Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 08:28:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1951.29 | 391.65 | 391.65 |
Net Site Energy | 1951.29 | 391.65 | 391.65 |
Total Source Energy | 5922.71 | 1188.78 | 1188.78 |
Net Source Energy | 5922.71 | 1188.78 | 1188.78 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 12.78 | 2.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 466.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 363.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 111.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 150.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 120.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1827.90 | 123.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 12.78 | 2.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 466.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 363.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 111.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 17.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 150.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 120.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 12.78 | 2.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 466.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 363.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 111.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 17.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 150.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 120.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 95.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 126.37 | 24.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 145.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 366.89 | 24.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 95.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 126.37 | 24.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 145.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 366.89 | 24.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1827.901 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1827.901 | 100.00 |
Total On-Site and Utility Electric Sources | 1827.901 | 100.00 |
Total Electricity End Uses | 1827.901 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 71.33 |
Time Setpoint Not Met During Occupied Cooling | 456.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 981.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 10.1959 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 10.1959 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.1959 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 10.1959 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
Total | 4982.19 | 10.1959 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 10.1959 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 10.1959 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-15:09 | 06-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 01-FEB-12:09 |
Heating | 0.00 | 28839.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 98276.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 30098.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 42072.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1224.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 26736.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8909.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 198414.89 | 37748.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 28839.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 98276.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 30098.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 7527.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1224.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 26736.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8909.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 40.49 | 2.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1477.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1152.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 353.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 54.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 475.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 131.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5788.96 | 133.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 8.13 | 0.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 296.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 231.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 95.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 26.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1161.93 | 26.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 8.13 | 0.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 296.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 231.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 95.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 26.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1161.93 | 26.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.36 | 0.223246 | 0.244000 | 0.819127 | 0.595323 | 0.500000 | 0.001707 |
CORE_MID VAV BOX COMPONENT | 2.55 | 0.293828 | 0.313000 | 0.798356 | 0.783542 | 0.500000 | 0.001297 |
CORE_TOP VAV BOX COMPONENT | 2.77 | 0.270661 | 0.299000 | 0.827925 | 0.721763 | 0.500000 | 0.001408 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.968045 | 0.163207 | 0.200000 | 0.193609 | 0.435218 | 0.500000 | 0.002334 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.840343 | 0.119025 | 0.200000 | 0.168069 | 0.317400 | 0.500000 | 0.003201 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.06 | 0.148794 | 0.200000 | 0.212363 | 0.396784 | 0.500000 | 0.002561 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.954812 | 0.104749 | 0.200000 | 0.190962 | 0.300000 | 0.500000 | 0.003637 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.810194 | 0.195005 | 0.213000 | 0.172571 | 0.520013 | 0.500000 | 0.001954 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.744829 | 0.134288 | 0.200000 | 0.148966 | 0.358102 | 0.500000 | 0.002837 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.895887 | 0.176352 | 0.200000 | 0.179177 | 0.470272 | 0.500000 | 0.002160 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.790410 | 0.126536 | 0.200000 | 0.158082 | 0.337429 | 0.500000 | 0.003011 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.841589 | 0.187730 | 0.200000 | 0.168318 | 0.500614 | 0.500000 | 0.002030 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.802618 | 0.124619 | 0.200000 | 0.160524 | 0.332318 | 0.500000 | 0.003057 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.935756 | 0.168839 | 0.200000 | 0.187151 | 0.450236 | 0.500000 | 0.002257 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.864097 | 0.115745 | 0.200000 | 0.172819 | 0.308654 | 0.500000 | 0.003292 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 24836.75 |
CORE_MID VAV BOX REHEAT COIL | 24206.94 |
CORE_TOP VAV BOX REHEAT COIL | 30372.16 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 13800.19 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 9083.51 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 13877.43 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9024.55 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 9406.36 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6289.11 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9501.25 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6226.53 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 10878.90 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 7231.39 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 10956.25 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 7172.86 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.30 | 1.48 | 6.60 | 1.48 | 6.09 | 6.09 | 0.300000 | 0.242756 | 6.09 |
PACU_VAV_MID | 3.00 | 1.49 | 5.99 | 1.77 | 5.41 | 5.41 | 0.300000 | 0.326915 | 5.41 |
PACU_VAV_TOP | 3.30 | 1.59 | 6.59 | 2.51 | 6.32 | 6.32 | 0.300000 | 0.397412 | 6.32 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 6.09 |
PACU_VAV_MID_OA_CONTROLLER | 5.41 |
PACU_VAV_TOP_OA_CONTROLLER | 6.32 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 6.09 | 118527.62 | 0.786603 | 2.03 | 39505.26 | 0.786603 |
PACU_VAV_MID COOLING COIL | 5.41 | 107846.57 | 0.777045 | 1.80 | 35945.26 | 0.777045 |
PACU_VAV_TOP COOLING COIL | 6.32 | 121901.97 | 0.790538 | 2.11 | 40629.93 | 0.790538 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 10462.63 |
PACU_VAV_MID HEATING COIL | 13084.54 |
PACU_VAV_TOP HEATING COIL | 12024.16 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 6.09 |
PACU_VAV_MID FAN | 5.41 |
PACU_VAV_TOP FAN | 6.32 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 35.030 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.015 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 1.000 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.258 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7516 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7656 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5610 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27848788E-12 | 0.13637022E-14 | -0.81023097E-13 | 0.79216012E-16 |
43 | 6 | 0.25824895E-07 | 0.27625343E-09 | 0.59397345E-08 | -0.11998209E-12 |
44 | 5 | -0.17554640E-03 | 0.24097886E-05 | -0.90470599E-04 | 0.58795774E-08 |
45 | 4 | 0.27494803 | 0.11927753E-02 | 0.93505830E-01 | -0.31160983E-04 |
46 | 3 | -6.9253412 | 0.37505722E-01 | -2.2377579 | 0.27339040E-01 |
47 | 2 | 39.746130 | 0.13507978 | 14.849253 | -0.32081291 |
48 | 1 | -79.683230 | 0.61641880E-01 | -28.768593 | 1.0602386 |
49 | 0 | 46.824344 | 0.12537427E-02 | 16.300359 | |
50 | 7 | -0.27402251E-12 | 0.13062726E-14 | -0.81664977E-13 | 0.79643054E-16 |
51 | 6 | 0.25995733E-07 | 0.27297844E-09 | 0.59774430E-08 | -0.12089174E-12 |
52 | 5 | -0.17642699E-03 | 0.23783059E-05 | -0.90913883E-04 | 0.59164366E-08 |
53 | 4 | 0.27599802 | 0.11759213E-02 | 0.93882490E-01 | -0.31307097E-04 |
54 | 3 | -6.9461820 | 0.36940511E-01 | -2.2439388 | 0.27441040E-01 |
55 | 2 | 39.814917 | 0.13293308 | 14.874721 | -0.32157873 |
56 | 1 | -79.735998 | 0.60618496E-01 | -28.791459 | 1.0613631 |
57 | 0 | 46.824344 | 0.12320537E-02 | 16.299787 | |
58 | 7 | -0.27749376E-12 | 0.16893975E-14 | -0.84125370E-13 | 0.18079425E-15 |
59 | 6 | 0.22886636E-07 | 0.32835403E-09 | 0.52910653E-08 | -0.10444131E-12 |
60 | 5 | -0.16025164E-03 | 0.29299438E-05 | -0.82748939E-04 | 0.52444335E-08 |
61 | 4 | 0.25649379 | 0.14793778E-02 | 0.86896489E-01 | -0.28615133E-04 |
62 | 3 | -6.5585231 | 0.47340314E-01 | -2.1290029 | 0.25545250E-01 |
63 | 2 | 38.534810 | 0.17312159 | 14.399826 | -0.30733026 |
64 | 1 | -78.753333 | 0.80044855E-01 | -28.364722 | 1.0404251 |
65 | 0 | 46.824351 | 0.16491755E-02 | 16.310723 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.567_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 3.224 | 3.224 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 3.224 | 3.224 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.567_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.224 | 3.224 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.567_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 3.224 | 3.224 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60245 | 0.60245 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.42129E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60245 | 0.60245 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.42129E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60245 | 0.60245 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.42129E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60245 | 0.60245 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.42129E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.973 | 0.1730 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2473E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2895E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8241E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8597E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4210E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4497E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9164E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9329E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1053 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8618E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1180 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3139E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8200E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1403E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2073E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2006E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2482E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2962E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8251E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8671E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4221E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4551E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9162E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9327E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8852E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7971E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5899E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5722E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7472E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3693E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7685E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7749E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4346E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4511E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1985E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2104E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0304E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0346E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4038E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4095E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9581E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9955E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4875E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5174E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1737E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1953E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9162E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9327E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7526E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5651E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1291E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1968E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9540E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.2688E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2073E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2006E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9578E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9955E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4870E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5164E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1727E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1916E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9164E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9329E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2344E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4945E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7944E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2014E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1578E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0995E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7686E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7749E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0185E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0582E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6866E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7282E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6698E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6889E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4040E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4097E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1056 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.9855E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1165 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5225E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3451E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.0194E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6593E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.7065E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.7289E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7070E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4516E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4922E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6374E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3036E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6984E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7326E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1544E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0597E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4880E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6246E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3114E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2193E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6593E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7065E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.0980E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4184E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6807E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1388E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.0652E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0456E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6984E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7326E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1056 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.9849E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1165 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5217E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3446E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.0189E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6589E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.7063E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.7288E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7068E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4514E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4920E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6371E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3033E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6980E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7324E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1544E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0596E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4880E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6245E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3112E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2192E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6589E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7063E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.0980E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4182E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6806E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1386E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.0649E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0454E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6980E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7324E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 42280.73676 | 42280.73676 | 3.35708 | 3.35708 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 5169.50956 | 5169.50956 | 0.24034 | 0.42469 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 32153.10104 | 32153.10104 | 2.55066 | 2.55066 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 12281.36153 | 12281.36153 | 0.57196 | 0.57196 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 34598.53835 | 34598.53835 | 2.76898 | 2.76898 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 40.26800 | 5.63027E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 21406.25969 | 21406.25969 | 1.00169 | 1.00169 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 12096.57224 | 12096.57224 | 0.96805 | 0.96805 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 40.53400 | 5.63070E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 9694.71089 | 9694.71089 | 0.45514 | 0.45514 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10500.87908 | 10500.87908 | 0.84034 | 0.84034 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 36.41100 | 5.62429E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6380.49642 | 6380.49642 | 0.29958 | 0.29958 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13268.31142 | 13268.31142 | 1.06181 | 1.06181 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 40.80000 | 5.63111E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 9748.80320 | 9748.80320 | 0.45768 | 0.45768 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11931.28257 | 11931.28257 | 0.95481 | 0.95481 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6339.20724 | 6339.20724 | 0.29763 | 0.29763 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 10123.83220 | 10123.83220 | 0.81019 | 0.81019 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 6616.15908 | 6616.15908 | 0.31023 | 0.31023 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9307.10842 | 9307.10842 | 0.74483 | 0.74483 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 36.41100 | 5.62429E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 4422.73720 | 4422.73720 | 0.20742 | 0.20742 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 11194.63022 | 11194.63022 | 0.89589 | 0.89589 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 6682.68456 | 6682.68456 | 0.31336 | 0.31336 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9876.68184 | 9876.68184 | 0.79041 | 0.79041 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 38.71633 | 5.62786E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 4378.91377 | 4378.91377 | 0.20535 | 0.20535 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 10516.29049 | 10516.29049 | 0.84159 | 0.84159 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 7648.37957 | 7648.37957 | 0.35879 | 0.35879 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10029.38823 | 10029.38823 | 0.80262 | 0.80262 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 35.74600 | 5.62327E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5083.09791 | 5083.09791 | 0.23849 | 0.23849 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11692.98800 | 11692.98800 | 0.93576 | 0.93576 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 40.80000 | 5.63111E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 7702.54995 | 7702.54995 | 0.36134 | 0.36134 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10797.61665 | 10797.61665 | 0.86410 | 0.86410 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5042.10857 | 5042.10857 | 0.23656 | 0.23656 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 96823.40 | 6.08809 | 6.08809 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 16075.72 | 1.46104 | 1.46104 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 88195.04 | 5.40553 | 5.40553 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 15951.59 | 1.76715 | 1.76715 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 99239.32 | 6.32020 | 6.32020 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 15762.95 | 2.51172 | 2.51172 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.35708 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22325 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24400 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81913 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59532 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.70664E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24836.74521 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.55066 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29383 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31300 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79836 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78354 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.29668E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24206.94107 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.76898 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27066 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29900 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.82792 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72176 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40766E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 30372.16361 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96805 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16321 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19361 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43522 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.33446E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13800.18894 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84034 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11902 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16807 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31740 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.20101E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9083.50686 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06181 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14879 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21236 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39678 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56059E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13877.43095 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95481 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10475 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19096 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.63728E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9024.55151 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81019 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19500 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17257 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52001 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.95380E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9406.35842 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74483 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13429 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14897 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35810 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.83718E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6289.10676 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89589 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17635 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17918 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47027 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.16045E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9501.24876 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79041 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12654 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15808 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33743 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.01101E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6226.53252 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84159 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18773 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16832 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50061 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.02951E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10878.89632 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80262 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12462 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16052 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33232 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.05731E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7231.38555 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93576 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16884 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18715 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45024 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.25659E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10956.24982 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86410 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11575 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17282 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30865 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.29171E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7172.85548 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.29920 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.47792 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.59840 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.47792 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.08809 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 6.08809 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.24276 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.99736 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.48717 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.99472 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.76715 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.40553 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.40553 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.32691 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.29700 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.59293 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.59399 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.51172 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.32020 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 6.32020 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.39741 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 6.08809 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.40553 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 6.32020 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.08809 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.08809 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 118527.62022 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.78660 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.02916 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 39505.25582 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.78660 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 10462.63251 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 6.08809 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.40553 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.40553 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 107846.57343 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.77704 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.80166 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35945.26292 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.77704 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 13084.53530 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.40553 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.32020 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.32020 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 121901.96872 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.79054 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.10652 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 40629.92617 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.79054 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 12024.15872 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 6.32020 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 117317.16 | 400302.76 | 11.35 | 2.87 | 3.25 | 3.42 | 3.59 | 9.80 | 11.08 | 11.67 | 12.26 | 6.3926 | 5.1074 | 3.4399 | 1.3806 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 106848.77 | 364583.13 | 11.40 | 2.88 | 3.26 | 3.44 | 3.60 | 9.84 | 11.14 | 11.73 | 12.29 | 5.6759 | 4.5324 | 3.0520 | 1.2349 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 120611.59 | 411543.82 | 11.33 | 2.87 | 3.24 | 3.41 | 3.59 | 9.79 | 11.06 | 11.65 | 12.24 | 6.6363 | 5.3048 | 3.5728 | 1.4290 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_EAST_0.25 | N/A | 3.224 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_WEST_0.25 | N/A | 3.224 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_EAST_0.25 | N/A | 3.224 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_EAST_0.25 | N/A | 3.224 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_WEST_0.25 | N/A | 3.224 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_WEST_0.25 | N/A | 3.224 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_EAST_0.25 | N/A | 3.224 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_WEST_0.25 | N/A | 3.224 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 8.4355332652E-003 | 5.2950898121E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1140757698 | 7.2730997862E-002 | Pass | Pass | 8.9408595505E-003 | 9.5573787648E-002 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.2641611430E-002 | 1.0540736868E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.9814901050E-002 | 9.2559814177E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.2125907950E-002 | 6.9093497915E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.0270299219E-002 | 2.6783691247E-002 | Pass | Pass | 7.3787585553E-003 | 8.5613772538E-002 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.2072546515E-002 | 5.3590523873E-002 | Pass | Pass | 8.7917265741E-003 | 0.1042327832 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.9853957407E-002 | 8.0605593106E-002 | Pass | Pass | 5.8806386030E-003 | 4.9740754819E-002 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1398652636 | 0.1012094659 | Pass | Pass | 6.6706344413E-003 | 6.0037285127E-002 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1262868732 | 0.1021187097 | Pass | Pass | 7.1115421737E-003 | 8.4346766697E-002 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.2537029664E-002 | 2.0923931352E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.6741124589E-002 | 6.9591302447E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.0258381921E-002 | 7.5530088857E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.4016389624E-002 | 8.2016693753E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.9300324492E-002 | 2.2648951010E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.9188657929E-002 | 8.2936761397E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1201345183 | 9.8243489123E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1043284296 | 9.7387732547E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2875.82 | 19.40 | 0.00 | 1263.81 | 2092.88 | 6251.93 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.567_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.224 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.567_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.224 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.224 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.567_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.224 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.567_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.567_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.567_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.567_SHGC_EAST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.567_SHGC_EAST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.567_SHGC_WEST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.567_SHGC_WEST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.567_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.224 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.567_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.224 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.224 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.567_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.224 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 3.224 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 195.79 | 3.224 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 456.84 | 3.224 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.40 | 0.0000 | Y | 10.87 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.69 | 0.0000 | Y | 6.71 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.40 | 0.0000 | Y | 10.48 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.09 | 0.0000 | Y | 6.80 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.28 | 0.0000 | Y | 10.82 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.62 | 0.0000 | Y | 6.69 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.35 | 0.0000 | Y | 10.46 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.01 | 0.0000 | Y | 6.78 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.40 | 0.0000 | Y | 10.87 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.69 | 0.0000 | Y | 6.71 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.40 | 0.0000 | Y | 10.48 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.09 | 0.0000 | Y | 6.80 |
Interior Lighting Total | 10.1959 | 4982.19 | 50797.72 | 363.97 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.28 | AstronomicalClock | - | 41.79 | 41.79 | 4.42 | |
EXTERIOR_LIGHTS_B | 8033.20 | AstronomicalClock | - | 83.79 | 71.19 | 107.34 | |
Exterior Lighting Total | 8596.48 | 111.76 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 118527.62 | 93234.20 | 25293.42 | 0.79 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 107846.57 | 83801.62 | 24044.96 | 0.78 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 121901.97 | 96368.15 | 25533.82 | 0.79 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 117317.2 | 2.87 | 9.80 | N/A | N/A | 11.35 | |
PACU_VAV_MID COOLING COIL | 106848.8 | 2.88 | 9.84 | N/A | N/A | 11.40 | |
PACU_VAV_TOP COOLING COIL | 120611.6 | 2.87 | 9.79 | N/A | N/A | 11.33 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 24836.75 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24206.94 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 30372.16 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13800.19 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9083.51 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13877.43 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9024.55 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9406.36 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6289.11 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9501.25 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6226.53 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10878.90 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7231.39 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10956.25 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7172.86 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 10462.63 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 13084.54 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 12024.16 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 6.09 | 13240.91 | 2174.89 | 1.00 | 1.13 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.41 | 11756.42 | 2174.89 | 1.00 | 1.14 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 6.32 | 13745.72 | 2174.89 | 1.00 | 1.13 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.97 | 0.17 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 117317.16 | 2.87 | 9.80 | 11.35 | 6.3926 | 3.25 | 11.08 | 5.1074 | 3.42 | 11.67 | 3.4399 | 3.59 | 12.26 | 1.3806 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 106848.77 | 2.88 | 9.84 | 11.40 | 5.6759 | 3.26 | 11.14 | 4.5324 | 3.44 | 11.73 | 3.0520 | 3.60 | 12.29 | 1.2349 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 120611.59 | 2.87 | 9.79 | 11.33 | 6.6363 | 3.24 | 11.06 | 5.3048 | 3.41 | 11.65 | 3.5728 | 3.59 | 12.24 | 1.4290 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 42280.74 | 42280.74 | 42.99 | 3.357 | 3.357 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00879 | 30.96 | 0.00562 | 0.425 | 0.00 |
CORE_MID | 32153.10 | 32153.10 | 32.69 | 2.551 | 2.551 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 30.96 | 0.00562 | 0.425 | 0.00 |
CORE_TOP | 34598.54 | 34598.54 | 35.18 | 2.769 | 2.769 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00885 | 40.27 | 0.00563 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 12096.57 | 12096.57 | 58.34 | 0.968 | 0.968 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00860 | 40.53 | 0.00563 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10500.88 | 10500.88 | 80.00 | 0.840 | 0.840 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 24.00 | 24.00 | 0.00857 | 36.41 | 0.00562 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13268.31 | 13268.31 | 63.99 | 1.062 | 1.062 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00860 | 40.80 | 0.00563 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11931.28 | 11931.28 | 90.90 | 0.955 | 0.955 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00856 | 38.94 | 0.00563 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 10123.83 | 10123.83 | 48.83 | 0.810 | 0.810 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00868 | 40.67 | 0.00563 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9307.11 | 9307.11 | 70.90 | 0.745 | 0.745 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 24.00 | 24.00 | 0.00862 | 36.41 | 0.00562 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11194.63 | 11194.63 | 53.99 | 0.896 | 0.896 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00866 | 40.80 | 0.00563 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9876.68 | 9876.68 | 75.25 | 0.790 | 0.790 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00862 | 38.72 | 0.00563 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 10516.29 | 10516.29 | 50.72 | 0.842 | 0.842 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00864 | 40.67 | 0.00563 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10029.39 | 10029.39 | 76.41 | 0.803 | 0.803 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 24.00 | 24.00 | 0.00859 | 35.75 | 0.00562 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11692.99 | 11692.99 | 56.40 | 0.936 | 0.936 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00863 | 40.80 | 0.00563 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10797.62 | 10797.62 | 82.27 | 0.864 | 0.864 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00858 | 38.94 | 0.00563 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 5169.51 | 5169.51 | 5.26 | 0.240 | 0.425 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 0.425 | 0.00 |
CORE_MID | 12281.36 | 12281.36 | 12.49 | 0.572 | 0.572 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 0.425 | 0.00 |
CORE_TOP | 21406.26 | 21406.26 | 21.76 | 1.002 | 1.002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9694.71 | 9694.71 | 46.76 | 0.455 | 0.455 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00786 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 6380.50 | 6380.50 | 48.61 | 0.300 | 0.300 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00786 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9748.80 | 9748.80 | 47.02 | 0.458 | 0.458 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00786 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6339.21 | 6339.21 | 48.30 | 0.298 | 0.298 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00786 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6616.16 | 6616.16 | 31.91 | 0.310 | 0.310 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 4422.74 | 4422.74 | 33.69 | 0.207 | 0.207 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 6682.68 | 6682.68 | 32.23 | 0.313 | 0.313 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 4378.91 | 4378.91 | 33.36 | 0.205 | 0.205 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7648.38 | 7648.38 | 36.89 | 0.359 | 0.359 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5083.10 | 5083.10 | 38.72 | 0.238 | 0.238 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 7702.55 | 7702.55 | 37.15 | 0.361 | 0.361 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 5042.11 | 5042.11 | 38.42 | 0.237 | 0.237 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 0.50 | 0.00432 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 6.09 | 6.09 | 1.46 | 1.46 | 6.0881 | 1.4779 | 6.0881 | 0.2428 | 0.3000 |
PACU_VAV_MID | 5.41 | 5.41 | 1.77 | 1.77 | 5.4055 | 1.7671 | 5.4055 | 0.3269 | 0.3000 |
PACU_VAV_TOP | 6.32 | 6.32 | 2.51 | 2.51 | 6.3202 | 2.5117 | 6.3202 | 0.3974 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 24836.745 | 24836.745 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24836.75 | 12877.06 | 0.424691 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 5169.51 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24206.941 | 24206.941 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24206.94 | 17342.26 | 0.571955 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 12281.36 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 30372.164 | 30372.164 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 30372.16 | 30372.16 | 1.001687 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 21406.26 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 13800.189 | 13800.189 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13800.19 | 13800.19 | 0.455136 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00785662 | 46.1220 | 9694.71 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 9083.507 | 9083.507 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9083.51 | 9083.51 | 0.299578 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00785677 | 46.1229 | 6380.50 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 13877.431 | 13877.431 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13877.43 | 13877.43 | 0.457684 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00785770 | 46.1282 | 9748.80 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 9024.552 | 9024.552 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9024.55 | 9024.55 | 0.297634 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00785557 | 46.1159 | 6339.21 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 9406.358 | 9406.358 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9406.36 | 9406.36 | 0.310226 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00781393 | 45.8747 | 6616.16 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6289.107 | 6289.107 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6289.11 | 6289.11 | 0.207417 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00782607 | 45.9450 | 4422.74 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9501.249 | 9501.249 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9501.25 | 9501.25 | 0.313355 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00781799 | 45.8982 | 6682.68 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 6226.533 | 6226.533 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6226.53 | 6226.53 | 0.205354 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00782224 | 45.9228 | 4378.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 10878.896 | 10878.896 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10878.90 | 10878.90 | 0.358791 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00781036 | 45.8541 | 7648.38 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 7231.386 | 7231.386 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7231.39 | 7231.39 | 0.238494 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00781942 | 45.9066 | 5083.10 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 10956.250 | 10956.250 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10956.25 | 10956.25 | 0.361342 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00781298 | 45.8693 | 7702.55 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 7172.855 | 7172.855 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7172.86 | 7172.86 | 0.236564 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00781640 | 45.8891 | 5042.11 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 118527.620 | 93234.204 | 6.088089 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 108060.01 | 108060.01 | 6.088089 | 27.30 | 16.22 | 0.00812583 | 10.85 | 10.06 | 0.00812583 | 40.80 | 0.00563111 | 18.58 | 19.6313 | 24.00 | 0.00873653 | 42.6821 | 75939.54 | 0.00 | 122217.89 | 90214.31 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 10462.633 | 10462.633 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10462.63 | 10462.63 | 1.826427 | 7.59 | 5.78 | 0.00555825 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 65.4376 | 21.00 | 0.00788383 | 46.2788 | 19521.88 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 107846.573 | 83801.616 | 5.405526 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 98322.24 | 98322.24 | 5.405526 | 27.73 | 16.30 | 0.00805568 | 10.85 | 9.99 | 0.00805568 | 40.80 | 0.00563111 | 18.58 | 22.1102 | 24.00 | 0.00874879 | 42.7408 | 67175.83 | 0.00 | 111204.29 | 81174.43 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 13084.535 | 13084.535 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13084.54 | 13084.54 | 1.621658 | 5.45 | 4.29 | 0.00519189 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 73.7005 | 19.60 | 0.00756268 | 48.4332 | 22083.81 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 121901.969 | 96368.147 | 6.320196 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 111302.48 | 111302.48 | 6.320196 | 27.17 | 16.17 | 0.00812010 | 10.85 | 10.05 | 0.00812010 | 40.67 | 0.00563090 | 18.54 | 18.9103 | 24.00 | 0.00870427 | 42.5262 | 78571.02 | 0.00 | 125697.29 | 93198.74 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 12024.159 | 12024.159 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12024.16 | 12024.16 | 1.896059 | 7.03 | 5.56 | 0.00559562 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 63.0344 | 19.60 | 0.00774862 | 49.6064 | 27009.56 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 24836.745 | 24836.745 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 24836.75 | 12877.06 | 1.0000 | 0.46426985 | 0.424691 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24836.75 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.69 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 5169.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24206.941 | 24206.941 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 24206.94 | 17342.26 | 1.0000 | 0.62525830 | 0.571955 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24206.94 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 12281.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 30372.164 | 30372.164 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 30372.16 | 30372.16 | 1.0000 | 1.09503870 | 1.001687 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30372.16 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 21406.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13800.189 | 13800.189 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13800.19 | 13800.19 | 1.0000 | 0.49755233 | 0.455136 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13800.19 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00785662 | 21.00 | 0.00785662 | 46.1220 | 9694.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9083.507 | 9083.507 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9083.51 | 9083.51 | 1.0000 | 0.32749697 | 0.299578 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9083.51 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00785677 | 21.00 | 0.00785677 | 46.1229 | 6380.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13877.431 | 13877.431 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13877.43 | 13877.43 | 1.0000 | 0.50033722 | 0.457684 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13877.43 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00785770 | 21.00 | 0.00785770 | 46.1282 | 9748.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9024.552 | 9024.552 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9024.55 | 9024.55 | 1.0000 | 0.32537139 | 0.297634 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9024.55 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00785557 | 21.00 | 0.00785557 | 46.1159 | 6339.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 9406.358 | 9406.358 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9406.36 | 9406.36 | 1.0000 | 0.33913707 | 0.310226 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9406.36 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00781393 | 21.00 | 0.00781393 | 45.8747 | 6616.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6289.107 | 6289.107 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6289.11 | 6289.11 | 1.0000 | 0.22674760 | 0.207417 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6289.11 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00782607 | 21.00 | 0.00782607 | 45.9450 | 4422.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 9501.249 | 9501.249 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9501.25 | 9501.25 | 1.0000 | 0.34255824 | 0.313355 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9501.25 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00781799 | 21.00 | 0.00781799 | 45.8982 | 6682.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 6226.533 | 6226.533 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6226.53 | 6226.53 | 1.0000 | 0.22449155 | 0.205354 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6226.53 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00782224 | 21.00 | 0.00782224 | 45.9228 | 4378.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10878.896 | 10878.896 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10878.90 | 10878.90 | 1.0000 | 0.39222798 | 0.358791 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10878.90 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00781036 | 21.00 | 0.00781036 | 45.8541 | 7648.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7231.386 | 7231.386 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7231.39 | 7231.39 | 1.0000 | 0.26072054 | 0.238494 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7231.39 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00781942 | 21.00 | 0.00781942 | 45.9066 | 5083.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10956.250 | 10956.250 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10956.25 | 10956.25 | 1.0000 | 0.39501689 | 0.361342 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10956.25 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00781298 | 21.00 | 0.00781298 | 45.8693 | 7702.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7172.855 | 7172.855 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7172.86 | 7172.86 | 1.0000 | 0.25861030 | 0.236564 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7172.86 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00781640 | 21.00 | 0.00781640 | 45.8891 | 5042.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 118527.620 | 93234.204 | 6.088089 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9455 | 1004.8586 | 1.0932 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.088089 | 6.65546410 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 108060.01 | 108060.01 | 0.9117 | 6.65546410 | 6.088089 | 27.30 | 16.22 | 0.00812583 | 48169.8 | 10.85 | 10.06 | 0.00812583 | 31388.0 | -999.0 | -999.00 | -999.00 | -999.00 | 13240.915 | 94819.09 | 40.80 | 0.00563111 | 18.58 | 1.19517000 | 19.6313 | 24.00 | 0.00873653 | 24.00 | 0.00873653 | 42.6821 | 75939.54 | 0.00 | 122217.89 | 90214.31 | 6.39262358 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.86 | 12.84 | 0.00922179 | 36203.8 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10462.633 | 10462.633 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.088089 | 6.65546410 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10462.63 | 10462.63 | 1.0000 | 1.99663923 | 1.826427 | 7.59 | 5.78 | 0.00555825 | 21601.2 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10462.63 | 0.50 | 0.00431558 | 0.50 | 1.19517000 | 65.4376 | 21.00 | 0.00791101 | 21.00 | 0.00788383 | 46.2788 | 19521.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 107846.573 | 83801.616 | 5.405526 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8151 | 1004.8586 | 1.0932 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.405526 | 5.90929005 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 98322.24 | 98322.24 | 0.9117 | 5.90929005 | 5.405526 | 27.73 | 16.30 | 0.00805568 | 48430.5 | 10.85 | 9.99 | 0.00805568 | 31210.9 | -999.0 | -999.00 | -999.00 | -999.00 | 11756.416 | 86565.83 | 40.80 | 0.00563111 | 18.58 | 1.19517000 | 22.1102 | 24.00 | 0.00874879 | 24.00 | 0.00874879 | 42.7408 | 67175.83 | 0.00 | 111204.29 | 81174.43 | 5.67591777 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.67 | 12.65 | 0.00911028 | 35730.1 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 13084.535 | 13084.535 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.405526 | 5.90929005 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13084.54 | 13084.54 | 1.0000 | 1.77278702 | 1.621658 | 5.45 | 4.29 | 0.00519189 | 18518.6 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13084.54 | 0.50 | 0.00431558 | 0.50 | 1.19517000 | 73.7005 | 19.34 | 0.00764762 | 19.60 | 0.00756268 | 48.4332 | 22083.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 121901.969 | 96368.147 | 6.320196 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9349 | 1004.8586 | 1.0932 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.320196 | 6.90920161 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 111302.48 | 111302.48 | 0.9130 | 6.90920161 | 6.320196 | 27.17 | 16.17 | 0.00812010 | 48016.7 | 10.85 | 10.05 | 0.00812010 | 31373.6 | -999.0 | -999.00 | -999.00 | -999.00 | 13745.720 | 97556.76 | 40.67 | 0.00563090 | 18.54 | 1.19517000 | 18.9103 | 24.00 | 0.00870427 | 24.00 | 0.00870427 | 42.5262 | 78571.02 | 0.00 | 125697.29 | 93198.74 | 6.63634038 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.93 | 12.90 | 0.00926463 | 36381.6 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12024.159 | 12024.159 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.320196 | 6.90920161 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12024.16 | 12024.16 | 1.0000 | 2.07276048 | 1.896059 | 7.03 | 5.56 | 0.00559562 | 21128.4 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12024.16 | 0.50 | 0.00431558 | 0.50 | 1.19517000 | 63.0344 | 18.16 | 0.00777836 | 19.60 | 0.00774862 | 49.6064 | 27009.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 6.09 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.41 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 6.32 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2181.00 | 999.33 | 2.83 |
CORE_MID | 1712.83 | 2268.67 | 17.83 |
CORE_TOP | 1742.17 | 2663.50 | 88.33 |
PERIMETER_TOP_ZN_3 | 2506.50 | 3067.00 | 645.17 |
PERIMETER_TOP_ZN_2 | 2868.50 | 2641.17 | 559.17 |
PERIMETER_TOP_ZN_1 | 2961.83 | 2131.17 | 459.50 |
PERIMETER_TOP_ZN_4 | 2824.33 | 2847.00 | 671.67 |
PERIMETER_BOT_ZN_3 | 1971.83 | 3015.83 | 190.00 |
PERIMETER_BOT_ZN_2 | 2573.83 | 2367.83 | 224.17 |
PERIMETER_BOT_ZN_1 | 2661.83 | 2002.50 | 285.83 |
PERIMETER_BOT_ZN_4 | 2476.83 | 2501.67 | 221.67 |
PERIMETER_MID_ZN_3 | 2136.17 | 2881.00 | 286.00 |
PERIMETER_MID_ZN_2 | 2228.17 | 2184.67 | 333.33 |
PERIMETER_MID_ZN_1 | 2791.33 | 1848.67 | 242.67 |
PERIMETER_MID_ZN_4 | 2559.83 | 2612.67 | 349.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4282.67 | 3627.00 | 981.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.17 | 41.00 | 0.17 | 25.33 |
PERIMETER_TOP_ZN_2 | 0.17 | 74.00 | 0.17 | 63.17 |
PERIMETER_TOP_ZN_1 | 0.00 | 71.00 | 0.00 | 56.83 |
PERIMETER_TOP_ZN_4 | 0.17 | 64.00 | 0.17 | 34.83 |
PERIMETER_BOT_ZN_3 | 0.00 | 12.83 | 0.00 | 8.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 56.67 | 0.00 | 50.50 |
PERIMETER_BOT_ZN_1 | 71.17 | 305.67 | 71.17 | 300.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 52.00 | 0.00 | 28.50 |
PERIMETER_MID_ZN_3 | 0.00 | 24.67 | 0.00 | 15.83 |
PERIMETER_MID_ZN_2 | 0.00 | 62.50 | 0.00 | 57.00 |
PERIMETER_MID_ZN_1 | 0.00 | 61.50 | 0.00 | 53.83 |
PERIMETER_MID_ZN_4 | 0.00 | 54.00 | 0.00 | 30.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 71.33 | 511.17 | 71.33 | 456.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 1.009 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.682 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.651 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.755 | 0.067 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 1.166 | 0.071 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 1.262 | 0.067 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 1.211 | 0.071 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.680 | 0.036 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 1.093 | 0.038 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 1.122 | 1.278 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 1.043 | 0.038 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.723 | 0.056 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 1.118 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 1.241 | 0.056 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 1.160 | 0.059 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.30 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 15975187.91 | 0.00 | 15975187.91 | 0.00 | 15975187.91 | 13393058.27 | 5824.12 | 67.90 | 2867.98 | 35.58 |
CORE_MID | 10794441.75 | 0.00 | 10794441.75 | 0.00 | 10794441.75 | 13393058.27 | 6387.28 | 19.56 | 2353.16 | 21.51 |
CORE_TOP | 10306271.20 | 0.00 | 10306271.20 | 0.00 | 10306271.20 | 13393058.27 | 6449.32 | 12.99 | 2297.70 | 21.22 |
PERIMETER_TOP_ZN_3 | 2521561.18 | 0.00 | 2521561.18 | 446659.24 | 2968220.42 | 2823374.22 | 4389.15 | 43.49 | 4327.36 | 21.22 |
PERIMETER_TOP_ZN_2 | 2461057.28 | 0.00 | 2461057.28 | 297771.03 | 2758828.31 | 1787429.43 | 4084.91 | 7.99 | 4667.11 | 21.22 |
PERIMETER_TOP_ZN_1 | 4202209.15 | 0.00 | 4202209.15 | 446659.24 | 4648868.39 | 2823374.22 | 4220.21 | 21.70 | 4518.09 | 21.22 |
PERIMETER_TOP_ZN_4 | 2560785.65 | 0.00 | 2560785.65 | 297771.03 | 2858556.68 | 1787312.18 | 4220.19 | 32.03 | 4507.78 | 21.22 |
PERIMETER_BOT_ZN_3 | 2278316.62 | 0.00 | 2278316.62 | 237487.89 | 2515804.51 | 2823374.22 | 5389.71 | 116.47 | 3253.82 | 35.58 |
PERIMETER_BOT_ZN_2 | 2314054.89 | 0.00 | 2314054.89 | 158324.31 | 2472379.20 | 1787429.43 | 4109.16 | 24.40 | 4626.44 | 35.58 |
PERIMETER_BOT_ZN_1 | 3748621.58 | 0.00 | 3748621.58 | 4361350.24 | 8109971.82 | 2823374.22 | 4230.21 | 58.85 | 4470.94 | 35.58 |
PERIMETER_BOT_ZN_4 | 2211870.49 | 0.00 | 2211870.49 | 158324.31 | 2370194.80 | 1787312.18 | 4467.79 | 61.53 | 4230.68 | 35.58 |
PERIMETER_MID_ZN_3 | 2412219.36 | 0.00 | 2412219.36 | 371810.73 | 2784030.08 | 2823374.22 | 4511.42 | 58.51 | 4190.07 | 21.51 |
PERIMETER_MID_ZN_2 | 2496680.21 | 0.00 | 2496680.21 | 247872.33 | 2744552.54 | 1787429.43 | 4079.75 | 8.21 | 4672.04 | 930.51 |
PERIMETER_MID_ZN_1 | 4131753.22 | 0.00 | 4131753.22 | 371810.73 | 4503563.95 | 2823374.22 | 4150.11 | 27.73 | 4582.16 | 21.51 |
PERIMETER_MID_ZN_4 | 2451582.88 | 0.00 | 2451582.88 | 247872.33 | 2699455.21 | 1787312.18 | 4178.29 | 36.46 | 4545.25 | 21.51 |
Total Facility | 70866613.38 | 0.00 | 70866613.38 | 7643713.41 | 78510326.78 | 67843644.98 | 6600.49 | 474.89 | 4808.91 | 955.41 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7412 | 0.0000 | 0.7412 | 0.0000 | 0.7412 | 0.4247 | 3042.70 | 67.90 | 2832.40 |
CORE_MID | 0.5013 | 0.0000 | 0.5013 | 0.0000 | 0.5013 | 0.4247 | 3591.79 | 19.56 | 2331.66 |
CORE_TOP | 0.4788 | 0.0000 | 0.4788 | 0.0000 | 0.4788 | 0.4247 | 3651.95 | 12.99 | 2278.06 |
PERIMETER_TOP_ZN_3 | 0.1172 | 0.0000 | 0.1172 | 0.0104 | 0.1276 | 0.0895 | 1591.78 | 43.49 | 4307.73 |
PERIMETER_TOP_ZN_2 | 0.1145 | 0.0000 | 0.1145 | 0.0070 | 0.1214 | 0.0567 | 1287.54 | 7.99 | 4647.47 |
PERIMETER_TOP_ZN_1 | 0.1957 | 0.0000 | 0.1957 | 0.0104 | 0.2061 | 0.0895 | 1422.84 | 21.70 | 4498.45 |
PERIMETER_TOP_ZN_4 | 0.1190 | 0.0000 | 0.1190 | 0.0070 | 0.1260 | 0.0567 | 1422.83 | 32.03 | 4488.15 |
PERIMETER_BOT_ZN_3 | 0.1054 | 0.0000 | 0.1054 | 0.0055 | 0.1109 | 0.0895 | 2608.29 | 116.47 | 3218.25 |
PERIMETER_BOT_ZN_2 | 0.1072 | 0.0000 | 0.1072 | 0.0037 | 0.1109 | 0.0567 | 1327.74 | 24.40 | 4590.86 |
PERIMETER_BOT_ZN_1 | 0.1740 | 0.0000 | 0.1740 | 0.1983 | 0.3723 | 0.0895 | 1448.79 | 58.85 | 4435.36 |
PERIMETER_BOT_ZN_4 | 0.1024 | 0.0000 | 0.1024 | 0.0037 | 0.1061 | 0.0567 | 1686.37 | 61.53 | 4195.10 |
PERIMETER_MID_ZN_3 | 0.1121 | 0.0000 | 0.1121 | 0.0087 | 0.1208 | 0.0895 | 1715.93 | 58.51 | 4168.56 |
PERIMETER_MID_ZN_2 | 0.1097 | 0.0000 | 0.1097 | 0.0062 | 0.1159 | 0.0567 | 1272.42 | 6.38 | 3755.20 |
PERIMETER_MID_ZN_1 | 0.1924 | 0.0000 | 0.1924 | 0.0087 | 0.2011 | 0.0895 | 1354.62 | 27.73 | 4560.65 |
PERIMETER_MID_ZN_4 | 0.1139 | 0.0000 | 0.1139 | 0.0058 | 0.1197 | 0.0567 | 1382.80 | 36.46 | 4523.74 |
Total Facility | 3.2846 | 0.0000 | 3.2846 | 0.2754 | 3.5601 | 2.1513 | 3795.43 | 474.89 | 4764.09 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 31702957.20 | 0.00 | 31702957.20 | 22614548.33 | 4011.64 | 1.42 | 4746.95 | 35.58 |
PACU_VAV_MID | 26634222.97 | 0.00 | 26634222.97 | 22614548.33 | 4045.83 | 1.04 | 4713.13 | 21.51 |
PACU_VAV_TOP | 26353621.54 | 0.00 | 26353621.54 | 22614548.33 | 4090.37 | 3.31 | 4666.32 | 21.22 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.4701 | 0.0000 | 1.4701 | 0.7171 | 1230.22 | 1.42 | 4711.37 |
PACU_VAV_MID | 1.2378 | 0.0000 | 1.2378 | 0.7171 | 1250.34 | 1.04 | 4691.62 |
PACU_VAV_TOP | 1.2250 | 0.0000 | 1.2250 | 0.7171 | 1293.01 | 3.31 | 4646.69 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.16 | 2554.10 | 0.00 | 0.00 | 0.00 | 2204.51 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 2444.56 | 0.00 | 0.00 | 0.00 | 2283.63 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2420.43 | 0.00 | 0.00 | 0.00 | 2297.48 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.6597 | 0.0000 | 0.0000 | 0.0000 | 0.9254 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.1462 | 0.0000 | 0.0000 | 0.0000 | 0.9445 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.1421 | 0.0000 | 0.0000 | 0.0000 | 0.9322 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 829 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1827.90 | 13162.99 | 04-JUN-17:20 | 198414.89 | 28-JUN-15:10 |
Electricity:Building | 1069.40 | 12913.45 | 16-APR-17:10 | 83993.65 | 20-JAN-08:30 |
Electricity:Zone:CORE_BOTTOM | 322.66 | 4214.70 | 01-JAN-00:10 | 25737.69 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1069.40 | 12913.45 | 16-APR-17:10 | 83993.65 | 20-JAN-08:30 |
InteriorLights:Electricity | 363.97 | 1672.11 | 01-JAN-10:20 | 38257.79 | 20-JAN-17:00 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 363.97 | 1672.11 | 01-JAN-10:20 | 38257.79 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity | 363.97 | 1672.11 | 01-JAN-10:20 | 38257.79 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 363.97 | 1672.11 | 01-JAN-10:20 | 38257.79 | 20-JAN-17:00 |
Electricity:Zone:CORE_MID | 201.92 | 2251.11 | 01-JAN-00:10 | 14360.82 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 201.92 | 2251.11 | 01-JAN-00:10 | 14360.82 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 35.21 | 428.29 | 02-APR-17:10 | 3027.38 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.87 | 42.19 | 01-JAN-10:20 | 1592.13 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.87 | 42.19 | 01-JAN-10:20 | 1592.13 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.11 | 271.13 | 16-APR-17:10 | 1916.52 | 20-JAN-08:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.71 | 26.71 | 01-JAN-08:00 | 1007.95 | 20-JAN-08:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.71 | 26.71 | 01-JAN-08:00 | 1007.95 | 20-JAN-08:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 34.81 | 428.29 | 02-APR-17:10 | 3027.37 | 20-JAN-08:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.48 | 42.19 | 01-JAN-08:00 | 1592.13 | 20-JAN-08:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.48 | 42.19 | 01-JAN-08:00 | 1592.13 | 20-JAN-08:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 22.21 | 271.13 | 12-MAR-17:10 | 1916.45 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.80 | 26.71 | 01-JAN-10:20 | 1007.89 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.80 | 26.71 | 01-JAN-10:20 | 1007.89 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 35.16 | 428.29 | 02-APR-17:10 | 3027.38 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.82 | 42.19 | 01-JAN-10:20 | 1592.13 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.82 | 42.19 | 01-JAN-10:20 | 1592.13 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.09 | 271.13 | 16-APR-17:10 | 1916.52 | 20-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.69 | 26.71 | 01-JAN-08:00 | 1007.95 | 20-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.69 | 26.71 | 01-JAN-08:00 | 1007.95 | 20-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 34.79 | 428.29 | 02-APR-17:10 | 3027.37 | 20-JAN-08:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.46 | 42.19 | 01-JAN-08:00 | 1592.13 | 20-JAN-08:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.46 | 42.19 | 01-JAN-08:00 | 1592.13 | 20-JAN-08:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 22.19 | 271.13 | 12-MAR-17:10 | 1916.45 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.78 | 26.71 | 01-JAN-10:10 | 1007.89 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.78 | 26.71 | 01-JAN-10:10 | 1007.89 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 35.21 | 428.29 | 02-APR-17:10 | 3027.38 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 10.87 | 42.19 | 01-JAN-10:20 | 1592.13 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 10.87 | 42.19 | 01-JAN-10:20 | 1592.13 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.11 | 271.13 | 16-APR-17:10 | 1916.52 | 20-JAN-08:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.71 | 26.71 | 01-JAN-08:00 | 1007.95 | 20-JAN-08:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.71 | 26.71 | 01-JAN-08:00 | 1007.95 | 20-JAN-08:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 34.81 | 428.29 | 02-APR-17:10 | 3027.37 | 20-JAN-08:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 10.48 | 42.19 | 01-JAN-08:00 | 1592.13 | 20-JAN-08:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 10.48 | 42.19 | 01-JAN-08:00 | 1592.13 | 20-JAN-08:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 22.21 | 271.13 | 12-MAR-17:10 | 1916.45 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.80 | 26.71 | 01-JAN-10:20 | 1007.89 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.80 | 26.71 | 01-JAN-10:20 | 1007.89 | 20-JAN-08:10 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 646.59 | 243.72 | 01-JAN-00:10 | 127277.53 | 28-JUN-15:00 |
ExteriorEquipment:Electricity | 17.11 | 243.72 | 01-JAN-00:10 | 1241.92 | 20-JAN-08:40 |
Transformer:ExteriorEquipment:Electricity | 17.11 | 243.72 | 01-JAN-00:10 | 1241.92 | 20-JAN-08:40 |
ElectricityPurchased:Facility | 1827.90 | 13162.99 | 04-JUN-17:20 | 198414.89 | 28-JUN-15:10 |
ElectricityPurchased:Plant | 1827.90 | 13162.99 | 04-JUN-17:20 | 198414.89 | 28-JUN-15:10 |
Cogeneration:ElectricityPurchased | 1827.90 | 13162.99 | 04-JUN-17:20 | 198414.89 | 28-JUN-15:10 |
General:Cogeneration:ElectricityPurchased | 1827.90 | 13162.99 | 04-JUN-17:20 | 198414.89 | 28-JUN-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1827.90 | 13162.99 | 04-JUN-17:20 | 198414.89 | 28-JUN-15:10 |
ElectricityNet:Plant | 1827.90 | 13162.99 | 04-JUN-17:20 | 198414.89 | 28-JUN-15:10 |
Cogeneration:ElectricityNet | 1827.90 | 13162.99 | 04-JUN-17:20 | 198414.89 | 28-JUN-15:10 |
General:Cogeneration:ElectricityNet | 1827.90 | 13162.99 | 04-JUN-17:20 | 198414.89 | 28-JUN-15:10 |
Heating:Electricity | 12.78 | 0.00 | 01-JAN-00:10 | 95722.24 | 02-JAN-07:10 |
General:Heating:Electricity | 12.78 | 0.00 | 01-JAN-00:10 | 95722.24 | 02-JAN-07:10 |
Fans:Electricity | 150.28 | 0.00 | 01-JAN-00:10 | 29552.23 | 19-JUN-15:10 |
General:Fans:Electricity | 150.28 | 0.00 | 01-JAN-00:10 | 29552.23 | 19-JUN-15:10 |
ExteriorLights:Electricity | 111.76 | 0.00 | 01-JAN-07:30 | 8596.48 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 111.76 | 0.00 | 01-JAN-07:30 | 8596.48 | 01-JAN-06:10 |
Cooling:Electricity | 466.41 | 0.00 | 01-JAN-00:10 | 98276.13 | 28-JUN-15:10 |
General:Cooling:Electricity | 466.41 | 0.00 | 01-JAN-00:10 | 98276.13 | 28-JUN-15:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 12-JAN-08:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 12-JAN-08:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 12-JAN-08:10 |
WIRED_LTG_ELECTRICITY | 10.23 | 0.00 | 01-JAN-00:10 | 1075.04 | 20-JAN-17:10 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 123.39 | 2003.43 | 24-FEB-17:10 | 37748.58 | 06-DEC-07:10 |
NaturalGas:HVAC | 2.52 | 0.00 | 01-JAN-00:10 | 29427.56 | 06-DEC-07:20 |
Heating:NaturalGas | 2.52 | 0.00 | 01-JAN-00:10 | 29427.56 | 06-DEC-07:20 |
General:Heating:NaturalGas | 2.52 | 0.00 | 01-JAN-00:10 | 29427.56 | 06-DEC-07:20 |
NaturalGas:Plant | 120.86 | 2003.43 | 13-FEB-08:10 | 9907.32 | 02-FEB-12:10 |
WaterSystems:NaturalGas | 120.86 | 2003.43 | 13-FEB-08:10 | 9907.32 | 02-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 120.86 | 2003.43 | 13-FEB-08:10 | 9907.32 | 02-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3289.67 | 0.00 | 01-JAN-00:10 | 443749.28 | 28-JUN-16:00 |
EnergyTransfer:Building | 1610.44 | 0.00 | 01-JAN-00:10 | 187579.05 | 28-JUN-16:00 |
EnergyTransfer:Zone:CORE_BOTTOM | 302.30 | 0.00 | 01-JAN-00:10 | 29546.52 | 05-SEP-08:00 |
Heating:EnergyTransfer | 14.26 | 0.00 | 01-JAN-00:10 | 79835.16 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 14.26 | 0.00 | 01-JAN-00:10 | 79835.16 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1596.18 | 0.00 | 01-JAN-00:10 | 187579.05 | 28-JUN-16:00 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 302.30 | 0.00 | 01-JAN-00:10 | 29546.52 | 05-SEP-08:00 |
General:Cooling:EnergyTransfer | 1596.18 | 0.00 | 01-JAN-00:10 | 187579.05 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 302.30 | 0.00 | 01-JAN-00:10 | 29546.52 | 05-SEP-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 73.13 | 0.00 | 01-JAN-00:10 | 13881.41 | 28-JUN-15:00 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.53 | 0.00 | 01-JAN-00:10 | 7812.66 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.53 | 0.00 | 01-JAN-00:10 | 7812.66 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 67.60 | 0.00 | 01-JAN-00:10 | 13881.41 | 28-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 67.60 | 0.00 | 01-JAN-00:10 | 13881.41 | 28-JUN-15:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 39.19 | 0.00 | 01-JAN-00:10 | 6546.39 | 19-JUN-14:50 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.70 | 0.00 | 01-JAN-00:10 | 2832.26 | 02-JAN-11:40 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.70 | 0.00 | 01-JAN-00:10 | 2832.26 | 02-JAN-11:40 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 37.49 | 0.00 | 01-JAN-00:10 | 6546.39 | 19-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 37.49 | 0.00 | 01-JAN-00:10 | 6546.39 | 19-JUN-14:50 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 44.85 | 0.00 | 01-JAN-00:10 | 6461.33 | 19-JUN-16:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.64 | 0.00 | 01-JAN-00:10 | 2447.69 | 02-JAN-09:00 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.64 | 0.00 | 01-JAN-00:10 | 2447.69 | 02-JAN-09:00 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 44.21 | 0.00 | 01-JAN-00:10 | 6461.33 | 19-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 44.21 | 0.00 | 01-JAN-00:10 | 6461.33 | 19-JUN-16:00 |
EnergyTransfer:Zone:CORE_MID | 207.78 | 0.00 | 01-JAN-00:10 | 21113.85 | 05-SEP-07:50 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 4366.02 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 4366.02 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 207.77 | 0.00 | 01-JAN-00:10 | 21113.85 | 05-SEP-07:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 207.77 | 0.00 | 01-JAN-00:10 | 21113.85 | 05-SEP-07:50 |
EnergyTransfer:Zone:CORE_TOP | 207.40 | 0.00 | 01-JAN-00:10 | 23081.79 | 19-JUN-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.13 | 0.00 | 01-JAN-00:10 | 13648.83 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.13 | 0.00 | 01-JAN-00:10 | 13648.83 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 207.26 | 0.00 | 01-JAN-00:10 | 23081.79 | 19-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 207.26 | 0.00 | 01-JAN-00:10 | 23081.79 | 19-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 57.33 | 0.00 | 01-JAN-00:10 | 8815.30 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.98 | 0.00 | 01-JAN-00:10 | 8353.84 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.98 | 0.00 | 01-JAN-00:10 | 8353.84 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 56.34 | 0.00 | 01-JAN-00:10 | 8815.30 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 56.34 | 0.00 | 01-JAN-00:10 | 8815.30 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 54.72 | 0.00 | 01-JAN-00:10 | 9193.59 | 19-JUN-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.43 | 0.00 | 01-JAN-00:10 | 5388.44 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.43 | 0.00 | 01-JAN-00:10 | 5388.44 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 54.29 | 0.00 | 01-JAN-00:10 | 9193.59 | 19-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 54.29 | 0.00 | 01-JAN-00:10 | 9193.59 | 19-JUN-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 83.04 | 0.00 | 01-JAN-00:10 | 13445.65 | 02-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.54 | 0.00 | 01-JAN-00:10 | 7248.76 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.54 | 0.00 | 01-JAN-00:10 | 7248.76 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 82.50 | 0.00 | 01-JAN-00:10 | 13445.65 | 02-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 82.50 | 0.00 | 01-JAN-00:10 | 13445.65 | 02-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 54.23 | 0.00 | 01-JAN-00:10 | 10112.91 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.61 | 0.00 | 01-JAN-00:10 | 5152.54 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.61 | 0.00 | 01-JAN-00:10 | 5152.54 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 53.62 | 0.00 | 01-JAN-00:10 | 10112.91 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 53.62 | 0.00 | 01-JAN-00:10 | 10112.91 | 26-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 52.83 | 0.00 | 01-JAN-00:10 | 7591.20 | 17-JUL-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.10 | 0.00 | 01-JAN-00:10 | 3801.43 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.10 | 0.00 | 01-JAN-00:10 | 3801.43 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 52.74 | 0.00 | 01-JAN-00:10 | 7591.20 | 17-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 52.74 | 0.00 | 01-JAN-00:10 | 7591.20 | 17-JUL-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 52.85 | 0.00 | 01-JAN-00:10 | 8226.76 | 14-AUG-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.03 | 0.00 | 01-JAN-00:10 | 1880.02 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.03 | 0.00 | 01-JAN-00:10 | 1880.02 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 52.82 | 0.00 | 01-JAN-00:10 | 8226.76 | 14-AUG-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 52.82 | 0.00 | 01-JAN-00:10 | 8226.76 | 14-AUG-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 89.68 | 0.00 | 01-JAN-00:10 | 15314.54 | 28-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.10 | 0.00 | 01-JAN-00:10 | 8975.65 | 06-DEC-07:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.10 | 0.00 | 01-JAN-00:10 | 8975.65 | 06-DEC-07:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 86.58 | 0.00 | 01-JAN-00:10 | 15314.54 | 28-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 86.58 | 0.00 | 01-JAN-00:10 | 15314.54 | 28-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 50.63 | 0.00 | 01-JAN-00:10 | 8382.06 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.04 | 0.00 | 01-JAN-00:10 | 1585.80 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.04 | 0.00 | 01-JAN-00:10 | 1585.80 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 50.59 | 0.00 | 01-JAN-00:10 | 8382.06 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 50.59 | 0.00 | 01-JAN-00:10 | 8382.06 | 26-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 54.28 | 0.00 | 01-JAN-00:10 | 7938.88 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.16 | 0.00 | 01-JAN-00:10 | 4533.45 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.16 | 0.00 | 01-JAN-00:10 | 4533.45 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 54.12 | 0.00 | 01-JAN-00:10 | 7938.88 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 54.12 | 0.00 | 01-JAN-00:10 | 7938.88 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 52.90 | 0.00 | 01-JAN-00:10 | 8931.48 | 19-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.09 | 0.00 | 01-JAN-00:10 | 2922.63 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.09 | 0.00 | 01-JAN-00:10 | 2922.63 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 52.82 | 0.00 | 01-JAN-00:10 | 8931.48 | 19-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 52.82 | 0.00 | 01-JAN-00:10 | 8931.48 | 19-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 81.08 | 0.00 | 01-JAN-00:10 | 12143.56 | 02-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.07 | 0.00 | 01-JAN-00:10 | 3256.93 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.07 | 0.00 | 01-JAN-00:10 | 3256.93 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 81.01 | 0.00 | 01-JAN-00:10 | 12143.56 | 02-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 81.01 | 0.00 | 01-JAN-00:10 | 12143.56 | 02-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 52.22 | 0.00 | 01-JAN-00:10 | 9470.73 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.11 | 0.00 | 01-JAN-00:10 | 2665.32 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.11 | 0.00 | 01-JAN-00:10 | 2665.32 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 52.11 | 0.00 | 01-JAN-00:10 | 9470.73 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 52.11 | 0.00 | 01-JAN-00:10 | 9470.73 | 26-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 38.47 | 0.00 | 01-JAN-00:10 | 5186.02 | 24-JAN-12:20 |
PlantLoopHeatingDemand:Plant | 38.47 | 0.00 | 01-JAN-00:10 | 5186.02 | 24-JAN-12:20 |
WaterSystems:PlantLoopHeatingDemand | 38.47 | 0.00 | 01-JAN-00:10 | 5186.02 | 24-JAN-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 38.47 | 0.00 | 01-JAN-00:10 | 5186.02 | 24-JAN-12:20 |
EnergyTransfer:HVAC | 1640.77 | 0.00 | 01-JAN-00:10 | 291285.03 | 05-SEP-07:40 |
HeatingCoils:EnergyTransfer | 14.80 | 0.00 | 01-JAN-00:10 | 104696.96 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 1625.96 | 0.00 | 01-JAN-00:10 | 291285.03 | 05-SEP-07:40 |
EnergyTransfer:Plant | 38.47 | 0.00 | 01-JAN-00:10 | 5186.02 | 24-JAN-12:20 |
WaterSystems:EnergyTransfer | 38.47 | 0.00 | 01-JAN-00:10 | 5186.02 | 24-JAN-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 38.47 | 0.00 | 01-JAN-00:10 | 5186.02 | 24-JAN-12:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -302.303 | 0.000 | 0.000 | 32.683 | 86.497 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -53.044 |
CORE_MID | 0.000 | 0.000 | 0.003 | -207.775 | 0.000 | 0.000 | 32.922 | 86.497 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -27.072 |
CORE_TOP | 0.000 | 0.000 | 0.132 | -207.264 | 0.000 | 0.000 | 33.338 | 86.497 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -28.128 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.984 | -56.343 | 0.000 | 0.000 | 7.206 | 10.873 | 24.333 | 26.173 | 0.000 | 0.988 | 11.048 | 0.000 | -23.145 | 0.000 | -2.117 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.433 | -54.288 | 0.000 | 0.000 | 4.476 | 6.706 | 15.404 | 44.283 | 0.000 | 0.650 | 0.002 | 0.000 | -14.515 | 0.000 | -1.468 | -1.680 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.538 | -82.501 | 0.000 | 0.000 | 7.033 | 10.477 | 24.332 | 72.832 | 0.000 | 0.965 | 0.001 | 0.000 | -23.063 | 0.000 | -2.328 | -8.286 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.608 | -53.618 | 0.000 | 0.000 | 4.577 | 6.805 | 15.403 | 42.964 | 0.000 | 0.644 | 0.001 | 0.000 | -15.809 | 0.000 | -1.467 | -0.108 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.098 | -52.735 | 0.000 | 0.000 | 7.124 | 10.825 | 24.333 | 26.236 | 0.000 | 0.546 | 9.482 | 0.000 | -24.678 | 0.000 | -1.229 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.026 | -52.820 | 0.000 | 0.000 | 4.429 | 6.688 | 15.404 | 44.310 | 0.000 | 0.350 | 0.001 | 0.000 | -15.855 | 0.000 | -0.875 | -1.656 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 3.096 | -86.580 | 0.000 | 0.000 | 6.997 | 10.457 | 24.332 | 72.976 | 0.000 | 15.177 | 0.001 | 0.000 | -25.308 | 0.000 | -15.941 | -5.206 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.035 | -50.590 | 0.000 | 0.000 | 4.495 | 6.784 | 15.403 | 43.061 | 0.000 | 0.343 | 0.001 | 0.000 | -17.320 | 0.000 | -0.876 | -1.336 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.161 | -54.122 | 0.000 | 0.000 | 7.100 | 10.873 | 24.333 | 26.008 | 0.000 | 0.826 | 11.560 | 0.000 | -24.818 | 0.000 | -1.922 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.086 | -52.818 | 0.000 | 0.000 | 3.286 | 6.706 | 15.404 | 44.185 | 0.000 | 0.548 | 0.001 | 0.000 | -15.391 | 0.000 | -1.316 | -0.690 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.073 | -81.005 | 0.000 | 0.000 | 6.971 | 10.477 | 24.332 | 72.714 | 0.000 | 0.809 | 0.003 | 0.000 | -24.486 | 0.000 | -2.084 | -7.801 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.113 | -52.111 | 0.000 | 0.000 | 4.520 | 6.805 | 15.403 | 42.928 | 0.000 | 0.536 | 0.000 | 0.000 | -16.855 | 0.000 | -1.322 | -0.018 |
TOPFLOOR_PLENUM | 5.528 | -67.599 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.282 | 64.060 | 0.000 | 0.000 | 0.000 | -3.271 | -0.001 |
MIDFLOOR_PLENUM | 1.703 | -37.490 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.285 | 37.983 | 0.000 | 0.000 | 0.000 | -3.481 | -0.000 |
FIRSTFLOOR_PLENUM | 0.639 | -44.212 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.992 | 45.424 | 0.000 | 0.000 | 0.000 | -2.843 | -0.000 |
Total Facility | 7.870 | -149.301 | 6.387 | -1446.872 | 0.000 | 0.000 | 167.158 | 363.967 | 705.434 | 558.670 | 0.000 | 25.941 | 179.567 | 0.000 | -241.245 | 0.000 | -42.540 | -135.026 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 27-JUN-04:02 | 0.00 | 0.00 | 0.00 | -45671.79 | 0.00 | 0.00 | 0.00 | 839.14 | 4405.64 | 0.00 | 0.00 | 0.00 | 40427.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 25-JUL-04:03 | 0.00 | 0.00 | 0.00 | -34664.44 | 0.00 | 0.00 | 0.00 | 839.14 | 2442.06 | 0.00 | 0.00 | 0.00 | 31383.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-04:02 | 0.00 | 0.00 | 0.00 | -38626.17 | 0.00 | 0.00 | 0.00 | 839.14 | 2442.06 | 0.00 | 0.00 | 0.00 | 35344.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-18:01 | 0.00 | 0.00 | 0.00 | -15139.94 | 0.00 | 0.00 | 0.00 | 42.19 | 386.10 | 3778.28 | 0.00 | 559.01 | 10374.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 23-JUL-09:21 | 0.00 | 0.00 | 0.00 | -14741.35 | 0.00 | 0.00 | 13.04 | 26.71 | 302.86 | 8004.62 | 0.00 | 36.38 | 6357.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-13:12 | 0.00 | 0.00 | 0.00 | -18309.77 | 0.00 | 0.00 | 22.30 | 42.19 | 478.41 | 11522.33 | 0.00 | 49.08 | 6195.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 13-AUG-16:51 | 0.00 | 0.00 | 0.00 | -16082.13 | 0.00 | 0.00 | 10.11 | 26.71 | 302.86 | 9079.43 | 0.00 | 391.40 | 6271.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-JUL-18:11 | 0.00 | 0.00 | 0.00 | -12859.23 | 0.00 | 0.00 | 0.00 | 42.19 | 386.10 | 3764.45 | 0.00 | 247.63 | 8418.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 30-JUL-09:31 | 0.00 | 0.00 | 0.00 | -12673.86 | 0.00 | 0.00 | 14.76 | 26.71 | 302.86 | 7799.79 | 0.00 | 24.47 | 4505.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-13:02 | 0.00 | 0.00 | 0.00 | -15437.46 | 0.00 | 0.00 | 23.04 | 42.19 | 478.41 | 11754.56 | 0.00 | 28.45 | 3110.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 25-JUN-17:31 | 0.00 | 0.00 | 0.00 | -14189.69 | 0.00 | 0.00 | 0.00 | 26.71 | 244.42 | 9721.83 | 0.00 | 148.94 | 4047.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-17:32 | 0.00 | 0.00 | 0.00 | -13585.67 | 0.00 | 0.00 | 0.00 | 42.19 | 386.10 | 4496.99 | 0.00 | 449.61 | 8210.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 30-JUL-09:31 | 0.00 | 0.00 | 0.00 | -14015.47 | 0.00 | 0.00 | 13.61 | 26.71 | 302.86 | 7709.77 | 0.00 | 32.62 | 5929.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 25-DEC-14:42 | 0.00 | 0.00 | 0.00 | -15521.43 | 0.00 | 0.00 | 23.93 | 42.19 | 478.41 | 11284.85 | 0.00 | 0.00 | 3708.24 | 0.00 | -0.00 | 0.00 | -16.20 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-17:31 | 0.00 | 0.00 | 0.00 | -15927.32 | 0.00 | 0.00 | 0.00 | 26.71 | 244.42 | 9595.42 | 0.00 | 216.47 | 5844.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-15:00 | 0.00 | -13881.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.65 | 13554.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 19-JUN-14:50 | 0.00 | -6546.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.28 | 6208.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 05-JUL-12:07 | 0.00 | -8082.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.84 | 8016.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-JUL-04:02 | 0.00 | 9934.70 | 0.00 | -231201.60 | 0.00 | 0.00 | 0.00 | 4250.75 | 14333.92 | 0.00 | 0.00 | 373.18 | 206317.91 | 0.00 | -4008.86 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-07:02 | 0.00 | 0.00 | 17524.58 | 0.00 | 0.00 | 0.00 | 910.03 | 2517.53 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23978.06 |
CORE_TOP | 02-JAN-06:11 | 0.00 | 0.00 | 25868.09 | 0.00 | 0.00 | 0.00 | 490.46 | 839.14 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -30223.61 |
PERIMETER_TOP_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 12570.57 | 0.00 | 0.00 | 0.00 | 112.08 | 176.90 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2154.04 | 0.00 | -45.18 | -11298.22 |
PERIMETER_TOP_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 8675.51 | 0.00 | 0.00 | 0.00 | 70.83 | 111.99 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1469.04 | 0.00 | -30.43 | -7762.68 |
PERIMETER_TOP_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 12928.26 | 0.00 | 0.00 | 0.00 | 109.37 | 176.90 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2337.49 | 0.00 | -48.44 | -11466.48 |
PERIMETER_TOP_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 8453.10 | 0.00 | 0.00 | 0.00 | 70.40 | 111.98 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1472.46 | 0.00 | -30.95 | -7535.88 |
PERIMETER_BOT_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 8055.41 | 0.00 | 0.00 | 0.00 | 104.12 | 176.90 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2525.80 | 0.00 | -28.19 | -6420.34 |
PERIMETER_BOT_ZN_2 | 03-JAN-07:03 | 0.00 | 0.00 | 4902.89 | 0.00 | 0.00 | 0.00 | 122.37 | 335.99 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1369.77 | 0.00 | -41.89 | -4353.40 |
PERIMETER_BOT_ZN_1 | 06-DEC-07:10 | 0.00 | 0.00 | 9453.43 | 0.00 | 0.00 | 0.00 | 193.30 | 530.72 | 637.88 | 0.00 | 0.00 | 0.00 | 12918.20 | 0.00 | -3790.95 | 0.00 | -19942.58 | 0.00 |
PERIMETER_BOT_ZN_4 | 03-JAN-07:03 | 0.00 | 0.00 | 4818.99 | 0.00 | 0.00 | 0.00 | 122.37 | 335.97 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1366.59 | 0.00 | -41.94 | -4272.59 |
PERIMETER_MID_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 9690.89 | 0.00 | 0.00 | 0.00 | 105.72 | 176.90 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2464.53 | 0.00 | -43.03 | -8103.83 |
PERIMETER_MID_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 6102.08 | 0.00 | 0.00 | 0.00 | 67.03 | 111.99 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1676.81 | 0.00 | -28.68 | -4979.43 |
PERIMETER_MID_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 9222.74 | 0.00 | 0.00 | 0.00 | 102.76 | 176.90 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2657.48 | 0.00 | -45.56 | -7437.23 |
PERIMETER_MID_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 5865.21 | 0.00 | 0.00 | 0.00 | 66.58 | 111.98 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1673.76 | 0.00 | -29.09 | -4744.72 |
TOPFLOOR_PLENUM | 02-JAN-07:02 | 10405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -89.15 | -10316.18 |
MIDFLOOR_PLENUM | 10-DEC-13:53 | 4896.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -33.08 | -4863.51 |
FIRSTFLOOR_PLENUM | 07-SEP-04:02 | 4091.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7.05 | -4084.47 |
Total Facility | 02-JAN-07:02 | 6069.24 | 5841.16 | 127118.12 | -5841.16 | 0.00 | 0.00 | 4552.62 | 12752.77 | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24898.48 | 0.00 | -17118.20 | -129574.87 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.5984 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.0881 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.9947 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.4055 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.5940 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.3202 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.2992 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4779 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.9974 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4872 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.2970 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5929 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3571 | 3.3571 | 0.8191 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5507 | 2.5507 | 0.7984 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7690 | 2.7690 | 0.8279 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9680 | 0.9680 | 0.1936 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8403 | 0.8403 | 0.1681 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0618 | 1.0618 | 0.2124 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9548 | 0.9548 | 0.1910 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8102 | 0.8102 | 0.1726 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7448 | 0.7448 | 0.1490 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8959 | 0.8959 | 0.1792 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7904 | 0.7904 | 0.1581 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8416 | 0.8416 | 0.1683 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8026 | 0.8026 | 0.1605 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9358 | 0.9358 | 0.1872 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8641 | 0.8641 | 0.1728 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.5984 | 6.0881 | 6.5984 | 1.4779 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.9947 | 5.4055 | 5.9947 | 1.4872 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.5940 | 6.3202 | 6.5940 | 1.5929 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6785 | 1.6785 | 0.8191 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2753 | 1.2753 | 0.7984 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3845 | 1.3845 | 0.8279 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4840 | 0.4840 | 0.1936 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4202 | 0.4202 | 0.1681 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5309 | 0.5309 | 0.2124 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4774 | 0.4774 | 0.1910 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4051 | 0.4051 | 0.1726 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3724 | 0.3724 | 0.1490 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4479 | 0.4479 | 0.1792 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3952 | 0.3952 | 0.1581 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4208 | 0.4208 | 0.1683 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4013 | 0.4013 | 0.1605 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4679 | 0.4679 | 0.1872 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4320 | 0.4320 | 0.1728 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.2992 | 1.4779 | 1.4779 | 1.4779 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.9974 | 1.4872 | 1.4872 | 1.4872 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.2970 | 1.5929 | 1.5929 | 1.5929 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 71.33 |
Number of hours cooling loads not met | 456.17 |
Number of hours not met | 527.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 12.78 | 95722.24 | 2.52 | 29427.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 466.41 | 98276.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 363.97 | 38257.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 111.76 | 8596.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 17.11 | 1241.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 150.28 | 29552.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 120.86 | 9907.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1827.90 |
Natural Gas | 0.00 | 123.39 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1951.29 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 73.05 |
Space Heating | 2.57 |
Space Cooling | 93.62 |
Fans (All) | 30.16 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 366.89 |
Subtotal | 366.89 |
Natural Gas [MJ/m2] | |
Space Heating | 0.51 |
Service Water Heating | 24.26 |
Miscellaneous (All) | 24.77 |
Subtotal | 24.77 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 18.65 |
Space Heating | 0.78 |
Space Cooling | 23.90 |
Fans (All) | 7.70 |
Service Water Heating | 6.19 |
Receptacle Equipment | 36.15 |
Miscellaneous | 6.61 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8574.33 | 185.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8740.50 | 19.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8745.83 | 14.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8653.00 | 107.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8607.33 | 152.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8620.00 | 140.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8584.00 | 176.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8732.67 | 27.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8604.67 | 155.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8607.17 | 152.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8599.17 | 160.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8675.50 | 84.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8620.00 | 140.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8626.50 | 133.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8582.17 | 177.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8527.33 | 232.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8749.17 | 10.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8755.17 | 4.83 | 0.00 | 0.00 | 0.00 |
Min | 8527.33 | 4.83 | 0.00 | 0.00 | 0.00 |
Max | 8755.17 | 232.67 | 0.00 | 0.00 | 0.00 |
Average | 8644.69 | 115.31 | 0.00 | 0.00 | 0.00 |
Sum | 155604.50 | 2075.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128252.33 | 51.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128300.00 | 4.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24885.50 | 23.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 51.67 | 0.00 | 0.00 | 0.00 |
Average | 34138.94 | 4.40 | 0.00 | 0.00 | 0.00 |
Sum | 614500.83 | 79.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8447.50 | 312.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8520.00 | 240.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8594.00 | 166.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8418.83 | 341.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8401.00 | 359.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8406.83 | 353.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8402.00 | 358.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8429.50 | 330.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8380.83 | 379.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8351.17 | 408.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8386.83 | 373.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8359.33 | 400.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8347.83 | 412.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8341.83 | 418.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8347.67 | 412.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8052.33 | 707.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8479.67 | 280.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8486.83 | 273.17 | 0.00 | 0.00 | 0.00 |
Min | 8052.33 | 166.00 | 0.00 | 0.00 | 0.00 |
Max | 8594.00 | 707.67 | 0.00 | 0.00 | 0.00 |
Average | 8397.44 | 362.56 | 0.00 | 0.00 | 0.00 |
Sum | 151154.00 | 6526.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128140.17 | 163.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128204.67 | 99.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128237.33 | 66.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24906.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24906.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24905.50 | 3.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24782.00 | 127.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24881.33 | 27.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24898.67 | 10.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128237.33 | 163.83 | 0.00 | 0.00 | 0.00 |
Average | 34115.38 | 27.95 | 0.00 | 0.00 | 0.00 |
Sum | 614076.83 | 503.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:44
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201921E+11 | 22535.14 | 27-JAN-07:03 | 11.83 | 4.80 | 0.198803E+10 | 2606.69 | 23-JAN-14:09 | 11.83 | 4.80 |
February | 0.164280E+11 | 24371.50 | 01-FEB-07:02 | 5.00 | 3.59 | 0.180330E+10 | 2606.75 | 15-FEB-14:00 | 20.00 | 13.98 |
March | 0.216956E+11 | 27426.17 | 17-MAR-06:03 | 14.30 | 9.49 | 0.215801E+10 | 2606.69 | 17-MAR-09:00 | 21.60 | 14.25 |
April | 0.256198E+11 | 41463.81 | 26-APR-05:12 | 19.73 | 10.26 | 0.191774E+10 | 2606.67 | 03-APR-09:30 | 19.73 | 10.26 |
May | 0.287825E+11 | 44357.27 | 30-MAY-05:12 | 18.00 | 8.93 | 0.207790E+10 | 2606.65 | 12-MAY-09:09 | 18.00 | 8.93 |
June | 0.309875E+11 | 45681.12 | 27-JUN-04:02 | 25.00 | 10.76 | 0.207151E+10 | 2606.66 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.303570E+11 | 45245.85 | 26-JUL-04:03 | 25.00 | 16.63 | 0.192549E+10 | 2606.70 | 28-JUL-13:50 | 29.50 | 20.43 |
August | 0.319537E+11 | 44772.71 | 09-AUG-04:03 | 26.00 | 19.09 | 0.216105E+10 | 2606.77 | 29-AUG-13:39 | 28.67 | 21.18 |
September | 0.290389E+11 | 44619.26 | 27-SEP-05:12 | 20.00 | 13.69 | 0.192046E+10 | 2606.66 | 15-SEP-09:09 | 20.00 | 13.69 |
October | 0.264468E+11 | 42590.76 | 10-OCT-06:02 | 16.50 | 11.11 | 0.199565E+10 | 2606.67 | 17-OCT-09:30 | 25.00 | 10.00 |
November | 0.222888E+11 | 42248.27 | 13-NOV-07:02 | 16.00 | 16.00 | 0.197422E+10 | 2606.77 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.185128E+11 | 21496.22 | 28-DEC-17:00 | 18.60 | 7.88 | 0.191814E+10 | 2606.65 | 13-DEC-10:09 | 18.60 | 7.88 |
Annual Sum or Average | 0.302303E+12 | 0.239115E+11 | ||||||||
Minimum of Months | 0.164280E+11 | 21496.22 | 5.00 | 3.59 | 0.180330E+10 | 2606.65 | 11.83 | 4.80 | ||
Maximum of Months | 0.319537E+11 | 45681.12 | 26.00 | 19.09 | 0.216105E+10 | 2606.77 | 33.17 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211246E+10 | 6194.94 | 31-JAN-15:30 | 28.50 | 10.89 | 0.00 | 0.00 | 01-JAN-00:10 | 28.50 | 10.89 |
February | 0.114788E+10 | 4500.37 | 23-FEB-14:30 | 18.00 | 10.57 | 0.00 | 0.00 | 01-FEB-00:10 | 18.00 | 10.57 |
March | 0.245133E+10 | 7381.33 | 16-MAR-15:30 | 28.80 | 13.83 | 0.00 | 0.00 | 01-MAR-00:10 | 28.80 | 13.83 |
April | 0.648386E+10 | 11490.18 | 14-APR-14:50 | 34.83 | 14.49 | 0.00 | 0.00 | 01-APR-00:10 | 34.83 | 14.49 |
May | 0.829605E+10 | 11425.57 | 19-MAY-14:20 | 36.00 | 14.39 | 0.00 | 0.00 | 01-MAY-00:10 | 36.00 | 14.39 |
June | 0.114753E+11 | 13881.41 | 28-JUN-15:00 | 42.00 | 19.34 | 0.00 | 0.00 | 01-JUN-00:10 | 42.00 | 19.34 |
July | 0.100777E+11 | 13056.10 | 20-JUL-14:20 | 39.33 | 20.22 | 0.00 | 0.00 | 01-JUL-00:10 | 39.33 | 20.22 |
August | 0.990825E+10 | 13128.92 | 09-AUG-14:00 | 38.00 | 21.22 | 0.00 | 0.00 | 01-AUG-00:10 | 38.00 | 21.22 |
September | 0.765801E+10 | 12273.14 | 07-SEP-15:00 | 37.20 | 19.77 | 0.00 | 0.00 | 01-SEP-00:10 | 37.20 | 19.77 |
October | 0.454162E+10 | 11135.74 | 02-OCT-14:20 | 35.00 | 19.60 | 0.00 | 0.00 | 01-OCT-00:10 | 35.00 | 19.60 |
November | 0.220260E+10 | 7550.07 | 01-NOV-15:30 | 28.50 | 15.96 | 0.00 | 0.00 | 01-NOV-00:10 | 28.50 | 15.96 |
December | 0.124458E+10 | 4998.48 | 22-DEC-16:00 | 25.00 | 10.09 | 0.00 | 0.00 | 01-DEC-00:10 | 25.00 | 10.09 |
Annual Sum or Average | 0.675996E+11 | 0.00 | ||||||||
Minimum of Months | 0.114788E+10 | 4500.37 | 18.00 | 10.09 | 0.00 | 0.00 | 18.00 | 10.09 | ||
Maximum of Months | 0.114753E+11 | 13881.41 | 42.00 | 21.22 | 0.00 | 0.00 | 42.00 | 21.22 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.791509E+09 | 2154.26 | 27-JAN-16:40 | 26.33 | 9.40 | 0.00 | 0.00 | 01-JAN-00:10 | 26.33 | 9.40 |
February | 0.500528E+09 | 1966.10 | 09-FEB-07:02 | 6.17 | 4.62 | 0.00 | 0.00 | 01-FEB-00:10 | 6.17 | 4.62 |
March | 0.101775E+10 | 3153.39 | 29-MAR-06:01 | 3.08 | 0.06 | 0.00 | 0.00 | 01-MAR-00:10 | 3.08 | 0.06 |
April | 0.331844E+10 | 4781.77 | 25-APR-15:30 | 33.00 | 14.95 | 0.00 | 0.00 | 01-APR-00:10 | 33.00 | 14.95 |
May | 0.456384E+10 | 5286.22 | 08-MAY-16:00 | 34.00 | 13.77 | 0.00 | 0.00 | 01-MAY-00:10 | 34.00 | 13.77 |
June | 0.639792E+10 | 6546.39 | 19-JUN-14:50 | 38.17 | 17.97 | 0.00 | 0.00 | 01-JUN-00:10 | 38.17 | 17.97 |
July | 0.591555E+10 | 6356.63 | 31-JUL-16:00 | 39.00 | 19.54 | 0.00 | 0.00 | 01-JUL-00:10 | 39.00 | 19.54 |
August | 0.590506E+10 | 6502.07 | 14-AUG-15:10 | 38.00 | 19.83 | 0.00 | 0.00 | 01-AUG-00:10 | 38.00 | 19.83 |
September | 0.485999E+10 | 6154.80 | 05-SEP-15:50 | 33.62 | 20.30 | 0.00 | 0.00 | 01-SEP-00:10 | 33.62 | 20.30 |
October | 0.271924E+10 | 5926.71 | 02-OCT-15:30 | 34.50 | 19.17 | 0.00 | 0.00 | 01-OCT-00:10 | 34.50 | 19.17 |
November | 0.107350E+10 | 3177.14 | 01-NOV-16:00 | 28.00 | 15.72 | 0.00 | 0.00 | 01-NOV-00:10 | 28.00 | 15.72 |
December | 0.427057E+09 | 2801.07 | 14-DEC-07:01 | 1.33 | -1.0 | 0.00 | 0.00 | 01-DEC-00:10 | 1.33 | -1.0 |
Annual Sum or Average | 0.374904E+11 | 0.00 | ||||||||
Minimum of Months | 0.427057E+09 | 1966.10 | 1.33 | -1.0 | 0.00 | 0.00 | 1.33 | -1.0 | ||
Maximum of Months | 0.639792E+10 | 6546.39 | 39.00 | 20.30 | 0.00 | 0.00 | 39.00 | 20.30 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153593E+10 | 3076.86 | 27-JAN-17:00 | 26.00 | 9.22 | 0.00 | 0.00 | 01-JAN-00:10 | 26.00 | 9.22 |
February | 0.936928E+09 | 2870.89 | 09-FEB-07:02 | 6.17 | 4.62 | 0.00 | 0.00 | 01-FEB-00:10 | 6.17 | 4.62 |
March | 0.164510E+10 | 3308.30 | 28-MAR-06:01 | 3.90 | 0.38 | 0.00 | 0.00 | 01-MAR-00:10 | 3.90 | 0.38 |
April | 0.384188E+10 | 5169.08 | 25-APR-16:00 | 33.00 | 14.80 | 0.00 | 0.00 | 01-APR-00:10 | 33.00 | 14.80 |
May | 0.495543E+10 | 6070.93 | 08-MAY-12:07 | 32.17 | 13.12 | 0.00 | 0.00 | 01-MAY-00:10 | 32.17 | 13.12 |
June | 0.655018E+10 | 7799.73 | 19-JUN-12:07 | 37.17 | 17.20 | 0.00 | 0.00 | 01-JUN-00:10 | 37.17 | 17.20 |
July | 0.621810E+10 | 8082.03 | 05-JUL-12:07 | 36.17 | 15.62 | 0.00 | 0.00 | 01-JUL-00:10 | 36.17 | 15.62 |
August | 0.636855E+10 | 7521.83 | 09-AUG-12:09 | 37.33 | 20.89 | 0.00 | 0.00 | 01-AUG-00:10 | 37.33 | 20.89 |
September | 0.554123E+10 | 7126.14 | 08-SEP-17:08 | 36.52 | 20.72 | 0.00 | 0.00 | 01-SEP-00:10 | 36.52 | 20.72 |
October | 0.367804E+10 | 6180.35 | 04-OCT-17:07 | 33.83 | 17.44 | 0.00 | 0.00 | 01-OCT-00:10 | 33.83 | 17.44 |
November | 0.200486E+10 | 3954.84 | 02-NOV-15:50 | 26.00 | 15.20 | 0.00 | 0.00 | 01-NOV-00:10 | 26.00 | 15.20 |
December | 0.935194E+09 | 3532.88 | 05-DEC-07:01 | -0.5 | -4.0 | 0.00 | 0.00 | 01-DEC-00:10 | -0.5 | -4.0 |
Annual Sum or Average | 0.442114E+11 | 0.00 | ||||||||
Minimum of Months | 0.935194E+09 | 2870.89 | -0.5 | -4.0 | 0.00 | 0.00 | -0.5 | -4.0 | ||
Maximum of Months | 0.655018E+10 | 8082.03 | 37.33 | 20.89 | 0.00 | 0.00 | 37.33 | 20.89 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122613E+11 | 14677.56 | 27-JAN-17:00 | 26.00 | 9.22 | 0.194412E+10 | 2606.63 | 06-JAN-14:09 | 26.00 | 9.22 |
February | 0.988207E+10 | 13379.38 | 01-FEB-17:00 | 15.00 | 6.61 | 0.175408E+10 | 2606.65 | 15-FEB-14:00 | 20.00 | 13.98 |
March | 0.133676E+11 | 15436.61 | 17-MAR-16:00 | 26.60 | 14.13 | 0.212974E+10 | 2606.67 | 14-MAR-13:50 | 26.60 | 14.13 |
April | 0.181801E+11 | 27409.20 | 26-APR-05:12 | 19.73 | 10.26 | 0.191173E+10 | 2606.66 | 03-APR-09:20 | 19.73 | 10.26 |
May | 0.211480E+11 | 34174.48 | 30-MAY-05:12 | 18.00 | 8.93 | 0.207452E+10 | 2606.64 | 12-MAY-09:09 | 18.00 | 8.93 |
June | 0.238092E+11 | 34498.60 | 12-JUN-05:12 | 20.33 | 10.58 | 0.206957E+10 | 2606.65 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.231278E+11 | 34669.51 | 25-JUL-04:03 | 26.00 | 17.51 | 0.192318E+10 | 2606.69 | 05-JUL-09:09 | 26.00 | 17.51 |
August | 0.236947E+11 | 34583.65 | 21-AUG-04:02 | 25.00 | 16.17 | 0.215862E+10 | 2606.69 | 28-AUG-09:20 | 32.00 | 20.57 |
September | 0.208704E+11 | 34595.13 | 19-SEP-04:02 | 26.10 | 12.72 | 0.191796E+10 | 2606.67 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.174557E+11 | 33777.97 | 02-OCT-04:02 | 26.00 | 17.05 | 0.198573E+10 | 2606.66 | 03-OCT-13:30 | 33.00 | 20.21 |
November | 0.133235E+11 | 16207.98 | 02-NOV-16:00 | 26.00 | 15.13 | 0.195167E+10 | 2606.71 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.106543E+11 | 13466.01 | 22-DEC-17:00 | 24.00 | 9.52 | 0.185163E+10 | 2606.56 | 22-DEC-10:09 | 24.00 | 9.52 |
Annual Sum or Average | 0.207775E+12 | 0.236725E+11 | ||||||||
Minimum of Months | 0.988207E+10 | 13379.38 | 15.00 | 6.61 | 0.175408E+10 | 2606.56 | 18.00 | 8.93 | ||
Maximum of Months | 0.238092E+11 | 34669.51 | 26.60 | 17.51 | 0.215862E+10 | 2606.71 | 38.17 | 20.57 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109357E+11 | 14621.04 | 27-JAN-17:00 | 26.00 | 9.22 | 0.187331E+10 | 2606.60 | 26-JAN-14:09 | 26.00 | 9.22 |
February | 0.900027E+10 | 12740.73 | 22-FEB-17:00 | 20.00 | 11.26 | 0.167868E+10 | 2606.56 | 03-FEB-14:00 | 20.00 | 11.26 |
March | 0.124785E+11 | 16753.71 | 17-MAR-16:00 | 26.60 | 14.13 | 0.206930E+10 | 2606.66 | 14-MAR-13:50 | 26.60 | 14.13 |
April | 0.182947E+11 | 20154.09 | 25-APR-16:00 | 33.00 | 14.80 | 0.190326E+10 | 2606.65 | 06-APR-09:30 | 33.00 | 14.80 |
May | 0.218956E+11 | 26996.85 | 08-MAY-06:03 | 20.50 | 9.41 | 0.207196E+10 | 2606.64 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.258611E+11 | 37819.07 | 27-JUN-04:02 | 25.00 | 10.76 | 0.206943E+10 | 2606.65 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.248963E+11 | 38622.39 | 24-JUL-04:02 | 25.42 | 19.04 | 0.192370E+10 | 2606.71 | 21-JUL-09:09 | 25.42 | 19.04 |
August | 0.250717E+11 | 38453.38 | 21-AUG-04:02 | 25.00 | 16.17 | 0.215837E+10 | 2606.70 | 18-AUG-09:09 | 25.00 | 16.17 |
September | 0.214391E+11 | 38102.41 | 08-SEP-04:02 | 25.92 | 19.60 | 0.191680E+10 | 2606.66 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.163458E+11 | 37804.00 | 02-OCT-04:02 | 26.00 | 17.05 | 0.196168E+10 | 2606.64 | 03-OCT-13:30 | 33.00 | 20.21 |
November | 0.117576E+11 | 17075.57 | 01-NOV-16:00 | 28.00 | 15.72 | 0.189721E+10 | 2606.69 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.928734E+10 | 13108.94 | 22-DEC-17:00 | 24.00 | 9.52 | 0.173273E+10 | 2606.59 | 22-DEC-14:39 | 24.00 | 9.52 |
Annual Sum or Average | 0.207264E+12 | 0.232564E+11 | ||||||||
Minimum of Months | 0.900027E+10 | 12740.73 | 20.00 | 9.22 | 0.167868E+10 | 2606.56 | 18.00 | 9.22 | ||
Maximum of Months | 0.258611E+11 | 38622.39 | 33.00 | 19.60 | 0.215837E+10 | 2606.71 | 33.17 | 20.21 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193589E+10 | 3059.27 | 31-JAN-16:30 | 29.00 | 10.73 | 0.363175E+09 | 549.48 | 27-JAN-14:09 | 29.00 | 10.73 |
February | 0.151131E+10 | 2207.47 | 22-FEB-16:30 | 20.50 | 11.47 | 0.320345E+09 | 549.46 | 22-FEB-14:00 | 20.50 | 11.47 |
March | 0.245419E+10 | 4385.20 | 16-MAR-16:00 | 28.80 | 13.95 | 0.407237E+09 | 549.50 | 21-MAR-13:39 | 25.33 | 12.85 |
April | 0.471698E+10 | 6936.55 | 30-APR-16:22 | 32.50 | 11.88 | 0.395328E+09 | 549.50 | 06-APR-09:30 | 32.50 | 11.88 |
May | 0.648411E+10 | 11574.46 | 07-MAY-17:32 | 35.33 | 14.08 | 0.436086E+09 | 549.50 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.921017E+10 | 15005.35 | 25-JUN-18:21 | 37.00 | 14.68 | 0.437058E+09 | 549.50 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.843246E+10 | 15140.06 | 16-JUL-18:01 | 34.83 | 21.45 | 0.406515E+09 | 549.51 | 21-JUL-09:09 | 31.17 | 20.71 |
August | 0.795294E+10 | 14988.82 | 13-AUG-16:11 | 38.00 | 20.37 | 0.455351E+09 | 549.51 | 18-AUG-09:09 | 32.50 | 20.95 |
September | 0.637259E+10 | 13548.07 | 17-SEP-13:43 | 34.50 | 17.78 | 0.403626E+09 | 549.50 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.375436E+10 | 10903.55 | 02-OCT-04:02 | 26.00 | 17.05 | 0.397554E+09 | 549.51 | 03-OCT-13:20 | 33.00 | 20.21 |
November | 0.213809E+10 | 4356.30 | 01-NOV-15:30 | 28.50 | 15.96 | 0.374743E+09 | 549.49 | 16-NOV-14:50 | 18.00 | 12.11 |
December | 0.137999E+10 | 2257.90 | 22-DEC-16:50 | 24.17 | 9.62 | 0.327784E+09 | 548.13 | 22-DEC-14:00 | 24.17 | 9.62 |
Annual Sum or Average | 0.563431E+11 | 0.472480E+10 | ||||||||
Minimum of Months | 0.137999E+10 | 2207.47 | 20.50 | 9.62 | 0.320345E+09 | 548.13 | 18.00 | 9.62 | ||
Maximum of Months | 0.921017E+10 | 15140.06 | 38.00 | 21.45 | 0.455351E+09 | 549.51 | 33.17 | 20.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196923E+10 | 2994.13 | 27-JAN-10:30 | 21.00 | 7.83 | 0.247209E+09 | 347.87 | 24-JAN-14:39 | 21.00 | 7.83 |
February | 0.150689E+10 | 3215.34 | 23-FEB-10:30 | 15.00 | 11.05 | 0.218167E+09 | 347.87 | 23-FEB-10:09 | 15.00 | 11.05 |
March | 0.253237E+10 | 4619.04 | 23-MAR-10:30 | 22.70 | 10.73 | 0.271146E+09 | 347.88 | 14-MAR-13:50 | 22.70 | 10.73 |
April | 0.518688E+10 | 11074.94 | 30-APR-09:42 | 27.50 | 10.26 | 0.254295E+09 | 347.90 | 03-APR-09:20 | 27.50 | 10.26 |
May | 0.652221E+10 | 11818.79 | 07-MAY-09:32 | 27.67 | 12.09 | 0.276963E+09 | 348.16 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.834977E+10 | 13790.73 | 18-JUN-09:02 | 32.33 | 17.55 | 0.276859E+09 | 348.19 | 08-JUN-09:00 | 32.33 | 17.55 |
July | 0.759000E+10 | 14742.43 | 23-JUL-09:21 | 32.50 | 22.15 | 0.257538E+09 | 348.14 | 05-JUL-09:00 | 32.50 | 22.15 |
August | 0.738597E+10 | 13720.36 | 13-AUG-09:32 | 32.67 | 21.08 | 0.288453E+09 | 348.18 | 01-AUG-09:00 | 32.67 | 21.08 |
September | 0.575685E+10 | 11975.31 | 10-SEP-10:22 | 32.45 | 19.22 | 0.255808E+09 | 348.38 | 08-SEP-09:50 | 32.45 | 19.22 |
October | 0.388971E+10 | 8794.31 | 15-OCT-09:43 | 25.67 | 10.35 | 0.259900E+09 | 347.90 | 17-OCT-09:20 | 24.67 | 9.84 |
November | 0.215085E+10 | 3932.94 | 01-NOV-10:20 | 23.67 | 16.07 | 0.249793E+09 | 347.89 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.144670E+10 | 1995.43 | 25-DEC-15:52 | 26.00 | 12.00 | 0.221176E+09 | 347.87 | 22-DEC-14:50 | 26.00 | 12.00 |
Annual Sum or Average | 0.542874E+11 | 0.307731E+10 | ||||||||
Minimum of Months | 0.144670E+10 | 1995.43 | 15.00 | 7.83 | 0.218167E+09 | 347.87 | 15.00 | 7.83 | ||
Maximum of Months | 0.834977E+10 | 14742.43 | 32.67 | 22.15 | 0.288453E+09 | 348.38 | 32.67 | 22.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.635060E+10 | 17384.80 | 29-JAN-14:22 | 24.00 | 9.34 | 0.400181E+09 | 549.70 | 31-JAN-14:00 | 28.00 | 11.02 |
February | 0.349390E+10 | 9504.95 | 28-FEB-14:10 | 18.17 | 7.92 | 0.351446E+09 | 549.50 | 13-FEB-14:00 | 18.17 | 7.92 |
March | 0.439210E+10 | 8999.95 | 16-MAR-13:40 | 27.53 | 13.09 | 0.424287E+09 | 549.52 | 09-MAR-14:00 | 27.53 | 13.09 |
April | 0.686323E+10 | 16505.29 | 23-APR-13:23 | 33.00 | 12.49 | 0.396303E+09 | 549.81 | 24-APR-13:00 | 33.00 | 13.29 |
May | 0.716979E+10 | 13603.12 | 07-MAY-15:32 | 35.67 | 14.01 | 0.435061E+09 | 549.50 | 16-MAY-13:00 | 36.00 | 15.44 |
June | 0.897964E+10 | 16026.89 | 04-JUN-16:41 | 38.00 | 16.06 | 0.436632E+09 | 549.50 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.868845E+10 | 16342.40 | 16-JUL-17:21 | 36.50 | 21.23 | 0.406297E+09 | 549.76 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.933863E+10 | 16640.60 | 13-AUG-16:11 | 38.00 | 20.37 | 0.455354E+09 | 549.84 | 09-AUG-13:00 | 38.00 | 20.37 |
September | 0.885099E+10 | 16982.20 | 10-SEP-13:02 | 34.50 | 19.00 | 0.404054E+09 | 555.52 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.777314E+10 | 18309.36 | 09-OCT-13:12 | 31.33 | 17.32 | 0.409506E+09 | 555.98 | 02-OCT-13:09 | 31.33 | 17.32 |
November | 0.591609E+10 | 16996.72 | 19-NOV-14:12 | 26.33 | 11.25 | 0.400770E+09 | 549.71 | 14-NOV-14:00 | 26.33 | 11.25 |
December | 0.468572E+10 | 17358.55 | 25-DEC-14:32 | 26.00 | 11.71 | 0.377164E+09 | 549.66 | 22-DEC-14:50 | 26.00 | 11.71 |
Annual Sum or Average | 0.825023E+11 | 0.489705E+10 | ||||||||
Minimum of Months | 0.349390E+10 | 8999.95 | 18.17 | 7.92 | 0.351446E+09 | 549.50 | 18.17 | 7.92 | ||
Maximum of Months | 0.933863E+10 | 18309.36 | 38.00 | 21.23 | 0.455354E+09 | 555.98 | 38.17 | 20.37 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241808E+10 | 7322.82 | 29-JAN-16:22 | 24.50 | 9.40 | 0.229247E+09 | 347.85 | 24-JAN-14:50 | 24.50 | 9.40 |
February | 0.166975E+10 | 6017.75 | 22-FEB-16:30 | 20.50 | 11.47 | 0.201856E+09 | 347.83 | 23-FEB-14:00 | 18.00 | 10.35 |
March | 0.269299E+10 | 8298.38 | 18-MAR-17:08 | 26.92 | 12.85 | 0.252598E+09 | 347.85 | 09-MAR-14:00 | 26.92 | 12.85 |
April | 0.519933E+10 | 15252.17 | 23-APR-16:42 | 33.05 | 12.67 | 0.247181E+09 | 347.85 | 06-APR-09:39 | 33.05 | 12.67 |
May | 0.634409E+10 | 15509.64 | 28-MAY-17:12 | 32.67 | 12.64 | 0.274137E+09 | 347.85 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.810420E+10 | 16028.95 | 25-JUN-17:41 | 38.00 | 15.02 | 0.276218E+09 | 347.85 | 19-JUN-13:00 | 38.00 | 15.02 |
July | 0.689107E+10 | 16061.00 | 16-JUL-17:21 | 36.50 | 21.23 | 0.256918E+09 | 347.86 | 21-JUL-09:09 | 31.17 | 20.71 |
August | 0.679129E+10 | 16082.25 | 13-AUG-16:51 | 38.00 | 19.94 | 0.287676E+09 | 347.86 | 18-AUG-09:09 | 32.50 | 20.95 |
September | 0.545968E+10 | 15149.11 | 04-SEP-15:52 | 31.60 | 21.45 | 0.254491E+09 | 347.85 | 13-SEP-09:09 | 27.98 | 18.77 |
October | 0.387982E+10 | 15749.58 | 09-OCT-15:52 | 33.00 | 17.36 | 0.248126E+09 | 347.86 | 03-OCT-13:20 | 33.00 | 17.36 |
November | 0.254526E+10 | 7467.59 | 01-NOV-16:00 | 28.00 | 15.72 | 0.234809E+09 | 347.85 | 16-NOV-14:00 | 18.00 | 12.18 |
December | 0.162326E+10 | 6177.13 | 22-DEC-16:30 | 24.50 | 9.81 | 0.212006E+09 | 347.85 | 22-DEC-14:50 | 24.50 | 9.81 |
Annual Sum or Average | 0.536188E+11 | 0.297526E+10 | ||||||||
Minimum of Months | 0.162326E+10 | 6017.75 | 20.50 | 9.40 | 0.201856E+09 | 347.83 | 18.00 | 9.40 | ||
Maximum of Months | 0.810420E+10 | 16082.25 | 38.00 | 21.45 | 0.287676E+09 | 347.86 | 38.00 | 20.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193916E+10 | 2312.16 | 27-JAN-16:30 | 26.50 | 9.48 | 0.374290E+09 | 549.47 | 27-JAN-14:50 | 26.50 | 9.48 |
February | 0.152377E+10 | 1558.53 | 22-FEB-16:40 | 20.33 | 11.40 | 0.324750E+09 | 532.15 | 22-FEB-14:30 | 20.33 | 11.40 |
March | 0.207899E+10 | 2982.43 | 20-MAR-14:30 | 27.70 | 14.31 | 0.408264E+09 | 549.49 | 21-MAR-13:00 | 25.50 | 12.96 |
April | 0.373218E+10 | 5154.14 | 25-APR-15:00 | 33.00 | 15.10 | 0.398354E+09 | 549.49 | 06-APR-09:30 | 33.00 | 15.10 |
May | 0.511942E+10 | 5770.64 | 08-MAY-15:20 | 34.00 | 13.77 | 0.436243E+09 | 549.50 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.771357E+10 | 12810.04 | 25-JUN-17:31 | 38.00 | 15.08 | 0.436803E+09 | 549.50 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.782381E+10 | 12859.38 | 16-JUL-18:11 | 33.67 | 21.26 | 0.406452E+09 | 549.51 | 28-JUL-13:50 | 29.50 | 20.43 |
August | 0.772956E+10 | 12593.67 | 27-AUG-17:41 | 39.17 | 18.06 | 0.455654E+09 | 549.52 | 29-AUG-13:39 | 28.67 | 21.18 |
September | 0.678504E+10 | 11144.24 | 17-SEP-16:52 | 34.40 | 17.12 | 0.404815E+09 | 549.50 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.410015E+10 | 9611.64 | 01-OCT-13:53 | 37.00 | 19.01 | 0.413219E+09 | 549.50 | 05-OCT-09:20 | 27.00 | 16.87 |
November | 0.241854E+10 | 4111.07 | 02-NOV-14:00 | 27.00 | 15.44 | 0.397473E+09 | 549.50 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.177145E+10 | 1986.55 | 24-DEC-15:43 | 23.17 | 10.23 | 0.350041E+09 | 549.46 | 01-DEC-14:00 | 23.17 | 10.23 |
Annual Sum or Average | 0.527356E+11 | 0.480636E+10 | ||||||||
Minimum of Months | 0.152377E+10 | 1558.53 | 20.33 | 9.48 | 0.324750E+09 | 532.15 | 20.00 | 9.48 | ||
Maximum of Months | 0.782381E+10 | 12859.38 | 39.17 | 21.26 | 0.455654E+09 | 549.52 | 33.17 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202378E+10 | 2896.93 | 27-JAN-10:30 | 21.00 | 7.83 | 0.254276E+09 | 347.87 | 09-JAN-10:09 | 21.00 | 7.83 |
February | 0.150812E+10 | 2600.43 | 23-FEB-10:30 | 15.00 | 11.05 | 0.222429E+09 | 347.87 | 23-FEB-10:09 | 15.00 | 11.05 |
March | 0.218946E+10 | 3687.78 | 23-MAR-10:30 | 22.70 | 10.73 | 0.274536E+09 | 347.87 | 16-MAR-09:00 | 22.70 | 10.73 |
April | 0.459288E+10 | 11640.90 | 23-APR-09:52 | 27.00 | 10.00 | 0.255124E+09 | 347.89 | 28-APR-09:00 | 25.00 | 10.77 |
May | 0.566607E+10 | 12032.12 | 29-MAY-09:52 | 28.00 | 12.49 | 0.277146E+09 | 347.88 | 12-MAY-09:09 | 28.00 | 12.49 |
June | 0.740009E+10 | 12548.76 | 25-JUN-09:31 | 32.33 | 14.93 | 0.276921E+09 | 348.12 | 02-JUN-09:50 | 32.33 | 14.93 |
July | 0.725477E+10 | 12673.43 | 30-JUL-09:31 | 31.00 | 18.77 | 0.257672E+09 | 348.02 | 13-JUL-09:50 | 31.00 | 18.77 |
August | 0.736497E+10 | 12303.75 | 27-AUG-11:02 | 37.17 | 17.45 | 0.288812E+09 | 348.08 | 15-AUG-09:00 | 37.17 | 17.45 |
September | 0.613917E+10 | 12205.97 | 04-SEP-09:42 | 26.33 | 22.09 | 0.256492E+09 | 348.08 | 06-SEP-09:30 | 30.25 | 19.77 |
October | 0.437515E+10 | 8596.57 | 15-OCT-09:43 | 25.67 | 10.35 | 0.264535E+09 | 347.89 | 17-OCT-09:30 | 25.00 | 10.00 |
November | 0.253481E+10 | 4103.94 | 02-NOV-08:40 | 21.00 | 14.47 | 0.258861E+09 | 347.89 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.177093E+10 | 2490.84 | 01-DEC-10:30 | 18.50 | 8.87 | 0.237240E+09 | 347.86 | 01-DEC-10:00 | 20.00 | 9.50 |
Annual Sum or Average | 0.528202E+11 | 0.312404E+10 | ||||||||
Minimum of Months | 0.150812E+10 | 2490.84 | 15.00 | 7.83 | 0.222429E+09 | 347.86 | 15.00 | 7.83 | ||
Maximum of Months | 0.740009E+10 | 12673.43 | 37.17 | 22.09 | 0.288812E+09 | 348.12 | 37.17 | 19.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.564914E+10 | 14662.07 | 29-JAN-14:22 | 24.00 | 9.34 | 0.404543E+09 | 549.63 | 30-JAN-14:50 | 24.83 | 9.61 |
February | 0.222373E+10 | 8674.74 | 27-FEB-13:06 | 16.17 | 9.56 | 0.341202E+09 | 549.50 | 13-FEB-14:00 | 16.17 | 9.56 |
March | 0.317036E+10 | 10346.24 | 16-MAR-16:10 | 28.72 | 13.89 | 0.415188E+09 | 549.51 | 16-MAR-13:00 | 28.72 | 13.89 |
April | 0.660565E+10 | 12861.36 | 14-APR-16:10 | 35.00 | 14.57 | 0.397196E+09 | 609.72 | 14-APR-12:09 | 35.00 | 14.57 |
May | 0.748973E+10 | 13263.48 | 15-MAY-17:00 | 37.00 | 15.57 | 0.436450E+09 | 608.73 | 18-MAY-12:09 | 34.00 | 13.67 |
June | 0.101833E+11 | 15314.54 | 28-JUN-17:00 | 42.00 | 19.33 | 0.444411E+09 | 714.09 | 28-JUN-12:09 | 42.00 | 19.33 |
July | 0.102874E+11 | 14360.70 | 20-JUL-17:00 | 39.00 | 20.23 | 0.412655E+09 | 698.18 | 12-JUL-12:09 | 39.00 | 20.23 |
August | 0.115115E+11 | 15081.94 | 25-AUG-17:00 | 41.00 | 17.61 | 0.464436E+09 | 750.73 | 25-AUG-12:09 | 41.00 | 17.61 |
September | 0.108244E+11 | 14576.10 | 04-SEP-13:02 | 30.18 | 21.78 | 0.413626E+09 | 702.04 | 07-SEP-12:09 | 36.10 | 19.38 |
October | 0.857893E+10 | 15437.12 | 09-OCT-13:02 | 31.17 | 17.33 | 0.419493E+09 | 686.02 | 02-OCT-12:09 | 31.17 | 17.33 |
November | 0.585417E+10 | 14300.00 | 05-NOV-13:32 | 22.00 | 8.04 | 0.406217E+09 | 566.26 | 20-NOV-14:30 | 27.00 | 11.68 |
December | 0.420369E+10 | 14311.42 | 25-DEC-12:13 | 23.67 | 10.77 | 0.377911E+09 | 549.74 | 29-DEC-14:50 | 19.83 | 9.07 |
Annual Sum or Average | 0.865820E+11 | 0.493333E+10 | ||||||||
Minimum of Months | 0.222373E+10 | 8674.74 | 16.17 | 8.04 | 0.341202E+09 | 549.50 | 16.17 | 9.07 | ||
Maximum of Months | 0.115115E+11 | 15437.12 | 42.00 | 21.78 | 0.464436E+09 | 750.73 | 42.00 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231239E+10 | 5511.27 | 29-JAN-16:22 | 24.50 | 9.40 | 0.241515E+09 | 347.84 | 18-JAN-14:00 | 24.50 | 9.40 |
February | 0.156677E+10 | 4375.34 | 22-FEB-16:30 | 20.50 | 11.47 | 0.207727E+09 | 347.83 | 23-FEB-14:00 | 18.00 | 10.35 |
March | 0.221217E+10 | 5272.33 | 18-MAR-17:10 | 26.92 | 12.85 | 0.258993E+09 | 347.84 | 21-MAR-13:00 | 25.50 | 12.96 |
April | 0.441500E+10 | 12727.81 | 16-APR-17:42 | 26.00 | 13.93 | 0.252962E+09 | 347.85 | 06-APR-09:30 | 26.00 | 13.93 |
May | 0.533354E+10 | 13629.62 | 29-MAY-17:51 | 31.00 | 13.66 | 0.276380E+09 | 347.85 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.708556E+10 | 14189.84 | 25-JUN-17:31 | 38.00 | 15.08 | 0.276681E+09 | 347.85 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.646359E+10 | 14076.66 | 30-JUL-18:11 | 37.33 | 18.54 | 0.257394E+09 | 347.86 | 28-JUL-13:50 | 37.33 | 18.54 |
August | 0.666823E+10 | 13881.84 | 27-AUG-17:41 | 39.17 | 18.06 | 0.288599E+09 | 347.87 | 29-AUG-13:39 | 28.67 | 21.18 |
September | 0.575376E+10 | 13271.80 | 04-SEP-17:01 | 31.60 | 21.23 | 0.256383E+09 | 347.85 | 15-SEP-09:09 | 25.45 | 16.44 |
October | 0.410850E+10 | 12903.00 | 09-OCT-15:42 | 32.83 | 17.35 | 0.261374E+09 | 347.85 | 16-OCT-09:30 | 25.50 | 10.18 |
November | 0.274670E+10 | 6789.59 | 01-NOV-16:00 | 28.00 | 15.72 | 0.252777E+09 | 347.86 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.192413E+10 | 5580.82 | 22-DEC-16:30 | 24.50 | 9.81 | 0.226293E+09 | 347.83 | 20-DEC-14:00 | 24.50 | 9.81 |
Annual Sum or Average | 0.505903E+11 | 0.305708E+10 | ||||||||
Minimum of Months | 0.156677E+10 | 4375.34 | 20.50 | 9.40 | 0.207727E+09 | 347.83 | 18.00 | 9.40 | ||
Maximum of Months | 0.708556E+10 | 14189.84 | 39.17 | 21.23 | 0.288599E+09 | 347.87 | 37.33 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203386E+10 | 3024.07 | 27-JAN-16:30 | 26.50 | 9.48 | 0.381033E+09 | 549.49 | 06-JAN-14:09 | 26.50 | 9.48 |
February | 0.160706E+10 | 2163.65 | 22-FEB-16:20 | 20.67 | 11.54 | 0.337597E+09 | 549.46 | 23-FEB-14:00 | 18.00 | 10.35 |
March | 0.246201E+10 | 4132.40 | 20-MAR-14:30 | 27.70 | 14.31 | 0.423970E+09 | 549.50 | 17-MAR-09:00 | 27.70 | 14.31 |
April | 0.449719E+10 | 6044.76 | 25-APR-15:00 | 33.00 | 15.10 | 0.400255E+09 | 549.50 | 06-APR-09:30 | 33.00 | 15.10 |
May | 0.612614E+10 | 12706.50 | 29-MAY-18:31 | 30.33 | 13.65 | 0.437209E+09 | 549.50 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.847529E+10 | 13585.64 | 25-JUN-17:32 | 38.00 | 15.08 | 0.437262E+09 | 549.50 | 19-JUN-13:09 | 38.00 | 15.08 |
July | 0.776330E+10 | 13360.83 | 30-JUL-18:11 | 37.33 | 18.54 | 0.406623E+09 | 549.51 | 05-JUL-09:09 | 37.33 | 18.54 |
August | 0.743573E+10 | 12836.16 | 27-AUG-18:31 | 37.67 | 18.06 | 0.455636E+09 | 549.51 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.607283E+10 | 11635.41 | 04-SEP-16:21 | 31.60 | 21.34 | 0.404486E+09 | 549.50 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.375154E+10 | 10812.90 | 01-OCT-13:53 | 37.00 | 19.01 | 0.408615E+09 | 549.51 | 03-OCT-13:30 | 33.00 | 20.21 |
November | 0.226789E+10 | 4117.33 | 01-NOV-15:30 | 28.50 | 15.96 | 0.391395E+09 | 549.50 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.162923E+10 | 2311.73 | 22-DEC-17:00 | 24.00 | 9.52 | 0.346043E+09 | 549.47 | 22-DEC-14:00 | 24.00 | 9.52 |
Annual Sum or Average | 0.541221E+11 | 0.483012E+10 | ||||||||
Minimum of Months | 0.160706E+10 | 2163.65 | 20.67 | 9.48 | 0.337597E+09 | 549.46 | 18.00 | 9.48 | ||
Maximum of Months | 0.847529E+10 | 13585.64 | 38.00 | 21.34 | 0.455636E+09 | 549.51 | 38.00 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.216288E+10 | 3532.03 | 27-JAN-10:00 | 20.00 | 7.78 | 0.184640E+09 | 338.72 | 09-JAN-09:09 | 20.00 | 7.78 |
February | 0.167878E+10 | 3725.46 | 23-FEB-10:00 | 14.00 | 11.11 | 0.163862E+09 | 338.72 | 16-FEB-16:10 | 14.00 | 11.11 |
March | 0.262095E+10 | 4849.86 | 23-MAR-10:20 | 22.33 | 10.61 | 0.201944E+09 | 338.73 | 16-MAR-10:09 | 22.33 | 10.61 |
April | 0.501999E+10 | 12963.86 | 23-APR-09:12 | 25.67 | 9.63 | 0.188410E+09 | 338.74 | 28-APR-10:09 | 25.17 | 10.76 |
May | 0.620228E+10 | 13423.37 | 29-MAY-09:12 | 26.67 | 11.70 | 0.204953E+09 | 338.82 | 18-MAY-08:20 | 26.67 | 11.70 |
June | 0.775977E+10 | 13956.25 | 25-JUN-08:51 | 31.00 | 14.52 | 0.204685E+09 | 341.65 | 19-JUN-07:19 | 31.00 | 14.52 |
July | 0.704264E+10 | 14015.42 | 30-JUL-09:31 | 31.00 | 18.77 | 0.190979E+09 | 339.39 | 31-JUL-10:30 | 33.00 | 18.45 |
August | 0.690861E+10 | 13909.15 | 27-AUG-09:11 | 33.67 | 16.18 | 0.213141E+09 | 339.44 | 14-AUG-10:50 | 33.67 | 16.18 |
September | 0.546722E+10 | 13312.69 | 04-SEP-09:42 | 26.33 | 22.09 | 0.189500E+09 | 338.96 | 18-SEP-10:20 | 32.90 | 14.78 |
October | 0.392973E+10 | 8264.12 | 01-OCT-13:53 | 37.00 | 19.01 | 0.193322E+09 | 338.74 | 04-OCT-07:30 | 23.00 | 17.79 |
November | 0.233845E+10 | 4388.94 | 10-NOV-09:40 | 22.33 | 9.69 | 0.187003E+09 | 338.74 | 22-NOV-11:09 | 19.33 | 11.05 |
December | 0.168625E+10 | 2454.39 | 01-DEC-10:00 | 17.00 | 8.19 | 0.168280E+09 | 338.71 | 29-DEC-11:30 | 17.50 | 8.08 |
Annual Sum or Average | 0.528176E+11 | 0.229072E+10 | ||||||||
Minimum of Months | 0.167878E+10 | 2454.39 | 14.00 | 7.78 | 0.163862E+09 | 338.71 | 14.00 | 7.78 | ||
Maximum of Months | 0.775977E+10 | 14015.42 | 37.00 | 22.09 | 0.213141E+09 | 341.65 | 33.67 | 18.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.668534E+10 | 15299.31 | 15-JAN-13:52 | 23.00 | 10.38 | 0.408437E+09 | 549.67 | 31-JAN-14:00 | 28.00 | 11.02 |
February | 0.373949E+10 | 9351.36 | 28-FEB-14:00 | 18.00 | 7.97 | 0.362082E+09 | 549.65 | 23-FEB-14:39 | 18.00 | 7.97 |
March | 0.449185E+10 | 8588.12 | 23-MAR-13:50 | 25.42 | 11.73 | 0.436201E+09 | 549.52 | 09-MAR-14:20 | 25.42 | 11.73 |
April | 0.657667E+10 | 14723.53 | 30-APR-13:23 | 34.00 | 12.40 | 0.400883E+09 | 549.80 | 12-APR-13:00 | 34.00 | 12.40 |
May | 0.675626E+10 | 12062.99 | 07-MAY-13:13 | 34.33 | 14.06 | 0.436868E+09 | 549.50 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.824347E+10 | 14613.12 | 25-JUN-17:31 | 38.00 | 15.08 | 0.436938E+09 | 549.50 | 19-JUN-13:09 | 38.00 | 15.08 |
July | 0.799770E+10 | 14744.92 | 30-JUL-18:11 | 37.33 | 18.54 | 0.406499E+09 | 549.72 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.874260E+10 | 14535.11 | 27-AUG-15:51 | 40.00 | 18.27 | 0.455752E+09 | 550.37 | 28-AUG-13:09 | 37.83 | 20.53 |
September | 0.846148E+10 | 15279.07 | 04-SEP-13:02 | 30.18 | 21.78 | 0.405000E+09 | 569.78 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.781264E+10 | 15000.73 | 09-OCT-13:22 | 31.50 | 17.30 | 0.415578E+09 | 570.46 | 02-OCT-13:09 | 31.50 | 17.30 |
November | 0.627505E+10 | 15245.51 | 19-NOV-13:32 | 26.00 | 11.06 | 0.408189E+09 | 553.24 | 01-NOV-13:00 | 26.00 | 11.06 |
December | 0.522344E+10 | 15521.38 | 25-DEC-14:42 | 26.00 | 11.63 | 0.387385E+09 | 549.75 | 29-DEC-14:00 | 20.00 | 9.12 |
Annual Sum or Average | 0.810060E+11 | 0.495981E+10 | ||||||||
Minimum of Months | 0.373949E+10 | 8588.12 | 18.00 | 7.97 | 0.362082E+09 | 549.50 | 18.00 | 7.97 | ||
Maximum of Months | 0.874260E+10 | 15521.38 | 40.00 | 21.78 | 0.455752E+09 | 570.46 | 38.00 | 20.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257333E+10 | 5998.73 | 31-JAN-16:30 | 29.00 | 10.73 | 0.237641E+09 | 347.85 | 06-JAN-14:09 | 29.00 | 10.73 |
February | 0.183153E+10 | 5890.89 | 22-FEB-16:30 | 20.50 | 11.47 | 0.209493E+09 | 347.83 | 03-FEB-14:00 | 20.50 | 11.47 |
March | 0.273064E+10 | 7463.15 | 18-MAR-17:08 | 26.92 | 12.85 | 0.261908E+09 | 347.85 | 09-MAR-14:00 | 26.92 | 12.85 |
April | 0.497034E+10 | 14748.11 | 02-APR-17:01 | 30.83 | 12.40 | 0.251586E+09 | 347.85 | 06-APR-09:30 | 25.00 | 12.31 |
May | 0.601350E+10 | 14892.39 | 29-MAY-17:51 | 31.00 | 13.66 | 0.275982E+09 | 347.85 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.755207E+10 | 15927.69 | 25-JUN-17:31 | 38.00 | 15.08 | 0.276576E+09 | 347.85 | 29-JUN-09:30 | 33.50 | 18.25 |
July | 0.640286E+10 | 15410.91 | 30-JUL-18:11 | 37.33 | 18.54 | 0.257142E+09 | 347.86 | 05-JUL-09:09 | 37.33 | 18.54 |
August | 0.637333E+10 | 14492.84 | 27-AUG-16:31 | 40.00 | 18.00 | 0.288177E+09 | 347.86 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.520169E+10 | 14535.82 | 04-SEP-16:21 | 31.60 | 21.34 | 0.255589E+09 | 347.85 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.386575E+10 | 11559.83 | 15-OCT-15:52 | 31.00 | 12.59 | 0.255010E+09 | 347.86 | 03-OCT-13:30 | 31.00 | 12.59 |
November | 0.269725E+10 | 7303.18 | 19-NOV-15:32 | 27.00 | 11.63 | 0.243520E+09 | 347.86 | 16-NOV-14:09 | 27.00 | 11.63 |
December | 0.189949E+10 | 7357.67 | 25-DEC-16:42 | 24.33 | 11.32 | 0.219502E+09 | 347.84 | 20-DEC-14:00 | 24.33 | 11.32 |
Annual Sum or Average | 0.521118E+11 | 0.303213E+10 | ||||||||
Minimum of Months | 0.183153E+10 | 5890.89 | 20.50 | 10.73 | 0.209493E+09 | 347.83 | 20.50 | 10.73 | ||
Maximum of Months | 0.755207E+10 | 15927.69 | 40.00 | 21.34 | 0.288177E+09 | 347.86 | 37.33 | 20.80 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.924641E+09 | 10405.42 | 02-JAN-07:02 | 6.00 |
February | 0.767622E+09 | 4946.89 | 13-FEB-07:02 | 8.33 |
March | 0.782178E+09 | 7457.39 | 27-MAR-06:01 | 1.97 |
April | 0.303690E+09 | 4006.39 | 21-APR-05:03 | 8.17 |
May | 0.147836E+09 | 3671.78 | 14-MAY-07:23 | 22.00 |
June | 34442670.43 | 3731.29 | 27-JUN-04:02 | 25.00 |
July | 28215641.89 | 4969.98 | 31-JUL-04:02 | 26.00 |
August | 27050581.65 | 4805.17 | 21-AUG-04:02 | 25.00 |
September | 37635072.98 | 4057.91 | 18-SEP-04:02 | 25.42 |
October | 0.451508E+09 | 4083.59 | 26-OCT-05:03 | 7.17 |
November | 0.656815E+09 | 6381.89 | 24-NOV-07:02 | 4.50 |
December | 0.136632E+10 | 9421.41 | 07-DEC-07:01 | 1.33 |
Annual Sum or Average | 0.552795E+10 | |||
Minimum of Months | 27050581.65 | 3671.78 | 1.33 | |
Maximum of Months | 0.136632E+10 | 10405.42 | 26.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307692E+09 | 4190.67 | 16-JAN-12:13 | 24.00 |
February | 0.321251E+09 | 3295.52 | 26-FEB-11:32 | 15.33 |
March | 0.175328E+09 | 2491.25 | 26-MAR-16:00 | 18.30 |
April | 20784776.81 | 3716.99 | 02-APR-15:02 | 31.00 |
May | 18610354.19 | 2467.70 | 07-MAY-15:52 | 36.00 |
June | 19021974.54 | 3224.89 | 25-JUN-16:11 | 38.00 |
July | 24430376.93 | 3306.40 | 02-JUL-16:31 | 38.00 |
August | 18571907.87 | 3171.29 | 27-AUG-15:11 | 40.00 |
September | 15939449.51 | 2350.93 | 04-SEP-15:41 | 31.60 |
October | 35112669.80 | 3711.14 | 15-OCT-15:52 | 31.00 |
November | 0.148623E+09 | 4572.99 | 19-NOV-15:32 | 27.00 |
December | 0.597559E+09 | 4896.63 | 10-DEC-13:53 | 21.00 |
Annual Sum or Average | 0.170293E+10 | |||
Minimum of Months | 15939449.51 | 2350.93 | 15.33 | |
Maximum of Months | 0.597559E+09 | 4896.63 | 40.00 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128196E+09 | 2930.31 | 15-JAN-13:12 | 21.67 |
February | 87929613.82 | 2547.90 | 13-FEB-08:07 | 10.17 |
March | 28426479.75 | 1952.88 | 27-MAR-07:06 | 4.73 |
April | 15851472.48 | 2351.90 | 23-APR-15:11 | 33.10 |
May | 12610276.01 | 1544.17 | 27-MAY-17:42 | 30.00 |
June | 16878847.76 | 3107.54 | 29-JUN-04:02 | 28.00 |
July | 31704880.70 | 3799.19 | 12-JUL-04:02 | 27.83 |
August | 25930082.68 | 3706.66 | 16-AUG-04:02 | 28.17 |
September | 26415544.39 | 4092.14 | 07-SEP-04:02 | 26.10 |
October | 31459690.17 | 2917.69 | 15-OCT-15:42 | 31.00 |
November | 40528036.41 | 3434.08 | 26-NOV-16:33 | 18.33 |
December | 0.192697E+09 | 3669.31 | 10-DEC-13:43 | 21.00 |
Annual Sum or Average | 0.638628E+09 | |||
Minimum of Months | 12610276.01 | 1544.17 | 4.73 | |
Maximum of Months | 0.192697E+09 | 4092.14 | 33.10 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3373359.45 | 17525.67 | 02-JAN-07:02 | 6.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 3373359.45 | |||
Minimum of Months | 0.00 | 0.00 | 6.00 | |
Maximum of Months | 3373359.45 | 17525.67 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 60777542.01 | 25868.77 | 02-JAN-06:11 | 4.67 |
February | 10101468.29 | 23010.55 | 13-FEB-07:02 | 8.33 |
March | 2902358.08 | 22962.00 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 3540120.13 | 23654.59 | 24-NOV-07:02 | 4.50 |
December | 54725632.99 | 24288.33 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.132047E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.97 | |
Maximum of Months | 60777542.01 | 25868.77 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164644E+09 | 12570.48 | 02-JAN-06:11 | 4.67 |
February | 0.136675E+09 | 11240.58 | 13-FEB-06:12 | 8.00 |
March | 0.102219E+09 | 11458.01 | 27-MAR-05:11 | 2.33 |
April | 158982.25 | 794.91 | 21-APR-06:03 | 9.33 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 15527550.39 | 9838.27 | 25-OCT-06:02 | 5.00 |
November | 87558705.38 | 11451.61 | 24-NOV-06:11 | 3.33 |
December | 0.476889E+09 | 12121.87 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.983672E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.476889E+09 | 12570.48 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73186581.42 | 8675.43 | 02-JAN-06:11 | 4.67 |
February | 62059500.41 | 7487.57 | 13-FEB-06:12 | 8.00 |
March | 47710521.17 | 7685.40 | 27-MAR-05:11 | 2.33 |
April | 43566.45 | 145.22 | 01-APR-06:05 | 14.33 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 9808045.60 | 7079.45 | 25-OCT-06:02 | 5.00 |
November | 31241263.24 | 7746.63 | 24-NOV-06:11 | 3.33 |
December | 0.209260E+09 | 8343.50 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.433309E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.209260E+09 | 8675.43 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 82028275.66 | 12928.17 | 02-JAN-06:11 | 4.67 |
February | 81439991.88 | 11783.87 | 13-FEB-06:12 | 8.00 |
March | 79149869.27 | 11878.45 | 27-MAR-05:11 | 2.33 |
April | 206548.22 | 1032.74 | 21-APR-06:03 | 9.33 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 9249180.12 | 9492.48 | 25-OCT-06:02 | 5.00 |
November | 35014179.24 | 11795.97 | 24-NOV-06:11 | 3.33 |
December | 0.250800E+09 | 12620.69 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.537888E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.250800E+09 | 12928.17 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 97546636.67 | 8453.02 | 02-JAN-06:11 | 4.67 |
February | 89168003.55 | 7252.39 | 13-FEB-06:12 | 8.00 |
March | 64259241.86 | 7345.64 | 27-MAR-05:11 | 2.33 |
April | 285608.53 | 1401.76 | 21-APR-06:03 | 9.33 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 11291646.91 | 7010.87 | 25-OCT-06:02 | 5.00 |
November | 53342236.25 | 7426.33 | 24-NOV-06:11 | 3.33 |
December | 0.292338E+09 | 8195.23 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.608232E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.292338E+09 | 8453.02 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 29046927.70 | 8055.39 | 02-JAN-06:11 | 4.67 |
February | 17541163.48 | 7285.98 | 14-FEB-07:03 | 7.33 |
March | 20386616.60 | 7656.83 | 27-MAR-05:11 | 2.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 496129.95 | 3884.89 | 24-NOV-07:02 | 4.50 |
December | 30362160.49 | 7300.39 | 06-DEC-07:01 | -0.5 |
Annual Sum or Average | 97832998.21 | |||
Minimum of Months | 0.00 | 0.00 | -0.5 | |
Maximum of Months | 30362160.49 | 8055.39 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7647172.80 | 4902.91 | 03-JAN-07:03 | 10.33 |
February | 5812168.43 | 4625.39 | 13-FEB-07:02 | 8.33 |
March | 4505895.84 | 4716.87 | 29-MAR-06:01 | 3.08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 30046.85 | 250.39 | 24-NOV-07:02 | 4.50 |
December | 7737805.56 | 4845.13 | 06-DEC-07:02 | -0.5 |
Annual Sum or Average | 25733089.48 | |||
Minimum of Months | 0.00 | 0.00 | -0.5 | |
Maximum of Months | 7737805.56 | 4902.91 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.542101E+09 | 8392.05 | 02-JAN-07:10 | 6.00 |
February | 0.587902E+09 | 8326.16 | 08-FEB-07:10 | 6.17 |
March | 0.674572E+09 | 9158.97 | 27-MAR-06:10 | 1.97 |
April | 0.101501E+09 | 7375.87 | 21-APR-06:10 | 9.33 |
May | 3734054.43 | 6178.97 | 01-MAY-06:05 | 13.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.218467E+09 | 7965.10 | 25-OCT-07:00 | 5.00 |
November | 0.300870E+09 | 8109.39 | 24-NOV-07:10 | 4.50 |
December | 0.666604E+09 | 9453.52 | 06-DEC-07:10 | -0.5 |
Annual Sum or Average | 0.309575E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.5 | |
Maximum of Months | 0.674572E+09 | 9453.52 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7833653.82 | 4819.00 | 03-JAN-07:03 | 10.33 |
February | 8413748.37 | 4673.06 | 14-FEB-07:03 | 7.33 |
March | 5655211.85 | 4541.45 | 29-MAR-06:01 | 3.08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 13570959.37 | 4781.20 | 14-DEC-07:01 | 1.33 |
Annual Sum or Average | 35473573.40 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 13570959.37 | 4819.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34123289.12 | 9690.71 | 02-JAN-06:11 | 4.67 |
February | 16975374.62 | 8460.78 | 13-FEB-07:02 | 8.33 |
March | 13853427.07 | 8676.73 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 6164490.42 | 8490.73 | 24-NOV-07:02 | 4.50 |
December | 89863748.04 | 9254.61 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.160980E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.97 | |
Maximum of Months | 89863748.04 | 9690.71 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18560921.48 | 6101.94 | 02-JAN-06:11 | 4.67 |
February | 11811993.30 | 5577.80 | 08-FEB-07:02 | 6.17 |
March | 8843552.71 | 5357.63 | 31-MAR-06:02 | 4.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 156353.41 | 1042.36 | 26-OCT-06:03 | 8.17 |
November | 3280236.02 | 5647.62 | 24-NOV-07:02 | 4.50 |
December | 43731694.87 | 5718.29 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 86384751.79 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 43731694.87 | 6101.94 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15323345.25 | 9222.57 | 02-JAN-06:11 | 4.67 |
February | 8633579.58 | 8281.03 | 13-FEB-07:02 | 8.33 |
March | 8422925.37 | 8499.94 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 1328885.12 | 8462.89 | 24-NOV-07:02 | 4.50 |
December | 39521082.04 | 8874.21 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 73229817.36 | |||
Minimum of Months | 0.00 | 0.00 | 1.97 | |
Maximum of Months | 39521082.04 | 9222.57 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21178249.47 | 5865.05 | 02-JAN-06:11 | 4.67 |
February | 14520554.07 | 5594.54 | 28-FEB-07:02 | 5.33 |
March | 9750405.44 | 5418.76 | 31-MAR-06:02 | 4.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 138601.17 | 924.01 | 26-OCT-06:03 | 8.17 |
November | 5236293.79 | 5454.46 | 24-NOV-07:02 | 4.50 |
December | 61930131.22 | 5615.46 | 06-DEC-06:01 | 0.67 |
Annual Sum or Average | 0.112754E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.67 | |
Maximum of Months | 61930131.22 | 5865.05 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101328E+10 | 1592.13 | 20-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.881179E+09 | 1592.13 | 03-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.964740E+09 | 1388.60 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.820720E+09 | 1111.04 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.858103E+09 | 833.48 | 25-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.833903E+09 | 759.45 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.797671E+09 | 907.52 | 10-JUL-15:39 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.920273E+09 | 1388.60 | 04-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.844675E+09 | 1388.60 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.955722E+09 | 1592.13 | 27-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.980091E+09 | 1592.13 | 02-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.100311E+10 | 1592.13 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.108735E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.797671E+09 | 759.45 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.101328E+10 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.598249E+09 | 1007.95 | 20-JAN-08:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.534726E+09 | 879.10 | 07-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.598722E+09 | 703.38 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.514026E+09 | 480.79 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.547380E+09 | 527.66 | 25-MAY-15:09 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.534510E+09 | 480.79 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.511361E+09 | 574.53 | 10-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.579582E+09 | 879.10 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.528632E+09 | 574.53 | 18-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.572796E+09 | 703.38 | 13-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.591287E+09 | 1007.95 | 28-NOV-16:19 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.594792E+09 | 1007.95 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.670606E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.511361E+09 | 480.79 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.598722E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.907569E+09 | 1592.13 | 20-JAN-08:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.824059E+09 | 1388.60 | 10-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.935704E+09 | 1388.60 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.824059E+09 | 1111.04 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.875129E+09 | 833.48 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.856954E+09 | 833.48 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.818958E+09 | 1111.04 | 10-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.926773E+09 | 1388.60 | 04-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.834850E+09 | 1111.04 | 05-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.876996E+09 | 1314.57 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.897603E+09 | 1592.13 | 28-NOV-16:30 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.898101E+09 | 1592.13 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.104768E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.818958E+09 | 833.48 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.935704E+09 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.614634E+09 | 1007.89 | 20-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.543780E+09 | 1007.89 | 03-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.605939E+09 | 1007.89 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.523750E+09 | 832.18 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.552855E+09 | 656.47 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.539289E+09 | 656.47 | 22-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.516700E+09 | 703.34 | 10-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.588443E+09 | 879.04 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.535660E+09 | 879.04 | 19-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.585939E+09 | 1007.89 | 27-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.594340E+09 | 1007.89 | 02-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.603346E+09 | 1007.89 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.680467E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.516700E+09 | 656.47 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.614634E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.100387E+10 | 1592.13 | 20-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.877024E+09 | 1592.13 | 03-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.961371E+09 | 1388.60 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.819133E+09 | 1111.04 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.857195E+09 | 833.48 | 25-MAY-12:20 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.833743E+09 | 759.45 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.796633E+09 | 907.52 | 10-JUL-15:50 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.917462E+09 | 1388.60 | 04-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.841938E+09 | 1111.04 | 05-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.949178E+09 | 1592.13 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.971941E+09 | 1592.13 | 02-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.995032E+09 | 1592.13 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.108245E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.796633E+09 | 759.45 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.100387E+10 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.596007E+09 | 1007.95 | 20-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.533048E+09 | 879.10 | 07-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.597121E+09 | 703.38 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.513518E+09 | 480.79 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.546915E+09 | 527.66 | 25-MAY-15:09 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.533652E+09 | 480.79 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.510513E+09 | 574.53 | 10-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.578380E+09 | 879.10 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.527561E+09 | 574.53 | 29-SEP-14:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.571001E+09 | 703.38 | 13-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.588271E+09 | 1007.95 | 28-NOV-16:19 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.592483E+09 | 1007.95 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.668847E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.510513E+09 | 480.79 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.597121E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.907001E+09 | 1592.13 | 20-JAN-08:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.822731E+09 | 1388.60 | 10-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.934161E+09 | 1388.60 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.821912E+09 | 1111.04 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.873251E+09 | 833.48 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.854827E+09 | 833.48 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.816283E+09 | 1111.04 | 13-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.923823E+09 | 1388.60 | 04-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.833363E+09 | 1111.04 | 05-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.875715E+09 | 1314.57 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.896977E+09 | 1592.13 | 28-NOV-16:30 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.897277E+09 | 1592.13 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.104573E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.816283E+09 | 833.48 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.934161E+09 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.611322E+09 | 1007.89 | 20-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.542112E+09 | 1007.89 | 03-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.604367E+09 | 1007.89 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.522139E+09 | 703.34 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.551765E+09 | 656.47 | 05-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.538213E+09 | 527.63 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.515430E+09 | 703.34 | 10-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.586466E+09 | 879.04 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.534148E+09 | 879.04 | 19-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.584269E+09 | 1007.89 | 27-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.592466E+09 | 1007.89 | 02-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.601465E+09 | 1007.89 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.678416E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.515430E+09 | 527.63 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.611322E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101328E+10 | 1592.13 | 20-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.881179E+09 | 1592.13 | 03-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.964740E+09 | 1388.60 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.820720E+09 | 1111.04 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.858103E+09 | 833.48 | 25-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.833903E+09 | 759.45 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.797671E+09 | 907.52 | 10-JUL-15:39 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.920273E+09 | 1388.60 | 04-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.844675E+09 | 1388.60 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.955722E+09 | 1592.13 | 27-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.980047E+09 | 1592.13 | 02-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.100311E+10 | 1592.13 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.108734E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.797671E+09 | 759.45 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.101328E+10 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.598249E+09 | 1007.95 | 20-JAN-08:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.534726E+09 | 879.10 | 07-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.598722E+09 | 703.38 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.514026E+09 | 480.79 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.547380E+09 | 527.66 | 25-MAY-15:09 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.534510E+09 | 480.79 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.511361E+09 | 574.53 | 10-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.579582E+09 | 879.10 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.528632E+09 | 574.53 | 18-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.572796E+09 | 703.38 | 13-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.591287E+09 | 1007.95 | 28-NOV-16:19 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.594792E+09 | 1007.95 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.670606E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.511361E+09 | 480.79 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.598722E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.907569E+09 | 1592.13 | 20-JAN-08:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.824059E+09 | 1388.60 | 10-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.935701E+09 | 1388.60 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.824059E+09 | 1111.04 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.875129E+09 | 833.48 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.856951E+09 | 833.48 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.818958E+09 | 1111.04 | 10-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.926773E+09 | 1388.60 | 04-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.834850E+09 | 1111.04 | 05-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.876996E+09 | 1314.57 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.897603E+09 | 1592.13 | 28-NOV-16:30 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.898101E+09 | 1592.13 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.104768E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.818958E+09 | 833.48 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.935701E+09 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.614634E+09 | 1007.89 | 20-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.543780E+09 | 1007.89 | 03-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.605939E+09 | 1007.89 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.523750E+09 | 832.18 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.552855E+09 | 656.47 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.539289E+09 | 656.47 | 22-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.516700E+09 | 703.34 | 10-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.588443E+09 | 879.04 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.535660E+09 | 879.04 | 19-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.585910E+09 | 1007.89 | 27-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.594340E+09 | 1007.89 | 02-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.603346E+09 | 1007.89 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.680465E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.516700E+09 | 656.47 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.614634E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.101328E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3890768.44 | 0.334360E+09 |
February | 0.901968E+09 | 0.881179E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269788E+09 |
March | 0.107774E+10 | 0.964740E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3775724.68 | 0.359690E+09 |
April | 0.956342E+09 | 0.820720E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69271516.40 | 0.124872E+09 |
May | 0.103597E+10 | 0.858103E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127942E+09 | 80908980.50 |
June | 0.103308E+10 | 0.833903E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229254E+09 | 25108784.71 |
July | 0.959235E+09 | 0.797671E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224240E+09 | 21668736.77 |
August | 0.107774E+10 | 0.920273E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157535E+09 | 29050184.75 |
September | 0.956342E+09 | 0.844675E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117323E+09 | 55476043.80 |
October | 0.994195E+09 | 0.955722E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46334674.15 | 0.185323E+09 |
November | 0.984487E+09 | 0.980091E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6557682.99 | 0.307971E+09 |
December | 0.959235E+09 | 0.100311E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2004163.19 | 0.323240E+09 |
Annual Sum or Average | 0.119305E+11 | 0.108735E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.988128E+09 | 0.211746E+10 |
Minimum of Months | 0.901968E+09 | 0.797671E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21668736.77 |
Maximum of Months | 0.107774E+10 | 0.101328E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229254E+09 | 0.359690E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.598249E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1595794.17 | 0.232934E+09 |
February | 0.571020E+09 | 0.534726E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186405E+09 |
March | 0.682301E+09 | 0.598722E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2407330.93 | 0.248734E+09 |
April | 0.605444E+09 | 0.514026E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44099901.74 | 88709066.34 |
May | 0.655854E+09 | 0.547380E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83405988.39 | 56285429.02 |
June | 0.654023E+09 | 0.534510E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153792E+09 | 17094182.96 |
July | 0.607275E+09 | 0.511361E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150203E+09 | 14936866.30 |
August | 0.682301E+09 | 0.579582E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103693E+09 | 20411757.77 |
September | 0.605444E+09 | 0.528632E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77536133.20 | 38021768.07 |
October | 0.629407E+09 | 0.572796E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28851835.14 | 0.129212E+09 |
November | 0.623262E+09 | 0.591287E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3158084.81 | 0.212995E+09 |
December | 0.607275E+09 | 0.594792E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 860806.73 | 0.221837E+09 |
Annual Sum or Average | 0.755301E+10 | 0.670606E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649604E+09 | 0.146758E+10 |
Minimum of Months | 0.571020E+09 | 0.511361E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14936866.30 |
Maximum of Months | 0.682301E+09 | 0.598722E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153792E+09 | 0.248734E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.907569E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1194361.48 | 0.388063E+09 |
February | 0.901968E+09 | 0.824059E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294811E+09 |
March | 0.107774E+10 | 0.935704E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3334588.94 | 0.383734E+09 |
April | 0.956342E+09 | 0.824059E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63825247.58 | 0.129330E+09 |
May | 0.103597E+10 | 0.875129E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127485E+09 | 80442159.52 |
June | 0.103308E+10 | 0.856954E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232628E+09 | 24314866.56 |
July | 0.959235E+09 | 0.818958E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225882E+09 | 21205645.50 |
August | 0.107774E+10 | 0.926773E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155998E+09 | 29889846.93 |
September | 0.956342E+09 | 0.834850E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113371E+09 | 58732783.64 |
October | 0.994195E+09 | 0.876996E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39305045.42 | 0.205774E+09 |
November | 0.984487E+09 | 0.897603E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2169512.71 | 0.347276E+09 |
December | 0.959235E+09 | 0.898101E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 106774.28 | 0.364809E+09 |
Annual Sum or Average | 0.119305E+11 | 0.104768E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.965300E+09 | 0.232838E+10 |
Minimum of Months | 0.901968E+09 | 0.818958E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21205645.50 |
Maximum of Months | 0.107774E+10 | 0.935704E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232628E+09 | 0.388063E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.614634E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1710959.91 | 0.233466E+09 |
February | 0.570983E+09 | 0.543780E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184755E+09 |
March | 0.682256E+09 | 0.605939E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2443657.03 | 0.247479E+09 |
April | 0.605404E+09 | 0.523750E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41938907.86 | 88766445.44 |
May | 0.655811E+09 | 0.552855E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82862346.22 | 56822687.20 |
June | 0.653980E+09 | 0.539289E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152236E+09 | 17637701.93 |
July | 0.607235E+09 | 0.516700E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148582E+09 | 15210606.18 |
August | 0.682256E+09 | 0.588443E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103641E+09 | 20305776.80 |
September | 0.605404E+09 | 0.535660E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77439059.88 | 38298233.13 |
October | 0.629366E+09 | 0.585939E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29193551.12 | 0.128721E+09 |
November | 0.623221E+09 | 0.594340E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3352021.43 | 0.213433E+09 |
December | 0.607235E+09 | 0.603346E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 648907.51 | 0.222312E+09 |
Annual Sum or Average | 0.755252E+10 | 0.680467E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644048E+09 | 0.146721E+10 |
Minimum of Months | 0.570983E+09 | 0.516700E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15210606.18 |
Maximum of Months | 0.682256E+09 | 0.614634E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152236E+09 | 0.247479E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.100387E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1937138.82 | 0.196086E+09 |
February | 0.901968E+09 | 0.877024E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153165E+09 |
March | 0.107774E+10 | 0.961371E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2241259.61 | 0.196336E+09 |
April | 0.956342E+09 | 0.819133E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40986012.18 | 66399939.96 |
May | 0.103597E+10 | 0.857195E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73594473.58 | 41631904.52 |
June | 0.103308E+10 | 0.833743E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125966E+09 | 12526421.79 |
July | 0.959235E+09 | 0.796633E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123093E+09 | 11574064.33 |
August | 0.107774E+10 | 0.917462E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85858927.88 | 17177315.75 |
September | 0.956342E+09 | 0.841938E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63682222.29 | 32977947.96 |
October | 0.994195E+09 | 0.949178E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24658974.70 | 0.113101E+09 |
November | 0.984487E+09 | 0.971941E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2979828.15 | 0.191212E+09 |
December | 0.959235E+09 | 0.995032E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 701638.49 | 0.196732E+09 |
Annual Sum or Average | 0.119305E+11 | 0.108245E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545699E+09 | 0.122892E+10 |
Minimum of Months | 0.901968E+09 | 0.796633E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11574064.33 |
Maximum of Months | 0.107774E+10 | 0.100387E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125966E+09 | 0.196732E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.596007E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 687768.20 | 0.140162E+09 |
February | 0.571020E+09 | 0.533048E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107778E+09 |
March | 0.682301E+09 | 0.597121E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1307917.96 | 0.139886E+09 |
April | 0.605444E+09 | 0.513518E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24595904.46 | 49522667.67 |
May | 0.655854E+09 | 0.546915E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45811305.78 | 30833417.99 |
June | 0.654023E+09 | 0.533652E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82710044.75 | 9320196.74 |
July | 0.607275E+09 | 0.510513E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80844157.59 | 8741766.69 |
August | 0.682301E+09 | 0.578380E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55383692.15 | 13031602.04 |
September | 0.605444E+09 | 0.527561E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41401796.26 | 23902463.05 |
October | 0.629407E+09 | 0.571001E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15215883.55 | 80166235.25 |
November | 0.623262E+09 | 0.588271E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1424044.13 | 0.134045E+09 |
December | 0.607275E+09 | 0.592483E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 258244.83 | 0.137537E+09 |
Annual Sum or Average | 0.755301E+10 | 0.668847E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349641E+09 | 0.874926E+09 |
Minimum of Months | 0.571020E+09 | 0.510513E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8741766.69 |
Maximum of Months | 0.682301E+09 | 0.597121E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82710044.75 | 0.140162E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.907001E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45208330.10 | 0.237189E+10 |
February | 0.901968E+09 | 0.822731E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286217E+10 |
March | 0.107774E+10 | 0.934161E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150078E+09 | 0.238164E+10 |
April | 0.956342E+09 | 0.821912E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118735E+10 | 0.722812E+09 |
May | 0.103597E+10 | 0.873251E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207693E+10 | 0.319836E+09 |
June | 0.103308E+10 | 0.854827E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330588E+10 | 64247294.14 |
July | 0.959235E+09 | 0.816283E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267830E+10 | 27023308.50 |
August | 0.107774E+10 | 0.923823E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285297E+10 | 90274610.85 |
September | 0.956342E+09 | 0.833363E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192893E+10 | 0.220459E+09 |
October | 0.994195E+09 | 0.875715E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847184E+09 | 0.137626E+10 |
November | 0.984487E+09 | 0.896977E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99335190.13 | 0.219995E+10 |
December | 0.959235E+09 | 0.897277E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4605816.72 | 0.330401E+10 |
Annual Sum or Average | 0.119305E+11 | 0.104573E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151768E+11 | 0.159406E+11 |
Minimum of Months | 0.901968E+09 | 0.816283E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27023308.50 |
Maximum of Months | 0.107774E+10 | 0.934161E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330588E+10 | 0.330401E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.611322E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 698605.57 | 0.140774E+09 |
February | 0.570983E+09 | 0.542112E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106434E+09 |
March | 0.682256E+09 | 0.604367E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1279386.55 | 0.138651E+09 |
April | 0.605404E+09 | 0.522139E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22819447.93 | 50383438.43 |
May | 0.655811E+09 | 0.551765E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44723265.11 | 31830594.03 |
June | 0.653980E+09 | 0.538213E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81438545.11 | 9878705.15 |
July | 0.607235E+09 | 0.515430E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79522295.70 | 8908385.32 |
August | 0.682256E+09 | 0.586466E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55003008.68 | 12911135.59 |
September | 0.605404E+09 | 0.534148E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41039806.27 | 24141488.49 |
October | 0.629366E+09 | 0.584269E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15115980.54 | 80617105.48 |
November | 0.623221E+09 | 0.592466E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1426270.15 | 0.134922E+09 |
December | 0.607235E+09 | 0.601465E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 168937.14 | 0.136932E+09 |
Annual Sum or Average | 0.755252E+10 | 0.678416E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343236E+09 | 0.876383E+09 |
Minimum of Months | 0.570983E+09 | 0.515430E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8908385.32 |
Maximum of Months | 0.682256E+09 | 0.611322E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81438545.11 | 0.140774E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.101328E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2585929.35 | 0.308116E+09 |
February | 0.901968E+09 | 0.881179E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245363E+09 |
March | 0.107774E+10 | 0.964740E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3151875.44 | 0.322897E+09 |
April | 0.956342E+09 | 0.820720E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58860284.45 | 0.110364E+09 |
May | 0.103597E+10 | 0.858103E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107820E+09 | 71118825.88 |
June | 0.103308E+10 | 0.833903E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191481E+09 | 21783701.31 |
July | 0.959235E+09 | 0.797671E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188121E+09 | 18601142.15 |
August | 0.107774E+10 | 0.920273E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131962E+09 | 25807586.20 |
September | 0.956342E+09 | 0.844675E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98003776.90 | 48894264.22 |
October | 0.994195E+09 | 0.955722E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38380857.09 | 0.168263E+09 |
November | 0.984487E+09 | 0.980047E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4820109.75 | 0.284010E+09 |
December | 0.959235E+09 | 0.100311E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1181810.32 | 0.296902E+09 |
Annual Sum or Average | 0.119305E+11 | 0.108734E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826369E+09 | 0.192212E+10 |
Minimum of Months | 0.901968E+09 | 0.797671E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18601142.15 |
Maximum of Months | 0.107774E+10 | 0.101328E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191481E+09 | 0.322897E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.598249E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1230921.48 | 0.211936E+09 |
February | 0.421807E+09 | 0.534726E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167276E+09 |
March | 0.502994E+09 | 0.598722E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2044341.71 | 0.220624E+09 |
April | 0.447140E+09 | 0.514026E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37903936.30 | 77236642.72 |
May | 0.484071E+09 | 0.547380E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70888625.33 | 48987314.47 |
June | 0.482240E+09 | 0.534510E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128962E+09 | 14721386.42 |
July | 0.448971E+09 | 0.511361E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126745E+09 | 12696044.41 |
August | 0.502994E+09 | 0.579582E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87308159.57 | 17968382.61 |
September | 0.447140E+09 | 0.528632E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65097832.81 | 33280988.13 |
October | 0.465148E+09 | 0.572796E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24375550.29 | 0.115365E+09 |
November | 0.460569E+09 | 0.591287E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2488204.19 | 0.194066E+09 |
December | 0.448971E+09 | 0.594792E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 571603.00 | 0.202217E+09 |
Annual Sum or Average | 0.557719E+10 | 0.670606E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547616E+09 | 0.131637E+10 |
Minimum of Months | 0.421807E+09 | 0.511361E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12696044.41 |
Maximum of Months | 0.502994E+09 | 0.598722E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128962E+09 | 0.220624E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.907569E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1011744.08 | 0.349715E+09 |
February | 0.901968E+09 | 0.824059E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264364E+09 |
March | 0.107774E+10 | 0.935701E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2824861.48 | 0.340885E+09 |
April | 0.956342E+09 | 0.824059E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53891841.81 | 0.113903E+09 |
May | 0.103597E+10 | 0.875129E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107231E+09 | 70842923.51 |
June | 0.103308E+10 | 0.856951E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194424E+09 | 21120828.99 |
July | 0.959235E+09 | 0.818958E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189633E+09 | 18212474.86 |
August | 0.107774E+10 | 0.926773E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130589E+09 | 26515872.34 |
September | 0.956342E+09 | 0.834850E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94641454.96 | 51629231.66 |
October | 0.994195E+09 | 0.876996E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32789466.98 | 0.183616E+09 |
November | 0.984487E+09 | 0.897603E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1816541.47 | 0.313771E+09 |
December | 0.959235E+09 | 0.898101E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91147.21 | 0.329494E+09 |
Annual Sum or Average | 0.119305E+11 | 0.104768E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808943E+09 | 0.208407E+10 |
Minimum of Months | 0.901968E+09 | 0.818958E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18212474.86 |
Maximum of Months | 0.107774E+10 | 0.935701E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194424E+09 | 0.349715E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.614634E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1209835.80 | 0.212927E+09 |
February | 0.570983E+09 | 0.543780E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166470E+09 |
March | 0.682256E+09 | 0.605939E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1952028.77 | 0.220743E+09 |
April | 0.605404E+09 | 0.523750E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35114716.12 | 78145225.12 |
May | 0.655811E+09 | 0.552855E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69216241.21 | 49939174.85 |
June | 0.653980E+09 | 0.539289E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126794E+09 | 15300017.63 |
July | 0.607235E+09 | 0.516700E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124315E+09 | 13025132.16 |
August | 0.682256E+09 | 0.588443E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86529359.98 | 18051779.93 |
September | 0.605404E+09 | 0.535660E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64360526.20 | 33793857.95 |
October | 0.629366E+09 | 0.585910E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24090938.31 | 0.115882E+09 |
November | 0.623221E+09 | 0.594340E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2497066.02 | 0.194938E+09 |
December | 0.607235E+09 | 0.603346E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 360391.20 | 0.202568E+09 |
Annual Sum or Average | 0.755252E+10 | 0.680465E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536440E+09 | 0.132178E+10 |
Minimum of Months | 0.570983E+09 | 0.516700E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13025132.16 |
Maximum of Months | 0.682256E+09 | 0.614634E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126794E+09 | 0.220743E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 898668.28 | 0.467324E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362967E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2946720.95 | 0.470064E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66238591.53 | 0.158652E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128598E+09 | 98521064.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236896E+09 | 28110048.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235012E+09 | 23930084.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160950E+09 | 35580648.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116524E+09 | 66603901.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40353966.51 | 0.251051E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2950954.67 | 0.429391E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325826.05 | 0.450337E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.991694E+09 | 0.284253E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23930084.41 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236896E+09 | 0.470064E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1890639.00 | 0.565460E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441853E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4212112.05 | 0.583958E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86556852.94 | 0.201103E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165118E+09 | 0.126426E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303887E+09 | 36719652.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301933E+09 | 30936429.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207923E+09 | 44060180.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152113E+09 | 83101614.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54924383.29 | 0.306865E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5717461.69 | 0.518281E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 922462.36 | 0.541849E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128520E+10 | 0.348061E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30936429.46 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303887E+09 | 0.583958E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 797711.78 | 0.529388E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432631E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2156192.84 | 0.569075E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73309439.83 | 0.187464E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155147E+09 | 0.108079E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318740E+09 | 30178130.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305064E+09 | 25979531.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217022E+09 | 36959864.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154592E+09 | 74160958.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51933299.47 | 0.288667E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2851652.23 | 0.484308E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290207.73 | 0.504139E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128190E+10 | 0.327103E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25979531.37 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318740E+09 | 0.569075E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 20-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 113.14 | 16-JAN-11:57 | 592.40 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 03-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 807.41 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 1388.60 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 18-MAR-17:03 | 689.52 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 1111.04 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 495.83 | 30-APR-15:48 | 363.49 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 833.48 | 25-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 457.64 | 20-MAY-17:02 | 305.91 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 759.45 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 735.10 | 17-JUN-17:10 | 156.18 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 10-JUL-15:39 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 929.70 | 22-JUL-17:43 | 249.28 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 1388.60 | 04-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 830.20 | 13-AUG-15:55 | 374.16 | 05-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 1388.60 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 581.29 | 17-SEP-12:00 | 257.91 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 27-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.55 | 01-OCT-14:58 | 730.21 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 02-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.99 | 19-NOV-12:40 | 671.26 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.73 | 25-DEC-16:00 | 577.94 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.18 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 929.70 | 807.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1007.95 | 20-JAN-08:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.42 | 16-JAN-13:53 | 403.45 | 01-JAN-01:00 |
February | 827.22 | 01-FEB-10:09 | 879.10 | 07-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 543.97 | 02-FEB-23:00 |
March | 827.22 | 01-MAR-10:09 | 703.38 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.81 | 18-MAR-17:03 | 460.31 | 28-MAR-04:00 |
April | 827.22 | 03-APR-09:09 | 480.79 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 344.87 | 30-APR-15:48 | 361.89 | 16-APR-08:50 |
May | 827.22 | 01-MAY-09:09 | 527.66 | 25-MAY-15:09 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.08 | 20-MAY-17:50 | 202.99 | 23-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 480.79 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 492.11 | 17-JUN-17:10 | 112.34 | 11-JUN-06:20 |
July | 827.22 | 03-JUL-09:09 | 574.53 | 10-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 627.43 | 22-JUL-17:45 | 166.35 | 26-JUL-24:00 |
August | 827.22 | 01-AUG-09:09 | 879.10 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 553.89 | 13-AUG-15:55 | 252.91 | 05-AUG-17:50 |
September | 827.22 | 01-SEP-09:09 | 574.53 | 18-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.79 | 17-SEP-12:00 | 171.20 | 03-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 703.38 | 13-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.96 | 01-OCT-14:58 | 533.69 | 22-OCT-14:00 |
November | 827.22 | 01-NOV-09:09 | 1007.95 | 28-NOV-16:19 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.60 | 19-NOV-15:00 | 448.95 | 29-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 1007.95 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.21 | 25-DEC-16:00 | 384.64 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.34 | |||||
Maximum of Months | 827.22 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 627.43 | 543.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 20-JAN-08:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.20 | 31-JAN-14:00 | 673.77 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1388.60 | 10-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 869.85 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 1388.60 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.18 | 15-MAR-13:00 | 706.62 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 1111.04 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 496.54 | 30-APR-15:46 | 365.98 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 833.48 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 457.05 | 20-MAY-17:02 | 305.64 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 833.48 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 735.18 | 17-JUN-17:10 | 155.30 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 1111.04 | 10-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 933.92 | 22-JUL-17:45 | 247.91 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 1388.60 | 04-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 830.20 | 13-AUG-15:55 | 384.20 | 05-AUG-17:50 |
September | 1306.65 | 01-SEP-09:09 | 1111.04 | 05-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 573.42 | 17-SEP-12:27 | 261.54 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1314.57 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.86 | 01-OCT-14:55 | 866.08 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 28-NOV-16:30 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.90 | 19-NOV-15:35 | 702.93 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 21-DEC-15:00 | 599.35 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.30 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 933.92 | 869.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1007.89 | 20-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 79.63 | 16-JAN-11:57 | 417.31 | 01-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 1007.89 | 03-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 557.55 | 02-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 1007.89 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.46 | 15-MAR-13:00 | 468.27 | 28-MAR-04:00 |
April | 827.17 | 03-APR-09:09 | 832.18 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 328.09 | 30-APR-15:04 | 254.64 | 26-APR-21:20 |
May | 827.17 | 01-MAY-09:09 | 656.47 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 313.90 | 20-MAY-18:30 | 207.88 | 23-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 656.47 | 22-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 491.67 | 17-JUN-17:10 | 108.37 | 13-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 703.34 | 10-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 611.80 | 22-JUL-18:00 | 177.26 | 26-JUL-24:00 |
August | 827.17 | 01-AUG-09:09 | 879.04 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 553.46 | 13-AUG-15:55 | 254.28 | 05-AUG-17:50 |
September | 827.17 | 01-SEP-09:09 | 879.04 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 416.10 | 17-SEP-12:00 | 170.85 | 03-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 1007.89 | 27-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.58 | 01-OCT-14:58 | 499.14 | 22-OCT-14:00 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 02-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.23 | 19-NOV-11:55 | 447.78 | 29-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.78 | 25-DEC-14:00 | 387.67 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 656.47 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.37 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 611.80 | 557.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 20-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.12 | 16-JAN-12:20 | 374.53 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 03-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 461.47 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 1388.60 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.15 | 18-MAR-17:03 | 391.38 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 1111.04 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 304.77 | 30-APR-15:30 | 210.07 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 833.48 | 25-MAY-12:20 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.21 | 20-MAY-18:10 | 169.02 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 759.45 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 401.90 | 17-JUN-17:03 | 83.89 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 10-JUL-15:50 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 495.31 | 22-JUL-17:45 | 137.54 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 1388.60 | 04-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 446.02 | 13-AUG-15:55 | 205.40 | 05-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 1111.04 | 05-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.04 | 17-SEP-12:00 | 155.76 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.47 | 01-OCT-14:38 | 417.48 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 02-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.84 | 19-NOV-14:42 | 413.49 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.74 | 25-DEC-16:00 | 346.76 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.89 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 495.31 | 461.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1007.95 | 20-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 29-JAN-16:00 | 265.78 | 01-JAN-01:00 |
February | 827.22 | 01-FEB-10:09 | 879.10 | 07-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 322.47 | 02-FEB-23:00 |
March | 827.22 | 01-MAR-10:09 | 703.38 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.97 | 18-MAR-17:03 | 271.75 | 28-MAR-04:00 |
April | 827.22 | 03-APR-09:09 | 480.79 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.98 | 30-APR-15:50 | 180.49 | 16-APR-08:40 |
May | 827.22 | 01-MAY-09:09 | 527.66 | 25-MAY-15:09 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.51 | 20-MAY-17:50 | 116.36 | 23-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 480.79 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.45 | 17-JUN-19:00 | 61.61 | 11-JUN-06:20 |
July | 827.22 | 03-JUL-09:09 | 574.53 | 10-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.64 | 22-JUL-18:00 | 96.40 | 26-JUL-24:00 |
August | 827.22 | 01-AUG-09:09 | 879.10 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.11 | 13-AUG-15:55 | 141.02 | 05-AUG-17:50 |
September | 827.22 | 01-SEP-09:09 | 574.53 | 29-SEP-14:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.21 | 17-SEP-12:20 | 106.70 | 03-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 703.38 | 13-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.83 | 01-OCT-14:38 | 304.59 | 22-OCT-14:00 |
November | 827.22 | 01-NOV-09:09 | 1007.95 | 28-NOV-16:19 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.22 | 19-NOV-15:10 | 284.71 | 29-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 1007.95 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.79 | 25-DEC-16:00 | 235.20 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.61 | |||||
Maximum of Months | 827.22 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 339.64 | 322.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 20-JAN-08:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4866.67 | 31-JAN-17:10 | 17961.76 | 12-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 1388.60 | 10-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 18451.47 | 01-FEB-07:02 |
March | 1306.65 | 01-MAR-10:09 | 1388.60 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5353.11 | 20-MAR-17:00 | 21293.25 | 27-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 1111.04 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11336.21 | 14-APR-16:03 | 13470.73 | 21-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 833.48 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13514.67 | 31-MAY-16:02 | 9943.67 | 01-MAY-06:02 |
June | 1306.65 | 01-JUN-09:09 | 833.48 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18564.62 | 28-JUN-16:01 | 4362.11 | 21-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 1111.04 | 13-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15579.51 | 20-JUL-16:01 | 1917.16 | 03-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 1388.60 | 04-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17583.66 | 25-AUG-16:01 | 4767.60 | 24-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 1111.04 | 05-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14049.49 | 08-SEP-16:01 | 6917.79 | 22-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1314.57 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11118.93 | 03-OCT-16:02 | 18680.57 | 25-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 28-NOV-16:30 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3676.80 | 01-NOV-16:05 | 18915.45 | 24-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 331.03 | 21-DEC-15:00 | 24484.16 | 05-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1917.16 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 18564.62 | 24484.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1007.89 | 20-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.53 | 16-JAN-12:00 | 273.66 | 01-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 1007.89 | 03-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 327.41 | 02-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 1007.89 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.16 | 15-MAR-13:00 | 275.20 | 28-MAR-04:00 |
April | 827.17 | 03-APR-09:09 | 703.34 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.71 | 30-APR-15:04 | 145.67 | 21-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 656.47 | 05-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.90 | 20-MAY-18:30 | 120.15 | 23-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 527.63 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.16 | 17-JUN-17:03 | 62.30 | 13-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 703.34 | 10-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.85 | 22-JUL-18:00 | 101.72 | 26-JUL-24:00 |
August | 827.17 | 01-AUG-09:09 | 879.04 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.62 | 13-AUG-15:55 | 140.64 | 05-AUG-17:50 |
September | 827.17 | 01-SEP-09:09 | 879.04 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.30 | 17-SEP-12:00 | 105.52 | 03-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 1007.89 | 27-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.36 | 01-OCT-14:38 | 287.84 | 22-OCT-14:00 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 02-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.84 | 19-NOV-12:43 | 283.95 | 29-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.05 | 25-DEC-13:52 | 235.46 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 527.63 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.30 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 326.85 | 327.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 20-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.92 | 16-JAN-11:53 | 566.68 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 03-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 730.99 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 1388.60 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 69.75 | 18-MAR-17:03 | 623.61 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 1111.04 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 427.00 | 30-APR-15:10 | 327.71 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 833.48 | 25-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 394.48 | 20-MAY-17:02 | 271.14 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 759.45 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 607.28 | 17-JUN-17:03 | 136.62 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 10-JUL-15:39 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 773.02 | 22-JUL-17:43 | 209.73 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 1388.60 | 04-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 693.13 | 13-AUG-15:55 | 310.72 | 05-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 1388.60 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 487.81 | 17-SEP-12:00 | 222.68 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 27-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.16 | 01-OCT-14:38 | 620.35 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 02-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.64 | 19-NOV-13:05 | 616.34 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 64.62 | 25-DEC-15:52 | 524.26 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.62 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 773.02 | 730.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1007.95 | 20-JAN-08:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.60 | 29-JAN-16:00 | 384.28 | 01-JAN-01:00 |
February | 805.43 | 01-FEB-08:09 | 879.10 | 07-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 488.46 | 02-FEB-23:00 |
March | 805.43 | 01-MAR-08:09 | 703.38 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.61 | 18-MAR-17:03 | 415.37 | 28-MAR-04:00 |
April | 805.43 | 03-APR-07:10 | 480.79 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.47 | 30-APR-15:30 | 299.32 | 16-APR-08:30 |
May | 805.43 | 01-MAY-07:10 | 527.66 | 25-MAY-15:09 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.79 | 20-MAY-18:00 | 179.81 | 23-MAY-05:00 |
June | 805.43 | 01-JUN-07:10 | 480.79 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 411.68 | 17-JUN-17:03 | 97.55 | 11-JUN-06:10 |
July | 805.43 | 03-JUL-07:10 | 574.53 | 10-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 530.35 | 22-JUL-18:00 | 139.94 | 26-JUL-24:00 |
August | 805.43 | 01-AUG-07:10 | 879.10 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 462.57 | 13-AUG-15:55 | 209.48 | 05-AUG-18:00 |
September | 805.43 | 01-SEP-07:10 | 574.53 | 18-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.49 | 17-SEP-12:00 | 147.73 | 03-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 703.38 | 13-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.67 | 01-OCT-14:38 | 449.09 | 22-OCT-14:00 |
November | 805.43 | 01-NOV-07:10 | 1007.95 | 28-NOV-16:19 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.74 | 19-NOV-15:00 | 410.15 | 29-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 1007.95 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.85 | 25-DEC-16:10 | 348.54 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.55 | |||||
Maximum of Months | 805.43 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 530.35 | 488.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 20-JAN-08:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.12 | 31-JAN-14:10 | 632.03 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1388.60 | 10-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 780.65 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 1388.60 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.63 | 15-MAR-13:00 | 636.81 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 1111.04 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 409.90 | 30-APR-15:24 | 329.60 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 833.48 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 394.93 | 20-MAY-18:00 | 270.89 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 833.48 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 612.07 | 17-JUN-17:03 | 135.84 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 1111.04 | 10-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 775.62 | 22-JUL-17:45 | 208.60 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 1388.60 | 04-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 692.66 | 13-AUG-15:55 | 318.28 | 05-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 1111.04 | 05-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 477.21 | 17-SEP-12:27 | 225.58 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1314.57 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.96 | 01-OCT-14:38 | 726.44 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 28-NOV-16:30 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.47 | 01-NOV-16:00 | 640.01 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.84 | 21-DEC-15:00 | 541.80 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.84 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 775.62 | 780.65 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1007.89 | 20-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.17 | 16-JAN-12:00 | 395.15 | 01-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 1007.89 | 03-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 501.41 | 02-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 1007.89 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.76 | 15-MAR-13:00 | 422.18 | 28-MAR-04:00 |
April | 827.17 | 03-APR-09:09 | 832.18 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.49 | 30-APR-15:24 | 220.57 | 21-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 656.47 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 257.99 | 20-MAY-18:30 | 184.01 | 23-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 656.47 | 22-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 417.21 | 17-JUN-17:03 | 94.65 | 13-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 703.34 | 10-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 510.49 | 22-JUL-18:00 | 148.86 | 26-JUL-24:00 |
August | 827.17 | 01-AUG-09:09 | 879.04 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 461.77 | 13-AUG-15:55 | 211.07 | 05-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 879.04 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.16 | 17-SEP-12:00 | 147.54 | 03-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 1007.89 | 27-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.11 | 01-OCT-14:38 | 422.12 | 22-OCT-14:00 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 02-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.11 | 19-NOV-12:20 | 410.21 | 29-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.02 | 25-DEC-13:52 | 350.85 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 656.47 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.65 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 510.49 | 501.41 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.57 | 31-JAN-14:00 | 892.75 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1096.75 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.91 | 18-MAR-17:03 | 916.62 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545.87 | 30-APR-14:52 | 473.76 | 21-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.69 | 20-MAY-17:02 | 382.52 | 23-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 812.56 | 17-JUN-17:03 | 186.37 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1000.89 | 22-JUL-18:00 | 283.66 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 874.70 | 13-AUG-16:00 | 427.22 | 05-AUG-17:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 633.50 | 17-SEP-12:00 | 317.82 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.31 | 01-OCT-14:23 | 855.66 | 22-OCT-14:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.02 | 19-NOV-14:52 | 922.51 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 25-DEC-16:00 | 778.69 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.37 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1000.89 | 1096.75 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.08 | 16-JAN-12:00 | 1039.58 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1359.33 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.03 | 18-MAR-17:03 | 1139.16 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 699.12 | 30-APR-15:10 | 598.58 | 21-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656.35 | 20-MAY-17:02 | 488.87 | 23-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1048.88 | 17-JUN-17:03 | 240.08 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1286.08 | 22-JUL-18:00 | 361.81 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1115.34 | 13-AUG-16:00 | 541.05 | 05-AUG-17:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 828.25 | 17-SEP-12:00 | 398.83 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.62 | 01-OCT-14:23 | 1037.83 | 22-OCT-14:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.71 | 19-NOV-14:50 | 1128.92 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.33 | 25-DEC-16:00 | 959.81 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.08 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1286.08 | 1359.33 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.40 | 16-JAN-11:43 | 910.54 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1238.94 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.44 | 15-MAR-13:00 | 1039.43 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.70 | 30-APR-16:00 | 555.91 | 26-APR-21:03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.45 | 20-MAY-17:02 | 438.00 | 23-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1074.91 | 17-JUN-17:03 | 212.92 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1264.21 | 22-JUL-18:00 | 375.45 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1034.39 | 13-AUG-16:00 | 629.60 | 05-AUG-17:35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 802.72 | 17-SEP-12:00 | 397.13 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.41 | 01-OCT-14:30 | 1343.71 | 22-OCT-14:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.87 | 19-NOV-14:42 | 1011.04 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.38 | 25-DEC-14:00 | 868.68 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.92 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1264.21 | 1343.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 22535.14 | 27-JAN-07:03 | 5082.11 | 10070.13 | 35187.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24371.50 | 01-FEB-07:02 | 7623.17 | 15105.19 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27426.17 | 17-MAR-06:03 | 5082.11 | 10070.13 | 35187.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41463.81 | 26-APR-05:12 | 2541.06 | 3356.58 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44357.27 | 30-MAY-05:12 | 2541.06 | 3356.58 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 45681.12 | 27-JUN-04:02 | 0.00 | 4195.72 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 45245.85 | 26-JUL-04:03 | 0.00 | 3356.58 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 44772.71 | 09-AUG-04:03 | 0.00 | 3356.58 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44619.26 | 27-SEP-05:12 | 2541.06 | 3356.58 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 42590.76 | 10-OCT-06:02 | 7623.17 | 15105.19 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 42248.27 | 13-NOV-07:02 | 6352.64 | 12587.66 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21496.22 | 28-DEC-17:00 | 6035.01 | 7552.50 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 21496.22 | 0.00 | 3356.58 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45681.12 | 7623.17 | 15105.19 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6194.94 | 31-JAN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.27 | 0.00 |
February | 4500.37 | 23-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.15 |
March | 7381.33 | 16-MAR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.78 | 0.00 |
April | 11490.18 | 14-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.49 | 0.00 |
May | 11425.57 | 19-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.94 | 0.00 |
June | 13881.41 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.65 | 0.00 |
July | 13056.10 | 20-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.31 | 0.00 |
August | 13128.92 | 09-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.28 | 0.00 |
September | 12273.14 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.76 | 0.00 |
October | 11135.74 | 02-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.36 | 0.00 |
November | 7550.07 | 01-NOV-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.85 | 0.00 |
December | 4998.48 | 22-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4500.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13881.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.65 | 69.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2154.26 | 27-JAN-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 | 0.00 |
February | 1966.10 | 09-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.08 |
March | 3153.39 | 29-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 |
April | 4781.77 | 25-APR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.26 | 0.00 |
May | 5286.22 | 08-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.45 | 0.00 |
June | 6546.39 | 19-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.28 | 0.00 |
July | 6356.63 | 31-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.86 | 0.00 |
August | 6502.07 | 14-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.30 | 0.00 |
September | 6154.80 | 05-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.68 | 0.00 |
October | 5926.71 | 02-OCT-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.16 | 0.00 |
November | 3177.14 | 01-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.55 | 0.00 |
December | 2801.07 | 14-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1966.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6546.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.28 | 204.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3076.86 | 27-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.56 | 0.00 |
February | 2870.89 | 09-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.59 |
March | 3308.30 | 28-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.91 |
April | 5169.08 | 25-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.55 | 0.00 |
May | 6070.93 | 08-MAY-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.91 | 0.00 |
June | 7799.73 | 19-JUN-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.25 | 0.00 |
July | 8082.03 | 05-JUL-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.84 | 0.00 |
August | 7521.83 | 09-AUG-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.39 | 0.00 |
September | 7126.14 | 08-SEP-17:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.14 | 0.00 |
October | 6180.35 | 04-OCT-17:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.75 | 0.00 |
November | 3954.84 | 02-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.36 | 0.00 |
December | 3532.88 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2870.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8082.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.25 | 197.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14677.56 | 27-JAN-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13379.38 | 01-FEB-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15436.61 | 17-MAR-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27409.20 | 26-APR-05:12 | 2541.06 | 3356.58 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34174.48 | 30-MAY-05:12 | 2541.06 | 3356.58 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34498.60 | 12-JUN-05:12 | 2541.06 | 3356.58 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34669.51 | 25-JUL-04:03 | 0.00 | 3356.58 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34583.65 | 21-AUG-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34595.13 | 19-SEP-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33777.97 | 02-OCT-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16207.98 | 02-NOV-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13466.01 | 22-DEC-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13379.38 | 0.00 | 3356.58 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34669.51 | 6035.01 | 7552.50 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14621.04 | 27-JAN-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12740.73 | 22-FEB-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16753.71 | 17-MAR-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20154.09 | 25-APR-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26996.85 | 08-MAY-06:03 | 3811.58 | 7552.60 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37819.07 | 27-JUN-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 38622.39 | 24-JUL-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38453.38 | 21-AUG-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38102.41 | 08-SEP-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 37804.00 | 02-OCT-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17075.57 | 01-NOV-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13108.94 | 22-DEC-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12740.73 | 0.00 | 4195.72 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38622.39 | 6035.01 | 7552.60 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3059.27 | 31-JAN-16:30 | 1272.23 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 21.31 | 0.00 |
February | 2207.47 | 22-FEB-16:30 | 1272.23 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 |
March | 4385.20 | 16-MAR-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 39.72 | 0.00 |
April | 6936.55 | 30-APR-16:22 | 401.76 | 253.14 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 403.59 | 0.00 |
May | 11574.46 | 07-MAY-17:32 | 0.00 | 253.14 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 352.64 | 0.00 |
June | 15005.35 | 25-JUN-18:21 | 0.00 | 295.33 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 537.32 | 0.00 |
July | 15140.06 | 16-JUL-18:01 | 0.00 | 337.52 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 559.01 | 0.00 |
August | 14988.82 | 13-AUG-16:11 | 468.72 | 295.33 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 754.61 | 0.00 |
September | 13548.07 | 17-SEP-13:43 | 267.84 | 168.76 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 398.01 | 0.00 |
October | 10903.55 | 02-OCT-04:02 | 0.00 | 884.49 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 9.60 | 0.00 |
November | 4356.30 | 01-NOV-15:30 | 1272.23 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 35.02 | 0.00 |
December | 2257.90 | 22-DEC-16:50 | 1272.23 | 1314.57 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2207.47 | 0.00 | 168.76 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15140.06 | 1272.23 | 1314.57 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 754.61 | 37.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2994.13 | 27-JAN-10:30 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.89 |
February | 3215.34 | 23-FEB-10:30 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.45 |
March | 4619.04 | 23-MAR-10:30 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 |
April | 11074.94 | 30-APR-09:42 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 | 0.00 |
May | 11818.79 | 07-MAY-09:32 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 0.00 |
June | 13790.73 | 18-JUN-09:02 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 108.31 | 0.00 |
July | 14742.43 | 23-JUL-09:21 | 296.74 | 186.97 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.38 | 0.00 |
August | 13720.36 | 13-AUG-09:32 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 47.46 | 0.00 |
September | 11975.31 | 10-SEP-10:22 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 97.38 | 0.00 |
October | 8794.31 | 15-OCT-09:43 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.20 |
November | 3932.94 | 01-NOV-10:20 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 |
December | 1995.43 | 25-DEC-15:52 | 211.95 | 146.57 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 40.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1995.43 | 169.56 | 106.84 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14742.43 | 827.22 | 480.79 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.31 | 30.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17384.80 | 29-JAN-14:22 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.24 |
February | 9504.95 | 28-FEB-14:10 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 |
March | 8999.95 | 16-MAR-13:40 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 24.29 | 0.00 |
April | 16505.29 | 23-APR-13:23 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 99.01 | 0.00 |
May | 13603.12 | 07-MAY-15:32 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 278.24 | 0.00 |
June | 16026.89 | 04-JUN-16:41 | 468.72 | 295.33 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 408.87 | 0.00 |
July | 16342.40 | 16-JUL-17:21 | 0.00 | 337.52 | 3088.80 | 0.00 | 0.00 | 0.00 | 0.00 | 636.48 | 0.00 |
August | 16640.60 | 13-AUG-16:11 | 468.72 | 295.33 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 742.81 | 0.00 |
September | 16982.20 | 10-SEP-13:02 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 304.63 | 0.00 |
October | 18309.36 | 09-OCT-13:12 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 49.08 | 0.00 |
November | 16996.72 | 19-NOV-14:12 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 |
December | 17358.55 | 25-DEC-14:32 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8999.95 | 0.00 | 168.76 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18309.36 | 1306.65 | 759.45 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 742.81 | 73.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7322.82 | 29-JAN-16:22 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.50 |
February | 6017.75 | 22-FEB-16:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.29 |
March | 8298.38 | 18-MAR-17:08 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 | 0.00 |
April | 15252.17 | 23-APR-16:42 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 195.64 | 0.00 |
May | 15509.64 | 28-MAY-17:12 | 0.00 | 160.25 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 174.72 | 0.00 |
June | 16028.95 | 25-JUN-17:41 | 0.00 | 186.96 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 337.91 | 0.00 |
July | 16061.00 | 16-JUL-17:21 | 0.00 | 213.67 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 366.41 | 0.00 |
August | 16082.25 | 13-AUG-16:51 | 296.72 | 186.96 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 391.40 | 0.00 |
September | 15149.11 | 04-SEP-15:52 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 58.60 | 0.00 |
October | 15749.58 | 09-OCT-15:52 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 113.09 | 0.00 |
November | 7467.59 | 01-NOV-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 27.48 | 0.00 |
December | 6177.13 | 22-DEC-16:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6017.75 | 0.00 | 106.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16082.25 | 805.38 | 480.76 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 391.40 | 48.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2312.16 | 27-JAN-16:30 | 1272.23 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 | 0.00 |
February | 1558.53 | 22-FEB-16:40 | 1272.23 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.14 |
March | 2982.43 | 20-MAR-14:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 | 0.00 |
April | 5154.14 | 25-APR-15:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 59.82 | 0.00 |
May | 5770.64 | 08-MAY-15:20 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.36 | 0.00 |
June | 12810.04 | 25-JUN-17:31 | 0.00 | 421.90 | 3861.03 | 0.00 | 0.00 | 0.00 | 0.00 | 273.69 | 0.00 |
July | 12859.38 | 16-JUL-18:11 | 0.00 | 337.52 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 247.63 | 0.00 |
August | 12593.67 | 27-AUG-17:41 | 0.00 | 370.43 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 242.65 | 0.00 |
September | 11144.24 | 17-SEP-16:52 | 334.80 | 210.95 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 81.90 | 0.00 |
October | 9611.64 | 01-OCT-13:53 | 267.84 | 168.76 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 178.34 | 0.00 |
November | 4111.07 | 02-NOV-14:00 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 | 0.00 |
December | 1986.55 | 24-DEC-15:43 | 267.84 | 246.89 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1558.53 | 0.00 | 168.76 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12859.38 | 1306.65 | 833.48 | 3861.03 | 0.00 | 0.00 | 0.00 | 0.00 | 273.69 | 19.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2896.93 | 27-JAN-10:30 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.15 |
February | 2600.43 | 23-FEB-10:30 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.98 |
March | 3687.78 | 23-MAR-10:30 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 |
April | 11640.90 | 23-APR-09:52 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 | 0.00 |
May | 12032.12 | 29-MAY-09:52 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 | 0.00 |
June | 12548.76 | 25-JUN-09:31 | 296.74 | 186.97 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.10 | 0.00 |
July | 12673.43 | 30-JUL-09:31 | 296.74 | 186.97 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.47 | 0.00 |
August | 12303.75 | 27-AUG-11:02 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 102.69 | 0.00 |
September | 12205.97 | 04-SEP-09:42 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.36 |
October | 8596.57 | 15-OCT-09:43 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 |
November | 4103.94 | 02-NOV-08:40 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.91 |
December | 2490.84 | 01-DEC-10:30 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2490.84 | 169.56 | 106.84 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12673.43 | 827.22 | 480.79 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.69 | 16.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14662.07 | 29-JAN-14:22 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.18 |
February | 8674.74 | 27-FEB-13:06 | 6361.16 | 3797.24 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1354.54 |
March | 10346.24 | 16-MAR-16:10 | 401.76 | 421.91 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 5270.32 | 0.00 |
April | 12861.36 | 14-APR-16:10 | 1607.03 | 1687.66 | 3189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 10084.77 | 0.00 |
May | 13263.48 | 15-MAY-17:00 | 401.76 | 421.91 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 11752.66 | 0.00 |
June | 15314.54 | 28-JUN-17:00 | 401.76 | 421.91 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 14840.10 | 0.00 |
July | 14360.70 | 20-JUL-17:00 | 401.76 | 421.91 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 12908.72 | 0.00 |
August | 15081.94 | 25-AUG-17:00 | 401.76 | 421.91 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 14064.72 | 0.00 |
September | 14576.10 | 04-SEP-13:02 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 35.55 | 0.00 |
October | 15437.12 | 09-OCT-13:02 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 28.45 | 0.00 |
November | 14300.00 | 05-NOV-13:32 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.14 |
December | 14311.42 | 25-DEC-12:13 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8674.74 | 267.84 | 168.76 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15437.12 | 6361.16 | 3797.24 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 14840.10 | 1354.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5511.27 | 29-JAN-16:22 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.03 |
February | 4375.34 | 22-FEB-16:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 |
March | 5272.33 | 18-MAR-17:10 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 0.00 |
April | 12727.81 | 16-APR-17:42 | 0.00 | 133.54 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 |
May | 13629.62 | 29-MAY-17:51 | 0.00 | 213.67 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 0.00 |
June | 14189.84 | 25-JUN-17:31 | 0.00 | 267.08 | 2444.18 | 0.00 | 0.00 | 0.00 | 0.00 | 148.94 | 0.00 |
July | 14076.66 | 30-JUL-18:11 | 0.00 | 240.37 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 176.14 | 0.00 |
August | 13881.84 | 27-AUG-17:41 | 0.00 | 213.67 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 137.03 | 0.00 |
September | 13271.80 | 04-SEP-17:01 | 0.00 | 186.96 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 36.61 | 0.00 |
October | 12903.00 | 09-OCT-15:42 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 56.19 | 0.00 |
November | 6789.59 | 01-NOV-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 0.00 |
December | 5580.82 | 22-DEC-16:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4375.34 | 0.00 | 106.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14189.84 | 805.38 | 480.76 | 2444.18 | 0.00 | 0.00 | 0.00 | 0.00 | 176.14 | 26.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3024.07 | 27-JAN-16:30 | 1272.23 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 0.00 |
February | 2163.65 | 22-FEB-16:20 | 1272.23 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.85 |
March | 4132.40 | 20-MAR-14:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 0.00 |
April | 6044.76 | 25-APR-15:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 93.39 | 0.00 |
May | 12706.50 | 29-MAY-18:31 | 0.00 | 295.33 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 184.61 | 0.00 |
June | 13585.64 | 25-JUN-17:32 | 0.00 | 421.90 | 3861.03 | 0.00 | 0.00 | 0.00 | 0.00 | 449.61 | 0.00 |
July | 13360.83 | 30-JUL-18:11 | 0.00 | 379.71 | 3474.93 | 0.00 | 0.00 | 0.00 | 0.00 | 491.82 | 0.00 |
August | 12836.16 | 27-AUG-18:31 | 0.00 | 619.15 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 304.52 | 0.00 |
September | 11635.41 | 04-SEP-16:21 | 468.72 | 295.33 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 100.26 | 0.00 |
October | 10812.90 | 01-OCT-13:53 | 267.84 | 168.76 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 278.03 | 0.00 |
November | 4117.33 | 01-NOV-15:30 | 1272.23 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.32 | 0.00 |
December | 2311.73 | 22-DEC-17:00 | 1272.23 | 1388.60 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2163.65 | 0.00 | 168.76 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13585.64 | 1272.23 | 1388.60 | 3861.03 | 0.00 | 0.00 | 0.00 | 0.00 | 491.82 | 29.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3532.03 | 27-JAN-10:00 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.69 |
February | 3725.46 | 23-FEB-10:00 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.94 |
March | 4849.86 | 23-MAR-10:20 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 |
April | 12963.86 | 23-APR-09:12 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.66 |
May | 13423.37 | 29-MAY-09:12 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.80 |
June | 13956.25 | 25-JUN-08:51 | 296.74 | 186.97 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.26 | 0.00 |
July | 14015.42 | 30-JUL-09:31 | 296.74 | 186.97 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.62 | 0.00 |
August | 13909.15 | 27-AUG-09:11 | 296.74 | 186.97 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.97 | 0.00 |
September | 13312.69 | 04-SEP-09:42 | 254.35 | 160.26 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.43 |
October | 8264.12 | 01-OCT-13:53 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 184.91 | 0.00 |
November | 4388.94 | 10-NOV-09:40 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.11 |
December | 2454.39 | 01-DEC-10:00 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2454.39 | 169.56 | 106.84 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14015.42 | 805.43 | 480.79 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.91 | 31.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15299.31 | 15-JAN-13:52 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.70 |
February | 9351.36 | 28-FEB-14:00 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.96 |
March | 8588.12 | 23-MAR-13:50 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 23.14 | 0.00 |
April | 14723.53 | 30-APR-13:23 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 269.64 | 0.00 |
May | 12062.99 | 07-MAY-13:13 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 206.29 | 0.00 |
June | 14613.12 | 25-JUN-17:31 | 0.00 | 463.03 | 3861.01 | 0.00 | 0.00 | 0.00 | 0.00 | 428.21 | 0.00 |
July | 14744.92 | 30-JUL-18:11 | 0.00 | 416.73 | 3474.90 | 0.00 | 0.00 | 0.00 | 0.00 | 497.22 | 0.00 |
August | 14535.11 | 27-AUG-15:51 | 669.60 | 421.90 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 471.61 | 0.00 |
September | 15279.07 | 04-SEP-13:02 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 53.71 | 0.00 |
October | 15000.73 | 09-OCT-13:22 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 51.32 | 0.00 |
November | 15245.51 | 19-NOV-13:32 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.95 |
December | 15521.38 | 25-DEC-14:42 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8588.12 | 0.00 | 168.76 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15521.38 | 1306.65 | 759.45 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 497.22 | 85.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5998.73 | 31-JAN-16:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 11.89 | 0.00 |
February | 5890.89 | 22-FEB-16:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 |
March | 7463.15 | 18-MAR-17:08 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 | 0.00 |
April | 14748.11 | 02-APR-17:01 | 0.00 | 186.96 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 25.99 | 0.00 |
May | 14892.39 | 29-MAY-17:51 | 0.00 | 213.67 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 74.08 | 0.00 |
June | 15927.69 | 25-JUN-17:31 | 0.00 | 267.08 | 2444.18 | 0.00 | 0.00 | 0.00 | 0.00 | 216.47 | 0.00 |
July | 15410.91 | 30-JUL-18:11 | 0.00 | 240.37 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 268.29 | 0.00 |
August | 14492.84 | 27-AUG-16:31 | 423.88 | 267.08 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 215.66 | 0.00 |
September | 14535.82 | 04-SEP-16:21 | 296.72 | 186.96 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 | 0.00 |
October | 11559.83 | 15-OCT-15:52 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 57.14 | 0.00 |
November | 7303.18 | 19-NOV-15:32 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 | 0.00 |
December | 7357.67 | 25-DEC-16:42 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5890.89 | 0.00 | 106.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15927.69 | 805.38 | 480.76 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 268.29 | 39.67 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.124457E+12 | 142477.36 | 02-JAN-07:10 | 0.111283E+11 | 22522.02 | 02-JAN-07:30 |
February | 0.102818E+12 | 103815.18 | 13-FEB-07:10 | 0.101251E+11 | 16608.01 | 01-FEB-07:30 |
March | 0.127003E+12 | 125871.45 | 16-MAR-15:39 | 0.114132E+11 | 30296.32 | 27-MAR-06:19 |
April | 0.147392E+12 | 162218.15 | 14-APR-15:30 | 0.997473E+10 | 9728.55 | 03-APR-11:50 |
May | 0.170868E+12 | 168109.41 | 31-MAY-15:00 | 0.100675E+11 | 9605.07 | 01-MAY-11:50 |
June | 0.202440E+12 | 198414.89 | 28-JUN-15:09 | 0.951522E+10 | 9489.17 | 02-JUN-11:09 |
July | 0.191599E+12 | 185436.39 | 31-JUL-15:00 | 0.935999E+10 | 9413.82 | 03-JUL-11:09 |
August | 0.200847E+12 | 191120.56 | 25-AUG-15:09 | 0.974982E+10 | 9442.17 | 30-AUG-11:20 |
September | 0.174377E+12 | 179659.74 | 08-SEP-15:00 | 0.942253E+10 | 9532.25 | 27-SEP-11:20 |
October | 0.145861E+12 | 162532.51 | 02-OCT-15:09 | 0.101417E+11 | 15916.33 | 25-OCT-06:00 |
November | 0.122528E+12 | 129186.21 | 01-NOV-15:00 | 0.103154E+11 | 19691.96 | 24-NOV-07:19 |
December | 0.117712E+12 | 118905.30 | 18-DEC-07:10 | 0.121735E+11 | 37748.58 | 06-DEC-07:10 |
Annual Sum or Average | 0.182790E+13 | 0.123387E+12 | ||||
Minimum of Months | 0.102818E+12 | 103815.18 | 0.935999E+10 | 9413.82 | ||
Maximum of Months | 0.202440E+12 | 198414.89 | 0.121735E+11 | 37748.58 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.310371E+11 | 0.112494E+11 | 0.593559E+11 | 0.143906E+10 | 0.664887E+10 | 12379742.02 | 0.220857E+10 | 0.125061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.279819E+11 | 0.955945E+10 | 0.537310E+11 | 0.130216E+10 | 0.481266E+10 | 11196021.66 | 0.234051E+10 | 0.307874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.326444E+11 | 0.968658E+10 | 0.617796E+11 | 0.150718E+10 | 0.667712E+10 | 12675672.10 | 0.191136E+10 | 0.127838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.288866E+11 | 0.845617E+10 | 0.572952E+11 | 0.138497E+10 | 0.126909E+11 | 11960507.72 | 0.154399E+09 | 0.385114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.309904E+11 | 0.794837E+10 | 0.605677E+11 | 0.147220E+10 | 0.162541E+11 | 12527707.06 | 7584402.11 | 0.536148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.306753E+11 | 0.736270E+10 | 0.594895E+11 | 0.144941E+10 | 0.223262E+11 | 12231776.97 | 0.00 | 0.811247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.288818E+11 | 0.773174E+10 | 0.583622E+11 | 0.140739E+10 | 0.199773E+11 | 12256437.81 | 0.00 | 0.752259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.323734E+11 | 0.838163E+10 | 0.617796E+11 | 0.150693E+10 | 0.204353E+11 | 12675672.10 | 0.00 | 0.763572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.290695E+11 | 0.896680E+10 | 0.572729E+11 | 0.138479E+10 | 0.164266E+11 | 11960507.72 | 0.00 | 0.612448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.306145E+11 | 0.102230E+11 | 0.593671E+11 | 0.143874E+10 | 0.110364E+11 | 12379742.02 | 0.468940E+09 | 0.327004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.305739E+11 | 0.106947E+11 | 0.580818E+11 | 0.141246E+10 | 0.732163E+10 | 12059151.09 | 0.109936E+10 | 0.133316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.302385E+11 | 0.115022E+11 | 0.583511E+11 | 0.140876E+10 | 0.567518E+10 | 12256437.81 | 0.459341E+10 | 0.593051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.363967E+12 | 0.111763E+12 | 0.705434E+12 | 0.171140E+11 | 0.150282E+12 | 0.146559E+09 | 0.127841E+11 | 0.466410E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.279819E+11 | 0.736270E+10 | 0.537310E+11 | 0.130216E+10 | 0.481266E+10 | 11196021.66 | 0.00 | 0.307874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.326444E+11 | 0.115022E+11 | 0.617796E+11 | 0.150718E+10 | 0.223262E+11 | 12675672.10 | 0.459341E+10 | 0.811247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.187952E+09 | 0.00 | 0.109403E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.254811E+09 | 0.00 | 0.987029E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.413946E+09 | 0.00 | 0.109992E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.997473E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.100675E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.951522E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.935999E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.974982E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.942253E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 51516627.16 | 0.00 | 0.100901E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.106617E+09 | 0.00 | 0.102087E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.150776E+10 | 0.00 | 0.106657E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.252260E+10 | 0.00 | 0.120864E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.935999E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.150776E+10 | 0.00 | 0.109992E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 38257.79 | 20-JAN-16:00 | 8596.48 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 1241.92 | 20-JAN-08:39 | 12258.79 | 27-JAN-16:00 | 6.85 | 12-JAN-08:09 | 95722.24 | 02-JAN-07:10 |
February | 36263.56 | 10-FEB-08:09 | 8596.48 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 1238.27 | 10-FEB-08:20 | 8647.67 | 22-FEB-16:30 | 6.85 | 01-FEB-08:09 | 57472.75 | 13-FEB-07:10 |
March | 35982.31 | 21-MAR-07:10 | 8596.48 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 1237.72 | 21-MAR-07:19 | 13892.23 | 16-MAR-15:30 | 6.85 | 07-MAR-08:09 | 57339.15 | 27-MAR-06:10 |
April | 33133.82 | 04-APR-07:10 | 8596.48 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 1232.15 | 04-APR-07:19 | 23938.37 | 25-APR-15:30 | 6.85 | 02-APR-16:30 | 12166.01 | 21-APR-06:10 |
May | 30964.85 | 26-MAY-08:30 | 8596.48 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 1227.70 | 05-MAY-07:19 | 25494.95 | 18-MAY-15:30 | 6.85 | 07-MAY-15:30 | 3183.79 | 01-MAY-06:10 |
June | 30719.22 | 22-JUN-07:10 | 8596.48 | 01-JUN-05:10 | 45864.70 | 01-JUN-07:10 | 1227.45 | 22-JUN-07:19 | 29552.23 | 19-JUN-15:09 | 6.85 | 02-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 32043.45 | 27-JUL-07:10 | 8596.48 | 01-JUL-05:10 | 45864.70 | 03-JUL-07:10 | 1230.03 | 27-JUL-07:19 | 27801.16 | 05-JUL-15:30 | 6.85 | 01-JUL-16:10 | 0.00 | 01-JUL-00:10 |
August | 36263.56 | 04-AUG-07:10 | 8596.48 | 01-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 1238.27 | 04-AUG-07:19 | 27480.84 | 14-AUG-15:09 | 6.85 | 10-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 34098.99 | 29-SEP-07:10 | 8596.48 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 1234.04 | 29-SEP-07:19 | 25213.67 | 06-SEP-15:00 | 6.85 | 04-SEP-15:50 | 0.00 | 01-SEP-00:10 |
October | 36038.41 | 27-OCT-07:10 | 8596.48 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 1237.83 | 27-OCT-07:19 | 21978.17 | 02-OCT-15:30 | 6.85 | 25-OCT-07:10 | 22685.25 | 26-OCT-06:10 |
November | 38257.79 | 28-NOV-16:30 | 8596.48 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 1240.17 | 28-NOV-16:40 | 15026.38 | 02-NOV-15:39 | 6.85 | 01-NOV-05:10 | 47006.79 | 24-NOV-07:10 |
December | 38257.79 | 01-DEC-16:30 | 8596.48 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 1240.17 | 01-DEC-16:40 | 10671.49 | 22-DEC-16:40 | 6.85 | 05-DEC-17:10 | 72430.99 | 18-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 30719.22 | 8596.48 | 45864.70 | 1227.45 | 8647.67 | 6.85 | 0.00 | |||||||
Maximum of Months | 38257.79 | 8596.48 | 45864.70 | 1241.92 | 29552.23 | 6.85 | 95722.24 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 36841.89 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16646.21 | 22-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 38596.14 | 16-MAR-15:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65515.63 | 14-APR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 70820.12 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98276.13 | 28-JUN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88490.92 | 19-JUL-13:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 91880.99 | 25-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81758.36 | 08-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 70901.68 | 02-OCT-13:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 43072.52 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28266.41 | 22-DEC-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 16646.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 98276.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 142477.36 | 02-JAN-07:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 3946.45 | 6.85 | 95722.24 | 0.00 | 0.00 |
February | 103815.18 | 13-FEB-07:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 3533.76 | 6.85 | 57472.75 | 0.00 | 0.00 |
March | 125871.45 | 16-MAR-15:39 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 13872.96 | 6.85 | 0.00 | 38596.14 | 0.00 |
April | 162218.15 | 14-APR-15:30 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 23300.16 | 6.85 | 0.00 | 65515.63 | 0.00 |
May | 168109.41 | 31-MAY-15:00 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 23886.93 | 6.85 | 0.00 | 70820.12 | 0.00 |
June | 198414.89 | 28-JUN-15:09 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 26736.40 | 6.85 | 0.00 | 98276.13 | 0.00 |
July | 185436.39 | 31-JUL-15:00 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 27342.74 | 6.85 | 0.00 | 84691.29 | 0.00 |
August | 191120.56 | 25-AUG-15:09 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 25945.64 | 6.85 | 0.00 | 91772.57 | 0.00 |
September | 179659.74 | 08-SEP-15:00 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 24588.22 | 6.85 | 0.00 | 81669.17 | 0.00 |
October | 162532.51 | 02-OCT-15:09 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 21737.83 | 6.85 | 0.00 | 67392.32 | 0.00 |
November | 129186.21 | 01-NOV-15:00 | 30461.55 | 42072.41 | 0.00 | 1224.96 | 13032.74 | 6.85 | 0.00 | 42387.69 | 0.00 |
December | 118905.30 | 18-DEC-07:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 3665.63 | 6.85 | 72430.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 103815.18 | 12752.77 | 21098.80 | 0.00 | 353.77 | 3533.76 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 198414.89 | 30461.55 | 42072.41 | 8596.48 | 1224.96 | 27342.74 | 6.85 | 95722.24 | 98276.13 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 13822.38 | 02-JAN-07:19 | 0.00 | 9898.71 | 25-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 7963.26 | 28-FEB-07:10 | 0.00 | 9907.32 | 02-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 21406.41 | 27-MAR-06:19 | 0.00 | 9851.92 | 01-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 9728.55 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 9605.07 | 01-MAY-11:50 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9489.17 | 02-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9413.82 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9442.17 | 30-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9532.25 | 27-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 7057.86 | 25-OCT-06:00 | 0.00 | 9666.83 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 10815.39 | 24-NOV-07:19 | 0.00 | 9790.38 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 29427.56 | 06-DEC-07:19 | 0.00 | 9873.94 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9413.82 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 29427.56 | 0.00 | 9907.32 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.27 | 0.00 | 26.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 26.27 | 0.00 | 26.27 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.27 | 0.00 | 26.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.12 | 0.17 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.43 | 1.17 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.71 | 6.17 | 27.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.66 | 8.50 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.69 | 4.33 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.54 | 3.83 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.46 | 1.17 | 27.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.12 | 0.17 | 19.12 | 41.00 | 27.58 | 25.33 | 27.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.12 | 0.17 | 19.12 | 13.83 | 27.71 | 8.50 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.22 | 0.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.77 | 6.67 | 27.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.85 | 12.17 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 28.16 | 11.00 | 28.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 28.06 | 14.00 | 28.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 28.13 | 8.33 | 28.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.81 | 8.33 | 27.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.60 | 2.67 | 27.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.22 | 0.17 | 19.22 | 74.00 | 27.94 | 63.17 | 27.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.22 | 0.17 | 19.22 | 17.67 | 28.16 | 14.00 | 28.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.81 | 4.83 | 27.81 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.72 | 5.67 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.54 | 5.67 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.72 | 6.00 | 27.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.80 | 9.00 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.98 | 5.17 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.03 | 6.83 | 28.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.02 | 6.83 | 28.04 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.70 | 2.83 | 27.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.76 | 4.00 | 27.76 |
Annual Sum or Average | 0.00 | 0.00 | 71.00 | 27.82 | 56.83 | 27.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 28.03 | 9.00 | 28.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.28 | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.80 | 0.17 | 27.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.24 | 4.17 | 28.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.52 | 4.83 | 28.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.45 | 5.67 | 28.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 28.36 | 7.83 | 28.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.51 | 4.33 | 28.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.11 | 4.67 | 28.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.99 | 3.17 | 28.02 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.28 | 0.17 | 19.28 | 64.00 | 28.31 | 34.83 | 28.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.28 | 0.17 | 19.28 | 15.17 | 28.52 | 7.83 | 28.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.42 | 1.50 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.44 | 2.83 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.44 | 1.83 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.36 | 1.67 | 27.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.83 | 27.42 | 8.00 | 27.41 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.44 | 2.83 | 27.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.59 | 3.17 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.75 | 5.50 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.87 | 9.33 | 27.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.77 | 13.17 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.86 | 8.00 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.65 | 8.33 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.50 | 3.00 | 27.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 56.67 | 27.76 | 50.50 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.87 | 13.17 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.83 | 19.65 | 12.83 | 19.65 | 5.17 | 21.01 | 5.17 | 21.98 |
February | 16.50 | 19.17 | 16.50 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
March | 16.17 | 18.88 | 16.17 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
April | 1.00 | 20.27 | 1.00 | 20.27 | 15.33 | 24.70 | 15.33 | 24.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 25.12 | 24.17 | 25.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 48.00 | 26.16 | 47.83 | 26.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 | 26.11 | 43.83 | 26.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 51.17 | 26.12 | 49.67 | 26.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 61.17 | 25.77 | 59.33 | 25.74 |
October | 4.17 | 19.79 | 4.17 | 19.79 | 46.00 | 24.82 | 44.83 | 25.22 |
November | 2.83 | 19.83 | 2.83 | 19.83 | 4.83 | 23.38 | 4.83 | 24.70 |
December | 17.67 | 18.62 | 17.67 | 18.62 | 5.00 | 19.76 | 5.00 | 20.64 |
Annual Sum or Average | 71.17 | 19.13 | 71.17 | 19.13 | 305.67 | 23.79 | 300.00 | 24.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 | 0.00 | 18.88 |
Maximum of Months | 17.67 | 20.27 | 17.67 | 20.27 | 61.17 | 26.16 | 59.33 | 26.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.95 | 2.83 | 27.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.14 | 3.83 | 28.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.20 | 3.50 | 28.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 28.07 | 6.17 | 28.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.04 | 4.33 | 28.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.85 | 4.67 | 27.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.82 | 3.17 | 27.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 52.00 | 28.04 | 28.50 | 28.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 28.20 | 6.17 | 28.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.00 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.55 | 4.67 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.51 | 5.33 | 27.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.54 | 2.83 | 27.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.41 | 2.33 | 27.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.67 | 27.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 24.67 | 27.51 | 15.83 | 27.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.55 | 5.33 | 27.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.81 | 5.67 | 27.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.88 | 8.83 | 27.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.03 | 10.83 | 28.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.91 | 13.33 | 27.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.98 | 8.17 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.69 | 7.17 | 27.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.54 | 3.00 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 62.50 | 27.89 | 57.00 | 27.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 28.03 | 13.33 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.83 | 5.83 | 27.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.36 | 0.17 | 27.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.60 | 4.67 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.41 | 2.33 | 27.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.57 | 4.33 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.60 | 8.17 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.80 | 5.00 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.86 | 7.00 | 27.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.94 | 7.17 | 27.95 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.69 | 4.33 | 27.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.84 | 4.83 | 27.84 |
Annual Sum or Average | 0.00 | 0.00 | 61.50 | 27.73 | 53.83 | 27.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.94 | 8.17 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.68 | 0.17 | 27.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.16 | 3.67 | 28.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.35 | 4.67 | 28.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.36 | 4.67 | 28.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.34 | 5.83 | 28.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.39 | 3.67 | 28.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.02 | 4.17 | 28.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.92 | 2.83 | 27.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
Annual Sum or Average | 0.00 | 0.00 | 54.00 | 28.26 | 30.17 | 28.27 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.39 | 5.83 | 28.47 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 185.83 | 23.91 | 45.83 | 24.23 | 0.00 | 24.23 |
February | 74.00 | 23.86 | 101.17 | 24.38 | 0.00 | 24.38 |
March | 118.67 | 24.03 | 84.67 | 24.57 | 0.00 | 24.57 |
April | 71.83 | 24.02 | 58.83 | 24.80 | 0.00 | 24.80 |
May | 27.17 | 24.01 | 52.83 | 25.52 | 0.00 | 25.52 |
June | 0.00 | 0.00 | 173.17 | 24.91 | 0.00 | 24.91 |
July | 4.83 | 24.00 | 416.50 | 24.49 | 0.00 | 24.49 |
August | 0.00 | 0.00 | 461.50 | 24.41 | 0.00 | 24.41 |
September | 0.00 | 0.00 | 421.17 | 24.54 | 0.00 | 24.54 |
October | 45.50 | 24.01 | 209.00 | 24.75 | 0.00 | 24.75 |
November | 137.83 | 24.02 | 153.17 | 24.45 | 2.83 | 24.44 |
December | 333.67 | 24.02 | 3.17 | 24.04 | 0.00 | 24.04 |
Annual Sum or Average | 999.33 | 23.99 | 2181.00 | 24.50 | 2.83 | 24.50 |
Minimum of Months | 0.00 | 0.00 | 3.17 | 24.04 | 0.00 | 24.04 |
Maximum of Months | 333.67 | 24.03 | 461.50 | 25.52 | 2.83 | 25.52 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 405.83 | 23.47 | 8.50 | 23.44 | 5.83 | 23.41 |
February | 358.33 | 23.32 | 5.50 | 23.34 | 0.00 | 23.34 |
March | 295.17 | 23.60 | 19.50 | 23.65 | 0.00 | 23.65 |
April | 159.17 | 23.92 | 24.50 | 24.17 | 0.00 | 24.17 |
May | 94.50 | 24.02 | 35.17 | 24.56 | 0.00 | 24.56 |
June | 3.67 | 24.02 | 131.67 | 24.85 | 0.00 | 24.85 |
July | 11.00 | 24.02 | 405.50 | 24.39 | 0.00 | 24.39 |
August | 3.83 | 24.01 | 451.67 | 24.31 | 0.67 | 24.31 |
September | 0.00 | 0.00 | 401.67 | 24.45 | 0.00 | 24.45 |
October | 169.17 | 23.85 | 134.67 | 24.18 | 0.00 | 24.18 |
November | 287.00 | 23.66 | 94.50 | 23.88 | 11.33 | 23.88 |
December | 481.00 | 23.35 | 0.00 | 23.35 | 0.00 | 23.35 |
Annual Sum or Average | 2268.67 | 23.55 | 1712.83 | 23.96 | 17.83 | 23.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.34 | 0.00 | 23.34 |
Maximum of Months | 481.00 | 24.02 | 451.67 | 24.85 | 11.33 | 24.85 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 468.17 | 22.97 | 18.67 | 22.85 | 18.67 | 22.74 |
February | 408.17 | 22.71 | 3.50 | 22.70 | 3.50 | 22.68 |
March | 378.50 | 23.18 | 12.67 | 23.16 | 6.67 | 23.12 |
April | 184.00 | 23.77 | 23.17 | 23.91 | 0.00 | 23.91 |
May | 116.17 | 23.98 | 35.33 | 24.36 | 0.00 | 24.36 |
June | 4.50 | 23.99 | 170.33 | 24.70 | 0.00 | 24.70 |
July | 11.67 | 24.01 | 409.00 | 24.42 | 0.00 | 24.42 |
August | 6.00 | 24.00 | 454.00 | 24.32 | 1.67 | 24.32 |
September | 2.67 | 23.77 | 399.33 | 24.44 | 0.00 | 24.44 |
October | 237.17 | 23.55 | 111.83 | 23.83 | 0.00 | 23.83 |
November | 350.33 | 23.07 | 62.83 | 23.23 | 16.33 | 23.24 |
December | 496.17 | 22.51 | 41.50 | 22.37 | 41.50 | 22.25 |
Annual Sum or Average | 2663.50 | 23.05 | 1742.17 | 23.54 | 88.33 | 23.49 |
Minimum of Months | 2.67 | 22.51 | 3.50 | 22.37 | 0.00 | 22.25 |
Maximum of Months | 496.17 | 24.01 | 454.00 | 24.70 | 41.50 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.01 | 95.17 | 21.69 | 95.17 | 21.46 |
February | 446.67 | 21.67 | 52.83 | 21.51 | 52.83 | 21.38 |
March | 429.83 | 22.28 | 56.17 | 22.13 | 47.00 | 21.96 |
April | 210.33 | 23.33 | 63.17 | 23.65 | 2.33 | 23.63 |
May | 108.33 | 23.70 | 103.00 | 24.40 | 0.17 | 24.41 |
June | 21.83 | 26.15 | 332.83 | 24.77 | 15.17 | 24.87 |
July | 45.50 | 26.02 | 450.67 | 24.75 | 40.17 | 24.86 |
August | 30.00 | 25.47 | 469.33 | 24.49 | 22.50 | 24.56 |
September | 54.50 | 24.99 | 414.17 | 24.57 | 32.50 | 24.67 |
October | 290.83 | 22.84 | 132.17 | 23.18 | 22.17 | 23.09 |
November | 430.17 | 22.19 | 117.33 | 22.11 | 95.50 | 21.98 |
December | 497.00 | 21.35 | 219.67 | 21.07 | 219.67 | 20.93 |
Annual Sum or Average | 3067.00 | 22.32 | 2506.50 | 22.95 | 645.17 | 22.80 |
Minimum of Months | 21.83 | 21.35 | 52.83 | 21.07 | 0.17 | 20.93 |
Maximum of Months | 502.00 | 26.15 | 469.33 | 24.77 | 219.67 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 444.67 | 22.39 | 65.17 | 22.10 | 62.67 | 21.87 |
February | 395.33 | 21.96 | 46.83 | 21.87 | 35.50 | 21.74 |
March | 341.00 | 22.44 | 69.67 | 22.50 | 27.83 | 22.34 |
April | 107.83 | 23.46 | 194.67 | 24.28 | 9.17 | 24.33 |
May | 62.33 | 24.51 | 256.50 | 24.73 | 16.50 | 24.86 |
June | 41.50 | 26.82 | 412.83 | 24.80 | 37.67 | 24.98 |
July | 63.00 | 26.61 | 468.67 | 24.90 | 60.33 | 25.09 |
August | 44.83 | 26.35 | 488.33 | 24.64 | 41.17 | 24.78 |
September | 61.33 | 25.65 | 436.83 | 24.68 | 44.83 | 24.83 |
October | 211.67 | 22.97 | 192.67 | 23.62 | 21.83 | 23.56 |
November | 370.67 | 22.44 | 96.50 | 22.45 | 61.83 | 22.34 |
December | 497.00 | 21.84 | 139.83 | 21.53 | 139.83 | 21.32 |
Annual Sum or Average | 2641.17 | 22.69 | 2868.50 | 23.43 | 559.17 | 23.38 |
Minimum of Months | 41.50 | 21.84 | 46.83 | 21.53 | 9.17 | 21.32 |
Maximum of Months | 497.00 | 26.82 | 488.33 | 24.90 | 139.83 | 25.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 264.17 | 22.32 | 183.67 | 22.81 | 52.83 | 22.59 |
February | 302.83 | 21.83 | 108.50 | 22.16 | 32.67 | 22.01 |
March | 309.67 | 22.39 | 107.00 | 22.60 | 34.00 | 22.42 |
April | 162.50 | 23.29 | 159.17 | 23.98 | 5.83 | 24.00 |
May | 121.17 | 23.60 | 149.17 | 24.31 | 1.67 | 24.33 |
June | 36.50 | 25.24 | 309.00 | 24.72 | 15.83 | 24.82 |
July | 54.00 | 25.80 | 442.17 | 24.74 | 42.50 | 24.87 |
August | 36.67 | 25.79 | 472.83 | 24.54 | 28.67 | 24.64 |
September | 64.83 | 25.55 | 430.00 | 24.70 | 44.83 | 24.85 |
October | 190.17 | 23.36 | 240.33 | 24.00 | 32.83 | 24.07 |
November | 258.83 | 22.55 | 189.17 | 23.05 | 59.50 | 22.93 |
December | 329.83 | 22.06 | 170.83 | 22.13 | 108.33 | 21.87 |
Annual Sum or Average | 2131.17 | 22.78 | 2961.83 | 23.62 | 459.50 | 23.56 |
Minimum of Months | 36.50 | 21.83 | 107.00 | 22.13 | 1.67 | 21.87 |
Maximum of Months | 329.83 | 25.80 | 472.83 | 24.74 | 108.33 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 404.67 | 21.74 | 109.67 | 21.59 | 87.83 | 21.37 |
February | 403.00 | 21.50 | 67.83 | 21.45 | 50.50 | 21.32 |
March | 387.00 | 22.05 | 94.50 | 22.13 | 45.83 | 21.97 |
April | 194.83 | 23.23 | 163.17 | 23.86 | 17.67 | 23.95 |
May | 139.67 | 23.84 | 200.33 | 24.39 | 19.33 | 24.54 |
June | 50.50 | 25.22 | 342.33 | 24.71 | 22.83 | 24.84 |
July | 63.00 | 25.83 | 447.17 | 24.75 | 50.50 | 24.89 |
August | 44.67 | 25.27 | 461.67 | 24.51 | 29.50 | 24.60 |
September | 68.33 | 24.80 | 416.00 | 24.55 | 39.50 | 24.67 |
October | 264.67 | 22.70 | 187.00 | 23.29 | 31.33 | 23.26 |
November | 370.50 | 22.02 | 136.50 | 22.12 | 84.50 | 21.99 |
December | 456.17 | 21.39 | 198.17 | 21.15 | 192.33 | 20.99 |
Annual Sum or Average | 2847.00 | 22.30 | 2824.33 | 23.08 | 671.67 | 22.98 |
Minimum of Months | 44.67 | 21.39 | 67.83 | 21.15 | 17.67 | 20.99 |
Maximum of Months | 456.17 | 25.83 | 461.67 | 24.75 | 192.33 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.43 | 32.17 | 22.29 | 32.17 | 22.17 |
February | 454.00 | 21.96 | 13.00 | 21.91 | 13.00 | 21.87 |
March | 484.00 | 22.50 | 20.17 | 22.42 | 20.17 | 22.35 |
April | 268.83 | 23.65 | 12.33 | 23.71 | 0.00 | 23.71 |
May | 150.17 | 23.91 | 21.00 | 24.12 | 0.00 | 24.12 |
June | 3.50 | 25.02 | 246.83 | 24.80 | 1.00 | 24.81 |
July | 8.83 | 25.76 | 452.67 | 24.62 | 8.00 | 24.64 |
August | 4.83 | 25.50 | 475.33 | 24.46 | 4.50 | 24.47 |
September | 18.50 | 26.24 | 440.00 | 24.61 | 18.50 | 24.68 |
October | 234.50 | 23.55 | 128.67 | 23.90 | 0.00 | 23.90 |
November | 389.67 | 23.06 | 67.17 | 23.23 | 30.17 | 23.27 |
December | 497.00 | 22.14 | 62.50 | 21.99 | 62.50 | 21.87 |
Annual Sum or Average | 3015.83 | 22.71 | 1971.83 | 23.34 | 190.00 | 23.30 |
Minimum of Months | 3.50 | 21.96 | 12.33 | 21.91 | 0.00 | 21.87 |
Maximum of Months | 502.00 | 26.24 | 475.33 | 24.80 | 62.50 | 24.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 429.83 | 22.93 | 17.50 | 22.89 | 11.50 | 22.82 |
February | 400.33 | 22.39 | 14.33 | 22.43 | 3.67 | 22.41 |
March | 367.50 | 22.80 | 34.83 | 22.89 | 9.33 | 22.83 |
April | 90.50 | 23.65 | 155.17 | 24.43 | 0.67 | 24.44 |
May | 39.83 | 24.10 | 186.50 | 24.83 | 2.83 | 24.87 |
June | 24.17 | 27.12 | 400.83 | 24.77 | 24.00 | 24.89 |
July | 39.83 | 26.84 | 472.50 | 24.85 | 39.83 | 25.00 |
August | 31.00 | 26.87 | 496.83 | 24.67 | 31.00 | 24.79 |
September | 38.33 | 26.71 | 461.83 | 24.75 | 38.33 | 24.89 |
October | 127.17 | 23.62 | 209.33 | 24.31 | 3.00 | 24.34 |
November | 303.50 | 23.34 | 93.00 | 23.57 | 29.00 | 23.61 |
December | 475.83 | 22.70 | 31.17 | 22.58 | 31.00 | 22.48 |
Annual Sum or Average | 2367.83 | 23.13 | 2573.83 | 23.88 | 224.17 | 23.93 |
Minimum of Months | 24.17 | 22.39 | 14.33 | 22.43 | 0.67 | 22.41 |
Maximum of Months | 475.83 | 27.12 | 496.83 | 24.85 | 39.83 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 228.50 | 22.98 | 146.50 | 23.63 | 12.50 | 23.58 |
February | 335.17 | 22.04 | 52.00 | 22.23 | 13.33 | 22.12 |
March | 356.67 | 22.45 | 64.67 | 22.54 | 22.50 | 22.38 |
April | 157.67 | 23.26 | 95.00 | 23.96 | 1.00 | 23.94 |
May | 148.00 | 23.59 | 64.50 | 24.20 | 0.00 | 24.20 |
June | 20.83 | 24.36 | 250.00 | 25.05 | 3.33 | 25.08 |
July | 43.00 | 25.17 | 450.50 | 24.80 | 38.50 | 24.84 |
August | 44.33 | 25.67 | 485.67 | 24.77 | 42.50 | 24.84 |
September | 65.17 | 26.08 | 461.17 | 24.97 | 62.00 | 25.10 |
October | 122.33 | 23.84 | 276.33 | 24.62 | 31.17 | 24.74 |
November | 180.83 | 23.19 | 214.83 | 23.96 | 30.67 | 23.97 |
December | 300.00 | 22.56 | 100.67 | 22.93 | 28.33 | 22.79 |
Annual Sum or Average | 2002.50 | 23.03 | 2661.83 | 24.00 | 285.83 | 24.01 |
Minimum of Months | 20.83 | 22.04 | 52.00 | 22.23 | 0.00 | 22.12 |
Maximum of Months | 356.67 | 26.08 | 485.67 | 25.05 | 62.00 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 410.00 | 22.57 | 27.33 | 22.55 | 15.83 | 22.47 |
February | 416.83 | 22.01 | 11.00 | 22.02 | 5.83 | 22.00 |
March | 412.00 | 22.50 | 43.50 | 22.58 | 15.17 | 22.52 |
April | 148.83 | 23.57 | 132.00 | 24.14 | 2.50 | 24.18 |
May | 100.17 | 24.01 | 161.67 | 24.56 | 6.67 | 24.64 |
June | 15.17 | 26.63 | 334.33 | 24.76 | 12.67 | 24.85 |
July | 30.00 | 26.62 | 462.50 | 24.75 | 28.33 | 24.86 |
August | 21.83 | 26.62 | 489.83 | 24.58 | 21.83 | 24.66 |
September | 32.50 | 26.60 | 455.50 | 24.71 | 32.50 | 24.83 |
October | 163.83 | 23.59 | 194.50 | 24.15 | 7.00 | 24.21 |
November | 298.33 | 23.13 | 111.67 | 23.48 | 26.17 | 23.53 |
December | 452.17 | 22.32 | 53.00 | 22.21 | 47.17 | 22.09 |
Annual Sum or Average | 2501.67 | 22.83 | 2476.83 | 23.65 | 221.67 | 23.68 |
Minimum of Months | 15.17 | 22.01 | 11.00 | 22.02 | 2.50 | 22.00 |
Maximum of Months | 452.17 | 26.63 | 489.83 | 24.76 | 47.17 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.17 | 22.56 | 33.00 | 22.41 | 33.00 | 22.26 |
February | 439.33 | 22.23 | 12.00 | 22.17 | 12.00 | 22.12 |
March | 411.50 | 22.76 | 28.17 | 22.72 | 16.50 | 22.64 |
April | 192.67 | 23.69 | 40.17 | 23.94 | 0.00 | 23.94 |
May | 90.00 | 23.95 | 77.00 | 24.66 | 0.00 | 24.66 |
June | 8.33 | 27.08 | 301.67 | 24.84 | 8.33 | 24.90 |
July | 26.00 | 26.10 | 452.83 | 24.71 | 25.50 | 24.78 |
August | 17.17 | 25.36 | 473.00 | 24.48 | 13.17 | 24.51 |
September | 29.17 | 25.81 | 419.17 | 24.62 | 24.67 | 24.70 |
October | 266.00 | 23.32 | 117.33 | 23.68 | 0.83 | 23.69 |
November | 405.67 | 22.76 | 75.00 | 22.86 | 45.17 | 22.86 |
December | 497.00 | 21.95 | 106.83 | 21.72 | 106.83 | 21.56 |
Annual Sum or Average | 2881.00 | 22.75 | 2136.17 | 23.39 | 286.00 | 23.33 |
Minimum of Months | 8.33 | 21.95 | 12.00 | 21.72 | 0.00 | 21.56 |
Maximum of Months | 498.17 | 27.08 | 473.00 | 24.84 | 106.83 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 360.00 | 22.56 | 35.17 | 22.49 | 24.50 | 22.36 |
February | 326.83 | 22.18 | 30.17 | 22.25 | 11.67 | 22.18 |
March | 289.33 | 22.65 | 57.00 | 22.88 | 11.33 | 22.80 |
April | 96.83 | 23.74 | 136.17 | 24.53 | 6.50 | 24.60 |
May | 49.00 | 24.70 | 181.00 | 25.04 | 13.17 | 25.16 |
June | 30.67 | 27.09 | 323.33 | 24.98 | 29.83 | 25.15 |
July | 51.33 | 26.68 | 394.33 | 25.01 | 51.17 | 25.18 |
August | 35.50 | 26.48 | 410.17 | 24.73 | 33.67 | 24.86 |
September | 47.17 | 26.06 | 365.83 | 24.82 | 39.17 | 24.97 |
October | 178.17 | 23.24 | 151.83 | 23.96 | 5.83 | 24.00 |
November | 307.67 | 22.77 | 72.00 | 22.93 | 35.33 | 22.91 |
December | 412.17 | 22.16 | 71.17 | 21.93 | 71.17 | 21.75 |
Annual Sum or Average | 2184.67 | 22.92 | 2228.17 | 23.73 | 333.33 | 23.75 |
Minimum of Months | 30.67 | 22.16 | 30.17 | 21.93 | 5.83 | 21.75 |
Maximum of Months | 412.17 | 27.09 | 410.17 | 25.04 | 71.17 | 25.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 243.50 | 22.92 | 161.67 | 23.54 | 16.67 | 23.54 |
February | 282.00 | 22.35 | 89.67 | 22.82 | 3.83 | 22.80 |
March | 273.33 | 22.80 | 93.17 | 23.13 | 12.67 | 23.04 |
April | 135.67 | 23.61 | 141.33 | 24.22 | 1.00 | 24.23 |
May | 96.17 | 23.83 | 110.83 | 24.56 | 0.00 | 24.56 |
June | 16.17 | 25.68 | 279.00 | 24.80 | 8.67 | 24.87 |
July | 39.50 | 25.94 | 443.50 | 24.73 | 34.50 | 24.83 |
August | 28.00 | 26.00 | 480.67 | 24.55 | 23.67 | 24.63 |
September | 47.33 | 26.37 | 438.67 | 24.76 | 43.33 | 24.92 |
October | 157.50 | 23.81 | 244.33 | 24.35 | 20.83 | 24.49 |
November | 222.83 | 23.10 | 188.50 | 23.73 | 31.00 | 23.75 |
December | 306.67 | 22.61 | 120.00 | 22.91 | 46.50 | 22.77 |
Annual Sum or Average | 1848.67 | 23.18 | 2791.33 | 24.01 | 242.67 | 24.04 |
Minimum of Months | 16.17 | 22.35 | 89.67 | 22.82 | 0.00 | 22.77 |
Maximum of Months | 306.67 | 26.37 | 480.67 | 24.80 | 46.50 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 396.50 | 22.26 | 48.17 | 22.28 | 23.50 | 22.16 |
February | 393.00 | 21.95 | 31.33 | 21.99 | 13.83 | 21.94 |
March | 365.17 | 22.47 | 67.33 | 22.62 | 18.17 | 22.54 |
April | 163.83 | 23.54 | 149.50 | 24.12 | 9.50 | 24.21 |
May | 112.83 | 24.11 | 187.17 | 24.58 | 15.83 | 24.71 |
June | 29.00 | 26.08 | 333.17 | 24.79 | 19.83 | 24.91 |
July | 44.83 | 26.08 | 451.33 | 24.73 | 39.50 | 24.85 |
August | 30.00 | 25.88 | 476.33 | 24.53 | 24.67 | 24.61 |
September | 50.00 | 25.45 | 424.33 | 24.63 | 34.33 | 24.75 |
October | 231.67 | 23.12 | 174.00 | 23.74 | 9.83 | 23.80 |
November | 347.17 | 22.55 | 109.50 | 22.83 | 41.17 | 22.82 |
December | 448.67 | 21.87 | 107.67 | 21.70 | 99.33 | 21.54 |
Annual Sum or Average | 2612.67 | 22.66 | 2559.83 | 23.48 | 349.50 | 23.47 |
Minimum of Months | 29.00 | 21.87 | 31.33 | 21.70 | 9.50 | 21.54 |
Maximum of Months | 448.67 | 26.08 | 476.33 | 24.79 | 99.33 | 24.91 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.23202 | 21.49043 | 0.28185 | 6.97165 |
February | 454.00000 | 24.22348 | 33.31714 | 0.34694 | 7.70009 |
March | 514.00000 | 24.31240 | 25.94225 | 0.33707 | 7.64135 |
April | 485.00000 | 24.36489 | 18.60143 | 0.33884 | 7.63061 |
May | 508.00000 | 24.38849 | 18.06414 | -0.4934 | 10.50698 |
June | 496.00000 | 24.36306 | 25.55510 | -0.4248 | 9.18055 |
July | 497.00000 | 24.44291 | 41.60503 | -0.2963 | 7.37660 |
August | 514.00000 | 24.38176 | 44.17546 | -0.2925 | 7.25254 |
September | 485.00000 | 24.47176 | 43.33604 | -0.2746 | 7.26870 |
October | 502.00000 | 24.45488 | 26.00439 | 0.41030 | 8.99654 |
November | 489.00000 | 24.40712 | 25.90442 | 0.37422 | 8.53992 |
December | 497.00000 | 24.21919 | 15.36226 | 0.22650 | 6.24072 |
Annual Sum or Average | 5943.00000 | 24.35579 | 28.24844 | 0.04138 | 7.94690 |
Minimum of Months | 454.00000 | 24.21919 | 15.36226 | -0.4934 | 6.24072 |
Maximum of Months | 514.00000 | 24.47176 | 44.17546 | 0.41030 | 10.50698 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.64030 | 23.86653 | 0.13388 | 5.94777 |
February | 454.00000 | 23.48483 | 35.70399 | 0.16442 | 5.96137 |
March | 514.00000 | 23.85553 | 27.51608 | 0.21601 | 6.37410 |
April | 485.00000 | 24.18589 | 19.48684 | 0.28427 | 6.92036 |
May | 508.00000 | 24.27413 | 18.89650 | -0.5501 | 11.64660 |
June | 496.00000 | 24.29488 | 26.40698 | -0.4627 | 9.81448 |
July | 497.00000 | 24.35444 | 43.42973 | -0.3330 | 7.77937 |
August | 514.00000 | 24.29663 | 46.18101 | -0.3325 | 7.68284 |
September | 485.00000 | 24.38106 | 45.03980 | -0.3220 | 7.75682 |
October | 502.00000 | 24.19575 | 27.17742 | 0.33031 | 7.77859 |
November | 489.00000 | 23.92510 | 27.45510 | 0.23948 | 6.94856 |
December | 497.00000 | 23.38487 | 17.21434 | 0.01704 | 5.57309 |
Annual Sum or Average | 5943.00000 | 24.02630 | 29.82876 | -0.0537 | 7.53143 |
Minimum of Months | 454.00000 | 23.38487 | 17.21434 | -0.5501 | 5.57309 |
Maximum of Months | 514.00000 | 24.38106 | 46.18101 | 0.33031 | 11.64660 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.04837 | 23.35596 | -0.0207 | 6.41411 |
February | 454.00000 | 22.84122 | 37.09830 | 0.00807 | 5.95707 |
March | 514.00000 | 23.42899 | 27.93054 | 0.10976 | 6.18706 |
April | 485.00000 | 24.07646 | 19.65845 | 0.26225 | 6.78795 |
May | 508.00000 | 24.23780 | 19.04636 | -0.5512 | 11.72481 |
June | 496.00000 | 24.30646 | 26.36185 | -0.4369 | 9.41077 |
July | 497.00000 | 24.38611 | 43.09004 | -0.3055 | 7.50887 |
August | 514.00000 | 24.30086 | 45.83559 | -0.3189 | 7.53382 |
September | 485.00000 | 24.36650 | 44.85870 | -0.3216 | 7.75183 |
October | 502.00000 | 23.93563 | 27.43372 | 0.26204 | 7.31442 |
November | 489.00000 | 23.36977 | 28.21099 | 0.09975 | 6.62170 |
December | 497.00000 | 22.51319 | 17.92220 | -0.1960 | 7.13220 |
Annual Sum or Average | 5943.00000 | 23.74044 | 30.02102 | -0.1192 | 7.54486 |
Minimum of Months | 454.00000 | 22.51319 | 17.92220 | -0.5512 | 5.95707 |
Maximum of Months | 514.00000 | 24.38611 | 45.83559 | 0.26225 | 11.72481 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.00724 | 25.55041 | -0.2708 | 8.96216 |
February | 454.00000 | 21.70880 | 40.32995 | -0.2623 | 7.92288 |
March | 514.00000 | 22.57937 | 29.88650 | -0.0913 | 7.50004 |
April | 485.00000 | 23.88919 | 20.10448 | 0.22603 | 7.17644 |
May | 508.00000 | 24.25322 | 18.91578 | -0.5142 | 11.67939 |
June | 496.00000 | 24.47952 | 25.79778 | -0.3017 | 8.07270 |
July | 497.00000 | 24.57989 | 43.13510 | -0.1739 | 6.97741 |
August | 514.00000 | 24.39596 | 45.99666 | -0.2352 | 7.14208 |
September | 485.00000 | 24.41034 | 45.76290 | -0.2662 | 7.81624 |
October | 502.00000 | 23.43524 | 28.78986 | 0.14727 | 7.91275 |
November | 489.00000 | 22.41762 | 30.63436 | -0.1285 | 8.12477 |
December | 497.00000 | 21.35002 | 19.39830 | -0.4885 | 11.99146 |
Annual Sum or Average | 5943.00000 | 23.30311 | 31.12947 | -0.1971 | 8.44749 |
Minimum of Months | 454.00000 | 21.35002 | 18.91578 | -0.5142 | 6.97741 |
Maximum of Months | 514.00000 | 24.57989 | 45.99666 | 0.22603 | 11.99146 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.57809 | 24.34502 | -0.1081 | 7.85737 |
February | 454.00000 | 22.23067 | 38.93273 | -0.1155 | 7.46811 |
March | 514.00000 | 23.02826 | 28.67280 | 0.04845 | 7.43285 |
April | 485.00000 | 24.19349 | 19.31158 | 0.37113 | 9.29411 |
May | 508.00000 | 24.41751 | 18.52136 | -0.3525 | 9.51805 |
June | 496.00000 | 24.51576 | 25.61824 | -0.1820 | 7.42839 |
July | 497.00000 | 24.63411 | 42.84588 | -0.0611 | 6.87725 |
August | 514.00000 | 24.45342 | 45.60548 | -0.1182 | 6.86555 |
September | 485.00000 | 24.45429 | 45.36133 | -0.1729 | 7.40916 |
October | 502.00000 | 23.76659 | 27.78170 | 0.27513 | 9.21508 |
November | 489.00000 | 22.83025 | 29.69101 | -0.0003 | 7.49428 |
December | 497.00000 | 21.84299 | 18.63427 | -0.3457 | 9.90297 |
Annual Sum or Average | 5943.00000 | 23.58818 | 30.38508 | -0.0639 | 8.06587 |
Minimum of Months | 454.00000 | 21.84299 | 18.52136 | -0.3525 | 6.86555 |
Maximum of Months | 514.00000 | 24.63411 | 45.60548 | 0.37113 | 9.90297 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.29272 | 22.26367 | 0.12063 | 9.38583 |
February | 454.00000 | 22.62251 | 37.29660 | -0.0022 | 8.14663 |
March | 514.00000 | 23.12521 | 28.21015 | 0.07598 | 7.98514 |
April | 485.00000 | 24.02779 | 19.56219 | 0.30452 | 8.58216 |
May | 508.00000 | 24.22842 | 18.86669 | -0.5029 | 12.00863 |
June | 496.00000 | 24.42574 | 25.89491 | -0.3275 | 8.51850 |
July | 497.00000 | 24.55646 | 43.13412 | -0.1751 | 7.23451 |
August | 514.00000 | 24.41110 | 45.79510 | -0.1926 | 7.11226 |
September | 485.00000 | 24.47637 | 45.25175 | -0.1706 | 7.55369 |
October | 502.00000 | 23.94567 | 27.11386 | 0.34828 | 10.55145 |
November | 489.00000 | 23.39087 | 27.93114 | 0.17858 | 8.98956 |
December | 497.00000 | 22.86383 | 16.71367 | -0.0603 | 10.06693 |
Annual Sum or Average | 5943.00000 | 23.78794 | 29.78705 | -0.0350 | 8.85299 |
Minimum of Months | 454.00000 | 22.62251 | 16.71367 | -0.5029 | 7.11226 |
Maximum of Months | 514.00000 | 24.55646 | 45.79510 | 0.34828 | 12.00863 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.21794 | 24.47772 | -0.1799 | 9.14773 |
February | 454.00000 | 21.79253 | 39.59547 | -0.2137 | 8.14778 |
March | 514.00000 | 22.58906 | 29.29337 | -0.0498 | 8.04006 |
April | 485.00000 | 23.87473 | 19.88616 | 0.29346 | 9.01860 |
May | 508.00000 | 24.19181 | 18.95188 | -0.4432 | 12.04449 |
June | 496.00000 | 24.42889 | 25.89056 | -0.2337 | 8.21275 |
July | 497.00000 | 24.53095 | 43.13651 | -0.1358 | 7.46889 |
August | 514.00000 | 24.35956 | 45.94611 | -0.1815 | 7.53718 |
September | 485.00000 | 24.36624 | 45.70938 | -0.2190 | 8.02988 |
October | 502.00000 | 23.44326 | 28.31420 | 0.19835 | 9.06265 |
November | 489.00000 | 22.54936 | 29.74906 | -0.0555 | 8.51303 |
December | 497.00000 | 21.62757 | 18.44575 | -0.3958 | 11.50899 |
Annual Sum or Average | 5943.00000 | 23.34137 | 30.72317 | -0.1351 | 8.90172 |
Minimum of Months | 454.00000 | 21.62757 | 18.44575 | -0.4432 | 7.46889 |
Maximum of Months | 514.00000 | 24.53095 | 45.94611 | 0.29346 | 12.04449 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.42516 | 25.46534 | -0.1694 | 6.87361 |
February | 454.00000 | 21.95967 | 40.28902 | -0.1995 | 6.54948 |
March | 514.00000 | 22.59765 | 30.69835 | -0.0955 | 6.57110 |
April | 485.00000 | 23.91026 | 20.16414 | 0.20415 | 6.40834 |
May | 508.00000 | 24.20012 | 18.81708 | -0.5792 | 12.46811 |
June | 496.00000 | 24.42939 | 25.54345 | -0.3667 | 8.52385 |
July | 497.00000 | 24.56296 | 41.99245 | -0.2080 | 6.77997 |
August | 514.00000 | 24.42127 | 44.64370 | -0.2439 | 6.87608 |
September | 485.00000 | 24.49699 | 44.21510 | -0.2355 | 7.08210 |
October | 502.00000 | 23.96941 | 27.92162 | 0.27904 | 7.70300 |
November | 489.00000 | 23.27405 | 29.50268 | 0.08237 | 6.60933 |
December | 497.00000 | 22.14485 | 19.01881 | -0.2767 | 7.68941 |
Annual Sum or Average | 5943.00000 | 23.54206 | 30.62750 | -0.1517 | 7.52659 |
Minimum of Months | 454.00000 | 21.95967 | 18.81708 | -0.5792 | 6.40834 |
Maximum of Months | 514.00000 | 24.56296 | 44.64370 | 0.27904 | 12.46811 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.11627 | 23.94274 | 0.02222 | 6.33860 |
February | 454.00000 | 22.59784 | 38.67664 | -0.0262 | 6.30447 |
March | 514.00000 | 23.21584 | 29.14066 | 0.08197 | 6.59771 |
April | 485.00000 | 24.28363 | 19.04282 | 0.36798 | 8.57218 |
May | 508.00000 | 24.43021 | 18.17568 | -0.3916 | 9.38693 |
June | 496.00000 | 24.52450 | 25.19877 | -0.2246 | 7.30363 |
July | 497.00000 | 24.65675 | 41.54932 | -0.0800 | 6.41695 |
August | 514.00000 | 24.51379 | 44.10747 | -0.1113 | 6.36453 |
September | 485.00000 | 24.56263 | 43.75524 | -0.1317 | 6.64192 |
October | 502.00000 | 24.23099 | 26.86130 | 0.39745 | 9.57143 |
November | 489.00000 | 23.66013 | 28.32926 | 0.20818 | 7.06141 |
December | 497.00000 | 22.77165 | 17.99482 | -0.1055 | 6.65150 |
Annual Sum or Average | 5943.00000 | 23.88821 | 29.67318 | -0.0004 | 7.27405 |
Minimum of Months | 454.00000 | 22.59784 | 17.99482 | -0.3916 | 6.30447 |
Maximum of Months | 514.00000 | 24.65675 | 44.10747 | 0.39745 | 9.57143 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.78294 | 21.35671 | 0.25725 | 8.50504 |
February | 454.00000 | 22.62603 | 37.07962 | 0.02554 | 6.95517 |
March | 514.00000 | 23.02582 | 28.16172 | 0.05691 | 7.22400 |
April | 485.00000 | 24.07571 | 18.48232 | 0.28729 | 7.81078 |
May | 508.00000 | 24.21422 | 17.42196 | -0.5642 | 12.79252 |
June | 496.00000 | 24.58558 | 24.30669 | -0.3477 | 8.71815 |
July | 497.00000 | 24.71386 | 41.72504 | -0.1625 | 6.76535 |
August | 514.00000 | 24.64969 | 44.04153 | -0.1402 | 6.59927 |
September | 485.00000 | 24.75119 | 43.25409 | -0.0825 | 6.81849 |
October | 502.00000 | 24.38396 | 25.72149 | 0.46894 | 11.67417 |
November | 489.00000 | 23.96236 | 26.82383 | 0.34845 | 9.18605 |
December | 497.00000 | 23.35489 | 15.75504 | 0.10659 | 8.40412 |
Annual Sum or Average | 5943.00000 | 24.01839 | 28.62409 | 0.01955 | 8.47080 |
Minimum of Months | 454.00000 | 22.62603 | 15.75504 | -0.5642 | 6.59927 |
Maximum of Months | 514.00000 | 24.75119 | 44.04153 | 0.46894 | 12.79252 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.87711 | 24.03288 | -0.0252 | 6.63205 |
February | 454.00000 | 22.18407 | 39.40479 | -0.1205 | 6.44496 |
March | 514.00000 | 22.85258 | 29.70582 | -0.0023 | 6.67061 |
April | 485.00000 | 24.13567 | 19.47584 | 0.32515 | 8.20595 |
May | 508.00000 | 24.31968 | 18.49784 | -0.4485 | 10.61769 |
June | 496.00000 | 24.47944 | 25.40895 | -0.2616 | 7.70146 |
July | 497.00000 | 24.59991 | 41.81999 | -0.1406 | 6.74207 |
August | 514.00000 | 24.46940 | 44.39742 | -0.1605 | 6.64133 |
September | 485.00000 | 24.54177 | 43.96692 | -0.1590 | 6.76550 |
October | 502.00000 | 24.11813 | 27.25334 | 0.36140 | 9.07302 |
November | 489.00000 | 23.55446 | 28.39460 | 0.18938 | 7.33654 |
December | 497.00000 | 22.49760 | 17.95002 | -0.1656 | 7.29833 |
Annual Sum or Average | 5943.00000 | 23.72826 | 29.96545 | -0.0515 | 7.52024 |
Minimum of Months | 454.00000 | 22.18407 | 17.95002 | -0.4485 | 6.44496 |
Maximum of Months | 514.00000 | 24.59991 | 44.39742 | 0.36140 | 10.61769 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.57796 | 25.37055 | -0.1270 | 6.99071 |
February | 454.00000 | 22.28219 | 39.47083 | -0.1185 | 6.34432 |
March | 514.00000 | 23.02639 | 29.69906 | 0.01885 | 6.53377 |
April | 485.00000 | 24.06385 | 19.89977 | 0.25988 | 6.95243 |
May | 508.00000 | 24.32651 | 18.70601 | -0.5044 | 10.97363 |
June | 496.00000 | 24.50172 | 25.72381 | -0.3195 | 8.14033 |
July | 497.00000 | 24.59253 | 43.31358 | -0.1904 | 6.86444 |
August | 514.00000 | 24.42094 | 46.18968 | -0.2421 | 7.00524 |
September | 485.00000 | 24.46349 | 45.70613 | -0.2587 | 7.47563 |
October | 502.00000 | 23.77637 | 28.54441 | 0.22903 | 7.56022 |
November | 489.00000 | 22.98685 | 30.12607 | 0.01327 | 6.90782 |
December | 497.00000 | 21.95126 | 19.30872 | -0.3262 | 8.68927 |
Annual Sum or Average | 5943.00000 | 23.58964 | 30.94857 | -0.1315 | 7.54869 |
Minimum of Months | 454.00000 | 21.95126 | 18.70601 | -0.5044 | 6.34432 |
Maximum of Months | 514.00000 | 24.59253 | 46.18968 | 0.25988 | 10.97363 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.82423 | 24.00788 | -0.0423 | 6.92624 |
February | 385.00000 | 22.50077 | 38.21626 | -0.0428 | 6.73525 |
March | 433.00000 | 23.21568 | 28.30777 | 0.09145 | 7.05004 |
April | 410.00000 | 24.32045 | 18.79389 | 0.37405 | 9.08272 |
May | 430.00000 | 24.52682 | 17.89527 | -0.3603 | 9.50908 |
June | 418.00000 | 24.62446 | 25.04556 | -0.2034 | 7.69395 |
July | 422.00000 | 24.74586 | 42.27491 | -0.0786 | 6.90759 |
August | 433.00000 | 24.55203 | 44.95043 | -0.1376 | 6.95295 |
September | 410.00000 | 24.57326 | 44.79733 | -0.1751 | 7.38442 |
October | 427.00000 | 23.95745 | 27.18929 | 0.30811 | 9.05633 |
November | 417.00000 | 23.14573 | 29.12145 | 0.07842 | 6.97055 |
December | 422.00000 | 22.21340 | 17.83889 | -0.2450 | 8.13235 |
Annual Sum or Average | 5034.00000 | 23.77365 | 29.80598 | -0.0368 | 7.70580 |
Minimum of Months | 385.00000 | 22.21340 | 17.83889 | -0.3603 | 6.73525 |
Maximum of Months | 433.00000 | 24.74586 | 44.95043 | 0.37405 | 9.50908 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.67076 | 21.98945 | 0.22217 | 8.76687 |
February | 454.00000 | 23.07403 | 36.29739 | 0.11415 | 7.42403 |
March | 514.00000 | 23.47870 | 27.92606 | 0.16567 | 7.43402 |
April | 485.00000 | 24.19490 | 19.33199 | 0.33508 | 8.31482 |
May | 508.00000 | 24.31907 | 18.63171 | -0.4891 | 11.03436 |
June | 496.00000 | 24.45350 | 25.81383 | -0.3434 | 8.48964 |
July | 497.00000 | 24.57431 | 43.29043 | -0.1906 | 7.03032 |
August | 514.00000 | 24.44121 | 45.95525 | -0.1996 | 6.87748 |
September | 485.00000 | 24.52791 | 45.14887 | -0.1661 | 7.14666 |
October | 502.00000 | 24.18348 | 26.85009 | 0.40689 | 10.46390 |
November | 489.00000 | 23.78334 | 27.41934 | 0.28197 | 8.83024 |
December | 497.00000 | 23.31811 | 16.35171 | 0.06773 | 8.65638 |
Annual Sum or Average | 5943.00000 | 24.00731 | 29.54121 | 0.01517 | 8.38127 |
Minimum of Months | 454.00000 | 23.07403 | 16.35171 | -0.4891 | 6.87748 |
Maximum of Months | 514.00000 | 24.57431 | 45.95525 | 0.40689 | 11.03436 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.67703 | 24.22956 | -0.0597 | 7.46662 |
February | 454.00000 | 22.24389 | 38.74256 | -0.0945 | 6.73459 |
March | 514.00000 | 22.98045 | 29.07176 | 0.04845 | 7.12220 |
April | 485.00000 | 24.07310 | 19.66163 | 0.33064 | 8.69044 |
May | 508.00000 | 24.29957 | 18.70777 | -0.4252 | 10.77933 |
June | 496.00000 | 24.46841 | 25.78250 | -0.2472 | 7.94053 |
July | 497.00000 | 24.55425 | 43.28894 | -0.1497 | 7.12003 |
August | 514.00000 | 24.40343 | 46.09100 | -0.1845 | 7.13165 |
September | 485.00000 | 24.43768 | 45.60112 | -0.2079 | 7.45167 |
October | 502.00000 | 23.75423 | 28.04501 | 0.27289 | 8.68515 |
November | 489.00000 | 23.03067 | 29.23371 | 0.06761 | 7.54709 |
December | 497.00000 | 22.10479 | 18.20110 | -0.2595 | 8.78255 |
Annual Sum or Average | 5943.00000 | 23.59453 | 30.50051 | -0.0766 | 7.96393 |
Minimum of Months | 454.00000 | 22.10479 | 18.20110 | -0.4252 | 6.73459 |
Maximum of Months | 514.00000 | 24.55425 | 46.09100 | 0.33064 | 10.77933 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.184766E+11 | 0.467120E+10 | 276.94 | 0.183342E+11 | 0.142405E+09 | 0.00 | 1.00 | 17-JAN-14:50 | 0.00 | 01-JAN-00:10 | 51341.82 | 31-JAN-17:00 | 51341.82 | 31-JAN-17:00 | 6345.97 | 08-JAN-15:53 | 13377.60 | 31-JAN-17:00 | 0.00 |
February | 0.414885E+10 | 0.113572E+10 | 149.83 | 0.362879E+10 | 0.520054E+09 | 0.00 | 0.62 | 22-FEB-16:10 | 0.00 | 01-FEB-00:10 | 22742.03 | 22-FEB-16:10 | 22742.03 | 22-FEB-16:10 | 4560.35 | 17-FEB-12:00 | 5779.14 | 22-FEB-16:10 | 0.00 |
March | 0.178912E+11 | 0.461218E+10 | 293.24 | 0.174640E+11 | 0.427207E+09 | 0.00 | 1.00 | 15-MAR-15:00 | 0.00 | 01-MAR-00:10 | 49546.37 | 16-MAR-15:50 | 49546.37 | 16-MAR-15:50 | 2856.01 | 18-MAR-09:10 | 12839.78 | 16-MAR-15:50 | 0.00 |
April | 0.495465E+11 | 0.133389E+11 | 407.99 | 0.494591E+11 | 87415851.19 | 0.00 | 1.00 | 03-APR-09:40 | 0.00 | 01-APR-00:10 | 70513.78 | 14-APR-16:00 | 70513.78 | 14-APR-16:00 | 2695.77 | 16-APR-09:50 | 21891.67 | 14-APR-16:00 | 0.00 |
May | 0.656547E+11 | 0.184547E+11 | 454.88 | 0.656160E+11 | 38669107.88 | 0.00 | 1.00 | 01-MAY-10:00 | 0.00 | 01-MAY-00:10 | 72785.79 | 31-MAY-16:00 | 72785.79 | 31-MAY-16:00 | 2470.85 | 26-MAY-05:10 | 24035.52 | 31-MAY-16:00 | 0.00 |
June | 0.876274E+11 | 0.275555E+11 | 480.58 | 0.873743E+11 | 0.253129E+09 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 94173.29 | 29-JUN-06:03 | 94173.29 | 29-JUN-06:03 | 5844.13 | 30-JUN-11:04 | 32493.63 | 28-JUN-16:00 | 0.00 |
July | 0.899113E+11 | 0.265795E+11 | 497.42 | 0.834805E+11 | 0.643085E+10 | 0.00 | 1.00 | 01-JUL-08:40 | 0.00 | 01-JUL-00:03 | 135399.87 | 15-JUL-06:03 | 97110.05 | 10-JUL-04:02 | 80913.13 | 14-JUL-04:03 | 30759.10 | 18-JUL-06:03 | 0.00 |
August | 0.936116E+11 | 0.275123E+11 | 496.35 | 0.864850E+11 | 0.712662E+10 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:15 | 133404.91 | 01-AUG-04:03 | 98108.23 | 28-AUG-06:03 | 64658.46 | 01-AUG-04:03 | 30750.38 | 01-AUG-04:03 | 0.00 |
September | 0.812670E+11 | 0.226908E+11 | 452.77 | 0.740676E+11 | 0.719943E+10 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 129378.55 | 08-SEP-04:02 | 92995.97 | 19-SEP-04:02 | 75889.99 | 05-SEP-06:03 | 30721.05 | 08-SEP-04:02 | 0.00 |
October | 0.460210E+11 | 0.122739E+11 | 381.46 | 0.446438E+11 | 0.137719E+10 | 0.00 | 1.00 | 01-OCT-11:53 | 0.00 | 01-OCT-00:10 | 105709.77 | 03-OCT-06:03 | 86820.59 | 02-OCT-06:03 | 49482.26 | 03-OCT-06:03 | 24413.17 | 02-OCT-14:00 | 0.00 |
November | 0.208365E+11 | 0.520887E+10 | 280.05 | 0.195607E+11 | 0.127577E+10 | 0.00 | 1.00 | 01-NOV-10:20 | 0.00 | 01-NOV-00:10 | 59139.41 | 01-NOV-16:00 | 59139.41 | 01-NOV-16:00 | 31535.96 | 13-NOV-07:02 | 15132.79 | 01-NOV-15:20 | 0.00 |
December | 0.876688E+10 | 0.227635E+10 | 190.25 | 0.873582E+10 | 31057452.45 | 0.00 | 1.00 | 21-DEC-16:10 | 0.00 | 01-DEC-00:10 | 45586.35 | 22-DEC-16:30 | 45586.35 | 22-DEC-16:30 | 1139.09 | 03-DEC-16:00 | 10622.22 | 22-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.583760E+12 | 0.166310E+12 | 4361.77 | 0.558850E+12 | 0.249098E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.414885E+10 | 0.113572E+10 | 149.83 | 0.362879E+10 | 31057452.45 | 0.00 | 0.62 | 0.00 | 22742.03 | 22742.03 | 1139.09 | 5779.14 | 0.00 | ||||||
Maximum of Months | 0.936116E+11 | 0.275555E+11 | 497.42 | 0.873743E+11 | 0.719943E+10 | 0.00 | 1.00 | 0.00 | 135399.87 | 98108.23 | 80913.13 | 32493.63 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.153005E+11 | 0.391758E+10 | 275.75 | 0.151552E+11 | 0.145316E+09 | 0.00 | 1.00 | 19-JAN-15:40 | 0.00 | 01-JAN-00:10 | 43264.20 | 31-JAN-16:30 | 43264.20 | 31-JAN-16:30 | 3262.67 | 08-JAN-12:00 | 11274.60 | 31-JAN-16:30 | 0.00 |
February | 0.349142E+10 | 0.960898E+09 | 151.04 | 0.296975E+10 | 0.521669E+09 | 0.00 | 0.64 | 22-FEB-16:00 | 0.00 | 01-FEB-00:10 | 21277.56 | 22-FEB-16:00 | 21277.56 | 22-FEB-16:00 | 3961.22 | 18-FEB-11:20 | 5385.36 | 22-FEB-16:00 | 0.00 |
March | 0.153215E+11 | 0.398304E+10 | 296.22 | 0.148250E+11 | 0.496441E+09 | 0.00 | 1.00 | 15-MAR-16:00 | 0.00 | 01-MAR-00:10 | 46341.36 | 16-MAR-15:40 | 46341.36 | 16-MAR-15:40 | 2704.02 | 18-MAR-09:20 | 12008.55 | 16-MAR-15:40 | 0.00 |
April | 0.443534E+11 | 0.119750E+11 | 411.05 | 0.442778E+11 | 75562654.65 | 0.00 | 1.00 | 02-APR-15:02 | 0.00 | 01-APR-00:10 | 65497.48 | 14-APR-15:20 | 65497.48 | 14-APR-15:20 | 2338.12 | 16-APR-09:55 | 20333.07 | 14-APR-15:20 | 0.00 |
May | 0.592859E+11 | 0.166928E+11 | 460.38 | 0.592587E+11 | 27190154.85 | 0.00 | 1.00 | 01-MAY-10:00 | 0.00 | 01-MAY-00:10 | 66364.82 | 18-MAY-15:30 | 66364.82 | 18-MAY-15:30 | 2031.68 | 26-MAY-05:10 | 21623.08 | 31-MAY-16:00 | 0.00 |
June | 0.801724E+11 | 0.252408E+11 | 483.31 | 0.800178E+11 | 0.154658E+09 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 84258.14 | 29-JUN-04:02 | 84258.14 | 29-JUN-04:02 | 4874.78 | 17-JUN-17:45 | 30681.11 | 28-JUN-15:00 | 0.00 |
July | 0.781421E+11 | 0.230871E+11 | 488.16 | 0.732269E+11 | 0.491521E+10 | 0.00 | 1.00 | 01-JUL-08:50 | 0.00 | 01-JUL-00:03 | 125051.45 | 14-JUL-05:03 | 86906.00 | 10-JUL-04:02 | 75329.89 | 14-JUL-05:03 | 28126.99 | 14-JUL-05:03 | 0.00 |
August | 0.792585E+11 | 0.233143E+11 | 485.08 | 0.740725E+11 | 0.518604E+10 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:05 | 121383.20 | 01-AUG-04:03 | 84489.25 | 16-AUG-04:02 | 61042.22 | 01-AUG-04:03 | 28565.64 | 25-AUG-15:10 | 0.00 |
September | 0.662385E+11 | 0.185794E+11 | 433.74 | 0.610238E+11 | 0.521477E+10 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 118722.30 | 02-SEP-05:03 | 79234.86 | 18-SEP-04:02 | 69418.52 | 05-SEP-06:03 | 27706.83 | 02-SEP-05:03 | 0.00 |
October | 0.370254E+11 | 0.998491E+10 | 374.00 | 0.358896E+11 | 0.113584E+10 | 0.00 | 1.00 | 01-OCT-11:53 | 0.00 | 01-OCT-00:10 | 84426.32 | 02-OCT-04:02 | 83653.13 | 02-OCT-04:02 | 33373.18 | 03-OCT-06:03 | 22179.36 | 02-OCT-14:00 | 0.00 |
November | 0.159651E+11 | 0.407104E+10 | 277.44 | 0.149077E+11 | 0.105738E+10 | 0.00 | 1.00 | 01-NOV-10:50 | 0.00 | 01-NOV-00:10 | 51099.53 | 01-NOV-15:30 | 51099.53 | 01-NOV-15:30 | 18971.96 | 13-NOV-15:40 | 13189.20 | 01-NOV-15:00 | 0.00 |
December | 0.699112E+10 | 0.184228E+10 | 186.89 | 0.694675E+10 | 44368995.40 | 0.00 | 1.00 | 22-DEC-16:30 | 0.00 | 01-DEC-00:10 | 37154.00 | 22-DEC-16:30 | 37154.00 | 22-DEC-16:30 | 1888.82 | 12-DEC-13:00 | 8627.26 | 22-DEC-16:30 | 0.00 |
Annual Sum or Average | 0.501546E+12 | 0.143649E+12 | 4323.06 | 0.482571E+12 | 0.189744E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.349142E+10 | 0.960898E+09 | 151.04 | 0.296975E+10 | 27190154.85 | 0.00 | 0.64 | 0.00 | 21277.56 | 21277.56 | 1888.82 | 5385.36 | 0.00 | ||||||
Maximum of Months | 0.801724E+11 | 0.252408E+11 | 488.16 | 0.800178E+11 | 0.521477E+10 | 0.00 | 1.00 | 0.00 | 125051.45 | 86906.00 | 75329.89 | 30681.11 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.150653E+11 | 0.391733E+10 | 272.93 | 0.148599E+11 | 0.205492E+09 | 0.00 | 1.00 | 27-JAN-14:30 | 0.00 | 01-JAN-00:10 | 47000.22 | 31-JAN-16:20 | 47000.22 | 31-JAN-16:20 | 2217.26 | 22-JAN-16:25 | 12249.10 | 31-JAN-16:20 | 0.00 |
February | 0.354421E+10 | 0.982119E+09 | 149.28 | 0.293063E+10 | 0.613580E+09 | 0.00 | 0.58 | 22-FEB-16:00 | 0.00 | 01-FEB-00:10 | 21457.72 | 22-FEB-16:00 | 21457.72 | 22-FEB-16:00 | 4523.21 | 18-FEB-14:00 | 5517.51 | 22-FEB-16:00 | 0.00 |
March | 0.159785E+11 | 0.418861E+10 | 296.03 | 0.152876E+11 | 0.690901E+09 | 0.00 | 1.00 | 16-MAR-12:40 | 0.00 | 01-MAR-00:10 | 53076.74 | 16-MAR-15:30 | 53076.74 | 16-MAR-15:30 | 3658.68 | 18-MAR-10:00 | 13753.54 | 16-MAR-15:30 | 0.00 |
April | 0.484437E+11 | 0.131975E+11 | 410.51 | 0.483197E+11 | 0.124057E+09 | 0.00 | 1.00 | 02-APR-13:53 | 0.00 | 01-APR-00:10 | 76240.85 | 14-APR-15:30 | 76240.85 | 14-APR-15:30 | 2703.71 | 16-APR-09:55 | 23666.14 | 14-APR-15:30 | 0.00 |
May | 0.649459E+11 | 0.184673E+11 | 460.01 | 0.648961E+11 | 49753523.52 | 0.00 | 1.00 | 01-MAY-10:50 | 0.00 | 01-MAY-00:10 | 77059.37 | 18-MAY-15:40 | 77059.37 | 18-MAY-15:40 | 2439.29 | 26-MAY-05:10 | 25161.53 | 31-MAY-16:00 | 0.00 |
June | 0.892306E+11 | 0.283284E+11 | 489.01 | 0.890263E+11 | 0.204298E+09 | 0.00 | 1.00 | 01-JUN-07:50 | 0.00 | 01-JUN-00:10 | 93747.43 | 28-JUN-15:00 | 93747.43 | 28-JUN-15:00 | 4901.27 | 17-JUN-17:10 | 36201.40 | 28-JUN-15:00 | 0.00 |
July | 0.859845E+11 | 0.255593E+11 | 492.57 | 0.808532E+11 | 0.513135E+10 | 0.00 | 1.00 | 01-JUL-09:40 | 0.00 | 01-JUL-00:03 | 131568.45 | 24-JUL-04:02 | 94419.87 | 12-JUL-04:02 | 62607.30 | 14-JUL-05:03 | 31497.69 | 19-JUL-13:40 | 0.00 |
August | 0.861538E+11 | 0.255306E+11 | 487.26 | 0.807472E+11 | 0.540658E+10 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:05 | 136760.59 | 01-AUG-04:03 | 92038.97 | 13-AUG-16:11 | 70525.33 | 01-AUG-04:03 | 33248.01 | 27-AUG-16:01 | 0.00 |
September | 0.706321E+11 | 0.199746E+11 | 436.17 | 0.652400E+11 | 0.539215E+10 | 0.00 | 1.00 | 01-SEP-08:00 | 0.00 | 01-SEP-00:10 | 106783.91 | 05-SEP-06:03 | 86168.14 | 08-SEP-15:50 | 63198.37 | 05-SEP-06:03 | 28893.45 | 08-SEP-15:50 | 0.00 |
October | 0.382625E+11 | 0.104416E+11 | 370.91 | 0.369912E+11 | 0.127128E+10 | 0.00 | 1.00 | 01-OCT-12:13 | 0.00 | 01-OCT-00:10 | 85906.80 | 02-OCT-04:02 | 85723.47 | 02-OCT-04:02 | 16043.37 | 03-OCT-06:03 | 24917.97 | 02-OCT-13:40 | 0.00 |
November | 0.156423E+11 | 0.405166E+10 | 275.03 | 0.145156E+11 | 0.112673E+10 | 0.00 | 1.00 | 01-NOV-12:10 | 0.00 | 01-NOV-00:10 | 57409.57 | 01-NOV-15:30 | 57409.57 | 01-NOV-15:30 | 15935.69 | 13-NOV-15:40 | 14770.28 | 01-NOV-15:20 | 0.00 |
December | 0.677516E+10 | 0.181189E+10 | 183.62 | 0.670870E+10 | 66458267.52 | 0.00 | 0.95 | 22-DEC-15:40 | 0.00 | 01-DEC-00:10 | 38897.30 | 22-DEC-15:40 | 38897.30 | 22-DEC-15:40 | 2217.67 | 12-DEC-15:00 | 9378.82 | 22-DEC-15:30 | 0.00 |
Annual Sum or Average | 0.540659E+12 | 0.156451E+12 | 4323.32 | 0.520376E+12 | 0.202826E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.354421E+10 | 0.982119E+09 | 149.28 | 0.293063E+10 | 49753523.52 | 0.00 | 0.58 | 0.00 | 21457.72 | 21457.72 | 2217.26 | 5517.51 | 0.00 | ||||||
Maximum of Months | 0.892306E+11 | 0.283284E+11 | 492.57 | 0.890263E+11 | 0.540658E+10 | 0.00 | 1.00 | 0.00 | 136760.59 | 94419.87 | 70525.33 | 36201.40 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 284.38 | 0.00 | 284.38 | 230.88 | 1238.97 | 0.00 | 0.00 | 0.00 |
February | 324.04 | 0.00 | 324.04 | 151.02 | 1221.37 | 0.00 | 0.00 | 0.00 |
March | 430.65 | 0.00 | 430.65 | 397.74 | 1103.15 | 0.00 | 0.00 | 0.00 |
April | 524.68 | 5.44 | 519.24 | 886.02 | 618.37 | 0.00 | 0.00 | 0.00 |
May | 614.20 | 49.18 | 565.02 | 1222.79 | 422.75 | 0.00 | 0.00 | 0.00 |
June | 713.74 | 129.68 | 584.06 | 1945.22 | 184.68 | 0.00 | 0.00 | 0.00 |
July | 608.68 | 63.41 | 545.27 | 1657.92 | 142.76 | 0.00 | 0.00 | 0.00 |
August | 491.32 | 12.21 | 479.11 | 1381.06 | 178.17 | 0.00 | 0.00 | 0.00 |
September | 463.55 | 0.12 | 463.43 | 1140.46 | 265.55 | 0.00 | 0.00 | 0.00 |
October | 358.64 | 0.00 | 358.64 | 539.24 | 800.57 | 0.00 | 0.00 | 0.00 |
November | 298.81 | 0.00 | 298.81 | 226.94 | 1151.08 | 0.00 | 0.00 | 0.00 |
December | 265.64 | 0.00 | 265.64 | 142.66 | 1503.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 448.64 | 21.72 | 426.93 | 829.94 | 733.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.64 | 0.00 | 265.64 | 142.66 | 142.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 713.74 | 129.68 | 584.06 | 1945.22 | 1503.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 612.46 | 384.21 | 228.25 | 782.11 | 769.98 | 0.00 | 0.00 | 0.00 |
February | 603.70 | 345.34 | 258.35 | 673.52 | 767.29 | 0.00 | 0.00 | 0.00 |
March | 755.50 | 388.63 | 366.86 | 973.19 | 689.27 | 0.00 | 0.00 | 0.00 |
April | 1078.43 | 642.76 | 435.67 | 1792.35 | 392.48 | 0.00 | 0.00 | 0.00 |
May | 1117.64 | 662.53 | 455.11 | 1999.20 | 281.27 | 0.00 | 0.00 | 0.00 |
June | 1164.95 | 723.88 | 441.07 | 2437.09 | 118.68 | 0.00 | 0.00 | 0.00 |
July | 983.87 | 554.77 | 429.11 | 2080.45 | 91.33 | 0.00 | 0.00 | 0.00 |
August | 933.78 | 532.91 | 400.87 | 1961.37 | 114.54 | 0.00 | 0.00 | 0.00 |
September | 766.23 | 369.34 | 396.89 | 1539.58 | 166.82 | 0.00 | 0.00 | 0.00 |
October | 769.63 | 468.39 | 301.24 | 1213.11 | 498.69 | 0.00 | 0.00 | 0.00 |
November | 591.80 | 355.27 | 236.54 | 747.08 | 721.29 | 0.00 | 0.00 | 0.00 |
December | 539.57 | 325.81 | 213.76 | 609.59 | 927.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 827.48 | 480.11 | 347.37 | 1404.20 | 460.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 539.57 | 325.81 | 213.76 | 609.59 | 91.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1164.95 | 723.88 | 455.11 | 2437.09 | 927.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2341.59 | 1870.16 | 471.43 | 3564.82 | 1232.35 | 0.00 | 0.00 | 0.00 |
February | 1480.56 | 998.54 | 482.02 | 1996.12 | 1180.53 | 0.00 | 0.00 | 0.00 |
March | 1231.93 | 634.51 | 597.42 | 1795.53 | 1108.28 | 0.00 | 0.00 | 0.00 |
April | 1048.70 | 423.78 | 624.92 | 2003.53 | 649.93 | 0.00 | 0.00 | 0.00 |
May | 702.74 | 116.10 | 586.64 | 1503.38 | 461.42 | 0.00 | 0.00 | 0.00 |
June | 601.75 | 46.39 | 555.36 | 1764.39 | 192.74 | 0.00 | 0.00 | 0.00 |
July | 614.88 | 63.61 | 551.26 | 1709.40 | 144.53 | 0.00 | 0.00 | 0.00 |
August | 747.66 | 206.62 | 541.05 | 1964.70 | 179.86 | 0.00 | 0.00 | 0.00 |
September | 1077.31 | 459.61 | 617.70 | 2336.68 | 268.79 | 0.00 | 0.00 | 0.00 |
October | 1716.58 | 1188.13 | 528.45 | 2892.40 | 792.15 | 0.00 | 0.00 | 0.00 |
November | 2000.47 | 1532.25 | 468.21 | 2996.33 | 1132.22 | 0.00 | 0.00 | 0.00 |
December | 2176.98 | 1723.38 | 453.61 | 3152.01 | 1454.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1311.80 | 771.77 | 540.02 | 2309.50 | 731.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 601.75 | 46.39 | 453.61 | 1503.38 | 144.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2341.59 | 1870.16 | 624.92 | 3564.82 | 1454.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.43 | 398.04 | 242.39 | 937.96 | 844.26 | 0.00 | 0.00 | 0.00 |
February | 518.81 | 250.82 | 268.00 | 599.47 | 806.46 | 0.00 | 0.00 | 0.00 |
March | 687.19 | 327.59 | 359.59 | 926.21 | 731.15 | 0.00 | 0.00 | 0.00 |
April | 1055.20 | 601.92 | 453.28 | 1818.17 | 441.54 | 0.00 | 0.00 | 0.00 |
May | 1057.90 | 593.17 | 464.74 | 1955.85 | 322.84 | 0.00 | 0.00 | 0.00 |
June | 1124.66 | 661.48 | 463.18 | 2397.34 | 142.57 | 0.00 | 0.00 | 0.00 |
July | 818.55 | 382.10 | 436.45 | 1809.47 | 104.97 | 0.00 | 0.00 | 0.00 |
August | 780.56 | 392.01 | 388.55 | 1717.16 | 127.95 | 0.00 | 0.00 | 0.00 |
September | 680.39 | 285.87 | 394.52 | 1414.86 | 182.98 | 0.00 | 0.00 | 0.00 |
October | 696.18 | 398.07 | 298.11 | 1151.70 | 541.96 | 0.00 | 0.00 | 0.00 |
November | 641.20 | 387.14 | 254.06 | 907.04 | 777.57 | 0.00 | 0.00 | 0.00 |
December | 516.78 | 294.24 | 222.54 | 674.67 | 1006.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 769.03 | 414.95 | 354.08 | 1362.39 | 501.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 516.78 | 250.82 | 222.54 | 599.47 | 104.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1124.66 | 661.48 | 464.74 | 2397.34 | 1006.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.79 | 0.00 | 94.79 | 74.06 | 441.12 | 0.00 | 0.00 | 0.00 |
February | 108.01 | 0.00 | 108.01 | 51.95 | 427.45 | 0.00 | 0.00 | 0.00 |
March | 143.54 | 0.00 | 143.54 | 139.47 | 372.12 | 0.00 | 0.00 | 0.00 |
April | 174.89 | 1.81 | 173.07 | 303.65 | 205.59 | 0.00 | 0.00 | 0.00 |
May | 204.72 | 16.39 | 188.33 | 416.93 | 136.81 | 0.00 | 0.00 | 0.00 |
June | 237.90 | 43.22 | 194.68 | 656.56 | 58.40 | 0.00 | 0.00 | 0.00 |
July | 202.88 | 21.14 | 181.75 | 556.50 | 47.51 | 0.00 | 0.00 | 0.00 |
August | 163.76 | 4.07 | 159.70 | 460.23 | 62.42 | 0.00 | 0.00 | 0.00 |
September | 154.51 | 0.04 | 154.47 | 376.71 | 96.68 | 0.00 | 0.00 | 0.00 |
October | 119.54 | 0.00 | 119.54 | 173.09 | 298.57 | 0.00 | 0.00 | 0.00 |
November | 99.60 | 0.00 | 99.60 | 67.15 | 434.70 | 0.00 | 0.00 | 0.00 |
December | 88.54 | 0.00 | 88.54 | 39.08 | 556.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.54 | 7.24 | 142.30 | 277.31 | 260.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.54 | 0.00 | 88.54 | 39.08 | 47.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.90 | 43.22 | 194.68 | 656.56 | 556.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.79 | 0.00 | 94.79 | 74.06 | 441.14 | 0.00 | 0.00 | 0.00 |
February | 108.01 | 0.00 | 108.01 | 51.95 | 427.47 | 0.00 | 0.00 | 0.00 |
March | 143.55 | 0.00 | 143.55 | 139.48 | 372.14 | 0.00 | 0.00 | 0.00 |
April | 174.89 | 1.81 | 173.08 | 303.66 | 205.60 | 0.00 | 0.00 | 0.00 |
May | 204.73 | 16.39 | 188.34 | 416.96 | 136.81 | 0.00 | 0.00 | 0.00 |
June | 237.91 | 43.23 | 194.69 | 656.60 | 58.41 | 0.00 | 0.00 | 0.00 |
July | 202.89 | 21.14 | 181.76 | 556.53 | 47.51 | 0.00 | 0.00 | 0.00 |
August | 163.77 | 4.07 | 159.70 | 460.25 | 62.42 | 0.00 | 0.00 | 0.00 |
September | 154.52 | 0.04 | 154.47 | 376.73 | 96.69 | 0.00 | 0.00 | 0.00 |
October | 119.55 | 0.00 | 119.55 | 173.10 | 298.59 | 0.00 | 0.00 | 0.00 |
November | 99.60 | 0.00 | 99.60 | 67.15 | 434.72 | 0.00 | 0.00 | 0.00 |
December | 88.54 | 0.00 | 88.54 | 39.08 | 556.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.55 | 7.24 | 142.31 | 277.32 | 260.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.54 | 0.00 | 88.54 | 39.08 | 47.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.91 | 43.23 | 194.69 | 656.60 | 556.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.79 | 0.00 | 94.79 | 74.06 | 441.14 | 0.00 | 0.00 | 0.00 |
February | 108.01 | 0.00 | 108.01 | 51.95 | 427.47 | 0.00 | 0.00 | 0.00 |
March | 143.55 | 0.00 | 143.55 | 139.48 | 372.14 | 0.00 | 0.00 | 0.00 |
April | 174.89 | 1.81 | 173.08 | 303.66 | 205.60 | 0.00 | 0.00 | 0.00 |
May | 204.73 | 16.39 | 188.34 | 416.96 | 136.81 | 0.00 | 0.00 | 0.00 |
June | 237.91 | 43.23 | 194.69 | 656.60 | 58.41 | 0.00 | 0.00 | 0.00 |
July | 202.89 | 21.14 | 181.76 | 556.53 | 47.51 | 0.00 | 0.00 | 0.00 |
August | 163.77 | 4.07 | 159.70 | 460.25 | 62.42 | 0.00 | 0.00 | 0.00 |
September | 154.52 | 0.04 | 154.47 | 376.73 | 96.69 | 0.00 | 0.00 | 0.00 |
October | 119.55 | 0.00 | 119.55 | 173.10 | 298.59 | 0.00 | 0.00 | 0.00 |
November | 99.60 | 0.00 | 99.60 | 67.15 | 434.72 | 0.00 | 0.00 | 0.00 |
December | 88.54 | 0.00 | 88.54 | 39.08 | 556.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.55 | 7.24 | 142.31 | 277.32 | 260.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.54 | 0.00 | 88.54 | 39.08 | 47.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.91 | 43.23 | 194.69 | 656.60 | 556.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 589.15 | 369.59 | 219.56 | 742.48 | 808.06 | 0.00 | 0.00 | 0.00 |
February | 580.72 | 332.20 | 248.52 | 650.92 | 790.86 | 0.00 | 0.00 | 0.00 |
March | 726.75 | 373.84 | 352.91 | 948.56 | 688.64 | 0.00 | 0.00 | 0.00 |
April | 1037.40 | 618.30 | 419.10 | 1742.55 | 391.71 | 0.00 | 0.00 | 0.00 |
May | 1075.12 | 637.32 | 437.80 | 1944.34 | 276.46 | 0.00 | 0.00 | 0.00 |
June | 1120.62 | 696.34 | 424.29 | 2362.18 | 116.75 | 0.00 | 0.00 | 0.00 |
July | 946.44 | 533.65 | 412.78 | 2009.76 | 94.75 | 0.00 | 0.00 | 0.00 |
August | 898.25 | 512.63 | 385.62 | 1889.95 | 125.22 | 0.00 | 0.00 | 0.00 |
September | 737.07 | 355.28 | 381.79 | 1477.41 | 183.02 | 0.00 | 0.00 | 0.00 |
October | 740.35 | 450.57 | 289.78 | 1156.22 | 545.34 | 0.00 | 0.00 | 0.00 |
November | 569.29 | 341.75 | 227.54 | 697.28 | 793.62 | 0.00 | 0.00 | 0.00 |
December | 519.04 | 313.41 | 205.63 | 558.20 | 1004.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 796.00 | 461.84 | 334.15 | 1351.62 | 483.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 519.04 | 313.41 | 205.63 | 558.20 | 94.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1120.62 | 696.34 | 437.80 | 2362.18 | 1004.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.29 | 14.61 | 8.68 | 29.36 | 31.95 | 0.00 | 0.00 | 0.00 |
February | 22.96 | 13.13 | 9.83 | 25.74 | 31.27 | 0.00 | 0.00 | 0.00 |
March | 28.74 | 14.78 | 13.95 | 37.51 | 27.23 | 0.00 | 0.00 | 0.00 |
April | 41.02 | 24.45 | 16.57 | 68.90 | 15.49 | 0.00 | 0.00 | 0.00 |
May | 42.51 | 25.20 | 17.31 | 76.88 | 10.93 | 0.00 | 0.00 | 0.00 |
June | 44.31 | 27.53 | 16.78 | 93.40 | 4.62 | 0.00 | 0.00 | 0.00 |
July | 37.42 | 21.10 | 16.32 | 79.46 | 3.75 | 0.00 | 0.00 | 0.00 |
August | 35.52 | 20.27 | 15.25 | 74.73 | 4.95 | 0.00 | 0.00 | 0.00 |
September | 29.14 | 14.05 | 15.10 | 58.42 | 7.24 | 0.00 | 0.00 | 0.00 |
October | 29.27 | 17.82 | 11.46 | 45.72 | 21.56 | 0.00 | 0.00 | 0.00 |
November | 22.51 | 13.51 | 9.00 | 27.57 | 31.38 | 0.00 | 0.00 | 0.00 |
December | 20.52 | 12.39 | 8.13 | 22.07 | 39.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.47 | 18.26 | 13.21 | 53.44 | 19.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.52 | 12.39 | 8.13 | 22.07 | 3.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.31 | 27.53 | 17.31 | 93.40 | 39.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 780.52 | 623.38 | 157.14 | 1188.59 | 463.02 | 0.00 | 0.00 | 0.00 |
February | 493.51 | 332.84 | 160.67 | 674.84 | 423.88 | 0.00 | 0.00 | 0.00 |
March | 410.64 | 211.50 | 199.14 | 610.60 | 382.58 | 0.00 | 0.00 | 0.00 |
April | 349.56 | 141.26 | 208.31 | 677.22 | 222.13 | 0.00 | 0.00 | 0.00 |
May | 234.24 | 38.70 | 195.54 | 509.50 | 151.92 | 0.00 | 0.00 | 0.00 |
June | 200.58 | 15.46 | 185.12 | 590.43 | 62.36 | 0.00 | 0.00 | 0.00 |
July | 204.96 | 21.20 | 183.75 | 569.13 | 49.89 | 0.00 | 0.00 | 0.00 |
August | 249.22 | 68.87 | 180.35 | 650.00 | 67.19 | 0.00 | 0.00 | 0.00 |
September | 359.10 | 153.20 | 205.90 | 772.81 | 104.05 | 0.00 | 0.00 | 0.00 |
October | 572.18 | 396.04 | 176.15 | 960.89 | 302.61 | 0.00 | 0.00 | 0.00 |
November | 666.81 | 510.74 | 156.07 | 995.01 | 435.63 | 0.00 | 0.00 | 0.00 |
December | 725.65 | 574.45 | 151.20 | 1046.43 | 552.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 437.26 | 257.25 | 180.01 | 771.37 | 267.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 200.58 | 15.46 | 151.20 | 509.50 | 49.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 780.52 | 623.38 | 208.31 | 1188.59 | 552.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 780.52 | 623.38 | 157.14 | 1188.59 | 463.02 | 0.00 | 0.00 | 0.00 |
February | 493.51 | 332.84 | 160.67 | 674.84 | 423.88 | 0.00 | 0.00 | 0.00 |
March | 410.64 | 211.50 | 199.14 | 610.60 | 382.58 | 0.00 | 0.00 | 0.00 |
April | 349.56 | 141.26 | 208.31 | 677.22 | 222.13 | 0.00 | 0.00 | 0.00 |
May | 234.24 | 38.70 | 195.54 | 509.50 | 151.92 | 0.00 | 0.00 | 0.00 |
June | 200.58 | 15.46 | 185.12 | 590.43 | 62.36 | 0.00 | 0.00 | 0.00 |
July | 204.96 | 21.20 | 183.75 | 569.13 | 49.89 | 0.00 | 0.00 | 0.00 |
August | 249.22 | 68.87 | 180.35 | 650.00 | 67.19 | 0.00 | 0.00 | 0.00 |
September | 359.10 | 153.20 | 205.90 | 772.81 | 104.05 | 0.00 | 0.00 | 0.00 |
October | 572.18 | 396.04 | 176.15 | 960.89 | 302.61 | 0.00 | 0.00 | 0.00 |
November | 666.81 | 510.74 | 156.07 | 995.01 | 435.63 | 0.00 | 0.00 | 0.00 |
December | 725.65 | 574.45 | 151.20 | 1046.43 | 552.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 437.26 | 257.25 | 180.01 | 771.37 | 267.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 200.58 | 15.46 | 151.20 | 509.50 | 49.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 780.52 | 623.38 | 208.31 | 1188.59 | 552.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 780.47 | 623.34 | 157.13 | 1188.52 | 462.99 | 0.00 | 0.00 | 0.00 |
February | 493.48 | 332.82 | 160.66 | 674.80 | 423.85 | 0.00 | 0.00 | 0.00 |
March | 410.61 | 211.49 | 199.13 | 610.56 | 382.56 | 0.00 | 0.00 | 0.00 |
April | 349.54 | 141.25 | 208.29 | 677.18 | 222.11 | 0.00 | 0.00 | 0.00 |
May | 234.23 | 38.70 | 195.53 | 509.47 | 151.91 | 0.00 | 0.00 | 0.00 |
June | 200.57 | 15.46 | 185.11 | 590.40 | 62.36 | 0.00 | 0.00 | 0.00 |
July | 204.95 | 21.20 | 183.74 | 569.09 | 49.89 | 0.00 | 0.00 | 0.00 |
August | 249.20 | 68.87 | 180.34 | 649.96 | 67.18 | 0.00 | 0.00 | 0.00 |
September | 359.08 | 153.19 | 205.89 | 772.76 | 104.04 | 0.00 | 0.00 | 0.00 |
October | 572.15 | 396.01 | 176.14 | 960.83 | 302.59 | 0.00 | 0.00 | 0.00 |
November | 666.77 | 510.71 | 156.06 | 994.94 | 435.60 | 0.00 | 0.00 | 0.00 |
December | 725.60 | 574.41 | 151.19 | 1046.37 | 552.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 437.23 | 257.24 | 179.99 | 771.32 | 267.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 200.57 | 15.46 | 151.19 | 509.47 | 49.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 780.47 | 623.34 | 208.29 | 1188.52 | 552.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 616.07 | 382.89 | 233.17 | 898.94 | 890.67 | 0.00 | 0.00 | 0.00 |
February | 499.07 | 241.27 | 257.80 | 584.19 | 829.82 | 0.00 | 0.00 | 0.00 |
March | 661.04 | 315.13 | 345.91 | 906.64 | 731.99 | 0.00 | 0.00 | 0.00 |
April | 1015.05 | 579.01 | 436.04 | 1766.78 | 445.28 | 0.00 | 0.00 | 0.00 |
May | 1017.65 | 570.60 | 447.06 | 1900.39 | 321.56 | 0.00 | 0.00 | 0.00 |
June | 1081.87 | 636.31 | 445.56 | 2322.21 | 142.64 | 0.00 | 0.00 | 0.00 |
July | 787.41 | 367.56 | 419.85 | 1746.60 | 108.24 | 0.00 | 0.00 | 0.00 |
August | 750.86 | 377.10 | 373.77 | 1651.65 | 138.00 | 0.00 | 0.00 | 0.00 |
September | 654.50 | 274.99 | 379.51 | 1356.13 | 200.29 | 0.00 | 0.00 | 0.00 |
October | 669.69 | 382.93 | 286.76 | 1097.92 | 595.64 | 0.00 | 0.00 | 0.00 |
November | 616.80 | 372.41 | 244.40 | 858.76 | 862.35 | 0.00 | 0.00 | 0.00 |
December | 497.12 | 283.04 | 214.07 | 635.15 | 1087.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 739.77 | 399.16 | 340.61 | 1313.51 | 528.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 497.12 | 241.27 | 214.07 | 584.19 | 108.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1081.87 | 636.31 | 447.06 | 2322.21 | 1087.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.36 | 15.14 | 9.22 | 35.54 | 35.22 | 0.00 | 0.00 | 0.00 |
February | 19.73 | 9.54 | 10.19 | 23.10 | 32.81 | 0.00 | 0.00 | 0.00 |
March | 26.14 | 12.46 | 13.68 | 35.85 | 28.94 | 0.00 | 0.00 | 0.00 |
April | 40.13 | 22.89 | 17.24 | 69.86 | 17.61 | 0.00 | 0.00 | 0.00 |
May | 40.24 | 22.56 | 17.68 | 75.14 | 12.71 | 0.00 | 0.00 | 0.00 |
June | 42.78 | 25.16 | 17.62 | 91.82 | 5.64 | 0.00 | 0.00 | 0.00 |
July | 31.13 | 14.53 | 16.60 | 69.06 | 4.28 | 0.00 | 0.00 | 0.00 |
August | 29.69 | 14.91 | 14.78 | 65.30 | 5.46 | 0.00 | 0.00 | 0.00 |
September | 25.88 | 10.87 | 15.01 | 53.62 | 7.92 | 0.00 | 0.00 | 0.00 |
October | 26.48 | 15.14 | 11.34 | 43.41 | 23.55 | 0.00 | 0.00 | 0.00 |
November | 24.39 | 14.72 | 9.66 | 33.95 | 34.10 | 0.00 | 0.00 | 0.00 |
December | 19.66 | 11.19 | 8.46 | 25.11 | 43.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.25 | 15.78 | 13.47 | 51.93 | 20.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.66 | 9.54 | 8.46 | 23.10 | 4.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.78 | 25.16 | 17.68 | 91.82 | 43.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 284.38 | 0.00 | 284.38 | 209.84 | 1341.67 | 0.00 | 0.00 | 0.00 |
February | 324.04 | 0.00 | 324.04 | 136.57 | 1329.81 | 0.00 | 0.00 | 0.00 |
March | 430.65 | 0.00 | 430.65 | 381.11 | 1177.93 | 0.00 | 0.00 | 0.00 |
April | 524.68 | 5.44 | 519.24 | 886.42 | 647.83 | 0.00 | 0.00 | 0.00 |
May | 614.20 | 49.18 | 565.02 | 1225.12 | 435.75 | 0.00 | 0.00 | 0.00 |
June | 713.74 | 129.68 | 584.06 | 1955.95 | 187.79 | 0.00 | 0.00 | 0.00 |
July | 608.68 | 63.41 | 545.27 | 1670.63 | 144.41 | 0.00 | 0.00 | 0.00 |
August | 491.32 | 12.21 | 479.11 | 1389.42 | 183.35 | 0.00 | 0.00 | 0.00 |
September | 463.55 | 0.12 | 463.43 | 1144.88 | 276.18 | 0.00 | 0.00 | 0.00 |
October | 358.64 | 0.00 | 358.64 | 529.55 | 860.11 | 0.00 | 0.00 | 0.00 |
November | 298.81 | 0.00 | 298.81 | 207.91 | 1254.16 | 0.00 | 0.00 | 0.00 |
December | 265.64 | 0.00 | 265.64 | 121.46 | 1631.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 448.64 | 21.72 | 426.93 | 824.71 | 786.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.64 | 0.00 | 265.64 | 121.46 | 144.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 713.74 | 129.68 | 584.06 | 1955.95 | 1631.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 612.46 | 384.21 | 228.25 | 764.62 | 823.05 | 0.00 | 0.00 | 0.00 |
February | 603.70 | 345.34 | 258.35 | 660.59 | 824.61 | 0.00 | 0.00 | 0.00 |
March | 755.50 | 388.63 | 366.86 | 961.68 | 727.28 | 0.00 | 0.00 | 0.00 |
April | 1078.43 | 642.76 | 435.67 | 1795.68 | 405.88 | 0.00 | 0.00 | 0.00 |
May | 1117.64 | 662.53 | 455.11 | 2006.08 | 288.99 | 0.00 | 0.00 | 0.00 |
June | 1164.95 | 723.88 | 441.07 | 2448.65 | 120.77 | 0.00 | 0.00 | 0.00 |
July | 983.87 | 554.77 | 429.11 | 2092.73 | 92.30 | 0.00 | 0.00 | 0.00 |
August | 933.78 | 532.91 | 400.87 | 1970.94 | 117.89 | 0.00 | 0.00 | 0.00 |
September | 766.23 | 369.34 | 396.89 | 1545.30 | 172.71 | 0.00 | 0.00 | 0.00 |
October | 769.63 | 468.39 | 301.24 | 1207.92 | 528.47 | 0.00 | 0.00 | 0.00 |
November | 591.80 | 355.27 | 236.54 | 730.87 | 775.45 | 0.00 | 0.00 | 0.00 |
December | 539.57 | 325.81 | 213.76 | 586.12 | 996.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 827.48 | 480.11 | 347.37 | 1401.11 | 488.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 539.57 | 325.81 | 213.76 | 586.12 | 92.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1164.95 | 723.88 | 455.11 | 2448.65 | 996.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2341.59 | 1870.16 | 471.43 | 3546.84 | 1313.15 | 0.00 | 0.00 | 0.00 |
February | 1480.56 | 998.54 | 482.02 | 1979.11 | 1271.35 | 0.00 | 0.00 | 0.00 |
March | 1231.93 | 634.51 | 597.42 | 1781.83 | 1174.18 | 0.00 | 0.00 | 0.00 |
April | 1048.70 | 423.78 | 624.92 | 2007.98 | 679.36 | 0.00 | 0.00 | 0.00 |
May | 702.74 | 116.10 | 586.64 | 1509.02 | 479.40 | 0.00 | 0.00 | 0.00 |
June | 601.75 | 46.39 | 555.36 | 1775.38 | 198.21 | 0.00 | 0.00 | 0.00 |
July | 614.88 | 63.61 | 551.26 | 1722.65 | 147.50 | 0.00 | 0.00 | 0.00 |
August | 747.66 | 206.62 | 541.05 | 1975.17 | 186.50 | 0.00 | 0.00 | 0.00 |
September | 1077.31 | 459.61 | 617.70 | 2344.88 | 279.74 | 0.00 | 0.00 | 0.00 |
October | 1716.58 | 1188.13 | 528.45 | 2887.58 | 840.39 | 0.00 | 0.00 | 0.00 |
November | 2000.47 | 1532.25 | 468.21 | 2977.91 | 1213.10 | 0.00 | 0.00 | 0.00 |
December | 2176.98 | 1723.38 | 453.61 | 3125.12 | 1558.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1311.80 | 771.77 | 540.02 | 2305.74 | 776.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 601.75 | 46.39 | 453.61 | 1509.02 | 147.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2341.59 | 1870.16 | 624.92 | 3546.84 | 1558.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.43 | 398.04 | 242.39 | 927.65 | 906.93 | 0.00 | 0.00 | 0.00 |
February | 518.81 | 250.82 | 268.00 | 591.66 | 871.69 | 0.00 | 0.00 | 0.00 |
March | 687.19 | 327.59 | 359.59 | 917.38 | 777.35 | 0.00 | 0.00 | 0.00 |
April | 1055.20 | 601.92 | 453.28 | 1820.95 | 460.91 | 0.00 | 0.00 | 0.00 |
May | 1057.90 | 593.17 | 464.74 | 1961.38 | 334.51 | 0.00 | 0.00 | 0.00 |
June | 1124.66 | 661.48 | 463.18 | 2407.57 | 146.30 | 0.00 | 0.00 | 0.00 |
July | 818.55 | 382.10 | 436.45 | 1819.37 | 106.81 | 0.00 | 0.00 | 0.00 |
August | 780.56 | 392.01 | 388.55 | 1724.29 | 132.27 | 0.00 | 0.00 | 0.00 |
September | 680.39 | 285.87 | 394.52 | 1419.02 | 190.39 | 0.00 | 0.00 | 0.00 |
October | 696.18 | 398.07 | 298.11 | 1147.52 | 578.88 | 0.00 | 0.00 | 0.00 |
November | 641.20 | 387.14 | 254.06 | 896.88 | 840.45 | 0.00 | 0.00 | 0.00 |
December | 516.78 | 294.24 | 222.54 | 662.09 | 1083.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 769.03 | 414.95 | 354.08 | 1361.23 | 534.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 516.78 | 250.82 | 222.54 | 591.66 | 106.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1124.66 | 661.48 | 464.74 | 2407.57 | 1083.77 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.761678E+09 | 0.00 | 0.761678E+09 | 0.618388E+09 | 0.331847E+10 |
February | 0.783922E+09 | 0.00 | 0.783922E+09 | 0.365346E+09 | 0.295473E+10 |
March | 0.115346E+10 | 0.00 | 0.115346E+10 | 0.106531E+10 | 0.295467E+10 |
April | 0.135998E+10 | 14113125.25 | 0.134587E+10 | 0.229657E+10 | 0.160282E+10 |
May | 0.164507E+10 | 0.131722E+09 | 0.151335E+10 | 0.327511E+10 | 0.113229E+10 |
June | 0.185001E+10 | 0.336128E+09 | 0.151388E+10 | 0.504200E+10 | 0.478692E+09 |
July | 0.163030E+10 | 0.169845E+09 | 0.146045E+10 | 0.444056E+10 | 0.382372E+09 |
August | 0.131594E+10 | 32691117.58 | 0.128325E+10 | 0.369904E+10 | 0.477212E+09 |
September | 0.120152E+10 | 320748.24 | 0.120120E+10 | 0.295607E+10 | 0.688304E+09 |
October | 0.960577E+09 | 0.00 | 0.960577E+09 | 0.144431E+10 | 0.214426E+10 |
November | 0.774520E+09 | 0.00 | 0.774520E+09 | 0.588234E+09 | 0.298360E+10 |
December | 0.711477E+09 | 0.00 | 0.711477E+09 | 0.382088E+09 | 0.402750E+10 |
Annual Sum or Average | 0.141485E+11 | 0.684819E+09 | 0.134636E+11 | 0.261730E+11 | 0.231449E+11 |
Minimum of Months | 0.711477E+09 | 0.00 | 0.711477E+09 | 0.365346E+09 | 0.382372E+09 |
Maximum of Months | 0.185001E+10 | 0.336128E+09 | 0.151388E+10 | 0.504200E+10 | 0.402750E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.164041E+10 | 0.102907E+10 | 0.611334E+09 | 0.209480E+10 | 0.206231E+10 |
February | 0.146046E+10 | 0.835450E+09 | 0.625010E+09 | 0.162938E+10 | 0.185622E+10 |
March | 0.202352E+10 | 0.104092E+10 | 0.982608E+09 | 0.260659E+10 | 0.184614E+10 |
April | 0.279530E+10 | 0.166603E+10 | 0.112926E+10 | 0.464577E+10 | 0.101730E+10 |
May | 0.299350E+10 | 0.177452E+10 | 0.121898E+10 | 0.535467E+10 | 0.753361E+09 |
June | 0.301954E+10 | 0.187630E+10 | 0.114324E+10 | 0.631694E+10 | 0.307622E+09 |
July | 0.263520E+10 | 0.148588E+10 | 0.114932E+10 | 0.557228E+10 | 0.244628E+09 |
August | 0.250104E+10 | 0.142734E+10 | 0.107370E+10 | 0.525334E+10 | 0.306792E+09 |
September | 0.198607E+10 | 0.957320E+09 | 0.102875E+10 | 0.399060E+10 | 0.432400E+09 |
October | 0.206138E+10 | 0.125454E+10 | 0.806840E+09 | 0.324920E+10 | 0.133570E+10 |
November | 0.153396E+10 | 0.920855E+09 | 0.613102E+09 | 0.193644E+10 | 0.186958E+10 |
December | 0.144519E+10 | 0.872646E+09 | 0.572541E+09 | 0.163274E+10 | 0.248340E+10 |
Annual Sum or Average | 0.260956E+11 | 0.151409E+11 | 0.109547E+11 | 0.442827E+11 | 0.145155E+11 |
Minimum of Months | 0.144519E+10 | 0.835450E+09 | 0.572541E+09 | 0.162938E+10 | 0.244628E+09 |
Maximum of Months | 0.301954E+10 | 0.187630E+10 | 0.121898E+10 | 0.631694E+10 | 0.248340E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.627172E+10 | 0.500905E+10 | 0.126267E+10 | 0.954801E+10 | 0.330072E+10 |
February | 0.358176E+10 | 0.241566E+10 | 0.116610E+10 | 0.482901E+10 | 0.285593E+10 |
March | 0.329961E+10 | 0.169947E+10 | 0.160014E+10 | 0.480914E+10 | 0.296841E+10 |
April | 0.271822E+10 | 0.109843E+10 | 0.161979E+10 | 0.519316E+10 | 0.168461E+10 |
May | 0.188221E+10 | 0.310962E+09 | 0.157124E+10 | 0.402665E+10 | 0.123588E+10 |
June | 0.155972E+10 | 0.120235E+09 | 0.143949E+10 | 0.457330E+10 | 0.499586E+09 |
July | 0.164689E+10 | 0.170384E+09 | 0.147651E+10 | 0.457845E+10 | 0.387113E+09 |
August | 0.200254E+10 | 0.553403E+09 | 0.144914E+10 | 0.526225E+10 | 0.481733E+09 |
September | 0.279239E+10 | 0.119130E+10 | 0.160109E+10 | 0.605668E+10 | 0.696699E+09 |
October | 0.459769E+10 | 0.318229E+10 | 0.141540E+10 | 0.774701E+10 | 0.212169E+10 |
November | 0.518521E+10 | 0.397160E+10 | 0.121361E+10 | 0.776648E+10 | 0.293471E+10 |
December | 0.583083E+10 | 0.461589E+10 | 0.121494E+10 | 0.844234E+10 | 0.389633E+10 |
Annual Sum or Average | 0.413688E+11 | 0.243387E+11 | 0.170301E+11 | 0.728325E+11 | 0.230634E+11 |
Minimum of Months | 0.155972E+10 | 0.120235E+09 | 0.116610E+10 | 0.402665E+10 | 0.387113E+09 |
Maximum of Months | 0.627172E+10 | 0.500905E+10 | 0.161979E+10 | 0.954801E+10 | 0.389633E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171534E+10 | 0.106611E+10 | 0.649229E+09 | 0.251223E+10 | 0.226127E+10 |
February | 0.125512E+10 | 0.606772E+09 | 0.648344E+09 | 0.145024E+10 | 0.195099E+10 |
March | 0.184056E+10 | 0.877424E+09 | 0.963135E+09 | 0.248076E+10 | 0.195830E+10 |
April | 0.273507E+10 | 0.156017E+10 | 0.117490E+10 | 0.471270E+10 | 0.114447E+10 |
May | 0.283349E+10 | 0.158874E+10 | 0.124475E+10 | 0.523855E+10 | 0.864704E+09 |
June | 0.291511E+10 | 0.171456E+10 | 0.120056E+10 | 0.621390E+10 | 0.369547E+09 |
July | 0.219241E+10 | 0.102341E+10 | 0.116900E+10 | 0.484650E+10 | 0.281142E+09 |
August | 0.209066E+10 | 0.104997E+10 | 0.104069E+10 | 0.459924E+10 | 0.342706E+09 |
September | 0.176357E+10 | 0.740980E+09 | 0.102259E+10 | 0.366730E+10 | 0.474274E+09 |
October | 0.186465E+10 | 0.106620E+10 | 0.798446E+09 | 0.308472E+10 | 0.145157E+10 |
November | 0.166199E+10 | 0.100346E+10 | 0.658528E+09 | 0.235104E+10 | 0.201545E+10 |
December | 0.138414E+10 | 0.788088E+09 | 0.596054E+09 | 0.180703E+10 | 0.269451E+10 |
Annual Sum or Average | 0.242521E+11 | 0.130859E+11 | 0.111662E+11 | 0.429642E+11 | 0.158089E+11 |
Minimum of Months | 0.125512E+10 | 0.606772E+09 | 0.596054E+09 | 0.145024E+10 | 0.281142E+09 |
Maximum of Months | 0.291511E+10 | 0.171456E+10 | 0.124475E+10 | 0.621390E+10 | 0.269451E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253881E+09 | 0.00 | 0.253881E+09 | 0.198364E+09 | 0.118149E+10 |
February | 0.261295E+09 | 0.00 | 0.261295E+09 | 0.125678E+09 | 0.103408E+10 |
March | 0.384467E+09 | 0.00 | 0.384467E+09 | 0.373564E+09 | 0.996673E+09 |
April | 0.453306E+09 | 4704152.51 | 0.448602E+09 | 0.787051E+09 | 0.532901E+09 |
May | 0.548331E+09 | 43905273.21 | 0.504426E+09 | 0.111672E+10 | 0.366425E+09 |
June | 0.616640E+09 | 0.112037E+09 | 0.504603E+09 | 0.170180E+10 | 0.151381E+09 |
July | 0.543407E+09 | 56612211.67 | 0.486794E+09 | 0.149053E+10 | 0.127258E+09 |
August | 0.438627E+09 | 10896523.63 | 0.427731E+09 | 0.123267E+10 | 0.167175E+09 |
September | 0.400489E+09 | 106911.02 | 0.400382E+09 | 0.976420E+09 | 0.250607E+09 |
October | 0.320177E+09 | 0.00 | 0.320177E+09 | 0.463613E+09 | 0.799692E+09 |
November | 0.258161E+09 | 0.00 | 0.258161E+09 | 0.174047E+09 | 0.112673E+10 |
December | 0.237148E+09 | 0.00 | 0.237148E+09 | 0.104668E+09 | 0.149145E+10 |
Annual Sum or Average | 0.471593E+10 | 0.228262E+09 | 0.448767E+10 | 0.874513E+10 | 0.822586E+10 |
Minimum of Months | 0.237148E+09 | 0.00 | 0.237148E+09 | 0.104668E+09 | 0.127258E+09 |
Maximum of Months | 0.616640E+09 | 0.112037E+09 | 0.504603E+09 | 0.170180E+10 | 0.149145E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253892E+09 | 0.00 | 0.253892E+09 | 0.198374E+09 | 0.118155E+10 |
February | 0.261306E+09 | 0.00 | 0.261306E+09 | 0.125681E+09 | 0.103414E+10 |
March | 0.384483E+09 | 0.00 | 0.384483E+09 | 0.373579E+09 | 0.996731E+09 |
April | 0.453327E+09 | 4704278.96 | 0.448622E+09 | 0.787095E+09 | 0.532928E+09 |
May | 0.548355E+09 | 43906453.40 | 0.504448E+09 | 0.111678E+10 | 0.366441E+09 |
June | 0.616666E+09 | 0.112040E+09 | 0.504626E+09 | 0.170189E+10 | 0.151386E+09 |
July | 0.543429E+09 | 56613733.42 | 0.486816E+09 | 0.149061E+10 | 0.127263E+09 |
August | 0.438646E+09 | 10896816.53 | 0.427750E+09 | 0.123274E+10 | 0.167182E+09 |
September | 0.400505E+09 | 106913.90 | 0.400398E+09 | 0.976473E+09 | 0.250618E+09 |
October | 0.320191E+09 | 0.00 | 0.320191E+09 | 0.463639E+09 | 0.799735E+09 |
November | 0.258172E+09 | 0.00 | 0.258172E+09 | 0.174055E+09 | 0.112680E+10 |
December | 0.237158E+09 | 0.00 | 0.237158E+09 | 0.104672E+09 | 0.149154E+10 |
Annual Sum or Average | 0.471613E+10 | 0.228268E+09 | 0.448786E+10 | 0.874559E+10 | 0.822631E+10 |
Minimum of Months | 0.237158E+09 | 0.00 | 0.237158E+09 | 0.104672E+09 | 0.127263E+09 |
Maximum of Months | 0.616666E+09 | 0.112040E+09 | 0.504626E+09 | 0.170189E+10 | 0.149154E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253892E+09 | 0.00 | 0.253892E+09 | 0.198374E+09 | 0.118155E+10 |
February | 0.261306E+09 | 0.00 | 0.261306E+09 | 0.125681E+09 | 0.103414E+10 |
March | 0.384483E+09 | 0.00 | 0.384483E+09 | 0.373579E+09 | 0.996731E+09 |
April | 0.453327E+09 | 4704278.96 | 0.448622E+09 | 0.787095E+09 | 0.532928E+09 |
May | 0.548355E+09 | 43906453.40 | 0.504448E+09 | 0.111678E+10 | 0.366441E+09 |
June | 0.616666E+09 | 0.112040E+09 | 0.504626E+09 | 0.170189E+10 | 0.151386E+09 |
July | 0.543429E+09 | 56613733.42 | 0.486816E+09 | 0.149061E+10 | 0.127263E+09 |
August | 0.438646E+09 | 10896816.53 | 0.427750E+09 | 0.123274E+10 | 0.167182E+09 |
September | 0.400505E+09 | 106913.90 | 0.400398E+09 | 0.976473E+09 | 0.250618E+09 |
October | 0.320191E+09 | 0.00 | 0.320191E+09 | 0.463639E+09 | 0.799735E+09 |
November | 0.258172E+09 | 0.00 | 0.258172E+09 | 0.174055E+09 | 0.112680E+10 |
December | 0.237158E+09 | 0.00 | 0.237158E+09 | 0.104672E+09 | 0.149154E+10 |
Annual Sum or Average | 0.471613E+10 | 0.228268E+09 | 0.448786E+10 | 0.874559E+10 | 0.822631E+10 |
Minimum of Months | 0.237158E+09 | 0.00 | 0.237158E+09 | 0.104672E+09 | 0.127263E+09 |
Maximum of Months | 0.616666E+09 | 0.112040E+09 | 0.504626E+09 | 0.170189E+10 | 0.149154E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.157799E+10 | 0.989912E+09 | 0.588076E+09 | 0.198865E+10 | 0.216432E+10 |
February | 0.140489E+10 | 0.803658E+09 | 0.601231E+09 | 0.157470E+10 | 0.191324E+10 |
March | 0.194653E+10 | 0.100131E+10 | 0.945223E+09 | 0.254061E+10 | 0.184446E+10 |
April | 0.268893E+10 | 0.160263E+10 | 0.108630E+10 | 0.451668E+10 | 0.101532E+10 |
May | 0.287959E+10 | 0.170699E+10 | 0.117260E+10 | 0.520773E+10 | 0.740458E+09 |
June | 0.290465E+10 | 0.180490E+10 | 0.109975E+10 | 0.612278E+10 | 0.302611E+09 |
July | 0.253493E+10 | 0.142934E+10 | 0.110559E+10 | 0.538293E+10 | 0.253770E+09 |
August | 0.240587E+10 | 0.137302E+10 | 0.103285E+10 | 0.506203E+10 | 0.335382E+09 |
September | 0.191050E+10 | 0.920890E+09 | 0.989608E+09 | 0.382945E+10 | 0.474385E+09 |
October | 0.198295E+10 | 0.120680E+10 | 0.776144E+09 | 0.309681E+10 | 0.146063E+10 |
November | 0.147559E+10 | 0.885812E+09 | 0.589777E+09 | 0.180736E+10 | 0.205706E+10 |
December | 0.139020E+10 | 0.839438E+09 | 0.550758E+09 | 0.149510E+10 | 0.269068E+10 |
Annual Sum or Average | 0.251026E+11 | 0.145647E+11 | 0.105379E+11 | 0.426248E+11 | 0.152523E+11 |
Minimum of Months | 0.139020E+10 | 0.803658E+09 | 0.550758E+09 | 0.149510E+10 | 0.253770E+09 |
Maximum of Months | 0.290465E+10 | 0.180490E+10 | 0.117260E+10 | 0.612278E+10 | 0.269068E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62392202.53 | 39140221.62 | 23251980.91 | 78629380.62 | 85575212.79 |
February | 55548056.57 | 31775917.81 | 23772138.76 | 62262143.52 | 75647651.92 |
March | 76963998.23 | 39590713.41 | 37373284.82 | 0.100454E+09 | 72928476.64 |
April | 0.106318E+09 | 63366664.28 | 42951347.18 | 0.178586E+09 | 40144748.66 |
May | 0.113857E+09 | 67492884.70 | 46363669.73 | 0.205909E+09 | 29277027.78 |
June | 0.114847E+09 | 71364156.88 | 43483059.21 | 0.242089E+09 | 11964976.16 |
July | 0.100229E+09 | 56514785.80 | 43714144.83 | 0.212836E+09 | 10033852.81 |
August | 95125942.06 | 54288084.66 | 40837857.40 | 0.200148E+09 | 13260704.51 |
September | 75539357.12 | 36411166.26 | 39128190.86 | 0.151413E+09 | 18756770.95 |
October | 78403961.98 | 47715931.65 | 30688030.33 | 0.122445E+09 | 57752143.47 |
November | 58343458.76 | 35024224.80 | 23319233.96 | 71461315.66 | 81334342.45 |
December | 54967120.76 | 33190635.74 | 21776485.02 | 59114714.88 | 0.106387E+09 |
Annual Sum or Average | 0.992535E+09 | 0.575875E+09 | 0.416659E+09 | 0.168535E+10 | 0.603063E+09 |
Minimum of Months | 54967120.76 | 31775917.81 | 21776485.02 | 59114714.88 | 10033852.81 |
Maximum of Months | 0.114847E+09 | 71364156.88 | 46363669.73 | 0.242089E+09 | 0.106387E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209053E+10 | 0.166965E+10 | 0.420887E+09 | 0.318352E+10 | 0.124015E+10 |
February | 0.119390E+10 | 0.805205E+09 | 0.388695E+09 | 0.163257E+10 | 0.102545E+10 |
March | 0.109985E+10 | 0.566478E+09 | 0.533373E+09 | 0.163543E+10 | 0.102471E+10 |
April | 0.906063E+09 | 0.366135E+09 | 0.539929E+09 | 0.175536E+10 | 0.575750E+09 |
May | 0.627399E+09 | 0.103652E+09 | 0.523747E+09 | 0.136465E+10 | 0.406906E+09 |
June | 0.519907E+09 | 40077367.12 | 0.479829E+09 | 0.153040E+10 | 0.161648E+09 |
July | 0.548960E+09 | 56793669.63 | 0.492167E+09 | 0.152435E+10 | 0.133637E+09 |
August | 0.667507E+09 | 0.184464E+09 | 0.483043E+09 | 0.174095E+10 | 0.179951E+09 |
September | 0.930783E+09 | 0.397093E+09 | 0.533691E+09 | 0.200313E+10 | 0.269686E+09 |
October | 0.153254E+10 | 0.106074E+10 | 0.471797E+09 | 0.257364E+10 | 0.810518E+09 |
November | 0.172837E+10 | 0.132384E+10 | 0.404531E+09 | 0.257906E+10 | 0.112914E+10 |
December | 0.194357E+10 | 0.153860E+10 | 0.404977E+09 | 0.280277E+10 | 0.147874E+10 |
Annual Sum or Average | 0.137894E+11 | 0.811272E+10 | 0.567666E+10 | 0.243258E+11 | 0.843629E+10 |
Minimum of Months | 0.519907E+09 | 40077367.12 | 0.388695E+09 | 0.136465E+10 | 0.133637E+09 |
Maximum of Months | 0.209053E+10 | 0.166965E+10 | 0.539929E+09 | 0.318352E+10 | 0.147874E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209053E+10 | 0.166965E+10 | 0.420887E+09 | 0.318352E+10 | 0.124015E+10 |
February | 0.119390E+10 | 0.805205E+09 | 0.388695E+09 | 0.163257E+10 | 0.102545E+10 |
March | 0.109985E+10 | 0.566478E+09 | 0.533373E+09 | 0.163543E+10 | 0.102471E+10 |
April | 0.906063E+09 | 0.366135E+09 | 0.539929E+09 | 0.175536E+10 | 0.575750E+09 |
May | 0.627399E+09 | 0.103652E+09 | 0.523747E+09 | 0.136465E+10 | 0.406906E+09 |
June | 0.519907E+09 | 40077367.12 | 0.479829E+09 | 0.153040E+10 | 0.161648E+09 |
July | 0.548960E+09 | 56793669.63 | 0.492167E+09 | 0.152435E+10 | 0.133637E+09 |
August | 0.667507E+09 | 0.184464E+09 | 0.483043E+09 | 0.174095E+10 | 0.179951E+09 |
September | 0.930783E+09 | 0.397093E+09 | 0.533691E+09 | 0.200313E+10 | 0.269686E+09 |
October | 0.153254E+10 | 0.106074E+10 | 0.471797E+09 | 0.257364E+10 | 0.810518E+09 |
November | 0.172837E+10 | 0.132384E+10 | 0.404531E+09 | 0.257906E+10 | 0.112914E+10 |
December | 0.194357E+10 | 0.153860E+10 | 0.404977E+09 | 0.280277E+10 | 0.147874E+10 |
Annual Sum or Average | 0.137894E+11 | 0.811272E+10 | 0.567666E+10 | 0.243258E+11 | 0.843629E+10 |
Minimum of Months | 0.519907E+09 | 40077367.12 | 0.388695E+09 | 0.136465E+10 | 0.133637E+09 |
Maximum of Months | 0.209053E+10 | 0.166965E+10 | 0.539929E+09 | 0.318352E+10 | 0.147874E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209040E+10 | 0.166954E+10 | 0.420860E+09 | 0.318332E+10 | 0.124007E+10 |
February | 0.119382E+10 | 0.805154E+09 | 0.388670E+09 | 0.163247E+10 | 0.102538E+10 |
March | 0.109978E+10 | 0.566442E+09 | 0.533340E+09 | 0.163532E+10 | 0.102465E+10 |
April | 0.906006E+09 | 0.366111E+09 | 0.539894E+09 | 0.175525E+10 | 0.575713E+09 |
May | 0.627359E+09 | 0.103645E+09 | 0.523714E+09 | 0.136456E+10 | 0.406880E+09 |
June | 0.519874E+09 | 40074834.45 | 0.479799E+09 | 0.153030E+10 | 0.161637E+09 |
July | 0.548926E+09 | 56790080.59 | 0.492136E+09 | 0.152425E+10 | 0.133628E+09 |
August | 0.667464E+09 | 0.184452E+09 | 0.483012E+09 | 0.174084E+10 | 0.179940E+09 |
September | 0.930725E+09 | 0.397068E+09 | 0.533657E+09 | 0.200300E+10 | 0.269669E+09 |
October | 0.153244E+10 | 0.106067E+10 | 0.471767E+09 | 0.257347E+10 | 0.810467E+09 |
November | 0.172826E+10 | 0.132376E+10 | 0.404505E+09 | 0.257889E+10 | 0.112907E+10 |
December | 0.194345E+10 | 0.153850E+10 | 0.404951E+09 | 0.280259E+10 | 0.147865E+10 |
Annual Sum or Average | 0.137885E+11 | 0.811221E+10 | 0.567630E+10 | 0.243243E+11 | 0.843576E+10 |
Minimum of Months | 0.519874E+09 | 40074834.45 | 0.388670E+09 | 0.136456E+10 | 0.133628E+09 |
Maximum of Months | 0.209040E+10 | 0.166954E+10 | 0.539894E+09 | 0.318332E+10 | 0.147865E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.165007E+10 | 0.102554E+10 | 0.624530E+09 | 0.240772E+10 | 0.238558E+10 |
February | 0.120736E+10 | 0.583684E+09 | 0.623678E+09 | 0.141328E+10 | 0.200750E+10 |
March | 0.177053E+10 | 0.844037E+09 | 0.926493E+09 | 0.242835E+10 | 0.196058E+10 |
April | 0.263101E+10 | 0.150080E+10 | 0.113020E+10 | 0.457949E+10 | 0.115417E+10 |
May | 0.272568E+10 | 0.152829E+10 | 0.119740E+10 | 0.509001E+10 | 0.861272E+09 |
June | 0.280420E+10 | 0.164932E+10 | 0.115488E+10 | 0.601916E+10 | 0.369721E+09 |
July | 0.210900E+10 | 0.984467E+09 | 0.112453E+10 | 0.467810E+10 | 0.289901E+09 |
August | 0.201112E+10 | 0.101002E+10 | 0.100110E+10 | 0.442379E+10 | 0.369621E+09 |
September | 0.169647E+10 | 0.712785E+09 | 0.983684E+09 | 0.351510E+10 | 0.519158E+09 |
October | 0.179370E+10 | 0.102563E+10 | 0.768071E+09 | 0.294066E+10 | 0.159537E+10 |
November | 0.159875E+10 | 0.965277E+09 | 0.633475E+09 | 0.222589E+10 | 0.223522E+10 |
December | 0.133148E+10 | 0.758101E+09 | 0.573378E+09 | 0.170118E+10 | 0.291338E+10 |
Annual Sum or Average | 0.233294E+11 | 0.125880E+11 | 0.107414E+11 | 0.414227E+11 | 0.166615E+11 |
Minimum of Months | 0.120736E+10 | 0.583684E+09 | 0.573378E+09 | 0.141328E+10 | 0.289901E+09 |
Maximum of Months | 0.280420E+10 | 0.164932E+10 | 0.119740E+10 | 0.601916E+10 | 0.291338E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 65242295.63 | 40548984.50 | 24693311.13 | 95198895.12 | 94323515.58 |
February | 47737872.79 | 23078251.15 | 24659621.64 | 55879490.87 | 79374772.19 |
March | 70004991.62 | 33372360.83 | 36632630.79 | 96014508.19 | 77519344.56 |
April | 0.104027E+09 | 59340110.61 | 44687199.50 | 0.181068E+09 | 45634954.26 |
May | 0.107771E+09 | 60426971.70 | 47343870.95 | 0.201254E+09 | 34053876.54 |
June | 0.110875E+09 | 65212250.69 | 45663009.11 | 0.237992E+09 | 14618421.61 |
July | 83387558.49 | 38924817.88 | 44462740.62 | 0.184968E+09 | 11462402.92 |
August | 79517495.35 | 39935124.05 | 39582371.30 | 0.174912E+09 | 14614453.61 |
September | 67076679.30 | 28182779.44 | 38893899.86 | 0.138983E+09 | 20526993.00 |
October | 70921161.17 | 40552403.64 | 30368757.53 | 0.116271E+09 | 63079322.13 |
November | 63213042.30 | 38166061.94 | 25046980.36 | 88009560.82 | 88378444.40 |
December | 52645328.69 | 29974517.73 | 22670810.96 | 67263018.28 | 0.115193E+09 |
Annual Sum or Average | 0.922420E+09 | 0.497715E+09 | 0.424705E+09 | 0.163781E+10 | 0.658779E+09 |
Minimum of Months | 47737872.79 | 23078251.15 | 22670810.96 | 55879490.87 | 11462402.92 |
Maximum of Months | 0.110875E+09 | 65212250.69 | 47343870.95 | 0.237992E+09 | 0.115193E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.761678E+09 | 0.00 | 0.761678E+09 | 0.562038E+09 | 0.359353E+10 |
February | 0.783922E+09 | 0.00 | 0.783922E+09 | 0.330386E+09 | 0.321708E+10 |
March | 0.115346E+10 | 0.00 | 0.115346E+10 | 0.102076E+10 | 0.315496E+10 |
April | 0.135998E+10 | 14113125.25 | 0.134587E+10 | 0.229760E+10 | 0.167917E+10 |
May | 0.164507E+10 | 0.131722E+09 | 0.151335E+10 | 0.328137E+10 | 0.116712E+10 |
June | 0.185001E+10 | 0.336128E+09 | 0.151388E+10 | 0.506982E+10 | 0.486757E+09 |
July | 0.163030E+10 | 0.169845E+09 | 0.146045E+10 | 0.447463E+10 | 0.386785E+09 |
August | 0.131594E+10 | 32691117.58 | 0.128325E+10 | 0.372142E+10 | 0.491073E+09 |
September | 0.120152E+10 | 320748.24 | 0.120120E+10 | 0.296754E+10 | 0.715852E+09 |
October | 0.960577E+09 | 0.00 | 0.960577E+09 | 0.141835E+10 | 0.230371E+10 |
November | 0.774520E+09 | 0.00 | 0.774520E+09 | 0.538912E+09 | 0.325078E+10 |
December | 0.711477E+09 | 0.00 | 0.711477E+09 | 0.325322E+09 | 0.437081E+10 |
Annual Sum or Average | 0.141485E+11 | 0.684819E+09 | 0.134636E+11 | 0.260081E+11 | 0.248176E+11 |
Minimum of Months | 0.711477E+09 | 0.00 | 0.711477E+09 | 0.325322E+09 | 0.386785E+09 |
Maximum of Months | 0.185001E+10 | 0.336128E+09 | 0.151388E+10 | 0.506982E+10 | 0.437081E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.164041E+10 | 0.102907E+10 | 0.611334E+09 | 0.204795E+10 | 0.220445E+10 |
February | 0.146046E+10 | 0.835450E+09 | 0.625010E+09 | 0.159809E+10 | 0.199490E+10 |
March | 0.202352E+10 | 0.104092E+10 | 0.982608E+09 | 0.257577E+10 | 0.194793E+10 |
April | 0.279530E+10 | 0.166603E+10 | 0.112926E+10 | 0.465440E+10 | 0.105204E+10 |
May | 0.299350E+10 | 0.177452E+10 | 0.121898E+10 | 0.537308E+10 | 0.774035E+09 |
June | 0.301954E+10 | 0.187630E+10 | 0.114324E+10 | 0.634691E+10 | 0.313031E+09 |
July | 0.263520E+10 | 0.148588E+10 | 0.114932E+10 | 0.560517E+10 | 0.247228E+09 |
August | 0.250104E+10 | 0.142734E+10 | 0.107370E+10 | 0.527895E+10 | 0.315745E+09 |
September | 0.198607E+10 | 0.957320E+09 | 0.102875E+10 | 0.400542E+10 | 0.447652E+09 |
October | 0.206138E+10 | 0.125454E+10 | 0.806840E+09 | 0.323530E+10 | 0.141544E+10 |
November | 0.153396E+10 | 0.920855E+09 | 0.613102E+09 | 0.189441E+10 | 0.200996E+10 |
December | 0.144519E+10 | 0.872646E+09 | 0.572541E+09 | 0.156986E+10 | 0.266864E+10 |
Annual Sum or Average | 0.260956E+11 | 0.151409E+11 | 0.109547E+11 | 0.441853E+11 | 0.153911E+11 |
Minimum of Months | 0.144519E+10 | 0.835450E+09 | 0.572541E+09 | 0.156986E+10 | 0.247228E+09 |
Maximum of Months | 0.301954E+10 | 0.187630E+10 | 0.121898E+10 | 0.634691E+10 | 0.266864E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.627172E+10 | 0.500905E+10 | 0.126267E+10 | 0.949986E+10 | 0.351714E+10 |
February | 0.358176E+10 | 0.241566E+10 | 0.116610E+10 | 0.478786E+10 | 0.307566E+10 |
March | 0.329961E+10 | 0.169947E+10 | 0.160014E+10 | 0.477246E+10 | 0.314494E+10 |
April | 0.271822E+10 | 0.109843E+10 | 0.161979E+10 | 0.520469E+10 | 0.176090E+10 |
May | 0.188221E+10 | 0.310962E+09 | 0.157124E+10 | 0.404177E+10 | 0.128402E+10 |
June | 0.155972E+10 | 0.120235E+09 | 0.143949E+10 | 0.460179E+10 | 0.513757E+09 |
July | 0.164689E+10 | 0.170384E+09 | 0.147651E+10 | 0.461395E+10 | 0.395065E+09 |
August | 0.200254E+10 | 0.553403E+09 | 0.144914E+10 | 0.529030E+10 | 0.499516E+09 |
September | 0.279239E+10 | 0.119130E+10 | 0.160109E+10 | 0.607792E+10 | 0.725088E+09 |
October | 0.459769E+10 | 0.318229E+10 | 0.141540E+10 | 0.773409E+10 | 0.225090E+10 |
November | 0.518521E+10 | 0.397160E+10 | 0.121361E+10 | 0.771874E+10 | 0.314436E+10 |
December | 0.583083E+10 | 0.461589E+10 | 0.121494E+10 | 0.837031E+10 | 0.417419E+10 |
Annual Sum or Average | 0.413688E+11 | 0.243387E+11 | 0.170301E+11 | 0.727137E+11 | 0.244855E+11 |
Minimum of Months | 0.155972E+10 | 0.120235E+09 | 0.116610E+10 | 0.404177E+10 | 0.395065E+09 |
Maximum of Months | 0.627172E+10 | 0.500905E+10 | 0.161979E+10 | 0.949986E+10 | 0.417419E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171534E+10 | 0.106611E+10 | 0.649229E+09 | 0.248463E+10 | 0.242913E+10 |
February | 0.125512E+10 | 0.606772E+09 | 0.648344E+09 | 0.143135E+10 | 0.210880E+10 |
March | 0.184056E+10 | 0.877424E+09 | 0.963135E+09 | 0.245712E+10 | 0.208206E+10 |
April | 0.273507E+10 | 0.156017E+10 | 0.117490E+10 | 0.471990E+10 | 0.119467E+10 |
May | 0.283349E+10 | 0.158874E+10 | 0.124475E+10 | 0.525336E+10 | 0.895956E+09 |
June | 0.291511E+10 | 0.171456E+10 | 0.120056E+10 | 0.624042E+10 | 0.379209E+09 |
July | 0.219241E+10 | 0.102341E+10 | 0.116900E+10 | 0.487301E+10 | 0.286069E+09 |
August | 0.209066E+10 | 0.104997E+10 | 0.104069E+10 | 0.461834E+10 | 0.354274E+09 |
September | 0.176357E+10 | 0.740980E+09 | 0.102259E+10 | 0.367809E+10 | 0.493485E+09 |
October | 0.186465E+10 | 0.106620E+10 | 0.798446E+09 | 0.307352E+10 | 0.155046E+10 |
November | 0.166199E+10 | 0.100346E+10 | 0.658528E+09 | 0.232471E+10 | 0.217844E+10 |
December | 0.138414E+10 | 0.788088E+09 | 0.596054E+09 | 0.177334E+10 | 0.290277E+10 |
Annual Sum or Average | 0.242521E+11 | 0.130859E+11 | 0.111662E+11 | 0.429278E+11 | 0.168553E+11 |
Minimum of Months | 0.125512E+10 | 0.606772E+09 | 0.596054E+09 | 0.143135E+10 | 0.286069E+09 |
Maximum of Months | 0.291511E+10 | 0.171456E+10 | 0.124475E+10 | 0.624042E+10 | 0.290277E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 230.88 | 1238.97 | 284.38 | 0.00 | 284.38 | 0.00 | 0.00 |
February | 151.02 | 1221.37 | 324.04 | 0.00 | 324.04 | 0.00 | 0.00 |
March | 397.74 | 1103.15 | 430.65 | 0.00 | 430.65 | 0.00 | 0.00 |
April | 886.02 | 618.37 | 524.68 | 5.44 | 519.24 | 0.00 | 0.00 |
May | 1222.79 | 422.75 | 614.20 | 49.18 | 565.02 | 0.00 | 0.00 |
June | 1945.22 | 184.68 | 713.74 | 129.68 | 584.06 | 0.00 | 0.00 |
July | 1657.92 | 142.76 | 608.68 | 63.41 | 545.27 | 0.00 | 0.00 |
August | 1381.06 | 178.17 | 491.32 | 12.21 | 479.11 | 0.00 | 0.00 |
September | 1140.46 | 265.55 | 463.55 | 0.12 | 463.43 | 0.00 | 0.00 |
October | 539.24 | 800.57 | 358.64 | 0.00 | 358.64 | 0.00 | 0.00 |
November | 226.94 | 1151.08 | 298.81 | 0.00 | 298.81 | 0.00 | 0.00 |
December | 142.66 | 1503.70 | 265.64 | 0.00 | 265.64 | 0.00 | 0.00 |
Annual Sum or Average | 829.94 | 733.92 | 448.64 | 21.72 | 426.93 | 0.00 | 0.00 |
Minimum of Months | 142.66 | 142.76 | 265.64 | 0.00 | 265.64 | 0.00 | 0.00 |
Maximum of Months | 1945.22 | 1503.70 | 713.74 | 129.68 | 584.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 782.11 | 769.98 | 612.46 | 384.21 | 228.25 | 0.00 | 0.00 |
February | 673.52 | 767.29 | 603.70 | 345.34 | 258.35 | 0.00 | 0.00 |
March | 973.19 | 689.27 | 755.50 | 388.63 | 366.86 | 0.00 | 0.00 |
April | 1792.35 | 392.48 | 1078.43 | 642.76 | 435.67 | 0.00 | 0.00 |
May | 1999.20 | 281.27 | 1117.64 | 662.53 | 455.11 | 0.00 | 0.00 |
June | 2437.09 | 118.68 | 1164.95 | 723.88 | 441.07 | 0.00 | 0.00 |
July | 2080.45 | 91.33 | 983.87 | 554.77 | 429.11 | 0.00 | 0.00 |
August | 1961.37 | 114.54 | 933.78 | 532.91 | 400.87 | 0.00 | 0.00 |
September | 1539.58 | 166.82 | 766.23 | 369.34 | 396.89 | 0.00 | 0.00 |
October | 1213.11 | 498.69 | 769.63 | 468.39 | 301.24 | 0.00 | 0.00 |
November | 747.08 | 721.29 | 591.80 | 355.27 | 236.54 | 0.00 | 0.00 |
December | 609.59 | 927.19 | 539.57 | 325.81 | 213.76 | 0.00 | 0.00 |
Annual Sum or Average | 1404.20 | 460.28 | 827.48 | 480.11 | 347.37 | 0.00 | 0.00 |
Minimum of Months | 609.59 | 91.33 | 539.57 | 325.81 | 213.76 | 0.00 | 0.00 |
Maximum of Months | 2437.09 | 927.19 | 1164.95 | 723.88 | 455.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3564.82 | 1232.35 | 2341.59 | 1870.16 | 471.43 | 0.00 | 0.00 |
February | 1996.12 | 1180.53 | 1480.56 | 998.54 | 482.02 | 0.00 | 0.00 |
March | 1795.53 | 1108.28 | 1231.93 | 634.51 | 597.42 | 0.00 | 0.00 |
April | 2003.53 | 649.93 | 1048.70 | 423.78 | 624.92 | 0.00 | 0.00 |
May | 1503.38 | 461.42 | 702.74 | 116.10 | 586.64 | 0.00 | 0.00 |
June | 1764.39 | 192.74 | 601.75 | 46.39 | 555.36 | 0.00 | 0.00 |
July | 1709.40 | 144.53 | 614.88 | 63.61 | 551.26 | 0.00 | 0.00 |
August | 1964.70 | 179.86 | 747.66 | 206.62 | 541.05 | 0.00 | 0.00 |
September | 2336.68 | 268.79 | 1077.31 | 459.61 | 617.70 | 0.00 | 0.00 |
October | 2892.40 | 792.15 | 1716.58 | 1188.13 | 528.45 | 0.00 | 0.00 |
November | 2996.33 | 1132.22 | 2000.47 | 1532.25 | 468.21 | 0.00 | 0.00 |
December | 3152.01 | 1454.72 | 2176.98 | 1723.38 | 453.61 | 0.00 | 0.00 |
Annual Sum or Average | 2309.50 | 731.34 | 1311.80 | 771.77 | 540.02 | 0.00 | 0.00 |
Minimum of Months | 1503.38 | 144.53 | 601.75 | 46.39 | 453.61 | 0.00 | 0.00 |
Maximum of Months | 3564.82 | 1454.72 | 2341.59 | 1870.16 | 624.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 937.96 | 844.26 | 640.43 | 398.04 | 242.39 | 0.00 | 0.00 |
February | 599.47 | 806.46 | 518.81 | 250.82 | 268.00 | 0.00 | 0.00 |
March | 926.21 | 731.15 | 687.19 | 327.59 | 359.59 | 0.00 | 0.00 |
April | 1818.17 | 441.54 | 1055.20 | 601.92 | 453.28 | 0.00 | 0.00 |
May | 1955.85 | 322.84 | 1057.90 | 593.17 | 464.74 | 0.00 | 0.00 |
June | 2397.34 | 142.57 | 1124.66 | 661.48 | 463.18 | 0.00 | 0.00 |
July | 1809.47 | 104.97 | 818.55 | 382.10 | 436.45 | 0.00 | 0.00 |
August | 1717.16 | 127.95 | 780.56 | 392.01 | 388.55 | 0.00 | 0.00 |
September | 1414.86 | 182.98 | 680.39 | 285.87 | 394.52 | 0.00 | 0.00 |
October | 1151.70 | 541.96 | 696.18 | 398.07 | 298.11 | 0.00 | 0.00 |
November | 907.04 | 777.57 | 641.20 | 387.14 | 254.06 | 0.00 | 0.00 |
December | 674.67 | 1006.01 | 516.78 | 294.24 | 222.54 | 0.00 | 0.00 |
Annual Sum or Average | 1362.39 | 501.30 | 769.03 | 414.95 | 354.08 | 0.00 | 0.00 |
Minimum of Months | 599.47 | 104.97 | 516.78 | 250.82 | 222.54 | 0.00 | 0.00 |
Maximum of Months | 2397.34 | 1006.01 | 1124.66 | 661.48 | 464.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 222.19 | 1323.40 | 284.37 | 0.00 | 284.37 | 0.00 | 0.00 |
February | 155.85 | 1282.39 | 324.04 | 0.00 | 324.04 | 0.00 | 0.00 |
March | 418.43 | 1116.39 | 430.64 | 0.00 | 430.64 | 0.00 | 0.00 |
April | 910.97 | 616.80 | 524.68 | 5.44 | 519.23 | 0.00 | 0.00 |
May | 1250.85 | 410.43 | 614.19 | 49.18 | 565.01 | 0.00 | 0.00 |
June | 1969.75 | 175.21 | 713.72 | 129.68 | 584.05 | 0.00 | 0.00 |
July | 1669.56 | 142.54 | 608.67 | 63.41 | 545.26 | 0.00 | 0.00 |
August | 1380.73 | 187.25 | 491.31 | 12.21 | 479.10 | 0.00 | 0.00 |
September | 1130.16 | 290.06 | 463.54 | 0.12 | 463.42 | 0.00 | 0.00 |
October | 519.30 | 895.74 | 358.63 | 0.00 | 358.63 | 0.00 | 0.00 |
November | 201.45 | 1304.14 | 298.81 | 0.00 | 298.81 | 0.00 | 0.00 |
December | 117.24 | 1670.60 | 265.63 | 0.00 | 265.63 | 0.00 | 0.00 |
Annual Sum or Average | 831.95 | 782.55 | 448.64 | 21.71 | 426.92 | 0.00 | 0.00 |
Minimum of Months | 117.24 | 142.54 | 265.63 | 0.00 | 265.63 | 0.00 | 0.00 |
Maximum of Months | 1969.75 | 1670.60 | 713.72 | 129.68 | 584.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 771.83 | 840.01 | 612.45 | 384.20 | 228.24 | 0.00 | 0.00 |
February | 676.65 | 822.12 | 603.69 | 345.33 | 258.35 | 0.00 | 0.00 |
March | 986.06 | 715.87 | 755.49 | 388.63 | 366.86 | 0.00 | 0.00 |
April | 1811.45 | 407.20 | 1078.41 | 642.75 | 435.67 | 0.00 | 0.00 |
May | 2021.22 | 287.39 | 1117.63 | 662.52 | 455.11 | 0.00 | 0.00 |
June | 2455.58 | 121.36 | 1164.93 | 723.87 | 441.06 | 0.00 | 0.00 |
July | 2089.22 | 98.49 | 983.86 | 554.75 | 429.10 | 0.00 | 0.00 |
August | 1964.67 | 130.17 | 933.76 | 532.90 | 400.87 | 0.00 | 0.00 |
September | 1535.83 | 190.26 | 766.22 | 369.33 | 396.89 | 0.00 | 0.00 |
October | 1201.93 | 566.90 | 769.62 | 468.38 | 301.24 | 0.00 | 0.00 |
November | 724.85 | 825.00 | 591.79 | 355.26 | 236.53 | 0.00 | 0.00 |
December | 580.28 | 1044.31 | 539.56 | 325.80 | 213.76 | 0.00 | 0.00 |
Annual Sum or Average | 1405.07 | 502.77 | 827.47 | 480.10 | 347.37 | 0.00 | 0.00 |
Minimum of Months | 580.28 | 98.49 | 539.56 | 325.80 | 213.76 | 0.00 | 0.00 |
Maximum of Months | 2455.58 | 1044.31 | 1164.93 | 723.87 | 455.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3565.70 | 1389.02 | 2341.50 | 1870.09 | 471.41 | 0.00 | 0.00 |
February | 2024.47 | 1271.61 | 1480.50 | 998.50 | 482.00 | 0.00 | 0.00 |
March | 1831.76 | 1147.73 | 1231.89 | 634.48 | 597.40 | 0.00 | 0.00 |
April | 2031.62 | 666.36 | 1048.66 | 423.76 | 624.90 | 0.00 | 0.00 |
May | 1528.47 | 455.75 | 702.72 | 116.10 | 586.62 | 0.00 | 0.00 |
June | 1771.26 | 187.09 | 601.73 | 46.38 | 555.35 | 0.00 | 0.00 |
July | 1707.35 | 149.68 | 614.86 | 63.61 | 551.25 | 0.00 | 0.00 |
August | 1949.95 | 201.55 | 747.64 | 206.61 | 541.03 | 0.00 | 0.00 |
September | 2318.39 | 312.13 | 1077.27 | 459.59 | 617.68 | 0.00 | 0.00 |
October | 2882.60 | 907.82 | 1716.52 | 1188.08 | 528.43 | 0.00 | 0.00 |
November | 2984.95 | 1306.85 | 2000.39 | 1532.19 | 468.20 | 0.00 | 0.00 |
December | 3139.24 | 1656.27 | 2176.90 | 1723.30 | 453.59 | 0.00 | 0.00 |
Annual Sum or Average | 2314.05 | 802.52 | 1311.75 | 771.74 | 540.01 | 0.00 | 0.00 |
Minimum of Months | 1528.47 | 149.68 | 601.73 | 46.38 | 453.59 | 0.00 | 0.00 |
Maximum of Months | 3565.70 | 1656.27 | 2341.50 | 1870.09 | 624.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 934.48 | 925.89 | 640.43 | 398.03 | 242.39 | 0.00 | 0.00 |
February | 607.29 | 862.63 | 518.81 | 250.81 | 268.00 | 0.00 | 0.00 |
March | 942.49 | 760.94 | 687.18 | 327.59 | 359.59 | 0.00 | 0.00 |
April | 1836.63 | 462.89 | 1055.18 | 601.91 | 453.28 | 0.00 | 0.00 |
May | 1975.53 | 334.28 | 1057.89 | 593.16 | 464.73 | 0.00 | 0.00 |
June | 2414.02 | 148.28 | 1124.64 | 661.47 | 463.17 | 0.00 | 0.00 |
July | 1815.66 | 112.52 | 818.54 | 382.09 | 436.45 | 0.00 | 0.00 |
August | 1716.96 | 143.46 | 780.55 | 392.01 | 388.54 | 0.00 | 0.00 |
September | 1409.75 | 208.21 | 680.38 | 285.87 | 394.51 | 0.00 | 0.00 |
October | 1141.33 | 619.19 | 696.17 | 398.07 | 298.10 | 0.00 | 0.00 |
November | 892.71 | 896.45 | 641.19 | 387.13 | 254.06 | 0.00 | 0.00 |
December | 660.26 | 1130.74 | 516.77 | 294.23 | 222.54 | 0.00 | 0.00 |
Annual Sum or Average | 1365.44 | 549.22 | 769.02 | 414.94 | 354.08 | 0.00 | 0.00 |
Minimum of Months | 607.29 | 112.52 | 516.77 | 250.81 | 222.54 | 0.00 | 0.00 |
Maximum of Months | 2414.02 | 1130.74 | 1124.64 | 661.47 | 464.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 209.84 | 1341.67 | 284.38 | 0.00 | 284.38 | 0.00 | 0.00 |
February | 136.57 | 1329.81 | 324.04 | 0.00 | 324.04 | 0.00 | 0.00 |
March | 381.11 | 1177.93 | 430.65 | 0.00 | 430.65 | 0.00 | 0.00 |
April | 886.42 | 647.83 | 524.68 | 5.44 | 519.24 | 0.00 | 0.00 |
May | 1225.12 | 435.75 | 614.20 | 49.18 | 565.02 | 0.00 | 0.00 |
June | 1955.95 | 187.79 | 713.74 | 129.68 | 584.06 | 0.00 | 0.00 |
July | 1670.63 | 144.41 | 608.68 | 63.41 | 545.27 | 0.00 | 0.00 |
August | 1389.42 | 183.35 | 491.32 | 12.21 | 479.11 | 0.00 | 0.00 |
September | 1144.88 | 276.18 | 463.55 | 0.12 | 463.43 | 0.00 | 0.00 |
October | 529.55 | 860.11 | 358.64 | 0.00 | 358.64 | 0.00 | 0.00 |
November | 207.91 | 1254.16 | 298.81 | 0.00 | 298.81 | 0.00 | 0.00 |
December | 121.46 | 1631.87 | 265.64 | 0.00 | 265.64 | 0.00 | 0.00 |
Annual Sum or Average | 824.71 | 786.96 | 448.64 | 21.72 | 426.93 | 0.00 | 0.00 |
Minimum of Months | 121.46 | 144.41 | 265.64 | 0.00 | 265.64 | 0.00 | 0.00 |
Maximum of Months | 1955.95 | 1631.87 | 713.74 | 129.68 | 584.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 764.62 | 823.05 | 612.46 | 384.21 | 228.25 | 0.00 | 0.00 |
February | 660.59 | 824.61 | 603.70 | 345.34 | 258.35 | 0.00 | 0.00 |
March | 961.68 | 727.28 | 755.50 | 388.63 | 366.86 | 0.00 | 0.00 |
April | 1795.68 | 405.88 | 1078.43 | 642.76 | 435.67 | 0.00 | 0.00 |
May | 2006.08 | 288.99 | 1117.64 | 662.53 | 455.11 | 0.00 | 0.00 |
June | 2448.65 | 120.77 | 1164.95 | 723.88 | 441.07 | 0.00 | 0.00 |
July | 2092.73 | 92.30 | 983.87 | 554.77 | 429.11 | 0.00 | 0.00 |
August | 1970.94 | 117.89 | 933.78 | 532.91 | 400.87 | 0.00 | 0.00 |
September | 1545.30 | 172.71 | 766.23 | 369.34 | 396.89 | 0.00 | 0.00 |
October | 1207.92 | 528.47 | 769.63 | 468.39 | 301.24 | 0.00 | 0.00 |
November | 730.87 | 775.45 | 591.80 | 355.27 | 236.54 | 0.00 | 0.00 |
December | 586.12 | 996.36 | 539.57 | 325.81 | 213.76 | 0.00 | 0.00 |
Annual Sum or Average | 1401.11 | 488.05 | 827.48 | 480.11 | 347.37 | 0.00 | 0.00 |
Minimum of Months | 586.12 | 92.30 | 539.57 | 325.81 | 213.76 | 0.00 | 0.00 |
Maximum of Months | 2448.65 | 996.36 | 1164.95 | 723.88 | 455.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3546.84 | 1313.15 | 2341.59 | 1870.16 | 471.43 | 0.00 | 0.00 |
February | 1979.11 | 1271.35 | 1480.56 | 998.54 | 482.02 | 0.00 | 0.00 |
March | 1781.83 | 1174.18 | 1231.93 | 634.51 | 597.42 | 0.00 | 0.00 |
April | 2007.98 | 679.36 | 1048.70 | 423.78 | 624.92 | 0.00 | 0.00 |
May | 1509.02 | 479.40 | 702.74 | 116.10 | 586.64 | 0.00 | 0.00 |
June | 1775.38 | 198.21 | 601.75 | 46.39 | 555.36 | 0.00 | 0.00 |
July | 1722.65 | 147.50 | 614.88 | 63.61 | 551.26 | 0.00 | 0.00 |
August | 1975.17 | 186.50 | 747.66 | 206.62 | 541.05 | 0.00 | 0.00 |
September | 2344.88 | 279.74 | 1077.31 | 459.61 | 617.70 | 0.00 | 0.00 |
October | 2887.58 | 840.39 | 1716.58 | 1188.13 | 528.45 | 0.00 | 0.00 |
November | 2977.91 | 1213.10 | 2000.47 | 1532.25 | 468.21 | 0.00 | 0.00 |
December | 3125.12 | 1558.47 | 2176.98 | 1723.38 | 453.61 | 0.00 | 0.00 |
Annual Sum or Average | 2305.74 | 776.43 | 1311.80 | 771.77 | 540.02 | 0.00 | 0.00 |
Minimum of Months | 1509.02 | 147.50 | 601.75 | 46.39 | 453.61 | 0.00 | 0.00 |
Maximum of Months | 3546.84 | 1558.47 | 2341.59 | 1870.16 | 624.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 927.65 | 906.93 | 640.43 | 398.04 | 242.39 | 0.00 | 0.00 |
February | 591.66 | 871.69 | 518.81 | 250.82 | 268.00 | 0.00 | 0.00 |
March | 917.38 | 777.35 | 687.19 | 327.59 | 359.59 | 0.00 | 0.00 |
April | 1820.95 | 460.91 | 1055.20 | 601.92 | 453.28 | 0.00 | 0.00 |
May | 1961.38 | 334.51 | 1057.90 | 593.17 | 464.74 | 0.00 | 0.00 |
June | 2407.57 | 146.30 | 1124.66 | 661.48 | 463.18 | 0.00 | 0.00 |
July | 1819.37 | 106.81 | 818.55 | 382.10 | 436.45 | 0.00 | 0.00 |
August | 1724.29 | 132.27 | 780.56 | 392.01 | 388.55 | 0.00 | 0.00 |
September | 1419.02 | 190.39 | 680.39 | 285.87 | 394.52 | 0.00 | 0.00 |
October | 1147.52 | 578.88 | 696.18 | 398.07 | 298.11 | 0.00 | 0.00 |
November | 896.88 | 840.45 | 641.20 | 387.14 | 254.06 | 0.00 | 0.00 |
December | 662.09 | 1083.77 | 516.78 | 294.24 | 222.54 | 0.00 | 0.00 |
Annual Sum or Average | 1361.23 | 534.48 | 769.03 | 414.95 | 354.08 | 0.00 | 0.00 |
Minimum of Months | 591.66 | 106.81 | 516.78 | 250.82 | 222.54 | 0.00 | 0.00 |
Maximum of Months | 2407.57 | 1083.77 | 1124.66 | 661.48 | 464.74 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.618388E+09 | 0.331847E+10 | 0.761678E+09 | 0.00 | 0.761678E+09 | 0.00 | 0.00 |
February | 0.365346E+09 | 0.295473E+10 | 0.783922E+09 | 0.00 | 0.783922E+09 | 0.00 | 0.00 |
March | 0.106531E+10 | 0.295467E+10 | 0.115346E+10 | 0.00 | 0.115346E+10 | 0.00 | 0.00 |
April | 0.229657E+10 | 0.160282E+10 | 0.135998E+10 | 14113125.25 | 0.134587E+10 | 0.00 | 0.00 |
May | 0.327511E+10 | 0.113229E+10 | 0.164507E+10 | 0.131722E+09 | 0.151335E+10 | 0.00 | 0.00 |
June | 0.504200E+10 | 0.478692E+09 | 0.185001E+10 | 0.336128E+09 | 0.151388E+10 | 0.00 | 0.00 |
July | 0.444056E+10 | 0.382372E+09 | 0.163030E+10 | 0.169845E+09 | 0.146045E+10 | 0.00 | 0.00 |
August | 0.369904E+10 | 0.477212E+09 | 0.131594E+10 | 32691117.58 | 0.128325E+10 | 0.00 | 0.00 |
September | 0.295607E+10 | 0.688304E+09 | 0.120152E+10 | 320748.24 | 0.120120E+10 | 0.00 | 0.00 |
October | 0.144431E+10 | 0.214426E+10 | 0.960577E+09 | 0.00 | 0.960577E+09 | 0.00 | 0.00 |
November | 0.588234E+09 | 0.298360E+10 | 0.774520E+09 | 0.00 | 0.774520E+09 | 0.00 | 0.00 |
December | 0.382088E+09 | 0.402750E+10 | 0.711477E+09 | 0.00 | 0.711477E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.261730E+11 | 0.231449E+11 | 0.141485E+11 | 0.684819E+09 | 0.134636E+11 | 0.00 | 0.00 |
Minimum of Months | 0.365346E+09 | 0.382372E+09 | 0.711477E+09 | 0.00 | 0.711477E+09 | 0.00 | 0.00 |
Maximum of Months | 0.504200E+10 | 0.402750E+10 | 0.185001E+10 | 0.336128E+09 | 0.151388E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.209480E+10 | 0.206231E+10 | 0.164041E+10 | 0.102907E+10 | 0.611334E+09 | 0.00 | 0.00 |
February | 0.162938E+10 | 0.185622E+10 | 0.146046E+10 | 0.835450E+09 | 0.625010E+09 | 0.00 | 0.00 |
March | 0.260659E+10 | 0.184614E+10 | 0.202352E+10 | 0.104092E+10 | 0.982608E+09 | 0.00 | 0.00 |
April | 0.464577E+10 | 0.101730E+10 | 0.279530E+10 | 0.166603E+10 | 0.112926E+10 | 0.00 | 0.00 |
May | 0.535467E+10 | 0.753361E+09 | 0.299350E+10 | 0.177452E+10 | 0.121898E+10 | 0.00 | 0.00 |
June | 0.631694E+10 | 0.307622E+09 | 0.301954E+10 | 0.187630E+10 | 0.114324E+10 | 0.00 | 0.00 |
July | 0.557228E+10 | 0.244628E+09 | 0.263520E+10 | 0.148588E+10 | 0.114932E+10 | 0.00 | 0.00 |
August | 0.525334E+10 | 0.306792E+09 | 0.250104E+10 | 0.142734E+10 | 0.107370E+10 | 0.00 | 0.00 |
September | 0.399060E+10 | 0.432400E+09 | 0.198607E+10 | 0.957320E+09 | 0.102875E+10 | 0.00 | 0.00 |
October | 0.324920E+10 | 0.133570E+10 | 0.206138E+10 | 0.125454E+10 | 0.806840E+09 | 0.00 | 0.00 |
November | 0.193644E+10 | 0.186958E+10 | 0.153396E+10 | 0.920855E+09 | 0.613102E+09 | 0.00 | 0.00 |
December | 0.163274E+10 | 0.248340E+10 | 0.144519E+10 | 0.872646E+09 | 0.572541E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.442827E+11 | 0.145155E+11 | 0.260956E+11 | 0.151409E+11 | 0.109547E+11 | 0.00 | 0.00 |
Minimum of Months | 0.162938E+10 | 0.244628E+09 | 0.144519E+10 | 0.835450E+09 | 0.572541E+09 | 0.00 | 0.00 |
Maximum of Months | 0.631694E+10 | 0.248340E+10 | 0.301954E+10 | 0.187630E+10 | 0.121898E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.954801E+10 | 0.330072E+10 | 0.627172E+10 | 0.500905E+10 | 0.126267E+10 | 0.00 | 0.00 |
February | 0.482901E+10 | 0.285593E+10 | 0.358176E+10 | 0.241566E+10 | 0.116610E+10 | 0.00 | 0.00 |
March | 0.480914E+10 | 0.296841E+10 | 0.329961E+10 | 0.169947E+10 | 0.160014E+10 | 0.00 | 0.00 |
April | 0.519316E+10 | 0.168461E+10 | 0.271822E+10 | 0.109843E+10 | 0.161979E+10 | 0.00 | 0.00 |
May | 0.402665E+10 | 0.123588E+10 | 0.188221E+10 | 0.310962E+09 | 0.157124E+10 | 0.00 | 0.00 |
June | 0.457330E+10 | 0.499586E+09 | 0.155972E+10 | 0.120235E+09 | 0.143949E+10 | 0.00 | 0.00 |
July | 0.457845E+10 | 0.387113E+09 | 0.164689E+10 | 0.170384E+09 | 0.147651E+10 | 0.00 | 0.00 |
August | 0.526225E+10 | 0.481733E+09 | 0.200254E+10 | 0.553403E+09 | 0.144914E+10 | 0.00 | 0.00 |
September | 0.605668E+10 | 0.696699E+09 | 0.279239E+10 | 0.119130E+10 | 0.160109E+10 | 0.00 | 0.00 |
October | 0.774701E+10 | 0.212169E+10 | 0.459769E+10 | 0.318229E+10 | 0.141540E+10 | 0.00 | 0.00 |
November | 0.776648E+10 | 0.293471E+10 | 0.518521E+10 | 0.397160E+10 | 0.121361E+10 | 0.00 | 0.00 |
December | 0.844234E+10 | 0.389633E+10 | 0.583083E+10 | 0.461589E+10 | 0.121494E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.728325E+11 | 0.230634E+11 | 0.413688E+11 | 0.243387E+11 | 0.170301E+11 | 0.00 | 0.00 |
Minimum of Months | 0.402665E+10 | 0.387113E+09 | 0.155972E+10 | 0.120235E+09 | 0.116610E+10 | 0.00 | 0.00 |
Maximum of Months | 0.954801E+10 | 0.389633E+10 | 0.627172E+10 | 0.500905E+10 | 0.161979E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.251223E+10 | 0.226127E+10 | 0.171534E+10 | 0.106611E+10 | 0.649229E+09 | 0.00 | 0.00 |
February | 0.145024E+10 | 0.195099E+10 | 0.125512E+10 | 0.606772E+09 | 0.648344E+09 | 0.00 | 0.00 |
March | 0.248076E+10 | 0.195830E+10 | 0.184056E+10 | 0.877424E+09 | 0.963135E+09 | 0.00 | 0.00 |
April | 0.471270E+10 | 0.114447E+10 | 0.273507E+10 | 0.156017E+10 | 0.117490E+10 | 0.00 | 0.00 |
May | 0.523855E+10 | 0.864704E+09 | 0.283349E+10 | 0.158874E+10 | 0.124475E+10 | 0.00 | 0.00 |
June | 0.621390E+10 | 0.369547E+09 | 0.291511E+10 | 0.171456E+10 | 0.120056E+10 | 0.00 | 0.00 |
July | 0.484650E+10 | 0.281142E+09 | 0.219241E+10 | 0.102341E+10 | 0.116900E+10 | 0.00 | 0.00 |
August | 0.459924E+10 | 0.342706E+09 | 0.209066E+10 | 0.104997E+10 | 0.104069E+10 | 0.00 | 0.00 |
September | 0.366730E+10 | 0.474274E+09 | 0.176357E+10 | 0.740980E+09 | 0.102259E+10 | 0.00 | 0.00 |
October | 0.308472E+10 | 0.145157E+10 | 0.186465E+10 | 0.106620E+10 | 0.798446E+09 | 0.00 | 0.00 |
November | 0.235104E+10 | 0.201545E+10 | 0.166199E+10 | 0.100346E+10 | 0.658528E+09 | 0.00 | 0.00 |
December | 0.180703E+10 | 0.269451E+10 | 0.138414E+10 | 0.788088E+09 | 0.596054E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.429642E+11 | 0.158089E+11 | 0.242521E+11 | 0.130859E+11 | 0.111662E+11 | 0.00 | 0.00 |
Minimum of Months | 0.145024E+10 | 0.281142E+09 | 0.125512E+10 | 0.606772E+09 | 0.596054E+09 | 0.00 | 0.00 |
Maximum of Months | 0.621390E+10 | 0.269451E+10 | 0.291511E+10 | 0.171456E+10 | 0.124475E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.595113E+09 | 0.354459E+10 | 0.761664E+09 | 0.00 | 0.761664E+09 | 0.00 | 0.00 |
February | 0.377040E+09 | 0.310236E+10 | 0.783906E+09 | 0.00 | 0.783906E+09 | 0.00 | 0.00 |
March | 0.112072E+10 | 0.299013E+10 | 0.115343E+10 | 0.00 | 0.115343E+10 | 0.00 | 0.00 |
April | 0.236124E+10 | 0.159876E+10 | 0.135996E+10 | 14112710.43 | 0.134585E+10 | 0.00 | 0.00 |
May | 0.335028E+10 | 0.109931E+10 | 0.164504E+10 | 0.131718E+09 | 0.151332E+10 | 0.00 | 0.00 |
June | 0.510559E+10 | 0.454153E+09 | 0.184997E+10 | 0.336118E+09 | 0.151386E+10 | 0.00 | 0.00 |
July | 0.447175E+10 | 0.381784E+09 | 0.163027E+10 | 0.169840E+09 | 0.146043E+10 | 0.00 | 0.00 |
August | 0.369815E+10 | 0.501540E+09 | 0.131592E+10 | 32690156.70 | 0.128323E+10 | 0.00 | 0.00 |
September | 0.292937E+10 | 0.751843E+09 | 0.120150E+10 | 320738.82 | 0.120118E+10 | 0.00 | 0.00 |
October | 0.139089E+10 | 0.239916E+10 | 0.960560E+09 | 0.00 | 0.960560E+09 | 0.00 | 0.00 |
November | 0.522157E+09 | 0.338032E+10 | 0.774506E+09 | 0.00 | 0.774506E+09 | 0.00 | 0.00 |
December | 0.314012E+09 | 0.447453E+10 | 0.711464E+09 | 0.00 | 0.711464E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.262363E+11 | 0.246785E+11 | 0.141482E+11 | 0.684799E+09 | 0.134634E+11 | 0.00 | 0.00 |
Minimum of Months | 0.314012E+09 | 0.381784E+09 | 0.711464E+09 | 0.00 | 0.711464E+09 | 0.00 | 0.00 |
Maximum of Months | 0.510559E+10 | 0.447453E+10 | 0.184997E+10 | 0.336118E+09 | 0.151386E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.206728E+10 | 0.224989E+10 | 0.164038E+10 | 0.102905E+10 | 0.611328E+09 | 0.00 | 0.00 |
February | 0.163696E+10 | 0.198888E+10 | 0.146044E+10 | 0.835434E+09 | 0.625003E+09 | 0.00 | 0.00 |
March | 0.264107E+10 | 0.191739E+10 | 0.202349E+10 | 0.104090E+10 | 0.982597E+09 | 0.00 | 0.00 |
April | 0.469527E+10 | 0.105546E+10 | 0.279525E+10 | 0.166600E+10 | 0.112925E+10 | 0.00 | 0.00 |
May | 0.541364E+10 | 0.769735E+09 | 0.299345E+10 | 0.177448E+10 | 0.121897E+10 | 0.00 | 0.00 |
June | 0.636487E+10 | 0.314576E+09 | 0.301950E+10 | 0.187627E+10 | 0.114323E+10 | 0.00 | 0.00 |
July | 0.559577E+10 | 0.263804E+09 | 0.263516E+10 | 0.148585E+10 | 0.114931E+10 | 0.00 | 0.00 |
August | 0.526218E+10 | 0.348643E+09 | 0.250100E+10 | 0.142731E+10 | 0.107369E+10 | 0.00 | 0.00 |
September | 0.398086E+10 | 0.493142E+09 | 0.198604E+10 | 0.957301E+09 | 0.102874E+10 | 0.00 | 0.00 |
October | 0.321925E+10 | 0.151839E+10 | 0.206135E+10 | 0.125452E+10 | 0.806832E+09 | 0.00 | 0.00 |
November | 0.187882E+10 | 0.213840E+10 | 0.153393E+10 | 0.920837E+09 | 0.613096E+09 | 0.00 | 0.00 |
December | 0.155421E+10 | 0.279707E+10 | 0.144516E+10 | 0.872629E+09 | 0.572535E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.443102E+11 | 0.158554E+11 | 0.260952E+11 | 0.151406E+11 | 0.109546E+11 | 0.00 | 0.00 |
Minimum of Months | 0.155421E+10 | 0.263804E+09 | 0.144516E+10 | 0.835434E+09 | 0.572535E+09 | 0.00 | 0.00 |
Maximum of Months | 0.636487E+10 | 0.279707E+10 | 0.301950E+10 | 0.187627E+10 | 0.121897E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.955037E+10 | 0.372036E+10 | 0.627147E+10 | 0.500884E+10 | 0.126263E+10 | 0.00 | 0.00 |
February | 0.489760E+10 | 0.307627E+10 | 0.358162E+10 | 0.241556E+10 | 0.116606E+10 | 0.00 | 0.00 |
March | 0.490617E+10 | 0.307408E+10 | 0.329948E+10 | 0.169940E+10 | 0.160009E+10 | 0.00 | 0.00 |
April | 0.526596E+10 | 0.172721E+10 | 0.271813E+10 | 0.109838E+10 | 0.161975E+10 | 0.00 | 0.00 |
May | 0.409386E+10 | 0.122069E+10 | 0.188216E+10 | 0.310949E+09 | 0.157121E+10 | 0.00 | 0.00 |
June | 0.459111E+10 | 0.484933E+09 | 0.155969E+10 | 0.120230E+09 | 0.143946E+10 | 0.00 | 0.00 |
July | 0.457295E+10 | 0.400902E+09 | 0.164685E+10 | 0.170377E+09 | 0.147647E+10 | 0.00 | 0.00 |
August | 0.522274E+10 | 0.539842E+09 | 0.200248E+10 | 0.553380E+09 | 0.144910E+10 | 0.00 | 0.00 |
September | 0.600927E+10 | 0.809042E+09 | 0.279229E+10 | 0.119125E+10 | 0.160104E+10 | 0.00 | 0.00 |
October | 0.772075E+10 | 0.243150E+10 | 0.459752E+10 | 0.318216E+10 | 0.141536E+10 | 0.00 | 0.00 |
November | 0.773700E+10 | 0.338735E+10 | 0.518500E+10 | 0.397144E+10 | 0.121357E+10 | 0.00 | 0.00 |
December | 0.840813E+10 | 0.443614E+10 | 0.583060E+10 | 0.461570E+10 | 0.121491E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.729759E+11 | 0.253083E+11 | 0.413673E+11 | 0.243377E+11 | 0.170296E+11 | 0.00 | 0.00 |
Minimum of Months | 0.409386E+10 | 0.400902E+09 | 0.155969E+10 | 0.120230E+09 | 0.116606E+10 | 0.00 | 0.00 |
Maximum of Months | 0.955037E+10 | 0.443614E+10 | 0.627147E+10 | 0.500884E+10 | 0.161975E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.250292E+10 | 0.247990E+10 | 0.171532E+10 | 0.106609E+10 | 0.649223E+09 | 0.00 | 0.00 |
February | 0.146916E+10 | 0.208688E+10 | 0.125510E+10 | 0.606762E+09 | 0.648338E+09 | 0.00 | 0.00 |
March | 0.252437E+10 | 0.203809E+10 | 0.184054E+10 | 0.877410E+09 | 0.963126E+09 | 0.00 | 0.00 |
April | 0.476056E+10 | 0.119981E+10 | 0.273503E+10 | 0.156014E+10 | 0.117489E+10 | 0.00 | 0.00 |
May | 0.529126E+10 | 0.895326E+09 | 0.283346E+10 | 0.158872E+10 | 0.124474E+10 | 0.00 | 0.00 |
June | 0.625715E+10 | 0.384340E+09 | 0.291508E+10 | 0.171453E+10 | 0.120055E+10 | 0.00 | 0.00 |
July | 0.486307E+10 | 0.301363E+09 | 0.219238E+10 | 0.102339E+10 | 0.116899E+10 | 0.00 | 0.00 |
August | 0.459870E+10 | 0.384235E+09 | 0.209063E+10 | 0.104995E+10 | 0.104068E+10 | 0.00 | 0.00 |
September | 0.365408E+10 | 0.539685E+09 | 0.176355E+10 | 0.740968E+09 | 0.102258E+10 | 0.00 | 0.00 |
October | 0.305693E+10 | 0.165845E+10 | 0.186462E+10 | 0.106618E+10 | 0.798439E+09 | 0.00 | 0.00 |
November | 0.231390E+10 | 0.232360E+10 | 0.166197E+10 | 0.100344E+10 | 0.658522E+09 | 0.00 | 0.00 |
December | 0.176845E+10 | 0.302858E+10 | 0.138412E+10 | 0.788075E+09 | 0.596049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.430605E+11 | 0.173202E+11 | 0.242518E+11 | 0.130857E+11 | 0.111661E+11 | 0.00 | 0.00 |
Minimum of Months | 0.146916E+10 | 0.301363E+09 | 0.125510E+10 | 0.606762E+09 | 0.596049E+09 | 0.00 | 0.00 |
Maximum of Months | 0.625715E+10 | 0.302858E+10 | 0.291508E+10 | 0.171453E+10 | 0.124474E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.562038E+09 | 0.359353E+10 | 0.761678E+09 | 0.00 | 0.761678E+09 | 0.00 | 0.00 |
February | 0.330386E+09 | 0.321708E+10 | 0.783922E+09 | 0.00 | 0.783922E+09 | 0.00 | 0.00 |
March | 0.102076E+10 | 0.315496E+10 | 0.115346E+10 | 0.00 | 0.115346E+10 | 0.00 | 0.00 |
April | 0.229760E+10 | 0.167917E+10 | 0.135998E+10 | 14113125.25 | 0.134587E+10 | 0.00 | 0.00 |
May | 0.328137E+10 | 0.116712E+10 | 0.164507E+10 | 0.131722E+09 | 0.151335E+10 | 0.00 | 0.00 |
June | 0.506982E+10 | 0.486757E+09 | 0.185001E+10 | 0.336128E+09 | 0.151388E+10 | 0.00 | 0.00 |
July | 0.447463E+10 | 0.386785E+09 | 0.163030E+10 | 0.169845E+09 | 0.146045E+10 | 0.00 | 0.00 |
August | 0.372142E+10 | 0.491073E+09 | 0.131594E+10 | 32691117.58 | 0.128325E+10 | 0.00 | 0.00 |
September | 0.296754E+10 | 0.715852E+09 | 0.120152E+10 | 320748.24 | 0.120120E+10 | 0.00 | 0.00 |
October | 0.141835E+10 | 0.230371E+10 | 0.960577E+09 | 0.00 | 0.960577E+09 | 0.00 | 0.00 |
November | 0.538912E+09 | 0.325078E+10 | 0.774520E+09 | 0.00 | 0.774520E+09 | 0.00 | 0.00 |
December | 0.325322E+09 | 0.437081E+10 | 0.711477E+09 | 0.00 | 0.711477E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.260081E+11 | 0.248176E+11 | 0.141485E+11 | 0.684819E+09 | 0.134636E+11 | 0.00 | 0.00 |
Minimum of Months | 0.325322E+09 | 0.386785E+09 | 0.711477E+09 | 0.00 | 0.711477E+09 | 0.00 | 0.00 |
Maximum of Months | 0.506982E+10 | 0.437081E+10 | 0.185001E+10 | 0.336128E+09 | 0.151388E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.204795E+10 | 0.220445E+10 | 0.164041E+10 | 0.102907E+10 | 0.611334E+09 | 0.00 | 0.00 |
February | 0.159809E+10 | 0.199490E+10 | 0.146046E+10 | 0.835450E+09 | 0.625010E+09 | 0.00 | 0.00 |
March | 0.257577E+10 | 0.194793E+10 | 0.202352E+10 | 0.104092E+10 | 0.982608E+09 | 0.00 | 0.00 |
April | 0.465440E+10 | 0.105204E+10 | 0.279530E+10 | 0.166603E+10 | 0.112926E+10 | 0.00 | 0.00 |
May | 0.537308E+10 | 0.774035E+09 | 0.299350E+10 | 0.177452E+10 | 0.121898E+10 | 0.00 | 0.00 |
June | 0.634691E+10 | 0.313031E+09 | 0.301954E+10 | 0.187630E+10 | 0.114324E+10 | 0.00 | 0.00 |
July | 0.560517E+10 | 0.247228E+09 | 0.263520E+10 | 0.148588E+10 | 0.114932E+10 | 0.00 | 0.00 |
August | 0.527895E+10 | 0.315745E+09 | 0.250104E+10 | 0.142734E+10 | 0.107370E+10 | 0.00 | 0.00 |
September | 0.400542E+10 | 0.447652E+09 | 0.198607E+10 | 0.957320E+09 | 0.102875E+10 | 0.00 | 0.00 |
October | 0.323530E+10 | 0.141544E+10 | 0.206138E+10 | 0.125454E+10 | 0.806840E+09 | 0.00 | 0.00 |
November | 0.189441E+10 | 0.200996E+10 | 0.153396E+10 | 0.920855E+09 | 0.613102E+09 | 0.00 | 0.00 |
December | 0.156986E+10 | 0.266864E+10 | 0.144519E+10 | 0.872646E+09 | 0.572541E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.441853E+11 | 0.153911E+11 | 0.260956E+11 | 0.151409E+11 | 0.109547E+11 | 0.00 | 0.00 |
Minimum of Months | 0.156986E+10 | 0.247228E+09 | 0.144519E+10 | 0.835450E+09 | 0.572541E+09 | 0.00 | 0.00 |
Maximum of Months | 0.634691E+10 | 0.266864E+10 | 0.301954E+10 | 0.187630E+10 | 0.121898E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.949986E+10 | 0.351714E+10 | 0.627172E+10 | 0.500905E+10 | 0.126267E+10 | 0.00 | 0.00 |
February | 0.478786E+10 | 0.307566E+10 | 0.358176E+10 | 0.241566E+10 | 0.116610E+10 | 0.00 | 0.00 |
March | 0.477246E+10 | 0.314494E+10 | 0.329961E+10 | 0.169947E+10 | 0.160014E+10 | 0.00 | 0.00 |
April | 0.520469E+10 | 0.176090E+10 | 0.271822E+10 | 0.109843E+10 | 0.161979E+10 | 0.00 | 0.00 |
May | 0.404177E+10 | 0.128402E+10 | 0.188221E+10 | 0.310962E+09 | 0.157124E+10 | 0.00 | 0.00 |
June | 0.460179E+10 | 0.513757E+09 | 0.155972E+10 | 0.120235E+09 | 0.143949E+10 | 0.00 | 0.00 |
July | 0.461395E+10 | 0.395065E+09 | 0.164689E+10 | 0.170384E+09 | 0.147651E+10 | 0.00 | 0.00 |
August | 0.529030E+10 | 0.499516E+09 | 0.200254E+10 | 0.553403E+09 | 0.144914E+10 | 0.00 | 0.00 |
September | 0.607792E+10 | 0.725088E+09 | 0.279239E+10 | 0.119130E+10 | 0.160109E+10 | 0.00 | 0.00 |
October | 0.773409E+10 | 0.225090E+10 | 0.459769E+10 | 0.318229E+10 | 0.141540E+10 | 0.00 | 0.00 |
November | 0.771874E+10 | 0.314436E+10 | 0.518521E+10 | 0.397160E+10 | 0.121361E+10 | 0.00 | 0.00 |
December | 0.837031E+10 | 0.417419E+10 | 0.583083E+10 | 0.461589E+10 | 0.121494E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.727137E+11 | 0.244855E+11 | 0.413688E+11 | 0.243387E+11 | 0.170301E+11 | 0.00 | 0.00 |
Minimum of Months | 0.404177E+10 | 0.395065E+09 | 0.155972E+10 | 0.120235E+09 | 0.116610E+10 | 0.00 | 0.00 |
Maximum of Months | 0.949986E+10 | 0.417419E+10 | 0.627172E+10 | 0.500905E+10 | 0.161979E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.248463E+10 | 0.242913E+10 | 0.171534E+10 | 0.106611E+10 | 0.649229E+09 | 0.00 | 0.00 |
February | 0.143135E+10 | 0.210880E+10 | 0.125512E+10 | 0.606772E+09 | 0.648344E+09 | 0.00 | 0.00 |
March | 0.245712E+10 | 0.208206E+10 | 0.184056E+10 | 0.877424E+09 | 0.963135E+09 | 0.00 | 0.00 |
April | 0.471990E+10 | 0.119467E+10 | 0.273507E+10 | 0.156017E+10 | 0.117490E+10 | 0.00 | 0.00 |
May | 0.525336E+10 | 0.895956E+09 | 0.283349E+10 | 0.158874E+10 | 0.124475E+10 | 0.00 | 0.00 |
June | 0.624042E+10 | 0.379209E+09 | 0.291511E+10 | 0.171456E+10 | 0.120056E+10 | 0.00 | 0.00 |
July | 0.487301E+10 | 0.286069E+09 | 0.219241E+10 | 0.102341E+10 | 0.116900E+10 | 0.00 | 0.00 |
August | 0.461834E+10 | 0.354274E+09 | 0.209066E+10 | 0.104997E+10 | 0.104069E+10 | 0.00 | 0.00 |
September | 0.367809E+10 | 0.493485E+09 | 0.176357E+10 | 0.740980E+09 | 0.102259E+10 | 0.00 | 0.00 |
October | 0.307352E+10 | 0.155046E+10 | 0.186465E+10 | 0.106620E+10 | 0.798446E+09 | 0.00 | 0.00 |
November | 0.232471E+10 | 0.217844E+10 | 0.166199E+10 | 0.100346E+10 | 0.658528E+09 | 0.00 | 0.00 |
December | 0.177334E+10 | 0.290277E+10 | 0.138414E+10 | 0.788088E+09 | 0.596054E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.429278E+11 | 0.168553E+11 | 0.242521E+11 | 0.130859E+11 | 0.111662E+11 | 0.00 | 0.00 |
Minimum of Months | 0.143135E+10 | 0.286069E+09 | 0.125512E+10 | 0.606772E+09 | 0.596054E+09 | 0.00 | 0.00 |
Maximum of Months | 0.624042E+10 | 0.290277E+10 | 0.291511E+10 | 0.171456E+10 | 0.124475E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.450478E+10 | -0.380901E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -695769173.3 | 58.98 | 0.00 | 0.00 |
February | 0.405738E+10 | -0.342745E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -629931201.2 | 58.98 | 0.00 | 0.00 |
March | 0.455195E+10 | -0.385816E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -693794298.8 | 58.98 | 0.00 | 0.00 |
April | 0.386279E+10 | -0.319596E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666829294.1 | 58.98 | 0.00 | 0.00 |
May | 0.379810E+10 | -0.311021E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687886332.1 | 58.98 | 0.00 | 0.00 |
June | 0.349097E+10 | -0.282457E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666409262.7 | 58.98 | 0.00 | 0.00 |
July | 0.322809E+10 | -0.254013E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687964540.7 | 58.98 | 0.00 | 0.00 |
August | 0.354033E+10 | -0.285153E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688796898.4 | 58.98 | 0.00 | 0.00 |
September | 0.341754E+10 | -0.275372E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -663827259.4 | 58.98 | 0.00 | 0.00 |
October | 0.381820E+10 | -0.313104E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687160938.4 | 58.98 | 0.00 | 0.00 |
November | 0.404955E+10 | -0.338156E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667982251.2 | 58.98 | 0.00 | 0.00 |
December | 0.428277E+10 | -0.358634E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -696422185.1 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.466024E+11 | -0.384697E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.813277E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.322809E+10 | -0.385816E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -696422185.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.455195E+10 | -0.254013E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -629931201.2 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.51 | 0.48 | 01-JAN-07:00 | 9218.88 | 38.85 | 306.33 | 291.50 | 2436.74 | 28.41 | 169.67 | 288.00 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:49 | 8283.88 | 36.27 | 234.17 | 264.83 | 1339.57 | 22.68 | 120.67 | 223.17 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:30 | 1574.63 | 17.89 | 2.33 | 328.00 | 935.58 | 20.09 | 122.33 | 287.00 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:09 | 1207.17 | 17.60 | 0.00 | 332.00 | 768.63 | 19.77 | 62.33 | 301.67 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:40 | 949.30 | 17.37 | 0.00 | 357.17 | 602.74 | 19.60 | 14.00 | 315.33 |
June | 418.17 | 0.53 | 0.48 | 01-JUN-07:30 | 784.93 | 16.62 | 0.00 | 361.17 | 511.77 | 18.90 | 0.83 | 309.17 |
July | 399.50 | 0.53 | 0.48 | 01-JUL-07:00 | 914.36 | 17.03 | 0.00 | 361.00 | 557.01 | 19.26 | 18.50 | 292.17 |
August | 361.83 | 0.53 | 0.48 | 01-AUG-07:00 | 1054.37 | 17.37 | 0.00 | 336.00 | 649.71 | 19.58 | 34.00 | 286.83 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:10 | 1522.06 | 18.32 | 11.00 | 318.17 | 866.34 | 20.07 | 103.67 | 286.00 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-07:19 | 3179.12 | 23.99 | 140.17 | 318.00 | 1155.51 | 20.01 | 87.50 | 300.33 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:40 | 8721.07 | 37.48 | 282.00 | 285.17 | 1670.68 | 25.02 | 132.50 | 267.33 |
December | 290.67 | 0.50 | 0.48 | 01-DEC-07:40 | 8517.76 | 38.33 | 284.17 | 279.67 | 2272.90 | 28.09 | 164.67 | 274.50 |
Annual Sum or Average | 4135.50 | 0.52 | 3371.53 | 23.55 | 1260.17 | 3832.67 | 1077.27 | 21.44 | 1030.67 | 3431.50 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 784.93 | 16.62 | 0.00 | 264.83 | 511.77 | 18.90 | 0.83 | 223.17 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 9218.88 | 38.85 | 306.33 | 361.17 | 2436.74 | 28.41 | 169.67 | 315.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.54 | 0.48 | 01-JAN-07:00 | 2076.31 | 20.48 | 87.17 | 266.83 | 1197.38 | 23.03 | 77.33 | 221.83 |
February | 241.00 | 0.53 | 0.48 | 01-FEB-07:49 | 2616.93 | 23.04 | 85.83 | 253.33 | 1462.84 | 23.47 | 63.17 | 184.17 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-07:30 | 2139.37 | 19.74 | 86.17 | 312.00 | 1159.01 | 21.90 | 69.67 | 277.17 |
April | 380.33 | 0.51 | 0.48 | 01-APR-06:40 | 3062.20 | 21.30 | 112.33 | 345.33 | 1724.30 | 22.22 | 82.33 | 321.33 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-05:00 | 3424.52 | 21.06 | 118.50 | 377.17 | 1393.54 | 21.68 | 72.33 | 351.00 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-05:49 | 3493.73 | 21.77 | 134.33 | 385.83 | 1377.15 | 21.14 | 74.83 | 347.33 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-05:49 | 3006.99 | 20.65 | 115.33 | 379.17 | 1242.19 | 21.13 | 68.33 | 319.00 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2977.51 | 21.56 | 114.50 | 350.50 | 1655.08 | 22.38 | 83.50 | 305.50 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-06:30 | 2342.57 | 21.09 | 102.00 | 316.67 | 1264.60 | 22.17 | 75.17 | 275.17 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-06:00 | 2215.46 | 19.43 | 87.83 | 288.83 | 1234.45 | 21.58 | 72.33 | 250.17 |
November | 288.50 | 0.53 | 0.48 | 01-NOV-07:40 | 1845.00 | 20.91 | 80.17 | 267.83 | 978.35 | 21.53 | 52.83 | 202.33 |
December | 290.67 | 0.53 | 0.48 | 01-DEC-07:40 | 2139.86 | 22.83 | 101.67 | 253.83 | 1196.01 | 23.53 | 77.17 | 200.00 |
Annual Sum or Average | 4135.50 | 0.52 | 2669.84 | 21.10 | 1225.83 | 3797.33 | 1333.23 | 22.06 | 869.00 | 3255.00 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1845.00 | 19.43 | 80.17 | 253.33 | 978.35 | 21.13 | 52.83 | 184.17 | |
Maximum of Months | 418.17 | 0.54 | 0.48 | 3493.73 | 23.04 | 134.33 | 385.83 | 1724.30 | 23.53 | 83.50 | 351.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.60 | 0.48 | 01-JAN-10:20 | 451.18 | 13.85 | 0.00 | 220.50 | 313.40 | 16.59 | 0.00 | 120.00 |
February | 241.00 | 0.57 | 0.48 | 01-FEB-12:50 | 556.81 | 14.87 | 0.00 | 222.83 | 360.28 | 17.29 | 0.00 | 125.67 |
March | 344.33 | 0.55 | 0.48 | 01-MAR-08:30 | 638.82 | 16.16 | 0.00 | 298.50 | 401.00 | 18.37 | 0.00 | 225.33 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:39 | 752.09 | 17.42 | 0.00 | 335.33 | 496.75 | 19.59 | 5.67 | 302.83 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-06:10 | 889.93 | 18.17 | 2.67 | 388.50 | 587.96 | 20.40 | 52.50 | 373.33 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-05:00 | 1036.62 | 21.17 | 81.50 | 399.17 | 637.57 | 23.31 | 125.00 | 395.00 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:00 | 917.83 | 20.49 | 62.50 | 394.00 | 586.42 | 22.60 | 109.00 | 360.00 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:40 | 762.89 | 17.46 | 0.00 | 347.67 | 486.84 | 19.65 | 7.67 | 293.67 |
September | 350.17 | 0.54 | 0.48 | 01-SEP-07:19 | 726.78 | 16.76 | 0.00 | 313.50 | 447.39 | 18.90 | 1.00 | 253.83 |
October | 348.00 | 0.58 | 0.48 | 01-OCT-07:00 | 521.46 | 14.79 | 0.00 | 256.83 | 349.89 | 17.23 | 0.00 | 173.67 |
November | 288.50 | 0.58 | 0.48 | 01-NOV-08:50 | 490.67 | 14.56 | 0.00 | 230.67 | 328.12 | 17.20 | 0.00 | 121.17 |
December | 290.67 | 0.59 | 0.48 | 01-DEC-09:30 | 455.16 | 14.01 | 0.00 | 206.33 | 308.45 | 16.76 | 0.00 | 95.67 |
Annual Sum or Average | 4135.50 | 0.54 | 707.24 | 16.94 | 146.67 | 3613.83 | 456.48 | 19.26 | 300.83 | 2840.17 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 451.18 | 13.85 | 0.00 | 206.33 | 308.45 | 16.59 | 0.00 | 95.67 | |
Maximum of Months | 418.17 | 0.60 | 0.48 | 1036.62 | 21.17 | 81.50 | 399.17 | 637.57 | 23.31 | 125.00 | 395.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.56 | 0.48 | 01-JAN-10:09 | 2330.95 | 21.98 | 105.67 | 243.83 | 1307.92 | 22.37 | 76.33 | 205.33 |
February | 241.00 | 0.55 | 0.48 | 01-FEB-12:20 | 2358.35 | 21.21 | 81.17 | 234.50 | 923.45 | 20.10 | 36.67 | 173.50 |
March | 344.33 | 0.53 | 0.48 | 02-MAR-09:20 | 1944.55 | 19.06 | 79.00 | 310.00 | 1087.61 | 21.53 | 65.33 | 272.83 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:50 | 2851.99 | 18.95 | 85.00 | 332.83 | 1592.24 | 20.26 | 55.00 | 304.50 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:00 | 3064.68 | 16.66 | 54.50 | 361.67 | 1695.54 | 17.20 | 0.00 | 330.33 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:40 | 3082.11 | 12.97 | 0.00 | 367.83 | 1260.22 | 16.79 | 0.00 | 339.17 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-08:20 | 2302.20 | 13.86 | 3.67 | 368.00 | 1045.55 | 17.23 | 0.00 | 318.83 |
August | 361.83 | 0.53 | 0.48 | 01-AUG-08:20 | 2379.75 | 16.50 | 49.17 | 340.33 | 1310.19 | 17.35 | 5.00 | 293.00 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:00 | 1871.79 | 19.18 | 81.83 | 315.83 | 1027.58 | 20.39 | 53.83 | 279.17 |
October | 348.00 | 0.55 | 0.48 | 01-OCT-08:09 | 2305.85 | 21.05 | 109.33 | 283.33 | 1269.07 | 22.00 | 81.17 | 248.50 |
November | 288.50 | 0.55 | 0.48 | 01-NOV-08:50 | 2102.96 | 20.25 | 80.83 | 249.00 | 1176.43 | 21.98 | 62.50 | 204.00 |
December | 290.67 | 0.55 | 0.48 | 01-DEC-09:30 | 1776.80 | 20.17 | 80.67 | 234.00 | 944.69 | 20.85 | 53.83 | 193.00 |
Annual Sum or Average | 4135.50 | 0.53 | 2401.43 | 18.16 | 810.83 | 3641.17 | 1239.43 | 19.64 | 489.67 | 3162.17 | ||
Minimum of Months | 241.00 | 0.52 | 0.48 | 1776.80 | 12.97 | 0.00 | 234.00 | 923.45 | 16.79 | 0.00 | 173.50 | |
Maximum of Months | 418.17 | 0.56 | 0.48 | 3082.11 | 21.98 | 109.33 | 368.00 | 1695.54 | 22.37 | 81.17 | 339.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.51 | 0.48 | 01-JAN-07:00 | 9059.71 | 38.64 | 306.33 | 291.00 | 2299.48 | 26.31 | 145.50 | 286.50 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:49 | 8157.66 | 36.03 | 234.17 | 264.17 | 1239.38 | 20.03 | 40.67 | 219.50 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:30 | 1490.94 | 14.06 | 2.33 | 326.67 | 872.47 | 17.66 | 1.83 | 283.50 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:20 | 1149.54 | 14.17 | 0.00 | 329.00 | 727.80 | 17.76 | 0.00 | 299.17 |
May | 403.17 | 0.53 | 0.48 | 01-MAY-07:40 | 913.49 | 13.98 | 0.00 | 354.17 | 581.20 | 17.59 | 0.00 | 312.00 |
June | 418.17 | 0.54 | 0.48 | 01-JUN-07:30 | 758.56 | 13.25 | 0.00 | 357.50 | 497.42 | 16.89 | 0.00 | 302.33 |
July | 399.50 | 0.54 | 0.48 | 01-JUL-07:00 | 880.71 | 13.53 | 0.00 | 357.83 | 537.19 | 17.11 | 0.00 | 287.50 |
August | 361.83 | 0.53 | 0.48 | 01-AUG-07:00 | 1009.53 | 13.84 | 0.00 | 333.33 | 620.01 | 17.44 | 0.00 | 282.17 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:10 | 1449.38 | 14.68 | 10.83 | 316.67 | 813.88 | 17.68 | 0.00 | 282.50 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-07:19 | 3070.44 | 21.30 | 139.83 | 316.50 | 1066.74 | 17.40 | 13.17 | 297.67 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:40 | 8577.71 | 37.20 | 281.83 | 284.83 | 1550.63 | 22.52 | 89.17 | 266.17 |
December | 290.67 | 0.50 | 0.48 | 01-DEC-07:40 | 8346.21 | 37.82 | 282.17 | 279.17 | 2135.55 | 25.86 | 130.67 | 273.67 |
Annual Sum or Average | 4135.50 | 0.52 | 3289.29 | 20.98 | 1257.50 | 3810.83 | 1014.14 | 19.19 | 421.00 | 3392.67 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 758.56 | 13.25 | 0.00 | 264.17 | 497.42 | 16.89 | 0.00 | 219.50 | |
Maximum of Months | 418.17 | 0.54 | 0.48 | 9059.71 | 38.64 | 306.33 | 357.83 | 2299.48 | 26.31 | 145.50 | 312.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.54 | 0.48 | 01-JAN-07:00 | 2023.01 | 19.99 | 87.17 | 263.00 | 1152.30 | 22.83 | 75.67 | 217.67 |
February | 241.00 | 0.53 | 0.48 | 01-FEB-07:49 | 2554.70 | 22.59 | 85.83 | 251.83 | 1413.18 | 23.27 | 63.00 | 179.17 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-07:30 | 2078.28 | 19.25 | 86.17 | 309.00 | 1105.93 | 21.71 | 69.83 | 273.50 |
April | 380.33 | 0.52 | 0.48 | 01-APR-06:40 | 2983.42 | 20.85 | 112.33 | 344.67 | 1663.05 | 22.04 | 82.33 | 318.17 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-05:00 | 3339.35 | 20.54 | 117.83 | 376.17 | 1329.32 | 21.52 | 72.33 | 348.33 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-05:49 | 3348.66 | 19.71 | 115.00 | 384.50 | 1315.81 | 20.98 | 74.83 | 342.00 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-05:00 | 2936.52 | 20.19 | 115.33 | 376.50 | 1184.14 | 20.97 | 68.33 | 314.50 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2899.22 | 21.11 | 114.50 | 348.00 | 1596.92 | 22.21 | 83.50 | 301.17 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-06:40 | 2282.27 | 20.63 | 102.00 | 314.67 | 1214.85 | 21.98 | 75.17 | 271.33 |
October | 348.00 | 0.55 | 0.48 | 01-OCT-06:00 | 2153.85 | 18.95 | 87.83 | 285.17 | 1183.40 | 21.39 | 72.17 | 248.33 |
November | 288.50 | 0.53 | 0.48 | 01-NOV-07:40 | 1763.91 | 19.93 | 76.33 | 262.17 | 936.64 | 21.31 | 52.83 | 198.00 |
December | 290.67 | 0.54 | 0.48 | 01-DEC-07:49 | 1995.49 | 20.38 | 85.33 | 248.00 | 1154.85 | 23.32 | 74.33 | 197.17 |
Annual Sum or Average | 4135.50 | 0.52 | 2587.16 | 20.29 | 1185.67 | 3763.67 | 1279.43 | 21.88 | 864.33 | 3209.33 | ||
Minimum of Months | 241.00 | 0.51 | 0.48 | 1763.91 | 18.95 | 76.33 | 248.00 | 936.64 | 20.97 | 52.83 | 179.17 | |
Maximum of Months | 418.17 | 0.55 | 0.48 | 3348.66 | 22.59 | 117.83 | 384.50 | 1663.05 | 23.32 | 83.50 | 348.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.60 | 0.48 | 01-JAN-10:20 | 434.94 | 10.39 | 0.00 | 212.50 | 305.59 | 14.32 | 0.00 | 111.50 |
February | 241.00 | 0.58 | 0.48 | 01-FEB-12:50 | 537.76 | 11.43 | 0.00 | 219.33 | 350.58 | 15.12 | 0.00 | 120.67 |
March | 344.33 | 0.55 | 0.48 | 01-MAR-08:30 | 617.28 | 12.79 | 0.00 | 296.17 | 389.74 | 16.37 | 0.00 | 218.67 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:39 | 727.10 | 14.30 | 0.00 | 333.83 | 484.35 | 17.92 | 0.00 | 299.50 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-06:10 | 859.89 | 14.78 | 2.67 | 386.67 | 571.76 | 18.48 | 4.17 | 371.17 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-05:00 | 1004.40 | 18.28 | 81.33 | 398.83 | 618.83 | 21.54 | 82.83 | 394.33 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:00 | 885.28 | 17.47 | 62.50 | 393.17 | 567.82 | 20.74 | 62.83 | 356.33 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:49 | 737.36 | 14.06 | 0.00 | 344.50 | 473.63 | 17.74 | 0.00 | 286.50 |
September | 350.17 | 0.54 | 0.48 | 01-SEP-07:19 | 701.62 | 13.41 | 0.00 | 310.33 | 433.96 | 16.91 | 0.00 | 247.67 |
October | 348.00 | 0.59 | 0.48 | 01-OCT-07:00 | 504.22 | 11.41 | 0.00 | 251.17 | 341.46 | 15.18 | 0.00 | 167.00 |
November | 288.50 | 0.58 | 0.48 | 01-NOV-08:50 | 473.48 | 10.98 | 0.00 | 223.33 | 319.60 | 14.91 | 0.00 | 112.00 |
December | 290.67 | 0.60 | 0.48 | 01-DEC-09:00 | 438.52 | 10.41 | 0.00 | 199.67 | 300.23 | 14.38 | 0.00 | 86.67 |
Annual Sum or Average | 4135.50 | 0.54 | 683.31 | 13.63 | 146.50 | 3569.50 | 443.80 | 17.26 | 149.83 | 2772.00 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 434.94 | 10.39 | 0.00 | 199.67 | 300.23 | 14.32 | 0.00 | 86.67 | |
Maximum of Months | 418.17 | 0.60 | 0.48 | 1004.40 | 18.28 | 81.33 | 398.83 | 618.83 | 21.54 | 82.83 | 394.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.56 | 0.48 | 01-JAN-10:20 | 2153.12 | 19.50 | 86.50 | 239.17 | 1260.16 | 22.27 | 76.17 | 201.83 |
February | 241.00 | 0.55 | 0.48 | 01-FEB-12:20 | 2301.06 | 20.81 | 81.17 | 232.67 | 880.91 | 19.98 | 36.67 | 171.33 |
March | 344.33 | 0.54 | 0.48 | 02-MAR-09:20 | 1887.80 | 18.61 | 79.00 | 308.17 | 1040.46 | 21.40 | 65.33 | 269.67 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:50 | 2772.25 | 18.47 | 85.00 | 330.17 | 1529.55 | 20.09 | 55.00 | 302.17 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:00 | 2982.56 | 16.16 | 54.50 | 359.50 | 1635.25 | 17.03 | 0.00 | 328.17 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:49 | 3011.52 | 12.44 | 0.00 | 365.00 | 1200.06 | 16.60 | 0.00 | 336.50 |
July | 399.50 | 0.53 | 0.48 | 01-JUL-08:20 | 2241.67 | 13.31 | 3.67 | 365.00 | 999.21 | 17.03 | 0.00 | 315.00 |
August | 361.83 | 0.53 | 0.48 | 01-AUG-08:20 | 2312.02 | 15.97 | 49.17 | 337.83 | 1262.26 | 17.16 | 5.00 | 290.00 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-08:09 | 1818.09 | 18.73 | 81.83 | 313.17 | 983.80 | 20.24 | 53.83 | 275.00 |
October | 348.00 | 0.55 | 0.48 | 01-OCT-08:20 | 2249.64 | 20.63 | 109.33 | 281.50 | 1223.26 | 21.88 | 81.17 | 246.33 |
November | 288.50 | 0.55 | 0.48 | 01-NOV-08:50 | 2041.05 | 19.82 | 80.83 | 245.67 | 1126.59 | 21.87 | 62.33 | 201.17 |
December | 290.67 | 0.55 | 0.48 | 01-DEC-09:30 | 1725.18 | 19.76 | 80.67 | 231.33 | 892.70 | 20.52 | 50.50 | 190.00 |
Annual Sum or Average | 4135.50 | 0.54 | 2328.57 | 17.53 | 791.67 | 3609.17 | 1188.36 | 19.47 | 486.00 | 3127.17 | ||
Minimum of Months | 241.00 | 0.52 | 0.48 | 1725.18 | 12.44 | 0.00 | 231.33 | 880.91 | 16.60 | 0.00 | 171.33 | |
Maximum of Months | 418.17 | 0.56 | 0.48 | 3011.52 | 20.81 | 109.33 | 365.00 | 1635.25 | 22.27 | 81.17 | 336.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.51 | 0.48 | 01-JAN-07:00 | 9059.70 | 38.64 | 306.33 | 291.00 | 2299.42 | 26.31 | 145.50 | 286.50 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:49 | 8157.59 | 36.03 | 234.17 | 264.17 | 1239.31 | 20.03 | 40.67 | 219.50 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:30 | 1490.86 | 14.06 | 2.33 | 326.67 | 872.41 | 17.66 | 1.83 | 283.50 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:20 | 1149.49 | 14.17 | 0.00 | 329.00 | 727.76 | 17.76 | 0.00 | 299.17 |
May | 403.17 | 0.53 | 0.48 | 01-MAY-07:40 | 913.46 | 13.98 | 0.00 | 354.17 | 581.17 | 17.59 | 0.00 | 312.00 |
June | 418.17 | 0.54 | 0.48 | 01-JUN-07:30 | 758.54 | 13.25 | 0.00 | 357.50 | 497.40 | 16.89 | 0.00 | 302.33 |
July | 399.50 | 0.54 | 0.48 | 01-JUL-07:00 | 880.67 | 13.53 | 0.00 | 357.83 | 537.16 | 17.11 | 0.00 | 287.50 |
August | 361.83 | 0.53 | 0.48 | 01-AUG-07:00 | 1009.49 | 13.84 | 0.00 | 333.33 | 619.97 | 17.44 | 0.00 | 282.17 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:10 | 1449.30 | 14.68 | 10.83 | 316.67 | 813.82 | 17.69 | 0.00 | 282.50 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-07:19 | 3070.38 | 21.30 | 139.83 | 316.50 | 1066.69 | 17.40 | 13.17 | 297.67 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:40 | 8577.68 | 37.20 | 281.83 | 284.83 | 1550.57 | 22.52 | 89.17 | 266.17 |
December | 290.67 | 0.50 | 0.48 | 01-DEC-07:40 | 8346.20 | 37.82 | 282.17 | 279.17 | 2135.48 | 25.86 | 130.67 | 273.67 |
Annual Sum or Average | 4135.50 | 0.52 | 3289.25 | 20.98 | 1257.50 | 3810.83 | 1014.09 | 19.19 | 421.00 | 3392.67 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 758.54 | 13.25 | 0.00 | 264.17 | 497.40 | 16.89 | 0.00 | 219.50 | |
Maximum of Months | 418.17 | 0.54 | 0.48 | 9059.70 | 38.64 | 306.33 | 357.83 | 2299.42 | 26.31 | 145.50 | 312.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.54 | 0.48 | 01-JAN-07:00 | 2023.01 | 19.99 | 87.17 | 263.00 | 1152.27 | 22.83 | 76.00 | 217.67 |
February | 241.00 | 0.53 | 0.48 | 01-FEB-07:49 | 2554.69 | 22.59 | 85.83 | 251.83 | 1413.14 | 23.27 | 63.00 | 179.17 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-07:30 | 2078.24 | 19.25 | 86.17 | 309.00 | 1105.89 | 21.71 | 69.83 | 273.50 |
April | 380.33 | 0.52 | 0.48 | 01-APR-06:40 | 2983.41 | 20.85 | 112.33 | 344.67 | 1663.00 | 22.04 | 82.33 | 318.17 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-05:00 | 3339.34 | 20.54 | 117.83 | 376.17 | 1329.28 | 21.52 | 72.33 | 348.33 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-05:49 | 3348.65 | 19.71 | 115.00 | 384.50 | 1315.77 | 20.98 | 74.83 | 342.00 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-05:00 | 2936.49 | 20.20 | 115.33 | 376.50 | 1184.10 | 20.97 | 68.33 | 314.50 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2899.19 | 21.11 | 114.50 | 348.00 | 1596.87 | 22.21 | 83.50 | 301.17 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-06:40 | 2282.23 | 20.64 | 102.00 | 314.67 | 1214.80 | 21.98 | 75.17 | 271.33 |
October | 348.00 | 0.55 | 0.48 | 01-OCT-06:00 | 2153.83 | 18.95 | 87.83 | 285.17 | 1183.37 | 21.39 | 72.17 | 248.33 |
November | 288.50 | 0.53 | 0.48 | 01-NOV-07:40 | 1763.89 | 19.93 | 76.33 | 262.17 | 936.61 | 21.31 | 52.83 | 198.00 |
December | 290.67 | 0.54 | 0.48 | 01-DEC-07:49 | 1995.49 | 20.38 | 85.33 | 248.00 | 1154.83 | 23.32 | 74.33 | 197.17 |
Annual Sum or Average | 4135.50 | 0.52 | 2587.14 | 20.29 | 1185.67 | 3763.67 | 1279.39 | 21.88 | 864.67 | 3209.33 | ||
Minimum of Months | 241.00 | 0.51 | 0.48 | 1763.89 | 18.95 | 76.33 | 248.00 | 936.61 | 20.97 | 52.83 | 179.17 | |
Maximum of Months | 418.17 | 0.55 | 0.48 | 3348.65 | 22.59 | 117.83 | 384.50 | 1663.00 | 23.32 | 83.50 | 348.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.60 | 0.48 | 01-JAN-10:20 | 434.95 | 10.39 | 0.00 | 212.50 | 305.57 | 14.32 | 0.00 | 111.50 |
February | 241.00 | 0.58 | 0.48 | 01-FEB-12:50 | 537.76 | 11.44 | 0.00 | 219.33 | 350.56 | 15.12 | 0.00 | 120.67 |
March | 344.33 | 0.55 | 0.48 | 01-MAR-08:30 | 617.26 | 12.79 | 0.00 | 296.17 | 389.72 | 16.37 | 0.00 | 218.67 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:39 | 727.09 | 14.30 | 0.00 | 333.83 | 484.33 | 17.92 | 0.00 | 299.50 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-06:10 | 859.88 | 14.79 | 2.67 | 386.67 | 571.73 | 18.49 | 4.17 | 371.17 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-05:00 | 1004.38 | 18.28 | 81.33 | 398.83 | 618.81 | 21.54 | 82.83 | 394.33 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:00 | 885.26 | 17.47 | 62.50 | 393.17 | 567.79 | 20.74 | 62.83 | 356.33 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:49 | 737.35 | 14.07 | 0.00 | 344.50 | 473.60 | 17.74 | 0.00 | 286.50 |
September | 350.17 | 0.54 | 0.48 | 01-SEP-07:19 | 701.61 | 13.41 | 0.00 | 310.33 | 433.93 | 16.91 | 0.00 | 247.67 |
October | 348.00 | 0.59 | 0.48 | 01-OCT-07:00 | 504.22 | 11.41 | 0.00 | 251.17 | 341.44 | 15.18 | 0.00 | 167.00 |
November | 288.50 | 0.58 | 0.48 | 01-NOV-08:50 | 473.48 | 10.98 | 0.00 | 223.33 | 319.59 | 14.91 | 0.00 | 112.00 |
December | 290.67 | 0.60 | 0.48 | 01-DEC-09:00 | 438.52 | 10.41 | 0.00 | 199.67 | 300.22 | 14.38 | 0.00 | 86.67 |
Annual Sum or Average | 4135.50 | 0.54 | 683.30 | 13.63 | 146.50 | 3569.50 | 443.78 | 17.26 | 149.83 | 2772.00 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 434.95 | 10.39 | 0.00 | 199.67 | 300.22 | 14.32 | 0.00 | 86.67 | |
Maximum of Months | 418.17 | 0.60 | 0.48 | 1004.38 | 18.28 | 81.33 | 398.83 | 618.81 | 21.54 | 82.83 | 394.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.56 | 0.48 | 01-JAN-10:20 | 2153.12 | 19.51 | 86.50 | 239.17 | 1260.13 | 22.27 | 76.17 | 201.83 |
February | 241.00 | 0.55 | 0.48 | 01-FEB-12:20 | 2301.04 | 20.82 | 81.17 | 232.67 | 880.87 | 19.98 | 36.67 | 171.33 |
March | 344.33 | 0.54 | 0.48 | 02-MAR-09:20 | 1887.77 | 18.61 | 79.00 | 308.17 | 1040.41 | 21.40 | 65.33 | 269.67 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:50 | 2772.24 | 18.47 | 85.00 | 330.17 | 1529.51 | 20.09 | 55.00 | 302.17 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:00 | 2982.54 | 16.16 | 54.50 | 359.50 | 1635.20 | 17.03 | 0.00 | 328.17 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:49 | 3011.51 | 12.44 | 0.00 | 365.00 | 1200.02 | 16.60 | 0.00 | 336.50 |
July | 399.50 | 0.53 | 0.48 | 01-JUL-08:20 | 2241.64 | 13.31 | 3.67 | 365.00 | 999.17 | 17.03 | 0.00 | 315.00 |
August | 361.83 | 0.53 | 0.48 | 01-AUG-08:20 | 2312.00 | 15.98 | 49.17 | 337.83 | 1262.22 | 17.16 | 5.00 | 290.00 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-08:09 | 1818.06 | 18.73 | 81.83 | 313.17 | 983.75 | 20.24 | 53.83 | 275.00 |
October | 348.00 | 0.55 | 0.48 | 01-OCT-08:20 | 2249.63 | 20.63 | 109.33 | 281.50 | 1223.22 | 21.88 | 81.17 | 246.33 |
November | 288.50 | 0.55 | 0.48 | 01-NOV-08:50 | 2041.05 | 19.82 | 80.83 | 245.67 | 1126.56 | 21.87 | 62.33 | 201.17 |
December | 290.67 | 0.55 | 0.48 | 01-DEC-09:30 | 1725.17 | 19.76 | 80.67 | 231.33 | 892.67 | 20.52 | 50.50 | 190.00 |
Annual Sum or Average | 4135.50 | 0.54 | 2328.55 | 17.54 | 791.67 | 3609.17 | 1188.32 | 19.47 | 486.00 | 3127.17 | ||
Minimum of Months | 241.00 | 0.52 | 0.48 | 1725.17 | 12.44 | 0.00 | 231.33 | 880.87 | 16.60 | 0.00 | 171.33 | |
Maximum of Months | 418.17 | 0.56 | 0.48 | 3011.51 | 20.82 | 109.33 | 365.00 | 1635.20 | 22.27 | 81.17 | 336.50 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.699145E+09 | 9501.25 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.767126E+09 | 9501.25 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.869523E+09 | 9501.25 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146502E+09 | 9501.25 | 07-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7584402.11 | 7941.44 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288475E+09 | 9501.25 | 12-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.400567E+09 | 9501.25 | 06-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.833828E+09 | 9501.25 | 01-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.401275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.869523E+09 | 9501.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 20748002.49 | 6289.11 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22816290.32 | 6289.11 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16716181.35 | 6289.11 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135572.84 | 1129.77 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 30117540.68 | 6289.11 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90533587.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30117540.68 | 6289.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 72531312.48 | 9406.36 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 65844928.12 | 9406.36 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 60093609.88 | 9406.36 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2564344.59 | 4978.72 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102564E+09 | 9406.36 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102564E+09 | 9406.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 25372406.43 | 6226.53 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 49712001.01 | 6226.53 | 08-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34284130.49 | 6226.53 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 119828.51 | 567.10 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 63870660.89 | 6226.53 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173359E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 63870660.89 | 6226.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 15389653.71 | 24206.94 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15389653.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15389653.71 | 24206.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 29062263.75 | 10956.25 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27636355.69 | 10956.25 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30902836.60 | 10956.25 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3536612.17 | 10822.09 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100348E+09 | 10956.25 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100348E+09 | 10956.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 47053765.34 | 7231.39 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 48161464.96 | 7231.39 | 08-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28717618.77 | 7231.39 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1746574.88 | 1997.58 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12954563.72 | 7231.39 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148657E+09 | 7231.39 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287291E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.148657E+09 | 7231.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 75646479.37 | 10878.90 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 55891965.74 | 10878.90 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 38903723.59 | 10878.90 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31682.51 | 211.22 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18997763.28 | 10878.90 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.228133E+09 | 10878.90 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.417605E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.228133E+09 | 10878.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 73535663.75 | 7172.86 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 81169432.66 | 7172.86 | 08-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50353228.76 | 7172.86 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3349443.89 | 1952.35 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 31719794.10 | 7172.86 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233298E+09 | 7172.86 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.473426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.233298E+09 | 7172.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118002E+09 | 30372.16 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 39598916.55 | 30372.16 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14917248.48 | 30372.16 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15865562.45 | 30372.16 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201740E+09 | 30372.16 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.390124E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201740E+09 | 30372.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181764E+09 | 13877.43 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.242627E+09 | 13877.43 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190947E+09 | 13877.43 | 27-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1524931.09 | 2292.98 | 21-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35287204.36 | 12160.39 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98174185.59 | 13877.43 | 24-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.467663E+09 | 13877.43 | 04-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.467663E+09 | 13877.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.182507E+09 | 9083.51 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.213861E+09 | 9083.51 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120368E+09 | 9083.51 | 27-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 525966.48 | 1145.24 | 01-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32235231.79 | 9083.51 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 95116628.60 | 9083.51 | 24-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.479903E+09 | 9083.51 | 04-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.479903E+09 | 9083.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.359773E+09 | 13117.37 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.370040E+09 | 13131.60 | 13-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232996E+09 | 13115.40 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1541566.00 | 1944.28 | 21-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 50611778.04 | 12602.11 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219079E+09 | 13046.30 | 24-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.950684E+09 | 13097.34 | 18-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.950684E+09 | 13131.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.308042E+09 | 9024.55 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.356028E+09 | 9024.55 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.222641E+09 | 9024.55 | 27-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4303913.49 | 2531.98 | 21-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 57202616.52 | 9024.55 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200532E+09 | 9024.55 | 24-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.752601E+09 | 9024.55 | 04-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.752601E+09 | 9024.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 8705009.76 | 2096.46 | 02-JAN-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 263998.47 | 500.91 | 28-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29303592.44 | 4243.01 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 441777.48 | 693.40 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168683E+09 | 6407.21 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207397E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168683E+09 | 6407.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 34789760.89 | 3943.18 | 02-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44868856.92 | 2422.90 | 28-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 97509773.81 | 5873.69 | 27-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7460683.08 | 1875.46 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19282074.52 | 3602.56 | 24-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.373301E+09 | 7961.25 | 06-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.577212E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.373301E+09 | 7961.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106867E+09 | 5535.07 | 02-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158716E+09 | 4496.45 | 28-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204343E+09 | 8227.85 | 27-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33752618.64 | 3778.01 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 65569387.03 | 6046.03 | 24-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.664222E+09 | 10814.48 | 06-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.664222E+09 | 10814.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.184766E+11 | 0.183342E+11 | 51341.82 | 31-JAN-17:00 | 51341.82 | 0.00 |
February | 0.00 | 0.00 | 0.414885E+10 | 0.362879E+10 | 22742.03 | 22-FEB-16:10 | 22742.03 | 0.00 |
March | 0.00 | 0.00 | 0.178912E+11 | 0.174640E+11 | 49546.37 | 16-MAR-15:50 | 49546.37 | 0.00 |
April | 0.00 | 0.00 | 0.495465E+11 | 0.494591E+11 | 70513.78 | 14-APR-16:00 | 70513.78 | 0.00 |
May | 0.00 | 0.00 | 0.656547E+11 | 0.656160E+11 | 72785.79 | 31-MAY-16:00 | 72785.79 | 0.00 |
June | 0.00 | 0.00 | 0.876274E+11 | 0.873743E+11 | 94173.29 | 29-JUN-06:03 | 94173.29 | 0.00 |
July | 0.00 | 0.00 | 0.899113E+11 | 0.834805E+11 | 135399.87 | 15-JUL-06:03 | 60763.55 | 0.00 |
August | 0.00 | 0.00 | 0.936116E+11 | 0.864850E+11 | 133404.91 | 01-AUG-04:03 | 68746.45 | 0.00 |
September | 0.00 | 0.00 | 0.812670E+11 | 0.740676E+11 | 129378.55 | 08-SEP-04:02 | 85234.74 | 0.00 |
October | 0.00 | 0.00 | 0.460210E+11 | 0.446438E+11 | 105709.77 | 03-OCT-06:03 | 56227.52 | 0.00 |
November | 0.00 | 0.00 | 0.208365E+11 | 0.195607E+11 | 59139.41 | 01-NOV-16:00 | 59139.41 | 0.00 |
December | 0.00 | 0.00 | 0.876688E+10 | 0.873582E+10 | 45586.35 | 22-DEC-16:30 | 45586.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.583760E+12 | 0.558850E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.414885E+10 | 0.362879E+10 | 22742.03 | 22742.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.936116E+11 | 0.873743E+11 | 135399.87 | 94173.29 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.153005E+11 | 0.151552E+11 | 43264.20 | 31-JAN-16:30 | 43264.20 | 0.00 |
February | 0.00 | 0.00 | 0.349142E+10 | 0.296975E+10 | 21277.56 | 22-FEB-16:00 | 21277.56 | 0.00 |
March | 0.00 | 0.00 | 0.153215E+11 | 0.148250E+11 | 46341.36 | 16-MAR-15:40 | 46341.36 | 0.00 |
April | 0.00 | 0.00 | 0.443534E+11 | 0.442778E+11 | 65497.48 | 14-APR-15:20 | 65497.48 | 0.00 |
May | 0.00 | 0.00 | 0.592859E+11 | 0.592587E+11 | 66364.82 | 18-MAY-15:30 | 66364.82 | 0.00 |
June | 0.00 | 0.00 | 0.801724E+11 | 0.800178E+11 | 84258.14 | 29-JUN-04:02 | 84258.14 | 0.00 |
July | 0.00 | 0.00 | 0.781421E+11 | 0.732269E+11 | 125051.45 | 14-JUL-05:03 | 49721.56 | 0.00 |
August | 0.00 | 0.00 | 0.792585E+11 | 0.740725E+11 | 121383.20 | 01-AUG-04:03 | 60340.98 | 0.00 |
September | 0.00 | 0.00 | 0.662385E+11 | 0.610238E+11 | 118722.30 | 02-SEP-05:03 | 62726.59 | 0.00 |
October | 0.00 | 0.00 | 0.370254E+11 | 0.358896E+11 | 84426.32 | 02-OCT-04:02 | 83653.13 | 0.00 |
November | 0.00 | 0.00 | 0.159651E+11 | 0.149077E+11 | 51099.53 | 01-NOV-15:30 | 51099.53 | 0.00 |
December | 0.00 | 0.00 | 0.699112E+10 | 0.694675E+10 | 37154.00 | 22-DEC-16:30 | 37154.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.501546E+12 | 0.482571E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.349142E+10 | 0.296975E+10 | 21277.56 | 21277.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.801724E+11 | 0.800178E+11 | 125051.45 | 84258.14 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.150653E+11 | 0.148599E+11 | 47000.22 | 31-JAN-16:20 | 47000.22 | 0.00 |
February | 0.00 | 0.00 | 0.354421E+10 | 0.293063E+10 | 21457.72 | 22-FEB-16:00 | 21457.72 | 0.00 |
March | 0.00 | 0.00 | 0.159785E+11 | 0.152876E+11 | 53076.74 | 16-MAR-15:30 | 53076.74 | 0.00 |
April | 0.00 | 0.00 | 0.484437E+11 | 0.483197E+11 | 76240.85 | 14-APR-15:30 | 76240.85 | 0.00 |
May | 0.00 | 0.00 | 0.649459E+11 | 0.648961E+11 | 77059.37 | 18-MAY-15:40 | 77059.37 | 0.00 |
June | 0.00 | 0.00 | 0.892306E+11 | 0.890263E+11 | 93747.43 | 28-JUN-15:00 | 93747.43 | 0.00 |
July | 0.00 | 0.00 | 0.859845E+11 | 0.808532E+11 | 131568.45 | 24-JUL-04:02 | 85763.27 | 0.00 |
August | 0.00 | 0.00 | 0.861538E+11 | 0.807472E+11 | 136760.59 | 01-AUG-04:03 | 66235.26 | 0.00 |
September | 0.00 | 0.00 | 0.706321E+11 | 0.652400E+11 | 106783.91 | 05-SEP-06:03 | 43585.54 | 0.00 |
October | 0.00 | 0.00 | 0.382625E+11 | 0.369912E+11 | 85906.80 | 02-OCT-04:02 | 85723.47 | 0.00 |
November | 0.00 | 0.00 | 0.156423E+11 | 0.145156E+11 | 57409.57 | 01-NOV-15:30 | 57409.57 | 0.00 |
December | 0.00 | 0.00 | 0.677516E+10 | 0.670870E+10 | 38897.30 | 22-DEC-15:40 | 38897.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.540659E+12 | 0.520376E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.354421E+10 | 0.293063E+10 | 21457.72 | 21457.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.892306E+11 | 0.890263E+11 | 136760.59 | 93747.43 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1574.99 | 5406.29 | 26-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1570.60 | 5429.80 | 02-FEB-12:06 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1598.08 | 5253.83 | 02-MAR-12:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1386.34 | 4877.95 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1316.76 | 4494.32 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1247.09 | 4113.76 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 1101.50 | 3848.59 | 03-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 1222.55 | 3941.68 | 28-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1216.70 | 4266.39 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1322.65 | 4685.29 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1459.27 | 5076.69 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1490.83 | 5329.59 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 1374.54 | ||||
Minimum of Months | 0.00 | 0.00 | 1101.50 | 3848.59 | ||
Maximum of Months | 0.00 | 0.00 | 1598.08 | 5429.80 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.268346E+10 | 0.36 | 5123.05 | 27-JAN-17:00 | 1.09 |
February | 0.187060E+10 | 0.32 | 3565.91 | 01-FEB-07:02 | 0.88 |
March | 0.261418E+10 | 0.36 | 4763.28 | 20-MAR-14:30 | 1.04 |
April | 0.457930E+10 | 0.48 | 8686.66 | 25-APR-16:00 | 1.50 |
May | 0.582793E+10 | 0.54 | 9038.45 | 18-MAY-16:00 | 1.54 |
June | 0.763772E+10 | 0.66 | 12491.05 | 05-JUN-06:03 | 1.89 |
July | 0.707325E+10 | 0.62 | 13235.62 | 10-JUL-04:02 | 1.95 |
August | 0.719586E+10 | 0.62 | 13235.62 | 15-AUG-04:02 | 1.95 |
September | 0.612868E+10 | 0.57 | 13235.62 | 07-SEP-04:02 | 1.94 |
October | 0.444259E+10 | 0.46 | 12640.61 | 02-OCT-06:03 | 1.89 |
November | 0.314666E+10 | 0.39 | 6306.94 | 02-NOV-16:00 | 1.22 |
December | 0.230155E+10 | 0.34 | 4540.45 | 22-DEC-16:50 | 1.02 |
Annual Sum or Average | 0.555018E+11 | 0.48 | |||
Minimum of Months | 0.187060E+10 | 0.32 | 3565.91 | 0.88 | |
Maximum of Months | 0.763772E+10 | 0.66 | 13235.62 | 1.95 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.202753E+10 | 0.34 | 4227.30 | 27-JAN-16:40 | 1.05 |
February | 0.148048E+10 | 0.31 | 2898.11 | 22-FEB-16:30 | 0.84 |
March | 0.207101E+10 | 0.35 | 4681.67 | 16-MAR-15:30 | 1.10 |
April | 0.417441E+10 | 0.49 | 8196.50 | 14-APR-15:20 | 1.56 |
May | 0.533983E+10 | 0.55 | 8305.81 | 08-MAY-16:00 | 1.58 |
June | 0.737190E+10 | 0.69 | 11751.71 | 29-JUN-04:02 | 1.96 |
July | 0.654156E+10 | 0.62 | 11751.71 | 10-JUL-04:02 | 1.95 |
August | 0.673655E+10 | 0.63 | 11751.71 | 16-AUG-04:02 | 1.95 |
September | 0.530004E+10 | 0.54 | 11751.71 | 18-SEP-04:02 | 1.96 |
October | 0.344203E+10 | 0.42 | 11751.71 | 02-OCT-04:02 | 1.94 |
November | 0.218363E+10 | 0.35 | 5140.70 | 02-NOV-15:30 | 1.16 |
December | 0.169995E+10 | 0.32 | 3620.19 | 22-DEC-16:40 | 0.96 |
Annual Sum or Average | 0.483689E+11 | 0.47 | |||
Minimum of Months | 0.148048E+10 | 0.31 | 2898.11 | 0.84 | |
Maximum of Months | 0.737190E+10 | 0.69 | 11751.71 | 1.96 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.193787E+10 | 0.32 | 3616.21 | 27-JAN-16:30 | 0.88 |
February | 0.146158E+10 | 0.30 | 2594.78 | 22-FEB-16:30 | 0.73 |
March | 0.199193E+10 | 0.34 | 4521.29 | 16-MAR-15:30 | 0.99 |
April | 0.393717E+10 | 0.44 | 8299.07 | 14-APR-15:40 | 1.43 |
May | 0.508640E+10 | 0.50 | 8397.45 | 18-MAY-15:50 | 1.44 |
June | 0.731663E+10 | 0.63 | 11338.24 | 28-JUN-15:00 | 1.73 |
July | 0.636251E+10 | 0.57 | 12291.35 | 22-JUL-04:02 | 1.81 |
August | 0.650284E+10 | 0.57 | 10769.36 | 14-AUG-15:20 | 1.66 |
September | 0.499791E+10 | 0.49 | 9772.26 | 06-SEP-15:50 | 1.56 |
October | 0.315177E+10 | 0.39 | 9701.31 | 02-OCT-04:02 | 1.56 |
November | 0.199135E+10 | 0.32 | 4709.04 | 02-NOV-15:00 | 1.01 |
December | 0.167368E+10 | 0.31 | 3154.31 | 22-DEC-16:30 | 0.81 |
Annual Sum or Average | 0.464117E+11 | 0.43 | |||
Minimum of Months | 0.146158E+10 | 0.30 | 2594.78 | 0.73 | |
Maximum of Months | 0.731663E+10 | 0.63 | 12291.35 | 1.81 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 56.79 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 56.88 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 56.38 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.32 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.11 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.48 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.04 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.09 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 56.76 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.12 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.84 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 56.36 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.32 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.12 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.69 | 57.69 | 1574.99 | 5406.29 | 26-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.26 | 57.26 | 1570.60 | 5429.80 | 02-FEB-12:06 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.16 | 57.16 | 1598.08 | 5253.83 | 02-MAR-12:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.63 | 57.63 | 1386.34 | 4877.95 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.09 | 58.09 | 1316.76 | 4494.32 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.67 | 56.67 | 1247.09 | 4113.76 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 57.18 | 57.18 | 1101.50 | 3848.59 | 03-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 58.19 | 58.19 | 1222.55 | 3941.68 | 28-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.95 | 56.95 | 1216.70 | 4266.39 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.60 | 56.60 | 1322.65 | 4685.29 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.15 | 57.15 | 1459.27 | 5076.69 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.04 | 57.04 | 1490.83 | 5329.59 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 1374.54 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.60 | 56.60 | 1101.50 | 3848.59 | ||
Maximum of Months | 0.00 | 0.00 | 58.19 | 58.19 | 1598.08 | 5429.80 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.817246E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.391182E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.820698E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.180647E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.242902E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.351933E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.336527E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.347082E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.288195E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.170049E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.875892E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.560827E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.226392E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.391182E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.351933E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.618579E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.265423E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.620292E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.161494E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.220326E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.326127E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.296287E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.300509E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.238795E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.134321E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.632188E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.425267E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.193403E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.265423E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.326127E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.700529E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.366585E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.696241E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.171426E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.235537E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.356451E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.319218E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.320334E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.249725E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.137687E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.667177E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.633816E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.209681E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.366585E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.356451E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.268346E+10 | 0.184766E+11 | 0.826501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187060E+10 | 0.414885E+10 | 0.905763E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261418E+10 | 0.178912E+11 | 0.100992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.457930E+10 | 0.495465E+11 | 0.146502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.582793E+10 | 0.656547E+11 | 7584402.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.763772E+10 | 0.876274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.707325E+10 | 0.899113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.719586E+10 | 0.936116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.612868E+10 | 0.812670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.444259E+10 | 0.460210E+11 | 0.288475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.314666E+10 | 0.208365E+11 | 0.403828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230155E+10 | 0.876688E+10 | 0.119906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.555018E+11 | 0.583760E+12 | 0.478764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.187060E+10 | 0.414885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.763772E+10 | 0.936116E+11 | 0.119906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.202753E+10 | 0.153005E+11 | 0.275478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148048E+10 | 0.349142E+10 | 0.257728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207101E+10 | 0.153215E+11 | 0.246387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.417441E+10 | 0.443534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.533983E+10 | 0.592859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.737190E+10 | 0.801724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.654156E+10 | 0.781421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.673655E+10 | 0.792585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.530004E+10 | 0.662385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.344203E+10 | 0.370254E+11 | 12588384.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.218363E+10 | 0.159651E+11 | 86490807.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169995E+10 | 0.699112E+10 | 0.108374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.483689E+11 | 0.501546E+12 | 0.196241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148048E+10 | 0.349142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.737190E+10 | 0.801724E+11 | 0.108374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.193787E+10 | 0.150653E+11 | 0.125695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146158E+10 | 0.354421E+10 | 0.138087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199193E+10 | 0.159785E+11 | 0.986212E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.393717E+10 | 0.484437E+11 | 7896377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.508640E+10 | 0.649459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.731663E+10 | 0.892306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.636251E+10 | 0.859845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.650284E+10 | 0.861538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.499791E+10 | 0.706321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.315177E+10 | 0.382625E+11 | 0.209089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.199135E+10 | 0.156423E+11 | 0.694337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167368E+10 | 0.677516E+10 | 0.351681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.464117E+11 | 0.540659E+12 | 0.805217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146158E+10 | 0.354421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.731663E+10 | 0.892306E+11 | 0.351681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.268346E+10 | 0.00 | 0.00 | 0.00 | 0.467120E+10 | 0.817796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187060E+10 | 0.00 | 0.00 | 0.00 | 0.113572E+10 | 0.905499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261418E+10 | 0.00 | 0.00 | 0.00 | 0.461218E+10 | 0.980616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.457930E+10 | 0.00 | 0.00 | 0.00 | 0.133389E+11 | 0.146502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.582793E+10 | 0.00 | 0.00 | 0.00 | 0.184547E+11 | 7584402.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.763772E+10 | 0.00 | 0.00 | 0.00 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.707325E+10 | 0.00 | 0.00 | 0.00 | 0.265795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.719586E+10 | 0.00 | 0.00 | 0.00 | 0.275123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.612868E+10 | 0.00 | 0.00 | 0.00 | 0.226908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.444259E+10 | 0.00 | 0.00 | 0.00 | 0.122739E+11 | 0.288475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.314666E+10 | 0.00 | 0.00 | 0.00 | 0.520887E+10 | 0.403387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230155E+10 | 0.00 | 0.00 | 0.00 | 0.227635E+10 | 0.103038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.555018E+11 | 0.00 | 0.00 | 0.00 | 0.166310E+12 | 0.458024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.187060E+10 | 0.00 | 0.00 | 0.00 | 0.113572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.763772E+10 | 0.00 | 0.00 | 0.00 | 0.275555E+11 | 0.103038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.202753E+10 | 0.00 | 0.00 | 0.00 | 0.391758E+10 | 0.240688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148048E+10 | 0.00 | 0.00 | 0.00 | 0.960898E+09 | 0.212859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207101E+10 | 0.00 | 0.00 | 0.00 | 0.398304E+10 | 0.148877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.417441E+10 | 0.00 | 0.00 | 0.00 | 0.119750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.533983E+10 | 0.00 | 0.00 | 0.00 | 0.166928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.737190E+10 | 0.00 | 0.00 | 0.00 | 0.252408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.654156E+10 | 0.00 | 0.00 | 0.00 | 0.230871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.673655E+10 | 0.00 | 0.00 | 0.00 | 0.233143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.530004E+10 | 0.00 | 0.00 | 0.00 | 0.185794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.344203E+10 | 0.00 | 0.00 | 0.00 | 0.998491E+10 | 5127701.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.218363E+10 | 0.00 | 0.00 | 0.00 | 0.407104E+10 | 67208733.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169995E+10 | 0.00 | 0.00 | 0.00 | 0.184228E+10 | 0.710437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.483689E+11 | 0.00 | 0.00 | 0.00 | 0.143649E+12 | 0.138520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148048E+10 | 0.00 | 0.00 | 0.00 | 0.960898E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.737190E+10 | 0.00 | 0.00 | 0.00 | 0.252408E+11 | 0.710437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.193787E+10 | 0.00 | 0.00 | 0.00 | 0.391733E+10 | 0.115009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146158E+10 | 0.00 | 0.00 | 0.00 | 0.982119E+09 | 0.122215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199193E+10 | 0.00 | 0.00 | 0.00 | 0.418861E+10 | 0.781869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.393717E+10 | 0.00 | 0.00 | 0.00 | 0.131975E+11 | 7896377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.508640E+10 | 0.00 | 0.00 | 0.00 | 0.184673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.731663E+10 | 0.00 | 0.00 | 0.00 | 0.283284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.636251E+10 | 0.00 | 0.00 | 0.00 | 0.255593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.650284E+10 | 0.00 | 0.00 | 0.00 | 0.255306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.499791E+10 | 0.00 | 0.00 | 0.00 | 0.199746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.315177E+10 | 0.00 | 0.00 | 0.00 | 0.104416E+11 | 0.175337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.199135E+10 | 0.00 | 0.00 | 0.00 | 0.405166E+10 | 0.628767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167368E+10 | 0.00 | 0.00 | 0.00 | 0.181189E+10 | 0.285259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.464117E+11 | 0.00 | 0.00 | 0.00 | 0.156451E+12 | 0.681870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146158E+10 | 0.00 | 0.00 | 0.00 | 0.982119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.731663E+10 | 0.00 | 0.00 | 0.00 | 0.283284E+11 | 0.285259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111745E+10 | 3278073.13 | 0.00 | 36834881.33 | 9696609.62 | 0.00 | 0.127096E+11 | 0.00 | 0.93 |
February | 0.831275E+09 | 0.00 | 0.00 | 34893447.31 | 2707183.22 | 0.00 | 0.159295E+11 | 0.00 | 0.88 |
March | 0.693441E+09 | 17372162.98 | 0.00 | 41177570.25 | 667930.82 | 0.00 | 0.141792E+11 | 0.00 | 0.98 |
April | 0.304588E+09 | 0.640447E+09 | 0.00 | 27122652.32 | 55851740.42 | 0.00 | 0.545006E+10 | 0.00 | 0.69 |
May | 0.183090E+09 | 0.132434E+10 | 0.00 | 17177432.11 | 41824028.30 | 0.00 | 0.225648E+10 | 0.00 | 0.51 |
June | 97274208.06 | 0.343921E+10 | 0.00 | 4464274.04 | 86074782.70 | 0.00 | 0.535003E+09 | 0.00 | 0.35 |
July | 64289215.04 | 0.466295E+10 | 0.00 | 1300059.90 | 0.174974E+09 | 0.00 | 0.173289E+09 | 0.00 | 0.32 |
August | 42920389.73 | 0.474052E+10 | 0.00 | 2452279.61 | 0.126279E+09 | 0.00 | 0.225117E+09 | 0.00 | 0.40 |
September | 62114657.08 | 0.323982E+10 | 0.00 | 9150240.75 | 0.450920E+09 | 0.00 | 0.780088E+09 | 0.00 | 0.48 |
October | 0.375845E+09 | 0.725809E+09 | 0.00 | 33366221.04 | 44892034.92 | 0.00 | 0.950168E+10 | 0.00 | 0.86 |
November | 0.836853E+09 | 24917103.82 | 0.00 | 43858366.80 | 5949360.35 | 0.00 | 0.145295E+11 | 0.00 | 1.04 |
December | 0.994678E+09 | 1047678.38 | 0.00 | 38352805.93 | 200130.88 | 0.00 | 0.158854E+11 | 0.00 | 0.84 |
Annual Sum or Average | 0.560381E+10 | 0.188197E+11 | 0.00 | 0.290150E+09 | 0.100004E+10 | 0.00 | 0.921549E+11 | 0.00 | 0.69 |
Minimum of Months | 42920389.73 | 0.00 | 0.00 | 1300059.90 | 200130.88 | 0.00 | 0.173289E+09 | 0.00 | 0.32 |
Maximum of Months | 0.111745E+10 | 0.474052E+10 | 0.00 | 43858366.80 | 0.450920E+09 | 0.00 | 0.159295E+11 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.320282E+10 | 131314.70 | 0.00 | 13561094.45 | 4994254.41 | 6324105.51 | 0.524748E+10 | 0.00 | 0.56 |
February | 0.430037E+10 | 0.00 | 0.00 | 10272232.75 | 3277529.92 | 0.00 | 0.606564E+10 | 0.00 | 0.55 |
March | 0.299247E+10 | 2979710.17 | 0.00 | 17070029.60 | 752608.51 | 0.00 | 0.640589E+10 | 0.00 | 0.61 |
April | 0.696006E+09 | 0.413207E+09 | 0.00 | 17865788.62 | 92540332.86 | 0.00 | 0.333309E+10 | 0.00 | 0.49 |
May | 0.322920E+09 | 0.963778E+09 | 0.00 | 12619692.01 | 48009806.29 | 0.00 | 0.154779E+10 | 0.00 | 0.40 |
June | 0.114130E+09 | 0.291102E+10 | 0.00 | 3379488.04 | 86863126.63 | 0.00 | 0.426146E+09 | 0.00 | 0.30 |
July | 69486012.44 | 0.376991E+10 | 0.00 | 1009668.73 | 0.155457E+09 | 0.00 | 0.125132E+09 | 0.00 | 0.29 |
August | 46390979.41 | 0.376030E+10 | 0.00 | 1512844.39 | 0.108359E+09 | 0.00 | 0.154538E+09 | 0.00 | 0.34 |
September | 86172826.90 | 0.254846E+10 | 0.00 | 6841903.93 | 0.230521E+09 | 0.00 | 0.483783E+09 | 0.00 | 0.38 |
October | 0.949260E+09 | 0.585702E+09 | 0.00 | 17942847.57 | 25051103.20 | 0.00 | 0.509509E+10 | 0.00 | 0.56 |
November | 0.251721E+10 | 12762461.47 | 0.00 | 18627616.66 | 17952687.07 | 0.00 | 0.666047E+10 | 0.00 | 0.62 |
December | 0.506941E+10 | 1371948.40 | 0.00 | 8486856.73 | 1490143.08 | 0.00 | 0.481147E+10 | 0.00 | 0.50 |
Annual Sum or Average | 0.203666E+11 | 0.149696E+11 | 0.00 | 0.129190E+09 | 0.775268E+09 | 6324105.51 | 0.403565E+11 | 0.00 | 0.47 |
Minimum of Months | 46390979.41 | 0.00 | 0.00 | 1009668.73 | 752608.51 | 0.00 | 0.125132E+09 | 0.00 | 0.29 |
Maximum of Months | 0.506941E+10 | 0.376991E+10 | 0.00 | 18627616.66 | 0.230521E+09 | 6324105.51 | 0.666047E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.432312E+10 | 0.00 | 0.00 | 8082294.86 | 210729.49 | 31844962.34 | 0.320097E+10 | 0.00 | 0.57 |
February | 0.551993E+10 | 0.00 | 0.00 | 5463122.27 | 3916612.19 | 12780486.30 | 0.401198E+10 | 0.00 | 0.52 |
March | 0.411044E+10 | 1190561.51 | 0.00 | 11857962.41 | 1224547.20 | 2487267.06 | 0.448020E+10 | 0.00 | 0.60 |
April | 0.105700E+10 | 0.278069E+09 | 0.00 | 16810630.63 | 69328793.80 | 0.00 | 0.226672E+10 | 0.00 | 0.47 |
May | 0.490660E+09 | 0.705446E+09 | 0.00 | 13649440.00 | 33598501.41 | 0.00 | 0.828941E+09 | 0.00 | 0.36 |
June | 0.140797E+09 | 0.260588E+10 | 0.00 | 2449281.50 | 83274362.97 | 0.00 | 0.235590E+09 | 0.00 | 0.29 |
July | 63165284.38 | 0.351145E+10 | 0.00 | 817491.52 | 0.202984E+09 | 0.00 | 64259041.48 | 0.00 | 0.27 |
August | 60426477.36 | 0.355731E+10 | 0.00 | 860743.92 | 0.133082E+09 | 0.00 | 57495789.89 | 0.00 | 0.32 |
September | 0.117134E+09 | 0.236139E+10 | 0.00 | 5922331.05 | 0.291634E+09 | 0.00 | 0.228653E+09 | 0.00 | 0.35 |
October | 0.157133E+10 | 0.484466E+09 | 0.00 | 13621771.41 | 66195468.57 | 0.00 | 0.339510E+10 | 0.00 | 0.51 |
November | 0.376797E+10 | 12840771.64 | 0.00 | 12056430.72 | 32203575.23 | 1233315.92 | 0.430360E+10 | 0.00 | 0.59 |
December | 0.646222E+10 | 0.00 | 0.00 | 3551728.86 | 4229138.64 | 73280792.11 | 0.240262E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.276842E+11 | 0.135180E+11 | 0.00 | 95143229.16 | 0.921882E+09 | 0.121627E+09 | 0.254761E+11 | 0.00 | 0.44 |
Minimum of Months | 60426477.36 | 0.00 | 0.00 | 817491.52 | 210729.49 | 0.00 | 57495789.89 | 0.00 | 0.27 |
Maximum of Months | 0.646222E+10 | 0.355731E+10 | 0.00 | 16810630.63 | 0.291634E+09 | 73280792.11 | 0.448020E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131143E+10 | 0.00 | 0.00 | 645524.93 | 49278.79 | 0.140693E+09 | 0.230922E+09 | 0.00 | 0.58 |
February | 0.182291E+10 | 0.00 | 0.00 | 160844.02 | 915894.19 | 0.128929E+09 | 0.171061E+09 | 0.00 | 0.55 |
March | 0.134953E+10 | 292601.56 | 0.00 | 1658533.76 | 286358.62 | 0.104572E+09 | 0.453443E+09 | 0.00 | 0.63 |
April | 0.364178E+09 | 90995864.72 | 0.00 | 3493485.70 | 14177886.01 | 257620.55 | 0.343258E+09 | 0.00 | 0.52 |
May | 0.164880E+09 | 0.249988E+09 | 0.00 | 3162820.41 | 7970558.33 | 0.00 | 0.135081E+09 | 0.00 | 0.47 |
June | 46469041.42 | 0.103064E+10 | 0.00 | 609449.82 | 16085989.30 | 0.00 | 42930481.31 | 0.00 | 0.47 |
July | 15717202.88 | 0.121900E+10 | 0.00 | 198799.28 | 49208260.97 | 0.00 | 13828191.40 | 0.00 | 0.42 |
August | 19397985.97 | 0.111875E+10 | 0.00 | 159538.88 | 32791272.11 | 0.00 | 6748135.62 | 0.00 | 0.46 |
September | 46059877.24 | 0.706400E+09 | 0.00 | 1393916.47 | 72813719.62 | 0.00 | 38529653.72 | 0.00 | 0.45 |
October | 0.689436E+09 | 0.134785E+09 | 0.00 | 2135192.76 | 14276865.84 | 21800731.23 | 0.332639E+09 | 0.00 | 0.53 |
November | 0.122388E+10 | 1560578.52 | 0.00 | 1293464.58 | 8930955.64 | 87163209.08 | 0.397606E+09 | 0.00 | 0.59 |
December | 0.159996E+10 | 0.00 | 0.00 | 121311.58 | 988978.06 | 0.386707E+09 | 70266063.07 | 0.00 | 0.52 |
Annual Sum or Average | 0.865385E+10 | 0.455241E+10 | 0.00 | 15032882.18 | 0.218496E+09 | 0.870123E+09 | 0.223631E+10 | 0.00 | 0.52 |
Minimum of Months | 15717202.88 | 0.00 | 0.00 | 121311.58 | 49278.79 | 0.00 | 6748135.62 | 0.00 | 0.42 |
Maximum of Months | 0.182291E+10 | 0.121900E+10 | 0.00 | 3493485.70 | 72813719.62 | 0.386707E+09 | 0.453443E+09 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.798177E+09 | 0.00 | 0.00 | 1506608.00 | 42778.05 | 71994971.09 | 0.652724E+09 | 0.00 | 0.84 |
February | 0.113055E+10 | 0.00 | 0.00 | 787971.61 | 795071.51 | 70910893.35 | 0.685296E+09 | 0.00 | 0.77 |
March | 0.818222E+09 | 713691.61 | 0.00 | 2728145.69 | 56331.98 | 52444306.35 | 0.992743E+09 | 0.00 | 0.97 |
April | 0.207366E+09 | 87400555.76 | 0.00 | 5319738.07 | 10979136.68 | 234810.68 | 0.734557E+09 | 0.00 | 1.02 |
May | 0.107132E+09 | 0.198168E+09 | 0.00 | 4598612.73 | 6576842.22 | 0.00 | 0.295189E+09 | 0.00 | 0.84 |
June | 36212030.45 | 0.853576E+09 | 0.00 | 746756.01 | 13403662.95 | 0.00 | 51522158.12 | 0.00 | 0.69 |
July | 13874358.07 | 0.108693E+10 | 0.00 | 233651.22 | 44878044.12 | 0.00 | 16818176.24 | 0.00 | 0.60 |
August | 16152642.35 | 0.104964E+10 | 0.00 | 156304.33 | 29375105.72 | 0.00 | 8646559.14 | 0.00 | 0.67 |
September | 35427726.20 | 0.669675E+09 | 0.00 | 1283511.61 | 55357558.41 | 0.00 | 38606026.77 | 0.00 | 0.68 |
October | 0.388377E+09 | 0.127255E+09 | 0.00 | 3087664.13 | 12597079.86 | 12239550.07 | 0.709129E+09 | 0.00 | 0.88 |
November | 0.809319E+09 | 679090.73 | 0.00 | 2089476.81 | 8395783.16 | 31933445.10 | 0.730451E+09 | 0.00 | 0.87 |
December | 0.135925E+10 | 0.00 | 0.00 | 388821.47 | 858514.32 | 0.201659E+09 | 0.221678E+09 | 0.00 | 0.71 |
Annual Sum or Average | 0.572006E+10 | 0.407404E+10 | 0.00 | 22927261.68 | 0.183316E+09 | 0.441417E+09 | 0.513736E+10 | 0.00 | 0.79 |
Minimum of Months | 13874358.07 | 0.00 | 0.00 | 156304.33 | 42778.05 | 0.00 | 8646559.14 | 0.00 | 0.60 |
Maximum of Months | 0.135925E+10 | 0.108693E+10 | 0.00 | 5319738.07 | 55357558.41 | 0.201659E+09 | 0.992743E+09 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.705414E+09 | 200601.08 | 0.00 | 10339729.05 | 0.00 | 62347095.63 | 0.303175E+10 | 0.00 | 1.52 |
February | 0.103836E+10 | 0.00 | 0.00 | 5514091.59 | 1004612.12 | 88996879.68 | 0.297319E+10 | 0.00 | 1.03 |
March | 0.952964E+09 | 872261.99 | 0.00 | 5980615.80 | 88369.01 | 82546158.19 | 0.188342E+10 | 0.00 | 1.02 |
April | 0.381342E+09 | 0.143165E+09 | 0.00 | 5473036.67 | 14128005.44 | 282574.92 | 0.549125E+09 | 0.00 | 0.72 |
May | 0.211064E+09 | 0.272811E+09 | 0.00 | 3264309.74 | 8951261.51 | 0.00 | 0.111399E+09 | 0.00 | 0.50 |
June | 61909094.37 | 0.100100E+10 | 0.00 | 420191.03 | 19120134.28 | 0.00 | 26209044.67 | 0.00 | 0.45 |
July | 20241317.01 | 0.122005E+10 | 0.00 | 162443.96 | 59723650.16 | 0.00 | 9726692.44 | 0.00 | 0.43 |
August | 23617515.73 | 0.127793E+10 | 0.00 | 149626.26 | 37375941.63 | 0.00 | 4752129.96 | 0.00 | 0.52 |
September | 49425913.67 | 0.954121E+09 | 0.00 | 2005546.56 | 72953139.74 | 0.00 | 53701779.36 | 0.00 | 0.59 |
October | 0.432981E+09 | 0.228148E+09 | 0.00 | 7724597.39 | 12872495.29 | 14064773.10 | 0.156890E+10 | 0.00 | 1.04 |
November | 0.731801E+09 | 3369484.30 | 0.00 | 9045322.30 | 8409661.98 | 30805413.26 | 0.293577E+10 | 0.00 | 1.36 |
December | 0.913866E+09 | 244640.38 | 0.00 | 7516652.83 | 906626.87 | 0.165158E+09 | 0.305876E+10 | 0.00 | 1.16 |
Annual Sum or Average | 0.552299E+10 | 0.510191E+10 | 0.00 | 57596163.19 | 0.235534E+09 | 0.444201E+09 | 0.162067E+11 | 0.00 | 0.86 |
Minimum of Months | 20241317.01 | 0.00 | 0.00 | 149626.26 | 0.00 | 0.00 | 4752129.96 | 0.00 | 0.43 |
Maximum of Months | 0.103836E+10 | 0.127793E+10 | 0.00 | 10339729.05 | 72953139.74 | 0.165158E+09 | 0.305876E+10 | 0.00 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117712E+10 | 96018.70 | 0.00 | 2022815.62 | 0.00 | 0.122965E+09 | 0.556205E+09 | 0.00 | 1.09 |
February | 0.151125E+10 | 0.00 | 0.00 | 1153977.56 | 903374.42 | 0.122681E+09 | 0.687577E+09 | 0.00 | 0.95 |
March | 0.126201E+10 | 297466.13 | 0.00 | 2412710.10 | 239074.74 | 98816784.86 | 0.685159E+09 | 0.00 | 1.11 |
April | 0.379500E+09 | 0.115608E+09 | 0.00 | 3852854.87 | 7252335.20 | 520895.10 | 0.358636E+09 | 0.00 | 0.89 |
May | 0.200030E+09 | 0.276405E+09 | 0.00 | 2266789.94 | 2642840.71 | 0.00 | 70771708.34 | 0.00 | 0.68 |
June | 60082282.43 | 0.929065E+09 | 0.00 | 234710.20 | 13746427.19 | 0.00 | 17429442.88 | 0.00 | 0.63 |
July | 22551619.31 | 0.949853E+09 | 0.00 | 95692.47 | 53025352.98 | 0.00 | 3883592.18 | 0.00 | 0.53 |
August | 22241098.85 | 0.888871E+09 | 0.00 | 102566.38 | 45079906.17 | 0.00 | 3053373.64 | 0.00 | 0.60 |
September | 47595411.47 | 0.569301E+09 | 0.00 | 1187660.66 | 78636612.58 | 0.00 | 31194294.71 | 0.00 | 0.61 |
October | 0.635427E+09 | 0.107073E+09 | 0.00 | 2827844.48 | 20855761.89 | 23035622.50 | 0.478376E+09 | 0.00 | 0.89 |
November | 0.112461E+10 | 1223699.13 | 0.00 | 2343609.57 | 9273493.83 | 83212016.61 | 0.695207E+09 | 0.00 | 1.07 |
December | 0.134691E+10 | 0.00 | 0.00 | 960294.11 | 975459.26 | 0.322674E+09 | 0.480716E+09 | 0.00 | 0.88 |
Annual Sum or Average | 0.778934E+10 | 0.383779E+10 | 0.00 | 19461525.95 | 0.232631E+09 | 0.773904E+09 | 0.406821E+10 | 0.00 | 0.83 |
Minimum of Months | 22241098.85 | 0.00 | 0.00 | 95692.47 | 0.00 | 0.00 | 3053373.64 | 0.00 | 0.53 |
Maximum of Months | 0.151125E+10 | 0.949853E+09 | 0.00 | 3852854.87 | 78636612.58 | 0.322674E+09 | 0.695207E+09 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150898E+10 | 172678.46 | 0.00 | 391468.63 | 2338230.45 | 37326952.04 | 0.146005E+09 | 0.00 | 0.52 |
February | 0.198456E+10 | 0.00 | 0.00 | 18945.52 | 570341.65 | 37570178.35 | 35551402.55 | 0.00 | 0.50 |
March | 0.155789E+10 | 1753205.07 | 0.00 | 629489.69 | 396005.18 | 29372843.61 | 0.174051E+09 | 0.00 | 0.53 |
April | 0.387159E+09 | 0.111085E+09 | 0.00 | 1934302.99 | 16802787.32 | 0.00 | 0.271984E+09 | 0.00 | 0.42 |
May | 0.168743E+09 | 0.281029E+09 | 0.00 | 1540765.77 | 8898520.51 | 0.00 | 0.149463E+09 | 0.00 | 0.37 |
June | 46153475.60 | 0.954697E+09 | 0.00 | 533207.57 | 20543714.21 | 0.00 | 63516090.20 | 0.00 | 0.39 |
July | 22193360.57 | 0.123052E+10 | 0.00 | 197252.20 | 42904872.16 | 0.00 | 22981235.78 | 0.00 | 0.38 |
August | 19622899.78 | 0.117274E+10 | 0.00 | 256055.53 | 30566359.95 | 0.00 | 24212950.88 | 0.00 | 0.43 |
September | 34328848.12 | 0.794229E+09 | 0.00 | 1403260.22 | 99203069.88 | 0.00 | 98511815.62 | 0.00 | 0.47 |
October | 0.533888E+09 | 0.157364E+09 | 0.00 | 2519281.28 | 10835700.99 | 0.00 | 0.588793E+09 | 0.00 | 0.54 |
November | 0.118771E+10 | 1362233.81 | 0.00 | 2099125.42 | 3861399.98 | 373943.84 | 0.618539E+09 | 0.00 | 0.56 |
December | 0.195752E+10 | 0.00 | 0.00 | 166202.66 | 172639.38 | 58939178.00 | 0.104700E+09 | 0.00 | 0.49 |
Annual Sum or Average | 0.940875E+10 | 0.470495E+10 | 0.00 | 11689357.48 | 0.237094E+09 | 0.163583E+09 | 0.229831E+10 | 0.00 | 0.47 |
Minimum of Months | 19622899.78 | 0.00 | 0.00 | 18945.52 | 172639.38 | 0.00 | 22981235.78 | 0.00 | 0.37 |
Maximum of Months | 0.198456E+10 | 0.123052E+10 | 0.00 | 2519281.28 | 99203069.88 | 58939178.00 | 0.618539E+09 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.874680E+09 | 197971.18 | 0.00 | 1792575.04 | 2018389.93 | 10706020.91 | 0.703918E+09 | 0.00 | 0.78 |
February | 0.117164E+10 | 0.00 | 0.00 | 764119.81 | 492326.09 | 7388170.64 | 0.653219E+09 | 0.00 | 0.71 |
March | 0.920172E+09 | 1916320.26 | 0.00 | 2021044.90 | 131813.93 | 7766220.09 | 0.749478E+09 | 0.00 | 0.81 |
April | 0.190219E+09 | 0.123264E+09 | 0.00 | 4053715.50 | 10208412.16 | 0.00 | 0.734144E+09 | 0.00 | 0.90 |
May | 0.109667E+09 | 0.257894E+09 | 0.00 | 2978234.57 | 7482535.82 | 0.00 | 0.335736E+09 | 0.00 | 0.74 |
June | 28831690.46 | 0.835389E+09 | 0.00 | 725279.77 | 13641614.61 | 0.00 | 83509929.52 | 0.00 | 0.60 |
July | 13194240.11 | 0.110160E+10 | 0.00 | 265199.09 | 34726727.49 | 0.00 | 33422785.79 | 0.00 | 0.55 |
August | 13574790.61 | 0.108488E+10 | 0.00 | 306978.65 | 22309257.02 | 0.00 | 30047634.14 | 0.00 | 0.63 |
September | 30142376.06 | 0.731470E+09 | 0.00 | 1346632.82 | 70596623.83 | 0.00 | 99935805.74 | 0.00 | 0.70 |
October | 0.284910E+09 | 0.144806E+09 | 0.00 | 3886953.62 | 7328548.07 | 0.00 | 0.106406E+10 | 0.00 | 0.97 |
November | 0.695998E+09 | 1155930.23 | 0.00 | 3371888.15 | 3333209.03 | 156410.11 | 0.113362E+10 | 0.00 | 0.90 |
December | 0.134393E+10 | 40202.52 | 0.00 | 916117.83 | 108821.97 | 12630506.96 | 0.529652E+09 | 0.00 | 0.69 |
Annual Sum or Average | 0.567696E+10 | 0.428261E+10 | 0.00 | 22428739.75 | 0.172378E+09 | 38647328.72 | 0.615075E+10 | 0.00 | 0.75 |
Minimum of Months | 13194240.11 | 0.00 | 0.00 | 265199.09 | 108821.97 | 0.00 | 30047634.14 | 0.00 | 0.55 |
Maximum of Months | 0.134393E+10 | 0.110160E+10 | 0.00 | 4053715.50 | 70596623.83 | 12630506.96 | 0.113362E+10 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.632514E+09 | 2595371.31 | 0.00 | 9016767.44 | 1871291.80 | 0.306783E+09 | 0.232299E+10 | 0.00 | 1.26 |
February | 0.136005E+10 | 0.00 | 0.00 | 1996946.63 | 592174.86 | 0.353823E+09 | 0.117536E+10 | 0.00 | 0.72 |
March | 0.116155E+10 | 4435743.40 | 0.00 | 3041950.22 | 146104.57 | 0.384559E+09 | 0.701558E+09 | 0.00 | 0.73 |
April | 0.378103E+09 | 0.241536E+09 | 0.00 | 3312554.79 | 12278782.67 | 67521974.76 | 0.330825E+09 | 0.00 | 0.61 |
May | 0.236404E+09 | 0.423287E+09 | 0.00 | 1526406.23 | 9292032.51 | 4814779.44 | 78701024.31 | 0.00 | 0.47 |
June | 77873265.99 | 0.123708E+10 | 0.00 | 333238.07 | 21844419.09 | 0.00 | 22291791.13 | 0.00 | 0.46 |
July | 25605607.44 | 0.156341E+10 | 0.00 | 157324.48 | 44763966.72 | 0.00 | 15861345.45 | 0.00 | 0.46 |
August | 25608453.22 | 0.168711E+10 | 0.00 | 194814.40 | 34721667.36 | 0.00 | 15848692.95 | 0.00 | 0.56 |
September | 54261822.46 | 0.123524E+10 | 0.00 | 1909210.90 | 86858893.83 | 0.00 | 89445901.85 | 0.00 | 0.64 |
October | 0.380620E+09 | 0.299870E+09 | 0.00 | 6993957.83 | 6184367.23 | 0.131396E+09 | 0.140574E+10 | 0.00 | 1.03 |
November | 0.574531E+09 | 2758654.09 | 0.00 | 9372644.09 | 3967341.61 | 0.176492E+09 | 0.266968E+10 | 0.00 | 1.22 |
December | 0.103825E+10 | 185856.61 | 0.00 | 6287878.18 | 87115.13 | 0.389093E+09 | 0.227603E+10 | 0.00 | 1.02 |
Annual Sum or Average | 0.594538E+10 | 0.669751E+10 | 0.00 | 44143693.27 | 0.222608E+09 | 0.181448E+10 | 0.111043E+11 | 0.00 | 0.77 |
Minimum of Months | 25605607.44 | 0.00 | 0.00 | 157324.48 | 87115.13 | 0.00 | 15848692.95 | 0.00 | 0.46 |
Maximum of Months | 0.136005E+10 | 0.168711E+10 | 0.00 | 9372644.09 | 86858893.83 | 0.389093E+09 | 0.266968E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126472E+10 | 647889.34 | 0.00 | 1694635.87 | 1885357.56 | 14723338.90 | 0.402633E+09 | 0.00 | 0.88 |
February | 0.155694E+10 | 0.00 | 0.00 | 781648.89 | 522455.37 | 21209281.63 | 0.434504E+09 | 0.00 | 0.79 |
March | 0.129061E+10 | 2339121.75 | 0.00 | 1427975.36 | 0.00 | 12009016.65 | 0.388508E+09 | 0.00 | 0.84 |
April | 0.315948E+09 | 0.157418E+09 | 0.00 | 2394404.38 | 7112492.19 | 0.00 | 0.337624E+09 | 0.00 | 0.73 |
May | 0.157372E+09 | 0.333470E+09 | 0.00 | 1153249.71 | 2677345.14 | 0.00 | 0.122514E+09 | 0.00 | 0.57 |
June | 43142989.79 | 0.918689E+09 | 0.00 | 357912.46 | 13346300.57 | 0.00 | 45855856.06 | 0.00 | 0.55 |
July | 17814544.51 | 0.989673E+09 | 0.00 | 150783.48 | 38129354.43 | 0.00 | 19462787.28 | 0.00 | 0.48 |
August | 13105069.20 | 0.992285E+09 | 0.00 | 208910.60 | 20317348.15 | 0.00 | 24647402.62 | 0.00 | 0.56 |
September | 30447863.17 | 0.670587E+09 | 0.00 | 1076815.53 | 85310302.63 | 0.00 | 76222753.98 | 0.00 | 0.61 |
October | 0.431219E+09 | 0.137517E+09 | 0.00 | 3008978.73 | 7752804.48 | 0.00 | 0.683362E+09 | 0.00 | 0.84 |
November | 0.903200E+09 | 2075570.71 | 0.00 | 3195372.46 | 3304139.13 | 0.00 | 0.951567E+09 | 0.00 | 0.95 |
December | 0.156347E+10 | 5228.11 | 0.00 | 1069498.98 | 152916.36 | 35817142.28 | 0.473331E+09 | 0.00 | 0.78 |
Annual Sum or Average | 0.758799E+10 | 0.420471E+10 | 0.00 | 16520186.45 | 0.180511E+09 | 83758779.46 | 0.396023E+10 | 0.00 | 0.71 |
Minimum of Months | 13105069.20 | 0.00 | 0.00 | 150783.48 | 0.00 | 0.00 | 19462787.28 | 0.00 | 0.48 |
Maximum of Months | 0.156347E+10 | 0.992285E+09 | 0.00 | 3195372.46 | 85310302.63 | 35817142.28 | 0.951567E+09 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130270E+10 | 25556.16 | 0.00 | 921142.67 | 1052941.26 | 31089746.20 | 0.269953E+09 | 0.00 | 0.50 |
February | 0.169349E+10 | 0.00 | 0.00 | 321040.64 | 691003.34 | 26416660.64 | 0.262965E+09 | 0.00 | 0.50 |
March | 0.123939E+10 | 745060.05 | 0.00 | 1955073.03 | 158672.84 | 21366471.92 | 0.532619E+09 | 0.00 | 0.55 |
April | 0.335759E+09 | 0.141993E+09 | 0.00 | 2988570.10 | 12591918.93 | 0.00 | 0.395580E+09 | 0.00 | 0.50 |
May | 0.139480E+09 | 0.348146E+09 | 0.00 | 2588228.37 | 10168378.88 | 0.00 | 0.227566E+09 | 0.00 | 0.49 |
June | 39039069.22 | 0.118873E+10 | 0.00 | 757391.14 | 15444432.81 | 0.00 | 82526598.52 | 0.00 | 0.49 |
July | 19370559.71 | 0.133718E+10 | 0.00 | 210071.51 | 35386914.95 | 0.00 | 23387701.70 | 0.00 | 0.44 |
August | 20734331.33 | 0.121679E+10 | 0.00 | 243597.82 | 27362110.84 | 0.00 | 18018415.53 | 0.00 | 0.47 |
September | 42403253.45 | 0.786839E+09 | 0.00 | 1415036.05 | 51693105.16 | 0.00 | 69245600.93 | 0.00 | 0.47 |
October | 0.601980E+09 | 0.155515E+09 | 0.00 | 2220344.02 | 8927764.29 | 0.00 | 0.443710E+09 | 0.00 | 0.51 |
November | 0.115700E+10 | 1517230.49 | 0.00 | 1840767.56 | 4924899.43 | 8912805.24 | 0.506254E+09 | 0.00 | 0.53 |
December | 0.172956E+10 | 0.00 | 0.00 | 205809.90 | 603416.23 | 0.135642E+09 | 0.104514E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.832090E+10 | 0.517748E+10 | 0.00 | 15667072.81 | 0.169006E+09 | 0.223428E+09 | 0.293634E+10 | 0.00 | 0.49 |
Minimum of Months | 19370559.71 | 0.00 | 0.00 | 205809.90 | 158672.84 | 0.00 | 18018415.53 | 0.00 | 0.44 |
Maximum of Months | 0.172956E+10 | 0.133718E+10 | 0.00 | 2988570.10 | 51693105.16 | 0.135642E+09 | 0.532619E+09 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.873115E+09 | 26201.66 | 0.00 | 1914099.45 | 1002410.30 | 21092163.34 | 0.785049E+09 | 0.00 | 0.81 |
February | 0.117784E+10 | 0.00 | 0.00 | 1088644.12 | 659005.92 | 15619219.79 | 0.811210E+09 | 0.00 | 0.78 |
March | 0.877725E+09 | 575672.42 | 0.00 | 2984595.89 | 151325.38 | 16874537.19 | 0.107725E+10 | 0.00 | 0.95 |
April | 0.216578E+09 | 0.128823E+09 | 0.00 | 4936813.36 | 11592849.93 | 0.00 | 0.860210E+09 | 0.00 | 1.03 |
May | 0.119206E+09 | 0.275515E+09 | 0.00 | 3895696.86 | 9383172.38 | 0.00 | 0.405679E+09 | 0.00 | 0.89 |
June | 38505261.17 | 0.959640E+09 | 0.00 | 849488.52 | 15383874.68 | 0.00 | 86338778.04 | 0.00 | 0.72 |
July | 16700909.62 | 0.115800E+10 | 0.00 | 248863.50 | 40185665.35 | 0.00 | 28678770.54 | 0.00 | 0.63 |
August | 21830172.17 | 0.109493E+10 | 0.00 | 246000.61 | 28251382.31 | 0.00 | 18608340.61 | 0.00 | 0.69 |
September | 42700981.76 | 0.707335E+09 | 0.00 | 1320626.14 | 45728972.00 | 0.00 | 69487625.96 | 0.00 | 0.70 |
October | 0.418245E+09 | 0.138162E+09 | 0.00 | 3174757.93 | 8636551.55 | 200485.56 | 0.853047E+09 | 0.00 | 0.91 |
November | 0.872805E+09 | 1042411.76 | 0.00 | 2557835.16 | 4931648.71 | 3405927.32 | 0.871107E+09 | 0.00 | 0.87 |
December | 0.146471E+10 | 0.00 | 0.00 | 650099.36 | 575474.60 | 81465790.45 | 0.364178E+09 | 0.00 | 0.71 |
Annual Sum or Average | 0.613997E+10 | 0.446404E+10 | 0.00 | 23867520.90 | 0.166482E+09 | 0.138658E+09 | 0.623085E+10 | 0.00 | 0.81 |
Minimum of Months | 16700909.62 | 0.00 | 0.00 | 246000.61 | 151325.38 | 0.00 | 18608340.61 | 0.00 | 0.63 |
Maximum of Months | 0.146471E+10 | 0.115800E+10 | 0.00 | 4936813.36 | 45728972.00 | 81465790.45 | 0.107725E+10 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.707513E+09 | 4343735.23 | 0.00 | 10499069.28 | 183957.94 | 15055530.20 | 0.297125E+10 | 0.00 | 1.38 |
February | 0.103484E+10 | 0.00 | 0.00 | 6108097.64 | 768321.15 | 11638845.89 | 0.306019E+10 | 0.00 | 1.04 |
March | 0.898829E+09 | 1247132.58 | 0.00 | 6448072.63 | 176427.08 | 16770492.03 | 0.190013E+10 | 0.00 | 0.95 |
April | 0.366362E+09 | 0.230421E+09 | 0.00 | 4376615.36 | 13515860.09 | 0.00 | 0.560549E+09 | 0.00 | 0.70 |
May | 0.190729E+09 | 0.389949E+09 | 0.00 | 2375698.88 | 11306140.18 | 0.00 | 0.180393E+09 | 0.00 | 0.52 |
June | 60580942.96 | 0.116216E+10 | 0.00 | 537620.28 | 20239159.04 | 0.00 | 51937905.27 | 0.00 | 0.47 |
July | 22012749.43 | 0.134846E+10 | 0.00 | 170850.71 | 46155327.94 | 0.00 | 18139223.43 | 0.00 | 0.44 |
August | 23600325.57 | 0.141604E+10 | 0.00 | 229541.00 | 28614415.68 | 0.00 | 16980195.51 | 0.00 | 0.54 |
September | 47249465.21 | 0.107917E+10 | 0.00 | 1921126.29 | 54758592.84 | 0.00 | 83515379.36 | 0.00 | 0.61 |
October | 0.408255E+09 | 0.272878E+09 | 0.00 | 7046356.28 | 9357799.91 | 0.00 | 0.162907E+10 | 0.00 | 1.04 |
November | 0.688227E+09 | 2265137.48 | 0.00 | 10286666.18 | 5475956.78 | 823126.22 | 0.303568E+10 | 0.00 | 1.30 |
December | 0.948595E+09 | 253989.93 | 0.00 | 8746227.56 | 477144.10 | 68095179.62 | 0.333062E+10 | 0.00 | 1.18 |
Annual Sum or Average | 0.539679E+10 | 0.590719E+10 | 0.00 | 58745942.09 | 0.191029E+09 | 0.112383E+09 | 0.168385E+11 | 0.00 | 0.85 |
Minimum of Months | 22012749.43 | 0.00 | 0.00 | 170850.71 | 176427.08 | 0.00 | 16980195.51 | 0.00 | 0.44 |
Maximum of Months | 0.103484E+10 | 0.141604E+10 | 0.00 | 10499069.28 | 54758592.84 | 68095179.62 | 0.333062E+10 | 0.00 | 1.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128868E+10 | 1576132.09 | 0.00 | 2073408.15 | 266599.58 | 33183859.65 | 0.492897E+09 | 0.00 | 0.95 |
February | 0.157528E+10 | 0.00 | 0.00 | 1257227.08 | 709484.67 | 34276880.69 | 0.659724E+09 | 0.00 | 0.91 |
March | 0.127585E+10 | 875429.03 | 0.00 | 2474458.46 | 0.00 | 23989863.94 | 0.652553E+09 | 0.00 | 1.00 |
April | 0.381762E+09 | 0.181092E+09 | 0.00 | 2900994.98 | 6226624.40 | 0.00 | 0.359037E+09 | 0.00 | 0.85 |
May | 0.204608E+09 | 0.393911E+09 | 0.00 | 1563852.59 | 3014003.79 | 0.00 | 0.107644E+09 | 0.00 | 0.70 |
June | 60289920.97 | 0.110895E+10 | 0.00 | 319088.39 | 14373711.07 | 0.00 | 36921277.74 | 0.00 | 0.67 |
July | 22250373.90 | 0.106342E+10 | 0.00 | 103593.14 | 40005264.41 | 0.00 | 12829755.03 | 0.00 | 0.55 |
August | 25908677.02 | 0.100631E+10 | 0.00 | 129610.56 | 23640425.37 | 0.00 | 9483517.86 | 0.00 | 0.62 |
September | 57967453.27 | 0.649545E+09 | 0.00 | 1032057.55 | 53475650.37 | 0.00 | 43864525.73 | 0.00 | 0.62 |
October | 0.648504E+09 | 0.134912E+09 | 0.00 | 2595148.43 | 9459309.00 | 414717.68 | 0.493866E+09 | 0.00 | 0.85 |
November | 0.114736E+10 | 2015314.34 | 0.00 | 2630797.69 | 4923892.65 | 9427064.41 | 0.737182E+09 | 0.00 | 0.97 |
December | 0.154557E+10 | 0.00 | 0.00 | 1122608.21 | 619555.00 | 0.131509E+09 | 0.491188E+09 | 0.00 | 0.83 |
Annual Sum or Average | 0.823403E+10 | 0.454261E+10 | 0.00 | 18202845.22 | 0.156715E+09 | 0.232801E+09 | 0.409719E+10 | 0.00 | 0.79 |
Minimum of Months | 22250373.90 | 0.00 | 0.00 | 103593.14 | 0.00 | 0.00 | 9483517.86 | 0.00 | 0.55 |
Maximum of Months | 0.157528E+10 | 0.110895E+10 | 0.00 | 2900994.98 | 53475650.37 | 0.131509E+09 | 0.737182E+09 | 0.00 | 1.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:44
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.196625E+12 | 0.706536E+10 | 0.00 | 0.199909E+12 | 0.613861E+11 |
February | 0.204366E+12 | 0.668361E+10 | 0.00 | 0.208052E+12 | 0.143142E+11 |
March | 0.258117E+12 | 0.722880E+10 | 0.00 | 0.205594E+12 | 0.620578E+11 |
April | 0.302864E+12 | 0.122377E+10 | 0.00 | 0.115061E+12 | 0.180855E+12 |
May | 0.293795E+12 | -897439897.9 | 0.00 | 0.737115E+11 | 0.243501E+12 |
June | 0.298456E+12 | -0.409504E+10 | 0.00 | 0.191845E+10 | 0.338155E+12 |
July | 0.276871E+12 | -0.626639E+10 | 0.00 | -0.385113E+11 | 0.329264E+12 |
August | 0.249559E+12 | -0.524904E+10 | 0.00 | -0.319371E+11 | 0.335381E+12 |
September | 0.216431E+12 | -0.343325E+10 | 0.00 | -0.318695E+11 | 0.279382E+12 |
October | 0.215739E+12 | 0.272361E+10 | 0.00 | 0.148720E+12 | 0.154020E+12 |
November | 0.198384E+12 | 0.646187E+10 | 0.00 | 0.199613E+12 | 0.657968E+11 |
December | 0.164609E+12 | 0.795224E+10 | 0.00 | 0.213513E+12 | 0.287652E+11 |
Annual Sum or Average | 0.287582E+13 | 0.193981E+11 | 0.00 | 0.126377E+13 | 0.209288E+13 |
Minimum of Months | 0.164609E+12 | -0.626639E+10 | 0.00 | -0.385113E+11 | 0.143142E+11 |