05-DEC-11:05 | 8.58 | 5.53 | 0.222210E+09 | 524.32 | 05-DEC-11:09 | 8.58 | 5.53 |
Annual Sum or Average | 0.372097E+11 | 0.329128E+10 | ||||||||
Minimum of Months | 0.302425E+09 | 1182.15 | 4.08 | 2.58 | 0.222210E+09 | 488.76 | 4.08 | 2.58 | ||
Maximum of Months | 0.693331E+10 | 25968.52 | 20.90 | 15.90 | 0.326535E+09 | 548.58 | 20.90 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165403E+10 | 15926.34 | 20-JAN-13:15 | 6.70 | 4.72 | 0.512368E+09 | 845.64 | 11-JAN-14:39 | 6.70 | 4.72 |
February | 0.346762E+10 | 21522.12 | 12-FEB-14:02 | 6.70 | 1.41 | 0.500210E+09 | 846.24 | 27-FEB-14:00 | 20.00 | 12.17 |
March | 0.597758E+10 | 21178.69 | 01-MAR-13:25 | 11.15 | 5.98 | 0.634382E+09 | 846.40 | 14-MAR-13:20 | 14.80 | 9.84 |
April | 0.669774E+10 | 22785.65 | 02-APR-14:12 | 19.47 | 11.50 | 0.585113E+09 | 847.06 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.743734E+10 | 27973.72 | 07-MAY-13:13 | 20.77 | 16.02 | 0.647659E+09 | 845.71 | 11-MAY-13:30 | 15.25 | 9.07 |
June | 0.766955E+10 | 26992.10 | 11-JUN-13:02 | 21.78 | 15.29 | 0.654176E+09 | 845.68 | 28-JUN-13:30 | 24.70 | 15.69 |
July | 0.954402E+10 | 31436.30 | 30-JUL-13:22 | 26.40 | 17.72 | 0.611846E+09 | 847.35 | 31-JUL-13:20 | 27.57 | 18.47 |
August | 0.112698E+11 | 34285.54 | 13-AUG-12:11 | 26.23 | 18.19 | 0.686930E+09 | 847.72 | 09-AUG-13:20 | 26.23 | 18.19 |
September | 0.986672E+10 | 32985.58 | 10-SEP-12:42 | 20.40 | 13.99 | 0.603688E+09 | 933.04 | 11-SEP-14:39 | 23.13 | 15.81 |
October | 0.700763E+10 | 31490.65 | 08-OCT-13:22 | 18.90 | 13.91 | 0.598030E+09 | 857.72 | 04-OCT-13:20 | 18.90 | 13.91 |
November | 0.290016E+10 | 31666.49 | 11-NOV-13:32 | 7.43 | 5.39 | 0.545882E+09 | 845.66 | 02-NOV-13:50 | 7.43 | 5.39 |
December | 0.238607E+10 | 16273.19 | 05-DEC-12:30 | 10.30 | 6.13 | 0.508444E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.758783E+11 | 0.708873E+10 | ||||||||
Minimum of Months | 0.165403E+10 | 15926.34 | 6.70 | 1.41 | 0.500210E+09 | 845.64 | 6.70 | 4.72 | ||
Maximum of Months | 0.112698E+11 | 34285.54 | 26.40 | 18.19 | 0.686930E+09 | 933.04 | 27.57 | 18.47 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.584126E+09 | 1823.68 | 05-JAN-15:40 | 6.30 | 4.80 | 0.313201E+09 | 527.34 | 05-JAN-14:00 | 6.30 | 4.80 |
February | 0.115371E+10 | 7912.82 | 27-FEB-15:30 | 19.70 | 12.30 | 0.305768E+09 | 544.96 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.228598E+10 | 10719.11 | 14-MAR-16:00 | 17.20 | 10.94 | 0.397330E+09 | 544.95 | 10-MAR-14:30 | 17.20 | 10.94 |
April | 0.363027E+10 | 17655.45 | 02-APR-15:32 | 20.60 | 11.94 | 0.374636E+09 | 544.96 | 13-APR-13:20 | 16.87 | 9.00 |
May | 0.544341E+10 | 25651.52 | 29-MAY-18:11 | 15.93 | 12.26 | 0.419152E+09 | 544.96 | 22-MAY-13:30 | 15.93 | 12.26 |
June | 0.602304E+10 | 25214.02 | 18-JUN-17:21 | 16.95 | 12.25 | 0.423637E+09 | 544.96 | 28-JUN-13:30 | 24.70 | 15.69 |
July | 0.810556E+10 | 29003.65 | 23-JUL-17:21 | 26.40 | 15.75 | 0.396132E+09 | 544.96 | 28-JUL-13:00 | 20.00 | 15.26 |
August | 0.774062E+10 | 25644.09 | 06-AUG-17:01 | 23.47 | 15.14 | 0.443998E+09 | 545.00 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.499411E+10 | 24598.94 | 10-SEP-16:42 | 22.20 | 14.22 | 0.389102E+09 | 580.70 | 11-SEP-15:39 | 23.30 | 16.04 |
October | 0.247761E+10 | 11949.75 | 04-OCT-16:00 | 21.10 | 11.40 | 0.377308E+09 | 544.95 | 25-OCT-13:20 | 13.50 | 10.37 |
November | 0.121170E+10 | 6065.27 | 04-NOV-15:30 | 20.55 | 15.94 | 0.336789E+09 | 544.94 | 08-NOV-14:00 | 9.40 | 8.82 |
December | 0.800267E+09 | 2951.30 | 05-DEC-15:30 | 8.05 | 5.82 | 0.310538E+09 | 544.94 | 05-DEC-14:00 | 8.05 | 5.82 |
Annual Sum or Average | 0.444504E+11 | 0.448759E+10 | ||||||||
Minimum of Months | 0.584126E+09 | 1823.68 | 6.30 | 4.80 | 0.305768E+09 | 527.34 | 6.30 | 4.80 | ||
Maximum of Months | 0.810556E+10 | 29003.65 | 26.40 | 15.94 | 0.443998E+09 | 580.70 | 24.70 | 16.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177304E+09 | 1473.79 | 11-JAN-16:10 | 14.03 | 10.30 | 0.464742E+09 | 663.42 | 11-JAN-14:00 | 14.03 | 10.30 |
February | 0.544056E+09 | 1912.83 | 28-FEB-15:00 | 13.90 | 10.81 | 0.432403E+09 | 795.23 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.141060E+10 | 2038.19 | 10-MAR-14:50 | 16.20 | 11.59 | 0.546280E+09 | 837.59 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.225501E+10 | 6423.98 | 27-APR-15:20 | 27.20 | 17.16 | 0.532479E+09 | 845.63 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.383129E+10 | 6868.74 | 15-MAY-14:30 | 23.30 | 13.06 | 0.622483E+09 | 845.63 | 05-MAY-09:20 | 23.30 | 13.06 |
June | 0.491261E+10 | 7621.88 | 21-JUN-15:30 | 24.70 | 15.68 | 0.644107E+09 | 845.64 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.576611E+10 | 9180.62 | 24-JUL-15:00 | 30.60 | 18.78 | 0.606042E+09 | 845.64 | 20-JUL-13:09 | 30.60 | 18.78 |
August | 0.578381E+10 | 8341.48 | 09-AUG-14:40 | 28.17 | 18.42 | 0.678203E+09 | 845.67 | 09-AUG-09:00 | 28.17 | 18.42 |
September | 0.330288E+10 | 6062.83 | 11-SEP-15:30 | 23.30 | 15.99 | 0.571273E+09 | 845.63 | 14-SEP-09:20 | 17.57 | 15.54 |
October | 0.164948E+10 | 3151.51 | 04-OCT-15:30 | 21.40 | 11.45 | 0.522456E+09 | 845.62 | 05-OCT-13:20 | 16.10 | 10.57 |
November | 0.660172E+09 | 1762.69 | 02-NOV-14:40 | 13.67 | 11.26 | 0.472101E+09 | 746.16 | 02-NOV-13:00 | 13.67 | 11.26 |
December | 0.164649E+09 | 1387.21 | 29-DEC-15:10 | 10.60 | 8.76 | 0.448620E+09 | 641.79 | 29-DEC-14:00 | 10.60 | 8.76 |
Annual Sum or Average | 0.304580E+11 | 0.654119E+10 | ||||||||
Minimum of Months | 0.164649E+09 | 1387.21 | 10.60 | 8.76 | 0.432403E+09 | 641.79 | 10.60 | 8.76 | ||
Maximum of Months | 0.578381E+10 | 9180.62 | 30.60 | 18.78 | 0.678203E+09 | 845.67 | 30.60 | 18.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190938E+09 | 1005.97 | 20-JAN-10:50 | 5.32 | 3.17 | 0.300541E+09 | 448.55 | 20-JAN-10:00 | 5.60 | 3.25 |
February | 0.531829E+09 | 1310.22 | 27-FEB-15:50 | 19.50 | 12.39 | 0.290299E+09 | 533.56 | 27-FEB-14:00 | 19.50 | 12.39 |
March | 0.143729E+10 | 5703.01 | 14-MAR-09:50 | 9.63 | 7.44 | 0.381408E+09 | 544.95 | 14-MAR-09:00 | 10.00 | 7.75 |
April | 0.303535E+10 | 12012.07 | 27-APR-09:10 | 17.98 | 12.34 | 0.370066E+09 | 544.96 | 20-APR-09:00 | 17.98 | 12.34 |
May | 0.436669E+10 | 23383.80 | 14-MAY-09:12 | 17.43 | 11.77 | 0.412417E+09 | 544.98 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.606191E+10 | 23379.90 | 25-JUN-10:12 | 18.33 | 13.04 | 0.421599E+09 | 544.97 | 09-JUN-13:09 | 18.33 | 13.04 |
July | 0.655660E+10 | 23547.52 | 30-JUL-08:21 | 19.45 | 15.24 | 0.393775E+09 | 545.88 | 31-JUL-09:00 | 23.30 | 17.69 |
August | 0.702819E+10 | 24591.57 | 06-AUG-09:21 | 16.20 | 13.22 | 0.441592E+09 | 545.91 | 14-AUG-09:00 | 21.10 | 15.94 |
September | 0.407545E+10 | 23721.84 | 10-SEP-08:31 | 15.53 | 13.26 | 0.379186E+09 | 544.97 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.174389E+10 | 7985.91 | 04-OCT-09:20 | 16.13 | 10.66 | 0.359705E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.541282E+09 | 1316.39 | 04-NOV-10:40 | 17.23 | 14.47 | 0.309980E+09 | 519.70 | 02-NOV-13:00 | 17.23 | 14.47 |
December | 0.233719E+09 | 1056.76 | 05-DEC-10:40 | 7.77 | 5.32 | 0.291193E+09 | 463.23 | 05-DEC-10:50 | 8.03 | 5.37 |
Annual Sum or Average | 0.358031E+11 | 0.435176E+10 | ||||||||
Minimum of Months | 0.190938E+09 | 1005.97 | 5.32 | 3.17 | 0.290299E+09 | 448.55 | 5.60 | 3.25 | ||
Maximum of Months | 0.702819E+10 | 24591.57 | 19.50 | 15.24 | 0.441592E+09 | 545.91 | 23.30 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108988E+10 | 14497.42 | 20-JAN-13:30 | 6.70 | 4.72 | 0.496396E+09 | 845.63 | 09-JAN-14:20 | 6.70 | 4.72 |
February | 0.261777E+10 | 17794.45 | 27-FEB-14:20 | 18.87 | 11.68 | 0.481449E+09 | 845.64 | 07-FEB-14:09 | 18.87 | 11.68 |
March | 0.481639E+10 | 20093.01 | 14-MAR-13:30 | 15.00 | 10.00 | 0.603786E+09 | 846.03 | 01-MAR-14:39 | 15.00 | 10.00 |
April | 0.592175E+10 | 27654.17 | 02-APR-12:32 | 18.33 | 10.92 | 0.566316E+09 | 846.48 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.695946E+10 | 33339.24 | 14-MAY-13:12 | 22.40 | 12.22 | 0.632344E+09 | 845.67 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.747126E+10 | 27862.12 | 11-JUN-12:43 | 21.70 | 15.34 | 0.645529E+09 | 845.67 | 09-JUN-13:09 | 21.70 | 15.34 |
July | 0.952930E+10 | 36432.23 | 30-JUL-13:01 | 26.20 | 17.74 | 0.607438E+09 | 846.51 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.110953E+11 | 35209.95 | 06-AUG-13:22 | 22.15 | 15.53 | 0.681877E+09 | 847.44 | 29-AUG-13:39 | 29.43 | 20.04 |
September | 0.931799E+10 | 38438.10 | 10-SEP-13:11 | 21.13 | 14.29 | 0.589509E+09 | 900.05 | 11-SEP-14:39 | 23.13 | 15.81 |
October | 0.578613E+10 | 30213.75 | 08-OCT-13:22 | 18.90 | 13.91 | 0.570491E+09 | 846.13 | 04-OCT-13:00 | 18.90 | 13.91 |
November | 0.186965E+10 | 17602.01 | 04-NOV-13:30 | 20.85 | 16.00 | 0.512607E+09 | 845.64 | 15-NOV-14:50 | 9.08 | 6.55 |
December | 0.151620E+10 | 13769.86 | 05-DEC-12:30 | 10.30 | 6.13 | 0.487436E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.679911E+11 | 0.687518E+10 | ||||||||
Minimum of Months | 0.108988E+10 | 13769.86 | 6.70 | 4.72 | 0.481449E+09 | 845.63 | 6.70 | 4.72 | ||
Maximum of Months | 0.110953E+11 | 38438.10 | 26.20 | 17.74 | 0.681877E+09 | 900.05 | 29.43 | 20.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.347367E+09 | 1562.50 | 05-JAN-15:40 | 6.30 | 4.80 | 0.306159E+09 | 521.18 | 05-JAN-16:10 | 5.73 | 4.38 |
February | 0.789499E+09 | 7416.84 | 27-FEB-15:30 | 19.70 | 12.30 | 0.295417E+09 | 544.94 | 28-FEB-14:30 | 14.15 | 11.19 |
March | 0.183974E+10 | 10543.71 | 14-MAR-16:00 | 17.20 | 10.94 | 0.374795E+09 | 544.94 | 01-MAR-14:20 | 17.20 | 10.94 |
April | 0.329391E+10 | 17847.16 | 02-APR-15:13 | 20.60 | 11.89 | 0.359705E+09 | 544.96 | 27-APR-13:50 | 26.10 | 16.74 |
May | 0.520530E+10 | 29564.50 | 07-MAY-16:51 | 21.70 | 16.17 | 0.409538E+09 | 544.96 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.591073E+10 | 27309.36 | 25-JUN-16:51 | 21.70 | 13.46 | 0.419082E+09 | 544.97 | 09-JUN-13:09 | 21.70 | 13.46 |
July | 0.809940E+10 | 30509.99 | 30-JUL-17:01 | 26.70 | 17.83 | 0.394483E+09 | 544.96 | 20-JUL-13:09 | 26.70 | 17.83 |
August | 0.762973E+10 | 29850.73 | 06-AUG-17:21 | 23.60 | 15.18 | 0.441533E+09 | 545.00 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.470408E+10 | 28952.39 | 10-SEP-16:31 | 22.20 | 14.28 | 0.379699E+09 | 557.12 | 11-SEP-15:30 | 23.30 | 15.99 |
October | 0.203199E+10 | 11902.28 | 04-OCT-16:00 | 21.10 | 11.40 | 0.355568E+09 | 544.95 | 25-OCT-13:20 | 13.50 | 10.37 |
November | 0.758450E+09 | 5572.36 | 04-NOV-15:30 | 20.55 | 15.94 | 0.317253E+09 | 544.93 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.419337E+09 | 2177.30 | 05-DEC-15:30 | 8.05 | 5.82 | 0.299070E+09 | 544.66 | 05-DEC-14:00 | 8.05 | 5.82 |
Annual Sum or Average | 0.410295E+11 | 0.435230E+10 | ||||||||
Minimum of Months | 0.347367E+09 | 1562.50 | 6.30 | 4.80 | 0.295417E+09 | 521.18 | 5.73 | 4.38 | ||
Maximum of Months | 0.809940E+10 | 30509.99 | 26.70 | 17.83 | 0.441533E+09 | 557.12 | 26.70 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.379992E+09 | 3519.56 | 17-JAN-06:01 | 1.20 | -0.4 | 0.00 | 0.00 | 01-JAN-00:10 | 1.20 | -0.4 |
February | 0.850509E+09 | 3295.72 | 28-FEB-06:15 | 10.60 | 9.74 | 0.00 | 0.00 | 01-FEB-00:10 | 10.60 | 9.74 |
March | 0.247165E+10 | 3999.16 | 20-MAR-05:15 | 5.97 | 4.27 | 0.00 | 0.00 | 01-MAR-00:10 | 5.97 | 4.27 |
April | 0.392297E+10 | 6114.55 | 03-APR-05:15 | 10.60 | 9.99 | 0.00 | 0.00 | 01-APR-00:10 | 10.60 | 9.99 |
May | 0.418212E+10 | 6267.08 | 08-MAY-05:15 | 9.60 | 9.49 | 0.00 | 0.00 | 01-MAY-00:10 | 9.60 | 9.49 |
June | 0.554191E+10 | 7219.08 | 05-JUN-05:15 | 10.77 | 9.45 | 0.00 | 0.00 | 01-JUN-00:10 | 10.77 | 9.45 |
July | 0.686767E+10 | 9502.36 | 31-JUL-05:15 | 17.40 | 14.58 | 0.00 | 0.00 | 01-JUL-00:10 | 17.40 | 14.58 |
August | 0.764935E+10 | 10047.84 | 14-AUG-05:10 | 15.37 | 13.48 | 0.00 | 0.00 | 01-AUG-00:10 | 15.37 | 13.48 |
September | 0.462168E+10 | 9154.38 | 11-SEP-15:40 | 23.30 | 16.04 | 0.00 | 0.00 | 01-SEP-00:10 | 23.30 | 16.04 |
October | 0.304565E+10 | 7557.40 | 10-OCT-05:15 | 12.20 | 11.16 | 0.00 | 0.00 | 01-OCT-00:10 | 12.20 | 11.16 |
November | 0.167769E+10 | 5854.67 | 06-NOV-06:15 | 11.47 | 8.44 | 0.00 | 0.00 | 01-NOV-00:10 | 11.47 | 8.44 |
December | 0.100660E+10 | 3147.35 | 04-DEC-06:15 | 3.13 | 1.80 | 0.00 | 0.00 | 01-DEC-00:10 | 3.13 | 1.80 |
Annual Sum or Average | 0.422178E+11 | 0.00 | ||||||||
Minimum of Months | 0.379992E+09 | 3147.35 | 1.20 | -0.4 | 0.00 | 0.00 | 1.20 | -0.4 | ||
Maximum of Months | 0.764935E+10 | 10047.84 | 23.30 | 16.04 | 0.00 | 0.00 | 23.30 | 16.04 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42349589.03 | 7413.87 | 14-JAN-05:11 | 2.20 | 1.37 | 0.00 | 0.00 | 01-JAN-00:10 | 2.20 | 1.37 |
February | 0.218909E+09 | 7055.39 | 13-FEB-05:01 | 1.28 | -1.7 | 0.00 | 0.00 | 01-FEB-00:10 | 1.28 | -1.7 |
March | 0.561206E+09 | 5748.36 | 06-MAR-05:11 | 6.70 | 6.18 | 0.00 | 0.00 | 01-MAR-00:10 | 6.70 | 6.18 |
April | 0.106521E+10 | 3529.07 | 27-APR-16:00 | 27.20 | 16.90 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 16.90 |
May | 0.220967E+10 | 3652.09 | 15-MAY-15:20 | 23.50 | 12.70 | 0.00 | 0.00 | 01-MAY-00:10 | 23.50 | 12.70 |
June | 0.314150E+10 | 4478.70 | 28-JUN-15:40 | 26.10 | 16.04 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 16.04 |
July | 0.409254E+10 | 5516.13 | 31-JUL-14:20 | 28.30 | 18.91 | 0.00 | 0.00 | 01-JUL-00:10 | 28.30 | 18.91 |
August | 0.470795E+10 | 6025.14 | 10-AUG-15:10 | 30.37 | 18.88 | 0.00 | 0.00 | 01-AUG-00:10 | 30.37 | 18.88 |
September | 0.292964E+10 | 6290.96 | 11-SEP-15:38 | 23.30 | 16.04 | 0.00 | 0.00 | 01-SEP-00:10 | 23.30 | 16.04 |
October | 0.114202E+10 | 2892.59 | 05-OCT-05:10 | 8.30 | 5.23 | 0.00 | 0.00 | 01-OCT-00:10 | 8.30 | 5.23 |
November | 0.356834E+09 | 6515.98 | 24-NOV-05:11 | 2.60 | 1.97 | 0.00 | 0.00 | 01-NOV-00:10 | 2.60 | 1.97 |
December | 0.148493E+09 | 7024.86 | 09-DEC-05:11 | 1.67 | 1.26 | 0.00 | 0.00 | 01-DEC-00:10 | 1.67 | 1.26 |
Annual Sum or Average | 0.206163E+11 | 0.00 | ||||||||
Minimum of Months | 42349589.03 | 2892.59 | 1.28 | -1.7 | 0.00 | 0.00 | 1.28 | -1.7 | ||
Maximum of Months | 0.470795E+10 | 7413.87 | 30.37 | 18.91 | 0.00 | 0.00 | 30.37 | 18.91 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 | 4.99 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 56228286.82 | 2143.08 | 27-FEB-15:30 | 19.70 | 12.30 | 0.00 | 0.00 | 01-FEB-00:10 | 19.70 | 12.30 |
March | 0.503871E+09 | 4625.20 | 14-MAR-15:10 | 16.28 | 10.42 | 0.00 | 0.00 | 01-MAR-00:10 | 16.28 | 10.42 |
April | 0.236286E+10 | 14470.53 | 27-APR-14:30 | 26.65 | 17.06 | 0.00 | 0.00 | 01-APR-00:10 | 26.65 | 17.06 |
May | 0.461006E+10 | 15213.31 | 15-MAY-14:20 | 23.30 | 13.21 | 0.00 | 0.00 | 01-MAY-00:10 | 23.30 | 13.21 |
June | 0.623802E+10 | 15279.87 | 28-JUN-14:20 | 25.37 | 15.62 | 0.00 | 0.00 | 01-JUN-00:10 | 25.37 | 15.62 |
July | 0.828849E+10 | 16814.66 | 24-JUL-13:50 | 29.22 | 18.16 | 0.00 | 0.00 | 01-JUL-00:10 | 29.22 | 18.16 |
August | 0.800684E+10 | 17637.62 | 10-AUG-14:30 | 29.80 | 19.03 | 0.00 | 0.00 | 01-AUG-00:10 | 29.80 | 19.03 |
September | 0.397916E+10 | 14031.10 | 11-SEP-14:13 | 22.97 | 15.78 | 0.00 | 0.00 | 01-SEP-00:10 | 22.97 | 15.78 |
October | 0.873310E+09 | 8079.71 | 04-OCT-14:50 | 21.60 | 11.48 | 0.00 | 0.00 | 01-OCT-00:10 | 21.60 | 11.48 |
November | 49595660.40 | 2924.56 | 04-NOV-14:15 | 21.10 | 15.94 | 0.00 | 0.00 | 01-NOV-00:10 | 21.10 | 15.94 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.349684E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.828849E+10 | 17637.62 | 29.80 | 19.03 | 0.00 | 0.00 | 29.80 | 19.03 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284914E+10 | 1841.45 | 05-JAN-16:10 | 5.73 | 4.38 | 95230013.16 | 126.82 | 19-JAN-14:09 | 5.40 | 2.91 |
February | 0.769327E+10 | 3933.74 | 07-FEB-16:50 | 7.30 | 3.84 | 86397199.11 | 126.83 | 24-FEB-10:00 | 13.30 | 12.07 |
March | 0.140776E+11 | 6965.26 | 31-MAR-24:00 | 8.00 | 7.45 | 0.103237E+09 | 126.83 | 09-MAR-14:00 | 8.00 | 7.45 |
April | 0.187604E+11 | 8091.82 | 26-APR-18:00 | 22.80 | 13.49 | 91605340.00 | 126.83 | 28-APR-09:00 | 11.70 | 11.07 |
May | 0.423328E+10 | 3409.16 | 31-MAY-24:00 | 13.00 | 10.11 | 99235946.07 | 126.84 | 31-MAY-13:00 | 13.00 | 10.11 |
June | 0.916089E+10 | 5295.33 | 30-JUN-24:00 | 15.50 | 12.58 | 98960733.24 | 126.84 | 12-JUN-13:00 | 15.50 | 12.58 |
July | 0.147244E+11 | 7240.55 | 31-JUL-24:00 | 17.40 | 14.08 | 91884446.09 | 126.84 | 11-JUL-09:00 | 17.40 | 14.08 |
August | 0.196792E+11 | 8601.39 | 06-AUG-19:06 | 21.43 | 14.77 | 0.103241E+09 | 126.83 | 02-AUG-09:09 | 21.43 | 14.77 |
September | 0.417131E+10 | 3293.73 | 30-SEP-24:00 | 14.30 | 12.32 | 91611631.22 | 126.84 | 13-SEP-13:09 | 14.30 | 12.32 |
October | 0.909869E+10 | 4987.21 | 31-OCT-24:00 | 9.10 | 7.85 | 95231733.84 | 126.83 | 26-OCT-13:00 | 9.10 | 7.85 |
November | 0.135025E+11 | 5801.03 | 11-NOV-16:05 | 6.42 | 5.03 | 94301365.83 | 126.83 | 01-NOV-13:00 | 6.42 | 5.03 |
December | 0.188853E+11 | 7644.96 | 05-DEC-15:50 | 6.75 | 4.97 | 91880897.39 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.136836E+12 | 0.114282E+10 | ||||||||
Minimum of Months | 0.284914E+10 | 1841.45 | 5.73 | 3.84 | 86397199.11 | 126.82 | 5.40 | 2.91 | ||
Maximum of Months | 0.196792E+11 | 8601.39 | 22.80 | 14.77 | 0.103241E+09 | 126.84 | 21.43 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.453203E+09 | 1325.82 | 20-JAN-16:20 | 5.20 | 3.48 | 94594536.61 | 126.82 | 19-JAN-14:09 | 5.20 | 3.48 |
February | 0.535660E+10 | 3575.15 | 08-FEB-17:00 | 6.70 | 3.26 | 86397157.92 | 126.83 | 24-FEB-10:00 | 13.30 | 12.07 |
March | 0.120293E+11 | 6120.46 | 31-MAR-23:40 | 8.10 | 7.54 | 0.103237E+09 | 126.83 | 09-MAR-14:00 | 8.10 | 7.54 |
April | 0.170258E+11 | 7713.67 | 26-APR-18:00 | 22.80 | 13.49 | 91605365.50 | 126.83 | 28-APR-09:00 | 11.70 | 11.07 |
May | 0.343623E+10 | 3164.02 | 31-MAY-23:50 | 13.17 | 10.29 | 99235799.27 | 126.84 | 31-MAY-13:00 | 13.17 | 10.29 |
June | 0.831017E+10 | 4954.98 | 30-JUN-24:00 | 15.50 | 12.58 | 98960575.56 | 126.84 | 12-JUN-13:00 | 15.50 | 12.58 |
July | 0.137524E+11 | 6958.79 | 31-JUL-24:00 | 17.40 | 14.08 | 91884319.91 | 126.83 | 11-JUL-09:00 | 17.40 | 14.08 |
August | 0.185510E+11 | 8132.04 | 06-AUG-18:32 | 22.47 | 15.07 | 0.103240E+09 | 126.83 | 02-AUG-09:00 | 22.47 | 15.07 |
September | 0.346608E+10 | 2913.02 | 30-SEP-23:50 | 14.25 | 12.27 | 91611278.47 | 126.84 | 13-SEP-13:09 | 14.25 | 12.27 |
October | 0.750825E+10 | 4075.00 | 31-OCT-24:00 | 9.10 | 7.85 | 95231658.29 | 126.83 | 26-OCT-13:00 | 9.10 | 7.85 |
November | 0.109625E+11 | 5242.85 | 04-NOV-16:02 | 19.82 | 15.68 | 94301325.68 | 126.83 | 01-NOV-13:00 | 19.82 | 15.68 |
December | 0.154377E+11 | 7021.57 | 05-DEC-16:00 | 6.10 | 4.53 | 91880927.00 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.116289E+12 | 0.114218E+10 | ||||||||
Minimum of Months | 0.453203E+09 | 1325.82 | 5.20 | 3.26 | 86397157.92 | 126.82 | 5.20 | 3.48 | ||
Maximum of Months | 0.185510E+11 | 8132.04 | 22.80 | 15.68 | 0.103240E+09 | 126.84 | 22.47 | 15.68 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142300E+09 | 1228.68 | 05-JAN-16:20 | 5.37 | 4.14 | 92277170.84 | 127.68 | 26-JAN-10:50 | 4.90 | 4.45 |
February | 0.385534E+10 | 3426.61 | 08-FEB-17:00 | 6.70 | 3.26 | 86397155.41 | 126.83 | 24-FEB-10:00 | 13.30 | 12.07 |
March | 0.106440E+11 | 5598.64 | 31-MAR-23:20 | 8.20 | 7.64 | 0.103237E+09 | 126.83 | 09-MAR-14:00 | 8.20 | 7.64 |
April | 0.162039E+11 | 7786.27 | 26-APR-18:00 | 22.80 | 13.49 | 91605389.81 | 126.83 | 28-APR-09:00 | 11.70 | 11.07 |
May | 0.291192E+10 | 3079.32 | 31-MAY-23:30 | 13.50 | 10.66 | 99236071.50 | 126.84 | 31-MAY-13:00 | 13.50 | 10.66 |
June | 0.807015E+10 | 4859.14 | 30-JUN-23:40 | 15.63 | 12.81 | 98960612.09 | 126.84 | 12-JUN-13:00 | 15.63 | 12.81 |
July | 0.136099E+11 | 6918.04 | 31-JUL-23:50 | 17.63 | 14.21 | 91884434.27 | 126.84 | 11-JUL-09:00 | 17.63 | 14.21 |
August | 0.183824E+11 | 8303.82 | 06-AUG-18:32 | 22.47 | 15.07 | 0.103240E+09 | 126.83 | 02-AUG-09:09 | 22.47 | 15.07 |
September | 0.292894E+10 | 2543.36 | 10-SEP-17:40 | 21.13 | 13.95 | 91610581.99 | 126.84 | 13-SEP-13:09 | 21.38 | 16.98 |
October | 0.625945E+10 | 4073.59 | 04-OCT-16:50 | 20.68 | 11.37 | 95231619.20 | 126.83 | 26-OCT-13:00 | 13.30 | 12.35 |
November | 0.928662E+10 | 5148.64 | 04-NOV-16:02 | 19.82 | 15.68 | 94301348.22 | 126.83 | 01-NOV-13:00 | 19.82 | 15.68 |
December | 0.135940E+11 | 6823.05 | 05-DEC-16:10 | 6.10 | 4.53 | 91880940.21 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.105889E+12 | 0.113986E+10 | ||||||||
Minimum of Months | 0.142300E+09 | 1228.68 | 5.37 | 3.26 | 86397155.41 | 126.82 | 4.90 | 4.45 | ||
Maximum of Months | 0.183824E+11 | 8303.82 | 22.80 | 15.68 | 0.103240E+09 | 127.68 | 22.47 | 16.98 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235304E+12 | 90197.08 | 12-JAN-17:00 | 7.20 | 5.41 | 0.206144E+10 | 2745.29 | 09-JAN-14:50 | 7.20 | 5.41 |
February | 0.433900E+12 | 182493.28 | 27-FEB-17:00 | 18.90 | 12.17 | 0.187024E+10 | 2745.78 | 22-FEB-14:39 | 18.90 | 12.17 |
March | 0.727678E+12 | 357930.47 | 31-MAR-24:00 | 8.00 | 7.45 | 0.223483E+10 | 2748.62 | 10-MAR-14:50 | 8.00 | 7.45 |
April | 0.941873E+12 | 367597.33 | 01-APR-18:12 | 24.67 | 11.75 | 0.198434E+10 | 2792.26 | 27-APR-15:00 | 27.20 | 16.90 |
May | 0.239628E+12 | 175694.43 | 31-MAY-24:00 | 13.00 | 10.11 | 0.214809E+10 | 2746.43 | 05-MAY-13:00 | 13.00 | 10.11 |
June | 0.468890E+12 | 267209.41 | 30-JUN-24:00 | 15.50 | 12.58 | 0.214221E+10 | 2747.05 | 21-JUN-13:09 | 15.50 | 12.58 |
July | 0.731052E+12 | 359887.23 | 31-JUL-24:00 | 17.40 | 14.08 | 0.199014E+10 | 2750.11 | 14-JUL-13:09 | 17.40 | 14.08 |
August | 0.975468E+12 | 371714.43 | 13-AUG-18:42 | 24.65 | 17.13 | 0.229612E+10 | 3506.97 | 29-AUG-13:20 | 29.17 | 20.09 |
September | 0.233538E+12 | 175399.34 | 30-SEP-24:00 | 14.30 | 12.32 | 0.198297E+10 | 2746.87 | 14-SEP-13:00 | 14.30 | 12.32 |
October | 0.484468E+12 | 266740.21 | 31-OCT-24:00 | 9.10 | 7.85 | 0.206143E+10 | 2746.58 | 02-OCT-13:20 | 9.10 | 7.85 |
November | 0.705432E+12 | 274970.72 | 06-NOV-15:00 | 11.10 | 10.22 | 0.204134E+10 | 2747.95 | 17-NOV-14:30 | 10.30 | 8.83 |
December | 0.973416E+12 | 366249.10 | 04-DEC-17:00 | 6.70 | 4.39 | 0.198901E+10 | 2747.02 | 28-DEC-10:09 | 10.10 | 8.95 |
Annual Sum or Average | 0.715065E+13 | 0.248022E+11 | ||||||||
Minimum of Months | 0.233538E+12 | 90197.08 | 6.70 | 4.39 | 0.187024E+10 | 2745.29 | 7.20 | 5.41 | ||
Maximum of Months | 0.975468E+12 | 371714.43 | 24.67 | 17.13 | 0.229612E+10 | 3506.97 | 29.17 | 20.09 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 92145933.23 | 9690.82 | 11-JAN-05:14 | 10.00 |
February | 83602269.80 | 10011.74 | 28-FEB-05:17 | 10.20 |
March | 69590457.63 | 9911.32 | 15-MAR-04:17 | 8.70 |
April | 93267374.57 | 11969.75 | 01-APR-16:01 | 27.12 |
May | 0.170829E+09 | 10016.34 | 23-MAY-04:17 | 8.13 |
June | 0.102083E+09 | 9996.47 | 07-JUN-04:17 | 10.00 |
July | 0.273728E+09 | 10221.46 | 22-JUL-16:01 | 25.92 |
August | 0.176764E+09 | 9624.60 | 15-AUG-04:57 | 12.70 |
September | 0.274896E+09 | 10039.67 | 19-SEP-04:17 | 12.20 |
October | 0.241191E+09 | 10012.08 | 24-OCT-04:17 | 6.67 |
November | 0.207473E+09 | 9942.19 | 03-NOV-04:17 | 10.60 |
December | 58857901.06 | 9748.13 | 01-DEC-06:00 | 3.30 |
Annual Sum or Average | 0.184443E+10 | |||
Minimum of Months | 58857901.06 | 9624.60 | 3.30 | |
Maximum of Months | 0.274896E+09 | 11969.75 | 27.12 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.496865E+09 | 39567.37 | 02-JAN-05:11 | 6.10 |
February | 4350934.21 | 29006.23 | 21-FEB-06:03 | 1.70 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 2913501.46 | 29135.01 | 26-DEC-06:02 | -0.8 |
Annual Sum or Average | 0.504130E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.496865E+09 | 39567.37 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281481E+10 | 68232.35 | 02-JAN-05:21 | 6.10 |
February | 0.122340E+10 | 65717.40 | 21-FEB-05:01 | 1.70 |
March | 0.260882E+09 | 60814.61 | 06-MAR-05:11 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 46222631.94 | 55194.05 | 30-OCT-05:02 | 7.20 |
November | 0.762516E+09 | 61348.37 | 13-NOV-05:01 | 1.20 |
December | 0.162020E+10 | 66135.94 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.672804E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.281481E+10 | 68232.35 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1389729.49 | 7810.25 | 17-JAN-06:01 | 1.20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 1389729.49 | |||
Minimum of Months | 0.00 | 0.00 | 1.20 | |
Maximum of Months | 1389729.49 | 7810.25 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4776927.46 | 6711.17 | 17-JAN-06:01 | 1.20 |
February | 614543.47 | 3332.76 | 18-FEB-06:01 | -1.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 5391470.93 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 4776927.46 | 6711.17 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 64907409.28 | 12471.08 | 17-JAN-05:01 | 1.60 |
February | 12774534.68 | 9764.39 | 18-FEB-06:01 | -1.8 |
March | 95726.04 | 638.17 | 06-MAR-06:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 355126.26 | 2296.22 | 24-NOV-06:03 | 2.02 |
December | 6824967.81 | 9598.24 | 26-DEC-06:02 | -0.8 |
Annual Sum or Average | 84957764.07 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 64907409.28 | 12471.08 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207664E+10 | 10900.58 | 02-JAN-05:11 | 6.10 |
February | 0.807926E+09 | 10256.30 | 21-FEB-04:53 | 1.70 |
March | 0.149513E+09 | 9543.15 | 06-MAR-05:11 | 6.70 |
April | 23804948.08 | 8810.95 | 11-APR-05:03 | 5.60 |
May | 610437.28 | 5086.98 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 30657888.01 | 9003.16 | 30-OCT-05:02 | 7.20 |
November | 0.377534E+09 | 9539.62 | 24-NOV-05:11 | 2.60 |
December | 0.117070E+10 | 10465.86 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.463739E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.207664E+10 | 10900.58 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128283E+10 | 15813.83 | 02-JAN-05:11 | 6.10 |
February | 0.463533E+09 | 14159.26 | 21-FEB-05:01 | 1.70 |
March | 79554709.30 | 13576.03 | 06-MAR-05:11 | 6.70 |
April | 15032707.55 | 10741.60 | 18-APR-05:02 | 3.30 |
May | 542338.54 | 4497.31 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 21156986.49 | 11719.97 | 30-OCT-05:02 | 7.20 |
November | 0.250694E+09 | 13657.41 | 24-NOV-05:11 | 2.60 |
December | 0.763126E+09 | 15097.07 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.287647E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.128283E+10 | 15813.83 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140946E+10 | 22786.09 | 02-JAN-05:11 | 6.10 |
February | 0.431117E+09 | 20502.01 | 21-FEB-05:01 | 1.70 |
March | 67729564.75 | 19458.59 | 06-MAR-05:11 | 6.70 |
April | 14570505.70 | 15050.88 | 18-APR-05:02 | 3.30 |
May | 800704.91 | 6572.32 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 10430678.19 | 15588.77 | 28-OCT-05:02 | 8.22 |
November | 0.252289E+09 | 19566.53 | 30-NOV-05:11 | 5.60 |
December | 0.819790E+09 | 21238.67 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.300619E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.140946E+10 | 22786.09 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.803316E+09 | 15639.81 | 02-JAN-05:11 | 6.10 |
February | 0.259974E+09 | 13891.78 | 21-FEB-05:01 | 1.70 |
March | 31936203.10 | 12787.10 | 06-MAR-05:11 | 6.70 |
April | 3358593.84 | 6054.03 | 18-APR-05:02 | 3.30 |
May | 252639.48 | 2105.33 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 3418518.63 | 7621.91 | 28-OCT-05:02 | 8.22 |
November | 0.118647E+09 | 12935.15 | 30-NOV-05:11 | 5.60 |
December | 0.374386E+09 | 13868.36 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.159529E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.803316E+09 | 15639.81 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486702E+10 | 12886.25 | 02-JAN-05:21 | 6.10 |
February | 0.299263E+10 | 12768.54 | 19-FEB-08:63 | -4.7 |
March | 0.113420E+10 | 12322.33 | 06-MAR-05:11 | 6.70 |
April | 0.391592E+09 | 11233.89 | 11-APR-04:11 | 5.20 |
May | 38398554.63 | 10386.74 | 18-MAY-04:12 | 6.33 |
June | 1754159.40 | 7396.67 | 14-JUN-05:03 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 10331758.22 | 9913.79 | 27-SEP-05:02 | 7.38 |
October | 0.523118E+09 | 11599.76 | 30-OCT-04:11 | 7.20 |
November | 0.197157E+10 | 12555.07 | 13-NOV-04:01 | 1.60 |
December | 0.386724E+10 | 12651.10 | 26-DEC-03:43 | -0.9 |
Annual Sum or Average | 0.157979E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.7 | |
Maximum of Months | 0.486702E+10 | 12886.25 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300110E+10 | 18380.79 | 02-JAN-05:21 | 6.10 |
February | 0.165577E+10 | 18022.19 | 21-FEB-05:01 | 1.70 |
March | 0.603054E+09 | 17582.78 | 06-MAR-05:11 | 6.70 |
April | 0.196826E+09 | 15953.20 | 11-APR-04:11 | 5.20 |
May | 26511878.08 | 11834.66 | 18-MAY-05:02 | 5.60 |
June | 1684792.36 | 5818.94 | 14-JUN-05:03 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 5823520.80 | 10781.51 | 27-SEP-05:02 | 7.38 |
October | 0.309329E+09 | 16124.59 | 30-OCT-04:11 | 7.20 |
November | 0.122185E+10 | 18012.05 | 24-NOV-05:11 | 2.60 |
December | 0.239297E+10 | 17890.44 | 18-DEC-05:11 | 3.50 |
Annual Sum or Average | 0.941491E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.70 | |
Maximum of Months | 0.300110E+10 | 18380.79 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.344348E+10 | 27275.83 | 02-JAN-05:21 | 6.10 |
February | 0.178339E+10 | 26612.69 | 21-FEB-05:01 | 1.70 |
March | 0.764939E+09 | 26134.87 | 06-MAR-05:11 | 6.70 |
April | 0.300640E+09 | 23428.17 | 11-APR-04:11 | 5.20 |
May | 40253768.10 | 19627.85 | 11-MAY-05:02 | 5.10 |
June | 1711960.10 | 6986.48 | 14-JUN-05:03 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 5635466.90 | 10857.05 | 27-SEP-05:02 | 7.38 |
October | 0.331556E+09 | 23327.48 | 16-OCT-04:11 | 7.20 |
November | 0.143079E+10 | 26394.26 | 24-NOV-05:11 | 2.60 |
December | 0.283887E+10 | 26530.60 | 18-DEC-05:11 | 3.50 |
Annual Sum or Average | 0.109413E+11 | |||
Minimum of Months | 0.00 | 0.00 | 1.70 | |
Maximum of Months | 0.344348E+10 | 27275.83 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213937E+10 | 18808.41 | 02-JAN-05:21 | 6.10 |
February | 0.102233E+10 | 18293.31 | 21-FEB-05:01 | 1.70 |
March | 0.380675E+09 | 17585.46 | 06-MAR-05:11 | 6.70 |
April | 0.115427E+09 | 15566.43 | 11-APR-04:11 | 5.20 |
May | 14080598.67 | 11205.23 | 18-MAY-05:02 | 5.60 |
June | 24082.88 | 160.55 | 14-JUN-05:03 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 5999.78 | 60.00 | 27-SEP-05:05 | 7.38 |
October | 0.153319E+09 | 15501.89 | 30-OCT-04:11 | 7.20 |
November | 0.718131E+09 | 17499.57 | 24-NOV-05:11 | 2.60 |
December | 0.144666E+10 | 18025.83 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.599001E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.213937E+10 | 18808.41 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486235E+09 | 10412.48 | 02-JAN-05:11 | 6.10 |
February | 0.188407E+09 | 9086.56 | 06-FEB-05:11 | 4.23 |
March | 70488710.12 | 10190.80 | 06-MAR-05:11 | 6.70 |
April | 0.141588E+09 | 11167.08 | 10-APR-04:12 | 9.63 |
May | 94749926.64 | 9457.40 | 07-MAY-15:41 | 22.12 |
June | 82835364.84 | 7886.60 | 26-JUN-04:12 | 12.80 |
July | 0.128686E+09 | 10960.51 | 30-JUL-16:31 | 27.07 |
August | 0.128859E+09 | 11781.94 | 13-AUG-14:11 | 27.50 |
September | 64638414.41 | 11114.26 | 10-SEP-14:31 | 22.60 |
October | 97891894.58 | 9078.77 | 23-OCT-04:11 | 10.60 |
November | 81374709.00 | 10884.36 | 27-NOV-05:11 | 12.03 |
December | 79219248.77 | 10967.55 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.164497E+10 | |||
Minimum of Months | 64638414.41 | 7886.60 | -0.6 | |
Maximum of Months | 0.486235E+09 | 11781.94 | 27.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281532E+10 | 15134.57 | 02-JAN-06:02 | 6.10 |
February | 0.147941E+10 | 10474.09 | 12-FEB-13:23 | 6.40 |
March | 0.714180E+09 | 6444.29 | 15-MAR-05:02 | 8.03 |
April | 0.227199E+09 | 11534.68 | 02-APR-15:32 | 20.60 |
May | 77873458.29 | 10804.21 | 14-MAY-14:42 | 23.22 |
June | 55093170.49 | 8982.13 | 25-JUN-15:01 | 21.70 |
July | 71813023.82 | 11698.67 | 23-JUL-16:41 | 26.88 |
August | 57659970.26 | 12225.34 | 13-AUG-14:11 | 27.50 |
September | 47350965.11 | 11139.04 | 10-SEP-16:02 | 22.20 |
October | 0.315482E+09 | 8416.15 | 29-OCT-12:32 | 10.93 |
November | 0.985339E+09 | 10012.08 | 11-NOV-12:52 | 6.70 |
December | 0.160415E+10 | 6138.43 | 03-DEC-14:03 | 12.20 |
Annual Sum or Average | 0.845087E+10 | |||
Minimum of Months | 47350965.11 | 6138.43 | 6.10 | |
Maximum of Months | 0.281532E+10 | 15134.57 | 27.50 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.682902E+10 | 22399.04 | 17-JAN-06:12 | 1.30 |
February | 0.441828E+10 | 20614.98 | 21-FEB-05:12 | 1.70 |
March | 0.254219E+10 | 15610.80 | 06-MAR-05:22 | 6.70 |
April | 0.127876E+10 | 11534.47 | 27-APR-05:03 | 9.37 |
May | 0.663994E+09 | 12679.97 | 04-MAY-05:02 | 10.78 |
June | 0.336463E+09 | 13122.80 | 02-JUN-05:02 | 10.18 |
July | 0.200030E+09 | 11450.92 | 07-JUL-05:03 | 11.47 |
August | 0.249639E+09 | 11517.66 | 21-AUG-05:03 | 11.20 |
September | 0.630722E+09 | 11957.02 | 08-SEP-05:02 | 10.18 |
October | 0.178558E+10 | 8316.56 | 30-OCT-05:02 | 7.20 |
November | 0.358008E+10 | 17142.75 | 13-NOV-06:13 | 1.70 |
December | 0.570435E+10 | 21171.83 | 26-DEC-05:12 | -0.6 |
Annual Sum or Average | 0.282191E+11 | |||
Minimum of Months | 0.200030E+09 | 8316.56 | -0.6 | |
Maximum of Months | 0.682902E+10 | 22399.04 | 11.47 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.365461E+09 | 550.06 | 03-JAN-00:10 | 7.20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.365461E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.365461E+09 | 550.06 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.796810E+09 | 602.32 | 08-JAN-17:35 | 2.93 |
February | 25895068.85 | 437.88 | 20-FEB-07:30 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 1211008.90 | 426.30 | 18-MAY-04:12 | 6.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.823916E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.796810E+09 | 602.32 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.968216E+10 | 10174.14 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.878253E+10 | 10174.14 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.104353E+11 | 10174.14 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.932187E+10 | 10174.14 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.100587E+11 | 10174.14 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.100099E+11 | 10174.14 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.937071E+10 | 10174.14 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.104353E+11 | 10174.14 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.932187E+10 | 10174.14 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.968216E+10 | 10174.14 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.956821E+10 | 10174.14 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.937071E+10 | 10174.14 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.116039E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.878253E+10 | 10174.14 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.104353E+11 | 10174.14 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.754976E+09 | 1147.25 | 02-JAN-16:30 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.618592E+09 | 1035.22 | 02-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.676041E+09 | 901.47 | 22-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.575229E+09 | 640.24 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.604131E+09 | 588.59 | 17-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.590382E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.556514E+09 | 633.09 | 12-JUL-08:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.626693E+09 | 626.70 | 02-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.593382E+09 | 909.01 | 25-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.661556E+09 | 1131.95 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.729433E+09 | 1147.25 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.757154E+09 | 1147.25 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.774408E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.556514E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.757154E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.473212E+09 | 739.33 | 02-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.393820E+09 | 674.87 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.433679E+09 | 553.82 | 22-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.370852E+09 | 393.53 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.391074E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.382543E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.360418E+09 | 376.13 | 12-JUL-08:30 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.405626E+09 | 391.90 | 02-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.379842E+09 | 560.58 | 25-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.421003E+09 | 726.95 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.460764E+09 | 739.33 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.471769E+09 | 739.33 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.494460E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.360418E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.473212E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.717840E+09 | 1147.28 | 02-JAN-16:30 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.599311E+09 | 1008.57 | 02-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.669392E+09 | 890.37 | 22-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.575714E+09 | 638.00 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.606793E+09 | 589.78 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.593407E+09 | 545.88 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.561125E+09 | 627.30 | 12-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.630403E+09 | 625.30 | 02-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.590624E+09 | 900.68 | 25-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.646922E+09 | 1129.06 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.700500E+09 | 1147.28 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.712972E+09 | 1147.28 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.760500E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.561125E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.717840E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.472792E+09 | 739.33 | 02-JAN-16:30 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.390340E+09 | 648.78 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.433384E+09 | 591.18 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.370560E+09 | 495.88 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.389660E+09 | 391.14 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.380590E+09 | 383.96 | 29-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.360099E+09 | 512.06 | 12-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.404243E+09 | 503.19 | 28-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.381856E+09 | 594.85 | 25-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.421170E+09 | 729.70 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.458501E+09 | 739.33 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.471180E+09 | 739.33 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.493438E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.360099E+09 | 383.96 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.472792E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.752075E+09 | 1147.25 | 02-JAN-16:30 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.616695E+09 | 1033.91 | 02-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.674635E+09 | 898.77 | 22-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.574729E+09 | 636.54 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.603835E+09 | 581.92 | 17-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.589942E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.555893E+09 | 628.90 | 12-JUL-08:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.626153E+09 | 622.19 | 02-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.592349E+09 | 906.37 | 25-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.659794E+09 | 1131.77 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.726425E+09 | 1147.25 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.754298E+09 | 1147.25 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.772682E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.555893E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.754298E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.472043E+09 | 739.33 | 02-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.393001E+09 | 673.22 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.432941E+09 | 549.66 | 22-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.370550E+09 | 390.78 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.390789E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.382296E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.360232E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.405328E+09 | 388.77 | 02-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.379496E+09 | 556.56 | 25-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.420237E+09 | 726.68 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.459558E+09 | 739.33 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.470502E+09 | 739.33 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.493697E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.360232E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.472043E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.716992E+09 | 1147.28 | 02-JAN-16:30 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.598618E+09 | 1006.98 | 02-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.668717E+09 | 887.62 | 22-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.575328E+09 | 634.19 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.606369E+09 | 583.17 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.593123E+09 | 545.88 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.560705E+09 | 622.85 | 12-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.629874E+09 | 620.71 | 02-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.590133E+09 | 897.98 | 25-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.646221E+09 | 1128.87 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.699782E+09 | 1147.28 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.712175E+09 | 1147.28 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.759804E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.560705E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.716992E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.471543E+09 | 739.33 | 02-JAN-16:30 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.389658E+09 | 646.44 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.432592E+09 | 587.33 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.370176E+09 | 489.46 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.389382E+09 | 387.61 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.380311E+09 | 380.02 | 29-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.359744E+09 | 505.62 | 12-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.403918E+09 | 496.59 | 28-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.381420E+09 | 591.09 | 25-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.420456E+09 | 729.45 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.457137E+09 | 739.33 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.469880E+09 | 739.33 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.492622E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.359744E+09 | 380.02 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.471543E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.751931E+09 | 1147.25 | 02-JAN-16:30 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.616612E+09 | 1033.70 | 02-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.674538E+09 | 898.27 | 22-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.574701E+09 | 636.39 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.603821E+09 | 581.66 | 17-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.589922E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.555880E+09 | 628.74 | 12-JUL-08:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.626114E+09 | 622.01 | 02-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.592325E+09 | 905.88 | 25-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.659735E+09 | 1131.74 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.726279E+09 | 1147.25 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.754091E+09 | 1147.25 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.772595E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.555880E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.754091E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.471972E+09 | 739.33 | 02-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.392971E+09 | 673.09 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.432907E+09 | 549.31 | 22-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.370566E+09 | 390.65 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.390779E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.382283E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.360228E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.405320E+09 | 388.63 | 02-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.379496E+09 | 556.22 | 25-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.420291E+09 | 726.65 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.459485E+09 | 739.33 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.470445E+09 | 739.33 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.493674E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.360228E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.471972E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.716925E+09 | 1147.28 | 02-JAN-16:30 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.598591E+09 | 1006.73 | 02-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.668681E+09 | 887.10 | 22-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.575293E+09 | 634.03 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.606351E+09 | 582.91 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.593110E+09 | 545.88 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.560693E+09 | 622.68 | 12-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.629858E+09 | 620.53 | 02-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.590110E+09 | 897.48 | 25-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.646186E+09 | 1128.84 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.699738E+09 | 1147.28 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.712103E+09 | 1147.28 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.759764E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.560693E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.716925E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.471430E+09 | 739.33 | 02-JAN-16:30 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.389623E+09 | 646.26 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.432546E+09 | 587.02 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.370165E+09 | 488.96 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.389369E+09 | 387.47 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.380304E+09 | 379.87 | 29-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.359696E+09 | 505.20 | 12-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.403910E+09 | 496.26 | 28-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.381402E+09 | 590.79 | 25-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.420416E+09 | 729.44 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.457071E+09 | 739.33 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.469717E+09 | 739.33 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.492565E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.359696E+09 | 379.87 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.471430E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.274130E+10 | 2868.67 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.248656E+10 | 2868.67 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.295472E+10 | 2868.67 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.263917E+10 | 2868.67 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.284801E+10 | 2868.67 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.283424E+10 | 2868.67 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.265294E+10 | 2868.67 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.295472E+10 | 2868.67 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.263917E+10 | 2868.67 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.274130E+10 | 2868.67 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.270917E+10 | 2868.67 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.265294E+10 | 2868.67 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.328542E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.248656E+10 | 2868.67 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.295472E+10 | 2868.67 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.100587E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.100099E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.956821E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.116039E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.754976E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802893E+09 |
February | 0.136985E+10 | 0.618592E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718000E+09 |
March | 0.163685E+10 | 0.676041E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690581E+09 |
April | 0.145243E+10 | 0.575229E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 908436.81 | 0.653125E+09 |
May | 0.157338E+10 | 0.604131E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38450.61 | 0.499062E+09 |
June | 0.156900E+10 | 0.590382E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 386366.34 | 0.413578E+09 |
July | 0.145680E+10 | 0.556514E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4449899.43 | 0.344630E+09 |
August | 0.163685E+10 | 0.626693E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8108053.89 | 0.276528E+09 |
September | 0.145243E+10 | 0.593382E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38315.18 | 0.233237E+09 |
October | 0.150991E+10 | 0.661556E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553576E+09 |
November | 0.149516E+10 | 0.729433E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643487E+09 |
December | 0.145680E+10 | 0.757154E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703076E+09 |
Annual Sum or Average | 0.181194E+11 | 0.774408E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13929522.26 | 0.653177E+10 |
Minimum of Months | 0.136985E+10 | 0.556514E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233237E+09 |
Maximum of Months | 0.163685E+10 | 0.757154E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8108053.89 | 0.802893E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.473212E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529086E+09 |
February | 0.882782E+09 | 0.393820E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476350E+09 |
March | 0.105485E+10 | 0.433679E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452905E+09 |
April | 0.936002E+09 | 0.370852E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 605656.11 | 0.428219E+09 |
May | 0.101394E+10 | 0.391074E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25632.75 | 0.334376E+09 |
June | 0.101113E+10 | 0.382543E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 257572.08 | 0.276171E+09 |
July | 0.938820E+09 | 0.360418E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2399812.78 | 0.226627E+09 |
August | 0.105485E+10 | 0.405626E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5270769.28 | 0.180644E+09 |
September | 0.936002E+09 | 0.379842E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25541.88 | 0.156013E+09 |
October | 0.973041E+09 | 0.421003E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364719E+09 |
November | 0.963541E+09 | 0.460764E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416881E+09 |
December | 0.938820E+09 | 0.471769E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453254E+09 |
Annual Sum or Average | 0.116768E+11 | 0.494460E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8584984.87 | 0.429525E+10 |
Minimum of Months | 0.882782E+09 | 0.360418E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156013E+09 |
Maximum of Months | 0.105485E+10 | 0.473212E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5270769.28 | 0.529086E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.717840E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778272E+09 |
February | 0.136988E+10 | 0.599311E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722667E+09 |
March | 0.163688E+10 | 0.669392E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686626E+09 |
April | 0.145246E+10 | 0.575714E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 680490.39 | 0.651856E+09 |
May | 0.157341E+10 | 0.606793E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38445.00 | 0.502649E+09 |
June | 0.156904E+10 | 0.593407E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 386346.15 | 0.416792E+09 |
July | 0.145684E+10 | 0.561125E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3367078.06 | 0.349885E+09 |
August | 0.163688E+10 | 0.630403E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7832908.37 | 0.283799E+09 |
September | 0.145246E+10 | 0.590624E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38159.62 | 0.240561E+09 |
October | 0.150994E+10 | 0.646922E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557060E+09 |
November | 0.149520E+10 | 0.700500E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624738E+09 |
December | 0.145684E+10 | 0.712972E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681202E+09 |
Annual Sum or Average | 0.181198E+11 | 0.760500E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12343427.59 | 0.649611E+10 |
Minimum of Months | 0.136988E+10 | 0.561125E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240561E+09 |
Maximum of Months | 0.163688E+10 | 0.717840E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7832908.37 | 0.778272E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.472792E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566123E+09 |
February | 0.882782E+09 | 0.390340E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524587E+09 |
March | 0.105485E+10 | 0.433384E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509542E+09 |
April | 0.936002E+09 | 0.370560E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 346258.64 | 0.491421E+09 |
May | 0.101394E+10 | 0.389660E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25631.91 | 0.362876E+09 |
June | 0.101113E+10 | 0.380590E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 257504.02 | 0.307796E+09 |
July | 0.938820E+09 | 0.360099E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2161081.40 | 0.271333E+09 |
August | 0.105485E+10 | 0.404243E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5199636.24 | 0.223348E+09 |
September | 0.936002E+09 | 0.381856E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25538.42 | 0.173172E+09 |
October | 0.973041E+09 | 0.421170E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408306E+09 |
November | 0.963541E+09 | 0.458501E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475797E+09 |
December | 0.938820E+09 | 0.471180E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527700E+09 |
Annual Sum or Average | 0.116768E+11 | 0.493438E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8015650.63 | 0.484200E+10 |
Minimum of Months | 0.882782E+09 | 0.360099E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173172E+09 |
Maximum of Months | 0.105485E+10 | 0.472792E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5199636.24 | 0.566123E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.752075E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155998E+10 |
February | 0.136985E+10 | 0.616695E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141263E+10 |
March | 0.163685E+10 | 0.674635E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139418E+10 |
April | 0.145243E+10 | 0.574729E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3099334.27 | 0.134163E+10 |
May | 0.157338E+10 | 0.603835E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64020.34 | 0.108146E+10 |
June | 0.156900E+10 | 0.589942E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 795771.48 | 0.898482E+09 |
July | 0.145680E+10 | 0.555893E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13385962.44 | 0.751566E+09 |
August | 0.163685E+10 | 0.626153E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19573250.83 | 0.612011E+09 |
September | 0.145243E+10 | 0.592349E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67131.38 | 0.499831E+09 |
October | 0.150991E+10 | 0.659794E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111656E+10 |
November | 0.149516E+10 | 0.726425E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124948E+10 |
December | 0.145680E+10 | 0.754298E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134643E+10 |
Annual Sum or Average | 0.181194E+11 | 0.772682E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36985470.73 | 0.132642E+11 |
Minimum of Months | 0.136985E+10 | 0.555893E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499831E+09 |
Maximum of Months | 0.163685E+10 | 0.754298E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19573250.83 | 0.155998E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.472043E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104191E+10 |
February | 0.649041E+09 | 0.393001E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.968347E+09 |
March | 0.773965E+09 | 0.432941E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.958717E+09 |
April | 0.688021E+09 | 0.370550E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1444348.78 | 0.931417E+09 |
May | 0.744847E+09 | 0.390789E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40111.64 | 0.747179E+09 |
June | 0.742030E+09 | 0.382296E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 509750.57 | 0.625915E+09 |
July | 0.690839E+09 | 0.360232E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4899119.39 | 0.521133E+09 |
August | 0.773965E+09 | 0.405328E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11396675.94 | 0.428859E+09 |
September | 0.688021E+09 | 0.379496E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42917.89 | 0.347912E+09 |
October | 0.715730E+09 | 0.420237E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769886E+09 |
November | 0.708685E+09 | 0.459558E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840509E+09 |
December | 0.690839E+09 | 0.470502E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902109E+09 |
Annual Sum or Average | 0.858171E+10 | 0.493697E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18332924.21 | 0.908390E+10 |
Minimum of Months | 0.649041E+09 | 0.360232E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347912E+09 |
Maximum of Months | 0.773965E+09 | 0.472043E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11396675.94 | 0.104191E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.716992E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163510E+10 |
February | 0.136988E+10 | 0.598618E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156034E+10 |
March | 0.163688E+10 | 0.668717E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149675E+10 |
April | 0.145246E+10 | 0.575328E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1483942.81 | 0.142538E+10 |
May | 0.157341E+10 | 0.606369E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64006.47 | 0.112993E+10 |
June | 0.156904E+10 | 0.593123E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 795707.25 | 0.932086E+09 |
July | 0.145684E+10 | 0.560705E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7294792.09 | 0.788929E+09 |
August | 0.163688E+10 | 0.629874E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17628320.54 | 0.653317E+09 |
September | 0.145246E+10 | 0.590133E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66275.56 | 0.545695E+09 |
October | 0.150994E+10 | 0.646221E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122622E+10 |
November | 0.149520E+10 | 0.699782E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131684E+10 |
December | 0.145684E+10 | 0.712175E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142109E+10 |
Annual Sum or Average | 0.181198E+11 | 0.759804E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27333044.72 | 0.141317E+11 |
Minimum of Months | 0.136988E+10 | 0.560705E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545695E+09 |
Maximum of Months | 0.163688E+10 | 0.716992E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17628320.54 | 0.163510E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.471543E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107666E+10 |
February | 0.882782E+09 | 0.389658E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100118E+10 |
March | 0.105485E+10 | 0.432592E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992099E+09 |
April | 0.936002E+09 | 0.370176E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 760962.73 | 0.965811E+09 |
May | 0.101394E+10 | 0.389382E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42628.80 | 0.782234E+09 |
June | 0.101113E+10 | 0.380311E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 530389.20 | 0.646370E+09 |
July | 0.938820E+09 | 0.359744E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4837328.96 | 0.565742E+09 |
August | 0.105485E+10 | 0.403918E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11744815.62 | 0.461010E+09 |
September | 0.936002E+09 | 0.381420E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44742.17 | 0.370549E+09 |
October | 0.973041E+09 | 0.420456E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802244E+09 |
November | 0.963541E+09 | 0.457137E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871531E+09 |
December | 0.938820E+09 | 0.469880E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939423E+09 |
Annual Sum or Average | 0.116768E+11 | 0.492622E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17960867.48 | 0.947486E+10 |
Minimum of Months | 0.882782E+09 | 0.359744E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370549E+09 |
Maximum of Months | 0.105485E+10 | 0.471543E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11744815.62 | 0.107666E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.751931E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182355E+10 |
February | 0.136985E+10 | 0.616612E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162318E+10 |
March | 0.163685E+10 | 0.674538E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157853E+10 |
April | 0.145243E+10 | 0.574701E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3893021.44 | 0.154893E+10 |
May | 0.157338E+10 | 0.603821E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51955.48 | 0.128011E+10 |
June | 0.156900E+10 | 0.589922E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 861565.36 | 0.108432E+10 |
July | 0.145680E+10 | 0.555880E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12981357.08 | 0.914707E+09 |
August | 0.163685E+10 | 0.626114E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22840791.15 | 0.740649E+09 |
September | 0.145243E+10 | 0.592325E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57894.23 | 0.584166E+09 |
October | 0.150991E+10 | 0.659735E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124549E+10 |
November | 0.149516E+10 | 0.726279E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139510E+10 |
December | 0.145680E+10 | 0.754091E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152224E+10 |
Annual Sum or Average | 0.181194E+11 | 0.772595E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40686584.74 | 0.153410E+11 |
Minimum of Months | 0.136985E+10 | 0.555880E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584166E+09 |
Maximum of Months | 0.163685E+10 | 0.754091E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22840791.15 | 0.182355E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.471972E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121739E+10 |
February | 0.882782E+09 | 0.392971E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110175E+10 |
March | 0.105485E+10 | 0.432907E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108408E+10 |
April | 0.936002E+09 | 0.370566E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1738630.68 | 0.107849E+10 |
May | 0.101394E+10 | 0.390779E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34633.40 | 0.886605E+09 |
June | 0.101113E+10 | 0.382283E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 574352.73 | 0.756698E+09 |
July | 0.938820E+09 | 0.360228E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5729408.44 | 0.633921E+09 |
August | 0.105485E+10 | 0.405320E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14064624.23 | 0.519244E+09 |
September | 0.936002E+09 | 0.379496E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38591.12 | 0.407895E+09 |
October | 0.973041E+09 | 0.420291E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.860844E+09 |
November | 0.963541E+09 | 0.459485E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936116E+09 |
December | 0.938820E+09 | 0.470445E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101855E+10 |
Annual Sum or Average | 0.116768E+11 | 0.493674E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22180240.60 | 0.105016E+11 |
Minimum of Months | 0.882782E+09 | 0.360228E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407895E+09 |
Maximum of Months | 0.105485E+10 | 0.471972E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14064624.23 | 0.121739E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.716925E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188842E+10 |
February | 0.136988E+10 | 0.598591E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177212E+10 |
March | 0.163688E+10 | 0.668681E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170828E+10 |
April | 0.145246E+10 | 0.575293E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1711743.91 | 0.166011E+10 |
May | 0.157341E+10 | 0.606351E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51941.26 | 0.134388E+10 |
June | 0.156904E+10 | 0.593110E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 861504.61 | 0.112594E+10 |
July | 0.145684E+10 | 0.560693E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8391618.31 | 0.961877E+09 |
August | 0.163688E+10 | 0.629858E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21013364.63 | 0.792881E+09 |
September | 0.145246E+10 | 0.590110E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57310.98 | 0.645804E+09 |
October | 0.150994E+10 | 0.646186E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139418E+10 |
November | 0.149520E+10 | 0.699738E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147531E+10 |
December | 0.145684E+10 | 0.712103E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160611E+10 |
Annual Sum or Average | 0.181198E+11 | 0.759764E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32087483.70 | 0.163749E+11 |
Minimum of Months | 0.136988E+10 | 0.560693E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645804E+09 |
Maximum of Months | 0.163688E+10 | 0.716925E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21013364.63 | 0.188842E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.471430E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125505E+10 |
February | 0.882782E+09 | 0.389623E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115430E+10 |
March | 0.105485E+10 | 0.432546E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114331E+10 |
April | 0.936002E+09 | 0.370165E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 879809.40 | 0.113217E+10 |
May | 0.101394E+10 | 0.389369E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34561.00 | 0.935858E+09 |
June | 0.101113E+10 | 0.380304E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 574253.27 | 0.782951E+09 |
July | 0.938820E+09 | 0.359696E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5566334.51 | 0.690120E+09 |
August | 0.105485E+10 | 0.403910E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13998760.43 | 0.560752E+09 |
September | 0.936002E+09 | 0.381402E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38590.39 | 0.441445E+09 |
October | 0.973041E+09 | 0.420416E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917094E+09 |
November | 0.963541E+09 | 0.457071E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992626E+09 |
December | 0.938820E+09 | 0.469717E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107642E+10 |
Annual Sum or Average | 0.116768E+11 | 0.492565E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21092309.01 | 0.110821E+11 |
Minimum of Months | 0.882782E+09 | 0.359696E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441445E+09 |
Maximum of Months | 0.105485E+10 | 0.471430E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13998760.43 | 0.125505E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.274130E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.248656E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.295472E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.263917E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.284801E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.283424E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.265294E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.295472E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.263917E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.274130E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.270917E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.265294E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.328542E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.248656E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.295472E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173386E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154322E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146940E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1383836.50 | 0.137640E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6211.58 | 0.105187E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315798.37 | 0.866366E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7607678.78 | 0.725289E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13194379.77 | 0.598149E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3633.91 | 0.496875E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118179E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137075E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150568E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22511538.90 | 0.139197E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496875E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13194379.77 | 0.173386E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270261E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250942E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246811E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3623273.60 | 0.232245E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10243.19 | 0.183042E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583391.22 | 0.150427E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17037673.97 | 0.125415E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24824727.96 | 0.104218E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5510.40 | 0.864829E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198973E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222873E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239699E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46084820.33 | 0.231139E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864829E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24824727.96 | 0.270261E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275545E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253435E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252779E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2596338.59 | 0.248782E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204622E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157834.21 | 0.172388E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5290609.18 | 0.145694E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17405149.56 | 0.117977E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939637E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201943E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219894E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236364E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25449931.54 | 0.242339E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939637E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17405149.56 | 0.275545E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 10174.14 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 10174.14 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 10174.14 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 10174.14 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 10174.14 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 10174.14 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 10174.14 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 10174.14 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 10174.14 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 10174.14 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 10174.14 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 10174.14 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-16:30 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1293.27 | 28-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 1035.22 | 02-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1219.95 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 901.47 | 22-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1143.61 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 640.24 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.46 | 01-APR-17:10 | 1175.75 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 588.59 | 17-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 | 05-MAY-16:00 | 849.11 | 18-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 | 28-JUN-16:00 | 1144.15 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 633.09 | 12-JUL-08:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.97 | 23-JUL-16:00 | 590.87 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 626.70 | 02-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.25 | 08-AUG-17:00 | 768.95 | 11-AUG-04:00 |
September | 2010.79 | 01-SEP-09:09 | 909.01 | 25-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 14-SEP-17:00 | 559.23 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 1131.95 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1032.89 | 31-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1246.28 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1033.36 | 17-DEC-20:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 559.23 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 110.97 | 1293.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 843.96 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 674.87 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 794.34 | 19-FEB-10:00 |
March | 1295.83 | 01-MAR-10:09 | 553.82 | 22-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 752.16 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 393.53 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.38 | 01-APR-17:10 | 771.35 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 05-MAY-16:00 | 556.38 | 18-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 | 28-JUN-16:00 | 745.96 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 376.13 | 12-JUL-08:30 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.95 | 23-JUL-15:54 | 379.12 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 391.90 | 02-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 | 08-AUG-17:00 | 498.40 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 560.58 | 25-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.63 | 14-SEP-17:00 | 365.84 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 726.95 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 670.08 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 802.86 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 660.96 | 17-DEC-20:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.84 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 66.38 | 843.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-16:30 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1243.01 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 1008.57 | 02-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1262.54 | 19-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 890.37 | 22-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1151.80 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 638.00 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.03 | 01-APR-17:10 | 1173.31 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 589.78 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 | 05-MAY-16:00 | 828.94 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 545.88 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 | 28-JUN-16:00 | 1116.72 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 627.30 | 12-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.81 | 23-JUL-15:53 | 581.19 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 625.30 | 02-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.25 | 08-AUG-17:00 | 787.37 | 11-AUG-04:00 |
September | 2010.83 | 01-SEP-09:09 | 900.68 | 25-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 14-SEP-17:00 | 546.77 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 1129.06 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 993.75 | 31-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1196.29 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 949.84 | 02-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.77 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 91.81 | 1262.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:30 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 912.78 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 648.78 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 876.59 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 591.18 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 850.15 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 495.88 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.63 | 01-APR-16:00 | 881.15 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 391.14 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 05-MAY-16:00 | 593.57 | 18-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 383.96 | 29-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 | 28-JUN-16:00 | 832.81 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 512.06 | 12-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.06 | 23-JUL-13:54 | 459.67 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 503.19 | 28-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 | 08-AUG-17:00 | 625.57 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 594.85 | 25-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.63 | 14-SEP-17:00 | 399.64 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 729.70 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 745.49 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 917.17 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 773.62 | 17-DEC-20:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 383.96 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.64 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 | 917.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-16:30 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2552.93 | 12-JAN-24:00 |
February | 2010.79 | 01-FEB-10:09 | 1033.91 | 02-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2343.37 | 16-FEB-22:03 |
March | 2010.79 | 01-MAR-10:09 | 898.77 | 22-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2269.48 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 636.54 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 372.75 | 01-APR-17:02 | 2400.63 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 581.92 | 17-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 | 05-MAY-16:00 | 1780.93 | 17-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.60 | 28-JUN-16:00 | 2327.35 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 628.90 | 12-JUL-08:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.29 | 23-JUL-14:10 | 1206.32 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 622.19 | 02-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.59 | 13-AUG-15:00 | 1667.74 | 11-AUG-04:00 |
September | 2010.79 | 01-SEP-09:09 | 906.37 | 25-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 | 14-SEP-17:00 | 1177.51 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 1131.77 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2163.57 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2437.92 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1969.89 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1177.51 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 372.75 | 2552.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 739.33 | 02-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1690.71 | 12-JAN-24:00 |
February | 1239.33 | 01-FEB-08:09 | 673.22 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1597.00 | 19-FEB-10:00 |
March | 1239.33 | 01-MAR-08:09 | 549.66 | 22-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1563.16 | 28-MAR-24:00 |
April | 1239.33 | 03-APR-07:10 | 390.78 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.13 | 01-APR-17:02 | 1650.32 | 07-APR-24:00 |
May | 1239.33 | 01-MAY-07:10 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.36 | 05-MAY-16:00 | 1193.62 | 22-MAY-24:00 |
June | 1239.33 | 01-JUN-07:10 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.07 | 28-JUN-16:00 | 1556.24 | 13-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.20 | 23-JUL-16:03 | 809.64 | 02-JUL-10:10 |
August | 1239.33 | 01-AUG-07:10 | 388.77 | 02-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.16 | 08-AUG-17:00 | 1134.35 | 11-AUG-04:00 |
September | 1239.33 | 01-SEP-07:10 | 556.56 | 25-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 | 14-SEP-17:00 | 785.71 | 18-SEP-23:00 |
October | 1239.33 | 02-OCT-07:10 | 726.68 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1440.86 | 31-OCT-21:03 |
November | 1239.33 | 01-NOV-07:10 | 739.33 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1615.04 | 29-NOV-23:00 |
December | 1239.33 | 01-DEC-08:09 | 739.33 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1307.49 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 785.71 | |||||
Maximum of Months | 1239.33 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 171.13 | 1690.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-16:30 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2572.63 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 1006.98 | 02-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2799.73 | 19-FEB-12:10 |
March | 2010.83 | 01-MAR-10:09 | 887.62 | 22-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2436.58 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 634.19 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.96 | 01-APR-17:10 | 2486.34 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 583.17 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 | 05-MAY-16:00 | 1802.80 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 545.88 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.60 | 28-JUN-16:00 | 2324.54 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 622.85 | 12-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.49 | 23-JUL-16:03 | 1231.53 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 620.71 | 02-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.74 | 08-AUG-17:00 | 1732.22 | 11-AUG-04:00 |
September | 2010.83 | 01-SEP-09:09 | 897.98 | 25-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 | 14-SEP-17:00 | 1191.83 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 1128.87 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2165.28 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2445.73 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2003.77 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1191.83 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 170.49 | 2799.73 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:30 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1731.49 | 12-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 646.44 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1590.84 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 587.33 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1598.50 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 489.46 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.33 | 01-APR-16:00 | 1696.21 | 10-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 387.61 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.36 | 05-MAY-16:00 | 1226.66 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 380.02 | 29-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.06 | 28-JUN-16:00 | 1572.01 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 505.62 | 12-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.84 | 23-JUL-14:03 | 862.99 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 496.59 | 28-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.17 | 08-AUG-17:00 | 1217.00 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 591.09 | 25-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 | 14-SEP-17:00 | 804.81 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 729.45 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1446.95 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1654.86 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1345.68 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 380.02 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 804.81 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 103.17 | 1731.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-16:30 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3103.02 | 12-JAN-22:03 |
February | 2010.79 | 01-FEB-10:09 | 1033.70 | 02-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2902.45 | 16-FEB-22:03 |
March | 2010.79 | 01-MAR-10:09 | 898.27 | 22-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2822.14 | 29-MAR-05:00 |
April | 2010.79 | 03-APR-09:09 | 636.39 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 469.96 | 01-APR-17:02 | 2905.41 | 10-APR-21:03 |
May | 2010.79 | 01-MAY-09:09 | 581.66 | 17-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 05-MAY-16:00 | 2132.82 | 18-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.13 | 28-JUN-16:00 | 2660.01 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 628.74 | 12-JUL-08:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.06 | 23-JUL-13:52 | 1380.92 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 622.01 | 02-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.45 | 08-AUG-17:00 | 1993.14 | 11-AUG-04:00 |
September | 2010.79 | 01-SEP-09:09 | 905.88 | 25-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 | 14-SEP-17:00 | 1326.49 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 1131.74 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2670.51 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2901.21 | 29-NOV-22:03 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2399.13 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1326.49 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 469.96 | 3103.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2066.75 | 12-JAN-22:03 |
February | 1295.83 | 01-FEB-10:09 | 673.09 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1933.69 | 16-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 549.31 | 22-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1900.44 | 29-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 390.65 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.96 | 01-APR-17:02 | 1936.10 | 10-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 | 05-MAY-16:00 | 1421.84 | 18-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.42 | 28-JUN-16:00 | 1777.09 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.63 | 23-JUL-15:35 | 992.55 | 02-JUL-10:00 |
August | 1295.83 | 01-AUG-09:09 | 388.63 | 02-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.63 | 08-AUG-17:00 | 1355.62 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 556.22 | 25-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 | 14-SEP-17:00 | 885.63 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 726.65 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1778.06 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1932.29 | 29-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1598.21 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 885.63 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 208.96 | 2066.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-16:30 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3105.12 | 12-JAN-22:03 |
February | 2010.83 | 01-FEB-10:09 | 1006.73 | 02-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3044.03 | 19-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 887.10 | 22-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2844.81 | 29-MAR-04:57 |
April | 2010.83 | 03-APR-09:09 | 634.03 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.70 | 01-APR-17:10 | 2919.52 | 10-APR-21:03 |
May | 2010.83 | 01-MAY-09:09 | 582.91 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 05-MAY-16:00 | 2142.66 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 545.88 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.12 | 28-JUN-16:00 | 2655.48 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 622.68 | 12-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.12 | 23-JUL-15:35 | 1413.32 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 620.53 | 02-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.45 | 08-AUG-17:00 | 2073.46 | 11-AUG-04:00 |
September | 2010.83 | 01-SEP-09:09 | 897.48 | 25-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 | 14-SEP-17:00 | 1349.89 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 1128.84 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2671.11 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2901.60 | 29-NOV-22:03 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2402.89 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1349.89 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 188.45 | 3105.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:30 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2073.83 | 12-JAN-22:03 |
February | 1295.83 | 01-FEB-10:09 | 646.26 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1939.01 | 16-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 587.02 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1895.38 | 29-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 488.96 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.27 | 01-APR-16:00 | 2011.84 | 10-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 387.47 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 | 05-MAY-16:00 | 1493.78 | 27-MAY-17:40 |
June | 1295.83 | 01-JUN-09:09 | 379.87 | 29-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.41 | 28-JUN-16:00 | 1806.54 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 505.20 | 12-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.76 | 23-JUL-16:00 | 1018.78 | 22-JUL-22:55 |
August | 1295.83 | 01-AUG-09:09 | 496.26 | 28-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.63 | 08-AUG-17:00 | 1459.05 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 590.79 | 25-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 | 14-SEP-17:00 | 925.69 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 729.44 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1786.29 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1939.19 | 29-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1604.72 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 379.87 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 925.69 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 125.63 | 2073.83 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 2868.67 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 2868.67 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 2868.67 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 2868.67 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 2868.67 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 2868.67 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 2868.67 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 2868.67 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 2868.67 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 2868.67 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 2868.67 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 2868.67 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2824.70 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2639.30 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2464.43 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.03 | 01-APR-17:02 | 2502.79 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 | 05-MAY-16:00 | 1850.99 | 18-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.23 | 28-JUN-15:00 | 2464.27 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.21 | 23-JUL-16:00 | 1248.17 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.78 | 13-AUG-15:00 | 1624.69 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 | 14-SEP-17:00 | 1170.23 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2233.39 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2691.19 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2217.25 | 17-DEC-20:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1170.23 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.21 | 2824.70 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4625.43 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4308.33 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4141.02 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.51 | 01-APR-17:02 | 4278.32 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.48 | 05-MAY-16:00 | 3240.15 | 18-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.13 | 28-JUN-15:00 | 4230.32 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.10 | 23-JUL-15:51 | 2145.46 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.08 | 13-AUG-15:00 | 2881.94 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 | 14-SEP-17:00 | 2016.26 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3747.51 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4355.49 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3497.86 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2016.26 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.10 | 4625.43 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4694.64 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4241.86 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4164.25 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.03 | 01-APR-17:02 | 4556.02 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 3292.02 | 22-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.69 | 28-JUN-17:00 | 4276.16 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.70 | 24-JUL-14:05 | 2193.28 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.51 | 08-AUG-17:00 | 3155.66 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2080.48 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3970.38 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4482.99 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3682.16 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2080.48 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.03 | 4694.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 99865.00 | 02-JAN-05:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 96303.84 | 27-FEB-05:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96834.85 | 13-MAR-04:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97446.96 | 03-APR-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97330.08 | 08-MAY-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 99943.06 | 05-JUN-04:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 98341.35 | 05-JUL-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 95877.59 | 07-AUG-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 100873.07 | 11-SEP-04:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 97888.69 | 16-OCT-04:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 97846.73 | 20-NOV-05:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 98217.40 | 26-DEC-04:01 | 0.00 | 3956.50 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 95877.59 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 100873.07 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 78473.24 | 02-JAN-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 79323.05 | 27-FEB-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 81047.58 | 27-MAR-04:11 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82299.67 | 17-APR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82860.35 | 01-MAY-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 88547.76 | 12-JUN-04:12 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84581.08 | 17-JUL-04:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82372.59 | 29-AUG-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85882.18 | 05-SEP-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86008.88 | 10-OCT-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84404.74 | 06-NOV-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 81452.58 | 04-DEC-05:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 78473.24 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88547.76 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17327.80 | 12-JAN-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29539.50 | 28-FEB-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 65478.56 | 03-MAR-06:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70367.27 | 28-APR-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72050.18 | 09-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73444.02 | 12-JUN-04:11 | 0.00 | 4298.88 | 47500.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 73593.71 | 17-JUL-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 73622.42 | 28-AUG-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 71853.63 | 08-SEP-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71800.06 | 10-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 64836.87 | 07-NOV-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21676.89 | 06-DEC-16:20 | 30632.53 | 18274.19 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17327.80 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73622.42 | 30632.53 | 18274.19 | 47500.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 15126.17 | 11-JAN-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21555.77 | 28-FEB-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24478.63 | 15-MAR-16:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63316.64 | 28-APR-05:03 | 4836.72 | 1612.08 | 22942.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 65662.75 | 05-MAY-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 70547.25 | 12-JUN-04:11 | 0.00 | 4298.88 | 47500.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 68773.36 | 10-JUL-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 69509.22 | 28-AUG-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 65069.01 | 14-SEP-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32378.53 | 04-OCT-15:50 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17992.08 | 03-NOV-16:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15121.85 | 06-DEC-16:25 | 30632.53 | 18274.19 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15121.85 | 0.00 | 1612.08 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 70547.25 | 30632.53 | 18274.19 | 47500.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2273.52 | 11-JAN-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.90 |
February | 4354.36 | 27-FEB-15:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.95 |
March | 4783.43 | 10-MAR-14:20 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.24 |
April | 7161.72 | 27-APR-15:20 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 22.77 | 0.00 |
May | 7229.42 | 15-MAY-13:50 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 |
June | 10995.53 | 12-JUN-04:11 | 0.00 | 539.77 | 5964.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.05 |
July | 10933.48 | 24-JUL-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 |
August | 10299.69 | 14-AUG-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.68 |
September | 7907.98 | 11-SEP-15:35 | 7692.44 | 2183.45 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 |
October | 5037.16 | 10-OCT-12:10 | 3846.22 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.73 |
November | 4282.60 | 06-NOV-11:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.04 |
December | 2550.46 | 04-DEC-05:12 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2273.52 | 0.00 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10995.53 | 7692.44 | 2183.45 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 22.77 | 279.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2598.83 | 05-JAN-09:25 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.19 |
February | 4667.30 | 08-FEB-09:45 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.21 |
March | 9110.69 | 14-MAR-08:55 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.60 |
April | 12244.39 | 27-APR-08:30 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 |
May | 19047.32 | 14-MAY-08:42 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.83 |
June | 20832.42 | 25-JUN-08:32 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.80 |
July | 24438.94 | 30-JUL-08:31 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.39 |
August | 24191.92 | 13-AUG-08:51 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.48 |
September | 23534.31 | 10-SEP-08:31 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.57 |
October | 10019.88 | 04-OCT-08:50 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.85 |
November | 4128.74 | 15-NOV-09:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.18 |
December | 3538.67 | 05-DEC-09:55 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2598.83 | 326.14 | 97.71 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 | |
Maximum of Months | 24438.94 | 2478.65 | 703.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16025.89 | 20-JAN-13:05 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 |
February | 20179.74 | 12-FEB-13:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 900.03 |
March | 19703.06 | 01-MAR-13:25 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.11 |
April | 28183.54 | 02-APR-11:32 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.35 |
May | 29049.15 | 07-MAY-15:41 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.13 |
June | 27262.22 | 11-JUN-12:53 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.21 |
July | 32392.57 | 30-JUL-13:11 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.85 |
August | 32478.48 | 13-AUG-12:11 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.26 |
September | 33847.39 | 10-SEP-13:11 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.85 |
October | 30456.90 | 29-OCT-12:22 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.39 |
November | 20195.58 | 11-NOV-12:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.94 |
December | 27188.98 | 03-DEC-13:32 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16025.89 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 | |
Maximum of Months | 33847.39 | 3846.30 | 1091.75 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 900.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5384.57 | 05-JAN-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.39 |
February | 11562.93 | 26-FEB-15:23 | 195.68 | 58.63 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.43 |
March | 16766.97 | 09-MAR-06:02 | 782.73 | 260.89 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 |
April | 26107.99 | 02-APR-15:32 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.51 |
May | 30378.30 | 07-MAY-16:21 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.63 |
June | 27002.84 | 18-JUN-16:52 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.65 |
July | 32064.62 | 30-JUL-16:31 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.47 |
August | 32027.98 | 06-AUG-16:51 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.56 |
September | 29983.02 | 10-SEP-16:31 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.52 |
October | 17514.09 | 01-OCT-15:53 | 260.91 | 78.17 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.47 |
November | 12321.51 | 07-NOV-06:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.30 |
December | 14043.78 | 04-DEC-05:11 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5384.57 | 0.00 | 58.63 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32064.62 | 1239.33 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1586.08 | 11-JAN-16:10 | 1923.11 | 999.23 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.90 |
February | 1998.88 | 28-FEB-15:10 | 3846.22 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 |
March | 2375.10 | 10-MAR-14:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.35 |
April | 5795.82 | 27-APR-15:20 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 51.58 | 0.00 |
May | 6421.01 | 05-MAY-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 |
June | 6975.47 | 21-JUN-15:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 0.00 |
July | 8188.44 | 24-JUL-15:00 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 81.06 | 0.00 |
August | 7728.81 | 25-AUG-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 34.71 | 0.00 |
September | 6147.01 | 11-SEP-15:30 | 3846.22 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.82 |
October | 3350.58 | 06-OCT-14:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.47 |
November | 1948.23 | 07-NOV-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.30 |
December | 1494.08 | 29-DEC-15:10 | 1923.11 | 826.23 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1494.08 | 1012.16 | 337.35 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8188.44 | 3846.22 | 1091.73 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 81.06 | 243.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1182.15 | 20-JAN-11:10 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.84 |
February | 3916.75 | 08-FEB-11:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.95 |
March | 9053.65 | 14-MAR-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.63 |
April | 13048.07 | 27-APR-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.44 |
May | 20507.73 | 14-MAY-09:22 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.40 |
June | 24700.55 | 25-JUN-08:21 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.55 |
July | 25886.91 | 23-JUL-08:41 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.65 |
August | 25968.52 | 13-AUG-08:51 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.54 |
September | 21163.75 | 10-SEP-08:42 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.59 |
October | 10045.98 | 04-OCT-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.79 |
November | 4473.56 | 04-NOV-10:05 | 782.73 | 234.52 | 1547.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.75 |
December | 1312.62 | 05-DEC-11:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1182.15 | 326.14 | 97.71 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.44 | |
Maximum of Months | 25968.52 | 2478.65 | 703.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15926.34 | 20-JAN-13:15 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.53 |
February | 21522.12 | 12-FEB-14:02 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2031.27 |
March | 21178.69 | 01-MAR-13:25 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.71 |
April | 22785.65 | 02-APR-14:12 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.64 |
May | 27973.72 | 07-MAY-13:13 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.23 |
June | 26992.10 | 11-JUN-13:02 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.27 |
July | 31436.30 | 30-JUL-13:22 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.84 |
August | 34285.54 | 13-AUG-12:11 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.25 |
September | 32985.58 | 10-SEP-12:42 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.13 |
October | 31490.65 | 08-OCT-13:22 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.47 |
November | 31666.49 | 11-NOV-13:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 797.31 |
December | 16273.19 | 05-DEC-12:30 | 1058.33 | 545.88 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15926.34 | 404.87 | 121.30 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.53 | |
Maximum of Months | 34285.54 | 3846.30 | 1091.75 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2031.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1823.68 | 05-JAN-15:40 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.45 |
February | 7912.82 | 27-FEB-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.99 |
March | 10719.11 | 14-MAR-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 |
April | 17655.45 | 02-APR-15:32 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.63 |
May | 25651.52 | 29-MAY-18:11 | 0.00 | 136.80 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.17 |
June | 25214.02 | 18-JUN-17:21 | 0.00 | 175.88 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.37 |
July | 29003.65 | 23-JUL-17:21 | 0.00 | 195.42 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.20 |
August | 25644.09 | 06-AUG-17:01 | 0.00 | 136.80 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.23 |
September | 24598.94 | 10-SEP-16:42 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.01 |
October | 11949.75 | 04-OCT-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.13 |
November | 6065.27 | 04-NOV-15:30 | 130.46 | 58.63 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 |
December | 2951.30 | 05-DEC-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1823.68 | 0.00 | 58.63 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 | |
Maximum of Months | 29003.65 | 1239.33 | 351.77 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1473.79 | 11-JAN-16:10 | 1923.11 | 998.94 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.56 |
February | 1912.83 | 28-FEB-15:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2038.19 | 10-MAR-14:50 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.87 |
April | 6423.98 | 27-APR-15:20 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 61.78 | 0.00 |
May | 6868.74 | 15-MAY-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 |
June | 7621.88 | 21-JUN-15:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 | 0.00 |
July | 9180.62 | 24-JUL-15:00 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 98.95 | 0.00 |
August | 8341.48 | 09-AUG-14:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 99.89 | 0.00 |
September | 6062.83 | 11-SEP-15:30 | 3846.22 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 |
October | 3151.51 | 04-OCT-15:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.18 |
November | 1762.69 | 02-NOV-14:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.75 |
December | 1387.21 | 29-DEC-15:10 | 1923.11 | 825.60 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1387.21 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9180.62 | 3846.22 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.89 | 248.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1005.97 | 20-JAN-10:50 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.51 |
February | 1310.22 | 27-FEB-15:50 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.63 |
March | 5703.01 | 14-MAR-09:50 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.97 |
April | 12012.07 | 27-APR-09:10 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.50 |
May | 23383.80 | 14-MAY-09:12 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.70 |
June | 23379.90 | 25-JUN-10:12 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.61 |
July | 23547.52 | 30-JUL-08:21 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.51 |
August | 24591.57 | 06-AUG-09:21 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.26 |
September | 23721.84 | 10-SEP-08:31 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.77 |
October | 7985.91 | 04-OCT-09:20 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.99 |
November | 1316.39 | 04-NOV-10:40 | 391.37 | 117.26 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 |
December | 1056.76 | 05-DEC-10:40 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1005.97 | 391.37 | 117.25 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 | |
Maximum of Months | 24591.57 | 2591.66 | 703.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14497.42 | 20-JAN-13:30 | 1923.15 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.20 |
February | 17794.45 | 27-FEB-14:20 | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.51 |
March | 20093.01 | 14-MAR-13:30 | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.83 |
April | 27654.17 | 02-APR-12:32 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 879.97 |
May | 33339.24 | 14-MAY-13:12 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 859.78 |
June | 27862.12 | 11-JUN-12:43 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.43 |
July | 36432.23 | 30-JUL-13:01 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.72 |
August | 35209.95 | 06-AUG-13:22 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.21 |
September | 38438.10 | 10-SEP-13:11 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.41 |
October | 30213.75 | 08-OCT-13:22 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.03 |
November | 17602.01 | 04-NOV-13:30 | 211.67 | 90.98 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13769.86 | 05-DEC-12:30 | 1058.33 | 545.88 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13769.86 | 211.67 | 90.98 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38438.10 | 2010.83 | 545.88 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 879.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1562.50 | 05-JAN-15:40 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.43 |
February | 7416.84 | 27-FEB-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.70 |
March | 10543.71 | 14-MAR-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
April | 17847.16 | 02-APR-15:13 | 260.91 | 78.17 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.18 |
May | 29564.50 | 07-MAY-16:51 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.59 |
June | 27309.36 | 25-JUN-16:51 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.35 |
July | 30509.99 | 30-JUL-17:01 | 0.00 | 195.42 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.67 |
August | 29850.73 | 06-AUG-17:21 | 0.00 | 195.42 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.72 |
September | 28952.39 | 10-SEP-16:31 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.51 |
October | 11902.28 | 04-OCT-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.49 |
November | 5572.36 | 04-NOV-15:30 | 130.46 | 58.63 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 |
December | 2177.30 | 05-DEC-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1562.50 | 0.00 | 58.63 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | |
Maximum of Months | 30509.99 | 1239.33 | 351.77 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3519.56 | 17-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.58 |
February | 3295.72 | 28-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.20 |
March | 3999.16 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.48 |
April | 6114.55 | 03-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.07 |
May | 6267.08 | 08-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.34 |
June | 7219.08 | 05-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.51 |
July | 9502.36 | 31-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.08 |
August | 10047.84 | 14-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.85 |
September | 9154.38 | 11-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.40 |
October | 7557.40 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.57 |
November | 5854.67 | 06-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.80 |
December | 3147.35 | 04-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3147.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10047.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7413.87 | 14-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2739.58 |
February | 7055.39 | 13-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2535.72 |
March | 5748.36 | 06-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1957.44 |
April | 3529.07 | 27-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.90 | 0.00 |
May | 3652.09 | 15-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.30 |
June | 4478.70 | 28-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.96 | 0.00 |
July | 5516.13 | 31-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.25 | 0.00 |
August | 6025.14 | 10-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.85 | 0.00 |
September | 6290.96 | 11-SEP-15:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.18 |
October | 2892.59 | 05-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.16 |
November | 6515.98 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1388.26 |
December | 7024.86 | 09-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1563.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2892.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7413.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.85 | 2739.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2078.58 |
February | 2143.08 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.33 |
March | 4625.20 | 14-MAR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.10 |
April | 14470.53 | 27-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.09 | 0.00 |
May | 15213.31 | 15-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.26 |
June | 15279.87 | 28-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.92 |
July | 16814.66 | 24-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.54 | 0.00 |
August | 17637.62 | 10-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.59 | 0.00 |
September | 14031.10 | 11-SEP-14:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.22 |
October | 8079.71 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.84 |
November | 2924.56 | 04-NOV-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.07 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17637.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.54 | 2078.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1841.45 | 05-JAN-16:10 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3933.74 | 07-FEB-16:50 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6965.26 | 31-MAR-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8091.82 | 26-APR-18:00 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3409.16 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5295.33 | 30-JUN-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7240.55 | 31-JUL-24:00 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8601.39 | 06-AUG-19:06 | 0.00 | 40.65 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3293.73 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4987.21 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5801.03 | 11-NOV-16:05 | 23.38 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7644.96 | 05-DEC-15:50 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1841.45 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8601.39 | 222.14 | 146.32 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1325.82 | 20-JAN-16:20 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3575.15 | 08-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6120.46 | 31-MAR-23:40 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7713.67 | 26-APR-18:00 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3164.02 | 31-MAY-23:50 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4954.98 | 30-JUN-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6958.79 | 31-JUL-24:00 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8132.04 | 06-AUG-18:32 | 0.00 | 65.03 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2913.02 | 30-SEP-23:50 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4075.00 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5242.85 | 04-NOV-16:02 | 70.15 | 48.78 | 35074.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7021.57 | 05-DEC-16:00 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1325.82 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8132.04 | 222.14 | 146.32 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1228.68 | 05-JAN-16:20 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3426.61 | 08-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5598.64 | 31-MAR-23:20 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7786.27 | 26-APR-18:00 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3079.32 | 31-MAY-23:30 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4859.14 | 30-JUN-23:40 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6918.04 | 31-JUL-23:50 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8303.82 | 06-AUG-18:32 | 0.00 | 65.03 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2543.36 | 10-SEP-17:40 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4073.59 | 04-OCT-16:50 | 70.15 | 81.29 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5148.64 | 04-NOV-16:02 | 70.15 | 48.78 | 35074.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6823.05 | 05-DEC-16:10 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1228.68 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8303.82 | 222.14 | 146.32 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 90197.08 | 12-JAN-17:00 | 4808.68 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182493.28 | 27-FEB-17:00 | 4808.68 | 2868.67 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357930.47 | 31-MAR-24:00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367597.33 | 01-APR-18:12 | 0.00 | 637.46 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175694.43 | 31-MAY-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267209.41 | 30-JUN-24:00 | 0.00 | 159.37 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359887.23 | 31-JUL-24:00 | 0.00 | 318.73 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 371714.43 | 13-AUG-18:42 | 0.00 | 956.20 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175399.34 | 30-SEP-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 266740.21 | 31-OCT-24:00 | 0.00 | 159.37 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 274970.72 | 06-NOV-15:00 | 5027.92 | 2868.67 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366249.10 | 04-DEC-17:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 90197.08 | 0.00 | 159.37 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 371714.43 | 5027.92 | 2868.67 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.130852E+13 | 804164.71 | 10-JAN-16:00 | 0.411952E+12 | 1272096.88 | 02-JAN-05:19 |
February | 0.153671E+13 | 1036987.62 | 27-FEB-14:00 | 0.248362E+12 | 675750.84 | 21-FEB-06:10 |
March | 0.211104E+13 | 1212213.16 | 14-MAR-15:50 | 0.148292E+12 | 465846.72 | 01-MAR-07:10 |
April | 0.237078E+13 | 1577434.23 | 27-APR-15:09 | 0.959964E+11 | 300436.32 | 19-APR-06:10 |
May | 0.134167E+13 | 1145724.19 | 15-MAY-15:20 | 0.740333E+11 | 336270.72 | 17-MAY-13:20 |
June | 0.168751E+13 | 1262663.70 | 28-JUN-15:20 | 0.638251E+11 | 303099.82 | 13-JUN-09:39 |
July | 0.217372E+13 | 1508760.17 | 31-JUL-15:20 | 0.608171E+11 | 93753.16 | 12-JUL-09:20 |
August | 0.269545E+13 | 1693406.60 | 29-AUG-15:09 | 0.642252E+11 | 106557.50 | 03-AUG-09:09 |
September | 0.129644E+13 | 1137119.00 | 11-SEP-15:39 | 0.612578E+11 | 313403.52 | 27-SEP-09:20 |
October | 0.164218E+13 | 1218748.47 | 04-OCT-15:09 | 0.829803E+11 | 334290.68 | 28-OCT-05:10 |
November | 0.195967E+13 | 1110075.96 | 13-NOV-16:00 | 0.191001E+12 | 515751.92 | 24-NOV-07:10 |
December | 0.243175E+13 | 1252179.74 | 05-DEC-16:19 | 0.316412E+12 | 835154.19 | 26-DEC-07:10 |
Annual Sum or Average | 0.225555E+14 | 0.181915E+13 | ||||
Minimum of Months | 0.129644E+13 | 804164.71 | 0.608171E+11 | 93753.16 | ||
Maximum of Months | 0.269545E+13 | 1693406.60 | 0.411952E+12 | 1272096.88 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.100412E+11 | 32948.72 | 30-JAN-11:30 | 0.00 | 0.00 |
February | 0.163293E+11 | 46825.78 | 27-FEB-12:30 | 0.00 | 0.00 |
March | 0.285795E+11 | 65947.85 | 24-MAR-12:30 | 0.00 | 0.00 |
April | 0.422474E+11 | 77387.84 | 25-APR-12:09 | 0.00 | 0.00 |
May | 0.545964E+11 | 89495.83 | 10-MAY-11:30 | 0.00 | 0.00 |
June | 0.566222E+11 | 83205.55 | 19-JUN-12:09 | 0.00 | 0.00 |
July | 0.602226E+11 | 83892.18 | 05-JUL-10:30 | 0.00 | 0.00 |
August | 0.488431E+11 | 75784.38 | 06-AUG-12:30 | 0.00 | 0.00 |
September | 0.347558E+11 | 66245.38 | 07-SEP-12:30 | 0.00 | 0.00 |
October | 0.224135E+11 | 56431.17 | 03-OCT-11:00 | 0.00 | 0.00 |
November | 0.110885E+11 | 34351.60 | 11-NOV-12:20 | 0.00 | 0.00 |
December | 0.859360E+10 | 27417.37 | 01-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.394333E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.859360E+10 | 27417.37 | 0.00 | 0.00 | |
Maximum of Months | 0.602226E+11 | 89495.83 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.147402E+12 | 0.334639E+11 | 0.766053E+12 | 0.102195E+12 | 0.152281E+12 | 0.103265E+11 | 0.00 | 0.678988E+10 | 0.104082E+10 | 0.889693E+11 | 0.00 | 0.00 | 0.00 |
February | 0.131419E+12 | 0.260478E+11 | 0.978954E+12 | 0.923113E+11 | 0.139679E+12 | 0.118572E+11 | 0.00 | 0.219844E+11 | 0.457512E+10 | 0.129883E+12 | 0.00 | 0.00 | 0.00 |
March | 0.154168E+12 | 0.232354E+11 | 0.141687E+13 | 0.102362E+12 | 0.163513E+12 | 0.164735E+11 | 0.00 | 0.451492E+11 | 0.100495E+11 | 0.179216E+12 | 0.00 | 0.00 | 0.00 |
April | 0.136728E+12 | 0.173499E+11 | 0.165903E+13 | 0.988819E+11 | 0.168579E+12 | 0.164835E+11 | 0.00 | 0.885875E+11 | 0.290258E+11 | 0.156121E+12 | 0.00 | 0.00 | 0.00 |
May | 0.146937E+12 | 0.145010E+11 | 0.774844E+12 | 0.102278E+12 | 0.185234E+12 | 0.206663E+11 | 0.00 | 0.410784E+11 | 0.214419E+11 | 0.346936E+11 | 0.00 | 0.00 | 0.00 |
June | 0.145803E+12 | 0.125435E+11 | 0.106252E+13 | 0.990390E+11 | 0.192557E+12 | 0.269581E+11 | 0.00 | 0.824782E+11 | 0.438757E+11 | 0.217424E+11 | 0.00 | 0.00 | 0.00 |
July | 0.136674E+12 | 0.134591E+11 | 0.139340E+13 | 0.102120E+12 | 0.210126E+12 | 0.354992E+11 | 0.00 | 0.182876E+12 | 0.782018E+11 | 0.213627E+11 | 0.00 | 0.00 | 0.00 |
August | 0.152443E+12 | 0.160903E+11 | 0.173200E+13 | 0.102362E+12 | 0.223504E+12 | 0.415874E+11 | 0.00 | 0.314509E+12 | 0.111880E+12 | 0.107765E+10 | 0.00 | 0.00 | 0.00 |
September | 0.137360E+12 | 0.200997E+11 | 0.740713E+12 | 0.988812E+11 | 0.186378E+12 | 0.247179E+11 | 0.00 | 0.555380E+11 | 0.311678E+11 | 0.158145E+10 | 0.00 | 0.00 | 0.00 |
October | 0.144209E+12 | 0.264690E+11 | 0.108340E+13 | 0.102195E+12 | 0.166740E+12 | 0.157034E+11 | 0.00 | 0.366523E+11 | 0.126140E+11 | 0.541990E+11 | 0.00 | 0.00 | 0.00 |
November | 0.145171E+12 | 0.308302E+11 | 0.135889E+13 | 0.989467E+11 | 0.149017E+12 | 0.140149E+11 | 0.00 | 0.363180E+11 | 0.870477E+10 | 0.117770E+12 | 0.00 | 0.00 | 0.00 |
December | 0.143522E+12 | 0.348256E+11 | 0.170972E+13 | 0.102122E+12 | 0.152332E+12 | 0.151883E+11 | 0.00 | 0.465268E+11 | 0.747877E+10 | 0.220039E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172184E+13 | 0.268915E+12 | 0.146764E+14 | 0.120369E+13 | 0.208994E+13 | 0.249476E+12 | 0.00 | 0.958488E+12 | 0.360056E+12 | 0.102666E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131419E+12 | 0.125435E+11 | 0.740713E+12 | 0.923113E+11 | 0.139679E+12 | 0.103265E+11 | 0.00 | 0.678988E+10 | 0.104082E+10 | 0.107765E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154168E+12 | 0.348256E+11 | 0.173200E+13 | 0.102362E+12 | 0.223504E+12 | 0.415874E+11 | 0.00 | 0.314509E+12 | 0.111880E+12 | 0.220039E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.344156E+12 | 0.00 | 0.677960E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.186565E+12 | 0.00 | 0.617969E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.774750E+11 | 0.00 | 0.708174E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.317680E+11 | 0.00 | 0.642284E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.790149E+10 | 0.00 | 0.661318E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.449239E+09 | 0.00 | 0.633758E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 51457949.79 | 0.00 | 0.607656E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 40509023.01 | 0.00 | 0.641847E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.123360E+10 | 0.00 | 0.600242E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.197228E+11 | 0.00 | 0.632575E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.127526E+12 | 0.00 | 0.634747E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.250882E+12 | 0.00 | 0.655304E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104777E+13 | 0.00 | 0.771384E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 40509023.01 | 0.00 | 0.600242E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.344156E+12 | 0.00 | 0.708174E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 169722.15 | 02-JAN-16:30 | 31088.59 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 73698.93 | 04-JAN-08:20 | 95087.50 | 02-JAN-06:10 | 18670.14 | 09-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 164619.53 | 02-FEB-16:00 | 31088.59 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 73697.29 | 02-FEB-08:20 | 113239.06 | 27-FEB-15:09 | 18923.48 | 27-FEB-15:09 | 0.00 | 01-FEB-00:10 |
March | 159536.17 | 22-MAR-07:10 | 31088.59 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 73695.29 | 22-MAR-07:19 | 130569.32 | 14-MAR-15:20 | 18880.83 | 14-MAR-15:39 | 0.00 | 01-MAR-00:10 |
April | 150271.05 | 03-APR-07:10 | 31088.59 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 73690.43 | 03-APR-07:19 | 214685.47 | 27-APR-14:39 | 36208.95 | 26-APR-14:39 | 0.00 | 01-APR-00:10 |
May | 147313.67 | 17-MAY-07:10 | 22480.63 | 01-MAY-19:19 | 423497.50 | 01-MAY-07:10 | 73688.88 | 17-MAY-07:19 | 200067.71 | 15-MAY-14:30 | 35246.21 | 05-MAY-13:20 | 0.00 | 01-MAY-00:10 |
June | 146329.95 | 29-JUN-07:10 | 22480.63 | 01-JUN-19:00 | 541788.89 | 01-JUN-07:10 | 73688.37 | 29-JUN-07:19 | 196851.74 | 28-JUN-15:20 | 36518.56 | 27-JUN-14:00 | 0.00 | 01-JUN-00:10 |
July | 149671.39 | 12-JUL-07:30 | 22480.63 | 01-JUL-20:10 | 660080.29 | 03-JUL-07:10 | 73690.12 | 12-JUL-07:40 | 233464.81 | 31-JUL-14:30 | 36292.76 | 20-JUL-16:49 | 0.00 | 01-JUL-00:10 |
August | 149092.51 | 28-AUG-07:30 | 31088.59 | 16-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 73689.81 | 28-AUG-07:40 | 247075.85 | 10-AUG-14:39 | 39118.35 | 30-AUG-15:50 | 0.00 | 01-AUG-00:10 |
September | 159879.33 | 25-SEP-07:10 | 31088.59 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 73695.47 | 25-SEP-07:19 | 262695.26 | 11-SEP-14:30 | 37573.93 | 11-SEP-15:39 | 0.00 | 01-SEP-00:10 |
October | 169045.81 | 31-OCT-07:10 | 31088.59 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 73700.29 | 31-OCT-07:19 | 182163.92 | 04-OCT-15:39 | 19162.28 | 04-OCT-14:30 | 0.00 | 01-OCT-00:10 |
November | 169722.15 | 06-NOV-16:49 | 31088.59 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 73700.30 | 03-NOV-07:19 | 92289.11 | 15-NOV-13:20 | 18569.62 | 04-NOV-14:09 | 0.00 | 01-NOV-00:10 |
December | 169722.15 | 01-DEC-16:19 | 31088.59 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 73700.33 | 28-DEC-08:20 | 88052.11 | 05-DEC-11:00 | 19052.03 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 146329.95 | 22480.63 | 423497.50 | 73688.37 | 88052.11 | 18569.62 | 0.00 | |||||||
Maximum of Months | 169722.15 | 31088.59 | 778371.69 | 73700.33 | 262695.26 | 39118.35 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 6243.98 | 20-JAN-15:39 | 2076.72 | 11-JAN-15:30 | 61312.69 | 09-JAN-11:00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 86462.23 | 27-FEB-15:09 | 44630.31 | 27-FEB-15:30 | 100000.00 | 11-FEB-17:10 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 105030.21 | 18-MAR-15:00 | 44285.17 | 14-MAR-15:00 | 100000.00 | 01-MAR-05:10 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 295863.59 | 27-APR-15:00 | 70839.74 | 27-APR-12:20 | 100000.00 | 01-APR-16:19 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 170470.26 | 05-MAY-15:20 | 70839.74 | 05-MAY-12:00 | 100000.00 | 14-MAY-12:39 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 227024.91 | 28-JUN-15:30 | 70839.74 | 20-JUN-14:39 | 100000.00 | 01-JUN-14:09 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 328250.04 | 31-JUL-15:00 | 70839.74 | 07-JUL-12:30 | 100000.00 | 18-JUL-14:39 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 378173.61 | 29-AUG-14:30 | 70839.74 | 07-AUG-10:30 | 96402.56 | 09-AUG-08:00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 206722.29 | 11-SEP-15:39 | 70839.74 | 11-SEP-15:00 | 29301.73 | 08-SEP-14:00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 154337.43 | 04-OCT-14:00 | 45359.73 | 04-OCT-14:00 | 100000.00 | 03-OCT-11:20 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 124387.63 | 04-NOV-14:09 | 45425.35 | 04-NOV-14:30 | 100000.00 | 13-NOV-22:10 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30226.52 | 14-DEC-11:00 | 11694.27 | 14-DEC-11:00 | 100000.00 | 02-DEC-05:19 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 6243.98 | 2076.72 | 29301.73 | 0.00 | 0.00 | 0.00 | ||||
Maximum of Months | 378173.61 | 70839.74 | 100000.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 804164.71 | 10-JAN-16:00 | 169722.15 | 423497.50 | 31088.59 | 52602.06 | 68484.74 | 3384.63 | 0.00 | 3971.48 | 937.78 |
February | 1036987.62 | 27-FEB-14:00 | 145987.23 | 541788.89 | 0.00 | 24458.17 | 110167.69 | 18894.83 | 0.00 | 85372.46 | 44382.20 |
March | 1212213.16 | 14-MAR-15:50 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 128212.99 | 18879.42 | 0.00 | 88930.70 | 44259.83 |
April | 1577434.23 | 27-APR-15:09 | 145987.23 | 778371.69 | 0.00 | 52589.61 | 202504.78 | 35296.31 | 0.00 | 291844.89 | 70839.74 |
May | 1145724.19 | 15-MAY-15:20 | 145987.23 | 423497.50 | 0.00 | 52589.61 | 196428.53 | 33959.96 | 0.00 | 148200.56 | 45060.81 |
June | 1262663.70 | 28-JUN-15:20 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 196851.74 | 35417.94 | 0.00 | 219188.56 | 70839.74 |
July | 1508760.17 | 31-JUL-15:20 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 228541.20 | 35646.32 | 0.00 | 315075.80 | 70839.74 |
August | 1693406.60 | 29-AUG-15:09 | 145987.23 | 778371.69 | 0.00 | 52589.61 | 245279.33 | 35877.41 | 0.00 | 364461.60 | 70839.74 |
September | 1137119.00 | 11-SEP-15:39 | 145987.23 | 423497.50 | 0.00 | 52589.61 | 206008.86 | 37573.93 | 0.00 | 206722.29 | 64739.58 |
October | 1218748.47 | 04-OCT-15:09 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 163021.39 | 18995.78 | 0.00 | 151039.97 | 45325.61 |
November | 1110075.96 | 13-NOV-16:00 | 169722.15 | 660080.29 | 31088.59 | 52602.06 | 71696.83 | 18336.19 | 0.00 | 15648.66 | 2202.86 |
December | 1252179.74 | 05-DEC-16:19 | 169722.15 | 778371.69 | 31088.59 | 52598.49 | 75519.57 | 18331.49 | 0.00 | 23373.17 | 3174.59 |
Annual Sum or Average | |||||||||||
Minimum of Months | 804164.71 | 145987.23 | 423497.50 | 0.00 | 24458.17 | 68484.74 | 3384.63 | 0.00 | 3971.48 | 937.78 | |
Maximum of Months | 1693406.60 | 169722.15 | 778371.69 | 31088.59 | 52602.06 | 245279.33 | 37573.93 | 0.00 | 364461.60 | 70839.74 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1264816.00 | 02-JAN-05:19 | 0.00 | 82953.01 | 31-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 668469.96 | 21-FEB-06:10 | 0.00 | 82993.97 | 13-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 434866.62 | 01-MAR-07:10 | 0.00 | 82873.73 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 285238.95 | 19-APR-06:10 | 0.00 | 82082.93 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 300549.79 | 17-MAY-13:20 | 0.00 | 80936.35 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 253007.92 | 13-JUN-09:39 | 0.00 | 79467.45 | 01-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 56894.50 | 12-JUL-09:20 | 0.00 | 78015.52 | 05-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 67515.04 | 03-AUG-09:09 | 0.00 | 77508.00 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 260010.98 | 27-SEP-09:20 | 0.00 | 78307.39 | 28-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 305952.51 | 28-OCT-05:10 | 0.00 | 79805.51 | 31-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 485035.64 | 24-NOV-07:10 | 0.00 | 81228.74 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 804955.99 | 26-DEC-07:10 | 0.00 | 82321.02 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 56894.50 | 0.00 | 77508.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1264816.00 | 0.00 | 82993.97 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.79 | 0.33 | 26.93 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.78 | 0.00 | 25.78 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.78 | 0.00 | 25.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.84 | 0.00 | 25.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 26.38 | 0.00 | 26.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 26.33 | 0.00 | 26.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.07 | 0.00 | 27.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.03 | 0.00 | 27.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.09 | 1.33 | 27.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 26.99 | 1.67 | 27.07 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.00 | 0.17 | 27.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.72 | 0.00 | 25.72 |
Annual Sum or Average | 0.00 | 0.00 | 41.83 | 26.72 | 3.50 | 26.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.72 | 0.00 | 25.72 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.09 | 1.67 | 27.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 25.59 | 0.00 | 25.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 19.62 | 1.17 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.83 | 19.62 | 1.17 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.62 | 1.17 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 18.94 | 1.33 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
February | 0.83 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
December | 0.83 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 |
Annual Sum or Average | 5.83 | 18.85 | 1.33 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 19.10 | 1.33 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.37 | 0.50 | 27.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.88 | 1.83 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.87 | 3.33 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.03 | 4.67 | 28.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.07 | 4.00 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.95 | 2.00 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.33 | 27.96 | 16.33 | 27.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.07 | 4.67 | 28.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.40 | 0.33 | 27.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.78 | 1.33 | 27.78 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.81 | 2.00 | 27.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.74 | 3.50 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.59 | 3.83 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.82 | 5.50 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.06 | 4.00 | 28.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.21 | 4.17 | 27.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.83 | 2.50 | 27.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.78 | 1.33 | 27.78 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.68 | 0.83 | 27.68 |
Annual Sum or Average | 0.00 | 0.00 | 30.17 | 27.71 | 29.67 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.21 | 0.33 | 27.21 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.06 | 5.50 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.44 | 0.83 | 27.44 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.44 | 1.50 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.71 | 5.00 | 27.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.40 | 4.33 | 28.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.95 | 5.00 | 27.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 27.68 | 10.50 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27.49 | 9.83 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.56 | 4.50 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.54 | 2.50 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.43 | 1.33 | 27.43 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.47 | 0.83 | 27.47 |
Annual Sum or Average | 0.00 | 0.00 | 81.17 | 27.70 | 46.17 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 28.40 | 10.50 | 28.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 19.10 | 1.67 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
February | 1.33 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
December | 1.67 | 19.33 | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Annual Sum or Average | 9.33 | 19.16 | 1.83 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 19.43 | 1.67 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.67 | 19.03 | 0.33 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
February | 1.17 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.98 | 1.67 | 27.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.88 | 3.17 | 27.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.08 | 5.17 | 28.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.16 | 4.33 | 28.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.03 | 1.67 | 28.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
December | 5.00 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
Annual Sum or Average | 13.17 | 19.22 | 0.33 | 19.12 | 16.00 | 23.96 | 16.00 | 25.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.67 | 19.47 | 0.33 | 19.47 | 5.17 | 28.16 | 5.17 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
February | 0.67 | 19.32 | 0.00 | 19.32 | 1.00 | 24.51 | 1.00 | 25.81 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.79 | 1.67 | 27.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.74 | 3.50 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.54 | 3.00 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.87 | 4.67 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.15 | 3.67 | 28.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.38 | 3.83 | 27.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.90 | 2.33 | 27.90 |
November | 0.17 | 19.43 | 0.00 | 19.43 | 1.00 | 26.71 | 1.00 | 27.27 |
December | 0.83 | 19.14 | 0.00 | 19.14 | 0.50 | 22.26 | 0.50 | 23.68 |
Annual Sum or Average | 4.33 | 19.18 | 0.00 | 19.18 | 25.67 | 26.53 | 25.17 | 27.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 19.43 | 0.00 | 19.43 | 4.83 | 28.15 | 4.67 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
February | 0.50 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.60 | 1.33 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.35 | 3.33 | 28.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.07 | 2.50 | 28.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.31 | 4.33 | 28.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.46 | 2.33 | 28.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.45 | 3.67 | 27.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Annual Sum or Average | 3.00 | 19.17 | 0.00 | 19.17 | 29.67 | 27.31 | 17.50 | 27.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.33 | 0.00 | 19.33 | 8.33 | 28.46 | 4.33 | 28.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.33 | 17.10 | 10.33 | 17.34 | 0.00 | 17.34 | 0.00 | 17.34 |
February | 19.17 | 17.32 | 5.67 | 17.38 | 0.00 | 17.38 | 0.00 | 17.38 |
March | 3.83 | 19.14 | 0.33 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
April | 0.83 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
November | 7.83 | 18.93 | 1.33 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
December | 15.83 | 18.37 | 3.67 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
Annual Sum or Average | 82.83 | 17.71 | 21.33 | 17.85 | 0.00 | 17.85 | 0.00 | 17.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.33 | 19.28 | 10.33 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.33 | 15.96 | 3.33 | 15.83 | 0.00 | 15.83 | 0.00 | 15.83 |
February | 9.17 | 16.67 | 1.00 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
March | 3.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
April | 0.83 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
May | 0.17 | 19.41 | 0.00 | 19.41 | 1.50 | 27.01 | 1.50 | 27.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.67 | 3.67 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.05 | 5.33 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.03 | 4.67 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.92 | 1.33 | 27.92 |
October | 0.83 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
November | 3.67 | 18.43 | 0.00 | 18.43 | 0.00 | 18.43 | 0.00 | 18.43 |
December | 7.67 | 17.43 | 0.17 | 17.38 | 0.00 | 17.38 | 0.00 | 17.38 |
Annual Sum or Average | 46.67 | 16.86 | 4.50 | 16.69 | 16.83 | 19.47 | 16.50 | 21.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 0.00 | 15.83 |
Maximum of Months | 21.33 | 19.41 | 3.33 | 19.41 | 5.50 | 28.05 | 5.33 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.83 | 16.47 | 1.00 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
February | 5.33 | 17.55 | 0.50 | 17.32 | 0.00 | 17.32 | 0.00 | 17.32 |
March | 1.67 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
April | 0.50 | 19.29 | 0.00 | 19.29 | 1.33 | 25.49 | 1.33 | 26.47 |
May | 0.17 | 19.43 | 0.00 | 19.43 | 3.50 | 27.35 | 3.50 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.59 | 2.83 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.98 | 4.17 | 28.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.22 | 3.33 | 28.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.21 | 3.50 | 27.20 |
October | 0.50 | 19.32 | 0.00 | 19.32 | 1.00 | 25.00 | 1.00 | 26.14 |
November | 3.00 | 18.86 | 0.00 | 18.86 | 0.50 | 20.07 | 0.50 | 20.98 |
December | 6.00 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 |
Annual Sum or Average | 32.00 | 17.41 | 1.50 | 17.30 | 21.50 | 21.39 | 20.17 | 23.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.37 | 0.00 | 16.37 |
Maximum of Months | 14.83 | 19.43 | 1.00 | 19.43 | 4.67 | 28.22 | 4.17 | 28.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.00 | 17.39 | 0.83 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
February | 4.33 | 17.83 | 0.67 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 |
March | 1.17 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
April | 0.33 | 19.42 | 0.00 | 19.42 | 1.33 | 25.95 | 1.00 | 26.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.39 | 3.33 | 28.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.12 | 2.50 | 28.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.38 | 4.50 | 28.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.50 | 2.33 | 28.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.61 | 3.17 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
December | 4.33 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
Annual Sum or Average | 21.17 | 18.07 | 1.50 | 17.86 | 28.50 | 23.64 | 16.83 | 24.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.00 | 19.42 | 0.83 | 19.42 | 8.50 | 28.50 | 4.50 | 28.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.25 | 4.33 | 28.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 28.67 | 68.00 | 28.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 73.67 | 28.65 | 72.33 | 28.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 28.67 | 68.00 | 28.68 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 155.83 | 23.91 | 55.33 | 24.45 | 0.00 | 24.45 |
February | 95.00 | 23.96 | 73.00 | 24.73 | 0.00 | 24.73 |
March | 59.83 | 24.01 | 83.00 | 25.12 | 0.00 | 25.12 |
April | 14.33 | 24.00 | 138.67 | 25.42 | 0.00 | 25.42 |
May | 3.83 | 24.00 | 186.83 | 25.15 | 0.00 | 25.15 |
June | 0.00 | 0.00 | 207.33 | 25.01 | 0.00 | 25.01 |
July | 0.00 | 0.00 | 362.00 | 24.78 | 0.00 | 24.78 |
August | 0.17 | 24.00 | 442.67 | 24.51 | 0.17 | 24.51 |
September | 0.00 | 0.00 | 312.17 | 24.77 | 0.00 | 24.77 |
October | 0.00 | 0.00 | 152.67 | 25.69 | 0.00 | 25.69 |
November | 9.67 | 24.00 | 159.33 | 25.44 | 0.00 | 25.44 |
December | 58.00 | 24.00 | 97.00 | 25.35 | 0.00 | 25.35 |
Annual Sum or Average | 396.67 | 23.96 | 2270.00 | 24.93 | 0.17 | 24.93 |
Minimum of Months | 0.00 | 0.00 | 55.33 | 24.45 | 0.00 | 24.45 |
Maximum of Months | 155.83 | 24.01 | 442.67 | 25.69 | 0.17 | 25.69 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 281.17 | 23.91 | 16.33 | 23.98 | 13.00 | 24.04 |
February | 132.67 | 23.91 | 56.67 | 24.21 | 0.00 | 24.21 |
March | 51.33 | 23.99 | 81.67 | 24.90 | 0.00 | 24.90 |
April | 4.83 | 24.00 | 147.83 | 24.92 | 0.00 | 24.92 |
May | 5.50 | 23.89 | 185.50 | 24.67 | 0.00 | 24.67 |
June | 0.00 | 0.00 | 245.00 | 24.54 | 0.00 | 24.54 |
July | 0.00 | 0.00 | 387.83 | 24.40 | 0.00 | 24.40 |
August | 0.00 | 0.00 | 469.00 | 24.25 | 0.00 | 24.25 |
September | 0.00 | 0.00 | 324.17 | 24.50 | 0.00 | 24.50 |
October | 3.83 | 23.82 | 137.17 | 25.20 | 0.00 | 25.20 |
November | 25.00 | 23.95 | 151.67 | 24.91 | 0.00 | 24.91 |
December | 78.50 | 23.97 | 85.33 | 24.86 | 0.00 | 24.86 |
Annual Sum or Average | 582.83 | 23.93 | 2288.17 | 24.51 | 13.00 | 24.51 |
Minimum of Months | 0.00 | 0.00 | 16.33 | 23.98 | 0.00 | 24.04 |
Maximum of Months | 281.17 | 24.00 | 469.00 | 25.20 | 13.00 | 25.20 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.27 | 26.67 | 22.12 | 26.67 | 21.98 |
February | 436.00 | 22.98 | 0.00 | 22.98 | 0.00 | 22.98 |
March | 395.33 | 23.60 | 0.17 | 23.60 | 0.00 | 23.60 |
April | 235.50 | 23.64 | 32.00 | 23.78 | 0.00 | 23.78 |
May | 117.17 | 23.66 | 84.00 | 24.02 | 0.00 | 24.02 |
June | 35.50 | 23.71 | 121.50 | 24.36 | 0.00 | 24.36 |
July | 2.83 | 23.59 | 267.83 | 24.37 | 0.00 | 24.37 |
August | 7.50 | 23.57 | 380.33 | 24.24 | 0.00 | 24.24 |
September | 26.33 | 23.56 | 227.83 | 24.34 | 0.00 | 24.34 |
October | 214.50 | 23.50 | 34.67 | 23.70 | 0.00 | 23.70 |
November | 386.00 | 23.26 | 14.50 | 23.31 | 0.00 | 23.31 |
December | 496.17 | 22.86 | 0.00 | 22.86 | 0.00 | 22.86 |
Annual Sum or Average | 2854.83 | 23.10 | 1189.50 | 23.45 | 26.67 | 23.42 |
Minimum of Months | 2.83 | 22.27 | 0.00 | 22.12 | 0.00 | 21.98 |
Maximum of Months | 502.00 | 23.71 | 380.33 | 24.37 | 26.67 | 24.37 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.02 | 168.83 | 20.66 | 168.83 | 20.45 |
February | 450.17 | 21.59 | 99.67 | 21.28 | 99.67 | 21.06 |
March | 501.33 | 22.54 | 23.00 | 22.45 | 23.00 | 22.37 |
April | 365.67 | 23.00 | 25.00 | 23.09 | 0.00 | 23.09 |
May | 230.17 | 23.32 | 63.33 | 23.52 | 0.00 | 23.52 |
June | 101.33 | 23.49 | 108.17 | 23.94 | 0.00 | 23.94 |
July | 43.50 | 23.56 | 262.00 | 24.19 | 0.00 | 24.19 |
August | 49.33 | 23.44 | 337.67 | 24.11 | 0.00 | 24.11 |
September | 166.50 | 23.27 | 136.50 | 23.69 | 0.00 | 23.69 |
October | 428.50 | 22.72 | 0.17 | 22.72 | 0.17 | 22.72 |
November | 481.50 | 21.90 | 51.33 | 21.74 | 51.33 | 21.61 |
December | 497.00 | 21.29 | 128.67 | 21.04 | 128.67 | 20.87 |
Annual Sum or Average | 3817.00 | 22.18 | 1404.33 | 22.34 | 471.67 | 22.14 |
Minimum of Months | 43.50 | 21.02 | 0.17 | 20.66 | 0.00 | 20.45 |
Maximum of Months | 502.00 | 23.56 | 337.67 | 24.19 | 168.83 | 24.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.10 | 23.17 | 22.03 | 23.17 | 21.98 |
February | 417.00 | 22.57 | 7.17 | 22.53 | 7.17 | 22.50 |
March | 418.50 | 23.30 | 0.00 | 23.30 | 0.00 | 23.30 |
April | 219.00 | 23.55 | 53.17 | 23.72 | 0.00 | 23.72 |
May | 145.33 | 23.52 | 115.00 | 23.93 | 0.00 | 23.93 |
June | 32.00 | 23.68 | 190.33 | 24.32 | 0.00 | 24.32 |
July | 0.00 | 0.00 | 369.67 | 24.35 | 0.00 | 24.35 |
August | 4.00 | 23.99 | 413.67 | 24.23 | 0.33 | 24.23 |
September | 100.83 | 23.42 | 193.17 | 24.04 | 0.00 | 24.04 |
October | 305.67 | 23.31 | 22.00 | 23.42 | 0.00 | 23.42 |
November | 396.83 | 23.02 | 9.00 | 23.06 | 0.00 | 23.06 |
December | 495.00 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
Annual Sum or Average | 3036.17 | 22.92 | 1396.33 | 23.34 | 30.67 | 23.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.03 | 0.00 | 21.98 |
Maximum of Months | 502.00 | 23.99 | 413.67 | 24.35 | 23.17 | 24.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.83 | 22.05 | 26.00 | 21.98 | 26.00 | 21.92 |
February | 402.67 | 22.54 | 9.67 | 22.53 | 6.33 | 22.50 |
March | 372.50 | 23.09 | 8.00 | 23.11 | 0.00 | 23.11 |
April | 182.00 | 23.32 | 116.00 | 23.74 | 0.33 | 23.75 |
May | 134.67 | 23.59 | 185.50 | 24.13 | 6.83 | 24.19 |
June | 54.83 | 24.38 | 273.17 | 24.44 | 13.50 | 24.54 |
July | 24.67 | 26.02 | 376.33 | 24.51 | 16.67 | 24.62 |
August | 34.33 | 25.23 | 406.00 | 24.34 | 16.83 | 24.44 |
September | 102.83 | 23.63 | 249.50 | 24.19 | 7.17 | 24.25 |
October | 289.83 | 23.18 | 64.50 | 23.44 | 0.17 | 23.44 |
November | 411.83 | 22.76 | 16.00 | 22.82 | 0.00 | 22.82 |
December | 492.67 | 22.37 | 0.00 | 22.37 | 0.00 | 22.37 |
Annual Sum or Average | 3004.67 | 22.81 | 1730.67 | 23.37 | 93.83 | 23.40 |
Minimum of Months | 24.67 | 22.05 | 0.00 | 21.98 | 0.00 | 21.92 |
Maximum of Months | 501.83 | 26.02 | 406.00 | 24.51 | 26.00 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 458.67 | 21.89 | 64.33 | 21.82 | 51.67 | 21.69 |
February | 340.83 | 22.44 | 80.67 | 22.72 | 18.33 | 22.66 |
March | 329.67 | 23.04 | 77.00 | 23.28 | 0.33 | 23.29 |
April | 189.67 | 23.44 | 147.83 | 23.89 | 5.17 | 23.94 |
May | 163.50 | 23.63 | 190.33 | 24.08 | 11.50 | 24.17 |
June | 69.67 | 24.18 | 262.00 | 24.39 | 13.17 | 24.49 |
July | 28.67 | 26.01 | 372.33 | 24.56 | 19.67 | 24.68 |
August | 29.00 | 25.56 | 426.50 | 24.40 | 16.67 | 24.49 |
September | 83.50 | 23.85 | 285.00 | 24.32 | 12.83 | 24.41 |
October | 243.33 | 23.23 | 134.83 | 23.72 | 8.17 | 23.79 |
November | 373.50 | 22.70 | 51.00 | 22.96 | 4.33 | 23.00 |
December | 423.83 | 22.30 | 42.67 | 22.48 | 4.17 | 22.47 |
Annual Sum or Average | 2733.83 | 22.80 | 2134.50 | 23.47 | 166.00 | 23.49 |
Minimum of Months | 28.67 | 21.89 | 42.67 | 21.82 | 0.33 | 21.69 |
Maximum of Months | 458.67 | 26.01 | 426.50 | 24.56 | 51.67 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 462.83 | 23.00 | 1.17 | 23.00 | 0.00 | 23.00 |
February | 259.50 | 23.59 | 69.33 | 23.85 | 1.50 | 23.86 |
March | 75.33 | 24.04 | 129.67 | 24.56 | 2.17 | 24.59 |
April | 26.50 | 26.57 | 301.33 | 24.99 | 22.67 | 25.12 |
May | 47.67 | 25.18 | 299.00 | 24.70 | 20.50 | 24.83 |
June | 19.17 | 27.04 | 430.50 | 24.64 | 19.17 | 24.74 |
July | 53.50 | 26.83 | 488.50 | 24.90 | 53.50 | 25.07 |
August | 61.67 | 26.33 | 514.00 | 24.73 | 61.67 | 24.89 |
September | 25.33 | 26.36 | 383.83 | 24.68 | 21.00 | 24.78 |
October | 39.83 | 24.45 | 184.17 | 24.87 | 8.17 | 24.94 |
November | 101.17 | 24.04 | 126.17 | 24.54 | 3.83 | 24.58 |
December | 144.33 | 23.99 | 57.83 | 24.37 | 0.67 | 24.38 |
Annual Sum or Average | 1316.83 | 23.99 | 2985.50 | 24.47 | 214.83 | 24.58 |
Minimum of Months | 19.17 | 23.00 | 1.17 | 23.00 | 0.00 | 23.00 |
Maximum of Months | 462.83 | 27.04 | 514.00 | 24.99 | 61.67 | 25.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.35 | 331.83 | 20.20 | 331.83 | 20.13 |
February | 454.00 | 20.83 | 196.33 | 20.59 | 196.33 | 20.46 |
March | 511.17 | 21.80 | 50.50 | 21.67 | 50.50 | 21.57 |
April | 426.00 | 22.52 | 18.83 | 22.56 | 3.67 | 22.55 |
May | 288.00 | 22.99 | 53.33 | 23.18 | 0.00 | 23.18 |
June | 147.67 | 23.31 | 91.00 | 23.66 | 0.00 | 23.66 |
July | 87.33 | 23.47 | 240.83 | 24.00 | 0.00 | 24.00 |
August | 104.67 | 23.34 | 294.00 | 23.94 | 0.00 | 23.94 |
September | 250.67 | 23.01 | 87.17 | 23.30 | 0.00 | 23.30 |
October | 483.00 | 22.21 | 9.17 | 22.17 | 9.17 | 22.14 |
November | 489.00 | 21.21 | 121.17 | 21.01 | 121.17 | 20.88 |
December | 497.00 | 20.61 | 273.67 | 20.46 | 273.67 | 20.39 |
Annual Sum or Average | 4240.50 | 21.71 | 1767.83 | 21.77 | 986.33 | 21.53 |
Minimum of Months | 87.33 | 20.35 | 9.17 | 20.20 | 0.00 | 20.13 |
Maximum of Months | 511.17 | 23.47 | 331.83 | 24.00 | 331.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.31 | 282.00 | 20.13 | 282.00 | 20.05 |
February | 383.50 | 21.15 | 151.67 | 20.88 | 151.67 | 20.73 |
March | 403.17 | 22.12 | 32.50 | 21.99 | 31.00 | 21.88 |
April | 255.67 | 22.65 | 67.67 | 23.02 | 1.50 | 23.01 |
May | 190.83 | 23.07 | 118.00 | 23.67 | 6.33 | 23.74 |
June | 96.00 | 23.73 | 187.50 | 24.29 | 13.00 | 24.40 |
July | 70.00 | 24.48 | 273.17 | 24.51 | 19.83 | 24.65 |
August | 72.83 | 24.26 | 308.50 | 24.37 | 17.67 | 24.48 |
September | 173.50 | 23.20 | 160.67 | 23.82 | 6.50 | 23.88 |
October | 337.00 | 22.25 | 32.00 | 22.36 | 7.83 | 22.32 |
November | 412.33 | 21.33 | 104.50 | 21.11 | 103.50 | 20.96 |
December | 422.00 | 20.67 | 230.83 | 20.48 | 230.83 | 20.38 |
Annual Sum or Average | 3243.83 | 21.79 | 1949.00 | 22.12 | 871.67 | 21.90 |
Minimum of Months | 70.00 | 20.31 | 32.00 | 20.13 | 1.50 | 20.05 |
Maximum of Months | 427.00 | 24.48 | 308.50 | 24.51 | 282.00 | 24.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 472.17 | 20.89 | 230.33 | 20.66 | 222.83 | 20.51 |
February | 373.33 | 21.57 | 146.17 | 21.64 | 99.17 | 21.46 |
March | 369.50 | 22.16 | 95.00 | 22.42 | 22.00 | 22.32 |
April | 266.83 | 22.66 | 124.00 | 23.25 | 4.83 | 23.29 |
May | 221.17 | 23.13 | 165.83 | 23.70 | 11.33 | 23.79 |
June | 143.33 | 23.48 | 203.33 | 24.03 | 10.67 | 24.12 |
July | 99.67 | 24.01 | 314.33 | 24.33 | 16.50 | 24.43 |
August | 82.17 | 24.02 | 360.50 | 24.27 | 15.50 | 24.37 |
September | 156.83 | 23.46 | 256.33 | 24.06 | 13.67 | 24.15 |
October | 316.00 | 22.61 | 122.17 | 23.17 | 10.17 | 23.25 |
November | 429.83 | 21.75 | 102.67 | 21.79 | 71.50 | 21.66 |
December | 446.50 | 21.15 | 203.00 | 21.04 | 178.33 | 20.88 |
Annual Sum or Average | 3377.33 | 22.09 | 2323.67 | 22.62 | 676.50 | 22.45 |
Minimum of Months | 82.17 | 20.89 | 95.00 | 20.66 | 4.83 | 20.51 |
Maximum of Months | 472.17 | 24.02 | 360.50 | 24.33 | 222.83 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.68 | 255.50 | 20.46 | 255.50 | 20.35 |
February | 429.67 | 21.32 | 121.83 | 21.09 | 117.83 | 20.93 |
March | 439.50 | 22.25 | 42.00 | 22.26 | 20.33 | 22.19 |
April | 303.83 | 22.86 | 86.00 | 23.24 | 4.67 | 23.28 |
May | 199.17 | 23.42 | 166.83 | 23.91 | 16.33 | 24.04 |
June | 92.17 | 23.72 | 230.00 | 24.20 | 9.83 | 24.28 |
July | 51.17 | 24.99 | 374.17 | 24.55 | 21.00 | 24.66 |
August | 38.17 | 24.54 | 399.17 | 24.36 | 13.50 | 24.44 |
September | 145.33 | 23.62 | 234.17 | 24.12 | 16.50 | 24.23 |
October | 385.00 | 22.54 | 50.50 | 22.77 | 1.00 | 22.78 |
November | 467.67 | 21.61 | 75.83 | 21.50 | 67.83 | 21.38 |
December | 494.17 | 21.05 | 182.33 | 20.84 | 182.33 | 20.72 |
Annual Sum or Average | 3547.83 | 21.97 | 2218.33 | 22.44 | 726.67 | 22.27 |
Minimum of Months | 38.17 | 20.68 | 42.00 | 20.46 | 1.00 | 20.35 |
Maximum of Months | 502.00 | 24.99 | 399.17 | 24.55 | 255.50 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.01 | 411.50 | 19.91 | 411.50 | 19.87 |
February | 454.00 | 20.36 | 288.00 | 20.15 | 288.00 | 20.06 |
March | 514.00 | 21.10 | 182.33 | 20.86 | 182.33 | 20.71 |
April | 439.83 | 21.96 | 70.67 | 21.81 | 60.83 | 21.65 |
May | 329.00 | 22.50 | 57.33 | 22.66 | 8.67 | 22.61 |
June | 196.33 | 22.98 | 91.83 | 23.38 | 0.00 | 23.38 |
July | 130.33 | 23.16 | 235.67 | 23.82 | 0.00 | 23.82 |
August | 144.33 | 23.00 | 269.83 | 23.74 | 0.00 | 23.74 |
September | 314.17 | 22.53 | 67.50 | 22.80 | 0.00 | 22.80 |
October | 498.50 | 21.48 | 81.00 | 21.26 | 81.00 | 21.09 |
November | 489.00 | 20.52 | 254.00 | 20.29 | 254.00 | 20.17 |
December | 497.00 | 20.11 | 407.00 | 20.02 | 407.00 | 19.99 |
Annual Sum or Average | 4508.50 | 21.26 | 2416.67 | 21.23 | 1693.33 | 20.97 |
Minimum of Months | 130.33 | 20.01 | 57.33 | 19.91 | 0.00 | 19.87 |
Maximum of Months | 514.00 | 23.16 | 411.50 | 23.82 | 411.50 | 23.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.06 | 390.00 | 19.93 | 390.00 | 19.88 |
February | 454.00 | 20.67 | 250.00 | 20.39 | 250.00 | 20.26 |
March | 492.00 | 21.58 | 120.00 | 21.27 | 119.50 | 21.05 |
April | 301.17 | 22.10 | 97.83 | 22.27 | 36.17 | 22.11 |
May | 235.00 | 22.58 | 148.17 | 23.23 | 12.83 | 23.23 |
June | 132.17 | 23.42 | 230.17 | 24.07 | 14.00 | 24.18 |
July | 107.17 | 23.98 | 326.33 | 24.29 | 21.33 | 24.42 |
August | 101.67 | 23.81 | 360.17 | 24.19 | 19.00 | 24.30 |
September | 224.67 | 22.61 | 172.00 | 23.37 | 5.17 | 23.41 |
October | 418.33 | 21.65 | 73.17 | 21.50 | 61.00 | 21.33 |
November | 487.83 | 20.68 | 233.17 | 20.41 | 233.17 | 20.28 |
December | 497.00 | 20.18 | 369.83 | 20.04 | 369.83 | 19.99 |
Annual Sum or Average | 3953.00 | 21.34 | 2770.83 | 21.61 | 1532.00 | 21.34 |
Minimum of Months | 101.67 | 20.06 | 73.17 | 19.93 | 5.17 | 19.88 |
Maximum of Months | 502.00 | 23.98 | 390.00 | 24.29 | 390.00 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.83 | 20.46 | 311.83 | 20.19 | 309.50 | 20.07 |
February | 394.33 | 21.00 | 211.83 | 20.89 | 180.67 | 20.70 |
March | 398.83 | 21.51 | 152.33 | 21.44 | 107.50 | 21.22 |
April | 299.83 | 22.12 | 142.83 | 22.48 | 46.00 | 22.34 |
May | 254.17 | 22.59 | 157.33 | 23.25 | 17.00 | 23.31 |
June | 179.33 | 23.11 | 192.17 | 23.79 | 11.50 | 23.88 |
July | 133.50 | 23.59 | 298.50 | 24.16 | 16.50 | 24.27 |
August | 128.50 | 23.52 | 341.00 | 24.10 | 14.83 | 24.20 |
September | 207.50 | 22.83 | 221.33 | 23.65 | 10.83 | 23.73 |
October | 345.83 | 21.81 | 137.50 | 22.24 | 40.50 | 22.11 |
November | 448.50 | 21.00 | 200.33 | 20.89 | 172.33 | 20.69 |
December | 462.83 | 20.55 | 296.50 | 20.34 | 286.33 | 20.21 |
Annual Sum or Average | 3741.00 | 21.58 | 2663.50 | 21.96 | 1213.50 | 21.70 |
Minimum of Months | 128.50 | 20.46 | 137.50 | 20.19 | 10.83 | 20.07 |
Maximum of Months | 487.83 | 23.59 | 341.00 | 24.16 | 309.50 | 24.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.25 | 338.33 | 20.05 | 338.33 | 19.96 |
February | 437.67 | 20.83 | 218.33 | 20.56 | 216.50 | 20.41 |
March | 460.50 | 21.60 | 120.50 | 21.43 | 106.50 | 21.25 |
April | 335.33 | 22.29 | 107.83 | 22.55 | 35.83 | 22.46 |
May | 250.00 | 22.92 | 157.67 | 23.51 | 18.00 | 23.64 |
June | 146.67 | 23.34 | 219.67 | 23.97 | 11.33 | 24.06 |
July | 95.50 | 24.18 | 348.50 | 24.40 | 23.17 | 24.52 |
August | 88.83 | 23.80 | 366.00 | 24.23 | 17.83 | 24.31 |
September | 214.50 | 23.08 | 199.00 | 23.72 | 16.00 | 23.84 |
October | 425.17 | 21.89 | 71.00 | 21.94 | 36.50 | 21.82 |
November | 477.33 | 20.95 | 178.50 | 20.73 | 172.67 | 20.58 |
December | 497.00 | 20.52 | 307.33 | 20.32 | 307.33 | 20.23 |
Annual Sum or Average | 3930.50 | 21.56 | 2632.67 | 21.88 | 1300.00 | 21.65 |
Minimum of Months | 88.83 | 20.25 | 71.00 | 20.05 | 11.33 | 19.96 |
Maximum of Months | 502.00 | 24.18 | 366.00 | 24.40 | 338.33 | 24.52 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.33 | 27.00 | 454.00 | 27.00 | 0.33 | 27.00 |
March | 6.33 | 27.00 | 514.00 | 27.00 | 6.33 | 27.00 |
April | 65.50 | 27.00 | 485.00 | 27.00 | 65.50 | 27.00 |
May | 2.00 | 27.00 | 508.00 | 27.00 | 2.00 | 27.00 |
June | 28.83 | 27.00 | 496.00 | 27.00 | 28.83 | 27.00 |
July | 138.83 | 27.00 | 497.00 | 27.00 | 138.83 | 27.00 |
August | 277.00 | 27.00 | 514.00 | 27.00 | 277.00 | 27.00 |
September | 20.00 | 27.00 | 485.00 | 27.00 | 20.00 | 27.00 |
October | 7.83 | 27.00 | 502.00 | 27.00 | 7.83 | 27.00 |
November | 6.33 | 27.00 | 489.00 | 27.00 | 6.33 | 27.00 |
December | 1.83 | 27.00 | 497.00 | 27.00 | 1.83 | 27.00 |
Annual Sum or Average | 554.83 | 27.00 | 5943.00 | 27.00 | 554.83 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 277.00 | 27.00 | 514.00 | 27.00 | 277.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.67 | 24.64 | 397.17 | 26.85 | 0.00 | 26.85 |
February | 0.00 | 0.00 | 420.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 5.50 | 27.00 | 485.00 | 27.00 | 5.50 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 4.33 | 27.00 | 496.00 | 27.00 | 4.33 | 27.00 |
July | 26.00 | 27.00 | 497.00 | 27.00 | 26.00 | 27.00 |
August | 49.33 | 27.01 | 514.00 | 27.00 | 49.33 | 27.00 |
September | 5.83 | 27.00 | 485.00 | 27.00 | 5.83 | 27.00 |
October | 2.00 | 27.00 | 502.00 | 27.00 | 2.00 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 117.67 | 26.51 | 5804.17 | 26.99 | 93.00 | 26.99 |
Minimum of Months | 0.00 | 0.00 | 397.17 | 26.85 | 0.00 | 26.85 |
Maximum of Months | 49.33 | 27.01 | 514.00 | 27.00 | 49.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 134.17 | 24.62 | 269.67 | 26.06 | 12.33 | 25.96 |
February | 24.00 | 27.00 | 337.17 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 478.17 | 27.00 | 0.00 | 27.00 |
April | 8.50 | 27.00 | 485.00 | 27.00 | 8.50 | 27.00 |
May | 0.83 | 27.00 | 508.00 | 27.00 | 0.83 | 27.00 |
June | 8.83 | 27.00 | 496.00 | 27.00 | 8.83 | 27.00 |
July | 43.17 | 27.00 | 497.00 | 27.00 | 43.17 | 27.00 |
August | 67.33 | 27.01 | 514.00 | 27.00 | 67.33 | 27.00 |
September | 9.00 | 27.00 | 485.00 | 27.00 | 9.00 | 27.00 |
October | 2.17 | 27.00 | 500.67 | 27.00 | 2.17 | 27.00 |
November | 0.00 | 0.00 | 450.83 | 27.00 | 0.00 | 27.00 |
December | 6.50 | 27.00 | 402.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 304.50 | 25.95 | 5423.83 | 26.93 | 152.17 | 26.93 |
Minimum of Months | 0.00 | 0.00 | 269.67 | 26.06 | 0.00 | 25.96 |
Maximum of Months | 134.17 | 27.01 | 514.00 | 27.00 | 67.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 151.00 | 27.00 | 502.00 | 27.00 | 151.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.01 | 485.00 | 27.01 | 485.00 | 27.01 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 27.25 | 514.00 | 27.25 | 514.00 | 27.25 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5592.00 | 27.02 | 5943.00 | 27.02 | 5592.00 | 27.02 |
Minimum of Months | 151.00 | 27.00 | 454.00 | 27.00 | 151.00 | 27.00 |
Maximum of Months | 514.00 | 27.25 | 514.00 | 27.25 | 514.00 | 27.25 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 26.85322 | 0.76642 | 17.46167 |
February | 454.00000 | 27.00006 | 27.14425 | 0.83389 | 19.78415 |
March | 514.00000 | 27.00003 | 28.04766 | 0.89806 | 22.09257 |
April | 485.00000 | 27.00002 | 30.79671 | 0.97583 | 25.16380 |
May | 508.00000 | 27.00023 | 33.79958 | 0.23336 | 6.21224 |
June | 496.00000 | 27.00025 | 35.08219 | 0.30620 | 7.00788 |
July | 497.00000 | 27.00029 | 36.35390 | 0.38864 | 8.21994 |
August | 514.00000 | 27.00130 | 37.01664 | 0.42773 | 8.90142 |
September | 485.00000 | 27.00058 | 36.65034 | 0.26654 | 6.56365 |
October | 502.00000 | 27.00012 | 33.30890 | 0.92042 | 22.92917 |
November | 489.00000 | 27.00009 | 31.35570 | 0.91376 | 22.68219 |
December | 497.00000 | 27.00000 | 27.25992 | 0.89839 | 22.07570 |
Annual Sum or Average | 5943.00000 | 27.00025 | 32.00399 | 0.65056 | 15.70876 |
Minimum of Months | 454.00000 | 27.00000 | 26.85322 | 0.23336 | 6.21224 |
Maximum of Months | 514.00000 | 27.00130 | 37.01664 | 0.97583 | 25.16380 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.85082 | 27.67712 | 0.58862 | 12.70054 |
February | 454.00000 | 27.00005 | 27.14944 | 0.68202 | 14.98128 |
March | 514.00000 | 27.00003 | 28.02751 | 0.76451 | 17.43382 |
April | 485.00000 | 27.00002 | 30.77536 | 0.84409 | 20.14465 |
May | 508.00000 | 27.00022 | 33.82358 | 0.15118 | 5.61289 |
June | 496.00000 | 27.00024 | 35.08278 | 0.20799 | 5.99214 |
July | 497.00000 | 27.00029 | 36.35477 | 0.27146 | 6.64524 |
August | 514.00000 | 27.00112 | 37.01865 | 0.29344 | 6.92262 |
September | 485.00000 | 27.00055 | 36.76230 | 0.18950 | 5.87365 |
October | 502.00000 | 27.00011 | 33.30774 | 0.81524 | 19.09796 |
November | 489.00000 | 27.00008 | 31.34301 | 0.74910 | 16.92450 |
December | 497.00000 | 27.00000 | 27.24772 | 0.68788 | 15.03170 |
Annual Sum or Average | 5943.00000 | 26.98763 | 32.07982 | 0.51868 | 12.24557 |
Minimum of Months | 454.00000 | 26.85082 | 27.14944 | 0.15118 | 5.61289 |
Maximum of Months | 514.00000 | 27.00112 | 37.01865 | 0.84409 | 20.14465 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.26817 | 28.13889 | 0.41910 | 10.69429 |
February | 454.00000 | 27.00006 | 27.16164 | 0.61325 | 13.22997 |
March | 514.00000 | 27.00003 | 28.03802 | 0.69919 | 15.50851 |
April | 485.00000 | 27.00002 | 30.78299 | 0.80211 | 18.79434 |
May | 508.00000 | 27.00035 | 33.84545 | 0.11858 | 5.60133 |
June | 496.00000 | 27.00024 | 35.08989 | 0.19549 | 5.99293 |
July | 497.00000 | 27.00030 | 36.35423 | 0.26725 | 6.70402 |
August | 514.00000 | 27.00099 | 37.01847 | 0.28446 | 6.91953 |
September | 485.00000 | 27.00051 | 36.84866 | 0.15127 | 5.74421 |
October | 502.00000 | 27.00011 | 33.33934 | 0.75417 | 17.14694 |
November | 489.00000 | 27.00009 | 31.36250 | 0.67046 | 14.62243 |
December | 497.00000 | 27.00000 | 27.25313 | 0.60967 | 12.94723 |
Annual Sum or Average | 5943.00000 | 26.93841 | 32.13546 | 0.46378 | 11.13022 |
Minimum of Months | 454.00000 | 26.26817 | 27.16164 | 0.11858 | 5.60133 |
Maximum of Months | 514.00000 | 27.00099 | 37.01847 | 0.80211 | 18.79434 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99998 | 30.01456 | 1.01302 | 26.67808 |
February | 454.00000 | 27.00034 | 30.51665 | 1.19363 | 34.94761 |
March | 514.00000 | 27.00040 | 28.90881 | 1.33875 | 42.28867 |
April | 485.00000 | 27.01455 | 29.81834 | 1.49169 | 50.45164 |
May | 508.00000 | 27.00011 | 32.19194 | 0.48386 | 9.95097 |
June | 496.00000 | 27.00077 | 32.82287 | 0.71868 | 15.89701 |
July | 497.00000 | 27.00650 | 35.48507 | 0.95880 | 24.44930 |
August | 514.00000 | 27.24634 | 35.49503 | 1.21842 | 36.39642 |
September | 485.00000 | 27.00010 | 36.86678 | 0.55087 | 11.42575 |
October | 502.00000 | 27.00027 | 31.24251 | 1.23462 | 36.96206 |
November | 489.00000 | 27.00056 | 31.22130 | 1.36937 | 43.89373 |
December | 497.00000 | 27.00048 | 28.59017 | 1.47006 | 49.27932 |
Annual Sum or Average | 5943.00000 | 27.02329 | 31.93635 | 1.08603 | 31.85519 |
Minimum of Months | 454.00000 | 26.99998 | 28.59017 | 0.48386 | 9.95097 |
Maximum of Months | 514.00000 | 27.24634 | 36.86678 | 1.49169 | 50.45164 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.35684 | 27.59346 | 0.33587 | 7.69325 |
February | 454.00000 | 24.38698 | 28.70859 | 0.35873 | 8.02856 |
March | 514.00000 | 24.36344 | 28.42975 | 0.36458 | 8.07000 |
April | 485.00000 | 24.47082 | 31.93644 | 0.41852 | 9.15397 |
May | 508.00000 | 24.44823 | 36.64784 | -0.4185 | 9.52667 |
June | 496.00000 | 24.42432 | 38.70823 | -0.4001 | 9.10700 |
July | 497.00000 | 24.56656 | 44.04071 | -0.3124 | 8.15120 |
August | 514.00000 | 24.44143 | 48.04871 | -0.3153 | 7.91172 |
September | 485.00000 | 24.49940 | 44.18416 | -0.3376 | 8.43625 |
October | 502.00000 | 24.52146 | 35.19169 | 0.45578 | 9.91278 |
November | 489.00000 | 24.51854 | 33.51161 | 0.43813 | 9.59309 |
December | 497.00000 | 24.47607 | 28.09615 | 0.38282 | 8.51060 |
Annual Sum or Average | 5943.00000 | 24.45613 | 35.47633 | 0.07791 | 8.67535 |
Minimum of Months | 454.00000 | 24.35684 | 27.59346 | -0.4185 | 7.69325 |
Maximum of Months | 514.00000 | 24.56656 | 48.04871 | 0.45578 | 9.91278 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.04693 | 31.96957 | 0.28600 | 7.20403 |
February | 454.00000 | 24.19979 | 30.65743 | 0.32833 | 7.48804 |
March | 514.00000 | 24.28533 | 30.15184 | 0.36691 | 8.03749 |
April | 485.00000 | 24.31371 | 32.92660 | 0.41007 | 8.77112 |
May | 508.00000 | 24.27439 | 38.11458 | -0.4489 | 9.64454 |
June | 496.00000 | 24.26884 | 40.11054 | -0.4155 | 8.98662 |
July | 497.00000 | 24.31577 | 44.84727 | -0.3536 | 7.99054 |
August | 514.00000 | 24.23172 | 48.72722 | -0.3432 | 7.71788 |
September | 485.00000 | 24.33667 | 45.72101 | -0.3705 | 8.44141 |
October | 502.00000 | 24.35163 | 36.95080 | 0.43091 | 9.18280 |
November | 489.00000 | 24.36315 | 35.56591 | 0.41550 | 8.92638 |
December | 497.00000 | 24.34413 | 30.46225 | 0.36934 | 8.12300 |
Annual Sum or Average | 5943.00000 | 24.27768 | 37.23406 | 0.05337 | 8.38000 |
Minimum of Months | 454.00000 | 24.04693 | 30.15184 | -0.4489 | 7.20403 |
Maximum of Months | 514.00000 | 24.36315 | 48.72722 | 0.43091 | 9.64454 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.26843 | 33.85207 | -0.1817 | 7.21522 |
February | 454.00000 | 23.02507 | 34.09914 | 0.01952 | 5.78563 |
March | 514.00000 | 23.71308 | 32.95870 | 0.19964 | 6.10634 |
April | 485.00000 | 23.92867 | 35.38610 | 0.28173 | 6.93486 |
May | 508.00000 | 24.05587 | 39.25137 | -0.5517 | 11.70175 |
June | 496.00000 | 24.11427 | 41.08586 | -0.5045 | 10.54366 |
July | 497.00000 | 24.19555 | 46.17594 | -0.4400 | 9.36324 |
August | 514.00000 | 24.16596 | 49.81670 | -0.4169 | 8.90280 |
September | 485.00000 | 24.15179 | 46.79425 | -0.4611 | 9.79810 |
October | 502.00000 | 23.88645 | 39.48674 | 0.29509 | 7.10264 |
November | 489.00000 | 23.43409 | 39.09596 | 0.15828 | 6.07535 |
December | 497.00000 | 22.86310 | 34.37881 | -0.0228 | 5.58246 |
Annual Sum or Average | 5943.00000 | 23.65480 | 39.40317 | -0.1373 | 7.94505 |
Minimum of Months | 454.00000 | 22.26843 | 32.95870 | -0.5517 | 5.58246 |
Maximum of Months | 514.00000 | 24.19555 | 49.81670 | 0.29509 | 11.70175 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.01639 | 35.30696 | -0.5007 | 13.10691 |
February | 454.00000 | 21.60573 | 35.92557 | -0.3381 | 10.04603 |
March | 514.00000 | 22.57605 | 35.29936 | -0.0886 | 6.46219 |
April | 485.00000 | 23.27493 | 37.07801 | 0.11559 | 6.29131 |
May | 508.00000 | 23.74083 | 40.28962 | -0.6679 | 15.32567 |
June | 496.00000 | 23.99876 | 41.44658 | -0.5458 | 11.61982 |
July | 497.00000 | 24.12150 | 46.43348 | -0.4598 | 9.77734 |
August | 514.00000 | 24.07098 | 50.20039 | -0.4481 | 9.57377 |
September | 485.00000 | 23.80719 | 48.23632 | -0.5918 | 13.04673 |
October | 502.00000 | 22.90880 | 42.30133 | 0.04541 | 6.16486 |
November | 489.00000 | 21.93576 | 42.71524 | -0.2161 | 7.61007 |
December | 497.00000 | 21.29151 | 36.94257 | -0.4204 | 10.12908 |
Annual Sum or Average | 5943.00000 | 22.87253 | 41.04731 | -0.3436 | 9.93109 |
Minimum of Months | 454.00000 | 21.01639 | 35.29936 | -0.6679 | 6.16486 |
Maximum of Months | 514.00000 | 24.12150 | 50.20039 | 0.11559 | 15.32567 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.09545 | 31.77793 | -0.2100 | 6.84777 |
February | 454.00000 | 22.68435 | 31.92669 | -0.0582 | 6.34546 |
March | 514.00000 | 23.43640 | 31.16358 | 0.12861 | 5.90510 |
April | 485.00000 | 23.87625 | 33.04573 | 0.27519 | 7.00479 |
May | 508.00000 | 23.98677 | 37.63908 | -0.5587 | 12.33474 |
June | 496.00000 | 24.16567 | 39.37603 | -0.4532 | 9.70575 |
July | 497.00000 | 24.27747 | 43.98135 | -0.3600 | 8.12222 |
August | 514.00000 | 24.18649 | 47.97410 | -0.3641 | 8.12681 |
September | 485.00000 | 24.02242 | 45.67073 | -0.5083 | 11.08551 |
October | 502.00000 | 23.63419 | 37.97104 | 0.22475 | 6.51488 |
November | 489.00000 | 23.22463 | 37.19563 | 0.10591 | 6.00089 |
December | 497.00000 | 22.77528 | 32.30582 | -0.0408 | 5.52600 |
Annual Sum or Average | 5943.00000 | 23.53652 | 37.54291 | -0.1530 | 7.80292 |
Minimum of Months | 454.00000 | 22.09545 | 31.16358 | -0.5587 | 5.52600 |
Maximum of Months | 514.00000 | 24.27747 | 47.97410 | 0.27519 | 12.33474 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.04820 | 31.91232 | -0.2212 | 6.99873 |
February | 454.00000 | 22.72192 | 31.87852 | -0.0447 | 6.51033 |
March | 514.00000 | 23.35823 | 31.09677 | 0.12779 | 6.15285 |
April | 485.00000 | 23.85881 | 32.81379 | 0.30735 | 7.80014 |
May | 508.00000 | 24.06949 | 37.22792 | -0.4786 | 11.59771 |
June | 496.00000 | 24.23194 | 38.95127 | -0.3600 | 9.23710 |
July | 497.00000 | 24.32630 | 43.74587 | -0.2832 | 8.18393 |
August | 514.00000 | 24.19184 | 47.82152 | -0.2932 | 8.21898 |
September | 485.00000 | 24.09101 | 45.22022 | -0.4277 | 10.48343 |
October | 502.00000 | 23.60790 | 37.77207 | 0.23821 | 7.01226 |
November | 489.00000 | 22.97109 | 37.73423 | 0.04981 | 6.10852 |
December | 497.00000 | 22.38407 | 32.98885 | -0.1288 | 6.10279 |
Annual Sum or Average | 5943.00000 | 23.49416 | 37.47025 | -0.1274 | 7.87560 |
Minimum of Months | 454.00000 | 22.04820 | 31.09677 | -0.4786 | 6.10279 |
Maximum of Months | 514.00000 | 24.32630 | 47.82152 | 0.30735 | 11.59771 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.09625 | 31.67662 | -0.2056 | 7.94703 |
February | 454.00000 | 22.94147 | 31.13278 | 0.02711 | 7.73550 |
March | 514.00000 | 23.44167 | 30.55623 | 0.17495 | 7.05260 |
April | 485.00000 | 23.90480 | 32.51877 | 0.33155 | 8.49136 |
May | 508.00000 | 24.01197 | 37.25068 | -0.4977 | 12.29650 |
June | 496.00000 | 24.20228 | 39.07611 | -0.4013 | 9.70356 |
July | 497.00000 | 24.35166 | 43.59816 | -0.2757 | 8.01981 |
August | 514.00000 | 24.25361 | 47.49001 | -0.2570 | 7.78358 |
September | 485.00000 | 24.17066 | 44.78596 | -0.3523 | 9.82488 |
October | 502.00000 | 23.76208 | 37.09130 | 0.30999 | 8.59001 |
November | 489.00000 | 23.07918 | 37.20597 | 0.08747 | 7.14196 |
December | 497.00000 | 22.58970 | 32.28481 | -0.0662 | 7.05744 |
Annual Sum or Average | 5943.00000 | 23.57164 | 37.09860 | -0.0953 | 8.47520 |
Minimum of Months | 454.00000 | 22.09625 | 30.55623 | -0.4977 | 7.05260 |
Maximum of Months | 514.00000 | 24.35166 | 47.49001 | 0.33155 | 12.29650 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.07842 | 29.97362 | 0.02377 | 5.83312 |
February | 454.00000 | 23.90601 | 29.13080 | 0.25279 | 7.25429 |
March | 514.00000 | 24.27742 | 28.51722 | 0.39451 | 8.68192 |
April | 485.00000 | 24.53328 | 30.97321 | 0.54361 | 12.14704 |
May | 508.00000 | 24.37468 | 36.25697 | -0.3167 | 8.97719 |
June | 496.00000 | 24.45939 | 38.20895 | -0.2138 | 7.47607 |
July | 497.00000 | 24.67797 | 42.54310 | -0.0285 | 7.27547 |
August | 514.00000 | 24.54050 | 46.50241 | -0.0341 | 6.96103 |
September | 485.00000 | 24.44419 | 43.90370 | -0.2475 | 7.99640 |
October | 502.00000 | 24.37147 | 35.39757 | 0.45313 | 9.93034 |
November | 489.00000 | 24.29681 | 33.91552 | 0.39377 | 8.83769 |
December | 497.00000 | 24.26841 | 28.48564 | 0.34401 | 7.76735 |
Annual Sum or Average | 5943.00000 | 24.27080 | 35.36484 | 0.12880 | 8.25900 |
Minimum of Months | 454.00000 | 23.07842 | 28.48564 | -0.3167 | 5.83312 |
Maximum of Months | 514.00000 | 24.67797 | 46.50241 | 0.54361 | 12.14704 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.34922 | 34.16039 | -0.6873 | 16.88836 |
February | 454.00000 | 20.83051 | 34.74498 | -0.5293 | 12.99866 |
March | 514.00000 | 21.80797 | 34.74532 | -0.2642 | 7.66515 |
April | 485.00000 | 22.70839 | 36.32594 | -0.0163 | 6.43112 |
May | 508.00000 | 23.45005 | 39.28328 | -0.7567 | 18.70764 |
June | 496.00000 | 23.84390 | 40.60613 | -0.5899 | 13.01981 |
July | 497.00000 | 24.01207 | 44.96247 | -0.4873 | 10.52575 |
August | 514.00000 | 23.94487 | 49.15513 | -0.4874 | 10.64610 |
September | 485.00000 | 23.50475 | 47.52267 | -0.6996 | 16.54109 |
October | 502.00000 | 22.27683 | 41.86913 | -0.1000 | 6.35911 |
November | 489.00000 | 21.21221 | 41.06019 | -0.3896 | 9.50076 |
December | 497.00000 | 20.60798 | 35.51345 | -0.5995 | 13.42699 |
Annual Sum or Average | 5943.00000 | 22.39169 | 40.03095 | -0.4672 | 11.88572 |
Minimum of Months | 454.00000 | 20.34922 | 34.16039 | -0.7567 | 6.35911 |
Maximum of Months | 514.00000 | 24.01207 | 49.15513 | -0.0163 | 18.70764 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.30899 | 33.51552 | -0.6957 | 17.26429 |
February | 385.00000 | 21.16453 | 33.45140 | -0.4479 | 11.48455 |
March | 433.00000 | 22.24679 | 33.25739 | -0.1508 | 7.31202 |
April | 410.00000 | 23.24508 | 34.13128 | 0.14037 | 7.32807 |
May | 430.00000 | 23.72491 | 37.75940 | -0.6177 | 16.25007 |
June | 418.00000 | 24.11558 | 39.19900 | -0.4226 | 11.10811 |
July | 422.00000 | 24.28307 | 43.59394 | -0.3278 | 9.50009 |
August | 433.00000 | 24.18888 | 47.63413 | -0.3239 | 9.32368 |
September | 410.00000 | 23.79818 | 45.82370 | -0.5492 | 14.07141 |
October | 427.00000 | 22.65101 | 40.19089 | 0.00039 | 6.78048 |
November | 417.00000 | 21.35779 | 40.03226 | -0.3569 | 9.37906 |
December | 422.00000 | 20.66568 | 34.80115 | -0.5857 | 13.35592 |
Annual Sum or Average | 5034.00000 | 22.65460 | 38.64857 | -0.3614 | 11.09510 |
Minimum of Months | 385.00000 | 20.30899 | 33.25739 | -0.6957 | 6.78048 |
Maximum of Months | 433.00000 | 24.28307 | 47.63413 | 0.14037 | 17.26429 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.09697 | 32.89423 | -0.4784 | 13.24906 |
February | 454.00000 | 22.07211 | 32.30492 | -0.1919 | 9.80937 |
March | 514.00000 | 22.73613 | 32.36814 | 0.00766 | 7.79384 |
April | 485.00000 | 23.36800 | 34.12122 | 0.19633 | 8.20833 |
May | 508.00000 | 23.71448 | 38.10701 | -0.6018 | 15.89583 |
June | 496.00000 | 23.97143 | 39.86529 | -0.4931 | 12.08356 |
July | 497.00000 | 24.18317 | 44.18800 | -0.3540 | 9.64391 |
August | 514.00000 | 24.13222 | 48.09941 | -0.3212 | 9.21554 |
September | 485.00000 | 23.96867 | 45.46045 | -0.4174 | 11.88154 |
October | 502.00000 | 23.22497 | 38.82517 | 0.18661 | 8.56129 |
November | 489.00000 | 22.07384 | 39.06855 | -0.1617 | 8.72092 |
December | 497.00000 | 21.48008 | 33.74704 | -0.3603 | 10.91815 |
Annual Sum or Average | 5943.00000 | 23.00934 | 38.29662 | -0.2501 | 10.50666 |
Minimum of Months | 454.00000 | 21.09697 | 32.30492 | -0.6018 | 7.79384 |
Maximum of Months | 514.00000 | 24.18317 | 48.09941 | 0.19633 | 15.89583 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.68132 | 33.57319 | -0.5852 | 14.11497 |
February | 454.00000 | 21.47166 | 33.42732 | -0.3565 | 10.29494 |
March | 514.00000 | 22.52542 | 33.05914 | -0.0747 | 7.00653 |
April | 485.00000 | 23.36623 | 34.43839 | 0.17966 | 7.68877 |
May | 508.00000 | 23.84778 | 37.96209 | -0.5449 | 14.45537 |
June | 496.00000 | 24.08335 | 39.66253 | -0.4265 | 10.54752 |
July | 497.00000 | 24.34663 | 43.69728 | -0.2497 | 8.44781 |
August | 514.00000 | 24.23107 | 47.88949 | -0.2794 | 8.48231 |
September | 485.00000 | 23.99874 | 45.63398 | -0.4512 | 11.74003 |
October | 502.00000 | 22.93246 | 39.94417 | 0.07479 | 6.79991 |
November | 489.00000 | 21.71949 | 39.87076 | -0.2589 | 8.14308 |
December | 497.00000 | 21.06234 | 34.63730 | -0.4708 | 10.86282 |
Annual Sum or Average | 5943.00000 | 22.86660 | 38.68599 | -0.2869 | 9.87913 |
Minimum of Months | 454.00000 | 20.68132 | 33.05914 | -0.5852 | 6.79991 |
Maximum of Months | 514.00000 | 24.34663 | 47.88949 | 0.17966 | 14.45537 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.01081 | 34.82311 | -0.8123 | 21.78363 |
February | 454.00000 | 20.35727 | 35.56849 | -0.6874 | 18.02249 |
March | 514.00000 | 21.10188 | 35.80505 | -0.4615 | 11.33940 |
April | 485.00000 | 22.14859 | 37.36353 | -0.1620 | 7.81246 |
May | 508.00000 | 23.04502 | 40.25727 | -0.8966 | 24.87957 |
June | 496.00000 | 23.64358 | 41.10971 | -0.6565 | 15.61562 |
July | 497.00000 | 23.87451 | 45.27761 | -0.5287 | 12.06707 |
August | 514.00000 | 23.78976 | 49.61855 | -0.5374 | 12.40875 |
September | 485.00000 | 23.04874 | 48.87889 | -0.8590 | 22.96392 |
October | 502.00000 | 21.49405 | 43.56312 | -0.3076 | 8.68133 |
November | 489.00000 | 20.51841 | 42.57958 | -0.5983 | 14.89265 |
December | 497.00000 | 20.11343 | 36.59215 | -0.7703 | 19.72979 |
Annual Sum or Average | 5943.00000 | 21.94216 | 40.98689 | -0.6061 | 15.83012 |
Minimum of Months | 454.00000 | 20.01081 | 34.82311 | -0.8966 | 7.81246 |
Maximum of Months | 514.00000 | 23.87451 | 49.61855 | -0.1620 | 24.87957 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.05709 | 34.74426 | -0.7918 | 21.07839 |
February | 454.00000 | 20.66549 | 35.06873 | -0.5988 | 15.71427 |
March | 514.00000 | 21.68501 | 34.76904 | -0.3066 | 9.91492 |
April | 485.00000 | 22.86396 | 35.31220 | 0.04531 | 7.87743 |
May | 508.00000 | 23.44545 | 38.88837 | -0.7033 | 19.81637 |
June | 496.00000 | 23.97434 | 39.68472 | -0.4546 | 12.14282 |
July | 497.00000 | 24.13377 | 44.25052 | -0.3536 | 10.16171 |
August | 514.00000 | 24.05720 | 48.37244 | -0.3474 | 9.99653 |
September | 485.00000 | 23.44883 | 47.29220 | -0.6609 | 18.29063 |
October | 502.00000 | 22.04357 | 41.97851 | -0.1613 | 8.23193 |
November | 489.00000 | 20.68827 | 42.15863 | -0.5517 | 14.02814 |
December | 497.00000 | 20.18063 | 36.47122 | -0.7439 | 18.92076 |
Annual Sum or Average | 5943.00000 | 22.28374 | 39.94735 | -0.4683 | 13.82759 |
Minimum of Months | 454.00000 | 20.05709 | 34.74426 | -0.7918 | 7.87743 |
Maximum of Months | 514.00000 | 24.13377 | 48.37244 | 0.04531 | 21.07839 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.56787 | 33.84678 | -0.6402 | 17.88308 |
February | 454.00000 | 21.42835 | 33.34602 | -0.3821 | 13.02953 |
March | 514.00000 | 22.08626 | 33.43663 | -0.1764 | 9.92110 |
April | 485.00000 | 22.90657 | 35.02386 | 0.07093 | 8.75311 |
May | 508.00000 | 23.36523 | 38.96587 | -0.7259 | 21.14481 |
June | 496.00000 | 23.77952 | 40.34027 | -0.5572 | 14.62917 |
July | 497.00000 | 24.04495 | 44.52038 | -0.3957 | 11.21315 |
August | 514.00000 | 23.99539 | 48.52180 | -0.3662 | 10.76717 |
September | 485.00000 | 23.61813 | 46.55751 | -0.5463 | 16.43151 |
October | 502.00000 | 22.58653 | 40.22697 | 0.00919 | 9.09221 |
November | 489.00000 | 21.30072 | 40.73660 | -0.3843 | 12.21074 |
December | 497.00000 | 20.80373 | 35.15323 | -0.5645 | 16.08319 |
Annual Sum or Average | 5943.00000 | 22.54963 | 39.26285 | -0.3887 | 13.43434 |
Minimum of Months | 454.00000 | 20.56787 | 33.34602 | -0.7259 | 8.75311 |
Maximum of Months | 514.00000 | 24.04495 | 48.52180 | 0.07093 | 21.14481 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.24594 | 34.36328 | -0.7229 | 18.99091 |
February | 454.00000 | 20.94872 | 34.29968 | -0.5119 | 14.09582 |
March | 514.00000 | 21.86820 | 34.07309 | -0.2515 | 9.20522 |
April | 485.00000 | 22.87530 | 35.36694 | 0.05377 | 8.18735 |
May | 508.00000 | 23.52205 | 38.76607 | -0.6590 | 19.10553 |
June | 496.00000 | 23.91272 | 40.09992 | -0.4836 | 12.63538 |
July | 497.00000 | 24.22930 | 43.98094 | -0.2852 | 9.55578 |
August | 514.00000 | 24.11582 | 48.25481 | -0.3180 | 9.65080 |
September | 485.00000 | 23.66720 | 46.67030 | -0.5714 | 15.86124 |
October | 502.00000 | 22.24638 | 41.39562 | -0.1043 | 7.68712 |
November | 489.00000 | 21.03272 | 41.28808 | -0.4527 | 11.64694 |
December | 497.00000 | 20.51656 | 35.71894 | -0.6385 | 15.67087 |
Annual Sum or Average | 5943.00000 | 22.44395 | 39.55764 | -0.4117 | 12.67932 |
Minimum of Months | 454.00000 | 20.24594 | 34.07309 | -0.7229 | 7.68712 |
Maximum of Months | 514.00000 | 24.22930 | 48.25481 | 0.05377 | 19.10553 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 68177244.80 | 2213.54 | 11-JAN-06:03 | 22.67 | 0.344413E+09 | 0.00 | 0.412590E+09 | 0.15 | 5.17 | 07-JAN-07:00 | 0.00 | 0.00 |
February | 0.189363E+10 | 66545.75 | 27-FEB-15:05 | 68.24 | 0.114286E+11 | 0.00 | 0.133222E+11 | 0.53 | 7.90 | 27-FEB-15:05 | 0.00 | 0.00 |
March | 0.714365E+10 | 61352.48 | 14-MAR-16:00 | 138.10 | 0.436602E+11 | 0.00 | 0.508038E+11 | 1.00 | 7.83 | 14-MAR-16:00 | 0.00 | 0.00 |
April | 0.139081E+11 | 126425.88 | 27-APR-16:10 | 135.26 | 0.948863E+11 | 0.00 | 0.108794E+12 | 1.10 | 7.96 | 26-APR-17:10 | 0.00 | 0.00 |
May | 0.239753E+11 | 128959.15 | 05-MAY-14:10 | 207.81 | 0.161008E+12 | 0.00 | 0.184983E+12 | 1.66 | 7.96 | 03-MAY-14:30 | 0.00 | 0.00 |
June | 0.419491E+11 | 129172.35 | 20-JUN-13:05 | 320.38 | 0.290990E+12 | 0.00 | 0.332939E+12 | 2.74 | 7.96 | 19-JUN-14:00 | 0.00 | 0.00 |
July | 0.675790E+11 | 135850.32 | 11-JUL-15:30 | 444.70 | 0.487951E+12 | 0.00 | 0.555530E+12 | 3.84 | 7.96 | 14-JUL-18:30 | 0.00 | 0.00 |
August | 0.793760E+11 | 138182.47 | 25-AUG-10:20 | 504.76 | 0.576256E+12 | 0.00 | 0.655632E+12 | 4.35 | 7.96 | 11-AUG-12:10 | 0.00 | 0.00 |
September | 0.355347E+11 | 134757.31 | 14-SEP-12:00 | 274.65 | 0.245052E+12 | 0.00 | 0.280587E+12 | 2.32 | 7.96 | 08-SEP-15:00 | 0.00 | 0.00 |
October | 0.117062E+11 | 117522.41 | 04-OCT-15:00 | 123.29 | 0.782938E+11 | 0.00 | 0.900000E+11 | 0.95 | 7.96 | 04-OCT-12:10 | 0.00 | 0.00 |
November | 0.205032E+10 | 58461.30 | 04-NOV-14:10 | 97.87 | 0.123191E+11 | 0.00 | 0.143694E+11 | 0.70 | 7.78 | 04-NOV-14:10 | 0.00 | 0.00 |
December | 0.102335E+10 | 8352.84 | 05-DEC-14:40 | 113.88 | 0.516150E+10 | 0.00 | 0.618486E+10 | 0.77 | 5.17 | 26-DEC-06:40 | 0.00 | 0.00 |
Annual Sum or Average | 0.286208E+12 | 2451.60 | 0.200735E+13 | 0.00 | 0.229356E+13 | 1.69 | 0.00 | 0.00 | ||||
Minimum of Months | 68177244.80 | 2213.54 | 22.67 | 0.344413E+09 | 0.00 | 0.412590E+09 | 0.15 | 5.17 | 0.00 | 0.00 | ||
Maximum of Months | 0.793760E+11 | 138182.47 | 504.76 | 0.576256E+12 | 0.00 | 0.655632E+12 | 4.35 | 7.96 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.174032E+10 | 94329.82 | 27-APR-12:10 | 6.83 | 0.135181E+11 | 0.00 | 0.152584E+11 | 0.07 | 7.96 | 26-APR-14:05 | 0.00 | 0.00 |
May | 0.121135E+10 | 71432.39 | 05-MAY-14:20 | 5.25 | 0.937916E+10 | 0.00 | 0.105905E+11 | 0.05 | 7.93 | 15-MAY-13:05 | 0.00 | 0.00 |
June | 0.279661E+10 | 84119.70 | 28-JUN-13:00 | 11.92 | 0.217638E+11 | 0.00 | 0.245604E+11 | 0.13 | 7.96 | 27-JUN-13:50 | 0.00 | 0.00 |
July | 0.932928E+10 | 105796.20 | 31-JUL-16:00 | 35.08 | 0.708416E+11 | 0.00 | 0.801709E+11 | 0.36 | 7.96 | 19-JUL-15:20 | 0.00 | 0.00 |
August | 0.233743E+11 | 115014.56 | 29-AUG-14:30 | 82.58 | 0.175740E+12 | 0.00 | 0.199115E+12 | 0.83 | 7.96 | 09-AUG-10:20 | 0.00 | 0.00 |
September | 0.394608E+10 | 129062.37 | 11-SEP-15:32 | 16.17 | 0.300309E+11 | 0.00 | 0.339769E+11 | 0.17 | 7.96 | 08-SEP-15:00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.423979E+11 | 157.83 | 0.321274E+12 | 0.00 | 0.363672E+12 | 0.14 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.233743E+11 | 129062.37 | 82.58 | 0.175740E+12 | 0.00 | 0.199115E+12 | 0.83 | 7.96 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.104082E+10 | 744.00 | 2076.72 | 11-JAN-15:30 | 27691.82 | 20-JAN-16:20 | 18.59 | 18.33 | 14.03 |
February | 0.456797E+10 | 672.00 | 43776.24 | 27-FEB-13:05 | 105716.32 | 27-FEB-15:05 | 19.27 | 18.34 | 14.03 |
March | 0.100332E+11 | 744.00 | 43776.24 | 09-MAR-12:00 | 275309.48 | 18-MAR-16:01 | 20.02 | 18.35 | 14.03 |
April | 0.284527E+11 | 720.00 | 43776.24 | 01-APR-10:05 | 628897.48 | 27-APR-15:10 | 22.11 | 18.90 | 14.03 |
May | 0.207544E+11 | 744.00 | 43776.24 | 02-MAY-15:30 | 147739.05 | 05-MAY-16:00 | 19.36 | 18.72 | 14.03 |
June | 0.426383E+11 | 720.00 | 43776.24 | 01-JUN-14:00 | 339720.26 | 28-JUN-17:00 | 20.86 | 19.27 | 14.03 |
July | 0.729806E+11 | 744.00 | 43776.24 | 01-JUL-12:20 | 549225.69 | 27-JUL-16:10 | 25.20 | 21.00 | 14.03 |
August | 0.101624E+12 | 744.00 | 43776.24 | 01-AUG-00:05 | 662573.98 | 10-AUG-19:15 | 31.42 | 23.08 | 14.03 |
September | 0.287305E+11 | 720.00 | 43776.24 | 01-SEP-14:20 | 149753.14 | 22-SEP-16:00 | 19.50 | 18.84 | 14.03 |
October | 0.125444E+11 | 744.00 | 43776.24 | 03-OCT-12:40 | 173476.31 | 04-OCT-15:00 | 19.46 | 18.38 | 14.03 |
November | 0.867999E+10 | 720.00 | 43776.24 | 04-NOV-10:30 | 343137.37 | 04-NOV-15:00 | 19.94 | 18.37 | 14.03 |
December | 0.747877E+10 | 744.00 | 11694.27 | 14-DEC-12:00 | 164015.73 | 14-DEC-12:00 | 20.37 | 18.33 | 14.03 |
Annual Sum or Average | 0.339525E+12 | 8760.00 | 21.37 | 19.17 | 14.03 | ||||
Minimum of Months | 0.104082E+10 | 672.00 | 2076.72 | 27691.82 | 18.59 | 18.33 | 14.03 | ||
Maximum of Months | 0.101624E+12 | 744.00 | 43776.24 | 662573.98 | 31.42 | 23.08 | 14.03 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 190561.52 | 07-JAN-05:52 | 21.04 | 21.03 | 0.15 |
February | 7147432.85 | 6.00 | 854.07 | 27-FEB-15:30 | 599438.16 | 27-FEB-15:10 | 21.03 | 21.00 | 1.56 |
March | 16301618.87 | 39.53 | 508.93 | 14-MAR-16:00 | 552088.78 | 14-MAR-16:00 | 21.18 | 21.08 | 4.55 |
April | 0.399161E+09 | 73.38 | 13531.75 | 27-APR-11:50 | 1054431.09 | 26-APR-14:00 | 21.34 | 21.12 | 6.86 |
May | 0.612811E+09 | 141.89 | 13531.75 | 04-MAY-13:20 | 1055737.59 | 04-MAY-13:40 | 21.65 | 21.29 | 11.94 |
June | 0.105721E+10 | 236.12 | 13531.75 | 20-JUN-12:30 | 1070869.34 | 20-JUN-13:10 | 21.87 | 21.20 | 19.31 |
July | 0.388746E+10 | 330.24 | 13531.75 | 07-JUL-11:00 | 1088129.42 | 28-JUL-13:10 | 22.26 | 21.20 | 25.54 |
August | 0.672662E+10 | 363.50 | 13531.75 | 07-AUG-09:50 | 1074676.25 | 15-AUG-12:30 | 22.51 | 21.26 | 28.39 |
September | 0.179665E+10 | 197.91 | 13531.75 | 11-SEP-13:20 | 1084354.45 | 11-SEP-14:00 | 21.81 | 21.25 | 16.72 |
October | 69670153.88 | 66.53 | 1583.49 | 04-OCT-15:00 | 1032482.49 | 04-OCT-15:00 | 21.27 | 21.09 | 6.03 |
November | 24779767.45 | 8.58 | 1649.10 | 04-NOV-14:30 | 522390.95 | 04-NOV-14:10 | 21.07 | 21.04 | 1.59 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 190041.21 | 26-DEC-04:13 | 20.94 | 20.92 | 1.11 |
Annual Sum or Average | 0.145978E+11 | 1463.69 | 21.50 | 21.12 | 10.38 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 190041.21 | 20.94 | 20.92 | 0.15 | ||
Maximum of Months | 0.672662E+10 | 363.50 | 13531.75 | 1088129.42 | 22.51 | 21.29 | 28.39 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 21.04 | 21.04 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.03 | 21.03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.18 | 21.18 | 0.00 |
April | 0.173946E+09 | 6.00 | 13531.75 | 27-APR-12:05 | 938847.06 | 26-APR-13:50 | 21.34 | 21.31 | 0.41 |
May | 74680121.83 | 4.42 | 13531.75 | 05-MAY-13:00 | 896571.32 | 15-MAY-13:05 | 21.65 | 21.63 | 0.29 |
June | 0.180104E+09 | 9.08 | 13531.75 | 20-JUN-14:40 | 946479.08 | 20-JUN-14:40 | 21.87 | 21.82 | 0.61 |
July | 0.133376E+10 | 30.33 | 13531.75 | 07-JUL-12:30 | 937326.35 | 19-JUL-15:20 | 22.26 | 22.11 | 1.98 |
August | 0.352926E+10 | 76.00 | 13531.75 | 07-AUG-10:05 | 962240.16 | 21-AUG-14:40 | 22.51 | 22.14 | 4.97 |
September | 0.640576E+09 | 13.87 | 13531.75 | 11-SEP-15:32 | 992229.18 | 11-SEP-15:35 | 21.81 | 21.74 | 0.93 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.27 | 21.27 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.07 | 21.07 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.94 | 20.94 | 0.00 |
Annual Sum or Average | 0.593232E+10 | 139.71 | 21.50 | 21.44 | 0.77 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.94 | 20.94 | 0.00 | ||
Maximum of Months | 0.352926E+10 | 76.00 | 13531.75 | 992229.18 | 22.51 | 22.14 | 4.97 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.320290E+12 | 0.00 | 486.70 | 1893200.91 | 02-JAN-05:11 | 0.00 | 36.60 | 51.71 | 1.36 | 0.00 | 0.06 | 0.99 | 02-JAN-05:11 |
February | 0.174124E+12 | 0.00 | 368.66 | 1527405.72 | 16-FEB-05:11 | 0.00 | 34.37 | 47.77 | 0.78 | 0.00 | 0.04 | 0.80 | 16-FEB-05:11 |
March | 0.731848E+11 | 0.00 | 311.49 | 1442645.70 | 06-MAR-05:11 | 0.00 | 32.57 | 43.86 | 0.26 | 0.00 | 0.01 | 0.75 | 06-MAR-05:11 |
April | 0.301099E+11 | 0.00 | 189.23 | 939686.88 | 18-APR-05:02 | 0.00 | 31.81 | 39.09 | 0.11 | 0.00 | 0.01 | 0.49 | 18-APR-05:02 |
May | 0.753040E+10 | 0.00 | 81.04 | 547852.12 | 18-MAY-05:02 | 0.00 | 31.15 | 34.26 | 0.02 | 0.00 | 0.00 | 0.29 | 18-MAY-05:02 |
June | 0.427902E+09 | 0.00 | 13.49 | 241070.98 | 13-JUN-09:40 | 0.00 | 31.08 | 31.60 | 0.00 | 0.00 | 0.00 | 0.13 | 13-JUN-09:40 |
July | 49084046.74 | 0.00 | 0.33 | 108521.25 | 12-JUL-09:20 | 0.00 | 31.70 | 31.71 | 0.00 | 0.00 | 0.00 | 0.06 | 12-JUL-09:20 |
August | 38596743.00 | 0.00 | 0.08 | 128655.81 | 03-AUG-09:05 | 0.00 | 32.13 | 32.13 | 0.00 | 0.00 | 0.00 | 0.07 | 03-AUG-09:05 |
September | 0.117695E+10 | 0.00 | 33.35 | 247325.26 | 27-SEP-09:20 | 0.00 | 31.90 | 33.21 | 0.00 | 0.00 | 0.00 | 0.13 | 27-SEP-09:20 |
October | 0.187998E+11 | 0.00 | 196.31 | 1226863.54 | 28-OCT-05:02 | 0.00 | 30.17 | 37.94 | 0.06 | 0.00 | 0.00 | 0.64 | 28-OCT-05:02 |
November | 0.120167E+12 | 0.00 | 334.91 | 1480421.24 | 24-NOV-05:11 | 0.00 | 32.28 | 44.79 | 0.45 | 0.00 | 0.02 | 0.77 | 24-NOV-05:11 |
December | 0.234989E+12 | 0.00 | 426.09 | 1387734.17 | 30-DEC-06:02 | 0.00 | 34.94 | 49.14 | 0.92 | 0.00 | 0.05 | 0.73 | 30-DEC-06:02 |
Annual Sum or Average | 0.980889E+12 | 0.00 | 2441.68 | 0.00 | 32.55 | 39.73 | 0.33 | 0.00 | 0.02 | ||||
Minimum of Months | 38596743.00 | 0.00 | 0.08 | 108521.25 | 0.00 | 30.17 | 31.60 | 0.00 | 0.00 | 0.00 | 0.06 | ||
Maximum of Months | 0.320290E+12 | 0.00 | 486.70 | 1893200.91 | 0.00 | 36.60 | 51.71 | 1.36 | 0.00 | 0.06 | 0.99 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 18.59 | 18.59 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.27 | 19.27 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 20.02 | 20.02 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 22.11 | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 19.36 | 19.36 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 20.86 | 20.86 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 25.20 | 25.20 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 31.42 | 31.42 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 19.50 | 19.50 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.46 | 19.46 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.94 | 19.94 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.37 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 21.37 | 21.37 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.59 | 18.59 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.42 | 31.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.223800E+09 | 0.00 | 14.72 | 0.223800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12160.15 | 20-JAN-13:40 | 12160.15 | 20-JAN-13:40 | 0.00 | 0.00 | 0.00 |
February | 0.349521E+10 | 0.00 | 60.87 | 0.349521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50132.69 | 27-FEB-15:00 | 50132.69 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.457988E+10 | 0.00 | 100.57 | 0.457988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53634.64 | 02-MAR-14:05 | 53634.64 | 02-MAR-14:05 | 0.00 | 0.00 | 0.00 |
April | 0.985621E+10 | 0.00 | 107.33 | 0.985621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113512.40 | 27-APR-14:40 | 113512.40 | 27-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.147860E+11 | 0.00 | 178.21 | 0.147820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90325.05 | 04-MAY-15:00 | 90325.05 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.291490E+11 | 0.00 | 293.12 | 0.291425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101336.36 | 28-JUN-15:20 | 101336.36 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.539283E+11 | 0.00 | 414.49 | 0.532572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134170.48 | 31-JUL-15:50 | 123730.05 | 31-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.736125E+11 | 0.00 | 488.93 | 0.716115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142152.16 | 29-AUG-14:30 | 129437.91 | 29-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.230622E+11 | 0.00 | 247.86 | 0.227683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117333.08 | 11-SEP-15:35 | 114827.27 | 11-SEP-15:35 | 0.00 | 0.00 | 0.00 |
October | 0.508775E+10 | 0.00 | 88.55 | 0.508775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70545.16 | 04-OCT-15:00 | 70545.16 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.331856E+10 | 0.00 | 85.82 | 0.331856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35557.42 | 15-NOV-14:00 | 35557.42 | 15-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.399675E+10 | 0.00 | 105.75 | 0.399675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39478.94 | 05-DEC-14:40 | 39478.94 | 05-DEC-14:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225096E+12 | 0.00 | 2186.22 | 0.222120E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.223800E+09 | 0.00 | 14.72 | 0.223800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12160.15 | 12160.15 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.736125E+11 | 0.00 | 488.93 | 0.716115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142152.16 | 129437.91 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 15669.10 | 0.00 | 8.09 | 15669.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 09-JAN-05:01 | 1.43 | 09-JAN-05:01 | 0.00 | 0.00 | 0.00 |
February | 0.652955E+10 | 0.00 | 21.58 | 0.652955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 433328.68 | 27-FEB-15:05 | 433328.68 | 27-FEB-15:05 | 0.00 | 0.00 | 0.00 |
March | 0.369237E+11 | 0.00 | 73.50 | 0.369237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 438531.99 | 14-MAR-15:50 | 438531.99 | 14-MAR-15:50 | 0.00 | 0.00 | 0.00 |
April | 0.852310E+11 | 0.00 | 109.81 | 0.852310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 957056.69 | 27-APR-14:40 | 957056.69 | 27-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.136074E+12 | 0.00 | 192.95 | 0.136054E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 854075.74 | 04-MAY-15:00 | 854075.74 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.240837E+12 | 0.00 | 291.22 | 0.240813E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 908871.81 | 28-JUN-15:20 | 908871.81 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.423535E+12 | 0.00 | 376.82 | 0.419837E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1171546.20 | 31-JUL-16:00 | 1056235.94 | 31-JUL-14:05 | 0.00 | 0.00 | 0.00 |
August | 0.564049E+12 | 0.00 | 395.43 | 0.550605E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1248019.42 | 29-AUG-14:30 | 1147867.46 | 29-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.216387E+12 | 0.00 | 255.06 | 0.212678E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 976656.24 | 14-SEP-13:00 | 947364.38 | 11-SEP-15:32 | 0.00 | 0.00 | 0.00 |
October | 0.664380E+11 | 0.00 | 98.08 | 0.664380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 641210.11 | 03-OCT-15:20 | 641210.11 | 03-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.734221E+10 | 0.00 | 19.53 | 0.734221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 379519.21 | 04-NOV-14:05 | 379519.21 | 04-NOV-14:05 | 0.00 | 0.00 | 0.00 |
December | 19689.31 | 0.00 | 7.96 | 19689.31 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 | 26-DEC-06:02 | 2.54 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178335E+13 | 0.00 | 1850.03 | 0.176245E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 15669.10 | 0.00 | 7.96 | 15669.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 1.43 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.564049E+12 | 0.00 | 395.43 | 0.550605E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1248019.42 | 1147867.46 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 35402.48 | 0.00 | 0.09 | 35402.48 | 0.00 | 0.00 | 0.00 | 0.00 | 139.91 | 09-JAN-04:06 | 139.91 | 09-JAN-04:06 | 0.00 | 0.00 | 0.00 |
February | 0.357279E+09 | 0.00 | 8.17 | 0.357279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25802.35 | 27-FEB-15:00 | 25802.35 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.844453E+09 | 0.00 | 28.88 | 0.844453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24720.18 | 01-MAR-15:00 | 24720.18 | 01-MAR-15:00 | 0.00 | 0.00 | 0.00 |
April | 0.707092E+10 | 0.00 | 78.15 | 0.707092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 112185.31 | 27-APR-14:40 | 112185.31 | 27-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.131420E+11 | 0.00 | 166.26 | 0.131390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94281.16 | 04-MAY-15:00 | 94281.16 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.249215E+11 | 0.00 | 275.22 | 0.249198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109389.52 | 28-JUN-15:20 | 109389.52 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.452653E+11 | 0.00 | 362.05 | 0.449182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 136071.67 | 31-JUL-16:00 | 125817.49 | 31-JUL-14:40 | 0.00 | 0.00 | 0.00 |
August | 0.591592E+11 | 0.00 | 383.03 | 0.579159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139414.56 | 10-AUG-15:40 | 133472.17 | 10-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.200373E+11 | 0.00 | 234.04 | 0.198124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104130.89 | 11-SEP-15:32 | 104130.89 | 11-SEP-15:32 | 0.00 | 0.00 | 0.00 |
October | 0.274691E+10 | 0.00 | 58.22 | 0.274691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60492.44 | 04-OCT-15:00 | 60492.44 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.488363E+09 | 0.00 | 8.00 | 0.488363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29057.60 | 04-NOV-14:10 | 29057.60 | 04-NOV-14:10 | 0.00 | 0.00 | 0.00 |
December | 21794.08 | 0.00 | 0.06 | 21794.08 | 0.00 | 0.00 | 0.00 | 0.00 | 108.97 | 26-DEC-04:50 | 108.97 | 26-DEC-04:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174033E+12 | 0.00 | 1602.16 | 0.172213E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 21794.08 | 0.00 | 0.06 | 21794.08 | 0.00 | 0.00 | 0.00 | 0.00 | 108.97 | 108.97 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.591592E+11 | 0.00 | 383.03 | 0.579159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139414.56 | 133472.17 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1824548.18 | 0.00 | 0.07 | 1824548.18 | 0.00 | 0.00 | 0.00 | 0.00 | 7750.04 | 11-JAN-06:03 | 7750.04 | 11-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.396869E+09 | 0.00 | 7.07 | 0.391437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42461.45 | 24-FEB-06:02 | 29044.00 | 24-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.103131E+09 | 0.00 | 4.15 | 96743716.39 | 0.00 | 0.00 | 0.00 | 0.00 | 33960.70 | 10-MAR-06:03 | 15477.13 | 10-MAR-06:03 | 0.00 | 0.00 | 0.00 |
April | 0.342650E+10 | 0.00 | 44.43 | 0.342164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51353.10 | 27-APR-15:00 | 51353.10 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.660191E+10 | 0.00 | 99.92 | 0.658350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50902.76 | 15-MAY-16:00 | 50902.76 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.138357E+11 | 0.00 | 198.49 | 0.137738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55512.94 | 12-JUN-04:11 | 49805.43 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.266650E+11 | 0.00 | 281.34 | 0.263222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73370.83 | 31-JUL-10:10 | 65941.32 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.366669E+11 | 0.00 | 313.96 | 0.362621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71753.00 | 25-AUG-04:12 | 62960.40 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.107371E+11 | 0.00 | 160.72 | 0.105685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61482.78 | 11-SEP-15:35 | 61482.78 | 11-SEP-15:35 | 0.00 | 0.00 | 0.00 |
October | 0.139670E+10 | 0.00 | 37.49 | 0.137789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36084.03 | 26-OCT-04:13 | 34274.10 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.272389E+09 | 0.00 | 7.20 | 0.259961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40441.10 | 04-NOV-04:13 | 24424.39 | 04-NOV-04:13 | 0.00 | 0.00 | 0.00 |
December | 4803387.88 | 0.00 | 0.16 | 4462355.55 | 0.00 | 0.00 | 0.00 | 0.00 | 14733.77 | 16-DEC-06:02 | 11891.83 | 16-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100109E+12 | 0.00 | 1155.00 | 0.990641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1824548.18 | 0.00 | 0.07 | 1824548.18 | 0.00 | 0.00 | 0.00 | 0.00 | 7750.04 | 7750.04 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.366669E+11 | 0.00 | 313.96 | 0.362621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73370.83 | 65941.32 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.434107E+10 | 0.317281E+10 | 740.67 | 0.434096E+10 | 105777.37 | 0.00 | 0.02 | 09-JAN-12:00 | 0.01 | 12-JAN-02:30 | 2990.67 | 09-JAN-12:00 | 2990.67 | 09-JAN-12:00 | 10.71 | 11-JAN-23:00 | 1516.81 | 09-JAN-12:00 | 0.00 |
February | 0.692948E+10 | 0.366748E+10 | 597.01 | 0.686141E+10 | 68069978.16 | 0.00 | 0.13 | 27-FEB-15:00 | 0.01 | 28-FEB-06:15 | 39383.88 | 27-FEB-15:00 | 39383.88 | 27-FEB-15:00 | 676.53 | 27-FEB-16:00 | 11277.75 | 27-FEB-15:00 | 0.00 |
March | 0.142634E+11 | 0.591110E+10 | 695.72 | 0.135376E+11 | 0.725822E+09 | 0.00 | 0.47 | 18-MAR-16:00 | 0.01 | 11-MAR-06:02 | 145856.80 | 18-MAR-16:00 | 145856.80 | 18-MAR-16:00 | 11873.83 | 09-MAR-12:00 | 41704.89 | 18-MAR-16:00 | 0.00 |
April | 0.106410E+12 | 0.299869E+11 | 671.57 | 0.974837E+11 | 0.892595E+10 | 0.00 | 1.00 | 01-APR-14:50 | 0.01 | 03-APR-01:07 | 387557.91 | 27-APR-15:00 | 387557.91 | 27-APR-15:00 | 83204.45 | 28-APR-13:00 | 111399.69 | 27-APR-15:10 | 0.00 |
May | 0.505115E+10 | 0.356545E+10 | 485.97 | 0.475764E+10 | 0.293511E+09 | 0.00 | 0.25 | 05-MAY-16:00 | 0.00 | 27-MAY-08:40 | 86272.19 | 05-MAY-16:00 | 74538.59 | 05-MAY-16:00 | 12501.07 | 06-MAY-13:00 | 24304.79 | 05-MAY-16:00 | 0.00 |
June | 0.414475E+11 | 0.135341E+11 | 384.50 | 0.392502E+11 | 0.219723E+10 | 0.00 | 0.58 | 28-JUN-17:00 | 0.01 | 18-JUN-08:13 | 209668.85 | 28-JUN-17:00 | 209668.85 | 28-JUN-17:00 | 18006.53 | 21-JUN-17:00 | 60852.89 | 28-JUN-17:00 | 0.00 |
July | 0.252053E+12 | 0.671653E+11 | 613.96 | 0.210174E+12 | 0.418794E+11 | 0.00 | 0.88 | 27-JUL-16:00 | 0.01 | 08-JUL-04:10 | 353290.67 | 27-JUL-16:00 | 312335.75 | 24-JUL-15:00 | 89189.01 | 15-JUL-18:11 | 98575.43 | 24-JUL-15:00 | 0.00 |
August | 0.629787E+12 | 0.159014E+12 | 735.47 | 0.486919E+12 | 0.142867E+12 | 0.00 | 1.00 | 07-AUG-11:30 | 0.01 | 31-AUG-23:25 | 411681.89 | 29-AUG-13:00 | 396533.60 | 08-AUG-17:20 | 185852.85 | 30-AUG-08:30 | 122244.66 | 10-AUG-17:00 | 0.00 |
September | 0.454809E+10 | 0.365125E+10 | 243.87 | 0.381794E+10 | 0.730145E+09 | 0.00 | 0.25 | 22-SEP-16:00 | 0.01 | 29-SEP-09:15 | 88436.61 | 22-SEP-16:00 | 75138.80 | 22-SEP-16:00 | 13420.51 | 15-SEP-16:00 | 24772.39 | 22-SEP-16:00 | 0.00 |
October | 0.451755E+10 | 0.335977E+10 | 501.86 | 0.437877E+10 | 0.138786E+09 | 0.00 | 0.28 | 04-OCT-15:00 | 0.01 | 08-OCT-19:10 | 86457.03 | 04-OCT-15:00 | 86457.03 | 04-OCT-15:00 | 6543.12 | 08-OCT-13:52 | 25424.70 | 04-OCT-15:00 | 0.00 |
November | 0.118086E+11 | 0.509134E+10 | 560.35 | 0.982669E+10 | 0.198192E+10 | 0.00 | 0.56 | 04-NOV-14:20 | 0.01 | 07-NOV-05:40 | 204532.90 | 04-NOV-14:20 | 153563.50 | 04-NOV-14:20 | 57596.15 | 04-NOV-16:00 | 51355.71 | 04-NOV-15:00 | 0.00 |
December | 0.140011E+11 | 0.602338E+10 | 723.91 | 0.128368E+11 | 0.116426E+10 | 0.00 | 0.19 | 14-DEC-12:00 | 0.01 | 16-DEC-05:14 | 52001.60 | 14-DEC-12:00 | 50551.00 | 14-DEC-12:00 | 2108.47 | 14-DEC-12:20 | 14574.85 | 14-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.109516E+13 | 0.304143E+12 | 6954.87 | 0.894185E+12 | 0.200972E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.434107E+10 | 0.317281E+10 | 243.87 | 0.381794E+10 | 105777.37 | 0.00 | 0.02 | 0.00 | 2990.67 | 2990.67 | 10.71 | 1516.81 | 0.00 | ||||||
Maximum of Months | 0.629787E+12 | 0.159014E+12 | 740.67 | 0.486919E+12 | 0.142867E+12 | 0.00 | 1.00 | 0.01 | 411681.89 | 396533.60 | 185852.85 | 122244.66 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.382204E+10 | 0.878113E+09 | 744.00 | 0.382170E+10 | 333149.34 | 0.00 | 0.27 | 08-JAN-16:15 | 0.11 | 07-JAN-08:00 | 2096.49 | 08-JAN-16:15 | 2096.49 | 08-JAN-16:15 | 15.81 | 02-JAN-07:10 | 478.83 | 08-JAN-16:15 | 0.00 |
February | 0.861254E+10 | 0.183190E+10 | 672.00 | 0.860210E+10 | 10441125.49 | 0.00 | 0.54 | 12-FEB-16:45 | 0.37 | 18-FEB-08:00 | 4406.38 | 12-FEB-16:45 | 4406.38 | 12-FEB-16:45 | 127.38 | 24-FEB-11:10 | 950.61 | 12-FEB-16:45 | 0.00 |
March | 0.151254E+11 | 0.305532E+10 | 744.00 | 0.151169E+11 | 8450938.97 | 0.00 | 0.82 | 31-MAR-24:00 | 0.57 | 01-MAR-07:10 | 7525.01 | 31-MAR-24:00 | 7525.01 | 31-MAR-24:00 | 136.63 | 09-MAR-17:00 | 1436.47 | 31-MAR-24:00 | 0.00 |
April | 0.198651E+11 | 0.388612E+10 | 720.00 | 0.198516E+11 | 13477071.62 | 0.00 | 1.00 | 01-APR-17:42 | 0.30 | 30-APR-24:00 | 8638.60 | 23-APR-18:20 | 8638.60 | 23-APR-18:20 | 163.25 | 28-APR-11:05 | 2365.27 | 01-APR-17:02 | 0.00 |
May | 0.545127E+10 | 0.119791E+10 | 744.00 | 0.541473E+10 | 36539456.59 | 0.00 | 0.45 | 31-MAY-24:00 | 0.17 | 18-MAY-06:10 | 3977.30 | 31-MAY-24:00 | 3968.98 | 31-MAY-24:00 | 132.47 | 05-MAY-16:10 | 802.50 | 31-MAY-24:00 | 0.00 |
June | 0.104138E+11 | 0.218379E+10 | 720.00 | 0.103603E+11 | 53452837.51 | 0.00 | 0.64 | 30-JUN-24:00 | 0.41 | 14-JUN-06:40 | 5861.17 | 30-JUN-24:00 | 5855.08 | 30-JUN-24:00 | 193.65 | 12-JUN-15:00 | 1222.98 | 28-JUN-17:00 | 0.00 |
July | 0.161619E+11 | 0.342368E+10 | 744.00 | 0.160461E+11 | 0.115756E+09 | 0.00 | 0.86 | 30-JUL-18:21 | 0.62 | 01-JUL-07:00 | 7827.94 | 31-JUL-23:55 | 7800.36 | 31-JUL-24:00 | 252.69 | 11-JUL-09:40 | 2018.16 | 30-JUL-18:01 | 0.00 |
August | 0.211707E+11 | 0.462147E+10 | 744.00 | 0.210147E+11 | 0.156016E+09 | 0.00 | 1.00 | 06-AUG-17:42 | 0.29 | 31-AUG-24:00 | 9187.18 | 06-AUG-19:06 | 9187.18 | 06-AUG-19:06 | 259.28 | 30-AUG-08:00 | 2652.15 | 10-AUG-17:30 | 0.00 |
September | 0.545766E+10 | 0.118555E+10 | 720.00 | 0.536696E+10 | 90701851.60 | 0.00 | 0.44 | 30-SEP-24:00 | 0.19 | 28-SEP-06:35 | 3854.65 | 30-SEP-24:00 | 3853.49 | 30-SEP-24:00 | 172.40 | 14-SEP-13:20 | 780.40 | 30-SEP-24:00 | 0.00 |
October | 0.102624E+11 | 0.210905E+10 | 744.00 | 0.102395E+11 | 22970353.92 | 0.00 | 0.62 | 31-OCT-24:00 | 0.39 | 28-OCT-07:00 | 5546.96 | 31-OCT-24:00 | 5546.96 | 31-OCT-24:00 | 135.20 | 26-OCT-14:10 | 1099.72 | 31-OCT-24:00 | 0.00 |
November | 0.145429E+11 | 0.289289E+10 | 720.00 | 0.145190E+11 | 23857608.73 | 0.00 | 0.71 | 11-NOV-15:55 | 0.59 | 24-NOV-07:20 | 6360.75 | 11-NOV-16:05 | 6360.75 | 11-NOV-16:05 | 165.14 | 03-NOV-16:00 | 1390.42 | 04-NOV-15:40 | 0.00 |
December | 0.198830E+11 | 0.388554E+10 | 744.00 | 0.198805E+11 | 2467874.92 | 0.00 | 0.91 | 03-DEC-15:25 | 0.77 | 18-DEC-07:10 | 8161.98 | 10-DEC-15:40 | 8161.98 | 10-DEC-15:40 | 85.60 | 28-DEC-15:00 | 1598.37 | 03-DEC-15:25 | 0.00 |
Annual Sum or Average | 0.150769E+12 | 0.311513E+11 | 8760.00 | 0.150234E+12 | 0.534464E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.382204E+10 | 0.878113E+09 | 672.00 | 0.382170E+10 | 333149.34 | 0.00 | 0.27 | 0.11 | 2096.49 | 2096.49 | 15.81 | 478.83 | 0.00 | ||||||
Maximum of Months | 0.211707E+11 | 0.462147E+10 | 744.00 | 0.210147E+11 | 0.156016E+09 | 0.00 | 1.00 | 0.77 | 9187.18 | 9187.18 | 259.28 | 2652.15 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.100180E+11 | 0.259140E+10 | 621.14 | 0.100180E+11 | -0.0 | 0.00 | 0.20 | 20-JAN-16:20 | 0.00 | 01-JAN-00:03 | 14535.71 | 20-JAN-16:20 | 14535.71 | 20-JAN-16:20 | 0.00 | 29-JAN-05:00 | 3311.48 | 20-JAN-16:20 | 0.00 |
February | 0.622184E+11 | 0.135476E+11 | 672.00 | 0.621170E+11 | 0.101464E+09 | 0.00 | 0.47 | 08-FEB-17:00 | 0.21 | 21-FEB-07:10 | 38845.44 | 27-FEB-16:30 | 38664.21 | 27-FEB-16:20 | 1220.57 | 24-FEB-11:20 | 8292.52 | 27-FEB-16:20 | 0.00 |
March | 0.130176E+12 | 0.266259E+11 | 744.00 | 0.130092E+12 | 84500018.40 | 0.00 | 0.76 | 31-MAR-23:40 | 0.48 | 06-MAR-07:10 | 66579.73 | 31-MAR-23:40 | 66579.73 | 31-MAR-23:40 | 1354.54 | 09-MAR-17:00 | 13114.64 | 18-MAR-17:03 | 0.00 |
April | 0.180730E+12 | 0.356328E+11 | 720.00 | 0.180593E+12 | 0.136128E+09 | 0.00 | 0.98 | 01-APR-17:42 | 0.22 | 30-APR-24:00 | 81712.53 | 26-APR-18:00 | 81712.53 | 26-APR-18:00 | 1627.68 | 28-APR-11:05 | 22122.74 | 01-APR-17:02 | 0.00 |
May | 0.459383E+11 | 0.102095E+11 | 744.00 | 0.455812E+11 | 0.357049E+09 | 0.00 | 0.44 | 31-MAY-23:40 | 0.11 | 18-MAY-06:30 | 37130.46 | 31-MAY-23:40 | 37016.16 | 31-MAY-23:50 | 1300.52 | 05-MAY-16:10 | 7510.63 | 31-MAY-23:40 | 0.00 |
June | 0.950486E+11 | 0.200471E+11 | 720.00 | 0.945196E+11 | 0.529070E+09 | 0.00 | 0.63 | 30-JUN-24:00 | 0.36 | 14-JUN-06:30 | 54989.40 | 30-JUN-24:00 | 54924.86 | 30-JUN-24:00 | 1922.31 | 12-JUN-15:00 | 11667.89 | 28-JUN-17:00 | 0.00 |
July | 0.151290E+12 | 0.321734E+11 | 744.00 | 0.150145E+12 | 0.114461E+10 | 0.00 | 0.85 | 31-JUL-23:15 | 0.59 | 18-JUL-06:10 | 75232.20 | 31-JUL-23:55 | 74963.63 | 31-JUL-24:00 | 2502.18 | 11-JUL-09:40 | 18987.20 | 30-JUL-18:11 | 0.00 |
August | 0.199819E+12 | 0.437601E+11 | 744.00 | 0.198270E+12 | 0.154893E+10 | 0.00 | 1.00 | 10-AUG-17:40 | 0.25 | 31-AUG-24:00 | 86695.44 | 06-AUG-18:32 | 86695.44 | 06-AUG-18:32 | 2583.18 | 30-AUG-08:00 | 25410.85 | 10-AUG-17:30 | 0.00 |
September | 0.469256E+11 | 0.102937E+11 | 720.00 | 0.460407E+11 | 0.884988E+09 | 0.00 | 0.42 | 30-SEP-23:40 | 0.13 | 28-SEP-06:55 | 34526.54 | 30-SEP-23:40 | 34505.47 | 30-SEP-23:50 | 1715.26 | 13-SEP-14:40 | 7036.16 | 30-SEP-23:40 | 0.00 |
October | 0.861219E+11 | 0.179196E+11 | 744.00 | 0.858949E+11 | 0.226974E+09 | 0.00 | 0.55 | 04-OCT-16:50 | 0.31 | 30-OCT-07:00 | 46125.06 | 31-OCT-24:00 | 46125.06 | 31-OCT-24:00 | 1319.20 | 26-OCT-14:10 | 10255.37 | 04-OCT-16:50 | 0.00 |
November | 0.119452E+12 | 0.241688E+11 | 720.00 | 0.119215E+12 | 0.237323E+09 | 0.00 | 0.67 | 04-NOV-16:00 | 0.47 | 24-NOV-07:10 | 57589.40 | 04-NOV-16:02 | 56450.26 | 04-NOV-16:02 | 1639.00 | 03-NOV-16:00 | 12827.66 | 04-NOV-15:50 | 0.00 |
December | 0.163760E+12 | 0.326485E+11 | 744.00 | 0.163735E+12 | 24881680.90 | 0.00 | 0.83 | 10-DEC-15:55 | 0.62 | 26-DEC-07:10 | 71668.56 | 05-DEC-15:50 | 71668.56 | 05-DEC-15:50 | 841.78 | 28-DEC-15:10 | 13940.43 | 10-DEC-15:55 | 0.00 |
Annual Sum or Average | 0.129150E+13 | 0.269618E+12 | 8637.14 | 0.128622E+13 | 0.527591E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.100180E+11 | 0.259140E+10 | 621.14 | 0.100180E+11 | -0.0 | 0.00 | 0.20 | 0.00 | 14535.71 | 14535.71 | 0.00 | 3311.48 | 0.00 | ||||||
Maximum of Months | 0.199819E+12 | 0.437601E+11 | 744.00 | 0.198270E+12 | 0.154893E+10 | 0.00 | 1.00 | 0.62 | 86695.44 | 86695.44 | 2583.18 | 25410.85 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.289428E+09 | 79386694.77 | 257.99 | 0.289428E+09 | -0.0 | 0.00 | 0.18 | 05-JAN-16:20 | 0.00 | 01-JAN-00:03 | 1367.30 | 05-JAN-16:20 | 1367.30 | 05-JAN-16:20 | 0.00 | 12-JAN-14:10 | 310.48 | 05-JAN-16:20 | 0.00 |
February | 0.471418E+10 | 0.104377E+10 | 671.86 | 0.470418E+10 | 10005288.33 | 0.00 | 0.46 | 27-FEB-16:30 | 0.00 | 19-FEB-04:55 | 3842.19 | 27-FEB-16:30 | 3818.78 | 27-FEB-16:20 | 120.91 | 24-FEB-11:30 | 821.30 | 27-FEB-16:20 | 0.00 |
March | 0.116540E+11 | 0.241321E+10 | 744.00 | 0.116456E+11 | 8359687.10 | 0.00 | 0.70 | 18-MAR-17:15 | 0.33 | 06-MAR-05:12 | 6144.25 | 31-MAR-23:20 | 6144.25 | 31-MAR-23:20 | 134.97 | 09-MAR-17:00 | 1292.28 | 18-MAR-17:03 | 0.00 |
April | 0.172721E+11 | 0.343328E+10 | 720.00 | 0.172585E+11 | 13554745.63 | 0.00 | 0.96 | 01-APR-17:42 | 0.16 | 30-APR-24:00 | 8251.96 | 26-APR-18:00 | 8251.96 | 26-APR-18:00 | 162.54 | 28-APR-11:05 | 2226.39 | 27-APR-16:00 | 0.00 |
May | 0.408982E+10 | 0.918911E+09 | 743.50 | 0.405436E+10 | 35459516.21 | 0.00 | 0.43 | 31-MAY-23:20 | 0.00 | 18-MAY-03:45 | 3642.32 | 31-MAY-23:20 | 3625.05 | 31-MAY-23:30 | 131.39 | 05-MAY-16:10 | 740.74 | 14-MAY-18:02 | 0.00 |
June | 0.928589E+10 | 0.196756E+10 | 720.00 | 0.923294E+10 | 52954034.07 | 0.00 | 0.61 | 30-JUN-23:40 | 0.30 | 14-JUN-06:20 | 5411.29 | 30-JUN-23:40 | 5404.76 | 30-JUN-23:40 | 192.30 | 12-JUN-15:00 | 1192.66 | 28-JUN-17:00 | 0.00 |
July | 0.150083E+11 | 0.320509E+10 | 744.00 | 0.148938E+11 | 0.114563E+09 | 0.00 | 0.86 | 30-JUL-18:31 | 0.55 | 18-JUL-06:10 | 7489.97 | 31-JUL-23:55 | 7463.71 | 31-JUL-23:50 | 249.92 | 11-JUL-09:40 | 1972.67 | 30-JUL-18:01 | 0.00 |
August | 0.198350E+11 | 0.436352E+10 | 744.00 | 0.196802E+11 | 0.154780E+09 | 0.00 | 1.00 | 06-AUG-18:11 | 0.23 | 31-AUG-24:00 | 8856.28 | 06-AUG-18:32 | 8856.28 | 06-AUG-18:32 | 257.46 | 30-AUG-08:00 | 2578.66 | 10-AUG-17:40 | 0.00 |
September | 0.417510E+10 | 0.926775E+09 | 720.00 | 0.408794E+10 | 87158018.78 | 0.00 | 0.38 | 10-SEP-17:22 | 0.06 | 27-SEP-06:40 | 3103.17 | 10-SEP-17:40 | 3089.02 | 10-SEP-17:40 | 174.56 | 14-SEP-13:20 | 717.11 | 10-SEP-17:22 | 0.00 |
October | 0.738463E+10 | 0.155762E+10 | 744.00 | 0.736244E+10 | 22191259.13 | 0.00 | 0.55 | 04-OCT-16:50 | 0.20 | 16-OCT-06:10 | 4499.85 | 04-OCT-16:50 | 4499.85 | 04-OCT-16:50 | 129.54 | 26-OCT-14:10 | 1032.81 | 04-OCT-16:50 | 0.00 |
November | 0.102901E+11 | 0.211467E+10 | 720.00 | 0.102666E+11 | 23463068.57 | 0.00 | 0.66 | 04-NOV-16:00 | 0.33 | 13-NOV-04:20 | 5672.25 | 04-NOV-16:02 | 5558.93 | 04-NOV-16:02 | 163.43 | 03-NOV-16:00 | 1267.65 | 04-NOV-15:50 | 0.00 |
December | 0.145540E+11 | 0.294606E+10 | 744.00 | 0.145515E+11 | 2463566.35 | 0.00 | 0.79 | 05-DEC-15:50 | 0.46 | 26-DEC-04:01 | 6974.84 | 05-DEC-16:10 | 6974.84 | 05-DEC-16:10 | 83.73 | 28-DEC-15:10 | 1361.39 | 05-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.118552E+12 | 0.249698E+11 | 8273.35 | 0.118027E+12 | 0.524953E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.289428E+09 | 79386694.77 | 257.99 | 0.289428E+09 | -0.0 | 0.00 | 0.18 | 0.00 | 1367.30 | 1367.30 | 0.00 | 310.48 | 0.00 | ||||||
Maximum of Months | 0.198350E+11 | 0.436352E+10 | 744.00 | 0.196802E+11 | 0.154780E+09 | 0.00 | 1.00 | 0.55 | 8856.28 | 8856.28 | 257.46 | 2578.66 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.32 | 0.00 | 85.32 | 0.90 | 618.83 | 0.00 | 0.00 | 0.00 |
February | 132.76 | 0.00 | 132.76 | 16.06 | 547.71 | 0.00 | 0.00 | 0.00 |
March | 195.60 | 0.00 | 195.60 | 65.40 | 446.03 | 0.00 | 0.00 | 0.00 |
April | 276.80 | 0.98 | 275.81 | 162.89 | 349.41 | 0.00 | 0.00 | 0.00 |
May | 356.17 | 10.58 | 345.59 | 279.76 | 267.61 | 0.00 | 0.00 | 0.00 |
June | 374.50 | 24.73 | 349.77 | 328.73 | 205.56 | 0.00 | 0.00 | 0.00 |
July | 355.94 | 27.91 | 328.04 | 354.64 | 184.71 | 0.00 | 0.00 | 0.00 |
August | 288.14 | 7.79 | 280.35 | 290.93 | 180.88 | 0.00 | 0.00 | 0.00 |
September | 223.82 | 0.07 | 223.75 | 164.62 | 274.56 | 0.00 | 0.00 | 0.00 |
October | 153.35 | 0.00 | 153.35 | 56.73 | 390.64 | 0.00 | 0.00 | 0.00 |
November | 96.60 | 0.00 | 96.60 | 7.25 | 516.75 | 0.00 | 0.00 | 0.00 |
December | 72.50 | 0.00 | 72.50 | 0.18 | 640.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 218.04 | 6.05 | 212.00 | 144.82 | 384.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.50 | 0.00 | 72.50 | 0.18 | 180.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.50 | 27.91 | 349.77 | 354.64 | 640.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.32 | 0.00 | 85.32 | 0.90 | 618.83 | 0.00 | 0.00 | 0.00 |
February | 132.76 | 0.00 | 132.76 | 16.06 | 547.71 | 0.00 | 0.00 | 0.00 |
March | 195.60 | 0.00 | 195.60 | 65.40 | 446.03 | 0.00 | 0.00 | 0.00 |
April | 276.80 | 0.98 | 275.81 | 162.89 | 349.41 | 0.00 | 0.00 | 0.00 |
May | 356.17 | 10.58 | 345.59 | 279.76 | 267.61 | 0.00 | 0.00 | 0.00 |
June | 374.50 | 24.73 | 349.77 | 328.73 | 205.56 | 0.00 | 0.00 | 0.00 |
July | 355.94 | 27.91 | 328.04 | 354.64 | 184.71 | 0.00 | 0.00 | 0.00 |
August | 288.14 | 7.79 | 280.35 | 290.93 | 180.88 | 0.00 | 0.00 | 0.00 |
September | 223.82 | 0.07 | 223.75 | 164.62 | 274.56 | 0.00 | 0.00 | 0.00 |
October | 153.35 | 0.00 | 153.35 | 56.73 | 390.64 | 0.00 | 0.00 | 0.00 |
November | 96.60 | 0.00 | 96.60 | 7.25 | 516.75 | 0.00 | 0.00 | 0.00 |
December | 72.50 | 0.00 | 72.50 | 0.18 | 640.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 218.04 | 6.05 | 212.00 | 144.82 | 384.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.50 | 0.00 | 72.50 | 0.18 | 180.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.50 | 27.91 | 349.77 | 354.64 | 640.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.32 | 0.00 | 85.32 | 0.90 | 618.83 | 0.00 | 0.00 | 0.00 |
February | 132.76 | 0.00 | 132.76 | 16.06 | 547.71 | 0.00 | 0.00 | 0.00 |
March | 195.60 | 0.00 | 195.60 | 65.40 | 446.03 | 0.00 | 0.00 | 0.00 |
April | 276.80 | 0.98 | 275.81 | 162.89 | 349.41 | 0.00 | 0.00 | 0.00 |
May | 356.17 | 10.58 | 345.59 | 279.76 | 267.61 | 0.00 | 0.00 | 0.00 |
June | 374.50 | 24.73 | 349.77 | 328.73 | 205.56 | 0.00 | 0.00 | 0.00 |
July | 355.94 | 27.91 | 328.04 | 354.64 | 184.71 | 0.00 | 0.00 | 0.00 |
August | 288.14 | 7.79 | 280.35 | 290.93 | 180.88 | 0.00 | 0.00 | 0.00 |
September | 223.82 | 0.07 | 223.75 | 164.62 | 274.56 | 0.00 | 0.00 | 0.00 |
October | 153.35 | 0.00 | 153.35 | 56.73 | 390.64 | 0.00 | 0.00 | 0.00 |
November | 96.60 | 0.00 | 96.60 | 7.25 | 516.75 | 0.00 | 0.00 | 0.00 |
December | 72.50 | 0.00 | 72.50 | 0.18 | 640.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 218.04 | 6.05 | 212.00 | 144.82 | 384.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.50 | 0.00 | 72.50 | 0.18 | 180.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.50 | 27.91 | 349.77 | 354.64 | 640.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.32 | 0.00 | 85.32 | 0.90 | 618.83 | 0.00 | 0.00 | 0.00 |
February | 132.76 | 0.00 | 132.76 | 16.06 | 547.71 | 0.00 | 0.00 | 0.00 |
March | 195.60 | 0.00 | 195.60 | 65.40 | 446.03 | 0.00 | 0.00 | 0.00 |
April | 276.80 | 0.98 | 275.81 | 162.89 | 349.41 | 0.00 | 0.00 | 0.00 |
May | 356.17 | 10.58 | 345.59 | 279.76 | 267.61 | 0.00 | 0.00 | 0.00 |
June | 374.50 | 24.73 | 349.77 | 328.73 | 205.56 | 0.00 | 0.00 | 0.00 |
July | 355.94 | 27.91 | 328.04 | 354.64 | 184.71 | 0.00 | 0.00 | 0.00 |
August | 288.14 | 7.79 | 280.35 | 290.93 | 180.88 | 0.00 | 0.00 | 0.00 |
September | 223.82 | 0.07 | 223.75 | 164.62 | 274.56 | 0.00 | 0.00 | 0.00 |
October | 153.35 | 0.00 | 153.35 | 56.73 | 390.64 | 0.00 | 0.00 | 0.00 |
November | 96.60 | 0.00 | 96.60 | 7.25 | 516.75 | 0.00 | 0.00 | 0.00 |
December | 72.50 | 0.00 | 72.50 | 0.18 | 640.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 218.04 | 6.05 | 212.00 | 144.82 | 384.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.50 | 0.00 | 72.50 | 0.18 | 180.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.50 | 27.91 | 349.77 | 354.64 | 640.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.32 | 0.00 | 85.32 | 0.90 | 618.81 | 0.00 | 0.00 | 0.00 |
February | 132.76 | 0.00 | 132.76 | 16.06 | 547.69 | 0.00 | 0.00 | 0.00 |
March | 195.59 | 0.00 | 195.59 | 65.40 | 446.01 | 0.00 | 0.00 | 0.00 |
April | 276.79 | 0.98 | 275.80 | 162.88 | 349.40 | 0.00 | 0.00 | 0.00 |
May | 356.15 | 10.58 | 345.57 | 279.75 | 267.60 | 0.00 | 0.00 | 0.00 |
June | 374.49 | 24.73 | 349.76 | 328.72 | 205.55 | 0.00 | 0.00 | 0.00 |
July | 355.93 | 27.91 | 328.02 | 354.63 | 184.70 | 0.00 | 0.00 | 0.00 |
August | 288.13 | 7.79 | 280.34 | 290.92 | 180.87 | 0.00 | 0.00 | 0.00 |
September | 223.81 | 0.07 | 223.74 | 164.62 | 274.55 | 0.00 | 0.00 | 0.00 |
October | 153.34 | 0.00 | 153.34 | 56.72 | 390.63 | 0.00 | 0.00 | 0.00 |
November | 96.59 | 0.00 | 96.59 | 7.25 | 516.73 | 0.00 | 0.00 | 0.00 |
December | 72.50 | 0.00 | 72.50 | 0.18 | 640.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 218.04 | 6.05 | 211.99 | 144.81 | 384.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.50 | 0.00 | 72.50 | 0.18 | 180.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.49 | 27.91 | 349.76 | 354.63 | 640.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.33 | 38.62 | 113.71 | 45.95 | 644.73 | 0.00 | 0.00 | 0.00 |
February | 279.51 | 99.20 | 180.31 | 163.23 | 559.60 | 0.00 | 0.00 | 0.00 |
March | 417.33 | 151.08 | 266.25 | 328.96 | 459.74 | 0.00 | 0.00 | 0.00 |
April | 646.93 | 268.81 | 378.12 | 640.03 | 360.35 | 0.00 | 0.00 | 0.00 |
May | 688.39 | 239.34 | 449.06 | 722.81 | 296.68 | 0.00 | 0.00 | 0.00 |
June | 824.43 | 358.72 | 465.71 | 937.69 | 229.87 | 0.00 | 0.00 | 0.00 |
July | 767.74 | 344.60 | 423.13 | 913.07 | 200.45 | 0.00 | 0.00 | 0.00 |
August | 754.58 | 377.48 | 377.09 | 929.67 | 193.47 | 0.00 | 0.00 | 0.00 |
September | 557.90 | 257.31 | 300.59 | 605.71 | 290.63 | 0.00 | 0.00 | 0.00 |
October | 363.64 | 154.51 | 209.13 | 316.76 | 407.40 | 0.00 | 0.00 | 0.00 |
November | 178.24 | 50.32 | 127.92 | 82.53 | 533.47 | 0.00 | 0.00 | 0.00 |
December | 146.19 | 47.06 | 99.13 | 59.43 | 656.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 482.32 | 199.36 | 282.96 | 480.46 | 401.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 146.19 | 38.62 | 99.13 | 45.95 | 193.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 824.43 | 377.48 | 465.71 | 937.69 | 656.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.33 | 38.62 | 113.71 | 45.95 | 644.73 | 0.00 | 0.00 | 0.00 |
February | 279.51 | 99.20 | 180.31 | 163.23 | 559.60 | 0.00 | 0.00 | 0.00 |
March | 417.33 | 151.08 | 266.25 | 328.96 | 459.74 | 0.00 | 0.00 | 0.00 |
April | 646.93 | 268.81 | 378.12 | 640.03 | 360.35 | 0.00 | 0.00 | 0.00 |
May | 688.39 | 239.34 | 449.06 | 722.81 | 296.68 | 0.00 | 0.00 | 0.00 |
June | 824.43 | 358.72 | 465.71 | 937.69 | 229.87 | 0.00 | 0.00 | 0.00 |
July | 767.74 | 344.60 | 423.13 | 913.07 | 200.45 | 0.00 | 0.00 | 0.00 |
August | 754.58 | 377.48 | 377.09 | 929.67 | 193.47 | 0.00 | 0.00 | 0.00 |
September | 557.90 | 257.31 | 300.59 | 605.71 | 290.63 | 0.00 | 0.00 | 0.00 |
October | 363.64 | 154.51 | 209.13 | 316.76 | 407.40 | 0.00 | 0.00 | 0.00 |
November | 178.24 | 50.32 | 127.92 | 82.53 | 533.47 | 0.00 | 0.00 | 0.00 |
December | 146.19 | 47.06 | 99.13 | 59.43 | 656.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 482.32 | 199.36 | 282.96 | 480.46 | 401.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 146.19 | 38.62 | 99.13 | 45.95 | 193.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 824.43 | 377.48 | 465.71 | 937.69 | 656.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.33 | 38.62 | 113.71 | 45.95 | 644.72 | 0.00 | 0.00 | 0.00 |
February | 279.51 | 99.20 | 180.30 | 163.23 | 559.59 | 0.00 | 0.00 | 0.00 |
March | 417.32 | 151.07 | 266.25 | 328.96 | 459.73 | 0.00 | 0.00 | 0.00 |
April | 646.92 | 268.81 | 378.12 | 640.02 | 360.35 | 0.00 | 0.00 | 0.00 |
May | 688.38 | 239.33 | 449.05 | 722.80 | 296.67 | 0.00 | 0.00 | 0.00 |
June | 824.41 | 358.71 | 465.71 | 937.68 | 229.86 | 0.00 | 0.00 | 0.00 |
July | 767.72 | 344.60 | 423.12 | 913.06 | 200.45 | 0.00 | 0.00 | 0.00 |
August | 754.56 | 377.48 | 377.09 | 929.66 | 193.47 | 0.00 | 0.00 | 0.00 |
September | 557.89 | 257.30 | 300.59 | 605.70 | 290.63 | 0.00 | 0.00 | 0.00 |
October | 363.63 | 154.51 | 209.12 | 316.76 | 407.39 | 0.00 | 0.00 | 0.00 |
November | 178.23 | 50.32 | 127.92 | 82.53 | 533.46 | 0.00 | 0.00 | 0.00 |
December | 146.19 | 47.06 | 99.13 | 59.43 | 656.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 482.31 | 199.36 | 282.96 | 480.45 | 401.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 146.19 | 38.62 | 99.13 | 45.95 | 193.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 824.41 | 377.48 | 465.71 | 937.68 | 656.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.97 | 223.85 | 153.12 | 322.19 | 526.67 | 0.00 | 0.00 | 0.00 |
February | 579.72 | 358.86 | 220.87 | 571.70 | 476.89 | 0.00 | 0.00 | 0.00 |
March | 623.62 | 332.57 | 291.05 | 649.94 | 419.08 | 0.00 | 0.00 | 0.00 |
April | 658.42 | 285.88 | 372.54 | 729.26 | 351.75 | 0.00 | 0.00 | 0.00 |
May | 602.04 | 179.35 | 422.69 | 677.79 | 284.71 | 0.00 | 0.00 | 0.00 |
June | 550.81 | 147.89 | 402.92 | 633.70 | 225.87 | 0.00 | 0.00 | 0.00 |
July | 600.68 | 220.00 | 380.68 | 764.34 | 204.36 | 0.00 | 0.00 | 0.00 |
August | 645.36 | 300.94 | 344.42 | 849.51 | 197.39 | 0.00 | 0.00 | 0.00 |
September | 715.03 | 394.86 | 320.17 | 882.14 | 275.50 | 0.00 | 0.00 | 0.00 |
October | 647.69 | 399.90 | 247.79 | 725.39 | 367.76 | 0.00 | 0.00 | 0.00 |
November | 382.94 | 219.46 | 163.48 | 351.59 | 452.93 | 0.00 | 0.00 | 0.00 |
December | 400.66 | 259.29 | 141.38 | 379.18 | 552.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 565.08 | 276.39 | 288.69 | 628.29 | 360.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.97 | 147.89 | 141.38 | 322.19 | 197.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 715.03 | 399.90 | 422.69 | 882.14 | 552.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.97 | 223.85 | 153.12 | 322.19 | 526.67 | 0.00 | 0.00 | 0.00 |
February | 579.72 | 358.86 | 220.87 | 571.69 | 476.89 | 0.00 | 0.00 | 0.00 |
March | 623.62 | 332.57 | 291.05 | 649.94 | 419.08 | 0.00 | 0.00 | 0.00 |
April | 658.42 | 285.88 | 372.54 | 729.26 | 351.75 | 0.00 | 0.00 | 0.00 |
May | 602.04 | 179.35 | 422.69 | 677.79 | 284.71 | 0.00 | 0.00 | 0.00 |
June | 550.81 | 147.89 | 402.92 | 633.69 | 225.87 | 0.00 | 0.00 | 0.00 |
July | 600.68 | 220.00 | 380.68 | 764.34 | 204.36 | 0.00 | 0.00 | 0.00 |
August | 645.36 | 300.94 | 344.42 | 849.51 | 197.39 | 0.00 | 0.00 | 0.00 |
September | 715.03 | 394.86 | 320.17 | 882.14 | 275.50 | 0.00 | 0.00 | 0.00 |
October | 647.69 | 399.90 | 247.79 | 725.39 | 367.76 | 0.00 | 0.00 | 0.00 |
November | 382.94 | 219.46 | 163.48 | 351.59 | 452.93 | 0.00 | 0.00 | 0.00 |
December | 400.66 | 259.28 | 141.38 | 379.18 | 552.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 565.08 | 276.39 | 288.69 | 628.29 | 360.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.97 | 147.89 | 141.38 | 322.19 | 197.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 715.03 | 399.90 | 422.69 | 882.14 | 552.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.97 | 223.85 | 153.12 | 322.19 | 526.67 | 0.00 | 0.00 | 0.00 |
February | 579.72 | 358.86 | 220.87 | 571.70 | 476.89 | 0.00 | 0.00 | 0.00 |
March | 623.62 | 332.57 | 291.05 | 649.94 | 419.08 | 0.00 | 0.00 | 0.00 |
April | 658.42 | 285.88 | 372.54 | 729.26 | 351.75 | 0.00 | 0.00 | 0.00 |
May | 602.04 | 179.35 | 422.69 | 677.79 | 284.71 | 0.00 | 0.00 | 0.00 |
June | 550.81 | 147.89 | 402.92 | 633.70 | 225.87 | 0.00 | 0.00 | 0.00 |
July | 600.68 | 220.00 | 380.68 | 764.34 | 204.36 | 0.00 | 0.00 | 0.00 |
August | 645.36 | 300.94 | 344.42 | 849.51 | 197.39 | 0.00 | 0.00 | 0.00 |
September | 715.03 | 394.86 | 320.17 | 882.14 | 275.50 | 0.00 | 0.00 | 0.00 |
October | 647.69 | 399.90 | 247.79 | 725.39 | 367.76 | 0.00 | 0.00 | 0.00 |
November | 382.94 | 219.46 | 163.48 | 351.59 | 452.93 | 0.00 | 0.00 | 0.00 |
December | 400.66 | 259.29 | 141.38 | 379.18 | 552.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 565.08 | 276.39 | 288.69 | 628.29 | 360.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.97 | 147.89 | 141.38 | 322.19 | 197.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 715.03 | 399.90 | 422.69 | 882.14 | 552.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.97 | 223.85 | 153.12 | 322.19 | 526.67 | 0.00 | 0.00 | 0.00 |
February | 579.72 | 358.86 | 220.87 | 571.69 | 476.89 | 0.00 | 0.00 | 0.00 |
March | 623.62 | 332.57 | 291.05 | 649.94 | 419.08 | 0.00 | 0.00 | 0.00 |
April | 658.42 | 285.88 | 372.54 | 729.26 | 351.75 | 0.00 | 0.00 | 0.00 |
May | 602.04 | 179.35 | 422.69 | 677.79 | 284.71 | 0.00 | 0.00 | 0.00 |
June | 550.81 | 147.89 | 402.92 | 633.69 | 225.87 | 0.00 | 0.00 | 0.00 |
July | 600.68 | 220.00 | 380.68 | 764.34 | 204.36 | 0.00 | 0.00 | 0.00 |
August | 645.36 | 300.94 | 344.42 | 849.51 | 197.39 | 0.00 | 0.00 | 0.00 |
September | 715.03 | 394.86 | 320.17 | 882.14 | 275.50 | 0.00 | 0.00 | 0.00 |
October | 647.69 | 399.90 | 247.79 | 725.39 | 367.76 | 0.00 | 0.00 | 0.00 |
November | 382.94 | 219.46 | 163.48 | 351.59 | 452.93 | 0.00 | 0.00 | 0.00 |
December | 400.66 | 259.28 | 141.38 | 379.18 | 552.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 565.08 | 276.39 | 288.69 | 628.29 | 360.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.97 | 147.89 | 141.38 | 322.19 | 197.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 715.03 | 399.90 | 422.69 | 882.14 | 552.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.96 | 223.84 | 153.12 | 322.18 | 526.65 | 0.00 | 0.00 | 0.00 |
February | 579.70 | 358.84 | 220.86 | 571.67 | 476.87 | 0.00 | 0.00 | 0.00 |
March | 623.59 | 332.55 | 291.04 | 649.92 | 419.07 | 0.00 | 0.00 | 0.00 |
April | 658.39 | 285.87 | 372.52 | 729.23 | 351.73 | 0.00 | 0.00 | 0.00 |
May | 602.02 | 179.35 | 422.67 | 677.77 | 284.69 | 0.00 | 0.00 | 0.00 |
June | 550.79 | 147.88 | 402.91 | 633.67 | 225.86 | 0.00 | 0.00 | 0.00 |
July | 600.66 | 219.99 | 380.66 | 764.31 | 204.35 | 0.00 | 0.00 | 0.00 |
August | 645.33 | 300.93 | 344.40 | 849.48 | 197.38 | 0.00 | 0.00 | 0.00 |
September | 715.00 | 394.85 | 320.15 | 882.10 | 275.49 | 0.00 | 0.00 | 0.00 |
October | 647.67 | 399.89 | 247.78 | 725.36 | 367.75 | 0.00 | 0.00 | 0.00 |
November | 382.92 | 219.45 | 163.48 | 351.58 | 452.91 | 0.00 | 0.00 | 0.00 |
December | 400.65 | 259.27 | 141.37 | 379.17 | 552.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 565.06 | 276.38 | 288.68 | 628.27 | 360.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.96 | 147.88 | 141.37 | 322.18 | 197.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 715.00 | 399.89 | 422.67 | 882.10 | 552.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.67 | 47.38 | 113.29 | 57.55 | 698.71 | 0.00 | 0.00 | 0.00 |
February | 288.07 | 108.27 | 179.81 | 177.28 | 632.36 | 0.00 | 0.00 | 0.00 |
March | 403.66 | 136.25 | 267.41 | 307.31 | 535.02 | 0.00 | 0.00 | 0.00 |
April | 614.13 | 234.80 | 379.32 | 581.78 | 439.55 | 0.00 | 0.00 | 0.00 |
May | 790.24 | 321.03 | 469.21 | 853.02 | 335.37 | 0.00 | 0.00 | 0.00 |
June | 759.99 | 295.08 | 464.91 | 836.46 | 272.54 | 0.00 | 0.00 | 0.00 |
July | 938.87 | 493.52 | 445.35 | 1138.28 | 256.80 | 0.00 | 0.00 | 0.00 |
August | 776.67 | 396.59 | 380.08 | 949.70 | 256.57 | 0.00 | 0.00 | 0.00 |
September | 632.48 | 303.48 | 329.00 | 714.45 | 332.88 | 0.00 | 0.00 | 0.00 |
October | 360.07 | 146.71 | 213.36 | 308.88 | 469.86 | 0.00 | 0.00 | 0.00 |
November | 179.31 | 50.57 | 128.74 | 80.70 | 615.69 | 0.00 | 0.00 | 0.00 |
December | 150.75 | 51.66 | 99.09 | 68.57 | 771.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 505.90 | 216.26 | 289.63 | 508.35 | 467.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 150.75 | 47.38 | 99.09 | 57.55 | 256.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 938.87 | 493.52 | 469.21 | 1138.28 | 771.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.67 | 47.38 | 113.29 | 57.55 | 698.71 | 0.00 | 0.00 | 0.00 |
February | 288.07 | 108.27 | 179.81 | 177.28 | 632.36 | 0.00 | 0.00 | 0.00 |
March | 403.66 | 136.25 | 267.41 | 307.31 | 535.02 | 0.00 | 0.00 | 0.00 |
April | 614.13 | 234.80 | 379.32 | 581.78 | 439.55 | 0.00 | 0.00 | 0.00 |
May | 790.24 | 321.03 | 469.21 | 853.02 | 335.37 | 0.00 | 0.00 | 0.00 |
June | 759.99 | 295.08 | 464.91 | 836.46 | 272.54 | 0.00 | 0.00 | 0.00 |
July | 938.87 | 493.52 | 445.35 | 1138.28 | 256.80 | 0.00 | 0.00 | 0.00 |
August | 776.67 | 396.59 | 380.08 | 949.70 | 256.57 | 0.00 | 0.00 | 0.00 |
September | 632.48 | 303.48 | 329.00 | 714.45 | 332.88 | 0.00 | 0.00 | 0.00 |
October | 360.07 | 146.71 | 213.36 | 308.88 | 469.86 | 0.00 | 0.00 | 0.00 |
November | 179.31 | 50.57 | 128.74 | 80.70 | 615.69 | 0.00 | 0.00 | 0.00 |
December | 150.75 | 51.66 | 99.09 | 68.57 | 771.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 505.90 | 216.26 | 289.63 | 508.35 | 467.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 150.75 | 47.38 | 99.09 | 57.55 | 256.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 938.87 | 493.52 | 469.21 | 1138.28 | 771.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.67 | 47.38 | 113.29 | 57.55 | 698.70 | 0.00 | 0.00 | 0.00 |
February | 288.07 | 108.26 | 179.80 | 177.27 | 632.35 | 0.00 | 0.00 | 0.00 |
March | 403.65 | 136.24 | 267.41 | 307.30 | 535.02 | 0.00 | 0.00 | 0.00 |
April | 614.12 | 234.80 | 379.32 | 581.77 | 439.55 | 0.00 | 0.00 | 0.00 |
May | 790.22 | 321.03 | 469.20 | 853.01 | 335.37 | 0.00 | 0.00 | 0.00 |
June | 759.98 | 295.07 | 464.90 | 836.44 | 272.53 | 0.00 | 0.00 | 0.00 |
July | 938.85 | 493.51 | 445.34 | 1138.25 | 256.80 | 0.00 | 0.00 | 0.00 |
August | 776.65 | 396.58 | 380.07 | 949.68 | 256.57 | 0.00 | 0.00 | 0.00 |
September | 632.47 | 303.47 | 329.00 | 714.44 | 332.88 | 0.00 | 0.00 | 0.00 |
October | 360.07 | 146.71 | 213.36 | 308.88 | 469.86 | 0.00 | 0.00 | 0.00 |
November | 179.31 | 50.57 | 128.74 | 80.70 | 615.68 | 0.00 | 0.00 | 0.00 |
December | 150.74 | 51.66 | 99.09 | 68.57 | 771.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 505.89 | 216.26 | 289.63 | 508.34 | 467.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 150.74 | 47.38 | 99.09 | 57.55 | 256.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 938.85 | 493.51 | 469.20 | 1138.25 | 771.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 426.60 | 0.00 | 426.60 | 14.66 | 2612.79 | 0.00 | 0.00 | 0.00 |
February | 663.80 | 0.00 | 663.80 | 128.11 | 2336.48 | 0.00 | 0.00 | 0.00 |
March | 978.00 | 0.00 | 978.00 | 399.42 | 1941.35 | 0.00 | 0.00 | 0.00 |
April | 1383.97 | 4.91 | 1379.06 | 889.90 | 1546.03 | 0.00 | 0.00 | 0.00 |
May | 1780.82 | 52.91 | 1727.91 | 1435.76 | 1253.46 | 0.00 | 0.00 | 0.00 |
June | 1872.49 | 123.65 | 1748.83 | 1672.09 | 964.80 | 0.00 | 0.00 | 0.00 |
July | 1779.69 | 139.54 | 1640.16 | 1806.35 | 863.87 | 0.00 | 0.00 | 0.00 |
August | 1440.68 | 38.95 | 1401.73 | 1488.70 | 846.90 | 0.00 | 0.00 | 0.00 |
September | 1119.07 | 0.33 | 1118.74 | 852.02 | 1276.56 | 0.00 | 0.00 | 0.00 |
October | 766.75 | 0.00 | 766.75 | 341.12 | 1708.36 | 0.00 | 0.00 | 0.00 |
November | 482.97 | 0.00 | 482.97 | 64.02 | 2155.75 | 0.00 | 0.00 | 0.00 |
December | 362.50 | 0.00 | 362.50 | 6.82 | 2658.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1090.21 | 30.25 | 1059.96 | 762.21 | 1677.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 362.50 | 0.00 | 362.50 | 6.82 | 846.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1872.49 | 139.54 | 1748.83 | 1806.35 | 2658.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.99 | 115.86 | 341.13 | 158.99 | 1657.29 | 0.00 | 0.00 | 0.00 |
February | 838.53 | 297.61 | 540.92 | 528.80 | 1489.90 | 0.00 | 0.00 | 0.00 |
March | 1251.98 | 453.23 | 798.75 | 1005.56 | 1260.36 | 0.00 | 0.00 | 0.00 |
April | 1940.78 | 806.42 | 1134.36 | 1924.23 | 1012.01 | 0.00 | 0.00 | 0.00 |
May | 2065.16 | 718.01 | 1347.15 | 2160.63 | 853.10 | 0.00 | 0.00 | 0.00 |
June | 2473.26 | 1076.14 | 1397.13 | 2790.96 | 669.34 | 0.00 | 0.00 | 0.00 |
July | 2303.18 | 1033.80 | 1269.38 | 2720.86 | 586.47 | 0.00 | 0.00 | 0.00 |
August | 2263.71 | 1132.44 | 1131.27 | 2766.69 | 575.59 | 0.00 | 0.00 | 0.00 |
September | 1673.68 | 771.92 | 901.76 | 1810.26 | 835.74 | 0.00 | 0.00 | 0.00 |
October | 1090.90 | 463.53 | 627.37 | 966.26 | 1117.39 | 0.00 | 0.00 | 0.00 |
November | 534.70 | 150.95 | 383.75 | 270.32 | 1397.71 | 0.00 | 0.00 | 0.00 |
December | 438.57 | 141.19 | 297.38 | 198.51 | 1707.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1446.95 | 598.07 | 848.88 | 1446.52 | 1094.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 438.57 | 115.86 | 297.38 | 158.99 | 575.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2473.26 | 1132.44 | 1397.13 | 2790.96 | 1707.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1884.84 | 1119.22 | 765.61 | 1638.47 | 2416.94 | 0.00 | 0.00 | 0.00 |
February | 2898.59 | 1794.27 | 1104.32 | 2880.43 | 2237.79 | 0.00 | 0.00 | 0.00 |
March | 3118.04 | 1662.82 | 1455.23 | 3249.64 | 1977.42 | 0.00 | 0.00 | 0.00 |
April | 3292.06 | 1429.40 | 1862.67 | 3642.30 | 1664.65 | 0.00 | 0.00 | 0.00 |
May | 3010.17 | 896.76 | 2113.41 | 3369.44 | 1381.27 | 0.00 | 0.00 | 0.00 |
June | 2754.01 | 739.42 | 2014.59 | 3154.38 | 1087.41 | 0.00 | 0.00 | 0.00 |
July | 3003.37 | 1099.99 | 1903.38 | 3808.07 | 982.16 | 0.00 | 0.00 | 0.00 |
August | 3226.74 | 1504.68 | 1722.06 | 4232.58 | 956.04 | 0.00 | 0.00 | 0.00 |
September | 3575.10 | 1974.29 | 1600.81 | 4390.49 | 1348.08 | 0.00 | 0.00 | 0.00 |
October | 3238.43 | 1999.49 | 1238.94 | 3615.55 | 1753.81 | 0.00 | 0.00 | 0.00 |
November | 1914.67 | 1097.27 | 817.40 | 1781.48 | 2089.37 | 0.00 | 0.00 | 0.00 |
December | 2003.29 | 1296.41 | 706.88 | 1923.30 | 2522.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2825.39 | 1381.95 | 1443.44 | 3141.53 | 1698.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1884.84 | 739.42 | 706.88 | 1638.47 | 956.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3575.10 | 1999.49 | 2113.41 | 4390.49 | 2522.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.01 | 142.14 | 339.87 | 196.76 | 1726.25 | 0.00 | 0.00 | 0.00 |
February | 864.20 | 324.79 | 539.41 | 584.59 | 1556.40 | 0.00 | 0.00 | 0.00 |
March | 1210.97 | 408.74 | 802.24 | 979.22 | 1331.26 | 0.00 | 0.00 | 0.00 |
April | 1842.36 | 704.41 | 1137.96 | 1812.05 | 1108.12 | 0.00 | 0.00 | 0.00 |
May | 2370.69 | 963.08 | 1407.61 | 2572.06 | 929.24 | 0.00 | 0.00 | 0.00 |
June | 2279.96 | 885.23 | 1394.72 | 2533.63 | 732.51 | 0.00 | 0.00 | 0.00 |
July | 2816.58 | 1480.54 | 1336.04 | 3441.89 | 680.86 | 0.00 | 0.00 | 0.00 |
August | 2329.98 | 1189.76 | 1140.23 | 2888.89 | 663.88 | 0.00 | 0.00 | 0.00 |
September | 1897.41 | 910.42 | 986.99 | 2157.69 | 917.64 | 0.00 | 0.00 | 0.00 |
October | 1080.20 | 440.13 | 640.07 | 969.64 | 1192.43 | 0.00 | 0.00 | 0.00 |
November | 537.94 | 151.72 | 386.21 | 281.09 | 1452.29 | 0.00 | 0.00 | 0.00 |
December | 452.24 | 154.97 | 297.27 | 234.69 | 1785.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1517.67 | 648.79 | 868.89 | 1560.77 | 1171.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 452.24 | 142.14 | 297.27 | 196.76 | 663.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2816.58 | 1480.54 | 1407.61 | 3441.89 | 1785.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 426.60 | 0.00 | 426.60 | 21.63 | 2451.76 | 0.00 | 0.00 | 0.00 |
February | 663.80 | 0.00 | 663.80 | 152.03 | 2158.19 | 0.00 | 0.00 | 0.00 |
March | 978.00 | 0.00 | 978.00 | 446.15 | 1772.61 | 0.00 | 0.00 | 0.00 |
April | 1383.97 | 4.91 | 1379.06 | 931.58 | 1442.99 | 0.00 | 0.00 | 0.00 |
May | 1780.82 | 52.91 | 1727.91 | 1463.19 | 1191.61 | 0.00 | 0.00 | 0.00 |
June | 1872.49 | 123.65 | 1748.83 | 1677.70 | 935.82 | 0.00 | 0.00 | 0.00 |
July | 1779.69 | 139.54 | 1640.16 | 1801.55 | 844.93 | 0.00 | 0.00 | 0.00 |
August | 1440.68 | 38.95 | 1401.73 | 1489.76 | 823.30 | 0.00 | 0.00 | 0.00 |
September | 1119.07 | 0.33 | 1118.74 | 877.13 | 1198.34 | 0.00 | 0.00 | 0.00 |
October | 766.75 | 0.00 | 766.75 | 388.46 | 1540.82 | 0.00 | 0.00 | 0.00 |
November | 482.97 | 0.00 | 482.97 | 86.02 | 1931.35 | 0.00 | 0.00 | 0.00 |
December | 362.50 | 0.00 | 362.50 | 14.03 | 2438.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1090.21 | 30.25 | 1059.96 | 783.01 | 1557.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 362.50 | 0.00 | 362.50 | 14.03 | 823.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1872.49 | 139.54 | 1748.83 | 1801.55 | 2451.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.99 | 115.86 | 341.13 | 171.23 | 1555.54 | 0.00 | 0.00 | 0.00 |
February | 838.53 | 297.61 | 540.92 | 560.70 | 1370.55 | 0.00 | 0.00 | 0.00 |
March | 1251.98 | 453.23 | 798.75 | 1046.75 | 1151.76 | 0.00 | 0.00 | 0.00 |
April | 1940.78 | 806.42 | 1134.36 | 1954.53 | 950.04 | 0.00 | 0.00 | 0.00 |
May | 2065.16 | 718.01 | 1347.15 | 2178.65 | 814.63 | 0.00 | 0.00 | 0.00 |
June | 2473.26 | 1076.14 | 1397.13 | 2793.77 | 651.41 | 0.00 | 0.00 | 0.00 |
July | 2303.18 | 1033.80 | 1269.38 | 2721.23 | 575.44 | 0.00 | 0.00 | 0.00 |
August | 2263.71 | 1132.44 | 1131.27 | 2768.71 | 561.56 | 0.00 | 0.00 | 0.00 |
September | 1673.68 | 771.92 | 901.76 | 1829.07 | 789.10 | 0.00 | 0.00 | 0.00 |
October | 1090.90 | 463.53 | 627.37 | 1003.76 | 1012.84 | 0.00 | 0.00 | 0.00 |
November | 534.70 | 150.95 | 383.75 | 297.50 | 1250.14 | 0.00 | 0.00 | 0.00 |
December | 438.57 | 141.19 | 297.38 | 215.65 | 1564.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1446.95 | 598.07 | 848.88 | 1466.39 | 1019.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 438.57 | 115.86 | 297.38 | 171.23 | 561.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2473.26 | 1132.44 | 1397.13 | 2793.77 | 1564.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1884.84 | 1119.22 | 765.61 | 1673.27 | 2253.45 | 0.00 | 0.00 | 0.00 |
February | 2898.59 | 1794.27 | 1104.32 | 2933.63 | 2063.49 | 0.00 | 0.00 | 0.00 |
March | 3118.04 | 1662.82 | 1455.23 | 3290.62 | 1817.28 | 0.00 | 0.00 | 0.00 |
April | 3292.06 | 1429.40 | 1862.67 | 3669.97 | 1566.85 | 0.00 | 0.00 | 0.00 |
May | 3010.17 | 896.76 | 2113.41 | 3382.37 | 1317.58 | 0.00 | 0.00 | 0.00 |
June | 2754.01 | 739.42 | 2014.59 | 3150.31 | 1054.80 | 0.00 | 0.00 | 0.00 |
July | 3003.37 | 1099.99 | 1903.38 | 3797.03 | 961.72 | 0.00 | 0.00 | 0.00 |
August | 3226.74 | 1504.68 | 1722.06 | 4224.34 | 931.63 | 0.00 | 0.00 | 0.00 |
September | 3575.10 | 1974.29 | 1600.81 | 4404.73 | 1278.85 | 0.00 | 0.00 | 0.00 |
October | 3238.43 | 1999.49 | 1238.94 | 3655.93 | 1605.70 | 0.00 | 0.00 | 0.00 |
November | 1914.67 | 1097.27 | 817.40 | 1830.60 | 1885.59 | 0.00 | 0.00 | 0.00 |
December | 2003.29 | 1296.41 | 706.88 | 1961.65 | 2314.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2825.39 | 1381.95 | 1443.44 | 3165.35 | 1585.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1884.84 | 739.42 | 706.88 | 1673.27 | 931.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3575.10 | 1999.49 | 2113.41 | 4404.73 | 2314.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.01 | 142.14 | 339.87 | 206.04 | 1620.89 | 0.00 | 0.00 | 0.00 |
February | 864.20 | 324.79 | 539.41 | 603.64 | 1452.28 | 0.00 | 0.00 | 0.00 |
March | 1210.97 | 408.74 | 802.24 | 1003.69 | 1234.41 | 0.00 | 0.00 | 0.00 |
April | 1842.36 | 704.41 | 1137.96 | 1829.97 | 1048.12 | 0.00 | 0.00 | 0.00 |
May | 2370.69 | 963.08 | 1407.61 | 2577.09 | 890.62 | 0.00 | 0.00 | 0.00 |
June | 2279.96 | 885.23 | 1394.72 | 2527.85 | 711.60 | 0.00 | 0.00 | 0.00 |
July | 2816.58 | 1480.54 | 1336.04 | 3430.55 | 666.32 | 0.00 | 0.00 | 0.00 |
August | 2329.98 | 1189.76 | 1140.23 | 2881.32 | 648.21 | 0.00 | 0.00 | 0.00 |
September | 1897.41 | 910.42 | 986.99 | 2164.42 | 874.93 | 0.00 | 0.00 | 0.00 |
October | 1080.20 | 440.13 | 640.07 | 993.68 | 1098.11 | 0.00 | 0.00 | 0.00 |
November | 537.94 | 151.72 | 386.21 | 298.61 | 1328.32 | 0.00 | 0.00 | 0.00 |
December | 452.24 | 154.97 | 297.27 | 244.22 | 1659.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1517.67 | 648.79 | 868.89 | 1569.76 | 1101.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 452.24 | 142.14 | 297.27 | 206.04 | 648.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2816.58 | 1480.54 | 1407.61 | 3430.55 | 1659.26 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228522E+09 | 0.00 | 0.228522E+09 | 2407828.13 | 0.165747E+10 |
February | 0.321175E+09 | 0.00 | 0.321175E+09 | 38849700.97 | 0.132503E+10 |
March | 0.523901E+09 | 0.00 | 0.523901E+09 | 0.175169E+09 | 0.119463E+10 |
April | 0.717457E+09 | 2545038.93 | 0.714912E+09 | 0.422211E+09 | 0.905671E+09 |
May | 0.953960E+09 | 28340757.90 | 0.925619E+09 | 0.749310E+09 | 0.716759E+09 |
June | 0.970708E+09 | 64101511.40 | 0.906607E+09 | 0.852079E+09 | 0.532813E+09 |
July | 0.953358E+09 | 74747816.12 | 0.878611E+09 | 0.949875E+09 | 0.494733E+09 |
August | 0.771750E+09 | 20862733.60 | 0.750888E+09 | 0.779219E+09 | 0.484468E+09 |
September | 0.580131E+09 | 171071.71 | 0.579959E+09 | 0.426702E+09 | 0.711656E+09 |
October | 0.410735E+09 | 0.00 | 0.410735E+09 | 0.151938E+09 | 0.104629E+10 |
November | 0.250377E+09 | 0.00 | 0.250377E+09 | 18794052.80 | 0.133941E+10 |
December | 0.194185E+09 | 0.00 | 0.194185E+09 | 481805.93 | 0.171673E+10 |
Annual Sum or Average | 0.687626E+10 | 0.190769E+09 | 0.668549E+10 | 0.456704E+10 | 0.121257E+11 |
Minimum of Months | 0.194185E+09 | 0.00 | 0.194185E+09 | 481805.93 | 0.484468E+09 |
Maximum of Months | 0.970708E+09 | 74747816.12 | 0.925619E+09 | 0.949875E+09 | 0.171673E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228522E+09 | 0.00 | 0.228522E+09 | 2407807.83 | 0.165747E+10 |
February | 0.321174E+09 | 0.00 | 0.321174E+09 | 38849575.08 | 0.132503E+10 |
March | 0.523900E+09 | 0.00 | 0.523900E+09 | 0.175168E+09 | 0.119463E+10 |
April | 0.717457E+09 | 2545035.87 | 0.714911E+09 | 0.422210E+09 | 0.905671E+09 |
May | 0.953959E+09 | 28340723.90 | 0.925618E+09 | 0.749309E+09 | 0.716759E+09 |
June | 0.970707E+09 | 64101434.48 | 0.906606E+09 | 0.852078E+09 | 0.532813E+09 |
July | 0.953358E+09 | 74747726.43 | 0.878610E+09 | 0.949874E+09 | 0.494733E+09 |
August | 0.771750E+09 | 20862708.56 | 0.750887E+09 | 0.779219E+09 | 0.484468E+09 |
September | 0.580130E+09 | 171071.50 | 0.579959E+09 | 0.426701E+09 | 0.711656E+09 |
October | 0.410735E+09 | 0.00 | 0.410735E+09 | 0.151938E+09 | 0.104629E+10 |
November | 0.250377E+09 | 0.00 | 0.250377E+09 | 18793984.92 | 0.133941E+10 |
December | 0.194185E+09 | 0.00 | 0.194185E+09 | 481801.18 | 0.171673E+10 |
Annual Sum or Average | 0.687625E+10 | 0.190769E+09 | 0.668549E+10 | 0.456703E+10 | 0.121257E+11 |
Minimum of Months | 0.194185E+09 | 0.00 | 0.194185E+09 | 481801.18 | 0.484468E+09 |
Maximum of Months | 0.970707E+09 | 74747726.43 | 0.925618E+09 | 0.949874E+09 | 0.171673E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228522E+09 | 0.00 | 0.228522E+09 | 2407828.13 | 0.165747E+10 |
February | 0.321175E+09 | 0.00 | 0.321175E+09 | 38849700.97 | 0.132503E+10 |
March | 0.523901E+09 | 0.00 | 0.523901E+09 | 0.175169E+09 | 0.119463E+10 |
April | 0.717457E+09 | 2545038.93 | 0.714912E+09 | 0.422211E+09 | 0.905671E+09 |
May | 0.953960E+09 | 28340757.90 | 0.925619E+09 | 0.749310E+09 | 0.716759E+09 |
June | 0.970708E+09 | 64101511.40 | 0.906607E+09 | 0.852079E+09 | 0.532813E+09 |
July | 0.953358E+09 | 74747816.12 | 0.878611E+09 | 0.949875E+09 | 0.494733E+09 |
August | 0.771750E+09 | 20862733.60 | 0.750888E+09 | 0.779219E+09 | 0.484468E+09 |
September | 0.580131E+09 | 171071.71 | 0.579959E+09 | 0.426702E+09 | 0.711656E+09 |
October | 0.410735E+09 | 0.00 | 0.410735E+09 | 0.151938E+09 | 0.104629E+10 |
November | 0.250377E+09 | 0.00 | 0.250377E+09 | 18794052.80 | 0.133941E+10 |
December | 0.194185E+09 | 0.00 | 0.194185E+09 | 481805.93 | 0.171673E+10 |
Annual Sum or Average | 0.687626E+10 | 0.190769E+09 | 0.668549E+10 | 0.456704E+10 | 0.121257E+11 |
Minimum of Months | 0.194185E+09 | 0.00 | 0.194185E+09 | 481805.93 | 0.484468E+09 |
Maximum of Months | 0.970708E+09 | 74747816.12 | 0.925619E+09 | 0.949875E+09 | 0.171673E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228522E+09 | 0.00 | 0.228522E+09 | 2407807.83 | 0.165747E+10 |
February | 0.321174E+09 | 0.00 | 0.321174E+09 | 38849575.08 | 0.132503E+10 |
March | 0.523900E+09 | 0.00 | 0.523900E+09 | 0.175168E+09 | 0.119463E+10 |
April | 0.717457E+09 | 2545035.87 | 0.714911E+09 | 0.422210E+09 | 0.905671E+09 |
May | 0.953959E+09 | 28340723.90 | 0.925618E+09 | 0.749309E+09 | 0.716759E+09 |
June | 0.970707E+09 | 64101434.48 | 0.906606E+09 | 0.852078E+09 | 0.532813E+09 |
July | 0.953358E+09 | 74747726.43 | 0.878610E+09 | 0.949874E+09 | 0.494733E+09 |
August | 0.771750E+09 | 20862708.56 | 0.750887E+09 | 0.779219E+09 | 0.484468E+09 |
September | 0.580130E+09 | 171071.50 | 0.579959E+09 | 0.426701E+09 | 0.711656E+09 |
October | 0.410735E+09 | 0.00 | 0.410735E+09 | 0.151938E+09 | 0.104629E+10 |
November | 0.250377E+09 | 0.00 | 0.250377E+09 | 18793984.92 | 0.133941E+10 |
December | 0.194185E+09 | 0.00 | 0.194185E+09 | 481801.18 | 0.171673E+10 |
Annual Sum or Average | 0.687625E+10 | 0.190769E+09 | 0.668549E+10 | 0.456703E+10 | 0.121257E+11 |
Minimum of Months | 0.194185E+09 | 0.00 | 0.194185E+09 | 481801.18 | 0.484468E+09 |
Maximum of Months | 0.970707E+09 | 74747726.43 | 0.925618E+09 | 0.949874E+09 | 0.171673E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228513E+09 | 0.00 | 0.228513E+09 | 2407731.08 | 0.165741E+10 |
February | 0.321162E+09 | 0.00 | 0.321162E+09 | 38848135.15 | 0.132497E+10 |
March | 0.523879E+09 | 0.00 | 0.523879E+09 | 0.175162E+09 | 0.119459E+10 |
April | 0.717428E+09 | 2544936.35 | 0.714883E+09 | 0.422194E+09 | 0.905635E+09 |
May | 0.953921E+09 | 28339615.65 | 0.925582E+09 | 0.749280E+09 | 0.716730E+09 |
June | 0.970669E+09 | 64098927.82 | 0.906570E+09 | 0.852045E+09 | 0.532792E+09 |
July | 0.953320E+09 | 74744803.46 | 0.878575E+09 | 0.949836E+09 | 0.494713E+09 |
August | 0.771719E+09 | 20861892.74 | 0.750857E+09 | 0.779188E+09 | 0.484449E+09 |
September | 0.580107E+09 | 171064.81 | 0.579936E+09 | 0.426684E+09 | 0.711627E+09 |
October | 0.410719E+09 | 0.00 | 0.410719E+09 | 0.151932E+09 | 0.104625E+10 |
November | 0.250367E+09 | 0.00 | 0.250367E+09 | 18793295.32 | 0.133936E+10 |
December | 0.194177E+09 | 0.00 | 0.194177E+09 | 481786.51 | 0.171666E+10 |
Annual Sum or Average | 0.687598E+10 | 0.190761E+09 | 0.668522E+10 | 0.456685E+10 | 0.121252E+11 |
Minimum of Months | 0.194177E+09 | 0.00 | 0.194177E+09 | 481786.51 | 0.484449E+09 |
Maximum of Months | 0.970669E+09 | 74744803.46 | 0.925582E+09 | 0.949836E+09 | 0.171666E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.408002E+09 | 0.103442E+09 | 0.304560E+09 | 0.123066E+09 | 0.172684E+10 |
February | 0.676194E+09 | 0.239995E+09 | 0.436198E+09 | 0.394889E+09 | 0.135379E+10 |
March | 0.111778E+10 | 0.404645E+09 | 0.713132E+09 | 0.881099E+09 | 0.123136E+10 |
April | 0.167685E+10 | 0.696756E+09 | 0.980094E+09 | 0.165897E+10 | 0.934036E+09 |
May | 0.184380E+10 | 0.641045E+09 | 0.120275E+10 | 0.193598E+10 | 0.794626E+09 |
June | 0.213692E+10 | 0.929790E+09 | 0.120713E+10 | 0.243050E+10 | 0.595812E+09 |
July | 0.205630E+10 | 0.922987E+09 | 0.113332E+10 | 0.244558E+10 | 0.536888E+09 |
August | 0.202106E+10 | 0.101105E+10 | 0.101001E+10 | 0.249004E+10 | 0.518199E+09 |
September | 0.144607E+10 | 0.666942E+09 | 0.779132E+09 | 0.157001E+10 | 0.753317E+09 |
October | 0.973968E+09 | 0.413845E+09 | 0.560123E+09 | 0.848417E+09 | 0.109117E+10 |
November | 0.461985E+09 | 0.130423E+09 | 0.331562E+09 | 0.213919E+09 | 0.138276E+10 |
December | 0.391563E+09 | 0.126056E+09 | 0.265507E+09 | 0.159181E+09 | 0.175742E+10 |
Annual Sum or Average | 0.152105E+11 | 0.628698E+10 | 0.892352E+10 | 0.151516E+11 | 0.126762E+11 |
Minimum of Months | 0.391563E+09 | 0.103442E+09 | 0.265507E+09 | 0.123066E+09 | 0.518199E+09 |
Maximum of Months | 0.213692E+10 | 0.101105E+10 | 0.120713E+10 | 0.249004E+10 | 0.175742E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.408002E+09 | 0.103442E+09 | 0.304560E+09 | 0.123066E+09 | 0.172684E+10 |
February | 0.676194E+09 | 0.239995E+09 | 0.436198E+09 | 0.394889E+09 | 0.135379E+10 |
March | 0.111778E+10 | 0.404645E+09 | 0.713132E+09 | 0.881099E+09 | 0.123136E+10 |
April | 0.167685E+10 | 0.696756E+09 | 0.980094E+09 | 0.165897E+10 | 0.934036E+09 |
May | 0.184380E+10 | 0.641045E+09 | 0.120275E+10 | 0.193598E+10 | 0.794626E+09 |
June | 0.213692E+10 | 0.929790E+09 | 0.120713E+10 | 0.243050E+10 | 0.595812E+09 |
July | 0.205630E+10 | 0.922987E+09 | 0.113332E+10 | 0.244558E+10 | 0.536888E+09 |
August | 0.202106E+10 | 0.101105E+10 | 0.101001E+10 | 0.249004E+10 | 0.518199E+09 |
September | 0.144607E+10 | 0.666942E+09 | 0.779132E+09 | 0.157001E+10 | 0.753317E+09 |
October | 0.973968E+09 | 0.413845E+09 | 0.560123E+09 | 0.848417E+09 | 0.109117E+10 |
November | 0.461985E+09 | 0.130423E+09 | 0.331562E+09 | 0.213919E+09 | 0.138276E+10 |
December | 0.391563E+09 | 0.126056E+09 | 0.265507E+09 | 0.159181E+09 | 0.175742E+10 |
Annual Sum or Average | 0.152105E+11 | 0.628698E+10 | 0.892352E+10 | 0.151516E+11 | 0.126762E+11 |
Minimum of Months | 0.391563E+09 | 0.103442E+09 | 0.265507E+09 | 0.123066E+09 | 0.518199E+09 |
Maximum of Months | 0.213692E+10 | 0.101105E+10 | 0.120713E+10 | 0.249004E+10 | 0.175742E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.407994E+09 | 0.103440E+09 | 0.304554E+09 | 0.123064E+09 | 0.172681E+10 |
February | 0.676181E+09 | 0.239991E+09 | 0.436190E+09 | 0.394882E+09 | 0.135376E+10 |
March | 0.111776E+10 | 0.404637E+09 | 0.713119E+09 | 0.881083E+09 | 0.123133E+10 |
April | 0.167682E+10 | 0.696743E+09 | 0.980077E+09 | 0.165894E+10 | 0.934019E+09 |
May | 0.184376E+10 | 0.641034E+09 | 0.120273E+10 | 0.193594E+10 | 0.794612E+09 |
June | 0.213688E+10 | 0.929773E+09 | 0.120711E+10 | 0.243046E+10 | 0.595801E+09 |
July | 0.205627E+10 | 0.922970E+09 | 0.113330E+10 | 0.244553E+10 | 0.536878E+09 |
August | 0.202102E+10 | 0.101103E+10 | 0.100999E+10 | 0.248999E+10 | 0.518190E+09 |
September | 0.144605E+10 | 0.666930E+09 | 0.779118E+09 | 0.156998E+10 | 0.753303E+09 |
October | 0.973950E+09 | 0.413837E+09 | 0.560113E+09 | 0.848401E+09 | 0.109115E+10 |
November | 0.461977E+09 | 0.130421E+09 | 0.331556E+09 | 0.213915E+09 | 0.138273E+10 |
December | 0.391556E+09 | 0.126053E+09 | 0.265502E+09 | 0.159178E+09 | 0.175739E+10 |
Annual Sum or Average | 0.152102E+11 | 0.628686E+10 | 0.892335E+10 | 0.151514E+11 | 0.126760E+11 |
Minimum of Months | 0.391556E+09 | 0.103440E+09 | 0.265502E+09 | 0.123064E+09 | 0.518190E+09 |
Maximum of Months | 0.213688E+10 | 0.101103E+10 | 0.120711E+10 | 0.248999E+10 | 0.175739E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100968E+10 | 0.599553E+09 | 0.410128E+09 | 0.862955E+09 | 0.141063E+10 |
February | 0.140247E+10 | 0.868148E+09 | 0.534322E+09 | 0.138304E+10 | 0.115369E+10 |
March | 0.167029E+10 | 0.890750E+09 | 0.779544E+09 | 0.174081E+10 | 0.112247E+10 |
April | 0.170663E+10 | 0.741008E+09 | 0.965618E+09 | 0.189025E+10 | 0.911732E+09 |
May | 0.161251E+10 | 0.480382E+09 | 0.113212E+10 | 0.181540E+10 | 0.762554E+09 |
June | 0.142770E+10 | 0.383319E+09 | 0.104438E+10 | 0.164254E+10 | 0.585464E+09 |
July | 0.160886E+10 | 0.589252E+09 | 0.101961E+10 | 0.204722E+10 | 0.547365E+09 |
August | 0.172852E+10 | 0.806038E+09 | 0.922483E+09 | 0.227533E+10 | 0.528677E+09 |
September | 0.185335E+10 | 0.102348E+10 | 0.829870E+09 | 0.228650E+10 | 0.714101E+09 |
October | 0.173478E+10 | 0.107110E+10 | 0.663683E+09 | 0.194289E+10 | 0.985009E+09 |
November | 0.992577E+09 | 0.568830E+09 | 0.423747E+09 | 0.911331E+09 | 0.117400E+10 |
December | 0.107314E+10 | 0.694469E+09 | 0.378667E+09 | 0.101560E+10 | 0.147971E+10 |
Annual Sum or Average | 0.178205E+11 | 0.871633E+10 | 0.910418E+10 | 0.198139E+11 | 0.113754E+11 |
Minimum of Months | 0.992577E+09 | 0.383319E+09 | 0.378667E+09 | 0.862955E+09 | 0.528677E+09 |
Maximum of Months | 0.185335E+10 | 0.107110E+10 | 0.113212E+10 | 0.228650E+10 | 0.147971E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100968E+10 | 0.599553E+09 | 0.410128E+09 | 0.862954E+09 | 0.141063E+10 |
February | 0.140247E+10 | 0.868147E+09 | 0.534322E+09 | 0.138304E+10 | 0.115369E+10 |
March | 0.167029E+10 | 0.890748E+09 | 0.779544E+09 | 0.174080E+10 | 0.112247E+10 |
April | 0.170662E+10 | 0.741007E+09 | 0.965618E+09 | 0.189025E+10 | 0.911732E+09 |
May | 0.161251E+10 | 0.480382E+09 | 0.113212E+10 | 0.181540E+10 | 0.762554E+09 |
June | 0.142770E+10 | 0.383318E+09 | 0.104438E+10 | 0.164254E+10 | 0.585464E+09 |
July | 0.160886E+10 | 0.589251E+09 | 0.101961E+10 | 0.204722E+10 | 0.547365E+09 |
August | 0.172852E+10 | 0.806038E+09 | 0.922483E+09 | 0.227533E+10 | 0.528677E+09 |
September | 0.185335E+10 | 0.102348E+10 | 0.829869E+09 | 0.228650E+10 | 0.714101E+09 |
October | 0.173478E+10 | 0.107110E+10 | 0.663682E+09 | 0.194289E+10 | 0.985009E+09 |
November | 0.992575E+09 | 0.568829E+09 | 0.423746E+09 | 0.911330E+09 | 0.117400E+10 |
December | 0.107314E+10 | 0.694468E+09 | 0.378667E+09 | 0.101560E+10 | 0.147971E+10 |
Annual Sum or Average | 0.178205E+11 | 0.871632E+10 | 0.910417E+10 | 0.198138E+11 | 0.113754E+11 |
Minimum of Months | 0.992575E+09 | 0.383318E+09 | 0.378667E+09 | 0.862954E+09 | 0.528677E+09 |
Maximum of Months | 0.185335E+10 | 0.107110E+10 | 0.113212E+10 | 0.228650E+10 | 0.147971E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100968E+10 | 0.599553E+09 | 0.410128E+09 | 0.862955E+09 | 0.141063E+10 |
February | 0.140247E+10 | 0.868148E+09 | 0.534322E+09 | 0.138304E+10 | 0.115369E+10 |
March | 0.167029E+10 | 0.890750E+09 | 0.779544E+09 | 0.174081E+10 | 0.112247E+10 |
April | 0.170663E+10 | 0.741008E+09 | 0.965618E+09 | 0.189025E+10 | 0.911732E+09 |
May | 0.161251E+10 | 0.480382E+09 | 0.113212E+10 | 0.181540E+10 | 0.762554E+09 |
June | 0.142770E+10 | 0.383319E+09 | 0.104438E+10 | 0.164254E+10 | 0.585464E+09 |
July | 0.160886E+10 | 0.589252E+09 | 0.101961E+10 | 0.204722E+10 | 0.547365E+09 |
August | 0.172852E+10 | 0.806038E+09 | 0.922483E+09 | 0.227533E+10 | 0.528677E+09 |
September | 0.185335E+10 | 0.102348E+10 | 0.829870E+09 | 0.228650E+10 | 0.714101E+09 |
October | 0.173478E+10 | 0.107110E+10 | 0.663683E+09 | 0.194289E+10 | 0.985009E+09 |
November | 0.992577E+09 | 0.568830E+09 | 0.423747E+09 | 0.911331E+09 | 0.117400E+10 |
December | 0.107314E+10 | 0.694469E+09 | 0.378667E+09 | 0.101560E+10 | 0.147971E+10 |
Annual Sum or Average | 0.178205E+11 | 0.871633E+10 | 0.910418E+10 | 0.198139E+11 | 0.113754E+11 |
Minimum of Months | 0.992577E+09 | 0.383319E+09 | 0.378667E+09 | 0.862955E+09 | 0.528677E+09 |
Maximum of Months | 0.185335E+10 | 0.107110E+10 | 0.113212E+10 | 0.228650E+10 | 0.147971E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100968E+10 | 0.599553E+09 | 0.410128E+09 | 0.862954E+09 | 0.141063E+10 |
February | 0.140247E+10 | 0.868147E+09 | 0.534322E+09 | 0.138304E+10 | 0.115369E+10 |
March | 0.167029E+10 | 0.890748E+09 | 0.779544E+09 | 0.174080E+10 | 0.112247E+10 |
April | 0.170662E+10 | 0.741007E+09 | 0.965618E+09 | 0.189025E+10 | 0.911732E+09 |
May | 0.161251E+10 | 0.480382E+09 | 0.113212E+10 | 0.181540E+10 | 0.762554E+09 |
June | 0.142770E+10 | 0.383318E+09 | 0.104438E+10 | 0.164254E+10 | 0.585464E+09 |
July | 0.160886E+10 | 0.589251E+09 | 0.101961E+10 | 0.204722E+10 | 0.547365E+09 |
August | 0.172852E+10 | 0.806038E+09 | 0.922483E+09 | 0.227533E+10 | 0.528677E+09 |
September | 0.185335E+10 | 0.102348E+10 | 0.829869E+09 | 0.228650E+10 | 0.714101E+09 |
October | 0.173478E+10 | 0.107110E+10 | 0.663682E+09 | 0.194289E+10 | 0.985009E+09 |
November | 0.992575E+09 | 0.568829E+09 | 0.423746E+09 | 0.911330E+09 | 0.117400E+10 |
December | 0.107314E+10 | 0.694468E+09 | 0.378667E+09 | 0.101560E+10 | 0.147971E+10 |
Annual Sum or Average | 0.178205E+11 | 0.871632E+10 | 0.910417E+10 | 0.198138E+11 | 0.113754E+11 |
Minimum of Months | 0.992575E+09 | 0.383318E+09 | 0.378667E+09 | 0.862954E+09 | 0.528677E+09 |
Maximum of Months | 0.185335E+10 | 0.107110E+10 | 0.113212E+10 | 0.228650E+10 | 0.147971E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100964E+10 | 0.599529E+09 | 0.410112E+09 | 0.862920E+09 | 0.141057E+10 |
February | 0.140241E+10 | 0.868113E+09 | 0.534301E+09 | 0.138299E+10 | 0.115364E+10 |
March | 0.167023E+10 | 0.890714E+09 | 0.779513E+09 | 0.174074E+10 | 0.112242E+10 |
April | 0.170656E+10 | 0.740978E+09 | 0.965579E+09 | 0.189018E+10 | 0.911696E+09 |
May | 0.161244E+10 | 0.480363E+09 | 0.113208E+10 | 0.181533E+10 | 0.762524E+09 |
June | 0.142764E+10 | 0.383303E+09 | 0.104434E+10 | 0.164247E+10 | 0.585440E+09 |
July | 0.160880E+10 | 0.589228E+09 | 0.101957E+10 | 0.204714E+10 | 0.547343E+09 |
August | 0.172845E+10 | 0.806006E+09 | 0.922446E+09 | 0.227524E+10 | 0.528656E+09 |
September | 0.185328E+10 | 0.102344E+10 | 0.829837E+09 | 0.228641E+10 | 0.714072E+09 |
October | 0.173471E+10 | 0.107106E+10 | 0.663656E+09 | 0.194281E+10 | 0.984970E+09 |
November | 0.992537E+09 | 0.568807E+09 | 0.423730E+09 | 0.911294E+09 | 0.117395E+10 |
December | 0.107309E+10 | 0.694441E+09 | 0.378652E+09 | 0.101556E+10 | 0.147965E+10 |
Annual Sum or Average | 0.178198E+11 | 0.871598E+10 | 0.910381E+10 | 0.198131E+11 | 0.113749E+11 |
Minimum of Months | 0.992537E+09 | 0.383303E+09 | 0.378652E+09 | 0.862920E+09 | 0.528656E+09 |
Maximum of Months | 0.185328E+10 | 0.107106E+10 | 0.113208E+10 | 0.228641E+10 | 0.147965E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.430342E+09 | 0.126900E+09 | 0.303442E+09 | 0.154150E+09 | 0.187143E+10 |
February | 0.696902E+09 | 0.261915E+09 | 0.434986E+09 | 0.428870E+09 | 0.152980E+10 |
March | 0.108117E+10 | 0.364923E+09 | 0.716244E+09 | 0.823091E+09 | 0.143301E+10 |
April | 0.159182E+10 | 0.608613E+09 | 0.983205E+09 | 0.150797E+10 | 0.113932E+10 |
May | 0.211658E+10 | 0.859850E+09 | 0.125673E+10 | 0.228474E+10 | 0.898265E+09 |
June | 0.196990E+10 | 0.764848E+09 | 0.120505E+10 | 0.216810E+10 | 0.706421E+09 |
July | 0.251466E+10 | 0.132184E+10 | 0.119283E+10 | 0.304876E+10 | 0.687813E+09 |
August | 0.208023E+10 | 0.106223E+10 | 0.101800E+10 | 0.254368E+10 | 0.687207E+09 |
September | 0.163938E+10 | 0.786612E+09 | 0.852771E+09 | 0.185186E+10 | 0.862829E+09 |
October | 0.964416E+09 | 0.392954E+09 | 0.571463E+09 | 0.827307E+09 | 0.125849E+10 |
November | 0.464781E+09 | 0.131087E+09 | 0.333693E+09 | 0.209181E+09 | 0.159587E+10 |
December | 0.403763E+09 | 0.138359E+09 | 0.265403E+09 | 0.183660E+09 | 0.206736E+10 |
Annual Sum or Average | 0.159539E+11 | 0.682012E+10 | 0.913382E+10 | 0.160314E+11 | 0.147378E+11 |
Minimum of Months | 0.403763E+09 | 0.126900E+09 | 0.265403E+09 | 0.154150E+09 | 0.687207E+09 |
Maximum of Months | 0.251466E+10 | 0.132184E+10 | 0.125673E+10 | 0.304876E+10 | 0.206736E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.430342E+09 | 0.126900E+09 | 0.303442E+09 | 0.154150E+09 | 0.187143E+10 |
February | 0.696902E+09 | 0.261915E+09 | 0.434986E+09 | 0.428870E+09 | 0.152980E+10 |
March | 0.108117E+10 | 0.364923E+09 | 0.716244E+09 | 0.823091E+09 | 0.143301E+10 |
April | 0.159182E+10 | 0.608613E+09 | 0.983205E+09 | 0.150797E+10 | 0.113932E+10 |
May | 0.211658E+10 | 0.859850E+09 | 0.125673E+10 | 0.228474E+10 | 0.898265E+09 |
June | 0.196990E+10 | 0.764848E+09 | 0.120505E+10 | 0.216810E+10 | 0.706421E+09 |
July | 0.251466E+10 | 0.132184E+10 | 0.119283E+10 | 0.304876E+10 | 0.687813E+09 |
August | 0.208023E+10 | 0.106223E+10 | 0.101800E+10 | 0.254368E+10 | 0.687207E+09 |
September | 0.163938E+10 | 0.786612E+09 | 0.852771E+09 | 0.185186E+10 | 0.862829E+09 |
October | 0.964416E+09 | 0.392954E+09 | 0.571463E+09 | 0.827307E+09 | 0.125849E+10 |
November | 0.464781E+09 | 0.131087E+09 | 0.333693E+09 | 0.209181E+09 | 0.159587E+10 |
December | 0.403763E+09 | 0.138359E+09 | 0.265403E+09 | 0.183660E+09 | 0.206736E+10 |
Annual Sum or Average | 0.159539E+11 | 0.682012E+10 | 0.913382E+10 | 0.160314E+11 | 0.147378E+11 |
Minimum of Months | 0.403763E+09 | 0.126900E+09 | 0.265403E+09 | 0.154150E+09 | 0.687207E+09 |
Maximum of Months | 0.251466E+10 | 0.132184E+10 | 0.125673E+10 | 0.304876E+10 | 0.206736E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.430334E+09 | 0.126898E+09 | 0.303437E+09 | 0.154147E+09 | 0.187139E+10 |
February | 0.696889E+09 | 0.261911E+09 | 0.434979E+09 | 0.428863E+09 | 0.152977E+10 |
March | 0.108115E+10 | 0.364916E+09 | 0.716231E+09 | 0.823076E+09 | 0.143298E+10 |
April | 0.159179E+10 | 0.608602E+09 | 0.983187E+09 | 0.150794E+10 | 0.113930E+10 |
May | 0.211654E+10 | 0.859835E+09 | 0.125670E+10 | 0.228470E+10 | 0.898249E+09 |
June | 0.196987E+10 | 0.764834E+09 | 0.120503E+10 | 0.216806E+10 | 0.706408E+09 |
July | 0.251462E+10 | 0.132181E+10 | 0.119281E+10 | 0.304870E+10 | 0.687801E+09 |
August | 0.208019E+10 | 0.106221E+10 | 0.101799E+10 | 0.254364E+10 | 0.687194E+09 |
September | 0.163935E+10 | 0.786597E+09 | 0.852756E+09 | 0.185183E+10 | 0.862813E+09 |
October | 0.964399E+09 | 0.392946E+09 | 0.571452E+09 | 0.827292E+09 | 0.125846E+10 |
November | 0.464772E+09 | 0.131085E+09 | 0.333687E+09 | 0.209177E+09 | 0.159584E+10 |
December | 0.403755E+09 | 0.138357E+09 | 0.265399E+09 | 0.183657E+09 | 0.206732E+10 |
Annual Sum or Average | 0.159537E+11 | 0.682000E+10 | 0.913365E+10 | 0.160311E+11 | 0.147375E+11 |
Minimum of Months | 0.403755E+09 | 0.126898E+09 | 0.265399E+09 | 0.154147E+09 | 0.687194E+09 |
Maximum of Months | 0.251462E+10 | 0.132181E+10 | 0.125670E+10 | 0.304870E+10 | 0.206732E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114260E+10 | 0.00 | 0.114260E+10 | 39270307.70 | 0.699811E+10 |
February | 0.160585E+10 | 0.00 | 0.160585E+10 | 0.309934E+09 | 0.565242E+10 |
March | 0.261947E+10 | 0.00 | 0.261947E+10 | 0.106981E+10 | 0.519971E+10 |
April | 0.358724E+10 | 12725040.77 | 0.357452E+10 | 0.230661E+10 | 0.400732E+10 |
May | 0.476974E+10 | 0.141702E+09 | 0.462804E+10 | 0.384555E+10 | 0.335727E+10 |
June | 0.485348E+10 | 0.320504E+09 | 0.453298E+10 | 0.433407E+10 | 0.250075E+10 |
July | 0.476673E+10 | 0.373735E+09 | 0.439300E+10 | 0.483813E+10 | 0.231379E+10 |
August | 0.385871E+10 | 0.104312E+09 | 0.375439E+10 | 0.398734E+10 | 0.226834E+10 |
September | 0.290062E+10 | 855348.19 | 0.289976E+10 | 0.220843E+10 | 0.330885E+10 |
October | 0.205365E+10 | 0.00 | 0.205365E+10 | 0.913659E+09 | 0.457566E+10 |
November | 0.125187E+10 | 0.00 | 0.125187E+10 | 0.165946E+09 | 0.558770E+10 |
December | 0.970912E+09 | 0.00 | 0.970912E+09 | 18261836.02 | 0.711967E+10 |
Annual Sum or Average | 0.343809E+11 | 0.953833E+09 | 0.334270E+11 | 0.240370E+11 | 0.528896E+11 |
Minimum of Months | 0.970912E+09 | 0.00 | 0.970912E+09 | 18261836.02 | 0.226834E+10 |
Maximum of Months | 0.485348E+10 | 0.373735E+09 | 0.462804E+10 | 0.483813E+10 | 0.711967E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122399E+10 | 0.310323E+09 | 0.913670E+09 | 0.425843E+09 | 0.443889E+10 |
February | 0.202856E+10 | 0.719979E+09 | 0.130858E+10 | 0.127928E+10 | 0.360436E+10 |
March | 0.335330E+10 | 0.121392E+10 | 0.213937E+10 | 0.269328E+10 | 0.337575E+10 |
April | 0.503050E+10 | 0.209025E+10 | 0.294025E+10 | 0.498760E+10 | 0.262313E+10 |
May | 0.553133E+10 | 0.192312E+10 | 0.360821E+10 | 0.578704E+10 | 0.228494E+10 |
June | 0.641070E+10 | 0.278934E+10 | 0.362136E+10 | 0.723417E+10 | 0.173492E+10 |
July | 0.616885E+10 | 0.276893E+10 | 0.339991E+10 | 0.728754E+10 | 0.157079E+10 |
August | 0.606311E+10 | 0.303312E+10 | 0.303000E+10 | 0.741030E+10 | 0.154166E+10 |
September | 0.433818E+10 | 0.200081E+10 | 0.233737E+10 | 0.469218E+10 | 0.216625E+10 |
October | 0.292187E+10 | 0.124152E+10 | 0.168035E+10 | 0.258803E+10 | 0.299281E+10 |
November | 0.138594E+10 | 0.391265E+09 | 0.994677E+09 | 0.700671E+09 | 0.362287E+10 |
December | 0.117468E+10 | 0.378163E+09 | 0.796514E+09 | 0.531677E+09 | 0.457313E+10 |
Annual Sum or Average | 0.456310E+11 | 0.188607E+11 | 0.267703E+11 | 0.456176E+11 | 0.345295E+11 |
Minimum of Months | 0.117468E+10 | 0.310323E+09 | 0.796514E+09 | 0.425843E+09 | 0.154166E+10 |
Maximum of Months | 0.641070E+10 | 0.303312E+10 | 0.362136E+10 | 0.741030E+10 | 0.457313E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.504835E+10 | 0.299773E+10 | 0.205062E+10 | 0.438849E+10 | 0.647354E+10 |
February | 0.701227E+10 | 0.434069E+10 | 0.267158E+10 | 0.696833E+10 | 0.541367E+10 |
March | 0.835137E+10 | 0.445369E+10 | 0.389768E+10 | 0.870382E+10 | 0.529633E+10 |
April | 0.853303E+10 | 0.370499E+10 | 0.482803E+10 | 0.944083E+10 | 0.431477E+10 |
May | 0.806244E+10 | 0.240188E+10 | 0.566056E+10 | 0.902470E+10 | 0.369959E+10 |
June | 0.713840E+10 | 0.191657E+10 | 0.522183E+10 | 0.817616E+10 | 0.281856E+10 |
July | 0.804422E+10 | 0.294622E+10 | 0.509800E+10 | 0.101995E+11 | 0.263061E+10 |
August | 0.864250E+10 | 0.403014E+10 | 0.461236E+10 | 0.113365E+11 | 0.256065E+10 |
September | 0.926665E+10 | 0.511735E+10 | 0.414930E+10 | 0.113801E+11 | 0.349423E+10 |
October | 0.867382E+10 | 0.535544E+10 | 0.331838E+10 | 0.968388E+10 | 0.469742E+10 |
November | 0.496282E+10 | 0.284412E+10 | 0.211871E+10 | 0.461760E+10 | 0.541564E+10 |
December | 0.536562E+10 | 0.347230E+10 | 0.189331E+10 | 0.515136E+10 | 0.675534E+10 |
Annual Sum or Average | 0.891015E+11 | 0.435811E+11 | 0.455203E+11 | 0.990714E+11 | 0.535703E+11 |
Minimum of Months | 0.496282E+10 | 0.191657E+10 | 0.189331E+10 | 0.438849E+10 | 0.256065E+10 |
Maximum of Months | 0.926665E+10 | 0.535544E+10 | 0.566056E+10 | 0.113801E+11 | 0.675534E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129101E+10 | 0.380696E+09 | 0.910317E+09 | 0.527010E+09 | 0.462359E+10 |
February | 0.209068E+10 | 0.785738E+09 | 0.130495E+10 | 0.141424E+10 | 0.376525E+10 |
March | 0.324347E+10 | 0.109476E+10 | 0.214871E+10 | 0.262275E+10 | 0.356564E+10 |
April | 0.477540E+10 | 0.182582E+10 | 0.294958E+10 | 0.469682E+10 | 0.287224E+10 |
May | 0.634966E+10 | 0.257952E+10 | 0.377014E+10 | 0.688899E+10 | 0.248888E+10 |
June | 0.590965E+10 | 0.229452E+10 | 0.361513E+10 | 0.656717E+10 | 0.189867E+10 |
July | 0.754391E+10 | 0.396547E+10 | 0.357845E+10 | 0.921876E+10 | 0.182362E+10 |
August | 0.624062E+10 | 0.318664E+10 | 0.305398E+10 | 0.773760E+10 | 0.177815E+10 |
September | 0.491810E+10 | 0.235981E+10 | 0.255829E+10 | 0.559275E+10 | 0.237852E+10 |
October | 0.289322E+10 | 0.117885E+10 | 0.171437E+10 | 0.259709E+10 | 0.319381E+10 |
November | 0.139433E+10 | 0.393258E+09 | 0.100107E+10 | 0.728577E+09 | 0.376434E+10 |
December | 0.121128E+10 | 0.415073E+09 | 0.796202E+09 | 0.628590E+09 | 0.478310E+10 |
Annual Sum or Average | 0.478613E+11 | 0.204602E+11 | 0.274012E+11 | 0.492203E+11 | 0.369358E+11 |
Minimum of Months | 0.121128E+10 | 0.380696E+09 | 0.796202E+09 | 0.527010E+09 | 0.177815E+10 |
Maximum of Months | 0.754391E+10 | 0.396547E+10 | 0.377014E+10 | 0.921876E+10 | 0.478310E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114260E+10 | 0.00 | 0.114260E+10 | 57933719.12 | 0.656680E+10 |
February | 0.160585E+10 | 0.00 | 0.160585E+10 | 0.367794E+09 | 0.522110E+10 |
March | 0.261947E+10 | 0.00 | 0.261947E+10 | 0.119498E+10 | 0.474776E+10 |
April | 0.358724E+10 | 12725040.77 | 0.357452E+10 | 0.241467E+10 | 0.374023E+10 |
May | 0.476974E+10 | 0.141702E+09 | 0.462804E+10 | 0.391901E+10 | 0.319161E+10 |
June | 0.485348E+10 | 0.320504E+09 | 0.453298E+10 | 0.434859E+10 | 0.242564E+10 |
July | 0.476673E+10 | 0.373735E+09 | 0.439300E+10 | 0.482527E+10 | 0.226307E+10 |
August | 0.385871E+10 | 0.104312E+09 | 0.375439E+10 | 0.399016E+10 | 0.220512E+10 |
September | 0.290062E+10 | 855348.19 | 0.289976E+10 | 0.227351E+10 | 0.310609E+10 |
October | 0.205365E+10 | 0.00 | 0.205365E+10 | 0.104044E+10 | 0.412694E+10 |
November | 0.125187E+10 | 0.00 | 0.125187E+10 | 0.222952E+09 | 0.500605E+10 |
December | 0.970912E+09 | 0.00 | 0.970912E+09 | 37579386.66 | 0.653144E+10 |
Annual Sum or Average | 0.343809E+11 | 0.953833E+09 | 0.334270E+11 | 0.246929E+11 | 0.491318E+11 |
Minimum of Months | 0.970912E+09 | 0.00 | 0.970912E+09 | 37579386.66 | 0.220512E+10 |
Maximum of Months | 0.485348E+10 | 0.373735E+09 | 0.462804E+10 | 0.482527E+10 | 0.656680E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122399E+10 | 0.310323E+09 | 0.913670E+09 | 0.458629E+09 | 0.416635E+10 |
February | 0.202856E+10 | 0.719979E+09 | 0.130858E+10 | 0.135645E+10 | 0.331565E+10 |
March | 0.335330E+10 | 0.121392E+10 | 0.213937E+10 | 0.280361E+10 | 0.308487E+10 |
April | 0.503050E+10 | 0.209025E+10 | 0.294025E+10 | 0.506615E+10 | 0.246249E+10 |
May | 0.553133E+10 | 0.192312E+10 | 0.360821E+10 | 0.583530E+10 | 0.218190E+10 |
June | 0.641070E+10 | 0.278934E+10 | 0.362136E+10 | 0.724144E+10 | 0.168845E+10 |
July | 0.616885E+10 | 0.276893E+10 | 0.339991E+10 | 0.728854E+10 | 0.154125E+10 |
August | 0.606311E+10 | 0.303312E+10 | 0.303000E+10 | 0.741570E+10 | 0.150408E+10 |
September | 0.433818E+10 | 0.200081E+10 | 0.233737E+10 | 0.474094E+10 | 0.204535E+10 |
October | 0.292187E+10 | 0.124152E+10 | 0.168035E+10 | 0.268847E+10 | 0.271279E+10 |
November | 0.138594E+10 | 0.391265E+09 | 0.994677E+09 | 0.771131E+09 | 0.324037E+10 |
December | 0.117468E+10 | 0.378163E+09 | 0.796514E+09 | 0.577601E+09 | 0.419154E+10 |
Annual Sum or Average | 0.456310E+11 | 0.188607E+11 | 0.267703E+11 | 0.462439E+11 | 0.321351E+11 |
Minimum of Months | 0.117468E+10 | 0.310323E+09 | 0.796514E+09 | 0.458629E+09 | 0.150408E+10 |
Maximum of Months | 0.641070E+10 | 0.303312E+10 | 0.362136E+10 | 0.741570E+10 | 0.419154E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.504835E+10 | 0.299773E+10 | 0.205062E+10 | 0.448169E+10 | 0.603565E+10 |
February | 0.701227E+10 | 0.434069E+10 | 0.267158E+10 | 0.709704E+10 | 0.499199E+10 |
March | 0.835137E+10 | 0.445369E+10 | 0.389768E+10 | 0.881360E+10 | 0.486741E+10 |
April | 0.853303E+10 | 0.370499E+10 | 0.482803E+10 | 0.951256E+10 | 0.406128E+10 |
May | 0.806244E+10 | 0.240188E+10 | 0.566056E+10 | 0.905933E+10 | 0.352900E+10 |
June | 0.713840E+10 | 0.191657E+10 | 0.522183E+10 | 0.816560E+10 | 0.273404E+10 |
July | 0.804422E+10 | 0.294622E+10 | 0.509800E+10 | 0.101700E+11 | 0.257587E+10 |
August | 0.864250E+10 | 0.403014E+10 | 0.461236E+10 | 0.113145E+11 | 0.249527E+10 |
September | 0.926665E+10 | 0.511735E+10 | 0.414930E+10 | 0.114171E+11 | 0.331477E+10 |
October | 0.867382E+10 | 0.535544E+10 | 0.331838E+10 | 0.979205E+10 | 0.430070E+10 |
November | 0.496282E+10 | 0.284412E+10 | 0.211871E+10 | 0.474491E+10 | 0.488745E+10 |
December | 0.536562E+10 | 0.347230E+10 | 0.189331E+10 | 0.525409E+10 | 0.619893E+10 |
Annual Sum or Average | 0.891015E+11 | 0.435811E+11 | 0.455203E+11 | 0.998224E+11 | 0.499923E+11 |
Minimum of Months | 0.496282E+10 | 0.191657E+10 | 0.189331E+10 | 0.448169E+10 | 0.249527E+10 |
Maximum of Months | 0.926665E+10 | 0.535544E+10 | 0.566056E+10 | 0.114171E+11 | 0.619893E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129101E+10 | 0.380696E+09 | 0.910317E+09 | 0.551848E+09 | 0.434140E+10 |
February | 0.209068E+10 | 0.785738E+09 | 0.130495E+10 | 0.146034E+10 | 0.351337E+10 |
March | 0.324347E+10 | 0.109476E+10 | 0.214871E+10 | 0.268829E+10 | 0.330624E+10 |
April | 0.477540E+10 | 0.182582E+10 | 0.294958E+10 | 0.474329E+10 | 0.271673E+10 |
May | 0.634966E+10 | 0.257952E+10 | 0.377014E+10 | 0.690247E+10 | 0.238545E+10 |
June | 0.590965E+10 | 0.229452E+10 | 0.361513E+10 | 0.655219E+10 | 0.184448E+10 |
July | 0.754391E+10 | 0.396547E+10 | 0.357845E+10 | 0.918838E+10 | 0.178466E+10 |
August | 0.624062E+10 | 0.318664E+10 | 0.305398E+10 | 0.771732E+10 | 0.173616E+10 |
September | 0.491810E+10 | 0.235981E+10 | 0.255829E+10 | 0.561019E+10 | 0.226782E+10 |
October | 0.289322E+10 | 0.117885E+10 | 0.171437E+10 | 0.266148E+10 | 0.294117E+10 |
November | 0.139433E+10 | 0.393258E+09 | 0.100107E+10 | 0.773988E+09 | 0.344300E+10 |
December | 0.121128E+10 | 0.415073E+09 | 0.796202E+09 | 0.654123E+09 | 0.444415E+10 |
Annual Sum or Average | 0.478613E+11 | 0.204602E+11 | 0.274012E+11 | 0.495039E+11 | 0.347246E+11 |
Minimum of Months | 0.121128E+10 | 0.380696E+09 | 0.796202E+09 | 0.551848E+09 | 0.173616E+10 |
Maximum of Months | 0.754391E+10 | 0.396547E+10 | 0.377014E+10 | 0.918838E+10 | 0.444415E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.49 | 3094.13 | 426.60 | 0.00 | 426.60 | 0.00 | 0.00 |
February | 80.29 | 2738.54 | 663.80 | 0.00 | 663.80 | 0.00 | 0.00 |
March | 327.00 | 2230.11 | 978.00 | 0.00 | 978.00 | 0.00 | 0.00 |
April | 814.44 | 1747.04 | 1383.97 | 4.91 | 1379.06 | 0.00 | 0.00 |
May | 1398.79 | 1338.03 | 1780.82 | 52.91 | 1727.92 | 0.00 | 0.00 |
June | 1643.66 | 1027.80 | 1872.49 | 123.65 | 1748.84 | 0.00 | 0.00 |
July | 1773.20 | 923.55 | 1779.70 | 139.54 | 1640.16 | 0.00 | 0.00 |
August | 1454.62 | 904.39 | 1440.68 | 38.95 | 1401.74 | 0.00 | 0.00 |
September | 823.11 | 1372.78 | 1119.07 | 0.33 | 1118.74 | 0.00 | 0.00 |
October | 283.63 | 1953.19 | 766.75 | 0.00 | 766.75 | 0.00 | 0.00 |
November | 36.25 | 2583.72 | 482.98 | 0.00 | 482.98 | 0.00 | 0.00 |
December | 0.90 | 3204.74 | 362.50 | 0.00 | 362.50 | 0.00 | 0.00 |
Annual Sum or Average | 724.09 | 1922.50 | 1090.21 | 30.25 | 1059.97 | 0.00 | 0.00 |
Minimum of Months | 0.90 | 904.39 | 362.50 | 0.00 | 362.50 | 0.00 | 0.00 |
Maximum of Months | 1773.20 | 3204.74 | 1872.49 | 139.54 | 1748.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 137.84 | 1934.18 | 456.99 | 115.86 | 341.13 | 0.00 | 0.00 |
February | 489.69 | 1678.79 | 838.53 | 297.61 | 540.92 | 0.00 | 0.00 |
March | 986.89 | 1379.20 | 1251.98 | 453.23 | 798.75 | 0.00 | 0.00 |
April | 1920.09 | 1081.05 | 1940.79 | 806.43 | 1134.36 | 0.00 | 0.00 |
May | 2168.42 | 890.03 | 2065.17 | 718.01 | 1347.16 | 0.00 | 0.00 |
June | 2813.07 | 689.59 | 2473.27 | 1076.14 | 1397.14 | 0.00 | 0.00 |
July | 2739.20 | 601.35 | 2303.19 | 1033.81 | 1269.39 | 0.00 | 0.00 |
August | 2789.00 | 580.42 | 2263.72 | 1132.44 | 1131.28 | 0.00 | 0.00 |
September | 1817.13 | 871.89 | 1673.69 | 771.92 | 901.77 | 0.00 | 0.00 |
October | 950.28 | 1222.18 | 1090.91 | 463.53 | 627.37 | 0.00 | 0.00 |
November | 247.59 | 1600.41 | 534.70 | 150.95 | 383.75 | 0.00 | 0.00 |
December | 178.29 | 1968.42 | 438.58 | 141.19 | 297.39 | 0.00 | 0.00 |
Annual Sum or Average | 1441.36 | 1205.87 | 1446.96 | 598.07 | 848.88 | 0.00 | 0.00 |
Minimum of Months | 137.84 | 580.42 | 438.58 | 115.86 | 297.39 | 0.00 | 0.00 |
Maximum of Months | 2813.07 | 1968.42 | 2473.27 | 1132.44 | 1397.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1610.94 | 2633.32 | 1884.84 | 1119.23 | 765.61 | 0.00 | 0.00 |
February | 2858.45 | 2384.42 | 2898.60 | 1794.27 | 1104.33 | 0.00 | 0.00 |
March | 3249.68 | 2095.39 | 3118.06 | 1662.82 | 1455.23 | 0.00 | 0.00 |
April | 3646.29 | 1758.73 | 3292.07 | 1429.40 | 1862.67 | 0.00 | 0.00 |
May | 3388.94 | 1423.51 | 3010.18 | 896.76 | 2113.42 | 0.00 | 0.00 |
June | 3168.45 | 1129.36 | 2754.02 | 739.42 | 2014.60 | 0.00 | 0.00 |
July | 3821.69 | 1021.80 | 3003.38 | 1100.00 | 1903.38 | 0.00 | 0.00 |
August | 4247.52 | 986.92 | 3226.75 | 1504.69 | 1722.06 | 0.00 | 0.00 |
September | 4410.65 | 1377.50 | 3575.11 | 1974.29 | 1600.82 | 0.00 | 0.00 |
October | 3626.93 | 1838.79 | 3238.44 | 1999.50 | 1238.94 | 0.00 | 0.00 |
November | 1757.95 | 2264.63 | 1914.68 | 1097.27 | 817.41 | 0.00 | 0.00 |
December | 1895.90 | 2762.28 | 2003.30 | 1296.41 | 706.89 | 0.00 | 0.00 |
Annual Sum or Average | 3141.44 | 1803.54 | 2825.40 | 1381.95 | 1443.45 | 0.00 | 0.00 |
Minimum of Months | 1610.94 | 986.92 | 1884.84 | 739.42 | 706.89 | 0.00 | 0.00 |
Maximum of Months | 4410.65 | 2762.28 | 3575.11 | 1999.50 | 2113.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 172.66 | 2096.12 | 482.01 | 142.14 | 339.87 | 0.00 | 0.00 |
February | 531.83 | 1897.06 | 864.21 | 324.79 | 539.41 | 0.00 | 0.00 |
March | 921.92 | 1605.06 | 1210.98 | 408.74 | 802.24 | 0.00 | 0.00 |
April | 1745.32 | 1318.65 | 1842.37 | 704.41 | 1137.96 | 0.00 | 0.00 |
May | 2559.06 | 1006.12 | 2370.70 | 963.09 | 1407.61 | 0.00 | 0.00 |
June | 2509.36 | 817.61 | 2279.97 | 885.24 | 1394.73 | 0.00 | 0.00 |
July | 3414.80 | 770.40 | 2816.59 | 1480.54 | 1336.04 | 0.00 | 0.00 |
August | 2849.09 | 769.72 | 2329.99 | 1189.76 | 1140.23 | 0.00 | 0.00 |
September | 2143.35 | 998.64 | 1897.42 | 910.42 | 987.00 | 0.00 | 0.00 |
October | 926.64 | 1409.59 | 1080.21 | 440.13 | 640.08 | 0.00 | 0.00 |
November | 242.11 | 1847.06 | 537.94 | 151.72 | 386.22 | 0.00 | 0.00 |
December | 205.71 | 2315.57 | 452.24 | 154.97 | 297.27 | 0.00 | 0.00 |
Annual Sum or Average | 1525.04 | 1401.99 | 1517.68 | 648.79 | 868.89 | 0.00 | 0.00 |
Minimum of Months | 172.66 | 769.72 | 452.24 | 142.14 | 297.27 | 0.00 | 0.00 |
Maximum of Months | 3414.80 | 2315.57 | 2816.59 | 1480.54 | 1407.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14.66 | 2612.79 | 426.60 | 0.00 | 426.60 | 0.00 | 0.00 |
February | 128.11 | 2336.48 | 663.80 | 0.00 | 663.80 | 0.00 | 0.00 |
March | 399.42 | 1941.35 | 978.00 | 0.00 | 978.00 | 0.00 | 0.00 |
April | 889.90 | 1546.03 | 1383.97 | 4.91 | 1379.06 | 0.00 | 0.00 |
May | 1435.76 | 1253.46 | 1780.82 | 52.91 | 1727.91 | 0.00 | 0.00 |
June | 1672.09 | 964.80 | 1872.49 | 123.65 | 1748.83 | 0.00 | 0.00 |
July | 1806.35 | 863.87 | 1779.69 | 139.54 | 1640.16 | 0.00 | 0.00 |
August | 1488.70 | 846.90 | 1440.68 | 38.95 | 1401.73 | 0.00 | 0.00 |
September | 852.02 | 1276.56 | 1119.07 | 0.33 | 1118.74 | 0.00 | 0.00 |
October | 341.12 | 1708.36 | 766.75 | 0.00 | 766.75 | 0.00 | 0.00 |
November | 64.02 | 2155.75 | 482.97 | 0.00 | 482.97 | 0.00 | 0.00 |
December | 6.82 | 2658.18 | 362.50 | 0.00 | 362.50 | 0.00 | 0.00 |
Annual Sum or Average | 762.21 | 1677.12 | 1090.21 | 30.25 | 1059.96 | 0.00 | 0.00 |
Minimum of Months | 6.82 | 846.90 | 362.50 | 0.00 | 362.50 | 0.00 | 0.00 |
Maximum of Months | 1806.35 | 2658.18 | 1872.49 | 139.54 | 1748.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 158.99 | 1657.29 | 456.99 | 115.86 | 341.13 | 0.00 | 0.00 |
February | 528.80 | 1489.90 | 838.53 | 297.61 | 540.92 | 0.00 | 0.00 |
March | 1005.56 | 1260.36 | 1251.98 | 453.23 | 798.75 | 0.00 | 0.00 |
April | 1924.23 | 1012.01 | 1940.78 | 806.42 | 1134.36 | 0.00 | 0.00 |
May | 2160.63 | 853.10 | 2065.16 | 718.01 | 1347.15 | 0.00 | 0.00 |
June | 2790.96 | 669.34 | 2473.26 | 1076.14 | 1397.13 | 0.00 | 0.00 |
July | 2720.86 | 586.47 | 2303.18 | 1033.80 | 1269.38 | 0.00 | 0.00 |
August | 2766.69 | 575.59 | 2263.71 | 1132.44 | 1131.27 | 0.00 | 0.00 |
September | 1810.26 | 835.74 | 1673.68 | 771.92 | 901.76 | 0.00 | 0.00 |
October | 966.26 | 1117.39 | 1090.90 | 463.53 | 627.37 | 0.00 | 0.00 |
November | 270.32 | 1397.71 | 534.70 | 150.95 | 383.75 | 0.00 | 0.00 |
December | 198.51 | 1707.41 | 438.57 | 141.19 | 297.38 | 0.00 | 0.00 |
Annual Sum or Average | 1446.52 | 1094.92 | 1446.95 | 598.07 | 848.88 | 0.00 | 0.00 |
Minimum of Months | 158.99 | 575.59 | 438.57 | 115.86 | 297.38 | 0.00 | 0.00 |
Maximum of Months | 2790.96 | 1707.41 | 2473.26 | 1132.44 | 1397.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1638.47 | 2416.94 | 1884.84 | 1119.22 | 765.61 | 0.00 | 0.00 |
February | 2880.43 | 2237.79 | 2898.59 | 1794.27 | 1104.32 | 0.00 | 0.00 |
March | 3249.64 | 1977.42 | 3118.04 | 1662.82 | 1455.23 | 0.00 | 0.00 |
April | 3642.30 | 1664.65 | 3292.06 | 1429.40 | 1862.67 | 0.00 | 0.00 |
May | 3369.44 | 1381.27 | 3010.17 | 896.76 | 2113.41 | 0.00 | 0.00 |
June | 3154.38 | 1087.41 | 2754.01 | 739.42 | 2014.59 | 0.00 | 0.00 |
July | 3808.07 | 982.16 | 3003.37 | 1099.99 | 1903.38 | 0.00 | 0.00 |
August | 4232.58 | 956.04 | 3226.74 | 1504.68 | 1722.06 | 0.00 | 0.00 |
September | 4390.49 | 1348.08 | 3575.10 | 1974.29 | 1600.81 | 0.00 | 0.00 |
October | 3615.55 | 1753.81 | 3238.43 | 1999.49 | 1238.94 | 0.00 | 0.00 |
November | 1781.48 | 2089.37 | 1914.67 | 1097.27 | 817.40 | 0.00 | 0.00 |
December | 1923.30 | 2522.15 | 2003.29 | 1296.41 | 706.88 | 0.00 | 0.00 |
Annual Sum or Average | 3141.53 | 1698.70 | 2825.39 | 1381.95 | 1443.44 | 0.00 | 0.00 |
Minimum of Months | 1638.47 | 956.04 | 1884.84 | 739.42 | 706.88 | 0.00 | 0.00 |
Maximum of Months | 4390.49 | 2522.15 | 3575.10 | 1999.49 | 2113.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 196.76 | 1726.25 | 482.01 | 142.14 | 339.87 | 0.00 | 0.00 |
February | 584.59 | 1556.40 | 864.20 | 324.79 | 539.41 | 0.00 | 0.00 |
March | 979.22 | 1331.26 | 1210.97 | 408.74 | 802.24 | 0.00 | 0.00 |
April | 1812.05 | 1108.12 | 1842.36 | 704.41 | 1137.96 | 0.00 | 0.00 |
May | 2572.06 | 929.24 | 2370.69 | 963.08 | 1407.61 | 0.00 | 0.00 |
June | 2533.63 | 732.51 | 2279.96 | 885.23 | 1394.72 | 0.00 | 0.00 |
July | 3441.89 | 680.86 | 2816.58 | 1480.54 | 1336.04 | 0.00 | 0.00 |
August | 2888.89 | 663.88 | 2329.98 | 1189.76 | 1140.23 | 0.00 | 0.00 |
September | 2157.69 | 917.64 | 1897.41 | 910.42 | 986.99 | 0.00 | 0.00 |
October | 969.64 | 1192.43 | 1080.20 | 440.13 | 640.07 | 0.00 | 0.00 |
November | 281.09 | 1452.29 | 537.94 | 151.72 | 386.21 | 0.00 | 0.00 |
December | 234.69 | 1785.81 | 452.24 | 154.97 | 297.27 | 0.00 | 0.00 |
Annual Sum or Average | 1560.77 | 1171.23 | 1517.67 | 648.79 | 868.89 | 0.00 | 0.00 |
Minimum of Months | 196.76 | 663.88 | 452.24 | 142.14 | 297.27 | 0.00 | 0.00 |
Maximum of Months | 3441.89 | 1785.81 | 2816.58 | 1480.54 | 1407.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 21.63 | 2451.76 | 426.60 | 0.00 | 426.60 | 0.00 | 0.00 |
February | 152.03 | 2158.19 | 663.80 | 0.00 | 663.80 | 0.00 | 0.00 |
March | 446.15 | 1772.61 | 978.00 | 0.00 | 978.00 | 0.00 | 0.00 |
April | 931.58 | 1442.99 | 1383.97 | 4.91 | 1379.06 | 0.00 | 0.00 |
May | 1463.19 | 1191.61 | 1780.82 | 52.91 | 1727.91 | 0.00 | 0.00 |
June | 1677.70 | 935.82 | 1872.49 | 123.65 | 1748.83 | 0.00 | 0.00 |
July | 1801.55 | 844.93 | 1779.69 | 139.54 | 1640.16 | 0.00 | 0.00 |
August | 1489.76 | 823.30 | 1440.68 | 38.95 | 1401.73 | 0.00 | 0.00 |
September | 877.13 | 1198.34 | 1119.07 | 0.33 | 1118.74 | 0.00 | 0.00 |
October | 388.46 | 1540.82 | 766.75 | 0.00 | 766.75 | 0.00 | 0.00 |
November | 86.02 | 1931.35 | 482.97 | 0.00 | 482.97 | 0.00 | 0.00 |
December | 14.03 | 2438.56 | 362.50 | 0.00 | 362.50 | 0.00 | 0.00 |
Annual Sum or Average | 783.01 | 1557.96 | 1090.21 | 30.25 | 1059.96 | 0.00 | 0.00 |
Minimum of Months | 14.03 | 823.30 | 362.50 | 0.00 | 362.50 | 0.00 | 0.00 |
Maximum of Months | 1801.55 | 2451.76 | 1872.49 | 139.54 | 1748.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 171.23 | 1555.54 | 456.99 | 115.86 | 341.13 | 0.00 | 0.00 |
February | 560.70 | 1370.55 | 838.53 | 297.61 | 540.92 | 0.00 | 0.00 |
March | 1046.75 | 1151.76 | 1251.98 | 453.23 | 798.75 | 0.00 | 0.00 |
April | 1954.53 | 950.04 | 1940.78 | 806.42 | 1134.36 | 0.00 | 0.00 |
May | 2178.65 | 814.63 | 2065.16 | 718.01 | 1347.15 | 0.00 | 0.00 |
June | 2793.77 | 651.41 | 2473.26 | 1076.14 | 1397.13 | 0.00 | 0.00 |
July | 2721.23 | 575.44 | 2303.18 | 1033.80 | 1269.38 | 0.00 | 0.00 |
August | 2768.71 | 561.56 | 2263.71 | 1132.44 | 1131.27 | 0.00 | 0.00 |
September | 1829.07 | 789.10 | 1673.68 | 771.92 | 901.76 | 0.00 | 0.00 |
October | 1003.76 | 1012.84 | 1090.90 | 463.53 | 627.37 | 0.00 | 0.00 |
November | 297.50 | 1250.14 | 534.70 | 150.95 | 383.75 | 0.00 | 0.00 |
December | 215.65 | 1564.94 | 438.57 | 141.19 | 297.38 | 0.00 | 0.00 |
Annual Sum or Average | 1466.39 | 1019.00 | 1446.95 | 598.07 | 848.88 | 0.00 | 0.00 |
Minimum of Months | 171.23 | 561.56 | 438.57 | 115.86 | 297.38 | 0.00 | 0.00 |
Maximum of Months | 2793.77 | 1564.94 | 2473.26 | 1132.44 | 1397.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1673.27 | 2253.45 | 1884.84 | 1119.22 | 765.61 | 0.00 | 0.00 |
February | 2933.63 | 2063.49 | 2898.59 | 1794.27 | 1104.32 | 0.00 | 0.00 |
March | 3290.62 | 1817.28 | 3118.04 | 1662.82 | 1455.23 | 0.00 | 0.00 |
April | 3669.97 | 1566.85 | 3292.06 | 1429.40 | 1862.67 | 0.00 | 0.00 |
May | 3382.37 | 1317.58 | 3010.17 | 896.76 | 2113.41 | 0.00 | 0.00 |
June | 3150.31 | 1054.80 | 2754.01 | 739.42 | 2014.59 | 0.00 | 0.00 |
July | 3797.03 | 961.72 | 3003.37 | 1099.99 | 1903.38 | 0.00 | 0.00 |
August | 4224.34 | 931.63 | 3226.74 | 1504.68 | 1722.06 | 0.00 | 0.00 |
September | 4404.73 | 1278.85 | 3575.10 | 1974.29 | 1600.81 | 0.00 | 0.00 |
October | 3655.93 | 1605.70 | 3238.43 | 1999.49 | 1238.94 | 0.00 | 0.00 |
November | 1830.60 | 1885.59 | 1914.67 | 1097.27 | 817.40 | 0.00 | 0.00 |
December | 1961.65 | 2314.41 | 2003.29 | 1296.41 | 706.88 | 0.00 | 0.00 |
Annual Sum or Average | 3165.35 | 1585.25 | 2825.39 | 1381.95 | 1443.44 | 0.00 | 0.00 |
Minimum of Months | 1673.27 | 931.63 | 1884.84 | 739.42 | 706.88 | 0.00 | 0.00 |
Maximum of Months | 4404.73 | 2314.41 | 3575.10 | 1999.49 | 2113.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 206.04 | 1620.89 | 482.01 | 142.14 | 339.87 | 0.00 | 0.00 |
February | 603.64 | 1452.28 | 864.20 | 324.79 | 539.41 | 0.00 | 0.00 |
March | 1003.69 | 1234.41 | 1210.97 | 408.74 | 802.24 | 0.00 | 0.00 |
April | 1829.97 | 1048.12 | 1842.36 | 704.41 | 1137.96 | 0.00 | 0.00 |
May | 2577.09 | 890.62 | 2370.69 | 963.08 | 1407.61 | 0.00 | 0.00 |
June | 2527.85 | 711.60 | 2279.96 | 885.23 | 1394.72 | 0.00 | 0.00 |
July | 3430.55 | 666.32 | 2816.58 | 1480.54 | 1336.04 | 0.00 | 0.00 |
August | 2881.32 | 648.21 | 2329.98 | 1189.76 | 1140.23 | 0.00 | 0.00 |
September | 2164.42 | 874.93 | 1897.41 | 910.42 | 986.99 | 0.00 | 0.00 |
October | 993.68 | 1098.11 | 1080.20 | 440.13 | 640.07 | 0.00 | 0.00 |
November | 298.61 | 1328.32 | 537.94 | 151.72 | 386.21 | 0.00 | 0.00 |
December | 244.22 | 1659.26 | 452.24 | 154.97 | 297.27 | 0.00 | 0.00 |
Annual Sum or Average | 1569.76 | 1101.11 | 1517.67 | 648.79 | 868.89 | 0.00 | 0.00 |
Minimum of Months | 206.04 | 648.21 | 452.24 | 142.14 | 297.27 | 0.00 | 0.00 |
Maximum of Months | 3430.55 | 1659.26 | 2816.58 | 1480.54 | 1407.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 12039003.00 | 0.828731E+10 | 0.114260E+10 | 0.00 | 0.114260E+10 | 0.00 | 0.00 |
February | 0.194247E+09 | 0.662508E+10 | 0.160586E+10 | 0.00 | 0.160586E+10 | 0.00 | 0.00 |
March | 0.875835E+09 | 0.597312E+10 | 0.261948E+10 | 0.00 | 0.261948E+10 | 0.00 | 0.00 |
April | 0.211104E+10 | 0.452832E+10 | 0.358726E+10 | 12725085.96 | 0.357453E+10 | 0.00 | 0.00 |
May | 0.374652E+10 | 0.358377E+10 | 0.476976E+10 | 0.141703E+09 | 0.462806E+10 | 0.00 | 0.00 |
June | 0.426036E+10 | 0.266404E+10 | 0.485350E+10 | 0.320505E+09 | 0.453300E+10 | 0.00 | 0.00 |
July | 0.474933E+10 | 0.247365E+10 | 0.476675E+10 | 0.373736E+09 | 0.439302E+10 | 0.00 | 0.00 |
August | 0.389606E+10 | 0.242232E+10 | 0.385872E+10 | 0.104313E+09 | 0.375441E+10 | 0.00 | 0.00 |
September | 0.213349E+10 | 0.355825E+10 | 0.290063E+10 | 855351.23 | 0.289977E+10 | 0.00 | 0.00 |
October | 0.759683E+09 | 0.523142E+10 | 0.205366E+10 | 0.00 | 0.205366E+10 | 0.00 | 0.00 |
November | 93969370.75 | 0.669701E+10 | 0.125188E+10 | 0.00 | 0.125188E+10 | 0.00 | 0.00 |
December | 2409000.72 | 0.858356E+10 | 0.970916E+09 | 0.00 | 0.970916E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.228350E+11 | 0.606279E+11 | 0.343810E+11 | 0.953837E+09 | 0.334272E+11 | 0.00 | 0.00 |
Minimum of Months | 2409000.72 | 0.242232E+10 | 0.970916E+09 | 0.00 | 0.970916E+09 | 0.00 | 0.00 |
Maximum of Months | 0.474933E+10 | 0.858356E+10 | 0.485350E+10 | 0.373736E+09 | 0.462806E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.369196E+09 | 0.518050E+10 | 0.122400E+10 | 0.310324E+09 | 0.913673E+09 | 0.00 | 0.00 |
February | 0.118466E+10 | 0.406134E+10 | 0.202857E+10 | 0.719982E+09 | 0.130859E+10 | 0.00 | 0.00 |
March | 0.264328E+10 | 0.369405E+10 | 0.335331E+10 | 0.121393E+10 | 0.213938E+10 | 0.00 | 0.00 |
April | 0.497687E+10 | 0.280209E+10 | 0.503052E+10 | 0.209025E+10 | 0.294027E+10 | 0.00 | 0.00 |
May | 0.580789E+10 | 0.238386E+10 | 0.553135E+10 | 0.192312E+10 | 0.360823E+10 | 0.00 | 0.00 |
June | 0.729147E+10 | 0.178743E+10 | 0.641073E+10 | 0.278935E+10 | 0.362137E+10 | 0.00 | 0.00 |
July | 0.733668E+10 | 0.161065E+10 | 0.616887E+10 | 0.276895E+10 | 0.339993E+10 | 0.00 | 0.00 |
August | 0.747006E+10 | 0.155459E+10 | 0.606314E+10 | 0.303313E+10 | 0.303001E+10 | 0.00 | 0.00 |
September | 0.471001E+10 | 0.225994E+10 | 0.433820E+10 | 0.200081E+10 | 0.233738E+10 | 0.00 | 0.00 |
October | 0.254523E+10 | 0.327348E+10 | 0.292188E+10 | 0.124153E+10 | 0.168036E+10 | 0.00 | 0.00 |
November | 0.641752E+09 | 0.414825E+10 | 0.138595E+10 | 0.391267E+09 | 0.994681E+09 | 0.00 | 0.00 |
December | 0.477540E+09 | 0.527223E+10 | 0.117468E+10 | 0.378165E+09 | 0.796517E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.454546E+11 | 0.380284E+11 | 0.456312E+11 | 0.188608E+11 | 0.267704E+11 | 0.00 | 0.00 |
Minimum of Months | 0.369196E+09 | 0.155459E+10 | 0.117468E+10 | 0.310324E+09 | 0.796517E+09 | 0.00 | 0.00 |
Maximum of Months | 0.747006E+10 | 0.527223E+10 | 0.641073E+10 | 0.303313E+10 | 0.362137E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.431474E+10 | 0.705310E+10 | 0.504836E+10 | 0.299774E+10 | 0.205062E+10 | 0.00 | 0.00 |
February | 0.691517E+10 | 0.576838E+10 | 0.701229E+10 | 0.434070E+10 | 0.267159E+10 | 0.00 | 0.00 |
March | 0.870396E+10 | 0.561230E+10 | 0.835140E+10 | 0.445371E+10 | 0.389769E+10 | 0.00 | 0.00 |
April | 0.945118E+10 | 0.455863E+10 | 0.853306E+10 | 0.370501E+10 | 0.482805E+10 | 0.00 | 0.00 |
May | 0.907693E+10 | 0.381274E+10 | 0.806247E+10 | 0.240189E+10 | 0.566058E+10 | 0.00 | 0.00 |
June | 0.821262E+10 | 0.292730E+10 | 0.713842E+10 | 0.191658E+10 | 0.522185E+10 | 0.00 | 0.00 |
July | 0.102360E+11 | 0.273680E+10 | 0.804425E+10 | 0.294623E+10 | 0.509802E+10 | 0.00 | 0.00 |
August | 0.113765E+11 | 0.264336E+10 | 0.864254E+10 | 0.403016E+10 | 0.461238E+10 | 0.00 | 0.00 |
September | 0.114324E+11 | 0.357048E+10 | 0.926669E+10 | 0.511737E+10 | 0.414932E+10 | 0.00 | 0.00 |
October | 0.971437E+10 | 0.492501E+10 | 0.867385E+10 | 0.535546E+10 | 0.331839E+10 | 0.00 | 0.00 |
November | 0.455662E+10 | 0.586993E+10 | 0.496284E+10 | 0.284413E+10 | 0.211872E+10 | 0.00 | 0.00 |
December | 0.507797E+10 | 0.739850E+10 | 0.536564E+10 | 0.347232E+10 | 0.189332E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.990685E+11 | 0.568765E+11 | 0.891018E+11 | 0.435813E+11 | 0.455205E+11 | 0.00 | 0.00 |
Minimum of Months | 0.431474E+10 | 0.264336E+10 | 0.496284E+10 | 0.191658E+10 | 0.189332E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114324E+11 | 0.739850E+10 | 0.926669E+10 | 0.535546E+10 | 0.566058E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.462446E+09 | 0.561424E+10 | 0.129102E+10 | 0.380698E+09 | 0.910321E+09 | 0.00 | 0.00 |
February | 0.128660E+10 | 0.458937E+10 | 0.209069E+10 | 0.785741E+09 | 0.130495E+10 | 0.00 | 0.00 |
March | 0.246926E+10 | 0.429901E+10 | 0.324348E+10 | 0.109476E+10 | 0.214872E+10 | 0.00 | 0.00 |
April | 0.452388E+10 | 0.341795E+10 | 0.477542E+10 | 0.182583E+10 | 0.294960E+10 | 0.00 | 0.00 |
May | 0.685418E+10 | 0.269478E+10 | 0.634969E+10 | 0.257953E+10 | 0.377015E+10 | 0.00 | 0.00 |
June | 0.650425E+10 | 0.211925E+10 | 0.590967E+10 | 0.229453E+10 | 0.361514E+10 | 0.00 | 0.00 |
July | 0.914621E+10 | 0.206343E+10 | 0.754395E+10 | 0.396548E+10 | 0.357846E+10 | 0.00 | 0.00 |
August | 0.763100E+10 | 0.206161E+10 | 0.624065E+10 | 0.318666E+10 | 0.305399E+10 | 0.00 | 0.00 |
September | 0.555555E+10 | 0.258847E+10 | 0.491812E+10 | 0.235982E+10 | 0.255830E+10 | 0.00 | 0.00 |
October | 0.248191E+10 | 0.377543E+10 | 0.289323E+10 | 0.117885E+10 | 0.171438E+10 | 0.00 | 0.00 |
November | 0.627538E+09 | 0.478757E+10 | 0.139433E+10 | 0.393260E+09 | 0.100107E+10 | 0.00 | 0.00 |
December | 0.550977E+09 | 0.620203E+10 | 0.121128E+10 | 0.415075E+09 | 0.796205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.480938E+11 | 0.442131E+11 | 0.478615E+11 | 0.204602E+11 | 0.274013E+11 | 0.00 | 0.00 |
Minimum of Months | 0.462446E+09 | 0.206161E+10 | 0.121128E+10 | 0.380698E+09 | 0.796205E+09 | 0.00 | 0.00 |
Maximum of Months | 0.914621E+10 | 0.620203E+10 | 0.754395E+10 | 0.396548E+10 | 0.377015E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 39270307.70 | 0.699811E+10 | 0.114260E+10 | 0.00 | 0.114260E+10 | 0.00 | 0.00 |
February | 0.309934E+09 | 0.565242E+10 | 0.160585E+10 | 0.00 | 0.160585E+10 | 0.00 | 0.00 |
March | 0.106981E+10 | 0.519971E+10 | 0.261947E+10 | 0.00 | 0.261947E+10 | 0.00 | 0.00 |
April | 0.230661E+10 | 0.400732E+10 | 0.358724E+10 | 12725040.77 | 0.357452E+10 | 0.00 | 0.00 |
May | 0.384555E+10 | 0.335727E+10 | 0.476974E+10 | 0.141702E+09 | 0.462804E+10 | 0.00 | 0.00 |
June | 0.433407E+10 | 0.250075E+10 | 0.485348E+10 | 0.320504E+09 | 0.453298E+10 | 0.00 | 0.00 |
July | 0.483813E+10 | 0.231379E+10 | 0.476673E+10 | 0.373735E+09 | 0.439300E+10 | 0.00 | 0.00 |
August | 0.398734E+10 | 0.226834E+10 | 0.385871E+10 | 0.104312E+09 | 0.375439E+10 | 0.00 | 0.00 |
September | 0.220843E+10 | 0.330885E+10 | 0.290062E+10 | 855348.19 | 0.289976E+10 | 0.00 | 0.00 |
October | 0.913659E+09 | 0.457566E+10 | 0.205365E+10 | 0.00 | 0.205365E+10 | 0.00 | 0.00 |
November | 0.165946E+09 | 0.558770E+10 | 0.125187E+10 | 0.00 | 0.125187E+10 | 0.00 | 0.00 |
December | 18261836.02 | 0.711967E+10 | 0.970912E+09 | 0.00 | 0.970912E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.240370E+11 | 0.528896E+11 | 0.343809E+11 | 0.953833E+09 | 0.334270E+11 | 0.00 | 0.00 |
Minimum of Months | 18261836.02 | 0.226834E+10 | 0.970912E+09 | 0.00 | 0.970912E+09 | 0.00 | 0.00 |
Maximum of Months | 0.483813E+10 | 0.711967E+10 | 0.485348E+10 | 0.373735E+09 | 0.462804E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.425843E+09 | 0.443889E+10 | 0.122399E+10 | 0.310323E+09 | 0.913670E+09 | 0.00 | 0.00 |
February | 0.127928E+10 | 0.360436E+10 | 0.202856E+10 | 0.719979E+09 | 0.130858E+10 | 0.00 | 0.00 |
March | 0.269328E+10 | 0.337575E+10 | 0.335330E+10 | 0.121392E+10 | 0.213937E+10 | 0.00 | 0.00 |
April | 0.498760E+10 | 0.262313E+10 | 0.503050E+10 | 0.209025E+10 | 0.294025E+10 | 0.00 | 0.00 |
May | 0.578704E+10 | 0.228494E+10 | 0.553133E+10 | 0.192312E+10 | 0.360821E+10 | 0.00 | 0.00 |
June | 0.723417E+10 | 0.173492E+10 | 0.641070E+10 | 0.278934E+10 | 0.362136E+10 | 0.00 | 0.00 |
July | 0.728754E+10 | 0.157079E+10 | 0.616885E+10 | 0.276893E+10 | 0.339991E+10 | 0.00 | 0.00 |
August | 0.741030E+10 | 0.154166E+10 | 0.606311E+10 | 0.303312E+10 | 0.303000E+10 | 0.00 | 0.00 |
September | 0.469218E+10 | 0.216625E+10 | 0.433818E+10 | 0.200081E+10 | 0.233737E+10 | 0.00 | 0.00 |
October | 0.258803E+10 | 0.299281E+10 | 0.292187E+10 | 0.124152E+10 | 0.168035E+10 | 0.00 | 0.00 |
November | 0.700671E+09 | 0.362287E+10 | 0.138594E+10 | 0.391265E+09 | 0.994677E+09 | 0.00 | 0.00 |
December | 0.531677E+09 | 0.457313E+10 | 0.117468E+10 | 0.378163E+09 | 0.796514E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.456176E+11 | 0.345295E+11 | 0.456310E+11 | 0.188607E+11 | 0.267703E+11 | 0.00 | 0.00 |
Minimum of Months | 0.425843E+09 | 0.154166E+10 | 0.117468E+10 | 0.310323E+09 | 0.796514E+09 | 0.00 | 0.00 |
Maximum of Months | 0.741030E+10 | 0.457313E+10 | 0.641070E+10 | 0.303312E+10 | 0.362136E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.438849E+10 | 0.647354E+10 | 0.504835E+10 | 0.299773E+10 | 0.205062E+10 | 0.00 | 0.00 |
February | 0.696833E+10 | 0.541367E+10 | 0.701227E+10 | 0.434069E+10 | 0.267158E+10 | 0.00 | 0.00 |
March | 0.870382E+10 | 0.529633E+10 | 0.835137E+10 | 0.445369E+10 | 0.389768E+10 | 0.00 | 0.00 |
April | 0.944083E+10 | 0.431477E+10 | 0.853303E+10 | 0.370499E+10 | 0.482803E+10 | 0.00 | 0.00 |
May | 0.902470E+10 | 0.369959E+10 | 0.806244E+10 | 0.240188E+10 | 0.566056E+10 | 0.00 | 0.00 |
June | 0.817616E+10 | 0.281856E+10 | 0.713840E+10 | 0.191657E+10 | 0.522183E+10 | 0.00 | 0.00 |
July | 0.101995E+11 | 0.263061E+10 | 0.804422E+10 | 0.294622E+10 | 0.509800E+10 | 0.00 | 0.00 |
August | 0.113365E+11 | 0.256065E+10 | 0.864250E+10 | 0.403014E+10 | 0.461236E+10 | 0.00 | 0.00 |
September | 0.113801E+11 | 0.349423E+10 | 0.926665E+10 | 0.511735E+10 | 0.414930E+10 | 0.00 | 0.00 |
October | 0.968388E+10 | 0.469742E+10 | 0.867382E+10 | 0.535544E+10 | 0.331838E+10 | 0.00 | 0.00 |
November | 0.461760E+10 | 0.541564E+10 | 0.496282E+10 | 0.284412E+10 | 0.211871E+10 | 0.00 | 0.00 |
December | 0.515136E+10 | 0.675534E+10 | 0.536562E+10 | 0.347230E+10 | 0.189331E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.990714E+11 | 0.535703E+11 | 0.891015E+11 | 0.435811E+11 | 0.455203E+11 | 0.00 | 0.00 |
Minimum of Months | 0.438849E+10 | 0.256065E+10 | 0.496282E+10 | 0.191657E+10 | 0.189331E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113801E+11 | 0.675534E+10 | 0.926665E+10 | 0.535544E+10 | 0.566056E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.527010E+09 | 0.462359E+10 | 0.129101E+10 | 0.380696E+09 | 0.910317E+09 | 0.00 | 0.00 |
February | 0.141424E+10 | 0.376525E+10 | 0.209068E+10 | 0.785738E+09 | 0.130495E+10 | 0.00 | 0.00 |
March | 0.262275E+10 | 0.356564E+10 | 0.324347E+10 | 0.109476E+10 | 0.214871E+10 | 0.00 | 0.00 |
April | 0.469682E+10 | 0.287224E+10 | 0.477540E+10 | 0.182582E+10 | 0.294958E+10 | 0.00 | 0.00 |
May | 0.688899E+10 | 0.248888E+10 | 0.634966E+10 | 0.257952E+10 | 0.377014E+10 | 0.00 | 0.00 |
June | 0.656717E+10 | 0.189867E+10 | 0.590965E+10 | 0.229452E+10 | 0.361513E+10 | 0.00 | 0.00 |
July | 0.921876E+10 | 0.182362E+10 | 0.754391E+10 | 0.396547E+10 | 0.357845E+10 | 0.00 | 0.00 |
August | 0.773760E+10 | 0.177815E+10 | 0.624062E+10 | 0.318664E+10 | 0.305398E+10 | 0.00 | 0.00 |
September | 0.559275E+10 | 0.237852E+10 | 0.491810E+10 | 0.235981E+10 | 0.255829E+10 | 0.00 | 0.00 |
October | 0.259709E+10 | 0.319381E+10 | 0.289322E+10 | 0.117885E+10 | 0.171437E+10 | 0.00 | 0.00 |
November | 0.728577E+09 | 0.376434E+10 | 0.139433E+10 | 0.393258E+09 | 0.100107E+10 | 0.00 | 0.00 |
December | 0.628590E+09 | 0.478310E+10 | 0.121128E+10 | 0.415073E+09 | 0.796202E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.492203E+11 | 0.369358E+11 | 0.478613E+11 | 0.204602E+11 | 0.274012E+11 | 0.00 | 0.00 |
Minimum of Months | 0.527010E+09 | 0.177815E+10 | 0.121128E+10 | 0.380696E+09 | 0.796202E+09 | 0.00 | 0.00 |
Maximum of Months | 0.921876E+10 | 0.478310E+10 | 0.754391E+10 | 0.396547E+10 | 0.377014E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 57933719.12 | 0.656680E+10 | 0.114260E+10 | 0.00 | 0.114260E+10 | 0.00 | 0.00 |
February | 0.367794E+09 | 0.522110E+10 | 0.160585E+10 | 0.00 | 0.160585E+10 | 0.00 | 0.00 |
March | 0.119498E+10 | 0.474776E+10 | 0.261947E+10 | 0.00 | 0.261947E+10 | 0.00 | 0.00 |
April | 0.241467E+10 | 0.374023E+10 | 0.358724E+10 | 12725040.77 | 0.357452E+10 | 0.00 | 0.00 |
May | 0.391901E+10 | 0.319161E+10 | 0.476974E+10 | 0.141702E+09 | 0.462804E+10 | 0.00 | 0.00 |
June | 0.434859E+10 | 0.242564E+10 | 0.485348E+10 | 0.320504E+09 | 0.453298E+10 | 0.00 | 0.00 |
July | 0.482527E+10 | 0.226307E+10 | 0.476673E+10 | 0.373735E+09 | 0.439300E+10 | 0.00 | 0.00 |
August | 0.399016E+10 | 0.220512E+10 | 0.385871E+10 | 0.104312E+09 | 0.375439E+10 | 0.00 | 0.00 |
September | 0.227351E+10 | 0.310609E+10 | 0.290062E+10 | 855348.19 | 0.289976E+10 | 0.00 | 0.00 |
October | 0.104044E+10 | 0.412694E+10 | 0.205365E+10 | 0.00 | 0.205365E+10 | 0.00 | 0.00 |
November | 0.222952E+09 | 0.500605E+10 | 0.125187E+10 | 0.00 | 0.125187E+10 | 0.00 | 0.00 |
December | 37579386.66 | 0.653144E+10 | 0.970912E+09 | 0.00 | 0.970912E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.246929E+11 | 0.491318E+11 | 0.343809E+11 | 0.953833E+09 | 0.334270E+11 | 0.00 | 0.00 |
Minimum of Months | 37579386.66 | 0.220512E+10 | 0.970912E+09 | 0.00 | 0.970912E+09 | 0.00 | 0.00 |
Maximum of Months | 0.482527E+10 | 0.656680E+10 | 0.485348E+10 | 0.373735E+09 | 0.462804E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.458629E+09 | 0.416635E+10 | 0.122399E+10 | 0.310323E+09 | 0.913670E+09 | 0.00 | 0.00 |
February | 0.135645E+10 | 0.331565E+10 | 0.202856E+10 | 0.719979E+09 | 0.130858E+10 | 0.00 | 0.00 |
March | 0.280361E+10 | 0.308487E+10 | 0.335330E+10 | 0.121392E+10 | 0.213937E+10 | 0.00 | 0.00 |
April | 0.506615E+10 | 0.246249E+10 | 0.503050E+10 | 0.209025E+10 | 0.294025E+10 | 0.00 | 0.00 |
May | 0.583530E+10 | 0.218190E+10 | 0.553133E+10 | 0.192312E+10 | 0.360821E+10 | 0.00 | 0.00 |
June | 0.724144E+10 | 0.168845E+10 | 0.641070E+10 | 0.278934E+10 | 0.362136E+10 | 0.00 | 0.00 |
July | 0.728854E+10 | 0.154125E+10 | 0.616885E+10 | 0.276893E+10 | 0.339991E+10 | 0.00 | 0.00 |
August | 0.741570E+10 | 0.150408E+10 | 0.606311E+10 | 0.303312E+10 | 0.303000E+10 | 0.00 | 0.00 |
September | 0.474094E+10 | 0.204535E+10 | 0.433818E+10 | 0.200081E+10 | 0.233737E+10 | 0.00 | 0.00 |
October | 0.268847E+10 | 0.271279E+10 | 0.292187E+10 | 0.124152E+10 | 0.168035E+10 | 0.00 | 0.00 |
November | 0.771131E+09 | 0.324037E+10 | 0.138594E+10 | 0.391265E+09 | 0.994677E+09 | 0.00 | 0.00 |
December | 0.577601E+09 | 0.419154E+10 | 0.117468E+10 | 0.378163E+09 | 0.796514E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.462439E+11 | 0.321351E+11 | 0.456310E+11 | 0.188607E+11 | 0.267703E+11 | 0.00 | 0.00 |
Minimum of Months | 0.458629E+09 | 0.150408E+10 | 0.117468E+10 | 0.310323E+09 | 0.796514E+09 | 0.00 | 0.00 |
Maximum of Months | 0.741570E+10 | 0.419154E+10 | 0.641070E+10 | 0.303312E+10 | 0.362136E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.448169E+10 | 0.603565E+10 | 0.504835E+10 | 0.299773E+10 | 0.205062E+10 | 0.00 | 0.00 |
February | 0.709704E+10 | 0.499199E+10 | 0.701227E+10 | 0.434069E+10 | 0.267158E+10 | 0.00 | 0.00 |
March | 0.881360E+10 | 0.486741E+10 | 0.835137E+10 | 0.445369E+10 | 0.389768E+10 | 0.00 | 0.00 |
April | 0.951256E+10 | 0.406128E+10 | 0.853303E+10 | 0.370499E+10 | 0.482803E+10 | 0.00 | 0.00 |
May | 0.905933E+10 | 0.352900E+10 | 0.806244E+10 | 0.240188E+10 | 0.566056E+10 | 0.00 | 0.00 |
June | 0.816560E+10 | 0.273404E+10 | 0.713840E+10 | 0.191657E+10 | 0.522183E+10 | 0.00 | 0.00 |
July | 0.101700E+11 | 0.257587E+10 | 0.804422E+10 | 0.294622E+10 | 0.509800E+10 | 0.00 | 0.00 |
August | 0.113145E+11 | 0.249527E+10 | 0.864250E+10 | 0.403014E+10 | 0.461236E+10 | 0.00 | 0.00 |
September | 0.114171E+11 | 0.331477E+10 | 0.926665E+10 | 0.511735E+10 | 0.414930E+10 | 0.00 | 0.00 |
October | 0.979205E+10 | 0.430070E+10 | 0.867382E+10 | 0.535544E+10 | 0.331838E+10 | 0.00 | 0.00 |
November | 0.474491E+10 | 0.488745E+10 | 0.496282E+10 | 0.284412E+10 | 0.211871E+10 | 0.00 | 0.00 |
December | 0.525409E+10 | 0.619893E+10 | 0.536562E+10 | 0.347230E+10 | 0.189331E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.998224E+11 | 0.499923E+11 | 0.891015E+11 | 0.435811E+11 | 0.455203E+11 | 0.00 | 0.00 |
Minimum of Months | 0.448169E+10 | 0.249527E+10 | 0.496282E+10 | 0.191657E+10 | 0.189331E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114171E+11 | 0.619893E+10 | 0.926665E+10 | 0.535544E+10 | 0.566056E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.551848E+09 | 0.434140E+10 | 0.129101E+10 | 0.380696E+09 | 0.910317E+09 | 0.00 | 0.00 |
February | 0.146034E+10 | 0.351337E+10 | 0.209068E+10 | 0.785738E+09 | 0.130495E+10 | 0.00 | 0.00 |
March | 0.268829E+10 | 0.330624E+10 | 0.324347E+10 | 0.109476E+10 | 0.214871E+10 | 0.00 | 0.00 |
April | 0.474329E+10 | 0.271673E+10 | 0.477540E+10 | 0.182582E+10 | 0.294958E+10 | 0.00 | 0.00 |
May | 0.690247E+10 | 0.238545E+10 | 0.634966E+10 | 0.257952E+10 | 0.377014E+10 | 0.00 | 0.00 |
June | 0.655219E+10 | 0.184448E+10 | 0.590965E+10 | 0.229452E+10 | 0.361513E+10 | 0.00 | 0.00 |
July | 0.918838E+10 | 0.178466E+10 | 0.754391E+10 | 0.396547E+10 | 0.357845E+10 | 0.00 | 0.00 |
August | 0.771732E+10 | 0.173616E+10 | 0.624062E+10 | 0.318664E+10 | 0.305398E+10 | 0.00 | 0.00 |
September | 0.561019E+10 | 0.226782E+10 | 0.491810E+10 | 0.235981E+10 | 0.255829E+10 | 0.00 | 0.00 |
October | 0.266148E+10 | 0.294117E+10 | 0.289322E+10 | 0.117885E+10 | 0.171437E+10 | 0.00 | 0.00 |
November | 0.773988E+09 | 0.344300E+10 | 0.139433E+10 | 0.393258E+09 | 0.100107E+10 | 0.00 | 0.00 |
December | 0.654123E+09 | 0.444415E+10 | 0.121128E+10 | 0.415073E+09 | 0.796202E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.495039E+11 | 0.347246E+11 | 0.478613E+11 | 0.204602E+11 | 0.274012E+11 | 0.00 | 0.00 |
Minimum of Months | 0.551848E+09 | 0.173616E+10 | 0.121128E+10 | 0.380696E+09 | 0.796202E+09 | 0.00 | 0.00 |
Maximum of Months | 0.918838E+10 | 0.444415E+10 | 0.754391E+10 | 0.396547E+10 | 0.377014E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.388310E+11 | -0.378001E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103092E+10 | 58.98 | 0.00 | 0.00 |
February | 0.355180E+11 | -0.345885E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -929482509.7 | 58.98 | 0.00 | 0.00 |
March | 0.412576E+11 | -0.402290E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102867E+10 | 58.97 | 0.00 | 0.00 |
April | 0.364610E+11 | -0.354699E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991131717.8 | 58.98 | 0.00 | 0.00 |
May | 0.374903E+11 | -0.364649E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102542E+10 | 58.98 | 0.00 | 0.00 |
June | 0.357758E+11 | -0.347835E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992266786.7 | 58.97 | 0.00 | 0.00 |
July | 0.331699E+11 | -0.321499E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102003E+10 | 58.98 | 0.00 | 0.00 |
August | 0.359273E+11 | -0.349030E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102428E+10 | 58.98 | 0.00 | 0.00 |
September | 0.330778E+11 | -0.320881E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989692500.1 | 58.98 | 0.00 | 0.00 |
October | 0.351831E+11 | -0.341608E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102233E+10 | 58.98 | 0.00 | 0.00 |
November | 0.358528E+11 | -0.348628E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989999292.2 | 58.97 | 0.00 | 0.00 |
December | 0.370089E+11 | -0.359840E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102494E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.435553E+12 | -0.423484E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120692E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.330778E+11 | -0.402290E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.103092E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.412576E+11 | -0.320881E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -929482509.7 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.50 | 0.48 | 01-JAN-09:39 | 2756.62 | 32.57 | 224.33 | 219.67 | 2173.73 | 33.68 | 226.67 | 187.33 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:30 | 4688.14 | 33.54 | 245.83 | 244.00 | 2034.17 | 29.26 | 224.33 | 218.83 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7763.86 | 33.51 | 209.67 | 313.00 | 1660.48 | 22.71 | 204.00 | 267.83 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:00 | 2218.16 | 20.35 | 170.67 | 345.33 | 1212.63 | 21.77 | 250.00 | 308.17 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 2038.95 | 20.20 | 160.83 | 386.00 | 1100.56 | 21.58 | 278.17 | 344.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:00 | 1789.61 | 19.74 | 112.33 | 396.33 | 1017.01 | 21.15 | 265.83 | 346.17 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:30 | 1590.99 | 18.58 | 117.17 | 395.50 | 923.34 | 19.97 | 191.67 | 340.83 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 1879.74 | 19.63 | 117.00 | 374.50 | 1111.35 | 21.04 | 209.17 | 328.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3010.85 | 22.37 | 143.67 | 320.17 | 1461.86 | 22.54 | 226.00 | 288.17 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:49 | 7206.81 | 34.96 | 224.33 | 285.00 | 1937.98 | 23.90 | 187.17 | 256.17 |
November | 242.67 | 0.50 | 0.48 | 01-NOV-08:09 | 3072.27 | 32.12 | 226.83 | 225.17 | 2440.53 | 33.30 | 230.50 | 193.67 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3700.35 | 35.79 | 149.50 | 207.33 | 3110.51 | 37.05 | 149.67 | 167.00 |
Annual Sum or Average | 3714.00 | 0.51 | 3130.76 | 25.12 | 2102.17 | 3712.00 | 1512.29 | 24.35 | 2643.17 | 3246.67 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1590.99 | 18.58 | 112.33 | 207.33 | 923.34 | 19.97 | 149.67 | 167.00 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7763.86 | 35.79 | 245.83 | 396.33 | 3110.51 | 37.05 | 278.17 | 346.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-09:50 | 933.44 | 21.20 | 70.33 | 200.50 | 572.67 | 22.53 | 94.00 | 132.00 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:30 | 1524.18 | 23.19 | 98.50 | 228.67 | 793.55 | 23.33 | 136.00 | 181.83 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 2743.39 | 25.62 | 117.17 | 304.17 | 1198.53 | 24.50 | 158.50 | 255.83 |
April | 379.50 | 0.50 | 0.48 | 01-APR-06:19 | 2863.42 | 24.33 | 148.33 | 347.83 | 1592.66 | 24.70 | 229.17 | 308.50 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2943.71 | 23.64 | 160.67 | 391.50 | 1283.58 | 23.41 | 248.00 | 351.83 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:10 | 3095.30 | 23.54 | 107.33 | 404.17 | 1694.29 | 23.99 | 208.33 | 359.00 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2908.98 | 23.76 | 170.33 | 410.83 | 1315.22 | 23.34 | 221.17 | 373.33 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3385.51 | 24.42 | 127.50 | 379.50 | 1472.71 | 23.72 | 177.50 | 340.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2778.60 | 24.19 | 99.33 | 323.83 | 1541.04 | 24.53 | 163.67 | 286.33 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2516.40 | 25.23 | 108.83 | 272.00 | 1100.58 | 24.04 | 139.33 | 227.00 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1158.69 | 22.44 | 87.83 | 208.33 | 601.01 | 22.59 | 93.33 | 146.83 |
December | 160.33 | 0.52 | 0.48 | 01-DEC-09:39 | 1093.97 | 23.41 | 64.83 | 185.83 | 586.52 | 23.34 | 71.50 | 107.67 |
Annual Sum or Average | 3714.00 | 0.51 | 2510.69 | 23.80 | 1361.00 | 3657.17 | 1228.01 | 23.71 | 1940.50 | 3070.50 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 933.44 | 21.20 | 64.83 | 185.83 | 572.67 | 22.53 | 71.50 | 107.67 | |
Maximum of Months | 471.00 | 0.52 | 0.48 | 3385.51 | 25.62 | 170.33 | 410.83 | 1694.29 | 24.70 | 248.00 | 373.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 02-JAN-10:50 | 506.54 | 16.03 | 0.00 | 179.67 | 275.32 | 17.36 | 0.00 | 53.67 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:20 | 644.35 | 17.21 | 0.00 | 215.50 | 363.52 | 18.62 | 1.50 | 131.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:09 | 870.97 | 18.63 | 0.00 | 298.67 | 514.77 | 20.08 | 68.17 | 217.67 |
April | 379.50 | 0.50 | 0.48 | 01-APR-07:10 | 1020.91 | 19.31 | 0.50 | 349.00 | 590.14 | 20.65 | 162.00 | 302.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1253.28 | 21.40 | 93.50 | 399.67 | 717.49 | 22.13 | 273.67 | 365.33 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:19 | 1332.20 | 22.47 | 125.83 | 413.83 | 756.05 | 22.46 | 261.67 | 380.50 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1124.24 | 21.62 | 126.83 | 423.50 | 645.66 | 21.55 | 230.67 | 378.00 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 976.04 | 19.35 | 15.33 | 388.83 | 608.15 | 20.70 | 131.33 | 345.50 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 948.85 | 19.41 | 0.00 | 314.17 | 574.27 | 20.84 | 101.33 | 256.83 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:09 | 707.02 | 17.69 | 0.00 | 260.67 | 426.98 | 19.21 | 13.17 | 170.67 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-09:00 | 545.83 | 16.34 | 0.00 | 193.17 | 296.72 | 17.63 | 0.17 | 69.17 |
December | 160.33 | 0.56 | 0.48 | 01-DEC-09:00 | 475.05 | 16.03 | 0.00 | 155.33 | 276.36 | 17.62 | 0.00 | 40.83 |
Annual Sum or Average | 3714.00 | 0.51 | 937.39 | 19.33 | 362.00 | 3592.00 | 544.60 | 20.32 | 1243.67 | 2711.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 475.05 | 16.03 | 0.00 | 155.33 | 275.32 | 17.36 | 0.00 | 40.83 | |
Maximum of Months | 471.00 | 0.56 | 0.48 | 1332.20 | 22.47 | 126.83 | 423.50 | 756.05 | 22.46 | 273.67 | 380.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-10:30 | 1062.71 | 22.55 | 87.33 | 201.83 | 564.79 | 22.66 | 94.67 | 138.50 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-09:20 | 1509.03 | 23.16 | 95.00 | 232.17 | 773.63 | 23.23 | 126.17 | 184.33 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-08:09 | 2398.88 | 24.40 | 112.33 | 306.67 | 1279.64 | 24.59 | 152.17 | 253.50 |
April | 379.50 | 0.50 | 0.48 | 01-APR-07:30 | 2867.28 | 23.20 | 133.67 | 345.83 | 1250.08 | 22.64 | 208.17 | 308.67 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:19 | 2973.53 | 20.76 | 88.17 | 392.67 | 1589.77 | 20.96 | 222.83 | 357.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:10 | 3033.87 | 20.34 | 51.83 | 403.50 | 1367.81 | 20.72 | 188.83 | 363.17 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:00 | 3326.90 | 19.59 | 75.50 | 405.00 | 1457.75 | 19.65 | 156.50 | 363.83 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-06:19 | 3174.65 | 22.00 | 92.83 | 383.83 | 1823.04 | 22.69 | 160.50 | 345.67 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3510.48 | 25.44 | 124.67 | 316.50 | 1949.38 | 25.50 | 180.33 | 273.83 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-08:20 | 2420.89 | 25.91 | 116.33 | 274.50 | 1075.29 | 24.69 | 153.17 | 228.00 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-09:39 | 1128.96 | 22.03 | 79.17 | 210.17 | 588.37 | 22.11 | 91.33 | 142.83 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:00 | 1115.30 | 22.55 | 55.67 | 185.83 | 590.02 | 22.54 | 66.00 | 103.50 |
Annual Sum or Average | 3714.00 | 0.51 | 2576.83 | 22.35 | 1112.50 | 3658.50 | 1282.23 | 22.38 | 1800.67 | 3063.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1062.71 | 19.59 | 51.83 | 185.83 | 564.79 | 19.65 | 66.00 | 103.50 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3510.48 | 25.91 | 133.67 | 405.00 | 1949.38 | 25.50 | 222.83 | 363.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.50 | 0.48 | 01-JAN-09:39 | 2760.85 | 31.99 | 220.33 | 219.67 | 2235.21 | 33.12 | 221.33 | 190.33 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:30 | 4711.16 | 32.96 | 238.83 | 244.50 | 2126.80 | 27.47 | 156.50 | 223.17 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7803.57 | 32.30 | 208.50 | 313.00 | 1771.56 | 17.99 | 8.50 | 272.00 |
April | 379.50 | 0.50 | 0.48 | 01-APR-06:00 | 2248.24 | 13.83 | 0.00 | 345.67 | 1295.51 | 17.29 | 0.67 | 312.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 2063.76 | 13.83 | 0.00 | 386.33 | 1173.44 | 17.24 | 0.00 | 349.50 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:49 | 1820.97 | 13.70 | 0.00 | 396.50 | 1086.63 | 17.11 | 0.00 | 351.50 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:19 | 1623.42 | 12.32 | 0.00 | 396.33 | 988.91 | 15.77 | 0.00 | 348.00 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 1922.77 | 13.42 | 0.00 | 374.67 | 1193.48 | 16.94 | 1.33 | 333.00 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3057.54 | 16.44 | 27.00 | 320.33 | 1567.48 | 18.15 | 11.17 | 291.83 |
October | 245.33 | 0.50 | 0.48 | 01-OCT-07:49 | 7248.74 | 34.05 | 220.33 | 285.00 | 2048.55 | 19.37 | 26.17 | 258.67 |
November | 242.67 | 0.50 | 0.48 | 01-NOV-07:00 | 3084.69 | 31.49 | 221.67 | 225.50 | 2503.98 | 32.76 | 226.17 | 197.00 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3717.24 | 34.96 | 149.17 | 207.67 | 3198.07 | 36.43 | 149.67 | 171.00 |
Annual Sum or Average | 3714.00 | 0.51 | 3160.84 | 20.93 | 1285.83 | 3715.17 | 1594.20 | 20.86 | 801.50 | 3298.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1623.42 | 12.32 | 0.00 | 207.67 | 988.91 | 15.77 | 0.00 | 171.00 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7803.57 | 34.96 | 238.83 | 396.50 | 3198.07 | 36.43 | 226.17 | 351.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-09:50 | 949.57 | 18.35 | 61.33 | 202.17 | 596.49 | 20.65 | 71.33 | 137.83 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:30 | 1550.38 | 20.50 | 81.17 | 230.17 | 829.80 | 21.28 | 61.67 | 188.17 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 2791.73 | 23.13 | 91.50 | 304.67 | 1257.06 | 22.33 | 51.50 | 260.50 |
April | 379.50 | 0.50 | 0.48 | 01-APR-06:19 | 2913.28 | 21.51 | 118.33 | 348.83 | 1657.09 | 22.52 | 91.67 | 313.50 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2986.18 | 20.40 | 132.67 | 392.83 | 1348.11 | 20.93 | 79.50 | 356.50 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-04:00 | 3145.62 | 20.40 | 98.83 | 405.33 | 1772.28 | 21.56 | 73.67 | 364.17 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2950.12 | 20.05 | 148.50 | 411.00 | 1380.03 | 20.90 | 99.33 | 379.17 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3440.35 | 21.54 | 116.33 | 380.50 | 1545.34 | 21.19 | 66.50 | 345.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2832.24 | 21.34 | 84.33 | 324.17 | 1604.96 | 22.31 | 61.50 | 290.00 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2556.25 | 22.88 | 93.33 | 273.17 | 1152.05 | 22.00 | 58.00 | 232.00 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1177.86 | 19.78 | 78.83 | 210.17 | 627.75 | 20.54 | 62.83 | 154.33 |
December | 160.33 | 0.52 | 0.48 | 01-DEC-09:39 | 1112.43 | 21.01 | 56.33 | 186.67 | 613.49 | 21.60 | 52.67 | 114.17 |
Annual Sum or Average | 3714.00 | 0.51 | 2551.51 | 20.86 | 1161.50 | 3669.67 | 1284.74 | 21.46 | 830.17 | 3135.67 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 949.57 | 18.35 | 56.33 | 186.67 | 596.49 | 20.54 | 51.50 | 114.17 | |
Maximum of Months | 471.00 | 0.52 | 0.48 | 3440.35 | 23.13 | 148.50 | 411.00 | 1772.28 | 22.52 | 99.33 | 379.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.54 | 0.48 | 02-JAN-10:39 | 511.49 | 9.50 | 0.00 | 180.00 | 292.01 | 12.98 | 0.00 | 67.50 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-09:09 | 652.10 | 11.06 | 0.00 | 216.33 | 386.04 | 14.56 | 0.00 | 142.17 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:09 | 884.58 | 12.96 | 0.00 | 298.83 | 547.55 | 16.43 | 0.00 | 228.83 |
April | 379.50 | 0.50 | 0.48 | 01-APR-07:10 | 1037.32 | 13.66 | 0.00 | 349.00 | 628.06 | 17.06 | 0.00 | 309.67 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1289.72 | 16.17 | 39.00 | 399.67 | 767.94 | 19.32 | 44.67 | 371.00 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:19 | 1357.26 | 17.80 | 60.17 | 414.17 | 830.52 | 20.87 | 62.00 | 388.33 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1151.12 | 16.75 | 78.00 | 424.00 | 717.63 | 19.88 | 80.00 | 389.33 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 1017.74 | 13.88 | 0.00 | 391.83 | 648.60 | 17.44 | 0.50 | 354.00 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 964.69 | 14.15 | 0.00 | 314.83 | 611.52 | 17.60 | 0.00 | 264.83 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:09 | 717.51 | 12.07 | 0.00 | 261.67 | 454.17 | 15.60 | 0.00 | 186.50 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-08:30 | 551.46 | 9.86 | 0.00 | 193.33 | 314.81 | 13.29 | 0.00 | 83.00 |
December | 160.33 | 0.56 | 0.48 | 01-DEC-09:00 | 479.56 | 9.78 | 0.00 | 156.00 | 293.19 | 13.49 | 0.00 | 51.00 |
Annual Sum or Average | 3714.00 | 0.51 | 957.63 | 13.81 | 177.17 | 3599.67 | 586.48 | 17.17 | 187.17 | 2836.17 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 479.56 | 9.50 | 0.00 | 156.00 | 292.01 | 12.98 | 0.00 | 51.00 | |
Maximum of Months | 471.00 | 0.56 | 0.48 | 1357.26 | 17.80 | 78.00 | 424.00 | 830.52 | 20.87 | 80.00 | 389.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-10:20 | 1080.07 | 19.99 | 79.17 | 203.67 | 589.73 | 20.70 | 64.17 | 145.17 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-09:20 | 1524.12 | 19.33 | 66.50 | 232.17 | 810.96 | 21.15 | 59.67 | 190.00 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-08:09 | 2436.52 | 21.61 | 78.17 | 307.50 | 1335.36 | 22.54 | 59.83 | 258.00 |
April | 379.50 | 0.50 | 0.48 | 01-APR-07:19 | 2915.14 | 20.19 | 105.33 | 346.50 | 1311.99 | 20.01 | 51.00 | 313.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:19 | 3009.64 | 16.83 | 52.17 | 392.83 | 1660.94 | 17.67 | 0.00 | 360.83 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:00 | 3080.87 | 16.45 | 42.83 | 404.00 | 1439.81 | 17.45 | 0.00 | 367.33 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:49 | 3375.83 | 15.57 | 58.83 | 406.33 | 1533.28 | 16.25 | 3.67 | 367.50 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-06:10 | 3208.24 | 18.52 | 75.83 | 384.00 | 1900.01 | 19.93 | 50.17 | 350.17 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3546.00 | 22.41 | 100.50 | 316.67 | 2024.72 | 23.30 | 76.83 | 279.67 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-08:20 | 2431.61 | 22.21 | 89.83 | 275.00 | 1127.09 | 22.70 | 64.50 | 232.33 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-08:30 | 1148.08 | 19.30 | 70.50 | 211.50 | 615.39 | 20.00 | 52.17 | 149.50 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:50 | 1133.58 | 19.89 | 48.67 | 186.50 | 616.83 | 20.65 | 45.33 | 110.83 |
Annual Sum or Average | 3714.00 | 0.51 | 2610.44 | 18.94 | 868.33 | 3666.67 | 1341.57 | 19.76 | 527.33 | 3124.50 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1080.07 | 15.57 | 42.83 | 186.50 | 589.73 | 16.25 | 0.00 | 110.83 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3546.00 | 22.41 | 105.33 | 406.33 | 2024.72 | 23.30 | 76.83 | 367.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.50 | 0.48 | 01-JAN-09:39 | 2762.01 | 31.99 | 220.33 | 219.67 | 2236.67 | 33.12 | 221.33 | 190.33 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:30 | 4712.94 | 32.95 | 238.83 | 244.50 | 2128.86 | 27.46 | 156.50 | 223.17 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7806.60 | 32.29 | 208.50 | 313.33 | 1774.13 | 17.97 | 8.50 | 272.17 |
April | 379.50 | 0.50 | 0.48 | 01-APR-06:00 | 2251.62 | 13.80 | 0.00 | 345.67 | 1297.60 | 17.28 | 0.67 | 312.50 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 2067.02 | 13.80 | 0.00 | 386.83 | 1175.35 | 17.23 | 0.00 | 349.67 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:49 | 1823.49 | 13.67 | 0.00 | 396.67 | 1088.20 | 17.10 | 0.00 | 351.83 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:19 | 1625.64 | 12.29 | 0.00 | 396.33 | 990.27 | 15.75 | 0.00 | 348.17 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 1925.22 | 13.39 | 0.00 | 374.83 | 1195.06 | 16.93 | 1.33 | 333.00 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3060.64 | 16.42 | 27.00 | 320.33 | 1569.76 | 18.13 | 11.00 | 291.83 |
October | 245.33 | 0.50 | 0.48 | 01-OCT-07:49 | 7250.69 | 34.04 | 220.33 | 285.00 | 2050.89 | 19.36 | 26.17 | 258.83 |
November | 242.67 | 0.50 | 0.48 | 01-NOV-07:00 | 3085.97 | 31.49 | 221.50 | 225.50 | 2505.63 | 32.76 | 226.17 | 197.33 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3717.99 | 34.95 | 149.17 | 207.83 | 3199.53 | 36.42 | 149.67 | 171.17 |
Annual Sum or Average | 3714.00 | 0.51 | 3163.23 | 20.90 | 1285.67 | 3716.50 | 1596.04 | 20.84 | 801.33 | 3300.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1625.64 | 12.29 | 0.00 | 207.83 | 990.27 | 15.75 | 0.00 | 171.17 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7806.60 | 34.95 | 238.83 | 396.67 | 3199.53 | 36.42 | 226.17 | 351.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-09:50 | 950.55 | 18.33 | 61.33 | 202.33 | 597.30 | 20.64 | 71.33 | 138.33 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:30 | 1551.59 | 20.47 | 81.00 | 230.33 | 830.85 | 21.26 | 61.50 | 188.17 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 2793.39 | 23.10 | 91.50 | 304.67 | 1258.52 | 22.32 | 51.33 | 260.83 |
April | 379.50 | 0.50 | 0.48 | 01-APR-06:19 | 2890.27 | 20.41 | 105.17 | 348.50 | 1658.69 | 22.50 | 91.67 | 313.67 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2988.57 | 20.37 | 132.50 | 393.17 | 1349.81 | 20.92 | 79.50 | 356.83 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-04:00 | 3147.66 | 20.37 | 98.83 | 405.33 | 1773.97 | 21.55 | 73.67 | 364.17 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2951.80 | 20.03 | 148.50 | 411.00 | 1381.35 | 20.89 | 99.33 | 379.33 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3441.77 | 21.51 | 116.33 | 380.50 | 1546.74 | 21.17 | 66.50 | 345.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2829.19 | 21.11 | 82.67 | 324.00 | 1606.36 | 22.30 | 61.33 | 290.17 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2517.97 | 21.42 | 83.00 | 273.33 | 1153.20 | 21.99 | 57.67 | 232.17 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1178.93 | 19.76 | 78.83 | 210.17 | 628.62 | 20.53 | 62.67 | 154.83 |
December | 160.33 | 0.52 | 0.48 | 01-DEC-09:39 | 1113.15 | 20.99 | 56.33 | 186.67 | 614.26 | 21.59 | 52.50 | 114.17 |
Annual Sum or Average | 3714.00 | 0.51 | 2547.57 | 20.62 | 1136.00 | 3670.00 | 1286.08 | 21.45 | 829.00 | 3138.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 950.55 | 18.33 | 56.33 | 186.67 | 597.30 | 20.53 | 51.33 | 114.17 | |
Maximum of Months | 471.00 | 0.52 | 0.48 | 3441.77 | 23.10 | 148.50 | 411.00 | 1773.97 | 22.50 | 99.33 | 379.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.54 | 0.48 | 02-JAN-10:39 | 512.19 | 9.47 | 0.00 | 180.33 | 292.50 | 12.97 | 0.00 | 68.00 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-09:09 | 652.89 | 11.03 | 0.00 | 216.33 | 386.64 | 14.54 | 0.00 | 142.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:09 | 885.47 | 12.92 | 0.00 | 298.83 | 548.30 | 16.42 | 0.00 | 229.17 |
April | 379.50 | 0.50 | 0.48 | 01-APR-07:10 | 1038.47 | 13.63 | 0.00 | 349.00 | 628.96 | 17.05 | 0.00 | 310.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1291.25 | 16.14 | 39.00 | 400.00 | 769.05 | 19.30 | 44.50 | 371.00 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:19 | 1358.51 | 17.77 | 60.17 | 414.17 | 831.56 | 20.86 | 62.00 | 388.33 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1152.22 | 16.73 | 78.00 | 424.00 | 718.51 | 19.86 | 79.83 | 389.33 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 1018.58 | 13.85 | 0.00 | 391.83 | 649.37 | 17.42 | 0.50 | 354.00 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 965.55 | 14.12 | 0.00 | 314.83 | 612.31 | 17.59 | 0.00 | 265.33 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:09 | 718.14 | 12.04 | 0.00 | 262.00 | 454.76 | 15.59 | 0.00 | 186.83 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-08:30 | 552.22 | 9.84 | 0.00 | 193.33 | 315.34 | 13.28 | 0.00 | 83.33 |
December | 160.33 | 0.56 | 0.48 | 01-DEC-09:00 | 480.01 | 9.75 | 0.00 | 156.17 | 293.61 | 13.47 | 0.00 | 51.33 |
Annual Sum or Average | 3714.00 | 0.51 | 958.61 | 13.78 | 177.17 | 3600.83 | 587.27 | 17.16 | 186.83 | 2839.33 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 480.01 | 9.47 | 0.00 | 156.17 | 292.50 | 12.97 | 0.00 | 51.33 | |
Maximum of Months | 471.00 | 0.56 | 0.48 | 1358.51 | 17.77 | 78.00 | 424.00 | 831.56 | 20.86 | 79.83 | 389.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-10:20 | 1081.04 | 19.97 | 79.17 | 203.83 | 590.53 | 20.69 | 63.83 | 145.33 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-09:20 | 1525.32 | 19.31 | 66.50 | 232.33 | 812.01 | 21.14 | 59.33 | 190.33 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-08:09 | 2438.13 | 21.58 | 78.17 | 307.67 | 1336.84 | 22.53 | 59.67 | 258.67 |
April | 379.50 | 0.50 | 0.48 | 01-APR-07:19 | 2917.08 | 20.16 | 105.33 | 346.50 | 1313.60 | 19.99 | 51.00 | 313.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:19 | 3012.06 | 16.80 | 52.17 | 392.83 | 1662.78 | 17.65 | 0.00 | 361.17 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:00 | 3082.91 | 16.42 | 42.83 | 404.00 | 1441.48 | 17.44 | 0.00 | 367.50 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:40 | 3377.59 | 15.54 | 58.83 | 406.33 | 1534.72 | 16.23 | 3.67 | 367.67 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-06:10 | 3209.68 | 18.49 | 75.83 | 384.00 | 1901.43 | 19.92 | 50.17 | 350.50 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3547.73 | 22.38 | 100.50 | 316.67 | 2026.45 | 23.29 | 76.83 | 280.00 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-08:20 | 2432.72 | 22.19 | 89.83 | 275.00 | 1128.29 | 22.69 | 64.50 | 232.33 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-08:30 | 1149.15 | 19.27 | 70.50 | 211.50 | 616.26 | 19.99 | 52.00 | 150.00 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:50 | 1134.27 | 19.87 | 48.67 | 186.67 | 617.59 | 20.63 | 45.17 | 111.00 |
Annual Sum or Average | 3714.00 | 0.51 | 2612.06 | 18.91 | 868.33 | 3667.33 | 1342.97 | 19.75 | 526.17 | 3127.67 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1081.04 | 15.54 | 42.83 | 186.67 | 590.53 | 16.23 | 0.00 | 111.00 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3547.73 | 22.38 | 105.33 | 406.33 | 2026.45 | 23.29 | 76.83 | 367.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118327E+11 | 28135.11 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.712041E+10 | 23935.44 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191280E+10 | 21005.77 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.596915E+09 | 15442.48 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.293448E+09 | 9110.60 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6935.42 | 0.89 | 26-JUN-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5421.70 | 1.05 | 31-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8744.09 | 1.06 | 23-AUG-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24204261.33 | 3683.01 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.342293E+09 | 7551.95 | 13-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316360E+10 | 19417.87 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.643592E+10 | 25125.41 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5421.70 | 0.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118327E+11 | 28135.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 43678886.75 | 10847.94 | 09-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2240158.97 | 530.05 | 18-FEB-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45919045.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43678886.75 | 10847.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 55497624.83 | 10990.99 | 09-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10526832.56 | 4676.64 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1652498.66 | 279.31 | 22-DEC-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67676956.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55497624.83 | 10990.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.245965E+09 | 17803.66 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 61538010.82 | 17623.17 | 14-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1617064.82 | 2583.63 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5531185.74 | 4259.38 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 42367842.52 | 17671.70 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.357019E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.245965E+09 | 17803.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.158273E+12 | 296488.74 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101080E+12 | 253032.87 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.499299E+11 | 211831.74 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223008E+11 | 178768.62 | 05-APR-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587917E+10 | 225303.83 | 17-MAY-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.333127E+09 | 184628.82 | 13-JUN-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 47828053.91 | 99459.39 | 12-JUL-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34591935.83 | 115306.45 | 03-AUG-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.890333E+09 | 186020.30 | 27-SEP-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104294E+11 | 144210.72 | 19-OCT-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.717920E+11 | 205959.61 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129996E+12 | 272532.36 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 34591935.83 | 99459.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.158273E+12 | 296488.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126655E+11 | 445475.57 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.332776E+09 | 440053.15 | 21-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.349007E+09 | 439658.21 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126655E+11 | 445475.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.351943E+11 | 111961.44 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165045E+11 | 111470.92 | 21-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401364E+10 | 119854.22 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.948467E+09 | 120255.10 | 20-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31362314.47 | 71703.35 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135056E+10 | 110623.43 | 30-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.984397E+10 | 111647.08 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240046E+11 | 111907.04 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.918914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.351943E+11 | 120255.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.203777E+11 | 163756.06 | 24-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.871652E+10 | 163728.55 | 13-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192667E+10 | 162932.38 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.422451E+09 | 133120.15 | 18-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29510041.84 | 63400.32 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.800032E+09 | 155327.34 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.585606E+10 | 163219.40 | 13-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139757E+11 | 163768.55 | 21-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.521047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.203777E+11 | 163768.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.236779E+11 | 235039.33 | 04-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.889673E+10 | 234468.79 | 21-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206127E+10 | 233971.85 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.642741E+09 | 186567.00 | 18-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 46273170.58 | 92697.53 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.697103E+09 | 198056.20 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.616544E+10 | 234135.25 | 27-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160520E+11 | 235035.30 | 20-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.582395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.236779E+11 | 235039.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152116E+11 | 161970.02 | 03-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.566907E+10 | 161843.94 | 21-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111539E+10 | 161292.63 | 06-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.206887E+09 | 75172.04 | 18-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10369882.97 | 33319.83 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.321452E+09 | 96914.78 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.343409E+10 | 161274.40 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.894657E+10 | 161907.48 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152116E+11 | 161970.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.174833E+11 | 33615.06 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117522E+11 | 30083.52 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.677008E+10 | 24212.39 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.315581E+10 | 19474.14 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.931808E+09 | 12409.43 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 52471794.48 | 4241.84 | 15-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.169927E+09 | 7102.91 | 27-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201145E+10 | 12466.70 | 16-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.893370E+10 | 24658.94 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151196E+11 | 30481.98 | 26-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.663804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.174833E+11 | 33615.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.680823E+10 | 70152.91 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.323821E+10 | 69842.52 | 21-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.637617E+09 | 70116.46 | 06-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25881601.04 | 4545.46 | 17-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.253104E+09 | 69332.33 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219765E+10 | 70186.61 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.472858E+10 | 70103.66 | 11-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.680823E+10 | 70186.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.673683E+10 | 12661.25 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.432505E+10 | 12653.84 | 01-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197484E+10 | 12665.87 | 06-MAR-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.717899E+09 | 12590.68 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111545E+09 | 12518.77 | 20-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10253442.78 | 9494.70 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 47001013.02 | 12569.81 | 28-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106016E+10 | 12604.52 | 30-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324874E+10 | 12665.50 | 27-NOV-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.570536E+10 | 12667.47 | 16-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.673683E+10 | 12667.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.418140E+10 | 18186.08 | 30-JAN-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.240660E+10 | 18209.15 | 06-FEB-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.977619E+09 | 18190.10 | 06-MAR-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.327559E+09 | 18175.78 | 11-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 65316500.43 | 15132.04 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7363489.47 | 7469.34 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23239545.45 | 13813.54 | 27-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.568412E+09 | 18199.67 | 30-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197493E+10 | 18213.43 | 24-NOV-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.349397E+10 | 18204.08 | 11-DEC-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.418140E+10 | 18213.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.486059E+10 | 26986.51 | 30-JAN-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264393E+10 | 26997.14 | 14-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128166E+10 | 26992.63 | 06-MAR-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.548133E+09 | 26971.20 | 11-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111133E+09 | 25119.29 | 11-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11729012.13 | 8971.54 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29883585.57 | 13930.72 | 27-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.646914E+09 | 26911.49 | 21-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.235842E+10 | 27026.93 | 24-NOV-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.411331E+10 | 26995.55 | 27-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.486059E+10 | 27026.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.314515E+10 | 18898.93 | 18-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164211E+10 | 18869.39 | 22-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.684926E+09 | 18870.33 | 06-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.233685E+09 | 18818.22 | 11-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38869344.76 | 14330.76 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 670762.47 | 1017.85 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6785256.41 | 916.29 | 27-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.341945E+09 | 18830.01 | 23-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130537E+10 | 18879.93 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233619E+10 | 18907.92 | 27-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.973569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.314515E+10 | 18907.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 70.70 | 0.71 | 09-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 249.98 | 0.81 | 15-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 395.62 | 0.80 | 18-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 260.07 | 0.76 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 115.21 | 0.96 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1091.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 395.62 | 0.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.223800E+09 | 0.223800E+09 | 12160.15 | 20-JAN-13:40 | 12160.15 | 0.00 |
February | 0.00 | 0.00 | 0.349521E+10 | 0.349521E+10 | 50132.69 | 27-FEB-15:00 | 50132.69 | 0.01 |
March | 0.00 | 0.00 | 0.457988E+10 | 0.457988E+10 | 53634.64 | 02-MAR-14:05 | 53634.64 | 0.03 |
April | 0.00 | 0.00 | 0.985621E+10 | 0.985621E+10 | 113512.40 | 27-APR-14:40 | 113512.40 | 0.05 |
May | 0.00 | 0.00 | 0.147860E+11 | 0.147820E+11 | 90325.05 | 04-MAY-15:00 | 90325.05 | 0.16 |
June | 0.00 | 0.00 | 0.291490E+11 | 0.291425E+11 | 101336.36 | 28-JUN-15:20 | 101336.36 | 0.33 |
July | 0.00 | 0.00 | 0.539283E+11 | 0.532572E+11 | 134170.48 | 31-JUL-15:50 | 117179.71 | 0.53 |
August | 0.00 | 0.00 | 0.736125E+11 | 0.716115E+11 | 142152.16 | 29-AUG-14:30 | 124869.45 | 0.66 |
September | 0.00 | 0.00 | 0.230622E+11 | 0.227683E+11 | 117333.08 | 11-SEP-15:35 | 114827.27 | 0.34 |
October | 0.00 | 0.00 | 0.508775E+10 | 0.508775E+10 | 70545.16 | 04-OCT-15:00 | 70545.16 | 0.06 |
November | 0.00 | 0.00 | 0.331856E+10 | 0.331856E+10 | 35557.42 | 15-NOV-14:00 | 35557.42 | 0.03 |
December | 0.00 | 0.00 | 0.399675E+10 | 0.399675E+10 | 39478.94 | 05-DEC-14:40 | 39478.94 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.225096E+12 | 0.222120E+12 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.223800E+09 | 0.223800E+09 | 12160.15 | 12160.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.736125E+11 | 0.716115E+11 | 142152.16 | 124869.45 | 0.66 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 15669.10 | 15669.10 | 1.43 | 09-JAN-05:01 | 1.43 | 0.00 |
February | 0.00 | 0.00 | 0.652955E+10 | 0.652955E+10 | 433328.68 | 27-FEB-15:05 | 433328.68 | 0.01 |
March | 0.00 | 0.00 | 0.369237E+11 | 0.369237E+11 | 438531.99 | 14-MAR-15:50 | 438531.99 | 0.02 |
April | 0.00 | 0.00 | 0.852310E+11 | 0.852310E+11 | 957056.69 | 27-APR-14:40 | 957056.69 | 0.06 |
May | 0.00 | 0.00 | 0.136074E+12 | 0.136054E+12 | 854075.74 | 04-MAY-15:00 | 854075.74 | 0.17 |
June | 0.00 | 0.00 | 0.240837E+12 | 0.240813E+12 | 908871.81 | 28-JUN-15:20 | 908871.81 | 0.33 |
July | 0.00 | 0.00 | 0.423535E+12 | 0.419837E+12 | 1171546.20 | 31-JUL-16:00 | 1002660.16 | 0.48 |
August | 0.00 | 0.00 | 0.564049E+12 | 0.550605E+12 | 1248019.42 | 29-AUG-14:30 | 1089098.53 | 0.53 |
September | 0.00 | 0.00 | 0.216387E+12 | 0.212678E+12 | 976656.24 | 14-SEP-13:00 | 722084.19 | 0.35 |
October | 0.00 | 0.00 | 0.664380E+11 | 0.664380E+11 | 641210.11 | 03-OCT-15:20 | 641210.11 | 0.08 |
November | 0.00 | 0.00 | 0.734221E+10 | 0.734221E+10 | 379519.21 | 04-NOV-14:05 | 379519.21 | 0.02 |
December | 0.00 | 0.00 | 19689.31 | 19689.31 | 2.54 | 26-DEC-06:02 | 2.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.178335E+13 | 0.176245E+13 | 0.17 | |||
Minimum of Months | 0.00 | 0.00 | 15669.10 | 15669.10 | 1.43 | 1.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.564049E+12 | 0.550605E+12 | 1248019.42 | 1089098.53 | 0.53 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 35402.48 | 35402.48 | 139.91 | 09-JAN-04:06 | 139.91 | 0.00 |
February | 0.00 | 0.00 | 0.357279E+09 | 0.357279E+09 | 25802.35 | 27-FEB-15:00 | 25802.35 | 0.01 |
March | 0.00 | 0.00 | 0.844453E+09 | 0.844453E+09 | 24720.18 | 01-MAR-15:00 | 24720.18 | 0.01 |
April | 0.00 | 0.00 | 0.707092E+10 | 0.707092E+10 | 112185.31 | 27-APR-14:40 | 112185.31 | 0.04 |
May | 0.00 | 0.00 | 0.131420E+11 | 0.131390E+11 | 94281.16 | 04-MAY-15:00 | 94281.16 | 0.15 |
June | 0.00 | 0.00 | 0.249215E+11 | 0.249198E+11 | 109389.52 | 28-JUN-15:20 | 109389.52 | 0.31 |
July | 0.00 | 0.00 | 0.452653E+11 | 0.449182E+11 | 136071.67 | 31-JUL-16:00 | 118240.76 | 0.46 |
August | 0.00 | 0.00 | 0.591592E+11 | 0.579159E+11 | 139414.56 | 10-AUG-15:40 | 128572.80 | 0.51 |
September | 0.00 | 0.00 | 0.200373E+11 | 0.198124E+11 | 104130.89 | 11-SEP-15:32 | 104130.89 | 0.32 |
October | 0.00 | 0.00 | 0.274691E+10 | 0.274691E+10 | 60492.44 | 04-OCT-15:00 | 60492.44 | 0.04 |
November | 0.00 | 0.00 | 0.488363E+09 | 0.488363E+09 | 29057.60 | 04-NOV-14:10 | 29057.60 | 0.01 |
December | 0.00 | 0.00 | 21794.08 | 21794.08 | 108.97 | 26-DEC-04:50 | 108.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.174033E+12 | 0.172213E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 21794.08 | 21794.08 | 108.97 | 108.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.591592E+11 | 0.579159E+11 | 139414.56 | 128572.80 | 0.51 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1824548.18 | 1824548.18 | 7750.04 | 11-JAN-06:03 | 7750.04 | 0.00 |
February | 0.00 | 0.00 | 0.396869E+09 | 0.391437E+09 | 42461.45 | 24-FEB-06:02 | 29044.00 | 0.00 |
March | 0.00 | 0.00 | 0.103131E+09 | 96743716.39 | 33960.70 | 10-MAR-06:03 | 15477.13 | 0.00 |
April | 0.00 | 0.00 | 0.342650E+10 | 0.342164E+10 | 51353.10 | 27-APR-15:00 | 51353.10 | 0.04 |
May | 0.00 | 0.00 | 0.660191E+10 | 0.658350E+10 | 50902.76 | 15-MAY-16:00 | 50902.76 | 0.11 |
June | 0.00 | 0.00 | 0.138357E+11 | 0.137738E+11 | 55512.94 | 12-JUN-04:11 | 29782.51 | 0.22 |
July | 0.00 | 0.00 | 0.266650E+11 | 0.263222E+11 | 73370.83 | 31-JUL-10:10 | 60561.47 | 0.36 |
August | 0.00 | 0.00 | 0.366669E+11 | 0.362621E+11 | 71753.00 | 25-AUG-04:12 | 42854.58 | 0.42 |
September | 0.00 | 0.00 | 0.107371E+11 | 0.105685E+11 | 61482.78 | 11-SEP-15:35 | 61482.78 | 0.22 |
October | 0.00 | 0.00 | 0.139670E+10 | 0.137789E+10 | 36084.03 | 26-OCT-04:13 | 23297.16 | 0.02 |
November | 0.00 | 0.00 | 0.272389E+09 | 0.259961E+09 | 40441.10 | 04-NOV-04:13 | 24424.39 | 0.01 |
December | 0.00 | 0.00 | 4803387.88 | 4462355.55 | 14733.77 | 16-DEC-06:02 | 11891.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.100109E+12 | 0.990641E+11 | 0.12 | |||
Minimum of Months | 0.00 | 0.00 | 1824548.18 | 1824548.18 | 7750.04 | 7750.04 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.366669E+11 | 0.362621E+11 | 73370.83 | 61482.78 | 0.42 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.434107E+10 | 0.434096E+10 | 2990.67 | 09-JAN-12:00 | 2990.67 | 0.00 |
February | 0.00 | 0.00 | 0.692948E+10 | 0.686141E+10 | 39383.88 | 27-FEB-15:00 | 39383.88 | 0.00 |
March | 0.00 | 0.00 | 0.142634E+11 | 0.135376E+11 | 145856.80 | 18-MAR-16:00 | 145856.80 | 0.00 |
April | 0.00 | 0.00 | 0.106410E+12 | 0.974837E+11 | 387557.91 | 27-APR-15:00 | 387557.91 | 0.00 |
May | 0.00 | 0.00 | 0.505115E+10 | 0.475764E+10 | 86272.19 | 05-MAY-16:00 | 74538.59 | 0.00 |
June | 0.00 | 0.00 | 0.414475E+11 | 0.392502E+11 | 209668.85 | 28-JUN-17:00 | 209668.85 | 0.00 |
July | 0.00 | 0.00 | 0.252053E+12 | 0.210174E+12 | 353290.67 | 27-JUL-16:00 | 287460.44 | 0.00 |
August | 0.00 | 0.00 | 0.629787E+12 | 0.486919E+12 | 411681.89 | 29-AUG-13:00 | 357010.69 | 0.00 |
September | 0.00 | 0.00 | 0.454809E+10 | 0.381794E+10 | 88436.61 | 22-SEP-16:00 | 75138.80 | 0.00 |
October | 0.00 | 0.00 | 0.451755E+10 | 0.437877E+10 | 86457.03 | 04-OCT-15:00 | 86457.03 | 0.00 |
November | 0.00 | 0.00 | 0.118086E+11 | 0.982669E+10 | 204532.90 | 04-NOV-14:20 | 153563.50 | 0.00 |
December | 0.00 | 0.00 | 0.140011E+11 | 0.128368E+11 | 52001.60 | 14-DEC-12:00 | 50551.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.109516E+13 | 0.894185E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.434107E+10 | 0.381794E+10 | 2990.67 | 2990.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.629787E+12 | 0.486919E+12 | 411681.89 | 387557.91 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.382204E+10 | 0.382170E+10 | 2096.49 | 08-JAN-16:15 | 2096.49 | 0.00 |
February | 0.00 | 0.00 | 0.861254E+10 | 0.860210E+10 | 4406.38 | 12-FEB-16:45 | 4406.38 | 0.00 |
March | 0.00 | 0.00 | 0.151254E+11 | 0.151169E+11 | 7525.01 | 31-MAR-24:00 | 7525.01 | 0.00 |
April | 0.00 | 0.00 | 0.198651E+11 | 0.198516E+11 | 8638.60 | 23-APR-18:20 | 8638.60 | 0.00 |
May | 0.00 | 0.00 | 0.545127E+10 | 0.541473E+10 | 3977.30 | 31-MAY-24:00 | 3968.98 | 0.00 |
June | 0.00 | 0.00 | 0.104138E+11 | 0.103603E+11 | 5861.17 | 30-JUN-24:00 | 5855.08 | 0.00 |
July | 0.00 | 0.00 | 0.161619E+11 | 0.160461E+11 | 7827.94 | 31-JUL-23:55 | 7800.25 | 0.00 |
August | 0.00 | 0.00 | 0.211707E+11 | 0.210147E+11 | 9187.18 | 06-AUG-19:06 | 9187.18 | 0.00 |
September | 0.00 | 0.00 | 0.545766E+10 | 0.536696E+10 | 3854.65 | 30-SEP-24:00 | 3853.49 | 0.00 |
October | 0.00 | 0.00 | 0.102624E+11 | 0.102395E+11 | 5546.96 | 31-OCT-24:00 | 5546.96 | 0.00 |
November | 0.00 | 0.00 | 0.145429E+11 | 0.145190E+11 | 6360.75 | 11-NOV-16:05 | 6360.75 | 0.00 |
December | 0.00 | 0.00 | 0.198830E+11 | 0.198805E+11 | 8161.98 | 10-DEC-15:40 | 8161.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150769E+12 | 0.150234E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.382204E+10 | 0.382170E+10 | 2096.49 | 2096.49 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.211707E+11 | 0.210147E+11 | 9187.18 | 9187.18 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.100180E+11 | 0.100180E+11 | 14535.71 | 20-JAN-16:20 | 14535.71 | 0.00 |
February | 0.00 | 0.00 | 0.622184E+11 | 0.621170E+11 | 38845.44 | 27-FEB-16:30 | 38604.07 | 0.00 |
March | 0.00 | 0.00 | 0.130176E+12 | 0.130092E+12 | 66579.73 | 31-MAR-23:40 | 66579.73 | 0.00 |
April | 0.00 | 0.00 | 0.180730E+12 | 0.180593E+12 | 81712.53 | 26-APR-18:00 | 81712.53 | 0.00 |
May | 0.00 | 0.00 | 0.459383E+11 | 0.455812E+11 | 37130.46 | 31-MAY-23:40 | 37005.20 | 0.00 |
June | 0.00 | 0.00 | 0.950486E+11 | 0.945196E+11 | 54989.40 | 30-JUN-24:00 | 54924.86 | 0.00 |
July | 0.00 | 0.00 | 0.151290E+12 | 0.150145E+12 | 75232.20 | 31-JUL-23:55 | 74962.51 | 0.00 |
August | 0.00 | 0.00 | 0.199819E+12 | 0.198270E+12 | 86695.44 | 06-AUG-18:32 | 86695.44 | 0.00 |
September | 0.00 | 0.00 | 0.469256E+11 | 0.460407E+11 | 34526.54 | 30-SEP-23:40 | 34505.25 | 0.00 |
October | 0.00 | 0.00 | 0.861219E+11 | 0.858949E+11 | 46125.06 | 31-OCT-24:00 | 46125.06 | 0.00 |
November | 0.00 | 0.00 | 0.119452E+12 | 0.119215E+12 | 57589.40 | 04-NOV-16:02 | 56450.26 | 0.00 |
December | 0.00 | 0.00 | 0.163760E+12 | 0.163735E+12 | 71668.56 | 05-DEC-15:50 | 71668.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.129150E+13 | 0.128622E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.100180E+11 | 0.100180E+11 | 14535.71 | 14535.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.199819E+12 | 0.198270E+12 | 86695.44 | 86695.44 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.289428E+09 | 0.289428E+09 | 1367.30 | 05-JAN-16:20 | 1367.30 | 0.00 |
February | 0.00 | 0.00 | 0.471418E+10 | 0.470418E+10 | 3842.19 | 27-FEB-16:30 | 3817.82 | 0.00 |
March | 0.00 | 0.00 | 0.116540E+11 | 0.116456E+11 | 6144.25 | 31-MAR-23:20 | 6144.25 | 0.00 |
April | 0.00 | 0.00 | 0.172721E+11 | 0.172585E+11 | 8251.96 | 26-APR-18:00 | 8251.96 | 0.00 |
May | 0.00 | 0.00 | 0.408982E+10 | 0.405436E+10 | 3642.32 | 31-MAY-23:20 | 3624.98 | 0.00 |
June | 0.00 | 0.00 | 0.928589E+10 | 0.923294E+10 | 5411.29 | 30-JUN-23:40 | 5404.76 | 0.00 |
July | 0.00 | 0.00 | 0.150083E+11 | 0.148938E+11 | 7489.97 | 31-JUL-23:55 | 7462.87 | 0.00 |
August | 0.00 | 0.00 | 0.198350E+11 | 0.196802E+11 | 8856.28 | 06-AUG-18:32 | 8856.28 | 0.00 |
September | 0.00 | 0.00 | 0.417510E+10 | 0.408794E+10 | 3103.17 | 10-SEP-17:40 | 3089.02 | 0.00 |
October | 0.00 | 0.00 | 0.738463E+10 | 0.736244E+10 | 4499.85 | 04-OCT-16:50 | 4499.85 | 0.00 |
November | 0.00 | 0.00 | 0.102901E+11 | 0.102666E+11 | 5672.25 | 04-NOV-16:02 | 5558.93 | 0.00 |
December | 0.00 | 0.00 | 0.145540E+11 | 0.145515E+11 | 6974.84 | 05-DEC-16:10 | 6974.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.118552E+12 | 0.118027E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.289428E+09 | 0.289428E+09 | 1367.30 | 1367.30 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.198350E+11 | 0.196802E+11 | 8856.28 | 8856.28 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 119582.74 | 1893200.91 | 02-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 71976.00 | 1527405.72 | 16-FEB-05:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 27324.07 | 1442645.70 | 06-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11616.48 | 939686.88 | 18-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 2811.53 | 547852.12 | 18-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 165.09 | 241070.98 | 13-JUN-09:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.33 | 108521.25 | 12-JUL-09:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 14.41 | 128655.81 | 03-AUG-09:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 454.07 | 247325.26 | 27-SEP-09:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7019.05 | 1226863.54 | 28-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 46360.79 | 1480421.24 | 24-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 87734.91 | 1387734.17 | 30-DEC-06:02 |
Annual Sum or Average | 0.00 | 31103.77 | ||||
Minimum of Months | 0.00 | 0.00 | 14.41 | 108521.25 | ||
Maximum of Months | 0.00 | 0.00 | 119582.74 | 1893200.91 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 128.59 | 11082.55 | 11-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 4724.13 | 525936.95 | 27-FEB-15:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 16300.84 | 480563.24 | 14-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 41990.09 | 1491080.21 | 27-APR-12:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 64878.43 | 1118500.35 | 05-MAY-15:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 121967.39 | 1338628.88 | 28-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 212111.53 | 1511026.53 | 31-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 283846.81 | 1590549.41 | 29-AUG-14:30 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 107616.52 | 2120391.72 | 11-SEP-15:32 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 29231.54 | 905723.73 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4752.74 | 454659.14 | 04-NOV-14:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1927.09 | 41850.12 | 05-DEC-14:40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 74748.62 | 0.00 | ||||
Minimum of Months | 128.59 | 11082.55 | 0.00 | 0.00 | ||
Maximum of Months | 283846.81 | 2120391.72 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 44.48 | 12361.13 | 11-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 4451.91 | 570129.13 | 27-FEB-14:40 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 15793.21 | 478847.77 | 14-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 41606.56 | 1276525.27 | 27-APR-12:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 65458.85 | 1441967.52 | 04-MAY-14:05 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 122158.31 | 1575192.59 | 28-JUN-12:40 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 212104.68 | 1708395.29 | 20-JUL-12:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 283635.03 | 1687226.15 | 15-AUG-12:50 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 108907.25 | 2282407.31 | 11-SEP-15:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 28804.31 | 906295.46 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4378.98 | 459277.91 | 04-NOV-14:05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1503.04 | 49657.41 | 16-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 74695.45 | 0.00 | ||||
Minimum of Months | 44.48 | 12361.13 | 0.00 | 0.00 | ||
Maximum of Months | 283635.03 | 2282407.31 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 12426.77 | 27691.82 | 20-JAN-16:20 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 45762.51 | 227542.48 | 27-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 82320.19 | 496509.96 | 18-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 184890.39 | 1342684.08 | 27-APR-15:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 50308.12 | 537427.97 | 05-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 123591.25 | 898091.08 | 28-JUN-17:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 338144.24 | 1350350.04 | 24-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 646823.61 | 1609328.00 | 10-AUG-17:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 56989.34 | 540314.16 | 22-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 54744.93 | 411224.22 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 78167.94 | 624156.48 | 04-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 99389.66 | 164015.73 | 14-DEC-12:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 149039.46 | 0.00 | ||||
Minimum of Months | 12426.77 | 27691.82 | 0.00 | 0.00 | ||
Maximum of Months | 646823.61 | 1609328.00 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 15525.23 | 52044.29 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 15708.60 | 52117.89 | 13-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16427.07 | 51936.17 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15096.85 | 50806.27 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15026.85 | 49250.02 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14828.83 | 47388.78 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 13417.83 | 45717.47 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 14440.76 | 45089.16 | 29-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 13797.29 | 46035.90 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14171.73 | 47784.61 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14865.82 | 49630.74 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14851.32 | 51137.32 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 14841.61 | ||||
Minimum of Months | 0.00 | 0.00 | 13417.83 | 45089.16 | ||
Maximum of Months | 0.00 | 0.00 | 16427.07 | 52117.89 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16.75 | 15988.11 | 30-JAN-11:50 | 819.78 | 89848.53 | 20-JAN-15:50 |
February | 3701.13 | 599438.16 | 27-FEB-15:10 | 2295.65 | 111749.58 | 08-FEB-06:30 |
March | 16342.97 | 552088.78 | 14-MAR-16:00 | 2657.19 | 105477.82 | 24-MAR-09:00 |
April | 50410.89 | 1884793.05 | 27-APR-12:05 | 1086.07 | 89736.35 | 12-APR-08:30 |
May | 76238.09 | 1803926.75 | 05-MAY-13:30 | 587.76 | 77898.97 | 27-MAY-06:00 |
June | 146505.14 | 1920468.31 | 20-JUN-14:40 | 819.24 | 65165.77 | 05-JUN-08:20 |
July | 266639.55 | 2799501.64 | 31-JUL-16:00 | 1087.75 | 67106.52 | 03-JUL-10:00 |
August | 388903.17 | 3185109.20 | 29-AUG-14:30 | 1190.25 | 53262.83 | 19-AUG-21:00 |
September | 132119.97 | 2316422.76 | 11-SEP-15:35 | 568.09 | 53875.17 | 05-SEP-10:00 |
October | 32702.85 | 1032482.49 | 04-OCT-15:00 | 808.85 | 81087.13 | 11-OCT-05:40 |
November | 3965.95 | 522390.95 | 04-NOV-14:10 | 3233.52 | 102107.85 | 24-NOV-06:50 |
December | 232.27 | 35875.72 | 05-DEC-10:30 | 4424.76 | 101742.81 | 21-DEC-06:30 |
Annual Sum or Average | 93991.88 | 1628.36 | ||||
Minimum of Months | 16.75 | 15988.11 | 568.09 | 53262.83 | ||
Maximum of Months | 388903.17 | 3185109.20 | 4424.76 | 111749.58 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.120828E+11 | 0.76 | 8324.04 | 01-JAN-06:15 | 1.41 |
February | 0.110110E+11 | 0.77 | 8324.04 | 01-FEB-05:11 | 1.40 |
March | 0.129738E+11 | 0.82 | 8324.04 | 01-MAR-05:02 | 1.41 |
April | 0.118642E+11 | 0.77 | 8324.04 | 01-APR-04:12 | 1.41 |
May | 0.125934E+11 | 0.79 | 8324.04 | 01-MAY-04:12 | 1.40 |
June | 0.125293E+11 | 0.81 | 8324.04 | 01-JUN-04:12 | 1.41 |
July | 0.122663E+11 | 0.77 | 8324.04 | 01-JUL-04:12 | 1.40 |
August | 0.133609E+11 | 0.84 | 8324.04 | 01-AUG-04:12 | 1.40 |
September | 0.124003E+11 | 0.80 | 8324.04 | 01-SEP-04:12 | 1.40 |
October | 0.124852E+11 | 0.79 | 8324.04 | 02-OCT-04:12 | 1.41 |
November | 0.119392E+11 | 0.78 | 8324.04 | 01-NOV-04:12 | 1.40 |
December | 0.119317E+11 | 0.75 | 8324.04 | 01-DEC-05:11 | 1.41 |
Annual Sum or Average | 0.147438E+12 | 0.79 | |||
Minimum of Months | 0.110110E+11 | 0.75 | 8324.04 | 1.40 | |
Maximum of Months | 0.133609E+11 | 0.84 | 8324.04 | 1.41 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.265526E+10 | 0.28 | 11555.03 | 09-JAN-06:01 | 1.32 |
February | 0.331640E+10 | 0.32 | 11598.65 | 27-FEB-14:50 | 1.31 |
March | 0.555702E+10 | 0.40 | 11505.29 | 14-MAR-14:40 | 1.31 |
April | 0.752836E+10 | 0.48 | 17123.09 | 27-APR-14:40 | 1.67 |
May | 0.676390E+10 | 0.44 | 14583.55 | 15-MAY-14:30 | 1.52 |
June | 0.843789E+10 | 0.51 | 18951.69 | 12-JUN-04:11 | 1.78 |
July | 0.105970E+11 | 0.58 | 18951.69 | 19-JUL-14:50 | 1.79 |
August | 0.123172E+11 | 0.66 | 18951.69 | 07-AUG-14:05 | 1.78 |
September | 0.696938E+10 | 0.44 | 18951.69 | 11-SEP-14:07 | 1.78 |
October | 0.551140E+10 | 0.38 | 13513.49 | 04-OCT-15:20 | 1.45 |
November | 0.402251E+10 | 0.34 | 9299.51 | 07-NOV-06:02 | 1.14 |
December | 0.388115E+10 | 0.32 | 9776.93 | 26-DEC-06:02 | 1.19 |
Annual Sum or Average | 0.775575E+11 | 0.43 | |||
Minimum of Months | 0.265526E+10 | 0.28 | 9299.51 | 1.14 | |
Maximum of Months | 0.123172E+11 | 0.66 | 18951.69 | 1.79 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.219211E+11 | 0.29 | 53515.17 | 02-JAN-05:11 | 0.87 |
February | 0.210091E+11 | 0.29 | 51353.39 | 27-FEB-15:05 | 0.85 |
March | 0.294746E+11 | 0.31 | 115912.02 | 30-MAR-05:02 | 1.39 |
April | 0.367743E+11 | 0.34 | 133330.17 | 27-APR-14:40 | 1.51 |
May | 0.487306E+11 | 0.38 | 124828.76 | 15-MAY-14:05 | 1.45 |
June | 0.571069E+11 | 0.43 | 120385.79 | 28-JUN-14:05 | 1.41 |
July | 0.678852E+11 | 0.45 | 147647.71 | 31-JUL-14:30 | 1.60 |
August | 0.777329E+11 | 0.49 | 161281.59 | 10-AUG-15:00 | 1.70 |
September | 0.532946E+11 | 0.40 | 173527.06 | 11-SEP-14:10 | 1.78 |
October | 0.331538E+11 | 0.31 | 110075.94 | 04-OCT-15:40 | 1.35 |
November | 0.216269E+11 | 0.28 | 67190.64 | 08-NOV-06:03 | 0.99 |
December | 0.212176E+11 | 0.28 | 53515.17 | 26-DEC-06:02 | 0.87 |
Annual Sum or Average | 0.489928E+12 | 0.35 | |||
Minimum of Months | 0.210091E+11 | 0.28 | 51353.39 | 0.85 | |
Maximum of Months | 0.777329E+11 | 0.49 | 173527.06 | 1.78 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.265153E+10 | 0.35 | 4625.29 | 02-JAN-05:21 | 0.75 |
February | 0.230423E+10 | 0.32 | 4625.29 | 06-FEB-05:11 | 0.75 |
March | 0.253666E+10 | 0.31 | 4625.29 | 06-MAR-05:11 | 0.75 |
April | 0.308542E+10 | 0.31 | 13729.80 | 27-APR-14:40 | 1.42 |
May | 0.417571E+10 | 0.35 | 13494.25 | 15-MAY-14:50 | 1.41 |
June | 0.515607E+10 | 0.39 | 13237.37 | 28-JUN-15:20 | 1.39 |
July | 0.640696E+10 | 0.41 | 16477.98 | 31-JUL-14:40 | 1.59 |
August | 0.712199E+10 | 0.44 | 17444.84 | 10-AUG-15:10 | 1.64 |
September | 0.438781E+10 | 0.35 | 19714.10 | 11-SEP-14:17 | 1.78 |
October | 0.261874E+10 | 0.29 | 9211.34 | 04-OCT-15:30 | 1.12 |
November | 0.210226E+10 | 0.28 | 4625.29 | 13-NOV-05:01 | 0.75 |
December | 0.233118E+10 | 0.30 | 4625.29 | 04-DEC-05:11 | 0.75 |
Annual Sum or Average | 0.448786E+11 | 0.34 | |||
Minimum of Months | 0.210226E+10 | 0.28 | 4625.29 | 0.75 | |
Maximum of Months | 0.712199E+10 | 0.44 | 19714.10 | 1.78 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.956133E+11 | 1.37 | 35697.93 | 01-JAN-00:03 | 1.37 |
February | 0.863604E+11 | 1.37 | 35697.93 | 01-FEB-00:20 | 1.37 |
March | 0.956133E+11 | 1.38 | 35697.93 | 01-MAR-00:10 | 1.38 |
April | 0.925290E+11 | 1.38 | 35697.93 | 01-APR-00:10 | 1.37 |
May | 0.956133E+11 | 1.37 | 35697.93 | 01-MAY-00:10 | 1.37 |
June | 0.925290E+11 | 1.37 | 35697.93 | 01-JUN-00:10 | 1.37 |
July | 0.956133E+11 | 1.37 | 35697.93 | 01-JUL-00:10 | 1.37 |
August | 0.956133E+11 | 1.37 | 35697.93 | 01-AUG-00:05 | 1.37 |
September | 0.925290E+11 | 1.37 | 35697.93 | 01-SEP-00:10 | 1.37 |
October | 0.956133E+11 | 1.37 | 35697.93 | 01-OCT-00:10 | 1.37 |
November | 0.925290E+11 | 1.37 | 35697.93 | 01-NOV-00:10 | 1.37 |
December | 0.956133E+11 | 1.38 | 35697.93 | 01-DEC-00:10 | 1.38 |
Annual Sum or Average | 0.112577E+13 | 1.37 | |||
Minimum of Months | 0.863604E+11 | 1.37 | 35697.93 | 1.37 | |
Maximum of Months | 0.956133E+11 | 1.38 | 35697.93 | 1.38 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149924E+10 | 0.93 | 559.75 | 01-JAN-00:03 | 0.93 |
February | 0.135415E+10 | 0.93 | 559.75 | 01-FEB-00:10 | 0.93 |
March | 0.149924E+10 | 0.93 | 559.75 | 01-MAR-00:10 | 0.93 |
April | 0.145088E+10 | 0.93 | 559.75 | 01-APR-00:10 | 0.93 |
May | 0.149924E+10 | 0.93 | 559.75 | 01-MAY-00:10 | 0.93 |
June | 0.145088E+10 | 0.93 | 559.75 | 01-JUN-00:10 | 0.93 |
July | 0.149924E+10 | 0.93 | 559.75 | 01-JUL-00:10 | 0.93 |
August | 0.149924E+10 | 0.92 | 559.75 | 01-AUG-00:05 | 0.93 |
September | 0.145088E+10 | 0.93 | 559.75 | 01-SEP-00:10 | 0.93 |
October | 0.149924E+10 | 0.93 | 559.75 | 01-OCT-00:10 | 0.93 |
November | 0.145088E+10 | 0.93 | 559.75 | 01-NOV-00:10 | 0.93 |
December | 0.149924E+10 | 0.93 | 559.75 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.176523E+11 | 0.93 | |||
Minimum of Months | 0.135415E+10 | 0.92 | 559.75 | 0.93 | |
Maximum of Months | 0.149924E+10 | 0.93 | 559.75 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143966E+11 | 0.93 | 5375.09 | 01-JAN-00:03 | 0.92 |
February | 0.130034E+11 | 0.93 | 5375.09 | 01-FEB-00:10 | 0.93 |
March | 0.143966E+11 | 0.93 | 5375.09 | 01-MAR-00:10 | 0.93 |
April | 0.139322E+11 | 0.93 | 5375.09 | 01-APR-00:10 | 0.93 |
May | 0.143966E+11 | 0.93 | 5375.09 | 01-MAY-00:10 | 0.93 |
June | 0.139322E+11 | 0.93 | 5375.09 | 01-JUN-00:10 | 0.93 |
July | 0.143966E+11 | 0.93 | 5375.09 | 01-JUL-00:10 | 0.93 |
August | 0.143966E+11 | 0.92 | 5375.09 | 01-AUG-00:05 | 0.93 |
September | 0.139322E+11 | 0.93 | 5375.09 | 01-SEP-00:10 | 0.93 |
October | 0.143966E+11 | 0.93 | 5375.09 | 01-OCT-00:10 | 0.93 |
November | 0.139322E+11 | 0.93 | 5375.09 | 01-NOV-00:10 | 0.93 |
December | 0.143966E+11 | 0.93 | 5375.09 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.169509E+12 | 0.93 | |||
Minimum of Months | 0.130034E+11 | 0.92 | 5375.09 | 0.92 | |
Maximum of Months | 0.143966E+11 | 0.93 | 5375.09 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146137E+10 | 0.93 | 545.61 | 01-JAN-00:03 | 0.92 |
February | 0.131995E+10 | 0.93 | 545.61 | 01-FEB-00:10 | 0.93 |
March | 0.146137E+10 | 0.93 | 545.61 | 01-MAR-00:10 | 0.93 |
April | 0.141423E+10 | 0.93 | 545.61 | 01-APR-00:10 | 0.93 |
May | 0.146137E+10 | 0.93 | 545.61 | 01-MAY-00:10 | 0.93 |
June | 0.141423E+10 | 0.93 | 545.61 | 01-JUN-00:10 | 0.93 |
July | 0.146137E+10 | 0.93 | 545.61 | 01-JUL-00:10 | 0.93 |
August | 0.146137E+10 | 0.92 | 545.61 | 01-AUG-00:05 | 0.93 |
September | 0.141423E+10 | 0.93 | 545.61 | 01-SEP-00:10 | 0.93 |
October | 0.146137E+10 | 0.93 | 545.61 | 01-OCT-00:10 | 0.93 |
November | 0.141423E+10 | 0.93 | 545.61 | 01-NOV-00:10 | 0.93 |
December | 0.146137E+10 | 0.93 | 545.61 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.172064E+11 | 0.93 | |||
Minimum of Months | 0.131995E+10 | 0.92 | 545.61 | 0.92 | |
Maximum of Months | 0.146137E+10 | 0.93 | 545.61 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 84581707.64 | 76884772.24 | 3006.01 | 17-JAN-06:01 | 2732.46 | 2732.46 | 45.91 | 23.18 |
February | 31740256.57 | 28851893.22 | 2914.42 | 21-FEB-06:03 | 2649.20 | 2649.20 | 45.81 | 22.88 |
March | 7819849.92 | 7108243.58 | 1000.85 | 06-MAR-05:11 | 909.77 | 909.77 | 36.03 | 14.40 |
April | 2669165.91 | 2426271.81 | 581.15 | 18-APR-05:02 | 528.26 | 528.26 | 39.91 | 11.19 |
May | 532069.47 | 483651.15 | 138.68 | 18-MAY-05:02 | 126.06 | 126.06 | 36.05 | 5.47 |
June | 34351.13 | 31225.18 | 25.57 | 13-JUN-09:40 | 23.24 | 23.24 | 31.66 | 2.04 |
July | 3441.69 | 3128.50 | 8.20 | 12-JUL-09:20 | 7.45 | 7.45 | 31.70 | 0.92 |
August | 3131.70 | 2846.71 | 10.44 | 03-AUG-09:05 | 9.49 | 9.49 | 31.97 | 1.10 |
September | 80150.17 | 72856.50 | 27.43 | 27-SEP-09:20 | 24.94 | 24.94 | 32.21 | 2.13 |
October | 1497581.84 | 1361301.90 | 685.48 | 28-OCT-05:02 | 623.10 | 623.10 | 35.75 | 12.11 |
November | 15303082.07 | 13910501.60 | 1010.45 | 24-NOV-06:03 | 918.50 | 918.50 | 43.17 | 14.42 |
December | 40425189.38 | 36746497.15 | 2910.15 | 26-DEC-06:02 | 2645.33 | 2645.33 | 46.05 | 22.87 |
Annual Sum or Average | 0.184690E+09 | 0.167883E+09 | ||||||
Minimum of Months | 3131.70 | 2846.71 | 8.20 | 7.45 | 7.45 | 31.66 | 0.92 | |
Maximum of Months | 84581707.64 | 76884772.24 | 3006.01 | 2732.46 | 2732.46 | 46.05 | 23.18 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 21284.00 | 19347.15 | 2.66 | 11-JAN-06:03 | 2.41 | 2.41 | 6.70 | 0.65 |
February | 5313658.12 | 4830115.23 | 601.42 | 27-FEB-15:05 | 546.70 | 546.70 | 6.71 | 17.54 |
March | 13153781.81 | 11956787.66 | 533.75 | 14-MAR-15:40 | 485.18 | 485.18 | 6.71 | 16.60 |
April | 98788523.60 | 89798767.95 | 3892.21 | 27-APR-12:00 | 3538.02 | 3538.02 | 8.90 | 39.21 |
May | 0.145124E+09 | 0.131918E+09 | 5990.43 | 04-MAY-14:10 | 5445.30 | 5445.30 | 10.43 | 46.66 |
June | 0.318956E+09 | 0.289931E+09 | 6840.86 | 28-JUN-12:40 | 6218.35 | 6218.35 | 10.08 | 49.19 |
July | 0.541823E+09 | 0.492517E+09 | 8107.60 | 19-JUL-14:50 | 7369.81 | 7369.81 | 10.40 | 52.60 |
August | 0.793015E+09 | 0.720850E+09 | 8012.73 | 15-AUG-12:50 | 7283.58 | 7283.58 | 10.40 | 52.36 |
September | 0.290271E+09 | 0.263856E+09 | 8859.29 | 11-SEP-14:07 | 8053.10 | 8053.10 | 10.58 | 54.48 |
October | 43789126.23 | 39804315.75 | 794.12 | 04-OCT-14:30 | 721.85 | 721.85 | 6.71 | 19.89 |
November | 3538531.92 | 3216525.52 | 228.56 | 04-NOV-14:05 | 207.76 | 207.76 | 6.70 | 11.07 |
December | 401242.34 | 364729.29 | 6.37 | 16-DEC-06:02 | 5.79 | 5.79 | 6.70 | 1.29 |
Annual Sum or Average | 0.225420E+10 | 0.204906E+10 | ||||||
Minimum of Months | 21284.00 | 19347.15 | 2.66 | 2.41 | 2.41 | 6.70 | 0.65 | |
Maximum of Months | 0.793015E+09 | 0.720850E+09 | 8859.29 | 8053.10 | 8053.10 | 10.58 | 54.48 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.248793E+09 | 0.226153E+09 | 3048.81 | 02-JAN-10:07 | 2771.36 | 2771.36 | 6.71 | 27.24 |
February | 0.748957E+09 | 0.680802E+09 | 3048.81 | 01-FEB-05:11 | 2771.36 | 2771.36 | 6.76 | 27.24 |
March | 0.151574E+10 | 0.137781E+10 | 3048.81 | 01-MAR-06:03 | 2771.36 | 2771.36 | 7.36 | 27.24 |
April | 0.148459E+10 | 0.134949E+10 | 3048.81 | 01-APR-05:02 | 2771.36 | 2771.36 | 6.96 | 27.24 |
May | 0.228081E+10 | 0.207325E+10 | 3048.81 | 01-MAY-04:12 | 2771.36 | 2771.36 | 6.91 | 27.24 |
June | 0.351642E+10 | 0.319643E+10 | 3048.81 | 01-JUN-04:12 | 2771.36 | 2771.36 | 6.95 | 27.24 |
July | 0.488094E+10 | 0.443677E+10 | 3048.81 | 01-JUL-04:12 | 2771.36 | 2771.36 | 7.36 | 27.24 |
August | 0.554011E+10 | 0.503596E+10 | 3048.81 | 01-AUG-00:05 | 2771.36 | 2771.36 | 6.79 | 27.24 |
September | 0.301445E+10 | 0.274013E+10 | 3048.81 | 01-SEP-04:12 | 2771.36 | 2771.36 | 7.70 | 27.24 |
October | 0.135322E+10 | 0.123007E+10 | 3048.81 | 01-OCT-12:40 | 2771.36 | 2771.36 | 6.83 | 27.24 |
November | 0.107419E+10 | 0.976443E+09 | 3048.81 | 01-NOV-04:12 | 2771.36 | 2771.36 | 6.91 | 27.24 |
December | 0.124986E+10 | 0.113612E+10 | 3048.81 | 01-DEC-10:25 | 2771.36 | 2771.36 | 6.73 | 27.24 |
Annual Sum or Average | 0.269081E+11 | 0.244594E+11 | ||||||
Minimum of Months | 0.248793E+09 | 0.226153E+09 | 3048.81 | 2771.36 | 2771.36 | 6.71 | 27.24 | |
Maximum of Months | 0.554011E+10 | 0.503596E+10 | 3048.81 | 2771.36 | 2771.36 | 7.70 | 27.24 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.76 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 7.84 | 0.00 |
April | 76829907.32 | 69838385.76 | 3048.81 | 26-APR-13:40 | 2771.36 | 2771.36 | 15.99 | 13.62 |
May | 86890966.62 | 78983888.65 | 3048.81 | 04-MAY-14:00 | 2771.36 | 2771.36 | 14.67 | 13.62 |
June | 0.148172E+09 | 0.134688E+09 | 3048.81 | 09-JUN-14:40 | 2771.36 | 2771.36 | 14.87 | 13.62 |
July | 0.446345E+09 | 0.405728E+09 | 3048.81 | 07-JUL-12:05 | 2771.36 | 2771.36 | 11.46 | 27.24 |
August | 0.954886E+09 | 0.867991E+09 | 3048.81 | 07-AUG-10:05 | 2771.36 | 2771.36 | 11.02 | 27.24 |
September | 0.194819E+09 | 0.177090E+09 | 3048.81 | 08-SEP-14:50 | 2771.36 | 2771.36 | 14.96 | 13.62 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 6.96 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.190794E+10 | 0.173432E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.954886E+09 | 0.867991E+09 | 3048.81 | 2771.36 | 2771.36 | 15.99 | 27.24 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.890980E+10 | 0.809901E+10 | 3326.54 | 01-JAN-00:03 | 3023.82 | 3023.82 | 18.48 | 14.03 |
February | 0.804756E+10 | 0.731523E+10 | 3326.54 | 01-FEB-00:10 | 3023.82 | 3023.82 | 19.13 | 14.03 |
March | 0.890980E+10 | 0.809901E+10 | 3326.54 | 01-MAR-00:10 | 3023.82 | 3023.82 | 19.92 | 14.03 |
April | 0.862239E+10 | 0.783775E+10 | 3326.54 | 01-APR-00:10 | 3023.82 | 3023.82 | 20.45 | 14.03 |
May | 0.890980E+10 | 0.809901E+10 | 3326.54 | 01-MAY-00:10 | 3023.82 | 3023.82 | 18.91 | 14.03 |
June | 0.862239E+10 | 0.783775E+10 | 3326.54 | 01-JUN-00:10 | 3023.82 | 3023.82 | 19.50 | 14.03 |
July | 0.890980E+10 | 0.809901E+10 | 3326.54 | 01-JUL-00:10 | 3023.82 | 3023.82 | 20.10 | 14.03 |
August | 0.890980E+10 | 0.809901E+10 | 3326.54 | 01-AUG-00:05 | 3023.82 | 3023.82 | 27.89 | 14.03 |
September | 0.862239E+10 | 0.783775E+10 | 3326.54 | 01-SEP-00:10 | 3023.82 | 3023.82 | 18.99 | 14.03 |
October | 0.890980E+10 | 0.809901E+10 | 3326.54 | 01-OCT-00:10 | 3023.82 | 3023.82 | 19.42 | 14.03 |
November | 0.862239E+10 | 0.783775E+10 | 3326.54 | 01-NOV-00:10 | 3023.82 | 3023.82 | 19.82 | 14.03 |
December | 0.890980E+10 | 0.809901E+10 | 3326.54 | 01-DEC-00:10 | 3023.82 | 3023.82 | 20.35 | 14.03 |
Annual Sum or Average | 0.104906E+12 | 0.953593E+11 | ||||||
Minimum of Months | 0.804756E+10 | 0.731523E+10 | 3326.54 | 3023.82 | 3023.82 | 18.48 | 14.03 | |
Maximum of Months | 0.890980E+10 | 0.809901E+10 | 3326.54 | 3023.82 | 3023.82 | 27.89 | 14.03 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 55.67 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 56.19 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 56.48 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 56.37 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 56.87 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 56.40 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 56.86 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 55.66 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 56.54 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 55.80 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 56.37 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 56.77 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.66 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 56.87 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.970389E+09 | 0.882084E+09 | 11893.32 | 30-JAN-11:50 | 10811.03 | 10811.03 | 21.18 | 48.68 |
February | 0.292164E+10 | 0.265577E+10 | 11917.87 | 27-FEB-15:10 | 10833.35 | 10833.35 | 24.05 | 48.68 |
March | 0.591409E+10 | 0.537591E+10 | 11915.88 | 14-MAR-16:00 | 10831.53 | 10831.53 | 23.81 | 48.68 |
April | 0.608898E+10 | 0.553488E+10 | 23866.83 | 27-APR-12:05 | 21694.95 | 21694.95 | 25.73 | 97.36 |
May | 0.913021E+10 | 0.829936E+10 | 23862.86 | 05-MAY-13:30 | 21691.34 | 21691.34 | 25.53 | 97.36 |
June | 0.142429E+11 | 0.129468E+11 | 23868.58 | 20-JUN-14:40 | 21696.54 | 21696.54 | 25.82 | 97.36 |
July | 0.206074E+11 | 0.187321E+11 | 23911.88 | 31-JUL-16:00 | 21735.90 | 21735.90 | 27.98 | 97.36 |
August | 0.252766E+11 | 0.229765E+11 | 23928.51 | 29-AUG-14:30 | 21751.01 | 21751.01 | 28.93 | 97.36 |
September | 0.124867E+11 | 0.113504E+11 | 23888.07 | 11-SEP-15:35 | 21714.25 | 21714.25 | 26.79 | 97.36 |
October | 0.528218E+10 | 0.480150E+10 | 11937.83 | 04-OCT-15:00 | 10851.48 | 10851.48 | 26.18 | 48.68 |
November | 0.419025E+10 | 0.380894E+10 | 11914.63 | 04-NOV-14:10 | 10830.39 | 10830.39 | 23.67 | 48.68 |
December | 0.487492E+10 | 0.443131E+10 | 11894.15 | 05-DEC-10:30 | 10811.79 | 10811.79 | 21.28 | 48.68 |
Annual Sum or Average | 0.111986E+12 | 0.101796E+12 | ||||||
Minimum of Months | 0.970389E+09 | 0.882084E+09 | 11893.32 | 10811.03 | 10811.03 | 21.18 | 48.68 | |
Maximum of Months | 0.252766E+11 | 0.229765E+11 | 23928.51 | 21751.01 | 21751.01 | 28.93 | 97.36 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 38.02 | 38.02 | 119582.74 | 1893200.91 | 02-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 33.88 | 33.88 | 71976.00 | 1527405.72 | 16-FEB-05:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 30.06 | 30.06 | 27324.07 | 1442645.70 | 06-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 29.26 | 29.26 | 11616.48 | 939686.88 | 18-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 31.28 | 31.28 | 2811.53 | 547852.12 | 18-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 30.43 | 30.43 | 165.09 | 241070.98 | 13-JUN-09:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.65 | 31.65 | 18.33 | 108521.25 | 12-JUL-09:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 31.77 | 31.77 | 14.41 | 128655.81 | 03-AUG-09:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 32.16 | 32.16 | 454.07 | 247325.26 | 27-SEP-09:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 30.92 | 30.92 | 7019.05 | 1226863.54 | 28-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 31.02 | 31.02 | 46360.79 | 1480421.24 | 24-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 35.37 | 35.37 | 87734.91 | 1387734.17 | 30-DEC-06:02 |
Annual Sum or Average | 0.00 | 31103.77 | ||||||
Minimum of Months | 0.00 | 0.00 | 29.26 | 29.26 | 14.41 | 108521.25 | ||
Maximum of Months | 0.00 | 0.00 | 38.02 | 38.02 | 119582.74 | 1893200.91 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 128.59 | 11082.55 | 11-JAN-06:03 | 6.80 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 4724.13 | 525936.95 | 27-FEB-15:05 | 11.31 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 16300.84 | 480563.24 | 14-MAR-16:00 | 10.91 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 41990.09 | 1491080.21 | 27-APR-12:10 | 13.24 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 64878.43 | 1118500.35 | 05-MAY-15:20 | 16.51 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 121967.39 | 1338628.88 | 28-JUN-13:00 | 12.57 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 212111.53 | 1511026.53 | 31-JUL-16:00 | 13.32 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 283846.81 | 1590549.41 | 29-AUG-14:30 | 13.67 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 107616.52 | 2120391.72 | 11-SEP-15:32 | 16.00 | 7.48 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 29231.54 | 905723.73 | 04-OCT-15:00 | 14.64 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4752.74 | 454659.14 | 04-NOV-14:10 | 10.68 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1927.09 | 41850.12 | 05-DEC-14:40 | 7.07 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 74748.62 | 0.00 | ||||||
Minimum of Months | 128.59 | 11082.55 | 6.80 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 283846.81 | 2120391.72 | 16.51 | 7.48 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 44.48 | 12361.13 | 11-JAN-06:03 | 11.27 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 4451.91 | 570129.13 | 27-FEB-14:40 | 15.26 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 15793.21 | 478847.77 | 14-MAR-16:00 | 13.63 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 41606.56 | 1276525.27 | 27-APR-12:10 | 15.96 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 65458.85 | 1441967.52 | 04-MAY-14:05 | 14.26 | 10.42 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 122158.31 | 1575192.59 | 28-JUN-12:40 | 14.35 | 10.10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 212104.68 | 1708395.29 | 20-JUL-12:20 | 15.05 | 11.45 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 283635.03 | 1687226.15 | 15-AUG-12:50 | 14.40 | 10.38 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 108907.25 | 2282407.31 | 11-SEP-15:30 | 16.71 | 13.19 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 28804.31 | 906295.46 | 04-OCT-15:00 | 18.27 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4378.98 | 459277.91 | 04-NOV-14:05 | 16.61 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1503.04 | 49657.41 | 16-DEC-06:02 | 15.90 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 74695.45 | 0.00 | ||||||
Minimum of Months | 44.48 | 12361.13 | 11.27 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 283635.03 | 2282407.31 | 18.27 | 13.19 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 12426.77 | 27691.82 | 20-JAN-16:20 | 18.90 | 18.33 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 45762.51 | 227542.48 | 27-FEB-15:00 | 22.99 | 20.88 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 82320.19 | 496509.96 | 18-MAR-16:00 | 28.45 | 22.92 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 184890.39 | 1342684.08 | 27-APR-15:10 | 45.26 | 32.65 | 0.00 | 0.00 | 01-APR-00:10 |
May | 50308.12 | 537427.97 | 05-MAY-16:00 | 29.27 | 26.27 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 123591.25 | 898091.08 | 28-JUN-17:00 | 36.50 | 29.62 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 338144.24 | 1350350.04 | 24-JUL-15:00 | 45.41 | 35.07 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 646823.61 | 1609328.00 | 10-AUG-17:00 | 50.45 | 37.46 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 56989.34 | 540314.16 | 22-SEP-16:00 | 29.33 | 26.28 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 54744.93 | 411224.22 | 04-OCT-15:00 | 26.73 | 23.18 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 78167.94 | 624156.48 | 04-NOV-15:00 | 31.02 | 24.04 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 99389.66 | 164015.73 | 14-DEC-12:00 | 21.69 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 149039.46 | 0.00 | ||||||
Minimum of Months | 12426.77 | 27691.82 | 18.90 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 646823.61 | 1609328.00 | 50.45 | 37.46 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.56 | 57.56 | 15525.23 | 52044.29 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.78 | 56.78 | 15708.60 | 52117.89 | 13-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.07 | 57.07 | 16427.07 | 51936.17 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.87 | 56.87 | 15096.85 | 50806.27 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.67 | 57.67 | 15026.85 | 49250.02 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.94 | 56.94 | 14828.83 | 47388.78 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.32 | 57.32 | 13417.83 | 45717.47 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 56.17 | 56.17 | 14440.76 | 45089.16 | 29-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.06 | 57.06 | 13797.29 | 46035.90 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.30 | 56.30 | 14171.73 | 47784.61 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.86 | 56.86 | 14865.82 | 49630.74 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.25 | 57.25 | 14851.32 | 51137.32 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 14841.61 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.17 | 56.17 | 13417.83 | 45089.16 | ||
Maximum of Months | 0.00 | 0.00 | 57.67 | 57.67 | 16427.07 | 52117.89 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16.75 | 15988.11 | 30-JAN-11:50 | 21.18 | 20.50 | 819.78 | 89848.53 | 20-JAN-15:50 |
February | 3701.13 | 599438.16 | 27-FEB-15:10 | 24.05 | 21.10 | 2295.65 | 111749.58 | 08-FEB-06:30 |
March | 16342.97 | 552088.78 | 14-MAR-16:00 | 23.81 | 21.10 | 2657.19 | 105477.82 | 24-MAR-09:00 |
April | 50410.89 | 1884793.05 | 27-APR-12:05 | 25.73 | 21.22 | 1086.07 | 89736.35 | 12-APR-08:30 |
May | 76238.09 | 1803926.75 | 05-MAY-13:30 | 25.53 | 21.46 | 587.76 | 77898.97 | 27-MAY-06:00 |
June | 146505.14 | 1920468.31 | 20-JUN-14:40 | 25.82 | 21.17 | 819.24 | 65165.77 | 05-JUN-08:20 |
July | 266639.55 | 2799501.64 | 31-JUL-16:00 | 27.98 | 23.71 | 1087.75 | 67106.52 | 03-JUL-10:00 |
August | 388903.17 | 3185109.20 | 29-AUG-14:30 | 28.93 | 24.42 | 1190.25 | 53262.83 | 19-AUG-21:00 |
September | 132119.97 | 2316422.76 | 11-SEP-15:35 | 26.79 | 21.92 | 568.09 | 53875.17 | 05-SEP-10:00 |
October | 32702.85 | 1032482.49 | 04-OCT-15:00 | 26.18 | 21.10 | 808.85 | 81087.13 | 11-OCT-05:40 |
November | 3965.95 | 522390.95 | 04-NOV-14:10 | 23.67 | 21.10 | 3233.52 | 102107.85 | 24-NOV-06:50 |
December | 232.27 | 35875.72 | 05-DEC-10:30 | 21.28 | 20.55 | 4424.76 | 101742.81 | 21-DEC-06:30 |
Annual Sum or Average | 93991.88 | 1628.36 | ||||||
Minimum of Months | 16.75 | 15988.11 | 21.18 | 20.50 | 568.09 | 53262.83 | ||
Maximum of Months | 388903.17 | 3185109.20 | 28.93 | 24.42 | 4424.76 | 111749.58 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.121778E+11 | 0.00 | 0.223800E+09 | 0.265526E+10 | 0.00 | 0.00 |
February | 0.719472E+10 | 0.00 | 0.349521E+10 | 0.331640E+10 | 0.00 | 0.00 |
March | 0.191442E+10 | 0.00 | 0.457988E+10 | 0.555702E+10 | 0.00 | 0.00 |
April | 0.596915E+09 | 0.00 | 0.985621E+10 | 0.752836E+10 | 0.00 | 0.00 |
May | 0.293448E+09 | 0.00 | 0.147860E+11 | 0.676390E+10 | 0.00 | 0.00 |
June | 6935.42 | 0.00 | 0.291490E+11 | 0.843789E+10 | 0.00 | 0.00 |
July | 5421.70 | 0.00 | 0.539283E+11 | 0.105970E+11 | 0.00 | 0.00 |
August | 8744.09 | 0.00 | 0.736125E+11 | 0.123172E+11 | 0.00 | 0.00 |
September | 24204261.33 | 0.00 | 0.230622E+11 | 0.696938E+10 | 0.00 | 0.00 |
October | 0.342293E+09 | 0.00 | 0.508775E+10 | 0.551140E+10 | 0.00 | 0.00 |
November | 0.316913E+10 | 0.00 | 0.331856E+10 | 0.402251E+10 | 0.00 | 0.00 |
December | 0.647994E+10 | 0.00 | 0.399675E+10 | 0.388115E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.321929E+11 | 0.00 | 0.225096E+12 | 0.775575E+11 | 0.00 | 0.00 |
Minimum of Months | 5421.70 | 0.00 | 0.223800E+09 | 0.265526E+10 | 0.00 | 0.00 |
Maximum of Months | 0.121778E+11 | 0.00 | 0.736125E+11 | 0.123172E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.265400E+12 | 0.00 | 15669.10 | 0.219211E+11 | 0.00 | 0.00 |
February | 0.141199E+12 | 0.00 | 0.652955E+10 | 0.210091E+11 | 0.00 | 0.00 |
March | 0.590469E+11 | 0.00 | 0.369237E+11 | 0.294746E+11 | 0.00 | 0.00 |
April | 0.245213E+11 | 0.00 | 0.852310E+11 | 0.367743E+11 | 0.00 | 0.00 |
May | 0.599669E+10 | 0.00 | 0.136074E+12 | 0.487306E+11 | 0.00 | 0.00 |
June | 0.333127E+09 | 0.00 | 0.240837E+12 | 0.571069E+11 | 0.00 | 0.00 |
July | 47828053.91 | 0.00 | 0.423535E+12 | 0.678852E+11 | 0.00 | 0.00 |
August | 34591935.83 | 0.00 | 0.564049E+12 | 0.777329E+11 | 0.00 | 0.00 |
September | 0.890333E+09 | 0.00 | 0.216387E+12 | 0.532946E+11 | 0.00 | 0.00 |
October | 0.135985E+11 | 0.00 | 0.664380E+11 | 0.331538E+11 | 0.00 | 0.00 |
November | 0.970915E+11 | 0.00 | 0.734221E+10 | 0.216269E+11 | 0.00 | 0.00 |
December | 0.193324E+12 | 0.00 | 19689.31 | 0.212176E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.801483E+12 | 0.00 | 0.178335E+13 | 0.489928E+12 | 0.00 | 0.00 |
Minimum of Months | 34591935.83 | 0.00 | 15669.10 | 0.210091E+11 | 0.00 | 0.00 |
Maximum of Months | 0.265400E+12 | 0.00 | 0.564049E+12 | 0.777329E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.432155E+11 | 0.00 | 35402.48 | 0.265153E+10 | 0.00 | 0.00 |
February | 0.260081E+11 | 0.00 | 0.357279E+09 | 0.230423E+10 | 0.00 | 0.00 |
March | 0.123267E+11 | 0.00 | 0.844453E+09 | 0.253666E+10 | 0.00 | 0.00 |
April | 0.500897E+10 | 0.00 | 0.707092E+10 | 0.308542E+10 | 0.00 | 0.00 |
May | 0.125867E+10 | 0.00 | 0.131420E+11 | 0.417571E+10 | 0.00 | 0.00 |
June | 82488501.33 | 0.00 | 0.249215E+11 | 0.515607E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.452653E+11 | 0.640696E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.591592E+11 | 0.712199E+10 | 0.00 | 0.00 |
September | 0.276837E+09 | 0.00 | 0.200373E+11 | 0.438781E+10 | 0.00 | 0.00 |
October | 0.488199E+10 | 0.00 | 0.274691E+10 | 0.261874E+10 | 0.00 | 0.00 |
November | 0.200188E+11 | 0.00 | 0.488363E+09 | 0.210226E+10 | 0.00 | 0.00 |
December | 0.354970E+11 | 0.00 | 21794.08 | 0.233118E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.148575E+12 | 0.00 | 0.174033E+12 | 0.448786E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 21794.08 | 0.210226E+10 | 0.00 | 0.00 |
Maximum of Months | 0.432155E+11 | 0.00 | 0.591592E+11 | 0.712199E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 1824548.18 | 0.120828E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.396869E+09 | 0.110110E+11 | 0.00 | 0.00 |
March | 70.70 | 0.00 | 0.103131E+09 | 0.129738E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.342650E+10 | 0.118642E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.660191E+10 | 0.125934E+11 | 0.00 | 0.00 |
June | 249.98 | 0.00 | 0.138357E+11 | 0.125293E+11 | 0.00 | 0.00 |
July | 395.62 | 0.00 | 0.266650E+11 | 0.122663E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.366669E+11 | 0.133609E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.107371E+11 | 0.124003E+11 | 0.00 | 0.00 |
October | 260.07 | 0.00 | 0.139670E+10 | 0.124852E+11 | 0.00 | 0.00 |
November | 115.21 | 0.00 | 0.272389E+09 | 0.119392E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 4803387.88 | 0.119317E+11 | 0.00 | 0.00 |
Annual Sum or Average | 1091.58 | 0.00 | 0.100109E+12 | 0.147438E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 1824548.18 | 0.110110E+11 | 0.00 | 0.00 |
Maximum of Months | 395.62 | 0.00 | 0.366669E+11 | 0.133609E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.751388E+10 | 0.187755E+12 | 0.00 | 33.10 |
February | 0.00 | 0.00 | 0.105970E+11 | 0.219911E+12 | 0.00 | 48.32 |
March | 0.00 | 0.00 | 0.201745E+11 | 0.280740E+12 | 0.00 | 66.67 |
April | 0.00 | 0.00 | 0.136397E+12 | 0.278637E+12 | 0.00 | 58.08 |
May | 0.00 | 0.00 | 0.861660E+10 | 0.133872E+12 | 0.00 | 12.91 |
June | 0.00 | 0.00 | 0.549816E+11 | 0.127806E+12 | 0.00 | 8.09 |
July | 0.00 | 0.00 | 0.319219E+12 | 0.184141E+12 | 0.00 | 7.95 |
August | 0.00 | 0.00 | 0.788800E+12 | 0.255705E+12 | 0.00 | 0.40 |
September | 0.00 | 0.00 | 0.819934E+10 | 0.977617E+11 | 0.00 | 0.59 |
October | 0.00 | 0.00 | 0.787732E+10 | 0.153172E+12 | 0.00 | 20.16 |
November | 0.00 | 0.00 | 0.169000E+11 | 0.215390E+12 | 0.00 | 43.81 |
December | 0.00 | 0.00 | 0.200244E+11 | 0.321676E+12 | 0.00 | 81.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.139930E+13 | 0.245657E+13 | 0.00 | 381.92 |
Minimum of Months | 0.00 | 0.00 | 0.751388E+10 | 0.977617E+11 | 0.00 | 0.40 |
Maximum of Months | 0.00 | 0.00 | 0.788800E+12 | 0.321676E+12 | 0.00 | 81.85 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.470015E+10 | 0.237735E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.104444E+11 | 0.318605E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.181807E+11 | 0.455456E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.237512E+11 | 0.533699E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.664918E+10 | 0.269715E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.125975E+11 | 0.363466E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.195855E+11 | 0.492292E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.257922E+11 | 0.612071E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.664322E+10 | 0.263643E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.123715E+11 | 0.360828E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.174358E+11 | 0.434377E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.237685E+11 | 0.538478E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.181920E+12 | 0.488036E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.470015E+10 | 0.237735E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.257922E+11 | 0.612071E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.126094E+11 | 0.169880E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.757661E+11 | 0.265510E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.156802E+12 | 0.410226E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.216362E+12 | 0.495650E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.561478E+11 | 0.246061E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.115096E+12 | 0.339793E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.183463E+12 | 0.465700E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.243579E+12 | 0.581567E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.572193E+11 | 0.242259E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.104042E+12 | 0.323163E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.143621E+12 | 0.381010E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.196408E+12 | 0.470451E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.156112E+13 | 0.439127E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.126094E+11 | 0.169880E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.243579E+12 | 0.581567E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.368814E+09 | 0.154076E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.575795E+10 | 0.236371E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.140672E+11 | 0.387458E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.207053E+11 | 0.484751E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.500873E+10 | 0.238028E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.112535E+11 | 0.338179E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.182134E+11 | 0.466646E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.241985E+11 | 0.582489E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.510187E+10 | 0.234100E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.894225E+10 | 0.301899E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.124047E+11 | 0.352890E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.175000E+11 | 0.440743E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143522E+12 | 0.421763E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.368814E+09 | 0.154076E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.241985E+11 | 0.582489E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.265526E+10 | 0.223800E+09 | 0.121778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.331640E+10 | 0.349521E+10 | 0.719472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.555702E+10 | 0.457988E+10 | 0.191442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.752836E+10 | 0.985621E+10 | 0.596915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.676390E+10 | 0.147860E+11 | 0.293448E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.843789E+10 | 0.291490E+11 | 6935.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105970E+11 | 0.539283E+11 | 5421.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123172E+11 | 0.736125E+11 | 8744.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.696938E+10 | 0.230622E+11 | 24204261.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.551140E+10 | 0.508775E+10 | 0.342293E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.402251E+10 | 0.331856E+10 | 0.316913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.388115E+10 | 0.399675E+10 | 0.647994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.775575E+11 | 0.225096E+12 | 0.321929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.265526E+10 | 0.223800E+09 | 5421.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.123172E+11 | 0.736125E+11 | 0.121778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.219211E+11 | 15669.10 | 0.265400E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.210091E+11 | 0.652955E+10 | 0.141199E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.294746E+11 | 0.369237E+11 | 0.590469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.367743E+11 | 0.852310E+11 | 0.245213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.487306E+11 | 0.136074E+12 | 0.599669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.571069E+11 | 0.240837E+12 | 0.333127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.678852E+11 | 0.423535E+12 | 47828053.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.777329E+11 | 0.564049E+12 | 34591935.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.532946E+11 | 0.216387E+12 | 0.890333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.331538E+11 | 0.664380E+11 | 0.135985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.216269E+11 | 0.734221E+10 | 0.970915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212176E+11 | 19689.31 | 0.193324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.489928E+12 | 0.178335E+13 | 0.801483E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.210091E+11 | 15669.10 | 34591935.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.777329E+11 | 0.564049E+12 | 0.265400E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.265153E+10 | 35402.48 | 0.432155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230423E+10 | 0.357279E+09 | 0.260081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.253666E+10 | 0.844453E+09 | 0.123267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.308542E+10 | 0.707092E+10 | 0.500897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.417571E+10 | 0.131420E+11 | 0.125867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.515607E+10 | 0.249215E+11 | 82488501.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.640696E+10 | 0.452653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.712199E+10 | 0.591592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.438781E+10 | 0.200373E+11 | 0.276837E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261874E+10 | 0.274691E+10 | 0.488199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210226E+10 | 0.488363E+09 | 0.200188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233118E+10 | 21794.08 | 0.354970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448786E+11 | 0.174033E+12 | 0.148575E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.210226E+10 | 21794.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.712199E+10 | 0.591592E+11 | 0.432155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.120828E+11 | 1824548.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110110E+11 | 0.396869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129738E+11 | 0.103131E+09 | 70.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118642E+11 | 0.342650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125934E+11 | 0.660191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125293E+11 | 0.138357E+11 | 249.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122663E+11 | 0.266650E+11 | 395.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133609E+11 | 0.366669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124003E+11 | 0.107371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124852E+11 | 0.139670E+10 | 260.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119392E+11 | 0.272389E+09 | 115.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119317E+11 | 4803387.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147438E+12 | 0.100109E+12 | 1091.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110110E+11 | 1824548.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133609E+11 | 0.366669E+11 | 395.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.956133E+11 | 0.434107E+10 | 0.00 | 0.00 | 0.00 | 0.885706E+11 | 0.00 | 0.00 |
February | 0.863604E+11 | 0.692948E+10 | 0.00 | 0.00 | 0.00 | 0.129301E+12 | 0.00 | 0.00 |
March | 0.956133E+11 | 0.142634E+11 | 0.00 | 0.00 | 0.00 | 0.178413E+12 | 0.00 | 0.00 |
April | 0.925290E+11 | 0.106410E+12 | 0.00 | 0.00 | 0.00 | 0.155422E+12 | 0.00 | 0.00 |
May | 0.956133E+11 | 0.505115E+10 | 0.00 | 0.00 | 0.00 | 0.345381E+11 | 0.00 | 0.00 |
June | 0.925290E+11 | 0.414475E+11 | 0.00 | 0.00 | 0.00 | 0.216450E+11 | 0.00 | 0.00 |
July | 0.956133E+11 | 0.252053E+12 | 0.00 | 0.00 | 0.00 | 0.212669E+11 | 0.00 | 0.00 |
August | 0.956133E+11 | 0.629787E+12 | 0.00 | 0.00 | 0.00 | 0.107282E+10 | 0.00 | 0.00 |
September | 0.925290E+11 | 0.454809E+10 | 0.00 | 0.00 | 0.00 | 0.157436E+10 | 0.00 | 0.00 |
October | 0.956133E+11 | 0.451755E+10 | 0.00 | 0.00 | 0.00 | 0.539561E+11 | 0.00 | 0.00 |
November | 0.925290E+11 | 0.118086E+11 | 0.00 | 0.00 | 0.00 | 0.117242E+12 | 0.00 | 0.00 |
December | 0.956133E+11 | 0.140011E+11 | 0.00 | 0.00 | 0.00 | 0.219053E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.112577E+13 | 0.109516E+13 | 0.00 | 0.00 | 0.00 | 0.102205E+13 | 0.00 | 0.00 |
Minimum of Months | 0.863604E+11 | 0.434107E+10 | 0.00 | 0.00 | 0.00 | 0.107282E+10 | 0.00 | 0.00 |
Maximum of Months | 0.956133E+11 | 0.629787E+12 | 0.00 | 0.00 | 0.00 | 0.219053E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149924E+10 | 0.382204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135415E+10 | 0.861254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149924E+10 | 0.151254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145088E+10 | 0.198651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149924E+10 | 0.545127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145088E+10 | 0.104138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149924E+10 | 0.161619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149924E+10 | 0.211707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145088E+10 | 0.545766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149924E+10 | 0.102624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145088E+10 | 0.145429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149924E+10 | 0.198830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176523E+11 | 0.150769E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135415E+10 | 0.382204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149924E+10 | 0.211707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143966E+11 | 0.100180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130034E+11 | 0.622184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143966E+11 | 0.130176E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139322E+11 | 0.180730E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143966E+11 | 0.459383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139322E+11 | 0.950486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143966E+11 | 0.151290E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143966E+11 | 0.199819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139322E+11 | 0.469256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143966E+11 | 0.861219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139322E+11 | 0.119452E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143966E+11 | 0.163760E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169509E+12 | 0.129150E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130034E+11 | 0.100180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143966E+11 | 0.199819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146137E+10 | 0.289428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131995E+10 | 0.471418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146137E+10 | 0.116540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141423E+10 | 0.172721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146137E+10 | 0.408982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141423E+10 | 0.928589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146137E+10 | 0.150083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146137E+10 | 0.198350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141423E+10 | 0.417510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146137E+10 | 0.738463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141423E+10 | 0.102901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146137E+10 | 0.145540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172064E+11 | 0.118552E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131995E+10 | 0.289428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146137E+10 | 0.198350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.265526E+10 | 0.121778E+11 | 0.223800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.331640E+10 | 0.719472E+10 | 0.349521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.555702E+10 | 0.191442E+10 | 0.457988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.752836E+10 | 0.596915E+09 | 0.985621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.676390E+10 | 0.293448E+09 | 0.147860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.843789E+10 | 6935.42 | 0.291490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105970E+11 | 5421.70 | 0.539283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123172E+11 | 8744.09 | 0.736125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.696938E+10 | 24204261.33 | 0.230622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.551140E+10 | 0.342293E+09 | 0.508775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.402251E+10 | 0.316913E+10 | 0.331856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.388115E+10 | 0.647994E+10 | 0.399675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.775575E+11 | 0.321929E+11 | 0.225096E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.265526E+10 | 5421.70 | 0.223800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.123172E+11 | 0.121778E+11 | 0.736125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.219211E+11 | 0.265400E+12 | 15669.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.210091E+11 | 0.141199E+12 | 0.652955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.294746E+11 | 0.590469E+11 | 0.369237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.367743E+11 | 0.245213E+11 | 0.852310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.487306E+11 | 0.599669E+10 | 0.136074E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.571069E+11 | 0.333127E+09 | 0.240837E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.678852E+11 | 47828053.91 | 0.423535E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.777329E+11 | 34591935.83 | 0.564049E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.532946E+11 | 0.890333E+09 | 0.216387E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.331538E+11 | 0.135985E+11 | 0.664380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.216269E+11 | 0.970915E+11 | 0.734221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212176E+11 | 0.193324E+12 | 19689.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.489928E+12 | 0.801483E+12 | 0.178335E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.210091E+11 | 34591935.83 | 15669.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.777329E+11 | 0.265400E+12 | 0.564049E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.265153E+10 | 0.432155E+11 | 35402.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230423E+10 | 0.260081E+11 | 0.357279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.253666E+10 | 0.123267E+11 | 0.844453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.308542E+10 | 0.500897E+10 | 0.707092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.417571E+10 | 0.125867E+10 | 0.131420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.515607E+10 | 82488501.33 | 0.249215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.640696E+10 | 0.00 | 0.452653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.712199E+10 | 0.00 | 0.591592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.438781E+10 | 0.276837E+09 | 0.200373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261874E+10 | 0.488199E+10 | 0.274691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210226E+10 | 0.200188E+11 | 0.488363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233118E+10 | 0.354970E+11 | 21794.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448786E+11 | 0.148575E+12 | 0.174033E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.210226E+10 | 0.00 | 21794.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.712199E+10 | 0.432155E+11 | 0.591592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.120828E+11 | 0.00 | 1824548.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110110E+11 | 0.00 | 0.396869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129738E+11 | 70.70 | 0.103131E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118642E+11 | 0.00 | 0.342650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125934E+11 | 0.00 | 0.660191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125293E+11 | 249.98 | 0.138357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122663E+11 | 395.62 | 0.266650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133609E+11 | 0.00 | 0.366669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124003E+11 | 0.00 | 0.107371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124852E+11 | 260.07 | 0.139670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119392E+11 | 115.21 | 0.272389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119317E+11 | 0.00 | 4803387.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147438E+12 | 1091.58 | 0.100109E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110110E+11 | 0.00 | 1824548.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133609E+11 | 395.62 | 0.366669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.956133E+11 | 0.00 | 0.751388E+10 | 0.00 | 0.317281E+10 | 0.00 | 0.00 | 0.00 | 0.889693E+11 | 0.00 | 0.00 | 0.00 |
February | 0.863604E+11 | 0.00 | 0.105970E+11 | 0.00 | 0.366748E+10 | 0.00 | 0.00 | 0.00 | 0.129883E+12 | 0.00 | 0.00 | 0.00 |
March | 0.956133E+11 | 0.00 | 0.201745E+11 | 0.00 | 0.591110E+10 | 0.00 | 0.00 | 0.00 | 0.179216E+12 | 0.00 | 0.00 | 0.00 |
April | 0.925290E+11 | 0.00 | 0.136397E+12 | 0.00 | 0.299869E+11 | 0.00 | 0.00 | 0.00 | 0.156121E+12 | 0.00 | 0.00 | 0.00 |
May | 0.956133E+11 | 0.00 | 0.861660E+10 | 0.00 | 0.356545E+10 | 0.00 | 0.00 | 0.00 | 0.346936E+11 | 0.00 | 0.00 | 0.00 |
June | 0.925290E+11 | 0.00 | 0.549816E+11 | 0.00 | 0.135341E+11 | 0.00 | 0.00 | 0.00 | 0.217424E+11 | 0.00 | 0.00 | 0.00 |
July | 0.956133E+11 | 0.00 | 0.319219E+12 | 0.00 | 0.671653E+11 | 0.00 | 0.00 | 0.00 | 0.213627E+11 | 0.00 | 0.00 | 0.00 |
August | 0.956133E+11 | 0.00 | 0.788800E+12 | 0.00 | 0.159014E+12 | 0.00 | 0.00 | 0.00 | 0.107765E+10 | 0.00 | 0.00 | 0.00 |
September | 0.925290E+11 | 0.00 | 0.819934E+10 | 0.00 | 0.365125E+10 | 0.00 | 0.00 | 0.00 | 0.158145E+10 | 0.00 | 0.00 | 0.00 |
October | 0.956133E+11 | 0.00 | 0.787732E+10 | 0.00 | 0.335977E+10 | 0.00 | 0.00 | 0.00 | 0.541990E+11 | 0.00 | 0.00 | 0.00 |
November | 0.925290E+11 | 0.00 | 0.169000E+11 | 0.00 | 0.509134E+10 | 0.00 | 0.00 | 0.00 | 0.117770E+12 | 0.00 | 0.00 | 0.00 |
December | 0.956133E+11 | 0.00 | 0.200244E+11 | 0.00 | 0.602338E+10 | 0.00 | 0.00 | 0.00 | 0.220039E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112577E+13 | 0.00 | 0.139930E+13 | 0.00 | 0.304143E+12 | 0.00 | 0.00 | 0.00 | 0.102666E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.863604E+11 | 0.00 | 0.751388E+10 | 0.00 | 0.317281E+10 | 0.00 | 0.00 | 0.00 | 0.107765E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.956133E+11 | 0.00 | 0.788800E+12 | 0.00 | 0.159014E+12 | 0.00 | 0.00 | 0.00 | 0.220039E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149924E+10 | 0.00 | 0.470015E+10 | 0.00 | 0.878113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135415E+10 | 0.00 | 0.104444E+11 | 0.00 | 0.183190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149924E+10 | 0.00 | 0.181807E+11 | 0.00 | 0.305532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145088E+10 | 0.00 | 0.237512E+11 | 0.00 | 0.388612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149924E+10 | 0.00 | 0.664918E+10 | 0.00 | 0.119791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145088E+10 | 0.00 | 0.125975E+11 | 0.00 | 0.218379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149924E+10 | 0.00 | 0.195855E+11 | 0.00 | 0.342368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149924E+10 | 0.00 | 0.257922E+11 | 0.00 | 0.462147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145088E+10 | 0.00 | 0.664322E+10 | 0.00 | 0.118555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149924E+10 | 0.00 | 0.123715E+11 | 0.00 | 0.210905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145088E+10 | 0.00 | 0.174358E+11 | 0.00 | 0.289289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149924E+10 | 0.00 | 0.237685E+11 | 0.00 | 0.388554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176523E+11 | 0.00 | 0.181920E+12 | 0.00 | 0.311513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135415E+10 | 0.00 | 0.470015E+10 | 0.00 | 0.878113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149924E+10 | 0.00 | 0.257922E+11 | 0.00 | 0.462147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.143966E+11 | 0.00 | 0.126094E+11 | 0.00 | 0.259140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130034E+11 | 0.00 | 0.757661E+11 | 0.00 | 0.135476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143966E+11 | 0.00 | 0.156802E+12 | 0.00 | 0.266259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139322E+11 | 0.00 | 0.216362E+12 | 0.00 | 0.356328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143966E+11 | 0.00 | 0.561478E+11 | 0.00 | 0.102095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139322E+11 | 0.00 | 0.115096E+12 | 0.00 | 0.200471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143966E+11 | 0.00 | 0.183463E+12 | 0.00 | 0.321734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143966E+11 | 0.00 | 0.243579E+12 | 0.00 | 0.437601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139322E+11 | 0.00 | 0.572193E+11 | 0.00 | 0.102937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143966E+11 | 0.00 | 0.104042E+12 | 0.00 | 0.179196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139322E+11 | 0.00 | 0.143621E+12 | 0.00 | 0.241688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143966E+11 | 0.00 | 0.196408E+12 | 0.00 | 0.326485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169509E+12 | 0.00 | 0.156112E+13 | 0.00 | 0.269618E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130034E+11 | 0.00 | 0.126094E+11 | 0.00 | 0.259140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143966E+11 | 0.00 | 0.243579E+12 | 0.00 | 0.437601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146137E+10 | 0.00 | 0.368814E+09 | 0.00 | 79386694.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131995E+10 | 0.00 | 0.575795E+10 | 0.00 | 0.104377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146137E+10 | 0.00 | 0.140672E+11 | 0.00 | 0.241321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141423E+10 | 0.00 | 0.207053E+11 | 0.00 | 0.343328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146137E+10 | 0.00 | 0.500873E+10 | 0.00 | 0.918911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141423E+10 | 0.00 | 0.112535E+11 | 0.00 | 0.196756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146137E+10 | 0.00 | 0.182134E+11 | 0.00 | 0.320509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146137E+10 | 0.00 | 0.241985E+11 | 0.00 | 0.436352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141423E+10 | 0.00 | 0.510187E+10 | 0.00 | 0.926775E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146137E+10 | 0.00 | 0.894225E+10 | 0.00 | 0.155762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141423E+10 | 0.00 | 0.124047E+11 | 0.00 | 0.211467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146137E+10 | 0.00 | 0.175000E+11 | 0.00 | 0.294606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172064E+11 | 0.00 | 0.143522E+12 | 0.00 | 0.249698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131995E+10 | 0.00 | 0.368814E+09 | 0.00 | 79386694.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146137E+10 | 0.00 | 0.241985E+11 | 0.00 | 0.436352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.865987E+09 | 0.00 | 0.00 | 86584290.90 | 0.00 | 0.00 | 0.564843E+11 | 0.00 | 0.48 |
February | 0.396227E+09 | 0.00 | 0.00 | 84314186.14 | 0.00 | 0.00 | 0.540501E+11 | 0.00 | 0.58 |
March | 0.277370E+09 | 0.00 | 0.00 | 0.111281E+09 | 0.00 | 0.00 | 0.679815E+11 | 0.00 | 0.74 |
April | 0.267971E+09 | 23179846.32 | 0.00 | 0.106628E+09 | 0.00 | 0.00 | 0.615081E+11 | 0.00 | 0.84 |
May | 0.182008E+09 | 8933764.72 | 0.00 | 0.106463E+09 | 0.00 | 0.00 | 0.609583E+11 | 0.00 | 1.02 |
June | 0.111608E+09 | 13883564.93 | 0.00 | 0.109261E+09 | 1234610.53 | 0.00 | 0.560914E+11 | 0.00 | 1.24 |
July | 0.160140E+09 | 0.179659E+09 | 0.00 | 0.108920E+09 | 3471557.38 | 0.00 | 0.438734E+11 | 0.00 | 1.20 |
August | 0.158586E+09 | 0.405534E+09 | 0.00 | 0.112670E+09 | 158478.97 | 0.00 | 0.409112E+11 | 0.00 | 1.18 |
September | 0.272922E+09 | 0.00 | 0.00 | 0.109803E+09 | 0.00 | 0.00 | 0.566548E+11 | 0.00 | 1.18 |
October | 0.327985E+09 | 0.00 | 0.00 | 0.111859E+09 | 0.00 | 0.00 | 0.671665E+11 | 0.00 | 0.91 |
November | 0.255518E+09 | 0.00 | 0.00 | 0.104600E+09 | 0.00 | 0.00 | 0.647464E+11 | 0.00 | 0.70 |
December | 0.494322E+09 | 0.00 | 0.00 | 0.106061E+09 | 0.00 | 0.00 | 0.623343E+11 | 0.00 | 0.54 |
Annual Sum or Average | 0.377064E+10 | 0.631190E+09 | 0.00 | 0.125845E+10 | 4864646.88 | 0.00 | 0.692760E+12 | 0.00 | 0.89 |
Minimum of Months | 0.111608E+09 | 0.00 | 0.00 | 84314186.14 | 0.00 | 0.00 | 0.409112E+11 | 0.00 | 0.48 |
Maximum of Months | 0.865987E+09 | 0.405534E+09 | 0.00 | 0.112670E+09 | 3471557.38 | 0.00 | 0.679815E+11 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.605767E+10 | 0.00 | 0.00 | 45886197.34 | 0.00 | 0.00 | 0.397222E+11 | 0.00 | 0.36 |
February | 0.164974E+10 | 0.00 | 0.00 | 59404632.14 | 0.00 | 0.00 | 0.408697E+11 | 0.00 | 0.43 |
March | 0.163931E+10 | 0.00 | 0.00 | 91813326.12 | 0.00 | 0.00 | 0.528845E+11 | 0.00 | 0.56 |
April | 0.418453E+10 | 16573035.68 | 0.00 | 94112381.71 | 0.00 | 0.00 | 0.516481E+11 | 0.00 | 0.72 |
May | 0.315945E+10 | 477575.04 | 0.00 | 85411817.91 | 0.00 | 0.00 | 0.464757E+11 | 0.00 | 0.76 |
June | 0.280075E+10 | 14979830.39 | 0.00 | 93198741.78 | 5918490.50 | 0.00 | 0.446612E+11 | 0.00 | 0.92 |
July | 0.615691E+10 | 0.134654E+09 | 0.00 | 92274118.92 | 3586687.89 | 0.00 | 0.348360E+11 | 0.00 | 0.96 |
August | 0.801192E+10 | 0.500550E+09 | 0.00 | 91213284.73 | 5023783.74 | 0.00 | 0.324110E+11 | 0.00 | 1.01 |
September | 0.250671E+10 | 0.00 | 0.00 | 84045306.76 | 0.00 | 0.00 | 0.409913E+11 | 0.00 | 0.81 |
October | 0.227886E+10 | 0.00 | 0.00 | 83414444.66 | 0.00 | 0.00 | 0.491606E+11 | 0.00 | 0.65 |
November | 0.174565E+10 | 0.00 | 0.00 | 76567798.89 | 0.00 | 0.00 | 0.479352E+11 | 0.00 | 0.50 |
December | 0.157859E+10 | 0.00 | 0.00 | 78317730.79 | 0.00 | 0.00 | 0.474086E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.417701E+11 | 0.667235E+09 | 0.00 | 0.975660E+09 | 14528962.13 | 0.00 | 0.529004E+12 | 0.00 | 0.67 |
Minimum of Months | 0.157859E+10 | 0.00 | 0.00 | 45886197.34 | 0.00 | 0.00 | 0.324110E+11 | 0.00 | 0.36 |
Maximum of Months | 0.801192E+10 | 0.500550E+09 | 0.00 | 94112381.71 | 5918490.50 | 0.00 | 0.528845E+11 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.301564E+12 | 0.00 | 0.00 | 16007734.55 | 0.00 | 0.705830E+10 | 0.342839E+11 | 0.00 | 0.30 |
February | 0.211355E+12 | 0.00 | 0.00 | 91444473.42 | 0.00 | 24834398.20 | 0.971702E+11 | 0.00 | 0.32 |
March | 0.134877E+12 | 0.00 | 0.00 | 0.321819E+09 | 0.00 | 0.00 | 0.224132E+12 | 0.00 | 0.36 |
April | 0.829380E+11 | 0.157978E+09 | 0.00 | 0.391738E+09 | 60639387.41 | 0.00 | 0.251780E+12 | 0.00 | 0.43 |
May | 0.381162E+11 | 5767862.35 | 0.00 | 0.573830E+09 | 0.00 | 0.00 | 0.342331E+12 | 0.00 | 0.59 |
June | 0.212154E+11 | 0.120724E+09 | 0.00 | 0.649080E+09 | 28217234.15 | 0.00 | 0.331052E+12 | 0.00 | 0.70 |
July | 0.270198E+11 | 0.102767E+10 | 0.00 | 0.621068E+09 | 44442664.01 | 0.00 | 0.246606E+12 | 0.00 | 0.67 |
August | 0.177354E+11 | 0.428044E+10 | 0.00 | 0.643945E+09 | 43709337.48 | 0.00 | 0.232726E+12 | 0.00 | 0.66 |
September | 0.271630E+11 | 0.00 | 0.00 | 0.590836E+09 | 0.00 | 0.00 | 0.303896E+12 | 0.00 | 0.63 |
October | 0.822757E+11 | 0.00 | 0.00 | 0.390679E+09 | 0.00 | 0.00 | 0.251042E+12 | 0.00 | 0.42 |
November | 0.163679E+12 | 0.00 | 0.00 | 0.172489E+09 | 0.00 | 0.00 | 0.163694E+12 | 0.00 | 0.33 |
December | 0.251954E+12 | 0.00 | 0.00 | 70179749.42 | 0.00 | 18882364.82 | 0.894994E+11 | 0.00 | 0.30 |
Annual Sum or Average | 0.135989E+13 | 0.559258E+10 | 0.00 | 0.453312E+10 | 0.177009E+09 | 0.710201E+10 | 0.256821E+13 | 0.00 | 0.48 |
Minimum of Months | 0.177354E+11 | 0.00 | 0.00 | 16007734.55 | 0.00 | 0.00 | 0.342839E+11 | 0.00 | 0.30 |
Maximum of Months | 0.301564E+12 | 0.428044E+10 | 0.00 | 0.649080E+09 | 60639387.41 | 0.705830E+10 | 0.342331E+12 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.283063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276349E+10 | 0.00 | 0.00 | 0.29 |
February | 0.248050E+11 | 0.00 | 0.00 | 1023186.85 | 0.00 | 0.101487E+10 | 0.158385E+10 | 0.00 | 0.31 |
March | 0.234434E+11 | 0.00 | 0.00 | 6746890.24 | 0.00 | 0.203914E+09 | 0.730810E+10 | 0.00 | 0.34 |
April | 0.138755E+11 | 3565193.63 | 0.00 | 20400265.45 | 1340159.52 | 0.00 | 0.156960E+11 | 0.00 | 0.40 |
May | 0.910266E+10 | 0.00 | 0.00 | 39804918.66 | 0.00 | 0.00 | 0.260572E+11 | 0.00 | 0.56 |
June | 0.506408E+10 | 4415827.33 | 0.00 | 53268374.19 | 1339207.15 | 0.00 | 0.291101E+11 | 0.00 | 0.69 |
July | 0.390231E+10 | 49505265.10 | 0.00 | 56897824.24 | 1632759.25 | 0.00 | 0.231077E+11 | 0.00 | 0.68 |
August | 0.301680E+10 | 0.269431E+09 | 0.00 | 57393836.64 | 7449895.58 | 0.00 | 0.201281E+11 | 0.00 | 0.65 |
September | 0.825702E+10 | 0.00 | 0.00 | 37212508.06 | 0.00 | 0.00 | 0.203398E+11 | 0.00 | 0.57 |
October | 0.164287E+11 | 0.00 | 0.00 | 13016942.67 | 0.00 | 58877953.79 | 0.109768E+11 | 0.00 | 0.37 |
November | 0.245564E+11 | 0.00 | 0.00 | 1446910.45 | 0.00 | 0.650905E+09 | 0.194135E+10 | 0.00 | 0.31 |
December | 0.277079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182158E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.188466E+12 | 0.326918E+09 | 0.00 | 0.287212E+09 | 11762021.50 | 0.651364E+10 | 0.156249E+12 | 0.00 | 0.46 |
Minimum of Months | 0.301680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.283063E+11 | 0.269431E+09 | 0.00 | 57393836.64 | 7449895.58 | 0.276349E+10 | 0.291101E+11 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.435776E+10 | 0.00 | 0.00 | 20036.38 | 0.00 | 4398965.72 | 39809472.02 | 0.00 | 0.27 |
February | 0.318243E+10 | 0.00 | 0.00 | 771274.14 | 0.00 | 0.00 | 0.657144E+09 | 0.00 | 0.31 |
March | 0.223968E+10 | 0.00 | 0.00 | 3521854.78 | 0.00 | 0.00 | 0.257606E+10 | 0.00 | 0.40 |
April | 0.150879E+10 | 2814666.92 | 0.00 | 6436769.24 | 0.00 | 0.00 | 0.418408E+10 | 0.00 | 0.62 |
May | 0.109357E+10 | 132998.65 | 0.00 | 8556890.16 | 0.00 | 0.00 | 0.502303E+10 | 0.00 | 0.80 |
June | 0.558145E+09 | 2873959.10 | 0.00 | 11464955.61 | 742528.29 | 0.00 | 0.568516E+10 | 0.00 | 1.04 |
July | 0.879531E+09 | 25910127.85 | 0.00 | 12115768.96 | 449982.51 | 0.00 | 0.468852E+10 | 0.00 | 1.12 |
August | 0.110324E+10 | 93534698.20 | 0.00 | 11163124.02 | 630279.22 | 0.00 | 0.397605E+10 | 0.00 | 1.09 |
September | 0.104342E+10 | 0.00 | 0.00 | 7129260.82 | 0.00 | 0.00 | 0.367250E+10 | 0.00 | 0.75 |
October | 0.189469E+10 | 0.00 | 0.00 | 3769637.73 | 0.00 | 0.00 | 0.272962E+10 | 0.00 | 0.48 |
November | 0.258439E+10 | 0.00 | 0.00 | 1562385.70 | 0.00 | 0.00 | 0.140420E+10 | 0.00 | 0.32 |
December | 0.356449E+10 | 0.00 | 0.00 | 271977.08 | 0.00 | 0.00 | 0.353802E+09 | 0.00 | 0.26 |
Annual Sum or Average | 0.240101E+11 | 0.125266E+09 | 0.00 | 66783934.61 | 1822790.02 | 4398965.72 | 0.349900E+11 | 0.00 | 0.62 |
Minimum of Months | 0.558145E+09 | 0.00 | 0.00 | 20036.38 | 0.00 | 0.00 | 39809472.02 | 0.00 | 0.26 |
Maximum of Months | 0.435776E+10 | 93534698.20 | 0.00 | 12115768.96 | 742528.29 | 4398965.72 | 0.568516E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.269782E+10 | 0.00 | 0.00 | 104378.39 | 0.00 | 36760717.16 | 0.100530E+09 | 0.00 | 0.27 |
February | 0.187258E+10 | 0.00 | 0.00 | 1168097.20 | 0.00 | 7475150.75 | 0.744409E+09 | 0.00 | 0.32 |
March | 0.136115E+10 | 0.00 | 0.00 | 4294440.94 | 0.00 | 0.00 | 0.241985E+10 | 0.00 | 0.48 |
April | 0.910098E+09 | 2157244.03 | 0.00 | 7509482.73 | 0.00 | 0.00 | 0.432649E+10 | 0.00 | 0.87 |
May | 0.653897E+09 | 106775.28 | 0.00 | 9312666.60 | 0.00 | 0.00 | 0.500150E+10 | 0.00 | 1.13 |
June | 0.352008E+09 | 1803721.30 | 0.00 | 12557410.03 | 476180.03 | 0.00 | 0.597419E+10 | 0.00 | 1.56 |
July | 0.540803E+09 | 20015504.33 | 0.00 | 13388337.47 | 288571.75 | 0.00 | 0.444615E+10 | 0.00 | 1.54 |
August | 0.759999E+09 | 71523918.97 | 0.00 | 12242039.29 | 125042.97 | 0.00 | 0.386799E+10 | 0.00 | 1.56 |
September | 0.609807E+09 | 0.00 | 0.00 | 8683735.57 | 0.00 | 0.00 | 0.404680E+10 | 0.00 | 1.14 |
October | 0.116903E+10 | 0.00 | 0.00 | 4395310.37 | 0.00 | 0.00 | 0.268901E+10 | 0.00 | 0.62 |
November | 0.180937E+10 | 0.00 | 0.00 | 1140706.03 | 0.00 | 0.00 | 0.782614E+09 | 0.00 | 0.33 |
December | 0.234718E+10 | 0.00 | 0.00 | 381128.92 | 0.00 | 0.00 | 0.203398E+09 | 0.00 | 0.26 |
Annual Sum or Average | 0.150837E+11 | 95607163.92 | 0.00 | 75177733.55 | 889794.76 | 44235867.91 | 0.346029E+11 | 0.00 | 0.84 |
Minimum of Months | 0.352008E+09 | 0.00 | 0.00 | 104378.39 | 0.00 | 0.00 | 0.100530E+09 | 0.00 | 0.26 |
Maximum of Months | 0.269782E+10 | 71523918.97 | 0.00 | 13388337.47 | 476180.03 | 36760717.16 | 0.597419E+10 | 0.00 | 1.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.345189E+10 | 0.00 | 0.00 | 2337547.51 | 0.00 | 0.246442E+09 | 0.163984E+10 | 0.00 | 0.33 |
February | 0.256828E+10 | 0.00 | 0.00 | 5767745.30 | 0.00 | 54080767.02 | 0.304884E+10 | 0.00 | 0.47 |
March | 0.193055E+10 | 0.00 | 0.00 | 10914846.80 | 0.00 | 418102.47 | 0.667872E+10 | 0.00 | 0.75 |
April | 0.134521E+10 | 7436582.20 | 0.00 | 13516486.65 | 0.00 | 0.00 | 0.780250E+10 | 0.00 | 1.07 |
May | 0.109170E+10 | 251843.96 | 0.00 | 14476381.33 | 0.00 | 0.00 | 0.742468E+10 | 0.00 | 1.18 |
June | 0.663659E+09 | 3379032.98 | 0.00 | 15725930.85 | 738861.72 | 0.00 | 0.693430E+10 | 0.00 | 1.35 |
July | 0.835132E+09 | 45121320.65 | 0.00 | 17735041.80 | 447760.52 | 0.00 | 0.591346E+10 | 0.00 | 1.50 |
August | 0.113643E+10 | 0.181051E+09 | 0.00 | 18072991.64 | 29156.93 | 0.00 | 0.517449E+10 | 0.00 | 1.52 |
September | 0.811513E+09 | 0.00 | 0.00 | 19580971.21 | 0.00 | 0.00 | 0.757574E+10 | 0.00 | 1.54 |
October | 0.149502E+10 | 0.00 | 0.00 | 13115256.20 | 0.00 | 0.00 | 0.754170E+10 | 0.00 | 1.02 |
November | 0.254110E+10 | 0.00 | 0.00 | 4795572.46 | 0.00 | 888757.25 | 0.252839E+10 | 0.00 | 0.44 |
December | 0.303649E+10 | 0.00 | 0.00 | 4282880.83 | 0.00 | 36215755.56 | 0.221907E+10 | 0.00 | 0.35 |
Annual Sum or Average | 0.209070E+11 | 0.237240E+09 | 0.00 | 0.140322E+09 | 1215779.17 | 0.338045E+09 | 0.644817E+11 | 0.00 | 0.96 |
Minimum of Months | 0.663659E+09 | 0.00 | 0.00 | 2337547.51 | 0.00 | 0.00 | 0.163984E+10 | 0.00 | 0.33 |
Maximum of Months | 0.345189E+10 | 0.181051E+09 | 0.00 | 19580971.21 | 738861.72 | 0.246442E+09 | 0.780250E+10 | 0.00 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.201962E+10 | 0.00 | 0.00 | 1221173.54 | 0.00 | 0.00 | 0.106977E+10 | 0.00 | 0.30 |
February | 0.699195E+09 | 0.00 | 0.00 | 4514998.98 | 0.00 | 0.00 | 0.307589E+10 | 0.00 | 0.50 |
March | 0.173350E+09 | 0.00 | 0.00 | 11087657.11 | 0.00 | 0.00 | 0.699700E+10 | 0.00 | 0.97 |
April | 0.150536E+09 | 5366568.60 | 0.00 | 17326946.90 | 0.00 | 0.00 | 0.916623E+10 | 0.00 | 1.63 |
May | 0.209234E+09 | 143298.60 | 0.00 | 17684623.78 | 0.00 | 0.00 | 0.722295E+10 | 0.00 | 1.64 |
June | 0.128461E+09 | 8622601.62 | 0.00 | 18884196.65 | 406265.15 | 0.00 | 0.751849E+10 | 0.00 | 2.11 |
July | 0.206832E+09 | 55908712.07 | 0.00 | 24104288.75 | 37083.44 | 0.00 | 0.730845E+10 | 0.00 | 2.54 |
August | 0.264095E+09 | 0.177450E+09 | 0.00 | 24882169.18 | 121788.23 | 0.00 | 0.677077E+10 | 0.00 | 2.43 |
September | 0.166460E+09 | 0.00 | 0.00 | 14579387.12 | 0.00 | 0.00 | 0.577686E+10 | 0.00 | 1.63 |
October | 0.207473E+09 | 0.00 | 0.00 | 9489199.38 | 0.00 | 0.00 | 0.578862E+10 | 0.00 | 1.02 |
November | 0.185581E+09 | 0.00 | 0.00 | 6852817.41 | 0.00 | 0.00 | 0.455950E+10 | 0.00 | 0.62 |
December | 0.145520E+09 | 0.00 | 0.00 | 7108390.61 | 0.00 | 0.00 | 0.464328E+10 | 0.00 | 0.49 |
Annual Sum or Average | 0.455635E+10 | 0.247491E+09 | 0.00 | 0.157736E+09 | 565136.81 | 0.00 | 0.698978E+11 | 0.00 | 1.33 |
Minimum of Months | 0.128461E+09 | 0.00 | 0.00 | 1221173.54 | 0.00 | 0.00 | 0.106977E+10 | 0.00 | 0.30 |
Maximum of Months | 0.201962E+10 | 0.177450E+09 | 0.00 | 24882169.18 | 406265.15 | 0.00 | 0.916623E+10 | 0.00 | 2.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272574E+11 | 0.00 | 0.00 | 0.30 |
February | 0.234503E+11 | 0.00 | 0.00 | 39533.37 | 0.00 | 0.143587E+11 | 0.204320E+09 | 0.00 | 0.31 |
March | 0.350140E+11 | 0.00 | 0.00 | 708832.93 | 0.00 | 0.349705E+10 | 0.882967E+09 | 0.00 | 0.32 |
April | 0.252653E+11 | 26735348.19 | 0.00 | 14742387.67 | 7609474.86 | 0.852350E+09 | 0.941929E+10 | 0.00 | 0.37 |
May | 0.169800E+11 | 1519638.71 | 0.00 | 49412659.43 | 0.00 | 3805777.75 | 0.279095E+11 | 0.00 | 0.60 |
June | 0.922006E+10 | 25083777.07 | 0.00 | 73615808.49 | 3540905.39 | 0.00 | 0.353052E+11 | 0.00 | 0.77 |
July | 0.780900E+10 | 0.217734E+09 | 0.00 | 80108881.56 | 5576991.28 | 0.00 | 0.291787E+11 | 0.00 | 0.80 |
August | 0.783937E+10 | 0.859796E+09 | 0.00 | 69638819.03 | 5484968.09 | 0.00 | 0.227856E+11 | 0.00 | 0.71 |
September | 0.171257E+11 | 0.00 | 0.00 | 39751042.36 | 0.00 | 0.00 | 0.181328E+11 | 0.00 | 0.57 |
October | 0.298844E+11 | 0.00 | 0.00 | 5499706.11 | 0.00 | 0.723849E+09 | 0.372727E+10 | 0.00 | 0.34 |
November | 0.297043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876733E+10 | 0.00 | 0.00 | 0.31 |
December | 0.202601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223888E+11 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.238857E+12 | 0.113087E+10 | 0.00 | 0.333518E+09 | 22212339.62 | 0.778493E+11 | 0.147546E+12 | 0.00 | 0.48 |
Minimum of Months | 0.780900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.350140E+11 | 0.859796E+09 | 0.00 | 80108881.56 | 7609474.86 | 0.272574E+11 | 0.353052E+11 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.863838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143675E+11 | 0.00 | 0.00 | 0.25 |
February | 0.122275E+11 | 0.00 | 0.00 | 1966760.75 | 0.00 | 0.675904E+10 | 0.137615E+10 | 0.00 | 0.26 |
March | 0.146412E+11 | 0.00 | 0.00 | 18701159.71 | 0.00 | 0.147128E+10 | 0.106690E+11 | 0.00 | 0.33 |
April | 0.891442E+10 | 32228343.44 | 0.00 | 50464393.96 | 0.00 | 0.357450E+09 | 0.279497E+11 | 0.00 | 0.63 |
May | 0.745259E+10 | 1575664.58 | 0.00 | 76202384.80 | 0.00 | 5102556.34 | 0.381706E+11 | 0.00 | 0.96 |
June | 0.397882E+10 | 18506771.44 | 0.00 | 0.113746E+09 | 2291606.13 | 0.00 | 0.508243E+11 | 0.00 | 1.39 |
July | 0.358551E+10 | 0.197810E+09 | 0.00 | 0.123128E+09 | 3609321.90 | 0.00 | 0.376522E+11 | 0.00 | 1.35 |
August | 0.310758E+10 | 0.786940E+09 | 0.00 | 0.115409E+09 | 0.00 | 0.00 | 0.336190E+11 | 0.00 | 1.33 |
September | 0.732784E+10 | 0.00 | 0.00 | 71673554.40 | 0.00 | 0.00 | 0.305255E+11 | 0.00 | 0.98 |
October | 0.126379E+11 | 0.00 | 0.00 | 24897457.23 | 0.00 | 0.497896E+09 | 0.134475E+11 | 0.00 | 0.43 |
November | 0.149832E+11 | 0.00 | 0.00 | 1013416.27 | 0.00 | 0.482468E+10 | 0.595871E+09 | 0.00 | 0.26 |
December | 0.109107E+11 | 0.00 | 0.00 | 7146.02 | 0.00 | 0.116751E+11 | 4943700.59 | 0.00 | 0.24 |
Annual Sum or Average | 0.108406E+12 | 0.103706E+10 | 0.00 | 0.597209E+09 | 5900928.03 | 0.399580E+11 | 0.244835E+12 | 0.00 | 0.70 |
Minimum of Months | 0.310758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.149832E+11 | 0.786940E+09 | 0.00 | 0.123128E+09 | 3609321.90 | 0.143675E+11 | 0.508243E+11 | 0.00 | 1.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.228743E+11 | 0.00 | 0.00 | 14199057.02 | 0.00 | 0.161123E+11 | 0.110233E+11 | 0.00 | 0.35 |
February | 0.232332E+11 | 0.00 | 0.00 | 47463196.54 | 0.00 | 0.709922E+10 | 0.294177E+11 | 0.00 | 0.50 |
March | 0.235246E+11 | 0.00 | 0.00 | 88801818.59 | 0.00 | 0.157157E+10 | 0.490766E+11 | 0.00 | 0.63 |
April | 0.156149E+11 | 0.135269E+09 | 0.00 | 0.102565E+09 | 0.00 | 0.498081E+09 | 0.544283E+11 | 0.00 | 0.84 |
May | 0.132206E+11 | 3343999.47 | 0.00 | 0.127845E+09 | 0.00 | 7612187.01 | 0.613016E+11 | 0.00 | 1.07 |
June | 0.912648E+10 | 33169969.01 | 0.00 | 0.130861E+09 | 3543510.71 | 0.00 | 0.545592E+11 | 0.00 | 1.16 |
July | 0.778184E+10 | 0.455219E+09 | 0.00 | 0.146138E+09 | 5581094.70 | 0.00 | 0.457098E+11 | 0.00 | 1.27 |
August | 0.616872E+10 | 0.201219E+10 | 0.00 | 0.154626E+09 | 0.00 | 0.00 | 0.402554E+11 | 0.00 | 1.24 |
September | 0.106471E+11 | 0.00 | 0.00 | 0.187510E+09 | 0.00 | 0.00 | 0.662597E+11 | 0.00 | 1.48 |
October | 0.181241E+11 | 0.00 | 0.00 | 0.117742E+09 | 0.00 | 0.405645E+09 | 0.555256E+11 | 0.00 | 0.83 |
November | 0.273944E+11 | 0.00 | 0.00 | 32041531.38 | 0.00 | 0.482086E+10 | 0.168417E+11 | 0.00 | 0.42 |
December | 0.231200E+11 | 0.00 | 0.00 | 26689465.37 | 0.00 | 0.135741E+11 | 0.188834E+11 | 0.00 | 0.39 |
Annual Sum or Average | 0.200830E+12 | 0.263919E+10 | 0.00 | 0.117648E+10 | 9124605.41 | 0.440895E+11 | 0.503282E+12 | 0.00 | 0.85 |
Minimum of Months | 0.616872E+10 | 0.00 | 0.00 | 14199057.02 | 0.00 | 0.00 | 0.110233E+11 | 0.00 | 0.35 |
Maximum of Months | 0.273944E+11 | 0.201219E+10 | 0.00 | 0.187510E+09 | 5581094.70 | 0.161123E+11 | 0.662597E+11 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155717E+11 | 0.00 | 0.00 | 231787.46 | 0.00 | 0.121525E+11 | 0.292565E+09 | 0.00 | 0.30 |
February | 0.176511E+11 | 0.00 | 0.00 | 5730348.39 | 0.00 | 0.482941E+10 | 0.376289E+10 | 0.00 | 0.34 |
March | 0.191385E+11 | 0.00 | 0.00 | 19737108.17 | 0.00 | 0.850267E+09 | 0.115065E+11 | 0.00 | 0.40 |
April | 0.111700E+11 | 68409029.52 | 0.00 | 48807567.13 | 50287.04 | 77539109.35 | 0.256137E+11 | 0.00 | 0.67 |
May | 0.696467E+10 | 1424500.92 | 0.00 | 0.122554E+09 | 0.00 | 2241238.94 | 0.431784E+11 | 0.00 | 1.20 |
June | 0.383520E+10 | 84525217.94 | 0.00 | 0.113175E+09 | 2281154.88 | 0.00 | 0.411526E+11 | 0.00 | 1.36 |
July | 0.244389E+10 | 0.531481E+09 | 0.00 | 0.137924E+09 | 412634.51 | 0.00 | 0.392125E+11 | 0.00 | 1.63 |
August | 0.257770E+10 | 0.154758E+10 | 0.00 | 0.121841E+09 | 3533576.96 | 0.00 | 0.288790E+11 | 0.00 | 1.29 |
September | 0.642153E+10 | 0.00 | 0.00 | 92004525.10 | 0.00 | 0.00 | 0.323364E+11 | 0.00 | 1.16 |
October | 0.154965E+11 | 0.00 | 0.00 | 24505620.84 | 0.00 | 0.155347E+09 | 0.125428E+11 | 0.00 | 0.47 |
November | 0.212299E+11 | 0.00 | 0.00 | 2543695.19 | 0.00 | 0.270968E+10 | 0.137580E+10 | 0.00 | 0.32 |
December | 0.187978E+11 | 0.00 | 0.00 | 978574.60 | 0.00 | 0.788182E+10 | 0.968119E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.141298E+12 | 0.223342E+10 | 0.00 | 0.690035E+09 | 6277653.39 | 0.286589E+11 | 0.240821E+12 | 0.00 | 0.79 |
Minimum of Months | 0.244389E+10 | 0.00 | 0.00 | 231787.46 | 0.00 | 0.00 | 0.292565E+09 | 0.00 | 0.30 |
Maximum of Months | 0.212299E+11 | 0.154758E+10 | 0.00 | 0.137924E+09 | 3533576.96 | 0.121525E+11 | 0.431784E+11 | 0.00 | 1.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.724827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337771E+10 | 0.00 | 0.00 | 0.31 |
February | 0.125399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230364E+10 | 0.00 | 0.00 | 0.32 |
March | 0.278990E+10 | 0.00 | 0.00 | 17164.01 | 0.00 | 0.103939E+10 | 30674810.26 | 0.00 | 0.34 |
April | 0.233476E+10 | 585362.82 | 0.00 | 1096056.12 | 168163.58 | 0.389257E+09 | 0.737828E+09 | 0.00 | 0.38 |
May | 0.190689E+10 | 0.00 | 0.00 | 4104148.57 | 0.00 | 52194894.61 | 0.243806E+10 | 0.00 | 0.58 |
June | 0.114395E+10 | 814001.62 | 0.00 | 6768322.66 | 168044.07 | 1922383.40 | 0.330391E+10 | 0.00 | 0.77 |
July | 0.824832E+09 | 9699852.25 | 0.00 | 8096503.36 | 204879.07 | 0.00 | 0.295342E+10 | 0.00 | 0.81 |
August | 0.845822E+09 | 51740492.51 | 0.00 | 6969771.17 | 934814.91 | 0.00 | 0.209986E+10 | 0.00 | 0.71 |
September | 0.187052E+10 | 0.00 | 0.00 | 3058888.83 | 0.00 | 27551232.57 | 0.143330E+10 | 0.00 | 0.55 |
October | 0.255632E+10 | 0.00 | 0.00 | 228691.28 | 0.00 | 0.545564E+09 | 0.163930E+09 | 0.00 | 0.35 |
November | 0.150387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197705E+10 | 0.00 | 0.00 | 0.31 |
December | 0.725963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314534E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.184816E+11 | 62839709.20 | 0.00 | 30339545.98 | 1475901.63 | 0.128596E+11 | 0.131610E+11 | 0.00 | 0.48 |
Minimum of Months | 0.724827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.278990E+10 | 51740492.51 | 0.00 | 8096503.36 | 934814.91 | 0.337771E+10 | 0.330391E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.688527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195722E+10 | 0.00 | 0.00 | 0.31 |
February | 0.105183E+10 | 0.00 | 0.00 | 13598.55 | 0.00 | 0.121590E+10 | 18748336.70 | 0.00 | 0.32 |
March | 0.161612E+10 | 0.00 | 0.00 | 1081010.61 | 0.00 | 0.436726E+09 | 0.698009E+09 | 0.00 | 0.37 |
April | 0.102745E+10 | 707959.54 | 0.00 | 4384997.36 | 0.00 | 0.143478E+09 | 0.254903E+10 | 0.00 | 0.65 |
May | 0.846194E+09 | 0.00 | 0.00 | 7300729.42 | 0.00 | 32654434.48 | 0.384467E+10 | 0.00 | 0.98 |
June | 0.425011E+09 | 611732.48 | 0.00 | 11295912.95 | 108013.21 | 3291195.34 | 0.530573E+10 | 0.00 | 1.45 |
July | 0.385131E+09 | 8673806.21 | 0.00 | 13265585.36 | 45963.30 | 0.00 | 0.402385E+10 | 0.00 | 1.43 |
August | 0.306666E+09 | 47322203.80 | 0.00 | 12207950.57 | 91057.51 | 0.00 | 0.340622E+10 | 0.00 | 1.40 |
September | 0.850920E+09 | 0.00 | 0.00 | 6753500.53 | 0.00 | 9207326.74 | 0.293260E+10 | 0.00 | 1.00 |
October | 0.126785E+10 | 0.00 | 0.00 | 1810039.42 | 0.00 | 0.276254E+09 | 0.108423E+10 | 0.00 | 0.45 |
November | 0.109910E+10 | 0.00 | 0.00 | 8462.04 | 0.00 | 0.113817E+10 | 7457123.49 | 0.00 | 0.31 |
December | 0.704079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180619E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.102689E+11 | 57315702.03 | 0.00 | 58121786.82 | 245034.02 | 0.701909E+10 | 0.238706E+11 | 0.00 | 0.75 |
Minimum of Months | 0.306666E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.161612E+10 | 47322203.80 | 0.00 | 13265585.36 | 108013.21 | 0.195722E+10 | 0.530573E+10 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.146541E+10 | 0.00 | 0.00 | 821052.50 | 0.00 | 0.227286E+10 | 0.681600E+09 | 0.00 | 0.33 |
February | 0.161669E+10 | 0.00 | 0.00 | 3457520.18 | 0.00 | 0.125650E+10 | 0.230998E+10 | 0.00 | 0.47 |
March | 0.204125E+10 | 0.00 | 0.00 | 6956163.89 | 0.00 | 0.596998E+09 | 0.459688E+10 | 0.00 | 0.65 |
April | 0.145480E+10 | 2773389.74 | 0.00 | 9180045.81 | 0.00 | 0.295075E+09 | 0.530556E+10 | 0.00 | 0.84 |
May | 0.139664E+10 | 0.00 | 0.00 | 11914591.92 | 0.00 | 50894395.92 | 0.611849E+10 | 0.00 | 1.04 |
June | 0.979069E+09 | 1099038.75 | 0.00 | 12701215.73 | 168028.62 | 1903466.78 | 0.562834E+10 | 0.00 | 1.17 |
July | 0.750036E+09 | 20197824.74 | 0.00 | 17281858.53 | 33732.73 | 0.00 | 0.498687E+10 | 0.00 | 1.31 |
August | 0.671171E+09 | 0.117019E+09 | 0.00 | 16706383.88 | 36215.25 | 0.00 | 0.407324E+10 | 0.00 | 1.27 |
September | 0.116704E+10 | 0.00 | 0.00 | 17998288.56 | 0.00 | 21897098.50 | 0.661162E+10 | 0.00 | 1.47 |
October | 0.160292E+10 | 0.00 | 0.00 | 9302300.94 | 0.00 | 0.321521E+09 | 0.544576E+10 | 0.00 | 0.86 |
November | 0.180628E+10 | 0.00 | 0.00 | 1891075.12 | 0.00 | 0.130031E+10 | 0.984677E+09 | 0.00 | 0.40 |
December | 0.141938E+10 | 0.00 | 0.00 | 1593623.08 | 0.00 | 0.199096E+10 | 0.117286E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.163707E+11 | 0.141089E+09 | 0.00 | 0.109804E+09 | 237976.60 | 0.810892E+10 | 0.479159E+11 | 0.00 | 0.85 |
Minimum of Months | 0.671171E+09 | 0.00 | 0.00 | 821052.50 | 0.00 | 0.00 | 0.681600E+09 | 0.00 | 0.33 |
Maximum of Months | 0.204125E+10 | 0.117019E+09 | 0.00 | 17998288.56 | 168028.62 | 0.227286E+10 | 0.661162E+10 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.941644E+09 | 0.00 | 0.00 | 11104.34 | 0.00 | 0.164378E+10 | 16417822.29 | 0.00 | 0.30 |
February | 0.120741E+10 | 0.00 | 0.00 | 404525.58 | 0.00 | 0.888878E+09 | 0.299677E+09 | 0.00 | 0.34 |
March | 0.168629E+10 | 0.00 | 0.00 | 1507179.04 | 0.00 | 0.331678E+09 | 0.114708E+10 | 0.00 | 0.44 |
April | 0.114435E+10 | 1568321.04 | 0.00 | 4389263.20 | 0.00 | 0.117798E+09 | 0.252880E+10 | 0.00 | 0.72 |
May | 0.802736E+09 | 0.00 | 0.00 | 11979607.62 | 0.00 | 15957568.68 | 0.431533E+10 | 0.00 | 1.18 |
June | 0.517179E+09 | 2617321.45 | 0.00 | 11062813.99 | 108746.86 | 141753.65 | 0.414804E+10 | 0.00 | 1.41 |
July | 0.333182E+09 | 22860184.61 | 0.00 | 17288142.41 | 12261.52 | 0.00 | 0.411780E+10 | 0.00 | 1.69 |
August | 0.275964E+09 | 89282263.72 | 0.00 | 12952398.35 | 153102.49 | 0.00 | 0.286871E+10 | 0.00 | 1.29 |
September | 0.760099E+09 | 0.00 | 0.00 | 8592141.83 | 0.00 | 114917.77 | 0.307422E+10 | 0.00 | 1.15 |
October | 0.142849E+10 | 0.00 | 0.00 | 1842122.35 | 0.00 | 0.183976E+09 | 0.122554E+10 | 0.00 | 0.51 |
November | 0.137140E+10 | 0.00 | 0.00 | 160116.05 | 0.00 | 0.787593E+09 | 95009898.12 | 0.00 | 0.32 |
December | 0.104732E+10 | 0.00 | 0.00 | 30646.64 | 0.00 | 0.136427E+10 | 33674600.56 | 0.00 | 0.29 |
Annual Sum or Average | 0.115161E+11 | 0.116328E+09 | 0.00 | 70220061.40 | 274110.87 | 0.533419E+10 | 0.238703E+11 | 0.00 | 0.81 |
Minimum of Months | 0.275964E+09 | 0.00 | 0.00 | 11104.34 | 0.00 | 0.00 | 16417822.29 | 0.00 | 0.29 |
Maximum of Months | 0.168629E+10 | 89282263.72 | 0.00 | 17288142.41 | 153102.49 | 0.164378E+10 | 0.431533E+10 | 0.00 | 1.69 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2878209.23 | 0.00 | 0.00 | 0.621654E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7196494.68 | 0.00 | 0.00 | 0.514710E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 14300724.10 | 0.00 | 0.00 | 0.541751E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 17958433.57 | 0.00 | 0.00 | 0.420566E+09 | 0.00 | 0.29 |
May | 0.00 | 14541.18 | 0.00 | 4049491.50 | 0.00 | 0.00 | 0.380334E+09 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 8807495.25 | 0.00 | 0.00 | 0.296006E+09 | 0.00 | 0.30 |
July | 0.00 | 3920110.80 | 0.00 | 11671317.49 | 0.00 | 0.00 | 0.169215E+09 | 0.00 | 0.28 |
August | 0.00 | 12786641.15 | 0.00 | 15122893.42 | 0.00 | 0.00 | 0.127875E+09 | 0.00 | 0.31 |
September | 0.00 | 84913.61 | 0.00 | 3913663.62 | 0.00 | 0.00 | 0.256765E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8329522.53 | 0.00 | 0.00 | 0.425676E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11849089.35 | 0.00 | 0.00 | 0.495936E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 17063640.00 | 0.00 | 0.00 | 0.576538E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 16806206.73 | 0.00 | 0.123141E+09 | 0.00 | 0.00 | 0.482702E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2878209.23 | 0.00 | 0.00 | 0.127875E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 12786641.15 | 0.00 | 17958433.57 | 0.00 | 0.00 | 0.621654E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.115820E+10 | 0.00 | 0.00 | 7504205.07 | 0.00 | 0.00 | 0.508993E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 54118956.32 | 0.00 | 0.00 | 0.516787E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.125426E+09 | 0.00 | 0.00 | 0.543418E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.165322E+09 | 0.00 | 0.00 | 0.421826E+10 | 0.00 | 0.29 |
May | 0.00 | 123856.39 | 0.00 | 34371753.93 | 0.00 | 0.00 | 0.381588E+10 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 81330111.76 | 0.00 | 0.00 | 0.296834E+10 | 0.00 | 0.30 |
July | 0.00 | 38826591.70 | 0.00 | 0.110122E+09 | 0.00 | 0.00 | 0.169948E+10 | 0.00 | 0.28 |
August | 0.00 | 0.127338E+09 | 0.00 | 0.143566E+09 | 0.00 | 0.00 | 0.128681E+10 | 0.00 | 0.31 |
September | 0.00 | 732791.83 | 0.00 | 33721319.79 | 0.00 | 0.00 | 0.259264E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 71041433.37 | 0.00 | 0.00 | 0.427068E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 99376176.62 | 0.00 | 0.00 | 0.497842E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.144200E+09 | 0.00 | 0.00 | 0.579154E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.115820E+10 | 0.167021E+09 | 0.00 | 0.107010E+10 | 0.00 | 0.00 | 0.473140E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 7504205.07 | 0.00 | 0.00 | 0.128681E+10 | 0.00 | 0.28 |
Maximum of Months | 0.115820E+10 | 0.127338E+09 | 0.00 | 0.165322E+09 | 0.00 | 0.00 | 0.579154E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.366722E+09 | 0.00 | 0.00 | 259418.94 | 0.00 | 0.00 | 0.248541E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4510131.36 | 0.00 | 0.00 | 0.517811E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 11493121.49 | 0.00 | 0.00 | 0.544555E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 15954572.51 | 0.00 | 0.00 | 0.422468E+09 | 0.00 | 0.29 |
May | 884877.28 | 12393.52 | 0.00 | 3131655.00 | 0.00 | 0.00 | 0.381332E+09 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 8020654.19 | 0.00 | 0.00 | 0.297034E+09 | 0.00 | 0.30 |
July | 0.00 | 3903155.14 | 0.00 | 10968016.81 | 0.00 | 0.00 | 0.170006E+09 | 0.00 | 0.28 |
August | 0.00 | 12773667.68 | 0.00 | 14262358.68 | 0.00 | 0.00 | 0.128814E+09 | 0.00 | 0.31 |
September | 0.00 | 70975.39 | 0.00 | 3020497.19 | 0.00 | 0.00 | 0.261059E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6239177.14 | 0.00 | 0.00 | 0.428438E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 8860981.23 | 0.00 | 0.00 | 0.499190E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13291387.00 | 0.00 | 0.00 | 0.580309E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.367607E+09 | 16760191.74 | 0.00 | 0.100012E+09 | 0.00 | 0.00 | 0.447956E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 259418.94 | 0.00 | 0.00 | 0.128814E+09 | 0.00 | 0.28 |
Maximum of Months | 0.366722E+09 | 12773667.68 | 0.00 | 15954572.51 | 0.00 | 0.00 | 0.580309E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.537471E+09 | 0.00 | 0.00 | 0.416653E+12 | 0.00 | 9.07 |
February | 0.00 | 0.00 | 0.00 | 0.950603E+09 | 0.00 | 0.00 | 0.643561E+12 | 0.00 | 17.31 |
March | 0.00 | 0.00 | 0.00 | 0.147902E+10 | 0.00 | 0.00 | 0.988090E+12 | 0.00 | 27.26 |
April | 0.00 | 0.00 | 0.00 | 0.211902E+10 | 0.00 | 0.00 | 0.108328E+13 | 0.00 | 37.35 |
May | 0.00 | 0.00 | 0.00 | 0.550863E+09 | 0.00 | 0.00 | 0.366341E+12 | 0.00 | 16.29 |
June | 0.00 | 0.00 | 0.00 | 0.106637E+10 | 0.00 | 0.00 | 0.542689E+12 | 0.00 | 30.82 |
July | 0.00 | 0.943622E+09 | 0.00 | 0.183588E+10 | 0.00 | 0.00 | 0.597425E+12 | 0.00 | 39.17 |
August | 0.00 | 0.115763E+10 | 0.00 | 0.245746E+10 | 0.00 | 0.00 | 0.443676E+12 | 0.00 | 40.86 |
September | 0.00 | 0.00 | 0.00 | 0.516874E+09 | 0.00 | 0.00 | 0.324563E+12 | 0.00 | 18.83 |
October | 0.00 | 0.00 | 0.00 | 0.101424E+10 | 0.00 | 0.00 | 0.630577E+12 | 0.00 | 23.32 |
November | 0.00 | 0.00 | 0.00 | 0.143754E+10 | 0.00 | 0.00 | 0.903977E+12 | 0.00 | 27.07 |
December | 0.00 | 0.00 | 0.00 | 0.207769E+10 | 0.00 | 0.00 | 0.127399E+13 | 0.00 | 30.24 |
Annual Sum or Average | 0.00 | 0.210126E+10 | 0.00 | 0.160430E+11 | 0.00 | 0.00 | 0.821482E+13 | 0.00 | 26.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.516874E+09 | 0.00 | 0.00 | 0.324563E+12 | 0.00 | 9.07 |
Maximum of Months | 0.00 | 0.115763E+10 | 0.00 | 0.245746E+10 | 0.00 | 0.00 | 0.127399E+13 | 0.00 | 40.86 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:56:56
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.108783E+12 | 0.230038E+11 | 0.00 | 0.182211E+13 | 0.595227E+11 |
February | 0.220979E+12 | 0.210181E+11 | 0.00 | 0.208691E+13 | 0.142061E+12 |
March | 0.410159E+12 | 0.202859E+11 | 0.00 | 0.274909E+13 | 0.287757E+12 |
April | 0.639367E+12 | 0.194970E+11 | 0.00 | 0.289835E+13 | 0.572406E+12 |
May | 0.844130E+12 | 0.156399E+11 | 0.00 | 0.228089E+13 | 0.315910E+12 |
June | 0.858512E+12 | 0.128631E+11 | 0.00 | 0.230739E+13 | 0.626324E+12 |
July | 0.903470E+12 | 0.111659E+11 | 0.00 | 0.235448E+13 | 0.128990E+13 |
August | 0.708434E+12 | 0.889232E+10 | 0.00 | 0.192142E+13 | 0.209848E+13 |
September | 0.490466E+12 | 0.749640E+10 | 0.00 | 0.223129E+13 | 0.446748E+12 |
October | 0.308511E+12 | 0.164968E+11 | 0.00 | 0.250404E+13 | 0.248782E+12 |
November | 0.127837E+12 | 0.186516E+11 | 0.00 | 0.259424E+13 | 0.230696E+12 |
December | 0.789625E+11 | 0.198613E+11 | 0.00 | 0.284599E+13 | 0.298660E+12 |
Annual Sum or Average | 0.569961E+13 | 0.194872E+12 | 0.00 | 0.285962E+14 | 0.661725E+13 |
Minimum of Months | 0.789625E+11 | 0.749640E+10 | 0.00 | 0.182211E+13 | 0.595227E+11 |
Maximum of Months | 0.903470E+12 | 0.230038E+11 | 0.00 | 0.289835E+13 | 0.209848E+13 |