Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 08:28:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1602.35 | 321.62 | 321.62 |
Net Site Energy | 1602.35 | 321.62 | 321.62 |
Total Source Energy | 4803.56 | 964.15 | 964.15 |
Net Source Energy | 4803.56 | 964.15 | 964.15 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 7.21 | 1.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 177.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 364.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 111.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 88.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 128.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1472.21 | 130.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 7.21 | 1.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 177.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 364.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 111.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 17.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 88.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 128.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 7.21 | 1.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 177.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 364.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 111.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 17.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 88.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 128.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 95.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 54.86 | 26.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 145.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 295.50 | 26.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 95.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 54.86 | 26.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 145.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 295.50 | 26.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1472.212 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1472.212 | 100.00 |
Total On-Site and Utility Electric Sources | 1472.212 | 100.00 |
Total Electricity End Uses | 1472.212 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 17.50 |
Time Setpoint Not Met During Occupied Cooling | 98.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 515.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 10.1959 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 10.1959 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.1959 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 10.1959 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
Total | 4982.19 | 10.1959 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 10.1959 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 10.1959 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-OCT-10:00 | 09-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 19890.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 64935.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 30098.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41577.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1224.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12169.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8931.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 150012.36 | 28822.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 19890.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 64935.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 30098.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 7036.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 53.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1224.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 12169.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8931.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 22.85 | 1.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 561.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1154.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 354.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 54.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 281.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 139.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4662.50 | 141.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 4.59 | 0.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 231.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 56.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 935.83 | 28.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 4.59 | 0.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 231.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 56.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 935.83 | 28.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.09 | 0.242636 | 0.254000 | 0.784555 | 0.647030 | 0.500000 | 0.001570 |
CORE_MID VAV BOX COMPONENT | 2.30 | 0.325618 | 0.328000 | 0.754939 | 0.868313 | 0.500000 | 0.001170 |
CORE_TOP VAV BOX COMPONENT | 2.34 | 0.320270 | 0.334000 | 0.781583 | 0.854054 | 0.500000 | 0.001190 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.671117 | 0.235416 | 0.246000 | 0.165095 | 0.627776 | 0.500000 | 0.001618 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.699586 | 0.142973 | 0.200000 | 0.139917 | 0.381261 | 0.500000 | 0.002665 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.894366 | 0.176652 | 0.200000 | 0.178873 | 0.471072 | 0.500000 | 0.002157 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.783963 | 0.127576 | 0.200000 | 0.156793 | 0.340204 | 0.500000 | 0.002986 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.543403 | 0.290745 | 0.304000 | 0.165195 | 0.775319 | 0.500000 | 0.001310 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.602171 | 0.166102 | 0.200000 | 0.120434 | 0.442939 | 0.500000 | 0.002294 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.743133 | 0.212602 | 0.222000 | 0.164976 | 0.566939 | 0.500000 | 0.001792 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.643039 | 0.155535 | 0.200000 | 0.128608 | 0.414761 | 0.500000 | 0.002450 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.595304 | 0.265397 | 0.268000 | 0.159542 | 0.707724 | 0.500000 | 0.001436 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.691256 | 0.144696 | 0.200000 | 0.138251 | 0.385855 | 0.500000 | 0.002633 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.814819 | 0.193898 | 0.200000 | 0.162964 | 0.517061 | 0.500000 | 0.001965 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.725417 | 0.137873 | 0.200000 | 0.145083 | 0.367661 | 0.500000 | 0.002763 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25716.13 |
CORE_MID VAV BOX REHEAT COIL | 24745.37 |
CORE_TOP VAV BOX REHEAT COIL | 28011.02 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 11891.47 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 7772.68 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 11918.51 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7751.94 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8807.74 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5887.35 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8867.46 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5848.28 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 9606.37 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 6389.65 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 9650.97 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 6351.70 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.81 | 1.36 | 5.62 | 1.36 | 5.04 | 5.04 | 0.300000 | 0.270506 | 5.04 |
PACU_VAV_MID | 2.56 | 1.36 | 5.13 | 1.45 | 4.43 | 4.43 | 0.300000 | 0.327207 | 4.43 |
PACU_VAV_TOP | 2.69 | 1.42 | 5.39 | 2.13 | 5.02 | 5.02 | 0.300000 | 0.424909 | 5.02 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.04 |
PACU_VAV_MID_OA_CONTROLLER | 4.43 |
PACU_VAV_TOP_OA_CONTROLLER | 5.02 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.04 | 89465.33 | 0.800957 | 1.68 | 29818.79 | 0.800957 |
PACU_VAV_MID COOLING COIL | 4.43 | 79916.64 | 0.800729 | 1.48 | 26636.21 | 0.800729 |
PACU_VAV_TOP COOLING COIL | 5.02 | 89188.90 | 0.800676 | 1.67 | 29726.66 | 0.800676 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 9684.02 |
PACU_VAV_MID HEATING COIL | 11456.46 |
PACU_VAV_TOP HEATING COIL | 10612.20 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.04 |
PACU_VAV_MID FAN | 4.43 |
PACU_VAV_TOP FAN | 5.02 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 35.030 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9622 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9482 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.202 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8052 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8206 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5978 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27384127E-12 | 0.12865281E-14 | -0.83346422E-13 | 0.81323336E-16 |
43 | 6 | 0.26454352E-07 | 0.26406074E-09 | 0.60786733E-08 | -0.12333448E-12 |
44 | 5 | -0.17878666E-03 | 0.22931636E-05 | -0.92101048E-04 | 0.60153540E-08 |
45 | 4 | 0.27880517 | 0.11305828E-02 | 0.94889811E-01 | -0.31698392E-04 |
46 | 3 | -7.0018852 | 0.35426556E-01 | -2.2604600 | 0.27713709E-01 |
47 | 2 | 39.998753 | 0.12720283 | 14.942758 | -0.32362551 |
48 | 1 | -79.877006 | 0.57894353E-01 | -28.852534 | 1.0643678 |
49 | 0 | 46.824343 | 0.11744712E-02 | 16.298269 | |
50 | 7 | -0.27620064E-12 | 0.12774393E-14 | -0.83964131E-13 | 0.81942822E-16 |
51 | 6 | 0.26622461E-07 | 0.26074659E-09 | 0.61157793E-08 | -0.12423095E-12 |
52 | 5 | -0.17965003E-03 | 0.22617301E-05 | -0.92535175E-04 | 0.60516003E-08 |
53 | 4 | 0.27982997 | 0.11139309E-02 | 0.95257664E-01 | -0.31841476E-04 |
54 | 3 | -7.0222151 | 0.34872839E-01 | -2.2664901 | 0.27813240E-01 |
55 | 2 | 40.065841 | 0.12511414 | 14.967577 | -0.32437249 |
56 | 1 | -79.928458 | 0.56904129E-01 | -28.874810 | 1.0654641 |
57 | 0 | 46.824343 | 0.11535943E-02 | 16.297719 | |
58 | 7 | -0.27931930E-12 | 0.13886628E-14 | -0.87137092E-13 | 0.18759942E-15 |
59 | 6 | 0.23561308E-07 | 0.31712788E-09 | 0.54400317E-08 | -0.10799411E-12 |
60 | 5 | -0.16378969E-03 | 0.28142694E-05 | -0.84539011E-04 | 0.53904798E-08 |
61 | 4 | 0.26080053 | 0.14141629E-02 | 0.88437074E-01 | -0.29205444E-04 |
62 | 3 | -6.6442204 | 0.45062581E-01 | -2.1544048 | 0.25964059E-01 |
63 | 2 | 38.817908 | 0.16418932 | 14.505027 | -0.31048073 |
64 | 1 | -78.970774 | 0.75677137E-01 | -28.459322 | 1.0450580 |
65 | 0 | 46.824349 | 0.15543837E-02 | 16.308247 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.498_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.498_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00974E-002 | 0.16139 | 0.61139 | 0.61139 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00974E-002 | 0.16139 | 0.61139 | 0.61139 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00974E-002 | 0.16139 | 0.61139 | 0.61139 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00974E-002 | 0.16139 | 0.61139 | 0.61139 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.973 | 0.1730 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2885E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3354E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8753E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9161E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4345E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4669E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9164E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9329E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1053 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9111E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1180 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3761E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8297E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1553E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2073E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2006E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2871E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3300E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8738E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9102E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4332E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4626E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9162E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9327E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3213E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5363E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8996E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2524E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2517E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1439E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7685E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7749E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0666E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0835E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7449E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7570E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7228E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7269E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4038E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4095E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9605E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9981E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4878E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5172E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1732E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1926E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9162E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9327E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7561E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5682E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1301E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1982E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9552E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.2731E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2073E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2006E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9610E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9984E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4884E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5182E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1742E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1954E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9164E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9329E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7688E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7436E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4468E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5063E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6566E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3288E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7686E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7749E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.3689E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.4140E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1177E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1660E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9798E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9999E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4040E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4097E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1052 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.0331E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1159 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5820E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3461E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.0350E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6593E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.7065E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1820E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4577E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7823E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1866E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1561E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.0877E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6984E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7326E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1580E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0630E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4889E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6260E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3127E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2199E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6593E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7065E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.6162E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6567E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.3130E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4305E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.5496E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2653E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6984E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7326E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1052 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.0324E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1159 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5813E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3456E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.0345E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6589E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.7063E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1820E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4575E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7822E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1864E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1558E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.0874E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6980E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7324E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1581E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0629E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4890E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6259E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3125E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2197E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6589E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7063E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.6161E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6566E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.3129E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4303E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.5493E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2651E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6980E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7324E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 42064.54818 | 42064.54818 | 3.08880 | 3.08880 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 4446.14656 | 4446.14656 | 0.19128 | 0.42469 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 31378.08129 | 31378.08129 | 2.30164 | 2.30164 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 11052.87612 | 11052.87612 | 0.47487 | 0.47487 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 31608.74103 | 31608.74103 | 2.34007 | 2.34007 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30000 | 8.23349E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 19766.96020 | 19766.96020 | 0.85457 | 0.85457 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9065.37670 | 9065.37670 | 0.67112 | 0.67112 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30000 | 8.23349E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 9071.62711 | 9071.62711 | 0.36279 | 0.36279 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9449.98738 | 9449.98738 | 0.69959 | 0.69959 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 26.65717 | 8.22614E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 5923.85103 | 5923.85103 | 0.23713 | 0.23713 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80000 | 5.05843E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 12081.03564 | 12081.03564 | 0.89437 | 0.89437 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.07750 | 8.23314E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 9091.58069 | 9091.58069 | 0.36361 | 0.36361 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10589.75694 | 10589.75694 | 0.78396 | 0.78396 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 5908.64309 | 5908.64309 | 0.23650 | 0.23650 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80000 | 5.05843E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7340.18514 | 7340.18514 | 0.54340 | 0.54340 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30000 | 8.23349E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 6198.85590 | 6198.85590 | 0.26871 | 0.26871 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8134.06067 | 8134.06067 | 0.60217 | 0.60217 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 26.65717 | 8.22614E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 4142.57609 | 4142.57609 | 0.17961 | 0.17961 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10038.12298 | 10038.12298 | 0.74313 | 0.74313 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.23302E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 6240.69686 | 6240.69686 | 0.27053 | 0.27053 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8686.10544 | 8686.10544 | 0.64304 | 0.64304 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 30.05400 | 8.23151E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 4115.19034 | 4115.19034 | 0.17842 | 0.17842 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8041.28540 | 8041.28540 | 0.59530 | 0.59530 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.23349E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 6759.51576 | 6759.51576 | 0.29307 | 0.29307 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9337.45303 | 9337.45303 | 0.69126 | 0.69126 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 26.12317 | 8.22530E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 4495.31691 | 4495.31691 | 0.19494 | 0.19494 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11006.48749 | 11006.48749 | 0.81482 | 0.81482 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.23290E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 6790.78310 | 6790.78310 | 0.29443 | 0.29443 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9798.88798 | 9798.88798 | 0.72542 | 0.72542 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4468.73447 | 4468.73447 | 0.19378 | 0.19378 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 77409.07 | 5.04154 | 5.04154 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 12769.12 | 1.32196 | 1.32196 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 69338.07 | 4.43479 | 4.43479 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 12770.75 | 1.45110 | 1.45110 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 77128.92 | 5.02183 | 5.02183 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 11999.96 | 2.13382 | 2.13382 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.08880 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24264 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25400 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78455 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64703 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57025E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25716.13052 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.30164 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32562 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32800 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.75494 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86831 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.17008E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24745.37204 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.34007 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32027 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33400 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78158 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85405 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18962E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 28011.02358 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67112 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23542 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24600 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16509 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62778 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61841E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11891.46710 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69959 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14297 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13992 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38126 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.66484E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7772.68445 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89437 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17665 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17887 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47107 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.15678E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11918.51198 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78396 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12758 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15679 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34020 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.98645E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7751.94434 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.54340 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29074 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30400 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16519 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77532 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.31043E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8807.74297 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60217 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16610 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12043 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44294 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.29377E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5887.35347 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74313 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21260 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22200 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16498 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56694 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79208E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8867.46259 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64304 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15554 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12861 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41476 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.44961E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5848.27720 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59530 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26540 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26800 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15954 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70772 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.43559E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9606.36741 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69126 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14470 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13825 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38586 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.63311E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6389.64610 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81482 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19390 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16296 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51706 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.96495E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9650.96918 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72542 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13787 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14508 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36766 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.76342E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6351.69622 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.81027 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36377 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.62054 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.36377 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.04154 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.04154 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.27051 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.56422 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36078 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.12844 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.45110 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.43479 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.43479 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.32721 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.69455 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.42226 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.38910 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.13382 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.02183 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.02183 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.42491 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.04154 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.43479 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.02183 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.04154 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.04154 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 89465.32961 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80096 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.68034 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 29818.79436 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80096 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 9684.01883 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.04154 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.43479 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.43479 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 79916.63552 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80073 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.47812 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 26636.21462 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80073 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 11456.46438 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.43479 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.02183 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.02183 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 89188.89537 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80068 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.67378 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 29726.65883 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80068 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 10612.19884 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.02183 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 88206.61 | 300973.45 | 10.98 | 2.83 | 3.14 | 3.31 | 3.49 | 9.66 | 10.72 | 11.29 | 11.91 | 5.7227 | 4.5422 | 3.0495 | 1.2369 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 78845.35 | 269031.51 | 11.02 | 2.84 | 3.15 | 3.32 | 3.50 | 9.68 | 10.76 | 11.32 | 11.95 | 5.0340 | 4.0007 | 2.6869 | 1.0826 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 87937.26 | 300054.39 | 10.98 | 2.83 | 3.14 | 3.31 | 3.49 | 9.66 | 10.72 | 11.29 | 11.91 | 5.7003 | 4.5246 | 3.0378 | 1.2323 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.0687569248E-003 | 5.0795839568E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.6951750020E-002 | 4.3844521927E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.0650844491E-002 | 6.9230496424E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.9477298614E-003 | 6.2771325606E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.9897621215E-003 | 5.5584254923E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.8149138866E-002 | 1.0872381370E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.1297215901E-002 | 2.1764314247E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.7775784371E-002 | 9.0539229596E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.2893488142E-002 | 7.5475653841E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.5843935724E-002 | 3.5119310211E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.2456905707E-002 | 1.8747591612E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.7062197349E-002 | 7.8888495242E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.7314918258E-002 | 6.1867201996E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.3600554090E-002 | 3.1814084155E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.5365487380E-002 | 2.0183649099E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.7296794703E-002 | 9.2909992954E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.0706900128E-002 | 7.6765441825E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.9016096105E-002 | 3.4984915681E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3539.07 | 55.03 | 0.00 | 2293.82 | 900.23 | 6788.18 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.498_SHGC_EAST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.498_SHGC_EAST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.498_SHGC_WEST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.498_SHGC_WEST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.831 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 195.79 | 2.831 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.831 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.35 | 0.0000 | Y | 10.85 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.06 | 0.0000 | Y | 6.80 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.67 | 0.0000 | Y | 10.58 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.96 | 0.0000 | Y | 6.77 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.25 | 0.0000 | Y | 10.81 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.00 | 0.0000 | Y | 6.78 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.64 | 0.0000 | Y | 10.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.90 | 0.0000 | Y | 6.76 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.35 | 0.0000 | Y | 10.85 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.06 | 0.0000 | Y | 6.80 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.67 | 0.0000 | Y | 10.58 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.96 | 0.0000 | Y | 6.77 |
Interior Lighting Total | 10.1959 | 4982.19 | 50797.72 | 364.43 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.28 | AstronomicalClock | - | 42.14 | 42.14 | 4.46 | |
EXTERIOR_LIGHTS_B | 8033.20 | AstronomicalClock | - | 83.75 | 71.27 | 107.47 | |
Exterior Lighting Total | 8596.48 | 111.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 89465.33 | 71657.92 | 17807.41 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 79916.64 | 63991.55 | 15925.08 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 89188.90 | 71411.36 | 17777.53 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 88206.6 | 2.83 | 9.66 | N/A | N/A | 10.98 | |
PACU_VAV_MID COOLING COIL | 78845.4 | 2.84 | 9.68 | N/A | N/A | 11.02 | |
PACU_VAV_TOP COOLING COIL | 87937.3 | 2.83 | 9.66 | N/A | N/A | 10.98 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25716.13 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24745.37 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 28011.02 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11891.47 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7772.68 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11918.51 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7751.94 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8807.74 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5887.35 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8867.46 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5848.28 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9606.37 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6389.65 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9650.97 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6351.70 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 9684.02 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 11456.46 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 10612.20 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.04 | 10964.78 | 2174.89 | 1.00 | 1.14 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.43 | 9707.81 | 2189.01 | 1.00 | 1.14 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.02 | 10992.84 | 2189.01 | 1.00 | 1.13 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.97 | 0.17 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 88206.61 | 2.83 | 9.66 | 10.98 | 5.7227 | 3.14 | 10.72 | 4.5422 | 3.31 | 11.29 | 3.0495 | 3.49 | 11.91 | 1.2369 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 78845.35 | 2.84 | 9.68 | 11.02 | 5.0340 | 3.15 | 10.76 | 4.0007 | 3.32 | 11.32 | 2.6869 | 3.50 | 11.95 | 1.0826 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 87937.26 | 2.83 | 9.66 | 10.98 | 5.7003 | 3.14 | 10.72 | 4.5246 | 3.31 | 11.29 | 3.0378 | 3.49 | 11.91 | 1.2323 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 42064.55 | 42064.55 | 42.77 | 3.089 | 3.089 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00879 | 24.71 | 0.00822 | 0.425 | 0.00 |
CORE_MID | 31378.08 | 31378.08 | 31.90 | 2.302 | 2.302 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 24.71 | 0.00822 | 0.425 | 0.00 |
CORE_TOP | 31608.74 | 31608.74 | 32.14 | 2.340 | 2.340 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00888 | 31.30 | 0.00823 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9065.38 | 9065.38 | 43.72 | 0.671 | 0.671 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00876 | 31.30 | 0.00823 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9449.99 | 9449.99 | 71.99 | 0.700 | 0.700 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00866 | 26.66 | 0.00823 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12081.04 | 12081.04 | 58.27 | 0.894 | 0.894 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00869 | 31.08 | 0.00823 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10589.76 | 10589.76 | 80.68 | 0.784 | 0.784 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00864 | 30.41 | 0.00823 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7340.19 | 7340.19 | 35.40 | 0.543 | 0.543 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00883 | 31.30 | 0.00823 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8134.06 | 8134.06 | 61.97 | 0.602 | 0.602 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00869 | 26.66 | 0.00823 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10038.12 | 10038.12 | 48.41 | 0.743 | 0.743 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00874 | 31.00 | 0.00823 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8686.11 | 8686.11 | 66.18 | 0.643 | 0.643 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00868 | 30.05 | 0.00823 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8041.29 | 8041.29 | 38.78 | 0.595 | 0.595 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00879 | 31.30 | 0.00823 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9337.45 | 9337.45 | 71.14 | 0.691 | 0.691 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00866 | 26.12 | 0.00823 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11006.49 | 11006.49 | 53.08 | 0.815 | 0.815 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00871 | 30.93 | 0.00823 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9798.89 | 9798.89 | 74.66 | 0.725 | 0.725 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00865 | 30.41 | 0.00823 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 4446.15 | 4446.15 | 4.52 | 0.191 | 0.425 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 0.425 | 0.00 |
CORE_MID | 11052.88 | 11052.88 | 11.24 | 0.475 | 0.475 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 0.425 | 0.00 |
CORE_TOP | 19766.96 | 19766.96 | 20.10 | 0.855 | 0.855 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9071.63 | 9071.63 | 43.75 | 0.363 | 0.363 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 21.00 | 20.69 | 0.00754 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 5923.85 | 5923.85 | 45.13 | 0.237 | 0.237 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 21.00 | 20.69 | 0.00756 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9091.58 | 9091.58 | 43.85 | 0.364 | 0.364 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 21.00 | 20.69 | 0.00754 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 5908.64 | 5908.64 | 45.02 | 0.236 | 0.236 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 21.00 | 20.69 | 0.00756 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6198.86 | 6198.86 | 29.90 | 0.269 | 0.269 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00770 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 4142.58 | 4142.58 | 31.56 | 0.180 | 0.180 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 6240.70 | 6240.70 | 30.10 | 0.271 | 0.271 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00770 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 4115.19 | 4115.19 | 31.35 | 0.178 | 0.178 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 6759.52 | 6759.52 | 32.60 | 0.293 | 0.293 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00765 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 4495.32 | 4495.32 | 34.25 | 0.195 | 0.195 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00767 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 6790.78 | 6790.78 | 32.75 | 0.294 | 0.294 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4468.73 | 4468.73 | 34.05 | 0.194 | 0.194 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00767 | 3.80 | 0.00506 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.04 | 5.04 | 1.32 | 1.32 | 5.0415 | 1.3638 | 5.0415 | 0.2705 | 0.3000 |
PACU_VAV_MID | 4.43 | 4.43 | 1.45 | 1.45 | 4.4348 | 1.4511 | 4.4348 | 0.3272 | 0.3000 |
PACU_VAV_TOP | 5.02 | 5.02 | 2.13 | 2.13 | 5.0218 | 2.1338 | 5.0218 | 0.4249 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25716.131 | 25716.131 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25716.13 | 13920.52 | 0.424691 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00799997 | 50.7557 | 4446.15 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24745.372 | 24745.372 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24745.37 | 15565.38 | 0.474873 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 11052.88 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 28011.024 | 28011.024 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 28011.02 | 28011.02 | 0.854568 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 19766.96 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 11891.467 | 11891.467 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 11891.47 | 11891.47 | 0.362788 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 20.69 | 0.00753536 | 48.7513 | 9071.63 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 7772.684 | 7772.684 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 7772.68 | 7772.68 | 0.237131 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 20.69 | 0.00756409 | 48.9357 | 5923.85 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 11918.512 | 11918.512 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 11918.51 | 11918.51 | 0.363613 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 20.69 | 0.00753979 | 48.7797 | 9091.58 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 7751.944 | 7751.944 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 7751.94 | 7751.94 | 0.236498 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 20.69 | 0.00755893 | 48.9026 | 5908.64 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 8807.743 | 8807.743 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8807.74 | 8807.74 | 0.268709 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00770172 | 48.8895 | 6198.86 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5887.353 | 5887.353 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5887.35 | 5887.35 | 0.179613 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00771553 | 48.9761 | 4142.58 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 8867.463 | 8867.463 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8867.46 | 8867.46 | 0.270531 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00770489 | 48.9094 | 6240.70 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 5848.277 | 5848.277 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5848.28 | 5848.28 | 0.178421 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00771248 | 48.9569 | 4115.19 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 9606.367 | 9606.367 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9606.37 | 9606.37 | 0.293074 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00765458 | 48.5945 | 6759.52 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 6389.646 | 6389.646 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6389.65 | 6389.65 | 0.194937 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00766854 | 48.6821 | 4495.32 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 9650.969 | 9650.969 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9650.97 | 9650.97 | 0.294434 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00765701 | 48.6097 | 6790.78 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 6351.696 | 6351.696 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6351.70 | 6351.70 | 0.193779 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00766550 | 48.6630 | 4468.73 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 89465.330 | 71657.917 | 5.041537 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 89364.86 | 86964.82 | 5.041537 | 25.73 | 16.93 | 0.00865930 | 11.00 | 11.00 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 23.7065 | 24.00 | 0.00879161 | 46.4279 | 68099.65 | 0.00 | 92250.76 | 71965.15 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 9684.019 | 9684.019 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9684.02 | 9684.02 | 1.512461 | 7.41 | 6.39 | 0.00565453 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 79.0215 | 21.00 | 0.00786997 | 49.9421 | 21069.46 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 79916.636 | 63991.554 | 4.434793 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 79953.82 | 77728.44 | 4.434793 | 25.97 | 17.02 | 0.00866795 | 10.99 | 10.99 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 26.9498 | 24.00 | 0.00882824 | 46.6185 | 59901.93 | 0.00 | 82404.78 | 64252.54 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 11456.464 | 11456.464 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11456.46 | 11456.46 | 1.330438 | 5.55 | 5.08 | 0.00534224 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 89.8328 | 21.00 | 0.00784123 | 49.7622 | 25880.90 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 89188.895 | 71411.364 | 5.021829 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 89089.25 | 86736.15 | 5.021829 | 25.74 | 16.93 | 0.00865668 | 10.99 | 10.99 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 23.7995 | 24.00 | 0.00878890 | 46.4136 | 67815.17 | 0.00 | 91965.72 | 71718.25 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 10612.199 | 10612.199 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10612.20 | 10612.20 | 1.506549 | 6.87 | 6.02 | 0.00556526 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 79.3317 | 19.60 | 0.00751064 | 52.0046 | 33496.34 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25716.131 | 25716.131 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25716.13 | 13920.52 | 1.0000 | 0.50189087 | 0.424691 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25716.13 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.74 | 0.00799997 | 21.00 | 0.00799997 | 50.7557 | 4446.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24745.372 | 24745.372 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 24745.37 | 15565.38 | 1.0000 | 0.56119454 | 0.474873 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24745.37 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 11052.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 28011.024 | 28011.024 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 28011.02 | 28011.02 | 1.0000 | 1.00991010 | 0.854568 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28011.02 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 19766.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 11891.467 | 11891.467 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | Sensible | 11891.47 | 11891.47 | 1.0000 | 0.42873523 | 0.362788 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11891.47 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 19.48 | 0.00753536 | 20.69 | 0.00753536 | 48.7513 | 9071.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7772.684 | 7772.684 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | Sensible | 7772.68 | 7772.68 | 1.0000 | 0.28023655 | 0.237131 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7772.68 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 19.48 | 0.00756409 | 20.69 | 0.00756409 | 48.9357 | 5923.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 11918.512 | 11918.512 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | Sensible | 11918.51 | 11918.51 | 1.0000 | 0.42971031 | 0.363613 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11918.51 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 19.48 | 0.00753979 | 20.69 | 0.00753979 | 48.7797 | 9091.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7751.944 | 7751.944 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | Sensible | 7751.94 | 7751.94 | 1.0000 | 0.27948878 | 0.236498 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7751.94 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 19.48 | 0.00755893 | 20.69 | 0.00755893 | 48.9026 | 5908.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 8807.743 | 8807.743 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8807.74 | 8807.74 | 1.0000 | 0.31755457 | 0.268709 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8807.74 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00770172 | 21.00 | 0.00770172 | 48.8895 | 6198.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 5887.353 | 5887.353 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5887.35 | 5887.35 | 1.0000 | 0.21226278 | 0.179613 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5887.35 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00771553 | 21.00 | 0.00771553 | 48.9761 | 4142.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 8867.463 | 8867.463 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8867.46 | 8867.46 | 1.0000 | 0.31970770 | 0.270531 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8867.46 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00770489 | 21.00 | 0.00770489 | 48.9094 | 6240.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5848.277 | 5848.277 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5848.28 | 5848.28 | 1.0000 | 0.21085392 | 0.178421 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5848.28 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00771248 | 21.00 | 0.00771248 | 48.9569 | 4115.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 9606.367 | 9606.367 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9606.37 | 9606.37 | 1.0000 | 0.34634820 | 0.293074 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9606.37 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00765458 | 21.00 | 0.00765458 | 48.5945 | 6759.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6389.646 | 6389.646 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6389.65 | 6389.65 | 1.0000 | 0.23037245 | 0.194937 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6389.65 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00766854 | 21.00 | 0.00766854 | 48.6821 | 4495.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 9650.969 | 9650.969 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9650.97 | 9650.97 | 1.0000 | 0.34795627 | 0.294434 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9650.97 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00765701 | 21.00 | 0.00765701 | 48.6097 | 6790.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 6351.696 | 6351.696 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6351.70 | 6351.70 | 1.0000 | 0.22900420 | 0.193779 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6351.70 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00766550 | 21.00 | 0.00766550 | 48.6630 | 4468.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 89465.330 | 71657.917 | 5.041537 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9372 | 1004.8586 | 1.1818 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.041537 | 5.95798117 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 89364.86 | 86964.82 | 0.9989 | 5.95798117 | 5.041537 | 25.73 | 16.93 | 0.00865930 | 47924.8 | 11.00 | 11.00 | 0.00850000 | 32482.4 | -999.0 | -999.00 | -999.00 | -999.00 | 10964.781 | 78400.08 | 31.30 | 0.00823349 | 18.45 | 1.19517000 | 23.7065 | 24.00 | 0.00879161 | 24.00 | 0.00879161 | 46.4279 | 68099.65 | 0.00 | 92250.76 | 71965.15 | 5.72268595 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.37 | 13.98 | 0.00979484 | 39202.2 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9684.019 | 9684.019 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.041537 | 5.95798117 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9684.02 | 9684.02 | 1.0000 | 1.78739435 | 1.512461 | 7.41 | 6.39 | 0.00565453 | 21663.6 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9684.02 | 3.80 | 0.00505843 | 3.80 | 1.19517000 | 79.0215 | 21.00 | 0.00789992 | 21.00 | 0.00786997 | 49.9421 | 21069.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 79916.636 | 63991.554 | 4.434793 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9533 | 1004.8586 | 1.1818 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.434793 | 5.24094400 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 79953.82 | 77728.44 | 1.0005 | 5.24094400 | 4.434793 | 25.97 | 17.02 | 0.00866795 | 48188.7 | 10.99 | 10.99 | 0.00850000 | 32470.5 | -999.0 | -999.00 | -999.00 | -999.00 | 9707.811 | 70246.01 | 31.30 | 0.00823349 | 18.45 | 1.19517000 | 26.9498 | 24.00 | 0.00882824 | 24.00 | 0.00882824 | 46.6185 | 59901.93 | 0.00 | 82404.78 | 64252.54 | 5.03396633 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.19 | 13.89 | 0.00977085 | 38952.6 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11456.464 | 11456.464 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.434793 | 5.24094400 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11456.46 | 11456.46 | 1.0000 | 1.57228320 | 1.330438 | 5.55 | 5.08 | 0.00534224 | 18991.3 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11456.46 | 3.80 | 0.00505843 | 3.80 | 1.19517000 | 89.8328 | 21.00 | 0.00784988 | 21.00 | 0.00784123 | 49.7622 | 25880.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 89188.895 | 71411.364 | 5.021829 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9323 | 1004.8586 | 1.1818 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.021829 | 5.93469003 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 89089.25 | 86736.15 | 0.9989 | 5.93469003 | 5.021829 | 25.74 | 16.93 | 0.00865668 | 47925.5 | 10.99 | 10.99 | 0.00850000 | 32470.4 | -999.0 | -999.00 | -999.00 | -999.00 | 10992.838 | 78096.42 | 31.30 | 0.00823349 | 18.45 | 1.19517000 | 23.7995 | 24.00 | 0.00878890 | 24.00 | 0.00878890 | 46.4136 | 67815.17 | 0.00 | 91965.72 | 71718.25 | 5.70031464 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.37 | 13.98 | 0.00979201 | 39188.9 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10612.199 | 10612.199 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.021829 | 5.93469003 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10612.20 | 10612.20 | 1.0000 | 1.78040701 | 1.506549 | 6.87 | 6.02 | 0.00556526 | 20891.0 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10612.20 | 3.80 | 0.00505843 | 3.80 | 1.19517000 | 79.3317 | 18.65 | 0.00751064 | 19.60 | 0.00751064 | 52.0046 | 33496.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.04 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.43 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.02 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 3843.83 | 381.67 | 7.67 |
CORE_MID | 2434.83 | 1827.83 | 0.00 |
CORE_TOP | 1902.00 | 2739.00 | 5.83 |
PERIMETER_TOP_ZN_3 | 1703.67 | 3673.83 | 238.17 |
PERIMETER_TOP_ZN_2 | 2166.67 | 3142.67 | 177.00 |
PERIMETER_TOP_ZN_1 | 2558.50 | 2631.17 | 174.50 |
PERIMETER_TOP_ZN_4 | 2209.50 | 3380.00 | 319.17 |
PERIMETER_BOT_ZN_3 | 1206.00 | 3842.67 | 34.67 |
PERIMETER_BOT_ZN_2 | 2132.50 | 2732.67 | 26.33 |
PERIMETER_BOT_ZN_1 | 2267.50 | 2683.17 | 90.67 |
PERIMETER_BOT_ZN_4 | 2277.50 | 2817.83 | 48.00 |
PERIMETER_MID_ZN_3 | 1720.33 | 3198.00 | 41.00 |
PERIMETER_MID_ZN_2 | 1740.33 | 2539.33 | 75.33 |
PERIMETER_MID_ZN_1 | 2792.17 | 2054.50 | 70.83 |
PERIMETER_MID_ZN_4 | 2332.50 | 2890.50 | 118.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4716.67 | 4440.33 | 515.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 8.83 | 0.00 | 8.83 |
PERIMETER_TOP_ZN_1 | 0.00 | 15.33 | 0.00 | 15.33 |
PERIMETER_TOP_ZN_4 | 0.00 | 21.50 | 0.00 | 17.67 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 2.83 | 0.00 | 2.83 |
PERIMETER_BOT_ZN_1 | 17.50 | 21.83 | 17.50 | 21.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 9.17 | 0.00 | 7.50 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 11.17 | 0.00 | 11.17 |
PERIMETER_MID_ZN_1 | 0.00 | 24.00 | 0.00 | 24.00 |
PERIMETER_MID_ZN_4 | 0.00 | 19.33 | 0.00 | 16.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 17.50 | 104.83 | 17.50 | 98.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.18 | 52.94 | 2698.04 | 1.534 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.18 | 52.94 | 2698.04 | 1.001 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.18 | 52.94 | 2698.04 | 0.986 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.68 | 11.16 | 568.77 | 0.982 | 0.058 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.96 | 7.07 | 360.08 | 1.520 | 0.061 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.68 | 11.16 | 568.77 | 1.583 | 0.058 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.96 | 7.06 | 360.05 | 1.704 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.68 | 11.16 | 568.77 | 0.877 | 0.031 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.96 | 7.07 | 360.08 | 1.308 | 0.032 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.68 | 11.16 | 568.77 | 1.250 | 0.829 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.96 | 7.06 | 360.05 | 1.400 | 0.032 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.68 | 11.16 | 568.77 | 0.963 | 0.048 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.60 | 7.07 | 360.08 | 1.381 | 0.052 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.68 | 11.16 | 568.77 | 1.553 | 0.048 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.96 | 7.06 | 360.05 | 1.628 | 0.051 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.18 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.18 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.18 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.96 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.96 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.96 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.96 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.60 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.96 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.18 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.18 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.18 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.96 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.96 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.96 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.96 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.60 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.96 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 112.00 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 24067420.38 | 0.00 | 24067420.38 | 0.00 | 24067420.38 | 13393058.27 | 4000.74 | 21.97 | 4737.29 | 21.31 |
CORE_MID | 15746361.35 | 0.00 | 15746361.35 | 0.00 | 15746361.35 | 13393058.27 | 4169.32 | 17.01 | 4573.67 | 28.42 |
CORE_TOP | 15524394.79 | 0.00 | 15524394.79 | 0.00 | 15524394.79 | 13393058.27 | 4195.78 | 12.85 | 4551.37 | 30.08 |
PERIMETER_TOP_ZN_3 | 3262555.07 | 0.00 | 3262555.07 | 331330.52 | 3593885.59 | 2823374.22 | 4120.03 | 17.82 | 4622.15 | 30.08 |
PERIMETER_TOP_ZN_2 | 3193029.98 | 0.00 | 3193029.98 | 220885.69 | 3413915.67 | 1787429.43 | 3903.61 | 1.86 | 4854.53 | 30.08 |
PERIMETER_TOP_ZN_1 | 5248830.95 | 0.00 | 5248830.95 | 331330.52 | 5580161.47 | 2823374.22 | 3924.93 | 2.97 | 4832.10 | 30.08 |
PERIMETER_TOP_ZN_4 | 3583289.97 | 0.00 | 3583289.97 | 220885.69 | 3804175.66 | 1787312.18 | 3905.07 | 4.81 | 4850.13 | 30.08 |
PERIMETER_BOT_ZN_3 | 2910675.53 | 0.00 | 2910675.53 | 176167.23 | 3086842.77 | 2823374.22 | 4147.98 | 19.37 | 4592.65 | 21.31 |
PERIMETER_BOT_ZN_2 | 2742835.00 | 0.00 | 2742835.00 | 117444.12 | 2860279.12 | 1787429.43 | 3949.68 | 6.10 | 4804.22 | 21.31 |
PERIMETER_BOT_ZN_1 | 4145729.93 | 0.00 | 4145729.93 | 2823248.61 | 6968978.55 | 2823374.22 | 3969.74 | 18.23 | 4772.04 | 21.31 |
PERIMETER_BOT_ZN_4 | 2936816.33 | 0.00 | 2936816.33 | 117444.12 | 3054260.44 | 1787312.18 | 3982.26 | 5.83 | 4771.90 | 21.31 |
PERIMETER_MID_ZN_3 | 3194628.71 | 0.00 | 3194628.71 | 275807.65 | 3470436.36 | 2823374.22 | 4069.32 | 22.03 | 4668.65 | 28.42 |
PERIMETER_MID_ZN_2 | 3150059.20 | 0.00 | 3150059.20 | 183870.66 | 3333929.86 | 1787429.43 | 3868.30 | 2.00 | 4889.70 | 937.42 |
PERIMETER_MID_ZN_1 | 5146424.62 | 0.00 | 5146424.62 | 275807.65 | 5422232.27 | 2823374.22 | 3901.62 | 72.67 | 4785.71 | 28.42 |
PERIMETER_MID_ZN_4 | 3418857.73 | 0.00 | 3418857.73 | 183870.66 | 3602728.39 | 1787312.18 | 3883.35 | 4.33 | 4872.31 | 28.42 |
Total Facility | 98271909.56 | 0.00 | 98271909.56 | 5258093.13 | 0.10E+09 | 67843644.98 | 4404.75 | 148.57 | 4993.40 | 949.22 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 1.1221 | 0.0000 | 1.1221 | 0.0000 | 1.1221 | 0.4247 | 1205.04 | 21.97 | 4715.99 |
CORE_MID | 0.7324 | 0.0000 | 0.7324 | 0.0000 | 0.7324 | 0.4247 | 1380.74 | 17.01 | 4545.25 |
CORE_TOP | 0.7217 | 0.0000 | 0.7217 | 0.0000 | 0.7217 | 0.4247 | 1408.86 | 12.85 | 4521.29 |
PERIMETER_TOP_ZN_3 | 0.1517 | 0.0000 | 0.1517 | 0.0089 | 0.1606 | 0.0895 | 1333.12 | 17.82 | 4592.06 |
PERIMETER_TOP_ZN_2 | 0.1485 | 0.0000 | 0.1485 | 0.0059 | 0.1545 | 0.0567 | 1116.69 | 1.86 | 4824.45 |
PERIMETER_TOP_ZN_1 | 0.2444 | 0.0000 | 0.2444 | 0.0089 | 0.2533 | 0.0895 | 1138.01 | 2.97 | 4802.01 |
PERIMETER_TOP_ZN_4 | 0.1666 | 0.0000 | 0.1666 | 0.0059 | 0.1725 | 0.0567 | 1118.15 | 4.81 | 4820.04 |
PERIMETER_BOT_ZN_3 | 0.1355 | 0.0000 | 0.1355 | 0.0047 | 0.1402 | 0.0895 | 1352.29 | 19.37 | 4571.34 |
PERIMETER_BOT_ZN_2 | 0.1278 | 0.0000 | 0.1278 | 0.0032 | 0.1309 | 0.0567 | 1153.99 | 6.10 | 4782.92 |
PERIMETER_BOT_ZN_1 | 0.1932 | 0.0000 | 0.1932 | 0.1285 | 0.3216 | 0.0895 | 1174.04 | 18.23 | 4750.73 |
PERIMETER_BOT_ZN_4 | 0.1368 | 0.0000 | 0.1368 | 0.0032 | 0.1399 | 0.0567 | 1186.57 | 5.83 | 4750.60 |
PERIMETER_MID_ZN_3 | 0.1486 | 0.0000 | 0.1486 | 0.0074 | 0.1560 | 0.0895 | 1280.73 | 22.03 | 4640.24 |
PERIMETER_MID_ZN_2 | 0.1350 | 0.0000 | 0.1350 | 0.0051 | 0.1401 | 0.0567 | 1073.39 | 1.00 | 3959.61 |
PERIMETER_MID_ZN_1 | 0.2398 | 0.0000 | 0.2398 | 0.0074 | 0.2472 | 0.0895 | 1113.04 | 72.67 | 4757.29 |
PERIMETER_MID_ZN_4 | 0.1590 | 0.0000 | 0.1590 | 0.0049 | 0.1640 | 0.0567 | 1094.77 | 4.33 | 4843.90 |
Total Facility | 4.5629 | 0.0000 | 4.5629 | 0.1942 | 4.7570 | 2.1513 | 1598.28 | 148.57 | 4953.18 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 51399769.98 | 0.00 | 51399769.98 | 22614548.33 | 3909.67 | 0.76 | 4849.57 | 21.31 |
PACU_VAV_MID | 42814671.29 | 0.00 | 42814671.29 | 22614548.33 | 3858.83 | 0.17 | 4901.00 | 28.42 |
PACU_VAV_TOP | 43032210.68 | 0.00 | 43032210.68 | 22614548.33 | 3889.17 | 2.42 | 4868.41 | 30.08 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 2.3956 | 0.0000 | 2.3956 | 0.7171 | 1113.97 | 0.76 | 4828.26 |
PACU_VAV_MID | 1.9920 | 0.0000 | 1.9920 | 0.7171 | 1070.25 | 0.17 | 4872.59 |
PACU_VAV_TOP | 2.0012 | 0.0000 | 2.0012 | 0.7171 | 1102.26 | 2.42 | 4838.32 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 4655.13 | 0.00 | 0.00 | 0.00 | 195.78 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 4644.54 | 0.00 | 0.00 | 0.00 | 258.75 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 4648.51 | 0.00 | 0.00 | 0.00 | 248.25 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 3.0233 | 0.0000 | 0.0000 | 0.0000 | 1.1775 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.5014 | 0.0000 | 0.0000 | 0.0000 | 1.1310 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.5159 | 0.0000 | 0.0000 | 0.0000 | 1.1060 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 829 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1472.21 | 13177.93 | 14-MAY-17:20 | 150012.36 | 16-OCT-11:00 |
Electricity:Building | 1069.87 | 12921.26 | 16-APR-17:10 | 80768.42 | 24-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 322.66 | 4214.70 | 01-JAN-00:10 | 25737.69 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1069.87 | 12921.26 | 16-APR-17:10 | 80768.42 | 24-OCT-07:10 |
InteriorLights:Electricity | 364.43 | 1672.11 | 01-JAN-09:10 | 38257.79 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 364.43 | 1672.11 | 01-JAN-09:10 | 38257.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 364.43 | 1672.11 | 01-JAN-09:10 | 38257.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 364.43 | 1672.11 | 01-JAN-09:10 | 38257.79 | 02-JAN-16:50 |
Electricity:Zone:CORE_MID | 201.92 | 2251.11 | 01-JAN-00:10 | 14360.82 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 201.92 | 2251.11 | 01-JAN-00:10 | 14360.82 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 35.19 | 428.29 | 16-APR-17:10 | 3027.38 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.85 | 42.19 | 01-JAN-09:10 | 1592.13 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.85 | 42.19 | 01-JAN-09:10 | 1592.13 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.20 | 273.73 | 16-APR-17:10 | 1916.52 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.80 | 26.71 | 01-JAN-07:20 | 1007.95 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.80 | 26.71 | 01-JAN-07:20 | 1007.95 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 34.92 | 428.29 | 16-APR-17:10 | 3027.37 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.58 | 42.19 | 01-JAN-07:30 | 1592.13 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.58 | 42.19 | 01-JAN-07:30 | 1592.13 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 22.18 | 271.13 | 12-MAR-17:10 | 1916.45 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.77 | 26.71 | 01-JAN-09:10 | 1007.89 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.77 | 26.71 | 01-JAN-09:10 | 1007.89 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 35.15 | 428.29 | 16-APR-17:10 | 3027.38 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.81 | 42.19 | 01-JAN-09:10 | 1592.13 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.81 | 42.19 | 01-JAN-09:10 | 1592.13 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.19 | 273.73 | 16-APR-17:10 | 1916.52 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.78 | 26.71 | 01-JAN-07:20 | 1007.95 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.78 | 26.71 | 01-JAN-07:20 | 1007.95 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 34.90 | 428.29 | 16-APR-17:10 | 3027.37 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.57 | 42.19 | 01-JAN-07:30 | 1592.13 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.57 | 42.19 | 01-JAN-07:30 | 1592.13 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 22.16 | 271.13 | 12-MAR-17:10 | 1916.45 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.76 | 26.71 | 01-JAN-09:10 | 1007.89 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.76 | 26.71 | 01-JAN-09:10 | 1007.89 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 35.19 | 428.29 | 16-APR-17:10 | 3027.38 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 10.85 | 42.19 | 01-JAN-09:10 | 1592.13 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 10.85 | 42.19 | 01-JAN-09:10 | 1592.13 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.20 | 273.73 | 16-APR-17:10 | 1916.52 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.80 | 26.71 | 01-JAN-07:20 | 1007.95 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.80 | 26.71 | 01-JAN-07:20 | 1007.95 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 34.92 | 428.29 | 16-APR-17:10 | 3027.37 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 10.58 | 42.19 | 01-JAN-07:30 | 1592.13 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 10.58 | 42.19 | 01-JAN-07:30 | 1592.13 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 22.18 | 271.13 | 12-MAR-17:10 | 1916.45 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.77 | 26.71 | 01-JAN-09:10 | 1007.89 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.77 | 26.71 | 01-JAN-09:10 | 1007.89 | 02-JAN-16:50 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 290.27 | 243.72 | 01-JAN-00:10 | 78328.90 | 16-OCT-11:00 |
ExteriorEquipment:Electricity | 17.11 | 243.72 | 01-JAN-00:10 | 1240.17 | 02-JAN-17:00 |
Transformer:ExteriorEquipment:Electricity | 17.11 | 243.72 | 01-JAN-00:10 | 1240.17 | 02-JAN-17:00 |
ElectricityPurchased:Facility | 1472.21 | 13177.93 | 14-MAY-17:20 | 150012.36 | 16-OCT-11:00 |
ElectricityPurchased:Plant | 1472.21 | 13177.93 | 14-MAY-17:20 | 150012.36 | 16-OCT-11:00 |
Cogeneration:ElectricityPurchased | 1472.21 | 13177.93 | 14-MAY-17:20 | 150012.36 | 16-OCT-11:00 |
General:Cogeneration:ElectricityPurchased | 1472.21 | 13177.93 | 14-MAY-17:20 | 150012.36 | 16-OCT-11:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1472.21 | 13177.93 | 14-MAY-17:20 | 150012.36 | 16-OCT-11:00 |
ElectricityNet:Plant | 1472.21 | 13177.93 | 14-MAY-17:20 | 150012.36 | 16-OCT-11:00 |
Cogeneration:ElectricityNet | 1472.21 | 13177.93 | 14-MAY-17:20 | 150012.36 | 16-OCT-11:00 |
General:Cogeneration:ElectricityNet | 1472.21 | 13177.93 | 14-MAY-17:20 | 150012.36 | 16-OCT-11:00 |
Heating:Electricity | 7.21 | 0.00 | 01-JAN-00:10 | 59513.74 | 02-JAN-07:10 |
General:Heating:Electricity | 7.21 | 0.00 | 01-JAN-00:10 | 59513.74 | 02-JAN-07:10 |
Fans:Electricity | 88.78 | 0.00 | 01-JAN-00:10 | 20307.78 | 29-SEP-16:00 |
General:Fans:Electricity | 88.78 | 0.00 | 01-JAN-00:10 | 20307.78 | 29-SEP-16:00 |
ExteriorLights:Electricity | 111.93 | 0.00 | 01-JAN-07:00 | 8596.48 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 111.93 | 0.00 | 01-JAN-07:00 | 8596.48 | 01-JAN-06:10 |
Cooling:Electricity | 177.17 | 0.00 | 01-JAN-00:10 | 64935.39 | 16-OCT-11:00 |
General:Cooling:Electricity | 177.17 | 0.00 | 01-JAN-00:10 | 64935.39 | 16-OCT-11:00 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-17:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-17:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-17:10 |
WIRED_LTG_ELECTRICITY | 10.24 | 0.00 | 01-JAN-00:10 | 1075.04 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 130.14 | 2003.43 | 02-JAN-06:20 | 28822.80 | 09-JAN-07:10 |
NaturalGas:HVAC | 1.27 | 0.00 | 01-JAN-00:10 | 21111.60 | 03-JAN-07:10 |
Heating:NaturalGas | 1.27 | 0.00 | 01-JAN-00:10 | 21111.60 | 03-JAN-07:10 |
General:Heating:NaturalGas | 1.27 | 0.00 | 01-JAN-00:10 | 21111.60 | 03-JAN-07:10 |
NaturalGas:Plant | 128.86 | 2003.43 | 02-JAN-06:20 | 9958.68 | 14-FEB-12:10 |
WaterSystems:NaturalGas | 128.86 | 2003.43 | 02-JAN-06:20 | 9958.68 | 14-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 128.86 | 2003.43 | 02-JAN-06:20 | 9958.68 | 14-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1916.22 | 0.00 | 01-JAN-00:10 | 376501.15 | 31-JUL-15:40 |
EnergyTransfer:Building | 1140.26 | 0.00 | 01-JAN-00:10 | 161424.77 | 16-OCT-14:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 265.94 | 0.00 | 01-JAN-00:10 | 26832.08 | 02-OCT-08:00 |
Heating:EnergyTransfer | 10.55 | 0.00 | 01-JAN-00:10 | 46228.39 | 03-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 10.55 | 0.00 | 01-JAN-00:10 | 46228.39 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1129.71 | 0.00 | 01-JAN-00:10 | 161424.77 | 16-OCT-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 265.94 | 0.00 | 01-JAN-00:10 | 26832.08 | 02-OCT-08:00 |
General:Cooling:EnergyTransfer | 1129.71 | 0.00 | 01-JAN-00:10 | 161424.77 | 16-OCT-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 265.94 | 0.00 | 01-JAN-00:10 | 26832.08 | 02-OCT-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 39.45 | 0.00 | 01-JAN-00:10 | 9670.96 | 29-SEP-14:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 4.99 | 0.00 | 01-JAN-00:10 | 5263.07 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 4.99 | 0.00 | 01-JAN-00:10 | 5263.07 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 34.46 | 0.00 | 01-JAN-00:10 | 9670.96 | 29-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 34.46 | 0.00 | 01-JAN-00:10 | 9670.96 | 29-SEP-14:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.32 | 0.00 | 01-JAN-00:10 | 4747.49 | 16-OCT-15:50 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.47 | 0.00 | 01-JAN-00:10 | 2334.82 | 02-JAN-11:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.47 | 0.00 | 01-JAN-00:10 | 2334.82 | 02-JAN-11:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.85 | 0.00 | 01-JAN-00:10 | 4747.49 | 16-OCT-15:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.85 | 0.00 | 01-JAN-00:10 | 4747.49 | 16-OCT-15:50 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.89 | 0.00 | 01-JAN-00:10 | 4910.11 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.44 | 0.00 | 01-JAN-00:10 | 2258.80 | 02-JAN-08:30 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.44 | 0.00 | 01-JAN-00:10 | 2258.80 | 02-JAN-08:30 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.44 | 0.00 | 01-JAN-00:10 | 4910.11 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.44 | 0.00 | 01-JAN-00:10 | 4910.11 | 16-OCT-16:00 |
EnergyTransfer:Zone:CORE_MID | 172.00 | 0.00 | 01-JAN-00:10 | 18414.61 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 1421.89 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 1421.89 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 172.00 | 0.00 | 01-JAN-00:10 | 18414.61 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 172.00 | 0.00 | 01-JAN-00:10 | 18414.61 | 16-OCT-16:00 |
EnergyTransfer:Zone:CORE_TOP | 164.05 | 0.00 | 01-JAN-00:10 | 20180.18 | 16-OCT-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.03 | 0.00 | 01-JAN-00:10 | 7907.45 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.03 | 0.00 | 01-JAN-00:10 | 7907.45 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 164.02 | 0.00 | 01-JAN-00:10 | 20180.18 | 16-OCT-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 164.02 | 0.00 | 01-JAN-00:10 | 20180.18 | 16-OCT-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.95 | 0.00 | 01-JAN-00:10 | 6032.55 | 16-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.44 | 0.00 | 01-JAN-00:10 | 4891.08 | 03-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.44 | 0.00 | 01-JAN-00:10 | 4891.08 | 03-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.51 | 0.00 | 01-JAN-00:10 | 6032.55 | 16-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.51 | 0.00 | 01-JAN-00:10 | 6032.55 | 16-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.17 | 0.00 | 01-JAN-00:10 | 6633.73 | 16-OCT-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.15 | 0.00 | 01-JAN-00:10 | 3395.05 | 03-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.15 | 0.00 | 01-JAN-00:10 | 3395.05 | 03-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.02 | 0.00 | 01-JAN-00:10 | 6633.73 | 16-OCT-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.02 | 0.00 | 01-JAN-00:10 | 6633.73 | 16-OCT-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 56.35 | 0.00 | 01-JAN-00:10 | 12519.41 | 16-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.20 | 0.00 | 01-JAN-00:10 | 4152.81 | 03-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.20 | 0.00 | 01-JAN-00:10 | 4152.81 | 03-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 56.15 | 0.00 | 01-JAN-00:10 | 12519.41 | 16-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 56.15 | 0.00 | 01-JAN-00:10 | 12519.41 | 16-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 36.17 | 0.00 | 01-JAN-00:10 | 7961.96 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.28 | 0.00 | 01-JAN-00:10 | 3196.85 | 03-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.28 | 0.00 | 01-JAN-00:10 | 3196.85 | 03-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 35.89 | 0.00 | 01-JAN-00:10 | 7961.96 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 35.89 | 0.00 | 01-JAN-00:10 | 7961.96 | 29-SEP-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 29.44 | 0.00 | 01-JAN-00:10 | 4688.28 | 16-OCT-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.04 | 0.00 | 01-JAN-00:10 | 2141.13 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.04 | 0.00 | 01-JAN-00:10 | 2141.13 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 29.40 | 0.00 | 01-JAN-00:10 | 4688.28 | 16-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 29.40 | 0.00 | 01-JAN-00:10 | 4688.28 | 16-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 29.37 | 0.00 | 01-JAN-00:10 | 5838.88 | 16-OCT-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1182.45 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1182.45 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 29.36 | 0.00 | 01-JAN-00:10 | 5838.88 | 16-OCT-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 29.36 | 0.00 | 01-JAN-00:10 | 5838.88 | 16-OCT-09:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 46.44 | 0.00 | 01-JAN-00:10 | 12692.20 | 16-OCT-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.37 | 0.00 | 01-JAN-00:10 | 7450.91 | 30-MAR-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.37 | 0.00 | 01-JAN-00:10 | 7450.91 | 30-MAR-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 44.07 | 0.00 | 01-JAN-00:10 | 12692.20 | 16-OCT-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 44.07 | 0.00 | 01-JAN-00:10 | 12692.20 | 16-OCT-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 31.07 | 0.00 | 01-JAN-00:10 | 6488.39 | 16-OCT-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1416.00 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1416.00 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 31.06 | 0.00 | 01-JAN-00:10 | 6488.39 | 16-OCT-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 31.06 | 0.00 | 01-JAN-00:10 | 6488.39 | 16-OCT-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 33.63 | 0.00 | 01-JAN-00:10 | 5546.39 | 16-OCT-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.04 | 0.00 | 01-JAN-00:10 | 2342.12 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.04 | 0.00 | 01-JAN-00:10 | 2342.12 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 33.59 | 0.00 | 01-JAN-00:10 | 5546.39 | 16-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 33.59 | 0.00 | 01-JAN-00:10 | 5546.39 | 16-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 33.61 | 0.00 | 01-JAN-00:10 | 6628.72 | 16-OCT-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1526.48 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1526.48 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 33.59 | 0.00 | 01-JAN-00:10 | 6628.72 | 16-OCT-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 33.59 | 0.00 | 01-JAN-00:10 | 6628.72 | 16-OCT-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 57.29 | 0.00 | 01-JAN-00:10 | 11560.40 | 16-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.02 | 0.00 | 01-JAN-00:10 | 2265.50 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.02 | 0.00 | 01-JAN-00:10 | 2265.50 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 57.28 | 0.00 | 01-JAN-00:10 | 11560.40 | 16-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 57.28 | 0.00 | 01-JAN-00:10 | 11560.40 | 16-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 36.12 | 0.00 | 01-JAN-00:10 | 7539.25 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.04 | 0.00 | 01-JAN-00:10 | 1646.78 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.04 | 0.00 | 01-JAN-00:10 | 1646.78 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 36.08 | 0.00 | 01-JAN-00:10 | 7539.25 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 36.08 | 0.00 | 01-JAN-00:10 | 7539.25 | 29-SEP-15:30 |
PlantLoopHeatingDemand:Facility | 44.91 | 0.00 | 01-JAN-00:10 | 5339.58 | 02-FEB-12:40 |
PlantLoopHeatingDemand:Plant | 44.91 | 0.00 | 01-JAN-00:10 | 5339.58 | 02-FEB-12:40 |
WaterSystems:PlantLoopHeatingDemand | 44.91 | 0.00 | 01-JAN-00:10 | 5339.58 | 02-FEB-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 44.91 | 0.00 | 01-JAN-00:10 | 5339.58 | 02-FEB-12:40 |
EnergyTransfer:HVAC | 731.04 | 0.00 | 01-JAN-00:10 | 242344.55 | 31-JUL-15:40 |
HeatingCoils:EnergyTransfer | 8.23 | 0.00 | 01-JAN-00:10 | 73931.57 | 03-JAN-07:10 |
CoolingCoils:EnergyTransfer | 722.81 | 0.00 | 01-JAN-00:10 | 242344.55 | 31-JUL-15:40 |
EnergyTransfer:Plant | 44.91 | 0.00 | 01-JAN-00:10 | 5339.58 | 02-FEB-12:40 |
WaterSystems:EnergyTransfer | 44.91 | 0.00 | 01-JAN-00:10 | 5339.58 | 02-FEB-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 44.91 | 0.00 | 01-JAN-00:10 | 5339.58 | 02-FEB-12:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -265.944 | 0.000 | 0.000 | 32.691 | 86.497 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -89.411 |
CORE_MID | 0.000 | 0.000 | 0.001 | -172.003 | 0.000 | 0.000 | 32.968 | 86.497 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -62.888 |
CORE_TOP | 0.000 | 0.000 | 0.033 | -164.020 | 0.000 | 0.000 | 33.436 | 86.497 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -71.371 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.436 | -32.510 | 0.000 | 0.000 | 7.230 | 10.853 | 24.333 | 12.790 | 0.000 | 0.030 | 6.752 | 0.000 | -27.117 | 0.000 | -2.797 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.150 | -33.021 | 0.000 | 0.000 | 4.497 | 6.798 | 15.404 | 28.918 | 0.000 | 0.017 | 0.000 | 0.000 | -17.565 | 0.000 | -1.939 | -3.257 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.200 | -56.146 | 0.000 | 0.000 | 7.075 | 10.585 | 24.332 | 56.967 | 0.000 | 0.023 | 0.004 | 0.000 | -27.510 | 0.000 | -3.040 | -12.486 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.284 | -35.888 | 0.000 | 0.000 | 4.604 | 6.773 | 15.403 | 33.039 | 0.000 | 0.020 | 0.001 | 0.000 | -18.303 | 0.000 | -1.955 | -3.978 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.040 | -29.399 | 0.000 | 0.000 | 7.197 | 10.814 | 24.333 | 13.161 | 0.000 | 0.017 | 3.495 | 0.000 | -28.094 | 0.000 | -1.563 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.005 | -29.360 | 0.000 | 0.000 | 4.448 | 6.783 | 15.404 | 29.032 | 0.000 | 0.009 | 0.000 | 0.000 | -18.680 | 0.000 | -1.115 | -6.527 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 2.373 | -44.071 | 0.000 | 0.000 | 7.112 | 10.571 | 24.332 | 57.599 | 0.000 | 0.354 | 0.001 | 0.000 | -29.179 | 0.000 | -18.451 | -10.642 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.013 | -31.060 | 0.000 | 0.000 | 4.506 | 6.757 | 15.403 | 33.322 | 0.000 | 0.010 | 0.001 | 0.000 | -19.635 | 0.000 | -1.130 | -8.186 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.045 | -33.588 | 0.000 | 0.000 | 7.112 | 10.853 | 24.333 | 12.436 | 0.000 | 0.024 | 10.319 | 0.000 | -29.026 | 0.000 | -2.507 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.017 | -33.591 | 0.000 | 0.000 | 3.300 | 6.798 | 15.404 | 28.657 | 0.000 | 0.014 | 0.001 | 0.000 | -18.624 | 0.000 | -1.722 | -0.252 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.016 | -57.278 | 0.000 | 0.000 | 6.990 | 10.585 | 24.332 | 56.668 | 0.000 | 0.019 | 0.001 | 0.000 | -29.259 | 0.000 | -2.700 | -9.374 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.035 | -36.082 | 0.000 | 0.000 | 4.522 | 6.773 | 15.403 | 32.871 | 0.000 | 0.016 | 0.000 | 0.000 | -19.548 | 0.000 | -1.747 | -2.244 |
TOPFLOOR_PLENUM | 4.991 | -34.456 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.026 | 34.027 | 0.000 | 0.000 | 0.000 | -4.588 | -0.001 |
MIDFLOOR_PLENUM | 1.471 | -16.854 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.032 | 19.848 | 0.000 | 0.000 | 0.000 | -4.498 | -0.000 |
FIRSTFLOOR_PLENUM | 0.440 | -24.445 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.023 | 27.643 | 0.000 | 0.000 | 0.000 | -3.662 | -0.000 |
Total Facility | 6.903 | -75.755 | 3.649 | -1053.962 | 0.000 | 0.000 | 167.688 | 364.433 | 705.434 | 395.459 | 0.000 | 0.636 | 102.093 | 0.000 | -282.538 | 0.000 | -53.412 | -280.619 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-OCT-05:12 | 0.00 | 0.00 | 0.00 | -44925.34 | 0.00 | 0.00 | 319.87 | 839.14 | 4989.51 | 0.00 | 0.00 | 0.00 | 38776.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-OCT-05:12 | 0.00 | 0.00 | 0.00 | -33211.21 | 0.00 | 0.00 | 332.71 | 839.14 | 3025.92 | 0.00 | 0.00 | 0.00 | 29013.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 16-OCT-14:00 | 0.00 | 0.00 | 0.00 | -20180.98 | 0.00 | 0.00 | 3591.74 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 2228.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-OCT-12:50 | 0.00 | 0.00 | 0.00 | -6033.12 | 0.00 | 0.00 | 737.22 | 759.45 | 1435.25 | 2801.81 | 0.00 | 117.00 | 182.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 15-OCT-08:43 | 0.00 | 0.00 | 0.00 | -11806.77 | 0.00 | 0.00 | 16.07 | 26.71 | 302.86 | 7578.85 | 0.00 | 138.16 | 3744.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 19-NOV-13:02 | 0.00 | 0.00 | 0.00 | -16249.95 | 0.00 | 0.00 | 23.78 | 42.19 | 478.41 | 11936.03 | 0.00 | 0.00 | 3817.47 | 0.00 | -0.00 | 0.00 | -47.94 | 0.00 |
PERIMETER_TOP_ZN_4 | 06-AUG-16:22 | 0.00 | 0.00 | 0.00 | -13724.35 | 0.00 | 0.00 | 15.33 | 26.71 | 302.86 | 7473.91 | 0.00 | 0.00 | 6006.43 | 0.00 | -0.00 | 0.00 | -100.88 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-OCT-12:30 | 0.00 | 0.00 | 0.00 | -4688.55 | 0.00 | 0.00 | 737.21 | 759.45 | 1435.25 | 2991.68 | 0.00 | 68.73 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1303.76 |
PERIMETER_BOT_ZN_2 | 15-OCT-08:32 | 0.00 | 0.00 | 0.00 | -9556.00 | 0.00 | 0.00 | 17.00 | 26.71 | 302.86 | 7886.21 | 0.00 | 64.59 | 1258.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 19-NOV-12:32 | 0.00 | 0.00 | 0.00 | -13149.35 | 0.00 | 0.00 | 25.34 | 42.19 | 478.41 | 12966.50 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -16.98 | -346.11 |
PERIMETER_BOT_ZN_4 | 23-JUL-16:22 | 0.00 | 0.00 | 0.00 | -11015.17 | 0.00 | 0.00 | 16.68 | 26.71 | 302.86 | 7511.42 | 0.00 | 0.00 | 3187.05 | 0.00 | -0.00 | 0.00 | -29.55 | 0.00 |
PERIMETER_MID_ZN_3 | 16-OCT-12:30 | 0.00 | 0.00 | 0.00 | -5546.72 | 0.00 | 0.00 | 737.21 | 759.45 | 1435.25 | 2970.17 | 0.00 | 107.35 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -462.71 |
PERIMETER_MID_ZN_2 | 15-OCT-08:23 | 0.00 | 0.00 | 0.00 | -11683.89 | 0.00 | 0.00 | 16.07 | 26.71 | 302.86 | 7959.25 | 0.00 | 80.06 | 3298.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 19-NOV-13:02 | 0.00 | 0.00 | 0.00 | -14851.63 | 0.00 | 0.00 | 23.93 | 42.19 | 478.41 | 11958.12 | 0.00 | 0.00 | 2389.54 | 0.00 | -0.00 | 0.00 | -40.56 | 0.00 |
PERIMETER_MID_ZN_4 | 23-JUL-16:22 | 0.00 | 0.00 | 0.00 | -12716.77 | 0.00 | 0.00 | 15.56 | 26.71 | 302.86 | 7394.38 | 0.00 | 0.00 | 5029.51 | 0.00 | -0.00 | 0.00 | -52.25 | 0.00 |
TOPFLOOR_PLENUM | 29-SEP-14:10 | 0.00 | -9671.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.36 | 9542.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 16-OCT-15:50 | 0.00 | -4747.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.74 | 4713.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 16-OCT-16:00 | 0.00 | -4910.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.66 | 4886.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-OCT-14:10 | 0.00 | -18000.03 | 0.00 | -143431.96 | 0.00 | 0.00 | 17646.68 | 30098.83 | 40588.47 | 59498.59 | 0.00 | 1510.68 | 12088.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-07:03 | 0.00 | 0.00 | 5687.67 | 0.00 | 0.00 | 0.00 | 886.15 | 2517.53 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12117.27 |
CORE_TOP | 02-JAN-07:03 | 0.00 | 0.00 | 21352.69 | 0.00 | 0.00 | 0.00 | 916.92 | 2517.53 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27813.06 |
PERIMETER_TOP_ZN_3 | 03-JAN-06:11 | 0.00 | 0.00 | 8755.96 | 0.00 | 0.00 | 0.00 | 105.86 | 176.90 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2307.58 | 0.00 | -47.41 | -7321.61 |
PERIMETER_TOP_ZN_2 | 03-JAN-06:11 | 0.00 | 0.00 | 6707.40 | 0.00 | 0.00 | 0.00 | 67.28 | 111.99 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1532.32 | 0.00 | -31.63 | -5726.54 |
PERIMETER_TOP_ZN_1 | 03-JAN-06:11 | 0.00 | 0.00 | 10296.05 | 0.00 | 0.00 | 0.00 | 104.40 | 176.90 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2338.51 | 0.00 | -49.09 | -8827.64 |
PERIMETER_TOP_ZN_4 | 03-JAN-06:11 | 0.00 | 0.00 | 6501.57 | 0.00 | 0.00 | 0.00 | 67.00 | 111.98 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1525.03 | 0.00 | -31.90 | -5527.44 |
PERIMETER_BOT_ZN_3 | 03-JAN-06:11 | 0.00 | 0.00 | 6522.55 | 0.00 | 0.00 | 0.00 | 98.76 | 176.90 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2576.73 | 0.00 | -28.30 | -4831.08 |
PERIMETER_BOT_ZN_2 | 30-MAR-06:03 | 0.00 | 0.00 | 4584.20 | 0.00 | 0.00 | 0.00 | 122.37 | 277.41 | 403.81 | 3069.66 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -53.58 | -8403.88 |
PERIMETER_BOT_ZN_1 | 30-MAR-06:10 | 0.00 | 0.00 | 7600.26 | 0.00 | 0.00 | 0.00 | 193.30 | 530.72 | 637.88 | 0.00 | 0.00 | 0.00 | 4169.15 | 0.00 | -2112.89 | 0.00 | -11018.42 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JAN-07:03 | 0.00 | 0.00 | 4464.85 | 0.00 | 0.00 | 0.00 | 122.22 | 335.97 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1688.90 | 0.00 | -39.65 | -3598.30 |
PERIMETER_MID_ZN_3 | 03-JAN-06:11 | 0.00 | 0.00 | 7243.00 | 0.00 | 0.00 | 0.00 | 99.98 | 176.90 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2547.98 | 0.00 | -43.58 | -5566.20 |
PERIMETER_MID_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 5227.09 | 0.00 | 0.00 | 0.00 | 63.00 | 111.99 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -973.41 | 0.00 | -42.41 | -4790.07 |
PERIMETER_MID_ZN_1 | 09-JAN-07:03 | 0.00 | 0.00 | 7501.91 | 0.00 | 0.00 | 0.00 | 193.01 | 438.20 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -811.60 | 0.00 | -93.58 | -7865.81 |
PERIMETER_MID_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 5049.70 | 0.00 | 0.00 | 0.00 | 63.22 | 111.98 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -983.11 | 0.00 | -41.93 | -4603.68 |
TOPFLOOR_PLENUM | 03-JAN-07:03 | 6407.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -19.26 | -6387.84 |
MIDFLOOR_PLENUM | 25-DEC-13:02 | 4473.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -21.36 | -4452.16 |
FIRSTFLOOR_PLENUM | 25-DEC-13:02 | 2937.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -33.30 | -2904.08 |
Total Facility | 02-JAN-07:03 | -3126.33 | 6528.54 | 101978.91 | -6528.54 | 0.00 | 0.00 | 4507.38 | 12420.39 | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10404.09 | 0.00 | -8540.75 | -117934.31 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.6205 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0415 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.1284 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.4348 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.3891 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0218 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.8103 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3638 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.5642 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3608 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.6946 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4223 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0888 | 3.0888 | 0.7846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3016 | 2.3016 | 0.7549 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3401 | 2.3401 | 0.7816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6711 | 0.6711 | 0.1651 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6996 | 0.6996 | 0.1399 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8944 | 0.8944 | 0.1789 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7840 | 0.7840 | 0.1568 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5434 | 0.5434 | 0.1652 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6022 | 0.6022 | 0.1204 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7431 | 0.7431 | 0.1650 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6430 | 0.6430 | 0.1286 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5953 | 0.5953 | 0.1595 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6913 | 0.6913 | 0.1383 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8148 | 0.8148 | 0.1630 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7254 | 0.7254 | 0.1451 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.6205 | 5.0415 | 5.6205 | 1.3638 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.1284 | 4.4348 | 5.1284 | 1.3608 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.3891 | 5.0218 | 5.3891 | 1.4223 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5444 | 1.5444 | 0.7846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1508 | 1.1508 | 0.7549 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1700 | 1.1700 | 0.7816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3356 | 0.3356 | 0.1651 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3498 | 0.3498 | 0.1399 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4472 | 0.4472 | 0.1789 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3920 | 0.3920 | 0.1568 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2717 | 0.2717 | 0.1652 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3011 | 0.3011 | 0.1204 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3716 | 0.3716 | 0.1650 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3215 | 0.3215 | 0.1286 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2977 | 0.2977 | 0.1595 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3456 | 0.3456 | 0.1383 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4074 | 0.4074 | 0.1630 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3627 | 0.3627 | 0.1451 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.8103 | 1.3638 | 1.3638 | 1.3638 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.5642 | 1.3608 | 1.3608 | 1.3608 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.6946 | 1.4223 | 1.4223 | 1.4223 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 17.50 |
Number of hours cooling loads not met | 98.17 |
Number of hours not met | 115.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 7.21 | 59513.74 | 1.27 | 21111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 177.17 | 64935.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 364.43 | 38257.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 111.93 | 8596.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 17.11 | 1240.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 88.78 | 20307.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 128.86 | 9958.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1472.21 |
Natural Gas | 0.00 | 130.14 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1602.35 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 73.15 |
Space Heating | 1.45 |
Space Cooling | 35.56 |
Fans (All) | 17.82 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 295.50 |
Subtotal | 295.50 |
Natural Gas [MJ/m2] | |
Space Heating | 0.26 |
Service Water Heating | 25.87 |
Miscellaneous (All) | 26.12 |
Subtotal | 26.12 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 22.74 |
Space Heating | 0.53 |
Space Cooling | 11.06 |
Fans (All) | 5.54 |
Service Water Heating | 8.04 |
Receptacle Equipment | 44.03 |
Miscellaneous | 8.06 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8716.50 | 43.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8729.67 | 30.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8707.17 | 52.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8707.83 | 52.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8720.67 | 39.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8708.33 | 51.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8710.00 | 50.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8721.83 | 38.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8701.33 | 58.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8689.83 | 70.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8689.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 70.17 | 0.00 | 0.00 | 0.00 |
Average | 8732.42 | 27.58 | 0.00 | 0.00 | 0.00 |
Sum | 157183.50 | 496.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7866.17 | 893.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8364.00 | 396.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8607.67 | 152.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8713.50 | 46.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8622.67 | 137.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8635.83 | 124.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8575.33 | 184.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8729.17 | 30.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8573.50 | 186.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8601.33 | 158.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8435.67 | 324.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8671.17 | 88.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8567.50 | 192.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8554.83 | 205.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8453.50 | 306.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8216.17 | 543.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8682.33 | 77.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8582.00 | 178.00 | 0.00 | 0.00 | 0.00 |
Min | 7866.17 | 30.83 | 0.00 | 0.00 | 0.00 |
Max | 8729.17 | 893.83 | 0.00 | 0.00 | 0.00 |
Average | 8525.13 | 234.87 | 0.00 | 0.00 | 0.00 |
Sum | 153452.33 | 4227.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127856.00 | 448.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128136.17 | 167.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128234.00 | 70.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24750.17 | 158.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24908.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24908.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128234.00 | 448.00 | 0.00 | 0.00 | 0.00 |
Average | 34096.31 | 47.03 | 0.00 | 0.00 | 0.00 |
Sum | 613733.50 | 846.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:42
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191920E+11 | 26054.70 | 20-JAN-07:02 | 13.33 | 12.02 | 0.198837E+10 | 2606.77 | 10-JAN-14:09 | 13.33 | 12.02 |
February | 0.175927E+11 | 21212.16 | 03-FEB-17:00 | 18.00 | 9.93 | 0.180439E+10 | 2606.92 | 01-FEB-14:09 | 18.00 | 9.93 |
March | 0.205527E+11 | 22934.11 | 24-MAR-06:03 | 12.17 | 12.17 | 0.215614E+10 | 2606.74 | 01-MAR-14:09 | 12.17 | 12.17 |
April | 0.208696E+11 | 29280.43 | 28-APR-06:03 | 14.17 | 12.31 | 0.191609E+10 | 2606.82 | 13-APR-09:00 | 14.17 | 12.31 |
May | 0.228113E+11 | 29781.93 | 05-MAY-06:03 | 16.17 | 14.82 | 0.207645E+10 | 2606.87 | 03-MAY-13:00 | 16.17 | 14.82 |
June | 0.242021E+11 | 31790.88 | 28-JUN-06:03 | 16.03 | 15.93 | 0.207059E+10 | 2606.65 | 22-JUN-09:39 | 16.03 | 15.93 |
July | 0.247586E+11 | 36144.92 | 20-JUL-06:03 | 17.00 | 17.00 | 0.192482E+10 | 2606.64 | 12-JUL-09:00 | 17.00 | 17.00 |
August | 0.270256E+11 | 39619.14 | 28-AUG-06:02 | 14.00 | 14.00 | 0.216025E+10 | 2606.66 | 15-AUG-13:50 | 14.00 | 14.00 |
September | 0.236063E+11 | 39304.85 | 26-SEP-06:02 | 15.00 | 14.41 | 0.191825E+10 | 2606.68 | 21-SEP-09:09 | 15.00 | 14.41 |
October | 0.245190E+11 | 44934.23 | 02-OCT-05:12 | 19.07 | 17.72 | 0.199418E+10 | 2606.79 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.210160E+11 | 35378.16 | 01-NOV-06:02 | 11.83 | 10.47 | 0.197322E+10 | 2606.99 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.197966E+11 | 23670.36 | 06-DEC-07:02 | 14.33 | 6.67 | 0.192020E+10 | 2607.06 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.265943E+12 | 0.239029E+11 | ||||||||
Minimum of Months | 0.175927E+11 | 21212.16 | 11.83 | 6.67 | 0.180439E+10 | 2606.64 | 12.17 | 9.93 | ||
Maximum of Months | 0.270256E+11 | 44934.23 | 19.07 | 17.72 | 0.216025E+10 | 2607.06 | 22.00 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133237E+10 | 5356.46 | 18-JAN-15:00 | 23.00 | 14.79 | 0.00 | 0.00 | 01-JAN-00:10 | 23.00 | 14.79 |
February | 0.118943E+10 | 4876.76 | 01-FEB-13:40 | 20.67 | 15.55 | 0.00 | 0.00 | 01-FEB-00:10 | 20.67 | 15.55 |
March | 0.169461E+10 | 6437.91 | 23-MAR-14:20 | 22.67 | 17.32 | 0.00 | 0.00 | 01-MAR-00:10 | 22.67 | 17.32 |
April | 0.305637E+10 | 8162.04 | 26-APR-13:50 | 26.17 | 16.81 | 0.00 | 0.00 | 01-APR-00:10 | 26.17 | 16.81 |
May | 0.301325E+10 | 7285.09 | 03-MAY-13:30 | 23.50 | 15.91 | 0.00 | 0.00 | 01-MAY-00:10 | 23.50 | 15.91 |
June | 0.402165E+10 | 7214.70 | 30-JUN-13:30 | 23.00 | 17.85 | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 | 17.85 |
July | 0.505259E+10 | 8597.06 | 31-JUL-13:30 | 27.50 | 21.02 | 0.00 | 0.00 | 01-JUL-00:10 | 27.50 | 21.02 |
August | 0.528411E+10 | 8299.83 | 14-AUG-13:10 | 25.83 | 20.42 | 0.00 | 0.00 | 01-AUG-00:10 | 25.83 | 20.42 |
September | 0.369401E+10 | 9670.96 | 29-SEP-14:10 | 33.83 | 17.79 | 0.00 | 0.00 | 01-SEP-00:10 | 33.83 | 17.79 |
October | 0.325212E+10 | 9619.17 | 16-OCT-13:10 | 33.75 | 16.65 | 0.00 | 0.00 | 01-OCT-00:10 | 33.75 | 16.65 |
November | 0.153229E+10 | 4785.40 | 10-NOV-14:10 | 19.83 | 15.69 | 0.00 | 0.00 | 01-NOV-00:10 | 19.83 | 15.69 |
December | 0.133335E+10 | 4809.58 | 19-DEC-14:10 | 22.83 | 9.79 | 0.00 | 0.00 | 01-DEC-00:10 | 22.83 | 9.79 |
Annual Sum or Average | 0.344561E+11 | 0.00 | ||||||||
Minimum of Months | 0.118943E+10 | 4785.40 | 19.83 | 9.79 | 0.00 | 0.00 | 19.83 | 9.79 | ||
Maximum of Months | 0.528411E+10 | 9670.96 | 33.83 | 21.02 | 0.00 | 0.00 | 33.83 | 21.02 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.594970E+09 | 1636.11 | 18-JAN-15:30 | 22.50 | 15.11 | 0.00 | 0.00 | 01-JAN-00:10 | 22.50 | 15.11 |
February | 0.586643E+09 | 1435.50 | 03-FEB-16:10 | 20.50 | 10.05 | 0.00 | 0.00 | 01-FEB-00:10 | 20.50 | 10.05 |
March | 0.665407E+09 | 1976.37 | 23-MAR-16:00 | 21.00 | 17.19 | 0.00 | 0.00 | 01-MAR-00:10 | 21.00 | 17.19 |
April | 0.121345E+10 | 2493.69 | 26-APR-16:00 | 22.00 | 16.41 | 0.00 | 0.00 | 01-APR-00:10 | 22.00 | 16.41 |
May | 0.130066E+10 | 2394.23 | 03-MAY-15:50 | 21.17 | 15.06 | 0.00 | 0.00 | 01-MAY-00:10 | 21.17 | 15.06 |
June | 0.191517E+10 | 2762.26 | 30-JUN-16:00 | 22.70 | 17.88 | 0.00 | 0.00 | 01-JUN-00:10 | 22.70 | 17.88 |
July | 0.247880E+10 | 3342.23 | 31-JUL-15:40 | 24.67 | 20.10 | 0.00 | 0.00 | 01-JUL-00:10 | 24.67 | 20.10 |
August | 0.272543E+10 | 3233.01 | 17-AUG-15:50 | 25.28 | 20.30 | 0.00 | 0.00 | 01-AUG-00:10 | 25.28 | 20.30 |
September | 0.199208E+10 | 4046.43 | 29-SEP-16:00 | 32.00 | 16.86 | 0.00 | 0.00 | 01-SEP-00:10 | 32.00 | 16.86 |
October | 0.195220E+10 | 4747.49 | 16-OCT-15:50 | 29.17 | 15.54 | 0.00 | 0.00 | 01-OCT-00:10 | 29.17 | 15.54 |
November | 0.788950E+09 | 1499.29 | 10-NOV-15:10 | 18.83 | 15.81 | 0.00 | 0.00 | 01-NOV-00:10 | 18.83 | 15.81 |
December | 0.639967E+09 | 1615.16 | 19-DEC-15:40 | 21.33 | 8.71 | 0.00 | 0.00 | 01-DEC-00:10 | 21.33 | 8.71 |
Annual Sum or Average | 0.168537E+11 | 0.00 | ||||||||
Minimum of Months | 0.586643E+09 | 1435.50 | 18.83 | 8.71 | 0.00 | 0.00 | 18.83 | 8.71 | ||
Maximum of Months | 0.272543E+10 | 4747.49 | 32.00 | 20.30 | 0.00 | 0.00 | 32.00 | 20.30 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116446E+10 | 2471.93 | 18-JAN-15:20 | 22.67 | 15.01 | 0.00 | 0.00 | 01-JAN-00:10 | 22.67 | 15.01 |
February | 0.107025E+10 | 2188.41 | 03-FEB-16:10 | 20.50 | 10.05 | 0.00 | 0.00 | 01-FEB-00:10 | 20.50 | 10.05 |
March | 0.115279E+10 | 2555.89 | 23-MAR-16:00 | 21.00 | 17.19 | 0.00 | 0.00 | 01-MAR-00:10 | 21.00 | 17.19 |
April | 0.178499E+10 | 2953.17 | 26-APR-15:50 | 22.17 | 16.38 | 0.00 | 0.00 | 01-APR-00:10 | 22.17 | 16.38 |
May | 0.194150E+10 | 2807.99 | 04-MAY-15:10 | 22.00 | 16.32 | 0.00 | 0.00 | 01-MAY-00:10 | 22.00 | 16.32 |
June | 0.251064E+10 | 3103.94 | 30-JUN-16:00 | 22.70 | 17.88 | 0.00 | 0.00 | 01-JUN-00:10 | 22.70 | 17.88 |
July | 0.307371E+10 | 3786.79 | 31-JUL-15:10 | 25.67 | 20.38 | 0.00 | 0.00 | 01-JUL-00:10 | 25.67 | 20.38 |
August | 0.342057E+10 | 3692.63 | 17-AUG-15:50 | 25.28 | 20.30 | 0.00 | 0.00 | 01-AUG-00:10 | 25.28 | 20.30 |
September | 0.268903E+10 | 4362.51 | 29-SEP-16:00 | 32.00 | 16.86 | 0.00 | 0.00 | 01-SEP-00:10 | 32.00 | 16.86 |
October | 0.275955E+10 | 4910.11 | 16-OCT-16:00 | 29.00 | 15.43 | 0.00 | 0.00 | 01-OCT-00:10 | 29.00 | 15.43 |
November | 0.158109E+10 | 2270.91 | 13-NOV-15:20 | 17.67 | 13.92 | 0.00 | 0.00 | 01-NOV-00:10 | 17.67 | 13.92 |
December | 0.129636E+10 | 2440.93 | 19-DEC-15:50 | 21.17 | 8.50 | 0.00 | 0.00 | 01-DEC-00:10 | 21.17 | 8.50 |
Annual Sum or Average | 0.244450E+11 | 0.00 | ||||||||
Minimum of Months | 0.107025E+10 | 2188.41 | 17.67 | 8.50 | 0.00 | 0.00 | 17.67 | 8.50 | ||
Maximum of Months | 0.342057E+10 | 4910.11 | 32.00 | 20.38 | 0.00 | 0.00 | 32.00 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116234E+11 | 14185.68 | 20-JAN-16:20 | 16.67 | 14.61 | 0.193484E+10 | 2606.73 | 10-JAN-14:09 | 16.67 | 14.61 |
February | 0.108311E+11 | 13883.48 | 03-FEB-17:00 | 18.00 | 9.93 | 0.176429E+10 | 2606.88 | 01-FEB-14:09 | 18.00 | 9.93 |
March | 0.125081E+11 | 14528.95 | 24-MAR-16:00 | 18.00 | 14.96 | 0.211257E+10 | 2606.69 | 01-MAR-14:09 | 18.00 | 14.96 |
April | 0.137101E+11 | 15541.32 | 27-APR-16:00 | 18.00 | 14.37 | 0.189581E+10 | 2606.75 | 13-APR-09:00 | 18.00 | 14.37 |
May | 0.148804E+11 | 15603.03 | 04-MAY-16:00 | 22.00 | 15.83 | 0.205910E+10 | 2606.81 | 03-MAY-13:00 | 22.00 | 15.83 |
June | 0.162171E+11 | 16020.29 | 30-JUN-16:00 | 22.70 | 17.88 | 0.206078E+10 | 2606.64 | 22-JUN-09:50 | 22.70 | 17.88 |
July | 0.171288E+11 | 16710.37 | 31-JUL-16:00 | 24.00 | 19.89 | 0.191803E+10 | 2606.63 | 13-JUL-09:09 | 24.00 | 19.89 |
August | 0.184272E+11 | 16518.37 | 18-AUG-16:00 | 24.00 | 19.89 | 0.215388E+10 | 2606.62 | 21-AUG-09:50 | 21.50 | 17.17 |
September | 0.156464E+11 | 16907.39 | 29-SEP-16:00 | 32.00 | 16.86 | 0.190851E+10 | 2606.65 | 21-SEP-09:09 | 32.00 | 16.86 |
October | 0.161720E+11 | 33216.51 | 02-OCT-05:12 | 19.07 | 17.72 | 0.198277E+10 | 2606.73 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.128005E+11 | 14532.18 | 01-NOV-16:00 | 16.80 | 12.58 | 0.194943E+10 | 2606.85 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.120576E+11 | 14163.91 | 07-DEC-16:30 | 17.00 | 14.57 | 0.188565E+10 | 2606.96 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.172003E+12 | 0.236257E+11 | ||||||||
Minimum of Months | 0.108311E+11 | 13883.48 | 16.67 | 9.93 | 0.176429E+10 | 2606.62 | 16.67 | 9.93 | ||
Maximum of Months | 0.184272E+11 | 33216.51 | 32.00 | 19.89 | 0.215388E+10 | 2606.96 | 32.00 | 19.89 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104057E+11 | 13697.79 | 19-JAN-16:00 | 19.00 | 14.77 | 0.185544E+10 | 2606.67 | 27-JAN-14:09 | 16.83 | 12.84 |
February | 0.984254E+10 | 13556.49 | 02-FEB-16:20 | 17.67 | 13.13 | 0.169989E+10 | 2606.88 | 01-FEB-14:09 | 17.67 | 13.13 |
March | 0.116123E+11 | 15095.01 | 24-MAR-15:40 | 18.00 | 15.12 | 0.203197E+10 | 2606.65 | 01-MAR-14:20 | 18.00 | 15.12 |
April | 0.132750E+11 | 16747.02 | 27-APR-15:20 | 18.80 | 14.83 | 0.186771E+10 | 2606.72 | 13-APR-09:00 | 18.80 | 14.83 |
May | 0.143987E+11 | 16908.62 | 03-MAY-15:20 | 21.67 | 15.26 | 0.203511E+10 | 2606.82 | 03-MAY-13:00 | 21.67 | 15.26 |
June | 0.162475E+11 | 17557.44 | 30-JUN-15:30 | 22.85 | 17.86 | 0.204840E+10 | 2606.64 | 27-JUN-09:09 | 22.85 | 17.86 |
July | 0.174520E+11 | 18374.78 | 31-JUL-15:20 | 25.33 | 20.29 | 0.190993E+10 | 2606.63 | 17-JUL-09:00 | 25.33 | 20.29 |
August | 0.185458E+11 | 18118.15 | 17-AUG-15:30 | 25.85 | 20.49 | 0.214478E+10 | 2606.63 | 14-AUG-13:20 | 25.85 | 20.49 |
September | 0.151233E+11 | 18421.31 | 29-SEP-14:50 | 33.17 | 17.55 | 0.189374E+10 | 2606.67 | 13-SEP-09:09 | 33.17 | 17.55 |
October | 0.151536E+11 | 20180.18 | 16-OCT-14:00 | 32.00 | 15.83 | 0.196096E+10 | 2606.70 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.113033E+11 | 13837.48 | 01-NOV-16:00 | 16.80 | 12.58 | 0.189740E+10 | 2606.84 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.106600E+11 | 13700.20 | 07-DEC-16:00 | 18.00 | 14.97 | 0.181286E+10 | 2606.94 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.164020E+12 | 0.231582E+11 | ||||||||
Minimum of Months | 0.984254E+10 | 13556.49 | 16.80 | 12.58 | 0.169989E+10 | 2606.63 | 16.83 | 12.37 | ||
Maximum of Months | 0.185458E+11 | 20180.18 | 33.17 | 20.49 | 0.214478E+10 | 2606.94 | 33.17 | 20.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168879E+10 | 2767.30 | 18-JAN-15:00 | 23.00 | 14.79 | 0.362508E+09 | 549.49 | 18-JAN-14:00 | 23.00 | 14.79 |
February | 0.162596E+10 | 2397.66 | 03-FEB-15:00 | 23.00 | 8.84 | 0.334784E+09 | 549.54 | 01-FEB-14:09 | 23.00 | 8.84 |
March | 0.199375E+10 | 3053.84 | 23-MAR-15:20 | 21.67 | 17.34 | 0.399589E+09 | 549.49 | 10-MAR-14:00 | 21.67 | 17.34 |
April | 0.253020E+10 | 4238.69 | 26-APR-14:00 | 26.00 | 16.74 | 0.380738E+09 | 549.51 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.293258E+10 | 4537.48 | 04-MAY-13:50 | 23.00 | 16.67 | 0.419346E+09 | 549.54 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.364107E+10 | 4358.20 | 27-JUN-16:00 | 22.00 | 18.09 | 0.427896E+09 | 549.49 | 27-JUN-09:09 | 22.00 | 18.09 |
July | 0.410093E+10 | 5016.56 | 31-JUL-14:00 | 27.00 | 20.84 | 0.400809E+09 | 549.49 | 13-JUL-09:39 | 27.00 | 20.84 |
August | 0.412477E+10 | 4894.03 | 18-AUG-15:00 | 27.00 | 20.85 | 0.448514E+09 | 549.50 | 14-AUG-13:20 | 27.00 | 20.85 |
September | 0.313467E+10 | 5891.54 | 29-SEP-13:50 | 34.33 | 17.92 | 0.392017E+09 | 549.49 | 05-SEP-13:09 | 34.33 | 17.92 |
October | 0.308189E+10 | 6032.55 | 16-OCT-12:50 | 34.42 | 16.94 | 0.403298E+09 | 549.50 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.190424E+10 | 2488.12 | 10-NOV-14:10 | 19.83 | 15.69 | 0.377312E+09 | 549.52 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.175093E+10 | 2762.74 | 05-DEC-15:00 | 25.00 | 13.22 | 0.353273E+09 | 549.48 | 07-DEC-14:00 | 19.00 | 15.27 |
Annual Sum or Average | 0.325098E+11 | 0.470009E+10 | ||||||||
Minimum of Months | 0.162596E+10 | 2397.66 | 19.83 | 8.84 | 0.334784E+09 | 549.48 | 19.00 | 8.84 | ||
Maximum of Months | 0.412477E+10 | 6032.55 | 34.42 | 20.85 | 0.448514E+09 | 549.54 | 34.33 | 20.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165973E+10 | 3172.63 | 20-JAN-10:00 | 19.00 | 14.77 | 0.243759E+09 | 347.88 | 19-JAN-10:00 | 19.00 | 14.77 |
February | 0.157467E+10 | 2940.82 | 02-FEB-10:10 | 17.17 | 12.19 | 0.221570E+09 | 347.90 | 01-FEB-14:09 | 17.17 | 12.19 |
March | 0.201069E+10 | 4817.25 | 23-MAR-09:40 | 21.00 | 15.89 | 0.264907E+09 | 347.88 | 23-MAR-09:00 | 22.00 | 16.42 |
April | 0.289124E+10 | 5891.58 | 26-APR-09:20 | 23.33 | 16.79 | 0.248707E+09 | 347.91 | 13-APR-09:00 | 23.33 | 16.79 |
May | 0.295211E+10 | 5155.70 | 04-MAY-09:30 | 21.00 | 15.49 | 0.269071E+09 | 347.91 | 03-MAY-13:00 | 21.00 | 15.49 |
June | 0.354545E+10 | 9065.53 | 18-JUN-08:32 | 21.00 | 16.35 | 0.271376E+09 | 347.88 | 22-JUN-09:00 | 23.00 | 17.27 |
July | 0.425692E+10 | 11347.66 | 04-JUL-09:02 | 22.00 | 15.93 | 0.254776E+09 | 347.88 | 17-JUL-09:50 | 22.67 | 17.64 |
August | 0.448986E+10 | 7542.06 | 20-AUG-09:13 | 22.00 | 18.63 | 0.285604E+09 | 347.88 | 31-AUG-09:09 | 23.00 | 18.43 |
September | 0.316874E+10 | 7458.62 | 10-SEP-09:23 | 22.50 | 17.63 | 0.249799E+09 | 347.89 | 13-SEP-09:09 | 22.17 | 18.15 |
October | 0.295495E+10 | 11807.23 | 15-OCT-08:43 | 32.33 | 15.60 | 0.259732E+09 | 347.90 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.181386E+10 | 2659.16 | 01-NOV-09:30 | 15.00 | 12.66 | 0.249724E+09 | 347.90 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.170286E+10 | 3139.73 | 05-DEC-09:50 | 25.67 | 12.88 | 0.236941E+09 | 347.91 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.330211E+11 | 0.305597E+10 | ||||||||
Minimum of Months | 0.157467E+10 | 2659.16 | 15.00 | 12.19 | 0.221570E+09 | 347.88 | 17.17 | 11.71 | ||
Maximum of Months | 0.448986E+10 | 11807.23 | 32.33 | 18.63 | 0.285604E+09 | 347.91 | 23.33 | 18.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.495068E+10 | 15326.52 | 22-JAN-13:13 | 17.33 | 12.40 | 0.401704E+09 | 549.82 | 18-JAN-14:00 | 17.33 | 12.40 |
February | 0.367350E+10 | 10608.25 | 20-FEB-13:43 | 17.00 | 10.89 | 0.357502E+09 | 549.72 | 03-FEB-14:20 | 17.00 | 10.89 |
March | 0.371978E+10 | 8886.88 | 23-MAR-13:30 | 22.50 | 17.06 | 0.419304E+09 | 549.53 | 01-MAR-14:09 | 22.50 | 17.06 |
April | 0.405932E+10 | 7827.07 | 26-APR-13:10 | 26.83 | 17.07 | 0.385912E+09 | 549.52 | 13-APR-13:50 | 26.83 | 17.07 |
May | 0.344964E+10 | 5951.46 | 04-MAY-12:40 | 23.33 | 16.64 | 0.417868E+09 | 549.55 | 03-MAY-13:00 | 23.33 | 16.64 |
June | 0.387459E+10 | 5388.38 | 30-JUN-13:10 | 23.00 | 17.85 | 0.425308E+09 | 549.49 | 27-JUN-09:09 | 23.00 | 17.85 |
July | 0.459132E+10 | 7404.26 | 31-JUL-13:00 | 28.00 | 21.19 | 0.399526E+09 | 549.49 | 07-JUL-13:09 | 28.00 | 21.19 |
August | 0.570813E+10 | 8429.49 | 30-AUG-13:00 | 24.00 | 18.12 | 0.448817E+09 | 549.50 | 14-AUG-13:20 | 24.00 | 18.12 |
September | 0.556155E+10 | 12216.18 | 29-SEP-13:20 | 35.33 | 18.10 | 0.395475E+09 | 558.04 | 29-SEP-13:20 | 35.33 | 18.10 |
October | 0.626291E+10 | 15888.34 | 29-OCT-12:32 | 22.33 | 15.66 | 0.411963E+09 | 572.34 | 16-OCT-13:09 | 22.33 | 15.66 |
November | 0.508235E+10 | 16250.14 | 19-NOV-13:02 | 26.67 | 15.00 | 0.402711E+09 | 549.89 | 30-NOV-14:50 | 21.33 | 12.71 |
December | 0.521150E+10 | 12128.53 | 17-DEC-12:53 | 24.00 | 11.21 | 0.389776E+09 | 549.78 | 07-DEC-14:00 | 24.00 | 11.21 |
Annual Sum or Average | 0.561453E+11 | 0.485586E+10 | ||||||||
Minimum of Months | 0.344964E+10 | 5388.38 | 17.00 | 10.89 | 0.357502E+09 | 549.49 | 17.00 | 10.89 | ||
Maximum of Months | 0.626291E+10 | 16250.14 | 35.33 | 21.19 | 0.448817E+09 | 572.34 | 35.33 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183554E+10 | 4698.77 | 18-JAN-15:00 | 23.00 | 14.79 | 0.231238E+09 | 347.85 | 18-JAN-14:00 | 23.00 | 14.79 |
February | 0.180611E+10 | 4951.15 | 22-FEB-15:50 | 16.30 | 12.09 | 0.210490E+09 | 347.89 | 01-FEB-14:09 | 16.30 | 12.09 |
March | 0.228703E+10 | 6576.13 | 23-MAR-15:50 | 21.17 | 17.23 | 0.250388E+09 | 347.86 | 10-MAR-14:00 | 21.17 | 17.23 |
April | 0.310639E+10 | 11335.52 | 30-APR-16:33 | 22.00 | 15.83 | 0.237446E+09 | 347.87 | 13-APR-13:00 | 22.00 | 15.83 |
May | 0.322613E+10 | 7200.53 | 21-MAY-16:53 | 18.00 | 13.88 | 0.260485E+09 | 347.89 | 03-MAY-13:00 | 18.00 | 13.88 |
June | 0.390795E+10 | 12087.93 | 25-JUN-15:53 | 21.00 | 16.52 | 0.266984E+09 | 347.85 | 26-JUN-09:30 | 23.00 | 17.49 |
July | 0.439656E+10 | 11686.00 | 23-JUL-15:13 | 24.00 | 19.32 | 0.251865E+09 | 347.85 | 17-JUL-09:00 | 24.00 | 19.32 |
August | 0.456111E+10 | 13728.46 | 06-AUG-16:22 | 23.50 | 19.44 | 0.281848E+09 | 347.85 | 14-AUG-13:20 | 25.67 | 20.38 |
September | 0.351611E+10 | 11797.47 | 04-SEP-16:03 | 19.67 | 15.96 | 0.245488E+09 | 347.85 | 05-SEP-13:09 | 21.83 | 18.03 |
October | 0.315060E+10 | 13107.74 | 15-OCT-15:22 | 30.50 | 15.19 | 0.252056E+09 | 347.86 | 25-OCT-13:00 | 24.00 | 11.58 |
November | 0.217781E+10 | 4777.92 | 10-NOV-14:50 | 19.17 | 15.85 | 0.236484E+09 | 347.90 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.191691E+10 | 4694.44 | 19-DEC-15:30 | 21.50 | 8.94 | 0.223877E+09 | 347.91 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.358883E+11 | 0.294865E+10 | ||||||||
Minimum of Months | 0.180611E+10 | 4694.44 | 16.30 | 8.94 | 0.210490E+09 | 347.85 | 16.30 | 11.58 | ||
Maximum of Months | 0.456111E+10 | 13728.46 | 30.50 | 19.44 | 0.281848E+09 | 347.91 | 25.67 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184739E+10 | 2160.04 | 18-JAN-13:30 | 25.30 | 14.77 | 0.368652E+09 | 549.49 | 18-JAN-14:00 | 23.00 | 14.79 |
February | 0.170440E+10 | 1767.34 | 01-FEB-12:10 | 25.67 | 14.54 | 0.334596E+09 | 544.52 | 03-FEB-14:00 | 23.00 | 8.84 |
March | 0.198382E+10 | 1864.71 | 23-MAR-15:20 | 21.67 | 17.34 | 0.399217E+09 | 549.48 | 23-MAR-13:50 | 21.67 | 17.34 |
April | 0.213656E+10 | 2757.38 | 26-APR-14:00 | 26.00 | 16.74 | 0.379907E+09 | 549.50 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.246059E+10 | 3204.37 | 04-MAY-14:10 | 22.83 | 16.63 | 0.421466E+09 | 549.53 | 03-MAY-13:00 | 22.83 | 16.63 |
June | 0.289268E+10 | 3154.70 | 29-JUN-16:00 | 23.00 | 18.43 | 0.428733E+09 | 549.49 | 23-JUN-09:09 | 23.00 | 18.43 |
July | 0.334166E+10 | 3771.95 | 19-JUL-15:00 | 27.00 | 20.17 | 0.401641E+09 | 549.49 | 11-JUL-09:09 | 27.00 | 20.17 |
August | 0.339296E+10 | 3736.99 | 18-AUG-15:00 | 27.00 | 20.85 | 0.449777E+09 | 549.49 | 15-AUG-13:50 | 27.00 | 20.85 |
September | 0.276082E+10 | 4446.77 | 29-SEP-13:10 | 35.67 | 18.16 | 0.395617E+09 | 549.49 | 13-SEP-09:09 | 35.67 | 18.16 |
October | 0.291265E+10 | 4688.28 | 16-OCT-12:30 | 35.05 | 17.21 | 0.409207E+09 | 549.50 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.202101E+10 | 2134.81 | 19-NOV-12:32 | 26.67 | 15.14 | 0.385501E+09 | 549.48 | 01-NOV-13:00 | 26.67 | 15.14 |
December | 0.194482E+10 | 2126.84 | 19-DEC-13:30 | 24.50 | 10.72 | 0.359537E+09 | 547.50 | 05-DEC-14:00 | 24.50 | 10.72 |
Annual Sum or Average | 0.293994E+11 | 0.473385E+10 | ||||||||
Minimum of Months | 0.170440E+10 | 1767.34 | 21.67 | 10.72 | 0.334596E+09 | 544.52 | 21.67 | 8.84 | ||
Maximum of Months | 0.339296E+10 | 4688.28 | 35.67 | 20.85 | 0.449777E+09 | 549.53 | 35.67 | 20.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165152E+10 | 2911.86 | 20-JAN-09:50 | 18.67 | 14.64 | 0.252129E+09 | 347.88 | 05-JAN-10:00 | 18.67 | 14.64 |
February | 0.148420E+10 | 2552.44 | 01-FEB-10:10 | 23.83 | 12.71 | 0.226091E+09 | 347.90 | 01-FEB-14:09 | 19.00 | 15.70 |
March | 0.180176E+10 | 3839.02 | 23-MAR-09:30 | 20.50 | 15.62 | 0.270140E+09 | 347.88 | 23-MAR-09:00 | 22.00 | 16.42 |
April | 0.240680E+10 | 4679.26 | 26-APR-09:20 | 23.33 | 16.79 | 0.251081E+09 | 347.91 | 13-APR-09:00 | 23.33 | 16.79 |
May | 0.248274E+10 | 4207.40 | 04-MAY-09:30 | 21.00 | 15.49 | 0.271934E+09 | 347.90 | 03-MAY-13:00 | 21.00 | 15.49 |
June | 0.288993E+10 | 4689.57 | 30-JUN-09:20 | 22.67 | 18.13 | 0.272842E+09 | 347.88 | 22-JUN-09:39 | 22.67 | 18.13 |
July | 0.364442E+10 | 8211.26 | 04-JUL-09:02 | 22.00 | 15.93 | 0.255789E+09 | 347.88 | 17-JUL-09:30 | 22.00 | 17.20 |
August | 0.390731E+10 | 5466.15 | 14-AUG-09:10 | 25.32 | 20.33 | 0.286942E+09 | 347.88 | 15-AUG-13:50 | 24.33 | 19.44 |
September | 0.281426E+10 | 5349.24 | 10-SEP-09:13 | 22.33 | 17.55 | 0.252718E+09 | 347.88 | 12-SEP-09:30 | 22.00 | 16.63 |
October | 0.278750E+10 | 9556.25 | 15-OCT-08:32 | 31.67 | 15.30 | 0.263167E+09 | 347.90 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.180125E+10 | 2677.66 | 01-NOV-09:30 | 15.00 | 12.66 | 0.256892E+09 | 347.90 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.168811E+10 | 2857.35 | 05-DEC-09:50 | 25.67 | 12.88 | 0.245371E+09 | 347.91 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.293598E+11 | 0.310510E+10 | ||||||||
Minimum of Months | 0.148420E+10 | 2552.44 | 15.00 | 12.66 | 0.226091E+09 | 347.88 | 18.67 | 11.71 | ||
Maximum of Months | 0.390731E+10 | 9556.25 | 31.67 | 20.33 | 0.286942E+09 | 347.91 | 24.33 | 19.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408782E+10 | 12778.95 | 22-JAN-13:23 | 17.50 | 12.39 | 0.402910E+09 | 549.80 | 18-JAN-14:00 | 17.50 | 12.39 |
February | 0.277125E+10 | 8119.51 | 01-FEB-12:10 | 25.67 | 14.54 | 0.353563E+09 | 549.54 | 01-FEB-14:09 | 19.00 | 15.70 |
March | 0.252599E+10 | 6719.80 | 23-MAR-14:00 | 23.00 | 17.27 | 0.409200E+09 | 549.52 | 01-MAR-14:09 | 23.00 | 17.27 |
April | 0.271971E+10 | 6592.67 | 26-APR-12:00 | 26.00 | 17.28 | 0.381291E+09 | 549.53 | 13-APR-09:00 | 26.00 | 17.28 |
May | 0.232822E+10 | 4204.98 | 04-MAY-12:30 | 23.50 | 16.62 | 0.407213E+09 | 549.54 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.259430E+10 | 3657.32 | 30-JUN-12:30 | 23.50 | 17.99 | 0.415207E+09 | 549.49 | 12-JUN-13:09 | 23.50 | 17.99 |
July | 0.343545E+10 | 8347.39 | 31-JUL-12:00 | 28.00 | 21.19 | 0.395867E+09 | 549.49 | 07-JUL-13:09 | 28.00 | 21.19 |
August | 0.447070E+10 | 8386.24 | 18-AUG-12:00 | 28.00 | 21.20 | 0.446709E+09 | 549.49 | 29-AUG-13:00 | 24.00 | 17.64 |
September | 0.455358E+10 | 12315.26 | 29-SEP-12:00 | 36.00 | 18.21 | 0.395970E+09 | 672.21 | 29-SEP-12:09 | 36.00 | 18.21 |
October | 0.572716E+10 | 13062.28 | 01-OCT-12:52 | 25.00 | 20.20 | 0.415584E+09 | 696.98 | 16-OCT-12:09 | 35.68 | 17.48 |
November | 0.427260E+10 | 13149.45 | 19-NOV-12:32 | 26.67 | 15.14 | 0.403855E+09 | 549.88 | 29-NOV-14:39 | 19.33 | 10.61 |
December | 0.458288E+10 | 12765.74 | 25-DEC-13:02 | 22.00 | 9.19 | 0.391153E+09 | 551.04 | 19-DEC-13:09 | 22.00 | 9.19 |
Annual Sum or Average | 0.440697E+11 | 0.481852E+10 | ||||||||
Minimum of Months | 0.232822E+10 | 3657.32 | 17.50 | 9.19 | 0.353563E+09 | 549.49 | 17.50 | 9.19 | ||
Maximum of Months | 0.572716E+10 | 13149.45 | 36.00 | 21.20 | 0.446709E+09 | 696.98 | 36.00 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173193E+10 | 3586.58 | 18-JAN-15:30 | 22.50 | 15.11 | 0.241424E+09 | 347.85 | 27-JAN-14:09 | 16.83 | 12.84 |
February | 0.162279E+10 | 3915.18 | 22-FEB-16:30 | 15.00 | 12.17 | 0.218614E+09 | 347.88 | 01-FEB-14:09 | 15.00 | 12.17 |
March | 0.194802E+10 | 4831.78 | 23-MAR-16:00 | 21.00 | 17.19 | 0.259573E+09 | 347.85 | 10-MAR-14:00 | 21.00 | 17.19 |
April | 0.248664E+10 | 5463.10 | 26-APR-16:00 | 22.00 | 16.41 | 0.245600E+09 | 347.86 | 13-APR-13:00 | 22.00 | 16.41 |
May | 0.264104E+10 | 5075.15 | 03-MAY-16:00 | 21.00 | 15.00 | 0.268858E+09 | 347.88 | 03-MAY-13:00 | 21.00 | 15.00 |
June | 0.316048E+10 | 8650.73 | 25-JUN-16:42 | 21.00 | 16.52 | 0.271942E+09 | 347.85 | 23-JUN-09:09 | 21.00 | 16.52 |
July | 0.374346E+10 | 11017.15 | 23-JUL-16:22 | 24.00 | 19.02 | 0.255571E+09 | 347.85 | 12-JUL-09:00 | 24.00 | 19.02 |
August | 0.391900E+10 | 9357.10 | 20-AUG-17:03 | 20.50 | 16.93 | 0.286526E+09 | 347.85 | 15-AUG-13:50 | 20.50 | 16.93 |
September | 0.308768E+10 | 8906.45 | 04-SEP-16:03 | 19.67 | 15.96 | 0.253007E+09 | 347.85 | 13-SEP-09:09 | 22.17 | 18.15 |
October | 0.286324E+10 | 10753.41 | 15-OCT-15:52 | 30.00 | 14.89 | 0.260815E+09 | 347.86 | 03-OCT-13:00 | 30.00 | 14.89 |
November | 0.202795E+10 | 3940.98 | 07-NOV-15:40 | 19.00 | 14.59 | 0.249303E+09 | 347.90 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.182789E+10 | 3846.35 | 19-DEC-15:30 | 21.50 | 8.94 | 0.235249E+09 | 347.90 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.310601E+11 | 0.304648E+10 | ||||||||
Minimum of Months | 0.162279E+10 | 3586.58 | 15.00 | 8.94 | 0.218614E+09 | 347.85 | 15.00 | 12.17 | ||
Maximum of Months | 0.391900E+10 | 11017.15 | 30.00 | 19.02 | 0.286526E+09 | 347.90 | 30.00 | 19.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193337E+10 | 2732.19 | 18-JAN-14:10 | 24.33 | 14.82 | 0.377657E+09 | 549.49 | 24-JAN-14:30 | 24.50 | 15.08 |
February | 0.182039E+10 | 2465.79 | 03-FEB-15:00 | 23.00 | 8.84 | 0.349316E+09 | 549.54 | 01-FEB-14:09 | 23.00 | 8.84 |
March | 0.217463E+10 | 2884.78 | 23-MAR-15:20 | 21.67 | 17.34 | 0.415993E+09 | 549.49 | 09-MAR-14:39 | 21.67 | 17.34 |
April | 0.256994E+10 | 3850.74 | 26-APR-14:00 | 26.00 | 16.74 | 0.389828E+09 | 549.51 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.297221E+10 | 4178.11 | 04-MAY-14:10 | 22.83 | 16.63 | 0.427581E+09 | 549.54 | 03-MAY-13:00 | 22.83 | 16.63 |
June | 0.359328E+10 | 4018.64 | 27-JUN-16:00 | 22.00 | 18.09 | 0.431999E+09 | 549.50 | 22-JUN-09:50 | 22.00 | 18.09 |
July | 0.398551E+10 | 4555.68 | 31-JUL-13:10 | 27.83 | 21.13 | 0.403010E+09 | 549.49 | 13-JUL-09:09 | 27.83 | 21.13 |
August | 0.404498E+10 | 4490.21 | 18-AUG-15:00 | 27.00 | 20.85 | 0.451630E+09 | 549.49 | 15-AUG-13:50 | 27.00 | 20.85 |
September | 0.317932E+10 | 5368.80 | 29-SEP-13:10 | 35.67 | 18.16 | 0.398004E+09 | 549.50 | 13-SEP-09:09 | 35.67 | 18.16 |
October | 0.320607E+10 | 5546.39 | 16-OCT-12:30 | 35.05 | 17.21 | 0.411234E+09 | 549.50 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.210413E+10 | 2513.03 | 01-NOV-14:00 | 17.00 | 13.47 | 0.392955E+09 | 549.52 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.200453E+10 | 2751.29 | 05-DEC-15:00 | 25.00 | 13.22 | 0.369782E+09 | 549.54 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.335884E+11 | 0.481899E+10 | ||||||||
Minimum of Months | 0.182039E+10 | 2465.79 | 17.00 | 8.84 | 0.349316E+09 | 549.49 | 19.00 | 8.84 | ||
Maximum of Months | 0.404498E+10 | 5546.39 | 35.67 | 21.13 | 0.451630E+09 | 549.54 | 35.67 | 21.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185499E+10 | 3743.04 | 20-JAN-09:30 | 18.00 | 14.38 | 0.183039E+09 | 338.72 | 19-JAN-11:20 | 18.00 | 14.38 |
February | 0.175761E+10 | 3441.80 | 02-FEB-09:40 | 16.33 | 12.33 | 0.166062E+09 | 338.75 | 01-FEB-13:39 | 16.33 | 12.33 |
March | 0.217990E+10 | 5153.48 | 23-MAR-09:00 | 19.00 | 14.76 | 0.198101E+09 | 339.03 | 30-MAR-08:09 | 9.50 | 6.96 |
April | 0.291349E+10 | 6175.48 | 30-APR-07:53 | 18.00 | 13.88 | 0.184535E+09 | 338.76 | 13-APR-10:09 | 18.00 | 13.88 |
May | 0.295242E+10 | 6112.94 | 28-MAY-08:23 | 18.50 | 14.07 | 0.199946E+09 | 338.77 | 24-MAY-10:39 | 18.50 | 14.07 |
June | 0.343418E+10 | 7546.95 | 18-JUN-08:63 | 19.50 | 15.55 | 0.200949E+09 | 338.73 | 02-JUN-10:09 | 19.50 | 15.55 |
July | 0.408949E+10 | 11239.93 | 23-JUL-09:43 | 25.00 | 20.11 | 0.188905E+09 | 338.73 | 12-JUL-10:09 | 25.00 | 20.11 |
August | 0.434151E+10 | 7541.82 | 20-AUG-09:33 | 22.00 | 18.63 | 0.211051E+09 | 338.72 | 22-AUG-10:30 | 21.50 | 15.92 |
September | 0.314625E+10 | 7325.07 | 10-SEP-09:43 | 22.83 | 17.78 | 0.185608E+09 | 338.73 | 13-SEP-08:39 | 21.33 | 17.45 |
October | 0.301990E+10 | 11684.19 | 15-OCT-08:23 | 31.00 | 15.00 | 0.193217E+09 | 338.77 | 18-OCT-12:09 | 23.83 | 17.80 |
November | 0.199430E+10 | 3353.22 | 13-NOV-09:20 | 17.33 | 13.62 | 0.186991E+09 | 338.74 | 30-NOV-11:00 | 21.00 | 11.99 |
December | 0.190683E+10 | 3613.83 | 05-DEC-09:30 | 25.00 | 12.45 | 0.178645E+09 | 338.74 | 07-DEC-11:39 | 21.00 | 14.37 |
Annual Sum or Average | 0.335909E+11 | 0.227705E+10 | ||||||||
Minimum of Months | 0.175761E+10 | 3353.22 | 16.33 | 12.33 | 0.166062E+09 | 338.72 | 9.50 | 6.96 | ||
Maximum of Months | 0.434151E+10 | 11684.19 | 31.00 | 20.11 | 0.211051E+09 | 339.03 | 25.00 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.534037E+10 | 14245.32 | 22-JAN-13:23 | 17.50 | 12.39 | 0.409286E+09 | 550.16 | 20-JAN-14:09 | 17.50 | 12.39 |
February | 0.394698E+10 | 11617.17 | 20-FEB-13:13 | 17.00 | 10.50 | 0.366681E+09 | 549.85 | 03-FEB-14:00 | 17.00 | 10.50 |
March | 0.388937E+10 | 8611.36 | 19-MAR-12:33 | 20.33 | 15.40 | 0.433411E+09 | 549.72 | 23-MAR-13:00 | 23.00 | 17.27 |
April | 0.403083E+10 | 7295.93 | 26-APR-13:00 | 27.00 | 17.13 | 0.393824E+09 | 549.53 | 13-APR-09:00 | 27.00 | 17.13 |
May | 0.342059E+10 | 5544.76 | 04-MAY-12:30 | 23.50 | 16.62 | 0.427026E+09 | 549.55 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.374821E+10 | 4933.59 | 30-JUN-13:10 | 23.00 | 17.85 | 0.430864E+09 | 549.49 | 22-JUN-09:50 | 23.00 | 17.85 |
July | 0.438459E+10 | 6875.70 | 31-JUL-12:40 | 28.00 | 21.19 | 0.402640E+09 | 549.49 | 28-JUL-13:39 | 28.00 | 21.19 |
August | 0.551324E+10 | 7959.73 | 30-AUG-12:50 | 23.83 | 17.97 | 0.452257E+09 | 549.50 | 15-AUG-13:50 | 23.83 | 17.97 |
September | 0.551627E+10 | 11240.64 | 29-SEP-13:10 | 35.67 | 18.16 | 0.400610E+09 | 563.18 | 29-SEP-13:20 | 35.33 | 18.10 |
October | 0.636825E+10 | 14825.30 | 15-OCT-11:02 | 32.00 | 16.46 | 0.417294E+09 | 580.19 | 16-OCT-13:09 | 33.75 | 16.65 |
November | 0.543994E+10 | 14851.68 | 19-NOV-13:02 | 26.67 | 15.00 | 0.409573E+09 | 549.99 | 28-NOV-14:50 | 23.33 | 10.84 |
December | 0.567810E+10 | 14043.96 | 25-DEC-13:02 | 22.00 | 9.19 | 0.397198E+09 | 549.94 | 20-DEC-14:00 | 22.00 | 9.19 |
Annual Sum or Average | 0.572767E+11 | 0.494066E+10 | ||||||||
Minimum of Months | 0.342059E+10 | 4933.59 | 17.00 | 9.19 | 0.366681E+09 | 549.49 | 17.00 | 9.19 | ||
Maximum of Months | 0.636825E+10 | 14851.68 | 35.67 | 21.19 | 0.452257E+09 | 580.19 | 35.33 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201328E+10 | 4627.12 | 18-JAN-15:00 | 23.00 | 14.79 | 0.239752E+09 | 347.85 | 09-JAN-14:00 | 23.00 | 14.79 |
February | 0.195599E+10 | 4934.24 | 22-FEB-15:40 | 16.60 | 12.17 | 0.219028E+09 | 347.88 | 01-FEB-14:09 | 16.60 | 12.17 |
March | 0.239847E+10 | 6362.04 | 23-MAR-15:50 | 21.17 | 17.23 | 0.260380E+09 | 347.86 | 01-MAR-14:09 | 21.17 | 17.23 |
April | 0.306003E+10 | 8354.42 | 02-APR-15:43 | 19.33 | 14.45 | 0.244419E+09 | 347.87 | 13-APR-13:00 | 20.00 | 15.65 |
May | 0.317954E+10 | 6721.07 | 21-MAY-16:53 | 18.00 | 13.88 | 0.267551E+09 | 347.89 | 03-MAY-13:00 | 18.00 | 13.88 |
June | 0.378006E+10 | 11986.73 | 25-JUN-16:12 | 21.00 | 16.52 | 0.271518E+09 | 347.85 | 22-JUN-09:50 | 21.00 | 16.52 |
July | 0.421997E+10 | 12720.16 | 23-JUL-16:22 | 24.00 | 19.02 | 0.254590E+09 | 347.85 | 13-JUL-09:09 | 24.00 | 19.02 |
August | 0.440764E+10 | 12203.62 | 06-AUG-15:53 | 24.00 | 19.90 | 0.285261E+09 | 347.85 | 15-AUG-13:00 | 24.00 | 19.31 |
September | 0.346064E+10 | 11581.41 | 04-SEP-15:32 | 20.33 | 16.11 | 0.250880E+09 | 347.85 | 12-SEP-09:50 | 22.67 | 17.05 |
October | 0.317487E+10 | 11588.63 | 15-OCT-15:42 | 30.17 | 14.99 | 0.258311E+09 | 347.86 | 03-OCT-13:00 | 30.17 | 14.99 |
November | 0.232134E+10 | 4731.62 | 10-NOV-14:50 | 19.17 | 15.85 | 0.245772E+09 | 347.90 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.211000E+10 | 4636.79 | 19-DEC-15:30 | 21.50 | 8.94 | 0.233213E+09 | 347.91 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.360818E+11 | 0.303068E+10 | ||||||||
Minimum of Months | 0.195599E+10 | 4627.12 | 16.60 | 8.94 | 0.219028E+09 | 347.85 | 16.60 | 12.17 | ||
Maximum of Months | 0.440764E+10 | 12720.16 | 30.17 | 19.90 | 0.285261E+09 | 347.91 | 30.17 | 19.31 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.854378E+09 | 6407.16 | 03-JAN-07:03 | 3.67 |
February | 0.616211E+09 | 3922.23 | 09-FEB-06:03 | 6.45 |
March | 0.729810E+09 | 4325.20 | 30-MAR-06:03 | 5.58 |
April | 0.352236E+09 | 3575.23 | 17-APR-05:03 | 11.00 |
May | 0.294970E+09 | 3710.09 | 19-MAY-05:03 | 8.67 |
June | 0.138619E+09 | 3442.12 | 14-JUN-05:03 | 13.17 |
July | 71801651.71 | 3051.50 | 06-JUL-05:03 | 14.33 |
August | 89313042.47 | 3066.74 | 06-AUG-07:07 | 19.50 |
September | 0.177587E+09 | 3420.72 | 20-SEP-05:03 | 12.00 |
October | 0.318213E+09 | 3648.81 | 30-OCT-05:03 | 10.83 |
November | 0.565670E+09 | 3981.89 | 24-NOV-06:03 | 8.92 |
December | 0.782294E+09 | 4076.43 | 20-DEC-06:03 | 8.67 |
Annual Sum or Average | 0.499110E+10 | |||
Minimum of Months | 71801651.71 | 3051.50 | 3.67 | |
Maximum of Months | 0.854378E+09 | 6407.16 | 19.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.392599E+09 | 3812.24 | 29-JAN-12:03 | 15.83 |
February | 0.229219E+09 | 3356.11 | 20-FEB-12:33 | 17.00 |
March | 0.315258E+09 | 2977.79 | 12-MAR-11:23 | 20.00 |
April | 42392855.37 | 2564.65 | 02-APR-14:30 | 22.00 |
May | 27907190.01 | 2283.83 | 14-MAY-14:43 | 18.17 |
June | 11766887.42 | 1771.71 | 25-JUN-13:38 | 22.67 |
July | 19138635.23 | 1760.22 | 09-JUL-13:40 | 21.33 |
August | 14532058.96 | 1598.21 | 20-AUG-13:55 | 23.00 |
September | 15128225.47 | 2286.80 | 24-SEP-11:23 | 21.00 |
October | 35100934.74 | 3441.47 | 15-OCT-09:43 | 31.33 |
November | 0.116541E+09 | 3611.92 | 05-NOV-12:13 | 18.00 |
December | 0.251407E+09 | 4472.97 | 25-DEC-13:02 | 22.00 |
Annual Sum or Average | 0.147099E+10 | |||
Minimum of Months | 11766887.42 | 1598.21 | 15.83 | |
Maximum of Months | 0.392599E+09 | 4472.97 | 31.33 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131737E+09 | 2585.87 | 08-JAN-11:30 | 16.50 |
February | 64318971.90 | 2311.67 | 20-FEB-10:50 | 15.67 |
March | 69996521.30 | 2169.65 | 12-MAR-12:07 | 19.33 |
April | 12020905.60 | 2287.80 | 30-APR-14:05 | 23.83 |
May | 12597094.98 | 2048.91 | 28-MAY-14:48 | 21.00 |
June | 10903778.23 | 1824.23 | 18-JUN-14:20 | 23.00 |
July | 15628614.21 | 1641.88 | 30-JUL-13:33 | 24.00 |
August | 13779811.47 | 1854.06 | 13-AUG-13:50 | 24.00 |
September | 19045624.67 | 1969.31 | 04-SEP-10:50 | 21.00 |
October | 23153091.44 | 2202.29 | 08-OCT-11:13 | 21.67 |
November | 20440890.73 | 2520.28 | 26-NOV-10:50 | 15.67 |
December | 46800140.27 | 2936.94 | 25-DEC-13:02 | 22.00 |
Annual Sum or Average | 0.440422E+09 | |||
Minimum of Months | 10903778.23 | 1641.88 | 15.67 | |
Maximum of Months | 0.131737E+09 | 2936.94 | 24.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 853133.19 | 5687.55 | 02-JAN-07:03 | 11.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 853133.19 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 853133.19 | 5687.55 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 25094006.58 | 21353.10 | 02-JAN-07:03 | 11.00 |
February | 2944631.77 | 10294.74 | 27-FEB-07:03 | 10.67 |
March | 3250074.45 | 17071.66 | 30-MAR-06:03 | 5.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 1594691.49 | 10631.28 | 26-DEC-07:03 | 7.67 |
Annual Sum or Average | 32883404.29 | |||
Minimum of Months | 0.00 | 0.00 | 5.58 | |
Maximum of Months | 25094006.58 | 21353.10 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174168E+09 | 8755.91 | 03-JAN-06:11 | 4.33 |
February | 51476646.11 | 7753.26 | 13-FEB-07:03 | 14.17 |
March | 89056924.63 | 8478.13 | 30-MAR-05:12 | 5.03 |
April | 8084274.39 | 7737.23 | 01-APR-06:03 | 7.67 |
May | 493433.87 | 2467.17 | 15-MAY-06:03 | 11.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 2398606.93 | 7693.03 | 30-OCT-06:02 | 10.50 |
November | 28816935.55 | 7729.96 | 27-NOV-07:03 | 14.67 |
December | 81319274.40 | 8199.76 | 13-DEC-06:12 | 6.33 |
Annual Sum or Average | 0.435814E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 0.174168E+09 | 8755.91 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 64096996.48 | 6707.34 | 03-JAN-06:11 | 4.33 |
February | 21332697.21 | 5680.12 | 10-FEB-07:03 | 7.57 |
March | 29138056.62 | 6457.61 | 30-MAR-05:12 | 5.03 |
April | 1974537.74 | 4960.05 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 1685084.17 | 5770.64 | 30-OCT-06:02 | 10.50 |
November | 6715981.84 | 4820.87 | 24-NOV-07:03 | 8.75 |
December | 24815339.45 | 6143.04 | 13-DEC-06:12 | 6.33 |
Annual Sum or Average | 0.149759E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 64096996.48 | 6707.34 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73612350.25 | 10295.98 | 03-JAN-06:11 | 4.33 |
February | 25604024.41 | 8617.37 | 27-FEB-07:03 | 10.67 |
March | 60727907.34 | 10088.14 | 30-MAR-05:12 | 5.03 |
April | 7091727.33 | 9178.35 | 01-APR-06:03 | 7.67 |
May | 2074468.98 | 5550.54 | 15-MAY-06:03 | 11.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 803415.22 | 2313.25 | 30-OCT-06:02 | 10.50 |
November | 6415715.69 | 7397.64 | 24-NOV-07:03 | 8.75 |
December | 24068975.87 | 9682.37 | 13-DEC-06:12 | 6.33 |
Annual Sum or Average | 0.200399E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 73612350.25 | 10295.98 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106800E+09 | 6501.50 | 03-JAN-06:11 | 4.33 |
February | 34382321.26 | 5805.93 | 06-FEB-07:03 | 9.50 |
March | 58102868.57 | 6364.93 | 29-MAR-05:12 | 7.00 |
April | 6694686.40 | 5883.91 | 01-APR-06:03 | 7.67 |
May | 1465486.07 | 3088.77 | 15-MAY-06:03 | 11.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 2448380.29 | 5438.53 | 30-OCT-06:02 | 10.50 |
November | 20489449.25 | 5721.41 | 20-NOV-07:02 | 11.00 |
December | 54074427.19 | 6096.56 | 13-DEC-06:12 | 6.33 |
Annual Sum or Average | 0.284458E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 0.106800E+09 | 6501.50 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20410170.31 | 6522.59 | 03-JAN-06:11 | 4.33 |
February | 4462056.01 | 4607.37 | 06-FEB-07:03 | 9.50 |
March | 10848900.40 | 6283.04 | 30-MAR-06:03 | 5.58 |
April | 1017345.74 | 5691.86 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 25396.75 | 169.31 | 27-NOV-07:03 | 14.67 |
December | 3392621.20 | 6102.08 | 26-DEC-07:03 | 7.67 |
Annual Sum or Average | 40156490.42 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 20410170.31 | 6522.59 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2992132.25 | 4537.80 | 03-JAN-07:03 | 3.67 |
February | 451900.62 | 1070.80 | 27-FEB-07:03 | 10.67 |
March | 1931192.35 | 4584.22 | 30-MAR-06:03 | 5.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 231.50 | 1.54 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 5375456.72 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 2992132.25 | 4584.22 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.354000E+09 | 7590.86 | 03-JAN-07:10 | 3.67 |
February | 0.340112E+09 | 6909.56 | 27-FEB-12:06 | 13.00 |
March | 0.658030E+09 | 7600.83 | 30-MAR-06:10 | 5.58 |
April | 0.250841E+09 | 6860.14 | 03-APR-06:10 | 10.17 |
May | 0.204925E+09 | 6798.64 | 15-MAY-06:07 | 11.33 |
June | 56301926.83 | 5099.17 | 12-JUN-06:07 | 14.00 |
July | 470505.99 | 1291.24 | 17-JUL-06:10 | 15.12 |
August | 2003310.69 | 2481.81 | 28-AUG-06:08 | 14.00 |
September | 15791381.82 | 4314.96 | 20-SEP-06:05 | 12.17 |
October | 56809921.43 | 6797.22 | 30-OCT-06:06 | 10.50 |
November | 0.146208E+09 | 6816.14 | 30-NOV-07:10 | 8.67 |
December | 0.288042E+09 | 6993.02 | 13-DEC-07:10 | 7.17 |
Annual Sum or Average | 0.237353E+10 | |||
Minimum of Months | 470505.99 | 1291.24 | 3.67 | |
Maximum of Months | 0.658030E+09 | 7600.83 | 15.12 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7010935.34 | 4464.97 | 09-JAN-07:03 | 3.67 |
February | 925970.95 | 1944.64 | 28-FEB-07:03 | 11.33 |
March | 3998730.93 | 4408.55 | 30-MAR-06:03 | 5.58 |
April | 607464.84 | 3463.08 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 828313.34 | 2363.72 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 13371415.39 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 7010935.34 | 4464.97 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26666767.60 | 7243.02 | 03-JAN-06:11 | 4.33 |
February | 2913600.83 | 4392.04 | 27-FEB-07:03 | 10.67 |
March | 9347376.29 | 6865.81 | 30-MAR-06:03 | 5.58 |
April | 672343.97 | 4482.29 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 434739.60 | 1484.86 | 27-NOV-07:03 | 14.67 |
December | 4566660.99 | 6476.84 | 26-DEC-07:03 | 7.67 |
Annual Sum or Average | 44601489.28 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 26666767.60 | 7243.02 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10882772.60 | 5227.09 | 02-JAN-06:11 | 11.00 |
February | 1429847.83 | 2534.45 | 27-FEB-07:03 | 10.67 |
March | 3204734.75 | 4737.58 | 30-MAR-06:03 | 5.58 |
April | 155809.76 | 1038.73 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 1523089.25 | 3049.94 | 26-DEC-07:03 | 7.67 |
Annual Sum or Average | 17196254.19 | |||
Minimum of Months | 0.00 | 0.00 | 5.58 | |
Maximum of Months | 10882772.60 | 5227.09 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8612712.44 | 7502.17 | 09-JAN-07:03 | 3.67 |
February | 662402.46 | 1630.55 | 13-FEB-07:03 | 14.17 |
March | 5545141.52 | 7322.05 | 30-MAR-06:03 | 5.58 |
April | 598685.82 | 3991.24 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 485487.59 | 3236.58 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 15904429.82 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 8612712.44 | 7502.17 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17797103.28 | 5049.71 | 02-JAN-06:11 | 11.00 |
February | 2974348.80 | 3413.44 | 28-FEB-07:03 | 11.33 |
March | 7859317.22 | 4948.28 | 08-MAR-07:03 | 6.50 |
April | 919074.13 | 4626.04 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 452670.66 | 1151.40 | 24-NOV-07:03 | 8.75 |
December | 5008480.42 | 4908.36 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 35010994.51 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 17797103.28 | 5049.71 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.100794E+10 | 1592.13 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.848681E+09 | 1592.13 | 27-FEB-16:49 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.963866E+09 | 1111.04 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.824015E+09 | 1111.04 | 21-APR-15:50 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.866322E+09 | 907.52 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.855717E+09 | 907.52 | 09-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.805216E+09 | 833.48 | 11-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.904604E+09 | 907.52 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.849814E+09 | 1388.60 | 18-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.951991E+09 | 1388.60 | 05-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.979966E+09 | 1592.13 | 06-NOV-16:19 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.994878E+09 | 1592.13 | 01-DEC-16:10 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.108530E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.805216E+09 | 833.48 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.100794E+10 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.617310E+09 | 1007.95 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.528887E+09 | 1007.95 | 27-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.605209E+09 | 703.38 | 01-MAR-16:49 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.522712E+09 | 703.38 | 21-APR-15:30 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.552816E+09 | 527.66 | 04-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.546628E+09 | 527.66 | 08-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.514368E+09 | 527.66 | 28-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.575591E+09 | 527.66 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.534386E+09 | 703.38 | 18-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.585810E+09 | 879.10 | 20-OCT-15:39 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.608422E+09 | 1007.95 | 06-NOV-16:19 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.605737E+09 | 1007.95 | 01-DEC-16:10 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.679788E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.514368E+09 | 527.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.617310E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.942195E+09 | 1592.13 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.815015E+09 | 1592.13 | 27-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.949034E+09 | 1111.04 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.824665E+09 | 1111.04 | 21-APR-15:00 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.874525E+09 | 907.52 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.866653E+09 | 907.52 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.814817E+09 | 907.52 | 12-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.910620E+09 | 907.52 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.842791E+09 | 1185.08 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.895867E+09 | 1111.04 | 04-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.927971E+09 | 1592.13 | 06-NOV-16:40 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.920531E+09 | 1592.13 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.105847E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.814817E+09 | 907.52 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.949034E+09 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.612921E+09 | 1007.89 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.525221E+09 | 1007.89 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.605326E+09 | 879.04 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.523135E+09 | 703.34 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.552507E+09 | 703.34 | 08-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.544740E+09 | 574.49 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.512562E+09 | 574.49 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.576446E+09 | 703.34 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.537812E+09 | 879.04 | 18-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.581235E+09 | 879.04 | 05-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.597109E+09 | 1007.89 | 06-NOV-16:40 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.604073E+09 | 1007.89 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.677309E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.512562E+09 | 574.49 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.612921E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.100201E+10 | 1592.13 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.844451E+09 | 1592.13 | 27-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.960720E+09 | 1111.04 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.823198E+09 | 1111.04 | 21-APR-15:50 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.865298E+09 | 907.52 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.854838E+09 | 907.52 | 09-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.804450E+09 | 833.48 | 11-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.903615E+09 | 907.52 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.847334E+09 | 1185.08 | 18-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.945453E+09 | 1388.60 | 20-OCT-15:50 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.975248E+09 | 1592.13 | 06-NOV-16:19 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.987482E+09 | 1592.13 | 01-DEC-16:10 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.108141E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.804450E+09 | 833.48 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.100201E+10 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.616049E+09 | 1007.95 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.527682E+09 | 1007.95 | 27-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.603883E+09 | 703.38 | 01-MAR-16:49 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.521862E+09 | 703.38 | 21-APR-15:39 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.551866E+09 | 527.66 | 04-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.545764E+09 | 527.66 | 08-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.513674E+09 | 527.66 | 28-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.574620E+09 | 527.66 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.533325E+09 | 703.38 | 18-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.583650E+09 | 879.10 | 20-OCT-15:39 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.606533E+09 | 1007.95 | 06-NOV-16:19 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.604166E+09 | 1007.95 | 01-DEC-16:10 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.678307E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.513674E+09 | 527.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.616049E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.940851E+09 | 1592.13 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.815692E+09 | 1592.13 | 27-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.947632E+09 | 1111.04 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.823459E+09 | 1111.04 | 21-APR-15:00 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.873138E+09 | 907.52 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.865047E+09 | 907.52 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.813535E+09 | 833.48 | 11-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.909445E+09 | 907.52 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.841285E+09 | 1111.04 | 05-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.894236E+09 | 1111.04 | 04-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.927444E+09 | 1592.13 | 06-NOV-16:40 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.919157E+09 | 1592.13 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.105709E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.813535E+09 | 833.48 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.947632E+09 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.611193E+09 | 1007.89 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.524035E+09 | 1007.89 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.603829E+09 | 879.04 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.522202E+09 | 703.34 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.551569E+09 | 703.34 | 09-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.544196E+09 | 574.49 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.511846E+09 | 574.49 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.575579E+09 | 703.34 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.536471E+09 | 879.04 | 18-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.579176E+09 | 879.04 | 05-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.595803E+09 | 1007.89 | 06-NOV-16:40 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.600624E+09 | 1007.89 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.675652E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.511846E+09 | 574.49 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.611193E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.100794E+10 | 1592.13 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.848640E+09 | 1592.13 | 27-FEB-16:49 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.963866E+09 | 1111.04 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.824015E+09 | 1111.04 | 21-APR-15:50 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.866322E+09 | 907.52 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.855717E+09 | 907.52 | 09-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.805216E+09 | 833.48 | 11-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.904604E+09 | 907.52 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.849814E+09 | 1388.60 | 18-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.951991E+09 | 1388.60 | 05-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.979966E+09 | 1592.13 | 06-NOV-16:19 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.994878E+09 | 1592.13 | 01-DEC-16:10 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.108530E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.805216E+09 | 833.48 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.100794E+10 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.617310E+09 | 1007.95 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.528887E+09 | 1007.95 | 27-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.605209E+09 | 703.38 | 01-MAR-16:49 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.522712E+09 | 703.38 | 21-APR-15:30 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.552816E+09 | 527.66 | 04-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.546628E+09 | 527.66 | 08-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.514368E+09 | 527.66 | 28-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.575591E+09 | 527.66 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.534386E+09 | 703.38 | 18-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.585810E+09 | 879.10 | 20-OCT-15:39 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.608422E+09 | 1007.95 | 06-NOV-16:19 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.605709E+09 | 1007.95 | 01-DEC-16:10 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.679785E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.514368E+09 | 527.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.617310E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.942195E+09 | 1592.13 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.815015E+09 | 1592.13 | 27-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.949034E+09 | 1111.04 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.824665E+09 | 1111.04 | 21-APR-15:00 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.874525E+09 | 907.52 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.866638E+09 | 907.52 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.814817E+09 | 907.52 | 12-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.910620E+09 | 907.52 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.842791E+09 | 1185.08 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.895867E+09 | 1111.04 | 04-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.927971E+09 | 1592.13 | 06-NOV-16:40 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.920531E+09 | 1592.13 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.105847E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.814817E+09 | 907.52 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.949034E+09 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.612921E+09 | 1007.89 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.525221E+09 | 1007.89 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.605326E+09 | 879.04 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.523135E+09 | 703.34 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.552507E+09 | 703.34 | 08-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.544740E+09 | 574.49 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.512562E+09 | 574.49 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.576446E+09 | 703.34 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.537812E+09 | 879.04 | 18-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.581235E+09 | 879.04 | 05-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.597109E+09 | 1007.89 | 06-NOV-16:40 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.604073E+09 | 1007.89 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.677309E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.512562E+09 | 574.49 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.612921E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.100794E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 835353.13 | 0.288541E+09 |
February | 0.901968E+09 | 0.848681E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66809.12 | 0.339469E+09 |
March | 0.107774E+10 | 0.963866E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120501.84 | 0.374594E+09 |
April | 0.956342E+09 | 0.824015E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1040453.72 | 0.226784E+09 |
May | 0.103597E+10 | 0.866322E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277935E+09 |
June | 0.103308E+10 | 0.855717E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32591.04 | 0.152114E+09 |
July | 0.959235E+09 | 0.805216E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2721978.06 | 0.109134E+09 |
August | 0.107774E+10 | 0.904604E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2776834.35 | 0.133042E+09 |
September | 0.956342E+09 | 0.849814E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4075120.75 | 0.127533E+09 |
October | 0.994195E+09 | 0.951991E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15393605.92 | 0.194031E+09 |
November | 0.984487E+09 | 0.979966E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1866989.47 | 0.280485E+09 |
December | 0.959235E+09 | 0.994878E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1379925.19 | 0.293532E+09 |
Annual Sum or Average | 0.119305E+11 | 0.108530E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30310162.59 | 0.279719E+10 |
Minimum of Months | 0.901968E+09 | 0.805216E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109134E+09 |
Maximum of Months | 0.107774E+10 | 0.100794E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15393605.92 | 0.374594E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.617310E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 350866.46 | 0.198837E+09 |
February | 0.571020E+09 | 0.528887E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36924.35 | 0.233829E+09 |
March | 0.682301E+09 | 0.605209E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1667.81 | 0.257399E+09 |
April | 0.605444E+09 | 0.522712E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 174981.97 | 0.160145E+09 |
May | 0.655854E+09 | 0.552816E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192460E+09 |
June | 0.654023E+09 | 0.546628E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21724.57 | 0.104122E+09 |
July | 0.607275E+09 | 0.514368E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1570868.66 | 77903033.84 |
August | 0.682301E+09 | 0.575591E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1635604.74 | 93934882.18 |
September | 0.605444E+09 | 0.534386E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2716246.12 | 89690977.45 |
October | 0.629407E+09 | 0.585810E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9137758.49 | 0.134682E+09 |
November | 0.623262E+09 | 0.608422E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 580617.03 | 0.193609E+09 |
December | 0.607275E+09 | 0.605737E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 285832.71 | 0.202630E+09 |
Annual Sum or Average | 0.755301E+10 | 0.679788E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16513092.91 | 0.193924E+10 |
Minimum of Months | 0.571020E+09 | 0.514368E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77903033.84 |
Maximum of Months | 0.682301E+09 | 0.617310E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9137758.49 | 0.257399E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.942195E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 337375.91 | 0.324487E+09 |
February | 0.901968E+09 | 0.815015E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55384.52 | 0.375307E+09 |
March | 0.107774E+10 | 0.949034E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396632E+09 |
April | 0.956342E+09 | 0.824665E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 379605.03 | 0.243193E+09 |
May | 0.103597E+10 | 0.874525E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281761E+09 |
June | 0.103308E+10 | 0.866653E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32592.28 | 0.150485E+09 |
July | 0.959235E+09 | 0.814817E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2675664.76 | 0.110528E+09 |
August | 0.107774E+10 | 0.910620E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2467928.61 | 0.139870E+09 |
September | 0.956342E+09 | 0.842791E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4055418.18 | 0.144326E+09 |
October | 0.994195E+09 | 0.895867E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13132518.44 | 0.220642E+09 |
November | 0.984487E+09 | 0.927971E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115108.62 | 0.315696E+09 |
December | 0.959235E+09 | 0.920531E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 221846.12 | 0.336733E+09 |
Annual Sum or Average | 0.119305E+11 | 0.105847E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23473442.48 | 0.303966E+10 |
Minimum of Months | 0.901968E+09 | 0.814817E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110528E+09 |
Maximum of Months | 0.107774E+10 | 0.949034E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13132518.44 | 0.396632E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.612921E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 477722.72 | 0.198010E+09 |
February | 0.570983E+09 | 0.525221E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68294.14 | 0.233828E+09 |
March | 0.682256E+09 | 0.605326E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69975.07 | 0.255303E+09 |
April | 0.605404E+09 | 0.523135E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 773162.94 | 0.162812E+09 |
May | 0.655811E+09 | 0.552507E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196318E+09 |
June | 0.653980E+09 | 0.544740E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22717.43 | 0.105889E+09 |
July | 0.607235E+09 | 0.512562E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2049203.67 | 79769465.01 |
August | 0.682256E+09 | 0.576446E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2086995.60 | 96165403.91 |
September | 0.605404E+09 | 0.537812E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2723005.20 | 93589451.47 |
October | 0.629366E+09 | 0.581235E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10045284.95 | 0.136922E+09 |
November | 0.623221E+09 | 0.597109E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1091862.97 | 0.194062E+09 |
December | 0.607235E+09 | 0.604073E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 866710.76 | 0.202284E+09 |
Annual Sum or Average | 0.755252E+10 | 0.677309E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20274935.44 | 0.195495E+10 |
Minimum of Months | 0.570983E+09 | 0.512562E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79769465.01 |
Maximum of Months | 0.682256E+09 | 0.612921E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10045284.95 | 0.255303E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.100201E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 442207.63 | 0.167647E+09 |
February | 0.901968E+09 | 0.844451E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44272.46 | 0.193028E+09 |
March | 0.107774E+10 | 0.960720E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94837.90 | 0.208748E+09 |
April | 0.956342E+09 | 0.823198E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 582679.11 | 0.122079E+09 |
May | 0.103597E+10 | 0.865298E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.04 | 0.150634E+09 |
June | 0.103308E+10 | 0.854838E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19272.92 | 79992246.93 |
July | 0.959235E+09 | 0.804450E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1620890.24 | 56846270.18 |
August | 0.107774E+10 | 0.903615E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1701786.09 | 70797261.62 |
September | 0.956342E+09 | 0.847334E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2187696.75 | 69178508.75 |
October | 0.994195E+09 | 0.945453E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8731808.38 | 0.110663E+09 |
November | 0.984487E+09 | 0.975248E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1027289.61 | 0.162786E+09 |
December | 0.959235E+09 | 0.987482E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 664903.82 | 0.170700E+09 |
Annual Sum or Average | 0.119305E+11 | 0.108141E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17117687.96 | 0.156310E+10 |
Minimum of Months | 0.901968E+09 | 0.804450E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.04 | 56846270.18 |
Maximum of Months | 0.107774E+10 | 0.100201E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8731808.38 | 0.208748E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.616049E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 151998.39 | 0.118635E+09 |
February | 0.571020E+09 | 0.527682E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20617.75 | 0.135840E+09 |
March | 0.682301E+09 | 0.603883E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4294.76 | 0.146885E+09 |
April | 0.605444E+09 | 0.521862E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97115.98 | 89325914.46 |
May | 0.655854E+09 | 0.551866E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.39 | 0.106912E+09 |
June | 0.654023E+09 | 0.545764E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12844.38 | 56324048.00 |
July | 0.607275E+09 | 0.513674E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 857598.54 | 42574596.06 |
August | 0.682301E+09 | 0.574620E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 898375.74 | 52610237.96 |
September | 0.605444E+09 | 0.533325E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1456292.98 | 50252807.61 |
October | 0.629407E+09 | 0.583650E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5035187.00 | 78954565.61 |
November | 0.623262E+09 | 0.606533E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 299588.98 | 0.114971E+09 |
December | 0.607275E+09 | 0.604166E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 125040.37 | 0.121242E+09 |
Annual Sum or Average | 0.755301E+10 | 0.678307E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8958982.26 | 0.111453E+10 |
Minimum of Months | 0.571020E+09 | 0.513674E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.39 | 42574596.06 |
Maximum of Months | 0.682301E+09 | 0.616049E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5035187.00 | 0.146885E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.940851E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5105692.37 | 0.222276E+10 |
February | 0.901968E+09 | 0.815692E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2723662.85 | 0.204553E+10 |
March | 0.107774E+10 | 0.947632E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.80 | 0.258409E+10 |
April | 0.956342E+09 | 0.823459E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8392186.31 | 0.156132E+10 |
May | 0.103597E+10 | 0.873138E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1617.59 | 0.151815E+10 |
June | 0.103308E+10 | 0.865047E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1451625.04 | 0.104454E+10 |
July | 0.959235E+09 | 0.813535E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53301748.74 | 0.641255E+09 |
August | 0.107774E+10 | 0.909445E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54366904.22 | 0.756854E+09 |
September | 0.956342E+09 | 0.841285E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81458776.16 | 0.102707E+10 |
October | 0.994195E+09 | 0.894236E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139562E+09 | 0.104024E+10 |
November | 0.984487E+09 | 0.927444E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 352292.47 | 0.199623E+10 |
December | 0.959235E+09 | 0.919157E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7290592.58 | 0.201267E+10 |
Annual Sum or Average | 0.119305E+11 | 0.105709E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354007E+09 | 0.184507E+11 |
Minimum of Months | 0.901968E+09 | 0.813535E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.80 | 0.641255E+09 |
Maximum of Months | 0.107774E+10 | 0.947632E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139562E+09 | 0.258409E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.611193E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173919.44 | 0.117474E+09 |
February | 0.570983E+09 | 0.524035E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25706.17 | 0.136170E+09 |
March | 0.682256E+09 | 0.603829E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31739.88 | 0.146292E+09 |
April | 0.605404E+09 | 0.522202E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 272469.67 | 91603772.18 |
May | 0.655811E+09 | 0.551569E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.74 | 0.110426E+09 |
June | 0.653980E+09 | 0.544196E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12856.47 | 58474388.35 |
July | 0.607235E+09 | 0.511846E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1062139.14 | 44521169.54 |
August | 0.682256E+09 | 0.575579E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1014878.99 | 54557437.66 |
September | 0.605404E+09 | 0.536471E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1452663.23 | 53246746.93 |
October | 0.629366E+09 | 0.579176E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5305285.32 | 80892044.70 |
November | 0.623221E+09 | 0.595803E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 492053.24 | 0.115604E+09 |
December | 0.607235E+09 | 0.600624E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 255223.89 | 0.120810E+09 |
Annual Sum or Average | 0.755252E+10 | 0.675652E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10098966.18 | 0.113007E+10 |
Minimum of Months | 0.570983E+09 | 0.511846E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.74 | 44521169.54 |
Maximum of Months | 0.682256E+09 | 0.611193E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5305285.32 | 0.146292E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.100794E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 494042.88 | 0.264340E+09 |
February | 0.901968E+09 | 0.848640E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47799.08 | 0.310368E+09 |
March | 0.107774E+10 | 0.963866E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82621.73 | 0.335730E+09 |
April | 0.956342E+09 | 0.824015E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 755863.23 | 0.199181E+09 |
May | 0.103597E+10 | 0.866322E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242970E+09 |
June | 0.103308E+10 | 0.855717E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28517.49 | 0.130741E+09 |
July | 0.959235E+09 | 0.805216E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2231143.65 | 93274276.11 |
August | 0.107774E+10 | 0.904604E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2356181.82 | 0.115714E+09 |
September | 0.956342E+09 | 0.849814E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3406131.12 | 0.111765E+09 |
October | 0.994195E+09 | 0.951991E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12924367.16 | 0.175784E+09 |
November | 0.984487E+09 | 0.979966E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1408314.65 | 0.256307E+09 |
December | 0.959235E+09 | 0.994878E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 656669.72 | 0.270853E+09 |
Annual Sum or Average | 0.119305E+11 | 0.108530E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24391652.54 | 0.250703E+10 |
Minimum of Months | 0.901968E+09 | 0.805216E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93274276.11 |
Maximum of Months | 0.107774E+10 | 0.100794E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12924367.16 | 0.335730E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.617310E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 235399.01 | 0.180613E+09 |
February | 0.421807E+09 | 0.528887E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31494.65 | 0.211555E+09 |
March | 0.502994E+09 | 0.605209E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4033.26 | 0.228754E+09 |
April | 0.447140E+09 | 0.522712E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 147965.04 | 0.139256E+09 |
May | 0.484071E+09 | 0.552816E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166955E+09 |
June | 0.482240E+09 | 0.546628E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19005.35 | 89090421.03 |
July | 0.448971E+09 | 0.514368E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1324987.65 | 66230466.37 |
August | 0.502994E+09 | 0.575591E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1386249.21 | 80980176.87 |
September | 0.447140E+09 | 0.534386E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2271163.19 | 77703214.52 |
October | 0.465148E+09 | 0.585810E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7779985.91 | 0.120720E+09 |
November | 0.460569E+09 | 0.608422E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 454862.25 | 0.175028E+09 |
December | 0.448971E+09 | 0.605709E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 207650.14 | 0.185239E+09 |
Annual Sum or Average | 0.557719E+10 | 0.679785E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13862795.67 | 0.172212E+10 |
Minimum of Months | 0.421807E+09 | 0.514368E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66230466.37 |
Maximum of Months | 0.502994E+09 | 0.617310E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7779985.91 | 0.228754E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.942195E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 239461.35 | 0.292387E+09 |
February | 0.901968E+09 | 0.815015E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47231.52 | 0.338281E+09 |
March | 0.107774E+10 | 0.949034E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353733E+09 |
April | 0.956342E+09 | 0.824665E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 266045.47 | 0.212720E+09 |
May | 0.103597E+10 | 0.874525E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246539E+09 |
June | 0.103308E+10 | 0.866638E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28518.20 | 0.129934E+09 |
July | 0.959235E+09 | 0.814817E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2169739.02 | 95037841.86 |
August | 0.107774E+10 | 0.910620E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2073810.97 | 0.121834E+09 |
September | 0.956342E+09 | 0.842791E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3384452.90 | 0.125759E+09 |
October | 0.994195E+09 | 0.895867E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10897703.86 | 0.196670E+09 |
November | 0.984487E+09 | 0.927971E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98847.92 | 0.283065E+09 |
December | 0.959235E+09 | 0.920531E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 189155.88 | 0.304109E+09 |
Annual Sum or Average | 0.119305E+11 | 0.105847E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19394967.10 | 0.270007E+10 |
Minimum of Months | 0.901968E+09 | 0.814817E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95037841.86 |
Maximum of Months | 0.107774E+10 | 0.949034E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10897703.86 | 0.353733E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.612921E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 273319.27 | 0.180408E+09 |
February | 0.570983E+09 | 0.525221E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38700.26 | 0.212496E+09 |
March | 0.682256E+09 | 0.605326E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44164.32 | 0.228176E+09 |
April | 0.605404E+09 | 0.523135E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 560287.76 | 0.142813E+09 |
May | 0.655811E+09 | 0.552507E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171547E+09 |
June | 0.653980E+09 | 0.544740E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21682.45 | 91526375.89 |
July | 0.607235E+09 | 0.512562E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1645032.62 | 68774822.17 |
August | 0.682256E+09 | 0.576446E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1660774.39 | 83867596.72 |
September | 0.605404E+09 | 0.537812E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2265466.11 | 81858324.37 |
October | 0.629366E+09 | 0.581235E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8240544.22 | 0.123452E+09 |
November | 0.623221E+09 | 0.597109E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 807128.22 | 0.176133E+09 |
December | 0.607235E+09 | 0.604073E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 440119.36 | 0.185457E+09 |
Annual Sum or Average | 0.755252E+10 | 0.677309E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15997218.98 | 0.174651E+10 |
Minimum of Months | 0.570983E+09 | 0.512562E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68774822.17 |
Maximum of Months | 0.682256E+09 | 0.612921E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8240544.22 | 0.228176E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290883.24 | 0.392421E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40855.25 | 0.457639E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484007E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398196.90 | 0.286447E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340795E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5670.59 | 0.182371E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1829714.33 | 0.134478E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1657928.33 | 0.169330E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3753661.35 | 0.165436E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14116558.54 | 0.261622E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813179.87 | 0.379797E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176338.79 | 0.407285E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23082987.20 | 0.366163E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134478E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14116558.54 | 0.484007E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 763804.90 | 0.473967E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70045.68 | 0.554713E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34256.34 | 0.595164E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 947586.20 | 0.355343E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424212E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8395.73 | 0.229667E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2456783.54 | 0.169274E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2330210.92 | 0.212947E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4935466.42 | 0.204300E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18855715.45 | 0.321499E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1570743.95 | 0.463567E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504261.00 | 0.493170E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32477270.14 | 0.449782E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169274E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18855715.45 | 0.595164E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769897.57 | 0.456235E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11043.67 | 0.541531E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597006E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151055.53 | 0.385561E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460931E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262779E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1071391.75 | 0.203146E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 785191.54 | 0.230543E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4737968.10 | 0.226458E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17059186.73 | 0.314782E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 862688.90 | 0.446085E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246212.79 | 0.462686E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25694636.58 | 0.458774E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203146E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17059186.73 | 0.597006E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.08 | 15-JAN-10:00 | 630.57 | 27-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 27-FEB-16:49 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.84 | 01-FEB-12:00 | 646.85 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 1111.04 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 | 11-MAR-13:00 | 750.96 | 28-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 1111.04 | 21-APR-15:50 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.43 | 30-APR-10:53 | 452.07 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 907.52 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 487.17 | 20-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 907.52 | 09-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.79 | 29-JUN-11:00 | 312.56 | 06-JUN-21:10 |
July | 1306.65 | 03-JUL-09:09 | 833.48 | 11-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.35 | 23-JUL-10:53 | 258.06 | 09-JUL-17:30 |
August | 1306.65 | 01-AUG-09:09 | 907.52 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.96 | 06-AUG-12:50 | 219.82 | 26-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 1388.60 | 18-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.88 | 29-SEP-14:00 | 271.98 | 04-SEP-18:00 |
October | 1306.65 | 02-OCT-09:09 | 1388.60 | 05-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.67 | 15-OCT-09:00 | 464.97 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 06-NOV-16:19 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.64 | 19-NOV-12:52 | 590.94 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:10 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 108.29 | 25-DEC-12:00 | 590.15 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.82 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 351.67 | 750.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1007.95 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.46 | 15-JAN-10:00 | 418.75 | 27-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 1007.95 | 27-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.89 | 01-FEB-12:00 | 425.36 | 25-FEB-03:00 |
March | 827.22 | 01-MAR-10:09 | 703.38 | 01-MAR-16:49 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 | 11-MAR-14:00 | 499.47 | 28-MAR-21:05 |
April | 827.22 | 03-APR-09:09 | 703.38 | 21-APR-15:30 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.93 | 26-APR-13:00 | 299.51 | 21-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 527.66 | 04-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 307.50 | 29-MAY-13:00 |
June | 827.22 | 01-JUN-09:09 | 527.66 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 | 29-JUN-11:00 | 220.97 | 04-JUN-13:40 |
July | 827.22 | 03-JUL-09:09 | 527.66 | 28-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.74 | 31-JUL-13:00 | 180.28 | 09-JUL-12:00 |
August | 827.22 | 01-AUG-09:09 | 527.66 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.96 | 17-AUG-14:00 | 149.94 | 27-AUG-18:30 |
September | 827.22 | 01-SEP-09:09 | 703.38 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.25 | 29-SEP-14:00 | 194.59 | 03-SEP-07:00 |
October | 827.22 | 02-OCT-09:09 | 879.10 | 20-OCT-15:39 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.24 | 15-OCT-12:50 | 313.54 | 30-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 1007.95 | 06-NOV-16:19 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.98 | 19-NOV-12:50 | 393.71 | 23-NOV-04:00 |
December | 827.22 | 01-DEC-10:09 | 1007.95 | 01-DEC-16:10 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.14 | 17-DEC-13:00 | 392.71 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 527.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.94 | |||||
Maximum of Months | 827.22 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 190.24 | 499.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.19 | 15-JAN-10:00 | 652.70 | 06-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 27-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.84 | 01-FEB-12:00 | 703.99 | 20-FEB-15:00 |
March | 1306.65 | 01-MAR-10:09 | 1111.04 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 753.06 | 28-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 1111.04 | 21-APR-15:00 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.03 | 30-APR-10:13 | 466.55 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 907.52 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 466.50 | 20-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 907.52 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.79 | 29-JUN-11:00 | 313.16 | 04-JUN-13:43 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 12-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.27 | 23-JUL-10:53 | 257.93 | 02-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 907.52 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.93 | 17-AUG-14:00 | 230.96 | 27-AUG-18:10 |
September | 1306.65 | 01-SEP-09:09 | 1185.08 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.72 | 29-SEP-14:00 | 344.25 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1111.04 | 04-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.81 | 15-OCT-12:57 | 497.20 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 06-NOV-16:40 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.37 | 18-NOV-13:00 | 618.35 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.74 | 05-DEC-10:00 | 609.51 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 907.52 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.96 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 261.81 | 753.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1007.89 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.09 | 15-JAN-10:00 | 420.66 | 27-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 1007.89 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.07 | 01-FEB-12:00 | 427.13 | 25-FEB-03:00 |
March | 827.17 | 01-MAR-10:09 | 879.04 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 | 11-MAR-12:20 | 501.28 | 28-MAR-21:05 |
April | 827.17 | 03-APR-09:09 | 703.34 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.53 | 30-APR-10:53 | 403.60 | 16-APR-17:47 |
May | 827.17 | 01-MAY-09:09 | 703.34 | 08-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 421.77 | 20-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 574.49 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 | 29-JUN-11:00 | 289.91 | 03-JUN-17:10 |
July | 827.17 | 03-JUL-09:09 | 574.49 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.56 | 23-JUL-10:53 | 247.87 | 09-JUL-17:30 |
August | 827.17 | 01-AUG-09:09 | 703.34 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.65 | 06-AUG-11:10 | 195.97 | 27-AUG-18:10 |
September | 827.17 | 01-SEP-09:09 | 879.04 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.25 | 29-SEP-14:00 | 267.89 | 03-SEP-16:50 |
October | 827.17 | 02-OCT-09:09 | 879.04 | 05-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.57 | 15-OCT-09:00 | 318.59 | 30-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 06-NOV-16:40 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.73 | 19-NOV-12:32 | 397.00 | 23-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.85 | 25-DEC-12:00 | 395.81 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 574.49 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.97 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 245.57 | 501.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.14 | 15-JAN-10:00 | 369.94 | 27-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 27-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.47 | 01-FEB-12:00 | 373.18 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 1111.04 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.96 | 11-MAR-14:00 | 409.44 | 28-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 1111.04 | 21-APR-15:50 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.86 | 30-APR-10:50 | 248.39 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 907.52 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:10 | 240.62 | 27-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 907.52 | 09-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 | 29-JUN-11:00 | 167.92 | 07-JUN-01:00 |
July | 1306.65 | 03-JUL-09:09 | 833.48 | 11-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.28 | 23-JUL-11:00 | 130.93 | 02-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 907.52 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 | 06-AUG-12:40 | 120.89 | 21-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1185.08 | 18-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.73 | 29-SEP-14:00 | 137.78 | 04-SEP-18:00 |
October | 1306.65 | 02-OCT-09:09 | 1388.60 | 20-OCT-15:50 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.30 | 15-OCT-13:00 | 271.67 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 06-NOV-16:19 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.12 | 19-NOV-13:00 | 364.59 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:10 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.87 | 25-DEC-12:00 | 340.46 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 120.89 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 194.30 | 409.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1007.95 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.40 | 15-JAN-14:50 | 249.52 | 27-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 1007.95 | 27-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.49 | 01-FEB-12:00 | 251.53 | 25-FEB-03:00 |
March | 827.22 | 01-MAR-10:09 | 703.38 | 01-MAR-16:49 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 | 11-MAR-14:00 | 272.76 | 28-MAR-22:00 |
April | 827.22 | 03-APR-09:09 | 703.38 | 21-APR-15:39 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.70 | 26-APR-13:00 | 171.29 | 21-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 527.66 | 04-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:00 | 161.58 | 27-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 527.66 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 | 29-JUN-11:00 | 114.26 | 04-JUN-13:53 |
July | 827.22 | 03-JUL-09:09 | 527.66 | 28-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 | 31-JUL-13:00 | 96.02 | 02-JUL-19:00 |
August | 827.22 | 01-AUG-09:09 | 527.66 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.90 | 17-AUG-14:00 | 83.23 | 21-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 703.38 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.15 | 29-SEP-14:00 | 113.28 | 03-SEP-07:00 |
October | 827.22 | 02-OCT-09:09 | 879.10 | 20-OCT-15:39 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.59 | 15-OCT-13:00 | 190.13 | 30-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 1007.95 | 06-NOV-16:19 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.77 | 19-NOV-13:00 | 249.79 | 23-NOV-04:00 |
December | 827.22 | 01-DEC-10:09 | 1007.95 | 01-DEC-16:10 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.72 | 17-DEC-12:53 | 232.13 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 527.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 83.23 | |||||
Maximum of Months | 827.22 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 108.59 | 272.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1598.77 | 18-JAN-13:00 | 14180.12 | 09-JAN-07:03 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 27-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1331.16 | 01-FEB-12:10 | 11559.28 | 09-FEB-07:03 |
March | 1306.65 | 01-MAR-10:09 | 1111.04 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 11-MAR-14:00 | 11989.28 | 30-MAR-06:03 |
April | 1306.65 | 03-APR-09:09 | 1111.04 | 21-APR-15:00 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1596.42 | 26-APR-11:10 | 9142.03 | 03-APR-06:05 |
May | 1306.65 | 01-MAY-09:09 | 907.52 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 | 03-MAY-12:00 | 8122.41 | 15-MAY-06:10 |
June | 1306.65 | 01-JUN-09:09 | 907.52 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 669.18 | 29-JUN-11:10 | 6514.78 | 01-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 833.48 | 11-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3174.43 | 19-JUL-12:00 | 5722.16 | 27-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 907.52 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3176.73 | 18-AUG-12:00 | 6644.60 | 28-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 1111.04 | 05-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8682.38 | 29-SEP-11:02 | 7594.68 | 20-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 1111.04 | 04-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8842.27 | 16-OCT-11:02 | 9574.75 | 12-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 06-NOV-16:40 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.58 | 28-NOV-14:00 | 10467.53 | 30-NOV-07:03 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.49 | 19-DEC-13:00 | 13106.86 | 22-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 5722.16 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8842.27 | 14180.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1007.89 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.69 | 15-JAN-10:00 | 249.79 | 27-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 1007.89 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.78 | 01-FEB-12:00 | 251.73 | 25-FEB-03:00 |
March | 827.17 | 01-MAR-10:09 | 879.04 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 | 11-MAR-12:30 | 274.71 | 28-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 703.34 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.43 | 30-APR-10:50 | 207.53 | 16-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 703.34 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:10 | 209.08 | 20-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 574.49 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 | 29-JUN-11:00 | 143.53 | 03-JUN-17:17 |
July | 827.17 | 03-JUL-09:09 | 574.49 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.76 | 23-JUL-11:00 | 131.24 | 09-JUL-17:10 |
August | 827.17 | 01-AUG-09:09 | 703.34 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.68 | 06-AUG-12:40 | 100.32 | 26-AUG-17:20 |
September | 827.17 | 01-SEP-09:09 | 879.04 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.15 | 29-SEP-14:00 | 137.49 | 03-SEP-16:30 |
October | 827.17 | 02-OCT-09:09 | 879.04 | 05-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.54 | 15-OCT-08:52 | 192.15 | 30-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 06-NOV-16:40 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.54 | 19-NOV-12:12 | 253.42 | 23-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.34 | 25-DEC-12:00 | 233.26 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 574.49 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 100.32 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 126.54 | 274.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.02 | 15-JAN-10:00 | 570.75 | 27-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 27-FEB-16:49 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 | 01-FEB-12:00 | 593.73 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 1111.04 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.70 | 11-MAR-13:30 | 640.16 | 28-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 1111.04 | 21-APR-15:50 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 | 30-APR-10:53 | 401.23 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 907.52 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 409.45 | 20-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 907.52 | 09-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 | 29-JUN-11:00 | 270.47 | 06-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 833.48 | 11-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.59 | 23-JUL-10:50 | 214.35 | 02-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 907.52 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.96 | 06-AUG-13:10 | 194.27 | 21-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1388.60 | 18-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.70 | 29-SEP-14:00 | 224.35 | 04-SEP-18:00 |
October | 1306.65 | 02-OCT-09:09 | 1388.60 | 05-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.82 | 15-OCT-08:52 | 425.37 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 06-NOV-16:19 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.60 | 19-NOV-12:52 | 560.59 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:10 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.42 | 25-DEC-12:00 | 531.97 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.27 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 284.82 | 640.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1007.95 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 | 15-JAN-14:50 | 378.35 | 27-JAN-05:00 |
February | 805.43 | 01-FEB-08:09 | 1007.95 | 27-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.03 | 01-FEB-12:00 | 389.96 | 25-FEB-03:00 |
March | 805.43 | 01-MAR-08:09 | 703.38 | 01-MAR-16:49 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.29 | 11-MAR-14:00 | 421.58 | 28-MAR-22:00 |
April | 805.43 | 03-APR-07:10 | 703.38 | 21-APR-15:30 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.06 | 26-APR-13:00 | 265.32 | 21-APR-22:00 |
May | 805.43 | 01-MAY-07:10 | 527.66 | 04-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 256.48 | 20-MAY-18:00 |
June | 805.43 | 01-JUN-07:10 | 527.66 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 29-JUN-11:00 | 182.10 | 04-JUN-13:43 |
July | 805.43 | 03-JUL-07:10 | 527.66 | 28-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.92 | 31-JUL-13:00 | 153.42 | 04-JUL-13:43 |
August | 805.43 | 01-AUG-07:10 | 527.66 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.07 | 17-AUG-14:00 | 128.54 | 21-AUG-24:00 |
September | 805.43 | 01-SEP-07:10 | 703.38 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.13 | 29-SEP-14:00 | 180.32 | 03-SEP-07:00 |
October | 805.43 | 02-OCT-07:10 | 879.10 | 20-OCT-15:39 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.43 | 15-OCT-12:50 | 285.98 | 30-OCT-03:00 |
November | 805.43 | 01-NOV-07:10 | 1007.95 | 06-NOV-16:19 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.19 | 19-NOV-12:32 | 373.12 | 23-NOV-07:00 |
December | 805.43 | 01-DEC-08:09 | 1007.95 | 01-DEC-16:10 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.81 | 17-DEC-12:53 | 353.31 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 527.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.54 | |||||
Maximum of Months | 805.43 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 162.43 | 421.58 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.44 | 14-JAN-11:00 | 582.25 | 27-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 27-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 | 01-FEB-12:00 | 597.99 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 1111.04 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 646.52 | 28-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 1111.04 | 21-APR-15:00 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 26-APR-13:00 | 401.25 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 907.52 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 393.23 | 20-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 907.52 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 | 29-JUN-11:00 | 269.44 | 06-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 12-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.52 | 23-JUL-10:45 | 214.95 | 02-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 907.52 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.11 | 17-AUG-14:00 | 196.08 | 21-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1185.08 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.88 | 29-SEP-14:00 | 276.23 | 24-SEP-14:55 |
October | 1306.65 | 02-OCT-09:09 | 1111.04 | 04-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.21 | 15-OCT-12:46 | 451.22 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 06-NOV-16:40 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 | 18-NOV-13:00 | 581.14 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 | 05-DEC-10:00 | 546.67 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 907.52 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.08 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 215.21 | 646.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1007.89 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 | 15-JAN-10:00 | 380.45 | 27-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 1007.89 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 | 01-FEB-12:00 | 392.47 | 25-FEB-03:00 |
March | 827.17 | 01-MAR-10:09 | 879.04 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 | 11-MAR-12:20 | 427.30 | 28-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 703.34 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.27 | 30-APR-10:53 | 335.89 | 16-APR-17:47 |
May | 827.17 | 01-MAY-09:09 | 703.34 | 08-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 351.15 | 20-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 574.49 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 29-JUN-11:00 | 237.94 | 03-JUN-17:10 |
July | 827.17 | 03-JUL-09:09 | 574.49 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.24 | 23-JUL-10:50 | 201.76 | 09-JUL-17:30 |
August | 827.17 | 01-AUG-09:09 | 703.34 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.59 | 06-AUG-12:40 | 159.98 | 27-AUG-17:50 |
September | 827.17 | 01-SEP-09:09 | 879.04 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.14 | 29-SEP-14:00 | 223.45 | 03-SEP-16:40 |
October | 827.17 | 02-OCT-09:09 | 879.04 | 05-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.76 | 15-OCT-08:52 | 290.36 | 30-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 06-NOV-16:40 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.18 | 19-NOV-12:32 | 375.54 | 23-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.66 | 25-DEC-12:00 | 356.09 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 574.49 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.98 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 196.76 | 427.30 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.46 | 15-JAN-10:00 | 826.32 | 27-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.88 | 01-FEB-12:00 | 883.76 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 933.24 | 28-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.19 | 30-APR-10:53 | 565.59 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 540.78 | 27-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.12 | 29-JUN-11:00 | 375.48 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.14 | 23-JUL-11:00 | 292.35 | 02-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.31 | 17-AUG-14:00 | 271.26 | 21-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.85 | 29-SEP-13:40 | 331.13 | 04-SEP-18:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.47 | 15-OCT-09:00 | 624.20 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.52 | 19-NOV-13:00 | 855.89 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.23 | 04-DEC-10:00 | 775.91 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.26 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.47 | 933.24 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.91 | 15-JAN-10:00 | 1032.94 | 27-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.57 | 01-FEB-12:00 | 1089.45 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.44 | 11-MAR-13:00 | 1155.84 | 28-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.29 | 30-APR-11:00 | 705.42 | 21-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 678.96 | 27-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 | 29-JUN-11:00 | 478.02 | 06-JUN-21:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.89 | 23-JUL-10:53 | 370.44 | 02-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.65 | 06-AUG-12:53 | 342.87 | 21-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.89 | 29-SEP-13:50 | 408.96 | 04-SEP-18:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.70 | 15-OCT-08:52 | 767.78 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.48 | 19-NOV-12:52 | 1049.14 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.44 | 04-DEC-10:00 | 965.98 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.87 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.70 | 1155.84 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.76 | 15-JAN-10:00 | 953.43 | 27-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.63 | 01-FEB-12:00 | 997.06 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1170.28 | 28-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.73 | 30-APR-10:53 | 785.85 | 16-APR-17:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 825.30 | 07-MAY-14:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 618.12 | 04-JUN-13:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.11 | 31-JUL-13:00 | 514.19 | 09-JUL-16:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 17-AUG-14:00 | 397.06 | 27-AUG-17:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.02 | 29-SEP-13:30 | 495.74 | 04-SEP-17:45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.45 | 15-OCT-08:52 | 697.50 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.97 | 19-NOV-10:05 | 858.74 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 04-DEC-10:00 | 908.91 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.06 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.45 | 1170.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 26054.70 | 20-JAN-07:02 | 6352.64 | 12587.66 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21212.16 | 03-FEB-17:00 | 6035.01 | 7552.50 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22934.11 | 24-MAR-06:03 | 5082.11 | 10070.13 | 35187.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29280.43 | 28-APR-06:03 | 5082.11 | 10070.13 | 35187.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29781.93 | 05-MAY-06:03 | 5082.11 | 10070.13 | 35187.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31790.88 | 28-JUN-06:03 | 5082.11 | 10070.13 | 35187.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 36144.92 | 20-JUL-06:03 | 5082.11 | 10070.13 | 35187.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39619.14 | 28-AUG-06:02 | 6352.64 | 12587.66 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39304.85 | 26-SEP-06:02 | 6352.64 | 12587.66 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44934.23 | 02-OCT-05:12 | 2541.06 | 3356.58 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35378.16 | 01-NOV-06:02 | 7623.17 | 15105.19 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23670.36 | 06-DEC-07:02 | 6352.64 | 12587.66 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 21212.16 | 2541.06 | 3356.58 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44934.23 | 7623.17 | 15105.19 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5356.46 | 18-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.11 |
February | 4876.76 | 01-FEB-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.93 |
March | 6437.91 | 23-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.91 |
April | 8162.04 | 26-APR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 | 0.00 |
May | 7285.09 | 03-MAY-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.08 |
June | 7214.70 | 30-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.95 |
July | 8597.06 | 31-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.58 | 0.00 |
August | 8299.83 | 14-AUG-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 |
September | 9670.96 | 29-SEP-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.36 | 0.00 |
October | 9619.17 | 16-OCT-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.80 | 0.00 |
November | 4785.40 | 10-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.81 |
December | 4809.58 | 19-DEC-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4785.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9670.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.36 | 101.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1636.11 | 18-JAN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.27 |
February | 1435.50 | 03-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.50 |
March | 1976.37 | 23-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.28 |
April | 2493.69 | 26-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.63 |
May | 2394.23 | 03-MAY-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 |
June | 2762.26 | 30-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.53 |
July | 3342.23 | 31-JUL-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 |
August | 3233.01 | 17-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 | 0.00 |
September | 4046.43 | 29-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.56 | 0.00 |
October | 4747.49 | 16-OCT-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.74 | 0.00 |
November | 1499.29 | 10-NOV-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.03 |
December | 1615.16 | 19-DEC-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1435.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4747.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.56 | 90.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2471.93 | 18-JAN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 |
February | 2188.41 | 03-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.05 |
March | 2555.89 | 23-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.99 |
April | 2953.17 | 26-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.77 |
May | 2807.99 | 04-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.98 |
June | 3103.94 | 30-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 |
July | 3786.79 | 31-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.29 | 0.00 |
August | 3692.63 | 17-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 0.00 |
September | 4362.51 | 29-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.43 | 0.00 |
October | 4910.11 | 16-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.66 | 0.00 |
November | 2270.91 | 13-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.05 |
December | 2440.93 | 19-DEC-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2188.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4910.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.43 | 69.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14185.68 | 20-JAN-16:20 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13883.48 | 03-FEB-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14528.95 | 24-MAR-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15541.32 | 27-APR-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15603.03 | 04-MAY-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16020.29 | 30-JUN-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16710.37 | 31-JUL-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16518.37 | 18-AUG-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16907.39 | 29-SEP-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33216.51 | 02-OCT-05:12 | 2541.06 | 3356.58 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14532.18 | 01-NOV-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14163.91 | 07-DEC-16:30 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13883.48 | 2541.06 | 3356.58 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33216.51 | 6035.01 | 7552.50 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13697.79 | 19-JAN-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13556.49 | 02-FEB-16:20 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15095.01 | 24-MAR-15:40 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16747.02 | 27-APR-15:20 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16908.62 | 03-MAY-15:20 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17557.44 | 30-JUN-15:30 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18374.78 | 31-JUL-15:20 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18118.15 | 17-AUG-15:30 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18421.31 | 29-SEP-14:50 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20180.18 | 16-OCT-14:00 | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13837.48 | 01-NOV-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13700.20 | 07-DEC-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13556.49 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20180.18 | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2767.30 | 18-JAN-15:00 | 1306.65 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.75 |
February | 2397.66 | 03-FEB-15:00 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 |
March | 3053.84 | 23-MAR-15:20 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.34 |
April | 4238.69 | 26-APR-14:00 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.66 | 0.00 |
May | 4537.48 | 04-MAY-13:50 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 |
June | 4358.20 | 27-JUN-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 |
July | 5016.56 | 31-JUL-14:00 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 33.42 | 0.00 |
August | 4894.03 | 18-AUG-15:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.66 | 0.00 |
September | 5891.54 | 29-SEP-13:50 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 109.75 | 0.00 |
October | 6032.55 | 16-OCT-12:50 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 117.00 | 0.00 |
November | 2488.12 | 10-NOV-14:10 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.10 |
December | 2762.74 | 05-DEC-15:00 | 1306.65 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2397.66 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6032.55 | 1306.65 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 117.00 | 49.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3172.63 | 20-JAN-10:00 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.62 |
February | 2940.82 | 02-FEB-10:10 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.23 |
March | 4817.25 | 23-MAR-09:40 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.48 |
April | 5891.58 | 26-APR-09:20 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
May | 5155.70 | 04-MAY-09:30 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 |
June | 9065.53 | 18-JUN-08:32 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.44 |
July | 11347.66 | 04-JUL-09:02 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.33 |
August | 7542.06 | 20-AUG-09:13 | 127.17 | 80.13 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 |
September | 7458.62 | 10-SEP-09:23 | 127.17 | 80.13 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.93 |
October | 11807.23 | 15-OCT-08:43 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 138.16 | 0.00 |
November | 2659.16 | 01-NOV-09:30 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.96 |
December | 3139.73 | 05-DEC-09:50 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2659.16 | 127.17 | 80.13 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11807.23 | 827.22 | 480.79 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 138.16 | 87.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15326.52 | 22-JAN-13:13 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.51 |
February | 10608.25 | 20-FEB-13:43 | 200.88 | 126.57 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.50 |
March | 8886.88 | 23-MAR-13:30 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.13 |
April | 7827.07 | 26-APR-13:10 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 24.87 | 0.00 |
May | 5951.46 | 04-MAY-12:40 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.44 |
June | 5388.38 | 30-JUN-13:10 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.89 |
July | 7404.26 | 31-JUL-13:00 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 44.61 | 0.00 |
August | 8429.49 | 30-AUG-13:00 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
September | 12216.18 | 29-SEP-13:20 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 106.39 | 0.00 |
October | 15888.34 | 29-OCT-12:32 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.58 |
November | 16250.14 | 19-NOV-13:02 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.94 |
December | 12128.53 | 17-DEC-12:53 | 200.88 | 126.57 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5388.38 | 200.88 | 126.57 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16250.14 | 1306.65 | 759.45 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 106.39 | 515.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4698.77 | 18-JAN-15:00 | 827.17 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 |
February | 4951.15 | 22-FEB-15:50 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.76 |
March | 6576.13 | 23-MAR-15:50 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.25 |
April | 11335.52 | 30-APR-16:33 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.26 |
May | 7200.53 | 21-MAY-16:53 | 127.16 | 80.12 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.92 |
June | 12087.93 | 25-JUN-15:53 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.33 |
July | 11686.00 | 23-JUL-15:13 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.23 |
August | 13728.46 | 06-AUG-16:22 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.88 |
September | 11797.47 | 04-SEP-16:03 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.34 |
October | 13107.74 | 15-OCT-15:22 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 74.45 | 0.00 |
November | 4777.92 | 10-NOV-14:50 | 827.17 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.00 |
December | 4694.44 | 19-DEC-15:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4694.44 | 127.16 | 80.12 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13728.46 | 827.17 | 480.76 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 74.45 | 249.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2160.04 | 18-JAN-13:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 | 0.00 |
February | 1767.34 | 01-FEB-12:10 | 687.71 | 759.45 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 10.05 | 0.00 |
March | 1864.71 | 23-MAR-15:20 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.58 |
April | 2757.38 | 26-APR-14:00 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 | 0.00 |
May | 3204.37 | 04-MAY-14:10 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.15 |
June | 3154.70 | 29-JUN-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
July | 3771.95 | 19-JUL-15:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 | 0.00 |
August | 3736.99 | 18-AUG-15:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.80 | 0.00 |
September | 4446.77 | 29-SEP-13:10 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 57.05 | 0.00 |
October | 4688.28 | 16-OCT-12:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 68.73 | 0.00 |
November | 2134.81 | 19-NOV-12:32 | 267.84 | 168.76 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 60.11 | 0.00 |
December | 2126.84 | 19-DEC-13:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1767.34 | 267.84 | 168.76 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4688.28 | 1306.65 | 759.45 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 68.73 | 10.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2911.86 | 20-JAN-09:50 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 |
February | 2552.44 | 01-FEB-10:10 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
March | 3839.02 | 23-MAR-09:30 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.97 |
April | 4679.26 | 26-APR-09:20 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 |
May | 4207.40 | 04-MAY-09:30 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.36 |
June | 4689.57 | 30-JUN-09:20 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 |
July | 8211.26 | 04-JUL-09:02 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.82 |
August | 5466.15 | 14-AUG-09:10 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 | 0.00 |
September | 5349.24 | 10-SEP-09:13 | 127.17 | 80.13 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.77 |
October | 9556.25 | 15-OCT-08:32 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 64.59 | 0.00 |
November | 2677.66 | 01-NOV-09:30 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.53 |
December | 2857.35 | 05-DEC-09:50 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2552.44 | 127.17 | 80.13 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9556.25 | 827.22 | 480.79 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 64.59 | 43.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12778.95 | 22-JAN-13:23 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.14 |
February | 8119.51 | 01-FEB-12:10 | 687.71 | 759.45 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1331.16 | 0.00 |
March | 6719.80 | 23-MAR-14:00 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.71 |
April | 6592.67 | 26-APR-12:00 | 687.71 | 759.45 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1593.31 | 0.00 |
May | 4204.98 | 04-MAY-12:30 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.55 |
June | 3657.32 | 30-JUN-12:30 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.06 |
July | 8347.39 | 31-JUL-12:00 | 687.71 | 759.45 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3163.99 | 0.00 |
August | 8386.24 | 18-AUG-12:00 | 687.71 | 759.45 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3176.73 | 0.00 |
September | 12315.26 | 29-SEP-12:00 | 687.71 | 759.45 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7234.17 | 0.00 |
October | 13062.28 | 01-OCT-12:52 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.47 |
November | 13149.45 | 19-NOV-12:32 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.98 |
December | 12765.74 | 25-DEC-13:02 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3657.32 | 267.84 | 168.76 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13149.45 | 1306.65 | 759.45 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 7234.17 | 146.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3586.58 | 18-JAN-15:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 |
February | 3915.18 | 22-FEB-16:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.26 |
March | 4831.78 | 23-MAR-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 |
April | 5463.10 | 26-APR-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 |
May | 5075.15 | 03-MAY-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 |
June | 8650.73 | 25-JUN-16:42 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.09 |
July | 11017.15 | 23-JUL-16:22 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.55 |
August | 9357.10 | 20-AUG-17:03 | 0.00 | 106.83 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.20 |
September | 8906.45 | 04-SEP-16:03 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.71 |
October | 10753.41 | 15-OCT-15:52 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 | 0.00 |
November | 3940.98 | 07-NOV-15:40 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.94 |
December | 3846.35 | 19-DEC-15:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3586.58 | 0.00 | 106.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11017.15 | 805.38 | 480.76 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 | 84.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2732.19 | 18-JAN-14:10 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 | 0.00 |
February | 2465.79 | 03-FEB-15:00 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 |
March | 2884.78 | 23-MAR-15:20 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.75 |
April | 3850.74 | 26-APR-14:00 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 | 0.00 |
May | 4178.11 | 04-MAY-14:10 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.64 |
June | 4018.64 | 27-JUN-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.70 |
July | 4555.68 | 31-JUL-13:10 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 35.83 | 0.00 |
August | 4490.21 | 18-AUG-15:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 0.00 |
September | 5368.80 | 29-SEP-13:10 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 89.12 | 0.00 |
October | 5546.39 | 16-OCT-12:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 107.35 | 0.00 |
November | 2513.03 | 01-NOV-14:00 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.01 |
December | 2751.29 | 05-DEC-15:00 | 1306.65 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2465.79 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5546.39 | 1306.65 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 107.35 | 35.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3743.04 | 20-JAN-09:30 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.79 |
February | 3441.80 | 02-FEB-09:40 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.01 |
March | 5153.48 | 23-MAR-09:00 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6175.48 | 30-APR-07:53 | 127.17 | 80.13 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6112.94 | 28-MAY-08:23 | 127.17 | 80.13 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.40 |
June | 7546.95 | 18-JUN-08:63 | 127.17 | 80.13 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.63 |
July | 11239.93 | 23-JUL-09:43 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.82 |
August | 7541.82 | 20-AUG-09:33 | 127.17 | 80.13 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.40 |
September | 7325.07 | 10-SEP-09:43 | 127.17 | 80.13 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.12 |
October | 11684.19 | 15-OCT-08:23 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 80.06 | 0.00 |
November | 3353.22 | 13-NOV-09:20 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 |
December | 3613.83 | 05-DEC-09:30 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3353.22 | 127.17 | 80.13 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11684.19 | 805.43 | 480.79 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 80.06 | 120.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14245.32 | 22-JAN-13:23 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.65 |
February | 11617.17 | 20-FEB-13:13 | 200.88 | 126.57 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.83 |
March | 8611.36 | 19-MAR-12:33 | 200.88 | 126.57 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.99 |
April | 7295.93 | 26-APR-13:00 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 0.00 |
May | 5544.76 | 04-MAY-12:30 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 |
June | 4933.59 | 30-JUN-13:10 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.84 |
July | 6875.70 | 31-JUL-12:40 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 33.71 | 0.00 |
August | 7959.73 | 30-AUG-12:50 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 |
September | 11240.64 | 29-SEP-13:10 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 87.08 | 0.00 |
October | 14825.30 | 15-OCT-11:02 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 59.31 | 0.00 |
November | 14851.68 | 19-NOV-13:02 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.56 |
December | 14043.96 | 25-DEC-13:02 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4933.59 | 200.88 | 126.57 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14851.68 | 1306.65 | 759.45 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 87.08 | 428.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4627.12 | 18-JAN-15:00 | 827.17 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 |
February | 4934.24 | 22-FEB-15:40 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.86 |
March | 6362.04 | 23-MAR-15:50 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.75 |
April | 8354.42 | 02-APR-15:43 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.80 |
May | 6721.07 | 21-MAY-16:53 | 127.16 | 80.12 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.05 |
June | 11986.73 | 25-JUN-16:12 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.84 |
July | 12720.16 | 23-JUL-16:22 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.25 |
August | 12203.62 | 06-AUG-15:53 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.50 |
September | 11581.41 | 04-SEP-15:32 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.25 |
October | 11588.63 | 15-OCT-15:42 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 51.71 | 0.00 |
November | 4731.62 | 10-NOV-14:50 | 827.17 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.47 |
December | 4636.79 | 19-DEC-15:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4627.12 | 127.16 | 80.12 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12720.16 | 827.17 | 480.76 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 51.71 | 207.05 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.116757E+12 | 107796.85 | 18-JAN-13:00 | 0.116646E+11 | 28822.80 | 09-JAN-07:10 |
February | 0.102013E+12 | 104053.82 | 01-FEB-11:00 | 0.101157E+11 | 15240.47 | 09-FEB-07:10 |
March | 0.117421E+12 | 112446.99 | 23-MAR-15:09 | 0.117450E+11 | 22519.35 | 30-MAR-06:19 |
April | 0.112896E+12 | 120533.86 | 26-APR-12:00 | 0.105915E+11 | 14719.98 | 01-APR-06:10 |
May | 0.118499E+12 | 109930.88 | 03-MAY-12:00 | 0.109882E+11 | 9869.24 | 01-MAY-11:00 |
June | 0.126084E+12 | 123776.33 | 29-JUN-12:00 | 0.106482E+11 | 9829.20 | 08-JUN-11:09 |
July | 0.136731E+12 | 146023.08 | 31-JUL-15:39 | 0.105137E+11 | 9793.98 | 03-JUL-11:20 |
August | 0.150052E+12 | 144711.48 | 18-AUG-15:50 | 0.109601E+11 | 9790.79 | 31-AUG-11:20 |
September | 0.127562E+12 | 147439.97 | 29-SEP-15:00 | 0.103423E+11 | 9826.96 | 29-SEP-11:20 |
October | 0.134674E+12 | 150012.36 | 16-OCT-10:00 | 0.107802E+11 | 9860.06 | 31-OCT-11:30 |
November | 0.114215E+12 | 107662.22 | 10-NOV-16:49 | 0.106423E+11 | 11013.72 | 24-NOV-07:30 |
December | 0.115309E+12 | 114142.02 | 05-DEC-16:40 | 0.111436E+11 | 17699.56 | 15-DEC-07:10 |
Annual Sum or Average | 0.147221E+13 | 0.130135E+12 | ||||
Minimum of Months | 0.102013E+12 | 104053.82 | 0.101157E+11 | 9790.79 | ||
Maximum of Months | 0.150052E+12 | 150012.36 | 0.117450E+11 | 28822.80 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.311823E+11 | 0.113268E+11 | 0.593559E+11 | 0.143931E+10 | 0.562654E+10 | 12379742.02 | 0.190413E+10 | 0.590944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277869E+11 | 0.958524E+10 | 0.537310E+11 | 0.130185E+10 | 0.499354E+10 | 11196021.66 | 0.108811E+10 | 0.351546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327001E+11 | 0.967626E+10 | 0.617796E+11 | 0.150713E+10 | 0.566876E+10 | 12675672.10 | 0.175429E+10 | 0.432227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.289246E+11 | 0.844585E+10 | 0.572952E+11 | 0.138496E+10 | 0.672716E+10 | 11960507.72 | 0.443950E+09 | 0.966215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.310285E+11 | 0.797292E+10 | 0.605677E+11 | 0.147222E+10 | 0.693359E+10 | 12527707.06 | 0.307195E+09 | 0.102039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.308229E+11 | 0.736142E+10 | 0.594895E+11 | 0.144950E+10 | 0.827315E+10 | 12231776.97 | 0.104534E+09 | 0.185712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.288910E+11 | 0.772495E+10 | 0.583622E+11 | 0.140732E+10 | 0.984081E+10 | 12256437.81 | 4118171.51 | 0.304882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.322349E+11 | 0.836100E+10 | 0.617796E+11 | 0.150672E+10 | 0.112158E+11 | 12675672.10 | 6026485.66 | 0.349350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.291329E+11 | 0.897196E+10 | 0.572729E+11 | 0.138482E+10 | 0.878910E+10 | 11960507.72 | 29820477.79 | 0.219687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.306838E+11 | 0.102230E+11 | 0.593671E+11 | 0.143877E+10 | 0.874211E+10 | 12379742.02 | 0.118910E+09 | 0.240882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.307296E+11 | 0.107256E+11 | 0.580818E+11 | 0.141276E+10 | 0.617764E+10 | 12059151.09 | 0.417737E+09 | 0.665747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303154E+11 | 0.115537E+11 | 0.583511E+11 | 0.140897E+10 | 0.578856E+10 | 12256437.81 | 0.103478E+10 | 0.684401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364433E+12 | 0.111929E+12 | 0.705434E+12 | 0.171143E+11 | 0.887767E+11 | 0.146559E+09 | 0.721360E+10 | 0.177166E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.277869E+11 | 0.736142E+10 | 0.537310E+11 | 0.130185E+10 | 0.499354E+10 | 11196021.66 | 4118171.51 | 0.351546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.327001E+11 | 0.115537E+11 | 0.617796E+11 | 0.150713E+10 | 0.112158E+11 | 12675672.10 | 0.190413E+10 | 0.349350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.581026E+09 | 0.00 | 0.110836E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 71960106.69 | 0.00 | 0.100438E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.340894E+09 | 0.00 | 0.114041E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 9150460.00 | 0.00 | 0.105824E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.109882E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.106482E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.105137E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.109601E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.103423E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 285777.01 | 0.00 | 0.107799E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 10936039.09 | 0.00 | 0.106313E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.256904E+09 | 0.00 | 0.108867E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.127116E+10 | 0.00 | 0.128864E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.100438E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.581026E+09 | 0.00 | 0.114041E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 38257.79 | 02-JAN-16:49 | 8596.48 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 1240.17 | 02-JAN-16:00 | 10871.98 | 18-JAN-15:20 | 6.85 | 02-JAN-17:10 | 59513.74 | 02-JAN-07:10 |
February | 38257.79 | 27-FEB-16:00 | 8596.48 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 1237.82 | 27-FEB-16:00 | 10214.09 | 03-FEB-14:00 | 6.85 | 01-FEB-06:10 | 31512.20 | 27-FEB-07:10 |
March | 33684.48 | 16-MAR-07:10 | 8596.48 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 1233.23 | 16-MAR-07:19 | 12094.60 | 23-MAR-15:20 | 6.85 | 01-MAR-06:10 | 47889.65 | 30-MAR-06:10 |
April | 33157.38 | 21-APR-15:00 | 8596.48 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 1229.55 | 05-APR-07:19 | 13638.63 | 26-APR-14:30 | 6.85 | 01-APR-05:10 | 22969.06 | 01-APR-06:10 |
May | 31795.58 | 09-MAY-07:10 | 8596.48 | 01-MAY-18:30 | 45864.70 | 01-MAY-07:10 | 1229.55 | 09-MAY-07:19 | 12284.56 | 03-MAY-15:20 | 6.85 | 01-MAY-05:10 | 13579.19 | 15-MAY-06:10 |
June | 31409.05 | 09-JUN-07:10 | 8596.48 | 01-JUN-18:49 | 45864.70 | 01-JUN-07:10 | 1228.79 | 09-JUN-07:19 | 13486.80 | 30-JUN-15:00 | 6.85 | 01-JUN-05:10 | 4845.02 | 01-JUN-06:19 |
July | 30972.31 | 12-JUL-07:10 | 8596.48 | 01-JUL-18:00 | 45864.70 | 03-JUL-07:10 | 1227.94 | 12-JUL-07:19 | 16986.55 | 31-JUL-15:09 | 6.85 | 01-JUL-05:10 | 891.98 | 17-JUL-06:40 |
August | 31795.58 | 21-AUG-07:10 | 8596.48 | 01-AUG-18:49 | 45864.70 | 01-AUG-07:10 | 1229.55 | 21-AUG-07:19 | 16893.52 | 18-AUG-15:09 | 6.85 | 01-AUG-05:10 | 1744.49 | 28-AUG-06:00 |
September | 34848.25 | 18-SEP-07:10 | 8596.48 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 1235.50 | 21-SEP-07:40 | 20307.78 | 29-SEP-15:00 | 6.85 | 01-SEP-05:10 | 4922.68 | 20-SEP-06:19 |
October | 34903.75 | 23-OCT-15:00 | 8596.48 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 1235.61 | 24-OCT-07:19 | 20268.50 | 16-OCT-15:00 | 6.85 | 01-OCT-05:10 | 10641.88 | 30-OCT-06:10 |
November | 38257.79 | 06-NOV-16:40 | 8596.48 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 1240.17 | 06-NOV-16:49 | 10275.37 | 10-NOV-14:39 | 6.85 | 01-NOV-05:10 | 17727.66 | 24-NOV-07:10 |
December | 38257.79 | 01-DEC-16:19 | 8596.48 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 1240.17 | 01-DEC-16:30 | 10404.37 | 19-DEC-15:39 | 6.85 | 13-DEC-17:10 | 32040.54 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 30972.31 | 8596.48 | 45864.70 | 1227.94 | 10214.09 | 6.85 | 891.98 | |||||||
Maximum of Months | 38257.79 | 8596.48 | 45864.70 | 1240.17 | 20307.78 | 6.85 | 59513.74 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 27121.99 | 18-JAN-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23897.52 | 01-FEB-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26993.88 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34226.73 | 26-APR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25067.00 | 03-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39136.25 | 29-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 56095.55 | 31-JUL-15:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 55102.60 | 18-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 61500.99 | 29-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 64935.39 | 16-OCT-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25665.45 | 28-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26962.38 | 05-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 23897.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 64935.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 107796.85 | 18-JAN-13:00 | 30098.83 | 42402.18 | 0.00 | 1224.43 | 7469.53 | 6.85 | 0.00 | 26595.02 | 0.00 |
February | 104053.82 | 01-FEB-11:00 | 30098.83 | 41577.77 | 0.00 | 1224.00 | 7248.85 | 6.85 | 0.00 | 23897.52 | 0.00 |
March | 112446.99 | 23-MAR-15:09 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 12064.18 | 6.85 | 0.00 | 26980.45 | 0.00 |
April | 120533.86 | 26-APR-12:00 | 30098.83 | 42402.18 | 0.00 | 1224.43 | 12574.83 | 6.85 | 0.00 | 34226.73 | 0.00 |
May | 109930.88 | 03-MAY-12:00 | 30098.83 | 42402.18 | 0.00 | 1224.43 | 11131.58 | 6.85 | 0.00 | 25067.00 | 0.00 |
June | 123776.33 | 29-JUN-12:00 | 30098.83 | 42402.18 | 0.00 | 1224.43 | 10907.79 | 6.85 | 0.00 | 39136.25 | 0.00 |
July | 146023.08 | 31-JUL-15:39 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 16525.18 | 6.85 | 0.00 | 56095.55 | 0.00 |
August | 144711.48 | 18-AUG-15:50 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 16206.53 | 6.85 | 0.00 | 55102.60 | 0.00 |
September | 147439.97 | 29-SEP-15:00 | 30461.55 | 42072.41 | 0.00 | 1224.53 | 20307.78 | 6.85 | 0.00 | 53366.84 | 0.00 |
October | 150012.36 | 16-OCT-10:00 | 30098.83 | 41577.77 | 0.00 | 1224.00 | 12169.52 | 6.85 | 0.00 | 64935.39 | 0.00 |
November | 107662.22 | 10-NOV-16:49 | 38257.79 | 42072.41 | 8596.48 | 1240.17 | 6627.61 | 6.85 | 0.00 | 10860.89 | 0.00 |
December | 114142.02 | 05-DEC-16:40 | 38257.79 | 42072.41 | 8596.48 | 1240.17 | 7639.09 | 6.85 | 0.00 | 16329.22 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 104053.82 | 30098.83 | 41577.77 | 0.00 | 1224.00 | 6627.61 | 6.85 | 0.00 | 10860.89 | 0.00 | |
Maximum of Months | 150012.36 | 38257.79 | 42402.18 | 8596.48 | 1240.17 | 20307.78 | 6.85 | 0.00 | 64935.39 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 21111.60 | 03-JAN-07:10 | 0.00 | 9950.97 | 25-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 6306.55 | 09-FEB-07:10 | 0.00 | 9958.68 | 14-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 13589.29 | 30-MAR-06:19 | 0.00 | 9948.68 | 06-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 5969.29 | 01-APR-06:10 | 0.00 | 9916.77 | 05-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 9869.24 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9829.20 | 08-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9793.98 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9790.79 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9826.96 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 476.30 | 12-OCT-06:10 | 0.00 | 9860.06 | 31-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 2935.17 | 24-NOV-07:10 | 0.00 | 9902.47 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 10231.91 | 12-DEC-21:00 | 0.00 | 9934.39 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9790.79 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 21111.60 | 0.00 | 9958.68 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.39 | 0.33 | 27.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.56 | 1.17 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.66 | 3.50 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.59 | 2.17 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.59 | 0.50 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.74 | 1.00 | 27.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.83 | 27.62 | 8.83 | 27.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.74 | 3.50 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.61 | 1.17 | 27.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.42 | 0.83 | 27.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.36 | 1.00 | 27.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.86 | 6.17 | 27.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.65 | 3.00 | 27.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.50 | 2.83 | 27.50 |
Annual Sum or Average | 0.00 | 0.00 | 15.33 | 27.66 | 15.33 | 27.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.86 | 6.17 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.33 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.58 | 2.17 | 27.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.52 | 2.33 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.70 | 1.83 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.84 | 4.83 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.87 | 2.83 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.64 | 2.00 | 27.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.03 | 1.50 | 28.06 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 21.50 | 27.75 | 17.67 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.03 | 4.83 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.42 | 1.33 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.38 | 0.67 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.52 | 0.83 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.83 | 27.44 | 2.83 | 27.44 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.52 | 1.33 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 19.95 | 6.17 | 19.95 | 1.17 | 20.60 | 1.17 | 21.15 |
February | 1.67 | 20.27 | 1.67 | 20.27 | 0.50 | 21.20 | 0.50 | 21.91 |
March | 7.50 | 19.72 | 7.50 | 19.72 | 0.17 | 19.81 | 0.17 | 19.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 25.20 | 3.17 | 25.20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 26.28 | 10.67 | 26.28 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.60 | 2.33 | 27.60 |
December | 2.17 | 20.20 | 2.17 | 20.20 | 3.83 | 23.61 | 3.83 | 24.84 |
Annual Sum or Average | 17.50 | 19.91 | 17.50 | 19.91 | 21.83 | 22.47 | 21.83 | 23.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.50 | 20.27 | 7.50 | 20.27 | 10.67 | 27.60 | 10.67 | 27.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.36 | 0.33 | 27.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.37 | 0.67 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.56 | 2.50 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.54 | 2.00 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.42 | 0.83 | 27.42 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.74 | 1.00 | 27.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.17 | 27.53 | 7.50 | 27.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.74 | 2.50 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.46 | 1.00 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.33 | 0.33 | 27.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.61 | 1.33 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.66 | 3.67 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.62 | 2.50 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.49 | 1.17 | 27.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.76 | 1.00 | 27.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.17 | 27.60 | 11.17 | 27.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.76 | 3.67 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.54 | 2.67 | 27.54 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.46 | 2.17 | 27.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.50 | 27.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.36 | 1.00 | 27.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.31 | 8.33 | 27.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.64 | 4.33 | 27.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.56 | 5.00 | 27.56 |
Annual Sum or Average | 0.00 | 0.00 | 24.00 | 27.46 | 24.00 | 27.46 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.64 | 8.33 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.54 | 1.83 | 27.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.49 | 1.67 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.61 | 1.67 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.74 | 4.83 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.77 | 2.33 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.61 | 2.17 | 27.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.91 | 1.67 | 27.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 19.33 | 27.68 | 16.50 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.91 | 4.83 | 27.91 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 117.67 | 23.88 | 161.67 | 24.34 | 7.67 | 24.33 |
February | 49.83 | 23.87 | 157.00 | 24.44 | 0.00 | 24.44 |
March | 33.17 | 23.86 | 230.17 | 24.44 | 0.00 | 24.44 |
April | 12.33 | 23.75 | 335.17 | 24.43 | 0.00 | 24.43 |
May | 0.67 | 23.73 | 359.33 | 24.52 | 0.00 | 24.52 |
June | 0.00 | 0.00 | 455.67 | 24.39 | 0.00 | 24.39 |
July | 0.00 | 0.00 | 497.00 | 24.41 | 0.00 | 24.41 |
August | 0.00 | 0.00 | 514.00 | 24.36 | 0.00 | 24.36 |
September | 0.00 | 0.00 | 448.33 | 24.43 | 0.00 | 24.43 |
October | 1.50 | 24.00 | 319.67 | 24.60 | 0.00 | 24.60 |
November | 55.67 | 24.03 | 239.00 | 24.52 | 0.00 | 24.52 |
December | 110.83 | 23.99 | 126.83 | 24.41 | 0.00 | 24.41 |
Annual Sum or Average | 381.67 | 23.93 | 3843.83 | 24.44 | 7.67 | 24.44 |
Minimum of Months | 0.00 | 0.00 | 126.83 | 24.34 | 0.00 | 24.33 |
Maximum of Months | 117.67 | 24.03 | 514.00 | 24.60 | 7.67 | 24.60 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 312.50 | 23.25 | 32.17 | 23.34 | 0.00 | 23.34 |
February | 278.67 | 23.30 | 22.67 | 23.37 | 0.00 | 23.37 |
March | 288.33 | 23.35 | 59.83 | 23.49 | 0.00 | 23.49 |
April | 130.50 | 23.34 | 163.00 | 23.84 | 0.00 | 23.84 |
May | 111.33 | 23.44 | 175.33 | 23.96 | 0.00 | 23.96 |
June | 23.50 | 23.43 | 339.33 | 24.20 | 0.00 | 24.20 |
July | 0.00 | 0.00 | 456.17 | 24.22 | 0.00 | 24.22 |
August | 0.00 | 0.00 | 498.83 | 24.17 | 0.00 | 24.17 |
September | 11.33 | 23.44 | 358.00 | 24.21 | 0.00 | 24.21 |
October | 92.00 | 23.64 | 221.17 | 24.14 | 0.00 | 24.14 |
November | 223.83 | 23.54 | 86.83 | 23.80 | 0.00 | 23.80 |
December | 355.83 | 23.46 | 21.50 | 23.50 | 0.00 | 23.50 |
Annual Sum or Average | 1827.83 | 23.39 | 2434.83 | 23.88 | 0.00 | 23.88 |
Minimum of Months | 0.00 | 0.00 | 21.50 | 23.34 | 0.00 | 23.34 |
Maximum of Months | 355.83 | 23.64 | 498.83 | 24.22 | 0.00 | 24.22 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 405.33 | 22.65 | 19.67 | 22.68 | 3.83 | 22.66 |
February | 361.67 | 22.76 | 14.50 | 22.81 | 0.00 | 22.81 |
March | 379.83 | 22.82 | 40.00 | 22.94 | 0.17 | 22.94 |
April | 218.00 | 23.02 | 120.50 | 23.39 | 0.00 | 23.39 |
May | 196.17 | 23.12 | 128.17 | 23.53 | 0.00 | 23.53 |
June | 82.83 | 23.28 | 275.00 | 23.96 | 0.00 | 23.96 |
July | 19.50 | 23.31 | 398.33 | 24.13 | 0.00 | 24.13 |
August | 17.67 | 23.26 | 424.50 | 24.09 | 0.00 | 24.09 |
September | 86.00 | 23.25 | 263.33 | 23.92 | 0.00 | 23.92 |
October | 198.33 | 23.36 | 171.50 | 23.74 | 0.00 | 23.74 |
November | 341.00 | 23.04 | 36.67 | 23.15 | 0.00 | 23.15 |
December | 432.67 | 22.83 | 9.83 | 22.84 | 1.83 | 22.83 |
Annual Sum or Average | 2739.00 | 22.93 | 1902.00 | 23.42 | 5.83 | 23.42 |
Minimum of Months | 17.67 | 22.65 | 9.83 | 22.68 | 0.00 | 22.66 |
Maximum of Months | 432.67 | 23.36 | 424.50 | 24.13 | 3.83 | 24.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.33 | 21.78 | 78.50 | 21.58 | 74.50 | 21.41 |
February | 424.17 | 21.92 | 36.67 | 21.81 | 34.00 | 21.70 |
March | 453.17 | 22.00 | 58.17 | 21.97 | 34.50 | 21.86 |
April | 314.67 | 22.49 | 82.67 | 22.76 | 5.33 | 22.73 |
May | 279.17 | 22.69 | 102.50 | 23.07 | 0.33 | 23.07 |
June | 149.67 | 23.05 | 241.00 | 23.69 | 0.00 | 23.69 |
July | 70.83 | 23.11 | 350.00 | 23.98 | 0.00 | 23.98 |
August | 114.00 | 23.10 | 331.67 | 23.83 | 0.17 | 23.83 |
September | 206.50 | 22.93 | 201.33 | 23.49 | 0.00 | 23.49 |
October | 274.33 | 22.79 | 127.00 | 23.23 | 0.83 | 23.22 |
November | 434.50 | 22.25 | 33.17 | 22.16 | 27.50 | 22.05 |
December | 486.50 | 21.91 | 61.00 | 21.72 | 61.00 | 21.57 |
Annual Sum or Average | 3673.83 | 22.28 | 1703.67 | 22.69 | 238.17 | 22.58 |
Minimum of Months | 70.83 | 21.78 | 33.17 | 21.58 | 0.00 | 21.41 |
Maximum of Months | 486.50 | 23.11 | 350.00 | 23.98 | 74.50 | 23.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 433.00 | 22.15 | 61.83 | 22.07 | 40.33 | 21.92 |
February | 365.83 | 22.01 | 49.33 | 22.07 | 19.83 | 21.98 |
March | 359.83 | 21.98 | 90.33 | 22.24 | 21.17 | 22.14 |
April | 214.50 | 22.39 | 210.17 | 23.33 | 3.00 | 23.32 |
May | 223.00 | 22.61 | 197.00 | 23.44 | 0.00 | 23.44 |
June | 147.50 | 23.04 | 279.67 | 23.83 | 5.50 | 23.87 |
July | 87.50 | 23.86 | 381.67 | 24.27 | 19.67 | 24.38 |
August | 102.50 | 23.56 | 375.67 | 24.10 | 15.67 | 24.18 |
September | 175.67 | 22.87 | 264.17 | 23.67 | 3.17 | 23.69 |
October | 203.33 | 22.76 | 177.33 | 23.48 | 2.83 | 23.49 |
November | 362.00 | 22.42 | 42.50 | 22.48 | 13.50 | 22.40 |
December | 468.00 | 22.32 | 37.00 | 22.19 | 32.33 | 22.05 |
Annual Sum or Average | 3142.67 | 22.44 | 2166.67 | 23.09 | 177.00 | 23.05 |
Minimum of Months | 87.50 | 21.98 | 37.00 | 22.07 | 0.00 | 21.92 |
Maximum of Months | 468.00 | 23.86 | 381.67 | 24.27 | 40.33 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 275.83 | 22.17 | 169.33 | 22.74 | 33.83 | 22.60 |
February | 277.67 | 21.99 | 121.33 | 22.57 | 19.17 | 22.47 |
March | 339.83 | 22.08 | 140.67 | 22.50 | 28.17 | 22.39 |
April | 238.17 | 22.42 | 184.33 | 23.22 | 4.33 | 23.19 |
May | 268.33 | 22.56 | 138.33 | 23.11 | 2.17 | 23.10 |
June | 179.67 | 22.93 | 226.00 | 23.58 | 0.00 | 23.58 |
July | 103.50 | 23.15 | 329.00 | 23.96 | 2.00 | 23.97 |
August | 104.83 | 23.19 | 348.83 | 23.95 | 4.83 | 23.98 |
September | 148.50 | 23.12 | 281.50 | 23.91 | 9.33 | 23.97 |
October | 180.50 | 23.39 | 262.83 | 24.06 | 24.67 | 24.22 |
November | 245.83 | 22.50 | 182.33 | 23.26 | 15.83 | 23.22 |
December | 268.50 | 22.29 | 174.00 | 22.92 | 30.17 | 22.76 |
Annual Sum or Average | 2631.17 | 22.51 | 2558.50 | 23.31 | 174.50 | 23.28 |
Minimum of Months | 103.50 | 21.99 | 121.33 | 22.50 | 0.00 | 22.39 |
Maximum of Months | 339.83 | 23.39 | 348.83 | 24.06 | 33.83 | 24.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 418.67 | 21.72 | 108.00 | 21.69 | 69.50 | 21.52 |
February | 368.50 | 21.73 | 81.00 | 21.89 | 33.00 | 21.78 |
March | 407.17 | 21.83 | 108.33 | 22.07 | 33.83 | 21.97 |
April | 282.50 | 22.44 | 159.33 | 23.11 | 13.33 | 23.15 |
May | 275.83 | 22.60 | 174.83 | 23.29 | 9.50 | 23.34 |
June | 169.67 | 23.02 | 271.17 | 23.76 | 10.67 | 23.83 |
July | 110.17 | 23.77 | 355.00 | 24.19 | 26.33 | 24.34 |
August | 117.17 | 23.34 | 355.33 | 23.98 | 16.50 | 24.07 |
September | 186.67 | 22.90 | 236.00 | 23.67 | 9.17 | 23.74 |
October | 251.83 | 22.71 | 183.67 | 23.39 | 8.83 | 23.45 |
November | 369.67 | 22.02 | 97.83 | 22.25 | 28.67 | 22.14 |
December | 422.17 | 21.80 | 79.00 | 21.71 | 59.83 | 21.55 |
Annual Sum or Average | 3380.00 | 22.24 | 2209.50 | 22.88 | 319.17 | 22.83 |
Minimum of Months | 110.17 | 21.72 | 79.00 | 21.69 | 8.83 | 21.52 |
Maximum of Months | 422.17 | 23.77 | 355.33 | 24.19 | 69.50 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 474.67 | 22.17 | 20.17 | 22.10 | 19.67 | 22.04 |
February | 451.00 | 22.20 | 2.50 | 22.19 | 2.50 | 22.18 |
March | 494.83 | 22.24 | 11.33 | 22.23 | 6.33 | 22.20 |
April | 388.50 | 22.76 | 21.17 | 22.82 | 0.50 | 22.82 |
May | 328.50 | 23.01 | 32.50 | 23.11 | 0.00 | 23.11 |
June | 176.17 | 23.22 | 168.00 | 23.64 | 0.00 | 23.64 |
July | 47.50 | 23.27 | 338.83 | 24.02 | 0.00 | 24.02 |
August | 82.50 | 23.19 | 318.67 | 23.88 | 0.00 | 23.88 |
September | 192.50 | 23.17 | 167.50 | 23.58 | 0.00 | 23.58 |
October | 267.33 | 23.20 | 111.50 | 23.47 | 0.00 | 23.47 |
November | 446.67 | 22.71 | 9.67 | 22.73 | 1.50 | 22.73 |
December | 492.50 | 22.29 | 4.17 | 22.28 | 4.17 | 22.27 |
Annual Sum or Average | 3842.67 | 22.60 | 1206.00 | 22.93 | 34.67 | 22.91 |
Minimum of Months | 47.50 | 22.17 | 2.50 | 22.10 | 0.00 | 22.04 |
Maximum of Months | 494.83 | 23.27 | 338.83 | 24.02 | 19.67 | 24.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 404.50 | 22.74 | 34.67 | 22.79 | 6.33 | 22.76 |
February | 370.33 | 22.51 | 13.83 | 22.59 | 0.00 | 22.59 |
March | 372.67 | 22.49 | 56.00 | 22.72 | 2.83 | 22.71 |
April | 205.50 | 22.86 | 181.33 | 23.58 | 0.00 | 23.58 |
May | 205.83 | 23.03 | 179.83 | 23.69 | 0.00 | 23.69 |
June | 119.67 | 23.13 | 265.83 | 23.92 | 0.17 | 23.92 |
July | 29.17 | 24.27 | 423.50 | 24.37 | 8.00 | 24.41 |
August | 29.67 | 24.13 | 431.50 | 24.25 | 7.17 | 24.29 |
September | 101.17 | 23.16 | 293.33 | 23.96 | 0.67 | 23.97 |
October | 137.17 | 23.28 | 205.17 | 23.95 | 0.50 | 23.95 |
November | 312.33 | 23.04 | 42.50 | 23.19 | 0.00 | 23.19 |
December | 444.67 | 22.92 | 5.00 | 22.93 | 0.67 | 22.92 |
Annual Sum or Average | 2732.67 | 22.86 | 2132.50 | 23.50 | 26.33 | 23.50 |
Minimum of Months | 29.17 | 22.49 | 5.00 | 22.59 | 0.00 | 22.59 |
Maximum of Months | 444.67 | 24.27 | 431.50 | 24.37 | 8.00 | 24.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 247.00 | 22.60 | 155.83 | 23.32 | 6.17 | 23.30 |
February | 301.83 | 22.35 | 90.33 | 22.89 | 0.00 | 22.89 |
March | 371.17 | 22.15 | 81.50 | 22.46 | 10.17 | 22.40 |
April | 285.67 | 22.61 | 128.50 | 23.17 | 0.00 | 23.17 |
May | 355.50 | 22.60 | 63.67 | 22.87 | 0.00 | 22.87 |
June | 274.17 | 22.82 | 118.33 | 23.21 | 0.00 | 23.21 |
July | 104.33 | 22.88 | 302.33 | 23.83 | 11.33 | 23.82 |
August | 82.00 | 22.80 | 379.67 | 23.89 | 21.00 | 23.87 |
September | 94.33 | 22.88 | 324.00 | 24.01 | 10.17 | 24.01 |
October | 123.33 | 23.54 | 303.33 | 24.29 | 27.50 | 24.38 |
November | 206.17 | 22.89 | 172.00 | 23.71 | 3.33 | 23.74 |
December | 237.67 | 22.78 | 148.00 | 23.56 | 1.00 | 23.57 |
Annual Sum or Average | 2683.17 | 22.64 | 2267.50 | 23.43 | 90.67 | 23.44 |
Minimum of Months | 82.00 | 22.15 | 63.67 | 22.46 | 0.00 | 22.40 |
Maximum of Months | 371.17 | 23.54 | 379.67 | 24.29 | 27.50 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.33 | 22.41 | 36.83 | 22.47 | 9.00 | 22.43 |
February | 376.17 | 22.36 | 33.33 | 22.52 | 0.00 | 22.52 |
March | 413.00 | 22.39 | 57.83 | 22.60 | 2.17 | 22.59 |
April | 237.83 | 22.91 | 154.67 | 23.50 | 0.50 | 23.50 |
May | 212.17 | 23.04 | 179.50 | 23.67 | 0.67 | 23.68 |
June | 104.17 | 23.22 | 302.50 | 23.99 | 1.50 | 24.00 |
July | 25.17 | 25.44 | 436.33 | 24.41 | 15.17 | 24.49 |
August | 26.33 | 24.72 | 443.67 | 24.27 | 10.83 | 24.33 |
September | 72.17 | 23.39 | 325.00 | 24.13 | 3.67 | 24.15 |
October | 172.00 | 23.35 | 220.17 | 23.92 | 4.00 | 23.95 |
November | 343.50 | 22.87 | 72.17 | 23.11 | 0.00 | 23.11 |
December | 421.00 | 22.56 | 15.50 | 22.62 | 0.50 | 22.61 |
Annual Sum or Average | 2817.83 | 22.73 | 2277.50 | 23.43 | 48.00 | 23.44 |
Minimum of Months | 25.17 | 22.36 | 15.50 | 22.47 | 0.00 | 22.43 |
Maximum of Months | 421.00 | 25.44 | 443.67 | 24.41 | 15.17 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 451.50 | 22.30 | 32.00 | 22.23 | 23.67 | 22.15 |
February | 404.67 | 22.42 | 5.67 | 22.43 | 2.17 | 22.42 |
March | 435.17 | 22.47 | 30.33 | 22.53 | 5.00 | 22.50 |
April | 293.50 | 22.92 | 73.83 | 23.13 | 0.00 | 23.13 |
May | 238.83 | 23.10 | 106.33 | 23.41 | 0.00 | 23.41 |
June | 89.17 | 23.30 | 272.33 | 23.91 | 0.00 | 23.91 |
July | 20.50 | 23.32 | 408.33 | 24.13 | 0.00 | 24.13 |
August | 35.67 | 23.25 | 387.67 | 24.01 | 0.17 | 24.01 |
September | 130.00 | 23.20 | 228.83 | 23.76 | 0.00 | 23.76 |
October | 229.17 | 23.21 | 149.33 | 23.60 | 0.00 | 23.60 |
November | 392.17 | 22.73 | 16.50 | 22.77 | 2.00 | 22.77 |
December | 477.67 | 22.48 | 9.17 | 22.46 | 8.00 | 22.43 |
Annual Sum or Average | 3198.00 | 22.68 | 1720.33 | 23.15 | 41.00 | 23.13 |
Minimum of Months | 20.50 | 22.30 | 5.67 | 22.23 | 0.00 | 22.15 |
Maximum of Months | 477.67 | 23.32 | 408.33 | 24.13 | 23.67 | 24.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 356.83 | 22.44 | 35.00 | 22.47 | 12.50 | 22.40 |
February | 313.00 | 22.36 | 24.50 | 22.51 | 1.00 | 22.50 |
March | 308.00 | 22.32 | 60.17 | 22.62 | 4.00 | 22.60 |
April | 194.83 | 22.80 | 155.83 | 23.55 | 2.33 | 23.56 |
May | 192.33 | 22.95 | 155.50 | 23.67 | 0.50 | 23.67 |
June | 115.67 | 23.30 | 227.17 | 24.00 | 6.33 | 24.05 |
July | 55.67 | 24.46 | 329.33 | 24.46 | 19.83 | 24.58 |
August | 57.83 | 24.02 | 324.83 | 24.26 | 14.50 | 24.35 |
September | 126.00 | 23.16 | 216.17 | 23.87 | 5.00 | 23.92 |
October | 156.33 | 23.08 | 160.17 | 23.79 | 1.83 | 23.81 |
November | 289.00 | 22.72 | 40.00 | 22.92 | 0.67 | 22.91 |
December | 373.83 | 22.62 | 11.67 | 22.60 | 6.83 | 22.56 |
Annual Sum or Average | 2539.33 | 22.74 | 1740.33 | 23.39 | 75.33 | 23.41 |
Minimum of Months | 55.67 | 22.32 | 11.67 | 22.47 | 0.50 | 22.40 |
Maximum of Months | 373.83 | 24.46 | 329.33 | 24.46 | 19.83 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 237.83 | 22.70 | 169.50 | 23.37 | 13.33 | 23.35 |
February | 251.50 | 22.58 | 119.83 | 23.22 | 3.50 | 23.25 |
March | 293.00 | 22.53 | 129.00 | 23.04 | 4.17 | 23.03 |
April | 205.00 | 22.91 | 187.50 | 23.59 | 0.00 | 23.59 |
May | 229.17 | 23.02 | 146.83 | 23.50 | 0.00 | 23.50 |
June | 122.17 | 23.24 | 252.67 | 23.84 | 0.00 | 23.84 |
July | 33.17 | 23.41 | 378.67 | 24.16 | 0.83 | 24.17 |
August | 28.17 | 23.51 | 411.67 | 24.14 | 2.17 | 24.16 |
September | 79.17 | 23.54 | 336.33 | 24.18 | 7.33 | 24.23 |
October | 132.50 | 23.99 | 300.50 | 24.37 | 26.67 | 24.52 |
November | 209.33 | 23.14 | 193.50 | 23.84 | 7.00 | 23.89 |
December | 233.50 | 22.91 | 166.17 | 23.64 | 5.83 | 23.68 |
Annual Sum or Average | 2054.50 | 22.96 | 2792.17 | 23.75 | 70.83 | 23.78 |
Minimum of Months | 28.17 | 22.53 | 119.83 | 23.04 | 0.00 | 23.03 |
Maximum of Months | 293.00 | 23.99 | 411.67 | 24.37 | 26.67 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 395.83 | 22.20 | 66.67 | 22.30 | 21.17 | 22.22 |
February | 350.83 | 22.24 | 56.17 | 22.51 | 2.33 | 22.50 |
March | 387.00 | 22.31 | 88.33 | 22.62 | 5.83 | 22.60 |
April | 236.33 | 22.83 | 169.50 | 23.48 | 6.83 | 23.52 |
May | 221.83 | 22.98 | 192.33 | 23.64 | 6.00 | 23.68 |
June | 112.67 | 23.34 | 310.33 | 24.01 | 9.33 | 24.07 |
July | 62.67 | 24.58 | 402.33 | 24.38 | 24.67 | 24.51 |
August | 60.00 | 24.00 | 415.67 | 24.18 | 15.33 | 24.27 |
September | 115.17 | 23.30 | 293.17 | 24.01 | 9.00 | 24.07 |
October | 199.83 | 23.15 | 214.50 | 23.79 | 7.50 | 23.84 |
November | 345.67 | 22.59 | 86.17 | 22.92 | 2.50 | 22.92 |
December | 402.67 | 22.35 | 37.33 | 22.44 | 8.17 | 22.41 |
Annual Sum or Average | 2890.50 | 22.64 | 2332.50 | 23.35 | 118.67 | 23.38 |
Minimum of Months | 60.00 | 22.20 | 37.33 | 22.30 | 2.33 | 22.22 |
Maximum of Months | 402.67 | 24.58 | 415.67 | 24.38 | 24.67 | 24.51 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.24910 | 36.44004 | 0.38282 | 8.36848 |
February | 454.00000 | 24.25105 | 38.43821 | 0.39993 | 8.54199 |
March | 514.00000 | 24.25700 | 41.02064 | 0.42161 | 8.91323 |
April | 485.00000 | 24.34047 | 43.70858 | 0.47528 | 9.94736 |
May | 508.00000 | 24.37003 | 42.91382 | -0.3831 | 8.45311 |
June | 496.00000 | 24.36171 | 47.86216 | -0.3312 | 7.67666 |
July | 497.00000 | 24.41440 | 51.63946 | -0.2769 | 7.01564 |
August | 514.00000 | 24.35665 | 53.02888 | -0.2771 | 6.97279 |
September | 485.00000 | 24.39819 | 48.96932 | -0.3073 | 7.39773 |
October | 502.00000 | 24.40140 | 40.51399 | 0.49024 | 10.39734 |
November | 489.00000 | 24.37224 | 36.44948 | 0.43170 | 9.34598 |
December | 497.00000 | 24.26971 | 31.81430 | 0.36461 | 8.07518 |
Annual Sum or Average | 5943.00000 | 24.33714 | 42.77508 | 0.11297 | 8.42140 |
Minimum of Months | 454.00000 | 24.24910 | 31.81430 | -0.3831 | 6.97279 |
Maximum of Months | 514.00000 | 24.41440 | 53.02888 | 0.49024 | 10.39734 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.56206 | 38.74654 | 0.21031 | 6.56589 |
February | 454.00000 | 23.59680 | 40.89150 | 0.23652 | 6.57436 |
March | 514.00000 | 23.66086 | 43.63649 | 0.27162 | 6.92730 |
April | 485.00000 | 23.88388 | 45.47825 | 0.35854 | 8.04026 |
May | 508.00000 | 23.97516 | 44.55275 | -0.5340 | 11.38121 |
June | 496.00000 | 24.10684 | 49.27116 | -0.4378 | 9.28951 |
July | 497.00000 | 24.19113 | 52.99709 | -0.3711 | 8.10749 |
August | 514.00000 | 24.16042 | 54.35284 | -0.3660 | 7.99357 |
September | 485.00000 | 24.12144 | 50.45147 | -0.4235 | 9.02595 |
October | 502.00000 | 24.10428 | 41.95323 | 0.40392 | 8.74569 |
November | 489.00000 | 23.86788 | 38.36848 | 0.29664 | 7.30553 |
December | 497.00000 | 23.63889 | 34.02676 | 0.20401 | 6.29504 |
Annual Sum or Average | 5943.00000 | 23.90770 | 44.59916 | -0.0153 | 8.03253 |
Minimum of Months | 454.00000 | 23.56206 | 34.02676 | -0.5340 | 6.29504 |
Maximum of Months | 514.00000 | 24.19113 | 54.35284 | 0.40392 | 11.38121 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.90874 | 40.30806 | 0.05022 | 6.36041 |
February | 454.00000 | 23.00384 | 42.46538 | 0.09220 | 6.12973 |
March | 514.00000 | 23.12213 | 44.94254 | 0.14065 | 6.35472 |
April | 485.00000 | 23.57460 | 46.25279 | 0.28530 | 7.37986 |
May | 508.00000 | 23.70169 | 45.15265 | -0.6265 | 14.18005 |
June | 496.00000 | 23.93757 | 49.51165 | -0.4918 | 10.51902 |
July | 497.00000 | 24.06704 | 53.16026 | -0.4058 | 8.71471 |
August | 514.00000 | 24.02959 | 54.62845 | -0.4058 | 8.69565 |
September | 485.00000 | 23.89855 | 50.97455 | -0.5003 | 10.71577 |
October | 502.00000 | 23.81209 | 42.67193 | 0.33073 | 7.85872 |
November | 489.00000 | 23.34112 | 39.77964 | 0.16501 | 6.46836 |
December | 497.00000 | 22.97539 | 35.58081 | 0.04142 | 5.99719 |
Annual Sum or Average | 5943.00000 | 23.53449 | 45.48576 | -0.1128 | 8.30034 |
Minimum of Months | 454.00000 | 22.90874 | 35.58081 | -0.6265 | 5.99719 |
Maximum of Months | 514.00000 | 24.06704 | 54.62845 | 0.33073 | 14.18005 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.93656 | 41.91328 | -0.1963 | 8.06241 |
February | 454.00000 | 22.05477 | 44.98839 | -0.1393 | 7.10713 |
March | 514.00000 | 22.22664 | 47.74956 | -0.0760 | 7.04571 |
April | 485.00000 | 23.01077 | 48.62166 | 0.14757 | 6.87627 |
May | 508.00000 | 23.29236 | 47.07155 | -0.7651 | 19.32634 |
June | 496.00000 | 23.73666 | 50.94060 | -0.5561 | 12.53219 |
July | 497.00000 | 23.95066 | 54.46269 | -0.4385 | 9.75225 |
August | 514.00000 | 23.81176 | 56.56381 | -0.4790 | 10.60855 |
September | 485.00000 | 23.53833 | 53.24887 | -0.6265 | 14.57719 |
October | 502.00000 | 23.37247 | 44.51562 | 0.22161 | 7.45310 |
November | 489.00000 | 22.43794 | 42.18273 | -0.0580 | 6.83816 |
December | 497.00000 | 21.94977 | 37.39739 | -0.2149 | 7.69022 |
Annual Sum or Average | 5943.00000 | 22.94946 | 47.50076 | -0.2668 | 9.85044 |
Minimum of Months | 454.00000 | 21.93656 | 37.39739 | -0.7651 | 6.83816 |
Maximum of Months | 514.00000 | 23.95066 | 56.56381 | 0.22161 | 19.32634 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.40458 | 40.63113 | -0.0620 | 7.31242 |
February | 454.00000 | 22.40342 | 43.89984 | -0.0340 | 7.03406 |
March | 514.00000 | 22.60604 | 46.35990 | 0.04116 | 7.51305 |
April | 485.00000 | 23.41333 | 46.90174 | 0.28621 | 8.58270 |
May | 508.00000 | 23.51847 | 46.00897 | -0.6372 | 16.38389 |
June | 496.00000 | 23.79441 | 50.42193 | -0.4772 | 11.88437 |
July | 497.00000 | 24.11647 | 53.46397 | -0.3065 | 9.03549 |
August | 514.00000 | 23.96951 | 55.36996 | -0.3410 | 9.32514 |
September | 485.00000 | 23.65745 | 52.37234 | -0.5269 | 13.06459 |
October | 502.00000 | 23.59230 | 43.65137 | 0.30774 | 8.39584 |
November | 489.00000 | 22.83394 | 41.00406 | 0.05911 | 6.78600 |
December | 497.00000 | 22.41533 | 36.27274 | -0.0814 | 6.84155 |
Annual Sum or Average | 5943.00000 | 23.23275 | 46.39229 | -0.1493 | 9.36559 |
Minimum of Months | 454.00000 | 22.40342 | 36.27274 | -0.6372 | 6.78600 |
Maximum of Months | 514.00000 | 24.11647 | 55.36996 | 0.30774 | 16.38389 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.11087 | 38.10918 | 0.14798 | 8.93135 |
February | 454.00000 | 22.88896 | 42.07520 | 0.10342 | 8.38423 |
March | 514.00000 | 22.78068 | 45.39503 | 0.08918 | 8.20232 |
April | 485.00000 | 23.34320 | 46.96915 | 0.25729 | 8.47983 |
May | 508.00000 | 23.29191 | 46.73948 | -0.7493 | 19.52791 |
June | 496.00000 | 23.63792 | 51.11100 | -0.5816 | 13.56694 |
July | 497.00000 | 23.92241 | 54.38370 | -0.4336 | 10.19077 |
August | 514.00000 | 23.89661 | 55.75584 | -0.4048 | 9.91190 |
September | 485.00000 | 23.84426 | 51.48294 | -0.4506 | 11.90300 |
October | 502.00000 | 23.90024 | 42.40426 | 0.40999 | 10.72757 |
November | 489.00000 | 23.41882 | 38.62889 | 0.23837 | 8.94857 |
December | 497.00000 | 23.25880 | 33.57347 | 0.16376 | 8.86404 |
Annual Sum or Average | 5943.00000 | 23.44385 | 45.59308 | -0.1036 | 10.66247 |
Minimum of Months | 454.00000 | 22.78068 | 33.57347 | -0.7493 | 8.20232 |
Maximum of Months | 514.00000 | 23.92241 | 55.75584 | 0.40999 | 19.52791 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.09963 | 40.84720 | -0.1297 | 8.23232 |
February | 454.00000 | 22.18252 | 43.94769 | -0.0782 | 7.68464 |
March | 514.00000 | 22.29176 | 46.77821 | -0.0251 | 7.73761 |
April | 485.00000 | 23.15416 | 47.60166 | 0.23324 | 8.79445 |
May | 508.00000 | 23.31339 | 46.51376 | -0.6915 | 19.27061 |
June | 496.00000 | 23.69331 | 50.73452 | -0.4936 | 12.85424 |
July | 497.00000 | 23.99469 | 54.02409 | -0.3407 | 9.95524 |
August | 514.00000 | 23.84999 | 55.98749 | -0.3780 | 10.28996 |
September | 485.00000 | 23.62506 | 52.44082 | -0.5214 | 13.66453 |
October | 502.00000 | 23.41461 | 43.89433 | 0.27279 | 8.78892 |
November | 489.00000 | 22.54238 | 41.04833 | 0.00200 | 7.53172 |
December | 497.00000 | 22.14055 | 36.26098 | -0.1407 | 7.90022 |
Annual Sum or Average | 5943.00000 | 23.03068 | 46.70575 | -0.1927 | 10.24981 |
Minimum of Months | 454.00000 | 22.09963 | 36.26098 | -0.6915 | 7.53172 |
Maximum of Months | 514.00000 | 23.99469 | 55.98749 | 0.27279 | 19.27061 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.26354 | 41.44926 | -0.1110 | 6.58446 |
February | 454.00000 | 22.21092 | 44.82959 | -0.1014 | 5.95758 |
March | 514.00000 | 22.29779 | 47.72936 | -0.0615 | 6.09076 |
April | 485.00000 | 23.00139 | 49.31740 | 0.13193 | 6.12716 |
May | 508.00000 | 23.35748 | 47.63389 | -0.7655 | 18.32446 |
June | 496.00000 | 23.72437 | 51.63158 | -0.5906 | 12.87575 |
July | 497.00000 | 23.95995 | 54.62826 | -0.4667 | 9.87140 |
August | 514.00000 | 23.83576 | 56.63829 | -0.5005 | 10.61849 |
September | 485.00000 | 23.65883 | 53.15950 | -0.6032 | 13.23087 |
October | 502.00000 | 23.59475 | 44.19475 | 0.26895 | 7.20035 |
November | 489.00000 | 22.82299 | 41.66785 | 0.03640 | 5.91935 |
December | 497.00000 | 22.30594 | 36.92705 | -0.1234 | 6.13913 |
Annual Sum or Average | 5943.00000 | 23.09186 | 47.51439 | -0.2425 | 9.11138 |
Minimum of Months | 454.00000 | 22.21092 | 36.92705 | -0.7655 | 5.91935 |
Maximum of Months | 514.00000 | 23.95995 | 56.63829 | 0.26895 | 18.32446 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.98697 | 39.91603 | 0.07725 | 6.37137 |
February | 454.00000 | 22.80752 | 43.47778 | 0.05600 | 6.17086 |
March | 514.00000 | 22.94698 | 45.99333 | 0.11118 | 6.76181 |
April | 485.00000 | 23.65676 | 46.82543 | 0.32328 | 8.18441 |
May | 508.00000 | 23.75137 | 46.06396 | -0.5879 | 13.86482 |
June | 496.00000 | 23.90901 | 50.65664 | -0.4762 | 11.08248 |
July | 497.00000 | 24.25386 | 53.14313 | -0.2973 | 8.03581 |
August | 514.00000 | 24.13980 | 54.83368 | -0.3177 | 8.12814 |
September | 485.00000 | 23.92261 | 51.82980 | -0.4611 | 10.52614 |
October | 502.00000 | 23.93689 | 43.02342 | 0.38118 | 8.69203 |
November | 489.00000 | 23.41664 | 40.20477 | 0.19566 | 6.57433 |
December | 497.00000 | 23.03673 | 35.56627 | 0.06485 | 5.91216 |
Annual Sum or Average | 5943.00000 | 23.56852 | 45.99062 | -0.0794 | 8.37602 |
Minimum of Months | 454.00000 | 22.80752 | 35.56627 | -0.5879 | 5.91216 |
Maximum of Months | 514.00000 | 24.25386 | 54.83368 | 0.38118 | 13.86482 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.48637 | 37.00132 | 0.25810 | 8.32712 |
February | 454.00000 | 23.03505 | 41.35573 | 0.15301 | 7.41174 |
March | 514.00000 | 22.72146 | 44.98434 | 0.08714 | 7.25052 |
April | 485.00000 | 23.27578 | 47.36889 | 0.23619 | 7.45437 |
May | 508.00000 | 23.05833 | 47.50517 | -0.8288 | 21.22248 |
June | 496.00000 | 23.33697 | 52.67100 | -0.6949 | 16.38748 |
July | 497.00000 | 23.81062 | 55.97808 | -0.4884 | 10.96586 |
August | 514.00000 | 23.88002 | 57.13674 | -0.4235 | 9.82525 |
September | 485.00000 | 23.96283 | 51.72625 | -0.4133 | 10.29100 |
October | 502.00000 | 24.15848 | 42.02702 | 0.47684 | 11.16785 |
November | 489.00000 | 23.74262 | 37.82661 | 0.33627 | 8.89606 |
December | 497.00000 | 23.65288 | 32.53760 | 0.27818 | 8.38865 |
Annual Sum or Average | 5943.00000 | 23.51132 | 45.72540 | -0.0885 | 10.67027 |
Minimum of Months | 454.00000 | 22.72146 | 32.53760 | -0.8288 | 7.25052 |
Maximum of Months | 514.00000 | 24.15848 | 57.13674 | 0.47684 | 21.22248 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.69521 | 40.22640 | 0.01159 | 6.56702 |
February | 454.00000 | 22.66471 | 43.44593 | 0.02780 | 6.30560 |
March | 514.00000 | 22.72825 | 46.20816 | 0.06477 | 6.58631 |
April | 485.00000 | 23.57862 | 47.06816 | 0.30756 | 8.26193 |
May | 508.00000 | 23.72968 | 46.08825 | -0.5873 | 14.20607 |
June | 496.00000 | 23.95749 | 50.47562 | -0.4468 | 10.43725 |
July | 497.00000 | 24.26094 | 53.24359 | -0.2904 | 7.87602 |
August | 514.00000 | 24.13933 | 55.02974 | -0.3181 | 8.05995 |
September | 485.00000 | 24.05004 | 51.38845 | -0.4067 | 9.53726 |
October | 502.00000 | 23.90552 | 43.06519 | 0.37641 | 8.92534 |
November | 489.00000 | 23.24445 | 40.18221 | 0.16300 | 6.68659 |
December | 497.00000 | 22.79210 | 35.64234 | 0.01202 | 6.15340 |
Annual Sum or Average | 5943.00000 | 23.48354 | 46.03714 | -0.0925 | 8.31846 |
Minimum of Months | 454.00000 | 22.66471 | 35.64234 | -0.5873 | 6.15340 |
Maximum of Months | 514.00000 | 24.26094 | 55.02974 | 0.37641 | 14.20607 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.46818 | 40.80368 | -0.0591 | 6.68022 |
February | 454.00000 | 22.58721 | 43.79516 | -0.0060 | 6.07278 |
March | 514.00000 | 22.69266 | 46.68598 | 0.04137 | 6.30588 |
April | 485.00000 | 23.33591 | 47.88190 | 0.22467 | 6.82478 |
May | 508.00000 | 23.58855 | 46.43381 | -0.6668 | 15.33504 |
June | 496.00000 | 23.91427 | 50.61771 | -0.4998 | 10.68331 |
July | 497.00000 | 24.07980 | 54.19149 | -0.4021 | 8.68612 |
August | 514.00000 | 23.95526 | 56.11178 | -0.4358 | 9.28099 |
September | 485.00000 | 23.78474 | 52.57081 | -0.5441 | 11.79502 |
October | 502.00000 | 23.68821 | 43.81808 | 0.29869 | 7.63763 |
November | 489.00000 | 22.98136 | 41.05584 | 0.07704 | 6.22157 |
December | 497.00000 | 22.53888 | 36.33128 | -0.0658 | 6.16579 |
Annual Sum or Average | 5943.00000 | 23.30599 | 46.72415 | -0.1719 | 8.49735 |
Minimum of Months | 454.00000 | 22.46818 | 36.33128 | -0.6668 | 6.07278 |
Maximum of Months | 514.00000 | 24.07980 | 56.11178 | 0.29869 | 15.33504 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.71354 | 39.82049 | 0.01947 | 6.63386 |
February | 385.00000 | 22.70409 | 42.93073 | 0.04335 | 6.41896 |
March | 433.00000 | 22.84559 | 45.20362 | 0.09998 | 6.99525 |
April | 410.00000 | 23.58410 | 46.48172 | 0.31790 | 8.46151 |
May | 430.00000 | 23.70506 | 45.58865 | -0.5863 | 14.38680 |
June | 418.00000 | 23.92262 | 50.17926 | -0.4548 | 11.04690 |
July | 422.00000 | 24.24146 | 53.16613 | -0.2942 | 8.68671 |
August | 433.00000 | 24.07404 | 55.09901 | -0.3330 | 8.89156 |
September | 410.00000 | 23.81914 | 51.88611 | -0.4888 | 11.60357 |
October | 427.00000 | 23.80204 | 43.36076 | 0.35258 | 8.63015 |
November | 417.00000 | 23.15420 | 40.18412 | 0.14026 | 6.55331 |
December | 422.00000 | 22.78264 | 35.26693 | 0.01209 | 6.14340 |
Annual Sum or Average | 5034.00000 | 23.44995 | 45.78112 | -0.0990 | 8.71865 |
Minimum of Months | 385.00000 | 22.70409 | 35.26693 | -0.5863 | 6.14340 |
Maximum of Months | 433.00000 | 24.24146 | 55.09901 | 0.35258 | 14.38680 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.52841 | 37.16577 | 0.25858 | 8.69039 |
February | 454.00000 | 23.33879 | 40.97085 | 0.21796 | 8.04844 |
March | 514.00000 | 23.22628 | 44.35990 | 0.20019 | 7.81544 |
April | 485.00000 | 23.66155 | 46.22849 | 0.33086 | 8.48596 |
May | 508.00000 | 23.61552 | 46.08015 | -0.6444 | 15.19504 |
June | 496.00000 | 23.85355 | 50.72853 | -0.5156 | 11.27157 |
July | 497.00000 | 24.08355 | 54.04819 | -0.3897 | 8.82125 |
August | 514.00000 | 24.05924 | 55.27010 | -0.3588 | 8.46262 |
September | 485.00000 | 24.08294 | 50.87203 | -0.3738 | 9.47191 |
October | 502.00000 | 24.16331 | 41.83126 | 0.47430 | 11.14525 |
November | 489.00000 | 23.82133 | 37.72167 | 0.34246 | 9.16390 |
December | 497.00000 | 23.69054 | 32.71354 | 0.27816 | 8.73079 |
Annual Sum or Average | 5943.00000 | 23.76212 | 44.87589 | -0.0179 | 9.62515 |
Minimum of Months | 454.00000 | 23.22628 | 32.71354 | -0.6444 | 7.81544 |
Maximum of Months | 514.00000 | 24.16331 | 55.27010 | 0.47430 | 15.19504 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.59614 | 39.84334 | -0.0006 | 7.03867 |
February | 454.00000 | 22.67379 | 42.87828 | 0.04615 | 6.78357 |
March | 514.00000 | 22.74384 | 45.76060 | 0.08836 | 7.05078 |
April | 485.00000 | 23.50855 | 46.83613 | 0.31435 | 8.77221 |
May | 508.00000 | 23.65051 | 45.85989 | -0.5833 | 14.80448 |
June | 496.00000 | 23.92207 | 50.34002 | -0.4248 | 10.46478 |
July | 497.00000 | 24.17096 | 53.63843 | -0.2935 | 8.49492 |
August | 514.00000 | 24.03353 | 55.45386 | -0.3262 | 8.65086 |
September | 485.00000 | 23.91062 | 51.73879 | -0.4306 | 10.64982 |
October | 502.00000 | 23.75522 | 43.23848 | 0.35355 | 9.01851 |
November | 489.00000 | 23.05125 | 40.05081 | 0.12898 | 6.98326 |
December | 497.00000 | 22.68163 | 35.31488 | -0.0023 | 6.65090 |
Annual Sum or Average | 5943.00000 | 23.39589 | 45.94767 | -0.0962 | 8.79762 |
Minimum of Months | 454.00000 | 22.59614 | 35.31488 | -0.5833 | 6.65090 |
Maximum of Months | 514.00000 | 24.17096 | 55.45386 | 0.35355 | 14.80448 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.884321E+10 | 0.223516E+10 | 201.85 | 0.809952E+10 | 0.743694E+09 | 0.00 | 1.00 | 13-JAN-11:50 | 0.00 | 01-JAN-00:10 | 42067.80 | 18-JAN-13:30 | 42067.80 | 18-JAN-13:30 | 6875.47 | 20-JAN-13:20 | 10035.75 | 18-JAN-13:10 | 0.00 |
February | 0.509901E+10 | 0.132656E+10 | 153.53 | 0.432781E+10 | 0.771199E+09 | 0.00 | 1.00 | 01-FEB-10:00 | 0.00 | 01-FEB-00:10 | 37886.24 | 01-FEB-12:00 | 37886.24 | 01-FEB-12:00 | 7847.95 | 01-FEB-14:00 | 9120.35 | 01-FEB-12:00 | 0.00 |
March | 0.612256E+10 | 0.155499E+10 | 144.83 | 0.479062E+10 | 0.133193E+10 | 0.00 | 1.00 | 22-MAR-12:10 | 0.00 | 01-MAR-00:10 | 40681.77 | 23-MAR-15:10 | 33563.35 | 23-MAR-14:00 | 11361.08 | 23-MAR-16:00 | 9336.83 | 23-MAR-15:10 | 0.00 |
April | 0.136394E+11 | 0.340215E+10 | 248.07 | 0.112621E+11 | 0.237732E+10 | 0.00 | 1.00 | 04-APR-12:20 | 0.00 | 01-APR-00:10 | 47029.37 | 26-APR-13:00 | 45685.11 | 26-APR-13:00 | 7604.58 | 13-APR-16:00 | 11601.23 | 26-APR-13:00 | 0.00 |
May | 0.146400E+11 | 0.369120E+10 | 297.35 | 0.122661E+11 | 0.237390E+10 | 0.00 | 1.00 | 02-MAY-12:50 | 0.00 | 01-MAY-00:10 | 38385.81 | 03-MAY-13:00 | 38385.81 | 03-MAY-13:00 | 11449.47 | 05-MAY-15:00 | 8807.07 | 03-MAY-13:00 | 0.00 |
June | 0.273446E+11 | 0.663085E+10 | 382.54 | 0.204196E+11 | 0.692502E+10 | 0.00 | 1.00 | 14-JUN-09:40 | 0.00 | 01-JUN-00:10 | 60281.38 | 29-JUN-13:00 | 39640.61 | 29-JUN-11:00 | 21830.62 | 29-JUN-13:00 | 13889.61 | 29-JUN-13:00 | 0.00 |
July | 0.457692E+11 | 0.108825E+11 | 419.97 | 0.303879E+11 | 0.153813E+11 | 0.00 | 1.00 | 03-JUL-09:20 | 0.00 | 01-JUL-00:10 | 84272.07 | 31-JUL-15:40 | 52695.24 | 31-JUL-13:00 | 35136.33 | 31-JUL-15:40 | 19506.09 | 31-JUL-15:40 | 0.00 |
August | 0.530155E+11 | 0.125370E+11 | 439.10 | 0.342860E+11 | 0.187294E+11 | 0.00 | 1.00 | 01-AUG-09:40 | 0.00 | 01-AUG-00:10 | 83300.01 | 18-AUG-15:50 | 51820.12 | 18-AUG-15:10 | 35207.92 | 18-AUG-15:50 | 19234.97 | 18-AUG-15:50 | 0.00 |
September | 0.326364E+11 | 0.800217E+10 | 372.32 | 0.233693E+11 | 0.926712E+10 | 0.00 | 1.00 | 01-SEP-10:40 | 0.00 | 01-SEP-00:10 | 70852.79 | 22-SEP-12:30 | 64345.93 | 29-SEP-13:00 | 36587.78 | 22-SEP-11:30 | 20588.65 | 29-SEP-13:00 | 0.00 |
October | 0.361133E+11 | 0.891472E+10 | 380.31 | 0.285933E+11 | 0.751991E+10 | 0.00 | 1.00 | 01-OCT-11:32 | 0.00 | 01-OCT-00:10 | 78193.07 | 03-OCT-13:20 | 67674.94 | 16-OCT-12:05 | 38380.21 | 02-OCT-06:03 | 21971.26 | 16-OCT-11:00 | 0.00 |
November | 0.100793E+11 | 0.255503E+10 | 228.58 | 0.891772E+10 | 0.116157E+10 | 0.00 | 1.00 | 08-NOV-10:50 | 0.00 | 01-NOV-00:10 | 40942.95 | 28-NOV-14:00 | 40942.95 | 28-NOV-14:00 | 8622.76 | 20-NOV-13:10 | 9615.64 | 28-NOV-14:00 | 0.00 |
December | 0.105375E+11 | 0.261599E+10 | 206.47 | 0.102135E+11 | 0.323983E+09 | 0.00 | 1.00 | 04-DEC-09:50 | 0.00 | 01-DEC-00:10 | 41903.87 | 19-DEC-13:10 | 41903.87 | 19-DEC-13:10 | 6031.67 | 07-DEC-15:40 | 9961.09 | 19-DEC-13:10 | 0.00 |
Annual Sum or Average | 0.263840E+12 | 0.643483E+11 | 3474.92 | 0.196933E+12 | 0.669064E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.509901E+10 | 0.132656E+10 | 144.83 | 0.432781E+10 | 0.323983E+09 | 0.00 | 1.00 | 0.00 | 37886.24 | 33563.35 | 6031.67 | 8807.07 | 0.00 | ||||||
Maximum of Months | 0.530155E+11 | 0.125370E+11 | 439.10 | 0.342860E+11 | 0.187294E+11 | 0.00 | 1.00 | 0.00 | 84272.07 | 67674.94 | 38380.21 | 21971.26 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.731082E+10 | 0.186503E+10 | 200.61 | 0.659307E+10 | 0.717750E+09 | 0.00 | 1.00 | 13-JAN-13:20 | 0.00 | 01-JAN-00:10 | 35655.26 | 18-JAN-14:00 | 35655.26 | 18-JAN-14:00 | 6985.19 | 20-JAN-13:20 | 8324.94 | 18-JAN-13:30 | 0.00 |
February | 0.425236E+10 | 0.111319E+10 | 153.67 | 0.359766E+10 | 0.654700E+09 | 0.00 | 1.00 | 01-FEB-11:30 | 0.00 | 01-FEB-00:10 | 30442.27 | 01-FEB-12:00 | 30442.27 | 01-FEB-12:00 | 6675.43 | 01-FEB-14:00 | 7329.81 | 01-FEB-12:00 | 0.00 |
March | 0.541944E+10 | 0.137949E+10 | 149.89 | 0.423096E+10 | 0.118849E+10 | 0.00 | 1.00 | 22-MAR-12:30 | 0.00 | 01-MAR-00:10 | 37752.59 | 23-MAR-15:00 | 31117.44 | 23-MAR-14:00 | 9946.76 | 23-MAR-16:00 | 8665.19 | 23-MAR-15:00 | 0.00 |
April | 0.121716E+11 | 0.304863E+10 | 256.46 | 0.101026E+11 | 0.206902E+10 | 0.00 | 1.00 | 04-APR-12:40 | 0.00 | 01-APR-00:10 | 43112.78 | 26-APR-14:10 | 41412.89 | 26-APR-14:10 | 6717.20 | 13-APR-16:00 | 10351.24 | 26-APR-13:00 | 0.00 |
May | 0.125422E+11 | 0.318316E+10 | 305.86 | 0.104637E+11 | 0.207857E+10 | 0.00 | 1.00 | 02-MAY-13:00 | 0.00 | 01-MAY-00:10 | 33788.55 | 03-MAY-13:00 | 33788.55 | 03-MAY-13:00 | 10197.85 | 05-MAY-15:00 | 7752.52 | 03-MAY-13:00 | 0.00 |
June | 0.237637E+11 | 0.578343E+10 | 388.99 | 0.178882E+11 | 0.587550E+10 | 0.00 | 1.00 | 14-JUN-09:50 | 0.00 | 01-JUN-00:10 | 52220.99 | 29-JUN-13:00 | 34724.46 | 29-JUN-11:00 | 18582.83 | 29-JUN-13:00 | 12033.46 | 29-JUN-13:00 | 0.00 |
July | 0.397158E+11 | 0.946666E+10 | 427.94 | 0.266314E+11 | 0.130844E+11 | 0.00 | 1.00 | 03-JUL-09:30 | 0.00 | 01-JUL-00:10 | 75842.75 | 31-JUL-15:40 | 46780.26 | 31-JUL-14:10 | 31462.96 | 31-JUL-15:40 | 17554.46 | 31-JUL-15:40 | 0.00 |
August | 0.458001E+11 | 0.108531E+11 | 444.58 | 0.299620E+11 | 0.158381E+11 | 0.00 | 1.00 | 01-AUG-09:50 | 0.00 | 01-AUG-00:10 | 74743.34 | 18-AUG-15:50 | 47128.33 | 18-AUG-15:00 | 31430.46 | 18-AUG-15:50 | 17258.82 | 18-AUG-15:50 | 0.00 |
September | 0.279158E+11 | 0.688083E+10 | 375.31 | 0.202313E+11 | 0.768448E+10 | 0.00 | 1.00 | 01-SEP-10:50 | 0.00 | 01-SEP-00:10 | 59558.56 | 29-SEP-15:20 | 59558.56 | 29-SEP-15:20 | 28986.53 | 22-SEP-10:00 | 19034.12 | 29-SEP-13:00 | 0.00 |
October | 0.302804E+11 | 0.753491E+10 | 381.28 | 0.241428E+11 | 0.613766E+10 | 0.00 | 1.00 | 01-OCT-11:32 | 0.00 | 01-OCT-00:10 | 70038.67 | 03-OCT-13:20 | 62352.87 | 16-OCT-11:00 | 29376.82 | 02-OCT-05:12 | 20573.18 | 16-OCT-11:00 | 0.00 |
November | 0.822610E+10 | 0.210368E+10 | 228.33 | 0.722455E+10 | 0.100155E+10 | 0.00 | 1.00 | 10-NOV-13:10 | 0.00 | 01-NOV-00:10 | 33403.97 | 28-NOV-14:00 | 33403.97 | 28-NOV-14:00 | 7356.38 | 20-NOV-13:10 | 7846.52 | 28-NOV-14:00 | 0.00 |
December | 0.864162E+10 | 0.216770E+10 | 205.36 | 0.834992E+10 | 0.291708E+09 | 0.00 | 1.00 | 05-DEC-09:40 | 0.00 | 01-DEC-00:10 | 35691.99 | 05-DEC-15:10 | 35691.99 | 05-DEC-15:10 | 6356.41 | 07-DEC-13:00 | 8359.34 | 05-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.226040E+12 | 0.553798E+11 | 3518.28 | 0.169418E+12 | 0.566219E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.425236E+10 | 0.111319E+10 | 149.89 | 0.359766E+10 | 0.291708E+09 | 0.00 | 1.00 | 0.00 | 30442.27 | 30442.27 | 6356.41 | 7329.81 | 0.00 | ||||||
Maximum of Months | 0.458001E+11 | 0.108531E+11 | 444.58 | 0.299620E+11 | 0.158381E+11 | 0.00 | 1.00 | 0.00 | 75842.75 | 62352.87 | 31462.96 | 20573.18 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.697836E+10 | 0.180925E+10 | 197.43 | 0.613798E+10 | 0.840376E+09 | 0.00 | 1.00 | 13-JAN-13:50 | 0.00 | 01-JAN-00:10 | 37104.04 | 18-JAN-13:30 | 37104.04 | 18-JAN-13:30 | 6780.38 | 20-JAN-13:10 | 8811.04 | 18-JAN-13:20 | 0.00 |
February | 0.404766E+10 | 0.107572E+10 | 149.56 | 0.333354E+10 | 0.714115E+09 | 0.00 | 1.00 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 | 30925.52 | 01-FEB-12:00 | 30925.52 | 01-FEB-12:00 | 7250.22 | 01-FEB-16:00 | 7447.35 | 01-FEB-12:00 | 0.00 |
March | 0.540857E+10 | 0.138778E+10 | 147.38 | 0.412083E+10 | 0.128774E+10 | 0.00 | 1.00 | 22-MAR-12:50 | 0.00 | 01-MAR-00:10 | 39874.12 | 23-MAR-15:00 | 32833.03 | 23-MAR-14:00 | 10758.96 | 23-MAR-15:50 | 9153.19 | 23-MAR-15:00 | 0.00 |
April | 0.127480E+11 | 0.321137E+10 | 254.61 | 0.103006E+11 | 0.244738E+10 | 0.00 | 1.00 | 04-APR-12:50 | 0.00 | 01-APR-00:10 | 51967.78 | 26-APR-14:00 | 50021.40 | 26-APR-14:00 | 7374.40 | 13-APR-16:00 | 12526.18 | 26-APR-13:50 | 0.00 |
May | 0.130490E+11 | 0.332949E+10 | 304.61 | 0.105969E+11 | 0.245214E+10 | 0.00 | 1.00 | 02-MAY-13:30 | 0.00 | 01-MAY-00:10 | 37077.47 | 03-MAY-13:00 | 37077.47 | 03-MAY-13:00 | 9942.92 | 05-MAY-15:00 | 8507.41 | 03-MAY-13:00 | 0.00 |
June | 0.251923E+11 | 0.615688E+10 | 390.35 | 0.185158E+11 | 0.667651E+10 | 0.00 | 1.00 | 14-JUN-12:10 | 0.00 | 01-JUN-00:10 | 57337.93 | 29-JUN-13:00 | 37284.36 | 27-JUN-13:00 | 20673.22 | 29-JUN-13:00 | 13213.18 | 29-JUN-13:00 | 0.00 |
July | 0.423633E+11 | 0.101390E+11 | 430.69 | 0.279900E+11 | 0.143732E+11 | 0.00 | 1.00 | 03-JUL-10:20 | 0.00 | 01-JUL-00:10 | 87798.92 | 31-JUL-15:10 | 55117.92 | 31-JUL-14:00 | 34519.41 | 31-JUL-15:20 | 20593.49 | 31-JUL-15:10 | 0.00 |
August | 0.485651E+11 | 0.115449E+11 | 444.67 | 0.311686E+11 | 0.173965E+11 | 0.00 | 1.00 | 01-AUG-10:30 | 0.00 | 01-AUG-00:10 | 86849.48 | 18-AUG-15:30 | 54681.88 | 17-AUG-14:00 | 34985.52 | 18-AUG-15:30 | 20305.99 | 18-AUG-15:30 | 0.00 |
September | 0.284996E+11 | 0.708573E+10 | 374.24 | 0.203673E+11 | 0.813230E+10 | 0.00 | 1.00 | 01-SEP-12:50 | 0.00 | 01-SEP-00:10 | 68935.58 | 29-SEP-13:40 | 68935.58 | 29-SEP-13:40 | 28095.49 | 22-SEP-11:40 | 21878.22 | 29-SEP-13:00 | 0.00 |
October | 0.303643E+11 | 0.763853E+10 | 379.33 | 0.239440E+11 | 0.642028E+10 | 0.00 | 1.00 | 01-OCT-11:03 | 0.00 | 01-OCT-00:10 | 74419.57 | 03-OCT-13:10 | 70256.04 | 16-OCT-13:10 | 28566.13 | 03-OCT-13:30 | 22390.96 | 16-OCT-11:00 | 0.00 |
November | 0.766985E+10 | 0.199875E+10 | 223.06 | 0.657386E+10 | 0.109600E+10 | 0.00 | 1.00 | 19-NOV-11:02 | 0.00 | 01-NOV-00:10 | 35395.92 | 19-NOV-13:02 | 35395.92 | 19-NOV-13:02 | 7601.03 | 10-NOV-15:00 | 8667.33 | 19-NOV-13:02 | 0.00 |
December | 0.804751E+10 | 0.206033E+10 | 201.81 | 0.771560E+10 | 0.331912E+09 | 0.00 | 1.00 | 05-DEC-13:50 | 0.00 | 01-DEC-00:10 | 38390.85 | 05-DEC-15:00 | 38390.85 | 05-DEC-15:00 | 6571.84 | 07-DEC-13:00 | 9017.40 | 05-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.232934E+12 | 0.574377E+11 | 3497.72 | 0.170765E+12 | 0.621685E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.404766E+10 | 0.107572E+10 | 147.38 | 0.333354E+10 | 0.331912E+09 | 0.00 | 1.00 | 0.00 | 30925.52 | 30925.52 | 6571.84 | 7447.35 | 0.00 | ||||||
Maximum of Months | 0.485651E+11 | 0.115449E+11 | 444.67 | 0.311686E+11 | 0.173965E+11 | 0.00 | 1.00 | 0.00 | 87798.92 | 70256.04 | 34985.52 | 22390.96 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 293.44 | 0.00 | 293.44 | 179.01 | 1156.93 | 0.00 | 0.00 | 0.00 |
February | 368.34 | 0.00 | 368.34 | 208.75 | 1053.89 | 0.00 | 0.00 | 0.00 |
March | 451.37 | 0.00 | 451.37 | 303.76 | 1087.27 | 0.00 | 0.00 | 0.00 |
April | 520.04 | 2.00 | 518.04 | 418.68 | 872.87 | 0.00 | 0.00 | 0.00 |
May | 624.92 | 29.10 | 595.82 | 532.40 | 763.84 | 0.00 | 0.00 | 0.00 |
June | 665.88 | 65.10 | 600.78 | 683.37 | 604.46 | 0.00 | 0.00 | 0.00 |
July | 630.49 | 52.85 | 577.64 | 724.81 | 542.14 | 0.00 | 0.00 | 0.00 |
August | 523.60 | 10.48 | 513.11 | 581.74 | 570.27 | 0.00 | 0.00 | 0.00 |
September | 443.17 | 0.07 | 443.10 | 452.86 | 680.53 | 0.00 | 0.00 | 0.00 |
October | 351.54 | 0.00 | 351.54 | 402.47 | 758.61 | 0.00 | 0.00 | 0.00 |
November | 318.29 | 0.00 | 318.29 | 202.28 | 1070.00 | 0.00 | 0.00 | 0.00 |
December | 273.17 | 0.00 | 273.17 | 161.99 | 1169.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 455.72 | 13.37 | 442.35 | 405.57 | 859.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 273.17 | 0.00 | 273.17 | 161.99 | 542.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 665.88 | 65.10 | 600.78 | 724.81 | 1169.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 527.68 | 282.22 | 245.47 | 628.16 | 727.37 | 0.00 | 0.00 | 0.00 |
February | 556.65 | 255.01 | 301.65 | 614.61 | 668.42 | 0.00 | 0.00 | 0.00 |
March | 676.17 | 301.26 | 374.91 | 779.92 | 688.23 | 0.00 | 0.00 | 0.00 |
April | 864.48 | 433.55 | 430.92 | 1136.91 | 567.80 | 0.00 | 0.00 | 0.00 |
May | 815.82 | 340.46 | 475.36 | 1026.05 | 520.72 | 0.00 | 0.00 | 0.00 |
June | 810.74 | 351.77 | 458.97 | 1095.66 | 418.35 | 0.00 | 0.00 | 0.00 |
July | 918.63 | 456.49 | 462.14 | 1345.48 | 376.79 | 0.00 | 0.00 | 0.00 |
August | 907.22 | 481.88 | 425.34 | 1349.06 | 384.14 | 0.00 | 0.00 | 0.00 |
September | 660.53 | 302.68 | 357.85 | 925.85 | 441.71 | 0.00 | 0.00 | 0.00 |
October | 584.69 | 300.51 | 284.17 | 841.55 | 486.04 | 0.00 | 0.00 | 0.00 |
November | 533.01 | 270.79 | 262.22 | 629.62 | 677.77 | 0.00 | 0.00 | 0.00 |
December | 508.48 | 282.52 | 225.96 | 605.40 | 733.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697.94 | 338.93 | 359.01 | 916.97 | 556.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 508.48 | 255.01 | 225.96 | 605.40 | 376.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 918.63 | 481.88 | 475.36 | 1349.06 | 733.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1936.48 | 1420.50 | 515.98 | 2811.89 | 1124.01 | 0.00 | 0.00 | 0.00 |
February | 1521.97 | 937.46 | 584.52 | 2060.88 | 1030.98 | 0.00 | 0.00 | 0.00 |
March | 1213.37 | 586.11 | 627.25 | 1615.02 | 1087.59 | 0.00 | 0.00 | 0.00 |
April | 1013.80 | 386.57 | 627.23 | 1438.22 | 914.97 | 0.00 | 0.00 | 0.00 |
May | 721.90 | 88.84 | 633.06 | 811.76 | 834.29 | 0.00 | 0.00 | 0.00 |
June | 633.30 | 38.24 | 595.06 | 712.16 | 655.89 | 0.00 | 0.00 | 0.00 |
July | 670.84 | 75.52 | 595.32 | 894.41 | 582.01 | 0.00 | 0.00 | 0.00 |
August | 861.83 | 271.85 | 589.98 | 1344.75 | 607.65 | 0.00 | 0.00 | 0.00 |
September | 1199.23 | 607.69 | 591.54 | 1884.56 | 702.54 | 0.00 | 0.00 | 0.00 |
October | 1525.14 | 1019.60 | 505.54 | 2416.72 | 762.63 | 0.00 | 0.00 | 0.00 |
November | 1853.66 | 1308.65 | 545.00 | 2674.61 | 1043.58 | 0.00 | 0.00 | 0.00 |
December | 2068.78 | 1574.62 | 494.17 | 3019.88 | 1131.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1267.30 | 692.14 | 575.16 | 1806.41 | 872.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 633.30 | 38.24 | 494.17 | 712.16 | 582.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2068.78 | 1574.62 | 633.06 | 3019.88 | 1131.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 502.26 | 253.32 | 248.94 | 626.48 | 762.14 | 0.00 | 0.00 | 0.00 |
February | 599.20 | 276.62 | 322.58 | 706.48 | 693.93 | 0.00 | 0.00 | 0.00 |
March | 686.85 | 303.87 | 382.97 | 820.92 | 713.26 | 0.00 | 0.00 | 0.00 |
April | 946.86 | 493.03 | 453.83 | 1279.84 | 596.32 | 0.00 | 0.00 | 0.00 |
May | 930.11 | 429.62 | 500.49 | 1213.07 | 543.26 | 0.00 | 0.00 | 0.00 |
June | 985.35 | 492.66 | 492.69 | 1363.52 | 430.69 | 0.00 | 0.00 | 0.00 |
July | 1043.07 | 558.14 | 484.93 | 1531.82 | 389.18 | 0.00 | 0.00 | 0.00 |
August | 978.60 | 530.36 | 448.24 | 1459.99 | 403.73 | 0.00 | 0.00 | 0.00 |
September | 837.87 | 448.33 | 389.54 | 1207.86 | 458.80 | 0.00 | 0.00 | 0.00 |
October | 640.51 | 349.69 | 290.82 | 952.96 | 509.18 | 0.00 | 0.00 | 0.00 |
November | 578.57 | 302.63 | 275.94 | 736.93 | 701.69 | 0.00 | 0.00 | 0.00 |
December | 510.98 | 274.07 | 236.91 | 651.90 | 769.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 770.69 | 393.19 | 377.49 | 1047.66 | 580.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 502.26 | 253.32 | 236.91 | 626.48 | 389.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1043.07 | 558.14 | 500.49 | 1531.82 | 769.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 97.81 | 0.00 | 97.81 | 57.46 | 409.26 | 0.00 | 0.00 | 0.00 |
February | 122.77 | 0.00 | 122.77 | 70.92 | 365.49 | 0.00 | 0.00 | 0.00 |
March | 150.45 | 0.00 | 150.45 | 105.65 | 372.37 | 0.00 | 0.00 | 0.00 |
April | 173.34 | 0.67 | 172.67 | 147.90 | 293.63 | 0.00 | 0.00 | 0.00 |
May | 208.30 | 9.70 | 198.60 | 185.01 | 258.93 | 0.00 | 0.00 | 0.00 |
June | 221.95 | 21.70 | 200.25 | 238.97 | 201.54 | 0.00 | 0.00 | 0.00 |
July | 210.15 | 17.61 | 192.54 | 250.83 | 182.07 | 0.00 | 0.00 | 0.00 |
August | 174.52 | 3.49 | 171.03 | 201.36 | 191.35 | 0.00 | 0.00 | 0.00 |
September | 147.72 | 0.02 | 147.69 | 155.05 | 233.20 | 0.00 | 0.00 | 0.00 |
October | 117.17 | 0.00 | 117.17 | 134.81 | 265.20 | 0.00 | 0.00 | 0.00 |
November | 106.09 | 0.00 | 106.09 | 65.05 | 379.85 | 0.00 | 0.00 | 0.00 |
December | 91.05 | 0.00 | 91.05 | 51.32 | 414.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.90 | 4.46 | 147.44 | 139.11 | 296.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.05 | 0.00 | 91.05 | 51.32 | 182.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.95 | 21.70 | 200.25 | 250.83 | 414.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 97.81 | 0.00 | 97.81 | 57.46 | 409.28 | 0.00 | 0.00 | 0.00 |
February | 122.78 | 0.00 | 122.78 | 70.92 | 365.51 | 0.00 | 0.00 | 0.00 |
March | 150.46 | 0.00 | 150.46 | 105.65 | 372.39 | 0.00 | 0.00 | 0.00 |
April | 173.34 | 0.67 | 172.68 | 147.90 | 293.64 | 0.00 | 0.00 | 0.00 |
May | 208.30 | 9.70 | 198.60 | 185.02 | 258.94 | 0.00 | 0.00 | 0.00 |
June | 221.96 | 21.70 | 200.26 | 238.98 | 201.55 | 0.00 | 0.00 | 0.00 |
July | 210.16 | 17.61 | 192.55 | 250.84 | 182.08 | 0.00 | 0.00 | 0.00 |
August | 174.53 | 3.49 | 171.04 | 201.37 | 191.36 | 0.00 | 0.00 | 0.00 |
September | 147.72 | 0.02 | 147.70 | 155.05 | 233.22 | 0.00 | 0.00 | 0.00 |
October | 117.18 | 0.00 | 117.18 | 134.81 | 265.22 | 0.00 | 0.00 | 0.00 |
November | 106.10 | 0.00 | 106.10 | 65.05 | 379.88 | 0.00 | 0.00 | 0.00 |
December | 91.05 | 0.00 | 91.05 | 51.32 | 414.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.91 | 4.46 | 147.45 | 139.11 | 296.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.05 | 0.00 | 91.05 | 51.32 | 182.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.96 | 21.70 | 200.26 | 250.84 | 414.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 97.81 | 0.00 | 97.81 | 57.46 | 409.28 | 0.00 | 0.00 | 0.00 |
February | 122.78 | 0.00 | 122.78 | 70.92 | 365.51 | 0.00 | 0.00 | 0.00 |
March | 150.46 | 0.00 | 150.46 | 105.65 | 372.39 | 0.00 | 0.00 | 0.00 |
April | 173.34 | 0.67 | 172.68 | 147.90 | 293.64 | 0.00 | 0.00 | 0.00 |
May | 208.30 | 9.70 | 198.60 | 185.02 | 258.94 | 0.00 | 0.00 | 0.00 |
June | 221.96 | 21.70 | 200.26 | 238.98 | 201.55 | 0.00 | 0.00 | 0.00 |
July | 210.16 | 17.61 | 192.55 | 250.84 | 182.08 | 0.00 | 0.00 | 0.00 |
August | 174.53 | 3.49 | 171.04 | 201.37 | 191.36 | 0.00 | 0.00 | 0.00 |
September | 147.72 | 0.02 | 147.70 | 155.05 | 233.22 | 0.00 | 0.00 | 0.00 |
October | 117.18 | 0.00 | 117.18 | 134.81 | 265.22 | 0.00 | 0.00 | 0.00 |
November | 106.10 | 0.00 | 106.10 | 65.05 | 379.88 | 0.00 | 0.00 | 0.00 |
December | 91.05 | 0.00 | 91.05 | 51.32 | 414.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.91 | 4.46 | 147.45 | 139.11 | 296.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.05 | 0.00 | 91.05 | 51.32 | 182.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.96 | 21.70 | 200.26 | 250.84 | 414.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 507.61 | 271.48 | 236.13 | 592.75 | 760.51 | 0.00 | 0.00 | 0.00 |
February | 535.47 | 245.30 | 290.17 | 589.93 | 685.12 | 0.00 | 0.00 | 0.00 |
March | 650.44 | 289.80 | 360.64 | 753.40 | 697.05 | 0.00 | 0.00 | 0.00 |
April | 831.58 | 417.05 | 414.53 | 1105.60 | 572.01 | 0.00 | 0.00 | 0.00 |
May | 784.78 | 327.50 | 457.27 | 997.56 | 522.61 | 0.00 | 0.00 | 0.00 |
June | 779.89 | 338.38 | 441.51 | 1070.95 | 412.43 | 0.00 | 0.00 | 0.00 |
July | 883.68 | 439.12 | 444.56 | 1309.07 | 378.66 | 0.00 | 0.00 | 0.00 |
August | 872.70 | 463.55 | 409.15 | 1311.00 | 387.75 | 0.00 | 0.00 | 0.00 |
September | 635.40 | 291.16 | 344.23 | 897.19 | 450.50 | 0.00 | 0.00 | 0.00 |
October | 562.44 | 289.08 | 273.36 | 810.00 | 502.53 | 0.00 | 0.00 | 0.00 |
November | 512.73 | 260.49 | 252.24 | 595.42 | 708.87 | 0.00 | 0.00 | 0.00 |
December | 489.14 | 271.77 | 217.37 | 569.78 | 766.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 671.38 | 326.03 | 345.35 | 885.60 | 569.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 489.14 | 245.30 | 217.37 | 569.78 | 378.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 883.68 | 463.55 | 457.27 | 1311.00 | 766.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.07 | 10.73 | 9.34 | 23.44 | 30.07 | 0.00 | 0.00 | 0.00 |
February | 21.17 | 9.70 | 11.47 | 23.33 | 27.09 | 0.00 | 0.00 | 0.00 |
March | 25.72 | 11.46 | 14.26 | 29.79 | 27.56 | 0.00 | 0.00 | 0.00 |
April | 32.88 | 16.49 | 16.39 | 43.71 | 22.62 | 0.00 | 0.00 | 0.00 |
May | 31.03 | 12.95 | 18.08 | 39.44 | 20.66 | 0.00 | 0.00 | 0.00 |
June | 30.84 | 13.38 | 17.46 | 42.34 | 16.31 | 0.00 | 0.00 | 0.00 |
July | 34.94 | 17.36 | 17.58 | 51.76 | 14.97 | 0.00 | 0.00 | 0.00 |
August | 34.51 | 18.33 | 16.18 | 51.84 | 15.33 | 0.00 | 0.00 | 0.00 |
September | 25.12 | 11.51 | 13.61 | 35.47 | 17.81 | 0.00 | 0.00 | 0.00 |
October | 22.24 | 11.43 | 10.81 | 32.03 | 19.87 | 0.00 | 0.00 | 0.00 |
November | 20.27 | 10.30 | 9.97 | 23.54 | 28.03 | 0.00 | 0.00 | 0.00 |
December | 19.34 | 10.75 | 8.59 | 22.53 | 30.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.55 | 12.89 | 13.65 | 35.02 | 22.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.34 | 9.70 | 8.59 | 22.53 | 14.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.94 | 18.33 | 18.08 | 51.84 | 30.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 645.48 | 473.49 | 171.99 | 936.50 | 415.68 | 0.00 | 0.00 | 0.00 |
February | 507.32 | 312.48 | 194.84 | 692.72 | 371.00 | 0.00 | 0.00 | 0.00 |
March | 404.45 | 195.37 | 209.08 | 546.86 | 379.60 | 0.00 | 0.00 | 0.00 |
April | 337.93 | 128.85 | 209.07 | 489.68 | 312.83 | 0.00 | 0.00 | 0.00 |
May | 240.63 | 29.61 | 211.02 | 282.90 | 279.67 | 0.00 | 0.00 | 0.00 |
June | 211.10 | 12.75 | 198.35 | 251.39 | 214.53 | 0.00 | 0.00 | 0.00 |
July | 223.61 | 25.17 | 198.44 | 308.42 | 194.38 | 0.00 | 0.00 | 0.00 |
August | 287.27 | 90.61 | 196.66 | 457.42 | 207.10 | 0.00 | 0.00 | 0.00 |
September | 399.74 | 202.56 | 197.18 | 634.85 | 248.66 | 0.00 | 0.00 | 0.00 |
October | 508.37 | 339.86 | 168.51 | 808.86 | 277.78 | 0.00 | 0.00 | 0.00 |
November | 617.87 | 436.21 | 181.67 | 892.93 | 384.48 | 0.00 | 0.00 | 0.00 |
December | 689.58 | 524.86 | 164.72 | 1006.18 | 419.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 422.43 | 230.71 | 191.72 | 608.83 | 308.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 211.10 | 12.75 | 164.72 | 251.39 | 194.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 689.58 | 524.86 | 211.02 | 1006.18 | 419.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 645.48 | 473.49 | 171.99 | 936.50 | 415.68 | 0.00 | 0.00 | 0.00 |
February | 507.32 | 312.48 | 194.84 | 692.72 | 371.00 | 0.00 | 0.00 | 0.00 |
March | 404.45 | 195.37 | 209.08 | 546.86 | 379.60 | 0.00 | 0.00 | 0.00 |
April | 337.93 | 128.85 | 209.07 | 489.68 | 312.83 | 0.00 | 0.00 | 0.00 |
May | 240.63 | 29.61 | 211.02 | 282.90 | 279.67 | 0.00 | 0.00 | 0.00 |
June | 211.10 | 12.75 | 198.35 | 251.39 | 214.53 | 0.00 | 0.00 | 0.00 |
July | 223.61 | 25.17 | 198.44 | 308.42 | 194.38 | 0.00 | 0.00 | 0.00 |
August | 287.27 | 90.61 | 196.66 | 457.42 | 207.10 | 0.00 | 0.00 | 0.00 |
September | 399.74 | 202.56 | 197.18 | 634.85 | 248.66 | 0.00 | 0.00 | 0.00 |
October | 508.37 | 339.86 | 168.51 | 808.86 | 277.78 | 0.00 | 0.00 | 0.00 |
November | 617.87 | 436.21 | 181.67 | 892.93 | 384.48 | 0.00 | 0.00 | 0.00 |
December | 689.58 | 524.86 | 164.72 | 1006.18 | 419.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 422.43 | 230.71 | 191.72 | 608.83 | 308.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 211.10 | 12.75 | 164.72 | 251.39 | 194.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 689.58 | 524.86 | 211.02 | 1006.18 | 419.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 645.44 | 473.46 | 171.98 | 936.44 | 415.65 | 0.00 | 0.00 | 0.00 |
February | 507.28 | 312.46 | 194.82 | 692.67 | 370.98 | 0.00 | 0.00 | 0.00 |
March | 404.42 | 195.35 | 209.07 | 546.82 | 379.58 | 0.00 | 0.00 | 0.00 |
April | 337.91 | 128.85 | 209.06 | 489.65 | 312.81 | 0.00 | 0.00 | 0.00 |
May | 240.62 | 29.61 | 211.01 | 282.88 | 279.66 | 0.00 | 0.00 | 0.00 |
June | 211.09 | 12.74 | 198.34 | 251.37 | 214.51 | 0.00 | 0.00 | 0.00 |
July | 223.60 | 25.17 | 198.43 | 308.40 | 194.37 | 0.00 | 0.00 | 0.00 |
August | 287.25 | 90.61 | 196.65 | 457.39 | 207.09 | 0.00 | 0.00 | 0.00 |
September | 399.71 | 202.55 | 197.17 | 634.81 | 248.65 | 0.00 | 0.00 | 0.00 |
October | 508.34 | 339.84 | 168.50 | 808.81 | 277.77 | 0.00 | 0.00 | 0.00 |
November | 617.84 | 436.18 | 181.65 | 892.87 | 384.46 | 0.00 | 0.00 | 0.00 |
December | 689.54 | 524.83 | 164.71 | 1006.11 | 419.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 422.40 | 230.69 | 191.71 | 608.79 | 308.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 211.09 | 12.74 | 164.71 | 251.37 | 194.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 689.54 | 524.83 | 211.01 | 1006.11 | 419.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 483.15 | 243.68 | 239.47 | 600.35 | 797.52 | 0.00 | 0.00 | 0.00 |
February | 576.40 | 266.09 | 310.31 | 684.24 | 715.94 | 0.00 | 0.00 | 0.00 |
March | 660.71 | 292.31 | 368.40 | 799.16 | 727.87 | 0.00 | 0.00 | 0.00 |
April | 910.83 | 474.27 | 436.56 | 1247.10 | 606.38 | 0.00 | 0.00 | 0.00 |
May | 894.72 | 413.27 | 481.45 | 1181.94 | 553.37 | 0.00 | 0.00 | 0.00 |
June | 947.86 | 473.91 | 473.95 | 1333.17 | 431.96 | 0.00 | 0.00 | 0.00 |
July | 1003.38 | 536.90 | 466.48 | 1491.27 | 395.21 | 0.00 | 0.00 | 0.00 |
August | 941.37 | 510.18 | 431.19 | 1420.73 | 410.96 | 0.00 | 0.00 | 0.00 |
September | 805.99 | 431.27 | 374.72 | 1171.55 | 475.27 | 0.00 | 0.00 | 0.00 |
October | 616.14 | 336.39 | 279.75 | 919.33 | 531.25 | 0.00 | 0.00 | 0.00 |
November | 556.56 | 291.12 | 265.44 | 705.61 | 740.97 | 0.00 | 0.00 | 0.00 |
December | 491.54 | 263.64 | 227.90 | 623.25 | 807.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 741.36 | 378.23 | 363.13 | 1016.43 | 598.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 483.15 | 243.68 | 227.90 | 600.35 | 395.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1003.38 | 536.90 | 481.45 | 1491.27 | 807.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.10 | 9.63 | 9.47 | 23.74 | 31.53 | 0.00 | 0.00 | 0.00 |
February | 22.79 | 10.52 | 12.27 | 27.05 | 28.31 | 0.00 | 0.00 | 0.00 |
March | 26.12 | 11.56 | 14.57 | 31.60 | 28.78 | 0.00 | 0.00 | 0.00 |
April | 36.01 | 18.75 | 17.26 | 49.31 | 23.98 | 0.00 | 0.00 | 0.00 |
May | 35.38 | 16.34 | 19.04 | 46.73 | 21.88 | 0.00 | 0.00 | 0.00 |
June | 37.48 | 18.74 | 18.74 | 52.71 | 17.08 | 0.00 | 0.00 | 0.00 |
July | 39.67 | 21.23 | 18.44 | 58.96 | 15.63 | 0.00 | 0.00 | 0.00 |
August | 37.22 | 20.17 | 17.05 | 56.17 | 16.25 | 0.00 | 0.00 | 0.00 |
September | 31.87 | 17.05 | 14.82 | 46.32 | 18.79 | 0.00 | 0.00 | 0.00 |
October | 24.36 | 13.30 | 11.06 | 36.35 | 21.01 | 0.00 | 0.00 | 0.00 |
November | 22.01 | 11.51 | 10.50 | 27.90 | 29.30 | 0.00 | 0.00 | 0.00 |
December | 19.43 | 10.42 | 9.01 | 24.64 | 31.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.31 | 14.95 | 14.36 | 40.19 | 23.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.10 | 9.63 | 9.01 | 23.74 | 15.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.67 | 21.23 | 19.04 | 58.96 | 31.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 293.44 | 0.00 | 293.44 | 160.06 | 1252.70 | 0.00 | 0.00 | 0.00 |
February | 368.34 | 0.00 | 368.34 | 189.43 | 1142.81 | 0.00 | 0.00 | 0.00 |
March | 451.37 | 0.00 | 451.37 | 286.44 | 1165.75 | 0.00 | 0.00 | 0.00 |
April | 520.04 | 2.00 | 518.04 | 409.60 | 926.54 | 0.00 | 0.00 | 0.00 |
May | 624.92 | 29.10 | 595.82 | 519.70 | 807.39 | 0.00 | 0.00 | 0.00 |
June | 665.88 | 65.10 | 600.78 | 680.09 | 634.13 | 0.00 | 0.00 | 0.00 |
July | 630.49 | 52.85 | 577.64 | 725.65 | 566.88 | 0.00 | 0.00 | 0.00 |
August | 523.60 | 10.48 | 513.11 | 581.45 | 598.59 | 0.00 | 0.00 | 0.00 |
September | 443.17 | 0.07 | 443.10 | 447.19 | 722.99 | 0.00 | 0.00 | 0.00 |
October | 351.54 | 0.00 | 351.54 | 392.46 | 811.44 | 0.00 | 0.00 | 0.00 |
November | 318.29 | 0.00 | 318.29 | 183.02 | 1158.64 | 0.00 | 0.00 | 0.00 |
December | 273.17 | 0.00 | 273.17 | 141.93 | 1270.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 455.72 | 13.37 | 442.35 | 394.35 | 920.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 273.17 | 0.00 | 273.17 | 141.93 | 566.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 665.88 | 65.10 | 600.78 | 725.65 | 1270.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 527.68 | 282.22 | 245.47 | 610.37 | 779.81 | 0.00 | 0.00 | 0.00 |
February | 556.65 | 255.01 | 301.65 | 599.71 | 717.61 | 0.00 | 0.00 | 0.00 |
March | 676.17 | 301.26 | 374.91 | 766.64 | 730.93 | 0.00 | 0.00 | 0.00 |
April | 864.48 | 433.55 | 430.92 | 1131.73 | 596.99 | 0.00 | 0.00 | 0.00 |
May | 815.82 | 340.46 | 475.36 | 1019.43 | 546.11 | 0.00 | 0.00 | 0.00 |
June | 810.74 | 351.77 | 458.97 | 1094.39 | 436.11 | 0.00 | 0.00 | 0.00 |
July | 918.63 | 456.49 | 462.14 | 1347.84 | 391.75 | 0.00 | 0.00 | 0.00 |
August | 907.22 | 481.88 | 425.34 | 1350.93 | 400.34 | 0.00 | 0.00 | 0.00 |
September | 660.53 | 302.68 | 357.85 | 923.20 | 466.22 | 0.00 | 0.00 | 0.00 |
October | 584.69 | 300.51 | 284.17 | 834.87 | 515.27 | 0.00 | 0.00 | 0.00 |
November | 533.01 | 270.79 | 262.22 | 613.31 | 725.60 | 0.00 | 0.00 | 0.00 |
December | 508.48 | 282.52 | 225.96 | 586.13 | 787.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697.94 | 338.93 | 359.01 | 908.70 | 590.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 508.48 | 255.01 | 225.96 | 586.13 | 391.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 918.63 | 481.88 | 475.36 | 1350.93 | 787.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1936.48 | 1420.50 | 515.98 | 2791.96 | 1203.93 | 0.00 | 0.00 | 0.00 |
February | 1521.97 | 937.46 | 584.52 | 2042.73 | 1109.37 | 0.00 | 0.00 | 0.00 |
March | 1213.37 | 586.11 | 627.25 | 1598.59 | 1162.07 | 0.00 | 0.00 | 0.00 |
April | 1013.80 | 386.57 | 627.23 | 1432.28 | 968.10 | 0.00 | 0.00 | 0.00 |
May | 721.90 | 88.84 | 633.06 | 803.53 | 883.42 | 0.00 | 0.00 | 0.00 |
June | 633.30 | 38.24 | 595.06 | 709.33 | 689.49 | 0.00 | 0.00 | 0.00 |
July | 670.84 | 75.52 | 595.32 | 895.53 | 609.38 | 0.00 | 0.00 | 0.00 |
August | 861.83 | 271.85 | 589.98 | 1347.10 | 637.58 | 0.00 | 0.00 | 0.00 |
September | 1199.23 | 607.69 | 591.54 | 1882.98 | 743.72 | 0.00 | 0.00 | 0.00 |
October | 1525.14 | 1019.60 | 505.54 | 2410.37 | 809.08 | 0.00 | 0.00 | 0.00 |
November | 1853.66 | 1308.65 | 545.00 | 2657.29 | 1116.16 | 0.00 | 0.00 | 0.00 |
December | 2068.78 | 1574.62 | 494.17 | 2999.00 | 1212.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1267.30 | 692.14 | 575.16 | 1796.93 | 927.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 633.30 | 38.24 | 494.17 | 709.33 | 609.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2068.78 | 1574.62 | 633.06 | 2999.00 | 1212.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 502.26 | 253.32 | 248.94 | 615.07 | 822.61 | 0.00 | 0.00 | 0.00 |
February | 599.20 | 276.62 | 322.58 | 695.07 | 749.63 | 0.00 | 0.00 | 0.00 |
March | 686.85 | 303.87 | 382.97 | 811.20 | 763.68 | 0.00 | 0.00 | 0.00 |
April | 946.86 | 493.03 | 453.83 | 1276.08 | 631.64 | 0.00 | 0.00 | 0.00 |
May | 930.11 | 429.62 | 500.49 | 1208.92 | 574.90 | 0.00 | 0.00 | 0.00 |
June | 985.35 | 492.66 | 492.69 | 1364.20 | 452.70 | 0.00 | 0.00 | 0.00 |
July | 1043.07 | 558.14 | 484.93 | 1535.03 | 407.42 | 0.00 | 0.00 | 0.00 |
August | 978.60 | 530.36 | 448.24 | 1462.70 | 423.70 | 0.00 | 0.00 | 0.00 |
September | 837.87 | 448.33 | 389.54 | 1205.96 | 486.89 | 0.00 | 0.00 | 0.00 |
October | 640.51 | 349.69 | 290.82 | 947.56 | 543.48 | 0.00 | 0.00 | 0.00 |
November | 578.57 | 302.63 | 275.94 | 725.93 | 757.49 | 0.00 | 0.00 | 0.00 |
December | 510.98 | 274.07 | 236.91 | 639.51 | 831.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 770.69 | 393.19 | 377.49 | 1042.32 | 619.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 502.26 | 253.32 | 236.91 | 615.07 | 407.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1043.07 | 558.14 | 500.49 | 1535.03 | 831.98 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.785942E+09 | 0.00 | 0.785942E+09 | 0.479470E+09 | 0.309873E+10 |
February | 0.891094E+09 | 0.00 | 0.891094E+09 | 0.505016E+09 | 0.254956E+10 |
March | 0.120896E+10 | 0.00 | 0.120896E+10 | 0.813586E+09 | 0.291215E+10 |
April | 0.134794E+10 | 5187996.30 | 0.134275E+10 | 0.108521E+10 | 0.226248E+10 |
May | 0.167378E+10 | 77940352.35 | 0.159584E+10 | 0.142599E+10 | 0.204587E+10 |
June | 0.172597E+10 | 0.168742E+09 | 0.155722E+10 | 0.177131E+10 | 0.156675E+10 |
July | 0.168869E+10 | 0.141540E+09 | 0.154715E+10 | 0.194134E+10 | 0.145208E+10 |
August | 0.140240E+10 | 28081717.27 | 0.137432E+10 | 0.155813E+10 | 0.152740E+10 |
September | 0.114870E+10 | 180046.04 | 0.114852E+10 | 0.117381E+10 | 0.176393E+10 |
October | 0.941559E+09 | 0.00 | 0.941559E+09 | 0.107797E+10 | 0.203185E+10 |
November | 0.825014E+09 | 0.00 | 0.825014E+09 | 0.524302E+09 | 0.277345E+10 |
December | 0.731645E+09 | 0.00 | 0.731645E+09 | 0.433884E+09 | 0.313264E+10 |
Annual Sum or Average | 0.143717E+11 | 0.421672E+09 | 0.139500E+11 | 0.127900E+11 | 0.271169E+11 |
Minimum of Months | 0.731645E+09 | 0.00 | 0.731645E+09 | 0.433884E+09 | 0.145208E+10 |
Maximum of Months | 0.172597E+10 | 0.168742E+09 | 0.159584E+10 | 0.194134E+10 | 0.313264E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141335E+10 | 0.755894E+09 | 0.657458E+09 | 0.168246E+10 | 0.194818E+10 |
February | 0.134666E+10 | 0.616914E+09 | 0.729742E+09 | 0.148687E+10 | 0.161704E+10 |
March | 0.181106E+10 | 0.806908E+09 | 0.100415E+10 | 0.208895E+10 | 0.184334E+10 |
April | 0.224072E+10 | 0.112377E+10 | 0.111695E+10 | 0.294686E+10 | 0.147174E+10 |
May | 0.218509E+10 | 0.911889E+09 | 0.127320E+10 | 0.274817E+10 | 0.139470E+10 |
June | 0.210143E+10 | 0.911775E+09 | 0.118966E+10 | 0.283996E+10 | 0.108435E+10 |
July | 0.246045E+10 | 0.122267E+10 | 0.123779E+10 | 0.360374E+10 | 0.100920E+10 |
August | 0.242990E+10 | 0.129068E+10 | 0.113922E+10 | 0.361333E+10 | 0.102889E+10 |
September | 0.171209E+10 | 0.784544E+09 | 0.927545E+09 | 0.239980E+10 | 0.114491E+10 |
October | 0.156603E+10 | 0.804899E+09 | 0.761130E+09 | 0.225401E+10 | 0.130181E+10 |
November | 0.138157E+10 | 0.701894E+09 | 0.679674E+09 | 0.163199E+10 | 0.175679E+10 |
December | 0.136192E+10 | 0.756698E+09 | 0.605224E+09 | 0.162151E+10 | 0.196358E+10 |
Annual Sum or Average | 0.220103E+11 | 0.106885E+11 | 0.113217E+11 | 0.289176E+11 | 0.175645E+11 |
Minimum of Months | 0.134666E+10 | 0.616914E+09 | 0.605224E+09 | 0.148687E+10 | 0.100920E+10 |
Maximum of Months | 0.246045E+10 | 0.129068E+10 | 0.127320E+10 | 0.361333E+10 | 0.196358E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.518668E+10 | 0.380467E+10 | 0.138201E+10 | 0.753137E+10 | 0.301055E+10 |
February | 0.368196E+10 | 0.226789E+10 | 0.141407E+10 | 0.498568E+10 | 0.249414E+10 |
March | 0.324988E+10 | 0.156985E+10 | 0.168004E+10 | 0.432568E+10 | 0.291300E+10 |
April | 0.262776E+10 | 0.100199E+10 | 0.162577E+10 | 0.372788E+10 | 0.237160E+10 |
May | 0.193354E+10 | 0.237949E+09 | 0.169559E+10 | 0.217422E+10 | 0.223457E+10 |
June | 0.164151E+10 | 99108672.29 | 0.154240E+10 | 0.184592E+10 | 0.170007E+10 |
July | 0.179677E+10 | 0.202265E+09 | 0.159451E+10 | 0.239560E+10 | 0.155886E+10 |
August | 0.230832E+10 | 0.728115E+09 | 0.158020E+10 | 0.360177E+10 | 0.162753E+10 |
September | 0.310841E+10 | 0.157514E+10 | 0.153327E+10 | 0.488478E+10 | 0.182097E+10 |
October | 0.408494E+10 | 0.273090E+10 | 0.135404E+10 | 0.647294E+10 | 0.204263E+10 |
November | 0.480468E+10 | 0.339203E+10 | 0.141265E+10 | 0.693258E+10 | 0.270496E+10 |
December | 0.554103E+10 | 0.421745E+10 | 0.132358E+10 | 0.808845E+10 | 0.303152E+10 |
Annual Sum or Average | 0.399655E+11 | 0.218273E+11 | 0.181381E+11 | 0.569669E+11 | 0.275104E+11 |
Minimum of Months | 0.164151E+10 | 99108672.29 | 0.132358E+10 | 0.184592E+10 | 0.155886E+10 |
Maximum of Months | 0.554103E+10 | 0.421745E+10 | 0.169559E+10 | 0.808845E+10 | 0.303152E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134526E+10 | 0.678490E+09 | 0.666773E+09 | 0.167795E+10 | 0.204132E+10 |
February | 0.144959E+10 | 0.669199E+09 | 0.780392E+09 | 0.170912E+10 | 0.167875E+10 |
March | 0.183965E+10 | 0.813890E+09 | 0.102576E+10 | 0.219876E+10 | 0.191039E+10 |
April | 0.245425E+10 | 0.127792E+10 | 0.117633E+10 | 0.331734E+10 | 0.154565E+10 |
May | 0.249121E+10 | 0.115068E+10 | 0.134052E+10 | 0.324909E+10 | 0.145506E+10 |
June | 0.255402E+10 | 0.127696E+10 | 0.127706E+10 | 0.353425E+10 | 0.111636E+10 |
July | 0.279376E+10 | 0.149492E+10 | 0.129884E+10 | 0.410283E+10 | 0.104239E+10 |
August | 0.262109E+10 | 0.142052E+10 | 0.120057E+10 | 0.391044E+10 | 0.108136E+10 |
September | 0.217175E+10 | 0.116207E+10 | 0.100968E+10 | 0.313077E+10 | 0.118921E+10 |
October | 0.171554E+10 | 0.936613E+09 | 0.778929E+09 | 0.255241E+10 | 0.136378E+10 |
November | 0.149966E+10 | 0.784427E+09 | 0.715232E+09 | 0.191013E+10 | 0.181877E+10 |
December | 0.136861E+10 | 0.734056E+09 | 0.634550E+09 | 0.174605E+10 | 0.206001E+10 |
Annual Sum or Average | 0.243044E+11 | 0.123998E+11 | 0.119046E+11 | 0.330391E+11 | 0.183030E+11 |
Minimum of Months | 0.134526E+10 | 0.669199E+09 | 0.634550E+09 | 0.167795E+10 | 0.104239E+10 |
Maximum of Months | 0.279376E+10 | 0.149492E+10 | 0.134052E+10 | 0.410283E+10 | 0.206001E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.261968E+09 | 0.00 | 0.261968E+09 | 0.153902E+09 | 0.109615E+10 |
February | 0.297017E+09 | 0.00 | 0.297017E+09 | 0.171576E+09 | 0.884198E+09 |
March | 0.402968E+09 | 0.00 | 0.402968E+09 | 0.282971E+09 | 0.997347E+09 |
April | 0.449291E+09 | 1729250.28 | 0.447561E+09 | 0.383346E+09 | 0.761081E+09 |
May | 0.557900E+09 | 25978888.28 | 0.531922E+09 | 0.495530E+09 | 0.693514E+09 |
June | 0.575295E+09 | 56244704.55 | 0.519050E+09 | 0.619417E+09 | 0.522385E+09 |
July | 0.562871E+09 | 47177856.02 | 0.515693E+09 | 0.671812E+09 | 0.487658E+09 |
August | 0.467445E+09 | 9360129.55 | 0.458085E+09 | 0.539324E+09 | 0.512515E+09 |
September | 0.382882E+09 | 60012.51 | 0.382822E+09 | 0.401884E+09 | 0.604464E+09 |
October | 0.313838E+09 | 0.00 | 0.313838E+09 | 0.361070E+09 | 0.710320E+09 |
November | 0.274992E+09 | 0.00 | 0.274992E+09 | 0.168607E+09 | 0.984578E+09 |
December | 0.243870E+09 | 0.00 | 0.243870E+09 | 0.137448E+09 | 0.110999E+10 |
Annual Sum or Average | 0.479034E+10 | 0.140551E+09 | 0.464979E+10 | 0.438689E+10 | 0.936421E+10 |
Minimum of Months | 0.243870E+09 | 0.00 | 0.243870E+09 | 0.137448E+09 | 0.487658E+09 |
Maximum of Months | 0.575295E+09 | 56244704.55 | 0.531922E+09 | 0.671812E+09 | 0.110999E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.261979E+09 | 0.00 | 0.261979E+09 | 0.153907E+09 | 0.109622E+10 |
February | 0.297029E+09 | 0.00 | 0.297029E+09 | 0.171580E+09 | 0.884251E+09 |
March | 0.402984E+09 | 0.00 | 0.402984E+09 | 0.282978E+09 | 0.997407E+09 |
April | 0.449310E+09 | 1729296.77 | 0.447581E+09 | 0.383362E+09 | 0.761127E+09 |
May | 0.557923E+09 | 25979586.60 | 0.531944E+09 | 0.495545E+09 | 0.693556E+09 |
June | 0.575318E+09 | 56246216.43 | 0.519072E+09 | 0.619438E+09 | 0.522417E+09 |
July | 0.562895E+09 | 47179124.17 | 0.515716E+09 | 0.671839E+09 | 0.487686E+09 |
August | 0.467466E+09 | 9360381.16 | 0.458106E+09 | 0.539349E+09 | 0.512545E+09 |
September | 0.382898E+09 | 60014.12 | 0.382838E+09 | 0.401901E+09 | 0.604499E+09 |
October | 0.313851E+09 | 0.00 | 0.313851E+09 | 0.361086E+09 | 0.710360E+09 |
November | 0.275003E+09 | 0.00 | 0.275003E+09 | 0.168612E+09 | 0.984636E+09 |
December | 0.243881E+09 | 0.00 | 0.243881E+09 | 0.137453E+09 | 0.111006E+10 |
Annual Sum or Average | 0.479054E+10 | 0.140555E+09 | 0.464998E+10 | 0.438705E+10 | 0.936476E+10 |
Minimum of Months | 0.243881E+09 | 0.00 | 0.243881E+09 | 0.137453E+09 | 0.487686E+09 |
Maximum of Months | 0.575318E+09 | 56246216.43 | 0.531944E+09 | 0.671839E+09 | 0.111006E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.261979E+09 | 0.00 | 0.261979E+09 | 0.153907E+09 | 0.109622E+10 |
February | 0.297029E+09 | 0.00 | 0.297029E+09 | 0.171580E+09 | 0.884251E+09 |
March | 0.402984E+09 | 0.00 | 0.402984E+09 | 0.282978E+09 | 0.997407E+09 |
April | 0.449310E+09 | 1729296.77 | 0.447581E+09 | 0.383362E+09 | 0.761127E+09 |
May | 0.557923E+09 | 25979586.60 | 0.531944E+09 | 0.495545E+09 | 0.693556E+09 |
June | 0.575318E+09 | 56246216.43 | 0.519072E+09 | 0.619438E+09 | 0.522417E+09 |
July | 0.562895E+09 | 47179124.17 | 0.515716E+09 | 0.671839E+09 | 0.487686E+09 |
August | 0.467466E+09 | 9360381.16 | 0.458106E+09 | 0.539349E+09 | 0.512545E+09 |
September | 0.382898E+09 | 60014.12 | 0.382838E+09 | 0.401901E+09 | 0.604499E+09 |
October | 0.313851E+09 | 0.00 | 0.313851E+09 | 0.361086E+09 | 0.710360E+09 |
November | 0.275003E+09 | 0.00 | 0.275003E+09 | 0.168612E+09 | 0.984636E+09 |
December | 0.243881E+09 | 0.00 | 0.243881E+09 | 0.137453E+09 | 0.111006E+10 |
Annual Sum or Average | 0.479054E+10 | 0.140555E+09 | 0.464998E+10 | 0.438705E+10 | 0.936476E+10 |
Minimum of Months | 0.243881E+09 | 0.00 | 0.243881E+09 | 0.137453E+09 | 0.487686E+09 |
Maximum of Months | 0.575318E+09 | 56246216.43 | 0.531944E+09 | 0.671839E+09 | 0.111006E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135957E+10 | 0.727129E+09 | 0.632444E+09 | 0.158762E+10 | 0.203695E+10 |
February | 0.129541E+10 | 0.593438E+09 | 0.701977E+09 | 0.142716E+10 | 0.165745E+10 |
March | 0.174214E+10 | 0.776202E+09 | 0.965943E+09 | 0.201791E+10 | 0.186697E+10 |
April | 0.215546E+10 | 0.108100E+10 | 0.107446E+10 | 0.286571E+10 | 0.148266E+10 |
May | 0.210195E+10 | 0.877188E+09 | 0.122476E+10 | 0.267185E+10 | 0.139976E+10 |
June | 0.202148E+10 | 0.877078E+09 | 0.114440E+10 | 0.277590E+10 | 0.106902E+10 |
July | 0.236684E+10 | 0.117614E+10 | 0.119070E+10 | 0.350622E+10 | 0.101421E+10 |
August | 0.233744E+10 | 0.124157E+10 | 0.109588E+10 | 0.351139E+10 | 0.103856E+10 |
September | 0.164695E+10 | 0.754689E+09 | 0.892256E+09 | 0.232552E+10 | 0.116768E+10 |
October | 0.150644E+10 | 0.774269E+09 | 0.732173E+09 | 0.216951E+10 | 0.134598E+10 |
November | 0.132900E+10 | 0.675184E+09 | 0.653815E+09 | 0.154333E+10 | 0.183738E+10 |
December | 0.131010E+10 | 0.727903E+09 | 0.582198E+09 | 0.152609E+10 | 0.205254E+10 |
Annual Sum or Average | 0.211728E+11 | 0.102818E+11 | 0.108910E+11 | 0.279282E+11 | 0.179692E+11 |
Minimum of Months | 0.129541E+10 | 0.593438E+09 | 0.582198E+09 | 0.142716E+10 | 0.101421E+10 |
Maximum of Months | 0.236684E+10 | 0.124157E+10 | 0.122476E+10 | 0.351139E+10 | 0.205254E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53756276.65 | 28750020.07 | 25006256.58 | 62773010.33 | 80539150.96 |
February | 51219536.05 | 23463985.50 | 27755550.55 | 56428676.72 | 65533959.98 |
March | 68882820.91 | 30690319.97 | 38192500.94 | 79786482.90 | 73818315.41 |
April | 85225060.99 | 42741889.79 | 42483171.20 | 0.113308E+09 | 58623009.97 |
May | 83109119.40 | 34683214.02 | 48425905.38 | 0.105643E+09 | 55345405.63 |
June | 79927343.63 | 34678888.28 | 45248455.35 | 0.109756E+09 | 42268239.69 |
July | 93582551.13 | 46503441.19 | 47079109.94 | 0.138633E+09 | 40100957.91 |
August | 92420346.18 | 49090365.00 | 43329981.18 | 0.138837E+09 | 41063705.74 |
September | 65118747.34 | 29839732.21 | 35279015.14 | 91949043.53 | 46169165.55 |
October | 59563348.69 | 30613901.41 | 28949447.28 | 85780615.46 | 53218715.40 |
November | 52547403.78 | 26696152.82 | 25851250.96 | 61021996.20 | 72648436.63 |
December | 51800200.31 | 28780626.60 | 23019573.71 | 60340176.11 | 81155472.96 |
Annual Sum or Average | 0.837153E+09 | 0.406533E+09 | 0.430620E+09 | 0.110426E+10 | 0.710485E+09 |
Minimum of Months | 51219536.05 | 23463985.50 | 23019573.71 | 56428676.72 | 40100957.91 |
Maximum of Months | 93582551.13 | 49090365.00 | 48425905.38 | 0.138837E+09 | 81155472.96 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172886E+10 | 0.126820E+10 | 0.460665E+09 | 0.250833E+10 | 0.111335E+10 |
February | 0.122730E+10 | 0.755948E+09 | 0.471349E+09 | 0.167583E+10 | 0.897530E+09 |
March | 0.108328E+10 | 0.523271E+09 | 0.560006E+09 | 0.146471E+10 | 0.101673E+10 |
April | 0.875911E+09 | 0.333991E+09 | 0.541921E+09 | 0.126925E+10 | 0.810848E+09 |
May | 0.644509E+09 | 79314692.39 | 0.565194E+09 | 0.757710E+09 | 0.749080E+09 |
June | 0.547168E+09 | 33035549.07 | 0.514132E+09 | 0.651590E+09 | 0.556050E+09 |
July | 0.598921E+09 | 67420449.29 | 0.531501E+09 | 0.826080E+09 | 0.520634E+09 |
August | 0.769431E+09 | 0.242700E+09 | 0.526731E+09 | 0.122516E+10 | 0.554696E+09 |
September | 0.103612E+10 | 0.525035E+09 | 0.511086E+09 | 0.164554E+10 | 0.644537E+09 |
October | 0.136162E+10 | 0.910281E+09 | 0.451344E+09 | 0.216646E+10 | 0.744016E+09 |
November | 0.160153E+10 | 0.113065E+10 | 0.470877E+09 | 0.231447E+10 | 0.996577E+09 |
December | 0.184698E+10 | 0.140579E+10 | 0.441190E+09 | 0.269494E+10 | 0.112247E+10 |
Annual Sum or Average | 0.133216E+11 | 0.727563E+10 | 0.604600E+10 | 0.192001E+11 | 0.972652E+10 |
Minimum of Months | 0.547168E+09 | 33035549.07 | 0.441190E+09 | 0.651590E+09 | 0.520634E+09 |
Maximum of Months | 0.184698E+10 | 0.140579E+10 | 0.565194E+09 | 0.269494E+10 | 0.112247E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172886E+10 | 0.126820E+10 | 0.460665E+09 | 0.250833E+10 | 0.111335E+10 |
February | 0.122730E+10 | 0.755948E+09 | 0.471349E+09 | 0.167583E+10 | 0.897530E+09 |
March | 0.108328E+10 | 0.523271E+09 | 0.560006E+09 | 0.146471E+10 | 0.101673E+10 |
April | 0.875911E+09 | 0.333991E+09 | 0.541921E+09 | 0.126925E+10 | 0.810848E+09 |
May | 0.644509E+09 | 79314692.39 | 0.565194E+09 | 0.757710E+09 | 0.749080E+09 |
June | 0.547168E+09 | 33035549.07 | 0.514132E+09 | 0.651590E+09 | 0.556050E+09 |
July | 0.598921E+09 | 67420449.29 | 0.531501E+09 | 0.826080E+09 | 0.520634E+09 |
August | 0.769431E+09 | 0.242700E+09 | 0.526731E+09 | 0.122516E+10 | 0.554696E+09 |
September | 0.103612E+10 | 0.525035E+09 | 0.511086E+09 | 0.164554E+10 | 0.644537E+09 |
October | 0.136162E+10 | 0.910281E+09 | 0.451344E+09 | 0.216646E+10 | 0.744016E+09 |
November | 0.160153E+10 | 0.113065E+10 | 0.470877E+09 | 0.231447E+10 | 0.996577E+09 |
December | 0.184698E+10 | 0.140579E+10 | 0.441190E+09 | 0.269494E+10 | 0.112247E+10 |
Annual Sum or Average | 0.133216E+11 | 0.727563E+10 | 0.604600E+10 | 0.192001E+11 | 0.972652E+10 |
Minimum of Months | 0.547168E+09 | 33035549.07 | 0.441190E+09 | 0.651590E+09 | 0.520634E+09 |
Maximum of Months | 0.184698E+10 | 0.140579E+10 | 0.565194E+09 | 0.269494E+10 | 0.112247E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172875E+10 | 0.126812E+10 | 0.460636E+09 | 0.250817E+10 | 0.111328E+10 |
February | 0.122722E+10 | 0.755901E+09 | 0.471320E+09 | 0.167572E+10 | 0.897474E+09 |
March | 0.108321E+10 | 0.523238E+09 | 0.559970E+09 | 0.146461E+10 | 0.101667E+10 |
April | 0.875856E+09 | 0.333969E+09 | 0.541886E+09 | 0.126917E+10 | 0.810796E+09 |
May | 0.644468E+09 | 79309680.15 | 0.565158E+09 | 0.757662E+09 | 0.749033E+09 |
June | 0.547133E+09 | 33033461.41 | 0.514100E+09 | 0.651549E+09 | 0.556015E+09 |
July | 0.598884E+09 | 67416188.70 | 0.531467E+09 | 0.826028E+09 | 0.520601E+09 |
August | 0.769383E+09 | 0.242685E+09 | 0.526698E+09 | 0.122508E+10 | 0.554661E+09 |
September | 0.103606E+10 | 0.525002E+09 | 0.511054E+09 | 0.164544E+10 | 0.644497E+09 |
October | 0.136154E+10 | 0.910223E+09 | 0.451315E+09 | 0.216633E+10 | 0.743969E+09 |
November | 0.160143E+10 | 0.113058E+10 | 0.470847E+09 | 0.231433E+10 | 0.996514E+09 |
December | 0.184686E+10 | 0.140570E+10 | 0.441162E+09 | 0.269477E+10 | 0.112240E+10 |
Annual Sum or Average | 0.133208E+11 | 0.727517E+10 | 0.604561E+10 | 0.191989E+11 | 0.972591E+10 |
Minimum of Months | 0.547133E+09 | 33033461.41 | 0.441162E+09 | 0.651549E+09 | 0.520601E+09 |
Maximum of Months | 0.184686E+10 | 0.140570E+10 | 0.565158E+09 | 0.269477E+10 | 0.112240E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129408E+10 | 0.652673E+09 | 0.641406E+09 | 0.160798E+10 | 0.213608E+10 |
February | 0.139444E+10 | 0.643735E+09 | 0.750702E+09 | 0.165531E+10 | 0.173200E+10 |
March | 0.176966E+10 | 0.782921E+09 | 0.986734E+09 | 0.214047E+10 | 0.194952E+10 |
April | 0.236087E+10 | 0.122930E+10 | 0.113157E+10 | 0.323247E+10 | 0.157174E+10 |
May | 0.239642E+10 | 0.110690E+10 | 0.128952E+10 | 0.316570E+10 | 0.148216E+10 |
June | 0.245685E+10 | 0.122837E+10 | 0.122848E+10 | 0.345557E+10 | 0.111965E+10 |
July | 0.268747E+10 | 0.143803E+10 | 0.124943E+10 | 0.399422E+10 | 0.105854E+10 |
August | 0.252137E+10 | 0.136647E+10 | 0.115490E+10 | 0.380527E+10 | 0.110071E+10 |
September | 0.208912E+10 | 0.111785E+10 | 0.971265E+09 | 0.303666E+10 | 0.123190E+10 |
October | 0.165027E+10 | 0.900974E+09 | 0.749296E+09 | 0.246233E+10 | 0.142291E+10 |
November | 0.144260E+10 | 0.754579E+09 | 0.688021E+09 | 0.182895E+10 | 0.192059E+10 |
December | 0.131653E+10 | 0.706125E+09 | 0.610409E+09 | 0.166932E+10 | 0.216197E+10 |
Annual Sum or Average | 0.233797E+11 | 0.119279E+11 | 0.114517E+11 | 0.320542E+11 | 0.188878E+11 |
Minimum of Months | 0.129408E+10 | 0.643735E+09 | 0.610409E+09 | 0.160798E+10 | 0.105854E+10 |
Maximum of Months | 0.268747E+10 | 0.143803E+10 | 0.128952E+10 | 0.399422E+10 | 0.216197E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51166564.13 | 25806011.66 | 25360552.48 | 63577704.25 | 84458647.75 |
February | 55134634.38 | 25452631.40 | 29682002.98 | 65449043.97 | 68481881.20 |
March | 69970390.27 | 30955887.14 | 39014503.12 | 84631767.78 | 77082186.63 |
April | 93346509.46 | 48605183.06 | 44741326.40 | 0.127809E+09 | 62144999.90 |
May | 94752110.83 | 43765657.45 | 50986453.38 | 0.125168E+09 | 58603133.13 |
June | 97141393.60 | 48568644.04 | 48572749.57 | 0.136630E+09 | 44270021.01 |
July | 0.106260E+09 | 56858395.59 | 49401293.77 | 0.157928E+09 | 41853738.90 |
August | 99692334.42 | 54028886.99 | 45663447.43 | 0.150457E+09 | 43520954.51 |
September | 82601628.21 | 44198754.81 | 38402873.41 | 0.120067E+09 | 48708170.84 |
October | 65249983.87 | 35623575.88 | 29626408.00 | 97358054.35 | 56260456.47 |
November | 57038942.33 | 29835268.09 | 27203674.24 | 72314905.25 | 75938572.40 |
December | 52054398.58 | 27919442.74 | 24134955.84 | 66003121.11 | 85482157.68 |
Annual Sum or Average | 0.924409E+09 | 0.471618E+09 | 0.452790E+09 | 0.126739E+10 | 0.746805E+09 |
Minimum of Months | 51166564.13 | 25452631.40 | 24134955.84 | 63577704.25 | 41853738.90 |
Maximum of Months | 0.106260E+09 | 56858395.59 | 50986453.38 | 0.157928E+09 | 85482157.68 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.785942E+09 | 0.00 | 0.785942E+09 | 0.428711E+09 | 0.335524E+10 |
February | 0.891094E+09 | 0.00 | 0.891094E+09 | 0.458269E+09 | 0.276469E+10 |
March | 0.120896E+10 | 0.00 | 0.120896E+10 | 0.767213E+09 | 0.312235E+10 |
April | 0.134794E+10 | 5187996.30 | 0.134275E+10 | 0.106167E+10 | 0.240158E+10 |
May | 0.167378E+10 | 77940352.35 | 0.159584E+10 | 0.139196E+10 | 0.216251E+10 |
June | 0.172597E+10 | 0.168742E+09 | 0.155722E+10 | 0.176278E+10 | 0.164368E+10 |
July | 0.168869E+10 | 0.141540E+09 | 0.154715E+10 | 0.194358E+10 | 0.151834E+10 |
August | 0.140240E+10 | 28081717.27 | 0.137432E+10 | 0.155735E+10 | 0.160325E+10 |
September | 0.114870E+10 | 180046.04 | 0.114852E+10 | 0.115910E+10 | 0.187398E+10 |
October | 0.941559E+09 | 0.00 | 0.941559E+09 | 0.105116E+10 | 0.217336E+10 |
November | 0.825014E+09 | 0.00 | 0.825014E+09 | 0.474379E+09 | 0.300320E+10 |
December | 0.731645E+09 | 0.00 | 0.731645E+09 | 0.380152E+09 | 0.340379E+10 |
Annual Sum or Average | 0.143717E+11 | 0.421672E+09 | 0.139500E+11 | 0.124363E+11 | 0.290260E+11 |
Minimum of Months | 0.731645E+09 | 0.00 | 0.731645E+09 | 0.380152E+09 | 0.151834E+10 |
Maximum of Months | 0.172597E+10 | 0.168742E+09 | 0.159584E+10 | 0.194358E+10 | 0.340379E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141335E+10 | 0.755894E+09 | 0.657458E+09 | 0.163482E+10 | 0.208865E+10 |
February | 0.134666E+10 | 0.616914E+09 | 0.729742E+09 | 0.145081E+10 | 0.173604E+10 |
March | 0.181106E+10 | 0.806908E+09 | 0.100415E+10 | 0.205338E+10 | 0.195772E+10 |
April | 0.224072E+10 | 0.112377E+10 | 0.111695E+10 | 0.293346E+10 | 0.154739E+10 |
May | 0.218509E+10 | 0.911889E+09 | 0.127320E+10 | 0.273045E+10 | 0.146271E+10 |
June | 0.210143E+10 | 0.911775E+09 | 0.118966E+10 | 0.283666E+10 | 0.113040E+10 |
July | 0.246045E+10 | 0.122267E+10 | 0.123779E+10 | 0.361007E+10 | 0.104925E+10 |
August | 0.242990E+10 | 0.129068E+10 | 0.113922E+10 | 0.361833E+10 | 0.107227E+10 |
September | 0.171209E+10 | 0.784544E+09 | 0.927545E+09 | 0.239293E+10 | 0.120845E+10 |
October | 0.156603E+10 | 0.804899E+09 | 0.761130E+09 | 0.223612E+10 | 0.138009E+10 |
November | 0.138157E+10 | 0.701894E+09 | 0.679674E+09 | 0.158971E+10 | 0.188075E+10 |
December | 0.136192E+10 | 0.756698E+09 | 0.605224E+09 | 0.156990E+10 | 0.210993E+10 |
Annual Sum or Average | 0.220103E+11 | 0.106885E+11 | 0.113217E+11 | 0.286566E+11 | 0.186237E+11 |
Minimum of Months | 0.134666E+10 | 0.616914E+09 | 0.605224E+09 | 0.145081E+10 | 0.104925E+10 |
Maximum of Months | 0.246045E+10 | 0.129068E+10 | 0.127320E+10 | 0.361833E+10 | 0.210993E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.518668E+10 | 0.380467E+10 | 0.138201E+10 | 0.747798E+10 | 0.322461E+10 |
February | 0.368196E+10 | 0.226789E+10 | 0.141407E+10 | 0.494177E+10 | 0.268379E+10 |
March | 0.324988E+10 | 0.156985E+10 | 0.168004E+10 | 0.428166E+10 | 0.311249E+10 |
April | 0.262776E+10 | 0.100199E+10 | 0.162577E+10 | 0.371247E+10 | 0.250932E+10 |
May | 0.193354E+10 | 0.237949E+09 | 0.169559E+10 | 0.215216E+10 | 0.236616E+10 |
June | 0.164151E+10 | 99108672.29 | 0.154240E+10 | 0.183858E+10 | 0.178715E+10 |
July | 0.179677E+10 | 0.202265E+09 | 0.159451E+10 | 0.239860E+10 | 0.163217E+10 |
August | 0.230832E+10 | 0.728115E+09 | 0.158020E+10 | 0.360806E+10 | 0.170769E+10 |
September | 0.310841E+10 | 0.157514E+10 | 0.153327E+10 | 0.488068E+10 | 0.192773E+10 |
October | 0.408494E+10 | 0.273090E+10 | 0.135404E+10 | 0.645594E+10 | 0.216705E+10 |
November | 0.480468E+10 | 0.339203E+10 | 0.141265E+10 | 0.688771E+10 | 0.289310E+10 |
December | 0.554103E+10 | 0.421745E+10 | 0.132358E+10 | 0.803252E+10 | 0.324741E+10 |
Annual Sum or Average | 0.399655E+11 | 0.218273E+11 | 0.181381E+11 | 0.566681E+11 | 0.292587E+11 |
Minimum of Months | 0.164151E+10 | 99108672.29 | 0.132358E+10 | 0.183858E+10 | 0.163217E+10 |
Maximum of Months | 0.554103E+10 | 0.421745E+10 | 0.169559E+10 | 0.803252E+10 | 0.324741E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134526E+10 | 0.678490E+09 | 0.666773E+09 | 0.164739E+10 | 0.220328E+10 |
February | 0.144959E+10 | 0.669199E+09 | 0.780392E+09 | 0.168151E+10 | 0.181351E+10 |
March | 0.183965E+10 | 0.813890E+09 | 0.102576E+10 | 0.217271E+10 | 0.204543E+10 |
April | 0.245425E+10 | 0.127792E+10 | 0.117633E+10 | 0.330760E+10 | 0.163722E+10 |
May | 0.249121E+10 | 0.115068E+10 | 0.134052E+10 | 0.323797E+10 | 0.153981E+10 |
June | 0.255402E+10 | 0.127696E+10 | 0.127706E+10 | 0.353600E+10 | 0.117340E+10 |
July | 0.279376E+10 | 0.149492E+10 | 0.129884E+10 | 0.411143E+10 | 0.109124E+10 |
August | 0.262109E+10 | 0.142052E+10 | 0.120057E+10 | 0.391769E+10 | 0.113483E+10 |
September | 0.217175E+10 | 0.116207E+10 | 0.100968E+10 | 0.312585E+10 | 0.126201E+10 |
October | 0.171554E+10 | 0.936613E+09 | 0.778929E+09 | 0.253794E+10 | 0.145567E+10 |
November | 0.149966E+10 | 0.784427E+09 | 0.715232E+09 | 0.188161E+10 | 0.196341E+10 |
December | 0.136861E+10 | 0.734056E+09 | 0.634550E+09 | 0.171285E+10 | 0.222838E+10 |
Annual Sum or Average | 0.243044E+11 | 0.123998E+11 | 0.119046E+11 | 0.328706E+11 | 0.195482E+11 |
Minimum of Months | 0.134526E+10 | 0.669199E+09 | 0.634550E+09 | 0.164739E+10 | 0.109124E+10 |
Maximum of Months | 0.279376E+10 | 0.149492E+10 | 0.134052E+10 | 0.411143E+10 | 0.222838E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 179.01 | 1156.93 | 293.44 | 0.00 | 293.44 | 0.00 | 0.00 |
February | 208.75 | 1053.89 | 368.34 | 0.00 | 368.34 | 0.00 | 0.00 |
March | 303.76 | 1087.27 | 451.37 | 0.00 | 451.37 | 0.00 | 0.00 |
April | 418.68 | 872.87 | 520.04 | 2.00 | 518.04 | 0.00 | 0.00 |
May | 532.40 | 763.84 | 624.92 | 29.10 | 595.82 | 0.00 | 0.00 |
June | 683.37 | 604.46 | 665.88 | 65.10 | 600.78 | 0.00 | 0.00 |
July | 724.81 | 542.14 | 630.49 | 52.85 | 577.64 | 0.00 | 0.00 |
August | 581.74 | 570.27 | 523.60 | 10.48 | 513.11 | 0.00 | 0.00 |
September | 452.86 | 680.53 | 443.17 | 0.07 | 443.10 | 0.00 | 0.00 |
October | 402.47 | 758.61 | 351.54 | 0.00 | 351.54 | 0.00 | 0.00 |
November | 202.28 | 1070.00 | 318.29 | 0.00 | 318.29 | 0.00 | 0.00 |
December | 161.99 | 1169.60 | 273.17 | 0.00 | 273.17 | 0.00 | 0.00 |
Annual Sum or Average | 405.57 | 859.87 | 455.72 | 13.37 | 442.35 | 0.00 | 0.00 |
Minimum of Months | 161.99 | 542.14 | 273.17 | 0.00 | 273.17 | 0.00 | 0.00 |
Maximum of Months | 724.81 | 1169.60 | 665.88 | 65.10 | 600.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 628.16 | 727.37 | 527.68 | 282.22 | 245.47 | 0.00 | 0.00 |
February | 614.61 | 668.42 | 556.65 | 255.01 | 301.65 | 0.00 | 0.00 |
March | 779.92 | 688.23 | 676.17 | 301.26 | 374.91 | 0.00 | 0.00 |
April | 1136.91 | 567.80 | 864.48 | 433.55 | 430.92 | 0.00 | 0.00 |
May | 1026.05 | 520.72 | 815.82 | 340.46 | 475.36 | 0.00 | 0.00 |
June | 1095.66 | 418.35 | 810.74 | 351.77 | 458.97 | 0.00 | 0.00 |
July | 1345.48 | 376.79 | 918.63 | 456.49 | 462.14 | 0.00 | 0.00 |
August | 1349.06 | 384.14 | 907.22 | 481.88 | 425.34 | 0.00 | 0.00 |
September | 925.85 | 441.71 | 660.53 | 302.68 | 357.85 | 0.00 | 0.00 |
October | 841.55 | 486.04 | 584.69 | 300.51 | 284.17 | 0.00 | 0.00 |
November | 629.62 | 677.77 | 533.01 | 270.79 | 262.22 | 0.00 | 0.00 |
December | 605.40 | 733.12 | 508.48 | 282.52 | 225.96 | 0.00 | 0.00 |
Annual Sum or Average | 916.97 | 556.97 | 697.94 | 338.93 | 359.01 | 0.00 | 0.00 |
Minimum of Months | 605.40 | 376.79 | 508.48 | 255.01 | 225.96 | 0.00 | 0.00 |
Maximum of Months | 1349.06 | 733.12 | 918.63 | 481.88 | 475.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2811.89 | 1124.01 | 1936.48 | 1420.50 | 515.98 | 0.00 | 0.00 |
February | 2060.88 | 1030.98 | 1521.97 | 937.46 | 584.52 | 0.00 | 0.00 |
March | 1615.02 | 1087.59 | 1213.37 | 586.11 | 627.25 | 0.00 | 0.00 |
April | 1438.22 | 914.97 | 1013.80 | 386.57 | 627.23 | 0.00 | 0.00 |
May | 811.76 | 834.29 | 721.90 | 88.84 | 633.06 | 0.00 | 0.00 |
June | 712.16 | 655.89 | 633.30 | 38.24 | 595.06 | 0.00 | 0.00 |
July | 894.41 | 582.01 | 670.84 | 75.52 | 595.32 | 0.00 | 0.00 |
August | 1344.75 | 607.65 | 861.83 | 271.85 | 589.98 | 0.00 | 0.00 |
September | 1884.56 | 702.54 | 1199.23 | 607.69 | 591.54 | 0.00 | 0.00 |
October | 2416.72 | 762.63 | 1525.14 | 1019.60 | 505.54 | 0.00 | 0.00 |
November | 2674.61 | 1043.58 | 1853.66 | 1308.65 | 545.00 | 0.00 | 0.00 |
December | 3019.88 | 1131.84 | 2068.78 | 1574.62 | 494.17 | 0.00 | 0.00 |
Annual Sum or Average | 1806.41 | 872.35 | 1267.30 | 692.14 | 575.16 | 0.00 | 0.00 |
Minimum of Months | 712.16 | 582.01 | 633.30 | 38.24 | 494.17 | 0.00 | 0.00 |
Maximum of Months | 3019.88 | 1131.84 | 2068.78 | 1574.62 | 633.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 626.48 | 762.14 | 502.26 | 253.32 | 248.94 | 0.00 | 0.00 |
February | 706.48 | 693.93 | 599.20 | 276.62 | 322.58 | 0.00 | 0.00 |
March | 820.92 | 713.26 | 686.85 | 303.87 | 382.97 | 0.00 | 0.00 |
April | 1279.84 | 596.32 | 946.86 | 493.03 | 453.83 | 0.00 | 0.00 |
May | 1213.07 | 543.26 | 930.11 | 429.62 | 500.49 | 0.00 | 0.00 |
June | 1363.52 | 430.69 | 985.35 | 492.66 | 492.69 | 0.00 | 0.00 |
July | 1531.82 | 389.18 | 1043.07 | 558.14 | 484.93 | 0.00 | 0.00 |
August | 1459.99 | 403.73 | 978.60 | 530.36 | 448.24 | 0.00 | 0.00 |
September | 1207.86 | 458.80 | 837.87 | 448.33 | 389.54 | 0.00 | 0.00 |
October | 952.96 | 509.18 | 640.51 | 349.69 | 290.82 | 0.00 | 0.00 |
November | 736.93 | 701.69 | 578.57 | 302.63 | 275.94 | 0.00 | 0.00 |
December | 651.90 | 769.12 | 510.98 | 274.07 | 236.91 | 0.00 | 0.00 |
Annual Sum or Average | 1047.66 | 580.39 | 770.69 | 393.19 | 377.49 | 0.00 | 0.00 |
Minimum of Months | 626.48 | 389.18 | 502.26 | 253.32 | 236.91 | 0.00 | 0.00 |
Maximum of Months | 1531.82 | 769.12 | 1043.07 | 558.14 | 500.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 172.38 | 1227.82 | 293.43 | 0.00 | 293.43 | 0.00 | 0.00 |
February | 212.77 | 1096.52 | 368.33 | 0.00 | 368.33 | 0.00 | 0.00 |
March | 316.95 | 1117.14 | 451.37 | 0.00 | 451.37 | 0.00 | 0.00 |
April | 443.70 | 880.92 | 520.03 | 2.00 | 518.03 | 0.00 | 0.00 |
May | 555.04 | 776.82 | 624.91 | 29.10 | 595.81 | 0.00 | 0.00 |
June | 716.93 | 604.64 | 665.87 | 65.10 | 600.77 | 0.00 | 0.00 |
July | 752.50 | 546.23 | 630.47 | 52.84 | 577.63 | 0.00 | 0.00 |
August | 604.10 | 574.08 | 523.59 | 10.48 | 513.10 | 0.00 | 0.00 |
September | 465.16 | 699.64 | 443.16 | 0.07 | 443.09 | 0.00 | 0.00 |
October | 404.44 | 795.64 | 351.53 | 0.00 | 351.53 | 0.00 | 0.00 |
November | 195.15 | 1139.60 | 318.29 | 0.00 | 318.29 | 0.00 | 0.00 |
December | 153.96 | 1243.32 | 273.16 | 0.00 | 273.16 | 0.00 | 0.00 |
Annual Sum or Average | 417.33 | 890.85 | 455.71 | 13.37 | 442.34 | 0.00 | 0.00 |
Minimum of Months | 153.96 | 546.23 | 273.16 | 0.00 | 273.16 | 0.00 | 0.00 |
Maximum of Months | 752.50 | 1243.32 | 665.87 | 65.10 | 600.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 616.19 | 790.58 | 527.68 | 282.21 | 245.46 | 0.00 | 0.00 |
February | 613.26 | 712.21 | 556.64 | 255.00 | 301.64 | 0.00 | 0.00 |
March | 783.19 | 724.61 | 676.16 | 301.26 | 374.90 | 0.00 | 0.00 |
April | 1149.31 | 594.63 | 864.46 | 433.54 | 430.92 | 0.00 | 0.00 |
May | 1037.00 | 543.28 | 815.81 | 340.45 | 475.35 | 0.00 | 0.00 |
June | 1113.29 | 428.74 | 810.73 | 351.76 | 458.97 | 0.00 | 0.00 |
July | 1360.83 | 393.63 | 918.61 | 456.48 | 462.13 | 0.00 | 0.00 |
August | 1362.84 | 403.09 | 907.21 | 481.88 | 425.33 | 0.00 | 0.00 |
September | 932.67 | 468.31 | 660.52 | 302.67 | 357.85 | 0.00 | 0.00 |
October | 842.03 | 522.40 | 584.68 | 300.51 | 284.17 | 0.00 | 0.00 |
November | 618.96 | 736.89 | 533.00 | 270.79 | 262.22 | 0.00 | 0.00 |
December | 592.30 | 796.63 | 508.48 | 282.51 | 225.96 | 0.00 | 0.00 |
Annual Sum or Average | 920.61 | 592.33 | 697.93 | 338.92 | 359.01 | 0.00 | 0.00 |
Minimum of Months | 592.30 | 393.63 | 508.48 | 255.00 | 225.96 | 0.00 | 0.00 |
Maximum of Months | 1362.84 | 796.63 | 918.61 | 481.88 | 475.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2809.45 | 1247.00 | 1936.41 | 1420.44 | 515.97 | 0.00 | 0.00 |
February | 2078.11 | 1112.99 | 1521.91 | 937.42 | 584.50 | 0.00 | 0.00 |
March | 1640.54 | 1138.79 | 1213.32 | 586.09 | 627.23 | 0.00 | 0.00 |
April | 1469.01 | 938.46 | 1013.76 | 386.55 | 627.21 | 0.00 | 0.00 |
May | 848.67 | 839.01 | 721.88 | 88.84 | 633.04 | 0.00 | 0.00 |
June | 754.14 | 643.56 | 633.28 | 38.23 | 595.05 | 0.00 | 0.00 |
July | 925.25 | 583.14 | 670.82 | 75.51 | 595.31 | 0.00 | 0.00 |
August | 1372.24 | 621.29 | 861.80 | 271.84 | 589.96 | 0.00 | 0.00 |
September | 1904.52 | 745.98 | 1199.19 | 607.67 | 591.52 | 0.00 | 0.00 |
October | 2426.54 | 833.33 | 1525.08 | 1019.56 | 505.53 | 0.00 | 0.00 |
November | 2678.73 | 1153.42 | 1853.58 | 1308.60 | 544.99 | 0.00 | 0.00 |
December | 3018.47 | 1257.22 | 2068.70 | 1574.55 | 494.15 | 0.00 | 0.00 |
Annual Sum or Average | 1826.45 | 925.26 | 1267.25 | 692.11 | 575.14 | 0.00 | 0.00 |
Minimum of Months | 754.14 | 583.14 | 633.28 | 38.23 | 494.15 | 0.00 | 0.00 |
Maximum of Months | 3018.47 | 1257.22 | 2068.70 | 1574.55 | 633.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 624.09 | 829.05 | 502.26 | 253.31 | 248.94 | 0.00 | 0.00 |
February | 711.29 | 744.25 | 599.19 | 276.62 | 322.58 | 0.00 | 0.00 |
March | 830.76 | 756.65 | 686.84 | 303.87 | 382.97 | 0.00 | 0.00 |
April | 1296.41 | 630.36 | 946.84 | 493.02 | 453.83 | 0.00 | 0.00 |
May | 1228.67 | 575.25 | 930.10 | 429.61 | 500.49 | 0.00 | 0.00 |
June | 1385.88 | 449.04 | 985.34 | 492.65 | 492.69 | 0.00 | 0.00 |
July | 1550.24 | 410.84 | 1043.06 | 558.13 | 484.93 | 0.00 | 0.00 |
August | 1476.90 | 427.21 | 978.59 | 530.35 | 448.24 | 0.00 | 0.00 |
September | 1217.87 | 494.06 | 837.85 | 448.32 | 389.53 | 0.00 | 0.00 |
October | 955.68 | 552.26 | 640.50 | 349.69 | 290.82 | 0.00 | 0.00 |
November | 733.51 | 770.27 | 578.56 | 302.63 | 275.94 | 0.00 | 0.00 |
December | 647.89 | 839.10 | 510.97 | 274.06 | 236.91 | 0.00 | 0.00 |
Annual Sum or Average | 1056.62 | 622.61 | 770.68 | 393.19 | 377.49 | 0.00 | 0.00 |
Minimum of Months | 624.09 | 410.84 | 502.26 | 253.31 | 236.91 | 0.00 | 0.00 |
Maximum of Months | 1550.24 | 839.10 | 1043.06 | 558.13 | 500.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 160.06 | 1252.70 | 293.44 | 0.00 | 293.44 | 0.00 | 0.00 |
February | 189.43 | 1142.81 | 368.34 | 0.00 | 368.34 | 0.00 | 0.00 |
March | 286.44 | 1165.75 | 451.37 | 0.00 | 451.37 | 0.00 | 0.00 |
April | 409.60 | 926.54 | 520.04 | 2.00 | 518.04 | 0.00 | 0.00 |
May | 519.70 | 807.39 | 624.92 | 29.10 | 595.82 | 0.00 | 0.00 |
June | 680.09 | 634.13 | 665.88 | 65.10 | 600.78 | 0.00 | 0.00 |
July | 725.65 | 566.88 | 630.49 | 52.85 | 577.64 | 0.00 | 0.00 |
August | 581.45 | 598.59 | 523.60 | 10.48 | 513.11 | 0.00 | 0.00 |
September | 447.19 | 722.99 | 443.17 | 0.07 | 443.10 | 0.00 | 0.00 |
October | 392.46 | 811.44 | 351.54 | 0.00 | 351.54 | 0.00 | 0.00 |
November | 183.02 | 1158.64 | 318.29 | 0.00 | 318.29 | 0.00 | 0.00 |
December | 141.93 | 1270.83 | 273.17 | 0.00 | 273.17 | 0.00 | 0.00 |
Annual Sum or Average | 394.35 | 920.41 | 455.72 | 13.37 | 442.35 | 0.00 | 0.00 |
Minimum of Months | 141.93 | 566.88 | 273.17 | 0.00 | 273.17 | 0.00 | 0.00 |
Maximum of Months | 725.65 | 1270.83 | 665.88 | 65.10 | 600.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 610.37 | 779.81 | 527.68 | 282.22 | 245.47 | 0.00 | 0.00 |
February | 599.71 | 717.61 | 556.65 | 255.01 | 301.65 | 0.00 | 0.00 |
March | 766.64 | 730.93 | 676.17 | 301.26 | 374.91 | 0.00 | 0.00 |
April | 1131.73 | 596.99 | 864.48 | 433.55 | 430.92 | 0.00 | 0.00 |
May | 1019.43 | 546.11 | 815.82 | 340.46 | 475.36 | 0.00 | 0.00 |
June | 1094.39 | 436.11 | 810.74 | 351.77 | 458.97 | 0.00 | 0.00 |
July | 1347.84 | 391.75 | 918.63 | 456.49 | 462.14 | 0.00 | 0.00 |
August | 1350.93 | 400.34 | 907.22 | 481.88 | 425.34 | 0.00 | 0.00 |
September | 923.20 | 466.22 | 660.53 | 302.68 | 357.85 | 0.00 | 0.00 |
October | 834.87 | 515.27 | 584.69 | 300.51 | 284.17 | 0.00 | 0.00 |
November | 613.31 | 725.60 | 533.01 | 270.79 | 262.22 | 0.00 | 0.00 |
December | 586.13 | 787.76 | 508.48 | 282.52 | 225.96 | 0.00 | 0.00 |
Annual Sum or Average | 908.70 | 590.55 | 697.94 | 338.93 | 359.01 | 0.00 | 0.00 |
Minimum of Months | 586.13 | 391.75 | 508.48 | 255.01 | 225.96 | 0.00 | 0.00 |
Maximum of Months | 1350.93 | 787.76 | 918.63 | 481.88 | 475.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2791.96 | 1203.93 | 1936.48 | 1420.50 | 515.98 | 0.00 | 0.00 |
February | 2042.73 | 1109.37 | 1521.97 | 937.46 | 584.52 | 0.00 | 0.00 |
March | 1598.59 | 1162.07 | 1213.37 | 586.11 | 627.25 | 0.00 | 0.00 |
April | 1432.28 | 968.10 | 1013.80 | 386.57 | 627.23 | 0.00 | 0.00 |
May | 803.53 | 883.42 | 721.90 | 88.84 | 633.06 | 0.00 | 0.00 |
June | 709.33 | 689.49 | 633.30 | 38.24 | 595.06 | 0.00 | 0.00 |
July | 895.53 | 609.38 | 670.84 | 75.52 | 595.32 | 0.00 | 0.00 |
August | 1347.10 | 637.58 | 861.83 | 271.85 | 589.98 | 0.00 | 0.00 |
September | 1882.98 | 743.72 | 1199.23 | 607.69 | 591.54 | 0.00 | 0.00 |
October | 2410.37 | 809.08 | 1525.14 | 1019.60 | 505.54 | 0.00 | 0.00 |
November | 2657.29 | 1116.16 | 1853.66 | 1308.65 | 545.00 | 0.00 | 0.00 |
December | 2999.00 | 1212.44 | 2068.78 | 1574.62 | 494.17 | 0.00 | 0.00 |
Annual Sum or Average | 1796.93 | 927.79 | 1267.30 | 692.14 | 575.16 | 0.00 | 0.00 |
Minimum of Months | 709.33 | 609.38 | 633.30 | 38.24 | 494.17 | 0.00 | 0.00 |
Maximum of Months | 2999.00 | 1212.44 | 2068.78 | 1574.62 | 633.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 615.07 | 822.61 | 502.26 | 253.32 | 248.94 | 0.00 | 0.00 |
February | 695.07 | 749.63 | 599.20 | 276.62 | 322.58 | 0.00 | 0.00 |
March | 811.20 | 763.68 | 686.85 | 303.87 | 382.97 | 0.00 | 0.00 |
April | 1276.08 | 631.64 | 946.86 | 493.03 | 453.83 | 0.00 | 0.00 |
May | 1208.92 | 574.90 | 930.11 | 429.62 | 500.49 | 0.00 | 0.00 |
June | 1364.20 | 452.70 | 985.35 | 492.66 | 492.69 | 0.00 | 0.00 |
July | 1535.03 | 407.42 | 1043.07 | 558.14 | 484.93 | 0.00 | 0.00 |
August | 1462.70 | 423.70 | 978.60 | 530.36 | 448.24 | 0.00 | 0.00 |
September | 1205.96 | 486.89 | 837.87 | 448.33 | 389.54 | 0.00 | 0.00 |
October | 947.56 | 543.48 | 640.51 | 349.69 | 290.82 | 0.00 | 0.00 |
November | 725.93 | 757.49 | 578.57 | 302.63 | 275.94 | 0.00 | 0.00 |
December | 639.51 | 831.98 | 510.98 | 274.07 | 236.91 | 0.00 | 0.00 |
Annual Sum or Average | 1042.32 | 619.87 | 770.69 | 393.19 | 377.49 | 0.00 | 0.00 |
Minimum of Months | 615.07 | 407.42 | 502.26 | 253.32 | 236.91 | 0.00 | 0.00 |
Maximum of Months | 1535.03 | 831.98 | 1043.07 | 558.14 | 500.49 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.479470E+09 | 0.309873E+10 | 0.785942E+09 | 0.00 | 0.785942E+09 | 0.00 | 0.00 |
February | 0.505016E+09 | 0.254956E+10 | 0.891094E+09 | 0.00 | 0.891094E+09 | 0.00 | 0.00 |
March | 0.813586E+09 | 0.291215E+10 | 0.120896E+10 | 0.00 | 0.120896E+10 | 0.00 | 0.00 |
April | 0.108521E+10 | 0.226248E+10 | 0.134794E+10 | 5187996.30 | 0.134275E+10 | 0.00 | 0.00 |
May | 0.142599E+10 | 0.204587E+10 | 0.167378E+10 | 77940352.35 | 0.159584E+10 | 0.00 | 0.00 |
June | 0.177131E+10 | 0.156675E+10 | 0.172597E+10 | 0.168742E+09 | 0.155722E+10 | 0.00 | 0.00 |
July | 0.194134E+10 | 0.145208E+10 | 0.168869E+10 | 0.141540E+09 | 0.154715E+10 | 0.00 | 0.00 |
August | 0.155813E+10 | 0.152740E+10 | 0.140240E+10 | 28081717.27 | 0.137432E+10 | 0.00 | 0.00 |
September | 0.117381E+10 | 0.176393E+10 | 0.114870E+10 | 180046.04 | 0.114852E+10 | 0.00 | 0.00 |
October | 0.107797E+10 | 0.203185E+10 | 0.941559E+09 | 0.00 | 0.941559E+09 | 0.00 | 0.00 |
November | 0.524302E+09 | 0.277345E+10 | 0.825014E+09 | 0.00 | 0.825014E+09 | 0.00 | 0.00 |
December | 0.433884E+09 | 0.313264E+10 | 0.731645E+09 | 0.00 | 0.731645E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127900E+11 | 0.271169E+11 | 0.143717E+11 | 0.421672E+09 | 0.139500E+11 | 0.00 | 0.00 |
Minimum of Months | 0.433884E+09 | 0.145208E+10 | 0.731645E+09 | 0.00 | 0.731645E+09 | 0.00 | 0.00 |
Maximum of Months | 0.194134E+10 | 0.313264E+10 | 0.172597E+10 | 0.168742E+09 | 0.159584E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.168246E+10 | 0.194818E+10 | 0.141335E+10 | 0.755894E+09 | 0.657458E+09 | 0.00 | 0.00 |
February | 0.148687E+10 | 0.161704E+10 | 0.134666E+10 | 0.616914E+09 | 0.729742E+09 | 0.00 | 0.00 |
March | 0.208895E+10 | 0.184334E+10 | 0.181106E+10 | 0.806908E+09 | 0.100415E+10 | 0.00 | 0.00 |
April | 0.294686E+10 | 0.147174E+10 | 0.224072E+10 | 0.112377E+10 | 0.111695E+10 | 0.00 | 0.00 |
May | 0.274817E+10 | 0.139470E+10 | 0.218509E+10 | 0.911889E+09 | 0.127320E+10 | 0.00 | 0.00 |
June | 0.283996E+10 | 0.108435E+10 | 0.210143E+10 | 0.911775E+09 | 0.118966E+10 | 0.00 | 0.00 |
July | 0.360374E+10 | 0.100920E+10 | 0.246045E+10 | 0.122267E+10 | 0.123779E+10 | 0.00 | 0.00 |
August | 0.361333E+10 | 0.102889E+10 | 0.242990E+10 | 0.129068E+10 | 0.113922E+10 | 0.00 | 0.00 |
September | 0.239980E+10 | 0.114491E+10 | 0.171209E+10 | 0.784544E+09 | 0.927545E+09 | 0.00 | 0.00 |
October | 0.225401E+10 | 0.130181E+10 | 0.156603E+10 | 0.804899E+09 | 0.761130E+09 | 0.00 | 0.00 |
November | 0.163199E+10 | 0.175679E+10 | 0.138157E+10 | 0.701894E+09 | 0.679674E+09 | 0.00 | 0.00 |
December | 0.162151E+10 | 0.196358E+10 | 0.136192E+10 | 0.756698E+09 | 0.605224E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.289176E+11 | 0.175645E+11 | 0.220103E+11 | 0.106885E+11 | 0.113217E+11 | 0.00 | 0.00 |
Minimum of Months | 0.148687E+10 | 0.100920E+10 | 0.134666E+10 | 0.616914E+09 | 0.605224E+09 | 0.00 | 0.00 |
Maximum of Months | 0.361333E+10 | 0.196358E+10 | 0.246045E+10 | 0.129068E+10 | 0.127320E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.753137E+10 | 0.301055E+10 | 0.518668E+10 | 0.380467E+10 | 0.138201E+10 | 0.00 | 0.00 |
February | 0.498568E+10 | 0.249414E+10 | 0.368196E+10 | 0.226789E+10 | 0.141407E+10 | 0.00 | 0.00 |
March | 0.432568E+10 | 0.291300E+10 | 0.324988E+10 | 0.156985E+10 | 0.168004E+10 | 0.00 | 0.00 |
April | 0.372788E+10 | 0.237160E+10 | 0.262776E+10 | 0.100199E+10 | 0.162577E+10 | 0.00 | 0.00 |
May | 0.217422E+10 | 0.223457E+10 | 0.193354E+10 | 0.237949E+09 | 0.169559E+10 | 0.00 | 0.00 |
June | 0.184592E+10 | 0.170007E+10 | 0.164151E+10 | 99108672.29 | 0.154240E+10 | 0.00 | 0.00 |
July | 0.239560E+10 | 0.155886E+10 | 0.179677E+10 | 0.202265E+09 | 0.159451E+10 | 0.00 | 0.00 |
August | 0.360177E+10 | 0.162753E+10 | 0.230832E+10 | 0.728115E+09 | 0.158020E+10 | 0.00 | 0.00 |
September | 0.488478E+10 | 0.182097E+10 | 0.310841E+10 | 0.157514E+10 | 0.153327E+10 | 0.00 | 0.00 |
October | 0.647294E+10 | 0.204263E+10 | 0.408494E+10 | 0.273090E+10 | 0.135404E+10 | 0.00 | 0.00 |
November | 0.693258E+10 | 0.270496E+10 | 0.480468E+10 | 0.339203E+10 | 0.141265E+10 | 0.00 | 0.00 |
December | 0.808845E+10 | 0.303152E+10 | 0.554103E+10 | 0.421745E+10 | 0.132358E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.569669E+11 | 0.275104E+11 | 0.399655E+11 | 0.218273E+11 | 0.181381E+11 | 0.00 | 0.00 |
Minimum of Months | 0.184592E+10 | 0.155886E+10 | 0.164151E+10 | 99108672.29 | 0.132358E+10 | 0.00 | 0.00 |
Maximum of Months | 0.808845E+10 | 0.303152E+10 | 0.554103E+10 | 0.421745E+10 | 0.169559E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.167795E+10 | 0.204132E+10 | 0.134526E+10 | 0.678490E+09 | 0.666773E+09 | 0.00 | 0.00 |
February | 0.170912E+10 | 0.167875E+10 | 0.144959E+10 | 0.669199E+09 | 0.780392E+09 | 0.00 | 0.00 |
March | 0.219876E+10 | 0.191039E+10 | 0.183965E+10 | 0.813890E+09 | 0.102576E+10 | 0.00 | 0.00 |
April | 0.331734E+10 | 0.154565E+10 | 0.245425E+10 | 0.127792E+10 | 0.117633E+10 | 0.00 | 0.00 |
May | 0.324909E+10 | 0.145506E+10 | 0.249121E+10 | 0.115068E+10 | 0.134052E+10 | 0.00 | 0.00 |
June | 0.353425E+10 | 0.111636E+10 | 0.255402E+10 | 0.127696E+10 | 0.127706E+10 | 0.00 | 0.00 |
July | 0.410283E+10 | 0.104239E+10 | 0.279376E+10 | 0.149492E+10 | 0.129884E+10 | 0.00 | 0.00 |
August | 0.391044E+10 | 0.108136E+10 | 0.262109E+10 | 0.142052E+10 | 0.120057E+10 | 0.00 | 0.00 |
September | 0.313077E+10 | 0.118921E+10 | 0.217175E+10 | 0.116207E+10 | 0.100968E+10 | 0.00 | 0.00 |
October | 0.255241E+10 | 0.136378E+10 | 0.171554E+10 | 0.936613E+09 | 0.778929E+09 | 0.00 | 0.00 |
November | 0.191013E+10 | 0.181877E+10 | 0.149966E+10 | 0.784427E+09 | 0.715232E+09 | 0.00 | 0.00 |
December | 0.174605E+10 | 0.206001E+10 | 0.136861E+10 | 0.734056E+09 | 0.634550E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.330391E+11 | 0.183030E+11 | 0.243044E+11 | 0.123998E+11 | 0.119046E+11 | 0.00 | 0.00 |
Minimum of Months | 0.167795E+10 | 0.104239E+10 | 0.134526E+10 | 0.669199E+09 | 0.634550E+09 | 0.00 | 0.00 |
Maximum of Months | 0.410283E+10 | 0.206001E+10 | 0.279376E+10 | 0.149492E+10 | 0.134052E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.461715E+09 | 0.328859E+10 | 0.785927E+09 | 0.00 | 0.785927E+09 | 0.00 | 0.00 |
February | 0.514736E+09 | 0.265270E+10 | 0.891075E+09 | 0.00 | 0.891075E+09 | 0.00 | 0.00 |
March | 0.848927E+09 | 0.299216E+10 | 0.120894E+10 | 0.00 | 0.120894E+10 | 0.00 | 0.00 |
April | 0.115007E+10 | 0.228333E+10 | 0.134791E+10 | 5187843.82 | 0.134272E+10 | 0.00 | 0.00 |
May | 0.148662E+10 | 0.208063E+10 | 0.167375E+10 | 77938061.47 | 0.159581E+10 | 0.00 | 0.00 |
June | 0.185829E+10 | 0.156722E+10 | 0.172593E+10 | 0.168737E+09 | 0.155719E+10 | 0.00 | 0.00 |
July | 0.201549E+10 | 0.146303E+10 | 0.168866E+10 | 0.141536E+09 | 0.154712E+10 | 0.00 | 0.00 |
August | 0.161802E+10 | 0.153760E+10 | 0.140238E+10 | 28080891.87 | 0.137430E+10 | 0.00 | 0.00 |
September | 0.120569E+10 | 0.181346E+10 | 0.114868E+10 | 180040.75 | 0.114850E+10 | 0.00 | 0.00 |
October | 0.108324E+10 | 0.213104E+10 | 0.941541E+09 | 0.00 | 0.941541E+09 | 0.00 | 0.00 |
November | 0.505831E+09 | 0.295385E+10 | 0.824997E+09 | 0.00 | 0.824997E+09 | 0.00 | 0.00 |
December | 0.412354E+09 | 0.333011E+10 | 0.731631E+09 | 0.00 | 0.731631E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.131610E+11 | 0.280937E+11 | 0.143714E+11 | 0.421660E+09 | 0.139498E+11 | 0.00 | 0.00 |
Minimum of Months | 0.412354E+09 | 0.146303E+10 | 0.731631E+09 | 0.00 | 0.731631E+09 | 0.00 | 0.00 |
Maximum of Months | 0.201549E+10 | 0.333011E+10 | 0.172593E+10 | 0.168737E+09 | 0.159581E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.165039E+10 | 0.211749E+10 | 0.141333E+10 | 0.755879E+09 | 0.657450E+09 | 0.00 | 0.00 |
February | 0.148359E+10 | 0.172298E+10 | 0.134663E+10 | 0.616902E+09 | 0.729733E+09 | 0.00 | 0.00 |
March | 0.209770E+10 | 0.194079E+10 | 0.181103E+10 | 0.806892E+09 | 0.100414E+10 | 0.00 | 0.00 |
April | 0.297902E+10 | 0.154128E+10 | 0.224069E+10 | 0.112375E+10 | 0.111694E+10 | 0.00 | 0.00 |
May | 0.277750E+10 | 0.145511E+10 | 0.218506E+10 | 0.911871E+09 | 0.127319E+10 | 0.00 | 0.00 |
June | 0.288565E+10 | 0.111129E+10 | 0.210140E+10 | 0.911757E+09 | 0.118965E+10 | 0.00 | 0.00 |
July | 0.364485E+10 | 0.105431E+10 | 0.246042E+10 | 0.122264E+10 | 0.123778E+10 | 0.00 | 0.00 |
August | 0.365023E+10 | 0.107962E+10 | 0.242986E+10 | 0.129066E+10 | 0.113921E+10 | 0.00 | 0.00 |
September | 0.241747E+10 | 0.121385E+10 | 0.171206E+10 | 0.784529E+09 | 0.927535E+09 | 0.00 | 0.00 |
October | 0.225529E+10 | 0.139920E+10 | 0.156601E+10 | 0.804883E+09 | 0.761122E+09 | 0.00 | 0.00 |
November | 0.160435E+10 | 0.191003E+10 | 0.138155E+10 | 0.701880E+09 | 0.679666E+09 | 0.00 | 0.00 |
December | 0.158643E+10 | 0.213369E+10 | 0.136190E+10 | 0.756684E+09 | 0.605217E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.290325E+11 | 0.186796E+11 | 0.220099E+11 | 0.106883E+11 | 0.113216E+11 | 0.00 | 0.00 |
Minimum of Months | 0.148359E+10 | 0.105431E+10 | 0.134663E+10 | 0.616902E+09 | 0.605217E+09 | 0.00 | 0.00 |
Maximum of Months | 0.365023E+10 | 0.213369E+10 | 0.246042E+10 | 0.129066E+10 | 0.127319E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.752482E+10 | 0.333998E+10 | 0.518648E+10 | 0.380451E+10 | 0.138197E+10 | 0.00 | 0.00 |
February | 0.502737E+10 | 0.269253E+10 | 0.368182E+10 | 0.226780E+10 | 0.141402E+10 | 0.00 | 0.00 |
March | 0.439402E+10 | 0.305013E+10 | 0.324976E+10 | 0.156978E+10 | 0.167998E+10 | 0.00 | 0.00 |
April | 0.380768E+10 | 0.243249E+10 | 0.262768E+10 | 0.100195E+10 | 0.162573E+10 | 0.00 | 0.00 |
May | 0.227308E+10 | 0.224719E+10 | 0.193349E+10 | 0.237939E+09 | 0.169555E+10 | 0.00 | 0.00 |
June | 0.195473E+10 | 0.166812E+10 | 0.164147E+10 | 99104559.54 | 0.154236E+10 | 0.00 | 0.00 |
July | 0.247819E+10 | 0.156187E+10 | 0.179673E+10 | 0.202257E+09 | 0.159447E+10 | 0.00 | 0.00 |
August | 0.367540E+10 | 0.166405E+10 | 0.230825E+10 | 0.728085E+09 | 0.158016E+10 | 0.00 | 0.00 |
September | 0.493651E+10 | 0.193357E+10 | 0.310830E+10 | 0.157507E+10 | 0.153323E+10 | 0.00 | 0.00 |
October | 0.649925E+10 | 0.223200E+10 | 0.408479E+10 | 0.273078E+10 | 0.135400E+10 | 0.00 | 0.00 |
November | 0.694328E+10 | 0.298967E+10 | 0.480449E+10 | 0.339189E+10 | 0.141260E+10 | 0.00 | 0.00 |
December | 0.808466E+10 | 0.336735E+10 | 0.554081E+10 | 0.421727E+10 | 0.132354E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.575990E+11 | 0.291790E+11 | 0.399640E+11 | 0.218264E+11 | 0.181376E+11 | 0.00 | 0.00 |
Minimum of Months | 0.195473E+10 | 0.156187E+10 | 0.164147E+10 | 99104559.54 | 0.132354E+10 | 0.00 | 0.00 |
Maximum of Months | 0.808466E+10 | 0.336735E+10 | 0.554081E+10 | 0.421727E+10 | 0.169555E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.167155E+10 | 0.222054E+10 | 0.134525E+10 | 0.678479E+09 | 0.666766E+09 | 0.00 | 0.00 |
February | 0.172075E+10 | 0.180049E+10 | 0.144957E+10 | 0.669188E+09 | 0.780384E+09 | 0.00 | 0.00 |
March | 0.222510E+10 | 0.202660E+10 | 0.183963E+10 | 0.813877E+09 | 0.102575E+10 | 0.00 | 0.00 |
April | 0.336028E+10 | 0.163388E+10 | 0.245422E+10 | 0.127790E+10 | 0.117632E+10 | 0.00 | 0.00 |
May | 0.329086E+10 | 0.154076E+10 | 0.249117E+10 | 0.115066E+10 | 0.134051E+10 | 0.00 | 0.00 |
June | 0.359220E+10 | 0.116392E+10 | 0.255399E+10 | 0.127694E+10 | 0.127705E+10 | 0.00 | 0.00 |
July | 0.415215E+10 | 0.110039E+10 | 0.279373E+10 | 0.149489E+10 | 0.129883E+10 | 0.00 | 0.00 |
August | 0.395573E+10 | 0.114423E+10 | 0.262106E+10 | 0.142050E+10 | 0.120056E+10 | 0.00 | 0.00 |
September | 0.315673E+10 | 0.128061E+10 | 0.217172E+10 | 0.116205E+10 | 0.100967E+10 | 0.00 | 0.00 |
October | 0.255969E+10 | 0.147917E+10 | 0.171552E+10 | 0.936597E+09 | 0.778922E+09 | 0.00 | 0.00 |
November | 0.190127E+10 | 0.199653E+10 | 0.149964E+10 | 0.784414E+09 | 0.715225E+09 | 0.00 | 0.00 |
December | 0.173532E+10 | 0.224745E+10 | 0.136859E+10 | 0.734044E+09 | 0.634544E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.333216E+11 | 0.196346E+11 | 0.243041E+11 | 0.123996E+11 | 0.119045E+11 | 0.00 | 0.00 |
Minimum of Months | 0.167155E+10 | 0.110039E+10 | 0.134525E+10 | 0.669188E+09 | 0.634544E+09 | 0.00 | 0.00 |
Maximum of Months | 0.415215E+10 | 0.224745E+10 | 0.279373E+10 | 0.149489E+10 | 0.134051E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.428711E+09 | 0.335524E+10 | 0.785942E+09 | 0.00 | 0.785942E+09 | 0.00 | 0.00 |
February | 0.458269E+09 | 0.276469E+10 | 0.891094E+09 | 0.00 | 0.891094E+09 | 0.00 | 0.00 |
March | 0.767213E+09 | 0.312235E+10 | 0.120896E+10 | 0.00 | 0.120896E+10 | 0.00 | 0.00 |
April | 0.106167E+10 | 0.240158E+10 | 0.134794E+10 | 5187996.30 | 0.134275E+10 | 0.00 | 0.00 |
May | 0.139196E+10 | 0.216251E+10 | 0.167378E+10 | 77940352.35 | 0.159584E+10 | 0.00 | 0.00 |
June | 0.176278E+10 | 0.164368E+10 | 0.172597E+10 | 0.168742E+09 | 0.155722E+10 | 0.00 | 0.00 |
July | 0.194358E+10 | 0.151834E+10 | 0.168869E+10 | 0.141540E+09 | 0.154715E+10 | 0.00 | 0.00 |
August | 0.155735E+10 | 0.160325E+10 | 0.140240E+10 | 28081717.27 | 0.137432E+10 | 0.00 | 0.00 |
September | 0.115910E+10 | 0.187398E+10 | 0.114870E+10 | 180046.04 | 0.114852E+10 | 0.00 | 0.00 |
October | 0.105116E+10 | 0.217336E+10 | 0.941559E+09 | 0.00 | 0.941559E+09 | 0.00 | 0.00 |
November | 0.474379E+09 | 0.300320E+10 | 0.825014E+09 | 0.00 | 0.825014E+09 | 0.00 | 0.00 |
December | 0.380152E+09 | 0.340379E+10 | 0.731645E+09 | 0.00 | 0.731645E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.124363E+11 | 0.290260E+11 | 0.143717E+11 | 0.421672E+09 | 0.139500E+11 | 0.00 | 0.00 |
Minimum of Months | 0.380152E+09 | 0.151834E+10 | 0.731645E+09 | 0.00 | 0.731645E+09 | 0.00 | 0.00 |
Maximum of Months | 0.194358E+10 | 0.340379E+10 | 0.172597E+10 | 0.168742E+09 | 0.159584E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.163482E+10 | 0.208865E+10 | 0.141335E+10 | 0.755894E+09 | 0.657458E+09 | 0.00 | 0.00 |
February | 0.145081E+10 | 0.173604E+10 | 0.134666E+10 | 0.616914E+09 | 0.729742E+09 | 0.00 | 0.00 |
March | 0.205338E+10 | 0.195772E+10 | 0.181106E+10 | 0.806908E+09 | 0.100415E+10 | 0.00 | 0.00 |
April | 0.293346E+10 | 0.154739E+10 | 0.224072E+10 | 0.112377E+10 | 0.111695E+10 | 0.00 | 0.00 |
May | 0.273045E+10 | 0.146271E+10 | 0.218509E+10 | 0.911889E+09 | 0.127320E+10 | 0.00 | 0.00 |
June | 0.283666E+10 | 0.113040E+10 | 0.210143E+10 | 0.911775E+09 | 0.118966E+10 | 0.00 | 0.00 |
July | 0.361007E+10 | 0.104925E+10 | 0.246045E+10 | 0.122267E+10 | 0.123779E+10 | 0.00 | 0.00 |
August | 0.361833E+10 | 0.107227E+10 | 0.242990E+10 | 0.129068E+10 | 0.113922E+10 | 0.00 | 0.00 |
September | 0.239293E+10 | 0.120845E+10 | 0.171209E+10 | 0.784544E+09 | 0.927545E+09 | 0.00 | 0.00 |
October | 0.223612E+10 | 0.138009E+10 | 0.156603E+10 | 0.804899E+09 | 0.761130E+09 | 0.00 | 0.00 |
November | 0.158971E+10 | 0.188075E+10 | 0.138157E+10 | 0.701894E+09 | 0.679674E+09 | 0.00 | 0.00 |
December | 0.156990E+10 | 0.210993E+10 | 0.136192E+10 | 0.756698E+09 | 0.605224E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.286566E+11 | 0.186237E+11 | 0.220103E+11 | 0.106885E+11 | 0.113217E+11 | 0.00 | 0.00 |
Minimum of Months | 0.145081E+10 | 0.104925E+10 | 0.134666E+10 | 0.616914E+09 | 0.605224E+09 | 0.00 | 0.00 |
Maximum of Months | 0.361833E+10 | 0.210993E+10 | 0.246045E+10 | 0.129068E+10 | 0.127320E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.747798E+10 | 0.322461E+10 | 0.518668E+10 | 0.380467E+10 | 0.138201E+10 | 0.00 | 0.00 |
February | 0.494177E+10 | 0.268379E+10 | 0.368196E+10 | 0.226789E+10 | 0.141407E+10 | 0.00 | 0.00 |
March | 0.428166E+10 | 0.311249E+10 | 0.324988E+10 | 0.156985E+10 | 0.168004E+10 | 0.00 | 0.00 |
April | 0.371247E+10 | 0.250932E+10 | 0.262776E+10 | 0.100199E+10 | 0.162577E+10 | 0.00 | 0.00 |
May | 0.215216E+10 | 0.236616E+10 | 0.193354E+10 | 0.237949E+09 | 0.169559E+10 | 0.00 | 0.00 |
June | 0.183858E+10 | 0.178715E+10 | 0.164151E+10 | 99108672.29 | 0.154240E+10 | 0.00 | 0.00 |
July | 0.239860E+10 | 0.163217E+10 | 0.179677E+10 | 0.202265E+09 | 0.159451E+10 | 0.00 | 0.00 |
August | 0.360806E+10 | 0.170769E+10 | 0.230832E+10 | 0.728115E+09 | 0.158020E+10 | 0.00 | 0.00 |
September | 0.488068E+10 | 0.192773E+10 | 0.310841E+10 | 0.157514E+10 | 0.153327E+10 | 0.00 | 0.00 |
October | 0.645594E+10 | 0.216705E+10 | 0.408494E+10 | 0.273090E+10 | 0.135404E+10 | 0.00 | 0.00 |
November | 0.688771E+10 | 0.289310E+10 | 0.480468E+10 | 0.339203E+10 | 0.141265E+10 | 0.00 | 0.00 |
December | 0.803252E+10 | 0.324741E+10 | 0.554103E+10 | 0.421745E+10 | 0.132358E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.566681E+11 | 0.292587E+11 | 0.399655E+11 | 0.218273E+11 | 0.181381E+11 | 0.00 | 0.00 |
Minimum of Months | 0.183858E+10 | 0.163217E+10 | 0.164151E+10 | 99108672.29 | 0.132358E+10 | 0.00 | 0.00 |
Maximum of Months | 0.803252E+10 | 0.324741E+10 | 0.554103E+10 | 0.421745E+10 | 0.169559E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.164739E+10 | 0.220328E+10 | 0.134526E+10 | 0.678490E+09 | 0.666773E+09 | 0.00 | 0.00 |
February | 0.168151E+10 | 0.181351E+10 | 0.144959E+10 | 0.669199E+09 | 0.780392E+09 | 0.00 | 0.00 |
March | 0.217271E+10 | 0.204543E+10 | 0.183965E+10 | 0.813890E+09 | 0.102576E+10 | 0.00 | 0.00 |
April | 0.330760E+10 | 0.163722E+10 | 0.245425E+10 | 0.127792E+10 | 0.117633E+10 | 0.00 | 0.00 |
May | 0.323797E+10 | 0.153981E+10 | 0.249121E+10 | 0.115068E+10 | 0.134052E+10 | 0.00 | 0.00 |
June | 0.353600E+10 | 0.117340E+10 | 0.255402E+10 | 0.127696E+10 | 0.127706E+10 | 0.00 | 0.00 |
July | 0.411143E+10 | 0.109124E+10 | 0.279376E+10 | 0.149492E+10 | 0.129884E+10 | 0.00 | 0.00 |
August | 0.391769E+10 | 0.113483E+10 | 0.262109E+10 | 0.142052E+10 | 0.120057E+10 | 0.00 | 0.00 |
September | 0.312585E+10 | 0.126201E+10 | 0.217175E+10 | 0.116207E+10 | 0.100968E+10 | 0.00 | 0.00 |
October | 0.253794E+10 | 0.145567E+10 | 0.171554E+10 | 0.936613E+09 | 0.778929E+09 | 0.00 | 0.00 |
November | 0.188161E+10 | 0.196341E+10 | 0.149966E+10 | 0.784427E+09 | 0.715232E+09 | 0.00 | 0.00 |
December | 0.171285E+10 | 0.222838E+10 | 0.136861E+10 | 0.734056E+09 | 0.634550E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.328706E+11 | 0.195482E+11 | 0.243044E+11 | 0.123998E+11 | 0.119046E+11 | 0.00 | 0.00 |
Minimum of Months | 0.164739E+10 | 0.109124E+10 | 0.134526E+10 | 0.669199E+09 | 0.634550E+09 | 0.00 | 0.00 |
Maximum of Months | 0.411143E+10 | 0.222838E+10 | 0.279376E+10 | 0.149492E+10 | 0.134052E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.462077E+10 | -0.392454E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -696231951.9 | 58.99 | 0.00 | 0.00 |
February | 0.419948E+10 | -0.357085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -628634000.3 | 58.99 | 0.00 | 0.00 |
March | 0.487719E+10 | -0.418138E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -695805619.0 | 58.98 | 0.00 | 0.00 |
April | 0.435426E+10 | -0.368410E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -670160242.0 | 58.98 | 0.00 | 0.00 |
May | 0.454247E+10 | -0.385092E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691553654.0 | 58.98 | 0.00 | 0.00 |
June | 0.440681E+10 | -0.373830E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668508995.7 | 58.98 | 0.00 | 0.00 |
July | 0.415786E+10 | -0.346931E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688556322.4 | 58.98 | 0.00 | 0.00 |
August | 0.452105E+10 | -0.383110E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689951791.1 | 58.99 | 0.00 | 0.00 |
September | 0.415808E+10 | -0.349139E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666684946.7 | 58.98 | 0.00 | 0.00 |
October | 0.437656E+10 | -0.368779E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688761811.5 | 58.98 | 0.00 | 0.00 |
November | 0.439201E+10 | -0.372242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669590987.3 | 58.98 | 0.00 | 0.00 |
December | 0.446140E+10 | -0.376659E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -694802735.4 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.530679E+11 | -0.449187E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.814924E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.415786E+10 | -0.418138E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -696231951.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.487719E+10 | -0.346931E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -628634000.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:30 | 7863.85 | 37.27 | 285.00 | 280.17 | 1734.18 | 25.88 | 169.00 | 265.33 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-07:40 | 6966.72 | 35.52 | 275.33 | 274.67 | 1233.16 | 21.06 | 138.50 | 244.83 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-07:10 | 2047.14 | 18.83 | 11.17 | 315.00 | 1002.95 | 20.31 | 149.17 | 286.17 |
April | 358.33 | 0.52 | 0.48 | 01-APR-07:19 | 1327.72 | 18.01 | 0.00 | 332.50 | 815.86 | 20.21 | 93.33 | 297.00 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-06:49 | 1133.88 | 17.85 | 0.00 | 364.50 | 656.92 | 20.01 | 61.83 | 320.83 |
June | 381.00 | 0.52 | 0.48 | 01-JUN-06:49 | 1002.22 | 17.50 | 0.00 | 355.67 | 598.21 | 19.70 | 20.67 | 308.50 |
July | 408.67 | 0.53 | 0.48 | 01-JUL-06:40 | 1009.80 | 17.54 | 0.00 | 365.17 | 622.94 | 19.76 | 25.83 | 329.00 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:19 | 1138.26 | 17.66 | 0.00 | 354.00 | 713.42 | 19.85 | 49.33 | 316.00 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-06:00 | 1623.56 | 18.46 | 11.00 | 308.83 | 950.96 | 20.21 | 88.50 | 277.83 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 3509.52 | 24.54 | 115.83 | 303.00 | 1189.50 | 20.86 | 83.83 | 276.83 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7604.11 | 36.90 | 292.67 | 279.17 | 1557.71 | 25.55 | 179.50 | 270.17 |
December | 297.00 | 0.51 | 0.48 | 01-DEC-07:19 | 7725.99 | 37.39 | 286.17 | 281.17 | 2206.69 | 28.83 | 181.50 | 271.83 |
Annual Sum or Average | 4065.67 | 0.52 | 3260.97 | 23.85 | 1277.17 | 3813.83 | 1055.84 | 21.61 | 1241.00 | 3464.33 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1002.22 | 17.50 | 0.00 | 274.67 | 598.21 | 19.70 | 20.67 | 244.83 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 7863.85 | 37.39 | 292.67 | 365.17 | 2206.69 | 28.83 | 181.50 | 329.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-07:19 | 1718.14 | 21.64 | 85.00 | 264.83 | 880.21 | 22.19 | 61.33 | 223.17 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-07:10 | 1846.04 | 20.34 | 70.83 | 267.17 | 990.44 | 22.46 | 55.83 | 220.83 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-06:49 | 2288.45 | 21.61 | 106.50 | 315.83 | 1260.41 | 22.51 | 77.67 | 274.83 |
April | 358.33 | 0.51 | 0.48 | 01-APR-05:00 | 2275.48 | 19.29 | 77.33 | 336.50 | 1234.96 | 21.79 | 65.17 | 305.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:19 | 2233.57 | 20.07 | 99.50 | 376.50 | 1221.82 | 21.34 | 69.50 | 329.50 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:19 | 2223.54 | 19.24 | 88.83 | 367.17 | 951.28 | 19.40 | 36.33 | 322.33 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-05:30 | 2452.96 | 19.73 | 99.67 | 376.17 | 1300.55 | 20.91 | 68.67 | 338.33 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-06:49 | 2469.60 | 20.47 | 102.17 | 362.50 | 1266.47 | 21.47 | 69.67 | 325.50 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-06:40 | 2566.34 | 20.47 | 92.83 | 311.00 | 981.04 | 20.49 | 43.83 | 273.00 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 2339.70 | 20.95 | 88.83 | 282.17 | 967.33 | 20.42 | 42.67 | 234.00 |
November | 300.00 | 0.53 | 0.48 | 01-NOV-06:40 | 1955.88 | 21.88 | 95.17 | 263.00 | 1062.89 | 22.50 | 68.83 | 228.83 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-07:19 | 1695.78 | 21.25 | 86.17 | 264.00 | 878.45 | 21.71 | 63.33 | 220.50 |
Annual Sum or Average | 4065.67 | 0.52 | 2196.64 | 20.50 | 1092.83 | 3786.83 | 1097.65 | 21.38 | 722.83 | 3296.17 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1695.78 | 19.24 | 70.83 | 263.00 | 878.45 | 19.40 | 36.33 | 220.50 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 2566.34 | 21.88 | 106.50 | 376.50 | 1300.55 | 22.51 | 77.67 | 338.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.57 | 0.48 | 01-JAN-09:09 | 526.31 | 15.18 | 0.00 | 233.17 | 343.32 | 17.79 | 0.00 | 152.17 |
February | 279.67 | 0.54 | 0.48 | 01-FEB-09:09 | 631.25 | 16.02 | 0.00 | 246.83 | 389.37 | 18.34 | 0.00 | 173.00 |
March | 338.17 | 0.54 | 0.48 | 01-MAR-08:39 | 740.26 | 16.43 | 0.00 | 305.67 | 444.10 | 18.56 | 0.00 | 248.67 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 819.89 | 17.66 | 0.00 | 335.83 | 523.13 | 19.85 | 6.50 | 296.17 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:40 | 1029.94 | 18.32 | 0.00 | 381.17 | 601.92 | 20.49 | 73.83 | 352.50 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:40 | 1089.10 | 20.15 | 42.50 | 374.17 | 651.16 | 22.23 | 125.83 | 342.00 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:49 | 1019.40 | 20.06 | 45.17 | 384.67 | 602.08 | 20.59 | 102.17 | 361.17 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:19 | 841.40 | 17.76 | 0.00 | 364.67 | 539.68 | 19.94 | 29.83 | 337.83 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-07:10 | 732.15 | 16.93 | 0.00 | 304.00 | 470.35 | 19.18 | 0.00 | 257.33 |
October | 296.17 | 0.56 | 0.48 | 01-OCT-09:39 | 558.82 | 15.42 | 0.00 | 258.17 | 366.86 | 17.86 | 0.00 | 172.17 |
November | 300.00 | 0.57 | 0.48 | 01-NOV-08:09 | 534.94 | 14.83 | 0.00 | 236.83 | 345.73 | 17.30 | 0.00 | 160.50 |
December | 297.00 | 0.58 | 0.48 | 01-DEC-08:50 | 478.41 | 14.44 | 0.00 | 226.17 | 317.95 | 17.12 | 0.00 | 131.83 |
Annual Sum or Average | 4065.67 | 0.53 | 774.72 | 17.15 | 87.67 | 3651.33 | 479.81 | 19.27 | 338.17 | 2985.33 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 478.41 | 14.44 | 0.00 | 226.17 | 317.95 | 17.12 | 0.00 | 131.83 | |
Maximum of Months | 408.67 | 0.58 | 0.48 | 1089.10 | 20.15 | 45.17 | 384.67 | 651.16 | 22.23 | 125.83 | 361.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.54 | 0.48 | 01-JAN-09:09 | 2233.07 | 22.54 | 105.17 | 251.33 | 844.59 | 21.23 | 50.83 | 209.83 |
February | 279.67 | 0.53 | 0.48 | 01-FEB-09:09 | 2006.85 | 20.29 | 73.50 | 253.00 | 1104.86 | 22.53 | 60.00 | 214.17 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:39 | 2282.83 | 21.01 | 100.17 | 309.17 | 1240.44 | 21.95 | 71.67 | 266.17 |
April | 358.33 | 0.52 | 0.48 | 01-APR-07:00 | 3157.99 | 19.49 | 82.33 | 330.67 | 1194.60 | 17.72 | 0.00 | 298.00 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-07:30 | 2934.35 | 17.06 | 52.50 | 365.50 | 1204.08 | 17.87 | 0.00 | 328.33 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-07:19 | 2503.50 | 14.28 | 0.00 | 360.83 | 1364.66 | 17.82 | 0.00 | 323.17 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-07:10 | 2641.64 | 14.40 | 5.67 | 369.83 | 1408.92 | 17.74 | 0.00 | 341.67 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:00 | 3250.99 | 19.15 | 88.17 | 353.00 | 1332.77 | 17.92 | 7.00 | 323.67 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-07:40 | 2809.81 | 21.86 | 101.83 | 303.83 | 1505.81 | 22.49 | 71.83 | 269.50 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 2086.81 | 20.53 | 82.00 | 284.33 | 1098.02 | 21.10 | 52.50 | 238.17 |
November | 300.00 | 0.55 | 0.48 | 01-NOV-08:09 | 2180.53 | 22.41 | 104.33 | 253.83 | 1198.93 | 22.97 | 75.17 | 213.83 |
December | 297.00 | 0.55 | 0.48 | 01-DEC-08:50 | 1981.58 | 22.40 | 104.67 | 245.67 | 1100.52 | 22.97 | 80.33 | 198.00 |
Annual Sum or Average | 4065.67 | 0.53 | 2549.07 | 19.32 | 900.33 | 3681.00 | 1230.24 | 20.10 | 469.33 | 3224.50 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1981.58 | 14.28 | 0.00 | 245.67 | 844.59 | 17.72 | 0.00 | 198.00 | |
Maximum of Months | 408.67 | 0.55 | 0.48 | 3250.99 | 22.54 | 105.17 | 369.83 | 1505.81 | 22.97 | 80.33 | 341.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:30 | 7710.22 | 36.97 | 284.83 | 279.17 | 1612.25 | 23.50 | 97.50 | 264.67 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:30 | 6848.72 | 35.29 | 275.33 | 274.00 | 1181.24 | 21.69 | 61.00 | 251.50 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-06:49 | 1958.06 | 15.06 | 11.17 | 314.00 | 941.18 | 17.96 | 5.50 | 282.83 |
April | 358.33 | 0.52 | 0.48 | 01-APR-07:19 | 1265.43 | 14.41 | 0.00 | 331.83 | 772.09 | 17.97 | 0.00 | 293.83 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-06:00 | 1090.27 | 14.29 | 0.00 | 362.17 | 630.15 | 17.78 | 0.00 | 315.83 |
June | 381.00 | 0.53 | 0.48 | 01-JUN-06:00 | 965.93 | 14.04 | 0.00 | 353.67 | 577.24 | 17.54 | 0.00 | 303.67 |
July | 408.67 | 0.53 | 0.48 | 01-JUL-06:49 | 971.73 | 14.19 | 0.00 | 363.00 | 600.59 | 17.73 | 0.00 | 324.00 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:30 | 1087.83 | 14.24 | 0.00 | 351.33 | 679.64 | 17.78 | 0.00 | 311.50 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-06:00 | 1542.90 | 14.79 | 11.00 | 307.17 | 889.59 | 17.81 | 2.00 | 275.17 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 3401.21 | 21.87 | 115.67 | 302.67 | 1097.65 | 18.20 | 14.00 | 272.83 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7463.42 | 36.66 | 292.67 | 278.50 | 1446.34 | 23.11 | 92.67 | 269.17 |
December | 297.00 | 0.51 | 0.48 | 01-DEC-07:19 | 7567.54 | 37.04 | 285.67 | 279.67 | 2077.94 | 26.76 | 143.00 | 270.00 |
Annual Sum or Average | 4065.67 | 0.52 | 3176.20 | 21.31 | 1276.33 | 3797.17 | 995.15 | 19.55 | 415.67 | 3435.00 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 965.93 | 14.04 | 0.00 | 274.00 | 577.24 | 17.54 | 0.00 | 251.50 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 7710.22 | 37.04 | 292.67 | 363.00 | 2077.94 | 26.76 | 143.00 | 324.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-07:19 | 1666.69 | 21.14 | 85.00 | 263.67 | 840.17 | 21.96 | 57.00 | 219.00 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-07:10 | 1791.42 | 19.83 | 70.83 | 265.00 | 947.24 | 22.24 | 54.83 | 216.67 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-06:49 | 2232.15 | 21.16 | 106.50 | 313.50 | 1214.87 | 22.32 | 77.67 | 270.00 |
April | 358.33 | 0.51 | 0.48 | 01-APR-05:00 | 2205.30 | 18.81 | 77.33 | 334.83 | 1179.69 | 21.61 | 65.17 | 302.00 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:19 | 2168.53 | 19.61 | 99.33 | 375.50 | 1175.14 | 21.17 | 69.33 | 323.50 |
June | 381.00 | 0.52 | 0.48 | 01-JUN-06:19 | 2165.90 | 18.77 | 88.83 | 364.00 | 905.61 | 19.22 | 36.33 | 317.17 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-05:30 | 2384.35 | 19.26 | 99.17 | 373.00 | 1248.36 | 20.74 | 68.67 | 335.00 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-06:49 | 2351.96 | 18.66 | 85.67 | 357.67 | 1211.83 | 21.30 | 69.67 | 322.33 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-06:40 | 2512.48 | 20.00 | 92.83 | 309.67 | 936.45 | 20.29 | 43.83 | 268.33 |
October | 296.17 | 0.54 | 0.48 | 01-OCT-09:39 | 2257.52 | 20.01 | 85.00 | 278.83 | 924.72 | 20.21 | 42.67 | 230.33 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-06:40 | 1838.64 | 19.66 | 79.50 | 258.83 | 1022.29 | 22.28 | 66.33 | 224.17 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-07:19 | 1646.80 | 20.76 | 86.17 | 261.83 | 838.34 | 21.48 | 58.83 | 216.00 |
Annual Sum or Average | 4065.67 | 0.52 | 2125.83 | 19.74 | 1056.17 | 3756.33 | 1051.20 | 21.19 | 710.33 | 3244.50 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1646.80 | 18.66 | 70.83 | 258.83 | 838.34 | 19.22 | 36.33 | 216.00 | |
Maximum of Months | 408.67 | 0.54 | 0.48 | 2512.48 | 21.16 | 106.50 | 375.50 | 1248.36 | 22.32 | 77.67 | 335.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.57 | 0.48 | 01-JAN-09:09 | 506.51 | 11.57 | 0.00 | 229.00 | 333.13 | 15.48 | 0.00 | 142.00 |
February | 279.67 | 0.55 | 0.48 | 01-FEB-09:20 | 608.47 | 12.55 | 0.00 | 244.33 | 377.20 | 16.16 | 0.00 | 164.67 |
March | 338.17 | 0.54 | 0.48 | 01-MAR-08:50 | 714.62 | 13.08 | 0.00 | 303.50 | 430.15 | 16.50 | 0.00 | 241.67 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 791.97 | 14.38 | 0.00 | 334.83 | 508.73 | 17.96 | 0.00 | 292.67 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:49 | 994.52 | 14.76 | 0.00 | 380.33 | 582.03 | 18.37 | 0.00 | 348.33 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:40 | 1051.62 | 16.96 | 42.50 | 373.67 | 629.76 | 20.22 | 41.17 | 338.67 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:00 | 984.41 | 17.01 | 45.17 | 382.67 | 582.81 | 18.57 | 0.00 | 358.67 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:30 | 812.83 | 14.50 | 0.00 | 364.00 | 524.92 | 18.12 | 0.00 | 333.50 |
September | 328.83 | 0.53 | 0.48 | 01-SEP-07:10 | 706.97 | 13.63 | 0.00 | 301.83 | 457.43 | 17.22 | 0.00 | 253.17 |
October | 296.17 | 0.56 | 0.48 | 01-OCT-09:39 | 540.01 | 11.98 | 0.00 | 253.67 | 357.43 | 15.74 | 0.00 | 162.83 |
November | 300.00 | 0.58 | 0.48 | 01-NOV-08:20 | 515.19 | 11.41 | 0.00 | 232.50 | 335.52 | 15.10 | 0.00 | 151.00 |
December | 297.00 | 0.59 | 0.48 | 01-DEC-08:00 | 460.02 | 10.90 | 0.00 | 219.67 | 308.61 | 14.79 | 0.00 | 120.00 |
Annual Sum or Average | 4065.67 | 0.54 | 747.72 | 13.79 | 87.67 | 3620.00 | 465.35 | 17.20 | 41.17 | 2907.17 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 460.02 | 10.90 | 0.00 | 219.67 | 308.61 | 14.79 | 0.00 | 120.00 | |
Maximum of Months | 408.67 | 0.59 | 0.48 | 1051.62 | 17.01 | 45.17 | 382.67 | 629.76 | 20.22 | 41.17 | 358.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.54 | 0.48 | 01-JAN-09:09 | 2180.92 | 22.14 | 105.17 | 248.83 | 804.57 | 21.13 | 50.17 | 207.83 |
February | 279.67 | 0.53 | 0.48 | 01-FEB-09:20 | 1946.53 | 19.86 | 73.50 | 251.33 | 1057.94 | 22.41 | 60.00 | 211.00 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:50 | 2224.51 | 20.61 | 100.17 | 307.50 | 1193.15 | 21.82 | 71.67 | 263.17 |
April | 358.33 | 0.52 | 0.48 | 01-APR-07:00 | 3081.86 | 19.02 | 82.33 | 329.00 | 1134.94 | 17.55 | 0.00 | 294.50 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-07:30 | 2855.44 | 16.55 | 52.50 | 363.50 | 1149.04 | 17.68 | 0.00 | 324.67 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-07:19 | 2429.75 | 13.74 | 0.00 | 359.83 | 1305.94 | 17.63 | 0.00 | 321.50 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-07:19 | 2560.38 | 13.87 | 5.67 | 368.17 | 1348.82 | 17.55 | 0.00 | 339.83 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:00 | 3167.56 | 18.68 | 88.17 | 350.33 | 1272.90 | 17.75 | 7.00 | 321.33 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-07:49 | 2739.84 | 21.44 | 101.83 | 302.67 | 1446.05 | 22.36 | 71.83 | 267.00 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 2026.26 | 20.10 | 81.83 | 281.00 | 1048.21 | 20.98 | 52.50 | 235.33 |
November | 300.00 | 0.55 | 0.48 | 01-NOV-08:20 | 2116.41 | 21.76 | 101.83 | 252.00 | 1155.12 | 22.87 | 75.17 | 210.50 |
December | 297.00 | 0.56 | 0.48 | 01-DEC-08:50 | 1863.59 | 20.23 | 88.17 | 239.83 | 1060.80 | 22.87 | 79.67 | 194.00 |
Annual Sum or Average | 4065.67 | 0.53 | 2475.43 | 18.72 | 881.17 | 3654.00 | 1177.71 | 19.96 | 468.00 | 3190.67 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1863.59 | 13.74 | 0.00 | 239.83 | 804.57 | 17.55 | 0.00 | 194.00 | |
Maximum of Months | 408.67 | 0.56 | 0.48 | 3167.56 | 22.14 | 105.17 | 368.17 | 1446.05 | 22.87 | 79.67 | 339.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:30 | 7710.19 | 36.97 | 284.83 | 279.17 | 1612.17 | 23.50 | 97.50 | 264.67 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:30 | 6848.64 | 35.29 | 275.33 | 274.00 | 1181.16 | 21.69 | 61.00 | 251.50 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-06:49 | 1957.96 | 15.07 | 11.17 | 314.00 | 941.11 | 17.96 | 5.50 | 282.83 |
April | 358.33 | 0.52 | 0.48 | 01-APR-07:19 | 1265.38 | 14.41 | 0.00 | 331.83 | 772.04 | 17.97 | 0.00 | 293.83 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-06:00 | 1090.22 | 14.30 | 0.00 | 362.17 | 630.11 | 17.78 | 0.00 | 315.83 |
June | 381.00 | 0.53 | 0.48 | 01-JUN-06:00 | 965.89 | 14.04 | 0.00 | 353.67 | 577.20 | 17.54 | 0.00 | 303.50 |
July | 408.67 | 0.53 | 0.48 | 01-JUL-06:49 | 971.69 | 14.19 | 0.00 | 363.00 | 600.55 | 17.73 | 0.00 | 324.00 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:30 | 1087.79 | 14.24 | 0.00 | 351.33 | 679.60 | 17.78 | 0.00 | 311.50 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-06:00 | 1542.83 | 14.79 | 11.00 | 307.17 | 889.53 | 17.81 | 2.00 | 275.17 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 3401.15 | 21.87 | 115.67 | 302.67 | 1097.59 | 18.20 | 14.00 | 272.83 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7463.37 | 36.66 | 292.67 | 278.50 | 1446.26 | 23.11 | 92.67 | 269.17 |
December | 297.00 | 0.51 | 0.48 | 01-DEC-07:19 | 7567.53 | 37.04 | 285.67 | 279.67 | 2077.86 | 26.76 | 143.00 | 270.00 |
Annual Sum or Average | 4065.67 | 0.52 | 3176.15 | 21.31 | 1276.33 | 3797.17 | 995.09 | 19.55 | 415.67 | 3434.83 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 965.89 | 14.04 | 0.00 | 274.00 | 577.20 | 17.54 | 0.00 | 251.50 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 7710.19 | 37.04 | 292.67 | 363.00 | 2077.86 | 26.76 | 143.00 | 324.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-07:19 | 1666.68 | 21.14 | 85.00 | 263.67 | 840.13 | 21.96 | 57.00 | 219.00 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-07:10 | 1791.39 | 19.84 | 70.83 | 265.00 | 947.19 | 22.24 | 54.83 | 216.67 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-06:49 | 2232.11 | 21.16 | 106.50 | 313.50 | 1214.82 | 22.32 | 77.67 | 270.00 |
April | 358.33 | 0.51 | 0.48 | 01-APR-05:00 | 2205.27 | 18.81 | 77.33 | 334.83 | 1179.64 | 21.61 | 65.17 | 302.00 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:19 | 2168.48 | 19.61 | 99.33 | 375.50 | 1175.08 | 21.17 | 69.33 | 323.50 |
June | 381.00 | 0.52 | 0.48 | 01-JUN-06:19 | 2165.86 | 18.77 | 88.83 | 364.00 | 905.56 | 19.22 | 36.33 | 317.17 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-05:30 | 2384.32 | 19.26 | 99.17 | 373.00 | 1248.32 | 20.74 | 68.67 | 335.00 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-06:49 | 2351.94 | 18.66 | 85.67 | 357.67 | 1211.78 | 21.30 | 69.67 | 322.33 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-06:40 | 2512.45 | 20.00 | 92.83 | 309.67 | 936.41 | 20.29 | 43.83 | 268.33 |
October | 296.17 | 0.54 | 0.48 | 01-OCT-09:39 | 2257.50 | 20.02 | 85.00 | 278.83 | 924.68 | 20.21 | 42.67 | 230.33 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-06:40 | 1838.62 | 19.66 | 79.50 | 258.83 | 1022.25 | 22.28 | 66.33 | 224.17 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-07:19 | 1646.79 | 20.76 | 86.17 | 261.83 | 838.31 | 21.48 | 58.83 | 215.83 |
Annual Sum or Average | 4065.67 | 0.52 | 2125.81 | 19.74 | 1056.17 | 3756.33 | 1051.15 | 21.19 | 710.33 | 3244.33 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1646.79 | 18.66 | 70.83 | 258.83 | 838.31 | 19.22 | 36.33 | 215.83 | |
Maximum of Months | 408.67 | 0.54 | 0.48 | 2512.45 | 21.16 | 106.50 | 375.50 | 1248.32 | 22.32 | 77.67 | 335.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.57 | 0.48 | 01-JAN-09:09 | 506.50 | 11.57 | 0.00 | 229.00 | 333.12 | 15.48 | 0.00 | 142.00 |
February | 279.67 | 0.55 | 0.48 | 01-FEB-09:20 | 608.46 | 12.55 | 0.00 | 244.17 | 377.18 | 16.16 | 0.00 | 164.67 |
March | 338.17 | 0.54 | 0.48 | 01-MAR-08:50 | 714.60 | 13.08 | 0.00 | 303.50 | 430.12 | 16.51 | 0.00 | 241.67 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 791.95 | 14.38 | 0.00 | 334.83 | 508.71 | 17.96 | 0.00 | 292.67 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:49 | 994.49 | 14.76 | 0.00 | 380.33 | 581.99 | 18.37 | 0.00 | 348.33 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:40 | 1051.59 | 16.96 | 42.50 | 373.67 | 629.72 | 20.22 | 41.17 | 338.67 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:00 | 984.39 | 17.01 | 45.17 | 382.67 | 582.78 | 18.57 | 0.00 | 358.67 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:30 | 812.82 | 14.50 | 0.00 | 364.00 | 524.90 | 18.12 | 0.00 | 333.50 |
September | 328.83 | 0.53 | 0.48 | 01-SEP-07:10 | 706.96 | 13.64 | 0.00 | 301.83 | 457.41 | 17.22 | 0.00 | 253.17 |
October | 296.17 | 0.56 | 0.48 | 01-OCT-09:39 | 540.00 | 11.98 | 0.00 | 253.67 | 357.42 | 15.75 | 0.00 | 162.83 |
November | 300.00 | 0.58 | 0.48 | 01-NOV-08:20 | 515.19 | 11.42 | 0.00 | 232.50 | 335.50 | 15.11 | 0.00 | 151.00 |
December | 297.00 | 0.59 | 0.48 | 01-DEC-08:00 | 460.02 | 10.90 | 0.00 | 219.67 | 308.59 | 14.79 | 0.00 | 120.00 |
Annual Sum or Average | 4065.67 | 0.54 | 747.70 | 13.79 | 87.67 | 3619.83 | 465.33 | 17.20 | 41.17 | 2907.17 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 460.02 | 10.90 | 0.00 | 219.67 | 308.59 | 14.79 | 0.00 | 120.00 | |
Maximum of Months | 408.67 | 0.59 | 0.48 | 1051.59 | 17.01 | 45.17 | 382.67 | 629.72 | 20.22 | 41.17 | 358.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.54 | 0.48 | 01-JAN-09:09 | 2180.90 | 22.15 | 105.17 | 248.83 | 804.54 | 21.13 | 50.17 | 207.83 |
February | 279.67 | 0.53 | 0.48 | 01-FEB-09:20 | 1946.51 | 19.86 | 73.50 | 251.33 | 1057.89 | 22.41 | 60.00 | 211.00 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:50 | 2224.47 | 20.61 | 100.17 | 307.50 | 1193.10 | 21.82 | 71.67 | 263.17 |
April | 358.33 | 0.52 | 0.48 | 01-APR-07:00 | 3081.84 | 19.02 | 82.33 | 329.00 | 1134.89 | 17.55 | 0.00 | 294.50 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-07:30 | 2855.39 | 16.56 | 52.50 | 363.50 | 1148.98 | 17.68 | 0.00 | 324.67 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-07:19 | 2429.71 | 13.75 | 0.00 | 359.83 | 1305.88 | 17.63 | 0.00 | 321.50 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-07:19 | 2560.36 | 13.88 | 5.67 | 368.17 | 1348.77 | 17.55 | 0.00 | 339.83 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:00 | 3167.54 | 18.69 | 88.17 | 350.33 | 1272.85 | 17.75 | 7.00 | 321.33 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-07:49 | 2739.81 | 21.44 | 101.83 | 302.67 | 1445.99 | 22.36 | 71.83 | 267.00 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 2026.25 | 20.10 | 81.83 | 281.00 | 1048.17 | 20.98 | 52.50 | 235.33 |
November | 300.00 | 0.55 | 0.48 | 01-NOV-08:20 | 2116.40 | 21.76 | 101.83 | 252.00 | 1155.08 | 22.87 | 75.17 | 210.50 |
December | 297.00 | 0.56 | 0.48 | 01-DEC-08:50 | 1863.59 | 20.23 | 88.17 | 239.83 | 1060.76 | 22.87 | 79.67 | 194.00 |
Annual Sum or Average | 4065.67 | 0.53 | 2475.41 | 18.72 | 881.17 | 3654.00 | 1177.66 | 19.96 | 468.00 | 3190.67 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1863.59 | 13.75 | 0.00 | 239.83 | 804.54 | 17.55 | 0.00 | 194.00 | |
Maximum of Months | 408.67 | 0.56 | 0.48 | 3167.54 | 22.15 | 105.17 | 368.17 | 1445.99 | 22.87 | 79.67 | 339.83 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.483959E+09 | 8867.46 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.471531E+09 | 8867.46 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.903515E+09 | 8867.46 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.343910E+09 | 8867.46 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.288846E+09 | 8867.46 | 15-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104534E+09 | 6596.91 | 12-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4118171.51 | 2342.83 | 17-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6026485.66 | 3544.62 | 28-AUG-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29817917.68 | 5618.98 | 20-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87814815.94 | 8867.46 | 12-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214248E+09 | 8867.46 | 03-NOV-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.397551E+09 | 8867.46 | 01-DEC-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.333587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4118171.51 | 2342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.903515E+09 | 8867.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 14418675.17 | 5887.35 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5844828.22 | 1851.42 | 27-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10587618.94 | 5887.35 | 30-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 100830.57 | 672.20 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 202750.74 | 781.54 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31154703.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14418675.17 | 5887.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 84246047.63 | 7964.07 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22251712.56 | 5904.40 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 47077222.52 | 7958.68 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4120443.41 | 7321.77 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 260780.49 | 1232.78 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14226401.11 | 7822.40 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172183E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84246047.63 | 7964.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 31270660.28 | 5848.28 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6675033.44 | 2776.99 | 28-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18317045.92 | 5848.28 | 30-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2980844.49 | 4455.56 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4131484.64 | 3194.59 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63375068.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31270660.28 | 5848.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3081390.27 | 10501.78 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3081390.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3081390.27 | 10501.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 20813380.01 | 9650.97 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3139651.05 | 2694.27 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15965288.51 | 9650.97 | 30-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2261336.91 | 5115.45 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 784555.66 | 4287.29 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42964212.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20813380.01 | 9650.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 37854361.75 | 6389.65 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11482628.21 | 3429.54 | 27-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15541450.58 | 6053.61 | 30-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 289557.18 | 1930.38 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4724639.26 | 3934.64 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 69892636.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37854361.75 | 6389.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 81821638.42 | 8713.49 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11362767.10 | 5636.78 | 27-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 32007660.53 | 8703.50 | 08-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2658053.84 | 5744.01 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1019802.22 | 2505.88 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16580655.20 | 8299.58 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81821638.42 | 8713.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 70603242.03 | 6351.70 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18892713.38 | 4377.88 | 28-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33815217.99 | 6351.70 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4080364.73 | 5922.98 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2497328.97 | 2082.94 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24038689.97 | 6351.70 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 70603242.03 | 6351.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 91666719.41 | 28011.02 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11276515.14 | 15312.41 | 27-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14265624.52 | 22047.76 | 30-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 507712.23 | 3384.75 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5870191.84 | 15605.81 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91666719.41 | 28011.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154894E+09 | 11918.51 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 91848731.96 | 11024.51 | 27-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151575E+09 | 11918.51 | 08-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23213843.66 | 11726.51 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7648168.06 | 7117.10 | 15-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1991724.09 | 3465.74 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12678422.80 | 9470.05 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 64139595.45 | 11918.51 | 13-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.507990E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.154894E+09 | 11918.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.163563E+09 | 7772.68 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 98527356.01 | 7259.50 | 10-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 97453170.14 | 7772.68 | 01-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5661379.76 | 6339.61 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 110162.95 | 136.61 | 16-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3333069.88 | 7384.80 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16191890.27 | 6170.31 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 80846061.90 | 7772.68 | 13-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.465686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163563E+09 | 7772.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.371759E+09 | 9863.54 | 30-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167282E+09 | 9889.94 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218855E+09 | 9855.80 | 28-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24923019.45 | 9806.65 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1768217.37 | 3537.81 | 15-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10238839.36 | 9826.70 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 82945509.21 | 9852.73 | 18-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220329E+09 | 9846.09 | 11-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.371759E+09 | 9889.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.294176E+09 | 7751.94 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167999E+09 | 7424.30 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195312E+09 | 7751.94 | 08-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29750250.87 | 7517.57 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8822460.40 | 4101.97 | 15-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2560.11 | 17.07 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15531110.11 | 6961.50 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 87387077.19 | 7328.14 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201351E+09 | 7751.94 | 13-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.294176E+09 | 7751.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 56219149.68 | 4494.98 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18509904.41 | 2189.39 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 288535.75 | 652.13 | 01-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6485234.90 | 1751.15 | 12-DEC-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81502824.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 56219149.68 | 4494.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138027E+09 | 6003.84 | 03-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8203623.20 | 1707.32 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 83729286.50 | 3839.28 | 30-MAR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1536747.11 | 1493.29 | 01-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 203322.68 | 340.29 | 24-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 50737672.06 | 3039.30 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.282437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138027E+09 | 6003.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.270575E+09 | 7929.09 | 03-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 49364462.14 | 3577.80 | 09-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170476E+09 | 5719.11 | 30-MAR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5495085.14 | 3167.94 | 01-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 228621.61 | 391.30 | 12-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8545508.59 | 2252.77 | 24-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148300E+09 | 4889.71 | 22-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.652985E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.270575E+09 | 7929.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.884321E+10 | 0.809952E+10 | 42067.80 | 18-JAN-13:30 | 42067.80 | 0.00 |
February | 0.00 | 0.00 | 0.509901E+10 | 0.432781E+10 | 37886.24 | 01-FEB-12:00 | 37886.24 | 0.00 |
March | 0.00 | 0.00 | 0.612256E+10 | 0.479062E+10 | 40681.77 | 23-MAR-15:10 | 30189.55 | 0.00 |
April | 0.00 | 0.00 | 0.136394E+11 | 0.112621E+11 | 47029.37 | 26-APR-13:00 | 45685.11 | 0.00 |
May | 0.00 | 0.00 | 0.146400E+11 | 0.122661E+11 | 38385.81 | 03-MAY-13:00 | 38385.81 | 0.00 |
June | 0.00 | 0.00 | 0.273446E+11 | 0.204196E+11 | 60281.38 | 29-JUN-13:00 | 38450.76 | 0.00 |
July | 0.00 | 0.00 | 0.457692E+11 | 0.303879E+11 | 84272.07 | 31-JUL-15:40 | 49135.74 | 0.00 |
August | 0.00 | 0.00 | 0.530155E+11 | 0.342860E+11 | 83300.01 | 18-AUG-15:50 | 48092.09 | 0.00 |
September | 0.00 | 0.00 | 0.326364E+11 | 0.233693E+11 | 70852.79 | 22-SEP-12:30 | 37183.77 | 0.00 |
October | 0.00 | 0.00 | 0.361133E+11 | 0.285933E+11 | 78193.07 | 03-OCT-13:20 | 48171.22 | 0.00 |
November | 0.00 | 0.00 | 0.100793E+11 | 0.891772E+10 | 40942.95 | 28-NOV-14:00 | 40942.95 | 0.00 |
December | 0.00 | 0.00 | 0.105375E+11 | 0.102135E+11 | 41903.87 | 19-DEC-13:10 | 41903.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.263840E+12 | 0.196933E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.509901E+10 | 0.432781E+10 | 37886.24 | 30189.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.530155E+11 | 0.342860E+11 | 84272.07 | 49135.74 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.731082E+10 | 0.659307E+10 | 35655.26 | 18-JAN-14:00 | 35655.26 | 0.00 |
February | 0.00 | 0.00 | 0.425236E+10 | 0.359766E+10 | 30442.27 | 01-FEB-12:00 | 30442.27 | 0.00 |
March | 0.00 | 0.00 | 0.541944E+10 | 0.423096E+10 | 37752.59 | 23-MAR-15:00 | 28686.17 | 0.00 |
April | 0.00 | 0.00 | 0.121716E+11 | 0.101026E+11 | 43112.78 | 26-APR-14:10 | 41412.89 | 0.00 |
May | 0.00 | 0.00 | 0.125422E+11 | 0.104637E+11 | 33788.55 | 03-MAY-13:00 | 33788.55 | 0.00 |
June | 0.00 | 0.00 | 0.237637E+11 | 0.178882E+11 | 52220.99 | 29-JUN-13:00 | 33638.16 | 0.00 |
July | 0.00 | 0.00 | 0.397158E+11 | 0.266314E+11 | 75842.75 | 31-JUL-15:40 | 44379.79 | 0.00 |
August | 0.00 | 0.00 | 0.458001E+11 | 0.299620E+11 | 74743.34 | 18-AUG-15:50 | 43312.88 | 0.00 |
September | 0.00 | 0.00 | 0.279158E+11 | 0.202313E+11 | 59558.56 | 29-SEP-15:20 | 59558.56 | 0.00 |
October | 0.00 | 0.00 | 0.302804E+11 | 0.241428E+11 | 70038.67 | 03-OCT-13:20 | 42638.49 | 0.00 |
November | 0.00 | 0.00 | 0.822610E+10 | 0.722455E+10 | 33403.97 | 28-NOV-14:00 | 33403.97 | 0.00 |
December | 0.00 | 0.00 | 0.864162E+10 | 0.834992E+10 | 35691.99 | 05-DEC-15:10 | 35691.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.226040E+12 | 0.169418E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.425236E+10 | 0.359766E+10 | 30442.27 | 28686.17 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.458001E+11 | 0.299620E+11 | 75842.75 | 59558.56 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.697836E+10 | 0.613798E+10 | 37104.04 | 18-JAN-13:30 | 37104.04 | 0.00 |
February | 0.00 | 0.00 | 0.404766E+10 | 0.333354E+10 | 30925.52 | 01-FEB-12:00 | 30925.52 | 0.00 |
March | 0.00 | 0.00 | 0.540857E+10 | 0.412083E+10 | 39874.12 | 23-MAR-15:00 | 29916.59 | 0.00 |
April | 0.00 | 0.00 | 0.127480E+11 | 0.103006E+11 | 51967.78 | 26-APR-14:00 | 50021.40 | 0.00 |
May | 0.00 | 0.00 | 0.130490E+11 | 0.105969E+11 | 37077.47 | 03-MAY-13:00 | 37077.47 | 0.00 |
June | 0.00 | 0.00 | 0.251923E+11 | 0.185158E+11 | 57337.93 | 29-JUN-13:00 | 36664.71 | 0.00 |
July | 0.00 | 0.00 | 0.423633E+11 | 0.279900E+11 | 87798.92 | 31-JUL-15:10 | 53380.98 | 0.00 |
August | 0.00 | 0.00 | 0.485651E+11 | 0.311686E+11 | 86849.48 | 18-AUG-15:30 | 51863.96 | 0.00 |
September | 0.00 | 0.00 | 0.284996E+11 | 0.203673E+11 | 68935.58 | 29-SEP-13:40 | 68935.58 | 0.00 |
October | 0.00 | 0.00 | 0.303643E+11 | 0.239440E+11 | 74419.57 | 03-OCT-13:10 | 46153.88 | 0.00 |
November | 0.00 | 0.00 | 0.766985E+10 | 0.657386E+10 | 35395.92 | 19-NOV-13:02 | 35395.92 | 0.00 |
December | 0.00 | 0.00 | 0.804751E+10 | 0.771560E+10 | 38390.85 | 05-DEC-15:00 | 38390.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.232934E+12 | 0.170765E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.404766E+10 | 0.333354E+10 | 30925.52 | 29916.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.485651E+11 | 0.311686E+11 | 87798.92 | 68935.58 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1618.79 | 5589.41 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1629.63 | 5589.86 | 14-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1717.99 | 5554.96 | 06-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1574.84 | 5452.12 | 05-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1592.73 | 5330.46 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1599.07 | 5196.83 | 02-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1447.75 | 5083.54 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1588.35 | 5074.60 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1500.18 | 5173.49 | 29-SEP-11:17 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1530.38 | 5291.97 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1590.38 | 5419.53 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1558.20 | 5514.87 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 1578.75 | ||||
Minimum of Months | 0.00 | 0.00 | 1447.75 | 5074.60 | ||
Maximum of Months | 0.00 | 0.00 | 1717.99 | 5589.86 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.229596E+10 | 0.33 | 4113.73 | 18-JAN-15:20 | 0.98 |
February | 0.200387E+10 | 0.32 | 3919.44 | 03-FEB-14:00 | 0.97 |
March | 0.225085E+10 | 0.34 | 4134.04 | 23-MAR-15:10 | 0.98 |
April | 0.254225E+10 | 0.35 | 4560.60 | 28-APR-06:03 | 1.04 |
May | 0.269947E+10 | 0.36 | 4711.34 | 05-MAY-06:03 | 1.06 |
June | 0.311177E+10 | 0.39 | 4711.34 | 06-JUN-06:03 | 1.06 |
July | 0.369649E+10 | 0.41 | 6324.17 | 24-JUL-06:03 | 1.27 |
August | 0.423297E+10 | 0.45 | 5935.26 | 18-AUG-15:10 | 1.22 |
September | 0.340731E+10 | 0.40 | 6078.12 | 30-SEP-06:03 | 1.25 |
October | 0.350035E+10 | 0.40 | 6943.16 | 16-OCT-08:00 | 1.36 |
November | 0.260839E+10 | 0.35 | 4711.34 | 01-NOV-06:02 | 1.07 |
December | 0.238962E+10 | 0.34 | 4022.08 | 19-DEC-15:50 | 0.98 |
Annual Sum or Average | 0.347393E+11 | 0.37 | |||
Minimum of Months | 0.200387E+10 | 0.32 | 3919.44 | 0.97 | |
Maximum of Months | 0.423297E+10 | 0.45 | 6943.16 | 1.36 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.173229E+10 | 0.31 | 3639.52 | 18-JAN-15:30 | 0.99 |
February | 0.155244E+10 | 0.31 | 3464.31 | 03-FEB-15:00 | 0.97 |
March | 0.174755E+10 | 0.32 | 4079.24 | 23-MAR-15:20 | 1.05 |
April | 0.214524E+10 | 0.35 | 4549.39 | 26-APR-14:30 | 1.13 |
May | 0.217093E+10 | 0.35 | 4005.93 | 03-MAY-15:20 | 1.05 |
June | 0.263056E+10 | 0.39 | 4427.92 | 30-JUN-16:00 | 1.11 |
July | 0.313076E+10 | 0.41 | 5488.02 | 31-JUL-14:50 | 1.26 |
August | 0.358660E+10 | 0.45 | 5468.70 | 18-AUG-15:00 | 1.26 |
September | 0.281363E+10 | 0.39 | 7536.56 | 29-SEP-16:00 | 1.55 |
October | 0.276942E+10 | 0.38 | 8001.40 | 16-OCT-16:00 | 1.61 |
November | 0.190332E+10 | 0.33 | 3417.61 | 10-NOV-14:40 | 0.95 |
December | 0.177684E+10 | 0.31 | 3582.41 | 05-DEC-15:20 | 0.99 |
Annual Sum or Average | 0.279596E+11 | 0.36 | |||
Minimum of Months | 0.155244E+10 | 0.31 | 3417.61 | 0.95 | |
Maximum of Months | 0.358660E+10 | 0.45 | 8001.40 | 1.61 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.159829E+10 | 0.29 | 3336.24 | 18-JAN-15:20 | 0.88 |
February | 0.143723E+10 | 0.29 | 2989.98 | 03-FEB-15:00 | 0.83 |
March | 0.167035E+10 | 0.31 | 3896.97 | 23-MAR-15:20 | 0.95 |
April | 0.203968E+10 | 0.33 | 4752.31 | 26-APR-14:30 | 1.08 |
May | 0.206319E+10 | 0.33 | 4173.15 | 03-MAY-15:00 | 1.00 |
June | 0.253082E+10 | 0.37 | 4502.82 | 30-JUN-16:00 | 1.04 |
July | 0.301356E+10 | 0.39 | 5715.57 | 31-JUL-14:40 | 1.20 |
August | 0.339619E+10 | 0.41 | 5583.49 | 17-AUG-15:20 | 1.18 |
September | 0.256815E+10 | 0.36 | 7542.87 | 29-SEP-16:00 | 1.43 |
October | 0.247234E+10 | 0.35 | 7978.76 | 16-OCT-15:50 | 1.49 |
November | 0.166593E+10 | 0.30 | 3161.36 | 10-NOV-14:30 | 0.85 |
December | 0.162211E+10 | 0.29 | 3255.34 | 19-DEC-15:20 | 0.87 |
Annual Sum or Average | 0.260778E+11 | 0.33 | |||
Minimum of Months | 0.143723E+10 | 0.29 | 2989.98 | 0.83 | |
Maximum of Months | 0.339619E+10 | 0.41 | 7978.76 | 1.49 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 56.57 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 56.62 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 56.08 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.01 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.14 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.08 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 56.45 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 56.07 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 56.96 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.26 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.39 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 56.75 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.01 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.26 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 56.53 | 56.53 | 1618.79 | 5589.41 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.07 | 57.07 | 1629.63 | 5589.86 | 14-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.55 | 56.55 | 1717.99 | 5554.96 | 06-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.61 | 57.61 | 1574.84 | 5452.12 | 05-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.47 | 57.47 | 1592.73 | 5330.46 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.47 | 57.47 | 1599.07 | 5196.83 | 02-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.71 | 57.71 | 1447.75 | 5083.54 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.41 | 56.41 | 1588.35 | 5074.60 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.32 | 57.32 | 1500.18 | 5173.49 | 29-SEP-11:17 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.57 | 56.57 | 1530.38 | 5291.97 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.77 | 56.77 | 1590.38 | 5419.53 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.18 | 57.18 | 1558.20 | 5514.87 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 1578.75 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.41 | 56.41 | 1447.75 | 5074.60 | ||
Maximum of Months | 0.00 | 0.00 | 57.71 | 57.71 | 1717.99 | 5589.86 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.514501E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.383673E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.478534E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.629550E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.667952E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.984715E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.145831E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.167760E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.114393E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.125029E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.537794E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.542172E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.102690E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.383673E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.167760E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.381149E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.271050E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.322437E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.520316E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.535409E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.841399E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.125974E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.144397E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.969447E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.103043E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.401051E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.399066E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.837547E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.271050E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.144397E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.448360E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.304989E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.373559E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.533460E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.541103E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.868770E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.131525E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.149411E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.965389E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.101420E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.386440E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.425497E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.867112E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.304989E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.149411E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.229596E+10 | 0.884321E+10 | 0.670113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200387E+10 | 0.509901E+10 | 0.506302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225085E+10 | 0.612256E+10 | 0.998007E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.254225E+10 | 0.136394E+11 | 0.351401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.269947E+10 | 0.146400E+11 | 0.288846E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.311177E+10 | 0.273446E+11 | 0.104534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.369649E+10 | 0.457692E+11 | 4118171.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.423297E+10 | 0.530155E+11 | 6026485.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.340731E+10 | 0.326364E+11 | 29817917.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.350035E+10 | 0.361133E+11 | 87814815.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.260839E+10 | 0.100793E+11 | 0.214509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.238962E+10 | 0.105375E+11 | 0.422597E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.347393E+11 | 0.263840E+12 | 0.368409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.200387E+10 | 0.509901E+10 | 4118171.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.423297E+10 | 0.530155E+11 | 0.998007E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.173229E+10 | 0.731082E+10 | 0.352201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155244E+10 | 0.425236E+10 | 53081382.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174755E+10 | 0.541944E+10 | 0.181059E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214524E+10 | 0.121716E+11 | 10826059.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.217093E+10 | 0.125422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.263056E+10 | 0.237637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.313076E+10 | 0.397158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.358660E+10 | 0.458001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.281363E+10 | 0.279158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.276942E+10 | 0.302804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190332E+10 | 0.822610E+10 | 3720453.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177684E+10 | 0.864162E+10 | 96866212.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279596E+11 | 0.226040E+12 | 0.697754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155244E+10 | 0.425236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.358660E+10 | 0.458001E+11 | 0.352201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.159829E+10 | 0.697836E+10 | 0.134663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143723E+10 | 0.404766E+10 | 0.586298E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167035E+10 | 0.540857E+10 | 0.847937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.203968E+10 | 0.127480E+11 | 89043578.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.206319E+10 | 0.130490E+11 | 18349008.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.253082E+10 | 0.251923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.301356E+10 | 0.423633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.339619E+10 | 0.485651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256815E+10 | 0.284996E+11 | 2560.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.247234E+10 | 0.303643E+11 | 31323365.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166593E+10 | 0.766985E+10 | 0.208256E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162211E+10 | 0.804751E+10 | 0.720836E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260778E+11 | 0.232934E+12 | 0.384868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143723E+10 | 0.404766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.339619E+10 | 0.485651E+11 | 0.134663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.229596E+10 | 0.00 | 0.00 | 0.00 | 0.223516E+10 | 0.613894E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200387E+10 | 0.00 | 0.00 | 0.00 | 0.132656E+10 | 0.506302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225085E+10 | 0.00 | 0.00 | 0.00 | 0.155499E+10 | 0.979497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.254225E+10 | 0.00 | 0.00 | 0.00 | 0.340215E+10 | 0.351112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.269947E+10 | 0.00 | 0.00 | 0.00 | 0.369120E+10 | 0.288846E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.311177E+10 | 0.00 | 0.00 | 0.00 | 0.663085E+10 | 0.104534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.369649E+10 | 0.00 | 0.00 | 0.00 | 0.108825E+11 | 4118171.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.423297E+10 | 0.00 | 0.00 | 0.00 | 0.125370E+11 | 6026485.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.340731E+10 | 0.00 | 0.00 | 0.00 | 0.800217E+10 | 29817917.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.350035E+10 | 0.00 | 0.00 | 0.00 | 0.891472E+10 | 87814815.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.260839E+10 | 0.00 | 0.00 | 0.00 | 0.255503E+10 | 0.214509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.238962E+10 | 0.00 | 0.00 | 0.00 | 0.261599E+10 | 0.416112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.347393E+11 | 0.00 | 0.00 | 0.00 | 0.643483E+11 | 0.360258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.200387E+10 | 0.00 | 0.00 | 0.00 | 0.132656E+10 | 4118171.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.423297E+10 | 0.00 | 0.00 | 0.00 | 0.125370E+11 | 0.979497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.173229E+10 | 0.00 | 0.00 | 0.00 | 0.186503E+10 | 0.214174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155244E+10 | 0.00 | 0.00 | 0.00 | 0.111319E+10 | 44877759.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174755E+10 | 0.00 | 0.00 | 0.00 | 0.137949E+10 | 97329617.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214524E+10 | 0.00 | 0.00 | 0.00 | 0.304863E+10 | 9289312.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.217093E+10 | 0.00 | 0.00 | 0.00 | 0.318316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.263056E+10 | 0.00 | 0.00 | 0.00 | 0.578343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.313076E+10 | 0.00 | 0.00 | 0.00 | 0.946666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.358660E+10 | 0.00 | 0.00 | 0.00 | 0.108531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.281363E+10 | 0.00 | 0.00 | 0.00 | 0.688083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.276942E+10 | 0.00 | 0.00 | 0.00 | 0.753491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190332E+10 | 0.00 | 0.00 | 0.00 | 0.210368E+10 | 3517131.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177684E+10 | 0.00 | 0.00 | 0.00 | 0.216770E+10 | 46128540.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279596E+11 | 0.00 | 0.00 | 0.00 | 0.553798E+11 | 0.415316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155244E+10 | 0.00 | 0.00 | 0.00 | 0.111319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.358660E+10 | 0.00 | 0.00 | 0.00 | 0.108531E+11 | 0.214174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.159829E+10 | 0.00 | 0.00 | 0.00 | 0.180925E+10 | 0.107606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143723E+10 | 0.00 | 0.00 | 0.00 | 0.107572E+10 | 0.536934E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167035E+10 | 0.00 | 0.00 | 0.00 | 0.138778E+10 | 0.677461E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.203968E+10 | 0.00 | 0.00 | 0.00 | 0.321137E+10 | 83548493.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.206319E+10 | 0.00 | 0.00 | 0.00 | 0.332949E+10 | 18349008.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.253082E+10 | 0.00 | 0.00 | 0.00 | 0.615688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.301356E+10 | 0.00 | 0.00 | 0.00 | 0.101390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.339619E+10 | 0.00 | 0.00 | 0.00 | 0.115449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256815E+10 | 0.00 | 0.00 | 0.00 | 0.708573E+10 | 2560.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.247234E+10 | 0.00 | 0.00 | 0.00 | 0.763853E+10 | 31094743.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166593E+10 | 0.00 | 0.00 | 0.00 | 0.199875E+10 | 0.199711E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162211E+10 | 0.00 | 0.00 | 0.00 | 0.206033E+10 | 0.572536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260778E+11 | 0.00 | 0.00 | 0.00 | 0.574377E+11 | 0.319569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143723E+10 | 0.00 | 0.00 | 0.00 | 0.107572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.339619E+10 | 0.00 | 0.00 | 0.00 | 0.115449E+11 | 0.107606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.151904E+10 | 31560590.08 | 0.00 | 36596531.93 | 0.00 | 0.00 | 0.159694E+11 | 0.00 | 0.85 |
February | 0.116936E+10 | 12789575.12 | 0.00 | 34463895.26 | 0.00 | 0.00 | 0.165842E+11 | 0.00 | 0.88 |
March | 0.102791E+10 | 0.00 | 0.00 | 39958507.89 | 13157578.95 | 0.00 | 0.195779E+11 | 0.00 | 0.90 |
April | 0.970948E+09 | 16575856.18 | 0.00 | 38646773.94 | 11807795.35 | 0.00 | 0.159373E+11 | 0.00 | 1.02 |
May | 0.887729E+09 | 17730024.61 | 0.00 | 42624398.00 | 0.00 | 0.00 | 0.174905E+11 | 0.00 | 1.11 |
June | 0.466864E+09 | 0.350157E+09 | 0.00 | 40628235.45 | 16363903.98 | 0.00 | 0.124452E+11 | 0.00 | 1.25 |
July | 0.396206E+09 | 0.245297E+10 | 0.00 | 26334832.76 | 0.168205E+09 | 0.00 | 0.542697E+10 | 0.00 | 1.15 |
August | 0.186914E+09 | 0.301447E+10 | 0.00 | 26207120.75 | 0.226103E+09 | 0.00 | 0.520747E+10 | 0.00 | 1.25 |
September | 0.414986E+09 | 0.762928E+09 | 0.00 | 34958616.51 | 33019770.15 | 0.00 | 0.102263E+11 | 0.00 | 1.15 |
October | 0.491211E+09 | 0.143269E+10 | 0.00 | 31599694.37 | 0.143256E+09 | 0.00 | 0.999779E+10 | 0.00 | 1.05 |
November | 0.109894E+10 | 4897243.97 | 0.00 | 41843101.45 | 9253570.85 | 0.00 | 0.183856E+11 | 0.00 | 1.01 |
December | 0.148116E+10 | 4133673.73 | 0.00 | 38381971.73 | 0.00 | 0.00 | 0.158310E+11 | 0.00 | 0.87 |
Annual Sum or Average | 0.101113E+11 | 0.810090E+10 | 0.00 | 0.432244E+09 | 0.621166E+09 | 0.00 | 0.163080E+12 | 0.00 | 1.04 |
Minimum of Months | 0.186914E+09 | 0.00 | 0.00 | 26207120.75 | 0.00 | 0.00 | 0.520747E+10 | 0.00 | 0.85 |
Maximum of Months | 0.151904E+10 | 0.301447E+10 | 0.00 | 42624398.00 | 0.226103E+09 | 0.00 | 0.195779E+11 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.519968E+10 | 3750423.36 | 0.00 | 11314160.57 | 21650445.07 | 1153694.27 | 0.575248E+10 | 0.00 | 0.52 |
February | 0.465733E+10 | 6530481.32 | 0.00 | 11617001.50 | 0.00 | 0.00 | 0.664004E+10 | 0.00 | 0.56 |
March | 0.500060E+10 | 0.00 | 0.00 | 13281997.36 | 20829510.94 | 0.00 | 0.794242E+10 | 0.00 | 0.56 |
April | 0.282514E+10 | 3738673.37 | 0.00 | 18454270.91 | 39447838.96 | 0.00 | 0.851566E+10 | 0.00 | 0.68 |
May | 0.249336E+10 | 13272572.16 | 0.00 | 21118359.00 | 0.00 | 0.00 | 0.983762E+10 | 0.00 | 0.74 |
June | 0.117964E+10 | 0.200630E+09 | 0.00 | 22895276.77 | 30176579.69 | 0.00 | 0.769684E+10 | 0.00 | 0.84 |
July | 0.827567E+09 | 0.158216E+10 | 0.00 | 15792154.44 | 0.177401E+09 | 0.00 | 0.330995E+10 | 0.00 | 0.80 |
August | 0.566769E+09 | 0.194827E+10 | 0.00 | 15681738.33 | 0.238259E+09 | 0.00 | 0.314176E+10 | 0.00 | 0.85 |
September | 0.963354E+09 | 0.505012E+09 | 0.00 | 18981104.64 | 36641359.92 | 0.00 | 0.611836E+10 | 0.00 | 0.77 |
October | 0.136882E+10 | 0.962865E+09 | 0.00 | 15978011.77 | 0.127715E+09 | 0.00 | 0.550796E+10 | 0.00 | 0.69 |
November | 0.351389E+10 | 1906146.99 | 0.00 | 16522400.77 | 13681215.41 | 0.00 | 0.857482E+10 | 0.00 | 0.62 |
December | 0.472427E+10 | 1577794.41 | 0.00 | 12975754.07 | 1378116.90 | 0.00 | 0.612602E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.333204E+11 | 0.522971E+10 | 0.00 | 0.194612E+09 | 0.707180E+09 | 1153694.27 | 0.791639E+11 | 0.00 | 0.68 |
Minimum of Months | 0.566769E+09 | 0.00 | 0.00 | 11314160.57 | 0.00 | 0.00 | 0.314176E+10 | 0.00 | 0.52 |
Maximum of Months | 0.519968E+10 | 0.194827E+10 | 0.00 | 22895276.77 | 0.238259E+09 | 1153694.27 | 0.983762E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.639987E+10 | 1634547.04 | 0.00 | 6425739.95 | 18150342.96 | 43232512.23 | 0.362765E+10 | 0.00 | 0.50 |
February | 0.570673E+10 | 2308596.70 | 0.00 | 7234652.01 | 0.00 | 1946456.86 | 0.470624E+10 | 0.00 | 0.53 |
March | 0.679080E+10 | 0.00 | 0.00 | 8168456.26 | 10493169.29 | 2611180.84 | 0.548235E+10 | 0.00 | 0.54 |
April | 0.374614E+10 | 353820.81 | 0.00 | 15680762.96 | 19855769.44 | 0.00 | 0.750371E+10 | 0.00 | 0.67 |
May | 0.357999E+10 | 4014816.56 | 0.00 | 18312603.81 | 0.00 | 0.00 | 0.863120E+10 | 0.00 | 0.72 |
June | 0.187462E+10 | 0.100942E+09 | 0.00 | 21001705.51 | 5596161.65 | 0.00 | 0.715919E+10 | 0.00 | 0.86 |
July | 0.121082E+10 | 0.128957E+10 | 0.00 | 14157383.60 | 0.155943E+09 | 0.00 | 0.294253E+10 | 0.00 | 0.84 |
August | 0.837702E+09 | 0.172480E+10 | 0.00 | 14358513.35 | 0.205517E+09 | 0.00 | 0.266427E+10 | 0.00 | 0.90 |
September | 0.184844E+10 | 0.359698E+09 | 0.00 | 15888016.60 | 46440930.93 | 0.00 | 0.498098E+10 | 0.00 | 0.76 |
October | 0.254004E+10 | 0.835483E+09 | 0.00 | 11622092.31 | 0.137195E+09 | 0.00 | 0.359199E+10 | 0.00 | 0.67 |
November | 0.497289E+10 | 5653.36 | 0.00 | 10499493.32 | 4889512.54 | 0.00 | 0.581767E+10 | 0.00 | 0.57 |
December | 0.589501E+10 | 145739.15 | 0.00 | 7250911.39 | 896217.82 | 802276.89 | 0.380639E+10 | 0.00 | 0.51 |
Annual Sum or Average | 0.454031E+11 | 0.431896E+10 | 0.00 | 0.150600E+09 | 0.604977E+09 | 48592426.82 | 0.609142E+11 | 0.00 | 0.67 |
Minimum of Months | 0.837702E+09 | 0.00 | 0.00 | 6425739.95 | 0.00 | 0.00 | 0.266427E+10 | 0.00 | 0.50 |
Maximum of Months | 0.679080E+10 | 0.172480E+10 | 0.00 | 21001705.51 | 0.205517E+09 | 43232512.23 | 0.863120E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163784E+10 | 303553.97 | 0.00 | 443081.77 | 3865679.31 | 0.185384E+09 | 0.217357E+09 | 0.00 | 0.48 |
February | 0.159419E+10 | 447146.83 | 0.00 | 476756.03 | 0.00 | 70202852.20 | 0.394903E+09 | 0.00 | 0.49 |
March | 0.194811E+10 | 0.00 | 0.00 | 712023.11 | 2216484.66 | 85885671.49 | 0.456701E+09 | 0.00 | 0.51 |
April | 0.118679E+10 | 81573.49 | 0.00 | 2332333.42 | 4194157.84 | 12243081.18 | 0.104972E+10 | 0.00 | 0.64 |
May | 0.108666E+10 | 919605.95 | 0.00 | 3289807.08 | 0.00 | 186857.49 | 0.144938E+10 | 0.00 | 0.72 |
June | 0.573967E+09 | 25229365.19 | 0.00 | 4630852.78 | 1182083.90 | 0.00 | 0.141427E+10 | 0.00 | 0.92 |
July | 0.334821E+09 | 0.347455E+09 | 0.00 | 2897137.94 | 33138975.30 | 0.00 | 0.574153E+09 | 0.00 | 0.93 |
August | 0.309832E+09 | 0.425444E+09 | 0.00 | 2518397.74 | 47106309.91 | 0.00 | 0.410825E+09 | 0.00 | 0.95 |
September | 0.665760E+09 | 91487865.88 | 0.00 | 2593005.41 | 11365739.55 | 0.00 | 0.707471E+09 | 0.00 | 0.74 |
October | 0.784913E+09 | 0.201104E+09 | 0.00 | 1655609.23 | 32469535.50 | 2389349.96 | 0.440893E+09 | 0.00 | 0.65 |
November | 0.150857E+10 | 857.81 | 0.00 | 766325.75 | 1032817.56 | 38235322.16 | 0.519002E+09 | 0.00 | 0.51 |
December | 0.162126E+10 | 5534.97 | 0.00 | 417907.46 | 214558.84 | 0.110947E+09 | 0.222591E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.132527E+11 | 0.109248E+10 | 0.00 | 22733237.73 | 0.136786E+09 | 0.505474E+09 | 0.785726E+10 | 0.00 | 0.67 |
Minimum of Months | 0.309832E+09 | 0.00 | 0.00 | 417907.46 | 0.00 | 0.00 | 0.217357E+09 | 0.00 | 0.48 |
Maximum of Months | 0.194811E+10 | 0.425444E+09 | 0.00 | 4630852.78 | 47106309.91 | 0.185384E+09 | 0.144938E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.115579E+10 | 1039121.41 | 0.00 | 882954.23 | 2506984.74 | 76140873.65 | 0.535828E+09 | 0.00 | 0.66 |
February | 0.110568E+10 | 418433.00 | 0.00 | 1147884.71 | 0.00 | 28120996.57 | 0.710651E+09 | 0.00 | 0.71 |
March | 0.129714E+10 | 171137.40 | 0.00 | 1622086.55 | 1791081.91 | 34220007.00 | 0.908314E+09 | 0.00 | 0.76 |
April | 0.782533E+09 | 1351056.39 | 0.00 | 3823951.43 | 2669844.83 | 1319347.03 | 0.159769E+10 | 0.00 | 1.11 |
May | 0.826346E+09 | 1172846.07 | 0.00 | 3844790.03 | 0.00 | 0.00 | 0.163923E+10 | 0.00 | 1.13 |
June | 0.505331E+09 | 25035452.60 | 0.00 | 4821737.14 | 539090.92 | 0.00 | 0.132860E+10 | 0.00 | 1.40 |
July | 0.259028E+09 | 0.348916E+09 | 0.00 | 3943807.05 | 13163472.28 | 0.00 | 0.669819E+09 | 0.00 | 1.51 |
August | 0.238057E+09 | 0.515679E+09 | 0.00 | 3255823.47 | 19086207.84 | 0.00 | 0.520142E+09 | 0.00 | 1.61 |
September | 0.523325E+09 | 84151226.34 | 0.00 | 3224365.73 | 8277344.22 | 0.00 | 0.824270E+09 | 0.00 | 1.17 |
October | 0.565831E+09 | 0.175871E+09 | 0.00 | 2053804.52 | 28851505.93 | 2154410.26 | 0.586819E+09 | 0.00 | 0.94 |
November | 0.100980E+10 | 779.26 | 0.00 | 1414547.73 | 875308.99 | 6070360.67 | 0.801531E+09 | 0.00 | 0.72 |
December | 0.122168E+10 | 58043.04 | 0.00 | 904343.25 | 160438.80 | 26892329.37 | 0.423056E+09 | 0.00 | 0.66 |
Annual Sum or Average | 0.949055E+10 | 0.115386E+10 | 0.00 | 30940095.84 | 77921280.45 | 0.174918E+09 | 0.105459E+11 | 0.00 | 1.04 |
Minimum of Months | 0.238057E+09 | 779.26 | 0.00 | 882954.23 | 0.00 | 0.00 | 0.423056E+09 | 0.00 | 0.66 |
Maximum of Months | 0.129714E+10 | 0.515679E+09 | 0.00 | 4821737.14 | 28851505.93 | 76140873.65 | 0.163923E+10 | 0.00 | 1.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.940115E+09 | 19560144.42 | 0.00 | 7105926.50 | 0.00 | 67288898.45 | 0.329782E+10 | 0.00 | 1.12 |
February | 0.109984E+10 | 1727343.13 | 0.00 | 5165166.53 | 0.00 | 26938402.57 | 0.257146E+10 | 0.00 | 0.97 |
March | 0.144370E+10 | 785676.08 | 0.00 | 4712571.53 | 1993590.21 | 61097540.13 | 0.229173E+10 | 0.00 | 0.88 |
April | 0.106235E+10 | 2490179.26 | 0.00 | 5485424.49 | 3193038.11 | 10686490.36 | 0.220647E+10 | 0.00 | 0.99 |
May | 0.121166E+10 | 1212061.93 | 0.00 | 4087561.69 | 0.00 | 1528282.90 | 0.172396E+10 | 0.00 | 0.85 |
June | 0.724837E+09 | 29459043.12 | 0.00 | 4618134.70 | 1280738.34 | 0.00 | 0.137493E+10 | 0.00 | 0.98 |
July | 0.401605E+09 | 0.406528E+09 | 0.00 | 2980843.95 | 35408066.69 | 0.00 | 0.580176E+09 | 0.00 | 1.03 |
August | 0.313517E+09 | 0.632682E+09 | 0.00 | 3733639.03 | 47541317.43 | 0.00 | 0.582353E+09 | 0.00 | 1.29 |
September | 0.559356E+09 | 0.157966E+09 | 0.00 | 6240239.46 | 11989235.44 | 0.00 | 0.156153E+10 | 0.00 | 1.26 |
October | 0.583547E+09 | 0.433660E+09 | 0.00 | 5843318.15 | 11664900.64 | 820134.57 | 0.138620E+10 | 0.00 | 1.19 |
November | 0.930424E+09 | 1375425.77 | 0.00 | 7435686.74 | 221320.59 | 3408393.44 | 0.335433E+10 | 0.00 | 1.20 |
December | 0.949417E+09 | 999184.58 | 0.00 | 7736055.64 | 0.00 | 18425778.21 | 0.295920E+10 | 0.00 | 1.16 |
Annual Sum or Average | 0.102204E+11 | 0.168845E+10 | 0.00 | 65144568.41 | 0.113292E+09 | 0.190194E+09 | 0.238901E+11 | 0.00 | 1.08 |
Minimum of Months | 0.313517E+09 | 785676.08 | 0.00 | 2980843.95 | 0.00 | 0.00 | 0.580176E+09 | 0.00 | 0.85 |
Maximum of Months | 0.144370E+10 | 0.632682E+09 | 0.00 | 7736055.64 | 47541317.43 | 67288898.45 | 0.335433E+10 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131780E+10 | 3285767.31 | 0.00 | 1141659.06 | 1362489.93 | 0.150952E+09 | 0.658604E+09 | 0.00 | 0.79 |
February | 0.139290E+10 | 536076.11 | 0.00 | 1365308.77 | 0.00 | 55794043.30 | 0.783041E+09 | 0.00 | 0.85 |
March | 0.162889E+10 | 0.00 | 0.00 | 1995282.71 | 2105024.64 | 72340080.61 | 0.105504E+10 | 0.00 | 0.92 |
April | 0.100854E+10 | 597116.58 | 0.00 | 4029406.34 | 3484734.80 | 12723423.12 | 0.168055E+10 | 0.00 | 1.23 |
May | 0.991112E+09 | 588584.83 | 0.00 | 4237480.58 | 0.00 | 1002889.68 | 0.182008E+10 | 0.00 | 1.25 |
June | 0.533418E+09 | 19802669.37 | 0.00 | 5456314.49 | 1077490.42 | 0.00 | 0.162631E+10 | 0.00 | 1.56 |
July | 0.262944E+09 | 0.386501E+09 | 0.00 | 3981953.17 | 28571853.53 | 0.00 | 0.740988E+09 | 0.00 | 1.57 |
August | 0.248790E+09 | 0.436668E+09 | 0.00 | 3522828.77 | 42189133.03 | 0.00 | 0.549122E+09 | 0.00 | 1.66 |
September | 0.547087E+09 | 79378446.79 | 0.00 | 3808450.99 | 11568179.19 | 0.00 | 0.104415E+10 | 0.00 | 1.32 |
October | 0.695930E+09 | 0.168638E+09 | 0.00 | 2126138.23 | 34599516.19 | 3921311.49 | 0.570491E+09 | 0.00 | 1.04 |
November | 0.135692E+10 | 24022.35 | 0.00 | 1671101.99 | 961603.43 | 33372259.68 | 0.896371E+09 | 0.00 | 0.92 |
December | 0.134623E+10 | 0.00 | 0.00 | 1168436.87 | 209025.99 | 97882344.96 | 0.579577E+09 | 0.00 | 0.81 |
Annual Sum or Average | 0.113306E+11 | 0.109602E+10 | 0.00 | 34504361.97 | 0.126129E+09 | 0.427989E+09 | 0.120043E+11 | 0.00 | 1.16 |
Minimum of Months | 0.248790E+09 | 0.00 | 0.00 | 1141659.06 | 0.00 | 0.00 | 0.549122E+09 | 0.00 | 0.79 |
Maximum of Months | 0.162889E+10 | 0.436668E+09 | 0.00 | 5456314.49 | 42189133.03 | 0.150952E+09 | 0.182008E+10 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.206152E+10 | 223827.51 | 0.00 | 320831.64 | 4941448.49 | 57471928.21 | 0.148148E+09 | 0.00 | 0.48 |
February | 0.212294E+10 | 1065304.91 | 0.00 | 87451.87 | 0.00 | 5262831.07 | 0.101675E+09 | 0.00 | 0.50 |
March | 0.241063E+10 | 0.00 | 0.00 | 191615.09 | 2770439.51 | 15461842.63 | 0.151198E+09 | 0.00 | 0.51 |
April | 0.150375E+10 | 491311.93 | 0.00 | 1035471.78 | 4383358.87 | 2034300.71 | 0.518053E+09 | 0.00 | 0.55 |
May | 0.132188E+10 | 2052638.22 | 0.00 | 1950002.31 | 0.00 | 0.00 | 0.872942E+09 | 0.00 | 0.61 |
June | 0.715710E+09 | 44081274.05 | 0.00 | 2882103.15 | 4277595.33 | 0.00 | 0.869642E+09 | 0.00 | 0.73 |
July | 0.372800E+09 | 0.358808E+09 | 0.00 | 1855847.59 | 35416907.42 | 0.00 | 0.393511E+09 | 0.00 | 0.75 |
August | 0.419523E+09 | 0.400356E+09 | 0.00 | 1295352.03 | 49395556.54 | 0.00 | 0.250489E+09 | 0.00 | 0.75 |
September | 0.779585E+09 | 0.100568E+09 | 0.00 | 1756178.26 | 10619821.96 | 0.00 | 0.494669E+09 | 0.00 | 0.66 |
October | 0.878920E+09 | 0.202017E+09 | 0.00 | 1334023.86 | 33591924.55 | 0.00 | 0.401619E+09 | 0.00 | 0.61 |
November | 0.176532E+10 | 325583.32 | 0.00 | 538973.21 | 2166101.77 | 471356.91 | 0.477734E+09 | 0.00 | 0.52 |
December | 0.207968E+10 | 322102.04 | 0.00 | 171590.50 | 64799.02 | 4331311.29 | 0.123397E+09 | 0.00 | 0.49 |
Annual Sum or Average | 0.164323E+11 | 0.111031E+10 | 0.00 | 13419441.29 | 0.147628E+09 | 85033570.83 | 0.480308E+10 | 0.00 | 0.60 |
Minimum of Months | 0.372800E+09 | 0.00 | 0.00 | 87451.87 | 0.00 | 0.00 | 0.101675E+09 | 0.00 | 0.48 |
Maximum of Months | 0.241063E+10 | 0.400356E+09 | 0.00 | 2882103.15 | 49395556.54 | 57471928.21 | 0.872942E+09 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108546E+10 | 1539659.47 | 0.00 | 1183143.78 | 2285192.05 | 3284892.77 | 0.650824E+09 | 0.00 | 0.60 |
February | 0.110282E+10 | 1092939.16 | 0.00 | 1094330.85 | 0.00 | 921246.89 | 0.629385E+09 | 0.00 | 0.63 |
March | 0.127074E+10 | 0.00 | 0.00 | 1391035.18 | 2019772.57 | 1124849.84 | 0.743173E+09 | 0.00 | 0.66 |
April | 0.748872E+09 | 2933957.58 | 0.00 | 3148413.01 | 1792910.03 | 0.00 | 0.121570E+10 | 0.00 | 0.92 |
May | 0.740295E+09 | 2606474.99 | 0.00 | 3260236.57 | 0.00 | 0.00 | 0.127770E+10 | 0.00 | 0.94 |
June | 0.452939E+09 | 48335529.95 | 0.00 | 3659238.42 | 2065114.82 | 0.00 | 0.973424E+09 | 0.00 | 1.14 |
July | 0.181602E+09 | 0.395169E+09 | 0.00 | 3089545.82 | 19835522.72 | 0.00 | 0.589679E+09 | 0.00 | 1.26 |
August | 0.179594E+09 | 0.523039E+09 | 0.00 | 2589226.24 | 26044621.72 | 0.00 | 0.487863E+09 | 0.00 | 1.34 |
September | 0.431195E+09 | 98041327.23 | 0.00 | 2803168.95 | 7417231.94 | 0.00 | 0.741436E+09 | 0.00 | 1.02 |
October | 0.448336E+09 | 0.183271E+09 | 0.00 | 2204336.33 | 22589058.87 | 0.00 | 0.682410E+09 | 0.00 | 0.85 |
November | 0.903368E+09 | 465828.27 | 0.00 | 1894325.97 | 1420482.35 | 0.00 | 0.911014E+09 | 0.00 | 0.68 |
December | 0.112444E+10 | 434493.01 | 0.00 | 1238796.76 | 0.00 | 187759.41 | 0.538221E+09 | 0.00 | 0.61 |
Annual Sum or Average | 0.866966E+10 | 0.125693E+10 | 0.00 | 27555797.91 | 85469907.06 | 5518748.90 | 0.944083E+10 | 0.00 | 0.89 |
Minimum of Months | 0.179594E+09 | 0.00 | 0.00 | 1094330.85 | 0.00 | 0.00 | 0.487863E+09 | 0.00 | 0.60 |
Maximum of Months | 0.127074E+10 | 0.523039E+09 | 0.00 | 3659238.42 | 26044621.72 | 3284892.77 | 0.127770E+10 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110670E+10 | 22152880.20 | 0.00 | 5160791.64 | 0.00 | 0.240288E+09 | 0.238478E+10 | 0.00 | 0.93 |
February | 0.138019E+10 | 4342125.49 | 0.00 | 2908754.88 | 0.00 | 0.226247E+09 | 0.139153E+10 | 0.00 | 0.77 |
March | 0.176507E+10 | 1574184.51 | 0.00 | 2065656.01 | 1574338.75 | 0.403329E+09 | 0.856247E+09 | 0.00 | 0.67 |
April | 0.132711E+10 | 4308971.05 | 0.00 | 2495288.91 | 2420468.64 | 0.153187E+09 | 0.855772E+09 | 0.00 | 0.70 |
May | 0.153958E+10 | 2325916.59 | 0.00 | 1406023.76 | 94784.62 | 0.135580E+09 | 0.542724E+09 | 0.00 | 0.63 |
June | 0.105951E+10 | 49289329.66 | 0.00 | 1509003.84 | 3563320.32 | 65462369.48 | 0.383471E+09 | 0.00 | 0.70 |
July | 0.497047E+09 | 0.420110E+09 | 0.00 | 1132712.98 | 36940642.59 | 764082.53 | 0.243143E+09 | 0.00 | 0.76 |
August | 0.372596E+09 | 0.618008E+09 | 0.00 | 1577540.79 | 48725718.91 | 5465504.95 | 0.331588E+09 | 0.00 | 0.96 |
September | 0.576941E+09 | 0.194350E+09 | 0.00 | 3971029.40 | 10842162.72 | 18332752.99 | 0.101907E+10 | 0.00 | 1.01 |
October | 0.491663E+09 | 0.444985E+09 | 0.00 | 4865992.18 | 15062470.29 | 64338570.32 | 0.122593E+10 | 0.00 | 1.03 |
November | 0.103166E+10 | 4377506.25 | 0.00 | 5678788.55 | 158487.00 | 0.119903E+09 | 0.251126E+10 | 0.00 | 1.02 |
December | 0.104486E+10 | 1506881.11 | 0.00 | 6534767.06 | 0.00 | 0.192788E+09 | 0.230650E+10 | 0.00 | 1.01 |
Annual Sum or Average | 0.121929E+11 | 0.176733E+10 | 0.00 | 39306350.00 | 0.119382E+09 | 0.162568E+10 | 0.140520E+11 | 0.00 | 0.85 |
Minimum of Months | 0.372596E+09 | 1506881.11 | 0.00 | 1132712.98 | 0.00 | 764082.53 | 0.243143E+09 | 0.00 | 0.63 |
Maximum of Months | 0.176507E+10 | 0.618008E+09 | 0.00 | 6534767.06 | 48725718.91 | 0.403329E+09 | 0.251126E+10 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137071E+10 | 3681966.88 | 0.00 | 982733.07 | 1098999.41 | 15104633.55 | 0.524795E+09 | 0.00 | 0.66 |
February | 0.134340E+10 | 1309492.94 | 0.00 | 1031144.30 | 0.00 | 966942.10 | 0.572882E+09 | 0.00 | 0.70 |
March | 0.154956E+10 | 0.00 | 0.00 | 1432210.82 | 2156850.90 | 6590692.46 | 0.687645E+09 | 0.00 | 0.74 |
April | 0.823218E+09 | 1143247.15 | 0.00 | 3153875.17 | 2832395.00 | 1503057.36 | 0.123848E+10 | 0.00 | 0.96 |
May | 0.749968E+09 | 1967578.53 | 0.00 | 3563561.64 | 0.00 | 0.00 | 0.141615E+10 | 0.00 | 1.00 |
June | 0.386823E+09 | 45225818.27 | 0.00 | 4206227.34 | 1865784.54 | 0.00 | 0.121302E+10 | 0.00 | 1.24 |
July | 0.168800E+09 | 0.435495E+09 | 0.00 | 3132272.63 | 18802120.41 | 0.00 | 0.621270E+09 | 0.00 | 1.30 |
August | 0.169150E+09 | 0.467642E+09 | 0.00 | 2605183.44 | 27603980.49 | 0.00 | 0.492892E+09 | 0.00 | 1.35 |
September | 0.331148E+09 | 97654084.47 | 0.00 | 3398982.34 | 8250050.79 | 0.00 | 0.977480E+09 | 0.00 | 1.12 |
October | 0.523494E+09 | 0.187495E+09 | 0.00 | 2067737.86 | 20785842.65 | 0.00 | 0.604262E+09 | 0.00 | 0.89 |
November | 0.115505E+10 | 717527.93 | 0.00 | 1674195.25 | 1516887.93 | 0.00 | 0.884456E+09 | 0.00 | 0.79 |
December | 0.136823E+10 | 310031.78 | 0.00 | 1038812.78 | 34566.73 | 840793.09 | 0.480502E+09 | 0.00 | 0.68 |
Annual Sum or Average | 0.993955E+10 | 0.124264E+10 | 0.00 | 28286936.64 | 84947478.85 | 25006118.56 | 0.971383E+10 | 0.00 | 0.95 |
Minimum of Months | 0.168800E+09 | 0.00 | 0.00 | 982733.07 | 0.00 | 0.00 | 0.480502E+09 | 0.00 | 0.66 |
Maximum of Months | 0.154956E+10 | 0.467642E+09 | 0.00 | 4206227.34 | 27603980.49 | 15104633.55 | 0.141615E+10 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.174194E+10 | 637525.09 | 0.00 | 662740.75 | 4631890.46 | 60385305.67 | 0.333632E+09 | 0.00 | 0.47 |
February | 0.164211E+10 | 1260779.74 | 0.00 | 736300.79 | 0.00 | 3682214.69 | 0.496874E+09 | 0.00 | 0.49 |
March | 0.196429E+10 | 0.00 | 0.00 | 950921.88 | 4401910.99 | 13354917.10 | 0.558327E+09 | 0.00 | 0.51 |
April | 0.116905E+10 | 534639.46 | 0.00 | 2525031.89 | 8594595.13 | 364755.38 | 0.102269E+10 | 0.00 | 0.63 |
May | 0.991072E+09 | 3131812.60 | 0.00 | 3589588.04 | 0.00 | 0.00 | 0.148421E+10 | 0.00 | 0.72 |
June | 0.505887E+09 | 50843139.51 | 0.00 | 4655394.56 | 5717025.98 | 0.00 | 0.139166E+10 | 0.00 | 0.89 |
July | 0.273769E+09 | 0.419741E+09 | 0.00 | 2822378.95 | 37490159.85 | 0.00 | 0.604991E+09 | 0.00 | 0.88 |
August | 0.304789E+09 | 0.477734E+09 | 0.00 | 2151917.12 | 50530656.00 | 0.00 | 0.426996E+09 | 0.00 | 0.88 |
September | 0.622769E+09 | 0.125482E+09 | 0.00 | 2616052.84 | 11580286.04 | 0.00 | 0.739151E+09 | 0.00 | 0.74 |
October | 0.779077E+09 | 0.235410E+09 | 0.00 | 1903457.83 | 27416983.70 | 0.00 | 0.526708E+09 | 0.00 | 0.65 |
November | 0.146116E+10 | 301083.96 | 0.00 | 1265047.08 | 2891258.11 | 633833.19 | 0.716115E+09 | 0.00 | 0.52 |
December | 0.173193E+10 | 237125.99 | 0.00 | 659359.62 | 291238.14 | 6108007.31 | 0.330105E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.131878E+11 | 0.131531E+10 | 0.00 | 24538191.35 | 0.153546E+09 | 84529033.35 | 0.863146E+10 | 0.00 | 0.66 |
Minimum of Months | 0.273769E+09 | 0.00 | 0.00 | 659359.62 | 0.00 | 0.00 | 0.330105E+09 | 0.00 | 0.47 |
Maximum of Months | 0.196429E+10 | 0.477734E+09 | 0.00 | 4655394.56 | 50530656.00 | 60385305.67 | 0.148421E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.121657E+10 | 1736192.43 | 0.00 | 1275949.98 | 2849029.41 | 25258041.79 | 0.691476E+09 | 0.00 | 0.68 |
February | 0.120252E+10 | 1159522.86 | 0.00 | 1437227.63 | 0.00 | 1865171.30 | 0.802768E+09 | 0.00 | 0.74 |
March | 0.137484E+10 | 34091.10 | 0.00 | 1906665.07 | 3780397.46 | 2377865.44 | 0.996337E+09 | 0.00 | 0.79 |
April | 0.828709E+09 | 3253841.20 | 0.00 | 3928755.29 | 5710126.82 | 256906.94 | 0.155612E+10 | 0.00 | 1.11 |
May | 0.828358E+09 | 3374788.97 | 0.00 | 3963582.52 | 0.00 | 0.00 | 0.160578E+10 | 0.00 | 1.12 |
June | 0.505964E+09 | 48457982.42 | 0.00 | 4605899.67 | 3342460.89 | 0.00 | 0.125347E+10 | 0.00 | 1.35 |
July | 0.251125E+09 | 0.399220E+09 | 0.00 | 3670599.91 | 23675132.45 | 0.00 | 0.675454E+09 | 0.00 | 1.43 |
August | 0.255811E+09 | 0.544448E+09 | 0.00 | 2941216.51 | 28372549.90 | 0.00 | 0.542744E+09 | 0.00 | 1.50 |
September | 0.527889E+09 | 0.107300E+09 | 0.00 | 3134784.37 | 9572697.92 | 0.00 | 0.828454E+09 | 0.00 | 1.16 |
October | 0.571436E+09 | 0.195068E+09 | 0.00 | 2285636.12 | 25613372.71 | 0.00 | 0.711800E+09 | 0.00 | 0.94 |
November | 0.104608E+10 | 582478.20 | 0.00 | 1925672.69 | 2158960.84 | 0.00 | 0.966599E+09 | 0.00 | 0.76 |
December | 0.124357E+10 | 529790.75 | 0.00 | 1321267.11 | 18917.62 | 1776637.25 | 0.594453E+09 | 0.00 | 0.68 |
Annual Sum or Average | 0.985288E+10 | 0.130516E+10 | 0.00 | 32397256.88 | 0.105094E+09 | 31534622.72 | 0.112254E+11 | 0.00 | 1.02 |
Minimum of Months | 0.251125E+09 | 34091.10 | 0.00 | 1275949.98 | 0.00 | 0.00 | 0.542744E+09 | 0.00 | 0.68 |
Maximum of Months | 0.137484E+10 | 0.544448E+09 | 0.00 | 4605899.67 | 28372549.90 | 25258041.79 | 0.160578E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.928386E+09 | 25173847.64 | 0.00 | 8137546.18 | 0.00 | 12771067.31 | 0.346816E+10 | 0.00 | 1.14 |
February | 0.108453E+10 | 4719184.28 | 0.00 | 5921555.22 | 0.00 | 574663.51 | 0.267024E+10 | 0.00 | 0.99 |
March | 0.135144E+10 | 3079985.10 | 0.00 | 5345166.94 | 2260578.04 | 6826386.95 | 0.232316E+10 | 0.00 | 0.88 |
April | 0.975154E+09 | 6850755.30 | 0.00 | 5579357.61 | 5727986.95 | 324842.06 | 0.204768E+10 | 0.00 | 0.96 |
May | 0.103141E+10 | 4182375.79 | 0.00 | 4392187.50 | 0.00 | 0.00 | 0.171096E+10 | 0.00 | 0.82 |
June | 0.614827E+09 | 59645116.68 | 0.00 | 4559500.18 | 5839659.13 | 0.00 | 0.130697E+10 | 0.00 | 0.94 |
July | 0.326842E+09 | 0.497821E+09 | 0.00 | 2707117.39 | 36782342.17 | 0.00 | 0.575366E+09 | 0.00 | 0.96 |
August | 0.268033E+09 | 0.716969E+09 | 0.00 | 3012607.67 | 49735482.23 | 0.00 | 0.575450E+09 | 0.00 | 1.18 |
September | 0.442450E+09 | 0.232053E+09 | 0.00 | 5841558.23 | 8659416.96 | 0.00 | 0.151437E+10 | 0.00 | 1.24 |
October | 0.485424E+09 | 0.507387E+09 | 0.00 | 6003018.63 | 6988230.66 | 0.00 | 0.148191E+10 | 0.00 | 1.15 |
November | 0.869090E+09 | 6124972.28 | 0.00 | 8500204.95 | 741862.03 | 0.00 | 0.351778E+10 | 0.00 | 1.24 |
December | 0.919114E+09 | 2582926.17 | 0.00 | 9027634.82 | 0.00 | 245816.67 | 0.316634E+10 | 0.00 | 1.17 |
Annual Sum or Average | 0.929670E+10 | 0.206659E+10 | 0.00 | 69027455.30 | 0.116736E+09 | 20742776.50 | 0.243584E+11 | 0.00 | 1.06 |
Minimum of Months | 0.268033E+09 | 2582926.17 | 0.00 | 2707117.39 | 0.00 | 0.00 | 0.575366E+09 | 0.00 | 0.82 |
Maximum of Months | 0.135144E+10 | 0.716969E+09 | 0.00 | 9027634.82 | 49735482.23 | 12771067.31 | 0.351778E+10 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.144017E+10 | 5086051.07 | 0.00 | 1327476.35 | 1488918.14 | 40651106.04 | 0.668660E+09 | 0.00 | 0.76 |
February | 0.140297E+10 | 1458910.85 | 0.00 | 1562785.08 | 0.00 | 3010340.21 | 0.823526E+09 | 0.00 | 0.84 |
March | 0.161440E+10 | 0.00 | 0.00 | 2133681.09 | 4002995.45 | 13766946.12 | 0.104807E+10 | 0.00 | 0.89 |
April | 0.909916E+09 | 4098201.66 | 0.00 | 4114813.69 | 4649718.97 | 1659709.50 | 0.158809E+10 | 0.00 | 1.18 |
May | 0.839683E+09 | 2506946.49 | 0.00 | 4448315.12 | 0.00 | 0.00 | 0.177166E+10 | 0.00 | 1.21 |
June | 0.435947E+09 | 45213046.37 | 0.00 | 5242823.70 | 3730568.66 | 0.00 | 0.152177E+10 | 0.00 | 1.48 |
July | 0.249745E+09 | 0.470102E+09 | 0.00 | 3500705.34 | 23721855.01 | 0.00 | 0.662715E+09 | 0.00 | 1.46 |
August | 0.239389E+09 | 0.512036E+09 | 0.00 | 2748697.25 | 32313987.34 | 0.00 | 0.510162E+09 | 0.00 | 1.52 |
September | 0.452434E+09 | 0.112893E+09 | 0.00 | 3684797.37 | 10716396.78 | 0.00 | 0.103113E+10 | 0.00 | 1.27 |
October | 0.655383E+09 | 0.209021E+09 | 0.00 | 2187330.84 | 22761180.92 | 0.00 | 0.609644E+09 | 0.00 | 1.00 |
November | 0.130516E+10 | 920998.13 | 0.00 | 1961161.47 | 2362132.33 | 1541088.22 | 0.989710E+09 | 0.00 | 0.90 |
December | 0.143659E+10 | 381136.04 | 0.00 | 1360263.43 | 244992.68 | 8664669.14 | 0.610592E+09 | 0.00 | 0.78 |
Annual Sum or Average | 0.109818E+11 | 0.136372E+10 | 0.00 | 34272850.73 | 0.105993E+09 | 69293859.23 | 0.118357E+11 | 0.00 | 1.11 |
Minimum of Months | 0.239389E+09 | 0.00 | 0.00 | 1327476.35 | 0.00 | 0.00 | 0.510162E+09 | 0.00 | 0.76 |
Maximum of Months | 0.161440E+10 | 0.512036E+09 | 0.00 | 5242823.70 | 32313987.34 | 40651106.04 | 0.177166E+10 | 0.00 | 1.52 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:42
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.190653E+12 | 0.662411E+10 | 0.00 | 0.218536E+12 | 0.291580E+11 |
February | 0.221676E+12 | 0.726752E+10 | 0.00 | 0.218656E+12 | 0.169289E+11 |
March | 0.297565E+12 | 0.794583E+10 | 0.00 | 0.226483E+12 | 0.213410E+11 |
April | 0.373111E+12 | 0.466815E+10 | 0.00 | 0.219503E+12 | 0.482230E+11 |
May | 0.386954E+12 | 0.528489E+10 | 0.00 | 0.230329E+12 | 0.504351E+11 |
June | 0.379048E+12 | 0.273802E+10 | 0.00 | 0.181990E+12 | 0.948717E+11 |
July | 0.404610E+12 | 0.867689E+09 | 0.00 | 0.109014E+12 | 0.158336E+12 |
August | 0.378131E+12 | 0.947985E+09 | 0.00 | 0.847642E+11 | 0.182316E+12 |
September | 0.304875E+12 | 0.210140E+10 | 0.00 | 0.156163E+12 | 0.111020E+12 |
October | 0.222181E+12 | 0.328851E+10 | 0.00 | 0.164450E+12 | 0.120846E+12 |
November | 0.204194E+12 | 0.637976E+10 | 0.00 | 0.242683E+12 | 0.326349E+11 |
December | 0.176074E+12 | 0.692074E+10 | 0.00 | 0.241208E+12 | 0.341220E+11 |
Annual Sum or Average | 0.353907E+13 | 0.550346E+11 | 0.00 | 0.229378E+13 | 0.900233E+12 |
Minimum of Months | 0.176074E+12 | 0.867689E+09 | 0.00 | 0.847642E+11 | 0.169289E+11 |