Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2023-10-16 08:28:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2085.95 | 418.68 | 418.68 |
Net Site Energy | 2085.95 | 418.68 | 418.68 |
Total Source Energy | 5828.05 | 1169.78 | 1169.78 |
Net Source Energy | 5828.05 | 1169.78 | 1169.78 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 292.02 | 231.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 116.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 364.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 111.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 104.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 141.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1712.38 | 373.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 292.02 | 231.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 116.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 364.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 111.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 17.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 104.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 141.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 292.02 | 231.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 116.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 364.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 111.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 17.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 104.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 141.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 95.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 103.05 | 74.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 145.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 343.70 | 74.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 95.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 103.05 | 74.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 145.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 343.70 | 74.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1712.379 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1712.379 | 100.00 |
Total On-Site and Utility Electric Sources | 1712.379 | 100.00 |
Total Electricity End Uses | 1712.379 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 349.83 |
Time Setpoint Not Met During Occupied Cooling | 79.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2891.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 10.1959 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 10.1959 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.1959 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 10.1959 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
Total | 4982.19 | 10.1959 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 10.1959 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 10.1959 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-JAN-07:10 | 10-JAN-21:40 | - | - | - | - | - | - | - | - | - | - | 05-JAN-12:09 |
Heating | 225214.60 | 148071.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12752.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 8596.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 353.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8787.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8706.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 276810.72 | 156778.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 225214.60 | 148071.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 12752.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 8596.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 353.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8787.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8706.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 924.81 | 251.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 368.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1154.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 353.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 54.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 332.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 153.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5423.10 | 404.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 185.62 | 50.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 73.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 231.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 66.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 30.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1088.50 | 81.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 185.62 | 50.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 73.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 231.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 66.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 30.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1088.50 | 81.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.52 | 0.212681 | 0.234000 | 0.824580 | 0.567149 | 0.500000 | 0.001791 |
CORE_MID VAV BOX COMPONENT | 2.66 | 0.282199 | 0.303000 | 0.804698 | 0.752530 | 0.500000 | 0.001350 |
CORE_TOP VAV BOX COMPONENT | 2.76 | 0.271740 | 0.301000 | 0.830154 | 0.724640 | 0.500000 | 0.001402 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.857512 | 0.184244 | 0.204000 | 0.174932 | 0.491318 | 0.500000 | 0.002068 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.994191 | 0.100606 | 0.200000 | 0.198838 | 0.300000 | 0.500000 | 0.003787 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.34 | 0.118291 | 0.200000 | 0.267124 | 0.315442 | 0.500000 | 0.003221 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.12 | 0.088933 | 0.200000 | 0.224922 | 0.300000 | 0.500000 | 0.004284 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.680248 | 0.232256 | 0.255000 | 0.173463 | 0.619349 | 0.500000 | 0.001640 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.821968 | 0.121686 | 0.200000 | 0.164394 | 0.324495 | 0.500000 | 0.003131 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.08 | 0.146768 | 0.200000 | 0.215294 | 0.391382 | 0.500000 | 0.002596 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.893578 | 0.111927 | 0.200000 | 0.178716 | 0.300000 | 0.500000 | 0.003404 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.755561 | 0.209105 | 0.225000 | 0.170001 | 0.557614 | 0.500000 | 0.001822 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.986072 | 0.101435 | 0.200000 | 0.197214 | 0.300000 | 0.500000 | 0.003756 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.23 | 0.128391 | 0.200000 | 0.246109 | 0.342377 | 0.500000 | 0.002967 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 1.05 | 0.095474 | 0.200000 | 0.209512 | 0.300000 | 0.500000 | 0.003991 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 24086.03 |
CORE_MID VAV BOX REHEAT COIL | 27649.75 |
CORE_TOP VAV BOX REHEAT COIL | 48057.58 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 23410.75 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15325.99 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 23634.49 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15486.94 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18240.61 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12034.66 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 18449.20 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 12172.81 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 18523.59 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 12199.63 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 18719.50 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 12344.64 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.50 | 1.56 | 7.00 | 2.60 | 6.20 | 6.20 | 0.300000 | 0.419463 | 6.20 |
PACU_VAV_MID | 3.34 | 1.63 | 6.68 | 3.06 | 5.62 | 5.62 | 0.300000 | 0.544870 | 5.62 |
PACU_VAV_TOP | 3.53 | 1.70 | 7.07 | 4.31 | 6.39 | 6.39 | 0.300000 | 0.674135 | 6.39 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 6.20 |
PACU_VAV_MID_OA_CONTROLLER | 5.62 |
PACU_VAV_TOP_OA_CONTROLLER | 6.39 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 6.20 | 102653.28 | 0.800655 | 2.07 | 34214.34 | 0.800655 |
PACU_VAV_MID COOLING COIL | 5.62 | 93021.59 | 0.800655 | 1.87 | 31004.10 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 6.39 | 105850.23 | 0.800655 | 2.13 | 35279.88 | 0.800655 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 47257.78 |
PACU_VAV_MID HEATING COIL | 48692.45 |
PACU_VAV_TOP HEATING COIL | 47498.09 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 6.20 |
PACU_VAV_MID FAN | 5.62 |
PACU_VAV_TOP FAN | 6.39 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 35.030 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7597 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7464 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.9868 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.082 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.106 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7793 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.237 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.236 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.31468885E-12 | 0.58742715E-14 | -0.96802560E-13 | 0.16792992E-15 |
43 | 6 | 0.28872123E-07 | 0.21416477E-09 | 0.66123209E-08 | -0.13627602E-12 |
44 | 5 | -0.19112651E-03 | 0.18301600E-05 | -0.98293898E-04 | 0.65360363E-08 |
45 | 4 | 0.29333920 | 0.88954174E-03 | 0.10011225 | -0.33739231E-04 |
46 | 3 | -7.2899446 | 0.27524297E-01 | -2.3459205 | 0.29124746E-01 |
47 | 2 | 40.949034 | 0.97737712E-01 | 15.293846 | -0.33420785 |
48 | 1 | -80.605481 | 0.44056480E-01 | -29.167461 | 1.0798913 |
49 | 0 | 46.824338 | 0.88531397E-03 | 16.290617 | |
50 | 7 | -0.30618227E-12 | 0.12614254E-14 | -0.97456297E-13 | 0.16278992E-15 |
51 | 6 | 0.29029541E-07 | 0.21075172E-09 | 0.66470638E-08 | -0.13712239E-12 |
52 | 5 | -0.19192439E-03 | 0.17992386E-05 | -0.98693455E-04 | 0.65698920E-08 |
53 | 4 | 0.29427084 | 0.87374093E-03 | 0.10044741 | -0.33870887E-04 |
54 | 3 | -7.3083902 | 0.27014250E-01 | -2.3513943 | 0.29215155E-01 |
55 | 2 | 41.009863 | 0.95860246E-01 | 15.316286 | -0.33488536 |
56 | 1 | -80.652088 | 0.43184114E-01 | -29.187576 | 1.0808846 |
57 | 0 | 46.824338 | 0.86726935E-03 | 16.290137 | |
58 | 7 | -0.27636417E-12 | 0.12990813E-14 | -0.82271001E-13 | 0.80162457E-16 |
59 | 6 | 0.26158967E-07 | 0.26982527E-09 | 0.60134738E-08 | -0.12176112E-12 |
60 | 5 | -0.17726759E-03 | 0.23481051E-05 | -0.91336903E-04 | 0.59516496E-08 |
61 | 4 | 0.27699908 | 0.11597994E-02 | 0.94241662E-01 | -0.31446529E-04 |
62 | 3 | -6.9660490 | 0.36401088E-01 | -2.2498311 | 0.27538282E-01 |
63 | 2 | 39.880486 | 0.13088809 | 14.898993 | -0.32230875 |
64 | 1 | -79.786295 | 0.59645051E-01 | -28.813249 | 1.0624348 |
65 | 0 | 46.824344 | 0.12114519E-02 | 16.299244 | |
66 | 7 | -0.19168505E-08 | -0.51383041E-15 | 0.68469349E-14 | -0.93730203E-16 |
67 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
68 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
69 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
70 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
71 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
72 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
73 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
74 | 7 | -0.18147523E-08 | -0.43765969E-15 | 0.59880535E-14 | -0.82299290E-16 |
75 | 6 | 0.64914511E-05 | 0.44428550E-08 | 0.31873263E-02 | -0.26737964E-04 |
76 | 5 | -0.46689866E-03 | 0.26323880E-05 | -0.22358000 | 0.19548742E-02 |
77 | 4 | 0.10740407E-01 | 0.11982633E-03 | 4.8271378 | -0.45241835E-01 |
78 | 3 | -0.94318369E-01 | 0.95296379E-03 | -38.007814 | 0.39850340 |
79 | 2 | 0.33490849 | 0.15853305E-02 | 116.45748 | -1.4175852 |
80 | 1 | -0.48339250 | 0.48313585E-03 | -143.89172 | 2.0487838 |
81 | 0 | 0.23567793 | 0.11657420E-04 | 60.838472 | |
82 | 7 | -0.19168505E-08 | -0.51383063E-15 | 0.68469351E-14 | -0.93730206E-16 |
83 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
84 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
85 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
86 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
87 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
88 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
89 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
90 | 7 | -0.18146260E-08 | -0.43662845E-15 | 0.62700332E-14 | -0.82012168E-16 |
91 | 6 | 0.64918823E-05 | 0.44431590E-08 | 0.31873251E-02 | -0.26737954E-04 |
92 | 5 | -0.46693053E-03 | 0.26325692E-05 | -0.22357993 | 0.19548736E-02 |
93 | 4 | 0.10741146E-01 | 0.11983458E-03 | 4.8271366 | -0.45241823E-01 |
94 | 3 | -0.94324870E-01 | 0.95302955E-03 | -38.007807 | 0.39850333 |
95 | 2 | 0.33493160 | 0.15854399E-02 | 116.45746 | -1.4175850 |
96 | 1 | -0.48342587 | 0.48316934E-03 | -143.89172 | 2.0487836 |
97 | 0 | 0.23569420 | 0.11658190E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.419_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.419_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.973 | 0.1730 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3532E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3601E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5191E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5250E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.5745E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.6222E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.6026E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6282E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1816 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1047 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2085 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1213 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1202 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2555E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0870E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9083E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3535E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3623E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5194E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5275E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.5774E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.6363E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.6024E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6280E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.9569E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.1943E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.7754E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.9959E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.2633E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1697E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9724E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8144E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.8346E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.8639E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.6421E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.6634E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8188E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.8264E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3717E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3805E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.1122E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.1759E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.2694E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3218E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6829E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.7225E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6024E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.6280E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.9798E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8511E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8510E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1822E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5212E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4806E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0870E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9083E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.1117E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.1770E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.2680E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3194E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6802E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.7124E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6026E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.6282E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.9903E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2080E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2578E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7273E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.8289E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4832E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9724E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8145E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5804E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.6650E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0294E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.1241E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9426E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.9746E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3719E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3807E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1863 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1280 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2114 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1479 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1300 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.6680E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.7993E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7067E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.6550E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.0203E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.4912E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.8316E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.0631E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.0503E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.8615E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7478E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.6515E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.6941E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.4471E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.9060E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.1166E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1391E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.7993E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7067E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.7543E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0776E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.0589E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6195E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6722E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3927E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.8615E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7479E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1863 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1280 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2114 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1479 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1300 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.6672E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.7987E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.7064E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.6549E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.0199E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.4911E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.8312E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.0627E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.0499E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.8609E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7475E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.6517E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.6939E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.4472E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.9059E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.1163E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.1389E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.7987E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7064E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.7543E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0774E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.0589E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6192E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.6718E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3923E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.8610E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7475E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 42751.92110 | 42751.92110 | 3.52385 | 3.52385 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 10696.82370 | 10696.82370 | 0.51641 | 0.51641 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 32248.94578 | 32248.94578 | 2.65577 | 2.65577 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 19494.79558 | 19494.79558 | 0.94658 | 0.94658 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 33198.42009 | 33198.42009 | 2.75799 | 2.75799 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 32.76000 | 6.30583E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 33791.80222 | 33791.80222 | 1.64524 | 1.64524 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 10322.63028 | 10322.63028 | 0.85751 | 0.85751 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.08000 | 6.30633E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 16426.21221 | 16426.21221 | 0.80146 | 0.80146 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11968.05619 | 11968.05619 | 0.99419 | 0.99419 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.96000 | 6.29539E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 10752.98655 | 10752.98655 | 0.52468 | 0.52468 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 16078.08506 | 16078.08506 | 1.33562 | 1.33562 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.30663E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 16582.93379 | 16582.93379 | 0.80912 | 0.80912 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 13538.01358 | 13538.01358 | 1.12461 | 1.12461 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 10865.72617 | 10865.72617 | 0.53019 | 0.53019 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 8188.57014 | 8188.57014 | 0.68025 | 0.68025 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.40000 | 6.30683E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 12803.13894 | 12803.13894 | 0.62446 | 0.62446 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9894.63868 | 9894.63868 | 0.82197 | 0.82197 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.86667 | 6.29676E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 8446.48416 | 8446.48416 | 0.41200 | 0.41200 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12958.19823 | 12958.19823 | 1.07647 | 1.07647 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.40000 | 6.30683E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 12949.23911 | 12949.23911 | 0.63160 | 0.63160 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 10756.65385 | 10756.65385 | 0.89358 | 0.89358 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 28.76000 | 6.29966E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 8543.24095 | 8543.24095 | 0.41673 | 0.41673 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 9095.28345 | 9095.28345 | 0.75556 | 0.75556 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.40000 | 6.30683E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 13002.28848 | 13002.28848 | 0.63415 | 0.63415 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 11870.23560 | 11870.23560 | 0.98607 | 0.98607 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.50667 | 6.29470E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 8562.64405 | 8562.64405 | 0.41765 | 0.41765 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 14813.12367 | 14813.12367 | 1.23055 | 1.23055 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.13333 | 6.30642E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 13139.50828 | 13139.50828 | 0.64086 | 0.64086 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 12610.43809 | 12610.43809 | 1.04756 | 1.04756 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 8664.21795 | 8664.21795 | 0.42262 | 0.42262 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 85320.56 | 6.20128 | 6.20128 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 50822.26 | 2.60121 | 2.60121 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 78325.28 | 5.61943 | 5.61943 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 50693.33 | 3.06186 | 3.06186 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 87286.60 | 6.39441 | 6.39441 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 51055.78 | 4.31070 | 4.31070 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.52385 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21268 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23400 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.82458 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56715 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79142E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24086.02843 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.65577 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28220 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30300 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80470 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75253 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.35011E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 27649.74713 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.75799 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27174 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30100 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.83015 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72464 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40208E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 48057.57774 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85751 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18424 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20400 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17493 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49132 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06791E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23410.75476 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99419 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10061 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19884 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.78704E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15325.99192 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.33562 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11829 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26712 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31544 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.22087E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23634.48776 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12461 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.89333E-002 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22492 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.28411E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15486.93557 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68025 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23226 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17346 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61935 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.64043E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18240.60648 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82197 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12169 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16439 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32450 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.13102E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12034.66368 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07647 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14677 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21529 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39138 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.59593E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18449.19624 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89358 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11193 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17872 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.40401E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12172.80503 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75556 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20911 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22500 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17000 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55761 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.82205E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18523.59361 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.98607 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10143 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19721 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.75611E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12199.63089 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23055 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12839 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24611 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34238 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96749E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18719.49961 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.04756 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.54743E-002 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20951 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.99060E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12344.64476 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.49806 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.55645 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.99611 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.60121 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.20128 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 6.20128 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.41946 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.33776 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.62754 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.67551 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 3.06186 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.61943 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.61943 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.54487 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.53496 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.69597 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.06992 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 4.31070 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.39441 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 6.39441 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.67414 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 6.20128 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.61943 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 6.39441 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.20128 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.20128 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 102653.28291 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.06689 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34214.33919 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 47257.77910 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 6.20128 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.61943 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.61943 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 93021.59477 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.87296 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31004.09754 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 48692.44802 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.61943 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.39441 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.39441 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 105850.22819 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.13126 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35279.88106 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 47498.08735 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 6.39441 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 100886.88 | 344240.31 | 11.07 | 2.80 | 3.17 | 3.34 | 3.50 | 9.54 | 10.82 | 11.40 | 11.93 | 6.2729 | 4.9600 | 3.3245 | 1.3998 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 91420.92 | 311941.14 | 11.07 | 2.80 | 3.17 | 3.34 | 3.50 | 9.54 | 10.82 | 11.40 | 11.93 | 5.6843 | 4.4946 | 3.0126 | 1.2685 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 104028.81 | 354961.03 | 11.07 | 2.80 | 3.17 | 3.34 | 3.50 | 9.54 | 10.82 | 11.40 | 11.93 | 6.4683 | 5.1144 | 3.4280 | 1.4434 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.232 | 0.219 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.232 | 0.219 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.9243245918E-002 | 7.7214167181E-002 | Pass | Pass | 0.1751918642 | 0.3764286722 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1295956913 | 9.4813938226E-002 | Pass | Pass | 0.4020731543 | 0.4773472218 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.8405807704E-002 | 2.6615438416E-002 | Pass | Pass | 0.1840580099 | 0.3751255486 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.5752232993E-002 | 2.4060243264E-002 | Pass | Pass | 0.2188875223 | 0.4213636328 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.5817375298E-002 | 3.5228609523E-002 | Pass | Pass | 0.1670687455 | 0.3656441128 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.6854039952E-002 | 3.1490737187E-002 | Pass | Pass | 0.3948162834 | 0.4899261635 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2688116061 | 0.3138667914 | Pass | Pass | 6.1398801296 | 21.9433770092 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2156274466 | 0.2876947276 | Pass | Pass | 6.7050148211 | 24.8080490310 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2304548786 | 0.2272456645 | Pass | Pass | 4.0187996029 | 35.9882344284 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2582434535 | 0.3006794009 | Pass | Pass | 5.8366717740 | 23.0099156562 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1062779243 | 0.1550251376 | Pass | Pass | 4.6763209755 | 46.5875600748 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.6481648631E-002 | 8.7969882188E-002 | Pass | Pass | 0.5152933738 | 2.2174057338 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1207615598 | 0.1034261233 | Pass | Pass | 0.1741355177 | 0.3734084149 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.7558057987E-002 | 0.1006272349 | Pass | Pass | 0.8042947681 | 3.6256739336 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 9.8283251956E-002 | 0.1517989029 | Pass | Pass | 0.6427797744 | 3.4974398968 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1047675658 | 0.1412598871 | Pass | Pass | 0.5497740349 | 3.4129525608 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1385113969 | 0.1394420308 | Pass | Pass | 0.5094027557 | 3.3383475953 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1233638302 | 0.1428039666 | Pass | Pass | 0.4638708209 | 2.1380598307 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3625.27 | 189.82 | 0.00 | 2293.18 | 614.46 | 6722.74 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.419_SHGC_NORTH_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.419_SHGC_EAST_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.419_SHGC_WEST_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.419_SHGC_EAST_0.4 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.419_SHGC_EAST_0.4 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.419_SHGC_WEST_0.4 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.419_SHGC_WEST_0.4 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.419_SHGC_NORTH_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.419_SHGC_EAST_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.419_SHGC_WEST_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.381 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 195.79 | 2.381 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.381 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.44 | 0.0000 | Y | 10.89 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.01 | 0.0000 | Y | 6.79 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.73 | 0.0000 | Y | 10.61 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.11 | 0.0000 | Y | 6.81 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.35 | 0.0000 | Y | 10.85 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.94 | 0.0000 | Y | 6.77 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.68 | 0.0000 | Y | 10.59 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.05 | 0.0000 | Y | 6.79 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.44 | 0.0000 | Y | 10.89 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.01 | 0.0000 | Y | 6.79 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.73 | 0.0000 | Y | 10.61 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.11 | 0.0000 | Y | 6.81 |
Interior Lighting Total | 10.1959 | 4982.19 | 50797.72 | 364.69 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.28 | AstronomicalClock | - | 42.11 | 42.11 | 4.45 | |
EXTERIOR_LIGHTS_B | 8033.20 | AstronomicalClock | - | 83.57 | 71.13 | 107.26 | |
Exterior Lighting Total | 8596.48 | 111.71 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 102653.28 | 82189.89 | 20463.39 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 93021.59 | 74478.23 | 18543.37 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 105850.23 | 84749.54 | 21100.69 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 100886.9 | 2.80 | 9.54 | N/A | N/A | 11.07 | |
PACU_VAV_MID COOLING COIL | 91420.9 | 2.80 | 9.54 | N/A | N/A | 11.07 | |
PACU_VAV_TOP COOLING COIL | 104028.8 | 2.80 | 9.54 | N/A | N/A | 11.07 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 24086.03 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 27649.75 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 48057.58 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 23410.75 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15325.99 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 23634.49 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15486.94 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18240.61 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12034.66 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18449.20 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12172.81 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18523.59 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12199.63 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18719.50 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12344.64 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 47257.78 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 48692.45 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 47498.09 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 6.20 | 14253.41 | 2298.46 | 1.00 | 1.12 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.62 | 12916.05 | 2298.46 | 1.00 | 1.13 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.61 | 1389.42 | 6.39 | 14603.10 | 2283.73 | 1.00 | 1.13 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.97 | 0.17 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 100886.88 | 2.80 | 9.54 | 11.07 | 6.2729 | 3.17 | 10.82 | 4.9600 | 3.34 | 11.40 | 3.3245 | 3.50 | 11.93 | 1.3998 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 91420.92 | 2.80 | 9.54 | 11.07 | 5.6843 | 3.17 | 10.82 | 4.4946 | 3.34 | 11.40 | 3.0126 | 3.50 | 11.93 | 1.2685 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 104028.81 | 2.80 | 9.54 | 11.07 | 6.4683 | 3.17 | 10.82 | 5.1144 | 3.34 | 11.40 | 3.4280 | 3.50 | 11.93 | 1.4434 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 42751.92 | 42751.92 | 43.47 | 3.524 | 3.524 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00878 | 21.56 | 0.00629 | 0.425 | 0.00 |
CORE_MID | 32248.95 | 32248.95 | 32.79 | 2.656 | 2.656 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 21.56 | 0.00629 | 0.425 | 0.00 |
CORE_TOP | 33198.42 | 33198.42 | 33.75 | 2.758 | 2.758 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00886 | 32.76 | 0.00631 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10322.63 | 10322.63 | 49.79 | 0.858 | 0.858 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00865 | 33.08 | 0.00631 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11968.06 | 11968.06 | 91.18 | 0.994 | 0.994 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00858 | 25.96 | 0.00630 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 16078.09 | 16078.09 | 77.55 | 1.336 | 1.336 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00860 | 33.27 | 0.00631 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 13538.01 | 13538.01 | 103.14 | 1.125 | 1.125 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00857 | 30.36 | 0.00630 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8188.57 | 8188.57 | 39.49 | 0.680 | 0.680 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00874 | 33.40 | 0.00631 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9894.64 | 9894.64 | 75.38 | 0.822 | 0.822 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00863 | 26.87 | 0.00630 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12958.20 | 12958.20 | 62.50 | 1.076 | 1.076 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00865 | 33.40 | 0.00631 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 10756.65 | 10756.65 | 81.95 | 0.894 | 0.894 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00862 | 28.76 | 0.00630 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9095.28 | 9095.28 | 43.87 | 0.756 | 0.756 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00869 | 33.40 | 0.00631 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 11870.24 | 11870.24 | 90.43 | 0.986 | 0.986 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00859 | 25.51 | 0.00629 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 14813.12 | 14813.12 | 71.44 | 1.231 | 1.231 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00862 | 33.13 | 0.00631 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 12610.44 | 12610.44 | 96.08 | 1.048 | 1.048 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00858 | 30.36 | 0.00630 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 10696.82 | 10696.82 | 10.88 | 0.516 | 0.516 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 0.425 | 0.00 |
CORE_MID | 19494.80 | 19494.80 | 19.82 | 0.947 | 0.947 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 0.425 | 0.00 |
CORE_TOP | 33791.80 | 33791.80 | 34.36 | 1.645 | 1.645 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 16426.21 | 16426.21 | 79.22 | 0.801 | 0.801 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10752.99 | 10752.99 | 81.92 | 0.525 | 0.525 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 16582.93 | 16582.93 | 79.98 | 0.809 | 0.809 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10865.73 | 10865.73 | 82.78 | 0.530 | 0.530 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 12803.14 | 12803.14 | 61.75 | 0.624 | 0.624 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8446.48 | 8446.48 | 64.35 | 0.412 | 0.412 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12949.24 | 12949.24 | 62.45 | 0.632 | 0.632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8543.24 | 8543.24 | 65.09 | 0.417 | 0.417 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 13002.29 | 13002.29 | 62.71 | 0.634 | 0.634 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8562.64 | 8562.64 | 65.23 | 0.418 | 0.418 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 13139.51 | 13139.51 | 63.37 | 0.641 | 0.641 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 8664.22 | 8664.22 | 66.01 | 0.423 | 0.423 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -27.60 | 0.00034 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 6.20 | 6.20 | 2.60 | 2.60 | 6.2013 | 2.6012 | 6.2013 | 0.4195 | 0.3000 |
PACU_VAV_MID | 5.62 | 5.62 | 3.06 | 3.06 | 5.6194 | 3.0619 | 5.6194 | 0.5449 | 0.3000 |
PACU_VAV_TOP | 6.39 | 6.39 | 4.31 | 4.31 | 6.3944 | 4.3107 | 6.3944 | 0.6741 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 24086.028 | 24086.028 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24086.03 | 15084.25 | 0.516406 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 10696.82 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 27649.747 | 27649.747 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27649.75 | 27649.75 | 0.946583 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 19494.80 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 48057.578 | 48057.578 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 48057.58 | 48057.58 | 1.645241 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 33791.80 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 23410.755 | 23410.755 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23410.75 | 23410.75 | 0.801462 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00776869 | 43.9434 | 16426.21 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 15325.992 | 15325.992 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15325.99 | 15325.99 | 0.524682 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00776449 | 43.9201 | 10752.99 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 23634.488 | 23634.488 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23634.49 | 23634.49 | 0.809122 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00777081 | 43.9552 | 16582.93 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 15486.936 | 15486.936 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15486.94 | 15486.94 | 0.530192 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00776685 | 43.9333 | 10865.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 18240.606 | 18240.606 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18240.61 | 18240.61 | 0.624463 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00784049 | 44.3427 | 12803.14 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 12034.664 | 12034.664 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12034.66 | 12034.66 | 0.412004 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783915 | 44.3353 | 8446.48 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 18449.196 | 18449.196 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18449.20 | 18449.20 | 0.631604 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00784235 | 44.3531 | 12949.24 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 12172.805 | 12172.805 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12172.81 | 12172.81 | 0.416733 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00784101 | 44.3457 | 8543.24 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 18523.594 | 18523.594 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18523.59 | 18523.59 | 0.634151 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00775695 | 43.8773 | 13002.29 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 12199.631 | 12199.631 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12199.63 | 12199.63 | 0.417652 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00775426 | 43.8624 | 8562.64 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 18719.500 | 18719.500 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18719.50 | 18719.50 | 0.640858 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00775948 | 43.8914 | 13139.51 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 12344.645 | 12344.645 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12344.64 | 12344.64 | 0.422616 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00775710 | 43.8783 | 8664.22 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 102653.283 | 82189.891 | 6.201285 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 100340.03 | 100340.03 | 6.201285 | 25.81 | 15.45 | 0.00827651 | 10.66 | 9.81 | 0.00827651 | 33.40 | 0.00630683 | 16.37 | 19.2729 | 24.00 | 0.00874726 | 41.1682 | 74583.35 | 0.00 | 105849.31 | 77989.96 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 47257.779 | 47257.779 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 47257.78 | 47257.78 | 1.860385 | -11.20 | -11.20 | 0.00297419 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 64.2431 | 18.15 | 0.00772472 | 52.1681 | 20237.76 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 93021.595 | 74478.229 | 5.619435 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 90925.39 | 90925.39 | 5.619435 | 26.00 | 15.48 | 0.00823606 | 10.66 | 9.77 | 0.00823606 | 33.40 | 0.00630683 | 16.37 | 21.2685 | 24.00 | 0.00875884 | 41.2217 | 67478.35 | 0.00 | 95917.75 | 70672.36 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 48692.448 | 48692.448 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 48692.45 | 48692.45 | 1.685830 | -14.49 | -14.49 | 0.00244849 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 70.8950 | 17.60 | 0.00739212 | 51.6951 | 22093.56 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 105850.228 | 84749.542 | 6.394412 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 103464.93 | 103464.93 | 6.394412 | 25.77 | 15.43 | 0.00826772 | 10.67 | 9.81 | 0.00826772 | 33.40 | 0.00630683 | 16.37 | 18.6908 | 24.00 | 0.00872132 | 41.0474 | 76580.49 | 0.00 | 109145.79 | 80418.81 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 47498.087 | 47498.087 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 47498.09 | 47498.09 | 1.918324 | -10.60 | -10.60 | 0.00304532 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 62.3028 | 15.75 | 0.00764306 | 60.1222 | 20412.20 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 24086.028 | 24086.028 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24086.03 | 15084.25 | 1.0000 | 0.54384804 | 0.516406 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24086.03 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 10696.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 27649.747 | 27649.747 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27649.75 | 27649.75 | 1.0000 | 0.99688463 | 0.946583 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27649.75 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 19494.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 48057.578 | 48057.578 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 48057.58 | 48057.58 | 1.0000 | 1.73266903 | 1.645241 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48057.58 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 33791.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 23410.755 | 23410.755 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23410.75 | 23410.75 | 1.0000 | 0.84405190 | 0.801462 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23410.75 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00776869 | 21.00 | 0.00776869 | 43.9434 | 16426.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 15325.992 | 15325.992 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15325.99 | 15325.99 | 1.0000 | 0.55256367 | 0.524682 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15325.99 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00776449 | 21.00 | 0.00776449 | 43.9201 | 10752.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 23634.488 | 23634.488 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23634.49 | 23634.49 | 1.0000 | 0.85211837 | 0.809122 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23634.49 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00777081 | 21.00 | 0.00777081 | 43.9552 | 16582.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 15486.936 | 15486.936 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15486.94 | 15486.94 | 1.0000 | 0.55836634 | 0.530192 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15486.94 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00776685 | 21.00 | 0.00776685 | 43.9333 | 10865.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 18240.606 | 18240.606 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18240.61 | 18240.61 | 1.0000 | 0.65764725 | 0.624463 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18240.61 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00784049 | 21.00 | 0.00784049 | 44.3427 | 12803.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 12034.664 | 12034.664 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12034.66 | 12034.66 | 1.0000 | 0.43389805 | 0.412004 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12034.66 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783915 | 21.00 | 0.00783915 | 44.3353 | 8446.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 18449.196 | 18449.196 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18449.20 | 18449.20 | 1.0000 | 0.66516775 | 0.631604 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18449.20 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00784235 | 21.00 | 0.00784235 | 44.3531 | 12949.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12172.805 | 12172.805 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12172.81 | 12172.81 | 1.0000 | 0.43887860 | 0.416733 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12172.81 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00784101 | 21.00 | 0.00784101 | 44.3457 | 8543.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 18523.594 | 18523.594 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18523.59 | 18523.59 | 1.0000 | 0.66785008 | 0.634151 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18523.59 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00775695 | 21.00 | 0.00775695 | 43.8773 | 13002.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 12199.631 | 12199.631 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12199.63 | 12199.63 | 1.0000 | 0.43984578 | 0.417652 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12199.63 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00775426 | 21.00 | 0.00775426 | 43.8624 | 8562.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 18719.500 | 18719.500 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18719.50 | 18719.50 | 1.0000 | 0.67491328 | 0.640858 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18719.50 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00775948 | 21.00 | 0.00775948 | 43.8914 | 13139.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12344.645 | 12344.645 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12344.64 | 12344.64 | 1.0000 | 0.44507411 | 0.422616 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12344.64 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00775710 | 21.00 | 0.00775710 | 43.8783 | 8664.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 102653.283 | 82189.891 | 6.201285 | -999.0 | -999.000 | -999.0000 | 1.02229 | 1.00000 | 1020.2256 | 1004.8586 | 1.0531 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.201285 | 6.53082035 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 100340.03 | 100340.03 | 0.9775 | 6.53082035 | 6.201285 | 25.81 | 15.45 | 0.00827651 | 47033.4 | 10.66 | 9.81 | 0.00827651 | 31575.5 | -999.0 | -999.00 | -999.00 | -999.00 | 14253.415 | 86086.61 | 33.40 | 0.00630683 | 16.37 | 1.19517000 | 19.2729 | 24.00 | 0.00874726 | 24.00 | 0.00874726 | 41.1682 | 74583.35 | 0.00 | 105849.31 | 77989.96 | 6.27290232 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.51 | 13.70 | 0.00944336 | 38448.3 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 47257.779 | 47257.779 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.201285 | 6.53082035 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 47257.78 | 47257.78 | 1.0000 | 1.95924611 | 1.860385 | -11.20 | -11.20 | 0.00297419 | -3881.7 | 12.80 | 10.41 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47257.78 | -27.60 | 0.00034190 | -27.60 | 1.19517000 | 64.2431 | 18.25 | 0.00770355 | 18.15 | 0.00772472 | 52.1681 | 20237.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 93021.595 | 74478.229 | 5.619435 | -999.0 | -999.000 | -999.0000 | 1.01018 | 1.00000 | 1020.1504 | 1004.8586 | 1.0531 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.619435 | 5.91805062 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 90925.39 | 90925.39 | 0.9775 | 5.91805062 | 5.619435 | 26.00 | 15.48 | 0.00823606 | 47125.2 | 10.66 | 9.77 | 0.00823606 | 31473.3 | -999.0 | -999.00 | -999.00 | -999.00 | 12916.054 | 78009.33 | 33.40 | 0.00630683 | 16.37 | 1.19517000 | 21.2685 | 24.00 | 0.00875884 | 24.00 | 0.00875884 | 41.2217 | 67478.35 | 0.00 | 95917.75 | 70672.36 | 5.68433236 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.51 | 13.70 | 0.00944336 | 38448.3 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 48692.448 | 48692.448 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.619435 | 5.91805062 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 48692.45 | 48692.45 | 1.0000 | 1.77541519 | 1.685830 | -14.49 | -14.49 | 0.00244849 | -8505.9 | 12.80 | 10.41 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48692.45 | -27.60 | 0.00034190 | -27.60 | 1.19517000 | 70.8950 | 17.43 | 0.00757980 | 17.60 | 0.00739212 | 51.6951 | 22093.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 105850.228 | 84749.542 | 6.394412 | -999.0 | -999.000 | -999.0000 | 1.02628 | 1.00000 | 1020.2093 | 1004.8586 | 1.0531 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.394412 | 6.73421059 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 103464.93 | 103464.93 | 0.9775 | 6.73421059 | 6.394412 | 25.77 | 15.43 | 0.00826772 | 46962.9 | 10.67 | 9.81 | 0.00826772 | 31567.2 | -999.0 | -999.00 | -999.00 | -999.00 | 14603.097 | 88861.83 | 33.40 | 0.00630683 | 16.37 | 1.19517000 | 18.6908 | 24.00 | 0.00872132 | 24.00 | 0.00872132 | 41.0474 | 76580.49 | 0.00 | 109145.79 | 80418.81 | 6.46826018 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.51 | 13.70 | 0.00944336 | 38448.3 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 47498.087 | 47498.087 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.394412 | 6.73421059 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 47498.09 | 47498.09 | 1.0000 | 2.02026318 | 1.918324 | -10.60 | -10.60 | 0.00304532 | -3092.3 | 12.80 | 10.41 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47498.09 | -27.60 | 0.00034190 | -27.60 | 1.19517000 | 62.3028 | 17.50 | 0.00751333 | 15.75 | 0.00764306 | 60.1222 | 20412.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 6.20 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.62 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 6.39 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1297.33 | 3196.00 | 165.00 |
CORE_MID | 1595.83 | 4060.50 | 819.67 |
CORE_TOP | 2282.00 | 4346.00 | 1615.33 |
PERIMETER_TOP_ZN_3 | 3317.67 | 4561.17 | 2613.00 |
PERIMETER_TOP_ZN_2 | 3470.17 | 4257.50 | 2383.33 |
PERIMETER_TOP_ZN_1 | 3121.50 | 4015.00 | 1965.83 |
PERIMETER_TOP_ZN_4 | 3413.17 | 4518.00 | 2466.83 |
PERIMETER_BOT_ZN_3 | 2991.67 | 4682.83 | 2464.00 |
PERIMETER_BOT_ZN_2 | 3221.33 | 4142.00 | 2069.67 |
PERIMETER_BOT_ZN_1 | 2719.17 | 4075.83 | 1635.00 |
PERIMETER_BOT_ZN_4 | 3107.33 | 4312.67 | 2122.50 |
PERIMETER_MID_ZN_3 | 2943.83 | 4376.83 | 2177.67 |
PERIMETER_MID_ZN_2 | 2705.00 | 3597.50 | 1800.33 |
PERIMETER_MID_ZN_1 | 2811.50 | 3746.50 | 1534.33 |
PERIMETER_MID_ZN_4 | 3062.00 | 4307.67 | 2041.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4756.17 | 5011.67 | 2891.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 1.17 | 0.00 | 1.00 | 0.00 |
CORE_TOP | 4.67 | 0.00 | 3.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 177.50 | 6.67 | 79.50 | 4.67 |
PERIMETER_TOP_ZN_2 | 118.00 | 23.00 | 25.17 | 21.83 |
PERIMETER_TOP_ZN_1 | 94.50 | 23.50 | 18.17 | 21.17 |
PERIMETER_TOP_ZN_4 | 118.83 | 24.50 | 27.00 | 12.17 |
PERIMETER_BOT_ZN_3 | 82.33 | 0.00 | 53.17 | 0.00 |
PERIMETER_BOT_ZN_2 | 34.17 | 16.83 | 7.17 | 16.33 |
PERIMETER_BOT_ZN_1 | 298.33 | 18.50 | 282.00 | 16.83 |
PERIMETER_BOT_ZN_4 | 35.17 | 16.50 | 8.33 | 7.67 |
PERIMETER_MID_ZN_3 | 75.33 | 2.83 | 34.17 | 2.00 |
PERIMETER_MID_ZN_2 | 50.33 | 21.50 | 9.00 | 21.17 |
PERIMETER_MID_ZN_1 | 37.67 | 23.83 | 6.17 | 22.17 |
PERIMETER_MID_ZN_4 | 53.33 | 24.00 | 11.17 | 12.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 491.00 | 100.17 | 349.83 | 79.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.52 | 52.94 | 2698.04 | 0.980 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.52 | 52.94 | 2698.04 | 0.686 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.52 | 52.94 | 2698.04 | 0.669 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.54 | 11.16 | 568.77 | 0.738 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 1.414 | 0.120 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.54 | 11.16 | 568.77 | 1.341 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 1.407 | 0.120 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.54 | 11.16 | 568.77 | 0.648 | 0.060 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 1.186 | 0.064 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.54 | 11.16 | 568.77 | 1.056 | 0.883 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 1.112 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.54 | 11.16 | 568.77 | 0.726 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 1.306 | 0.106 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.54 | 11.16 | 568.77 | 1.316 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 1.346 | 0.100 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.52 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.52 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.52 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.52 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.52 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.52 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.51 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.66 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 15573910.70 | 0.00 | 15573910.70 | 0.00 | 15573910.70 | 13393058.27 | 5744.37 | 46.64 | 2969.00 | 170.31 |
CORE_MID | 10965555.41 | 0.00 | 10965555.41 | 0.00 | 10965555.41 | 13393058.27 | 6505.21 | 35.62 | 2219.17 | 226.59 |
CORE_TOP | 10701378.27 | 0.00 | 10701378.27 | 0.00 | 10701378.27 | 13393058.27 | 6537.54 | 26.08 | 2196.38 | 101.27 |
PERIMETER_TOP_ZN_3 | 2487544.32 | 0.00 | 2487544.32 | 759318.16 | 3246862.48 | 2823374.22 | 5765.67 | 60.60 | 2933.73 | 101.27 |
PERIMETER_TOP_ZN_2 | 3013712.03 | 0.00 | 3013712.03 | 506209.06 | 3519921.10 | 1787429.43 | 4126.89 | 2.56 | 4630.55 | 101.27 |
PERIMETER_TOP_ZN_1 | 4504790.21 | 0.00 | 4504790.21 | 759318.16 | 5264108.37 | 2823374.22 | 4143.86 | 2.07 | 4614.07 | 101.27 |
PERIMETER_TOP_ZN_4 | 3016388.66 | 0.00 | 3016388.66 | 506209.06 | 3522597.73 | 1787312.18 | 4139.00 | 8.20 | 4612.80 | 101.27 |
PERIMETER_BOT_ZN_3 | 2191095.14 | 0.00 | 2191095.14 | 403724.27 | 2594819.41 | 2823374.22 | 6127.41 | 52.32 | 2580.27 | 170.31 |
PERIMETER_BOT_ZN_2 | 2527644.82 | 0.00 | 2527644.82 | 269147.90 | 2796792.71 | 1787429.43 | 4120.62 | 5.44 | 4633.94 | 170.31 |
PERIMETER_BOT_ZN_1 | 3560661.28 | 0.00 | 3560661.28 | 3161469.32 | 6722130.60 | 2823374.22 | 4277.14 | 45.44 | 4437.43 | 170.31 |
PERIMETER_BOT_ZN_4 | 2380383.81 | 0.00 | 2380383.81 | 269147.90 | 2649531.70 | 1787312.18 | 4161.95 | 14.46 | 4583.60 | 170.31 |
PERIMETER_MID_ZN_3 | 2449691.85 | 0.00 | 2449691.85 | 632073.14 | 3081764.99 | 2823374.22 | 5948.97 | 61.17 | 2749.86 | 226.50 |
PERIMETER_MID_ZN_2 | 3035697.76 | 0.00 | 3035697.76 | 421379.56 | 3457077.33 | 1787429.43 | 4059.07 | 6.64 | 4694.29 | 1135.50 |
PERIMETER_MID_ZN_1 | 4422457.74 | 0.00 | 4422457.74 | 632073.14 | 5054530.88 | 2823374.22 | 4107.34 | 5.81 | 4646.84 | 226.50 |
PERIMETER_MID_ZN_4 | 2885576.82 | 0.00 | 2885576.82 | 421379.56 | 3306956.39 | 1787312.18 | 4073.27 | 9.03 | 4677.70 | 226.50 |
Total Facility | 73716488.82 | 0.00 | 73716488.82 | 8741449.25 | 82457938.07 | 67843644.98 | 6709.92 | 283.88 | 4775.55 | 1228.52 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7209 | 0.0000 | 0.7209 | 0.0000 | 0.7209 | 0.4247 | 2966.33 | 46.64 | 2930.03 |
CORE_MID | 0.5054 | 0.0000 | 0.5054 | 0.0000 | 0.5054 | 0.4247 | 3729.19 | 35.62 | 2178.18 |
CORE_TOP | 0.4935 | 0.0000 | 0.4935 | 0.0000 | 0.4935 | 0.4247 | 3766.35 | 26.08 | 2150.57 |
PERIMETER_TOP_ZN_3 | 0.1149 | 0.0000 | 0.1149 | 0.0178 | 0.1327 | 0.0895 | 2994.48 | 60.60 | 2887.92 |
PERIMETER_TOP_ZN_2 | 0.1393 | 0.0000 | 0.1393 | 0.0119 | 0.1511 | 0.0567 | 1355.70 | 2.56 | 4584.74 |
PERIMETER_TOP_ZN_1 | 0.2084 | 0.0000 | 0.2084 | 0.0178 | 0.2262 | 0.0895 | 1372.67 | 2.07 | 4568.26 |
PERIMETER_TOP_ZN_4 | 0.1388 | 0.0000 | 0.1388 | 0.0119 | 0.1506 | 0.0567 | 1367.80 | 8.20 | 4567.00 |
PERIMETER_BOT_ZN_3 | 0.1009 | 0.0000 | 0.1009 | 0.0095 | 0.1104 | 0.0895 | 3349.37 | 52.32 | 2541.31 |
PERIMETER_BOT_ZN_2 | 0.1167 | 0.0000 | 0.1167 | 0.0063 | 0.1230 | 0.0567 | 1342.85 | 5.41 | 4594.74 |
PERIMETER_BOT_ZN_1 | 0.1646 | 0.0000 | 0.1646 | 0.1384 | 0.3029 | 0.0895 | 1499.10 | 45.44 | 4398.46 |
PERIMETER_BOT_ZN_4 | 0.1095 | 0.0000 | 0.1095 | 0.0063 | 0.1159 | 0.0567 | 1384.29 | 14.42 | 4544.30 |
PERIMETER_MID_ZN_3 | 0.1130 | 0.0000 | 0.1130 | 0.0148 | 0.1278 | 0.0895 | 3172.96 | 61.17 | 2708.87 |
PERIMETER_MID_ZN_2 | 0.1286 | 0.0000 | 0.1286 | 0.0105 | 0.1391 | 0.0567 | 1282.54 | 6.62 | 3744.84 |
PERIMETER_MID_ZN_1 | 0.2045 | 0.0000 | 0.2045 | 0.0148 | 0.2193 | 0.0895 | 1331.40 | 5.79 | 4605.81 |
PERIMETER_MID_ZN_4 | 0.1326 | 0.0000 | 0.1326 | 0.0099 | 0.1425 | 0.0567 | 1297.59 | 9.03 | 4636.38 |
Total Facility | 3.3916 | 0.0000 | 3.3916 | 0.2698 | 3.6613 | 2.1513 | 3915.32 | 283.77 | 4711.85 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 29095873.50 | 0.00 | 29095873.50 | 22614548.33 | 4140.78 | 4.07 | 4615.15 | 170.31 |
PACU_VAV_MID | 26351184.38 | 0.00 | 26351184.38 | 22614548.33 | 4123.05 | 2.38 | 4634.57 | 226.01 |
PACU_VAV_TOP | 26312155.35 | 0.00 | 26312155.35 | 22614548.33 | 4149.71 | 1.35 | 4608.94 | 100.89 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.3449 | 0.0000 | 1.3449 | 0.7171 | 1362.74 | 4.07 | 4576.18 |
PACU_VAV_MID | 1.2151 | 0.0000 | 1.2151 | 0.7171 | 1347.03 | 2.38 | 4593.58 |
PACU_VAV_TOP | 1.2143 | 0.0000 | 1.2143 | 0.7171 | 1378.51 | 1.35 | 4563.13 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 3056.39 | 0.00 | 0.00 | 0.00 | 1898.26 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 2834.61 | 0.00 | 0.00 | 0.00 | 2210.97 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2661.23 | 0.00 | 0.00 | 0.00 | 2210.01 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.1894 | 0.0000 | 0.0000 | 0.0000 | 0.8821 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.0170 | 0.0000 | 0.0000 | 0.0000 | 0.8873 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.0557 | 0.0000 | 0.0000 | 0.0000 | 0.8842 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 829 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1712.38 | 13157.78 | 26-MAR-17:10 | 276810.72 | 09-JAN-07:10 |
Electricity:Building | 1070.12 | 12913.45 | 26-MAR-17:10 | 84122.50 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 322.66 | 4214.70 | 01-JAN-00:10 | 25737.69 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1070.12 | 12913.45 | 26-MAR-17:10 | 84122.50 | 02-JAN-08:10 |
InteriorLights:Electricity | 364.69 | 1672.11 | 01-JAN-10:50 | 38257.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 364.69 | 1672.11 | 01-JAN-10:50 | 38257.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 364.69 | 1672.11 | 01-JAN-10:50 | 38257.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 364.69 | 1672.11 | 01-JAN-10:50 | 38257.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 201.92 | 2251.11 | 01-JAN-00:10 | 14360.82 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 201.92 | 2251.11 | 01-JAN-00:10 | 14360.82 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 35.22 | 428.29 | 26-MAR-17:10 | 3027.38 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.89 | 42.19 | 01-JAN-10:50 | 1592.13 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.89 | 42.19 | 01-JAN-10:50 | 1592.13 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.19 | 271.13 | 26-MAR-17:10 | 1916.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.79 | 26.71 | 01-JAN-08:50 | 1007.95 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.79 | 26.71 | 01-JAN-08:50 | 1007.95 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 34.94 | 428.29 | 12-MAR-17:10 | 3027.37 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.61 | 42.19 | 01-JAN-08:50 | 1592.13 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.61 | 42.19 | 01-JAN-08:50 | 1592.13 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 22.21 | 271.13 | 12-MAR-17:10 | 1916.45 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.81 | 26.71 | 01-JAN-10:30 | 1007.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.81 | 26.71 | 01-JAN-10:30 | 1007.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 35.19 | 428.29 | 19-MAR-17:10 | 3027.38 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.85 | 42.19 | 01-JAN-10:30 | 1592.13 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.85 | 42.19 | 01-JAN-10:30 | 1592.13 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.17 | 271.13 | 26-MAR-17:10 | 1916.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.77 | 26.71 | 01-JAN-08:50 | 1007.95 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.77 | 26.71 | 01-JAN-08:50 | 1007.95 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 34.92 | 428.29 | 12-MAR-17:10 | 3027.37 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.59 | 42.19 | 01-JAN-08:50 | 1592.13 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.59 | 42.19 | 01-JAN-08:50 | 1592.13 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 22.20 | 271.13 | 12-MAR-17:10 | 1916.45 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.79 | 26.71 | 01-JAN-10:30 | 1007.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.79 | 26.71 | 01-JAN-10:30 | 1007.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 35.22 | 428.29 | 26-MAR-17:10 | 3027.38 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 10.89 | 42.19 | 01-JAN-10:50 | 1592.13 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 10.89 | 42.19 | 01-JAN-10:50 | 1592.13 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.19 | 271.13 | 26-MAR-17:10 | 1916.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.79 | 26.71 | 01-JAN-08:50 | 1007.95 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.79 | 26.71 | 01-JAN-08:50 | 1007.95 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 34.94 | 428.29 | 12-MAR-17:10 | 3027.37 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 10.61 | 42.19 | 01-JAN-08:50 | 1592.13 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 10.61 | 42.19 | 01-JAN-08:50 | 1592.13 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 22.21 | 271.13 | 12-MAR-17:10 | 1916.45 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.81 | 26.71 | 01-JAN-10:30 | 1007.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.81 | 26.71 | 01-JAN-10:30 | 1007.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 530.40 | 243.72 | 01-JAN-00:10 | 234355.82 | 09-JAN-07:10 |
ExteriorEquipment:Electricity | 17.12 | 243.72 | 01-JAN-00:10 | 1242.18 | 06-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 17.12 | 243.72 | 01-JAN-00:10 | 1242.18 | 06-JAN-08:20 |
ElectricityPurchased:Facility | 1712.38 | 13157.78 | 24-JUN-18:20 | 276810.72 | 09-JAN-07:10 |
ElectricityPurchased:Plant | 1712.38 | 13157.78 | 24-JUN-18:20 | 276810.72 | 09-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1712.38 | 13157.78 | 24-JUN-18:20 | 276810.72 | 09-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1712.38 | 13157.78 | 24-JUN-18:20 | 276810.72 | 09-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1712.38 | 13157.78 | 24-JUN-18:20 | 276810.72 | 09-JAN-07:10 |
ElectricityNet:Plant | 1712.38 | 13157.78 | 24-JUN-18:20 | 276810.72 | 09-JAN-07:10 |
Cogeneration:ElectricityNet | 1712.38 | 13157.78 | 24-JUN-18:20 | 276810.72 | 09-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1712.38 | 13157.78 | 24-JUN-18:20 | 276810.72 | 09-JAN-07:10 |
Heating:Electricity | 292.02 | 0.00 | 01-JAN-00:10 | 225214.60 | 09-JAN-07:10 |
General:Heating:Electricity | 292.02 | 0.00 | 01-JAN-00:10 | 225214.60 | 09-JAN-07:10 |
Fans:Electricity | 104.99 | 0.00 | 01-JAN-00:10 | 37222.62 | 17-JUL-15:20 |
General:Fans:Electricity | 104.99 | 0.00 | 01-JAN-00:10 | 37222.62 | 17-JUL-15:20 |
ExteriorLights:Electricity | 111.71 | 0.00 | 01-JAN-08:20 | 8596.48 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 111.71 | 0.00 | 01-JAN-08:20 | 8596.48 | 01-JAN-06:10 |
Cooling:Electricity | 116.28 | 0.00 | 01-JAN-00:10 | 83931.56 | 17-JUL-16:00 |
General:Cooling:Electricity | 116.28 | 0.00 | 01-JAN-00:10 | 83931.56 | 17-JUL-16:00 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 04-JAN-06:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 04-JAN-06:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 04-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 10.25 | 0.00 | 01-JAN-00:10 | 1075.04 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 373.57 | 2003.43 | 05-JAN-05:10 | 156778.00 | 10-JAN-21:40 |
NaturalGas:HVAC | 231.90 | 0.00 | 01-JAN-00:10 | 151900.12 | 10-JAN-22:00 |
Heating:NaturalGas | 231.90 | 0.00 | 01-JAN-00:10 | 151900.12 | 10-JAN-22:00 |
General:Heating:NaturalGas | 231.90 | 0.00 | 01-JAN-00:10 | 151900.12 | 10-JAN-22:00 |
NaturalGas:Plant | 141.67 | 2003.43 | 02-JAN-07:10 | 12281.55 | 10-FEB-12:30 |
WaterSystems:NaturalGas | 141.67 | 2003.43 | 02-JAN-07:10 | 12281.55 | 10-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 141.67 | 2003.43 | 02-JAN-07:10 | 12281.55 | 10-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2155.53 | 0.00 | 01-JAN-00:10 | 540799.17 | 09-JAN-07:10 |
EnergyTransfer:Building | 1171.12 | 0.00 | 01-JAN-00:10 | 226610.48 | 09-JAN-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 215.68 | 0.00 | 01-JAN-00:10 | 28024.64 | 05-SEP-08:00 |
Heating:EnergyTransfer | 253.22 | 0.00 | 01-JAN-00:10 | 226156.09 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.10 | 0.00 | 01-JAN-00:10 | 9008.30 | 02-JAN-07:10 |
General:Heating:EnergyTransfer | 253.22 | 0.00 | 01-JAN-00:10 | 226156.09 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.10 | 0.00 | 01-JAN-00:10 | 9008.30 | 02-JAN-07:10 |
Cooling:EnergyTransfer | 917.90 | 0.00 | 01-JAN-00:10 | 191466.81 | 17-JUL-15:50 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 215.58 | 0.00 | 01-JAN-00:10 | 28024.64 | 05-SEP-08:00 |
General:Cooling:EnergyTransfer | 917.90 | 0.00 | 01-JAN-00:10 | 191466.81 | 17-JUL-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 215.58 | 0.00 | 01-JAN-00:10 | 28024.64 | 05-SEP-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 61.80 | 0.00 | 01-JAN-00:10 | 19446.63 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 35.65 | 0.00 | 01-JAN-00:10 | 19446.63 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 35.65 | 0.00 | 01-JAN-00:10 | 19446.63 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 26.14 | 0.00 | 01-JAN-00:10 | 13292.07 | 17-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 26.14 | 0.00 | 01-JAN-00:10 | 13292.07 | 17-JUL-14:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 29.04 | 0.00 | 01-JAN-00:10 | 11687.46 | 09-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.98 | 0.00 | 01-JAN-00:10 | 11687.46 | 09-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.98 | 0.00 | 01-JAN-00:10 | 11687.46 | 09-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.06 | 0.00 | 01-JAN-00:10 | 6367.06 | 17-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.06 | 0.00 | 01-JAN-00:10 | 6367.06 | 17-JUL-15:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 27.95 | 0.00 | 01-JAN-00:10 | 6517.82 | 17-JUL-16:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.09 | 0.00 | 01-JAN-00:10 | 6120.54 | 09-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.09 | 0.00 | 01-JAN-00:10 | 6120.54 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.86 | 0.00 | 01-JAN-00:10 | 6517.82 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.86 | 0.00 | 01-JAN-00:10 | 6517.82 | 17-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 140.45 | 0.00 | 01-JAN-00:10 | 22755.93 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 2.24 | 0.00 | 01-JAN-00:10 | 22755.93 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 2.24 | 0.00 | 01-JAN-00:10 | 22755.93 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 138.21 | 0.00 | 01-JAN-00:10 | 20623.18 | 05-SEP-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 138.21 | 0.00 | 01-JAN-00:10 | 20623.18 | 05-SEP-07:40 |
EnergyTransfer:Zone:CORE_TOP | 135.69 | 0.00 | 01-JAN-00:10 | 31967.76 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 11.65 | 0.00 | 01-JAN-00:10 | 31967.76 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 11.65 | 0.00 | 01-JAN-00:10 | 31967.76 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 124.03 | 0.00 | 01-JAN-00:10 | 22612.24 | 17-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 124.03 | 0.00 | 01-JAN-00:10 | 22612.24 | 17-JUL-15:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 49.57 | 0.00 | 01-JAN-00:10 | 11395.42 | 09-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 26.16 | 0.00 | 01-JAN-00:10 | 11395.42 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 26.16 | 0.00 | 01-JAN-00:10 | 11395.42 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.41 | 0.00 | 01-JAN-00:10 | 7734.91 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.41 | 0.00 | 01-JAN-00:10 | 7734.91 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 44.65 | 0.00 | 01-JAN-00:10 | 11047.40 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 15.11 | 0.00 | 01-JAN-00:10 | 11047.40 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 15.11 | 0.00 | 01-JAN-00:10 | 11047.40 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 29.54 | 0.00 | 01-JAN-00:10 | 10690.23 | 07-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 29.54 | 0.00 | 01-JAN-00:10 | 10690.23 | 07-AUG-09:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 69.09 | 0.00 | 01-JAN-00:10 | 15800.51 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 18.59 | 0.00 | 01-JAN-00:10 | 15800.51 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 18.59 | 0.00 | 01-JAN-00:10 | 15800.51 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 50.50 | 0.00 | 01-JAN-00:10 | 15080.08 | 01-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 50.50 | 0.00 | 01-JAN-00:10 | 15080.08 | 01-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 45.24 | 0.00 | 01-JAN-00:10 | 12055.27 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 16.32 | 0.00 | 01-JAN-00:10 | 12055.27 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 16.32 | 0.00 | 01-JAN-00:10 | 12055.27 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 28.92 | 0.00 | 01-JAN-00:10 | 11275.84 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 28.92 | 0.00 | 01-JAN-00:10 | 11275.84 | 17-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 35.79 | 0.00 | 01-JAN-00:10 | 8632.66 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 15.35 | 0.00 | 01-JAN-00:10 | 8632.66 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 15.35 | 0.00 | 01-JAN-00:10 | 8632.66 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.43 | 0.00 | 01-JAN-00:10 | 6062.71 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.43 | 0.00 | 01-JAN-00:10 | 6062.71 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 34.91 | 0.00 | 01-JAN-00:10 | 9039.82 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 8.26 | 0.00 | 01-JAN-00:10 | 9039.82 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 8.26 | 0.00 | 01-JAN-00:10 | 9039.82 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 26.65 | 0.00 | 01-JAN-00:10 | 8777.52 | 07-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 26.65 | 0.00 | 01-JAN-00:10 | 8777.52 | 07-AUG-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 66.53 | 0.00 | 01-JAN-00:10 | 18430.33 | 09-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 28.74 | 0.00 | 01-JAN-00:10 | 18430.33 | 09-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 28.74 | 0.00 | 01-JAN-00:10 | 18430.33 | 09-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 37.79 | 0.00 | 01-JAN-00:10 | 14180.60 | 07-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 37.79 | 0.00 | 01-JAN-00:10 | 14180.60 | 07-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 33.83 | 0.00 | 01-JAN-00:10 | 9444.76 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 8.88 | 0.00 | 01-JAN-00:10 | 9444.76 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 8.88 | 0.00 | 01-JAN-00:10 | 9444.76 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 24.95 | 0.00 | 01-JAN-00:10 | 8951.89 | 04-AUG-18:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 24.95 | 0.00 | 01-JAN-00:10 | 8951.89 | 04-AUG-18:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 39.56 | 0.00 | 01-JAN-00:10 | 9635.70 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 14.32 | 0.00 | 01-JAN-00:10 | 9635.70 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 14.32 | 0.00 | 01-JAN-00:10 | 9635.70 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.23 | 0.00 | 01-JAN-00:10 | 7028.40 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.23 | 0.00 | 01-JAN-00:10 | 7028.40 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 39.58 | 0.00 | 01-JAN-00:10 | 10664.10 | 07-AUG-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 8.46 | 0.00 | 01-JAN-00:10 | 10044.87 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 8.46 | 0.00 | 01-JAN-00:10 | 10044.87 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 31.12 | 0.00 | 01-JAN-00:10 | 10664.10 | 07-AUG-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 31.12 | 0.00 | 01-JAN-00:10 | 10664.10 | 07-AUG-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 62.60 | 0.00 | 01-JAN-00:10 | 14611.37 | 01-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 9.38 | 0.00 | 01-JAN-00:10 | 13634.20 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 9.38 | 0.00 | 01-JAN-00:10 | 13634.20 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 53.22 | 0.00 | 01-JAN-00:10 | 14611.37 | 01-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 53.22 | 0.00 | 01-JAN-00:10 | 14611.37 | 01-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 39.16 | 0.00 | 01-JAN-00:10 | 10677.12 | 17-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 8.92 | 0.00 | 01-JAN-00:10 | 9967.54 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 8.92 | 0.00 | 01-JAN-00:10 | 9967.54 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 30.23 | 0.00 | 01-JAN-00:10 | 10677.12 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 30.23 | 0.00 | 01-JAN-00:10 | 10677.12 | 17-JUL-17:00 |
PlantLoopHeatingDemand:Facility | 55.07 | 0.00 | 01-JAN-00:10 | 6986.30 | 21-FEB-12:20 |
PlantLoopHeatingDemand:Plant | 55.07 | 0.00 | 01-JAN-00:10 | 6986.30 | 21-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 55.07 | 0.00 | 01-JAN-00:10 | 6986.30 | 21-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 55.07 | 0.00 | 01-JAN-00:10 | 6986.30 | 21-FEB-12:20 |
EnergyTransfer:HVAC | 929.33 | 0.00 | 01-JAN-00:10 | 320828.08 | 09-JAN-07:10 |
HeatingCoils:EnergyTransfer | 477.54 | 0.00 | 01-JAN-00:10 | 320828.08 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 451.80 | 0.00 | 01-JAN-00:10 | 304719.76 | 07-SEP-15:00 |
EnergyTransfer:Plant | 55.07 | 0.00 | 01-JAN-00:10 | 6986.30 | 21-FEB-12:20 |
WaterSystems:EnergyTransfer | 55.07 | 0.00 | 01-JAN-00:10 | 6986.30 | 21-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 55.07 | 0.00 | 01-JAN-00:10 | 6986.30 | 21-FEB-12:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.099 | -215.578 | 0.000 | 0.000 | 33.148 | 86.497 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -140.334 |
CORE_MID | 0.000 | 0.000 | 2.242 | -138.211 | 0.000 | 0.000 | 34.549 | 86.497 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -100.502 |
CORE_TOP | 0.000 | 0.000 | 11.654 | -124.031 | 0.000 | 0.000 | 35.418 | 86.497 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -124.963 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 26.157 | -23.413 | 0.000 | 0.000 | 7.700 | 10.891 | 24.333 | 17.018 | 0.000 | 0.111 | 0.001 | 0.000 | -46.124 | 0.000 | -11.152 | -5.521 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 15.109 | -29.542 | 0.000 | 0.000 | 4.819 | 6.785 | 15.404 | 38.984 | 0.000 | 0.073 | 0.000 | 0.000 | -28.847 | 0.000 | -7.541 | -15.244 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 18.590 | -50.495 | 0.000 | 0.000 | 7.499 | 10.608 | 24.332 | 84.216 | 0.000 | 0.105 | 0.000 | 0.000 | -43.229 | 0.000 | -11.689 | -39.938 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 16.325 | -28.919 | 0.000 | 0.000 | 4.902 | 6.811 | 15.403 | 37.366 | 0.000 | 0.074 | 0.000 | 0.000 | -30.398 | 0.000 | -7.557 | -14.007 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 15.354 | -20.435 | 0.000 | 0.000 | 7.687 | 10.854 | 24.333 | 17.433 | 0.000 | 0.065 | 0.003 | 0.000 | -47.305 | 0.000 | -6.203 | -1.784 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 8.258 | -26.653 | 0.000 | 0.000 | 4.777 | 6.769 | 15.404 | 39.126 | 0.000 | 0.039 | 0.002 | 0.000 | -30.109 | 0.000 | -4.268 | -13.343 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 28.742 | -37.787 | 0.000 | 0.000 | 7.619 | 10.588 | 24.332 | 85.054 | 0.000 | 1.246 | 0.002 | 0.000 | -45.386 | 0.000 | -46.575 | -27.834 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 8.877 | -24.953 | 0.000 | 0.000 | 4.843 | 6.794 | 15.403 | 37.627 | 0.000 | 0.039 | 0.001 | 0.000 | -31.679 | 0.000 | -4.272 | -12.680 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 14.323 | -25.234 | 0.000 | 0.000 | 7.607 | 10.891 | 24.333 | 16.697 | 0.000 | 0.094 | 9.326 | 0.000 | -48.271 | 0.000 | -9.765 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 8.459 | -31.122 | 0.000 | 0.000 | 3.540 | 6.785 | 15.404 | 38.727 | 0.000 | 0.062 | 0.000 | 0.000 | -30.104 | 0.000 | -6.586 | -5.165 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 9.383 | -53.221 | 0.000 | 0.000 | 7.393 | 10.608 | 24.332 | 83.810 | 0.000 | 0.088 | 0.001 | 0.000 | -45.297 | 0.000 | -10.249 | -26.849 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 8.924 | -30.231 | 0.000 | 0.000 | 4.846 | 6.811 | 15.403 | 37.166 | 0.000 | 0.062 | 0.000 | 0.000 | -31.783 | 0.000 | -6.607 | -4.591 |
TOPFLOOR_PLENUM | 35.653 | -26.144 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.114 | 7.535 | 0.000 | 0.000 | 0.000 | -17.158 | -0.005 |
MIDFLOOR_PLENUM | 14.979 | -14.061 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.136 | 15.917 | 0.000 | 0.000 | 0.000 | -16.971 | -0.000 |
FIRSTFLOOR_PLENUM | 10.092 | -17.862 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.104 | 21.453 | 0.000 | 0.000 | 0.000 | -13.787 | -0.000 |
Total Facility | 60.724 | -58.067 | 192.496 | -859.825 | 0.000 | 0.000 | 176.348 | 364.686 | 705.434 | 533.226 | 0.000 | 2.413 | 54.241 | 0.000 | -458.531 | 0.000 | -180.381 | -532.760 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 18-JUL-05:12 | 0.00 | 0.00 | 0.00 | -44748.14 | 0.00 | 0.00 | 321.26 | 839.14 | 4989.51 | 0.00 | 0.00 | 0.00 | 38598.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 18-JUL-05:12 | 0.00 | 0.00 | 0.00 | -34102.38 | 0.00 | 0.00 | 329.52 | 839.14 | 3025.92 | 0.00 | 0.00 | 0.00 | 29907.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 05-SEP-06:03 | 0.00 | 0.00 | 0.00 | -33358.83 | 0.00 | 0.00 | 688.52 | 2517.53 | 3025.92 | 0.00 | 0.00 | 0.00 | 27126.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-18:41 | 0.00 | 0.00 | 0.00 | -12638.00 | 0.00 | 0.00 | 0.00 | 42.19 | 386.10 | 4001.06 | 0.00 | 123.39 | 8085.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 06-AUG-09:32 | 0.00 | 0.00 | 0.00 | -15864.06 | 0.00 | 0.00 | 11.27 | 26.71 | 302.86 | 11865.77 | 0.00 | 30.21 | 3627.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 03-SEP-13:01 | 0.00 | 0.00 | 0.00 | -21881.86 | 0.00 | 0.00 | 17.43 | 42.19 | 478.41 | 17372.28 | 0.00 | 325.50 | 3646.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 16-JUL-17:21 | 0.00 | 0.00 | 0.00 | -18496.80 | 0.00 | 0.00 | 0.00 | 26.71 | 244.42 | 13723.09 | 0.00 | 53.04 | 4449.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 06-AUG-16:41 | 0.00 | 0.00 | 0.00 | -7818.96 | 0.00 | 0.00 | 30.23 | 42.19 | 478.42 | 2698.11 | 0.00 | 194.42 | 4375.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 06-AUG-09:21 | 0.00 | 0.00 | 0.00 | -13781.81 | 0.00 | 0.00 | 14.13 | 26.71 | 302.86 | 12477.28 | 0.00 | 1.36 | 959.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 03-SEP-13:22 | 0.00 | 0.00 | 0.00 | -17025.57 | 0.00 | 0.00 | 20.80 | 42.19 | 478.41 | 16927.12 | 0.00 | 172.65 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -615.61 |
PERIMETER_BOT_ZN_4 | 06-AUG-16:41 | 0.00 | 0.00 | 0.00 | -14932.59 | 0.00 | 0.00 | 13.31 | 26.71 | 302.86 | 10716.96 | 0.00 | 95.79 | 3776.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 06-AUG-16:41 | 0.00 | 0.00 | 0.00 | -11048.43 | 0.00 | 0.00 | 27.78 | 42.19 | 478.42 | 2594.07 | 0.00 | 279.80 | 7626.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-08:41 | 0.00 | 0.00 | 0.00 | -17646.99 | 0.00 | 0.00 | 11.31 | 26.71 | 302.86 | 13713.05 | 0.00 | 0.00 | 3643.49 | 0.00 | -0.00 | 0.00 | -50.43 | 0.00 |
PERIMETER_MID_ZN_1 | 03-SEP-13:22 | 0.00 | 0.00 | 0.00 | -19924.10 | 0.00 | 0.00 | 18.38 | 42.19 | 478.41 | 16792.12 | 0.00 | 252.81 | 2340.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 06-AUG-16:41 | 0.00 | 0.00 | 0.00 | -17978.39 | 0.00 | 0.00 | 11.06 | 26.71 | 302.86 | 10602.16 | 0.00 | 129.30 | 6906.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 17-JUL-14:50 | 0.00 | -13291.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.79 | 13283.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-15:30 | 0.00 | -6366.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.32 | 6296.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 17-JUL-12:07 | 0.00 | -6638.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.58 | 6585.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-JUL-15:50 | 0.00 | -25297.39 | 0.00 | -166166.13 | 0.00 | 0.00 | 17713.94 | 30098.83 | 42072.41 | 79331.54 | 0.00 | 2270.92 | 19975.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 27-DEC-07:01 | 0.00 | 0.00 | 18651.47 | 0.00 | 0.00 | 0.00 | 887.40 | 2517.53 | 8796.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -30853.20 |
CORE_MID | 09-JAN-05:11 | 0.00 | 0.00 | 26443.20 | 0.00 | 0.00 | 0.00 | 0.00 | 839.14 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29724.40 |
CORE_TOP | 31-DEC-22:41 | 0.00 | 0.00 | 35796.33 | 0.00 | 0.00 | 0.00 | 0.00 | 419.57 | 1831.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -38047.44 |
PERIMETER_TOP_ZN_3 | 09-JAN-05:21 | 0.00 | 0.00 | 12476.68 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5132.36 | 0.00 | -992.72 | -7043.31 |
PERIMETER_TOP_ZN_2 | 09-JAN-05:21 | 0.00 | 0.00 | 14018.66 | 0.00 | 0.00 | 0.00 | 0.00 | 111.99 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3460.41 | 0.00 | -675.92 | -10320.21 |
PERIMETER_TOP_ZN_1 | 09-JAN-05:21 | 0.00 | 0.00 | 18798.41 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5053.06 | 0.00 | -1015.11 | -13421.94 |
PERIMETER_TOP_ZN_4 | 09-JAN-05:21 | 0.00 | 0.00 | 15735.35 | 0.00 | 0.00 | 0.00 | 0.00 | 111.98 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3359.67 | 0.00 | -679.34 | -12134.22 |
PERIMETER_BOT_ZN_3 | 11-JAN-05:11 | 0.00 | 0.00 | 9211.62 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5727.73 | 0.00 | -231.15 | -3944.44 |
PERIMETER_BOT_ZN_2 | 11-JAN-05:11 | 0.00 | 0.00 | 10982.66 | 0.00 | 0.00 | 0.00 | 0.00 | 111.99 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3749.99 | 0.00 | -155.27 | -7515.29 |
PERIMETER_BOT_ZN_1 | 09-JAN-08:00 | 0.00 | 0.00 | 18430.11 | 0.00 | 0.00 | 0.00 | 262.31 | 530.72 | 637.88 | 0.00 | 0.00 | 0.00 | 14551.80 | 0.00 | -4741.57 | 0.00 | -29671.25 | 0.00 |
PERIMETER_BOT_ZN_4 | 11-JAN-05:11 | 0.00 | 0.00 | 11920.10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.98 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3809.66 | 0.00 | -155.41 | -8392.90 |
PERIMETER_MID_ZN_3 | 06-MAR-05:11 | 0.00 | 0.00 | 10407.07 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4194.62 | 0.00 | -1044.61 | -5859.55 |
PERIMETER_MID_ZN_2 | 06-MAR-05:11 | 0.00 | 0.00 | 12875.97 | 0.00 | 0.00 | 0.00 | 0.00 | 111.99 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2794.25 | 0.00 | -705.44 | -9814.17 |
PERIMETER_MID_ZN_1 | 06-MAR-05:11 | 0.00 | 0.00 | 16627.16 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4346.79 | 0.00 | -1060.85 | -11911.23 |
PERIMETER_MID_ZN_4 | 06-MAR-05:11 | 0.00 | 0.00 | 13073.38 | 0.00 | 0.00 | 0.00 | 0.00 | 111.98 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2874.66 | 0.00 | -705.04 | -9931.56 |
TOPFLOOR_PLENUM | 28-JAN-06:12 | 20706.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -466.71 | -20239.40 |
MIDFLOOR_PLENUM | 09-JAN-07:04 | 12090.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -408.85 | -11681.45 |
FIRSTFLOOR_PLENUM | 22-MAY-05:01 | 8389.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -926.78 | -7462.65 |
Total Facility | 09-JAN-06:01 | 29792.43 | 0.00 | 222881.77 | 0.00 | 0.00 | 0.00 | 2599.27 | 4250.75 | 17291.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -53113.34 | 0.00 | -8270.98 | -215431.42 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.9961 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.2013 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 6.6755 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.6194 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 7.0699 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.3944 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.4981 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5564 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 3.3378 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.6275 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.5350 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.6960 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.5238 | 3.5238 | 0.8246 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6558 | 2.6558 | 0.8047 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7580 | 2.7580 | 0.8302 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8575 | 0.8575 | 0.1749 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9942 | 0.9942 | 0.1988 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3356 | 1.3356 | 0.2671 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1246 | 1.1246 | 0.2249 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6802 | 0.6802 | 0.1735 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8220 | 0.8220 | 0.1644 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0765 | 1.0765 | 0.2153 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8936 | 0.8936 | 0.1787 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7556 | 0.7556 | 0.1700 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9861 | 0.9861 | 0.1972 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2305 | 1.2305 | 0.2461 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0476 | 1.0476 | 0.2095 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.9961 | 6.2013 | 6.9961 | 1.5564 | 0.0000 | 1.0000 |
PACU_VAV_MID | 6.6755 | 5.6194 | 6.6755 | 1.6275 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 7.0699 | 6.3944 | 7.0699 | 1.6960 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7619 | 1.7619 | 0.8246 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3279 | 1.3279 | 0.8047 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3790 | 1.3790 | 0.8302 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4288 | 0.4288 | 0.1749 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4971 | 0.4971 | 0.1988 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6678 | 0.6678 | 0.2671 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5623 | 0.5623 | 0.2249 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3401 | 0.3401 | 0.1735 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4110 | 0.4110 | 0.1644 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5382 | 0.5382 | 0.2153 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4468 | 0.4468 | 0.1787 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3778 | 0.3778 | 0.1700 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4930 | 0.4930 | 0.1972 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6153 | 0.6153 | 0.2461 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5238 | 0.5238 | 0.2095 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.4981 | 1.5564 | 1.5564 | 1.5564 | 0.0000 | 1.0000 |
PACU_VAV_MID | 3.3378 | 1.6275 | 1.6275 | 1.6275 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.5350 | 1.6960 | 1.6960 | 1.6960 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 349.83 |
Number of hours cooling loads not met | 79.33 |
Number of hours not met | 429.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 292.02 | 225214.60 | 231.90 | 151900.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 116.28 | 83931.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 364.69 | 38257.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 111.71 | 8596.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 17.12 | 1242.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 104.99 | 37222.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 141.67 | 12281.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1712.38 |
Natural Gas | 0.00 | 373.57 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 2085.95 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 73.20 |
Space Heating | 58.61 |
Space Cooling | 23.34 |
Fans (All) | 21.07 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 343.70 |
Subtotal | 343.70 |
Natural Gas [MJ/m2] | |
Space Heating | 46.55 |
Service Water Heating | 28.43 |
Miscellaneous (All) | 74.98 |
Subtotal | 74.98 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 17.48 |
Space Heating | 25.12 |
Space Cooling | 5.57 |
Fans (All) | 5.03 |
Service Water Heating | 6.79 |
Receptacle Equipment | 33.82 |
Miscellaneous | 6.18 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8752.83 | 7.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8742.67 | 17.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8741.00 | 19.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8751.83 | 8.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8743.83 | 16.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8746.83 | 13.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8717.33 | 42.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8717.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 42.67 | 0.00 | 0.00 | 0.00 |
Average | 8749.96 | 10.04 | 0.00 | 0.00 | 0.00 |
Sum | 157499.33 | 180.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128296.33 | 7.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 7.67 | 0.00 | 0.00 | 0.00 |
Average | 34142.91 | 0.43 | 0.00 | 0.00 | 0.00 |
Sum | 614572.33 | 7.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8726.67 | 33.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8756.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8751.17 | 8.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8750.50 | 9.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8749.67 | 10.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8726.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 33.33 | 0.00 | 0.00 | 0.00 |
Average | 8752.44 | 7.56 | 0.00 | 0.00 | 0.00 |
Sum | 157543.83 | 136.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128273.67 | 30.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128288.00 | 16.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128297.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128297.33 | 30.33 | 0.00 | 0.00 | 0.00 |
Average | 34140.39 | 2.94 | 0.00 | 0.00 | 0.00 |
Sum | 614527.00 | 53.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.952220E+10 | 10041.56 | 19-JAN-16:40 | -6.1 | -7.8 | 0.179743E+10 | 2606.63 | 20-JAN-10:09 | -3.1 | -5.8 |
February | 0.100724E+11 | 16890.73 | 28-FEB-08:05 | -4.5 | -4.7 | 0.172327E+10 | 2608.34 | 15-FEB-14:50 | -4.5 | -4.7 |
March | 0.143306E+11 | 19898.15 | 01-MAR-08:03 | -9.3 | -10.0 | 0.211259E+10 | 2609.03 | 15-MAR-13:09 | 3.07 | -1.2 |
April | 0.156946E+11 | 19717.52 | 07-APR-16:00 | 21.10 | 8.72 | 0.190409E+10 | 2608.38 | 20-APR-09:00 | 3.90 | 2.38 |
May | 0.190606E+11 | 43676.91 | 22-MAY-05:01 | -0.6 | -0.6 | 0.207106E+10 | 2609.11 | 23-MAY-09:20 | 2.40 | 1.23 |
June | 0.254792E+11 | 41268.76 | 26-JUN-06:02 | 13.03 | 10.64 | 0.207019E+10 | 2606.67 | 29-JUN-09:20 | 25.17 | 12.64 |
July | 0.269733E+11 | 44745.80 | 18-JUL-05:12 | 17.93 | 11.91 | 0.192551E+10 | 2606.73 | 13-JUL-09:00 | 17.93 | 11.91 |
August | 0.282747E+11 | 42974.01 | 14-AUG-06:02 | 11.88 | 9.87 | 0.216181E+10 | 2606.67 | 24-AUG-09:00 | 20.00 | 12.25 |
September | 0.230005E+11 | 42917.68 | 11-SEP-05:12 | 10.93 | 10.10 | 0.191749E+10 | 2606.73 | 07-SEP-09:00 | 10.93 | 10.10 |
October | 0.185589E+11 | 31759.78 | 19-OCT-06:02 | 12.02 | 5.45 | 0.198783E+10 | 2609.11 | 06-OCT-09:30 | 12.02 | 5.45 |
November | 0.137826E+11 | 19177.94 | 06-NOV-08:03 | -2.4 | -3.5 | 0.194217E+10 | 2606.65 | 16-NOV-14:09 | 10.63 | 6.46 |
December | 0.108286E+11 | 15334.01 | 08-DEC-08:20 | -0.2 | -3.0 | 0.183218E+10 | 2608.67 | 08-DEC-14:09 | 3.80 | -0.6 |
Annual Sum or Average | 0.215578E+12 | 0.234456E+11 | ||||||||
Minimum of Months | 0.952220E+10 | 10041.56 | -9.3 | -10.0 | 0.172327E+10 | 2606.63 | -4.5 | -5.8 | ||
Maximum of Months | 0.282747E+11 | 44745.80 | 21.10 | 11.91 | 0.216181E+10 | 2609.11 | 25.17 | 12.64 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1403010.96 | 425.36 | 14-JAN-17:25 | 8.90 | 3.99 | 0.00 | 0.00 | 01-JAN-00:10 | 8.90 | 3.99 |
February | 0.101477E+09 | 1985.17 | 26-FEB-15:02 | 16.60 | 6.44 | 0.00 | 0.00 | 01-FEB-00:10 | 16.60 | 6.44 |
March | 0.403906E+09 | 2503.67 | 22-MAR-16:10 | 11.10 | 4.35 | 0.00 | 0.00 | 01-MAR-00:10 | 11.10 | 4.35 |
April | 0.119062E+10 | 6025.81 | 25-APR-15:20 | 17.27 | 7.54 | 0.00 | 0.00 | 01-APR-00:10 | 17.27 | 7.54 |
May | 0.250654E+10 | 9352.24 | 19-MAY-15:00 | 28.30 | 14.88 | 0.00 | 0.00 | 01-MAY-00:10 | 28.30 | 14.88 |
June | 0.519863E+10 | 10686.89 | 23-JUN-13:30 | 31.40 | 15.21 | 0.00 | 0.00 | 01-JUN-00:10 | 31.40 | 15.21 |
July | 0.698947E+10 | 13292.07 | 17-JUL-14:50 | 36.20 | 17.00 | 0.00 | 0.00 | 01-JUL-00:10 | 36.20 | 17.00 |
August | 0.599388E+10 | 12059.82 | 07-AUG-15:30 | 32.50 | 16.07 | 0.00 | 0.00 | 01-AUG-00:10 | 32.50 | 16.07 |
September | 0.286493E+10 | 9014.34 | 01-SEP-15:40 | 28.30 | 14.15 | 0.00 | 0.00 | 01-SEP-00:10 | 28.30 | 14.15 |
October | 0.820188E+09 | 5690.93 | 18-OCT-15:20 | 24.80 | 11.42 | 0.00 | 0.00 | 01-OCT-00:10 | 24.80 | 11.42 |
November | 73641119.56 | 1347.13 | 03-NOV-14:30 | 14.80 | 7.76 | 0.00 | 0.00 | 01-NOV-00:10 | 14.80 | 7.76 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.261447E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.1 | -4.2 | 0.00 | 0.00 | -2.1 | -4.2 | ||
Maximum of Months | 0.698947E+10 | 13292.07 | 36.20 | 17.00 | 0.00 | 0.00 | 36.20 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44499546.00 | 3690.42 | 28-JAN-03:22 | -29.4 | -29.8 | 0.00 | 0.00 | 01-JAN-00:10 | -29.4 | -29.8 |
February | 44704558.21 | 4523.25 | 01-FEB-05:11 | -25.0 | -25.2 | 0.00 | 0.00 | 01-FEB-00:10 | -25.0 | -25.2 |
March | 0.126523E+09 | 4696.46 | 04-MAR-05:01 | -19.1 | -19.6 | 0.00 | 0.00 | 01-MAR-00:10 | -19.1 | -19.6 |
April | 0.380396E+09 | 3193.28 | 29-APR-05:01 | -7.7 | -8.6 | 0.00 | 0.00 | 01-APR-00:10 | -7.7 | -8.6 |
May | 0.870647E+09 | 3271.92 | 19-MAY-16:00 | 27.80 | 14.54 | 0.00 | 0.00 | 01-MAY-00:10 | 27.80 | 14.54 |
June | 0.273028E+10 | 4532.45 | 23-JUN-15:30 | 27.50 | 14.33 | 0.00 | 0.00 | 01-JUN-00:10 | 27.50 | 14.33 |
July | 0.394975E+10 | 6367.06 | 17-JUL-15:30 | 36.65 | 17.14 | 0.00 | 0.00 | 01-JUL-00:10 | 36.65 | 17.14 |
August | 0.358808E+10 | 6362.65 | 07-AUG-15:30 | 32.50 | 16.07 | 0.00 | 0.00 | 01-AUG-00:10 | 32.50 | 16.07 |
September | 0.173756E+10 | 5565.82 | 05-SEP-14:30 | 24.40 | 14.96 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 14.96 |
October | 0.449227E+09 | 1784.82 | 18-OCT-16:00 | 24.40 | 11.02 | 0.00 | 0.00 | 01-OCT-00:10 | 24.40 | 11.02 |
November | 0.113850E+09 | 2081.55 | 28-NOV-05:01 | -5.5 | -6.7 | 0.00 | 0.00 | 01-NOV-00:10 | -5.5 | -6.7 |
December | 25638732.97 | 3599.20 | 23-DEC-05:01 | -11.6 | -12.4 | 0.00 | 0.00 | 01-DEC-00:10 | -11.6 | -12.4 |
Annual Sum or Average | 0.140612E+11 | 0.00 | ||||||||
Minimum of Months | 25638732.97 | 1784.82 | -29.4 | -29.8 | 0.00 | 0.00 | -29.4 | -29.8 | ||
Maximum of Months | 0.394975E+10 | 6367.06 | 36.65 | 17.14 | 0.00 | 0.00 | 36.65 | 17.14 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58134369.50 | 3616.05 | 28-JAN-05:01 | -27.5 | -27.9 | 0.00 | 0.00 | 01-JAN-00:10 | -27.5 | -27.9 |
February | 85757627.17 | 3987.93 | 04-FEB-05:11 | -20.2 | -20.6 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.6 |
March | 0.245064E+09 | 4366.02 | 04-MAR-05:01 | -19.1 | -19.6 | 0.00 | 0.00 | 01-MAR-00:10 | -19.1 | -19.6 |
April | 0.637586E+09 | 3799.58 | 29-APR-05:01 | -7.7 | -8.6 | 0.00 | 0.00 | 01-APR-00:10 | -7.7 | -8.6 |
May | 0.123050E+10 | 3468.48 | 19-MAY-16:00 | 27.80 | 14.54 | 0.00 | 0.00 | 01-MAY-00:10 | 27.80 | 14.54 |
June | 0.328313E+10 | 4770.63 | 23-JUN-15:30 | 27.50 | 14.33 | 0.00 | 0.00 | 01-JUN-00:10 | 27.50 | 14.33 |
July | 0.448533E+10 | 6639.01 | 17-JUL-12:07 | 35.18 | 16.48 | 0.00 | 0.00 | 01-JUL-00:10 | 35.18 | 16.48 |
August | 0.431519E+10 | 6332.41 | 07-AUG-16:00 | 32.20 | 16.16 | 0.00 | 0.00 | 01-AUG-00:10 | 32.20 | 16.16 |
September | 0.237951E+10 | 5843.48 | 05-SEP-15:10 | 24.03 | 14.68 | 0.00 | 0.00 | 01-SEP-00:10 | 24.03 | 14.68 |
October | 0.873551E+09 | 2805.35 | 18-OCT-16:00 | 24.40 | 11.02 | 0.00 | 0.00 | 01-OCT-00:10 | 24.40 | 11.02 |
November | 0.213749E+09 | 2401.20 | 02-NOV-06:03 | -1.6 | -3.2 | 0.00 | 0.00 | 01-NOV-00:10 | -1.6 | -3.2 |
December | 54279528.04 | 3565.85 | 30-DEC-05:11 | -20.6 | -21.1 | 0.00 | 0.00 | 01-DEC-00:10 | -20.6 | -21.1 |
Annual Sum or Average | 0.178618E+11 | 0.00 | ||||||||
Minimum of Months | 54279528.04 | 2401.20 | -27.5 | -27.9 | 0.00 | 0.00 | -27.5 | -27.9 | ||
Maximum of Months | 0.448533E+10 | 6639.01 | 35.18 | 16.48 | 0.00 | 0.00 | 35.18 | 16.48 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.532028E+10 | 6324.32 | 13-JAN-17:00 | 7.80 | 3.93 | 0.153888E+10 | 2286.81 | 13-JAN-16:00 | 7.80 | 3.93 |
February | 0.627771E+10 | 9161.65 | 28-FEB-17:00 | 10.00 | 4.31 | 0.149764E+10 | 2606.34 | 28-FEB-14:00 | 10.00 | 4.31 |
March | 0.868788E+10 | 9424.37 | 01-MAR-17:00 | 7.80 | 3.22 | 0.191948E+10 | 2606.59 | 02-MAR-14:30 | 10.85 | 4.60 |
April | 0.973492E+10 | 13205.07 | 25-APR-16:00 | 17.80 | 7.70 | 0.182506E+10 | 2606.62 | 13-APR-09:20 | 17.80 | 7.70 |
May | 0.119913E+11 | 16269.56 | 30-MAY-16:00 | 19.40 | 11.02 | 0.199791E+10 | 2606.67 | 04-MAY-13:09 | 19.40 | 11.02 |
June | 0.176366E+11 | 29032.49 | 26-JUN-06:02 | 13.03 | 10.64 | 0.206092E+10 | 2606.65 | 20-JUN-09:00 | 13.03 | 10.64 |
July | 0.194235E+11 | 34102.29 | 18-JUL-05:12 | 17.93 | 11.91 | 0.192087E+10 | 2606.69 | 13-JUL-09:00 | 17.93 | 11.91 |
August | 0.195472E+11 | 31968.39 | 07-AUG-06:03 | 19.45 | 10.91 | 0.215550E+10 | 2606.65 | 01-AUG-13:09 | 19.45 | 10.91 |
September | 0.145690E+11 | 32499.93 | 05-SEP-06:03 | 18.90 | 13.05 | 0.189635E+10 | 2606.70 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.106048E+11 | 14137.28 | 19-OCT-16:00 | 21.10 | 10.04 | 0.191799E+10 | 2606.62 | 20-OCT-09:09 | 7.98 | 4.07 |
November | 0.789150E+10 | 10194.22 | 03-NOV-16:00 | 14.30 | 7.69 | 0.174805E+10 | 2606.58 | 09-NOV-14:09 | 9.33 | 4.09 |
December | 0.652716E+10 | 6962.81 | 07-DEC-16:20 | 5.93 | 1.89 | 0.156619E+10 | 2498.37 | 07-DEC-14:00 | 5.93 | 1.89 |
Annual Sum or Average | 0.138212E+12 | 0.220448E+11 | ||||||||
Minimum of Months | 0.532028E+10 | 6324.32 | 5.93 | 1.89 | 0.149764E+10 | 2286.81 | 5.93 | 1.89 | ||
Maximum of Months | 0.195472E+11 | 34102.29 | 21.10 | 13.05 | 0.215550E+10 | 2606.70 | 19.45 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.327171E+10 | 6205.33 | 13-JAN-16:50 | 7.98 | 4.06 | 0.147691E+10 | 2215.25 | 13-JAN-16:00 | 7.80 | 3.93 |
February | 0.455192E+10 | 7703.77 | 28-FEB-17:00 | 10.00 | 4.31 | 0.140804E+10 | 2536.43 | 28-FEB-16:00 | 10.00 | 4.31 |
March | 0.724761E+10 | 7815.99 | 29-MAR-16:00 | 12.20 | 4.07 | 0.179149E+10 | 2585.57 | 23-MAR-13:00 | 12.20 | 4.07 |
April | 0.878431E+10 | 14265.83 | 25-APR-16:00 | 17.80 | 7.70 | 0.172712E+10 | 2606.59 | 13-APR-13:00 | 17.80 | 7.70 |
May | 0.113559E+11 | 17680.68 | 19-MAY-16:00 | 27.80 | 14.54 | 0.193146E+10 | 2606.63 | 04-MAY-13:30 | 27.80 | 14.54 |
June | 0.173465E+11 | 19970.71 | 23-JUN-14:00 | 31.70 | 15.26 | 0.204758E+10 | 2606.64 | 20-JUN-09:00 | 31.70 | 15.26 |
July | 0.195680E+11 | 30895.15 | 17-JUL-06:03 | 19.05 | 13.84 | 0.191504E+10 | 2606.68 | 13-JUL-09:00 | 19.05 | 13.84 |
August | 0.189567E+11 | 26846.71 | 07-AUG-06:03 | 19.45 | 10.91 | 0.214468E+10 | 2606.66 | 01-AUG-13:09 | 19.45 | 10.91 |
September | 0.133767E+11 | 33355.85 | 05-SEP-06:03 | 18.90 | 13.05 | 0.184436E+10 | 2606.69 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.910112E+10 | 13803.86 | 18-OCT-16:00 | 24.40 | 11.02 | 0.180412E+10 | 2606.57 | 19-OCT-13:09 | 21.10 | 10.07 |
November | 0.621590E+10 | 8231.09 | 03-NOV-16:00 | 14.30 | 7.69 | 0.161609E+10 | 2548.98 | 03-NOV-13:00 | 14.30 | 7.69 |
December | 0.425524E+10 | 6706.80 | 07-DEC-16:20 | 5.93 | 1.89 | 0.146956E+10 | 2367.16 | 07-DEC-14:00 | 5.93 | 1.89 |
Annual Sum or Average | 0.124032E+12 | 0.211765E+11 | ||||||||
Minimum of Months | 0.327171E+10 | 6205.33 | 5.93 | 1.89 | 0.140804E+10 | 2215.25 | 5.93 | 1.89 | ||
Maximum of Months | 0.195680E+11 | 33355.85 | 31.70 | 15.26 | 0.214468E+10 | 2606.69 | 31.70 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15267087.53 | 950.55 | 14-JAN-17:03 | 8.90 | 4.06 | 0.302623E+09 | 406.72 | 05-JAN-14:39 | 8.90 | 4.06 |
February | 0.167011E+09 | 1379.93 | 27-FEB-16:10 | 17.78 | 6.92 | 0.279239E+09 | 486.03 | 27-FEB-16:19 | 16.67 | 6.71 |
March | 0.596616E+09 | 1437.73 | 29-MAR-16:00 | 12.20 | 4.07 | 0.343296E+09 | 500.83 | 29-MAR-15:00 | 12.20 | 4.07 |
April | 0.124152E+10 | 3452.23 | 07-APR-14:30 | 22.50 | 9.29 | 0.331951E+09 | 549.48 | 07-APR-13:00 | 22.50 | 9.29 |
May | 0.225051E+10 | 5517.75 | 19-MAY-16:00 | 27.80 | 14.54 | 0.384555E+09 | 549.50 | 19-MAY-13:09 | 27.80 | 14.54 |
June | 0.448480E+10 | 6667.51 | 29-JUN-15:20 | 31.83 | 14.57 | 0.425223E+09 | 549.50 | 29-JUN-09:30 | 31.83 | 14.57 |
July | 0.550976E+10 | 12638.28 | 16-JUL-18:41 | 32.30 | 17.18 | 0.402533E+09 | 549.51 | 13-JUL-09:00 | 32.30 | 17.18 |
August | 0.473342E+10 | 12339.84 | 06-AUG-16:11 | 35.40 | 16.13 | 0.444764E+09 | 549.50 | 01-AUG-13:09 | 35.40 | 16.13 |
September | 0.264416E+10 | 11298.06 | 04-SEP-15:41 | 32.70 | 16.52 | 0.367697E+09 | 549.50 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.124423E+10 | 2753.43 | 19-OCT-14:40 | 21.50 | 10.24 | 0.344876E+09 | 549.48 | 19-OCT-13:00 | 21.50 | 10.24 |
November | 0.453032E+09 | 1338.16 | 03-NOV-16:00 | 14.30 | 7.69 | 0.310094E+09 | 478.62 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 72824647.74 | 1059.77 | 06-DEC-16:20 | 8.50 | 3.80 | 0.293791E+09 | 413.47 | 06-DEC-14:00 | 8.50 | 3.80 |
Annual Sum or Average | 0.234131E+11 | 0.423064E+10 | ||||||||
Minimum of Months | 15267087.53 | 950.55 | 8.50 | 3.80 | 0.279239E+09 | 406.72 | 8.50 | 3.80 | ||
Maximum of Months | 0.550976E+10 | 12638.28 | 35.40 | 17.18 | 0.444764E+09 | 549.51 | 35.40 | 17.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 56957840.49 | 1146.22 | 20-JAN-10:25 | -2.8 | -5.5 | 0.192964E+09 | 257.93 | 20-JAN-10:39 | -2.6 | -5.4 |
February | 0.399947E+09 | 1752.93 | 27-FEB-10:40 | 13.50 | 5.02 | 0.180454E+09 | 343.76 | 27-FEB-10:50 | 13.95 | 5.20 |
March | 0.987727E+09 | 3769.16 | 23-MAR-10:10 | 8.40 | 1.62 | 0.227772E+09 | 347.88 | 22-MAR-09:00 | 8.40 | 1.62 |
April | 0.189724E+10 | 6431.20 | 25-APR-09:20 | 10.33 | 5.07 | 0.220776E+09 | 347.88 | 12-APR-09:30 | 10.33 | 5.07 |
May | 0.293240E+10 | 8034.19 | 19-MAY-08:50 | 17.52 | 11.29 | 0.253242E+09 | 347.89 | 02-MAY-13:09 | 17.52 | 11.29 |
June | 0.528106E+10 | 11947.44 | 25-JUN-08:22 | 16.15 | 11.58 | 0.270835E+09 | 348.64 | 23-JUN-09:00 | 16.15 | 11.58 |
July | 0.653894E+10 | 15586.44 | 16-JUL-09:22 | 22.75 | 16.30 | 0.255127E+09 | 348.52 | 03-JUL-09:00 | 22.75 | 16.30 |
August | 0.582080E+10 | 15864.10 | 06-AUG-09:32 | 29.07 | 14.77 | 0.283525E+09 | 348.55 | 11-AUG-09:50 | 27.52 | 12.49 |
September | 0.322524E+10 | 11697.95 | 04-SEP-08:22 | 26.15 | 14.59 | 0.237377E+09 | 347.88 | 14-SEP-13:00 | 21.70 | 13.42 |
October | 0.162648E+10 | 4693.66 | 18-OCT-09:40 | 19.07 | 8.41 | 0.226987E+09 | 347.87 | 27-OCT-09:50 | 9.53 | 4.51 |
November | 0.636474E+09 | 1755.61 | 03-NOV-09:50 | 8.30 | 5.09 | 0.198435E+09 | 343.22 | 03-NOV-09:00 | 8.70 | 5.33 |
December | 0.138640E+09 | 1222.89 | 20-DEC-10:20 | 3.67 | -0.4 | 0.186294E+09 | 267.78 | 20-DEC-10:30 | 3.85 | -0.4 |
Annual Sum or Average | 0.295419E+11 | 0.273379E+10 | ||||||||
Minimum of Months | 56957840.49 | 1146.22 | -2.8 | -5.5 | 0.180454E+09 | 257.93 | -2.6 | -5.4 | ||
Maximum of Months | 0.653894E+10 | 15864.10 | 29.07 | 16.30 | 0.283525E+09 | 348.64 | 27.52 | 16.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.772344E+09 | 5368.88 | 19-JAN-13:40 | -6.0 | -7.8 | 0.323234E+09 | 549.49 | 31-JAN-14:00 | -1.1 | -4.4 |
February | 0.181767E+10 | 11797.13 | 26-FEB-14:02 | 15.78 | 5.88 | 0.312569E+09 | 549.49 | 01-FEB-14:00 | 15.78 | 5.88 |
March | 0.272681E+10 | 11421.24 | 01-MAR-14:00 | 6.70 | 2.77 | 0.378204E+09 | 549.50 | 14-MAR-13:00 | 15.00 | 6.94 |
April | 0.315196E+10 | 11254.18 | 25-APR-13:30 | 16.40 | 7.12 | 0.346347E+09 | 549.50 | 13-APR-13:00 | 16.40 | 7.12 |
May | 0.415630E+10 | 10991.17 | 19-MAY-13:40 | 26.83 | 14.98 | 0.390740E+09 | 549.52 | 02-MAY-13:09 | 26.83 | 14.98 |
June | 0.641517E+10 | 10924.90 | 23-JUN-13:10 | 31.20 | 15.18 | 0.419095E+09 | 549.50 | 29-JUN-09:30 | 25.55 | 12.82 |
July | 0.818432E+10 | 19613.94 | 09-JUL-15:12 | 28.30 | 13.14 | 0.399256E+09 | 550.02 | 17-JUL-13:00 | 36.70 | 17.01 |
August | 0.882016E+10 | 20744.83 | 06-AUG-13:32 | 34.23 | 15.17 | 0.442371E+09 | 550.11 | 31-AUG-13:20 | 25.73 | 14.32 |
September | 0.660235E+10 | 21881.87 | 03-SEP-13:01 | 33.40 | 15.99 | 0.375200E+09 | 550.25 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.443704E+10 | 21247.79 | 15-OCT-14:42 | 22.88 | 11.06 | 0.376081E+09 | 549.73 | 18-OCT-13:00 | 25.00 | 11.40 |
November | 0.229943E+10 | 11733.43 | 03-NOV-13:30 | 14.35 | 7.74 | 0.348760E+09 | 549.49 | 13-NOV-14:00 | 4.30 | -1.8 |
December | 0.111224E+10 | 5738.16 | 07-DEC-13:40 | 8.67 | 3.00 | 0.319514E+09 | 549.49 | 12-DEC-14:00 | -2.8 | -5.6 |
Annual Sum or Average | 0.504958E+11 | 0.443137E+10 | ||||||||
Minimum of Months | 0.772344E+09 | 5368.88 | -6.0 | -7.8 | 0.312569E+09 | 549.49 | -2.8 | -5.6 | ||
Maximum of Months | 0.882016E+10 | 21881.87 | 34.23 | 15.99 | 0.442371E+09 | 550.25 | 36.70 | 17.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112099E+09 | 1660.95 | 13-JAN-15:50 | 9.08 | 4.76 | 0.193320E+09 | 293.29 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.435483E+09 | 4259.08 | 28-FEB-16:40 | 10.37 | 4.49 | 0.180550E+09 | 338.90 | 28-FEB-14:00 | 10.37 | 4.49 |
March | 0.954455E+09 | 5395.05 | 28-MAR-16:00 | 10.60 | 3.09 | 0.220635E+09 | 347.82 | 02-MAR-14:00 | 10.60 | 3.09 |
April | 0.192043E+10 | 10470.25 | 22-APR-17:06 | 16.10 | 8.62 | 0.206067E+09 | 347.84 | 07-APR-13:00 | 16.10 | 8.62 |
May | 0.317064E+10 | 16454.29 | 28-MAY-17:12 | 20.73 | 10.39 | 0.237138E+09 | 347.85 | 19-MAY-13:09 | 20.73 | 10.39 |
June | 0.497905E+10 | 17078.90 | 24-JUN-17:42 | 26.38 | 11.78 | 0.260728E+09 | 347.85 | 29-JUN-09:39 | 25.93 | 13.00 |
July | 0.598443E+10 | 18497.86 | 16-JUL-17:21 | 33.05 | 17.12 | 0.250143E+09 | 347.86 | 13-JUL-09:00 | 33.05 | 17.12 |
August | 0.537162E+10 | 17646.08 | 06-AUG-16:11 | 35.40 | 16.13 | 0.274165E+09 | 347.85 | 01-AUG-13:09 | 35.40 | 16.13 |
September | 0.337848E+10 | 17790.39 | 04-SEP-16:21 | 32.80 | 16.63 | 0.225067E+09 | 347.85 | 05-SEP-09:09 | 17.20 | 11.96 |
October | 0.173644E+10 | 8462.89 | 15-OCT-16:42 | 21.28 | 10.50 | 0.215076E+09 | 347.83 | 18-OCT-13:00 | 25.00 | 11.40 |
November | 0.675892E+09 | 3281.68 | 03-NOV-15:40 | 14.40 | 7.69 | 0.200387E+09 | 339.38 | 09-NOV-14:00 | 9.00 | 3.82 |
December | 0.200632E+09 | 1805.07 | 06-DEC-15:50 | 9.68 | 4.65 | 0.187417E+09 | 311.27 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.289196E+11 | 0.265069E+10 | ||||||||
Minimum of Months | 0.112099E+09 | 1660.95 | 9.08 | 3.09 | 0.180550E+09 | 293.29 | 8.90 | 3.09 | ||
Maximum of Months | 0.598443E+10 | 18497.86 | 35.40 | 17.12 | 0.274165E+09 | 347.86 | 35.40 | 17.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13657817.01 | 942.92 | 14-JAN-17:03 | 8.90 | 4.06 | 0.302611E+09 | 406.71 | 10-JAN-14:30 | 8.90 | 4.06 |
February | 0.145568E+09 | 1192.42 | 27-FEB-16:20 | 16.67 | 6.71 | 0.278812E+09 | 445.34 | 27-FEB-14:00 | 16.67 | 6.71 |
March | 0.474734E+09 | 1234.45 | 29-MAR-16:00 | 12.20 | 4.07 | 0.337467E+09 | 457.70 | 29-MAR-13:00 | 12.20 | 4.07 |
April | 0.100939E+10 | 1497.34 | 07-APR-14:40 | 22.23 | 9.16 | 0.316990E+09 | 529.29 | 07-APR-13:00 | 22.23 | 9.16 |
May | 0.176676E+10 | 3333.82 | 19-MAY-16:00 | 27.80 | 14.54 | 0.375556E+09 | 549.48 | 19-MAY-13:00 | 27.80 | 14.54 |
June | 0.338076E+10 | 4861.70 | 23-JUN-13:50 | 31.60 | 15.24 | 0.426624E+09 | 549.50 | 23-JUN-09:09 | 31.60 | 15.24 |
July | 0.448116E+10 | 6743.85 | 17-JUL-06:03 | 19.05 | 13.84 | 0.403234E+09 | 549.50 | 13-JUL-09:00 | 19.05 | 13.84 |
August | 0.398146E+10 | 7818.94 | 06-AUG-16:41 | 35.10 | 15.80 | 0.449056E+09 | 549.50 | 01-AUG-13:09 | 35.10 | 15.80 |
September | 0.265620E+10 | 5525.82 | 05-SEP-06:03 | 18.90 | 13.05 | 0.379025E+09 | 549.50 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.164014E+10 | 2392.92 | 19-OCT-14:30 | 21.40 | 10.24 | 0.360875E+09 | 549.48 | 19-OCT-13:00 | 21.40 | 10.24 |
November | 0.759359E+09 | 1346.88 | 08-NOV-14:10 | 13.78 | 7.92 | 0.318293E+09 | 491.81 | 08-NOV-14:20 | 13.67 | 7.87 |
December | 0.125620E+09 | 1063.74 | 06-DEC-16:20 | 8.50 | 3.80 | 0.295054E+09 | 420.21 | 06-DEC-14:00 | 8.50 | 3.80 |
Annual Sum or Average | 0.204348E+11 | 0.424360E+10 | ||||||||
Minimum of Months | 13657817.01 | 942.92 | 8.50 | 3.80 | 0.278812E+09 | 406.71 | 8.50 | 3.80 | ||
Maximum of Months | 0.448116E+10 | 7818.94 | 35.10 | 15.80 | 0.449056E+09 | 549.50 | 35.10 | 15.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 51759803.76 | 983.91 | 20-JAN-09:55 | -3.3 | -5.9 | 0.193514E+09 | 263.80 | 20-JAN-10:09 | -3.1 | -5.8 |
February | 0.379341E+09 | 1427.33 | 27-FEB-10:40 | 13.50 | 5.02 | 0.181725E+09 | 339.81 | 27-FEB-10:50 | 13.95 | 5.20 |
March | 0.827066E+09 | 2171.32 | 23-MAR-10:30 | 8.60 | 1.66 | 0.227386E+09 | 347.88 | 28-MAR-09:09 | 5.37 | 0.68 |
April | 0.145969E+10 | 4023.65 | 25-APR-09:30 | 10.80 | 5.26 | 0.220153E+09 | 347.87 | 24-APR-09:39 | 10.80 | 5.26 |
May | 0.224480E+10 | 5267.67 | 19-MAY-09:20 | 18.53 | 11.74 | 0.253899E+09 | 347.87 | 02-MAY-09:00 | 18.53 | 11.74 |
June | 0.442214E+10 | 9185.73 | 30-JUN-06:02 | 12.67 | 9.41 | 0.272700E+09 | 348.27 | 23-JUN-09:50 | 12.67 | 9.41 |
July | 0.582804E+10 | 12340.51 | 16-JUL-09:42 | 23.12 | 16.45 | 0.256606E+09 | 348.15 | 14-JUL-09:00 | 23.12 | 16.45 |
August | 0.534766E+10 | 13781.69 | 06-AUG-09:21 | 28.60 | 14.63 | 0.286389E+09 | 348.20 | 09-AUG-09:50 | 28.95 | 16.07 |
September | 0.316021E+10 | 9030.07 | 04-SEP-08:22 | 26.15 | 14.59 | 0.246470E+09 | 347.88 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.184619E+10 | 3908.52 | 18-OCT-09:50 | 19.53 | 8.61 | 0.241731E+09 | 347.88 | 11-OCT-09:09 | 19.53 | 8.61 |
November | 0.871018E+09 | 1740.76 | 03-NOV-09:15 | 7.10 | 4.34 | 0.208197E+09 | 347.88 | 03-NOV-09:20 | 7.10 | 4.34 |
December | 0.214946E+09 | 1080.47 | 07-DEC-10:50 | 5.55 | 2.29 | 0.187634E+09 | 278.90 | 07-DEC-10:00 | 6.10 | 2.52 |
Annual Sum or Average | 0.266529E+11 | 0.277640E+10 | ||||||||
Minimum of Months | 51759803.76 | 983.91 | -3.3 | -5.9 | 0.181725E+09 | 263.80 | -3.1 | -5.8 | ||
Maximum of Months | 0.582804E+10 | 13781.69 | 28.60 | 16.45 | 0.286389E+09 | 348.27 | 28.95 | 16.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324974E+09 | 2492.05 | 14-JAN-12:30 | 10.30 | 4.97 | 0.292447E+09 | 494.38 | 13-JAN-14:00 | 10.30 | 4.97 |
February | 0.984247E+09 | 13949.47 | 26-FEB-13:12 | 15.20 | 5.59 | 0.289235E+09 | 549.50 | 24-FEB-14:09 | 15.20 | 5.59 |
March | 0.125411E+10 | 7017.27 | 01-MAR-13:20 | 5.97 | 2.26 | 0.358155E+09 | 549.50 | 16-MAR-13:09 | 5.10 | -1.2 |
April | 0.157824E+10 | 6519.90 | 25-APR-12:08 | 15.28 | 6.55 | 0.332507E+09 | 549.50 | 13-APR-13:09 | 15.28 | 6.55 |
May | 0.235226E+10 | 7815.45 | 19-MAY-14:00 | 27.20 | 15.02 | 0.373331E+09 | 549.51 | 25-MAY-13:09 | 17.20 | 8.78 |
June | 0.460314E+10 | 11280.44 | 29-JUN-12:00 | 30.60 | 14.31 | 0.413011E+09 | 549.52 | 19-JUN-13:39 | 30.60 | 14.31 |
July | 0.710085E+10 | 14178.82 | 17-JUL-12:00 | 35.00 | 16.37 | 0.399687E+09 | 589.97 | 17-JUL-12:09 | 35.18 | 16.48 |
August | 0.774003E+10 | 16724.23 | 06-AUG-16:41 | 35.10 | 15.80 | 0.444532E+09 | 590.70 | 07-AUG-12:09 | 32.80 | 15.88 |
September | 0.571153E+10 | 17025.61 | 03-SEP-13:22 | 33.60 | 16.11 | 0.380302E+09 | 549.74 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.378923E+10 | 15572.39 | 15-OCT-14:12 | 23.13 | 11.13 | 0.381115E+09 | 549.70 | 23-OCT-13:00 | 20.60 | 9.52 |
November | 0.176013E+10 | 8520.49 | 03-NOV-12:05 | 12.62 | 7.22 | 0.345091E+09 | 549.50 | 15-NOV-14:09 | 10.28 | 4.16 |
December | 0.588605E+09 | 3299.33 | 06-DEC-14:40 | 11.30 | 5.42 | 0.302121E+09 | 549.50 | 07-DEC-14:09 | 8.30 | 2.72 |
Annual Sum or Average | 0.377873E+11 | 0.431153E+10 | ||||||||
Minimum of Months | 0.324974E+09 | 2492.05 | 5.97 | 2.26 | 0.289235E+09 | 494.38 | 5.10 | -1.2 | ||
Maximum of Months | 0.774003E+10 | 17025.61 | 35.10 | 16.37 | 0.444532E+09 | 590.70 | 35.18 | 16.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 72018888.35 | 1290.04 | 13-JAN-15:50 | 9.08 | 4.76 | 0.193749E+09 | 288.51 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.365975E+09 | 3136.51 | 28-FEB-16:50 | 10.18 | 4.40 | 0.180374E+09 | 338.69 | 27-FEB-16:30 | 10.18 | 4.40 |
March | 0.752953E+09 | 3345.09 | 28-MAR-17:30 | 9.75 | 2.59 | 0.219130E+09 | 342.33 | 02-MAR-14:00 | 9.75 | 2.59 |
April | 0.141069E+10 | 5821.35 | 16-APR-17:12 | 19.80 | 8.90 | 0.205764E+09 | 344.21 | 25-APR-13:00 | 16.10 | 6.69 |
May | 0.237288E+10 | 13694.90 | 28-MAY-18:21 | 19.45 | 10.26 | 0.241155E+09 | 347.84 | 30-MAY-13:00 | 18.90 | 10.34 |
June | 0.394894E+10 | 13508.39 | 18-JUN-18:12 | 25.00 | 15.04 | 0.267821E+09 | 347.85 | 29-JUN-09:20 | 25.17 | 12.64 |
July | 0.509098E+10 | 14401.54 | 16-JUL-18:21 | 32.50 | 17.04 | 0.255170E+09 | 347.86 | 13-JUL-09:00 | 32.50 | 17.04 |
August | 0.469244E+10 | 14932.55 | 06-AUG-16:41 | 35.10 | 15.80 | 0.283004E+09 | 347.85 | 01-AUG-13:09 | 35.10 | 15.80 |
September | 0.315697E+10 | 14008.66 | 04-SEP-17:01 | 32.62 | 16.70 | 0.238826E+09 | 347.86 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.193350E+10 | 5686.66 | 18-OCT-16:00 | 24.40 | 11.02 | 0.229682E+09 | 347.84 | 19-OCT-13:00 | 21.10 | 10.22 |
November | 0.921510E+09 | 2802.51 | 03-NOV-15:50 | 14.35 | 7.69 | 0.206036E+09 | 338.68 | 06-NOV-16:40 | 6.87 | 2.36 |
December | 0.234885E+09 | 1450.98 | 06-DEC-15:50 | 9.68 | 4.65 | 0.188647E+09 | 313.77 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.249537E+11 | 0.270936E+10 | ||||||||
Minimum of Months | 72018888.35 | 1290.04 | 9.08 | 2.59 | 0.180374E+09 | 288.51 | 6.87 | 2.36 | ||
Maximum of Months | 0.509098E+10 | 14932.55 | 35.10 | 17.04 | 0.283004E+09 | 347.86 | 35.10 | 17.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28817969.73 | 1002.01 | 13-JAN-17:00 | 7.80 | 3.93 | 0.304232E+09 | 406.71 | 10-JAN-14:39 | 7.80 | 3.93 |
February | 0.300997E+09 | 1389.28 | 27-FEB-13:30 | 17.75 | 6.76 | 0.281679E+09 | 495.15 | 27-FEB-16:19 | 16.67 | 6.71 |
March | 0.877083E+09 | 1438.78 | 29-MAR-16:00 | 12.20 | 4.07 | 0.351700E+09 | 513.98 | 29-MAR-13:00 | 12.20 | 4.07 |
April | 0.152927E+10 | 3424.12 | 07-APR-14:30 | 22.50 | 9.29 | 0.344930E+09 | 549.49 | 13-APR-13:00 | 13.30 | 7.60 |
May | 0.239888E+10 | 5014.48 | 19-MAY-16:00 | 27.80 | 14.54 | 0.396054E+09 | 549.49 | 19-MAY-13:20 | 27.80 | 14.54 |
June | 0.451393E+10 | 7024.47 | 30-JUN-06:02 | 12.67 | 9.41 | 0.430765E+09 | 549.50 | 29-JUN-09:20 | 12.67 | 9.41 |
July | 0.542333E+10 | 10139.23 | 16-JUL-18:21 | 32.50 | 17.04 | 0.404351E+09 | 549.51 | 13-JUL-09:00 | 32.50 | 17.04 |
August | 0.477456E+10 | 11048.52 | 06-AUG-16:41 | 35.10 | 15.80 | 0.450528E+09 | 549.50 | 01-AUG-13:09 | 35.10 | 15.80 |
September | 0.286005E+10 | 8664.83 | 05-SEP-06:03 | 18.90 | 13.05 | 0.380758E+09 | 549.51 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.161593E+10 | 3041.56 | 19-OCT-14:30 | 21.40 | 10.24 | 0.362938E+09 | 549.48 | 19-OCT-13:00 | 21.40 | 10.24 |
November | 0.748908E+09 | 1437.17 | 03-NOV-13:30 | 14.35 | 7.74 | 0.319899E+09 | 504.75 | 08-NOV-14:20 | 13.67 | 7.87 |
December | 0.162540E+09 | 1098.33 | 06-DEC-16:50 | 7.15 | 2.74 | 0.295280E+09 | 430.34 | 06-DEC-14:00 | 7.15 | 2.74 |
Annual Sum or Average | 0.252343E+11 | 0.432312E+10 | ||||||||
Minimum of Months | 28817969.73 | 1002.01 | 7.15 | 2.74 | 0.281679E+09 | 406.71 | 7.15 | 2.74 | ||
Maximum of Months | 0.542333E+10 | 11048.52 | 35.10 | 17.04 | 0.450528E+09 | 549.51 | 35.10 | 17.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 98816216.64 | 1254.28 | 20-JAN-10:00 | -3.3 | -5.9 | 0.142298E+09 | 263.84 | 20-JAN-09:00 | -3.3 | -5.9 |
February | 0.527426E+09 | 2559.84 | 28-FEB-09:55 | 1.10 | -0.5 | 0.134362E+09 | 338.71 | 28-FEB-09:50 | 1.10 | -0.5 |
March | 0.123043E+10 | 4409.16 | 23-MAR-10:10 | 8.40 | 1.62 | 0.169429E+09 | 338.72 | 22-MAR-10:09 | 8.40 | 1.62 |
April | 0.219809E+10 | 7006.53 | 25-APR-08:50 | 9.03 | 4.36 | 0.164702E+09 | 338.72 | 12-APR-10:09 | 9.03 | 4.36 |
May | 0.308688E+10 | 8236.03 | 19-MAY-08:50 | 17.52 | 11.29 | 0.188427E+09 | 339.28 | 10-MAY-08:39 | 17.52 | 11.29 |
June | 0.526465E+10 | 14985.46 | 11-JUN-09:22 | 20.30 | 11.53 | 0.200829E+09 | 339.00 | 21-JUN-08:00 | 21.10 | 14.53 |
July | 0.639361E+10 | 15468.18 | 02-JUL-09:02 | 22.48 | 15.33 | 0.189498E+09 | 343.57 | 17-JUL-07:19 | 23.53 | 15.09 |
August | 0.579852E+10 | 17644.52 | 06-AUG-08:41 | 26.55 | 14.17 | 0.210090E+09 | 340.39 | 07-AUG-10:50 | 30.60 | 14.99 |
September | 0.343114E+10 | 12260.33 | 04-SEP-08:22 | 26.15 | 14.59 | 0.177928E+09 | 338.77 | 07-SEP-15:09 | 24.78 | 20.11 |
October | 0.197032E+10 | 5182.23 | 18-OCT-09:00 | 17.20 | 7.57 | 0.171463E+09 | 339.05 | 11-OCT-10:09 | 17.20 | 7.57 |
November | 0.892811E+09 | 2438.08 | 03-NOV-10:10 | 9.10 | 5.57 | 0.150049E+09 | 338.72 | 03-NOV-10:09 | 9.10 | 5.57 |
December | 0.229357E+09 | 1331.75 | 20-DEC-10:00 | 3.30 | -0.6 | 0.137739E+09 | 273.74 | 20-DEC-09:00 | 3.30 | -0.6 |
Annual Sum or Average | 0.311220E+11 | 0.203681E+10 | ||||||||
Minimum of Months | 98816216.64 | 1254.28 | -3.3 | -5.9 | 0.134362E+09 | 263.84 | -3.3 | -5.9 | ||
Maximum of Months | 0.639361E+10 | 17644.52 | 26.55 | 15.33 | 0.210090E+09 | 343.57 | 30.60 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.927312E+09 | 6277.42 | 19-JAN-13:30 | -6.2 | -7.9 | 0.328190E+09 | 549.49 | 31-JAN-14:00 | -1.1 | -4.4 |
February | 0.212988E+10 | 19141.98 | 26-FEB-13:12 | 15.20 | 5.59 | 0.321116E+09 | 549.49 | 28-FEB-10:09 | 1.57 | -0.3 |
March | 0.316742E+10 | 12147.95 | 01-MAR-13:40 | 6.33 | 2.52 | 0.387641E+09 | 549.50 | 23-MAR-13:20 | 9.60 | 2.08 |
April | 0.351614E+10 | 12869.34 | 16-APR-13:53 | 19.40 | 8.41 | 0.356964E+09 | 549.50 | 13-APR-13:00 | 19.40 | 8.41 |
May | 0.428928E+10 | 10477.19 | 19-MAY-13:30 | 26.65 | 14.96 | 0.401020E+09 | 549.52 | 02-MAY-13:09 | 26.65 | 14.96 |
June | 0.633477E+10 | 11982.94 | 11-JUN-13:23 | 25.25 | 13.15 | 0.426593E+09 | 549.52 | 19-JUN-13:30 | 24.70 | 12.18 |
July | 0.793258E+10 | 17083.48 | 16-JUL-13:42 | 31.32 | 18.41 | 0.403092E+09 | 550.18 | 18-JUL-13:50 | 32.07 | 17.42 |
August | 0.874410E+10 | 19406.47 | 06-AUG-10:41 | 30.50 | 14.92 | 0.448916E+09 | 550.16 | 31-AUG-13:39 | 25.37 | 13.99 |
September | 0.686335E+10 | 19924.10 | 03-SEP-13:22 | 33.60 | 16.11 | 0.386048E+09 | 550.24 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.508455E+10 | 18793.59 | 15-OCT-13:32 | 22.93 | 11.00 | 0.389571E+09 | 549.85 | 20-OCT-13:50 | 13.30 | 6.62 |
November | 0.285632E+10 | 12327.12 | 03-NOV-13:20 | 14.13 | 7.69 | 0.360996E+09 | 549.96 | 03-NOV-13:20 | 14.13 | 7.69 |
December | 0.137557E+10 | 6692.10 | 12-DEC-12:30 | -2.8 | -5.7 | 0.327715E+09 | 549.49 | 12-DEC-10:00 | -2.8 | -5.7 |
Annual Sum or Average | 0.532213E+11 | 0.453786E+10 | ||||||||
Minimum of Months | 0.927312E+09 | 6277.42 | -6.2 | -7.9 | 0.321116E+09 | 549.49 | -2.8 | -5.7 | ||
Maximum of Months | 0.874410E+10 | 19924.10 | 33.60 | 18.41 | 0.448916E+09 | 550.24 | 32.07 | 17.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141994E+09 | 1629.99 | 13-JAN-15:50 | 9.08 | 4.76 | 0.194021E+09 | 304.29 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.561750E+09 | 4473.87 | 28-FEB-16:40 | 10.37 | 4.49 | 0.182378E+09 | 347.23 | 28-FEB-14:00 | 10.37 | 4.49 |
March | 0.122460E+10 | 5405.34 | 28-MAR-16:00 | 10.60 | 3.09 | 0.223640E+09 | 347.83 | 02-MAR-14:00 | 10.60 | 3.09 |
April | 0.217362E+10 | 15405.18 | 16-APR-16:32 | 20.00 | 8.92 | 0.211647E+09 | 347.84 | 07-APR-13:00 | 20.00 | 8.92 |
May | 0.326499E+10 | 15863.70 | 28-MAY-17:12 | 20.73 | 10.39 | 0.243527E+09 | 347.85 | 30-MAY-13:00 | 18.90 | 10.34 |
June | 0.490522E+10 | 16294.96 | 18-JUN-18:12 | 25.00 | 15.04 | 0.266580E+09 | 347.85 | 29-JUN-09:20 | 25.17 | 12.64 |
July | 0.579283E+10 | 17098.11 | 16-JUL-17:01 | 33.22 | 17.33 | 0.253549E+09 | 347.86 | 13-JUL-09:00 | 33.22 | 17.33 |
August | 0.529284E+10 | 17978.48 | 06-AUG-16:41 | 35.10 | 15.80 | 0.280145E+09 | 347.85 | 01-AUG-13:09 | 35.10 | 15.80 |
September | 0.351568E+10 | 16528.43 | 04-SEP-16:21 | 32.80 | 16.63 | 0.233036E+09 | 347.86 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.209404E+10 | 6862.48 | 18-OCT-16:00 | 24.40 | 11.02 | 0.223639E+09 | 347.84 | 19-OCT-13:00 | 21.10 | 10.22 |
November | 0.971027E+09 | 3570.31 | 03-NOV-15:40 | 14.40 | 7.69 | 0.205239E+09 | 347.80 | 09-NOV-14:00 | 9.00 | 3.82 |
December | 0.293183E+09 | 1772.68 | 06-DEC-15:50 | 9.68 | 4.65 | 0.188996E+09 | 323.55 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.302318E+11 | 0.270640E+10 | ||||||||
Minimum of Months | 0.141994E+09 | 1629.99 | 9.08 | 3.09 | 0.182378E+09 | 304.29 | 8.90 | 3.09 | ||
Maximum of Months | 0.579283E+10 | 17978.48 | 35.10 | 17.33 | 0.280145E+09 | 347.86 | 35.10 | 17.33 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 82823546.84 | 18536.13 | 10-JAN-07:03 | -23.3 |
February | 9704510.32 | 18133.03 | 06-FEB-06:01 | 0.60 |
March | 1868450.44 | 15662.79 | 06-MAR-07:02 | -19.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 4686588.66 | 18651.49 | 27-DEC-07:01 | -10.1 |
Annual Sum or Average | 99083096.26 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 82823546.84 | 18651.49 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101644E+11 | 20706.10 | 28-JAN-06:12 | -25.9 |
February | 0.519665E+10 | 18886.72 | 01-FEB-06:12 | -25.0 |
March | 0.368404E+10 | 18690.93 | 06-MAR-06:13 | -17.1 |
April | 0.144266E+10 | 9236.37 | 29-APR-06:03 | -6.8 |
May | 0.104329E+10 | 10512.13 | 08-MAY-06:01 | -2.7 |
June | 0.299920E+09 | 4426.88 | 15-JUN-05:03 | 3.17 |
July | 0.153750E+09 | 4570.88 | 09-JUL-08:32 | 19.10 |
August | 0.260819E+09 | 4457.80 | 06-AUG-07:32 | 22.57 |
September | 0.623775E+09 | 4432.97 | 20-SEP-05:15 | 3.30 |
October | 0.142524E+10 | 11649.12 | 10-OCT-06:01 | -6.1 |
November | 0.372356E+10 | 17926.73 | 27-NOV-06:13 | -14.4 |
December | 0.763481E+10 | 18462.09 | 28-DEC-06:12 | -22.8 |
Annual Sum or Average | 0.356529E+11 | |||
Minimum of Months | 0.153750E+09 | 4426.88 | -25.9 | |
Maximum of Months | 0.101644E+11 | 20706.10 | 22.57 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.416274E+10 | 12090.28 | 09-JAN-07:04 | -27.2 |
February | 0.234473E+10 | 9851.99 | 06-FEB-06:12 | 0.60 |
March | 0.170878E+10 | 9588.14 | 06-MAR-07:02 | -19.7 |
April | 0.583074E+09 | 6115.96 | 16-APR-16:32 | 20.00 |
May | 0.577774E+09 | 3652.89 | 28-MAY-17:12 | 20.73 |
June | 25388998.62 | 4243.98 | 18-JUN-14:52 | 24.40 |
July | 33613833.79 | 4106.98 | 16-JUL-15:02 | 33.22 |
August | 25444935.72 | 5732.93 | 06-AUG-15:21 | 35.00 |
September | 0.199057E+09 | 5729.24 | 17-SEP-13:02 | 11.28 |
October | 0.670574E+09 | 6711.51 | 15-OCT-12:12 | 21.47 |
November | 0.174245E+10 | 9430.88 | 27-NOV-07:11 | -13.4 |
December | 0.290537E+10 | 10095.27 | 26-DEC-07:02 | -8.5 |
Annual Sum or Average | 0.149790E+11 | |||
Minimum of Months | 25388998.62 | 3652.89 | -27.2 | |
Maximum of Months | 0.416274E+10 | 12090.28 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315752E+10 | 8268.98 | 09-JAN-07:01 | -27.2 |
February | 0.169082E+10 | 6452.93 | 06-FEB-07:02 | 0.50 |
March | 0.112855E+10 | 5929.47 | 06-MAR-07:01 | -19.7 |
April | 0.266790E+09 | 3118.60 | 21-APR-07:05 | 2.80 |
May | 0.296235E+09 | 8386.27 | 22-MAY-05:01 | -0.6 |
June | 13802259.96 | 2581.72 | 18-JUN-14:02 | 23.48 |
July | 22275227.87 | 2580.65 | 16-JUL-15:42 | 32.88 |
August | 17223929.14 | 3594.93 | 06-AUG-15:21 | 35.00 |
September | 50902252.01 | 2977.63 | 04-SEP-15:41 | 32.70 |
October | 0.235826E+09 | 4317.49 | 15-OCT-12:52 | 22.20 |
November | 0.108053E+10 | 5079.77 | 27-NOV-08:15 | -12.5 |
December | 0.213108E+10 | 6241.87 | 26-DEC-07:02 | -8.5 |
Annual Sum or Average | 0.100915E+11 | |||
Minimum of Months | 13802259.96 | 2580.65 | -27.2 | |
Maximum of Months | 0.315752E+10 | 8386.27 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119387E+10 | 26443.23 | 09-JAN-05:11 | -27.2 |
February | 0.291417E+09 | 25553.15 | 06-FEB-05:01 | -0.4 |
March | 0.147637E+09 | 24358.02 | 06-MAR-06:01 | -16.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 9484107.60 | 21209.10 | 08-MAY-06:01 | -2.7 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 4435133.46 | 21315.86 | 10-OCT-06:01 | -6.1 |
November | 0.138639E+09 | 24095.50 | 27-NOV-06:01 | -14.5 |
December | 0.456312E+09 | 25425.45 | 26-DEC-05:01 | -7.3 |
Annual Sum or Average | 0.224179E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.119387E+10 | 26443.23 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.480172E+10 | 35400.74 | 09-JAN-05:21 | -27.2 |
February | 0.180392E+10 | 35002.98 | 06-FEB-05:01 | -0.4 |
March | 0.947097E+09 | 35536.77 | 06-MAR-05:11 | -17.8 |
April | 65816409.99 | 29722.90 | 29-APR-05:01 | -7.7 |
May | 0.174307E+09 | 31816.63 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 3923177.32 | 14725.04 | 19-SEP-06:03 | 2.20 |
October | 0.117071E+09 | 31928.99 | 10-OCT-05:01 | -6.1 |
November | 0.994817E+09 | 35232.33 | 27-NOV-05:01 | -15.4 |
December | 0.274578E+10 | 35796.18 | 31-DEC-22:41 | -23.9 |
Annual Sum or Average | 0.116545E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.480172E+10 | 35796.18 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.892464E+10 | 12476.72 | 09-JAN-05:21 | -27.2 |
February | 0.435474E+10 | 11790.44 | 05-FEB-20:52 | -18.3 |
March | 0.252588E+10 | 12225.30 | 06-MAR-05:11 | -17.8 |
April | 0.508518E+09 | 10536.62 | 29-APR-04:02 | -7.8 |
May | 0.368780E+09 | 10891.33 | 01-MAY-04:01 | -0.6 |
June | 2505200.27 | 6277.97 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 1281567.54 | 6405.14 | 18-AUG-06:03 | 8.17 |
September | 79123468.76 | 9667.76 | 19-SEP-05:11 | 2.20 |
October | 0.505238E+09 | 10856.18 | 10-OCT-04:01 | -5.2 |
November | 0.261897E+10 | 12036.45 | 27-NOV-03:02 | -15.9 |
December | 0.626740E+10 | 12308.59 | 31-DEC-20:41 | -24.3 |
Annual Sum or Average | 0.261571E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.892464E+10 | 12476.72 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.536680E+10 | 14018.74 | 09-JAN-05:21 | -27.2 |
February | 0.241741E+10 | 13257.79 | 05-FEB-02:52 | -20.0 |
March | 0.137888E+10 | 13961.17 | 06-MAR-05:11 | -17.8 |
April | 0.240823E+09 | 11952.59 | 29-APR-04:02 | -7.8 |
May | 0.194129E+09 | 12389.18 | 01-MAY-04:01 | -0.6 |
June | 1759954.61 | 4717.22 | 16-JUN-06:03 | 2.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 772900.64 | 2302.24 | 18-AUG-05:13 | 7.40 |
September | 42367521.57 | 11011.98 | 19-SEP-05:11 | 2.20 |
October | 0.262022E+09 | 12292.38 | 10-OCT-04:01 | -5.2 |
November | 0.150147E+10 | 13615.45 | 27-NOV-03:02 | -15.9 |
December | 0.370236E+10 | 13959.17 | 31-DEC-20:41 | -24.3 |
Annual Sum or Average | 0.151088E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.536680E+10 | 14018.74 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.655401E+10 | 18798.51 | 09-JAN-05:21 | -27.2 |
February | 0.283276E+10 | 17857.90 | 05-FEB-02:52 | -20.0 |
March | 0.186980E+10 | 18761.75 | 06-MAR-05:11 | -17.8 |
April | 0.448851E+09 | 16080.92 | 29-APR-04:02 | -7.8 |
May | 0.394521E+09 | 16619.49 | 08-MAY-04:01 | -2.3 |
June | 9221090.21 | 8188.08 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 3252182.24 | 7677.87 | 18-AUG-06:03 | 8.17 |
September | 63202595.71 | 14784.29 | 19-SEP-05:11 | 2.20 |
October | 0.322783E+09 | 16632.23 | 10-OCT-04:01 | -5.2 |
November | 0.174739E+10 | 18315.44 | 27-NOV-03:02 | -15.9 |
December | 0.434372E+10 | 18795.45 | 31-DEC-06:41 | -27.9 |
Annual Sum or Average | 0.185895E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.9 | |
Maximum of Months | 0.655401E+10 | 18798.51 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.568259E+10 | 15735.45 | 09-JAN-05:21 | -27.2 |
February | 0.259462E+10 | 14836.28 | 05-FEB-09:32 | -19.8 |
March | 0.157383E+10 | 15732.20 | 06-MAR-05:11 | -17.8 |
April | 0.323819E+09 | 12965.57 | 01-APR-05:11 | 5.60 |
May | 0.255612E+09 | 13801.03 | 08-MAY-04:01 | -2.3 |
June | 6937811.79 | 5248.10 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 2983951.60 | 4988.86 | 18-AUG-06:03 | 8.17 |
September | 54779439.81 | 12411.78 | 19-SEP-05:11 | 2.20 |
October | 0.314705E+09 | 13811.46 | 10-OCT-04:01 | -5.2 |
November | 0.160039E+10 | 15301.08 | 27-NOV-03:02 | -15.9 |
December | 0.391422E+10 | 15691.56 | 31-DEC-06:41 | -27.9 |
Annual Sum or Average | 0.163245E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.9 | |
Maximum of Months | 0.568259E+10 | 15735.45 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.613214E+10 | 9211.63 | 11-JAN-05:11 | -30.2 |
February | 0.303036E+10 | 8845.12 | 05-FEB-22:42 | -11.6 |
March | 0.161935E+10 | 9010.57 | 06-MAR-05:01 | -18.4 |
April | 0.260835E+09 | 7847.27 | 29-APR-05:01 | -7.7 |
May | 0.134970E+09 | 7989.80 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 3399360.41 | 6231.92 | 20-SEP-06:03 | 3.48 |
October | 56471380.54 | 7601.51 | 10-OCT-05:01 | -6.1 |
November | 0.919647E+09 | 8839.62 | 27-NOV-05:01 | -15.4 |
December | 0.319726E+10 | 9061.36 | 31-DEC-23:51 | -23.3 |
Annual Sum or Average | 0.153544E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.2 | |
Maximum of Months | 0.613214E+10 | 9211.63 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.354064E+10 | 10982.68 | 11-JAN-05:11 | -30.2 |
February | 0.154529E+10 | 10395.02 | 04-FEB-05:11 | -20.2 |
March | 0.706500E+09 | 10729.52 | 06-MAR-05:01 | -18.4 |
April | 86646623.88 | 9304.90 | 29-APR-05:01 | -7.7 |
May | 53613619.94 | 9395.78 | 01-MAY-05:01 | -0.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 1216761.24 | 3261.77 | 20-SEP-06:03 | 3.48 |
October | 21152225.09 | 8942.07 | 10-OCT-05:01 | -6.1 |
November | 0.498375E+09 | 10508.93 | 27-NOV-05:01 | -15.4 |
December | 0.180504E+10 | 10760.65 | 31-DEC-23:51 | -23.3 |
Annual Sum or Average | 0.825849E+10 | |||
Minimum of Months | 0.00 | 0.00 | -30.2 | |
Maximum of Months | 0.354064E+10 | 10982.68 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.837124E+10 | 18430.33 | 09-JAN-08:00 | -27.2 |
February | 0.440857E+10 | 16882.05 | 01-FEB-07:10 | -24.9 |
March | 0.332654E+10 | 16426.70 | 06-MAR-08:00 | -18.3 |
April | 0.175889E+10 | 13390.41 | 28-APR-06:10 | -5.2 |
May | 0.148381E+10 | 13127.51 | 08-MAY-06:50 | -2.3 |
June | 0.258720E+09 | 11373.53 | 16-JUN-07:00 | 2.20 |
July | 22499758.31 | 7172.33 | 05-JUL-06:05 | 9.40 |
August | 0.146080E+09 | 11000.07 | 18-AUG-06:03 | 8.17 |
September | 0.494844E+09 | 11485.64 | 19-SEP-06:03 | 2.20 |
October | 0.889655E+09 | 13569.06 | 10-OCT-06:10 | -6.1 |
November | 0.240788E+10 | 15280.65 | 27-NOV-07:50 | -13.0 |
December | 0.517431E+10 | 17896.44 | 29-DEC-08:00 | -27.8 |
Annual Sum or Average | 0.287430E+11 | |||
Minimum of Months | 22499758.31 | 7172.33 | -27.8 | |
Maximum of Months | 0.837124E+10 | 18430.33 | 9.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.379832E+10 | 11920.12 | 11-JAN-05:11 | -30.2 |
February | 0.161566E+10 | 11268.79 | 04-FEB-05:11 | -20.2 |
March | 0.825256E+09 | 11642.61 | 06-MAR-05:01 | -18.4 |
April | 0.115241E+09 | 9939.79 | 29-APR-05:01 | -7.7 |
May | 65217929.83 | 10223.71 | 08-MAY-05:01 | -2.8 |
June | 290778.49 | 1938.52 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 1509986.24 | 3485.61 | 19-SEP-06:03 | 2.20 |
October | 28514083.57 | 9743.46 | 10-OCT-05:01 | -6.1 |
November | 0.507794E+09 | 11409.18 | 27-NOV-05:01 | -15.4 |
December | 0.191932E+10 | 11675.39 | 31-DEC-23:51 | -23.3 |
Annual Sum or Average | 0.887713E+10 | |||
Minimum of Months | 0.00 | 0.00 | -30.2 | |
Maximum of Months | 0.379832E+10 | 11920.12 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.583437E+10 | 10310.80 | 09-JAN-02:31 | -27.2 |
February | 0.251006E+10 | 9865.21 | 05-FEB-22:42 | -11.6 |
March | 0.110964E+10 | 10407.14 | 06-MAR-05:11 | -17.8 |
April | 0.105570E+09 | 8671.77 | 29-APR-05:01 | -7.7 |
May | 0.101767E+09 | 9024.47 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 7400719.44 | 7693.27 | 19-SEP-06:03 | 2.20 |
October | 0.112593E+09 | 8945.76 | 10-OCT-04:01 | -5.2 |
November | 0.112264E+10 | 10294.89 | 27-NOV-05:11 | -15.3 |
December | 0.341864E+10 | 10171.02 | 31-DEC-23:51 | -23.3 |
Annual Sum or Average | 0.143227E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.583437E+10 | 10407.14 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.350835E+10 | 12799.77 | 09-JAN-05:11 | -27.2 |
February | 0.140523E+10 | 12054.54 | 04-FEB-05:11 | -20.2 |
March | 0.615865E+09 | 12876.06 | 06-MAR-05:11 | -17.8 |
April | 53400278.73 | 10666.22 | 29-APR-05:01 | -7.7 |
May | 61035998.91 | 10747.30 | 01-MAY-05:01 | -0.5 |
June | 30579.83 | 203.87 | 16-JUN-06:03 | 2.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 5492960.93 | 5061.56 | 19-SEP-06:03 | 2.20 |
October | 61004349.42 | 10534.16 | 10-OCT-05:01 | -6.1 |
November | 0.691054E+09 | 12725.43 | 27-NOV-05:11 | -15.3 |
December | 0.205747E+10 | 12541.25 | 31-DEC-07:51 | -27.8 |
Annual Sum or Average | 0.845892E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.8 | |
Maximum of Months | 0.350835E+10 | 12876.06 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.396851E+10 | 16524.62 | 09-JAN-05:11 | -27.2 |
February | 0.144827E+10 | 15673.52 | 04-FEB-05:11 | -20.2 |
March | 0.756816E+09 | 16627.29 | 06-MAR-05:11 | -17.8 |
April | 96922882.90 | 13897.81 | 29-APR-05:01 | -7.7 |
May | 0.118222E+09 | 14068.37 | 09-MAY-05:01 | -2.0 |
June | 420369.94 | 2802.47 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 58990.60 | 393.27 | 18-AUG-06:03 | 8.17 |
September | 6547090.74 | 7780.60 | 19-SEP-06:03 | 2.20 |
October | 69934328.93 | 13928.04 | 10-OCT-05:01 | -6.1 |
November | 0.733297E+09 | 16465.19 | 27-NOV-05:11 | -15.3 |
December | 0.218415E+10 | 16284.39 | 31-DEC-07:51 | -27.8 |
Annual Sum or Average | 0.938315E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.8 | |
Maximum of Months | 0.396851E+10 | 16627.29 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367633E+10 | 12951.97 | 09-JAN-05:11 | -27.2 |
February | 0.146136E+10 | 12203.56 | 04-FEB-05:11 | -20.2 |
March | 0.704502E+09 | 13073.46 | 06-MAR-05:11 | -17.8 |
April | 76763522.23 | 10588.29 | 29-APR-05:01 | -7.7 |
May | 76794802.97 | 10644.25 | 08-MAY-05:01 | -2.8 |
June | 564449.29 | 3318.84 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 322000.90 | 2146.67 | 18-AUG-06:03 | 8.17 |
September | 6882414.76 | 5093.06 | 19-SEP-06:03 | 2.20 |
October | 74480890.35 | 10573.97 | 10-OCT-05:01 | -6.1 |
November | 0.701148E+09 | 12917.38 | 27-NOV-05:11 | -15.3 |
December | 0.214434E+10 | 12734.54 | 31-DEC-07:51 | -27.8 |
Annual Sum or Average | 0.892349E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.8 | |
Maximum of Months | 0.367633E+10 | 13073.46 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.108438E+10 | 1592.13 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.868045E+09 | 1592.13 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.956936E+09 | 1592.13 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.813328E+09 | 1388.60 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.842719E+09 | 1111.04 | 03-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.817051E+09 | 833.48 | 16-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.782598E+09 | 907.52 | 07-JUL-07:19 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.877824E+09 | 907.52 | 17-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.835039E+09 | 1388.60 | 11-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.931978E+09 | 1592.13 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.101926E+10 | 1592.13 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.106152E+10 | 1592.13 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.108907E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.782598E+09 | 833.48 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.108438E+10 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.659201E+09 | 1007.95 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.536812E+09 | 879.10 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.597408E+09 | 1007.95 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.511838E+09 | 703.38 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.535194E+09 | 574.53 | 03-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.522617E+09 | 480.79 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.497007E+09 | 527.66 | 03-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.558892E+09 | 574.53 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.524559E+09 | 703.38 | 13-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.573432E+09 | 1007.95 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.624129E+09 | 1007.95 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.644036E+09 | 1007.95 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.678513E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.497007E+09 | 480.79 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.659201E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101516E+10 | 1592.13 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.827016E+09 | 1314.57 | 02-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.941731E+09 | 1592.13 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.813872E+09 | 1388.60 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.848449E+09 | 1111.04 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.827517E+09 | 833.48 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.789124E+09 | 907.52 | 07-JUL-07:19 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.885217E+09 | 907.52 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.829513E+09 | 1388.60 | 11-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.894370E+09 | 1592.13 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.953303E+09 | 1592.13 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.983070E+09 | 1592.13 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.106083E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.789124E+09 | 833.48 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.101516E+10 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.667090E+09 | 1007.89 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.536478E+09 | 1007.89 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.602996E+09 | 1007.89 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.517023E+09 | 879.04 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.535456E+09 | 703.34 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.519300E+09 | 527.63 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.497931E+09 | 574.49 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.558675E+09 | 703.34 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.528698E+09 | 879.04 | 11-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.582783E+09 | 1007.89 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.621366E+09 | 1007.89 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.643276E+09 | 1007.89 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.681107E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.497931E+09 | 527.63 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.667090E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.107792E+10 | 1592.13 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.864088E+09 | 1388.60 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.953925E+09 | 1592.13 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.811756E+09 | 1185.08 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.842133E+09 | 1111.04 | 03-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.816295E+09 | 833.48 | 16-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.781952E+09 | 907.52 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.877201E+09 | 907.52 | 17-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.833387E+09 | 1388.60 | 11-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.927647E+09 | 1592.13 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.101347E+10 | 1592.13 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.105435E+10 | 1592.13 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.108541E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.781952E+09 | 833.48 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.107792E+10 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.656076E+09 | 1007.95 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.535198E+09 | 879.10 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.596449E+09 | 1007.95 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.511053E+09 | 703.38 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.534612E+09 | 574.53 | 03-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.521807E+09 | 480.79 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.496481E+09 | 527.66 | 07-JUL-07:19 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.558210E+09 | 527.66 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.523517E+09 | 703.38 | 13-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.572276E+09 | 1007.95 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.622446E+09 | 1007.95 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.640897E+09 | 1007.95 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.676902E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.496481E+09 | 480.79 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.656076E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101338E+10 | 1592.13 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.825739E+09 | 1314.57 | 02-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.939930E+09 | 1592.13 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.812037E+09 | 1185.08 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.847428E+09 | 1111.04 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.826294E+09 | 833.48 | 16-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.788082E+09 | 907.52 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.883957E+09 | 907.52 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.828032E+09 | 1111.04 | 11-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.892746E+09 | 1592.13 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.950993E+09 | 1592.13 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.979024E+09 | 1592.13 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.105876E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.788082E+09 | 833.48 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.101338E+10 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.664796E+09 | 1007.89 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.535184E+09 | 1007.89 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.601282E+09 | 1007.89 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.516027E+09 | 879.04 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.534664E+09 | 703.34 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.518792E+09 | 527.63 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.497457E+09 | 574.49 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.557878E+09 | 703.34 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.527477E+09 | 879.04 | 11-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.580459E+09 | 1007.89 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.618930E+09 | 1007.89 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.641274E+09 | 1007.89 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.679422E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.497457E+09 | 527.63 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.664796E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.108433E+10 | 1592.13 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.868045E+09 | 1592.13 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.956936E+09 | 1592.13 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.813328E+09 | 1388.60 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.842719E+09 | 1111.04 | 03-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.817051E+09 | 833.48 | 16-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.782598E+09 | 907.52 | 07-JUL-07:19 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.877824E+09 | 907.52 | 17-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.835039E+09 | 1388.60 | 11-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.931978E+09 | 1592.13 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.101926E+10 | 1592.13 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.106152E+10 | 1592.13 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.108906E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.782598E+09 | 833.48 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.108433E+10 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.659201E+09 | 1007.95 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.536812E+09 | 879.10 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.597408E+09 | 1007.95 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.511838E+09 | 703.38 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.535194E+09 | 574.53 | 03-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.522617E+09 | 480.79 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.496990E+09 | 527.66 | 03-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.558892E+09 | 574.53 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.524559E+09 | 703.38 | 13-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.573432E+09 | 1007.95 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.624129E+09 | 1007.95 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.644036E+09 | 1007.95 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.678511E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.496990E+09 | 480.79 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.659201E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101516E+10 | 1592.13 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.827016E+09 | 1314.57 | 02-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.941731E+09 | 1592.13 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.813872E+09 | 1388.60 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.848449E+09 | 1111.04 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.827517E+09 | 833.48 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.789080E+09 | 907.52 | 07-JUL-07:19 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.885217E+09 | 907.52 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.829513E+09 | 1388.60 | 11-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.894370E+09 | 1592.13 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.953303E+09 | 1592.13 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.983070E+09 | 1592.13 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.106083E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.789080E+09 | 833.48 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.101516E+10 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.667090E+09 | 1007.89 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.536478E+09 | 1007.89 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.602996E+09 | 1007.89 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.517023E+09 | 879.04 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.535456E+09 | 703.34 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.519300E+09 | 527.63 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.497931E+09 | 574.49 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.558675E+09 | 703.34 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.528698E+09 | 879.04 | 11-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.582755E+09 | 1007.89 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.621366E+09 | 1007.89 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.643276E+09 | 1007.89 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.681104E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.497931E+09 | 527.63 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.667090E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.108438E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173036E+10 |
February | 0.901968E+09 | 0.868045E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129610E+10 |
March | 0.107774E+10 | 0.956936E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120887E+10 |
April | 0.956342E+09 | 0.813328E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857789E+09 |
May | 0.103597E+10 | 0.842719E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2239081.47 | 0.882341E+09 |
June | 0.103308E+10 | 0.817051E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11744489.69 | 0.466601E+09 |
July | 0.959235E+09 | 0.782598E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40335949.53 | 0.316435E+09 |
August | 0.107774E+10 | 0.877824E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34203881.81 | 0.340142E+09 |
September | 0.956342E+09 | 0.835039E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21446708.71 | 0.585663E+09 |
October | 0.994195E+09 | 0.931978E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 912096.62 | 0.806412E+09 |
November | 0.984487E+09 | 0.101926E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115637E+10 |
December | 0.959235E+09 | 0.106152E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150448E+10 |
Annual Sum or Average | 0.119305E+11 | 0.108907E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110882E+09 | 0.111516E+11 |
Minimum of Months | 0.901968E+09 | 0.782598E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316435E+09 |
Maximum of Months | 0.107774E+10 | 0.108438E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40335949.53 | 0.173036E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.659201E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115973E+10 |
February | 0.571020E+09 | 0.536812E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.880904E+09 |
March | 0.682301E+09 | 0.597408E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820354E+09 |
April | 0.605444E+09 | 0.511838E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589696E+09 |
May | 0.655854E+09 | 0.535194E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1593354.34 | 0.589836E+09 |
June | 0.654023E+09 | 0.522617E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7948169.76 | 0.315059E+09 |
July | 0.607275E+09 | 0.497007E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26292081.36 | 0.216660E+09 |
August | 0.682301E+09 | 0.558892E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22710196.21 | 0.230025E+09 |
September | 0.605444E+09 | 0.524559E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13800759.63 | 0.400182E+09 |
October | 0.629407E+09 | 0.573432E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161191.69 | 0.554630E+09 |
November | 0.623262E+09 | 0.624129E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776652E+09 |
December | 0.607275E+09 | 0.644036E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100701E+10 |
Annual Sum or Average | 0.755301E+10 | 0.678513E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72505752.99 | 0.754073E+10 |
Minimum of Months | 0.571020E+09 | 0.497007E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216660E+09 |
Maximum of Months | 0.682301E+09 | 0.659201E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26292081.36 | 0.115973E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.101516E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178264E+10 |
February | 0.901968E+09 | 0.827016E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139769E+10 |
March | 0.107774E+10 | 0.941731E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127451E+10 |
April | 0.956342E+09 | 0.813872E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905098E+09 |
May | 0.103597E+10 | 0.848449E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2233788.57 | 0.897331E+09 |
June | 0.103308E+10 | 0.827517E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11682813.10 | 0.466478E+09 |
July | 0.959235E+09 | 0.789124E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38619429.82 | 0.319120E+09 |
August | 0.107774E+10 | 0.885217E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33516128.94 | 0.348787E+09 |
September | 0.956342E+09 | 0.829513E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18969926.98 | 0.615283E+09 |
October | 0.994195E+09 | 0.894370E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 128287.78 | 0.889664E+09 |
November | 0.984487E+09 | 0.953303E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122512E+10 |
December | 0.959235E+09 | 0.983070E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156739E+10 |
Annual Sum or Average | 0.119305E+11 | 0.106083E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105150E+09 | 0.116891E+11 |
Minimum of Months | 0.901968E+09 | 0.789124E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319120E+09 |
Maximum of Months | 0.107774E+10 | 0.101516E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38619429.82 | 0.178264E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.667090E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115759E+10 |
February | 0.570983E+09 | 0.536478E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881202E+09 |
March | 0.682256E+09 | 0.602996E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821535E+09 |
April | 0.605404E+09 | 0.517023E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592043E+09 |
May | 0.655811E+09 | 0.535456E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1502000.38 | 0.605415E+09 |
June | 0.653980E+09 | 0.519300E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7764513.12 | 0.316206E+09 |
July | 0.607235E+09 | 0.497931E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26841195.01 | 0.218994E+09 |
August | 0.682256E+09 | 0.558675E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22931164.80 | 0.230000E+09 |
September | 0.605404E+09 | 0.528698E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14750912.18 | 0.396379E+09 |
October | 0.629366E+09 | 0.582783E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 285350.25 | 0.550416E+09 |
November | 0.623221E+09 | 0.621366E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779829E+09 |
December | 0.607235E+09 | 0.643276E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100788E+10 |
Annual Sum or Average | 0.755252E+10 | 0.681107E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74075135.73 | 0.755748E+10 |
Minimum of Months | 0.570983E+09 | 0.497931E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218994E+09 |
Maximum of Months | 0.682256E+09 | 0.667090E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26841195.01 | 0.115759E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.107792E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.948266E+09 |
February | 0.901968E+09 | 0.864088E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725707E+09 |
March | 0.107774E+10 | 0.953925E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662665E+09 |
April | 0.956342E+09 | 0.811756E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460628E+09 |
May | 0.103597E+10 | 0.842133E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1390046.24 | 0.475928E+09 |
June | 0.103308E+10 | 0.816295E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6770304.92 | 0.248259E+09 |
July | 0.959235E+09 | 0.781952E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24198986.47 | 0.167810E+09 |
August | 0.107774E+10 | 0.877201E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19223477.14 | 0.185947E+09 |
September | 0.956342E+09 | 0.833387E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12984946.26 | 0.333508E+09 |
October | 0.994195E+09 | 0.927647E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 352161.63 | 0.478421E+09 |
November | 0.984487E+09 | 0.101347E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669879E+09 |
December | 0.959235E+09 | 0.105435E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845634E+09 |
Annual Sum or Average | 0.119305E+11 | 0.108541E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64919922.67 | 0.620265E+10 |
Minimum of Months | 0.901968E+09 | 0.781952E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167810E+09 |
Maximum of Months | 0.107774E+10 | 0.107792E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24198986.47 | 0.948266E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.656076E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637681E+09 |
February | 0.571020E+09 | 0.535198E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496878E+09 |
March | 0.682301E+09 | 0.596449E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454343E+09 |
April | 0.605444E+09 | 0.511053E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325995E+09 |
May | 0.655854E+09 | 0.534612E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 851592.39 | 0.329763E+09 |
June | 0.654023E+09 | 0.521807E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4317592.15 | 0.175395E+09 |
July | 0.607275E+09 | 0.496481E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14343140.17 | 0.122233E+09 |
August | 0.682301E+09 | 0.558210E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12188522.73 | 0.131813E+09 |
September | 0.605444E+09 | 0.523517E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7463442.75 | 0.234581E+09 |
October | 0.629407E+09 | 0.572276E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49675.16 | 0.335720E+09 |
November | 0.623262E+09 | 0.622446E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454583E+09 |
December | 0.607275E+09 | 0.640897E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569350E+09 |
Annual Sum or Average | 0.755301E+10 | 0.676902E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39213965.35 | 0.426833E+10 |
Minimum of Months | 0.571020E+09 | 0.496481E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122233E+09 |
Maximum of Months | 0.682301E+09 | 0.656076E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14343140.17 | 0.637681E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.101338E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779553E+10 |
February | 0.901968E+09 | 0.825739E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583308E+10 |
March | 0.107774E+10 | 0.939930E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559533E+10 |
April | 0.956342E+09 | 0.812037E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359696E+10 |
May | 0.103597E+10 | 0.847428E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15684539.55 | 0.335469E+10 |
June | 0.103308E+10 | 0.826294E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223572E+09 | 0.160665E+10 |
July | 0.959235E+09 | 0.788082E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544582E+09 | 0.725606E+09 |
August | 0.107774E+10 | 0.883957E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391877E+09 | 0.127703E+10 |
September | 0.956342E+09 | 0.828032E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69139743.70 | 0.224507E+10 |
October | 0.994195E+09 | 0.892746E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 907633.83 | 0.344567E+10 |
November | 0.984487E+09 | 0.950993E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481562E+10 |
December | 0.959235E+09 | 0.979024E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628351E+10 |
Annual Sum or Average | 0.119305E+11 | 0.105876E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124576E+10 | 0.465747E+11 |
Minimum of Months | 0.901968E+09 | 0.788082E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725606E+09 |
Maximum of Months | 0.107774E+10 | 0.101338E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544582E+09 | 0.779553E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.664796E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635807E+09 |
February | 0.570983E+09 | 0.535184E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495897E+09 |
March | 0.682256E+09 | 0.601282E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453908E+09 |
April | 0.605404E+09 | 0.516027E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325757E+09 |
May | 0.655811E+09 | 0.534664E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 834895.14 | 0.339666E+09 |
June | 0.653980E+09 | 0.518792E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4148009.20 | 0.175750E+09 |
July | 0.607235E+09 | 0.497457E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14505273.87 | 0.123904E+09 |
August | 0.682256E+09 | 0.557878E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12156476.04 | 0.131636E+09 |
September | 0.605404E+09 | 0.527477E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7768845.36 | 0.233438E+09 |
October | 0.629366E+09 | 0.580459E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54301.81 | 0.332584E+09 |
November | 0.623221E+09 | 0.618930E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455149E+09 |
December | 0.607235E+09 | 0.641274E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568688E+09 |
Annual Sum or Average | 0.755252E+10 | 0.679422E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39467801.44 | 0.427218E+10 |
Minimum of Months | 0.570983E+09 | 0.497457E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123904E+09 |
Maximum of Months | 0.682256E+09 | 0.664796E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14505273.87 | 0.635807E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.108433E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147641E+10 |
February | 0.901968E+09 | 0.868045E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113970E+10 |
March | 0.107774E+10 | 0.956936E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105609E+10 |
April | 0.956342E+09 | 0.813328E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759599E+09 |
May | 0.103597E+10 | 0.842719E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1914995.27 | 0.775639E+09 |
June | 0.103308E+10 | 0.817051E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9975311.60 | 0.403467E+09 |
July | 0.959235E+09 | 0.782598E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34667714.65 | 0.273679E+09 |
August | 0.107774E+10 | 0.877824E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28701744.33 | 0.297157E+09 |
September | 0.956342E+09 | 0.835039E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18244250.90 | 0.521952E+09 |
October | 0.994195E+09 | 0.931978E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 475784.41 | 0.734539E+09 |
November | 0.984487E+09 | 0.101926E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102787E+10 |
December | 0.959235E+09 | 0.106152E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129880E+10 |
Annual Sum or Average | 0.119305E+11 | 0.108906E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93979801.16 | 0.976490E+10 |
Minimum of Months | 0.901968E+09 | 0.782598E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273679E+09 |
Maximum of Months | 0.107774E+10 | 0.108433E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34667714.65 | 0.147641E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.659201E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989546E+09 |
February | 0.421807E+09 | 0.536812E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774075E+09 |
March | 0.502994E+09 | 0.597408E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715236E+09 |
April | 0.447140E+09 | 0.511838E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518658E+09 |
May | 0.484071E+09 | 0.535194E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1379215.56 | 0.516387E+09 |
June | 0.482240E+09 | 0.522617E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6778774.19 | 0.271180E+09 |
July | 0.448971E+09 | 0.496990E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22614293.90 | 0.186423E+09 |
August | 0.502994E+09 | 0.558892E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19079848.62 | 0.199756E+09 |
September | 0.447140E+09 | 0.524559E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11833444.47 | 0.352992E+09 |
October | 0.465148E+09 | 0.573432E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115225.79 | 0.500822E+09 |
November | 0.460569E+09 | 0.624129E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689133E+09 |
December | 0.448971E+09 | 0.644036E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871685E+09 |
Annual Sum or Average | 0.557719E+10 | 0.678511E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61800802.55 | 0.658589E+10 |
Minimum of Months | 0.421807E+09 | 0.496990E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186423E+09 |
Maximum of Months | 0.502994E+09 | 0.659201E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22614293.90 | 0.989546E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.101516E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153089E+10 |
February | 0.901968E+09 | 0.827016E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122909E+10 |
March | 0.107774E+10 | 0.941731E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111256E+10 |
April | 0.956342E+09 | 0.813872E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.797726E+09 |
May | 0.103597E+10 | 0.848449E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1902153.66 | 0.788126E+09 |
June | 0.103308E+10 | 0.827517E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9879504.93 | 0.404561E+09 |
July | 0.959235E+09 | 0.789080E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32455286.49 | 0.277224E+09 |
August | 0.107774E+10 | 0.885217E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28009700.45 | 0.304716E+09 |
September | 0.956342E+09 | 0.829513E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15969061.39 | 0.544492E+09 |
October | 0.994195E+09 | 0.894370E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 110637.52 | 0.799746E+09 |
November | 0.984487E+09 | 0.953303E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108968E+10 |
December | 0.959235E+09 | 0.983070E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137012E+10 |
Annual Sum or Average | 0.119305E+11 | 0.106083E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88326344.44 | 0.102489E+11 |
Minimum of Months | 0.901968E+09 | 0.789080E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277224E+09 |
Maximum of Months | 0.107774E+10 | 0.101516E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32455286.49 | 0.153089E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.667090E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986899E+09 |
February | 0.570983E+09 | 0.536478E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773772E+09 |
March | 0.682256E+09 | 0.602996E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716048E+09 |
April | 0.605404E+09 | 0.517023E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522097E+09 |
May | 0.655811E+09 | 0.535456E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1266948.01 | 0.530887E+09 |
June | 0.653980E+09 | 0.519300E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6471827.87 | 0.274221E+09 |
July | 0.607235E+09 | 0.497931E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22470199.63 | 0.190017E+09 |
August | 0.682256E+09 | 0.558675E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18992626.73 | 0.201290E+09 |
September | 0.605404E+09 | 0.528698E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12223508.98 | 0.351893E+09 |
October | 0.629366E+09 | 0.582755E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 130835.79 | 0.498112E+09 |
November | 0.623221E+09 | 0.621366E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691255E+09 |
December | 0.607235E+09 | 0.643276E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.870817E+09 |
Annual Sum or Average | 0.755252E+10 | 0.681104E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61555947.02 | 0.660731E+10 |
Minimum of Months | 0.570983E+09 | 0.497931E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190017E+09 |
Maximum of Months | 0.682256E+09 | 0.667090E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22470199.63 | 0.986899E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202501E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161817E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148642E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107430E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1861457.95 | 0.108010E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10025595.13 | 0.552334E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38866405.20 | 0.375764E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32602615.84 | 0.413579E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21030786.52 | 0.746174E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41665.46 | 0.107674E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148642E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185217E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104429E+09 | 0.137872E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375764E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38866405.20 | 0.202501E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250710E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197882E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183970E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133446E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2490110.55 | 0.134963E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13067230.21 | 0.702098E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50706175.33 | 0.476906E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42234589.05 | 0.521286E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27521957.72 | 0.924481E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99174.75 | 0.129710E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179159E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224821E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136119E+09 | 0.169714E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476906E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50706175.33 | 0.250710E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258249E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199008E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187238E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135471E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1483512.00 | 0.138225E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10739619.59 | 0.732146E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41329604.58 | 0.491767E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38524062.51 | 0.529716E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22422839.55 | 0.921537E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127345E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176609E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226155E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114500E+09 | 0.171582E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491767E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41329604.58 | 0.258249E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3205.26 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1761.31 | 08-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 1592.13 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2173.74 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 1388.60 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1501.38 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 1111.04 | 03-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.91 | 20-MAY-17:02 | 2775.30 | 22-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 833.48 | 16-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.87 | 29-JUN-15:00 | 1209.15 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 07-JUL-07:19 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 337.59 | 30-JUL-12:00 | 720.74 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 907.52 | 17-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 412.39 | 06-AUG-17:36 | 894.54 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 1388.60 | 11-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 467.44 | 03-SEP-12:51 | 1550.34 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.87 | 15-OCT-13:52 | 1379.89 | 30-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1782.14 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2430.50 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 720.74 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 467.44 | 3205.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1007.95 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2136.19 | 05-JAN-22:01 |
February | 827.22 | 01-FEB-10:09 | 879.10 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1173.43 | 08-FEB-22:02 |
March | 827.22 | 01-MAR-10:09 | 1007.95 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1446.77 | 02-MAR-23:00 |
April | 827.22 | 03-APR-09:09 | 703.38 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 998.43 | 27-APR-02:00 |
May | 827.22 | 01-MAY-09:09 | 574.53 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.12 | 20-MAY-17:02 | 1850.08 | 22-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 480.79 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.58 | 29-JUN-15:00 | 829.00 | 04-JUN-14:00 |
July | 827.22 | 03-JUL-09:09 | 527.66 | 03-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.47 | 30-JUL-12:00 | 478.31 | 05-JUL-01:00 |
August | 827.22 | 01-AUG-09:09 | 574.53 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.16 | 06-AUG-17:38 | 583.35 | 22-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 703.38 | 13-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.25 | 03-SEP-13:06 | 1021.12 | 12-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 1007.95 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.87 | 15-OCT-14:10 | 920.54 | 30-OCT-21:05 |
November | 827.22 | 01-NOV-09:09 | 1007.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1186.89 | 29-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 1007.95 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1620.32 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.31 | |||||
Maximum of Months | 827.22 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 315.25 | 2136.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3206.28 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 1314.57 | 02-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1765.52 | 08-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 1592.13 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2237.93 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 1388.60 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1511.58 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 1111.04 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.20 | 20-MAY-17:02 | 2775.23 | 22-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 833.48 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.87 | 29-JUN-15:00 | 1215.77 | 04-JUN-14:00 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 07-JUL-07:19 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 336.30 | 30-JUL-14:00 | 726.55 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 907.52 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 425.33 | 06-AUG-17:36 | 897.57 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 1388.60 | 11-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 427.87 | 03-SEP-13:04 | 1549.49 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 | 18-OCT-14:00 | 1400.28 | 30-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1782.48 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2440.52 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 726.55 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 427.87 | 3206.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1007.89 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2135.68 | 05-JAN-22:01 |
February | 827.17 | 01-FEB-10:09 | 1007.89 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1174.59 | 08-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 1007.89 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1468.08 | 02-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 879.04 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 997.99 | 27-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 703.34 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.90 | 20-MAY-17:02 | 1850.03 | 22-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 527.63 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.58 | 29-JUN-15:00 | 805.11 | 14-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 574.49 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.38 | 30-JUL-12:00 | 495.74 | 05-JUL-01:00 |
August | 827.17 | 01-AUG-09:09 | 703.34 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.93 | 06-AUG-11:52 | 596.01 | 22-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 879.04 | 11-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.95 | 03-SEP-12:51 | 1014.65 | 12-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 1007.89 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.99 | 15-OCT-12:50 | 922.80 | 30-OCT-21:05 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1186.57 | 29-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1620.32 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 527.63 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.74 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 345.95 | 2135.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1708.13 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 1388.60 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 938.13 | 08-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 1592.13 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1192.65 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 1185.08 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 824.49 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 1111.04 | 03-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.31 | 20-MAY-17:02 | 1650.04 | 22-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 833.48 | 16-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.15 | 29-JUN-15:00 | 688.28 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.64 | 30-JUL-12:00 | 408.09 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 907.52 | 17-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.94 | 06-AUG-17:50 | 516.12 | 23-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1388.60 | 11-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 283.68 | 03-SEP-13:00 | 954.81 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.26 | 15-OCT-13:52 | 778.85 | 30-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 952.86 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1366.64 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.09 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 283.68 | 1708.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1007.95 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1138.48 | 05-JAN-22:01 |
February | 827.22 | 01-FEB-10:09 | 879.10 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 625.22 | 08-FEB-22:02 |
March | 827.22 | 01-MAR-10:09 | 1007.95 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 804.57 | 02-MAR-23:00 |
April | 827.22 | 03-APR-09:09 | 703.38 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 572.21 | 27-APR-02:00 |
May | 827.22 | 01-MAY-09:09 | 574.53 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.89 | 20-MAY-17:02 | 1102.87 | 22-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 480.79 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.10 | 29-JUN-15:00 | 462.62 | 14-JUN-02:00 |
July | 827.22 | 03-JUL-09:09 | 527.66 | 07-JUL-07:19 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.66 | 30-JUL-12:00 | 280.30 | 05-JUL-01:00 |
August | 827.22 | 01-AUG-09:09 | 527.66 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.72 | 06-AUG-17:24 | 355.38 | 23-AUG-03:00 |
September | 827.22 | 01-SEP-09:09 | 703.38 | 13-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.83 | 03-SEP-12:51 | 634.99 | 12-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 1007.95 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 18-OCT-14:00 | 530.92 | 30-OCT-22:00 |
November | 827.22 | 01-NOV-09:09 | 1007.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 634.76 | 29-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 1007.95 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 903.82 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.30 | |||||
Maximum of Months | 827.22 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 169.83 | 1138.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 39043.66 | 10-JAN-17:01 |
February | 1306.65 | 01-FEB-10:09 | 1314.57 | 02-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 37139.25 | 01-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1592.13 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 31503.02 | 06-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 1185.08 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 19476.54 | 28-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 1111.04 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2521.94 | 19-MAY-16:10 | 17562.23 | 08-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 833.48 | 16-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4922.98 | 28-JUN-16:10 | 13961.87 | 16-JUN-07:00 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8591.97 | 17-JUL-16:05 | 8944.44 | 05-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 907.52 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5681.13 | 10-AUG-17:00 | 10978.84 | 28-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 1111.04 | 11-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.98 | 01-SEP-16:10 | 13963.53 | 19-SEP-06:20 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.92 | 18-OCT-14:00 | 20505.34 | 10-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 26938.60 | 27-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 37483.82 | 29-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8944.44 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8591.97 | 39043.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1007.89 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1138.28 | 05-JAN-22:01 |
February | 827.17 | 01-FEB-10:09 | 1007.89 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 627.24 | 17-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 1007.89 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 823.72 | 02-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 879.04 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 567.56 | 27-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 703.34 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.66 | 20-MAY-17:02 | 1103.98 | 22-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 527.63 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.10 | 29-JUN-15:00 | 468.23 | 14-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 574.49 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.22 | 30-JUL-12:00 | 286.54 | 05-JUL-01:00 |
August | 827.17 | 01-AUG-09:09 | 703.34 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.92 | 06-AUG-12:10 | 356.03 | 23-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 879.04 | 11-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.03 | 03-SEP-12:51 | 634.69 | 12-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 1007.89 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.46 | 18-OCT-14:00 | 534.18 | 30-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 634.62 | 29-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 909.27 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 527.63 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.54 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 185.03 | 1138.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2673.66 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1470.56 | 08-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 1592.13 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1892.36 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 1388.60 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1334.10 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 1111.04 | 03-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.76 | 20-MAY-17:02 | 2498.19 | 22-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 833.48 | 16-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.01 | 29-JUN-15:00 | 1077.46 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 07-JUL-07:19 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.40 | 30-JUL-12:00 | 640.60 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 907.52 | 17-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.52 | 06-AUG-17:26 | 797.92 | 23-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1388.60 | 11-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.58 | 03-SEP-13:00 | 1418.74 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.17 | 15-OCT-13:52 | 1188.36 | 30-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1490.47 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2020.07 | 01-DEC-05:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 640.60 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 405.58 | 2673.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1007.95 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1781.93 | 05-JAN-22:01 |
February | 805.43 | 01-FEB-08:09 | 879.10 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 979.79 | 08-FEB-22:02 |
March | 805.43 | 01-MAR-08:09 | 1007.95 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1257.57 | 02-MAR-23:00 |
April | 805.43 | 03-APR-07:10 | 703.38 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 885.66 | 27-APR-02:00 |
May | 805.43 | 01-MAY-07:10 | 574.53 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.29 | 20-MAY-17:02 | 1653.48 | 22-MAY-04:00 |
June | 805.43 | 01-JUN-07:10 | 480.79 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.67 | 29-JUN-15:00 | 707.38 | 14-JUN-02:00 |
July | 805.43 | 03-JUL-07:10 | 527.66 | 03-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.68 | 30-JUL-14:00 | 425.09 | 05-JUL-01:00 |
August | 805.43 | 01-AUG-07:10 | 574.53 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.66 | 06-AUG-17:26 | 527.89 | 23-AUG-03:00 |
September | 805.43 | 01-SEP-07:10 | 703.38 | 13-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.27 | 03-SEP-12:51 | 934.16 | 12-SEP-03:00 |
October | 805.43 | 02-OCT-07:10 | 1007.95 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.73 | 15-OCT-14:20 | 791.29 | 30-OCT-22:00 |
November | 805.43 | 01-NOV-07:10 | 1007.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 992.72 | 29-NOV-22:02 |
December | 805.43 | 01-DEC-08:09 | 1007.95 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1378.66 | 01-DEC-05:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.09 | |||||
Maximum of Months | 805.43 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 269.27 | 1781.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2674.45 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 1314.57 | 02-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1505.06 | 19-FEB-13:00 |
March | 1306.65 | 01-MAR-10:09 | 1592.13 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1944.41 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 1388.60 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1342.31 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 1111.04 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.84 | 20-MAY-17:02 | 2507.15 | 22-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 833.48 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.00 | 29-JUN-15:00 | 1071.89 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 07-JUL-07:19 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.17 | 30-JUL-13:53 | 645.46 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 907.52 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.62 | 06-AUG-17:24 | 807.18 | 23-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1388.60 | 11-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.82 | 03-SEP-12:55 | 1419.65 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 18-OCT-14:00 | 1243.89 | 30-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1490.83 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2055.13 | 01-DEC-05:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 645.46 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 373.82 | 2674.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1007.89 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1781.57 | 05-JAN-22:01 |
February | 827.17 | 01-FEB-10:09 | 1007.89 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 980.71 | 08-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 1007.89 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1275.29 | 02-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 879.04 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 887.34 | 27-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 703.34 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.33 | 20-MAY-17:02 | 1649.71 | 22-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 527.63 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.67 | 29-JUN-15:00 | 718.02 | 14-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 574.49 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.92 | 30-JUL-11:53 | 439.71 | 05-JUL-01:00 |
August | 827.17 | 01-AUG-09:09 | 703.34 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.41 | 06-AUG-12:10 | 533.41 | 23-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 879.04 | 11-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.57 | 03-SEP-12:52 | 929.75 | 12-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 1007.89 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.29 | 15-OCT-13:12 | 797.81 | 30-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 992.51 | 29-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1377.43 | 01-DEC-05:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 527.63 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.71 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 295.57 | 1781.57 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3384.75 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2143.56 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2679.82 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1891.62 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.13 | 20-MAY-17:02 | 3730.87 | 22-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.48 | 29-JUN-15:00 | 1526.11 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.63 | 30-JUL-11:53 | 898.55 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.51 | 06-AUG-17:50 | 1153.67 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.89 | 03-SEP-13:00 | 2076.26 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 | 18-OCT-14:00 | 1729.54 | 30-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2001.97 | 26-NOV-19:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3081.19 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 898.55 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.89 | 3730.87 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4307.60 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2623.56 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3371.90 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2394.78 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.09 | 20-MAY-17:02 | 4626.82 | 22-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.98 | 29-JUN-15:00 | 1932.38 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.24 | 30-JUL-12:00 | 1124.51 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540.71 | 06-AUG-17:50 | 1445.36 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 659.26 | 03-SEP-13:00 | 2565.55 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.81 | 18-OCT-14:00 | 2120.25 | 30-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2422.81 | 26-NOV-20:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3704.68 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1124.51 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 659.26 | 4626.82 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4671.49 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2586.24 | 08-FEB-22:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3423.04 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2326.69 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.51 | 20-MAY-17:02 | 4399.43 | 22-MAY-04:40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.90 | 29-JUN-15:00 | 1986.13 | 04-JUN-14:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.40 | 30-JUL-14:10 | 1099.15 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.27 | 06-AUG-18:00 | 1420.77 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.95 | 03-SEP-12:51 | 2397.98 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2127.03 | 30-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2562.33 | 29-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3447.13 | 31-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1099.15 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.95 | 4671.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 10041.56 | 19-JAN-16:40 | 6035.01 | 7552.50 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16890.73 | 28-FEB-08:05 | 48280.06 | 60419.97 | 145481.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19898.15 | 01-MAR-08:03 | 60350.08 | 75524.96 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19717.52 | 07-APR-16:00 | 6035.01 | 7552.50 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43676.91 | 22-MAY-05:01 | 4446.85 | 5874.01 | 34926.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41268.76 | 26-JUN-06:02 | 6352.64 | 12587.66 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 44745.80 | 18-JUL-05:12 | 2541.06 | 3356.58 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 42974.01 | 14-AUG-06:02 | 7623.17 | 15105.19 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42917.68 | 11-SEP-05:12 | 2541.06 | 3356.58 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31759.78 | 19-OCT-06:02 | 7623.17 | 15105.19 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19177.94 | 06-NOV-08:03 | 42245.05 | 52867.47 | 127296.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15334.01 | 08-DEC-08:20 | 12070.02 | 15104.99 | 36370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 10041.56 | 2541.06 | 3356.58 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44745.80 | 60350.08 | 75524.96 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 425.36 | 14-JAN-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.82 |
February | 1985.17 | 26-FEB-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.05 |
March | 2503.67 | 22-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.90 |
April | 6025.81 | 25-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.42 |
May | 9352.24 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.97 | 0.00 |
June | 10686.89 | 23-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.83 | 0.00 |
July | 13292.07 | 17-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.79 | 0.00 |
August | 12059.82 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.63 | 0.00 |
September | 9014.34 | 01-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.93 | 0.00 |
October | 5690.93 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.43 |
November | 1347.13 | 03-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.04 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2213.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13292.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.97 | 2213.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3690.42 | 28-JAN-03:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2105.53 |
February | 4523.25 | 01-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.85 |
March | 4696.46 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1313.79 |
April | 3193.28 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.59 |
May | 3271.92 | 19-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.38 | 0.00 |
June | 4532.45 | 23-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.19 | 0.00 |
July | 6367.06 | 17-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.32 | 0.00 |
August | 6362.65 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.55 | 0.00 |
September | 5565.82 | 05-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 |
October | 1784.82 | 18-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 |
November | 2081.55 | 28-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2309.78 |
December | 3599.20 | 23-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2009.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1784.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6367.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.38 | 2309.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3616.05 | 28-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1271.34 |
February | 3987.93 | 04-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1164.63 |
March | 4366.02 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1054.34 |
April | 3799.58 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.59 |
May | 3468.48 | 19-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.57 | 0.00 |
June | 4770.63 | 23-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.31 | 0.00 |
July | 6639.01 | 17-JUL-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.58 | 0.00 |
August | 6332.41 | 07-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.63 | 0.00 |
September | 5843.48 | 05-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 |
October | 2805.35 | 18-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 |
November | 2401.20 | 02-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.38 |
December | 3565.85 | 30-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 732.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2401.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6639.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.57 | 1271.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6324.32 | 13-JAN-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9161.65 | 28-FEB-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9424.37 | 01-MAR-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13205.07 | 25-APR-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16269.56 | 30-MAY-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29032.49 | 26-JUN-06:02 | 6352.64 | 12587.66 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34102.29 | 18-JUL-05:12 | 2541.06 | 3356.58 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31968.39 | 07-AUG-06:03 | 3811.58 | 7552.60 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32499.93 | 05-SEP-06:03 | 5082.11 | 10070.13 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14137.28 | 19-OCT-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10194.22 | 03-NOV-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6962.81 | 07-DEC-16:20 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6324.32 | 2541.06 | 3356.58 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34102.29 | 6352.64 | 12587.66 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6205.33 | 13-JAN-16:50 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7703.77 | 28-FEB-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7815.99 | 29-MAR-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14265.83 | 25-APR-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17680.68 | 19-MAY-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19970.71 | 23-JUN-14:00 | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30895.15 | 17-JUL-06:03 | 3811.58 | 7552.60 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26846.71 | 07-AUG-06:03 | 3811.58 | 7552.60 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33355.85 | 05-SEP-06:03 | 5082.11 | 10070.13 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13803.86 | 18-OCT-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8231.09 | 03-NOV-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6706.80 | 07-DEC-16:20 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6205.33 | 3811.58 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33355.85 | 6198.29 | 10070.13 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 950.55 | 14-JAN-17:03 | 200.88 | 265.35 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.34 |
February | 1379.93 | 27-FEB-16:10 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.16 |
March | 1437.73 | 29-MAR-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.43 |
April | 3452.23 | 07-APR-14:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.82 |
May | 5517.75 | 19-MAY-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 99.40 | 0.00 |
June | 6667.51 | 29-JUN-15:20 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 153.21 | 0.00 |
July | 12638.28 | 16-JUL-18:41 | 0.00 | 295.33 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 123.39 | 0.00 |
August | 12339.84 | 06-AUG-16:11 | 468.72 | 295.33 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 352.98 | 0.00 |
September | 11298.06 | 04-SEP-15:41 | 468.72 | 295.33 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 149.69 | 0.00 |
October | 2753.43 | 19-OCT-14:40 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.91 |
November | 1338.16 | 03-NOV-16:00 | 1272.23 | 1111.04 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.92 |
December | 1059.77 | 06-DEC-16:20 | 1272.23 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 950.55 | 0.00 | 265.35 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12638.28 | 1272.23 | 1592.13 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 352.98 | 298.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1146.22 | 20-JAN-10:25 | 1654.44 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.75 |
February | 1752.93 | 27-FEB-10:40 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.01 |
March | 3769.16 | 23-MAR-10:10 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.12 |
April | 6431.20 | 25-APR-09:20 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.64 |
May | 8034.19 | 19-MAY-08:50 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.35 |
June | 11947.44 | 25-JUN-08:22 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.93 |
July | 15586.44 | 16-JUL-09:22 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.84 |
August | 15864.10 | 06-AUG-09:32 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 30.21 | 0.00 |
September | 11697.95 | 04-SEP-08:22 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.49 |
October | 4693.66 | 18-OCT-09:40 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.49 |
November | 1755.61 | 03-NOV-09:50 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.14 |
December | 1222.89 | 20-DEC-10:20 | 1654.44 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1146.22 | 211.95 | 133.55 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15864.10 | 1654.44 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 30.21 | 318.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5368.88 | 19-JAN-13:40 | 2544.47 | 1518.89 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.34 |
February | 11797.13 | 26-FEB-14:02 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.44 |
March | 11421.24 | 01-MAR-14:00 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.75 |
April | 11254.18 | 25-APR-13:30 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.63 |
May | 10991.17 | 19-MAY-13:40 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 47.58 | 0.00 |
June | 10924.90 | 23-JUN-13:10 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 31.66 | 0.00 |
July | 19613.94 | 09-JUL-15:12 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 84.16 | 0.00 |
August | 20744.83 | 06-AUG-13:32 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 267.31 | 0.00 |
September | 21881.87 | 03-SEP-13:01 | 468.72 | 295.33 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 325.50 | 0.00 |
October | 21247.79 | 15-OCT-14:42 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.27 |
November | 11733.43 | 03-NOV-13:30 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.10 |
December | 5738.16 | 07-DEC-13:40 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5368.88 | 267.84 | 168.76 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21881.87 | 2544.47 | 1518.89 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 325.50 | 554.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1660.95 | 13-JAN-15:50 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.25 |
February | 4259.08 | 28-FEB-16:40 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.44 |
March | 5395.05 | 28-MAR-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.39 |
April | 10470.25 | 22-APR-17:06 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.45 |
May | 16454.29 | 28-MAY-17:12 | 0.00 | 160.25 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.73 |
June | 17078.90 | 24-JUN-17:42 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.29 |
July | 18497.86 | 16-JUL-17:21 | 0.00 | 213.67 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 53.04 | 0.00 |
August | 17646.08 | 06-AUG-16:11 | 296.72 | 186.96 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 201.71 | 0.00 |
September | 17790.39 | 04-SEP-16:21 | 296.72 | 186.96 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 68.72 | 0.00 |
October | 8462.89 | 15-OCT-16:42 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.55 |
November | 3281.68 | 03-NOV-15:40 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.92 |
December | 1805.07 | 06-DEC-15:50 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1660.95 | 0.00 | 106.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18497.86 | 805.38 | 480.76 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 201.71 | 329.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 942.92 | 14-JAN-17:03 | 200.88 | 265.35 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.96 |
February | 1192.42 | 27-FEB-16:20 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.46 |
March | 1234.45 | 29-MAR-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.29 |
April | 1497.34 | 07-APR-14:40 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.40 |
May | 3333.82 | 19-MAY-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 53.58 | 0.00 |
June | 4861.70 | 23-JUN-13:50 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.11 | 0.00 |
July | 6743.85 | 17-JUL-06:03 | 803.52 | 759.46 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.37 |
August | 7818.94 | 06-AUG-16:41 | 669.60 | 421.90 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 194.42 | 0.00 |
September | 5525.82 | 05-SEP-06:03 | 1071.35 | 2122.87 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.79 |
October | 2392.92 | 19-OCT-14:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.01 |
November | 1346.88 | 08-NOV-14:10 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.04 |
December | 1063.74 | 06-DEC-16:20 | 1272.23 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 942.92 | 200.88 | 265.35 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7818.94 | 1306.65 | 2122.87 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 194.42 | 149.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 983.91 | 20-JAN-09:55 | 1610.86 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.79 |
February | 1427.33 | 27-FEB-10:40 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.79 |
March | 2171.32 | 23-MAR-10:30 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.03 |
April | 4023.65 | 25-APR-09:30 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.58 |
May | 5267.67 | 19-MAY-09:20 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.31 |
June | 9185.73 | 30-JUN-06:02 | 847.82 | 801.33 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.12 |
July | 12340.51 | 16-JUL-09:42 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.37 |
August | 13781.69 | 06-AUG-09:21 | 381.52 | 240.39 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | 0.00 |
September | 9030.07 | 04-SEP-08:22 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.81 |
October | 3908.52 | 18-OCT-09:50 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.64 |
November | 1740.76 | 03-NOV-09:15 | 1654.44 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.48 |
December | 1080.47 | 07-DEC-10:50 | 1654.44 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 983.91 | 211.95 | 133.55 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13781.69 | 1654.44 | 961.59 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | 179.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2492.05 | 14-JAN-12:30 | 137.54 | 126.57 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.82 |
February | 13949.47 | 26-FEB-13:12 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.50 |
March | 7017.27 | 01-MAR-13:20 | 2544.47 | 1518.89 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1881.73 |
April | 6519.90 | 25-APR-12:08 | 5088.93 | 3037.79 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 887.36 |
May | 7815.45 | 19-MAY-14:00 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 326.84 | 0.00 |
June | 11280.44 | 29-JUN-12:00 | 687.71 | 759.45 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4624.04 | 0.00 |
July | 14178.82 | 17-JUL-12:00 | 687.71 | 759.45 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6892.30 | 0.00 |
August | 16724.23 | 06-AUG-16:41 | 669.60 | 421.90 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 169.06 | 0.00 |
September | 17025.61 | 03-SEP-13:22 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 172.65 | 0.00 |
October | 15572.39 | 15-OCT-14:12 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.06 |
November | 8520.49 | 03-NOV-12:05 | 5088.93 | 3037.79 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1194.30 |
December | 3299.33 | 06-DEC-14:40 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2492.05 | 137.54 | 126.57 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17025.61 | 5088.93 | 3037.79 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 6892.30 | 1881.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1290.04 | 13-JAN-15:50 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.63 |
February | 3136.51 | 28-FEB-16:50 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.76 |
March | 3345.09 | 28-MAR-17:30 | 84.78 | 160.26 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.56 |
April | 5821.35 | 16-APR-17:12 | 0.00 | 133.54 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.65 |
May | 13694.90 | 28-MAY-18:21 | 0.00 | 213.67 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.57 |
June | 13508.39 | 18-JUN-18:12 | 0.00 | 160.25 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 |
July | 14401.54 | 16-JUL-18:21 | 0.00 | 186.96 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 33.55 | 0.00 |
August | 14932.55 | 06-AUG-16:41 | 423.88 | 267.08 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 95.79 | 0.00 |
September | 14008.66 | 04-SEP-17:01 | 0.00 | 186.96 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 34.62 | 0.00 |
October | 5686.66 | 18-OCT-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.20 | 0.00 |
November | 2802.51 | 03-NOV-15:50 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.37 |
December | 1450.98 | 06-DEC-15:50 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1290.04 | 0.00 | 133.54 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14932.55 | 805.38 | 480.76 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 95.79 | 172.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1002.01 | 13-JAN-17:00 | 1272.23 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.54 |
February | 1389.28 | 27-FEB-13:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.51 |
March | 1438.78 | 29-MAR-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.93 |
April | 3424.12 | 07-APR-14:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.04 |
May | 5014.48 | 19-MAY-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 83.32 | 0.00 |
June | 7024.47 | 30-JUN-06:02 | 1339.19 | 1265.76 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 |
July | 10139.23 | 16-JUL-18:21 | 0.00 | 295.33 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 97.53 | 0.00 |
August | 11048.52 | 06-AUG-16:41 | 669.60 | 421.90 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 279.80 | 0.00 |
September | 8664.83 | 05-SEP-06:03 | 1071.35 | 2122.87 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.07 |
October | 3041.56 | 19-OCT-14:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.63 |
November | 1437.17 | 03-NOV-13:30 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.00 |
December | 1098.33 | 06-DEC-16:50 | 1272.23 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1002.01 | 0.00 | 295.33 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11048.52 | 1339.19 | 2122.87 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 279.80 | 252.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1254.28 | 20-JAN-10:00 | 1610.86 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.83 |
February | 2559.84 | 28-FEB-09:55 | 1610.86 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.48 |
March | 4409.16 | 23-MAR-10:10 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.08 |
April | 7006.53 | 25-APR-08:50 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.63 |
May | 8236.03 | 19-MAY-08:50 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.45 |
June | 14985.46 | 11-JUN-09:22 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.31 |
July | 15468.18 | 02-JUL-09:02 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.81 |
August | 17644.52 | 06-AUG-08:41 | 381.52 | 240.39 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.43 |
September | 12260.33 | 04-SEP-08:22 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.51 |
October | 5182.23 | 18-OCT-09:00 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.25 |
November | 2438.08 | 03-NOV-10:10 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.60 |
December | 1331.75 | 20-DEC-10:00 | 1610.86 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1254.28 | 211.95 | 133.55 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.51 | |
Maximum of Months | 17644.52 | 1610.86 | 961.59 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6277.42 | 19-JAN-13:30 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.06 |
February | 19141.98 | 26-FEB-13:12 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.50 |
March | 12147.95 | 01-MAR-13:40 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.21 |
April | 12869.34 | 16-APR-13:53 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.95 |
May | 10477.19 | 19-MAY-13:30 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 35.87 | 0.00 |
June | 11982.94 | 11-JUN-13:23 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.37 |
July | 17083.48 | 16-JUL-13:42 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 72.45 | 0.00 |
August | 19406.47 | 06-AUG-10:41 | 535.68 | 337.52 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 73.19 | 0.00 |
September | 19924.10 | 03-SEP-13:22 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 252.81 | 0.00 |
October | 18793.59 | 15-OCT-13:32 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.11 |
November | 12327.12 | 03-NOV-13:20 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.16 |
December | 6692.10 | 12-DEC-12:30 | 687.71 | 759.45 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6277.42 | 267.84 | 168.76 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19924.10 | 1306.65 | 759.45 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 252.81 | 528.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1629.99 | 13-JAN-15:50 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.84 |
February | 4473.87 | 28-FEB-16:40 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.99 |
March | 5405.34 | 28-MAR-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.72 |
April | 15405.18 | 16-APR-16:32 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.99 |
May | 15863.70 | 28-MAY-17:12 | 0.00 | 160.25 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.62 |
June | 16294.96 | 18-JUN-18:12 | 0.00 | 160.25 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.43 |
July | 17098.11 | 16-JUL-17:01 | 0.00 | 186.96 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 53.77 | 0.00 |
August | 17978.48 | 06-AUG-16:41 | 423.88 | 267.08 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 129.30 | 0.00 |
September | 16528.43 | 04-SEP-16:21 | 296.72 | 186.96 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 58.47 | 0.00 |
October | 6862.48 | 18-OCT-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.22 | 0.00 |
November | 3570.31 | 03-NOV-15:40 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.35 |
December | 1772.68 | 06-DEC-15:50 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1629.99 | 0.00 | 133.54 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17978.48 | 805.38 | 480.76 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 129.30 | 274.62 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.209379E+12 | 276810.72 | 09-JAN-07:10 | 0.891108E+11 | 156778.00 | 10-JAN-21:40 |
February | 0.146662E+12 | 236803.35 | 06-FEB-07:10 | 0.535996E+11 | 131647.67 | 01-FEB-07:19 |
March | 0.142292E+12 | 237228.45 | 06-MAR-07:10 | 0.388621E+11 | 111529.72 | 04-MAR-07:19 |
April | 0.111857E+12 | 109045.51 | 20-APR-07:10 | 0.191126E+11 | 58142.90 | 29-APR-06:30 |
May | 0.119311E+12 | 151048.27 | 08-MAY-06:10 | 0.165502E+11 | 48898.90 | 08-MAY-06:19 |
June | 0.132576E+12 | 159270.96 | 29-JUN-15:09 | 0.117324E+11 | 20098.58 | 16-JUN-06:00 |
July | 0.150374E+12 | 193815.52 | 17-JUL-15:30 | 0.111920E+11 | 10079.57 | 05-JUL-11:09 |
August | 0.151359E+12 | 177326.13 | 07-AUG-15:30 | 0.115927E+11 | 10004.65 | 01-AUG-11:00 |
September | 0.122378E+12 | 168341.89 | 07-SEP-14:00 | 0.118766E+11 | 26958.36 | 19-SEP-06:40 |
October | 0.117459E+12 | 163725.54 | 10-OCT-06:10 | 0.165868E+11 | 61134.08 | 10-OCT-06:30 |
November | 0.135080E+12 | 231808.99 | 27-NOV-07:10 | 0.307085E+11 | 89821.18 | 27-NOV-08:09 |
December | 0.173651E+12 | 242848.58 | 26-DEC-07:10 | 0.626433E+11 | 143622.95 | 29-DEC-08:09 |
Annual Sum or Average | 0.171238E+13 | 0.373568E+12 | ||||
Minimum of Months | 0.111857E+12 | 109045.51 | 0.111920E+11 | 10004.65 | ||
Maximum of Months | 0.209379E+12 | 276810.72 | 0.891108E+11 | 156778.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.319152E+11 | 0.126369E+11 | 0.593559E+11 | 0.144055E+10 | 0.642414E+10 | 12379742.02 | 0.975944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.279364E+11 | 0.102867E+11 | 0.537310E+11 | 0.130205E+10 | 0.510361E+10 | 11196021.66 | 0.481590E+11 | 0.132171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.326269E+11 | 0.981037E+10 | 0.617796E+11 | 0.150715E+10 | 0.584310E+10 | 12675672.10 | 0.307124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.288078E+11 | 0.789912E+10 | 0.572952E+11 | 0.138494E+10 | 0.566527E+10 | 11960507.72 | 0.927743E+10 | 0.151557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.307768E+11 | 0.680545E+10 | 0.605677E+11 | 0.147205E+10 | 0.730767E+10 | 12527707.06 | 0.641652E+10 | 0.595236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.304417E+11 | 0.595010E+10 | 0.594895E+11 | 0.144924E+10 | 0.132006E+11 | 12231776.97 | 0.482312E+09 | 0.215501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.286508E+11 | 0.640391E+10 | 0.583622E+11 | 0.140718E+10 | 0.174719E+11 | 12256437.81 | 43461956.41 | 0.380228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.319756E+11 | 0.752542E+10 | 0.617796E+11 | 0.150655E+10 | 0.165924E+11 | 12675672.10 | 0.259845E+09 | 0.317072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.289929E+11 | 0.879659E+10 | 0.572729E+11 | 0.138471E+10 | 0.987276E+10 | 11960507.72 | 0.166362E+10 | 0.143825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.305897E+11 | 0.107285E+11 | 0.593671E+11 | 0.143866E+10 | 0.638985E+10 | 12379742.02 | 0.604753E+10 | 0.288493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.310396E+11 | 0.118243E+11 | 0.580818E+11 | 0.141319E+10 | 0.533225E+10 | 12059151.09 | 0.272468E+11 | 0.129752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.309329E+11 | 0.130444E+11 | 0.583511E+11 | 0.140996E+10 | 0.578806E+10 | 12256437.81 | 0.641119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364686E+12 | 0.111712E+12 | 0.705434E+12 | 0.171162E+11 | 0.104992E+12 | 0.146559E+09 | 0.292015E+12 | 0.116277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.279364E+11 | 0.595010E+10 | 0.537310E+11 | 0.130205E+10 | 0.510361E+10 | 11196021.66 | 43461956.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.326269E+11 | 0.130444E+11 | 0.617796E+11 | 0.150715E+10 | 0.174719E+11 | 12675672.10 | 0.975944E+11 | 0.380228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.765559E+11 | 0.00 | 0.125549E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.421467E+11 | 0.00 | 0.114529E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.258221E+11 | 0.00 | 0.130401E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.719330E+10 | 0.00 | 0.119193E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.435690E+10 | 0.00 | 0.121933E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.151572E+09 | 0.00 | 0.115808E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.111920E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1273833.16 | 0.00 | 0.115915E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.952405E+09 | 0.00 | 0.109242E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.505122E+10 | 0.00 | 0.115356E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.191201E+11 | 0.00 | 0.115884E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.505484E+11 | 0.00 | 0.120949E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.231900E+12 | 0.00 | 0.141668E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.109242E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.765559E+11 | 0.00 | 0.130401E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 38257.79 | 02-JAN-08:09 | 8596.48 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 1242.18 | 06-JAN-08:20 | 8787.44 | 09-JAN-07:10 | 6.85 | 04-JAN-06:10 | 225214.60 | 09-JAN-07:10 |
February | 35900.82 | 02-FEB-08:09 | 8596.48 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 1237.56 | 02-FEB-08:20 | 6582.30 | 28-FEB-16:30 | 6.85 | 01-FEB-17:10 | 187624.63 | 06-FEB-07:10 |
March | 38257.79 | 17-MAR-07:10 | 8596.48 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 1242.18 | 17-MAR-07:19 | 7234.03 | 06-MAR-06:10 | 6.85 | 01-MAR-07:10 | 196629.01 | 06-MAR-07:10 |
April | 35329.34 | 14-APR-07:10 | 8596.48 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 1236.44 | 14-APR-07:19 | 12736.26 | 25-APR-15:00 | 6.85 | 03-APR-05:10 | 74306.43 | 29-APR-05:10 |
May | 33157.35 | 03-MAY-07:10 | 8596.48 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 1232.20 | 03-MAY-07:19 | 21631.25 | 19-MAY-15:30 | 6.85 | 01-MAY-05:10 | 114090.38 | 08-MAY-06:10 |
June | 30683.64 | 16-JUN-07:10 | 8596.48 | 01-JUN-20:10 | 45864.70 | 01-JUN-07:10 | 1227.38 | 16-JUN-07:19 | 27772.80 | 29-JUN-15:09 | 6.85 | 18-JUN-16:00 | 23797.48 | 16-JUN-06:10 |
July | 31409.05 | 07-JUL-07:30 | 8596.48 | 01-JUL-20:30 | 45864.70 | 03-JUL-07:10 | 1228.79 | 07-JUL-07:40 | 37222.62 | 17-JUL-15:20 | 6.85 | 02-JUL-07:40 | 6257.41 | 05-JUL-06:19 |
August | 31889.32 | 17-AUG-07:10 | 8596.48 | 01-AUG-19:00 | 45864.70 | 01-AUG-07:10 | 1229.73 | 17-AUG-07:19 | 34499.07 | 07-AUG-15:30 | 6.85 | 05-AUG-16:10 | 21354.24 | 18-AUG-06:10 |
September | 34931.68 | 11-SEP-07:10 | 8596.48 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 1235.66 | 11-SEP-07:19 | 27115.82 | 01-SEP-15:50 | 6.85 | 03-SEP-11:39 | 54525.59 | 19-SEP-06:10 |
October | 38257.79 | 25-OCT-07:10 | 8596.48 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 1242.18 | 25-OCT-07:19 | 15497.00 | 18-OCT-15:00 | 6.85 | 05-OCT-05:10 | 116375.18 | 10-OCT-06:10 |
November | 38257.79 | 01-NOV-07:10 | 8596.48 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 1242.18 | 27-NOV-08:20 | 7665.65 | 03-NOV-15:30 | 6.85 | 06-NOV-13:09 | 182499.25 | 27-NOV-07:10 |
December | 38257.79 | 01-DEC-08:09 | 8596.48 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 1242.18 | 12-DEC-08:20 | 6823.92 | 26-DEC-07:10 | 6.85 | 01-DEC-08:09 | 193215.99 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 30683.64 | 8596.48 | 45864.70 | 1227.38 | 6582.30 | 6.85 | 6257.41 | |||||||
Maximum of Months | 38257.79 | 8596.48 | 45864.70 | 1242.18 | 37222.62 | 6.85 | 225214.60 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9233.77 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20431.97 | 06-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44049.59 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 58301.99 | 29-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83931.56 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 69424.70 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 70214.08 | 07-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32333.00 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4442.70 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83931.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 276810.72 | 09-JAN-07:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 8787.44 | 6.85 | 225214.60 | 0.00 | 0.00 |
February | 236803.35 | 06-FEB-07:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 6370.05 | 6.85 | 187624.63 | 0.00 | 0.00 |
March | 237228.45 | 06-MAR-07:10 | 12068.94 | 21098.80 | 0.00 | 353.77 | 7071.08 | 6.85 | 196629.01 | 0.00 | 0.00 |
April | 109045.51 | 20-APR-07:10 | 33157.35 | 45864.70 | 0.00 | 1189.68 | 3745.11 | 6.85 | 25081.82 | 0.00 | 0.00 |
May | 151048.27 | 08-MAY-06:10 | 10984.75 | 21098.80 | 0.00 | 353.47 | 4514.01 | 6.85 | 114090.38 | 0.00 | 0.00 |
June | 159270.96 | 29-JUN-15:09 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 27772.80 | 6.85 | 0.00 | 58095.80 | 0.00 |
July | 193815.52 | 17-JUL-15:30 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 36947.32 | 6.85 | 0.00 | 83465.84 | 0.00 |
August | 177326.13 | 07-AUG-15:30 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 34499.07 | 6.85 | 0.00 | 69424.70 | 0.00 |
September | 168341.89 | 07-SEP-14:00 | 30098.83 | 40588.47 | 0.00 | 1223.48 | 26210.17 | 6.85 | 0.00 | 70214.08 | 0.00 |
October | 163725.54 | 10-OCT-06:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 4541.69 | 6.85 | 116375.18 | 0.00 | 0.00 |
November | 231808.99 | 27-NOV-07:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 6501.08 | 6.85 | 182499.25 | 0.00 | 0.00 |
December | 242848.58 | 26-DEC-07:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 6823.92 | 6.85 | 193215.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 109045.51 | 10984.75 | 21098.80 | 0.00 | 353.47 | 3745.11 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 276810.72 | 33157.35 | 45864.70 | 8596.48 | 1224.26 | 36947.32 | 6.85 | 225214.60 | 83465.84 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 151900.12 | 10-JAN-21:00 | 0.00 | 12116.78 | 30-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 122754.74 | 01-FEB-07:30 | 0.00 | 12281.55 | 10-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 102875.33 | 04-MAR-07:19 | 0.00 | 12228.56 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 50870.93 | 29-APR-06:10 | 0.00 | 11422.45 | 04-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 39873.36 | 08-MAY-06:19 | 0.00 | 10350.46 | 02-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 11133.46 | 16-JUN-06:00 | 0.00 | 10217.78 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 10079.57 | 05-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 1091.57 | 18-AUG-06:10 | 0.00 | 10004.65 | 01-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 18489.78 | 19-SEP-06:19 | 0.00 | 10061.71 | 28-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 52190.03 | 10-OCT-06:30 | 0.00 | 10184.77 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 80309.03 | 27-NOV-08:09 | 0.00 | 10317.69 | 29-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 134753.84 | 29-DEC-07:00 | 0.00 | 11204.45 | 27-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10004.65 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 151900.12 | 0.00 | 12281.55 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 18.93 | 0.67 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
February | 0.17 | 19.36 | 0.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.40 | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Annual Sum or Average | 1.17 | 19.06 | 1.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 19.40 | 0.67 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 18.68 | 2.17 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
February | 0.33 | 18.10 | 0.17 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
March | 0.50 | 17.10 | 0.17 | 17.58 | 0.00 | 17.58 | 0.00 | 17.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 17.79 | 0.17 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 |
December | 0.50 | 18.52 | 0.33 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
Annual Sum or Average | 4.67 | 18.35 | 3.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 18.68 | 2.17 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 73.50 | 16.17 | 37.00 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 |
February | 24.17 | 16.08 | 9.67 | 16.57 | 0.00 | 16.57 | 0.00 | 16.57 |
March | 14.33 | 15.89 | 5.33 | 16.31 | 0.00 | 16.31 | 0.00 | 16.31 |
April | 0.17 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 |
May | 0.50 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.45 | 1.33 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.58 | 1.17 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.49 | 2.17 | 27.50 |
October | 0.33 | 16.80 | 0.00 | 16.80 | 0.00 | 16.80 | 0.00 | 16.80 |
November | 17.50 | 15.82 | 7.17 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 |
December | 47.00 | 15.68 | 20.33 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 |
Annual Sum or Average | 177.50 | 15.98 | 79.50 | 16.43 | 6.67 | 16.71 | 4.67 | 16.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.50 | 16.87 | 37.00 | 16.87 | 2.50 | 27.58 | 2.17 | 27.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.33 | 14.50 | 10.67 | 14.61 | 0.00 | 14.61 | 0.00 | 14.61 |
February | 17.67 | 14.96 | 3.17 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 |
March | 9.83 | 14.81 | 1.17 | 14.78 | 0.00 | 14.78 | 0.00 | 14.78 |
April | 0.17 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
May | 0.50 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.85 | 4.67 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.08 | 9.50 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.41 | 2.83 | 28.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.95 | 4.83 | 27.96 |
October | 0.50 | 16.19 | 0.00 | 16.19 | 0.00 | 16.19 | 0.00 | 16.19 |
November | 12.33 | 14.85 | 2.83 | 14.83 | 0.00 | 14.83 | 0.00 | 14.83 |
December | 33.67 | 14.66 | 7.33 | 14.62 | 0.00 | 14.62 | 0.00 | 14.62 |
Annual Sum or Average | 118.00 | 14.70 | 25.17 | 14.73 | 23.00 | 16.57 | 21.83 | 17.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 | 0.00 | 14.61 |
Maximum of Months | 43.33 | 16.79 | 10.67 | 16.79 | 10.00 | 28.41 | 9.50 | 28.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.50 | 14.79 | 9.17 | 15.03 | 0.00 | 15.03 | 0.00 | 15.03 |
February | 13.83 | 15.17 | 1.50 | 15.30 | 1.00 | 16.07 | 1.00 | 16.75 |
March | 8.67 | 14.82 | 1.00 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
April | 0.17 | 16.87 | 0.00 | 16.87 | 0.50 | 24.72 | 0.50 | 25.84 |
May | 0.50 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.54 | 2.33 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.93 | 6.33 | 27.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.11 | 3.67 | 28.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.28 | 5.50 | 28.33 |
October | 0.17 | 16.49 | 0.00 | 16.49 | 1.83 | 27.05 | 1.83 | 27.51 |
November | 7.50 | 15.02 | 1.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
December | 27.17 | 14.80 | 5.50 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
Annual Sum or Average | 94.50 | 14.89 | 18.17 | 14.99 | 23.50 | 17.24 | 21.17 | 18.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 0.00 | 14.79 |
Maximum of Months | 36.50 | 16.87 | 9.17 | 16.87 | 7.33 | 28.28 | 6.33 | 28.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.00 | 14.41 | 10.17 | 14.47 | 0.00 | 14.47 | 0.00 | 14.47 |
February | 17.00 | 14.78 | 3.00 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 |
March | 9.83 | 14.70 | 1.50 | 14.67 | 0.00 | 14.67 | 0.00 | 14.67 |
April | 0.17 | 16.87 | 0.00 | 16.87 | 1.00 | 26.32 | 0.50 | 26.81 |
May | 0.50 | 16.76 | 0.00 | 16.76 | 2.83 | 26.41 | 1.00 | 26.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.26 | 1.83 | 28.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.65 | 4.17 | 28.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.39 | 2.00 | 28.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.44 | 2.50 | 28.53 |
October | 0.67 | 15.90 | 0.00 | 15.90 | 0.17 | 18.21 | 0.17 | 19.75 |
November | 11.67 | 14.79 | 2.83 | 14.76 | 0.00 | 14.76 | 0.00 | 14.76 |
December | 36.00 | 14.65 | 9.50 | 14.60 | 0.00 | 14.60 | 0.00 | 14.60 |
Annual Sum or Average | 118.83 | 14.62 | 27.00 | 14.61 | 24.50 | 16.59 | 12.17 | 17.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.47 | 0.00 | 14.47 |
Maximum of Months | 43.00 | 16.87 | 10.17 | 16.87 | 8.67 | 28.65 | 4.17 | 28.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.33 | 17.61 | 37.50 | 18.08 | 0.00 | 18.08 | 0.00 | 18.08 |
February | 10.17 | 16.81 | 5.00 | 17.27 | 0.00 | 17.27 | 0.00 | 17.27 |
March | 5.50 | 17.19 | 2.67 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 18.75 | 0.83 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
December | 11.00 | 17.04 | 7.17 | 17.42 | 0.00 | 17.42 | 0.00 | 17.42 |
Annual Sum or Average | 82.33 | 17.43 | 53.17 | 17.91 | 0.00 | 17.91 | 0.00 | 17.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.33 | 18.75 | 37.50 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.17 | 15.06 | 4.67 | 15.16 | 0.00 | 15.16 | 0.00 | 15.16 |
February | 5.33 | 15.43 | 0.50 | 15.38 | 0.00 | 15.38 | 0.00 | 15.38 |
March | 2.50 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.68 | 1.67 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.79 | 7.50 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.01 | 2.67 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.66 | 4.50 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 16.72 | 0.00 | 16.72 | 0.00 | 16.72 | 0.00 | 16.72 |
December | 5.83 | 14.99 | 2.00 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
Annual Sum or Average | 34.17 | 15.12 | 7.17 | 15.14 | 16.83 | 18.80 | 16.33 | 20.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.17 | 16.72 | 4.67 | 16.72 | 7.67 | 28.01 | 7.50 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 93.67 | 16.48 | 83.50 | 16.56 | 0.00 | 16.56 | 0.00 | 16.56 |
February | 41.33 | 17.06 | 40.00 | 17.08 | 0.83 | 17.19 | 0.83 | 17.29 |
March | 38.33 | 18.39 | 37.17 | 18.43 | 0.00 | 18.43 | 0.00 | 18.43 |
April | 20.33 | 19.38 | 20.33 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
May | 14.33 | 19.32 | 14.33 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
June | 1.00 | 20.30 | 1.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 26.59 | 4.83 | 26.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.95 | 3.33 | 26.90 |
September | 1.50 | 20.15 | 1.50 | 20.15 | 6.67 | 25.57 | 5.50 | 26.49 |
October | 7.17 | 18.98 | 7.17 | 18.98 | 2.33 | 20.22 | 2.33 | 21.16 |
November | 26.33 | 18.35 | 26.00 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
December | 54.33 | 17.15 | 51.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
Annual Sum or Average | 298.33 | 17.52 | 282.00 | 17.58 | 18.50 | 17.88 | 16.83 | 18.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 0.00 | 16.56 |
Maximum of Months | 93.67 | 20.30 | 83.50 | 20.30 | 6.67 | 26.95 | 5.50 | 26.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.67 | 14.92 | 4.50 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
February | 5.83 | 15.39 | 1.00 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
March | 2.67 | 15.08 | 0.00 | 15.08 | 0.00 | 15.08 | 0.00 | 15.08 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.86 | 0.33 | 27.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.78 | 0.83 | 27.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.11 | 3.33 | 28.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.31 | 1.00 | 28.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.08 | 2.00 | 28.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.48 | 0.17 | 27.48 |
November | 0.33 | 16.70 | 0.00 | 16.70 | 0.00 | 16.70 | 0.00 | 16.70 |
December | 6.67 | 14.97 | 2.83 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
Annual Sum or Average | 35.17 | 15.04 | 8.33 | 15.01 | 16.50 | 18.60 | 7.67 | 19.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 19.67 | 16.70 | 4.50 | 16.70 | 6.83 | 28.31 | 3.33 | 28.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.83 | 16.51 | 21.83 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
February | 10.50 | 15.63 | 3.83 | 15.79 | 0.00 | 15.79 | 0.00 | 15.79 |
March | 6.17 | 16.37 | 2.00 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.45 | 0.00 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.38 | 0.83 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.36 | 1.17 | 27.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5.00 | 16.19 | 1.33 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
December | 11.83 | 15.75 | 5.17 | 16.01 | 0.00 | 16.01 | 0.00 | 16.01 |
Annual Sum or Average | 75.33 | 16.23 | 34.17 | 16.70 | 2.83 | 16.97 | 2.00 | 17.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.83 | 16.51 | 21.83 | 17.12 | 1.33 | 27.45 | 1.17 | 27.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.33 | 14.86 | 5.00 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
February | 7.83 | 15.18 | 1.00 | 15.14 | 0.00 | 15.14 | 0.00 | 15.14 |
March | 4.50 | 14.89 | 0.17 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.02 | 4.50 | 28.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.17 | 8.17 | 28.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.22 | 3.33 | 28.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.84 | 5.17 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.50 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 |
December | 10.17 | 14.90 | 2.83 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 |
Annual Sum or Average | 50.33 | 14.93 | 9.00 | 14.96 | 21.50 | 18.44 | 21.17 | 20.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.33 | 15.18 | 5.00 | 15.14 | 8.17 | 28.22 | 8.17 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.17 | 15.11 | 3.67 | 15.25 | 0.17 | 15.33 | 0.17 | 15.41 |
February | 4.83 | 15.56 | 0.50 | 15.49 | 1.33 | 17.98 | 1.33 | 19.65 |
March | 3.33 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.45 | 0.67 | 27.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.37 | 0.17 | 27.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.50 | 1.67 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.84 | 6.00 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.03 | 3.33 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.16 | 6.00 | 28.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.14 | 2.33 | 28.14 |
November | 2.00 | 15.24 | 0.00 | 15.24 | 0.50 | 17.65 | 0.50 | 19.25 |
December | 7.33 | 15.04 | 2.00 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
Annual Sum or Average | 37.67 | 15.15 | 6.17 | 15.21 | 23.83 | 19.70 | 22.17 | 21.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 | 0.00 | 15.02 |
Maximum of Months | 20.17 | 15.56 | 3.67 | 15.49 | 6.83 | 28.16 | 6.00 | 28.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.33 | 14.86 | 5.67 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
February | 8.33 | 15.17 | 1.50 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
March | 5.17 | 14.89 | 0.67 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.86 | 0.50 | 27.86 |
May | 0.17 | 17.24 | 0.00 | 17.24 | 3.00 | 27.47 | 1.17 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.18 | 1.33 | 28.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.48 | 4.67 | 28.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.24 | 2.00 | 28.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.36 | 2.33 | 28.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.59 | 0.33 | 27.59 |
November | 3.33 | 14.96 | 0.17 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
December | 11.00 | 14.87 | 3.17 | 14.77 | 0.00 | 14.77 | 0.00 | 14.77 |
Annual Sum or Average | 53.33 | 14.93 | 11.17 | 14.94 | 24.00 | 18.56 | 12.33 | 19.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.77 | 0.00 | 14.77 |
Maximum of Months | 25.33 | 17.24 | 5.67 | 17.24 | 8.50 | 28.48 | 4.67 | 28.46 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.35 | 102.50 | 22.07 | 102.50 | 21.87 |
February | 452.33 | 23.08 | 20.67 | 22.97 | 20.67 | 22.87 |
March | 505.00 | 23.57 | 6.67 | 23.54 | 6.67 | 23.51 |
April | 363.50 | 23.89 | 0.83 | 23.89 | 0.00 | 23.89 |
May | 208.00 | 23.89 | 71.17 | 24.34 | 0.00 | 24.34 |
June | 6.50 | 23.93 | 225.67 | 24.63 | 0.00 | 24.63 |
July | 0.83 | 26.77 | 361.00 | 24.57 | 0.83 | 24.58 |
August | 0.00 | 0.00 | 264.83 | 24.77 | 0.00 | 24.77 |
September | 33.50 | 24.01 | 183.50 | 24.69 | 0.00 | 24.69 |
October | 217.50 | 23.98 | 26.17 | 24.18 | 0.00 | 24.18 |
November | 409.83 | 23.70 | 1.50 | 23.69 | 1.50 | 23.68 |
December | 497.00 | 23.02 | 32.83 | 22.88 | 32.83 | 22.75 |
Annual Sum or Average | 3196.00 | 23.33 | 1297.33 | 23.60 | 165.00 | 23.50 |
Minimum of Months | 0.00 | 0.00 | 0.83 | 22.07 | 0.00 | 21.87 |
Maximum of Months | 505.00 | 26.77 | 361.00 | 24.77 | 102.50 | 24.77 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.93 | 325.50 | 20.77 | 325.50 | 20.70 |
February | 454.00 | 21.61 | 150.33 | 21.37 | 150.33 | 21.23 |
March | 514.00 | 22.33 | 60.33 | 22.13 | 60.33 | 21.98 |
April | 468.50 | 23.10 | 0.00 | 23.10 | 0.00 | 23.10 |
May | 347.00 | 23.26 | 46.50 | 23.44 | 5.00 | 23.40 |
June | 89.67 | 23.60 | 144.67 | 24.11 | 0.00 | 24.11 |
July | 22.67 | 23.74 | 289.83 | 24.39 | 0.00 | 24.39 |
August | 33.50 | 23.60 | 168.33 | 24.50 | 0.00 | 24.50 |
September | 191.83 | 23.51 | 133.50 | 23.96 | 1.67 | 23.96 |
October | 451.33 | 23.30 | 2.00 | 23.29 | 2.00 | 23.28 |
November | 489.00 | 22.39 | 59.17 | 22.21 | 59.17 | 22.06 |
December | 497.00 | 21.32 | 215.67 | 21.05 | 215.67 | 20.90 |
Annual Sum or Average | 4060.50 | 22.34 | 1595.83 | 22.38 | 819.67 | 22.15 |
Minimum of Months | 22.67 | 20.93 | 0.00 | 20.77 | 0.00 | 20.70 |
Maximum of Months | 514.00 | 23.74 | 325.50 | 24.50 | 325.50 | 24.50 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.38 | 438.83 | 20.31 | 438.83 | 20.28 |
February | 454.00 | 20.93 | 300.00 | 20.73 | 300.00 | 20.65 |
March | 514.00 | 21.54 | 176.50 | 21.23 | 176.50 | 21.05 |
April | 472.50 | 22.42 | 57.17 | 22.21 | 57.17 | 22.05 |
May | 377.83 | 22.83 | 56.67 | 22.75 | 34.67 | 22.59 |
June | 149.33 | 23.38 | 134.33 | 23.83 | 0.00 | 23.83 |
July | 50.00 | 23.48 | 258.33 | 24.23 | 0.00 | 24.23 |
August | 90.00 | 23.45 | 147.17 | 24.11 | 0.00 | 24.11 |
September | 261.33 | 23.01 | 108.83 | 23.44 | 4.00 | 23.44 |
October | 489.00 | 22.50 | 36.67 | 22.35 | 36.67 | 22.22 |
November | 489.00 | 21.43 | 206.17 | 21.13 | 206.17 | 20.97 |
December | 497.00 | 20.57 | 361.33 | 20.39 | 361.33 | 20.31 |
Annual Sum or Average | 4346.00 | 21.75 | 2282.00 | 21.67 | 1615.33 | 21.40 |
Minimum of Months | 50.00 | 20.38 | 36.67 | 20.31 | 0.00 | 20.28 |
Maximum of Months | 514.00 | 23.48 | 438.83 | 24.23 | 438.83 | 24.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.68 | 496.67 | 19.68 | 496.67 | 19.67 |
February | 454.00 | 20.10 | 427.17 | 20.06 | 427.17 | 20.04 |
March | 514.00 | 20.51 | 361.50 | 20.33 | 361.50 | 20.26 |
April | 477.83 | 21.39 | 176.33 | 21.05 | 176.33 | 20.85 |
May | 405.33 | 22.10 | 120.17 | 21.91 | 90.50 | 21.65 |
June | 171.17 | 22.91 | 166.33 | 23.56 | 1.83 | 23.54 |
July | 78.33 | 23.42 | 273.00 | 24.21 | 3.50 | 24.23 |
August | 154.00 | 23.03 | 158.67 | 23.72 | 2.50 | 23.72 |
September | 320.67 | 22.24 | 126.50 | 22.58 | 41.67 | 22.45 |
October | 497.83 | 21.37 | 167.17 | 21.06 | 167.17 | 20.87 |
November | 489.00 | 20.30 | 363.50 | 20.13 | 363.50 | 20.07 |
December | 497.00 | 19.82 | 480.67 | 19.80 | 480.67 | 19.79 |
Annual Sum or Average | 4561.17 | 20.96 | 3317.67 | 20.93 | 2613.00 | 20.68 |
Minimum of Months | 78.33 | 19.68 | 120.17 | 19.68 | 1.83 | 19.67 |
Maximum of Months | 514.00 | 23.42 | 496.67 | 24.21 | 496.67 | 24.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 485.33 | 19.82 | 485.33 | 19.82 |
February | 454.00 | 20.37 | 368.33 | 20.23 | 368.33 | 20.17 |
March | 504.17 | 20.78 | 303.83 | 20.52 | 303.83 | 20.40 |
April | 400.17 | 21.40 | 142.17 | 21.16 | 127.00 | 20.94 |
May | 319.83 | 21.86 | 140.83 | 21.96 | 70.00 | 21.68 |
June | 138.50 | 23.06 | 261.00 | 23.95 | 16.67 | 24.04 |
July | 84.17 | 24.54 | 368.33 | 24.53 | 31.50 | 24.69 |
August | 127.33 | 23.07 | 296.83 | 23.98 | 11.33 | 24.05 |
September | 271.17 | 22.34 | 178.33 | 23.01 | 45.67 | 23.00 |
October | 470.17 | 21.54 | 123.83 | 21.24 | 122.33 | 21.03 |
November | 489.00 | 20.47 | 331.00 | 20.28 | 331.00 | 20.21 |
December | 497.00 | 19.88 | 470.33 | 19.85 | 470.33 | 19.84 |
Annual Sum or Average | 4257.50 | 21.02 | 3470.17 | 21.22 | 2383.33 | 20.97 |
Minimum of Months | 84.17 | 19.84 | 123.83 | 19.82 | 11.33 | 19.82 |
Maximum of Months | 504.17 | 24.54 | 485.33 | 24.53 | 485.33 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.00 | 20.35 | 403.17 | 20.15 | 402.00 | 20.07 |
February | 410.33 | 20.86 | 285.83 | 20.63 | 270.83 | 20.47 |
March | 439.00 | 20.89 | 285.17 | 20.72 | 260.33 | 20.56 |
April | 379.17 | 21.39 | 179.67 | 21.30 | 140.83 | 21.06 |
May | 336.00 | 21.82 | 162.17 | 21.96 | 85.17 | 21.69 |
June | 189.33 | 22.63 | 201.67 | 23.50 | 10.83 | 23.52 |
July | 121.83 | 23.60 | 304.00 | 24.23 | 21.00 | 24.37 |
August | 155.67 | 23.01 | 268.17 | 23.89 | 12.33 | 23.96 |
September | 240.67 | 22.38 | 219.83 | 23.20 | 46.83 | 23.18 |
October | 359.67 | 21.62 | 183.67 | 21.74 | 110.17 | 21.51 |
November | 422.00 | 20.95 | 262.17 | 20.77 | 239.50 | 20.59 |
December | 471.33 | 20.32 | 366.00 | 20.09 | 366.00 | 20.01 |
Annual Sum or Average | 4015.00 | 21.29 | 3121.50 | 21.49 | 1965.83 | 21.22 |
Minimum of Months | 121.83 | 20.32 | 162.17 | 20.09 | 10.83 | 20.01 |
Maximum of Months | 490.00 | 23.60 | 403.17 | 24.23 | 402.00 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 479.83 | 19.80 | 479.83 | 19.79 |
February | 446.00 | 20.29 | 370.50 | 20.16 | 369.50 | 20.11 |
March | 493.17 | 20.60 | 332.67 | 20.41 | 330.33 | 20.32 |
April | 424.50 | 21.20 | 185.33 | 21.05 | 162.17 | 20.87 |
May | 365.33 | 21.86 | 165.83 | 22.01 | 86.50 | 21.78 |
June | 215.00 | 22.56 | 222.17 | 23.44 | 12.50 | 23.48 |
July | 143.00 | 23.34 | 298.17 | 24.10 | 20.00 | 24.23 |
August | 188.00 | 22.71 | 231.00 | 23.62 | 10.17 | 23.67 |
September | 311.33 | 22.02 | 169.17 | 22.60 | 50.67 | 22.54 |
October | 449.00 | 21.17 | 168.83 | 20.97 | 155.50 | 20.80 |
November | 483.67 | 20.49 | 331.00 | 20.28 | 331.00 | 20.19 |
December | 497.00 | 19.91 | 458.67 | 19.85 | 458.67 | 19.83 |
Annual Sum or Average | 4518.00 | 20.98 | 3413.17 | 21.10 | 2466.83 | 20.87 |
Minimum of Months | 143.00 | 19.83 | 165.83 | 19.80 | 10.17 | 19.79 |
Maximum of Months | 502.00 | 23.34 | 479.83 | 24.10 | 479.83 | 24.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.89 | 501.17 | 19.89 | 501.17 | 19.89 |
February | 454.00 | 20.31 | 438.00 | 20.29 | 438.00 | 20.28 |
March | 514.00 | 20.56 | 409.17 | 20.48 | 409.17 | 20.44 |
April | 485.00 | 21.16 | 201.17 | 20.95 | 201.17 | 20.84 |
May | 463.00 | 22.12 | 94.67 | 21.91 | 86.83 | 21.71 |
June | 245.17 | 23.30 | 98.00 | 23.55 | 0.00 | 23.55 |
July | 69.17 | 23.58 | 225.33 | 24.16 | 0.00 | 24.16 |
August | 149.83 | 23.38 | 113.33 | 23.83 | 0.00 | 23.83 |
September | 312.67 | 22.70 | 91.50 | 23.08 | 8.33 | 23.06 |
October | 502.00 | 22.04 | 56.33 | 21.90 | 56.33 | 21.78 |
November | 489.00 | 20.84 | 285.33 | 20.65 | 285.33 | 20.56 |
December | 497.00 | 20.11 | 477.67 | 20.09 | 477.67 | 20.09 |
Annual Sum or Average | 4682.83 | 21.24 | 2991.67 | 21.13 | 2464.00 | 20.91 |
Minimum of Months | 69.17 | 19.89 | 56.33 | 19.89 | 0.00 | 19.89 |
Maximum of Months | 514.00 | 23.58 | 501.17 | 24.16 | 501.17 | 24.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.09 | 493.67 | 20.08 | 493.67 | 20.08 |
February | 454.00 | 20.63 | 358.83 | 20.50 | 358.83 | 20.45 |
March | 514.00 | 21.00 | 291.67 | 20.77 | 291.67 | 20.66 |
April | 443.83 | 21.78 | 117.00 | 21.52 | 113.33 | 21.34 |
May | 355.67 | 22.28 | 96.17 | 22.31 | 50.50 | 22.11 |
June | 116.67 | 23.20 | 254.67 | 24.10 | 4.83 | 24.13 |
July | 40.17 | 25.23 | 403.83 | 24.62 | 20.67 | 24.73 |
August | 73.00 | 23.67 | 318.67 | 24.32 | 9.00 | 24.38 |
September | 215.67 | 22.94 | 171.50 | 23.70 | 15.50 | 23.78 |
October | 441.00 | 22.36 | 28.00 | 22.29 | 24.33 | 22.20 |
November | 489.00 | 21.16 | 228.67 | 20.93 | 228.67 | 20.80 |
December | 497.00 | 20.23 | 458.67 | 20.19 | 458.67 | 20.17 |
Annual Sum or Average | 4142.00 | 21.36 | 3221.33 | 21.58 | 2069.67 | 21.32 |
Minimum of Months | 40.17 | 20.09 | 28.00 | 20.08 | 4.83 | 20.08 |
Maximum of Months | 514.00 | 25.23 | 493.67 | 24.62 | 493.67 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.33 | 19.85 | 408.00 | 19.66 | 406.50 | 19.58 |
February | 418.50 | 20.60 | 268.33 | 20.38 | 257.17 | 20.22 |
March | 475.50 | 20.90 | 230.50 | 20.63 | 228.17 | 20.48 |
April | 438.33 | 21.55 | 132.00 | 21.36 | 121.33 | 21.16 |
May | 397.33 | 21.80 | 116.33 | 21.79 | 77.83 | 21.58 |
June | 223.67 | 22.54 | 156.33 | 23.31 | 0.83 | 23.30 |
July | 74.83 | 23.21 | 311.50 | 24.25 | 7.67 | 24.30 |
August | 112.33 | 22.89 | 284.33 | 24.07 | 6.83 | 24.12 |
September | 204.67 | 22.74 | 219.00 | 23.75 | 24.17 | 23.84 |
October | 326.83 | 22.29 | 92.00 | 22.63 | 23.33 | 22.57 |
November | 416.83 | 21.38 | 166.83 | 21.18 | 147.17 | 20.96 |
December | 488.67 | 20.37 | 334.00 | 20.09 | 334.00 | 19.97 |
Annual Sum or Average | 4075.83 | 21.28 | 2719.17 | 21.48 | 1635.00 | 21.18 |
Minimum of Months | 74.83 | 19.85 | 92.00 | 19.66 | 0.83 | 19.58 |
Maximum of Months | 498.33 | 23.21 | 408.00 | 24.25 | 406.50 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.06 | 490.50 | 20.04 | 490.50 | 20.04 |
February | 451.00 | 20.55 | 372.50 | 20.44 | 372.50 | 20.39 |
March | 507.00 | 20.82 | 328.00 | 20.65 | 328.00 | 20.57 |
April | 457.50 | 21.51 | 137.83 | 21.32 | 130.00 | 21.16 |
May | 373.67 | 22.19 | 104.33 | 22.28 | 53.50 | 22.10 |
June | 177.17 | 23.01 | 193.67 | 23.75 | 2.67 | 23.77 |
July | 56.67 | 24.02 | 345.00 | 24.40 | 11.17 | 24.47 |
August | 110.50 | 23.23 | 249.00 | 24.10 | 4.83 | 24.13 |
September | 251.83 | 22.69 | 160.33 | 23.44 | 13.00 | 23.50 |
October | 442.67 | 22.09 | 50.00 | 22.02 | 40.17 | 21.91 |
November | 485.67 | 21.09 | 234.17 | 20.86 | 234.17 | 20.74 |
December | 497.00 | 20.22 | 442.00 | 20.15 | 442.00 | 20.13 |
Annual Sum or Average | 4312.67 | 21.29 | 3107.33 | 21.43 | 2122.50 | 21.18 |
Minimum of Months | 56.67 | 20.06 | 50.00 | 20.04 | 2.67 | 20.04 |
Maximum of Months | 507.00 | 24.02 | 490.50 | 24.40 | 490.50 | 24.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.90 | 493.17 | 19.90 | 493.17 | 19.89 |
February | 454.00 | 20.38 | 397.67 | 20.31 | 397.67 | 20.28 |
March | 514.00 | 20.84 | 294.00 | 20.62 | 294.00 | 20.52 |
April | 480.67 | 21.85 | 108.83 | 21.58 | 108.83 | 21.39 |
May | 384.33 | 22.44 | 81.50 | 22.37 | 49.33 | 22.16 |
June | 133.33 | 23.29 | 172.50 | 23.85 | 0.00 | 23.85 |
July | 36.67 | 23.66 | 300.33 | 24.35 | 0.67 | 24.35 |
August | 110.50 | 23.38 | 165.00 | 24.02 | 0.67 | 24.03 |
September | 279.50 | 22.63 | 110.83 | 23.11 | 13.33 | 23.07 |
October | 495.83 | 21.99 | 74.50 | 21.77 | 74.50 | 21.60 |
November | 489.00 | 20.76 | 285.50 | 20.52 | 285.50 | 20.41 |
December | 497.00 | 20.02 | 460.00 | 19.97 | 460.00 | 19.96 |
Annual Sum or Average | 4376.83 | 21.24 | 2943.83 | 21.24 | 2177.67 | 20.97 |
Minimum of Months | 36.67 | 19.90 | 74.50 | 19.90 | 0.00 | 19.89 |
Maximum of Months | 514.00 | 23.66 | 493.17 | 24.35 | 493.17 | 24.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.87 | 409.17 | 19.85 | 409.17 | 19.84 |
February | 382.33 | 20.52 | 293.00 | 20.36 | 293.00 | 20.30 |
March | 425.17 | 20.94 | 222.17 | 20.68 | 222.17 | 20.55 |
April | 345.33 | 21.68 | 95.83 | 21.55 | 78.00 | 21.35 |
May | 272.83 | 22.08 | 98.33 | 22.26 | 40.17 | 22.04 |
June | 124.50 | 23.47 | 217.00 | 24.17 | 15.67 | 24.29 |
July | 61.33 | 25.03 | 313.50 | 24.73 | 28.67 | 24.89 |
August | 101.50 | 23.43 | 230.83 | 24.20 | 11.00 | 24.30 |
September | 227.50 | 22.63 | 139.83 | 23.39 | 21.83 | 23.47 |
October | 392.17 | 21.85 | 66.00 | 21.68 | 61.33 | 21.51 |
November | 415.83 | 20.79 | 234.33 | 20.57 | 234.33 | 20.47 |
December | 422.00 | 19.95 | 385.00 | 19.89 | 385.00 | 19.87 |
Annual Sum or Average | 3597.50 | 21.23 | 2705.00 | 21.42 | 1800.33 | 21.17 |
Minimum of Months | 61.33 | 19.87 | 66.00 | 19.85 | 11.00 | 19.84 |
Maximum of Months | 427.00 | 25.03 | 409.17 | 24.73 | 409.17 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.83 | 20.64 | 378.67 | 20.42 | 375.50 | 20.31 |
February | 396.17 | 21.18 | 253.50 | 20.98 | 233.33 | 20.80 |
March | 429.33 | 21.26 | 222.67 | 21.12 | 192.17 | 20.93 |
April | 370.33 | 21.85 | 125.33 | 21.85 | 84.17 | 21.65 |
May | 312.50 | 22.17 | 128.67 | 22.39 | 50.83 | 22.17 |
June | 158.33 | 23.03 | 205.83 | 23.81 | 3.50 | 23.84 |
July | 72.00 | 24.16 | 332.33 | 24.44 | 18.83 | 24.55 |
August | 116.83 | 23.44 | 284.67 | 24.16 | 10.17 | 24.24 |
September | 203.67 | 22.84 | 217.33 | 23.72 | 25.33 | 23.82 |
October | 334.83 | 22.20 | 135.67 | 22.51 | 48.17 | 22.38 |
November | 405.17 | 21.44 | 207.50 | 21.31 | 173.00 | 21.08 |
December | 460.50 | 20.65 | 319.33 | 20.38 | 319.33 | 20.26 |
Annual Sum or Average | 3746.50 | 21.62 | 2811.50 | 21.89 | 1534.33 | 21.61 |
Minimum of Months | 72.00 | 20.64 | 125.33 | 20.38 | 3.50 | 20.26 |
Maximum of Months | 486.83 | 24.16 | 378.67 | 24.44 | 375.50 | 24.55 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.02 | 474.50 | 19.98 | 474.50 | 19.97 |
February | 444.50 | 20.56 | 341.83 | 20.41 | 340.83 | 20.35 |
March | 490.17 | 20.88 | 260.50 | 20.66 | 259.33 | 20.55 |
April | 418.33 | 21.59 | 125.17 | 21.50 | 101.50 | 21.34 |
May | 338.67 | 22.15 | 135.83 | 22.39 | 54.17 | 22.22 |
June | 183.00 | 22.97 | 227.00 | 23.74 | 8.50 | 23.80 |
July | 89.17 | 23.88 | 323.83 | 24.34 | 19.83 | 24.47 |
August | 145.17 | 23.08 | 243.67 | 23.93 | 7.50 | 23.99 |
September | 282.83 | 22.39 | 162.50 | 23.10 | 24.67 | 23.14 |
October | 437.67 | 21.68 | 89.33 | 21.58 | 72.67 | 21.43 |
November | 479.17 | 20.87 | 250.83 | 20.62 | 250.83 | 20.50 |
December | 497.00 | 20.12 | 427.00 | 20.02 | 427.00 | 19.99 |
Annual Sum or Average | 4307.67 | 21.23 | 3062.00 | 21.40 | 2041.33 | 21.15 |
Minimum of Months | 89.17 | 20.02 | 89.33 | 19.98 | 7.50 | 19.97 |
Maximum of Months | 502.00 | 23.88 | 474.50 | 24.34 | 474.50 | 24.47 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.35470 | 14.43474 | -0.3164 | 8.63482 |
February | 454.00000 | 23.08961 | 16.09219 | -0.1109 | 6.32693 |
March | 514.00000 | 23.59387 | 16.95623 | 0.04050 | 5.72554 |
April | 485.00000 | 24.02895 | 19.96597 | 0.19113 | 5.98511 |
May | 508.00000 | 24.26987 | 22.97627 | -0.6011 | 13.57203 |
June | 496.00000 | 24.33778 | 30.69797 | -0.4476 | 9.62501 |
July | 497.00000 | 24.43090 | 34.56406 | -0.3707 | 8.46062 |
August | 514.00000 | 24.41183 | 30.49948 | -0.4080 | 9.00352 |
September | 485.00000 | 24.37475 | 30.09184 | -0.4585 | 10.04296 |
October | 502.00000 | 24.22705 | 22.15116 | 0.27187 | 6.72646 |
November | 489.00000 | 23.83087 | 18.23461 | 0.10974 | 5.82508 |
December | 497.00000 | 23.02127 | 15.66332 | -0.1280 | 6.58138 |
Annual Sum or Average | 5943.00000 | 23.83562 | 22.73601 | -0.1873 | 8.06345 |
Minimum of Months | 454.00000 | 22.35470 | 14.43474 | -0.6011 | 5.72554 |
Maximum of Months | 514.00000 | 24.43090 | 34.56406 | 0.27187 | 13.57203 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.92986 | 15.22791 | -0.6477 | 15.14865 |
February | 454.00000 | 21.61452 | 17.49997 | -0.4461 | 10.58052 |
March | 514.00000 | 22.32811 | 18.85681 | -0.2518 | 7.86634 |
April | 485.00000 | 23.14384 | 22.02499 | -0.0163 | 5.93879 |
May | 508.00000 | 23.64402 | 24.64050 | -0.8211 | 21.31215 |
June | 496.00000 | 24.09816 | 31.78025 | -0.5482 | 11.83810 |
July | 497.00000 | 24.27392 | 35.46940 | -0.4439 | 9.57512 |
August | 514.00000 | 24.23497 | 31.43285 | -0.4931 | 10.52990 |
September | 485.00000 | 24.00744 | 31.58802 | -0.6096 | 13.98024 |
October | 502.00000 | 23.39038 | 24.38533 | 0.06231 | 5.78194 |
November | 489.00000 | 22.39446 | 20.33662 | -0.2292 | 7.64336 |
December | 497.00000 | 21.32370 | 17.16203 | -0.5214 | 12.50410 |
Annual Sum or Average | 5943.00000 | 22.95815 | 24.24110 | -0.4146 | 11.07797 |
Minimum of Months | 454.00000 | 20.92986 | 15.22791 | -0.8211 | 5.78194 |
Maximum of Months | 514.00000 | 24.27392 | 35.46940 | 0.06231 | 21.31215 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.37924 | 15.35105 | -0.8142 | 20.91836 |
February | 454.00000 | 20.93321 | 17.94887 | -0.6340 | 15.27712 |
March | 514.00000 | 21.53744 | 19.44374 | -0.4540 | 11.44722 |
April | 485.00000 | 22.45622 | 22.73240 | -0.1842 | 7.49192 |
May | 508.00000 | 23.21257 | 25.02566 | -0.9709 | 27.66861 |
June | 496.00000 | 23.93284 | 31.88438 | -0.6044 | 13.66874 |
July | 497.00000 | 24.17589 | 35.38185 | -0.4742 | 10.29485 |
August | 514.00000 | 24.09619 | 31.50060 | -0.5440 | 11.90001 |
September | 485.00000 | 23.60202 | 32.25544 | -0.7557 | 19.45623 |
October | 502.00000 | 22.54260 | 25.60230 | -0.1469 | 6.97508 |
November | 489.00000 | 21.42668 | 21.17376 | -0.4769 | 11.91892 |
December | 497.00000 | 20.57083 | 17.41258 | -0.7337 | 18.78150 |
Annual Sum or Average | 5943.00000 | 22.41693 | 24.68153 | -0.5663 | 14.65982 |
Minimum of Months | 454.00000 | 20.37924 | 15.35105 | -0.9709 | 6.97508 |
Maximum of Months | 514.00000 | 24.17589 | 35.38185 | -0.1469 | 27.66861 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.68404 | 15.53392 | -1.0814 | 31.86468 |
February | 454.00000 | 20.10273 | 18.72198 | -0.9013 | 24.34732 |
March | 514.00000 | 20.51140 | 20.53796 | -0.7338 | 18.78710 |
April | 485.00000 | 21.43206 | 24.48589 | -0.4333 | 11.90642 |
May | 508.00000 | 22.53628 | 26.78923 | -1.1854 | 37.36151 |
June | 496.00000 | 23.73215 | 32.64237 | -0.6477 | 16.11198 |
July | 497.00000 | 24.14521 | 35.46472 | -0.4545 | 10.82352 |
August | 514.00000 | 23.85796 | 32.32402 | -0.6088 | 14.86164 |
September | 485.00000 | 22.94769 | 34.07968 | -0.9750 | 29.84784 |
October | 502.00000 | 21.39579 | 27.63093 | -0.4271 | 11.28531 |
November | 489.00000 | 20.29845 | 22.50182 | -0.7839 | 20.65154 |
December | 497.00000 | 19.82055 | 18.18559 | -0.9991 | 28.47750 |
Annual Sum or Average | 5943.00000 | 21.71887 | 25.78008 | -0.7688 | 21.34673 |
Minimum of Months | 454.00000 | 19.68404 | 15.53392 | -1.1854 | 10.82352 |
Maximum of Months | 514.00000 | 24.14521 | 35.46472 | -0.4271 | 37.36151 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.84142 | 15.06940 | -1.0278 | 29.49799 |
February | 454.00000 | 20.36562 | 17.80534 | -0.8091 | 21.47301 |
March | 514.00000 | 20.84186 | 19.37724 | -0.6228 | 16.53728 |
April | 485.00000 | 21.88595 | 22.96116 | -0.2819 | 10.93986 |
May | 508.00000 | 22.72254 | 25.65587 | -1.0435 | 32.27879 |
June | 496.00000 | 23.89337 | 31.78877 | -0.4783 | 13.78019 |
July | 497.00000 | 24.28958 | 34.82146 | -0.2673 | 9.43063 |
August | 514.00000 | 23.94567 | 31.52864 | -0.4499 | 12.64391 |
September | 485.00000 | 23.18185 | 33.01616 | -0.8144 | 25.34732 |
October | 502.00000 | 21.70104 | 26.35507 | -0.3202 | 10.10619 |
November | 489.00000 | 20.47105 | 21.54214 | -0.7225 | 18.50399 |
December | 497.00000 | 19.88441 | 17.56873 | -0.9676 | 27.19754 |
Annual Sum or Average | 5943.00000 | 21.93134 | 24.83018 | -0.6498 | 18.96579 |
Minimum of Months | 454.00000 | 19.84142 | 15.06940 | -1.0435 | 9.43063 |
Maximum of Months | 514.00000 | 24.28958 | 34.82146 | -0.2673 | 32.27879 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.44556 | 14.40254 | -0.8355 | 24.31163 |
February | 454.00000 | 21.19963 | 16.73311 | -0.5621 | 17.83167 |
March | 514.00000 | 21.35923 | 18.44208 | -0.4734 | 15.29958 |
April | 485.00000 | 22.02754 | 22.55165 | -0.2504 | 11.34001 |
May | 508.00000 | 22.65939 | 25.57490 | -1.0844 | 34.60111 |
June | 496.00000 | 23.61264 | 32.36021 | -0.6271 | 17.54819 |
July | 497.00000 | 24.07830 | 35.26295 | -0.3962 | 11.56557 |
August | 514.00000 | 23.87108 | 31.56460 | -0.4862 | 14.04375 |
September | 485.00000 | 23.34145 | 32.36100 | -0.7190 | 23.83896 |
October | 502.00000 | 22.35780 | 24.85076 | -0.1280 | 10.48244 |
November | 489.00000 | 21.40105 | 20.13093 | -0.4630 | 14.95911 |
December | 497.00000 | 20.50706 | 16.74051 | -0.7671 | 22.41844 |
Annual Sum or Average | 5943.00000 | 22.24653 | 24.29253 | -0.5669 | 18.20508 |
Minimum of Months | 454.00000 | 20.44556 | 14.40254 | -1.0844 | 10.48244 |
Maximum of Months | 514.00000 | 24.07830 | 35.26295 | -0.1280 | 34.60111 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.82733 | 14.89336 | -1.0399 | 30.10296 |
February | 454.00000 | 20.35952 | 17.59095 | -0.8184 | 22.50724 |
March | 514.00000 | 20.73907 | 19.23321 | -0.6585 | 17.76113 |
April | 485.00000 | 21.57219 | 23.26987 | -0.3601 | 11.93491 |
May | 508.00000 | 22.53054 | 25.91120 | -1.1035 | 35.80560 |
June | 496.00000 | 23.48248 | 32.78898 | -0.6308 | 18.41868 |
July | 497.00000 | 23.95661 | 35.74784 | -0.4098 | 12.53378 |
August | 514.00000 | 23.66483 | 32.27506 | -0.5665 | 16.12039 |
September | 485.00000 | 22.81617 | 33.55548 | -0.9322 | 30.33471 |
October | 502.00000 | 21.48815 | 26.40763 | -0.3707 | 11.28053 |
November | 489.00000 | 20.52417 | 21.25237 | -0.7139 | 18.97265 |
December | 497.00000 | 19.90607 | 17.33678 | -0.9677 | 27.40223 |
Annual Sum or Average | 5943.00000 | 21.75071 | 25.06421 | -0.7140 | 21.09362 |
Minimum of Months | 454.00000 | 19.82733 | 14.89336 | -1.1035 | 11.28053 |
Maximum of Months | 514.00000 | 23.95661 | 35.74784 | -0.3601 | 35.80560 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.89133 | 15.74700 | -1.0133 | 28.51114 |
February | 454.00000 | 20.31085 | 18.86657 | -0.8461 | 21.45784 |
March | 514.00000 | 20.56089 | 20.78605 | -0.7271 | 17.41755 |
April | 485.00000 | 21.16038 | 25.01984 | -0.5105 | 11.54721 |
May | 508.00000 | 22.31369 | 27.55751 | -1.2840 | 41.40215 |
June | 496.00000 | 23.70938 | 33.21345 | -0.6999 | 16.63198 |
July | 497.00000 | 24.12317 | 35.81150 | -0.4981 | 10.78707 |
August | 514.00000 | 23.95647 | 32.50997 | -0.6034 | 13.59404 |
September | 485.00000 | 23.27338 | 33.56115 | -0.8689 | 24.02659 |
October | 502.00000 | 22.04330 | 26.67659 | -0.2564 | 7.58379 |
November | 489.00000 | 20.84185 | 22.06982 | -0.6194 | 14.69389 |
December | 497.00000 | 20.11272 | 18.34306 | -0.8877 | 23.49387 |
Annual Sum or Average | 5943.00000 | 21.87056 | 25.88727 | -0.7345 | 19.27637 |
Minimum of Months | 454.00000 | 19.89133 | 15.74700 | -1.2840 | 7.58379 |
Maximum of Months | 514.00000 | 24.12317 | 35.81150 | -0.2564 | 41.40215 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.08638 | 15.42309 | -0.9517 | 25.87718 |
February | 454.00000 | 20.63340 | 18.17217 | -0.7386 | 18.48154 |
March | 514.00000 | 21.00112 | 19.84714 | -0.5853 | 14.37094 |
April | 485.00000 | 21.98246 | 23.33578 | -0.2777 | 9.25687 |
May | 508.00000 | 22.87111 | 26.02342 | -1.0316 | 31.19441 |
June | 496.00000 | 24.05270 | 31.76331 | -0.4700 | 12.12280 |
July | 497.00000 | 24.44154 | 34.63622 | -0.2507 | 7.97187 |
August | 514.00000 | 24.20601 | 31.25385 | -0.3873 | 9.85110 |
September | 485.00000 | 23.71857 | 32.13462 | -0.6427 | 17.59229 |
October | 502.00000 | 22.58084 | 25.28379 | -0.0990 | 6.92440 |
November | 489.00000 | 21.16019 | 21.24440 | -0.5252 | 12.61594 |
December | 497.00000 | 20.22713 | 17.90295 | -0.8456 | 21.87637 |
Annual Sum or Average | 5943.00000 | 22.25884 | 24.79035 | -0.5667 | 15.68104 |
Minimum of Months | 454.00000 | 20.08638 | 15.42309 | -1.0316 | 6.92440 |
Maximum of Months | 514.00000 | 24.44154 | 34.63622 | -0.0990 | 31.19441 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.89283 | 13.47759 | -0.9039 | 25.87401 |
February | 454.00000 | 20.92340 | 15.98106 | -0.5781 | 17.11097 |
March | 514.00000 | 21.13975 | 17.83577 | -0.4901 | 13.44031 |
April | 485.00000 | 21.83587 | 22.20251 | -0.2959 | 9.71756 |
May | 508.00000 | 22.36932 | 25.61739 | -1.1886 | 38.35036 |
June | 496.00000 | 23.48594 | 32.55074 | -0.7018 | 18.55894 |
July | 497.00000 | 24.15429 | 34.94045 | -0.4069 | 10.42762 |
August | 514.00000 | 24.02159 | 31.11855 | -0.4519 | 12.01418 |
September | 485.00000 | 23.72190 | 31.35332 | -0.5757 | 17.55194 |
October | 502.00000 | 23.00634 | 23.25167 | 0.06115 | 7.95860 |
November | 489.00000 | 21.84481 | 18.84702 | -0.2995 | 11.02889 |
December | 497.00000 | 20.43965 | 15.79753 | -0.7144 | 19.76352 |
Annual Sum or Average | 5943.00000 | 22.24483 | 23.62819 | -0.5465 | 16.85126 |
Minimum of Months | 454.00000 | 19.89283 | 13.47759 | -1.1886 | 7.95860 |
Maximum of Months | 514.00000 | 24.15429 | 34.94045 | 0.06115 | 38.35036 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.05690 | 15.28589 | -0.9674 | 26.54649 |
February | 454.00000 | 20.57927 | 18.01215 | -0.7561 | 19.23878 |
March | 514.00000 | 20.86297 | 19.75720 | -0.6271 | 15.38256 |
April | 485.00000 | 21.66258 | 23.64670 | -0.3569 | 9.88655 |
May | 508.00000 | 22.76924 | 26.10558 | -1.0617 | 33.00630 |
June | 496.00000 | 23.79232 | 32.53991 | -0.5800 | 14.67430 |
July | 497.00000 | 24.25321 | 35.27494 | -0.3518 | 9.18225 |
August | 514.00000 | 24.05441 | 31.82378 | -0.4697 | 11.66384 |
September | 485.00000 | 23.48040 | 32.51776 | -0.7236 | 20.49878 |
October | 502.00000 | 22.33596 | 25.42297 | -0.1541 | 7.33586 |
November | 489.00000 | 21.11172 | 21.08085 | -0.5348 | 13.06207 |
December | 497.00000 | 20.21800 | 17.71641 | -0.8510 | 22.32821 |
Annual Sum or Average | 5943.00000 | 22.10999 | 24.97264 | -0.6193 | 16.90658 |
Minimum of Months | 454.00000 | 20.05690 | 15.28589 | -1.0617 | 7.33586 |
Maximum of Months | 514.00000 | 24.25321 | 35.27494 | -0.1541 | 33.00630 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.90488 | 15.57919 | -0.9853 | 27.59009 |
February | 454.00000 | 20.38179 | 18.63935 | -0.7939 | 20.02957 |
March | 514.00000 | 20.84110 | 20.38763 | -0.6183 | 14.99966 |
April | 485.00000 | 21.87411 | 24.07425 | -0.3090 | 9.01259 |
May | 508.00000 | 22.88853 | 26.42712 | -1.0556 | 31.85675 |
June | 496.00000 | 23.92981 | 32.39581 | -0.5823 | 13.31546 |
July | 497.00000 | 24.25727 | 35.42657 | -0.4203 | 9.50684 |
August | 514.00000 | 24.04930 | 32.09641 | -0.5443 | 12.33454 |
September | 485.00000 | 23.34954 | 33.40834 | -0.8300 | 23.30617 |
October | 502.00000 | 22.01141 | 26.80541 | -0.2607 | 8.18810 |
November | 489.00000 | 20.76024 | 22.03456 | -0.6343 | 15.77950 |
December | 497.00000 | 20.01511 | 18.24338 | -0.8987 | 24.36988 |
Annual Sum or Average | 5943.00000 | 22.03502 | 25.49846 | -0.6607 | 17.51961 |
Minimum of Months | 454.00000 | 19.90488 | 15.57919 | -1.0556 | 8.18810 |
Maximum of Months | 514.00000 | 24.25727 | 35.42657 | -0.2607 | 31.85675 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.87308 | 14.40796 | -0.9802 | 27.39140 |
February | 385.00000 | 20.54367 | 17.11692 | -0.7364 | 18.85734 |
March | 433.00000 | 20.99140 | 18.66076 | -0.5630 | 14.32425 |
April | 410.00000 | 22.09031 | 22.35544 | -0.2210 | 9.15636 |
May | 430.00000 | 22.88419 | 25.18720 | -0.9893 | 30.24050 |
June | 418.00000 | 24.03222 | 31.44451 | -0.4535 | 12.67785 |
July | 422.00000 | 24.43643 | 34.52496 | -0.2525 | 9.02195 |
August | 433.00000 | 24.09671 | 31.09519 | -0.4290 | 11.63491 |
September | 410.00000 | 23.40783 | 32.33752 | -0.7397 | 22.27709 |
October | 427.00000 | 22.05265 | 25.30401 | -0.2226 | 8.22830 |
November | 417.00000 | 20.80043 | 20.44037 | -0.6129 | 15.07354 |
December | 422.00000 | 19.94614 | 16.87365 | -0.9063 | 24.62649 |
Annual Sum or Average | 5034.00000 | 22.10526 | 24.17632 | -0.5920 | 16.96182 |
Minimum of Months | 385.00000 | 19.87308 | 14.40796 | -0.9893 | 8.22830 |
Maximum of Months | 433.00000 | 24.43643 | 34.52496 | -0.2210 | 30.24050 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.75846 | 14.23676 | -0.7230 | 20.58300 |
February | 454.00000 | 21.59504 | 16.44530 | -0.4353 | 14.61091 |
March | 514.00000 | 21.74518 | 18.19269 | -0.3502 | 12.14758 |
April | 485.00000 | 22.43468 | 22.15602 | -0.1348 | 8.99739 |
May | 508.00000 | 22.99506 | 25.23350 | -0.9608 | 29.40053 |
June | 496.00000 | 23.84813 | 32.09231 | -0.5525 | 14.14544 |
July | 497.00000 | 24.24873 | 35.12350 | -0.3483 | 9.66004 |
August | 514.00000 | 24.08057 | 31.34265 | -0.4196 | 11.30723 |
September | 485.00000 | 23.68699 | 31.78950 | -0.5920 | 18.44629 |
October | 502.00000 | 22.88493 | 24.09664 | 0.01794 | 8.73807 |
November | 489.00000 | 21.94390 | 19.57504 | -0.3017 | 11.78920 |
December | 497.00000 | 20.90370 | 16.49717 | -0.6314 | 18.34072 |
Annual Sum or Average | 5943.00000 | 22.60105 | 23.94386 | -0.4537 | 14.86646 |
Minimum of Months | 454.00000 | 20.75846 | 14.23676 | -0.9608 | 8.73807 |
Maximum of Months | 514.00000 | 24.24873 | 35.12350 | 0.01794 | 29.40053 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.01921 | 14.78532 | -0.9507 | 26.25381 |
February | 454.00000 | 20.63852 | 17.40415 | -0.7127 | 18.61831 |
March | 514.00000 | 21.02339 | 19.11346 | -0.5527 | 14.34930 |
April | 485.00000 | 21.94899 | 22.94756 | -0.2491 | 9.36040 |
May | 508.00000 | 22.85469 | 25.60281 | -0.9825 | 30.69510 |
June | 496.00000 | 23.73450 | 32.52304 | -0.5516 | 14.83011 |
July | 497.00000 | 24.14472 | 35.58638 | -0.3566 | 10.34549 |
August | 514.00000 | 23.90948 | 32.01562 | -0.4894 | 12.92512 |
September | 485.00000 | 23.18989 | 32.98496 | -0.7958 | 24.21279 |
October | 502.00000 | 21.99923 | 25.72365 | -0.2253 | 8.57744 |
November | 489.00000 | 20.93159 | 20.84517 | -0.5757 | 14.75658 |
December | 497.00000 | 20.11670 | 17.27043 | -0.8659 | 23.38015 |
Annual Sum or Average | 5943.00000 | 22.05401 | 24.77627 | -0.6088 | 17.35933 |
Minimum of Months | 454.00000 | 20.01921 | 14.78532 | -0.9825 | 8.57744 |
Maximum of Months | 514.00000 | 24.14472 | 35.58638 | -0.2253 | 30.69510 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.167922E+09 | 46238166.13 | 8.17 | 0.167736E+09 | 186560.86 | 0.00 | 0.41 | 27-FEB-15:40 | 0.00 | 01-FEB-00:10 | 12450.91 | 27-FEB-15:40 | 12450.91 | 27-FEB-15:40 | 39.97 | 26-FEB-15:55 | 3338.45 | 27-FEB-15:40 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.185752E+10 | 0.494455E+09 | 59.24 | 0.184407E+10 | 13451518.05 | 0.00 | 0.83 | 06-APR-16:00 | 0.00 | 01-APR-00:10 | 27755.34 | 06-APR-16:00 | 27755.34 | 06-APR-16:00 | 606.00 | 22-APR-15:10 | 6665.64 | 06-APR-16:00 | 0.00 |
May | 0.751772E+10 | 0.193793E+10 | 143.93 | 0.730856E+10 | 0.209159E+09 | 0.00 | 1.00 | 19-MAY-11:50 | 0.00 | 01-MAY-00:10 | 54045.09 | 19-MAY-15:40 | 54045.09 | 19-MAY-15:40 | 5602.76 | 02-MAY-13:00 | 13715.26 | 19-MAY-15:30 | 0.00 |
June | 0.286436E+11 | 0.722273E+10 | 303.39 | 0.273465E+11 | 0.129711E+10 | 0.00 | 1.00 | 05-JUN-12:40 | 0.00 | 01-JUN-00:10 | 67162.17 | 29-JUN-15:10 | 67162.17 | 29-JUN-15:10 | 13038.27 | 22-JUN-06:03 | 19055.68 | 29-JUN-15:10 | 0.00 |
July | 0.501399E+11 | 0.130236E+11 | 400.29 | 0.484278E+11 | 0.171207E+10 | 0.00 | 1.00 | 01-JUL-14:00 | 0.00 | 01-JUL-00:10 | 84235.48 | 17-JUL-16:00 | 84235.48 | 17-JUL-16:00 | 18436.83 | 19-JUL-06:03 | 27961.31 | 17-JUL-16:00 | 0.00 |
August | 0.429099E+11 | 0.110100E+11 | 361.74 | 0.424712E+11 | 0.438663E+09 | 0.00 | 1.00 | 01-AUG-11:00 | 0.00 | 01-AUG-00:10 | 77688.13 | 07-AUG-16:00 | 77688.13 | 07-AUG-16:00 | 6437.47 | 09-AUG-11:10 | 22150.70 | 07-AUG-16:00 | 0.00 |
September | 0.201333E+11 | 0.510801E+10 | 237.31 | 0.184157E+11 | 0.171760E+10 | 0.00 | 1.00 | 01-SEP-09:30 | 0.00 | 01-SEP-00:10 | 104363.77 | 07-SEP-15:00 | 65709.70 | 01-SEP-16:00 | 51366.20 | 07-SEP-15:00 | 24047.69 | 07-SEP-15:00 | 0.00 |
October | 0.431794E+10 | 0.109314E+10 | 93.78 | 0.429203E+10 | 25910657.89 | 0.00 | 1.00 | 18-OCT-12:00 | 0.00 | 01-OCT-00:10 | 49547.04 | 18-OCT-15:40 | 49547.04 | 18-OCT-15:40 | 875.39 | 15-OCT-11:40 | 11524.72 | 18-OCT-15:40 | 0.00 |
November | 0.160415E+09 | 46060120.90 | 14.67 | 0.153649E+09 | 6765881.24 | 0.00 | 0.21 | 17-NOV-17:00 | 0.00 | 01-NOV-00:10 | 6158.37 | 17-NOV-17:00 | 6108.64 | 17-NOV-17:00 | 424.69 | 17-NOV-18:05 | 1734.29 | 17-NOV-17:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.155848E+12 | 0.399821E+11 | 1622.52 | 0.150427E+12 | 0.542092E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.501399E+11 | 0.130236E+11 | 400.29 | 0.484278E+11 | 0.171760E+10 | 0.00 | 1.00 | 0.00 | 104363.77 | 84235.48 | 51366.20 | 27961.31 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.160678E+09 | 44307912.63 | 8.50 | 0.160678E+09 | 0.00 | 0.00 | 0.41 | 27-FEB-15:30 | 0.00 | 01-FEB-00:10 | 11034.02 | 27-FEB-15:30 | 11034.02 | 27-FEB-15:30 | 0.00 | 27-FEB-13:10 | 2964.73 | 27-FEB-15:30 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.190872E+10 | 0.506205E+09 | 65.16 | 0.189837E+10 | 10351403.64 | 0.00 | 0.91 | 06-APR-16:00 | 0.00 | 01-APR-00:10 | 28374.79 | 06-APR-16:00 | 28374.79 | 06-APR-16:00 | 593.88 | 23-APR-13:35 | 6653.08 | 06-APR-16:00 | 0.00 |
May | 0.762283E+10 | 0.194433E+10 | 150.06 | 0.744576E+10 | 0.177075E+09 | 0.00 | 1.00 | 19-MAY-11:40 | 0.00 | 01-MAY-00:10 | 55097.27 | 19-MAY-15:30 | 55097.27 | 19-MAY-15:30 | 5111.93 | 02-MAY-13:00 | 13984.01 | 19-MAY-15:20 | 0.00 |
June | 0.273921E+11 | 0.689056E+10 | 311.92 | 0.262009E+11 | 0.119121E+10 | 0.00 | 1.00 | 05-JUN-12:30 | 0.00 | 01-JUN-00:10 | 64772.51 | 29-JUN-14:50 | 64772.51 | 29-JUN-14:50 | 7920.72 | 20-JUN-15:00 | 18442.43 | 29-JUN-15:00 | 0.00 |
July | 0.462026E+11 | 0.120065E+11 | 400.35 | 0.447981E+11 | 0.140448E+10 | 0.00 | 1.00 | 01-JUL-12:10 | 0.00 | 01-JUL-00:10 | 81160.12 | 17-JUL-15:30 | 81160.12 | 17-JUL-15:30 | 12543.11 | 19-JUL-09:10 | 26476.49 | 17-JUL-15:30 | 0.00 |
August | 0.390027E+11 | 0.100376E+11 | 366.01 | 0.386078E+11 | 0.394877E+09 | 0.00 | 1.00 | 01-AUG-10:50 | 0.00 | 01-AUG-00:10 | 77387.90 | 07-AUG-15:30 | 77387.90 | 07-AUG-15:30 | 4283.03 | 22-AUG-15:30 | 23707.26 | 06-AUG-16:01 | 0.00 |
September | 0.178363E+11 | 0.453217E+10 | 229.78 | 0.164142E+11 | 0.142216E+10 | 0.00 | 1.00 | 01-SEP-09:20 | 0.00 | 01-SEP-00:10 | 103287.59 | 07-SEP-15:00 | 66386.04 | 04-SEP-15:41 | 48781.17 | 07-SEP-15:00 | 23790.11 | 07-SEP-15:00 | 0.00 |
October | 0.357998E+10 | 0.914914E+09 | 92.50 | 0.355998E+10 | 20002912.98 | 0.00 | 1.00 | 18-OCT-12:10 | 0.00 | 01-OCT-00:10 | 43964.35 | 18-OCT-15:30 | 43964.35 | 18-OCT-15:30 | 573.70 | 15-OCT-10:55 | 10250.86 | 18-OCT-15:30 | 0.00 |
November | 0.145542E+09 | 41845818.96 | 15.17 | 0.137246E+09 | 8296051.66 | 0.00 | 0.21 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 5433.76 | 04-NOV-14:00 | 5433.76 | 04-NOV-14:00 | 429.26 | 17-NOV-17:00 | 1532.21 | 04-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.143851E+12 | 0.369183E+11 | 1639.44 | 0.139223E+12 | 0.462846E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.462026E+11 | 0.120065E+11 | 400.35 | 0.447981E+11 | 0.142216E+10 | 0.00 | 1.00 | 0.00 | 103287.59 | 81160.12 | 48781.17 | 26476.49 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.149396E+09 | 41625008.50 | 7.83 | 0.149372E+09 | 23285.08 | 0.00 | 0.35 | 27-FEB-15:30 | 0.00 | 01-FEB-00:10 | 10820.23 | 27-FEB-15:30 | 10820.23 | 27-FEB-15:30 | 10.85 | 26-FEB-16:10 | 2945.09 | 27-FEB-15:30 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.192048E+10 | 0.514908E+09 | 63.66 | 0.190427E+10 | 16214868.63 | 0.00 | 0.86 | 06-APR-16:00 | 0.00 | 01-APR-00:10 | 29862.46 | 06-APR-16:00 | 29862.46 | 06-APR-16:00 | 734.02 | 23-APR-13:35 | 7113.25 | 06-APR-16:00 | 0.00 |
May | 0.806731E+10 | 0.207009E+10 | 147.62 | 0.782642E+10 | 0.240885E+09 | 0.00 | 1.00 | 19-MAY-12:00 | 0.00 | 01-MAY-00:10 | 64418.82 | 19-MAY-15:30 | 64418.82 | 19-MAY-15:30 | 5580.12 | 02-MAY-13:00 | 16365.02 | 19-MAY-15:20 | 0.00 |
June | 0.293650E+11 | 0.743680E+10 | 310.16 | 0.280013E+11 | 0.136371E+10 | 0.00 | 1.00 | 05-JUN-13:10 | 0.00 | 01-JUN-00:10 | 73929.03 | 29-JUN-14:50 | 73929.03 | 29-JUN-14:50 | 8012.13 | 20-JUN-15:00 | 21068.08 | 29-JUN-15:00 | 0.00 |
July | 0.496044E+11 | 0.129927E+11 | 399.10 | 0.480036E+11 | 0.160086E+10 | 0.00 | 1.00 | 01-JUL-12:00 | 0.00 | 01-JUL-00:10 | 93568.73 | 17-JUL-15:20 | 93568.73 | 17-JUL-15:20 | 11853.68 | 19-JUL-09:30 | 30349.58 | 17-JUL-15:20 | 0.00 |
August | 0.410155E+11 | 0.106597E+11 | 363.60 | 0.404671E+11 | 0.548395E+09 | 0.00 | 1.00 | 01-AUG-11:50 | 0.00 | 01-AUG-00:10 | 89948.58 | 06-AUG-16:11 | 89948.58 | 06-AUG-16:11 | 4655.77 | 22-AUG-15:30 | 28234.75 | 06-AUG-16:11 | 0.00 |
September | 0.184616E+11 | 0.474232E+10 | 228.49 | 0.168682E+11 | 0.159339E+10 | 0.00 | 1.00 | 01-SEP-10:00 | 0.00 | 01-SEP-00:10 | 99946.14 | 07-SEP-15:20 | 84280.66 | 04-SEP-15:41 | 47512.57 | 07-SEP-15:00 | 24384.59 | 04-SEP-15:41 | 0.00 |
October | 0.336947E+10 | 0.876875E+09 | 88.97 | 0.332816E+10 | 41309367.64 | 0.00 | 1.00 | 18-OCT-13:00 | 0.00 | 01-OCT-00:10 | 45479.68 | 18-OCT-15:00 | 45479.68 | 18-OCT-15:00 | 806.71 | 15-OCT-11:24 | 10682.50 | 18-OCT-15:00 | 0.00 |
November | 0.145172E+09 | 41846365.08 | 14.17 | 0.132949E+09 | 12222527.03 | 0.00 | 0.18 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 5227.64 | 04-NOV-14:00 | 5219.90 | 04-NOV-14:00 | 561.73 | 17-NOV-17:00 | 1485.10 | 04-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.152098E+12 | 0.393769E+11 | 1623.59 | 0.146681E+12 | 0.541701E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.496044E+11 | 0.129927E+11 | 399.10 | 0.480036E+11 | 0.160086E+10 | 0.00 | 1.00 | 0.00 | 99946.14 | 93568.73 | 47512.57 | 30349.58 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 339.38 | 0.00 | 339.38 | 10.31 | 3056.47 | 0.00 | 0.00 | 0.00 |
February | 479.19 | 0.00 | 479.19 | 77.94 | 2237.00 | 0.00 | 0.00 | 0.00 |
March | 778.42 | 0.00 | 778.42 | 251.04 | 1779.84 | 0.00 | 0.00 | 0.00 |
April | 887.57 | 5.18 | 882.39 | 449.71 | 1251.88 | 0.00 | 0.00 | 0.00 |
May | 1165.59 | 69.07 | 1096.52 | 827.90 | 940.77 | 0.00 | 0.00 | 0.00 |
June | 1357.26 | 156.01 | 1201.26 | 1342.17 | 623.59 | 0.00 | 0.00 | 0.00 |
July | 1239.93 | 116.13 | 1123.80 | 1478.65 | 523.36 | 0.00 | 0.00 | 0.00 |
August | 993.57 | 26.63 | 966.93 | 1072.60 | 593.59 | 0.00 | 0.00 | 0.00 |
September | 744.11 | 0.27 | 743.84 | 623.75 | 887.34 | 0.00 | 0.00 | 0.00 |
October | 542.79 | 0.00 | 542.79 | 242.01 | 1275.39 | 0.00 | 0.00 | 0.00 |
November | 368.99 | 0.00 | 368.99 | 60.83 | 1836.72 | 0.00 | 0.00 | 0.00 |
December | 284.59 | 0.00 | 284.59 | 4.42 | 2579.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 766.65 | 31.26 | 735.39 | 539.65 | 1462.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 284.59 | 0.00 | 284.59 | 4.42 | 523.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1357.26 | 156.01 | 1201.26 | 1478.65 | 3056.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 519.55 | 238.19 | 281.36 | 264.66 | 1870.30 | 0.00 | 0.00 | 0.00 |
February | 812.62 | 403.44 | 409.17 | 596.09 | 1366.67 | 0.00 | 0.00 | 0.00 |
March | 1092.64 | 452.10 | 640.53 | 866.52 | 1112.77 | 0.00 | 0.00 | 0.00 |
April | 1394.10 | 690.90 | 703.19 | 1321.61 | 797.96 | 0.00 | 0.00 | 0.00 |
May | 1539.96 | 685.19 | 854.78 | 1562.39 | 631.47 | 0.00 | 0.00 | 0.00 |
June | 1993.28 | 1025.74 | 967.54 | 2341.24 | 427.26 | 0.00 | 0.00 | 0.00 |
July | 2092.00 | 1182.67 | 909.34 | 2666.95 | 349.74 | 0.00 | 0.00 | 0.00 |
August | 1818.05 | 1012.96 | 805.09 | 2260.49 | 391.06 | 0.00 | 0.00 | 0.00 |
September | 1286.09 | 663.87 | 622.21 | 1443.29 | 557.10 | 0.00 | 0.00 | 0.00 |
October | 922.70 | 468.53 | 454.17 | 860.54 | 797.76 | 0.00 | 0.00 | 0.00 |
November | 584.79 | 273.02 | 311.77 | 399.64 | 1117.24 | 0.00 | 0.00 | 0.00 |
December | 431.32 | 185.25 | 246.07 | 206.92 | 1576.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1209.33 | 607.87 | 601.45 | 1236.18 | 914.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 431.32 | 185.25 | 246.07 | 206.92 | 349.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2092.00 | 1182.67 | 967.54 | 2666.95 | 1870.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2392.28 | 1708.62 | 683.67 | 2163.99 | 2606.90 | 0.00 | 0.00 | 0.00 |
February | 3046.54 | 2191.18 | 855.35 | 3056.27 | 1939.74 | 0.00 | 0.00 | 0.00 |
March | 2723.21 | 1529.23 | 1193.98 | 2718.06 | 1728.94 | 0.00 | 0.00 | 0.00 |
April | 2189.00 | 1047.01 | 1141.99 | 2276.90 | 1288.49 | 0.00 | 0.00 | 0.00 |
May | 1944.87 | 645.95 | 1298.93 | 2050.37 | 1026.08 | 0.00 | 0.00 | 0.00 |
June | 1932.43 | 563.59 | 1368.84 | 2341.04 | 722.84 | 0.00 | 0.00 | 0.00 |
July | 2083.35 | 769.58 | 1313.77 | 2841.97 | 576.25 | 0.00 | 0.00 | 0.00 |
August | 2475.92 | 1248.32 | 1227.61 | 3277.69 | 643.48 | 0.00 | 0.00 | 0.00 |
September | 2746.10 | 1682.62 | 1063.47 | 3356.53 | 902.00 | 0.00 | 0.00 | 0.00 |
October | 2870.90 | 1985.19 | 885.71 | 3213.82 | 1241.56 | 0.00 | 0.00 | 0.00 |
November | 2617.41 | 1895.95 | 721.46 | 2664.72 | 1603.46 | 0.00 | 0.00 | 0.00 |
December | 2274.93 | 1642.73 | 632.20 | 2120.42 | 2193.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2437.21 | 1403.96 | 1033.24 | 2670.49 | 1370.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1932.43 | 563.59 | 632.20 | 2050.37 | 576.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3046.54 | 2191.18 | 1368.84 | 3356.53 | 2606.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 470.60 | 189.65 | 280.94 | 231.53 | 1955.70 | 0.00 | 0.00 | 0.00 |
February | 803.24 | 394.83 | 408.41 | 599.57 | 1404.43 | 0.00 | 0.00 | 0.00 |
March | 1027.95 | 376.66 | 651.30 | 795.77 | 1168.98 | 0.00 | 0.00 | 0.00 |
April | 1342.00 | 594.57 | 747.43 | 1287.59 | 846.97 | 0.00 | 0.00 | 0.00 |
May | 1659.96 | 757.03 | 902.93 | 1742.57 | 674.39 | 0.00 | 0.00 | 0.00 |
June | 1805.97 | 829.55 | 976.42 | 2132.64 | 473.69 | 0.00 | 0.00 | 0.00 |
July | 1850.01 | 934.84 | 915.17 | 2389.59 | 395.75 | 0.00 | 0.00 | 0.00 |
August | 1570.91 | 770.97 | 799.94 | 1971.79 | 425.42 | 0.00 | 0.00 | 0.00 |
September | 1263.70 | 638.88 | 624.82 | 1448.79 | 598.87 | 0.00 | 0.00 | 0.00 |
October | 903.20 | 448.75 | 454.45 | 867.33 | 844.40 | 0.00 | 0.00 | 0.00 |
November | 639.38 | 317.19 | 322.19 | 492.86 | 1166.45 | 0.00 | 0.00 | 0.00 |
December | 429.78 | 181.40 | 248.38 | 221.71 | 1629.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1148.79 | 536.71 | 612.08 | 1184.86 | 963.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 429.78 | 181.40 | 248.38 | 221.71 | 395.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1850.01 | 934.84 | 976.42 | 2389.59 | 1955.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.12 | 0.00 | 113.12 | 2.86 | 1029.20 | 0.00 | 0.00 | 0.00 |
February | 159.72 | 0.00 | 159.72 | 25.83 | 757.40 | 0.00 | 0.00 | 0.00 |
March | 259.46 | 0.00 | 259.46 | 89.15 | 600.22 | 0.00 | 0.00 | 0.00 |
April | 295.84 | 1.73 | 294.12 | 162.90 | 414.17 | 0.00 | 0.00 | 0.00 |
May | 388.51 | 23.02 | 365.49 | 292.12 | 314.60 | 0.00 | 0.00 | 0.00 |
June | 452.40 | 52.00 | 400.40 | 459.24 | 206.44 | 0.00 | 0.00 | 0.00 |
July | 413.29 | 38.71 | 374.58 | 501.44 | 173.55 | 0.00 | 0.00 | 0.00 |
August | 331.17 | 8.88 | 322.30 | 362.59 | 201.08 | 0.00 | 0.00 | 0.00 |
September | 248.03 | 0.09 | 247.94 | 208.92 | 311.36 | 0.00 | 0.00 | 0.00 |
October | 180.92 | 0.00 | 180.92 | 75.20 | 460.53 | 0.00 | 0.00 | 0.00 |
November | 122.99 | 0.00 | 122.99 | 17.66 | 653.06 | 0.00 | 0.00 | 0.00 |
December | 94.86 | 0.00 | 94.86 | 1.50 | 889.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.54 | 10.42 | 245.12 | 184.26 | 499.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.86 | 0.00 | 94.86 | 1.50 | 173.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 452.40 | 52.00 | 400.40 | 501.44 | 1029.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.13 | 0.00 | 113.13 | 2.86 | 1029.26 | 0.00 | 0.00 | 0.00 |
February | 159.73 | 0.00 | 159.73 | 25.83 | 757.44 | 0.00 | 0.00 | 0.00 |
March | 259.47 | 0.00 | 259.47 | 89.15 | 600.26 | 0.00 | 0.00 | 0.00 |
April | 295.85 | 1.73 | 294.13 | 162.91 | 414.20 | 0.00 | 0.00 | 0.00 |
May | 388.53 | 23.02 | 365.50 | 292.12 | 314.62 | 0.00 | 0.00 | 0.00 |
June | 452.42 | 52.00 | 400.42 | 459.26 | 206.45 | 0.00 | 0.00 | 0.00 |
July | 413.31 | 38.71 | 374.60 | 501.46 | 173.56 | 0.00 | 0.00 | 0.00 |
August | 331.19 | 8.88 | 322.31 | 362.61 | 201.09 | 0.00 | 0.00 | 0.00 |
September | 248.04 | 0.09 | 247.95 | 208.93 | 311.38 | 0.00 | 0.00 | 0.00 |
October | 180.93 | 0.00 | 180.93 | 75.20 | 460.56 | 0.00 | 0.00 | 0.00 |
November | 123.00 | 0.00 | 123.00 | 17.66 | 653.10 | 0.00 | 0.00 | 0.00 |
December | 94.86 | 0.00 | 94.86 | 1.50 | 889.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.55 | 10.42 | 245.13 | 184.27 | 500.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.86 | 0.00 | 94.86 | 1.50 | 173.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 452.42 | 52.00 | 400.42 | 501.46 | 1029.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.13 | 0.00 | 113.13 | 2.86 | 1029.26 | 0.00 | 0.00 | 0.00 |
February | 159.73 | 0.00 | 159.73 | 25.83 | 757.44 | 0.00 | 0.00 | 0.00 |
March | 259.47 | 0.00 | 259.47 | 89.15 | 600.26 | 0.00 | 0.00 | 0.00 |
April | 295.85 | 1.73 | 294.13 | 162.91 | 414.20 | 0.00 | 0.00 | 0.00 |
May | 388.53 | 23.02 | 365.50 | 292.12 | 314.62 | 0.00 | 0.00 | 0.00 |
June | 452.42 | 52.00 | 400.42 | 459.26 | 206.45 | 0.00 | 0.00 | 0.00 |
July | 413.31 | 38.71 | 374.60 | 501.46 | 173.56 | 0.00 | 0.00 | 0.00 |
August | 331.19 | 8.88 | 322.31 | 362.61 | 201.09 | 0.00 | 0.00 | 0.00 |
September | 248.04 | 0.09 | 247.95 | 208.93 | 311.38 | 0.00 | 0.00 | 0.00 |
October | 180.93 | 0.00 | 180.93 | 75.20 | 460.56 | 0.00 | 0.00 | 0.00 |
November | 123.00 | 0.00 | 123.00 | 17.66 | 653.10 | 0.00 | 0.00 | 0.00 |
December | 94.86 | 0.00 | 94.86 | 1.50 | 889.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.55 | 10.42 | 245.13 | 184.27 | 500.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.86 | 0.00 | 94.86 | 1.50 | 173.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 452.42 | 52.00 | 400.42 | 501.46 | 1029.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 499.78 | 229.13 | 270.65 | 254.53 | 1827.20 | 0.00 | 0.00 | 0.00 |
February | 781.70 | 388.09 | 393.60 | 575.11 | 1347.35 | 0.00 | 0.00 | 0.00 |
March | 1051.06 | 434.90 | 616.16 | 845.01 | 1101.09 | 0.00 | 0.00 | 0.00 |
April | 1341.05 | 664.61 | 676.44 | 1290.82 | 787.62 | 0.00 | 0.00 | 0.00 |
May | 1481.37 | 659.11 | 822.25 | 1522.72 | 629.09 | 0.00 | 0.00 | 0.00 |
June | 1917.44 | 986.71 | 930.73 | 2268.21 | 425.18 | 0.00 | 0.00 | 0.00 |
July | 2012.40 | 1137.66 | 874.74 | 2577.16 | 353.80 | 0.00 | 0.00 | 0.00 |
August | 1748.87 | 974.41 | 774.46 | 2181.72 | 400.43 | 0.00 | 0.00 | 0.00 |
September | 1237.15 | 638.61 | 598.54 | 1386.19 | 583.70 | 0.00 | 0.00 | 0.00 |
October | 887.59 | 450.70 | 436.89 | 811.57 | 849.64 | 0.00 | 0.00 | 0.00 |
November | 562.54 | 262.63 | 299.91 | 370.70 | 1158.08 | 0.00 | 0.00 | 0.00 |
December | 414.90 | 178.20 | 236.70 | 195.93 | 1576.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1163.31 | 584.74 | 578.57 | 1193.50 | 918.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 414.90 | 178.20 | 236.70 | 195.93 | 353.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2012.40 | 1137.66 | 930.73 | 2577.16 | 1827.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.76 | 9.06 | 10.70 | 10.06 | 72.25 | 0.00 | 0.00 | 0.00 |
February | 30.91 | 15.34 | 15.56 | 22.74 | 53.27 | 0.00 | 0.00 | 0.00 |
March | 41.56 | 17.20 | 24.36 | 33.41 | 43.54 | 0.00 | 0.00 | 0.00 |
April | 53.02 | 26.28 | 26.75 | 51.04 | 31.14 | 0.00 | 0.00 | 0.00 |
May | 58.57 | 26.06 | 32.51 | 60.21 | 24.87 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 39.01 | 36.80 | 89.68 | 16.81 | 0.00 | 0.00 | 0.00 |
July | 79.57 | 44.98 | 34.59 | 101.90 | 13.99 | 0.00 | 0.00 | 0.00 |
August | 69.15 | 38.53 | 30.62 | 86.26 | 15.83 | 0.00 | 0.00 | 0.00 |
September | 48.92 | 25.25 | 23.67 | 54.81 | 23.08 | 0.00 | 0.00 | 0.00 |
October | 35.09 | 17.82 | 17.27 | 32.09 | 33.59 | 0.00 | 0.00 | 0.00 |
November | 22.24 | 10.38 | 11.86 | 14.66 | 45.79 | 0.00 | 0.00 | 0.00 |
December | 16.40 | 7.05 | 9.36 | 7.75 | 62.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.00 | 23.12 | 22.88 | 47.19 | 36.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.40 | 7.05 | 9.36 | 7.75 | 13.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 79.57 | 44.98 | 36.80 | 101.90 | 72.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 797.41 | 569.53 | 227.89 | 732.50 | 881.77 | 0.00 | 0.00 | 0.00 |
February | 1015.49 | 730.38 | 285.11 | 1032.27 | 674.89 | 0.00 | 0.00 | 0.00 |
March | 907.72 | 509.73 | 397.99 | 920.99 | 600.21 | 0.00 | 0.00 | 0.00 |
April | 729.66 | 349.00 | 380.66 | 774.11 | 440.97 | 0.00 | 0.00 | 0.00 |
May | 648.28 | 215.31 | 432.97 | 700.68 | 348.62 | 0.00 | 0.00 | 0.00 |
June | 644.13 | 187.86 | 456.28 | 795.01 | 242.66 | 0.00 | 0.00 | 0.00 |
July | 694.44 | 256.52 | 437.92 | 956.27 | 198.33 | 0.00 | 0.00 | 0.00 |
August | 825.30 | 416.10 | 409.20 | 1099.75 | 227.51 | 0.00 | 0.00 | 0.00 |
September | 915.35 | 560.86 | 354.49 | 1123.53 | 331.53 | 0.00 | 0.00 | 0.00 |
October | 956.95 | 661.72 | 295.23 | 1070.47 | 467.36 | 0.00 | 0.00 | 0.00 |
November | 872.45 | 631.97 | 240.48 | 885.33 | 587.00 | 0.00 | 0.00 | 0.00 |
December | 758.29 | 547.56 | 210.73 | 709.82 | 764.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 812.39 | 467.98 | 344.41 | 899.04 | 479.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 644.13 | 187.86 | 210.73 | 700.68 | 198.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1015.49 | 730.38 | 456.28 | 1123.53 | 881.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 797.41 | 569.53 | 227.89 | 732.50 | 881.77 | 0.00 | 0.00 | 0.00 |
February | 1015.49 | 730.38 | 285.11 | 1032.27 | 674.89 | 0.00 | 0.00 | 0.00 |
March | 907.72 | 509.73 | 397.99 | 920.99 | 600.21 | 0.00 | 0.00 | 0.00 |
April | 729.66 | 349.00 | 380.66 | 774.11 | 440.97 | 0.00 | 0.00 | 0.00 |
May | 648.28 | 215.31 | 432.97 | 700.68 | 348.62 | 0.00 | 0.00 | 0.00 |
June | 644.13 | 187.86 | 456.28 | 795.01 | 242.66 | 0.00 | 0.00 | 0.00 |
July | 694.44 | 256.52 | 437.92 | 956.27 | 198.33 | 0.00 | 0.00 | 0.00 |
August | 825.30 | 416.10 | 409.20 | 1099.75 | 227.51 | 0.00 | 0.00 | 0.00 |
September | 915.35 | 560.86 | 354.49 | 1123.53 | 331.53 | 0.00 | 0.00 | 0.00 |
October | 956.95 | 661.72 | 295.23 | 1070.47 | 467.36 | 0.00 | 0.00 | 0.00 |
November | 872.45 | 631.97 | 240.48 | 885.33 | 587.00 | 0.00 | 0.00 | 0.00 |
December | 758.29 | 547.56 | 210.73 | 709.82 | 764.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 812.39 | 467.98 | 344.41 | 899.04 | 479.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 644.13 | 187.86 | 210.73 | 700.68 | 198.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1015.49 | 730.38 | 456.28 | 1123.53 | 881.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 797.36 | 569.49 | 227.87 | 732.45 | 881.72 | 0.00 | 0.00 | 0.00 |
February | 1015.43 | 730.33 | 285.10 | 1032.20 | 674.85 | 0.00 | 0.00 | 0.00 |
March | 907.66 | 509.70 | 397.96 | 920.93 | 600.17 | 0.00 | 0.00 | 0.00 |
April | 729.61 | 348.98 | 380.63 | 774.06 | 440.94 | 0.00 | 0.00 | 0.00 |
May | 648.24 | 215.30 | 432.94 | 700.63 | 348.59 | 0.00 | 0.00 | 0.00 |
June | 644.09 | 187.85 | 456.25 | 794.96 | 242.65 | 0.00 | 0.00 | 0.00 |
July | 694.40 | 256.51 | 437.89 | 956.21 | 198.32 | 0.00 | 0.00 | 0.00 |
August | 825.24 | 416.07 | 409.17 | 1099.68 | 227.49 | 0.00 | 0.00 | 0.00 |
September | 915.29 | 560.83 | 354.47 | 1123.46 | 331.51 | 0.00 | 0.00 | 0.00 |
October | 956.89 | 661.67 | 295.21 | 1070.40 | 467.33 | 0.00 | 0.00 | 0.00 |
November | 872.40 | 631.93 | 240.47 | 885.28 | 586.97 | 0.00 | 0.00 | 0.00 |
December | 758.25 | 547.53 | 210.72 | 709.78 | 764.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 812.34 | 467.95 | 344.39 | 898.98 | 479.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 644.09 | 187.85 | 210.72 | 700.63 | 198.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1015.43 | 730.33 | 456.25 | 1123.46 | 881.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 452.69 | 182.44 | 270.26 | 226.00 | 1904.11 | 0.00 | 0.00 | 0.00 |
February | 772.68 | 379.81 | 392.87 | 585.74 | 1386.52 | 0.00 | 0.00 | 0.00 |
March | 988.84 | 362.33 | 626.52 | 783.75 | 1152.23 | 0.00 | 0.00 | 0.00 |
April | 1290.94 | 571.94 | 718.99 | 1262.74 | 831.69 | 0.00 | 0.00 | 0.00 |
May | 1596.80 | 728.22 | 868.58 | 1698.67 | 674.46 | 0.00 | 0.00 | 0.00 |
June | 1737.26 | 797.98 | 939.27 | 2069.18 | 472.15 | 0.00 | 0.00 | 0.00 |
July | 1779.63 | 899.27 | 880.36 | 2309.73 | 399.95 | 0.00 | 0.00 | 0.00 |
August | 1511.14 | 741.63 | 769.51 | 1902.86 | 434.59 | 0.00 | 0.00 | 0.00 |
September | 1215.62 | 614.57 | 601.05 | 1393.25 | 627.34 | 0.00 | 0.00 | 0.00 |
October | 868.83 | 431.68 | 437.16 | 823.52 | 896.28 | 0.00 | 0.00 | 0.00 |
November | 615.05 | 305.12 | 309.93 | 468.74 | 1207.20 | 0.00 | 0.00 | 0.00 |
December | 413.43 | 174.50 | 238.93 | 214.12 | 1626.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1105.08 | 516.29 | 588.79 | 1147.77 | 966.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 413.43 | 174.50 | 238.93 | 214.12 | 399.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1779.63 | 899.27 | 939.27 | 2309.73 | 1904.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.90 | 7.21 | 10.69 | 8.94 | 75.29 | 0.00 | 0.00 | 0.00 |
February | 30.55 | 15.02 | 15.53 | 23.16 | 54.82 | 0.00 | 0.00 | 0.00 |
March | 39.10 | 14.33 | 24.77 | 30.99 | 45.56 | 0.00 | 0.00 | 0.00 |
April | 51.04 | 22.61 | 28.43 | 49.93 | 32.88 | 0.00 | 0.00 | 0.00 |
May | 63.14 | 28.79 | 34.34 | 67.16 | 26.67 | 0.00 | 0.00 | 0.00 |
June | 68.69 | 31.55 | 37.14 | 81.81 | 18.67 | 0.00 | 0.00 | 0.00 |
July | 70.36 | 35.56 | 34.81 | 91.32 | 15.81 | 0.00 | 0.00 | 0.00 |
August | 59.75 | 29.32 | 30.43 | 75.24 | 17.18 | 0.00 | 0.00 | 0.00 |
September | 48.06 | 24.30 | 23.77 | 55.09 | 24.80 | 0.00 | 0.00 | 0.00 |
October | 34.35 | 17.07 | 17.28 | 32.56 | 35.44 | 0.00 | 0.00 | 0.00 |
November | 24.32 | 12.06 | 12.25 | 18.53 | 47.73 | 0.00 | 0.00 | 0.00 |
December | 16.35 | 6.90 | 9.45 | 8.47 | 64.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.69 | 20.41 | 23.28 | 45.38 | 38.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.35 | 6.90 | 9.45 | 8.47 | 15.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.36 | 35.56 | 37.14 | 91.32 | 75.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 339.38 | 0.00 | 339.38 | 7.95 | 3131.97 | 0.00 | 0.00 | 0.00 |
February | 479.19 | 0.00 | 479.19 | 68.49 | 2323.96 | 0.00 | 0.00 | 0.00 |
March | 778.42 | 0.00 | 778.42 | 236.46 | 1867.26 | 0.00 | 0.00 | 0.00 |
April | 887.57 | 5.18 | 882.39 | 432.34 | 1329.80 | 0.00 | 0.00 | 0.00 |
May | 1165.59 | 69.07 | 1096.52 | 813.17 | 996.02 | 0.00 | 0.00 | 0.00 |
June | 1357.26 | 156.01 | 1201.26 | 1332.84 | 648.23 | 0.00 | 0.00 | 0.00 |
July | 1239.93 | 116.13 | 1123.80 | 1475.58 | 539.86 | 0.00 | 0.00 | 0.00 |
August | 993.57 | 26.63 | 966.93 | 1066.88 | 621.30 | 0.00 | 0.00 | 0.00 |
September | 744.11 | 0.27 | 743.84 | 611.21 | 945.23 | 0.00 | 0.00 | 0.00 |
October | 542.79 | 0.00 | 542.79 | 219.32 | 1374.32 | 0.00 | 0.00 | 0.00 |
November | 368.99 | 0.00 | 368.99 | 50.69 | 1952.07 | 0.00 | 0.00 | 0.00 |
December | 284.59 | 0.00 | 284.59 | 3.85 | 2674.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 766.65 | 31.26 | 735.39 | 529.45 | 1530.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 284.59 | 0.00 | 284.59 | 3.85 | 539.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1357.26 | 156.01 | 1201.26 | 1475.58 | 3131.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 519.55 | 238.19 | 281.36 | 259.06 | 1915.84 | 0.00 | 0.00 | 0.00 |
February | 812.62 | 403.44 | 409.17 | 583.88 | 1418.73 | 0.00 | 0.00 | 0.00 |
March | 1092.64 | 452.10 | 640.53 | 853.45 | 1165.24 | 0.00 | 0.00 | 0.00 |
April | 1394.10 | 690.90 | 703.19 | 1310.13 | 842.26 | 0.00 | 0.00 | 0.00 |
May | 1539.96 | 685.19 | 854.78 | 1555.11 | 664.27 | 0.00 | 0.00 | 0.00 |
June | 1993.28 | 1025.74 | 967.54 | 2338.97 | 441.91 | 0.00 | 0.00 | 0.00 |
July | 2092.00 | 1182.67 | 909.34 | 2668.26 | 360.09 | 0.00 | 0.00 | 0.00 |
August | 1818.05 | 1012.96 | 805.09 | 2259.27 | 406.51 | 0.00 | 0.00 | 0.00 |
September | 1286.09 | 663.87 | 622.21 | 1435.83 | 587.97 | 0.00 | 0.00 | 0.00 |
October | 922.70 | 468.53 | 454.17 | 842.78 | 853.52 | 0.00 | 0.00 | 0.00 |
November | 584.79 | 273.02 | 311.77 | 384.29 | 1183.76 | 0.00 | 0.00 | 0.00 |
December | 431.32 | 185.25 | 246.07 | 200.85 | 1635.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1209.33 | 607.87 | 601.45 | 1228.02 | 954.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 431.32 | 185.25 | 246.07 | 200.85 | 360.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2092.00 | 1182.67 | 967.54 | 2668.26 | 1915.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2392.28 | 1708.62 | 683.67 | 2150.17 | 2680.58 | 0.00 | 0.00 | 0.00 |
February | 3046.54 | 2191.18 | 855.35 | 3037.02 | 2022.78 | 0.00 | 0.00 | 0.00 |
March | 2723.21 | 1529.23 | 1193.98 | 2701.52 | 1813.94 | 0.00 | 0.00 | 0.00 |
April | 2189.00 | 1047.01 | 1141.99 | 2262.43 | 1363.27 | 0.00 | 0.00 | 0.00 |
May | 1944.87 | 645.95 | 1298.93 | 2040.94 | 1083.17 | 0.00 | 0.00 | 0.00 |
June | 1932.43 | 563.59 | 1368.84 | 2338.24 | 754.60 | 0.00 | 0.00 | 0.00 |
July | 2083.35 | 769.58 | 1313.77 | 2843.07 | 598.34 | 0.00 | 0.00 | 0.00 |
August | 2475.92 | 1248.32 | 1227.61 | 3277.33 | 673.58 | 0.00 | 0.00 | 0.00 |
September | 2746.10 | 1682.62 | 1063.47 | 3349.28 | 955.73 | 0.00 | 0.00 | 0.00 |
October | 2870.90 | 1985.19 | 885.71 | 3192.04 | 1329.42 | 0.00 | 0.00 | 0.00 |
November | 2617.41 | 1895.95 | 721.46 | 2635.01 | 1702.64 | 0.00 | 0.00 | 0.00 |
December | 2274.93 | 1642.73 | 632.20 | 2099.55 | 2283.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2437.21 | 1403.96 | 1033.24 | 2657.61 | 1436.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1932.43 | 563.59 | 632.20 | 2040.94 | 598.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3046.54 | 2191.18 | 1368.84 | 3349.28 | 2680.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 470.60 | 189.65 | 280.94 | 228.61 | 2002.28 | 0.00 | 0.00 | 0.00 |
February | 803.24 | 394.83 | 408.41 | 592.23 | 1460.96 | 0.00 | 0.00 | 0.00 |
March | 1027.95 | 376.66 | 651.30 | 787.75 | 1225.14 | 0.00 | 0.00 | 0.00 |
April | 1342.00 | 594.57 | 747.43 | 1277.64 | 895.59 | 0.00 | 0.00 | 0.00 |
May | 1659.96 | 757.03 | 902.93 | 1736.47 | 711.48 | 0.00 | 0.00 | 0.00 |
June | 1805.97 | 829.55 | 976.42 | 2129.96 | 494.10 | 0.00 | 0.00 | 0.00 |
July | 1850.01 | 934.84 | 915.17 | 2389.37 | 410.19 | 0.00 | 0.00 | 0.00 |
August | 1570.91 | 770.97 | 799.94 | 1968.76 | 445.22 | 0.00 | 0.00 | 0.00 |
September | 1263.70 | 638.88 | 624.82 | 1441.77 | 635.89 | 0.00 | 0.00 | 0.00 |
October | 903.20 | 448.75 | 454.45 | 853.16 | 905.79 | 0.00 | 0.00 | 0.00 |
November | 639.38 | 317.19 | 322.19 | 482.37 | 1236.94 | 0.00 | 0.00 | 0.00 |
December | 429.78 | 181.40 | 248.38 | 217.57 | 1689.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1148.79 | 536.71 | 612.08 | 1178.54 | 1007.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 429.78 | 181.40 | 248.38 | 217.57 | 410.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1850.01 | 934.84 | 976.42 | 2389.37 | 2002.28 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.909008E+09 | 0.00 | 0.909008E+09 | 27624492.45 | 0.818644E+10 |
February | 0.115926E+10 | 0.00 | 0.115926E+10 | 0.188550E+09 | 0.541174E+10 |
March | 0.208493E+10 | 0.00 | 0.208493E+10 | 0.672381E+09 | 0.476713E+10 |
April | 0.230057E+10 | 13425633.98 | 0.228715E+10 | 0.116565E+10 | 0.324487E+10 |
May | 0.312191E+10 | 0.184993E+09 | 0.293692E+10 | 0.221746E+10 | 0.251977E+10 |
June | 0.351802E+10 | 0.404367E+09 | 0.311366E+10 | 0.347890E+10 | 0.161635E+10 |
July | 0.332104E+10 | 0.311055E+09 | 0.300998E+10 | 0.396041E+10 | 0.140176E+10 |
August | 0.266116E+10 | 71331635.12 | 0.258983E+10 | 0.287284E+10 | 0.158986E+10 |
September | 0.192874E+10 | 692135.30 | 0.192804E+10 | 0.161675E+10 | 0.229997E+10 |
October | 0.145380E+10 | 0.00 | 0.145380E+10 | 0.648207E+09 | 0.341601E+10 |
November | 0.956425E+09 | 0.00 | 0.956425E+09 | 0.157682E+09 | 0.476077E+10 |
December | 0.762255E+09 | 0.00 | 0.762255E+09 | 11834581.05 | 0.690943E+10 |
Annual Sum or Average | 0.241771E+11 | 0.985864E+09 | 0.231913E+11 | 0.170183E+11 | 0.461241E+11 |
Minimum of Months | 0.762255E+09 | 0.00 | 0.762255E+09 | 11834581.05 | 0.140176E+10 |
Maximum of Months | 0.351802E+10 | 0.404367E+09 | 0.311366E+10 | 0.396041E+10 | 0.818644E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139155E+10 | 0.637971E+09 | 0.753582E+09 | 0.708860E+09 | 0.500941E+10 |
February | 0.196588E+10 | 0.976014E+09 | 0.989869E+09 | 0.144206E+10 | 0.330626E+10 |
March | 0.292652E+10 | 0.121091E+10 | 0.171561E+10 | 0.232089E+10 | 0.298044E+10 |
April | 0.361350E+10 | 0.179082E+10 | 0.182268E+10 | 0.342561E+10 | 0.206831E+10 |
May | 0.412464E+10 | 0.183520E+10 | 0.228943E+10 | 0.418472E+10 | 0.169133E+10 |
June | 0.516659E+10 | 0.265872E+10 | 0.250786E+10 | 0.606849E+10 | 0.110745E+10 |
July | 0.560323E+10 | 0.316765E+10 | 0.243557E+10 | 0.714315E+10 | 0.936754E+09 |
August | 0.486945E+10 | 0.271311E+10 | 0.215634E+10 | 0.605449E+10 | 0.104741E+10 |
September | 0.333354E+10 | 0.172076E+10 | 0.161278E+10 | 0.374100E+10 | 0.144400E+10 |
October | 0.247136E+10 | 0.125492E+10 | 0.121644E+10 | 0.230487E+10 | 0.213672E+10 |
November | 0.151578E+10 | 0.707668E+09 | 0.808108E+09 | 0.103587E+10 | 0.289589E+10 |
December | 0.115524E+10 | 0.496178E+09 | 0.659061E+09 | 0.554220E+09 | 0.422316E+10 |
Annual Sum or Average | 0.381373E+11 | 0.191699E+11 | 0.189673E+11 | 0.389842E+11 | 0.288471E+11 |
Minimum of Months | 0.115524E+10 | 0.496178E+09 | 0.659061E+09 | 0.554220E+09 | 0.936754E+09 |
Maximum of Months | 0.560323E+10 | 0.316765E+10 | 0.250786E+10 | 0.714315E+10 | 0.500941E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.640749E+10 | 0.457636E+10 | 0.183113E+10 | 0.579604E+10 | 0.698232E+10 |
February | 0.737018E+10 | 0.530091E+10 | 0.206927E+10 | 0.739372E+10 | 0.469262E+10 |
March | 0.729384E+10 | 0.409588E+10 | 0.319795E+10 | 0.728004E+10 | 0.463079E+10 |
April | 0.567389E+10 | 0.271386E+10 | 0.296003E+10 | 0.590173E+10 | 0.333976E+10 |
May | 0.520915E+10 | 0.173010E+10 | 0.347905E+10 | 0.549171E+10 | 0.274825E+10 |
June | 0.500885E+10 | 0.146082E+10 | 0.354803E+10 | 0.606797E+10 | 0.187359E+10 |
July | 0.558004E+10 | 0.206125E+10 | 0.351879E+10 | 0.761194E+10 | 0.154343E+10 |
August | 0.663152E+10 | 0.334349E+10 | 0.328803E+10 | 0.877897E+10 | 0.172349E+10 |
September | 0.711789E+10 | 0.436136E+10 | 0.275653E+10 | 0.870011E+10 | 0.233798E+10 |
October | 0.768941E+10 | 0.531713E+10 | 0.237228E+10 | 0.860788E+10 | 0.332538E+10 |
November | 0.678432E+10 | 0.491429E+10 | 0.187003E+10 | 0.690696E+10 | 0.415617E+10 |
December | 0.609317E+10 | 0.439988E+10 | 0.169328E+10 | 0.567934E+10 | 0.587506E+10 |
Annual Sum or Average | 0.768598E+11 | 0.442753E+11 | 0.325844E+11 | 0.842164E+11 | 0.432288E+11 |
Minimum of Months | 0.500885E+10 | 0.146082E+10 | 0.169328E+10 | 0.549171E+10 | 0.154343E+10 |
Maximum of Months | 0.768941E+10 | 0.531713E+10 | 0.354803E+10 | 0.877897E+10 | 0.698232E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126045E+10 | 0.507971E+09 | 0.752480E+09 | 0.620129E+09 | 0.523815E+10 |
February | 0.194320E+10 | 0.955182E+09 | 0.988019E+09 | 0.145049E+10 | 0.339759E+10 |
March | 0.275327E+10 | 0.100884E+10 | 0.174443E+10 | 0.213139E+10 | 0.313098E+10 |
April | 0.347846E+10 | 0.154112E+10 | 0.193734E+10 | 0.333742E+10 | 0.219534E+10 |
May | 0.444603E+10 | 0.202763E+10 | 0.241840E+10 | 0.466729E+10 | 0.180628E+10 |
June | 0.468107E+10 | 0.215019E+10 | 0.253088E+10 | 0.552779E+10 | 0.122782E+10 |
July | 0.495508E+10 | 0.250387E+10 | 0.245120E+10 | 0.640027E+10 | 0.105998E+10 |
August | 0.420753E+10 | 0.206497E+10 | 0.214256E+10 | 0.528124E+10 | 0.113944E+10 |
September | 0.327551E+10 | 0.165596E+10 | 0.161954E+10 | 0.375526E+10 | 0.155228E+10 |
October | 0.241913E+10 | 0.120193E+10 | 0.121719E+10 | 0.232307E+10 | 0.226163E+10 |
November | 0.165727E+10 | 0.822147E+09 | 0.835122E+09 | 0.127748E+10 | 0.302343E+10 |
December | 0.115112E+10 | 0.485855E+09 | 0.665265E+09 | 0.593830E+09 | 0.436470E+10 |
Annual Sum or Average | 0.362281E+11 | 0.169257E+11 | 0.193024E+11 | 0.373657E+11 | 0.303976E+11 |
Minimum of Months | 0.115112E+10 | 0.485855E+09 | 0.665265E+09 | 0.593830E+09 | 0.105998E+10 |
Maximum of Months | 0.495508E+10 | 0.250387E+10 | 0.253088E+10 | 0.640027E+10 | 0.523815E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302988E+09 | 0.00 | 0.302988E+09 | 7662462.08 | 0.275661E+10 |
February | 0.386400E+09 | 0.00 | 0.386400E+09 | 62496413.91 | 0.183229E+10 |
March | 0.694943E+09 | 0.00 | 0.694943E+09 | 0.238779E+09 | 0.160763E+10 |
April | 0.766822E+09 | 4474999.60 | 0.762347E+09 | 0.422242E+09 | 0.107353E+10 |
May | 0.104059E+10 | 61661249.44 | 0.978926E+09 | 0.782405E+09 | 0.842613E+09 |
June | 0.117262E+10 | 0.134783E+09 | 0.103784E+10 | 0.119035E+10 | 0.535093E+09 |
July | 0.110696E+10 | 0.103680E+09 | 0.100328E+10 | 0.134304E+10 | 0.464833E+09 |
August | 0.887013E+09 | 23776086.76 | 0.863237E+09 | 0.971172E+09 | 0.538565E+09 |
September | 0.642882E+09 | 230700.85 | 0.642651E+09 | 0.541522E+09 | 0.807058E+09 |
October | 0.484576E+09 | 0.00 | 0.484576E+09 | 0.201416E+09 | 0.123349E+10 |
November | 0.318793E+09 | 0.00 | 0.318793E+09 | 45770645.67 | 0.169274E+10 |
December | 0.254073E+09 | 0.00 | 0.254073E+09 | 4010982.29 | 0.238319E+10 |
Annual Sum or Average | 0.805866E+10 | 0.328606E+09 | 0.773005E+10 | 0.581087E+10 | 0.157676E+11 |
Minimum of Months | 0.254073E+09 | 0.00 | 0.254073E+09 | 4010982.29 | 0.464833E+09 |
Maximum of Months | 0.117262E+10 | 0.134783E+09 | 0.103784E+10 | 0.134304E+10 | 0.275661E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.303000E+09 | 0.00 | 0.303000E+09 | 7662000.48 | 0.275678E+10 |
February | 0.386416E+09 | 0.00 | 0.386416E+09 | 62496563.79 | 0.183241E+10 |
March | 0.694970E+09 | 0.00 | 0.694970E+09 | 0.238780E+09 | 0.160773E+10 |
April | 0.766852E+09 | 4475119.89 | 0.762377E+09 | 0.422253E+09 | 0.107359E+10 |
May | 0.104063E+10 | 61662906.91 | 0.978965E+09 | 0.782426E+09 | 0.842666E+09 |
June | 0.117267E+10 | 0.134786E+09 | 0.103788E+10 | 0.119039E+10 | 0.535126E+09 |
July | 0.110701E+10 | 0.103683E+09 | 0.100332E+10 | 0.134310E+10 | 0.464859E+09 |
August | 0.887050E+09 | 23776725.87 | 0.863273E+09 | 0.971213E+09 | 0.538596E+09 |
September | 0.642908E+09 | 230707.05 | 0.642677E+09 | 0.541542E+09 | 0.807107E+09 |
October | 0.484596E+09 | 0.00 | 0.484596E+09 | 0.201419E+09 | 0.123356E+10 |
November | 0.318806E+09 | 0.00 | 0.318806E+09 | 45770317.66 | 0.169284E+10 |
December | 0.254083E+09 | 0.00 | 0.254083E+09 | 4010693.02 | 0.238334E+10 |
Annual Sum or Average | 0.805898E+10 | 0.328615E+09 | 0.773036E+10 | 0.581106E+10 | 0.157686E+11 |
Minimum of Months | 0.254083E+09 | 0.00 | 0.254083E+09 | 4010693.02 | 0.464859E+09 |
Maximum of Months | 0.117267E+10 | 0.134786E+09 | 0.103788E+10 | 0.134310E+10 | 0.275678E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.303000E+09 | 0.00 | 0.303000E+09 | 7662000.48 | 0.275678E+10 |
February | 0.386416E+09 | 0.00 | 0.386416E+09 | 62496563.79 | 0.183241E+10 |
March | 0.694970E+09 | 0.00 | 0.694970E+09 | 0.238780E+09 | 0.160773E+10 |
April | 0.766852E+09 | 4475119.89 | 0.762377E+09 | 0.422253E+09 | 0.107359E+10 |
May | 0.104063E+10 | 61662906.91 | 0.978965E+09 | 0.782426E+09 | 0.842666E+09 |
June | 0.117267E+10 | 0.134786E+09 | 0.103788E+10 | 0.119039E+10 | 0.535126E+09 |
July | 0.110701E+10 | 0.103683E+09 | 0.100332E+10 | 0.134310E+10 | 0.464859E+09 |
August | 0.887050E+09 | 23776725.87 | 0.863273E+09 | 0.971213E+09 | 0.538596E+09 |
September | 0.642908E+09 | 230707.05 | 0.642677E+09 | 0.541542E+09 | 0.807107E+09 |
October | 0.484596E+09 | 0.00 | 0.484596E+09 | 0.201419E+09 | 0.123356E+10 |
November | 0.318806E+09 | 0.00 | 0.318806E+09 | 45770317.66 | 0.169284E+10 |
December | 0.254083E+09 | 0.00 | 0.254083E+09 | 4010693.02 | 0.238334E+10 |
Annual Sum or Average | 0.805898E+10 | 0.328615E+09 | 0.773036E+10 | 0.581106E+10 | 0.157686E+11 |
Minimum of Months | 0.254083E+09 | 0.00 | 0.254083E+09 | 4010693.02 | 0.464859E+09 |
Maximum of Months | 0.117267E+10 | 0.134786E+09 | 0.103788E+10 | 0.134310E+10 | 0.275678E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133860E+10 | 0.613693E+09 | 0.724910E+09 | 0.681729E+09 | 0.489396E+10 |
February | 0.189108E+10 | 0.938873E+09 | 0.952207E+09 | 0.139129E+10 | 0.325950E+10 |
March | 0.281516E+10 | 0.116483E+10 | 0.165033E+10 | 0.226327E+10 | 0.294917E+10 |
April | 0.347601E+10 | 0.172268E+10 | 0.175333E+10 | 0.334580E+10 | 0.204152E+10 |
May | 0.396769E+10 | 0.176537E+10 | 0.220233E+10 | 0.407846E+10 | 0.168496E+10 |
June | 0.496999E+10 | 0.255755E+10 | 0.241245E+10 | 0.587920E+10 | 0.110206E+10 |
July | 0.539002E+10 | 0.304711E+10 | 0.234291E+10 | 0.690268E+10 | 0.947631E+09 |
August | 0.468417E+10 | 0.260986E+10 | 0.207430E+10 | 0.584351E+10 | 0.107252E+10 |
September | 0.320670E+10 | 0.165528E+10 | 0.155142E+10 | 0.359301E+10 | 0.151294E+10 |
October | 0.237733E+10 | 0.120717E+10 | 0.117016E+10 | 0.217370E+10 | 0.227568E+10 |
November | 0.145810E+10 | 0.680739E+09 | 0.777361E+09 | 0.960842E+09 | 0.300175E+10 |
December | 0.111128E+10 | 0.477296E+09 | 0.633985E+09 | 0.524778E+09 | 0.422180E+10 |
Annual Sum or Average | 0.366861E+11 | 0.184404E+11 | 0.182457E+11 | 0.376383E+11 | 0.289635E+11 |
Minimum of Months | 0.111128E+10 | 0.477296E+09 | 0.633985E+09 | 0.524778E+09 | 0.947631E+09 |
Maximum of Months | 0.539002E+10 | 0.304711E+10 | 0.241245E+10 | 0.690268E+10 | 0.489396E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52927167.64 | 24264883.73 | 28662283.91 | 26954969.40 | 0.193503E+09 |
February | 74771572.24 | 37122182.26 | 37649389.99 | 55010517.34 | 0.128878E+09 |
March | 0.111309E+09 | 46056402.48 | 65252643.09 | 89487531.46 | 0.116607E+09 |
April | 0.137438E+09 | 68113079.73 | 69325033.87 | 0.132290E+09 | 80719723.02 |
May | 0.156879E+09 | 69801028.93 | 87077951.22 | 0.161258E+09 | 66621853.26 |
June | 0.196509E+09 | 0.101123E+09 | 95386044.30 | 0.232458E+09 | 43574560.21 |
July | 0.213117E+09 | 0.120480E+09 | 92636517.15 | 0.272926E+09 | 37468463.74 |
August | 0.185208E+09 | 0.103192E+09 | 82016115.23 | 0.231047E+09 | 42406380.29 |
September | 0.126790E+09 | 65448262.81 | 61341707.84 | 0.142064E+09 | 59820316.05 |
October | 93997321.50 | 47730217.26 | 46267104.23 | 85946001.79 | 89978383.56 |
November | 57651956.98 | 26915793.88 | 30736163.10 | 37990846.80 | 0.118686E+09 |
December | 43939043.72 | 18871857.87 | 25067185.85 | 20749260.67 | 0.166926E+09 |
Annual Sum or Average | 0.145054E+10 | 0.729118E+09 | 0.721418E+09 | 0.148818E+10 | 0.114519E+10 |
Minimum of Months | 43939043.72 | 18871857.87 | 25067185.85 | 20749260.67 | 37468463.74 |
Maximum of Months | 0.213117E+09 | 0.120480E+09 | 95386044.30 | 0.272926E+09 | 0.193503E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213579E+10 | 0.152542E+10 | 0.610369E+09 | 0.196192E+10 | 0.236173E+10 |
February | 0.245668E+10 | 0.176693E+10 | 0.689748E+09 | 0.249727E+10 | 0.163270E+10 |
March | 0.243124E+10 | 0.136527E+10 | 0.106597E+10 | 0.246679E+10 | 0.160760E+10 |
April | 0.189127E+10 | 0.904601E+09 | 0.986668E+09 | 0.200649E+10 | 0.114298E+10 |
May | 0.173636E+10 | 0.576688E+09 | 0.115967E+10 | 0.187670E+10 | 0.933732E+09 |
June | 0.166960E+10 | 0.486930E+09 | 0.118267E+10 | 0.206068E+10 | 0.628987E+09 |
July | 0.185999E+10 | 0.687070E+09 | 0.117292E+10 | 0.256127E+10 | 0.531208E+09 |
August | 0.221047E+10 | 0.111447E+10 | 0.109600E+10 | 0.294557E+10 | 0.609350E+09 |
September | 0.237259E+10 | 0.145376E+10 | 0.918833E+09 | 0.291219E+10 | 0.859330E+09 |
October | 0.256309E+10 | 0.177234E+10 | 0.790751E+09 | 0.286715E+10 | 0.125178E+10 |
November | 0.226140E+10 | 0.163806E+10 | 0.623335E+09 | 0.229479E+10 | 0.152151E+10 |
December | 0.203102E+10 | 0.146660E+10 | 0.564419E+09 | 0.190119E+10 | 0.204797E+10 |
Annual Sum or Average | 0.256195E+11 | 0.147581E+11 | 0.108614E+11 | 0.283520E+11 | 0.151289E+11 |
Minimum of Months | 0.166960E+10 | 0.486930E+09 | 0.564419E+09 | 0.187670E+10 | 0.531208E+09 |
Maximum of Months | 0.256309E+10 | 0.177234E+10 | 0.118267E+10 | 0.294557E+10 | 0.236173E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213579E+10 | 0.152542E+10 | 0.610369E+09 | 0.196192E+10 | 0.236173E+10 |
February | 0.245668E+10 | 0.176693E+10 | 0.689748E+09 | 0.249727E+10 | 0.163270E+10 |
March | 0.243124E+10 | 0.136527E+10 | 0.106597E+10 | 0.246679E+10 | 0.160760E+10 |
April | 0.189127E+10 | 0.904601E+09 | 0.986668E+09 | 0.200649E+10 | 0.114298E+10 |
May | 0.173636E+10 | 0.576688E+09 | 0.115967E+10 | 0.187670E+10 | 0.933732E+09 |
June | 0.166960E+10 | 0.486930E+09 | 0.118267E+10 | 0.206068E+10 | 0.628987E+09 |
July | 0.185999E+10 | 0.687070E+09 | 0.117292E+10 | 0.256127E+10 | 0.531208E+09 |
August | 0.221047E+10 | 0.111447E+10 | 0.109600E+10 | 0.294557E+10 | 0.609350E+09 |
September | 0.237259E+10 | 0.145376E+10 | 0.918833E+09 | 0.291219E+10 | 0.859330E+09 |
October | 0.256309E+10 | 0.177234E+10 | 0.790751E+09 | 0.286715E+10 | 0.125178E+10 |
November | 0.226140E+10 | 0.163806E+10 | 0.623335E+09 | 0.229479E+10 | 0.152151E+10 |
December | 0.203102E+10 | 0.146660E+10 | 0.564419E+09 | 0.190119E+10 | 0.204797E+10 |
Annual Sum or Average | 0.256195E+11 | 0.147581E+11 | 0.108614E+11 | 0.283520E+11 | 0.151289E+11 |
Minimum of Months | 0.166960E+10 | 0.486930E+09 | 0.564419E+09 | 0.187670E+10 | 0.531208E+09 |
Maximum of Months | 0.256309E+10 | 0.177234E+10 | 0.118267E+10 | 0.294557E+10 | 0.236173E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213566E+10 | 0.152533E+10 | 0.610330E+09 | 0.196180E+10 | 0.236159E+10 |
February | 0.245653E+10 | 0.176682E+10 | 0.689705E+09 | 0.249711E+10 | 0.163259E+10 |
March | 0.243108E+10 | 0.136518E+10 | 0.106590E+10 | 0.246663E+10 | 0.160750E+10 |
April | 0.189115E+10 | 0.904544E+09 | 0.986605E+09 | 0.200636E+10 | 0.114291E+10 |
May | 0.173625E+10 | 0.576652E+09 | 0.115960E+10 | 0.187658E+10 | 0.933673E+09 |
June | 0.166949E+10 | 0.486899E+09 | 0.118259E+10 | 0.206055E+10 | 0.628947E+09 |
July | 0.185987E+10 | 0.687026E+09 | 0.117285E+10 | 0.256111E+10 | 0.531175E+09 |
August | 0.221033E+10 | 0.111440E+10 | 0.109593E+10 | 0.294538E+10 | 0.609312E+09 |
September | 0.237244E+10 | 0.145366E+10 | 0.918775E+09 | 0.291200E+10 | 0.859275E+09 |
October | 0.256293E+10 | 0.177223E+10 | 0.790701E+09 | 0.286697E+10 | 0.125170E+10 |
November | 0.226126E+10 | 0.163796E+10 | 0.623296E+09 | 0.229464E+10 | 0.152142E+10 |
December | 0.203089E+10 | 0.146650E+10 | 0.564384E+09 | 0.190107E+10 | 0.204784E+10 |
Annual Sum or Average | 0.256179E+11 | 0.147572E+11 | 0.108607E+11 | 0.283502E+11 | 0.151279E+11 |
Minimum of Months | 0.166949E+10 | 0.486899E+09 | 0.564384E+09 | 0.187658E+10 | 0.531175E+09 |
Maximum of Months | 0.256293E+10 | 0.177223E+10 | 0.118259E+10 | 0.294538E+10 | 0.236159E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121249E+10 | 0.488643E+09 | 0.723851E+09 | 0.605312E+09 | 0.509997E+10 |
February | 0.186927E+10 | 0.918836E+09 | 0.950429E+09 | 0.141703E+10 | 0.335427E+10 |
March | 0.264851E+10 | 0.970452E+09 | 0.167806E+10 | 0.209919E+10 | 0.308613E+10 |
April | 0.334611E+10 | 0.148248E+10 | 0.186363E+10 | 0.327301E+10 | 0.215575E+10 |
May | 0.427686E+10 | 0.195047E+10 | 0.232639E+10 | 0.454973E+10 | 0.180647E+10 |
June | 0.450297E+10 | 0.206837E+10 | 0.243459E+10 | 0.536331E+10 | 0.122382E+10 |
July | 0.476655E+10 | 0.240860E+10 | 0.235795E+10 | 0.618639E+10 | 0.107124E+10 |
August | 0.404744E+10 | 0.198639E+10 | 0.206105E+10 | 0.509662E+10 | 0.116401E+10 |
September | 0.315088E+10 | 0.159295E+10 | 0.155793E+10 | 0.361131E+10 | 0.162607E+10 |
October | 0.232708E+10 | 0.115620E+10 | 0.117088E+10 | 0.220572E+10 | 0.240061E+10 |
November | 0.159421E+10 | 0.790863E+09 | 0.803349E+09 | 0.121499E+10 | 0.312907E+10 |
December | 0.110732E+10 | 0.467368E+09 | 0.639954E+09 | 0.573486E+09 | 0.435684E+10 |
Annual Sum or Average | 0.348497E+11 | 0.162816E+11 | 0.185681E+11 | 0.361961E+11 | 0.304743E+11 |
Minimum of Months | 0.110732E+10 | 0.467368E+09 | 0.639954E+09 | 0.573486E+09 | 0.107124E+10 |
Maximum of Months | 0.476655E+10 | 0.240860E+10 | 0.243459E+10 | 0.618639E+10 | 0.509997E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 47940791.39 | 19320428.56 | 28620362.83 | 23933389.16 | 0.201648E+09 |
February | 73908879.09 | 36329845.25 | 37579033.83 | 56027788.13 | 0.132625E+09 |
March | 0.104720E+09 | 38370693.06 | 66348889.56 | 82999939.15 | 0.122023E+09 |
April | 0.132302E+09 | 58615649.48 | 73686259.38 | 0.129412E+09 | 85236396.08 |
May | 0.169103E+09 | 77119687.82 | 91983232.37 | 0.179892E+09 | 71426241.04 |
June | 0.178043E+09 | 81781373.99 | 96261424.93 | 0.212060E+09 | 48388743.71 |
July | 0.188465E+09 | 95233511.60 | 93231038.90 | 0.244604E+09 | 42355812.44 |
August | 0.160032E+09 | 78539908.25 | 81491891.64 | 0.201515E+09 | 46023832.57 |
September | 0.124583E+09 | 62983752.76 | 61599007.06 | 0.142787E+09 | 64293366.98 |
October | 92010501.44 | 45714899.29 | 46295602.16 | 87212056.16 | 94917800.83 |
November | 63033538.01 | 31269916.93 | 31763621.08 | 48039231.67 | 0.123721E+09 |
December | 43782396.77 | 18479253.60 | 25303143.16 | 22675010.12 | 0.172266E+09 |
Annual Sum or Average | 0.137792E+10 | 0.643759E+09 | 0.734164E+09 | 0.143116E+10 | 0.120492E+10 |
Minimum of Months | 43782396.77 | 18479253.60 | 25303143.16 | 22675010.12 | 42355812.44 |
Maximum of Months | 0.188465E+09 | 95233511.60 | 96261424.93 | 0.244604E+09 | 0.201648E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.909008E+09 | 0.00 | 0.909008E+09 | 21283910.01 | 0.838868E+10 |
February | 0.115926E+10 | 0.00 | 0.115926E+10 | 0.165683E+09 | 0.562212E+10 |
March | 0.208493E+10 | 0.00 | 0.208493E+10 | 0.633345E+09 | 0.500127E+10 |
April | 0.230057E+10 | 13425633.98 | 0.228715E+10 | 0.112062E+10 | 0.344683E+10 |
May | 0.312191E+10 | 0.184993E+09 | 0.293692E+10 | 0.217801E+10 | 0.266773E+10 |
June | 0.351802E+10 | 0.404367E+09 | 0.311366E+10 | 0.345473E+10 | 0.168020E+10 |
July | 0.332104E+10 | 0.311055E+09 | 0.300998E+10 | 0.395219E+10 | 0.144596E+10 |
August | 0.266116E+10 | 71331635.12 | 0.258983E+10 | 0.285754E+10 | 0.166408E+10 |
September | 0.192874E+10 | 692135.30 | 0.192804E+10 | 0.158425E+10 | 0.245005E+10 |
October | 0.145380E+10 | 0.00 | 0.145380E+10 | 0.587429E+09 | 0.368099E+10 |
November | 0.956425E+09 | 0.00 | 0.956425E+09 | 0.131385E+09 | 0.505977E+10 |
December | 0.762255E+09 | 0.00 | 0.762255E+09 | 10322970.05 | 0.716345E+10 |
Annual Sum or Average | 0.241771E+11 | 0.985864E+09 | 0.231913E+11 | 0.166968E+11 | 0.482711E+11 |
Minimum of Months | 0.762255E+09 | 0.00 | 0.762255E+09 | 10322970.05 | 0.144596E+10 |
Maximum of Months | 0.351802E+10 | 0.404367E+09 | 0.311366E+10 | 0.395219E+10 | 0.838868E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139155E+10 | 0.637971E+09 | 0.753582E+09 | 0.693862E+09 | 0.513137E+10 |
February | 0.196588E+10 | 0.976014E+09 | 0.989869E+09 | 0.141252E+10 | 0.343219E+10 |
March | 0.292652E+10 | 0.121091E+10 | 0.171561E+10 | 0.228588E+10 | 0.312098E+10 |
April | 0.361350E+10 | 0.179082E+10 | 0.182268E+10 | 0.339585E+10 | 0.218313E+10 |
May | 0.412464E+10 | 0.183520E+10 | 0.228943E+10 | 0.416520E+10 | 0.177917E+10 |
June | 0.516659E+10 | 0.265872E+10 | 0.250786E+10 | 0.606261E+10 | 0.114544E+10 |
July | 0.560323E+10 | 0.316765E+10 | 0.243557E+10 | 0.714666E+10 | 0.964471E+09 |
August | 0.486945E+10 | 0.271311E+10 | 0.215634E+10 | 0.605123E+10 | 0.108881E+10 |
September | 0.333354E+10 | 0.172076E+10 | 0.161278E+10 | 0.372166E+10 | 0.152403E+10 |
October | 0.247136E+10 | 0.125492E+10 | 0.121644E+10 | 0.225729E+10 | 0.228606E+10 |
November | 0.151578E+10 | 0.707668E+09 | 0.808108E+09 | 0.996084E+09 | 0.306830E+10 |
December | 0.115524E+10 | 0.496178E+09 | 0.659061E+09 | 0.537957E+09 | 0.437990E+10 |
Annual Sum or Average | 0.381373E+11 | 0.191699E+11 | 0.189673E+11 | 0.387268E+11 | 0.301039E+11 |
Minimum of Months | 0.115524E+10 | 0.496178E+09 | 0.659061E+09 | 0.537957E+09 | 0.964471E+09 |
Maximum of Months | 0.560323E+10 | 0.316765E+10 | 0.250786E+10 | 0.714666E+10 | 0.513137E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.640749E+10 | 0.457636E+10 | 0.183113E+10 | 0.575902E+10 | 0.717966E+10 |
February | 0.737018E+10 | 0.530091E+10 | 0.206927E+10 | 0.734716E+10 | 0.489351E+10 |
March | 0.729384E+10 | 0.409588E+10 | 0.319795E+10 | 0.723576E+10 | 0.485847E+10 |
April | 0.567389E+10 | 0.271386E+10 | 0.296003E+10 | 0.586423E+10 | 0.353359E+10 |
May | 0.520915E+10 | 0.173010E+10 | 0.347905E+10 | 0.546646E+10 | 0.290115E+10 |
June | 0.500885E+10 | 0.146082E+10 | 0.354803E+10 | 0.606071E+10 | 0.195592E+10 |
July | 0.558004E+10 | 0.206125E+10 | 0.351879E+10 | 0.761487E+10 | 0.160258E+10 |
August | 0.663152E+10 | 0.334349E+10 | 0.328803E+10 | 0.877801E+10 | 0.180411E+10 |
September | 0.711789E+10 | 0.436136E+10 | 0.275653E+10 | 0.868134E+10 | 0.247726E+10 |
October | 0.768941E+10 | 0.531713E+10 | 0.237228E+10 | 0.854955E+10 | 0.356072E+10 |
November | 0.678432E+10 | 0.491429E+10 | 0.187003E+10 | 0.682995E+10 | 0.441325E+10 |
December | 0.609317E+10 | 0.439988E+10 | 0.169328E+10 | 0.562343E+10 | 0.611658E+10 |
Annual Sum or Average | 0.768598E+11 | 0.442753E+11 | 0.325844E+11 | 0.838105E+11 | 0.452968E+11 |
Minimum of Months | 0.500885E+10 | 0.146082E+10 | 0.169328E+10 | 0.546646E+10 | 0.160258E+10 |
Maximum of Months | 0.768941E+10 | 0.531713E+10 | 0.354803E+10 | 0.877801E+10 | 0.717966E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126045E+10 | 0.507971E+09 | 0.752480E+09 | 0.612314E+09 | 0.536290E+10 |
February | 0.194320E+10 | 0.955182E+09 | 0.988019E+09 | 0.143271E+10 | 0.353436E+10 |
March | 0.275327E+10 | 0.100884E+10 | 0.174443E+10 | 0.210992E+10 | 0.328142E+10 |
April | 0.347846E+10 | 0.154112E+10 | 0.193734E+10 | 0.331163E+10 | 0.232136E+10 |
May | 0.444603E+10 | 0.202763E+10 | 0.241840E+10 | 0.465097E+10 | 0.190564E+10 |
June | 0.468107E+10 | 0.215019E+10 | 0.253088E+10 | 0.552085E+10 | 0.128071E+10 |
July | 0.495508E+10 | 0.250387E+10 | 0.245120E+10 | 0.639969E+10 | 0.109865E+10 |
August | 0.420753E+10 | 0.206497E+10 | 0.214256E+10 | 0.527313E+10 | 0.119247E+10 |
September | 0.327551E+10 | 0.165596E+10 | 0.161954E+10 | 0.373705E+10 | 0.164822E+10 |
October | 0.241913E+10 | 0.120193E+10 | 0.121719E+10 | 0.228511E+10 | 0.242605E+10 |
November | 0.165727E+10 | 0.822147E+09 | 0.835122E+09 | 0.125032E+10 | 0.320614E+10 |
December | 0.115112E+10 | 0.485855E+09 | 0.665265E+09 | 0.582733E+09 | 0.452493E+10 |
Annual Sum or Average | 0.362281E+11 | 0.169257E+11 | 0.193024E+11 | 0.371664E+11 | 0.317829E+11 |
Minimum of Months | 0.115112E+10 | 0.485855E+09 | 0.665265E+09 | 0.582733E+09 | 0.109865E+10 |
Maximum of Months | 0.495508E+10 | 0.250387E+10 | 0.253088E+10 | 0.639969E+10 | 0.536290E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.31 | 3056.47 | 339.38 | 0.00 | 339.38 | 0.00 | 0.00 |
February | 77.94 | 2237.00 | 479.19 | 0.00 | 479.19 | 0.00 | 0.00 |
March | 251.04 | 1779.84 | 778.42 | 0.00 | 778.42 | 0.00 | 0.00 |
April | 449.71 | 1251.88 | 887.57 | 5.18 | 882.39 | 0.00 | 0.00 |
May | 827.90 | 940.77 | 1165.59 | 69.07 | 1096.52 | 0.00 | 0.00 |
June | 1342.17 | 623.59 | 1357.26 | 156.01 | 1201.26 | 0.00 | 0.00 |
July | 1478.65 | 523.36 | 1239.93 | 116.13 | 1123.80 | 0.00 | 0.00 |
August | 1072.60 | 593.59 | 993.57 | 26.63 | 966.93 | 0.00 | 0.00 |
September | 623.75 | 887.34 | 744.11 | 0.27 | 743.84 | 0.00 | 0.00 |
October | 242.01 | 1275.39 | 542.79 | 0.00 | 542.79 | 0.00 | 0.00 |
November | 60.83 | 1836.72 | 368.99 | 0.00 | 368.99 | 0.00 | 0.00 |
December | 4.42 | 2579.69 | 284.59 | 0.00 | 284.59 | 0.00 | 0.00 |
Annual Sum or Average | 539.65 | 1462.59 | 766.65 | 31.26 | 735.39 | 0.00 | 0.00 |
Minimum of Months | 4.42 | 523.36 | 284.59 | 0.00 | 284.59 | 0.00 | 0.00 |
Maximum of Months | 1478.65 | 3056.47 | 1357.26 | 156.01 | 1201.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 264.66 | 1870.30 | 519.55 | 238.19 | 281.36 | 0.00 | 0.00 |
February | 596.09 | 1366.67 | 812.62 | 403.44 | 409.17 | 0.00 | 0.00 |
March | 866.52 | 1112.77 | 1092.64 | 452.10 | 640.53 | 0.00 | 0.00 |
April | 1321.61 | 797.96 | 1394.10 | 690.90 | 703.19 | 0.00 | 0.00 |
May | 1562.39 | 631.47 | 1539.96 | 685.19 | 854.78 | 0.00 | 0.00 |
June | 2341.24 | 427.26 | 1993.28 | 1025.74 | 967.54 | 0.00 | 0.00 |
July | 2666.95 | 349.74 | 2092.00 | 1182.67 | 909.34 | 0.00 | 0.00 |
August | 2260.49 | 391.06 | 1818.05 | 1012.96 | 805.09 | 0.00 | 0.00 |
September | 1443.29 | 557.10 | 1286.09 | 663.87 | 622.21 | 0.00 | 0.00 |
October | 860.54 | 797.76 | 922.70 | 468.53 | 454.17 | 0.00 | 0.00 |
November | 399.64 | 1117.24 | 584.79 | 273.02 | 311.77 | 0.00 | 0.00 |
December | 206.92 | 1576.75 | 431.32 | 185.25 | 246.07 | 0.00 | 0.00 |
Annual Sum or Average | 1236.18 | 914.74 | 1209.33 | 607.87 | 601.45 | 0.00 | 0.00 |
Minimum of Months | 206.92 | 349.74 | 431.32 | 185.25 | 246.07 | 0.00 | 0.00 |
Maximum of Months | 2666.95 | 1870.30 | 2092.00 | 1182.67 | 967.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2163.99 | 2606.90 | 2392.28 | 1708.62 | 683.67 | 0.00 | 0.00 |
February | 3056.27 | 1939.74 | 3046.54 | 2191.18 | 855.35 | 0.00 | 0.00 |
March | 2718.06 | 1728.94 | 2723.21 | 1529.23 | 1193.98 | 0.00 | 0.00 |
April | 2276.90 | 1288.49 | 2189.00 | 1047.01 | 1141.99 | 0.00 | 0.00 |
May | 2050.37 | 1026.08 | 1944.87 | 645.95 | 1298.93 | 0.00 | 0.00 |
June | 2341.04 | 722.84 | 1932.43 | 563.59 | 1368.84 | 0.00 | 0.00 |
July | 2841.97 | 576.25 | 2083.35 | 769.58 | 1313.77 | 0.00 | 0.00 |
August | 3277.69 | 643.48 | 2475.92 | 1248.32 | 1227.61 | 0.00 | 0.00 |
September | 3356.53 | 902.00 | 2746.10 | 1682.62 | 1063.47 | 0.00 | 0.00 |
October | 3213.82 | 1241.56 | 2870.90 | 1985.19 | 885.71 | 0.00 | 0.00 |
November | 2664.72 | 1603.46 | 2617.41 | 1895.95 | 721.46 | 0.00 | 0.00 |
December | 2120.42 | 2193.50 | 2274.93 | 1642.73 | 632.20 | 0.00 | 0.00 |
Annual Sum or Average | 2670.49 | 1370.78 | 2437.21 | 1403.96 | 1033.24 | 0.00 | 0.00 |
Minimum of Months | 2050.37 | 576.25 | 1932.43 | 563.59 | 632.20 | 0.00 | 0.00 |
Maximum of Months | 3356.53 | 2606.90 | 3046.54 | 2191.18 | 1368.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 231.53 | 1955.70 | 470.60 | 189.65 | 280.94 | 0.00 | 0.00 |
February | 599.57 | 1404.43 | 803.24 | 394.83 | 408.41 | 0.00 | 0.00 |
March | 795.77 | 1168.98 | 1027.95 | 376.66 | 651.30 | 0.00 | 0.00 |
April | 1287.59 | 846.97 | 1342.00 | 594.57 | 747.43 | 0.00 | 0.00 |
May | 1742.57 | 674.39 | 1659.96 | 757.03 | 902.93 | 0.00 | 0.00 |
June | 2132.64 | 473.69 | 1805.97 | 829.55 | 976.42 | 0.00 | 0.00 |
July | 2389.59 | 395.75 | 1850.01 | 934.84 | 915.17 | 0.00 | 0.00 |
August | 1971.79 | 425.42 | 1570.91 | 770.97 | 799.94 | 0.00 | 0.00 |
September | 1448.79 | 598.87 | 1263.70 | 638.88 | 624.82 | 0.00 | 0.00 |
October | 867.33 | 844.40 | 903.20 | 448.75 | 454.45 | 0.00 | 0.00 |
November | 492.86 | 1166.45 | 639.38 | 317.19 | 322.19 | 0.00 | 0.00 |
December | 221.71 | 1629.59 | 429.78 | 181.40 | 248.38 | 0.00 | 0.00 |
Annual Sum or Average | 1184.86 | 963.90 | 1148.79 | 536.71 | 612.08 | 0.00 | 0.00 |
Minimum of Months | 221.71 | 395.75 | 429.78 | 181.40 | 248.38 | 0.00 | 0.00 |
Maximum of Months | 2389.59 | 1955.70 | 1850.01 | 934.84 | 976.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8.58 | 3087.73 | 339.38 | 0.00 | 339.38 | 0.00 | 0.00 |
February | 77.50 | 2272.28 | 479.18 | 0.00 | 479.18 | 0.00 | 0.00 |
March | 267.45 | 1800.73 | 778.41 | 0.00 | 778.41 | 0.00 | 0.00 |
April | 488.71 | 1242.56 | 887.55 | 5.18 | 882.37 | 0.00 | 0.00 |
May | 876.37 | 943.83 | 1165.56 | 69.07 | 1096.50 | 0.00 | 0.00 |
June | 1377.75 | 619.35 | 1357.23 | 156.00 | 1201.23 | 0.00 | 0.00 |
July | 1504.35 | 520.67 | 1239.91 | 116.13 | 1123.78 | 0.00 | 0.00 |
August | 1087.81 | 603.25 | 993.55 | 26.63 | 966.91 | 0.00 | 0.00 |
September | 626.78 | 934.13 | 744.10 | 0.27 | 743.83 | 0.00 | 0.00 |
October | 225.60 | 1381.65 | 542.77 | 0.00 | 542.77 | 0.00 | 0.00 |
November | 52.98 | 1959.27 | 368.98 | 0.00 | 368.98 | 0.00 | 0.00 |
December | 4.49 | 2669.46 | 284.59 | 0.00 | 284.59 | 0.00 | 0.00 |
Annual Sum or Average | 552.80 | 1500.03 | 766.64 | 31.26 | 735.37 | 0.00 | 0.00 |
Minimum of Months | 4.49 | 520.67 | 284.59 | 0.00 | 284.59 | 0.00 | 0.00 |
Maximum of Months | 1504.35 | 3087.73 | 1357.23 | 156.00 | 1201.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 264.59 | 1899.44 | 519.54 | 238.19 | 281.35 | 0.00 | 0.00 |
February | 597.84 | 1400.62 | 812.60 | 403.44 | 409.17 | 0.00 | 0.00 |
March | 878.42 | 1144.63 | 1092.62 | 452.09 | 640.53 | 0.00 | 0.00 |
April | 1341.86 | 818.76 | 1394.08 | 690.89 | 703.18 | 0.00 | 0.00 |
May | 1582.93 | 653.97 | 1539.94 | 685.17 | 854.77 | 0.00 | 0.00 |
June | 2357.89 | 441.99 | 1993.25 | 1025.72 | 967.53 | 0.00 | 0.00 |
July | 2679.06 | 367.79 | 2091.97 | 1182.64 | 909.33 | 0.00 | 0.00 |
August | 2267.98 | 416.26 | 1818.02 | 1012.94 | 805.08 | 0.00 | 0.00 |
September | 1441.00 | 606.78 | 1286.07 | 663.86 | 622.21 | 0.00 | 0.00 |
October | 843.65 | 883.24 | 922.69 | 468.52 | 454.16 | 0.00 | 0.00 |
November | 385.35 | 1203.87 | 584.78 | 273.01 | 311.77 | 0.00 | 0.00 |
December | 203.68 | 1638.56 | 431.31 | 185.25 | 246.06 | 0.00 | 0.00 |
Annual Sum or Average | 1240.69 | 954.74 | 1209.31 | 607.86 | 601.44 | 0.00 | 0.00 |
Minimum of Months | 203.68 | 367.79 | 431.31 | 185.25 | 246.06 | 0.00 | 0.00 |
Maximum of Months | 2679.06 | 1899.44 | 2091.97 | 1182.64 | 967.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2197.45 | 2645.26 | 2392.19 | 1708.55 | 683.64 | 0.00 | 0.00 |
February | 3096.75 | 2024.63 | 3046.42 | 2191.09 | 855.32 | 0.00 | 0.00 |
March | 2762.92 | 1800.59 | 2723.10 | 1529.16 | 1193.94 | 0.00 | 0.00 |
April | 2322.28 | 1322.87 | 2188.92 | 1046.97 | 1141.95 | 0.00 | 0.00 |
May | 2101.99 | 1045.82 | 1944.81 | 645.92 | 1298.89 | 0.00 | 0.00 |
June | 2384.99 | 727.98 | 1932.36 | 563.56 | 1368.80 | 0.00 | 0.00 |
July | 2868.75 | 594.98 | 2083.28 | 769.55 | 1313.73 | 0.00 | 0.00 |
August | 3299.18 | 682.50 | 2475.84 | 1248.26 | 1227.57 | 0.00 | 0.00 |
September | 3370.52 | 994.57 | 2745.99 | 1682.55 | 1063.44 | 0.00 | 0.00 |
October | 3211.35 | 1402.05 | 2870.79 | 1985.11 | 885.68 | 0.00 | 0.00 |
November | 2655.95 | 1760.98 | 2617.30 | 1895.87 | 721.44 | 0.00 | 0.00 |
December | 2129.42 | 2293.82 | 2274.84 | 1642.66 | 632.18 | 0.00 | 0.00 |
Annual Sum or Average | 2697.05 | 1439.17 | 2437.12 | 1403.90 | 1033.21 | 0.00 | 0.00 |
Minimum of Months | 2101.99 | 594.98 | 1932.36 | 563.56 | 632.18 | 0.00 | 0.00 |
Maximum of Months | 3370.52 | 2645.26 | 3046.42 | 2191.09 | 1368.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 234.93 | 1979.40 | 470.59 | 189.65 | 280.94 | 0.00 | 0.00 |
February | 608.90 | 1441.34 | 803.23 | 394.83 | 408.40 | 0.00 | 0.00 |
March | 814.74 | 1197.79 | 1027.94 | 376.65 | 651.29 | 0.00 | 0.00 |
April | 1312.66 | 864.58 | 1341.98 | 594.56 | 747.42 | 0.00 | 0.00 |
May | 1765.84 | 701.13 | 1659.93 | 757.02 | 902.92 | 0.00 | 0.00 |
June | 2150.99 | 490.82 | 1805.95 | 829.54 | 976.41 | 0.00 | 0.00 |
July | 2401.06 | 415.77 | 1849.99 | 934.82 | 915.17 | 0.00 | 0.00 |
August | 1978.10 | 451.77 | 1570.89 | 770.96 | 799.93 | 0.00 | 0.00 |
September | 1448.34 | 652.15 | 1263.68 | 638.86 | 624.82 | 0.00 | 0.00 |
October | 856.08 | 931.72 | 903.19 | 448.74 | 454.44 | 0.00 | 0.00 |
November | 487.28 | 1254.94 | 639.37 | 317.18 | 322.19 | 0.00 | 0.00 |
December | 222.58 | 1690.98 | 429.77 | 181.39 | 248.38 | 0.00 | 0.00 |
Annual Sum or Average | 1193.15 | 1004.54 | 1148.77 | 536.70 | 612.07 | 0.00 | 0.00 |
Minimum of Months | 222.58 | 415.77 | 429.77 | 181.39 | 248.38 | 0.00 | 0.00 |
Maximum of Months | 2401.06 | 1979.40 | 1849.99 | 934.82 | 976.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.95 | 3131.97 | 339.38 | 0.00 | 339.38 | 0.00 | 0.00 |
February | 68.49 | 2323.96 | 479.19 | 0.00 | 479.19 | 0.00 | 0.00 |
March | 236.46 | 1867.26 | 778.42 | 0.00 | 778.42 | 0.00 | 0.00 |
April | 432.34 | 1329.80 | 887.57 | 5.18 | 882.39 | 0.00 | 0.00 |
May | 813.17 | 996.02 | 1165.59 | 69.07 | 1096.52 | 0.00 | 0.00 |
June | 1332.84 | 648.23 | 1357.26 | 156.01 | 1201.26 | 0.00 | 0.00 |
July | 1475.58 | 539.86 | 1239.93 | 116.13 | 1123.80 | 0.00 | 0.00 |
August | 1066.88 | 621.30 | 993.57 | 26.63 | 966.93 | 0.00 | 0.00 |
September | 611.21 | 945.23 | 744.11 | 0.27 | 743.84 | 0.00 | 0.00 |
October | 219.32 | 1374.32 | 542.79 | 0.00 | 542.79 | 0.00 | 0.00 |
November | 50.69 | 1952.07 | 368.99 | 0.00 | 368.99 | 0.00 | 0.00 |
December | 3.85 | 2674.53 | 284.59 | 0.00 | 284.59 | 0.00 | 0.00 |
Annual Sum or Average | 529.45 | 1530.67 | 766.65 | 31.26 | 735.39 | 0.00 | 0.00 |
Minimum of Months | 3.85 | 539.86 | 284.59 | 0.00 | 284.59 | 0.00 | 0.00 |
Maximum of Months | 1475.58 | 3131.97 | 1357.26 | 156.01 | 1201.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 259.06 | 1915.84 | 519.55 | 238.19 | 281.36 | 0.00 | 0.00 |
February | 583.88 | 1418.73 | 812.62 | 403.44 | 409.17 | 0.00 | 0.00 |
March | 853.45 | 1165.24 | 1092.64 | 452.10 | 640.53 | 0.00 | 0.00 |
April | 1310.13 | 842.26 | 1394.10 | 690.90 | 703.19 | 0.00 | 0.00 |
May | 1555.11 | 664.27 | 1539.96 | 685.19 | 854.78 | 0.00 | 0.00 |
June | 2338.97 | 441.91 | 1993.28 | 1025.74 | 967.54 | 0.00 | 0.00 |
July | 2668.26 | 360.09 | 2092.00 | 1182.67 | 909.34 | 0.00 | 0.00 |
August | 2259.27 | 406.51 | 1818.05 | 1012.96 | 805.09 | 0.00 | 0.00 |
September | 1435.83 | 587.97 | 1286.09 | 663.87 | 622.21 | 0.00 | 0.00 |
October | 842.78 | 853.52 | 922.70 | 468.53 | 454.17 | 0.00 | 0.00 |
November | 384.29 | 1183.76 | 584.79 | 273.02 | 311.77 | 0.00 | 0.00 |
December | 200.85 | 1635.27 | 431.32 | 185.25 | 246.07 | 0.00 | 0.00 |
Annual Sum or Average | 1228.02 | 954.59 | 1209.33 | 607.87 | 601.45 | 0.00 | 0.00 |
Minimum of Months | 200.85 | 360.09 | 431.32 | 185.25 | 246.07 | 0.00 | 0.00 |
Maximum of Months | 2668.26 | 1915.84 | 2092.00 | 1182.67 | 967.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2150.17 | 2680.58 | 2392.28 | 1708.62 | 683.67 | 0.00 | 0.00 |
February | 3037.02 | 2022.78 | 3046.54 | 2191.18 | 855.35 | 0.00 | 0.00 |
March | 2701.52 | 1813.94 | 2723.21 | 1529.23 | 1193.98 | 0.00 | 0.00 |
April | 2262.43 | 1363.27 | 2189.00 | 1047.01 | 1141.99 | 0.00 | 0.00 |
May | 2040.94 | 1083.17 | 1944.87 | 645.95 | 1298.93 | 0.00 | 0.00 |
June | 2338.24 | 754.60 | 1932.43 | 563.59 | 1368.84 | 0.00 | 0.00 |
July | 2843.07 | 598.34 | 2083.35 | 769.58 | 1313.77 | 0.00 | 0.00 |
August | 3277.33 | 673.58 | 2475.92 | 1248.32 | 1227.61 | 0.00 | 0.00 |
September | 3349.28 | 955.73 | 2746.10 | 1682.62 | 1063.47 | 0.00 | 0.00 |
October | 3192.04 | 1329.42 | 2870.90 | 1985.19 | 885.71 | 0.00 | 0.00 |
November | 2635.01 | 1702.64 | 2617.41 | 1895.95 | 721.46 | 0.00 | 0.00 |
December | 2099.55 | 2283.67 | 2274.93 | 1642.73 | 632.20 | 0.00 | 0.00 |
Annual Sum or Average | 2657.61 | 1436.35 | 2437.21 | 1403.96 | 1033.24 | 0.00 | 0.00 |
Minimum of Months | 2040.94 | 598.34 | 1932.43 | 563.59 | 632.20 | 0.00 | 0.00 |
Maximum of Months | 3349.28 | 2680.58 | 3046.54 | 2191.18 | 1368.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 228.61 | 2002.28 | 470.60 | 189.65 | 280.94 | 0.00 | 0.00 |
February | 592.23 | 1460.96 | 803.24 | 394.83 | 408.41 | 0.00 | 0.00 |
March | 787.75 | 1225.14 | 1027.95 | 376.66 | 651.30 | 0.00 | 0.00 |
April | 1277.64 | 895.59 | 1342.00 | 594.57 | 747.43 | 0.00 | 0.00 |
May | 1736.47 | 711.48 | 1659.96 | 757.03 | 902.93 | 0.00 | 0.00 |
June | 2129.96 | 494.10 | 1805.97 | 829.55 | 976.42 | 0.00 | 0.00 |
July | 2389.37 | 410.19 | 1850.01 | 934.84 | 915.17 | 0.00 | 0.00 |
August | 1968.76 | 445.22 | 1570.91 | 770.97 | 799.94 | 0.00 | 0.00 |
September | 1441.77 | 635.89 | 1263.70 | 638.88 | 624.82 | 0.00 | 0.00 |
October | 853.16 | 905.79 | 903.20 | 448.75 | 454.45 | 0.00 | 0.00 |
November | 482.37 | 1236.94 | 639.38 | 317.19 | 322.19 | 0.00 | 0.00 |
December | 217.57 | 1689.41 | 429.78 | 181.40 | 248.38 | 0.00 | 0.00 |
Annual Sum or Average | 1178.54 | 1007.83 | 1148.79 | 536.71 | 612.08 | 0.00 | 0.00 |
Minimum of Months | 217.57 | 410.19 | 429.78 | 181.40 | 248.38 | 0.00 | 0.00 |
Maximum of Months | 2389.37 | 2002.28 | 1850.01 | 934.84 | 976.42 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 27624492.45 | 0.818644E+10 | 0.909008E+09 | 0.00 | 0.909008E+09 | 0.00 | 0.00 |
February | 0.188550E+09 | 0.541174E+10 | 0.115926E+10 | 0.00 | 0.115926E+10 | 0.00 | 0.00 |
March | 0.672381E+09 | 0.476713E+10 | 0.208493E+10 | 0.00 | 0.208493E+10 | 0.00 | 0.00 |
April | 0.116565E+10 | 0.324487E+10 | 0.230057E+10 | 13425633.98 | 0.228715E+10 | 0.00 | 0.00 |
May | 0.221746E+10 | 0.251977E+10 | 0.312191E+10 | 0.184993E+09 | 0.293692E+10 | 0.00 | 0.00 |
June | 0.347890E+10 | 0.161635E+10 | 0.351802E+10 | 0.404367E+09 | 0.311366E+10 | 0.00 | 0.00 |
July | 0.396041E+10 | 0.140176E+10 | 0.332104E+10 | 0.311055E+09 | 0.300998E+10 | 0.00 | 0.00 |
August | 0.287284E+10 | 0.158986E+10 | 0.266116E+10 | 71331635.12 | 0.258983E+10 | 0.00 | 0.00 |
September | 0.161675E+10 | 0.229997E+10 | 0.192874E+10 | 692135.30 | 0.192804E+10 | 0.00 | 0.00 |
October | 0.648207E+09 | 0.341601E+10 | 0.145380E+10 | 0.00 | 0.145380E+10 | 0.00 | 0.00 |
November | 0.157682E+09 | 0.476077E+10 | 0.956425E+09 | 0.00 | 0.956425E+09 | 0.00 | 0.00 |
December | 11834581.05 | 0.690943E+10 | 0.762255E+09 | 0.00 | 0.762255E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170183E+11 | 0.461241E+11 | 0.241771E+11 | 0.985864E+09 | 0.231913E+11 | 0.00 | 0.00 |
Minimum of Months | 11834581.05 | 0.140176E+10 | 0.762255E+09 | 0.00 | 0.762255E+09 | 0.00 | 0.00 |
Maximum of Months | 0.396041E+10 | 0.818644E+10 | 0.351802E+10 | 0.404367E+09 | 0.311366E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.708860E+09 | 0.500941E+10 | 0.139155E+10 | 0.637971E+09 | 0.753582E+09 | 0.00 | 0.00 |
February | 0.144206E+10 | 0.330626E+10 | 0.196588E+10 | 0.976014E+09 | 0.989869E+09 | 0.00 | 0.00 |
March | 0.232089E+10 | 0.298044E+10 | 0.292652E+10 | 0.121091E+10 | 0.171561E+10 | 0.00 | 0.00 |
April | 0.342561E+10 | 0.206831E+10 | 0.361350E+10 | 0.179082E+10 | 0.182268E+10 | 0.00 | 0.00 |
May | 0.418472E+10 | 0.169133E+10 | 0.412464E+10 | 0.183520E+10 | 0.228943E+10 | 0.00 | 0.00 |
June | 0.606849E+10 | 0.110745E+10 | 0.516659E+10 | 0.265872E+10 | 0.250786E+10 | 0.00 | 0.00 |
July | 0.714315E+10 | 0.936754E+09 | 0.560323E+10 | 0.316765E+10 | 0.243557E+10 | 0.00 | 0.00 |
August | 0.605449E+10 | 0.104741E+10 | 0.486945E+10 | 0.271311E+10 | 0.215634E+10 | 0.00 | 0.00 |
September | 0.374100E+10 | 0.144400E+10 | 0.333354E+10 | 0.172076E+10 | 0.161278E+10 | 0.00 | 0.00 |
October | 0.230487E+10 | 0.213672E+10 | 0.247136E+10 | 0.125492E+10 | 0.121644E+10 | 0.00 | 0.00 |
November | 0.103587E+10 | 0.289589E+10 | 0.151578E+10 | 0.707668E+09 | 0.808108E+09 | 0.00 | 0.00 |
December | 0.554220E+09 | 0.422316E+10 | 0.115524E+10 | 0.496178E+09 | 0.659061E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.389842E+11 | 0.288471E+11 | 0.381373E+11 | 0.191699E+11 | 0.189673E+11 | 0.00 | 0.00 |
Minimum of Months | 0.554220E+09 | 0.936754E+09 | 0.115524E+10 | 0.496178E+09 | 0.659061E+09 | 0.00 | 0.00 |
Maximum of Months | 0.714315E+10 | 0.500941E+10 | 0.560323E+10 | 0.316765E+10 | 0.250786E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.579604E+10 | 0.698232E+10 | 0.640749E+10 | 0.457636E+10 | 0.183113E+10 | 0.00 | 0.00 |
February | 0.739372E+10 | 0.469262E+10 | 0.737018E+10 | 0.530091E+10 | 0.206927E+10 | 0.00 | 0.00 |
March | 0.728004E+10 | 0.463079E+10 | 0.729384E+10 | 0.409588E+10 | 0.319795E+10 | 0.00 | 0.00 |
April | 0.590173E+10 | 0.333976E+10 | 0.567389E+10 | 0.271386E+10 | 0.296003E+10 | 0.00 | 0.00 |
May | 0.549171E+10 | 0.274825E+10 | 0.520915E+10 | 0.173010E+10 | 0.347905E+10 | 0.00 | 0.00 |
June | 0.606797E+10 | 0.187359E+10 | 0.500885E+10 | 0.146082E+10 | 0.354803E+10 | 0.00 | 0.00 |
July | 0.761194E+10 | 0.154343E+10 | 0.558004E+10 | 0.206125E+10 | 0.351879E+10 | 0.00 | 0.00 |
August | 0.877897E+10 | 0.172349E+10 | 0.663152E+10 | 0.334349E+10 | 0.328803E+10 | 0.00 | 0.00 |
September | 0.870011E+10 | 0.233798E+10 | 0.711789E+10 | 0.436136E+10 | 0.275653E+10 | 0.00 | 0.00 |
October | 0.860788E+10 | 0.332538E+10 | 0.768941E+10 | 0.531713E+10 | 0.237228E+10 | 0.00 | 0.00 |
November | 0.690696E+10 | 0.415617E+10 | 0.678432E+10 | 0.491429E+10 | 0.187003E+10 | 0.00 | 0.00 |
December | 0.567934E+10 | 0.587506E+10 | 0.609317E+10 | 0.439988E+10 | 0.169328E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.842164E+11 | 0.432288E+11 | 0.768598E+11 | 0.442753E+11 | 0.325844E+11 | 0.00 | 0.00 |
Minimum of Months | 0.549171E+10 | 0.154343E+10 | 0.500885E+10 | 0.146082E+10 | 0.169328E+10 | 0.00 | 0.00 |
Maximum of Months | 0.877897E+10 | 0.698232E+10 | 0.768941E+10 | 0.531713E+10 | 0.354803E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.620129E+09 | 0.523815E+10 | 0.126045E+10 | 0.507971E+09 | 0.752480E+09 | 0.00 | 0.00 |
February | 0.145049E+10 | 0.339759E+10 | 0.194320E+10 | 0.955182E+09 | 0.988019E+09 | 0.00 | 0.00 |
March | 0.213139E+10 | 0.313098E+10 | 0.275327E+10 | 0.100884E+10 | 0.174443E+10 | 0.00 | 0.00 |
April | 0.333742E+10 | 0.219534E+10 | 0.347846E+10 | 0.154112E+10 | 0.193734E+10 | 0.00 | 0.00 |
May | 0.466729E+10 | 0.180628E+10 | 0.444603E+10 | 0.202763E+10 | 0.241840E+10 | 0.00 | 0.00 |
June | 0.552779E+10 | 0.122782E+10 | 0.468107E+10 | 0.215019E+10 | 0.253088E+10 | 0.00 | 0.00 |
July | 0.640027E+10 | 0.105998E+10 | 0.495508E+10 | 0.250387E+10 | 0.245120E+10 | 0.00 | 0.00 |
August | 0.528124E+10 | 0.113944E+10 | 0.420753E+10 | 0.206497E+10 | 0.214256E+10 | 0.00 | 0.00 |
September | 0.375526E+10 | 0.155228E+10 | 0.327551E+10 | 0.165596E+10 | 0.161954E+10 | 0.00 | 0.00 |
October | 0.232307E+10 | 0.226163E+10 | 0.241913E+10 | 0.120193E+10 | 0.121719E+10 | 0.00 | 0.00 |
November | 0.127748E+10 | 0.302343E+10 | 0.165727E+10 | 0.822147E+09 | 0.835122E+09 | 0.00 | 0.00 |
December | 0.593830E+09 | 0.436470E+10 | 0.115112E+10 | 0.485855E+09 | 0.665265E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.373657E+11 | 0.303976E+11 | 0.362281E+11 | 0.169257E+11 | 0.193024E+11 | 0.00 | 0.00 |
Minimum of Months | 0.593830E+09 | 0.105998E+10 | 0.115112E+10 | 0.485855E+09 | 0.665265E+09 | 0.00 | 0.00 |
Maximum of Months | 0.640027E+10 | 0.523815E+10 | 0.495508E+10 | 0.250387E+10 | 0.253088E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 22986463.04 | 0.827017E+10 | 0.908988E+09 | 0.00 | 0.908988E+09 | 0.00 | 0.00 |
February | 0.187490E+09 | 0.549711E+10 | 0.115923E+10 | 0.00 | 0.115923E+10 | 0.00 | 0.00 |
March | 0.716339E+09 | 0.482308E+10 | 0.208488E+10 | 0.00 | 0.208488E+10 | 0.00 | 0.00 |
April | 0.126675E+10 | 0.322071E+10 | 0.230053E+10 | 13425239.37 | 0.228710E+10 | 0.00 | 0.00 |
May | 0.234726E+10 | 0.252795E+10 | 0.312184E+10 | 0.184987E+09 | 0.293686E+10 | 0.00 | 0.00 |
June | 0.357114E+10 | 0.160534E+10 | 0.351795E+10 | 0.404355E+09 | 0.311360E+10 | 0.00 | 0.00 |
July | 0.402924E+10 | 0.139455E+10 | 0.332097E+10 | 0.311046E+09 | 0.300993E+10 | 0.00 | 0.00 |
August | 0.291360E+10 | 0.161576E+10 | 0.266111E+10 | 71329538.49 | 0.258978E+10 | 0.00 | 0.00 |
September | 0.162461E+10 | 0.242127E+10 | 0.192870E+10 | 692114.96 | 0.192801E+10 | 0.00 | 0.00 |
October | 0.604254E+09 | 0.370062E+10 | 0.145377E+10 | 0.00 | 0.145377E+10 | 0.00 | 0.00 |
November | 0.137311E+09 | 0.507842E+10 | 0.956405E+09 | 0.00 | 0.956405E+09 | 0.00 | 0.00 |
December | 12032368.32 | 0.714987E+10 | 0.762238E+09 | 0.00 | 0.762238E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.174330E+11 | 0.473049E+11 | 0.241766E+11 | 0.985835E+09 | 0.231908E+11 | 0.00 | 0.00 |
Minimum of Months | 12032368.32 | 0.139455E+10 | 0.762238E+09 | 0.00 | 0.762238E+09 | 0.00 | 0.00 |
Maximum of Months | 0.402924E+10 | 0.827017E+10 | 0.351795E+10 | 0.404355E+09 | 0.311360E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.708684E+09 | 0.508747E+10 | 0.139153E+10 | 0.637958E+09 | 0.753572E+09 | 0.00 | 0.00 |
February | 0.144630E+10 | 0.338838E+10 | 0.196585E+10 | 0.975995E+09 | 0.989856E+09 | 0.00 | 0.00 |
March | 0.235275E+10 | 0.306577E+10 | 0.292647E+10 | 0.121089E+10 | 0.171558E+10 | 0.00 | 0.00 |
April | 0.347809E+10 | 0.212224E+10 | 0.361344E+10 | 0.179079E+10 | 0.182265E+10 | 0.00 | 0.00 |
May | 0.423971E+10 | 0.175158E+10 | 0.412457E+10 | 0.183517E+10 | 0.228940E+10 | 0.00 | 0.00 |
June | 0.611166E+10 | 0.114564E+10 | 0.516650E+10 | 0.265867E+10 | 0.250783E+10 | 0.00 | 0.00 |
July | 0.717560E+10 | 0.985099E+09 | 0.560314E+10 | 0.316759E+10 | 0.243555E+10 | 0.00 | 0.00 |
August | 0.607456E+10 | 0.111492E+10 | 0.486938E+10 | 0.271306E+10 | 0.215632E+10 | 0.00 | 0.00 |
September | 0.373507E+10 | 0.157276E+10 | 0.333349E+10 | 0.172073E+10 | 0.161276E+10 | 0.00 | 0.00 |
October | 0.225964E+10 | 0.236566E+10 | 0.247132E+10 | 0.125490E+10 | 0.121643E+10 | 0.00 | 0.00 |
November | 0.998833E+09 | 0.312044E+10 | 0.151575E+10 | 0.707654E+09 | 0.808097E+09 | 0.00 | 0.00 |
December | 0.545528E+09 | 0.438873E+10 | 0.115522E+10 | 0.496168E+09 | 0.659052E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.391264E+11 | 0.301087E+11 | 0.381367E+11 | 0.191696E+11 | 0.189671E+11 | 0.00 | 0.00 |
Minimum of Months | 0.545528E+09 | 0.985099E+09 | 0.115522E+10 | 0.496168E+09 | 0.659052E+09 | 0.00 | 0.00 |
Maximum of Months | 0.717560E+10 | 0.508747E+10 | 0.560314E+10 | 0.316759E+10 | 0.250783E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.588564E+10 | 0.708506E+10 | 0.640724E+10 | 0.457617E+10 | 0.183107E+10 | 0.00 | 0.00 |
February | 0.749165E+10 | 0.489799E+10 | 0.736989E+10 | 0.530069E+10 | 0.206920E+10 | 0.00 | 0.00 |
March | 0.740021E+10 | 0.482271E+10 | 0.729356E+10 | 0.409571E+10 | 0.319785E+10 | 0.00 | 0.00 |
April | 0.601934E+10 | 0.342888E+10 | 0.567369E+10 | 0.271375E+10 | 0.295994E+10 | 0.00 | 0.00 |
May | 0.562997E+10 | 0.280114E+10 | 0.520897E+10 | 0.173003E+10 | 0.347894E+10 | 0.00 | 0.00 |
June | 0.618190E+10 | 0.188692E+10 | 0.500869E+10 | 0.146076E+10 | 0.354793E+10 | 0.00 | 0.00 |
July | 0.768366E+10 | 0.159359E+10 | 0.557986E+10 | 0.206117E+10 | 0.351869E+10 | 0.00 | 0.00 |
August | 0.883652E+10 | 0.182801E+10 | 0.663128E+10 | 0.334335E+10 | 0.328793E+10 | 0.00 | 0.00 |
September | 0.873638E+10 | 0.257793E+10 | 0.711762E+10 | 0.436118E+10 | 0.275644E+10 | 0.00 | 0.00 |
October | 0.860127E+10 | 0.375525E+10 | 0.768911E+10 | 0.531691E+10 | 0.237220E+10 | 0.00 | 0.00 |
November | 0.688422E+10 | 0.456445E+10 | 0.678405E+10 | 0.491409E+10 | 0.186997E+10 | 0.00 | 0.00 |
December | 0.570345E+10 | 0.614377E+10 | 0.609292E+10 | 0.439970E+10 | 0.169322E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.850542E+11 | 0.453857E+11 | 0.768569E+11 | 0.442735E+11 | 0.325834E+11 | 0.00 | 0.00 |
Minimum of Months | 0.562997E+10 | 0.159359E+10 | 0.500869E+10 | 0.146076E+10 | 0.169322E+10 | 0.00 | 0.00 |
Maximum of Months | 0.883652E+10 | 0.708506E+10 | 0.768911E+10 | 0.531691E+10 | 0.354793E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.629246E+09 | 0.530162E+10 | 0.126043E+10 | 0.507963E+09 | 0.752472E+09 | 0.00 | 0.00 |
February | 0.147306E+10 | 0.348689E+10 | 0.194317E+10 | 0.955166E+09 | 0.988008E+09 | 0.00 | 0.00 |
March | 0.218219E+10 | 0.320816E+10 | 0.275323E+10 | 0.100882E+10 | 0.174441E+10 | 0.00 | 0.00 |
April | 0.340242E+10 | 0.224099E+10 | 0.347841E+10 | 0.154109E+10 | 0.193732E+10 | 0.00 | 0.00 |
May | 0.472962E+10 | 0.187790E+10 | 0.444597E+10 | 0.202759E+10 | 0.241838E+10 | 0.00 | 0.00 |
June | 0.557537E+10 | 0.127221E+10 | 0.468101E+10 | 0.215016E+10 | 0.253085E+10 | 0.00 | 0.00 |
July | 0.643099E+10 | 0.111360E+10 | 0.495501E+10 | 0.250383E+10 | 0.245118E+10 | 0.00 | 0.00 |
August | 0.529813E+10 | 0.121003E+10 | 0.420747E+10 | 0.206493E+10 | 0.214254E+10 | 0.00 | 0.00 |
September | 0.375410E+10 | 0.169036E+10 | 0.327547E+10 | 0.165594E+10 | 0.161953E+10 | 0.00 | 0.00 |
October | 0.229294E+10 | 0.249552E+10 | 0.241909E+10 | 0.120191E+10 | 0.121718E+10 | 0.00 | 0.00 |
November | 0.126302E+10 | 0.325279E+10 | 0.165725E+10 | 0.822133E+09 | 0.835113E+09 | 0.00 | 0.00 |
December | 0.596161E+09 | 0.452911E+10 | 0.115110E+10 | 0.485847E+09 | 0.665257E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.376273E+11 | 0.316792E+11 | 0.362276E+11 | 0.169254E+11 | 0.193022E+11 | 0.00 | 0.00 |
Minimum of Months | 0.596161E+09 | 0.111360E+10 | 0.115110E+10 | 0.485847E+09 | 0.665257E+09 | 0.00 | 0.00 |
Maximum of Months | 0.643099E+10 | 0.530162E+10 | 0.495501E+10 | 0.250383E+10 | 0.253085E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 21283910.01 | 0.838868E+10 | 0.909008E+09 | 0.00 | 0.909008E+09 | 0.00 | 0.00 |
February | 0.165683E+09 | 0.562212E+10 | 0.115926E+10 | 0.00 | 0.115926E+10 | 0.00 | 0.00 |
March | 0.633345E+09 | 0.500127E+10 | 0.208493E+10 | 0.00 | 0.208493E+10 | 0.00 | 0.00 |
April | 0.112062E+10 | 0.344683E+10 | 0.230057E+10 | 13425633.98 | 0.228715E+10 | 0.00 | 0.00 |
May | 0.217801E+10 | 0.266773E+10 | 0.312191E+10 | 0.184993E+09 | 0.293692E+10 | 0.00 | 0.00 |
June | 0.345473E+10 | 0.168020E+10 | 0.351802E+10 | 0.404367E+09 | 0.311366E+10 | 0.00 | 0.00 |
July | 0.395219E+10 | 0.144596E+10 | 0.332104E+10 | 0.311055E+09 | 0.300998E+10 | 0.00 | 0.00 |
August | 0.285754E+10 | 0.166408E+10 | 0.266116E+10 | 71331635.12 | 0.258983E+10 | 0.00 | 0.00 |
September | 0.158425E+10 | 0.245005E+10 | 0.192874E+10 | 692135.30 | 0.192804E+10 | 0.00 | 0.00 |
October | 0.587429E+09 | 0.368099E+10 | 0.145380E+10 | 0.00 | 0.145380E+10 | 0.00 | 0.00 |
November | 0.131385E+09 | 0.505977E+10 | 0.956425E+09 | 0.00 | 0.956425E+09 | 0.00 | 0.00 |
December | 10322970.05 | 0.716345E+10 | 0.762255E+09 | 0.00 | 0.762255E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.166968E+11 | 0.482711E+11 | 0.241771E+11 | 0.985864E+09 | 0.231913E+11 | 0.00 | 0.00 |
Minimum of Months | 10322970.05 | 0.144596E+10 | 0.762255E+09 | 0.00 | 0.762255E+09 | 0.00 | 0.00 |
Maximum of Months | 0.395219E+10 | 0.838868E+10 | 0.351802E+10 | 0.404367E+09 | 0.311366E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.693862E+09 | 0.513137E+10 | 0.139155E+10 | 0.637971E+09 | 0.753582E+09 | 0.00 | 0.00 |
February | 0.141252E+10 | 0.343219E+10 | 0.196588E+10 | 0.976014E+09 | 0.989869E+09 | 0.00 | 0.00 |
March | 0.228588E+10 | 0.312098E+10 | 0.292652E+10 | 0.121091E+10 | 0.171561E+10 | 0.00 | 0.00 |
April | 0.339585E+10 | 0.218313E+10 | 0.361350E+10 | 0.179082E+10 | 0.182268E+10 | 0.00 | 0.00 |
May | 0.416520E+10 | 0.177917E+10 | 0.412464E+10 | 0.183520E+10 | 0.228943E+10 | 0.00 | 0.00 |
June | 0.606261E+10 | 0.114544E+10 | 0.516659E+10 | 0.265872E+10 | 0.250786E+10 | 0.00 | 0.00 |
July | 0.714666E+10 | 0.964471E+09 | 0.560323E+10 | 0.316765E+10 | 0.243557E+10 | 0.00 | 0.00 |
August | 0.605123E+10 | 0.108881E+10 | 0.486945E+10 | 0.271311E+10 | 0.215634E+10 | 0.00 | 0.00 |
September | 0.372166E+10 | 0.152403E+10 | 0.333354E+10 | 0.172076E+10 | 0.161278E+10 | 0.00 | 0.00 |
October | 0.225729E+10 | 0.228606E+10 | 0.247136E+10 | 0.125492E+10 | 0.121644E+10 | 0.00 | 0.00 |
November | 0.996084E+09 | 0.306830E+10 | 0.151578E+10 | 0.707668E+09 | 0.808108E+09 | 0.00 | 0.00 |
December | 0.537957E+09 | 0.437990E+10 | 0.115524E+10 | 0.496178E+09 | 0.659061E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.387268E+11 | 0.301039E+11 | 0.381373E+11 | 0.191699E+11 | 0.189673E+11 | 0.00 | 0.00 |
Minimum of Months | 0.537957E+09 | 0.964471E+09 | 0.115524E+10 | 0.496178E+09 | 0.659061E+09 | 0.00 | 0.00 |
Maximum of Months | 0.714666E+10 | 0.513137E+10 | 0.560323E+10 | 0.316765E+10 | 0.250786E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.575902E+10 | 0.717966E+10 | 0.640749E+10 | 0.457636E+10 | 0.183113E+10 | 0.00 | 0.00 |
February | 0.734716E+10 | 0.489351E+10 | 0.737018E+10 | 0.530091E+10 | 0.206927E+10 | 0.00 | 0.00 |
March | 0.723576E+10 | 0.485847E+10 | 0.729384E+10 | 0.409588E+10 | 0.319795E+10 | 0.00 | 0.00 |
April | 0.586423E+10 | 0.353359E+10 | 0.567389E+10 | 0.271386E+10 | 0.296003E+10 | 0.00 | 0.00 |
May | 0.546646E+10 | 0.290115E+10 | 0.520915E+10 | 0.173010E+10 | 0.347905E+10 | 0.00 | 0.00 |
June | 0.606071E+10 | 0.195592E+10 | 0.500885E+10 | 0.146082E+10 | 0.354803E+10 | 0.00 | 0.00 |
July | 0.761487E+10 | 0.160258E+10 | 0.558004E+10 | 0.206125E+10 | 0.351879E+10 | 0.00 | 0.00 |
August | 0.877801E+10 | 0.180411E+10 | 0.663152E+10 | 0.334349E+10 | 0.328803E+10 | 0.00 | 0.00 |
September | 0.868134E+10 | 0.247726E+10 | 0.711789E+10 | 0.436136E+10 | 0.275653E+10 | 0.00 | 0.00 |
October | 0.854955E+10 | 0.356072E+10 | 0.768941E+10 | 0.531713E+10 | 0.237228E+10 | 0.00 | 0.00 |
November | 0.682995E+10 | 0.441325E+10 | 0.678432E+10 | 0.491429E+10 | 0.187003E+10 | 0.00 | 0.00 |
December | 0.562343E+10 | 0.611658E+10 | 0.609317E+10 | 0.439988E+10 | 0.169328E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.838105E+11 | 0.452968E+11 | 0.768598E+11 | 0.442753E+11 | 0.325844E+11 | 0.00 | 0.00 |
Minimum of Months | 0.546646E+10 | 0.160258E+10 | 0.500885E+10 | 0.146082E+10 | 0.169328E+10 | 0.00 | 0.00 |
Maximum of Months | 0.877801E+10 | 0.717966E+10 | 0.768941E+10 | 0.531713E+10 | 0.354803E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.612314E+09 | 0.536290E+10 | 0.126045E+10 | 0.507971E+09 | 0.752480E+09 | 0.00 | 0.00 |
February | 0.143271E+10 | 0.353436E+10 | 0.194320E+10 | 0.955182E+09 | 0.988019E+09 | 0.00 | 0.00 |
March | 0.210992E+10 | 0.328142E+10 | 0.275327E+10 | 0.100884E+10 | 0.174443E+10 | 0.00 | 0.00 |
April | 0.331163E+10 | 0.232136E+10 | 0.347846E+10 | 0.154112E+10 | 0.193734E+10 | 0.00 | 0.00 |
May | 0.465097E+10 | 0.190564E+10 | 0.444603E+10 | 0.202763E+10 | 0.241840E+10 | 0.00 | 0.00 |
June | 0.552085E+10 | 0.128071E+10 | 0.468107E+10 | 0.215019E+10 | 0.253088E+10 | 0.00 | 0.00 |
July | 0.639969E+10 | 0.109865E+10 | 0.495508E+10 | 0.250387E+10 | 0.245120E+10 | 0.00 | 0.00 |
August | 0.527313E+10 | 0.119247E+10 | 0.420753E+10 | 0.206497E+10 | 0.214256E+10 | 0.00 | 0.00 |
September | 0.373705E+10 | 0.164822E+10 | 0.327551E+10 | 0.165596E+10 | 0.161954E+10 | 0.00 | 0.00 |
October | 0.228511E+10 | 0.242605E+10 | 0.241913E+10 | 0.120193E+10 | 0.121719E+10 | 0.00 | 0.00 |
November | 0.125032E+10 | 0.320614E+10 | 0.165727E+10 | 0.822147E+09 | 0.835122E+09 | 0.00 | 0.00 |
December | 0.582733E+09 | 0.452493E+10 | 0.115112E+10 | 0.485855E+09 | 0.665265E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.371664E+11 | 0.317829E+11 | 0.362281E+11 | 0.169257E+11 | 0.193024E+11 | 0.00 | 0.00 |
Minimum of Months | 0.582733E+09 | 0.109865E+10 | 0.115112E+10 | 0.485855E+09 | 0.665265E+09 | 0.00 | 0.00 |
Maximum of Months | 0.639969E+10 | 0.536290E+10 | 0.495508E+10 | 0.250387E+10 | 0.253088E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.580825E+10 | -0.506153E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -746718647.0 | 58.98 | 0.00 | 0.00 |
February | 0.533883E+10 | -0.468085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -657976359.0 | 58.99 | 0.00 | 0.00 |
March | 0.619953E+10 | -0.548391E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -715618065.6 | 58.98 | 0.00 | 0.00 |
April | 0.543509E+10 | -0.475449E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -680604337.5 | 58.98 | 0.00 | 0.00 |
May | 0.551675E+10 | -0.482059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -696156300.5 | 58.98 | 0.00 | 0.00 |
June | 0.516078E+10 | -0.449215E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668634211.5 | 58.99 | 0.00 | 0.00 |
July | 0.470452E+10 | -0.401720E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687324296.3 | 58.98 | 0.00 | 0.00 |
August | 0.503063E+10 | -0.434265E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687975202.0 | 58.98 | 0.00 | 0.00 |
September | 0.463159E+10 | -0.396346E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668121694.6 | 58.98 | 0.00 | 0.00 |
October | 0.498187E+10 | -0.428484E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -697027715.3 | 58.98 | 0.00 | 0.00 |
November | 0.516787E+10 | -0.448151E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -686353697.9 | 58.98 | 0.00 | 0.00 |
December | 0.543736E+10 | -0.470721E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -730142020.1 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.634131E+11 | -0.550904E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.832265E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.463159E+10 | -0.548391E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -746718647.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.619953E+10 | -0.396346E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -657976359.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.51 | 0.48 | 01-JAN-08:50 | 6273.26 | 36.84 | 217.67 | 231.50 | 5291.76 | 37.85 | 219.83 | 215.00 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:20 | 8487.19 | 37.17 | 268.17 | 259.33 | 3694.38 | 32.01 | 239.83 | 247.17 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:49 | 9878.72 | 33.00 | 260.33 | 324.00 | 2070.36 | 22.60 | 220.50 | 295.33 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:50 | 2477.10 | 19.40 | 12.33 | 349.83 | 1440.65 | 21.67 | 201.00 | 318.00 |
May | 385.83 | 0.51 | 0.48 | 01-MAY-06:30 | 2176.98 | 19.18 | 4.83 | 398.00 | 1238.90 | 21.41 | 229.00 | 358.67 |
June | 434.17 | 0.52 | 0.48 | 01-JUN-13:39 | 1859.20 | 18.66 | 0.33 | 412.33 | 1093.17 | 20.93 | 236.67 | 367.17 |
July | 417.33 | 0.51 | 0.48 | 01-JUL-06:40 | 2002.78 | 19.05 | 3.83 | 406.17 | 1211.94 | 21.35 | 210.50 | 371.83 |
August | 421.33 | 0.52 | 0.48 | 01-AUG-06:49 | 2156.27 | 18.52 | 4.17 | 384.83 | 1310.49 | 20.80 | 196.33 | 349.83 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 3064.20 | 20.00 | 42.83 | 327.50 | 1569.80 | 21.16 | 175.83 | 300.67 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:39 | 8586.68 | 34.77 | 286.00 | 301.67 | 2494.90 | 25.27 | 212.83 | 285.67 |
November | 269.50 | 0.51 | 0.48 | 01-NOV-07:00 | 6399.81 | 37.03 | 260.33 | 250.50 | 5677.80 | 38.52 | 263.50 | 241.17 |
December | 236.83 | 0.51 | 0.48 | 01-DEC-08:50 | 4942.63 | 36.20 | 218.33 | 231.67 | 4382.40 | 38.87 | 239.50 | 219.67 |
Annual Sum or Average | 3965.83 | 0.51 | 4452.83 | 25.92 | 1579.17 | 3877.33 | 2329.43 | 25.57 | 2645.33 | 3570.17 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1859.20 | 18.52 | 0.33 | 231.50 | 1093.17 | 20.80 | 175.83 | 215.00 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 9878.72 | 37.17 | 286.00 | 412.33 | 5677.80 | 38.87 | 263.50 | 371.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-08:50 | 1952.47 | 23.81 | 89.67 | 216.83 | 1119.82 | 24.08 | 96.00 | 184.67 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-08:09 | 2138.61 | 21.32 | 75.17 | 246.67 | 1142.84 | 22.07 | 95.83 | 215.33 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:49 | 3409.89 | 22.89 | 95.00 | 319.67 | 1904.85 | 23.80 | 138.83 | 288.67 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:39 | 3428.91 | 22.11 | 85.33 | 356.67 | 1919.47 | 23.20 | 83.33 | 324.33 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-05:40 | 3766.05 | 22.35 | 113.67 | 407.00 | 1661.06 | 22.30 | 69.17 | 372.17 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 4581.35 | 22.70 | 134.17 | 423.17 | 2007.45 | 23.30 | 91.83 | 392.17 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 4985.59 | 23.51 | 132.67 | 421.83 | 2149.07 | 23.14 | 79.83 | 396.33 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-05:30 | 3936.63 | 21.82 | 115.67 | 390.83 | 2305.85 | 23.86 | 116.50 | 361.17 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:19 | 2990.71 | 22.10 | 104.33 | 327.17 | 1672.13 | 23.07 | 112.67 | 298.00 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:20 | 2673.23 | 22.50 | 107.33 | 290.00 | 1541.90 | 23.69 | 126.50 | 255.33 |
November | 269.50 | 0.53 | 0.48 | 01-NOV-07:49 | 1686.71 | 21.22 | 83.50 | 231.50 | 967.54 | 23.24 | 105.83 | 200.83 |
December | 236.83 | 0.54 | 0.48 | 01-DEC-08:50 | 1515.46 | 23.74 | 100.67 | 210.50 | 906.47 | 24.25 | 102.00 | 171.50 |
Annual Sum or Average | 3965.83 | 0.51 | 3298.15 | 22.48 | 1237.17 | 3841.83 | 1691.07 | 23.30 | 1218.33 | 3460.50 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1515.46 | 21.22 | 75.17 | 210.50 | 906.47 | 22.07 | 69.17 | 171.50 | |
Maximum of Months | 434.17 | 0.54 | 0.48 | 4985.59 | 23.81 | 134.17 | 423.17 | 2305.85 | 24.25 | 138.83 | 396.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.57 | 0.48 | 01-JAN-10:30 | 629.46 | 15.10 | 0.00 | 193.83 | 373.93 | 17.56 | 0.00 | 130.17 |
February | 275.00 | 0.54 | 0.48 | 01-FEB-11:20 | 688.71 | 16.11 | 0.00 | 232.00 | 425.76 | 18.59 | 0.00 | 178.50 |
March | 304.00 | 0.51 | 0.48 | 01-MAR-08:09 | 1086.71 | 18.10 | 0.00 | 312.67 | 641.07 | 20.37 | 52.50 | 272.67 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 1131.87 | 18.77 | 0.00 | 352.33 | 677.93 | 20.95 | 78.50 | 314.67 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-06:10 | 1402.27 | 20.73 | 45.00 | 412.17 | 791.68 | 21.52 | 176.33 | 377.33 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 1456.29 | 22.27 | 103.83 | 440.83 | 828.43 | 22.79 | 257.00 | 416.50 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 1426.67 | 21.84 | 80.00 | 426.67 | 825.71 | 21.75 | 201.50 | 401.17 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1105.18 | 18.40 | 0.00 | 400.17 | 705.73 | 20.63 | 116.67 | 379.50 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 902.93 | 17.41 | 0.00 | 324.33 | 562.56 | 19.68 | 23.50 | 280.83 |
October | 317.67 | 0.54 | 0.48 | 01-OCT-09:20 | 745.58 | 16.48 | 0.00 | 275.50 | 456.34 | 18.88 | 0.83 | 215.50 |
November | 269.50 | 0.57 | 0.48 | 01-NOV-08:00 | 590.53 | 15.22 | 0.00 | 210.67 | 356.85 | 17.71 | 0.00 | 141.67 |
December | 236.83 | 0.59 | 0.48 | 01-DEC-09:50 | 513.90 | 14.54 | 0.00 | 187.67 | 309.43 | 17.12 | 0.00 | 95.50 |
Annual Sum or Average | 3965.83 | 0.52 | 1033.99 | 18.38 | 228.83 | 3768.83 | 614.46 | 20.13 | 906.83 | 3204.00 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 513.90 | 14.54 | 0.00 | 187.67 | 309.43 | 17.12 | 0.00 | 95.50 | |
Maximum of Months | 434.17 | 0.59 | 0.48 | 1456.29 | 22.27 | 103.83 | 440.83 | 828.43 | 22.79 | 257.00 | 416.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.54 | 0.48 | 01-JAN-10:30 | 1814.22 | 22.48 | 85.00 | 210.17 | 1064.47 | 23.02 | 88.00 | 174.33 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-11:09 | 2259.95 | 21.30 | 77.50 | 243.67 | 1287.46 | 23.80 | 111.83 | 216.33 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:20 | 3186.07 | 22.46 | 92.33 | 317.83 | 1782.84 | 24.43 | 134.00 | 288.00 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 3335.15 | 20.83 | 75.83 | 349.33 | 1882.16 | 22.08 | 74.50 | 315.67 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:49 | 3803.68 | 19.78 | 75.17 | 403.50 | 1785.40 | 19.34 | 6.83 | 369.67 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 3895.12 | 17.93 | 52.00 | 425.00 | 1768.55 | 19.02 | 5.17 | 393.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:00 | 4518.84 | 19.88 | 79.67 | 410.50 | 2056.45 | 19.35 | 5.83 | 383.17 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:49 | 3469.97 | 19.63 | 88.67 | 389.17 | 1953.60 | 21.12 | 72.83 | 360.83 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-07:19 | 3449.58 | 21.56 | 98.83 | 328.00 | 1476.93 | 22.49 | 91.17 | 298.17 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-09:20 | 2289.60 | 21.11 | 85.50 | 287.00 | 1308.92 | 23.30 | 115.67 | 254.67 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-08:00 | 2025.51 | 23.26 | 103.17 | 230.17 | 1158.94 | 23.92 | 104.83 | 198.33 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-09:50 | 1383.48 | 21.21 | 79.00 | 210.17 | 806.27 | 23.28 | 93.50 | 173.67 |
Annual Sum or Average | 3965.83 | 0.52 | 3128.81 | 20.71 | 992.67 | 3804.50 | 1595.32 | 21.77 | 904.17 | 3426.17 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1383.48 | 17.93 | 52.00 | 210.17 | 806.27 | 19.02 | 5.17 | 173.67 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 4518.84 | 23.26 | 103.17 | 425.00 | 2056.45 | 24.43 | 134.00 | 393.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.51 | 0.48 | 01-JAN-08:50 | 6080.72 | 36.57 | 216.17 | 230.50 | 5140.75 | 37.56 | 215.67 | 213.50 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:20 | 8257.57 | 35.95 | 256.83 | 256.83 | 3536.16 | 30.59 | 180.17 | 246.50 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:49 | 9686.47 | 32.23 | 253.67 | 322.50 | 1930.01 | 19.77 | 24.00 | 293.33 |
April | 325.17 | 0.51 | 0.48 | 01-APR-08:50 | 2348.85 | 15.61 | 0.00 | 347.50 | 1346.62 | 19.17 | 25.17 | 314.17 |
May | 385.83 | 0.51 | 0.48 | 01-MAY-06:40 | 2077.56 | 15.50 | 0.00 | 396.33 | 1170.25 | 19.00 | 18.33 | 355.67 |
June | 434.17 | 0.52 | 0.48 | 01-JUN-13:39 | 1776.49 | 15.07 | 0.00 | 409.50 | 1037.44 | 18.64 | 4.33 | 363.83 |
July | 417.33 | 0.51 | 0.48 | 01-JUL-06:49 | 1908.90 | 15.48 | 0.00 | 403.67 | 1146.52 | 19.08 | 17.67 | 369.00 |
August | 421.33 | 0.52 | 0.48 | 01-AUG-06:49 | 2042.59 | 14.78 | 0.00 | 382.00 | 1225.68 | 18.37 | 15.67 | 347.67 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 2914.91 | 16.36 | 29.50 | 326.50 | 1454.90 | 18.54 | 27.33 | 298.33 |
October | 317.67 | 0.51 | 0.48 | 01-OCT-08:39 | 8396.08 | 33.93 | 280.00 | 301.17 | 2355.75 | 22.86 | 84.17 | 285.00 |
November | 269.50 | 0.51 | 0.48 | 01-NOV-07:00 | 6177.85 | 35.29 | 246.33 | 248.33 | 5538.72 | 38.30 | 263.00 | 239.83 |
December | 236.83 | 0.51 | 0.48 | 01-DEC-08:50 | 4693.74 | 33.05 | 197.00 | 228.33 | 4249.57 | 38.67 | 232.17 | 218.50 |
Annual Sum or Average | 3965.83 | 0.51 | 4301.49 | 23.23 | 1479.50 | 3853.17 | 2223.95 | 23.60 | 1107.67 | 3545.33 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1776.49 | 14.78 | 0.00 | 228.33 | 1037.44 | 18.37 | 4.33 | 213.50 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 9686.47 | 36.57 | 280.00 | 409.50 | 5538.72 | 38.67 | 263.00 | 369.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-08:50 | 1806.55 | 21.20 | 74.83 | 213.67 | 1078.39 | 23.86 | 86.17 | 181.33 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-08:09 | 2068.59 | 20.82 | 75.17 | 244.67 | 1087.73 | 21.85 | 86.33 | 212.83 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:49 | 3317.17 | 22.44 | 94.83 | 318.67 | 1831.71 | 23.60 | 126.00 | 286.17 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:39 | 3334.91 | 21.64 | 85.33 | 355.67 | 1845.02 | 23.01 | 73.83 | 320.67 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-05:40 | 3675.09 | 21.90 | 113.67 | 406.00 | 1588.73 | 22.12 | 61.33 | 367.83 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 4473.30 | 22.25 | 134.17 | 420.00 | 1908.06 | 22.43 | 79.83 | 388.00 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 4869.09 | 23.06 | 132.67 | 419.50 | 2055.41 | 22.97 | 77.17 | 393.83 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-05:40 | 3811.17 | 21.14 | 112.67 | 388.83 | 2221.52 | 23.68 | 107.50 | 359.00 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:30 | 2808.81 | 19.99 | 85.17 | 325.17 | 1603.76 | 22.88 | 103.50 | 294.17 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:30 | 2606.17 | 22.04 | 107.00 | 287.67 | 1488.60 | 23.48 | 119.17 | 253.83 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-07:49 | 1634.38 | 20.54 | 81.00 | 230.00 | 927.34 | 23.02 | 96.17 | 198.17 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-08:50 | 1395.67 | 20.78 | 80.17 | 206.67 | 874.89 | 24.03 | 94.83 | 167.17 |
Annual Sum or Average | 3965.83 | 0.51 | 3191.63 | 21.57 | 1176.67 | 3816.50 | 1621.47 | 23.03 | 1111.83 | 3423.00 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1395.67 | 19.99 | 74.83 | 206.67 | 874.89 | 21.85 | 61.33 | 167.17 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 4869.09 | 23.06 | 134.17 | 420.00 | 2221.52 | 24.03 | 126.00 | 393.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.58 | 0.48 | 01-JAN-10:50 | 605.53 | 11.41 | 0.00 | 190.33 | 360.77 | 15.06 | 0.00 | 122.83 |
February | 275.00 | 0.55 | 0.48 | 01-FEB-11:20 | 663.18 | 12.49 | 0.00 | 230.17 | 412.16 | 16.22 | 0.00 | 173.00 |
March | 304.00 | 0.51 | 0.48 | 01-MAR-08:20 | 1048.27 | 14.68 | 0.00 | 309.83 | 619.97 | 18.19 | 0.00 | 269.00 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 1092.52 | 15.47 | 0.00 | 350.33 | 656.71 | 18.99 | 5.33 | 311.50 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-06:10 | 1354.31 | 17.61 | 38.50 | 411.33 | 798.05 | 20.86 | 61.00 | 377.33 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 1405.89 | 19.58 | 96.67 | 439.33 | 799.67 | 20.84 | 76.33 | 413.17 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 1379.31 | 19.04 | 72.17 | 425.17 | 799.73 | 19.75 | 48.00 | 398.00 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1067.64 | 15.06 | 0.00 | 398.83 | 685.77 | 18.67 | 11.83 | 377.17 |
September | 352.17 | 0.53 | 0.48 | 01-SEP-06:00 | 871.22 | 14.10 | 0.00 | 322.00 | 545.93 | 17.64 | 0.00 | 276.17 |
October | 317.67 | 0.54 | 0.48 | 01-OCT-12:39 | 718.37 | 12.96 | 0.00 | 271.00 | 441.79 | 16.62 | 0.00 | 209.83 |
November | 269.50 | 0.57 | 0.48 | 01-NOV-08:00 | 568.14 | 11.48 | 0.00 | 207.50 | 344.70 | 15.24 | 0.00 | 134.83 |
December | 236.83 | 0.59 | 0.48 | 01-DEC-09:00 | 493.14 | 10.70 | 0.00 | 182.00 | 298.07 | 14.50 | 0.00 | 83.67 |
Annual Sum or Average | 3965.83 | 0.52 | 997.76 | 15.08 | 207.33 | 3737.83 | 597.88 | 18.11 | 202.50 | 3146.50 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 493.14 | 10.70 | 0.00 | 182.00 | 298.07 | 14.50 | 0.00 | 83.67 | |
Maximum of Months | 434.17 | 0.59 | 0.48 | 1405.89 | 19.58 | 96.67 | 439.33 | 799.73 | 20.86 | 76.33 | 413.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.55 | 0.48 | 01-JAN-10:30 | 1765.63 | 22.13 | 85.00 | 207.67 | 1027.42 | 22.94 | 86.50 | 172.00 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-11:09 | 2195.54 | 20.88 | 77.33 | 242.00 | 1235.28 | 23.70 | 111.33 | 214.50 |
March | 304.00 | 0.51 | 0.48 | 01-MAR-08:20 | 3101.28 | 22.06 | 92.17 | 315.67 | 1690.18 | 23.47 | 120.33 | 283.67 |
April | 325.17 | 0.50 | 0.48 | 01-APR-09:09 | 3236.89 | 20.38 | 75.83 | 348.00 | 1806.57 | 21.93 | 69.33 | 312.50 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:00 | 3636.52 | 19.32 | 75.00 | 401.00 | 1704.31 | 19.18 | 2.67 | 367.17 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 3797.38 | 17.42 | 52.00 | 423.83 | 1692.97 | 18.85 | 4.33 | 389.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:00 | 4410.39 | 19.41 | 79.67 | 409.33 | 1971.37 | 19.18 | 4.50 | 380.17 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:00 | 3377.08 | 19.17 | 88.50 | 387.00 | 1880.38 | 20.97 | 67.50 | 357.50 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-07:19 | 3367.39 | 21.14 | 98.67 | 326.00 | 1408.87 | 22.37 | 88.67 | 295.67 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-12:39 | 2201.48 | 20.34 | 81.33 | 284.17 | 1254.65 | 23.19 | 113.17 | 250.83 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-08:00 | 1869.01 | 20.69 | 82.33 | 227.17 | 1116.67 | 23.83 | 104.00 | 195.50 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-09:50 | 1340.74 | 20.83 | 78.50 | 208.67 | 773.50 | 23.20 | 91.83 | 170.33 |
Annual Sum or Average | 3965.83 | 0.52 | 3031.22 | 20.10 | 966.33 | 3780.50 | 1528.17 | 21.58 | 864.17 | 3389.17 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1340.74 | 17.42 | 52.00 | 207.67 | 773.50 | 18.85 | 2.67 | 170.33 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 4410.39 | 22.13 | 98.67 | 423.83 | 1971.37 | 23.83 | 120.33 | 389.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.51 | 0.48 | 01-JAN-08:50 | 6080.72 | 36.57 | 216.17 | 230.50 | 5140.66 | 37.56 | 215.67 | 213.50 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:20 | 8257.54 | 35.95 | 256.83 | 256.83 | 3536.06 | 30.59 | 180.17 | 246.50 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:49 | 9686.33 | 32.23 | 253.67 | 322.50 | 1929.87 | 19.77 | 24.17 | 293.33 |
April | 325.17 | 0.51 | 0.48 | 01-APR-08:50 | 2348.71 | 15.61 | 0.00 | 347.50 | 1346.52 | 19.17 | 25.17 | 314.17 |
May | 385.83 | 0.51 | 0.48 | 01-MAY-06:40 | 2077.44 | 15.50 | 0.00 | 396.33 | 1170.16 | 19.00 | 18.33 | 355.67 |
June | 434.17 | 0.52 | 0.48 | 01-JUN-13:39 | 1776.40 | 15.07 | 0.00 | 409.50 | 1037.37 | 18.64 | 4.33 | 363.83 |
July | 417.33 | 0.51 | 0.48 | 01-JUL-06:49 | 1908.81 | 15.48 | 0.00 | 403.67 | 1146.44 | 19.08 | 17.67 | 369.00 |
August | 421.33 | 0.52 | 0.48 | 01-AUG-06:49 | 2042.49 | 14.79 | 0.00 | 382.00 | 1225.60 | 18.37 | 15.67 | 347.67 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 2914.81 | 16.36 | 29.50 | 326.50 | 1454.80 | 18.55 | 27.33 | 298.33 |
October | 317.67 | 0.51 | 0.48 | 01-OCT-08:39 | 8396.03 | 33.93 | 280.00 | 301.17 | 2355.64 | 22.86 | 84.17 | 285.00 |
November | 269.50 | 0.51 | 0.48 | 01-NOV-07:00 | 6177.85 | 35.29 | 246.33 | 248.33 | 5538.63 | 38.30 | 263.00 | 239.83 |
December | 236.83 | 0.51 | 0.48 | 01-DEC-08:50 | 4693.76 | 33.05 | 197.00 | 228.33 | 4249.50 | 38.67 | 232.17 | 218.50 |
Annual Sum or Average | 3965.83 | 0.51 | 4301.41 | 23.23 | 1479.50 | 3853.17 | 2223.86 | 23.60 | 1107.83 | 3545.33 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1776.40 | 14.79 | 0.00 | 228.33 | 1037.37 | 18.37 | 4.33 | 213.50 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 9686.33 | 36.57 | 280.00 | 409.50 | 5538.63 | 38.67 | 263.00 | 369.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-08:50 | 1806.53 | 21.20 | 74.83 | 213.67 | 1078.35 | 23.86 | 86.17 | 181.33 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-08:09 | 2068.57 | 20.83 | 75.17 | 244.67 | 1087.68 | 21.85 | 86.67 | 212.83 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:49 | 3317.11 | 22.45 | 95.00 | 318.67 | 1831.63 | 23.60 | 126.00 | 286.17 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:39 | 3334.85 | 21.64 | 85.33 | 355.67 | 1844.95 | 23.01 | 73.83 | 320.67 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-05:40 | 3675.02 | 21.90 | 113.67 | 406.00 | 1588.65 | 22.12 | 61.33 | 367.83 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 4473.25 | 22.25 | 134.17 | 420.00 | 1907.98 | 22.43 | 79.83 | 388.00 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 4869.05 | 23.06 | 132.67 | 419.50 | 2055.34 | 22.97 | 77.17 | 393.83 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-05:40 | 3811.13 | 21.14 | 112.67 | 388.83 | 2221.45 | 23.69 | 107.50 | 359.00 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:30 | 2808.77 | 19.99 | 85.17 | 325.17 | 1603.69 | 22.88 | 103.50 | 294.17 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:30 | 2606.15 | 22.04 | 107.00 | 287.67 | 1488.55 | 23.48 | 119.17 | 253.83 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-07:49 | 1634.36 | 20.54 | 81.00 | 230.00 | 927.30 | 23.02 | 96.17 | 198.17 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-08:50 | 1395.65 | 20.79 | 80.17 | 206.67 | 874.85 | 24.03 | 94.83 | 167.17 |
Annual Sum or Average | 3965.83 | 0.51 | 3191.59 | 21.57 | 1176.83 | 3816.50 | 1621.41 | 23.03 | 1112.17 | 3423.00 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1395.65 | 19.99 | 74.83 | 206.67 | 874.85 | 21.85 | 61.33 | 167.17 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 4869.05 | 23.06 | 134.17 | 420.00 | 2221.45 | 24.03 | 126.00 | 393.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.58 | 0.48 | 01-JAN-10:50 | 605.51 | 11.41 | 0.00 | 190.33 | 360.75 | 15.07 | 0.00 | 122.83 |
February | 275.00 | 0.55 | 0.48 | 01-FEB-11:20 | 663.16 | 12.49 | 0.00 | 230.17 | 412.14 | 16.22 | 0.00 | 173.00 |
March | 304.00 | 0.51 | 0.48 | 01-MAR-08:20 | 1048.23 | 14.69 | 0.00 | 309.83 | 619.93 | 18.19 | 0.00 | 269.00 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 1092.48 | 15.47 | 0.00 | 350.33 | 656.66 | 18.99 | 5.33 | 311.50 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-06:10 | 1354.27 | 17.61 | 38.50 | 411.33 | 798.00 | 20.86 | 61.00 | 377.33 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 1405.86 | 19.58 | 96.67 | 439.33 | 799.62 | 20.84 | 76.33 | 413.17 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 1379.28 | 19.04 | 72.17 | 425.17 | 799.69 | 19.75 | 48.00 | 398.00 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1067.62 | 15.06 | 0.00 | 398.83 | 685.74 | 18.67 | 12.00 | 377.17 |
September | 352.17 | 0.53 | 0.48 | 01-SEP-06:00 | 871.20 | 14.10 | 0.00 | 322.00 | 545.90 | 17.64 | 0.00 | 276.17 |
October | 317.67 | 0.54 | 0.48 | 01-OCT-12:39 | 718.35 | 12.96 | 0.00 | 271.00 | 441.76 | 16.62 | 0.00 | 209.83 |
November | 269.50 | 0.57 | 0.48 | 01-NOV-08:00 | 568.13 | 11.48 | 0.00 | 207.50 | 344.68 | 15.24 | 0.00 | 134.83 |
December | 236.83 | 0.59 | 0.48 | 01-DEC-09:00 | 493.13 | 10.70 | 0.00 | 182.00 | 298.05 | 14.50 | 0.00 | 83.67 |
Annual Sum or Average | 3965.83 | 0.52 | 997.74 | 15.08 | 207.33 | 3737.83 | 597.84 | 18.11 | 202.67 | 3146.50 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 493.13 | 10.70 | 0.00 | 182.00 | 298.05 | 14.50 | 0.00 | 83.67 | |
Maximum of Months | 434.17 | 0.59 | 0.48 | 1405.86 | 19.58 | 96.67 | 439.33 | 799.69 | 20.86 | 76.33 | 413.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.55 | 0.48 | 01-JAN-10:30 | 1765.60 | 22.13 | 85.00 | 207.67 | 1027.38 | 22.94 | 86.67 | 172.00 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-11:09 | 2195.51 | 20.89 | 77.33 | 242.00 | 1235.23 | 23.70 | 111.33 | 214.50 |
March | 304.00 | 0.51 | 0.48 | 01-MAR-08:20 | 3101.22 | 22.06 | 92.17 | 315.67 | 1690.10 | 23.47 | 120.33 | 283.67 |
April | 325.17 | 0.50 | 0.48 | 01-APR-09:09 | 3236.83 | 20.38 | 75.83 | 348.00 | 1806.49 | 21.93 | 69.33 | 312.50 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:00 | 3636.45 | 19.32 | 75.00 | 401.00 | 1704.22 | 19.18 | 2.67 | 367.17 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 3797.32 | 17.42 | 52.00 | 423.83 | 1692.89 | 18.85 | 4.33 | 389.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:00 | 4410.34 | 19.41 | 79.67 | 409.33 | 1971.29 | 19.19 | 4.67 | 380.17 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:00 | 3377.03 | 19.17 | 88.50 | 387.00 | 1880.31 | 20.97 | 67.50 | 357.50 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-07:19 | 3367.36 | 21.14 | 98.67 | 326.00 | 1408.81 | 22.37 | 88.67 | 295.67 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-12:39 | 2201.46 | 20.34 | 81.33 | 284.17 | 1254.60 | 23.20 | 113.17 | 250.67 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-08:00 | 1868.99 | 20.69 | 82.33 | 227.17 | 1116.63 | 23.83 | 104.00 | 195.50 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-09:50 | 1340.73 | 20.83 | 78.50 | 208.67 | 773.46 | 23.20 | 91.83 | 170.33 |
Annual Sum or Average | 3965.83 | 0.52 | 3031.18 | 20.10 | 966.33 | 3780.50 | 1528.10 | 21.58 | 864.50 | 3389.00 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1340.73 | 17.42 | 52.00 | 207.67 | 773.46 | 18.85 | 2.67 | 170.33 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 4410.34 | 22.13 | 98.67 | 423.83 | 1971.29 | 23.83 | 120.33 | 389.33 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.339125E+09 | 24086.03 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44898442.49 | 24086.03 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8666869.78 | 24086.03 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15595281.55 | 24086.03 | 26-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.408286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.339125E+09 | 24086.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.998616E+10 | 14088.56 | 02-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.555311E+10 | 14070.73 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.446623E+10 | 14027.50 | 21-MAR-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.255251E+10 | 14053.44 | 20-APR-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205244E+10 | 14190.83 | 22-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.370638E+09 | 14212.55 | 16-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 42342488.78 | 9417.49 | 05-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.216753E+09 | 13966.13 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.658289E+09 | 14069.70 | 13-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118031E+10 | 14198.37 | 20-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.312627E+10 | 14017.75 | 29-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.653566E+10 | 14103.22 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 42342488.78 | 9417.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.998616E+10 | 14212.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.490346E+10 | 10727.33 | 31-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.242982E+10 | 10693.81 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141276E+10 | 10685.76 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.343211E+09 | 10686.12 | 22-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159667E+09 | 10683.85 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4314766.47 | 4203.49 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86931099.57 | 10660.51 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100938E+10 | 10677.95 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.290047E+10 | 10676.62 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.490346E+10 | 10727.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.779787E+10 | 8935.33 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.426749E+10 | 8890.54 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.267868E+10 | 8866.26 | 11-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.725725E+09 | 8866.34 | 04-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.317084E+09 | 8861.47 | 08-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12422964.98 | 7987.21 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162566E+09 | 8866.42 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158341E+10 | 8858.64 | 29-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.454420E+10 | 8913.61 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.779787E+10 | 8935.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.524504E+10 | 11647.44 | 09-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262280E+10 | 11625.43 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172103E+10 | 11589.95 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.475108E+09 | 11616.99 | 22-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205878E+09 | 11582.88 | 08-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2365875.19 | 2967.37 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81426.54 | 476.26 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9532400.07 | 4510.30 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121229E+09 | 11589.26 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108866E+10 | 11608.17 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.310968E+10 | 11603.06 | 19-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.524504E+10 | 11647.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.344116E+10 | 27649.75 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114468E+10 | 27649.75 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.491689E+09 | 27649.75 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39134009.32 | 27649.75 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17570585.32 | 27649.75 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.478239E+09 | 27649.75 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161089E+10 | 27649.75 | 01-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.722336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.344116E+10 | 27649.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.546114E+10 | 16090.73 | 10-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230948E+10 | 16101.60 | 06-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141486E+10 | 16036.03 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.343596E+09 | 15872.55 | 28-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.288883E+09 | 16053.35 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2343766.52 | 4220.05 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 426557.99 | 1811.84 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31331871.94 | 9957.59 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185577E+09 | 15886.37 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133616E+10 | 16106.28 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.332965E+10 | 16067.37 | 29-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.546114E+10 | 16106.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.503002E+10 | 12199.63 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.240318E+10 | 12199.63 | 01-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133597E+10 | 12199.63 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.279253E+09 | 12199.63 | 01-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179018E+09 | 12199.63 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1157152.12 | 1339.62 | 16-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39196750.25 | 6476.99 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.247876E+09 | 12199.63 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142800E+10 | 12199.63 | 13-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.339024E+10 | 12199.63 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.503002E+10 | 12199.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.745018E+10 | 9927.55 | 05-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.355397E+10 | 9938.03 | 08-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180719E+10 | 9928.21 | 08-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.290746E+09 | 9838.85 | 21-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205299E+09 | 9952.45 | 08-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23431302.84 | 9833.98 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.260803E+09 | 9944.81 | 10-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179598E+10 | 9940.73 | 29-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.470974E+10 | 9938.20 | 04-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.745018E+10 | 9952.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.525185E+10 | 12344.64 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.254948E+10 | 12344.64 | 01-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156869E+10 | 12344.64 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.371434E+09 | 12344.64 | 01-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.241448E+09 | 12344.64 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4315071.88 | 4521.92 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2185799.66 | 3350.47 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 57129980.61 | 6517.17 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.316136E+09 | 12344.64 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149860E+10 | 12344.64 | 13-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.352103E+10 | 12344.64 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.525185E+10 | 12344.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.899009E+10 | 36091.60 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.414823E+10 | 36157.14 | 08-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.219470E+10 | 36061.07 | 20-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.344577E+09 | 35798.39 | 21-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.372245E+09 | 36128.31 | 08-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13878744.92 | 19471.50 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.278051E+09 | 36122.87 | 10-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.237573E+10 | 36080.62 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.601582E+10 | 36076.43 | 22-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.899009E+10 | 36157.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.839137E+10 | 17472.56 | 25-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.396110E+10 | 17461.85 | 17-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.292456E+10 | 17427.90 | 09-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102224E+10 | 17450.72 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.752004E+09 | 17423.88 | 09-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39047364.98 | 10489.20 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 428285.83 | 1037.35 | 08-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13641678.86 | 9838.39 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212928E+09 | 17308.44 | 19-SEP-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.720907E+09 | 17423.04 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.268696E+10 | 17437.02 | 22-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.584757E+10 | 17464.03 | 05-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 428285.83 | 1037.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.839137E+10 | 17472.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.701998E+10 | 12975.56 | 24-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.355351E+10 | 12931.32 | 15-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.230237E+10 | 12972.79 | 09-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.654191E+09 | 12902.47 | 01-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.404509E+09 | 12934.74 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11896235.55 | 6044.32 | 16-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4712581.65 | 3232.12 | 18-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157852E+09 | 12883.82 | 19-SEP-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.645382E+09 | 12874.09 | 06-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.246159E+10 | 12979.59 | 22-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.518171E+10 | 12968.23 | 02-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.701998E+10 | 12979.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108227E+11 | 11257.89 | 13-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.570219E+10 | 11253.80 | 11-FEB-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.357462E+10 | 11255.29 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.950339E+09 | 11249.67 | 28-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.605518E+09 | 11232.78 | 08-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9394393.18 | 8048.63 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4413517.97 | 8212.82 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189754E+09 | 11229.22 | 19-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.934136E+09 | 11252.84 | 11-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.362569E+10 | 11250.17 | 29-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.787290E+10 | 11256.36 | 20-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108227E+11 | 11257.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.746425E+10 | 14677.72 | 24-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.391503E+10 | 14620.54 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.281042E+10 | 14674.58 | 09-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.924502E+09 | 14585.23 | 21-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.593394E+09 | 14577.16 | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41153834.29 | 6722.57 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 691181.80 | 909.39 | 08-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17630423.94 | 6392.03 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.253561E+09 | 14573.93 | 19-SEP-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.890064E+09 | 14562.77 | 06-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275210E+10 | 14682.18 | 22-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.552681E+10 | 14669.41 | 02-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 691181.80 | 909.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.746425E+10 | 14682.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.188690E+11 | 39562.42 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100928E+11 | 32105.47 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.553233E+10 | 28482.94 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108876E+10 | 12175.57 | 29-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.655932E+09 | 9364.10 | 08-MAY-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 391399.14 | 625.98 | 16-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54540957.46 | 3107.60 | 19-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.714909E+09 | 12494.88 | 10-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.403408E+10 | 21979.32 | 27-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118170E+11 | 35812.57 | 29-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.528597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.188690E+11 | 39562.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.197804E+11 | 39294.91 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112526E+11 | 32873.48 | 01-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.707277E+10 | 28305.22 | 06-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.208958E+10 | 13484.88 | 29-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130403E+10 | 11161.23 | 08-MAY-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29645780.28 | 3594.49 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.253437E+09 | 5173.30 | 19-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142719E+10 | 14170.83 | 10-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.521448E+10 | 22642.66 | 27-NOV-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133130E+11 | 34345.18 | 29-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.617371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.197804E+11 | 39294.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225953E+11 | 42662.77 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123719E+11 | 36438.27 | 01-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.805254E+10 | 31591.53 | 04-MAR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.257630E+10 | 16309.93 | 29-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152556E+10 | 12849.46 | 08-MAY-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 91220341.31 | 5312.27 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1019066.53 | 1092.19 | 18-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453946E+09 | 7288.36 | 19-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189888E+10 | 16529.96 | 10-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.604752E+10 | 22110.45 | 27-NOV-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153089E+11 | 37716.16 | 29-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.709230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.225953E+11 | 42662.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.167922E+09 | 0.167736E+09 | 12450.91 | 27-FEB-15:40 | 12450.91 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.185752E+10 | 0.184407E+10 | 27755.34 | 06-APR-16:00 | 27755.34 | 0.00 |
May | 0.00 | 0.00 | 0.751772E+10 | 0.730856E+10 | 54045.09 | 19-MAY-15:40 | 54045.09 | 0.00 |
June | 0.00 | 0.00 | 0.286436E+11 | 0.273465E+11 | 67162.17 | 29-JUN-15:10 | 67162.17 | 0.00 |
July | 0.00 | 0.00 | 0.501399E+11 | 0.484278E+11 | 84235.48 | 17-JUL-16:00 | 84235.48 | 0.00 |
August | 0.00 | 0.00 | 0.429099E+11 | 0.424712E+11 | 77688.13 | 07-AUG-16:00 | 77688.13 | 0.00 |
September | 0.00 | 0.00 | 0.201333E+11 | 0.184157E+11 | 104363.77 | 07-SEP-15:00 | 52997.57 | 0.00 |
October | 0.00 | 0.00 | 0.431794E+10 | 0.429203E+10 | 49547.04 | 18-OCT-15:40 | 49547.04 | 0.00 |
November | 0.00 | 0.00 | 0.160415E+09 | 0.153649E+09 | 6158.37 | 17-NOV-17:00 | 6108.64 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.155848E+12 | 0.150427E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.501399E+11 | 0.484278E+11 | 104363.77 | 84235.48 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.160678E+09 | 0.160678E+09 | 11034.02 | 27-FEB-15:30 | 11034.02 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.190872E+10 | 0.189837E+10 | 28374.79 | 06-APR-16:00 | 28374.79 | 0.00 |
May | 0.00 | 0.00 | 0.762283E+10 | 0.744576E+10 | 55097.27 | 19-MAY-15:30 | 55097.27 | 0.00 |
June | 0.00 | 0.00 | 0.273921E+11 | 0.262009E+11 | 64772.51 | 29-JUN-14:50 | 64772.51 | 0.00 |
July | 0.00 | 0.00 | 0.462026E+11 | 0.447981E+11 | 81160.12 | 17-JUL-15:30 | 81160.12 | 0.00 |
August | 0.00 | 0.00 | 0.390027E+11 | 0.386078E+11 | 77387.90 | 07-AUG-15:30 | 77387.90 | 0.00 |
September | 0.00 | 0.00 | 0.178363E+11 | 0.164142E+11 | 103287.59 | 07-SEP-15:00 | 54506.42 | 0.00 |
October | 0.00 | 0.00 | 0.357998E+10 | 0.355998E+10 | 43964.35 | 18-OCT-15:30 | 43964.35 | 0.00 |
November | 0.00 | 0.00 | 0.145542E+09 | 0.137246E+09 | 5433.76 | 04-NOV-14:00 | 5433.76 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143851E+12 | 0.139223E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.462026E+11 | 0.447981E+11 | 103287.59 | 81160.12 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.149396E+09 | 0.149372E+09 | 10820.23 | 27-FEB-15:30 | 10820.23 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.192048E+10 | 0.190427E+10 | 29862.46 | 06-APR-16:00 | 29862.46 | 0.00 |
May | 0.00 | 0.00 | 0.806731E+10 | 0.782642E+10 | 64418.82 | 19-MAY-15:30 | 64418.82 | 0.00 |
June | 0.00 | 0.00 | 0.293650E+11 | 0.280013E+11 | 73929.03 | 29-JUN-14:50 | 73929.03 | 0.00 |
July | 0.00 | 0.00 | 0.496044E+11 | 0.480036E+11 | 93568.73 | 17-JUL-15:20 | 93568.73 | 0.00 |
August | 0.00 | 0.00 | 0.410155E+11 | 0.404671E+11 | 89948.58 | 06-AUG-16:11 | 89948.58 | 0.00 |
September | 0.00 | 0.00 | 0.184616E+11 | 0.168682E+11 | 99946.14 | 07-SEP-15:20 | 54281.69 | 0.00 |
October | 0.00 | 0.00 | 0.336947E+10 | 0.332816E+10 | 45479.68 | 18-OCT-15:00 | 45479.68 | 0.00 |
November | 0.00 | 0.00 | 0.145172E+09 | 0.132949E+09 | 5227.64 | 04-NOV-14:00 | 5219.90 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.152098E+12 | 0.146681E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.496044E+11 | 0.480036E+11 | 99946.14 | 93568.73 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2041.85 | 7202.34 | 30-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2087.33 | 7241.90 | 22-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2202.87 | 7213.08 | 03-MAR-12:05 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1986.50 | 7020.52 | 05-APR-11:07 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1954.18 | 6690.01 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1889.14 | 6327.62 | 01-JUN-11:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1651.24 | 5942.68 | 05-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1777.84 | 5749.18 | 02-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1682.12 | 5875.62 | 28-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1752.87 | 6238.89 | 31-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1882.85 | 6604.53 | 29-NOV-12:08 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1908.52 | 6963.76 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 1900.37 | ||||
Minimum of Months | 0.00 | 0.00 | 1651.24 | 5749.18 | ||
Maximum of Months | 0.00 | 0.00 | 2202.87 | 7241.90 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.196393E+10 | 0.40 | 3372.73 | 02-JAN-06:01 | 0.91 |
February | 0.164307E+10 | 0.36 | 3372.73 | 06-FEB-07:02 | 0.91 |
March | 0.199553E+10 | 0.37 | 3372.73 | 06-MAR-07:01 | 0.91 |
April | 0.204293E+10 | 0.35 | 3714.68 | 25-APR-16:00 | 0.95 |
May | 0.261652E+10 | 0.38 | 6423.19 | 19-MAY-15:50 | 1.30 |
June | 0.472648E+10 | 0.51 | 9338.01 | 29-JUN-15:10 | 1.64 |
July | 0.623420E+10 | 0.58 | 12963.37 | 18-JUL-12:10 | 2.01 |
August | 0.610213E+10 | 0.57 | 11503.18 | 11-AUG-16:00 | 1.87 |
September | 0.388905E+10 | 0.46 | 10557.25 | 05-SEP-06:03 | 1.77 |
October | 0.256662E+10 | 0.37 | 5928.00 | 18-OCT-16:00 | 1.25 |
November | 0.187066E+10 | 0.34 | 3464.20 | 03-NOV-15:30 | 0.92 |
December | 0.172728E+10 | 0.35 | 3372.73 | 26-DEC-07:01 | 0.91 |
Annual Sum or Average | 0.373784E+11 | 0.42 | |||
Minimum of Months | 0.164307E+10 | 0.34 | 3372.73 | 0.91 | |
Maximum of Months | 0.623420E+10 | 0.58 | 12963.37 | 2.01 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.200117E+10 | 0.41 | 3424.07 | 02-JAN-06:01 | 0.96 |
February | 0.163061E+10 | 0.37 | 3424.07 | 01-FEB-06:01 | 0.97 |
March | 0.185924E+10 | 0.37 | 3424.07 | 06-MAR-06:01 | 0.97 |
April | 0.182162E+10 | 0.35 | 4607.35 | 25-APR-16:00 | 1.14 |
May | 0.237130E+10 | 0.38 | 7529.68 | 19-MAY-15:30 | 1.52 |
June | 0.440355E+10 | 0.52 | 9484.58 | 29-JUN-14:30 | 1.76 |
July | 0.582960E+10 | 0.58 | 12910.89 | 17-JUL-15:00 | 2.14 |
August | 0.551138E+10 | 0.57 | 12910.89 | 07-AUG-15:30 | 2.14 |
September | 0.315085E+10 | 0.44 | 12910.89 | 07-SEP-15:00 | 2.12 |
October | 0.197357E+10 | 0.35 | 5537.27 | 18-OCT-15:40 | 1.27 |
November | 0.165589E+10 | 0.34 | 3424.07 | 21-NOV-07:01 | 0.97 |
December | 0.181384E+10 | 0.38 | 3424.07 | 04-DEC-06:01 | 0.96 |
Annual Sum or Average | 0.340226E+11 | 0.42 | |||
Minimum of Months | 0.163061E+10 | 0.34 | 3424.07 | 0.96 | |
Maximum of Months | 0.582960E+10 | 0.58 | 12910.89 | 2.14 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.245904E+10 | 0.47 | 3309.13 | 02-JAN-05:01 | 0.88 |
February | 0.182993E+10 | 0.39 | 3309.13 | 01-FEB-06:01 | 0.88 |
March | 0.198833E+10 | 0.38 | 3309.13 | 01-MAR-07:01 | 0.88 |
April | 0.180073E+10 | 0.34 | 4414.23 | 25-APR-16:00 | 1.03 |
May | 0.231985E+10 | 0.37 | 7685.71 | 19-MAY-15:30 | 1.42 |
June | 0.407056E+10 | 0.48 | 9382.24 | 29-JUN-14:30 | 1.61 |
July | 0.540806E+10 | 0.52 | 14391.83 | 17-JUL-15:20 | 2.11 |
August | 0.497887E+10 | 0.51 | 13334.40 | 07-AUG-15:40 | 2.01 |
September | 0.283287E+10 | 0.40 | 9719.94 | 01-SEP-15:40 | 1.64 |
October | 0.184966E+10 | 0.34 | 4735.26 | 18-OCT-15:20 | 1.07 |
November | 0.180570E+10 | 0.37 | 3309.13 | 13-NOV-05:11 | 0.88 |
December | 0.224694E+10 | 0.44 | 3309.13 | 01-DEC-06:01 | 0.88 |
Annual Sum or Average | 0.335905E+11 | 0.42 | |||
Minimum of Months | 0.180073E+10 | 0.34 | 3309.13 | 0.88 | |
Maximum of Months | 0.540806E+10 | 0.52 | 14391.83 | 2.11 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 57.58 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 55.51 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 55.92 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 54.93 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:01 | 2.06 | 2.06 | 56.65 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.11 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 56.34 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 56.00 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 56.27 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.36 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:05 | 2.06 | 2.06 | 55.75 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 56.59 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 54.93 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.58 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.48 | 57.48 | 2041.85 | 7202.34 | 30-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 55.98 | 55.98 | 2087.33 | 7241.90 | 22-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.39 | 56.39 | 2202.87 | 7213.08 | 03-MAR-12:05 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.15 | 56.15 | 1986.50 | 7020.52 | 05-APR-11:07 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.23 | 57.23 | 1954.18 | 6690.01 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.61 | 56.61 | 1889.14 | 6327.62 | 01-JUN-11:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.79 | 56.79 | 1651.24 | 5942.68 | 05-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.38 | 56.38 | 1777.84 | 5749.18 | 02-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.51 | 57.51 | 1682.12 | 5875.62 | 28-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.00 | 56.00 | 1752.87 | 6238.89 | 31-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.37 | 56.37 | 1882.85 | 6604.53 | 29-NOV-12:08 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.05 | 57.05 | 1908.52 | 6963.76 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 1900.37 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.98 | 55.98 | 1651.24 | 5749.18 | ||
Maximum of Months | 0.00 | 0.00 | 57.51 | 57.51 | 2202.87 | 7241.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.302356E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.166074E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.122829E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.663393E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.728952E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.123222E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.193001E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.173289E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.968162E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.521079E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.872444E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.188329E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.164450E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.521079E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.302356E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.286355E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.136357E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.847765E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.361285E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.526942E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.113019E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.178361E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.155515E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.783411E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.391644E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.823473E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.183754E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.142681E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.361285E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.286355E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.451474E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.231516E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.157950E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.621149E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.711761E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.116089E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.184019E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.156789E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.840316E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.619508E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.157496E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.326917E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.206152E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.619508E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.451474E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.196393E+10 | 0.00 | 0.471406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164307E+10 | 0.167922E+09 | 0.250110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199553E+10 | 0.00 | 0.158197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204293E+10 | 0.185752E+10 | 0.518531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261652E+10 | 0.751772E+10 | 0.339100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.472648E+10 | 0.286436E+11 | 0.373396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.623420E+10 | 0.501399E+11 | 42342488.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.610213E+10 | 0.429099E+11 | 0.216835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.388905E+10 | 0.201333E+11 | 0.739101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.256662E+10 | 0.431794E+10 | 0.226594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187066E+10 | 0.160415E+09 | 0.108418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172728E+10 | 0.00 | 0.289226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.373784E+11 | 0.155848E+12 | 0.139950E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.164307E+10 | 0.00 | 42342488.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.623420E+10 | 0.501399E+11 | 0.471406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.200117E+10 | 0.00 | 0.464148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163061E+10 | 0.160678E+09 | 0.232134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185924E+10 | 0.00 | 0.136912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182162E+10 | 0.190872E+10 | 0.337461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.237130E+10 | 0.762283E+10 | 0.225781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.440355E+10 | 0.273921E+11 | 37461770.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.582960E+10 | 0.462026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.551138E+10 | 0.390027E+11 | 2612357.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.315085E+10 | 0.178363E+11 | 0.404527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197357E+10 | 0.357998E+10 | 0.245515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165589E+10 | 0.145542E+09 | 0.117515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181384E+10 | 0.00 | 0.298745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.340226E+11 | 0.143851E+12 | 0.133477E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.163061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.582960E+10 | 0.462026E+11 | 0.464148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.245904E+10 | 0.00 | 0.652837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182993E+10 | 0.149396E+09 | 0.336520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198833E+10 | 0.00 | 0.218592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180073E+10 | 0.192048E+10 | 0.647214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.231985E+10 | 0.806731E+10 | 0.425323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.407056E+10 | 0.293650E+11 | 0.192712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.540806E+10 | 0.496044E+11 | 1119467.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.497887E+10 | 0.410155E+11 | 41417268.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.283287E+10 | 0.184616E+11 | 0.128192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184966E+10 | 0.336947E+10 | 0.536742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180570E+10 | 0.145172E+09 | 0.199496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224694E+10 | 0.00 | 0.457536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335905E+11 | 0.152098E+12 | 0.204108E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.180073E+10 | 0.00 | 1119467.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.540806E+10 | 0.496044E+11 | 0.652837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.196393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164307E+10 | 0.00 | 0.00 | 0.00 | 46238166.13 | 0.149181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204293E+10 | 0.00 | 0.00 | 0.00 | 0.494455E+09 | 0.409655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261652E+10 | 0.00 | 0.00 | 0.00 | 0.193793E+10 | 0.273507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.472648E+10 | 0.00 | 0.00 | 0.00 | 0.722273E+10 | 0.373004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.623420E+10 | 0.00 | 0.00 | 0.00 | 0.130236E+11 | 42342488.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.610213E+10 | 0.00 | 0.00 | 0.00 | 0.110100E+11 | 0.216835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.388905E+10 | 0.00 | 0.00 | 0.00 | 0.510801E+10 | 0.684560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.256662E+10 | 0.00 | 0.00 | 0.00 | 0.109314E+10 | 0.155103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187066E+10 | 0.00 | 0.00 | 0.00 | 46060120.90 | 0.680772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.373784E+11 | 0.00 | 0.00 | 0.00 | 0.399821E+11 | 0.870899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.164307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42342488.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.623420E+10 | 0.00 | 0.00 | 0.00 | 0.130236E+11 | 0.282717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.200117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163061E+10 | 0.00 | 0.00 | 0.00 | 44307912.63 | 0.119608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182162E+10 | 0.00 | 0.00 | 0.00 | 0.506205E+09 | 0.128503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.237130E+10 | 0.00 | 0.00 | 0.00 | 0.194433E+10 | 0.953782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.440355E+10 | 0.00 | 0.00 | 0.00 | 0.689056E+10 | 7815990.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.582960E+10 | 0.00 | 0.00 | 0.00 | 0.120065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.551138E+10 | 0.00 | 0.00 | 0.00 | 0.100376E+11 | 2612357.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.315085E+10 | 0.00 | 0.00 | 0.00 | 0.453217E+10 | 0.151090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197357E+10 | 0.00 | 0.00 | 0.00 | 0.914914E+09 | 0.102796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165589E+10 | 0.00 | 0.00 | 0.00 | 41845818.96 | 0.653699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.340226E+11 | 0.00 | 0.00 | 0.00 | 0.369183E+11 | 0.717404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.163061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.582960E+10 | 0.00 | 0.00 | 0.00 | 0.120065E+11 | 0.266343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.245904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182993E+10 | 0.00 | 0.00 | 0.00 | 41625008.50 | 0.212801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180073E+10 | 0.00 | 0.00 | 0.00 | 0.514908E+09 | 0.389585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.231985E+10 | 0.00 | 0.00 | 0.00 | 0.207009E+10 | 0.272767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.407056E+10 | 0.00 | 0.00 | 0.00 | 0.743680E+10 | 0.101492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.540806E+10 | 0.00 | 0.00 | 0.00 | 0.129927E+11 | 1119467.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.497887E+10 | 0.00 | 0.00 | 0.00 | 0.106597E+11 | 40398202.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.283287E+10 | 0.00 | 0.00 | 0.00 | 0.474232E+10 | 0.827973E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184966E+10 | 0.00 | 0.00 | 0.00 | 0.876875E+09 | 0.346854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180570E+10 | 0.00 | 0.00 | 0.00 | 41846365.08 | 0.139021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335905E+11 | 0.00 | 0.00 | 0.00 | 0.393769E+11 | 0.133185E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.180073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1119467.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.540806E+10 | 0.00 | 0.00 | 0.00 | 0.129927E+11 | 0.426884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127479E+11 | 0.00 | 0.00 | 3422246.96 | 0.00 | 0.155796E+09 | 0.464776E+10 | 0.00 | 0.27 |
February | 0.784095E+10 | 0.00 | 0.00 | 10041631.14 | 0.00 | 12995738.17 | 0.726881E+10 | 0.00 | 0.33 |
March | 0.514401E+10 | 0.00 | 0.00 | 23402595.54 | 0.00 | 1799301.64 | 0.130407E+11 | 0.00 | 0.41 |
April | 0.179789E+10 | 0.00 | 0.00 | 28960817.46 | 0.00 | 0.00 | 0.155407E+11 | 0.00 | 0.59 |
May | 0.140505E+10 | 13780440.57 | 0.00 | 35489515.95 | 2972464.47 | 0.00 | 0.172459E+11 | 0.00 | 0.79 |
June | 0.652483E+09 | 0.189097E+09 | 0.00 | 42183058.48 | 27990823.71 | 0.00 | 0.160875E+11 | 0.00 | 1.11 |
July | 0.544273E+09 | 0.381963E+09 | 0.00 | 34599388.10 | 21386825.89 | 0.00 | 0.851385E+10 | 0.00 | 0.92 |
August | 0.507998E+09 | 0.210726E+09 | 0.00 | 43431158.93 | 18403909.51 | 0.00 | 0.135438E+11 | 0.00 | 1.09 |
September | 0.757070E+09 | 0.275403E+09 | 0.00 | 39969215.78 | 16365867.72 | 0.00 | 0.173952E+11 | 0.00 | 1.00 |
October | 0.118762E+10 | 0.00 | 0.00 | 37929197.82 | 0.00 | 0.00 | 0.186340E+11 | 0.00 | 0.75 |
November | 0.388676E+10 | 0.00 | 0.00 | 24624431.02 | 0.00 | 0.00 | 0.130434E+11 | 0.00 | 0.47 |
December | 0.958605E+10 | 0.00 | 0.00 | 11833388.34 | 0.00 | 5018546.58 | 0.694050E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.460581E+11 | 0.107097E+10 | 0.00 | 0.335887E+09 | 87119891.30 | 0.175610E+09 | 0.151902E+12 | 0.00 | 0.67 |
Minimum of Months | 0.507998E+09 | 0.00 | 0.00 | 3422246.96 | 0.00 | 0.00 | 0.464776E+10 | 0.00 | 0.27 |
Maximum of Months | 0.127479E+11 | 0.381963E+09 | 0.00 | 43431158.93 | 27990823.71 | 0.155796E+09 | 0.186340E+11 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340740E+10 | 0.00 | 0.00 | 0.26 |
February | 0.118287E+11 | 0.00 | 0.00 | 322658.64 | 0.00 | 0.106442E+10 | 0.321136E+09 | 0.00 | 0.29 |
March | 0.112725E+11 | 0.00 | 0.00 | 1677323.37 | 0.00 | 0.267972E+09 | 0.214531E+10 | 0.00 | 0.31 |
April | 0.635981E+10 | 0.00 | 0.00 | 7435837.45 | 0.00 | 0.00 | 0.548972E+10 | 0.00 | 0.41 |
May | 0.470689E+10 | 8873139.24 | 0.00 | 13641987.23 | 6913134.43 | 14342143.02 | 0.754730E+10 | 0.00 | 0.53 |
June | 0.149201E+10 | 0.142106E+09 | 0.00 | 25360029.66 | 24621570.46 | 0.00 | 0.976404E+10 | 0.00 | 0.77 |
July | 0.900502E+09 | 0.279305E+09 | 0.00 | 22765024.22 | 14831559.10 | 0.00 | 0.544035E+10 | 0.00 | 0.66 |
August | 0.110056E+10 | 0.156234E+09 | 0.00 | 26919956.24 | 19067292.71 | 0.00 | 0.825710E+10 | 0.00 | 0.75 |
September | 0.256048E+10 | 0.211748E+09 | 0.00 | 18432855.54 | 15232887.20 | 0.00 | 0.856569E+10 | 0.00 | 0.64 |
October | 0.560838E+10 | 0.00 | 0.00 | 10286166.89 | 0.00 | 13719855.04 | 0.628058E+10 | 0.00 | 0.45 |
November | 0.923327E+10 | 0.00 | 0.00 | 2203711.07 | 0.00 | 0.383256E+09 | 0.210367E+10 | 0.00 | 0.32 |
December | 0.132061E+11 | 0.00 | 0.00 | 48306.58 | 0.00 | 0.115905E+10 | 0.127124E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.816248E+11 | 0.798265E+09 | 0.00 | 0.129094E+09 | 80666443.90 | 0.631015E+10 | 0.560420E+11 | 0.00 | 0.47 |
Minimum of Months | 0.900502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.133556E+11 | 0.279305E+09 | 0.00 | 26919956.24 | 24621570.46 | 0.340740E+10 | 0.976404E+10 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.791439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710260E+10 | 0.00 | 0.00 | 0.24 |
February | 0.913600E+10 | 0.00 | 0.00 | 130841.11 | 0.00 | 0.287019E+10 | 0.179602E+09 | 0.00 | 0.28 |
March | 0.107409E+11 | 0.00 | 0.00 | 590239.38 | 0.00 | 0.138135E+10 | 0.815758E+09 | 0.00 | 0.30 |
April | 0.793857E+10 | 0.00 | 0.00 | 4281658.92 | 0.00 | 99677949.53 | 0.332843E+10 | 0.00 | 0.40 |
May | 0.599609E+10 | 3552367.88 | 0.00 | 10193782.27 | 2162507.13 | 0.113701E+09 | 0.598883E+10 | 0.00 | 0.52 |
June | 0.205370E+10 | 0.100732E+09 | 0.00 | 23313120.16 | 10637138.95 | 0.00 | 0.870529E+10 | 0.00 | 0.78 |
July | 0.134091E+10 | 0.212987E+09 | 0.00 | 21188169.43 | 13875964.14 | 0.00 | 0.462630E+10 | 0.00 | 0.67 |
August | 0.166938E+10 | 0.106630E+09 | 0.00 | 23838166.33 | 14835218.86 | 0.00 | 0.674363E+10 | 0.00 | 0.73 |
September | 0.391378E+10 | 0.203366E+09 | 0.00 | 12718441.35 | 11996171.94 | 1657351.96 | 0.589186E+10 | 0.00 | 0.60 |
October | 0.725355E+10 | 0.00 | 0.00 | 4178438.27 | 0.00 | 0.117303E+09 | 0.324857E+10 | 0.00 | 0.42 |
November | 0.880109E+10 | 0.00 | 0.00 | 448376.41 | 0.00 | 0.112631E+10 | 0.726613E+09 | 0.00 | 0.31 |
December | 0.863028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443963E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.753887E+11 | 0.627268E+09 | 0.00 | 0.100881E+09 | 53507001.02 | 0.172524E+11 | 0.402549E+11 | 0.00 | 0.46 |
Minimum of Months | 0.134091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.107409E+11 | 0.212987E+09 | 0.00 | 23838166.33 | 14835218.86 | 0.710260E+10 | 0.870529E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 65090788.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465149E+10 | 0.00 | 0.00 | 0.33 |
February | 0.450823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261497E+10 | 0.00 | 0.00 | 0.31 |
March | 0.124968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163823E+10 | 0.00 | 0.00 | 0.31 |
April | 0.154433E+10 | 0.00 | 0.00 | 414000.85 | 0.00 | 0.503068E+09 | 0.306834E+09 | 0.00 | 0.39 |
May | 0.131915E+10 | 1804378.96 | 0.00 | 2064499.79 | 455690.11 | 0.274010E+09 | 0.998643E+09 | 0.00 | 0.56 |
June | 0.594371E+09 | 33324096.34 | 0.00 | 5856278.86 | 2241490.40 | 5841689.54 | 0.183332E+10 | 0.00 | 0.92 |
July | 0.320924E+09 | 73229729.20 | 0.00 | 5651569.28 | 2923985.53 | 0.00 | 0.105807E+10 | 0.00 | 0.82 |
August | 0.548159E+09 | 40241314.92 | 0.00 | 5245690.80 | 3126122.61 | 1109938.20 | 0.124602E+10 | 0.00 | 0.80 |
September | 0.111499E+10 | 58010047.62 | 0.00 | 1955179.63 | 2724844.14 | 98215245.94 | 0.735623E+09 | 0.00 | 0.59 |
October | 0.152625E+10 | 0.00 | 0.00 | 282653.78 | 0.00 | 0.493674E+09 | 0.183378E+09 | 0.00 | 0.41 |
November | 0.831270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154839E+10 | 0.00 | 0.00 | 0.32 |
December | 0.239870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322206E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.980491E+10 | 0.206610E+09 | 0.00 | 21469872.99 | 11472132.79 | 0.150511E+11 | 0.636190E+10 | 0.00 | 0.51 |
Minimum of Months | 65090788.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.154433E+10 | 73229729.20 | 0.00 | 5856278.86 | 3126122.61 | 0.465149E+10 | 0.183332E+10 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.259759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359495E+10 | 0.00 | 0.00 | 0.46 |
February | 0.841200E+09 | 0.00 | 0.00 | 26535.99 | 0.00 | 0.209825E+10 | 29510776.19 | 0.00 | 0.50 |
March | 0.167733E+10 | 0.00 | 0.00 | 406226.00 | 0.00 | 0.126275E+10 | 0.212765E+09 | 0.00 | 0.55 |
April | 0.147706E+10 | 0.00 | 0.00 | 1960052.36 | 0.00 | 0.391626E+09 | 0.114682E+10 | 0.00 | 0.79 |
May | 0.123373E+10 | 1373654.67 | 0.00 | 3631371.12 | 462513.87 | 0.219146E+09 | 0.186146E+10 | 0.00 | 1.10 |
June | 0.558301E+09 | 26683947.33 | 0.00 | 8294070.77 | 2547806.11 | 5608071.43 | 0.259955E+10 | 0.00 | 1.81 |
July | 0.281809E+09 | 61389673.88 | 0.00 | 9597784.87 | 2710120.11 | 0.00 | 0.181829E+10 | 0.00 | 1.78 |
August | 0.515362E+09 | 40823678.15 | 0.00 | 7371172.32 | 3369806.68 | 673106.21 | 0.208436E+10 | 0.00 | 1.70 |
September | 0.108713E+10 | 48616024.85 | 0.00 | 3091136.73 | 2774305.46 | 81469938.65 | 0.130163E+10 | 0.00 | 1.15 |
October | 0.171346E+10 | 0.00 | 0.00 | 801232.53 | 0.00 | 0.370415E+09 | 0.447686E+09 | 0.00 | 0.75 |
November | 0.120233E+10 | 0.00 | 0.00 | 12100.49 | 0.00 | 0.135261E+10 | 10333136.33 | 0.00 | 0.55 |
December | 0.459416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275787E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.113069E+11 | 0.178887E+09 | 0.00 | 35191683.19 | 11864552.24 | 0.121354E+11 | 0.115124E+11 | 0.00 | 0.97 |
Minimum of Months | 0.259759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.171346E+10 | 61389673.88 | 0.00 | 9597784.87 | 3369806.68 | 0.359495E+10 | 0.259955E+10 | 0.00 | 1.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.907742E+09 | 0.00 | 0.00 | 608890.57 | 0.00 | 0.397758E+10 | 0.491776E+09 | 0.00 | 0.41 |
February | 0.123006E+10 | 0.00 | 0.00 | 2529074.95 | 0.00 | 0.211250E+10 | 0.135498E+10 | 0.00 | 0.56 |
March | 0.170654E+10 | 0.00 | 0.00 | 4524923.54 | 0.00 | 0.152569E+10 | 0.229569E+10 | 0.00 | 0.64 |
April | 0.165780E+10 | 0.00 | 0.00 | 4332114.16 | 0.00 | 0.598547E+09 | 0.248212E+10 | 0.00 | 0.83 |
May | 0.164765E+10 | 2732685.65 | 0.00 | 5361848.75 | 621352.05 | 0.379228E+09 | 0.263660E+10 | 0.00 | 1.02 |
June | 0.106464E+10 | 46264909.11 | 0.00 | 8032615.10 | 2827642.28 | 20149325.15 | 0.251815E+10 | 0.00 | 1.33 |
July | 0.581384E+09 | 0.105703E+09 | 0.00 | 8465043.46 | 2259216.69 | 0.00 | 0.153892E+10 | 0.00 | 1.22 |
August | 0.837354E+09 | 79991833.78 | 0.00 | 10295621.30 | 3221065.51 | 5729097.22 | 0.240905E+10 | 0.00 | 1.50 |
September | 0.126410E+10 | 0.139493E+09 | 0.00 | 7611441.30 | 1343491.71 | 0.109078E+09 | 0.296001E+10 | 0.00 | 1.40 |
October | 0.158197E+10 | 0.00 | 0.00 | 6825717.63 | 0.00 | 0.389421E+09 | 0.316537E+10 | 0.00 | 1.08 |
November | 0.140010E+10 | 0.00 | 0.00 | 3352877.72 | 0.00 | 0.131693E+10 | 0.165425E+10 | 0.00 | 0.61 |
December | 0.116852E+10 | 0.00 | 0.00 | 1203249.57 | 0.00 | 0.280471E+10 | 0.617296E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.150479E+11 | 0.374186E+09 | 0.00 | 63143418.06 | 10272768.23 | 0.132396E+11 | 0.241242E+11 | 0.00 | 0.92 |
Minimum of Months | 0.581384E+09 | 0.00 | 0.00 | 608890.57 | 0.00 | 0.00 | 0.491776E+09 | 0.00 | 0.41 |
Maximum of Months | 0.170654E+10 | 0.139493E+09 | 0.00 | 10295621.30 | 3221065.51 | 0.397758E+10 | 0.316537E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.357558E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390377E+10 | 0.00 | 0.00 | 0.51 |
February | 0.827950E+09 | 0.00 | 0.00 | 213835.18 | 0.00 | 0.239357E+10 | 0.142082E+09 | 0.00 | 0.57 |
March | 0.155127E+10 | 0.00 | 0.00 | 785394.96 | 0.00 | 0.167833E+10 | 0.432777E+09 | 0.00 | 0.64 |
April | 0.187946E+10 | 0.00 | 0.00 | 1885597.82 | 0.00 | 0.534104E+09 | 0.992779E+09 | 0.00 | 0.93 |
May | 0.155585E+10 | 1579763.60 | 0.00 | 3970700.62 | 585909.74 | 0.310368E+09 | 0.180666E+10 | 0.00 | 1.25 |
June | 0.994544E+09 | 38028566.29 | 0.00 | 6497979.86 | 1204062.12 | 14639021.44 | 0.179141E+10 | 0.00 | 1.64 |
July | 0.536027E+09 | 83807441.96 | 0.00 | 6407072.27 | 1889109.06 | 0.00 | 0.992425E+09 | 0.00 | 1.38 |
August | 0.836916E+09 | 44499193.94 | 0.00 | 5517020.79 | 1957456.63 | 5784732.34 | 0.122694E+10 | 0.00 | 1.44 |
September | 0.144757E+10 | 81744522.10 | 0.00 | 2556629.84 | 1528827.04 | 0.122821E+09 | 0.102561E+10 | 0.00 | 1.22 |
October | 0.182308E+10 | 0.00 | 0.00 | 1097588.05 | 0.00 | 0.536278E+09 | 0.603754E+09 | 0.00 | 0.89 |
November | 0.121521E+10 | 0.00 | 0.00 | 145933.03 | 0.00 | 0.153128E+10 | 0.158444E+09 | 0.00 | 0.63 |
December | 0.577485E+09 | 0.00 | 0.00 | 58.49 | 0.00 | 0.300962E+10 | 2754380.93 | 0.00 | 0.52 |
Annual Sum or Average | 0.136029E+11 | 0.249659E+09 | 0.00 | 29077810.91 | 7165364.58 | 0.140406E+11 | 0.917563E+10 | 0.00 | 0.97 |
Minimum of Months | 0.357558E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.187946E+10 | 83807441.96 | 0.00 | 6497979.86 | 1957456.63 | 0.390377E+10 | 0.180666E+10 | 0.00 | 1.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 74780253.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471442E+10 | 0.00 | 0.00 | 0.33 |
February | 0.435675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279416E+10 | 0.00 | 0.00 | 0.31 |
March | 0.114781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187356E+10 | 0.00 | 0.00 | 0.31 |
April | 0.176704E+10 | 0.00 | 0.00 | 6944.68 | 0.00 | 0.566827E+09 | 6936226.40 | 0.00 | 0.37 |
May | 0.177557E+10 | 1635700.47 | 0.00 | 665316.50 | 1435009.17 | 0.207348E+09 | 0.310408E+09 | 0.00 | 0.45 |
June | 0.702966E+09 | 33079117.14 | 0.00 | 3618382.29 | 5888305.87 | 0.00 | 0.122441E+10 | 0.00 | 0.67 |
July | 0.301417E+09 | 84915061.15 | 0.00 | 4133441.19 | 4499052.03 | 0.00 | 0.872867E+09 | 0.00 | 0.64 |
August | 0.565674E+09 | 46347703.54 | 0.00 | 3841457.03 | 3871549.10 | 0.00 | 0.106535E+10 | 0.00 | 0.66 |
September | 0.130093E+10 | 48641497.28 | 0.00 | 1831809.35 | 3442815.26 | 9471920.07 | 0.734431E+09 | 0.00 | 0.57 |
October | 0.205973E+10 | 0.00 | 0.00 | 248039.57 | 0.00 | 0.115436E+09 | 0.217490E+09 | 0.00 | 0.41 |
November | 0.146365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114758E+10 | 0.00 | 0.00 | 0.32 |
December | 0.382274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310608E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.119775E+11 | 0.214619E+09 | 0.00 | 14345390.60 | 19136731.43 | 0.145349E+11 | 0.443189E+10 | 0.00 | 0.45 |
Minimum of Months | 74780253.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.205973E+10 | 84915061.15 | 0.00 | 4133441.19 | 5888305.87 | 0.471442E+10 | 0.122441E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.246814E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355344E+10 | 0.00 | 0.00 | 0.42 |
February | 0.811799E+09 | 0.00 | 0.00 | 19471.29 | 0.00 | 0.195380E+10 | 29513553.72 | 0.00 | 0.44 |
March | 0.155525E+10 | 0.00 | 0.00 | 170024.17 | 0.00 | 0.114298E+10 | 0.102288E+09 | 0.00 | 0.46 |
April | 0.146579E+10 | 0.00 | 0.00 | 1054095.64 | 0.00 | 0.252873E+09 | 0.669492E+09 | 0.00 | 0.60 |
May | 0.120076E+10 | 2302448.17 | 0.00 | 2402158.71 | 592609.97 | 0.115427E+09 | 0.119256E+10 | 0.00 | 0.81 |
June | 0.450131E+09 | 37450497.15 | 0.00 | 6342320.87 | 5559865.95 | 0.00 | 0.211246E+10 | 0.00 | 1.43 |
July | 0.179565E+09 | 86062082.81 | 0.00 | 7767929.01 | 3264649.92 | 0.00 | 0.163852E+10 | 0.00 | 1.48 |
August | 0.362016E+09 | 52795162.09 | 0.00 | 6839357.24 | 3588740.23 | 0.00 | 0.201504E+10 | 0.00 | 1.50 |
September | 0.863787E+09 | 42783737.48 | 0.00 | 3418565.54 | 2988379.04 | 1133613.73 | 0.148998E+10 | 0.00 | 1.05 |
October | 0.160284E+10 | 0.00 | 0.00 | 1273226.87 | 0.00 | 51663786.42 | 0.732427E+09 | 0.00 | 0.67 |
November | 0.155931E+10 | 0.00 | 0.00 | 43821.18 | 0.00 | 0.842302E+09 | 38112038.74 | 0.00 | 0.48 |
December | 0.713295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230913E+10 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.110114E+11 | 0.221394E+09 | 0.00 | 29330970.53 | 15994245.11 | 0.102227E+11 | 0.100204E+11 | 0.00 | 0.81 |
Minimum of Months | 0.179565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.160284E+10 | 86062082.81 | 0.00 | 7767929.01 | 5559865.95 | 0.355344E+10 | 0.211246E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.640812E+09 | 0.00 | 0.00 | 14868.31 | 0.00 | 0.629115E+10 | 11240401.74 | 0.00 | 0.47 |
February | 0.911409E+09 | 0.00 | 0.00 | 930481.76 | 0.00 | 0.351504E+10 | 0.510432E+09 | 0.00 | 0.51 |
March | 0.137441E+10 | 0.00 | 0.00 | 981379.71 | 0.00 | 0.257182E+10 | 0.624563E+09 | 0.00 | 0.47 |
April | 0.141966E+10 | 0.00 | 0.00 | 1044576.21 | 0.00 | 0.141078E+10 | 0.645675E+09 | 0.00 | 0.56 |
May | 0.167897E+10 | 3716257.36 | 0.00 | 1822601.06 | 1285756.96 | 0.935982E+09 | 0.689550E+09 | 0.00 | 0.67 |
June | 0.119602E+10 | 58861243.25 | 0.00 | 4022156.69 | 6875993.50 | 0.162561E+09 | 0.105630E+10 | 0.00 | 0.88 |
July | 0.501744E+09 | 0.151877E+09 | 0.00 | 5839528.82 | 5458476.05 | 23482025.98 | 0.997474E+09 | 0.00 | 0.91 |
August | 0.646637E+09 | 0.107665E+09 | 0.00 | 7771880.91 | 3609831.93 | 0.115965E+09 | 0.173043E+10 | 0.00 | 1.18 |
September | 0.111398E+10 | 0.127577E+09 | 0.00 | 6298260.11 | 1313635.14 | 0.267524E+09 | 0.223614E+10 | 0.00 | 1.16 |
October | 0.151355E+10 | 0.00 | 0.00 | 5073544.47 | 0.00 | 0.549045E+09 | 0.239843E+10 | 0.00 | 0.90 |
November | 0.157001E+10 | 0.00 | 0.00 | 1452987.30 | 0.00 | 0.164980E+10 | 0.939675E+09 | 0.00 | 0.52 |
December | 0.100157E+10 | 0.00 | 0.00 | 143522.43 | 0.00 | 0.411721E+10 | 0.134067E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.135688E+11 | 0.449697E+09 | 0.00 | 35395787.78 | 18543693.58 | 0.216104E+11 | 0.119740E+11 | 0.00 | 0.72 |
Minimum of Months | 0.501744E+09 | 0.00 | 0.00 | 14868.31 | 0.00 | 23482025.98 | 11240401.74 | 0.00 | 0.42 |
Maximum of Months | 0.167897E+10 | 0.151877E+09 | 0.00 | 7771880.91 | 6875993.50 | 0.629115E+10 | 0.239843E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.269049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379463E+10 | 0.00 | 0.00 | 0.46 |
February | 0.808286E+09 | 0.00 | 0.00 | 103491.42 | 0.00 | 0.215825E+10 | 67274954.24 | 0.00 | 0.48 |
March | 0.154925E+10 | 0.00 | 0.00 | 298115.44 | 0.00 | 0.136407E+10 | 0.160590E+09 | 0.00 | 0.50 |
April | 0.179087E+10 | 0.00 | 0.00 | 772689.95 | 0.00 | 0.348119E+09 | 0.408380E+09 | 0.00 | 0.66 |
May | 0.151102E+10 | 1857827.43 | 0.00 | 2305194.18 | 1478459.76 | 0.137244E+09 | 0.970996E+09 | 0.00 | 0.87 |
June | 0.712341E+09 | 45480574.79 | 0.00 | 4394936.69 | 4093255.05 | 254172.05 | 0.141724E+10 | 0.00 | 1.20 |
July | 0.303544E+09 | 0.108791E+09 | 0.00 | 4990575.98 | 2284092.70 | 0.00 | 0.944155E+09 | 0.00 | 1.11 |
August | 0.548117E+09 | 58839855.22 | 0.00 | 4718203.71 | 2072031.69 | 0.00 | 0.118054E+10 | 0.00 | 1.17 |
September | 0.117454E+10 | 68062697.35 | 0.00 | 2600661.42 | 1160705.85 | 2260194.75 | 0.107006E+10 | 0.00 | 1.03 |
October | 0.192724E+10 | 0.00 | 0.00 | 1064938.48 | 0.00 | 76506670.37 | 0.594188E+09 | 0.00 | 0.74 |
November | 0.154109E+10 | 0.00 | 0.00 | 156333.22 | 0.00 | 0.965409E+09 | 0.155184E+09 | 0.00 | 0.53 |
December | 0.680510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258491E+10 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.128159E+11 | 0.283032E+09 | 0.00 | 21405140.48 | 11088545.04 | 0.114317E+11 | 0.696861E+10 | 0.00 | 0.77 |
Minimum of Months | 0.269049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.192724E+10 | 0.108791E+09 | 0.00 | 4990575.98 | 4093255.05 | 0.379463E+10 | 0.141724E+10 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442050E+10 | 0.00 | 0.00 | 0.32 |
February | 0.696558E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231710E+10 | 0.00 | 0.00 | 0.30 |
March | 0.174808E+10 | 0.00 | 0.00 | 288.21 | 0.00 | 0.119559E+10 | 4610259.04 | 0.00 | 0.31 |
April | 0.187082E+10 | 0.00 | 0.00 | 479762.37 | 0.00 | 0.207980E+09 | 0.324582E+09 | 0.00 | 0.39 |
May | 0.138462E+10 | 3377939.85 | 0.00 | 2304205.54 | 1874866.33 | 0.113222E+09 | 0.104185E+10 | 0.00 | 0.55 |
June | 0.493464E+09 | 47649550.02 | 0.00 | 5963061.42 | 5201576.61 | 0.00 | 0.197813E+10 | 0.00 | 0.90 |
July | 0.249282E+09 | 0.101414E+09 | 0.00 | 5698794.49 | 3133329.41 | 0.00 | 0.117084E+10 | 0.00 | 0.80 |
August | 0.476461E+09 | 59505540.00 | 0.00 | 5249667.97 | 4028174.56 | 0.00 | 0.139108E+10 | 0.00 | 0.80 |
September | 0.114471E+10 | 62143291.01 | 0.00 | 2398283.73 | 3218114.37 | 13172918.07 | 0.925864E+09 | 0.00 | 0.60 |
October | 0.183998E+10 | 0.00 | 0.00 | 496478.81 | 0.00 | 0.181205E+09 | 0.300986E+09 | 0.00 | 0.41 |
November | 0.137110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114271E+10 | 0.00 | 0.00 | 0.32 |
December | 0.447269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296097E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.118526E+11 | 0.274090E+09 | 0.00 | 22590542.55 | 17456061.28 | 0.125524E+11 | 0.713794E+10 | 0.00 | 0.50 |
Minimum of Months | 0.130239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.187082E+10 | 0.101414E+09 | 0.00 | 5963061.42 | 5201576.61 | 0.442050E+10 | 0.197813E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.388745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384986E+10 | 0.00 | 0.00 | 0.49 |
February | 0.107271E+10 | 0.00 | 0.00 | 115636.11 | 0.00 | 0.212722E+10 | 62908644.75 | 0.00 | 0.53 |
March | 0.204256E+10 | 0.00 | 0.00 | 623445.53 | 0.00 | 0.108511E+10 | 0.306728E+09 | 0.00 | 0.57 |
April | 0.179648E+10 | 0.00 | 0.00 | 2248178.41 | 0.00 | 0.165248E+09 | 0.125797E+10 | 0.00 | 0.82 |
May | 0.132199E+10 | 4011565.05 | 0.00 | 3868691.23 | 830289.07 | 0.136319E+09 | 0.190776E+10 | 0.00 | 1.10 |
June | 0.524809E+09 | 39566703.41 | 0.00 | 8283818.21 | 5915657.77 | 320554.96 | 0.269660E+10 | 0.00 | 1.76 |
July | 0.248220E+09 | 84210188.32 | 0.00 | 9244110.44 | 2870743.30 | 0.00 | 0.191821E+10 | 0.00 | 1.72 |
August | 0.526746E+09 | 56826452.70 | 0.00 | 7326497.81 | 4630477.29 | 0.00 | 0.220432E+10 | 0.00 | 1.68 |
September | 0.119060E+10 | 50644248.59 | 0.00 | 3507472.64 | 3541216.74 | 8399418.71 | 0.149875E+10 | 0.00 | 1.17 |
October | 0.195348E+10 | 0.00 | 0.00 | 1185771.71 | 0.00 | 0.140537E+09 | 0.686908E+09 | 0.00 | 0.78 |
November | 0.168419E+10 | 0.00 | 0.00 | 66442.42 | 0.00 | 0.112516E+10 | 46251650.65 | 0.00 | 0.58 |
December | 0.779742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280298E+10 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.135303E+11 | 0.235259E+09 | 0.00 | 36470064.54 | 17788384.18 | 0.114411E+11 | 0.125864E+11 | 0.00 | 0.98 |
Minimum of Months | 0.248220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.204256E+10 | 84210188.32 | 0.00 | 9244110.44 | 5915657.77 | 0.384986E+10 | 0.269660E+10 | 0.00 | 1.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.113415E+10 | 0.00 | 0.00 | 960673.77 | 0.00 | 0.378293E+10 | 0.711303E+09 | 0.00 | 0.41 |
February | 0.142513E+10 | 0.00 | 0.00 | 3356149.04 | 0.00 | 0.189609E+10 | 0.163002E+10 | 0.00 | 0.59 |
March | 0.212907E+10 | 0.00 | 0.00 | 5225236.41 | 0.00 | 0.112224E+10 | 0.239255E+10 | 0.00 | 0.64 |
April | 0.196661E+10 | 0.00 | 0.00 | 4872081.45 | 0.00 | 0.242798E+09 | 0.244128E+10 | 0.00 | 0.83 |
May | 0.169007E+10 | 9607286.17 | 0.00 | 5629163.25 | 1036141.72 | 0.175640E+09 | 0.251014E+10 | 0.00 | 0.97 |
June | 0.943137E+09 | 71839893.58 | 0.00 | 7765721.78 | 4480065.83 | 332914.36 | 0.247211E+10 | 0.00 | 1.24 |
July | 0.496658E+09 | 0.150180E+09 | 0.00 | 7858124.17 | 4221546.07 | 0.00 | 0.147541E+10 | 0.00 | 1.12 |
August | 0.737220E+09 | 0.121483E+09 | 0.00 | 9658875.04 | 3872967.26 | 321709.91 | 0.236266E+10 | 0.00 | 1.43 |
September | 0.123563E+10 | 0.153789E+09 | 0.00 | 8113430.51 | 2051215.70 | 17394901.96 | 0.310842E+10 | 0.00 | 1.39 |
October | 0.169468E+10 | 0.00 | 0.00 | 8283646.56 | 0.00 | 0.109324E+09 | 0.361281E+10 | 0.00 | 1.11 |
November | 0.164474E+10 | 0.00 | 0.00 | 4451984.89 | 0.00 | 0.102248E+10 | 0.213440E+10 | 0.00 | 0.64 |
December | 0.145674E+10 | 0.00 | 0.00 | 1744068.83 | 0.00 | 0.252692E+10 | 0.905739E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.165538E+11 | 0.506900E+09 | 0.00 | 67919155.69 | 15661936.58 | 0.108965E+11 | 0.257569E+11 | 0.00 | 0.90 |
Minimum of Months | 0.496658E+09 | 0.00 | 0.00 | 960673.77 | 0.00 | 0.00 | 0.711303E+09 | 0.00 | 0.41 |
Maximum of Months | 0.212907E+10 | 0.153789E+09 | 0.00 | 9658875.04 | 4480065.83 | 0.378293E+10 | 0.361281E+10 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.444613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402568E+10 | 0.00 | 0.00 | 0.52 |
February | 0.106002E+10 | 0.00 | 0.00 | 265777.75 | 0.00 | 0.228064E+10 | 0.152524E+09 | 0.00 | 0.57 |
March | 0.199803E+10 | 0.00 | 0.00 | 881161.09 | 0.00 | 0.128283E+10 | 0.445513E+09 | 0.00 | 0.63 |
April | 0.211723E+10 | 0.00 | 0.00 | 1953895.08 | 0.00 | 0.236822E+09 | 0.966970E+09 | 0.00 | 0.90 |
May | 0.158437E+10 | 2951393.37 | 0.00 | 4048365.90 | 2433711.69 | 0.155772E+09 | 0.170505E+10 | 0.00 | 1.17 |
June | 0.834217E+09 | 54359276.74 | 0.00 | 5847784.47 | 4795704.01 | 566926.44 | 0.181032E+10 | 0.00 | 1.50 |
July | 0.463057E+09 | 0.121784E+09 | 0.00 | 6077596.42 | 1574140.26 | 0.00 | 0.981780E+09 | 0.00 | 1.28 |
August | 0.751997E+09 | 68226911.66 | 0.00 | 5173102.59 | 2589717.54 | 273870.98 | 0.124688E+10 | 0.00 | 1.36 |
September | 0.147495E+10 | 88831005.04 | 0.00 | 2780614.22 | 744365.37 | 16640465.85 | 0.109904E+10 | 0.00 | 1.17 |
October | 0.213098E+10 | 0.00 | 0.00 | 1315128.01 | 0.00 | 0.204230E+09 | 0.689059E+09 | 0.00 | 0.87 |
November | 0.159767E+10 | 0.00 | 0.00 | 266867.21 | 0.00 | 0.122825E+10 | 0.230849E+09 | 0.00 | 0.62 |
December | 0.834680E+09 | 0.00 | 0.00 | 3535.17 | 0.00 | 0.295542E+10 | 8545808.28 | 0.00 | 0.52 |
Annual Sum or Average | 0.152918E+11 | 0.336153E+09 | 0.00 | 28613827.91 | 12137638.86 | 0.123871E+11 | 0.933653E+10 | 0.00 | 0.93 |
Minimum of Months | 0.444613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.213098E+10 | 0.121784E+09 | 0.00 | 6077596.42 | 4795704.01 | 0.402568E+10 | 0.181032E+10 | 0.00 | 1.50 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.155396E+12 | 0.294433E+11 | 0.00 | 0.152735E+12 | 0.153112E+11 |
February | 0.204321E+12 | 0.226567E+11 | 0.00 | 0.151548E+12 | 0.903951E+10 |
March | 0.329823E+12 | 0.215578E+11 | 0.00 | 0.183447E+12 | 0.516441E+10 |
April | 0.346955E+12 | 0.150105E+11 | 0.00 | 0.213457E+12 | 0.864095E+10 |
May | 0.454302E+12 | 0.146667E+11 | 0.00 | 0.225333E+12 | 0.300316E+11 |
June | 0.489538E+12 | 0.723660E+10 | 0.00 | 0.209406E+12 | 0.106981E+12 |
July | 0.485967E+12 | 0.404616E+10 | 0.00 | 0.178027E+12 | 0.183970E+12 |
August | 0.408039E+12 | 0.528854E+10 | 0.00 | 0.204325E+12 | 0.154635E+12 |
September | 0.313707E+12 | 0.972140E+10 | 0.00 | 0.208548E+12 | 0.710043E+11 |
October | 0.212080E+12 | 0.145468E+11 | 0.00 | 0.231244E+12 | 0.151626E+11 |
November | 0.122643E+12 | 0.201290E+11 | 0.00 | 0.181433E+12 | 0.440490E+10 |
December | 0.102497E+12 | 0.255208E+11 | 0.00 | 0.153676E+12 | 0.101097E+11 |
Annual Sum or Average | 0.362527E+13 | 0.189824E+12 | 0.00 | 0.229318E+13 | 0.614455E+12 |
Minimum of Months | 0.102497E+12 | 0.404616E+10 | 0.00 | 0.151548E+12 | 0.440490E+10 |
Maximum of Months | 0.489538E+12 | 0.294433E+11 | 0.00 | 0.231244E+12 | 0.183970E+12 |