Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 08:28:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1890.56 | 379.46 | 379.46 |
Net Site Energy | 1890.56 | 379.46 | 379.46 |
Total Source Energy | 5680.61 | 1140.18 | 1140.18 |
Net Source Energy | 5680.61 | 1140.18 | 1140.18 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 131.49 | 19.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 340.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 365.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 111.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 70.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 128.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1743.27 | 147.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 131.49 | 19.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 340.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 365.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 111.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 17.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 70.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 128.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 131.49 | 19.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 340.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 365.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 111.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 17.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 70.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 128.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 95.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 109.09 | 29.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 145.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 349.90 | 29.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 95.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 109.09 | 29.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 145.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 349.90 | 29.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1743.274 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1743.274 | 100.00 |
Total On-Site and Utility Electric Sources | 1743.274 | 100.00 |
Total Electricity End Uses | 1743.274 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 134.00 |
Time Setpoint Not Met During Occupied Cooling | 98.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1916.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 10.1959 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 10.1959 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.1959 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 10.1959 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
Total | 4982.19 | 10.1959 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 10.1959 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 10.1959 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-JAN-07:10 | 03-FEB-07:40 | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:20 |
Heating | 199863.23 | 49970.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12752.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 8596.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 353.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6103.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8983.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 248775.13 | 58954.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 199863.23 | 49970.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 12752.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 8596.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 353.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6103.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8983.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 416.44 | 20.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1079.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1157.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 353.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 54.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 224.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 138.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5520.95 | 159.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 83.59 | 4.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 216.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 232.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 45.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1108.14 | 32.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 83.59 | 4.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 216.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 232.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 45.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1108.14 | 32.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.11 | 0.241067 | 0.254000 | 0.789663 | 0.642845 | 0.500000 | 0.001580 |
CORE_MID VAV BOX COMPONENT | 2.33 | 0.321770 | 0.328000 | 0.763965 | 0.858054 | 0.500000 | 0.001184 |
CORE_TOP VAV BOX COMPONENT | 2.46 | 0.305144 | 0.324000 | 0.795767 | 0.813717 | 0.500000 | 0.001249 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.769699 | 0.205264 | 0.218000 | 0.167794 | 0.547371 | 0.500000 | 0.001856 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.722558 | 0.138427 | 0.200000 | 0.144512 | 0.369139 | 0.500000 | 0.002752 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.885534 | 0.178414 | 0.200000 | 0.177107 | 0.475770 | 0.500000 | 0.002135 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.797405 | 0.125426 | 0.200000 | 0.159481 | 0.334469 | 0.500000 | 0.003038 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.629142 | 0.251122 | 0.265000 | 0.166723 | 0.669660 | 0.500000 | 0.001517 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.626169 | 0.159736 | 0.200000 | 0.125234 | 0.425963 | 0.500000 | 0.002385 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.732191 | 0.215779 | 0.228000 | 0.166940 | 0.575411 | 0.500000 | 0.001766 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.648464 | 0.154234 | 0.200000 | 0.129693 | 0.411291 | 0.500000 | 0.002470 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.674101 | 0.234374 | 0.239000 | 0.161110 | 0.624997 | 0.500000 | 0.001626 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.696928 | 0.143518 | 0.200000 | 0.139386 | 0.382715 | 0.500000 | 0.002655 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.789073 | 0.200224 | 0.204000 | 0.160971 | 0.533932 | 0.500000 | 0.001903 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.727279 | 0.137520 | 0.200000 | 0.145456 | 0.366719 | 0.500000 | 0.002771 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25427.96 |
CORE_MID VAV BOX REHEAT COIL | 24600.45 |
CORE_TOP VAV BOX REHEAT COIL | 37310.37 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 18161.66 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11779.41 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17983.38 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11889.36 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13821.51 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9013.58 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 13670.29 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9112.58 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 14509.04 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 9450.73 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 14341.82 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 9551.95 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.87 | 1.38 | 5.74 | 1.84 | 5.23 | 5.23 | 0.300000 | 0.351747 | 5.23 |
PACU_VAV_MID | 2.61 | 1.37 | 5.22 | 2.17 | 4.62 | 4.62 | 0.300000 | 0.469553 | 4.62 |
PACU_VAV_TOP | 2.82 | 1.44 | 5.63 | 3.02 | 5.33 | 5.33 | 0.300000 | 0.565560 | 5.33 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.23 |
PACU_VAV_MID_OA_CONTROLLER | 4.62 |
PACU_VAV_TOP_OA_CONTROLLER | 5.33 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.23 | 116631.39 | 0.736164 | 1.74 | 38873.24 | 0.736164 |
PACU_VAV_MID COOLING COIL | 4.62 | 106937.14 | 0.722798 | 1.54 | 35642.15 | 0.722798 |
PACU_VAV_TOP COOLING COIL | 5.33 | 118390.25 | 0.737154 | 1.78 | 39459.47 | 0.737154 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 23859.92 |
PACU_VAV_MID HEATING COIL | 25304.04 |
PACU_VAV_TOP HEATING COIL | 24439.90 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.23 |
PACU_VAV_MID FAN | 4.62 |
PACU_VAV_TOP FAN | 5.33 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 35.030 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9622 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9482 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.202 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8052 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8206 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5978 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27384127E-12 | 0.12865281E-14 | -0.83346422E-13 | 0.81323336E-16 |
43 | 6 | 0.26454352E-07 | 0.26406074E-09 | 0.60786733E-08 | -0.12333448E-12 |
44 | 5 | -0.17878666E-03 | 0.22931636E-05 | -0.92101048E-04 | 0.60153540E-08 |
45 | 4 | 0.27880517 | 0.11305828E-02 | 0.94889811E-01 | -0.31698392E-04 |
46 | 3 | -7.0018852 | 0.35426556E-01 | -2.2604600 | 0.27713709E-01 |
47 | 2 | 39.998753 | 0.12720283 | 14.942758 | -0.32362551 |
48 | 1 | -79.877006 | 0.57894353E-01 | -28.852534 | 1.0643678 |
49 | 0 | 46.824343 | 0.11744712E-02 | 16.298269 | |
50 | 7 | -0.27620064E-12 | 0.12774393E-14 | -0.83964131E-13 | 0.81942822E-16 |
51 | 6 | 0.26622461E-07 | 0.26074659E-09 | 0.61157793E-08 | -0.12423095E-12 |
52 | 5 | -0.17965003E-03 | 0.22617301E-05 | -0.92535175E-04 | 0.60516003E-08 |
53 | 4 | 0.27982997 | 0.11139309E-02 | 0.95257664E-01 | -0.31841476E-04 |
54 | 3 | -7.0222151 | 0.34872839E-01 | -2.2664901 | 0.27813240E-01 |
55 | 2 | 40.065841 | 0.12511414 | 14.967577 | -0.32437249 |
56 | 1 | -79.928458 | 0.56904129E-01 | -28.874810 | 1.0654641 |
57 | 0 | 46.824343 | 0.11535943E-02 | 16.297719 | |
58 | 7 | -0.27931930E-12 | 0.13886628E-14 | -0.87137092E-13 | 0.18759942E-15 |
59 | 6 | 0.23561308E-07 | 0.31712788E-09 | 0.54400317E-08 | -0.10799411E-12 |
60 | 5 | -0.16378969E-03 | 0.28142694E-05 | -0.84539011E-04 | 0.53904798E-08 |
61 | 4 | 0.26080053 | 0.14141629E-02 | 0.88437074E-01 | -0.29205444E-04 |
62 | 3 | -6.6442204 | 0.45062581E-01 | -2.1544048 | 0.25964059E-01 |
63 | 2 | 38.817908 | 0.16418932 | 14.505027 | -0.31048073 |
64 | 1 | -78.970774 | 0.75677137E-01 | -28.459322 | 1.0450580 |
65 | 0 | 46.824349 | 0.15543837E-02 | 16.308247 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.498_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.498_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00974E-002 | 0.16139 | 0.61139 | 0.61139 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00974E-002 | 0.16139 | 0.61139 | 0.61139 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00974E-002 | 0.16139 | 0.61139 | 0.61139 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00974E-002 | 0.16139 | 0.61139 | 0.61139 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.973 | 0.1730 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.0154E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0548E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.5333E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5658E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3333E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3590E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9164E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9329E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1011 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6105E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1127 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9971E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6512E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0535E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2073E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2006E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.0182E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0717E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.5364E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5846E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3363E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3723E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9162E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9327E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4712E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0617E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3095E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8955E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1866E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5629E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7685E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7749E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8084E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8244E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6586E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.6702E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2994E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.3039E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4038E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4095E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9419E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9799E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4803E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5112E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1854E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2090E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9162E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9327E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7332E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5479E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1205E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1871E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9704E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.3399E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2073E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2006E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9411E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9793E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4790E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5082E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1828E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1998E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9164E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9329E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9026E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3393E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3943E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0120E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7737E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9199E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7686E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7749E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7990E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8327E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4179E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4521E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4291E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4468E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4040E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4097E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1093 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.7177E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1214 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.1854E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3417E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.9225E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6593E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.7065E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2977E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9600E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1501E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.8013E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.0648E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4890E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6984E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7326E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1345E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0406E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4795E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6142E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3290E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2281E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6593E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7065E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.7764E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2698E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2932E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9575E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6925E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8735E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6984E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7326E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1093 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.7171E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1214 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.1847E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3412E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.9220E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6589E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.7063E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2976E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9597E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1499E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.8011E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.0645E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4887E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6980E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7324E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1346E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0405E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4795E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6142E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3289E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2279E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6589E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7063E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.7763E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2696E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2931E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9574E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6923E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8733E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6980E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7324E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 41590.71841 | 41590.71841 | 3.10891 | 3.10891 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 7796.14613 | 7796.14613 | 0.34000 | 0.42469 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 31191.15968 | 31191.15968 | 2.32916 | 2.32916 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 15528.39808 | 15528.39808 | 0.68213 | 0.68213 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 32591.65548 | 32591.65548 | 2.45607 | 2.45607 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 34.02000 | 1.44726E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 26273.41187 | 26273.41187 | 1.15867 | 1.15867 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 10213.09516 | 10213.09516 | 0.76970 | 0.76970 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 34.11500 | 1.44727E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 12752.26629 | 12752.26629 | 0.56401 | 0.56401 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9587.61429 | 9587.61429 | 0.72256 | 0.72256 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 8270.52079 | 8270.52079 | 0.36581 | 0.36581 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 11750.12794 | 11750.12794 | 0.88553 | 0.88553 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 12627.39617 | 12627.39617 | 0.55847 | 0.55847 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10580.77273 | 10580.77273 | 0.79740 | 0.79740 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 8347.53636 | 8347.53636 | 0.36922 | 0.36922 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 8348.32333 | 8348.32333 | 0.62914 | 0.62914 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 9711.01947 | 9711.01947 | 0.42923 | 0.42923 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8308.92452 | 8308.92452 | 0.62617 | 0.62617 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 6332.40067 | 6332.40067 | 0.27992 | 0.27992 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 9715.74067 | 9715.74067 | 0.73219 | 0.73219 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 9605.12146 | 9605.12146 | 0.42453 | 0.42453 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8604.76551 | 8604.76551 | 0.64846 | 0.64846 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 6401.72759 | 6401.72759 | 0.28299 | 0.28299 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8944.70587 | 8944.70587 | 0.67410 | 0.67410 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 10193.34399 | 10193.34399 | 0.45058 | 0.45058 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9247.64162 | 9247.64162 | 0.69693 | 0.69693 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 31.02750 | 1.44671E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 6639.09415 | 6639.09415 | 0.29349 | 0.29349 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 10470.29252 | 10470.29252 | 0.78907 | 0.78907 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 10076.22737 | 10076.22737 | 0.44538 | 0.44538 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9650.38330 | 9650.38330 | 0.72728 | 0.72728 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 6709.98808 | 6709.98808 | 0.29664 | 0.29664 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 82776.90 | 5.23488 | 5.23488 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 26370.75 | 1.84135 | 1.84135 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 74468.05 | 4.61762 | 4.61762 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 26422.19 | 2.16822 | 2.16822 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 83638.81 | 5.33309 | 5.33309 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 26428.43 | 3.01618 | 3.01618 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.10891 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24107 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25400 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78966 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64284 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.58048E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25427.96295 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.32916 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32177 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32800 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76396 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85805 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18407E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24600.45353 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.45607 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30514 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32400 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79577 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81372 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.24859E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 37310.37176 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76970 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20526 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21800 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16779 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54737 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.85614E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18161.65660 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72256 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13843 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14451 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36914 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.75235E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11779.40530 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88553 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17841 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17711 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47577 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.13548E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17983.37806 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79740 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12543 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15948 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33447 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.03765E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11889.36300 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62914 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25112 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16672 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66966 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.51719E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13821.51277 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62617 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15974 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12523 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42596 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.38519E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9013.58219 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73219 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21578 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22800 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16694 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57541 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.76569E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13670.29151 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64846 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15423 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12969 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41129 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.47027E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9112.57953 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67410 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23437 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23900 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16111 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62500 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.62561E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14509.03869 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69693 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14352 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13939 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38271 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.65472E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9450.72650 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78907 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20022 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20400 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16097 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53393 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.90286E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14341.81566 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72728 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13752 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14546 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36672 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.77051E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9551.95192 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.87244 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37825 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.74488 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.84135 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.23488 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.23488 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.35175 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.60827 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37089 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.21654 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.16822 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.61762 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.61762 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.46955 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.81563 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.44466 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.63127 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.01618 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.33309 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.33309 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.56556 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.23488 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.61762 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.33309 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.23488 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.23488 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 116631.39251 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73616 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.74479 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 38873.24312 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73616 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 23859.92394 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.23488 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.61762 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.61762 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 106937.13851 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.72280 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.53905 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35642.14827 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.72280 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 25304.03747 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.61762 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.33309 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.33309 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 118390.24998 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73715 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.77752 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 39459.47032 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73715 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 24439.89572 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.33309 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 116024.77 | 395892.93 | 11.50 | 2.93 | 3.30 | 3.47 | 3.62 | 10.00 | 11.25 | 11.86 | 12.34 | 5.8376 | 4.6466 | 3.1272 | 1.3045 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 106521.78 | 363467.41 | 11.58 | 2.95 | 3.32 | 3.50 | 3.63 | 10.05 | 11.32 | 11.94 | 12.39 | 5.1492 | 4.0935 | 2.7546 | 1.1643 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 117759.58 | 401812.36 | 11.50 | 2.93 | 3.29 | 3.47 | 3.61 | 9.99 | 11.24 | 11.85 | 12.33 | 5.9471 | 4.7336 | 3.1859 | 1.3282 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.0327860366E-003 | 5.8850146643E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.1118200060E-002 | 5.2287870559E-002 | Pass | Pass | 0.1164864798 | 0.3127427814 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.8892373449E-003 | 5.7579029479E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.4587546101E-003 | 5.0026059477E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.5184434348E-003 | 6.8316455945E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.3498657202E-002 | 7.4041299358E-002 | Pass | Pass | 0.1148732782 | 0.3149891319 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.9008575110E-002 | 0.1236781265 | Pass | Pass | 0.2548150535 | 0.8239578978 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.1060575476E-002 | 0.1248911206 | Pass | Pass | 0.2661048861 | 0.8924005451 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.5211022457E-002 | 0.1110369998 | Pass | Pass | 0.2460559104 | 0.8031361859 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.4638097849E-002 | 0.1330795306 | Pass | Pass | 0.2703155090 | 0.9100499772 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.5087235766E-002 | 2.4186584773E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.5941109490E-002 | 2.5656275998E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.6287724371E-002 | 2.6711542644E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.5987613723E-002 | 2.4636595727E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.0071168596E-002 | 2.7584392861E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.1326022692E-002 | 2.9405403666E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 3.1600055157E-002 | 3.0720671346E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.1359674611E-002 | 2.8277516503E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2930.68 | 46.56 | 0.00 | 1207.47 | 1683.83 | 5868.53 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.498_SHGC_EAST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.498_SHGC_EAST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.498_SHGC_WEST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.498_SHGC_WEST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.831 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 195.79 | 2.831 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.831 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.77 | 0.0000 | Y | 11.02 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.13 | 0.0000 | Y | 6.82 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.80 | 0.0000 | Y | 10.64 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.43 | 0.0000 | Y | 6.89 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.64 | 0.0000 | Y | 10.97 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.05 | 0.0000 | Y | 6.80 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.74 | 0.0000 | Y | 10.61 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.33 | 0.0000 | Y | 6.87 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.77 | 0.0000 | Y | 11.02 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.13 | 0.0000 | Y | 6.82 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.80 | 0.0000 | Y | 10.64 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.43 | 0.0000 | Y | 6.89 |
Interior Lighting Total | 10.1959 | 4982.19 | 50797.72 | 365.45 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.28 | AstronomicalClock | - | 41.77 | 41.77 | 4.42 | |
EXTERIOR_LIGHTS_B | 8033.20 | AstronomicalClock | - | 83.77 | 71.17 | 107.32 | |
Exterior Lighting Total | 8596.48 | 111.74 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 116631.39 | 85859.81 | 30771.58 | 0.74 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 106937.14 | 77293.94 | 29643.20 | 0.72 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 118390.25 | 87271.86 | 31118.39 | 0.74 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 116024.8 | 2.93 | 10.00 | N/A | N/A | 11.50 | |
PACU_VAV_MID COOLING COIL | 106521.8 | 2.95 | 10.05 | N/A | N/A | 11.58 | |
PACU_VAV_TOP COOLING COIL | 117759.6 | 2.93 | 9.99 | N/A | N/A | 11.50 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25427.96 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24600.45 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 37310.37 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18161.66 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11779.41 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17983.38 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11889.36 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13821.51 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9013.58 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13670.29 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9112.58 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14509.04 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9450.73 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14341.82 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9551.95 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 23859.92 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 25304.04 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 24439.90 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.23 | 11385.28 | 2174.89 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.62 | 10108.03 | 2189.01 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.33 | 11598.87 | 2174.89 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.97 | 0.17 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 116024.77 | 2.93 | 10.00 | 11.50 | 5.8376 | 3.30 | 11.25 | 4.6466 | 3.47 | 11.86 | 3.1272 | 3.62 | 12.34 | 1.3045 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 106521.78 | 2.95 | 10.05 | 11.58 | 5.1492 | 3.32 | 11.32 | 4.0935 | 3.50 | 11.94 | 2.7546 | 3.63 | 12.39 | 1.1643 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 117759.58 | 2.93 | 9.99 | 11.50 | 5.9471 | 3.29 | 11.24 | 4.7336 | 3.47 | 11.85 | 3.1859 | 3.61 | 12.33 | 1.3282 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 41590.72 | 41590.72 | 42.29 | 3.109 | 3.109 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00879 | 27.37 | 0.01446 | 0.425 | 0.00 |
CORE_MID | 31191.16 | 31191.16 | 31.71 | 2.329 | 2.329 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 27.37 | 0.01446 | 0.425 | 0.00 |
CORE_TOP | 32591.66 | 32591.66 | 33.14 | 2.456 | 2.456 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00887 | 34.02 | 0.01447 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10213.10 | 10213.10 | 49.26 | 0.770 | 0.770 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00895 | 34.12 | 0.01447 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9587.61 | 9587.61 | 73.04 | 0.723 | 0.723 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.00 | 24.00 | 0.00882 | 31.50 | 0.01447 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11750.13 | 11750.13 | 56.67 | 0.886 | 0.886 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00889 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10580.77 | 10580.77 | 80.61 | 0.797 | 0.797 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00879 | 32.91 | 0.01447 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8348.32 | 8348.32 | 40.26 | 0.629 | 0.629 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00894 | 34.30 | 0.01447 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8308.92 | 8308.92 | 63.30 | 0.626 | 0.626 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.00 | 24.00 | 0.00878 | 31.50 | 0.01447 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9715.74 | 9715.74 | 46.86 | 0.732 | 0.732 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00888 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8604.77 | 8604.77 | 65.56 | 0.648 | 0.648 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00877 | 32.75 | 0.01447 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8944.71 | 8944.71 | 43.14 | 0.674 | 0.674 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00898 | 34.30 | 0.01447 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9247.64 | 9247.64 | 70.45 | 0.697 | 0.697 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00880 | 31.03 | 0.01447 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 10470.29 | 10470.29 | 50.50 | 0.789 | 0.789 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00891 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9650.38 | 9650.38 | 73.52 | 0.727 | 0.727 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00879 | 32.75 | 0.01447 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 7796.15 | 7796.15 | 7.93 | 0.340 | 0.425 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
CORE_MID | 15528.40 | 15528.40 | 15.79 | 0.682 | 0.682 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
CORE_TOP | 26273.41 | 26273.41 | 26.71 | 1.159 | 1.159 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 12752.27 | 12752.27 | 61.50 | 0.564 | 0.564 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00758 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8270.52 | 8270.52 | 63.01 | 0.366 | 0.366 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00757 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12627.40 | 12627.40 | 60.90 | 0.558 | 0.558 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00757 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 8347.54 | 8347.54 | 63.60 | 0.369 | 0.369 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00757 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 9711.02 | 9711.02 | 46.84 | 0.429 | 0.429 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 6332.40 | 6332.40 | 48.24 | 0.280 | 0.280 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9605.12 | 9605.12 | 46.33 | 0.425 | 0.425 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 6401.73 | 6401.73 | 48.77 | 0.283 | 0.283 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 10193.34 | 10193.34 | 49.16 | 0.451 | 0.451 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 6639.09 | 6639.09 | 50.58 | 0.293 | 0.293 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 10076.23 | 10076.23 | 48.60 | 0.445 | 0.445 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 6709.99 | 6709.99 | 51.12 | 0.297 | 0.297 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -6.30 | 0.00230 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.23 | 5.23 | 1.84 | 1.84 | 5.2349 | 1.8414 | 5.2349 | 0.3517 | 0.3000 |
PACU_VAV_MID | 4.62 | 4.62 | 2.17 | 2.17 | 4.6176 | 2.1682 | 4.6176 | 0.4696 | 0.3000 |
PACU_VAV_TOP | 5.33 | 5.33 | 3.02 | 3.02 | 5.3331 | 3.0162 | 5.3331 | 0.5656 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25427.963 | 25427.963 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25427.96 | 13675.49 | 0.424691 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 7796.15 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24600.454 | 24600.454 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24600.45 | 21965.41 | 0.682134 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 15528.40 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 37310.372 | 37310.372 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37310.37 | 37310.37 | 1.158670 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 26273.41 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 18161.657 | 18161.657 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18161.66 | 18161.66 | 0.564009 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00757587 | 47.2570 | 12752.27 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 11779.405 | 11779.405 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11779.41 | 11779.41 | 0.365808 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00756557 | 47.1938 | 8270.52 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 17983.378 | 17983.378 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17983.38 | 17983.38 | 0.558472 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00757174 | 47.2315 | 12627.40 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 11889.363 | 11889.363 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11889.36 | 11889.36 | 0.369223 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00756948 | 47.2178 | 8347.54 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 13821.513 | 13821.513 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13821.51 | 13821.51 | 0.429226 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00766331 | 47.7938 | 9711.02 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 9013.582 | 9013.582 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9013.58 | 9013.58 | 0.279916 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00766255 | 47.7892 | 6332.40 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 13670.292 | 13670.292 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13670.29 | 13670.29 | 0.424530 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00765689 | 47.7543 | 9605.12 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9112.580 | 9112.580 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9112.58 | 9112.58 | 0.282990 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00766824 | 47.8242 | 6401.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 14509.039 | 14509.039 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14509.04 | 14509.04 | 0.450577 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00754297 | 47.0537 | 10193.34 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 9450.727 | 9450.727 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9450.73 | 9450.73 | 0.293491 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00753645 | 47.0137 | 6639.09 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 14341.816 | 14341.816 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14341.82 | 14341.82 | 0.445384 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00753669 | 47.0150 | 10076.23 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 9551.952 | 9551.952 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9551.95 | 9551.95 | 0.296635 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00754205 | 47.0482 | 6709.99 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 116631.393 | 85859.813 | 5.234880 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 116861.27 | 92300.17 | 5.234880 | 26.38 | 18.15 | 0.01013275 | 10.97 | 10.97 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 22.8309 | 24.00 | 0.00884574 | 45.8883 | 69346.45 | 0.00 | 120262.62 | 85801.92 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 23859.924 | 23859.924 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23859.92 | 23859.92 | 1.570464 | -0.22 | -0.71 | 0.00351580 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 76.1030 | 19.60 | 0.00707198 | 48.1384 | 19485.23 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 106937.139 | 77293.943 | 4.617624 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 107886.70 | 83075.68 | 4.617624 | 26.71 | 18.45 | 0.01037144 | 10.96 | 10.96 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 25.8828 | 24.00 | 0.00892737 | 46.3063 | 60906.82 | 0.00 | 110266.54 | 77349.70 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 25304.037 | 25304.037 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25304.04 | 25304.04 | 1.385287 | -2.86 | -3.01 | 0.00299183 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 86.2760 | 19.60 | 0.00713477 | 48.5562 | 23548.24 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 118390.250 | 87271.859 | 5.333088 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 118740.43 | 93554.99 | 5.333088 | 26.30 | 18.13 | 0.01014311 | 10.97 | 10.97 | 0.00850000 | 34.21 | 0.01447292 | 23.49 | 22.4105 | 24.00 | 0.00888620 | 46.0958 | 70490.64 | 0.00 | 122076.24 | 87218.13 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 24439.896 | 24439.896 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24439.90 | 24439.90 | 1.599926 | -0.29 | -0.66 | 0.00357391 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 74.7016 | 17.60 | 0.00722220 | 55.7070 | 28448.36 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25427.963 | 25427.963 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25427.96 | 13675.49 | 1.0000 | 0.49305639 | 0.424691 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25427.96 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 7796.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24600.454 | 24600.454 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24600.45 | 21965.41 | 1.0000 | 0.79194140 | 0.682134 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24600.45 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 15528.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 37310.372 | 37310.372 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 37310.37 | 37310.37 | 1.0000 | 1.34518902 | 1.158670 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37310.37 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 26273.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 18161.657 | 18161.657 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18161.66 | 18161.66 | 1.0000 | 0.65480079 | 0.564009 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18161.66 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00757587 | 21.00 | 0.00757587 | 47.2570 | 12752.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11779.405 | 11779.405 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11779.41 | 11779.41 | 1.0000 | 0.42469495 | 0.365808 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11779.41 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00756557 | 21.00 | 0.00756557 | 47.1938 | 8270.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 17983.378 | 17983.378 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17983.38 | 17983.38 | 1.0000 | 0.64837313 | 0.558472 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17983.38 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00757174 | 21.00 | 0.00757174 | 47.2315 | 12627.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 11889.363 | 11889.363 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11889.36 | 11889.36 | 1.0000 | 0.42865937 | 0.369223 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11889.36 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00756948 | 21.00 | 0.00756948 | 47.2178 | 8347.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13821.513 | 13821.513 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13821.51 | 13821.51 | 1.0000 | 0.49832114 | 0.429226 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13821.51 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00766331 | 21.00 | 0.00766331 | 47.7938 | 9711.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9013.582 | 9013.582 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9013.58 | 9013.58 | 1.0000 | 0.32497590 | 0.279916 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9013.58 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00766255 | 21.00 | 0.00766255 | 47.7892 | 6332.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13670.292 | 13670.292 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13670.29 | 13670.29 | 1.0000 | 0.49286901 | 0.424530 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13670.29 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765689 | 21.00 | 0.00765689 | 47.7543 | 9605.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9112.580 | 9112.580 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9112.58 | 9112.58 | 1.0000 | 0.32854516 | 0.282990 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9112.58 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00766824 | 21.00 | 0.00766824 | 47.8242 | 6401.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 14509.039 | 14509.039 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14509.04 | 14509.04 | 1.0000 | 0.52310922 | 0.450577 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14509.04 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00754297 | 21.00 | 0.00754297 | 47.0537 | 10193.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9450.727 | 9450.727 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9450.73 | 9450.73 | 1.0000 | 0.34073671 | 0.293491 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9450.73 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00753645 | 21.00 | 0.00753645 | 47.0137 | 6639.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 14341.816 | 14341.816 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14341.82 | 14341.82 | 1.0000 | 0.51708016 | 0.445384 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14341.82 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00753669 | 21.00 | 0.00753669 | 47.0150 | 10076.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9551.952 | 9551.952 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9551.95 | 9551.95 | 1.0000 | 0.34438630 | 0.296635 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9551.95 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00754205 | 21.00 | 0.00754205 | 47.0482 | 6709.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 116631.393 | 85859.813 | 5.234880 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6763 | 1004.8586 | 1.1610 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.234880 | 6.07757258 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 116861.27 | 92300.17 | 1.0020 | 6.07757258 | 5.234880 | 26.38 | 18.15 | 0.01013275 | 52343.3 | 10.97 | 10.97 | 0.00850000 | 32454.4 | -999.0 | -999.00 | -999.00 | -999.00 | 11385.279 | 105475.99 | 34.40 | 0.01447326 | 23.54 | 1.19517000 | 22.8309 | 24.00 | 0.00884574 | 24.00 | 0.00884574 | 45.8883 | 69346.45 | 0.00 | 120262.62 | 85801.92 | 5.83755441 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.28 | 12.25 | 0.00887012 | 34720.8 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23859.924 | 23859.924 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.234880 | 6.07757258 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23859.92 | 23859.92 | 1.0000 | 1.82327178 | 1.570464 | -0.22 | -0.71 | 0.00351580 | 8567.2 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23859.92 | -6.30 | 0.00229779 | -6.30 | 1.19517000 | 76.1030 | 19.13 | 0.00739471 | 19.60 | 0.00707198 | 48.1384 | 19485.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 106937.139 | 77293.943 | 4.617624 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1200 | 1004.8586 | 1.1610 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.617624 | 5.36095301 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | Sensible | 107886.70 | 83075.68 | 1.0089 | 5.36095301 | 4.617624 | 26.71 | 18.45 | 0.01037144 | 53289.3 | 10.96 | 10.96 | 0.00850000 | 32443.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10108.029 | 97778.67 | 34.40 | 0.01447326 | 23.54 | 1.19517000 | 25.8828 | 24.00 | 0.00892737 | 24.00 | 0.00892737 | 46.3063 | 60906.82 | 0.00 | 110266.54 | 77349.70 | 5.14923589 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.95 | 11.93 | 0.00867828 | 33908.2 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25304.037 | 25304.037 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.617624 | 5.36095301 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25304.04 | 25304.04 | 1.0000 | 1.60828590 | 1.385287 | -2.86 | -3.01 | 0.00299183 | 4595.2 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25304.04 | -6.30 | 0.00229779 | -6.30 | 1.19517000 | 86.2760 | 18.78 | 0.00735487 | 19.60 | 0.00713477 | 48.5562 | 23548.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 118390.250 | 87271.859 | 5.333088 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6955 | 1004.8586 | 1.1610 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.333088 | 6.19158994 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | Sensible | 118740.43 | 93554.99 | 1.0030 | 6.19158994 | 5.333088 | 26.30 | 18.13 | 0.01014311 | 52286.2 | 10.97 | 10.97 | 0.00850000 | 32454.5 | -999.0 | -999.00 | -999.00 | -999.00 | 11598.871 | 107141.56 | 34.21 | 0.01447292 | 23.49 | 1.19517000 | 22.4105 | 24.00 | 0.00888620 | 24.00 | 0.00888620 | 46.0958 | 70490.64 | 0.00 | 122076.24 | 87218.13 | 5.94706894 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.31 | 12.28 | 0.00888654 | 34795.3 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24439.896 | 24439.896 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.333088 | 6.19158994 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24439.90 | 24439.90 | 1.0000 | 1.85747698 | 1.599926 | -0.29 | -0.66 | 0.00357391 | 8640.8 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24439.90 | -6.30 | 0.00229779 | -6.30 | 1.19517000 | 74.7016 | 17.44 | 0.00734203 | 17.60 | 0.00722220 | 55.7070 | 28448.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 5.23 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.62 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 5.33 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2806.17 | 2043.00 | 29.33 |
CORE_MID | 2392.17 | 3093.33 | 314.67 |
CORE_TOP | 2639.33 | 3395.00 | 730.50 |
PERIMETER_TOP_ZN_3 | 3416.83 | 3633.67 | 1501.33 |
PERIMETER_TOP_ZN_2 | 3401.33 | 3498.83 | 1363.00 |
PERIMETER_TOP_ZN_1 | 3246.00 | 3149.67 | 1079.17 |
PERIMETER_TOP_ZN_4 | 3274.00 | 3626.50 | 1394.33 |
PERIMETER_BOT_ZN_3 | 3007.17 | 3676.83 | 1156.00 |
PERIMETER_BOT_ZN_2 | 3128.67 | 3328.83 | 962.50 |
PERIMETER_BOT_ZN_1 | 2966.83 | 3371.00 | 918.67 |
PERIMETER_BOT_ZN_4 | 3079.00 | 3385.50 | 986.00 |
PERIMETER_MID_ZN_3 | 3227.33 | 3421.33 | 1165.17 |
PERIMETER_MID_ZN_2 | 2704.67 | 2908.17 | 974.17 |
PERIMETER_MID_ZN_1 | 3143.17 | 2819.83 | 761.00 |
PERIMETER_MID_ZN_4 | 3174.17 | 3381.67 | 1081.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4571.50 | 4347.50 | 1916.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 1.17 | 0.00 | 1.00 | 0.00 |
CORE_TOP | 2.00 | 0.00 | 1.33 | 0.00 |
PERIMETER_TOP_ZN_3 | 35.33 | 4.00 | 14.17 | 2.83 |
PERIMETER_TOP_ZN_2 | 24.33 | 22.33 | 4.33 | 21.33 |
PERIMETER_TOP_ZN_1 | 17.50 | 17.50 | 4.50 | 16.17 |
PERIMETER_TOP_ZN_4 | 25.00 | 25.33 | 7.33 | 14.33 |
PERIMETER_BOT_ZN_3 | 3.17 | 0.00 | 2.67 | 0.00 |
PERIMETER_BOT_ZN_2 | 1.00 | 9.50 | 0.33 | 9.50 |
PERIMETER_BOT_ZN_1 | 123.00 | 34.50 | 122.50 | 34.50 |
PERIMETER_BOT_ZN_4 | 1.00 | 15.33 | 0.33 | 8.17 |
PERIMETER_MID_ZN_3 | 6.67 | 0.50 | 3.00 | 0.50 |
PERIMETER_MID_ZN_2 | 5.00 | 17.17 | 1.17 | 17.17 |
PERIMETER_MID_ZN_1 | 2.33 | 14.33 | 1.17 | 14.33 |
PERIMETER_MID_ZN_4 | 5.00 | 21.17 | 1.50 | 12.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 159.83 | 116.83 | 134.00 | 98.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.719 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.570 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.574 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.633 | 0.084 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.889 | 0.088 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 0.784 | 0.084 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.951 | 0.088 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.583 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.765 | 0.047 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.712 | 0.841 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.769 | 0.047 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.619 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.809 | 0.078 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 0.766 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.902 | 0.074 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.55 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.93 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 11330654.12 | 0.00 | 11330654.12 | 0.00 | 11330654.12 | 13393058.27 | 5144.69 | 369.98 | 3245.33 | 13.96 |
CORE_MID | 9022751.42 | 0.00 | 9022751.42 | 0.00 | 9022751.42 | 13393058.27 | 6371.26 | 152.45 | 2236.29 | 40.01 |
CORE_TOP | 9136012.80 | 0.00 | 9136012.80 | 0.00 | 9136012.80 | 13393058.27 | 6533.25 | 51.20 | 2175.55 | 122.95 |
PERIMETER_TOP_ZN_3 | 2120113.59 | 0.00 | 2120113.59 | 563886.35 | 2683999.94 | 2823374.22 | 5232.97 | 68.72 | 3458.32 | 122.95 |
PERIMETER_TOP_ZN_2 | 1884443.82 | 0.00 | 1884443.82 | 375921.98 | 2260365.79 | 1787429.43 | 4239.33 | 9.01 | 4511.66 | 122.95 |
PERIMETER_TOP_ZN_1 | 2618901.38 | 0.00 | 2618901.38 | 563886.35 | 3182787.73 | 2823374.22 | 4389.37 | 64.10 | 4306.54 | 122.95 |
PERIMETER_TOP_ZN_4 | 2017200.66 | 0.00 | 2017200.66 | 375921.98 | 2393122.64 | 1787312.18 | 4272.12 | 22.54 | 4465.34 | 122.95 |
PERIMETER_BOT_ZN_3 | 1945823.25 | 0.00 | 1945823.25 | 299816.06 | 2245639.32 | 2823374.22 | 5775.87 | 388.62 | 2595.51 | 13.96 |
PERIMETER_BOT_ZN_2 | 1613512.45 | 0.00 | 1613512.45 | 199876.17 | 1813388.62 | 1787429.43 | 4399.30 | 43.62 | 4317.08 | 13.96 |
PERIMETER_BOT_ZN_1 | 2372338.20 | 0.00 | 2372338.20 | 2951634.14 | 5323972.34 | 2823374.22 | 4937.45 | 354.78 | 3467.76 | 13.96 |
PERIMETER_BOT_ZN_4 | 1622457.48 | 0.00 | 1622457.48 | 199876.17 | 1822333.65 | 1787312.18 | 4678.57 | 74.85 | 4006.58 | 13.96 |
PERIMETER_MID_ZN_3 | 2066756.61 | 0.00 | 2066756.61 | 469392.62 | 2536149.23 | 2823374.22 | 5080.81 | 183.40 | 3495.79 | 40.01 |
PERIMETER_MID_ZN_2 | 1851981.75 | 0.00 | 1851981.75 | 312926.53 | 2164908.28 | 1787429.43 | 4234.80 | 8.41 | 4516.79 | 949.01 |
PERIMETER_MID_ZN_1 | 2551131.70 | 0.00 | 2551131.70 | 469392.62 | 3020524.32 | 2823374.22 | 4982.50 | 142.29 | 3635.21 | 40.01 |
PERIMETER_MID_ZN_4 | 1906958.27 | 0.00 | 1906958.27 | 312926.53 | 2219884.81 | 1787312.18 | 4295.51 | 28.54 | 4435.95 | 40.01 |
Total Facility | 54061037.49 | 0.00 | 54061037.49 | 7095457.52 | 61156495.01 | 67843644.98 | 6717.35 | 875.91 | 4565.20 | 1038.36 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.5289 | 0.0000 | 0.5289 | 0.0000 | 0.5289 | 0.4247 | 2328.90 | 369.98 | 3244.12 |
CORE_MID | 0.4202 | 0.0000 | 0.4202 | 0.0000 | 0.4202 | 0.4247 | 3556.79 | 152.45 | 2233.76 |
CORE_TOP | 0.4242 | 0.0000 | 0.4242 | 0.0000 | 0.4242 | 0.4247 | 3719.83 | 51.20 | 2171.96 |
PERIMETER_TOP_ZN_3 | 0.0985 | 0.0000 | 0.0985 | 0.0131 | 0.1115 | 0.0895 | 2419.59 | 68.72 | 3454.69 |
PERIMETER_TOP_ZN_2 | 0.0876 | 0.0000 | 0.0876 | 0.0087 | 0.0963 | 0.0567 | 1426.40 | 8.98 | 4507.62 |
PERIMETER_TOP_ZN_1 | 0.1218 | 0.0000 | 0.1218 | 0.0131 | 0.1348 | 0.0895 | 1576.04 | 64.08 | 4302.88 |
PERIMETER_TOP_ZN_4 | 0.0937 | 0.0000 | 0.0937 | 0.0087 | 0.1024 | 0.0567 | 1459.39 | 22.37 | 4461.24 |
PERIMETER_BOT_ZN_3 | 0.0908 | 0.0000 | 0.0908 | 0.0069 | 0.0977 | 0.0895 | 2960.41 | 388.62 | 2593.96 |
PERIMETER_BOT_ZN_2 | 0.0753 | 0.0000 | 0.0753 | 0.0046 | 0.0799 | 0.0567 | 1583.88 | 43.62 | 4315.50 |
PERIMETER_BOT_ZN_1 | 0.1107 | 0.0000 | 0.1107 | 0.1309 | 0.2416 | 0.0895 | 2121.85 | 354.76 | 3466.39 |
PERIMETER_BOT_ZN_4 | 0.0757 | 0.0000 | 0.0757 | 0.0046 | 0.0803 | 0.0567 | 1863.13 | 74.85 | 4005.02 |
PERIMETER_MID_ZN_3 | 0.0963 | 0.0000 | 0.0963 | 0.0109 | 0.1071 | 0.0895 | 2266.91 | 183.38 | 3492.71 |
PERIMETER_MID_ZN_2 | 0.0797 | 0.0000 | 0.0797 | 0.0077 | 0.0874 | 0.0567 | 1411.99 | 6.20 | 3615.81 |
PERIMETER_MID_ZN_1 | 0.1189 | 0.0000 | 0.1189 | 0.0109 | 0.1298 | 0.0895 | 2168.30 | 142.29 | 3632.41 |
PERIMETER_MID_ZN_4 | 0.0888 | 0.0000 | 0.0888 | 0.0073 | 0.0961 | 0.0567 | 1481.89 | 28.54 | 4432.56 |
Total Facility | 2.5111 | 0.0000 | 2.5111 | 0.2274 | 2.7385 | 2.1513 | 3901.18 | 875.60 | 4559.41 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 25454153.87 | 0.00 | 25454153.87 | 22614548.33 | 4212.12 | 2.18 | 4545.70 | 13.96 |
PACU_VAV_MID | 23452345.09 | 0.00 | 23452345.09 | 22614548.33 | 4211.46 | 0.57 | 4547.96 | 40.01 |
PACU_VAV_TOP | 23960578.85 | 0.00 | 23960578.85 | 22614548.33 | 4230.72 | 1.28 | 4528.00 | 122.92 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.1881 | 0.0000 | 1.1881 | 0.7171 | 1397.93 | 1.68 | 4543.39 |
PACU_VAV_MID | 1.0924 | 0.0000 | 1.0924 | 0.7171 | 1397.45 | 0.53 | 4545.03 |
PACU_VAV_TOP | 1.1130 | 0.0000 | 1.1130 | 0.7171 | 1417.31 | 1.28 | 4524.42 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 2380.04 | 0.00 | 0.00 | 0.00 | 2197.91 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 2287.19 | 0.00 | 0.00 | 0.00 | 2328.18 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2393.58 | 0.00 | 0.00 | 0.00 | 2330.49 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.0005 | 0.0000 | 0.0000 | 0.0000 | 1.0594 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 1.7961 | 0.0000 | 0.0000 | 0.0000 | 1.0551 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 1.8368 | 0.0000 | 0.0000 | 0.0000 | 1.0493 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 829 |
Defaulted Fields | 545 |
Fields with Defaults | 2217 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1743.27 | 13157.78 | 23-JUL-17:10 | 248775.13 | 09-JAN-07:10 |
Electricity:Building | 1070.89 | 12913.45 | 21-MAY-17:10 | 84122.50 | 03-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 322.66 | 4214.70 | 01-JAN-00:10 | 25737.69 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1070.89 | 12913.45 | 21-MAY-17:10 | 84122.50 | 03-JAN-08:10 |
InteriorLights:Electricity | 365.46 | 1672.11 | 01-JAN-11:30 | 38257.79 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 365.46 | 1672.11 | 01-JAN-11:30 | 38257.79 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 365.46 | 1672.11 | 01-JAN-11:30 | 38257.79 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 365.46 | 1672.11 | 01-JAN-11:30 | 38257.79 | 03-JAN-08:10 |
Electricity:Zone:CORE_MID | 201.92 | 2251.11 | 01-JAN-00:10 | 14360.82 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 201.92 | 2251.11 | 01-JAN-00:10 | 14360.82 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 35.35 | 428.29 | 16-APR-17:10 | 3027.38 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 11.02 | 42.19 | 01-JAN-11:30 | 1592.13 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 11.02 | 42.19 | 01-JAN-11:30 | 1592.13 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.22 | 271.13 | 21-MAY-17:10 | 1916.52 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.82 | 26.71 | 01-JAN-09:20 | 1007.95 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.82 | 26.71 | 01-JAN-09:20 | 1007.95 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 34.97 | 428.29 | 12-MAR-17:10 | 3027.37 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.64 | 42.19 | 01-JAN-09:20 | 1592.13 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.64 | 42.19 | 01-JAN-09:20 | 1592.13 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 22.29 | 271.13 | 05-MAR-18:10 | 1916.45 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.89 | 26.71 | 01-JAN-11:00 | 1007.89 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.89 | 26.71 | 01-JAN-11:00 | 1007.89 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 35.30 | 428.29 | 16-APR-17:10 | 3027.38 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.97 | 42.19 | 01-JAN-11:20 | 1592.13 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.97 | 42.19 | 01-JAN-11:20 | 1592.13 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.20 | 271.13 | 23-APR-17:10 | 1916.52 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.80 | 26.71 | 01-JAN-09:10 | 1007.95 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.80 | 26.71 | 01-JAN-09:10 | 1007.95 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 34.94 | 428.29 | 12-MAR-17:10 | 3027.37 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.61 | 42.19 | 01-JAN-09:20 | 1592.13 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.61 | 42.19 | 01-JAN-09:20 | 1592.13 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 22.27 | 271.13 | 05-MAR-18:10 | 1916.45 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.87 | 26.71 | 01-JAN-11:00 | 1007.89 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.87 | 26.71 | 01-JAN-11:00 | 1007.89 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 35.35 | 428.29 | 16-APR-17:10 | 3027.38 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 11.02 | 42.19 | 01-JAN-11:30 | 1592.13 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 11.02 | 42.19 | 01-JAN-11:30 | 1592.13 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.22 | 271.13 | 21-MAY-17:10 | 1916.52 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.82 | 26.71 | 01-JAN-09:20 | 1007.95 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.82 | 26.71 | 01-JAN-09:20 | 1007.95 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 34.97 | 428.29 | 12-MAR-17:10 | 3027.37 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 10.64 | 42.19 | 01-JAN-09:20 | 1592.13 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 10.64 | 42.19 | 01-JAN-09:20 | 1592.13 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 22.29 | 271.13 | 05-MAR-18:10 | 1916.45 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.89 | 26.71 | 01-JAN-11:00 | 1007.89 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.89 | 26.71 | 01-JAN-11:00 | 1007.89 | 03-JAN-08:10 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 560.50 | 244.33 | 23-APR-17:10 | 206320.23 | 09-JAN-07:10 |
ExteriorEquipment:Electricity | 17.12 | 243.72 | 01-JAN-00:10 | 1242.18 | 03-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 17.12 | 243.72 | 01-JAN-00:10 | 1242.18 | 03-JAN-08:20 |
ElectricityPurchased:Facility | 1743.27 | 13157.78 | 23-JUL-17:10 | 248775.13 | 09-JAN-07:10 |
ElectricityPurchased:Plant | 1743.27 | 13157.78 | 23-JUL-17:10 | 248775.13 | 09-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1743.27 | 13157.78 | 23-JUL-17:10 | 248775.13 | 09-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1743.27 | 13157.78 | 23-JUL-17:10 | 248775.13 | 09-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1743.27 | 13157.78 | 23-JUL-17:10 | 248775.13 | 09-JAN-07:10 |
ElectricityNet:Plant | 1743.27 | 13157.78 | 23-JUL-17:10 | 248775.13 | 09-JAN-07:10 |
Cogeneration:ElectricityNet | 1743.27 | 13157.78 | 23-JUL-17:10 | 248775.13 | 09-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1743.27 | 13157.78 | 23-JUL-17:10 | 248775.13 | 09-JAN-07:10 |
Heating:Electricity | 131.49 | 0.00 | 01-JAN-00:40 | 199863.23 | 09-JAN-07:10 |
General:Heating:Electricity | 131.49 | 0.00 | 01-JAN-00:40 | 199863.23 | 09-JAN-07:10 |
Fans:Electricity | 70.99 | 0.00 | 01-JAN-00:40 | 14150.04 | 02-AUG-15:50 |
General:Fans:Electricity | 70.99 | 0.00 | 01-JAN-00:40 | 14150.04 | 02-AUG-15:50 |
ExteriorLights:Electricity | 111.74 | 0.00 | 01-JAN-07:50 | 8596.48 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 111.74 | 0.00 | 01-JAN-07:50 | 8596.48 | 01-JAN-06:10 |
Cooling:Electricity | 340.90 | 0.00 | 01-JAN-00:10 | 78630.70 | 07-JUL-16:00 |
General:Cooling:Electricity | 340.90 | 0.00 | 01-JAN-00:10 | 78630.70 | 07-JUL-16:00 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 05-JAN-06:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 05-JAN-06:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 05-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 10.27 | 0.00 | 01-JAN-00:10 | 1075.04 | 03-JAN-08:20 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 147.29 | 2003.43 | 06-JAN-05:10 | 58954.41 | 03-FEB-07:40 |
NaturalGas:HVAC | 19.16 | 0.00 | 01-JAN-00:10 | 49980.68 | 03-FEB-07:30 |
Heating:NaturalGas | 19.16 | 0.00 | 01-JAN-00:10 | 49980.68 | 03-FEB-07:30 |
General:Heating:NaturalGas | 19.16 | 0.00 | 01-JAN-00:10 | 49980.68 | 03-FEB-07:30 |
NaturalGas:Plant | 128.13 | 2003.43 | 03-JAN-17:10 | 10135.32 | 01-FEB-12:10 |
WaterSystems:NaturalGas | 128.13 | 2003.43 | 03-JAN-17:10 | 10135.32 | 01-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 128.13 | 2003.43 | 03-JAN-17:10 | 10135.32 | 01-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2805.69 | 0.00 | 01-JAN-00:40 | 425805.91 | 07-JUL-16:00 |
EnergyTransfer:Building | 1275.56 | 0.00 | 01-JAN-00:40 | 167683.35 | 09-JAN-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 258.34 | 0.00 | 01-JAN-00:10 | 27670.66 | 21-AUG-08:00 |
Heating:EnergyTransfer | 76.67 | 0.00 | 01-JAN-00:40 | 162908.23 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.04 | 0.00 | 01-JAN-00:10 | 6752.18 | 02-JAN-07:10 |
General:Heating:EnergyTransfer | 76.67 | 0.00 | 01-JAN-00:40 | 162908.23 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.04 | 0.00 | 01-JAN-00:10 | 6752.18 | 02-JAN-07:10 |
Cooling:EnergyTransfer | 1198.89 | 0.00 | 01-JAN-00:40 | 166132.75 | 02-AUG-15:50 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 258.30 | 0.00 | 01-JAN-00:10 | 27670.66 | 21-AUG-08:00 |
General:Cooling:EnergyTransfer | 1198.89 | 0.00 | 01-JAN-00:40 | 166132.75 | 02-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 258.30 | 0.00 | 01-JAN-00:10 | 27670.66 | 21-AUG-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.60 | 0.00 | 01-JAN-00:40 | 13989.47 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 12.82 | 0.00 | 01-JAN-00:40 | 13989.47 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 12.82 | 0.00 | 01-JAN-00:40 | 13989.47 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 37.78 | 0.00 | 01-JAN-00:10 | 10712.64 | 01-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 37.78 | 0.00 | 01-JAN-00:10 | 10712.64 | 01-AUG-14:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 25.86 | 0.00 | 01-JAN-00:10 | 8045.66 | 09-JAN-07:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.64 | 0.00 | 01-JAN-00:10 | 8045.66 | 09-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.64 | 0.00 | 01-JAN-00:10 | 8045.66 | 09-JAN-07:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 21.22 | 0.00 | 01-JAN-00:10 | 4529.37 | 10-JUL-15:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 21.22 | 0.00 | 01-JAN-00:10 | 4529.37 | 10-JUL-15:50 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 28.04 | 0.00 | 01-JAN-00:10 | 4931.96 | 18-AUG-16:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 3.26 | 0.00 | 01-JAN-00:10 | 4608.53 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 3.26 | 0.00 | 01-JAN-00:10 | 4608.53 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.79 | 0.00 | 01-JAN-00:10 | 4931.96 | 18-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.79 | 0.00 | 01-JAN-00:10 | 4931.96 | 18-AUG-16:00 |
EnergyTransfer:Zone:CORE_MID | 186.46 | 0.00 | 01-JAN-00:10 | 19217.04 | 21-AUG-08:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.69 | 0.00 | 01-JAN-00:10 | 16607.19 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.69 | 0.00 | 01-JAN-00:10 | 16607.19 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_MID | 185.77 | 0.00 | 01-JAN-00:10 | 19217.04 | 21-AUG-08:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 185.77 | 0.00 | 01-JAN-00:10 | 19217.04 | 21-AUG-08:10 |
EnergyTransfer:Zone:CORE_TOP | 185.49 | 0.00 | 01-JAN-00:40 | 29762.97 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 3.69 | 0.00 | 01-JAN-00:10 | 29762.97 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 3.69 | 0.00 | 01-JAN-00:10 | 29762.97 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 181.80 | 0.00 | 01-JAN-00:40 | 21529.98 | 07-JUL-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 181.80 | 0.00 | 01-JAN-00:40 | 21529.98 | 07-JUL-15:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 48.99 | 0.00 | 01-JAN-00:40 | 10414.85 | 13-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 8.66 | 0.00 | 01-JAN-00:40 | 10414.85 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 8.66 | 0.00 | 01-JAN-00:40 | 10414.85 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 0.00 | 01-JAN-00:20 | 7522.16 | 14-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 0.00 | 01-JAN-00:20 | 7522.16 | 14-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 41.42 | 0.00 | 01-JAN-00:40 | 8311.19 | 07-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.48 | 0.00 | 01-JAN-00:40 | 8280.27 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.48 | 0.00 | 01-JAN-00:40 | 8280.27 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 36.94 | 0.00 | 01-JAN-00:20 | 8311.19 | 07-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 36.94 | 0.00 | 01-JAN-00:20 | 8311.19 | 07-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 59.29 | 0.00 | 01-JAN-00:40 | 11081.43 | 10-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.44 | 0.00 | 01-JAN-00:40 | 10976.81 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.44 | 0.00 | 01-JAN-00:40 | 10976.81 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 53.85 | 0.00 | 01-JAN-00:20 | 11081.43 | 10-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 53.85 | 0.00 | 01-JAN-00:20 | 11081.43 | 10-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 42.20 | 0.00 | 01-JAN-00:40 | 8447.57 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.16 | 0.00 | 01-JAN-00:40 | 8351.03 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.16 | 0.00 | 01-JAN-00:40 | 8351.03 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 37.05 | 0.00 | 01-JAN-00:20 | 8447.57 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 37.05 | 0.00 | 01-JAN-00:20 | 8447.57 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 41.26 | 0.00 | 01-JAN-00:10 | 7874.15 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.85 | 0.00 | 01-JAN-00:10 | 7874.15 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.85 | 0.00 | 01-JAN-00:10 | 7874.15 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.41 | 0.00 | 01-JAN-00:10 | 6144.98 | 09-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.41 | 0.00 | 01-JAN-00:10 | 6144.98 | 09-AUG-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 35.90 | 0.00 | 01-JAN-00:10 | 6949.32 | 07-JUL-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.80 | 0.00 | 01-JAN-00:10 | 5809.02 | 13-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.80 | 0.00 | 01-JAN-00:10 | 5809.02 | 13-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 34.10 | 0.00 | 01-JAN-00:10 | 6949.32 | 07-JUL-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 34.10 | 0.00 | 01-JAN-00:10 | 6949.32 | 07-JUL-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 58.61 | 0.00 | 01-JAN-00:10 | 11257.65 | 13-FEB-07:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 9.30 | 0.00 | 01-JAN-00:10 | 11257.65 | 13-FEB-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 9.30 | 0.00 | 01-JAN-00:10 | 11257.65 | 13-FEB-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 49.30 | 0.00 | 01-JAN-00:10 | 11044.58 | 18-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 49.30 | 0.00 | 01-JAN-00:10 | 11044.58 | 18-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 35.05 | 0.00 | 01-JAN-00:10 | 6948.41 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.98 | 0.00 | 01-JAN-00:10 | 5691.00 | 09-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.98 | 0.00 | 01-JAN-00:10 | 5691.00 | 09-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 33.07 | 0.00 | 01-JAN-00:10 | 6948.41 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 33.07 | 0.00 | 01-JAN-00:10 | 6948.41 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 44.55 | 0.00 | 01-JAN-00:10 | 8360.57 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 4.05 | 0.00 | 01-JAN-00:10 | 8360.57 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 4.05 | 0.00 | 01-JAN-00:10 | 8360.57 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 40.50 | 0.00 | 01-JAN-00:10 | 6739.60 | 14-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 40.50 | 0.00 | 01-JAN-00:10 | 6739.60 | 14-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 38.72 | 0.00 | 01-JAN-00:10 | 7930.54 | 07-JUL-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.15 | 0.00 | 01-JAN-00:10 | 6369.22 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.15 | 0.00 | 01-JAN-00:10 | 6369.22 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 36.57 | 0.00 | 01-JAN-00:10 | 7930.54 | 07-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 36.57 | 0.00 | 01-JAN-00:10 | 7930.54 | 07-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 55.88 | 0.00 | 01-JAN-00:10 | 10523.35 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.30 | 0.00 | 01-JAN-00:10 | 9273.15 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.30 | 0.00 | 01-JAN-00:10 | 9273.15 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 53.58 | 0.00 | 01-JAN-00:10 | 10523.35 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 53.58 | 0.00 | 01-JAN-00:10 | 10523.35 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 38.91 | 0.00 | 01-JAN-00:10 | 7841.71 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.37 | 0.00 | 01-JAN-00:10 | 6414.87 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.37 | 0.00 | 01-JAN-00:10 | 6414.87 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 36.54 | 0.00 | 01-JAN-00:10 | 7841.71 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 36.54 | 0.00 | 01-JAN-00:10 | 7841.71 | 02-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 44.21 | 0.00 | 01-JAN-00:10 | 5832.45 | 27-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 44.21 | 0.00 | 01-JAN-00:10 | 5832.45 | 27-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 44.21 | 0.00 | 01-JAN-00:10 | 5832.45 | 27-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 44.21 | 0.00 | 01-JAN-00:10 | 5832.45 | 27-JAN-12:10 |
EnergyTransfer:HVAC | 1485.91 | 0.00 | 01-JAN-00:40 | 259136.04 | 07-JUL-16:00 |
HeatingCoils:EnergyTransfer | 146.82 | 0.00 | 01-JAN-00:40 | 215164.88 | 13-FEB-07:10 |
CoolingCoils:EnergyTransfer | 1339.09 | 0.00 | 01-JAN-00:10 | 259136.04 | 07-JUL-16:00 |
EnergyTransfer:Plant | 44.21 | 0.00 | 01-JAN-00:10 | 5832.45 | 27-JAN-12:10 |
WaterSystems:EnergyTransfer | 44.21 | 0.00 | 01-JAN-00:10 | 5832.45 | 27-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 44.21 | 0.00 | 01-JAN-00:10 | 5832.45 | 27-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.038 | -258.300 | 0.000 | 0.000 | 33.081 | 86.497 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -97.484 |
CORE_MID | 0.000 | 0.000 | 0.691 | -185.765 | 0.000 | 0.000 | 34.332 | 86.497 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -51.179 |
CORE_TOP | 0.000 | 0.000 | 3.687 | -181.804 | 0.000 | 0.000 | 34.976 | 86.497 | 115.425 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -58.782 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 8.656 | -40.337 | 0.000 | 0.000 | 7.497 | 11.019 | 24.333 | 18.124 | 0.000 | 0.299 | 3.295 | 0.000 | -27.824 | 0.000 | -5.062 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 4.478 | -36.937 | 0.000 | 0.000 | 4.703 | 6.817 | 15.404 | 29.185 | 0.000 | 0.192 | 0.000 | 0.000 | -16.985 | 0.000 | -3.436 | -3.421 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 5.444 | -53.844 | 0.000 | 0.000 | 7.308 | 10.636 | 24.332 | 51.223 | 0.000 | 0.279 | 0.000 | 0.000 | -25.841 | 0.000 | -5.389 | -14.149 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 5.157 | -37.045 | 0.000 | 0.000 | 4.767 | 6.890 | 15.403 | 29.654 | 0.000 | 0.191 | 0.000 | 0.000 | -18.202 | 0.000 | -3.456 | -3.360 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 3.853 | -37.407 | 0.000 | 0.000 | 7.474 | 10.970 | 24.333 | 18.547 | 0.000 | 0.174 | 3.937 | 0.000 | -29.009 | 0.000 | -2.871 | -0.001 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.796 | -34.101 | 0.000 | 0.000 | 4.658 | 6.797 | 15.404 | 29.356 | 0.000 | 0.105 | 0.003 | 0.000 | -18.085 | 0.000 | -1.985 | -3.944 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 9.304 | -49.303 | 0.000 | 0.000 | 7.367 | 10.610 | 24.332 | 51.839 | 0.000 | 4.071 | 0.003 | 0.000 | -27.552 | 0.000 | -21.898 | -8.770 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.977 | -33.070 | 0.000 | 0.000 | 4.702 | 6.865 | 15.403 | 29.896 | 0.000 | 0.102 | 0.000 | 0.000 | -19.417 | 0.000 | -1.997 | -4.461 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 4.054 | -40.494 | 0.000 | 0.000 | 7.422 | 11.019 | 24.333 | 17.997 | 0.000 | 0.255 | 9.406 | 0.000 | -29.497 | 0.000 | -4.494 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 2.147 | -36.571 | 0.000 | 0.000 | 3.454 | 6.817 | 15.404 | 29.040 | 0.000 | 0.164 | 0.530 | 0.000 | -17.940 | 0.000 | -3.044 | -0.001 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 2.300 | -53.580 | 0.000 | 0.000 | 7.217 | 10.636 | 24.332 | 50.964 | 0.000 | 0.236 | 0.000 | 0.000 | -27.404 | 0.000 | -4.789 | -9.912 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 2.374 | -36.540 | 0.000 | 0.000 | 4.713 | 6.890 | 15.403 | 29.557 | 0.000 | 0.159 | 0.000 | 0.000 | -19.290 | 0.000 | -3.066 | -0.200 |
TOPFLOOR_PLENUM | 12.818 | -37.777 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.291 | 32.447 | 0.000 | 0.000 | 0.000 | -7.779 | -0.000 |
MIDFLOOR_PLENUM | 4.638 | -21.217 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.364 | 24.133 | 0.000 | 0.000 | 0.000 | -7.918 | -0.000 |
FIRSTFLOOR_PLENUM | 3.258 | -24.785 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.274 | 27.783 | 0.000 | 0.000 | 0.000 | -6.531 | -0.001 |
Total Facility | 20.714 | -83.779 | 55.956 | -1115.098 | 0.000 | 0.000 | 173.670 | 365.456 | 705.434 | 385.382 | 0.000 | 7.156 | 101.539 | 0.000 | -277.046 | 0.000 | -83.716 | -255.664 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 10-AUG-04:02 | 0.00 | 0.00 | 0.00 | -46028.68 | 0.00 | 0.00 | 0.00 | 839.14 | 4405.64 | 0.00 | 0.00 | 0.00 | 40783.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 03-AUG-04:02 | 0.00 | 0.00 | 0.00 | -34131.03 | 0.00 | 0.00 | 0.00 | 839.14 | 2442.06 | 0.00 | 0.00 | 0.00 | 30849.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-JUL-04:02 | 0.00 | 0.00 | 0.00 | -35923.92 | 0.00 | 0.00 | 0.00 | 839.14 | 2442.06 | 0.00 | 0.00 | 0.00 | 32642.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-13:43 | 0.00 | 0.00 | 0.00 | -12496.39 | 0.00 | 0.00 | 27.09 | 42.19 | 478.42 | 3589.66 | 0.00 | 150.26 | 8208.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 13-AUG-10:23 | 0.00 | 0.00 | 0.00 | -12002.27 | 0.00 | 0.00 | 16.03 | 26.71 | 302.86 | 5446.55 | 0.00 | 7.13 | 6202.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-14:32 | 0.00 | 0.00 | 0.00 | -15075.39 | 0.00 | 0.00 | 25.47 | 42.19 | 478.41 | 8565.30 | 0.00 | 10.84 | 5953.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 13-AUG-17:02 | 0.00 | 0.00 | 0.00 | -13717.53 | 0.00 | 0.00 | 0.00 | 26.71 | 244.42 | 7302.55 | 0.00 | 73.34 | 6070.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 09-AUG-15:00 | 0.00 | 0.00 | 0.00 | -6144.90 | 0.00 | 0.00 | 737.23 | 759.45 | 1435.25 | 4050.77 | 0.00 | 15.09 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -852.89 |
PERIMETER_BOT_ZN_2 | 27-AUG-09:52 | 0.00 | 0.00 | 0.00 | -10884.69 | 0.00 | 0.00 | 16.09 | 26.71 | 302.86 | 7208.63 | 0.00 | 0.00 | 3331.79 | 0.00 | -0.00 | 0.00 | -1.38 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-14:23 | 0.00 | 0.00 | 0.00 | -12626.55 | 0.00 | 0.00 | 25.70 | 42.19 | 478.41 | 8982.19 | 0.00 | 1.50 | 3096.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-JUN-16:32 | 0.00 | 0.00 | 0.00 | -11001.95 | 0.00 | 0.00 | 16.28 | 26.71 | 302.86 | 7414.31 | 0.00 | 40.95 | 3200.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-13:43 | 0.00 | 0.00 | 0.00 | -9462.87 | 0.00 | 0.00 | 28.61 | 42.19 | 478.42 | 3670.61 | 0.00 | 128.81 | 5114.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 27-AUG-09:52 | 0.00 | 0.00 | 0.00 | -12414.35 | 0.00 | 0.00 | 14.99 | 26.71 | 302.86 | 7116.43 | 0.00 | 0.00 | 4958.50 | 0.00 | -0.00 | 0.00 | -5.14 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-14:23 | 0.00 | 0.00 | 0.00 | -13478.53 | 0.00 | 0.00 | 25.75 | 42.19 | 478.41 | 8963.38 | 0.00 | 4.96 | 3963.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 04-JUL-17:52 | 0.00 | 0.00 | 0.00 | -12927.63 | 0.00 | 0.00 | 0.00 | 26.71 | 244.42 | 5880.60 | 0.00 | 52.76 | 6723.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 01-AUG-14:00 | 0.00 | -10712.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.96 | 10622.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 10-JUL-15:50 | 0.00 | -4529.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.50 | 4408.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 18-AUG-16:00 | 0.00 | -4931.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.30 | 4851.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-AUG-04:02 | 0.00 | 8556.90 | 0.00 | -187737.14 | 0.00 | 0.00 | 0.00 | 4250.75 | 14333.92 | 0.00 | 0.00 | 0.00 | 166686.00 | 0.00 | -5573.93 | 0.00 | -516.50 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-06:13 | 0.00 | 0.00 | 17973.42 | 0.00 | 0.00 | 0.00 | 475.83 | 839.14 | 4989.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24277.90 |
CORE_MID | 09-JAN-05:11 | 0.00 | 0.00 | 18575.59 | 0.00 | 0.00 | 0.00 | 0.00 | 839.14 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21856.79 |
CORE_TOP | 09-JAN-05:11 | 0.00 | 0.00 | 32901.30 | 0.00 | 0.00 | 0.00 | 0.00 | 839.14 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -36182.50 |
PERIMETER_TOP_ZN_3 | 12-FEB-08:42 | 0.00 | 0.00 | 11664.24 | 0.00 | 0.00 | 0.00 | 59.96 | 61.72 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3264.70 | 0.00 | -1350.71 | -7648.93 |
PERIMETER_TOP_ZN_2 | 12-FEB-04:42 | 0.00 | 0.00 | 10789.47 | 0.00 | 0.00 | 0.00 | 0.00 | 56.00 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2690.59 | 0.00 | -1196.75 | -7202.54 |
PERIMETER_TOP_ZN_1 | 12-FEB-04:42 | 0.00 | 0.00 | 13271.37 | 0.00 | 0.00 | 0.00 | 0.00 | 88.45 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4064.25 | 0.00 | -1788.71 | -7892.96 |
PERIMETER_TOP_ZN_4 | 12-FEB-08:42 | 0.00 | 0.00 | 11134.71 | 0.00 | 0.00 | 0.00 | 38.03 | 39.07 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2174.62 | 0.00 | -914.68 | -8425.36 |
PERIMETER_BOT_ZN_3 | 09-JAN-05:01 | 0.00 | 0.00 | 8965.84 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2814.89 | 0.00 | -520.59 | -6322.05 |
PERIMETER_BOT_ZN_2 | 09-JAN-05:01 | 0.00 | 0.00 | 7906.76 | 0.00 | 0.00 | 0.00 | 0.00 | 111.99 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1820.44 | 0.00 | -349.98 | -6174.22 |
PERIMETER_BOT_ZN_1 | 03-FEB-07:10 | 0.00 | 0.00 | 11369.47 | 0.00 | 0.00 | 0.00 | 193.30 | 530.72 | 637.88 | 0.00 | 0.00 | 0.00 | 11651.80 | 0.00 | -4375.65 | 0.00 | -20007.52 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JAN-05:01 | 0.00 | 0.00 | 7974.41 | 0.00 | 0.00 | 0.00 | 0.00 | 111.98 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1873.53 | 0.00 | -349.56 | -6189.19 |
PERIMETER_MID_ZN_3 | 13-FEB-04:12 | 0.00 | 0.00 | 9865.67 | 0.00 | 0.00 | 0.00 | 0.00 | 88.45 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3333.75 | 0.00 | -1433.22 | -5701.96 |
PERIMETER_MID_ZN_2 | 13-FEB-04:12 | 0.00 | 0.00 | 8513.62 | 0.00 | 0.00 | 0.00 | 0.00 | 56.00 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2227.74 | 0.00 | -967.44 | -5700.32 |
PERIMETER_MID_ZN_1 | 09-JAN-05:11 | 0.00 | 0.00 | 11299.53 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2678.94 | 0.00 | -798.29 | -8514.00 |
PERIMETER_MID_ZN_4 | 12-FEB-07:12 | 0.00 | 0.00 | 8609.31 | 0.00 | 0.00 | 0.00 | 37.29 | 55.99 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2947.99 | 0.00 | -1076.58 | -4980.88 |
TOPFLOOR_PLENUM | 13-FEB-06:12 | 14839.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -592.98 | -14246.82 |
MIDFLOOR_PLENUM | 09-JAN-07:11 | 8537.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -366.70 | -8170.61 |
FIRSTFLOOR_PLENUM | 02-JAN-07:03 | 5910.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -141.09 | -5769.28 |
Total Facility | 02-JAN-06:11 | 6746.93 | 0.00 | 180119.15 | 0.00 | 0.00 | 0.00 | 2632.28 | 4250.75 | 17291.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18598.77 | 0.00 | -2617.81 | -189824.05 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.7449 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.2349 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.2165 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6176 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.6313 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.3331 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.8724 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3783 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.6083 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3709 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.8156 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4447 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1089 | 3.1089 | 0.7897 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3292 | 2.3292 | 0.7640 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4561 | 2.4561 | 0.7958 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7697 | 0.7697 | 0.1678 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7226 | 0.7226 | 0.1445 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8855 | 0.8855 | 0.1771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7974 | 0.7974 | 0.1595 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6291 | 0.6291 | 0.1667 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6262 | 0.6262 | 0.1252 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7322 | 0.7322 | 0.1669 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6485 | 0.6485 | 0.1297 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6741 | 0.6741 | 0.1611 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6969 | 0.6969 | 0.1394 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7891 | 0.7891 | 0.1610 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7273 | 0.7273 | 0.1455 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.7449 | 5.2349 | 5.7449 | 1.3783 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.2165 | 4.6176 | 5.2165 | 1.3709 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.6313 | 5.3331 | 5.6313 | 1.4447 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5545 | 1.5545 | 0.7897 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1646 | 1.1646 | 0.7640 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2280 | 1.2280 | 0.7958 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3848 | 0.3848 | 0.1678 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3613 | 0.3613 | 0.1445 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4428 | 0.4428 | 0.1771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3987 | 0.3987 | 0.1595 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3146 | 0.3146 | 0.1667 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3131 | 0.3131 | 0.1252 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3661 | 0.3661 | 0.1669 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3242 | 0.3242 | 0.1297 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3371 | 0.3371 | 0.1611 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3485 | 0.3485 | 0.1394 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3945 | 0.3945 | 0.1610 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3636 | 0.3636 | 0.1455 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.8724 | 1.3783 | 1.3783 | 1.3783 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.6083 | 1.3709 | 1.3709 | 1.3709 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.8156 | 1.4447 | 1.4447 | 1.4447 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 134.00 |
Number of hours cooling loads not met | 98.83 |
Number of hours not met | 232.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 131.49 | 199863.23 | 19.16 | 49980.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 340.90 | 78630.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 365.46 | 38257.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 111.74 | 8596.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 17.12 | 1242.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 70.99 | 14150.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 128.13 | 10135.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1743.27 |
Natural Gas | 0.00 | 147.29 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1890.56 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 73.35 |
Space Heating | 26.39 |
Space Cooling | 68.42 |
Fans (All) | 14.25 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 349.90 |
Subtotal | 349.90 |
Natural Gas [MJ/m2] | |
Space Heating | 3.85 |
Service Water Heating | 25.72 |
Miscellaneous (All) | 29.56 |
Subtotal | 29.56 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.33 |
Space Heating | 7.97 |
Space Cooling | 18.03 |
Fans (All) | 3.75 |
Service Water Heating | 6.78 |
Receptacle Equipment | 37.31 |
Miscellaneous | 6.82 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8627.17 | 132.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8722.33 | 37.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8675.83 | 84.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8691.67 | 68.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8640.50 | 119.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8704.33 | 55.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8732.50 | 27.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8679.00 | 81.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8693.00 | 67.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8710.17 | 49.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8645.17 | 114.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8592.00 | 168.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8592.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 168.00 | 0.00 | 0.00 | 0.00 |
Average | 8703.05 | 56.95 | 0.00 | 0.00 | 0.00 |
Sum | 156654.83 | 1025.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128287.67 | 16.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 16.33 | 0.00 | 0.00 | 0.00 |
Average | 34142.43 | 0.91 | 0.00 | 0.00 | 0.00 |
Sum | 614563.67 | 16.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8419.83 | 340.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8739.67 | 20.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7913.33 | 846.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7905.50 | 854.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7887.67 | 872.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7901.50 | 858.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8134.67 | 625.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8016.67 | 743.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7894.50 | 865.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7986.00 | 774.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7896.50 | 863.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7884.00 | 876.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7850.83 | 909.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7861.67 | 898.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8208.50 | 551.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8248.17 | 511.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8312.83 | 447.17 | 0.00 | 0.00 | 0.00 |
Min | 7850.83 | 4.50 | 0.00 | 0.00 | 0.00 |
Max | 8755.50 | 909.17 | 0.00 | 0.00 | 0.00 |
Average | 8100.96 | 659.04 | 0.00 | 0.00 | 0.00 |
Sum | 145817.33 | 11862.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128192.00 | 112.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128303.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128302.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24880.83 | 28.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24883.50 | 25.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24897.33 | 11.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 23953.50 | 955.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24879.67 | 29.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24879.50 | 29.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128303.00 | 955.50 | 0.00 | 0.00 | 0.00 |
Average | 34077.00 | 66.33 | 0.00 | 0.00 | 0.00 |
Sum | 613386.00 | 1194.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124653E+11 | 12699.98 | 31-JAN-17:00 | 19.40 | 13.37 | 0.179540E+10 | 2606.50 | 26-JAN-14:09 | 19.40 | 13.37 |
February | 0.132773E+11 | 18206.91 | 28-FEB-17:00 | 23.90 | 12.94 | 0.171476E+10 | 2606.65 | 22-FEB-14:09 | 23.90 | 12.94 |
March | 0.197783E+11 | 21932.94 | 31-MAR-08:00 | 18.30 | 16.52 | 0.214094E+10 | 2606.71 | 08-MAR-10:09 | 18.30 | 16.52 |
April | 0.204235E+11 | 22497.11 | 18-APR-08:00 | 19.40 | 14.96 | 0.191059E+10 | 2606.62 | 17-APR-09:09 | 19.40 | 14.96 |
May | 0.249622E+11 | 34869.32 | 30-MAY-05:13 | 19.07 | 17.52 | 0.207635E+10 | 2606.73 | 11-MAY-09:00 | 19.07 | 17.52 |
June | 0.280545E+11 | 36072.92 | 26-JUN-05:13 | 23.30 | 21.67 | 0.207029E+10 | 2606.67 | 09-JUN-09:00 | 23.30 | 21.67 |
July | 0.280235E+11 | 46015.24 | 15-JUL-04:02 | 23.90 | 20.50 | 0.192442E+10 | 2606.54 | 03-JUL-09:09 | 23.90 | 20.50 |
August | 0.307688E+11 | 46030.61 | 10-AUG-04:02 | 23.98 | 22.68 | 0.215998E+10 | 2606.54 | 28-AUG-13:30 | 28.30 | 22.11 |
September | 0.259621E+11 | 36603.11 | 08-SEP-05:13 | 21.10 | 19.18 | 0.191805E+10 | 2606.65 | 15-SEP-09:00 | 23.90 | 16.09 |
October | 0.221458E+11 | 26692.08 | 19-OCT-05:13 | 20.73 | 20.73 | 0.198698E+10 | 2606.60 | 04-OCT-13:09 | 20.73 | 20.73 |
November | 0.179510E+11 | 20116.13 | 06-NOV-17:00 | 18.90 | 9.61 | 0.195632E+10 | 2606.76 | 16-NOV-10:09 | 10.68 | 10.03 |
December | 0.144875E+11 | 18735.47 | 13-DEC-08:10 | 16.78 | 15.73 | 0.185932E+10 | 2606.57 | 06-DEC-14:09 | 16.78 | 15.73 |
Annual Sum or Average | 0.258300E+12 | 0.235134E+11 | ||||||||
Minimum of Months | 0.124653E+11 | 12699.98 | 16.78 | 9.61 | 0.171476E+10 | 2606.50 | 10.68 | 10.03 | ||
Maximum of Months | 0.307688E+11 | 46030.61 | 23.98 | 22.68 | 0.215998E+10 | 2606.76 | 28.30 | 22.11 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154314E+09 | 1645.19 | 28-JAN-17:25 | 11.40 | 4.15 | 0.00 | 0.00 | 01-JAN-00:10 | 11.40 | 4.15 |
February | 0.545623E+09 | 3632.33 | 26-FEB-14:50 | 24.90 | 12.71 | 0.00 | 0.00 | 01-FEB-00:10 | 24.90 | 12.71 |
March | 0.166077E+10 | 7039.17 | 30-MAR-14:50 | 27.80 | 17.21 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 17.21 |
April | 0.289981E+10 | 7930.03 | 17-APR-15:10 | 28.90 | 16.41 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 16.41 |
May | 0.458556E+10 | 8824.50 | 30-MAY-15:00 | 30.60 | 21.44 | 0.00 | 0.00 | 01-MAY-00:10 | 30.60 | 21.44 |
June | 0.650776E+10 | 9519.04 | 27-JUN-14:40 | 32.20 | 23.14 | 0.00 | 0.00 | 01-JUN-00:10 | 32.20 | 23.14 |
July | 0.693140E+10 | 10593.76 | 07-JUL-15:20 | 35.20 | 23.90 | 0.00 | 0.00 | 01-JUL-00:10 | 35.20 | 23.90 |
August | 0.722823E+10 | 10712.64 | 01-AUG-14:00 | 33.90 | 23.66 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 23.66 |
September | 0.405359E+10 | 9206.78 | 06-SEP-14:20 | 30.53 | 23.42 | 0.00 | 0.00 | 01-SEP-00:10 | 30.53 | 23.42 |
October | 0.203814E+10 | 6962.27 | 10-OCT-14:40 | 29.07 | 20.78 | 0.00 | 0.00 | 01-OCT-00:10 | 29.07 | 20.78 |
November | 0.857288E+09 | 3514.58 | 05-NOV-14:53 | 23.90 | 18.46 | 0.00 | 0.00 | 01-NOV-00:10 | 23.90 | 18.46 |
December | 0.315647E+09 | 2150.05 | 12-DEC-14:40 | 22.80 | 16.47 | 0.00 | 0.00 | 01-DEC-00:10 | 22.80 | 16.47 |
Annual Sum or Average | 0.377781E+11 | 0.00 | ||||||||
Minimum of Months | 0.154314E+09 | 1645.19 | 11.40 | 4.15 | 0.00 | 0.00 | 11.40 | 4.15 | ||
Maximum of Months | 0.722823E+10 | 10712.64 | 35.20 | 23.90 | 0.00 | 0.00 | 35.20 | 23.90 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59849587.80 | 2060.16 | 14-JAN-05:02 | -6.2 | -7.4 | 0.00 | 0.00 | 01-JAN-00:10 | -6.2 | -7.4 |
February | 0.215918E+09 | 2322.37 | 03-FEB-05:01 | -7.9 | -9.5 | 0.00 | 0.00 | 01-FEB-00:10 | -7.9 | -9.5 |
March | 0.807919E+09 | 2336.67 | 30-MAR-16:00 | 27.80 | 17.47 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 17.47 |
April | 0.139623E+10 | 2873.87 | 06-APR-06:02 | 1.20 | -0.4 | 0.00 | 0.00 | 01-APR-00:10 | 1.20 | -0.4 |
May | 0.238163E+10 | 3683.53 | 30-MAY-15:30 | 29.20 | 21.54 | 0.00 | 0.00 | 01-MAY-00:10 | 29.20 | 21.54 |
June | 0.360329E+10 | 4123.16 | 26-JUN-15:30 | 30.00 | 23.57 | 0.00 | 0.00 | 01-JUN-00:10 | 30.00 | 23.57 |
July | 0.400203E+10 | 4529.37 | 10-JUL-15:50 | 32.70 | 22.31 | 0.00 | 0.00 | 01-JUL-00:10 | 32.70 | 22.31 |
August | 0.434443E+10 | 4513.56 | 02-AUG-16:00 | 35.00 | 23.13 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 23.13 |
September | 0.265194E+10 | 4140.61 | 07-SEP-16:00 | 31.70 | 23.71 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 23.71 |
October | 0.118070E+10 | 2766.46 | 11-OCT-16:00 | 26.10 | 17.12 | 0.00 | 0.00 | 01-OCT-00:10 | 26.10 | 17.12 |
November | 0.417030E+09 | 2043.28 | 07-NOV-07:03 | 5.68 | 2.52 | 0.00 | 0.00 | 01-NOV-00:10 | 5.68 | 2.52 |
December | 0.156134E+09 | 2367.50 | 09-DEC-06:11 | 2.20 | -1.0 | 0.00 | 0.00 | 01-DEC-00:10 | 2.20 | -1.0 |
Annual Sum or Average | 0.212171E+11 | 0.00 | ||||||||
Minimum of Months | 59849587.80 | 2043.28 | -7.9 | -9.5 | 0.00 | 0.00 | -7.9 | -9.5 | ||
Maximum of Months | 0.434443E+10 | 4529.37 | 35.00 | 23.71 | 0.00 | 0.00 | 35.00 | 23.71 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70814363.42 | 2073.52 | 13-JAN-06:11 | 3.90 | 2.25 | 0.00 | 0.00 | 01-JAN-00:10 | 3.90 | 2.25 |
February | 0.275631E+09 | 2492.01 | 23-FEB-07:03 | 5.00 | 3.70 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | 3.70 |
March | 0.109520E+10 | 2823.43 | 13-MAR-06:03 | 6.52 | 2.95 | 0.00 | 0.00 | 01-MAR-00:10 | 6.52 | 2.95 |
April | 0.172536E+10 | 3132.70 | 06-APR-06:02 | 1.20 | -0.4 | 0.00 | 0.00 | 01-APR-00:10 | 1.20 | -0.4 |
May | 0.268452E+10 | 3927.22 | 30-MAY-15:10 | 30.13 | 21.49 | 0.00 | 0.00 | 01-MAY-00:10 | 30.13 | 21.49 |
June | 0.395150E+10 | 4268.25 | 19-JUN-16:00 | 32.20 | 23.34 | 0.00 | 0.00 | 01-JUN-00:10 | 32.20 | 23.34 |
July | 0.434569E+10 | 4781.63 | 07-JUL-16:00 | 35.60 | 24.05 | 0.00 | 0.00 | 01-JUL-00:10 | 35.60 | 24.05 |
August | 0.486787E+10 | 4931.96 | 18-AUG-16:00 | 35.00 | 23.11 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 23.11 |
September | 0.327457E+10 | 4726.21 | 07-SEP-16:00 | 31.70 | 23.71 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 23.71 |
October | 0.165436E+10 | 3557.95 | 11-OCT-16:00 | 26.10 | 17.12 | 0.00 | 0.00 | 01-OCT-00:10 | 26.10 | 17.12 |
November | 0.619598E+09 | 2303.41 | 14-NOV-07:03 | 3.03 | 0.85 | 0.00 | 0.00 | 01-NOV-00:10 | 3.03 | 0.85 |
December | 0.220208E+09 | 2283.59 | 15-DEC-07:03 | 3.22 | 0.92 | 0.00 | 0.00 | 01-DEC-00:10 | 3.22 | 0.92 |
Annual Sum or Average | 0.247853E+11 | 0.00 | ||||||||
Minimum of Months | 70814363.42 | 2073.52 | 1.20 | -0.4 | 0.00 | 0.00 | 1.20 | -0.4 | ||
Maximum of Months | 0.486787E+10 | 4931.96 | 35.60 | 24.05 | 0.00 | 0.00 | 35.60 | 24.05 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.830941E+10 | 9111.62 | 20-JAN-17:00 | 16.70 | 11.48 | 0.153727E+10 | 2292.79 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.951332E+10 | 11031.88 | 28-FEB-17:00 | 23.90 | 12.94 | 0.149003E+10 | 2590.85 | 28-FEB-14:00 | 23.90 | 12.94 |
March | 0.140323E+11 | 14796.67 | 30-MAR-16:00 | 27.80 | 17.47 | 0.200603E+10 | 2606.60 | 13-MAR-13:00 | 27.80 | 17.47 |
April | 0.147350E+11 | 15679.44 | 18-APR-16:00 | 25.60 | 16.92 | 0.186171E+10 | 2606.60 | 17-APR-09:09 | 25.60 | 16.92 |
May | 0.182857E+11 | 18110.09 | 30-MAY-05:13 | 19.07 | 17.52 | 0.205823E+10 | 2606.68 | 11-MAY-09:00 | 19.07 | 17.52 |
June | 0.208486E+11 | 30540.38 | 26-JUN-05:13 | 23.30 | 21.67 | 0.206257E+10 | 2606.66 | 09-JUN-09:39 | 23.30 | 21.67 |
July | 0.213213E+11 | 33509.24 | 07-JUL-04:02 | 25.22 | 21.53 | 0.191802E+10 | 2606.56 | 03-JUL-09:09 | 25.22 | 21.53 |
August | 0.229710E+11 | 34132.06 | 03-AUG-04:02 | 23.90 | 22.21 | 0.215571E+10 | 2606.54 | 25-AUG-09:09 | 24.97 | 18.13 |
September | 0.184734E+11 | 22023.41 | 08-SEP-05:13 | 21.10 | 19.18 | 0.190452E+10 | 2606.61 | 25-SEP-09:09 | 24.78 | 19.25 |
October | 0.149614E+11 | 16222.42 | 11-OCT-16:00 | 26.10 | 17.12 | 0.190799E+10 | 2606.58 | 10-OCT-09:00 | 26.10 | 17.12 |
November | 0.120982E+11 | 11958.06 | 06-NOV-17:00 | 18.90 | 9.61 | 0.178096E+10 | 2606.52 | 03-NOV-13:00 | 18.90 | 9.61 |
December | 0.102156E+11 | 9979.06 | 13-DEC-17:00 | 16.70 | 16.70 | 0.157955E+10 | 2530.53 | 13-DEC-14:00 | 16.70 | 16.70 |
Annual Sum or Average | 0.185765E+12 | 0.222626E+11 | ||||||||
Minimum of Months | 0.830941E+10 | 9111.62 | 16.70 | 9.61 | 0.149003E+10 | 2292.79 | 16.70 | 9.61 | ||
Maximum of Months | 0.229710E+11 | 34132.06 | 27.80 | 22.21 | 0.215571E+10 | 2606.68 | 27.80 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.653767E+10 | 9343.23 | 20-JAN-17:00 | 16.70 | 11.48 | 0.148735E+10 | 2242.40 | 20-JAN-16:00 | 16.70 | 11.48 |
February | 0.809045E+10 | 11126.59 | 28-FEB-17:00 | 23.90 | 12.94 | 0.142076E+10 | 2548.06 | 28-FEB-14:00 | 23.90 | 12.94 |
March | 0.135160E+11 | 16855.37 | 30-MAR-16:00 | 27.80 | 17.47 | 0.190470E+10 | 2606.56 | 30-MAR-13:09 | 27.80 | 17.47 |
April | 0.148093E+11 | 17710.91 | 17-APR-16:00 | 28.90 | 16.41 | 0.180618E+10 | 2606.62 | 11-APR-13:09 | 28.90 | 16.41 |
May | 0.188269E+11 | 19987.36 | 30-MAY-15:40 | 28.73 | 21.54 | 0.203799E+10 | 2606.63 | 15-MAY-13:09 | 28.73 | 21.54 |
June | 0.219921E+11 | 30567.93 | 26-JUN-05:13 | 23.30 | 21.67 | 0.205661E+10 | 2606.65 | 06-JUN-09:09 | 23.30 | 21.67 |
July | 0.225730E+11 | 35925.05 | 07-JUL-04:02 | 25.22 | 21.53 | 0.191547E+10 | 2606.60 | 03-JUL-09:09 | 25.22 | 21.53 |
August | 0.241462E+11 | 35916.90 | 03-AUG-04:02 | 23.90 | 22.21 | 0.215329E+10 | 2606.62 | 25-AUG-09:50 | 27.23 | 18.71 |
September | 0.183395E+11 | 20269.67 | 07-SEP-16:00 | 31.70 | 23.71 | 0.188524E+10 | 2606.66 | 25-SEP-09:09 | 24.78 | 19.25 |
October | 0.140585E+11 | 17214.71 | 11-OCT-16:00 | 26.10 | 17.12 | 0.181880E+10 | 2606.57 | 11-OCT-09:00 | 26.10 | 17.12 |
November | 0.108653E+11 | 10655.50 | 06-NOV-17:00 | 18.90 | 9.61 | 0.164498E+10 | 2550.49 | 06-NOV-14:00 | 18.90 | 9.61 |
December | 0.804935E+10 | 10046.65 | 13-DEC-17:00 | 16.70 | 16.70 | 0.148645E+10 | 2447.27 | 13-DEC-14:00 | 16.70 | 16.70 |
Annual Sum or Average | 0.181804E+12 | 0.216178E+11 | ||||||||
Minimum of Months | 0.653767E+10 | 9343.23 | 16.70 | 9.61 | 0.142076E+10 | 2242.40 | 16.70 | 9.61 | ||
Maximum of Months | 0.241462E+11 | 35925.05 | 31.70 | 23.71 | 0.215329E+10 | 2606.66 | 28.90 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329391E+09 | 1897.20 | 31-JAN-17:00 | 19.40 | 13.37 | 0.307475E+09 | 463.43 | 31-JAN-14:00 | 19.40 | 13.37 |
February | 0.808377E+09 | 2517.03 | 28-FEB-15:40 | 23.87 | 12.92 | 0.288375E+09 | 549.47 | 28-FEB-14:00 | 23.87 | 12.92 |
March | 0.229574E+10 | 4806.79 | 30-MAR-15:50 | 27.80 | 17.41 | 0.378035E+09 | 549.47 | 29-MAR-13:00 | 27.80 | 17.41 |
April | 0.310136E+10 | 5150.49 | 19-APR-14:30 | 26.15 | 17.54 | 0.364974E+09 | 549.49 | 12-APR-13:50 | 26.15 | 17.54 |
May | 0.465814E+10 | 6633.83 | 30-MAY-15:00 | 30.60 | 21.44 | 0.423863E+09 | 549.49 | 15-MAY-13:09 | 30.60 | 21.44 |
June | 0.639744E+10 | 9431.44 | 25-JUN-16:22 | 33.05 | 22.20 | 0.433391E+09 | 549.49 | 02-JUN-13:09 | 33.05 | 22.20 |
July | 0.668584E+10 | 12495.76 | 16-JUL-13:43 | 33.62 | 23.40 | 0.404393E+09 | 549.48 | 03-JUL-09:09 | 33.62 | 23.40 |
August | 0.697725E+10 | 9343.10 | 06-AUG-14:43 | 31.88 | 23.78 | 0.454315E+09 | 549.48 | 25-AUG-09:50 | 27.23 | 18.71 |
September | 0.435990E+10 | 6513.16 | 06-SEP-14:30 | 30.25 | 23.24 | 0.392176E+09 | 549.49 | 25-SEP-09:20 | 25.17 | 19.30 |
October | 0.256314E+10 | 4438.63 | 02-OCT-14:40 | 26.70 | 20.10 | 0.361701E+09 | 549.47 | 19-OCT-13:39 | 23.33 | 19.60 |
November | 0.149262E+10 | 2208.60 | 05-NOV-16:33 | 22.93 | 17.72 | 0.324583E+09 | 529.95 | 03-NOV-13:00 | 22.93 | 17.72 |
December | 0.669269E+09 | 2039.16 | 13-DEC-15:00 | 18.30 | 16.86 | 0.300389E+09 | 501.18 | 13-DEC-14:00 | 18.30 | 16.86 |
Annual Sum or Average | 0.403385E+11 | 0.443367E+10 | ||||||||
Minimum of Months | 0.329391E+09 | 1897.20 | 18.30 | 12.92 | 0.288375E+09 | 463.43 | 18.30 | 12.92 | ||
Maximum of Months | 0.697725E+10 | 12495.76 | 33.62 | 23.78 | 0.454315E+09 | 549.49 | 33.62 | 23.40 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.393260E+09 | 1588.47 | 31-JAN-15:10 | 20.92 | 13.08 | 0.194577E+09 | 288.61 | 31-JAN-14:00 | 20.92 | 13.08 |
February | 0.848385E+09 | 2105.93 | 28-FEB-15:00 | 25.00 | 13.71 | 0.187501E+09 | 347.86 | 28-FEB-14:00 | 25.00 | 13.71 |
March | 0.214775E+10 | 3670.53 | 30-MAR-11:00 | 22.20 | 17.83 | 0.250328E+09 | 347.87 | 08-MAR-10:30 | 22.20 | 17.83 |
April | 0.306666E+10 | 5727.06 | 17-APR-10:20 | 23.73 | 15.75 | 0.241553E+09 | 347.88 | 12-APR-13:50 | 23.73 | 15.75 |
May | 0.438272E+10 | 11664.77 | 07-MAY-09:23 | 24.15 | 19.65 | 0.270790E+09 | 347.89 | 11-MAY-09:00 | 17.20 | 13.27 |
June | 0.560020E+10 | 11892.02 | 04-JUN-08:23 | 23.30 | 17.57 | 0.275011E+09 | 347.88 | 09-JUN-09:00 | 24.40 | 15.46 |
July | 0.588070E+10 | 11979.89 | 02-JUL-10:32 | 26.83 | 22.39 | 0.255726E+09 | 347.86 | 03-JUL-09:09 | 25.60 | 20.69 |
August | 0.599963E+10 | 11998.20 | 13-AUG-10:23 | 27.25 | 22.90 | 0.287443E+09 | 347.88 | 25-AUG-09:50 | 27.23 | 18.71 |
September | 0.407958E+10 | 10002.36 | 04-SEP-09:53 | 26.70 | 22.31 | 0.249059E+09 | 347.88 | 25-SEP-09:30 | 25.55 | 19.33 |
October | 0.239553E+10 | 4482.03 | 11-OCT-10:30 | 24.20 | 19.54 | 0.237910E+09 | 347.87 | 11-OCT-09:00 | 24.20 | 19.54 |
November | 0.141832E+10 | 1915.41 | 05-NOV-16:33 | 22.93 | 17.72 | 0.209259E+09 | 342.03 | 06-NOV-10:00 | 17.20 | 13.02 |
December | 0.725386E+09 | 1697.12 | 12-DEC-16:50 | 21.78 | 16.11 | 0.190678E+09 | 306.29 | 12-DEC-14:00 | 21.78 | 16.11 |
Annual Sum or Average | 0.369381E+11 | 0.284983E+10 | ||||||||
Minimum of Months | 0.393260E+09 | 1588.47 | 20.92 | 13.08 | 0.187501E+09 | 288.61 | 17.20 | 13.02 | ||
Maximum of Months | 0.599963E+10 | 11998.20 | 27.25 | 22.90 | 0.287443E+09 | 347.89 | 27.23 | 20.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130656E+10 | 4516.25 | 11-JAN-14:30 | 6.70 | 2.05 | 0.337512E+09 | 549.48 | 05-JAN-14:00 | 6.70 | 2.05 |
February | 0.186228E+10 | 12786.09 | 26-FEB-14:43 | 24.90 | 12.71 | 0.314763E+09 | 549.49 | 21-FEB-14:00 | 24.90 | 12.71 |
March | 0.362003E+10 | 9739.50 | 30-MAR-13:50 | 27.62 | 17.92 | 0.403448E+09 | 549.50 | 13-MAR-13:00 | 27.62 | 17.92 |
April | 0.422194E+10 | 8495.55 | 17-APR-14:00 | 28.90 | 16.63 | 0.374306E+09 | 549.53 | 12-APR-13:50 | 28.90 | 16.63 |
May | 0.534072E+10 | 7908.73 | 30-MAY-14:30 | 30.60 | 21.24 | 0.423004E+09 | 549.49 | 15-MAY-13:09 | 30.60 | 21.24 |
June | 0.664517E+10 | 11084.89 | 25-JUN-16:22 | 33.05 | 22.20 | 0.431952E+09 | 549.50 | 02-JUN-13:09 | 33.05 | 22.20 |
July | 0.705573E+10 | 14299.82 | 16-JUL-13:43 | 33.62 | 23.40 | 0.404013E+09 | 549.48 | 03-JUL-09:09 | 33.62 | 23.40 |
August | 0.818652E+10 | 14713.50 | 20-AUG-13:32 | 28.50 | 24.36 | 0.454365E+09 | 549.48 | 25-AUG-09:50 | 27.23 | 18.71 |
September | 0.608342E+10 | 15029.50 | 24-SEP-14:02 | 28.40 | 19.93 | 0.394259E+09 | 549.50 | 22-SEP-13:50 | 28.40 | 19.93 |
October | 0.463776E+10 | 15072.99 | 09-OCT-14:32 | 27.60 | 19.53 | 0.383925E+09 | 549.49 | 04-OCT-13:00 | 27.60 | 19.53 |
November | 0.297076E+10 | 14380.31 | 11-NOV-14:32 | 21.10 | 11.78 | 0.361815E+09 | 549.49 | 14-NOV-14:00 | 20.00 | 9.44 |
December | 0.191518E+10 | 6154.84 | 12-DEC-13:40 | 22.23 | 16.93 | 0.338734E+09 | 549.47 | 07-DEC-14:00 | 22.23 | 16.93 |
Annual Sum or Average | 0.538461E+11 | 0.462210E+10 | ||||||||
Minimum of Months | 0.130656E+10 | 4516.25 | 6.70 | 2.05 | 0.314763E+09 | 549.47 | 6.70 | 2.05 | ||
Maximum of Months | 0.818652E+10 | 15072.99 | 33.62 | 24.36 | 0.454365E+09 | 549.53 | 33.62 | 23.40 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.466303E+09 | 1861.46 | 20-JAN-16:40 | 16.87 | 11.91 | 0.195702E+09 | 298.00 | 20-JAN-16:49 | 16.78 | 11.69 |
February | 0.882366E+09 | 4203.90 | 27-FEB-17:00 | 22.20 | 11.44 | 0.183951E+09 | 346.46 | 28-FEB-14:00 | 25.00 | 13.71 |
March | 0.234816E+10 | 6468.03 | 30-MAR-16:00 | 27.80 | 17.47 | 0.237618E+09 | 347.83 | 30-MAR-13:09 | 27.80 | 17.47 |
April | 0.323438E+10 | 11470.75 | 09-APR-17:23 | 21.40 | 11.01 | 0.226197E+09 | 347.85 | 12-APR-13:00 | 28.90 | 17.10 |
May | 0.438128E+10 | 11359.79 | 21-MAY-18:23 | 24.75 | 19.04 | 0.261865E+09 | 347.84 | 15-MAY-13:09 | 24.75 | 19.04 |
June | 0.541881E+10 | 13438.02 | 25-JUN-16:22 | 33.05 | 22.20 | 0.271194E+09 | 347.85 | 02-JUN-09:00 | 33.05 | 22.20 |
July | 0.563163E+10 | 13711.13 | 23-JUL-18:32 | 28.50 | 21.82 | 0.254038E+09 | 347.84 | 03-JUL-09:09 | 28.50 | 21.82 |
August | 0.591733E+10 | 13717.34 | 13-AUG-17:02 | 31.10 | 22.35 | 0.286038E+09 | 347.84 | 25-AUG-09:00 | 27.80 | 18.82 |
September | 0.404533E+10 | 11421.12 | 04-SEP-16:33 | 28.13 | 22.40 | 0.243002E+09 | 347.84 | 19-SEP-13:09 | 24.90 | 16.60 |
October | 0.253127E+10 | 7620.53 | 08-OCT-16:12 | 27.03 | 18.83 | 0.226008E+09 | 347.83 | 16-OCT-13:00 | 25.00 | 19.11 |
November | 0.146050E+10 | 3783.25 | 06-NOV-16:00 | 20.60 | 10.48 | 0.207225E+09 | 347.80 | 06-NOV-14:00 | 20.60 | 10.48 |
December | 0.729629E+09 | 2002.06 | 11-DEC-16:00 | 21.10 | 15.91 | 0.192408E+09 | 321.49 | 12-DEC-14:00 | 22.80 | 16.17 |
Annual Sum or Average | 0.370470E+11 | 0.278525E+10 | ||||||||
Minimum of Months | 0.466303E+09 | 1861.46 | 16.87 | 10.48 | 0.183951E+09 | 298.00 | 16.78 | 10.48 | ||
Maximum of Months | 0.591733E+10 | 13717.34 | 33.05 | 22.40 | 0.286038E+09 | 347.85 | 33.05 | 22.20 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.341670E+09 | 1803.75 | 31-JAN-15:10 | 20.92 | 13.08 | 0.307950E+09 | 448.80 | 31-JAN-14:00 | 20.92 | 13.08 |
February | 0.829816E+09 | 2066.91 | 28-FEB-15:20 | 24.43 | 13.32 | 0.286256E+09 | 512.92 | 28-FEB-14:00 | 24.43 | 13.32 |
March | 0.218183E+10 | 2762.47 | 30-MAR-16:00 | 27.80 | 17.47 | 0.367997E+09 | 549.47 | 30-MAR-13:20 | 27.80 | 17.47 |
April | 0.253644E+10 | 3092.49 | 19-APR-14:30 | 26.15 | 17.54 | 0.351967E+09 | 549.47 | 20-APR-13:00 | 23.90 | 16.60 |
May | 0.351205E+10 | 4668.72 | 30-MAY-15:00 | 30.60 | 21.44 | 0.419422E+09 | 549.48 | 18-MAY-09:30 | 30.60 | 21.44 |
June | 0.522703E+10 | 5591.37 | 30-JUN-14:30 | 33.05 | 22.98 | 0.433794E+09 | 549.49 | 09-JUN-09:00 | 33.05 | 22.98 |
July | 0.576704E+10 | 6120.60 | 14-JUL-15:00 | 35.00 | 23.85 | 0.404477E+09 | 549.48 | 03-JUL-09:09 | 35.00 | 23.85 |
August | 0.634887E+10 | 6144.98 | 09-AUG-15:00 | 32.80 | 23.20 | 0.454633E+09 | 549.47 | 18-AUG-13:00 | 33.30 | 22.95 |
September | 0.438133E+10 | 5805.52 | 06-SEP-14:00 | 31.10 | 23.78 | 0.399819E+09 | 549.49 | 15-SEP-09:00 | 23.90 | 16.09 |
October | 0.304127E+10 | 4002.80 | 18-OCT-14:00 | 25.00 | 22.63 | 0.381869E+09 | 549.47 | 20-OCT-13:09 | 18.22 | 11.22 |
November | 0.217309E+10 | 2277.05 | 05-NOV-13:03 | 22.38 | 18.19 | 0.342999E+09 | 539.36 | 03-NOV-13:00 | 22.38 | 18.19 |
December | 0.106718E+10 | 2032.64 | 13-DEC-13:30 | 19.45 | 17.14 | 0.305245E+09 | 501.23 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.374076E+11 | 0.445643E+10 | ||||||||
Minimum of Months | 0.341670E+09 | 1803.75 | 19.45 | 13.08 | 0.286256E+09 | 448.80 | 18.22 | 11.22 | ||
Maximum of Months | 0.634887E+10 | 6144.98 | 35.00 | 23.85 | 0.454633E+09 | 549.49 | 35.00 | 23.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.441698E+09 | 1385.69 | 31-JAN-15:00 | 21.10 | 12.97 | 0.195824E+09 | 290.74 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.820203E+09 | 1752.40 | 27-FEB-10:40 | 14.27 | 6.32 | 0.188751E+09 | 347.86 | 28-FEB-10:00 | 20.60 | 11.95 |
March | 0.192468E+10 | 2556.30 | 14-MAR-11:00 | 20.60 | 15.46 | 0.250029E+09 | 347.87 | 08-MAR-10:00 | 20.60 | 15.46 |
April | 0.235902E+10 | 4304.22 | 17-APR-10:10 | 23.27 | 15.57 | 0.240178E+09 | 347.87 | 17-APR-09:09 | 23.27 | 15.57 |
May | 0.339717E+10 | 5387.24 | 30-MAY-10:00 | 27.80 | 21.16 | 0.271118E+09 | 347.89 | 11-MAY-09:00 | 27.80 | 21.16 |
June | 0.475837E+10 | 8031.09 | 11-JUN-10:02 | 25.28 | 14.81 | 0.275614E+09 | 347.88 | 09-JUN-09:00 | 25.28 | 14.81 |
July | 0.520586E+10 | 9059.35 | 09-JUL-10:22 | 28.85 | 23.10 | 0.256505E+09 | 347.86 | 17-JUL-09:00 | 27.80 | 22.02 |
August | 0.557577E+10 | 10882.78 | 27-AUG-09:52 | 27.20 | 21.81 | 0.288215E+09 | 347.86 | 18-AUG-13:00 | 27.20 | 21.81 |
September | 0.404356E+10 | 6426.75 | 08-SEP-09:30 | 26.65 | 22.11 | 0.253816E+09 | 347.88 | 15-SEP-09:00 | 23.90 | 16.09 |
October | 0.270909E+10 | 4421.43 | 11-OCT-10:30 | 24.20 | 19.54 | 0.249567E+09 | 347.87 | 04-OCT-13:00 | 24.20 | 19.54 |
November | 0.180693E+10 | 2299.40 | 06-NOV-10:20 | 15.33 | 12.73 | 0.227935E+09 | 347.86 | 06-NOV-10:09 | 15.33 | 12.73 |
December | 0.105900E+10 | 1525.85 | 13-DEC-12:00 | 20.00 | 17.41 | 0.197611E+09 | 316.27 | 13-DEC-14:09 | 18.30 | 16.86 |
Annual Sum or Average | 0.341014E+11 | 0.289516E+10 | ||||||||
Minimum of Months | 0.441698E+09 | 1385.69 | 14.27 | 6.32 | 0.188751E+09 | 290.74 | 15.33 | 11.95 | ||
Maximum of Months | 0.557577E+10 | 10882.78 | 28.85 | 23.10 | 0.288215E+09 | 347.89 | 27.80 | 22.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.827400E+09 | 2493.14 | 28-JAN-14:50 | 11.93 | 4.48 | 0.314228E+09 | 525.34 | 31-JAN-14:50 | 21.02 | 13.03 |
February | 0.131572E+10 | 6311.83 | 21-FEB-14:30 | 22.25 | 10.82 | 0.299636E+09 | 549.49 | 28-FEB-10:00 | 20.60 | 11.95 |
March | 0.269557E+10 | 7835.91 | 30-MAR-16:10 | 27.62 | 17.53 | 0.390442E+09 | 549.50 | 13-MAR-13:00 | 27.62 | 17.53 |
April | 0.305979E+10 | 7892.73 | 17-APR-16:10 | 28.80 | 16.45 | 0.361420E+09 | 549.51 | 12-APR-13:39 | 28.80 | 16.45 |
May | 0.411522E+10 | 9063.84 | 30-MAY-12:00 | 29.40 | 21.24 | 0.414352E+09 | 549.49 | 09-MAY-13:09 | 29.40 | 21.24 |
June | 0.620962E+10 | 10351.27 | 06-JUN-16:20 | 33.90 | 21.85 | 0.431003E+09 | 559.49 | 06-JUN-12:09 | 33.90 | 21.85 |
July | 0.690033E+10 | 10830.95 | 07-JUL-16:10 | 35.50 | 23.98 | 0.404085E+09 | 584.49 | 14-JUL-12:09 | 33.40 | 24.44 |
August | 0.850498E+10 | 12034.55 | 27-AUG-15:12 | 31.70 | 21.48 | 0.456105E+09 | 609.66 | 18-AUG-12:09 | 31.70 | 21.48 |
September | 0.631042E+10 | 10700.43 | 07-SEP-12:00 | 31.10 | 23.22 | 0.398886E+09 | 588.63 | 07-SEP-12:09 | 31.02 | 23.18 |
October | 0.461404E+10 | 12625.03 | 09-OCT-14:23 | 27.50 | 19.51 | 0.392231E+09 | 573.39 | 10-OCT-13:00 | 29.40 | 21.05 |
November | 0.295825E+10 | 12006.86 | 12-NOV-14:53 | 20.00 | 10.89 | 0.369790E+09 | 549.49 | 14-NOV-14:00 | 20.00 | 9.44 |
December | 0.179248E+10 | 5787.16 | 12-DEC-14:00 | 22.80 | 17.07 | 0.331625E+09 | 549.49 | 05-DEC-14:09 | 22.80 | 17.07 |
Annual Sum or Average | 0.493038E+11 | 0.456380E+10 | ||||||||
Minimum of Months | 0.827400E+09 | 2493.14 | 11.93 | 4.48 | 0.299636E+09 | 525.34 | 20.00 | 9.44 | ||
Maximum of Months | 0.850498E+10 | 12625.03 | 35.50 | 23.98 | 0.456105E+09 | 609.66 | 33.90 | 24.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.444222E+09 | 1496.23 | 20-JAN-16:40 | 16.87 | 11.91 | 0.196543E+09 | 294.50 | 20-JAN-16:49 | 16.78 | 11.69 |
February | 0.803196E+09 | 3006.42 | 27-FEB-17:00 | 22.20 | 11.44 | 0.184620E+09 | 340.90 | 28-FEB-14:00 | 25.00 | 13.71 |
March | 0.201042E+10 | 4353.03 | 30-MAR-16:00 | 27.80 | 17.47 | 0.240242E+09 | 347.83 | 30-MAR-13:20 | 27.80 | 17.47 |
April | 0.239169E+10 | 4916.64 | 17-APR-16:00 | 28.90 | 16.41 | 0.227673E+09 | 347.83 | 20-APR-13:00 | 23.90 | 16.60 |
May | 0.324485E+10 | 6154.94 | 06-MAY-17:42 | 27.30 | 19.67 | 0.265558E+09 | 347.84 | 22-MAY-09:30 | 21.70 | 19.13 |
June | 0.448367E+10 | 11001.06 | 04-JUN-16:32 | 31.50 | 19.59 | 0.274414E+09 | 347.85 | 09-JUN-09:00 | 24.40 | 15.46 |
July | 0.485660E+10 | 10919.89 | 09-JUL-17:02 | 33.22 | 22.71 | 0.256095E+09 | 347.84 | 03-JUL-09:09 | 33.22 | 22.71 |
August | 0.541484E+10 | 10948.91 | 06-AUG-16:31 | 32.40 | 23.43 | 0.288109E+09 | 347.83 | 10-AUG-13:00 | 30.60 | 23.74 |
September | 0.387790E+10 | 8473.05 | 04-SEP-16:23 | 28.05 | 22.55 | 0.253127E+09 | 347.85 | 15-SEP-09:00 | 23.90 | 16.09 |
October | 0.270503E+10 | 7894.83 | 09-OCT-16:23 | 27.25 | 19.48 | 0.244270E+09 | 347.84 | 04-OCT-13:00 | 27.25 | 19.48 |
November | 0.185177E+10 | 3726.03 | 06-NOV-16:30 | 19.75 | 10.05 | 0.222607E+09 | 347.82 | 15-NOV-14:00 | 21.70 | 11.58 |
December | 0.986835E+09 | 1672.58 | 11-DEC-16:20 | 20.93 | 15.86 | 0.197364E+09 | 330.43 | 12-DEC-14:50 | 22.80 | 16.32 |
Annual Sum or Average | 0.330710E+11 | 0.285062E+10 | ||||||||
Minimum of Months | 0.444222E+09 | 1496.23 | 16.87 | 10.05 | 0.184620E+09 | 294.50 | 16.78 | 11.58 | ||
Maximum of Months | 0.541484E+10 | 11001.06 | 33.22 | 23.43 | 0.288109E+09 | 347.85 | 33.22 | 23.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.429142E+09 | 1852.25 | 31-JAN-17:00 | 19.40 | 13.37 | 0.309178E+09 | 472.78 | 31-JAN-14:00 | 19.40 | 13.37 |
February | 0.100227E+10 | 2500.81 | 28-FEB-15:30 | 24.15 | 13.12 | 0.292478E+09 | 549.47 | 28-FEB-14:39 | 24.15 | 13.12 |
March | 0.255253E+10 | 4281.02 | 30-MAR-16:00 | 27.80 | 17.47 | 0.390369E+09 | 549.47 | 29-MAR-13:00 | 27.80 | 17.47 |
April | 0.309099E+10 | 4683.62 | 18-APR-14:00 | 27.20 | 15.86 | 0.374937E+09 | 549.48 | 19-APR-09:09 | 19.78 | 15.80 |
May | 0.444587E+10 | 6002.17 | 30-MAY-15:00 | 30.60 | 21.44 | 0.429813E+09 | 549.49 | 24-MAY-09:09 | 30.60 | 21.44 |
June | 0.603206E+10 | 6415.58 | 30-JUN-14:30 | 33.05 | 22.98 | 0.434957E+09 | 549.50 | 09-JUN-09:39 | 33.05 | 22.98 |
July | 0.628561E+10 | 9461.74 | 16-JUL-13:43 | 33.62 | 23.40 | 0.404984E+09 | 549.47 | 03-JUL-09:09 | 33.62 | 23.40 |
August | 0.661434E+10 | 7297.69 | 14-AUG-04:02 | 24.22 | 20.90 | 0.454871E+09 | 549.47 | 18-AUG-13:00 | 33.30 | 22.95 |
September | 0.431606E+10 | 5943.80 | 06-SEP-14:30 | 30.25 | 23.24 | 0.398104E+09 | 549.49 | 25-SEP-09:09 | 24.78 | 19.25 |
October | 0.286686E+10 | 4125.54 | 02-OCT-14:40 | 26.70 | 20.10 | 0.375711E+09 | 549.47 | 05-OCT-13:09 | 20.00 | 14.95 |
November | 0.190590E+10 | 2139.71 | 03-NOV-15:20 | 21.50 | 17.22 | 0.337815E+09 | 546.29 | 03-NOV-13:00 | 21.50 | 17.22 |
December | 0.953722E+09 | 2016.92 | 13-DEC-13:30 | 19.45 | 17.14 | 0.305510E+09 | 516.09 | 13-DEC-14:00 | 18.30 | 16.86 |
Annual Sum or Average | 0.404954E+11 | 0.450873E+10 | ||||||||
Minimum of Months | 0.429142E+09 | 1852.25 | 19.40 | 13.12 | 0.292478E+09 | 472.78 | 18.30 | 13.12 | ||
Maximum of Months | 0.661434E+10 | 9461.74 | 33.62 | 23.40 | 0.454871E+09 | 549.50 | 33.62 | 23.40 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.487662E+09 | 1545.68 | 31-JAN-16:30 | 19.70 | 13.48 | 0.144107E+09 | 284.06 | 31-JAN-15:39 | 19.70 | 13.48 |
February | 0.962560E+09 | 2532.38 | 27-FEB-10:00 | 12.80 | 5.65 | 0.139656E+09 | 338.72 | 28-FEB-11:09 | 20.87 | 12.02 |
March | 0.230559E+10 | 3685.74 | 30-MAR-11:00 | 22.20 | 17.83 | 0.187080E+09 | 338.72 | 08-MAR-09:50 | 22.20 | 17.83 |
April | 0.304265E+10 | 6493.23 | 16-APR-10:53 | 26.10 | 15.47 | 0.179605E+09 | 338.74 | 18-APR-14:30 | 26.40 | 16.44 |
May | 0.417461E+10 | 11578.45 | 07-MAY-09:13 | 23.87 | 19.51 | 0.200880E+09 | 338.74 | 11-MAY-10:09 | 17.67 | 13.57 |
June | 0.524501E+10 | 11517.78 | 11-JUN-09:53 | 25.00 | 14.66 | 0.203290E+09 | 338.73 | 05-JUN-07:30 | 25.00 | 14.66 |
July | 0.549367E+10 | 12076.45 | 04-JUL-09:52 | 27.20 | 23.54 | 0.189744E+09 | 338.73 | 03-JUL-07:40 | 27.20 | 23.54 |
August | 0.564001E+10 | 12412.39 | 27-AUG-09:52 | 27.20 | 21.81 | 0.212440E+09 | 338.72 | 14-AUG-07:19 | 27.20 | 21.81 |
September | 0.397162E+10 | 10843.34 | 04-SEP-09:23 | 25.85 | 21.92 | 0.185397E+09 | 338.74 | 11-SEP-07:30 | 20.85 | 19.50 |
October | 0.260749E+10 | 4662.83 | 11-OCT-10:20 | 23.73 | 19.29 | 0.178297E+09 | 338.72 | 10-OCT-10:09 | 23.73 | 19.29 |
November | 0.170177E+10 | 2470.17 | 06-NOV-10:00 | 14.40 | 12.50 | 0.159374E+09 | 338.70 | 06-NOV-09:39 | 14.40 | 12.50 |
December | 0.939290E+09 | 1672.45 | 13-DEC-13:30 | 19.45 | 17.14 | 0.142824E+09 | 305.40 | 13-DEC-13:39 | 19.07 | 17.05 |
Annual Sum or Average | 0.365719E+11 | 0.212269E+10 | ||||||||
Minimum of Months | 0.487662E+09 | 1545.68 | 12.80 | 5.65 | 0.139656E+09 | 284.06 | 14.40 | 12.02 | ||
Maximum of Months | 0.564001E+10 | 12412.39 | 27.20 | 23.54 | 0.212440E+09 | 338.74 | 27.20 | 23.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145561E+10 | 4616.73 | 11-JAN-14:10 | 6.70 | 2.05 | 0.344856E+09 | 549.48 | 05-JAN-14:00 | 6.70 | 2.05 |
February | 0.205246E+10 | 8400.35 | 21-FEB-14:30 | 22.25 | 10.82 | 0.322010E+09 | 549.50 | 28-FEB-14:09 | 25.00 | 13.72 |
March | 0.380260E+10 | 9148.07 | 30-MAR-13:40 | 27.43 | 17.97 | 0.416806E+09 | 549.50 | 13-MAR-13:00 | 27.43 | 17.97 |
April | 0.411991E+10 | 7825.34 | 17-APR-13:50 | 28.72 | 16.68 | 0.384226E+09 | 549.49 | 11-APR-13:09 | 28.72 | 16.68 |
May | 0.503808E+10 | 7222.34 | 30-MAY-14:20 | 30.60 | 21.17 | 0.429932E+09 | 549.49 | 24-MAY-09:09 | 30.60 | 21.17 |
June | 0.621043E+10 | 7196.69 | 30-JUN-14:00 | 32.80 | 23.21 | 0.434380E+09 | 549.50 | 09-JUN-09:39 | 32.80 | 23.21 |
July | 0.658069E+10 | 11122.11 | 16-JUL-13:43 | 33.62 | 23.40 | 0.405051E+09 | 549.47 | 03-JUL-09:09 | 33.62 | 23.40 |
August | 0.772956E+10 | 13084.05 | 13-AUG-13:32 | 30.40 | 22.46 | 0.455218E+09 | 549.47 | 25-AUG-13:00 | 31.10 | 18.60 |
September | 0.594192E+10 | 9927.53 | 17-SEP-14:43 | 28.12 | 22.39 | 0.399778E+09 | 549.50 | 22-SEP-13:39 | 26.50 | 17.31 |
October | 0.494938E+10 | 13476.58 | 09-OCT-14:23 | 27.50 | 19.51 | 0.395193E+09 | 551.93 | 10-OCT-13:50 | 29.22 | 21.00 |
November | 0.340335E+10 | 10673.16 | 12-NOV-13:43 | 18.72 | 10.43 | 0.376770E+09 | 549.49 | 14-NOV-14:00 | 20.00 | 9.44 |
December | 0.229767E+10 | 6636.01 | 08-DEC-14:00 | 12.80 | 5.54 | 0.349614E+09 | 549.47 | 07-DEC-14:00 | 12.80 | 5.54 |
Annual Sum or Average | 0.535816E+11 | 0.471383E+10 | ||||||||
Minimum of Months | 0.145561E+10 | 4616.73 | 6.70 | 2.05 | 0.322010E+09 | 549.47 | 6.70 | 2.05 | ||
Maximum of Months | 0.772956E+10 | 13476.58 | 33.62 | 23.40 | 0.455218E+09 | 551.93 | 33.62 | 23.40 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.544528E+09 | 1735.77 | 20-JAN-16:40 | 16.87 | 11.91 | 0.197393E+09 | 304.50 | 20-JAN-16:49 | 16.78 | 11.69 |
February | 0.101184E+10 | 4061.09 | 27-FEB-17:00 | 22.20 | 11.44 | 0.186398E+09 | 347.81 | 28-FEB-14:00 | 25.00 | 13.71 |
March | 0.250555E+10 | 6065.38 | 30-MAR-16:00 | 27.80 | 17.47 | 0.244818E+09 | 347.83 | 29-MAR-13:00 | 27.80 | 17.47 |
April | 0.315064E+10 | 10665.75 | 09-APR-17:12 | 21.50 | 10.93 | 0.233251E+09 | 347.84 | 20-APR-13:00 | 23.90 | 16.60 |
May | 0.411610E+10 | 10093.51 | 21-MAY-18:23 | 24.75 | 19.04 | 0.267773E+09 | 347.85 | 17-MAY-09:00 | 24.75 | 19.04 |
June | 0.506881E+10 | 12669.74 | 04-JUN-16:42 | 31.60 | 19.67 | 0.273710E+09 | 347.85 | 02-JUN-13:09 | 31.60 | 19.67 |
July | 0.525071E+10 | 12924.90 | 04-JUL-17:52 | 30.60 | 22.43 | 0.255561E+09 | 347.84 | 03-JUL-09:09 | 30.60 | 22.43 |
August | 0.557120E+10 | 12709.90 | 13-AUG-16:51 | 31.10 | 22.45 | 0.287382E+09 | 347.83 | 25-AUG-09:09 | 24.97 | 18.13 |
September | 0.389581E+10 | 10669.39 | 04-SEP-16:12 | 27.97 | 22.70 | 0.249025E+09 | 347.84 | 13-SEP-13:09 | 23.92 | 15.70 |
October | 0.272404E+10 | 8558.16 | 09-OCT-16:23 | 27.25 | 19.48 | 0.234501E+09 | 347.83 | 19-OCT-13:09 | 22.48 | 19.30 |
November | 0.176393E+10 | 3913.98 | 06-NOV-16:00 | 20.60 | 10.48 | 0.214164E+09 | 347.82 | 07-NOV-14:00 | 18.90 | 8.70 |
December | 0.937711E+09 | 1884.57 | 11-DEC-15:50 | 21.10 | 15.67 | 0.195916E+09 | 330.54 | 11-DEC-15:00 | 21.10 | 15.91 |
Annual Sum or Average | 0.365409E+11 | 0.283989E+10 | ||||||||
Minimum of Months | 0.544528E+09 | 1735.77 | 16.87 | 10.48 | 0.186398E+09 | 304.50 | 16.78 | 8.70 | ||
Maximum of Months | 0.557120E+10 | 12924.90 | 31.60 | 22.70 | 0.287382E+09 | 347.85 | 31.60 | 22.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33997141.37 | 17979.75 | 02-JAN-06:13 | 3.30 |
February | 4194854.72 | 16031.65 | 14-FEB-07:01 | 1.02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 38191996.08 | |||
Minimum of Months | 0.00 | 0.00 | 1.02 | |
Maximum of Months | 33997141.37 | 17979.75 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.425254E+10 | 13532.20 | 09-JAN-06:12 | -2.6 |
February | 0.266569E+10 | 14839.80 | 13-FEB-06:12 | -5.6 |
March | 0.810321E+09 | 5725.26 | 18-MAR-06:03 | 2.70 |
April | 0.428709E+09 | 6041.95 | 06-APR-05:02 | 0.18 |
May | 0.128272E+09 | 3786.08 | 10-MAY-05:03 | 8.98 |
June | 56827414.13 | 3350.31 | 08-JUN-05:03 | 11.70 |
July | 18960276.19 | 3492.73 | 07-JUL-04:02 | 25.22 |
August | 18302414.19 | 4074.41 | 14-AUG-04:02 | 24.22 |
September | 0.104087E+09 | 3215.71 | 29-SEP-05:03 | 12.30 |
October | 0.619312E+09 | 6202.40 | 26-OCT-06:03 | 2.20 |
November | 0.120151E+10 | 10290.11 | 22-NOV-07:02 | -3.2 |
December | 0.251303E+10 | 14100.90 | 18-DEC-06:13 | -5.0 |
Annual Sum or Average | 0.128175E+11 | |||
Minimum of Months | 18302414.19 | 3215.71 | -5.6 | |
Maximum of Months | 0.425254E+10 | 14839.80 | 25.22 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189068E+10 | 8537.31 | 09-JAN-07:11 | -3.3 |
February | 0.100936E+10 | 7994.01 | 13-FEB-07:11 | -5.6 |
March | 0.173854E+09 | 2763.94 | 26-MAR-14:13 | 19.27 |
April | 40066411.25 | 2198.23 | 09-APR-15:20 | 21.70 |
May | 9568503.55 | 1819.56 | 14-MAY-16:30 | 25.60 |
June | 7784073.14 | 1568.71 | 11-JUN-09:13 | 23.87 |
July | 10469962.27 | 2018.68 | 30-JUL-10:53 | 27.20 |
August | 9434997.59 | 1871.94 | 27-AUG-15:12 | 31.70 |
September | 9300977.03 | 2147.38 | 03-SEP-12:23 | 27.50 |
October | 0.121197E+09 | 2692.81 | 22-OCT-11:32 | 21.67 |
November | 0.367508E+09 | 3294.14 | 11-NOV-11:23 | 18.05 |
December | 0.988741E+09 | 5168.50 | 26-DEC-07:03 | 3.30 |
Annual Sum or Average | 0.463797E+10 | |||
Minimum of Months | 7784073.14 | 1568.71 | -5.6 | |
Maximum of Months | 0.189068E+10 | 8537.31 | 31.70 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142219E+10 | 5909.91 | 02-JAN-07:03 | 3.30 |
February | 0.757380E+09 | 4360.30 | 13-FEB-08:19 | -4.8 |
March | 80022290.34 | 1520.91 | 07-MAR-08:08 | 5.18 |
April | 11572168.31 | 1888.95 | 07-APR-07:06 | 3.53 |
May | 6520730.72 | 1978.07 | 29-MAY-14:12 | 28.67 |
June | 7991836.14 | 1524.30 | 18-JUN-13:00 | 28.30 |
July | 9199886.73 | 2971.24 | 07-JUL-04:02 | 25.22 |
August | 10332743.76 | 3195.92 | 04-AUG-04:02 | 23.90 |
September | 12937626.08 | 2128.11 | 03-SEP-12:25 | 27.50 |
October | 66916886.78 | 2750.94 | 22-OCT-11:32 | 21.67 |
November | 0.184204E+09 | 2550.54 | 12-NOV-11:33 | 15.77 |
December | 0.688688E+09 | 2815.66 | 18-DEC-08:10 | -5.0 |
Annual Sum or Average | 0.325795E+10 | |||
Minimum of Months | 6520730.72 | 1520.91 | -5.0 | |
Maximum of Months | 0.142219E+10 | 5909.91 | 28.67 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.440762E+09 | 18575.61 | 09-JAN-05:11 | -2.2 |
February | 0.158298E+09 | 17578.35 | 13-FEB-06:16 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 3572422.86 | 15896.40 | 22-NOV-07:01 | -3.2 |
December | 87974097.61 | 17157.08 | 20-DEC-07:03 | 2.88 |
Annual Sum or Average | 0.690607E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 0.440762E+09 | 18575.61 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190501E+10 | 32901.33 | 09-JAN-05:11 | -2.2 |
February | 0.853302E+09 | 32815.18 | 13-FEB-05:01 | -5.1 |
March | 36051026.41 | 26139.98 | 20-MAR-06:03 | 5.00 |
April | 5280611.68 | 25932.61 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 17326632.49 | 26073.69 | 26-OCT-06:03 | 2.20 |
November | 0.121433E+09 | 28535.91 | 22-NOV-06:01 | -3.3 |
December | 0.748797E+09 | 31354.34 | 04-DEC-05:01 | -2.8 |
Annual Sum or Average | 0.368720E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.190501E+10 | 32901.33 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372939E+10 | 11323.83 | 09-JAN-04:33 | -2.0 |
February | 0.210005E+10 | 11664.34 | 12-FEB-08:42 | -10.9 |
March | 0.245056E+09 | 9713.30 | 18-MAR-05:11 | 3.13 |
April | 65469877.10 | 9492.26 | 06-APR-05:02 | 0.18 |
May | 1041327.44 | 4521.77 | 11-MAY-06:03 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.101584E+09 | 9800.08 | 26-OCT-05:11 | 2.20 |
November | 0.572871E+09 | 10615.42 | 22-NOV-05:01 | -2.9 |
December | 0.184082E+10 | 11128.44 | 18-DEC-05:11 | -5.0 |
Annual Sum or Average | 0.865628E+10 | |||
Minimum of Months | 0.00 | 0.00 | -10.9 | |
Maximum of Months | 0.372939E+10 | 11664.34 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201177E+10 | 10512.44 | 09-JAN-05:11 | -2.2 |
February | 0.108745E+10 | 10789.61 | 12-FEB-04:42 | -11.7 |
March | 0.119343E+09 | 9076.74 | 18-MAR-05:11 | 3.13 |
April | 31298352.71 | 8805.61 | 06-APR-05:02 | 0.18 |
May | 747720.34 | 2595.53 | 11-MAY-06:03 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 305406.28 | 1527.03 | 29-SEP-06:03 | 12.88 |
October | 64192586.42 | 9150.52 | 26-OCT-05:11 | 2.20 |
November | 0.268158E+09 | 9836.15 | 22-NOV-05:01 | -2.9 |
December | 0.895078E+09 | 10335.56 | 18-DEC-05:11 | -5.0 |
Annual Sum or Average | 0.447835E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.7 | |
Maximum of Months | 0.201177E+10 | 10789.61 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241354E+10 | 12931.59 | 09-JAN-05:11 | -2.2 |
February | 0.135851E+10 | 13271.57 | 12-FEB-04:42 | -11.7 |
March | 0.174399E+09 | 11040.93 | 23-MAR-05:11 | 6.10 |
April | 57540540.34 | 10778.82 | 06-APR-05:02 | 0.18 |
May | 1395393.43 | 6161.12 | 11-MAY-06:03 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 5154.42 | 25.77 | 29-SEP-06:03 | 12.88 |
October | 78167966.34 | 11039.39 | 26-OCT-05:11 | 2.20 |
November | 0.328450E+09 | 11899.56 | 22-NOV-05:01 | -2.9 |
December | 0.103169E+10 | 12636.29 | 18-DEC-05:11 | -5.0 |
Annual Sum or Average | 0.544370E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.7 | |
Maximum of Months | 0.241354E+10 | 13271.57 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221225E+10 | 10806.66 | 09-JAN-05:11 | -2.2 |
February | 0.123691E+10 | 11134.74 | 12-FEB-08:42 | -10.9 |
March | 0.148453E+09 | 9135.08 | 18-MAR-05:11 | 3.13 |
April | 41087411.50 | 8855.24 | 06-APR-05:02 | 0.18 |
May | 1306179.95 | 4657.42 | 11-MAY-06:03 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 433656.27 | 2168.28 | 29-SEP-06:03 | 12.88 |
October | 66880941.18 | 9193.16 | 26-OCT-05:11 | 2.20 |
November | 0.354750E+09 | 10078.79 | 22-NOV-05:01 | -2.9 |
December | 0.109522E+10 | 10648.65 | 18-DEC-05:11 | -5.0 |
Annual Sum or Average | 0.515728E+10 | |||
Minimum of Months | 0.00 | 0.00 | -10.9 | |
Maximum of Months | 0.221225E+10 | 11134.74 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213044E+10 | 8965.94 | 09-JAN-05:01 | -2.2 |
February | 0.108773E+10 | 8824.48 | 13-FEB-05:01 | -5.1 |
March | 79994035.60 | 7549.51 | 20-MAR-05:11 | 5.00 |
April | 20976015.28 | 7189.90 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 4061835.55 | 7084.79 | 26-OCT-06:03 | 2.20 |
November | 54291794.64 | 7613.44 | 22-NOV-06:01 | -3.3 |
December | 0.475264E+09 | 8182.71 | 18-DEC-05:01 | -5.0 |
Annual Sum or Average | 0.385276E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.213044E+10 | 8965.94 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107111E+10 | 7906.92 | 09-JAN-05:01 | -2.2 |
February | 0.482693E+09 | 7777.81 | 13-FEB-05:01 | -5.1 |
March | 31428154.18 | 6600.18 | 18-MAR-05:11 | 3.13 |
April | 6736316.91 | 6142.42 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 2971301.01 | 5066.55 | 26-OCT-06:03 | 2.20 |
November | 15807539.48 | 6468.43 | 22-NOV-06:01 | -3.3 |
December | 0.185215E+09 | 7046.91 | 04-DEC-06:01 | -2.9 |
Annual Sum or Average | 0.179596E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.107111E+10 | 7906.92 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.337206E+10 | 11139.75 | 09-JAN-08:00 | -3.3 |
February | 0.204106E+10 | 11369.72 | 03-FEB-07:10 | -8.9 |
March | 0.804221E+09 | 9197.35 | 06-MAR-07:50 | 2.80 |
April | 0.447136E+09 | 9626.17 | 06-APR-06:10 | 1.20 |
May | 0.106191E+09 | 8425.15 | 11-MAY-06:03 | 8.17 |
June | 12391656.13 | 5758.80 | 08-JUN-06:07 | 12.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 12481317.73 | 4291.83 | 29-SEP-06:07 | 12.88 |
October | 0.389484E+09 | 9193.25 | 26-OCT-07:00 | 2.20 |
November | 0.793838E+09 | 10168.49 | 22-NOV-07:10 | -3.2 |
December | 0.132504E+10 | 10693.25 | 18-DEC-07:10 | -5.1 |
Annual Sum or Average | 0.930390E+10 | |||
Minimum of Months | 0.00 | 0.00 | -8.9 | |
Maximum of Months | 0.337206E+10 | 11369.72 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113870E+10 | 7974.59 | 09-JAN-05:01 | -2.2 |
February | 0.543303E+09 | 7824.67 | 13-FEB-05:01 | -5.1 |
March | 31740862.20 | 6705.39 | 23-MAR-05:11 | 6.10 |
April | 7405365.47 | 6289.61 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 2304337.70 | 4825.86 | 31-OCT-06:03 | 8.22 |
November | 24941950.89 | 6517.54 | 22-NOV-06:01 | -3.3 |
December | 0.228124E+09 | 7052.81 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.197652E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.113870E+10 | 7974.59 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206449E+10 | 9703.96 | 09-JAN-05:11 | -2.2 |
February | 0.103579E+10 | 9865.67 | 13-FEB-04:12 | -5.0 |
March | 51040741.63 | 7974.97 | 22-MAR-05:11 | 5.93 |
April | 10157660.23 | 7680.85 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 14253706.37 | 7956.85 | 26-OCT-05:11 | 2.20 |
November | 0.154177E+09 | 8652.51 | 22-NOV-06:01 | -3.3 |
December | 0.723964E+09 | 9326.00 | 18-DEC-05:01 | -5.0 |
Annual Sum or Average | 0.405388E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.206449E+10 | 9865.67 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114510E+10 | 8382.74 | 09-JAN-05:11 | -2.2 |
February | 0.539304E+09 | 8513.61 | 13-FEB-04:12 | -5.0 |
March | 30679665.13 | 6948.94 | 23-MAR-05:11 | 6.10 |
April | 6112003.55 | 6598.50 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 12123176.00 | 6784.92 | 26-OCT-05:11 | 2.20 |
November | 71469562.47 | 7266.59 | 22-NOV-06:01 | -3.3 |
December | 0.342232E+09 | 7928.45 | 18-DEC-05:01 | -5.0 |
Annual Sum or Average | 0.214702E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.114510E+10 | 8513.61 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123257E+10 | 11299.54 | 09-JAN-05:11 | -2.2 |
February | 0.580871E+09 | 11134.23 | 12-FEB-06:32 | -12.6 |
March | 32648095.92 | 8800.99 | 18-MAR-06:03 | 2.70 |
April | 8397339.84 | 8942.79 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 11299730.42 | 8719.75 | 26-OCT-06:03 | 2.20 |
November | 73129770.41 | 9865.61 | 22-NOV-06:01 | -3.3 |
December | 0.361105E+09 | 10674.76 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.230002E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.6 | |
Maximum of Months | 0.123257E+10 | 11299.54 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120840E+10 | 8443.35 | 09-JAN-05:11 | -2.2 |
February | 0.590891E+09 | 8609.29 | 12-FEB-07:12 | -12.6 |
March | 33313265.34 | 7002.24 | 22-MAR-05:11 | 5.93 |
April | 7251196.11 | 6653.00 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 11578931.26 | 5700.01 | 26-OCT-06:03 | 2.20 |
November | 97720524.51 | 7290.07 | 22-NOV-06:01 | -3.3 |
December | 0.424873E+09 | 7932.59 | 18-DEC-05:01 | -5.0 |
Annual Sum or Average | 0.237402E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.6 | |
Maximum of Months | 0.120840E+10 | 8609.29 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103111E+10 | 1592.13 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.929764E+09 | 1592.13 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.972187E+09 | 1592.13 | 16-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.828854E+09 | 1388.60 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.857826E+09 | 1111.04 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.841344E+09 | 907.52 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.801261E+09 | 1111.04 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.910311E+09 | 1388.60 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.861875E+09 | 1592.13 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.986464E+09 | 1592.13 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.989356E+09 | 1592.13 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.100826E+10 | 1592.13 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.110186E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.801261E+09 | 907.52 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.103111E+10 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620557E+09 | 1007.95 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.562270E+09 | 1007.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.601362E+09 | 1007.95 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.521657E+09 | 879.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.548101E+09 | 527.66 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.538692E+09 | 527.66 | 23-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.510968E+09 | 703.38 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.576955E+09 | 879.10 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.535748E+09 | 879.10 | 05-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.592241E+09 | 1007.95 | 19-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.603931E+09 | 1007.95 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.604162E+09 | 1007.95 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.681665E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.510968E+09 | 527.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.620557E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.937008E+09 | 1592.13 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.862302E+09 | 1592.13 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.949971E+09 | 1592.13 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.831012E+09 | 1388.60 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.872507E+09 | 1111.04 | 02-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.857548E+09 | 1111.04 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.815829E+09 | 1111.04 | 19-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.916366E+09 | 1388.60 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.848919E+09 | 1592.13 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.919213E+09 | 1592.13 | 19-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.914812E+09 | 1592.13 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.910332E+09 | 1592.13 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.106358E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.815829E+09 | 1111.04 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.949971E+09 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620283E+09 | 1007.89 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.571192E+09 | 1007.89 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.614070E+09 | 1007.89 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.528958E+09 | 1007.89 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.553426E+09 | 879.04 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.541771E+09 | 703.34 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.516789E+09 | 879.04 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.583281E+09 | 879.04 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.547240E+09 | 1007.89 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.611028E+09 | 1007.89 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.598805E+09 | 1007.89 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.603565E+09 | 1007.89 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.689041E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.516789E+09 | 703.34 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.620283E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.102323E+10 | 1592.13 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.923893E+09 | 1592.13 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.967909E+09 | 1592.13 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.826378E+09 | 1388.60 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.857454E+09 | 907.52 | 02-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.840466E+09 | 907.52 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.800857E+09 | 1111.04 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.908723E+09 | 1388.60 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.858942E+09 | 1592.13 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.980011E+09 | 1592.13 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.981605E+09 | 1592.13 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.100024E+10 | 1592.13 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.109697E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.800857E+09 | 907.52 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.102323E+10 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.618032E+09 | 1007.95 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.559640E+09 | 1007.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.599956E+09 | 1007.95 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.520589E+09 | 879.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.547228E+09 | 527.66 | 02-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.537885E+09 | 480.79 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.510197E+09 | 574.53 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.576068E+09 | 879.10 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.534410E+09 | 879.10 | 05-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.589749E+09 | 1007.95 | 19-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.601511E+09 | 1007.95 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.601578E+09 | 1007.95 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.679684E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.510197E+09 | 480.79 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.618032E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.934863E+09 | 1592.13 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.861436E+09 | 1592.13 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.947047E+09 | 1592.13 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.828710E+09 | 1388.60 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.870787E+09 | 1111.04 | 02-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.855823E+09 | 1111.04 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.813729E+09 | 1111.04 | 19-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.914248E+09 | 1388.60 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.846502E+09 | 1592.13 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.916677E+09 | 1592.13 | 19-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.913157E+09 | 1592.13 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.907322E+09 | 1592.13 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.106103E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.813729E+09 | 1111.04 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.947047E+09 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.617563E+09 | 1007.89 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.568672E+09 | 1007.89 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.612266E+09 | 1007.89 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.527180E+09 | 1007.89 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.551308E+09 | 879.04 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.540557E+09 | 703.34 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.515143E+09 | 879.04 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.581738E+09 | 879.04 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.544792E+09 | 1007.89 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.608696E+09 | 1007.89 | 13-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.595911E+09 | 1007.89 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.601409E+09 | 1007.89 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.686523E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.515143E+09 | 703.34 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.617563E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103111E+10 | 1592.13 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.929764E+09 | 1592.13 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.972187E+09 | 1592.13 | 16-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.828854E+09 | 1388.60 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.857826E+09 | 1111.04 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.841344E+09 | 907.52 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.801261E+09 | 1111.04 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.910311E+09 | 1388.60 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.861875E+09 | 1592.13 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.986464E+09 | 1592.13 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.989356E+09 | 1592.13 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.100826E+10 | 1592.13 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.110186E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.801261E+09 | 907.52 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.103111E+10 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620557E+09 | 1007.95 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.562270E+09 | 1007.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.601362E+09 | 1007.95 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.521657E+09 | 879.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.548101E+09 | 527.66 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.538692E+09 | 527.66 | 23-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.510968E+09 | 703.38 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.576955E+09 | 879.10 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.535748E+09 | 879.10 | 05-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.592241E+09 | 1007.95 | 19-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.603931E+09 | 1007.95 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.604134E+09 | 1007.95 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.681662E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.510968E+09 | 527.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.620557E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.936967E+09 | 1592.13 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.862302E+09 | 1592.13 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.949926E+09 | 1592.13 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.831012E+09 | 1388.60 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.872507E+09 | 1111.04 | 02-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.857548E+09 | 1111.04 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.815829E+09 | 1111.04 | 19-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.916366E+09 | 1388.60 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.848919E+09 | 1592.13 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.919211E+09 | 1592.13 | 19-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.914812E+09 | 1592.13 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.910332E+09 | 1592.13 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.106357E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.815829E+09 | 1111.04 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.949926E+09 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620283E+09 | 1007.89 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.571192E+09 | 1007.89 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.614070E+09 | 1007.89 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.528958E+09 | 1007.89 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.553426E+09 | 879.04 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.541771E+09 | 703.34 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.516789E+09 | 879.04 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.583281E+09 | 879.04 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.547240E+09 | 1007.89 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.611028E+09 | 1007.89 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.598805E+09 | 1007.89 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.603565E+09 | 1007.89 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.689041E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.516789E+09 | 703.34 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.620283E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.103111E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995361E+09 |
February | 0.901968E+09 | 0.929764E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2461680.12 | 0.848239E+09 |
March | 0.107774E+10 | 0.972187E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3122014.69 | 0.537860E+09 |
April | 0.956342E+09 | 0.828854E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7630355.42 | 0.339564E+09 |
May | 0.103597E+10 | 0.857826E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19065137.18 | 0.226782E+09 |
June | 0.103308E+10 | 0.841344E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74895131.77 | 0.114487E+09 |
July | 0.959235E+09 | 0.801261E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80827269.06 | 76588165.18 |
August | 0.107774E+10 | 0.910311E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78139262.11 | 48824143.68 |
September | 0.956342E+09 | 0.861875E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24101057.65 | 0.111773E+09 |
October | 0.994195E+09 | 0.986464E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8088099.88 | 0.361456E+09 |
November | 0.984487E+09 | 0.989356E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1028612.27 | 0.514806E+09 |
December | 0.959235E+09 | 0.100826E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1643.40 | 0.886651E+09 |
Annual Sum or Average | 0.119305E+11 | 0.110186E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299360E+09 | 0.506239E+10 |
Minimum of Months | 0.901968E+09 | 0.801261E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48824143.68 |
Maximum of Months | 0.107774E+10 | 0.103111E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80827269.06 | 0.995361E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.620557E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670007E+09 |
February | 0.571020E+09 | 0.562270E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 840856.67 | 0.574971E+09 |
March | 0.682301E+09 | 0.601362E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2192321.47 | 0.370574E+09 |
April | 0.605444E+09 | 0.521657E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4367931.63 | 0.233369E+09 |
May | 0.655854E+09 | 0.548101E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11592907.53 | 0.156644E+09 |
June | 0.654023E+09 | 0.538692E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49084105.66 | 77727203.27 |
July | 0.607275E+09 | 0.510968E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52699798.96 | 52102520.80 |
August | 0.682301E+09 | 0.576955E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51425085.16 | 33065551.67 |
September | 0.605444E+09 | 0.535748E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15266446.81 | 74600045.69 |
October | 0.629407E+09 | 0.592241E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4284709.28 | 0.247625E+09 |
November | 0.623262E+09 | 0.603931E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 652852.41 | 0.350665E+09 |
December | 0.607275E+09 | 0.604162E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3484.73 | 0.594837E+09 |
Annual Sum or Average | 0.755301E+10 | 0.681665E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192411E+09 | 0.343619E+10 |
Minimum of Months | 0.571020E+09 | 0.510968E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33065551.67 |
Maximum of Months | 0.682301E+09 | 0.620557E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52699798.96 | 0.670007E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.937008E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105127E+10 |
February | 0.901968E+09 | 0.862302E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114325.07 | 0.901788E+09 |
March | 0.107774E+10 | 0.949971E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2131870.92 | 0.590423E+09 |
April | 0.956342E+09 | 0.831012E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5436335.18 | 0.353958E+09 |
May | 0.103597E+10 | 0.872507E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17685953.19 | 0.228506E+09 |
June | 0.103308E+10 | 0.857548E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74810686.49 | 0.112812E+09 |
July | 0.959235E+09 | 0.815829E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80356516.04 | 76002297.15 |
August | 0.107774E+10 | 0.916366E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75503107.73 | 50308409.48 |
September | 0.956342E+09 | 0.848919E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19880175.99 | 0.116404E+09 |
October | 0.994195E+09 | 0.919213E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3133895.50 | 0.396522E+09 |
November | 0.984487E+09 | 0.914812E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570490E+09 |
December | 0.959235E+09 | 0.910332E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940241E+09 |
Annual Sum or Average | 0.119305E+11 | 0.106358E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279053E+09 | 0.538873E+10 |
Minimum of Months | 0.901968E+09 | 0.815829E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50308409.48 |
Maximum of Months | 0.107774E+10 | 0.949971E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80356516.04 | 0.105127E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.620283E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672213E+09 |
February | 0.570983E+09 | 0.571192E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1062953.15 | 0.575658E+09 |
March | 0.682256E+09 | 0.614070E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1676415.58 | 0.379589E+09 |
April | 0.605404E+09 | 0.528958E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4421903.71 | 0.234673E+09 |
May | 0.655811E+09 | 0.553426E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12116579.60 | 0.154862E+09 |
June | 0.653980E+09 | 0.541771E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49010948.27 | 78007605.26 |
July | 0.607235E+09 | 0.516789E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53381937.19 | 51652457.18 |
August | 0.682256E+09 | 0.583281E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50346424.83 | 35016409.20 |
September | 0.605404E+09 | 0.547240E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15355069.91 | 75530375.40 |
October | 0.629366E+09 | 0.611028E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3923854.41 | 0.248626E+09 |
November | 0.623221E+09 | 0.598805E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 106488.46 | 0.352974E+09 |
December | 0.607235E+09 | 0.603565E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.37 | 0.597154E+09 |
Annual Sum or Average | 0.755252E+10 | 0.689041E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191403E+09 | 0.345596E+10 |
Minimum of Months | 0.570983E+09 | 0.516789E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35016409.20 |
Maximum of Months | 0.682256E+09 | 0.620283E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53381937.19 | 0.672213E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.102323E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564581E+09 |
February | 0.901968E+09 | 0.923893E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1478219.64 | 0.472067E+09 |
March | 0.107774E+10 | 0.967909E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2572078.32 | 0.287578E+09 |
April | 0.956342E+09 | 0.826378E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5890495.27 | 0.171643E+09 |
May | 0.103597E+10 | 0.857454E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11792237.89 | 0.114536E+09 |
June | 0.103308E+10 | 0.840466E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42584998.11 | 58820575.07 |
July | 0.959235E+09 | 0.800857E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47231951.08 | 39569932.42 |
August | 0.107774E+10 | 0.908723E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44487506.85 | 25425330.76 |
September | 0.956342E+09 | 0.858942E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13274116.29 | 67711096.25 |
October | 0.994195E+09 | 0.980011E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4180566.62 | 0.220191E+09 |
November | 0.984487E+09 | 0.981605E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 165060.86 | 0.313770E+09 |
December | 0.959235E+09 | 0.100024E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3294.90 | 0.534943E+09 |
Annual Sum or Average | 0.119305E+11 | 0.109697E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173661E+09 | 0.287084E+10 |
Minimum of Months | 0.901968E+09 | 0.800857E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25425330.76 |
Maximum of Months | 0.107774E+10 | 0.102323E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47231951.08 | 0.564581E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.618032E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382552E+09 |
February | 0.571020E+09 | 0.559640E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 422091.05 | 0.323666E+09 |
March | 0.682301E+09 | 0.599956E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1479207.94 | 0.203767E+09 |
April | 0.605444E+09 | 0.520589E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2758928.25 | 0.122605E+09 |
May | 0.655854E+09 | 0.547228E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6437311.59 | 83215034.58 |
June | 0.654023E+09 | 0.537885E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26764210.51 | 41879608.30 |
July | 0.607275E+09 | 0.510197E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28923306.99 | 28508742.57 |
August | 0.682301E+09 | 0.576068E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27809306.46 | 18801765.62 |
September | 0.605444E+09 | 0.534410E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7996483.41 | 46784561.93 |
October | 0.629407E+09 | 0.589749E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1916236.90 | 0.153602E+09 |
November | 0.623262E+09 | 0.601511E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52156.05 | 0.217446E+09 |
December | 0.607275E+09 | 0.601578E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361843E+09 |
Annual Sum or Average | 0.755301E+10 | 0.679684E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104559E+09 | 0.198467E+10 |
Minimum of Months | 0.571020E+09 | 0.510197E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18801765.62 |
Maximum of Months | 0.682301E+09 | 0.618032E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28923306.99 | 0.382552E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.934863E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462638E+10 |
February | 0.901968E+09 | 0.861436E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 656387.34 | 0.341841E+10 |
March | 0.107774E+10 | 0.947047E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28186308.23 | 0.241871E+10 |
April | 0.956342E+09 | 0.828710E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143386E+09 | 0.136740E+10 |
May | 0.103597E+10 | 0.870787E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339918E+09 | 0.728051E+09 |
June | 0.103308E+10 | 0.855823E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973097E+09 | 0.277328E+09 |
July | 0.959235E+09 | 0.813729E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101111E+10 | 0.204801E+09 |
August | 0.107774E+10 | 0.914248E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111741E+10 | 0.128599E+09 |
September | 0.956342E+09 | 0.846502E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385493E+09 | 0.486901E+09 |
October | 0.994195E+09 | 0.916677E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71337840.20 | 0.187775E+10 |
November | 0.984487E+09 | 0.913157E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285325E+10 |
December | 0.959235E+09 | 0.907322E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351089E+10 |
Annual Sum or Average | 0.119305E+11 | 0.106103E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407059E+10 | 0.218985E+11 |
Minimum of Months | 0.901968E+09 | 0.813729E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128599E+09 |
Maximum of Months | 0.107774E+10 | 0.947047E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111741E+10 | 0.462638E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.617563E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383395E+09 |
February | 0.570983E+09 | 0.568672E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 518521.14 | 0.323024E+09 |
March | 0.682256E+09 | 0.612266E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1027612.97 | 0.209218E+09 |
April | 0.605404E+09 | 0.527180E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2566923.53 | 0.124463E+09 |
May | 0.655811E+09 | 0.551308E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6231334.57 | 82922007.37 |
June | 0.653980E+09 | 0.540557E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26289237.53 | 42578067.23 |
July | 0.607235E+09 | 0.515143E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28783761.54 | 28465838.01 |
August | 0.682256E+09 | 0.581738E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26774196.64 | 20225602.99 |
September | 0.605404E+09 | 0.544792E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7830246.95 | 47935666.11 |
October | 0.629366E+09 | 0.608696E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1694332.72 | 0.155002E+09 |
November | 0.623221E+09 | 0.595911E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218234E+09 |
December | 0.607235E+09 | 0.601409E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361919E+09 |
Annual Sum or Average | 0.755252E+10 | 0.686523E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101716E+09 | 0.199738E+10 |
Minimum of Months | 0.570983E+09 | 0.515143E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20225602.99 |
Maximum of Months | 0.682256E+09 | 0.617563E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28783761.54 | 0.383395E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.103111E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.869357E+09 |
February | 0.901968E+09 | 0.929764E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1864165.58 | 0.741524E+09 |
March | 0.107774E+10 | 0.972187E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2572530.58 | 0.479178E+09 |
April | 0.956342E+09 | 0.828854E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6558775.24 | 0.299856E+09 |
May | 0.103597E+10 | 0.857826E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16266007.47 | 0.198084E+09 |
June | 0.103308E+10 | 0.841344E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63800187.70 | 99189425.64 |
July | 0.959235E+09 | 0.801261E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69857351.86 | 65745656.33 |
August | 0.107774E+10 | 0.910311E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67031842.29 | 42057244.43 |
September | 0.956342E+09 | 0.861875E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20370726.92 | 0.101813E+09 |
October | 0.994195E+09 | 0.986464E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6514430.66 | 0.328926E+09 |
November | 0.984487E+09 | 0.989356E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 428229.91 | 0.468726E+09 |
December | 0.959235E+09 | 0.100826E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799808E+09 |
Annual Sum or Average | 0.119305E+11 | 0.110186E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255264E+09 | 0.449426E+10 |
Minimum of Months | 0.901968E+09 | 0.801261E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42057244.43 |
Maximum of Months | 0.107774E+10 | 0.103111E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69857351.86 | 0.869357E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.620557E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586306E+09 |
February | 0.421807E+09 | 0.562270E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 709920.88 | 0.503408E+09 |
March | 0.502994E+09 | 0.601362E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1855786.24 | 0.328251E+09 |
April | 0.447140E+09 | 0.521657E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3866217.43 | 0.204708E+09 |
May | 0.484071E+09 | 0.548101E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9996542.64 | 0.136129E+09 |
June | 0.482240E+09 | 0.538692E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41682636.54 | 67071380.18 |
July | 0.448971E+09 | 0.510968E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45383432.22 | 44692662.43 |
August | 0.502994E+09 | 0.576955E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43945920.82 | 28445977.94 |
September | 0.447140E+09 | 0.535748E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12919507.38 | 67585219.12 |
October | 0.465148E+09 | 0.592241E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3546688.31 | 0.222981E+09 |
November | 0.460569E+09 | 0.603931E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262789.02 | 0.317591E+09 |
December | 0.448971E+09 | 0.604134E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7805.62 | 0.537137E+09 |
Annual Sum or Average | 0.557719E+10 | 0.681662E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164177E+09 | 0.304431E+10 |
Minimum of Months | 0.421807E+09 | 0.510968E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28445977.94 |
Maximum of Months | 0.502994E+09 | 0.620557E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45383432.22 | 0.586306E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.936967E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924400E+09 |
February | 0.901968E+09 | 0.862302E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98663.25 | 0.792270E+09 |
March | 0.107774E+10 | 0.949926E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1768485.44 | 0.523363E+09 |
April | 0.956342E+09 | 0.831012E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4595632.55 | 0.312180E+09 |
May | 0.103597E+10 | 0.872507E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14854803.25 | 0.200206E+09 |
June | 0.103308E+10 | 0.857548E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63195567.20 | 98203841.85 |
July | 0.959235E+09 | 0.815829E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68575877.57 | 65608724.77 |
August | 0.107774E+10 | 0.916366E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63742829.53 | 43517611.75 |
September | 0.956342E+09 | 0.848919E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16493316.88 | 0.105884E+09 |
October | 0.994195E+09 | 0.919211E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2624233.41 | 0.357239E+09 |
November | 0.984487E+09 | 0.914812E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515842E+09 |
December | 0.959235E+09 | 0.910332E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850522E+09 |
Annual Sum or Average | 0.119305E+11 | 0.106357E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235949E+09 | 0.478924E+10 |
Minimum of Months | 0.901968E+09 | 0.815829E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43517611.75 |
Maximum of Months | 0.107774E+10 | 0.949926E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68575877.57 | 0.924400E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.620283E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587509E+09 |
February | 0.570983E+09 | 0.571192E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 768691.97 | 0.503497E+09 |
March | 0.682256E+09 | 0.614070E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1333044.33 | 0.336509E+09 |
April | 0.605404E+09 | 0.528958E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3587111.33 | 0.207139E+09 |
May | 0.655811E+09 | 0.553426E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9772835.80 | 0.135952E+09 |
June | 0.653980E+09 | 0.541771E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40828222.46 | 68069853.11 |
July | 0.607235E+09 | 0.516789E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44815685.64 | 44780995.69 |
August | 0.682256E+09 | 0.583281E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42073352.15 | 30404117.94 |
September | 0.605404E+09 | 0.547240E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12617233.44 | 69237037.95 |
October | 0.629366E+09 | 0.611028E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3030067.30 | 0.224935E+09 |
November | 0.623221E+09 | 0.598805E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7629.98 | 0.319823E+09 |
December | 0.607235E+09 | 0.603565E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538062E+09 |
Annual Sum or Average | 0.755252E+10 | 0.689041E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158834E+09 | 0.306592E+10 |
Minimum of Months | 0.570983E+09 | 0.516789E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30404117.94 |
Maximum of Months | 0.682256E+09 | 0.620283E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44815685.64 | 0.587509E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124551E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 862377.60 | 0.107186E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875482.47 | 0.701888E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5598606.31 | 0.423723E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15914864.23 | 0.274996E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71287607.48 | 0.133132E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81159002.79 | 87391812.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74080637.88 | 55487591.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19095456.85 | 0.148654E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4002648.45 | 0.493709E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335934.83 | 0.706460E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118787E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274213E+09 | 0.653068E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55487591.88 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81159002.79 | 0.124551E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151401E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2206115.25 | 0.130235E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2888386.09 | 0.859931E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8589511.89 | 0.530252E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21915583.10 | 0.347985E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92713313.54 | 0.169742E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104327E+09 | 0.110822E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95764195.87 | 70323304.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26719872.54 | 0.178883E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6662446.25 | 0.587036E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1777292.95 | 0.834393E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141230E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363563E+09 | 0.791803E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70323304.37 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104327E+09 | 0.151401E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150276E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143644.67 | 0.129212E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1266150.43 | 0.858310E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2685155.52 | 0.536936E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11916852.15 | 0.352971E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78068769.39 | 0.162557E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89391399.51 | 0.109419E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84879047.21 | 65100417.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19638512.28 | 0.168390E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2877669.20 | 0.570703E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505814.67 | 0.803372E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135612E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291373E+09 | 0.777876E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65100417.99 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89391399.51 | 0.150276E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1939.73 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 159.18 | 26-FEB-13:10 | 2420.66 | 12-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1592.13 | 16-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 83.73 | 11-MAR-18:03 | 1313.49 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 1388.60 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.85 | 16-APR-12:00 | 758.42 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 1111.04 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.73 | 07-MAY-12:10 | 604.48 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 907.52 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 413.39 | 11-JUN-15:00 | 452.45 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 1111.04 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 371.49 | 08-JUL-18:53 | 322.19 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 1388.60 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 395.40 | 06-AUG-13:52 | 213.18 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 1592.13 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.34 | 17-SEP-15:00 | 403.84 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.40 | 08-OCT-14:00 | 785.19 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.91 | 19-NOV-15:00 | 1384.36 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 12-DEC-14:00 | 1924.28 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 907.52 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.18 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 413.39 | 2420.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1007.95 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1281.84 | 07-JAN-18:05 |
February | 827.22 | 01-FEB-10:09 | 1007.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.64 | 26-FEB-15:50 | 1613.77 | 12-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 1007.95 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.85 | 11-MAR-18:03 | 865.36 | 22-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 879.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.50 | 08-APR-17:20 | 502.34 | 05-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 527.66 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.83 | 29-MAY-17:50 | 400.53 | 10-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 527.66 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.00 | 11-JUN-15:00 | 302.23 | 07-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 703.38 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.90 | 08-JUL-18:53 | 214.87 | 01-JUL-20:00 |
August | 827.22 | 01-AUG-09:09 | 879.10 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.23 | 06-AUG-14:10 | 141.61 | 23-AUG-05:00 |
September | 827.22 | 01-SEP-09:09 | 879.10 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.48 | 17-SEP-15:10 | 266.02 | 29-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 1007.95 | 19-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.87 | 09-OCT-16:00 | 519.03 | 28-OCT-04:00 |
November | 827.22 | 01-NOV-09:09 | 1007.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.02 | 19-NOV-15:00 | 921.74 | 30-NOV-22:03 |
December | 827.22 | 01-DEC-10:09 | 1007.95 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | 12-DEC-14:00 | 1277.04 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 527.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.61 | |||||
Maximum of Months | 827.22 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 270.00 | 1613.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1961.09 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 28-FEB-15:00 | 2420.66 | 12-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1592.13 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.79 | 30-MAR-16:00 | 1319.64 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 1388.60 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.23 | 08-APR-17:20 | 760.16 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 1111.04 | 02-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.43 | 07-MAY-12:13 | 607.69 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 1111.04 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 387.80 | 11-JUN-15:00 | 453.44 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 1111.04 | 19-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 370.96 | 08-JUL-18:53 | 321.93 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 1388.60 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.41 | 06-AUG-14:05 | 214.48 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 1592.13 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.24 | 17-SEP-14:48 | 405.15 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 19-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.58 | 09-OCT-15:18 | 812.24 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1384.70 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1957.13 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 1111.04 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.48 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 387.80 | 2420.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1007.89 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1291.79 | 07-JAN-18:05 |
February | 827.17 | 01-FEB-10:09 | 1007.89 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 116.32 | 26-FEB-13:00 | 1625.72 | 11-FEB-18:05 |
March | 827.17 | 01-MAR-10:09 | 1007.89 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.20 | 30-MAR-16:00 | 870.43 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 1007.89 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.39 | 16-APR-12:00 | 498.34 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 879.04 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.26 | 07-MAY-12:10 | 408.11 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 703.34 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.99 | 11-JUN-15:00 | 305.67 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 879.04 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.46 | 08-JUL-19:10 | 211.22 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 879.04 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.38 | 06-AUG-13:52 | 144.42 | 25-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 1007.89 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.70 | 17-SEP-12:10 | 264.67 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 1007.89 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.21 | 08-OCT-13:53 | 524.06 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 | 19-NOV-15:00 | 922.33 | 30-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 12-DEC-14:00 | 1273.42 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 703.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.42 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 271.38 | 1625.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1080.59 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 89.00 | 26-FEB-16:00 | 1308.50 | 12-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1592.13 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 72.71 | 11-MAR-18:03 | 769.94 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 1388.60 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.93 | 16-APR-12:00 | 404.52 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 907.52 | 02-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.91 | 07-MAY-12:00 | 343.26 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 907.52 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.01 | 11-JUN-15:00 | 245.94 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 1111.04 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.32 | 08-JUL-18:53 | 181.47 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 1388.60 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.27 | 06-AUG-14:00 | 122.17 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 1592.13 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.98 | 17-SEP-15:00 | 253.68 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.93 | 08-OCT-13:53 | 490.84 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.85 | 19-NOV-15:00 | 744.82 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 | 12-DEC-14:00 | 1240.41 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 907.52 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.17 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 249.01 | 1308.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1007.95 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 717.15 | 07-JAN-18:10 |
February | 827.22 | 01-FEB-10:09 | 1007.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.97 | 26-FEB-15:50 | 869.96 | 12-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 1007.95 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.09 | 11-MAR-18:03 | 518.90 | 22-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 879.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.72 | 08-APR-17:03 | 268.30 | 05-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 527.66 | 02-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.73 | 29-MAY-18:00 | 233.69 | 10-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 480.79 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.84 | 11-JUN-15:00 | 169.72 | 07-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 574.53 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.92 | 08-JUL-18:53 | 119.01 | 28-JUL-22:00 |
August | 827.22 | 01-AUG-09:09 | 879.10 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.16 | 06-AUG-14:00 | 81.34 | 25-AUG-05:00 |
September | 827.22 | 01-SEP-09:09 | 879.10 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.76 | 17-SEP-15:00 | 168.16 | 29-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 1007.95 | 19-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.82 | 09-OCT-15:50 | 332.95 | 28-OCT-04:00 |
November | 827.22 | 01-NOV-09:09 | 1007.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.42 | 19-NOV-15:00 | 497.54 | 07-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 1007.95 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 828.40 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.34 | |||||
Maximum of Months | 827.22 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 151.16 | 869.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 23180.95 | 27-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 115.15 | 28-FEB-15:00 | 25127.54 | 03-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1592.13 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2827.79 | 30-MAR-16:10 | 14377.02 | 06-MAR-07:03 |
April | 1306.65 | 03-APR-09:09 | 1388.60 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3720.02 | 17-APR-16:10 | 15738.19 | 06-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 1111.04 | 02-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5114.20 | 19-MAY-16:10 | 10482.93 | 11-MAY-06:10 |
June | 1306.65 | 01-JUN-09:09 | 1111.04 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7267.33 | 06-JUN-16:05 | 7321.60 | 08-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 1111.04 | 19-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8356.90 | 07-JUL-16:03 | 3472.33 | 28-JUL-16:03 |
August | 1306.65 | 01-AUG-09:09 | 1388.60 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7994.16 | 01-AUG-16:03 | 3609.92 | 25-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 1592.13 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5433.27 | 07-SEP-16:05 | 7845.08 | 14-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 19-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4161.98 | 10-OCT-16:05 | 14895.72 | 26-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19689.24 | 22-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 21618.17 | 18-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 1111.04 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3472.33 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8356.90 | 25127.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1007.89 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 721.78 | 07-JAN-18:10 |
February | 827.17 | 01-FEB-10:09 | 1007.89 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.44 | 26-FEB-13:20 | 892.82 | 11-FEB-18:05 |
March | 827.17 | 01-MAR-10:09 | 1007.89 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | 30-MAR-16:00 | 522.04 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 1007.89 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.16 | 16-APR-12:00 | 267.82 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 879.04 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.22 | 07-MAY-12:00 | 237.93 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 703.34 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.87 | 11-JUN-15:00 | 171.88 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 879.04 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.44 | 08-JUL-18:53 | 121.03 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 879.04 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.85 | 06-AUG-14:00 | 85.04 | 25-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 1007.89 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.64 | 24-SEP-13:00 | 168.09 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 1007.89 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.72 | 08-OCT-13:53 | 335.79 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 502.01 | 07-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 824.03 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 703.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.04 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 151.85 | 892.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1670.39 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 124.34 | 26-FEB-13:00 | 2012.98 | 12-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1592.13 | 16-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 69.54 | 11-MAR-18:03 | 1210.03 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 1388.60 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.07 | 16-APR-12:00 | 673.06 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 1111.04 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.70 | 07-MAY-12:00 | 544.75 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 907.52 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.43 | 11-JUN-15:00 | 392.35 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 1111.04 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 337.75 | 08-JUL-18:53 | 282.22 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 1388.60 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.95 | 06-AUG-14:00 | 190.55 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 1592.13 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.53 | 17-SEP-15:10 | 373.99 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.57 | 08-OCT-13:58 | 727.36 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.89 | 19-NOV-15:00 | 1159.75 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1792.92 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 907.52 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.55 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 361.43 | 2012.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1007.95 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1103.14 | 07-JAN-18:05 |
February | 805.43 | 01-FEB-08:09 | 1007.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 60.96 | 26-FEB-15:45 | 1341.98 | 12-FEB-01:00 |
March | 805.43 | 01-MAR-08:09 | 1007.95 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.32 | 11-MAR-18:03 | 796.37 | 22-MAR-03:00 |
April | 805.43 | 03-APR-07:10 | 879.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.52 | 08-APR-17:20 | 445.63 | 05-APR-05:00 |
May | 805.43 | 01-MAY-07:10 | 527.66 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.66 | 21-MAY-17:10 | 360.80 | 10-MAY-04:00 |
June | 805.43 | 01-JUN-07:10 | 527.66 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.57 | 11-JUN-15:00 | 261.88 | 07-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 703.38 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.82 | 08-JUL-18:53 | 182.71 | 28-JUL-22:00 |
August | 805.43 | 01-AUG-07:10 | 879.10 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.01 | 06-AUG-14:00 | 125.51 | 25-AUG-05:00 |
September | 805.43 | 01-SEP-07:10 | 879.10 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.57 | 17-SEP-15:10 | 246.58 | 29-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 1007.95 | 19-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.55 | 09-OCT-15:50 | 479.60 | 28-OCT-04:00 |
November | 805.43 | 01-NOV-07:10 | 1007.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.23 | 19-NOV-15:00 | 772.33 | 30-NOV-22:03 |
December | 805.43 | 01-DEC-08:09 | 1007.95 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.31 | 12-DEC-15:00 | 1190.00 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 527.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.51 | |||||
Maximum of Months | 805.43 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 238.01 | 1341.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1689.00 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 | 28-FEB-15:00 | 2047.55 | 11-FEB-18:05 |
March | 1306.65 | 01-MAR-10:09 | 1592.13 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.28 | 30-MAR-16:00 | 1216.02 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 1388.60 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.18 | 08-APR-17:20 | 675.14 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 1111.04 | 02-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.19 | 07-MAY-12:00 | 547.63 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 1111.04 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 335.32 | 11-JUN-15:10 | 393.23 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 1111.04 | 19-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.54 | 08-JUL-18:53 | 282.91 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 1388.60 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.10 | 06-AUG-13:56 | 191.69 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 1592.13 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.86 | 17-SEP-14:48 | 375.37 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 19-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.23 | 09-OCT-15:48 | 749.06 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1159.99 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1822.63 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 1111.04 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.69 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 335.32 | 2047.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1007.89 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1111.81 | 07-JAN-18:05 |
February | 827.17 | 01-FEB-10:09 | 1007.89 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 93.11 | 26-FEB-13:00 | 1395.92 | 11-FEB-18:05 |
March | 827.17 | 01-MAR-10:09 | 1007.89 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.86 | 30-MAR-16:00 | 801.51 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 1007.89 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.30 | 16-APR-12:00 | 443.22 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 879.04 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.21 | 07-MAY-12:00 | 367.56 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 703.34 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.47 | 11-JUN-15:00 | 265.10 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 879.04 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.63 | 08-JUL-18:50 | 186.23 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 879.04 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.07 | 06-AUG-14:00 | 128.95 | 25-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 1007.89 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.88 | 17-SEP-12:10 | 246.07 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 1007.89 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.16 | 08-OCT-13:53 | 484.66 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 27-NOV-13:00 | 772.72 | 30-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1186.54 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 703.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.95 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 236.07 | 1395.92 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2374.64 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.21 | 26-FEB-14:43 | 2928.23 | 12-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.05 | 11-MAR-16:00 | 1814.53 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.41 | 16-APR-12:00 | 951.11 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.27 | 07-MAY-12:00 | 785.35 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.13 | 11-JUN-15:00 | 541.98 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.15 | 08-JUL-18:53 | 387.09 | 28-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.15 | 06-AUG-14:00 | 264.64 | 25-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.37 | 17-SEP-14:55 | 547.58 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.63 | 09-OCT-16:00 | 1095.83 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.59 | 19-NOV-15:00 | 1618.05 | 07-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2747.32 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.64 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.15 | 2928.23 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2968.16 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.61 | 26-FEB-13:20 | 3612.03 | 12-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.84 | 11-MAR-16:00 | 2211.59 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.95 | 16-APR-12:00 | 1203.18 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.34 | 07-MAY-12:20 | 993.94 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585.52 | 11-JUN-15:00 | 692.10 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.15 | 08-JUL-18:53 | 485.21 | 28-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.74 | 06-AUG-14:00 | 333.34 | 25-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.14 | 17-SEP-15:00 | 674.51 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.09 | 08-OCT-14:00 | 1308.93 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.89 | 19-NOV-15:00 | 1973.64 | 07-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3300.19 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.34 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585.52 | 3612.03 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3154.67 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.92 | 26-FEB-14:30 | 3758.52 | 11-FEB-18:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.95 | 11-MAR-16:00 | 2016.15 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.83 | 16-APR-11:55 | 1145.10 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.73 | 07-MAY-11:53 | 888.86 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.71 | 11-JUN-15:00 | 679.38 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.58 | 08-JUL-18:53 | 516.22 | 01-JUL-20:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.37 | 06-AUG-13:52 | 321.42 | 23-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.19 | 17-SEP-15:00 | 580.91 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.01 | 08-OCT-14:00 | 1201.92 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.51 | 19-NOV-15:00 | 2026.17 | 30-NOV-22:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2966.62 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.42 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.58 | 3758.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12699.98 | 31-JAN-17:00 | 6035.01 | 7552.50 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18206.91 | 28-FEB-17:00 | 6035.01 | 7552.50 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21932.94 | 31-MAR-08:00 | 6035.01 | 7552.50 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22497.11 | 18-APR-08:00 | 6035.01 | 7552.50 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34869.32 | 30-MAY-05:13 | 1905.79 | 2517.43 | 14968.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36072.92 | 26-JUN-05:13 | 1905.79 | 2517.43 | 14968.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 46015.24 | 15-JUL-04:02 | 0.00 | 2097.86 | 18975.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 46030.61 | 10-AUG-04:02 | 0.00 | 4195.72 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36603.11 | 08-SEP-05:13 | 1905.79 | 2517.43 | 14968.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26692.08 | 19-OCT-05:13 | 1905.79 | 2517.43 | 14968.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20116.13 | 06-NOV-17:00 | 6035.01 | 7552.50 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18735.47 | 13-DEC-08:10 | 18105.02 | 22657.49 | 54555.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12699.98 | 0.00 | 2097.86 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46030.61 | 18105.02 | 22657.49 | 54555.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1645.19 | 28-JAN-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.97 |
February | 3632.33 | 26-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.47 | 0.00 |
March | 7039.17 | 30-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.61 | 0.00 |
April | 7930.03 | 17-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.57 | 0.00 |
May | 8824.50 | 30-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.57 | 0.00 |
June | 9519.04 | 27-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.28 | 0.00 |
July | 10593.76 | 07-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.76 | 0.00 |
August | 10712.64 | 01-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.96 | 0.00 |
September | 9206.78 | 06-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.92 | 0.00 |
October | 6962.27 | 10-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.62 | 0.00 |
November | 3514.58 | 05-NOV-14:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 |
December | 2150.05 | 12-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1645.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10712.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.28 | 144.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2060.16 | 14-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1595.67 |
February | 2322.37 | 03-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1750.65 |
March | 2336.67 | 30-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.10 | 0.00 |
April | 2873.87 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.67 |
May | 3683.53 | 30-MAY-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.34 | 0.00 |
June | 4123.16 | 26-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.10 | 0.00 |
July | 4529.37 | 10-JUL-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.50 | 0.00 |
August | 4513.56 | 02-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.03 | 0.00 |
September | 4140.61 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.87 | 0.00 |
October | 2766.46 | 11-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 | 0.00 |
November | 2043.28 | 07-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.76 |
December | 2367.50 | 09-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2043.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4529.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.50 | 1750.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2073.52 | 13-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.73 |
February | 2492.01 | 23-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.20 |
March | 2823.43 | 13-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.55 |
April | 3132.70 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.89 |
May | 3927.22 | 30-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.21 | 0.00 |
June | 4268.25 | 19-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.81 | 0.00 |
July | 4781.63 | 07-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.28 | 0.00 |
August | 4931.96 | 18-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.30 | 0.00 |
September | 4726.21 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.34 | 0.00 |
October | 3557.95 | 11-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 | 0.00 |
November | 2303.41 | 14-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.28 |
December | 2283.59 | 15-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2073.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4931.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.30 | 315.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9111.62 | 20-JAN-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11031.88 | 28-FEB-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14796.67 | 30-MAR-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15679.44 | 18-APR-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18110.09 | 30-MAY-05:13 | 1905.79 | 2517.43 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30540.38 | 26-JUN-05:13 | 1905.79 | 2517.43 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33509.24 | 07-JUL-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34132.06 | 03-AUG-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22023.41 | 08-SEP-05:13 | 1905.79 | 2517.43 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16222.42 | 11-OCT-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11958.06 | 06-NOV-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9979.06 | 13-DEC-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9111.62 | 0.00 | 2517.43 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34132.06 | 6035.01 | 7552.50 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9343.23 | 20-JAN-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11126.59 | 28-FEB-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16855.37 | 30-MAR-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17710.91 | 17-APR-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19987.36 | 30-MAY-15:40 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30567.93 | 26-JUN-05:13 | 1905.79 | 2517.43 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35925.05 | 07-JUL-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35916.90 | 03-AUG-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20269.67 | 07-SEP-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17214.71 | 11-OCT-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10655.50 | 06-NOV-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10046.65 | 13-DEC-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9343.23 | 0.00 | 2517.43 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35925.05 | 6035.01 | 7552.50 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1897.20 | 31-JAN-17:00 | 1272.23 | 1111.04 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.57 |
February | 2517.03 | 28-FEB-15:40 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 |
March | 4806.79 | 30-MAR-15:50 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 58.11 | 0.00 |
April | 5150.49 | 19-APR-14:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.52 | 0.00 |
May | 6633.83 | 30-MAY-15:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 50.98 | 0.00 |
June | 9431.44 | 25-JUN-16:22 | 401.76 | 253.14 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 319.35 | 0.00 |
July | 12495.76 | 16-JUL-13:43 | 267.84 | 168.76 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 150.26 | 0.00 |
August | 9343.10 | 06-AUG-14:43 | 267.84 | 168.76 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 243.81 | 0.00 |
September | 6513.16 | 06-SEP-14:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 51.54 | 0.00 |
October | 4438.63 | 02-OCT-14:40 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.79 | 0.00 |
November | 2208.60 | 05-NOV-16:33 | 267.84 | 246.89 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.78 |
December | 2039.16 | 13-DEC-15:00 | 1306.65 | 907.52 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1897.20 | 267.84 | 168.76 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12495.76 | 1306.65 | 1111.04 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 319.35 | 33.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1588.47 | 31-JAN-15:10 | 805.43 | 527.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 |
February | 2105.93 | 28-FEB-15:00 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 15.06 | 0.00 |
March | 3670.53 | 30-MAR-11:00 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.64 |
April | 5727.06 | 17-APR-10:20 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.69 |
May | 11664.77 | 07-MAY-09:23 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.35 |
June | 11892.02 | 04-JUN-08:23 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.96 |
July | 11979.89 | 02-JUL-10:32 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 |
August | 11998.20 | 13-AUG-10:23 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 | 0.00 |
September | 10002.36 | 04-SEP-09:53 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 |
October | 4482.03 | 11-OCT-10:30 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 | 0.00 |
November | 1915.41 | 05-NOV-16:33 | 169.56 | 156.30 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 |
December | 1697.12 | 12-DEC-16:50 | 805.43 | 879.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1588.47 | 169.56 | 106.84 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11998.20 | 827.22 | 879.10 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 15.06 | 75.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4516.25 | 11-JAN-14:30 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.25 |
February | 12786.09 | 26-FEB-14:43 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.39 |
March | 9739.50 | 30-MAR-13:50 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 44.32 | 0.00 |
April | 8495.55 | 17-APR-14:00 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 15.85 | 0.00 |
May | 7908.73 | 30-MAY-14:30 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 54.52 | 0.00 |
June | 11084.89 | 25-JUN-16:22 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 318.60 | 0.00 |
July | 14299.82 | 16-JUL-13:43 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 151.86 | 0.00 |
August | 14713.50 | 20-AUG-13:32 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 74.03 | 0.00 |
September | 15029.50 | 24-SEP-14:02 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 40.86 | 0.00 |
October | 15072.99 | 09-OCT-14:32 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 0.00 |
November | 14380.31 | 11-NOV-14:32 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.37 |
December | 6154.84 | 12-DEC-13:40 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4516.25 | 267.84 | 168.76 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15072.99 | 1306.65 | 759.45 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 318.60 | 246.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1861.46 | 20-JAN-16:40 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.10 |
February | 4203.90 | 27-FEB-17:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 |
March | 6468.03 | 30-MAR-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 39.20 | 0.00 |
April | 11470.75 | 09-APR-17:23 | 0.00 | 106.83 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.29 |
May | 11359.79 | 21-MAY-18:23 | 0.00 | 106.83 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.63 |
June | 13438.02 | 25-JUN-16:22 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 193.13 | 0.00 |
July | 13711.13 | 23-JUL-18:32 | 0.00 | 133.54 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.18 | 0.00 |
August | 13717.34 | 13-AUG-17:02 | 0.00 | 160.25 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 73.34 | 0.00 |
September | 11421.12 | 04-SEP-16:33 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 19.76 | 0.00 |
October | 7620.53 | 08-OCT-16:12 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 0.00 |
November | 3783.25 | 06-NOV-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.94 |
December | 2002.06 | 11-DEC-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1861.46 | 0.00 | 106.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13717.34 | 805.38 | 480.76 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 193.13 | 75.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1803.75 | 31-JAN-15:10 | 1272.23 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.29 |
February | 2066.91 | 28-FEB-15:20 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 | 0.00 |
March | 2762.47 | 30-MAR-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.69 | 0.00 |
April | 3092.49 | 19-APR-14:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.99 | 0.00 |
May | 4668.72 | 30-MAY-15:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.32 | 0.00 |
June | 5591.37 | 30-JUN-14:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 71.98 | 0.00 |
July | 6120.60 | 14-JUL-15:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 51.44 | 0.00 |
August | 6144.98 | 09-AUG-15:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.09 | 0.00 |
September | 5805.52 | 06-SEP-14:00 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.27 | 0.00 |
October | 4002.80 | 18-OCT-14:00 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.28 | 0.00 |
November | 2277.05 | 05-NOV-13:03 | 200.88 | 126.57 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.60 |
December | 2032.64 | 13-DEC-13:30 | 1272.23 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1803.75 | 200.88 | 126.57 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6144.98 | 1306.65 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 71.98 | 22.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1385.69 | 31-JAN-15:00 | 827.22 | 527.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 |
February | 1752.40 | 27-FEB-10:40 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.89 |
March | 2556.30 | 14-MAR-11:00 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.05 |
April | 4304.22 | 17-APR-10:10 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.22 |
May | 5387.24 | 30-MAY-10:00 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 0.00 |
June | 8031.09 | 11-JUN-10:02 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.39 |
July | 9059.35 | 09-JUL-10:22 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 27.90 | 0.00 |
August | 10882.78 | 27-AUG-09:52 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 |
September | 6426.75 | 08-SEP-09:30 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.38 | 0.00 |
October | 4421.43 | 11-OCT-10:30 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 |
November | 2299.40 | 06-NOV-10:20 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.63 |
December | 1525.85 | 13-DEC-12:00 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1385.69 | 169.56 | 106.84 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10882.78 | 827.22 | 527.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 27.90 | 45.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2493.14 | 28-JAN-14:50 | 137.54 | 126.57 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.04 |
February | 6311.83 | 21-FEB-14:30 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.80 |
March | 7835.91 | 30-MAR-16:10 | 401.76 | 421.91 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 2827.79 | 0.00 |
April | 7892.73 | 17-APR-16:10 | 401.76 | 421.91 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3720.02 | 0.00 |
May | 9063.84 | 30-MAY-12:00 | 687.71 | 759.45 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4181.58 | 0.00 |
June | 10351.27 | 06-JUN-16:20 | 401.76 | 421.91 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 6994.09 | 0.00 |
July | 10830.95 | 07-JUL-16:10 | 1205.27 | 1265.74 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 7784.31 | 0.00 |
August | 12034.55 | 27-AUG-15:12 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 94.40 | 0.00 |
September | 10700.43 | 07-SEP-12:00 | 687.71 | 759.45 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4654.20 | 0.00 |
October | 12625.03 | 09-OCT-14:23 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 0.00 |
November | 12006.86 | 12-NOV-14:53 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.90 |
December | 5787.16 | 12-DEC-14:00 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2493.14 | 137.54 | 126.57 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12625.03 | 1306.65 | 1265.74 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 7784.31 | 190.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1496.23 | 20-JAN-16:40 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.28 |
February | 3006.42 | 27-FEB-17:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 |
March | 4353.03 | 30-MAR-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | 0.00 |
April | 4916.64 | 17-APR-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 | 0.00 |
May | 6154.94 | 06-MAY-17:42 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 | 0.00 |
June | 11001.06 | 04-JUN-16:32 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 40.95 | 0.00 |
July | 10919.89 | 09-JUL-17:02 | 0.00 | 160.25 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 73.77 | 0.00 |
August | 10948.91 | 06-AUG-16:31 | 296.72 | 186.96 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 94.82 | 0.00 |
September | 8473.05 | 04-SEP-16:23 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 12.27 | 0.00 |
October | 7894.83 | 09-OCT-16:23 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 5.99 | 0.00 |
November | 3726.03 | 06-NOV-16:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.70 |
December | 1672.58 | 11-DEC-16:20 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1496.23 | 0.00 | 106.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11001.06 | 805.38 | 480.76 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 94.82 | 26.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1852.25 | 31-JAN-17:00 | 1272.23 | 1111.04 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.36 |
February | 2500.81 | 28-FEB-15:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 | 0.00 |
March | 4281.02 | 30-MAR-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 49.28 | 0.00 |
April | 4683.62 | 18-APR-14:00 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 0.00 |
May | 6002.17 | 30-MAY-15:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 42.60 | 0.00 |
June | 6415.58 | 30-JUN-14:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 112.37 | 0.00 |
July | 9461.74 | 16-JUL-13:43 | 267.84 | 168.76 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 128.81 | 0.00 |
August | 7297.69 | 14-AUG-04:02 | 0.00 | 884.49 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 |
September | 5943.80 | 06-SEP-14:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 43.08 | 0.00 |
October | 4125.54 | 02-OCT-14:40 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 26.72 | 0.00 |
November | 2139.71 | 03-NOV-15:20 | 1272.23 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.75 |
December | 2016.92 | 13-DEC-13:30 | 1272.23 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1852.25 | 0.00 | 168.76 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9461.74 | 1306.65 | 1111.04 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 128.81 | 34.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1545.68 | 31-JAN-16:30 | 805.43 | 574.53 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 |
February | 2532.38 | 27-FEB-10:00 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.05 |
March | 3685.74 | 30-MAR-11:00 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.84 |
April | 6493.23 | 16-APR-10:53 | 127.17 | 80.13 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.72 |
May | 11578.45 | 07-MAY-09:13 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.66 |
June | 11517.78 | 11-JUN-09:53 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.63 |
July | 12076.45 | 04-JUL-09:52 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 |
August | 12412.39 | 27-AUG-09:52 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 |
September | 10843.34 | 04-SEP-09:23 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 |
October | 4662.83 | 11-OCT-10:20 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.02 |
November | 2470.17 | 06-NOV-10:00 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.46 |
December | 1672.45 | 13-DEC-13:30 | 805.43 | 527.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1545.68 | 127.17 | 80.13 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.02 | |
Maximum of Months | 12412.39 | 805.43 | 574.53 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4616.73 | 11-JAN-14:10 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.69 |
February | 8400.35 | 21-FEB-14:30 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.01 |
March | 9148.07 | 30-MAR-13:40 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 35.29 | 0.00 |
April | 7825.34 | 17-APR-13:50 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 0.00 |
May | 7222.34 | 30-MAY-14:20 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 46.54 | 0.00 |
June | 7196.69 | 30-JUN-14:00 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 97.65 | 0.00 |
July | 11122.11 | 16-JUL-13:43 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 128.46 | 0.00 |
August | 13084.05 | 13-AUG-13:32 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 82.71 | 0.00 |
September | 9927.53 | 17-SEP-14:43 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 60.08 | 0.00 |
October | 13476.58 | 09-OCT-14:23 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 4.96 | 0.00 |
November | 10673.16 | 12-NOV-13:43 | 200.88 | 126.57 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.82 |
December | 6636.01 | 08-DEC-14:00 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4616.73 | 200.88 | 126.57 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13476.58 | 1306.65 | 759.45 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 128.46 | 177.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1735.77 | 20-JAN-16:40 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.78 |
February | 4061.09 | 27-FEB-17:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
March | 6065.38 | 30-MAR-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 32.86 | 0.00 |
April | 10665.75 | 09-APR-17:12 | 0.00 | 106.83 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.37 |
May | 10093.51 | 21-MAY-18:23 | 0.00 | 106.83 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.23 |
June | 12669.74 | 04-JUN-16:42 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 58.97 | 0.00 |
July | 12924.90 | 04-JUL-17:52 | 0.00 | 160.25 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 52.76 | 0.00 |
August | 12709.90 | 13-AUG-16:51 | 339.11 | 213.67 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 59.20 | 0.00 |
September | 10669.39 | 04-SEP-16:12 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 18.52 | 0.00 |
October | 8558.16 | 09-OCT-16:23 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 8.57 | 0.00 |
November | 3913.98 | 06-NOV-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.65 |
December | 1884.57 | 11-DEC-15:50 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1735.77 | 0.00 | 106.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12924.90 | 805.38 | 480.76 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 59.20 | 61.23 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.163269E+12 | 248775.13 | 09-JAN-07:10 | 0.225470E+11 | 51214.25 | 27-JAN-07:40 |
February | 0.131756E+12 | 245064.60 | 13-FEB-07:10 | 0.155843E+11 | 58954.41 | 03-FEB-07:40 |
March | 0.127700E+12 | 119840.44 | 30-MAR-15:09 | 0.118796E+11 | 17293.41 | 18-MAR-07:10 |
April | 0.122467E+12 | 124172.35 | 17-APR-15:20 | 0.107504E+11 | 18842.90 | 06-APR-06:30 |
May | 0.144000E+12 | 139770.80 | 30-MAY-15:09 | 0.108019E+11 | 9855.39 | 01-MAY-11:09 |
June | 0.163923E+12 | 151182.81 | 27-JUN-15:50 | 0.102048E+11 | 9714.76 | 01-JUN-11:20 |
July | 0.170538E+12 | 165517.46 | 07-JUL-15:00 | 0.995589E+10 | 9614.26 | 03-JUL-11:30 |
August | 0.186331E+12 | 163383.77 | 02-AUG-15:00 | 0.103428E+11 | 9609.12 | 31-AUG-11:00 |
September | 0.146957E+12 | 155349.73 | 07-SEP-15:50 | 0.990766E+10 | 9700.26 | 29-SEP-11:09 |
October | 0.128863E+12 | 132956.20 | 10-OCT-15:00 | 0.106213E+11 | 16498.34 | 26-OCT-06:40 |
November | 0.121995E+12 | 146994.77 | 22-NOV-07:10 | 0.113824E+11 | 36579.38 | 22-NOV-07:40 |
December | 0.135475E+12 | 198791.42 | 18-DEC-07:10 | 0.133084E+11 | 47594.87 | 18-DEC-07:00 |
Annual Sum or Average | 0.174327E+13 | 0.147287E+12 | ||||
Minimum of Months | 0.121995E+12 | 119840.44 | 0.990766E+10 | 9609.12 | ||
Maximum of Months | 0.186331E+12 | 248775.13 | 0.225470E+11 | 58954.41 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.312630E+11 | 0.113887E+11 | 0.593559E+11 | 0.143945E+10 | 0.412933E+10 | 12379742.02 | 0.540085E+11 | 0.167167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.284042E+11 | 0.962135E+10 | 0.537310E+11 | 0.130299E+10 | 0.377013E+10 | 11196021.66 | 0.308656E+11 | 0.404919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327395E+11 | 0.968658E+10 | 0.617796E+11 | 0.150739E+10 | 0.444932E+10 | 12675672.10 | 0.594228E+10 | 0.115828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.289687E+11 | 0.840975E+10 | 0.572952E+11 | 0.138510E+10 | 0.470543E+10 | 11960507.72 | 0.173288E+10 | 0.199578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.309848E+11 | 0.785037E+10 | 0.605677E+11 | 0.147222E+10 | 0.619684E+10 | 12527707.06 | 0.211828E+09 | 0.367039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.307190E+11 | 0.722859E+10 | 0.594895E+11 | 0.144944E+10 | 0.846778E+10 | 12231776.97 | 28016725.35 | 0.565285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.288832E+11 | 0.760795E+10 | 0.583622E+11 | 0.140738E+10 | 0.913221E+10 | 12256437.81 | 0.00 | 0.651327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.322918E+11 | 0.830942E+10 | 0.617796E+11 | 0.150686E+10 | 0.102168E+11 | 12675672.10 | 0.00 | 0.722142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.292170E+11 | 0.895648E+10 | 0.572729E+11 | 0.138503E+10 | 0.702587E+10 | 11960507.72 | 38596599.06 | 0.430491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.309645E+11 | 0.102539E+11 | 0.593671E+11 | 0.143938E+10 | 0.502412E+10 | 12379742.02 | 0.295014E+10 | 0.188515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.307037E+11 | 0.107979E+11 | 0.580818E+11 | 0.141267E+10 | 0.399728E+10 | 12059151.09 | 0.887603E+10 | 0.811373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303168E+11 | 0.116259E+11 | 0.583511E+11 | 0.140888E+10 | 0.387154E+10 | 12256437.81 | 0.268391E+11 | 0.304899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.365456E+12 | 0.111737E+12 | 0.705434E+12 | 0.171168E+11 | 0.709866E+11 | 0.146559E+09 | 0.131493E+12 | 0.340904E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.284042E+11 | 0.722859E+10 | 0.537310E+11 | 0.130299E+10 | 0.377013E+10 | 11196021.66 | 0.00 | 0.167167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.327395E+11 | 0.116259E+11 | 0.617796E+11 | 0.150739E+10 | 0.102168E+11 | 12675672.10 | 0.540085E+11 | 0.722142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.109815E+11 | 0.00 | 0.115655E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.511115E+10 | 0.00 | 0.104732E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.136928E+09 | 0.00 | 0.117427E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 83441022.88 | 0.00 | 0.106669E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.108019E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.102048E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.995589E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.103428E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.990766E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 43441581.39 | 0.00 | 0.105778E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.688020E+09 | 0.00 | 0.106944E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.211330E+10 | 0.00 | 0.111951E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.191578E+11 | 0.00 | 0.128129E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.990766E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.109815E+11 | 0.00 | 0.117427E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 38257.79 | 03-JAN-08:09 | 8596.48 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 1242.18 | 03-JAN-08:20 | 6103.23 | 09-JAN-07:10 | 6.85 | 05-JAN-06:10 | 199863.23 | 09-JAN-07:10 |
February | 38257.79 | 01-FEB-08:09 | 8596.48 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 1242.18 | 01-FEB-08:20 | 5973.19 | 13-FEB-07:10 | 6.85 | 01-FEB-06:10 | 196282.74 | 13-FEB-07:10 |
March | 38257.79 | 21-MAR-07:10 | 8596.48 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 1242.18 | 21-MAR-07:19 | 7636.35 | 30-MAR-15:00 | 6.85 | 06-MAR-08:09 | 72423.43 | 23-MAR-06:10 |
April | 36650.08 | 03-APR-07:10 | 8596.48 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 1239.02 | 03-APR-07:19 | 8091.08 | 17-APR-15:50 | 6.85 | 01-APR-05:10 | 63051.86 | 07-APR-06:10 |
May | 33199.73 | 24-MAY-07:10 | 8596.48 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 1232.28 | 24-MAY-07:19 | 10533.99 | 30-MAY-15:09 | 6.85 | 01-MAY-05:10 | 19335.34 | 11-MAY-06:10 |
June | 32359.29 | 23-JUN-07:10 | 8596.48 | 01-JUN-05:10 | 45864.70 | 01-JUN-07:10 | 1230.64 | 23-JUN-07:19 | 11513.23 | 27-JUN-15:30 | 6.85 | 01-JUN-05:10 | 5163.63 | 08-JUN-06:19 |
July | 33942.18 | 27-JUL-07:10 | 8596.48 | 01-JUL-05:10 | 45864.70 | 03-JUL-07:10 | 1233.73 | 27-JUL-07:19 | 13484.40 | 07-JUL-15:00 | 6.85 | 09-JUL-16:19 | 0.00 | 01-JUL-00:10 |
August | 36263.56 | 24-AUG-07:10 | 8596.48 | 01-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 1238.27 | 24-AUG-07:19 | 14150.04 | 02-AUG-15:50 | 6.85 | 13-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 37871.25 | 29-SEP-07:10 | 8596.48 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 1241.42 | 29-SEP-07:19 | 13278.73 | 07-SEP-15:30 | 6.85 | 01-SEP-05:10 | 6788.31 | 29-SEP-06:10 |
October | 38257.79 | 19-OCT-07:10 | 8596.48 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 1242.18 | 19-OCT-07:19 | 9441.24 | 11-OCT-15:20 | 6.85 | 26-OCT-05:19 | 70019.17 | 26-OCT-06:10 |
November | 38257.79 | 01-NOV-07:10 | 8596.48 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 1242.18 | 01-NOV-07:19 | 4772.47 | 06-NOV-15:30 | 6.85 | 13-NOV-12:09 | 100670.57 | 22-NOV-07:10 |
December | 38257.79 | 06-DEC-08:09 | 8596.48 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 1242.18 | 06-DEC-08:20 | 4412.86 | 26-DEC-06:19 | 6.85 | 01-DEC-06:10 | 151587.24 | 18-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 32359.29 | 8596.48 | 45864.70 | 1230.64 | 4412.86 | 6.85 | 0.00 | |||||||
Maximum of Months | 38257.79 | 8596.48 | 45864.70 | 1242.18 | 14150.04 | 6.85 | 199863.23 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 16761.30 | 19-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21065.23 | 28-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 39059.23 | 30-MAR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42804.78 | 17-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 56166.72 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 66355.18 | 27-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 78630.70 | 07-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 76415.55 | 01-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 68908.75 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 50134.03 | 10-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23091.20 | 02-NOV-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22527.78 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 16761.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 78630.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 248775.13 | 09-JAN-07:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 6103.23 | 6.85 | 199863.23 | 0.00 | 0.00 |
February | 245064.60 | 13-FEB-07:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 5973.19 | 6.85 | 196282.74 | 0.00 | 0.00 |
March | 119840.44 | 30-MAR-15:09 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 7378.85 | 6.85 | 0.00 | 39059.23 | 0.00 |
April | 124172.35 | 17-APR-15:20 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 7965.21 | 6.85 | 0.00 | 42804.78 | 0.00 |
May | 139770.80 | 30-MAY-15:09 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 10533.99 | 6.85 | 0.00 | 55834.45 | 0.00 |
June | 151182.81 | 27-JUN-15:50 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 11457.79 | 6.85 | 0.00 | 66322.66 | 0.00 |
July | 165517.46 | 07-JUL-15:00 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 13484.40 | 6.85 | 0.00 | 78630.70 | 0.00 |
August | 163383.77 | 02-AUG-15:00 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 14146.89 | 6.85 | 0.00 | 75834.52 | 0.00 |
September | 155349.73 | 07-SEP-15:50 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 13128.43 | 6.85 | 0.00 | 68818.95 | 0.00 |
October | 132956.20 | 10-OCT-15:00 | 30461.55 | 42072.41 | 0.00 | 1224.44 | 9056.92 | 6.85 | 0.00 | 50134.03 | 0.00 |
November | 146994.77 | 22-NOV-07:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 3515.53 | 6.85 | 100670.57 | 0.00 | 0.00 |
December | 198791.42 | 18-DEC-07:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 4395.51 | 6.85 | 151587.24 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 119840.44 | 12752.77 | 21098.80 | 0.00 | 353.77 | 3515.53 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 248775.13 | 30461.55 | 42072.41 | 8596.48 | 1224.44 | 14146.89 | 6.85 | 199863.23 | 78630.70 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 42659.34 | 14-JAN-07:19 | 0.00 | 10133.87 | 30-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 49980.68 | 03-FEB-07:30 | 0.00 | 10135.32 | 01-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 8706.30 | 18-MAR-06:00 | 0.00 | 10094.64 | 02-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 10298.67 | 06-APR-06:19 | 0.00 | 9982.51 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 9855.39 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9714.76 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9614.26 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9609.12 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9700.26 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 7746.54 | 26-OCT-06:19 | 0.00 | 9843.15 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 28008.43 | 22-NOV-07:19 | 0.00 | 9967.21 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 38651.06 | 18-DEC-07:00 | 0.00 | 10071.11 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9609.12 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 49980.68 | 0.00 | 10135.32 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.16 | 0.83 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
February | 0.17 | 19.18 | 0.17 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 19.16 | 1.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.18 | 0.83 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 17.91 | 0.67 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 |
February | 0.50 | 18.57 | 0.33 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 18.40 | 0.33 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
Annual Sum or Average | 2.00 | 18.20 | 1.33 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 18.57 | 0.67 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.00 | 16.05 | 6.50 | 16.39 | 0.00 | 16.39 | 0.00 | 16.39 |
February | 11.67 | 15.92 | 4.83 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.41 | 0.50 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.55 | 2.00 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
December | 6.33 | 16.77 | 2.83 | 17.26 | 0.00 | 17.26 | 0.00 | 17.26 |
Annual Sum or Average | 35.33 | 16.14 | 14.17 | 16.53 | 4.00 | 17.35 | 2.83 | 17.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.00 | 16.95 | 6.50 | 17.26 | 3.00 | 27.55 | 2.00 | 27.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.33 | 15.51 | 2.50 | 15.69 | 0.00 | 15.69 | 0.00 | 15.69 |
February | 7.83 | 14.91 | 1.17 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.59 | 1.00 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.79 | 4.33 | 27.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.78 | 8.67 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.72 | 6.17 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.45 | 1.00 | 27.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
December | 3.83 | 15.79 | 0.67 | 15.98 | 0.00 | 15.98 | 0.00 | 15.98 |
Annual Sum or Average | 24.33 | 15.38 | 4.33 | 15.52 | 22.33 | 20.87 | 21.33 | 22.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.33 | 16.93 | 2.50 | 16.93 | 9.33 | 27.79 | 8.67 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.83 | 15.88 | 2.50 | 16.13 | 0.00 | 16.13 | 0.00 | 16.13 |
February | 5.83 | 15.33 | 1.50 | 15.51 | 0.50 | 16.26 | 0.50 | 16.93 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.39 | 0.67 | 27.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.52 | 1.17 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.58 | 3.50 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.66 | 5.00 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.57 | 1.83 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.63 | 2.83 | 27.63 |
November | 0.33 | 17.07 | 0.00 | 17.07 | 0.67 | 24.05 | 0.67 | 25.45 |
December | 1.50 | 17.38 | 0.50 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 |
Annual Sum or Average | 17.50 | 15.85 | 4.50 | 16.09 | 17.50 | 21.19 | 16.17 | 23.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.83 | 17.38 | 2.50 | 17.81 | 5.50 | 27.66 | 5.00 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.67 | 15.47 | 4.00 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
February | 7.50 | 14.87 | 2.33 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.63 | 0.50 | 27.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.80 | 1.83 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.07 | 2.83 | 28.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.21 | 4.33 | 28.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.12 | 3.33 | 28.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.58 | 1.33 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.44 | 0.17 | 27.44 |
November | 0.33 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 |
December | 3.50 | 15.78 | 1.00 | 15.92 | 0.00 | 15.92 | 0.00 | 15.92 |
Annual Sum or Average | 25.00 | 15.35 | 7.33 | 15.43 | 25.33 | 20.97 | 14.33 | 22.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.67 | 16.90 | 4.00 | 16.90 | 8.67 | 28.21 | 4.33 | 28.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 18.98 | 1.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
February | 1.67 | 19.12 | 1.33 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.40 | 0.33 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Annual Sum or Average | 3.17 | 19.10 | 2.67 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.40 | 1.33 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 17.66 | 0.17 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 |
February | 0.50 | 17.36 | 0.17 | 17.82 | 0.00 | 17.82 | 0.00 | 17.82 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.55 | 1.67 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.59 | 3.83 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.59 | 3.33 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.67 | 27.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 17.51 | 0.33 | 17.90 | 9.50 | 26.38 | 9.50 | 26.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 17.66 | 0.17 | 17.99 | 3.83 | 27.59 | 3.83 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 44.83 | 18.12 | 44.67 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 |
February | 30.17 | 18.39 | 29.83 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 |
March | 11.00 | 19.54 | 11.00 | 19.54 | 0.00 | 19.54 | 0.00 | 19.54 |
April | 4.50 | 18.83 | 4.50 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.64 | 0.83 | 24.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 24.81 | 8.17 | 24.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 25.10 | 16.50 | 25.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 25.36 | 3.83 | 25.36 |
October | 2.00 | 19.49 | 2.00 | 19.49 | 4.00 | 23.35 | 4.00 | 24.63 |
November | 10.50 | 19.43 | 10.50 | 19.43 | 1.17 | 19.85 | 1.17 | 20.22 |
December | 20.00 | 18.44 | 20.00 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
Annual Sum or Average | 123.00 | 18.53 | 122.50 | 18.53 | 34.50 | 19.37 | 34.50 | 20.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.83 | 19.54 | 44.67 | 19.54 | 16.50 | 25.36 | 16.50 | 25.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 17.64 | 0.17 | 17.97 | 0.00 | 17.97 | 0.00 | 17.97 |
February | 0.50 | 17.44 | 0.17 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.30 | 0.33 | 27.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.69 | 1.50 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.82 | 2.83 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.80 | 2.67 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.41 | 0.67 | 27.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 17.54 | 0.33 | 17.93 | 15.33 | 26.95 | 8.17 | 27.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 17.64 | 0.17 | 17.97 | 6.00 | 27.82 | 2.83 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 17.92 | 1.17 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
February | 3.67 | 16.37 | 1.67 | 16.67 | 0.00 | 16.67 | 0.00 | 16.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.28 | 0.50 | 27.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 17.70 | 0.17 | 18.02 | 0.00 | 18.02 | 0.00 | 18.02 |
Annual Sum or Average | 6.67 | 17.05 | 3.00 | 17.39 | 0.50 | 17.88 | 0.50 | 18.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 17.92 | 1.67 | 18.33 | 0.50 | 27.28 | 0.50 | 27.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 17.59 | 0.67 | 18.00 | 0.00 | 18.00 | 0.00 | 18.00 |
February | 2.50 | 15.39 | 0.33 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.38 | 0.50 | 27.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.55 | 1.33 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.83 | 3.33 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.69 | 7.00 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.80 | 4.17 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.64 | 0.83 | 27.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 17.78 | 0.17 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 |
Annual Sum or Average | 5.00 | 16.51 | 1.17 | 16.78 | 17.17 | 24.83 | 17.17 | 26.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 17.78 | 0.67 | 18.15 | 7.00 | 27.83 | 7.00 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 17.64 | 0.50 | 18.10 | 0.00 | 18.10 | 0.00 | 18.10 |
February | 1.00 | 15.16 | 0.50 | 15.07 | 0.67 | 18.87 | 0.67 | 20.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.39 | 2.00 | 27.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.52 | 4.33 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.59 | 1.17 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.59 | 3.67 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.52 | 2.00 | 27.52 |
December | 0.17 | 19.23 | 0.17 | 19.23 | 0.17 | 21.91 | 0.17 | 23.25 |
Annual Sum or Average | 2.33 | 16.69 | 1.17 | 16.91 | 14.33 | 25.43 | 14.33 | 26.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.23 | 0.50 | 19.23 | 4.33 | 27.59 | 4.33 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 17.23 | 0.50 | 17.62 | 0.00 | 17.62 | 0.00 | 17.62 |
February | 2.50 | 15.24 | 0.83 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.52 | 0.50 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.74 | 1.33 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.94 | 2.17 | 27.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.05 | 3.83 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.98 | 2.83 | 28.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.52 | 1.17 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.40 | 0.17 | 27.40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 17.80 | 0.17 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 |
Annual Sum or Average | 5.00 | 16.29 | 1.50 | 16.39 | 21.17 | 25.21 | 12.00 | 26.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 17.80 | 0.83 | 18.15 | 7.33 | 28.05 | 3.83 | 28.06 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.83 | 22.49 | 23.50 | 22.39 | 23.50 | 22.30 |
February | 423.50 | 23.10 | 7.17 | 23.07 | 5.83 | 23.04 |
March | 257.83 | 23.66 | 75.83 | 23.84 | 0.00 | 23.84 |
April | 86.50 | 23.65 | 180.67 | 24.31 | 0.00 | 24.31 |
May | 9.00 | 23.78 | 378.67 | 24.50 | 0.00 | 24.50 |
June | 0.83 | 23.81 | 430.00 | 24.38 | 0.00 | 24.38 |
July | 0.00 | 0.00 | 490.83 | 24.41 | 0.00 | 24.41 |
August | 0.00 | 0.00 | 513.83 | 24.35 | 0.00 | 24.35 |
September | 0.50 | 23.39 | 437.67 | 24.44 | 0.00 | 24.44 |
October | 58.67 | 23.51 | 206.67 | 24.39 | 0.00 | 24.39 |
November | 268.50 | 23.73 | 49.33 | 23.88 | 0.00 | 23.88 |
December | 439.83 | 23.29 | 12.00 | 23.32 | 0.00 | 23.32 |
Annual Sum or Average | 2043.00 | 23.18 | 2806.17 | 23.89 | 29.33 | 23.87 |
Minimum of Months | 0.00 | 0.00 | 7.17 | 22.39 | 0.00 | 22.30 |
Maximum of Months | 497.83 | 23.81 | 513.83 | 24.50 | 23.50 | 24.50 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.08 | 189.00 | 20.90 | 189.00 | 20.79 |
February | 451.67 | 21.74 | 81.00 | 21.55 | 81.00 | 21.41 |
March | 437.33 | 22.85 | 21.83 | 22.92 | 0.00 | 22.92 |
April | 266.50 | 23.19 | 88.83 | 23.47 | 0.00 | 23.47 |
May | 85.33 | 23.27 | 251.83 | 24.04 | 0.00 | 24.04 |
June | 33.83 | 23.47 | 377.17 | 24.20 | 0.00 | 24.20 |
July | 11.50 | 23.11 | 446.17 | 24.26 | 0.00 | 24.26 |
August | 0.00 | 0.00 | 479.50 | 24.26 | 0.00 | 24.26 |
September | 54.67 | 23.13 | 325.17 | 24.17 | 0.00 | 24.17 |
October | 288.67 | 22.96 | 87.00 | 23.24 | 0.00 | 23.24 |
November | 468.00 | 22.67 | 0.17 | 22.67 | 0.17 | 22.67 |
December | 493.83 | 21.68 | 44.50 | 21.61 | 44.50 | 21.55 |
Annual Sum or Average | 3093.33 | 22.25 | 2392.17 | 22.92 | 314.67 | 22.79 |
Minimum of Months | 0.00 | 0.00 | 0.17 | 20.90 | 0.00 | 20.79 |
Maximum of Months | 502.00 | 23.47 | 479.50 | 24.26 | 189.00 | 24.26 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.57 | 316.00 | 20.40 | 316.00 | 20.33 |
February | 452.50 | 21.20 | 147.83 | 20.96 | 147.83 | 20.82 |
March | 461.00 | 22.30 | 42.33 | 22.30 | 21.17 | 22.24 |
April | 315.00 | 22.84 | 68.33 | 23.07 | 1.17 | 23.06 |
May | 133.17 | 23.13 | 224.67 | 23.83 | 0.00 | 23.83 |
June | 43.33 | 23.30 | 361.33 | 24.16 | 0.00 | 24.16 |
July | 15.00 | 22.81 | 439.67 | 24.25 | 0.00 | 24.25 |
August | 2.17 | 23.39 | 472.17 | 24.25 | 0.00 | 24.25 |
September | 110.83 | 22.95 | 264.17 | 23.89 | 0.00 | 23.89 |
October | 377.83 | 22.46 | 60.33 | 22.67 | 1.83 | 22.66 |
November | 485.17 | 21.86 | 51.33 | 21.73 | 51.33 | 21.63 |
December | 497.00 | 21.00 | 191.17 | 20.79 | 191.17 | 20.67 |
Annual Sum or Average | 3395.00 | 21.78 | 2639.33 | 22.38 | 730.50 | 22.15 |
Minimum of Months | 2.17 | 20.57 | 42.33 | 20.40 | 0.00 | 20.33 |
Maximum of Months | 502.00 | 23.39 | 472.17 | 24.25 | 316.00 | 24.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.03 | 420.17 | 19.93 | 420.17 | 19.89 |
February | 451.33 | 20.63 | 262.17 | 20.41 | 262.17 | 20.31 |
March | 466.33 | 21.57 | 120.00 | 21.47 | 94.33 | 21.31 |
April | 331.67 | 22.30 | 108.33 | 22.56 | 31.67 | 22.48 |
May | 158.67 | 22.87 | 263.00 | 23.72 | 8.17 | 23.71 |
June | 58.83 | 23.86 | 398.67 | 24.26 | 21.17 | 24.31 |
July | 55.17 | 24.74 | 461.67 | 24.47 | 40.50 | 24.54 |
August | 42.33 | 25.00 | 494.50 | 24.39 | 37.33 | 24.45 |
September | 174.67 | 23.16 | 276.33 | 23.87 | 27.67 | 23.94 |
October | 410.83 | 21.83 | 94.00 | 22.04 | 40.17 | 21.99 |
November | 484.83 | 21.11 | 174.50 | 20.88 | 174.50 | 20.75 |
December | 497.00 | 20.30 | 343.50 | 20.12 | 343.50 | 20.05 |
Annual Sum or Average | 3633.67 | 21.36 | 3416.83 | 21.97 | 1501.33 | 21.71 |
Minimum of Months | 42.33 | 20.03 | 94.00 | 19.93 | 8.17 | 19.89 |
Maximum of Months | 502.00 | 25.00 | 494.50 | 24.47 | 420.17 | 24.54 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.15 | 401.83 | 20.04 | 401.83 | 20.00 |
February | 449.67 | 20.87 | 228.33 | 20.59 | 228.33 | 20.45 |
March | 435.17 | 21.83 | 92.50 | 21.80 | 58.00 | 21.64 |
April | 273.33 | 22.39 | 156.17 | 22.95 | 23.33 | 22.90 |
May | 138.67 | 22.99 | 309.17 | 23.96 | 17.17 | 24.01 |
June | 63.50 | 24.46 | 421.00 | 24.40 | 31.17 | 24.50 |
July | 85.83 | 25.26 | 453.33 | 24.64 | 63.50 | 24.80 |
August | 62.83 | 25.54 | 482.83 | 24.53 | 53.67 | 24.66 |
September | 166.83 | 23.07 | 307.33 | 23.91 | 29.17 | 24.01 |
October | 341.33 | 21.81 | 129.50 | 22.24 | 37.50 | 22.18 |
November | 482.67 | 21.30 | 122.50 | 21.09 | 122.50 | 20.94 |
December | 497.00 | 20.39 | 296.83 | 20.18 | 296.83 | 20.08 |
Annual Sum or Average | 3498.83 | 21.53 | 3401.33 | 22.21 | 1363.00 | 21.99 |
Minimum of Months | 62.83 | 20.15 | 92.50 | 20.04 | 17.17 | 20.00 |
Maximum of Months | 502.00 | 25.54 | 482.83 | 24.64 | 401.83 | 24.80 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 489.50 | 20.78 | 292.00 | 20.44 | 290.00 | 20.28 |
February | 402.83 | 21.10 | 204.33 | 20.93 | 187.33 | 20.74 |
March | 356.50 | 21.83 | 133.33 | 22.02 | 62.17 | 21.82 |
April | 267.17 | 22.36 | 152.00 | 22.91 | 28.33 | 22.84 |
May | 157.50 | 22.81 | 273.00 | 23.74 | 8.83 | 23.75 |
June | 75.67 | 23.77 | 387.50 | 24.24 | 24.00 | 24.31 |
July | 65.83 | 24.89 | 452.83 | 24.51 | 47.67 | 24.60 |
August | 56.33 | 25.48 | 493.17 | 24.49 | 50.83 | 24.60 |
September | 152.00 | 23.38 | 311.50 | 24.08 | 35.50 | 24.20 |
October | 288.17 | 22.04 | 183.33 | 22.83 | 38.33 | 22.85 |
November | 383.50 | 21.58 | 138.00 | 21.66 | 92.00 | 21.45 |
December | 454.67 | 20.97 | 225.00 | 20.66 | 214.17 | 20.45 |
Annual Sum or Average | 3149.67 | 21.78 | 3246.00 | 22.51 | 1079.17 | 22.29 |
Minimum of Months | 56.33 | 20.78 | 133.33 | 20.44 | 8.83 | 20.28 |
Maximum of Months | 489.50 | 25.48 | 493.17 | 24.51 | 290.00 | 24.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.18 | 379.67 | 20.03 | 379.67 | 19.97 |
February | 437.67 | 20.69 | 248.00 | 20.50 | 243.33 | 20.39 |
March | 419.50 | 21.49 | 130.00 | 21.57 | 81.67 | 21.40 |
April | 305.83 | 22.12 | 145.83 | 22.67 | 30.83 | 22.63 |
May | 187.17 | 22.68 | 264.17 | 23.63 | 15.00 | 23.68 |
June | 98.17 | 23.60 | 379.67 | 24.21 | 28.67 | 24.31 |
July | 83.50 | 24.42 | 423.17 | 24.45 | 47.00 | 24.56 |
August | 61.17 | 24.91 | 458.17 | 24.44 | 43.17 | 24.54 |
September | 196.67 | 22.91 | 261.17 | 23.76 | 32.83 | 23.87 |
October | 379.33 | 21.71 | 120.67 | 22.13 | 36.83 | 22.10 |
November | 458.50 | 21.10 | 157.33 | 20.93 | 149.17 | 20.79 |
December | 497.00 | 20.44 | 306.17 | 20.22 | 306.17 | 20.12 |
Annual Sum or Average | 3626.50 | 21.41 | 3274.00 | 22.06 | 1394.33 | 21.83 |
Minimum of Months | 61.17 | 20.18 | 120.67 | 20.03 | 15.00 | 19.97 |
Maximum of Months | 502.00 | 24.91 | 458.17 | 24.45 | 379.67 | 24.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.32 | 412.50 | 20.24 | 412.50 | 20.21 |
February | 454.00 | 20.75 | 241.33 | 20.58 | 241.33 | 20.49 |
March | 502.00 | 21.55 | 77.83 | 21.42 | 74.17 | 21.32 |
April | 432.33 | 22.23 | 38.33 | 22.24 | 23.17 | 22.19 |
May | 247.83 | 23.02 | 172.00 | 23.52 | 11.17 | 23.56 |
June | 50.83 | 23.84 | 382.50 | 24.21 | 12.00 | 24.24 |
July | 31.50 | 24.58 | 470.17 | 24.36 | 22.17 | 24.40 |
August | 18.17 | 25.39 | 505.00 | 24.34 | 18.17 | 24.37 |
September | 81.50 | 23.66 | 315.83 | 24.19 | 18.83 | 24.25 |
October | 381.50 | 22.52 | 80.33 | 22.79 | 12.33 | 22.83 |
November | 478.17 | 21.79 | 52.67 | 21.68 | 51.50 | 21.57 |
December | 497.00 | 20.81 | 258.67 | 20.66 | 258.67 | 20.59 |
Annual Sum or Average | 3676.83 | 21.62 | 3007.17 | 22.18 | 1156.00 | 21.96 |
Minimum of Months | 18.17 | 20.32 | 38.33 | 20.24 | 11.17 | 20.21 |
Maximum of Months | 502.00 | 25.39 | 505.00 | 24.36 | 412.50 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.49 | 372.83 | 20.39 | 372.83 | 20.35 |
February | 451.83 | 21.12 | 195.83 | 20.88 | 195.83 | 20.75 |
March | 476.33 | 22.05 | 42.17 | 21.99 | 30.67 | 21.90 |
April | 318.17 | 22.51 | 88.17 | 22.85 | 10.83 | 22.84 |
May | 164.00 | 23.14 | 273.67 | 23.96 | 13.00 | 24.02 |
June | 32.50 | 24.62 | 431.67 | 24.39 | 15.67 | 24.45 |
July | 53.17 | 25.34 | 471.67 | 24.60 | 39.17 | 24.71 |
August | 31.33 | 26.21 | 508.33 | 24.52 | 31.33 | 24.61 |
September | 69.33 | 23.86 | 373.00 | 24.33 | 22.00 | 24.41 |
October | 279.17 | 22.56 | 143.50 | 23.15 | 12.50 | 23.18 |
November | 454.00 | 22.13 | 35.17 | 22.09 | 26.00 | 22.01 |
December | 497.00 | 21.00 | 192.67 | 20.83 | 192.67 | 20.72 |
Annual Sum or Average | 3328.83 | 21.84 | 3128.67 | 22.57 | 962.50 | 22.38 |
Minimum of Months | 31.33 | 20.49 | 35.17 | 20.39 | 10.83 | 20.35 |
Maximum of Months | 502.00 | 26.21 | 508.33 | 24.60 | 372.83 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.17 | 20.68 | 272.50 | 20.41 | 268.67 | 20.26 |
February | 413.50 | 21.05 | 168.83 | 20.87 | 157.00 | 20.68 |
March | 419.50 | 21.93 | 78.50 | 22.04 | 35.17 | 21.92 |
April | 352.17 | 22.30 | 85.83 | 22.58 | 17.50 | 22.53 |
May | 234.50 | 22.81 | 201.67 | 23.48 | 19.67 | 23.52 |
June | 108.83 | 23.56 | 389.83 | 24.09 | 55.83 | 24.08 |
July | 91.33 | 24.05 | 470.83 | 24.32 | 80.00 | 24.30 |
August | 98.83 | 24.43 | 508.67 | 24.41 | 97.83 | 24.42 |
September | 97.67 | 23.66 | 389.00 | 24.29 | 43.50 | 24.34 |
October | 238.50 | 22.58 | 212.67 | 23.47 | 35.00 | 23.53 |
November | 359.83 | 22.20 | 77.33 | 22.54 | 14.50 | 22.46 |
December | 460.17 | 21.36 | 111.17 | 21.21 | 94.00 | 21.01 |
Annual Sum or Average | 3371.00 | 21.97 | 2966.83 | 22.70 | 918.67 | 22.55 |
Minimum of Months | 91.33 | 20.68 | 77.33 | 20.41 | 14.50 | 20.26 |
Maximum of Months | 496.17 | 24.43 | 508.67 | 24.41 | 268.67 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.49 | 363.50 | 20.37 | 363.50 | 20.32 |
February | 444.67 | 20.94 | 204.00 | 20.74 | 202.83 | 20.63 |
March | 453.00 | 21.83 | 69.67 | 21.86 | 42.67 | 21.75 |
April | 351.67 | 22.43 | 82.17 | 22.75 | 11.67 | 22.74 |
May | 190.67 | 23.05 | 237.67 | 23.78 | 13.00 | 23.83 |
June | 50.00 | 24.03 | 402.33 | 24.32 | 15.50 | 24.38 |
July | 48.00 | 25.06 | 462.50 | 24.50 | 34.67 | 24.58 |
August | 28.50 | 26.14 | 505.33 | 24.49 | 28.50 | 24.58 |
September | 74.17 | 23.75 | 366.00 | 24.31 | 21.67 | 24.38 |
October | 303.33 | 22.55 | 133.00 | 23.09 | 12.67 | 23.12 |
November | 442.50 | 21.96 | 50.00 | 21.93 | 36.50 | 21.84 |
December | 497.00 | 21.01 | 202.83 | 20.82 | 202.83 | 20.72 |
Annual Sum or Average | 3385.50 | 21.76 | 3079.00 | 22.48 | 986.00 | 22.28 |
Minimum of Months | 28.50 | 20.49 | 50.00 | 20.37 | 11.67 | 20.32 |
Maximum of Months | 502.00 | 26.14 | 505.33 | 24.50 | 363.50 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.26 | 399.33 | 20.15 | 399.33 | 20.11 |
February | 451.00 | 20.86 | 213.67 | 20.63 | 213.67 | 20.51 |
March | 461.33 | 21.93 | 76.67 | 21.90 | 49.50 | 21.77 |
April | 308.17 | 22.61 | 91.00 | 22.92 | 10.83 | 22.90 |
May | 118.83 | 23.14 | 286.83 | 23.94 | 3.50 | 23.95 |
June | 37.83 | 24.14 | 420.33 | 24.30 | 16.00 | 24.33 |
July | 36.83 | 24.83 | 476.33 | 24.45 | 30.00 | 24.49 |
August | 28.17 | 25.13 | 506.33 | 24.38 | 28.17 | 24.42 |
September | 111.00 | 23.55 | 305.50 | 24.12 | 27.00 | 24.20 |
October | 389.00 | 22.26 | 83.33 | 22.53 | 19.17 | 22.55 |
November | 480.17 | 21.57 | 88.00 | 21.39 | 88.00 | 21.26 |
December | 497.00 | 20.65 | 280.00 | 20.46 | 280.00 | 20.37 |
Annual Sum or Average | 3421.33 | 21.58 | 3227.33 | 22.25 | 1165.17 | 22.01 |
Minimum of Months | 28.17 | 20.26 | 76.67 | 20.15 | 3.50 | 20.11 |
Maximum of Months | 502.00 | 25.13 | 506.33 | 24.45 | 399.33 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.29 | 318.50 | 20.16 | 318.50 | 20.11 |
February | 374.33 | 20.98 | 163.17 | 20.71 | 162.83 | 20.57 |
March | 368.83 | 22.04 | 53.50 | 22.07 | 26.17 | 21.97 |
April | 231.67 | 22.58 | 111.33 | 23.15 | 12.00 | 23.15 |
May | 116.50 | 23.27 | 251.17 | 24.15 | 13.17 | 24.23 |
June | 43.67 | 24.87 | 358.83 | 24.50 | 26.00 | 24.60 |
July | 63.00 | 25.48 | 396.33 | 24.72 | 50.00 | 24.86 |
August | 43.33 | 25.82 | 415.50 | 24.59 | 40.83 | 24.71 |
September | 125.00 | 23.50 | 259.00 | 24.17 | 30.50 | 24.29 |
October | 291.67 | 22.14 | 96.50 | 22.64 | 18.17 | 22.65 |
November | 401.17 | 21.61 | 61.17 | 21.48 | 56.33 | 21.35 |
December | 422.00 | 20.65 | 219.67 | 20.44 | 219.67 | 20.34 |
Annual Sum or Average | 2908.17 | 21.72 | 2704.67 | 22.43 | 974.17 | 22.24 |
Minimum of Months | 43.33 | 20.29 | 53.50 | 20.16 | 12.00 | 20.11 |
Maximum of Months | 427.00 | 25.82 | 415.50 | 24.72 | 318.50 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 472.17 | 21.04 | 254.33 | 20.73 | 250.00 | 20.55 |
February | 393.33 | 21.41 | 147.67 | 21.28 | 130.00 | 21.08 |
March | 335.17 | 22.24 | 107.17 | 22.56 | 26.50 | 22.44 |
April | 229.67 | 22.69 | 144.50 | 23.31 | 10.67 | 23.31 |
May | 110.67 | 23.09 | 299.33 | 24.00 | 3.67 | 24.01 |
June | 49.17 | 24.07 | 413.33 | 24.30 | 18.17 | 24.35 |
July | 43.00 | 25.14 | 474.00 | 24.50 | 36.17 | 24.57 |
August | 46.00 | 25.81 | 507.67 | 24.51 | 46.00 | 24.61 |
September | 96.17 | 23.96 | 344.17 | 24.33 | 33.50 | 24.45 |
October | 254.83 | 22.50 | 199.67 | 23.32 | 26.50 | 23.38 |
November | 355.83 | 22.07 | 97.67 | 22.32 | 39.33 | 22.18 |
December | 433.83 | 21.36 | 153.67 | 21.12 | 140.50 | 20.91 |
Annual Sum or Average | 2819.83 | 22.05 | 3143.17 | 22.88 | 761.00 | 22.71 |
Minimum of Months | 43.00 | 21.04 | 97.67 | 20.73 | 3.67 | 20.55 |
Maximum of Months | 472.17 | 25.81 | 507.67 | 24.51 | 250.00 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.42 | 351.00 | 20.26 | 351.00 | 20.19 |
February | 435.83 | 20.92 | 195.50 | 20.73 | 190.50 | 20.60 |
March | 406.00 | 21.81 | 95.00 | 21.98 | 41.50 | 21.86 |
April | 278.83 | 22.47 | 140.00 | 23.05 | 15.17 | 23.07 |
May | 144.00 | 22.99 | 294.83 | 23.91 | 9.33 | 23.95 |
June | 65.83 | 24.10 | 405.67 | 24.33 | 24.83 | 24.41 |
July | 59.17 | 25.02 | 453.17 | 24.50 | 43.17 | 24.61 |
August | 42.50 | 25.52 | 493.00 | 24.45 | 37.83 | 24.54 |
September | 145.67 | 23.35 | 301.33 | 24.06 | 31.67 | 24.17 |
October | 354.50 | 22.10 | 116.17 | 22.60 | 18.67 | 22.62 |
November | 451.67 | 21.52 | 87.83 | 21.43 | 76.67 | 21.30 |
December | 495.67 | 20.78 | 240.67 | 20.56 | 240.67 | 20.45 |
Annual Sum or Average | 3381.67 | 21.65 | 3174.17 | 22.38 | 1081.00 | 22.19 |
Minimum of Months | 42.50 | 20.42 | 87.83 | 20.26 | 9.33 | 20.19 |
Maximum of Months | 502.00 | 25.52 | 493.00 | 24.50 | 351.00 | 24.61 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.50073 | 26.87814 | -0.1696 | 6.69304 |
February | 454.00000 | 23.17624 | 27.27080 | 0.01955 | 6.09259 |
March | 514.00000 | 23.96868 | 30.64486 | 0.27299 | 6.96382 |
April | 485.00000 | 24.22843 | 35.38388 | 0.38550 | 8.43046 |
May | 508.00000 | 24.38261 | 41.77189 | -0.3667 | 8.31443 |
June | 496.00000 | 24.34757 | 43.98005 | -0.3265 | 7.70366 |
July | 497.00000 | 24.40256 | 46.15225 | -0.2904 | 7.23565 |
August | 514.00000 | 24.35309 | 46.60876 | -0.2920 | 7.21512 |
September | 485.00000 | 24.39664 | 44.53032 | -0.3168 | 7.62898 |
October | 502.00000 | 24.23445 | 37.98257 | 0.41172 | 8.84746 |
November | 489.00000 | 23.99182 | 28.85306 | 0.26071 | 6.80780 |
December | 497.00000 | 23.38418 | 28.51304 | 0.08056 | 5.74841 |
Annual Sum or Average | 5943.00000 | 23.95228 | 36.62456 | -0.0288 | 7.31466 |
Minimum of Months | 454.00000 | 22.50073 | 26.87814 | -0.3667 | 5.74841 |
Maximum of Months | 514.00000 | 24.40256 | 46.60876 | 0.41172 | 8.84746 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.08069 | 28.38306 | -0.4952 | 11.22312 |
February | 454.00000 | 21.75414 | 29.28637 | -0.3025 | 8.54189 |
March | 514.00000 | 23.03151 | 32.98508 | 0.05911 | 6.06555 |
April | 485.00000 | 23.62394 | 37.47206 | 0.24666 | 6.89941 |
May | 508.00000 | 23.99615 | 43.43264 | -0.4988 | 10.76587 |
June | 496.00000 | 24.14536 | 45.22876 | -0.4062 | 8.95925 |
July | 497.00000 | 24.21765 | 47.42896 | -0.3628 | 8.17986 |
August | 514.00000 | 24.22390 | 47.74991 | -0.3514 | 7.92367 |
September | 485.00000 | 24.08181 | 45.90248 | -0.4408 | 9.69308 |
October | 502.00000 | 23.43584 | 40.49359 | 0.21765 | 6.78981 |
November | 489.00000 | 22.72285 | 31.60752 | -0.0348 | 5.89250 |
December | 497.00000 | 21.69460 | 31.27493 | -0.3028 | 7.89511 |
Annual Sum or Average | 5943.00000 | 23.17790 | 38.51181 | -0.2227 | 8.23521 |
Minimum of Months | 454.00000 | 21.08069 | 28.38306 | -0.4988 | 5.89250 |
Maximum of Months | 514.00000 | 24.22390 | 47.74991 | 0.24666 | 11.22312 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.56821 | 27.33955 | -0.6519 | 16.13554 |
February | 454.00000 | 21.20638 | 29.73369 | -0.4518 | 11.58437 |
March | 514.00000 | 22.46969 | 33.50354 | -0.0766 | 6.76655 |
April | 485.00000 | 23.27333 | 37.55239 | 0.16381 | 6.69838 |
May | 508.00000 | 23.85381 | 43.06324 | -0.5421 | 12.04712 |
June | 496.00000 | 24.10154 | 44.93542 | -0.4107 | 9.17756 |
July | 497.00000 | 24.20921 | 47.22186 | -0.3533 | 8.12960 |
August | 514.00000 | 24.20973 | 47.59150 | -0.3443 | 7.82628 |
September | 485.00000 | 23.88588 | 45.81377 | -0.5094 | 11.44165 |
October | 502.00000 | 22.84529 | 41.48947 | 0.07294 | 6.51682 |
November | 489.00000 | 21.87160 | 32.72636 | -0.2445 | 7.50454 |
December | 497.00000 | 21.00080 | 31.61814 | -0.4953 | 11.70310 |
Annual Sum or Average | 5943.00000 | 22.80387 | 38.61980 | -0.3197 | 9.61265 |
Minimum of Months | 454.00000 | 20.56821 | 27.33955 | -0.6519 | 6.51682 |
Maximum of Months | 514.00000 | 24.20973 | 47.59150 | 0.16381 | 16.13554 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.03088 | 29.05639 | -0.8456 | 23.10080 |
February | 454.00000 | 20.65270 | 31.09548 | -0.6346 | 16.55614 |
March | 514.00000 | 21.79710 | 35.87625 | -0.2465 | 9.04668 |
April | 485.00000 | 22.85589 | 40.67576 | 0.07390 | 7.59840 |
May | 508.00000 | 23.76240 | 45.96819 | -0.5481 | 13.32954 |
June | 496.00000 | 24.17768 | 47.27616 | -0.3357 | 8.62232 |
July | 497.00000 | 24.35658 | 50.64229 | -0.2429 | 7.42632 |
August | 514.00000 | 24.30743 | 51.18575 | -0.2537 | 7.15900 |
September | 485.00000 | 23.79214 | 49.76013 | -0.5182 | 12.85561 |
October | 502.00000 | 22.21965 | 46.09273 | -0.0706 | 7.58199 |
November | 489.00000 | 21.13281 | 36.03823 | -0.4393 | 11.13204 |
December | 497.00000 | 20.30079 | 32.83786 | -0.7106 | 18.43539 |
Annual Sum or Average | 5943.00000 | 22.46344 | 41.45493 | -0.3961 | 11.86506 |
Minimum of Months | 454.00000 | 20.03088 | 29.05639 | -0.8456 | 7.15900 |
Maximum of Months | 514.00000 | 24.35658 | 51.18575 | 0.07390 | 23.10080 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.14625 | 28.75972 | -0.7951 | 21.03431 |
February | 454.00000 | 20.90413 | 30.55375 | -0.5490 | 14.87503 |
March | 514.00000 | 22.15636 | 35.01012 | -0.1362 | 8.08558 |
April | 485.00000 | 23.16289 | 39.60375 | 0.18395 | 8.23229 |
May | 508.00000 | 23.89248 | 44.94639 | -0.4411 | 12.06940 |
June | 496.00000 | 24.24167 | 46.56102 | -0.2481 | 8.01243 |
July | 497.00000 | 24.39891 | 49.77728 | -0.1608 | 7.71234 |
August | 514.00000 | 24.33624 | 50.39780 | -0.1804 | 7.13275 |
September | 485.00000 | 23.79188 | 48.98354 | -0.4562 | 12.60991 |
October | 502.00000 | 22.53516 | 44.82360 | 0.02877 | 7.99106 |
November | 489.00000 | 21.33360 | 35.37125 | -0.3685 | 9.84651 |
December | 497.00000 | 20.38540 | 32.56506 | -0.6648 | 16.86434 |
Annual Sum or Average | 5943.00000 | 22.62123 | 40.69030 | -0.3140 | 11.17107 |
Minimum of Months | 454.00000 | 20.14625 | 28.75972 | -0.7951 | 7.13275 |
Maximum of Months | 514.00000 | 24.39891 | 50.39780 | 0.18395 | 21.03431 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.87462 | 27.86566 | -0.5924 | 17.28656 |
February | 454.00000 | 21.49829 | 29.68762 | -0.3920 | 13.15388 |
March | 514.00000 | 22.57805 | 34.01420 | -0.0369 | 8.76033 |
April | 485.00000 | 23.17809 | 39.50750 | 0.17159 | 8.45785 |
May | 508.00000 | 23.77562 | 45.62509 | -0.5246 | 13.28960 |
June | 496.00000 | 24.13720 | 47.27475 | -0.3430 | 9.09356 |
July | 497.00000 | 24.35028 | 50.51128 | -0.2356 | 7.63063 |
August | 514.00000 | 24.34270 | 50.72338 | -0.2094 | 7.10674 |
September | 485.00000 | 23.93789 | 48.68905 | -0.4193 | 11.77783 |
October | 502.00000 | 22.97356 | 43.44270 | 0.14569 | 9.23748 |
November | 489.00000 | 22.20581 | 33.53059 | -0.1509 | 9.65622 |
December | 497.00000 | 21.24940 | 31.22660 | -0.4378 | 13.76701 |
Annual Sum or Average | 5943.00000 | 22.93661 | 40.25769 | -0.2514 | 10.74793 |
Minimum of Months | 454.00000 | 20.87462 | 27.86566 | -0.5924 | 7.10674 |
Maximum of Months | 514.00000 | 24.35028 | 50.72338 | 0.17159 | 17.28656 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.17740 | 28.48794 | -0.7936 | 21.35350 |
February | 454.00000 | 20.82374 | 30.41519 | -0.5749 | 15.52027 |
March | 514.00000 | 21.98920 | 34.96740 | -0.1726 | 9.18856 |
April | 485.00000 | 22.87211 | 40.09936 | 0.12024 | 8.48221 |
May | 508.00000 | 23.60882 | 45.67179 | -0.5357 | 14.48193 |
June | 496.00000 | 24.06767 | 47.12029 | -0.3156 | 9.54254 |
July | 497.00000 | 24.24659 | 50.39133 | -0.2259 | 8.24925 |
August | 514.00000 | 24.24991 | 50.71536 | -0.2148 | 7.58079 |
September | 485.00000 | 23.63463 | 49.44166 | -0.5104 | 14.13672 |
October | 502.00000 | 22.29956 | 45.22375 | -0.0235 | 8.17527 |
November | 489.00000 | 21.29983 | 35.16715 | -0.3815 | 10.76959 |
December | 497.00000 | 20.43832 | 32.30577 | -0.6622 | 17.09625 |
Annual Sum or Average | 5943.00000 | 22.48947 | 40.91372 | -0.3561 | 12.01619 |
Minimum of Months | 454.00000 | 20.17740 | 28.48794 | -0.7936 | 7.58079 |
Maximum of Months | 514.00000 | 24.24991 | 50.71536 | 0.12024 | 21.35350 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.31984 | 28.97649 | -0.7584 | 18.91108 |
February | 454.00000 | 20.75065 | 31.35524 | -0.5981 | 14.57367 |
March | 514.00000 | 21.59895 | 36.79430 | -0.2948 | 8.33528 |
April | 485.00000 | 22.41794 | 42.15331 | -0.0457 | 6.68984 |
May | 508.00000 | 23.55859 | 47.30453 | -0.6586 | 15.66855 |
June | 496.00000 | 24.13436 | 47.08455 | -0.3940 | 8.92671 |
July | 497.00000 | 24.30214 | 49.69306 | -0.2995 | 7.44200 |
August | 514.00000 | 24.29183 | 49.90380 | -0.2893 | 7.18397 |
September | 485.00000 | 24.07159 | 48.58655 | -0.4285 | 9.81997 |
October | 502.00000 | 22.87101 | 44.24192 | 0.09614 | 6.65776 |
November | 489.00000 | 21.84029 | 34.74738 | -0.2384 | 7.60016 |
December | 497.00000 | 20.80668 | 32.29575 | -0.5492 | 12.65373 |
Annual Sum or Average | 5943.00000 | 22.59385 | 41.17232 | -0.3706 | 10.35293 |
Minimum of Months | 454.00000 | 20.31984 | 28.97649 | -0.7584 | 6.65776 |
Maximum of Months | 514.00000 | 24.30214 | 49.90380 | 0.09614 | 18.91108 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.49014 | 29.01891 | -0.6941 | 16.70796 |
February | 454.00000 | 21.14007 | 31.04005 | -0.4828 | 12.38852 |
March | 514.00000 | 22.18759 | 35.88166 | -0.1341 | 7.10103 |
April | 485.00000 | 23.06660 | 40.63248 | 0.13444 | 7.15932 |
May | 508.00000 | 23.90257 | 45.84341 | -0.4889 | 12.30726 |
June | 496.00000 | 24.28767 | 46.22923 | -0.2780 | 7.60499 |
July | 497.00000 | 24.45111 | 48.81978 | -0.1835 | 7.05958 |
August | 514.00000 | 24.40368 | 49.12470 | -0.1875 | 6.67904 |
September | 485.00000 | 24.18326 | 47.83620 | -0.3320 | 8.83273 |
October | 502.00000 | 23.27563 | 42.98649 | 0.21567 | 7.77425 |
November | 489.00000 | 22.27195 | 34.15206 | -0.1196 | 6.85653 |
December | 497.00000 | 21.00456 | 32.20915 | -0.4772 | 11.04681 |
Annual Sum or Average | 5943.00000 | 22.90152 | 40.38858 | -0.2513 | 9.27637 |
Minimum of Months | 454.00000 | 20.49014 | 29.01891 | -0.6941 | 6.67904 |
Maximum of Months | 514.00000 | 24.45111 | 49.12470 | 0.21567 | 16.70796 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.74408 | 26.84565 | -0.5748 | 15.10498 |
February | 454.00000 | 21.37341 | 29.04923 | -0.3871 | 11.86397 |
March | 514.00000 | 22.37638 | 34.64028 | -0.0695 | 7.58047 |
April | 485.00000 | 22.82053 | 40.65273 | 0.07439 | 7.30063 |
May | 508.00000 | 23.52299 | 48.79877 | -0.6335 | 15.62989 |
June | 496.00000 | 24.06640 | 50.62728 | -0.3854 | 9.25123 |
July | 497.00000 | 24.31317 | 54.08092 | -0.2559 | 7.16749 |
August | 514.00000 | 24.39615 | 54.54948 | -0.1858 | 6.45030 |
September | 485.00000 | 24.18896 | 50.27530 | -0.3121 | 8.87707 |
October | 502.00000 | 23.49845 | 42.58891 | 0.30292 | 9.34161 |
November | 489.00000 | 22.82009 | 31.97461 | 0.04431 | 7.82949 |
December | 497.00000 | 21.58767 | 30.03516 | -0.2954 | 9.64132 |
Annual Sum or Average | 5943.00000 | 22.98710 | 41.28055 | -0.2228 | 9.66307 |
Minimum of Months | 454.00000 | 20.74408 | 26.84565 | -0.6335 | 6.45030 |
Maximum of Months | 514.00000 | 24.39615 | 54.54948 | 0.30292 | 15.62989 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.49190 | 28.90791 | -0.6966 | 17.03680 |
February | 454.00000 | 21.00913 | 31.07149 | -0.5169 | 13.08553 |
March | 514.00000 | 22.11542 | 35.76680 | -0.1494 | 7.63030 |
April | 485.00000 | 22.90689 | 40.88878 | 0.09740 | 7.13248 |
May | 508.00000 | 23.75158 | 46.36978 | -0.5466 | 13.32059 |
June | 496.00000 | 24.20992 | 46.64765 | -0.3174 | 8.25627 |
July | 497.00000 | 24.36597 | 49.29509 | -0.2286 | 7.26629 |
August | 514.00000 | 24.38824 | 49.31367 | -0.2004 | 6.75855 |
September | 485.00000 | 24.16674 | 48.02319 | -0.3461 | 9.03045 |
October | 502.00000 | 23.18145 | 43.29929 | 0.19295 | 7.58296 |
November | 489.00000 | 22.17463 | 34.11136 | -0.1427 | 7.23163 |
December | 497.00000 | 21.00661 | 32.13701 | -0.4836 | 11.35086 |
Annual Sum or Average | 5943.00000 | 22.82740 | 40.56090 | -0.2771 | 9.62238 |
Minimum of Months | 454.00000 | 20.49190 | 28.90791 | -0.6966 | 6.75855 |
Maximum of Months | 514.00000 | 24.38824 | 49.31367 | 0.19295 | 17.03680 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.26120 | 28.94799 | -0.7562 | 19.45585 |
February | 454.00000 | 20.88493 | 30.90209 | -0.5484 | 14.10220 |
March | 514.00000 | 22.13672 | 35.59973 | -0.1520 | 7.58892 |
April | 485.00000 | 23.14116 | 40.48243 | 0.14405 | 7.20917 |
May | 508.00000 | 23.92743 | 45.99120 | -0.5001 | 11.45632 |
June | 496.00000 | 24.23378 | 47.21819 | -0.3301 | 8.04697 |
July | 497.00000 | 24.37788 | 50.38732 | -0.2515 | 7.13245 |
August | 514.00000 | 24.32898 | 50.91937 | -0.2614 | 7.04294 |
September | 485.00000 | 23.99515 | 49.44669 | -0.4515 | 10.62683 |
October | 502.00000 | 22.64205 | 45.18362 | 0.04098 | 6.89259 |
November | 489.00000 | 21.60768 | 35.30063 | -0.3016 | 8.58342 |
December | 497.00000 | 20.65186 | 32.34484 | -0.5917 | 14.38128 |
Annual Sum or Average | 5943.00000 | 22.69640 | 41.13978 | -0.3288 | 10.18026 |
Minimum of Months | 454.00000 | 20.26120 | 28.94799 | -0.7562 | 6.89259 |
Maximum of Months | 514.00000 | 24.37788 | 50.91937 | 0.14405 | 19.45585 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.28895 | 27.93896 | -0.7361 | 18.54118 |
February | 385.00000 | 21.07316 | 29.92375 | -0.4884 | 13.15241 |
March | 433.00000 | 22.34034 | 34.24665 | -0.0884 | 7.33468 |
April | 410.00000 | 23.30544 | 39.35944 | 0.20947 | 7.97277 |
May | 430.00000 | 24.01946 | 44.74176 | -0.4270 | 11.40458 |
June | 418.00000 | 24.33395 | 46.39070 | -0.2573 | 7.89947 |
July | 422.00000 | 24.50900 | 49.51768 | -0.1666 | 7.51394 |
August | 433.00000 | 24.42432 | 50.24006 | -0.1918 | 7.19272 |
September | 410.00000 | 23.98565 | 48.72131 | -0.4133 | 11.11322 |
October | 427.00000 | 22.78409 | 43.91893 | 0.09215 | 7.57649 |
November | 417.00000 | 21.70868 | 34.15399 | -0.2644 | 8.20917 |
December | 422.00000 | 20.64764 | 31.55091 | -0.5775 | 13.75132 |
Annual Sum or Average | 5034.00000 | 22.79547 | 40.12381 | -0.2748 | 10.11813 |
Minimum of Months | 385.00000 | 20.28895 | 27.93896 | -0.7361 | 7.19272 |
Maximum of Months | 433.00000 | 24.50900 | 50.24006 | 0.20947 | 18.54118 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.24353 | 27.67514 | -0.4790 | 14.19258 |
February | 454.00000 | 21.83394 | 29.43066 | -0.2893 | 10.97499 |
March | 514.00000 | 22.95108 | 33.66076 | 0.06137 | 7.81026 |
April | 485.00000 | 23.48638 | 39.25319 | 0.24458 | 8.19985 |
May | 508.00000 | 23.97238 | 45.63386 | -0.4687 | 11.14445 |
June | 496.00000 | 24.22226 | 47.21631 | -0.3296 | 8.27091 |
July | 497.00000 | 24.40130 | 50.26792 | -0.2363 | 7.19436 |
August | 514.00000 | 24.38578 | 50.47184 | -0.2121 | 6.89821 |
September | 485.00000 | 24.15402 | 48.40758 | -0.3511 | 9.56522 |
October | 502.00000 | 23.36050 | 42.58299 | 0.24744 | 9.00514 |
November | 489.00000 | 22.72639 | 32.69368 | -0.0087 | 8.27723 |
December | 497.00000 | 21.72457 | 30.57301 | -0.2989 | 10.62365 |
Annual Sum or Average | 5943.00000 | 23.21564 | 39.90530 | -0.1764 | 9.33384 |
Minimum of Months | 454.00000 | 21.24353 | 27.67514 | -0.4790 | 6.89821 |
Maximum of Months | 514.00000 | 24.40130 | 50.47184 | 0.24744 | 14.19258 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.42055 | 28.47810 | -0.7022 | 17.90245 |
February | 454.00000 | 21.05725 | 30.33244 | -0.4894 | 13.17210 |
March | 514.00000 | 22.31822 | 34.78555 | -0.0809 | 7.92030 |
April | 485.00000 | 23.19156 | 39.88460 | 0.19593 | 8.13175 |
May | 508.00000 | 23.84538 | 45.65137 | -0.4696 | 11.90738 |
June | 496.00000 | 24.18229 | 47.03880 | -0.2944 | 8.41888 |
July | 497.00000 | 24.32773 | 50.12345 | -0.2186 | 7.54494 |
August | 514.00000 | 24.32124 | 50.46627 | -0.2096 | 7.12129 |
September | 485.00000 | 23.91053 | 49.13378 | -0.4251 | 11.19374 |
October | 502.00000 | 22.70255 | 44.46355 | 0.08375 | 7.60261 |
November | 489.00000 | 21.73235 | 34.60781 | -0.2527 | 8.50601 |
December | 497.00000 | 20.78784 | 31.91885 | -0.5444 | 13.30462 |
Annual Sum or Average | 5943.00000 | 22.74649 | 40.65310 | -0.2828 | 10.20264 |
Minimum of Months | 454.00000 | 20.42055 | 28.47810 | -0.7022 | 7.12129 |
Maximum of Months | 514.00000 | 24.32773 | 50.46627 | 0.19593 | 17.90245 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.207129E+10 | 0.554398E+09 | 52.83 | 0.127632E+10 | 0.794962E+09 | 0.00 | 0.61 | 19-JAN-20:00 | 0.00 | 01-JAN-00:05 | 21943.07 | 19-JAN-20:00 | 15031.49 | 31-JAN-15:00 | 10532.64 | 19-JAN-16:00 | 5591.55 | 19-JAN-20:00 | 0.00 |
February | 0.507757E+10 | 0.135736E+10 | 131.58 | 0.413709E+10 | 0.940481E+09 | 0.00 | 0.84 | 28-FEB-14:00 | 0.00 | 01-FEB-00:10 | 31838.46 | 28-FEB-14:00 | 31838.46 | 28-FEB-14:00 | 9080.41 | 18-FEB-16:20 | 7845.99 | 28-FEB-14:00 | 0.00 |
March | 0.156883E+11 | 0.400957E+10 | 267.83 | 0.121579E+11 | 0.353043E+10 | 0.00 | 1.00 | 29-MAR-15:40 | 0.00 | 01-MAR-00:10 | 50142.09 | 30-MAR-15:10 | 50142.09 | 30-MAR-15:10 | 15820.71 | 31-MAR-11:30 | 12634.62 | 30-MAR-15:10 | 0.00 |
April | 0.266429E+11 | 0.671581E+10 | 328.75 | 0.216743E+11 | 0.496860E+10 | 0.00 | 1.00 | 04-APR-13:40 | 0.00 | 01-APR-00:10 | 56387.77 | 17-APR-15:20 | 56387.77 | 17-APR-15:20 | 16874.58 | 04-APR-07:10 | 14648.46 | 17-APR-15:20 | 0.00 |
May | 0.502870E+11 | 0.124432E+11 | 408.78 | 0.379620E+11 | 0.123250E+11 | 0.00 | 1.00 | 02-MAY-12:50 | 0.00 | 01-MAY-00:10 | 70198.26 | 30-MAY-12:00 | 55602.23 | 30-MAY-15:10 | 20352.26 | 22-MAY-05:13 | 18395.36 | 30-MAY-15:10 | 0.00 |
June | 0.756851E+11 | 0.194471E+11 | 433.31 | 0.569592E+11 | 0.187259E+11 | 0.00 | 1.00 | 01-JUN-05:13 | 0.00 | 01-JUN-00:10 | 85294.90 | 28-JUN-11:50 | 61189.18 | 06-JUN-15:50 | 27828.16 | 27-JUN-12:00 | 23079.96 | 23-JUN-12:00 | 0.00 |
July | 0.864519E+11 | 0.224342E+11 | 437.78 | 0.618014E+11 | 0.246505E+11 | 0.00 | 1.00 | 01-JUL-05:13 | 0.00 | 01-JUL-00:10 | 93600.12 | 07-JUL-12:03 | 69463.54 | 07-JUL-04:02 | 32657.44 | 26-JUL-12:00 | 26520.79 | 07-JUL-12:03 | 0.00 |
August | 0.988962E+11 | 0.253673E+11 | 463.82 | 0.692370E+11 | 0.296591E+11 | 0.00 | 1.00 | 01-AUG-05:13 | 0.00 | 01-AUG-00:10 | 94826.33 | 19-AUG-04:02 | 78944.36 | 14-AUG-04:02 | 32466.80 | 24-AUG-06:05 | 25819.37 | 18-AUG-12:02 | 0.00 |
September | 0.632565E+11 | 0.155722E+11 | 410.16 | 0.467305E+11 | 0.165260E+11 | 0.00 | 1.00 | 01-SEP-05:13 | 0.00 | 01-SEP-00:10 | 89089.95 | 06-SEP-12:03 | 66189.08 | 07-SEP-15:30 | 26220.96 | 06-SEP-12:03 | 23850.18 | 07-SEP-16:00 | 0.00 |
October | 0.280203E+11 | 0.690942E+10 | 301.01 | 0.207091E+11 | 0.731119E+10 | 0.00 | 1.00 | 02-OCT-08:00 | 0.00 | 01-OCT-00:10 | 68465.76 | 10-OCT-16:00 | 56750.83 | 10-OCT-16:00 | 25713.10 | 19-OCT-05:13 | 18126.36 | 10-OCT-16:00 | 0.00 |
November | 0.112537E+11 | 0.290078E+10 | 218.43 | 0.853204E+10 | 0.272162E+10 | 0.00 | 0.92 | 02-NOV-13:00 | 0.00 | 01-NOV-00:10 | 36500.82 | 02-NOV-13:00 | 28327.71 | 02-NOV-14:20 | 12671.92 | 02-NOV-11:00 | 8564.28 | 02-NOV-13:00 | 0.00 |
December | 0.406788E+10 | 0.105364E+10 | 112.28 | 0.267636E+10 | 0.139152E+10 | 0.00 | 0.87 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 33923.98 | 12-DEC-14:00 | 25993.40 | 12-DEC-14:00 | 14620.12 | 13-DEC-10:10 | 8045.82 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.467399E+12 | 0.118765E+12 | 3566.58 | 0.343853E+12 | 0.123545E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.207129E+10 | 0.554398E+09 | 52.83 | 0.127632E+10 | 0.794962E+09 | 0.00 | 0.61 | 0.00 | 21943.07 | 15031.49 | 9080.41 | 5591.55 | 0.00 | ||||||
Maximum of Months | 0.988962E+11 | 0.253673E+11 | 463.82 | 0.692370E+11 | 0.296591E+11 | 0.00 | 1.00 | 0.00 | 94826.33 | 78944.36 | 32657.44 | 26520.79 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.203768E+10 | 0.541480E+09 | 52.83 | 0.128302E+10 | 0.754656E+09 | 0.00 | 0.67 | 19-JAN-16:00 | 0.00 | 01-JAN-00:05 | 22345.11 | 19-JAN-16:00 | 14268.55 | 31-JAN-15:00 | 10028.04 | 19-JAN-15:10 | 5607.34 | 19-JAN-16:00 | 0.00 |
February | 0.488464E+10 | 0.130569E+10 | 133.54 | 0.398652E+10 | 0.898124E+09 | 0.00 | 0.76 | 28-FEB-15:20 | 0.00 | 01-FEB-00:10 | 26146.64 | 28-FEB-15:20 | 26146.64 | 28-FEB-15:20 | 8696.02 | 18-FEB-16:00 | 6527.01 | 28-FEB-15:00 | 0.00 |
March | 0.142906E+11 | 0.366719E+10 | 270.67 | 0.110693E+11 | 0.322125E+10 | 0.00 | 1.00 | 29-MAR-15:10 | 0.00 | 01-MAR-00:10 | 49604.81 | 30-MAR-15:10 | 49604.81 | 30-MAR-15:10 | 12669.16 | 31-MAR-11:30 | 12497.27 | 30-MAR-15:10 | 0.00 |
April | 0.250784E+11 | 0.633531E+10 | 338.33 | 0.204293E+11 | 0.464915E+10 | 0.00 | 1.00 | 04-APR-14:10 | 0.00 | 01-APR-00:10 | 54545.34 | 17-APR-15:20 | 54545.34 | 17-APR-15:20 | 14326.04 | 21-APR-10:40 | 14168.03 | 17-APR-15:20 | 0.00 |
May | 0.467794E+11 | 0.115998E+11 | 420.73 | 0.353656E+11 | 0.114138E+11 | 0.00 | 1.00 | 02-MAY-13:00 | 0.00 | 01-MAY-00:10 | 66436.52 | 30-MAY-15:10 | 53164.30 | 30-MAY-15:00 | 17186.72 | 31-MAY-13:00 | 17791.37 | 30-MAY-15:00 | 0.00 |
June | 0.694462E+11 | 0.178161E+11 | 437.78 | 0.515177E+11 | 0.179285E+11 | 0.00 | 1.00 | 01-JUN-08:70 | 0.00 | 01-JUN-00:10 | 76227.58 | 26-JUN-15:00 | 57765.16 | 26-JUN-05:13 | 24107.96 | 23-JUN-10:50 | 20784.77 | 27-JUN-16:00 | 0.00 |
July | 0.795670E+11 | 0.205805E+11 | 443.14 | 0.556086E+11 | 0.239584E+11 | 0.00 | 1.00 | 01-JUL-07:20 | 0.00 | 01-JUL-00:10 | 85633.97 | 07-JUL-04:02 | 64263.77 | 07-JUL-04:02 | 27219.51 | 26-JUL-10:50 | 24475.60 | 07-JUL-16:00 | 0.00 |
August | 0.888946E+11 | 0.227113E+11 | 464.89 | 0.603130E+11 | 0.285816E+11 | 0.00 | 1.00 | 01-AUG-05:13 | 0.00 | 01-AUG-00:10 | 89145.94 | 19-AUG-05:03 | 69567.49 | 14-AUG-04:02 | 34918.37 | 21-AUG-06:03 | 23770.59 | 01-AUG-15:20 | 0.00 |
September | 0.543672E+11 | 0.134195E+11 | 410.06 | 0.388036E+11 | 0.155636E+11 | 0.00 | 1.00 | 01-SEP-09:30 | 0.00 | 01-SEP-00:10 | 78678.14 | 07-SEP-16:00 | 58506.41 | 07-SEP-15:30 | 26480.40 | 17-SEP-11:23 | 21497.51 | 07-SEP-16:00 | 0.00 |
October | 0.236554E+11 | 0.587367E+10 | 301.17 | 0.169937E+11 | 0.666174E+10 | 0.00 | 1.00 | 02-OCT-10:10 | 0.00 | 01-OCT-00:10 | 60111.37 | 11-OCT-14:10 | 47823.84 | 11-OCT-16:00 | 22767.00 | 18-OCT-15:00 | 15351.03 | 10-OCT-16:00 | 0.00 |
November | 0.979441E+10 | 0.254324E+10 | 218.11 | 0.724845E+10 | 0.254596E+10 | 0.00 | 0.82 | 02-NOV-13:00 | 0.00 | 01-NOV-00:10 | 29018.61 | 02-NOV-13:00 | 21354.97 | 08-NOV-15:10 | 10829.49 | 27-NOV-18:00 | 7000.32 | 02-NOV-13:00 | 0.00 |
December | 0.374489E+10 | 0.975459E+09 | 112.33 | 0.252995E+10 | 0.121494E+10 | 0.00 | 0.83 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 28945.33 | 12-DEC-14:00 | 21095.08 | 12-DEC-14:00 | 10749.31 | 13-DEC-17:02 | 6949.98 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.422541E+12 | 0.107369E+12 | 3603.59 | 0.305149E+12 | 0.117392E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.203768E+10 | 0.541480E+09 | 52.83 | 0.128302E+10 | 0.754656E+09 | 0.00 | 0.67 | 0.00 | 22345.11 | 14268.55 | 8696.02 | 5607.34 | 0.00 | ||||||
Maximum of Months | 0.888946E+11 | 0.227113E+11 | 464.89 | 0.603130E+11 | 0.285816E+11 | 0.00 | 1.00 | 0.00 | 89145.94 | 69567.49 | 34918.37 | 24475.60 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.215439E+10 | 0.575792E+09 | 53.33 | 0.133638E+10 | 0.818005E+09 | 0.00 | 0.62 | 19-JAN-17:50 | 0.00 | 01-JAN-00:05 | 22719.85 | 19-JAN-17:50 | 15032.40 | 31-JAN-15:00 | 10993.54 | 19-JAN-16:00 | 5773.35 | 19-JAN-17:50 | 0.00 |
February | 0.516494E+10 | 0.138614E+10 | 133.40 | 0.418385E+10 | 0.981088E+09 | 0.00 | 0.77 | 26-FEB-14:43 | 0.00 | 01-FEB-00:10 | 29282.86 | 26-FEB-14:43 | 29282.86 | 26-FEB-14:43 | 9167.52 | 18-FEB-16:00 | 7331.28 | 26-FEB-14:43 | 0.00 |
March | 0.151383E+11 | 0.390604E+10 | 270.64 | 0.116590E+11 | 0.347926E+10 | 0.00 | 1.00 | 29-MAR-15:10 | 0.00 | 01-MAR-00:10 | 55563.18 | 30-MAR-15:20 | 55563.18 | 30-MAR-15:20 | 12616.40 | 31-MAR-11:30 | 13995.36 | 30-MAR-15:20 | 0.00 |
April | 0.272316E+11 | 0.690666E+10 | 340.29 | 0.221856E+11 | 0.504603E+10 | 0.00 | 1.00 | 11-APR-14:10 | 0.00 | 01-APR-00:10 | 61494.92 | 17-APR-15:50 | 61494.92 | 17-APR-15:50 | 16239.87 | 23-APR-13:13 | 15972.51 | 17-APR-15:50 | 0.00 |
May | 0.507755E+11 | 0.126609E+11 | 423.57 | 0.390349E+11 | 0.117406E+11 | 0.00 | 1.00 | 01-MAY-15:50 | 0.00 | 01-MAY-00:10 | 75167.87 | 30-MAY-15:10 | 64934.85 | 16-MAY-15:40 | 17350.86 | 31-MAY-13:00 | 20090.31 | 30-MAY-15:00 | 0.00 |
June | 0.747331E+11 | 0.192652E+11 | 440.82 | 0.564070E+11 | 0.183261E+11 | 0.00 | 1.00 | 01-JUN-09:30 | 0.00 | 01-JUN-00:10 | 84554.92 | 26-JUN-15:00 | 66080.44 | 27-JUN-15:30 | 24428.28 | 23-JUN-10:40 | 23420.35 | 27-JUN-15:50 | 0.00 |
July | 0.850538E+11 | 0.221180E+11 | 444.78 | 0.607612E+11 | 0.242925E+11 | 0.00 | 1.00 | 01-JUL-08:70 | 0.00 | 01-JUL-00:10 | 91547.07 | 07-JUL-16:00 | 73533.51 | 07-JUL-16:00 | 27496.96 | 26-JUL-10:40 | 27705.41 | 07-JUL-16:00 | 0.00 |
August | 0.940089E+11 | 0.241356E+11 | 466.04 | 0.651501E+11 | 0.288588E+11 | 0.00 | 1.00 | 01-AUG-07:20 | 0.00 | 01-AUG-00:10 | 90620.69 | 01-AUG-15:00 | 73604.48 | 02-AUG-16:00 | 30260.23 | 20-AUG-09:32 | 26974.81 | 01-AUG-15:00 | 0.00 |
September | 0.565249E+11 | 0.140573E+11 | 411.29 | 0.404371E+11 | 0.160878E+11 | 0.00 | 1.00 | 01-SEP-10:40 | 0.00 | 01-SEP-00:10 | 86724.34 | 06-SEP-14:00 | 66469.95 | 07-SEP-15:30 | 28263.37 | 17-SEP-11:23 | 23561.06 | 07-SEP-16:00 | 0.00 |
October | 0.242471E+11 | 0.606846E+10 | 298.31 | 0.172446E+11 | 0.700249E+10 | 0.00 | 1.00 | 02-OCT-11:30 | 0.00 | 01-OCT-00:10 | 65525.04 | 11-OCT-14:00 | 52585.41 | 10-OCT-15:40 | 22963.31 | 18-OCT-15:00 | 16664.38 | 10-OCT-15:40 | 0.00 |
November | 0.102233E+11 | 0.266971E+10 | 216.87 | 0.749113E+10 | 0.273214E+10 | 0.00 | 0.83 | 05-NOV-13:43 | 0.00 | 01-NOV-00:10 | 32739.81 | 05-NOV-13:43 | 24264.48 | 05-NOV-15:18 | 11293.56 | 27-NOV-18:00 | 7888.74 | 05-NOV-13:43 | 0.00 |
December | 0.389730E+10 | 0.101989E+10 | 111.00 | 0.259573E+10 | 0.130157E+10 | 0.00 | 0.81 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 31177.63 | 12-DEC-14:00 | 22782.67 | 12-DEC-14:10 | 11199.98 | 13-DEC-16:00 | 7531.98 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.449153E+12 | 0.114770E+12 | 3610.36 | 0.328487E+12 | 0.120666E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.215439E+10 | 0.575792E+09 | 53.33 | 0.133638E+10 | 0.818005E+09 | 0.00 | 0.62 | 0.00 | 22719.85 | 15032.40 | 9167.52 | 5773.35 | 0.00 | ||||||
Maximum of Months | 0.940089E+11 | 0.241356E+11 | 466.04 | 0.651501E+11 | 0.288588E+11 | 0.00 | 1.00 | 0.00 | 91547.07 | 73604.48 | 30260.23 | 27705.41 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 278.63 | 0.00 | 278.63 | 45.13 | 1929.07 | 0.00 | 0.00 | 0.00 |
February | 308.83 | 0.00 | 308.83 | 136.94 | 1574.62 | 0.00 | 0.00 | 0.00 |
March | 433.58 | 0.00 | 433.58 | 304.47 | 979.01 | 0.00 | 0.00 | 0.00 |
April | 524.46 | 2.33 | 522.13 | 585.92 | 784.92 | 0.00 | 0.00 | 0.00 |
May | 627.24 | 20.02 | 607.23 | 883.18 | 516.03 | 0.00 | 0.00 | 0.00 |
June | 690.31 | 45.58 | 644.73 | 1276.03 | 330.54 | 0.00 | 0.00 | 0.00 |
July | 651.31 | 31.66 | 619.65 | 1278.27 | 240.68 | 0.00 | 0.00 | 0.00 |
August | 579.23 | 6.31 | 572.92 | 1168.57 | 200.71 | 0.00 | 0.00 | 0.00 |
September | 437.84 | 0.06 | 437.78 | 666.78 | 433.44 | 0.00 | 0.00 | 0.00 |
October | 332.91 | 0.00 | 332.91 | 305.27 | 892.47 | 0.00 | 0.00 | 0.00 |
November | 297.94 | 0.00 | 297.94 | 171.01 | 1210.01 | 0.00 | 0.00 | 0.00 |
December | 257.57 | 0.00 | 257.57 | 45.66 | 1538.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.43 | 8.87 | 443.57 | 574.72 | 882.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.57 | 0.00 | 257.57 | 45.13 | 200.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 690.31 | 45.58 | 644.73 | 1278.27 | 1929.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 407.94 | 184.00 | 223.94 | 285.27 | 1143.75 | 0.00 | 0.00 | 0.00 |
February | 514.28 | 276.32 | 237.96 | 499.41 | 940.25 | 0.00 | 0.00 | 0.00 |
March | 647.02 | 294.54 | 352.48 | 736.67 | 599.36 | 0.00 | 0.00 | 0.00 |
April | 782.42 | 356.76 | 425.66 | 1084.08 | 492.17 | 0.00 | 0.00 | 0.00 |
May | 859.15 | 363.32 | 495.83 | 1320.78 | 338.60 | 0.00 | 0.00 | 0.00 |
June | 889.51 | 372.82 | 516.70 | 1571.38 | 219.63 | 0.00 | 0.00 | 0.00 |
July | 867.31 | 364.63 | 502.68 | 1586.64 | 160.49 | 0.00 | 0.00 | 0.00 |
August | 793.30 | 314.73 | 478.57 | 1478.34 | 132.76 | 0.00 | 0.00 | 0.00 |
September | 651.99 | 288.88 | 363.11 | 1050.72 | 277.48 | 0.00 | 0.00 | 0.00 |
October | 556.20 | 289.40 | 266.80 | 719.80 | 551.23 | 0.00 | 0.00 | 0.00 |
November | 444.69 | 201.35 | 243.33 | 453.50 | 722.61 | 0.00 | 0.00 | 0.00 |
December | 385.18 | 175.58 | 209.60 | 292.36 | 909.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 650.57 | 290.15 | 360.42 | 925.45 | 538.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 385.18 | 175.58 | 209.60 | 285.27 | 132.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 889.51 | 372.82 | 516.70 | 1586.64 | 1143.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1490.14 | 1038.92 | 451.22 | 1684.34 | 1601.19 | 0.00 | 0.00 | 0.00 |
February | 1390.80 | 932.29 | 458.51 | 1715.63 | 1379.36 | 0.00 | 0.00 | 0.00 |
March | 1250.80 | 651.84 | 598.96 | 1677.66 | 955.30 | 0.00 | 0.00 | 0.00 |
April | 936.76 | 304.94 | 631.83 | 1403.71 | 810.27 | 0.00 | 0.00 | 0.00 |
May | 756.87 | 87.97 | 668.90 | 1200.13 | 546.06 | 0.00 | 0.00 | 0.00 |
June | 699.80 | 38.94 | 660.86 | 1337.73 | 351.30 | 0.00 | 0.00 | 0.00 |
July | 707.49 | 52.75 | 654.73 | 1423.51 | 250.65 | 0.00 | 0.00 | 0.00 |
August | 844.69 | 157.79 | 686.90 | 1728.58 | 209.89 | 0.00 | 0.00 | 0.00 |
September | 928.95 | 345.52 | 583.43 | 1606.94 | 444.80 | 0.00 | 0.00 | 0.00 |
October | 1346.71 | 872.40 | 474.31 | 1998.67 | 870.22 | 0.00 | 0.00 | 0.00 |
November | 1448.82 | 961.41 | 487.41 | 1936.77 | 1113.90 | 0.00 | 0.00 | 0.00 |
December | 1468.86 | 1033.36 | 435.51 | 1779.54 | 1336.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1104.67 | 538.01 | 566.66 | 1624.27 | 819.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 699.80 | 38.94 | 435.51 | 1200.13 | 209.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1490.14 | 1038.92 | 686.90 | 1998.67 | 1601.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 419.01 | 194.36 | 224.64 | 330.81 | 1189.92 | 0.00 | 0.00 | 0.00 |
February | 481.02 | 224.90 | 256.11 | 495.84 | 996.90 | 0.00 | 0.00 | 0.00 |
March | 708.99 | 342.60 | 366.39 | 885.69 | 647.16 | 0.00 | 0.00 | 0.00 |
April | 797.60 | 364.98 | 432.62 | 1148.57 | 535.04 | 0.00 | 0.00 | 0.00 |
May | 801.61 | 303.70 | 497.91 | 1266.82 | 366.68 | 0.00 | 0.00 | 0.00 |
June | 843.00 | 324.30 | 518.70 | 1512.63 | 241.45 | 0.00 | 0.00 | 0.00 |
July | 795.14 | 294.81 | 500.33 | 1481.71 | 172.18 | 0.00 | 0.00 | 0.00 |
August | 779.13 | 291.36 | 487.76 | 1467.02 | 145.80 | 0.00 | 0.00 | 0.00 |
September | 634.78 | 264.41 | 370.36 | 1038.59 | 293.72 | 0.00 | 0.00 | 0.00 |
October | 565.51 | 293.56 | 271.95 | 782.60 | 596.28 | 0.00 | 0.00 | 0.00 |
November | 451.32 | 202.57 | 248.74 | 522.56 | 790.00 | 0.00 | 0.00 | 0.00 |
December | 372.33 | 162.86 | 209.47 | 323.01 | 977.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 638.25 | 272.24 | 366.02 | 940.33 | 577.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 372.33 | 162.86 | 209.47 | 323.01 | 145.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 843.00 | 364.98 | 518.70 | 1512.63 | 1189.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.87 | 0.00 | 92.87 | 14.67 | 667.79 | 0.00 | 0.00 | 0.00 |
February | 102.94 | 0.00 | 102.94 | 47.80 | 538.36 | 0.00 | 0.00 | 0.00 |
March | 144.52 | 0.00 | 144.52 | 111.42 | 324.15 | 0.00 | 0.00 | 0.00 |
April | 174.81 | 0.78 | 174.04 | 213.32 | 248.87 | 0.00 | 0.00 | 0.00 |
May | 209.07 | 6.67 | 202.40 | 310.10 | 162.32 | 0.00 | 0.00 | 0.00 |
June | 230.09 | 15.19 | 214.90 | 435.32 | 106.25 | 0.00 | 0.00 | 0.00 |
July | 217.09 | 10.55 | 206.54 | 435.23 | 77.06 | 0.00 | 0.00 | 0.00 |
August | 193.07 | 2.10 | 190.97 | 395.25 | 66.02 | 0.00 | 0.00 | 0.00 |
September | 145.94 | 0.02 | 145.92 | 220.61 | 158.08 | 0.00 | 0.00 | 0.00 |
October | 110.96 | 0.00 | 110.96 | 96.09 | 332.69 | 0.00 | 0.00 | 0.00 |
November | 99.31 | 0.00 | 99.31 | 48.99 | 449.32 | 0.00 | 0.00 | 0.00 |
December | 85.85 | 0.00 | 85.85 | 13.59 | 562.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.80 | 2.96 | 147.85 | 196.03 | 306.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.85 | 0.00 | 85.85 | 13.59 | 66.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 230.09 | 15.19 | 214.90 | 435.32 | 667.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.88 | 0.00 | 92.88 | 14.67 | 667.83 | 0.00 | 0.00 | 0.00 |
February | 102.94 | 0.00 | 102.94 | 47.80 | 538.39 | 0.00 | 0.00 | 0.00 |
March | 144.53 | 0.00 | 144.53 | 111.42 | 324.17 | 0.00 | 0.00 | 0.00 |
April | 174.82 | 0.78 | 174.04 | 213.33 | 248.88 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 6.67 | 202.41 | 310.11 | 162.33 | 0.00 | 0.00 | 0.00 |
June | 230.10 | 15.19 | 214.91 | 435.34 | 106.26 | 0.00 | 0.00 | 0.00 |
July | 217.10 | 10.55 | 206.55 | 435.25 | 77.06 | 0.00 | 0.00 | 0.00 |
August | 193.08 | 2.10 | 190.97 | 395.27 | 66.03 | 0.00 | 0.00 | 0.00 |
September | 145.95 | 0.02 | 145.93 | 220.62 | 158.08 | 0.00 | 0.00 | 0.00 |
October | 110.97 | 0.00 | 110.97 | 96.10 | 332.71 | 0.00 | 0.00 | 0.00 |
November | 99.31 | 0.00 | 99.31 | 48.99 | 449.35 | 0.00 | 0.00 | 0.00 |
December | 85.86 | 0.00 | 85.86 | 13.59 | 562.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.81 | 2.96 | 147.85 | 196.04 | 306.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.86 | 0.00 | 85.86 | 13.59 | 66.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 230.10 | 15.19 | 214.91 | 435.34 | 667.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.88 | 0.00 | 92.88 | 14.67 | 667.83 | 0.00 | 0.00 | 0.00 |
February | 102.94 | 0.00 | 102.94 | 47.80 | 538.39 | 0.00 | 0.00 | 0.00 |
March | 144.53 | 0.00 | 144.53 | 111.42 | 324.17 | 0.00 | 0.00 | 0.00 |
April | 174.82 | 0.78 | 174.04 | 213.33 | 248.88 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 6.67 | 202.41 | 310.11 | 162.33 | 0.00 | 0.00 | 0.00 |
June | 230.10 | 15.19 | 214.91 | 435.34 | 106.26 | 0.00 | 0.00 | 0.00 |
July | 217.10 | 10.55 | 206.55 | 435.25 | 77.06 | 0.00 | 0.00 | 0.00 |
August | 193.08 | 2.10 | 190.97 | 395.27 | 66.03 | 0.00 | 0.00 | 0.00 |
September | 145.95 | 0.02 | 145.93 | 220.62 | 158.08 | 0.00 | 0.00 | 0.00 |
October | 110.97 | 0.00 | 110.97 | 96.10 | 332.71 | 0.00 | 0.00 | 0.00 |
November | 99.31 | 0.00 | 99.31 | 48.99 | 449.35 | 0.00 | 0.00 | 0.00 |
December | 85.86 | 0.00 | 85.86 | 13.59 | 562.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.81 | 2.96 | 147.85 | 196.04 | 306.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.86 | 0.00 | 85.86 | 13.59 | 66.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 230.10 | 15.19 | 214.91 | 435.34 | 667.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 392.41 | 177.00 | 215.42 | 271.44 | 1154.45 | 0.00 | 0.00 | 0.00 |
February | 494.71 | 265.80 | 228.91 | 484.28 | 941.89 | 0.00 | 0.00 | 0.00 |
March | 622.40 | 283.33 | 339.07 | 726.17 | 589.41 | 0.00 | 0.00 | 0.00 |
April | 752.65 | 343.19 | 409.46 | 1071.50 | 467.21 | 0.00 | 0.00 | 0.00 |
May | 826.46 | 349.50 | 476.96 | 1297.51 | 320.05 | 0.00 | 0.00 | 0.00 |
June | 855.67 | 358.63 | 497.04 | 1530.08 | 212.07 | 0.00 | 0.00 | 0.00 |
July | 834.31 | 350.75 | 483.55 | 1542.29 | 156.52 | 0.00 | 0.00 | 0.00 |
August | 763.12 | 302.75 | 460.36 | 1433.01 | 134.12 | 0.00 | 0.00 | 0.00 |
September | 627.18 | 277.89 | 349.29 | 1006.91 | 301.04 | 0.00 | 0.00 | 0.00 |
October | 535.04 | 278.39 | 256.64 | 677.37 | 604.21 | 0.00 | 0.00 | 0.00 |
November | 427.77 | 193.69 | 234.08 | 409.08 | 789.60 | 0.00 | 0.00 | 0.00 |
December | 370.53 | 168.90 | 201.63 | 270.10 | 973.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 625.81 | 279.11 | 346.71 | 895.45 | 551.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 370.53 | 168.90 | 201.63 | 270.10 | 134.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 855.67 | 358.63 | 497.04 | 1542.29 | 1154.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.52 | 7.00 | 8.52 | 10.73 | 45.65 | 0.00 | 0.00 | 0.00 |
February | 19.56 | 10.51 | 9.05 | 19.15 | 37.24 | 0.00 | 0.00 | 0.00 |
March | 24.61 | 11.20 | 13.41 | 28.71 | 23.30 | 0.00 | 0.00 | 0.00 |
April | 29.76 | 13.57 | 16.19 | 42.37 | 18.47 | 0.00 | 0.00 | 0.00 |
May | 32.68 | 13.82 | 18.86 | 51.30 | 12.65 | 0.00 | 0.00 | 0.00 |
June | 33.83 | 14.18 | 19.65 | 60.50 | 8.38 | 0.00 | 0.00 | 0.00 |
July | 32.99 | 13.87 | 19.12 | 60.98 | 6.19 | 0.00 | 0.00 | 0.00 |
August | 30.17 | 11.97 | 18.20 | 56.66 | 5.30 | 0.00 | 0.00 | 0.00 |
September | 24.80 | 10.99 | 13.81 | 39.81 | 11.90 | 0.00 | 0.00 | 0.00 |
October | 21.15 | 11.01 | 10.15 | 26.78 | 23.89 | 0.00 | 0.00 | 0.00 |
November | 16.91 | 7.66 | 9.26 | 16.17 | 31.22 | 0.00 | 0.00 | 0.00 |
December | 14.65 | 6.68 | 7.97 | 10.68 | 38.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.74 | 11.04 | 13.71 | 35.41 | 21.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.65 | 6.68 | 7.97 | 10.68 | 5.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.83 | 14.18 | 19.65 | 60.98 | 45.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 496.70 | 346.30 | 150.40 | 567.91 | 566.88 | 0.00 | 0.00 | 0.00 |
February | 463.59 | 310.76 | 152.83 | 580.90 | 484.59 | 0.00 | 0.00 | 0.00 |
March | 416.93 | 217.28 | 199.65 | 573.72 | 328.96 | 0.00 | 0.00 | 0.00 |
April | 312.25 | 101.64 | 210.61 | 486.38 | 263.27 | 0.00 | 0.00 | 0.00 |
May | 252.29 | 29.32 | 222.96 | 416.22 | 173.17 | 0.00 | 0.00 | 0.00 |
June | 233.27 | 12.98 | 220.29 | 456.34 | 113.23 | 0.00 | 0.00 | 0.00 |
July | 235.83 | 17.58 | 218.24 | 483.35 | 81.10 | 0.00 | 0.00 | 0.00 |
August | 281.56 | 52.60 | 228.96 | 581.30 | 71.79 | 0.00 | 0.00 | 0.00 |
September | 309.65 | 115.17 | 194.47 | 535.58 | 164.90 | 0.00 | 0.00 | 0.00 |
October | 448.90 | 290.79 | 158.10 | 664.33 | 331.86 | 0.00 | 0.00 | 0.00 |
November | 482.93 | 320.46 | 162.47 | 638.47 | 426.19 | 0.00 | 0.00 | 0.00 |
December | 489.61 | 344.44 | 145.17 | 591.68 | 501.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 368.22 | 179.33 | 188.88 | 547.95 | 291.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 233.27 | 12.98 | 145.17 | 416.22 | 71.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.70 | 346.30 | 228.96 | 664.33 | 566.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 496.70 | 346.30 | 150.40 | 567.91 | 566.88 | 0.00 | 0.00 | 0.00 |
February | 463.59 | 310.76 | 152.83 | 580.90 | 484.59 | 0.00 | 0.00 | 0.00 |
March | 416.93 | 217.28 | 199.65 | 573.72 | 328.96 | 0.00 | 0.00 | 0.00 |
April | 312.25 | 101.64 | 210.61 | 486.38 | 263.27 | 0.00 | 0.00 | 0.00 |
May | 252.29 | 29.32 | 222.96 | 416.22 | 173.17 | 0.00 | 0.00 | 0.00 |
June | 233.27 | 12.98 | 220.29 | 456.34 | 113.23 | 0.00 | 0.00 | 0.00 |
July | 235.83 | 17.58 | 218.24 | 483.35 | 81.10 | 0.00 | 0.00 | 0.00 |
August | 281.56 | 52.60 | 228.96 | 581.30 | 71.79 | 0.00 | 0.00 | 0.00 |
September | 309.65 | 115.17 | 194.47 | 535.58 | 164.90 | 0.00 | 0.00 | 0.00 |
October | 448.90 | 290.79 | 158.10 | 664.33 | 331.86 | 0.00 | 0.00 | 0.00 |
November | 482.93 | 320.46 | 162.47 | 638.47 | 426.19 | 0.00 | 0.00 | 0.00 |
December | 489.61 | 344.44 | 145.17 | 591.68 | 501.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 368.22 | 179.33 | 188.88 | 547.95 | 291.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 233.27 | 12.98 | 145.17 | 416.22 | 71.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.70 | 346.30 | 228.96 | 664.33 | 566.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 496.67 | 346.28 | 150.39 | 567.87 | 566.84 | 0.00 | 0.00 | 0.00 |
February | 463.56 | 310.74 | 152.82 | 580.87 | 484.56 | 0.00 | 0.00 | 0.00 |
March | 416.90 | 217.26 | 199.64 | 573.68 | 328.94 | 0.00 | 0.00 | 0.00 |
April | 312.23 | 101.64 | 210.59 | 486.35 | 263.25 | 0.00 | 0.00 | 0.00 |
May | 252.27 | 29.32 | 222.95 | 416.19 | 173.16 | 0.00 | 0.00 | 0.00 |
June | 233.25 | 12.98 | 220.27 | 456.31 | 113.22 | 0.00 | 0.00 | 0.00 |
July | 235.81 | 17.58 | 218.23 | 483.32 | 81.09 | 0.00 | 0.00 | 0.00 |
August | 281.54 | 52.59 | 228.95 | 581.26 | 71.79 | 0.00 | 0.00 | 0.00 |
September | 309.63 | 115.16 | 194.46 | 535.55 | 164.88 | 0.00 | 0.00 | 0.00 |
October | 448.87 | 290.78 | 158.09 | 664.28 | 331.84 | 0.00 | 0.00 | 0.00 |
November | 482.90 | 320.44 | 162.46 | 638.43 | 426.16 | 0.00 | 0.00 | 0.00 |
December | 489.58 | 344.42 | 145.16 | 591.64 | 501.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 368.19 | 179.32 | 188.87 | 547.92 | 291.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 233.25 | 12.98 | 145.16 | 416.19 | 71.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.67 | 346.28 | 228.95 | 664.28 | 566.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 403.06 | 186.97 | 216.10 | 321.49 | 1201.77 | 0.00 | 0.00 | 0.00 |
February | 462.72 | 216.35 | 246.37 | 486.32 | 997.54 | 0.00 | 0.00 | 0.00 |
March | 682.02 | 329.56 | 352.45 | 873.05 | 640.99 | 0.00 | 0.00 | 0.00 |
April | 767.26 | 351.09 | 416.16 | 1134.21 | 512.79 | 0.00 | 0.00 | 0.00 |
May | 771.11 | 292.14 | 478.97 | 1242.02 | 349.80 | 0.00 | 0.00 | 0.00 |
June | 810.93 | 311.96 | 498.97 | 1473.02 | 235.29 | 0.00 | 0.00 | 0.00 |
July | 764.89 | 283.59 | 481.30 | 1439.17 | 168.63 | 0.00 | 0.00 | 0.00 |
August | 749.48 | 280.28 | 469.21 | 1420.14 | 148.38 | 0.00 | 0.00 | 0.00 |
September | 610.62 | 254.35 | 356.27 | 992.91 | 320.38 | 0.00 | 0.00 | 0.00 |
October | 543.99 | 282.39 | 261.60 | 741.91 | 655.83 | 0.00 | 0.00 | 0.00 |
November | 434.15 | 194.87 | 239.28 | 485.79 | 860.13 | 0.00 | 0.00 | 0.00 |
December | 358.17 | 156.66 | 201.51 | 306.12 | 1040.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 613.97 | 261.88 | 352.09 | 911.93 | 592.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 358.17 | 156.66 | 201.51 | 306.12 | 148.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 810.93 | 351.09 | 498.97 | 1473.02 | 1201.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.94 | 7.39 | 8.54 | 12.71 | 47.52 | 0.00 | 0.00 | 0.00 |
February | 18.30 | 8.55 | 9.74 | 19.23 | 39.44 | 0.00 | 0.00 | 0.00 |
March | 26.97 | 13.03 | 13.94 | 34.52 | 25.34 | 0.00 | 0.00 | 0.00 |
April | 30.34 | 13.88 | 16.45 | 44.85 | 20.28 | 0.00 | 0.00 | 0.00 |
May | 30.49 | 11.55 | 18.94 | 49.11 | 13.83 | 0.00 | 0.00 | 0.00 |
June | 32.06 | 12.33 | 19.73 | 58.24 | 9.30 | 0.00 | 0.00 | 0.00 |
July | 30.24 | 11.21 | 19.03 | 56.90 | 6.67 | 0.00 | 0.00 | 0.00 |
August | 29.63 | 11.08 | 18.55 | 56.15 | 5.87 | 0.00 | 0.00 | 0.00 |
September | 24.14 | 10.06 | 14.09 | 39.26 | 12.67 | 0.00 | 0.00 | 0.00 |
October | 21.51 | 11.17 | 10.34 | 29.33 | 25.93 | 0.00 | 0.00 | 0.00 |
November | 17.17 | 7.70 | 9.46 | 19.21 | 34.01 | 0.00 | 0.00 | 0.00 |
December | 14.16 | 6.19 | 7.97 | 12.10 | 41.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.28 | 10.35 | 13.92 | 36.06 | 23.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.16 | 6.19 | 7.97 | 12.10 | 5.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.06 | 13.88 | 19.73 | 58.24 | 47.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 278.63 | 0.00 | 278.63 | 41.12 | 2020.22 | 0.00 | 0.00 | 0.00 |
February | 308.83 | 0.00 | 308.83 | 130.70 | 1656.55 | 0.00 | 0.00 | 0.00 |
March | 433.58 | 0.00 | 433.58 | 292.70 | 1044.63 | 0.00 | 0.00 | 0.00 |
April | 524.46 | 2.33 | 522.13 | 578.16 | 827.24 | 0.00 | 0.00 | 0.00 |
May | 627.24 | 20.02 | 607.23 | 882.38 | 537.23 | 0.00 | 0.00 | 0.00 |
June | 690.31 | 45.58 | 644.73 | 1282.11 | 339.28 | 0.00 | 0.00 | 0.00 |
July | 651.31 | 31.66 | 619.65 | 1288.51 | 244.72 | 0.00 | 0.00 | 0.00 |
August | 579.23 | 6.31 | 572.92 | 1177.60 | 205.02 | 0.00 | 0.00 | 0.00 |
September | 437.84 | 0.06 | 437.78 | 662.23 | 463.18 | 0.00 | 0.00 | 0.00 |
October | 332.91 | 0.00 | 332.91 | 291.54 | 966.19 | 0.00 | 0.00 | 0.00 |
November | 297.94 | 0.00 | 297.94 | 151.87 | 1309.51 | 0.00 | 0.00 | 0.00 |
December | 257.57 | 0.00 | 257.57 | 39.46 | 1654.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.43 | 8.87 | 443.57 | 570.69 | 935.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.57 | 0.00 | 257.57 | 39.46 | 205.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 690.31 | 45.58 | 644.73 | 1288.51 | 2020.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 407.94 | 184.00 | 223.94 | 276.31 | 1199.45 | 0.00 | 0.00 | 0.00 |
February | 514.28 | 276.32 | 237.96 | 489.83 | 989.51 | 0.00 | 0.00 | 0.00 |
March | 647.02 | 294.54 | 352.48 | 726.07 | 635.00 | 0.00 | 0.00 | 0.00 |
April | 782.42 | 356.76 | 425.66 | 1079.15 | 514.58 | 0.00 | 0.00 | 0.00 |
May | 859.15 | 363.32 | 495.83 | 1321.95 | 349.91 | 0.00 | 0.00 | 0.00 |
June | 889.51 | 372.82 | 516.70 | 1577.08 | 224.64 | 0.00 | 0.00 | 0.00 |
July | 867.31 | 364.63 | 502.68 | 1594.76 | 162.98 | 0.00 | 0.00 | 0.00 |
August | 793.30 | 314.73 | 478.57 | 1485.76 | 135.40 | 0.00 | 0.00 | 0.00 |
September | 651.99 | 288.88 | 363.11 | 1048.65 | 294.27 | 0.00 | 0.00 | 0.00 |
October | 556.20 | 289.40 | 266.80 | 708.98 | 590.73 | 0.00 | 0.00 | 0.00 |
November | 444.69 | 201.35 | 243.33 | 434.14 | 777.88 | 0.00 | 0.00 | 0.00 |
December | 385.18 | 175.58 | 209.60 | 280.43 | 978.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 650.57 | 290.15 | 360.42 | 920.84 | 568.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 385.18 | 175.58 | 209.60 | 276.31 | 135.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 889.51 | 372.82 | 516.70 | 1594.76 | 1199.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1490.14 | 1038.92 | 451.22 | 1662.79 | 1685.60 | 0.00 | 0.00 | 0.00 |
February | 1390.80 | 932.29 | 458.51 | 1699.60 | 1457.23 | 0.00 | 0.00 | 0.00 |
March | 1250.80 | 651.84 | 598.96 | 1664.31 | 1016.62 | 0.00 | 0.00 | 0.00 |
April | 936.76 | 304.94 | 631.83 | 1397.36 | 853.07 | 0.00 | 0.00 | 0.00 |
May | 756.87 | 87.97 | 668.90 | 1200.76 | 569.80 | 0.00 | 0.00 | 0.00 |
June | 699.80 | 38.94 | 660.86 | 1344.44 | 362.81 | 0.00 | 0.00 | 0.00 |
July | 707.49 | 52.75 | 654.73 | 1433.52 | 256.57 | 0.00 | 0.00 | 0.00 |
August | 844.69 | 157.79 | 686.90 | 1738.40 | 215.35 | 0.00 | 0.00 | 0.00 |
September | 928.95 | 345.52 | 583.43 | 1604.19 | 473.77 | 0.00 | 0.00 | 0.00 |
October | 1346.71 | 872.40 | 474.31 | 1985.90 | 935.09 | 0.00 | 0.00 | 0.00 |
November | 1448.82 | 961.41 | 487.41 | 1909.04 | 1201.65 | 0.00 | 0.00 | 0.00 |
December | 1468.86 | 1033.36 | 435.51 | 1753.78 | 1438.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1104.67 | 538.01 | 566.66 | 1616.06 | 868.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 699.80 | 38.94 | 435.51 | 1200.76 | 215.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1490.14 | 1038.92 | 686.90 | 1985.90 | 1685.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 419.01 | 194.36 | 224.64 | 325.49 | 1248.27 | 0.00 | 0.00 | 0.00 |
February | 481.02 | 224.90 | 256.11 | 490.93 | 1049.74 | 0.00 | 0.00 | 0.00 |
March | 708.99 | 342.60 | 366.39 | 879.34 | 688.96 | 0.00 | 0.00 | 0.00 |
April | 797.60 | 364.98 | 432.62 | 1144.15 | 563.45 | 0.00 | 0.00 | 0.00 |
May | 801.61 | 303.70 | 497.91 | 1266.35 | 382.78 | 0.00 | 0.00 | 0.00 |
June | 843.00 | 324.30 | 518.70 | 1517.38 | 249.74 | 0.00 | 0.00 | 0.00 |
July | 795.14 | 294.81 | 500.33 | 1487.64 | 176.47 | 0.00 | 0.00 | 0.00 |
August | 779.13 | 291.36 | 487.76 | 1472.63 | 149.62 | 0.00 | 0.00 | 0.00 |
September | 634.78 | 264.41 | 370.36 | 1034.53 | 314.04 | 0.00 | 0.00 | 0.00 |
October | 565.51 | 293.56 | 271.95 | 774.71 | 642.70 | 0.00 | 0.00 | 0.00 |
November | 451.32 | 202.57 | 248.74 | 509.66 | 851.85 | 0.00 | 0.00 | 0.00 |
December | 372.33 | 162.86 | 209.47 | 315.50 | 1049.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 638.25 | 272.24 | 366.02 | 937.23 | 611.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 372.33 | 162.86 | 209.47 | 315.50 | 149.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 843.00 | 364.98 | 518.70 | 1517.38 | 1248.27 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.746277E+09 | 0.00 | 0.746277E+09 | 0.120879E+09 | 0.516683E+10 |
February | 0.747125E+09 | 0.00 | 0.747125E+09 | 0.331290E+09 | 0.380931E+10 |
March | 0.116131E+10 | 0.00 | 0.116131E+10 | 0.815485E+09 | 0.262219E+10 |
April | 0.135940E+10 | 6029322.01 | 0.135337E+10 | 0.151871E+10 | 0.203452E+10 |
May | 0.168001E+10 | 53616748.83 | 0.162639E+10 | 0.236552E+10 | 0.138215E+10 |
June | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.330747E+10 | 0.856761E+09 |
July | 0.174447E+10 | 84799715.93 | 0.165967E+10 | 0.342372E+10 | 0.644626E+09 |
August | 0.155141E+10 | 16900235.20 | 0.153451E+10 | 0.312990E+10 | 0.537584E+09 |
September | 0.113489E+10 | 159761.37 | 0.113473E+10 | 0.172830E+10 | 0.112347E+10 |
October | 0.891659E+09 | 0.00 | 0.891659E+09 | 0.817640E+09 | 0.239039E+10 |
November | 0.772262E+09 | 0.00 | 0.772262E+09 | 0.443268E+09 | 0.313634E+10 |
December | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.122298E+09 | 0.411975E+10 |
Annual Sum or Average | 0.142680E+11 | 0.279641E+09 | 0.139883E+11 | 0.181245E+11 | 0.278239E+11 |
Minimum of Months | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.120879E+09 | 0.537584E+09 |
Maximum of Months | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.342372E+10 | 0.516683E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109261E+10 | 0.492825E+09 | 0.599790E+09 | 0.764069E+09 | 0.306341E+10 |
February | 0.124414E+10 | 0.668469E+09 | 0.575674E+09 | 0.120817E+10 | 0.227466E+10 |
March | 0.173298E+10 | 0.788905E+09 | 0.944080E+09 | 0.197310E+10 | 0.160534E+10 |
April | 0.202802E+10 | 0.924727E+09 | 0.110330E+10 | 0.280994E+10 | 0.127571E+10 |
May | 0.230115E+10 | 0.973125E+09 | 0.132803E+10 | 0.353757E+10 | 0.906918E+09 |
June | 0.230561E+10 | 0.966340E+09 | 0.133927E+10 | 0.407301E+10 | 0.569288E+09 |
July | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.424967E+10 | 0.429846E+09 |
August | 0.212478E+10 | 0.842976E+09 | 0.128180E+10 | 0.395957E+10 | 0.355588E+09 |
September | 0.168995E+10 | 0.748772E+09 | 0.941176E+09 | 0.272347E+10 | 0.719222E+09 |
October | 0.148972E+10 | 0.775140E+09 | 0.714585E+09 | 0.192792E+10 | 0.147641E+10 |
November | 0.115263E+10 | 0.521905E+09 | 0.630721E+09 | 0.117546E+10 | 0.187300E+10 |
December | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.783052E+09 | 0.243592E+10 |
Annual Sum or Average | 0.205163E+11 | 0.915008E+10 | 0.113662E+11 | 0.291850E+11 | 0.169853E+11 |
Minimum of Months | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.764069E+09 | 0.355588E+09 |
Maximum of Months | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.424967E+10 | 0.306341E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.399118E+10 | 0.278264E+10 | 0.120854E+10 | 0.451135E+10 | 0.428863E+10 |
February | 0.336461E+10 | 0.225539E+10 | 0.110922E+10 | 0.415044E+10 | 0.333695E+10 |
March | 0.335013E+10 | 0.174589E+10 | 0.160424E+10 | 0.449345E+10 | 0.255867E+10 |
April | 0.242809E+10 | 0.790395E+09 | 0.163769E+10 | 0.363841E+10 | 0.210021E+10 |
May | 0.202719E+10 | 0.235614E+09 | 0.179158E+10 | 0.321442E+10 | 0.146257E+10 |
June | 0.181389E+10 | 0.100936E+09 | 0.171295E+10 | 0.346740E+10 | 0.910557E+09 |
July | 0.189493E+10 | 0.141297E+09 | 0.175364E+10 | 0.381272E+10 | 0.671353E+09 |
August | 0.226241E+10 | 0.422627E+09 | 0.183979E+10 | 0.462984E+10 | 0.562164E+09 |
September | 0.240784E+10 | 0.895590E+09 | 0.151225E+10 | 0.416520E+10 | 0.115293E+10 |
October | 0.360703E+10 | 0.233664E+10 | 0.127039E+10 | 0.535324E+10 | 0.233081E+10 |
November | 0.375534E+10 | 0.249198E+10 | 0.126336E+10 | 0.502012E+10 | 0.288723E+10 |
December | 0.393420E+10 | 0.276774E+10 | 0.116646E+10 | 0.476632E+10 | 0.357869E+10 |
Annual Sum or Average | 0.348369E+11 | 0.169667E+11 | 0.178701E+11 | 0.512229E+11 | 0.258408E+11 |
Minimum of Months | 0.181389E+10 | 0.100936E+09 | 0.110922E+10 | 0.321442E+10 | 0.562164E+09 |
Maximum of Months | 0.399118E+10 | 0.278264E+10 | 0.183979E+10 | 0.535324E+10 | 0.428863E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112227E+10 | 0.520587E+09 | 0.601681E+09 | 0.886029E+09 | 0.318707E+10 |
February | 0.116368E+10 | 0.544089E+09 | 0.619587E+09 | 0.119954E+10 | 0.241170E+10 |
March | 0.189896E+10 | 0.917621E+09 | 0.981340E+09 | 0.237223E+10 | 0.173334E+10 |
April | 0.206738E+10 | 0.946027E+09 | 0.112136E+10 | 0.297710E+10 | 0.138683E+10 |
May | 0.214704E+10 | 0.813430E+09 | 0.133361E+10 | 0.339305E+10 | 0.982116E+09 |
June | 0.218506E+10 | 0.840583E+09 | 0.134448E+10 | 0.392075E+10 | 0.625833E+09 |
July | 0.212971E+10 | 0.789625E+09 | 0.134009E+10 | 0.396861E+10 | 0.461154E+09 |
August | 0.208681E+10 | 0.780386E+09 | 0.130643E+10 | 0.392927E+10 | 0.390504E+09 |
September | 0.164534E+10 | 0.685356E+09 | 0.959983E+09 | 0.269202E+10 | 0.761329E+09 |
October | 0.151466E+10 | 0.786276E+09 | 0.728386E+09 | 0.209611E+10 | 0.159707E+10 |
November | 0.116982E+10 | 0.525073E+09 | 0.644742E+09 | 0.135448E+10 | 0.204768E+10 |
December | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.865153E+09 | 0.261778E+10 |
Annual Sum or Average | 0.201280E+11 | 0.858525E+10 | 0.115427E+11 | 0.296543E+11 | 0.182024E+11 |
Minimum of Months | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.865153E+09 | 0.390504E+09 |
Maximum of Months | 0.218506E+10 | 0.946027E+09 | 0.134448E+10 | 0.396861E+10 | 0.318707E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248747E+09 | 0.00 | 0.248747E+09 | 39286070.66 | 0.178860E+10 |
February | 0.249030E+09 | 0.00 | 0.249030E+09 | 0.115629E+09 | 0.130239E+10 |
March | 0.387084E+09 | 0.00 | 0.387084E+09 | 0.298417E+09 | 0.868199E+09 |
April | 0.453110E+09 | 2009678.92 | 0.451101E+09 | 0.552916E+09 | 0.645064E+09 |
May | 0.559977E+09 | 17871404.04 | 0.542106E+09 | 0.830561E+09 | 0.434761E+09 |
June | 0.596400E+09 | 39376456.78 | 0.557023E+09 | 0.112835E+10 | 0.275405E+09 |
July | 0.581461E+09 | 28265234.63 | 0.553196E+09 | 0.116572E+10 | 0.206388E+09 |
August | 0.517114E+09 | 5633145.20 | 0.511481E+09 | 0.105864E+10 | 0.176835E+09 |
September | 0.378280E+09 | 53251.27 | 0.378227E+09 | 0.571827E+09 | 0.409733E+09 |
October | 0.297206E+09 | 0.00 | 0.297206E+09 | 0.257377E+09 | 0.891065E+09 |
November | 0.257408E+09 | 0.00 | 0.257408E+09 | 0.126984E+09 | 0.116463E+10 |
December | 0.229948E+09 | 0.00 | 0.229948E+09 | 36398556.58 | 0.150611E+10 |
Annual Sum or Average | 0.475577E+10 | 93209170.84 | 0.466256E+10 | 0.618211E+10 | 0.966918E+10 |
Minimum of Months | 0.229948E+09 | 0.00 | 0.229948E+09 | 36398556.58 | 0.176835E+09 |
Maximum of Months | 0.596400E+09 | 39376456.78 | 0.557023E+09 | 0.116572E+10 | 0.178860E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248757E+09 | 0.00 | 0.248757E+09 | 39286614.67 | 0.178871E+10 |
February | 0.249040E+09 | 0.00 | 0.249040E+09 | 0.115633E+09 | 0.130247E+10 |
March | 0.387100E+09 | 0.00 | 0.387100E+09 | 0.298426E+09 | 0.868250E+09 |
April | 0.453129E+09 | 2009732.94 | 0.451119E+09 | 0.552939E+09 | 0.645101E+09 |
May | 0.560000E+09 | 17871884.42 | 0.542128E+09 | 0.830595E+09 | 0.434785E+09 |
June | 0.596423E+09 | 39377515.23 | 0.557046E+09 | 0.112840E+10 | 0.275419E+09 |
July | 0.581484E+09 | 28265994.40 | 0.553218E+09 | 0.116577E+10 | 0.206398E+09 |
August | 0.517135E+09 | 5633296.63 | 0.511501E+09 | 0.105869E+10 | 0.176843E+09 |
September | 0.378295E+09 | 53252.70 | 0.378242E+09 | 0.571852E+09 | 0.409754E+09 |
October | 0.297218E+09 | 0.00 | 0.297218E+09 | 0.257387E+09 | 0.891118E+09 |
November | 0.257419E+09 | 0.00 | 0.257419E+09 | 0.126987E+09 | 0.116470E+10 |
December | 0.229957E+09 | 0.00 | 0.229957E+09 | 36398409.67 | 0.150620E+10 |
Annual Sum or Average | 0.475596E+10 | 93211676.32 | 0.466275E+10 | 0.618237E+10 | 0.966976E+10 |
Minimum of Months | 0.229957E+09 | 0.00 | 0.229957E+09 | 36398409.67 | 0.176843E+09 |
Maximum of Months | 0.596423E+09 | 39377515.23 | 0.557046E+09 | 0.116577E+10 | 0.178871E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248757E+09 | 0.00 | 0.248757E+09 | 39286614.67 | 0.178871E+10 |
February | 0.249040E+09 | 0.00 | 0.249040E+09 | 0.115633E+09 | 0.130247E+10 |
March | 0.387100E+09 | 0.00 | 0.387100E+09 | 0.298426E+09 | 0.868250E+09 |
April | 0.453129E+09 | 2009732.94 | 0.451119E+09 | 0.552939E+09 | 0.645101E+09 |
May | 0.560000E+09 | 17871884.42 | 0.542128E+09 | 0.830595E+09 | 0.434785E+09 |
June | 0.596423E+09 | 39377515.23 | 0.557046E+09 | 0.112840E+10 | 0.275419E+09 |
July | 0.581484E+09 | 28265994.40 | 0.553218E+09 | 0.116577E+10 | 0.206398E+09 |
August | 0.517135E+09 | 5633296.63 | 0.511501E+09 | 0.105869E+10 | 0.176843E+09 |
September | 0.378295E+09 | 53252.70 | 0.378242E+09 | 0.571852E+09 | 0.409754E+09 |
October | 0.297218E+09 | 0.00 | 0.297218E+09 | 0.257387E+09 | 0.891118E+09 |
November | 0.257419E+09 | 0.00 | 0.257419E+09 | 0.126987E+09 | 0.116470E+10 |
December | 0.229957E+09 | 0.00 | 0.229957E+09 | 36398409.67 | 0.150620E+10 |
Annual Sum or Average | 0.475596E+10 | 93211676.32 | 0.466275E+10 | 0.618237E+10 | 0.966976E+10 |
Minimum of Months | 0.229957E+09 | 0.00 | 0.229957E+09 | 36398409.67 | 0.176843E+09 |
Maximum of Months | 0.596423E+09 | 39377515.23 | 0.557046E+09 | 0.116577E+10 | 0.178871E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105104E+10 | 0.474071E+09 | 0.576970E+09 | 0.727018E+09 | 0.309207E+10 |
February | 0.119680E+10 | 0.643031E+09 | 0.553772E+09 | 0.117157E+10 | 0.227861E+10 |
March | 0.166704E+10 | 0.758884E+09 | 0.908160E+09 | 0.194499E+10 | 0.157867E+10 |
April | 0.195086E+10 | 0.889537E+09 | 0.106132E+10 | 0.277732E+10 | 0.121102E+10 |
May | 0.221359E+10 | 0.936093E+09 | 0.127750E+10 | 0.347524E+10 | 0.857226E+09 |
June | 0.221789E+10 | 0.929567E+09 | 0.128832E+10 | 0.396596E+10 | 0.549679E+09 |
July | 0.223461E+10 | 0.939459E+09 | 0.129515E+10 | 0.413087E+10 | 0.419230E+09 |
August | 0.204393E+10 | 0.810897E+09 | 0.123303E+10 | 0.383817E+10 | 0.359238E+09 |
September | 0.162564E+10 | 0.720278E+09 | 0.905366E+09 | 0.260991E+10 | 0.780289E+09 |
October | 0.143304E+10 | 0.745643E+09 | 0.687397E+09 | 0.181426E+10 | 0.161831E+10 |
November | 0.110877E+10 | 0.502044E+09 | 0.606724E+09 | 0.106032E+10 | 0.204664E+10 |
December | 0.992421E+09 | 0.452382E+09 | 0.540039E+09 | 0.723433E+09 | 0.260626E+10 |
Annual Sum or Average | 0.197356E+11 | 0.880189E+10 | 0.109338E+11 | 0.282390E+11 | 0.173972E+11 |
Minimum of Months | 0.992421E+09 | 0.452382E+09 | 0.540039E+09 | 0.723433E+09 | 0.359238E+09 |
Maximum of Months | 0.223461E+10 | 0.939459E+09 | 0.129515E+10 | 0.413087E+10 | 0.309207E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41557201.42 | 18744328.32 | 22812873.10 | 28745648.98 | 0.122258E+09 |
February | 47320506.07 | 25424863.36 | 21895642.72 | 46322782.35 | 90094165.00 |
March | 65913438.86 | 30005591.80 | 35907847.06 | 76903002.53 | 62419271.87 |
April | 77135194.26 | 35171493.49 | 41963700.77 | 0.109813E+09 | 47882660.94 |
May | 87523548.73 | 37012286.17 | 50511262.56 | 0.137408E+09 | 33893936.85 |
June | 87693210.88 | 36754233.49 | 50938977.38 | 0.156811E+09 | 21733819.96 |
July | 88354573.77 | 37145363.44 | 51209210.33 | 0.163331E+09 | 16575987.60 |
August | 80815226.94 | 32062140.92 | 48753086.02 | 0.151758E+09 | 14203957.16 |
September | 64276518.48 | 28479146.03 | 35797372.45 | 0.103193E+09 | 30851916.42 |
October | 56661118.88 | 29482041.05 | 27179077.83 | 71734092.21 | 63986688.24 |
November | 43839703.36 | 19850374.49 | 23989328.87 | 41924228.85 | 80922385.59 |
December | 39239425.34 | 17886781.13 | 21352644.21 | 28603908.37 | 0.103049E+09 |
Annual Sum or Average | 0.780330E+09 | 0.348019E+09 | 0.432311E+09 | 0.111655E+10 | 0.687871E+09 |
Minimum of Months | 39239425.34 | 17886781.13 | 21352644.21 | 28603908.37 | 14203957.16 |
Maximum of Months | 88354573.77 | 37145363.44 | 51209210.33 | 0.163331E+09 | 0.122258E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133037E+10 | 0.927527E+09 | 0.402843E+09 | 0.152109E+10 | 0.151832E+10 |
February | 0.112152E+10 | 0.751783E+09 | 0.369736E+09 | 0.140533E+10 | 0.117233E+10 |
March | 0.111669E+10 | 0.581952E+09 | 0.534742E+09 | 0.153665E+10 | 0.881084E+09 |
April | 0.809353E+09 | 0.263460E+09 | 0.545893E+09 | 0.126069E+10 | 0.682393E+09 |
May | 0.675724E+09 | 78536548.52 | 0.597187E+09 | 0.111480E+10 | 0.463821E+09 |
June | 0.604624E+09 | 33644551.71 | 0.570980E+09 | 0.118284E+10 | 0.293489E+09 |
July | 0.631639E+09 | 47098022.03 | 0.584540E+09 | 0.129460E+10 | 0.217209E+09 |
August | 0.754129E+09 | 0.140873E+09 | 0.613257E+09 | 0.155695E+10 | 0.192286E+09 |
September | 0.802601E+09 | 0.298524E+09 | 0.504077E+09 | 0.138824E+10 | 0.427408E+09 |
October | 0.120232E+10 | 0.778864E+09 | 0.423460E+09 | 0.177933E+10 | 0.888846E+09 |
November | 0.125176E+10 | 0.830643E+09 | 0.421114E+09 | 0.165492E+10 | 0.110467E+10 |
December | 0.131138E+10 | 0.922561E+09 | 0.388815E+09 | 0.158476E+10 | 0.134220E+10 |
Annual Sum or Average | 0.116121E+11 | 0.565547E+10 | 0.595665E+10 | 0.172802E+11 | 0.918406E+10 |
Minimum of Months | 0.604624E+09 | 33644551.71 | 0.369736E+09 | 0.111480E+10 | 0.192286E+09 |
Maximum of Months | 0.133037E+10 | 0.927527E+09 | 0.613257E+09 | 0.177933E+10 | 0.151832E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133037E+10 | 0.927527E+09 | 0.402843E+09 | 0.152109E+10 | 0.151832E+10 |
February | 0.112152E+10 | 0.751783E+09 | 0.369736E+09 | 0.140533E+10 | 0.117233E+10 |
March | 0.111669E+10 | 0.581952E+09 | 0.534742E+09 | 0.153665E+10 | 0.881084E+09 |
April | 0.809353E+09 | 0.263460E+09 | 0.545893E+09 | 0.126069E+10 | 0.682393E+09 |
May | 0.675724E+09 | 78536548.52 | 0.597187E+09 | 0.111480E+10 | 0.463821E+09 |
June | 0.604624E+09 | 33644551.71 | 0.570980E+09 | 0.118284E+10 | 0.293489E+09 |
July | 0.631639E+09 | 47098022.03 | 0.584540E+09 | 0.129460E+10 | 0.217209E+09 |
August | 0.754129E+09 | 0.140873E+09 | 0.613257E+09 | 0.155695E+10 | 0.192286E+09 |
September | 0.802601E+09 | 0.298524E+09 | 0.504077E+09 | 0.138824E+10 | 0.427408E+09 |
October | 0.120232E+10 | 0.778864E+09 | 0.423460E+09 | 0.177933E+10 | 0.888846E+09 |
November | 0.125176E+10 | 0.830643E+09 | 0.421114E+09 | 0.165492E+10 | 0.110467E+10 |
December | 0.131138E+10 | 0.922561E+09 | 0.388815E+09 | 0.158476E+10 | 0.134220E+10 |
Annual Sum or Average | 0.116121E+11 | 0.565547E+10 | 0.595665E+10 | 0.172802E+11 | 0.918406E+10 |
Minimum of Months | 0.604624E+09 | 33644551.71 | 0.369736E+09 | 0.111480E+10 | 0.192286E+09 |
Maximum of Months | 0.133037E+10 | 0.927527E+09 | 0.613257E+09 | 0.177933E+10 | 0.151832E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133029E+10 | 0.927469E+09 | 0.402817E+09 | 0.152099E+10 | 0.151822E+10 |
February | 0.112145E+10 | 0.751735E+09 | 0.369713E+09 | 0.140524E+10 | 0.117226E+10 |
March | 0.111662E+10 | 0.581915E+09 | 0.534708E+09 | 0.153656E+10 | 0.881028E+09 |
April | 0.809302E+09 | 0.263443E+09 | 0.545859E+09 | 0.126061E+10 | 0.682349E+09 |
May | 0.675681E+09 | 78531585.46 | 0.597149E+09 | 0.111473E+10 | 0.463792E+09 |
June | 0.604586E+09 | 33642425.56 | 0.570944E+09 | 0.118276E+10 | 0.293471E+09 |
July | 0.631599E+09 | 47095045.70 | 0.584504E+09 | 0.129452E+10 | 0.217195E+09 |
August | 0.754082E+09 | 0.140864E+09 | 0.613218E+09 | 0.155685E+10 | 0.192274E+09 |
September | 0.802550E+09 | 0.298505E+09 | 0.504045E+09 | 0.138815E+10 | 0.427381E+09 |
October | 0.120225E+10 | 0.778815E+09 | 0.423434E+09 | 0.177922E+10 | 0.888789E+09 |
November | 0.125168E+10 | 0.830591E+09 | 0.421088E+09 | 0.165481E+10 | 0.110460E+10 |
December | 0.131129E+10 | 0.922503E+09 | 0.388791E+09 | 0.158466E+10 | 0.134212E+10 |
Annual Sum or Average | 0.116114E+11 | 0.565511E+10 | 0.595627E+10 | 0.172791E+11 | 0.918348E+10 |
Minimum of Months | 0.604586E+09 | 33642425.56 | 0.369713E+09 | 0.111473E+10 | 0.192274E+09 |
Maximum of Months | 0.133029E+10 | 0.927469E+09 | 0.613218E+09 | 0.177922E+10 | 0.151822E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107957E+10 | 0.500778E+09 | 0.578790E+09 | 0.861086E+09 | 0.321883E+10 |
February | 0.111940E+10 | 0.523386E+09 | 0.596015E+09 | 0.117651E+10 | 0.241324E+10 |
March | 0.182671E+10 | 0.882705E+09 | 0.944005E+09 | 0.233838E+10 | 0.171682E+10 |
April | 0.198873E+10 | 0.910029E+09 | 0.107870E+10 | 0.293986E+10 | 0.132916E+10 |
May | 0.206535E+10 | 0.782478E+09 | 0.128288E+10 | 0.332663E+10 | 0.936912E+09 |
June | 0.210193E+10 | 0.808598E+09 | 0.129333E+10 | 0.381807E+10 | 0.609883E+09 |
July | 0.204868E+10 | 0.759579E+09 | 0.128910E+10 | 0.385468E+10 | 0.451654E+09 |
August | 0.200742E+10 | 0.750692E+09 | 0.125673E+10 | 0.380370E+10 | 0.397419E+09 |
September | 0.158274E+10 | 0.659277E+09 | 0.923461E+09 | 0.257363E+10 | 0.830432E+09 |
October | 0.145703E+10 | 0.756357E+09 | 0.700675E+09 | 0.198714E+10 | 0.175658E+10 |
November | 0.112531E+10 | 0.505094E+09 | 0.620213E+09 | 0.125916E+10 | 0.222946E+10 |
December | 0.959316E+09 | 0.419605E+09 | 0.539712E+09 | 0.819906E+09 | 0.278770E+10 |
Annual Sum or Average | 0.193622E+11 | 0.825858E+10 | 0.111036E+11 | 0.287588E+11 | 0.186781E+11 |
Minimum of Months | 0.959316E+09 | 0.419605E+09 | 0.539712E+09 | 0.819906E+09 | 0.397419E+09 |
Maximum of Months | 0.210193E+10 | 0.910029E+09 | 0.129333E+10 | 0.385468E+10 | 0.321883E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42685035.43 | 19800245.05 | 22884790.38 | 34046415.02 | 0.127270E+09 |
February | 44259987.63 | 20694142.70 | 23565844.93 | 46518065.46 | 95417348.09 |
March | 72226267.00 | 34901238.65 | 37325028.36 | 92457289.74 | 67881524.69 |
April | 78632209.33 | 35981626.23 | 42650583.10 | 0.116239E+09 | 52553898.84 |
May | 81662019.58 | 30938378.45 | 50723641.13 | 0.131532E+09 | 37044633.35 |
June | 83108020.92 | 31971121.65 | 51136899.27 | 0.150963E+09 | 24114188.04 |
July | 81002876.45 | 30032981.75 | 50969894.70 | 0.152410E+09 | 17857978.06 |
August | 79371262.08 | 29681575.71 | 49689686.37 | 0.150394E+09 | 15713582.62 |
September | 62579864.35 | 26067143.10 | 36512721.25 | 0.101759E+09 | 32834493.94 |
October | 57609595.62 | 29905591.65 | 27704003.97 | 78569338.41 | 69453650.24 |
November | 44493501.38 | 19970895.60 | 24522605.78 | 49785977.64 | 88150728.57 |
December | 37930402.25 | 16590743.33 | 21339658.92 | 32418222.28 | 0.110223E+09 |
Annual Sum or Average | 0.765561E+09 | 0.326536E+09 | 0.439025E+09 | 0.113709E+10 | 0.738515E+09 |
Minimum of Months | 37930402.25 | 16590743.33 | 21339658.92 | 32418222.28 | 15713582.62 |
Maximum of Months | 83108020.92 | 35981626.23 | 51136899.27 | 0.152410E+09 | 0.127270E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.746277E+09 | 0.00 | 0.746277E+09 | 0.110137E+09 | 0.541095E+10 |
February | 0.747125E+09 | 0.00 | 0.747125E+09 | 0.316197E+09 | 0.400752E+10 |
March | 0.116131E+10 | 0.00 | 0.116131E+10 | 0.783967E+09 | 0.279795E+10 |
April | 0.135940E+10 | 6029322.01 | 0.135337E+10 | 0.149858E+10 | 0.214421E+10 |
May | 0.168001E+10 | 53616748.83 | 0.162639E+10 | 0.236336E+10 | 0.143892E+10 |
June | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.332322E+10 | 0.879420E+09 |
July | 0.174447E+10 | 84799715.93 | 0.165967E+10 | 0.345113E+10 | 0.655459E+09 |
August | 0.155141E+10 | 16900235.20 | 0.153451E+10 | 0.315407E+10 | 0.549126E+09 |
September | 0.113489E+10 | 159761.37 | 0.113473E+10 | 0.171649E+10 | 0.120057E+10 |
October | 0.891659E+09 | 0.00 | 0.891659E+09 | 0.780871E+09 | 0.258784E+10 |
November | 0.772262E+09 | 0.00 | 0.772262E+09 | 0.393635E+09 | 0.339424E+10 |
December | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.105689E+09 | 0.443106E+10 |
Annual Sum or Average | 0.142680E+11 | 0.279641E+09 | 0.139883E+11 | 0.179974E+11 | 0.294973E+11 |
Minimum of Months | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.105689E+09 | 0.549126E+09 |
Maximum of Months | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.345113E+10 | 0.541095E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109261E+10 | 0.492825E+09 | 0.599790E+09 | 0.740082E+09 | 0.321262E+10 |
February | 0.124414E+10 | 0.668469E+09 | 0.575674E+09 | 0.118499E+10 | 0.239382E+10 |
March | 0.173298E+10 | 0.788905E+09 | 0.944080E+09 | 0.194471E+10 | 0.170079E+10 |
April | 0.202802E+10 | 0.924727E+09 | 0.110330E+10 | 0.279716E+10 | 0.133379E+10 |
May | 0.230115E+10 | 0.973125E+09 | 0.132803E+10 | 0.354071E+10 | 0.937211E+09 |
June | 0.230561E+10 | 0.966340E+09 | 0.133927E+10 | 0.408780E+10 | 0.582266E+09 |
July | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.427141E+10 | 0.436517E+09 |
August | 0.212478E+10 | 0.842976E+09 | 0.128180E+10 | 0.397947E+10 | 0.362643E+09 |
September | 0.168995E+10 | 0.748772E+09 | 0.941176E+09 | 0.271809E+10 | 0.762740E+09 |
October | 0.148972E+10 | 0.775140E+09 | 0.714585E+09 | 0.189892E+10 | 0.158222E+10 |
November | 0.115263E+10 | 0.521905E+09 | 0.630721E+09 | 0.112528E+10 | 0.201626E+10 |
December | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.751110E+09 | 0.261954E+10 |
Annual Sum or Average | 0.205163E+11 | 0.915008E+10 | 0.113662E+11 | 0.290397E+11 | 0.179404E+11 |
Minimum of Months | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.740082E+09 | 0.362643E+09 |
Maximum of Months | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.427141E+10 | 0.321262E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.399118E+10 | 0.278264E+10 | 0.120854E+10 | 0.445362E+10 | 0.451472E+10 |
February | 0.336461E+10 | 0.225539E+10 | 0.110922E+10 | 0.411168E+10 | 0.352532E+10 |
March | 0.335013E+10 | 0.174589E+10 | 0.160424E+10 | 0.445768E+10 | 0.272291E+10 |
April | 0.242809E+10 | 0.790395E+09 | 0.163769E+10 | 0.362195E+10 | 0.221116E+10 |
May | 0.202719E+10 | 0.235614E+09 | 0.179158E+10 | 0.321612E+10 | 0.152614E+10 |
June | 0.181389E+10 | 0.100936E+09 | 0.171295E+10 | 0.348480E+10 | 0.940403E+09 |
July | 0.189493E+10 | 0.141297E+09 | 0.175364E+10 | 0.383955E+10 | 0.687201E+09 |
August | 0.226241E+10 | 0.422627E+09 | 0.183979E+10 | 0.465614E+10 | 0.576790E+09 |
September | 0.240784E+10 | 0.895590E+09 | 0.151225E+10 | 0.415807E+10 | 0.122801E+10 |
October | 0.360703E+10 | 0.233664E+10 | 0.127039E+10 | 0.531904E+10 | 0.250454E+10 |
November | 0.375534E+10 | 0.249198E+10 | 0.126336E+10 | 0.494822E+10 | 0.311469E+10 |
December | 0.393420E+10 | 0.276774E+10 | 0.116646E+10 | 0.469732E+10 | 0.385165E+10 |
Annual Sum or Average | 0.348369E+11 | 0.169667E+11 | 0.178701E+11 | 0.509642E+11 | 0.274035E+11 |
Minimum of Months | 0.181389E+10 | 0.100936E+09 | 0.110922E+10 | 0.321612E+10 | 0.576790E+09 |
Maximum of Months | 0.399118E+10 | 0.278264E+10 | 0.183979E+10 | 0.531904E+10 | 0.451472E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112227E+10 | 0.520587E+09 | 0.601681E+09 | 0.871783E+09 | 0.334337E+10 |
February | 0.116368E+10 | 0.544089E+09 | 0.619587E+09 | 0.118767E+10 | 0.253954E+10 |
March | 0.189896E+10 | 0.917621E+09 | 0.981340E+09 | 0.235523E+10 | 0.184531E+10 |
April | 0.206738E+10 | 0.946027E+09 | 0.112136E+10 | 0.296565E+10 | 0.146046E+10 |
May | 0.214704E+10 | 0.813430E+09 | 0.133361E+10 | 0.339179E+10 | 0.102523E+10 |
June | 0.218506E+10 | 0.840583E+09 | 0.134448E+10 | 0.393306E+10 | 0.647330E+09 |
July | 0.212971E+10 | 0.789625E+09 | 0.134009E+10 | 0.398449E+10 | 0.472668E+09 |
August | 0.208681E+10 | 0.780386E+09 | 0.130643E+10 | 0.394430E+10 | 0.400746E+09 |
September | 0.164534E+10 | 0.685356E+09 | 0.959983E+09 | 0.268149E+10 | 0.813994E+09 |
October | 0.151466E+10 | 0.786276E+09 | 0.728386E+09 | 0.207499E+10 | 0.172140E+10 |
November | 0.116982E+10 | 0.525073E+09 | 0.644742E+09 | 0.132105E+10 | 0.220799E+10 |
December | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.845040E+09 | 0.281220E+10 |
Annual Sum or Average | 0.201280E+11 | 0.858525E+10 | 0.115427E+11 | 0.295565E+11 | 0.192903E+11 |
Minimum of Months | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.845040E+09 | 0.400746E+09 |
Maximum of Months | 0.218506E+10 | 0.946027E+09 | 0.134448E+10 | 0.398449E+10 | 0.334337E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 45.13 | 1929.07 | 278.63 | 0.00 | 278.63 | 0.00 | 0.00 |
February | 136.94 | 1574.62 | 308.83 | 0.00 | 308.83 | 0.00 | 0.00 |
March | 304.47 | 979.01 | 433.58 | 0.00 | 433.58 | 0.00 | 0.00 |
April | 585.92 | 784.92 | 524.46 | 2.33 | 522.13 | 0.00 | 0.00 |
May | 883.18 | 516.03 | 627.24 | 20.02 | 607.23 | 0.00 | 0.00 |
June | 1276.03 | 330.54 | 690.31 | 45.58 | 644.73 | 0.00 | 0.00 |
July | 1278.27 | 240.68 | 651.31 | 31.66 | 619.65 | 0.00 | 0.00 |
August | 1168.57 | 200.71 | 579.23 | 6.31 | 572.92 | 0.00 | 0.00 |
September | 666.78 | 433.44 | 437.84 | 0.06 | 437.78 | 0.00 | 0.00 |
October | 305.27 | 892.47 | 332.91 | 0.00 | 332.91 | 0.00 | 0.00 |
November | 171.01 | 1210.01 | 297.94 | 0.00 | 297.94 | 0.00 | 0.00 |
December | 45.66 | 1538.14 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Annual Sum or Average | 574.72 | 882.29 | 452.43 | 8.87 | 443.57 | 0.00 | 0.00 |
Minimum of Months | 45.13 | 200.71 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Maximum of Months | 1278.27 | 1929.07 | 690.31 | 45.58 | 644.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 285.27 | 1143.75 | 407.94 | 184.00 | 223.94 | 0.00 | 0.00 |
February | 499.41 | 940.25 | 514.28 | 276.32 | 237.96 | 0.00 | 0.00 |
March | 736.67 | 599.36 | 647.02 | 294.54 | 352.48 | 0.00 | 0.00 |
April | 1084.08 | 492.17 | 782.42 | 356.76 | 425.66 | 0.00 | 0.00 |
May | 1320.78 | 338.60 | 859.15 | 363.32 | 495.83 | 0.00 | 0.00 |
June | 1571.38 | 219.63 | 889.51 | 372.82 | 516.70 | 0.00 | 0.00 |
July | 1586.64 | 160.49 | 867.31 | 364.63 | 502.68 | 0.00 | 0.00 |
August | 1478.34 | 132.76 | 793.30 | 314.73 | 478.57 | 0.00 | 0.00 |
September | 1050.72 | 277.48 | 651.99 | 288.88 | 363.11 | 0.00 | 0.00 |
October | 719.80 | 551.23 | 556.20 | 289.40 | 266.80 | 0.00 | 0.00 |
November | 453.50 | 722.61 | 444.69 | 201.35 | 243.33 | 0.00 | 0.00 |
December | 292.36 | 909.47 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Annual Sum or Average | 925.45 | 538.60 | 650.57 | 290.15 | 360.42 | 0.00 | 0.00 |
Minimum of Months | 285.27 | 132.76 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Maximum of Months | 1586.64 | 1143.75 | 889.51 | 372.82 | 516.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1684.34 | 1601.19 | 1490.14 | 1038.92 | 451.22 | 0.00 | 0.00 |
February | 1715.63 | 1379.36 | 1390.80 | 932.29 | 458.51 | 0.00 | 0.00 |
March | 1677.66 | 955.30 | 1250.80 | 651.84 | 598.96 | 0.00 | 0.00 |
April | 1403.71 | 810.27 | 936.76 | 304.94 | 631.83 | 0.00 | 0.00 |
May | 1200.13 | 546.06 | 756.87 | 87.97 | 668.90 | 0.00 | 0.00 |
June | 1337.73 | 351.30 | 699.80 | 38.94 | 660.86 | 0.00 | 0.00 |
July | 1423.51 | 250.65 | 707.49 | 52.75 | 654.73 | 0.00 | 0.00 |
August | 1728.58 | 209.89 | 844.69 | 157.79 | 686.90 | 0.00 | 0.00 |
September | 1606.94 | 444.80 | 928.95 | 345.52 | 583.43 | 0.00 | 0.00 |
October | 1998.67 | 870.22 | 1346.71 | 872.40 | 474.31 | 0.00 | 0.00 |
November | 1936.77 | 1113.90 | 1448.82 | 961.41 | 487.41 | 0.00 | 0.00 |
December | 1779.54 | 1336.13 | 1468.86 | 1033.36 | 435.51 | 0.00 | 0.00 |
Annual Sum or Average | 1624.27 | 819.41 | 1104.67 | 538.01 | 566.66 | 0.00 | 0.00 |
Minimum of Months | 1200.13 | 209.89 | 699.80 | 38.94 | 435.51 | 0.00 | 0.00 |
Maximum of Months | 1998.67 | 1601.19 | 1490.14 | 1038.92 | 686.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 330.81 | 1189.92 | 419.01 | 194.36 | 224.64 | 0.00 | 0.00 |
February | 495.84 | 996.90 | 481.02 | 224.90 | 256.11 | 0.00 | 0.00 |
March | 885.69 | 647.16 | 708.99 | 342.60 | 366.39 | 0.00 | 0.00 |
April | 1148.57 | 535.04 | 797.60 | 364.98 | 432.62 | 0.00 | 0.00 |
May | 1266.82 | 366.68 | 801.61 | 303.70 | 497.91 | 0.00 | 0.00 |
June | 1512.63 | 241.45 | 843.00 | 324.30 | 518.70 | 0.00 | 0.00 |
July | 1481.71 | 172.18 | 795.14 | 294.81 | 500.33 | 0.00 | 0.00 |
August | 1467.02 | 145.80 | 779.13 | 291.36 | 487.76 | 0.00 | 0.00 |
September | 1038.59 | 293.72 | 634.78 | 264.41 | 370.36 | 0.00 | 0.00 |
October | 782.60 | 596.28 | 565.51 | 293.56 | 271.95 | 0.00 | 0.00 |
November | 522.56 | 790.00 | 451.32 | 202.57 | 248.74 | 0.00 | 0.00 |
December | 323.01 | 977.37 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Annual Sum or Average | 940.33 | 577.19 | 638.25 | 272.24 | 366.02 | 0.00 | 0.00 |
Minimum of Months | 323.01 | 145.80 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Maximum of Months | 1512.63 | 1189.92 | 843.00 | 364.98 | 518.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 44.00 | 2003.44 | 278.62 | 0.00 | 278.62 | 0.00 | 0.00 |
February | 143.39 | 1615.13 | 308.83 | 0.00 | 308.83 | 0.00 | 0.00 |
March | 334.26 | 972.48 | 433.57 | 0.00 | 433.57 | 0.00 | 0.00 |
April | 639.97 | 746.63 | 524.45 | 2.33 | 522.12 | 0.00 | 0.00 |
May | 930.31 | 486.98 | 627.23 | 20.02 | 607.21 | 0.00 | 0.00 |
June | 1306.00 | 318.77 | 690.30 | 45.58 | 644.72 | 0.00 | 0.00 |
July | 1305.73 | 231.18 | 651.30 | 31.66 | 619.64 | 0.00 | 0.00 |
August | 1185.79 | 198.07 | 579.22 | 6.31 | 572.91 | 0.00 | 0.00 |
September | 661.86 | 474.24 | 437.84 | 0.06 | 437.77 | 0.00 | 0.00 |
October | 288.29 | 998.10 | 332.90 | 0.00 | 332.90 | 0.00 | 0.00 |
November | 146.98 | 1348.01 | 297.93 | 0.00 | 297.93 | 0.00 | 0.00 |
December | 40.77 | 1687.02 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Annual Sum or Average | 588.12 | 919.86 | 452.43 | 8.87 | 443.56 | 0.00 | 0.00 |
Minimum of Months | 40.77 | 198.07 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Maximum of Months | 1306.00 | 2003.44 | 690.30 | 45.58 | 644.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 282.17 | 1200.09 | 407.93 | 184.00 | 223.93 | 0.00 | 0.00 |
February | 503.43 | 979.13 | 514.27 | 276.31 | 237.96 | 0.00 | 0.00 |
March | 754.89 | 612.71 | 647.01 | 294.54 | 352.47 | 0.00 | 0.00 |
April | 1113.86 | 485.69 | 782.41 | 356.75 | 425.65 | 0.00 | 0.00 |
May | 1348.81 | 332.71 | 859.14 | 363.32 | 495.82 | 0.00 | 0.00 |
June | 1590.58 | 220.45 | 889.50 | 372.81 | 516.69 | 0.00 | 0.00 |
July | 1603.27 | 162.71 | 867.30 | 364.62 | 502.67 | 0.00 | 0.00 |
August | 1489.67 | 139.43 | 793.29 | 314.72 | 478.56 | 0.00 | 0.00 |
September | 1046.72 | 312.94 | 651.98 | 288.87 | 363.10 | 0.00 | 0.00 |
October | 704.15 | 628.10 | 556.19 | 289.40 | 266.79 | 0.00 | 0.00 |
November | 425.25 | 820.82 | 444.68 | 201.35 | 243.33 | 0.00 | 0.00 |
December | 280.78 | 1011.54 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Annual Sum or Average | 930.86 | 573.48 | 650.56 | 290.14 | 360.42 | 0.00 | 0.00 |
Minimum of Months | 280.78 | 139.43 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Maximum of Months | 1603.27 | 1200.09 | 889.50 | 372.81 | 516.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1703.69 | 1700.59 | 1490.08 | 1038.88 | 451.20 | 0.00 | 0.00 |
February | 1742.68 | 1453.75 | 1390.74 | 932.25 | 458.49 | 0.00 | 0.00 |
March | 1721.13 | 986.86 | 1250.75 | 651.81 | 598.94 | 0.00 | 0.00 |
April | 1459.10 | 789.79 | 936.73 | 304.92 | 631.81 | 0.00 | 0.00 |
May | 1248.63 | 519.50 | 756.84 | 87.96 | 668.88 | 0.00 | 0.00 |
June | 1368.99 | 339.68 | 699.78 | 38.94 | 660.84 | 0.00 | 0.00 |
July | 1450.01 | 243.28 | 707.47 | 52.75 | 654.71 | 0.00 | 0.00 |
August | 1743.86 | 215.37 | 844.66 | 157.78 | 686.88 | 0.00 | 0.00 |
September | 1606.72 | 494.68 | 928.92 | 345.51 | 583.41 | 0.00 | 0.00 |
October | 1992.94 | 995.55 | 1346.66 | 872.37 | 474.30 | 0.00 | 0.00 |
November | 1915.37 | 1278.53 | 1448.76 | 961.37 | 487.39 | 0.00 | 0.00 |
December | 1775.01 | 1503.33 | 1468.80 | 1033.31 | 435.49 | 0.00 | 0.00 |
Annual Sum or Average | 1643.82 | 873.66 | 1104.63 | 537.99 | 566.64 | 0.00 | 0.00 |
Minimum of Months | 1248.63 | 215.37 | 699.78 | 38.94 | 435.49 | 0.00 | 0.00 |
Maximum of Months | 1992.94 | 1700.59 | 1490.08 | 1038.88 | 686.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 334.20 | 1249.29 | 419.00 | 194.36 | 224.64 | 0.00 | 0.00 |
February | 505.55 | 1036.98 | 481.01 | 224.90 | 256.11 | 0.00 | 0.00 |
March | 907.57 | 666.33 | 708.98 | 342.59 | 366.39 | 0.00 | 0.00 |
April | 1179.05 | 533.07 | 797.59 | 364.97 | 432.62 | 0.00 | 0.00 |
May | 1291.13 | 363.63 | 801.60 | 303.69 | 497.91 | 0.00 | 0.00 |
June | 1531.26 | 244.60 | 842.99 | 324.29 | 518.70 | 0.00 | 0.00 |
July | 1496.08 | 175.30 | 795.13 | 294.81 | 500.33 | 0.00 | 0.00 |
August | 1476.29 | 154.25 | 779.12 | 291.36 | 487.76 | 0.00 | 0.00 |
September | 1032.17 | 333.05 | 634.77 | 264.41 | 370.36 | 0.00 | 0.00 |
October | 771.25 | 681.76 | 565.50 | 293.56 | 271.95 | 0.00 | 0.00 |
November | 505.00 | 894.14 | 451.31 | 202.57 | 248.74 | 0.00 | 0.00 |
December | 318.22 | 1081.96 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Annual Sum or Average | 947.99 | 615.70 | 638.25 | 272.23 | 366.01 | 0.00 | 0.00 |
Minimum of Months | 318.22 | 154.25 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Maximum of Months | 1531.26 | 1249.29 | 842.99 | 364.97 | 518.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 41.12 | 2020.22 | 278.63 | 0.00 | 278.63 | 0.00 | 0.00 |
February | 130.70 | 1656.55 | 308.83 | 0.00 | 308.83 | 0.00 | 0.00 |
March | 292.70 | 1044.63 | 433.58 | 0.00 | 433.58 | 0.00 | 0.00 |
April | 578.16 | 827.24 | 524.46 | 2.33 | 522.13 | 0.00 | 0.00 |
May | 882.38 | 537.23 | 627.24 | 20.02 | 607.23 | 0.00 | 0.00 |
June | 1282.11 | 339.28 | 690.31 | 45.58 | 644.73 | 0.00 | 0.00 |
July | 1288.51 | 244.72 | 651.31 | 31.66 | 619.65 | 0.00 | 0.00 |
August | 1177.60 | 205.02 | 579.23 | 6.31 | 572.92 | 0.00 | 0.00 |
September | 662.23 | 463.18 | 437.84 | 0.06 | 437.78 | 0.00 | 0.00 |
October | 291.54 | 966.19 | 332.91 | 0.00 | 332.91 | 0.00 | 0.00 |
November | 151.87 | 1309.51 | 297.94 | 0.00 | 297.94 | 0.00 | 0.00 |
December | 39.46 | 1654.37 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Annual Sum or Average | 570.69 | 935.35 | 452.43 | 8.87 | 443.57 | 0.00 | 0.00 |
Minimum of Months | 39.46 | 205.02 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Maximum of Months | 1288.51 | 2020.22 | 690.31 | 45.58 | 644.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 276.31 | 1199.45 | 407.94 | 184.00 | 223.94 | 0.00 | 0.00 |
February | 489.83 | 989.51 | 514.28 | 276.32 | 237.96 | 0.00 | 0.00 |
March | 726.07 | 635.00 | 647.02 | 294.54 | 352.48 | 0.00 | 0.00 |
April | 1079.15 | 514.58 | 782.42 | 356.76 | 425.66 | 0.00 | 0.00 |
May | 1321.95 | 349.91 | 859.15 | 363.32 | 495.83 | 0.00 | 0.00 |
June | 1577.08 | 224.64 | 889.51 | 372.82 | 516.70 | 0.00 | 0.00 |
July | 1594.76 | 162.98 | 867.31 | 364.63 | 502.68 | 0.00 | 0.00 |
August | 1485.76 | 135.40 | 793.30 | 314.73 | 478.57 | 0.00 | 0.00 |
September | 1048.65 | 294.27 | 651.99 | 288.88 | 363.11 | 0.00 | 0.00 |
October | 708.98 | 590.73 | 556.20 | 289.40 | 266.80 | 0.00 | 0.00 |
November | 434.14 | 777.88 | 444.69 | 201.35 | 243.33 | 0.00 | 0.00 |
December | 280.43 | 978.02 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Annual Sum or Average | 920.84 | 568.89 | 650.57 | 290.15 | 360.42 | 0.00 | 0.00 |
Minimum of Months | 276.31 | 135.40 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Maximum of Months | 1594.76 | 1199.45 | 889.51 | 372.82 | 516.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1662.79 | 1685.60 | 1490.14 | 1038.92 | 451.22 | 0.00 | 0.00 |
February | 1699.60 | 1457.23 | 1390.80 | 932.29 | 458.51 | 0.00 | 0.00 |
March | 1664.31 | 1016.62 | 1250.80 | 651.84 | 598.96 | 0.00 | 0.00 |
April | 1397.36 | 853.07 | 936.76 | 304.94 | 631.83 | 0.00 | 0.00 |
May | 1200.76 | 569.80 | 756.87 | 87.97 | 668.90 | 0.00 | 0.00 |
June | 1344.44 | 362.81 | 699.80 | 38.94 | 660.86 | 0.00 | 0.00 |
July | 1433.52 | 256.57 | 707.49 | 52.75 | 654.73 | 0.00 | 0.00 |
August | 1738.40 | 215.35 | 844.69 | 157.79 | 686.90 | 0.00 | 0.00 |
September | 1604.19 | 473.77 | 928.95 | 345.52 | 583.43 | 0.00 | 0.00 |
October | 1985.90 | 935.09 | 1346.71 | 872.40 | 474.31 | 0.00 | 0.00 |
November | 1909.04 | 1201.65 | 1448.82 | 961.41 | 487.41 | 0.00 | 0.00 |
December | 1753.78 | 1438.04 | 1468.86 | 1033.36 | 435.51 | 0.00 | 0.00 |
Annual Sum or Average | 1616.06 | 868.96 | 1104.67 | 538.01 | 566.66 | 0.00 | 0.00 |
Minimum of Months | 1200.76 | 215.35 | 699.80 | 38.94 | 435.51 | 0.00 | 0.00 |
Maximum of Months | 1985.90 | 1685.60 | 1490.14 | 1038.92 | 686.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 325.49 | 1248.27 | 419.01 | 194.36 | 224.64 | 0.00 | 0.00 |
February | 490.93 | 1049.74 | 481.02 | 224.90 | 256.11 | 0.00 | 0.00 |
March | 879.34 | 688.96 | 708.99 | 342.60 | 366.39 | 0.00 | 0.00 |
April | 1144.15 | 563.45 | 797.60 | 364.98 | 432.62 | 0.00 | 0.00 |
May | 1266.35 | 382.78 | 801.61 | 303.70 | 497.91 | 0.00 | 0.00 |
June | 1517.38 | 249.74 | 843.00 | 324.30 | 518.70 | 0.00 | 0.00 |
July | 1487.64 | 176.47 | 795.14 | 294.81 | 500.33 | 0.00 | 0.00 |
August | 1472.63 | 149.62 | 779.13 | 291.36 | 487.76 | 0.00 | 0.00 |
September | 1034.53 | 314.04 | 634.78 | 264.41 | 370.36 | 0.00 | 0.00 |
October | 774.71 | 642.70 | 565.51 | 293.56 | 271.95 | 0.00 | 0.00 |
November | 509.66 | 851.85 | 451.32 | 202.57 | 248.74 | 0.00 | 0.00 |
December | 315.50 | 1049.96 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Annual Sum or Average | 937.23 | 611.69 | 638.25 | 272.24 | 366.02 | 0.00 | 0.00 |
Minimum of Months | 315.50 | 149.62 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Maximum of Months | 1517.38 | 1248.27 | 843.00 | 364.98 | 518.70 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.120879E+09 | 0.516683E+10 | 0.746277E+09 | 0.00 | 0.746277E+09 | 0.00 | 0.00 |
February | 0.331290E+09 | 0.380931E+10 | 0.747125E+09 | 0.00 | 0.747125E+09 | 0.00 | 0.00 |
March | 0.815485E+09 | 0.262219E+10 | 0.116131E+10 | 0.00 | 0.116131E+10 | 0.00 | 0.00 |
April | 0.151871E+10 | 0.203452E+10 | 0.135940E+10 | 6029322.01 | 0.135337E+10 | 0.00 | 0.00 |
May | 0.236552E+10 | 0.138215E+10 | 0.168001E+10 | 53616748.83 | 0.162639E+10 | 0.00 | 0.00 |
June | 0.330747E+10 | 0.856761E+09 | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.00 | 0.00 |
July | 0.342372E+10 | 0.644626E+09 | 0.174447E+10 | 84799715.93 | 0.165967E+10 | 0.00 | 0.00 |
August | 0.312990E+10 | 0.537584E+09 | 0.155141E+10 | 16900235.20 | 0.153451E+10 | 0.00 | 0.00 |
September | 0.172830E+10 | 0.112347E+10 | 0.113489E+10 | 159761.37 | 0.113473E+10 | 0.00 | 0.00 |
October | 0.817640E+09 | 0.239039E+10 | 0.891659E+09 | 0.00 | 0.891659E+09 | 0.00 | 0.00 |
November | 0.443268E+09 | 0.313634E+10 | 0.772262E+09 | 0.00 | 0.772262E+09 | 0.00 | 0.00 |
December | 0.122298E+09 | 0.411975E+10 | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.181245E+11 | 0.278239E+11 | 0.142680E+11 | 0.279641E+09 | 0.139883E+11 | 0.00 | 0.00 |
Minimum of Months | 0.120879E+09 | 0.537584E+09 | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.00 | 0.00 |
Maximum of Months | 0.342372E+10 | 0.516683E+10 | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.764069E+09 | 0.306341E+10 | 0.109261E+10 | 0.492825E+09 | 0.599790E+09 | 0.00 | 0.00 |
February | 0.120817E+10 | 0.227466E+10 | 0.124414E+10 | 0.668469E+09 | 0.575674E+09 | 0.00 | 0.00 |
March | 0.197310E+10 | 0.160534E+10 | 0.173298E+10 | 0.788905E+09 | 0.944080E+09 | 0.00 | 0.00 |
April | 0.280994E+10 | 0.127571E+10 | 0.202802E+10 | 0.924727E+09 | 0.110330E+10 | 0.00 | 0.00 |
May | 0.353757E+10 | 0.906918E+09 | 0.230115E+10 | 0.973125E+09 | 0.132803E+10 | 0.00 | 0.00 |
June | 0.407301E+10 | 0.569288E+09 | 0.230561E+10 | 0.966340E+09 | 0.133927E+10 | 0.00 | 0.00 |
July | 0.424967E+10 | 0.429846E+09 | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.00 | 0.00 |
August | 0.395957E+10 | 0.355588E+09 | 0.212478E+10 | 0.842976E+09 | 0.128180E+10 | 0.00 | 0.00 |
September | 0.272347E+10 | 0.719222E+09 | 0.168995E+10 | 0.748772E+09 | 0.941176E+09 | 0.00 | 0.00 |
October | 0.192792E+10 | 0.147641E+10 | 0.148972E+10 | 0.775140E+09 | 0.714585E+09 | 0.00 | 0.00 |
November | 0.117546E+10 | 0.187300E+10 | 0.115263E+10 | 0.521905E+09 | 0.630721E+09 | 0.00 | 0.00 |
December | 0.783052E+09 | 0.243592E+10 | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.291850E+11 | 0.169853E+11 | 0.205163E+11 | 0.915008E+10 | 0.113662E+11 | 0.00 | 0.00 |
Minimum of Months | 0.764069E+09 | 0.355588E+09 | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.00 | 0.00 |
Maximum of Months | 0.424967E+10 | 0.306341E+10 | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.451135E+10 | 0.428863E+10 | 0.399118E+10 | 0.278264E+10 | 0.120854E+10 | 0.00 | 0.00 |
February | 0.415044E+10 | 0.333695E+10 | 0.336461E+10 | 0.225539E+10 | 0.110922E+10 | 0.00 | 0.00 |
March | 0.449345E+10 | 0.255867E+10 | 0.335013E+10 | 0.174589E+10 | 0.160424E+10 | 0.00 | 0.00 |
April | 0.363841E+10 | 0.210021E+10 | 0.242809E+10 | 0.790395E+09 | 0.163769E+10 | 0.00 | 0.00 |
May | 0.321442E+10 | 0.146257E+10 | 0.202719E+10 | 0.235614E+09 | 0.179158E+10 | 0.00 | 0.00 |
June | 0.346740E+10 | 0.910557E+09 | 0.181389E+10 | 0.100936E+09 | 0.171295E+10 | 0.00 | 0.00 |
July | 0.381272E+10 | 0.671353E+09 | 0.189493E+10 | 0.141297E+09 | 0.175364E+10 | 0.00 | 0.00 |
August | 0.462984E+10 | 0.562164E+09 | 0.226241E+10 | 0.422627E+09 | 0.183979E+10 | 0.00 | 0.00 |
September | 0.416520E+10 | 0.115293E+10 | 0.240784E+10 | 0.895590E+09 | 0.151225E+10 | 0.00 | 0.00 |
October | 0.535324E+10 | 0.233081E+10 | 0.360703E+10 | 0.233664E+10 | 0.127039E+10 | 0.00 | 0.00 |
November | 0.502012E+10 | 0.288723E+10 | 0.375534E+10 | 0.249198E+10 | 0.126336E+10 | 0.00 | 0.00 |
December | 0.476632E+10 | 0.357869E+10 | 0.393420E+10 | 0.276774E+10 | 0.116646E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.512229E+11 | 0.258408E+11 | 0.348369E+11 | 0.169667E+11 | 0.178701E+11 | 0.00 | 0.00 |
Minimum of Months | 0.321442E+10 | 0.562164E+09 | 0.181389E+10 | 0.100936E+09 | 0.110922E+10 | 0.00 | 0.00 |
Maximum of Months | 0.535324E+10 | 0.428863E+10 | 0.399118E+10 | 0.278264E+10 | 0.183979E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.886029E+09 | 0.318707E+10 | 0.112227E+10 | 0.520587E+09 | 0.601681E+09 | 0.00 | 0.00 |
February | 0.119954E+10 | 0.241170E+10 | 0.116368E+10 | 0.544089E+09 | 0.619587E+09 | 0.00 | 0.00 |
March | 0.237223E+10 | 0.173334E+10 | 0.189896E+10 | 0.917621E+09 | 0.981340E+09 | 0.00 | 0.00 |
April | 0.297710E+10 | 0.138683E+10 | 0.206738E+10 | 0.946027E+09 | 0.112136E+10 | 0.00 | 0.00 |
May | 0.339305E+10 | 0.982116E+09 | 0.214704E+10 | 0.813430E+09 | 0.133361E+10 | 0.00 | 0.00 |
June | 0.392075E+10 | 0.625833E+09 | 0.218506E+10 | 0.840583E+09 | 0.134448E+10 | 0.00 | 0.00 |
July | 0.396861E+10 | 0.461154E+09 | 0.212971E+10 | 0.789625E+09 | 0.134009E+10 | 0.00 | 0.00 |
August | 0.392927E+10 | 0.390504E+09 | 0.208681E+10 | 0.780386E+09 | 0.130643E+10 | 0.00 | 0.00 |
September | 0.269202E+10 | 0.761329E+09 | 0.164534E+10 | 0.685356E+09 | 0.959983E+09 | 0.00 | 0.00 |
October | 0.209611E+10 | 0.159707E+10 | 0.151466E+10 | 0.786276E+09 | 0.728386E+09 | 0.00 | 0.00 |
November | 0.135448E+10 | 0.204768E+10 | 0.116982E+10 | 0.525073E+09 | 0.644742E+09 | 0.00 | 0.00 |
December | 0.865153E+09 | 0.261778E+10 | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.296543E+11 | 0.182024E+11 | 0.201280E+11 | 0.858525E+10 | 0.115427E+11 | 0.00 | 0.00 |
Minimum of Months | 0.865153E+09 | 0.390504E+09 | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.396861E+10 | 0.318707E+10 | 0.218506E+10 | 0.946027E+09 | 0.134448E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117859E+09 | 0.536602E+10 | 0.746261E+09 | 0.00 | 0.746261E+09 | 0.00 | 0.00 |
February | 0.346894E+09 | 0.390733E+10 | 0.747110E+09 | 0.00 | 0.747110E+09 | 0.00 | 0.00 |
March | 0.895269E+09 | 0.260470E+10 | 0.116128E+10 | 0.00 | 0.116128E+10 | 0.00 | 0.00 |
April | 0.165879E+10 | 0.193527E+10 | 0.135937E+10 | 6029144.79 | 0.135334E+10 | 0.00 | 0.00 |
May | 0.249175E+10 | 0.130433E+10 | 0.167998E+10 | 53615172.89 | 0.162636E+10 | 0.00 | 0.00 |
June | 0.338516E+10 | 0.826242E+09 | 0.178925E+10 | 0.118131E+09 | 0.167111E+10 | 0.00 | 0.00 |
July | 0.349726E+10 | 0.619185E+09 | 0.174443E+10 | 84797223.43 | 0.165963E+10 | 0.00 | 0.00 |
August | 0.317602E+10 | 0.530521E+09 | 0.155138E+10 | 16899738.46 | 0.153448E+10 | 0.00 | 0.00 |
September | 0.171553E+10 | 0.122924E+10 | 0.113487E+10 | 159756.68 | 0.113471E+10 | 0.00 | 0.00 |
October | 0.772152E+09 | 0.267330E+10 | 0.891642E+09 | 0.00 | 0.891642E+09 | 0.00 | 0.00 |
November | 0.380959E+09 | 0.349404E+10 | 0.772246E+09 | 0.00 | 0.772246E+09 | 0.00 | 0.00 |
December | 0.109195E+09 | 0.451852E+10 | 0.689863E+09 | 0.00 | 0.689863E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.185468E+11 | 0.290087E+11 | 0.142677E+11 | 0.279633E+09 | 0.139880E+11 | 0.00 | 0.00 |
Minimum of Months | 0.109195E+09 | 0.530521E+09 | 0.689863E+09 | 0.00 | 0.689863E+09 | 0.00 | 0.00 |
Maximum of Months | 0.349726E+10 | 0.536602E+10 | 0.178925E+10 | 0.118131E+09 | 0.167111E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.755764E+09 | 0.321432E+10 | 0.109260E+10 | 0.492815E+09 | 0.599783E+09 | 0.00 | 0.00 |
February | 0.121789E+10 | 0.236870E+10 | 0.124412E+10 | 0.668456E+09 | 0.575668E+09 | 0.00 | 0.00 |
March | 0.202189E+10 | 0.164109E+10 | 0.173296E+10 | 0.788890E+09 | 0.944068E+09 | 0.00 | 0.00 |
April | 0.288713E+10 | 0.125890E+10 | 0.202799E+10 | 0.924709E+09 | 0.110329E+10 | 0.00 | 0.00 |
May | 0.361265E+10 | 0.891120E+09 | 0.230112E+10 | 0.973106E+09 | 0.132801E+10 | 0.00 | 0.00 |
June | 0.412277E+10 | 0.571413E+09 | 0.230558E+10 | 0.966321E+09 | 0.133926E+10 | 0.00 | 0.00 |
July | 0.429420E+10 | 0.435806E+09 | 0.232297E+10 | 0.976604E+09 | 0.134636E+10 | 0.00 | 0.00 |
August | 0.398992E+10 | 0.373442E+09 | 0.212475E+10 | 0.842959E+09 | 0.128179E+10 | 0.00 | 0.00 |
September | 0.271310E+10 | 0.811141E+09 | 0.168992E+10 | 0.748757E+09 | 0.941164E+09 | 0.00 | 0.00 |
October | 0.188599E+10 | 0.168230E+10 | 0.148970E+10 | 0.775125E+09 | 0.714577E+09 | 0.00 | 0.00 |
November | 0.110225E+10 | 0.212756E+10 | 0.115261E+10 | 0.521895E+09 | 0.630714E+09 | 0.00 | 0.00 |
December | 0.752037E+09 | 0.270931E+10 | 0.103166E+10 | 0.470269E+09 | 0.561391E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.293556E+11 | 0.180851E+11 | 0.205160E+11 | 0.914990E+10 | 0.113661E+11 | 0.00 | 0.00 |
Minimum of Months | 0.752037E+09 | 0.373442E+09 | 0.103166E+10 | 0.470269E+09 | 0.561391E+09 | 0.00 | 0.00 |
Maximum of Months | 0.429420E+10 | 0.321432E+10 | 0.232297E+10 | 0.976604E+09 | 0.134636E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.456317E+10 | 0.455486E+10 | 0.399103E+10 | 0.278252E+10 | 0.120850E+10 | 0.00 | 0.00 |
February | 0.421589E+10 | 0.351692E+10 | 0.336449E+10 | 0.225530E+10 | 0.110919E+10 | 0.00 | 0.00 |
March | 0.460986E+10 | 0.264320E+10 | 0.335001E+10 | 0.174582E+10 | 0.160419E+10 | 0.00 | 0.00 |
April | 0.378198E+10 | 0.204713E+10 | 0.242801E+10 | 0.790362E+09 | 0.163765E+10 | 0.00 | 0.00 |
May | 0.334433E+10 | 0.139143E+10 | 0.202713E+10 | 0.235605E+09 | 0.179152E+10 | 0.00 | 0.00 |
June | 0.354843E+10 | 0.880449E+09 | 0.181384E+10 | 0.100932E+09 | 0.171290E+10 | 0.00 | 0.00 |
July | 0.388371E+10 | 0.651613E+09 | 0.189488E+10 | 0.141291E+09 | 0.175358E+10 | 0.00 | 0.00 |
August | 0.467075E+10 | 0.576846E+09 | 0.226234E+10 | 0.422609E+09 | 0.183973E+10 | 0.00 | 0.00 |
September | 0.416462E+10 | 0.128220E+10 | 0.240775E+10 | 0.895553E+09 | 0.151220E+10 | 0.00 | 0.00 |
October | 0.533788E+10 | 0.266648E+10 | 0.360690E+10 | 0.233654E+10 | 0.127035E+10 | 0.00 | 0.00 |
November | 0.496464E+10 | 0.331395E+10 | 0.375519E+10 | 0.249188E+10 | 0.126332E+10 | 0.00 | 0.00 |
December | 0.475418E+10 | 0.402652E+10 | 0.393405E+10 | 0.276763E+10 | 0.116642E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.518395E+11 | 0.275516E+11 | 0.348356E+11 | 0.169660E+11 | 0.178696E+11 | 0.00 | 0.00 |
Minimum of Months | 0.334433E+10 | 0.576846E+09 | 0.181384E+10 | 0.100932E+09 | 0.110919E+10 | 0.00 | 0.00 |
Maximum of Months | 0.533788E+10 | 0.455486E+10 | 0.399103E+10 | 0.278252E+10 | 0.183973E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.895132E+09 | 0.334610E+10 | 0.112225E+10 | 0.520578E+09 | 0.601675E+09 | 0.00 | 0.00 |
February | 0.122303E+10 | 0.250866E+10 | 0.116366E+10 | 0.544080E+09 | 0.619581E+09 | 0.00 | 0.00 |
March | 0.243084E+10 | 0.178470E+10 | 0.189894E+10 | 0.917606E+09 | 0.981330E+09 | 0.00 | 0.00 |
April | 0.305610E+10 | 0.138172E+10 | 0.206736E+10 | 0.946011E+09 | 0.112135E+10 | 0.00 | 0.00 |
May | 0.345816E+10 | 0.973957E+09 | 0.214702E+10 | 0.813416E+09 | 0.133360E+10 | 0.00 | 0.00 |
June | 0.396904E+10 | 0.633997E+09 | 0.218503E+10 | 0.840569E+09 | 0.134446E+10 | 0.00 | 0.00 |
July | 0.400709E+10 | 0.469512E+09 | 0.212969E+10 | 0.789612E+09 | 0.134007E+10 | 0.00 | 0.00 |
August | 0.395409E+10 | 0.413133E+09 | 0.208679E+10 | 0.780373E+09 | 0.130642E+10 | 0.00 | 0.00 |
September | 0.267539E+10 | 0.863266E+09 | 0.164532E+10 | 0.685344E+09 | 0.959973E+09 | 0.00 | 0.00 |
October | 0.206571E+10 | 0.182604E+10 | 0.151464E+10 | 0.786263E+09 | 0.728379E+09 | 0.00 | 0.00 |
November | 0.130895E+10 | 0.231761E+10 | 0.116980E+10 | 0.525065E+09 | 0.644736E+09 | 0.00 | 0.00 |
December | 0.852325E+09 | 0.289793E+10 | 0.997247E+09 | 0.436196E+09 | 0.561051E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.298959E+11 | 0.194166E+11 | 0.201277E+11 | 0.858511E+10 | 0.115426E+11 | 0.00 | 0.00 |
Minimum of Months | 0.852325E+09 | 0.413133E+09 | 0.997247E+09 | 0.436196E+09 | 0.561051E+09 | 0.00 | 0.00 |
Maximum of Months | 0.400709E+10 | 0.334610E+10 | 0.218503E+10 | 0.946011E+09 | 0.134446E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.110137E+09 | 0.541095E+10 | 0.746277E+09 | 0.00 | 0.746277E+09 | 0.00 | 0.00 |
February | 0.316197E+09 | 0.400752E+10 | 0.747125E+09 | 0.00 | 0.747125E+09 | 0.00 | 0.00 |
March | 0.783967E+09 | 0.279795E+10 | 0.116131E+10 | 0.00 | 0.116131E+10 | 0.00 | 0.00 |
April | 0.149858E+10 | 0.214421E+10 | 0.135940E+10 | 6029322.01 | 0.135337E+10 | 0.00 | 0.00 |
May | 0.236336E+10 | 0.143892E+10 | 0.168001E+10 | 53616748.83 | 0.162639E+10 | 0.00 | 0.00 |
June | 0.332322E+10 | 0.879420E+09 | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.00 | 0.00 |
July | 0.345113E+10 | 0.655459E+09 | 0.174447E+10 | 84799715.93 | 0.165967E+10 | 0.00 | 0.00 |
August | 0.315407E+10 | 0.549126E+09 | 0.155141E+10 | 16900235.20 | 0.153451E+10 | 0.00 | 0.00 |
September | 0.171649E+10 | 0.120057E+10 | 0.113489E+10 | 159761.37 | 0.113473E+10 | 0.00 | 0.00 |
October | 0.780871E+09 | 0.258784E+10 | 0.891659E+09 | 0.00 | 0.891659E+09 | 0.00 | 0.00 |
November | 0.393635E+09 | 0.339424E+10 | 0.772262E+09 | 0.00 | 0.772262E+09 | 0.00 | 0.00 |
December | 0.105689E+09 | 0.443106E+10 | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.179974E+11 | 0.294973E+11 | 0.142680E+11 | 0.279641E+09 | 0.139883E+11 | 0.00 | 0.00 |
Minimum of Months | 0.105689E+09 | 0.549126E+09 | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.00 | 0.00 |
Maximum of Months | 0.345113E+10 | 0.541095E+10 | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.740082E+09 | 0.321262E+10 | 0.109261E+10 | 0.492825E+09 | 0.599790E+09 | 0.00 | 0.00 |
February | 0.118499E+10 | 0.239382E+10 | 0.124414E+10 | 0.668469E+09 | 0.575674E+09 | 0.00 | 0.00 |
March | 0.194471E+10 | 0.170079E+10 | 0.173298E+10 | 0.788905E+09 | 0.944080E+09 | 0.00 | 0.00 |
April | 0.279716E+10 | 0.133379E+10 | 0.202802E+10 | 0.924727E+09 | 0.110330E+10 | 0.00 | 0.00 |
May | 0.354071E+10 | 0.937211E+09 | 0.230115E+10 | 0.973125E+09 | 0.132803E+10 | 0.00 | 0.00 |
June | 0.408780E+10 | 0.582266E+09 | 0.230561E+10 | 0.966340E+09 | 0.133927E+10 | 0.00 | 0.00 |
July | 0.427141E+10 | 0.436517E+09 | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.00 | 0.00 |
August | 0.397947E+10 | 0.362643E+09 | 0.212478E+10 | 0.842976E+09 | 0.128180E+10 | 0.00 | 0.00 |
September | 0.271809E+10 | 0.762740E+09 | 0.168995E+10 | 0.748772E+09 | 0.941176E+09 | 0.00 | 0.00 |
October | 0.189892E+10 | 0.158222E+10 | 0.148972E+10 | 0.775140E+09 | 0.714585E+09 | 0.00 | 0.00 |
November | 0.112528E+10 | 0.201626E+10 | 0.115263E+10 | 0.521905E+09 | 0.630721E+09 | 0.00 | 0.00 |
December | 0.751110E+09 | 0.261954E+10 | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.290397E+11 | 0.179404E+11 | 0.205163E+11 | 0.915008E+10 | 0.113662E+11 | 0.00 | 0.00 |
Minimum of Months | 0.740082E+09 | 0.362643E+09 | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.00 | 0.00 |
Maximum of Months | 0.427141E+10 | 0.321262E+10 | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.445362E+10 | 0.451472E+10 | 0.399118E+10 | 0.278264E+10 | 0.120854E+10 | 0.00 | 0.00 |
February | 0.411168E+10 | 0.352532E+10 | 0.336461E+10 | 0.225539E+10 | 0.110922E+10 | 0.00 | 0.00 |
March | 0.445768E+10 | 0.272291E+10 | 0.335013E+10 | 0.174589E+10 | 0.160424E+10 | 0.00 | 0.00 |
April | 0.362195E+10 | 0.221116E+10 | 0.242809E+10 | 0.790395E+09 | 0.163769E+10 | 0.00 | 0.00 |
May | 0.321612E+10 | 0.152614E+10 | 0.202719E+10 | 0.235614E+09 | 0.179158E+10 | 0.00 | 0.00 |
June | 0.348480E+10 | 0.940403E+09 | 0.181389E+10 | 0.100936E+09 | 0.171295E+10 | 0.00 | 0.00 |
July | 0.383955E+10 | 0.687201E+09 | 0.189493E+10 | 0.141297E+09 | 0.175364E+10 | 0.00 | 0.00 |
August | 0.465614E+10 | 0.576790E+09 | 0.226241E+10 | 0.422627E+09 | 0.183979E+10 | 0.00 | 0.00 |
September | 0.415807E+10 | 0.122801E+10 | 0.240784E+10 | 0.895590E+09 | 0.151225E+10 | 0.00 | 0.00 |
October | 0.531904E+10 | 0.250454E+10 | 0.360703E+10 | 0.233664E+10 | 0.127039E+10 | 0.00 | 0.00 |
November | 0.494822E+10 | 0.311469E+10 | 0.375534E+10 | 0.249198E+10 | 0.126336E+10 | 0.00 | 0.00 |
December | 0.469732E+10 | 0.385165E+10 | 0.393420E+10 | 0.276774E+10 | 0.116646E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.509642E+11 | 0.274035E+11 | 0.348369E+11 | 0.169667E+11 | 0.178701E+11 | 0.00 | 0.00 |
Minimum of Months | 0.321612E+10 | 0.576790E+09 | 0.181389E+10 | 0.100936E+09 | 0.110922E+10 | 0.00 | 0.00 |
Maximum of Months | 0.531904E+10 | 0.451472E+10 | 0.399118E+10 | 0.278264E+10 | 0.183979E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.871783E+09 | 0.334337E+10 | 0.112227E+10 | 0.520587E+09 | 0.601681E+09 | 0.00 | 0.00 |
February | 0.118767E+10 | 0.253954E+10 | 0.116368E+10 | 0.544089E+09 | 0.619587E+09 | 0.00 | 0.00 |
March | 0.235523E+10 | 0.184531E+10 | 0.189896E+10 | 0.917621E+09 | 0.981340E+09 | 0.00 | 0.00 |
April | 0.296565E+10 | 0.146046E+10 | 0.206738E+10 | 0.946027E+09 | 0.112136E+10 | 0.00 | 0.00 |
May | 0.339179E+10 | 0.102523E+10 | 0.214704E+10 | 0.813430E+09 | 0.133361E+10 | 0.00 | 0.00 |
June | 0.393306E+10 | 0.647330E+09 | 0.218506E+10 | 0.840583E+09 | 0.134448E+10 | 0.00 | 0.00 |
July | 0.398449E+10 | 0.472668E+09 | 0.212971E+10 | 0.789625E+09 | 0.134009E+10 | 0.00 | 0.00 |
August | 0.394430E+10 | 0.400746E+09 | 0.208681E+10 | 0.780386E+09 | 0.130643E+10 | 0.00 | 0.00 |
September | 0.268149E+10 | 0.813994E+09 | 0.164534E+10 | 0.685356E+09 | 0.959983E+09 | 0.00 | 0.00 |
October | 0.207499E+10 | 0.172140E+10 | 0.151466E+10 | 0.786276E+09 | 0.728386E+09 | 0.00 | 0.00 |
November | 0.132105E+10 | 0.220799E+10 | 0.116982E+10 | 0.525073E+09 | 0.644742E+09 | 0.00 | 0.00 |
December | 0.845040E+09 | 0.281220E+10 | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.295565E+11 | 0.192903E+11 | 0.201280E+11 | 0.858525E+10 | 0.115427E+11 | 0.00 | 0.00 |
Minimum of Months | 0.845040E+09 | 0.400746E+09 | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.398449E+10 | 0.334337E+10 | 0.218506E+10 | 0.946027E+09 | 0.134448E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.501166E+10 | -0.427283E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -738826721.8 | 58.98 | 0.00 | 0.00 |
February | 0.454425E+10 | -0.389178E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -652475551.6 | 58.98 | 0.00 | 0.00 |
March | 0.515313E+10 | -0.445083E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -702299606.9 | 58.98 | 0.00 | 0.00 |
April | 0.442200E+10 | -0.374959E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -672413127.9 | 58.98 | 0.00 | 0.00 |
May | 0.438982E+10 | -0.370009E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689732896.3 | 58.98 | 0.00 | 0.00 |
June | 0.404867E+10 | -0.338182E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666840948.3 | 58.98 | 0.00 | 0.00 |
July | 0.370868E+10 | -0.302127E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687413521.6 | 58.98 | 0.00 | 0.00 |
August | 0.401944E+10 | -0.333098E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688458128.1 | 58.98 | 0.00 | 0.00 |
September | 0.381083E+10 | -0.314526E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -665565796.7 | 58.98 | 0.00 | 0.00 |
October | 0.420973E+10 | -0.351557E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -694157736.1 | 58.98 | 0.00 | 0.00 |
November | 0.444370E+10 | -0.376446E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -679238478.8 | 58.98 | 0.00 | 0.00 |
December | 0.471022E+10 | -0.399244E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -717782579.7 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.524721E+11 | -0.442169E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.825521E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.370868E+10 | -0.445083E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -738826721.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.515313E+10 | -0.302127E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -652475551.6 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.51 | 0.48 | 01-JAN-09:20 | 5944.13 | 33.56 | 265.83 | 271.50 | 1657.27 | 25.59 | 178.50 | 250.33 |
February | 263.00 | 0.52 | 0.48 | 01-FEB-13:39 | 6962.61 | 33.59 | 230.83 | 246.83 | 1109.82 | 19.25 | 74.67 | 210.83 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:50 | 1639.75 | 18.12 | 6.83 | 317.83 | 961.50 | 20.22 | 124.00 | 283.00 |
April | 369.33 | 0.53 | 0.48 | 01-APR-09:39 | 1350.13 | 17.76 | 0.00 | 324.17 | 773.30 | 19.91 | 104.50 | 280.33 |
May | 407.00 | 0.53 | 0.48 | 01-MAY-07:49 | 1220.07 | 17.94 | 0.00 | 358.50 | 683.84 | 20.09 | 89.67 | 310.67 |
June | 411.67 | 0.53 | 0.48 | 01-JUN-07:19 | 1133.53 | 17.68 | 0.00 | 358.67 | 641.54 | 19.85 | 91.67 | 311.00 |
July | 411.00 | 0.53 | 0.48 | 01-JUL-07:49 | 1195.26 | 17.85 | 0.00 | 362.50 | 668.51 | 19.99 | 118.50 | 312.83 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-07:30 | 1461.06 | 18.48 | 0.00 | 349.33 | 801.51 | 20.60 | 174.83 | 311.50 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:40 | 1564.17 | 18.59 | 6.50 | 307.83 | 880.51 | 20.47 | 122.67 | 268.33 |
October | 293.50 | 0.51 | 0.48 | 01-OCT-10:39 | 2832.02 | 23.85 | 119.33 | 291.83 | 1070.85 | 19.63 | 83.17 | 255.17 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-08:30 | 5850.38 | 34.50 | 285.50 | 272.83 | 1203.10 | 24.25 | 167.17 | 252.83 |
December | 285.17 | 0.50 | 0.48 | 01-DEC-07:00 | 5602.08 | 34.35 | 269.83 | 267.67 | 1598.52 | 26.54 | 179.50 | 245.17 |
Annual Sum or Average | 4071.00 | 0.52 | 2776.74 | 22.92 | 1184.67 | 3729.50 | 962.96 | 21.19 | 1508.83 | 3292.00 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1133.53 | 17.68 | 0.00 | 246.83 | 641.54 | 19.25 | 74.67 | 210.83 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 6962.61 | 34.50 | 285.50 | 362.50 | 1657.27 | 26.54 | 179.50 | 312.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-09:09 | 1403.14 | 19.13 | 71.83 | 240.83 | 715.25 | 19.99 | 55.33 | 179.00 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 1863.36 | 18.94 | 60.17 | 222.67 | 1030.30 | 21.08 | 50.00 | 177.17 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-08:39 | 2242.56 | 20.56 | 105.50 | 309.83 | 881.09 | 20.10 | 47.50 | 267.33 |
April | 369.33 | 0.52 | 0.48 | 01-APR-08:09 | 2159.60 | 19.96 | 93.33 | 325.00 | 1163.95 | 21.19 | 67.17 | 287.67 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-07:10 | 2462.38 | 20.32 | 108.50 | 366.67 | 1018.16 | 20.21 | 50.17 | 327.67 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-06:30 | 2486.06 | 20.25 | 110.67 | 368.50 | 1042.13 | 20.91 | 64.00 | 332.50 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-05:00 | 2460.73 | 20.28 | 105.50 | 371.83 | 1042.79 | 20.29 | 51.83 | 330.50 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-06:40 | 2255.62 | 20.63 | 102.17 | 350.83 | 1190.30 | 21.92 | 73.50 | 313.33 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:10 | 2082.99 | 19.39 | 67.33 | 303.17 | 1122.96 | 21.64 | 55.33 | 259.33 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-08:20 | 2490.79 | 20.88 | 90.83 | 267.17 | 929.04 | 19.93 | 43.83 | 214.83 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-08:20 | 1701.57 | 21.17 | 97.00 | 246.83 | 918.85 | 22.00 | 75.50 | 200.83 |
December | 285.17 | 0.54 | 0.48 | 01-DEC-07:49 | 1440.43 | 19.73 | 73.33 | 236.67 | 771.34 | 21.42 | 60.17 | 177.50 |
Annual Sum or Average | 4071.00 | 0.53 | 2130.75 | 20.15 | 1086.17 | 3610.00 | 996.80 | 20.87 | 694.33 | 3067.67 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1403.14 | 18.94 | 60.17 | 222.67 | 715.25 | 19.93 | 43.83 | 177.17 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 2490.79 | 21.17 | 110.67 | 371.83 | 1190.30 | 22.00 | 75.50 | 332.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.59 | 0.48 | 01-JAN-11:20 | 500.43 | 14.35 | 0.00 | 211.33 | 302.57 | 16.75 | 0.00 | 89.17 |
February | 263.00 | 0.59 | 0.48 | 01-FEB-13:50 | 531.48 | 14.55 | 0.00 | 190.50 | 330.34 | 16.90 | 0.00 | 111.67 |
March | 351.67 | 0.54 | 0.48 | 01-MAR-09:30 | 678.09 | 16.37 | 0.00 | 299.67 | 413.74 | 18.58 | 0.00 | 226.17 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:30 | 809.95 | 17.28 | 0.00 | 328.17 | 485.58 | 19.39 | 0.67 | 271.17 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:40 | 1012.67 | 20.33 | 51.83 | 382.67 | 584.27 | 20.48 | 66.67 | 342.50 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:49 | 1101.66 | 21.05 | 66.83 | 385.83 | 648.41 | 23.06 | 178.00 | 363.83 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-06:10 | 1110.01 | 20.48 | 53.33 | 384.83 | 617.52 | 21.45 | 145.83 | 348.83 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:10 | 990.02 | 18.23 | 0.00 | 359.33 | 578.27 | 20.31 | 54.67 | 324.83 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:49 | 752.92 | 17.08 | 0.00 | 302.50 | 456.60 | 19.19 | 0.00 | 219.83 |
October | 293.50 | 0.58 | 0.48 | 01-OCT-10:50 | 556.20 | 15.08 | 0.00 | 237.00 | 355.94 | 17.47 | 0.00 | 143.83 |
November | 299.00 | 0.58 | 0.48 | 01-NOV-09:00 | 517.80 | 14.66 | 0.00 | 224.67 | 315.06 | 17.00 | 0.00 | 121.50 |
December | 285.17 | 0.59 | 0.48 | 01-DEC-10:20 | 483.52 | 14.43 | 0.00 | 203.50 | 293.36 | 16.87 | 0.00 | 82.83 |
Annual Sum or Average | 4071.00 | 0.54 | 789.00 | 17.35 | 172.00 | 3510.00 | 467.36 | 19.24 | 445.83 | 2646.17 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 483.52 | 14.35 | 0.00 | 190.50 | 293.36 | 16.75 | 0.00 | 82.83 | |
Maximum of Months | 411.67 | 0.59 | 0.48 | 1110.01 | 21.05 | 66.83 | 385.83 | 648.41 | 23.06 | 178.00 | 363.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.54 | 0.48 | 01-JAN-10:00 | 1724.54 | 21.14 | 89.83 | 243.83 | 955.65 | 21.84 | 68.00 | 191.33 |
February | 263.00 | 0.56 | 0.48 | 01-FEB-13:39 | 1648.22 | 18.89 | 64.00 | 214.33 | 856.95 | 19.72 | 40.33 | 165.33 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-11:50 | 2222.20 | 20.89 | 98.17 | 309.33 | 1182.08 | 21.80 | 72.00 | 266.50 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:39 | 2368.78 | 18.68 | 78.67 | 330.67 | 1304.67 | 20.04 | 51.83 | 288.67 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-08:30 | 2368.37 | 17.04 | 50.83 | 364.67 | 1008.52 | 18.03 | 0.00 | 325.83 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-07:49 | 2490.05 | 14.72 | 1.67 | 367.50 | 1066.09 | 17.98 | 0.00 | 330.83 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-08:09 | 2471.35 | 17.03 | 52.17 | 367.50 | 1043.28 | 18.02 | 0.00 | 328.00 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-07:00 | 2423.28 | 19.52 | 89.00 | 352.67 | 1057.45 | 18.72 | 7.67 | 319.17 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-08:00 | 2175.17 | 21.47 | 90.83 | 305.00 | 1149.50 | 22.24 | 62.67 | 256.67 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:50 | 2351.32 | 20.91 | 92.67 | 262.50 | 902.70 | 19.99 | 42.83 | 210.33 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:00 | 1596.56 | 19.48 | 80.83 | 248.50 | 857.86 | 21.75 | 68.67 | 200.00 |
December | 285.17 | 0.54 | 0.48 | 01-DEC-10:09 | 1393.57 | 19.37 | 74.17 | 236.50 | 757.14 | 21.35 | 63.33 | 177.83 |
Annual Sum or Average | 4071.00 | 0.53 | 2150.89 | 18.88 | 862.83 | 3603.00 | 1024.87 | 19.93 | 477.33 | 3060.50 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1393.57 | 14.72 | 1.67 | 214.33 | 757.14 | 17.98 | 0.00 | 165.33 | |
Maximum of Months | 411.67 | 0.56 | 0.48 | 2490.05 | 21.47 | 98.17 | 367.50 | 1304.67 | 22.24 | 72.00 | 330.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.51 | 0.48 | 01-JAN-09:20 | 5823.08 | 33.12 | 258.17 | 269.83 | 1561.52 | 23.29 | 103.33 | 249.00 |
February | 263.00 | 0.52 | 0.48 | 01-FEB-13:39 | 6853.73 | 33.22 | 229.67 | 245.83 | 1060.06 | 18.04 | 25.83 | 214.17 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:00 | 1553.16 | 14.23 | 6.67 | 314.67 | 896.80 | 17.63 | 0.50 | 278.83 |
April | 369.33 | 0.53 | 0.48 | 01-APR-09:50 | 1289.89 | 14.01 | 0.00 | 321.83 | 731.87 | 17.52 | 0.00 | 277.33 |
May | 407.00 | 0.53 | 0.48 | 01-MAY-07:49 | 1172.51 | 14.26 | 0.00 | 355.83 | 654.37 | 17.73 | 0.00 | 307.83 |
June | 411.67 | 0.53 | 0.48 | 01-JUN-07:19 | 1091.09 | 14.07 | 0.00 | 356.33 | 616.22 | 17.53 | 0.00 | 306.83 |
July | 411.00 | 0.53 | 0.48 | 01-JUL-07:49 | 1149.36 | 14.24 | 0.00 | 359.33 | 640.70 | 17.67 | 0.00 | 308.33 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-07:40 | 1400.63 | 14.86 | 0.00 | 347.33 | 762.74 | 18.28 | 0.00 | 307.17 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:49 | 1490.14 | 14.98 | 6.50 | 305.00 | 828.73 | 18.12 | 0.00 | 265.50 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-10:39 | 2727.91 | 21.24 | 117.33 | 290.33 | 988.09 | 16.85 | 2.17 | 251.33 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-08:30 | 5736.91 | 34.09 | 281.17 | 271.67 | 1115.61 | 21.76 | 82.17 | 249.67 |
December | 285.17 | 0.51 | 0.48 | 01-DEC-07:00 | 5429.53 | 32.30 | 249.50 | 263.83 | 1501.05 | 24.34 | 116.17 | 243.00 |
Annual Sum or Average | 4071.00 | 0.52 | 2695.29 | 20.12 | 1149.00 | 3701.83 | 908.51 | 18.87 | 330.17 | 3259.00 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1091.09 | 14.01 | 0.00 | 245.83 | 616.22 | 16.85 | 0.00 | 214.17 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 6853.73 | 34.09 | 281.17 | 359.33 | 1561.52 | 24.34 | 116.17 | 308.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-09:20 | 1363.77 | 18.62 | 71.50 | 239.00 | 684.67 | 19.74 | 48.67 | 172.50 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 1813.50 | 18.44 | 60.17 | 219.33 | 989.09 | 20.87 | 48.50 | 174.00 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-08:39 | 2191.30 | 20.09 | 105.33 | 308.00 | 839.46 | 19.89 | 47.33 | 262.83 |
April | 369.33 | 0.53 | 0.48 | 01-APR-08:09 | 2098.61 | 19.49 | 93.00 | 322.67 | 1115.83 | 21.00 | 67.17 | 283.50 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-07:19 | 2391.36 | 19.87 | 108.33 | 364.00 | 967.49 | 20.04 | 50.17 | 323.50 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-06:30 | 2421.72 | 19.80 | 110.33 | 366.00 | 992.13 | 20.75 | 64.00 | 329.00 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-05:00 | 2392.59 | 19.83 | 105.33 | 369.00 | 991.41 | 20.11 | 51.83 | 328.17 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-06:40 | 2184.22 | 20.17 | 102.17 | 349.17 | 1140.60 | 21.75 | 73.50 | 309.67 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:10 | 2023.73 | 18.89 | 67.33 | 301.33 | 1074.78 | 21.45 | 55.33 | 253.33 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:39 | 2436.85 | 20.40 | 90.50 | 265.00 | 884.47 | 19.72 | 42.67 | 210.00 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-08:20 | 1659.27 | 20.71 | 97.00 | 244.33 | 885.48 | 21.78 | 72.83 | 195.83 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-07:49 | 1400.26 | 19.22 | 73.00 | 234.17 | 739.07 | 21.18 | 57.50 | 173.33 |
Annual Sum or Average | 4071.00 | 0.53 | 2073.27 | 19.67 | 1084.00 | 3582.00 | 952.46 | 20.68 | 679.50 | 3015.67 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1363.77 | 18.44 | 60.17 | 219.33 | 684.67 | 19.72 | 42.67 | 172.50 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 2436.85 | 20.71 | 110.33 | 369.00 | 1140.60 | 21.78 | 73.50 | 329.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.60 | 0.48 | 01-JAN-11:30 | 482.96 | 10.47 | 0.00 | 206.50 | 293.15 | 14.20 | 0.00 | 79.67 |
February | 263.00 | 0.60 | 0.48 | 01-FEB-13:00 | 513.49 | 10.78 | 0.00 | 185.33 | 320.90 | 14.47 | 0.00 | 106.83 |
March | 351.67 | 0.54 | 0.48 | 01-MAR-12:20 | 654.86 | 12.86 | 0.00 | 296.67 | 401.31 | 16.43 | 0.00 | 220.17 |
April | 369.33 | 0.53 | 0.48 | 01-APR-10:39 | 782.39 | 13.81 | 0.00 | 325.67 | 470.58 | 17.33 | 0.00 | 266.50 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:49 | 976.23 | 17.28 | 51.83 | 380.33 | 573.88 | 20.45 | 52.50 | 348.50 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:49 | 1061.26 | 18.08 | 65.67 | 384.67 | 624.76 | 21.23 | 68.17 | 361.00 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-06:19 | 1065.85 | 16.16 | 27.33 | 383.17 | 604.40 | 20.59 | 54.00 | 350.83 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:10 | 953.90 | 14.80 | 0.00 | 357.83 | 557.88 | 18.26 | 0.00 | 320.67 |
September | 298.50 | 0.54 | 0.48 | 01-SEP-07:00 | 725.98 | 13.77 | 0.00 | 299.67 | 441.99 | 17.24 | 0.00 | 210.33 |
October | 293.50 | 0.58 | 0.48 | 01-OCT-10:50 | 537.67 | 11.52 | 0.00 | 231.00 | 346.46 | 15.26 | 0.00 | 136.67 |
November | 299.00 | 0.59 | 0.48 | 01-NOV-10:09 | 499.26 | 10.90 | 0.00 | 219.33 | 305.08 | 14.56 | 0.00 | 110.00 |
December | 285.17 | 0.60 | 0.48 | 01-DEC-10:20 | 465.99 | 10.51 | 0.00 | 198.00 | 283.90 | 14.30 | 0.00 | 70.17 |
Annual Sum or Average | 4071.00 | 0.54 | 760.54 | 13.79 | 144.83 | 3468.17 | 453.78 | 17.40 | 174.67 | 2581.33 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 465.99 | 10.47 | 0.00 | 185.33 | 283.90 | 14.20 | 0.00 | 70.17 | |
Maximum of Months | 411.67 | 0.60 | 0.48 | 1065.85 | 18.08 | 65.67 | 384.67 | 624.76 | 21.23 | 68.17 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-10:00 | 1682.62 | 20.74 | 89.33 | 240.83 | 922.67 | 21.73 | 68.00 | 186.83 |
February | 263.00 | 0.56 | 0.48 | 01-FEB-13:39 | 1597.52 | 18.47 | 64.00 | 211.67 | 817.05 | 19.59 | 40.00 | 162.83 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-11:50 | 2096.20 | 18.82 | 77.50 | 306.83 | 1133.94 | 21.68 | 72.17 | 263.17 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:39 | 2307.77 | 18.21 | 78.50 | 327.83 | 1256.61 | 19.87 | 51.83 | 285.83 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-08:39 | 2300.27 | 16.53 | 50.83 | 361.83 | 961.70 | 17.84 | 0.00 | 322.83 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-07:00 | 2402.94 | 14.17 | 1.67 | 364.17 | 1018.49 | 17.79 | 0.00 | 328.17 |
July | 411.00 | 0.53 | 0.48 | 01-JUL-08:20 | 2386.26 | 16.52 | 52.00 | 365.33 | 995.72 | 17.82 | 0.00 | 324.50 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-08:09 | 2349.84 | 18.89 | 86.50 | 351.17 | 1000.66 | 18.55 | 7.83 | 314.00 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-08:00 | 2071.15 | 19.40 | 75.50 | 301.17 | 1102.03 | 22.11 | 62.67 | 252.50 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:50 | 2298.89 | 20.49 | 92.50 | 260.67 | 859.80 | 19.86 | 42.83 | 206.50 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:00 | 1552.04 | 19.05 | 80.83 | 245.83 | 823.42 | 21.64 | 68.17 | 196.50 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-10:09 | 1354.65 | 18.95 | 73.83 | 233.83 | 726.36 | 21.24 | 63.17 | 173.83 |
Annual Sum or Average | 4071.00 | 0.53 | 2079.55 | 18.14 | 823.00 | 3571.17 | 980.42 | 19.78 | 476.67 | 3017.50 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1354.65 | 14.17 | 1.67 | 211.67 | 726.36 | 17.79 | 0.00 | 162.83 | |
Maximum of Months | 411.67 | 0.56 | 0.48 | 2402.94 | 20.74 | 92.50 | 365.33 | 1256.61 | 22.11 | 72.17 | 328.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.51 | 0.48 | 01-JAN-09:20 | 5823.03 | 33.12 | 258.17 | 269.83 | 1561.45 | 23.29 | 103.33 | 249.00 |
February | 263.00 | 0.52 | 0.48 | 01-FEB-13:39 | 6853.66 | 33.22 | 229.67 | 245.83 | 1059.99 | 18.05 | 25.83 | 214.17 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:00 | 1553.07 | 14.23 | 6.67 | 314.67 | 896.74 | 17.63 | 0.50 | 278.67 |
April | 369.33 | 0.53 | 0.48 | 01-APR-09:50 | 1289.81 | 14.01 | 0.00 | 321.83 | 731.82 | 17.52 | 0.00 | 277.33 |
May | 407.00 | 0.53 | 0.48 | 01-MAY-07:49 | 1172.44 | 14.26 | 0.00 | 355.83 | 654.32 | 17.73 | 0.00 | 307.83 |
June | 411.67 | 0.53 | 0.48 | 01-JUN-07:19 | 1091.03 | 14.07 | 0.00 | 356.33 | 616.17 | 17.53 | 0.00 | 306.83 |
July | 411.00 | 0.53 | 0.48 | 01-JUL-07:49 | 1149.30 | 14.24 | 0.00 | 359.33 | 640.65 | 17.68 | 0.00 | 308.33 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-07:40 | 1400.54 | 14.86 | 0.00 | 347.33 | 762.68 | 18.28 | 0.00 | 307.17 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:49 | 1490.05 | 14.99 | 6.50 | 305.00 | 828.67 | 18.12 | 0.00 | 265.50 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-10:39 | 2727.84 | 21.24 | 117.33 | 290.33 | 988.03 | 16.85 | 2.17 | 251.33 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-08:30 | 5736.86 | 34.09 | 281.17 | 271.67 | 1115.53 | 21.76 | 82.17 | 249.67 |
December | 285.17 | 0.51 | 0.48 | 01-DEC-07:00 | 5429.50 | 32.30 | 249.50 | 263.83 | 1500.98 | 24.34 | 116.17 | 243.00 |
Annual Sum or Average | 4071.00 | 0.52 | 2695.22 | 20.12 | 1149.00 | 3701.83 | 908.45 | 18.87 | 330.17 | 3258.83 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1091.03 | 14.01 | 0.00 | 245.83 | 616.17 | 16.85 | 0.00 | 214.17 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 6853.66 | 34.09 | 281.17 | 359.33 | 1561.45 | 24.34 | 116.17 | 308.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-09:20 | 1363.74 | 18.63 | 71.50 | 239.00 | 684.64 | 19.74 | 48.67 | 172.50 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 1813.48 | 18.44 | 60.17 | 219.33 | 989.06 | 20.87 | 48.50 | 174.00 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-08:39 | 2191.27 | 20.09 | 105.33 | 308.00 | 839.42 | 19.89 | 47.33 | 262.83 |
April | 369.33 | 0.53 | 0.48 | 01-APR-08:09 | 2098.57 | 19.50 | 93.00 | 322.67 | 1115.78 | 21.00 | 67.17 | 283.50 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-07:19 | 2391.30 | 19.87 | 108.33 | 364.00 | 967.43 | 20.04 | 50.17 | 323.50 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-06:30 | 2421.66 | 19.80 | 110.33 | 366.00 | 992.07 | 20.75 | 64.00 | 329.00 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-05:00 | 2392.53 | 19.84 | 105.33 | 369.00 | 991.34 | 20.12 | 51.83 | 328.17 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-06:40 | 2184.16 | 20.18 | 102.17 | 349.17 | 1140.53 | 21.75 | 73.50 | 309.67 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:10 | 2023.69 | 18.90 | 67.33 | 301.33 | 1074.73 | 21.45 | 55.33 | 253.33 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:39 | 2436.83 | 20.40 | 90.50 | 265.00 | 884.43 | 19.72 | 42.67 | 210.00 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-08:20 | 1659.24 | 20.71 | 97.00 | 244.33 | 885.44 | 21.78 | 72.83 | 195.83 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-07:49 | 1400.23 | 19.22 | 73.00 | 234.17 | 739.04 | 21.18 | 57.50 | 173.17 |
Annual Sum or Average | 4071.00 | 0.53 | 2073.23 | 19.67 | 1084.00 | 3582.00 | 952.41 | 20.68 | 679.50 | 3015.50 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1363.74 | 18.44 | 60.17 | 219.33 | 684.64 | 19.72 | 42.67 | 172.50 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 2436.83 | 20.71 | 110.33 | 369.00 | 1140.53 | 21.78 | 73.50 | 329.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.60 | 0.48 | 01-JAN-11:30 | 482.94 | 10.47 | 0.00 | 206.50 | 293.13 | 14.20 | 0.00 | 79.67 |
February | 263.00 | 0.60 | 0.48 | 01-FEB-13:00 | 513.48 | 10.78 | 0.00 | 185.33 | 320.88 | 14.48 | 0.00 | 106.83 |
March | 351.67 | 0.54 | 0.48 | 01-MAR-12:20 | 654.84 | 12.86 | 0.00 | 296.67 | 401.28 | 16.43 | 0.00 | 220.17 |
April | 369.33 | 0.53 | 0.48 | 01-APR-10:39 | 782.36 | 13.81 | 0.00 | 325.67 | 470.55 | 17.33 | 0.00 | 266.50 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:49 | 976.19 | 17.28 | 51.83 | 380.33 | 573.84 | 20.45 | 52.50 | 348.50 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:49 | 1061.22 | 18.08 | 65.67 | 384.67 | 624.72 | 21.23 | 68.17 | 361.00 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-06:19 | 1065.80 | 16.16 | 27.33 | 383.17 | 604.36 | 20.59 | 54.00 | 350.83 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:10 | 953.87 | 14.80 | 0.00 | 357.83 | 557.84 | 18.26 | 0.00 | 320.67 |
September | 298.50 | 0.54 | 0.48 | 01-SEP-07:00 | 725.96 | 13.78 | 0.00 | 299.67 | 441.96 | 17.24 | 0.00 | 210.33 |
October | 293.50 | 0.58 | 0.48 | 01-OCT-10:50 | 537.66 | 11.52 | 0.00 | 231.00 | 346.44 | 15.26 | 0.00 | 136.67 |
November | 299.00 | 0.59 | 0.48 | 01-NOV-10:09 | 499.24 | 10.90 | 0.00 | 219.33 | 305.06 | 14.56 | 0.00 | 110.00 |
December | 285.17 | 0.60 | 0.48 | 01-DEC-10:20 | 465.98 | 10.51 | 0.00 | 198.00 | 283.88 | 14.30 | 0.00 | 70.17 |
Annual Sum or Average | 4071.00 | 0.54 | 760.51 | 13.79 | 144.83 | 3468.17 | 453.75 | 17.40 | 174.67 | 2581.33 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 465.98 | 10.47 | 0.00 | 185.33 | 283.88 | 14.20 | 0.00 | 70.17 | |
Maximum of Months | 411.67 | 0.60 | 0.48 | 1065.80 | 18.08 | 65.67 | 384.67 | 624.72 | 21.23 | 68.17 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-10:00 | 1682.59 | 20.74 | 89.33 | 240.83 | 922.63 | 21.73 | 68.00 | 186.83 |
February | 263.00 | 0.56 | 0.48 | 01-FEB-13:39 | 1597.50 | 18.47 | 64.00 | 211.67 | 817.01 | 19.59 | 40.00 | 162.83 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-11:50 | 2096.16 | 18.82 | 77.50 | 306.83 | 1133.89 | 21.68 | 72.17 | 263.17 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:39 | 2307.72 | 18.21 | 78.50 | 327.83 | 1256.56 | 19.87 | 51.83 | 285.83 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-08:39 | 2300.21 | 16.54 | 50.83 | 361.83 | 961.64 | 17.84 | 0.00 | 322.83 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-07:00 | 2402.88 | 14.17 | 1.67 | 364.17 | 1018.43 | 17.79 | 0.00 | 328.17 |
July | 411.00 | 0.53 | 0.48 | 01-JUL-08:20 | 2386.20 | 16.52 | 52.00 | 365.33 | 995.66 | 17.82 | 0.00 | 324.50 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-08:09 | 2349.78 | 18.89 | 86.50 | 351.17 | 1000.60 | 18.55 | 7.83 | 314.00 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-08:00 | 2071.10 | 19.40 | 75.50 | 301.17 | 1101.97 | 22.11 | 62.67 | 252.50 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:50 | 2298.87 | 20.49 | 92.50 | 260.67 | 859.76 | 19.86 | 42.83 | 206.50 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:00 | 1552.01 | 19.05 | 80.83 | 245.83 | 823.38 | 21.64 | 68.17 | 196.50 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-10:09 | 1354.63 | 18.95 | 73.83 | 233.83 | 726.32 | 21.24 | 63.17 | 173.83 |
Annual Sum or Average | 4071.00 | 0.53 | 2079.50 | 18.14 | 823.00 | 3571.17 | 980.37 | 19.78 | 476.67 | 3017.50 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1354.63 | 14.17 | 1.67 | 211.67 | 726.32 | 17.79 | 0.00 | 162.83 | |
Maximum of Months | 411.67 | 0.56 | 0.48 | 2402.88 | 20.74 | 92.50 | 365.33 | 1256.56 | 22.11 | 72.17 | 328.17 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.280005E+09 | 25427.96 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16917155.61 | 25427.96 | 13-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296922E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.280005E+09 | 25427.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.511658E+10 | 11826.61 | 19-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329133E+10 | 11804.62 | 17-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131549E+10 | 11783.67 | 24-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.708860E+09 | 11763.76 | 05-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185721E+09 | 11719.82 | 11-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28016725.35 | 8257.30 | 08-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26675768.14 | 6144.74 | 29-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.601072E+09 | 11784.19 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119782E+10 | 11771.42 | 30-NOV-17:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219923E+10 | 11801.37 | 07-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.511658E+10 | 11826.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.233216E+10 | 9013.58 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129624E+10 | 9013.58 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198260E+09 | 9013.58 | 23-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33300171.45 | 9013.58 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25284225.67 | 7230.23 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120254E+09 | 9013.58 | 21-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.838153E+09 | 9013.58 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.484365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.233216E+10 | 9013.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.407255E+10 | 10154.46 | 02-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.238256E+10 | 10148.29 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.504939E+09 | 10113.41 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116916E+09 | 10102.79 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29341069.09 | 10059.48 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321315E+09 | 10090.70 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165624E+10 | 10099.81 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.908386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.407255E+10 | 10154.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.246338E+10 | 9112.58 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142922E+10 | 9112.58 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.253161E+09 | 9093.01 | 23-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 47863289.51 | 9112.58 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23873631.14 | 6884.20 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187443E+09 | 9112.58 | 21-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101674E+10 | 9112.58 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.542169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.246338E+10 | 9112.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.309200E+10 | 24600.45 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134616E+10 | 24600.45 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1849872.94 | 3533.06 | 23-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 110135.12 | 485.64 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 56145054.62 | 24600.45 | 22-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.899933E+09 | 24600.45 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.539620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.309200E+10 | 24600.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.238169E+10 | 12693.12 | 02-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132365E+10 | 12663.37 | 08-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159223E+09 | 12533.28 | 18-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36472920.41 | 12561.81 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 68294665.65 | 12415.49 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250607E+09 | 12584.86 | 21-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.963451E+09 | 12683.20 | 26-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.518338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.238169E+10 | 12693.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.258360E+10 | 9450.73 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144502E+10 | 9450.73 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193206E+09 | 9450.73 | 18-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27716572.61 | 9450.73 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138024E+09 | 9450.73 | 26-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.386044E+09 | 9450.73 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128935E+10 | 9450.73 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.606296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.258360E+10 | 9450.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.390991E+10 | 10875.22 | 02-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217330E+10 | 10873.39 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.272283E+09 | 10781.69 | 22-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46382040.09 | 10731.48 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107091E+09 | 10821.79 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.569614E+09 | 10818.98 | 25-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196517E+10 | 10842.42 | 27-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.904375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.390991E+10 | 10875.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.268895E+10 | 9551.95 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155185E+10 | 9551.95 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.264207E+09 | 9551.95 | 22-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 47100465.93 | 9551.95 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141054E+09 | 8115.22 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.503353E+09 | 9551.95 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147312E+10 | 9551.95 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.666964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.268895E+10 | 9551.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.715794E+10 | 37310.37 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.373911E+10 | 37310.37 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340957E+09 | 37310.37 | 18-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31565863.73 | 36882.60 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193573E+09 | 37310.37 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.957688E+09 | 37310.37 | 01-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.407683E+10 | 37310.37 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.715794E+10 | 37310.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.404941E+10 | 14276.95 | 18-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248291E+10 | 14263.16 | 08-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.531153E+09 | 14211.88 | 23-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164565E+09 | 14100.28 | 07-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7457087.58 | 8809.93 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1244965.85 | 1743.71 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.340056E+09 | 14202.50 | 30-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.835135E+09 | 14224.79 | 24-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212785E+10 | 14239.14 | 01-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.404941E+10 | 14276.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.376119E+10 | 11618.68 | 19-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221873E+10 | 11638.24 | 08-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.466189E+09 | 11550.60 | 22-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101931E+09 | 11505.35 | 07-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1989851.45 | 3987.08 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3242943.94 | 2925.58 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.354391E+09 | 11588.46 | 30-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.881142E+09 | 11607.37 | 24-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.217947E+10 | 11612.09 | 07-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.996827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.376119E+10 | 11638.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.602134E+10 | 12409.45 | 18-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361456E+10 | 12397.47 | 08-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.759258E+09 | 12364.88 | 22-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187984E+09 | 12296.45 | 27-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4637181.56 | 6469.58 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1059100.18 | 1542.91 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.463679E+09 | 12373.45 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143134E+10 | 12364.02 | 24-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.356377E+10 | 12376.40 | 01-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.602134E+10 | 12409.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.409781E+10 | 11889.36 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.255406E+10 | 11889.36 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.682099E+09 | 11889.36 | 06-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182217E+09 | 11889.36 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12022812.24 | 6655.40 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6373820.94 | 3710.03 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.464292E+09 | 11889.36 | 26-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117813E+10 | 11889.36 | 08-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.258977E+10 | 11889.36 | 01-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.409781E+10 | 11889.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.251042E+10 | 10324.27 | 14-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108828E+10 | 12174.96 | 03-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7035449.91 | 1140.37 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2597422.40 | 966.87 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 65764.06 | 876.85 | 26-OCT-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 87199783.01 | 5944.99 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.361560E+09 | 9451.95 | 18-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.251042E+10 | 12174.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.313663E+10 | 11522.17 | 14-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147689E+10 | 13466.31 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25995793.40 | 2189.33 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18108297.04 | 2822.57 | 06-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11687664.86 | 2303.59 | 26-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185997E+09 | 7799.74 | 22-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.607335E+09 | 10591.02 | 18-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.546265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.313663E+10 | 13466.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.313816E+10 | 13634.23 | 27-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152375E+10 | 16009.13 | 03-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 76510860.14 | 3635.33 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46047098.87 | 4924.77 | 06-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22999836.19 | 4099.34 | 26-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.277219E+09 | 9424.99 | 22-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.721749E+09 | 10955.73 | 18-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.580643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.313816E+10 | 16009.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.207129E+10 | 0.127632E+10 | 21943.07 | 19-JAN-20:00 | 12155.95 | 0.00 |
February | 0.00 | 0.00 | 0.507757E+10 | 0.413709E+10 | 31838.46 | 28-FEB-14:00 | 31838.46 | 0.00 |
March | 0.00 | 0.00 | 0.156883E+11 | 0.121579E+11 | 50142.09 | 30-MAR-15:10 | 50142.09 | 0.00 |
April | 0.00 | 0.00 | 0.266429E+11 | 0.216743E+11 | 56387.77 | 17-APR-15:20 | 56387.77 | 0.00 |
May | 0.00 | 0.00 | 0.502870E+11 | 0.379620E+11 | 70198.26 | 30-MAY-12:00 | 54362.25 | 0.00 |
June | 0.00 | 0.00 | 0.756851E+11 | 0.569592E+11 | 85294.90 | 28-JUN-11:50 | 59500.51 | 0.00 |
July | 0.00 | 0.00 | 0.864519E+11 | 0.618014E+11 | 93600.12 | 07-JUL-12:03 | 65615.92 | 0.00 |
August | 0.00 | 0.00 | 0.988962E+11 | 0.692370E+11 | 94826.33 | 19-AUG-04:02 | 67056.42 | 0.00 |
September | 0.00 | 0.00 | 0.632565E+11 | 0.467305E+11 | 89089.95 | 06-SEP-12:03 | 62869.00 | 0.00 |
October | 0.00 | 0.00 | 0.280203E+11 | 0.207091E+11 | 68465.76 | 10-OCT-16:00 | 56750.83 | 0.00 |
November | 0.00 | 0.00 | 0.112537E+11 | 0.853204E+10 | 36500.82 | 02-NOV-13:00 | 28170.32 | 0.00 |
December | 0.00 | 0.00 | 0.406788E+10 | 0.267636E+10 | 33923.98 | 12-DEC-14:00 | 25993.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.467399E+12 | 0.343853E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.207129E+10 | 0.127632E+10 | 21943.07 | 12155.95 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.988962E+11 | 0.692370E+11 | 94826.33 | 67056.42 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.203768E+10 | 0.128302E+10 | 22345.11 | 19-JAN-16:00 | 12744.25 | 0.00 |
February | 0.00 | 0.00 | 0.488464E+10 | 0.398652E+10 | 26146.64 | 28-FEB-15:20 | 26146.64 | 0.00 |
March | 0.00 | 0.00 | 0.142906E+11 | 0.110693E+11 | 49604.81 | 30-MAR-15:10 | 49604.81 | 0.00 |
April | 0.00 | 0.00 | 0.250784E+11 | 0.204293E+11 | 54545.34 | 17-APR-15:20 | 54545.34 | 0.00 |
May | 0.00 | 0.00 | 0.467794E+11 | 0.353656E+11 | 66436.52 | 30-MAY-15:10 | 52614.26 | 0.00 |
June | 0.00 | 0.00 | 0.694462E+11 | 0.515177E+11 | 76227.58 | 26-JUN-15:00 | 54768.34 | 0.00 |
July | 0.00 | 0.00 | 0.795670E+11 | 0.556086E+11 | 85633.97 | 07-JUL-04:02 | 64263.77 | 0.00 |
August | 0.00 | 0.00 | 0.888946E+11 | 0.603130E+11 | 89145.94 | 19-AUG-05:03 | 60398.73 | 0.00 |
September | 0.00 | 0.00 | 0.543672E+11 | 0.388036E+11 | 78678.14 | 07-SEP-16:00 | 57988.80 | 0.00 |
October | 0.00 | 0.00 | 0.236554E+11 | 0.169937E+11 | 60111.37 | 11-OCT-14:10 | 45352.34 | 0.00 |
November | 0.00 | 0.00 | 0.979441E+10 | 0.724845E+10 | 29018.61 | 02-NOV-13:00 | 20150.78 | 0.00 |
December | 0.00 | 0.00 | 0.374489E+10 | 0.252995E+10 | 28945.33 | 12-DEC-14:00 | 21095.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.422541E+12 | 0.305149E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.203768E+10 | 0.128302E+10 | 22345.11 | 12744.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.888946E+11 | 0.603130E+11 | 89145.94 | 64263.77 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.215439E+10 | 0.133638E+10 | 22719.85 | 19-JAN-17:50 | 12483.63 | 0.00 |
February | 0.00 | 0.00 | 0.516494E+10 | 0.418385E+10 | 29282.86 | 26-FEB-14:43 | 29282.86 | 0.00 |
March | 0.00 | 0.00 | 0.151383E+11 | 0.116590E+11 | 55563.18 | 30-MAR-15:20 | 55563.18 | 0.00 |
April | 0.00 | 0.00 | 0.272316E+11 | 0.221856E+11 | 61494.92 | 17-APR-15:50 | 61494.92 | 0.00 |
May | 0.00 | 0.00 | 0.507755E+11 | 0.390349E+11 | 75167.87 | 30-MAY-15:10 | 61340.48 | 0.00 |
June | 0.00 | 0.00 | 0.747331E+11 | 0.564070E+11 | 84554.92 | 26-JUN-15:00 | 63024.26 | 0.00 |
July | 0.00 | 0.00 | 0.850538E+11 | 0.607612E+11 | 91547.07 | 07-JUL-16:00 | 73533.51 | 0.00 |
August | 0.00 | 0.00 | 0.940089E+11 | 0.651501E+11 | 90620.69 | 01-AUG-15:00 | 72794.30 | 0.00 |
September | 0.00 | 0.00 | 0.565249E+11 | 0.404371E+11 | 86724.34 | 06-SEP-14:00 | 64744.57 | 0.00 |
October | 0.00 | 0.00 | 0.242471E+11 | 0.172446E+11 | 65525.04 | 11-OCT-14:00 | 50071.74 | 0.00 |
November | 0.00 | 0.00 | 0.102233E+11 | 0.749113E+10 | 32739.81 | 05-NOV-13:43 | 23878.29 | 0.00 |
December | 0.00 | 0.00 | 0.389730E+10 | 0.259573E+10 | 31177.63 | 12-DEC-14:00 | 22780.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.449153E+12 | 0.328487E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.215439E+10 | 0.133638E+10 | 22719.85 | 12483.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.940089E+11 | 0.651501E+11 | 91547.07 | 73533.51 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1748.42 | 6081.89 | 30-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1761.78 | 6094.83 | 01-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1818.26 | 5984.17 | 02-MAR-12:06 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1599.84 | 5645.69 | 03-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1536.76 | 5279.27 | 01-MAY-11:07 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1461.83 | 4833.73 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1280.78 | 4511.10 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1401.33 | 4494.15 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1367.09 | 4776.35 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1466.27 | 5233.41 | 31-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1606.97 | 5627.13 | 29-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1642.33 | 5938.55 | 29-DEC-12:15 |
Annual Sum or Average | 0.00 | 1556.49 | ||||
Minimum of Months | 0.00 | 0.00 | 1280.78 | 4494.15 | ||
Maximum of Months | 0.00 | 0.00 | 1818.26 | 6094.83 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.126021E+10 | 0.28 | 2539.43 | 02-JAN-06:11 | 0.75 |
February | 0.120668E+10 | 0.29 | 2539.43 | 13-FEB-07:01 | 0.76 |
March | 0.157683E+10 | 0.30 | 2316.33 | 30-MAR-16:00 | 0.71 |
April | 0.164907E+10 | 0.30 | 2508.97 | 17-APR-15:50 | 0.74 |
May | 0.216319E+10 | 0.33 | 3441.70 | 30-MAY-15:10 | 0.88 |
June | 0.306316E+10 | 0.40 | 3955.26 | 28-JUN-11:10 | 0.95 |
July | 0.334647E+10 | 0.41 | 6563.67 | 07-JUL-04:02 | 1.30 |
August | 0.387489E+10 | 0.45 | 9249.31 | 14-AUG-04:02 | 1.61 |
September | 0.279400E+10 | 0.37 | 4933.65 | 05-SEP-06:03 | 1.09 |
October | 0.195037E+10 | 0.32 | 3651.66 | 11-OCT-15:20 | 0.91 |
November | 0.145534E+10 | 0.29 | 2036.92 | 06-NOV-16:10 | 0.67 |
December | 0.126516E+10 | 0.27 | 1434.58 | 01-DEC-06:01 | 0.58 |
Annual Sum or Average | 0.256054E+11 | 0.33 | |||
Minimum of Months | 0.120668E+10 | 0.27 | 1434.58 | 0.58 | |
Maximum of Months | 0.387489E+10 | 0.45 | 9249.31 | 1.61 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.129871E+10 | 0.29 | 2398.85 | 07-JAN-07:03 | 0.79 |
February | 0.120654E+10 | 0.30 | 2398.85 | 09-FEB-07:01 | 0.79 |
March | 0.141575E+10 | 0.30 | 2585.88 | 30-MAR-16:00 | 0.81 |
April | 0.151188E+10 | 0.31 | 2690.84 | 17-APR-15:50 | 0.83 |
May | 0.200558E+10 | 0.34 | 3482.36 | 30-MAY-15:00 | 0.96 |
June | 0.270132E+10 | 0.40 | 4863.48 | 26-JUN-05:13 | 1.17 |
July | 0.289221E+10 | 0.40 | 6629.52 | 07-JUL-04:02 | 1.41 |
August | 0.319679E+10 | 0.43 | 8064.77 | 14-AUG-04:02 | 1.60 |
September | 0.217235E+10 | 0.36 | 4176.58 | 07-SEP-15:30 | 1.06 |
October | 0.156071E+10 | 0.30 | 2983.40 | 11-OCT-15:30 | 0.87 |
November | 0.124919E+10 | 0.29 | 1974.50 | 22-NOV-07:01 | 0.71 |
December | 0.122178E+10 | 0.28 | 2398.85 | 04-DEC-06:01 | 0.79 |
Annual Sum or Average | 0.224328E+11 | 0.33 | |||
Minimum of Months | 0.120654E+10 | 0.28 | 1974.50 | 0.71 | |
Maximum of Months | 0.319679E+10 | 0.43 | 8064.77 | 1.60 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157041E+10 | 0.33 | 2387.23 | 02-JAN-06:13 | 0.72 |
February | 0.135691E+10 | 0.32 | 2387.23 | 06-FEB-07:01 | 0.72 |
March | 0.145674E+10 | 0.30 | 2734.14 | 30-MAR-16:00 | 0.77 |
April | 0.154447E+10 | 0.30 | 2891.27 | 17-APR-15:50 | 0.79 |
May | 0.202807E+10 | 0.33 | 3647.26 | 30-MAY-15:00 | 0.90 |
June | 0.270329E+10 | 0.38 | 3951.48 | 27-JUN-15:30 | 0.94 |
July | 0.289354E+10 | 0.38 | 5248.10 | 15-JUL-05:03 | 1.12 |
August | 0.314511E+10 | 0.41 | 5850.72 | 14-AUG-04:02 | 1.19 |
September | 0.205952E+10 | 0.33 | 4194.65 | 07-SEP-15:30 | 0.98 |
October | 0.151303E+10 | 0.29 | 2814.47 | 11-OCT-15:30 | 0.78 |
November | 0.129275E+10 | 0.28 | 2387.23 | 21-NOV-07:01 | 0.72 |
December | 0.138460E+10 | 0.30 | 2387.23 | 02-DEC-07:03 | 0.72 |
Annual Sum or Average | 0.229484E+11 | 0.33 | |||
Minimum of Months | 0.129275E+10 | 0.28 | 2387.23 | 0.72 | |
Maximum of Months | 0.314511E+10 | 0.41 | 5850.72 | 1.19 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 57.74 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 55.62 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 56.37 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 56.21 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.51 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.11 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 56.44 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 56.96 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 56.77 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.96 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.08 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 56.45 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.62 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.96 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.77 | 56.77 | 1748.42 | 6081.89 | 30-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 55.98 | 55.98 | 1761.78 | 6094.83 | 01-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.87 | 56.87 | 1818.26 | 5984.17 | 02-MAR-12:06 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.66 | 56.66 | 1599.84 | 5645.69 | 03-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.93 | 56.93 | 1536.76 | 5279.27 | 01-MAY-11:07 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.39 | 56.39 | 1461.83 | 4833.73 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.70 | 56.70 | 1280.78 | 4511.10 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.71 | 57.71 | 1401.33 | 4494.15 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.03 | 57.03 | 1367.09 | 4776.35 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.00 | 56.00 | 1466.27 | 5233.41 | 31-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.88 | 56.88 | 1606.97 | 5627.13 | 29-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.94 | 56.94 | 1642.33 | 5938.55 | 29-DEC-12:15 |
Annual Sum or Average | 0.00 | 1556.49 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.98 | 55.98 | 1280.78 | 4494.15 | ||
Maximum of Months | 0.00 | 0.00 | 57.71 | 57.71 | 1818.26 | 6094.83 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.160793E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.109803E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.785824E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.927181E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.147921E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.225383E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.257807E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.292422E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.183929E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.953936E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.618295E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.802916E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.178687E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.618295E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.292422E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.164963E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.103522E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.597371E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.800487E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.136054E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.205174E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.234728E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.259081E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.155919E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.788896E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.555820E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.878825E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.162158E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.555820E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.259081E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.272339E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.173524E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.814243E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.911940E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.147151E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.219685E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.250115E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.272807E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.161287E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.939748E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.924590E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.169422E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.202538E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.814243E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.272807E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.126021E+10 | 0.207129E+10 | 0.167751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120668E+10 | 0.507757E+10 | 0.950455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157683E+10 | 0.156883E+11 | 0.227889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164907E+10 | 0.266429E+11 | 0.909537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.216319E+10 | 0.502870E+11 | 0.185721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.306316E+10 | 0.756851E+11 | 28016725.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.334647E+10 | 0.864519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.387489E+10 | 0.988962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.279400E+10 | 0.632565E+11 | 26675768.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195037E+10 | 0.280203E+11 | 0.679637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145534E+10 | 0.112537E+11 | 0.191403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126516E+10 | 0.406788E+10 | 0.607192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256054E+11 | 0.467399E+12 | 0.383741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120668E+10 | 0.207129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.387489E+10 | 0.988962E+11 | 0.167751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.129871E+10 | 0.203768E+10 | 0.177928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120654E+10 | 0.488464E+10 | 0.931687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141575E+10 | 0.142906E+11 | 0.916765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151188E+10 | 0.250784E+11 | 0.175780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200558E+10 | 0.467794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.270132E+10 | 0.694462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.289221E+10 | 0.795670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.319679E+10 | 0.888946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.217235E+10 | 0.543672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156071E+10 | 0.236554E+11 | 0.466261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124919E+10 | 0.979441E+10 | 0.195176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122178E+10 | 0.374489E+10 | 0.719835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224328E+11 | 0.422541E+12 | 0.378186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120654E+10 | 0.203768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.319679E+10 | 0.888946E+11 | 0.177928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157041E+10 | 0.215439E+10 | 0.282259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135691E+10 | 0.516494E+10 | 0.161331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145674E+10 | 0.151383E+11 | 0.285617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154447E+10 | 0.272316E+11 | 0.714311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202807E+10 | 0.507755E+11 | 26106932.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.270329E+10 | 0.747331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.289354E+10 | 0.850538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.314511E+10 | 0.940089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.205952E+10 | 0.565249E+11 | 11920830.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151303E+10 | 0.242471E+11 | 0.183899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129275E+10 | 0.102233E+11 | 0.556066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138460E+10 | 0.389730E+10 | 0.152594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229484E+11 | 0.449153E+12 | 0.706266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129275E+10 | 0.215439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.314511E+10 | 0.940089E+11 | 0.282259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.126021E+10 | 0.00 | 0.00 | 0.00 | 0.554398E+09 | 0.142647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120668E+10 | 0.00 | 0.00 | 0.00 | 0.135736E+10 | 0.841627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157683E+10 | 0.00 | 0.00 | 0.00 | 0.400957E+10 | 0.227185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164907E+10 | 0.00 | 0.00 | 0.00 | 0.671581E+10 | 0.906940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.216319E+10 | 0.00 | 0.00 | 0.00 | 0.124432E+11 | 0.185721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.306316E+10 | 0.00 | 0.00 | 0.00 | 0.194471E+11 | 28016725.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.334647E+10 | 0.00 | 0.00 | 0.00 | 0.224342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.387489E+10 | 0.00 | 0.00 | 0.00 | 0.253673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.279400E+10 | 0.00 | 0.00 | 0.00 | 0.155722E+11 | 26675768.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195037E+10 | 0.00 | 0.00 | 0.00 | 0.690942E+10 | 0.679571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145534E+10 | 0.00 | 0.00 | 0.00 | 0.290078E+10 | 0.182683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126516E+10 | 0.00 | 0.00 | 0.00 | 0.105364E+10 | 0.571036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256054E+11 | 0.00 | 0.00 | 0.00 | 0.118765E+12 | 0.343169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120668E+10 | 0.00 | 0.00 | 0.00 | 0.554398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.387489E+10 | 0.00 | 0.00 | 0.00 | 0.253673E+11 | 0.142647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.129871E+10 | 0.00 | 0.00 | 0.00 | 0.541480E+09 | 0.146562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120654E+10 | 0.00 | 0.00 | 0.00 | 0.130569E+10 | 0.783998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141575E+10 | 0.00 | 0.00 | 0.00 | 0.366719E+10 | 0.890769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151188E+10 | 0.00 | 0.00 | 0.00 | 0.633531E+10 | 0.157672E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200558E+10 | 0.00 | 0.00 | 0.00 | 0.115998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.270132E+10 | 0.00 | 0.00 | 0.00 | 0.178161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.289221E+10 | 0.00 | 0.00 | 0.00 | 0.205805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.319679E+10 | 0.00 | 0.00 | 0.00 | 0.227113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.217235E+10 | 0.00 | 0.00 | 0.00 | 0.134195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156071E+10 | 0.00 | 0.00 | 0.00 | 0.587367E+10 | 0.454573E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124919E+10 | 0.00 | 0.00 | 0.00 | 0.254324E+10 | 0.176576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122178E+10 | 0.00 | 0.00 | 0.00 | 0.975459E+09 | 0.659102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224328E+11 | 0.00 | 0.00 | 0.00 | 0.107369E+12 | 0.323559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120654E+10 | 0.00 | 0.00 | 0.00 | 0.541480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.319679E+10 | 0.00 | 0.00 | 0.00 | 0.227113E+11 | 0.146562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.157041E+10 | 0.00 | 0.00 | 0.00 | 0.575792E+09 | 0.250877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135691E+10 | 0.00 | 0.00 | 0.00 | 0.138614E+10 | 0.146094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145674E+10 | 0.00 | 0.00 | 0.00 | 0.390604E+10 | 0.277966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154447E+10 | 0.00 | 0.00 | 0.00 | 0.690666E+10 | 0.668264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202807E+10 | 0.00 | 0.00 | 0.00 | 0.126609E+11 | 26106932.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.270329E+10 | 0.00 | 0.00 | 0.00 | 0.192652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.289354E+10 | 0.00 | 0.00 | 0.00 | 0.221180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.314511E+10 | 0.00 | 0.00 | 0.00 | 0.241356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.205952E+10 | 0.00 | 0.00 | 0.00 | 0.140573E+11 | 11920830.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151303E+10 | 0.00 | 0.00 | 0.00 | 0.606846E+10 | 0.181599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129275E+10 | 0.00 | 0.00 | 0.00 | 0.266971E+10 | 0.528344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138460E+10 | 0.00 | 0.00 | 0.00 | 0.101989E+10 | 0.145377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229484E+11 | 0.00 | 0.00 | 0.00 | 0.114770E+12 | 0.648201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129275E+10 | 0.00 | 0.00 | 0.00 | 0.575792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.314511E+10 | 0.00 | 0.00 | 0.00 | 0.241356E+11 | 0.250877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101399E+11 | 0.00 | 0.00 | 4519523.23 | 12919713.80 | 74653098.16 | 0.353436E+10 | 0.00 | 0.35 |
February | 0.637832E+10 | 0.00 | 0.00 | 11240079.58 | 939522.60 | 4038995.06 | 0.567966E+10 | 0.00 | 0.46 |
March | 0.262926E+10 | 0.258725E+09 | 0.00 | 25236343.84 | 79795528.06 | 0.00 | 0.107950E+11 | 0.00 | 0.65 |
April | 0.905704E+09 | 0.523358E+09 | 0.00 | 25254178.01 | 81460386.46 | 0.00 | 0.740063E+10 | 0.00 | 0.67 |
May | 0.328762E+09 | 0.293175E+10 | 0.00 | 13258343.37 | 58744169.64 | 0.00 | 0.257493E+10 | 0.00 | 0.53 |
June | 97411142.19 | 0.815536E+10 | 0.00 | 6179368.47 | 77155883.95 | 0.00 | 0.122034E+10 | 0.00 | 0.41 |
July | 0.00 | 0.105369E+11 | 0.00 | 0.00 | 0.194026E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 2138564.15 | 0.126740E+11 | 0.00 | 227871.60 | 0.145249E+09 | 0.00 | 7916889.72 | 0.00 | 0.30 |
September | 0.177304E+09 | 0.515295E+10 | 0.00 | 13173374.18 | 0.104565E+09 | 0.00 | 0.176802E+10 | 0.00 | 0.50 |
October | 0.109464E+10 | 0.158106E+10 | 0.00 | 27187077.13 | 14468532.98 | 0.00 | 0.107199E+11 | 0.00 | 0.64 |
November | 0.252301E+10 | 0.133588E+09 | 0.00 | 25170110.55 | 91914762.10 | 0.00 | 0.115155E+11 | 0.00 | 0.61 |
December | 0.604316E+10 | 23276720.50 | 0.00 | 13566631.30 | 0.00 | 0.00 | 0.746620E+10 | 0.00 | 0.45 |
Annual Sum or Average | 0.303196E+11 | 0.419710E+11 | 0.00 | 0.165013E+09 | 0.861238E+09 | 78692093.23 | 0.626825E+11 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.101399E+11 | 0.126740E+11 | 0.00 | 27187077.13 | 0.194026E+09 | 74653098.16 | 0.115155E+11 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120268E+11 | 0.00 | 0.00 | 0.00 | 30148796.94 | 0.924219E+09 | 0.00 | 0.00 | 0.34 |
February | 0.100730E+11 | 22139.73 | 0.00 | 494894.41 | 4760904.15 | 0.210441E+09 | 0.329844E+09 | 0.00 | 0.42 |
March | 0.746402E+10 | 0.118024E+09 | 0.00 | 3889485.99 | 0.173051E+09 | 0.00 | 0.259357E+10 | 0.00 | 0.50 |
April | 0.319223E+10 | 0.246443E+09 | 0.00 | 8667811.42 | 0.247891E+09 | 0.00 | 0.290462E+10 | 0.00 | 0.49 |
May | 0.809437E+09 | 0.198296E+10 | 0.00 | 5881678.00 | 0.321610E+09 | 0.00 | 0.131890E+10 | 0.00 | 0.39 |
June | 0.292990E+09 | 0.693773E+10 | 0.00 | 3232295.49 | 0.118705E+09 | 0.00 | 0.687465E+09 | 0.00 | 0.33 |
July | 310469.47 | 0.910275E+10 | 0.00 | 21293.10 | 0.373850E+09 | 0.00 | 96931.43 | 0.00 | 0.24 |
August | 8494613.56 | 0.114025E+11 | 0.00 | 124468.06 | 0.143800E+09 | 0.00 | 5834858.55 | 0.00 | 0.27 |
September | 0.391855E+09 | 0.423497E+10 | 0.00 | 5993669.30 | 0.495244E+09 | 0.00 | 0.861385E+09 | 0.00 | 0.38 |
October | 0.467799E+10 | 0.123118E+10 | 0.00 | 6868861.84 | 0.126831E+09 | 0.00 | 0.330247E+10 | 0.00 | 0.46 |
November | 0.835568E+10 | 32115403.72 | 0.00 | 1767559.25 | 0.253691E+09 | 2597938.74 | 0.152081E+10 | 0.00 | 0.45 |
December | 0.108804E+11 | 20961404.80 | 0.00 | 71200.73 | 47737690.52 | 0.173308E+09 | 0.128623E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.581732E+11 | 0.353096E+11 | 0.00 | 37013217.59 | 0.233732E+10 | 0.131057E+10 | 0.136536E+11 | 0.00 | 0.39 |
Minimum of Months | 310469.47 | 0.00 | 0.00 | 0.00 | 4760904.15 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.120268E+11 | 0.114025E+11 | 0.00 | 8667811.42 | 0.495244E+09 | 0.924219E+09 | 0.330247E+10 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.985135E+10 | 0.00 | 0.00 | 0.00 | 24570013.33 | 0.271332E+10 | 0.00 | 0.00 | 0.35 |
February | 0.895417E+10 | 0.00 | 0.00 | 230935.26 | 8358555.09 | 0.110029E+10 | 0.105752E+09 | 0.00 | 0.42 |
March | 0.852574E+10 | 0.119198E+09 | 0.00 | 2240804.71 | 0.174733E+09 | 29773491.37 | 0.108551E+10 | 0.00 | 0.51 |
April | 0.367484E+10 | 0.190909E+09 | 0.00 | 7463234.39 | 0.266433E+09 | 1666647.06 | 0.209135E+10 | 0.00 | 0.52 |
May | 0.843395E+09 | 0.182480E+10 | 0.00 | 3882635.33 | 0.383926E+09 | 0.00 | 0.103324E+10 | 0.00 | 0.39 |
June | 0.374624E+09 | 0.666765E+10 | 0.00 | 2682584.16 | 0.132921E+09 | 0.00 | 0.518410E+09 | 0.00 | 0.33 |
July | 0.00 | 0.877049E+10 | 0.00 | 0.00 | 0.424633E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 7510791.25 | 0.110804E+11 | 0.00 | 3054.46 | 0.142869E+09 | 0.00 | 792292.90 | 0.00 | 0.27 |
September | 0.472252E+09 | 0.377980E+10 | 0.00 | 4577386.87 | 0.975053E+09 | 0.00 | 0.526246E+09 | 0.00 | 0.37 |
October | 0.566528E+10 | 0.107061E+10 | 0.00 | 3040005.88 | 0.285172E+09 | 22281285.40 | 0.158119E+10 | 0.00 | 0.46 |
November | 0.867986E+10 | 20694027.02 | 1427261.50 | 379698.62 | 0.295253E+09 | 0.171863E+09 | 0.348715E+09 | 38932.08 | 0.45 |
December | 0.995214E+10 | 6251315.84 | 0.00 | 0.00 | 68064481.22 | 0.894805E+09 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.570012E+11 | 0.335308E+11 | 1427261.50 | 24500339.69 | 0.318199E+10 | 0.493400E+10 | 0.729121E+10 | 38932.08 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8358555.09 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.995214E+10 | 0.110804E+11 | 1427261.50 | 7463234.39 | 0.975053E+09 | 0.271332E+10 | 0.209135E+10 | 38932.08 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.502193E+09 | 0.00 | 0.00 | 0.00 | 5180801.36 | 0.236297E+10 | 0.00 | 0.00 | 0.37 |
February | 0.846703E+09 | 0.00 | 285671.28 | 56813.18 | 1475674.00 | 0.138559E+10 | 16323119.21 | 1128.88 | 0.44 |
March | 0.163550E+10 | 27291328.81 | 0.00 | 310968.36 | 36740213.31 | 0.289566E+09 | 0.109683E+09 | 0.00 | 0.51 |
April | 0.934388E+09 | 63147158.21 | 0.00 | 1436802.43 | 39737129.79 | 63246985.41 | 0.228664E+09 | 0.00 | 0.54 |
May | 0.235804E+09 | 0.517318E+09 | 0.00 | 767105.10 | 57544457.96 | 587944.20 | 0.165727E+09 | 0.00 | 0.43 |
June | 83510531.02 | 0.206965E+10 | 0.00 | 667331.52 | 34596114.15 | 0.00 | 0.114312E+09 | 0.00 | 0.44 |
July | 0.00 | 0.279490E+10 | 0.00 | 0.00 | 79603393.55 | 0.00 | 0.00 | 0.00 | 0.34 |
August | 1751421.69 | 0.331443E+10 | 0.00 | 0.00 | 38133040.43 | 0.00 | 0.00 | 0.00 | 0.37 |
September | 0.123743E+09 | 0.986313E+09 | 0.00 | 917441.86 | 0.191286E+09 | 0.00 | 93435746.90 | 0.00 | 0.41 |
October | 0.122844E+10 | 0.250450E+09 | 0.00 | 281925.97 | 63093836.65 | 0.160406E+09 | 0.132060E+09 | 0.00 | 0.46 |
November | 0.140917E+10 | 3867307.11 | 2924967.33 | 11923.36 | 60189228.34 | 0.549601E+09 | 2832322.26 | 14057.73 | 0.45 |
December | 0.919217E+09 | 0.00 | 70507.05 | 0.00 | 15598747.76 | 0.145996E+10 | 0.00 | 878.43 | 0.41 |
Annual Sum or Average | 0.792042E+10 | 0.100274E+11 | 3281145.66 | 4450311.79 | 0.623179E+09 | 0.627193E+10 | 0.863037E+09 | 16065.04 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1475674.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.163550E+10 | 0.331443E+10 | 2924967.33 | 1436802.43 | 0.191286E+09 | 0.236297E+10 | 0.228664E+09 | 14057.73 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.786983E+09 | 0.00 | 0.00 | 0.00 | 4461924.62 | 0.155555E+10 | 0.00 | 0.00 | 0.49 |
February | 0.861884E+09 | 0.00 | 245908.17 | 156065.89 | 1270912.68 | 0.911402E+09 | 0.100179E+09 | 1096.23 | 0.58 |
March | 0.130307E+10 | 21969938.37 | 0.00 | 702357.26 | 32816113.97 | 0.163449E+09 | 0.292531E+09 | 0.00 | 0.70 |
April | 0.608981E+09 | 43305841.14 | 0.00 | 2311481.97 | 44389174.63 | 32395311.72 | 0.494883E+09 | 0.00 | 0.82 |
May | 0.152762E+09 | 0.492610E+09 | 0.00 | 1174217.42 | 54041022.18 | 468555.95 | 0.253527E+09 | 0.00 | 0.66 |
June | 55126339.30 | 0.173858E+10 | 0.00 | 874266.25 | 34272338.25 | 0.00 | 0.166195E+09 | 0.00 | 0.63 |
July | 0.00 | 0.241967E+10 | 0.00 | 0.00 | 97324441.91 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 1508398.22 | 0.278372E+10 | 0.00 | 0.00 | 54021453.92 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 97022635.97 | 0.927047E+09 | 0.00 | 1102367.68 | 0.173755E+09 | 294212.85 | 0.115312E+09 | 0.00 | 0.62 |
October | 0.860414E+09 | 0.211268E+09 | 0.00 | 869636.04 | 62692265.21 | 0.124777E+09 | 0.378353E+09 | 0.00 | 0.65 |
November | 0.132513E+10 | 4534602.99 | 2470919.22 | 39702.79 | 50633586.82 | 0.314797E+09 | 37411545.38 | 8106.60 | 0.61 |
December | 0.111184E+10 | 0.00 | 59469.72 | 0.00 | 13434299.42 | 0.884022E+09 | 0.00 | 2010.47 | 0.55 |
Annual Sum or Average | 0.716473E+10 | 0.864270E+10 | 2776297.10 | 7230095.30 | 0.623113E+09 | 0.398715E+10 | 0.183839E+10 | 11213.30 | 0.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1270912.68 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.132513E+10 | 0.278372E+10 | 2470919.22 | 2311481.97 | 0.173755E+09 | 0.155555E+10 | 0.494883E+09 | 8106.60 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101605E+10 | 0.00 | 0.00 | 734666.64 | 5468331.35 | 0.151166E+10 | 0.490223E+09 | 0.00 | 0.40 |
February | 0.100083E+10 | 0.00 | 302304.13 | 1676039.74 | 1557572.63 | 0.905334E+09 | 0.641131E+09 | 413.20 | 0.53 |
March | 0.129253E+10 | 60826695.72 | 0.00 | 3066826.81 | 22038025.88 | 0.207170E+09 | 0.982038E+09 | 0.00 | 0.67 |
April | 0.762313E+09 | 87263172.70 | 0.00 | 3336525.99 | 30943042.96 | 60886654.92 | 0.651127E+09 | 0.00 | 0.71 |
May | 0.239645E+09 | 0.583576E+09 | 0.00 | 1078644.62 | 69106451.75 | 928256.00 | 0.222572E+09 | 0.00 | 0.50 |
June | 99519842.32 | 0.209984E+10 | 0.00 | 678344.74 | 61045223.31 | 0.00 | 0.111852E+09 | 0.00 | 0.46 |
July | 0.00 | 0.290971E+10 | 0.00 | 0.00 | 0.102626E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 1848624.07 | 0.383468E+10 | 0.00 | 0.00 | 46193029.61 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.120768E+09 | 0.137286E+10 | 0.00 | 1799576.99 | 0.187628E+09 | 360573.86 | 0.177284E+09 | 0.00 | 0.57 |
October | 0.887612E+09 | 0.429107E+09 | 0.00 | 3597509.85 | 39667595.83 | 0.126546E+09 | 0.118414E+10 | 0.00 | 0.71 |
November | 0.119591E+10 | 8603653.81 | 2410705.93 | 2795722.05 | 61340607.20 | 0.312767E+09 | 0.994431E+09 | 10523.14 | 0.61 |
December | 0.120688E+10 | 5288533.61 | 0.00 | 1633787.13 | 13789372.96 | 0.746154E+09 | 0.745957E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.782391E+10 | 0.113918E+11 | 2713010.05 | 20397644.55 | 0.641403E+09 | 0.387180E+10 | 0.620076E+10 | 10936.33 | 0.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1557572.63 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.129253E+10 | 0.383468E+10 | 2410705.93 | 3597509.85 | 0.187628E+09 | 0.151166E+10 | 0.118414E+10 | 10523.14 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.773831E+09 | 0.00 | 0.00 | 0.00 | 4924115.08 | 0.179469E+10 | 0.00 | 0.00 | 0.54 |
February | 0.917434E+09 | 0.00 | 272378.41 | 277675.42 | 1402560.74 | 0.106894E+10 | 98014458.38 | 212.05 | 0.65 |
March | 0.137564E+10 | 32525416.37 | 0.00 | 1084764.32 | 31376779.23 | 0.255850E+09 | 0.368265E+09 | 0.00 | 0.81 |
April | 0.759978E+09 | 42791243.37 | 0.00 | 2267474.29 | 51408019.82 | 56021442.14 | 0.438555E+09 | 0.00 | 0.91 |
May | 0.229401E+09 | 0.420726E+09 | 0.00 | 909011.62 | 85878304.47 | 784865.88 | 0.202926E+09 | 0.00 | 0.68 |
June | 96671027.70 | 0.162096E+10 | 0.00 | 612467.03 | 84489579.09 | 0.00 | 98903823.78 | 0.00 | 0.61 |
July | 0.00 | 0.220822E+10 | 0.00 | 0.00 | 0.144257E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 1664646.32 | 0.273076E+10 | 0.00 | 0.00 | 85801460.72 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.124079E+09 | 0.830981E+09 | 0.00 | 937756.13 | 0.238748E+09 | 324689.02 | 89540611.43 | 0.00 | 0.63 |
October | 0.106237E+10 | 0.188586E+09 | 0.00 | 908798.02 | 94110908.66 | 0.143020E+09 | 0.324779E+09 | 0.00 | 0.74 |
November | 0.128577E+10 | 417063.49 | 2714091.31 | 342307.00 | 60465747.93 | 0.455599E+09 | 0.134535E+09 | 7993.09 | 0.69 |
December | 0.105429E+10 | 433096.39 | 65432.92 | 3358.25 | 14392800.94 | 0.113151E+10 | 12005388.63 | 2415.72 | 0.61 |
Annual Sum or Average | 0.768113E+10 | 0.807641E+10 | 3051902.64 | 7343612.06 | 0.897256E+09 | 0.490674E+10 | 0.176753E+10 | 10620.86 | 0.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1402560.74 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.137564E+10 | 0.273076E+10 | 2714091.31 | 2267474.29 | 0.238748E+09 | 0.179469E+10 | 0.438555E+09 | 7993.09 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.652089E+09 | 0.00 | 0.00 | 0.00 | 2727755.89 | 0.232320E+10 | 0.00 | 0.00 | 0.36 |
February | 0.111492E+10 | 0.00 | 0.00 | 0.00 | 198362.62 | 0.134703E+10 | 0.00 | 0.00 | 0.43 |
March | 0.200649E+10 | 8326528.01 | 0.00 | 24715.14 | 51139623.75 | 0.214333E+09 | 29950159.04 | 0.00 | 0.50 |
April | 0.118541E+10 | 20711207.53 | 0.00 | 254795.92 | 81431167.74 | 48182566.53 | 45501729.57 | 0.00 | 0.47 |
May | 0.343724E+09 | 0.360809E+09 | 0.00 | 255758.10 | 0.111932E+09 | 0.00 | 72596459.72 | 0.00 | 0.36 |
June | 0.102316E+09 | 0.159925E+10 | 0.00 | 510611.41 | 25396064.88 | 0.00 | 90481321.61 | 0.00 | 0.34 |
July | 0.00 | 0.223528E+10 | 0.00 | 0.00 | 62083280.82 | 0.00 | 0.00 | 0.00 | 0.27 |
August | 1460394.79 | 0.268743E+10 | 0.00 | 1828.29 | 30865827.69 | 0.00 | 258786.33 | 0.00 | 0.29 |
September | 0.150980E+09 | 0.942882E+09 | 0.00 | 1033083.10 | 36496983.55 | 0.00 | 0.130100E+09 | 0.00 | 0.38 |
October | 0.156035E+10 | 0.237531E+09 | 0.00 | 429153.53 | 16026035.26 | 9018415.69 | 0.214028E+09 | 0.00 | 0.46 |
November | 0.214834E+10 | 2418166.70 | 133767.31 | 25794.97 | 40057771.84 | 0.156673E+09 | 29958641.85 | 3294.94 | 0.47 |
December | 0.179117E+10 | 0.00 | 0.00 | 0.00 | 3386531.02 | 0.906867E+09 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.110572E+11 | 0.809464E+10 | 133767.31 | 2535740.46 | 0.461741E+09 | 0.500531E+10 | 0.612875E+09 | 3294.94 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 198362.62 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.214834E+10 | 0.268743E+10 | 133767.31 | 1033083.10 | 0.111932E+09 | 0.232320E+10 | 0.214028E+09 | 3294.94 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.909309E+09 | 0.00 | 0.00 | 0.00 | 2048957.20 | 0.130082E+10 | 0.00 | 0.00 | 0.42 |
February | 0.960868E+09 | 0.00 | 0.00 | 121447.68 | 149000.33 | 0.774233E+09 | 94998704.41 | 0.00 | 0.51 |
March | 0.142981E+10 | 10773268.89 | 0.00 | 337843.52 | 34648591.00 | 73879994.08 | 0.192286E+09 | 0.00 | 0.60 |
April | 0.682220E+09 | 29232018.83 | 0.00 | 1315621.51 | 50407288.21 | 14878029.28 | 0.317367E+09 | 0.00 | 0.63 |
May | 0.171906E+09 | 0.386169E+09 | 0.00 | 966409.07 | 67187978.42 | 0.00 | 0.204484E+09 | 0.00 | 0.54 |
June | 50593891.95 | 0.141270E+10 | 0.00 | 855682.70 | 17150152.23 | 0.00 | 0.162534E+09 | 0.00 | 0.52 |
July | 0.00 | 0.202286E+10 | 0.00 | 0.00 | 58924192.05 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 1096977.34 | 0.233884E+10 | 0.00 | 1466.62 | 23183482.44 | 0.00 | 194294.37 | 0.00 | 0.41 |
September | 0.105261E+09 | 0.868352E+09 | 0.00 | 1287348.85 | 22140850.32 | 0.00 | 0.160438E+09 | 0.00 | 0.56 |
October | 0.900020E+09 | 0.208909E+09 | 0.00 | 1429086.78 | 5821765.65 | 6180340.89 | 0.595150E+09 | 0.00 | 0.62 |
November | 0.152916E+10 | 2302365.07 | 0.00 | 292579.39 | 29706442.96 | 40149778.32 | 0.190226E+09 | 0.00 | 0.56 |
December | 0.164617E+10 | 0.00 | 0.00 | 0.00 | 2543796.95 | 0.376499E+09 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.838641E+10 | 0.728013E+10 | 0.00 | 6607486.12 | 0.313912E+09 | 0.258664E+10 | 0.191768E+10 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 149000.33 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.164617E+10 | 0.233884E+10 | 0.00 | 1429086.78 | 67187978.42 | 0.130082E+10 | 0.595150E+09 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112676E+10 | 0.00 | 0.00 | 52019.16 | 2731305.95 | 0.236993E+10 | 41870780.77 | 0.00 | 0.41 |
February | 0.106842E+10 | 0.00 | 0.00 | 746491.43 | 198620.78 | 0.157783E+10 | 0.229546E+09 | 0.00 | 0.51 |
March | 0.164238E+10 | 47892267.92 | 0.00 | 860475.94 | 24027294.17 | 0.599386E+09 | 0.252546E+09 | 0.00 | 0.57 |
April | 0.971901E+09 | 49012176.79 | 0.00 | 1125913.10 | 66269492.70 | 0.308076E+09 | 0.113723E+09 | 0.00 | 0.55 |
May | 0.308267E+09 | 0.480946E+09 | 0.00 | 353948.11 | 0.102862E+09 | 69059782.23 | 69733374.46 | 0.00 | 0.41 |
June | 0.113293E+09 | 0.189138E+10 | 0.00 | 393246.22 | 75035307.09 | 19379210.37 | 60511457.41 | 0.00 | 0.39 |
July | 0.00 | 0.262988E+10 | 0.00 | 0.00 | 0.115554E+09 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 1723249.23 | 0.357289E+10 | 0.00 | 0.00 | 46835790.33 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.152816E+09 | 0.137375E+10 | 0.00 | 1699528.24 | 51084567.71 | 15246093.49 | 0.167605E+09 | 0.00 | 0.53 |
October | 0.102627E+10 | 0.403930E+09 | 0.00 | 2916218.05 | 9178944.53 | 0.269280E+09 | 0.977649E+09 | 0.00 | 0.66 |
November | 0.152615E+10 | 11233264.96 | 0.00 | 2132165.43 | 32844715.39 | 0.508169E+09 | 0.813290E+09 | 0.00 | 0.60 |
December | 0.169753E+10 | 3688206.20 | 0.00 | 636845.33 | 1040247.40 | 0.982067E+09 | 0.343243E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.963550E+10 | 0.104646E+11 | 0.00 | 10916851.00 | 0.527662E+09 | 0.671843E+10 | 0.306972E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 198620.78 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.169753E+10 | 0.357289E+10 | 0.00 | 2916218.05 | 0.115554E+09 | 0.236993E+10 | 0.977649E+09 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.770724E+09 | 0.00 | 0.00 | 0.00 | 2121910.55 | 0.151396E+10 | 0.00 | 0.00 | 0.43 |
February | 0.994074E+09 | 0.00 | 0.00 | 162354.46 | 154305.50 | 0.862091E+09 | 44985975.51 | 0.00 | 0.53 |
March | 0.148595E+10 | 25960018.83 | 0.00 | 506454.77 | 25702459.20 | 94817582.82 | 0.189697E+09 | 0.00 | 0.64 |
April | 0.835268E+09 | 32633478.10 | 0.00 | 973661.48 | 53141594.31 | 14280193.36 | 0.174335E+09 | 0.00 | 0.64 |
May | 0.234602E+09 | 0.361234E+09 | 0.00 | 540920.51 | 64240391.06 | 0.00 | 0.127491E+09 | 0.00 | 0.52 |
June | 81351150.57 | 0.135709E+10 | 0.00 | 526822.82 | 21154553.54 | 0.00 | 81673617.27 | 0.00 | 0.48 |
July | 0.00 | 0.188578E+10 | 0.00 | 0.00 | 54803014.37 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 1136035.34 | 0.233530E+10 | 0.00 | 1657.72 | 14729529.66 | 0.00 | 201073.36 | 0.00 | 0.40 |
September | 0.117754E+09 | 0.838110E+09 | 0.00 | 1053520.57 | 26808949.72 | 0.00 | 0.110853E+09 | 0.00 | 0.53 |
October | 0.106166E+10 | 0.206487E+09 | 0.00 | 1106042.31 | 7817497.65 | 4407169.22 | 0.415350E+09 | 0.00 | 0.63 |
November | 0.159156E+10 | 1953714.23 | 106184.96 | 456185.52 | 31089108.25 | 67311327.08 | 0.190402E+09 | 435.22 | 0.60 |
December | 0.155745E+10 | 338201.85 | 0.00 | 9888.80 | 2296167.27 | 0.513857E+09 | 22646244.05 | 0.00 | 0.51 |
Annual Sum or Average | 0.873152E+10 | 0.704488E+10 | 106184.96 | 5337508.97 | 0.304059E+09 | 0.307073E+10 | 0.135764E+10 | 435.22 | 0.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 154305.50 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.159156E+10 | 0.233530E+10 | 106184.96 | 1106042.31 | 64240391.06 | 0.151396E+10 | 0.415350E+09 | 435.22 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.669046E+09 | 0.00 | 0.00 | 0.00 | 6357988.57 | 0.215355E+10 | 0.00 | 0.00 | 0.35 |
February | 0.112076E+10 | 4668.98 | 0.00 | 60362.96 | 1004012.67 | 0.115693E+10 | 11692530.79 | 0.00 | 0.42 |
March | 0.189777E+10 | 31703764.06 | 0.00 | 286314.53 | 32431653.92 | 0.114681E+09 | 0.105545E+09 | 0.00 | 0.50 |
April | 0.100888E+10 | 80558894.57 | 0.00 | 1192455.55 | 31907261.65 | 17287736.94 | 0.238957E+09 | 0.00 | 0.50 |
May | 0.263232E+09 | 0.580299E+09 | 0.00 | 882401.83 | 32849884.02 | 0.00 | 0.174191E+09 | 0.00 | 0.43 |
June | 88683720.49 | 0.220639E+10 | 0.00 | 703561.74 | 16608338.06 | 0.00 | 0.117573E+09 | 0.00 | 0.44 |
July | 78727.68 | 0.295686E+10 | 0.00 | 0.00 | 54259119.92 | 0.00 | 0.00 | 0.00 | 0.35 |
August | 2505009.68 | 0.347000E+10 | 0.00 | 398.91 | 30536842.85 | 0.00 | 483504.62 | 0.00 | 0.37 |
September | 0.155051E+09 | 0.113611E+10 | 0.00 | 890290.08 | 55842653.02 | 0.00 | 97953143.20 | 0.00 | 0.40 |
October | 0.142929E+10 | 0.286185E+09 | 0.00 | 396512.95 | 27668434.73 | 25864347.43 | 0.176543E+09 | 0.00 | 0.45 |
November | 0.175683E+10 | 5584172.38 | 256916.25 | 20590.80 | 54427598.84 | 0.303646E+09 | 27254774.74 | 7447.86 | 0.45 |
December | 0.141212E+10 | 0.00 | 0.00 | 0.00 | 14487744.36 | 0.981570E+09 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.980423E+10 | 0.107537E+11 | 256916.25 | 4432889.34 | 0.358382E+09 | 0.475353E+10 | 0.950193E+09 | 7447.86 | 0.42 |
Minimum of Months | 78727.68 | 0.00 | 0.00 | 0.00 | 1004012.67 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.189777E+10 | 0.347000E+10 | 256916.25 | 1192455.55 | 55842653.02 | 0.215355E+10 | 0.238957E+09 | 7447.86 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.967174E+09 | 0.00 | 0.00 | 0.00 | 5500656.71 | 0.142316E+10 | 0.00 | 0.00 | 0.47 |
February | 0.102669E+10 | 4356.23 | 0.00 | 229550.70 | 868628.34 | 0.803455E+09 | 0.126959E+09 | 0.00 | 0.57 |
March | 0.139549E+10 | 23171461.98 | 0.00 | 800921.05 | 30687932.72 | 71559955.32 | 0.392872E+09 | 0.00 | 0.69 |
April | 0.654208E+09 | 59629038.04 | 0.00 | 2194034.84 | 35221876.22 | 8656053.32 | 0.561149E+09 | 0.00 | 0.78 |
May | 0.184314E+09 | 0.513990E+09 | 0.00 | 1327375.93 | 41410820.21 | 0.00 | 0.275403E+09 | 0.00 | 0.66 |
June | 61576701.22 | 0.180394E+10 | 0.00 | 926890.31 | 18561370.21 | 0.00 | 0.179496E+09 | 0.00 | 0.62 |
July | 68111.78 | 0.250063E+10 | 0.00 | 0.00 | 76166963.71 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 2508666.18 | 0.286242E+10 | 0.00 | 125.78 | 32057982.08 | 0.00 | 77086.47 | 0.00 | 0.50 |
September | 0.129140E+09 | 0.945542E+09 | 0.00 | 1064710.07 | 0.126250E+09 | 0.00 | 0.128122E+09 | 0.00 | 0.60 |
October | 0.101382E+10 | 0.216957E+09 | 0.00 | 1128276.42 | 44308803.29 | 24457208.52 | 0.483265E+09 | 0.00 | 0.66 |
November | 0.151231E+10 | 5058509.25 | 827254.69 | 131367.88 | 46203692.92 | 0.177679E+09 | 0.116745E+09 | 5245.91 | 0.61 |
December | 0.145804E+10 | 0.00 | 0.00 | 0.00 | 12534169.78 | 0.596707E+09 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.840534E+10 | 0.893134E+10 | 827254.69 | 7803252.97 | 0.469773E+09 | 0.310568E+10 | 0.226409E+10 | 5245.91 | 0.60 |
Minimum of Months | 68111.78 | 0.00 | 0.00 | 0.00 | 868628.34 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.151231E+10 | 0.286242E+10 | 827254.69 | 2194034.84 | 0.126250E+09 | 0.142316E+10 | 0.561149E+09 | 5245.91 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111256E+10 | 0.00 | 0.00 | 1111230.32 | 6352488.85 | 0.123681E+10 | 0.614017E+09 | 0.00 | 0.37 |
February | 0.115440E+10 | 12332.88 | 0.00 | 2003049.54 | 1003144.19 | 0.679094E+09 | 0.716301E+09 | 0.00 | 0.51 |
March | 0.140210E+10 | 78473012.59 | 0.00 | 3175390.22 | 11615934.06 | 66660452.32 | 0.102953E+10 | 0.00 | 0.64 |
April | 0.784483E+09 | 0.117333E+09 | 0.00 | 2947165.44 | 16351493.47 | 16166841.59 | 0.641317E+09 | 0.00 | 0.64 |
May | 0.260638E+09 | 0.670198E+09 | 0.00 | 1147078.50 | 32971171.98 | 0.00 | 0.212324E+09 | 0.00 | 0.48 |
June | 0.100701E+09 | 0.226698E+10 | 0.00 | 672099.01 | 19319696.79 | 0.00 | 0.107133E+09 | 0.00 | 0.45 |
July | 78659.58 | 0.310965E+10 | 0.00 | 0.00 | 53846703.14 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 2502842.82 | 0.404782E+10 | 0.00 | 303.54 | 30299411.84 | 0.00 | 483181.40 | 0.00 | 0.43 |
September | 0.143739E+09 | 0.155565E+10 | 0.00 | 1669302.16 | 41450378.29 | 0.00 | 0.168070E+09 | 0.00 | 0.55 |
October | 0.972909E+09 | 0.462919E+09 | 0.00 | 4066735.60 | 12401188.81 | 20834663.67 | 0.132409E+10 | 0.00 | 0.72 |
November | 0.132868E+10 | 16048864.80 | 131885.80 | 3629642.52 | 47642366.63 | 0.116254E+09 | 0.122588E+10 | 2840.12 | 0.63 |
December | 0.138549E+10 | 14941159.03 | 0.00 | 2213802.14 | 4472566.53 | 0.414862E+09 | 0.939351E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.864828E+10 | 0.123400E+11 | 131885.80 | 22635798.99 | 0.277727E+09 | 0.255068E+10 | 0.697850E+10 | 2840.12 | 0.52 |
Minimum of Months | 78659.58 | 0.00 | 0.00 | 0.00 | 1003144.19 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.140210E+10 | 0.404782E+10 | 131885.80 | 4066735.60 | 53846703.14 | 0.123681E+10 | 0.132409E+10 | 2840.12 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.847716E+09 | 0.00 | 0.00 | 0.00 | 5740205.79 | 0.164277E+10 | 0.00 | 0.00 | 0.49 |
February | 0.108002E+10 | 4215.31 | 0.00 | 305423.74 | 906456.39 | 0.885117E+09 | 90890478.65 | 0.00 | 0.61 |
March | 0.154569E+10 | 46475511.62 | 0.00 | 1044084.42 | 18851033.50 | 98149741.26 | 0.337309E+09 | 0.00 | 0.76 |
April | 0.820078E+09 | 69409123.63 | 0.00 | 1876622.08 | 34182809.17 | 15967526.48 | 0.387472E+09 | 0.00 | 0.81 |
May | 0.254725E+09 | 0.499812E+09 | 0.00 | 823776.74 | 43974549.61 | 0.00 | 0.182980E+09 | 0.00 | 0.65 |
June | 99743782.69 | 0.179459E+10 | 0.00 | 578399.02 | 30058977.13 | 0.00 | 88617250.12 | 0.00 | 0.60 |
July | 71078.00 | 0.241667E+10 | 0.00 | 0.00 | 71393311.63 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 2698491.30 | 0.293629E+10 | 0.00 | 0.00 | 24620442.73 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.148065E+09 | 0.925487E+09 | 0.00 | 820897.67 | 0.138646E+09 | 0.00 | 80190109.12 | 0.00 | 0.59 |
October | 0.120650E+10 | 0.226328E+09 | 0.00 | 998831.67 | 44868447.23 | 24704948.56 | 0.332467E+09 | 0.00 | 0.70 |
November | 0.149580E+10 | 3663651.59 | 855929.19 | 438468.86 | 49850589.86 | 0.241165E+09 | 0.180963E+09 | 5419.76 | 0.66 |
December | 0.138018E+10 | 1133134.61 | 0.00 | 19073.69 | 11946887.97 | 0.731734E+09 | 31269991.76 | 0.00 | 0.56 |
Annual Sum or Average | 0.888130E+10 | 0.891987E+10 | 855929.19 | 6905577.90 | 0.475040E+09 | 0.363961E+10 | 0.171216E+10 | 5419.76 | 0.61 |
Minimum of Months | 71078.00 | 0.00 | 0.00 | 0.00 | 906456.39 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.154569E+10 | 0.293629E+10 | 855929.19 | 1876622.08 | 0.138646E+09 | 0.164277E+10 | 0.387472E+09 | 5419.76 | 0.81 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.190212E+12 | 0.175567E+11 | 0.00 | 0.194020E+12 | 0.101313E+11 |
February | 0.187559E+12 | 0.147070E+11 | 0.00 | 0.191558E+12 | 0.201986E+11 |
March | 0.268122E+12 | 0.926739E+10 | 0.00 | 0.212644E+12 | 0.567273E+11 |
April | 0.297014E+12 | 0.436288E+10 | 0.00 | 0.140451E+12 | 0.989274E+11 |
May | 0.325574E+12 | -165899696.7 | 0.00 | 0.469192E+11 | 0.184546E+12 |
June | 0.315458E+12 | -0.594314E+10 | 0.00 | -0.156284E+11 | 0.276393E+12 |
July | 0.305667E+12 | -0.886113E+10 | 0.00 | -0.600775E+11 | 0.316205E+12 |
August | 0.285221E+12 | -0.106467E+11 | 0.00 | -0.728055E+11 | 0.354014E+12 |
September | 0.223988E+12 | -0.298099E+10 | 0.00 | -864564763.6 | 0.217198E+12 |
October | 0.216419E+12 | 0.454438E+10 | 0.00 | 0.156830E+12 | 0.947831E+11 |
November | 0.160411E+12 | 0.919725E+10 | 0.00 | 0.194465E+12 | 0.395227E+11 |
December | 0.155034E+12 | 0.155184E+11 | 0.00 | 0.219940E+12 | 0.151817E+11 |
Annual Sum or Average | 0.293068E+13 | 0.465562E+11 | 0.00 | 0.120745E+13 | 0.168383E+13 |
Minimum of Months | 0.155034E+12 | -0.106467E+11 | 0.00 | -0.728055E+11 | 0.101313E+11 |