Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 08:28:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1817.36 | 364.77 | 364.77 |
Net Site Energy | 1817.36 | 364.77 | 364.77 |
Total Source Energy | 5389.04 | 1081.66 | 1081.66 |
Net Source Energy | 5389.04 | 1081.66 | 1081.66 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 52.60 | 43.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 250.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 362.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 111.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 141.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 132.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1641.40 | 175.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 52.60 | 43.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 250.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 362.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 111.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 17.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 141.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 132.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 52.60 | 43.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 250.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 362.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 111.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 17.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 141.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 132.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 95.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 89.33 | 35.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 145.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 329.45 | 35.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 95.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 89.33 | 35.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 145.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 329.45 | 35.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1641.397 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1641.397 | 100.00 |
Total On-Site and Utility Electric Sources | 1641.397 | 100.00 |
Total Electricity End Uses | 1641.397 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 82.00 |
Time Setpoint Not Met During Occupied Cooling | 249.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1880.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 10.1959 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 10.1959 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.1959 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 10.1959 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
Total | 4982.19 | 10.1959 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 10.1959 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 10.1959 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-14:50 | 15-DEC-07:19 | - | - | - | - | - | - | - | - | - | - | 12-JAN-12:09 |
Heating | 0.00 | 51556.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 82562.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 30098.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 40588.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1223.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 34809.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8985.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 189289.74 | 60541.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 51556.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 82562.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 30098.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 6054.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 46.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1223.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 34809.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8985.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 166.57 | 47.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 793.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1146.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 353.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 54.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 449.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 143.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5198.30 | 190.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 33.43 | 9.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 159.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 230.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 90.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1043.38 | 38.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 33.43 | 9.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 159.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 230.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 90.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1043.38 | 38.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.75 | 0.199612 | 0.222000 | 0.833513 | 0.532298 | 0.500000 | 0.001909 |
CORE_MID VAV BOX COMPONENT | 2.84 | 0.264015 | 0.287000 | 0.814703 | 0.704039 | 0.500000 | 0.001443 |
CORE_TOP VAV BOX COMPONENT | 3.00 | 0.250087 | 0.281000 | 0.842096 | 0.666898 | 0.500000 | 0.001523 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.974234 | 0.162170 | 0.200000 | 0.194847 | 0.432454 | 0.500000 | 0.002349 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.06 | 0.094504 | 0.200000 | 0.211677 | 0.300000 | 0.500000 | 0.004032 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.18 | 0.134246 | 0.200000 | 0.235377 | 0.357988 | 0.500000 | 0.002838 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.19 | 0.083769 | 0.200000 | 0.238788 | 0.300000 | 0.500000 | 0.004548 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.797375 | 0.198140 | 0.221000 | 0.176220 | 0.528373 | 0.500000 | 0.001923 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.891545 | 0.112189 | 0.200000 | 0.178309 | 0.300000 | 0.500000 | 0.003396 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.971580 | 0.162613 | 0.200000 | 0.194316 | 0.433635 | 0.500000 | 0.002343 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.948380 | 0.105459 | 0.200000 | 0.189676 | 0.300000 | 0.500000 | 0.003613 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.852814 | 0.185259 | 0.201000 | 0.171416 | 0.494025 | 0.500000 | 0.002057 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 1.04 | 0.096444 | 0.200000 | 0.207419 | 0.300000 | 0.500000 | 0.003950 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.06 | 0.149245 | 0.200000 | 0.211721 | 0.397988 | 0.500000 | 0.002553 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 1.10 | 0.090636 | 0.200000 | 0.220696 | 0.300000 | 0.500000 | 0.004204 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 22896.72 |
CORE_MID VAV BOX REHEAT COIL | 22380.00 |
CORE_TOP VAV BOX REHEAT COIL | 35036.69 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 16271.02 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10643.40 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 16147.18 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10643.22 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 12161.35 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8034.46 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12051.14 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8034.39 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 12882.61 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 8477.60 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 12767.77 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 8477.52 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.68 | 1.57 | 7.36 | 1.89 | 6.60 | 6.60 | 0.300000 | 0.286671 | 6.60 |
PACU_VAV_MID | 3.45 | 1.63 | 6.89 | 2.30 | 5.91 | 5.91 | 0.300000 | 0.388206 | 5.91 |
PACU_VAV_TOP | 3.70 | 1.72 | 7.40 | 3.23 | 6.82 | 6.82 | 0.300000 | 0.473460 | 6.82 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 6.60 |
PACU_VAV_MID_OA_CONTROLLER | 5.91 |
PACU_VAV_TOP_OA_CONTROLLER | 6.82 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 6.60 | 109197.46 | 0.800655 | 2.20 | 36395.51 | 0.800655 |
PACU_VAV_MID COOLING COIL | 5.91 | 97905.72 | 0.800655 | 1.97 | 32631.98 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 6.82 | 112946.86 | 0.800655 | 2.27 | 37645.19 | 0.800655 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 19602.12 |
PACU_VAV_MID HEATING COIL | 21094.23 |
PACU_VAV_TOP HEATING COIL | 20692.45 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 6.60 |
PACU_VAV_MID FAN | 5.91 |
PACU_VAV_TOP FAN | 6.82 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 35.030 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.8668 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.8532 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.101 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9196 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9381 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6745 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.29350128E-12 | 0.14024199E-14 | -0.85558835E-13 | 0.14795563E-15 |
43 | 6 | 0.27596652E-07 | 0.24107488E-09 | 0.63308017E-08 | -0.12943591E-12 |
44 | 5 | -0.18463709E-03 | 0.20772830E-05 | -0.95040309E-04 | 0.62615177E-08 |
45 | 4 | 0.28572581 | 0.10171039E-02 | 0.97375121E-01 | -0.32667087E-04 |
46 | 3 | -7.1391205 | 0.31676816E-01 | -2.3011695 | 0.28385744E-01 |
47 | 2 | 40.451560 | 0.11313072 | 15.110175 | -0.32866754 |
48 | 1 | -80.224209 | 0.51250674E-01 | -29.002757 | 1.0717664 |
49 | 0 | 46.824341 | 0.10349526E-02 | 16.294583 | |
50 | 7 | -0.29575366E-12 | 0.13916748E-14 | -0.86470795E-13 | 0.14800413E-15 |
51 | 6 | 0.27759747E-07 | 0.23770535E-09 | 0.63667993E-08 | -0.13030888E-12 |
52 | 5 | -0.18546937E-03 | 0.20460315E-05 | -0.95457978E-04 | 0.62966404E-08 |
53 | 4 | 0.28670590 | 0.10008406E-02 | 0.97727300E-01 | -0.32804728E-04 |
54 | 3 | -7.1585449 | 0.31143840E-01 | -2.3069324 | 0.28480895E-01 |
55 | 2 | 40.515639 | 0.11114407 | 15.133849 | -0.32938113 |
56 | 1 | -80.273331 | 0.50317938E-01 | -29.023991 | 1.0728132 |
57 | 0 | 46.824340 | 0.10154678E-02 | 16.294067 | |
58 | 7 | -0.28281898E-12 | 0.14025464E-14 | -0.82622143E-13 | 0.19904483E-15 |
59 | 6 | 0.24787521E-07 | 0.29557932E-09 | 0.57107416E-08 | -0.11447606E-12 |
60 | 5 | -0.17017937E-03 | 0.25981591E-05 | -0.87765911E-04 | 0.56555961E-08 |
61 | 4 | 0.26851995 | 0.12946983E-02 | 0.91201294E-01 | -0.30269387E-04 |
62 | 3 | -6.7976835 | 0.40953066E-01 | -2.1999024 | 0.26714449E-01 |
63 | 2 | 39.324706 | 0.14826279 | 14.693101 | -0.31612152 |
64 | 1 | -79.359856 | 0.67961194E-01 | -28.628348 | 1.0533482 |
65 | 0 | 46.824347 | 0.13883650E-02 | 16.303898 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.42_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.387 | 2.387 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.387 | 2.387 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.42_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.387 | 2.387 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.42_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.387 | 2.387 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.973 | 0.1730 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1983E-002 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2053E-002 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3046E-002 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3106E-002 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.6636E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.7121E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.6026E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6282E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1710 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.3696E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1924 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.2724E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1248 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1389E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0870E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9083E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1983E-002 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2054E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3046E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3108E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.6634E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.7133E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.6024E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6280E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.3581E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2843E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7933E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8838E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.2449E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6459E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9724E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8144E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7612E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.7877E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.3211E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.3401E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1900E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.1965E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3717E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3805E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7423E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.8011E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9737E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0203E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4686E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.5014E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6024E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.6280E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4569E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5481E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4354E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9420E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1645E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3402E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0870E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9083E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7425E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.8013E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9738E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0202E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4685E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.5005E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6026E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.6282E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.1596E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1894E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5490E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7665E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.0702E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5646E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9724E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8145E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6485E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.7203E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1822E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.2596E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0908E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.1221E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3719E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3807E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1698 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1017 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1877 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1121 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1330 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5345E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.7993E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7067E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.1198E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1488E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.5864E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.7664E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.0781E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.5473E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.8615E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7478E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0955E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.3382E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0046E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6234E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.7332E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9656E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.7993E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7067E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.9278E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0595E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3502E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6561E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.9089E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4701E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.8615E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7479E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1698 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1017 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1877 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1121 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1330 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5337E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.7987E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.7064E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.1197E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1485E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.5863E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.7661E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.0777E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.5469E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.8609E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7475E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0957E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.3380E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0047E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6233E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.7329E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9654E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.7987E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7064E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.9277E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0592E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3500E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6559E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.9085E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4698E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.8610E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7475E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 42831.60139 | 42831.60139 | 3.75456 | 3.75456 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 7050.70296 | 7050.70296 | 0.36083 | 0.42469 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 32409.96121 | 32409.96121 | 2.83869 | 2.83869 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 14458.96760 | 14458.96760 | 0.74506 | 0.74506 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 33924.04164 | 33924.04164 | 2.99678 | 2.99678 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 34.83000 | 5.69897E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 24660.82378 | 24660.82378 | 1.27545 | 1.27545 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 11029.15811 | 11029.15811 | 0.97423 | 0.97423 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.69938E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 11423.04151 | 11423.04151 | 0.59232 | 0.59232 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11981.93692 | 11981.93692 | 1.05839 | 1.05839 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.82250 | 5.68971E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 7471.66083 | 7471.66083 | 0.38745 | 0.38745 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13323.35219 | 13323.35219 | 1.17688 | 1.17688 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.87500 | 5.69904E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 11336.30182 | 11336.30182 | 0.58781 | 0.58781 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 13516.49887 | 13516.49887 | 1.19394 | 1.19394 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 7471.53580 | 7471.53580 | 0.38745 | 0.38745 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 9026.75258 | 9026.75258 | 0.79737 | 0.79737 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 35.10000 | 5.69938E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 8543.43066 | 8543.43066 | 0.44271 | 0.44271 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 10092.90312 | 10092.90312 | 0.89154 | 0.89154 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 29.58750 | 5.69088E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5643.56899 | 5643.56899 | 0.29248 | 0.29248 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10998.87876 | 10998.87876 | 0.97158 | 0.97158 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.87500 | 5.69904E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 8466.24660 | 8466.24660 | 0.43870 | 0.43870 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 10736.31045 | 10736.31045 | 0.94838 | 0.94838 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.76000 | 5.69575E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 5643.51679 | 5643.51679 | 0.29248 | 0.29248 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 9654.49566 | 9654.49566 | 0.85281 | 0.85281 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 35.10000 | 5.69938E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 9049.27403 | 9049.27403 | 0.46897 | 0.46897 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 11740.78301 | 11740.78301 | 1.03709 | 1.03709 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44000 | 5.68912E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5954.38851 | 5954.38851 | 0.30861 | 0.30861 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11984.20320 | 11984.20320 | 1.05860 | 1.05860 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 8968.84553 | 8968.84553 | 0.46479 | 0.46479 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 12492.34398 | 12492.34398 | 1.10348 | 1.10348 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5954.32746 | 5954.32746 | 0.30861 | 0.30861 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 86658.82 | 6.59662 | 6.59662 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 24203.31 | 1.89106 | 1.89106 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 78809.21 | 5.91448 | 5.91448 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 24447.64 | 2.29604 | 2.29604 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 88844.10 | 6.82312 | 6.82312 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 24505.67 | 3.23047 | 3.23047 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.75456 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19961 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.83351 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53230 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.90871E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22896.71681 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.83869 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26401 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28700 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81470 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70404 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44310E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22379.99533 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.99678 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25009 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28100 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.84210 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66690 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.52347E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 35036.68965 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97423 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16217 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19485 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43245 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.34938E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16271.02408 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05839 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.45040E-002 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21168 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.03158E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10643.40000 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.17688 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13425 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23538 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35799 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.83808E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16147.18405 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.19394 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.37691E-002 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23879 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.54821E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10643.22300 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79737 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19814 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22100 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17622 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52837 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.92288E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12161.34669 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89154 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11219 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17831 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.39605E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8034.46373 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97158 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16261 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19432 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43364 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.34298E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12051.13617 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94838 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10546 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18968 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.61278E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8034.39071 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85281 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18526 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20100 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17142 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49402 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.05658E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12882.60722 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03709 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.64444E-002 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20742 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.95046E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8477.60496 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05860 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14925 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21172 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39799 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55284E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12767.76951 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.10348 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.06361E-002 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22070 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.20362E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8477.51933 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.68172 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.57203 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.36344 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.89106 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.59662 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 6.59662 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.28667 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.44534 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.62595 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.89068 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.29604 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.91448 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.91448 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.38821 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.70011 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.72278 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.40023 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.23047 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.82312 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 6.82312 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.47346 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 6.59662 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.91448 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 6.82312 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.59662 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.59662 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 109197.46053 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.19865 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 36395.51359 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 19602.11841 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 6.59662 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.91448 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.91448 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 97905.71922 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.97130 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32631.97622 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 21094.22841 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.91448 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.82312 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.82312 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 112946.85830 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.27415 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37645.18787 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 20692.45130 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 6.82312 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 107318.44 | 366185.73 | 11.20 | 2.80 | 3.21 | 3.38 | 3.53 | 9.54 | 10.95 | 11.55 | 12.05 | 6.2753 | 4.9620 | 3.3258 | 1.4074 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 96221.01 | 328319.70 | 11.20 | 2.80 | 3.21 | 3.38 | 3.53 | 9.54 | 10.95 | 11.55 | 12.05 | 5.6264 | 4.4489 | 2.9819 | 1.2618 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 111003.32 | 378759.06 | 11.20 | 2.80 | 3.21 | 3.38 | 3.53 | 9.54 | 10.95 | 11.55 | 12.05 | 6.4908 | 5.1324 | 3.4400 | 1.4557 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_EAST_0.4 | N/A | 2.387 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_WEST_0.4 | N/A | 2.387 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_EAST_0.4 | N/A | 2.387 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_EAST_0.4 | N/A | 2.387 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_WEST_0.4 | N/A | 2.387 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_WEST_0.4 | N/A | 2.387 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_NORTH_0.4 | N/A | 2.387 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_EAST_0.4 | N/A | 2.387 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_SOUTH_0.4 | N/A | 2.387 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.42_SHGC_WEST_0.4 | N/A | 2.387 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 7.5328857352E-002 | 0.1422007017 | Pass | Pass | 0.1330125363 | 0.3381795861 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1102941314 | 8.8206761411E-002 | Pass | Pass | 9.7687793933E-002 | 0.2906267727 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.7344435277E-002 | 6.7768147735E-002 | Pass | Pass | 0.1415789663 | 0.3637822975 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.5020701610E-002 | 4.3564582953E-002 | Pass | Pass | 34.1071744194 | 402.4053974758 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.8871972597E-002 | 0.1028270558 | Pass | Pass | 0.1187276420 | 0.3223412627 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.8968417583E-002 | 7.6439809035E-002 | Pass | Pass | 8.9928782277E-002 | 0.2836346168 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.3139259008E-002 | 5.6135525841E-002 | Pass | Pass | 8.8603538800E-002 | 0.2789431060 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1413876705 | 0.1752155744 | Pass | Pass | 9.3137557511E-002 | 0.2880392024 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2484633980 | 0.3014159077 | Pass | Pass | 9.5962104451E-002 | 0.2901288253 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1457307252 | 0.2041126024 | Pass | Pass | 8.6413856269E-002 | 0.2683512460 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.3579067288E-002 | 6.6184190879E-002 | Pass | Pass | 0.1319837647 | 0.3357998818 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1341565754 | 0.1836613544 | Pass | Pass | 0.1350656877 | 0.3416881170 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2331868605 | 0.3836138413 | Pass | Pass | 0.1467013315 | 0.3625298239 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1148167836 | 0.1783029340 | Pass | Pass | 0.1305543544 | 0.3295404185 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.7436492734E-002 | 6.3436830575E-002 | Pass | Pass | 0.1179412985 | 0.3195674787 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1576444699 | 0.2000555609 | Pass | Pass | 0.1217892121 | 0.3277802672 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2652629246 | 0.4020362849 | Pass | Pass | 0.1260539721 | 0.3305092876 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1419618021 | 0.2043756524 | Pass | Pass | 0.1162714573 | 0.3110065588 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4523.63 | 90.38 | 0.00 | 2045.54 | 1219.08 | 7878.64 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.42_SHGC_NORTH_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.387 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.42_SHGC_EAST_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.387 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.387 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.42_SHGC_WEST_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.387 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.42_SHGC_NORTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.42_SHGC_NORTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.42_SHGC_NORTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.42_SHGC_EAST_0.4 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.42_SHGC_EAST_0.4 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.42_SHGC_WEST_0.4 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.42_SHGC_WEST_0.4 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.387 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.42_SHGC_NORTH_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.387 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.42_SHGC_EAST_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.387 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.42_SHGC_SOUTH_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.387 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.42_SHGC_WEST_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.387 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.387 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 195.79 | 2.387 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.387 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.62 | 0.0000 | Y | 10.56 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.51 | 0.0000 | Y | 6.66 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.21 | 0.0000 | Y | 10.40 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.26 | 0.0000 | Y | 6.60 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.57 | 0.0000 | Y | 10.54 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.47 | 0.0000 | Y | 6.65 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.18 | 0.0000 | Y | 10.39 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.22 | 0.0000 | Y | 6.59 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.62 | 0.0000 | Y | 10.56 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.51 | 0.0000 | Y | 6.66 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.21 | 0.0000 | Y | 10.40 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.26 | 0.0000 | Y | 6.60 |
Interior Lighting Total | 10.1959 | 4982.19 | 50797.72 | 362.11 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.28 | AstronomicalClock | - | 41.81 | 41.81 | 4.42 | |
EXTERIOR_LIGHTS_B | 8033.20 | AstronomicalClock | - | 83.71 | 71.14 | 107.27 | |
Exterior Lighting Total | 8596.48 | 111.69 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 109197.46 | 87429.52 | 21767.94 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 97905.72 | 78388.73 | 19516.99 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 112946.86 | 90431.50 | 22515.36 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 107318.4 | 2.80 | 9.54 | N/A | N/A | 11.20 | |
PACU_VAV_MID COOLING COIL | 96221.0 | 2.80 | 9.54 | N/A | N/A | 11.20 | |
PACU_VAV_TOP COOLING COIL | 111003.3 | 2.80 | 9.54 | N/A | N/A | 11.20 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 22896.72 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 22380.00 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 35036.69 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16271.02 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10643.40 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16147.18 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10643.22 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12161.35 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8034.46 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12051.14 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8034.39 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12882.61 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8477.60 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12767.77 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8477.52 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 19602.12 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 21094.23 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 20692.45 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 6.60 | 14346.91 | 2174.89 | 1.00 | 1.13 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.91 | 12863.34 | 2174.89 | 1.00 | 1.13 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.61 | 1314.72 | 6.82 | 14744.40 | 2160.95 | 1.00 | 1.13 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.97 | 0.17 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 107318.44 | 2.80 | 9.54 | 11.20 | 6.2753 | 3.21 | 10.95 | 4.9620 | 3.38 | 11.55 | 3.3258 | 3.53 | 12.05 | 1.4074 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 96221.01 | 2.80 | 9.54 | 11.20 | 5.6264 | 3.21 | 10.95 | 4.4489 | 3.38 | 11.55 | 2.9819 | 3.53 | 12.05 | 1.2618 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 111003.32 | 2.80 | 9.54 | 11.20 | 6.4908 | 3.21 | 10.95 | 5.1324 | 3.38 | 11.55 | 3.4400 | 3.53 | 12.05 | 1.4557 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 42831.60 | 42831.60 | 43.55 | 3.755 | 3.755 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00878 | 25.11 | 0.00568 | 0.425 | 0.00 |
CORE_MID | 32409.96 | 32409.96 | 32.95 | 2.839 | 2.839 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 25.11 | 0.00568 | 0.425 | 0.00 |
CORE_TOP | 33924.04 | 33924.04 | 34.49 | 2.997 | 2.997 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00885 | 34.83 | 0.00570 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 11029.16 | 11029.16 | 53.19 | 0.974 | 0.974 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00863 | 35.10 | 0.00570 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11981.94 | 11981.94 | 91.28 | 1.058 | 1.058 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00857 | 28.82 | 0.00569 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13323.35 | 13323.35 | 64.26 | 1.177 | 1.177 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00861 | 34.88 | 0.00570 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 13516.50 | 13516.50 | 102.98 | 1.194 | 1.194 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00857 | 33.39 | 0.00570 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 9026.75 | 9026.75 | 43.54 | 0.797 | 0.797 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00872 | 35.10 | 0.00570 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 10092.90 | 10092.90 | 76.89 | 0.892 | 0.892 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00862 | 29.59 | 0.00569 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10998.88 | 10998.88 | 53.05 | 0.972 | 0.972 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00868 | 34.88 | 0.00570 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 10736.31 | 10736.31 | 81.80 | 0.948 | 0.948 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00861 | 32.76 | 0.00570 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9654.50 | 9654.50 | 46.56 | 0.853 | 0.853 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00867 | 35.10 | 0.00570 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 11740.78 | 11740.78 | 89.45 | 1.037 | 1.037 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00859 | 28.44 | 0.00569 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11984.20 | 11984.20 | 57.80 | 1.059 | 1.059 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00864 | 34.76 | 0.00570 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 12492.34 | 12492.34 | 95.18 | 1.103 | 1.103 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00858 | 33.21 | 0.00570 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 7050.70 | 7050.70 | 7.17 | 0.361 | 0.425 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 0.425 | 0.00 |
CORE_MID | 14458.97 | 14458.97 | 14.70 | 0.745 | 0.745 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 0.425 | 0.00 |
CORE_TOP | 24660.82 | 24660.82 | 25.07 | 1.275 | 1.275 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 11423.04 | 11423.04 | 55.09 | 0.592 | 0.592 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 7471.66 | 7471.66 | 56.92 | 0.387 | 0.387 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -7.90 | 0.00234 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11336.30 | 11336.30 | 54.68 | 0.588 | 0.588 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 7471.54 | 7471.54 | 56.92 | 0.387 | 0.387 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -7.90 | 0.00234 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8543.43 | 8543.43 | 41.21 | 0.443 | 0.443 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5643.57 | 5643.57 | 42.99 | 0.292 | 0.292 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -7.90 | 0.00234 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8466.25 | 8466.25 | 40.83 | 0.439 | 0.439 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 5643.52 | 5643.52 | 43.00 | 0.292 | 0.292 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -7.90 | 0.00234 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9049.27 | 9049.27 | 43.65 | 0.469 | 0.469 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5954.39 | 5954.39 | 45.36 | 0.309 | 0.309 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -7.90 | 0.00234 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8968.85 | 8968.85 | 43.26 | 0.465 | 0.465 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 5954.33 | 5954.33 | 45.37 | 0.309 | 0.309 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -7.90 | 0.00234 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 6.60 | 6.60 | 1.89 | 1.89 | 6.5966 | 1.8911 | 6.5966 | 0.2867 | 0.3000 |
PACU_VAV_MID | 5.91 | 5.91 | 2.30 | 2.30 | 5.9145 | 2.2960 | 5.9145 | 0.3882 | 0.3000 |
PACU_VAV_TOP | 6.82 | 6.82 | 3.23 | 3.23 | 6.8231 | 3.2305 | 6.8231 | 0.4735 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 22896.717 | 22896.717 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22896.72 | 11666.32 | 0.424691 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 7050.70 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 22379.995 | 22379.995 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22380.00 | 20466.95 | 0.745062 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 14458.97 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 35036.690 | 35036.690 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 35036.69 | 35036.69 | 1.275447 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 24660.82 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 16271.024 | 16271.024 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16271.02 | 16271.02 | 0.592317 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00775014 | 41.2277 | 11423.04 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 10643.400 | 10643.400 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10643.40 | 10643.40 | 0.387454 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00774582 | 41.2051 | 7471.66 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 16147.184 | 16147.184 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16147.18 | 16147.18 | 0.587809 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00774824 | 41.2177 | 11336.30 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 10643.223 | 10643.223 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10643.22 | 10643.22 | 0.387447 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00774582 | 41.2051 | 7471.54 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 12161.347 | 12161.347 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12161.35 | 12161.35 | 0.442712 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00779894 | 41.4831 | 8543.43 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 8034.464 | 8034.464 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8034.46 | 8034.46 | 0.292480 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00780282 | 41.5035 | 5643.57 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 12051.136 | 12051.136 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12051.14 | 12051.14 | 0.438700 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00779582 | 41.4667 | 8466.25 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8034.391 | 8034.391 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8034.39 | 8034.39 | 0.292477 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00780282 | 41.5035 | 5643.52 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 12882.607 | 12882.607 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12882.61 | 12882.61 | 0.468968 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00772928 | 41.1178 | 9049.27 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 8477.605 | 8477.605 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8477.60 | 8477.60 | 0.308612 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00772842 | 41.1134 | 5954.39 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 12767.770 | 12767.770 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12767.77 | 12767.77 | 0.464787 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00772628 | 41.1021 | 8968.85 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 8477.519 | 8477.519 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8477.52 | 8477.52 | 0.308609 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00772842 | 41.1134 | 5954.33 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 109197.461 | 87429.521 | 6.596619 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 105284.28 | 105284.28 | 6.596619 | 26.01 | 14.81 | 0.00819343 | 10.65 | 9.18 | 0.00819343 | 35.10 | 0.00569938 | 15.77 | 18.1179 | 24.00 | 0.00874590 | 38.7101 | 74608.15 | 0.00 | 112597.24 | 80672.07 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 19602.118 | 19602.118 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19602.12 | 19602.12 | 1.978986 | 2.85 | 1.29 | 0.00441904 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 60.3931 | 19.60 | 0.00737354 | 42.7988 | 17743.98 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 97905.719 | 78388.729 | 5.914484 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 94397.19 | 94397.19 | 5.914484 | 26.25 | 14.84 | 0.00813830 | 10.65 | 9.13 | 0.00813830 | 35.10 | 0.00569938 | 15.77 | 20.2075 | 24.00 | 0.00875967 | 38.7699 | 66635.40 | 0.00 | 100953.94 | 72330.05 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 21094.228 | 21094.228 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21094.23 | 21094.23 | 1.774345 | 0.85 | -0.34 | 0.00404012 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 67.3584 | 19.60 | 0.00738614 | 42.8654 | 20021.86 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 112946.858 | 90431.496 | 6.823120 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 109023.07 | 109023.07 | 6.823120 | 25.93 | 14.77 | 0.00818715 | 10.66 | 9.18 | 0.00818715 | 34.97 | 0.00569918 | 15.73 | 17.5165 | 24.00 | 0.00871758 | 38.5861 | 76991.07 | 0.00 | 116463.37 | 83442.03 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 20692.451 | 20692.451 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20692.45 | 20692.45 | 2.046936 | 2.64 | 1.31 | 0.00451388 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 58.3882 | 17.60 | 0.00746905 | 49.1257 | 23487.24 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 22896.717 | 22896.717 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 22896.72 | 11666.32 | 1.0000 | 0.42061783 | 0.424691 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22896.72 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.90 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 7050.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 22379.995 | 22379.995 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 22380.00 | 20466.95 | 1.0000 | 0.73791593 | 0.745062 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22380.00 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 14458.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 35036.690 | 35036.690 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 35036.69 | 35036.69 | 1.0000 | 1.26321363 | 1.275447 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35036.69 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 24660.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 16271.024 | 16271.024 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16271.02 | 16271.02 | 1.0000 | 0.58663588 | 0.592317 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16271.02 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00775014 | 21.00 | 0.00775014 | 41.2277 | 11423.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10643.400 | 10643.400 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10643.40 | 10643.40 | 1.0000 | 0.38373739 | 0.387454 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10643.40 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00774582 | 21.00 | 0.00774582 | 41.2051 | 7471.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 16147.184 | 16147.184 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16147.18 | 16147.18 | 1.0000 | 0.58217095 | 0.587809 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16147.18 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00774824 | 21.00 | 0.00774824 | 41.2177 | 11336.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10643.223 | 10643.223 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10643.22 | 10643.22 | 1.0000 | 0.38373101 | 0.387447 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10643.22 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00774582 | 21.00 | 0.00774582 | 41.2051 | 7471.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 12161.347 | 12161.347 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12161.35 | 12161.35 | 1.0000 | 0.43846548 | 0.442712 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12161.35 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00779894 | 21.00 | 0.00779894 | 41.4831 | 8543.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8034.464 | 8034.464 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8034.46 | 8034.46 | 1.0000 | 0.28967474 | 0.292480 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8034.46 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00780282 | 21.00 | 0.00780282 | 41.5035 | 5643.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 12051.136 | 12051.136 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12051.14 | 12051.14 | 1.0000 | 0.43449195 | 0.438700 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12051.14 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00779582 | 21.00 | 0.00779582 | 41.4667 | 8466.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8034.391 | 8034.391 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8034.39 | 8034.39 | 1.0000 | 0.28967211 | 0.292477 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8034.39 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00780282 | 21.00 | 0.00780282 | 41.5035 | 5643.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 12882.607 | 12882.607 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12882.61 | 12882.61 | 1.0000 | 0.46446982 | 0.468968 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12882.61 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00772928 | 21.00 | 0.00772928 | 41.1178 | 9049.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8477.605 | 8477.605 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8477.60 | 8477.60 | 1.0000 | 0.30565177 | 0.308612 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8477.60 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00772842 | 21.00 | 0.00772842 | 41.1134 | 5954.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 12767.770 | 12767.770 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12767.77 | 12767.77 | 1.0000 | 0.46032946 | 0.464787 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12767.77 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00772628 | 21.00 | 0.00772628 | 41.1021 | 8968.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8477.519 | 8477.519 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8477.52 | 8477.52 | 1.0000 | 0.30564868 | 0.308609 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8477.52 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00772842 | 21.00 | 0.00772842 | 41.1134 | 5954.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 109197.461 | 87429.521 | 6.596619 | -999.0 | -999.000 | -999.0000 | 1.05805 | 1.00000 | 1020.0712 | 1004.8586 | 0.9904 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.596619 | 6.53334972 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 105284.28 | 105284.28 | 0.9642 | 6.53334972 | 6.596619 | 26.01 | 14.81 | 0.00819343 | 47025.3 | 10.65 | 9.18 | 0.00819343 | 31352.2 | -999.0 | -999.00 | -999.00 | -999.00 | 14346.909 | 90937.37 | 35.10 | 0.00569938 | 15.77 | 1.19517000 | 18.1179 | 24.00 | 0.00874590 | 24.00 | 0.00874590 | 38.7101 | 74608.15 | 0.00 | 112597.24 | 80672.07 | 6.27533180 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.09 | 13.30 | 0.00919000 | 37379.6 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19602.118 | 19602.118 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.596619 | 6.53334972 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19602.12 | 19602.12 | 1.0000 | 1.96000492 | 1.978986 | 2.85 | 1.29 | 0.00441904 | 13936.2 | 12.80 | 9.86 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19602.12 | -7.90 | 0.00234317 | -7.90 | 1.19517000 | 60.3931 | 19.23 | 0.00758436 | 19.60 | 0.00737354 | 42.7988 | 17743.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 97905.719 | 78388.729 | 5.914484 | -999.0 | -999.000 | -999.0000 | 1.04252 | 1.00000 | 1019.9687 | 1004.8586 | 0.9904 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.914484 | 5.85775805 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 94397.19 | 94397.19 | 0.9642 | 5.85775805 | 5.914484 | 26.25 | 14.84 | 0.00813830 | 47130.6 | 10.65 | 9.13 | 0.00813830 | 31213.0 | -999.0 | -999.00 | -999.00 | -999.00 | 12863.343 | 81533.84 | 35.10 | 0.00569938 | 15.77 | 1.19517000 | 20.2075 | 24.00 | 0.00875967 | 24.00 | 0.00875967 | 38.7699 | 66635.40 | 0.00 | 100953.94 | 72330.05 | 5.62642089 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.09 | 13.30 | 0.00919000 | 37379.6 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 21094.228 | 21094.228 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.914484 | 5.85775805 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21094.23 | 21094.23 | 1.0000 | 1.75732742 | 1.774345 | 0.85 | -0.34 | 0.00404012 | 10969.1 | 12.80 | 9.86 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21094.23 | -7.90 | 0.00234317 | -7.90 | 1.19517000 | 67.3584 | 18.92 | 0.00754189 | 19.60 | 0.00738614 | 42.8654 | 20021.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 112946.858 | 90431.496 | 6.823120 | -999.0 | -999.000 | -999.0000 | 1.06591 | 1.00000 | 1020.0595 | 1004.8586 | 0.9904 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.823120 | 6.75767845 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 109023.07 | 109023.07 | 0.9653 | 6.75767845 | 6.823120 | 25.93 | 14.77 | 0.00818715 | 46921.8 | 10.66 | 9.18 | 0.00818715 | 31350.5 | -999.0 | -999.00 | -999.00 | -999.00 | 14744.398 | 94278.68 | 34.97 | 0.00569918 | 15.73 | 1.19517000 | 17.5165 | 24.00 | 0.00871758 | 24.00 | 0.00871758 | 38.5861 | 76991.07 | 0.00 | 116463.37 | 83442.03 | 6.49080123 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.09 | 13.30 | 0.00919000 | 37379.6 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20692.451 | 20692.451 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.823120 | 6.75767845 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20692.45 | 20692.45 | 1.0000 | 2.02730353 | 2.046936 | 2.64 | 1.31 | 0.00451388 | 13966.4 | 12.80 | 9.86 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20692.45 | -7.90 | 0.00234317 | -7.90 | 1.19517000 | 58.3882 | 17.44 | 0.00755974 | 17.60 | 0.00746905 | 49.1257 | 23487.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 6.60 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.91 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 6.82 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2091.00 | 2267.67 | 8.67 |
CORE_MID | 1798.00 | 3157.33 | 33.67 |
CORE_TOP | 2104.67 | 3388.33 | 456.83 |
PERIMETER_TOP_ZN_3 | 3153.00 | 3702.17 | 1553.83 |
PERIMETER_TOP_ZN_2 | 3107.33 | 3262.33 | 1178.83 |
PERIMETER_TOP_ZN_1 | 3013.67 | 2674.00 | 860.83 |
PERIMETER_TOP_ZN_4 | 3109.83 | 3494.00 | 1362.17 |
PERIMETER_BOT_ZN_3 | 2783.17 | 3677.67 | 1121.33 |
PERIMETER_BOT_ZN_2 | 2772.00 | 3021.50 | 656.50 |
PERIMETER_BOT_ZN_1 | 2484.00 | 2546.33 | 339.33 |
PERIMETER_BOT_ZN_4 | 2697.17 | 3178.17 | 694.50 |
PERIMETER_MID_ZN_3 | 2704.33 | 3495.33 | 974.00 |
PERIMETER_MID_ZN_2 | 2419.00 | 2751.00 | 776.50 |
PERIMETER_MID_ZN_1 | 2841.33 | 2374.50 | 517.17 |
PERIMETER_MID_ZN_4 | 2800.67 | 3227.33 | 889.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4715.33 | 4263.33 | 1880.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7.67 | 16.00 | 0.33 | 11.33 |
PERIMETER_TOP_ZN_2 | 8.17 | 53.17 | 0.17 | 50.33 |
PERIMETER_TOP_ZN_1 | 3.33 | 65.67 | 0.17 | 61.83 |
PERIMETER_TOP_ZN_4 | 6.00 | 40.83 | 0.17 | 27.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 1.67 | 0.00 | 1.17 |
PERIMETER_BOT_ZN_2 | 0.00 | 48.33 | 0.00 | 46.00 |
PERIMETER_BOT_ZN_1 | 81.67 | 78.67 | 81.67 | 76.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 33.83 | 0.00 | 20.67 |
PERIMETER_MID_ZN_3 | 0.33 | 9.67 | 0.00 | 6.33 |
PERIMETER_MID_ZN_2 | 0.33 | 51.33 | 0.00 | 50.17 |
PERIMETER_MID_ZN_1 | 0.17 | 88.67 | 0.00 | 86.33 |
PERIMETER_MID_ZN_4 | 0.33 | 39.50 | 0.00 | 26.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 90.83 | 276.83 | 82.00 | 249.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.96 | 52.94 | 2698.04 | 1.226 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.96 | 52.94 | 2698.04 | 0.823 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.96 | 52.94 | 2698.04 | 0.809 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.63 | 11.16 | 568.77 | 0.926 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 1.863 | 0.088 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.63 | 11.16 | 568.77 | 1.689 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 1.737 | 0.088 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.63 | 11.16 | 568.77 | 0.790 | 0.044 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 1.622 | 0.047 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.63 | 11.16 | 568.77 | 1.341 | 0.850 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 1.407 | 0.047 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.63 | 11.16 | 568.77 | 0.877 | 0.069 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 1.722 | 0.079 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.63 | 11.16 | 568.77 | 1.649 | 0.069 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 1.635 | 0.073 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.57 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.86 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 19527576.98 | 0.00 | 19527576.98 | 0.00 | 19527576.98 | 13393058.27 | 5243.50 | 43.14 | 3473.36 | 57.25 |
CORE_MID | 13122621.04 | 0.00 | 13122621.04 | 0.00 | 13122621.04 | 13393058.27 | 5940.84 | 37.93 | 2781.24 | 44.29 |
CORE_TOP | 12954723.78 | 0.00 | 12954723.78 | 0.00 | 12954723.78 | 13393058.27 | 5926.14 | 31.90 | 2801.96 | 90.26 |
PERIMETER_TOP_ZN_3 | 3125953.52 | 0.00 | 3125953.52 | 559603.69 | 3685557.21 | 2823374.22 | 4226.82 | 719.76 | 3813.43 | 90.26 |
PERIMETER_TOP_ZN_2 | 3972938.18 | 0.00 | 3972938.18 | 373066.89 | 4346005.07 | 1787429.43 | 3928.81 | 1.68 | 4829.51 | 90.26 |
PERIMETER_TOP_ZN_1 | 5676876.71 | 0.00 | 5676876.71 | 559603.69 | 6236480.40 | 2823374.22 | 3979.29 | 7.46 | 4773.25 | 90.26 |
PERIMETER_TOP_ZN_4 | 3721533.92 | 0.00 | 3721533.92 | 373066.89 | 4094600.81 | 1787312.18 | 3951.55 | 13.38 | 4795.08 | 90.26 |
PERIMETER_BOT_ZN_3 | 2668972.85 | 0.00 | 2668972.85 | 297538.75 | 2966511.61 | 2823374.22 | 5622.56 | 85.02 | 3052.42 | 57.25 |
PERIMETER_BOT_ZN_2 | 3458876.25 | 0.00 | 3458876.25 | 198357.98 | 3657234.22 | 1787429.43 | 3894.52 | 7.32 | 4858.16 | 57.25 |
PERIMETER_BOT_ZN_1 | 4512922.28 | 0.00 | 4512922.28 | 2993046.37 | 7505968.65 | 2823374.22 | 4311.79 | 46.64 | 4401.57 | 57.25 |
PERIMETER_BOT_ZN_4 | 3012898.67 | 0.00 | 3012898.67 | 198357.98 | 3211256.64 | 1787312.18 | 4001.41 | 33.42 | 4725.18 | 57.25 |
PERIMETER_MID_ZN_3 | 2948644.95 | 0.00 | 2948644.95 | 465827.44 | 3414472.40 | 2823374.22 | 5114.25 | 60.06 | 3585.68 | 44.29 |
PERIMETER_MID_ZN_2 | 3919258.68 | 0.00 | 3919258.68 | 310549.76 | 4229808.44 | 1787429.43 | 3875.85 | 6.67 | 4877.47 | 953.29 |
PERIMETER_MID_ZN_1 | 5529543.15 | 0.00 | 5529543.15 | 465827.44 | 5995370.59 | 2823374.22 | 3968.77 | 6.92 | 4784.31 | 44.29 |
PERIMETER_MID_ZN_4 | 3491279.83 | 0.00 | 3491279.83 | 310549.76 | 3801829.59 | 1787312.18 | 3894.41 | 15.03 | 4850.57 | 44.29 |
Total Facility | 91644620.78 | 0.00 | 91644620.78 | 7105396.64 | 98750017.43 | 67843644.98 | 6210.39 | 983.30 | 5053.31 | 1034.29 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.9048 | 0.0000 | 0.9048 | 0.0000 | 0.9048 | 0.4247 | 2482.92 | 43.14 | 3416.94 |
CORE_MID | 0.6076 | 0.0000 | 0.6076 | 0.0000 | 0.6076 | 0.4247 | 3165.46 | 37.93 | 2739.61 |
CORE_TOP | 0.5980 | 0.0000 | 0.5980 | 0.0000 | 0.5980 | 0.4247 | 3159.66 | 31.90 | 2751.44 |
PERIMETER_TOP_ZN_3 | 0.1444 | 0.0000 | 0.1444 | 0.0130 | 0.1574 | 0.0895 | 1460.34 | 719.76 | 3762.90 |
PERIMETER_TOP_ZN_2 | 0.1838 | 0.0000 | 0.1838 | 0.0087 | 0.1925 | 0.0567 | 1162.34 | 1.68 | 4778.98 |
PERIMETER_TOP_ZN_1 | 0.2632 | 0.0000 | 0.2632 | 0.0130 | 0.2762 | 0.0895 | 1212.81 | 7.46 | 4722.72 |
PERIMETER_TOP_ZN_4 | 0.1716 | 0.0000 | 0.1716 | 0.0087 | 0.1802 | 0.0567 | 1185.08 | 13.38 | 4744.55 |
PERIMETER_BOT_ZN_3 | 0.1231 | 0.0000 | 0.1231 | 0.0069 | 0.1300 | 0.0895 | 2861.98 | 85.02 | 2996.00 |
PERIMETER_BOT_ZN_2 | 0.1600 | 0.0000 | 0.1600 | 0.0046 | 0.1646 | 0.0567 | 1133.94 | 7.32 | 4801.74 |
PERIMETER_BOT_ZN_1 | 0.2090 | 0.0000 | 0.2090 | 0.1329 | 0.3419 | 0.0895 | 1551.21 | 46.64 | 4345.15 |
PERIMETER_BOT_ZN_4 | 0.1389 | 0.0000 | 0.1389 | 0.0046 | 0.1435 | 0.0567 | 1240.83 | 33.42 | 4668.76 |
PERIMETER_MID_ZN_3 | 0.1366 | 0.0000 | 0.1366 | 0.0108 | 0.1474 | 0.0895 | 2338.88 | 60.06 | 3544.05 |
PERIMETER_MID_ZN_2 | 0.1699 | 0.0000 | 0.1699 | 0.0078 | 0.1776 | 0.0567 | 1100.53 | 6.67 | 3926.80 |
PERIMETER_MID_ZN_1 | 0.2569 | 0.0000 | 0.2569 | 0.0108 | 0.2678 | 0.0895 | 1193.40 | 6.92 | 4742.68 |
PERIMETER_MID_ZN_4 | 0.1614 | 0.0000 | 0.1614 | 0.0072 | 0.1686 | 0.0567 | 1119.09 | 15.03 | 4808.89 |
Total Facility | 4.2291 | 0.0000 | 4.2291 | 0.2289 | 4.4580 | 2.1513 | 3416.13 | 983.30 | 4969.56 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 32547773.95 | 0.00 | 32547773.95 | 22614548.33 | 3944.27 | 216.69 | 4599.04 | 57.25 |
PACU_VAV_MID | 28457545.24 | 0.00 | 28457545.24 | 22614548.33 | 3954.22 | 7.49 | 4798.30 | 44.29 |
PACU_VAV_TOP | 28889778.01 | 0.00 | 28889778.01 | 22614548.33 | 3962.82 | 6.15 | 4791.03 | 90.18 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.5064 | 0.0000 | 1.5064 | 0.7171 | 1183.68 | 216.69 | 4542.62 |
PACU_VAV_MID | 1.3186 | 0.0000 | 1.3186 | 0.7171 | 1178.85 | 7.49 | 4756.67 |
PACU_VAV_TOP | 1.3350 | 0.0000 | 1.3350 | 0.7171 | 1196.34 | 6.15 | 4740.50 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.04 | 3470.91 | 0.00 | 0.00 | 0.00 | 1468.92 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 3194.02 | 0.00 | 0.00 | 0.00 | 1745.82 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 3243.01 | 0.00 | 0.00 | 0.00 | 1740.10 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.2963 | 0.0000 | 0.0000 | 0.0000 | 0.7594 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.0562 | 0.0000 | 0.0000 | 0.0000 | 0.7802 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.0902 | 0.0000 | 0.0000 | 0.0000 | 0.7733 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 829 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1641.40 | 13165.59 | 26-MAR-17:10 | 189289.74 | 28-JUN-14:50 |
Electricity:Building | 1067.54 | 12913.45 | 09-APR-17:10 | 82128.26 | 16-FEB-08:10 |
Electricity:Zone:CORE_BOTTOM | 322.66 | 4214.70 | 01-JAN-00:10 | 25737.69 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1067.54 | 12913.45 | 09-APR-17:10 | 82128.26 | 16-FEB-08:10 |
InteriorLights:Electricity | 362.11 | 1672.11 | 01-JAN-09:30 | 38257.79 | 09-NOV-16:50 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 362.11 | 1672.11 | 01-JAN-09:30 | 38257.79 | 09-NOV-16:50 |
LightsWired:InteriorLights:Electricity | 362.11 | 1672.11 | 01-JAN-09:30 | 38257.79 | 09-NOV-16:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 362.11 | 1672.11 | 01-JAN-09:30 | 38257.79 | 09-NOV-16:50 |
Electricity:Zone:CORE_MID | 201.92 | 2251.11 | 01-JAN-00:10 | 14360.82 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 201.92 | 2251.11 | 01-JAN-00:10 | 14360.82 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 34.90 | 428.29 | 26-MAR-17:10 | 3027.38 | 04-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.56 | 42.19 | 01-JAN-09:30 | 1592.13 | 04-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.56 | 42.19 | 01-JAN-09:30 | 1592.13 | 04-JAN-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.06 | 271.13 | 09-APR-17:10 | 1916.52 | 04-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.66 | 26.71 | 01-JAN-07:40 | 1007.95 | 04-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.66 | 26.71 | 01-JAN-07:40 | 1007.95 | 04-JAN-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 34.73 | 428.29 | 12-MAR-17:10 | 3027.37 | 08-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.40 | 42.19 | 01-JAN-07:40 | 1592.13 | 08-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.40 | 42.19 | 01-JAN-07:40 | 1592.13 | 08-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 22.00 | 271.13 | 12-MAR-17:10 | 1916.45 | 09-NOV-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.60 | 26.71 | 01-JAN-09:20 | 1007.89 | 09-NOV-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.60 | 26.71 | 01-JAN-09:20 | 1007.89 | 09-NOV-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 34.88 | 428.29 | 26-MAR-17:10 | 3027.38 | 04-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.54 | 42.19 | 01-JAN-09:20 | 1592.13 | 04-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.54 | 42.19 | 01-JAN-09:20 | 1592.13 | 04-JAN-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.05 | 271.13 | 09-APR-17:10 | 1916.52 | 04-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.65 | 26.71 | 01-JAN-07:40 | 1007.95 | 04-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.65 | 26.71 | 01-JAN-07:40 | 1007.95 | 04-JAN-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 34.72 | 428.29 | 12-MAR-17:10 | 3027.37 | 08-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.39 | 42.19 | 01-JAN-07:40 | 1592.13 | 08-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.39 | 42.19 | 01-JAN-07:40 | 1592.13 | 08-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 21.99 | 271.13 | 12-MAR-17:10 | 1916.45 | 09-NOV-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.59 | 26.71 | 01-JAN-09:20 | 1007.89 | 09-NOV-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.59 | 26.71 | 01-JAN-09:20 | 1007.89 | 09-NOV-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 34.90 | 428.29 | 26-MAR-17:10 | 3027.38 | 04-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 10.56 | 42.19 | 01-JAN-09:30 | 1592.13 | 04-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 10.56 | 42.19 | 01-JAN-09:30 | 1592.13 | 04-JAN-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.06 | 271.13 | 09-APR-17:10 | 1916.52 | 04-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.66 | 26.71 | 01-JAN-07:40 | 1007.95 | 04-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.66 | 26.71 | 01-JAN-07:40 | 1007.95 | 04-JAN-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 34.73 | 428.29 | 12-MAR-17:10 | 3027.37 | 08-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 10.40 | 42.19 | 01-JAN-07:40 | 1592.13 | 08-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 10.40 | 42.19 | 01-JAN-07:40 | 1592.13 | 08-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 22.00 | 271.13 | 12-MAR-17:10 | 1916.45 | 09-NOV-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.60 | 26.71 | 01-JAN-09:20 | 1007.89 | 09-NOV-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.60 | 26.71 | 01-JAN-09:20 | 1007.89 | 09-NOV-16:50 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 462.01 | 243.72 | 01-JAN-00:10 | 127567.48 | 06-FEB-07:10 |
ExteriorEquipment:Electricity | 17.11 | 243.72 | 01-JAN-00:10 | 1240.17 | 09-NOV-17:00 |
Transformer:ExteriorEquipment:Electricity | 17.11 | 243.72 | 01-JAN-00:10 | 1240.17 | 09-NOV-17:00 |
ElectricityPurchased:Facility | 1641.40 | 13165.59 | 24-JUN-18:20 | 189289.74 | 28-JUN-14:50 |
ElectricityPurchased:Plant | 1641.40 | 13165.59 | 24-JUN-18:20 | 189289.74 | 28-JUN-14:50 |
Cogeneration:ElectricityPurchased | 1641.40 | 13165.59 | 24-JUN-18:20 | 189289.74 | 28-JUN-14:50 |
General:Cogeneration:ElectricityPurchased | 1641.40 | 13165.59 | 24-JUN-18:20 | 189289.74 | 28-JUN-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1641.40 | 13165.59 | 24-JUN-18:20 | 189289.74 | 28-JUN-14:50 |
ElectricityNet:Plant | 1641.40 | 13165.59 | 24-JUN-18:20 | 189289.74 | 28-JUN-14:50 |
Cogeneration:ElectricityNet | 1641.40 | 13165.59 | 24-JUN-18:20 | 189289.74 | 28-JUN-14:50 |
General:Cogeneration:ElectricityNet | 1641.40 | 13165.59 | 24-JUN-18:20 | 189289.74 | 28-JUN-14:50 |
Heating:Electricity | 52.60 | 0.00 | 01-JAN-00:10 | 122537.87 | 06-FEB-07:10 |
General:Heating:Electricity | 52.60 | 0.00 | 01-JAN-00:10 | 122537.87 | 06-FEB-07:10 |
Fans:Electricity | 141.79 | 0.00 | 01-JAN-00:10 | 37068.67 | 05-JUL-15:00 |
General:Fans:Electricity | 141.79 | 0.00 | 01-JAN-00:10 | 37068.67 | 05-JUL-15:00 |
ExteriorLights:Electricity | 111.69 | 0.00 | 01-JAN-07:20 | 8596.48 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 111.69 | 0.00 | 01-JAN-07:20 | 8596.48 | 01-JAN-06:10 |
Cooling:Electricity | 250.52 | 0.00 | 01-JAN-00:10 | 82663.02 | 28-JUN-15:10 |
General:Cooling:Electricity | 250.52 | 0.00 | 01-JAN-00:10 | 82663.02 | 28-JUN-15:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-06:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-06:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 10.18 | 0.00 | 01-JAN-00:10 | 1075.04 | 09-NOV-17:00 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 175.96 | 2003.43 | 02-JAN-06:10 | 60541.78 | 15-DEC-07:20 |
NaturalGas:HVAC | 43.76 | 0.00 | 01-JAN-00:10 | 51556.54 | 15-DEC-07:20 |
Heating:NaturalGas | 43.76 | 0.00 | 01-JAN-00:10 | 51556.54 | 15-DEC-07:20 |
General:Heating:NaturalGas | 43.76 | 0.00 | 01-JAN-00:10 | 51556.54 | 15-DEC-07:20 |
NaturalGas:Plant | 132.20 | 2003.43 | 02-JAN-06:10 | 10254.51 | 01-FEB-12:10 |
WaterSystems:NaturalGas | 132.20 | 2003.43 | 02-JAN-06:10 | 10254.51 | 01-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 132.20 | 2003.43 | 02-JAN-06:10 | 10254.51 | 01-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2496.77 | 0.00 | 01-JAN-00:10 | 449276.12 | 05-SEP-13:30 |
EnergyTransfer:Building | 1401.77 | 0.00 | 01-JAN-00:10 | 189117.94 | 07-AUG-15:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 272.06 | 0.00 | 01-JAN-00:10 | 28862.12 | 05-SEP-08:00 |
Heating:EnergyTransfer | 46.08 | 0.00 | 01-JAN-00:10 | 107269.26 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 46.08 | 0.00 | 01-JAN-00:10 | 107269.26 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1355.69 | 0.00 | 01-JAN-00:10 | 189117.94 | 07-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 272.06 | 0.00 | 01-JAN-00:10 | 28862.12 | 05-SEP-08:00 |
General:Cooling:EnergyTransfer | 1355.69 | 0.00 | 01-JAN-00:10 | 189117.94 | 07-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 272.06 | 0.00 | 01-JAN-00:10 | 28862.12 | 05-SEP-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 60.81 | 0.00 | 01-JAN-00:10 | 13009.68 | 28-JUN-14:40 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 11.59 | 0.00 | 01-JAN-00:10 | 10684.46 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 11.59 | 0.00 | 01-JAN-00:10 | 10684.46 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 49.22 | 0.00 | 01-JAN-00:10 | 13009.68 | 28-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 49.22 | 0.00 | 01-JAN-00:10 | 13009.68 | 28-JUN-14:40 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 31.54 | 0.00 | 01-JAN-00:10 | 6428.09 | 07-AUG-15:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.61 | 0.00 | 01-JAN-00:10 | 4033.41 | 26-DEC-10:40 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.61 | 0.00 | 01-JAN-00:10 | 4033.41 | 26-DEC-10:40 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 25.93 | 0.00 | 01-JAN-00:10 | 6428.09 | 07-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 25.93 | 0.00 | 01-JAN-00:10 | 6428.09 | 07-AUG-15:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 34.76 | 0.00 | 01-JAN-00:10 | 6888.28 | 05-JUL-12:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 2.43 | 0.00 | 01-JAN-00:10 | 3333.86 | 17-JAN-08:40 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 2.43 | 0.00 | 01-JAN-00:10 | 3333.86 | 17-JAN-08:40 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 32.33 | 0.00 | 01-JAN-00:10 | 6888.28 | 05-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 32.33 | 0.00 | 01-JAN-00:10 | 6888.28 | 05-JUL-12:10 |
EnergyTransfer:Zone:CORE_MID | 179.80 | 0.00 | 01-JAN-00:10 | 21179.00 | 05-JUL-07:30 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.03 | 0.00 | 01-JAN-00:10 | 6749.66 | 26-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.03 | 0.00 | 01-JAN-00:10 | 6749.66 | 26-DEC-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 179.78 | 0.00 | 01-JAN-00:10 | 21179.00 | 05-JUL-07:30 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 179.78 | 0.00 | 01-JAN-00:10 | 21179.00 | 05-JUL-07:30 |
EnergyTransfer:Zone:CORE_TOP | 173.06 | 0.00 | 01-JAN-00:10 | 22901.06 | 07-AUG-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 1.17 | 0.00 | 01-JAN-00:10 | 17112.43 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 1.17 | 0.00 | 01-JAN-00:10 | 17112.43 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 171.89 | 0.00 | 01-JAN-00:10 | 22901.06 | 07-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 171.89 | 0.00 | 01-JAN-00:10 | 22901.06 | 07-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.73 | 0.00 | 01-JAN-00:10 | 9836.72 | 06-FEB-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 5.33 | 0.00 | 01-JAN-00:10 | 9836.72 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 5.33 | 0.00 | 01-JAN-00:10 | 9836.72 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 40.40 | 0.00 | 01-JAN-00:10 | 8366.79 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 40.40 | 0.00 | 01-JAN-00:10 | 8366.79 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 51.70 | 0.00 | 01-JAN-00:10 | 11024.73 | 05-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 2.34 | 0.00 | 01-JAN-00:10 | 6690.30 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 2.34 | 0.00 | 01-JAN-00:10 | 6690.30 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.36 | 0.00 | 01-JAN-00:10 | 11024.73 | 05-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.36 | 0.00 | 01-JAN-00:10 | 11024.73 | 05-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 79.05 | 0.00 | 01-JAN-00:10 | 14302.06 | 28-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 2.69 | 0.00 | 01-JAN-00:10 | 9607.20 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 2.69 | 0.00 | 01-JAN-00:10 | 9607.20 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 76.36 | 0.00 | 01-JAN-00:10 | 14302.06 | 28-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 76.36 | 0.00 | 01-JAN-00:10 | 14302.06 | 28-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 50.18 | 0.00 | 01-JAN-00:10 | 12120.77 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 2.99 | 0.00 | 01-JAN-00:10 | 6569.25 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 2.99 | 0.00 | 01-JAN-00:10 | 6569.25 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 47.19 | 0.00 | 01-JAN-00:10 | 12120.77 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 47.19 | 0.00 | 01-JAN-00:10 | 12120.77 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.96 | 0.00 | 01-JAN-00:10 | 6908.73 | 07-AUG-14:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 1.47 | 0.00 | 01-JAN-00:10 | 5668.24 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 1.47 | 0.00 | 01-JAN-00:10 | 5668.24 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 36.49 | 0.00 | 01-JAN-00:10 | 6908.73 | 07-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 36.49 | 0.00 | 01-JAN-00:10 | 6908.73 | 07-AUG-14:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 47.69 | 0.00 | 01-JAN-00:10 | 9271.03 | 05-JUL-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.38 | 0.00 | 01-JAN-00:10 | 3095.05 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.38 | 0.00 | 01-JAN-00:10 | 3095.05 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 47.31 | 0.00 | 01-JAN-00:10 | 9271.03 | 05-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 47.31 | 0.00 | 01-JAN-00:10 | 9271.03 | 05-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 71.79 | 0.00 | 01-JAN-00:10 | 12008.32 | 29-JUN-16:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 6.10 | 0.00 | 01-JAN-00:10 | 11189.47 | 22-DEC-07:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 6.10 | 0.00 | 01-JAN-00:10 | 11189.47 | 22-DEC-07:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 65.69 | 0.00 | 01-JAN-00:10 | 12008.32 | 29-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 65.69 | 0.00 | 01-JAN-00:10 | 12008.32 | 29-JUN-16:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 43.71 | 0.00 | 01-JAN-00:10 | 9403.11 | 21-JUL-17:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.44 | 0.00 | 01-JAN-00:10 | 3099.12 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.44 | 0.00 | 01-JAN-00:10 | 3099.12 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 43.27 | 0.00 | 01-JAN-00:10 | 9403.11 | 21-JUL-17:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 43.27 | 0.00 | 01-JAN-00:10 | 9403.11 | 21-JUL-17:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 42.38 | 0.00 | 01-JAN-00:10 | 7609.35 | 31-JUL-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1.44 | 0.00 | 01-JAN-00:10 | 6200.17 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1.44 | 0.00 | 01-JAN-00:10 | 6200.17 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 40.94 | 0.00 | 01-JAN-00:10 | 7609.35 | 31-JUL-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 40.94 | 0.00 | 01-JAN-00:10 | 7609.35 | 31-JUL-12:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 51.32 | 0.00 | 01-JAN-00:10 | 10898.22 | 05-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.66 | 0.00 | 01-JAN-00:10 | 4037.28 | 17-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.66 | 0.00 | 01-JAN-00:10 | 4037.28 | 17-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 50.66 | 0.00 | 01-JAN-00:10 | 10898.22 | 05-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 50.66 | 0.00 | 01-JAN-00:10 | 10898.22 | 05-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 79.37 | 0.00 | 01-JAN-00:10 | 13213.60 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.61 | 0.00 | 01-JAN-00:10 | 5601.26 | 17-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.61 | 0.00 | 01-JAN-00:10 | 5601.26 | 17-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 78.75 | 0.00 | 01-JAN-00:10 | 13213.60 | 28-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 78.75 | 0.00 | 01-JAN-00:10 | 13213.60 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 48.87 | 0.00 | 01-JAN-00:10 | 11458.70 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.80 | 0.00 | 01-JAN-00:10 | 3936.15 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.80 | 0.00 | 01-JAN-00:10 | 3936.15 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 48.07 | 0.00 | 01-JAN-00:10 | 11458.70 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 48.07 | 0.00 | 01-JAN-00:10 | 11458.70 | 28-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 47.58 | 0.00 | 01-JAN-00:10 | 6171.54 | 07-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 47.58 | 0.00 | 01-JAN-00:10 | 6171.54 | 07-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 47.58 | 0.00 | 01-JAN-00:10 | 6171.54 | 07-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 47.58 | 0.00 | 01-JAN-00:10 | 6171.54 | 07-FEB-12:10 |
EnergyTransfer:HVAC | 1047.42 | 0.00 | 01-JAN-00:10 | 278620.03 | 05-SEP-13:00 |
HeatingCoils:EnergyTransfer | 87.60 | 0.00 | 01-JAN-00:10 | 157385.75 | 06-FEB-07:10 |
CoolingCoils:EnergyTransfer | 959.81 | 0.00 | 01-JAN-00:10 | 278620.03 | 05-SEP-13:00 |
EnergyTransfer:Plant | 47.58 | 0.00 | 01-JAN-00:10 | 6171.54 | 07-FEB-12:10 |
WaterSystems:EnergyTransfer | 47.58 | 0.00 | 01-JAN-00:10 | 6171.54 | 07-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 47.58 | 0.00 | 01-JAN-00:10 | 6171.54 | 07-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -272.055 | 0.000 | 0.000 | 32.721 | 86.497 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -83.331 |
CORE_MID | 0.000 | 0.000 | 0.027 | -179.774 | 0.000 | 0.000 | 33.257 | 86.497 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -55.432 |
CORE_TOP | 0.000 | 0.000 | 1.173 | -171.884 | 0.000 | 0.000 | 33.908 | 86.497 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -65.119 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 5.332 | -40.398 | 0.000 | 0.000 | 7.398 | 10.564 | 24.333 | 25.052 | 0.000 | 0.233 | 4.438 | 0.000 | -31.641 | 0.000 | -5.311 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 2.343 | -49.361 | 0.000 | 0.000 | 4.591 | 6.660 | 15.404 | 58.392 | 0.000 | 0.157 | 0.000 | 0.000 | -19.967 | 0.000 | -3.650 | -14.569 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 2.690 | -76.360 | 0.000 | 0.000 | 7.111 | 10.402 | 24.332 | 104.138 | 0.000 | 0.231 | 0.002 | 0.000 | -30.882 | 0.000 | -5.724 | -35.937 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 2.991 | -47.186 | 0.000 | 0.000 | 4.686 | 6.597 | 15.403 | 54.123 | 0.000 | 0.154 | 0.000 | 0.000 | -21.259 | 0.000 | -3.663 | -11.846 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 1.471 | -36.489 | 0.000 | 0.000 | 7.354 | 10.544 | 24.333 | 25.310 | 0.000 | 0.135 | 3.304 | 0.000 | -32.978 | 0.000 | -2.983 | -0.001 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.382 | -47.308 | 0.000 | 0.000 | 4.530 | 6.651 | 15.404 | 58.437 | 0.000 | 0.084 | 0.001 | 0.000 | -21.541 | 0.000 | -2.123 | -14.515 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 6.095 | -65.691 | 0.000 | 0.000 | 7.124 | 10.390 | 24.332 | 104.585 | 0.000 | 3.237 | 0.003 | 0.000 | -33.733 | 0.000 | -26.892 | -29.448 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.440 | -43.265 | 0.000 | 0.000 | 4.605 | 6.588 | 15.403 | 54.280 | 0.000 | 0.083 | 0.001 | 0.000 | -22.888 | 0.000 | -2.128 | -13.118 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 1.438 | -40.940 | 0.000 | 0.000 | 7.289 | 10.564 | 24.333 | 24.746 | 0.000 | 0.197 | 10.681 | 0.000 | -33.585 | 0.000 | -4.723 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.660 | -50.662 | 0.000 | 0.000 | 3.368 | 6.660 | 15.404 | 58.177 | 0.000 | 0.134 | 0.003 | 0.000 | -21.036 | 0.000 | -3.219 | -9.485 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.613 | -78.753 | 0.000 | 0.000 | 7.027 | 10.402 | 24.332 | 103.849 | 0.000 | 0.195 | 0.004 | 0.000 | -32.614 | 0.000 | -5.053 | -29.999 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.803 | -48.064 | 0.000 | 0.000 | 4.630 | 6.597 | 15.403 | 53.980 | 0.000 | 0.129 | 0.001 | 0.000 | -22.478 | 0.000 | -3.242 | -7.758 |
TOPFLOOR_PLENUM | 11.588 | -49.222 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.242 | 45.751 | 0.000 | 0.000 | 0.000 | -8.359 | -0.000 |
MIDFLOOR_PLENUM | 5.607 | -25.930 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.288 | 28.396 | 0.000 | 0.000 | 0.000 | -8.361 | -0.000 |
FIRSTFLOOR_PLENUM | 2.431 | -32.325 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.223 | 36.434 | 0.000 | 0.000 | 0.000 | -6.762 | 0.000 |
Total Facility | 19.626 | -107.477 | 26.457 | -1248.188 | 0.000 | 0.000 | 169.599 | 362.109 | 705.434 | 725.068 | 0.000 | 5.720 | 129.018 | 0.000 | -324.602 | 0.000 | -92.191 | -370.560 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 29-JUN-04:02 | 0.00 | 0.00 | 0.00 | -46924.95 | 0.00 | 0.00 | 0.00 | 839.14 | 4405.64 | 0.00 | 0.00 | 0.00 | 41680.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 29-JUN-04:02 | 0.00 | 0.00 | 0.00 | -35388.55 | 0.00 | 0.00 | 0.00 | 839.14 | 2442.06 | 0.00 | 0.00 | 0.00 | 32107.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-05:12 | 0.00 | 0.00 | 0.00 | -36512.51 | 0.00 | 0.00 | 324.35 | 839.14 | 3025.92 | 0.00 | 0.00 | 0.00 | 32323.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-JUL-18:21 | 0.00 | 0.00 | 0.00 | -13614.34 | 0.00 | 0.00 | 0.00 | 42.19 | 386.10 | 4566.21 | 0.00 | 269.42 | 8350.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-09:01 | 0.00 | 0.00 | 0.00 | -16352.22 | 0.00 | 0.00 | 10.66 | 26.71 | 302.86 | 12144.97 | 0.00 | 0.00 | 3882.30 | 0.00 | -0.00 | 0.00 | -15.27 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-12:32 | 0.00 | 0.00 | 0.00 | -18195.79 | 0.00 | 0.00 | 18.17 | 42.19 | 478.41 | 17568.64 | 0.00 | 0.00 | 105.45 | 0.00 | -0.00 | 0.00 | -17.06 | 0.00 |
PERIMETER_TOP_ZN_4 | 24-SEP-16:21 | 0.00 | 0.00 | 0.00 | -18890.98 | 0.00 | 0.00 | 12.27 | 26.71 | 302.86 | 12417.79 | 0.00 | 0.00 | 6183.77 | 0.00 | -0.00 | 0.00 | -52.42 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-JUL-18:11 | 0.00 | 0.00 | 0.00 | -11383.07 | 0.00 | 0.00 | 0.00 | 42.19 | 386.10 | 4706.46 | 0.00 | 145.79 | 6102.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-09:31 | 0.00 | 0.00 | 0.00 | -14555.37 | 0.00 | 0.00 | 13.14 | 26.71 | 302.86 | 10823.41 | 0.00 | 0.00 | 3398.39 | 0.00 | -0.00 | 0.00 | -9.13 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-OCT-14:51 | 0.00 | 0.00 | 0.00 | -15509.13 | 0.00 | 0.00 | 21.40 | 42.19 | 478.41 | 10481.54 | 0.00 | 0.00 | 4488.71 | 0.00 | -0.00 | 0.00 | -3.12 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-JUL-17:31 | 0.00 | 0.00 | 0.00 | -15859.92 | 0.00 | 0.00 | 0.00 | 26.71 | 244.42 | 13076.19 | 0.00 | 91.23 | 2421.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUL-18:12 | 0.00 | 0.00 | 0.00 | -12681.80 | 0.00 | 0.00 | 0.00 | 42.19 | 386.10 | 4635.65 | 0.00 | 250.20 | 7367.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-08:51 | 0.00 | 0.00 | 0.00 | -17841.59 | 0.00 | 0.00 | 10.85 | 26.71 | 302.86 | 12546.30 | 0.00 | 0.00 | 4988.71 | 0.00 | -0.00 | 0.00 | -33.84 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-13:01 | 0.00 | 0.00 | 0.00 | -18046.46 | 0.00 | 0.00 | 18.70 | 42.19 | 478.41 | 16806.19 | 0.00 | 0.00 | 723.50 | 0.00 | -0.00 | 0.00 | -22.53 | 0.00 |
PERIMETER_MID_ZN_4 | 04-JUL-16:51 | 0.00 | 0.00 | 0.00 | -19070.62 | 0.00 | 0.00 | 8.71 | 26.71 | 302.86 | 14432.22 | 0.00 | 191.80 | 4108.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-14:40 | 0.00 | -13007.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.95 | 12889.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 07-AUG-15:30 | 0.00 | -6428.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.75 | 6340.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 05-JUL-12:10 | 0.00 | -6887.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.05 | 6841.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-JUL-06:03 | 0.00 | -10030.37 | 0.00 | -194213.50 | 0.00 | 0.00 | 3486.40 | 10153.98 | 21098.80 | 40911.21 | 0.00 | 0.00 | 129864.82 | 0.00 | 0.00 | 0.00 | -1271.34 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 06-FEB-07:01 | 0.00 | 0.00 | 16194.79 | 0.00 | 0.00 | 0.00 | 916.94 | 2517.53 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22655.18 |
CORE_TOP | 06-FEB-06:01 | 0.00 | 0.00 | 31428.62 | 0.00 | 0.00 | 0.00 | 500.87 | 839.14 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -35794.56 |
PERIMETER_TOP_ZN_3 | 17-JAN-05:11 | 0.00 | 0.00 | 11926.56 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2494.34 | 0.00 | -1220.11 | -8903.82 |
PERIMETER_TOP_ZN_2 | 17-JAN-05:11 | 0.00 | 0.00 | 10614.66 | 0.00 | 0.00 | 0.00 | 0.00 | 111.99 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1661.80 | 0.00 | -823.28 | -8567.47 |
PERIMETER_TOP_ZN_1 | 17-JAN-05:11 | 0.00 | 0.00 | 14277.99 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2434.87 | 0.00 | -1234.35 | -11300.47 |
PERIMETER_TOP_ZN_4 | 17-JAN-05:11 | 0.00 | 0.00 | 10590.57 | 0.00 | 0.00 | 0.00 | 0.00 | 111.98 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1608.45 | 0.00 | -824.75 | -8595.24 |
PERIMETER_BOT_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 8970.31 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3055.76 | 0.00 | -669.73 | -5936.51 |
PERIMETER_BOT_ZN_2 | 06-FEB-06:01 | 0.00 | 0.00 | 6821.57 | 0.00 | 0.00 | 0.00 | 66.79 | 111.99 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2050.24 | 0.00 | -94.91 | -5259.01 |
PERIMETER_BOT_ZN_1 | 06-FEB-07:10 | 0.00 | 0.00 | 11468.71 | 0.00 | 0.00 | 0.00 | 193.30 | 370.35 | 637.88 | 0.00 | 0.00 | 0.00 | 5764.68 | 0.00 | -2219.71 | 0.00 | -16215.23 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-FEB-06:01 | 0.00 | 0.00 | 6746.03 | 0.00 | 0.00 | 0.00 | 66.78 | 111.98 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2102.04 | 0.00 | -94.89 | -5131.67 |
PERIMETER_MID_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 9883.65 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2995.92 | 0.00 | -1016.78 | -6562.65 |
PERIMETER_MID_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 7834.25 | 0.00 | 0.00 | 0.00 | 0.00 | 111.99 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1948.36 | 0.00 | -684.36 | -5639.41 |
PERIMETER_MID_ZN_1 | 06-FEB-05:01 | 0.00 | 0.00 | 11806.60 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3008.25 | 0.00 | -1054.18 | -8435.88 |
PERIMETER_MID_ZN_4 | 06-FEB-05:01 | 0.00 | 0.00 | 7756.62 | 0.00 | 0.00 | 0.00 | 0.00 | 111.98 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2011.16 | 0.00 | -686.47 | -5496.87 |
TOPFLOOR_PLENUM | 06-FEB-06:12 | 14535.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -367.70 | -14168.20 |
MIDFLOOR_PLENUM | 01-JAN-12:02 | 7376.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -237.10 | -7139.73 |
FIRSTFLOOR_PLENUM | 25-OCT-05:02 | 5278.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -128.70 | -5149.61 |
Total Facility | 06-FEB-07:01 | 11067.78 | 5591.02 | 142216.03 | -5591.02 | 0.00 | 0.00 | 4544.20 | 11634.72 | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22465.47 | 0.00 | -21577.28 | -146518.79 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 7.3634 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.5966 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 6.8907 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.9145 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 7.4002 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.8231 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.6817 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5720 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 3.4453 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.6260 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.7001 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.7228 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7546 | 3.7546 | 0.8335 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8387 | 2.8387 | 0.8147 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9968 | 2.9968 | 0.8421 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9742 | 0.9742 | 0.1948 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0584 | 1.0584 | 0.2117 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1769 | 1.1769 | 0.2354 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1939 | 1.1939 | 0.2388 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7974 | 0.7974 | 0.1762 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8915 | 0.8915 | 0.1783 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9716 | 0.9716 | 0.1943 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9484 | 0.9484 | 0.1897 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8528 | 0.8528 | 0.1714 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0371 | 1.0371 | 0.2074 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0586 | 1.0586 | 0.2117 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1035 | 1.1035 | 0.2207 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 7.3634 | 6.5966 | 7.3634 | 1.5720 | 0.0000 | 1.0000 |
PACU_VAV_MID | 6.8907 | 5.9145 | 6.8907 | 1.6260 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 7.4002 | 6.8231 | 7.4002 | 1.7228 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8773 | 1.8773 | 0.8335 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4193 | 1.4193 | 0.8147 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4984 | 1.4984 | 0.8421 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4871 | 0.4871 | 0.1948 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5292 | 0.5292 | 0.2117 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5884 | 0.5884 | 0.2354 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5970 | 0.5970 | 0.2388 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3987 | 0.3987 | 0.1762 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4458 | 0.4458 | 0.1783 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4858 | 0.4858 | 0.1943 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4742 | 0.4742 | 0.1897 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4264 | 0.4264 | 0.1714 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5185 | 0.5185 | 0.2074 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5293 | 0.5293 | 0.2117 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5517 | 0.5517 | 0.2207 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.6817 | 1.5720 | 1.5720 | 1.5720 | 0.0000 | 1.0000 |
PACU_VAV_MID | 3.4453 | 1.6260 | 1.6260 | 1.6260 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.7001 | 1.7228 | 1.7228 | 1.7228 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 82.00 |
Number of hours cooling loads not met | 249.50 |
Number of hours not met | 331.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 52.60 | 122537.87 | 43.76 | 51556.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 250.52 | 82663.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 362.11 | 38257.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 111.69 | 8596.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 17.11 | 1240.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 141.79 | 37068.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 132.20 | 10254.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1641.40 |
Natural Gas | 0.00 | 175.96 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1817.36 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 72.68 |
Space Heating | 10.56 |
Space Cooling | 50.28 |
Fans (All) | 28.46 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 329.45 |
Subtotal | 329.45 |
Natural Gas [MJ/m2] | |
Space Heating | 8.78 |
Service Water Heating | 26.53 |
Miscellaneous (All) | 35.32 |
Subtotal | 35.32 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.93 |
Space Heating | 5.30 |
Space Cooling | 13.78 |
Fans (All) | 7.80 |
Service Water Heating | 7.27 |
Receptacle Equipment | 38.82 |
Miscellaneous | 7.10 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8741.50 | 18.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8706.50 | 53.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8726.33 | 33.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8724.67 | 35.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8701.67 | 58.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8737.00 | 23.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8731.50 | 28.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8751.50 | 8.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8705.50 | 54.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8725.83 | 34.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8724.17 | 35.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8618.67 | 141.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8618.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 141.33 | 0.00 | 0.00 | 0.00 |
Average | 8730.01 | 29.99 | 0.00 | 0.00 | 0.00 |
Sum | 157140.17 | 539.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128300.67 | 3.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 3.33 | 0.00 | 0.00 | 0.00 |
Average | 34143.15 | 0.19 | 0.00 | 0.00 | 0.00 |
Sum | 614576.67 | 3.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8707.50 | 52.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8739.33 | 20.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8752.50 | 7.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8744.17 | 15.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8698.50 | 61.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8730.67 | 29.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8714.00 | 46.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8696.33 | 63.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8725.83 | 34.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8739.33 | 20.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8692.33 | 67.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8725.17 | 34.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8706.83 | 53.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8676.50 | 83.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
Min | 8676.50 | 4.17 | 0.00 | 0.00 | 0.00 |
Max | 8755.83 | 83.50 | 0.00 | 0.00 | 0.00 |
Average | 8725.35 | 34.65 | 0.00 | 0.00 | 0.00 |
Sum | 157056.33 | 623.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128286.67 | 17.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128296.67 | 7.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128302.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128302.00 | 17.33 | 0.00 | 0.00 | 0.00 |
Average | 34141.85 | 1.48 | 0.00 | 0.00 | 0.00 |
Sum | 614553.33 | 26.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146928E+11 | 19021.20 | 12-JAN-08:02 | -1.9 | -3.1 | 0.197478E+10 | 2608.61 | 19-JAN-14:30 | 4.70 | 1.54 |
February | 0.145390E+11 | 20764.21 | 15-FEB-17:00 | 16.70 | 5.85 | 0.179757E+10 | 2606.66 | 15-FEB-10:09 | 16.70 | 5.85 |
March | 0.202355E+11 | 20482.31 | 10-MAR-17:00 | 13.90 | 3.52 | 0.215492E+10 | 2606.65 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.222360E+11 | 37901.85 | 28-APR-06:02 | 10.97 | 3.96 | 0.191716E+10 | 2606.68 | 17-APR-13:00 | 10.97 | 3.96 |
May | 0.260476E+11 | 41759.75 | 30-MAY-06:02 | 13.77 | 10.85 | 0.207660E+10 | 2606.77 | 11-MAY-09:09 | 13.77 | 10.85 |
June | 0.284885E+11 | 46916.46 | 29-JUN-04:02 | 24.40 | 15.17 | 0.207149E+10 | 2606.71 | 08-JUN-13:09 | 24.40 | 15.17 |
July | 0.288817E+11 | 43206.29 | 24-JUL-05:12 | 22.20 | 14.92 | 0.192635E+10 | 2606.64 | 21-JUL-09:09 | 22.20 | 14.92 |
August | 0.309138E+11 | 43937.73 | 22-AUG-05:12 | 21.33 | 15.21 | 0.216203E+10 | 2606.90 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.270379E+11 | 43461.17 | 18-SEP-05:12 | 13.53 | 10.70 | 0.191985E+10 | 2606.70 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.246902E+11 | 42301.97 | 03-OCT-06:02 | 15.00 | 12.40 | 0.199366E+10 | 2606.71 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.193568E+11 | 39585.80 | 01-NOV-06:01 | 7.30 | 5.03 | 0.197002E+10 | 2606.62 | 08-NOV-10:30 | 13.60 | 6.17 |
December | 0.149368E+11 | 19270.44 | 01-DEC-16:30 | 12.50 | 4.57 | 0.190843E+10 | 2608.42 | 13-DEC-10:39 | 1.67 | -3.2 |
Annual Sum or Average | 0.272057E+12 | 0.238728E+11 | ||||||||
Minimum of Months | 0.145390E+11 | 19021.20 | -1.9 | -3.1 | 0.179757E+10 | 2606.62 | 1.67 | -3.2 | ||
Maximum of Months | 0.309138E+11 | 46916.46 | 24.40 | 15.21 | 0.216203E+10 | 2608.61 | 24.40 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.481994E+09 | 2248.68 | 08-JAN-14:10 | 12.80 | 4.25 | 0.00 | 0.00 | 01-JAN-00:10 | 12.80 | 4.25 |
February | 0.879835E+09 | 4833.66 | 14-FEB-15:40 | 22.03 | 7.70 | 0.00 | 0.00 | 01-FEB-00:10 | 22.03 | 7.70 |
March | 0.191992E+10 | 6319.78 | 08-MAR-14:50 | 22.30 | 9.20 | 0.00 | 0.00 | 01-MAR-00:10 | 22.30 | 9.20 |
April | 0.391102E+10 | 9402.53 | 28-APR-14:10 | 24.50 | 10.31 | 0.00 | 0.00 | 01-APR-00:10 | 24.50 | 10.31 |
May | 0.531686E+10 | 10752.28 | 30-MAY-14:30 | 27.20 | 12.25 | 0.00 | 0.00 | 01-MAY-00:10 | 27.20 | 12.25 |
June | 0.815721E+10 | 13009.68 | 28-JUN-14:40 | 38.13 | 14.26 | 0.00 | 0.00 | 01-JUN-00:10 | 38.13 | 14.26 |
July | 0.923612E+10 | 12856.01 | 21-JUL-14:20 | 37.80 | 15.31 | 0.00 | 0.00 | 01-JUL-00:10 | 37.80 | 15.31 |
August | 0.890390E+10 | 12965.13 | 07-AUG-14:20 | 33.13 | 15.81 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 15.81 |
September | 0.596760E+10 | 10428.00 | 12-SEP-15:00 | 28.90 | 14.53 | 0.00 | 0.00 | 01-SEP-00:10 | 28.90 | 14.53 |
October | 0.321464E+10 | 8548.53 | 05-OCT-15:30 | 26.70 | 12.13 | 0.00 | 0.00 | 01-OCT-00:10 | 26.70 | 12.13 |
November | 0.957008E+09 | 4430.63 | 02-NOV-15:00 | 17.20 | 9.31 | 0.00 | 0.00 | 01-NOV-00:10 | 17.20 | 9.31 |
December | 0.276827E+09 | 2073.56 | 31-DEC-15:16 | 10.73 | 1.97 | 0.00 | 0.00 | 01-DEC-00:10 | 10.73 | 1.97 |
Annual Sum or Average | 0.492229E+11 | 0.00 | ||||||||
Minimum of Months | 0.276827E+09 | 2073.56 | 10.73 | 1.97 | 0.00 | 0.00 | 10.73 | 1.97 | ||
Maximum of Months | 0.923612E+10 | 13009.68 | 38.13 | 15.81 | 0.00 | 0.00 | 38.13 | 15.81 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145011E+09 | 2231.95 | 21-JAN-06:01 | -6.5 | -6.8 | 0.00 | 0.00 | 01-JAN-00:10 | -6.5 | -6.8 |
February | 0.221664E+09 | 2933.00 | 04-FEB-06:01 | -6.7 | -8.2 | 0.00 | 0.00 | 01-FEB-00:10 | -6.7 | -8.2 |
March | 0.550146E+09 | 2138.46 | 04-MAR-06:01 | -1.7 | -4.4 | 0.00 | 0.00 | 01-MAR-00:10 | -1.7 | -4.4 |
April | 0.160094E+10 | 3528.30 | 28-APR-15:00 | 25.00 | 10.42 | 0.00 | 0.00 | 01-APR-00:10 | 25.00 | 10.42 |
May | 0.264173E+10 | 4317.36 | 30-MAY-14:30 | 27.20 | 12.25 | 0.00 | 0.00 | 01-MAY-00:10 | 27.20 | 12.25 |
June | 0.442502E+10 | 6062.90 | 26-JUN-15:30 | 35.55 | 15.63 | 0.00 | 0.00 | 01-JUN-00:10 | 35.55 | 15.63 |
July | 0.521931E+10 | 6282.73 | 05-JUL-06:10 | 22.57 | 13.90 | 0.00 | 0.00 | 01-JUL-00:10 | 22.57 | 13.90 |
August | 0.521145E+10 | 6428.09 | 07-AUG-15:30 | 33.05 | 15.91 | 0.00 | 0.00 | 01-AUG-00:10 | 33.05 | 15.91 |
September | 0.351147E+10 | 5249.25 | 05-SEP-14:50 | 24.40 | 17.68 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 17.68 |
October | 0.184022E+10 | 4990.40 | 02-OCT-15:50 | 24.45 | 14.87 | 0.00 | 0.00 | 01-OCT-00:10 | 24.45 | 14.87 |
November | 0.449049E+09 | 1966.14 | 01-NOV-15:40 | 11.33 | 6.68 | 0.00 | 0.00 | 01-NOV-00:10 | 11.33 | 6.68 |
December | 0.114590E+09 | 2496.11 | 15-DEC-06:01 | -7.9 | -10.9 | 0.00 | 0.00 | 01-DEC-00:10 | -7.9 | -10.9 |
Annual Sum or Average | 0.259306E+11 | 0.00 | ||||||||
Minimum of Months | 0.114590E+09 | 1966.14 | -7.9 | -10.9 | 0.00 | 0.00 | -7.9 | -10.9 | ||
Maximum of Months | 0.521931E+10 | 6428.09 | 35.55 | 17.68 | 0.00 | 0.00 | 35.55 | 17.68 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274515E+09 | 2451.24 | 27-JAN-07:02 | -5.5 | -7.8 | 0.00 | 0.00 | 01-JAN-00:10 | -5.5 | -7.8 |
February | 0.442249E+09 | 2234.98 | 15-FEB-16:50 | 16.78 | 5.96 | 0.00 | 0.00 | 01-FEB-00:10 | 16.78 | 5.96 |
March | 0.107717E+10 | 2567.59 | 24-MAR-06:03 | -0.7 | -2.9 | 0.00 | 0.00 | 01-MAR-00:10 | -0.7 | -2.9 |
April | 0.227229E+10 | 3957.79 | 28-APR-15:10 | 25.00 | 10.42 | 0.00 | 0.00 | 01-APR-00:10 | 25.00 | 10.42 |
May | 0.326929E+10 | 4619.00 | 15-MAY-16:00 | 28.90 | 11.34 | 0.00 | 0.00 | 01-MAY-00:10 | 28.90 | 11.34 |
June | 0.495683E+10 | 6217.26 | 26-JUN-15:30 | 35.55 | 15.63 | 0.00 | 0.00 | 01-JUN-00:10 | 35.55 | 15.63 |
July | 0.569239E+10 | 6888.28 | 05-JUL-12:10 | 30.78 | 17.16 | 0.00 | 0.00 | 01-JUL-00:10 | 30.78 | 17.16 |
August | 0.588275E+10 | 6505.98 | 07-AUG-16:00 | 33.30 | 16.21 | 0.00 | 0.00 | 01-AUG-00:10 | 33.30 | 16.21 |
September | 0.442420E+10 | 5756.68 | 05-SEP-15:30 | 24.15 | 17.41 | 0.00 | 0.00 | 01-SEP-00:10 | 24.15 | 17.41 |
October | 0.280158E+10 | 5238.17 | 02-OCT-16:10 | 23.35 | 15.07 | 0.00 | 0.00 | 01-OCT-00:10 | 23.35 | 15.07 |
November | 0.980975E+09 | 2978.27 | 01-NOV-16:00 | 10.60 | 6.24 | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 6.24 |
December | 0.251503E+09 | 2329.98 | 21-DEC-07:02 | -7.5 | -8.5 | 0.00 | 0.00 | 01-DEC-00:10 | -7.5 | -8.5 |
Annual Sum or Average | 0.323257E+11 | 0.00 | ||||||||
Minimum of Months | 0.251503E+09 | 2234.98 | -7.5 | -8.5 | 0.00 | 0.00 | -7.5 | -8.5 | ||
Maximum of Months | 0.588275E+10 | 6888.28 | 35.55 | 17.41 | 0.00 | 0.00 | 35.55 | 17.41 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.866445E+10 | 9786.65 | 27-JAN-17:00 | 10.00 | 1.22 | 0.181677E+10 | 2606.50 | 04-JAN-14:00 | 10.00 | 1.22 |
February | 0.847276E+10 | 13681.49 | 15-FEB-17:00 | 16.70 | 5.85 | 0.170010E+10 | 2606.63 | 15-FEB-10:09 | 16.70 | 5.85 |
March | 0.120211E+11 | 13337.00 | 09-MAR-17:00 | 16.70 | 5.52 | 0.211679E+10 | 2606.72 | 21-MAR-13:09 | 5.65 | 3.53 |
April | 0.145295E+11 | 16822.06 | 28-APR-16:00 | 25.00 | 10.41 | 0.190422E+10 | 2606.65 | 17-APR-13:00 | 25.00 | 10.41 |
May | 0.177838E+11 | 28814.05 | 30-MAY-06:02 | 13.77 | 10.85 | 0.206959E+10 | 2606.73 | 11-MAY-09:09 | 13.77 | 10.85 |
June | 0.205727E+11 | 35384.51 | 29-JUN-04:02 | 24.40 | 15.17 | 0.206790E+10 | 2606.68 | 08-JUN-13:09 | 24.40 | 15.17 |
July | 0.214646E+11 | 33908.92 | 24-JUL-05:12 | 22.20 | 14.92 | 0.192333E+10 | 2606.63 | 21-JUL-09:09 | 22.20 | 14.92 |
August | 0.224753E+11 | 34090.23 | 22-AUG-05:12 | 21.33 | 15.21 | 0.215900E+10 | 2606.85 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.187451E+11 | 32807.66 | 05-SEP-06:02 | 15.10 | 14.31 | 0.191558E+10 | 2606.67 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.155992E+11 | 31889.83 | 02-OCT-06:03 | 16.60 | 12.55 | 0.197723E+10 | 2606.65 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.108942E+11 | 15445.13 | 01-NOV-16:00 | 10.60 | 6.24 | 0.192133E+10 | 2606.62 | 08-NOV-10:20 | 13.50 | 6.09 |
December | 0.855237E+10 | 10603.60 | 01-DEC-16:40 | 12.40 | 4.45 | 0.176503E+10 | 2606.61 | 01-DEC-10:20 | 12.40 | 4.45 |
Annual Sum or Average | 0.179775E+12 | 0.233369E+11 | ||||||||
Minimum of Months | 0.847276E+10 | 9786.65 | 10.00 | 1.22 | 0.170010E+10 | 2606.50 | 5.65 | 1.22 | ||
Maximum of Months | 0.224753E+11 | 35384.51 | 25.00 | 15.21 | 0.215900E+10 | 2606.85 | 25.00 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.715292E+10 | 8262.38 | 05-JAN-16:50 | 13.77 | 5.77 | 0.168449E+10 | 2599.34 | 27-JAN-14:00 | 11.70 | 2.33 |
February | 0.738576E+10 | 13399.03 | 15-FEB-17:00 | 16.70 | 5.85 | 0.159326E+10 | 2606.46 | 15-FEB-14:00 | 16.70 | 5.85 |
March | 0.108459E+11 | 13564.77 | 08-MAR-17:00 | 22.20 | 8.27 | 0.203478E+10 | 2606.61 | 02-MAR-14:09 | 22.20 | 8.27 |
April | 0.137429E+11 | 18338.73 | 28-APR-15:00 | 25.00 | 10.42 | 0.187963E+10 | 2606.65 | 17-APR-13:00 | 25.00 | 10.42 |
May | 0.175185E+11 | 20124.51 | 30-MAY-14:50 | 27.20 | 12.25 | 0.205855E+10 | 2606.71 | 11-MAY-09:09 | 27.20 | 12.25 |
June | 0.212849E+11 | 29917.72 | 26-JUN-06:03 | 19.97 | 12.34 | 0.206432E+10 | 2606.69 | 08-JUN-13:09 | 19.97 | 12.34 |
July | 0.225861E+11 | 36505.76 | 24-JUL-05:12 | 22.20 | 14.92 | 0.192233E+10 | 2606.63 | 21-JUL-09:09 | 22.20 | 14.92 |
August | 0.231575E+11 | 33727.17 | 21-AUG-06:03 | 21.28 | 15.38 | 0.215714E+10 | 2606.87 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.182161E+11 | 33952.28 | 05-SEP-06:02 | 15.10 | 14.31 | 0.190913E+10 | 2606.64 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.138768E+11 | 20178.17 | 02-OCT-15:00 | 27.20 | 15.21 | 0.193383E+10 | 2606.63 | 18-OCT-09:09 | 12.35 | 5.73 |
November | 0.914111E+10 | 14629.90 | 01-NOV-16:00 | 10.60 | 6.24 | 0.182372E+10 | 2606.61 | 01-NOV-09:09 | 10.60 | 6.24 |
December | 0.697694E+10 | 8228.95 | 01-DEC-16:30 | 12.50 | 4.57 | 0.162505E+10 | 2606.48 | 01-DEC-14:00 | 12.50 | 4.57 |
Annual Sum or Average | 0.171885E+12 | 0.226862E+11 | ||||||||
Minimum of Months | 0.697694E+10 | 8228.95 | 10.60 | 4.57 | 0.159326E+10 | 2599.34 | 10.60 | 2.33 | ||
Maximum of Months | 0.231575E+11 | 36505.76 | 27.20 | 15.38 | 0.215714E+10 | 2606.87 | 27.20 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.615639E+09 | 1564.45 | 05-JAN-14:10 | 16.10 | 6.84 | 0.317184E+09 | 483.67 | 05-JAN-16:30 | 14.70 | 6.21 |
February | 0.869251E+09 | 2064.51 | 15-FEB-14:10 | 16.28 | 6.32 | 0.297594E+09 | 538.78 | 15-FEB-14:00 | 17.20 | 6.67 |
March | 0.181280E+10 | 2902.67 | 16-MAR-14:50 | 20.10 | 8.53 | 0.393210E+09 | 549.49 | 28-MAR-13:00 | 15.00 | 7.35 |
April | 0.296730E+10 | 5460.18 | 14-APR-14:30 | 23.60 | 10.45 | 0.380379E+09 | 549.50 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.436493E+10 | 6210.69 | 31-MAY-15:20 | 27.57 | 11.01 | 0.427869E+09 | 549.50 | 31-MAY-13:20 | 27.57 | 11.01 |
June | 0.667214E+10 | 13539.49 | 25-JUN-17:21 | 33.05 | 15.18 | 0.434719E+09 | 549.51 | 30-JUN-13:39 | 29.47 | 17.83 |
July | 0.726508E+10 | 13613.80 | 04-JUL-18:21 | 33.05 | 13.57 | 0.405690E+09 | 549.50 | 21-JUL-09:09 | 30.18 | 16.59 |
August | 0.682767E+10 | 13333.97 | 20-AUG-16:11 | 34.80 | 15.86 | 0.454197E+09 | 549.55 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.453462E+10 | 9105.12 | 03-SEP-13:52 | 32.80 | 16.76 | 0.398472E+09 | 549.50 | 13-SEP-13:39 | 26.67 | 14.56 |
October | 0.267723E+10 | 5832.01 | 02-OCT-13:40 | 26.33 | 15.37 | 0.382239E+09 | 549.49 | 02-OCT-13:39 | 26.33 | 15.37 |
November | 0.130121E+10 | 2122.44 | 01-NOV-14:10 | 12.30 | 7.31 | 0.340546E+09 | 549.47 | 03-NOV-13:00 | 12.20 | 2.42 |
December | 0.490636E+09 | 1516.08 | 29-DEC-13:40 | 10.03 | 3.18 | 0.300555E+09 | 491.84 | 01-DEC-14:00 | 10.03 | 3.18 |
Annual Sum or Average | 0.403985E+11 | 0.453265E+10 | ||||||||
Minimum of Months | 0.490636E+09 | 1516.08 | 10.03 | 3.18 | 0.297594E+09 | 483.67 | 10.03 | 2.42 | ||
Maximum of Months | 0.726508E+10 | 13613.80 | 34.80 | 16.76 | 0.454197E+09 | 549.55 | 30.18 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101201E+10 | 1944.39 | 27-JAN-09:45 | 2.43 | -2.7 | 0.210965E+09 | 347.87 | 27-JAN-10:30 | 4.45 | -1.6 |
February | 0.132754E+10 | 4121.61 | 14-FEB-09:40 | 8.90 | 2.72 | 0.201924E+09 | 347.87 | 28-FEB-10:09 | 6.88 | 2.31 |
March | 0.265977E+10 | 7268.94 | 26-MAR-09:43 | 13.77 | 5.28 | 0.265587E+09 | 347.87 | 30-MAR-09:20 | 7.93 | 3.09 |
April | 0.453540E+10 | 15008.94 | 30-APR-08:32 | 15.40 | 4.96 | 0.251772E+09 | 348.44 | 28-APR-09:00 | 15.40 | 4.96 |
May | 0.554954E+10 | 15325.17 | 29-MAY-08:52 | 18.30 | 12.78 | 0.274329E+09 | 348.40 | 15-MAY-09:50 | 18.30 | 12.78 |
June | 0.737292E+10 | 15954.68 | 18-JUN-08:41 | 25.13 | 11.87 | 0.275656E+09 | 348.66 | 22-JUN-09:00 | 30.60 | 15.11 |
July | 0.763553E+10 | 16358.20 | 04-JUL-09:01 | 26.97 | 18.48 | 0.257190E+09 | 348.64 | 12-JUL-09:00 | 28.30 | 16.24 |
August | 0.751912E+10 | 16237.26 | 20-AUG-08:51 | 26.10 | 15.49 | 0.287932E+09 | 348.53 | 16-AUG-09:00 | 26.10 | 15.49 |
September | 0.545247E+10 | 15561.19 | 03-SEP-09:12 | 26.33 | 15.30 | 0.253539E+09 | 347.97 | 13-SEP-09:09 | 22.48 | 13.60 |
October | 0.354004E+10 | 10970.41 | 01-OCT-09:12 | 18.90 | 11.69 | 0.252533E+09 | 348.31 | 27-OCT-09:30 | 5.55 | 1.41 |
November | 0.176349E+10 | 5352.73 | 01-NOV-09:10 | 10.47 | 6.68 | 0.231141E+09 | 347.87 | 01-NOV-09:09 | 10.47 | 6.68 |
December | 0.993829E+09 | 1810.66 | 29-DEC-09:40 | 2.23 | -0.6 | 0.199180E+09 | 345.72 | 29-DEC-10:09 | 3.27 | 0.11 |
Annual Sum or Average | 0.493616E+11 | 0.296175E+10 | ||||||||
Minimum of Months | 0.993829E+09 | 1810.66 | 2.23 | -2.7 | 0.199180E+09 | 345.72 | 3.27 | -1.6 | ||
Maximum of Months | 0.763553E+10 | 16358.20 | 26.97 | 18.48 | 0.287932E+09 | 348.66 | 30.60 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.414782E+10 | 16446.89 | 29-JAN-14:02 | 10.10 | 2.83 | 0.376561E+09 | 549.63 | 30-JAN-14:50 | 14.90 | 4.78 |
February | 0.441174E+10 | 16582.77 | 19-FEB-13:42 | 15.92 | 6.62 | 0.348610E+09 | 556.22 | 14-FEB-14:09 | 15.92 | 6.62 |
March | 0.505269E+10 | 16968.81 | 26-MAR-14:22 | 20.30 | 7.65 | 0.420657E+09 | 549.98 | 08-MAR-14:00 | 20.30 | 7.65 |
April | 0.557352E+10 | 15064.45 | 30-APR-13:13 | 20.97 | 7.31 | 0.386157E+09 | 550.26 | 27-APR-13:50 | 20.97 | 7.31 |
May | 0.555202E+10 | 9727.09 | 28-MAY-12:32 | 23.87 | 13.84 | 0.425948E+09 | 549.51 | 08-MAY-13:50 | 23.87 | 13.84 |
June | 0.695417E+10 | 15517.15 | 25-JUN-16:01 | 35.22 | 14.86 | 0.432599E+09 | 549.51 | 30-JUN-13:39 | 29.47 | 17.83 |
July | 0.808631E+10 | 16410.41 | 30-JUL-14:52 | 33.30 | 17.94 | 0.405249E+09 | 549.50 | 21-JUL-09:09 | 33.30 | 17.94 |
August | 0.933235E+10 | 16710.07 | 20-AUG-12:52 | 32.80 | 17.07 | 0.454036E+09 | 550.18 | 07-AUG-13:00 | 32.80 | 17.07 |
September | 0.883831E+10 | 17883.71 | 03-SEP-13:12 | 31.67 | 16.75 | 0.400727E+09 | 592.69 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.816345E+10 | 18197.25 | 01-OCT-12:32 | 26.67 | 14.27 | 0.404799E+09 | 588.80 | 05-OCT-13:30 | 26.15 | 12.94 |
November | 0.565437E+10 | 16939.46 | 12-NOV-14:22 | 9.15 | 2.53 | 0.394121E+09 | 569.83 | 01-NOV-13:09 | 9.15 | 2.53 |
December | 0.459552E+10 | 17074.45 | 31-DEC-15:12 | 10.73 | 1.97 | 0.370303E+09 | 549.55 | 29-DEC-14:00 | 10.73 | 1.97 |
Annual Sum or Average | 0.763623E+11 | 0.481977E+10 | ||||||||
Minimum of Months | 0.414782E+10 | 9727.09 | 9.15 | 1.97 | 0.348610E+09 | 549.50 | 9.15 | 1.97 | ||
Maximum of Months | 0.933235E+10 | 18197.25 | 35.22 | 17.94 | 0.454036E+09 | 592.69 | 33.30 | 17.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110212E+10 | 4804.72 | 26-JAN-16:30 | 10.30 | 1.40 | 0.210540E+09 | 347.78 | 05-JAN-14:00 | 10.30 | 1.40 |
February | 0.158214E+10 | 7651.65 | 15-FEB-16:30 | 16.95 | 6.18 | 0.196167E+09 | 347.83 | 28-FEB-14:00 | 13.90 | 4.60 |
March | 0.277075E+10 | 8343.29 | 12-MAR-16:03 | 19.60 | 6.14 | 0.243131E+09 | 347.84 | 07-MAR-14:00 | 19.60 | 6.14 |
April | 0.415871E+10 | 16405.91 | 16-APR-16:12 | 19.80 | 7.90 | 0.233527E+09 | 347.86 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.511412E+10 | 17627.05 | 14-MAY-16:31 | 28.30 | 10.81 | 0.263142E+09 | 347.86 | 08-MAY-13:50 | 28.30 | 10.81 |
June | 0.665000E+10 | 18631.44 | 25-JUN-16:41 | 33.68 | 14.48 | 0.271458E+09 | 347.86 | 30-JUN-13:39 | 29.47 | 17.83 |
July | 0.690595E+10 | 18845.38 | 04-JUL-17:01 | 35.73 | 14.63 | 0.255468E+09 | 347.85 | 21-JUL-09:09 | 30.18 | 16.59 |
August | 0.689297E+10 | 18412.24 | 20-AUG-16:11 | 34.80 | 15.86 | 0.285335E+09 | 347.89 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.523481E+10 | 18890.99 | 24-SEP-16:21 | 25.30 | 15.57 | 0.247661E+09 | 347.86 | 13-SEP-13:39 | 25.30 | 15.57 |
October | 0.380509E+10 | 15496.24 | 01-OCT-15:12 | 28.50 | 13.01 | 0.236862E+09 | 347.86 | 05-OCT-13:50 | 26.52 | 12.57 |
November | 0.199156E+10 | 6519.07 | 02-NOV-16:00 | 16.70 | 9.78 | 0.219279E+09 | 347.84 | 14-NOV-14:00 | 12.20 | 4.12 |
December | 0.978925E+09 | 3840.59 | 29-DEC-16:00 | 11.70 | 3.88 | 0.203655E+09 | 347.71 | 20-DEC-14:00 | 11.70 | 3.88 |
Annual Sum or Average | 0.471871E+11 | 0.286623E+10 | ||||||||
Minimum of Months | 0.978925E+09 | 3840.59 | 10.30 | 1.40 | 0.196167E+09 | 347.71 | 10.30 | 1.40 | ||
Maximum of Months | 0.690595E+10 | 18890.99 | 35.73 | 15.86 | 0.285335E+09 | 347.89 | 30.18 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.717825E+09 | 1557.88 | 27-JAN-13:07 | 9.60 | 1.39 | 0.319102E+09 | 476.05 | 05-JAN-14:00 | 9.60 | 1.39 |
February | 0.848382E+09 | 1721.64 | 14-FEB-14:50 | 21.52 | 7.30 | 0.296289E+09 | 505.88 | 15-FEB-14:00 | 17.20 | 6.67 |
March | 0.159960E+10 | 1474.92 | 27-MAR-15:20 | 18.50 | 7.17 | 0.386737E+09 | 545.59 | 17-MAR-13:00 | 18.50 | 7.17 |
April | 0.221503E+10 | 3760.81 | 14-APR-14:30 | 23.60 | 10.45 | 0.381012E+09 | 549.49 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.331987E+10 | 4607.22 | 31-MAY-16:00 | 28.30 | 11.06 | 0.429912E+09 | 549.50 | 23-MAY-13:50 | 28.30 | 11.06 |
June | 0.554664E+10 | 11104.68 | 25-JUN-17:51 | 32.80 | 15.93 | 0.435332E+09 | 549.51 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.636995E+10 | 11383.63 | 04-JUL-18:11 | 33.33 | 13.61 | 0.405657E+09 | 549.50 | 21-JUL-09:09 | 30.18 | 16.59 |
August | 0.622899E+10 | 11055.87 | 20-AUG-16:01 | 34.90 | 15.92 | 0.454861E+09 | 549.55 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.442363E+10 | 6588.32 | 05-SEP-06:02 | 15.10 | 14.31 | 0.402627E+09 | 549.50 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.285652E+10 | 5147.03 | 02-OCT-13:40 | 26.33 | 15.37 | 0.399435E+09 | 549.49 | 24-OCT-13:50 | 8.87 | 4.55 |
November | 0.162283E+10 | 1946.93 | 01-NOV-14:50 | 12.70 | 7.48 | 0.359261E+09 | 549.47 | 09-NOV-14:00 | 18.30 | 9.49 |
December | 0.739837E+09 | 1565.12 | 29-DEC-13:07 | 9.18 | 2.77 | 0.306780E+09 | 507.48 | 01-DEC-14:00 | 9.18 | 2.77 |
Annual Sum or Average | 0.364891E+11 | 0.457701E+10 | ||||||||
Minimum of Months | 0.717825E+09 | 1474.92 | 9.18 | 1.39 | 0.296289E+09 | 476.05 | 8.87 | 1.39 | ||
Maximum of Months | 0.636995E+10 | 11383.63 | 34.90 | 15.93 | 0.454861E+09 | 549.55 | 30.18 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115491E+10 | 1792.03 | 27-JAN-13:07 | 9.60 | 1.39 | 0.218788E+09 | 347.87 | 27-JAN-10:09 | 9.60 | 1.39 |
February | 0.128978E+10 | 2875.25 | 14-FEB-10:10 | 10.83 | 3.59 | 0.205732E+09 | 347.87 | 15-FEB-10:09 | 11.38 | 5.33 |
March | 0.229440E+10 | 3903.14 | 31-MAR-08:65 | 8.07 | 3.18 | 0.269324E+09 | 347.87 | 13-MAR-09:09 | 8.07 | 3.18 |
April | 0.389495E+10 | 13098.02 | 30-APR-07:41 | 14.63 | 5.07 | 0.253586E+09 | 347.88 | 17-APR-13:00 | 14.63 | 5.07 |
May | 0.485782E+10 | 13522.30 | 29-MAY-08:41 | 17.93 | 12.73 | 0.275971E+09 | 347.99 | 15-MAY-09:09 | 17.93 | 12.73 |
June | 0.668512E+10 | 13953.64 | 25-JUN-09:11 | 27.23 | 16.34 | 0.276428E+09 | 348.27 | 22-JUN-09:00 | 27.23 | 16.34 |
July | 0.720612E+10 | 14553.07 | 04-JUL-09:31 | 27.77 | 17.84 | 0.257644E+09 | 348.29 | 12-JUL-09:00 | 28.30 | 16.24 |
August | 0.728677E+10 | 14436.77 | 20-AUG-09:21 | 27.20 | 16.00 | 0.288677E+09 | 348.28 | 18-AUG-09:39 | 27.20 | 16.00 |
September | 0.549864E+10 | 13159.42 | 03-SEP-10:52 | 28.90 | 16.43 | 0.255667E+09 | 347.89 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.385818E+10 | 10365.74 | 01-OCT-08:51 | 17.80 | 11.25 | 0.260865E+09 | 347.88 | 18-OCT-09:09 | 12.35 | 5.73 |
November | 0.206628E+10 | 4771.60 | 01-NOV-08:20 | 8.53 | 5.80 | 0.247956E+09 | 347.87 | 01-NOV-09:09 | 10.47 | 6.68 |
December | 0.121593E+10 | 1795.34 | 29-DEC-08:55 | 1.10 | -1.2 | 0.211920E+09 | 347.84 | 29-DEC-10:09 | 3.27 | 0.11 |
Annual Sum or Average | 0.473089E+11 | 0.302256E+10 | ||||||||
Minimum of Months | 0.115491E+10 | 1792.03 | 1.10 | -1.2 | 0.205732E+09 | 347.84 | 3.27 | 0.11 | ||
Maximum of Months | 0.728677E+10 | 14553.07 | 28.90 | 17.84 | 0.288677E+09 | 348.29 | 28.30 | 16.34 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305355E+10 | 14291.56 | 01-JAN-14:32 | 15.93 | 5.77 | 0.371533E+09 | 550.54 | 30-JAN-14:50 | 14.90 | 4.78 |
February | 0.291666E+10 | 12631.37 | 19-FEB-13:42 | 15.92 | 6.62 | 0.342678E+09 | 550.87 | 14-FEB-14:39 | 15.92 | 6.62 |
March | 0.325442E+10 | 8608.67 | 13-MAR-14:20 | 20.97 | 7.20 | 0.414185E+09 | 549.68 | 08-MAR-14:39 | 20.97 | 7.20 |
April | 0.374963E+10 | 9676.98 | 30-APR-13:42 | 21.52 | 7.52 | 0.383181E+09 | 549.51 | 17-APR-13:00 | 21.52 | 7.52 |
May | 0.399307E+10 | 8337.26 | 19-MAY-16:10 | 30.00 | 12.47 | 0.420402E+09 | 549.51 | 09-MAY-13:30 | 30.00 | 12.47 |
June | 0.629875E+10 | 12847.49 | 25-JUN-15:51 | 35.60 | 14.95 | 0.431622E+09 | 574.59 | 29-JUN-12:09 | 35.37 | 17.08 |
July | 0.797118E+10 | 13822.87 | 04-JUL-15:31 | 35.60 | 13.95 | 0.405710E+09 | 571.22 | 20-JUL-12:09 | 34.60 | 17.14 |
August | 0.927159E+10 | 14405.14 | 20-AUG-15:21 | 35.00 | 15.81 | 0.454720E+09 | 573.59 | 07-AUG-12:09 | 35.00 | 15.81 |
September | 0.886993E+10 | 14907.37 | 03-SEP-14:12 | 32.07 | 16.57 | 0.403896E+09 | 597.71 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.792186E+10 | 15510.60 | 09-OCT-14:01 | 21.88 | 11.30 | 0.411691E+09 | 597.67 | 05-OCT-13:00 | 21.88 | 11.30 |
November | 0.497430E+10 | 14363.33 | 19-NOV-14:52 | 15.00 | 4.07 | 0.400368E+09 | 567.09 | 01-NOV-13:20 | 15.00 | 4.07 |
December | 0.341815E+10 | 13817.98 | 31-DEC-14:12 | 10.37 | 1.81 | 0.366428E+09 | 549.81 | 13-DEC-10:39 | 10.37 | 1.81 |
Annual Sum or Average | 0.656931E+11 | 0.480641E+10 | ||||||||
Minimum of Months | 0.291666E+10 | 8337.26 | 10.37 | 1.81 | 0.342678E+09 | 549.51 | 10.37 | 1.81 | ||
Maximum of Months | 0.927159E+10 | 15510.60 | 35.60 | 16.57 | 0.454720E+09 | 597.71 | 35.37 | 17.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120162E+10 | 4013.21 | 26-JAN-16:30 | 10.30 | 1.40 | 0.213394E+09 | 347.39 | 05-JAN-14:00 | 10.30 | 1.40 |
February | 0.144561E+10 | 5974.29 | 15-FEB-16:40 | 16.87 | 6.07 | 0.199041E+09 | 347.82 | 15-FEB-14:00 | 16.87 | 6.07 |
March | 0.225383E+10 | 5617.40 | 07-MAR-17:00 | 20.60 | 8.53 | 0.249408E+09 | 347.83 | 09-MAR-14:00 | 16.70 | 5.68 |
April | 0.328928E+10 | 14638.17 | 16-APR-17:21 | 20.00 | 7.87 | 0.242869E+09 | 347.86 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.415531E+10 | 14169.64 | 29-MAY-16:41 | 26.28 | 13.29 | 0.270566E+09 | 347.85 | 09-MAY-13:30 | 26.28 | 13.29 |
June | 0.577006E+10 | 15481.41 | 25-JUN-17:11 | 33.13 | 14.92 | 0.274753E+09 | 347.86 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.624727E+10 | 15860.68 | 04-JUL-17:31 | 34.63 | 14.06 | 0.256873E+09 | 347.85 | 21-JUL-09:09 | 30.18 | 16.59 |
August | 0.648184E+10 | 15590.92 | 20-AUG-17:21 | 34.40 | 15.47 | 0.288197E+09 | 347.89 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.508548E+10 | 13907.87 | 17-SEP-16:01 | 24.90 | 14.18 | 0.255295E+09 | 347.85 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.385215E+10 | 14014.13 | 01-OCT-15:31 | 28.70 | 13.14 | 0.254059E+09 | 347.85 | 04-OCT-13:00 | 25.60 | 13.67 |
November | 0.222272E+10 | 6174.25 | 02-NOV-16:00 | 16.70 | 9.78 | 0.235374E+09 | 347.84 | 03-NOV-13:00 | 12.20 | 2.42 |
December | 0.126124E+10 | 3256.03 | 29-DEC-16:10 | 11.42 | 3.74 | 0.207558E+09 | 347.25 | 20-DEC-14:00 | 11.42 | 3.74 |
Annual Sum or Average | 0.432664E+11 | 0.294739E+10 | ||||||||
Minimum of Months | 0.120162E+10 | 3256.03 | 10.30 | 1.40 | 0.199041E+09 | 347.25 | 10.30 | 1.40 | ||
Maximum of Months | 0.648184E+10 | 15860.68 | 34.63 | 15.47 | 0.288197E+09 | 347.89 | 30.18 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.930162E+09 | 1639.19 | 05-JAN-14:10 | 16.10 | 6.84 | 0.326983E+09 | 501.64 | 24-JAN-14:00 | 16.10 | 4.97 |
February | 0.110179E+10 | 2033.96 | 15-FEB-16:20 | 17.03 | 6.28 | 0.310196E+09 | 549.46 | 15-FEB-14:00 | 17.03 | 6.28 |
March | 0.197206E+10 | 3046.91 | 27-MAR-14:40 | 18.13 | 6.99 | 0.412607E+09 | 549.49 | 28-MAR-13:00 | 15.00 | 7.35 |
April | 0.299869E+10 | 5215.70 | 14-APR-14:30 | 23.60 | 10.45 | 0.391655E+09 | 549.50 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.430967E+10 | 5771.14 | 31-MAY-15:30 | 27.75 | 11.03 | 0.433368E+09 | 549.51 | 11-MAY-09:09 | 27.75 | 11.03 |
June | 0.638647E+10 | 12023.31 | 25-JUN-17:51 | 32.80 | 15.93 | 0.436005E+09 | 549.51 | 30-JUN-13:39 | 29.47 | 17.83 |
July | 0.688277E+10 | 12681.26 | 04-JUL-18:12 | 33.33 | 13.61 | 0.406108E+09 | 549.87 | 31-JUL-13:30 | 30.00 | 18.38 |
August | 0.656821E+10 | 11896.40 | 20-AUG-16:01 | 34.90 | 15.92 | 0.455022E+09 | 549.55 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.451612E+10 | 10207.55 | 04-SEP-16:51 | 26.70 | 16.12 | 0.402213E+09 | 549.50 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.285835E+10 | 5582.47 | 02-OCT-13:40 | 26.33 | 15.37 | 0.397114E+09 | 549.50 | 24-OCT-13:50 | 8.87 | 4.55 |
November | 0.161484E+10 | 2220.59 | 02-NOV-15:30 | 16.95 | 9.55 | 0.360983E+09 | 549.48 | 09-NOV-14:00 | 18.30 | 9.49 |
December | 0.801163E+09 | 1591.49 | 29-DEC-14:20 | 10.77 | 3.61 | 0.309438E+09 | 523.25 | 01-DEC-14:00 | 10.77 | 3.61 |
Annual Sum or Average | 0.409403E+11 | 0.464169E+10 | ||||||||
Minimum of Months | 0.801163E+09 | 1591.49 | 10.77 | 3.61 | 0.309438E+09 | 501.64 | 8.87 | 3.61 | ||
Maximum of Months | 0.688277E+10 | 12681.26 | 34.90 | 16.12 | 0.455022E+09 | 549.87 | 30.00 | 18.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132250E+10 | 2996.32 | 27-JAN-09:25 | 1.70 | -3.2 | 0.159608E+09 | 338.71 | 24-JAN-09:50 | 1.70 | -3.2 |
February | 0.162830E+10 | 5133.52 | 14-FEB-09:30 | 8.35 | 2.46 | 0.151824E+09 | 338.72 | 14-FEB-08:20 | 8.35 | 2.46 |
March | 0.300148E+10 | 10108.83 | 26-MAR-09:53 | 14.40 | 5.52 | 0.197550E+09 | 338.78 | 10-MAR-08:50 | 14.40 | 5.52 |
April | 0.468616E+10 | 15970.19 | 30-APR-07:41 | 14.63 | 5.07 | 0.186510E+09 | 339.75 | 26-APR-08:39 | 14.63 | 5.07 |
May | 0.555293E+10 | 16695.67 | 29-MAY-08:41 | 17.93 | 12.73 | 0.203116E+09 | 339.00 | 23-MAY-08:00 | 17.93 | 12.73 |
June | 0.711155E+10 | 17182.80 | 25-JUN-08:31 | 25.77 | 15.91 | 0.203852E+09 | 342.90 | 29-JUN-07:19 | 27.93 | 17.35 |
July | 0.736381E+10 | 17825.92 | 04-JUL-08:51 | 26.70 | 18.67 | 0.190792E+09 | 343.44 | 21-JUL-07:19 | 27.43 | 15.33 |
August | 0.726756E+10 | 17752.02 | 20-AUG-08:41 | 25.82 | 15.35 | 0.212804E+09 | 344.15 | 07-AUG-07:19 | 25.82 | 15.35 |
September | 0.540067E+10 | 16898.86 | 03-SEP-09:01 | 25.97 | 15.10 | 0.187994E+09 | 339.05 | 13-SEP-08:00 | 22.20 | 13.47 |
October | 0.381983E+10 | 15539.05 | 01-OCT-08:22 | 16.70 | 10.70 | 0.188391E+09 | 338.73 | 06-OCT-10:09 | 21.57 | 12.33 |
November | 0.221209E+10 | 6088.83 | 01-NOV-09:00 | 10.00 | 6.46 | 0.174434E+09 | 338.72 | 09-NOV-08:20 | 13.33 | 8.67 |
December | 0.129506E+10 | 2799.02 | 29-DEC-09:15 | 1.67 | -0.9 | 0.152691E+09 | 338.71 | 29-DEC-09:39 | 2.23 | -0.6 |
Annual Sum or Average | 0.506619E+11 | 0.220957E+10 | ||||||||
Minimum of Months | 0.129506E+10 | 2799.02 | 1.67 | -3.2 | 0.151824E+09 | 338.71 | 1.70 | -3.2 | ||
Maximum of Months | 0.736381E+10 | 17825.92 | 26.70 | 18.67 | 0.212804E+09 | 344.15 | 27.93 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.483089E+10 | 14981.88 | 01-JAN-12:02 | 11.05 | 3.73 | 0.385842E+09 | 562.62 | 26-JAN-14:09 | 10.10 | 1.50 |
February | 0.495955E+10 | 15114.67 | 12-FEB-13:22 | 16.40 | 5.55 | 0.358184E+09 | 578.86 | 14-FEB-14:09 | 20.78 | 7.02 |
March | 0.544511E+10 | 14980.58 | 12-MAR-12:23 | 16.40 | 5.19 | 0.433058E+09 | 550.00 | 16-MAR-13:00 | 20.60 | 8.86 |
April | 0.566413E+10 | 15005.89 | 30-APR-13:42 | 21.52 | 7.52 | 0.394404E+09 | 550.44 | 27-APR-13:00 | 21.52 | 7.52 |
May | 0.545557E+10 | 13728.71 | 21-MAY-13:12 | 27.07 | 12.24 | 0.432054E+09 | 549.52 | 09-MAY-13:20 | 27.07 | 12.24 |
June | 0.662622E+10 | 14545.19 | 25-JUN-16:31 | 34.07 | 14.58 | 0.434740E+09 | 549.51 | 30-JUN-13:39 | 29.47 | 17.83 |
July | 0.768234E+10 | 15234.21 | 30-JUL-11:22 | 29.45 | 17.97 | 0.405899E+09 | 549.60 | 31-JUL-13:50 | 30.40 | 18.52 |
August | 0.900094E+10 | 15872.54 | 20-AUG-12:42 | 32.80 | 17.07 | 0.455192E+09 | 550.26 | 25-AUG-13:00 | 28.90 | 17.11 |
September | 0.874916E+10 | 16409.58 | 17-SEP-13:22 | 23.90 | 14.61 | 0.404432E+09 | 610.22 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.849125E+10 | 18045.72 | 01-OCT-13:01 | 27.38 | 14.05 | 0.415154E+09 | 606.92 | 05-OCT-13:20 | 25.97 | 13.11 |
November | 0.642836E+10 | 15296.51 | 23-NOV-12:02 | 12.48 | 4.07 | 0.403999E+09 | 598.67 | 01-NOV-13:09 | 12.48 | 4.07 |
December | 0.542116E+10 | 15682.09 | 31-DEC-15:22 | 10.55 | 1.85 | 0.380546E+09 | 556.62 | 29-DEC-14:09 | 10.55 | 1.85 |
Annual Sum or Average | 0.787547E+11 | 0.490350E+10 | ||||||||
Minimum of Months | 0.483089E+10 | 13728.71 | 10.55 | 1.85 | 0.358184E+09 | 549.51 | 10.10 | 1.50 | ||
Maximum of Months | 0.900094E+10 | 18045.72 | 34.07 | 17.97 | 0.455192E+09 | 610.22 | 30.40 | 18.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144583E+10 | 5018.11 | 26-JAN-16:30 | 10.30 | 1.40 | 0.214110E+09 | 347.81 | 26-JAN-14:00 | 10.30 | 1.40 |
February | 0.189069E+10 | 7582.13 | 15-FEB-16:30 | 16.95 | 6.18 | 0.200050E+09 | 347.83 | 15-FEB-14:00 | 16.95 | 6.18 |
March | 0.302630E+10 | 10058.75 | 12-MAR-16:22 | 20.00 | 6.24 | 0.251389E+09 | 347.84 | 17-MAR-13:00 | 16.10 | 5.42 |
April | 0.420573E+10 | 17412.06 | 16-APR-16:41 | 20.40 | 8.08 | 0.240691E+09 | 347.86 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.500046E+10 | 17476.24 | 29-MAY-16:41 | 26.28 | 13.29 | 0.269121E+09 | 347.86 | 09-MAY-13:20 | 26.28 | 13.29 |
June | 0.636638E+10 | 18662.46 | 25-JUN-16:31 | 34.07 | 14.58 | 0.273812E+09 | 347.86 | 30-JUN-13:39 | 29.47 | 17.83 |
July | 0.660855E+10 | 19072.17 | 04-JUL-16:51 | 36.10 | 14.82 | 0.256315E+09 | 347.85 | 21-JUL-09:09 | 30.18 | 16.59 |
August | 0.663868E+10 | 18566.30 | 20-AUG-16:01 | 34.90 | 15.92 | 0.287092E+09 | 347.89 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.513159E+10 | 17035.17 | 04-SEP-16:51 | 26.70 | 16.12 | 0.252115E+09 | 347.85 | 14-SEP-09:09 | 21.47 | 13.38 |
October | 0.399692E+10 | 16548.71 | 09-OCT-15:31 | 23.53 | 12.36 | 0.244761E+09 | 347.85 | 04-OCT-13:00 | 23.53 | 12.36 |
November | 0.240257E+10 | 6619.29 | 02-NOV-15:50 | 16.78 | 9.71 | 0.226654E+09 | 347.84 | 14-NOV-14:00 | 12.20 | 4.12 |
December | 0.135145E+10 | 4036.10 | 29-DEC-16:00 | 11.70 | 3.88 | 0.206804E+09 | 347.80 | 20-DEC-14:00 | 11.70 | 3.88 |
Annual Sum or Average | 0.480651E+11 | 0.292291E+10 | ||||||||
Minimum of Months | 0.135145E+10 | 4036.10 | 10.30 | 1.40 | 0.200050E+09 | 347.80 | 10.30 | 1.40 | ||
Maximum of Months | 0.663868E+10 | 19072.17 | 36.10 | 16.12 | 0.287092E+09 | 347.89 | 30.18 | 17.83 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267738E+10 | 12606.50 | 17-JAN-06:13 | -3.5 |
February | 0.186249E+10 | 14535.89 | 06-FEB-06:12 | -4.8 |
March | 0.117846E+10 | 6926.31 | 06-MAR-07:03 | -0.3 |
April | 0.529725E+09 | 5337.79 | 30-APR-07:52 | 15.00 |
May | 0.299390E+09 | 4610.19 | 29-MAY-07:32 | 15.00 |
June | 0.116622E+09 | 4930.35 | 11-JUN-07:32 | 17.40 |
July | 36940063.05 | 3809.02 | 30-JUL-07:32 | 22.97 |
August | 45537799.09 | 3886.27 | 20-AUG-07:32 | 23.30 |
September | 0.176007E+09 | 3898.52 | 03-SEP-07:52 | 23.30 |
October | 0.740701E+09 | 6276.92 | 26-OCT-05:02 | -2.5 |
November | 0.125317E+10 | 9576.64 | 27-NOV-07:03 | -4.2 |
December | 0.267154E+10 | 10868.30 | 15-DEC-07:01 | -8.1 |
Annual Sum or Average | 0.115880E+11 | |||
Minimum of Months | 36940063.05 | 3809.02 | -8.1 | |
Maximum of Months | 0.267738E+10 | 14535.89 | 23.30 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153129E+10 | 7377.02 | 01-JAN-12:02 | 11.05 |
February | 0.104323E+10 | 6032.61 | 19-FEB-11:13 | 11.33 |
March | 0.461712E+09 | 5286.06 | 26-MAR-15:53 | 20.60 |
April | 59281041.73 | 5041.81 | 16-APR-15:22 | 19.15 |
May | 31555451.07 | 4476.94 | 07-MAY-15:52 | 24.40 |
June | 23990023.39 | 4864.35 | 25-JUN-15:11 | 34.47 |
July | 33369955.81 | 5265.47 | 30-JUL-15:21 | 33.60 |
August | 23546104.46 | 4930.27 | 20-AUG-15:21 | 35.00 |
September | 29219115.02 | 5116.14 | 03-SEP-13:41 | 32.52 |
October | 0.178395E+09 | 6245.44 | 09-OCT-15:31 | 23.53 |
November | 0.651291E+09 | 6425.41 | 05-NOV-11:13 | 8.87 |
December | 0.154032E+10 | 7153.12 | 17-DEC-12:02 | 9.60 |
Annual Sum or Average | 0.560719E+10 | |||
Minimum of Months | 23546104.46 | 4476.94 | 8.87 | |
Maximum of Months | 0.154032E+10 | 7377.02 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.815050E+09 | 5056.69 | 01-JAN-11:53 | 10.60 |
February | 0.443832E+09 | 3939.20 | 19-FEB-13:42 | 15.92 |
March | 99099172.13 | 2699.28 | 06-MAR-08:06 | 1.75 |
April | 16406782.40 | 3014.56 | 16-APR-17:21 | 20.00 |
May | 16641587.06 | 2858.04 | 07-MAY-16:21 | 24.40 |
June | 19558073.55 | 3150.17 | 29-JUN-04:02 | 24.40 |
July | 26931281.81 | 3362.12 | 30-JUL-15:21 | 33.60 |
August | 22197965.77 | 3247.73 | 20-AUG-14:41 | 34.90 |
September | 27347811.03 | 3534.06 | 03-SEP-13:31 | 32.23 |
October | 60586113.18 | 5278.02 | 25-OCT-05:02 | -1.1 |
November | 0.154777E+09 | 4886.95 | 25-NOV-06:01 | 1.10 |
December | 0.728443E+09 | 4907.44 | 24-DEC-13:53 | 12.20 |
Annual Sum or Average | 0.243087E+10 | |||
Minimum of Months | 16406782.40 | 2699.28 | -1.1 | |
Maximum of Months | 0.815050E+09 | 5278.02 | 34.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12057907.92 | 16139.29 | 17-JAN-07:01 | -3.9 |
February | 6037445.83 | 16194.83 | 06-FEB-07:01 | -5.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 8650144.83 | 15872.53 | 26-DEC-07:02 | -1.8 |
Annual Sum or Average | 26745498.58 | |||
Minimum of Months | 0.00 | 0.00 | -5.4 | |
Maximum of Months | 12057907.92 | 16194.83 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.462969E+09 | 31330.36 | 17-JAN-06:01 | -3.4 |
February | 0.217176E+09 | 31428.65 | 06-FEB-06:01 | -4.6 |
March | 12242471.63 | 27387.88 | 06-MAR-07:03 | -0.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 3357836.34 | 21029.20 | 26-OCT-06:03 | -1.4 |
November | 57209733.92 | 29841.49 | 27-NOV-06:01 | -4.4 |
December | 0.419595E+09 | 31364.83 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.117255E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.6 | |
Maximum of Months | 0.462969E+09 | 31428.65 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171183E+10 | 11926.53 | 17-JAN-05:11 | -3.3 |
February | 0.102602E+10 | 11549.34 | 06-FEB-05:01 | -4.4 |
March | 0.277671E+09 | 10489.46 | 06-MAR-06:01 | -2.9 |
April | 23508798.74 | 8107.20 | 08-APR-06:03 | 1.78 |
May | 1223478.42 | 4187.81 | 06-MAY-06:03 | 5.78 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.109083E+09 | 10499.38 | 26-OCT-05:01 | -2.5 |
November | 0.425081E+09 | 11421.38 | 27-NOV-05:01 | -4.0 |
December | 0.175734E+10 | 11639.97 | 26-DEC-05:11 | -0.9 |
Annual Sum or Average | 0.533176E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.175734E+10 | 11926.53 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.824004E+09 | 10614.62 | 17-JAN-05:11 | -3.3 |
February | 0.430337E+09 | 10174.51 | 06-FEB-05:01 | -4.4 |
March | 93964756.83 | 9027.11 | 06-MAR-06:01 | -2.9 |
April | 4851902.85 | 5216.88 | 08-APR-05:12 | 2.43 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 55875857.13 | 9126.48 | 26-OCT-05:01 | -2.5 |
November | 0.148387E+09 | 9948.37 | 27-NOV-05:01 | -4.0 |
December | 0.785294E+09 | 10280.12 | 04-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.234271E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.824004E+09 | 10614.62 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.933451E+09 | 14277.95 | 17-JAN-05:11 | -3.3 |
February | 0.521372E+09 | 13821.43 | 06-FEB-05:01 | -4.4 |
March | 0.165176E+09 | 12541.80 | 04-MAR-06:01 | -1.7 |
April | 21100633.84 | 8134.77 | 08-APR-06:03 | 1.78 |
May | 3445899.58 | 6942.93 | 06-MAY-06:03 | 5.78 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 68686416.53 | 12556.70 | 26-OCT-05:01 | -2.5 |
November | 0.149542E+09 | 12767.98 | 27-NOV-05:01 | -4.0 |
December | 0.826874E+09 | 13937.11 | 26-DEC-05:11 | -0.9 |
Annual Sum or Average | 0.268965E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.933451E+09 | 14277.95 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.965292E+09 | 10590.53 | 17-JAN-05:11 | -3.3 |
February | 0.573822E+09 | 10115.69 | 06-FEB-05:01 | -4.4 |
March | 0.171338E+09 | 8832.21 | 04-MAR-06:01 | -1.7 |
April | 16433947.06 | 5159.36 | 08-APR-06:03 | 1.78 |
May | 2814212.23 | 4418.24 | 05-MAY-06:03 | 6.20 |
June | 311968.89 | 1559.84 | 09-JUN-06:03 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 70740267.32 | 8915.27 | 26-OCT-05:01 | -2.5 |
November | 0.239183E+09 | 9733.66 | 27-NOV-05:01 | -4.0 |
December | 0.951343E+09 | 10233.06 | 04-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.299128E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.965292E+09 | 10590.53 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.579861E+09 | 8826.71 | 17-JAN-06:01 | -3.4 |
February | 0.374267E+09 | 8970.38 | 06-FEB-05:01 | -4.4 |
March | 67144954.73 | 8205.02 | 06-MAR-06:01 | -2.9 |
April | 1167770.42 | 4148.08 | 08-APR-06:03 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 2054151.39 | 4674.49 | 26-OCT-06:03 | -1.4 |
November | 31347335.12 | 8053.45 | 27-NOV-06:01 | -4.4 |
December | 0.415115E+09 | 8460.84 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.147096E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.579861E+09 | 8970.38 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187488E+09 | 6805.05 | 17-JAN-06:01 | -3.4 |
February | 78956389.39 | 6821.52 | 06-FEB-06:01 | -4.6 |
March | 8647018.06 | 6075.73 | 04-MAR-06:01 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 1175902.89 | 4429.35 | 26-OCT-06:03 | -1.4 |
November | 1547549.83 | 4205.98 | 27-NOV-07:03 | -4.2 |
December | 0.104103E+09 | 6545.44 | 27-DEC-06:01 | -4.0 |
Annual Sum or Average | 0.381918E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.6 | |
Maximum of Months | 0.187488E+09 | 6821.52 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150659E+10 | 11437.26 | 20-JAN-07:10 | -4.3 |
February | 0.103021E+10 | 11468.95 | 06-FEB-07:10 | -5.4 |
March | 0.879836E+09 | 10454.23 | 30-MAR-06:10 | -1.7 |
April | 0.401848E+09 | 9684.17 | 06-APR-06:10 | 1.88 |
May | 0.160712E+09 | 9435.62 | 05-MAY-06:03 | 6.20 |
June | 16412186.50 | 6596.91 | 09-JUN-06:07 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 320728.49 | 1496.79 | 20-SEP-06:08 | 11.33 |
October | 0.334009E+09 | 10530.16 | 26-OCT-07:00 | -2.8 |
November | 0.554371E+09 | 10236.15 | 27-NOV-07:10 | -4.2 |
December | 0.121127E+10 | 11414.36 | 22-DEC-07:10 | -6.1 |
Annual Sum or Average | 0.609557E+10 | |||
Minimum of Months | 0.00 | 0.00 | -6.1 | |
Maximum of Months | 0.150659E+10 | 11468.95 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189053E+09 | 6664.16 | 17-JAN-06:01 | -3.4 |
February | 0.103060E+09 | 6745.98 | 06-FEB-06:01 | -4.6 |
March | 20930315.16 | 6415.85 | 04-MAR-06:01 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 1706409.52 | 4425.33 | 26-OCT-06:03 | -1.4 |
November | 4811918.98 | 4724.47 | 27-NOV-07:03 | -4.2 |
December | 0.120547E+09 | 6379.74 | 09-DEC-06:01 | -4.2 |
Annual Sum or Average | 0.440108E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.6 | |
Maximum of Months | 0.189053E+09 | 6745.98 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.546168E+09 | 9800.90 | 17-JAN-05:02 | -3.3 |
February | 0.275755E+09 | 9883.66 | 06-FEB-05:01 | -4.4 |
March | 35743070.78 | 8674.78 | 06-MAR-06:01 | -2.9 |
April | 393938.44 | 2626.26 | 08-APR-06:03 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 11290757.43 | 7822.25 | 26-OCT-06:03 | -1.4 |
November | 64954968.30 | 9032.77 | 27-NOV-06:01 | -4.4 |
December | 0.504129E+09 | 9237.82 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.143844E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.546168E+09 | 9883.66 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.275274E+09 | 7764.69 | 17-JAN-05:02 | -3.3 |
February | 0.107210E+09 | 7834.26 | 06-FEB-05:01 | -4.4 |
March | 14288016.33 | 6726.46 | 06-MAR-06:01 | -2.9 |
April | 129421.37 | 862.81 | 08-APR-06:03 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 7531684.82 | 5034.31 | 26-OCT-06:03 | -1.4 |
November | 19912600.53 | 6803.17 | 27-NOV-06:01 | -4.4 |
December | 0.235236E+09 | 7050.22 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.659581E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.275274E+09 | 7834.26 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258629E+09 | 11776.28 | 17-JAN-05:02 | -3.3 |
February | 0.110970E+09 | 11806.62 | 06-FEB-05:01 | -4.4 |
March | 15125347.00 | 9879.53 | 04-MAR-06:01 | -1.7 |
April | 393888.45 | 2625.92 | 08-APR-06:03 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 6407148.87 | 7759.71 | 26-OCT-06:03 | -1.4 |
November | 12025798.27 | 10561.23 | 27-NOV-06:01 | -4.4 |
December | 0.209932E+09 | 11295.56 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.613483E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.258629E+09 | 11806.62 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305014E+09 | 7714.87 | 17-JAN-05:02 | -3.3 |
February | 0.151504E+09 | 7756.63 | 06-FEB-05:01 | -4.4 |
March | 27188877.51 | 6734.69 | 04-MAR-06:01 | -1.7 |
April | 920582.97 | 2978.31 | 08-APR-06:03 | 1.78 |
May | 46361.84 | 309.08 | 05-MAY-06:03 | 6.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 9011687.47 | 5018.57 | 26-OCT-06:03 | -1.4 |
November | 36388405.45 | 6910.97 | 28-NOV-06:01 | -2.1 |
December | 0.272526E+09 | 6968.92 | 07-DEC-06:01 | -4.7 |
Annual Sum or Average | 0.802601E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.7 | |
Maximum of Months | 0.305014E+09 | 7756.63 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.958041E+09 | 1592.13 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.834930E+09 | 1388.60 | 16-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.938595E+09 | 1111.04 | 20-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.803816E+09 | 759.45 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.857666E+09 | 907.52 | 22-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.839858E+09 | 907.52 | 01-JUN-15:00 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.796086E+09 | 907.52 | 07-JUL-15:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.889848E+09 | 759.45 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.825875E+09 | 1388.60 | 08-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.901449E+09 | 1388.60 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.945537E+09 | 1592.13 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.972356E+09 | 1592.13 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.105641E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.796086E+09 | 759.45 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.972356E+09 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.596070E+09 | 1007.95 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.522710E+09 | 879.10 | 16-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.591419E+09 | 703.38 | 14-MAR-15:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.511352E+09 | 480.79 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.547600E+09 | 527.66 | 03-MAY-15:20 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.536456E+09 | 574.53 | 01-JUN-15:00 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.507351E+09 | 574.53 | 07-JUL-15:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.565650E+09 | 480.79 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.521182E+09 | 879.10 | 08-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.561288E+09 | 703.38 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.594430E+09 | 1007.95 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.604653E+09 | 1007.95 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.666016E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.507351E+09 | 480.79 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.604653E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.913783E+09 | 1388.60 | 04-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.811948E+09 | 1388.60 | 16-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.930884E+09 | 1111.04 | 20-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.807344E+09 | 759.45 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.864781E+09 | 907.52 | 22-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.851009E+09 | 907.52 | 01-JUN-15:00 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.803483E+09 | 907.52 | 07-JUL-15:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.894510E+09 | 759.45 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.822857E+09 | 1388.60 | 08-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.874897E+09 | 1388.60 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.910149E+09 | 1592.13 | 08-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.916166E+09 | 1592.13 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.104018E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.803483E+09 | 759.45 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.930884E+09 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.587514E+09 | 879.04 | 04-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.518172E+09 | 879.04 | 16-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.589783E+09 | 832.18 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.507580E+09 | 480.76 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.541572E+09 | 574.49 | 22-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.533765E+09 | 703.34 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.505478E+09 | 574.49 | 07-JUL-15:39 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.563653E+09 | 527.63 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.520282E+09 | 879.04 | 08-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.561918E+09 | 879.04 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.577785E+09 | 1007.89 | 09-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.589610E+09 | 1007.89 | 01-DEC-16:49 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.659711E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.505478E+09 | 480.76 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.589783E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.954705E+09 | 1592.13 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.832296E+09 | 1388.60 | 16-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.936819E+09 | 1111.04 | 20-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.803481E+09 | 759.45 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.856855E+09 | 907.52 | 22-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.838886E+09 | 907.52 | 01-JUN-15:00 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.795600E+09 | 907.52 | 07-JUL-15:39 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.889813E+09 | 759.45 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.824407E+09 | 1388.60 | 08-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.899835E+09 | 1388.60 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.942752E+09 | 1592.13 | 08-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.968352E+09 | 1592.13 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.105438E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.795600E+09 | 759.45 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.968352E+09 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.594804E+09 | 1007.95 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.522262E+09 | 879.10 | 16-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.590357E+09 | 703.38 | 14-MAR-15:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.510874E+09 | 480.79 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.547007E+09 | 527.66 | 03-MAY-15:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.536082E+09 | 574.53 | 01-JUN-15:00 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.506979E+09 | 574.53 | 07-JUL-15:39 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.565419E+09 | 480.79 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.520450E+09 | 879.10 | 08-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.559881E+09 | 703.38 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.593259E+09 | 1007.95 | 08-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.603165E+09 | 1007.95 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.665054E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.506979E+09 | 480.79 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.603165E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.912701E+09 | 1388.60 | 04-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.810711E+09 | 1388.60 | 16-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.929377E+09 | 1111.04 | 20-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.806597E+09 | 759.45 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.863999E+09 | 907.52 | 22-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.849281E+09 | 907.52 | 01-JUN-15:00 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.802580E+09 | 907.52 | 07-JUL-15:39 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.893638E+09 | 759.45 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.821742E+09 | 1388.60 | 08-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.874134E+09 | 1388.60 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.909313E+09 | 1592.13 | 08-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.915606E+09 | 1592.13 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.103897E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.802580E+09 | 759.45 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.929377E+09 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.586287E+09 | 879.04 | 04-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.516774E+09 | 879.04 | 16-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.588993E+09 | 703.34 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.507163E+09 | 480.76 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.541196E+09 | 574.49 | 22-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.533163E+09 | 703.34 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.504953E+09 | 574.49 | 07-JUL-15:50 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.563203E+09 | 527.63 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.519379E+09 | 879.04 | 08-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.561158E+09 | 879.04 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.577111E+09 | 1007.89 | 09-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.588568E+09 | 1007.89 | 01-DEC-16:49 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.658795E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.504953E+09 | 480.76 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.588993E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.958041E+09 | 1592.13 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.834930E+09 | 1388.60 | 16-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.938595E+09 | 1111.04 | 20-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.803816E+09 | 759.45 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.857666E+09 | 907.52 | 22-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.839858E+09 | 907.52 | 01-JUN-15:00 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.796086E+09 | 907.52 | 07-JUL-15:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.889848E+09 | 759.45 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.825875E+09 | 1388.60 | 08-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.901425E+09 | 1388.60 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.945537E+09 | 1592.13 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.972356E+09 | 1592.13 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.105640E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.796086E+09 | 759.45 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.972356E+09 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.596070E+09 | 1007.95 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.522710E+09 | 879.10 | 16-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.591419E+09 | 703.38 | 14-MAR-15:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.511352E+09 | 480.79 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.547600E+09 | 527.66 | 03-MAY-15:20 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.536456E+09 | 574.53 | 01-JUN-15:00 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.507351E+09 | 574.53 | 07-JUL-15:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.565650E+09 | 480.79 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.521182E+09 | 879.10 | 08-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.561288E+09 | 703.38 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.594430E+09 | 1007.95 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.604653E+09 | 1007.95 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.666016E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.507351E+09 | 480.79 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.604653E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.913783E+09 | 1388.60 | 04-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.811948E+09 | 1388.60 | 16-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.930884E+09 | 1111.04 | 20-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.807344E+09 | 759.45 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.864781E+09 | 907.52 | 22-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.851009E+09 | 907.52 | 01-JUN-15:00 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.803483E+09 | 907.52 | 07-JUL-15:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.894510E+09 | 759.45 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.822857E+09 | 1388.60 | 08-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.874897E+09 | 1388.60 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.910149E+09 | 1592.13 | 08-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.916166E+09 | 1592.13 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.104018E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.803483E+09 | 759.45 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.930884E+09 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.587514E+09 | 879.04 | 04-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.518172E+09 | 879.04 | 16-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.589783E+09 | 832.18 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.507580E+09 | 480.76 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.541572E+09 | 574.49 | 22-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.533765E+09 | 703.34 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.505478E+09 | 574.49 | 07-JUL-15:39 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.563653E+09 | 527.63 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.520282E+09 | 879.04 | 08-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.561918E+09 | 879.04 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.577785E+09 | 1007.89 | 09-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.589610E+09 | 1007.89 | 01-DEC-16:49 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.659711E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.505478E+09 | 480.76 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.589783E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.958041E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736080E+09 |
February | 0.901968E+09 | 0.834930E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696436E+09 |
March | 0.107774E+10 | 0.938595E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691085E+09 |
April | 0.956342E+09 | 0.803816E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1400124.21 | 0.510049E+09 |
May | 0.103597E+10 | 0.857666E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12801761.80 | 0.357681E+09 |
June | 0.103308E+10 | 0.839858E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62990354.20 | 0.195615E+09 |
July | 0.959235E+09 | 0.796086E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90153410.72 | 0.114551E+09 |
August | 0.107774E+10 | 0.889848E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46497930.16 | 0.148544E+09 |
September | 0.956342E+09 | 0.825875E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15528647.20 | 0.214731E+09 |
October | 0.994195E+09 | 0.901449E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3768638.44 | 0.381749E+09 |
November | 0.984487E+09 | 0.945537E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593290E+09 |
December | 0.959235E+09 | 0.972356E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670943E+09 |
Annual Sum or Average | 0.119305E+11 | 0.105641E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233141E+09 | 0.531076E+10 |
Minimum of Months | 0.901968E+09 | 0.796086E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114551E+09 |
Maximum of Months | 0.107774E+10 | 0.972356E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90153410.72 | 0.736080E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.596070E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503069E+09 |
February | 0.571020E+09 | 0.522710E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474621E+09 |
March | 0.682301E+09 | 0.591419E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473706E+09 |
April | 0.605444E+09 | 0.511352E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 944394.36 | 0.359523E+09 |
May | 0.655854E+09 | 0.547600E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8451511.22 | 0.247265E+09 |
June | 0.654023E+09 | 0.536456E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42903226.53 | 0.131429E+09 |
July | 0.607275E+09 | 0.507351E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60822173.15 | 79965370.11 |
August | 0.682301E+09 | 0.565650E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31343131.28 | 0.102944E+09 |
September | 0.605444E+09 | 0.521182E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10327275.51 | 0.146199E+09 |
October | 0.629407E+09 | 0.561288E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2431883.25 | 0.264816E+09 |
November | 0.623262E+09 | 0.594430E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409316E+09 |
December | 0.607275E+09 | 0.604653E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456667E+09 |
Annual Sum or Average | 0.755301E+10 | 0.666016E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157224E+09 | 0.364952E+10 |
Minimum of Months | 0.571020E+09 | 0.507351E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79965370.11 |
Maximum of Months | 0.682301E+09 | 0.604653E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60822173.15 | 0.503069E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.913783E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.811028E+09 |
February | 0.901968E+09 | 0.811948E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760511E+09 |
March | 0.107774E+10 | 0.930884E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735495E+09 |
April | 0.956342E+09 | 0.807344E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1289382.47 | 0.535340E+09 |
May | 0.103597E+10 | 0.864781E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11923386.26 | 0.360787E+09 |
June | 0.103308E+10 | 0.851009E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64580263.27 | 0.190981E+09 |
July | 0.959235E+09 | 0.803483E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90372519.43 | 0.113244E+09 |
August | 0.107774E+10 | 0.894510E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45512459.54 | 0.152706E+09 |
September | 0.956342E+09 | 0.822857E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14147978.58 | 0.229254E+09 |
October | 0.994195E+09 | 0.874897E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3289416.81 | 0.420601E+09 |
November | 0.984487E+09 | 0.910149E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668533E+09 |
December | 0.959235E+09 | 0.916166E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745023E+09 |
Annual Sum or Average | 0.119305E+11 | 0.104018E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231115E+09 | 0.572350E+10 |
Minimum of Months | 0.901968E+09 | 0.803483E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113244E+09 |
Maximum of Months | 0.107774E+10 | 0.930884E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90372519.43 | 0.811028E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.587514E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505622E+09 |
February | 0.570983E+09 | 0.518172E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479703E+09 |
March | 0.682256E+09 | 0.589783E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474834E+09 |
April | 0.605404E+09 | 0.507580E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 850751.58 | 0.356866E+09 |
May | 0.655811E+09 | 0.541572E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7982080.12 | 0.244534E+09 |
June | 0.653980E+09 | 0.533765E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41339619.08 | 0.133740E+09 |
July | 0.607235E+09 | 0.505478E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60567548.35 | 78927091.52 |
August | 0.682256E+09 | 0.563653E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30765858.07 | 0.103247E+09 |
September | 0.605404E+09 | 0.520282E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10132073.86 | 0.149178E+09 |
October | 0.629366E+09 | 0.561918E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2395529.76 | 0.264198E+09 |
November | 0.623221E+09 | 0.577785E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410796E+09 |
December | 0.607235E+09 | 0.589610E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461847E+09 |
Annual Sum or Average | 0.755252E+10 | 0.659711E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154033E+09 | 0.366349E+10 |
Minimum of Months | 0.570983E+09 | 0.505478E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78927091.52 |
Maximum of Months | 0.682256E+09 | 0.589783E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60567548.35 | 0.505622E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.954705E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421812E+09 |
February | 0.901968E+09 | 0.832296E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388945E+09 |
March | 0.107774E+10 | 0.936819E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375946E+09 |
April | 0.956342E+09 | 0.803481E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 984683.46 | 0.273091E+09 |
May | 0.103597E+10 | 0.856855E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8794830.28 | 0.190762E+09 |
June | 0.103308E+10 | 0.838886E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36139355.13 | 0.104853E+09 |
July | 0.959235E+09 | 0.795600E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51423800.26 | 59693379.83 |
August | 0.107774E+10 | 0.889813E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26253326.21 | 80784164.03 |
September | 0.956342E+09 | 0.824407E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8880254.46 | 0.120980E+09 |
October | 0.994195E+09 | 0.899835E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2137183.86 | 0.221742E+09 |
November | 0.984487E+09 | 0.942752E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351787E+09 |
December | 0.959235E+09 | 0.968352E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392317E+09 |
Annual Sum or Average | 0.119305E+11 | 0.105438E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134613E+09 | 0.298271E+10 |
Minimum of Months | 0.901968E+09 | 0.795600E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59693379.83 |
Maximum of Months | 0.107774E+10 | 0.968352E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51423800.26 | 0.421812E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.594804E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293785E+09 |
February | 0.571020E+09 | 0.522262E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271229E+09 |
March | 0.682301E+09 | 0.590357E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268523E+09 |
April | 0.605444E+09 | 0.510874E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 529379.47 | 0.203091E+09 |
May | 0.655854E+09 | 0.547007E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4648379.10 | 0.139839E+09 |
June | 0.654023E+09 | 0.536082E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22978212.46 | 74932379.33 |
July | 0.607275E+09 | 0.506979E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32290406.88 | 46075915.32 |
August | 0.682301E+09 | 0.565419E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16516147.44 | 60839390.88 |
September | 0.605444E+09 | 0.520450E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5519767.02 | 87207894.52 |
October | 0.629407E+09 | 0.559881E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1317608.07 | 0.158335E+09 |
November | 0.623262E+09 | 0.593259E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247772E+09 |
December | 0.607275E+09 | 0.603165E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271859E+09 |
Annual Sum or Average | 0.755301E+10 | 0.665054E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83799900.45 | 0.212349E+10 |
Minimum of Months | 0.571020E+09 | 0.506979E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46075915.32 |
Maximum of Months | 0.682301E+09 | 0.603165E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32290406.88 | 0.293785E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.912701E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449808E+10 |
February | 0.901968E+09 | 0.810711E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368923E+10 |
March | 0.107774E+10 | 0.929377E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323068E+10 |
April | 0.956342E+09 | 0.806597E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20010075.70 | 0.192468E+10 |
May | 0.103597E+10 | 0.863999E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146686E+09 | 0.132143E+10 |
June | 0.103308E+10 | 0.849281E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.920325E+09 | 0.524816E+09 |
July | 0.959235E+09 | 0.802580E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101530E+10 | 0.208514E+09 |
August | 0.107774E+10 | 0.893638E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780370E+09 | 0.430526E+09 |
September | 0.956342E+09 | 0.821742E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307881E+09 | 0.720205E+09 |
October | 0.994195E+09 | 0.874134E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46295777.68 | 0.213896E+10 |
November | 0.984487E+09 | 0.909313E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356831E+10 |
December | 0.959235E+09 | 0.915606E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463609E+10 |
Annual Sum or Average | 0.119305E+11 | 0.103897E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323687E+10 | 0.268915E+11 |
Minimum of Months | 0.901968E+09 | 0.802580E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208514E+09 |
Maximum of Months | 0.107774E+10 | 0.929377E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101530E+10 | 0.463609E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.586287E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294788E+09 |
February | 0.570983E+09 | 0.516774E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274244E+09 |
March | 0.682256E+09 | 0.588993E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267412E+09 |
April | 0.605404E+09 | 0.507163E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 482118.04 | 0.201978E+09 |
May | 0.655811E+09 | 0.541196E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4395154.04 | 0.138269E+09 |
June | 0.653980E+09 | 0.533163E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22183929.70 | 76704016.89 |
July | 0.607235E+09 | 0.504953E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32433141.33 | 44973032.43 |
August | 0.682256E+09 | 0.563203E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16381859.40 | 60718156.77 |
September | 0.605404E+09 | 0.519379E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5398828.71 | 89049661.61 |
October | 0.629366E+09 | 0.561158E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1277547.47 | 0.158710E+09 |
November | 0.623221E+09 | 0.577111E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247237E+09 |
December | 0.607235E+09 | 0.588568E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273797E+09 |
Annual Sum or Average | 0.755252E+10 | 0.658795E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82552578.70 | 0.212788E+10 |
Minimum of Months | 0.570983E+09 | 0.504953E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44973032.43 |
Maximum of Months | 0.682256E+09 | 0.588993E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32433141.33 | 0.294788E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.958041E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658171E+09 |
February | 0.901968E+09 | 0.834930E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618677E+09 |
March | 0.107774E+10 | 0.938595E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614250E+09 |
April | 0.956342E+09 | 0.803816E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1195737.09 | 0.448801E+09 |
May | 0.103597E+10 | 0.857666E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11189270.22 | 0.312726E+09 |
June | 0.103308E+10 | 0.839858E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53338421.54 | 0.170339E+09 |
July | 0.959235E+09 | 0.796086E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75663730.64 | 98829539.59 |
August | 0.107774E+10 | 0.889848E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39149982.42 | 0.129008E+09 |
September | 0.956342E+09 | 0.825875E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13193268.73 | 0.188926E+09 |
October | 0.994195E+09 | 0.901425E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3201821.04 | 0.341599E+09 |
November | 0.984487E+09 | 0.945537E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537467E+09 |
December | 0.959235E+09 | 0.972356E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604247E+09 |
Annual Sum or Average | 0.119305E+11 | 0.105640E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196932E+09 | 0.472304E+10 |
Minimum of Months | 0.901968E+09 | 0.796086E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98829539.59 |
Maximum of Months | 0.107774E+10 | 0.972356E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75663730.64 | 0.658171E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.596070E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448127E+09 |
February | 0.421807E+09 | 0.522710E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419613E+09 |
March | 0.502994E+09 | 0.591419E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416579E+09 |
April | 0.447140E+09 | 0.511352E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 836658.24 | 0.311662E+09 |
May | 0.484071E+09 | 0.547600E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7481856.25 | 0.213617E+09 |
June | 0.482240E+09 | 0.536456E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36712160.82 | 0.113794E+09 |
July | 0.448971E+09 | 0.507351E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51336691.94 | 68359642.92 |
August | 0.502994E+09 | 0.565650E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26518311.27 | 88847590.21 |
September | 0.447140E+09 | 0.521182E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8875887.36 | 0.127649E+09 |
October | 0.465148E+09 | 0.561288E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2100695.73 | 0.233698E+09 |
November | 0.460569E+09 | 0.594430E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366855E+09 |
December | 0.448971E+09 | 0.604653E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409943E+09 |
Annual Sum or Average | 0.557719E+10 | 0.666016E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133862E+09 | 0.321874E+10 |
Minimum of Months | 0.421807E+09 | 0.507351E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68359642.92 |
Maximum of Months | 0.502994E+09 | 0.604653E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51336691.94 | 0.448127E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.913783E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720723E+09 |
February | 0.901968E+09 | 0.811948E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671197E+09 |
March | 0.107774E+10 | 0.930884E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648115E+09 |
April | 0.956342E+09 | 0.807344E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1106488.93 | 0.468090E+09 |
May | 0.103597E+10 | 0.864781E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10247245.27 | 0.315263E+09 |
June | 0.103308E+10 | 0.851009E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54802895.86 | 0.166834E+09 |
July | 0.959235E+09 | 0.803483E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75781512.88 | 97846518.63 |
August | 0.107774E+10 | 0.894510E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38261991.36 | 0.132669E+09 |
September | 0.956342E+09 | 0.822857E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11850867.43 | 0.200692E+09 |
October | 0.994195E+09 | 0.874897E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2659140.10 | 0.371117E+09 |
November | 0.984487E+09 | 0.910149E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595399E+09 |
December | 0.959235E+09 | 0.916166E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664575E+09 |
Annual Sum or Average | 0.119305E+11 | 0.104018E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194710E+09 | 0.505252E+10 |
Minimum of Months | 0.901968E+09 | 0.803483E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97846518.63 |
Maximum of Months | 0.107774E+10 | 0.930884E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75781512.88 | 0.720723E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.587514E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450260E+09 |
February | 0.570983E+09 | 0.518172E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423827E+09 |
March | 0.682256E+09 | 0.589783E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418868E+09 |
April | 0.605404E+09 | 0.507580E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 730019.37 | 0.311936E+09 |
May | 0.655811E+09 | 0.541572E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6712386.29 | 0.214029E+09 |
June | 0.653980E+09 | 0.533765E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34664214.33 | 0.116845E+09 |
July | 0.607235E+09 | 0.505478E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50298514.83 | 68174758.25 |
August | 0.682256E+09 | 0.563653E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25631827.48 | 89871298.42 |
September | 0.605404E+09 | 0.520282E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8527104.37 | 0.131199E+09 |
October | 0.629366E+09 | 0.561918E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1978143.39 | 0.234432E+09 |
November | 0.623221E+09 | 0.577785E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368503E+09 |
December | 0.607235E+09 | 0.589610E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413773E+09 |
Annual Sum or Average | 0.755252E+10 | 0.659711E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128542E+09 | 0.324172E+10 |
Minimum of Months | 0.570983E+09 | 0.505478E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68174758.25 |
Maximum of Months | 0.682256E+09 | 0.589783E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50298514.83 | 0.450260E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.958573E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892559E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.873368E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489737.10 | 0.630823E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11515049.95 | 0.432859E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62671410.29 | 0.230604E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90486795.97 | 0.129694E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42825819.76 | 0.176553E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12530160.40 | 0.266932E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2283585.02 | 0.494578E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789271E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886419E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222803E+09 | 0.676223E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129694E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90486795.97 | 0.958573E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116565E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109798E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108740E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 692177.06 | 0.792950E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15009048.68 | 0.549042E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80517485.89 | 0.293560E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116200E+09 | 0.166215E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55333873.03 | 0.223987E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16664601.17 | 0.334428E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3191231.14 | 0.611599E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962929E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107508E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287608E+09 | 0.836082E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166215E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116200E+09 | 0.116565E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115263E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109807E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109714E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26370.73 | 0.823253E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7786230.58 | 0.564789E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71085936.86 | 0.293006E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102196E+09 | 0.164332E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48022895.04 | 0.221850E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11288755.02 | 0.337110E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1601833.08 | 0.607517E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.948465E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105105E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242008E+09 | 0.835922E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164332E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102196E+09 | 0.115263E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1935.31 | 16-JAN-18:00 |
February | 1306.65 | 01-FEB-10:09 | 1388.60 | 16-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1556.40 | 05-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1111.04 | 20-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1399.66 | 14-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 759.45 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.78 | 29-APR-16:00 | 1656.26 | 07-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 907.52 | 22-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.66 | 14-MAY-17:00 | 1045.46 | 03-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 907.52 | 01-JUN-15:00 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 481.47 | 18-JUN-16:04 | 767.88 | 10-JUN-01:00 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 07-JUL-15:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 616.64 | 04-JUL-14:51 | 461.11 | 15-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 759.45 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.78 | 20-AUG-16:54 | 423.68 | 22-AUG-22:00 |
September | 1306.65 | 01-SEP-09:09 | 1388.60 | 08-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.83 | 03-SEP-14:36 | 577.97 | 07-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 1388.60 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.24 | 01-OCT-16:00 | 977.00 | 11-OCT-23:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1660.54 | 03-NOV-21:03 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2158.77 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.68 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 616.64 | 2158.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1007.95 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1302.81 | 16-JAN-18:00 |
February | 827.22 | 01-FEB-10:09 | 879.10 | 16-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1046.27 | 05-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 703.38 | 14-MAR-15:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 942.14 | 14-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 480.79 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.65 | 01-APR-17:50 | 1156.68 | 23-APR-09:10 |
May | 827.22 | 01-MAY-09:09 | 527.66 | 03-MAY-15:20 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.72 | 14-MAY-16:40 | 687.77 | 03-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 574.53 | 01-JUN-15:00 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.82 | 18-JUN-16:10 | 509.36 | 04-JUN-17:00 |
July | 827.22 | 03-JUL-09:09 | 574.53 | 07-JUL-15:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 438.17 | 04-JUL-15:04 | 315.64 | 15-JUL-19:00 |
August | 827.22 | 01-AUG-09:09 | 480.79 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.61 | 20-AUG-16:55 | 378.94 | 27-AUG-07:40 |
September | 827.22 | 01-SEP-09:09 | 879.10 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.55 | 03-SEP-14:36 | 405.09 | 17-SEP-20:00 |
October | 827.22 | 02-OCT-09:09 | 703.38 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.41 | 01-OCT-16:00 | 649.98 | 11-OCT-23:00 |
November | 827.22 | 01-NOV-09:09 | 1007.95 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1107.69 | 03-NOV-21:03 |
December | 827.22 | 01-DEC-10:09 | 1007.95 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1441.58 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.64 | |||||
Maximum of Months | 827.22 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 438.17 | 1441.58 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1388.60 | 04-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2077.99 | 16-JAN-18:00 |
February | 1306.65 | 01-FEB-10:09 | 1388.60 | 16-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1672.77 | 05-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1111.04 | 20-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1452.11 | 14-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 759.45 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.78 | 29-APR-16:00 | 1691.69 | 07-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 907.52 | 22-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.61 | 14-MAY-16:40 | 1033.70 | 03-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 907.52 | 01-JUN-15:00 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 489.21 | 18-JUN-16:04 | 758.54 | 10-JUN-01:00 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 07-JUL-15:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 614.13 | 04-JUL-15:04 | 466.06 | 15-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 759.45 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.41 | 20-AUG-16:54 | 437.15 | 22-AUG-22:00 |
September | 1306.65 | 01-SEP-09:09 | 1388.60 | 08-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.41 | 03-SEP-14:36 | 654.98 | 17-SEP-20:00 |
October | 1306.65 | 02-OCT-09:09 | 1388.60 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.20 | 11-OCT-13:00 | 1005.28 | 11-OCT-23:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 08-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1736.12 | 03-NOV-21:03 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2257.85 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.15 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 614.13 | 2257.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 879.04 | 04-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1327.50 | 16-JAN-18:00 |
February | 827.17 | 01-FEB-10:09 | 879.04 | 16-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1075.34 | 05-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 832.18 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 939.32 | 14-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 480.76 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.86 | 29-APR-16:00 | 1290.65 | 15-APR-17:08 |
May | 827.17 | 01-MAY-09:09 | 574.49 | 22-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.54 | 14-MAY-17:16 | 689.72 | 03-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 703.34 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 294.81 | 18-JUN-16:10 | 537.60 | 10-JUN-01:00 |
July | 827.17 | 03-JUL-09:09 | 574.49 | 07-JUL-15:39 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 398.75 | 04-JUL-15:10 | 323.58 | 15-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 527.63 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.65 | 20-AUG-16:54 | 297.00 | 08-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 879.04 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.61 | 03-SEP-14:36 | 444.27 | 17-SEP-20:00 |
October | 827.17 | 02-OCT-09:09 | 879.04 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.57 | 11-OCT-13:00 | 661.01 | 11-OCT-23:00 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 09-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1119.81 | 03-NOV-21:10 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 01-DEC-16:49 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1454.34 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.00 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 398.75 | 1454.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1186.66 | 16-JAN-18:00 |
February | 1306.65 | 01-FEB-10:09 | 1388.60 | 16-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 921.72 | 05-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1111.04 | 20-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 778.15 | 14-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 759.45 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.79 | 01-APR-17:01 | 909.67 | 07-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 907.52 | 22-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.33 | 14-MAY-17:10 | 579.67 | 03-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 907.52 | 01-JUN-15:00 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.14 | 18-JUN-16:00 | 438.44 | 10-JUN-01:30 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 07-JUL-15:39 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.96 | 04-JUL-14:53 | 239.04 | 15-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 759.45 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.32 | 05-AUG-17:02 | 240.88 | 22-AUG-22:00 |
September | 1306.65 | 01-SEP-09:09 | 1388.60 | 08-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.64 | 03-SEP-15:00 | 340.50 | 07-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 1388.60 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.27 | 01-OCT-16:00 | 557.58 | 11-OCT-23:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 08-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 970.66 | 03-NOV-24:00 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1304.09 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.04 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 352.96 | 1304.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1007.95 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 821.57 | 16-JAN-18:00 |
February | 827.22 | 01-FEB-10:09 | 879.10 | 16-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 638.70 | 05-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 703.38 | 14-MAR-15:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 568.12 | 14-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 480.79 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.89 | 01-APR-17:50 | 639.00 | 07-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 527.66 | 03-MAY-15:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.42 | 14-MAY-17:10 | 396.02 | 03-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 574.53 | 01-JUN-15:00 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.07 | 18-JUN-15:50 | 302.98 | 10-JUN-01:00 |
July | 827.22 | 03-JUL-09:09 | 574.53 | 07-JUL-15:39 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.02 | 04-JUL-14:53 | 176.14 | 15-JUL-19:00 |
August | 827.22 | 01-AUG-09:09 | 480.79 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.84 | 20-AUG-16:51 | 182.25 | 27-AUG-08:10 |
September | 827.22 | 01-SEP-09:09 | 879.10 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.66 | 03-SEP-14:56 | 246.16 | 18-SEP-01:00 |
October | 827.22 | 02-OCT-09:09 | 703.38 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 01-OCT-16:20 | 382.08 | 11-OCT-23:00 |
November | 827.22 | 01-NOV-09:09 | 1007.95 | 08-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 659.53 | 03-NOV-24:00 |
December | 827.22 | 01-DEC-10:09 | 1007.95 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 895.21 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.14 | |||||
Maximum of Months | 827.22 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 239.02 | 895.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1388.60 | 04-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 19258.14 | 30-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 1388.60 | 16-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 18487.24 | 06-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1111.04 | 20-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 15635.25 | 30-MAR-06:03 |
April | 1306.65 | 03-APR-09:09 | 759.45 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1404.60 | 13-APR-17:00 | 13261.02 | 06-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 907.52 | 22-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3988.77 | 19-MAY-16:10 | 10789.45 | 04-MAY-06:10 |
June | 1306.65 | 01-JUN-09:09 | 907.52 | 01-JUN-15:00 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9153.59 | 28-JUN-16:03 | 8400.53 | 09-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 07-JUL-15:39 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8268.34 | 21-JUL-16:05 | 3328.51 | 17-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 759.45 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6737.22 | 01-AUG-16:05 | 6465.52 | 31-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 1388.60 | 08-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4351.11 | 20-SEP-17:00 | 8011.12 | 20-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1388.60 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2110.12 | 06-OCT-16:10 | 16266.54 | 27-OCT-06:55 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 08-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 18020.17 | 27-NOV-07:03 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 20806.55 | 15-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3328.51 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9153.59 | 20806.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 879.04 | 04-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 832.65 | 16-JAN-18:00 |
February | 827.17 | 01-FEB-10:09 | 879.04 | 16-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 651.34 | 05-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 703.34 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 558.05 | 14-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 480.76 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 29-APR-16:00 | 676.26 | 15-APR-17:10 |
May | 827.17 | 01-MAY-09:09 | 574.49 | 22-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.38 | 14-MAY-17:05 | 403.26 | 18-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 703.34 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.65 | 18-JUN-16:00 | 316.26 | 10-JUN-01:00 |
July | 827.17 | 03-JUL-09:09 | 574.49 | 07-JUL-15:50 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.12 | 04-JUL-14:53 | 175.00 | 15-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 527.63 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.95 | 20-AUG-17:00 | 177.89 | 08-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 879.04 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.77 | 03-SEP-14:56 | 253.67 | 17-SEP-20:00 |
October | 827.17 | 02-OCT-09:09 | 879.04 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.12 | 11-OCT-13:00 | 389.51 | 11-OCT-23:00 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 09-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 678.34 | 03-NOV-24:00 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 01-DEC-16:49 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 902.41 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.00 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 229.12 | 902.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1795.42 | 16-JAN-18:00 |
February | 1306.65 | 01-FEB-10:09 | 1388.60 | 16-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1425.84 | 05-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1111.04 | 20-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1267.74 | 14-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 759.45 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.74 | 29-APR-16:00 | 1452.35 | 07-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 907.52 | 22-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.45 | 14-MAY-17:10 | 919.41 | 03-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 907.52 | 01-JUN-15:00 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.56 | 18-JUN-15:46 | 683.65 | 10-JUN-01:00 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 07-JUL-15:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 531.32 | 04-JUL-14:53 | 373.85 | 15-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 759.45 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.73 | 20-AUG-16:51 | 367.22 | 22-AUG-22:00 |
September | 1306.65 | 01-SEP-09:09 | 1388.60 | 08-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.86 | 03-SEP-15:06 | 510.46 | 07-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 1388.60 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.10 | 01-OCT-16:00 | 849.85 | 11-OCT-23:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1459.01 | 03-NOV-21:03 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1977.61 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.22 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 531.32 | 1977.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1007.95 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1206.69 | 16-JAN-18:00 |
February | 805.43 | 01-FEB-08:09 | 879.10 | 16-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 958.20 | 05-FEB-01:00 |
March | 805.43 | 01-MAR-08:09 | 703.38 | 14-MAR-15:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 850.09 | 14-MAR-03:00 |
April | 805.43 | 03-APR-07:10 | 480.79 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.22 | 01-APR-17:50 | 1018.14 | 23-APR-09:00 |
May | 805.43 | 01-MAY-07:10 | 527.66 | 03-MAY-15:20 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.64 | 14-MAY-17:10 | 603.20 | 03-MAY-22:00 |
June | 805.43 | 01-JUN-07:10 | 574.53 | 01-JUN-15:00 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 286.33 | 18-JUN-15:50 | 456.52 | 04-JUN-16:55 |
July | 805.43 | 03-JUL-07:10 | 574.53 | 07-JUL-15:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 382.40 | 04-JUL-14:53 | 255.03 | 15-JUL-19:00 |
August | 805.43 | 01-AUG-07:10 | 480.79 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.98 | 05-AUG-17:02 | 320.07 | 27-AUG-08:10 |
September | 805.43 | 01-SEP-07:10 | 879.10 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.88 | 03-SEP-15:06 | 349.00 | 18-SEP-01:00 |
October | 805.43 | 02-OCT-07:10 | 703.38 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.68 | 01-OCT-16:10 | 564.72 | 11-OCT-23:00 |
November | 805.43 | 01-NOV-07:10 | 1007.95 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 960.66 | 03-NOV-24:00 |
December | 805.43 | 01-DEC-08:09 | 1007.95 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1319.74 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.03 | |||||
Maximum of Months | 805.43 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 382.40 | 1319.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1388.60 | 04-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1911.73 | 16-JAN-18:00 |
February | 1306.65 | 01-FEB-10:09 | 1388.60 | 16-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1521.34 | 05-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1111.04 | 20-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1309.07 | 14-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 759.45 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.74 | 29-APR-16:00 | 1477.78 | 07-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 907.52 | 22-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.71 | 14-MAY-17:10 | 910.34 | 03-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 907.52 | 01-JUN-15:00 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 396.43 | 18-JUN-15:46 | 676.65 | 10-JUN-01:30 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 07-JUL-15:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 533.58 | 04-JUL-14:53 | 377.93 | 15-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 759.45 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.26 | 20-AUG-16:51 | 378.37 | 22-AUG-22:00 |
September | 1306.65 | 01-SEP-09:09 | 1388.60 | 08-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.23 | 03-SEP-14:24 | 558.71 | 17-SEP-20:00 |
October | 1306.65 | 02-OCT-09:09 | 1388.60 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.69 | 11-OCT-14:00 | 872.38 | 11-OCT-23:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 08-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1518.46 | 03-NOV-21:10 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2062.89 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.93 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 533.58 | 2062.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 879.04 | 04-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1226.52 | 16-JAN-18:00 |
February | 827.17 | 01-FEB-10:09 | 879.04 | 16-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 981.39 | 05-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 832.18 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 849.49 | 14-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 480.76 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 29-APR-16:00 | 1073.62 | 15-APR-17:05 |
May | 827.17 | 01-MAY-09:09 | 574.49 | 22-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.19 | 21-MAY-17:00 | 608.40 | 03-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 703.34 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.33 | 18-JUN-16:00 | 476.90 | 10-JUN-01:00 |
July | 827.17 | 03-JUL-09:09 | 574.49 | 07-JUL-15:39 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.89 | 04-JUL-14:53 | 262.15 | 15-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 527.63 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 20-AUG-17:00 | 256.81 | 08-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 879.04 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.20 | 03-SEP-15:06 | 378.83 | 17-SEP-20:00 |
October | 827.17 | 02-OCT-09:09 | 879.04 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.71 | 11-OCT-13:00 | 574.53 | 11-OCT-23:00 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 09-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 985.10 | 03-NOV-21:13 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 01-DEC-16:49 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1329.45 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.81 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 359.89 | 1329.45 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2690.07 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2142.56 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1855.54 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.42 | 17-APR-15:00 | 2055.08 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.16 | 14-MAY-16:51 | 1268.90 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.93 | 18-JUN-16:00 | 970.08 | 10-JUN-01:30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.46 | 04-JUL-15:00 | 487.69 | 15-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.40 | 05-AUG-17:02 | 496.81 | 22-AUG-22:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.38 | 03-SEP-14:42 | 730.95 | 18-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 01-OCT-16:00 | 1178.44 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2137.12 | 03-NOV-24:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2970.20 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.69 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.46 | 2970.20 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3194.04 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2625.78 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2305.28 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.57 | 17-APR-15:00 | 2598.87 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.30 | 14-MAY-16:51 | 1603.54 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651.14 | 18-JUN-16:00 | 1219.79 | 10-JUN-01:30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858.45 | 04-JUL-15:00 | 618.19 | 15-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.11 | 05-AUG-17:02 | 628.65 | 22-AUG-22:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.90 | 03-SEP-14:50 | 907.30 | 18-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.06 | 01-OCT-16:00 | 1490.27 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2654.78 | 03-NOV-24:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3638.64 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618.19 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858.45 | 3638.64 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3141.81 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2410.60 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2155.79 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 | 13-APR-17:00 | 2586.85 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.20 | 19-MAY-15:00 | 1582.88 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.98 | 18-JUN-16:10 | 1276.41 | 04-JUN-16:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 731.27 | 04-JUL-16:51 | 755.85 | 15-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.74 | 20-AUG-17:00 | 617.46 | 10-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.12 | 03-SEP-14:20 | 938.71 | 17-SEP-20:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.08 | 11-OCT-15:00 | 1494.97 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2682.27 | 03-NOV-21:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3360.81 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 617.46 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 731.27 | 3360.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19021.20 | 12-JAN-08:02 | 48280.06 | 60419.97 | 145481.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20764.21 | 15-FEB-17:00 | 6035.01 | 7552.50 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20482.31 | 10-MAR-17:00 | 6035.01 | 7552.50 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37901.85 | 28-APR-06:02 | 6352.64 | 12587.66 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41759.75 | 30-MAY-06:02 | 6352.64 | 12587.66 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 46916.46 | 29-JUN-04:02 | 0.00 | 4195.72 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 43206.29 | 24-JUL-05:12 | 2541.06 | 3356.58 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43937.73 | 22-AUG-05:12 | 2541.06 | 3356.58 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43461.17 | 18-SEP-05:12 | 2541.06 | 3356.58 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 42301.97 | 03-OCT-06:02 | 6352.64 | 12587.66 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 39585.80 | 01-NOV-06:01 | 8893.70 | 17622.73 | 61577.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19270.44 | 01-DEC-16:30 | 6035.01 | 7552.50 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 19021.20 | 0.00 | 3356.58 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46916.46 | 48280.06 | 60419.97 | 145481.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2248.68 | 08-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.92 |
February | 4833.66 | 14-FEB-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.11 |
March | 6319.78 | 08-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.31 |
April | 9402.53 | 28-APR-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.94 |
May | 10752.28 | 30-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.90 | 0.00 |
June | 13009.68 | 28-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.95 | 0.00 |
July | 12856.01 | 21-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.18 | 0.00 |
August | 12965.13 | 07-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.05 | 0.00 |
September | 10428.00 | 12-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.29 | 0.00 |
October | 8548.53 | 05-OCT-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 | 0.00 |
November | 4430.63 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.85 |
December | 2073.56 | 31-DEC-15:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2073.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13009.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.18 | 201.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2231.95 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2933.00 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.81 |
March | 2138.46 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.19 |
April | 3528.30 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 | 0.00 |
May | 4317.36 | 30-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.31 | 0.00 |
June | 6062.90 | 26-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.09 | 0.00 |
July | 6282.73 | 05-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.64 |
August | 6428.09 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.75 | 0.00 |
September | 5249.25 | 05-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 |
October | 4990.40 | 02-OCT-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.87 |
November | 1966.14 | 01-NOV-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.64 |
December | 2496.11 | 15-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1966.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6428.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.09 | 428.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2451.24 | 27-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.42 |
February | 2234.98 | 15-FEB-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.90 |
March | 2567.59 | 24-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.62 |
April | 3957.79 | 28-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 0.00 |
May | 4619.00 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.76 | 0.00 |
June | 6217.26 | 26-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.58 | 0.00 |
July | 6888.28 | 05-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.05 | 0.00 |
August | 6505.98 | 07-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.60 | 0.00 |
September | 5756.68 | 05-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.58 |
October | 5238.17 | 02-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.82 |
November | 2978.27 | 01-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.60 |
December | 2329.98 | 21-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2234.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6888.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.58 | 347.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9786.65 | 27-JAN-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13681.49 | 15-FEB-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13337.00 | 09-MAR-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16822.06 | 28-APR-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28814.05 | 30-MAY-06:02 | 6352.64 | 12587.66 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35384.51 | 29-JUN-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33908.92 | 24-JUL-05:12 | 2541.06 | 3356.58 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34090.23 | 22-AUG-05:12 | 2541.06 | 3356.58 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32807.66 | 05-SEP-06:02 | 6352.64 | 12587.66 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31889.83 | 02-OCT-06:03 | 5082.11 | 10070.13 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15445.13 | 01-NOV-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10603.60 | 01-DEC-16:40 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9786.65 | 0.00 | 3356.58 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35384.51 | 6352.64 | 12587.66 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8262.38 | 05-JAN-16:50 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13399.03 | 15-FEB-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13564.77 | 08-MAR-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18338.73 | 28-APR-15:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20124.51 | 30-MAY-14:50 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29917.72 | 26-JUN-06:03 | 3811.58 | 7552.60 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 36505.76 | 24-JUL-05:12 | 2541.06 | 3356.58 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33727.17 | 21-AUG-06:03 | 5082.11 | 10070.13 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33952.28 | 05-SEP-06:02 | 6352.64 | 12587.66 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20178.17 | 02-OCT-15:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14629.90 | 01-NOV-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8228.95 | 01-DEC-16:30 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 8228.95 | 2541.06 | 3356.58 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36505.76 | 6352.64 | 12587.66 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1564.45 | 05-JAN-14:10 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.18 |
February | 2064.51 | 15-FEB-14:10 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.24 |
March | 2902.67 | 16-MAR-14:50 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.28 |
April | 5460.18 | 14-APR-14:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.61 |
May | 6210.69 | 31-MAY-15:20 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 55.34 | 0.00 |
June | 13539.49 | 25-JUN-17:21 | 0.00 | 337.52 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 282.47 | 0.00 |
July | 13613.80 | 04-JUL-18:21 | 0.00 | 295.33 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 269.42 | 0.00 |
August | 13333.97 | 20-AUG-16:11 | 535.68 | 337.52 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 226.56 | 0.00 |
September | 9105.12 | 03-SEP-13:52 | 401.76 | 253.14 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 158.63 | 0.00 |
October | 5832.01 | 02-OCT-13:40 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 | 0.00 |
November | 2122.44 | 01-NOV-14:10 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.42 |
December | 1516.08 | 29-DEC-13:40 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1516.08 | 0.00 | 253.14 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13613.80 | 1306.65 | 759.45 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 282.47 | 257.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1944.39 | 27-JAN-09:45 | 1610.86 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4121.61 | 14-FEB-09:40 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.12 |
March | 7268.94 | 26-MAR-09:43 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.41 |
April | 15008.94 | 30-APR-08:32 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.95 |
May | 15325.17 | 29-MAY-08:52 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.94 |
June | 15954.68 | 18-JUN-08:41 | 296.74 | 186.97 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.93 |
July | 16358.20 | 04-JUL-09:01 | 296.74 | 186.97 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 |
August | 16237.26 | 20-AUG-08:51 | 296.74 | 186.97 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.71 |
September | 15561.19 | 03-SEP-09:12 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.29 |
October | 10970.41 | 01-OCT-09:12 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.60 |
November | 5352.73 | 01-NOV-09:10 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.12 |
December | 1810.66 | 29-DEC-09:40 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1810.66 | 169.56 | 106.84 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16358.20 | 1610.86 | 961.59 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16446.89 | 29-JAN-14:02 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.50 |
February | 16582.77 | 19-FEB-13:42 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.37 |
March | 16968.81 | 26-MAR-14:22 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.26 |
April | 15064.45 | 30-APR-13:13 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.92 |
May | 9727.09 | 28-MAY-12:32 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.45 |
June | 15517.15 | 25-JUN-16:01 | 535.68 | 337.52 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 211.67 | 0.00 |
July | 16410.41 | 30-JUL-14:52 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 165.17 | 0.00 |
August | 16710.07 | 20-AUG-12:52 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 63.89 | 0.00 |
September | 17883.71 | 03-SEP-13:12 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 96.17 | 0.00 |
October | 18197.25 | 01-OCT-12:32 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.06 |
November | 16939.46 | 12-NOV-14:22 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.31 |
December | 17074.45 | 31-DEC-15:12 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9727.09 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18197.25 | 535.68 | 337.52 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 211.67 | 501.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4804.72 | 26-JAN-16:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.89 |
February | 7651.65 | 15-FEB-16:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.89 |
March | 8343.29 | 12-MAR-16:03 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.16 |
April | 16405.91 | 16-APR-16:12 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.86 |
May | 17627.05 | 14-MAY-16:31 | 296.72 | 186.96 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 28.21 | 0.00 |
June | 18631.44 | 25-JUN-16:41 | 339.11 | 213.67 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 162.34 | 0.00 |
July | 18845.38 | 04-JUL-17:01 | 0.00 | 213.67 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 273.48 | 0.00 |
August | 18412.24 | 20-AUG-16:11 | 339.11 | 213.67 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 117.82 | 0.00 |
September | 18890.99 | 24-SEP-16:21 | 339.11 | 213.67 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.42 |
October | 15496.24 | 01-OCT-15:12 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 17.05 | 0.00 |
November | 6519.07 | 02-NOV-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.74 |
December | 3840.59 | 29-DEC-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3840.59 | 0.00 | 106.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18890.99 | 805.38 | 480.76 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 273.48 | 101.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1557.88 | 27-JAN-13:07 | 3816.70 | 2278.34 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.64 |
February | 1721.64 | 14-FEB-14:50 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 |
March | 1474.92 | 27-MAR-15:20 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.52 |
April | 3760.81 | 14-APR-14:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 |
May | 4607.22 | 31-MAY-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 41.89 | 0.00 |
June | 11104.68 | 25-JUN-17:51 | 0.00 | 421.90 | 3861.03 | 0.00 | 0.00 | 0.00 | 0.00 | 118.89 | 0.00 |
July | 11383.63 | 04-JUL-18:11 | 0.00 | 421.90 | 3861.03 | 0.00 | 0.00 | 0.00 | 0.00 | 145.79 | 0.00 |
August | 11055.87 | 20-AUG-16:01 | 669.60 | 421.90 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 108.21 | 0.00 |
September | 6588.32 | 05-SEP-06:02 | 1339.19 | 2653.59 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 |
October | 5147.03 | 02-OCT-13:40 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 0.00 |
November | 1946.93 | 01-NOV-14:50 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.43 |
December | 1565.12 | 29-DEC-13:07 | 3816.70 | 2278.34 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1474.92 | 0.00 | 421.90 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11383.63 | 3816.70 | 2653.59 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 145.79 | 141.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1792.03 | 27-JAN-13:07 | 2416.29 | 1442.38 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.02 |
February | 2875.25 | 14-FEB-10:10 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 |
March | 3903.14 | 31-MAR-08:65 | 1610.86 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.11 |
April | 13098.02 | 30-APR-07:41 | 296.74 | 186.97 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.14 |
May | 13522.30 | 29-MAY-08:41 | 339.13 | 213.68 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.94 |
June | 13953.64 | 25-JUN-09:11 | 381.52 | 240.39 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 |
July | 14553.07 | 04-JUL-09:31 | 423.91 | 267.10 | 3028.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 |
August | 14436.77 | 20-AUG-09:21 | 423.91 | 267.10 | 3028.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.51 |
September | 13159.42 | 03-SEP-10:52 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11.10 | 0.00 |
October | 10365.74 | 01-OCT-08:51 | 296.74 | 186.97 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.13 |
November | 4771.60 | 01-NOV-08:20 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.61 |
December | 1795.34 | 29-DEC-08:55 | 1610.86 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1792.03 | 254.35 | 160.26 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14553.07 | 2416.29 | 1442.38 | 3028.58 | 0.00 | 0.00 | 0.00 | 0.00 | 11.10 | 219.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14291.56 | 01-JAN-14:32 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.89 |
February | 12631.37 | 19-FEB-13:42 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.65 |
March | 8608.67 | 13-MAR-14:20 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.29 |
April | 9676.98 | 30-APR-13:42 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.16 |
May | 8337.26 | 19-MAY-16:10 | 401.76 | 421.91 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3988.77 | 0.00 |
June | 12847.49 | 25-JUN-15:51 | 669.60 | 421.90 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 89.82 | 0.00 |
July | 13822.87 | 04-JUL-15:31 | 669.60 | 421.90 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 245.71 | 0.00 |
August | 14405.14 | 20-AUG-15:21 | 669.60 | 421.90 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 71.07 | 0.00 |
September | 14907.37 | 03-SEP-14:12 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 66.98 | 0.00 |
October | 15510.60 | 09-OCT-14:01 | 468.72 | 295.33 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.79 |
November | 14363.33 | 19-NOV-14:52 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.53 |
December | 13817.98 | 31-DEC-14:12 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8337.26 | 334.80 | 210.95 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15510.60 | 1272.23 | 759.45 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3988.77 | 354.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4013.21 | 26-JAN-16:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.61 |
February | 5974.29 | 15-FEB-16:40 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.39 |
March | 5617.40 | 07-MAR-17:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.12 |
April | 14638.17 | 16-APR-17:21 | 0.00 | 213.67 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.26 |
May | 14169.64 | 29-MAY-16:41 | 339.11 | 213.67 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 |
June | 15481.41 | 25-JUN-17:11 | 0.00 | 267.08 | 2444.18 | 0.00 | 0.00 | 0.00 | 0.00 | 66.51 | 0.00 |
July | 15860.68 | 04-JUL-17:31 | 0.00 | 267.08 | 2444.18 | 0.00 | 0.00 | 0.00 | 0.00 | 91.23 | 0.00 |
August | 15590.92 | 20-AUG-17:21 | 0.00 | 267.08 | 2444.18 | 0.00 | 0.00 | 0.00 | 0.00 | 54.94 | 0.00 |
September | 13907.87 | 17-SEP-16:01 | 296.72 | 186.96 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.20 |
October | 14014.13 | 01-OCT-15:31 | 296.72 | 186.96 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 9.08 | 0.00 |
November | 6174.25 | 02-NOV-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 |
December | 3256.03 | 29-DEC-16:10 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3256.03 | 0.00 | 186.96 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15860.68 | 805.38 | 480.76 | 2444.18 | 0.00 | 0.00 | 0.00 | 0.00 | 91.23 | 40.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1639.19 | 05-JAN-14:10 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.21 |
February | 2033.96 | 15-FEB-16:20 | 1272.23 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.56 |
March | 3046.91 | 27-MAR-14:40 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.67 |
April | 5215.70 | 14-APR-14:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 |
May | 5771.14 | 31-MAY-15:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 50.81 | 0.00 |
June | 12023.31 | 25-JUN-17:51 | 0.00 | 421.90 | 3861.03 | 0.00 | 0.00 | 0.00 | 0.00 | 166.44 | 0.00 |
July | 12681.26 | 04-JUL-18:12 | 0.00 | 421.90 | 3861.03 | 0.00 | 0.00 | 0.00 | 0.00 | 250.20 | 0.00 |
August | 11896.40 | 20-AUG-16:01 | 669.60 | 421.90 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 161.05 | 0.00 |
September | 10207.55 | 04-SEP-16:51 | 535.68 | 337.52 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 |
October | 5582.47 | 02-OCT-13:40 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 | 0.00 |
November | 2220.59 | 02-NOV-15:30 | 1272.23 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.66 |
December | 1591.49 | 29-DEC-14:20 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1591.49 | 0.00 | 337.52 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12681.26 | 1306.65 | 833.48 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 250.20 | 54.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2996.32 | 27-JAN-09:25 | 1610.86 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5133.52 | 14-FEB-09:30 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.99 |
March | 10108.83 | 26-MAR-09:53 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.74 |
April | 15970.19 | 30-APR-07:41 | 296.74 | 186.97 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.83 |
May | 16695.67 | 29-MAY-08:41 | 339.13 | 213.68 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.57 |
June | 17182.80 | 25-JUN-08:31 | 381.52 | 240.39 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.82 |
July | 17825.92 | 04-JUL-08:51 | 423.91 | 267.10 | 3028.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.84 |
August | 17752.02 | 20-AUG-08:41 | 423.91 | 267.10 | 3028.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.28 |
September | 16898.86 | 03-SEP-09:01 | 381.52 | 240.39 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.19 |
October | 15539.05 | 01-OCT-08:22 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.30 |
November | 6088.83 | 01-NOV-09:00 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.04 |
December | 2799.02 | 29-DEC-09:15 | 1610.86 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2799.02 | 169.56 | 106.84 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17825.92 | 1610.86 | 961.59 | 3028.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14981.88 | 01-JAN-12:02 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.59 |
February | 15114.67 | 12-FEB-13:22 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.94 |
March | 14980.58 | 12-MAR-12:23 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.57 |
April | 15005.89 | 30-APR-13:42 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.89 |
May | 13728.71 | 21-MAY-13:12 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 | 0.00 |
June | 14545.19 | 25-JUN-16:31 | 669.60 | 421.90 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 250.02 | 0.00 |
July | 15234.21 | 30-JUL-11:22 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 54.74 | 0.00 |
August | 15872.54 | 20-AUG-12:42 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 43.94 | 0.00 |
September | 16409.58 | 17-SEP-13:22 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.26 |
October | 18045.72 | 01-OCT-13:01 | 602.64 | 379.71 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.53 |
November | 15296.51 | 23-NOV-12:02 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.24 |
December | 15682.09 | 31-DEC-15:22 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13728.71 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18045.72 | 669.60 | 421.90 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 250.02 | 296.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5018.11 | 26-JAN-16:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.44 |
February | 7582.13 | 15-FEB-16:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.28 |
March | 10058.75 | 12-MAR-16:22 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.58 |
April | 17412.06 | 16-APR-16:41 | 339.11 | 213.67 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.46 |
May | 17476.24 | 29-MAY-16:41 | 339.11 | 213.67 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.69 |
June | 18662.46 | 25-JUN-16:31 | 423.88 | 267.08 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 89.91 | 0.00 |
July | 19072.17 | 04-JUL-16:51 | 423.88 | 267.08 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 191.80 | 0.00 |
August | 18566.30 | 20-AUG-16:01 | 423.88 | 267.08 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 66.56 | 0.00 |
September | 17035.17 | 04-SEP-16:51 | 339.11 | 213.67 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.28 |
October | 16548.71 | 09-OCT-15:31 | 296.72 | 186.96 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.52 |
November | 6619.29 | 02-NOV-15:50 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.21 |
December | 4036.10 | 29-DEC-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4036.10 | 211.94 | 133.54 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19072.17 | 805.38 | 480.76 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 191.80 | 114.58 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.125902E+12 | 169688.59 | 17-JAN-07:10 | 0.262846E+11 | 57444.84 | 21-JAN-07:10 |
February | 0.108736E+12 | 160307.86 | 06-FEB-07:10 | 0.191501E+11 | 54700.18 | 06-FEB-07:19 |
March | 0.119073E+12 | 107422.43 | 08-MAR-16:10 | 0.142469E+11 | 37329.21 | 04-MAR-07:10 |
April | 0.117851E+12 | 134085.27 | 13-APR-15:20 | 0.113787E+11 | 25454.26 | 08-APR-06:30 |
May | 0.135360E+12 | 149022.37 | 19-MAY-15:20 | 0.112581E+11 | 11328.92 | 05-MAY-06:19 |
June | 0.165134E+12 | 189289.74 | 28-JUN-14:50 | 0.106425E+11 | 9863.37 | 01-JUN-11:00 |
July | 0.178388E+12 | 186658.28 | 21-JUL-15:09 | 0.103505E+11 | 9756.55 | 03-JUL-11:20 |
August | 0.181641E+12 | 179189.78 | 07-AUG-15:30 | 0.107416E+11 | 9729.38 | 31-AUG-11:39 |
September | 0.146359E+12 | 156232.90 | 05-SEP-14:30 | 0.102305E+11 | 9803.43 | 29-SEP-11:50 |
October | 0.128065E+12 | 139645.97 | 06-OCT-15:00 | 0.122145E+11 | 39550.44 | 26-OCT-06:40 |
November | 0.111952E+12 | 115128.36 | 27-NOV-07:10 | 0.139659E+11 | 48072.99 | 27-NOV-07:30 |
December | 0.122936E+12 | 160468.67 | 26-DEC-07:10 | 0.254948E+11 | 60541.78 | 15-DEC-07:19 |
Annual Sum or Average | 0.164140E+13 | 0.175959E+12 | ||||
Minimum of Months | 0.108736E+12 | 107422.43 | 0.102305E+11 | 9729.38 | ||
Maximum of Months | 0.181641E+12 | 189289.74 | 0.262846E+11 | 60541.78 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.308108E+11 | 0.114712E+11 | 0.593559E+11 | 0.143862E+10 | 0.566028E+10 | 12379742.02 | 0.169920E+11 | 0.161038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276970E+11 | 0.966777E+10 | 0.537310E+11 | 0.130175E+10 | 0.542107E+10 | 11196021.66 | 0.100046E+11 | 0.901086E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.324841E+11 | 0.970205E+10 | 0.617796E+11 | 0.150692E+10 | 0.717358E+10 | 12675672.10 | 0.370186E+10 | 0.271255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.287331E+11 | 0.836333E+10 | 0.572952E+11 | 0.138480E+10 | 0.100680E+11 | 11960507.72 | 0.802453E+09 | 0.111926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.309266E+11 | 0.777498E+10 | 0.605677E+11 | 0.147213E+10 | 0.128044E+11 | 12527707.06 | 0.275889E+09 | 0.215253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.306651E+11 | 0.710674E+10 | 0.594895E+11 | 0.144940E+10 | 0.191031E+11 | 12231776.97 | 27376276.49 | 0.472804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.287885E+11 | 0.753058E+10 | 0.583622E+11 | 0.140726E+10 | 0.218226E+11 | 12256437.81 | 0.00 | 0.604642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.320766E+11 | 0.824753E+10 | 0.617796E+11 | 0.150660E+10 | 0.219224E+11 | 12675672.10 | 0.00 | 0.560957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.289112E+11 | 0.895648E+10 | 0.572729E+11 | 0.138460E+10 | 0.149523E+11 | 11960507.72 | 1010829.92 | 0.348683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.303455E+11 | 0.102952E+11 | 0.593671E+11 | 0.143828E+10 | 0.104622E+11 | 12379742.02 | 0.143319E+10 | 0.147116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304759E+11 | 0.108597E+11 | 0.580818E+11 | 0.141230E+10 | 0.671209E+10 | 12059151.09 | 0.379173E+10 | 0.606465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.301948E+11 | 0.117188E+11 | 0.583511E+11 | 0.140864E+10 | 0.568508E+10 | 12256437.81 | 0.155651E+11 | 74749.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.362109E+12 | 0.111694E+12 | 0.705434E+12 | 0.171113E+11 | 0.141787E+12 | 0.146559E+09 | 0.525953E+11 | 0.250519E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.276970E+11 | 0.710674E+10 | 0.537310E+11 | 0.130175E+10 | 0.542107E+10 | 11196021.66 | 0.00 | 74749.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.324841E+11 | 0.117188E+11 | 0.617796E+11 | 0.150692E+10 | 0.219224E+11 | 12675672.10 | 0.169920E+11 | 0.604642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.144658E+11 | 0.00 | 0.118188E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.841110E+10 | 0.00 | 0.107390E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.211947E+10 | 0.00 | 0.121274E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.331447E+09 | 0.00 | 0.110473E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 24346976.14 | 0.00 | 0.112337E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.106425E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.103505E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.107416E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.102305E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.135030E+10 | 0.00 | 0.108641E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.300770E+10 | 0.00 | 0.109582E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.140517E+11 | 0.00 | 0.114430E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.437619E+11 | 0.00 | 0.132197E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.102305E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.144658E+11 | 0.00 | 0.121274E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 37260.69 | 04-JAN-16:00 | 8596.48 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 1236.27 | 04-JAN-16:00 | 7962.98 | 26-JAN-16:30 | 6.85 | 03-JAN-06:10 | 122149.50 | 17-JAN-07:10 |
February | 36263.56 | 16-FEB-08:09 | 8596.48 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 1238.27 | 16-FEB-08:20 | 13462.56 | 15-FEB-16:30 | 6.85 | 03-FEB-08:09 | 122537.87 | 06-FEB-07:10 |
March | 33415.05 | 20-MAR-07:10 | 8596.48 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 1232.70 | 20-MAR-07:19 | 12024.59 | 24-MAR-15:30 | 6.85 | 21-MAR-16:10 | 60118.37 | 06-MAR-07:10 |
April | 30098.83 | 03-APR-07:10 | 8596.48 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 1226.25 | 03-APR-07:19 | 22176.87 | 28-APR-14:30 | 6.85 | 04-APR-11:09 | 23395.39 | 06-APR-06:10 |
May | 31409.05 | 22-MAY-07:10 | 8596.48 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 1228.79 | 22-MAY-07:19 | 25815.34 | 30-MAY-14:30 | 6.85 | 07-MAY-15:50 | 18333.69 | 05-MAY-06:10 |
June | 31580.93 | 08-JUN-07:10 | 8596.48 | 01-JUN-19:10 | 45864.70 | 01-JUN-07:10 | 1229.13 | 08-JUN-07:19 | 36694.75 | 26-JUN-15:30 | 6.85 | 03-JUN-16:10 | 7309.19 | 09-JUN-06:10 |
July | 31549.66 | 07-JUL-15:50 | 8596.48 | 01-JUL-19:19 | 45864.70 | 03-JUL-07:10 | 1227.08 | 07-JUL-15:00 | 37068.67 | 05-JUL-14:00 | 6.85 | 02-JUL-08:09 | 0.00 | 01-JUL-00:10 |
August | 30239.43 | 28-AUG-07:10 | 8596.48 | 01-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 1226.52 | 28-AUG-07:19 | 35268.61 | 07-AUG-15:30 | 6.85 | 05-AUG-16:10 | 0.00 | 01-AUG-00:10 |
September | 36263.56 | 08-SEP-07:10 | 8596.48 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 1238.27 | 08-SEP-07:19 | 27196.72 | 13-SEP-15:00 | 6.85 | 02-SEP-17:40 | 666.57 | 27-SEP-06:10 |
October | 35736.40 | 25-OCT-07:10 | 8596.48 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 1237.24 | 25-OCT-07:19 | 21705.05 | 02-OCT-15:50 | 6.85 | 01-OCT-10:00 | 58977.07 | 26-OCT-06:10 |
November | 38257.79 | 09-NOV-16:49 | 8596.48 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 1240.17 | 09-NOV-16:00 | 13464.37 | 02-NOV-15:00 | 6.85 | 06-NOV-06:10 | 77151.35 | 27-NOV-07:10 |
December | 38257.79 | 01-DEC-16:49 | 8596.48 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 1240.17 | 01-DEC-16:00 | 7386.53 | 29-DEC-15:50 | 6.85 | 04-DEC-08:09 | 113236.27 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 30098.83 | 8596.48 | 45864.70 | 1226.25 | 7386.53 | 6.85 | 0.00 | |||||||
Maximum of Months | 38257.79 | 8596.48 | 45864.70 | 1240.17 | 37068.67 | 6.85 | 122537.87 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 5645.78 | 05-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21692.81 | 14-FEB-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22341.92 | 08-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39124.32 | 13-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 50710.91 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82663.02 | 28-JUN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80903.89 | 21-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 70846.92 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 64327.01 | 05-SEP-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49191.33 | 02-OCT-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12546.51 | 02-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 124.58 | 24-DEC-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 124.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82663.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 169688.59 | 17-JAN-07:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 4730.41 | 6.85 | 122149.50 | 0.00 | 0.00 |
February | 160307.86 | 06-FEB-07:10 | 11634.72 | 21098.80 | 0.00 | 353.77 | 4675.85 | 6.85 | 122537.87 | 0.00 | 0.00 |
March | 107422.43 | 08-MAR-16:10 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 11678.16 | 6.85 | 0.00 | 22341.92 | 0.00 |
April | 134085.27 | 13-APR-15:20 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 22032.03 | 6.85 | 0.00 | 38650.88 | 0.00 |
May | 149022.37 | 19-MAY-15:20 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 24909.10 | 6.85 | 0.00 | 50710.91 | 0.00 |
June | 189289.74 | 28-JUN-14:50 | 30098.83 | 40588.47 | 0.00 | 1223.48 | 34809.19 | 6.85 | 0.00 | 82562.90 | 0.00 |
July | 186658.28 | 21-JUL-15:09 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 32763.37 | 6.85 | 0.00 | 80492.56 | 0.00 |
August | 179189.78 | 07-AUG-15:30 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 35268.61 | 6.85 | 0.00 | 70518.81 | 0.00 |
September | 156232.90 | 05-SEP-14:30 | 30098.83 | 40588.47 | 0.00 | 1223.48 | 23965.82 | 6.85 | 0.00 | 60349.43 | 0.00 |
October | 139645.97 | 06-OCT-15:00 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 18871.06 | 6.85 | 0.00 | 47372.56 | 0.00 |
November | 115128.36 | 27-NOV-07:10 | 12623.92 | 21098.80 | 0.00 | 353.77 | 3893.67 | 6.85 | 77151.35 | 0.00 | 0.00 |
December | 160468.67 | 26-DEC-07:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 4423.73 | 6.85 | 113236.27 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 107422.43 | 11634.72 | 21098.80 | 0.00 | 353.77 | 3893.67 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 189289.74 | 30098.83 | 42072.41 | 8596.48 | 1224.26 | 35268.61 | 6.85 | 122537.87 | 82562.90 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 50612.48 | 21-JAN-07:10 | 0.00 | 10246.31 | 27-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 46911.01 | 04-FEB-07:19 | 0.00 | 10254.51 | 01-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 28884.10 | 04-MAR-07:19 | 0.00 | 10231.24 | 02-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 17134.57 | 08-APR-06:19 | 0.00 | 10131.50 | 04-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 3890.30 | 06-MAY-06:10 | 0.00 | 10005.89 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9863.37 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9756.55 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9729.38 | 31-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9803.43 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 32194.07 | 26-OCT-06:00 | 0.00 | 9931.83 | 31-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 39926.39 | 27-NOV-07:19 | 0.00 | 10070.26 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 51556.54 | 15-DEC-07:19 | 0.00 | 10187.53 | 28-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9729.38 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 51556.54 | 0.00 | 10254.51 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 16.25 | 0.17 | 16.42 | 0.00 | 16.42 | 0.00 | 16.42 |
February | 2.33 | 15.96 | 0.17 | 16.17 | 0.00 | 16.17 | 0.00 | 16.17 |
March | 0.17 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.59 | 2.00 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.64 | 5.50 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.56 | 3.00 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.43 | 0.83 | 27.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
December | 2.00 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 |
Annual Sum or Average | 7.67 | 16.37 | 0.33 | 16.49 | 16.00 | 23.89 | 11.33 | 25.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 17.21 | 0.17 | 17.21 | 7.50 | 27.64 | 5.50 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 15.90 | 0.00 | 15.90 | 0.00 | 15.90 | 0.00 | 15.90 |
February | 2.00 | 16.15 | 0.17 | 16.40 | 0.00 | 16.40 | 0.00 | 16.40 |
March | 0.17 | 17.15 | 0.00 | 17.15 | 0.17 | 22.28 | 0.17 | 23.99 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.51 | 1.17 | 28.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.01 | 8.83 | 28.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.22 | 8.67 | 28.25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 28.42 | 16.00 | 28.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 28.35 | 10.00 | 28.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.21 | 4.17 | 28.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.00 | 1.33 | 28.00 |
November | 0.17 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 |
December | 2.50 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 |
Annual Sum or Average | 8.17 | 16.24 | 0.17 | 16.30 | 53.17 | 26.65 | 50.33 | 27.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.90 | 0.00 | 15.90 |
Maximum of Months | 3.33 | 17.15 | 0.17 | 17.15 | 17.33 | 28.51 | 16.00 | 28.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 16.19 | 0.00 | 16.19 | 4.33 | 24.99 | 4.33 | 26.17 |
February | 1.00 | 16.82 | 0.17 | 17.18 | 2.33 | 24.32 | 2.33 | 25.75 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.84 | 2.33 | 27.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.70 | 1.17 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.51 | 3.67 | 27.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.62 | 3.17 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.88 | 8.33 | 27.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.09 | 6.17 | 28.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.28 | 11.00 | 27.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 26.91 | 11.83 | 26.91 |
November | 0.17 | 17.23 | 0.00 | 17.23 | 4.83 | 27.50 | 4.83 | 27.68 |
December | 0.83 | 16.65 | 0.00 | 16.65 | 2.67 | 25.16 | 2.67 | 26.31 |
Annual Sum or Average | 3.33 | 16.55 | 0.17 | 16.68 | 65.67 | 27.02 | 61.83 | 27.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.32 | 1.17 | 25.75 |
Maximum of Months | 1.33 | 17.23 | 0.17 | 17.23 | 12.00 | 28.09 | 11.83 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 16.03 | 0.00 | 16.03 | 0.00 | 16.03 | 0.00 | 16.03 |
February | 1.83 | 16.09 | 0.17 | 16.36 | 0.00 | 16.36 | 0.00 | 16.36 |
March | 0.17 | 17.17 | 0.00 | 17.17 | 1.00 | 26.37 | 0.83 | 26.99 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.28 | 2.50 | 28.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.41 | 3.33 | 28.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.99 | 3.67 | 29.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.81 | 5.67 | 28.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.70 | 4.00 | 28.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.42 | 4.33 | 28.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.35 | 2.67 | 28.40 |
November | 0.17 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
December | 1.50 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
Annual Sum or Average | 6.00 | 16.30 | 0.17 | 16.39 | 40.83 | 27.02 | 27.00 | 27.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 | 0.00 | 16.03 |
Maximum of Months | 2.33 | 17.17 | 0.17 | 17.17 | 9.17 | 28.99 | 5.67 | 29.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.40 | 1.17 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.67 | 27.40 | 1.17 | 27.38 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.40 | 1.17 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.02 | 1.17 | 28.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.85 | 5.17 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.94 | 7.00 | 27.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 28.05 | 16.17 | 28.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 28.02 | 10.17 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.85 | 4.83 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.72 | 1.50 | 27.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 48.33 | 27.97 | 46.00 | 27.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 28.05 | 16.17 | 28.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.17 | 18.91 | 27.17 | 18.91 | 4.67 | 19.60 | 4.67 | 20.19 |
February | 15.83 | 19.00 | 15.83 | 19.00 | 1.83 | 19.47 | 1.83 | 19.90 |
March | 9.83 | 19.69 | 9.83 | 19.69 | 1.83 | 20.36 | 1.83 | 20.92 |
April | 1.00 | 20.19 | 1.00 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.86 | 2.67 | 24.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 26.48 | 8.17 | 26.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 26.99 | 8.00 | 26.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 26.50 | 15.33 | 26.48 |
October | 3.00 | 19.20 | 3.00 | 19.20 | 24.83 | 24.66 | 23.83 | 25.21 |
November | 3.33 | 19.96 | 3.33 | 19.96 | 6.17 | 23.69 | 6.17 | 25.00 |
December | 21.50 | 18.76 | 21.50 | 18.76 | 3.67 | 19.47 | 3.67 | 20.08 |
Annual Sum or Average | 81.67 | 19.05 | 81.67 | 19.05 | 78.67 | 21.51 | 76.17 | 22.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 27.17 | 20.19 | 27.17 | 20.19 | 24.83 | 26.99 | 23.83 | 26.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.49 | 0.17 | 27.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.91 | 1.33 | 27.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.98 | 2.17 | 28.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.41 | 3.00 | 28.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.29 | 4.83 | 28.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.22 | 3.17 | 28.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.00 | 3.67 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.01 | 2.33 | 28.05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 33.83 | 28.18 | 20.67 | 28.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.41 | 4.83 | 28.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 |
February | 0.17 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.44 | 1.00 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.50 | 3.67 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.44 | 1.67 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 17.07 | 0.00 | 17.07 | 9.67 | 27.12 | 6.33 | 27.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.09 | 0.00 | 17.09 | 5.00 | 27.50 | 3.67 | 27.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
February | 0.17 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.67 | 1.17 | 27.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.00 | 3.00 | 28.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.32 | 6.67 | 28.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.25 | 7.67 | 28.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 28.36 | 15.50 | 28.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.30 | 9.33 | 28.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.25 | 4.00 | 28.25 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.88 | 2.83 | 27.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 17.05 | 0.00 | 17.05 | 51.33 | 28.18 | 50.17 | 28.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.06 | 0.00 | 17.06 | 16.00 | 28.36 | 15.50 | 28.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.19 | 0.00 | 17.19 | 5.67 | 27.68 | 5.67 | 27.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.14 | 4.00 | 27.14 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.80 | 3.17 | 27.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.59 | 1.50 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.39 | 2.67 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.47 | 2.00 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.70 | 8.00 | 27.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.89 | 6.33 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 26.78 | 14.17 | 26.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 26.00 | 25.17 | 26.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.10 | 9.33 | 27.10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.99 | 4.33 | 27.99 |
Annual Sum or Average | 0.17 | 17.19 | 0.00 | 17.19 | 88.67 | 26.99 | 86.33 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.00 | 1.50 | 26.00 |
Maximum of Months | 0.17 | 17.19 | 0.00 | 17.19 | 25.33 | 27.99 | 25.17 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
February | 0.17 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.80 | 1.33 | 27.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.19 | 2.83 | 28.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.30 | 3.17 | 28.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.91 | 3.33 | 28.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.70 | 5.33 | 28.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.48 | 4.00 | 28.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.34 | 3.67 | 28.39 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.23 | 3.00 | 28.30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 17.07 | 0.00 | 17.07 | 39.50 | 28.39 | 26.67 | 28.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.08 | 0.00 | 17.08 | 8.33 | 28.91 | 5.33 | 28.93 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 481.67 | 23.85 | 0.00 | 23.85 | 0.00 | 23.85 |
February | 383.00 | 23.96 | 0.00 | 23.96 | 0.00 | 23.96 |
March | 311.67 | 24.03 | 5.50 | 24.05 | 0.00 | 24.05 |
April | 179.00 | 24.02 | 29.00 | 24.31 | 0.00 | 24.31 |
May | 67.00 | 24.04 | 143.83 | 24.64 | 0.00 | 24.64 |
June | 0.00 | 0.00 | 333.83 | 24.51 | 0.00 | 24.51 |
July | 5.17 | 24.00 | 485.83 | 24.47 | 5.17 | 24.46 |
August | 3.50 | 24.52 | 508.17 | 24.41 | 3.50 | 24.41 |
September | 0.00 | 0.00 | 409.83 | 24.52 | 0.00 | 24.52 |
October | 88.00 | 24.02 | 163.50 | 24.53 | 0.00 | 24.53 |
November | 271.67 | 24.01 | 11.50 | 24.08 | 0.00 | 24.08 |
December | 477.00 | 23.94 | 0.00 | 23.94 | 0.00 | 23.94 |
Annual Sum or Average | 2267.67 | 23.96 | 2091.00 | 24.25 | 8.67 | 24.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.85 | 0.00 | 23.85 |
Maximum of Months | 481.67 | 24.52 | 508.17 | 24.64 | 5.17 | 24.64 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.63 | 11.17 | 22.59 | 11.17 | 22.55 |
February | 451.17 | 23.03 | 3.67 | 23.01 | 3.67 | 22.99 |
March | 492.00 | 23.59 | 0.00 | 23.59 | 0.00 | 23.59 |
April | 348.50 | 23.88 | 2.67 | 23.89 | 0.00 | 23.89 |
May | 157.50 | 23.89 | 85.00 | 24.14 | 0.00 | 24.14 |
June | 13.83 | 23.90 | 278.83 | 24.38 | 0.00 | 24.38 |
July | 7.67 | 24.00 | 478.83 | 24.36 | 7.67 | 24.35 |
August | 4.67 | 24.06 | 497.00 | 24.32 | 4.67 | 24.31 |
September | 1.83 | 24.00 | 339.33 | 24.41 | 1.67 | 24.41 |
October | 233.83 | 23.73 | 96.67 | 23.94 | 0.00 | 23.94 |
November | 447.33 | 23.45 | 0.00 | 23.45 | 0.00 | 23.45 |
December | 497.00 | 22.70 | 4.83 | 22.68 | 4.83 | 22.66 |
Annual Sum or Average | 3157.33 | 23.26 | 1798.00 | 23.65 | 33.67 | 23.64 |
Minimum of Months | 1.83 | 22.63 | 0.00 | 22.59 | 0.00 | 22.55 |
Maximum of Months | 502.00 | 24.06 | 497.00 | 24.41 | 11.17 | 24.41 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.67 | 159.00 | 21.37 | 159.00 | 21.19 |
February | 454.00 | 22.18 | 77.33 | 21.94 | 77.33 | 21.76 |
March | 506.17 | 23.02 | 11.33 | 22.97 | 11.33 | 22.92 |
April | 372.67 | 23.60 | 1.00 | 23.60 | 0.00 | 23.60 |
May | 194.83 | 23.66 | 66.33 | 23.85 | 0.00 | 23.85 |
June | 32.17 | 23.66 | 270.50 | 24.28 | 0.00 | 24.28 |
July | 7.33 | 24.00 | 481.67 | 24.33 | 7.33 | 24.33 |
August | 4.83 | 23.87 | 488.67 | 24.28 | 4.83 | 24.28 |
September | 36.67 | 23.60 | 280.83 | 24.25 | 2.00 | 24.25 |
October | 309.83 | 23.26 | 75.17 | 23.44 | 2.17 | 23.43 |
November | 470.83 | 22.62 | 34.00 | 22.49 | 34.00 | 22.38 |
December | 497.00 | 21.65 | 158.83 | 21.37 | 158.83 | 21.19 |
Annual Sum or Average | 3388.33 | 22.59 | 2104.67 | 22.95 | 456.83 | 22.77 |
Minimum of Months | 4.83 | 21.65 | 1.00 | 21.37 | 0.00 | 21.19 |
Maximum of Months | 506.17 | 24.00 | 488.67 | 24.33 | 159.00 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.46 | 377.00 | 20.30 | 377.00 | 20.23 |
February | 454.00 | 20.91 | 245.00 | 20.66 | 245.00 | 20.55 |
March | 511.67 | 21.93 | 130.67 | 21.62 | 130.67 | 21.42 |
April | 391.83 | 22.88 | 36.83 | 22.71 | 34.67 | 22.55 |
May | 231.17 | 23.21 | 91.83 | 23.55 | 4.67 | 23.50 |
June | 50.50 | 23.57 | 319.17 | 24.31 | 4.17 | 24.34 |
July | 44.17 | 25.75 | 484.17 | 24.57 | 42.67 | 24.67 |
August | 34.83 | 24.74 | 468.83 | 24.35 | 24.17 | 24.40 |
September | 116.33 | 23.34 | 259.00 | 24.00 | 9.50 | 24.04 |
October | 380.83 | 22.33 | 115.83 | 22.35 | 56.67 | 22.17 |
November | 487.83 | 21.25 | 211.33 | 20.94 | 211.33 | 20.77 |
December | 497.00 | 20.36 | 413.33 | 20.26 | 413.33 | 20.22 |
Annual Sum or Average | 3702.17 | 21.66 | 3153.00 | 22.02 | 1553.83 | 21.74 |
Minimum of Months | 34.83 | 20.36 | 36.83 | 20.26 | 4.17 | 20.22 |
Maximum of Months | 511.67 | 25.75 | 484.17 | 24.57 | 413.33 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.94 | 283.00 | 20.68 | 283.00 | 20.56 |
February | 437.67 | 21.33 | 158.67 | 21.01 | 157.83 | 20.81 |
March | 397.00 | 22.04 | 88.83 | 21.89 | 71.17 | 21.69 |
April | 213.67 | 22.89 | 111.50 | 23.34 | 19.83 | 23.24 |
May | 172.00 | 23.56 | 209.50 | 24.15 | 26.00 | 24.29 |
June | 61.33 | 24.74 | 387.83 | 24.53 | 26.67 | 24.67 |
July | 81.00 | 26.41 | 477.50 | 24.86 | 77.83 | 25.07 |
August | 58.83 | 25.85 | 478.50 | 24.58 | 47.67 | 24.74 |
September | 105.17 | 23.67 | 340.33 | 24.21 | 21.17 | 24.32 |
October | 274.83 | 22.42 | 159.67 | 22.87 | 39.17 | 22.74 |
November | 461.83 | 21.71 | 120.83 | 21.44 | 117.33 | 21.25 |
December | 497.00 | 20.74 | 291.17 | 20.51 | 291.17 | 20.40 |
Annual Sum or Average | 3262.33 | 21.98 | 3107.33 | 22.56 | 1178.83 | 22.36 |
Minimum of Months | 58.83 | 20.74 | 88.83 | 20.51 | 19.83 | 20.40 |
Maximum of Months | 502.00 | 26.41 | 478.50 | 24.86 | 291.17 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 359.67 | 21.32 | 261.00 | 21.44 | 188.00 | 21.18 |
February | 297.00 | 21.52 | 188.67 | 21.67 | 120.33 | 21.41 |
March | 345.00 | 22.11 | 143.67 | 22.17 | 82.00 | 21.94 |
April | 261.33 | 22.73 | 95.67 | 22.95 | 29.83 | 22.79 |
May | 228.67 | 23.12 | 126.83 | 23.60 | 12.00 | 23.59 |
June | 86.67 | 23.39 | 293.67 | 24.18 | 7.17 | 24.23 |
July | 58.00 | 25.76 | 462.67 | 24.61 | 52.50 | 24.74 |
August | 54.00 | 25.20 | 462.67 | 24.46 | 36.67 | 24.58 |
September | 117.50 | 24.16 | 329.00 | 24.40 | 39.00 | 24.57 |
October | 223.67 | 22.90 | 243.33 | 23.57 | 52.17 | 23.56 |
November | 302.33 | 22.01 | 167.17 | 22.41 | 65.67 | 22.20 |
December | 340.17 | 21.24 | 239.33 | 21.29 | 175.50 | 21.02 |
Annual Sum or Average | 2674.00 | 22.30 | 3013.67 | 22.97 | 860.83 | 22.78 |
Minimum of Months | 54.00 | 21.24 | 95.67 | 21.29 | 7.17 | 21.02 |
Maximum of Months | 359.67 | 25.76 | 462.67 | 24.61 | 188.00 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 478.50 | 20.76 | 308.50 | 20.50 | 308.50 | 20.39 |
February | 399.67 | 21.01 | 209.50 | 20.80 | 199.33 | 20.65 |
March | 423.17 | 21.57 | 156.50 | 21.55 | 116.83 | 21.37 |
April | 317.67 | 22.50 | 122.67 | 22.77 | 47.17 | 22.70 |
May | 243.50 | 22.90 | 161.83 | 23.46 | 21.00 | 23.53 |
June | 113.00 | 23.45 | 327.67 | 24.19 | 18.67 | 24.31 |
July | 59.67 | 25.01 | 445.67 | 24.49 | 43.50 | 24.60 |
August | 69.17 | 24.19 | 441.17 | 24.32 | 31.33 | 24.40 |
September | 148.33 | 23.23 | 277.00 | 23.98 | 24.33 | 24.10 |
October | 330.83 | 22.12 | 161.83 | 22.49 | 61.33 | 22.40 |
November | 431.33 | 21.23 | 169.00 | 20.99 | 161.67 | 20.82 |
December | 479.17 | 20.75 | 328.50 | 20.50 | 328.50 | 20.39 |
Annual Sum or Average | 3494.00 | 21.71 | 3109.83 | 22.22 | 1362.17 | 21.99 |
Minimum of Months | 59.67 | 20.75 | 122.67 | 20.50 | 18.67 | 20.39 |
Maximum of Months | 479.17 | 25.01 | 445.67 | 24.49 | 328.50 | 24.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.80 | 343.50 | 20.66 | 343.50 | 20.61 |
February | 454.00 | 21.06 | 231.67 | 20.89 | 231.67 | 20.80 |
March | 514.00 | 21.85 | 94.00 | 21.66 | 94.00 | 21.52 |
April | 467.83 | 23.08 | 12.67 | 23.02 | 12.67 | 22.96 |
May | 300.00 | 23.51 | 41.50 | 23.62 | 0.00 | 23.62 |
June | 33.00 | 23.63 | 285.33 | 24.30 | 0.00 | 24.30 |
July | 17.50 | 24.65 | 490.67 | 24.44 | 17.50 | 24.45 |
August | 9.67 | 24.22 | 494.50 | 24.32 | 8.50 | 24.32 |
September | 40.33 | 23.66 | 307.17 | 24.24 | 2.17 | 24.24 |
October | 356.33 | 23.01 | 74.83 | 23.18 | 4.00 | 23.16 |
November | 486.00 | 22.00 | 64.83 | 21.85 | 64.83 | 21.72 |
December | 497.00 | 20.85 | 342.50 | 20.73 | 342.50 | 20.69 |
Annual Sum or Average | 3677.67 | 21.95 | 2783.17 | 22.34 | 1121.33 | 22.09 |
Minimum of Months | 9.67 | 20.80 | 12.67 | 20.66 | 0.00 | 20.61 |
Maximum of Months | 514.00 | 24.65 | 494.50 | 24.44 | 343.50 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.47 | 171.83 | 21.24 | 171.83 | 21.11 |
February | 445.33 | 21.76 | 102.00 | 21.53 | 101.67 | 21.36 |
March | 434.17 | 22.58 | 29.33 | 22.54 | 21.67 | 22.45 |
April | 204.50 | 23.38 | 80.67 | 23.89 | 1.33 | 23.90 |
May | 130.50 | 23.91 | 199.33 | 24.40 | 16.00 | 24.52 |
June | 32.83 | 25.59 | 410.17 | 24.61 | 19.83 | 24.71 |
July | 74.00 | 26.62 | 493.00 | 24.90 | 74.00 | 25.10 |
August | 45.50 | 26.65 | 509.83 | 24.66 | 45.00 | 24.81 |
September | 33.33 | 25.58 | 412.17 | 24.55 | 21.33 | 24.66 |
October | 193.83 | 23.18 | 176.33 | 23.85 | 6.00 | 23.87 |
November | 428.50 | 22.68 | 18.17 | 22.69 | 8.67 | 22.64 |
December | 497.00 | 21.50 | 169.17 | 21.28 | 169.17 | 21.14 |
Annual Sum or Average | 3021.50 | 22.49 | 2772.00 | 23.16 | 656.50 | 23.07 |
Minimum of Months | 32.83 | 21.47 | 18.17 | 21.24 | 1.33 | 21.11 |
Maximum of Months | 502.00 | 26.65 | 509.83 | 24.90 | 171.83 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 359.83 | 21.88 | 135.00 | 22.03 | 78.50 | 21.76 |
February | 311.17 | 22.01 | 84.17 | 22.20 | 39.00 | 22.00 |
March | 376.17 | 22.39 | 49.33 | 22.46 | 24.83 | 22.33 |
April | 293.17 | 22.95 | 27.00 | 23.14 | 4.17 | 23.11 |
May | 263.00 | 23.03 | 67.83 | 23.39 | 1.00 | 23.39 |
June | 87.83 | 23.11 | 248.83 | 24.07 | 0.00 | 24.07 |
July | 32.33 | 25.48 | 476.17 | 24.53 | 31.33 | 24.59 |
August | 42.33 | 25.32 | 493.50 | 24.50 | 35.67 | 24.59 |
September | 60.00 | 25.01 | 409.67 | 24.65 | 36.67 | 24.79 |
October | 140.83 | 23.27 | 276.33 | 24.28 | 27.00 | 24.39 |
November | 244.17 | 22.90 | 120.00 | 23.57 | 6.67 | 23.60 |
December | 335.50 | 22.03 | 96.17 | 22.14 | 54.50 | 21.92 |
Annual Sum or Average | 2546.33 | 22.63 | 2484.00 | 23.45 | 339.33 | 23.39 |
Minimum of Months | 32.33 | 21.88 | 27.00 | 22.03 | 0.00 | 21.76 |
Maximum of Months | 376.17 | 25.48 | 493.50 | 24.65 | 78.50 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.33 | 21.31 | 212.67 | 21.09 | 212.67 | 20.97 |
February | 422.00 | 21.58 | 111.83 | 21.37 | 111.00 | 21.23 |
March | 450.67 | 22.11 | 53.50 | 22.07 | 41.17 | 21.96 |
April | 309.00 | 23.10 | 49.00 | 23.37 | 1.17 | 23.38 |
May | 195.50 | 23.33 | 143.00 | 23.85 | 5.83 | 23.91 |
June | 53.67 | 24.09 | 359.17 | 24.42 | 13.50 | 24.50 |
July | 35.50 | 25.93 | 494.33 | 24.57 | 35.50 | 24.65 |
August | 23.67 | 26.08 | 511.50 | 24.46 | 23.67 | 24.53 |
September | 34.50 | 25.15 | 381.17 | 24.54 | 19.17 | 24.63 |
October | 238.50 | 23.02 | 149.50 | 23.57 | 9.17 | 23.61 |
November | 429.33 | 22.33 | 26.83 | 22.31 | 17.00 | 22.25 |
December | 491.50 | 21.41 | 204.67 | 21.19 | 204.67 | 21.08 |
Annual Sum or Average | 3178.17 | 22.21 | 2697.17 | 22.87 | 694.50 | 22.72 |
Minimum of Months | 23.67 | 21.31 | 26.83 | 21.09 | 1.17 | 20.97 |
Maximum of Months | 494.33 | 26.08 | 511.50 | 24.57 | 212.67 | 24.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.92 | 291.17 | 20.71 | 291.17 | 20.62 |
February | 454.00 | 21.40 | 151.50 | 21.15 | 151.50 | 21.00 |
March | 511.33 | 22.47 | 51.67 | 22.30 | 51.67 | 22.15 |
April | 386.50 | 23.34 | 2.33 | 23.33 | 1.67 | 23.32 |
May | 192.83 | 23.57 | 94.83 | 23.91 | 0.00 | 23.91 |
June | 19.50 | 23.78 | 340.50 | 24.41 | 1.50 | 24.43 |
July | 34.00 | 25.60 | 491.50 | 24.58 | 34.00 | 24.64 |
August | 16.83 | 25.15 | 494.00 | 24.38 | 15.50 | 24.41 |
September | 57.00 | 23.63 | 295.83 | 24.23 | 4.33 | 24.24 |
October | 345.50 | 22.84 | 82.50 | 22.99 | 14.17 | 22.92 |
November | 478.83 | 21.90 | 91.50 | 21.67 | 91.50 | 21.50 |
December | 497.00 | 20.83 | 317.00 | 20.67 | 317.00 | 20.60 |
Annual Sum or Average | 3495.33 | 22.06 | 2704.33 | 22.50 | 974.00 | 22.25 |
Minimum of Months | 16.83 | 20.83 | 2.33 | 20.67 | 0.00 | 20.60 |
Maximum of Months | 511.33 | 25.60 | 494.00 | 24.58 | 317.00 | 24.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 424.33 | 21.25 | 186.00 | 21.00 | 186.00 | 20.87 |
February | 363.67 | 21.55 | 100.33 | 21.33 | 96.50 | 21.16 |
March | 351.33 | 22.30 | 55.00 | 22.33 | 30.17 | 22.21 |
April | 194.83 | 23.19 | 92.67 | 23.73 | 8.50 | 23.75 |
May | 148.67 | 23.81 | 167.67 | 24.36 | 22.33 | 24.54 |
June | 49.83 | 25.12 | 319.33 | 24.69 | 24.33 | 24.84 |
July | 74.50 | 26.64 | 410.17 | 25.01 | 74.50 | 25.23 |
August | 46.00 | 26.47 | 410.00 | 24.71 | 42.83 | 24.89 |
September | 74.00 | 24.13 | 283.67 | 24.43 | 20.50 | 24.55 |
October | 231.17 | 22.71 | 131.50 | 23.29 | 19.00 | 23.25 |
November | 373.83 | 21.95 | 51.83 | 21.88 | 41.00 | 21.74 |
December | 418.83 | 21.12 | 210.83 | 20.88 | 210.83 | 20.76 |
Annual Sum or Average | 2751.00 | 22.28 | 2419.00 | 22.92 | 776.50 | 22.80 |
Minimum of Months | 46.00 | 21.12 | 51.83 | 20.88 | 8.50 | 20.76 |
Maximum of Months | 424.33 | 26.64 | 410.17 | 25.01 | 210.83 | 25.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 342.50 | 21.85 | 194.00 | 22.11 | 110.00 | 21.88 |
February | 282.50 | 22.10 | 141.17 | 22.39 | 64.83 | 22.21 |
March | 324.67 | 22.63 | 89.00 | 22.85 | 25.83 | 22.75 |
April | 237.83 | 23.19 | 61.50 | 23.55 | 2.00 | 23.54 |
May | 183.00 | 23.44 | 121.50 | 23.94 | 1.83 | 23.96 |
June | 56.50 | 23.72 | 304.83 | 24.32 | 4.50 | 24.35 |
July | 49.50 | 26.05 | 482.50 | 24.64 | 49.50 | 24.76 |
August | 36.83 | 26.19 | 491.33 | 24.52 | 35.50 | 24.63 |
September | 76.67 | 25.04 | 362.50 | 24.62 | 39.17 | 24.78 |
October | 190.17 | 23.51 | 246.50 | 24.17 | 33.67 | 24.30 |
November | 273.50 | 22.67 | 154.33 | 23.22 | 38.83 | 23.16 |
December | 320.83 | 21.84 | 192.17 | 22.05 | 111.50 | 21.81 |
Annual Sum or Average | 2374.50 | 22.77 | 2841.33 | 23.50 | 517.17 | 23.43 |
Minimum of Months | 36.83 | 21.84 | 61.50 | 22.05 | 1.83 | 21.81 |
Maximum of Months | 342.50 | 26.19 | 491.33 | 24.64 | 111.50 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 467.83 | 21.09 | 231.67 | 20.86 | 231.67 | 20.74 |
February | 392.50 | 21.38 | 132.83 | 21.22 | 122.00 | 21.07 |
March | 418.67 | 22.02 | 91.83 | 22.09 | 52.50 | 21.95 |
April | 302.00 | 22.94 | 83.67 | 23.30 | 11.83 | 23.37 |
May | 191.50 | 23.21 | 166.33 | 23.81 | 10.67 | 23.91 |
June | 86.17 | 23.89 | 345.67 | 24.34 | 17.83 | 24.45 |
July | 45.17 | 25.73 | 474.67 | 24.55 | 42.50 | 24.65 |
August | 35.50 | 25.37 | 474.33 | 24.42 | 27.83 | 24.50 |
September | 100.83 | 23.75 | 319.00 | 24.26 | 21.83 | 24.37 |
October | 300.83 | 22.57 | 142.83 | 23.07 | 25.17 | 23.08 |
November | 420.67 | 21.72 | 90.00 | 21.60 | 77.33 | 21.44 |
December | 465.67 | 21.09 | 247.83 | 20.86 | 247.83 | 20.76 |
Annual Sum or Average | 3227.33 | 22.03 | 2800.67 | 22.66 | 889.00 | 22.49 |
Minimum of Months | 35.50 | 21.09 | 83.67 | 20.86 | 10.67 | 20.74 |
Maximum of Months | 467.83 | 25.73 | 474.67 | 24.55 | 247.83 | 24.65 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.89284 | 15.83398 | 0.11667 | 5.49140 |
February | 454.00000 | 24.06013 | 16.59177 | 0.17363 | 5.79028 |
March | 514.00000 | 24.21169 | 15.93749 | 0.23252 | 6.24268 |
April | 485.00000 | 24.36509 | 13.70506 | 0.27946 | 6.81871 |
May | 508.00000 | 24.35444 | 21.28585 | -0.5058 | 10.84904 |
June | 496.00000 | 24.37079 | 31.45853 | -0.4015 | 8.81214 |
July | 497.00000 | 24.46024 | 41.44626 | -0.2943 | 7.26998 |
August | 514.00000 | 24.40463 | 41.32937 | -0.3078 | 7.42275 |
September | 485.00000 | 24.44338 | 35.83639 | -0.3507 | 8.12713 |
October | 502.00000 | 24.38320 | 22.35520 | 0.35689 | 8.02480 |
November | 489.00000 | 24.25685 | 16.55716 | 0.25033 | 6.46351 |
December | 497.00000 | 23.97519 | 13.94532 | 0.12844 | 5.49447 |
Annual Sum or Average | 5943.00000 | 24.26598 | 23.92884 | -0.0291 | 7.24775 |
Minimum of Months | 454.00000 | 23.89284 | 13.70506 | -0.5058 | 5.49140 |
Maximum of Months | 514.00000 | 24.46024 | 41.44626 | 0.35689 | 10.84904 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.62843 | 18.01631 | -0.1797 | 6.54117 |
February | 454.00000 | 23.03853 | 18.75063 | -0.0703 | 5.86754 |
March | 514.00000 | 23.62865 | 17.47101 | 0.08263 | 5.57825 |
April | 485.00000 | 24.03606 | 14.56382 | 0.18723 | 5.96237 |
May | 508.00000 | 24.16154 | 22.09824 | -0.5950 | 12.91308 |
June | 496.00000 | 24.25361 | 32.29807 | -0.4624 | 9.82122 |
July | 497.00000 | 24.35057 | 42.61930 | -0.3462 | 7.82648 |
August | 514.00000 | 24.30749 | 42.38179 | -0.3620 | 8.04242 |
September | 485.00000 | 24.29957 | 36.67660 | -0.4276 | 9.22173 |
October | 502.00000 | 24.03086 | 23.44409 | 0.25171 | 6.85106 |
November | 489.00000 | 23.51126 | 18.39027 | 0.05708 | 5.60145 |
December | 497.00000 | 22.69716 | 16.14329 | -0.1744 | 6.39187 |
Annual Sum or Average | 5943.00000 | 23.75029 | 25.30464 | -0.1714 | 7.57006 |
Minimum of Months | 454.00000 | 22.62843 | 14.56382 | -0.5950 | 5.57825 |
Maximum of Months | 514.00000 | 24.35057 | 42.61930 | 0.25171 | 12.91308 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.67306 | 18.81120 | -0.4197 | 10.33276 |
February | 454.00000 | 22.17671 | 19.46251 | -0.2832 | 8.32135 |
March | 514.00000 | 23.03744 | 18.12404 | -0.0628 | 6.21873 |
April | 485.00000 | 23.74318 | 14.73439 | 0.11481 | 5.86775 |
May | 508.00000 | 24.00479 | 21.97582 | -0.6478 | 14.62226 |
June | 496.00000 | 24.19937 | 32.26252 | -0.4713 | 10.07648 |
July | 497.00000 | 24.32888 | 42.70061 | -0.3371 | 7.71749 |
August | 514.00000 | 24.27264 | 42.51959 | -0.3634 | 8.06269 |
September | 485.00000 | 24.18184 | 36.44699 | -0.4725 | 10.14244 |
October | 502.00000 | 23.60903 | 23.84714 | 0.14147 | 6.58693 |
November | 489.00000 | 22.67338 | 19.49737 | -0.1509 | 6.91134 |
December | 497.00000 | 21.65037 | 16.88926 | -0.4363 | 10.52791 |
Annual Sum or Average | 5943.00000 | 23.30425 | 25.67063 | -0.2830 | 8.79199 |
Minimum of Months | 454.00000 | 21.65037 | 14.73439 | -0.6478 | 5.86775 |
Maximum of Months | 514.00000 | 24.32888 | 42.70061 | 0.14147 | 14.62226 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.45860 | 20.19979 | -0.7437 | 18.70813 |
February | 454.00000 | 20.90815 | 21.24795 | -0.6042 | 14.76061 |
March | 514.00000 | 21.94193 | 19.91056 | -0.3235 | 9.48389 |
April | 485.00000 | 23.12386 | 15.81633 | -0.0238 | 6.87600 |
May | 508.00000 | 23.76439 | 22.85673 | -0.7106 | 17.87891 |
June | 496.00000 | 24.22559 | 32.35942 | -0.4113 | 9.71519 |
July | 497.00000 | 24.44939 | 42.90623 | -0.2387 | 7.22473 |
August | 514.00000 | 24.27095 | 42.87822 | -0.3233 | 8.05160 |
September | 485.00000 | 23.98885 | 37.47651 | -0.5244 | 12.36675 |
October | 502.00000 | 22.75413 | 25.62071 | -0.0636 | 7.92347 |
November | 489.00000 | 21.25276 | 21.09083 | -0.4968 | 12.43410 |
December | 497.00000 | 20.35701 | 18.45650 | -0.7835 | 19.71761 |
Annual Sum or Average | 5943.00000 | 22.63802 | 26.79473 | -0.4364 | 12.07945 |
Minimum of Months | 454.00000 | 20.35701 | 15.81633 | -0.7835 | 6.87600 |
Maximum of Months | 514.00000 | 24.44939 | 42.90623 | -0.0238 | 19.71761 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.93821 | 19.00132 | -0.5958 | 14.71366 |
February | 454.00000 | 21.43389 | 19.94721 | -0.4365 | 12.01808 |
March | 514.00000 | 22.52255 | 18.40529 | -0.1304 | 8.41649 |
April | 485.00000 | 23.67014 | 14.39151 | 0.19740 | 8.13061 |
May | 508.00000 | 24.01158 | 21.86067 | -0.4974 | 14.34352 |
June | 496.00000 | 24.31703 | 31.96240 | -0.2407 | 8.67230 |
July | 497.00000 | 24.55925 | 42.30390 | -0.0660 | 7.85022 |
August | 514.00000 | 24.35187 | 42.32458 | -0.1562 | 7.73031 |
September | 485.00000 | 24.08325 | 36.72269 | -0.3666 | 10.58277 |
October | 502.00000 | 23.25456 | 24.20715 | 0.11761 | 8.76706 |
November | 489.00000 | 21.84182 | 19.70544 | -0.3172 | 9.68062 |
December | 497.00000 | 20.74253 | 17.43559 | -0.6497 | 16.02947 |
Annual Sum or Average | 5943.00000 | 22.98912 | 25.75085 | -0.2609 | 10.56856 |
Minimum of Months | 454.00000 | 20.74253 | 14.39151 | -0.6497 | 7.73031 |
Maximum of Months | 514.00000 | 24.55925 | 42.32458 | 0.19740 | 16.02947 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.22530 | 17.32188 | -0.2355 | 12.98115 |
February | 454.00000 | 22.48411 | 18.26012 | -0.1384 | 11.47096 |
March | 514.00000 | 22.81022 | 17.83254 | -0.0502 | 9.06701 |
April | 485.00000 | 23.44578 | 14.69463 | 0.10962 | 7.89247 |
May | 508.00000 | 23.75818 | 22.55191 | -0.6757 | 17.90910 |
June | 496.00000 | 24.10706 | 32.51624 | -0.4431 | 10.96056 |
July | 497.00000 | 24.41284 | 42.88237 | -0.2267 | 7.63374 |
August | 514.00000 | 24.29444 | 42.54317 | -0.2438 | 7.93554 |
September | 485.00000 | 24.18496 | 36.37272 | -0.3276 | 10.70790 |
October | 502.00000 | 23.67149 | 23.22865 | 0.26358 | 10.80383 |
November | 489.00000 | 22.93561 | 17.94351 | -0.0031 | 10.12350 |
December | 497.00000 | 22.22547 | 15.59345 | -0.2307 | 13.20188 |
Annual Sum or Average | 5943.00000 | 23.38578 | 25.21766 | -0.1847 | 10.89489 |
Minimum of Months | 454.00000 | 22.22530 | 14.69463 | -0.6757 | 7.63374 |
Maximum of Months | 514.00000 | 24.41284 | 42.88237 | 0.26358 | 17.90910 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.91107 | 18.77726 | -0.6067 | 16.50894 |
February | 454.00000 | 21.38058 | 19.72682 | -0.4499 | 13.42793 |
March | 514.00000 | 22.05205 | 18.78751 | -0.2425 | 9.96461 |
April | 485.00000 | 23.09160 | 15.18748 | 0.04739 | 8.50859 |
May | 508.00000 | 23.56522 | 22.82668 | -0.6678 | 19.18642 |
June | 496.00000 | 24.03747 | 32.68699 | -0.3729 | 11.56923 |
July | 497.00000 | 24.30094 | 43.13247 | -0.1922 | 8.26969 |
August | 514.00000 | 24.16331 | 42.98990 | -0.2514 | 8.67116 |
September | 485.00000 | 23.86308 | 37.41005 | -0.4531 | 13.18373 |
October | 502.00000 | 22.80563 | 24.78287 | 0.01920 | 9.28499 |
November | 489.00000 | 21.56958 | 19.71540 | -0.3786 | 11.51937 |
December | 497.00000 | 20.87102 | 17.06144 | -0.6311 | 17.06113 |
Annual Sum or Average | 5943.00000 | 22.72791 | 26.15724 | -0.3480 | 12.25843 |
Minimum of Months | 454.00000 | 20.87102 | 15.18748 | -0.6678 | 8.26969 |
Maximum of Months | 514.00000 | 24.30094 | 43.13247 | 0.04739 | 19.18642 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.79549 | 20.15189 | -0.6424 | 14.46341 |
February | 454.00000 | 21.05810 | 21.31864 | -0.5619 | 12.50941 |
March | 514.00000 | 21.84749 | 20.37931 | -0.3528 | 8.67328 |
April | 485.00000 | 23.10882 | 16.58360 | -0.0519 | 6.07778 |
May | 508.00000 | 23.77619 | 23.52267 | -0.7475 | 17.98217 |
June | 496.00000 | 24.22326 | 32.32103 | -0.4532 | 9.82429 |
July | 497.00000 | 24.42748 | 42.25122 | -0.2856 | 7.23377 |
August | 514.00000 | 24.30525 | 42.18520 | -0.3384 | 7.79407 |
September | 485.00000 | 24.19351 | 37.25290 | -0.4617 | 10.02905 |
October | 502.00000 | 23.33575 | 25.10219 | 0.07912 | 6.64309 |
November | 489.00000 | 22.01231 | 20.46919 | -0.3014 | 8.02391 |
December | 497.00000 | 20.85003 | 18.11613 | -0.6311 | 13.99053 |
Annual Sum or Average | 5943.00000 | 22.84004 | 26.69659 | -0.3954 | 10.26935 |
Minimum of Months | 454.00000 | 20.79549 | 16.58360 | -0.7475 | 6.07778 |
Maximum of Months | 514.00000 | 24.42748 | 42.25122 | 0.07912 | 17.98217 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.47263 | 18.80733 | -0.4456 | 10.51055 |
February | 454.00000 | 21.81351 | 19.83078 | -0.3399 | 9.14603 |
March | 514.00000 | 22.84270 | 18.41746 | -0.0683 | 6.91386 |
April | 485.00000 | 23.96141 | 14.44044 | 0.24042 | 7.38865 |
May | 508.00000 | 24.21479 | 21.92627 | -0.4652 | 11.85413 |
June | 496.00000 | 24.41651 | 31.58221 | -0.2425 | 7.69317 |
July | 497.00000 | 24.63894 | 41.28762 | -0.0728 | 6.96887 |
August | 514.00000 | 24.47704 | 41.32795 | -0.1342 | 6.77677 |
September | 485.00000 | 24.38470 | 36.28254 | -0.2669 | 7.84271 |
October | 502.00000 | 23.90763 | 23.45804 | 0.28151 | 8.45397 |
November | 489.00000 | 22.87500 | 18.77399 | -0.0602 | 6.41250 |
December | 497.00000 | 21.50117 | 16.87642 | -0.4386 | 10.17404 |
Annual Sum or Average | 5943.00000 | 23.38611 | 25.31070 | -0.1672 | 8.34429 |
Minimum of Months | 454.00000 | 21.47263 | 14.44044 | -0.4652 | 6.41250 |
Maximum of Months | 514.00000 | 24.63894 | 41.32795 | 0.28151 | 11.85413 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.66616 | 16.20398 | -0.0775 | 9.35026 |
February | 454.00000 | 22.79485 | 17.42789 | -0.0319 | 8.43219 |
March | 514.00000 | 22.92530 | 17.45208 | -0.0149 | 7.33325 |
April | 485.00000 | 23.50718 | 14.73023 | 0.10853 | 6.76419 |
May | 508.00000 | 23.63625 | 22.78306 | -0.7442 | 18.98510 |
June | 496.00000 | 24.06745 | 31.89649 | -0.5012 | 11.43974 |
July | 497.00000 | 24.44123 | 42.03789 | -0.2589 | 7.31802 |
August | 514.00000 | 24.36960 | 41.67997 | -0.2400 | 7.28613 |
September | 485.00000 | 24.41911 | 35.82834 | -0.2400 | 8.31276 |
October | 502.00000 | 24.15213 | 22.35141 | 0.40621 | 11.14325 |
November | 489.00000 | 23.68310 | 16.64645 | 0.21743 | 8.19453 |
December | 497.00000 | 22.81050 | 14.11578 | -0.0346 | 8.62968 |
Annual Sum or Average | 5943.00000 | 23.62700 | 24.50358 | -0.1195 | 9.45555 |
Minimum of Months | 454.00000 | 22.66616 | 14.11578 | -0.7442 | 6.76419 |
Maximum of Months | 514.00000 | 24.44123 | 42.03789 | 0.40621 | 18.98510 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.35687 | 18.71424 | -0.4713 | 11.36758 |
February | 454.00000 | 21.75521 | 19.65924 | -0.3506 | 9.67678 |
March | 514.00000 | 22.38838 | 18.83168 | -0.1777 | 7.62968 |
April | 485.00000 | 23.56512 | 15.21199 | 0.12624 | 6.85947 |
May | 508.00000 | 23.91222 | 22.84697 | -0.6006 | 14.86967 |
June | 496.00000 | 24.26705 | 32.12027 | -0.3395 | 9.15121 |
July | 497.00000 | 24.46593 | 41.94782 | -0.1785 | 6.90440 |
August | 514.00000 | 24.38649 | 41.74707 | -0.2032 | 6.90875 |
September | 485.00000 | 24.34345 | 36.52328 | -0.3033 | 8.35442 |
October | 502.00000 | 23.67339 | 23.84652 | 0.22553 | 8.14312 |
November | 489.00000 | 22.55058 | 18.86787 | -0.1303 | 6.94988 |
December | 497.00000 | 21.44295 | 16.70540 | -0.4534 | 10.96280 |
Annual Sum or Average | 5943.00000 | 23.18489 | 25.64948 | -0.2382 | 8.98711 |
Minimum of Months | 454.00000 | 21.35687 | 15.21199 | -0.6006 | 6.85947 |
Maximum of Months | 514.00000 | 24.46593 | 41.94782 | 0.22553 | 14.86967 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.91597 | 20.11808 | -0.5970 | 13.76104 |
February | 454.00000 | 21.40109 | 21.11685 | -0.4590 | 10.89230 |
March | 514.00000 | 22.47925 | 19.63651 | -0.1858 | 7.27100 |
April | 485.00000 | 23.51265 | 15.66188 | 0.06751 | 6.05546 |
May | 508.00000 | 23.99197 | 22.84111 | -0.6385 | 14.84765 |
June | 496.00000 | 24.31347 | 32.25232 | -0.3938 | 8.99060 |
July | 497.00000 | 24.50428 | 42.68370 | -0.2386 | 7.05283 |
August | 514.00000 | 24.33681 | 42.56854 | -0.3136 | 7.65847 |
September | 485.00000 | 24.17736 | 37.43121 | -0.4619 | 10.31066 |
October | 502.00000 | 23.24166 | 25.25258 | 0.05899 | 6.89747 |
November | 489.00000 | 21.94189 | 20.62417 | -0.3148 | 8.68119 |
December | 497.00000 | 20.82791 | 18.38075 | -0.6294 | 14.31512 |
Annual Sum or Average | 5943.00000 | 22.98223 | 26.60632 | -0.3418 | 9.72470 |
Minimum of Months | 454.00000 | 20.82791 | 15.66188 | -0.6385 | 6.05546 |
Maximum of Months | 514.00000 | 24.50428 | 42.68370 | 0.06751 | 14.84765 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.26647 | 18.11765 | -0.4926 | 11.88915 |
February | 385.00000 | 21.71180 | 19.08556 | -0.3531 | 9.95374 |
March | 433.00000 | 22.69061 | 17.75998 | -0.0836 | 7.56716 |
April | 410.00000 | 23.82937 | 14.20452 | 0.22381 | 7.97312 |
May | 430.00000 | 24.14351 | 21.99593 | -0.4740 | 13.56693 |
June | 418.00000 | 24.43031 | 31.39853 | -0.2435 | 8.62902 |
July | 422.00000 | 24.69297 | 41.49531 | -0.0724 | 8.06005 |
August | 433.00000 | 24.46545 | 41.55655 | -0.1646 | 7.79981 |
September | 410.00000 | 24.23740 | 36.44498 | -0.3437 | 9.86634 |
October | 427.00000 | 23.48286 | 23.56162 | 0.17112 | 8.51907 |
November | 417.00000 | 22.20465 | 18.76916 | -0.2138 | 8.06242 |
December | 422.00000 | 21.14806 | 16.53915 | -0.5288 | 12.52470 |
Annual Sum or Average | 5034.00000 | 23.20039 | 25.12822 | -0.2142 | 9.53597 |
Minimum of Months | 385.00000 | 21.14806 | 14.20452 | -0.5288 | 7.56716 |
Maximum of Months | 433.00000 | 24.69297 | 41.55655 | 0.22381 | 13.56693 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.69631 | 16.89348 | -0.0920 | 10.57998 |
February | 454.00000 | 22.93249 | 17.82101 | -0.0075 | 9.44432 |
March | 514.00000 | 23.22576 | 17.37893 | 0.06063 | 7.75017 |
April | 485.00000 | 23.76464 | 14.52048 | 0.18575 | 7.25622 |
May | 508.00000 | 23.99265 | 22.53112 | -0.6026 | 14.71819 |
June | 496.00000 | 24.21984 | 32.35908 | -0.4189 | 9.78408 |
July | 497.00000 | 24.47910 | 42.60054 | -0.2241 | 7.25026 |
August | 514.00000 | 24.37216 | 42.16895 | -0.2328 | 7.35535 |
September | 485.00000 | 24.35825 | 36.35466 | -0.2721 | 8.96919 |
October | 502.00000 | 24.02502 | 22.90726 | 0.35697 | 10.74999 |
November | 489.00000 | 23.44275 | 17.29107 | 0.13781 | 9.01200 |
December | 497.00000 | 22.72935 | 15.11876 | -0.0782 | 10.37902 |
Annual Sum or Average | 5943.00000 | 23.69137 | 24.90165 | -0.1005 | 9.44427 |
Minimum of Months | 454.00000 | 22.69631 | 14.52048 | -0.6026 | 7.25026 |
Maximum of Months | 514.00000 | 24.47910 | 42.60054 | 0.35697 | 14.71819 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.29894 | 18.46799 | -0.4762 | 12.42482 |
February | 454.00000 | 21.75037 | 19.44204 | -0.3307 | 10.34385 |
March | 514.00000 | 22.44533 | 18.46045 | -0.1334 | 8.08909 |
April | 485.00000 | 23.43794 | 15.05139 | 0.12976 | 7.67409 |
May | 508.00000 | 23.83659 | 22.80344 | -0.5848 | 15.53192 |
June | 496.00000 | 24.17590 | 32.48726 | -0.3426 | 10.02302 |
July | 497.00000 | 24.39232 | 42.78809 | -0.1831 | 7.57518 |
August | 514.00000 | 24.27196 | 42.58091 | -0.2318 | 7.78462 |
September | 485.00000 | 24.09696 | 37.30978 | -0.3802 | 10.56895 |
October | 502.00000 | 23.20088 | 24.43587 | 0.12285 | 8.44301 |
November | 489.00000 | 22.07001 | 19.15818 | -0.2347 | 8.65784 |
December | 497.00000 | 21.27744 | 16.72685 | -0.4929 | 12.63464 |
Annual Sum or Average | 5943.00000 | 23.03063 | 25.87581 | -0.2616 | 9.98121 |
Minimum of Months | 454.00000 | 21.27744 | 15.05139 | -0.5848 | 7.57518 |
Maximum of Months | 514.00000 | 24.39232 | 42.78809 | 0.12976 | 15.53192 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.144076E+09 | 41543348.45 | 15.62 | 0.143835E+09 | 241328.97 | 0.00 | 0.28 | 01-JAN-14:32 | 0.00 | 01-JAN-00:10 | 8829.30 | 01-JAN-14:32 | 8829.30 | 01-JAN-14:32 | 84.59 | 01-JAN-15:18 | 2444.61 | 01-JAN-14:32 | 0.00 |
February | 0.119027E+10 | 0.303504E+09 | 26.67 | 0.118843E+10 | 1837110.49 | 0.00 | 0.90 | 14-FEB-16:10 | 0.00 | 01-FEB-00:10 | 32760.21 | 14-FEB-16:10 | 32760.21 | 14-FEB-16:10 | 328.27 | 19-FEB-15:10 | 7707.80 | 14-FEB-16:10 | 0.00 |
March | 0.351248E+10 | 0.938593E+09 | 112.26 | 0.350990E+10 | 2582593.10 | 0.00 | 0.90 | 08-MAR-16:10 | 0.00 | 01-MAR-00:10 | 32771.86 | 08-MAR-16:10 | 32771.86 | 08-MAR-16:10 | 258.34 | 07-MAR-18:30 | 7709.97 | 08-MAR-16:10 | 0.00 |
April | 0.154436E+11 | 0.382980E+10 | 222.97 | 0.154304E+11 | 13136806.38 | 0.00 | 1.00 | 11-APR-13:30 | 0.00 | 01-APR-00:10 | 54175.21 | 28-APR-15:10 | 54175.21 | 28-APR-15:10 | 998.43 | 14-APR-20:00 | 12853.50 | 13-APR-16:00 | 0.00 |
May | 0.295510E+11 | 0.738616E+10 | 331.23 | 0.289259E+11 | 0.625073E+09 | 0.00 | 1.00 | 08-MAY-12:10 | 0.00 | 01-MAY-00:10 | 62392.29 | 19-MAY-16:00 | 62392.29 | 19-MAY-16:00 | 7769.35 | 24-MAY-13:00 | 16706.95 | 19-MAY-16:00 | 0.00 |
June | 0.597090E+11 | 0.162679E+11 | 427.77 | 0.582671E+11 | 0.144194E+10 | 0.00 | 1.00 | 02-JUN-13:50 | 0.00 | 01-JUN-00:10 | 90275.45 | 29-JUN-06:03 | 80612.20 | 28-JUN-15:10 | 13342.97 | 29-JUN-06:03 | 27793.45 | 28-JUN-15:10 | 0.00 |
July | 0.780542E+11 | 0.210226E+11 | 458.64 | 0.699847E+11 | 0.806943E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 84970.89 | 31-JUL-15:30 | 80724.90 | 21-JUL-15:10 | 27110.54 | 17-JUL-09:40 | 27228.68 | 21-JUL-15:10 | 0.00 |
August | 0.765899E+11 | 0.197874E+11 | 466.46 | 0.682338E+11 | 0.835608E+10 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 92904.14 | 21-AUG-06:03 | 79271.28 | 07-AUG-16:00 | 43811.40 | 14-AUG-06:03 | 23887.47 | 01-AUG-15:40 | 0.00 |
September | 0.509589E+11 | 0.126266E+11 | 402.07 | 0.467985E+11 | 0.416041E+10 | 0.00 | 1.00 | 01-SEP-07:50 | 0.00 | 01-SEP-00:10 | 100196.86 | 05-SEP-13:00 | 67704.31 | 13-SEP-16:00 | 42350.26 | 05-SEP-13:00 | 23060.00 | 05-SEP-13:00 | 0.00 |
October | 0.222264E+11 | 0.544138E+10 | 249.26 | 0.211318E+11 | 0.109461E+10 | 0.00 | 1.00 | 01-OCT-14:11 | 0.00 | 01-OCT-00:10 | 68213.78 | 02-OCT-15:10 | 64980.84 | 06-OCT-16:00 | 14705.42 | 11-OCT-06:03 | 16678.50 | 02-OCT-15:10 | 0.00 |
November | 0.880309E+09 | 0.244976E+09 | 42.30 | 0.851842E+09 | 28467201.40 | 0.00 | 0.52 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 | 17287.71 | 02-NOV-15:00 | 17287.71 | 02-NOV-15:00 | 1404.89 | 02-NOV-13:30 | 4505.02 | 02-NOV-15:00 | 0.00 |
December | 255765.86 | 74749.28 | 0.04 | 255765.86 | 0.00 | 0.00 | 0.06 | 24-DEC-14:32 | 0.00 | 01-DEC-00:10 | 1705.11 | 24-DEC-14:32 | 1705.11 | 24-DEC-14:32 | 0.00 | 24-DEC-14:32 | 498.33 | 24-DEC-14:32 | 0.00 |
Annual Sum or Average | 0.338260E+12 | 0.878905E+11 | 2755.29 | 0.314467E+12 | 0.237938E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 255765.86 | 74749.28 | 0.04 | 255765.86 | 0.00 | 0.00 | 0.06 | 0.00 | 1705.11 | 1705.11 | 0.00 | 498.33 | 0.00 | ||||||
Maximum of Months | 0.780542E+11 | 0.210226E+11 | 466.46 | 0.699847E+11 | 0.835608E+10 | 0.00 | 1.00 | 0.00 | 100196.86 | 80724.90 | 43811.40 | 27793.45 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.287961E+09 | 81600427.77 | 21.42 | 0.287715E+09 | 245869.43 | 0.00 | 0.33 | 05-JAN-14:00 | 0.00 | 01-JAN-00:10 | 9215.44 | 05-JAN-14:00 | 9215.44 | 05-JAN-14:00 | 82.86 | 05-JAN-12:40 | 2524.50 | 05-JAN-14:00 | 0.00 |
February | 0.120227E+10 | 0.308782E+09 | 30.03 | 0.120146E+10 | 810022.94 | 0.00 | 0.91 | 14-FEB-15:30 | 0.00 | 01-FEB-00:10 | 30001.94 | 14-FEB-15:30 | 30001.94 | 14-FEB-15:30 | 201.66 | 19-FEB-14:53 | 7027.86 | 14-FEB-15:30 | 0.00 |
March | 0.336882E+10 | 0.896859E+09 | 114.25 | 0.336618E+10 | 2645280.06 | 0.00 | 0.93 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 | 30833.43 | 08-MAR-16:00 | 30833.43 | 08-MAR-16:00 | 230.23 | 20-MAR-12:15 | 7181.01 | 08-MAR-16:00 | 0.00 |
April | 0.145722E+11 | 0.360535E+10 | 229.08 | 0.145580E+11 | 14190310.86 | 0.00 | 1.00 | 11-APR-13:00 | 0.00 | 01-APR-00:10 | 52569.42 | 13-APR-15:20 | 52569.42 | 13-APR-15:20 | 1034.74 | 14-APR-20:00 | 12401.36 | 13-APR-15:20 | 0.00 |
May | 0.272904E+11 | 0.680393E+10 | 333.15 | 0.267625E+11 | 0.527938E+09 | 0.00 | 1.00 | 08-MAY-12:10 | 0.00 | 01-MAY-00:10 | 59187.99 | 19-MAY-15:20 | 59187.99 | 19-MAY-15:20 | 6740.50 | 24-MAY-13:00 | 15846.43 | 19-MAY-15:20 | 0.00 |
June | 0.540589E+11 | 0.147289E+11 | 424.73 | 0.528892E+11 | 0.116976E+10 | 0.00 | 1.00 | 02-JUN-13:50 | 0.00 | 01-JUN-00:10 | 79559.83 | 29-JUN-06:03 | 75523.79 | 26-JUN-15:00 | 13012.34 | 29-JUN-06:03 | 25636.91 | 28-JUN-14:50 | 0.00 |
July | 0.696625E+11 | 0.187807E+11 | 452.56 | 0.628126E+11 | 0.684998E+10 | 0.00 | 1.00 | 01-JUL-10:00 | 0.00 | 01-JUL-00:10 | 82276.99 | 31-JUL-15:00 | 74957.22 | 31-JUL-15:00 | 24774.02 | 17-JUL-06:03 | 25056.51 | 21-JUL-14:50 | 0.00 |
August | 0.671558E+11 | 0.174051E+11 | 462.49 | 0.602369E+11 | 0.691897E+10 | 0.00 | 1.00 | 01-AUG-07:30 | 0.00 | 01-AUG-00:10 | 82607.06 | 14-AUG-06:03 | 76394.90 | 07-AUG-15:40 | 46061.31 | 14-AUG-06:03 | 22543.66 | 20-AUG-16:01 | 0.00 |
September | 0.433802E+11 | 0.107868E+11 | 395.22 | 0.399259E+11 | 0.345433E+10 | 0.00 | 1.00 | 01-SEP-08:70 | 0.00 | 01-SEP-00:10 | 88422.12 | 05-SEP-13:00 | 63889.56 | 13-SEP-16:00 | 37340.04 | 05-SEP-13:00 | 20441.76 | 05-SEP-13:30 | 0.00 |
October | 0.187911E+11 | 0.462346E+10 | 243.58 | 0.179197E+11 | 0.871459E+09 | 0.00 | 1.00 | 01-OCT-10:22 | 0.00 | 01-OCT-00:10 | 63471.58 | 02-OCT-14:50 | 59967.21 | 02-OCT-15:00 | 10129.29 | 02-OCT-17:00 | 15705.89 | 02-OCT-14:50 | 0.00 |
November | 0.760015E+09 | 0.212559E+09 | 47.22 | 0.720175E+09 | 39840613.24 | 0.00 | 0.57 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 | 16964.77 | 02-NOV-15:00 | 16905.97 | 02-NOV-15:00 | 1712.34 | 02-NOV-13:00 | 4371.22 | 02-NOV-15:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.300530E+12 | 0.782341E+11 | 2753.71 | 0.280680E+12 | 0.198502E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.696625E+11 | 0.187807E+11 | 462.49 | 0.628126E+11 | 0.691897E+10 | 0.00 | 1.00 | 0.00 | 88422.12 | 76394.90 | 46061.31 | 25636.91 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.131364E+09 | 37893892.74 | 14.67 | 0.131024E+09 | 339442.64 | 0.00 | 0.20 | 05-JAN-14:00 | 0.00 | 01-JAN-00:10 | 6368.22 | 05-JAN-14:00 | 6368.22 | 05-JAN-14:00 | 64.05 | 01-JAN-15:15 | 1798.71 | 05-JAN-14:00 | 0.00 |
February | 0.110702E+10 | 0.288800E+09 | 27.95 | 0.110577E+10 | 1250249.03 | 0.00 | 0.80 | 14-FEB-15:40 | 0.00 | 01-FEB-00:10 | 29222.20 | 14-FEB-15:40 | 29222.20 | 14-FEB-15:40 | 294.62 | 19-FEB-15:10 | 7075.62 | 14-FEB-15:40 | 0.00 |
March | 0.325293E+10 | 0.877096E+09 | 112.17 | 0.324231E+10 | 10625208.24 | 0.00 | 0.85 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 | 31712.60 | 08-MAR-16:00 | 31712.60 | 08-MAR-16:00 | 436.82 | 20-MAR-12:40 | 7561.01 | 08-MAR-16:00 | 0.00 |
April | 0.150710E+11 | 0.375745E+10 | 223.95 | 0.150484E+11 | 22618625.16 | 0.00 | 1.00 | 11-APR-13:20 | 0.00 | 01-APR-00:10 | 59554.61 | 26-APR-15:00 | 59554.61 | 26-APR-15:00 | 1436.30 | 14-APR-19:50 | 14187.90 | 26-APR-15:00 | 0.00 |
May | 0.291832E+11 | 0.733519E+10 | 333.03 | 0.285503E+11 | 0.632832E+09 | 0.00 | 1.00 | 08-MAY-12:20 | 0.00 | 01-MAY-00:10 | 68808.90 | 19-MAY-15:20 | 68808.90 | 19-MAY-15:20 | 7073.97 | 24-MAY-13:00 | 18421.83 | 19-MAY-15:20 | 0.00 |
June | 0.592037E+11 | 0.162836E+11 | 425.01 | 0.578419E+11 | 0.136173E+10 | 0.00 | 1.00 | 02-JUN-14:30 | 0.00 | 01-JUN-00:10 | 88774.56 | 29-JUN-14:30 | 88774.56 | 29-JUN-14:30 | 7828.13 | 08-JUN-09:40 | 29973.36 | 28-JUN-14:50 | 0.00 |
July | 0.759540E+11 | 0.206609E+11 | 453.83 | 0.688361E+11 | 0.711788E+10 | 0.00 | 1.00 | 01-JUL-10:30 | 0.00 | 01-JUL-00:10 | 91440.09 | 23-JUL-15:11 | 91440.09 | 23-JUL-15:11 | 23335.73 | 17-JUL-09:50 | 29429.79 | 23-JUL-14:32 | 0.00 |
August | 0.722681E+11 | 0.189032E+11 | 463.49 | 0.652257E+11 | 0.704236E+10 | 0.00 | 1.00 | 01-AUG-08:00 | 0.00 | 01-AUG-00:10 | 91208.55 | 20-AUG-15:31 | 91208.55 | 20-AUG-15:31 | 32512.12 | 23-AUG-16:00 | 28286.90 | 20-AUG-15:31 | 0.00 |
September | 0.456330E+11 | 0.114549E+11 | 394.55 | 0.420930E+11 | 0.353998E+10 | 0.00 | 1.00 | 01-SEP-08:50 | 0.00 | 01-SEP-00:10 | 91530.23 | 05-SEP-13:30 | 74533.20 | 03-SEP-13:52 | 36625.39 | 05-SEP-13:00 | 21643.00 | 03-SEP-13:52 | 0.00 |
October | 0.186898E+11 | 0.464678E+10 | 238.07 | 0.178169E+11 | 0.872916E+09 | 0.00 | 1.00 | 01-OCT-12:32 | 0.00 | 01-OCT-00:10 | 68952.51 | 02-OCT-14:30 | 65756.25 | 02-OCT-15:00 | 10911.83 | 02-OCT-17:00 | 16991.30 | 02-OCT-14:30 | 0.00 |
November | 0.525626E+09 | 0.148930E+09 | 39.27 | 0.478430E+09 | 47195823.94 | 0.00 | 0.41 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 | 13687.33 | 02-NOV-15:00 | 13435.95 | 02-NOV-15:00 | 1661.50 | 02-NOV-13:30 | 3670.27 | 02-NOV-15:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.321020E+12 | 0.843948E+11 | 2725.97 | 0.300370E+12 | 0.206497E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.759540E+11 | 0.206609E+11 | 463.49 | 0.688361E+11 | 0.711788E+10 | 0.00 | 1.00 | 0.00 | 91530.23 | 91440.09 | 36625.39 | 29973.36 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 519.13 | 0.00 | 519.13 | 130.25 | 1772.29 | 0.00 | 0.00 | 0.00 |
February | 648.82 | 0.00 | 648.82 | 254.18 | 1611.45 | 0.00 | 0.00 | 0.00 |
March | 818.41 | 0.00 | 818.41 | 517.13 | 1276.80 | 0.00 | 0.00 | 0.00 |
April | 1038.30 | 8.89 | 1029.41 | 821.62 | 862.10 | 0.00 | 0.00 | 0.00 |
May | 1128.64 | 72.77 | 1055.88 | 1133.83 | 638.44 | 0.00 | 0.00 | 0.00 |
June | 1282.44 | 209.87 | 1072.57 | 1747.71 | 430.01 | 0.00 | 0.00 | 0.00 |
July | 1177.08 | 97.97 | 1079.11 | 1734.92 | 296.86 | 0.00 | 0.00 | 0.00 |
August | 1091.94 | 24.45 | 1067.49 | 1469.64 | 333.45 | 0.00 | 0.00 | 0.00 |
September | 873.21 | 0.22 | 872.99 | 1001.14 | 579.86 | 0.00 | 0.00 | 0.00 |
October | 651.59 | 0.00 | 651.59 | 465.71 | 1009.72 | 0.00 | 0.00 | 0.00 |
November | 553.36 | 0.00 | 553.36 | 177.37 | 1413.01 | 0.00 | 0.00 | 0.00 |
December | 441.86 | 0.00 | 441.86 | 45.38 | 1851.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 852.81 | 34.58 | 818.23 | 794.40 | 1003.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 441.86 | 0.00 | 441.86 | 45.38 | 296.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1282.44 | 209.87 | 1079.11 | 1747.71 | 1851.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 958.46 | 535.87 | 422.59 | 818.60 | 1088.11 | 0.00 | 0.00 | 0.00 |
February | 1164.50 | 627.79 | 536.71 | 1081.14 | 998.16 | 0.00 | 0.00 | 0.00 |
March | 1536.16 | 873.28 | 662.88 | 1599.88 | 797.72 | 0.00 | 0.00 | 0.00 |
April | 2098.70 | 1195.62 | 903.08 | 2397.70 | 562.27 | 0.00 | 0.00 | 0.00 |
May | 2002.61 | 1141.27 | 861.34 | 2419.02 | 432.68 | 0.00 | 0.00 | 0.00 |
June | 2158.97 | 1330.03 | 828.94 | 2877.85 | 284.13 | 0.00 | 0.00 | 0.00 |
July | 1997.73 | 1142.38 | 855.35 | 2779.14 | 198.91 | 0.00 | 0.00 | 0.00 |
August | 1976.89 | 1089.90 | 886.99 | 2665.39 | 222.77 | 0.00 | 0.00 | 0.00 |
September | 1645.43 | 920.63 | 724.80 | 2095.25 | 372.29 | 0.00 | 0.00 | 0.00 |
October | 1431.02 | 907.92 | 523.09 | 1603.29 | 632.11 | 0.00 | 0.00 | 0.00 |
November | 1118.41 | 657.51 | 460.91 | 1064.02 | 888.20 | 0.00 | 0.00 | 0.00 |
December | 906.23 | 551.52 | 354.71 | 776.36 | 1141.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1584.47 | 915.61 | 668.86 | 1851.58 | 633.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 906.23 | 535.87 | 354.71 | 776.36 | 198.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2158.97 | 1330.03 | 903.08 | 2877.85 | 1141.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3837.92 | 2986.43 | 851.49 | 4278.78 | 1651.89 | 0.00 | 0.00 | 0.00 |
February | 3755.93 | 2743.58 | 1012.35 | 4271.95 | 1533.17 | 0.00 | 0.00 | 0.00 |
March | 2767.73 | 1673.26 | 1094.47 | 3213.35 | 1262.29 | 0.00 | 0.00 | 0.00 |
April | 2158.48 | 886.02 | 1272.46 | 2594.11 | 914.50 | 0.00 | 0.00 | 0.00 |
May | 1439.53 | 316.67 | 1122.86 | 1740.24 | 680.15 | 0.00 | 0.00 | 0.00 |
June | 1217.72 | 150.07 | 1067.65 | 1744.09 | 454.80 | 0.00 | 0.00 | 0.00 |
July | 1347.47 | 215.18 | 1132.29 | 2087.66 | 309.36 | 0.00 | 0.00 | 0.00 |
August | 1852.87 | 602.28 | 1250.59 | 2743.83 | 355.34 | 0.00 | 0.00 | 0.00 |
September | 2562.12 | 1428.71 | 1133.40 | 3518.19 | 601.04 | 0.00 | 0.00 | 0.00 |
October | 3505.28 | 2581.62 | 923.66 | 4345.21 | 988.58 | 0.00 | 0.00 | 0.00 |
November | 3904.22 | 2996.48 | 907.74 | 4483.35 | 1349.03 | 0.00 | 0.00 | 0.00 |
December | 4164.03 | 3434.89 | 729.14 | 4671.28 | 1685.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2703.57 | 1662.41 | 1041.16 | 3302.18 | 979.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1217.72 | 150.07 | 729.14 | 1740.24 | 309.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4164.03 | 3434.89 | 1272.46 | 4671.28 | 1685.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 988.61 | 563.77 | 424.84 | 924.26 | 1159.38 | 0.00 | 0.00 | 0.00 |
February | 1272.67 | 735.19 | 537.49 | 1272.19 | 1064.32 | 0.00 | 0.00 | 0.00 |
March | 1421.43 | 756.66 | 664.78 | 1504.89 | 852.99 | 0.00 | 0.00 | 0.00 |
April | 1814.17 | 965.51 | 848.66 | 2060.70 | 602.67 | 0.00 | 0.00 | 0.00 |
May | 1720.10 | 886.32 | 833.78 | 2071.29 | 457.45 | 0.00 | 0.00 | 0.00 |
June | 1843.94 | 1028.90 | 815.04 | 2496.04 | 319.94 | 0.00 | 0.00 | 0.00 |
July | 1663.18 | 813.94 | 849.24 | 2352.98 | 215.65 | 0.00 | 0.00 | 0.00 |
August | 1699.47 | 786.08 | 913.40 | 2324.20 | 244.53 | 0.00 | 0.00 | 0.00 |
September | 1535.02 | 808.43 | 726.59 | 1985.02 | 401.13 | 0.00 | 0.00 | 0.00 |
October | 1404.34 | 872.85 | 531.49 | 1625.30 | 681.46 | 0.00 | 0.00 | 0.00 |
November | 1102.40 | 648.57 | 453.83 | 1089.02 | 924.30 | 0.00 | 0.00 | 0.00 |
December | 953.35 | 597.85 | 355.50 | 870.49 | 1189.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1451.69 | 788.30 | 663.39 | 1716.22 | 674.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 953.35 | 563.77 | 355.50 | 870.49 | 215.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1843.94 | 1028.90 | 913.40 | 2496.04 | 1189.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 173.03 | 0.00 | 173.03 | 41.48 | 618.88 | 0.00 | 0.00 | 0.00 |
February | 216.26 | 0.00 | 216.26 | 86.49 | 552.91 | 0.00 | 0.00 | 0.00 |
March | 272.79 | 0.00 | 272.79 | 180.31 | 429.23 | 0.00 | 0.00 | 0.00 |
April | 346.08 | 2.96 | 343.12 | 283.42 | 288.53 | 0.00 | 0.00 | 0.00 |
May | 376.20 | 24.25 | 351.94 | 387.31 | 212.44 | 0.00 | 0.00 | 0.00 |
June | 427.46 | 69.95 | 357.51 | 589.85 | 143.19 | 0.00 | 0.00 | 0.00 |
July | 392.34 | 32.65 | 359.69 | 584.84 | 98.07 | 0.00 | 0.00 | 0.00 |
August | 363.96 | 8.15 | 355.81 | 493.82 | 113.23 | 0.00 | 0.00 | 0.00 |
September | 291.06 | 0.07 | 290.98 | 334.24 | 204.07 | 0.00 | 0.00 | 0.00 |
October | 217.19 | 0.00 | 217.19 | 151.34 | 363.67 | 0.00 | 0.00 | 0.00 |
November | 184.44 | 0.00 | 184.44 | 53.19 | 512.14 | 0.00 | 0.00 | 0.00 |
December | 147.28 | 0.00 | 147.28 | 12.56 | 658.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 284.26 | 11.52 | 272.73 | 267.52 | 348.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 147.28 | 0.00 | 147.28 | 12.56 | 98.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 427.46 | 69.95 | 359.69 | 589.85 | 658.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 173.04 | 0.00 | 173.04 | 41.48 | 618.92 | 0.00 | 0.00 | 0.00 |
February | 216.27 | 0.00 | 216.27 | 86.50 | 552.94 | 0.00 | 0.00 | 0.00 |
March | 272.80 | 0.00 | 272.80 | 180.32 | 429.26 | 0.00 | 0.00 | 0.00 |
April | 346.10 | 2.96 | 343.14 | 283.43 | 288.55 | 0.00 | 0.00 | 0.00 |
May | 376.21 | 24.26 | 351.96 | 387.33 | 212.45 | 0.00 | 0.00 | 0.00 |
June | 427.48 | 69.96 | 357.52 | 589.87 | 143.20 | 0.00 | 0.00 | 0.00 |
July | 392.36 | 32.66 | 359.70 | 584.87 | 98.08 | 0.00 | 0.00 | 0.00 |
August | 363.98 | 8.15 | 355.83 | 493.84 | 113.24 | 0.00 | 0.00 | 0.00 |
September | 291.07 | 0.07 | 291.00 | 334.25 | 204.08 | 0.00 | 0.00 | 0.00 |
October | 217.20 | 0.00 | 217.20 | 151.35 | 363.69 | 0.00 | 0.00 | 0.00 |
November | 184.45 | 0.00 | 184.45 | 53.19 | 512.17 | 0.00 | 0.00 | 0.00 |
December | 147.28 | 0.00 | 147.28 | 12.56 | 658.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 284.27 | 11.53 | 272.74 | 267.53 | 348.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 147.28 | 0.00 | 147.28 | 12.56 | 98.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 427.48 | 69.96 | 359.70 | 589.87 | 658.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 173.04 | 0.00 | 173.04 | 41.48 | 618.92 | 0.00 | 0.00 | 0.00 |
February | 216.27 | 0.00 | 216.27 | 86.50 | 552.94 | 0.00 | 0.00 | 0.00 |
March | 272.80 | 0.00 | 272.80 | 180.32 | 429.26 | 0.00 | 0.00 | 0.00 |
April | 346.10 | 2.96 | 343.14 | 283.43 | 288.55 | 0.00 | 0.00 | 0.00 |
May | 376.21 | 24.26 | 351.96 | 387.33 | 212.45 | 0.00 | 0.00 | 0.00 |
June | 427.48 | 69.96 | 357.52 | 589.87 | 143.20 | 0.00 | 0.00 | 0.00 |
July | 392.36 | 32.66 | 359.70 | 584.87 | 98.08 | 0.00 | 0.00 | 0.00 |
August | 363.98 | 8.15 | 355.83 | 493.84 | 113.24 | 0.00 | 0.00 | 0.00 |
September | 291.07 | 0.07 | 291.00 | 334.25 | 204.08 | 0.00 | 0.00 | 0.00 |
October | 217.20 | 0.00 | 217.20 | 151.35 | 363.69 | 0.00 | 0.00 | 0.00 |
November | 184.45 | 0.00 | 184.45 | 53.19 | 512.17 | 0.00 | 0.00 | 0.00 |
December | 147.28 | 0.00 | 147.28 | 12.56 | 658.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 284.27 | 11.53 | 272.74 | 267.53 | 348.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 147.28 | 0.00 | 147.28 | 12.56 | 98.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 427.48 | 69.96 | 359.70 | 589.87 | 658.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 921.99 | 515.48 | 406.51 | 776.61 | 1118.64 | 0.00 | 0.00 | 0.00 |
February | 1120.19 | 603.90 | 516.29 | 1040.09 | 1014.49 | 0.00 | 0.00 | 0.00 |
March | 1477.71 | 840.05 | 637.66 | 1548.01 | 807.16 | 0.00 | 0.00 | 0.00 |
April | 2018.85 | 1150.12 | 868.72 | 2318.51 | 573.30 | 0.00 | 0.00 | 0.00 |
May | 1926.41 | 1097.84 | 828.57 | 2341.58 | 440.53 | 0.00 | 0.00 | 0.00 |
June | 2076.82 | 1279.41 | 797.40 | 2780.86 | 289.65 | 0.00 | 0.00 | 0.00 |
July | 1921.72 | 1098.91 | 822.81 | 2683.56 | 205.86 | 0.00 | 0.00 | 0.00 |
August | 1901.67 | 1048.42 | 853.25 | 2571.86 | 234.35 | 0.00 | 0.00 | 0.00 |
September | 1582.82 | 885.60 | 697.22 | 2016.55 | 394.55 | 0.00 | 0.00 | 0.00 |
October | 1376.56 | 873.37 | 503.19 | 1533.41 | 676.66 | 0.00 | 0.00 | 0.00 |
November | 1075.85 | 632.48 | 443.37 | 1004.78 | 953.76 | 0.00 | 0.00 | 0.00 |
December | 871.75 | 530.54 | 341.21 | 734.98 | 1197.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1524.18 | 880.77 | 643.42 | 1782.56 | 657.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 871.75 | 515.48 | 341.21 | 734.98 | 205.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2076.82 | 1279.41 | 868.72 | 2780.86 | 1197.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.45 | 20.38 | 16.07 | 30.71 | 44.23 | 0.00 | 0.00 | 0.00 |
February | 44.29 | 23.88 | 20.41 | 41.12 | 40.11 | 0.00 | 0.00 | 0.00 |
March | 58.43 | 33.21 | 25.21 | 61.21 | 31.91 | 0.00 | 0.00 | 0.00 |
April | 79.82 | 45.47 | 34.35 | 91.67 | 22.67 | 0.00 | 0.00 | 0.00 |
May | 76.17 | 43.41 | 32.76 | 92.58 | 17.42 | 0.00 | 0.00 | 0.00 |
June | 82.12 | 50.59 | 31.53 | 109.95 | 11.45 | 0.00 | 0.00 | 0.00 |
July | 75.98 | 43.45 | 32.53 | 106.11 | 8.14 | 0.00 | 0.00 | 0.00 |
August | 75.19 | 41.45 | 33.74 | 101.69 | 9.27 | 0.00 | 0.00 | 0.00 |
September | 62.58 | 35.02 | 27.57 | 79.73 | 15.60 | 0.00 | 0.00 | 0.00 |
October | 54.43 | 34.53 | 19.90 | 60.63 | 26.75 | 0.00 | 0.00 | 0.00 |
November | 42.54 | 25.01 | 17.53 | 39.73 | 37.71 | 0.00 | 0.00 | 0.00 |
December | 34.47 | 20.98 | 13.49 | 29.06 | 47.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.26 | 34.82 | 25.44 | 70.48 | 25.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.47 | 20.38 | 13.49 | 29.06 | 8.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.12 | 50.59 | 34.35 | 109.95 | 47.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1279.28 | 995.46 | 283.83 | 1426.29 | 611.85 | 0.00 | 0.00 | 0.00 |
February | 1251.95 | 914.51 | 337.45 | 1429.78 | 560.68 | 0.00 | 0.00 | 0.00 |
March | 922.56 | 557.74 | 364.82 | 1080.49 | 447.50 | 0.00 | 0.00 | 0.00 |
April | 719.48 | 295.33 | 424.15 | 875.82 | 317.82 | 0.00 | 0.00 | 0.00 |
May | 479.84 | 105.55 | 374.28 | 592.22 | 228.79 | 0.00 | 0.00 | 0.00 |
June | 405.90 | 50.02 | 355.88 | 589.56 | 151.92 | 0.00 | 0.00 | 0.00 |
July | 449.15 | 71.72 | 377.43 | 702.29 | 104.08 | 0.00 | 0.00 | 0.00 |
August | 617.62 | 200.75 | 416.86 | 919.93 | 125.73 | 0.00 | 0.00 | 0.00 |
September | 854.03 | 476.23 | 377.80 | 1176.07 | 221.80 | 0.00 | 0.00 | 0.00 |
October | 1168.41 | 860.52 | 307.88 | 1447.61 | 372.59 | 0.00 | 0.00 | 0.00 |
November | 1301.38 | 998.81 | 302.58 | 1490.05 | 514.13 | 0.00 | 0.00 | 0.00 |
December | 1387.98 | 1144.94 | 243.04 | 1557.67 | 634.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 901.17 | 554.12 | 347.05 | 1105.48 | 356.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 405.90 | 50.02 | 243.04 | 589.56 | 104.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1387.98 | 1144.94 | 424.15 | 1557.67 | 634.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1279.28 | 995.46 | 283.83 | 1426.29 | 611.85 | 0.00 | 0.00 | 0.00 |
February | 1251.95 | 914.51 | 337.45 | 1429.78 | 560.68 | 0.00 | 0.00 | 0.00 |
March | 922.56 | 557.74 | 364.82 | 1080.49 | 447.50 | 0.00 | 0.00 | 0.00 |
April | 719.48 | 295.33 | 424.15 | 875.82 | 317.82 | 0.00 | 0.00 | 0.00 |
May | 479.84 | 105.55 | 374.28 | 592.22 | 228.79 | 0.00 | 0.00 | 0.00 |
June | 405.90 | 50.02 | 355.88 | 589.56 | 151.92 | 0.00 | 0.00 | 0.00 |
July | 449.15 | 71.72 | 377.43 | 702.29 | 104.08 | 0.00 | 0.00 | 0.00 |
August | 617.62 | 200.75 | 416.86 | 919.93 | 125.73 | 0.00 | 0.00 | 0.00 |
September | 854.03 | 476.23 | 377.80 | 1176.07 | 221.80 | 0.00 | 0.00 | 0.00 |
October | 1168.41 | 860.52 | 307.88 | 1447.61 | 372.59 | 0.00 | 0.00 | 0.00 |
November | 1301.38 | 998.81 | 302.58 | 1490.05 | 514.13 | 0.00 | 0.00 | 0.00 |
December | 1387.98 | 1144.94 | 243.04 | 1557.67 | 634.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 901.17 | 554.12 | 347.05 | 1105.48 | 356.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 405.90 | 50.02 | 243.04 | 589.56 | 104.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1387.98 | 1144.94 | 424.15 | 1557.67 | 634.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1279.20 | 995.39 | 283.81 | 1426.20 | 611.82 | 0.00 | 0.00 | 0.00 |
February | 1251.87 | 914.45 | 337.43 | 1429.69 | 560.64 | 0.00 | 0.00 | 0.00 |
March | 922.50 | 557.71 | 364.80 | 1080.42 | 447.47 | 0.00 | 0.00 | 0.00 |
April | 719.44 | 295.31 | 424.12 | 875.76 | 317.80 | 0.00 | 0.00 | 0.00 |
May | 479.81 | 105.55 | 374.26 | 592.18 | 228.77 | 0.00 | 0.00 | 0.00 |
June | 405.88 | 50.02 | 355.86 | 589.52 | 151.91 | 0.00 | 0.00 | 0.00 |
July | 449.12 | 71.72 | 377.40 | 702.24 | 104.07 | 0.00 | 0.00 | 0.00 |
August | 617.58 | 200.74 | 416.83 | 919.87 | 125.72 | 0.00 | 0.00 | 0.00 |
September | 853.97 | 476.20 | 377.77 | 1176.00 | 221.79 | 0.00 | 0.00 | 0.00 |
October | 1168.33 | 860.47 | 307.86 | 1447.51 | 372.56 | 0.00 | 0.00 | 0.00 |
November | 1301.30 | 998.74 | 302.56 | 1489.95 | 514.10 | 0.00 | 0.00 | 0.00 |
December | 1387.90 | 1144.87 | 243.03 | 1557.58 | 634.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 901.12 | 554.09 | 347.03 | 1105.41 | 356.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 405.88 | 50.02 | 243.03 | 589.52 | 104.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1387.90 | 1144.87 | 424.12 | 1557.58 | 634.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 951.00 | 542.32 | 408.67 | 890.28 | 1193.05 | 0.00 | 0.00 | 0.00 |
February | 1224.25 | 707.21 | 517.04 | 1232.20 | 1084.98 | 0.00 | 0.00 | 0.00 |
March | 1367.35 | 727.86 | 639.48 | 1461.93 | 858.37 | 0.00 | 0.00 | 0.00 |
April | 1745.15 | 928.77 | 816.37 | 1995.53 | 613.02 | 0.00 | 0.00 | 0.00 |
May | 1654.65 | 852.59 | 802.06 | 2006.25 | 461.15 | 0.00 | 0.00 | 0.00 |
June | 1773.79 | 989.75 | 784.04 | 2411.48 | 325.37 | 0.00 | 0.00 | 0.00 |
July | 1599.90 | 782.97 | 816.93 | 2273.73 | 219.22 | 0.00 | 0.00 | 0.00 |
August | 1634.81 | 756.17 | 878.65 | 2242.33 | 255.18 | 0.00 | 0.00 | 0.00 |
September | 1476.62 | 777.67 | 698.95 | 1908.61 | 425.88 | 0.00 | 0.00 | 0.00 |
October | 1350.91 | 839.63 | 511.27 | 1555.59 | 730.06 | 0.00 | 0.00 | 0.00 |
November | 1060.46 | 623.89 | 436.57 | 1036.72 | 991.27 | 0.00 | 0.00 | 0.00 |
December | 917.08 | 575.10 | 341.97 | 836.81 | 1243.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1396.45 | 758.30 | 638.15 | 1655.74 | 698.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 917.08 | 542.32 | 341.97 | 836.81 | 219.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1773.79 | 989.75 | 878.65 | 2411.48 | 1243.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.60 | 21.44 | 16.16 | 35.20 | 47.17 | 0.00 | 0.00 | 0.00 |
February | 48.41 | 27.96 | 20.44 | 48.72 | 42.90 | 0.00 | 0.00 | 0.00 |
March | 54.06 | 28.78 | 25.28 | 57.80 | 33.94 | 0.00 | 0.00 | 0.00 |
April | 69.00 | 36.72 | 32.28 | 78.90 | 24.24 | 0.00 | 0.00 | 0.00 |
May | 65.42 | 33.71 | 31.71 | 79.32 | 18.23 | 0.00 | 0.00 | 0.00 |
June | 70.13 | 39.13 | 31.00 | 95.35 | 12.86 | 0.00 | 0.00 | 0.00 |
July | 63.26 | 30.96 | 32.30 | 89.90 | 8.67 | 0.00 | 0.00 | 0.00 |
August | 64.64 | 29.90 | 34.74 | 88.66 | 10.09 | 0.00 | 0.00 | 0.00 |
September | 58.38 | 30.75 | 27.64 | 75.46 | 16.84 | 0.00 | 0.00 | 0.00 |
October | 53.41 | 33.20 | 20.22 | 61.51 | 28.87 | 0.00 | 0.00 | 0.00 |
November | 41.93 | 24.67 | 17.26 | 40.99 | 39.19 | 0.00 | 0.00 | 0.00 |
December | 36.26 | 22.74 | 13.52 | 33.09 | 49.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.21 | 29.98 | 25.23 | 65.47 | 27.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.26 | 21.44 | 13.52 | 33.09 | 8.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.13 | 39.13 | 34.74 | 95.35 | 49.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 519.13 | 0.00 | 519.13 | 113.54 | 1884.74 | 0.00 | 0.00 | 0.00 |
February | 648.82 | 0.00 | 648.82 | 235.21 | 1712.15 | 0.00 | 0.00 | 0.00 |
March | 818.41 | 0.00 | 818.41 | 497.07 | 1356.46 | 0.00 | 0.00 | 0.00 |
April | 1038.30 | 8.89 | 1029.41 | 807.93 | 912.27 | 0.00 | 0.00 | 0.00 |
May | 1128.64 | 72.77 | 1055.88 | 1125.57 | 666.08 | 0.00 | 0.00 | 0.00 |
June | 1282.44 | 209.87 | 1072.57 | 1748.22 | 443.42 | 0.00 | 0.00 | 0.00 |
July | 1177.08 | 97.97 | 1079.11 | 1740.32 | 304.20 | 0.00 | 0.00 | 0.00 |
August | 1091.94 | 24.45 | 1067.49 | 1472.52 | 344.36 | 0.00 | 0.00 | 0.00 |
September | 873.21 | 0.22 | 872.99 | 997.86 | 608.62 | 0.00 | 0.00 | 0.00 |
October | 651.59 | 0.00 | 651.59 | 451.39 | 1079.91 | 0.00 | 0.00 | 0.00 |
November | 553.36 | 0.00 | 553.36 | 155.91 | 1526.45 | 0.00 | 0.00 | 0.00 |
December | 441.86 | 0.00 | 441.86 | 35.90 | 1978.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 852.81 | 34.58 | 818.23 | 784.68 | 1064.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 441.86 | 0.00 | 441.86 | 35.90 | 304.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1282.44 | 209.87 | 1079.11 | 1748.22 | 1978.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 958.46 | 535.87 | 422.59 | 798.25 | 1151.36 | 0.00 | 0.00 | 0.00 |
February | 1164.50 | 627.79 | 536.71 | 1063.94 | 1054.84 | 0.00 | 0.00 | 0.00 |
March | 1536.16 | 873.28 | 662.88 | 1588.36 | 839.68 | 0.00 | 0.00 | 0.00 |
April | 2098.70 | 1195.62 | 903.08 | 2392.83 | 587.67 | 0.00 | 0.00 | 0.00 |
May | 2002.61 | 1141.27 | 861.34 | 2419.54 | 449.34 | 0.00 | 0.00 | 0.00 |
June | 2158.97 | 1330.03 | 828.94 | 2881.86 | 292.64 | 0.00 | 0.00 | 0.00 |
July | 1997.73 | 1142.38 | 855.35 | 2785.44 | 203.59 | 0.00 | 0.00 | 0.00 |
August | 1976.89 | 1089.90 | 886.99 | 2670.26 | 229.49 | 0.00 | 0.00 | 0.00 |
September | 1645.43 | 920.63 | 724.80 | 2095.12 | 388.02 | 0.00 | 0.00 | 0.00 |
October | 1431.02 | 907.92 | 523.09 | 1594.77 | 667.48 | 0.00 | 0.00 | 0.00 |
November | 1118.41 | 657.51 | 460.91 | 1045.71 | 947.79 | 0.00 | 0.00 | 0.00 |
December | 906.23 | 551.52 | 354.71 | 759.13 | 1215.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1584.47 | 915.61 | 668.86 | 1844.78 | 667.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 906.23 | 535.87 | 354.71 | 759.13 | 203.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2158.97 | 1330.03 | 903.08 | 2881.86 | 1215.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3837.92 | 2986.43 | 851.49 | 4253.70 | 1750.36 | 0.00 | 0.00 | 0.00 |
February | 3755.93 | 2743.58 | 1012.35 | 4252.42 | 1623.45 | 0.00 | 0.00 | 0.00 |
March | 2767.73 | 1673.26 | 1094.47 | 3198.32 | 1332.79 | 0.00 | 0.00 | 0.00 |
April | 2158.48 | 886.02 | 1272.46 | 2587.52 | 963.13 | 0.00 | 0.00 | 0.00 |
May | 1439.53 | 316.67 | 1122.86 | 1737.07 | 711.68 | 0.00 | 0.00 | 0.00 |
June | 1217.72 | 150.07 | 1067.65 | 1746.82 | 472.22 | 0.00 | 0.00 | 0.00 |
July | 1347.47 | 215.18 | 1132.29 | 2094.50 | 317.99 | 0.00 | 0.00 | 0.00 |
August | 1852.87 | 602.28 | 1250.59 | 2750.13 | 367.79 | 0.00 | 0.00 | 0.00 |
September | 2562.12 | 1428.71 | 1133.40 | 3519.10 | 627.98 | 0.00 | 0.00 | 0.00 |
October | 3505.28 | 2581.62 | 923.66 | 4333.00 | 1044.66 | 0.00 | 0.00 | 0.00 |
November | 3904.22 | 2996.48 | 907.74 | 4459.59 | 1439.60 | 0.00 | 0.00 | 0.00 |
December | 4164.03 | 3434.89 | 729.14 | 4649.23 | 1795.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2703.57 | 1662.41 | 1041.16 | 3293.02 | 1034.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1217.72 | 150.07 | 729.14 | 1737.07 | 317.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4164.03 | 3434.89 | 1272.46 | 4649.23 | 1795.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 988.61 | 563.77 | 424.84 | 914.14 | 1229.82 | 0.00 | 0.00 | 0.00 |
February | 1272.67 | 735.19 | 537.49 | 1263.03 | 1126.84 | 0.00 | 0.00 | 0.00 |
March | 1421.43 | 756.66 | 664.78 | 1495.92 | 901.18 | 0.00 | 0.00 | 0.00 |
April | 1814.17 | 965.51 | 848.66 | 2055.20 | 634.27 | 0.00 | 0.00 | 0.00 |
May | 1720.10 | 886.32 | 833.78 | 2068.48 | 478.13 | 0.00 | 0.00 | 0.00 |
June | 1843.94 | 1028.90 | 815.04 | 2498.29 | 331.56 | 0.00 | 0.00 | 0.00 |
July | 1663.18 | 813.94 | 849.24 | 2357.65 | 221.57 | 0.00 | 0.00 | 0.00 |
August | 1699.47 | 786.08 | 913.40 | 2327.32 | 252.89 | 0.00 | 0.00 | 0.00 |
September | 1535.02 | 808.43 | 726.59 | 1983.25 | 420.04 | 0.00 | 0.00 | 0.00 |
October | 1404.34 | 872.85 | 531.49 | 1618.36 | 723.53 | 0.00 | 0.00 | 0.00 |
November | 1102.40 | 648.57 | 453.83 | 1077.19 | 991.15 | 0.00 | 0.00 | 0.00 |
December | 953.35 | 597.85 | 355.50 | 862.72 | 1267.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1451.69 | 788.30 | 663.39 | 1711.68 | 712.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 953.35 | 563.77 | 355.50 | 862.72 | 221.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1843.94 | 1028.90 | 913.40 | 2498.29 | 1267.08 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139043E+10 | 0.00 | 0.139043E+10 | 0.348857E+09 | 0.474691E+10 |
February | 0.156963E+10 | 0.00 | 0.156963E+10 | 0.614915E+09 | 0.389842E+10 |
March | 0.219202E+10 | 0.00 | 0.219202E+10 | 0.138507E+10 | 0.341979E+10 |
April | 0.269128E+10 | 23041611.60 | 0.266824E+10 | 0.212965E+10 | 0.223455E+10 |
May | 0.302296E+10 | 0.194900E+09 | 0.282806E+10 | 0.303684E+10 | 0.171000E+10 |
June | 0.332409E+10 | 0.543982E+09 | 0.278011E+10 | 0.453006E+10 | 0.111458E+10 |
July | 0.315270E+10 | 0.262399E+09 | 0.289030E+10 | 0.464681E+10 | 0.795116E+09 |
August | 0.292465E+10 | 65476725.60 | 0.285918E+10 | 0.393629E+10 | 0.893110E+09 |
September | 0.226337E+10 | 580897.12 | 0.226279E+10 | 0.259495E+10 | 0.150299E+10 |
October | 0.174523E+10 | 0.00 | 0.174523E+10 | 0.124737E+10 | 0.270444E+10 |
November | 0.143430E+10 | 0.00 | 0.143430E+10 | 0.459731E+09 | 0.366251E+10 |
December | 0.118347E+10 | 0.00 | 0.118347E+10 | 0.121553E+09 | 0.495850E+10 |
Annual Sum or Average | 0.268941E+11 | 0.109038E+10 | 0.258038E+11 | 0.250521E+11 | 0.316409E+11 |
Minimum of Months | 0.118347E+10 | 0.00 | 0.118347E+10 | 0.121553E+09 | 0.795116E+09 |
Maximum of Months | 0.332409E+10 | 0.543982E+09 | 0.289030E+10 | 0.464681E+10 | 0.495850E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256713E+10 | 0.143527E+10 | 0.113186E+10 | 0.219253E+10 | 0.291440E+10 |
February | 0.281717E+10 | 0.151876E+10 | 0.129841E+10 | 0.261549E+10 | 0.241474E+10 |
March | 0.411444E+10 | 0.233899E+10 | 0.177546E+10 | 0.428513E+10 | 0.213661E+10 |
April | 0.543984E+10 | 0.309905E+10 | 0.234079E+10 | 0.621483E+10 | 0.145741E+10 |
May | 0.536379E+10 | 0.305678E+10 | 0.230701E+10 | 0.647910E+10 | 0.115890E+10 |
June | 0.559604E+10 | 0.344743E+10 | 0.214861E+10 | 0.745939E+10 | 0.736462E+09 |
July | 0.535072E+10 | 0.305976E+10 | 0.229096E+10 | 0.744364E+10 | 0.532755E+09 |
August | 0.529490E+10 | 0.291918E+10 | 0.237572E+10 | 0.713898E+10 | 0.596663E+09 |
September | 0.426495E+10 | 0.238627E+10 | 0.187867E+10 | 0.543089E+10 | 0.964969E+09 |
October | 0.383283E+10 | 0.243178E+10 | 0.140105E+10 | 0.429424E+10 | 0.169304E+10 |
November | 0.289892E+10 | 0.170425E+10 | 0.119467E+10 | 0.275794E+10 | 0.230221E+10 |
December | 0.242724E+10 | 0.147720E+10 | 0.950044E+09 | 0.207940E+10 | 0.305844E+10 |
Annual Sum or Average | 0.499680E+11 | 0.288747E+11 | 0.210932E+11 | 0.583916E+11 | 0.199666E+11 |
Minimum of Months | 0.242724E+10 | 0.143527E+10 | 0.950044E+09 | 0.207940E+10 | 0.532755E+09 |
Maximum of Months | 0.559604E+10 | 0.344743E+10 | 0.237572E+10 | 0.745939E+10 | 0.305844E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102795E+11 | 0.799886E+10 | 0.228063E+10 | 0.114603E+11 | 0.442442E+10 |
February | 0.908634E+10 | 0.663726E+10 | 0.244908E+10 | 0.103347E+11 | 0.370905E+10 |
March | 0.741310E+10 | 0.448167E+10 | 0.293143E+10 | 0.860663E+10 | 0.338091E+10 |
April | 0.559478E+10 | 0.229655E+10 | 0.329822E+10 | 0.672394E+10 | 0.237039E+10 |
May | 0.385563E+10 | 0.848168E+09 | 0.300746E+10 | 0.466106E+10 | 0.182171E+10 |
June | 0.315633E+10 | 0.388983E+09 | 0.276734E+10 | 0.452069E+10 | 0.117883E+10 |
July | 0.360905E+10 | 0.576333E+09 | 0.303272E+10 | 0.559159E+10 | 0.828583E+09 |
August | 0.496272E+10 | 0.161314E+10 | 0.334958E+10 | 0.734907E+10 | 0.951744E+09 |
September | 0.664101E+10 | 0.370322E+10 | 0.293779E+10 | 0.911916E+10 | 0.155789E+10 |
October | 0.938855E+10 | 0.691462E+10 | 0.247393E+10 | 0.116382E+11 | 0.264782E+10 |
November | 0.101197E+11 | 0.776687E+10 | 0.235287E+10 | 0.116208E+11 | 0.349667E+10 |
December | 0.111529E+11 | 0.920001E+10 | 0.195293E+10 | 0.125116E+11 | 0.451414E+10 |
Annual Sum or Average | 0.852597E+11 | 0.524257E+11 | 0.328340E+11 | 0.104138E+12 | 0.308822E+11 |
Minimum of Months | 0.315633E+10 | 0.388983E+09 | 0.195293E+10 | 0.452069E+10 | 0.828583E+09 |
Maximum of Months | 0.111529E+11 | 0.920001E+10 | 0.334958E+10 | 0.125116E+11 | 0.451414E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.264789E+10 | 0.151001E+10 | 0.113788E+10 | 0.247554E+10 | 0.310527E+10 |
February | 0.307885E+10 | 0.177856E+10 | 0.130029E+10 | 0.307768E+10 | 0.257481E+10 |
March | 0.380716E+10 | 0.202663E+10 | 0.178053E+10 | 0.403071E+10 | 0.228466E+10 |
April | 0.470233E+10 | 0.250260E+10 | 0.219973E+10 | 0.534134E+10 | 0.156212E+10 |
May | 0.460711E+10 | 0.237391E+10 | 0.223321E+10 | 0.554775E+10 | 0.122525E+10 |
June | 0.477950E+10 | 0.266691E+10 | 0.211259E+10 | 0.646972E+10 | 0.829276E+09 |
July | 0.445466E+10 | 0.218005E+10 | 0.227461E+10 | 0.630223E+10 | 0.577603E+09 |
August | 0.455187E+10 | 0.210543E+10 | 0.244644E+10 | 0.622514E+10 | 0.654951E+09 |
September | 0.397878E+10 | 0.209546E+10 | 0.188332E+10 | 0.514518E+10 | 0.103973E+10 |
October | 0.376138E+10 | 0.233783E+10 | 0.142355E+10 | 0.435320E+10 | 0.182522E+10 |
November | 0.285742E+10 | 0.168109E+10 | 0.117634E+10 | 0.282274E+10 | 0.239579E+10 |
December | 0.255346E+10 | 0.160129E+10 | 0.952167E+09 | 0.233152E+10 | 0.318475E+10 |
Annual Sum or Average | 0.457804E+11 | 0.248598E+11 | 0.209206E+11 | 0.541228E+11 | 0.212594E+11 |
Minimum of Months | 0.255346E+10 | 0.151001E+10 | 0.952167E+09 | 0.233152E+10 | 0.577603E+09 |
Maximum of Months | 0.477950E+10 | 0.266691E+10 | 0.244644E+10 | 0.646972E+10 | 0.318475E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.463455E+09 | 0.00 | 0.463455E+09 | 0.111087E+09 | 0.165761E+10 |
February | 0.523185E+09 | 0.00 | 0.523185E+09 | 0.209248E+09 | 0.133759E+10 |
March | 0.730639E+09 | 0.00 | 0.730639E+09 | 0.482947E+09 | 0.114966E+10 |
April | 0.897051E+09 | 7680173.82 | 0.889371E+09 | 0.734623E+09 | 0.747867E+09 |
May | 0.100761E+10 | 64963637.69 | 0.942642E+09 | 0.103738E+10 | 0.569001E+09 |
June | 0.110798E+10 | 0.181319E+09 | 0.926660E+09 | 0.152888E+10 | 0.371144E+09 |
July | 0.105085E+10 | 87462236.12 | 0.963387E+09 | 0.156645E+10 | 0.262675E+09 |
August | 0.974838E+09 | 21824542.59 | 0.953014E+09 | 0.132264E+10 | 0.303285E+09 |
September | 0.754421E+09 | 193623.21 | 0.754228E+09 | 0.866340E+09 | 0.528947E+09 |
October | 0.581714E+09 | 0.00 | 0.581714E+09 | 0.405353E+09 | 0.974044E+09 |
November | 0.478078E+09 | 0.00 | 0.478078E+09 | 0.137875E+09 | 0.132746E+10 |
December | 0.394470E+09 | 0.00 | 0.394470E+09 | 33628548.78 | 0.176306E+10 |
Annual Sum or Average | 0.896429E+10 | 0.363443E+09 | 0.860084E+10 | 0.843646E+10 | 0.109923E+11 |
Minimum of Months | 0.394470E+09 | 0.00 | 0.394470E+09 | 33628548.78 | 0.262675E+09 |
Maximum of Months | 0.110798E+10 | 0.181319E+09 | 0.963387E+09 | 0.156645E+10 | 0.176306E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.463474E+09 | 0.00 | 0.463474E+09 | 0.111088E+09 | 0.165771E+10 |
February | 0.523207E+09 | 0.00 | 0.523207E+09 | 0.209253E+09 | 0.133768E+10 |
March | 0.730670E+09 | 0.00 | 0.730670E+09 | 0.482963E+09 | 0.114972E+10 |
April | 0.897090E+09 | 7680380.26 | 0.889410E+09 | 0.734651E+09 | 0.747911E+09 |
May | 0.100765E+10 | 64965383.93 | 0.942684E+09 | 0.103742E+10 | 0.569033E+09 |
June | 0.110803E+10 | 0.181324E+09 | 0.926702E+09 | 0.152895E+10 | 0.371163E+09 |
July | 0.105089E+10 | 87464587.13 | 0.963430E+09 | 0.156652E+10 | 0.262688E+09 |
August | 0.974880E+09 | 21825129.24 | 0.953055E+09 | 0.132271E+10 | 0.303301E+09 |
September | 0.754454E+09 | 193628.42 | 0.754261E+09 | 0.866379E+09 | 0.528976E+09 |
October | 0.581740E+09 | 0.00 | 0.581740E+09 | 0.405369E+09 | 0.974101E+09 |
November | 0.478098E+09 | 0.00 | 0.478098E+09 | 0.137876E+09 | 0.132754E+10 |
December | 0.394487E+09 | 0.00 | 0.394487E+09 | 33627634.01 | 0.176317E+10 |
Annual Sum or Average | 0.896467E+10 | 0.363453E+09 | 0.860122E+10 | 0.843681E+10 | 0.109930E+11 |
Minimum of Months | 0.394487E+09 | 0.00 | 0.394487E+09 | 33627634.01 | 0.262688E+09 |
Maximum of Months | 0.110803E+10 | 0.181324E+09 | 0.963430E+09 | 0.156652E+10 | 0.176317E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.463474E+09 | 0.00 | 0.463474E+09 | 0.111088E+09 | 0.165771E+10 |
February | 0.523207E+09 | 0.00 | 0.523207E+09 | 0.209253E+09 | 0.133768E+10 |
March | 0.730670E+09 | 0.00 | 0.730670E+09 | 0.482963E+09 | 0.114972E+10 |
April | 0.897090E+09 | 7680380.26 | 0.889410E+09 | 0.734651E+09 | 0.747911E+09 |
May | 0.100765E+10 | 64965383.93 | 0.942684E+09 | 0.103742E+10 | 0.569033E+09 |
June | 0.110803E+10 | 0.181324E+09 | 0.926702E+09 | 0.152895E+10 | 0.371163E+09 |
July | 0.105089E+10 | 87464587.13 | 0.963430E+09 | 0.156652E+10 | 0.262688E+09 |
August | 0.974880E+09 | 21825129.24 | 0.953055E+09 | 0.132271E+10 | 0.303301E+09 |
September | 0.754454E+09 | 193628.42 | 0.754261E+09 | 0.866379E+09 | 0.528976E+09 |
October | 0.581740E+09 | 0.00 | 0.581740E+09 | 0.405369E+09 | 0.974101E+09 |
November | 0.478098E+09 | 0.00 | 0.478098E+09 | 0.137876E+09 | 0.132754E+10 |
December | 0.394487E+09 | 0.00 | 0.394487E+09 | 33627634.01 | 0.176317E+10 |
Annual Sum or Average | 0.896467E+10 | 0.363453E+09 | 0.860122E+10 | 0.843681E+10 | 0.109930E+11 |
Minimum of Months | 0.394487E+09 | 0.00 | 0.394487E+09 | 33627634.01 | 0.262688E+09 |
Maximum of Months | 0.110803E+10 | 0.181324E+09 | 0.963430E+09 | 0.156652E+10 | 0.176317E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246945E+10 | 0.138065E+10 | 0.108880E+10 | 0.208006E+10 | 0.299616E+10 |
February | 0.270997E+10 | 0.146096E+10 | 0.124901E+10 | 0.251619E+10 | 0.245426E+10 |
March | 0.395789E+10 | 0.224998E+10 | 0.170791E+10 | 0.414618E+10 | 0.216190E+10 |
April | 0.523285E+10 | 0.298112E+10 | 0.225173E+10 | 0.600957E+10 | 0.148600E+10 |
May | 0.515969E+10 | 0.294045E+10 | 0.221924E+10 | 0.627168E+10 | 0.117991E+10 |
June | 0.538311E+10 | 0.331624E+10 | 0.206687E+10 | 0.720799E+10 | 0.750781E+09 |
July | 0.514712E+10 | 0.294332E+10 | 0.220380E+10 | 0.718766E+10 | 0.551382E+09 |
August | 0.509342E+10 | 0.280809E+10 | 0.228533E+10 | 0.688847E+10 | 0.627671E+09 |
September | 0.410266E+10 | 0.229547E+10 | 0.180720E+10 | 0.522691E+10 | 0.102267E+10 |
October | 0.368699E+10 | 0.233924E+10 | 0.134775E+10 | 0.410708E+10 | 0.181237E+10 |
November | 0.278861E+10 | 0.163940E+10 | 0.114921E+10 | 0.260438E+10 | 0.247215E+10 |
December | 0.233489E+10 | 0.142099E+10 | 0.913900E+09 | 0.196858E+10 | 0.320607E+10 |
Annual Sum or Average | 0.480667E+11 | 0.277759E+11 | 0.202907E+11 | 0.562147E+11 | 0.207213E+11 |
Minimum of Months | 0.233489E+10 | 0.138065E+10 | 0.913900E+09 | 0.196858E+10 | 0.551382E+09 |
Maximum of Months | 0.538311E+10 | 0.331624E+10 | 0.228533E+10 | 0.720799E+10 | 0.320607E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 97639649.37 | 54589599.15 | 43050050.22 | 82243695.31 | 0.118465E+09 |
February | 0.107150E+09 | 57765094.06 | 49384837.30 | 99488080.38 | 97039215.95 |
March | 0.156491E+09 | 88962096.34 | 67529164.65 | 0.163936E+09 | 85479673.72 |
April | 0.206902E+09 | 0.117871E+09 | 89031490.37 | 0.237613E+09 | 58755167.72 |
May | 0.204010E+09 | 0.116263E+09 | 87746697.98 | 0.247976E+09 | 46652738.86 |
June | 0.212843E+09 | 0.131121E+09 | 81722126.16 | 0.284998E+09 | 29685210.17 |
July | 0.203513E+09 | 0.116376E+09 | 87136306.52 | 0.284193E+09 | 21801146.80 |
August | 0.201389E+09 | 0.111029E+09 | 90360024.41 | 0.272364E+09 | 24817559.41 |
September | 0.162216E+09 | 90760712.84 | 71454917.54 | 0.206667E+09 | 40435533.93 |
October | 0.145780E+09 | 92491572.82 | 53288700.14 | 0.162390E+09 | 71659609.59 |
November | 0.110259E+09 | 64820389.66 | 45438871.25 | 0.102975E+09 | 97746572.00 |
December | 92319326.68 | 56184559.57 | 36134767.11 | 77835694.65 | 0.126765E+09 |
Annual Sum or Average | 0.190051E+10 | 0.109823E+10 | 0.802278E+09 | 0.222268E+10 | 0.819303E+09 |
Minimum of Months | 92319326.68 | 54589599.15 | 36134767.11 | 77835694.65 | 21801146.80 |
Maximum of Months | 0.212843E+09 | 0.131121E+09 | 90360024.41 | 0.284998E+09 | 0.126765E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.342643E+10 | 0.266623E+10 | 0.760201E+09 | 0.382017E+10 | 0.163879E+10 |
February | 0.302873E+10 | 0.221238E+10 | 0.816351E+09 | 0.345892E+10 | 0.135640E+10 |
March | 0.247099E+10 | 0.149386E+10 | 0.977133E+09 | 0.289399E+10 | 0.119858E+10 |
April | 0.186490E+10 | 0.765502E+09 | 0.109940E+10 | 0.227012E+10 | 0.823790E+09 |
May | 0.128520E+10 | 0.282717E+09 | 0.100248E+10 | 0.158620E+10 | 0.612788E+09 |
June | 0.105210E+10 | 0.129658E+09 | 0.922446E+09 | 0.152813E+10 | 0.393765E+09 |
July | 0.120301E+10 | 0.192107E+09 | 0.101090E+10 | 0.188101E+10 | 0.278764E+09 |
August | 0.165422E+10 | 0.537701E+09 | 0.111652E+10 | 0.246393E+10 | 0.336746E+09 |
September | 0.221364E+10 | 0.123438E+10 | 0.979254E+09 | 0.304838E+10 | 0.574909E+09 |
October | 0.312946E+10 | 0.230483E+10 | 0.824638E+09 | 0.387727E+10 | 0.997933E+09 |
November | 0.337319E+10 | 0.258890E+10 | 0.784281E+09 | 0.386220E+10 | 0.133262E+10 |
December | 0.371758E+10 | 0.306661E+10 | 0.650970E+09 | 0.417208E+10 | 0.169949E+10 |
Annual Sum or Average | 0.284195E+11 | 0.174749E+11 | 0.109446E+11 | 0.348624E+11 | 0.112446E+11 |
Minimum of Months | 0.105210E+10 | 0.129658E+09 | 0.650970E+09 | 0.152813E+10 | 0.278764E+09 |
Maximum of Months | 0.371758E+10 | 0.306661E+10 | 0.111652E+10 | 0.417208E+10 | 0.169949E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.342643E+10 | 0.266623E+10 | 0.760201E+09 | 0.382017E+10 | 0.163879E+10 |
February | 0.302873E+10 | 0.221238E+10 | 0.816351E+09 | 0.345892E+10 | 0.135640E+10 |
March | 0.247099E+10 | 0.149386E+10 | 0.977133E+09 | 0.289399E+10 | 0.119858E+10 |
April | 0.186490E+10 | 0.765502E+09 | 0.109940E+10 | 0.227012E+10 | 0.823790E+09 |
May | 0.128520E+10 | 0.282717E+09 | 0.100248E+10 | 0.158620E+10 | 0.612788E+09 |
June | 0.105210E+10 | 0.129658E+09 | 0.922446E+09 | 0.152813E+10 | 0.393765E+09 |
July | 0.120301E+10 | 0.192107E+09 | 0.101090E+10 | 0.188101E+10 | 0.278764E+09 |
August | 0.165422E+10 | 0.537701E+09 | 0.111652E+10 | 0.246393E+10 | 0.336746E+09 |
September | 0.221364E+10 | 0.123438E+10 | 0.979254E+09 | 0.304838E+10 | 0.574909E+09 |
October | 0.312946E+10 | 0.230483E+10 | 0.824638E+09 | 0.387727E+10 | 0.997933E+09 |
November | 0.337319E+10 | 0.258890E+10 | 0.784281E+09 | 0.386220E+10 | 0.133262E+10 |
December | 0.371758E+10 | 0.306661E+10 | 0.650970E+09 | 0.417208E+10 | 0.169949E+10 |
Annual Sum or Average | 0.284195E+11 | 0.174749E+11 | 0.109446E+11 | 0.348624E+11 | 0.112446E+11 |
Minimum of Months | 0.105210E+10 | 0.129658E+09 | 0.650970E+09 | 0.152813E+10 | 0.278764E+09 |
Maximum of Months | 0.371758E+10 | 0.306661E+10 | 0.111652E+10 | 0.417208E+10 | 0.169949E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.342622E+10 | 0.266606E+10 | 0.760153E+09 | 0.381993E+10 | 0.163869E+10 |
February | 0.302853E+10 | 0.221224E+10 | 0.816299E+09 | 0.345870E+10 | 0.135631E+10 |
March | 0.247084E+10 | 0.149377E+10 | 0.977071E+09 | 0.289381E+10 | 0.119850E+10 |
April | 0.186478E+10 | 0.765454E+09 | 0.109933E+10 | 0.226998E+10 | 0.823738E+09 |
May | 0.128512E+10 | 0.282699E+09 | 0.100242E+10 | 0.158610E+10 | 0.612750E+09 |
June | 0.105204E+10 | 0.129650E+09 | 0.922387E+09 | 0.152803E+10 | 0.393740E+09 |
July | 0.120293E+10 | 0.192095E+09 | 0.101084E+10 | 0.188089E+10 | 0.278746E+09 |
August | 0.165412E+10 | 0.537667E+09 | 0.111645E+10 | 0.246377E+10 | 0.336725E+09 |
September | 0.221350E+10 | 0.123430E+10 | 0.979193E+09 | 0.304819E+10 | 0.574873E+09 |
October | 0.312927E+10 | 0.230468E+10 | 0.824586E+09 | 0.387702E+10 | 0.997870E+09 |
November | 0.337297E+10 | 0.258874E+10 | 0.784232E+09 | 0.386196E+10 | 0.133254E+10 |
December | 0.371734E+10 | 0.306641E+10 | 0.650929E+09 | 0.417181E+10 | 0.169938E+10 |
Annual Sum or Average | 0.284177E+11 | 0.174738E+11 | 0.109439E+11 | 0.348602E+11 | 0.112439E+11 |
Minimum of Months | 0.105204E+10 | 0.129650E+09 | 0.650929E+09 | 0.152803E+10 | 0.278746E+09 |
Maximum of Months | 0.371734E+10 | 0.306641E+10 | 0.111645E+10 | 0.417181E+10 | 0.169938E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.254715E+10 | 0.145255E+10 | 0.109459E+10 | 0.238451E+10 | 0.319546E+10 |
February | 0.296171E+10 | 0.171088E+10 | 0.125082E+10 | 0.298094E+10 | 0.262478E+10 |
March | 0.366231E+10 | 0.194951E+10 | 0.171280E+10 | 0.391562E+10 | 0.229906E+10 |
April | 0.452342E+10 | 0.240738E+10 | 0.211604E+10 | 0.517241E+10 | 0.158895E+10 |
May | 0.443183E+10 | 0.228358E+10 | 0.214825E+10 | 0.537353E+10 | 0.123515E+10 |
June | 0.459765E+10 | 0.256543E+10 | 0.203222E+10 | 0.625054E+10 | 0.843369E+09 |
July | 0.428517E+10 | 0.209710E+10 | 0.218807E+10 | 0.608997E+10 | 0.587164E+09 |
August | 0.437868E+10 | 0.202531E+10 | 0.235337E+10 | 0.600586E+10 | 0.683485E+09 |
September | 0.382740E+10 | 0.201573E+10 | 0.181167E+10 | 0.494711E+10 | 0.110387E+10 |
October | 0.361827E+10 | 0.224888E+10 | 0.136939E+10 | 0.416648E+10 | 0.195538E+10 |
November | 0.274870E+10 | 0.161712E+10 | 0.113158E+10 | 0.268719E+10 | 0.256937E+10 |
December | 0.245630E+10 | 0.154036E+10 | 0.915943E+09 | 0.224132E+10 | 0.333135E+10 |
Annual Sum or Average | 0.440386E+11 | 0.239138E+11 | 0.201248E+11 | 0.522155E+11 | 0.220174E+11 |
Minimum of Months | 0.245630E+10 | 0.145255E+10 | 0.915943E+09 | 0.224132E+10 | 0.587164E+09 |
Maximum of Months | 0.459765E+10 | 0.256543E+10 | 0.235337E+10 | 0.625054E+10 | 0.333135E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100712E+09 | 57432454.07 | 43279152.30 | 94281145.98 | 0.126346E+09 |
February | 0.117103E+09 | 67646613.61 | 49456288.35 | 0.117863E+09 | 0.103781E+09 |
March | 0.144804E+09 | 77081696.93 | 67722242.38 | 0.154820E+09 | 90902861.21 |
April | 0.178852E+09 | 95185272.54 | 83666272.12 | 0.204512E+09 | 62825446.57 |
May | 0.175230E+09 | 90290331.32 | 84939606.87 | 0.212464E+09 | 48836785.87 |
June | 0.181787E+09 | 0.101435E+09 | 80351982.72 | 0.247140E+09 | 33346029.28 |
July | 0.169431E+09 | 82917082.45 | 86514287.52 | 0.240791E+09 | 23215894.24 |
August | 0.173129E+09 | 80078784.46 | 93049984.42 | 0.237466E+09 | 27024371.36 |
September | 0.151331E+09 | 79699840.40 | 71631615.22 | 0.195604E+09 | 43645987.33 |
October | 0.143063E+09 | 88918326.60 | 54144315.86 | 0.164738E+09 | 77313938.39 |
November | 0.108681E+09 | 63939202.34 | 44741703.14 | 0.106249E+09 | 0.101591E+09 |
December | 97119744.60 | 60904249.25 | 36215495.34 | 88619269.32 | 0.131719E+09 |
Annual Sum or Average | 0.174124E+10 | 0.945528E+09 | 0.795713E+09 | 0.206455E+10 | 0.870548E+09 |
Minimum of Months | 97119744.60 | 57432454.07 | 36215495.34 | 88619269.32 | 23215894.24 |
Maximum of Months | 0.181787E+09 | 0.101435E+09 | 93049984.42 | 0.247140E+09 | 0.131719E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139043E+10 | 0.00 | 0.139043E+10 | 0.304115E+09 | 0.504810E+10 |
February | 0.156963E+10 | 0.00 | 0.156963E+10 | 0.569024E+09 | 0.414203E+10 |
March | 0.219202E+10 | 0.00 | 0.219202E+10 | 0.133136E+10 | 0.363315E+10 |
April | 0.269128E+10 | 23041611.60 | 0.266824E+10 | 0.209417E+10 | 0.236459E+10 |
May | 0.302296E+10 | 0.194900E+09 | 0.282806E+10 | 0.301473E+10 | 0.178404E+10 |
June | 0.332409E+10 | 0.543982E+09 | 0.278011E+10 | 0.453138E+10 | 0.114935E+10 |
July | 0.315270E+10 | 0.262399E+09 | 0.289030E+10 | 0.466127E+10 | 0.814758E+09 |
August | 0.292465E+10 | 65476725.60 | 0.285918E+10 | 0.394400E+10 | 0.922346E+09 |
September | 0.226337E+10 | 580897.12 | 0.226279E+10 | 0.258646E+10 | 0.157755E+10 |
October | 0.174523E+10 | 0.00 | 0.174523E+10 | 0.120899E+10 | 0.289244E+10 |
November | 0.143430E+10 | 0.00 | 0.143430E+10 | 0.404114E+09 | 0.395657E+10 |
December | 0.118347E+10 | 0.00 | 0.118347E+10 | 96156304.41 | 0.529980E+10 |
Annual Sum or Average | 0.268941E+11 | 0.109038E+10 | 0.258038E+11 | 0.247458E+11 | 0.335847E+11 |
Minimum of Months | 0.118347E+10 | 0.00 | 0.118347E+10 | 96156304.41 | 0.814758E+09 |
Maximum of Months | 0.332409E+10 | 0.543982E+09 | 0.289030E+10 | 0.466127E+10 | 0.529980E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256713E+10 | 0.143527E+10 | 0.113186E+10 | 0.213803E+10 | 0.308380E+10 |
February | 0.281717E+10 | 0.151876E+10 | 0.129841E+10 | 0.257389E+10 | 0.255186E+10 |
March | 0.411444E+10 | 0.233899E+10 | 0.177546E+10 | 0.425426E+10 | 0.224899E+10 |
April | 0.543984E+10 | 0.309905E+10 | 0.234079E+10 | 0.620222E+10 | 0.152324E+10 |
May | 0.536379E+10 | 0.305678E+10 | 0.230701E+10 | 0.648048E+10 | 0.120352E+10 |
June | 0.559604E+10 | 0.344743E+10 | 0.214861E+10 | 0.746979E+10 | 0.758526E+09 |
July | 0.535072E+10 | 0.305976E+10 | 0.229096E+10 | 0.746053E+10 | 0.545298E+09 |
August | 0.529490E+10 | 0.291918E+10 | 0.237572E+10 | 0.715201E+10 | 0.614655E+09 |
September | 0.426495E+10 | 0.238627E+10 | 0.187867E+10 | 0.543055E+10 | 0.100576E+10 |
October | 0.383283E+10 | 0.243178E+10 | 0.140105E+10 | 0.427142E+10 | 0.178779E+10 |
November | 0.289892E+10 | 0.170425E+10 | 0.119467E+10 | 0.271048E+10 | 0.245666E+10 |
December | 0.242724E+10 | 0.147720E+10 | 0.950044E+09 | 0.203327E+10 | 0.325639E+10 |
Annual Sum or Average | 0.499680E+11 | 0.288747E+11 | 0.210932E+11 | 0.581769E+11 | 0.210365E+11 |
Minimum of Months | 0.242724E+10 | 0.143527E+10 | 0.950044E+09 | 0.203327E+10 | 0.545298E+09 |
Maximum of Months | 0.559604E+10 | 0.344743E+10 | 0.237572E+10 | 0.746979E+10 | 0.325639E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102795E+11 | 0.799886E+10 | 0.228063E+10 | 0.113931E+11 | 0.468817E+10 |
February | 0.908634E+10 | 0.663726E+10 | 0.244908E+10 | 0.102875E+11 | 0.392744E+10 |
March | 0.741310E+10 | 0.448167E+10 | 0.293143E+10 | 0.856638E+10 | 0.356974E+10 |
April | 0.559478E+10 | 0.229655E+10 | 0.329822E+10 | 0.670686E+10 | 0.249645E+10 |
May | 0.385563E+10 | 0.848168E+09 | 0.300746E+10 | 0.465256E+10 | 0.190616E+10 |
June | 0.315633E+10 | 0.388983E+09 | 0.276734E+10 | 0.452775E+10 | 0.122401E+10 |
July | 0.360905E+10 | 0.576333E+09 | 0.303272E+10 | 0.560991E+10 | 0.851700E+09 |
August | 0.496272E+10 | 0.161314E+10 | 0.334958E+10 | 0.736594E+10 | 0.985077E+09 |
September | 0.664101E+10 | 0.370322E+10 | 0.293779E+10 | 0.912150E+10 | 0.162774E+10 |
October | 0.938855E+10 | 0.691462E+10 | 0.247393E+10 | 0.116055E+11 | 0.279802E+10 |
November | 0.101197E+11 | 0.776687E+10 | 0.235287E+10 | 0.115593E+11 | 0.373144E+10 |
December | 0.111529E+11 | 0.920001E+10 | 0.195293E+10 | 0.124525E+11 | 0.480782E+10 |
Annual Sum or Average | 0.852597E+11 | 0.524257E+11 | 0.328340E+11 | 0.103849E+12 | 0.326138E+11 |
Minimum of Months | 0.315633E+10 | 0.388983E+09 | 0.195293E+10 | 0.452775E+10 | 0.851700E+09 |
Maximum of Months | 0.111529E+11 | 0.920001E+10 | 0.334958E+10 | 0.124525E+11 | 0.480782E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.264789E+10 | 0.151001E+10 | 0.113788E+10 | 0.244844E+10 | 0.329394E+10 |
February | 0.307885E+10 | 0.177856E+10 | 0.130029E+10 | 0.305552E+10 | 0.272606E+10 |
March | 0.380716E+10 | 0.202663E+10 | 0.178053E+10 | 0.400666E+10 | 0.241372E+10 |
April | 0.470233E+10 | 0.250260E+10 | 0.219973E+10 | 0.532707E+10 | 0.164404E+10 |
May | 0.460711E+10 | 0.237391E+10 | 0.223321E+10 | 0.554022E+10 | 0.128062E+10 |
June | 0.477950E+10 | 0.266691E+10 | 0.211259E+10 | 0.647557E+10 | 0.859413E+09 |
July | 0.445466E+10 | 0.218005E+10 | 0.227461E+10 | 0.631474E+10 | 0.593460E+09 |
August | 0.455187E+10 | 0.210543E+10 | 0.244644E+10 | 0.623349E+10 | 0.677333E+09 |
September | 0.397878E+10 | 0.209546E+10 | 0.188332E+10 | 0.514058E+10 | 0.108874E+10 |
October | 0.376138E+10 | 0.233783E+10 | 0.142355E+10 | 0.433460E+10 | 0.193792E+10 |
November | 0.285742E+10 | 0.168109E+10 | 0.117634E+10 | 0.279209E+10 | 0.256905E+10 |
December | 0.255346E+10 | 0.160129E+10 | 0.952167E+09 | 0.231072E+10 | 0.339373E+10 |
Annual Sum or Average | 0.457804E+11 | 0.248598E+11 | 0.209206E+11 | 0.539797E+11 | 0.224780E+11 |
Minimum of Months | 0.255346E+10 | 0.151001E+10 | 0.952167E+09 | 0.231072E+10 | 0.593460E+09 |
Maximum of Months | 0.477950E+10 | 0.266691E+10 | 0.244644E+10 | 0.647557E+10 | 0.339373E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 130.25 | 1772.29 | 519.13 | 0.00 | 519.13 | 0.00 | 0.00 |
February | 254.18 | 1611.45 | 648.82 | 0.00 | 648.82 | 0.00 | 0.00 |
March | 517.13 | 1276.80 | 818.41 | 0.00 | 818.41 | 0.00 | 0.00 |
April | 821.62 | 862.10 | 1038.30 | 8.89 | 1029.41 | 0.00 | 0.00 |
May | 1133.83 | 638.44 | 1128.64 | 72.77 | 1055.88 | 0.00 | 0.00 |
June | 1747.71 | 430.01 | 1282.44 | 209.87 | 1072.57 | 0.00 | 0.00 |
July | 1734.92 | 296.86 | 1177.08 | 97.97 | 1079.11 | 0.00 | 0.00 |
August | 1469.64 | 333.45 | 1091.94 | 24.45 | 1067.49 | 0.00 | 0.00 |
September | 1001.14 | 579.86 | 873.21 | 0.22 | 872.99 | 0.00 | 0.00 |
October | 465.71 | 1009.72 | 651.59 | 0.00 | 651.59 | 0.00 | 0.00 |
November | 177.37 | 1413.01 | 553.36 | 0.00 | 553.36 | 0.00 | 0.00 |
December | 45.38 | 1851.29 | 441.86 | 0.00 | 441.86 | 0.00 | 0.00 |
Annual Sum or Average | 794.40 | 1003.33 | 852.81 | 34.58 | 818.23 | 0.00 | 0.00 |
Minimum of Months | 45.38 | 296.86 | 441.86 | 0.00 | 441.86 | 0.00 | 0.00 |
Maximum of Months | 1747.71 | 1851.29 | 1282.44 | 209.87 | 1079.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 818.60 | 1088.11 | 958.46 | 535.87 | 422.59 | 0.00 | 0.00 |
February | 1081.14 | 998.16 | 1164.50 | 627.79 | 536.71 | 0.00 | 0.00 |
March | 1599.88 | 797.72 | 1536.16 | 873.28 | 662.88 | 0.00 | 0.00 |
April | 2397.70 | 562.27 | 2098.70 | 1195.62 | 903.08 | 0.00 | 0.00 |
May | 2419.02 | 432.68 | 2002.61 | 1141.27 | 861.34 | 0.00 | 0.00 |
June | 2877.85 | 284.13 | 2158.97 | 1330.03 | 828.94 | 0.00 | 0.00 |
July | 2779.14 | 198.91 | 1997.73 | 1142.38 | 855.35 | 0.00 | 0.00 |
August | 2665.39 | 222.77 | 1976.89 | 1089.90 | 886.99 | 0.00 | 0.00 |
September | 2095.25 | 372.29 | 1645.43 | 920.63 | 724.80 | 0.00 | 0.00 |
October | 1603.29 | 632.11 | 1431.02 | 907.92 | 523.09 | 0.00 | 0.00 |
November | 1064.02 | 888.20 | 1118.41 | 657.51 | 460.91 | 0.00 | 0.00 |
December | 776.36 | 1141.89 | 906.23 | 551.52 | 354.71 | 0.00 | 0.00 |
Annual Sum or Average | 1851.58 | 633.14 | 1584.47 | 915.61 | 668.86 | 0.00 | 0.00 |
Minimum of Months | 776.36 | 198.91 | 906.23 | 535.87 | 354.71 | 0.00 | 0.00 |
Maximum of Months | 2877.85 | 1141.89 | 2158.97 | 1330.03 | 903.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4278.78 | 1651.89 | 3837.92 | 2986.43 | 851.49 | 0.00 | 0.00 |
February | 4271.95 | 1533.17 | 3755.93 | 2743.58 | 1012.35 | 0.00 | 0.00 |
March | 3213.35 | 1262.29 | 2767.73 | 1673.26 | 1094.47 | 0.00 | 0.00 |
April | 2594.11 | 914.50 | 2158.48 | 886.02 | 1272.46 | 0.00 | 0.00 |
May | 1740.24 | 680.15 | 1439.53 | 316.67 | 1122.86 | 0.00 | 0.00 |
June | 1744.09 | 454.80 | 1217.72 | 150.07 | 1067.65 | 0.00 | 0.00 |
July | 2087.66 | 309.36 | 1347.47 | 215.18 | 1132.29 | 0.00 | 0.00 |
August | 2743.83 | 355.34 | 1852.87 | 602.28 | 1250.59 | 0.00 | 0.00 |
September | 3518.19 | 601.04 | 2562.12 | 1428.71 | 1133.40 | 0.00 | 0.00 |
October | 4345.21 | 988.58 | 3505.28 | 2581.62 | 923.66 | 0.00 | 0.00 |
November | 4483.35 | 1349.03 | 3904.22 | 2996.48 | 907.74 | 0.00 | 0.00 |
December | 4671.28 | 1685.39 | 4164.03 | 3434.89 | 729.14 | 0.00 | 0.00 |
Annual Sum or Average | 3302.18 | 979.27 | 2703.57 | 1662.41 | 1041.16 | 0.00 | 0.00 |
Minimum of Months | 1740.24 | 309.36 | 1217.72 | 150.07 | 729.14 | 0.00 | 0.00 |
Maximum of Months | 4671.28 | 1685.39 | 4164.03 | 3434.89 | 1272.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 924.26 | 1159.38 | 988.61 | 563.77 | 424.84 | 0.00 | 0.00 |
February | 1272.19 | 1064.32 | 1272.67 | 735.19 | 537.49 | 0.00 | 0.00 |
March | 1504.89 | 852.99 | 1421.43 | 756.66 | 664.78 | 0.00 | 0.00 |
April | 2060.70 | 602.67 | 1814.17 | 965.51 | 848.66 | 0.00 | 0.00 |
May | 2071.29 | 457.45 | 1720.10 | 886.32 | 833.78 | 0.00 | 0.00 |
June | 2496.04 | 319.94 | 1843.94 | 1028.90 | 815.04 | 0.00 | 0.00 |
July | 2352.98 | 215.65 | 1663.18 | 813.94 | 849.24 | 0.00 | 0.00 |
August | 2324.20 | 244.53 | 1699.47 | 786.08 | 913.40 | 0.00 | 0.00 |
September | 1985.02 | 401.13 | 1535.02 | 808.43 | 726.59 | 0.00 | 0.00 |
October | 1625.30 | 681.46 | 1404.34 | 872.85 | 531.49 | 0.00 | 0.00 |
November | 1089.02 | 924.30 | 1102.40 | 648.57 | 453.83 | 0.00 | 0.00 |
December | 870.49 | 1189.05 | 953.35 | 597.85 | 355.50 | 0.00 | 0.00 |
Annual Sum or Average | 1716.22 | 674.13 | 1451.69 | 788.30 | 663.39 | 0.00 | 0.00 |
Minimum of Months | 870.49 | 215.65 | 953.35 | 563.77 | 355.50 | 0.00 | 0.00 |
Maximum of Months | 2496.04 | 1189.05 | 1843.94 | 1028.90 | 913.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 124.43 | 1856.72 | 519.12 | 0.00 | 519.12 | 0.00 | 0.00 |
February | 259.49 | 1658.79 | 648.81 | 0.00 | 648.81 | 0.00 | 0.00 |
March | 540.95 | 1287.75 | 818.39 | 0.00 | 818.39 | 0.00 | 0.00 |
April | 850.28 | 865.62 | 1038.28 | 8.89 | 1029.39 | 0.00 | 0.00 |
May | 1161.97 | 637.35 | 1128.62 | 72.77 | 1055.86 | 0.00 | 0.00 |
June | 1769.59 | 429.58 | 1282.42 | 209.86 | 1072.56 | 0.00 | 0.00 |
July | 1754.59 | 294.22 | 1177.06 | 97.97 | 1079.09 | 0.00 | 0.00 |
August | 1481.50 | 339.71 | 1091.92 | 24.45 | 1067.47 | 0.00 | 0.00 |
September | 1002.74 | 612.23 | 873.20 | 0.22 | 872.97 | 0.00 | 0.00 |
October | 454.04 | 1091.04 | 651.58 | 0.00 | 651.58 | 0.00 | 0.00 |
November | 159.58 | 1536.47 | 553.35 | 0.00 | 553.35 | 0.00 | 0.00 |
December | 37.67 | 1974.83 | 441.85 | 0.00 | 441.85 | 0.00 | 0.00 |
Annual Sum or Average | 802.58 | 1045.74 | 852.79 | 34.57 | 818.22 | 0.00 | 0.00 |
Minimum of Months | 37.67 | 294.22 | 441.85 | 0.00 | 441.85 | 0.00 | 0.00 |
Maximum of Months | 1769.59 | 1974.83 | 1282.42 | 209.86 | 1079.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 807.31 | 1162.87 | 958.44 | 535.86 | 422.58 | 0.00 | 0.00 |
February | 1081.22 | 1054.60 | 1164.49 | 627.78 | 536.71 | 0.00 | 0.00 |
March | 1609.21 | 839.08 | 1536.13 | 873.26 | 662.87 | 0.00 | 0.00 |
April | 2410.18 | 595.97 | 2098.67 | 1195.60 | 903.07 | 0.00 | 0.00 |
May | 2434.16 | 457.95 | 2002.58 | 1141.25 | 861.33 | 0.00 | 0.00 |
June | 2890.81 | 301.11 | 2158.93 | 1330.00 | 828.93 | 0.00 | 0.00 |
July | 2789.67 | 214.00 | 1997.70 | 1142.36 | 855.34 | 0.00 | 0.00 |
August | 2673.55 | 243.61 | 1976.86 | 1089.87 | 886.98 | 0.00 | 0.00 |
September | 2096.29 | 410.15 | 1645.40 | 920.61 | 724.79 | 0.00 | 0.00 |
October | 1594.04 | 703.42 | 1430.99 | 907.91 | 523.09 | 0.00 | 0.00 |
November | 1044.50 | 991.47 | 1118.39 | 657.49 | 460.90 | 0.00 | 0.00 |
December | 764.04 | 1244.34 | 906.21 | 551.51 | 354.70 | 0.00 | 0.00 |
Annual Sum or Average | 1853.04 | 683.05 | 1584.45 | 915.59 | 668.86 | 0.00 | 0.00 |
Minimum of Months | 764.04 | 214.00 | 906.21 | 535.86 | 354.70 | 0.00 | 0.00 |
Maximum of Months | 2890.81 | 1244.34 | 2158.93 | 1330.00 | 903.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4278.77 | 1835.53 | 3837.77 | 2986.31 | 851.46 | 0.00 | 0.00 |
February | 4289.24 | 1682.01 | 3755.78 | 2743.46 | 1012.32 | 0.00 | 0.00 |
March | 3241.41 | 1342.47 | 2767.63 | 1673.20 | 1094.44 | 0.00 | 0.00 |
April | 2627.40 | 953.44 | 2158.41 | 885.98 | 1272.43 | 0.00 | 0.00 |
May | 1776.62 | 686.35 | 1439.49 | 316.66 | 1122.83 | 0.00 | 0.00 |
June | 1768.63 | 455.74 | 1217.69 | 150.06 | 1067.62 | 0.00 | 0.00 |
July | 2106.82 | 312.23 | 1347.43 | 215.17 | 1132.26 | 0.00 | 0.00 |
August | 2759.72 | 377.17 | 1852.81 | 602.25 | 1250.56 | 0.00 | 0.00 |
September | 3528.14 | 665.39 | 2562.03 | 1428.65 | 1133.37 | 0.00 | 0.00 |
October | 4342.73 | 1117.73 | 3505.15 | 2581.52 | 923.63 | 0.00 | 0.00 |
November | 4470.05 | 1542.36 | 3904.07 | 2996.35 | 907.71 | 0.00 | 0.00 |
December | 4672.92 | 1903.51 | 4163.87 | 3434.75 | 729.12 | 0.00 | 0.00 |
Annual Sum or Average | 3316.37 | 1069.67 | 2703.47 | 1662.34 | 1041.13 | 0.00 | 0.00 |
Minimum of Months | 1768.63 | 312.23 | 1217.69 | 150.06 | 729.12 | 0.00 | 0.00 |
Maximum of Months | 4672.92 | 1903.51 | 4163.87 | 3434.75 | 1272.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 925.48 | 1240.22 | 988.60 | 563.76 | 424.83 | 0.00 | 0.00 |
February | 1280.92 | 1127.88 | 1272.66 | 735.17 | 537.48 | 0.00 | 0.00 |
March | 1519.73 | 892.31 | 1421.41 | 756.64 | 664.77 | 0.00 | 0.00 |
April | 2074.43 | 637.26 | 1814.15 | 965.50 | 848.65 | 0.00 | 0.00 |
May | 2085.57 | 479.39 | 1720.08 | 886.30 | 833.78 | 0.00 | 0.00 |
June | 2506.82 | 338.24 | 1843.92 | 1028.88 | 815.04 | 0.00 | 0.00 |
July | 2363.63 | 227.89 | 1663.16 | 813.92 | 849.23 | 0.00 | 0.00 |
August | 2330.99 | 265.27 | 1699.45 | 786.06 | 913.39 | 0.00 | 0.00 |
September | 1984.07 | 442.71 | 1535.00 | 808.42 | 726.58 | 0.00 | 0.00 |
October | 1617.09 | 758.92 | 1404.32 | 872.83 | 531.49 | 0.00 | 0.00 |
November | 1077.71 | 1030.47 | 1102.39 | 648.56 | 453.83 | 0.00 | 0.00 |
December | 869.90 | 1292.96 | 953.34 | 597.84 | 355.50 | 0.00 | 0.00 |
Annual Sum or Average | 1721.21 | 725.77 | 1451.67 | 788.29 | 663.38 | 0.00 | 0.00 |
Minimum of Months | 869.90 | 227.89 | 953.34 | 563.76 | 355.50 | 0.00 | 0.00 |
Maximum of Months | 2506.82 | 1292.96 | 1843.92 | 1028.88 | 913.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 113.54 | 1884.74 | 519.13 | 0.00 | 519.13 | 0.00 | 0.00 |
February | 235.21 | 1712.15 | 648.82 | 0.00 | 648.82 | 0.00 | 0.00 |
March | 497.07 | 1356.46 | 818.41 | 0.00 | 818.41 | 0.00 | 0.00 |
April | 807.93 | 912.27 | 1038.30 | 8.89 | 1029.41 | 0.00 | 0.00 |
May | 1125.57 | 666.08 | 1128.64 | 72.77 | 1055.88 | 0.00 | 0.00 |
June | 1748.22 | 443.42 | 1282.44 | 209.87 | 1072.57 | 0.00 | 0.00 |
July | 1740.32 | 304.20 | 1177.08 | 97.97 | 1079.11 | 0.00 | 0.00 |
August | 1472.52 | 344.36 | 1091.94 | 24.45 | 1067.49 | 0.00 | 0.00 |
September | 997.86 | 608.62 | 873.21 | 0.22 | 872.99 | 0.00 | 0.00 |
October | 451.39 | 1079.91 | 651.59 | 0.00 | 651.59 | 0.00 | 0.00 |
November | 155.91 | 1526.45 | 553.36 | 0.00 | 553.36 | 0.00 | 0.00 |
December | 35.90 | 1978.72 | 441.86 | 0.00 | 441.86 | 0.00 | 0.00 |
Annual Sum or Average | 784.68 | 1064.96 | 852.81 | 34.58 | 818.23 | 0.00 | 0.00 |
Minimum of Months | 35.90 | 304.20 | 441.86 | 0.00 | 441.86 | 0.00 | 0.00 |
Maximum of Months | 1748.22 | 1978.72 | 1282.44 | 209.87 | 1079.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 798.25 | 1151.36 | 958.46 | 535.87 | 422.59 | 0.00 | 0.00 |
February | 1063.94 | 1054.84 | 1164.50 | 627.79 | 536.71 | 0.00 | 0.00 |
March | 1588.36 | 839.68 | 1536.16 | 873.28 | 662.88 | 0.00 | 0.00 |
April | 2392.83 | 587.67 | 2098.70 | 1195.62 | 903.08 | 0.00 | 0.00 |
May | 2419.54 | 449.34 | 2002.61 | 1141.27 | 861.34 | 0.00 | 0.00 |
June | 2881.86 | 292.64 | 2158.97 | 1330.03 | 828.94 | 0.00 | 0.00 |
July | 2785.44 | 203.59 | 1997.73 | 1142.38 | 855.35 | 0.00 | 0.00 |
August | 2670.26 | 229.49 | 1976.89 | 1089.90 | 886.99 | 0.00 | 0.00 |
September | 2095.12 | 388.02 | 1645.43 | 920.63 | 724.80 | 0.00 | 0.00 |
October | 1594.77 | 667.48 | 1431.02 | 907.92 | 523.09 | 0.00 | 0.00 |
November | 1045.71 | 947.79 | 1118.41 | 657.51 | 460.91 | 0.00 | 0.00 |
December | 759.13 | 1215.80 | 906.23 | 551.52 | 354.71 | 0.00 | 0.00 |
Annual Sum or Average | 1844.78 | 667.06 | 1584.47 | 915.61 | 668.86 | 0.00 | 0.00 |
Minimum of Months | 759.13 | 203.59 | 906.23 | 535.87 | 354.71 | 0.00 | 0.00 |
Maximum of Months | 2881.86 | 1215.80 | 2158.97 | 1330.03 | 903.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4253.70 | 1750.36 | 3837.92 | 2986.43 | 851.49 | 0.00 | 0.00 |
February | 4252.42 | 1623.45 | 3755.93 | 2743.58 | 1012.35 | 0.00 | 0.00 |
March | 3198.32 | 1332.79 | 2767.73 | 1673.26 | 1094.47 | 0.00 | 0.00 |
April | 2587.52 | 963.13 | 2158.48 | 886.02 | 1272.46 | 0.00 | 0.00 |
May | 1737.07 | 711.68 | 1439.53 | 316.67 | 1122.86 | 0.00 | 0.00 |
June | 1746.82 | 472.22 | 1217.72 | 150.07 | 1067.65 | 0.00 | 0.00 |
July | 2094.50 | 317.99 | 1347.47 | 215.18 | 1132.29 | 0.00 | 0.00 |
August | 2750.13 | 367.79 | 1852.87 | 602.28 | 1250.59 | 0.00 | 0.00 |
September | 3519.10 | 627.98 | 2562.12 | 1428.71 | 1133.40 | 0.00 | 0.00 |
October | 4333.00 | 1044.66 | 3505.28 | 2581.62 | 923.66 | 0.00 | 0.00 |
November | 4459.59 | 1439.60 | 3904.22 | 2996.48 | 907.74 | 0.00 | 0.00 |
December | 4649.23 | 1795.03 | 4164.03 | 3434.89 | 729.14 | 0.00 | 0.00 |
Annual Sum or Average | 3293.02 | 1034.18 | 2703.57 | 1662.41 | 1041.16 | 0.00 | 0.00 |
Minimum of Months | 1737.07 | 317.99 | 1217.72 | 150.07 | 729.14 | 0.00 | 0.00 |
Maximum of Months | 4649.23 | 1795.03 | 4164.03 | 3434.89 | 1272.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 914.14 | 1229.82 | 988.61 | 563.77 | 424.84 | 0.00 | 0.00 |
February | 1263.03 | 1126.84 | 1272.67 | 735.19 | 537.49 | 0.00 | 0.00 |
March | 1495.92 | 901.18 | 1421.43 | 756.66 | 664.78 | 0.00 | 0.00 |
April | 2055.20 | 634.27 | 1814.17 | 965.51 | 848.66 | 0.00 | 0.00 |
May | 2068.48 | 478.13 | 1720.10 | 886.32 | 833.78 | 0.00 | 0.00 |
June | 2498.29 | 331.56 | 1843.94 | 1028.90 | 815.04 | 0.00 | 0.00 |
July | 2357.65 | 221.57 | 1663.18 | 813.94 | 849.24 | 0.00 | 0.00 |
August | 2327.32 | 252.89 | 1699.47 | 786.08 | 913.40 | 0.00 | 0.00 |
September | 1983.25 | 420.04 | 1535.02 | 808.43 | 726.59 | 0.00 | 0.00 |
October | 1618.36 | 723.53 | 1404.34 | 872.85 | 531.49 | 0.00 | 0.00 |
November | 1077.19 | 991.15 | 1102.40 | 648.57 | 453.83 | 0.00 | 0.00 |
December | 862.72 | 1267.08 | 953.35 | 597.85 | 355.50 | 0.00 | 0.00 |
Annual Sum or Average | 1711.68 | 712.77 | 1451.69 | 788.30 | 663.39 | 0.00 | 0.00 |
Minimum of Months | 862.72 | 221.57 | 953.35 | 563.77 | 355.50 | 0.00 | 0.00 |
Maximum of Months | 2498.29 | 1267.08 | 1843.94 | 1028.90 | 913.40 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.348857E+09 | 0.474691E+10 | 0.139043E+10 | 0.00 | 0.139043E+10 | 0.00 | 0.00 |
February | 0.614915E+09 | 0.389842E+10 | 0.156963E+10 | 0.00 | 0.156963E+10 | 0.00 | 0.00 |
March | 0.138507E+10 | 0.341979E+10 | 0.219202E+10 | 0.00 | 0.219202E+10 | 0.00 | 0.00 |
April | 0.212965E+10 | 0.223455E+10 | 0.269128E+10 | 23041611.60 | 0.266824E+10 | 0.00 | 0.00 |
May | 0.303684E+10 | 0.171000E+10 | 0.302296E+10 | 0.194900E+09 | 0.282806E+10 | 0.00 | 0.00 |
June | 0.453006E+10 | 0.111458E+10 | 0.332409E+10 | 0.543982E+09 | 0.278011E+10 | 0.00 | 0.00 |
July | 0.464681E+10 | 0.795116E+09 | 0.315270E+10 | 0.262399E+09 | 0.289030E+10 | 0.00 | 0.00 |
August | 0.393629E+10 | 0.893110E+09 | 0.292465E+10 | 65476725.60 | 0.285918E+10 | 0.00 | 0.00 |
September | 0.259495E+10 | 0.150299E+10 | 0.226337E+10 | 580897.12 | 0.226279E+10 | 0.00 | 0.00 |
October | 0.124737E+10 | 0.270444E+10 | 0.174523E+10 | 0.00 | 0.174523E+10 | 0.00 | 0.00 |
November | 0.459731E+09 | 0.366251E+10 | 0.143430E+10 | 0.00 | 0.143430E+10 | 0.00 | 0.00 |
December | 0.121553E+09 | 0.495850E+10 | 0.118347E+10 | 0.00 | 0.118347E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.250521E+11 | 0.316409E+11 | 0.268941E+11 | 0.109038E+10 | 0.258038E+11 | 0.00 | 0.00 |
Minimum of Months | 0.121553E+09 | 0.795116E+09 | 0.118347E+10 | 0.00 | 0.118347E+10 | 0.00 | 0.00 |
Maximum of Months | 0.464681E+10 | 0.495850E+10 | 0.332409E+10 | 0.543982E+09 | 0.289030E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.219253E+10 | 0.291440E+10 | 0.256713E+10 | 0.143527E+10 | 0.113186E+10 | 0.00 | 0.00 |
February | 0.261549E+10 | 0.241474E+10 | 0.281717E+10 | 0.151876E+10 | 0.129841E+10 | 0.00 | 0.00 |
March | 0.428513E+10 | 0.213661E+10 | 0.411444E+10 | 0.233899E+10 | 0.177546E+10 | 0.00 | 0.00 |
April | 0.621483E+10 | 0.145741E+10 | 0.543984E+10 | 0.309905E+10 | 0.234079E+10 | 0.00 | 0.00 |
May | 0.647910E+10 | 0.115890E+10 | 0.536379E+10 | 0.305678E+10 | 0.230701E+10 | 0.00 | 0.00 |
June | 0.745939E+10 | 0.736462E+09 | 0.559604E+10 | 0.344743E+10 | 0.214861E+10 | 0.00 | 0.00 |
July | 0.744364E+10 | 0.532755E+09 | 0.535072E+10 | 0.305976E+10 | 0.229096E+10 | 0.00 | 0.00 |
August | 0.713898E+10 | 0.596663E+09 | 0.529490E+10 | 0.291918E+10 | 0.237572E+10 | 0.00 | 0.00 |
September | 0.543089E+10 | 0.964969E+09 | 0.426495E+10 | 0.238627E+10 | 0.187867E+10 | 0.00 | 0.00 |
October | 0.429424E+10 | 0.169304E+10 | 0.383283E+10 | 0.243178E+10 | 0.140105E+10 | 0.00 | 0.00 |
November | 0.275794E+10 | 0.230221E+10 | 0.289892E+10 | 0.170425E+10 | 0.119467E+10 | 0.00 | 0.00 |
December | 0.207940E+10 | 0.305844E+10 | 0.242724E+10 | 0.147720E+10 | 0.950044E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.583916E+11 | 0.199666E+11 | 0.499680E+11 | 0.288747E+11 | 0.210932E+11 | 0.00 | 0.00 |
Minimum of Months | 0.207940E+10 | 0.532755E+09 | 0.242724E+10 | 0.143527E+10 | 0.950044E+09 | 0.00 | 0.00 |
Maximum of Months | 0.745939E+10 | 0.305844E+10 | 0.559604E+10 | 0.344743E+10 | 0.237572E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114603E+11 | 0.442442E+10 | 0.102795E+11 | 0.799886E+10 | 0.228063E+10 | 0.00 | 0.00 |
February | 0.103347E+11 | 0.370905E+10 | 0.908634E+10 | 0.663726E+10 | 0.244908E+10 | 0.00 | 0.00 |
March | 0.860663E+10 | 0.338091E+10 | 0.741310E+10 | 0.448167E+10 | 0.293143E+10 | 0.00 | 0.00 |
April | 0.672394E+10 | 0.237039E+10 | 0.559478E+10 | 0.229655E+10 | 0.329822E+10 | 0.00 | 0.00 |
May | 0.466106E+10 | 0.182171E+10 | 0.385563E+10 | 0.848168E+09 | 0.300746E+10 | 0.00 | 0.00 |
June | 0.452069E+10 | 0.117883E+10 | 0.315633E+10 | 0.388983E+09 | 0.276734E+10 | 0.00 | 0.00 |
July | 0.559159E+10 | 0.828583E+09 | 0.360905E+10 | 0.576333E+09 | 0.303272E+10 | 0.00 | 0.00 |
August | 0.734907E+10 | 0.951744E+09 | 0.496272E+10 | 0.161314E+10 | 0.334958E+10 | 0.00 | 0.00 |
September | 0.911916E+10 | 0.155789E+10 | 0.664101E+10 | 0.370322E+10 | 0.293779E+10 | 0.00 | 0.00 |
October | 0.116382E+11 | 0.264782E+10 | 0.938855E+10 | 0.691462E+10 | 0.247393E+10 | 0.00 | 0.00 |
November | 0.116208E+11 | 0.349667E+10 | 0.101197E+11 | 0.776687E+10 | 0.235287E+10 | 0.00 | 0.00 |
December | 0.125116E+11 | 0.451414E+10 | 0.111529E+11 | 0.920001E+10 | 0.195293E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.104138E+12 | 0.308822E+11 | 0.852597E+11 | 0.524257E+11 | 0.328340E+11 | 0.00 | 0.00 |
Minimum of Months | 0.452069E+10 | 0.828583E+09 | 0.315633E+10 | 0.388983E+09 | 0.195293E+10 | 0.00 | 0.00 |
Maximum of Months | 0.125116E+11 | 0.451414E+10 | 0.111529E+11 | 0.920001E+10 | 0.334958E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.247554E+10 | 0.310527E+10 | 0.264789E+10 | 0.151001E+10 | 0.113788E+10 | 0.00 | 0.00 |
February | 0.307768E+10 | 0.257481E+10 | 0.307885E+10 | 0.177856E+10 | 0.130029E+10 | 0.00 | 0.00 |
March | 0.403071E+10 | 0.228466E+10 | 0.380716E+10 | 0.202663E+10 | 0.178053E+10 | 0.00 | 0.00 |
April | 0.534134E+10 | 0.156212E+10 | 0.470233E+10 | 0.250260E+10 | 0.219973E+10 | 0.00 | 0.00 |
May | 0.554775E+10 | 0.122525E+10 | 0.460711E+10 | 0.237391E+10 | 0.223321E+10 | 0.00 | 0.00 |
June | 0.646972E+10 | 0.829276E+09 | 0.477950E+10 | 0.266691E+10 | 0.211259E+10 | 0.00 | 0.00 |
July | 0.630223E+10 | 0.577603E+09 | 0.445466E+10 | 0.218005E+10 | 0.227461E+10 | 0.00 | 0.00 |
August | 0.622514E+10 | 0.654951E+09 | 0.455187E+10 | 0.210543E+10 | 0.244644E+10 | 0.00 | 0.00 |
September | 0.514518E+10 | 0.103973E+10 | 0.397878E+10 | 0.209546E+10 | 0.188332E+10 | 0.00 | 0.00 |
October | 0.435320E+10 | 0.182522E+10 | 0.376138E+10 | 0.233783E+10 | 0.142355E+10 | 0.00 | 0.00 |
November | 0.282274E+10 | 0.239579E+10 | 0.285742E+10 | 0.168109E+10 | 0.117634E+10 | 0.00 | 0.00 |
December | 0.233152E+10 | 0.318475E+10 | 0.255346E+10 | 0.160129E+10 | 0.952167E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.541228E+11 | 0.212594E+11 | 0.457804E+11 | 0.248598E+11 | 0.209206E+11 | 0.00 | 0.00 |
Minimum of Months | 0.233152E+10 | 0.577603E+09 | 0.255346E+10 | 0.151001E+10 | 0.952167E+09 | 0.00 | 0.00 |
Maximum of Months | 0.646972E+10 | 0.318475E+10 | 0.477950E+10 | 0.266691E+10 | 0.244644E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.333262E+09 | 0.497304E+10 | 0.139040E+10 | 0.00 | 0.139040E+10 | 0.00 | 0.00 |
February | 0.627753E+09 | 0.401295E+10 | 0.156960E+10 | 0.00 | 0.156960E+10 | 0.00 | 0.00 |
March | 0.144887E+10 | 0.344910E+10 | 0.219198E+10 | 0.00 | 0.219198E+10 | 0.00 | 0.00 |
April | 0.220393E+10 | 0.224369E+10 | 0.269123E+10 | 23040934.35 | 0.266819E+10 | 0.00 | 0.00 |
May | 0.311223E+10 | 0.170707E+10 | 0.302290E+10 | 0.194894E+09 | 0.282801E+10 | 0.00 | 0.00 |
June | 0.458678E+10 | 0.111347E+10 | 0.332403E+10 | 0.543966E+09 | 0.278006E+10 | 0.00 | 0.00 |
July | 0.469949E+10 | 0.788050E+09 | 0.315264E+10 | 0.262391E+09 | 0.289025E+10 | 0.00 | 0.00 |
August | 0.396806E+10 | 0.909887E+09 | 0.292460E+10 | 65474801.06 | 0.285912E+10 | 0.00 | 0.00 |
September | 0.259910E+10 | 0.158690E+10 | 0.226333E+10 | 580880.05 | 0.226275E+10 | 0.00 | 0.00 |
October | 0.121609E+10 | 0.292225E+10 | 0.174520E+10 | 0.00 | 0.174520E+10 | 0.00 | 0.00 |
November | 0.413627E+09 | 0.398254E+10 | 0.143427E+10 | 0.00 | 0.143427E+10 | 0.00 | 0.00 |
December | 0.100884E+09 | 0.528939E+10 | 0.118344E+10 | 0.00 | 0.118344E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.253101E+11 | 0.329783E+11 | 0.268936E+11 | 0.109035E+10 | 0.258033E+11 | 0.00 | 0.00 |
Minimum of Months | 0.100884E+09 | 0.788050E+09 | 0.118344E+10 | 0.00 | 0.118344E+10 | 0.00 | 0.00 |
Maximum of Months | 0.469949E+10 | 0.528939E+10 | 0.332403E+10 | 0.543966E+09 | 0.289025E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.216230E+10 | 0.311462E+10 | 0.256709E+10 | 0.143524E+10 | 0.113185E+10 | 0.00 | 0.00 |
February | 0.261568E+10 | 0.255130E+10 | 0.281712E+10 | 0.151873E+10 | 0.129840E+10 | 0.00 | 0.00 |
March | 0.431012E+10 | 0.224738E+10 | 0.411438E+10 | 0.233894E+10 | 0.177544E+10 | 0.00 | 0.00 |
April | 0.624718E+10 | 0.154476E+10 | 0.543975E+10 | 0.309899E+10 | 0.234076E+10 | 0.00 | 0.00 |
May | 0.651965E+10 | 0.122657E+10 | 0.536370E+10 | 0.305672E+10 | 0.230699E+10 | 0.00 | 0.00 |
June | 0.749299E+10 | 0.780466E+09 | 0.559595E+10 | 0.344736E+10 | 0.214859E+10 | 0.00 | 0.00 |
July | 0.747185E+10 | 0.573183E+09 | 0.535063E+10 | 0.305970E+10 | 0.229094E+10 | 0.00 | 0.00 |
August | 0.716083E+10 | 0.652489E+09 | 0.529481E+10 | 0.291912E+10 | 0.237569E+10 | 0.00 | 0.00 |
September | 0.543357E+10 | 0.106311E+10 | 0.426488E+10 | 0.238623E+10 | 0.187865E+10 | 0.00 | 0.00 |
October | 0.426947E+10 | 0.188403E+10 | 0.383277E+10 | 0.243173E+10 | 0.140104E+10 | 0.00 | 0.00 |
November | 0.270735E+10 | 0.256990E+10 | 0.289887E+10 | 0.170422E+10 | 0.119465E+10 | 0.00 | 0.00 |
December | 0.204641E+10 | 0.333284E+10 | 0.242721E+10 | 0.147717E+10 | 0.950034E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.584374E+11 | 0.215406E+11 | 0.499672E+11 | 0.288741E+11 | 0.210930E+11 | 0.00 | 0.00 |
Minimum of Months | 0.204641E+10 | 0.573183E+09 | 0.242721E+10 | 0.143524E+10 | 0.950034E+09 | 0.00 | 0.00 |
Maximum of Months | 0.749299E+10 | 0.333284E+10 | 0.559595E+10 | 0.344736E+10 | 0.237569E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114603E+11 | 0.491627E+10 | 0.102791E+11 | 0.799853E+10 | 0.228055E+10 | 0.00 | 0.00 |
February | 0.103765E+11 | 0.406911E+10 | 0.908599E+10 | 0.663699E+10 | 0.244900E+10 | 0.00 | 0.00 |
March | 0.868180E+10 | 0.359566E+10 | 0.741282E+10 | 0.448149E+10 | 0.293134E+10 | 0.00 | 0.00 |
April | 0.681021E+10 | 0.247132E+10 | 0.559459E+10 | 0.229646E+10 | 0.329813E+10 | 0.00 | 0.00 |
May | 0.475851E+10 | 0.183833E+10 | 0.385552E+10 | 0.848133E+09 | 0.300739E+10 | 0.00 | 0.00 |
June | 0.458429E+10 | 0.118127E+10 | 0.315625E+10 | 0.388967E+09 | 0.276728E+10 | 0.00 | 0.00 |
July | 0.564290E+10 | 0.836275E+09 | 0.360896E+10 | 0.576309E+09 | 0.303265E+10 | 0.00 | 0.00 |
August | 0.739163E+10 | 0.101022E+10 | 0.496256E+10 | 0.161307E+10 | 0.334949E+10 | 0.00 | 0.00 |
September | 0.914494E+10 | 0.172469E+10 | 0.664077E+10 | 0.370307E+10 | 0.293770E+10 | 0.00 | 0.00 |
October | 0.116316E+11 | 0.299374E+10 | 0.938820E+10 | 0.691433E+10 | 0.247386E+10 | 0.00 | 0.00 |
November | 0.115864E+11 | 0.399779E+10 | 0.101193E+11 | 0.776655E+10 | 0.235279E+10 | 0.00 | 0.00 |
December | 0.125160E+11 | 0.509836E+10 | 0.111525E+11 | 0.919963E+10 | 0.195287E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.104585E+12 | 0.337330E+11 | 0.852566E+11 | 0.524235E+11 | 0.328331E+11 | 0.00 | 0.00 |
Minimum of Months | 0.458429E+10 | 0.836275E+09 | 0.315625E+10 | 0.388967E+09 | 0.195287E+10 | 0.00 | 0.00 |
Maximum of Months | 0.125160E+11 | 0.509836E+10 | 0.111525E+11 | 0.919963E+10 | 0.334949E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.247879E+10 | 0.332181E+10 | 0.264786E+10 | 0.150999E+10 | 0.113787E+10 | 0.00 | 0.00 |
February | 0.309881E+10 | 0.272856E+10 | 0.307881E+10 | 0.177853E+10 | 0.130028E+10 | 0.00 | 0.00 |
March | 0.407044E+10 | 0.238997E+10 | 0.380711E+10 | 0.202659E+10 | 0.178052E+10 | 0.00 | 0.00 |
April | 0.537693E+10 | 0.165177E+10 | 0.470227E+10 | 0.250256E+10 | 0.219971E+10 | 0.00 | 0.00 |
May | 0.558599E+10 | 0.128399E+10 | 0.460706E+10 | 0.237387E+10 | 0.223319E+10 | 0.00 | 0.00 |
June | 0.649768E+10 | 0.876715E+09 | 0.477944E+10 | 0.266687E+10 | 0.211257E+10 | 0.00 | 0.00 |
July | 0.633076E+10 | 0.610379E+09 | 0.445460E+10 | 0.218001E+10 | 0.227459E+10 | 0.00 | 0.00 |
August | 0.624332E+10 | 0.710510E+09 | 0.455181E+10 | 0.210539E+10 | 0.244642E+10 | 0.00 | 0.00 |
September | 0.514272E+10 | 0.114752E+10 | 0.397873E+10 | 0.209543E+10 | 0.188330E+10 | 0.00 | 0.00 |
October | 0.433122E+10 | 0.203269E+10 | 0.376133E+10 | 0.233780E+10 | 0.142353E+10 | 0.00 | 0.00 |
November | 0.279344E+10 | 0.267097E+10 | 0.285738E+10 | 0.168106E+10 | 0.117633E+10 | 0.00 | 0.00 |
December | 0.232994E+10 | 0.346307E+10 | 0.255342E+10 | 0.160126E+10 | 0.952159E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.542800E+11 | 0.228879E+11 | 0.457798E+11 | 0.248594E+11 | 0.209205E+11 | 0.00 | 0.00 |
Minimum of Months | 0.232994E+10 | 0.610379E+09 | 0.255342E+10 | 0.150999E+10 | 0.952159E+09 | 0.00 | 0.00 |
Maximum of Months | 0.649768E+10 | 0.346307E+10 | 0.477944E+10 | 0.266687E+10 | 0.244642E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.304115E+09 | 0.504810E+10 | 0.139043E+10 | 0.00 | 0.139043E+10 | 0.00 | 0.00 |
February | 0.569024E+09 | 0.414203E+10 | 0.156963E+10 | 0.00 | 0.156963E+10 | 0.00 | 0.00 |
March | 0.133136E+10 | 0.363315E+10 | 0.219202E+10 | 0.00 | 0.219202E+10 | 0.00 | 0.00 |
April | 0.209417E+10 | 0.236459E+10 | 0.269128E+10 | 23041611.60 | 0.266824E+10 | 0.00 | 0.00 |
May | 0.301473E+10 | 0.178404E+10 | 0.302296E+10 | 0.194900E+09 | 0.282806E+10 | 0.00 | 0.00 |
June | 0.453138E+10 | 0.114935E+10 | 0.332409E+10 | 0.543982E+09 | 0.278011E+10 | 0.00 | 0.00 |
July | 0.466127E+10 | 0.814758E+09 | 0.315270E+10 | 0.262399E+09 | 0.289030E+10 | 0.00 | 0.00 |
August | 0.394400E+10 | 0.922346E+09 | 0.292465E+10 | 65476725.60 | 0.285918E+10 | 0.00 | 0.00 |
September | 0.258646E+10 | 0.157755E+10 | 0.226337E+10 | 580897.12 | 0.226279E+10 | 0.00 | 0.00 |
October | 0.120899E+10 | 0.289244E+10 | 0.174523E+10 | 0.00 | 0.174523E+10 | 0.00 | 0.00 |
November | 0.404114E+09 | 0.395657E+10 | 0.143430E+10 | 0.00 | 0.143430E+10 | 0.00 | 0.00 |
December | 96156304.41 | 0.529980E+10 | 0.118347E+10 | 0.00 | 0.118347E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.247458E+11 | 0.335847E+11 | 0.268941E+11 | 0.109038E+10 | 0.258038E+11 | 0.00 | 0.00 |
Minimum of Months | 96156304.41 | 0.814758E+09 | 0.118347E+10 | 0.00 | 0.118347E+10 | 0.00 | 0.00 |
Maximum of Months | 0.466127E+10 | 0.529980E+10 | 0.332409E+10 | 0.543982E+09 | 0.289030E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.213803E+10 | 0.308380E+10 | 0.256713E+10 | 0.143527E+10 | 0.113186E+10 | 0.00 | 0.00 |
February | 0.257389E+10 | 0.255186E+10 | 0.281717E+10 | 0.151876E+10 | 0.129841E+10 | 0.00 | 0.00 |
March | 0.425426E+10 | 0.224899E+10 | 0.411444E+10 | 0.233899E+10 | 0.177546E+10 | 0.00 | 0.00 |
April | 0.620222E+10 | 0.152324E+10 | 0.543984E+10 | 0.309905E+10 | 0.234079E+10 | 0.00 | 0.00 |
May | 0.648048E+10 | 0.120352E+10 | 0.536379E+10 | 0.305678E+10 | 0.230701E+10 | 0.00 | 0.00 |
June | 0.746979E+10 | 0.758526E+09 | 0.559604E+10 | 0.344743E+10 | 0.214861E+10 | 0.00 | 0.00 |
July | 0.746053E+10 | 0.545298E+09 | 0.535072E+10 | 0.305976E+10 | 0.229096E+10 | 0.00 | 0.00 |
August | 0.715201E+10 | 0.614655E+09 | 0.529490E+10 | 0.291918E+10 | 0.237572E+10 | 0.00 | 0.00 |
September | 0.543055E+10 | 0.100576E+10 | 0.426495E+10 | 0.238627E+10 | 0.187867E+10 | 0.00 | 0.00 |
October | 0.427142E+10 | 0.178779E+10 | 0.383283E+10 | 0.243178E+10 | 0.140105E+10 | 0.00 | 0.00 |
November | 0.271048E+10 | 0.245666E+10 | 0.289892E+10 | 0.170425E+10 | 0.119467E+10 | 0.00 | 0.00 |
December | 0.203327E+10 | 0.325639E+10 | 0.242724E+10 | 0.147720E+10 | 0.950044E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.581769E+11 | 0.210365E+11 | 0.499680E+11 | 0.288747E+11 | 0.210932E+11 | 0.00 | 0.00 |
Minimum of Months | 0.203327E+10 | 0.545298E+09 | 0.242724E+10 | 0.143527E+10 | 0.950044E+09 | 0.00 | 0.00 |
Maximum of Months | 0.746979E+10 | 0.325639E+10 | 0.559604E+10 | 0.344743E+10 | 0.237572E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113931E+11 | 0.468817E+10 | 0.102795E+11 | 0.799886E+10 | 0.228063E+10 | 0.00 | 0.00 |
February | 0.102875E+11 | 0.392744E+10 | 0.908634E+10 | 0.663726E+10 | 0.244908E+10 | 0.00 | 0.00 |
March | 0.856638E+10 | 0.356974E+10 | 0.741310E+10 | 0.448167E+10 | 0.293143E+10 | 0.00 | 0.00 |
April | 0.670686E+10 | 0.249645E+10 | 0.559478E+10 | 0.229655E+10 | 0.329822E+10 | 0.00 | 0.00 |
May | 0.465256E+10 | 0.190616E+10 | 0.385563E+10 | 0.848168E+09 | 0.300746E+10 | 0.00 | 0.00 |
June | 0.452775E+10 | 0.122401E+10 | 0.315633E+10 | 0.388983E+09 | 0.276734E+10 | 0.00 | 0.00 |
July | 0.560991E+10 | 0.851700E+09 | 0.360905E+10 | 0.576333E+09 | 0.303272E+10 | 0.00 | 0.00 |
August | 0.736594E+10 | 0.985077E+09 | 0.496272E+10 | 0.161314E+10 | 0.334958E+10 | 0.00 | 0.00 |
September | 0.912150E+10 | 0.162774E+10 | 0.664101E+10 | 0.370322E+10 | 0.293779E+10 | 0.00 | 0.00 |
October | 0.116055E+11 | 0.279802E+10 | 0.938855E+10 | 0.691462E+10 | 0.247393E+10 | 0.00 | 0.00 |
November | 0.115593E+11 | 0.373144E+10 | 0.101197E+11 | 0.776687E+10 | 0.235287E+10 | 0.00 | 0.00 |
December | 0.124525E+11 | 0.480782E+10 | 0.111529E+11 | 0.920001E+10 | 0.195293E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.103849E+12 | 0.326138E+11 | 0.852597E+11 | 0.524257E+11 | 0.328340E+11 | 0.00 | 0.00 |
Minimum of Months | 0.452775E+10 | 0.851700E+09 | 0.315633E+10 | 0.388983E+09 | 0.195293E+10 | 0.00 | 0.00 |
Maximum of Months | 0.124525E+11 | 0.480782E+10 | 0.111529E+11 | 0.920001E+10 | 0.334958E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244844E+10 | 0.329394E+10 | 0.264789E+10 | 0.151001E+10 | 0.113788E+10 | 0.00 | 0.00 |
February | 0.305552E+10 | 0.272606E+10 | 0.307885E+10 | 0.177856E+10 | 0.130029E+10 | 0.00 | 0.00 |
March | 0.400666E+10 | 0.241372E+10 | 0.380716E+10 | 0.202663E+10 | 0.178053E+10 | 0.00 | 0.00 |
April | 0.532707E+10 | 0.164404E+10 | 0.470233E+10 | 0.250260E+10 | 0.219973E+10 | 0.00 | 0.00 |
May | 0.554022E+10 | 0.128062E+10 | 0.460711E+10 | 0.237391E+10 | 0.223321E+10 | 0.00 | 0.00 |
June | 0.647557E+10 | 0.859413E+09 | 0.477950E+10 | 0.266691E+10 | 0.211259E+10 | 0.00 | 0.00 |
July | 0.631474E+10 | 0.593460E+09 | 0.445466E+10 | 0.218005E+10 | 0.227461E+10 | 0.00 | 0.00 |
August | 0.623349E+10 | 0.677333E+09 | 0.455187E+10 | 0.210543E+10 | 0.244644E+10 | 0.00 | 0.00 |
September | 0.514058E+10 | 0.108874E+10 | 0.397878E+10 | 0.209546E+10 | 0.188332E+10 | 0.00 | 0.00 |
October | 0.433460E+10 | 0.193792E+10 | 0.376138E+10 | 0.233783E+10 | 0.142355E+10 | 0.00 | 0.00 |
November | 0.279209E+10 | 0.256905E+10 | 0.285742E+10 | 0.168109E+10 | 0.117634E+10 | 0.00 | 0.00 |
December | 0.231072E+10 | 0.339373E+10 | 0.255346E+10 | 0.160129E+10 | 0.952167E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.539797E+11 | 0.224780E+11 | 0.457804E+11 | 0.248598E+11 | 0.209206E+11 | 0.00 | 0.00 |
Minimum of Months | 0.231072E+10 | 0.593460E+09 | 0.255346E+10 | 0.151001E+10 | 0.952167E+09 | 0.00 | 0.00 |
Maximum of Months | 0.647557E+10 | 0.339373E+10 | 0.477950E+10 | 0.266691E+10 | 0.244644E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.521375E+10 | -0.450625E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -707500217.2 | 58.99 | 0.00 | 0.00 |
February | 0.476178E+10 | -0.412718E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -634603161.5 | 58.98 | 0.00 | 0.00 |
March | 0.546138E+10 | -0.476417E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -697208040.9 | 58.98 | 0.00 | 0.00 |
April | 0.472916E+10 | -0.406024E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668921670.6 | 58.98 | 0.00 | 0.00 |
May | 0.474203E+10 | -0.405225E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689780258.4 | 58.98 | 0.00 | 0.00 |
June | 0.440213E+10 | -0.373567E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666460497.2 | 58.98 | 0.00 | 0.00 |
July | 0.402671E+10 | -0.334106E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -685658515.5 | 58.98 | 0.00 | 0.00 |
August | 0.434269E+10 | -0.365564E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687048285.5 | 58.98 | 0.00 | 0.00 |
September | 0.406934E+10 | -0.340514E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -664204924.6 | 58.98 | 0.00 | 0.00 |
October | 0.444472E+10 | -0.375499E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689735288.4 | 58.98 | 0.00 | 0.00 |
November | 0.465559E+10 | -0.398221E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -673378554.5 | 58.98 | 0.00 | 0.00 |
December | 0.491008E+10 | -0.420509E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -704986016.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.557594E+11 | -0.475899E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.816949E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.402671E+10 | -0.476417E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -707500217.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.546138E+10 | -0.334106E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -634603161.5 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-07:40 | 11645.42 | 37.83 | 289.00 | 288.33 | 3060.27 | 27.75 | 202.50 | 278.50 |
February | 282.00 | 0.49 | 0.48 | 01-FEB-07:40 | 14253.02 | 37.92 | 272.83 | 277.33 | 2360.16 | 25.13 | 177.67 | 265.50 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:10 | 2616.83 | 18.87 | 28.83 | 333.83 | 1563.24 | 20.94 | 148.83 | 304.83 |
April | 381.83 | 0.51 | 0.48 | 01-APR-06:40 | 2091.54 | 19.16 | 14.50 | 355.00 | 1285.68 | 21.37 | 204.83 | 332.50 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-06:30 | 1595.50 | 18.53 | 0.00 | 376.33 | 995.13 | 20.79 | 149.00 | 344.50 |
June | 412.83 | 0.51 | 0.48 | 01-JUN-06:10 | 1264.41 | 17.64 | 0.00 | 378.50 | 795.35 | 19.97 | 101.50 | 334.83 |
July | 395.33 | 0.51 | 0.48 | 01-JUL-06:00 | 1537.79 | 18.35 | 1.83 | 380.50 | 947.75 | 20.66 | 144.50 | 344.67 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-06:30 | 1936.67 | 18.92 | 10.67 | 375.83 | 1173.09 | 21.16 | 210.00 | 350.17 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:40 | 2562.19 | 19.39 | 41.00 | 333.33 | 1448.93 | 20.94 | 153.00 | 307.67 |
October | 329.00 | 0.50 | 0.48 | 01-OCT-06:00 | 6981.32 | 28.50 | 183.67 | 320.83 | 1980.18 | 21.18 | 117.17 | 306.50 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-06:49 | 13153.38 | 38.91 | 280.17 | 285.83 | 3059.46 | 27.87 | 188.17 | 276.33 |
December | 265.67 | 0.50 | 0.48 | 01-DEC-07:49 | 13317.93 | 40.23 | 263.83 | 270.50 | 4450.45 | 31.08 | 178.33 | 263.00 |
Annual Sum or Average | 4149.83 | 0.50 | 5365.68 | 24.92 | 1386.33 | 3976.17 | 1785.86 | 22.79 | 1975.50 | 3709.00 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 1264.41 | 17.64 | 0.00 | 270.50 | 795.35 | 19.97 | 101.50 | 263.00 | |
Maximum of Months | 412.83 | 0.51 | 0.48 | 14253.02 | 40.23 | 289.00 | 380.50 | 4450.45 | 31.08 | 210.00 | 350.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-07:40 | 2975.87 | 23.42 | 106.67 | 267.67 | 1668.71 | 23.96 | 110.67 | 240.50 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-07:30 | 3780.36 | 23.27 | 97.00 | 269.17 | 2110.44 | 23.90 | 114.17 | 245.67 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-06:00 | 3838.41 | 22.48 | 105.67 | 330.00 | 2081.75 | 23.18 | 110.50 | 304.17 |
April | 381.83 | 0.51 | 0.48 | 01-APR-05:00 | 5394.08 | 22.67 | 114.83 | 359.50 | 2197.95 | 22.98 | 69.00 | 343.17 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-05:00 | 4369.00 | 21.34 | 95.50 | 379.17 | 2445.75 | 22.39 | 68.33 | 354.33 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-05:30 | 4176.49 | 20.94 | 111.83 | 395.00 | 2381.03 | 22.04 | 85.17 | 362.17 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-06:40 | 4154.53 | 21.37 | 102.33 | 388.00 | 2234.07 | 22.39 | 82.17 | 360.00 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:40 | 4973.17 | 22.28 | 118.83 | 382.17 | 2066.12 | 22.78 | 81.00 | 362.67 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:19 | 4295.08 | 22.43 | 109.67 | 335.83 | 2399.92 | 23.33 | 101.17 | 313.00 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-06:30 | 3903.89 | 22.74 | 103.00 | 307.50 | 2161.13 | 23.35 | 92.83 | 284.83 |
November | 284.17 | 0.52 | 0.48 | 01-NOV-06:49 | 3128.76 | 22.27 | 80.67 | 269.17 | 1676.11 | 22.92 | 87.17 | 244.50 |
December | 265.67 | 0.53 | 0.48 | 01-DEC-07:49 | 3471.02 | 23.75 | 95.67 | 251.00 | 2020.66 | 24.06 | 90.00 | 216.50 |
Annual Sum or Average | 4149.83 | 0.51 | 4111.43 | 22.32 | 1241.67 | 3934.17 | 2142.44 | 23.03 | 1092.17 | 3631.50 | ||
Minimum of Months | 265.67 | 0.50 | 0.48 | 2975.87 | 20.94 | 80.67 | 251.00 | 1668.71 | 22.04 | 68.33 | 216.50 | |
Maximum of Months | 412.83 | 0.53 | 0.48 | 5394.08 | 23.75 | 118.83 | 395.00 | 2445.75 | 24.06 | 114.17 | 362.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.54 | 0.48 | 01-JAN-09:20 | 709.11 | 15.90 | 0.00 | 251.17 | 455.73 | 18.55 | 0.00 | 200.83 |
February | 282.00 | 0.52 | 0.48 | 01-FEB-08:20 | 833.23 | 16.71 | 0.00 | 256.83 | 550.65 | 19.29 | 10.50 | 217.83 |
March | 351.33 | 0.51 | 0.48 | 01-MAR-07:30 | 991.59 | 17.43 | 0.00 | 323.67 | 622.71 | 19.76 | 60.67 | 280.83 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:19 | 1247.62 | 18.95 | 0.00 | 363.00 | 795.98 | 21.14 | 157.67 | 344.83 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:19 | 1454.60 | 19.06 | 21.83 | 391.17 | 848.15 | 21.33 | 164.00 | 361.67 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-05:40 | 1492.35 | 20.19 | 54.17 | 404.33 | 826.72 | 21.97 | 171.17 | 384.00 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:49 | 1478.63 | 20.29 | 46.83 | 396.83 | 869.99 | 21.97 | 192.67 | 374.83 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1323.34 | 18.99 | 6.17 | 384.50 | 842.02 | 21.21 | 199.33 | 369.83 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:40 | 1047.46 | 17.96 | 0.00 | 330.67 | 673.53 | 20.28 | 92.00 | 297.83 |
October | 329.00 | 0.54 | 0.48 | 01-OCT-07:30 | 759.12 | 16.25 | 0.00 | 291.50 | 519.65 | 18.81 | 6.67 | 248.33 |
November | 284.17 | 0.53 | 0.48 | 01-NOV-07:30 | 750.70 | 16.55 | 0.00 | 258.17 | 500.58 | 19.21 | 1.17 | 217.33 |
December | 265.67 | 0.56 | 0.48 | 01-DEC-08:30 | 622.77 | 15.06 | 0.00 | 234.67 | 430.71 | 17.90 | 0.17 | 181.17 |
Annual Sum or Average | 4149.83 | 0.51 | 1101.24 | 18.00 | 129.00 | 3886.50 | 683.19 | 20.30 | 1056.00 | 3479.33 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 622.77 | 15.06 | 0.00 | 234.67 | 430.71 | 17.90 | 0.00 | 181.17 | |
Maximum of Months | 412.83 | 0.56 | 0.48 | 1492.35 | 20.29 | 54.17 | 404.33 | 869.99 | 21.97 | 199.33 | 384.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-09:20 | 2563.20 | 21.73 | 85.33 | 273.50 | 1294.90 | 22.18 | 84.83 | 244.33 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-08:30 | 3759.70 | 23.56 | 93.17 | 267.50 | 2074.19 | 24.06 | 104.83 | 243.50 |
March | 351.33 | 0.51 | 0.48 | 01-MAR-07:40 | 3961.73 | 22.04 | 106.50 | 332.00 | 1519.89 | 21.21 | 78.33 | 304.50 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:00 | 4804.48 | 22.07 | 110.33 | 361.33 | 2017.87 | 21.71 | 56.00 | 345.50 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:49 | 3608.44 | 17.61 | 46.67 | 388.17 | 2033.65 | 18.61 | 0.83 | 369.17 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-06:19 | 3814.89 | 13.93 | 0.00 | 387.33 | 2203.65 | 17.64 | 0.50 | 361.83 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-07:10 | 3675.44 | 15.03 | 3.67 | 388.67 | 2022.46 | 18.41 | 2.17 | 363.83 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-06:49 | 3645.63 | 18.60 | 62.50 | 379.00 | 1921.50 | 19.19 | 13.67 | 357.50 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:00 | 4096.52 | 22.07 | 107.83 | 335.83 | 1617.76 | 21.58 | 73.00 | 314.83 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-07:30 | 3616.66 | 20.92 | 86.17 | 306.67 | 1922.20 | 22.69 | 85.33 | 284.50 |
November | 284.17 | 0.50 | 0.48 | 01-NOV-07:30 | 3651.78 | 24.45 | 105.00 | 277.50 | 1459.49 | 23.14 | 83.17 | 255.50 |
December | 265.67 | 0.52 | 0.48 | 01-DEC-08:30 | 3365.21 | 24.82 | 106.17 | 254.50 | 1819.14 | 24.68 | 92.83 | 231.17 |
Annual Sum or Average | 4149.83 | 0.51 | 3743.63 | 20.16 | 913.33 | 3952.00 | 1844.68 | 20.97 | 675.50 | 3676.17 | ||
Minimum of Months | 265.67 | 0.50 | 0.48 | 2563.20 | 13.93 | 0.00 | 254.50 | 1294.90 | 17.64 | 0.50 | 231.17 | |
Maximum of Months | 412.83 | 0.52 | 0.48 | 4804.48 | 24.82 | 110.33 | 388.67 | 2203.65 | 24.68 | 104.83 | 369.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-07:40 | 11420.41 | 37.48 | 288.83 | 287.50 | 2873.73 | 25.49 | 127.33 | 277.50 |
February | 282.00 | 0.50 | 0.48 | 01-FEB-07:40 | 14033.10 | 37.64 | 272.33 | 276.33 | 2182.10 | 22.60 | 81.50 | 264.67 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:10 | 2472.08 | 14.97 | 10.67 | 331.67 | 1449.87 | 18.33 | 20.67 | 302.00 |
April | 381.83 | 0.51 | 0.48 | 01-APR-06:40 | 1990.47 | 15.66 | 0.00 | 353.50 | 1213.57 | 19.23 | 40.33 | 330.67 |
May | 378.00 | 0.52 | 0.48 | 01-MAY-06:40 | 1532.13 | 15.07 | 0.00 | 375.50 | 954.87 | 18.65 | 9.50 | 342.50 |
June | 412.83 | 0.51 | 0.48 | 01-JUN-06:10 | 1220.94 | 14.05 | 0.00 | 376.00 | 769.95 | 17.73 | 0.00 | 331.33 |
July | 395.33 | 0.51 | 0.48 | 01-JUL-06:00 | 1480.23 | 14.81 | 0.00 | 378.00 | 912.62 | 18.44 | 3.50 | 341.33 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-06:30 | 1850.54 | 15.39 | 0.00 | 374.50 | 1114.41 | 18.95 | 41.33 | 346.50 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:40 | 2435.27 | 15.74 | 16.50 | 331.50 | 1351.30 | 18.51 | 30.33 | 306.00 |
October | 329.00 | 0.51 | 0.48 | 01-OCT-06:00 | 6782.87 | 26.17 | 181.17 | 319.67 | 1824.73 | 18.48 | 26.50 | 305.00 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-06:49 | 12881.14 | 37.99 | 273.17 | 284.50 | 2864.45 | 25.55 | 113.17 | 275.50 |
December | 265.67 | 0.50 | 0.48 | 01-DEC-07:49 | 13053.41 | 40.02 | 263.83 | 269.83 | 4224.50 | 29.15 | 146.67 | 262.17 |
Annual Sum or Average | 4149.83 | 0.51 | 5226.47 | 22.29 | 1306.50 | 3958.50 | 1680.06 | 20.48 | 640.83 | 3685.17 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 1220.94 | 14.05 | 0.00 | 269.83 | 769.95 | 17.73 | 0.00 | 262.17 | |
Maximum of Months | 412.83 | 0.52 | 0.48 | 14033.10 | 40.02 | 288.83 | 378.00 | 4224.50 | 29.15 | 146.67 | 346.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-07:40 | 2744.46 | 20.98 | 86.33 | 264.83 | 1611.46 | 23.76 | 102.00 | 239.67 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-07:30 | 3696.79 | 22.82 | 97.00 | 268.33 | 2044.77 | 23.70 | 107.83 | 244.17 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-06:00 | 3588.94 | 20.31 | 86.50 | 328.17 | 1999.06 | 23.00 | 99.50 | 302.00 |
April | 381.83 | 0.51 | 0.48 | 01-APR-05:00 | 5258.39 | 22.22 | 114.83 | 358.00 | 2016.47 | 21.74 | 55.33 | 341.00 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-05:00 | 4237.71 | 20.88 | 95.50 | 378.00 | 2348.06 | 22.23 | 66.83 | 351.83 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-05:30 | 4070.56 | 20.47 | 111.83 | 394.17 | 2290.08 | 21.87 | 84.33 | 360.00 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-06:40 | 4038.79 | 20.91 | 102.33 | 387.33 | 2139.39 | 22.23 | 81.00 | 358.00 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-05:40 | 4852.18 | 21.83 | 118.83 | 381.33 | 1973.09 | 22.62 | 78.33 | 361.17 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:19 | 4170.70 | 21.72 | 106.83 | 333.67 | 2318.56 | 23.15 | 97.17 | 310.67 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-06:30 | 3617.70 | 20.23 | 82.67 | 304.50 | 2079.76 | 23.16 | 86.83 | 282.83 |
November | 284.17 | 0.52 | 0.48 | 01-NOV-06:49 | 3038.67 | 21.78 | 80.67 | 267.50 | 1603.80 | 22.71 | 81.67 | 242.33 |
December | 265.67 | 0.53 | 0.48 | 01-DEC-07:49 | 3345.84 | 22.78 | 91.83 | 249.00 | 1959.38 | 23.86 | 86.67 | 213.83 |
Annual Sum or Average | 4149.83 | 0.51 | 3962.25 | 21.35 | 1175.17 | 3914.83 | 2051.62 | 22.75 | 1027.50 | 3607.50 | ||
Minimum of Months | 265.67 | 0.50 | 0.48 | 2744.46 | 20.23 | 80.67 | 249.00 | 1603.80 | 21.74 | 55.33 | 213.83 | |
Maximum of Months | 412.83 | 0.53 | 0.48 | 5258.39 | 22.82 | 118.83 | 394.17 | 2348.06 | 23.86 | 107.83 | 361.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.55 | 0.48 | 01-JAN-09:30 | 684.73 | 12.27 | 0.00 | 248.50 | 443.31 | 16.15 | 0.00 | 197.67 |
February | 282.00 | 0.53 | 0.48 | 01-FEB-08:20 | 805.15 | 13.27 | 0.00 | 255.17 | 536.74 | 17.08 | 0.00 | 214.50 |
March | 351.33 | 0.52 | 0.48 | 01-MAR-07:30 | 960.07 | 14.03 | 0.00 | 320.50 | 606.53 | 17.66 | 0.00 | 278.50 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:19 | 1206.29 | 15.85 | 0.00 | 362.17 | 774.72 | 19.42 | 31.50 | 343.83 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:19 | 1409.21 | 15.65 | 0.00 | 389.83 | 823.88 | 19.36 | 53.50 | 359.50 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-05:49 | 1447.89 | 16.94 | 49.67 | 404.00 | 800.85 | 19.88 | 51.67 | 382.67 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:49 | 1432.57 | 17.09 | 35.00 | 395.50 | 844.10 | 19.95 | 51.50 | 373.33 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1300.31 | 15.72 | 0.00 | 385.50 | 818.34 | 19.32 | 41.50 | 368.50 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:40 | 1013.58 | 14.71 | 0.00 | 328.83 | 656.46 | 18.34 | 1.33 | 295.50 |
October | 329.00 | 0.54 | 0.48 | 01-OCT-07:30 | 735.20 | 12.90 | 0.00 | 290.17 | 508.40 | 16.73 | 0.00 | 245.83 |
November | 284.17 | 0.53 | 0.48 | 01-NOV-07:30 | 723.80 | 13.12 | 0.00 | 256.00 | 487.19 | 16.99 | 0.00 | 213.67 |
December | 265.67 | 0.56 | 0.48 | 01-DEC-08:30 | 600.53 | 11.53 | 0.00 | 231.67 | 420.04 | 15.51 | 0.00 | 176.00 |
Annual Sum or Average | 4149.83 | 0.52 | 1067.78 | 14.66 | 84.67 | 3867.83 | 664.47 | 18.23 | 231.00 | 3449.50 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 600.53 | 11.53 | 0.00 | 231.67 | 420.04 | 15.51 | 0.00 | 176.00 | |
Maximum of Months | 412.83 | 0.56 | 0.48 | 1447.89 | 17.09 | 49.67 | 404.00 | 844.10 | 19.95 | 53.50 | 382.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-09:20 | 2493.57 | 21.28 | 84.83 | 272.00 | 1239.50 | 22.08 | 83.83 | 241.83 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-08:30 | 3479.44 | 21.17 | 75.17 | 264.67 | 1999.60 | 23.96 | 103.67 | 240.83 |
March | 351.33 | 0.51 | 0.48 | 01-MAR-07:49 | 3873.66 | 21.55 | 105.33 | 331.17 | 1448.70 | 21.08 | 74.17 | 301.67 |
April | 381.83 | 0.50 | 0.48 | 01-APR-07:10 | 4695.92 | 21.62 | 110.33 | 359.83 | 1930.32 | 21.56 | 54.33 | 343.83 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:49 | 3503.20 | 17.11 | 46.67 | 386.50 | 1955.45 | 18.42 | 0.33 | 366.67 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-06:19 | 3717.98 | 13.39 | 0.00 | 385.50 | 2124.68 | 17.45 | 0.33 | 359.00 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-07:10 | 3573.29 | 14.49 | 3.67 | 386.50 | 1945.40 | 18.23 | 0.83 | 361.67 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-06:49 | 3536.08 | 18.10 | 62.50 | 377.67 | 1839.92 | 19.02 | 11.67 | 356.17 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-07:10 | 4002.20 | 21.64 | 107.83 | 334.00 | 1538.66 | 21.45 | 69.33 | 313.00 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-07:30 | 3522.82 | 20.49 | 86.17 | 305.33 | 1843.19 | 22.58 | 84.00 | 283.17 |
November | 284.17 | 0.51 | 0.48 | 01-NOV-07:30 | 3572.62 | 24.07 | 105.00 | 276.33 | 1394.65 | 23.04 | 82.00 | 253.33 |
December | 265.67 | 0.52 | 0.48 | 01-DEC-08:30 | 3293.46 | 24.46 | 106.17 | 253.50 | 1759.69 | 24.59 | 91.83 | 228.67 |
Annual Sum or Average | 4149.83 | 0.51 | 3636.71 | 19.56 | 893.67 | 3933.00 | 1769.79 | 20.82 | 656.33 | 3649.83 | ||
Minimum of Months | 265.67 | 0.50 | 0.48 | 2493.57 | 13.39 | 0.00 | 253.50 | 1239.50 | 17.45 | 0.33 | 228.67 | |
Maximum of Months | 412.83 | 0.52 | 0.48 | 4695.92 | 24.46 | 110.33 | 386.50 | 2124.68 | 24.59 | 103.67 | 366.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-07:40 | 11420.38 | 37.48 | 288.83 | 287.50 | 2873.63 | 25.49 | 127.33 | 277.50 |
February | 282.00 | 0.50 | 0.48 | 01-FEB-07:40 | 14033.02 | 37.64 | 272.33 | 276.33 | 2181.99 | 22.60 | 81.50 | 264.67 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:10 | 2471.97 | 14.97 | 10.67 | 331.67 | 1449.77 | 18.33 | 20.67 | 302.00 |
April | 381.83 | 0.51 | 0.48 | 01-APR-06:40 | 1990.38 | 15.66 | 0.00 | 353.50 | 1213.50 | 19.23 | 40.33 | 330.67 |
May | 378.00 | 0.52 | 0.48 | 01-MAY-06:40 | 1532.07 | 15.07 | 0.00 | 375.50 | 954.82 | 18.66 | 9.50 | 342.50 |
June | 412.83 | 0.51 | 0.48 | 01-JUN-06:10 | 1220.89 | 14.06 | 0.00 | 376.00 | 769.91 | 17.73 | 0.00 | 331.33 |
July | 395.33 | 0.51 | 0.48 | 01-JUL-06:00 | 1480.17 | 14.81 | 0.00 | 378.00 | 912.57 | 18.44 | 3.67 | 341.33 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-06:30 | 1850.46 | 15.39 | 0.00 | 374.50 | 1114.33 | 18.95 | 41.33 | 346.50 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:40 | 2435.17 | 15.74 | 16.50 | 331.50 | 1351.22 | 18.51 | 30.33 | 306.00 |
October | 329.00 | 0.51 | 0.48 | 01-OCT-06:00 | 6782.79 | 26.17 | 181.17 | 319.67 | 1824.65 | 18.48 | 26.50 | 305.00 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-06:49 | 12881.11 | 37.99 | 273.17 | 284.50 | 2864.35 | 25.56 | 113.17 | 275.50 |
December | 265.67 | 0.50 | 0.48 | 01-DEC-07:49 | 13053.42 | 40.02 | 263.83 | 269.83 | 4224.41 | 29.15 | 146.67 | 262.17 |
Annual Sum or Average | 4149.83 | 0.51 | 5226.40 | 22.29 | 1306.50 | 3958.50 | 1679.98 | 20.48 | 641.00 | 3685.17 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 1220.89 | 14.06 | 0.00 | 269.83 | 769.91 | 17.73 | 0.00 | 262.17 | |
Maximum of Months | 412.83 | 0.52 | 0.48 | 14033.02 | 40.02 | 288.83 | 378.00 | 4224.41 | 29.15 | 146.67 | 346.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-07:40 | 2744.44 | 20.98 | 86.33 | 264.83 | 1611.41 | 23.76 | 102.00 | 239.67 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-07:30 | 3696.76 | 22.82 | 97.00 | 268.33 | 2044.72 | 23.70 | 107.83 | 244.17 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-06:00 | 3588.89 | 20.31 | 86.50 | 328.17 | 1999.00 | 23.00 | 99.50 | 302.00 |
April | 381.83 | 0.51 | 0.48 | 01-APR-05:00 | 5258.35 | 22.22 | 114.83 | 358.00 | 2016.39 | 21.74 | 55.33 | 341.00 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-05:00 | 4237.68 | 20.88 | 95.50 | 378.00 | 2347.99 | 22.23 | 66.83 | 351.83 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-05:30 | 4070.53 | 20.47 | 111.83 | 394.17 | 2290.02 | 21.88 | 84.33 | 360.00 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-06:40 | 4038.75 | 20.91 | 102.33 | 387.33 | 2139.33 | 22.23 | 81.00 | 358.00 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-05:40 | 4852.14 | 21.83 | 118.83 | 381.33 | 1973.02 | 22.62 | 78.33 | 361.17 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:19 | 4170.66 | 21.72 | 106.83 | 333.67 | 2318.49 | 23.15 | 97.17 | 310.67 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-06:30 | 3617.68 | 20.23 | 82.67 | 304.50 | 2079.71 | 23.17 | 86.83 | 282.83 |
November | 284.17 | 0.52 | 0.48 | 01-NOV-06:49 | 3038.66 | 21.78 | 80.67 | 267.50 | 1603.76 | 22.71 | 81.67 | 242.33 |
December | 265.67 | 0.53 | 0.48 | 01-DEC-07:49 | 3345.84 | 22.79 | 91.83 | 249.00 | 1959.35 | 23.86 | 86.67 | 213.83 |
Annual Sum or Average | 4149.83 | 0.51 | 3962.22 | 21.36 | 1175.17 | 3914.83 | 2051.56 | 22.75 | 1027.50 | 3607.50 | ||
Minimum of Months | 265.67 | 0.50 | 0.48 | 2744.44 | 20.23 | 80.67 | 249.00 | 1603.76 | 21.74 | 55.33 | 213.83 | |
Maximum of Months | 412.83 | 0.53 | 0.48 | 5258.35 | 22.82 | 118.83 | 394.17 | 2347.99 | 23.86 | 107.83 | 361.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.55 | 0.48 | 01-JAN-09:30 | 684.72 | 12.27 | 0.00 | 248.50 | 443.29 | 16.15 | 0.00 | 197.67 |
February | 282.00 | 0.53 | 0.48 | 01-FEB-08:20 | 805.14 | 13.27 | 0.00 | 255.17 | 536.71 | 17.08 | 0.00 | 214.50 |
March | 351.33 | 0.52 | 0.48 | 01-MAR-07:30 | 960.04 | 14.03 | 0.00 | 320.50 | 606.49 | 17.66 | 0.00 | 278.50 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:19 | 1206.27 | 15.86 | 0.00 | 362.17 | 774.68 | 19.43 | 31.50 | 343.83 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:19 | 1409.18 | 15.66 | 0.00 | 389.83 | 823.83 | 19.36 | 53.50 | 359.50 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-05:49 | 1447.86 | 16.94 | 49.67 | 404.00 | 800.81 | 19.89 | 51.67 | 382.67 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:49 | 1432.54 | 17.10 | 35.00 | 395.50 | 844.05 | 19.95 | 51.50 | 373.33 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1300.28 | 15.72 | 0.00 | 385.50 | 818.30 | 19.32 | 41.50 | 368.50 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:40 | 1013.56 | 14.72 | 0.00 | 328.83 | 656.42 | 18.34 | 1.33 | 295.50 |
October | 329.00 | 0.54 | 0.48 | 01-OCT-07:30 | 735.19 | 12.90 | 0.00 | 290.17 | 508.38 | 16.73 | 0.00 | 245.83 |
November | 284.17 | 0.53 | 0.48 | 01-NOV-07:30 | 723.80 | 13.12 | 0.00 | 256.00 | 487.17 | 16.99 | 0.00 | 213.67 |
December | 265.67 | 0.56 | 0.48 | 01-DEC-08:30 | 600.53 | 11.53 | 0.00 | 231.67 | 420.02 | 15.52 | 0.00 | 176.00 |
Annual Sum or Average | 4149.83 | 0.52 | 1067.76 | 14.66 | 84.67 | 3867.83 | 664.43 | 18.23 | 231.00 | 3449.50 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 600.53 | 11.53 | 0.00 | 231.67 | 420.02 | 15.52 | 0.00 | 176.00 | |
Maximum of Months | 412.83 | 0.56 | 0.48 | 1447.86 | 17.10 | 49.67 | 404.00 | 844.05 | 19.95 | 53.50 | 382.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-09:20 | 2493.55 | 21.29 | 84.83 | 272.00 | 1239.46 | 22.08 | 83.83 | 241.83 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-08:30 | 3479.42 | 21.17 | 75.17 | 264.67 | 1999.54 | 23.96 | 103.67 | 240.83 |
March | 351.33 | 0.51 | 0.48 | 01-MAR-07:49 | 3873.61 | 21.55 | 105.33 | 331.17 | 1448.64 | 21.09 | 74.17 | 301.67 |
April | 381.83 | 0.50 | 0.48 | 01-APR-07:10 | 4695.88 | 21.62 | 110.33 | 359.83 | 1930.25 | 21.56 | 54.33 | 343.83 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:49 | 3503.16 | 17.11 | 46.67 | 386.50 | 1955.39 | 18.42 | 0.33 | 366.67 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-06:19 | 3717.94 | 13.39 | 0.00 | 385.50 | 2124.62 | 17.46 | 0.33 | 359.00 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-07:10 | 3573.24 | 14.49 | 3.67 | 386.50 | 1945.33 | 18.23 | 0.83 | 361.67 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-06:49 | 3536.02 | 18.11 | 62.50 | 377.67 | 1839.84 | 19.02 | 11.67 | 356.17 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-07:10 | 4002.15 | 21.64 | 107.83 | 334.00 | 1538.59 | 21.45 | 69.50 | 313.00 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-07:30 | 3522.80 | 20.49 | 86.17 | 305.33 | 1843.14 | 22.58 | 84.00 | 283.17 |
November | 284.17 | 0.51 | 0.48 | 01-NOV-07:30 | 3572.61 | 24.07 | 105.00 | 276.33 | 1394.60 | 23.04 | 82.00 | 253.33 |
December | 265.67 | 0.52 | 0.48 | 01-DEC-08:30 | 3293.46 | 24.46 | 106.17 | 253.50 | 1759.66 | 24.59 | 91.83 | 228.67 |
Annual Sum or Average | 4149.83 | 0.51 | 3636.68 | 19.57 | 893.67 | 3933.00 | 1769.73 | 20.82 | 656.50 | 3649.83 | ||
Minimum of Months | 265.67 | 0.50 | 0.48 | 2493.55 | 13.39 | 0.00 | 253.50 | 1239.46 | 17.46 | 0.33 | 228.67 | |
Maximum of Months | 412.83 | 0.52 | 0.48 | 4695.88 | 24.46 | 110.33 | 386.50 | 2124.62 | 24.59 | 103.67 | 366.67 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.193504E+10 | 11912.57 | 19-JAN-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132396E+10 | 11922.22 | 16-FEB-17:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113986E+10 | 11930.94 | 16-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.530850E+09 | 11985.54 | 20-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232881E+09 | 11974.46 | 05-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25160609.85 | 8636.25 | 09-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1010829.92 | 2559.55 | 20-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.431956E+09 | 12051.14 | 13-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.711208E+09 | 11889.37 | 14-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152508E+10 | 11901.47 | 08-DEC-17:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.785702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.193504E+10 | 12051.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.596043E+09 | 8034.46 | 17-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311744E+09 | 8034.46 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 41981266.39 | 7413.74 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4538026.74 | 5672.84 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11817496.91 | 5387.69 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.428940E+09 | 8034.46 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.596043E+09 | 8034.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.127892E+10 | 9768.80 | 12-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.856321E+09 | 9769.10 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203967E+09 | 9745.48 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6070574.98 | 5321.70 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9249275.08 | 5993.02 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 97590210.68 | 9731.06 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105912E+10 | 9772.02 | 27-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.351124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.127892E+10 | 9772.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.684882E+09 | 8034.39 | 17-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.406420E+09 | 8034.39 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118966E+09 | 7827.69 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 381684.25 | 552.77 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10381653.97 | 5667.83 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27995161.90 | 6050.47 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.535253E+09 | 8034.39 | 09-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.684882E+09 | 8034.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 57857157.24 | 22380.00 | 17-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23465827.08 | 22380.00 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 31470836.43 | 22380.00 | 26-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57857157.24 | 22380.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.539969E+09 | 12767.77 | 17-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244282E+09 | 12767.77 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 51441474.98 | 11990.77 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2250595.93 | 3767.04 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23022874.16 | 9925.94 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32050739.28 | 12767.77 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.427316E+09 | 12767.77 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.539969E+09 | 12767.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.828403E+09 | 8477.60 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.386074E+09 | 8477.60 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 60599585.66 | 8477.60 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296965.40 | 1979.77 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 43528790.32 | 6439.29 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106019E+09 | 8477.60 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.739900E+09 | 8477.60 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.828403E+09 | 8477.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108239E+10 | 10484.29 | 17-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.590210E+09 | 10464.01 | 06-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96652501.46 | 10399.98 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1792727.38 | 3550.34 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32103822.30 | 10004.97 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157627E+09 | 10450.56 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110210E+10 | 10494.73 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.306287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110210E+10 | 10494.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.968393E+09 | 8477.52 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.545716E+09 | 8477.52 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157714E+09 | 8477.52 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9918981.14 | 4163.77 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 850588.13 | 1500.03 | 05-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 62002078.03 | 6419.36 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191475E+09 | 8477.52 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.947221E+09 | 8477.52 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.968393E+09 | 8477.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121893E+10 | 35036.69 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.578782E+09 | 35036.69 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 46905421.28 | 35036.69 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14608393.85 | 26888.84 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147726E+09 | 35036.69 | 06-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113443E+10 | 35036.69 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.314138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121893E+10 | 35036.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.148114E+10 | 14497.50 | 20-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.875312E+09 | 14461.58 | 01-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.376670E+09 | 14303.64 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 69818855.04 | 10419.94 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14694244.17 | 8900.50 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 114450.36 | 572.25 | 09-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157234E+09 | 14406.39 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.333798E+09 | 14423.16 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129011E+10 | 14518.30 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.459889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.148114E+10 | 14518.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160735E+10 | 10643.40 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.895049E+09 | 10643.40 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.287149E+09 | 10643.40 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16660641.87 | 6348.95 | 08-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 764428.99 | 719.29 | 06-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156258E+09 | 10643.40 | 25-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.436056E+09 | 10643.40 | 06-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150762E+10 | 10643.40 | 04-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.490690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.160735E+10 | 10643.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.270713E+10 | 12017.99 | 18-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167417E+10 | 11993.30 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.547073E+09 | 11923.20 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 67943181.95 | 10384.16 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3825323.05 | 5375.62 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.231893E+09 | 11926.00 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.829846E+09 | 11951.66 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.281776E+10 | 12018.49 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.887963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.281776E+10 | 12018.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.200560E+10 | 10643.22 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129314E+10 | 10643.22 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.572878E+09 | 10643.22 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96468604.93 | 6609.12 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22873518.34 | 5699.65 | 05-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2101216.28 | 2848.56 | 09-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.256410E+09 | 10643.22 | 26-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.708516E+09 | 10643.22 | 06-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201880E+10 | 10643.22 | 04-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.697678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201880E+10 | 10643.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.275195E+10 | 12239.21 | 21-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141746E+10 | 11041.26 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234798E+09 | 6636.49 | 04-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14727224.53 | 3562.43 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100229E+09 | 6343.35 | 26-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.294370E+09 | 8813.86 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.252463E+10 | 12015.85 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.733817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.275195E+10 | 12239.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.406401E+10 | 13547.29 | 21-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235544E+10 | 12771.52 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.533329E+09 | 7557.45 | 04-MAR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 66688434.73 | 4272.46 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1061580.55 | 613.29 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377617E+09 | 8615.39 | 26-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.811680E+09 | 10716.39 | 27-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.396562E+10 | 13350.25 | 15-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.406401E+10 | 13547.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.475670E+10 | 16043.06 | 21-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.295599E+10 | 15016.26 | 04-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.927449E+09 | 10082.14 | 04-MAR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183742E+09 | 6657.33 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18416000.36 | 2609.46 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.602396E+09 | 10796.52 | 26-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130011E+10 | 13157.95 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.475114E+10 | 16810.60 | 15-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.475670E+10 | 16810.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.144076E+09 | 0.143835E+09 | 8829.30 | 01-JAN-14:32 | 8829.30 | 0.00 |
February | 0.00 | 0.00 | 0.119027E+10 | 0.118843E+10 | 32760.21 | 14-FEB-16:10 | 32760.21 | 0.00 |
March | 0.00 | 0.00 | 0.351248E+10 | 0.350990E+10 | 32771.86 | 08-MAR-16:10 | 32771.86 | 0.00 |
April | 0.00 | 0.00 | 0.154436E+11 | 0.154304E+11 | 54175.21 | 28-APR-15:10 | 54175.21 | 0.00 |
May | 0.00 | 0.00 | 0.295510E+11 | 0.289259E+11 | 62392.29 | 19-MAY-16:00 | 62392.29 | 0.00 |
June | 0.00 | 0.00 | 0.597090E+11 | 0.582671E+11 | 90275.45 | 29-JUN-06:03 | 76932.48 | 0.00 |
July | 0.00 | 0.00 | 0.780542E+11 | 0.699847E+11 | 84970.89 | 31-JUL-15:30 | 77311.53 | 0.00 |
August | 0.00 | 0.00 | 0.765899E+11 | 0.682338E+11 | 92904.14 | 21-AUG-06:03 | 65646.49 | 0.00 |
September | 0.00 | 0.00 | 0.509589E+11 | 0.467985E+11 | 100196.86 | 05-SEP-13:00 | 57846.60 | 0.00 |
October | 0.00 | 0.00 | 0.222264E+11 | 0.211318E+11 | 68213.78 | 02-OCT-15:10 | 64379.50 | 0.00 |
November | 0.00 | 0.00 | 0.880309E+09 | 0.851842E+09 | 17287.71 | 02-NOV-15:00 | 17287.71 | 0.00 |
December | 0.00 | 0.00 | 255765.86 | 255765.86 | 1705.11 | 24-DEC-14:32 | 1705.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.338260E+12 | 0.314467E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 255765.86 | 255765.86 | 1705.11 | 1705.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.780542E+11 | 0.699847E+11 | 100196.86 | 77311.53 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.287961E+09 | 0.287715E+09 | 9215.44 | 05-JAN-14:00 | 9215.44 | 0.00 |
February | 0.00 | 0.00 | 0.120227E+10 | 0.120146E+10 | 30001.94 | 14-FEB-15:30 | 30001.94 | 0.00 |
March | 0.00 | 0.00 | 0.336882E+10 | 0.336618E+10 | 30833.43 | 08-MAR-16:00 | 30833.43 | 0.00 |
April | 0.00 | 0.00 | 0.145722E+11 | 0.145580E+11 | 52569.42 | 13-APR-15:20 | 52569.42 | 0.00 |
May | 0.00 | 0.00 | 0.272904E+11 | 0.267625E+11 | 59187.99 | 19-MAY-15:20 | 59187.99 | 0.00 |
June | 0.00 | 0.00 | 0.540589E+11 | 0.528892E+11 | 79559.83 | 29-JUN-06:03 | 66547.49 | 0.00 |
July | 0.00 | 0.00 | 0.696625E+11 | 0.628126E+11 | 82276.99 | 31-JUL-15:00 | 74957.22 | 0.00 |
August | 0.00 | 0.00 | 0.671558E+11 | 0.602369E+11 | 82607.06 | 14-AUG-06:03 | 36545.75 | 0.00 |
September | 0.00 | 0.00 | 0.433802E+11 | 0.399259E+11 | 88422.12 | 05-SEP-13:00 | 51082.08 | 0.00 |
October | 0.00 | 0.00 | 0.187911E+11 | 0.179197E+11 | 63471.58 | 02-OCT-14:50 | 59802.86 | 0.00 |
November | 0.00 | 0.00 | 0.760015E+09 | 0.720175E+09 | 16964.77 | 02-NOV-15:00 | 16905.97 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.300530E+12 | 0.280680E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.696625E+11 | 0.628126E+11 | 88422.12 | 74957.22 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.131364E+09 | 0.131024E+09 | 6368.22 | 05-JAN-14:00 | 6368.22 | 0.00 |
February | 0.00 | 0.00 | 0.110702E+10 | 0.110577E+10 | 29222.20 | 14-FEB-15:40 | 29222.20 | 0.00 |
March | 0.00 | 0.00 | 0.325293E+10 | 0.324231E+10 | 31712.60 | 08-MAR-16:00 | 31712.60 | 0.00 |
April | 0.00 | 0.00 | 0.150710E+11 | 0.150484E+11 | 59554.61 | 26-APR-15:00 | 59554.61 | 0.00 |
May | 0.00 | 0.00 | 0.291832E+11 | 0.285503E+11 | 68808.90 | 19-MAY-15:20 | 68808.90 | 0.00 |
June | 0.00 | 0.00 | 0.592037E+11 | 0.578419E+11 | 88774.56 | 29-JUN-14:30 | 88774.56 | 0.00 |
July | 0.00 | 0.00 | 0.759540E+11 | 0.688361E+11 | 91440.09 | 23-JUL-15:11 | 91440.09 | 0.00 |
August | 0.00 | 0.00 | 0.722681E+11 | 0.652257E+11 | 91208.55 | 20-AUG-15:31 | 91208.55 | 0.00 |
September | 0.00 | 0.00 | 0.456330E+11 | 0.420930E+11 | 91530.23 | 05-SEP-13:30 | 56346.53 | 0.00 |
October | 0.00 | 0.00 | 0.186898E+11 | 0.178169E+11 | 68952.51 | 02-OCT-14:30 | 65001.91 | 0.00 |
November | 0.00 | 0.00 | 0.525626E+09 | 0.478430E+09 | 13687.33 | 02-NOV-15:00 | 13435.95 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.321020E+12 | 0.300370E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.759540E+11 | 0.688361E+11 | 91530.23 | 91440.09 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1835.60 | 6411.55 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1858.77 | 6432.66 | 01-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1935.26 | 6363.63 | 02-MAR-12:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1719.51 | 6084.71 | 04-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1667.97 | 5713.46 | 01-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1597.87 | 5296.21 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1399.55 | 4967.05 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1522.02 | 4881.18 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1467.16 | 5112.39 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1555.70 | 5507.01 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1690.39 | 5918.81 | 30-NOV-12:07 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1721.65 | 6246.71 | 28-DEC-12:06 |
Annual Sum or Average | 0.00 | 1663.19 | ||||
Minimum of Months | 0.00 | 0.00 | 1399.55 | 4881.18 | ||
Maximum of Months | 0.00 | 0.00 | 1935.26 | 6432.66 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205935E+10 | 0.36 | 3583.98 | 26-JAN-16:30 | 0.94 |
February | 0.199362E+10 | 0.37 | 5053.19 | 15-FEB-16:30 | 1.14 |
March | 0.273925E+10 | 0.40 | 4186.33 | 08-MAR-16:30 | 1.02 |
April | 0.368851E+10 | 0.45 | 7221.91 | 28-APR-15:10 | 1.41 |
May | 0.470902E+10 | 0.51 | 8531.88 | 15-MAY-16:00 | 1.56 |
June | 0.693860E+10 | 0.64 | 13381.50 | 26-JUN-12:10 | 2.06 |
July | 0.788705E+10 | 0.66 | 14341.17 | 05-JUL-12:10 | 2.15 |
August | 0.789583E+10 | 0.67 | 14341.17 | 21-AUG-06:03 | 2.15 |
September | 0.579568E+10 | 0.57 | 10294.56 | 05-SEP-15:30 | 1.74 |
October | 0.427494E+10 | 0.48 | 8965.28 | 02-OCT-08:00 | 1.60 |
November | 0.279025E+10 | 0.40 | 5691.89 | 01-NOV-16:00 | 1.22 |
December | 0.208484E+10 | 0.36 | 3381.32 | 29-DEC-16:10 | 0.91 |
Annual Sum or Average | 0.528569E+11 | 0.49 | |||
Minimum of Months | 0.199362E+10 | 0.36 | 3381.32 | 0.91 | |
Maximum of Months | 0.789583E+10 | 0.67 | 14341.17 | 2.15 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.175736E+10 | 0.35 | 3265.59 | 17-JAN-07:01 | 0.95 |
February | 0.170030E+10 | 0.35 | 4642.61 | 15-FEB-16:30 | 1.16 |
March | 0.227730E+10 | 0.39 | 4280.04 | 24-MAR-15:30 | 1.11 |
April | 0.334322E+10 | 0.46 | 7752.10 | 28-APR-14:30 | 1.58 |
May | 0.421858E+10 | 0.51 | 8856.13 | 30-MAY-14:30 | 1.71 |
June | 0.623829E+10 | 0.63 | 12116.32 | 26-JUN-15:30 | 2.07 |
July | 0.713106E+10 | 0.66 | 12577.54 | 31-JUL-15:20 | 2.12 |
August | 0.721006E+10 | 0.67 | 12858.20 | 07-AUG-15:30 | 2.15 |
September | 0.477381E+10 | 0.54 | 10353.25 | 13-SEP-16:00 | 1.87 |
October | 0.327567E+10 | 0.44 | 8541.29 | 02-OCT-15:50 | 1.66 |
November | 0.203300E+10 | 0.37 | 4704.08 | 02-NOV-16:00 | 1.16 |
December | 0.177137E+10 | 0.34 | 2808.32 | 26-DEC-07:02 | 0.87 |
Annual Sum or Average | 0.457300E+11 | 0.48 | |||
Minimum of Months | 0.170030E+10 | 0.34 | 2808.32 | 0.87 | |
Maximum of Months | 0.721006E+10 | 0.67 | 12858.20 | 2.15 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.184357E+10 | 0.36 | 3208.10 | 02-JAN-06:01 | 0.87 |
February | 0.172714E+10 | 0.36 | 3920.07 | 15-FEB-16:10 | 0.97 |
March | 0.215703E+10 | 0.38 | 3828.41 | 24-MAR-15:30 | 0.95 |
April | 0.303627E+10 | 0.41 | 7453.01 | 13-APR-15:30 | 1.41 |
May | 0.387677E+10 | 0.46 | 8896.74 | 30-MAY-14:30 | 1.56 |
June | 0.592617E+10 | 0.57 | 12583.99 | 29-JUN-14:30 | 1.93 |
July | 0.680452E+10 | 0.60 | 12401.56 | 31-JUL-15:20 | 1.91 |
August | 0.681650E+10 | 0.60 | 13246.04 | 07-AUG-15:20 | 1.99 |
September | 0.438285E+10 | 0.48 | 9767.57 | 01-SEP-15:40 | 1.64 |
October | 0.291157E+10 | 0.40 | 8268.97 | 02-OCT-15:40 | 1.48 |
November | 0.188884E+10 | 0.35 | 3741.86 | 02-NOV-15:40 | 0.94 |
December | 0.182886E+10 | 0.35 | 3208.10 | 04-DEC-06:01 | 0.87 |
Annual Sum or Average | 0.432001E+11 | 0.44 | |||
Minimum of Months | 0.172714E+10 | 0.35 | 3208.10 | 0.87 | |
Maximum of Months | 0.681650E+10 | 0.60 | 13246.04 | 1.99 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 56.51 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 56.49 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:02 | 2.06 | 2.06 | 56.10 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 55.46 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.59 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.35 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 56.26 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 56.16 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 56.24 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.36 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.34 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 56.83 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.46 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.36 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.22 | 57.22 | 1835.60 | 6411.55 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.24 | 57.24 | 1858.77 | 6432.66 | 01-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.57 | 56.57 | 1935.26 | 6363.63 | 02-MAR-12:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.03 | 56.03 | 1719.51 | 6084.71 | 04-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.46 | 57.46 | 1667.97 | 5713.46 | 01-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.62 | 57.62 | 1597.87 | 5296.21 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.74 | 56.74 | 1399.55 | 4967.05 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.43 | 56.43 | 1522.02 | 4881.18 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.53 | 56.53 | 1467.16 | 5112.39 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.65 | 56.65 | 1555.70 | 5507.01 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.72 | 56.72 | 1690.39 | 5918.81 | 30-NOV-12:07 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.34 | 57.34 | 1721.65 | 6246.71 | 28-DEC-12:06 |
Annual Sum or Average | 0.00 | 1663.19 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.03 | 56.03 | 1399.55 | 4881.18 | ||
Maximum of Months | 0.00 | 0.00 | 57.62 | 57.62 | 1935.26 | 6432.66 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.659578E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.519557E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.518261E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.805561E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.123281E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.232316E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.289097E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.276833E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.184233E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.101724E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.388384E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.563331E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.155295E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.388384E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.289097E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.531597E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.379883E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.354057E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.696283E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.110234E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.209672E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.259117E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.246152E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.155606E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.805979E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.273273E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.501937E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.133508E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.273273E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.259117E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.109016E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.733240E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.486480E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.704461E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.112541E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.222120E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.274655E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.257197E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.158378E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.837475E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.449371E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.105976E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.156098E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.449371E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.274655E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.205935E+10 | 0.144076E+09 | 0.724685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199362E+10 | 0.119027E+10 | 0.431590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.273925E+10 | 0.351248E+10 | 0.173957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.368851E+10 | 0.154436E+11 | 0.552029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.470902E+10 | 0.295510E+11 | 0.232881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.693860E+10 | 0.597090E+11 | 25160609.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.788705E+10 | 0.780542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.789583E+10 | 0.765899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.579568E+10 | 0.509589E+11 | 1010829.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.427494E+10 | 0.222264E+11 | 0.556354E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279025E+10 | 0.880309E+09 | 0.114298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208484E+10 | 255765.86 | 0.607303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.528569E+11 | 0.338260E+12 | 0.218858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.199362E+10 | 255765.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.789583E+10 | 0.780542E+11 | 0.724685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.175736E+10 | 0.287961E+09 | 0.754102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170030E+10 | 0.120227E+10 | 0.414519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227730E+10 | 0.336882E+10 | 0.899736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.334322E+10 | 0.145722E+11 | 80947704.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.421858E+10 | 0.272904E+11 | 1912168.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.623829E+10 | 0.540589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.713106E+10 | 0.696625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.721006E+10 | 0.671558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.477381E+10 | 0.433802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.327567E+10 | 0.187911E+11 | 0.538275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203300E+10 | 0.760015E+09 | 0.129885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177137E+10 | 0.00 | 0.721362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.457300E+11 | 0.300530E+12 | 0.217195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.170030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.721006E+10 | 0.696625E+11 | 0.754102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.184357E+10 | 0.131364E+09 | 0.137768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172714E+10 | 0.110702E+10 | 0.827245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.215703E+10 | 0.325293E+10 | 0.275812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.303627E+10 | 0.150710E+11 | 0.434633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.387677E+10 | 0.291832E+11 | 60573514.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.592617E+10 | 0.592037E+11 | 2215666.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.680452E+10 | 0.759540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.681650E+10 | 0.722681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.438285E+10 | 0.456330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.291157E+10 | 0.186898E+11 | 0.141880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188884E+10 | 0.525626E+09 | 0.375605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182886E+10 | 0.00 | 0.135198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432001E+11 | 0.321020E+12 | 0.439995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.172714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.681650E+10 | 0.759540E+11 | 0.137768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.205935E+10 | 0.00 | 0.00 | 0.00 | 41543348.45 | 0.449489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199362E+10 | 0.00 | 0.00 | 0.00 | 0.303504E+09 | 0.289845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.273925E+10 | 0.00 | 0.00 | 0.00 | 0.938593E+09 | 0.150478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.368851E+10 | 0.00 | 0.00 | 0.00 | 0.382980E+10 | 0.537302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.470902E+10 | 0.00 | 0.00 | 0.00 | 0.738616E+10 | 0.232881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.693860E+10 | 0.00 | 0.00 | 0.00 | 0.162679E+11 | 25160609.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.788705E+10 | 0.00 | 0.00 | 0.00 | 0.210226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.789583E+10 | 0.00 | 0.00 | 0.00 | 0.197874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.579568E+10 | 0.00 | 0.00 | 0.00 | 0.126266E+11 | 1010829.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.427494E+10 | 0.00 | 0.00 | 0.00 | 0.544138E+10 | 0.456125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279025E+10 | 0.00 | 0.00 | 0.00 | 0.244976E+09 | 0.848611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208484E+10 | 0.00 | 0.00 | 0.00 | 74749.28 | 0.354840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.528569E+11 | 0.00 | 0.00 | 0.00 | 0.878905E+11 | 0.145476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.199362E+10 | 0.00 | 0.00 | 0.00 | 74749.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.789583E+10 | 0.00 | 0.00 | 0.00 | 0.210226E+11 | 0.449489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.175736E+10 | 0.00 | 0.00 | 0.00 | 81600427.77 | 0.347701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170030E+10 | 0.00 | 0.00 | 0.00 | 0.308782E+09 | 0.178975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227730E+10 | 0.00 | 0.00 | 0.00 | 0.896859E+09 | 0.366408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.334322E+10 | 0.00 | 0.00 | 0.00 | 0.360535E+10 | 14259269.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.421858E+10 | 0.00 | 0.00 | 0.00 | 0.680393E+10 | 850588.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.623829E+10 | 0.00 | 0.00 | 0.00 | 0.147289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.713106E+10 | 0.00 | 0.00 | 0.00 | 0.187807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.721006E+10 | 0.00 | 0.00 | 0.00 | 0.174051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.477381E+10 | 0.00 | 0.00 | 0.00 | 0.107868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.327567E+10 | 0.00 | 0.00 | 0.00 | 0.462346E+10 | 0.160658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203300E+10 | 0.00 | 0.00 | 0.00 | 0.212559E+09 | 0.487172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.457300E+11 | 0.00 | 0.00 | 0.00 | 0.782341E+11 | 0.954411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.170030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.721006E+10 | 0.00 | 0.00 | 0.00 | 0.187807E+11 | 0.347701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.184357E+10 | 0.00 | 0.00 | 0.00 | 37893892.74 | 0.902013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172714E+10 | 0.00 | 0.00 | 0.00 | 0.288800E+09 | 0.531646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.215703E+10 | 0.00 | 0.00 | 0.00 | 0.877096E+09 | 0.183068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.303627E+10 | 0.00 | 0.00 | 0.00 | 0.375745E+10 | 0.250891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.387677E+10 | 0.00 | 0.00 | 0.00 | 0.733519E+10 | 42157514.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.592617E+10 | 0.00 | 0.00 | 0.00 | 0.162836E+11 | 2215666.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.680452E+10 | 0.00 | 0.00 | 0.00 | 0.206609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.681650E+10 | 0.00 | 0.00 | 0.00 | 0.189032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.438285E+10 | 0.00 | 0.00 | 0.00 | 0.114549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.291157E+10 | 0.00 | 0.00 | 0.00 | 0.464678E+10 | 0.816404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188884E+10 | 0.00 | 0.00 | 0.00 | 0.148930E+09 | 0.245594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432001E+11 | 0.00 | 0.00 | 0.00 | 0.843948E+11 | 0.285036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.172714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.681650E+10 | 0.00 | 0.00 | 0.00 | 0.206609E+11 | 0.902013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.275534E+10 | 0.00 | 0.00 | 28477049.82 | 0.00 | 0.00 | 0.149605E+11 | 0.00 | 0.49 |
February | 0.155688E+10 | 0.00 | 0.00 | 30769103.15 | 0.00 | 0.00 | 0.151318E+11 | 0.00 | 0.56 |
March | 0.106893E+10 | 0.00 | 0.00 | 42263120.48 | 0.00 | 0.00 | 0.211308E+11 | 0.00 | 0.92 |
April | 0.107374E+10 | 1107465.64 | 0.00 | 41691797.42 | 0.00 | 0.00 | 0.178689E+11 | 0.00 | 1.15 |
May | 0.703348E+09 | 23060724.55 | 0.00 | 46449122.82 | 7126961.22 | 0.00 | 0.155169E+11 | 0.00 | 1.20 |
June | 0.348422E+09 | 0.585001E+09 | 0.00 | 29125980.19 | 30149192.39 | 0.00 | 0.602473E+10 | 0.00 | 0.84 |
July | 0.100413E+09 | 0.195446E+10 | 0.00 | 9266204.59 | 0.265336E+09 | 0.00 | 0.642419E+09 | 0.00 | 0.62 |
August | 0.164377E+09 | 0.128036E+10 | 0.00 | 22015845.82 | 0.141629E+09 | 0.00 | 0.307121E+10 | 0.00 | 0.88 |
September | 0.381291E+09 | 0.263562E+09 | 0.00 | 41904618.87 | 55995852.20 | 0.00 | 0.856206E+10 | 0.00 | 1.08 |
October | 0.131250E+10 | 9613072.81 | 0.00 | 47433363.09 | 2150824.12 | 0.00 | 0.180668E+11 | 0.00 | 1.08 |
November | 0.137685E+10 | 0.00 | 0.00 | 41523172.31 | 0.00 | 0.00 | 0.213167E+11 | 0.00 | 0.79 |
December | 0.214719E+10 | 0.00 | 0.00 | 32264482.82 | 0.00 | 0.00 | 0.158621E+11 | 0.00 | 0.43 |
Annual Sum or Average | 0.129893E+11 | 0.411717E+10 | 0.00 | 0.413184E+09 | 0.502388E+09 | 0.00 | 0.158155E+12 | 0.00 | 0.84 |
Minimum of Months | 0.100413E+09 | 0.00 | 0.00 | 9266204.59 | 0.00 | 0.00 | 0.642419E+09 | 0.00 | 0.43 |
Maximum of Months | 0.275534E+10 | 0.195446E+10 | 0.00 | 47433363.09 | 0.265336E+09 | 0.00 | 0.213167E+11 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.920672E+10 | 0.00 | 0.00 | 2569898.22 | 0.00 | 29072005.19 | 0.274853E+10 | 0.00 | 0.33 |
February | 0.675601E+10 | 0.00 | 0.00 | 4740800.18 | 0.00 | 20644009.75 | 0.387827E+10 | 0.00 | 0.36 |
March | 0.422611E+10 | 0.00 | 0.00 | 15063993.99 | 0.00 | 0.00 | 0.923830E+10 | 0.00 | 0.56 |
April | 0.213052E+10 | 1084794.56 | 0.00 | 22488130.42 | 316796.62 | 0.00 | 0.100781E+11 | 0.00 | 0.76 |
May | 0.136596E+10 | 17939575.45 | 0.00 | 28734329.74 | 5553068.25 | 0.00 | 0.947307E+10 | 0.00 | 0.82 |
June | 0.536637E+09 | 0.431804E+09 | 0.00 | 20192300.65 | 19746471.92 | 0.00 | 0.392533E+10 | 0.00 | 0.61 |
July | 0.126771E+09 | 0.146655E+10 | 0.00 | 6998514.45 | 0.180624E+09 | 0.00 | 0.488822E+09 | 0.00 | 0.48 |
August | 0.265379E+09 | 0.899696E+09 | 0.00 | 15856694.50 | 70928179.77 | 0.00 | 0.207295E+10 | 0.00 | 0.65 |
September | 0.631577E+09 | 0.198606E+09 | 0.00 | 26980110.53 | 36568256.24 | 0.00 | 0.545533E+10 | 0.00 | 0.75 |
October | 0.249050E+10 | 6554254.13 | 0.00 | 23540602.24 | 1144952.75 | 0.00 | 0.926547E+10 | 0.00 | 0.69 |
November | 0.487374E+10 | 0.00 | 0.00 | 12201928.36 | 0.00 | 0.00 | 0.812220E+10 | 0.00 | 0.46 |
December | 0.906041E+10 | 0.00 | 0.00 | 2656505.92 | 0.00 | 17362282.09 | 0.276370E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.416703E+11 | 0.302224E+10 | 0.00 | 0.182024E+09 | 0.314881E+09 | 67078297.03 | 0.675101E+11 | 0.00 | 0.56 |
Minimum of Months | 0.126771E+09 | 0.00 | 0.00 | 2569898.22 | 0.00 | 0.00 | 0.488822E+09 | 0.00 | 0.29 |
Maximum of Months | 0.920672E+10 | 0.146655E+10 | 0.00 | 28734329.74 | 0.180624E+09 | 29072005.19 | 0.100781E+11 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.948253E+10 | 0.00 | 0.00 | 858262.30 | 0.00 | 0.570535E+09 | 0.115627E+10 | 0.00 | 0.32 |
February | 0.771549E+10 | 0.00 | 0.00 | 2104957.88 | 0.00 | 0.235427E+09 | 0.215066E+10 | 0.00 | 0.35 |
March | 0.592820E+10 | 0.00 | 0.00 | 8852116.99 | 0.00 | 17953695.59 | 0.669344E+10 | 0.00 | 0.53 |
April | 0.275345E+10 | 0.00 | 0.00 | 18684879.74 | 0.00 | 0.00 | 0.901281E+10 | 0.00 | 0.77 |
May | 0.184363E+10 | 7680142.07 | 0.00 | 25481864.39 | 7879187.14 | 0.00 | 0.871680E+10 | 0.00 | 0.85 |
June | 0.741423E+09 | 0.321843E+09 | 0.00 | 21619419.46 | 25427125.87 | 0.00 | 0.347385E+10 | 0.00 | 0.61 |
July | 0.142341E+09 | 0.130318E+10 | 0.00 | 6134770.30 | 0.240484E+09 | 0.00 | 0.253871E+09 | 0.00 | 0.48 |
August | 0.368603E+09 | 0.681533E+09 | 0.00 | 17945103.98 | 95493071.96 | 0.00 | 0.160541E+10 | 0.00 | 0.66 |
September | 0.986060E+09 | 0.119448E+09 | 0.00 | 24405925.19 | 22753382.63 | 0.00 | 0.433893E+10 | 0.00 | 0.77 |
October | 0.361710E+10 | 7623893.51 | 0.00 | 16459632.72 | 0.00 | 6166302.72 | 0.662739E+10 | 0.00 | 0.65 |
November | 0.645077E+10 | 0.00 | 0.00 | 5533942.88 | 0.00 | 62044022.75 | 0.491322E+10 | 0.00 | 0.41 |
December | 0.941316E+10 | 0.00 | 0.00 | 599287.10 | 0.00 | 0.588772E+09 | 0.954965E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.494427E+11 | 0.244131E+10 | 0.00 | 0.148680E+09 | 0.392036E+09 | 0.148090E+10 | 0.498976E+11 | 0.00 | 0.56 |
Minimum of Months | 0.142341E+09 | 0.00 | 0.00 | 599287.10 | 0.00 | 0.00 | 0.253871E+09 | 0.00 | 0.27 |
Maximum of Months | 0.948253E+10 | 0.130318E+10 | 0.00 | 25481864.39 | 0.240484E+09 | 0.588772E+09 | 0.901281E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135276E+10 | 0.00 | 0.00 | 0.35 |
February | 0.147833E+10 | 0.00 | 0.00 | 59287.41 | 0.00 | 0.804793E+09 | 54757402.66 | 0.00 | 0.37 |
March | 0.189606E+10 | 0.00 | 0.00 | 688654.76 | 0.00 | 0.249818E+09 | 0.590010E+09 | 0.00 | 0.53 |
April | 0.107418E+10 | 0.00 | 0.00 | 3307323.79 | 0.00 | 36096722.46 | 0.140987E+10 | 0.00 | 0.84 |
May | 0.653458E+09 | 3269913.39 | 0.00 | 5751954.54 | 1646977.22 | 704415.38 | 0.170027E+10 | 0.00 | 0.98 |
June | 0.237628E+09 | 0.117169E+09 | 0.00 | 6338023.93 | 5652171.59 | 0.00 | 0.803677E+09 | 0.00 | 0.82 |
July | 38449605.16 | 0.437552E+09 | 0.00 | 1785120.22 | 51771072.99 | 0.00 | 63070272.78 | 0.00 | 0.66 |
August | 0.113444E+09 | 0.212372E+09 | 0.00 | 4732124.27 | 21837721.13 | 0.00 | 0.354779E+09 | 0.00 | 0.83 |
September | 0.340628E+09 | 34642962.52 | 0.00 | 5519001.09 | 4876970.72 | 0.00 | 0.834203E+09 | 0.00 | 0.85 |
October | 0.131800E+10 | 2287518.66 | 0.00 | 2354116.49 | 4729.67 | 0.126798E+09 | 0.678466E+09 | 0.00 | 0.65 |
November | 0.198067E+10 | 0.00 | 0.00 | 112311.17 | 0.00 | 0.374530E+09 | 0.151258E+09 | 0.00 | 0.42 |
December | 0.112113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148083E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.115514E+11 | 0.807293E+09 | 0.00 | 30647917.66 | 85789643.33 | 0.442634E+10 | 0.664035E+10 | 0.00 | 0.64 |
Minimum of Months | 38449605.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.198067E+10 | 0.437552E+09 | 0.00 | 6338023.93 | 51771072.99 | 0.148083E+10 | 0.170027E+10 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.178646E+10 | 0.00 | 0.00 | 70899.68 | 0.00 | 0.966917E+09 | 65291357.59 | 0.00 | 0.60 |
February | 0.169401E+10 | 0.00 | 0.00 | 541419.27 | 0.00 | 0.489358E+09 | 0.375306E+09 | 0.00 | 0.65 |
March | 0.150492E+10 | 0.00 | 0.00 | 3028692.38 | 0.00 | 0.121519E+09 | 0.181660E+10 | 0.00 | 1.04 |
April | 0.672308E+09 | 0.00 | 0.00 | 7292360.80 | 0.00 | 4715417.60 | 0.344891E+10 | 0.00 | 1.87 |
May | 0.433331E+09 | 3026735.04 | 0.00 | 9861729.35 | 1656928.75 | 0.00 | 0.319267E+10 | 0.00 | 2.07 |
June | 0.193832E+09 | 0.110661E+09 | 0.00 | 9011421.20 | 2940178.31 | 0.00 | 0.122791E+10 | 0.00 | 1.66 |
July | 35825929.43 | 0.530065E+09 | 0.00 | 2147549.56 | 26359575.91 | 0.00 | 81693711.64 | 0.00 | 1.26 |
August | 96798832.86 | 0.251871E+09 | 0.00 | 6465999.42 | 18019781.30 | 0.00 | 0.541105E+09 | 0.00 | 1.69 |
September | 0.294746E+09 | 29402986.55 | 0.00 | 7730562.80 | 4646777.47 | 0.00 | 0.143175E+10 | 0.00 | 1.86 |
October | 0.986372E+09 | 1429555.87 | 0.00 | 4675858.26 | 348469.85 | 91057885.26 | 0.180257E+10 | 0.00 | 1.33 |
November | 0.197507E+10 | 0.00 | 0.00 | 798263.18 | 0.00 | 0.189184E+09 | 0.627314E+09 | 0.00 | 0.74 |
December | 0.186121E+10 | 0.00 | 0.00 | 25084.42 | 0.00 | 0.865711E+09 | 28521976.50 | 0.00 | 0.52 |
Annual Sum or Average | 0.115349E+11 | 0.926456E+09 | 0.00 | 51649840.31 | 53971711.59 | 0.272846E+10 | 0.146396E+11 | 0.00 | 1.28 |
Minimum of Months | 35825929.43 | 0.00 | 0.00 | 25084.42 | 0.00 | 0.00 | 28521976.50 | 0.00 | 0.52 |
Maximum of Months | 0.197507E+10 | 0.530065E+09 | 0.00 | 9861729.35 | 26359575.91 | 0.966917E+09 | 0.344891E+10 | 0.00 | 2.07 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117629E+10 | 0.00 | 0.00 | 7759006.38 | 0.00 | 0.670587E+09 | 0.398975E+10 | 0.00 | 0.88 |
February | 0.975890E+09 | 0.00 | 0.00 | 8838418.91 | 0.00 | 0.373202E+09 | 0.435909E+10 | 0.00 | 1.01 |
March | 0.121699E+10 | 0.00 | 0.00 | 8367584.27 | 0.00 | 0.196933E+09 | 0.476749E+10 | 0.00 | 1.29 |
April | 0.893254E+09 | 0.00 | 0.00 | 8574606.37 | 0.00 | 34291821.45 | 0.379206E+10 | 0.00 | 1.54 |
May | 0.777108E+09 | 4874952.38 | 0.00 | 7744267.14 | 1842439.11 | 4168455.08 | 0.230207E+10 | 0.00 | 1.26 |
June | 0.359400E+09 | 0.113774E+09 | 0.00 | 6163116.87 | 8555913.61 | 0.00 | 0.774246E+09 | 0.00 | 0.85 |
July | 53945490.35 | 0.481184E+09 | 0.00 | 1725632.43 | 62638422.90 | 0.00 | 54408396.62 | 0.00 | 0.70 |
August | 0.153283E+09 | 0.293012E+09 | 0.00 | 6317717.02 | 22438046.81 | 0.00 | 0.436254E+09 | 0.00 | 1.07 |
September | 0.352236E+09 | 70106774.59 | 0.00 | 13016661.56 | 3511920.31 | 0.00 | 0.160037E+10 | 0.00 | 1.55 |
October | 0.742553E+09 | 3462537.71 | 0.00 | 15866731.63 | 0.00 | 91138753.22 | 0.499194E+10 | 0.00 | 1.80 |
November | 0.102306E+10 | 0.00 | 0.00 | 10345185.86 | 0.00 | 0.148259E+09 | 0.593163E+10 | 0.00 | 1.19 |
December | 0.113145E+10 | 0.00 | 0.00 | 9700486.45 | 0.00 | 0.546991E+09 | 0.443965E+10 | 0.00 | 0.74 |
Annual Sum or Average | 0.885546E+10 | 0.966415E+09 | 0.00 | 0.104419E+09 | 98986742.73 | 0.206557E+10 | 0.374390E+11 | 0.00 | 1.16 |
Minimum of Months | 53945490.35 | 0.00 | 0.00 | 1725632.43 | 0.00 | 0.00 | 54408396.62 | 0.00 | 0.70 |
Maximum of Months | 0.121699E+10 | 0.481184E+09 | 0.00 | 15866731.63 | 62638422.90 | 0.670587E+09 | 0.593163E+10 | 0.00 | 1.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.151731E+10 | 0.00 | 0.00 | 657881.48 | 0.00 | 0.124851E+10 | 0.536045E+09 | 0.00 | 0.71 |
February | 0.151135E+10 | 0.00 | 0.00 | 1571203.71 | 0.00 | 0.730561E+09 | 0.980600E+09 | 0.00 | 0.86 |
March | 0.202317E+10 | 0.00 | 0.00 | 2907791.54 | 0.00 | 0.296273E+09 | 0.169659E+10 | 0.00 | 1.29 |
April | 0.131605E+10 | 0.00 | 0.00 | 6103674.67 | 0.00 | 45618638.14 | 0.213133E+10 | 0.00 | 1.86 |
May | 0.933028E+09 | 5631601.81 | 0.00 | 6941172.88 | 1675309.89 | 5789152.25 | 0.178763E+10 | 0.00 | 1.80 |
June | 0.409943E+09 | 0.112452E+09 | 0.00 | 5778275.63 | 8585284.26 | 458417.81 | 0.591820E+09 | 0.00 | 1.24 |
July | 57934613.36 | 0.377742E+09 | 0.00 | 1532908.75 | 65516473.38 | 0.00 | 45520976.39 | 0.00 | 0.92 |
August | 0.178826E+09 | 0.202049E+09 | 0.00 | 4323937.80 | 24601756.13 | 0.00 | 0.279334E+09 | 0.00 | 1.24 |
September | 0.494701E+09 | 35777042.62 | 0.00 | 7117721.60 | 5760311.31 | 0.00 | 0.769214E+09 | 0.00 | 1.44 |
October | 0.143621E+10 | 2360974.92 | 0.00 | 4711609.13 | 0.00 | 0.150972E+09 | 0.142483E+10 | 0.00 | 1.45 |
November | 0.200204E+10 | 0.00 | 0.00 | 1377429.45 | 0.00 | 0.363008E+09 | 0.110020E+10 | 0.00 | 0.93 |
December | 0.138830E+10 | 0.00 | 0.00 | 546250.82 | 0.00 | 0.128558E+10 | 0.492613E+09 | 0.00 | 0.59 |
Annual Sum or Average | 0.132689E+11 | 0.736012E+09 | 0.00 | 43569857.47 | 0.106139E+09 | 0.412678E+10 | 0.118357E+11 | 0.00 | 1.19 |
Minimum of Months | 57934613.36 | 0.00 | 0.00 | 546250.82 | 0.00 | 0.00 | 45520976.39 | 0.00 | 0.59 |
Maximum of Months | 0.202317E+10 | 0.377742E+09 | 0.00 | 7117721.60 | 65516473.38 | 0.128558E+10 | 0.213133E+10 | 0.00 | 1.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102217E+10 | 0.00 | 0.00 | 0.32 |
February | 0.156378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677435E+09 | 0.00 | 0.00 | 0.34 |
March | 0.225719E+10 | 0.00 | 0.00 | 76123.26 | 0.00 | 0.127721E+09 | 0.105298E+09 | 0.00 | 0.47 |
April | 0.129746E+10 | 172463.79 | 0.00 | 1628901.02 | 0.00 | 2266735.57 | 0.674423E+09 | 0.00 | 0.59 |
May | 0.665865E+09 | 4606459.58 | 0.00 | 4038140.43 | 1506769.04 | 0.00 | 0.114907E+10 | 0.00 | 0.70 |
June | 0.203721E+09 | 0.141590E+09 | 0.00 | 4150565.46 | 7222624.21 | 0.00 | 0.687584E+09 | 0.00 | 0.66 |
July | 44226761.80 | 0.453344E+09 | 0.00 | 1324483.45 | 57356198.77 | 0.00 | 82902684.48 | 0.00 | 0.58 |
August | 98150958.37 | 0.281525E+09 | 0.00 | 3185727.34 | 31064039.59 | 0.00 | 0.382648E+09 | 0.00 | 0.74 |
September | 0.253463E+09 | 54317530.83 | 0.00 | 5395437.25 | 11769909.05 | 0.00 | 0.941575E+09 | 0.00 | 0.78 |
October | 0.127535E+10 | 1556233.81 | 0.00 | 2765702.35 | 454723.28 | 7195238.90 | 0.870418E+09 | 0.00 | 0.62 |
November | 0.220870E+10 | 0.00 | 0.00 | 221642.88 | 0.00 | 70954689.55 | 0.230132E+09 | 0.00 | 0.40 |
December | 0.155127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.979228E+09 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.129759E+11 | 0.937112E+09 | 0.00 | 22786723.46 | 0.109374E+09 | 0.288697E+10 | 0.512405E+10 | 0.00 | 0.54 |
Minimum of Months | 44226761.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.225719E+10 | 0.453344E+09 | 0.00 | 5395437.25 | 57356198.77 | 0.102217E+10 | 0.114907E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.205822E+10 | 0.00 | 0.00 | 85425.02 | 0.00 | 0.443470E+09 | 97433362.29 | 0.00 | 0.52 |
February | 0.177238E+10 | 0.00 | 0.00 | 416924.43 | 0.00 | 0.239279E+09 | 0.280308E+09 | 0.00 | 0.56 |
March | 0.147210E+10 | 0.00 | 0.00 | 2369584.57 | 0.00 | 14280095.79 | 0.140812E+10 | 0.00 | 0.86 |
April | 0.512967E+09 | 253421.87 | 0.00 | 6500725.10 | 0.00 | 0.00 | 0.292281E+10 | 0.00 | 1.55 |
May | 0.325336E+09 | 5858068.31 | 0.00 | 8496011.01 | 1524632.44 | 0.00 | 0.269720E+10 | 0.00 | 1.69 |
June | 0.127211E+09 | 0.143365E+09 | 0.00 | 6695351.92 | 4124151.38 | 0.00 | 0.113615E+10 | 0.00 | 1.39 |
July | 30462768.32 | 0.536278E+09 | 0.00 | 2069983.39 | 30714590.54 | 0.00 | 0.129443E+09 | 0.00 | 1.12 |
August | 67046880.74 | 0.321934E+09 | 0.00 | 4910468.71 | 23850519.96 | 0.00 | 0.593006E+09 | 0.00 | 1.51 |
September | 0.180516E+09 | 52229762.80 | 0.00 | 8011285.98 | 8853990.20 | 0.00 | 0.156349E+10 | 0.00 | 1.66 |
October | 0.721940E+09 | 1554986.08 | 0.00 | 5959227.64 | 402175.17 | 2718274.64 | 0.226288E+10 | 0.00 | 1.31 |
November | 0.144142E+10 | 0.00 | 0.00 | 1799784.84 | 0.00 | 2126913.51 | 0.130088E+10 | 0.00 | 0.69 |
December | 0.215009E+10 | 0.00 | 0.00 | 51197.43 | 0.00 | 0.349346E+09 | 55164472.16 | 0.00 | 0.45 |
Annual Sum or Average | 0.108597E+11 | 0.106147E+10 | 0.00 | 47365970.05 | 69470059.70 | 0.105122E+10 | 0.144469E+11 | 0.00 | 1.11 |
Minimum of Months | 30462768.32 | 0.00 | 0.00 | 51197.43 | 0.00 | 0.00 | 55164472.16 | 0.00 | 0.45 |
Maximum of Months | 0.215009E+10 | 0.536278E+09 | 0.00 | 8496011.01 | 30714590.54 | 0.443470E+09 | 0.292281E+10 | 0.00 | 1.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131549E+10 | 0.00 | 0.00 | 4639859.74 | 0.00 | 0.100210E+10 | 0.251349E+10 | 0.00 | 0.69 |
February | 0.113932E+10 | 0.00 | 0.00 | 4299840.63 | 0.00 | 0.606775E+09 | 0.233299E+10 | 0.00 | 0.72 |
March | 0.146669E+10 | 0.00 | 0.00 | 4004502.83 | 0.00 | 0.440622E+09 | 0.224693E+10 | 0.00 | 0.88 |
April | 0.100132E+10 | 397047.22 | 0.00 | 4743947.05 | 0.00 | 0.210541E+09 | 0.174965E+10 | 0.00 | 1.01 |
May | 0.898986E+09 | 7924465.26 | 0.00 | 4463401.70 | 1661500.47 | 0.112534E+09 | 0.102561E+10 | 0.00 | 0.83 |
June | 0.385755E+09 | 0.166425E+09 | 0.00 | 3494662.24 | 10355390.17 | 15791045.92 | 0.413198E+09 | 0.00 | 0.65 |
July | 68658348.61 | 0.572946E+09 | 0.00 | 1026616.11 | 64152321.98 | 0.00 | 51080148.27 | 0.00 | 0.63 |
August | 0.168001E+09 | 0.434645E+09 | 0.00 | 3696279.30 | 31539434.72 | 0.00 | 0.359451E+09 | 0.00 | 0.95 |
September | 0.317805E+09 | 0.121056E+09 | 0.00 | 11506165.19 | 4225854.92 | 563904.59 | 0.152253E+10 | 0.00 | 1.36 |
October | 0.637344E+09 | 4615918.03 | 0.00 | 14920130.93 | 11972.70 | 0.187493E+09 | 0.437728E+10 | 0.00 | 1.66 |
November | 0.896298E+09 | 0.00 | 0.00 | 8888756.13 | 0.00 | 0.284333E+09 | 0.508397E+10 | 0.00 | 1.05 |
December | 0.131962E+10 | 0.00 | 0.00 | 5743410.06 | 0.00 | 0.730996E+09 | 0.296985E+10 | 0.00 | 0.59 |
Annual Sum or Average | 0.961530E+10 | 0.130801E+10 | 0.00 | 71427571.90 | 0.111946E+09 | 0.359175E+10 | 0.246460E+11 | 0.00 | 0.92 |
Minimum of Months | 68658348.61 | 0.00 | 0.00 | 1026616.11 | 0.00 | 0.00 | 51080148.27 | 0.00 | 0.59 |
Maximum of Months | 0.146669E+10 | 0.572946E+09 | 0.00 | 14920130.93 | 64152321.98 | 0.100210E+10 | 0.508397E+10 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193312E+10 | 0.00 | 0.00 | 412587.75 | 0.00 | 0.550493E+09 | 0.346056E+09 | 0.00 | 0.57 |
February | 0.173376E+10 | 0.00 | 0.00 | 951722.62 | 0.00 | 0.291092E+09 | 0.562956E+09 | 0.00 | 0.66 |
March | 0.201062E+10 | 0.00 | 0.00 | 1686085.51 | 0.00 | 63642914.35 | 0.950410E+09 | 0.00 | 0.96 |
April | 0.103626E+10 | 216920.75 | 0.00 | 4405515.12 | 0.00 | 0.00 | 0.153930E+10 | 0.00 | 1.33 |
May | 0.656653E+09 | 8942609.58 | 0.00 | 5328793.55 | 958712.93 | 0.00 | 0.141763E+10 | 0.00 | 1.33 |
June | 0.272345E+09 | 0.162177E+09 | 0.00 | 3739860.89 | 5722237.51 | 0.00 | 0.543229E+09 | 0.00 | 1.00 |
July | 45979482.17 | 0.439775E+09 | 0.00 | 1072106.36 | 54780898.77 | 0.00 | 68457715.05 | 0.00 | 0.82 |
August | 97069996.28 | 0.298140E+09 | 0.00 | 3020088.36 | 26758401.51 | 0.00 | 0.342133E+09 | 0.00 | 1.12 |
September | 0.230954E+09 | 61070147.74 | 0.00 | 6485407.37 | 8983350.95 | 0.00 | 0.992813E+09 | 0.00 | 1.27 |
October | 0.104208E+10 | 1998543.45 | 0.00 | 5160290.62 | 489445.87 | 6944653.13 | 0.163194E+10 | 0.00 | 1.27 |
November | 0.191962E+10 | 0.00 | 0.00 | 1468718.91 | 0.00 | 15870763.16 | 0.113030E+10 | 0.00 | 0.80 |
December | 0.197016E+10 | 0.00 | 0.00 | 453040.29 | 0.00 | 0.405089E+09 | 0.404479E+09 | 0.00 | 0.49 |
Annual Sum or Average | 0.129486E+11 | 0.972320E+09 | 0.00 | 34184217.36 | 97693047.54 | 0.133313E+10 | 0.992971E+10 | 0.00 | 0.97 |
Minimum of Months | 45979482.17 | 0.00 | 0.00 | 412587.75 | 0.00 | 0.00 | 68457715.05 | 0.00 | 0.49 |
Maximum of Months | 0.201062E+10 | 0.439775E+09 | 0.00 | 6485407.37 | 54780898.77 | 0.550493E+09 | 0.163194E+10 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.178831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728867E+09 | 0.00 | 0.00 | 0.32 |
February | 0.171597E+10 | 0.00 | 0.00 | 94540.82 | 0.00 | 0.404103E+09 | 67612958.37 | 0.00 | 0.34 |
March | 0.174696E+10 | 0.00 | 0.00 | 1032169.12 | 0.00 | 64369091.79 | 0.746492E+09 | 0.00 | 0.50 |
April | 0.839790E+09 | 463802.73 | 0.00 | 3739145.24 | 13980.12 | 254260.88 | 0.151710E+10 | 0.00 | 0.77 |
May | 0.465787E+09 | 7857668.79 | 0.00 | 6277750.50 | 1168380.04 | 0.00 | 0.179349E+10 | 0.00 | 0.90 |
June | 0.158449E+09 | 0.162553E+09 | 0.00 | 5575679.30 | 4328671.68 | 0.00 | 0.891613E+09 | 0.00 | 0.80 |
July | 41031268.86 | 0.515328E+09 | 0.00 | 1824312.10 | 37668674.05 | 0.00 | 0.104693E+09 | 0.00 | 0.67 |
August | 94565936.57 | 0.293873E+09 | 0.00 | 3770873.71 | 14985153.01 | 0.00 | 0.411845E+09 | 0.00 | 0.80 |
September | 0.262003E+09 | 59194172.21 | 0.00 | 5456908.25 | 7290315.73 | 0.00 | 0.932210E+09 | 0.00 | 0.79 |
October | 0.117105E+10 | 2048571.45 | 0.00 | 2885122.64 | 240901.04 | 25162927.43 | 0.895209E+09 | 0.00 | 0.62 |
November | 0.199810E+10 | 0.00 | 0.00 | 372209.61 | 0.00 | 0.115760E+09 | 0.313384E+09 | 0.00 | 0.40 |
December | 0.158832E+10 | 0.00 | 0.00 | 16.78 | 0.00 | 0.885122E+09 | 4520188.55 | 0.00 | 0.28 |
Annual Sum or Average | 0.118703E+11 | 0.104132E+10 | 0.00 | 31028728.08 | 65696075.67 | 0.222364E+10 | 0.767816E+10 | 0.00 | 0.60 |
Minimum of Months | 41031268.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.199810E+10 | 0.515328E+09 | 0.00 | 6277750.50 | 37668674.05 | 0.885122E+09 | 0.179349E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.219896E+10 | 0.00 | 0.00 | 319121.03 | 0.00 | 0.628598E+09 | 0.217331E+09 | 0.00 | 0.62 |
February | 0.197774E+10 | 0.00 | 0.00 | 873648.83 | 0.00 | 0.254131E+09 | 0.515317E+09 | 0.00 | 0.68 |
March | 0.160479E+10 | 0.00 | 0.00 | 3746542.05 | 0.00 | 18283686.09 | 0.205532E+10 | 0.00 | 1.08 |
April | 0.651781E+09 | 434310.48 | 0.00 | 7933568.22 | 10962.13 | 307664.21 | 0.358517E+10 | 0.00 | 1.84 |
May | 0.422428E+09 | 7061841.51 | 0.00 | 10411515.78 | 1413779.12 | 0.00 | 0.322236E+10 | 0.00 | 1.98 |
June | 0.180140E+09 | 0.140448E+09 | 0.00 | 7984861.41 | 3245549.87 | 0.00 | 0.129490E+10 | 0.00 | 1.60 |
July | 47943793.48 | 0.562954E+09 | 0.00 | 2514365.56 | 24349878.28 | 0.00 | 0.134673E+09 | 0.00 | 1.26 |
August | 0.100024E+09 | 0.307510E+09 | 0.00 | 5582385.29 | 15004350.74 | 0.00 | 0.619133E+09 | 0.00 | 1.62 |
September | 0.255568E+09 | 47384815.13 | 0.00 | 7712903.06 | 8463274.90 | 0.00 | 0.158276E+10 | 0.00 | 1.73 |
October | 0.105915E+10 | 1539576.88 | 0.00 | 5371904.50 | 266428.34 | 21015979.59 | 0.207306E+10 | 0.00 | 1.34 |
November | 0.213882E+10 | 0.00 | 0.00 | 1455387.11 | 0.00 | 49115718.91 | 0.927767E+09 | 0.00 | 0.79 |
December | 0.221973E+10 | 0.00 | 0.00 | 186965.84 | 0.00 | 0.624611E+09 | 0.150395E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.128571E+11 | 0.106733E+10 | 0.00 | 54093168.66 | 52754223.38 | 0.159606E+10 | 0.163782E+11 | 0.00 | 1.26 |
Minimum of Months | 47943793.48 | 0.00 | 0.00 | 186965.84 | 0.00 | 0.00 | 0.134673E+09 | 0.00 | 0.54 |
Maximum of Months | 0.221973E+10 | 0.562954E+09 | 0.00 | 10411515.78 | 24349878.28 | 0.628598E+09 | 0.358517E+10 | 0.00 | 1.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133536E+10 | 0.00 | 0.00 | 9715364.39 | 0.00 | 0.415044E+09 | 0.434733E+10 | 0.00 | 0.92 |
February | 0.115543E+10 | 0.00 | 0.00 | 10284689.97 | 0.00 | 0.142424E+09 | 0.450957E+10 | 0.00 | 1.03 |
March | 0.124560E+10 | 0.00 | 0.00 | 9465099.28 | 0.00 | 25938926.47 | 0.475516E+10 | 0.00 | 1.30 |
April | 0.802898E+09 | 868545.47 | 0.00 | 8945755.60 | 17267.27 | 314045.28 | 0.359051E+10 | 0.00 | 1.45 |
May | 0.628992E+09 | 12125696.21 | 0.00 | 7730545.63 | 1443101.41 | 0.00 | 0.222531E+10 | 0.00 | 1.14 |
June | 0.291449E+09 | 0.166936E+09 | 0.00 | 5126338.57 | 5544358.80 | 0.00 | 0.789241E+09 | 0.00 | 0.80 |
July | 61947690.67 | 0.585357E+09 | 0.00 | 1633861.29 | 46813075.55 | 0.00 | 84568332.54 | 0.00 | 0.69 |
August | 0.127041E+09 | 0.414562E+09 | 0.00 | 4555102.57 | 17918698.92 | 0.00 | 0.463231E+09 | 0.00 | 1.01 |
September | 0.294183E+09 | 0.127419E+09 | 0.00 | 11502053.36 | 4679693.44 | 0.00 | 0.154894E+10 | 0.00 | 1.37 |
October | 0.714145E+09 | 4626293.33 | 0.00 | 16574465.59 | 0.00 | 22320897.96 | 0.495359E+10 | 0.00 | 1.71 |
November | 0.107213E+10 | 0.00 | 0.00 | 12787341.23 | 0.00 | 19765903.60 | 0.638255E+10 | 0.00 | 1.26 |
December | 0.123144E+10 | 0.00 | 0.00 | 12031200.29 | 0.00 | 0.330990E+09 | 0.513527E+10 | 0.00 | 0.81 |
Annual Sum or Average | 0.896063E+10 | 0.131189E+10 | 0.00 | 0.110352E+09 | 76416195.40 | 0.956797E+09 | 0.387853E+11 | 0.00 | 1.13 |
Minimum of Months | 61947690.67 | 0.00 | 0.00 | 1633861.29 | 0.00 | 0.00 | 84568332.54 | 0.00 | 0.69 |
Maximum of Months | 0.133536E+10 | 0.585357E+09 | 0.00 | 16574465.59 | 46813075.55 | 0.415044E+09 | 0.638255E+10 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.205011E+10 | 0.00 | 0.00 | 796867.77 | 0.00 | 0.759892E+09 | 0.566898E+09 | 0.00 | 0.71 |
February | 0.185011E+10 | 0.00 | 0.00 | 1753425.63 | 0.00 | 0.387643E+09 | 0.969126E+09 | 0.00 | 0.85 |
March | 0.213935E+10 | 0.00 | 0.00 | 3094762.59 | 0.00 | 87091230.41 | 0.162558E+10 | 0.00 | 1.26 |
April | 0.121158E+10 | 663322.09 | 0.00 | 6250176.78 | 17999.30 | 2182836.67 | 0.201687E+10 | 0.00 | 1.69 |
May | 0.781446E+09 | 13881206.42 | 0.00 | 6525893.61 | 460365.19 | 294688.10 | 0.170508E+10 | 0.00 | 1.59 |
June | 0.369166E+09 | 0.169726E+09 | 0.00 | 4342755.61 | 5137473.39 | 0.00 | 0.565056E+09 | 0.00 | 1.15 |
July | 76425637.42 | 0.471755E+09 | 0.00 | 1196017.58 | 42803361.59 | 0.00 | 59714300.26 | 0.00 | 0.90 |
August | 0.178710E+09 | 0.291951E+09 | 0.00 | 2992068.17 | 15895495.21 | 0.00 | 0.282638E+09 | 0.00 | 1.16 |
September | 0.446691E+09 | 65716456.83 | 0.00 | 6052658.71 | 7085458.21 | 0.00 | 0.781325E+09 | 0.00 | 1.26 |
October | 0.146144E+10 | 2161845.07 | 0.00 | 4918579.15 | 303460.19 | 31936024.50 | 0.146117E+10 | 0.00 | 1.36 |
November | 0.226249E+10 | 0.00 | 0.00 | 1617519.45 | 0.00 | 0.103789E+09 | 0.117729E+10 | 0.00 | 0.94 |
December | 0.199934E+10 | 0.00 | 0.00 | 714941.41 | 0.00 | 0.744944E+09 | 0.551388E+09 | 0.00 | 0.60 |
Annual Sum or Average | 0.148269E+11 | 0.101586E+10 | 0.00 | 40255666.47 | 71703613.07 | 0.211777E+10 | 0.117621E+11 | 0.00 | 1.12 |
Minimum of Months | 76425637.42 | 0.00 | 0.00 | 714941.41 | 0.00 | 0.00 | 59714300.26 | 0.00 | 0.60 |
Maximum of Months | 0.226249E+10 | 0.471755E+09 | 0.00 | 6525893.61 | 42803361.59 | 0.759892E+09 | 0.201687E+10 | 0.00 | 1.69 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.257712E+12 | 0.145078E+11 | 0.00 | 0.195243E+12 | 0.361760E+10 |
February | 0.308704E+12 | 0.129973E+11 | 0.00 | 0.189809E+12 | 0.608287E+10 |
March | 0.387466E+12 | 0.122651E+11 | 0.00 | 0.230307E+12 | 0.132707E+11 |
April | 0.468734E+12 | 0.850184E+10 | 0.00 | 0.242036E+12 | 0.563456E+11 |
May | 0.489474E+12 | 0.551994E+10 | 0.00 | 0.198628E+12 | 0.107555E+12 |
June | 0.455165E+12 | 0.189570E+10 | 0.00 | 0.112247E+12 | 0.220252E+12 |
July | 0.466135E+12 | -0.124652E+10 | 0.00 | 0.516988E+10 | 0.284135E+12 |
August | 0.462315E+12 | 0.424822E+09 | 0.00 | 0.557687E+11 | 0.272110E+12 |
September | 0.384599E+12 | 0.278718E+10 | 0.00 | 0.149430E+12 | 0.174840E+12 |
October | 0.326726E+12 | 0.713241E+10 | 0.00 | 0.234381E+12 | 0.746890E+11 |
November | 0.270676E+12 | 0.117617E+11 | 0.00 | 0.232769E+12 | 0.337395E+10 |
December | 0.245920E+12 | 0.138340E+11 | 0.00 | 0.199698E+12 | 0.281068E+10 |
Annual Sum or Average | 0.452363E+13 | 0.903813E+11 | 0.00 | 0.204549E+13 | 0.121908E+13 |
Minimum of Months | 0.245920E+12 | -0.124652E+10 | 0.00 | 0.516988E+10 | 0.281068E+10 |