Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 08:28:45
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1661.15 | 333.42 | 333.42 |
Net Site Energy | 1661.15 | 333.42 | 333.42 |
Total Source Energy | 4809.14 | 965.27 | 965.27 |
Net Source Energy | 4809.14 | 965.27 | 965.27 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 123.79 | 78.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 42.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 366.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 111.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 76.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 138.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1444.29 | 216.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 123.79 | 78.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 42.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 366.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 111.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 17.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 76.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 138.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 123.79 | 78.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 42.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 366.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 111.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 17.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 76.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 138.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 96.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 48.77 | 43.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 145.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 289.89 | 43.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 96.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 48.77 | 43.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 145.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 289.89 | 43.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1444.289 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1444.289 | 100.00 |
Total On-Site and Utility Electric Sources | 1444.289 | 100.00 |
Total Electricity End Uses | 1444.289 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 265.83 |
Time Setpoint Not Met During Occupied Cooling | 65.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1939.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 10.1959 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 10.1959 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.1959 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 10.1959 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
Total | 4982.19 | 10.1959 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 10.1959 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 10.1959 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 10-JAN-07:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 166765.69 | 59207.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12752.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 8596.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 353.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5809.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8984.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 215384.09 | 68192.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 166765.69 | 59207.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 12752.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 8596.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 353.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5809.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8984.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 392.03 | 84.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 135.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1161.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 354.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 54.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 241.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 150.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4574.06 | 235.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 78.69 | 17.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 27.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 233.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 48.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 30.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 918.08 | 47.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 78.69 | 17.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 27.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 233.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 48.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 30.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 918.08 | 47.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.09 | 0.242195 | 0.256000 | 0.792174 | 0.645853 | 0.500000 | 0.001573 |
CORE_MID VAV BOX COMPONENT | 2.31 | 0.324950 | 0.334000 | 0.770329 | 0.866532 | 0.500000 | 0.001172 |
CORE_TOP VAV BOX COMPONENT | 2.31 | 0.324980 | 0.343000 | 0.791012 | 0.866613 | 0.500000 | 0.001172 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.618876 | 0.255288 | 0.270000 | 0.167096 | 0.680769 | 0.500000 | 0.001492 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.825259 | 0.121200 | 0.200000 | 0.165052 | 0.323201 | 0.500000 | 0.003144 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.24 | 0.127722 | 0.200000 | 0.247400 | 0.340592 | 0.500000 | 0.002983 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.912196 | 0.109642 | 0.200000 | 0.182439 | 0.300000 | 0.500000 | 0.003475 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.501588 | 0.314983 | 0.333000 | 0.167029 | 0.839955 | 0.500000 | 0.001210 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.679009 | 0.147306 | 0.200000 | 0.135802 | 0.392815 | 0.500000 | 0.002586 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.02 | 0.155177 | 0.200000 | 0.203627 | 0.413807 | 0.500000 | 0.002455 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.764484 | 0.130827 | 0.200000 | 0.152897 | 0.348872 | 0.500000 | 0.002912 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.557845 | 0.283218 | 0.291000 | 0.162333 | 0.755248 | 0.500000 | 0.001345 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.832790 | 0.120104 | 0.200000 | 0.166558 | 0.320279 | 0.500000 | 0.003172 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.17 | 0.135542 | 0.200000 | 0.233125 | 0.361446 | 0.500000 | 0.002811 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.860546 | 0.116223 | 0.200000 | 0.172109 | 0.309928 | 0.500000 | 0.003278 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 26176.66 |
CORE_MID VAV BOX REHEAT COIL | 25454.80 |
CORE_TOP VAV BOX REHEAT COIL | 30750.18 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 13835.98 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 9086.32 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 13884.69 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9046.08 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10892.21 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7264.79 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10954.07 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7224.03 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 10763.10 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 7134.06 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 10808.12 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 7095.20 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.03 | 1.45 | 6.06 | 1.52 | 5.30 | 5.30 | 0.300000 | 0.287617 | 5.30 |
PACU_VAV_MID | 2.86 | 1.50 | 5.72 | 1.60 | 4.74 | 4.74 | 0.300000 | 0.338167 | 4.74 |
PACU_VAV_TOP | 2.95 | 1.55 | 5.90 | 2.32 | 5.24 | 5.24 | 0.300000 | 0.442082 | 5.24 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.30 |
PACU_VAV_MID_OA_CONTROLLER | 4.74 |
PACU_VAV_TOP_OA_CONTROLLER | 5.24 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.30 | 87728.93 | 0.800655 | 1.77 | 29240.05 | 0.800655 |
PACU_VAV_MID COOLING COIL | 4.74 | 78468.45 | 0.800655 | 1.58 | 26153.53 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 5.24 | 86804.38 | 0.800655 | 1.75 | 28931.90 | 0.800655 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 20996.85 |
PACU_VAV_MID HEATING COIL | 22239.39 |
PACU_VAV_TOP HEATING COIL | 22050.46 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.30 |
PACU_VAV_MID FAN | 4.74 |
PACU_VAV_TOP FAN | 5.24 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 35.030 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.8022 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7887 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.032 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.013 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.034 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7350 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.29755900E-12 | 0.81313074E-15 | -0.93602003E-13 | 0.14510957E-15 |
43 | 6 | 0.28367368E-07 | 0.22496401E-09 | 0.65009128E-08 | -0.13359594E-12 |
44 | 5 | -0.18856357E-03 | 0.19286971E-05 | -0.97009749E-04 | 0.64274374E-08 |
45 | 4 | 0.29034011 | 0.94012602E-03 | 0.99033658E-01 | -0.33316087E-04 |
46 | 3 | -7.2305496 | 0.29163423E-01 | -2.3282961 | 0.28833673E-01 |
47 | 2 | 40.753148 | 0.10379063 | 15.221555 | -0.33202618 |
48 | 1 | -80.455373 | 0.46876469E-01 | -29.102648 | 1.0766925 |
49 | 0 | 46.824339 | 0.94379271E-03 | 16.292168 | |
50 | 7 | -0.29905644E-12 | 0.21441847E-14 | -0.94350753E-13 | 0.15229914E-15 |
51 | 6 | 0.28527035E-07 | 0.22156944E-09 | 0.65361533E-08 | -0.13441220E-12 |
52 | 5 | -0.18937502E-03 | 0.18976302E-05 | -0.97416439E-04 | 0.64617957E-08 |
53 | 4 | 0.29129073 | 0.92413897E-03 | 0.99375489E-01 | -0.33450099E-04 |
54 | 3 | -7.2493786 | 0.28644335E-01 | -2.3338831 | 0.28925940E-01 |
55 | 2 | 40.815249 | 0.10187053 | 15.244478 | -0.33271782 |
56 | 1 | -80.502964 | 0.45980673E-01 | -29.123201 | 1.0777067 |
57 | 0 | 46.824339 | 0.92519179E-03 | 16.291675 | |
58 | 7 | -0.27570686E-12 | 0.13707328E-14 | -0.80264236E-13 | 0.78378346E-16 |
59 | 6 | 0.25615968E-07 | 0.28022365E-09 | 0.58936169E-08 | -0.11887149E-12 |
60 | 5 | -0.17446821E-03 | 0.24481169E-05 | -0.89927666E-04 | 0.58344893E-08 |
61 | 4 | 0.27366067 | 0.12133616E-02 | 0.93044102E-01 | -0.30982017E-04 |
62 | 3 | -6.8997845 | 0.38197916E-01 | -2.2301787 | 0.27213971E-01 |
63 | 2 | 39.661773 | 0.13771433 | 14.818013 | -0.31987377 |
64 | 1 | -79.618511 | 0.62899977E-01 | -28.740542 | 1.0588596 |
65 | 0 | 46.824345 | 0.12804488E-02 | 16.301062 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.419_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.419_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.973 | 0.1730 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3649E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3720E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5343E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5405E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.5901E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.6395E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.6026E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6282E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1823 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1058 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2094 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1228 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1204 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2730E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0870E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9083E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3651E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3735E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5345E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5422E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.5920E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.6490E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.6024E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6280E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.5463E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.9914E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.2495E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7364E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.0196E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0555E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9724E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8144E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.5727E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.6023E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.3063E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.3279E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6705E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.6780E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3717E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3805E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.1256E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.1891E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.2767E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3286E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6806E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.7190E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6024E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.6280E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.9978E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8637E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8612E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1898E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5185E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4787E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0870E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9083E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.1253E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.1900E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.2759E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3272E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6788E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.7122E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6026E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.6282E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.2116E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.3191E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5399E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8710E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.0424E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5868E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9724E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8145E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.7285E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.8210E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2206E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.3255E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0761E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.1090E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3719E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3807E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1829 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1268 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2069 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1462 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1297 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.6635E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.7993E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7067E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.2577E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.8260E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.9824E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.5830E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.8265E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.9407E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.8615E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7478E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.6703E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.7083E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.4576E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.9144E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.1139E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1369E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.7993E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7067E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.9682E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.1843E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3313E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.7573E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8791E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4921E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.8615E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7479E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1829 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1268 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2069 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1462 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1296 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.6627E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.7987E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.7064E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.2577E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.8257E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.9823E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.5827E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.8261E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.9403E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.8609E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7475E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.6705E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.7081E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.4577E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.9143E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.1137E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.1367E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.7987E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7064E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.9682E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.1840E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3313E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.7571E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8787E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4917E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.8610E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7475E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 42483.19966 | 42483.19966 | 3.09443 | 3.09443 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 6094.70401 | 6094.70401 | 0.25890 | 0.42469 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 31697.53464 | 31697.53464 | 2.30637 | 2.30637 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 12174.83098 | 12174.83098 | 0.51959 | 0.51959 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 31403.56547 | 31403.56547 | 2.30616 | 2.30616 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 26.30900 | 8.40693E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 21684.86303 | 21684.86303 | 0.93058 | 0.93058 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8427.52154 | 8427.52154 | 0.61888 | 0.61888 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 26.30900 | 8.40693E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 9722.50369 | 9722.50369 | 0.41871 | 0.41871 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11238.04376 | 11238.04376 | 0.82526 | 0.82526 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.65283 | 8.39969E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6384.19177 | 6384.19177 | 0.27498 | 0.27498 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 16844.90773 | 16844.90773 | 1.23700 | 1.23700 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 9756.61069 | 9756.61069 | 0.42019 | 0.42019 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12421.92435 | 12421.92435 | 0.91220 | 0.91220 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6356.00589 | 6356.00589 | 0.27376 | 0.27376 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6830.32472 | 6830.32472 | 0.50159 | 0.50159 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.40000 | 8.40708E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 7659.82480 | 7659.82480 | 0.32963 | 0.32963 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9246.44118 | 9246.44118 | 0.67901 | 0.67901 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 21.91067 | 8.40008E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5107.83574 | 5107.83574 | 0.21985 | 0.21985 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 13864.48243 | 13864.48243 | 1.01814 | 1.01814 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 26.32417 | 8.40696E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 7703.14204 | 7703.14204 | 0.33150 | 0.33150 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 10410.39729 | 10410.39729 | 0.76448 | 0.76448 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.21600 | 8.40365E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 5079.29284 | 5079.29284 | 0.21862 | 0.21862 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7596.42071 | 7596.42071 | 0.55784 | 0.55784 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.40000 | 8.40708E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 7570.02471 | 7570.02471 | 0.32572 | 0.32572 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 11340.58649 | 11340.58649 | 0.83279 | 0.83279 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 21.10683 | 8.39884E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5016.67937 | 5016.67937 | 0.21590 | 0.21590 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 15872.97420 | 15872.97420 | 1.16563 | 1.16563 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 26.09667 | 8.40660E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 7601.55547 | 7601.55547 | 0.32708 | 0.32708 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11718.56104 | 11718.56104 | 0.86055 | 0.86055 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4989.46073 | 4989.46073 | 0.21472 | 0.21472 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 74477.22 | 5.29970 | 5.29970 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 24403.40 | 1.52429 | 1.52429 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 66976.01 | 4.74028 | 4.74028 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 24460.08 | 1.60300 | 1.60300 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 20:10:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 73669.07 | 5.24385 | 5.24385 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 24384.40 | 2.31821 | 2.31821 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.09443 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24219 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79217 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64585 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57311E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26176.65577 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.30637 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32495 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33400 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77033 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86653 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.17249E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25454.80247 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.30616 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32498 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34300 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79101 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86661 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.17238E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 30750.18162 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61888 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25529 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16710 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68077 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49243E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13835.98426 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82526 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12120 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16505 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32320 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.14355E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9086.32269 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23700 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12772 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24740 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34059 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.98304E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13884.68771 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91220 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10964 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18244 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.47494E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9046.07776 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.50159 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31498 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16703 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83995 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20959E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10892.21467 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67901 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14731 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13580 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39281 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.58646E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7264.78924 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.01814 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15518 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20363 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41381 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.45525E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10954.06706 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76448 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13083 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15290 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34887 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.91224E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7224.03491 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55784 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28322 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29100 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16233 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75525 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34525E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10763.09633 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83279 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12010 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16656 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32028 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.17224E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7134.06398 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.16563 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13554 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23313 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36145 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.81093E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10808.12135 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86055 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11622 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17211 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30993 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.27818E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7095.19889 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.02882 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.45153 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.05765 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.52429 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.29970 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.29970 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.28762 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.86159 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.50445 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.72318 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.60300 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.74028 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.74028 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.33817 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.94974 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.55300 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.89949 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.31821 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.24385 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.24385 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.44208 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.29970 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.74028 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.24385 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.29970 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.29970 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 87728.92836 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.76639 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 29240.05182 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 20996.84813 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.29970 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.74028 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.74028 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 78468.45094 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.57994 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 26153.53470 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 22239.38765 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.74028 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.24385 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.24385 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 86804.38020 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.74778 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28931.89992 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 22050.46062 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.24385 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 86219.33 | 294192.57 | 10.80 | 2.80 | 3.09 | 3.25 | 3.42 | 9.54 | 10.54 | 11.09 | 11.68 | 6.0646 | 4.7967 | 3.2152 | 1.3392 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 77118.20 | 263138.24 | 10.80 | 2.80 | 3.09 | 3.25 | 3.42 | 9.54 | 10.54 | 11.09 | 11.68 | 5.4244 | 4.2903 | 2.8758 | 1.1978 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 85310.69 | 291092.17 | 10.80 | 2.80 | 3.09 | 3.25 | 3.42 | 9.54 | 10.54 | 11.09 | 11.68 | 6.0007 | 4.7461 | 3.1813 | 1.3251 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_NORTH_0.4 | N/A | 2.381 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_EAST_0.4 | N/A | 2.381 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_SOUTH_0.4 | N/A | 2.381 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.419_SHGC_WEST_0.4 | N/A | 2.381 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.1571778244E-003 | 6.5772462628E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1123671687 | 8.1395450359E-002 | Pass | Pass | 0.3219155466 | 0.4511408529 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.2092259334E-002 | 1.0131973895E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.8604238642E-003 | 8.2793301033E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 8.8499260972E-003 | 8.0409003253E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.4719066815E-002 | 2.6128367766E-002 | Pass | Pass | 0.7264606301 | 2.0421503715 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1672500064 | 0.1880441338 | Pass | Pass | 6.8113516639 | 21.1322543698 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1480319391 | 0.1544672993 | Pass | Pass | 5.7394768477 | 18.2165175566 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1179962656 | 0.1239655746 | Pass | Pass | 4.2161891778 | 17.0515008088 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1594116533 | 0.1625018611 | Pass | Pass | 5.5451049092 | 17.2828511584 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.5961952255E-002 | 1.3118655095E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.9934359110E-002 | 6.5506010975E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.0991639481E-002 | 8.3826994596E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.5682843902E-002 | 4.6219994974E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.9030436752E-002 | 1.5103714353E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.1010082854E-002 | 7.5472660800E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.0516215964E-002 | 0.1035334188 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.2840051375E-002 | 5.3123807204E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3127.07 | 102.95 | 0.00 | 2708.69 | 231.26 | 6169.99 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.419_SHGC_NORTH_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.419_SHGC_EAST_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.419_SHGC_WEST_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.381 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.419_SHGC_NORTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.419_SHGC_EAST_0.4 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.419_SHGC_EAST_0.4 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.419_SHGC_WEST_0.4 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.419_SHGC_WEST_0.4 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.381 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.419_SHGC_NORTH_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.419_SHGC_EAST_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.419_SHGC_SOUTH_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.419_SHGC_WEST_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.381 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.381 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 195.79 | 2.381 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.381 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 28.01 | 0.0000 | Y | 11.11 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.53 | 0.0000 | Y | 6.92 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.30 | 0.0000 | Y | 10.83 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.70 | 0.0000 | Y | 6.96 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.91 | 0.0000 | Y | 11.07 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.47 | 0.0000 | Y | 6.90 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.24 | 0.0000 | Y | 10.81 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.62 | 0.0000 | Y | 6.94 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 28.01 | 0.0000 | Y | 11.11 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.53 | 0.0000 | Y | 6.92 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.30 | 0.0000 | Y | 10.83 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.70 | 0.0000 | Y | 6.96 |
Interior Lighting Total | 10.1959 | 4982.19 | 50797.72 | 366.86 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.28 | AstronomicalClock | - | 42.50 | 42.50 | 4.49 | |
EXTERIOR_LIGHTS_B | 8033.20 | AstronomicalClock | - | 83.54 | 71.23 | 107.41 | |
Exterior Lighting Total | 8596.48 | 111.90 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 87728.93 | 70240.63 | 17488.30 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 78468.45 | 62826.18 | 15642.27 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 86804.38 | 69500.38 | 17304.00 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 86219.3 | 2.80 | 9.54 | N/A | N/A | 10.80 | |
PACU_VAV_MID COOLING COIL | 77118.2 | 2.80 | 9.54 | N/A | N/A | 10.80 | |
PACU_VAV_TOP COOLING COIL | 85310.7 | 2.80 | 9.54 | N/A | N/A | 10.80 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 26176.66 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 25454.80 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 30750.18 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13835.98 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9086.32 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13884.69 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9046.08 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10892.21 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7264.79 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10954.07 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7224.03 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10763.10 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7134.06 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10808.12 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7095.20 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 20996.85 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 22239.39 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 22050.46 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.30 | 11526.27 | 2174.89 | 1.00 | 1.14 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.74 | 10376.52 | 2189.01 | 1.00 | 1.14 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.24 | 11404.79 | 2174.89 | 1.00 | 1.14 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.97 | 0.17 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 86219.33 | 2.80 | 9.54 | 10.80 | 6.0646 | 3.09 | 10.54 | 4.7967 | 3.25 | 11.09 | 3.2152 | 3.42 | 11.68 | 1.3392 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 77118.20 | 2.80 | 9.54 | 10.80 | 5.4244 | 3.09 | 10.54 | 4.2903 | 3.25 | 11.09 | 2.8758 | 3.42 | 11.68 | 1.1978 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 85310.69 | 2.80 | 9.54 | 10.80 | 6.0007 | 3.09 | 10.54 | 4.7461 | 3.25 | 11.09 | 3.1813 | 3.42 | 11.68 | 1.3251 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 42483.20 | 42483.20 | 43.19 | 3.094 | 3.094 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00879 | 19.67 | 0.00840 | 0.425 | 0.00 |
CORE_MID | 31697.53 | 31697.53 | 32.23 | 2.306 | 2.306 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 19.67 | 0.00840 | 0.425 | 0.00 |
CORE_TOP | 31403.57 | 31403.57 | 31.93 | 2.306 | 2.306 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00888 | 26.31 | 0.00841 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8427.52 | 8427.52 | 40.65 | 0.619 | 0.619 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00879 | 26.31 | 0.00841 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11238.04 | 11238.04 | 85.62 | 0.825 | 0.825 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00864 | 21.65 | 0.00840 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 16844.91 | 16844.91 | 81.24 | 1.237 | 1.237 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00865 | 26.17 | 0.00841 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12421.92 | 12421.92 | 94.64 | 0.912 | 0.912 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00863 | 24.97 | 0.00840 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6830.32 | 6830.32 | 32.94 | 0.502 | 0.502 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00886 | 26.40 | 0.00841 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9246.44 | 9246.44 | 70.44 | 0.679 | 0.679 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.00 | 24.00 | 0.00867 | 21.91 | 0.00840 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 13864.48 | 13864.48 | 66.87 | 1.018 | 1.018 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00868 | 26.32 | 0.00841 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 10410.40 | 10410.40 | 79.32 | 0.764 | 0.764 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.00 | 24.00 | 0.00865 | 24.22 | 0.00840 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7596.42 | 7596.42 | 36.64 | 0.558 | 0.558 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00882 | 26.40 | 0.00841 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 11340.59 | 11340.59 | 86.40 | 0.833 | 0.833 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00864 | 21.11 | 0.00840 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 15872.97 | 15872.97 | 76.56 | 1.166 | 1.166 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00866 | 26.10 | 0.00841 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11718.56 | 11718.56 | 89.28 | 0.861 | 0.861 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00863 | 24.97 | 0.00840 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 6094.70 | 6094.70 | 6.20 | 0.259 | 0.425 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 0.425 | 0.00 |
CORE_MID | 12174.83 | 12174.83 | 12.38 | 0.520 | 0.520 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 0.425 | 0.00 |
CORE_TOP | 21684.86 | 21684.86 | 22.05 | 0.931 | 0.931 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9722.50 | 9722.50 | 46.89 | 0.419 | 0.419 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 6384.19 | 6384.19 | 48.64 | 0.275 | 0.275 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9756.61 | 9756.61 | 47.06 | 0.420 | 0.420 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6356.01 | 6356.01 | 48.43 | 0.274 | 0.274 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7659.82 | 7659.82 | 36.94 | 0.330 | 0.330 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5107.84 | 5107.84 | 38.91 | 0.220 | 0.220 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 7703.14 | 7703.14 | 37.15 | 0.331 | 0.331 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 5079.29 | 5079.29 | 38.70 | 0.219 | 0.219 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7570.02 | 7570.02 | 36.51 | 0.326 | 0.326 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5016.68 | 5016.68 | 38.22 | 0.216 | 0.216 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 7601.56 | 7601.56 | 36.66 | 0.327 | 0.327 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4989.46 | 4989.46 | 38.01 | 0.215 | 0.215 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.30 | 0.00266 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.30 | 5.30 | 1.52 | 1.52 | 5.2997 | 1.5243 | 5.2997 | 0.2876 | 0.3000 |
PACU_VAV_MID | 4.74 | 4.74 | 1.60 | 1.60 | 4.7403 | 1.6030 | 4.7403 | 0.3382 | 0.3000 |
PACU_VAV_TOP | 5.24 | 5.24 | 2.32 | 2.32 | 5.2439 | 2.3182 | 5.2439 | 0.4421 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 26176.656 | 26176.656 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26176.66 | 14033.53 | 0.424691 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 6094.70 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 25454.802 | 25454.802 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25454.80 | 17169.32 | 0.519588 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 12174.83 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 30750.182 | 30750.182 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30750.18 | 30750.18 | 0.930581 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 21684.86 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 13835.984 | 13835.984 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13835.98 | 13835.98 | 0.418713 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00784884 | 50.2150 | 9722.50 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 9086.323 | 9086.323 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9086.32 | 9086.32 | 0.274976 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00785039 | 50.2249 | 6384.19 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 13884.688 | 13884.688 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13884.69 | 13884.69 | 0.420187 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00784982 | 50.2212 | 9756.61 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 9046.078 | 9046.078 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9046.08 | 9046.08 | 0.273758 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00784926 | 50.2177 | 6356.01 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 10892.215 | 10892.215 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10892.21 | 10892.21 | 0.329627 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00782831 | 50.0854 | 7659.82 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7264.789 | 7264.789 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7264.79 | 7264.79 | 0.219851 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00783883 | 50.1518 | 5107.84 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 10954.067 | 10954.067 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10954.07 | 10954.07 | 0.331499 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00783051 | 50.0992 | 7703.14 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 7224.035 | 7224.035 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7224.03 | 7224.03 | 0.218618 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00783673 | 50.1386 | 5079.29 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 10763.096 | 10763.096 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10763.10 | 10763.10 | 0.325719 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00776025 | 49.6560 | 7570.02 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 7134.064 | 7134.064 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7134.06 | 7134.06 | 0.215895 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00777389 | 49.7421 | 5016.68 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 10808.121 | 10808.121 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10808.12 | 10808.12 | 0.327082 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00776266 | 49.6712 | 7601.56 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 7095.199 | 7095.199 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7095.20 | 7095.20 | 0.214719 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00777068 | 49.7218 | 4989.46 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 87728.928 | 70240.628 | 5.299705 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 89665.74 | 86457.01 | 5.299705 | 24.54 | 16.64 | 0.00869491 | 11.01 | 11.01 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 22.5516 | 24.00 | 0.00877874 | 46.7372 | 72157.40 | 0.00 | 90460.30 | 70815.00 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 20996.848 | 20996.848 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20996.85 | 20996.85 | 1.589911 | 1.77 | 1.20 | 0.00393649 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 75.1721 | 20.73 | 0.00773344 | 50.3147 | 21160.39 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 78468.451 | 62826.178 | 4.740279 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 80242.15 | 77187.87 | 4.740279 | 24.60 | 16.67 | 0.00870881 | 11.00 | 11.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 25.2131 | 24.00 | 0.00881056 | 46.9042 | 64538.40 | 0.00 | 80911.51 | 63339.92 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 22239.388 | 22239.388 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 20:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22239.39 | 22239.39 | 1.422084 | -0.26 | -0.63 | 0.00349109 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 84.0436 | 21.00 | 0.00787062 | 50.3517 | 25343.32 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 86804.380 | 69500.384 | 5.243853 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 88724.32 | 85542.07 | 5.243853 | 24.55 | 16.64 | 0.00869546 | 11.01 | 11.01 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 22.7918 | 24.00 | 0.00878070 | 46.7474 | 71336.60 | 0.00 | 89506.97 | 70068.70 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 22050.461 | 22050.461 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22050.46 | 22050.46 | 1.573156 | 1.09 | 0.75 | 0.00388997 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 75.9728 | 19.60 | 0.00775446 | 54.1016 | 27832.72 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 26176.656 | 26176.656 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26176.66 | 14033.53 | 1.0000 | 0.50596508 | 0.424691 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26176.66 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.64 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 6094.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 25454.802 | 25454.802 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25454.80 | 17169.32 | 1.0000 | 0.61902305 | 0.519588 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25454.80 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 12174.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 30750.182 | 30750.182 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30750.18 | 30750.18 | 1.0000 | 1.10866777 | 0.930581 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30750.18 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 21684.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13835.984 | 13835.984 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13835.98 | 13835.98 | 1.0000 | 0.49884290 | 0.418713 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13835.98 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00784884 | 21.00 | 0.00784884 | 50.2150 | 9722.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9086.323 | 9086.323 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9086.32 | 9086.32 | 1.0000 | 0.32759849 | 0.274976 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9086.32 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00785039 | 21.00 | 0.00785039 | 50.2249 | 6384.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13884.688 | 13884.688 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13884.69 | 13884.69 | 1.0000 | 0.50059886 | 0.420187 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13884.69 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00784982 | 21.00 | 0.00784982 | 50.2212 | 9756.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9046.078 | 9046.078 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9046.08 | 9046.08 | 1.0000 | 0.32614750 | 0.273758 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9046.08 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00784926 | 21.00 | 0.00784926 | 50.2177 | 6356.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10892.215 | 10892.215 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10892.21 | 10892.21 | 1.0000 | 0.39270816 | 0.329627 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10892.21 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00782831 | 21.00 | 0.00782831 | 50.0854 | 7659.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7264.789 | 7264.789 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7264.79 | 7264.79 | 1.0000 | 0.26192488 | 0.219851 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7264.79 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00783883 | 21.00 | 0.00783883 | 50.1518 | 5107.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10954.067 | 10954.067 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10954.07 | 10954.07 | 1.0000 | 0.39493819 | 0.331499 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10954.07 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00783051 | 21.00 | 0.00783051 | 50.0992 | 7703.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7224.035 | 7224.035 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7224.03 | 7224.03 | 1.0000 | 0.26045552 | 0.218618 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7224.03 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00783673 | 21.00 | 0.00783673 | 50.1386 | 5079.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10763.096 | 10763.096 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10763.10 | 10763.10 | 1.0000 | 0.38805293 | 0.325719 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10763.10 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00776025 | 21.00 | 0.00776025 | 49.6560 | 7570.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7134.064 | 7134.064 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7134.06 | 7134.06 | 1.0000 | 0.25721171 | 0.215895 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7134.06 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00777389 | 21.00 | 0.00777389 | 49.7421 | 5016.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10808.121 | 10808.121 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10808.12 | 10808.12 | 1.0000 | 0.38967626 | 0.327082 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10808.12 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00776266 | 21.00 | 0.00776266 | 49.6712 | 7601.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7095.199 | 7095.199 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7095.20 | 7095.20 | 1.0000 | 0.25581047 | 0.214719 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7095.20 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00777068 | 21.00 | 0.00777068 | 49.7218 | 4989.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 87728.928 | 70240.628 | 5.299705 | -999.0 | -999.000 | -999.0000 | 1.01837 | 1.00000 | 1021.0034 | 1004.8586 | 1.1914 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.299705 | 6.31391968 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 89665.74 | 86457.01 | 1.0221 | 6.31391968 | 5.299705 | 24.54 | 16.64 | 0.00869491 | 46801.3 | 11.01 | 11.01 | 0.00850000 | 32497.3 | -999.0 | -999.00 | -999.00 | -999.00 | 11526.266 | 78139.47 | 26.40 | 0.00840708 | 17.04 | 1.19517000 | 22.5516 | 24.00 | 0.00877874 | 24.00 | 0.00877874 | 46.7372 | 72157.40 | 0.00 | 90460.30 | 70815.00 | 6.06456759 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.26 | 14.43 | 0.00991458 | 40406.2 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20996.848 | 20996.848 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.299705 | 6.31391968 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20996.85 | 20996.85 | 1.0000 | 1.89417591 | 1.589911 | 1.77 | 1.20 | 0.00393649 | 11635.1 | 12.80 | 11.50 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20996.85 | -4.30 | 0.00265759 | -4.30 | 1.19517000 | 75.1721 | 20.14 | 0.00780866 | 20.73 | 0.00773344 | 50.3147 | 21160.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 78468.451 | 62826.178 | 4.740279 | -999.0 | -999.000 | -999.0000 | 1.01116 | 1.00000 | 1021.0292 | 1004.8586 | 1.1914 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.740279 | 5.64743587 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 80242.15 | 77187.87 | 1.0226 | 5.64743587 | 4.740279 | 24.60 | 16.67 | 0.00870881 | 46902.0 | 11.00 | 11.00 | 0.00850000 | 32485.5 | -999.0 | -999.00 | -999.00 | -999.00 | 10376.523 | 69865.63 | 26.40 | 0.00840708 | 17.04 | 1.19517000 | 25.2131 | 24.00 | 0.00881056 | 24.00 | 0.00881056 | 46.9042 | 64538.40 | 0.00 | 80911.51 | 63339.92 | 5.42440484 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.26 | 14.43 | 0.00991458 | 40406.2 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22239.388 | 22239.388 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.740279 | 5.64743587 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 20:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22239.39 | 22239.39 | 1.0000 | 1.69423076 | 1.422084 | -0.26 | -0.63 | 0.00349109 | 8465.0 | 12.80 | 11.50 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22239.39 | -4.30 | 0.00265759 | -4.30 | 1.19517000 | 84.0436 | 21.00 | 0.00788122 | 21.00 | 0.00787062 | 50.3517 | 25343.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 86804.380 | 69500.384 | 5.243853 | -999.0 | -999.000 | -999.0000 | 1.01788 | 1.00000 | 1021.0044 | 1004.8586 | 1.1914 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.243853 | 6.24737923 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 88724.32 | 85542.07 | 1.0221 | 6.24737923 | 5.243853 | 24.55 | 16.64 | 0.00869546 | 46809.1 | 11.01 | 11.01 | 0.00850000 | 32497.3 | -999.0 | -999.00 | -999.00 | -999.00 | 11404.794 | 77319.53 | 26.40 | 0.00840708 | 17.04 | 1.19517000 | 22.7918 | 24.00 | 0.00878070 | 24.00 | 0.00878070 | 46.7474 | 71336.60 | 0.00 | 89506.97 | 70068.70 | 6.00065497 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.26 | 14.43 | 0.00991458 | 40406.2 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22050.461 | 22050.461 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.243853 | 6.24737923 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22050.46 | 22050.46 | 1.0000 | 1.87421377 | 1.573156 | 1.09 | 0.75 | 0.00388997 | 10833.5 | 12.80 | 11.50 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22050.46 | -4.30 | 0.00265759 | -4.30 | 1.19517000 | 75.9728 | 18.14 | 0.00778670 | 19.60 | 0.00775446 | 54.1016 | 27832.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.30 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.74 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.24 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1699.00 | 2472.17 | 18.33 |
CORE_MID | 957.83 | 3778.17 | 115.00 |
CORE_TOP | 1290.17 | 4370.17 | 643.50 |
PERIMETER_TOP_ZN_3 | 2255.00 | 4778.17 | 1696.33 |
PERIMETER_TOP_ZN_2 | 2682.83 | 4284.33 | 1569.67 |
PERIMETER_TOP_ZN_1 | 2518.50 | 4245.00 | 1367.50 |
PERIMETER_TOP_ZN_4 | 2554.67 | 4680.33 | 1681.17 |
PERIMETER_BOT_ZN_3 | 1565.00 | 4968.00 | 1246.00 |
PERIMETER_BOT_ZN_2 | 2246.00 | 3996.67 | 1075.83 |
PERIMETER_BOT_ZN_1 | 1937.33 | 4331.33 | 930.83 |
PERIMETER_BOT_ZN_4 | 2150.33 | 4367.50 | 1154.67 |
PERIMETER_MID_ZN_3 | 1656.67 | 4496.17 | 1053.17 |
PERIMETER_MID_ZN_2 | 1844.17 | 3627.17 | 969.33 |
PERIMETER_MID_ZN_1 | 2058.50 | 3953.67 | 779.50 |
PERIMETER_MID_ZN_4 | 2058.83 | 4431.17 | 1058.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4174.50 | 5258.50 | 1939.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.17 | 0.00 | 0.17 | 0.00 |
CORE_TOP | 0.67 | 0.00 | 0.67 | 0.00 |
PERIMETER_TOP_ZN_3 | 8.83 | 0.00 | 6.67 | 0.00 |
PERIMETER_TOP_ZN_2 | 3.33 | 7.67 | 1.00 | 7.67 |
PERIMETER_TOP_ZN_1 | 2.00 | 13.50 | 0.83 | 13.50 |
PERIMETER_TOP_ZN_4 | 3.17 | 16.17 | 1.17 | 9.50 |
PERIMETER_BOT_ZN_3 | 2.33 | 0.00 | 2.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.17 | 4.00 | 0.00 | 4.00 |
PERIMETER_BOT_ZN_1 | 260.17 | 7.17 | 260.17 | 7.17 |
PERIMETER_BOT_ZN_4 | 0.17 | 9.67 | 0.00 | 5.00 |
PERIMETER_MID_ZN_3 | 1.00 | 0.00 | 0.83 | 0.00 |
PERIMETER_MID_ZN_2 | 0.50 | 11.50 | 0.33 | 11.50 |
PERIMETER_MID_ZN_1 | 0.33 | 14.50 | 0.17 | 14.50 |
PERIMETER_MID_ZN_4 | 0.67 | 16.33 | 0.50 | 9.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 268.83 | 78.83 | 265.83 | 65.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.52 | 52.94 | 2698.04 | 1.023 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.52 | 52.94 | 2698.04 | 0.710 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.52 | 52.94 | 2698.04 | 0.683 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.54 | 11.16 | 568.77 | 0.700 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 1.242 | 0.051 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.54 | 11.16 | 568.77 | 1.306 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 1.328 | 0.051 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.54 | 11.16 | 568.77 | 0.645 | 0.026 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 1.079 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.54 | 11.16 | 568.77 | 1.011 | 0.841 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 1.112 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.54 | 11.16 | 568.77 | 0.714 | 0.040 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 1.173 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.54 | 11.16 | 568.77 | 1.313 | 0.041 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 1.309 | 0.043 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.52 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.52 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.52 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.52 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.52 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.52 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.51 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.66 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 16154555.94 | 0.00 | 16154555.94 | 0.00 | 16154555.94 | 13393058.27 | 5083.51 | 32.95 | 3643.54 | 27.00 |
CORE_MID | 11278257.60 | 0.00 | 11278257.60 | 0.00 | 11278257.60 | 13393058.27 | 5983.10 | 74.02 | 2702.88 | 36.93 |
CORE_TOP | 10862222.08 | 0.00 | 10862222.08 | 0.00 | 10862222.08 | 13393058.27 | 6071.64 | 57.40 | 2630.95 | 49.07 |
PERIMETER_TOP_ZN_3 | 2348767.22 | 0.00 | 2348767.22 | 327463.48 | 2676230.69 | 2823374.22 | 6003.18 | 59.24 | 2697.58 | 49.07 |
PERIMETER_TOP_ZN_2 | 2633323.61 | 0.00 | 2633323.61 | 218307.67 | 2851631.28 | 1787429.43 | 4101.49 | 3.99 | 4654.52 | 49.07 |
PERIMETER_TOP_ZN_1 | 4367855.25 | 0.00 | 4367855.25 | 327463.48 | 4695318.73 | 2823374.22 | 4113.18 | 3.43 | 4643.39 | 49.07 |
PERIMETER_TOP_ZN_4 | 2824791.19 | 0.00 | 2824791.19 | 218307.67 | 3043098.86 | 1787312.18 | 4082.11 | 4.24 | 4673.65 | 49.07 |
PERIMETER_BOT_ZN_3 | 2161910.97 | 0.00 | 2161910.97 | 174110.49 | 2336021.46 | 2823374.22 | 5765.61 | 67.13 | 2927.26 | 27.00 |
PERIMETER_BOT_ZN_2 | 2282311.99 | 0.00 | 2282311.99 | 116072.96 | 2398384.95 | 1787429.43 | 4083.39 | 8.55 | 4668.06 | 27.00 |
PERIMETER_BOT_ZN_1 | 3385212.61 | 0.00 | 3385212.61 | 2905154.06 | 6290366.67 | 2823374.22 | 4104.62 | 13.97 | 4641.41 | 27.00 |
PERIMETER_BOT_ZN_4 | 2355497.88 | 0.00 | 2355497.88 | 116072.96 | 2471570.84 | 1787312.18 | 4047.25 | 9.86 | 4702.89 | 27.00 |
PERIMETER_MID_ZN_3 | 2393128.28 | 0.00 | 2393128.28 | 272588.12 | 2665716.39 | 2823374.22 | 5953.69 | 77.72 | 2728.58 | 36.93 |
PERIMETER_MID_ZN_2 | 2724651.93 | 0.00 | 2724651.93 | 181724.32 | 2906376.25 | 1787429.43 | 4008.40 | 4.45 | 4747.15 | 945.93 |
PERIMETER_MID_ZN_1 | 4388589.71 | 0.00 | 4388589.71 | 272588.12 | 4661177.83 | 2823374.22 | 4036.13 | 3.80 | 4720.08 | 36.93 |
PERIMETER_MID_ZN_4 | 2781596.93 | 0.00 | 2781596.93 | 181724.32 | 2963321.25 | 1787312.18 | 3998.50 | 5.79 | 4755.72 | 36.93 |
Total Facility | 72942673.18 | 0.00 | 72942673.18 | 5311577.65 | 78254250.83 | 67843644.98 | 6205.61 | 264.41 | 4809.29 | 970.64 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7518 | 0.0000 | 0.7518 | 0.0000 | 0.7518 | 0.4247 | 2292.01 | 32.95 | 3618.04 |
CORE_MID | 0.5230 | 0.0000 | 0.5230 | 0.0000 | 0.5230 | 0.4247 | 3200.33 | 74.02 | 2668.65 |
CORE_TOP | 0.5035 | 0.0000 | 0.5035 | 0.0000 | 0.5035 | 0.4247 | 3287.34 | 57.40 | 2598.26 |
PERIMETER_TOP_ZN_3 | 0.1089 | 0.0000 | 0.1089 | 0.0076 | 0.1165 | 0.0895 | 3218.87 | 59.24 | 2664.89 |
PERIMETER_TOP_ZN_2 | 0.1222 | 0.0000 | 0.1222 | 0.0051 | 0.1273 | 0.0567 | 1317.18 | 3.99 | 4621.83 |
PERIMETER_TOP_ZN_1 | 0.2028 | 0.0000 | 0.2028 | 0.0076 | 0.2104 | 0.0895 | 1328.87 | 3.43 | 4610.70 |
PERIMETER_TOP_ZN_4 | 0.1308 | 0.0000 | 0.1308 | 0.0051 | 0.1358 | 0.0567 | 1297.81 | 4.24 | 4640.96 |
PERIMETER_BOT_ZN_3 | 0.1004 | 0.0000 | 0.1004 | 0.0040 | 0.1044 | 0.0895 | 2974.11 | 67.13 | 2901.76 |
PERIMETER_BOT_ZN_2 | 0.1061 | 0.0000 | 0.1061 | 0.0027 | 0.1088 | 0.0567 | 1291.89 | 8.55 | 4642.56 |
PERIMETER_BOT_ZN_1 | 0.1574 | 0.0000 | 0.1574 | 0.1317 | 0.2891 | 0.0895 | 1313.12 | 13.97 | 4615.91 |
PERIMETER_BOT_ZN_4 | 0.1093 | 0.0000 | 0.1093 | 0.0027 | 0.1120 | 0.0567 | 1255.75 | 9.86 | 4677.39 |
PERIMETER_MID_ZN_3 | 0.1110 | 0.0000 | 0.1110 | 0.0063 | 0.1173 | 0.0895 | 3170.92 | 77.72 | 2694.36 |
PERIMETER_MID_ZN_2 | 0.1155 | 0.0000 | 0.1155 | 0.0044 | 0.1199 | 0.0567 | 1225.64 | 4.45 | 3803.90 |
PERIMETER_MID_ZN_1 | 0.2039 | 0.0000 | 0.2039 | 0.0063 | 0.2102 | 0.0895 | 1253.35 | 3.80 | 4685.85 |
PERIMETER_MID_ZN_4 | 0.1288 | 0.0000 | 0.1288 | 0.0042 | 0.1330 | 0.0567 | 1215.74 | 5.79 | 4721.47 |
Total Facility | 3.3752 | 0.0000 | 3.3752 | 0.1876 | 3.5628 | 2.1513 | 3402.99 | 264.41 | 4765.24 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 37385414.28 | 0.00 | 37385414.28 | 22614548.33 | 4025.44 | 7.80 | 4726.76 | 27.00 |
PACU_VAV_MID | 33449144.51 | 0.00 | 33449144.51 | 22614548.33 | 4004.75 | 5.82 | 4749.43 | 36.93 |
PACU_VAV_TOP | 32697906.89 | 0.00 | 32697906.89 | 22614548.33 | 4093.39 | 2.67 | 4663.93 | 48.89 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.7387 | 0.0000 | 1.7387 | 0.7171 | 1233.94 | 7.80 | 4701.26 |
PACU_VAV_MID | 1.5514 | 0.0000 | 1.5514 | 0.7171 | 1221.97 | 5.82 | 4715.21 |
PACU_VAV_TOP | 1.5162 | 0.0000 | 1.5162 | 0.7171 | 1309.09 | 2.67 | 4631.24 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 3682.28 | 0.00 | 0.00 | 0.00 | 1099.61 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 3167.63 | 0.00 | 0.00 | 0.00 | 1661.89 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 3108.23 | 0.00 | 0.00 | 0.00 | 1716.31 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.4953 | 0.0000 | 0.0000 | 0.0000 | 1.1035 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.3561 | 0.0000 | 0.0000 | 0.0000 | 1.1112 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.3244 | 0.0000 | 0.0000 | 0.0000 | 1.1074 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 829 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1444.29 | 13157.78 | 16-APR-17:10 | 215384.09 | 02-JAN-07:10 |
Electricity:Building | 1072.30 | 12913.45 | 16-APR-17:10 | 84122.50 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 322.66 | 4214.70 | 01-JAN-00:10 | 25737.69 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1072.30 | 12913.45 | 16-APR-17:10 | 84122.50 | 02-JAN-08:10 |
InteriorLights:Electricity | 366.86 | 1672.11 | 01-JAN-10:30 | 38257.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 366.86 | 1672.11 | 01-JAN-10:30 | 38257.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 366.86 | 1672.11 | 01-JAN-10:30 | 38257.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 366.86 | 1672.11 | 01-JAN-10:30 | 38257.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 201.92 | 2251.11 | 01-JAN-00:10 | 14360.82 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 201.92 | 2251.11 | 01-JAN-00:10 | 14360.82 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 35.45 | 428.29 | 02-APR-17:10 | 3027.38 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 11.11 | 42.19 | 01-JAN-10:30 | 1592.13 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 11.11 | 42.19 | 01-JAN-10:30 | 1592.13 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.32 | 271.13 | 16-APR-17:10 | 1916.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.92 | 26.71 | 01-JAN-08:40 | 1007.95 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.92 | 26.71 | 01-JAN-08:40 | 1007.95 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 35.17 | 428.29 | 02-APR-17:10 | 3027.37 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.83 | 42.19 | 01-JAN-08:40 | 1592.13 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.83 | 42.19 | 01-JAN-08:40 | 1592.13 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 22.36 | 271.13 | 12-MAR-17:10 | 1916.45 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.96 | 26.71 | 01-JAN-10:20 | 1007.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.96 | 26.71 | 01-JAN-10:20 | 1007.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 35.41 | 428.29 | 02-APR-17:10 | 3027.38 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 11.07 | 42.19 | 01-JAN-10:30 | 1592.13 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 11.07 | 42.19 | 01-JAN-10:30 | 1592.13 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.30 | 271.13 | 16-APR-17:10 | 1916.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.90 | 26.71 | 01-JAN-08:40 | 1007.95 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.90 | 26.71 | 01-JAN-08:40 | 1007.95 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 35.14 | 428.29 | 02-APR-17:10 | 3027.37 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.81 | 42.19 | 01-JAN-08:40 | 1592.13 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.81 | 42.19 | 01-JAN-08:40 | 1592.13 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 22.34 | 271.13 | 12-MAR-17:10 | 1916.45 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.94 | 26.71 | 01-JAN-10:20 | 1007.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.94 | 26.71 | 01-JAN-10:20 | 1007.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 35.45 | 428.29 | 02-APR-17:10 | 3027.38 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 11.11 | 42.19 | 01-JAN-10:30 | 1592.13 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 11.11 | 42.19 | 01-JAN-10:30 | 1592.13 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.32 | 271.13 | 16-APR-17:10 | 1916.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.92 | 26.71 | 01-JAN-08:40 | 1007.95 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.92 | 26.71 | 01-JAN-08:40 | 1007.95 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 35.17 | 428.29 | 02-APR-17:10 | 3027.37 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 10.83 | 42.19 | 01-JAN-08:40 | 1592.13 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 10.83 | 42.19 | 01-JAN-08:40 | 1592.13 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 22.36 | 271.13 | 12-MAR-17:10 | 1916.45 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.96 | 26.71 | 01-JAN-10:20 | 1007.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.96 | 26.71 | 01-JAN-10:20 | 1007.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 259.95 | 243.72 | 01-JAN-00:10 | 172929.19 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 17.12 | 243.72 | 01-JAN-00:10 | 1242.18 | 09-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 17.12 | 243.72 | 01-JAN-00:10 | 1242.18 | 09-JAN-08:20 |
ElectricityPurchased:Facility | 1444.29 | 13157.78 | 22-JUL-18:20 | 215384.09 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1444.29 | 13157.78 | 22-JUL-18:20 | 215384.09 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1444.29 | 13157.78 | 22-JUL-18:20 | 215384.09 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1444.29 | 13157.78 | 22-JUL-18:20 | 215384.09 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1444.29 | 13157.78 | 22-JUL-18:20 | 215384.09 | 02-JAN-07:10 |
ElectricityNet:Plant | 1444.29 | 13157.78 | 22-JUL-18:20 | 215384.09 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1444.29 | 13157.78 | 22-JUL-18:20 | 215384.09 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1444.29 | 13157.78 | 22-JUL-18:20 | 215384.09 | 02-JAN-07:10 |
Heating:Electricity | 123.79 | 0.00 | 01-JAN-00:10 | 166765.69 | 02-JAN-07:10 |
General:Heating:Electricity | 123.79 | 0.00 | 01-JAN-00:10 | 166765.69 | 02-JAN-07:10 |
Fans:Electricity | 76.13 | 0.00 | 01-JAN-00:10 | 21559.88 | 13-JUN-15:40 |
General:Fans:Electricity | 76.13 | 0.00 | 01-JAN-00:10 | 21559.88 | 13-JUN-15:40 |
ExteriorLights:Electricity | 111.90 | 0.00 | 01-JAN-08:20 | 8596.48 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 111.90 | 0.00 | 01-JAN-08:20 | 8596.48 | 01-JAN-06:10 |
Cooling:Electricity | 42.91 | 0.00 | 01-JAN-00:10 | 46522.12 | 13-JUN-16:00 |
General:Cooling:Electricity | 42.91 | 0.00 | 01-JAN-00:10 | 46522.12 | 13-JUN-16:00 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-06:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-06:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 10.31 | 0.00 | 01-JAN-00:10 | 1075.04 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 216.86 | 2003.43 | 02-JAN-06:10 | 68192.36 | 10-JAN-08:00 |
NaturalGas:HVAC | 78.34 | 0.00 | 01-JAN-00:10 | 59207.84 | 10-JAN-08:00 |
Heating:NaturalGas | 78.34 | 0.00 | 01-JAN-00:10 | 59207.84 | 10-JAN-08:00 |
General:Heating:NaturalGas | 78.34 | 0.00 | 01-JAN-00:10 | 59207.84 | 10-JAN-08:00 |
NaturalGas:Plant | 138.52 | 2003.43 | 02-JAN-06:10 | 10291.73 | 17-FEB-12:10 |
WaterSystems:NaturalGas | 138.52 | 2003.43 | 02-JAN-06:10 | 10291.73 | 17-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 138.52 | 2003.43 | 02-JAN-06:10 | 10291.73 | 17-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1370.65 | 0.00 | 01-JAN-00:10 | 346223.60 | 13-JUN-15:40 |
EnergyTransfer:Building | 958.93 | 0.00 | 01-JAN-00:10 | 150227.41 | 13-JUN-15:40 |
EnergyTransfer:Zone:CORE_BOTTOM | 218.66 | 0.00 | 01-JAN-00:10 | 25184.42 | 24-JUL-08:00 |
Heating:EnergyTransfer | 82.42 | 0.00 | 01-JAN-00:10 | 146021.93 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.03 | 0.00 | 01-JAN-00:10 | 7806.93 | 02-JAN-07:10 |
General:Heating:EnergyTransfer | 82.42 | 0.00 | 01-JAN-00:10 | 146021.93 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.03 | 0.00 | 01-JAN-00:10 | 7806.93 | 02-JAN-07:10 |
Cooling:EnergyTransfer | 876.51 | 0.00 | 01-JAN-00:10 | 150227.41 | 13-JUN-15:40 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 218.63 | 0.00 | 01-JAN-00:10 | 25184.42 | 24-JUL-08:00 |
General:Cooling:EnergyTransfer | 876.51 | 0.00 | 01-JAN-00:10 | 150227.41 | 13-JUN-15:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 218.63 | 0.00 | 01-JAN-00:10 | 25184.42 | 24-JUL-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 36.47 | 0.00 | 01-JAN-00:10 | 9903.27 | 26-DEC-06:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 16.47 | 0.00 | 01-JAN-00:10 | 9903.27 | 26-DEC-06:30 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 16.47 | 0.00 | 01-JAN-00:10 | 9903.27 | 26-DEC-06:30 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 20.00 | 0.00 | 01-JAN-00:10 | 9252.01 | 21-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 20.00 | 0.00 | 01-JAN-00:10 | 9252.01 | 21-JUL-14:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 17.71 | 0.00 | 01-JAN-00:10 | 7159.94 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.04 | 0.00 | 01-JAN-00:10 | 7159.94 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.04 | 0.00 | 01-JAN-00:10 | 7159.94 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.67 | 0.00 | 01-JAN-00:10 | 3881.01 | 24-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.67 | 0.00 | 01-JAN-00:10 | 3881.01 | 24-JUL-16:00 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 20.42 | 0.00 | 01-JAN-00:10 | 4530.21 | 02-JAN-08:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 4.89 | 0.00 | 01-JAN-00:10 | 4530.21 | 02-JAN-08:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 4.89 | 0.00 | 01-JAN-00:10 | 4530.21 | 02-JAN-08:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.53 | 0.00 | 01-JAN-00:10 | 4302.06 | 24-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.53 | 0.00 | 01-JAN-00:10 | 4302.06 | 24-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 142.36 | 0.00 | 01-JAN-00:10 | 17700.04 | 24-JUL-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.30 | 0.00 | 01-JAN-00:10 | 17463.16 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.30 | 0.00 | 01-JAN-00:10 | 17463.16 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 142.06 | 0.00 | 01-JAN-00:10 | 17700.04 | 24-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 142.06 | 0.00 | 01-JAN-00:10 | 17700.04 | 24-JUL-16:00 |
EnergyTransfer:Zone:CORE_TOP | 129.17 | 0.00 | 01-JAN-00:10 | 25809.84 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 2.48 | 0.00 | 01-JAN-00:10 | 25809.84 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 2.48 | 0.00 | 01-JAN-00:10 | 25809.84 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 126.70 | 0.00 | 01-JAN-00:10 | 18885.90 | 24-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 126.70 | 0.00 | 01-JAN-00:10 | 18885.90 | 24-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 28.44 | 0.00 | 01-JAN-00:10 | 8231.19 | 26-DEC-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 7.15 | 0.00 | 01-JAN-00:10 | 8231.19 | 26-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 7.15 | 0.00 | 01-JAN-00:10 | 8231.19 | 26-DEC-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.30 | 0.00 | 01-JAN-00:10 | 5621.27 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.30 | 0.00 | 01-JAN-00:10 | 5621.27 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 29.57 | 0.00 | 01-JAN-00:10 | 8416.87 | 13-JUN-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.15 | 0.00 | 01-JAN-00:10 | 6657.81 | 26-DEC-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.15 | 0.00 | 01-JAN-00:10 | 6657.81 | 26-DEC-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.42 | 0.00 | 01-JAN-00:10 | 8416.87 | 13-JUN-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.42 | 0.00 | 01-JAN-00:10 | 8416.87 | 13-JUN-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 49.94 | 0.00 | 01-JAN-00:10 | 13272.82 | 11-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.21 | 0.00 | 01-JAN-00:10 | 9779.54 | 26-DEC-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.21 | 0.00 | 01-JAN-00:10 | 9779.54 | 26-DEC-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 44.73 | 0.00 | 01-JAN-00:10 | 13272.82 | 11-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 44.73 | 0.00 | 01-JAN-00:10 | 13272.82 | 11-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.35 | 0.00 | 01-JAN-00:10 | 9869.17 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.53 | 0.00 | 01-JAN-00:10 | 6653.67 | 26-DEC-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.53 | 0.00 | 01-JAN-00:10 | 6653.67 | 26-DEC-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.82 | 0.00 | 01-JAN-00:10 | 9869.17 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.82 | 0.00 | 01-JAN-00:10 | 9869.17 | 13-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.33 | 0.00 | 01-JAN-00:10 | 6418.89 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.01 | 0.00 | 01-JAN-00:10 | 6418.89 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.01 | 0.00 | 01-JAN-00:10 | 6418.89 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.32 | 0.00 | 01-JAN-00:10 | 4065.59 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.32 | 0.00 | 01-JAN-00:10 | 4065.59 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 25.21 | 0.00 | 01-JAN-00:10 | 6513.83 | 13-JUN-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.67 | 0.00 | 01-JAN-00:10 | 5006.79 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.67 | 0.00 | 01-JAN-00:10 | 5006.79 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 23.54 | 0.00 | 01-JAN-00:10 | 6513.83 | 13-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 23.54 | 0.00 | 01-JAN-00:10 | 6513.83 | 13-JUN-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 46.18 | 0.00 | 01-JAN-00:10 | 11518.31 | 10-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 16.53 | 0.00 | 01-JAN-00:10 | 11518.31 | 10-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 16.53 | 0.00 | 01-JAN-00:10 | 11518.31 | 10-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 29.65 | 0.00 | 01-JAN-00:10 | 10828.34 | 11-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 29.65 | 0.00 | 01-JAN-00:10 | 10828.34 | 11-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 24.97 | 0.00 | 01-JAN-00:10 | 7432.97 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.78 | 0.00 | 01-JAN-00:10 | 5055.64 | 02-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.78 | 0.00 | 01-JAN-00:10 | 5055.64 | 02-JAN-07:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 23.20 | 0.00 | 01-JAN-00:10 | 7432.97 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 23.20 | 0.00 | 01-JAN-00:10 | 7432.97 | 13-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.79 | 0.00 | 01-JAN-00:10 | 7050.84 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.41 | 0.00 | 01-JAN-00:10 | 7050.84 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.41 | 0.00 | 01-JAN-00:10 | 7050.84 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.37 | 0.00 | 01-JAN-00:10 | 5178.46 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.37 | 0.00 | 01-JAN-00:10 | 5178.46 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.49 | 0.00 | 01-JAN-00:10 | 8492.76 | 13-JUN-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.54 | 0.00 | 01-JAN-00:10 | 4998.79 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.54 | 0.00 | 01-JAN-00:10 | 4998.79 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 27.95 | 0.00 | 01-JAN-00:10 | 8492.76 | 13-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 27.95 | 0.00 | 01-JAN-00:10 | 8492.76 | 13-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 50.27 | 0.00 | 01-JAN-00:10 | 13003.67 | 11-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.67 | 0.00 | 01-JAN-00:10 | 6948.07 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.67 | 0.00 | 01-JAN-00:10 | 6948.07 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 48.61 | 0.00 | 01-JAN-00:10 | 13003.67 | 11-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 48.61 | 0.00 | 01-JAN-00:10 | 13003.67 | 11-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 29.59 | 0.00 | 01-JAN-00:10 | 9424.67 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.59 | 0.00 | 01-JAN-00:10 | 4983.69 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.59 | 0.00 | 01-JAN-00:10 | 4983.69 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 28.00 | 0.00 | 01-JAN-00:10 | 9424.67 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 28.00 | 0.00 | 01-JAN-00:10 | 9424.67 | 13-JUN-17:00 |
PlantLoopHeatingDemand:Facility | 52.59 | 0.00 | 01-JAN-00:10 | 6268.75 | 14-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 52.59 | 0.00 | 01-JAN-00:10 | 6268.75 | 14-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 52.59 | 0.00 | 01-JAN-00:10 | 6268.75 | 14-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 52.59 | 0.00 | 01-JAN-00:10 | 6268.75 | 14-FEB-12:10 |
EnergyTransfer:HVAC | 359.14 | 0.00 | 01-JAN-00:10 | 191542.92 | 13-JUN-15:40 |
HeatingCoils:EnergyTransfer | 186.45 | 0.00 | 01-JAN-00:10 | 187546.71 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 172.68 | 0.00 | 01-JAN-00:10 | 191542.92 | 13-JUN-15:40 |
EnergyTransfer:Plant | 52.59 | 0.00 | 01-JAN-00:10 | 6268.75 | 14-FEB-12:10 |
WaterSystems:EnergyTransfer | 52.59 | 0.00 | 01-JAN-00:10 | 6268.75 | 14-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 52.59 | 0.00 | 01-JAN-00:10 | 6268.75 | 14-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.025 | -218.631 | 0.000 | 0.000 | 32.903 | 86.497 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -136.961 |
CORE_MID | 0.000 | 0.000 | 0.296 | -142.062 | 0.000 | 0.000 | 34.290 | 86.497 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -94.447 |
CORE_TOP | 0.000 | 0.000 | 2.476 | -126.699 | 0.000 | 0.000 | 35.194 | 86.497 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -112.893 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 7.148 | -21.296 | 0.000 | 0.000 | 7.662 | 11.114 | 24.333 | 14.380 | 0.000 | 0.002 | 0.001 | 0.000 | -35.425 | 0.000 | -4.604 | -3.315 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 4.145 | -25.422 | 0.000 | 0.000 | 4.805 | 6.917 | 15.404 | 31.804 | 0.000 | 0.001 | 0.000 | 0.000 | -22.816 | 0.000 | -3.124 | -11.714 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 5.207 | -44.732 | 0.000 | 0.000 | 7.538 | 10.833 | 24.332 | 63.827 | 0.000 | 0.002 | 0.000 | 0.000 | -35.343 | 0.000 | -4.793 | -26.872 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.530 | -25.817 | 0.000 | 0.000 | 4.890 | 6.959 | 15.403 | 31.170 | 0.000 | 0.001 | 0.000 | 0.000 | -23.746 | 0.000 | -3.134 | -10.257 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 3.008 | -20.322 | 0.000 | 0.000 | 7.630 | 11.075 | 24.333 | 14.670 | 0.000 | 0.001 | 0.002 | 0.000 | -36.940 | 0.000 | -2.574 | -0.881 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.668 | -23.542 | 0.000 | 0.000 | 4.759 | 6.901 | 15.404 | 31.830 | 0.000 | 0.001 | 0.001 | 0.000 | -24.209 | 0.000 | -1.785 | -11.026 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 16.531 | -29.650 | 0.000 | 0.000 | 7.660 | 10.810 | 24.332 | 64.347 | 0.000 | 0.044 | 0.000 | 0.000 | -37.466 | 0.000 | -38.996 | -17.612 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.776 | -23.198 | 0.000 | 0.000 | 4.822 | 6.939 | 15.403 | 31.289 | 0.000 | 0.001 | 0.001 | 0.000 | -25.167 | 0.000 | -1.789 | -10.077 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 2.412 | -24.373 | 0.000 | 0.000 | 7.539 | 11.114 | 24.333 | 13.948 | 0.000 | 0.002 | 6.831 | 0.000 | -37.734 | 0.000 | -4.073 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.542 | -27.946 | 0.000 | 0.000 | 3.527 | 6.917 | 15.404 | 31.513 | 0.000 | 0.001 | 0.002 | 0.000 | -24.169 | 0.000 | -2.748 | -4.043 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 1.665 | -48.607 | 0.000 | 0.000 | 7.419 | 10.833 | 24.332 | 63.355 | 0.000 | 0.002 | 0.002 | 0.000 | -37.528 | 0.000 | -4.227 | -17.244 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 1.588 | -28.004 | 0.000 | 0.000 | 4.818 | 6.959 | 15.403 | 30.906 | 0.000 | 0.001 | 0.002 | 0.000 | -25.231 | 0.000 | -2.767 | -3.673 |
TOPFLOOR_PLENUM | 16.468 | -20.002 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.001 | 10.745 | 0.000 | 0.000 | 0.000 | -7.213 | -0.001 |
MIDFLOOR_PLENUM | 7.044 | -10.670 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.002 | 10.728 | 0.000 | 0.000 | 0.000 | -7.104 | -0.001 |
FIRSTFLOOR_PLENUM | 4.892 | -15.530 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.002 | 16.390 | 0.000 | 0.000 | 0.000 | -5.754 | -0.001 |
Total Facility | 28.404 | -46.202 | 54.020 | -830.303 | 0.000 | 0.000 | 175.457 | 366.863 | 705.434 | 423.039 | 0.000 | 0.064 | 44.707 | 0.000 | -365.773 | 0.000 | -94.683 | -461.016 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 24-JUL-06:02 | 0.00 | 0.00 | 0.00 | -41650.75 | 0.00 | 0.00 | 697.51 | 2517.53 | 8796.80 | 0.00 | 0.00 | 0.00 | 29638.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 24-JUL-06:02 | 0.00 | 0.00 | 0.00 | -27956.23 | 0.00 | 0.00 | 717.15 | 2517.53 | 3025.92 | 0.00 | 0.00 | 0.00 | 21695.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-16:00 | 0.00 | 0.00 | 0.00 | -18885.48 | 0.00 | 0.00 | 3497.12 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 1027.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | -5621.06 | 0.00 | 0.00 | 737.23 | 759.45 | 1435.25 | 2887.41 | 0.00 | 22.56 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -220.83 |
PERIMETER_TOP_ZN_2 | 16-JUL-09:32 | 0.00 | 0.00 | 0.00 | -14390.05 | 0.00 | 0.00 | 15.41 | 26.71 | 302.86 | 9253.48 | 0.00 | 0.00 | 5031.69 | 0.00 | -0.00 | 0.00 | -240.10 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:22 | 0.00 | 0.00 | 0.00 | -22427.66 | 0.00 | 0.00 | 23.36 | 42.19 | 478.41 | 15561.58 | 0.00 | 0.00 | 6581.18 | 0.00 | -0.00 | 0.00 | -259.06 | 0.00 |
PERIMETER_TOP_ZN_4 | 11-JUN-17:12 | 0.00 | 0.00 | 0.00 | -16633.90 | 0.00 | 0.00 | 0.00 | 26.71 | 244.42 | 10995.73 | 0.00 | 0.00 | 5637.64 | 0.00 | -0.00 | 0.00 | -270.60 | 0.00 |
PERIMETER_BOT_ZN_3 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | -4065.57 | 0.00 | 0.00 | 737.23 | 759.45 | 1435.25 | 2950.41 | 0.00 | 12.25 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1829.00 |
PERIMETER_BOT_ZN_2 | 23-JUL-11:23 | 0.00 | 0.00 | 0.00 | -9209.23 | 0.00 | 0.00 | 16.90 | 26.71 | 302.86 | 3365.39 | 0.00 | 0.00 | 5551.28 | 0.00 | -0.00 | 0.00 | -53.90 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-13:22 | 0.00 | 0.00 | 0.00 | -17839.87 | 0.00 | 0.00 | 25.92 | 42.19 | 478.41 | 15730.28 | 0.00 | 0.00 | 1689.05 | 0.00 | -0.00 | 0.00 | -125.98 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-APR-17:31 | 0.00 | 0.00 | 0.00 | -13082.57 | 0.00 | 0.00 | 0.00 | 26.71 | 244.42 | 9586.80 | 0.00 | 0.00 | 3239.10 | 0.00 | -0.00 | 0.00 | -14.46 | 0.00 |
PERIMETER_MID_ZN_3 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | -5178.26 | 0.00 | 0.00 | 737.23 | 759.45 | 1435.25 | 2905.48 | 0.00 | 18.97 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -678.11 |
PERIMETER_MID_ZN_2 | 23-JUL-08:42 | 0.00 | 0.00 | 0.00 | -14069.72 | 0.00 | 0.00 | 13.64 | 26.71 | 302.86 | 11166.73 | 0.00 | 0.00 | 2669.84 | 0.00 | -0.00 | 0.00 | -110.05 | 0.00 |
PERIMETER_MID_ZN_1 | 24-SEP-13:12 | 0.00 | 0.00 | 0.00 | -20625.47 | 0.00 | 0.00 | 24.12 | 42.19 | 478.41 | 15371.59 | 0.00 | 0.00 | 4895.94 | 0.00 | -0.00 | 0.00 | -186.78 | 0.00 |
PERIMETER_MID_ZN_4 | 09-JUL-16:51 | 0.00 | 0.00 | 0.00 | -16223.80 | 0.00 | 0.00 | 13.68 | 26.71 | 302.86 | 12686.46 | 0.00 | 0.00 | 3330.68 | 0.00 | -0.00 | 0.00 | -136.58 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-14:50 | 0.00 | -9252.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 | 9239.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 24-JUL-16:00 | 0.00 | -3880.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3935.88 | 0.00 | -0.00 | 0.00 | -54.94 | 0.00 |
FIRSTFLOOR_PLENUM | 24-JUL-16:00 | 0.00 | -4301.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4344.37 | 0.00 | -0.00 | 0.00 | -42.43 | 0.00 |
Total Facility | 13-JUN-15:40 | 0.00 | -17025.38 | 0.00 | -133201.73 | 0.00 | 0.00 | 17714.92 | 30098.83 | 42072.41 | 66793.80 | 0.00 | 471.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6924.59 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-06:01 | 0.00 | 0.00 | 19829.65 | 0.00 | 0.00 | 0.00 | 478.81 | 839.14 | 4989.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26137.11 |
CORE_MID | 02-JAN-06:01 | 0.00 | 0.00 | 22353.77 | 0.00 | 0.00 | 0.00 | 500.41 | 839.14 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26719.24 |
CORE_TOP | 02-JAN-05:01 | 0.00 | 0.00 | 29829.39 | 0.00 | 0.00 | 0.00 | 0.00 | 839.14 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33110.59 |
PERIMETER_TOP_ZN_3 | 18-DEC-05:01 | 0.00 | 0.00 | 9022.67 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2003.83 | 0.00 | -375.67 | -7334.88 |
PERIMETER_TOP_ZN_2 | 18-DEC-05:01 | 0.00 | 0.00 | 8901.98 | 0.00 | 0.00 | 0.00 | 0.00 | 111.99 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1362.32 | 0.00 | -254.49 | -7723.05 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:01 | 0.00 | 0.00 | 13545.92 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1802.31 | 0.00 | 0.00 | -12435.31 |
PERIMETER_TOP_ZN_4 | 18-DEC-05:01 | 0.00 | 0.00 | 8842.73 | 0.00 | 0.00 | 0.00 | 0.00 | 111.98 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1335.54 | 0.00 | -254.50 | -7690.57 |
PERIMETER_BOT_ZN_3 | 02-JAN-05:01 | 0.00 | 0.00 | 7360.54 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1811.52 | 0.00 | 0.00 | -6240.72 |
PERIMETER_BOT_ZN_2 | 02-JAN-05:01 | 0.00 | 0.00 | 6945.93 | 0.00 | 0.00 | 0.00 | 0.00 | 111.99 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1254.44 | 0.00 | 0.00 | -6129.37 |
PERIMETER_BOT_ZN_1 | 10-JAN-08:00 | 0.00 | 0.00 | 11517.49 | 0.00 | 0.00 | 0.00 | 231.67 | 530.72 | 637.88 | 0.00 | 0.00 | 0.00 | 8389.59 | 0.00 | -2935.12 | 0.00 | -18372.23 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 6951.63 | 0.00 | 0.00 | 0.00 | 0.00 | 111.98 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1238.71 | 0.00 | 0.00 | -6150.80 |
PERIMETER_MID_ZN_3 | 02-JAN-05:01 | 0.00 | 0.00 | 8156.06 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1818.14 | 0.00 | 0.00 | -7029.62 |
PERIMETER_MID_ZN_2 | 02-JAN-05:01 | 0.00 | 0.00 | 7008.75 | 0.00 | 0.00 | 0.00 | 0.00 | 111.99 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1222.40 | 0.00 | 0.00 | -6224.24 |
PERIMETER_MID_ZN_1 | 02-JAN-05:01 | 0.00 | 0.00 | 10228.03 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1910.57 | 0.00 | 0.00 | -9009.15 |
PERIMETER_MID_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 6979.63 | 0.00 | 0.00 | 0.00 | 0.00 | 111.98 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1220.40 | 0.00 | 0.00 | -6197.10 |
TOPFLOOR_PLENUM | 26-DEC-06:16 | 12200.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -216.36 | -11983.98 |
MIDFLOOR_PLENUM | 02-JAN-07:04 | 8052.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8052.90 |
FIRSTFLOOR_PLENUM | 02-JAN-07:03 | 5741.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5741.83 |
Total Facility | 02-JAN-06:01 | 14116.54 | 0.00 | 161800.41 | 0.00 | 0.00 | 0.00 | 2513.34 | 4250.75 | 17291.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19809.19 | 0.00 | -1968.05 | -178195.32 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.0576 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.2997 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.7232 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7403 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.8995 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.2439 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.0288 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4515 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.8616 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5045 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.9497 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5530 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0944 | 3.0944 | 0.7922 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3064 | 2.3064 | 0.7703 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3062 | 2.3062 | 0.7910 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6189 | 0.6189 | 0.1671 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8253 | 0.8253 | 0.1651 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2370 | 1.2370 | 0.2474 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9122 | 0.9122 | 0.1824 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5016 | 0.5016 | 0.1670 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6790 | 0.6790 | 0.1358 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0181 | 1.0181 | 0.2036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7645 | 0.7645 | 0.1529 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5578 | 0.5578 | 0.1623 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8328 | 0.8328 | 0.1666 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1656 | 1.1656 | 0.2331 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8605 | 0.8605 | 0.1721 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.0576 | 5.2997 | 6.0576 | 1.4515 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.7232 | 4.7403 | 5.7232 | 1.5045 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.8995 | 5.2439 | 5.8995 | 1.5530 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5472 | 1.5472 | 0.7922 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1532 | 1.1532 | 0.7703 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1531 | 1.1531 | 0.7910 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3094 | 0.3094 | 0.1671 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4126 | 0.4126 | 0.1651 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6185 | 0.6185 | 0.2474 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4561 | 0.4561 | 0.1824 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2508 | 0.2508 | 0.1670 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3395 | 0.3395 | 0.1358 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5091 | 0.5091 | 0.2036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3822 | 0.3822 | 0.1529 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2789 | 0.2789 | 0.1623 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4164 | 0.4164 | 0.1666 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5828 | 0.5828 | 0.2331 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4303 | 0.4303 | 0.1721 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.0288 | 1.4515 | 1.4515 | 1.4515 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.8616 | 1.5045 | 1.5045 | 1.5045 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.9497 | 1.5530 | 1.5530 | 1.5530 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 265.83 |
Number of hours cooling loads not met | 65.00 |
Number of hours not met | 330.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 123.79 | 166765.69 | 78.34 | 59207.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 42.91 | 46522.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 366.86 | 38257.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 111.90 | 8596.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 17.12 | 1242.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 76.13 | 21559.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 138.52 | 10291.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1444.29 |
Natural Gas | 0.00 | 216.86 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1661.15 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 73.64 |
Space Heating | 24.85 |
Space Cooling | 8.61 |
Fans (All) | 15.28 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 289.89 |
Subtotal | 289.89 |
Natural Gas [MJ/m2] | |
Space Heating | 15.72 |
Service Water Heating | 27.80 |
Miscellaneous (All) | 43.53 |
Subtotal | 43.53 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 22.08 |
Space Heating | 12.17 |
Space Cooling | 2.58 |
Fans (All) | 4.58 |
Service Water Heating | 8.34 |
Receptacle Equipment | 42.47 |
Miscellaneous | 7.78 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8746.50 | 13.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8742.67 | 17.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8748.83 | 11.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8746.50 | 13.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8745.00 | 15.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8744.50 | 15.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8740.50 | 19.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8740.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 19.50 | 0.00 | 0.00 | 0.00 |
Average | 8752.51 | 7.49 | 0.00 | 0.00 | 0.00 |
Sum | 157545.17 | 134.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8709.50 | 50.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8752.83 | 7.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8750.00 | 10.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8750.50 | 9.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8744.83 | 15.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8709.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 50.50 | 0.00 | 0.00 | 0.00 |
Average | 8751.52 | 8.48 | 0.00 | 0.00 | 0.00 |
Sum | 157527.33 | 152.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128274.50 | 29.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128301.67 | 2.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 29.50 | 0.00 | 0.00 | 0.00 |
Average | 34141.56 | 1.77 | 0.00 | 0.00 | 0.00 |
Sum | 614548.17 | 31.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:45
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117435E+11 | 17483.26 | 26-JAN-08:06 | 4.27 | 3.77 | 0.191590E+10 | 2606.65 | 20-JAN-10:30 | 4.27 | 3.77 |
February | 0.118475E+11 | 16320.87 | 10-FEB-08:20 | 4.67 | 4.37 | 0.177970E+10 | 2606.65 | 22-FEB-10:09 | 8.33 | 8.16 |
March | 0.147104E+11 | 17387.33 | 23-MAR-07:07 | 7.00 | 4.55 | 0.213166E+10 | 2606.66 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.188863E+11 | 28786.15 | 20-APR-05:03 | 1.17 | -0.2 | 0.191225E+10 | 2606.76 | 14-APR-13:00 | 1.17 | -0.2 |
May | 0.216706E+11 | 29123.69 | 01-MAY-06:03 | 6.17 | 4.70 | 0.207489E+10 | 2606.65 | 05-MAY-13:00 | 8.00 | 6.98 |
June | 0.242513E+11 | 40784.70 | 14-JUN-06:02 | 12.00 | 12.00 | 0.207024E+10 | 2606.77 | 08-JUN-13:09 | 12.00 | 12.00 |
July | 0.241843E+11 | 41652.95 | 24-JUL-06:02 | 13.17 | 13.07 | 0.192447E+10 | 2606.68 | 03-JUL-09:09 | 13.17 | 13.07 |
August | 0.265405E+11 | 41090.87 | 07-AUG-06:02 | 11.67 | 10.35 | 0.215903E+10 | 2606.70 | 08-AUG-13:09 | 17.83 | 16.43 |
September | 0.225315E+11 | 40869.14 | 14-SEP-06:02 | 12.17 | 11.07 | 0.191641E+10 | 2606.78 | 19-SEP-13:39 | 14.67 | 13.92 |
October | 0.172495E+11 | 21097.21 | 03-OCT-16:00 | 14.00 | 8.96 | 0.198297E+10 | 2606.71 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.135631E+11 | 18575.70 | 15-NOV-08:07 | 8.00 | 7.91 | 0.195012E+10 | 2608.74 | 28-NOV-14:39 | 7.00 | 4.69 |
December | 0.114529E+11 | 14471.06 | 22-DEC-08:20 | 3.33 | 2.75 | 0.187328E+10 | 2608.61 | 07-DEC-10:09 | 3.33 | 2.75 |
Annual Sum or Average | 0.218631E+12 | 0.236909E+11 | ||||||||
Minimum of Months | 0.114529E+11 | 14471.06 | 1.17 | -0.2 | 0.177970E+10 | 2606.65 | 1.17 | -0.2 | ||
Maximum of Months | 0.265405E+11 | 41652.95 | 14.00 | 13.07 | 0.215903E+10 | 2608.74 | 17.83 | 16.43 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26680444.65 | 718.60 | 21-JAN-13:15 | 7.67 | 6.07 | 0.00 | 0.00 | 01-JAN-00:10 | 7.67 | 6.07 |
February | 74379998.10 | 1110.00 | 27-FEB-17:45 | 7.17 | 6.55 | 0.00 | 0.00 | 01-FEB-00:10 | 7.17 | 6.55 |
March | 0.201119E+09 | 2088.81 | 25-MAR-12:50 | 13.67 | 10.83 | 0.00 | 0.00 | 01-MAR-00:10 | 13.67 | 10.83 |
April | 0.210201E+10 | 7752.35 | 28-APR-14:50 | 20.08 | 13.54 | 0.00 | 0.00 | 01-APR-00:10 | 20.08 | 13.54 |
May | 0.244046E+10 | 8203.61 | 22-MAY-14:50 | 23.83 | 16.03 | 0.00 | 0.00 | 01-MAY-00:10 | 23.83 | 16.03 |
June | 0.360569E+10 | 9223.92 | 13-JUN-14:30 | 25.55 | 17.64 | 0.00 | 0.00 | 01-JUN-00:10 | 25.55 | 17.64 |
July | 0.423778E+10 | 9252.01 | 21-JUL-14:50 | 27.00 | 15.89 | 0.00 | 0.00 | 01-JUL-00:10 | 27.00 | 15.89 |
August | 0.409310E+10 | 8358.12 | 14-AUG-15:00 | 25.00 | 16.02 | 0.00 | 0.00 | 01-AUG-00:10 | 25.00 | 16.02 |
September | 0.257748E+10 | 7110.05 | 13-SEP-14:20 | 23.00 | 16.22 | 0.00 | 0.00 | 01-SEP-00:10 | 23.00 | 16.22 |
October | 0.609350E+09 | 3394.48 | 03-OCT-14:40 | 14.00 | 9.11 | 0.00 | 0.00 | 01-OCT-00:10 | 14.00 | 9.11 |
November | 33952331.00 | 872.42 | 11-NOV-13:47 | 9.00 | 7.08 | 0.00 | 0.00 | 01-NOV-00:10 | 9.00 | 7.08 |
December | 80436.30 | 111.12 | 06-DEC-13:05 | 7.00 | 5.20 | 0.00 | 0.00 | 01-DEC-00:10 | 7.00 | 5.20 |
Annual Sum or Average | 0.200021E+11 | 0.00 | ||||||||
Minimum of Months | 80436.30 | 111.12 | 7.00 | 5.20 | 0.00 | 0.00 | 7.00 | 5.20 | ||
Maximum of Months | 0.423778E+10 | 9252.01 | 27.00 | 17.64 | 0.00 | 0.00 | 27.00 | 17.64 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 64782634.77 | 1986.44 | 07-JAN-06:11 | 3.00 | 2.13 | 0.00 | 0.00 | 01-JAN-00:10 | 3.00 | 2.13 |
February | 76669940.96 | 1770.18 | 16-FEB-06:11 | 3.00 | 2.70 | 0.00 | 0.00 | 01-FEB-00:10 | 3.00 | 2.70 |
March | 0.186553E+09 | 2010.80 | 04-MAR-06:11 | 3.00 | 0.90 | 0.00 | 0.00 | 01-MAR-00:10 | 3.00 | 0.90 |
April | 0.828722E+09 | 2743.64 | 28-APR-16:00 | 20.00 | 12.32 | 0.00 | 0.00 | 01-APR-00:10 | 20.00 | 12.32 |
May | 0.108615E+10 | 2880.80 | 23-MAY-16:00 | 18.00 | 14.38 | 0.00 | 0.00 | 01-MAY-00:10 | 18.00 | 14.38 |
June | 0.186712E+10 | 3804.84 | 13-JUN-15:40 | 26.33 | 17.74 | 0.00 | 0.00 | 01-JUN-00:10 | 26.33 | 17.74 |
July | 0.224829E+10 | 3881.01 | 24-JUL-16:00 | 20.00 | 16.18 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 16.18 |
August | 0.230890E+10 | 3313.81 | 14-AUG-16:00 | 26.00 | 15.86 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 15.86 |
September | 0.148279E+10 | 3165.71 | 13-SEP-16:00 | 23.00 | 16.22 | 0.00 | 0.00 | 01-SEP-00:10 | 23.00 | 16.22 |
October | 0.395171E+09 | 1377.00 | 19-OCT-06:03 | 5.33 | 4.70 | 0.00 | 0.00 | 01-OCT-00:10 | 5.33 | 4.70 |
November | 0.109962E+09 | 1956.78 | 17-NOV-06:11 | 2.33 | 1.25 | 0.00 | 0.00 | 01-NOV-00:10 | 2.33 | 1.25 |
December | 15309960.48 | 2087.62 | 23-DEC-06:11 | 3.00 | 2.55 | 0.00 | 0.00 | 01-DEC-00:10 | 3.00 | 2.55 |
Annual Sum or Average | 0.106704E+11 | 0.00 | ||||||||
Minimum of Months | 15309960.48 | 1377.00 | 2.33 | 0.90 | 0.00 | 0.00 | 2.33 | 0.90 | ||
Maximum of Months | 0.230890E+10 | 3881.01 | 26.33 | 17.74 | 0.00 | 0.00 | 26.33 | 17.74 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144176E+09 | 2522.57 | 06-JAN-06:11 | 3.80 | 3.31 | 0.00 | 0.00 | 01-JAN-00:10 | 3.80 | 3.31 |
February | 0.169153E+09 | 2817.50 | 16-FEB-06:11 | 3.00 | 2.70 | 0.00 | 0.00 | 01-FEB-00:10 | 3.00 | 2.70 |
March | 0.314655E+09 | 2698.86 | 04-MAR-06:11 | 3.00 | 0.90 | 0.00 | 0.00 | 01-MAR-00:10 | 3.00 | 0.90 |
April | 0.135727E+10 | 3219.13 | 28-APR-16:00 | 20.00 | 12.32 | 0.00 | 0.00 | 01-APR-00:10 | 20.00 | 12.32 |
May | 0.172112E+10 | 3289.88 | 01-MAY-06:08 | 6.17 | 4.70 | 0.00 | 0.00 | 01-MAY-00:10 | 6.17 | 4.70 |
June | 0.255378E+10 | 4231.70 | 13-JUN-16:00 | 26.50 | 17.70 | 0.00 | 0.00 | 01-JUN-00:10 | 26.50 | 17.70 |
July | 0.290669E+10 | 4302.06 | 24-JUL-16:00 | 20.00 | 16.18 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 16.18 |
August | 0.308796E+10 | 3900.11 | 14-AUG-16:00 | 26.00 | 15.86 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 15.86 |
September | 0.224851E+10 | 3867.97 | 13-SEP-16:00 | 23.00 | 16.22 | 0.00 | 0.00 | 01-SEP-00:10 | 23.00 | 16.22 |
October | 0.751516E+09 | 2305.87 | 06-OCT-06:10 | 3.00 | 3.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3.00 | 3.00 |
November | 0.211625E+09 | 2321.90 | 17-NOV-07:02 | 1.17 | 0.28 | 0.00 | 0.00 | 01-NOV-00:10 | 1.17 | 0.28 |
December | 64049126.96 | 2682.77 | 08-DEC-06:11 | 1.67 | 1.24 | 0.00 | 0.00 | 01-DEC-00:10 | 1.67 | 1.24 |
Annual Sum or Average | 0.155305E+11 | 0.00 | ||||||||
Minimum of Months | 64049126.96 | 2305.87 | 1.17 | 0.28 | 0.00 | 0.00 | 1.17 | 0.28 | ||
Maximum of Months | 0.308796E+10 | 4302.06 | 26.50 | 17.70 | 0.00 | 0.00 | 26.50 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.774331E+10 | 7704.24 | 20-JAN-17:00 | 5.00 | 4.51 | 0.167852E+10 | 2533.04 | 20-JAN-14:00 | 5.00 | 4.51 |
February | 0.775638E+10 | 7656.89 | 10-FEB-17:00 | 6.00 | 4.60 | 0.156629E+10 | 2493.85 | 10-FEB-14:00 | 6.00 | 4.60 |
March | 0.947988E+10 | 7768.51 | 31-MAR-16:00 | 9.00 | 4.96 | 0.191468E+10 | 2533.94 | 31-MAR-13:00 | 9.00 | 4.96 |
April | 0.119081E+11 | 15332.31 | 28-APR-16:00 | 20.00 | 12.32 | 0.187090E+10 | 2606.71 | 14-APR-13:00 | 20.00 | 12.32 |
May | 0.139383E+11 | 15872.34 | 23-MAY-16:00 | 18.00 | 14.38 | 0.204696E+10 | 2606.63 | 22-MAY-13:00 | 18.00 | 14.38 |
June | 0.161403E+11 | 16975.45 | 13-JUN-16:00 | 26.50 | 17.70 | 0.205757E+10 | 2606.69 | 08-JUN-13:09 | 26.50 | 17.70 |
July | 0.165307E+11 | 27955.81 | 24-JUL-06:02 | 13.17 | 13.07 | 0.191316E+10 | 2606.64 | 03-JUL-09:09 | 13.17 | 13.07 |
August | 0.177449E+11 | 16549.88 | 18-AUG-16:00 | 21.00 | 16.54 | 0.214965E+10 | 2606.68 | 08-AUG-13:09 | 21.00 | 16.54 |
September | 0.146446E+11 | 16309.34 | 13-SEP-16:00 | 23.00 | 16.22 | 0.189856E+10 | 2606.73 | 19-SEP-13:50 | 14.33 | 13.96 |
October | 0.103228E+11 | 13202.11 | 04-OCT-16:00 | 14.00 | 10.28 | 0.187368E+10 | 2606.64 | 02-OCT-09:20 | 14.00 | 10.28 |
November | 0.842873E+10 | 8026.61 | 10-NOV-16:50 | 7.67 | 6.84 | 0.173770E+10 | 2576.63 | 10-NOV-14:00 | 7.67 | 6.84 |
December | 0.742430E+10 | 7204.30 | 21-DEC-17:00 | 6.00 | 5.49 | 0.159595E+10 | 2433.70 | 21-DEC-14:00 | 6.00 | 5.49 |
Annual Sum or Average | 0.142062E+12 | 0.223036E+11 | ||||||||
Minimum of Months | 0.742430E+10 | 7204.30 | 5.00 | 4.51 | 0.156629E+10 | 2433.70 | 5.00 | 4.51 | ||
Maximum of Months | 0.177449E+11 | 27955.81 | 26.50 | 17.70 | 0.214965E+10 | 2606.73 | 26.50 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.598103E+10 | 7453.26 | 20-JAN-16:40 | 5.67 | 5.02 | 0.157217E+10 | 2419.86 | 20-JAN-14:00 | 5.67 | 5.02 |
February | 0.621223E+10 | 7448.99 | 09-FEB-17:00 | 6.00 | 4.60 | 0.145989E+10 | 2389.26 | 09-FEB-16:00 | 6.00 | 4.60 |
March | 0.814569E+10 | 7664.98 | 31-MAR-16:00 | 9.00 | 4.96 | 0.178870E+10 | 2439.75 | 31-MAR-15:00 | 9.00 | 4.96 |
April | 0.110876E+11 | 16382.89 | 28-APR-16:00 | 20.00 | 12.32 | 0.180344E+10 | 2606.70 | 14-APR-13:00 | 20.00 | 12.32 |
May | 0.129228E+11 | 17164.37 | 23-MAY-16:00 | 18.00 | 14.38 | 0.199458E+10 | 2606.63 | 22-MAY-13:00 | 18.00 | 14.38 |
June | 0.154269E+11 | 18736.50 | 13-JUN-16:00 | 26.50 | 17.70 | 0.203854E+10 | 2606.67 | 09-JUN-13:00 | 26.50 | 17.70 |
July | 0.159903E+11 | 18885.90 | 24-JUL-16:00 | 20.00 | 16.18 | 0.189828E+10 | 2606.64 | 21-JUL-13:09 | 20.00 | 16.18 |
August | 0.167750E+11 | 17538.48 | 17-AUG-16:00 | 21.00 | 16.00 | 0.213214E+10 | 2606.68 | 08-AUG-13:09 | 21.00 | 16.00 |
September | 0.131901E+11 | 16877.28 | 13-SEP-16:00 | 23.00 | 16.22 | 0.186259E+10 | 2606.72 | 19-SEP-13:50 | 14.33 | 13.96 |
October | 0.903516E+10 | 12112.68 | 03-OCT-16:00 | 14.00 | 8.96 | 0.175113E+10 | 2606.56 | 02-OCT-13:00 | 14.00 | 8.96 |
November | 0.684581E+10 | 7713.63 | 10-NOV-16:30 | 9.00 | 7.52 | 0.160763E+10 | 2484.01 | 10-NOV-14:00 | 9.00 | 7.52 |
December | 0.508618E+10 | 7001.46 | 21-DEC-15:20 | 7.67 | 6.81 | 0.149142E+10 | 2320.64 | 21-DEC-14:00 | 7.67 | 6.81 |
Annual Sum or Average | 0.126699E+12 | 0.214005E+11 | ||||||||
Minimum of Months | 0.508618E+10 | 7001.46 | 5.67 | 4.60 | 0.145989E+10 | 2320.64 | 5.67 | 4.60 | ||
Maximum of Months | 0.167750E+11 | 18885.90 | 26.50 | 17.70 | 0.213214E+10 | 2606.72 | 26.50 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324824E+09 | 1287.57 | 19-JAN-16:20 | 7.33 | 6.98 | 0.308619E+09 | 444.74 | 19-JAN-14:00 | 7.33 | 6.98 |
February | 0.439065E+09 | 1251.97 | 09-FEB-16:10 | 7.67 | 5.50 | 0.280980E+09 | 437.15 | 03-FEB-14:00 | 7.67 | 5.50 |
March | 0.865813E+09 | 1448.05 | 30-MAR-15:40 | 12.00 | 6.06 | 0.346295E+09 | 483.57 | 30-MAR-13:00 | 12.00 | 6.06 |
April | 0.197430E+10 | 3942.56 | 28-APR-15:30 | 20.05 | 13.01 | 0.357589E+09 | 549.50 | 14-APR-13:00 | 20.05 | 13.01 |
May | 0.250102E+10 | 4384.56 | 22-MAY-15:20 | 23.67 | 15.81 | 0.400123E+09 | 549.50 | 22-MAY-13:00 | 23.67 | 15.81 |
June | 0.344067E+10 | 5621.27 | 13-JUN-16:00 | 26.50 | 17.70 | 0.422655E+09 | 549.50 | 09-JUN-13:00 | 26.50 | 17.70 |
July | 0.373158E+10 | 5373.53 | 21-JUL-15:50 | 27.83 | 16.07 | 0.395778E+09 | 549.50 | 21-JUL-13:09 | 27.83 | 16.07 |
August | 0.362037E+10 | 4845.56 | 14-AUG-16:00 | 26.00 | 15.86 | 0.440985E+09 | 549.50 | 11-AUG-13:00 | 26.00 | 15.86 |
September | 0.247978E+10 | 4173.69 | 13-SEP-15:30 | 23.00 | 16.22 | 0.375348E+09 | 549.51 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.123158E+10 | 1849.51 | 06-OCT-15:50 | 17.00 | 9.21 | 0.336155E+09 | 537.95 | 06-OCT-13:00 | 17.00 | 9.21 |
November | 0.527834E+09 | 1377.83 | 10-NOV-15:30 | 11.50 | 8.42 | 0.308845E+09 | 468.66 | 10-NOV-14:00 | 11.50 | 8.42 |
December | 0.159558E+09 | 1140.03 | 21-DEC-15:20 | 7.67 | 6.81 | 0.294809E+09 | 413.01 | 21-DEC-14:00 | 7.67 | 6.81 |
Annual Sum or Average | 0.212964E+11 | 0.426818E+10 | ||||||||
Minimum of Months | 0.159558E+09 | 1140.03 | 7.33 | 5.50 | 0.280980E+09 | 413.01 | 7.33 | 5.50 | ||
Maximum of Months | 0.373158E+10 | 5621.27 | 27.83 | 17.70 | 0.440985E+09 | 549.51 | 27.83 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.385656E+09 | 1412.72 | 20-JAN-10:30 | 5.00 | 4.55 | 0.195468E+09 | 306.30 | 20-JAN-10:39 | 5.33 | 4.86 |
February | 0.515520E+09 | 1506.55 | 24-FEB-10:30 | 5.50 | 4.13 | 0.180579E+09 | 320.85 | 24-FEB-10:39 | 5.67 | 4.28 |
March | 0.857259E+09 | 1458.93 | 25-MAR-09:50 | 10.67 | 7.61 | 0.218701E+09 | 308.36 | 31-MAR-09:00 | 9.00 | 5.32 |
April | 0.276747E+10 | 8651.47 | 30-APR-09:02 | 18.33 | 12.10 | 0.241225E+09 | 347.89 | 14-APR-13:00 | 18.33 | 12.10 |
May | 0.316418E+10 | 10044.28 | 21-MAY-09:23 | 13.00 | 9.81 | 0.261267E+09 | 347.88 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.390225E+10 | 11586.51 | 25-JUN-10:23 | 19.50 | 13.70 | 0.269173E+09 | 347.93 | 13-JUN-09:09 | 19.50 | 13.70 |
July | 0.416948E+10 | 14393.75 | 16-JUL-09:32 | 16.00 | 13.59 | 0.252933E+09 | 347.89 | 03-JUL-09:09 | 16.00 | 13.59 |
August | 0.438809E+10 | 14173.82 | 20-AUG-09:22 | 16.50 | 13.27 | 0.281799E+09 | 347.89 | 14-AUG-09:50 | 16.50 | 13.27 |
September | 0.322645E+10 | 7115.48 | 10-SEP-09:23 | 17.50 | 14.17 | 0.246604E+09 | 347.89 | 06-SEP-09:09 | 17.50 | 14.17 |
October | 0.133082E+10 | 3447.03 | 04-OCT-10:00 | 13.00 | 9.81 | 0.218361E+09 | 347.88 | 04-OCT-09:09 | 13.00 | 9.81 |
November | 0.517855E+09 | 1375.54 | 03-NOV-09:50 | 6.83 | 5.00 | 0.195347E+09 | 300.68 | 03-NOV-09:00 | 7.00 | 5.17 |
December | 0.196822E+09 | 1192.97 | 06-DEC-10:10 | 4.50 | 3.47 | 0.186899E+09 | 273.74 | 06-DEC-10:20 | 5.00 | 3.82 |
Annual Sum or Average | 0.254219E+11 | 0.274836E+10 | ||||||||
Minimum of Months | 0.196822E+09 | 1192.97 | 4.50 | 3.47 | 0.180579E+09 | 273.74 | 5.00 | 3.82 | ||
Maximum of Months | 0.438809E+10 | 14393.75 | 19.50 | 14.17 | 0.281799E+09 | 347.93 | 23.00 | 15.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129890E+10 | 6758.29 | 20-JAN-12:00 | 8.00 | 6.08 | 0.331297E+09 | 549.49 | 17-JAN-14:30 | 8.00 | 6.08 |
February | 0.160252E+10 | 8304.78 | 17-FEB-13:40 | 6.00 | 3.25 | 0.309381E+09 | 549.49 | 24-FEB-14:20 | 6.00 | 4.60 |
March | 0.157909E+10 | 4131.80 | 28-MAR-12:05 | 11.67 | 7.18 | 0.359534E+09 | 549.50 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.485748E+10 | 21117.83 | 30-APR-13:02 | 22.17 | 13.02 | 0.369482E+09 | 549.53 | 14-APR-13:00 | 22.17 | 13.02 |
May | 0.462562E+10 | 10418.11 | 22-MAY-13:10 | 22.17 | 14.96 | 0.399587E+09 | 549.51 | 22-MAY-13:50 | 22.83 | 15.60 |
June | 0.532829E+10 | 10924.81 | 11-JUN-13:53 | 18.00 | 14.39 | 0.415510E+09 | 549.53 | 08-JUN-13:09 | 18.00 | 14.39 |
July | 0.605900E+10 | 13800.97 | 30-JUL-14:23 | 17.00 | 12.42 | 0.391678E+09 | 549.52 | 21-JUL-13:09 | 17.00 | 12.42 |
August | 0.722639E+10 | 21463.10 | 06-AUG-13:22 | 17.50 | 13.70 | 0.438898E+09 | 549.51 | 21-AUG-13:30 | 21.00 | 14.72 |
September | 0.661252E+10 | 22430.93 | 10-SEP-13:22 | 21.00 | 15.72 | 0.383706E+09 | 550.02 | 11-SEP-13:00 | 21.00 | 15.99 |
October | 0.336508E+10 | 14512.45 | 01-OCT-13:32 | 12.67 | 9.47 | 0.355409E+09 | 549.51 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.141900E+10 | 7144.79 | 03-NOV-12:40 | 9.00 | 5.48 | 0.328035E+09 | 549.49 | 03-NOV-13:00 | 9.00 | 5.72 |
December | 0.758845E+09 | 5503.20 | 18-DEC-13:25 | 8.00 | 5.46 | 0.309553E+09 | 549.49 | 21-DEC-14:00 | 8.00 | 6.98 |
Annual Sum or Average | 0.447327E+11 | 0.439207E+10 | ||||||||
Minimum of Months | 0.758845E+09 | 4131.80 | 6.00 | 3.25 | 0.309381E+09 | 549.49 | 6.00 | 4.60 | ||
Maximum of Months | 0.722639E+10 | 22430.93 | 22.17 | 15.72 | 0.438898E+09 | 550.02 | 22.83 | 15.99 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.381989E+09 | 1770.50 | 19-JAN-16:00 | 8.00 | 7.45 | 0.196737E+09 | 326.16 | 19-JAN-16:10 | 7.67 | 7.22 |
February | 0.575423E+09 | 2745.91 | 27-FEB-16:30 | 8.00 | 6.72 | 0.183543E+09 | 338.68 | 09-FEB-16:00 | 8.00 | 6.72 |
March | 0.881441E+09 | 2996.68 | 23-MAR-16:50 | 10.00 | 6.65 | 0.217526E+09 | 338.67 | 31-MAR-15:00 | 9.00 | 4.96 |
April | 0.270591E+10 | 15067.85 | 30-APR-16:22 | 24.00 | 12.86 | 0.220136E+09 | 347.85 | 14-APR-13:00 | 24.00 | 12.86 |
May | 0.325557E+10 | 12429.59 | 21-MAY-16:32 | 19.33 | 11.98 | 0.244572E+09 | 347.85 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.415046E+10 | 16635.46 | 11-JUN-17:12 | 14.00 | 12.24 | 0.259423E+09 | 347.86 | 09-JUN-13:00 | 14.00 | 12.24 |
July | 0.446770E+10 | 15777.40 | 16-JUL-16:52 | 18.00 | 14.98 | 0.245105E+09 | 347.85 | 21-JUL-13:09 | 26.17 | 16.40 |
August | 0.423753E+10 | 16478.67 | 13-AUG-16:32 | 19.67 | 15.02 | 0.272152E+09 | 347.85 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.309281E+10 | 11825.75 | 10-SEP-16:03 | 20.67 | 16.45 | 0.230404E+09 | 347.86 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.137842E+10 | 5334.89 | 03-OCT-15:40 | 14.00 | 8.96 | 0.209786E+09 | 347.83 | 04-OCT-13:00 | 14.00 | 10.28 |
November | 0.520537E+09 | 1799.30 | 10-NOV-15:40 | 11.33 | 8.41 | 0.196019E+09 | 330.37 | 10-NOV-15:50 | 11.17 | 8.40 |
December | 0.169636E+09 | 1431.92 | 21-DEC-14:40 | 8.00 | 6.98 | 0.186922E+09 | 288.17 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.258174E+11 | 0.266233E+10 | ||||||||
Minimum of Months | 0.169636E+09 | 1431.92 | 8.00 | 6.65 | 0.183543E+09 | 288.17 | 7.67 | 4.96 | ||
Maximum of Months | 0.446770E+10 | 16635.46 | 24.00 | 16.45 | 0.272152E+09 | 347.86 | 26.17 | 16.40 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.426823E+09 | 1230.36 | 19-JAN-15:30 | 8.50 | 7.46 | 0.309874E+09 | 436.33 | 19-JAN-14:00 | 8.50 | 7.46 |
February | 0.537013E+09 | 1199.71 | 10-FEB-15:50 | 7.00 | 5.15 | 0.281434E+09 | 429.23 | 10-FEB-14:00 | 7.00 | 5.15 |
March | 0.967232E+09 | 1359.86 | 30-MAR-14:00 | 13.00 | 7.37 | 0.345016E+09 | 467.03 | 30-MAR-13:00 | 13.00 | 7.37 |
April | 0.184328E+10 | 2305.19 | 28-APR-15:40 | 20.03 | 12.78 | 0.350920E+09 | 549.48 | 28-APR-13:00 | 20.03 | 12.78 |
May | 0.221139E+10 | 2669.91 | 23-MAY-14:00 | 19.00 | 14.77 | 0.399849E+09 | 549.49 | 22-MAY-13:00 | 19.00 | 14.77 |
June | 0.285660E+10 | 4065.59 | 13-JUN-16:00 | 26.50 | 17.70 | 0.425228E+09 | 549.50 | 09-JUN-13:00 | 26.50 | 17.70 |
July | 0.315130E+10 | 4005.83 | 21-JUL-16:00 | 28.00 | 16.11 | 0.398705E+09 | 549.49 | 18-JUL-13:09 | 28.00 | 16.11 |
August | 0.310296E+10 | 3392.52 | 14-AUG-16:00 | 26.00 | 15.86 | 0.445019E+09 | 549.50 | 11-AUG-13:00 | 26.00 | 15.86 |
September | 0.234677E+10 | 3101.47 | 13-SEP-15:30 | 23.00 | 16.22 | 0.382729E+09 | 549.49 | 28-SEP-13:00 | 16.00 | 13.03 |
October | 0.161803E+10 | 1637.23 | 06-OCT-16:00 | 17.00 | 9.21 | 0.348064E+09 | 525.84 | 06-OCT-13:00 | 17.00 | 9.21 |
November | 0.918718E+09 | 1381.75 | 10-NOV-15:10 | 11.83 | 8.42 | 0.316578E+09 | 471.17 | 10-NOV-14:00 | 11.83 | 8.42 |
December | 0.342174E+09 | 1155.78 | 22-DEC-14:10 | 7.00 | 5.54 | 0.296669E+09 | 420.08 | 22-DEC-14:09 | 7.00 | 5.54 |
Annual Sum or Average | 0.203223E+11 | 0.430009E+10 | ||||||||
Minimum of Months | 0.342174E+09 | 1155.78 | 7.00 | 5.15 | 0.281434E+09 | 420.08 | 7.00 | 5.15 | ||
Maximum of Months | 0.315130E+10 | 4065.59 | 28.00 | 17.70 | 0.445019E+09 | 549.50 | 28.00 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.438739E+09 | 1176.28 | 20-JAN-10:20 | 4.67 | 4.23 | 0.197483E+09 | 308.78 | 20-JAN-10:30 | 5.00 | 4.55 |
February | 0.551210E+09 | 1225.50 | 24-FEB-10:30 | 5.50 | 4.13 | 0.182588E+09 | 318.11 | 24-FEB-10:39 | 5.67 | 4.28 |
March | 0.835853E+09 | 1165.08 | 31-MAR-09:50 | 8.33 | 5.01 | 0.220219E+09 | 306.81 | 31-MAR-09:00 | 9.00 | 5.32 |
April | 0.233789E+10 | 7766.47 | 30-APR-07:33 | 16.93 | 12.78 | 0.243964E+09 | 347.89 | 14-APR-13:00 | 16.93 | 12.78 |
May | 0.271157E+10 | 6089.61 | 23-MAY-09:10 | 19.17 | 14.75 | 0.266470E+09 | 347.88 | 22-MAY-13:00 | 19.17 | 14.75 |
June | 0.334553E+10 | 7692.47 | 25-JUN-10:32 | 20.00 | 13.96 | 0.272536E+09 | 347.89 | 20-JUN-09:09 | 20.00 | 13.96 |
July | 0.367132E+10 | 9208.74 | 23-JUL-11:23 | 21.00 | 15.99 | 0.255267E+09 | 347.88 | 03-JUL-09:09 | 21.00 | 15.99 |
August | 0.394445E+10 | 6097.00 | 21-AUG-09:30 | 18.00 | 13.89 | 0.285760E+09 | 347.88 | 23-AUG-09:09 | 16.17 | 12.09 |
September | 0.305789E+10 | 5525.85 | 12-SEP-09:20 | 17.67 | 14.44 | 0.251918E+09 | 347.89 | 06-SEP-09:09 | 17.67 | 14.44 |
October | 0.151274E+10 | 3057.28 | 04-OCT-10:00 | 13.00 | 9.81 | 0.228314E+09 | 347.88 | 04-OCT-09:09 | 13.00 | 9.81 |
November | 0.793915E+09 | 1198.02 | 03-NOV-09:30 | 6.50 | 4.66 | 0.201233E+09 | 312.91 | 03-NOV-09:39 | 6.67 | 4.83 |
December | 0.340453E+09 | 1049.65 | 08-DEC-10:30 | 5.00 | 3.66 | 0.188618E+09 | 285.75 | 08-DEC-10:39 | 5.33 | 3.83 |
Annual Sum or Average | 0.235416E+11 | 0.279437E+10 | ||||||||
Minimum of Months | 0.340453E+09 | 1049.65 | 4.67 | 3.66 | 0.182588E+09 | 285.75 | 5.00 | 3.83 | ||
Maximum of Months | 0.394445E+10 | 9208.74 | 21.00 | 15.99 | 0.285760E+09 | 347.89 | 21.00 | 15.99 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.641491E+09 | 3538.95 | 21-JAN-11:30 | 6.00 | 5.05 | 0.314173E+09 | 541.22 | 17-JAN-14:09 | 6.00 | 5.05 |
February | 0.838983E+09 | 4039.89 | 04-FEB-14:00 | 9.00 | 6.13 | 0.291891E+09 | 549.50 | 17-FEB-14:00 | 6.00 | 3.38 |
March | 0.750286E+09 | 1910.43 | 25-MAR-11:50 | 11.92 | 8.82 | 0.336703E+09 | 489.78 | 10-MAR-14:00 | 11.92 | 8.82 |
April | 0.282782E+10 | 17308.79 | 30-APR-13:31 | 22.67 | 12.88 | 0.354579E+09 | 549.52 | 14-APR-13:00 | 22.67 | 12.88 |
May | 0.272248E+10 | 7496.11 | 22-MAY-13:50 | 22.83 | 15.60 | 0.384468E+09 | 549.51 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.337415E+10 | 7914.12 | 13-JUN-13:40 | 24.73 | 17.32 | 0.403702E+09 | 549.51 | 08-JUN-13:20 | 24.73 | 17.32 |
July | 0.418396E+10 | 12801.98 | 23-JUL-13:23 | 21.50 | 16.21 | 0.388361E+09 | 549.50 | 12-JUL-13:00 | 21.50 | 16.21 |
August | 0.528770E+10 | 11729.59 | 13-AUG-13:02 | 21.00 | 15.45 | 0.440469E+09 | 549.50 | 21-AUG-13:30 | 21.00 | 14.72 |
September | 0.511133E+10 | 17841.29 | 10-SEP-13:22 | 21.00 | 15.72 | 0.388522E+09 | 549.67 | 12-SEP-13:30 | 20.50 | 16.36 |
October | 0.255604E+10 | 10870.22 | 03-OCT-12:07 | 13.00 | 9.72 | 0.353199E+09 | 549.50 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.101720E+10 | 3896.42 | 11-NOV-13:03 | 9.00 | 7.36 | 0.318467E+09 | 549.50 | 03-NOV-13:09 | 9.00 | 7.36 |
December | 0.338743E+09 | 2071.61 | 18-DEC-13:50 | 8.00 | 5.60 | 0.296291E+09 | 547.57 | 18-DEC-14:09 | 8.00 | 5.67 |
Annual Sum or Average | 0.296502E+11 | 0.427082E+10 | ||||||||
Minimum of Months | 0.338743E+09 | 1910.43 | 6.00 | 5.05 | 0.291891E+09 | 489.78 | 6.00 | 3.38 | ||
Maximum of Months | 0.528770E+10 | 17841.29 | 24.73 | 17.32 | 0.440469E+09 | 549.67 | 24.73 | 17.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.433136E+09 | 1426.99 | 19-JAN-15:50 | 8.17 | 7.46 | 0.197608E+09 | 316.86 | 19-JAN-15:00 | 8.00 | 7.45 |
February | 0.609315E+09 | 1772.29 | 27-FEB-16:30 | 8.00 | 6.72 | 0.183382E+09 | 338.68 | 27-FEB-16:00 | 8.00 | 6.97 |
March | 0.873960E+09 | 1864.31 | 23-MAR-17:00 | 10.00 | 6.65 | 0.217517E+09 | 324.53 | 23-MAR-15:00 | 10.00 | 6.65 |
April | 0.218126E+10 | 13082.64 | 30-APR-17:31 | 24.00 | 12.95 | 0.224745E+09 | 347.84 | 28-APR-13:00 | 24.00 | 12.95 |
May | 0.271564E+10 | 6631.95 | 22-MAY-16:00 | 23.00 | 15.28 | 0.254537E+09 | 347.85 | 22-MAY-13:00 | 23.00 | 15.28 |
June | 0.348515E+10 | 8787.33 | 25-JUN-17:42 | 21.83 | 18.99 | 0.268306E+09 | 347.85 | 09-JUN-13:00 | 21.83 | 18.99 |
July | 0.386581E+10 | 10536.67 | 22-JUL-17:04 | 29.17 | 16.61 | 0.252416E+09 | 347.85 | 12-JUL-13:00 | 29.17 | 16.61 |
August | 0.364737E+10 | 8630.24 | 13-AUG-17:02 | 18.83 | 14.64 | 0.282508E+09 | 347.86 | 15-AUG-09:09 | 16.00 | 13.59 |
September | 0.274614E+10 | 6313.83 | 12-SEP-16:00 | 21.00 | 15.99 | 0.242904E+09 | 347.85 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.157026E+10 | 4455.98 | 03-OCT-16:00 | 14.00 | 8.96 | 0.219233E+09 | 347.83 | 04-OCT-13:00 | 14.00 | 10.28 |
November | 0.808488E+09 | 1490.09 | 10-NOV-15:40 | 11.33 | 8.41 | 0.199284E+09 | 327.44 | 10-NOV-15:50 | 11.17 | 8.40 |
December | 0.262110E+09 | 1206.72 | 21-DEC-14:50 | 8.00 | 6.98 | 0.187981E+09 | 289.26 | 21-DEC-14:00 | 8.00 | 6.98 |
Annual Sum or Average | 0.231987E+11 | 0.273042E+10 | ||||||||
Minimum of Months | 0.262110E+09 | 1206.72 | 8.00 | 6.65 | 0.183382E+09 | 289.26 | 8.00 | 6.65 | ||
Maximum of Months | 0.386581E+10 | 13082.64 | 29.17 | 18.99 | 0.282508E+09 | 347.86 | 29.17 | 18.99 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.582522E+09 | 1316.96 | 19-JAN-15:40 | 8.33 | 7.46 | 0.314413E+09 | 462.75 | 19-JAN-14:00 | 8.33 | 7.46 |
February | 0.726643E+09 | 1298.13 | 24-FEB-16:10 | 6.00 | 4.60 | 0.288466E+09 | 456.65 | 10-FEB-14:00 | 6.00 | 4.60 |
March | 0.128659E+10 | 1471.72 | 30-MAR-14:00 | 13.00 | 7.37 | 0.359123E+09 | 503.23 | 30-MAR-13:00 | 13.00 | 7.37 |
April | 0.217590E+10 | 3741.43 | 28-APR-15:30 | 20.05 | 13.01 | 0.372267E+09 | 549.51 | 14-APR-13:00 | 20.05 | 13.01 |
May | 0.267134E+10 | 4001.45 | 22-MAY-15:20 | 23.67 | 15.81 | 0.415882E+09 | 549.50 | 22-MAY-13:00 | 23.67 | 15.81 |
June | 0.357632E+10 | 5178.46 | 13-JUN-16:00 | 26.50 | 17.70 | 0.430205E+09 | 549.51 | 08-JUN-13:09 | 26.50 | 17.70 |
July | 0.384000E+10 | 4957.41 | 21-JUL-15:50 | 27.83 | 16.07 | 0.400852E+09 | 549.50 | 03-JUL-09:09 | 27.83 | 16.07 |
August | 0.378801E+10 | 4544.55 | 14-AUG-16:00 | 26.00 | 15.86 | 0.448659E+09 | 549.51 | 15-AUG-09:09 | 16.00 | 13.59 |
September | 0.270948E+10 | 4066.20 | 13-SEP-15:30 | 23.00 | 16.22 | 0.388367E+09 | 549.51 | 19-SEP-13:50 | 14.33 | 13.96 |
October | 0.164658E+10 | 2143.58 | 06-OCT-15:40 | 17.00 | 9.21 | 0.355869E+09 | 549.47 | 06-OCT-13:00 | 17.00 | 9.21 |
November | 0.956773E+09 | 1411.61 | 10-NOV-15:20 | 11.67 | 8.42 | 0.319723E+09 | 486.86 | 10-NOV-14:00 | 11.67 | 8.42 |
December | 0.412668E+09 | 1187.23 | 21-DEC-16:10 | 6.83 | 6.31 | 0.297637E+09 | 433.42 | 22-DEC-14:20 | 7.00 | 5.54 |
Annual Sum or Average | 0.243728E+11 | 0.439146E+10 | ||||||||
Minimum of Months | 0.412668E+09 | 1187.23 | 6.00 | 4.60 | 0.288466E+09 | 433.42 | 6.00 | 4.60 | ||
Maximum of Months | 0.384000E+10 | 5178.46 | 27.83 | 17.70 | 0.448659E+09 | 549.51 | 27.83 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.573987E+09 | 1535.22 | 20-JAN-10:00 | 4.00 | 3.60 | 0.145754E+09 | 310.91 | 20-JAN-09:00 | 4.00 | 3.60 |
February | 0.729623E+09 | 1662.60 | 17-FEB-10:00 | 3.00 | 2.16 | 0.135313E+09 | 332.80 | 17-FEB-09:00 | 3.00 | 2.16 |
March | 0.116191E+10 | 1585.50 | 25-MAR-09:50 | 10.67 | 7.61 | 0.164018E+09 | 317.17 | 30-MAR-10:39 | 9.67 | 6.89 |
April | 0.302277E+10 | 11036.24 | 30-APR-10:43 | 19.17 | 11.38 | 0.179339E+09 | 338.79 | 28-APR-07:49 | 19.17 | 11.38 |
May | 0.337789E+10 | 12086.50 | 21-MAY-08:53 | 13.00 | 9.30 | 0.195119E+09 | 338.73 | 22-MAY-14:09 | 23.17 | 15.81 |
June | 0.397311E+10 | 11811.99 | 11-JUN-09:23 | 16.00 | 13.04 | 0.199855E+09 | 338.75 | 09-JUN-07:10 | 16.00 | 13.04 |
July | 0.422878E+10 | 14070.73 | 23-JUL-08:42 | 19.83 | 15.59 | 0.187935E+09 | 338.73 | 31-JUL-08:09 | 14.83 | 10.71 |
August | 0.447971E+10 | 11221.59 | 20-AUG-10:13 | 16.33 | 13.20 | 0.208961E+09 | 338.74 | 21-AUG-07:10 | 14.33 | 12.39 |
September | 0.347145E+10 | 7275.57 | 12-SEP-09:00 | 18.00 | 14.38 | 0.183603E+09 | 338.74 | 21-SEP-08:09 | 13.00 | 11.30 |
October | 0.172171E+10 | 4160.45 | 04-OCT-08:55 | 12.00 | 9.31 | 0.164756E+09 | 338.72 | 02-OCT-10:30 | 12.00 | 9.31 |
November | 0.840002E+09 | 1506.92 | 03-NOV-10:30 | 8.00 | 5.31 | 0.146743E+09 | 308.35 | 03-NOV-10:30 | 8.00 | 5.31 |
December | 0.364639E+09 | 1326.71 | 06-DEC-10:00 | 4.00 | 3.12 | 0.138694E+09 | 282.44 | 06-DEC-09:00 | 4.00 | 3.12 |
Annual Sum or Average | 0.279456E+11 | 0.205009E+10 | ||||||||
Minimum of Months | 0.364639E+09 | 1326.71 | 3.00 | 2.16 | 0.135313E+09 | 282.44 | 3.00 | 2.16 | ||
Maximum of Months | 0.447971E+10 | 14070.73 | 19.83 | 15.59 | 0.208961E+09 | 338.79 | 23.17 | 15.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173230E+10 | 7686.45 | 20-JAN-12:00 | 8.00 | 6.08 | 0.339796E+09 | 549.50 | 20-JAN-10:30 | 8.00 | 6.08 |
February | 0.209132E+10 | 8854.73 | 17-FEB-13:40 | 6.00 | 3.25 | 0.318421E+09 | 549.62 | 13-FEB-14:09 | 6.00 | 3.25 |
March | 0.207327E+10 | 4740.33 | 28-MAR-12:05 | 11.67 | 7.18 | 0.372379E+09 | 549.50 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.514751E+10 | 19916.05 | 30-APR-12:42 | 22.00 | 13.22 | 0.379979E+09 | 549.53 | 14-APR-13:00 | 22.00 | 13.22 |
May | 0.483509E+10 | 9942.59 | 22-MAY-13:10 | 22.17 | 14.96 | 0.413032E+09 | 549.51 | 22-MAY-13:50 | 22.83 | 15.60 |
June | 0.536609E+10 | 9761.90 | 13-JUN-13:10 | 24.18 | 17.12 | 0.424788E+09 | 549.53 | 08-JUN-13:09 | 24.18 | 17.12 |
July | 0.606097E+10 | 18155.29 | 23-JUL-13:23 | 21.50 | 16.21 | 0.398290E+09 | 549.50 | 12-JUL-13:50 | 21.50 | 16.21 |
August | 0.728660E+10 | 18764.05 | 06-AUG-14:13 | 18.00 | 13.90 | 0.447120E+09 | 549.50 | 21-AUG-13:30 | 21.00 | 14.72 |
September | 0.692676E+10 | 20627.05 | 24-SEP-13:12 | 19.67 | 15.02 | 0.392515E+09 | 550.02 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.398646E+10 | 11975.69 | 03-OCT-13:10 | 13.17 | 9.32 | 0.369213E+09 | 549.72 | 03-OCT-13:30 | 13.50 | 9.36 |
November | 0.201143E+10 | 9057.81 | 11-NOV-12:53 | 9.00 | 7.43 | 0.339396E+09 | 549.49 | 03-NOV-13:00 | 9.00 | 7.43 |
December | 0.108940E+10 | 6159.26 | 18-DEC-13:25 | 8.00 | 5.46 | 0.316994E+09 | 549.49 | 26-DEC-14:00 | 6.00 | 3.37 |
Annual Sum or Average | 0.486072E+11 | 0.451192E+10 | ||||||||
Minimum of Months | 0.108940E+10 | 4740.33 | 6.00 | 3.25 | 0.316994E+09 | 549.49 | 6.00 | 3.25 | ||
Maximum of Months | 0.728660E+10 | 20627.05 | 24.18 | 17.12 | 0.447120E+09 | 550.02 | 24.18 | 17.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.605246E+09 | 1737.89 | 19-JAN-15:50 | 8.17 | 7.46 | 0.199463E+09 | 336.18 | 19-JAN-15:00 | 8.00 | 7.45 |
February | 0.840737E+09 | 2892.47 | 27-FEB-16:30 | 8.00 | 6.72 | 0.186683E+09 | 341.64 | 09-FEB-14:00 | 8.00 | 6.72 |
March | 0.123018E+10 | 3251.71 | 23-MAR-16:40 | 10.00 | 6.65 | 0.222831E+09 | 338.68 | 10-MAR-16:49 | 10.00 | 6.65 |
April | 0.286575E+10 | 13917.98 | 30-APR-16:02 | 24.00 | 13.04 | 0.228303E+09 | 347.86 | 14-APR-13:00 | 24.00 | 13.04 |
May | 0.338432E+10 | 12139.38 | 21-MAY-16:32 | 19.33 | 11.98 | 0.254345E+09 | 347.85 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.415566E+10 | 13693.99 | 25-JUN-17:22 | 21.50 | 17.05 | 0.266570E+09 | 347.86 | 08-JUN-13:09 | 21.50 | 17.05 |
July | 0.444849E+10 | 16224.05 | 09-JUL-16:51 | 21.00 | 15.03 | 0.250568E+09 | 347.85 | 12-JUL-13:00 | 21.00 | 15.44 |
August | 0.425171E+10 | 12905.18 | 20-AUG-16:12 | 23.33 | 14.80 | 0.279716E+09 | 347.85 | 11-AUG-13:00 | 23.33 | 14.80 |
September | 0.322360E+10 | 11556.62 | 10-SEP-16:12 | 20.33 | 16.35 | 0.239640E+09 | 347.86 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.177045E+10 | 5488.88 | 03-OCT-15:40 | 14.00 | 8.96 | 0.218148E+09 | 347.84 | 04-OCT-13:00 | 14.00 | 10.28 |
November | 0.885921E+09 | 1902.44 | 10-NOV-15:40 | 11.33 | 8.41 | 0.199899E+09 | 340.13 | 15-NOV-14:00 | 12.00 | 8.90 |
December | 0.342545E+09 | 1448.33 | 21-DEC-14:40 | 8.00 | 6.98 | 0.188242E+09 | 302.01 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.280046E+11 | 0.273441E+10 | ||||||||
Minimum of Months | 0.342545E+09 | 1448.33 | 8.00 | 6.65 | 0.186683E+09 | 302.01 | 8.00 | 6.65 | ||
Maximum of Months | 0.444849E+10 | 16224.05 | 24.00 | 17.05 | 0.279716E+09 | 347.86 | 24.00 | 17.05 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 25042325.27 | 19831.54 | 02-JAN-06:01 | 1.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 25042325.27 | |||
Minimum of Months | 0.00 | 0.00 | 1.17 | |
Maximum of Months | 25042325.27 | 19831.54 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310670E+10 | 10717.92 | 09-JAN-07:02 | -2.0 |
February | 0.210375E+10 | 9441.39 | 17-FEB-07:02 | -3.8 |
March | 0.180892E+10 | 7865.31 | 06-MAR-07:02 | 4.33 |
April | 0.734052E+09 | 4763.39 | 20-APR-05:03 | 1.17 |
May | 0.519349E+09 | 4574.02 | 21-MAY-07:27 | 11.85 |
June | 0.240931E+09 | 4155.89 | 01-JUN-05:03 | 6.50 |
July | 0.202089E+09 | 4368.32 | 16-JUL-07:32 | 15.33 |
August | 0.303888E+09 | 4260.54 | 20-AUG-07:23 | 15.00 |
September | 0.499397E+09 | 4102.29 | 24-SEP-08:28 | 17.00 |
October | 0.125565E+10 | 6146.16 | 23-OCT-06:03 | 4.00 |
November | 0.214536E+10 | 10491.02 | 27-NOV-06:22 | 4.00 |
December | 0.354815E+10 | 12200.35 | 26-DEC-06:16 | 1.93 |
Annual Sum or Average | 0.164682E+11 | |||
Minimum of Months | 0.202089E+09 | 4102.29 | -3.8 | |
Maximum of Months | 0.354815E+10 | 12200.35 | 17.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151963E+10 | 8053.21 | 02-JAN-07:04 | 1.83 |
February | 0.104913E+10 | 3308.31 | 19-FEB-13:30 | 6.00 |
March | 0.862068E+09 | 2608.18 | 06-MAR-07:08 | 4.33 |
April | 0.235829E+09 | 5485.35 | 30-APR-10:43 | 19.17 |
May | 0.146022E+09 | 4005.87 | 21-MAY-08:53 | 13.00 |
June | 17444008.48 | 3244.13 | 11-JUN-09:23 | 16.00 |
July | 30112474.53 | 3775.60 | 09-JUL-16:11 | 21.00 |
August | 23470579.46 | 4585.66 | 20-AUG-14:53 | 23.00 |
September | 56876236.08 | 5458.23 | 17-SEP-12:43 | 16.00 |
October | 0.503159E+09 | 2959.47 | 01-OCT-11:43 | 14.00 |
November | 0.994794E+09 | 3620.29 | 11-NOV-12:53 | 9.00 |
December | 0.160479E+10 | 5790.79 | 26-DEC-07:03 | 1.83 |
Annual Sum or Average | 0.704333E+10 | |||
Minimum of Months | 17444008.48 | 2608.18 | 1.83 | |
Maximum of Months | 0.160479E+10 | 8053.21 | 23.00 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117043E+10 | 5742.02 | 02-JAN-07:03 | 1.83 |
February | 0.729608E+09 | 3371.84 | 24-FEB-08:07 | 0.50 |
March | 0.642960E+09 | 3194.01 | 03-MAR-08:07 | 3.17 |
April | 41985382.41 | 3764.27 | 20-APR-05:03 | 1.17 |
May | 20818787.27 | 2411.94 | 07-MAY-16:03 | 13.83 |
June | 14807400.47 | 2065.15 | 18-JUN-08:40 | 13.67 |
July | 22315739.44 | 2366.50 | 30-JUL-12:13 | 16.33 |
August | 15944735.34 | 2039.59 | 27-AUG-08:40 | 16.00 |
September | 28932253.49 | 3081.19 | 10-SEP-13:22 | 21.00 |
October | 0.239929E+09 | 2801.55 | 01-OCT-09:58 | 13.00 |
November | 0.698744E+09 | 3665.47 | 03-NOV-07:05 | 3.83 |
December | 0.126547E+10 | 3543.72 | 08-DEC-08:10 | 1.00 |
Annual Sum or Average | 0.489194E+10 | |||
Minimum of Months | 14807400.47 | 2039.59 | 0.50 | |
Maximum of Months | 0.126547E+10 | 5742.02 | 21.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173329E+09 | 22354.67 | 02-JAN-06:01 | 1.17 |
February | 13059985.21 | 18962.43 | 13-FEB-07:01 | -0.7 |
March | 7592536.94 | 18943.12 | 06-MAR-07:02 | 4.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 14361213.60 | 19108.19 | 27-NOV-07:02 | 4.00 |
December | 87754537.02 | 20951.03 | 18-DEC-06:01 | 0.17 |
Annual Sum or Average | 0.296097E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 0.173329E+09 | 22354.67 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.789382E+09 | 29829.40 | 02-JAN-05:01 | 1.00 |
February | 0.319955E+09 | 26621.06 | 13-FEB-06:01 | -1.0 |
March | 0.211652E+09 | 26442.68 | 06-MAR-06:11 | 4.00 |
April | 5364011.35 | 18755.27 | 03-APR-06:03 | 3.17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 45383349.34 | 24050.28 | 17-OCT-06:03 | 7.17 |
November | 0.301364E+09 | 27047.34 | 27-NOV-06:11 | 4.00 |
December | 0.802891E+09 | 28520.61 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.247599E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.802891E+09 | 29829.40 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186553E+10 | 8959.79 | 02-JAN-05:01 | 1.00 |
February | 0.111967E+10 | 8804.94 | 13-FEB-05:01 | -1.0 |
March | 0.702771E+09 | 8554.21 | 06-MAR-06:11 | 4.00 |
April | 78762066.29 | 7576.54 | 01-APR-05:12 | 2.33 |
May | 15264444.27 | 7180.02 | 17-MAY-06:03 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 7312186.61 | 7161.53 | 20-SEP-06:03 | 6.17 |
October | 0.255452E+09 | 8164.61 | 23-OCT-05:11 | 3.33 |
November | 0.948569E+09 | 8885.37 | 20-NOV-05:01 | 0.67 |
December | 0.215504E+10 | 9022.57 | 18-DEC-05:01 | 0.83 |
Annual Sum or Average | 0.714836E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.215504E+10 | 9022.57 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106477E+10 | 8867.27 | 02-JAN-05:01 | 1.00 |
February | 0.623964E+09 | 8565.07 | 13-FEB-05:01 | -1.0 |
March | 0.416714E+09 | 8390.84 | 06-MAR-06:11 | 4.00 |
April | 23974797.13 | 7048.60 | 01-APR-05:12 | 2.33 |
May | 5884562.53 | 5413.99 | 17-MAY-06:03 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 4739901.65 | 4798.02 | 20-SEP-06:03 | 6.17 |
October | 0.155152E+09 | 7785.95 | 23-OCT-05:11 | 3.33 |
November | 0.549005E+09 | 8741.74 | 27-NOV-06:11 | 4.00 |
December | 0.130128E+10 | 8901.80 | 18-DEC-05:01 | 0.83 |
Annual Sum or Average | 0.414549E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.130128E+10 | 8901.80 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123444E+10 | 13545.91 | 02-JAN-05:01 | 1.00 |
February | 0.731907E+09 | 12799.42 | 13-FEB-05:01 | -1.0 |
March | 0.582138E+09 | 12767.25 | 06-MAR-06:11 | 4.00 |
April | 72017550.66 | 9790.52 | 01-APR-06:03 | 3.17 |
May | 32353004.16 | 9090.95 | 06-MAY-06:03 | 3.50 |
June | 1250640.86 | 4714.58 | 08-JUN-06:03 | 7.50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 7047426.70 | 8135.88 | 20-SEP-06:03 | 6.17 |
October | 0.200078E+09 | 11645.55 | 23-OCT-05:11 | 3.33 |
November | 0.657685E+09 | 13264.95 | 27-NOV-06:11 | 4.00 |
December | 0.168852E+10 | 13493.71 | 18-DEC-05:01 | 0.83 |
Annual Sum or Average | 0.520744E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.168852E+10 | 13545.91 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112810E+10 | 8808.45 | 02-JAN-05:01 | 1.00 |
February | 0.648935E+09 | 8542.64 | 13-FEB-05:01 | -1.0 |
March | 0.452098E+09 | 8287.18 | 06-MAR-06:11 | 4.00 |
April | 56139261.10 | 6447.30 | 01-APR-05:12 | 2.33 |
May | 22811419.64 | 5798.48 | 05-MAY-06:03 | 6.17 |
June | 657638.91 | 2743.88 | 08-JUN-06:03 | 7.50 |
July | 84725.03 | 282.42 | 01-JUL-06:05 | 11.33 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 8535239.08 | 5277.88 | 20-SEP-06:03 | 6.17 |
October | 0.177400E+09 | 7572.48 | 23-OCT-05:11 | 3.33 |
November | 0.608224E+09 | 8706.99 | 27-NOV-06:11 | 4.00 |
December | 0.142735E+10 | 8842.55 | 18-DEC-05:01 | 0.83 |
Annual Sum or Average | 0.453033E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.142735E+10 | 8842.55 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110031E+10 | 7360.64 | 02-JAN-05:01 | 1.00 |
February | 0.491461E+09 | 6495.14 | 13-FEB-06:01 | -1.0 |
March | 0.272811E+09 | 6426.23 | 06-MAR-06:11 | 4.00 |
April | 15795617.91 | 5863.47 | 03-APR-06:03 | 3.17 |
May | 125044.63 | 440.88 | 17-MAY-06:03 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 22308898.42 | 5879.12 | 30-OCT-06:03 | 6.83 |
November | 0.215789E+09 | 6403.10 | 27-NOV-06:11 | 4.00 |
December | 0.889706E+09 | 6758.41 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.300831E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.110031E+10 | 7360.64 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.585518E+09 | 6946.20 | 02-JAN-05:01 | 1.00 |
February | 0.236680E+09 | 5908.53 | 11-FEB-06:11 | 2.00 |
March | 0.157449E+09 | 5995.31 | 06-MAR-06:11 | 4.00 |
April | 2390983.99 | 5063.47 | 01-APR-06:03 | 3.17 |
May | 23526.74 | 156.84 | 17-MAY-06:03 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 16532355.55 | 5586.24 | 23-OCT-06:03 | 4.00 |
November | 0.125987E+09 | 5901.37 | 27-NOV-06:11 | 4.00 |
December | 0.543384E+09 | 6388.69 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.166796E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 0.585518E+09 | 6946.20 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304112E+10 | 11518.31 | 10-JAN-08:00 | -6.0 |
February | 0.215562E+10 | 11241.80 | 17-FEB-07:10 | -3.8 |
March | 0.260225E+10 | 10505.04 | 08-MAR-07:10 | -0.5 |
April | 0.861200E+09 | 9109.36 | 03-APR-06:10 | 3.17 |
May | 0.867291E+09 | 8623.41 | 05-MAY-06:10 | 6.17 |
June | 0.312044E+09 | 8555.54 | 07-JUN-06:05 | 8.33 |
July | 0.108051E+09 | 7713.31 | 31-JUL-06:07 | 10.50 |
August | 88798496.70 | 7761.22 | 24-AUG-06:10 | 8.83 |
September | 0.288378E+09 | 8522.77 | 21-SEP-07:00 | 7.00 |
October | 0.110936E+10 | 8923.31 | 23-OCT-06:50 | 4.00 |
November | 0.203702E+10 | 10557.18 | 29-NOV-07:10 | -1.0 |
December | 0.306098E+10 | 10703.71 | 27-DEC-07:10 | -1.8 |
Annual Sum or Average | 0.165321E+11 | |||
Minimum of Months | 88798496.70 | 7713.31 | -6.0 | |
Maximum of Months | 0.306098E+10 | 11518.31 | 10.50 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.618982E+09 | 6951.93 | 02-JAN-05:01 | 1.00 |
February | 0.211576E+09 | 5880.66 | 23-FEB-06:12 | 1.67 |
March | 0.164367E+09 | 5926.21 | 28-MAR-05:12 | 4.30 |
April | 8884208.47 | 5494.89 | 01-APR-06:03 | 3.17 |
May | 1629575.96 | 2870.71 | 05-MAY-06:03 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 19198881.65 | 5534.65 | 30-OCT-06:03 | 6.83 |
November | 0.142217E+09 | 5800.63 | 21-NOV-06:11 | 4.00 |
December | 0.609368E+09 | 6267.04 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.177622E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 0.618982E+09 | 6951.93 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.773539E+09 | 8156.10 | 02-JAN-05:01 | 1.00 |
February | 0.306171E+09 | 7281.39 | 13-FEB-06:01 | -1.0 |
March | 0.161049E+09 | 7146.09 | 06-MAR-06:11 | 4.00 |
April | 6533542.78 | 6479.34 | 03-APR-06:03 | 3.17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 31397646.97 | 6783.45 | 23-OCT-05:11 | 3.33 |
November | 0.258076E+09 | 7352.63 | 27-NOV-06:11 | 4.00 |
December | 0.875600E+09 | 7802.18 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.241237E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.875600E+09 | 8156.10 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.471228E+09 | 7008.88 | 02-JAN-05:01 | 1.00 |
February | 0.188834E+09 | 5752.72 | 11-FEB-06:11 | 2.00 |
March | 0.107219E+09 | 5741.60 | 14-MAR-05:11 | 2.00 |
April | 3481575.94 | 4917.11 | 01-APR-06:03 | 3.17 |
May | 270908.32 | 1532.03 | 17-MAY-06:03 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 29538123.58 | 5705.02 | 23-OCT-05:11 | 3.33 |
November | 0.166551E+09 | 5946.68 | 27-NOV-06:11 | 4.00 |
December | 0.575375E+09 | 6631.98 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.154250E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 0.575375E+09 | 7008.88 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.481548E+09 | 10228.18 | 02-JAN-05:01 | 1.00 |
February | 0.184204E+09 | 8817.37 | 24-FEB-06:01 | -0.3 |
March | 0.135907E+09 | 8658.24 | 06-MAR-06:11 | 4.00 |
April | 8147532.39 | 8335.83 | 01-APR-06:03 | 3.17 |
May | 1631687.48 | 4918.78 | 05-MAY-06:03 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 31586248.87 | 8450.54 | 28-OCT-06:03 | 6.50 |
November | 0.175715E+09 | 9027.81 | 27-NOV-06:11 | 4.00 |
December | 0.646452E+09 | 9818.15 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.166519E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.3 | |
Maximum of Months | 0.646452E+09 | 10228.18 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472847E+09 | 6979.76 | 02-JAN-05:01 | 1.00 |
February | 0.181423E+09 | 5733.21 | 13-FEB-06:01 | -1.0 |
March | 0.113886E+09 | 5755.24 | 06-MAR-06:13 | 4.00 |
April | 7686475.67 | 5392.30 | 01-APR-06:03 | 3.17 |
May | 1893332.51 | 4218.29 | 05-MAY-06:03 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 30144478.99 | 5803.29 | 23-OCT-05:11 | 3.33 |
November | 0.180613E+09 | 5911.08 | 27-NOV-06:11 | 4.00 |
December | 0.599224E+09 | 6586.72 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.158772E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.599224E+09 | 6979.76 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110087E+10 | 1592.13 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.890719E+09 | 1592.13 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.965925E+09 | 1388.60 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.806491E+09 | 1388.60 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.837315E+09 | 833.48 | 03-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.820964E+09 | 759.45 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.774714E+09 | 833.48 | 07-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.885677E+09 | 1111.04 | 22-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.831154E+09 | 1111.04 | 08-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.966933E+09 | 1592.13 | 16-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.108451E+10 | 1592.13 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.114872E+10 | 1592.13 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.111140E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.774714E+09 | 759.45 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.114872E+10 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.667464E+09 | 1007.95 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.548527E+09 | 1007.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.605242E+09 | 879.10 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.510006E+09 | 703.38 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.532298E+09 | 527.66 | 15-MAY-15:20 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.522680E+09 | 480.79 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.493195E+09 | 527.66 | 07-JUL-15:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.561208E+09 | 574.53 | 22-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.521131E+09 | 703.38 | 08-SEP-07:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.599299E+09 | 1007.95 | 16-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.663397E+09 | 1007.95 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.692881E+09 | 1007.95 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.691733E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.493195E+09 | 480.79 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.692881E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103006E+10 | 1592.13 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.850911E+09 | 1592.13 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.949504E+09 | 1388.60 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.807384E+09 | 1185.08 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.842608E+09 | 833.48 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.826828E+09 | 759.45 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.780731E+09 | 833.48 | 07-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.889545E+09 | 1111.04 | 22-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.825753E+09 | 1111.04 | 08-SEP-07:19 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.936031E+09 | 1592.13 | 16-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.102380E+10 | 1592.13 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.106964E+10 | 1592.13 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.108328E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.780731E+09 | 759.45 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.106964E+10 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.674731E+09 | 1007.89 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.552063E+09 | 1007.89 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.608530E+09 | 879.04 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.511438E+09 | 879.04 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.531878E+09 | 574.49 | 04-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.521446E+09 | 527.63 | 14-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.492138E+09 | 527.63 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.563431E+09 | 703.34 | 22-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.526736E+09 | 879.04 | 08-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.604732E+09 | 1007.89 | 16-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.667356E+09 | 1007.89 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.705007E+09 | 1007.89 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.695948E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.492138E+09 | 527.63 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.705007E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.109479E+10 | 1592.13 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.886512E+09 | 1592.13 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.962002E+09 | 1388.60 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.805318E+09 | 1185.08 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.836335E+09 | 833.48 | 03-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.820466E+09 | 759.45 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.773981E+09 | 833.48 | 07-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.884798E+09 | 907.52 | 08-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.829599E+09 | 1111.04 | 08-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.962510E+09 | 1592.13 | 16-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.107765E+10 | 1592.13 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.114097E+10 | 1592.13 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.110749E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.773981E+09 | 759.45 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.114097E+10 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.665583E+09 | 1007.95 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.546605E+09 | 1007.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.603886E+09 | 879.10 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.509413E+09 | 703.38 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.531847E+09 | 527.66 | 15-MAY-15:20 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.522328E+09 | 480.79 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.492626E+09 | 527.66 | 07-JUL-15:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.560546E+09 | 574.53 | 22-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.520453E+09 | 574.53 | 08-SEP-07:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.597212E+09 | 1007.95 | 16-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.660934E+09 | 1007.95 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.689704E+09 | 1007.95 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.690114E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.492626E+09 | 480.79 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.689704E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.102610E+10 | 1592.13 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.849162E+09 | 1592.13 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.947198E+09 | 1388.60 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.806629E+09 | 1111.04 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.841602E+09 | 833.48 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.825801E+09 | 759.45 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.779878E+09 | 833.48 | 07-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.888514E+09 | 907.52 | 08-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.824407E+09 | 1111.04 | 08-SEP-07:30 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.933415E+09 | 1592.13 | 16-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.102084E+10 | 1592.13 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.106623E+10 | 1592.13 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.108098E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.779878E+09 | 759.45 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.106623E+10 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.671929E+09 | 1007.89 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.550283E+09 | 1007.89 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.606855E+09 | 879.04 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.510403E+09 | 879.04 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.531384E+09 | 527.63 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.520876E+09 | 527.63 | 14-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.491814E+09 | 527.63 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.562761E+09 | 703.34 | 22-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.525332E+09 | 879.04 | 08-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.602440E+09 | 1007.89 | 16-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.663579E+09 | 1007.89 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.701702E+09 | 1007.89 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.693936E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.491814E+09 | 527.63 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.701702E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110087E+10 | 1592.13 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.890719E+09 | 1592.13 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.965925E+09 | 1388.60 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.806491E+09 | 1388.60 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.837315E+09 | 833.48 | 03-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.820964E+09 | 759.45 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.774714E+09 | 833.48 | 07-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.885670E+09 | 1111.04 | 22-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.831154E+09 | 1111.04 | 08-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.966933E+09 | 1592.13 | 16-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.108447E+10 | 1592.13 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.114872E+10 | 1592.13 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.111139E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.774714E+09 | 759.45 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.114872E+10 | 1592.13 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.667464E+09 | 1007.95 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.548527E+09 | 1007.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.605242E+09 | 879.10 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.510006E+09 | 703.38 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.532298E+09 | 527.66 | 15-MAY-15:20 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.522680E+09 | 480.79 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.493195E+09 | 527.66 | 07-JUL-15:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.561208E+09 | 574.53 | 22-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.521131E+09 | 703.38 | 08-SEP-07:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.599299E+09 | 1007.95 | 16-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.663397E+09 | 1007.95 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.692881E+09 | 1007.95 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.691733E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.493195E+09 | 480.79 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.692881E+09 | 1007.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103006E+10 | 1592.13 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.850911E+09 | 1592.13 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.949504E+09 | 1388.60 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.807384E+09 | 1185.08 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.842608E+09 | 833.48 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.826828E+09 | 759.45 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.780731E+09 | 833.48 | 07-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.889545E+09 | 1111.04 | 22-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.825753E+09 | 1111.04 | 08-SEP-07:19 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.936031E+09 | 1592.13 | 16-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.102380E+10 | 1592.13 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.106964E+10 | 1592.13 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.108328E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.780731E+09 | 759.45 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.106964E+10 | 1592.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.674731E+09 | 1007.89 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.552063E+09 | 1007.89 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.608530E+09 | 879.04 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.511438E+09 | 879.04 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.531878E+09 | 574.49 | 04-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.521446E+09 | 527.63 | 14-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.492138E+09 | 527.63 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.563431E+09 | 703.34 | 22-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.526736E+09 | 879.04 | 08-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.604732E+09 | 1007.89 | 16-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.667356E+09 | 1007.89 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.705007E+09 | 1007.89 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.695948E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.492138E+09 | 527.63 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.705007E+09 | 1007.89 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.110087E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225733E+09 |
February | 0.901968E+09 | 0.890719E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322709E+09 |
March | 0.107774E+10 | 0.965925E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193507E+09 |
April | 0.956342E+09 | 0.806491E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256404E+09 |
May | 0.103597E+10 | 0.837315E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628716E+09 |
June | 0.103308E+10 | 0.820964E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 310326.22 | 0.496640E+09 |
July | 0.959235E+09 | 0.774714E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1466020.50 | 0.472735E+09 |
August | 0.107774E+10 | 0.885677E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 201938.22 | 0.339768E+09 |
September | 0.956342E+09 | 0.831154E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344549E+09 |
October | 0.994195E+09 | 0.966933E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348177E+09 |
November | 0.984487E+09 | 0.108451E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413896E+09 |
December | 0.959235E+09 | 0.114872E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560723E+09 |
Annual Sum or Average | 0.119305E+11 | 0.111140E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1978284.94 | 0.460356E+10 |
Minimum of Months | 0.901968E+09 | 0.774714E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193507E+09 |
Maximum of Months | 0.107774E+10 | 0.114872E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1466020.50 | 0.628716E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.667464E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151769E+09 |
February | 0.571020E+09 | 0.548527E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217616E+09 |
March | 0.682301E+09 | 0.605242E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129977E+09 |
April | 0.605444E+09 | 0.510006E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177630E+09 |
May | 0.655854E+09 | 0.532298E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428279E+09 |
June | 0.654023E+09 | 0.522680E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 206887.37 | 0.334508E+09 |
July | 0.607275E+09 | 0.493195E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1060712.35 | 0.323208E+09 |
August | 0.682301E+09 | 0.561208E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 134628.04 | 0.232772E+09 |
September | 0.605444E+09 | 0.521131E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240852E+09 |
October | 0.629407E+09 | 0.599299E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236069E+09 |
November | 0.623262E+09 | 0.663397E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277429E+09 |
December | 0.607275E+09 | 0.692881E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374082E+09 |
Annual Sum or Average | 0.755301E+10 | 0.691733E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1402227.76 | 0.312419E+10 |
Minimum of Months | 0.571020E+09 | 0.493195E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129977E+09 |
Maximum of Months | 0.682301E+09 | 0.692881E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1060712.35 | 0.428279E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.103006E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239366E+09 |
February | 0.901968E+09 | 0.850911E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342260E+09 |
March | 0.107774E+10 | 0.949504E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199350E+09 |
April | 0.956342E+09 | 0.807384E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271582E+09 |
May | 0.103597E+10 | 0.842608E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644553E+09 |
June | 0.103308E+10 | 0.826828E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 310316.31 | 0.500403E+09 |
July | 0.959235E+09 | 0.780731E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1548914.27 | 0.484421E+09 |
August | 0.107774E+10 | 0.889545E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 201936.81 | 0.355288E+09 |
September | 0.956342E+09 | 0.825753E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371880E+09 |
October | 0.994195E+09 | 0.936031E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372406E+09 |
November | 0.984487E+09 | 0.102380E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434244E+09 |
December | 0.959235E+09 | 0.106964E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576815E+09 |
Annual Sum or Average | 0.119305E+11 | 0.108328E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2061167.40 | 0.479257E+10 |
Minimum of Months | 0.901968E+09 | 0.780731E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199350E+09 |
Maximum of Months | 0.107774E+10 | 0.106964E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1548914.27 | 0.644553E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.674731E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151607E+09 |
February | 0.570983E+09 | 0.552063E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218888E+09 |
March | 0.682256E+09 | 0.608530E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129177E+09 |
April | 0.605404E+09 | 0.511438E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174939E+09 |
May | 0.655811E+09 | 0.531878E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432291E+09 |
June | 0.653980E+09 | 0.521446E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 206880.97 | 0.340190E+09 |
July | 0.607235E+09 | 0.492138E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 876275.70 | 0.328468E+09 |
August | 0.682256E+09 | 0.563431E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 134634.98 | 0.235474E+09 |
September | 0.605404E+09 | 0.526736E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236607E+09 |
October | 0.629366E+09 | 0.604732E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236432E+09 |
November | 0.623221E+09 | 0.667356E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277204E+09 |
December | 0.607235E+09 | 0.705007E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373123E+09 |
Annual Sum or Average | 0.755252E+10 | 0.695948E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1217791.64 | 0.313440E+10 |
Minimum of Months | 0.570983E+09 | 0.492138E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129177E+09 |
Maximum of Months | 0.682256E+09 | 0.705007E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 876275.70 | 0.432291E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.109479E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126619E+09 |
February | 0.901968E+09 | 0.886512E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182737E+09 |
March | 0.107774E+10 | 0.962002E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106465E+09 |
April | 0.956342E+09 | 0.805318E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21777.82 | 0.137812E+09 |
May | 0.103597E+10 | 0.836335E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.73 | 0.343142E+09 |
June | 0.103308E+10 | 0.820466E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 172489.87 | 0.270039E+09 |
July | 0.959235E+09 | 0.773981E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 890760.46 | 0.258175E+09 |
August | 0.107774E+10 | 0.884798E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111870.13 | 0.184527E+09 |
September | 0.956342E+09 | 0.829599E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193906E+09 |
October | 0.994195E+09 | 0.962510E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200893E+09 |
November | 0.984487E+09 | 0.107765E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243008E+09 |
December | 0.959235E+09 | 0.114097E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327147E+09 |
Annual Sum or Average | 0.119305E+11 | 0.110749E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1196901.01 | 0.257447E+10 |
Minimum of Months | 0.901968E+09 | 0.773981E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106465E+09 |
Maximum of Months | 0.107774E+10 | 0.114097E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 890760.46 | 0.343142E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.665583E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85666503.81 |
February | 0.571020E+09 | 0.546605E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123834E+09 |
March | 0.682301E+09 | 0.603886E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71846324.88 |
April | 0.605444E+09 | 0.509413E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99041223.69 |
May | 0.655854E+09 | 0.531847E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 0.242280E+09 |
June | 0.654023E+09 | 0.522328E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113628.61 | 0.187246E+09 |
July | 0.607275E+09 | 0.492626E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 575144.49 | 0.182926E+09 |
August | 0.682301E+09 | 0.560546E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73687.89 | 0.132199E+09 |
September | 0.605444E+09 | 0.520453E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140198E+09 |
October | 0.629407E+09 | 0.597212E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138349E+09 |
November | 0.623262E+09 | 0.660934E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163477E+09 |
December | 0.607275E+09 | 0.689704E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218310E+09 |
Annual Sum or Average | 0.755301E+10 | 0.690114E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 762462.79 | 0.178537E+10 |
Minimum of Months | 0.571020E+09 | 0.492626E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71846324.88 |
Maximum of Months | 0.682301E+09 | 0.689704E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 575144.49 | 0.242280E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.102610E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444452E+10 |
February | 0.901968E+09 | 0.849162E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390123E+10 |
March | 0.107774E+10 | 0.947198E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426346E+10 |
April | 0.956342E+09 | 0.806629E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314484E+10 |
May | 0.103597E+10 | 0.841602E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.58 | 0.337752E+10 |
June | 0.103308E+10 | 0.825801E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12642650.86 | 0.240048E+10 |
July | 0.959235E+09 | 0.779878E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21664887.61 | 0.185907E+10 |
August | 0.107774E+10 | 0.888514E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9492216.00 | 0.187884E+10 |
September | 0.956342E+09 | 0.824407E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222101E+10 |
October | 0.994195E+09 | 0.933415E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324387E+10 |
November | 0.984487E+09 | 0.102084E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394440E+10 |
December | 0.959235E+09 | 0.106623E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431654E+10 |
Annual Sum or Average | 0.119305E+11 | 0.108098E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43799839.04 | 0.389958E+11 |
Minimum of Months | 0.901968E+09 | 0.779878E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185907E+10 |
Maximum of Months | 0.107774E+10 | 0.106623E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21664887.61 | 0.444452E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.671929E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85349850.55 |
February | 0.570983E+09 | 0.550283E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124650E+09 |
March | 0.682256E+09 | 0.606855E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71220819.30 |
April | 0.605404E+09 | 0.510403E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97432377.16 |
May | 0.655811E+09 | 0.531384E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 0.243820E+09 |
June | 0.653980E+09 | 0.520876E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113630.41 | 0.191613E+09 |
July | 0.607235E+09 | 0.491814E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 467090.62 | 0.185734E+09 |
August | 0.682256E+09 | 0.562761E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73692.76 | 0.133649E+09 |
September | 0.605404E+09 | 0.525332E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137313E+09 |
October | 0.629366E+09 | 0.602440E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137785E+09 |
November | 0.623221E+09 | 0.663579E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162946E+09 |
December | 0.607235E+09 | 0.701702E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217494E+09 |
Annual Sum or Average | 0.755252E+10 | 0.693936E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 654415.65 | 0.178901E+10 |
Minimum of Months | 0.570983E+09 | 0.491814E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71220819.30 |
Maximum of Months | 0.682256E+09 | 0.701702E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 467090.62 | 0.243820E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.110087E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199044E+09 |
February | 0.901968E+09 | 0.890719E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288491E+09 |
March | 0.107774E+10 | 0.965925E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170480E+09 |
April | 0.956342E+09 | 0.806491E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225534E+09 |
May | 0.103597E+10 | 0.837315E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551995E+09 |
June | 0.103308E+10 | 0.820964E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262560.84 | 0.430955E+09 |
July | 0.959235E+09 | 0.774714E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1284762.75 | 0.410852E+09 |
August | 0.107774E+10 | 0.885670E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 170538.91 | 0.296388E+09 |
September | 0.956342E+09 | 0.831154E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307219E+09 |
October | 0.994195E+09 | 0.966933E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314684E+09 |
November | 0.984487E+09 | 0.108447E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374189E+09 |
December | 0.959235E+09 | 0.114872E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502705E+09 |
Annual Sum or Average | 0.119305E+11 | 0.111139E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1717862.49 | 0.407254E+10 |
Minimum of Months | 0.901968E+09 | 0.774714E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170480E+09 |
Maximum of Months | 0.107774E+10 | 0.114872E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1284762.75 | 0.551995E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.667464E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133881E+09 |
February | 0.421807E+09 | 0.548527E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194020E+09 |
March | 0.502994E+09 | 0.605242E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113907E+09 |
April | 0.447140E+09 | 0.510006E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154646E+09 |
May | 0.484071E+09 | 0.532298E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373031E+09 |
June | 0.482240E+09 | 0.522680E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 175035.90 | 0.288958E+09 |
July | 0.448971E+09 | 0.493195E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 930734.82 | 0.278970E+09 |
August | 0.502994E+09 | 0.561208E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113692.16 | 0.201468E+09 |
September | 0.447140E+09 | 0.521131E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211970E+09 |
October | 0.465148E+09 | 0.599299E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211579E+09 |
November | 0.460569E+09 | 0.663397E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250016E+09 |
December | 0.448971E+09 | 0.692881E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335177E+09 |
Annual Sum or Average | 0.557719E+10 | 0.691733E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1219462.88 | 0.274762E+10 |
Minimum of Months | 0.421807E+09 | 0.493195E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113907E+09 |
Maximum of Months | 0.502994E+09 | 0.692881E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 930734.82 | 0.373031E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.103006E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211823E+09 |
February | 0.901968E+09 | 0.850911E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304591E+09 |
March | 0.107774E+10 | 0.949504E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175313E+09 |
April | 0.956342E+09 | 0.807384E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236995E+09 |
May | 0.103597E+10 | 0.842608E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563653E+09 |
June | 0.103308E+10 | 0.826828E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262552.19 | 0.434485E+09 |
July | 0.959235E+09 | 0.780731E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1329038.25 | 0.420863E+09 |
August | 0.107774E+10 | 0.889545E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 170535.97 | 0.309430E+09 |
September | 0.956342E+09 | 0.825753E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327766E+09 |
October | 0.994195E+09 | 0.936031E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332961E+09 |
November | 0.984487E+09 | 0.102380E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391122E+09 |
December | 0.959235E+09 | 0.106964E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517731E+09 |
Annual Sum or Average | 0.119305E+11 | 0.108328E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1762126.41 | 0.422673E+10 |
Minimum of Months | 0.901968E+09 | 0.780731E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175313E+09 |
Maximum of Months | 0.107774E+10 | 0.106964E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1329038.25 | 0.563653E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.674731E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133726E+09 |
February | 0.570983E+09 | 0.552063E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195085E+09 |
March | 0.682256E+09 | 0.608530E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113489E+09 |
April | 0.605404E+09 | 0.511438E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153382E+09 |
May | 0.655811E+09 | 0.531878E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378122E+09 |
June | 0.653980E+09 | 0.521446E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 175035.26 | 0.295219E+09 |
July | 0.607235E+09 | 0.492138E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 723144.34 | 0.285413E+09 |
August | 0.682256E+09 | 0.563431E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113699.91 | 0.205430E+09 |
September | 0.605404E+09 | 0.526736E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210172E+09 |
October | 0.629366E+09 | 0.604732E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212344E+09 |
November | 0.623221E+09 | 0.667356E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249867E+09 |
December | 0.607235E+09 | 0.705007E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334368E+09 |
Annual Sum or Average | 0.755252E+10 | 0.695948E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1011879.51 | 0.276662E+10 |
Minimum of Months | 0.570983E+09 | 0.492138E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113489E+09 |
Maximum of Months | 0.682256E+09 | 0.705007E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 723144.34 | 0.378122E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281315E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411777E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237557E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312791E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766645E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184806.22 | 0.591311E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1308241.42 | 0.569725E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130910.74 | 0.418793E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440884E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454629E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544083E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724172E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1623958.37 | 0.575368E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237557E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1308241.42 | 0.766645E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342510E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501506E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291412E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390979E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961245E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239016.69 | 0.746827E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1732127.78 | 0.716344E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172178.38 | 0.526836E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545726E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552447E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655475E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872311E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2143322.85 | 0.710362E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291412E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1732127.78 | 0.961245E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345559E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498446E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300830E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413592E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994184E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88817.89 | 0.784102E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1098774.25 | 0.753761E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95089.74 | 0.544103E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550873E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543176E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633296E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851201E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1282681.87 | 0.721312E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300830E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1098774.25 | 0.994184E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 699.78 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 780.42 | 08-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 1388.60 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 772.97 | 27-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 1388.60 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 746.16 | 23-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 833.48 | 03-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1183.13 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 759.45 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 | 13-JUN-15:30 | 875.51 | 05-JUN-21:13 |
July | 1306.65 | 03-JUL-09:09 | 833.48 | 07-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.31 | 22-JUL-17:01 | 809.42 | 30-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 1111.04 | 22-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.31 | 14-AUG-16:50 | 582.94 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 1111.04 | 08-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 705.80 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 16-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 863.53 | 20-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 796.18 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1382.49 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.94 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 69.31 | 1382.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1007.95 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 465.00 | 08-JAN-08:00 |
February | 827.22 | 01-FEB-10:09 | 1007.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 519.67 | 08-FEB-22:03 |
March | 827.22 | 01-MAR-10:09 | 879.10 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 514.68 | 27-MAR-21:05 |
April | 827.22 | 03-APR-09:09 | 703.38 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 495.72 | 23-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 527.66 | 15-MAY-15:20 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 778.99 | 04-MAY-23:00 |
June | 827.22 | 01-JUN-09:09 | 480.79 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 | 13-JUN-15:30 | 685.31 | 18-JUN-10:07 |
July | 827.22 | 03-JUL-09:09 | 527.66 | 07-JUL-15:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.87 | 22-JUL-19:10 | 538.55 | 30-JUL-19:00 |
August | 827.22 | 01-AUG-09:09 | 574.53 | 22-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 14-AUG-16:50 | 376.43 | 22-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 703.38 | 08-SEP-07:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 472.16 | 06-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 1007.95 | 16-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 570.31 | 20-OCT-22:00 |
November | 827.22 | 01-NOV-09:09 | 1007.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 528.61 | 16-NOV-22:05 |
December | 827.22 | 01-DEC-10:09 | 1007.95 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 910.23 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.43 | |||||
Maximum of Months | 827.22 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 60.87 | 910.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 719.83 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 782.37 | 08-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 1388.60 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 772.95 | 27-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 1185.08 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 855.30 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 833.48 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1179.87 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 759.45 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 | 13-JUN-15:30 | 987.94 | 18-JUN-15:50 |
July | 1306.65 | 03-JUL-09:09 | 833.48 | 07-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.87 | 22-JUL-19:10 | 864.89 | 30-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 1111.04 | 22-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.31 | 14-AUG-16:50 | 591.20 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 1111.04 | 08-SEP-07:19 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 716.49 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 16-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 882.35 | 20-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 800.70 | 26-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1393.14 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 591.20 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 83.87 | 1393.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1007.89 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 464.83 | 08-JAN-08:00 |
February | 827.17 | 01-FEB-10:09 | 1007.89 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 520.69 | 08-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 879.04 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 514.76 | 27-MAR-21:05 |
April | 827.17 | 03-APR-09:09 | 879.04 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 501.38 | 15-APR-17:40 |
May | 827.17 | 01-MAY-09:09 | 574.49 | 04-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 783.31 | 04-MAY-23:00 |
June | 827.17 | 01-JUN-09:09 | 527.63 | 14-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 | 13-JUN-15:30 | 716.10 | 18-JUN-16:30 |
July | 827.17 | 03-JUL-09:09 | 527.63 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.18 | 22-JUL-19:08 | 719.86 | 30-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 703.34 | 22-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 14-AUG-16:50 | 403.39 | 22-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 879.04 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 470.73 | 06-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 1007.89 | 16-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 580.40 | 20-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 529.03 | 16-NOV-22:05 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 906.89 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 527.63 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.39 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 40.18 | 906.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 426.53 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 416.75 | 08-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 1388.60 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 413.59 | 27-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 1185.08 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 | 30-APR-19:00 | 431.24 | 23-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 833.48 | 03-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 674.83 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 759.45 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 | 13-JUN-15:30 | 474.97 | 05-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 833.48 | 07-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.07 | 22-JUL-19:10 | 429.54 | 30-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 907.52 | 08-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.38 | 14-AUG-16:50 | 319.06 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 1111.04 | 08-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 419.57 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 16-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 500.87 | 20-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 493.80 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 776.19 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.06 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 48.07 | 776.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1007.95 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 286.64 | 08-JAN-08:00 |
February | 827.22 | 01-FEB-10:09 | 1007.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 277.70 | 08-FEB-22:03 |
March | 827.22 | 01-MAR-10:09 | 879.10 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 275.72 | 27-MAR-21:05 |
April | 827.22 | 03-APR-09:09 | 703.38 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 296.01 | 23-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 527.66 | 15-MAY-15:20 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 449.07 | 04-MAY-23:00 |
June | 827.22 | 01-JUN-09:09 | 480.79 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.25 | 13-JUN-15:30 | 361.27 | 18-JUN-10:55 |
July | 827.22 | 03-JUL-09:09 | 527.66 | 07-JUL-15:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.42 | 22-JUL-19:10 | 301.62 | 30-JUL-19:00 |
August | 827.22 | 01-AUG-09:09 | 574.53 | 22-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.25 | 14-AUG-16:50 | 218.39 | 22-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 574.53 | 08-SEP-07:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 297.21 | 06-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 1007.95 | 16-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 335.93 | 01-OCT-24:00 |
November | 827.22 | 01-NOV-09:09 | 1007.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 325.41 | 26-NOV-04:00 |
December | 827.22 | 01-DEC-10:09 | 1007.95 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 513.50 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.39 | |||||
Maximum of Months | 827.22 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 32.42 | 513.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 20989.64 | 10-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 20748.92 | 17-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1388.60 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 17548.58 | 08-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 1111.04 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 14753.36 | 20-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 833.48 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 | 22-MAY-15:00 | 13539.29 | 02-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 759.45 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2398.91 | 13-JUN-17:00 | 11177.66 | 08-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 833.48 | 07-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3978.43 | 21-JUL-17:00 | 9851.95 | 05-JUL-06:05 |
August | 1306.65 | 01-AUG-09:09 | 907.52 | 08-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2401.35 | 14-AUG-17:00 | 10403.50 | 24-AUG-06:05 |
September | 1306.65 | 01-SEP-09:09 | 1111.04 | 08-SEP-07:30 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 13590.61 | 21-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 16-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 15471.10 | 04-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 18257.96 | 29-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 19805.73 | 29-DEC-17:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9851.95 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3978.43 | 20989.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1007.89 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 284.42 | 08-JAN-08:00 |
February | 827.17 | 01-FEB-10:09 | 1007.89 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 278.22 | 08-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 879.04 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 275.46 | 27-MAR-21:05 |
April | 827.17 | 03-APR-09:09 | 879.04 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 292.34 | 23-APR-22:00 |
May | 827.17 | 01-MAY-09:09 | 527.63 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 453.80 | 04-MAY-23:00 |
June | 827.17 | 01-JUN-09:09 | 527.63 | 14-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.25 | 13-JUN-15:30 | 367.53 | 18-JUN-16:00 |
July | 827.17 | 03-JUL-09:09 | 527.63 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.15 | 22-JUL-19:10 | 373.23 | 30-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 703.34 | 22-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.25 | 14-AUG-16:50 | 236.80 | 22-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 879.04 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 288.19 | 06-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 1007.89 | 16-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 339.70 | 01-OCT-24:00 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 324.88 | 25-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 511.71 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 527.63 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.80 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 21.15 | 511.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 658.98 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 654.36 | 08-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 1388.60 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 649.30 | 27-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 1388.60 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 683.90 | 23-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 833.48 | 03-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1059.37 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 759.45 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.15 | 13-JUN-15:30 | 754.97 | 05-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 833.48 | 07-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.35 | 22-JUL-17:01 | 684.64 | 30-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 1111.04 | 22-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 | 14-AUG-16:50 | 508.82 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 1111.04 | 08-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 650.27 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 16-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 775.03 | 20-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 743.78 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1203.76 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.82 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 62.35 | 1203.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1007.95 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 437.90 | 08-JAN-08:00 |
February | 805.43 | 01-FEB-08:09 | 1007.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 435.56 | 08-FEB-22:03 |
March | 805.43 | 01-MAR-08:09 | 879.10 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 432.07 | 27-MAR-21:05 |
April | 805.43 | 03-APR-07:10 | 703.38 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 454.21 | 23-APR-22:00 |
May | 805.43 | 01-MAY-07:10 | 527.66 | 15-MAY-15:20 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 694.16 | 04-MAY-23:00 |
June | 805.43 | 01-JUN-07:10 | 480.79 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 | 13-JUN-15:30 | 578.16 | 18-JUN-10:13 |
July | 805.43 | 03-JUL-07:10 | 527.66 | 07-JUL-15:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.57 | 22-JUL-19:10 | 452.60 | 30-JUL-19:00 |
August | 805.43 | 01-AUG-07:10 | 574.53 | 22-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.70 | 14-AUG-16:50 | 327.66 | 22-AUG-21:10 |
September | 805.43 | 01-SEP-07:10 | 703.38 | 08-SEP-07:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 433.74 | 06-SEP-04:00 |
October | 805.43 | 02-OCT-07:10 | 1007.95 | 16-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 509.74 | 20-OCT-22:00 |
November | 805.43 | 01-NOV-07:10 | 1007.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 490.23 | 25-NOV-05:00 |
December | 805.43 | 01-DEC-08:09 | 1007.95 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 790.64 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.66 | |||||
Maximum of Months | 805.43 | 1007.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 55.57 | 790.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1592.13 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 675.92 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 1592.13 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 679.22 | 05-FEB-14:00 |
March | 1306.65 | 01-MAR-10:09 | 1388.60 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 649.22 | 27-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 1185.08 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 688.97 | 16-APR-11:53 |
May | 1306.65 | 01-MAY-09:09 | 833.48 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1054.25 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 759.45 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.15 | 13-JUN-15:30 | 821.54 | 18-JUN-15:50 |
July | 1306.65 | 03-JUL-09:09 | 833.48 | 07-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.87 | 22-JUL-19:10 | 729.64 | 30-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 1111.04 | 22-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 14-AUG-16:50 | 515.99 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 1111.04 | 08-SEP-07:19 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 658.15 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1592.13 | 16-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 798.85 | 01-OCT-24:00 |
November | 1306.65 | 01-NOV-09:09 | 1592.13 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 750.43 | 26-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1592.13 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1213.13 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.99 | |||||
Maximum of Months | 1306.65 | 1592.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 75.87 | 1213.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1007.89 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 437.76 | 08-JAN-08:00 |
February | 827.17 | 01-FEB-10:09 | 1007.89 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 436.69 | 08-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 879.04 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 432.23 | 27-MAR-21:05 |
April | 827.17 | 03-APR-09:09 | 879.04 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 452.47 | 23-APR-22:00 |
May | 827.17 | 01-MAY-09:09 | 574.49 | 04-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 700.10 | 04-MAY-23:00 |
June | 827.17 | 01-JUN-09:09 | 527.63 | 14-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 | 13-JUN-15:30 | 597.72 | 18-JUN-16:30 |
July | 827.17 | 03-JUL-09:09 | 527.63 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.58 | 22-JUL-19:08 | 598.17 | 30-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 703.34 | 22-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.70 | 14-AUG-16:50 | 351.51 | 22-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 879.04 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 433.33 | 06-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 1007.89 | 16-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 519.02 | 20-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 1007.89 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 489.89 | 25-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 1007.89 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 789.07 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 527.63 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.51 | |||||
Maximum of Months | 827.17 | 1007.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 32.58 | 789.07 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 975.13 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 908.63 | 08-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 888.54 | 27-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 987.57 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1524.26 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 13-JUN-16:00 | 1037.81 | 05-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.13 | 22-JUL-18:52 | 957.47 | 30-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.66 | 14-AUG-17:00 | 721.29 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 948.19 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1125.88 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1125.59 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1760.46 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.29 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.13 | 1760.46 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1182.08 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1121.47 | 08-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1089.70 | 27-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1209.92 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1899.91 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.15 | 13-JUN-16:00 | 1314.98 | 05-JUN-21:17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.90 | 22-JUL-18:52 | 1187.39 | 30-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 | 14-AUG-17:00 | 912.20 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1169.13 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1367.01 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1334.51 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2140.95 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 912.20 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.90 | 2140.95 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1046.02 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1155.74 | 08-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1158.95 | 27-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1145.87 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1834.62 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.37 | 13-JUN-17:00 | 1582.44 | 18-JUN-15:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.74 | 22-JUL-18:52 | 1391.49 | 30-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 14-AUG-18:00 | 911.50 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1052.09 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1306.65 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1218.63 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2277.43 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 911.50 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.74 | 2277.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17483.26 | 26-JAN-08:06 | 48280.06 | 60419.97 | 145481.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16320.87 | 10-FEB-08:20 | 12070.02 | 15104.99 | 36370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17387.33 | 23-MAR-07:07 | 36210.05 | 45314.98 | 109111.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28786.15 | 20-APR-05:03 | 2541.06 | 3356.58 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29123.69 | 01-MAY-06:03 | 5082.11 | 10070.13 | 35187.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40784.70 | 14-JUN-06:02 | 6352.64 | 12587.66 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41652.95 | 24-JUL-06:02 | 6352.64 | 12587.66 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41090.87 | 07-AUG-06:02 | 7623.17 | 15105.19 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40869.14 | 14-SEP-06:02 | 7623.17 | 15105.19 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21097.21 | 03-OCT-16:00 | 6035.01 | 7552.50 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18575.70 | 15-NOV-08:07 | 24140.03 | 30209.98 | 72740.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14471.06 | 22-DEC-08:20 | 12070.02 | 15104.99 | 36370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14471.06 | 2541.06 | 3356.58 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41652.95 | 48280.06 | 60419.97 | 145481.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 718.60 | 21-JAN-13:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.22 |
February | 1110.00 | 27-FEB-17:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.10 |
March | 2088.81 | 25-MAR-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.65 |
April | 7752.35 | 28-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.90 |
May | 8203.61 | 22-MAY-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 |
June | 9223.92 | 13-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 |
July | 9252.01 | 21-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 | 0.00 |
August | 8358.12 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 |
September | 7110.05 | 13-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.40 |
October | 3394.48 | 03-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.07 |
November | 872.42 | 11-NOV-13:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.53 |
December | 111.12 | 06-DEC-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 111.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9252.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 | 517.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1986.44 | 07-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.20 |
February | 1770.18 | 16-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.17 |
March | 2010.80 | 04-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.60 |
April | 2743.64 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 |
May | 2880.80 | 23-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.84 |
June | 3804.84 | 13-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 0.00 |
July | 3881.01 | 24-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.94 |
August | 3313.81 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 | 0.00 |
September | 3165.71 | 13-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 |
October | 1377.00 | 19-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.17 |
November | 1956.78 | 17-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.47 |
December | 2087.62 | 23-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1377.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3881.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 203.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2522.57 | 06-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2817.50 | 16-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.71 |
March | 2698.86 | 04-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.88 |
April | 3219.13 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 |
May | 3289.88 | 01-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.44 |
June | 4231.70 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 0.00 |
July | 4302.06 | 24-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.43 |
August | 3900.11 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.75 | 0.00 |
September | 3867.97 | 13-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.07 |
October | 2305.87 | 06-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.66 |
November | 2321.90 | 17-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.68 |
December | 2682.77 | 08-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2305.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4302.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 197.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7704.24 | 20-JAN-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7656.89 | 10-FEB-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7768.51 | 31-MAR-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15332.31 | 28-APR-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15872.34 | 23-MAY-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16975.45 | 13-JUN-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 27955.81 | 24-JUL-06:02 | 6352.64 | 12587.66 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16549.88 | 18-AUG-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16309.34 | 13-SEP-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13202.11 | 04-OCT-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8026.61 | 10-NOV-16:50 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7204.30 | 21-DEC-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7204.30 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27955.81 | 6352.64 | 12587.66 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7453.26 | 20-JAN-16:40 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7448.99 | 09-FEB-17:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7664.98 | 31-MAR-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16382.89 | 28-APR-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17164.37 | 23-MAY-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18736.50 | 13-JUN-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18885.90 | 24-JUL-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17538.48 | 17-AUG-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16877.28 | 13-SEP-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12112.68 | 03-OCT-16:00 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7713.63 | 10-NOV-16:30 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7001.46 | 21-DEC-15:20 | 12070.02 | 15104.99 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7001.46 | 6035.01 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18885.90 | 12070.02 | 15104.99 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1287.57 | 19-JAN-16:20 | 1272.23 | 1388.60 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1251.97 | 09-FEB-16:10 | 1272.23 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.07 |
March | 1448.05 | 30-MAR-15:40 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.91 |
April | 3942.56 | 28-APR-15:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.25 |
May | 4384.56 | 22-MAY-15:20 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 |
June | 5621.27 | 13-JUN-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 22.56 | 0.00 |
July | 5373.53 | 21-JUL-15:50 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 | 0.00 |
August | 4845.56 | 14-AUG-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 | 0.00 |
September | 4173.69 | 13-SEP-15:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 |
October | 1849.51 | 06-OCT-15:50 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.09 |
November | 1377.83 | 10-NOV-15:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.25 |
December | 1140.03 | 21-DEC-15:20 | 2544.47 | 2777.21 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1140.03 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5621.27 | 2544.47 | 2777.21 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 22.56 | 144.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1412.72 | 20-JAN-10:30 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1506.55 | 24-FEB-10:30 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.37 |
March | 1458.93 | 25-MAR-09:50 | 261.23 | 160.27 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8651.47 | 30-APR-09:02 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.47 |
May | 10044.28 | 21-MAY-09:23 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.89 |
June | 11586.51 | 25-JUN-10:23 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.37 |
July | 14393.75 | 16-JUL-09:32 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.10 |
August | 14173.82 | 20-AUG-09:22 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.59 |
September | 7115.48 | 10-SEP-09:23 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.53 |
October | 3447.03 | 04-OCT-10:00 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1375.54 | 03-NOV-09:50 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 |
December | 1192.97 | 06-DEC-10:10 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1192.97 | 169.56 | 106.84 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14393.75 | 827.22 | 480.79 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6758.29 | 20-JAN-12:00 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8304.78 | 17-FEB-13:40 | 2544.47 | 1518.89 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.74 |
March | 4131.80 | 28-MAR-12:05 | 5088.93 | 3037.79 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.46 |
April | 21117.83 | 30-APR-13:02 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.06 |
May | 10418.11 | 22-MAY-13:10 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.38 |
June | 10924.81 | 11-JUN-13:53 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.67 |
July | 13800.97 | 30-JUL-14:23 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.93 |
August | 21463.10 | 06-AUG-13:22 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.90 |
September | 22430.93 | 10-SEP-13:22 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.06 |
October | 14512.45 | 01-OCT-13:32 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.72 |
November | 7144.79 | 03-NOV-12:40 | 2544.47 | 1518.89 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.42 |
December | 5503.20 | 18-DEC-13:25 | 2544.47 | 1518.89 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4131.80 | 267.84 | 168.76 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22430.93 | 5088.93 | 3037.79 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1770.50 | 19-JAN-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2745.91 | 27-FEB-16:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2996.68 | 23-MAR-16:50 | 254.33 | 267.09 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.51 |
April | 15067.85 | 30-APR-16:22 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.89 |
May | 12429.59 | 21-MAY-16:32 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.62 |
June | 16635.46 | 11-JUN-17:12 | 0.00 | 160.25 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.60 |
July | 15777.40 | 16-JUL-16:52 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.05 |
August | 16478.67 | 13-AUG-16:32 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.90 |
September | 11825.75 | 10-SEP-16:03 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.34 |
October | 5334.89 | 03-OCT-15:40 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.48 |
November | 1799.30 | 10-NOV-15:40 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.12 |
December | 1431.92 | 21-DEC-14:40 | 827.17 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1431.92 | 0.00 | 106.83 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16635.46 | 827.17 | 480.76 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1230.36 | 19-JAN-15:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1199.71 | 10-FEB-15:50 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.47 |
March | 1359.86 | 30-MAR-14:00 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.61 |
April | 2305.19 | 28-APR-15:40 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 |
May | 2669.91 | 23-MAY-14:00 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 |
June | 4065.59 | 13-JUN-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 | 0.00 |
July | 4005.83 | 21-JUL-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3392.52 | 14-AUG-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.65 | 0.00 |
September | 3101.47 | 13-SEP-15:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.04 |
October | 1637.23 | 06-OCT-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.60 |
November | 1381.75 | 10-NOV-15:10 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.22 |
December | 1155.78 | 22-DEC-14:10 | 1306.65 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1155.78 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4065.59 | 1306.65 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 | 40.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1176.28 | 20-JAN-10:20 | 1654.44 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1225.50 | 24-FEB-10:30 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 |
March | 1165.08 | 31-MAR-09:50 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.72 |
April | 7766.47 | 30-APR-07:33 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.91 |
May | 6089.61 | 23-MAY-09:10 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 |
June | 7692.47 | 25-JUN-10:32 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.14 |
July | 9208.74 | 23-JUL-11:23 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.90 |
August | 6097.00 | 21-AUG-09:30 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.79 |
September | 5525.85 | 12-SEP-09:20 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 |
October | 3057.28 | 04-OCT-10:00 | 827.22 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1198.02 | 03-NOV-09:30 | 1654.44 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 |
December | 1049.65 | 08-DEC-10:30 | 1654.44 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1049.65 | 169.56 | 106.84 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9208.74 | 1654.44 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3538.95 | 21-JAN-11:30 | 401.76 | 253.15 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4039.89 | 04-FEB-14:00 | 133.92 | 126.57 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.02 |
March | 1910.43 | 25-MAR-11:50 | 137.54 | 126.57 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17308.79 | 30-APR-13:31 | 468.72 | 295.33 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.21 |
May | 7496.11 | 22-MAY-13:50 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.90 |
June | 7914.12 | 13-JUN-13:40 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 80.34 | 0.00 |
July | 12801.98 | 23-JUL-13:23 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.99 |
August | 11729.59 | 13-AUG-13:02 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.44 |
September | 17841.29 | 10-SEP-13:22 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.98 |
October | 10870.22 | 03-OCT-12:07 | 3816.70 | 2278.34 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1265.53 |
November | 3896.42 | 11-NOV-13:03 | 200.88 | 126.57 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.36 |
December | 2071.61 | 18-DEC-13:50 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1847.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1910.43 | 133.92 | 126.57 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17841.29 | 3816.70 | 2278.34 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 80.34 | 1847.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1426.99 | 19-JAN-15:50 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1772.29 | 27-FEB-16:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1864.31 | 23-MAR-17:00 | 254.33 | 267.09 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.69 |
April | 13082.64 | 30-APR-17:31 | 0.00 | 186.96 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.46 |
May | 6631.95 | 22-MAY-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 |
June | 8787.33 | 25-JUN-17:42 | 0.00 | 133.54 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 |
July | 10536.67 | 22-JUL-17:04 | 296.72 | 186.96 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 16.08 | 0.00 |
August | 8630.24 | 13-AUG-17:02 | 0.00 | 160.25 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.59 |
September | 6313.83 | 12-SEP-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 |
October | 4455.98 | 03-OCT-16:00 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.79 |
November | 1490.09 | 10-NOV-15:40 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.29 |
December | 1206.72 | 21-DEC-14:50 | 827.17 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1206.72 | 0.00 | 133.54 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13082.64 | 827.17 | 480.76 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 16.08 | 74.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1316.96 | 19-JAN-15:40 | 1272.23 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1298.13 | 24-FEB-16:10 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.92 |
March | 1471.72 | 30-MAR-14:00 | 1306.65 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.95 |
April | 3741.43 | 28-APR-15:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 |
May | 4001.45 | 22-MAY-15:20 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 |
June | 5178.46 | 13-JUN-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18.97 | 0.00 |
July | 4957.41 | 21-JUL-15:50 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 0.00 |
August | 4544.55 | 14-AUG-16:00 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.36 | 0.00 |
September | 4066.20 | 13-SEP-15:30 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.49 |
October | 2143.58 | 06-OCT-15:40 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.33 |
November | 1411.61 | 10-NOV-15:20 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.93 |
December | 1187.23 | 21-DEC-16:10 | 1272.23 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1187.23 | 1272.23 | 759.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5178.46 | 1306.65 | 1592.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18.97 | 56.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1535.22 | 20-JAN-10:00 | 1610.86 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1662.60 | 17-FEB-10:00 | 1610.86 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1585.50 | 25-MAR-09:50 | 0.00 | 160.27 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11036.24 | 30-APR-10:43 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.94 |
May | 12086.50 | 21-MAY-08:53 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.32 |
June | 11811.99 | 11-JUN-09:23 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.51 |
July | 14070.73 | 23-JUL-08:42 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.05 |
August | 11221.59 | 20-AUG-10:13 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.19 |
September | 7275.57 | 12-SEP-09:00 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.27 |
October | 4160.45 | 04-OCT-08:55 | 1610.86 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.41 |
November | 1506.92 | 03-NOV-10:30 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 |
December | 1326.71 | 06-DEC-10:00 | 805.43 | 480.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1326.71 | 0.00 | 106.84 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14070.73 | 1610.86 | 961.59 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7686.45 | 20-JAN-12:00 | 1272.23 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8854.73 | 17-FEB-13:40 | 2544.47 | 1518.89 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.01 |
March | 4740.33 | 28-MAR-12:05 | 5088.93 | 3037.79 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.22 |
April | 19916.05 | 30-APR-12:42 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.95 |
May | 9942.59 | 22-MAY-13:10 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.71 |
June | 9761.90 | 13-JUN-13:10 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 |
July | 18155.29 | 23-JUL-13:23 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.70 |
August | 18764.05 | 06-AUG-14:13 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.72 |
September | 20627.05 | 24-SEP-13:12 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.78 |
October | 11975.69 | 03-OCT-13:10 | 1306.65 | 759.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.58 |
November | 9057.81 | 11-NOV-12:53 | 200.88 | 126.57 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.63 |
December | 6159.26 | 18-DEC-13:25 | 2544.47 | 1518.89 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4740.33 | 200.88 | 126.57 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20627.05 | 5088.93 | 3037.79 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 | 369.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1737.89 | 19-JAN-15:50 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2892.47 | 27-FEB-16:30 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3251.71 | 23-MAR-16:40 | 254.33 | 267.09 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.41 |
April | 13917.98 | 30-APR-16:02 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 |
May | 12139.38 | 21-MAY-16:32 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.58 |
June | 13693.99 | 25-JUN-17:22 | 0.00 | 133.54 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.35 |
July | 16224.05 | 09-JUL-16:51 | 296.72 | 186.96 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.58 |
August | 12905.18 | 20-AUG-16:12 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.71 |
September | 11556.62 | 10-SEP-16:12 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.85 |
October | 5488.88 | 03-OCT-15:40 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.60 |
November | 1902.44 | 10-NOV-15:40 | 805.38 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.82 |
December | 1448.33 | 21-DEC-14:40 | 827.17 | 480.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1448.33 | 0.00 | 106.83 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16224.05 | 827.17 | 480.76 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.58 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.138846E+12 | 215384.09 | 02-JAN-07:10 | 0.333628E+11 | 68192.36 | 10-JAN-07:00 |
February | 0.115596E+12 | 143885.99 | 13-FEB-07:10 | 0.247456E+11 | 58150.65 | 17-FEB-07:30 |
March | 0.126206E+12 | 133035.08 | 06-MAR-07:10 | 0.228816E+11 | 44335.68 | 08-MAR-07:19 |
April | 0.105048E+12 | 109343.94 | 28-APR-15:20 | 0.129543E+11 | 38668.27 | 08-APR-06:10 |
May | 0.110123E+12 | 118281.92 | 22-MAY-15:09 | 0.122288E+11 | 20945.93 | 06-MAY-06:10 |
June | 0.113202E+12 | 141425.65 | 13-JUN-15:39 | 0.114806E+11 | 10676.90 | 08-JUN-06:19 |
July | 0.115947E+12 | 138726.50 | 21-JUL-15:50 | 0.112454E+11 | 10087.49 | 03-JUL-11:09 |
August | 0.127693E+12 | 133758.84 | 14-AUG-15:50 | 0.117401E+11 | 10054.98 | 09-AUG-11:09 |
September | 0.112277E+12 | 124292.71 | 13-SEP-15:09 | 0.110959E+11 | 17218.46 | 21-SEP-06:10 |
October | 0.113849E+12 | 112361.40 | 23-OCT-06:10 | 0.132199E+11 | 29498.03 | 23-OCT-06:19 |
November | 0.123717E+12 | 154313.08 | 27-NOV-07:10 | 0.201511E+11 | 49515.22 | 29-NOV-07:19 |
December | 0.141785E+12 | 181269.51 | 26-DEC-07:10 | 0.317517E+11 | 52475.62 | 29-DEC-20:40 |
Annual Sum or Average | 0.144429E+13 | 0.216858E+12 | ||||
Minimum of Months | 0.105048E+12 | 109343.94 | 0.110959E+11 | 10054.98 | ||
Maximum of Months | 0.141785E+12 | 215384.09 | 0.333628E+11 | 68192.36 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.320561E+11 | 0.127452E+11 | 0.593559E+11 | 0.144080E+10 | 0.422358E+10 | 12379742.02 | 0.290124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.281565E+11 | 0.103280E+11 | 0.537310E+11 | 0.130242E+10 | 0.386666E+10 | 11196021.66 | 0.182005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327155E+11 | 0.981037E+10 | 0.617796E+11 | 0.150724E+10 | 0.452349E+10 | 12675672.10 | 0.158574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.287472E+11 | 0.785270E+10 | 0.572952E+11 | 0.138484E+10 | 0.606683E+10 | 11960507.72 | 0.232367E+10 | 0.136515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.307237E+11 | 0.680460E+10 | 0.605677E+11 | 0.147200E+10 | 0.695951E+10 | 12527707.06 | 0.157183E+10 | 0.201085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.304589E+11 | 0.592702E+10 | 0.594895E+11 | 0.144925E+10 | 0.876698E+10 | 12231776.97 | 0.465324E+09 | 0.663293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.285734E+11 | 0.637925E+10 | 0.583622E+11 | 0.140712E+10 | 0.972409E+10 | 12256437.81 | 0.182348E+09 | 0.113058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.320335E+11 | 0.748276E+10 | 0.617796E+11 | 0.150660E+10 | 0.104749E+11 | 12675672.10 | 0.163818E+09 | 0.142393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.289542E+11 | 0.878112E+10 | 0.572729E+11 | 0.138465E+10 | 0.825404E+10 | 11960507.72 | 0.542291E+09 | 0.707574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.309610E+11 | 0.107594E+11 | 0.593671E+11 | 0.143923E+10 | 0.505675E+10 | 12379742.02 | 0.597735E+10 | 0.276045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316988E+11 | 0.118862E+11 | 0.580818E+11 | 0.141443E+10 | 0.412069E+10 | 12059151.09 | 0.164999E+11 | 2971157.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.317847E+11 | 0.131424E+11 | 0.583511E+11 | 0.141150E+10 | 0.409504E+10 | 12256437.81 | 0.329882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.366863E+12 | 0.111899E+12 | 0.705434E+12 | 0.171201E+11 | 0.761326E+11 | 0.146559E+09 | 0.123785E+12 | 0.429088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.281565E+11 | 0.592702E+10 | 0.537310E+11 | 0.130242E+10 | 0.386666E+10 | 11196021.66 | 0.163818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.327155E+11 | 0.131424E+11 | 0.617796E+11 | 0.150724E+10 | 0.104749E+11 | 12675672.10 | 0.329882E+11 | 0.142393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.214142E+11 | 0.00 | 0.119487E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.138976E+11 | 0.00 | 0.108480E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.105144E+11 | 0.00 | 0.123672E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.152570E+10 | 0.00 | 0.114286E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.365764E+09 | 0.00 | 0.118631E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5048979.51 | 0.00 | 0.114755E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.112454E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.117401E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 69502096.75 | 0.00 | 0.110264E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.170701E+10 | 0.00 | 0.115129E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.877012E+10 | 0.00 | 0.113810E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.200671E+11 | 0.00 | 0.116846E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.783364E+11 | 0.00 | 0.138521E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.108480E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.214142E+11 | 0.00 | 0.123672E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 38257.79 | 02-JAN-08:09 | 8596.48 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 1242.18 | 09-JAN-08:20 | 5809.74 | 02-JAN-07:10 | 6.85 | 03-JAN-06:10 | 166765.69 | 02-JAN-07:10 |
February | 38257.79 | 01-FEB-08:09 | 8596.48 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 1242.18 | 01-FEB-08:20 | 4314.33 | 17-FEB-13:39 | 6.85 | 04-FEB-06:10 | 97180.23 | 13-FEB-07:10 |
March | 36263.56 | 15-MAR-07:10 | 8596.48 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 1238.27 | 15-MAR-07:19 | 3891.14 | 06-MAR-06:19 | 6.85 | 02-MAR-08:09 | 95492.83 | 06-MAR-07:10 |
April | 34848.25 | 10-APR-07:10 | 8596.48 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 1235.50 | 10-APR-07:19 | 17066.73 | 28-APR-15:20 | 6.85 | 06-APR-16:10 | 47607.37 | 03-APR-06:10 |
May | 30777.37 | 04-MAY-07:10 | 8596.48 | 01-MAY-19:19 | 45864.70 | 01-MAY-07:10 | 1227.56 | 04-MAY-07:19 | 15756.60 | 23-MAY-15:09 | 6.85 | 01-MAY-11:09 | 25682.85 | 17-MAY-06:10 |
June | 30239.43 | 14-JUN-07:10 | 8596.48 | 01-JUN-19:00 | 45864.70 | 01-JUN-07:10 | 1226.52 | 14-JUN-07:19 | 21559.88 | 13-JUN-15:39 | 6.85 | 06-JUN-16:10 | 14422.13 | 08-JUN-06:10 |
July | 30683.64 | 07-JUL-07:10 | 8596.48 | 01-JUL-20:19 | 45864.70 | 03-JUL-07:10 | 1227.38 | 07-JUL-07:19 | 20948.48 | 21-JUL-15:39 | 6.85 | 01-JUL-05:10 | 8652.03 | 05-JUL-06:10 |
August | 32750.30 | 22-AUG-07:30 | 8596.48 | 01-AUG-19:49 | 45864.70 | 01-AUG-07:10 | 1231.41 | 22-AUG-07:40 | 20067.25 | 14-AUG-15:30 | 6.85 | 01-AUG-05:10 | 8452.83 | 24-AUG-06:10 |
September | 33415.05 | 08-SEP-07:30 | 8596.48 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 1232.70 | 08-SEP-07:40 | 19082.43 | 12-SEP-15:09 | 6.85 | 01-SEP-05:10 | 21014.91 | 20-SEP-06:10 |
October | 38257.79 | 16-OCT-07:10 | 8596.48 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 1242.18 | 16-OCT-07:19 | 9910.00 | 03-OCT-15:09 | 6.85 | 23-OCT-05:19 | 66075.09 | 23-OCT-06:10 |
November | 38257.79 | 01-NOV-07:10 | 8596.48 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 1242.18 | 01-NOV-07:19 | 4400.56 | 03-NOV-12:50 | 6.85 | 03-NOV-07:10 | 107420.32 | 27-NOV-07:10 |
December | 38257.79 | 01-DEC-08:09 | 8596.48 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 1242.18 | 01-DEC-08:20 | 5087.04 | 26-DEC-06:19 | 6.85 | 01-DEC-06:19 | 133758.08 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 30239.43 | 8596.48 | 45864.70 | 1226.52 | 3891.14 | 6.85 | 8452.83 | |||||||
Maximum of Months | 38257.79 | 8596.48 | 45864.70 | 1242.18 | 21559.88 | 6.85 | 166765.69 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18874.85 | 28-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29869.42 | 22-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 46522.12 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 44688.33 | 21-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 40523.11 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32314.46 | 13-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8304.51 | 07-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2209.84 | 24-NOV-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46522.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 215384.09 | 02-JAN-07:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 5809.74 | 6.85 | 166765.69 | 0.00 | 0.00 |
February | 143885.99 | 13-FEB-07:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 3897.08 | 6.85 | 97180.23 | 0.00 | 0.00 |
March | 133035.08 | 06-MAR-07:10 | 12216.86 | 21098.80 | 0.00 | 353.74 | 3866.00 | 6.85 | 95492.83 | 0.00 | 0.00 |
April | 109343.94 | 28-APR-15:20 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 17066.73 | 6.85 | 0.00 | 18874.85 | 0.00 |
May | 118281.92 | 22-MAY-15:09 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 15327.73 | 6.85 | 0.00 | 29551.83 | 0.00 |
June | 141425.65 | 13-JUN-15:39 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 21559.88 | 6.85 | 0.00 | 46463.41 | 0.00 |
July | 138726.50 | 21-JUL-15:50 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 20723.70 | 6.85 | 0.00 | 44600.45 | 0.00 |
August | 133758.84 | 14-AUG-15:50 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 19900.24 | 6.85 | 0.00 | 40456.25 | 0.00 |
September | 124292.71 | 13-SEP-15:09 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 18610.64 | 6.85 | 0.00 | 32279.71 | 0.00 |
October | 112361.40 | 23-OCT-06:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 3477.63 | 6.85 | 66075.09 | 0.00 | 0.00 |
November | 154313.08 | 27-NOV-07:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 4084.08 | 6.85 | 107420.32 | 0.00 | 0.00 |
December | 181269.51 | 26-DEC-07:10 | 12752.77 | 21098.80 | 8596.48 | 353.77 | 4702.76 | 6.85 | 133758.08 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 109343.94 | 12216.86 | 21098.80 | 0.00 | 353.74 | 3477.63 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 215384.09 | 30098.83 | 42072.41 | 8596.48 | 1224.26 | 21559.88 | 6.85 | 166765.69 | 46463.41 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 59207.84 | 10-JAN-07:00 | 0.00 | 10281.33 | 20-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 49876.29 | 17-FEB-07:19 | 0.00 | 10291.73 | 17-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 35400.80 | 08-MAR-07:10 | 0.00 | 10279.58 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 29903.13 | 08-APR-06:10 | 0.00 | 10252.87 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 18942.50 | 06-MAY-06:10 | 0.00 | 10203.23 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 2409.35 | 08-JUN-06:10 | 0.00 | 10136.27 | 02-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 10087.49 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 10054.98 | 09-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 8363.64 | 21-SEP-06:10 | 0.00 | 10076.00 | 26-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 20534.61 | 23-OCT-06:19 | 0.00 | 10139.52 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 40513.29 | 29-NOV-07:19 | 0.00 | 10193.93 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 44826.00 | 29-DEC-20:00 | 0.00 | 10249.11 | 28-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10054.98 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 59207.84 | 0.00 | 10291.73 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.31 | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.31 | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.31 | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.14 | 0.17 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.23 | 0.50 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
Annual Sum or Average | 0.67 | 19.21 | 0.67 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.23 | 0.50 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 18.60 | 2.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
February | 0.83 | 18.79 | 0.67 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
March | 0.33 | 19.24 | 0.33 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 18.75 | 0.67 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
December | 4.00 | 18.37 | 3.00 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
Annual Sum or Average | 8.83 | 18.55 | 6.67 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 19.24 | 3.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 |
February | 0.17 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
March | 0.17 | 19.42 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.96 | 1.00 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.58 | 0.50 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.63 | 1.67 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.06 | 2.67 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.62 | 1.83 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 18.04 | 0.17 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 |
December | 1.50 | 17.48 | 0.67 | 17.97 | 0.00 | 17.97 | 0.00 | 17.97 |
Annual Sum or Average | 3.33 | 17.21 | 1.00 | 17.65 | 7.67 | 24.15 | 7.67 | 25.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.42 | 0.67 | 19.42 | 2.67 | 28.06 | 2.67 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
February | 0.17 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
March | 0.17 | 19.44 | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.27 | 1.67 | 28.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.33 | 1.00 | 27.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.70 | 2.33 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.79 | 4.17 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.86 | 3.50 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.48 | 0.67 | 27.48 |
November | 0.33 | 18.15 | 0.17 | 18.48 | 0.17 | 20.68 | 0.17 | 21.99 |
December | 0.83 | 18.19 | 0.50 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
Annual Sum or Average | 2.00 | 17.86 | 0.83 | 18.23 | 13.50 | 26.14 | 13.50 | 26.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 19.44 | 0.50 | 19.44 | 4.17 | 28.27 | 4.17 | 28.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 16.44 | 0.00 | 16.44 | 0.00 | 16.44 | 0.00 | 16.44 |
February | 0.33 | 18.21 | 0.17 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
March | 0.17 | 19.40 | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.36 | 1.00 | 28.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.83 | 1.00 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.09 | 1.67 | 28.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.22 | 2.67 | 28.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.04 | 2.33 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.80 | 0.83 | 27.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 18.03 | 0.17 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
December | 1.50 | 17.47 | 0.67 | 17.96 | 0.00 | 17.96 | 0.00 | 17.96 |
Annual Sum or Average | 3.17 | 17.44 | 1.17 | 17.90 | 16.17 | 25.94 | 9.50 | 26.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.40 | 0.67 | 19.40 | 5.17 | 28.36 | 2.67 | 28.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.28 | 1.83 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.27 | 0.17 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Annual Sum or Average | 2.33 | 19.28 | 2.00 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.28 | 1.83 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.54 | 0.83 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.41 | 0.33 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.72 | 2.17 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.44 | 0.67 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 17.08 | 0.00 | 17.08 | 4.00 | 27.19 | 4.00 | 27.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.08 | 0.00 | 17.08 | 2.17 | 27.72 | 2.17 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 50.50 | 18.51 | 50.50 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
February | 39.83 | 19.06 | 39.83 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
March | 44.17 | 19.05 | 44.17 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
April | 15.17 | 19.69 | 15.17 | 19.69 | 1.33 | 20.03 | 1.33 | 20.35 |
May | 8.17 | 20.10 | 8.17 | 20.10 | 0.00 | 20.10 | 0.00 | 20.10 |
June | 0.17 | 20.42 | 0.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.42 | 0.67 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.48 | 2.00 | 27.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.67 | 2.33 | 27.67 |
October | 15.33 | 19.80 | 15.33 | 19.80 | 0.83 | 20.00 | 0.83 | 20.19 |
November | 33.83 | 19.24 | 33.83 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
December | 53.00 | 18.72 | 53.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
Annual Sum or Average | 260.17 | 19.02 | 260.17 | 19.02 | 7.17 | 19.14 | 7.17 | 19.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 0.00 | 18.51 |
Maximum of Months | 53.00 | 20.42 | 53.00 | 20.42 | 2.33 | 27.67 | 2.33 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.89 | 0.67 | 27.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.63 | 0.33 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.73 | 0.83 | 27.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.74 | 1.67 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.62 | 1.50 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 17.01 | 0.00 | 17.01 | 9.67 | 27.54 | 5.00 | 27.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.01 | 0.00 | 17.01 | 4.00 | 27.89 | 1.67 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.95 | 0.50 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.05 | 0.33 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
Annual Sum or Average | 1.00 | 18.99 | 0.83 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.05 | 0.50 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.18 | 0.17 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.01 | 1.17 | 28.01 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.65 | 1.00 | 27.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.77 | 2.00 | 27.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.00 | 3.17 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.69 | 2.83 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.55 | 1.33 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.05 | 0.17 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
Annual Sum or Average | 0.50 | 18.47 | 0.33 | 18.78 | 11.50 | 27.19 | 11.50 | 27.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.05 | 0.17 | 19.05 | 3.17 | 28.01 | 3.17 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.19 | 0.00 | 17.19 | 0.17 | 22.24 | 0.17 | 23.93 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.10 | 1.83 | 28.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.62 | 2.33 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.76 | 4.17 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.82 | 4.50 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.66 | 1.00 | 27.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.37 | 0.17 | 27.37 |
December | 0.17 | 19.25 | 0.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Annual Sum or Average | 0.33 | 18.22 | 0.17 | 18.56 | 14.50 | 27.46 | 14.50 | 27.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.25 | 0.17 | 19.25 | 4.50 | 28.10 | 4.50 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.17 | 0.17 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.39 | 0.83 | 28.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.72 | 1.50 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.05 | 1.50 | 28.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.15 | 2.67 | 28.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.96 | 2.50 | 27.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.80 | 0.83 | 27.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.23 | 0.33 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
Annual Sum or Average | 0.67 | 18.70 | 0.50 | 18.95 | 16.33 | 27.41 | 9.83 | 27.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.23 | 0.33 | 19.23 | 5.00 | 28.39 | 2.67 | 28.37 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 461.33 | 23.22 | 18.33 | 23.10 | 18.33 | 23.00 |
February | 428.83 | 23.64 | 0.00 | 23.64 | 0.00 | 23.64 |
March | 475.67 | 23.70 | 0.00 | 23.70 | 0.00 | 23.70 |
April | 109.83 | 23.87 | 47.33 | 24.39 | 0.00 | 24.39 |
May | 28.17 | 23.88 | 144.17 | 24.82 | 0.00 | 24.82 |
June | 0.00 | 0.00 | 337.83 | 24.51 | 0.00 | 24.51 |
July | 0.00 | 0.00 | 397.50 | 24.51 | 0.00 | 24.51 |
August | 0.00 | 0.00 | 408.33 | 24.39 | 0.00 | 24.39 |
September | 0.00 | 0.00 | 287.50 | 24.54 | 0.00 | 24.54 |
October | 144.83 | 23.71 | 57.17 | 24.14 | 0.00 | 24.14 |
November | 329.17 | 23.64 | 0.83 | 23.64 | 0.00 | 23.64 |
December | 494.33 | 23.38 | 0.00 | 23.38 | 0.00 | 23.38 |
Annual Sum or Average | 2472.17 | 23.54 | 1699.00 | 23.94 | 18.33 | 23.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.10 | 0.00 | 23.00 |
Maximum of Months | 494.33 | 23.88 | 408.33 | 24.82 | 18.33 | 24.82 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.83 | 44.50 | 21.68 | 44.50 | 21.56 |
February | 454.00 | 22.15 | 2.50 | 22.14 | 2.50 | 22.13 |
March | 514.00 | 22.43 | 1.50 | 22.42 | 1.50 | 22.42 |
April | 343.00 | 23.43 | 4.00 | 23.45 | 0.00 | 23.45 |
May | 242.50 | 23.45 | 36.33 | 23.57 | 0.00 | 23.57 |
June | 86.17 | 23.51 | 182.17 | 24.08 | 0.00 | 24.08 |
July | 61.50 | 23.42 | 261.67 | 24.14 | 0.00 | 24.14 |
August | 30.00 | 23.50 | 246.67 | 24.21 | 0.00 | 24.21 |
September | 137.83 | 23.38 | 112.00 | 23.80 | 0.00 | 23.80 |
October | 421.33 | 22.97 | 0.00 | 22.97 | 0.00 | 22.97 |
November | 488.83 | 22.36 | 3.33 | 22.35 | 3.33 | 22.34 |
December | 497.00 | 21.65 | 63.17 | 21.54 | 63.17 | 21.45 |
Annual Sum or Average | 3778.17 | 22.51 | 957.83 | 22.78 | 115.00 | 22.72 |
Minimum of Months | 30.00 | 21.65 | 0.00 | 21.54 | 0.00 | 21.45 |
Maximum of Months | 514.00 | 23.51 | 261.67 | 24.21 | 63.17 | 24.21 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.08 | 181.50 | 20.85 | 181.50 | 20.71 |
February | 454.00 | 21.31 | 101.83 | 21.10 | 101.83 | 20.95 |
March | 514.00 | 21.67 | 58.83 | 21.53 | 58.83 | 21.42 |
April | 396.00 | 22.94 | 1.50 | 22.93 | 1.17 | 22.92 |
May | 340.67 | 23.05 | 34.00 | 23.15 | 0.00 | 23.15 |
June | 163.67 | 23.25 | 135.83 | 23.66 | 0.00 | 23.66 |
July | 140.67 | 23.22 | 219.33 | 23.84 | 0.00 | 23.84 |
August | 131.33 | 23.29 | 183.83 | 23.80 | 0.00 | 23.80 |
September | 261.50 | 23.06 | 73.33 | 23.29 | 0.00 | 23.29 |
October | 480.33 | 22.22 | 13.17 | 22.17 | 13.17 | 22.13 |
November | 489.00 | 21.47 | 85.00 | 21.30 | 85.00 | 21.17 |
December | 497.00 | 20.90 | 202.00 | 20.66 | 202.00 | 20.53 |
Annual Sum or Average | 4370.17 | 21.98 | 1290.17 | 22.03 | 643.50 | 21.84 |
Minimum of Months | 131.33 | 20.90 | 1.50 | 20.66 | 0.00 | 20.53 |
Maximum of Months | 514.00 | 23.29 | 219.33 | 23.84 | 202.00 | 23.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.30 | 352.67 | 20.16 | 352.67 | 20.10 |
February | 454.00 | 20.40 | 275.67 | 20.23 | 275.67 | 20.15 |
March | 514.00 | 20.86 | 227.50 | 20.69 | 227.50 | 20.59 |
April | 429.17 | 22.12 | 55.00 | 21.95 | 51.00 | 21.79 |
May | 409.67 | 22.38 | 48.50 | 22.42 | 16.33 | 22.35 |
June | 217.33 | 22.85 | 129.33 | 23.32 | 0.00 | 23.32 |
July | 191.67 | 22.96 | 194.67 | 23.56 | 0.00 | 23.56 |
August | 224.83 | 22.92 | 154.67 | 23.38 | 0.00 | 23.38 |
September | 347.50 | 22.40 | 48.33 | 22.55 | 4.50 | 22.53 |
October | 502.00 | 21.29 | 110.33 | 21.06 | 110.33 | 20.91 |
November | 489.00 | 20.52 | 257.17 | 20.33 | 257.17 | 20.23 |
December | 497.00 | 20.10 | 401.17 | 20.00 | 401.17 | 19.96 |
Annual Sum or Average | 4778.17 | 21.32 | 2255.00 | 21.22 | 1696.33 | 20.98 |
Minimum of Months | 191.67 | 20.10 | 48.33 | 20.00 | 0.00 | 19.96 |
Maximum of Months | 514.00 | 22.96 | 401.17 | 23.56 | 401.17 | 23.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.38 | 336.50 | 20.24 | 336.50 | 20.18 |
February | 454.00 | 20.58 | 246.50 | 20.39 | 246.50 | 20.30 |
March | 514.00 | 20.89 | 208.50 | 20.73 | 208.50 | 20.64 |
April | 318.33 | 22.23 | 84.67 | 22.39 | 31.50 | 22.28 |
May | 300.17 | 22.31 | 121.50 | 22.80 | 9.83 | 22.75 |
June | 192.33 | 22.80 | 229.00 | 23.61 | 6.67 | 23.66 |
July | 155.17 | 23.17 | 287.50 | 23.99 | 13.33 | 24.08 |
August | 177.83 | 22.98 | 277.00 | 23.76 | 7.83 | 23.82 |
September | 233.00 | 22.27 | 182.33 | 23.14 | 5.00 | 23.11 |
October | 451.50 | 21.23 | 95.50 | 21.06 | 90.17 | 20.92 |
November | 489.00 | 20.59 | 226.83 | 20.39 | 226.83 | 20.29 |
December | 497.00 | 20.15 | 387.00 | 20.04 | 387.00 | 20.00 |
Annual Sum or Average | 4284.33 | 21.24 | 2682.83 | 21.49 | 1569.67 | 21.24 |
Minimum of Months | 155.17 | 20.15 | 84.67 | 20.04 | 5.00 | 20.00 |
Maximum of Months | 514.00 | 23.17 | 387.00 | 23.99 | 387.00 | 24.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 469.17 | 20.74 | 273.83 | 20.55 | 267.83 | 20.44 |
February | 409.17 | 20.94 | 206.17 | 20.77 | 190.17 | 20.62 |
March | 500.83 | 21.07 | 191.83 | 20.87 | 191.83 | 20.75 |
April | 309.83 | 22.09 | 136.50 | 22.40 | 48.67 | 22.27 |
May | 330.67 | 22.08 | 132.00 | 22.54 | 21.00 | 22.44 |
June | 230.50 | 22.53 | 198.33 | 23.31 | 3.67 | 23.32 |
July | 199.67 | 22.85 | 239.67 | 23.69 | 12.00 | 23.77 |
August | 208.17 | 23.00 | 251.33 | 23.71 | 16.33 | 23.82 |
September | 240.83 | 22.49 | 215.33 | 23.37 | 17.00 | 23.45 |
October | 403.33 | 21.38 | 136.50 | 21.54 | 74.83 | 21.37 |
November | 457.17 | 20.88 | 200.50 | 20.72 | 187.67 | 20.56 |
December | 485.67 | 20.46 | 336.50 | 20.28 | 336.50 | 20.20 |
Annual Sum or Average | 4245.00 | 21.45 | 2518.50 | 21.71 | 1367.50 | 21.48 |
Minimum of Months | 199.67 | 20.46 | 132.00 | 20.28 | 3.67 | 20.20 |
Maximum of Months | 500.83 | 23.00 | 336.50 | 23.71 | 336.50 | 23.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.39 | 337.83 | 20.24 | 337.83 | 20.17 |
February | 446.67 | 20.62 | 250.83 | 20.40 | 250.83 | 20.30 |
March | 509.17 | 20.83 | 223.83 | 20.67 | 223.83 | 20.58 |
April | 381.33 | 21.91 | 108.17 | 22.03 | 54.00 | 21.90 |
May | 367.33 | 22.07 | 121.17 | 22.47 | 25.67 | 22.42 |
June | 244.00 | 22.61 | 199.50 | 23.35 | 8.83 | 23.40 |
July | 203.00 | 22.76 | 238.17 | 23.60 | 13.33 | 23.70 |
August | 248.50 | 22.80 | 196.33 | 23.43 | 12.33 | 23.53 |
September | 324.83 | 22.13 | 116.33 | 22.65 | 10.00 | 22.65 |
October | 467.67 | 21.13 | 116.50 | 21.04 | 98.50 | 20.89 |
November | 488.83 | 20.58 | 240.17 | 20.38 | 240.17 | 20.28 |
December | 497.00 | 20.12 | 405.83 | 20.03 | 405.83 | 19.99 |
Annual Sum or Average | 4680.33 | 21.25 | 2554.67 | 21.36 | 1681.17 | 21.15 |
Minimum of Months | 203.00 | 20.12 | 108.17 | 20.03 | 8.83 | 19.99 |
Maximum of Months | 509.17 | 22.80 | 405.83 | 23.60 | 405.83 | 23.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.56 | 316.33 | 20.44 | 316.33 | 20.38 |
February | 454.00 | 20.67 | 242.00 | 20.54 | 242.00 | 20.48 |
March | 514.00 | 20.97 | 176.33 | 20.85 | 176.33 | 20.78 |
April | 480.00 | 22.19 | 18.17 | 22.12 | 18.17 | 22.06 |
May | 454.50 | 22.61 | 2.50 | 22.61 | 0.00 | 22.61 |
June | 262.00 | 23.20 | 77.17 | 23.40 | 0.00 | 23.40 |
July | 185.17 | 23.28 | 141.33 | 23.63 | 0.00 | 23.63 |
August | 251.00 | 23.25 | 78.50 | 23.43 | 0.00 | 23.43 |
September | 377.33 | 22.88 | 19.50 | 22.94 | 0.00 | 22.94 |
October | 502.00 | 21.75 | 17.00 | 21.70 | 17.00 | 21.66 |
November | 489.00 | 20.98 | 134.17 | 20.85 | 134.17 | 20.77 |
December | 497.00 | 20.51 | 342.00 | 20.42 | 342.00 | 20.38 |
Annual Sum or Average | 4968.00 | 21.67 | 1565.00 | 21.53 | 1246.00 | 21.33 |
Minimum of Months | 185.17 | 20.51 | 2.50 | 20.42 | 0.00 | 20.38 |
Maximum of Months | 514.00 | 23.28 | 342.00 | 23.63 | 342.00 | 23.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.68 | 284.00 | 20.56 | 284.00 | 20.50 |
February | 454.00 | 20.89 | 185.50 | 20.75 | 185.50 | 20.67 |
March | 514.00 | 21.05 | 146.83 | 20.93 | 146.83 | 20.85 |
April | 322.33 | 22.66 | 38.33 | 22.82 | 5.67 | 22.80 |
May | 273.17 | 22.82 | 107.00 | 23.29 | 0.00 | 23.29 |
June | 142.83 | 23.15 | 223.83 | 23.88 | 0.50 | 23.89 |
July | 87.50 | 23.67 | 312.33 | 24.30 | 9.83 | 24.36 |
August | 96.00 | 23.39 | 303.83 | 24.07 | 3.00 | 24.09 |
September | 174.33 | 23.04 | 199.33 | 23.77 | 0.00 | 23.77 |
October | 444.50 | 21.88 | 18.17 | 21.86 | 13.67 | 21.82 |
November | 489.00 | 21.07 | 104.67 | 20.95 | 104.67 | 20.86 |
December | 497.00 | 20.56 | 322.17 | 20.46 | 322.17 | 20.41 |
Annual Sum or Average | 3996.67 | 21.55 | 2246.00 | 21.89 | 1075.83 | 21.67 |
Minimum of Months | 87.50 | 20.56 | 18.17 | 20.46 | 0.00 | 20.41 |
Maximum of Months | 514.00 | 23.67 | 322.17 | 24.30 | 322.17 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 491.17 | 20.79 | 223.17 | 20.57 | 219.83 | 20.43 |
February | 436.50 | 21.04 | 122.00 | 20.84 | 118.67 | 20.68 |
March | 514.00 | 20.85 | 153.33 | 20.66 | 153.33 | 20.55 |
April | 361.67 | 22.12 | 68.67 | 22.32 | 22.67 | 22.26 |
May | 380.17 | 22.11 | 64.33 | 22.44 | 5.50 | 22.41 |
June | 285.83 | 22.49 | 135.67 | 23.08 | 0.00 | 23.08 |
July | 176.67 | 22.76 | 209.33 | 23.64 | 2.50 | 23.67 |
August | 145.17 | 22.91 | 271.17 | 23.83 | 7.17 | 23.88 |
September | 176.67 | 22.86 | 235.83 | 23.78 | 9.67 | 23.85 |
October | 399.33 | 21.78 | 70.83 | 22.02 | 17.33 | 21.96 |
November | 468.00 | 21.12 | 92.33 | 21.02 | 83.50 | 20.89 |
December | 496.17 | 20.56 | 290.67 | 20.36 | 290.67 | 20.28 |
Annual Sum or Average | 4331.33 | 21.50 | 1937.33 | 21.77 | 930.83 | 21.56 |
Minimum of Months | 145.17 | 20.56 | 64.33 | 20.36 | 0.00 | 20.28 |
Maximum of Months | 514.00 | 22.91 | 290.67 | 23.83 | 290.67 | 23.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.66 | 294.17 | 20.53 | 294.17 | 20.47 |
February | 453.17 | 20.94 | 182.50 | 20.77 | 182.50 | 20.68 |
March | 512.67 | 20.98 | 164.17 | 20.86 | 164.17 | 20.79 |
April | 392.00 | 22.30 | 44.33 | 22.40 | 14.33 | 22.36 |
May | 341.00 | 22.57 | 84.17 | 22.95 | 0.50 | 22.95 |
June | 180.33 | 23.16 | 211.67 | 23.77 | 3.17 | 23.80 |
July | 124.33 | 23.28 | 300.17 | 24.02 | 8.17 | 24.08 |
August | 140.33 | 23.26 | 246.00 | 23.89 | 5.17 | 23.93 |
September | 268.17 | 22.85 | 131.50 | 23.33 | 0.33 | 23.33 |
October | 467.50 | 21.74 | 25.67 | 21.73 | 16.17 | 21.68 |
November | 489.00 | 21.01 | 119.00 | 20.89 | 119.00 | 20.80 |
December | 497.00 | 20.52 | 347.00 | 20.43 | 347.00 | 20.39 |
Annual Sum or Average | 4367.50 | 21.56 | 2150.33 | 21.77 | 1154.67 | 21.58 |
Minimum of Months | 124.33 | 20.52 | 25.67 | 20.43 | 0.33 | 20.39 |
Maximum of Months | 512.67 | 23.28 | 347.00 | 24.02 | 347.00 | 24.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.64 | 278.50 | 20.48 | 278.50 | 20.40 |
February | 454.00 | 20.81 | 183.33 | 20.62 | 183.33 | 20.52 |
March | 514.00 | 21.25 | 109.50 | 21.10 | 109.50 | 20.99 |
April | 416.83 | 22.62 | 12.00 | 22.58 | 10.00 | 22.53 |
May | 379.17 | 22.89 | 28.17 | 22.97 | 0.00 | 22.97 |
June | 160.17 | 23.27 | 143.17 | 23.68 | 0.00 | 23.68 |
July | 126.83 | 23.32 | 212.50 | 23.85 | 0.00 | 23.85 |
August | 157.17 | 23.28 | 164.83 | 23.67 | 0.00 | 23.67 |
September | 304.17 | 22.90 | 52.83 | 23.06 | 0.00 | 23.06 |
October | 495.83 | 21.87 | 25.67 | 21.79 | 25.67 | 21.71 |
November | 489.00 | 20.98 | 135.33 | 20.82 | 135.33 | 20.71 |
December | 497.00 | 20.45 | 310.83 | 20.31 | 310.83 | 20.25 |
Annual Sum or Average | 4496.17 | 21.67 | 1656.67 | 21.65 | 1053.17 | 21.44 |
Minimum of Months | 126.83 | 20.45 | 12.00 | 20.31 | 0.00 | 20.25 |
Maximum of Months | 514.00 | 23.32 | 310.83 | 23.85 | 310.83 | 23.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.62 | 236.83 | 20.47 | 236.83 | 20.40 |
February | 385.00 | 20.87 | 154.00 | 20.71 | 154.00 | 20.62 |
March | 433.00 | 21.12 | 99.50 | 20.98 | 99.50 | 20.89 |
April | 274.00 | 22.52 | 54.17 | 22.78 | 10.00 | 22.78 |
May | 252.00 | 22.65 | 98.33 | 23.18 | 3.00 | 23.21 |
June | 160.67 | 23.17 | 182.33 | 23.84 | 8.50 | 23.91 |
July | 117.83 | 23.50 | 230.83 | 24.22 | 12.67 | 24.32 |
August | 145.67 | 23.36 | 213.17 | 23.95 | 11.00 | 24.04 |
September | 204.83 | 22.78 | 137.17 | 23.48 | 5.33 | 23.53 |
October | 388.17 | 21.62 | 33.17 | 21.60 | 23.83 | 21.52 |
November | 417.00 | 20.91 | 122.17 | 20.76 | 122.17 | 20.66 |
December | 422.00 | 20.39 | 282.50 | 20.27 | 282.50 | 20.21 |
Annual Sum or Average | 3627.17 | 21.54 | 1844.17 | 21.81 | 969.33 | 21.62 |
Minimum of Months | 117.83 | 20.39 | 33.17 | 20.27 | 3.00 | 20.21 |
Maximum of Months | 433.00 | 23.50 | 282.50 | 24.22 | 282.50 | 24.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 458.00 | 21.09 | 188.00 | 20.94 | 177.83 | 20.81 |
February | 393.33 | 21.29 | 130.00 | 21.25 | 104.00 | 21.10 |
March | 496.00 | 21.45 | 87.50 | 21.29 | 87.50 | 21.18 |
April | 283.67 | 22.53 | 106.17 | 22.99 | 12.17 | 23.00 |
May | 304.50 | 22.58 | 118.67 | 23.09 | 1.00 | 23.08 |
June | 193.83 | 22.98 | 216.67 | 23.66 | 1.50 | 23.67 |
July | 152.17 | 23.25 | 259.83 | 23.97 | 10.83 | 24.05 |
August | 151.50 | 23.47 | 278.33 | 24.00 | 17.17 | 24.11 |
September | 208.00 | 23.08 | 231.33 | 23.79 | 16.17 | 23.91 |
October | 388.33 | 21.93 | 91.00 | 22.24 | 19.33 | 22.20 |
November | 444.50 | 21.29 | 104.67 | 21.27 | 85.83 | 21.14 |
December | 479.83 | 20.84 | 246.33 | 20.63 | 246.17 | 20.53 |
Annual Sum or Average | 3953.67 | 21.82 | 2058.50 | 22.20 | 779.50 | 22.04 |
Minimum of Months | 151.50 | 20.84 | 87.50 | 20.63 | 1.00 | 20.53 |
Maximum of Months | 496.00 | 23.47 | 278.33 | 24.00 | 246.17 | 24.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.17 | 20.71 | 254.50 | 20.54 | 254.50 | 20.45 |
February | 440.33 | 20.95 | 152.00 | 20.75 | 152.00 | 20.64 |
March | 506.83 | 21.14 | 113.33 | 21.00 | 113.33 | 20.91 |
April | 369.33 | 22.38 | 69.67 | 22.60 | 14.83 | 22.58 |
May | 343.17 | 22.57 | 108.00 | 22.99 | 6.00 | 23.03 |
June | 201.83 | 23.06 | 217.50 | 23.69 | 7.17 | 23.75 |
July | 156.17 | 23.17 | 274.83 | 23.91 | 12.83 | 24.00 |
August | 181.33 | 23.19 | 236.33 | 23.79 | 12.33 | 23.87 |
September | 286.83 | 22.63 | 131.83 | 23.17 | 4.67 | 23.21 |
October | 460.67 | 21.61 | 48.50 | 21.63 | 28.33 | 21.55 |
November | 486.50 | 20.95 | 131.00 | 20.80 | 131.00 | 20.70 |
December | 497.00 | 20.46 | 321.33 | 20.33 | 321.33 | 20.28 |
Annual Sum or Average | 4431.17 | 21.58 | 2058.83 | 21.80 | 1058.33 | 21.62 |
Minimum of Months | 156.17 | 20.46 | 48.50 | 20.33 | 4.67 | 20.28 |
Maximum of Months | 506.83 | 23.19 | 321.33 | 23.91 | 321.33 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.28959 | 33.18843 | 0.05677 | 5.98977 |
February | 454.00000 | 23.66120 | 31.65901 | 0.15366 | 5.74386 |
March | 514.00000 | 23.74618 | 30.83387 | 0.17725 | 5.87488 |
April | 485.00000 | 24.24277 | 29.25502 | 0.33406 | 7.53689 |
May | 508.00000 | 24.32653 | 34.69333 | -0.4693 | 9.98644 |
June | 496.00000 | 24.35081 | 41.71309 | -0.3784 | 8.37947 |
July | 497.00000 | 24.40826 | 43.22347 | -0.3462 | 7.91835 |
August | 514.00000 | 24.31542 | 43.11495 | -0.3650 | 8.10725 |
September | 485.00000 | 24.33382 | 41.10254 | -0.3957 | 8.64418 |
October | 502.00000 | 24.14189 | 36.43023 | 0.33977 | 7.62234 |
November | 489.00000 | 23.83378 | 34.63296 | 0.22248 | 6.33676 |
December | 497.00000 | 23.37988 | 30.87076 | 0.06577 | 5.51770 |
Annual Sum or Average | 5943.00000 | 24.00427 | 35.92952 | -0.0529 | 7.31640 |
Minimum of Months | 454.00000 | 23.28959 | 29.25502 | -0.4693 | 5.51770 |
Maximum of Months | 514.00000 | 24.40826 | 43.22347 | 0.33977 | 9.98644 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.82852 | 36.08990 | -0.2720 | 7.57230 |
February | 454.00000 | 22.15264 | 34.99680 | -0.1879 | 6.35072 |
March | 514.00000 | 22.42963 | 34.25728 | -0.1208 | 5.86401 |
April | 485.00000 | 23.66379 | 31.29402 | 0.19063 | 6.21520 |
May | 508.00000 | 23.80729 | 36.58197 | -0.6580 | 14.76156 |
June | 496.00000 | 24.04525 | 43.13063 | -0.5029 | 10.63603 |
July | 497.00000 | 24.09697 | 44.47115 | -0.4709 | 10.03715 |
August | 514.00000 | 24.08144 | 44.31647 | -0.4711 | 9.89740 |
September | 485.00000 | 23.90618 | 42.63772 | -0.5632 | 12.09970 |
October | 502.00000 | 23.14739 | 39.78682 | 0.10224 | 5.85992 |
November | 489.00000 | 22.36552 | 38.50898 | -0.1139 | 6.00561 |
December | 497.00000 | 21.64954 | 34.17180 | -0.3259 | 7.94539 |
Annual Sum or Average | 5943.00000 | 23.10393 | 38.38387 | -0.2845 | 8.62506 |
Minimum of Months | 454.00000 | 21.64954 | 31.29402 | -0.6580 | 5.85992 |
Maximum of Months | 514.00000 | 24.09697 | 44.47115 | 0.19063 | 14.76156 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.08451 | 35.84588 | -0.4747 | 11.25998 |
February | 454.00000 | 21.31492 | 36.56606 | -0.4015 | 9.51292 |
March | 514.00000 | 21.66747 | 35.58622 | -0.3120 | 7.90549 |
April | 485.00000 | 23.13939 | 32.26040 | 0.06437 | 6.13934 |
May | 508.00000 | 23.38246 | 37.57381 | -0.8050 | 20.11223 |
June | 496.00000 | 23.81659 | 43.79799 | -0.5824 | 12.85571 |
July | 497.00000 | 23.88393 | 45.05752 | -0.5431 | 11.95422 |
August | 514.00000 | 23.86776 | 44.86393 | -0.5491 | 11.82819 |
September | 485.00000 | 23.50812 | 43.93748 | -0.7056 | 16.56626 |
October | 502.00000 | 22.29763 | 41.75664 | -0.1056 | 6.35003 |
November | 489.00000 | 21.46748 | 40.35634 | -0.3408 | 8.49246 |
December | 497.00000 | 20.89540 | 35.39197 | -0.5319 | 12.19178 |
Annual Sum or Average | 5943.00000 | 22.53545 | 39.44031 | -0.4418 | 11.28407 |
Minimum of Months | 454.00000 | 20.89540 | 32.26040 | -0.8050 | 6.13934 |
Maximum of Months | 514.00000 | 23.88393 | 45.05752 | 0.06437 | 20.11223 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.29733 | 38.15795 | -0.7084 | 17.49943 |
February | 454.00000 | 20.40270 | 38.67188 | -0.6575 | 15.73173 |
March | 514.00000 | 20.85862 | 37.99815 | -0.5281 | 11.90113 |
April | 485.00000 | 22.34609 | 34.41005 | -0.1248 | 7.48655 |
May | 508.00000 | 22.69577 | 39.51398 | -1.0285 | 29.83441 |
June | 496.00000 | 23.51912 | 44.92038 | -0.6735 | 16.33709 |
July | 497.00000 | 23.65350 | 45.84742 | -0.6102 | 14.47674 |
August | 514.00000 | 23.52703 | 46.28466 | -0.6638 | 15.82324 |
September | 485.00000 | 22.84624 | 45.79602 | -0.9368 | 26.02037 |
October | 502.00000 | 21.28603 | 45.16444 | -0.3537 | 9.13377 |
November | 489.00000 | 20.52092 | 42.63534 | -0.5993 | 14.02874 |
December | 497.00000 | 20.09681 | 37.11035 | -0.7746 | 19.75470 |
Annual Sum or Average | 5943.00000 | 21.84818 | 41.39971 | -0.6389 | 16.51446 |
Minimum of Months | 454.00000 | 20.09681 | 34.41005 | -1.0285 | 7.48655 |
Maximum of Months | 514.00000 | 23.65350 | 46.28466 | -0.1248 | 29.83441 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.38067 | 37.35544 | -0.6778 | 16.38626 |
February | 454.00000 | 20.58188 | 37.71994 | -0.6015 | 14.06446 |
March | 514.00000 | 20.88896 | 37.25879 | -0.5079 | 11.43864 |
April | 485.00000 | 22.86975 | 32.47423 | 0.05364 | 7.97073 |
May | 508.00000 | 23.07022 | 37.95909 | -0.8268 | 23.52963 |
June | 496.00000 | 23.60775 | 44.11935 | -0.5590 | 14.71312 |
July | 497.00000 | 23.89419 | 44.81336 | -0.4431 | 12.14922 |
August | 514.00000 | 23.72237 | 45.04131 | -0.4996 | 13.07672 |
September | 485.00000 | 23.28021 | 43.81124 | -0.7071 | 19.66264 |
October | 502.00000 | 21.51248 | 44.04702 | -0.2797 | 8.87739 |
November | 489.00000 | 20.58527 | 41.95897 | -0.5753 | 13.25194 |
December | 497.00000 | 20.15132 | 36.48385 | -0.7564 | 19.00146 |
Annual Sum or Average | 5943.00000 | 22.05509 | 40.27910 | -0.5323 | 14.51852 |
Minimum of Months | 454.00000 | 20.15132 | 32.47423 | -0.8268 | 7.97073 |
Maximum of Months | 514.00000 | 23.89419 | 45.04131 | 0.05364 | 23.52963 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.97362 | 35.61186 | -0.5134 | 13.94491 |
February | 454.00000 | 21.25818 | 35.79721 | -0.4176 | 12.33730 |
March | 514.00000 | 21.14443 | 36.25289 | -0.4425 | 10.89150 |
April | 485.00000 | 22.83131 | 32.02951 | 0.05077 | 8.75192 |
May | 508.00000 | 22.83005 | 38.14017 | -0.9189 | 27.75200 |
June | 496.00000 | 23.38210 | 44.48996 | -0.6577 | 17.69668 |
July | 497.00000 | 23.64089 | 45.26673 | -0.5417 | 15.03514 |
August | 514.00000 | 23.63168 | 45.00686 | -0.5209 | 14.61651 |
September | 485.00000 | 23.34416 | 43.14315 | -0.6423 | 19.77826 |
October | 502.00000 | 21.92824 | 42.32263 | -0.1577 | 9.09605 |
November | 489.00000 | 21.11432 | 40.31799 | -0.4323 | 11.84722 |
December | 497.00000 | 20.54325 | 35.20946 | -0.6463 | 16.52010 |
Annual Sum or Average | 5943.00000 | 22.22406 | 39.50121 | -0.4886 | 14.88604 |
Minimum of Months | 454.00000 | 20.54325 | 32.02951 | -0.9189 | 8.75192 |
Maximum of Months | 514.00000 | 23.64089 | 45.26673 | 0.05077 | 27.75200 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.39232 | 37.07761 | -0.6792 | 16.73220 |
February | 454.00000 | 20.67620 | 37.26356 | -0.5795 | 14.51725 |
March | 514.00000 | 20.85681 | 37.05363 | -0.5178 | 11.92230 |
April | 485.00000 | 22.37417 | 33.34196 | -0.0676 | 8.40139 |
May | 508.00000 | 22.64289 | 38.84309 | -0.9656 | 29.89414 |
June | 496.00000 | 23.35141 | 44.84821 | -0.6341 | 17.71783 |
July | 497.00000 | 23.54756 | 45.83838 | -0.5469 | 15.63462 |
August | 514.00000 | 23.41820 | 46.09270 | -0.6074 | 16.57444 |
September | 485.00000 | 22.78045 | 45.18546 | -0.8785 | 26.12430 |
October | 502.00000 | 21.32967 | 44.19309 | -0.3237 | 9.26387 |
November | 489.00000 | 20.58556 | 41.70018 | -0.5789 | 13.67209 |
December | 497.00000 | 20.12114 | 36.31857 | -0.7709 | 19.56924 |
Annual Sum or Average | 5943.00000 | 21.84811 | 40.67625 | -0.5968 | 16.69012 |
Minimum of Months | 454.00000 | 20.12114 | 33.34196 | -0.9656 | 8.40139 |
Maximum of Months | 514.00000 | 23.54756 | 46.09270 | -0.0676 | 29.89414 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.55615 | 37.79607 | -0.6314 | 14.52234 |
February | 454.00000 | 20.66533 | 38.33886 | -0.5805 | 12.64984 |
March | 514.00000 | 20.96736 | 37.58016 | -0.4947 | 10.56844 |
April | 485.00000 | 22.20576 | 34.78686 | -0.1644 | 6.62479 |
May | 508.00000 | 22.74703 | 39.70925 | -1.0312 | 28.85099 |
June | 496.00000 | 23.58479 | 45.25540 | -0.6787 | 15.52703 |
July | 497.00000 | 23.76324 | 46.04116 | -0.5981 | 13.17211 |
August | 514.00000 | 23.60952 | 46.58749 | -0.6557 | 14.68643 |
September | 485.00000 | 23.12516 | 45.53327 | -0.8528 | 21.50734 |
October | 502.00000 | 21.75316 | 43.75804 | -0.2284 | 6.85994 |
November | 489.00000 | 20.97876 | 41.58154 | -0.4601 | 10.03207 |
December | 497.00000 | 20.51248 | 36.53149 | -0.6439 | 14.41265 |
Annual Sum or Average | 5943.00000 | 22.04889 | 41.14999 | -0.5860 | 14.14690 |
Minimum of Months | 454.00000 | 20.51248 | 34.78686 | -1.0312 | 6.62479 |
Maximum of Months | 514.00000 | 23.76324 | 46.58749 | -0.1644 | 28.85099 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.68041 | 37.53027 | -0.5891 | 13.26455 |
February | 454.00000 | 20.89243 | 37.85645 | -0.5113 | 11.10622 |
March | 514.00000 | 21.05420 | 37.33075 | -0.4621 | 10.00920 |
April | 485.00000 | 23.16969 | 32.31002 | 0.10701 | 7.00353 |
May | 508.00000 | 23.48154 | 37.42669 | -0.7202 | 18.44591 |
June | 496.00000 | 23.88498 | 43.74122 | -0.5001 | 11.86747 |
July | 497.00000 | 24.16830 | 44.39032 | -0.3809 | 9.60739 |
August | 514.00000 | 24.02770 | 44.55892 | -0.4207 | 9.95740 |
September | 485.00000 | 23.81309 | 42.75966 | -0.5429 | 13.08214 |
October | 502.00000 | 22.13373 | 42.74031 | -0.1196 | 6.82872 |
November | 489.00000 | 21.06541 | 41.41676 | -0.4283 | 9.44077 |
December | 497.00000 | 20.56357 | 36.41343 | -0.6250 | 13.89047 |
Annual Sum or Average | 5943.00000 | 22.42048 | 39.89625 | -0.4335 | 11.22080 |
Minimum of Months | 454.00000 | 20.56357 | 32.31002 | -0.7202 | 6.82872 |
Maximum of Months | 514.00000 | 24.16830 | 44.55892 | 0.10701 | 18.44591 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.87445 | 34.52928 | -0.4945 | 12.37007 |
February | 454.00000 | 21.17541 | 34.94225 | -0.3929 | 10.16570 |
March | 514.00000 | 20.84573 | 35.13918 | -0.4844 | 10.73411 |
April | 485.00000 | 22.65987 | 31.75797 | 0.01582 | 7.54466 |
May | 508.00000 | 22.66854 | 38.09046 | -0.9660 | 28.20828 |
June | 496.00000 | 23.19025 | 44.99434 | -0.7284 | 18.75693 |
July | 497.00000 | 23.66641 | 45.50536 | -0.5476 | 13.60469 |
August | 514.00000 | 23.78956 | 44.98469 | -0.4762 | 12.02754 |
September | 485.00000 | 23.73827 | 42.15956 | -0.5042 | 13.65096 |
October | 502.00000 | 22.28261 | 40.54844 | -0.0421 | 7.56602 |
November | 489.00000 | 21.28520 | 38.73541 | -0.3407 | 9.10901 |
December | 497.00000 | 20.56337 | 34.00229 | -0.5894 | 13.60940 |
Annual Sum or Average | 5943.00000 | 22.23334 | 38.82055 | -0.4648 | 13.16094 |
Minimum of Months | 454.00000 | 20.56337 | 31.75797 | -0.9660 | 7.54466 |
Maximum of Months | 514.00000 | 23.78956 | 45.50536 | 0.01582 | 28.20828 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.65967 | 37.18969 | -0.5972 | 13.64111 |
February | 454.00000 | 20.94574 | 37.36166 | -0.4961 | 11.17309 |
March | 514.00000 | 20.98904 | 37.05586 | -0.4780 | 10.37889 |
April | 485.00000 | 22.66012 | 33.18859 | -0.0187 | 6.97261 |
May | 508.00000 | 23.12517 | 38.12621 | -0.8376 | 23.09062 |
June | 496.00000 | 23.78690 | 44.03961 | -0.5263 | 12.63748 |
July | 497.00000 | 23.95533 | 45.00598 | -0.4431 | 10.99450 |
August | 514.00000 | 23.86404 | 45.25697 | -0.4885 | 11.39287 |
September | 485.00000 | 23.42797 | 43.95180 | -0.6846 | 17.08117 |
October | 502.00000 | 21.89673 | 42.97092 | -0.1735 | 6.96803 |
November | 489.00000 | 21.00891 | 41.15523 | -0.4432 | 9.80977 |
December | 497.00000 | 20.51794 | 36.15218 | -0.6443 | 14.43410 |
Annual Sum or Average | 5943.00000 | 22.24505 | 40.14756 | -0.4869 | 12.40255 |
Minimum of Months | 454.00000 | 20.51794 | 33.18859 | -0.8376 | 6.96803 |
Maximum of Months | 514.00000 | 23.95533 | 45.25697 | -0.0187 | 23.09062 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.64061 | 37.57972 | -0.5898 | 13.69923 |
February | 454.00000 | 20.80606 | 37.99677 | -0.5245 | 11.61098 |
March | 514.00000 | 21.24761 | 37.33524 | -0.4052 | 9.20009 |
April | 485.00000 | 22.81983 | 33.60217 | -0.0059 | 6.33706 |
May | 508.00000 | 23.17476 | 38.50180 | -0.8656 | 22.44957 |
June | 496.00000 | 23.79383 | 44.13736 | -0.5805 | 12.87663 |
July | 497.00000 | 23.89267 | 45.18200 | -0.5298 | 11.60368 |
August | 514.00000 | 23.78304 | 45.57560 | -0.5741 | 12.53903 |
September | 485.00000 | 23.30527 | 44.56502 | -0.7775 | 19.15244 |
October | 502.00000 | 21.89580 | 43.73121 | -0.1897 | 6.91897 |
November | 489.00000 | 20.98029 | 41.70942 | -0.4542 | 10.23366 |
December | 497.00000 | 20.45411 | 36.43335 | -0.6482 | 14.92338 |
Annual Sum or Average | 5943.00000 | 22.24296 | 40.55286 | -0.5129 | 12.64301 |
Minimum of Months | 454.00000 | 20.45411 | 33.60217 | -0.8656 | 6.33706 |
Maximum of Months | 514.00000 | 23.89267 | 45.57560 | -0.0059 | 22.44957 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.61641 | 36.22141 | -0.5929 | 13.58436 |
February | 385.00000 | 20.87425 | 36.32651 | -0.5046 | 11.15477 |
March | 433.00000 | 21.12208 | 36.20688 | -0.4285 | 9.55525 |
April | 410.00000 | 23.06691 | 31.82729 | 0.10032 | 7.37583 |
May | 430.00000 | 23.31029 | 36.95393 | -0.7511 | 20.29298 |
June | 418.00000 | 23.77526 | 43.31393 | -0.5154 | 13.06095 |
July | 422.00000 | 24.06505 | 44.12202 | -0.4030 | 10.94587 |
August | 433.00000 | 23.86328 | 44.49989 | -0.4670 | 11.79736 |
September | 410.00000 | 23.51243 | 42.92628 | -0.6332 | 16.71230 |
October | 427.00000 | 21.85162 | 42.45482 | -0.1833 | 7.35610 |
November | 417.00000 | 20.90754 | 40.53007 | -0.4683 | 10.36188 |
December | 422.00000 | 20.39404 | 35.28588 | -0.6626 | 15.23657 |
Annual Sum or Average | 5034.00000 | 22.28611 | 39.24951 | -0.4599 | 12.29903 |
Minimum of Months | 385.00000 | 20.39404 | 31.82729 | -0.7511 | 7.35610 |
Maximum of Months | 433.00000 | 24.06505 | 44.49989 | 0.10032 | 20.29298 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.36644 | 34.96500 | -0.3873 | 10.99917 |
February | 454.00000 | 21.68667 | 35.07181 | -0.2826 | 9.62866 |
March | 514.00000 | 21.54014 | 35.59906 | -0.3197 | 8.62987 |
April | 485.00000 | 23.21451 | 31.34932 | 0.14982 | 8.01198 |
May | 508.00000 | 23.24745 | 37.25355 | -0.7746 | 21.25870 |
June | 496.00000 | 23.68574 | 43.71123 | -0.5587 | 13.73290 |
July | 497.00000 | 23.90284 | 44.58423 | -0.4574 | 11.78002 |
August | 514.00000 | 23.89719 | 44.36996 | -0.4319 | 11.34324 |
September | 485.00000 | 23.70413 | 42.20654 | -0.5133 | 14.61154 |
October | 502.00000 | 22.43031 | 41.10731 | -0.0168 | 7.76543 |
November | 489.00000 | 21.58544 | 39.41136 | -0.2868 | 9.15508 |
December | 497.00000 | 20.95668 | 34.45861 | -0.5100 | 12.52631 |
Annual Sum or Average | 5943.00000 | 22.60648 | 38.70967 | -0.3677 | 11.64359 |
Minimum of Months | 454.00000 | 20.95668 | 31.34932 | -0.7746 | 7.76543 |
Maximum of Months | 514.00000 | 23.90284 | 44.58423 | 0.14982 | 21.25870 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.71026 | 36.59009 | -0.5659 | 13.17495 |
February | 454.00000 | 21.03967 | 36.67882 | -0.4552 | 10.96953 |
March | 514.00000 | 21.17780 | 36.53268 | -0.4081 | 9.43645 |
April | 485.00000 | 22.79526 | 32.65656 | 0.04015 | 7.34563 |
May | 508.00000 | 23.08010 | 37.93432 | -0.8151 | 22.95626 |
June | 496.00000 | 23.67447 | 44.04489 | -0.5292 | 13.58072 |
July | 497.00000 | 23.83339 | 45.11765 | -0.4553 | 12.14328 |
August | 514.00000 | 23.72873 | 45.37186 | -0.5045 | 12.69593 |
September | 485.00000 | 23.23491 | 44.06675 | -0.7219 | 19.37201 |
October | 502.00000 | 21.81027 | 43.07450 | -0.1844 | 7.32755 |
November | 489.00000 | 20.96432 | 40.99585 | -0.4492 | 10.25436 |
December | 497.00000 | 20.45905 | 35.68855 | -0.6487 | 14.90249 |
Annual Sum or Average | 5943.00000 | 22.21707 | 39.92564 | -0.4758 | 12.86564 |
Minimum of Months | 454.00000 | 20.45905 | 32.65656 | -0.8151 | 7.32755 |
Maximum of Months | 514.00000 | 23.83339 | 45.37186 | 0.04015 | 22.95626 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.169697E+10 | 0.445594E+09 | 49.67 | 0.160972E+10 | 87247262.77 | 0.00 | 1.00 | 30-APR-14:11 | 0.00 | 01-APR-00:10 | 34587.31 | 30-APR-15:31 | 34587.31 | 30-APR-15:31 | 5668.79 | 28-APR-08:00 | 7936.83 | 30-APR-15:31 | 0.00 |
May | 0.272817E+10 | 0.683132E+09 | 60.39 | 0.230597E+10 | 0.422197E+09 | 0.00 | 1.00 | 22-MAY-13:00 | 0.00 | 01-MAY-00:10 | 42887.00 | 22-MAY-15:10 | 42887.00 | 22-MAY-15:10 | 5789.93 | 23-MAY-15:20 | 9799.77 | 22-MAY-15:10 | 0.00 |
June | 0.929234E+10 | 0.226916E+10 | 150.61 | 0.768278E+10 | 0.160956E+10 | 0.00 | 1.00 | 12-JUN-12:10 | 0.00 | 01-JUN-00:10 | 63095.73 | 13-JUN-16:00 | 57836.77 | 13-JUN-16:00 | 16588.92 | 26-JUN-16:00 | 15370.54 | 13-JUN-16:00 | 0.00 |
July | 0.157367E+11 | 0.391831E+10 | 272.21 | 0.127469E+11 | 0.298979E+10 | 0.00 | 1.00 | 06-JUL-15:10 | 0.00 | 01-JUL-00:10 | 59321.42 | 21-JUL-16:00 | 59321.42 | 21-JUL-16:00 | 12606.42 | 24-JUL-15:40 | 15021.46 | 21-JUL-16:00 | 0.00 |
August | 0.204444E+11 | 0.507459E+10 | 355.64 | 0.160795E+11 | 0.436489E+10 | 0.00 | 1.00 | 14-AUG-09:20 | 0.00 | 01-AUG-00:10 | 56917.10 | 14-AUG-15:50 | 56164.23 | 14-AUG-16:00 | 12257.86 | 08-AUG-13:00 | 13685.73 | 14-AUG-16:00 | 0.00 |
September | 0.102777E+11 | 0.253867E+10 | 195.65 | 0.844142E+10 | 0.183630E+10 | 0.00 | 1.00 | 10-SEP-13:22 | 0.00 | 01-SEP-00:10 | 49804.86 | 13-SEP-15:30 | 45382.49 | 13-SEP-15:30 | 11991.72 | 12-SEP-14:00 | 11362.06 | 13-SEP-15:30 | 0.00 |
October | 0.360563E+09 | 0.101199E+09 | 22.17 | 0.343436E+09 | 17126627.86 | 0.00 | 0.38 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 9720.54 | 07-OCT-15:00 | 9720.54 | 07-OCT-15:00 | 1640.60 | 17-OCT-15:00 | 2627.89 | 07-OCT-15:00 | 0.00 |
November | 3685265.88 | 1070842.64 | 0.67 | 2540364.76 | 1144901.12 | 0.00 | 0.12 | 24-NOV-12:00 | 0.00 | 01-NOV-00:10 | 2760.89 | 24-NOV-12:00 | 1943.04 | 24-NOV-12:00 | 817.85 | 24-NOV-12:00 | 796.14 | 24-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.605405E+11 | 0.150317E+11 | 1107.00 | 0.492123E+11 | 0.113282E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.204444E+11 | 0.507459E+10 | 355.64 | 0.160795E+11 | 0.436489E+10 | 0.00 | 1.00 | 0.00 | 63095.73 | 59321.42 | 16588.92 | 15370.54 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.176791E+10 | 0.455971E+09 | 50.58 | 0.170294E+10 | 64968693.45 | 0.00 | 1.00 | 28-APR-15:00 | 0.00 | 01-APR-00:10 | 37010.43 | 30-APR-16:02 | 37010.43 | 30-APR-16:02 | 3826.16 | 28-APR-08:00 | 8489.84 | 30-APR-16:02 | 0.00 |
May | 0.261810E+10 | 0.651327E+09 | 61.94 | 0.223363E+10 | 0.384475E+09 | 0.00 | 1.00 | 22-MAY-12:50 | 0.00 | 01-MAY-00:10 | 42108.83 | 22-MAY-15:00 | 42108.83 | 22-MAY-15:00 | 5533.31 | 23-MAY-15:20 | 9656.48 | 22-MAY-15:00 | 0.00 |
June | 0.877174E+10 | 0.213640E+10 | 152.51 | 0.727314E+10 | 0.149860E+10 | 0.00 | 1.00 | 12-JUN-12:10 | 0.00 | 01-JUN-00:10 | 60103.99 | 13-JUN-15:40 | 54755.17 | 13-JUN-15:40 | 18703.31 | 25-JUN-18:02 | 14599.78 | 13-JUN-16:00 | 0.00 |
July | 0.146163E+11 | 0.362870E+10 | 274.12 | 0.118718E+11 | 0.274444E+10 | 0.00 | 1.00 | 06-JUL-14:00 | 0.00 | 01-JUL-00:10 | 54806.81 | 21-JUL-15:40 | 54806.81 | 21-JUL-15:40 | 12093.39 | 24-JUL-15:30 | 13862.74 | 21-JUL-16:00 | 0.00 |
August | 0.184819E+11 | 0.457847E+10 | 358.54 | 0.145619E+11 | 0.392002E+10 | 0.00 | 1.00 | 10-AUG-14:30 | 0.00 | 01-AUG-00:10 | 53538.66 | 14-AUG-15:30 | 51986.58 | 14-AUG-15:50 | 11601.71 | 18-AUG-15:30 | 12765.09 | 14-AUG-15:50 | 0.00 |
September | 0.935693E+10 | 0.230720E+10 | 197.00 | 0.768226E+10 | 0.167468E+10 | 0.00 | 1.00 | 10-SEP-11:32 | 0.00 | 01-SEP-00:10 | 45811.57 | 13-SEP-14:50 | 41660.34 | 13-SEP-14:50 | 11766.36 | 12-SEP-14:00 | 10450.29 | 13-SEP-14:50 | 0.00 |
October | 0.325315E+09 | 91003591.71 | 22.17 | 0.311267E+09 | 14047203.15 | 0.00 | 0.46 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 10756.74 | 07-OCT-15:00 | 10756.74 | 07-OCT-15:00 | 1230.91 | 17-OCT-15:00 | 2849.04 | 07-OCT-15:00 | 0.00 |
November | 3215995.54 | 934964.43 | 0.67 | 2204570.42 | 1011425.12 | 0.00 | 0.11 | 24-NOV-12:00 | 0.00 | 01-NOV-00:10 | 2401.74 | 24-NOV-12:00 | 1679.53 | 24-NOV-12:00 | 722.21 | 24-NOV-12:00 | 693.08 | 24-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.559414E+11 | 0.138500E+11 | 1117.54 | 0.456391E+11 | 0.103022E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.184819E+11 | 0.457847E+10 | 358.54 | 0.145619E+11 | 0.392002E+10 | 0.00 | 1.00 | 0.00 | 60103.99 | 54806.81 | 18703.31 | 14599.78 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.178458E+10 | 0.463586E+09 | 49.86 | 0.170897E+10 | 75611181.17 | 0.00 | 1.00 | 30-APR-13:02 | 0.00 | 01-APR-00:10 | 38238.98 | 30-APR-16:22 | 38238.98 | 30-APR-16:22 | 2801.62 | 28-APR-08:00 | 8772.92 | 30-APR-16:22 | 0.00 |
May | 0.270300E+10 | 0.676396E+09 | 60.92 | 0.228872E+10 | 0.414281E+09 | 0.00 | 1.00 | 22-MAY-13:00 | 0.00 | 01-MAY-00:10 | 45657.02 | 22-MAY-15:00 | 45657.02 | 22-MAY-15:00 | 5938.16 | 23-MAY-14:50 | 10470.67 | 22-MAY-15:00 | 0.00 |
June | 0.910533E+10 | 0.222737E+10 | 149.94 | 0.752183E+10 | 0.158350E+10 | 0.00 | 1.00 | 12-JUN-12:10 | 0.00 | 01-JUN-00:10 | 69283.85 | 13-JUN-14:40 | 63036.19 | 13-JUN-15:40 | 19404.60 | 25-JUN-17:42 | 16606.27 | 13-JUN-15:40 | 0.00 |
July | 0.150370E+11 | 0.375880E+10 | 270.97 | 0.121932E+11 | 0.284373E+10 | 0.00 | 1.00 | 06-JUL-14:40 | 0.00 | 01-JUL-00:10 | 63122.38 | 21-JUL-15:50 | 63122.38 | 21-JUL-15:50 | 12312.60 | 24-JUL-15:30 | 15903.14 | 21-JUL-15:50 | 0.00 |
August | 0.183243E+11 | 0.458625E+10 | 356.64 | 0.142952E+11 | 0.402910E+10 | 0.00 | 1.00 | 13-AUG-15:52 | 0.00 | 01-AUG-00:10 | 58719.79 | 14-AUG-15:40 | 58719.79 | 14-AUG-15:40 | 11806.88 | 18-AUG-15:30 | 14074.87 | 14-AUG-16:00 | 0.00 |
September | 0.894594E+10 | 0.222988E+10 | 190.67 | 0.727486E+10 | 0.167108E+10 | 0.00 | 1.00 | 10-SEP-12:02 | 0.00 | 01-SEP-00:10 | 46175.71 | 13-SEP-15:00 | 42283.58 | 13-SEP-15:00 | 11334.12 | 12-SEP-14:00 | 10535.87 | 13-SEP-15:00 | 0.00 |
October | 0.297295E+09 | 83841801.05 | 21.67 | 0.280211E+09 | 17083476.97 | 0.00 | 0.41 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 10547.40 | 07-OCT-15:00 | 10547.40 | 07-OCT-15:00 | 1284.16 | 17-OCT-15:00 | 2827.58 | 07-OCT-15:00 | 0.00 |
November | 3316737.71 | 965350.73 | 0.67 | 2247985.04 | 1068752.67 | 0.00 | 0.11 | 24-NOV-12:00 | 0.00 | 01-NOV-00:10 | 2493.24 | 24-NOV-12:00 | 1722.23 | 24-NOV-12:00 | 771.01 | 24-NOV-12:00 | 720.62 | 24-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.562007E+11 | 0.140271E+11 | 1101.33 | 0.455653E+11 | 0.106355E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.183243E+11 | 0.458625E+10 | 356.64 | 0.142952E+11 | 0.402910E+10 | 0.00 | 1.00 | 0.00 | 69283.85 | 63122.38 | 19404.60 | 16606.27 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 277.08 | 0.00 | 277.08 | 22.82 | 1606.97 | 0.00 | 0.00 | 0.00 |
February | 432.67 | 0.00 | 432.67 | 68.33 | 1509.76 | 0.00 | 0.00 | 0.00 |
March | 598.74 | 0.00 | 598.74 | 204.60 | 1246.97 | 0.00 | 0.00 | 0.00 |
April | 974.84 | 4.36 | 970.48 | 596.75 | 1052.39 | 0.00 | 0.00 | 0.00 |
May | 1218.80 | 58.80 | 1160.00 | 753.01 | 850.36 | 0.00 | 0.00 | 0.00 |
June | 1347.31 | 84.48 | 1262.82 | 1072.80 | 681.81 | 0.00 | 0.00 | 0.00 |
July | 1277.99 | 72.87 | 1205.13 | 1092.55 | 630.00 | 0.00 | 0.00 | 0.00 |
August | 1004.57 | 15.74 | 988.83 | 839.26 | 704.12 | 0.00 | 0.00 | 0.00 |
September | 764.61 | 0.17 | 764.44 | 553.65 | 923.34 | 0.00 | 0.00 | 0.00 |
October | 489.96 | 0.00 | 489.96 | 206.39 | 1169.27 | 0.00 | 0.00 | 0.00 |
November | 294.39 | 0.00 | 294.39 | 35.30 | 1410.19 | 0.00 | 0.00 | 0.00 |
December | 200.48 | 0.00 | 200.48 | 2.85 | 1718.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 741.49 | 19.84 | 721.66 | 455.98 | 1123.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 200.48 | 0.00 | 200.48 | 2.85 | 630.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1347.31 | 84.48 | 1262.82 | 1092.55 | 1718.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 377.56 | 151.67 | 225.89 | 220.91 | 1006.35 | 0.00 | 0.00 | 0.00 |
February | 563.01 | 207.98 | 355.03 | 364.77 | 957.13 | 0.00 | 0.00 | 0.00 |
March | 588.36 | 115.94 | 472.41 | 359.07 | 790.05 | 0.00 | 0.00 | 0.00 |
April | 1579.79 | 742.35 | 837.44 | 1604.17 | 671.44 | 0.00 | 0.00 | 0.00 |
May | 1661.10 | 724.38 | 936.72 | 1638.60 | 582.36 | 0.00 | 0.00 | 0.00 |
June | 1644.18 | 656.67 | 987.51 | 1726.47 | 463.62 | 0.00 | 0.00 | 0.00 |
July | 1678.39 | 713.31 | 965.07 | 1842.18 | 429.95 | 0.00 | 0.00 | 0.00 |
August | 1589.90 | 759.64 | 830.26 | 1800.06 | 466.42 | 0.00 | 0.00 | 0.00 |
September | 1431.76 | 761.35 | 670.42 | 1570.20 | 587.01 | 0.00 | 0.00 | 0.00 |
October | 691.13 | 286.42 | 404.71 | 602.17 | 752.67 | 0.00 | 0.00 | 0.00 |
November | 360.31 | 122.80 | 237.51 | 208.88 | 896.98 | 0.00 | 0.00 | 0.00 |
December | 267.03 | 99.28 | 167.75 | 136.79 | 1091.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1037.54 | 445.72 | 591.82 | 1008.49 | 723.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 267.03 | 99.28 | 167.75 | 136.79 | 429.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1678.39 | 761.35 | 987.51 | 1842.18 | 1091.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1573.07 | 1018.31 | 554.76 | 1533.08 | 1457.54 | 0.00 | 0.00 | 0.00 |
February | 1921.21 | 1172.35 | 748.86 | 1916.46 | 1442.91 | 0.00 | 0.00 | 0.00 |
March | 1187.82 | 345.84 | 841.98 | 950.66 | 1210.05 | 0.00 | 0.00 | 0.00 |
April | 2466.61 | 1114.88 | 1351.73 | 2733.55 | 1098.00 | 0.00 | 0.00 | 0.00 |
May | 2040.11 | 664.19 | 1375.92 | 2081.02 | 956.92 | 0.00 | 0.00 | 0.00 |
June | 1879.38 | 454.92 | 1424.46 | 1992.41 | 750.52 | 0.00 | 0.00 | 0.00 |
July | 2036.27 | 637.68 | 1398.59 | 2331.94 | 698.92 | 0.00 | 0.00 | 0.00 |
August | 2386.06 | 1073.34 | 1312.72 | 2902.52 | 759.13 | 0.00 | 0.00 | 0.00 |
September | 2819.70 | 1651.83 | 1167.87 | 3404.83 | 949.30 | 0.00 | 0.00 | 0.00 |
October | 1937.25 | 1132.24 | 805.02 | 2097.21 | 1162.37 | 0.00 | 0.00 | 0.00 |
November | 1373.51 | 835.54 | 537.97 | 1345.10 | 1350.83 | 0.00 | 0.00 | 0.00 |
December | 1088.63 | 697.49 | 391.14 | 1032.48 | 1632.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1889.58 | 896.39 | 993.19 | 2023.93 | 1120.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1088.63 | 345.84 | 391.14 | 950.66 | 698.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2819.70 | 1651.83 | 1424.46 | 3404.83 | 1632.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 367.16 | 121.31 | 245.85 | 220.18 | 1024.71 | 0.00 | 0.00 | 0.00 |
February | 650.08 | 274.48 | 375.59 | 507.30 | 986.62 | 0.00 | 0.00 | 0.00 |
March | 587.81 | 112.45 | 475.36 | 357.55 | 802.12 | 0.00 | 0.00 | 0.00 |
April | 1386.95 | 550.91 | 836.04 | 1390.23 | 710.94 | 0.00 | 0.00 | 0.00 |
May | 1627.22 | 661.68 | 965.53 | 1614.72 | 615.31 | 0.00 | 0.00 | 0.00 |
June | 1757.22 | 723.38 | 1033.84 | 1882.30 | 493.02 | 0.00 | 0.00 | 0.00 |
July | 1789.65 | 789.06 | 1000.59 | 2005.87 | 460.06 | 0.00 | 0.00 | 0.00 |
August | 1503.19 | 650.84 | 852.35 | 1703.46 | 500.34 | 0.00 | 0.00 | 0.00 |
September | 1205.95 | 540.78 | 665.18 | 1317.18 | 623.92 | 0.00 | 0.00 | 0.00 |
October | 643.33 | 231.34 | 411.99 | 558.65 | 776.22 | 0.00 | 0.00 | 0.00 |
November | 348.15 | 101.63 | 246.52 | 211.37 | 924.10 | 0.00 | 0.00 | 0.00 |
December | 197.06 | 41.58 | 155.48 | 72.68 | 1132.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1006.38 | 400.12 | 606.26 | 988.39 | 752.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 197.06 | 41.58 | 155.48 | 72.68 | 460.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1789.65 | 789.06 | 1033.84 | 2005.87 | 1132.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.36 | 0.00 | 92.36 | 7.01 | 556.74 | 0.00 | 0.00 | 0.00 |
February | 144.22 | 0.00 | 144.22 | 21.69 | 524.37 | 0.00 | 0.00 | 0.00 |
March | 199.57 | 0.00 | 199.57 | 69.70 | 428.76 | 0.00 | 0.00 | 0.00 |
April | 324.93 | 1.45 | 323.48 | 209.37 | 353.92 | 0.00 | 0.00 | 0.00 |
May | 406.25 | 19.60 | 386.65 | 259.84 | 289.02 | 0.00 | 0.00 | 0.00 |
June | 449.08 | 28.16 | 420.92 | 366.93 | 230.96 | 0.00 | 0.00 | 0.00 |
July | 425.98 | 24.29 | 401.69 | 370.72 | 214.65 | 0.00 | 0.00 | 0.00 |
August | 334.84 | 5.25 | 329.59 | 285.78 | 239.76 | 0.00 | 0.00 | 0.00 |
September | 254.86 | 0.06 | 254.80 | 185.82 | 321.03 | 0.00 | 0.00 | 0.00 |
October | 163.31 | 0.00 | 163.31 | 65.85 | 417.96 | 0.00 | 0.00 | 0.00 |
November | 98.13 | 0.00 | 98.13 | 9.70 | 506.26 | 0.00 | 0.00 | 0.00 |
December | 66.82 | 0.00 | 66.82 | 0.27 | 609.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 247.15 | 6.61 | 240.54 | 155.06 | 390.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.82 | 0.00 | 66.82 | 0.27 | 214.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 449.08 | 28.16 | 420.92 | 370.72 | 609.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.36 | 0.00 | 92.36 | 7.01 | 556.78 | 0.00 | 0.00 | 0.00 |
February | 144.22 | 0.00 | 144.22 | 21.69 | 524.40 | 0.00 | 0.00 | 0.00 |
March | 199.58 | 0.00 | 199.58 | 69.70 | 428.79 | 0.00 | 0.00 | 0.00 |
April | 324.94 | 1.45 | 323.49 | 209.38 | 353.94 | 0.00 | 0.00 | 0.00 |
May | 406.26 | 19.60 | 386.66 | 259.85 | 289.04 | 0.00 | 0.00 | 0.00 |
June | 449.10 | 28.16 | 420.94 | 366.94 | 230.97 | 0.00 | 0.00 | 0.00 |
July | 425.99 | 24.29 | 401.71 | 370.73 | 214.67 | 0.00 | 0.00 | 0.00 |
August | 334.85 | 5.25 | 329.61 | 285.79 | 239.77 | 0.00 | 0.00 | 0.00 |
September | 254.87 | 0.06 | 254.81 | 185.83 | 321.05 | 0.00 | 0.00 | 0.00 |
October | 163.32 | 0.00 | 163.32 | 65.85 | 417.99 | 0.00 | 0.00 | 0.00 |
November | 98.13 | 0.00 | 98.13 | 9.70 | 506.29 | 0.00 | 0.00 | 0.00 |
December | 66.83 | 0.00 | 66.83 | 0.27 | 609.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 247.16 | 6.61 | 240.55 | 155.06 | 390.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.83 | 0.00 | 66.83 | 0.27 | 214.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 449.10 | 28.16 | 420.94 | 370.73 | 609.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.36 | 0.00 | 92.36 | 7.01 | 556.78 | 0.00 | 0.00 | 0.00 |
February | 144.22 | 0.00 | 144.22 | 21.69 | 524.40 | 0.00 | 0.00 | 0.00 |
March | 199.58 | 0.00 | 199.58 | 69.70 | 428.79 | 0.00 | 0.00 | 0.00 |
April | 324.94 | 1.45 | 323.49 | 209.38 | 353.94 | 0.00 | 0.00 | 0.00 |
May | 406.26 | 19.60 | 386.66 | 259.85 | 289.04 | 0.00 | 0.00 | 0.00 |
June | 449.10 | 28.16 | 420.94 | 366.94 | 230.97 | 0.00 | 0.00 | 0.00 |
July | 425.99 | 24.29 | 401.71 | 370.73 | 214.67 | 0.00 | 0.00 | 0.00 |
August | 334.85 | 5.25 | 329.61 | 285.79 | 239.77 | 0.00 | 0.00 | 0.00 |
September | 254.87 | 0.06 | 254.81 | 185.83 | 321.05 | 0.00 | 0.00 | 0.00 |
October | 163.32 | 0.00 | 163.32 | 65.85 | 417.99 | 0.00 | 0.00 | 0.00 |
November | 98.13 | 0.00 | 98.13 | 9.70 | 506.29 | 0.00 | 0.00 | 0.00 |
December | 66.83 | 0.00 | 66.83 | 0.27 | 609.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 247.16 | 6.61 | 240.55 | 155.06 | 390.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.83 | 0.00 | 66.83 | 0.27 | 214.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 449.10 | 28.16 | 420.94 | 370.73 | 609.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 363.20 | 145.90 | 217.30 | 210.01 | 1012.49 | 0.00 | 0.00 | 0.00 |
February | 541.59 | 200.07 | 341.52 | 347.24 | 965.73 | 0.00 | 0.00 | 0.00 |
March | 565.97 | 111.53 | 454.44 | 347.11 | 788.23 | 0.00 | 0.00 | 0.00 |
April | 1519.68 | 714.10 | 805.57 | 1551.86 | 677.64 | 0.00 | 0.00 | 0.00 |
May | 1597.89 | 696.81 | 901.08 | 1581.73 | 593.84 | 0.00 | 0.00 | 0.00 |
June | 1581.62 | 631.68 | 949.94 | 1670.46 | 468.24 | 0.00 | 0.00 | 0.00 |
July | 1614.52 | 686.17 | 928.35 | 1779.38 | 438.45 | 0.00 | 0.00 | 0.00 |
August | 1529.41 | 730.73 | 798.67 | 1737.28 | 478.01 | 0.00 | 0.00 | 0.00 |
September | 1377.28 | 732.37 | 644.91 | 1508.24 | 611.84 | 0.00 | 0.00 | 0.00 |
October | 664.83 | 275.52 | 389.31 | 570.12 | 789.15 | 0.00 | 0.00 | 0.00 |
November | 346.60 | 118.12 | 228.47 | 194.01 | 933.20 | 0.00 | 0.00 | 0.00 |
December | 256.87 | 95.50 | 161.37 | 126.90 | 1118.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 998.06 | 428.76 | 569.30 | 970.93 | 738.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 256.87 | 95.50 | 161.37 | 126.90 | 438.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1614.52 | 732.37 | 949.94 | 1779.38 | 1118.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.36 | 5.77 | 8.59 | 8.30 | 40.03 | 0.00 | 0.00 | 0.00 |
February | 21.41 | 7.91 | 13.50 | 13.73 | 38.18 | 0.00 | 0.00 | 0.00 |
March | 22.38 | 4.41 | 17.97 | 13.72 | 31.17 | 0.00 | 0.00 | 0.00 |
April | 60.09 | 28.24 | 31.85 | 61.36 | 26.79 | 0.00 | 0.00 | 0.00 |
May | 63.18 | 27.55 | 35.63 | 62.54 | 23.48 | 0.00 | 0.00 | 0.00 |
June | 62.54 | 24.98 | 37.56 | 66.05 | 18.51 | 0.00 | 0.00 | 0.00 |
July | 63.84 | 27.13 | 36.71 | 70.36 | 17.34 | 0.00 | 0.00 | 0.00 |
August | 60.47 | 28.89 | 31.58 | 68.69 | 18.90 | 0.00 | 0.00 | 0.00 |
September | 54.46 | 28.96 | 25.50 | 59.63 | 24.19 | 0.00 | 0.00 | 0.00 |
October | 26.29 | 10.89 | 15.39 | 22.54 | 31.20 | 0.00 | 0.00 | 0.00 |
November | 13.70 | 4.67 | 9.03 | 7.67 | 36.90 | 0.00 | 0.00 | 0.00 |
December | 10.16 | 3.78 | 6.38 | 5.02 | 44.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.46 | 16.95 | 22.51 | 38.39 | 29.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.16 | 3.78 | 6.38 | 5.02 | 17.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.84 | 28.96 | 37.56 | 70.36 | 44.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 524.35 | 339.43 | 184.92 | 513.36 | 511.93 | 0.00 | 0.00 | 0.00 |
February | 640.39 | 390.78 | 249.62 | 642.42 | 510.67 | 0.00 | 0.00 | 0.00 |
March | 395.93 | 115.28 | 280.66 | 323.59 | 416.74 | 0.00 | 0.00 | 0.00 |
April | 822.19 | 371.62 | 450.57 | 922.92 | 381.53 | 0.00 | 0.00 | 0.00 |
May | 680.03 | 221.39 | 458.63 | 705.34 | 331.11 | 0.00 | 0.00 | 0.00 |
June | 626.45 | 151.64 | 474.82 | 676.92 | 256.03 | 0.00 | 0.00 | 0.00 |
July | 678.75 | 212.56 | 466.19 | 786.27 | 242.92 | 0.00 | 0.00 | 0.00 |
August | 795.34 | 357.77 | 437.57 | 973.98 | 269.65 | 0.00 | 0.00 | 0.00 |
September | 939.89 | 550.60 | 389.29 | 1137.37 | 346.24 | 0.00 | 0.00 | 0.00 |
October | 645.74 | 377.40 | 268.33 | 698.22 | 426.37 | 0.00 | 0.00 | 0.00 |
November | 457.83 | 278.51 | 179.32 | 448.27 | 489.86 | 0.00 | 0.00 | 0.00 |
December | 362.87 | 232.49 | 130.38 | 344.58 | 576.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 629.85 | 298.79 | 331.06 | 680.16 | 396.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 362.87 | 115.28 | 130.38 | 323.59 | 242.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 939.89 | 550.60 | 474.82 | 1137.37 | 576.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 524.35 | 339.43 | 184.92 | 513.36 | 511.93 | 0.00 | 0.00 | 0.00 |
February | 640.39 | 390.78 | 249.62 | 642.42 | 510.67 | 0.00 | 0.00 | 0.00 |
March | 395.93 | 115.28 | 280.66 | 323.59 | 416.74 | 0.00 | 0.00 | 0.00 |
April | 822.19 | 371.62 | 450.57 | 922.92 | 381.53 | 0.00 | 0.00 | 0.00 |
May | 680.03 | 221.39 | 458.63 | 705.34 | 331.11 | 0.00 | 0.00 | 0.00 |
June | 626.45 | 151.64 | 474.82 | 676.92 | 256.03 | 0.00 | 0.00 | 0.00 |
July | 678.75 | 212.56 | 466.19 | 786.27 | 242.92 | 0.00 | 0.00 | 0.00 |
August | 795.34 | 357.77 | 437.57 | 973.98 | 269.65 | 0.00 | 0.00 | 0.00 |
September | 939.89 | 550.60 | 389.29 | 1137.37 | 346.24 | 0.00 | 0.00 | 0.00 |
October | 645.74 | 377.40 | 268.33 | 698.22 | 426.37 | 0.00 | 0.00 | 0.00 |
November | 457.83 | 278.51 | 179.32 | 448.27 | 489.86 | 0.00 | 0.00 | 0.00 |
December | 362.87 | 232.49 | 130.38 | 344.58 | 576.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 629.85 | 298.79 | 331.06 | 680.16 | 396.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 362.87 | 115.28 | 130.38 | 323.59 | 242.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 939.89 | 550.60 | 474.82 | 1137.37 | 576.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 524.31 | 339.41 | 184.90 | 513.33 | 511.90 | 0.00 | 0.00 | 0.00 |
February | 640.35 | 390.75 | 249.60 | 642.38 | 510.64 | 0.00 | 0.00 | 0.00 |
March | 395.91 | 115.27 | 280.64 | 323.57 | 416.71 | 0.00 | 0.00 | 0.00 |
April | 822.14 | 371.59 | 450.54 | 922.87 | 381.50 | 0.00 | 0.00 | 0.00 |
May | 679.99 | 221.38 | 458.61 | 705.30 | 331.09 | 0.00 | 0.00 | 0.00 |
June | 626.41 | 151.63 | 474.79 | 676.88 | 256.01 | 0.00 | 0.00 | 0.00 |
July | 678.71 | 212.54 | 466.16 | 786.22 | 242.90 | 0.00 | 0.00 | 0.00 |
August | 795.29 | 357.75 | 437.54 | 973.91 | 269.63 | 0.00 | 0.00 | 0.00 |
September | 939.83 | 550.56 | 389.26 | 1137.30 | 346.22 | 0.00 | 0.00 | 0.00 |
October | 645.70 | 377.38 | 268.32 | 698.18 | 426.35 | 0.00 | 0.00 | 0.00 |
November | 457.80 | 278.49 | 179.31 | 448.25 | 489.83 | 0.00 | 0.00 | 0.00 |
December | 362.85 | 232.48 | 130.37 | 344.56 | 576.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 629.81 | 298.77 | 331.04 | 680.12 | 396.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 362.85 | 115.27 | 130.37 | 323.57 | 242.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 939.83 | 550.56 | 474.79 | 1137.30 | 576.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.19 | 116.70 | 236.50 | 212.04 | 1030.56 | 0.00 | 0.00 | 0.00 |
February | 625.34 | 264.04 | 361.30 | 489.15 | 998.46 | 0.00 | 0.00 | 0.00 |
March | 565.44 | 108.17 | 457.27 | 349.85 | 800.82 | 0.00 | 0.00 | 0.00 |
April | 1334.18 | 529.95 | 804.24 | 1350.54 | 711.76 | 0.00 | 0.00 | 0.00 |
May | 1565.30 | 636.50 | 928.80 | 1562.70 | 626.37 | 0.00 | 0.00 | 0.00 |
June | 1690.36 | 695.85 | 994.51 | 1821.78 | 502.13 | 0.00 | 0.00 | 0.00 |
July | 1721.56 | 759.04 | 962.52 | 1939.01 | 470.47 | 0.00 | 0.00 | 0.00 |
August | 1445.99 | 626.07 | 819.92 | 1645.77 | 512.87 | 0.00 | 0.00 | 0.00 |
September | 1160.07 | 520.20 | 639.87 | 1264.96 | 646.35 | 0.00 | 0.00 | 0.00 |
October | 618.85 | 222.54 | 396.32 | 530.99 | 809.63 | 0.00 | 0.00 | 0.00 |
November | 334.90 | 97.76 | 237.14 | 199.99 | 959.44 | 0.00 | 0.00 | 0.00 |
December | 189.56 | 40.00 | 149.56 | 67.95 | 1157.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 968.09 | 384.89 | 583.20 | 954.44 | 767.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 189.56 | 40.00 | 149.56 | 67.95 | 470.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1721.56 | 759.04 | 994.51 | 1939.01 | 1157.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.96 | 4.61 | 9.35 | 8.38 | 40.75 | 0.00 | 0.00 | 0.00 |
February | 24.73 | 10.44 | 14.29 | 19.34 | 39.48 | 0.00 | 0.00 | 0.00 |
March | 22.36 | 4.28 | 18.08 | 13.83 | 31.66 | 0.00 | 0.00 | 0.00 |
April | 52.75 | 20.95 | 31.80 | 53.40 | 28.14 | 0.00 | 0.00 | 0.00 |
May | 61.89 | 25.17 | 36.72 | 61.79 | 24.77 | 0.00 | 0.00 | 0.00 |
June | 66.84 | 27.51 | 39.32 | 72.03 | 19.85 | 0.00 | 0.00 | 0.00 |
July | 68.07 | 30.01 | 38.06 | 76.67 | 18.60 | 0.00 | 0.00 | 0.00 |
August | 57.17 | 24.75 | 32.42 | 65.07 | 20.28 | 0.00 | 0.00 | 0.00 |
September | 45.87 | 20.57 | 25.30 | 50.02 | 25.56 | 0.00 | 0.00 | 0.00 |
October | 24.47 | 8.80 | 15.67 | 20.99 | 32.01 | 0.00 | 0.00 | 0.00 |
November | 13.24 | 3.87 | 9.38 | 7.91 | 37.94 | 0.00 | 0.00 | 0.00 |
December | 7.50 | 1.58 | 5.91 | 2.69 | 45.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.28 | 15.22 | 23.06 | 37.74 | 30.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 7.50 | 1.58 | 5.91 | 2.69 | 18.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.07 | 30.01 | 39.32 | 76.67 | 45.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 277.08 | 0.00 | 277.08 | 17.58 | 1704.15 | 0.00 | 0.00 | 0.00 |
February | 432.67 | 0.00 | 432.67 | 55.75 | 1613.05 | 0.00 | 0.00 | 0.00 |
March | 598.74 | 0.00 | 598.74 | 187.17 | 1328.91 | 0.00 | 0.00 | 0.00 |
April | 974.84 | 4.36 | 970.48 | 578.27 | 1116.38 | 0.00 | 0.00 | 0.00 |
May | 1218.80 | 58.80 | 1160.00 | 727.20 | 902.22 | 0.00 | 0.00 | 0.00 |
June | 1347.31 | 84.48 | 1262.82 | 1059.00 | 714.96 | 0.00 | 0.00 | 0.00 |
July | 1277.99 | 72.87 | 1205.13 | 1080.21 | 659.62 | 0.00 | 0.00 | 0.00 |
August | 1004.57 | 15.74 | 988.83 | 828.66 | 740.67 | 0.00 | 0.00 | 0.00 |
September | 764.61 | 0.17 | 764.44 | 536.39 | 983.72 | 0.00 | 0.00 | 0.00 |
October | 489.96 | 0.00 | 489.96 | 185.97 | 1266.65 | 0.00 | 0.00 | 0.00 |
November | 294.39 | 0.00 | 294.39 | 26.94 | 1521.92 | 0.00 | 0.00 | 0.00 |
December | 200.48 | 0.00 | 200.48 | 0.83 | 1831.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 741.49 | 19.84 | 721.66 | 442.29 | 1196.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 200.48 | 0.00 | 200.48 | 0.83 | 659.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1347.31 | 84.48 | 1262.82 | 1080.21 | 1831.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 377.56 | 151.67 | 225.89 | 213.15 | 1065.69 | 0.00 | 0.00 | 0.00 |
February | 563.01 | 207.98 | 355.03 | 351.64 | 1018.82 | 0.00 | 0.00 | 0.00 |
March | 588.36 | 115.94 | 472.41 | 346.03 | 838.68 | 0.00 | 0.00 | 0.00 |
April | 1579.79 | 742.35 | 837.44 | 1593.21 | 705.54 | 0.00 | 0.00 | 0.00 |
May | 1661.10 | 724.38 | 936.72 | 1626.72 | 612.35 | 0.00 | 0.00 | 0.00 |
June | 1644.18 | 656.67 | 987.51 | 1720.37 | 483.65 | 0.00 | 0.00 | 0.00 |
July | 1678.39 | 713.31 | 965.07 | 1837.63 | 447.94 | 0.00 | 0.00 | 0.00 |
August | 1589.90 | 759.64 | 830.26 | 1795.62 | 486.78 | 0.00 | 0.00 | 0.00 |
September | 1431.76 | 761.35 | 670.42 | 1560.65 | 618.81 | 0.00 | 0.00 | 0.00 |
October | 691.13 | 286.42 | 404.71 | 588.55 | 808.49 | 0.00 | 0.00 | 0.00 |
November | 360.31 | 122.80 | 237.51 | 199.46 | 963.43 | 0.00 | 0.00 | 0.00 |
December | 267.03 | 99.28 | 167.75 | 130.39 | 1161.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1037.54 | 445.72 | 591.82 | 999.28 | 766.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 267.03 | 99.28 | 167.75 | 130.39 | 447.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1678.39 | 761.35 | 987.51 | 1837.63 | 1161.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1573.07 | 1018.31 | 554.76 | 1515.34 | 1545.88 | 0.00 | 0.00 | 0.00 |
February | 1921.21 | 1172.35 | 748.86 | 1893.87 | 1534.89 | 0.00 | 0.00 | 0.00 |
March | 1187.82 | 345.84 | 841.98 | 929.21 | 1286.93 | 0.00 | 0.00 | 0.00 |
April | 2466.61 | 1114.88 | 1351.73 | 2719.81 | 1158.04 | 0.00 | 0.00 | 0.00 |
May | 2040.11 | 664.19 | 1375.92 | 2065.41 | 1013.30 | 0.00 | 0.00 | 0.00 |
June | 1879.38 | 454.92 | 1424.46 | 1982.47 | 788.55 | 0.00 | 0.00 | 0.00 |
July | 2036.27 | 637.68 | 1398.59 | 2324.53 | 733.63 | 0.00 | 0.00 | 0.00 |
August | 2386.06 | 1073.34 | 1312.72 | 2896.46 | 797.56 | 0.00 | 0.00 | 0.00 |
September | 2819.70 | 1651.83 | 1167.87 | 3393.24 | 1004.16 | 0.00 | 0.00 | 0.00 |
October | 1937.25 | 1132.24 | 805.02 | 2077.34 | 1249.91 | 0.00 | 0.00 | 0.00 |
November | 1373.51 | 835.54 | 537.97 | 1326.29 | 1451.55 | 0.00 | 0.00 | 0.00 |
December | 1088.63 | 697.49 | 391.14 | 1017.34 | 1737.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1889.58 | 896.39 | 993.19 | 2008.98 | 1190.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1088.63 | 345.84 | 391.14 | 929.21 | 733.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2819.70 | 1651.83 | 1424.46 | 3393.24 | 1737.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 367.16 | 121.31 | 245.85 | 214.20 | 1085.71 | 0.00 | 0.00 | 0.00 |
February | 650.08 | 274.48 | 375.59 | 497.22 | 1051.09 | 0.00 | 0.00 | 0.00 |
March | 587.81 | 112.45 | 475.36 | 346.24 | 853.41 | 0.00 | 0.00 | 0.00 |
April | 1386.95 | 550.91 | 836.04 | 1379.33 | 750.80 | 0.00 | 0.00 | 0.00 |
May | 1627.22 | 661.68 | 965.53 | 1603.01 | 651.38 | 0.00 | 0.00 | 0.00 |
June | 1757.22 | 723.38 | 1033.84 | 1876.06 | 517.95 | 0.00 | 0.00 | 0.00 |
July | 1789.65 | 789.06 | 1000.59 | 2000.81 | 482.92 | 0.00 | 0.00 | 0.00 |
August | 1503.19 | 650.84 | 852.35 | 1697.87 | 526.12 | 0.00 | 0.00 | 0.00 |
September | 1205.95 | 540.78 | 665.18 | 1306.41 | 662.57 | 0.00 | 0.00 | 0.00 |
October | 643.33 | 231.34 | 411.99 | 545.99 | 835.58 | 0.00 | 0.00 | 0.00 |
November | 348.15 | 101.63 | 246.52 | 204.43 | 993.51 | 0.00 | 0.00 | 0.00 |
December | 197.06 | 41.58 | 155.48 | 69.11 | 1205.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1006.38 | 400.12 | 606.26 | 980.01 | 800.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 197.06 | 41.58 | 155.48 | 69.11 | 482.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1789.65 | 789.06 | 1033.84 | 2000.81 | 1205.29 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.742129E+09 | 0.00 | 0.742129E+09 | 61112990.53 | 0.430410E+10 |
February | 0.104672E+10 | 0.00 | 0.104672E+10 | 0.165292E+09 | 0.365241E+10 |
March | 0.160366E+10 | 0.00 | 0.160366E+10 | 0.547997E+09 | 0.333990E+10 |
April | 0.252679E+10 | 11308836.08 | 0.251548E+10 | 0.154678E+10 | 0.272780E+10 |
May | 0.326443E+10 | 0.157493E+09 | 0.310694E+10 | 0.201685E+10 | 0.227759E+10 |
June | 0.349222E+10 | 0.218985E+09 | 0.327323E+10 | 0.278069E+10 | 0.176726E+10 |
July | 0.342297E+10 | 0.195162E+09 | 0.322781E+10 | 0.292629E+10 | 0.168738E+10 |
August | 0.269063E+10 | 42155565.45 | 0.264848E+10 | 0.224787E+10 | 0.188591E+10 |
September | 0.198188E+10 | 438550.08 | 0.198144E+10 | 0.143507E+10 | 0.239329E+10 |
October | 0.131231E+10 | 0.00 | 0.131231E+10 | 0.552808E+09 | 0.313178E+10 |
November | 0.763066E+09 | 0.00 | 0.763066E+09 | 91500347.21 | 0.365520E+10 |
December | 0.536968E+09 | 0.00 | 0.536968E+09 | 7632916.82 | 0.460206E+10 |
Annual Sum or Average | 0.233838E+11 | 0.625543E+09 | 0.227582E+11 | 0.143799E+11 | 0.354247E+11 |
Minimum of Months | 0.536968E+09 | 0.00 | 0.536968E+09 | 7632916.82 | 0.168738E+10 |
Maximum of Months | 0.349222E+10 | 0.218985E+09 | 0.327323E+10 | 0.292629E+10 | 0.460206E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101126E+10 | 0.406225E+09 | 0.605036E+09 | 0.591685E+09 | 0.269540E+10 |
February | 0.136203E+10 | 0.503146E+09 | 0.858889E+09 | 0.882458E+09 | 0.231550E+10 |
March | 0.157586E+10 | 0.310544E+09 | 0.126531E+10 | 0.961744E+09 | 0.211606E+10 |
April | 0.409481E+10 | 0.192418E+10 | 0.217063E+10 | 0.415801E+10 | 0.174038E+10 |
May | 0.444909E+10 | 0.194017E+10 | 0.250892E+10 | 0.438883E+10 | 0.155980E+10 |
June | 0.426172E+10 | 0.170209E+10 | 0.255963E+10 | 0.447501E+10 | 0.120170E+10 |
July | 0.449539E+10 | 0.191054E+10 | 0.258485E+10 | 0.493410E+10 | 0.115158E+10 |
August | 0.425840E+10 | 0.203462E+10 | 0.222378E+10 | 0.482128E+10 | 0.124926E+10 |
September | 0.371113E+10 | 0.197341E+10 | 0.173772E+10 | 0.406997E+10 | 0.152154E+10 |
October | 0.185112E+10 | 0.767154E+09 | 0.108397E+10 | 0.161286E+10 | 0.201596E+10 |
November | 0.933916E+09 | 0.318292E+09 | 0.615624E+09 | 0.541426E+09 | 0.232498E+10 |
December | 0.715217E+09 | 0.265908E+09 | 0.449309E+09 | 0.366386E+09 | 0.292369E+10 |
Annual Sum or Average | 0.327200E+11 | 0.140563E+11 | 0.186637E+11 | 0.318038E+11 | 0.228159E+11 |
Minimum of Months | 0.715217E+09 | 0.265908E+09 | 0.449309E+09 | 0.366386E+09 | 0.115158E+10 |
Maximum of Months | 0.449539E+10 | 0.203462E+10 | 0.258485E+10 | 0.493410E+10 | 0.292369E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.421330E+10 | 0.272744E+10 | 0.148586E+10 | 0.410621E+10 | 0.390387E+10 |
February | 0.464780E+10 | 0.283615E+10 | 0.181165E+10 | 0.463630E+10 | 0.349069E+10 |
March | 0.318146E+10 | 0.926297E+09 | 0.225516E+10 | 0.254624E+10 | 0.324100E+10 |
April | 0.639344E+10 | 0.288976E+10 | 0.350368E+10 | 0.708537E+10 | 0.284601E+10 |
May | 0.546423E+10 | 0.177898E+10 | 0.368526E+10 | 0.557380E+10 | 0.256302E+10 |
June | 0.487135E+10 | 0.117915E+10 | 0.369220E+10 | 0.516434E+10 | 0.194536E+10 |
July | 0.545395E+10 | 0.170796E+10 | 0.374598E+10 | 0.624587E+10 | 0.187198E+10 |
August | 0.639083E+10 | 0.287483E+10 | 0.351600E+10 | 0.777411E+10 | 0.203325E+10 |
September | 0.730867E+10 | 0.428154E+10 | 0.302713E+10 | 0.882533E+10 | 0.246059E+10 |
October | 0.518874E+10 | 0.303258E+10 | 0.215615E+10 | 0.561717E+10 | 0.311331E+10 |
November | 0.356014E+10 | 0.216572E+10 | 0.139442E+10 | 0.348651E+10 | 0.350136E+10 |
December | 0.291580E+10 | 0.186817E+10 | 0.104763E+10 | 0.276539E+10 | 0.437261E+10 |
Annual Sum or Average | 0.595897E+11 | 0.282686E+11 | 0.313211E+11 | 0.638266E+11 | 0.353430E+11 |
Minimum of Months | 0.291580E+10 | 0.926297E+09 | 0.104763E+10 | 0.254624E+10 | 0.187198E+10 |
Maximum of Months | 0.730867E+10 | 0.428154E+10 | 0.374598E+10 | 0.882533E+10 | 0.437261E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.983402E+09 | 0.324920E+09 | 0.658482E+09 | 0.589726E+09 | 0.274459E+10 |
February | 0.157266E+10 | 0.664029E+09 | 0.908634E+09 | 0.122727E+10 | 0.238683E+10 |
March | 0.157438E+10 | 0.301180E+09 | 0.127320E+10 | 0.957650E+09 | 0.214841E+10 |
April | 0.359498E+10 | 0.142796E+10 | 0.216702E+10 | 0.360348E+10 | 0.184276E+10 |
May | 0.435833E+10 | 0.177225E+10 | 0.258609E+10 | 0.432486E+10 | 0.164806E+10 |
June | 0.455471E+10 | 0.187500E+10 | 0.267971E+10 | 0.487893E+10 | 0.127792E+10 |
July | 0.479340E+10 | 0.211342E+10 | 0.267998E+10 | 0.537252E+10 | 0.123222E+10 |
August | 0.402613E+10 | 0.174320E+10 | 0.228293E+10 | 0.456253E+10 | 0.134012E+10 |
September | 0.312583E+10 | 0.140169E+10 | 0.172414E+10 | 0.341414E+10 | 0.161720E+10 |
October | 0.172310E+10 | 0.619618E+09 | 0.110348E+10 | 0.149628E+10 | 0.207902E+10 |
November | 0.902400E+09 | 0.263422E+09 | 0.638978E+09 | 0.547865E+09 | 0.239526E+10 |
December | 0.527811E+09 | 0.111380E+09 | 0.416431E+09 | 0.194658E+09 | 0.303400E+10 |
Annual Sum or Average | 0.317371E+11 | 0.126181E+11 | 0.191191E+11 | 0.311699E+11 | 0.237464E+11 |
Minimum of Months | 0.527811E+09 | 0.111380E+09 | 0.416431E+09 | 0.194658E+09 | 0.123222E+10 |
Maximum of Months | 0.479340E+10 | 0.211342E+10 | 0.267998E+10 | 0.537252E+10 | 0.303400E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247365E+09 | 0.00 | 0.247365E+09 | 18771810.87 | 0.149118E+10 |
February | 0.348889E+09 | 0.00 | 0.348889E+09 | 52481080.68 | 0.126856E+10 |
March | 0.534530E+09 | 0.00 | 0.534530E+09 | 0.186679E+09 | 0.114839E+10 |
April | 0.842222E+09 | 3769433.68 | 0.838453E+09 | 0.542688E+09 | 0.917366E+09 |
May | 0.108809E+10 | 52495202.52 | 0.103560E+10 | 0.695959E+09 | 0.774104E+09 |
June | 0.116402E+10 | 72991400.42 | 0.109103E+10 | 0.951082E+09 | 0.598641E+09 |
July | 0.114094E+10 | 65050899.12 | 0.107589E+10 | 0.992925E+09 | 0.574931E+09 |
August | 0.896836E+09 | 14051190.33 | 0.882784E+09 | 0.765436E+09 | 0.642167E+09 |
September | 0.660595E+09 | 146176.44 | 0.660449E+09 | 0.481647E+09 | 0.832117E+09 |
October | 0.437415E+09 | 0.00 | 0.437415E+09 | 0.176372E+09 | 0.111946E+10 |
November | 0.254343E+09 | 0.00 | 0.254343E+09 | 25153313.11 | 0.131223E+10 |
December | 0.178981E+09 | 0.00 | 0.178981E+09 | 728712.69 | 0.163360E+10 |
Annual Sum or Average | 0.779422E+10 | 0.208504E+09 | 0.758572E+10 | 0.488992E+10 | 0.123128E+11 |
Minimum of Months | 0.178981E+09 | 0.00 | 0.178981E+09 | 728712.69 | 0.574931E+09 |
Maximum of Months | 0.116402E+10 | 72991400.42 | 0.109103E+10 | 0.992925E+09 | 0.163360E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247374E+09 | 0.00 | 0.247374E+09 | 18770720.77 | 0.149128E+10 |
February | 0.348902E+09 | 0.00 | 0.348902E+09 | 52478743.66 | 0.126864E+10 |
March | 0.534549E+09 | 0.00 | 0.534549E+09 | 0.186677E+09 | 0.114846E+10 |
April | 0.842255E+09 | 3769535.00 | 0.838486E+09 | 0.542701E+09 | 0.917423E+09 |
May | 0.108813E+10 | 52496613.61 | 0.103564E+10 | 0.695972E+09 | 0.774153E+09 |
June | 0.116406E+10 | 72993362.45 | 0.109107E+10 | 0.951107E+09 | 0.598677E+09 |
July | 0.114098E+10 | 65052647.71 | 0.107593E+10 | 0.992954E+09 | 0.574965E+09 |
August | 0.896872E+09 | 14051568.03 | 0.882820E+09 | 0.765462E+09 | 0.642205E+09 |
September | 0.660622E+09 | 146180.37 | 0.660476E+09 | 0.481662E+09 | 0.832166E+09 |
October | 0.437431E+09 | 0.00 | 0.437431E+09 | 0.176374E+09 | 0.111953E+10 |
November | 0.254353E+09 | 0.00 | 0.254353E+09 | 25151908.92 | 0.131232E+10 |
December | 0.178987E+09 | 0.00 | 0.178987E+09 | 728452.42 | 0.163370E+10 |
Annual Sum or Average | 0.779452E+10 | 0.208510E+09 | 0.758601E+10 | 0.489004E+10 | 0.123135E+11 |
Minimum of Months | 0.178987E+09 | 0.00 | 0.178987E+09 | 728452.42 | 0.574965E+09 |
Maximum of Months | 0.116406E+10 | 72993362.45 | 0.109107E+10 | 0.992954E+09 | 0.163370E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247374E+09 | 0.00 | 0.247374E+09 | 18770720.77 | 0.149128E+10 |
February | 0.348902E+09 | 0.00 | 0.348902E+09 | 52478743.66 | 0.126864E+10 |
March | 0.534549E+09 | 0.00 | 0.534549E+09 | 0.186677E+09 | 0.114846E+10 |
April | 0.842255E+09 | 3769535.00 | 0.838486E+09 | 0.542701E+09 | 0.917423E+09 |
May | 0.108813E+10 | 52496613.61 | 0.103564E+10 | 0.695972E+09 | 0.774153E+09 |
June | 0.116406E+10 | 72993362.45 | 0.109107E+10 | 0.951107E+09 | 0.598677E+09 |
July | 0.114098E+10 | 65052647.71 | 0.107593E+10 | 0.992954E+09 | 0.574965E+09 |
August | 0.896872E+09 | 14051568.03 | 0.882820E+09 | 0.765462E+09 | 0.642205E+09 |
September | 0.660622E+09 | 146180.37 | 0.660476E+09 | 0.481662E+09 | 0.832166E+09 |
October | 0.437431E+09 | 0.00 | 0.437431E+09 | 0.176374E+09 | 0.111953E+10 |
November | 0.254353E+09 | 0.00 | 0.254353E+09 | 25151908.92 | 0.131232E+10 |
December | 0.178987E+09 | 0.00 | 0.178987E+09 | 728452.42 | 0.163370E+10 |
Annual Sum or Average | 0.779452E+10 | 0.208510E+09 | 0.758601E+10 | 0.489004E+10 | 0.123135E+11 |
Minimum of Months | 0.178987E+09 | 0.00 | 0.178987E+09 | 728452.42 | 0.574965E+09 |
Maximum of Months | 0.116406E+10 | 72993362.45 | 0.109107E+10 | 0.992954E+09 | 0.163370E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.972782E+09 | 0.390767E+09 | 0.582015E+09 | 0.562497E+09 | 0.271184E+10 |
February | 0.131021E+10 | 0.483999E+09 | 0.826209E+09 | 0.840035E+09 | 0.233629E+10 |
March | 0.151590E+10 | 0.298727E+09 | 0.121717E+10 | 0.929688E+09 | 0.211120E+10 |
April | 0.393900E+10 | 0.185096E+10 | 0.208805E+10 | 0.402243E+10 | 0.175645E+10 |
May | 0.427980E+10 | 0.186634E+10 | 0.241346E+10 | 0.423650E+10 | 0.159055E+10 |
June | 0.409957E+10 | 0.163732E+10 | 0.246225E+10 | 0.432982E+10 | 0.121368E+10 |
July | 0.432434E+10 | 0.183784E+10 | 0.248650E+10 | 0.476590E+10 | 0.117434E+10 |
August | 0.409637E+10 | 0.195720E+10 | 0.213917E+10 | 0.465313E+10 | 0.128030E+10 |
September | 0.356992E+10 | 0.189831E+10 | 0.167161E+10 | 0.390937E+10 | 0.158589E+10 |
October | 0.178069E+10 | 0.737960E+09 | 0.104273E+10 | 0.152702E+10 | 0.211366E+10 |
November | 0.898380E+09 | 0.306180E+09 | 0.592200E+09 | 0.502872E+09 | 0.241887E+10 |
December | 0.688002E+09 | 0.255789E+09 | 0.432213E+09 | 0.339886E+09 | 0.299496E+10 |
Annual Sum or Average | 0.314750E+11 | 0.135214E+11 | 0.179536E+11 | 0.306191E+11 | 0.232880E+11 |
Minimum of Months | 0.688002E+09 | 0.255789E+09 | 0.432213E+09 | 0.339886E+09 | 0.117434E+10 |
Maximum of Months | 0.432434E+10 | 0.195720E+10 | 0.248650E+10 | 0.476590E+10 | 0.299496E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38462912.81 | 15450563.66 | 23012349.15 | 22240613.08 | 0.107224E+09 |
February | 51804438.50 | 19136878.50 | 32667559.99 | 33214217.43 | 92374997.36 |
March | 59937168.25 | 11811377.35 | 48125790.89 | 36759033.73 | 83475042.01 |
April | 0.155745E+09 | 73185173.08 | 82559454.94 | 0.159043E+09 | 69448490.24 |
May | 0.169219E+09 | 73793362.72 | 95425981.64 | 0.167508E+09 | 62889028.54 |
June | 0.162093E+09 | 64738127.62 | 97355023.25 | 0.171197E+09 | 47987620.76 |
July | 0.170981E+09 | 72666393.88 | 98314160.78 | 0.188439E+09 | 46432229.73 |
August | 0.161967E+09 | 77385855.50 | 84580812.97 | 0.183980E+09 | 50621787.33 |
September | 0.141151E+09 | 75057624.30 | 66093765.37 | 0.154573E+09 | 62704786.68 |
October | 70406809.12 | 29178290.72 | 41228518.40 | 60376843.49 | 83572047.23 |
November | 35521132.71 | 12106073.24 | 23415059.46 | 19883111.34 | 95639770.24 |
December | 27202991.32 | 10113659.09 | 17089332.23 | 13438783.64 | 0.118418E+09 |
Annual Sum or Average | 0.124449E+10 | 0.534623E+09 | 0.709868E+09 | 0.121065E+10 | 0.920788E+09 |
Minimum of Months | 27202991.32 | 10113659.09 | 17089332.23 | 13438783.64 | 46432229.73 |
Maximum of Months | 0.170981E+09 | 77385855.50 | 98314160.78 | 0.188439E+09 | 0.118418E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140441E+10 | 0.909129E+09 | 0.495279E+09 | 0.137499E+10 | 0.137115E+10 |
February | 0.154924E+10 | 0.945364E+09 | 0.603874E+09 | 0.155415E+10 | 0.123542E+10 |
March | 0.106047E+10 | 0.308759E+09 | 0.751709E+09 | 0.866696E+09 | 0.111619E+10 |
April | 0.213111E+10 | 0.963234E+09 | 0.116788E+10 | 0.239222E+10 | 0.988913E+09 |
May | 0.182139E+10 | 0.592980E+09 | 0.122841E+10 | 0.188919E+10 | 0.886844E+09 |
June | 0.162376E+10 | 0.393042E+09 | 0.123072E+10 | 0.175458E+10 | 0.663629E+09 |
July | 0.181796E+10 | 0.569310E+09 | 0.124865E+10 | 0.210593E+10 | 0.650624E+09 |
August | 0.213025E+10 | 0.958258E+09 | 0.117199E+10 | 0.260870E+10 | 0.722232E+09 |
September | 0.243618E+10 | 0.142715E+10 | 0.100903E+10 | 0.294807E+10 | 0.897460E+09 |
October | 0.172955E+10 | 0.101084E+10 | 0.718708E+09 | 0.187011E+10 | 0.114200E+10 |
November | 0.118669E+10 | 0.721894E+09 | 0.464799E+09 | 0.116193E+10 | 0.126973E+10 |
December | 0.971914E+09 | 0.622709E+09 | 0.349205E+09 | 0.922927E+09 | 0.154475E+10 |
Annual Sum or Average | 0.198629E+11 | 0.942267E+10 | 0.104403E+11 | 0.214495E+11 | 0.124889E+11 |
Minimum of Months | 0.971914E+09 | 0.308759E+09 | 0.349205E+09 | 0.866696E+09 | 0.650624E+09 |
Maximum of Months | 0.243618E+10 | 0.142715E+10 | 0.124865E+10 | 0.294807E+10 | 0.154475E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140441E+10 | 0.909129E+09 | 0.495279E+09 | 0.137499E+10 | 0.137115E+10 |
February | 0.154924E+10 | 0.945364E+09 | 0.603874E+09 | 0.155415E+10 | 0.123542E+10 |
March | 0.106047E+10 | 0.308759E+09 | 0.751709E+09 | 0.866696E+09 | 0.111619E+10 |
April | 0.213111E+10 | 0.963234E+09 | 0.116788E+10 | 0.239222E+10 | 0.988913E+09 |
May | 0.182139E+10 | 0.592980E+09 | 0.122841E+10 | 0.188919E+10 | 0.886844E+09 |
June | 0.162376E+10 | 0.393042E+09 | 0.123072E+10 | 0.175458E+10 | 0.663629E+09 |
July | 0.181796E+10 | 0.569310E+09 | 0.124865E+10 | 0.210593E+10 | 0.650624E+09 |
August | 0.213025E+10 | 0.958258E+09 | 0.117199E+10 | 0.260870E+10 | 0.722232E+09 |
September | 0.243618E+10 | 0.142715E+10 | 0.100903E+10 | 0.294807E+10 | 0.897460E+09 |
October | 0.172955E+10 | 0.101084E+10 | 0.718708E+09 | 0.187011E+10 | 0.114200E+10 |
November | 0.118669E+10 | 0.721894E+09 | 0.464799E+09 | 0.116193E+10 | 0.126973E+10 |
December | 0.971914E+09 | 0.622709E+09 | 0.349205E+09 | 0.922927E+09 | 0.154475E+10 |
Annual Sum or Average | 0.198629E+11 | 0.942267E+10 | 0.104403E+11 | 0.214495E+11 | 0.124889E+11 |
Minimum of Months | 0.971914E+09 | 0.308759E+09 | 0.349205E+09 | 0.866696E+09 | 0.650624E+09 |
Maximum of Months | 0.243618E+10 | 0.142715E+10 | 0.124865E+10 | 0.294807E+10 | 0.154475E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140432E+10 | 0.909072E+09 | 0.495247E+09 | 0.137491E+10 | 0.137106E+10 |
February | 0.154914E+10 | 0.945304E+09 | 0.603836E+09 | 0.155405E+10 | 0.123535E+10 |
March | 0.106040E+10 | 0.308740E+09 | 0.751662E+09 | 0.866641E+09 | 0.111612E+10 |
April | 0.213098E+10 | 0.963173E+09 | 0.116781E+10 | 0.239207E+10 | 0.988851E+09 |
May | 0.182127E+10 | 0.592943E+09 | 0.122833E+10 | 0.188907E+10 | 0.886788E+09 |
June | 0.162366E+10 | 0.393017E+09 | 0.123064E+10 | 0.175447E+10 | 0.663587E+09 |
July | 0.181784E+10 | 0.569274E+09 | 0.124857E+10 | 0.210580E+10 | 0.650583E+09 |
August | 0.213011E+10 | 0.958198E+09 | 0.117191E+10 | 0.260853E+10 | 0.722187E+09 |
September | 0.243603E+10 | 0.142706E+10 | 0.100897E+10 | 0.294788E+10 | 0.897403E+09 |
October | 0.172944E+10 | 0.101078E+10 | 0.718663E+09 | 0.187000E+10 | 0.114192E+10 |
November | 0.118662E+10 | 0.721848E+09 | 0.464769E+09 | 0.116185E+10 | 0.126965E+10 |
December | 0.971853E+09 | 0.622670E+09 | 0.349183E+09 | 0.922869E+09 | 0.154465E+10 |
Annual Sum or Average | 0.198617E+11 | 0.942208E+10 | 0.104396E+11 | 0.214481E+11 | 0.124881E+11 |
Minimum of Months | 0.971853E+09 | 0.308740E+09 | 0.349183E+09 | 0.866641E+09 | 0.650583E+09 |
Maximum of Months | 0.243603E+10 | 0.142706E+10 | 0.124857E+10 | 0.294788E+10 | 0.154465E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.945986E+09 | 0.312557E+09 | 0.633429E+09 | 0.567918E+09 | 0.276025E+10 |
February | 0.151283E+10 | 0.638762E+09 | 0.874064E+09 | 0.118335E+10 | 0.241548E+10 |
March | 0.151448E+10 | 0.289720E+09 | 0.122476E+10 | 0.937035E+09 | 0.214492E+10 |
April | 0.345820E+10 | 0.137362E+10 | 0.208458E+10 | 0.350060E+10 | 0.184488E+10 |
May | 0.419251E+10 | 0.170481E+10 | 0.248770E+10 | 0.418553E+10 | 0.167767E+10 |
June | 0.438141E+10 | 0.180366E+10 | 0.257776E+10 | 0.472204E+10 | 0.130152E+10 |
July | 0.461102E+10 | 0.203300E+10 | 0.257802E+10 | 0.519345E+10 | 0.126009E+10 |
August | 0.387295E+10 | 0.167687E+10 | 0.219608E+10 | 0.440803E+10 | 0.137367E+10 |
September | 0.300690E+10 | 0.134836E+10 | 0.165854E+10 | 0.327877E+10 | 0.167534E+10 |
October | 0.165754E+10 | 0.596041E+09 | 0.106150E+10 | 0.142219E+10 | 0.216852E+10 |
November | 0.868065E+09 | 0.253398E+09 | 0.614667E+09 | 0.518368E+09 | 0.248688E+10 |
December | 0.507729E+09 | 0.107142E+09 | 0.400588E+09 | 0.181997E+09 | 0.310052E+10 |
Annual Sum or Average | 0.305296E+11 | 0.121379E+11 | 0.183917E+11 | 0.300993E+11 | 0.242097E+11 |
Minimum of Months | 0.507729E+09 | 0.107142E+09 | 0.400588E+09 | 0.181997E+09 | 0.126009E+10 |
Maximum of Months | 0.461102E+10 | 0.203300E+10 | 0.257802E+10 | 0.519345E+10 | 0.310052E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37403321.09 | 12358166.03 | 25045155.06 | 22454842.01 | 0.109138E+09 |
February | 59815591.04 | 25255982.72 | 34559608.31 | 46788343.14 | 95505998.95 |
March | 59881123.83 | 11455211.39 | 48425912.44 | 37049315.98 | 84808064.09 |
April | 0.136734E+09 | 54311605.87 | 82422134.32 | 0.138410E+09 | 72944846.93 |
May | 0.165768E+09 | 67406582.89 | 98361057.70 | 0.165492E+09 | 66333570.88 |
June | 0.173237E+09 | 71314673.97 | 0.101922E+09 | 0.186705E+09 | 51461103.59 |
July | 0.182315E+09 | 80382916.61 | 0.101932E+09 | 0.205344E+09 | 49822991.27 |
August | 0.153133E+09 | 66301837.26 | 86830703.43 | 0.174289E+09 | 54313777.48 |
September | 0.118890E+09 | 53312735.22 | 65577218.40 | 0.129639E+09 | 66241470.75 |
October | 65537295.38 | 23566840.06 | 41970455.32 | 56232087.34 | 85741345.72 |
November | 34322429.76 | 10019108.50 | 24303321.26 | 20495717.93 | 98328911.25 |
December | 20075105.27 | 4236267.53 | 15838837.74 | 7195941.44 | 0.122592E+09 |
Annual Sum or Average | 0.120711E+10 | 0.479922E+09 | 0.727189E+09 | 0.119009E+10 | 0.957232E+09 |
Minimum of Months | 20075105.27 | 4236267.53 | 15838837.74 | 7195941.44 | 49822991.27 |
Maximum of Months | 0.182315E+09 | 80382916.61 | 0.101932E+09 | 0.205344E+09 | 0.122592E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.742129E+09 | 0.00 | 0.742129E+09 | 47081820.72 | 0.456438E+10 |
February | 0.104672E+10 | 0.00 | 0.104672E+10 | 0.134861E+09 | 0.390229E+10 |
March | 0.160366E+10 | 0.00 | 0.160366E+10 | 0.501327E+09 | 0.355936E+10 |
April | 0.252679E+10 | 11308836.08 | 0.251548E+10 | 0.149887E+10 | 0.289367E+10 |
May | 0.326443E+10 | 0.157493E+09 | 0.310694E+10 | 0.194773E+10 | 0.241650E+10 |
June | 0.349222E+10 | 0.218985E+09 | 0.327323E+10 | 0.274492E+10 | 0.185317E+10 |
July | 0.342297E+10 | 0.195162E+09 | 0.322781E+10 | 0.289324E+10 | 0.176674E+10 |
August | 0.269063E+10 | 42155565.45 | 0.264848E+10 | 0.221949E+10 | 0.198381E+10 |
September | 0.198188E+10 | 438550.08 | 0.198144E+10 | 0.139033E+10 | 0.254981E+10 |
October | 0.131231E+10 | 0.00 | 0.131231E+10 | 0.498105E+09 | 0.339260E+10 |
November | 0.763066E+09 | 0.00 | 0.763066E+09 | 69841079.70 | 0.394481E+10 |
December | 0.536968E+09 | 0.00 | 0.536968E+09 | 2226315.89 | 0.490637E+10 |
Annual Sum or Average | 0.233838E+11 | 0.625543E+09 | 0.227582E+11 | 0.139480E+11 | 0.377335E+11 |
Minimum of Months | 0.536968E+09 | 0.00 | 0.536968E+09 | 2226315.89 | 0.176674E+10 |
Maximum of Months | 0.349222E+10 | 0.218985E+09 | 0.327323E+10 | 0.289324E+10 | 0.490637E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101126E+10 | 0.406225E+09 | 0.605036E+09 | 0.570900E+09 | 0.285434E+10 |
February | 0.136203E+10 | 0.503146E+09 | 0.858889E+09 | 0.850684E+09 | 0.246473E+10 |
March | 0.157586E+10 | 0.310544E+09 | 0.126531E+10 | 0.926807E+09 | 0.224633E+10 |
April | 0.409481E+10 | 0.192418E+10 | 0.217063E+10 | 0.412960E+10 | 0.182876E+10 |
May | 0.444909E+10 | 0.194017E+10 | 0.250892E+10 | 0.435702E+10 | 0.164011E+10 |
June | 0.426172E+10 | 0.170209E+10 | 0.255963E+10 | 0.445919E+10 | 0.125361E+10 |
July | 0.449539E+10 | 0.191054E+10 | 0.258485E+10 | 0.492191E+10 | 0.119975E+10 |
August | 0.425840E+10 | 0.203462E+10 | 0.222378E+10 | 0.480938E+10 | 0.130379E+10 |
September | 0.371113E+10 | 0.197341E+10 | 0.173772E+10 | 0.404520E+10 | 0.160396E+10 |
October | 0.185112E+10 | 0.767154E+09 | 0.108397E+10 | 0.157638E+10 | 0.216547E+10 |
November | 0.933916E+09 | 0.318292E+09 | 0.615624E+09 | 0.517008E+09 | 0.249722E+10 |
December | 0.715217E+09 | 0.265908E+09 | 0.449309E+09 | 0.349248E+09 | 0.311075E+10 |
Annual Sum or Average | 0.327200E+11 | 0.140563E+11 | 0.186637E+11 | 0.315133E+11 | 0.241688E+11 |
Minimum of Months | 0.715217E+09 | 0.265908E+09 | 0.449309E+09 | 0.349248E+09 | 0.119975E+10 |
Maximum of Months | 0.449539E+10 | 0.203462E+10 | 0.258485E+10 | 0.492191E+10 | 0.311075E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.421330E+10 | 0.272744E+10 | 0.148586E+10 | 0.405869E+10 | 0.414047E+10 |
February | 0.464780E+10 | 0.283615E+10 | 0.181165E+10 | 0.458165E+10 | 0.371321E+10 |
March | 0.318146E+10 | 0.926297E+09 | 0.225516E+10 | 0.248881E+10 | 0.344692E+10 |
April | 0.639344E+10 | 0.288976E+10 | 0.350368E+10 | 0.704974E+10 | 0.300164E+10 |
May | 0.546423E+10 | 0.177898E+10 | 0.368526E+10 | 0.553199E+10 | 0.271401E+10 |
June | 0.487135E+10 | 0.117915E+10 | 0.369220E+10 | 0.513856E+10 | 0.204392E+10 |
July | 0.545395E+10 | 0.170796E+10 | 0.374598E+10 | 0.622603E+10 | 0.196496E+10 |
August | 0.639083E+10 | 0.287483E+10 | 0.351600E+10 | 0.775788E+10 | 0.213618E+10 |
September | 0.730867E+10 | 0.428154E+10 | 0.302713E+10 | 0.879528E+10 | 0.260279E+10 |
October | 0.518874E+10 | 0.303258E+10 | 0.215615E+10 | 0.556395E+10 | 0.334776E+10 |
November | 0.356014E+10 | 0.216572E+10 | 0.139442E+10 | 0.343774E+10 | 0.376241E+10 |
December | 0.291580E+10 | 0.186817E+10 | 0.104763E+10 | 0.272485E+10 | 0.465369E+10 |
Annual Sum or Average | 0.595897E+11 | 0.282686E+11 | 0.313211E+11 | 0.633552E+11 | 0.375280E+11 |
Minimum of Months | 0.291580E+10 | 0.926297E+09 | 0.104763E+10 | 0.248881E+10 | 0.196496E+10 |
Maximum of Months | 0.730867E+10 | 0.428154E+10 | 0.374598E+10 | 0.879528E+10 | 0.465369E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.983402E+09 | 0.324920E+09 | 0.658482E+09 | 0.573718E+09 | 0.290796E+10 |
February | 0.157266E+10 | 0.664029E+09 | 0.908634E+09 | 0.120288E+10 | 0.254279E+10 |
March | 0.157438E+10 | 0.301180E+09 | 0.127320E+10 | 0.927364E+09 | 0.228576E+10 |
April | 0.359498E+10 | 0.142796E+10 | 0.216702E+10 | 0.357522E+10 | 0.194607E+10 |
May | 0.435833E+10 | 0.177225E+10 | 0.258609E+10 | 0.429350E+10 | 0.174467E+10 |
June | 0.455471E+10 | 0.187500E+10 | 0.267971E+10 | 0.486274E+10 | 0.134253E+10 |
July | 0.479340E+10 | 0.211342E+10 | 0.267998E+10 | 0.535896E+10 | 0.129346E+10 |
August | 0.402613E+10 | 0.174320E+10 | 0.228293E+10 | 0.454759E+10 | 0.140916E+10 |
September | 0.312583E+10 | 0.140169E+10 | 0.172414E+10 | 0.338621E+10 | 0.171739E+10 |
October | 0.172310E+10 | 0.619618E+09 | 0.110348E+10 | 0.146237E+10 | 0.223802E+10 |
November | 0.902400E+09 | 0.263422E+09 | 0.638978E+09 | 0.529876E+09 | 0.257517E+10 |
December | 0.527811E+09 | 0.111380E+09 | 0.416431E+09 | 0.185107E+09 | 0.322824E+10 |
Annual Sum or Average | 0.317371E+11 | 0.126181E+11 | 0.191191E+11 | 0.309055E+11 | 0.252312E+11 |
Minimum of Months | 0.527811E+09 | 0.111380E+09 | 0.416431E+09 | 0.185107E+09 | 0.129346E+10 |
Maximum of Months | 0.479340E+10 | 0.211342E+10 | 0.267998E+10 | 0.535896E+10 | 0.322824E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.82 | 1606.97 | 277.08 | 0.00 | 277.08 | 0.00 | 0.00 |
February | 68.33 | 1509.76 | 432.67 | 0.00 | 432.67 | 0.00 | 0.00 |
March | 204.60 | 1246.97 | 598.74 | 0.00 | 598.74 | 0.00 | 0.00 |
April | 596.75 | 1052.39 | 974.84 | 4.36 | 970.48 | 0.00 | 0.00 |
May | 753.01 | 850.36 | 1218.80 | 58.80 | 1160.00 | 0.00 | 0.00 |
June | 1072.80 | 681.81 | 1347.31 | 84.48 | 1262.82 | 0.00 | 0.00 |
July | 1092.55 | 630.00 | 1277.99 | 72.87 | 1205.13 | 0.00 | 0.00 |
August | 839.26 | 704.12 | 1004.57 | 15.74 | 988.83 | 0.00 | 0.00 |
September | 553.65 | 923.34 | 764.61 | 0.17 | 764.44 | 0.00 | 0.00 |
October | 206.39 | 1169.27 | 489.96 | 0.00 | 489.96 | 0.00 | 0.00 |
November | 35.30 | 1410.19 | 294.39 | 0.00 | 294.39 | 0.00 | 0.00 |
December | 2.85 | 1718.21 | 200.48 | 0.00 | 200.48 | 0.00 | 0.00 |
Annual Sum or Average | 455.98 | 1123.31 | 741.49 | 19.84 | 721.66 | 0.00 | 0.00 |
Minimum of Months | 2.85 | 630.00 | 200.48 | 0.00 | 200.48 | 0.00 | 0.00 |
Maximum of Months | 1092.55 | 1718.21 | 1347.31 | 84.48 | 1262.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 220.91 | 1006.35 | 377.56 | 151.67 | 225.89 | 0.00 | 0.00 |
February | 364.77 | 957.13 | 563.01 | 207.98 | 355.03 | 0.00 | 0.00 |
March | 359.07 | 790.05 | 588.36 | 115.94 | 472.41 | 0.00 | 0.00 |
April | 1604.17 | 671.44 | 1579.79 | 742.35 | 837.44 | 0.00 | 0.00 |
May | 1638.60 | 582.36 | 1661.10 | 724.38 | 936.72 | 0.00 | 0.00 |
June | 1726.47 | 463.62 | 1644.18 | 656.67 | 987.51 | 0.00 | 0.00 |
July | 1842.18 | 429.95 | 1678.39 | 713.31 | 965.07 | 0.00 | 0.00 |
August | 1800.06 | 466.42 | 1589.90 | 759.64 | 830.26 | 0.00 | 0.00 |
September | 1570.20 | 587.01 | 1431.76 | 761.35 | 670.42 | 0.00 | 0.00 |
October | 602.17 | 752.67 | 691.13 | 286.42 | 404.71 | 0.00 | 0.00 |
November | 208.88 | 896.98 | 360.31 | 122.80 | 237.51 | 0.00 | 0.00 |
December | 136.79 | 1091.58 | 267.03 | 99.28 | 167.75 | 0.00 | 0.00 |
Annual Sum or Average | 1008.49 | 723.49 | 1037.54 | 445.72 | 591.82 | 0.00 | 0.00 |
Minimum of Months | 136.79 | 429.95 | 267.03 | 99.28 | 167.75 | 0.00 | 0.00 |
Maximum of Months | 1842.18 | 1091.58 | 1678.39 | 761.35 | 987.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1533.08 | 1457.54 | 1573.07 | 1018.31 | 554.76 | 0.00 | 0.00 |
February | 1916.46 | 1442.91 | 1921.21 | 1172.35 | 748.86 | 0.00 | 0.00 |
March | 950.66 | 1210.05 | 1187.82 | 345.84 | 841.98 | 0.00 | 0.00 |
April | 2733.55 | 1098.00 | 2466.61 | 1114.88 | 1351.73 | 0.00 | 0.00 |
May | 2081.02 | 956.92 | 2040.11 | 664.19 | 1375.92 | 0.00 | 0.00 |
June | 1992.41 | 750.52 | 1879.38 | 454.92 | 1424.46 | 0.00 | 0.00 |
July | 2331.94 | 698.92 | 2036.27 | 637.68 | 1398.59 | 0.00 | 0.00 |
August | 2902.52 | 759.13 | 2386.06 | 1073.34 | 1312.72 | 0.00 | 0.00 |
September | 3404.83 | 949.30 | 2819.70 | 1651.83 | 1167.87 | 0.00 | 0.00 |
October | 2097.21 | 1162.37 | 1937.25 | 1132.24 | 805.02 | 0.00 | 0.00 |
November | 1345.10 | 1350.83 | 1373.51 | 835.54 | 537.97 | 0.00 | 0.00 |
December | 1032.48 | 1632.55 | 1088.63 | 697.49 | 391.14 | 0.00 | 0.00 |
Annual Sum or Average | 2023.93 | 1120.72 | 1889.58 | 896.39 | 993.19 | 0.00 | 0.00 |
Minimum of Months | 950.66 | 698.92 | 1088.63 | 345.84 | 391.14 | 0.00 | 0.00 |
Maximum of Months | 3404.83 | 1632.55 | 2819.70 | 1651.83 | 1424.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 220.18 | 1024.71 | 367.16 | 121.31 | 245.85 | 0.00 | 0.00 |
February | 507.30 | 986.62 | 650.08 | 274.48 | 375.59 | 0.00 | 0.00 |
March | 357.55 | 802.12 | 587.81 | 112.45 | 475.36 | 0.00 | 0.00 |
April | 1390.23 | 710.94 | 1386.95 | 550.91 | 836.04 | 0.00 | 0.00 |
May | 1614.72 | 615.31 | 1627.22 | 661.68 | 965.53 | 0.00 | 0.00 |
June | 1882.30 | 493.02 | 1757.22 | 723.38 | 1033.84 | 0.00 | 0.00 |
July | 2005.87 | 460.06 | 1789.65 | 789.06 | 1000.59 | 0.00 | 0.00 |
August | 1703.46 | 500.34 | 1503.19 | 650.84 | 852.35 | 0.00 | 0.00 |
September | 1317.18 | 623.92 | 1205.95 | 540.78 | 665.18 | 0.00 | 0.00 |
October | 558.65 | 776.22 | 643.33 | 231.34 | 411.99 | 0.00 | 0.00 |
November | 211.37 | 924.10 | 348.15 | 101.63 | 246.52 | 0.00 | 0.00 |
December | 72.68 | 1132.77 | 197.06 | 41.58 | 155.48 | 0.00 | 0.00 |
Annual Sum or Average | 988.39 | 752.99 | 1006.38 | 400.12 | 606.26 | 0.00 | 0.00 |
Minimum of Months | 72.68 | 460.06 | 197.06 | 41.58 | 155.48 | 0.00 | 0.00 |
Maximum of Months | 2005.87 | 1132.77 | 1789.65 | 789.06 | 1033.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 21.02 | 1670.30 | 277.07 | 0.00 | 277.07 | 0.00 | 0.00 |
February | 65.08 | 1573.18 | 432.66 | 0.00 | 432.66 | 0.00 | 0.00 |
March | 209.09 | 1286.34 | 598.73 | 0.00 | 598.73 | 0.00 | 0.00 |
April | 628.12 | 1061.81 | 974.82 | 4.36 | 970.46 | 0.00 | 0.00 |
May | 779.53 | 867.09 | 1218.77 | 58.80 | 1159.97 | 0.00 | 0.00 |
June | 1100.81 | 692.90 | 1347.28 | 84.48 | 1262.79 | 0.00 | 0.00 |
July | 1112.17 | 643.99 | 1277.97 | 72.86 | 1205.10 | 0.00 | 0.00 |
August | 857.36 | 719.30 | 1004.55 | 15.74 | 988.81 | 0.00 | 0.00 |
September | 557.47 | 963.14 | 764.60 | 0.17 | 764.43 | 0.00 | 0.00 |
October | 197.55 | 1253.93 | 489.95 | 0.00 | 489.95 | 0.00 | 0.00 |
November | 29.11 | 1518.85 | 294.39 | 0.00 | 294.39 | 0.00 | 0.00 |
December | 0.82 | 1829.83 | 200.48 | 0.00 | 200.48 | 0.00 | 0.00 |
Annual Sum or Average | 465.18 | 1171.35 | 741.48 | 19.84 | 721.64 | 0.00 | 0.00 |
Minimum of Months | 0.82 | 643.99 | 200.48 | 0.00 | 200.48 | 0.00 | 0.00 |
Maximum of Months | 1112.17 | 1829.83 | 1347.28 | 84.48 | 1262.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 218.32 | 1052.52 | 377.56 | 151.66 | 225.89 | 0.00 | 0.00 |
February | 360.97 | 1003.91 | 563.00 | 207.98 | 355.03 | 0.00 | 0.00 |
March | 360.83 | 819.40 | 588.35 | 115.94 | 472.41 | 0.00 | 0.00 |
April | 1613.22 | 704.44 | 1579.76 | 742.34 | 837.42 | 0.00 | 0.00 |
May | 1644.27 | 617.32 | 1661.07 | 724.36 | 936.71 | 0.00 | 0.00 |
June | 1736.51 | 486.75 | 1644.16 | 656.66 | 987.50 | 0.00 | 0.00 |
July | 1849.74 | 455.78 | 1678.36 | 713.30 | 965.06 | 0.00 | 0.00 |
August | 1805.97 | 496.91 | 1589.88 | 759.63 | 830.25 | 0.00 | 0.00 |
September | 1567.88 | 636.03 | 1431.74 | 761.33 | 670.41 | 0.00 | 0.00 |
October | 592.66 | 820.35 | 691.12 | 286.42 | 404.70 | 0.00 | 0.00 |
November | 201.68 | 970.10 | 360.30 | 122.80 | 237.51 | 0.00 | 0.00 |
December | 131.92 | 1162.40 | 267.03 | 99.28 | 167.75 | 0.00 | 0.00 |
Annual Sum or Average | 1009.32 | 767.66 | 1037.53 | 445.71 | 591.81 | 0.00 | 0.00 |
Minimum of Months | 131.92 | 455.78 | 267.03 | 99.28 | 167.75 | 0.00 | 0.00 |
Maximum of Months | 1849.74 | 1162.40 | 1678.36 | 761.33 | 987.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1540.06 | 1535.75 | 1573.00 | 1018.27 | 554.74 | 0.00 | 0.00 |
February | 1927.23 | 1531.99 | 1921.14 | 1172.30 | 748.84 | 0.00 | 0.00 |
March | 970.74 | 1250.19 | 1187.78 | 345.83 | 841.95 | 0.00 | 0.00 |
April | 2768.72 | 1144.55 | 2466.52 | 1114.83 | 1351.69 | 0.00 | 0.00 |
May | 2115.98 | 993.31 | 2040.04 | 664.17 | 1375.88 | 0.00 | 0.00 |
June | 2030.73 | 768.07 | 1879.32 | 454.90 | 1424.42 | 0.00 | 0.00 |
July | 2358.75 | 728.73 | 2036.20 | 637.65 | 1398.55 | 0.00 | 0.00 |
August | 2921.86 | 808.93 | 2385.98 | 1073.30 | 1312.68 | 0.00 | 0.00 |
September | 3412.04 | 1038.70 | 2819.60 | 1651.76 | 1167.84 | 0.00 | 0.00 |
October | 2094.62 | 1279.09 | 1937.18 | 1132.19 | 804.99 | 0.00 | 0.00 |
November | 1344.79 | 1469.56 | 1373.46 | 835.51 | 537.95 | 0.00 | 0.00 |
December | 1033.72 | 1730.19 | 1088.59 | 697.46 | 391.13 | 0.00 | 0.00 |
Annual Sum or Average | 2040.43 | 1188.04 | 1889.51 | 896.35 | 993.15 | 0.00 | 0.00 |
Minimum of Months | 970.74 | 728.73 | 1088.59 | 345.83 | 391.13 | 0.00 | 0.00 |
Maximum of Months | 3412.04 | 1730.19 | 2819.60 | 1651.76 | 1424.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 220.42 | 1071.31 | 367.16 | 121.31 | 245.85 | 0.00 | 0.00 |
February | 508.49 | 1037.94 | 650.07 | 274.48 | 375.59 | 0.00 | 0.00 |
March | 363.68 | 832.48 | 587.80 | 112.45 | 475.35 | 0.00 | 0.00 |
April | 1403.94 | 739.90 | 1386.93 | 550.90 | 836.03 | 0.00 | 0.00 |
May | 1624.49 | 651.14 | 1627.19 | 661.67 | 965.52 | 0.00 | 0.00 |
June | 1893.81 | 521.99 | 1757.20 | 723.37 | 1033.83 | 0.00 | 0.00 |
July | 2015.68 | 489.07 | 1789.63 | 789.05 | 1000.58 | 0.00 | 0.00 |
August | 1710.84 | 533.15 | 1503.17 | 650.83 | 852.34 | 0.00 | 0.00 |
September | 1314.97 | 671.91 | 1205.94 | 540.77 | 665.17 | 0.00 | 0.00 |
October | 551.98 | 841.65 | 643.32 | 231.33 | 411.99 | 0.00 | 0.00 |
November | 207.90 | 997.38 | 348.14 | 101.63 | 246.52 | 0.00 | 0.00 |
December | 70.64 | 1203.37 | 197.06 | 41.58 | 155.48 | 0.00 | 0.00 |
Annual Sum or Average | 992.18 | 798.04 | 1006.37 | 400.11 | 606.26 | 0.00 | 0.00 |
Minimum of Months | 70.64 | 489.07 | 197.06 | 41.58 | 155.48 | 0.00 | 0.00 |
Maximum of Months | 2015.68 | 1203.37 | 1789.63 | 789.05 | 1033.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 17.58 | 1704.15 | 277.08 | 0.00 | 277.08 | 0.00 | 0.00 |
February | 55.75 | 1613.05 | 432.67 | 0.00 | 432.67 | 0.00 | 0.00 |
March | 187.17 | 1328.91 | 598.74 | 0.00 | 598.74 | 0.00 | 0.00 |
April | 578.27 | 1116.38 | 974.84 | 4.36 | 970.48 | 0.00 | 0.00 |
May | 727.20 | 902.22 | 1218.80 | 58.80 | 1160.00 | 0.00 | 0.00 |
June | 1059.00 | 714.96 | 1347.31 | 84.48 | 1262.82 | 0.00 | 0.00 |
July | 1080.21 | 659.62 | 1277.99 | 72.87 | 1205.13 | 0.00 | 0.00 |
August | 828.66 | 740.67 | 1004.57 | 15.74 | 988.83 | 0.00 | 0.00 |
September | 536.39 | 983.72 | 764.61 | 0.17 | 764.44 | 0.00 | 0.00 |
October | 185.97 | 1266.65 | 489.96 | 0.00 | 489.96 | 0.00 | 0.00 |
November | 26.94 | 1521.92 | 294.39 | 0.00 | 294.39 | 0.00 | 0.00 |
December | 0.83 | 1831.83 | 200.48 | 0.00 | 200.48 | 0.00 | 0.00 |
Annual Sum or Average | 442.29 | 1196.52 | 741.49 | 19.84 | 721.66 | 0.00 | 0.00 |
Minimum of Months | 0.83 | 659.62 | 200.48 | 0.00 | 200.48 | 0.00 | 0.00 |
Maximum of Months | 1080.21 | 1831.83 | 1347.31 | 84.48 | 1262.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 213.15 | 1065.69 | 377.56 | 151.67 | 225.89 | 0.00 | 0.00 |
February | 351.64 | 1018.82 | 563.01 | 207.98 | 355.03 | 0.00 | 0.00 |
March | 346.03 | 838.68 | 588.36 | 115.94 | 472.41 | 0.00 | 0.00 |
April | 1593.21 | 705.54 | 1579.79 | 742.35 | 837.44 | 0.00 | 0.00 |
May | 1626.72 | 612.35 | 1661.10 | 724.38 | 936.72 | 0.00 | 0.00 |
June | 1720.37 | 483.65 | 1644.18 | 656.67 | 987.51 | 0.00 | 0.00 |
July | 1837.63 | 447.94 | 1678.39 | 713.31 | 965.07 | 0.00 | 0.00 |
August | 1795.62 | 486.78 | 1589.90 | 759.64 | 830.26 | 0.00 | 0.00 |
September | 1560.65 | 618.81 | 1431.76 | 761.35 | 670.42 | 0.00 | 0.00 |
October | 588.55 | 808.49 | 691.13 | 286.42 | 404.71 | 0.00 | 0.00 |
November | 199.46 | 963.43 | 360.31 | 122.80 | 237.51 | 0.00 | 0.00 |
December | 130.39 | 1161.42 | 267.03 | 99.28 | 167.75 | 0.00 | 0.00 |
Annual Sum or Average | 999.28 | 766.39 | 1037.54 | 445.72 | 591.82 | 0.00 | 0.00 |
Minimum of Months | 130.39 | 447.94 | 267.03 | 99.28 | 167.75 | 0.00 | 0.00 |
Maximum of Months | 1837.63 | 1161.42 | 1678.39 | 761.35 | 987.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1515.34 | 1545.88 | 1573.07 | 1018.31 | 554.76 | 0.00 | 0.00 |
February | 1893.87 | 1534.89 | 1921.21 | 1172.35 | 748.86 | 0.00 | 0.00 |
March | 929.21 | 1286.93 | 1187.82 | 345.84 | 841.98 | 0.00 | 0.00 |
April | 2719.81 | 1158.04 | 2466.61 | 1114.88 | 1351.73 | 0.00 | 0.00 |
May | 2065.41 | 1013.30 | 2040.11 | 664.19 | 1375.92 | 0.00 | 0.00 |
June | 1982.47 | 788.55 | 1879.38 | 454.92 | 1424.46 | 0.00 | 0.00 |
July | 2324.53 | 733.63 | 2036.27 | 637.68 | 1398.59 | 0.00 | 0.00 |
August | 2896.46 | 797.56 | 2386.06 | 1073.34 | 1312.72 | 0.00 | 0.00 |
September | 3393.24 | 1004.16 | 2819.70 | 1651.83 | 1167.87 | 0.00 | 0.00 |
October | 2077.34 | 1249.91 | 1937.25 | 1132.24 | 805.02 | 0.00 | 0.00 |
November | 1326.29 | 1451.55 | 1373.51 | 835.54 | 537.97 | 0.00 | 0.00 |
December | 1017.34 | 1737.49 | 1088.63 | 697.49 | 391.14 | 0.00 | 0.00 |
Annual Sum or Average | 2008.98 | 1190.00 | 1889.58 | 896.39 | 993.19 | 0.00 | 0.00 |
Minimum of Months | 929.21 | 733.63 | 1088.63 | 345.84 | 391.14 | 0.00 | 0.00 |
Maximum of Months | 3393.24 | 1737.49 | 2819.70 | 1651.83 | 1424.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 214.20 | 1085.71 | 367.16 | 121.31 | 245.85 | 0.00 | 0.00 |
February | 497.22 | 1051.09 | 650.08 | 274.48 | 375.59 | 0.00 | 0.00 |
March | 346.24 | 853.41 | 587.81 | 112.45 | 475.36 | 0.00 | 0.00 |
April | 1379.33 | 750.80 | 1386.95 | 550.91 | 836.04 | 0.00 | 0.00 |
May | 1603.01 | 651.38 | 1627.22 | 661.68 | 965.53 | 0.00 | 0.00 |
June | 1876.06 | 517.95 | 1757.22 | 723.38 | 1033.84 | 0.00 | 0.00 |
July | 2000.81 | 482.92 | 1789.65 | 789.06 | 1000.59 | 0.00 | 0.00 |
August | 1697.87 | 526.12 | 1503.19 | 650.84 | 852.35 | 0.00 | 0.00 |
September | 1306.41 | 662.57 | 1205.95 | 540.78 | 665.18 | 0.00 | 0.00 |
October | 545.99 | 835.58 | 643.33 | 231.34 | 411.99 | 0.00 | 0.00 |
November | 204.43 | 993.51 | 348.15 | 101.63 | 246.52 | 0.00 | 0.00 |
December | 69.11 | 1205.29 | 197.06 | 41.58 | 155.48 | 0.00 | 0.00 |
Annual Sum or Average | 980.01 | 800.08 | 1006.38 | 400.12 | 606.26 | 0.00 | 0.00 |
Minimum of Months | 69.11 | 482.92 | 197.06 | 41.58 | 155.48 | 0.00 | 0.00 |
Maximum of Months | 2000.81 | 1205.29 | 1789.65 | 789.06 | 1033.84 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 61112990.53 | 0.430410E+10 | 0.742129E+09 | 0.00 | 0.742129E+09 | 0.00 | 0.00 |
February | 0.165292E+09 | 0.365241E+10 | 0.104672E+10 | 0.00 | 0.104672E+10 | 0.00 | 0.00 |
March | 0.547997E+09 | 0.333990E+10 | 0.160366E+10 | 0.00 | 0.160366E+10 | 0.00 | 0.00 |
April | 0.154678E+10 | 0.272780E+10 | 0.252679E+10 | 11308836.08 | 0.251548E+10 | 0.00 | 0.00 |
May | 0.201685E+10 | 0.227759E+10 | 0.326443E+10 | 0.157493E+09 | 0.310694E+10 | 0.00 | 0.00 |
June | 0.278069E+10 | 0.176726E+10 | 0.349222E+10 | 0.218985E+09 | 0.327323E+10 | 0.00 | 0.00 |
July | 0.292629E+10 | 0.168738E+10 | 0.342297E+10 | 0.195162E+09 | 0.322781E+10 | 0.00 | 0.00 |
August | 0.224787E+10 | 0.188591E+10 | 0.269063E+10 | 42155565.45 | 0.264848E+10 | 0.00 | 0.00 |
September | 0.143507E+10 | 0.239329E+10 | 0.198188E+10 | 438550.08 | 0.198144E+10 | 0.00 | 0.00 |
October | 0.552808E+09 | 0.313178E+10 | 0.131231E+10 | 0.00 | 0.131231E+10 | 0.00 | 0.00 |
November | 91500347.21 | 0.365520E+10 | 0.763066E+09 | 0.00 | 0.763066E+09 | 0.00 | 0.00 |
December | 7632916.82 | 0.460206E+10 | 0.536968E+09 | 0.00 | 0.536968E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.143799E+11 | 0.354247E+11 | 0.233838E+11 | 0.625543E+09 | 0.227582E+11 | 0.00 | 0.00 |
Minimum of Months | 7632916.82 | 0.168738E+10 | 0.536968E+09 | 0.00 | 0.536968E+09 | 0.00 | 0.00 |
Maximum of Months | 0.292629E+10 | 0.460206E+10 | 0.349222E+10 | 0.218985E+09 | 0.327323E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.591685E+09 | 0.269540E+10 | 0.101126E+10 | 0.406225E+09 | 0.605036E+09 | 0.00 | 0.00 |
February | 0.882458E+09 | 0.231550E+10 | 0.136203E+10 | 0.503146E+09 | 0.858889E+09 | 0.00 | 0.00 |
March | 0.961744E+09 | 0.211606E+10 | 0.157586E+10 | 0.310544E+09 | 0.126531E+10 | 0.00 | 0.00 |
April | 0.415801E+10 | 0.174038E+10 | 0.409481E+10 | 0.192418E+10 | 0.217063E+10 | 0.00 | 0.00 |
May | 0.438883E+10 | 0.155980E+10 | 0.444909E+10 | 0.194017E+10 | 0.250892E+10 | 0.00 | 0.00 |
June | 0.447501E+10 | 0.120170E+10 | 0.426172E+10 | 0.170209E+10 | 0.255963E+10 | 0.00 | 0.00 |
July | 0.493410E+10 | 0.115158E+10 | 0.449539E+10 | 0.191054E+10 | 0.258485E+10 | 0.00 | 0.00 |
August | 0.482128E+10 | 0.124926E+10 | 0.425840E+10 | 0.203462E+10 | 0.222378E+10 | 0.00 | 0.00 |
September | 0.406997E+10 | 0.152154E+10 | 0.371113E+10 | 0.197341E+10 | 0.173772E+10 | 0.00 | 0.00 |
October | 0.161286E+10 | 0.201596E+10 | 0.185112E+10 | 0.767154E+09 | 0.108397E+10 | 0.00 | 0.00 |
November | 0.541426E+09 | 0.232498E+10 | 0.933916E+09 | 0.318292E+09 | 0.615624E+09 | 0.00 | 0.00 |
December | 0.366386E+09 | 0.292369E+10 | 0.715217E+09 | 0.265908E+09 | 0.449309E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.318038E+11 | 0.228159E+11 | 0.327200E+11 | 0.140563E+11 | 0.186637E+11 | 0.00 | 0.00 |
Minimum of Months | 0.366386E+09 | 0.115158E+10 | 0.715217E+09 | 0.265908E+09 | 0.449309E+09 | 0.00 | 0.00 |
Maximum of Months | 0.493410E+10 | 0.292369E+10 | 0.449539E+10 | 0.203462E+10 | 0.258485E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.410621E+10 | 0.390387E+10 | 0.421330E+10 | 0.272744E+10 | 0.148586E+10 | 0.00 | 0.00 |
February | 0.463630E+10 | 0.349069E+10 | 0.464780E+10 | 0.283615E+10 | 0.181165E+10 | 0.00 | 0.00 |
March | 0.254624E+10 | 0.324100E+10 | 0.318146E+10 | 0.926297E+09 | 0.225516E+10 | 0.00 | 0.00 |
April | 0.708537E+10 | 0.284601E+10 | 0.639344E+10 | 0.288976E+10 | 0.350368E+10 | 0.00 | 0.00 |
May | 0.557380E+10 | 0.256302E+10 | 0.546423E+10 | 0.177898E+10 | 0.368526E+10 | 0.00 | 0.00 |
June | 0.516434E+10 | 0.194536E+10 | 0.487135E+10 | 0.117915E+10 | 0.369220E+10 | 0.00 | 0.00 |
July | 0.624587E+10 | 0.187198E+10 | 0.545395E+10 | 0.170796E+10 | 0.374598E+10 | 0.00 | 0.00 |
August | 0.777411E+10 | 0.203325E+10 | 0.639083E+10 | 0.287483E+10 | 0.351600E+10 | 0.00 | 0.00 |
September | 0.882533E+10 | 0.246059E+10 | 0.730867E+10 | 0.428154E+10 | 0.302713E+10 | 0.00 | 0.00 |
October | 0.561717E+10 | 0.311331E+10 | 0.518874E+10 | 0.303258E+10 | 0.215615E+10 | 0.00 | 0.00 |
November | 0.348651E+10 | 0.350136E+10 | 0.356014E+10 | 0.216572E+10 | 0.139442E+10 | 0.00 | 0.00 |
December | 0.276539E+10 | 0.437261E+10 | 0.291580E+10 | 0.186817E+10 | 0.104763E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.638266E+11 | 0.353430E+11 | 0.595897E+11 | 0.282686E+11 | 0.313211E+11 | 0.00 | 0.00 |
Minimum of Months | 0.254624E+10 | 0.187198E+10 | 0.291580E+10 | 0.926297E+09 | 0.104763E+10 | 0.00 | 0.00 |
Maximum of Months | 0.882533E+10 | 0.437261E+10 | 0.730867E+10 | 0.428154E+10 | 0.374598E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.589726E+09 | 0.274459E+10 | 0.983402E+09 | 0.324920E+09 | 0.658482E+09 | 0.00 | 0.00 |
February | 0.122727E+10 | 0.238683E+10 | 0.157266E+10 | 0.664029E+09 | 0.908634E+09 | 0.00 | 0.00 |
March | 0.957650E+09 | 0.214841E+10 | 0.157438E+10 | 0.301180E+09 | 0.127320E+10 | 0.00 | 0.00 |
April | 0.360348E+10 | 0.184276E+10 | 0.359498E+10 | 0.142796E+10 | 0.216702E+10 | 0.00 | 0.00 |
May | 0.432486E+10 | 0.164806E+10 | 0.435833E+10 | 0.177225E+10 | 0.258609E+10 | 0.00 | 0.00 |
June | 0.487893E+10 | 0.127792E+10 | 0.455471E+10 | 0.187500E+10 | 0.267971E+10 | 0.00 | 0.00 |
July | 0.537252E+10 | 0.123222E+10 | 0.479340E+10 | 0.211342E+10 | 0.267998E+10 | 0.00 | 0.00 |
August | 0.456253E+10 | 0.134012E+10 | 0.402613E+10 | 0.174320E+10 | 0.228293E+10 | 0.00 | 0.00 |
September | 0.341414E+10 | 0.161720E+10 | 0.312583E+10 | 0.140169E+10 | 0.172414E+10 | 0.00 | 0.00 |
October | 0.149628E+10 | 0.207902E+10 | 0.172310E+10 | 0.619618E+09 | 0.110348E+10 | 0.00 | 0.00 |
November | 0.547865E+09 | 0.239526E+10 | 0.902400E+09 | 0.263422E+09 | 0.638978E+09 | 0.00 | 0.00 |
December | 0.194658E+09 | 0.303400E+10 | 0.527811E+09 | 0.111380E+09 | 0.416431E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.311699E+11 | 0.237464E+11 | 0.317371E+11 | 0.126181E+11 | 0.191191E+11 | 0.00 | 0.00 |
Minimum of Months | 0.194658E+09 | 0.123222E+10 | 0.527811E+09 | 0.111380E+09 | 0.416431E+09 | 0.00 | 0.00 |
Maximum of Months | 0.537252E+10 | 0.303400E+10 | 0.479340E+10 | 0.211342E+10 | 0.267998E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 56313252.42 | 0.447374E+10 | 0.742112E+09 | 0.00 | 0.742112E+09 | 0.00 | 0.00 |
February | 0.157439E+09 | 0.380583E+10 | 0.104669E+10 | 0.00 | 0.104669E+10 | 0.00 | 0.00 |
March | 0.560034E+09 | 0.344532E+10 | 0.160363E+10 | 0.00 | 0.160363E+10 | 0.00 | 0.00 |
April | 0.162809E+10 | 0.275221E+10 | 0.252673E+10 | 11308503.69 | 0.251542E+10 | 0.00 | 0.00 |
May | 0.208790E+10 | 0.232241E+10 | 0.326436E+10 | 0.157488E+09 | 0.310687E+10 | 0.00 | 0.00 |
June | 0.285330E+10 | 0.179600E+10 | 0.349214E+10 | 0.218978E+09 | 0.327316E+10 | 0.00 | 0.00 |
July | 0.297883E+10 | 0.172486E+10 | 0.342290E+10 | 0.195156E+09 | 0.322775E+10 | 0.00 | 0.00 |
August | 0.229636E+10 | 0.192658E+10 | 0.269058E+10 | 42154326.39 | 0.264842E+10 | 0.00 | 0.00 |
September | 0.144497E+10 | 0.249645E+10 | 0.198184E+10 | 438537.19 | 0.198140E+10 | 0.00 | 0.00 |
October | 0.529119E+09 | 0.335853E+10 | 0.131228E+10 | 0.00 | 0.131228E+10 | 0.00 | 0.00 |
November | 75457130.95 | 0.393686E+10 | 0.763049E+09 | 0.00 | 0.763049E+09 | 0.00 | 0.00 |
December | 2185617.54 | 0.490101E+10 | 0.536955E+09 | 0.00 | 0.536955E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.146700E+11 | 0.369398E+11 | 0.233833E+11 | 0.625524E+09 | 0.227577E+11 | 0.00 | 0.00 |
Minimum of Months | 2185617.54 | 0.172486E+10 | 0.536955E+09 | 0.00 | 0.536955E+09 | 0.00 | 0.00 |
Maximum of Months | 0.297883E+10 | 0.490101E+10 | 0.349214E+10 | 0.218978E+09 | 0.327316E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.584737E+09 | 0.281907E+10 | 0.101124E+10 | 0.406217E+09 | 0.605027E+09 | 0.00 | 0.00 |
February | 0.873249E+09 | 0.242867E+10 | 0.136201E+10 | 0.503136E+09 | 0.858877E+09 | 0.00 | 0.00 |
March | 0.966447E+09 | 0.219468E+10 | 0.157583E+10 | 0.310538E+09 | 0.126530E+10 | 0.00 | 0.00 |
April | 0.418147E+10 | 0.182590E+10 | 0.409475E+10 | 0.192414E+10 | 0.217061E+10 | 0.00 | 0.00 |
May | 0.440401E+10 | 0.165344E+10 | 0.444902E+10 | 0.194013E+10 | 0.250888E+10 | 0.00 | 0.00 |
June | 0.450102E+10 | 0.126166E+10 | 0.426166E+10 | 0.170206E+10 | 0.255960E+10 | 0.00 | 0.00 |
July | 0.495434E+10 | 0.122077E+10 | 0.449532E+10 | 0.191050E+10 | 0.258482E+10 | 0.00 | 0.00 |
August | 0.483711E+10 | 0.133092E+10 | 0.425833E+10 | 0.203458E+10 | 0.222375E+10 | 0.00 | 0.00 |
September | 0.406394E+10 | 0.164860E+10 | 0.371107E+10 | 0.197337E+10 | 0.173770E+10 | 0.00 | 0.00 |
October | 0.158739E+10 | 0.219723E+10 | 0.185110E+10 | 0.767139E+09 | 0.108396E+10 | 0.00 | 0.00 |
November | 0.522755E+09 | 0.251451E+10 | 0.933901E+09 | 0.318286E+09 | 0.615615E+09 | 0.00 | 0.00 |
December | 0.353325E+09 | 0.311338E+10 | 0.715205E+09 | 0.265902E+09 | 0.449303E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.318298E+11 | 0.242088E+11 | 0.327194E+11 | 0.140560E+11 | 0.186634E+11 | 0.00 | 0.00 |
Minimum of Months | 0.353325E+09 | 0.122077E+10 | 0.715205E+09 | 0.265902E+09 | 0.449303E+09 | 0.00 | 0.00 |
Maximum of Months | 0.495434E+10 | 0.311338E+10 | 0.449532E+10 | 0.203458E+10 | 0.258482E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.412490E+10 | 0.411336E+10 | 0.421314E+10 | 0.272733E+10 | 0.148580E+10 | 0.00 | 0.00 |
February | 0.466235E+10 | 0.370619E+10 | 0.464762E+10 | 0.283603E+10 | 0.181158E+10 | 0.00 | 0.00 |
March | 0.260003E+10 | 0.334851E+10 | 0.318134E+10 | 0.926259E+09 | 0.225508E+10 | 0.00 | 0.00 |
April | 0.717651E+10 | 0.296668E+10 | 0.639321E+10 | 0.288964E+10 | 0.350357E+10 | 0.00 | 0.00 |
May | 0.566745E+10 | 0.266048E+10 | 0.546405E+10 | 0.177890E+10 | 0.368514E+10 | 0.00 | 0.00 |
June | 0.526364E+10 | 0.199085E+10 | 0.487119E+10 | 0.117910E+10 | 0.369209E+10 | 0.00 | 0.00 |
July | 0.631766E+10 | 0.195183E+10 | 0.545376E+10 | 0.170789E+10 | 0.374587E+10 | 0.00 | 0.00 |
August | 0.782592E+10 | 0.216665E+10 | 0.639060E+10 | 0.287471E+10 | 0.351589E+10 | 0.00 | 0.00 |
September | 0.884401E+10 | 0.269232E+10 | 0.730840E+10 | 0.428137E+10 | 0.302703E+10 | 0.00 | 0.00 |
October | 0.561022E+10 | 0.342592E+10 | 0.518854E+10 | 0.303246E+10 | 0.215608E+10 | 0.00 | 0.00 |
November | 0.348570E+10 | 0.380910E+10 | 0.356000E+10 | 0.216564E+10 | 0.139437E+10 | 0.00 | 0.00 |
December | 0.276872E+10 | 0.463414E+10 | 0.291568E+10 | 0.186809E+10 | 0.104759E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.643471E+11 | 0.374660E+11 | 0.595875E+11 | 0.282674E+11 | 0.313201E+11 | 0.00 | 0.00 |
Minimum of Months | 0.260003E+10 | 0.195183E+10 | 0.291568E+10 | 0.926259E+09 | 0.104759E+10 | 0.00 | 0.00 |
Maximum of Months | 0.884401E+10 | 0.463414E+10 | 0.730840E+10 | 0.428137E+10 | 0.374587E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.590372E+09 | 0.286939E+10 | 0.983389E+09 | 0.324915E+09 | 0.658474E+09 | 0.00 | 0.00 |
February | 0.123014E+10 | 0.251099E+10 | 0.157264E+10 | 0.664018E+09 | 0.908623E+09 | 0.00 | 0.00 |
March | 0.974084E+09 | 0.222972E+10 | 0.157436E+10 | 0.301175E+09 | 0.127319E+10 | 0.00 | 0.00 |
April | 0.363901E+10 | 0.191782E+10 | 0.359493E+10 | 0.142793E+10 | 0.216700E+10 | 0.00 | 0.00 |
May | 0.435102E+10 | 0.174400E+10 | 0.435828E+10 | 0.177222E+10 | 0.258606E+10 | 0.00 | 0.00 |
June | 0.490875E+10 | 0.135299E+10 | 0.455465E+10 | 0.187497E+10 | 0.267968E+10 | 0.00 | 0.00 |
July | 0.539880E+10 | 0.130992E+10 | 0.479333E+10 | 0.211339E+10 | 0.267995E+10 | 0.00 | 0.00 |
August | 0.458232E+10 | 0.142799E+10 | 0.402608E+10 | 0.174317E+10 | 0.228291E+10 | 0.00 | 0.00 |
September | 0.340841E+10 | 0.174158E+10 | 0.312579E+10 | 0.140167E+10 | 0.172412E+10 | 0.00 | 0.00 |
October | 0.147843E+10 | 0.225426E+10 | 0.172307E+10 | 0.619608E+09 | 0.110347E+10 | 0.00 | 0.00 |
November | 0.538864E+09 | 0.258521E+10 | 0.902388E+09 | 0.263417E+09 | 0.638970E+09 | 0.00 | 0.00 |
December | 0.189193E+09 | 0.322311E+10 | 0.527804E+09 | 0.111378E+09 | 0.416427E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.312894E+11 | 0.251670E+11 | 0.317367E+11 | 0.126179E+11 | 0.191189E+11 | 0.00 | 0.00 |
Minimum of Months | 0.189193E+09 | 0.130992E+10 | 0.527804E+09 | 0.111378E+09 | 0.416427E+09 | 0.00 | 0.00 |
Maximum of Months | 0.539880E+10 | 0.322311E+10 | 0.479333E+10 | 0.211339E+10 | 0.267995E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 47081820.72 | 0.456438E+10 | 0.742129E+09 | 0.00 | 0.742129E+09 | 0.00 | 0.00 |
February | 0.134861E+09 | 0.390229E+10 | 0.104672E+10 | 0.00 | 0.104672E+10 | 0.00 | 0.00 |
March | 0.501327E+09 | 0.355936E+10 | 0.160366E+10 | 0.00 | 0.160366E+10 | 0.00 | 0.00 |
April | 0.149887E+10 | 0.289367E+10 | 0.252679E+10 | 11308836.08 | 0.251548E+10 | 0.00 | 0.00 |
May | 0.194773E+10 | 0.241650E+10 | 0.326443E+10 | 0.157493E+09 | 0.310694E+10 | 0.00 | 0.00 |
June | 0.274492E+10 | 0.185317E+10 | 0.349222E+10 | 0.218985E+09 | 0.327323E+10 | 0.00 | 0.00 |
July | 0.289324E+10 | 0.176674E+10 | 0.342297E+10 | 0.195162E+09 | 0.322781E+10 | 0.00 | 0.00 |
August | 0.221949E+10 | 0.198381E+10 | 0.269063E+10 | 42155565.45 | 0.264848E+10 | 0.00 | 0.00 |
September | 0.139033E+10 | 0.254981E+10 | 0.198188E+10 | 438550.08 | 0.198144E+10 | 0.00 | 0.00 |
October | 0.498105E+09 | 0.339260E+10 | 0.131231E+10 | 0.00 | 0.131231E+10 | 0.00 | 0.00 |
November | 69841079.70 | 0.394481E+10 | 0.763066E+09 | 0.00 | 0.763066E+09 | 0.00 | 0.00 |
December | 2226315.89 | 0.490637E+10 | 0.536968E+09 | 0.00 | 0.536968E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.139480E+11 | 0.377335E+11 | 0.233838E+11 | 0.625543E+09 | 0.227582E+11 | 0.00 | 0.00 |
Minimum of Months | 2226315.89 | 0.176674E+10 | 0.536968E+09 | 0.00 | 0.536968E+09 | 0.00 | 0.00 |
Maximum of Months | 0.289324E+10 | 0.490637E+10 | 0.349222E+10 | 0.218985E+09 | 0.327323E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.570900E+09 | 0.285434E+10 | 0.101126E+10 | 0.406225E+09 | 0.605036E+09 | 0.00 | 0.00 |
February | 0.850684E+09 | 0.246473E+10 | 0.136203E+10 | 0.503146E+09 | 0.858889E+09 | 0.00 | 0.00 |
March | 0.926807E+09 | 0.224633E+10 | 0.157586E+10 | 0.310544E+09 | 0.126531E+10 | 0.00 | 0.00 |
April | 0.412960E+10 | 0.182876E+10 | 0.409481E+10 | 0.192418E+10 | 0.217063E+10 | 0.00 | 0.00 |
May | 0.435702E+10 | 0.164011E+10 | 0.444909E+10 | 0.194017E+10 | 0.250892E+10 | 0.00 | 0.00 |
June | 0.445919E+10 | 0.125361E+10 | 0.426172E+10 | 0.170209E+10 | 0.255963E+10 | 0.00 | 0.00 |
July | 0.492191E+10 | 0.119975E+10 | 0.449539E+10 | 0.191054E+10 | 0.258485E+10 | 0.00 | 0.00 |
August | 0.480938E+10 | 0.130379E+10 | 0.425840E+10 | 0.203462E+10 | 0.222378E+10 | 0.00 | 0.00 |
September | 0.404520E+10 | 0.160396E+10 | 0.371113E+10 | 0.197341E+10 | 0.173772E+10 | 0.00 | 0.00 |
October | 0.157638E+10 | 0.216547E+10 | 0.185112E+10 | 0.767154E+09 | 0.108397E+10 | 0.00 | 0.00 |
November | 0.517008E+09 | 0.249722E+10 | 0.933916E+09 | 0.318292E+09 | 0.615624E+09 | 0.00 | 0.00 |
December | 0.349248E+09 | 0.311075E+10 | 0.715217E+09 | 0.265908E+09 | 0.449309E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.315133E+11 | 0.241688E+11 | 0.327200E+11 | 0.140563E+11 | 0.186637E+11 | 0.00 | 0.00 |
Minimum of Months | 0.349248E+09 | 0.119975E+10 | 0.715217E+09 | 0.265908E+09 | 0.449309E+09 | 0.00 | 0.00 |
Maximum of Months | 0.492191E+10 | 0.311075E+10 | 0.449539E+10 | 0.203462E+10 | 0.258485E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.405869E+10 | 0.414047E+10 | 0.421330E+10 | 0.272744E+10 | 0.148586E+10 | 0.00 | 0.00 |
February | 0.458165E+10 | 0.371321E+10 | 0.464780E+10 | 0.283615E+10 | 0.181165E+10 | 0.00 | 0.00 |
March | 0.248881E+10 | 0.344692E+10 | 0.318146E+10 | 0.926297E+09 | 0.225516E+10 | 0.00 | 0.00 |
April | 0.704974E+10 | 0.300164E+10 | 0.639344E+10 | 0.288976E+10 | 0.350368E+10 | 0.00 | 0.00 |
May | 0.553199E+10 | 0.271401E+10 | 0.546423E+10 | 0.177898E+10 | 0.368526E+10 | 0.00 | 0.00 |
June | 0.513856E+10 | 0.204392E+10 | 0.487135E+10 | 0.117915E+10 | 0.369220E+10 | 0.00 | 0.00 |
July | 0.622603E+10 | 0.196496E+10 | 0.545395E+10 | 0.170796E+10 | 0.374598E+10 | 0.00 | 0.00 |
August | 0.775788E+10 | 0.213618E+10 | 0.639083E+10 | 0.287483E+10 | 0.351600E+10 | 0.00 | 0.00 |
September | 0.879528E+10 | 0.260279E+10 | 0.730867E+10 | 0.428154E+10 | 0.302713E+10 | 0.00 | 0.00 |
October | 0.556395E+10 | 0.334776E+10 | 0.518874E+10 | 0.303258E+10 | 0.215615E+10 | 0.00 | 0.00 |
November | 0.343774E+10 | 0.376241E+10 | 0.356014E+10 | 0.216572E+10 | 0.139442E+10 | 0.00 | 0.00 |
December | 0.272485E+10 | 0.465369E+10 | 0.291580E+10 | 0.186817E+10 | 0.104763E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.633552E+11 | 0.375280E+11 | 0.595897E+11 | 0.282686E+11 | 0.313211E+11 | 0.00 | 0.00 |
Minimum of Months | 0.248881E+10 | 0.196496E+10 | 0.291580E+10 | 0.926297E+09 | 0.104763E+10 | 0.00 | 0.00 |
Maximum of Months | 0.879528E+10 | 0.465369E+10 | 0.730867E+10 | 0.428154E+10 | 0.374598E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.573718E+09 | 0.290796E+10 | 0.983402E+09 | 0.324920E+09 | 0.658482E+09 | 0.00 | 0.00 |
February | 0.120288E+10 | 0.254279E+10 | 0.157266E+10 | 0.664029E+09 | 0.908634E+09 | 0.00 | 0.00 |
March | 0.927364E+09 | 0.228576E+10 | 0.157438E+10 | 0.301180E+09 | 0.127320E+10 | 0.00 | 0.00 |
April | 0.357522E+10 | 0.194607E+10 | 0.359498E+10 | 0.142796E+10 | 0.216702E+10 | 0.00 | 0.00 |
May | 0.429350E+10 | 0.174467E+10 | 0.435833E+10 | 0.177225E+10 | 0.258609E+10 | 0.00 | 0.00 |
June | 0.486274E+10 | 0.134253E+10 | 0.455471E+10 | 0.187500E+10 | 0.267971E+10 | 0.00 | 0.00 |
July | 0.535896E+10 | 0.129346E+10 | 0.479340E+10 | 0.211342E+10 | 0.267998E+10 | 0.00 | 0.00 |
August | 0.454759E+10 | 0.140916E+10 | 0.402613E+10 | 0.174320E+10 | 0.228293E+10 | 0.00 | 0.00 |
September | 0.338621E+10 | 0.171739E+10 | 0.312583E+10 | 0.140169E+10 | 0.172414E+10 | 0.00 | 0.00 |
October | 0.146237E+10 | 0.223802E+10 | 0.172310E+10 | 0.619618E+09 | 0.110348E+10 | 0.00 | 0.00 |
November | 0.529876E+09 | 0.257517E+10 | 0.902400E+09 | 0.263422E+09 | 0.638978E+09 | 0.00 | 0.00 |
December | 0.185107E+09 | 0.322824E+10 | 0.527811E+09 | 0.111380E+09 | 0.416431E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.309055E+11 | 0.252312E+11 | 0.317371E+11 | 0.126181E+11 | 0.191191E+11 | 0.00 | 0.00 |
Minimum of Months | 0.185107E+09 | 0.129346E+10 | 0.527811E+09 | 0.111380E+09 | 0.416431E+09 | 0.00 | 0.00 |
Maximum of Months | 0.535896E+10 | 0.322824E+10 | 0.479340E+10 | 0.211342E+10 | 0.267998E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.531868E+10 | -0.459583E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -722844067.5 | 58.99 | 0.00 | 0.00 |
February | 0.484915E+10 | -0.420482E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -644325193.3 | 58.98 | 0.00 | 0.00 |
March | 0.565537E+10 | -0.494451E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -710861696.8 | 58.98 | 0.00 | 0.00 |
April | 0.503838E+10 | -0.436493E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -673454473.6 | 58.98 | 0.00 | 0.00 |
May | 0.525072E+10 | -0.455725E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -693464584.6 | 58.98 | 0.00 | 0.00 |
June | 0.507389E+10 | -0.440500E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668892828.1 | 58.98 | 0.00 | 0.00 |
July | 0.475210E+10 | -0.406270E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689397010.4 | 58.98 | 0.00 | 0.00 |
August | 0.514892E+10 | -0.445776E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691159264.2 | 58.99 | 0.00 | 0.00 |
September | 0.471246E+10 | -0.404360E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668858489.6 | 58.98 | 0.00 | 0.00 |
October | 0.496468E+10 | -0.426522E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -699459370.2 | 58.98 | 0.00 | 0.00 |
November | 0.499948E+10 | -0.431333E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -686150166.8 | 58.99 | 0.00 | 0.00 |
December | 0.510484E+10 | -0.438413E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -720712287.4 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.608687E+11 | -0.525991E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.826958E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.471246E+10 | -0.494451E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -722844067.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.565537E+10 | -0.404360E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -644325193.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.52 | 0.48 | 01-JAN-08:39 | 4208.62 | 36.33 | 191.17 | 223.50 | 3536.34 | 37.60 | 190.17 | 196.50 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 6037.01 | 36.03 | 213.67 | 246.50 | 2883.77 | 31.92 | 201.83 | 224.67 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 4445.81 | 31.10 | 182.33 | 312.00 | 1272.08 | 21.67 | 184.50 | 271.67 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:10 | 2793.51 | 19.73 | 36.00 | 356.00 | 1587.34 | 21.96 | 261.00 | 332.67 |
May | 417.17 | 0.51 | 0.48 | 01-MAY-06:00 | 2216.40 | 19.35 | 2.17 | 411.67 | 1249.60 | 21.57 | 272.67 | 377.50 |
June | 410.67 | 0.50 | 0.48 | 01-JUN-05:00 | 2153.48 | 19.65 | 0.67 | 414.00 | 1199.94 | 21.85 | 283.00 | 375.67 |
July | 429.00 | 0.51 | 0.48 | 01-JUL-05:00 | 2148.77 | 19.41 | 4.17 | 422.67 | 1228.21 | 21.63 | 282.17 | 385.50 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:19 | 2494.94 | 19.38 | 27.83 | 383.17 | 1446.62 | 21.63 | 274.67 | 351.17 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:49 | 3700.09 | 21.41 | 63.00 | 332.50 | 1761.89 | 22.16 | 239.83 | 306.67 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:49 | 7635.26 | 35.17 | 216.83 | 281.17 | 2274.63 | 24.69 | 194.50 | 244.00 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 4846.45 | 36.17 | 167.17 | 218.50 | 4049.80 | 37.51 | 168.00 | 176.17 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:50 | 4075.23 | 37.21 | 128.67 | 185.17 | 3434.09 | 38.57 | 128.67 | 135.67 |
Annual Sum or Average | 3515.67 | 0.51 | 3475.56 | 24.87 | 1233.67 | 3786.83 | 1863.17 | 24.87 | 2681.00 | 3377.83 | ||
Minimum of Months | 131.67 | 0.50 | 0.48 | 2148.77 | 19.35 | 0.67 | 185.17 | 1199.94 | 21.57 | 128.67 | 135.67 | |
Maximum of Months | 429.00 | 0.52 | 0.48 | 7635.26 | 37.21 | 216.83 | 422.67 | 4049.80 | 38.57 | 283.00 | 385.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.54 | 0.48 | 01-JAN-08:39 | 1530.72 | 23.39 | 82.67 | 211.00 | 913.61 | 23.98 | 83.00 | 149.17 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 1816.62 | 21.45 | 62.33 | 239.00 | 1040.48 | 24.09 | 88.33 | 200.83 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 2093.68 | 22.01 | 71.33 | 306.00 | 943.02 | 22.79 | 72.83 | 256.17 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:10 | 3889.57 | 22.98 | 107.17 | 364.33 | 2287.61 | 25.18 | 145.17 | 343.17 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:40 | 4027.99 | 23.02 | 133.50 | 423.33 | 1816.47 | 22.90 | 87.67 | 386.50 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:49 | 4046.53 | 22.92 | 129.67 | 421.00 | 1858.62 | 23.70 | 86.83 | 391.33 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-04:49 | 3960.86 | 23.16 | 139.67 | 432.67 | 1809.67 | 23.75 | 95.33 | 403.33 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3821.97 | 23.50 | 128.00 | 391.67 | 1692.54 | 23.22 | 95.17 | 364.00 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 3613.25 | 23.79 | 109.33 | 339.17 | 2004.81 | 24.62 | 135.33 | 310.17 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-06:40 | 2819.03 | 23.23 | 82.33 | 274.83 | 1300.37 | 23.95 | 104.50 | 219.67 |
November | 171.33 | 0.53 | 0.48 | 01-NOV-11:50 | 1530.64 | 21.55 | 55.83 | 205.83 | 899.29 | 23.93 | 82.00 | 139.33 |
December | 131.67 | 0.52 | 0.48 | 02-DEC-08:50 | 1319.39 | 23.96 | 53.00 | 168.50 | 923.32 | 26.09 | 73.17 | 102.17 |
Annual Sum or Average | 3515.67 | 0.51 | 3247.08 | 22.99 | 1154.83 | 3777.33 | 1608.70 | 23.90 | 1149.33 | 3265.83 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1319.39 | 21.45 | 53.00 | 168.50 | 899.29 | 22.79 | 72.83 | 102.17 | |
Maximum of Months | 429.00 | 0.54 | 0.48 | 4046.53 | 23.96 | 139.67 | 432.67 | 2287.61 | 26.09 | 145.17 | 403.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.58 | 0.48 | 01-JAN-10:30 | 554.12 | 14.71 | 0.00 | 190.50 | 323.28 | 17.10 | 0.00 | 82.50 |
February | 217.00 | 0.54 | 0.48 | 01-FEB-11:00 | 734.49 | 16.47 | 0.00 | 226.00 | 431.14 | 18.76 | 0.00 | 148.67 |
March | 215.50 | 0.53 | 0.48 | 01-MAR-11:39 | 907.96 | 17.22 | 0.00 | 303.00 | 494.08 | 19.28 | 5.67 | 228.67 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:19 | 1201.11 | 18.95 | 0.00 | 361.83 | 717.71 | 21.07 | 137.00 | 333.17 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:00 | 1425.50 | 20.82 | 50.50 | 426.83 | 821.77 | 22.94 | 237.00 | 402.50 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1624.14 | 21.94 | 91.17 | 429.33 | 934.99 | 24.00 | 270.50 | 405.67 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 1508.95 | 21.72 | 84.17 | 440.00 | 888.80 | 23.80 | 280.33 | 419.00 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:00 | 1221.51 | 18.99 | 0.67 | 392.67 | 740.17 | 21.18 | 171.67 | 362.17 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:00 | 982.17 | 18.32 | 0.00 | 327.50 | 616.69 | 20.59 | 46.33 | 287.17 |
October | 234.00 | 0.53 | 0.48 | 01-OCT-07:40 | 832.13 | 17.14 | 0.00 | 264.83 | 499.68 | 19.42 | 1.33 | 184.17 |
November | 171.33 | 0.56 | 0.48 | 01-NOV-12:09 | 614.41 | 15.49 | 0.00 | 185.33 | 360.61 | 17.84 | 0.00 | 84.17 |
December | 131.67 | 0.59 | 0.48 | 02-DEC-10:50 | 519.92 | 14.90 | 0.00 | 138.67 | 307.45 | 17.38 | 0.00 | 45.00 |
Annual Sum or Average | 3515.67 | 0.52 | 1134.54 | 18.87 | 226.50 | 3686.50 | 668.51 | 21.05 | 1149.83 | 2982.83 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 519.92 | 14.71 | 0.00 | 138.67 | 307.45 | 17.10 | 0.00 | 45.00 | |
Maximum of Months | 429.00 | 0.59 | 0.48 | 1624.14 | 21.94 | 91.17 | 440.00 | 934.99 | 24.00 | 280.33 | 419.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.55 | 0.48 | 01-JAN-10:20 | 1336.06 | 20.45 | 64.50 | 204.83 | 795.09 | 23.11 | 79.00 | 151.17 |
February | 217.00 | 0.53 | 0.48 | 01-FEB-11:39 | 2119.02 | 21.05 | 58.33 | 234.50 | 1172.43 | 22.94 | 84.67 | 187.00 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 1980.87 | 21.90 | 72.33 | 305.67 | 1077.37 | 22.90 | 78.17 | 254.50 |
April | 359.67 | 0.51 | 0.48 | 01-APR-08:09 | 3755.60 | 21.92 | 102.33 | 356.00 | 1706.18 | 22.00 | 93.67 | 330.50 |
May | 417.17 | 0.51 | 0.48 | 01-MAY-07:19 | 3375.30 | 19.70 | 73.83 | 413.67 | 1892.62 | 21.34 | 51.67 | 385.00 |
June | 410.67 | 0.50 | 0.48 | 01-JUN-06:10 | 3936.43 | 18.78 | 50.67 | 420.50 | 1766.12 | 19.75 | 6.17 | 383.17 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-06:10 | 3906.55 | 18.67 | 53.33 | 428.67 | 1796.12 | 19.70 | 5.83 | 396.67 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:30 | 3467.51 | 20.60 | 86.83 | 383.00 | 1950.45 | 21.94 | 83.33 | 352.83 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-08:09 | 3357.63 | 22.27 | 96.83 | 325.33 | 1859.71 | 23.56 | 109.33 | 300.33 |
October | 234.00 | 0.52 | 0.48 | 01-OCT-07:49 | 2657.70 | 22.64 | 80.17 | 270.67 | 1212.51 | 23.19 | 101.50 | 214.33 |
November | 171.33 | 0.54 | 0.48 | 01-NOV-11:50 | 1492.00 | 20.81 | 51.67 | 199.67 | 817.69 | 22.79 | 72.83 | 135.00 |
December | 131.67 | 0.56 | 0.48 | 02-DEC-10:09 | 1087.91 | 20.39 | 37.67 | 162.33 | 571.84 | 20.90 | 41.17 | 87.33 |
Annual Sum or Average | 3515.67 | 0.52 | 3051.55 | 20.58 | 828.50 | 3704.83 | 1547.73 | 21.77 | 807.33 | 3177.83 | ||
Minimum of Months | 131.67 | 0.50 | 0.48 | 1087.91 | 18.67 | 37.67 | 162.33 | 571.84 | 19.70 | 5.83 | 87.33 | |
Maximum of Months | 429.00 | 0.56 | 0.48 | 3936.43 | 22.64 | 102.33 | 428.67 | 1950.45 | 23.56 | 109.33 | 396.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.52 | 0.48 | 01-JAN-08:39 | 4022.30 | 34.12 | 177.50 | 221.17 | 3427.05 | 37.37 | 190.17 | 194.83 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 5875.92 | 35.81 | 213.67 | 246.00 | 2760.33 | 30.57 | 141.83 | 222.33 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 4332.01 | 30.32 | 181.50 | 310.50 | 1196.13 | 18.72 | 8.83 | 267.00 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:10 | 2652.75 | 16.03 | 0.00 | 355.17 | 1485.74 | 19.55 | 48.17 | 329.50 |
May | 417.17 | 0.51 | 0.48 | 01-MAY-06:00 | 2115.63 | 15.70 | 0.00 | 409.67 | 1180.49 | 19.17 | 27.17 | 373.33 |
June | 410.67 | 0.50 | 0.48 | 01-JUN-05:00 | 2061.44 | 16.02 | 0.00 | 412.33 | 1139.17 | 19.46 | 21.17 | 372.00 |
July | 429.00 | 0.51 | 0.48 | 01-JUL-05:00 | 2051.77 | 15.81 | 0.00 | 420.83 | 1162.25 | 19.29 | 29.17 | 382.83 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:19 | 2369.54 | 15.70 | 0.00 | 381.83 | 1356.48 | 19.22 | 48.83 | 348.50 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:49 | 3534.31 | 17.91 | 29.50 | 330.17 | 1636.33 | 19.64 | 54.50 | 304.33 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:49 | 7453.51 | 34.73 | 216.67 | 279.83 | 2141.23 | 22.12 | 49.50 | 240.00 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 4684.71 | 35.93 | 167.00 | 216.50 | 3935.95 | 37.30 | 167.67 | 173.50 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:50 | 3910.28 | 36.41 | 126.00 | 182.33 | 3320.41 | 38.33 | 128.67 | 132.83 |
Annual Sum or Average | 3515.67 | 0.51 | 3343.11 | 22.19 | 1111.83 | 3766.33 | 1770.17 | 22.79 | 915.67 | 3341.00 | ||
Minimum of Months | 131.67 | 0.50 | 0.48 | 2051.77 | 15.70 | 0.00 | 182.33 | 1139.17 | 18.72 | 8.83 | 132.83 | |
Maximum of Months | 429.00 | 0.52 | 0.48 | 7453.51 | 36.41 | 216.67 | 420.83 | 3935.95 | 38.33 | 190.17 | 382.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.54 | 0.48 | 01-JAN-08:39 | 1487.57 | 22.96 | 82.67 | 209.67 | 881.16 | 23.76 | 78.83 | 145.00 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 1758.67 | 20.95 | 62.33 | 237.33 | 995.82 | 23.86 | 83.67 | 194.33 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 2034.97 | 21.55 | 71.33 | 304.00 | 899.82 | 22.58 | 65.00 | 251.17 |
April | 359.67 | 0.51 | 0.48 | 01-APR-06:10 | 3775.71 | 22.53 | 107.17 | 363.33 | 2152.60 | 23.82 | 112.83 | 337.33 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3929.29 | 22.58 | 133.33 | 422.50 | 1739.65 | 22.73 | 76.17 | 382.00 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:49 | 3946.17 | 22.48 | 129.50 | 420.50 | 1783.85 | 23.50 | 81.00 | 389.00 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-04:49 | 3853.01 | 22.59 | 137.67 | 431.00 | 1724.21 | 22.97 | 80.00 | 400.00 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3672.77 | 21.70 | 109.83 | 389.33 | 1613.37 | 23.04 | 86.33 | 360.67 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 3510.97 | 23.34 | 109.33 | 337.50 | 1916.83 | 24.26 | 123.83 | 307.50 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-06:49 | 2742.05 | 22.78 | 82.33 | 272.33 | 1203.93 | 22.70 | 88.83 | 213.67 |
November | 171.33 | 0.53 | 0.48 | 01-NOV-11:00 | 1481.84 | 21.06 | 55.67 | 203.83 | 863.49 | 23.70 | 77.83 | 135.50 |
December | 131.67 | 0.52 | 0.48 | 02-DEC-08:50 | 1266.52 | 23.01 | 50.50 | 165.00 | 890.68 | 25.88 | 69.00 | 99.00 |
Annual Sum or Average | 3515.67 | 0.51 | 3153.14 | 22.35 | 1131.67 | 3756.33 | 1532.63 | 23.42 | 1023.33 | 3215.17 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1266.52 | 20.95 | 50.50 | 165.00 | 863.49 | 22.58 | 65.00 | 99.00 | |
Maximum of Months | 429.00 | 0.54 | 0.48 | 3946.17 | 23.34 | 137.67 | 431.00 | 2152.60 | 25.88 | 123.83 | 400.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.59 | 0.48 | 01-JAN-10:30 | 532.05 | 11.00 | 0.00 | 186.67 | 310.95 | 14.60 | 0.00 | 74.83 |
February | 217.00 | 0.54 | 0.48 | 01-FEB-12:09 | 706.36 | 12.88 | 0.00 | 223.17 | 415.56 | 16.43 | 0.00 | 142.17 |
March | 215.50 | 0.53 | 0.48 | 01-MAR-11:39 | 876.18 | 13.47 | 0.00 | 300.17 | 475.66 | 16.83 | 0.00 | 219.33 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:19 | 1158.20 | 15.80 | 0.00 | 360.67 | 694.42 | 19.26 | 14.83 | 329.33 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:00 | 1375.38 | 17.74 | 38.00 | 425.17 | 793.66 | 21.03 | 83.67 | 399.00 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1566.83 | 18.93 | 56.83 | 427.67 | 902.13 | 22.14 | 110.00 | 403.67 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:00 | 1448.04 | 17.57 | 34.17 | 438.17 | 858.55 | 22.03 | 115.67 | 416.33 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-05:00 | 1177.43 | 15.74 | 0.00 | 391.50 | 716.37 | 19.28 | 21.67 | 359.83 |
September | 337.67 | 0.52 | 0.48 | 01-SEP-07:00 | 945.46 | 15.25 | 0.00 | 325.50 | 597.36 | 18.78 | 0.00 | 283.33 |
October | 234.00 | 0.53 | 0.48 | 01-OCT-07:49 | 800.46 | 13.75 | 0.00 | 262.33 | 482.40 | 17.27 | 0.00 | 177.33 |
November | 171.33 | 0.57 | 0.48 | 01-NOV-12:20 | 590.14 | 11.76 | 0.00 | 180.17 | 347.12 | 15.37 | 0.00 | 78.33 |
December | 131.67 | 0.59 | 0.48 | 02-DEC-10:00 | 498.63 | 10.99 | 0.00 | 133.00 | 295.63 | 14.78 | 0.00 | 39.83 |
Annual Sum or Average | 3515.67 | 0.52 | 1092.58 | 15.45 | 129.00 | 3654.17 | 645.70 | 19.03 | 345.83 | 2923.33 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 498.63 | 10.99 | 0.00 | 133.00 | 295.63 | 14.60 | 0.00 | 39.83 | |
Maximum of Months | 429.00 | 0.59 | 0.48 | 1566.83 | 18.93 | 56.83 | 438.17 | 902.13 | 22.14 | 115.67 | 416.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.56 | 0.48 | 01-JAN-10:20 | 1293.56 | 20.07 | 64.50 | 202.17 | 763.59 | 23.02 | 78.33 | 145.17 |
February | 217.00 | 0.53 | 0.48 | 01-FEB-11:39 | 2051.73 | 20.64 | 58.33 | 232.83 | 1078.59 | 21.67 | 74.83 | 181.17 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 1924.01 | 21.51 | 72.33 | 303.17 | 1034.31 | 22.68 | 74.50 | 250.33 |
April | 359.67 | 0.51 | 0.48 | 01-APR-08:09 | 3581.17 | 21.49 | 102.33 | 353.17 | 1633.94 | 21.86 | 87.33 | 327.33 |
May | 417.17 | 0.51 | 0.48 | 01-MAY-07:19 | 3277.34 | 19.23 | 73.83 | 412.33 | 1817.68 | 21.19 | 49.00 | 382.17 |
June | 410.67 | 0.50 | 0.48 | 01-JUN-06:10 | 3829.71 | 18.30 | 50.67 | 417.67 | 1684.82 | 19.59 | 3.00 | 380.00 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-06:10 | 3800.31 | 18.18 | 53.33 | 427.17 | 1711.84 | 19.54 | 5.00 | 394.17 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:30 | 3369.65 | 20.16 | 86.83 | 381.83 | 1860.49 | 21.79 | 78.83 | 349.17 |
September | 337.67 | 0.52 | 0.48 | 01-SEP-08:20 | 3269.50 | 21.84 | 96.83 | 323.33 | 1765.91 | 23.18 | 102.17 | 295.67 |
October | 234.00 | 0.52 | 0.48 | 01-OCT-07:49 | 2585.12 | 22.25 | 79.83 | 268.50 | 1132.74 | 22.23 | 93.50 | 209.83 |
November | 171.33 | 0.54 | 0.48 | 01-NOV-11:00 | 1444.92 | 20.42 | 51.67 | 196.33 | 783.43 | 22.69 | 72.17 | 132.17 |
December | 131.67 | 0.56 | 0.48 | 02-DEC-10:20 | 1053.40 | 19.99 | 37.67 | 160.17 | 547.17 | 20.80 | 40.17 | 82.17 |
Annual Sum or Average | 3515.67 | 0.52 | 2958.74 | 20.14 | 828.17 | 3678.67 | 1474.42 | 21.48 | 758.83 | 3129.33 | ||
Minimum of Months | 131.67 | 0.50 | 0.48 | 1053.40 | 18.18 | 37.67 | 160.17 | 547.17 | 19.54 | 3.00 | 82.17 | |
Maximum of Months | 429.00 | 0.56 | 0.48 | 3829.71 | 22.25 | 102.33 | 427.17 | 1860.49 | 23.18 | 102.17 | 394.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.52 | 0.48 | 01-JAN-08:39 | 4022.31 | 34.12 | 177.50 | 221.17 | 3426.98 | 37.37 | 190.17 | 194.83 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 5875.88 | 35.81 | 213.67 | 246.00 | 2760.22 | 30.57 | 141.83 | 222.33 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 4331.88 | 30.32 | 181.50 | 310.50 | 1196.01 | 18.72 | 8.83 | 267.00 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:10 | 2652.60 | 16.03 | 0.00 | 355.17 | 1485.62 | 19.55 | 48.33 | 329.50 |
May | 417.17 | 0.51 | 0.48 | 01-MAY-06:00 | 2115.50 | 15.70 | 0.00 | 409.67 | 1180.40 | 19.17 | 27.33 | 373.33 |
June | 410.67 | 0.50 | 0.48 | 01-JUN-05:00 | 2061.31 | 16.02 | 0.00 | 412.33 | 1139.08 | 19.46 | 21.33 | 372.00 |
July | 429.00 | 0.51 | 0.48 | 01-JUL-05:00 | 2051.65 | 15.81 | 0.00 | 420.83 | 1162.16 | 19.29 | 29.33 | 382.83 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:19 | 2369.41 | 15.70 | 0.00 | 381.83 | 1356.38 | 19.22 | 48.83 | 348.50 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:49 | 3534.19 | 17.91 | 29.50 | 330.17 | 1636.21 | 19.64 | 54.50 | 304.33 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:49 | 7453.45 | 34.73 | 216.67 | 279.83 | 2141.10 | 22.12 | 49.50 | 240.00 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 4684.72 | 35.93 | 167.00 | 216.50 | 3935.85 | 37.30 | 167.67 | 173.50 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:50 | 3910.31 | 36.41 | 126.00 | 182.33 | 3320.34 | 38.34 | 128.67 | 132.83 |
Annual Sum or Average | 3515.67 | 0.51 | 3343.02 | 22.19 | 1111.83 | 3766.33 | 1770.07 | 22.80 | 916.33 | 3341.00 | ||
Minimum of Months | 131.67 | 0.50 | 0.48 | 2051.65 | 15.70 | 0.00 | 182.33 | 1139.08 | 18.72 | 8.83 | 132.83 | |
Maximum of Months | 429.00 | 0.52 | 0.48 | 7453.45 | 36.41 | 216.67 | 420.83 | 3935.85 | 38.34 | 190.17 | 382.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.54 | 0.48 | 01-JAN-08:39 | 1487.55 | 22.96 | 82.67 | 209.67 | 881.12 | 23.76 | 78.83 | 145.00 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 1758.64 | 20.95 | 62.33 | 237.33 | 995.77 | 23.86 | 83.67 | 194.33 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 2034.90 | 21.56 | 71.33 | 304.00 | 899.75 | 22.58 | 65.00 | 251.17 |
April | 359.67 | 0.51 | 0.48 | 01-APR-06:10 | 3775.66 | 22.53 | 107.17 | 363.33 | 2152.51 | 23.82 | 112.83 | 337.33 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3929.22 | 22.58 | 133.33 | 422.50 | 1739.56 | 22.73 | 76.17 | 382.00 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:49 | 3946.09 | 22.48 | 129.50 | 420.50 | 1783.75 | 23.50 | 81.00 | 389.00 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-04:49 | 3852.93 | 22.59 | 137.67 | 431.00 | 1724.12 | 22.97 | 80.00 | 400.00 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3672.72 | 21.70 | 109.83 | 389.33 | 1613.28 | 23.04 | 86.33 | 360.67 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 3510.95 | 23.34 | 109.33 | 337.50 | 1916.75 | 24.26 | 123.83 | 307.50 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-06:49 | 2742.02 | 22.78 | 82.33 | 272.33 | 1203.87 | 22.70 | 88.83 | 213.67 |
November | 171.33 | 0.53 | 0.48 | 01-NOV-11:00 | 1481.82 | 21.07 | 55.67 | 203.83 | 863.44 | 23.70 | 77.83 | 135.50 |
December | 131.67 | 0.52 | 0.48 | 02-DEC-08:50 | 1266.51 | 23.01 | 50.50 | 165.00 | 890.64 | 25.88 | 69.00 | 99.00 |
Annual Sum or Average | 3515.67 | 0.51 | 3153.08 | 22.35 | 1131.67 | 3756.33 | 1532.56 | 23.42 | 1023.33 | 3215.17 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1266.51 | 20.95 | 50.50 | 165.00 | 863.44 | 22.58 | 65.00 | 99.00 | |
Maximum of Months | 429.00 | 0.54 | 0.48 | 3946.09 | 23.34 | 137.67 | 431.00 | 2152.51 | 25.88 | 123.83 | 400.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.59 | 0.48 | 01-JAN-10:30 | 532.04 | 11.01 | 0.00 | 186.67 | 310.93 | 14.60 | 0.00 | 74.83 |
February | 217.00 | 0.54 | 0.48 | 01-FEB-12:09 | 706.34 | 12.88 | 0.00 | 223.17 | 415.53 | 16.43 | 0.00 | 142.17 |
March | 215.50 | 0.53 | 0.48 | 01-MAR-11:39 | 876.13 | 13.47 | 0.00 | 300.17 | 475.62 | 16.83 | 0.00 | 219.33 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:19 | 1158.16 | 15.81 | 0.00 | 360.67 | 694.37 | 19.26 | 14.83 | 329.33 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:00 | 1375.34 | 17.74 | 38.00 | 425.17 | 793.61 | 21.04 | 83.67 | 399.00 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1566.77 | 18.93 | 56.83 | 427.67 | 902.07 | 22.14 | 110.17 | 403.67 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:00 | 1448.00 | 17.57 | 34.17 | 438.17 | 858.50 | 22.03 | 115.67 | 416.33 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-05:00 | 1177.40 | 15.74 | 0.00 | 391.50 | 716.33 | 19.28 | 21.67 | 359.83 |
September | 337.67 | 0.52 | 0.48 | 01-SEP-07:00 | 945.44 | 15.25 | 0.00 | 325.50 | 597.33 | 18.78 | 0.00 | 283.33 |
October | 234.00 | 0.53 | 0.48 | 01-OCT-07:49 | 800.44 | 13.75 | 0.00 | 262.33 | 482.37 | 17.27 | 0.00 | 177.33 |
November | 171.33 | 0.57 | 0.48 | 01-NOV-12:20 | 590.12 | 11.76 | 0.00 | 180.17 | 347.10 | 15.37 | 0.00 | 78.33 |
December | 131.67 | 0.59 | 0.48 | 02-DEC-10:00 | 498.61 | 10.99 | 0.00 | 133.00 | 295.61 | 14.78 | 0.00 | 39.83 |
Annual Sum or Average | 3515.67 | 0.52 | 1092.55 | 15.45 | 129.00 | 3654.17 | 645.66 | 19.03 | 346.00 | 2923.33 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 498.61 | 10.99 | 0.00 | 133.00 | 295.61 | 14.60 | 0.00 | 39.83 | |
Maximum of Months | 429.00 | 0.59 | 0.48 | 1566.77 | 18.93 | 56.83 | 438.17 | 902.07 | 22.14 | 115.67 | 416.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.56 | 0.48 | 01-JAN-10:20 | 1293.54 | 20.07 | 64.50 | 202.17 | 763.55 | 23.02 | 78.33 | 145.17 |
February | 217.00 | 0.53 | 0.48 | 01-FEB-11:39 | 2051.70 | 20.64 | 58.33 | 232.83 | 1078.54 | 21.67 | 74.83 | 181.17 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 1923.94 | 21.52 | 72.33 | 303.17 | 1034.24 | 22.68 | 74.50 | 250.33 |
April | 359.67 | 0.51 | 0.48 | 01-APR-08:09 | 3581.10 | 21.50 | 102.33 | 353.17 | 1633.86 | 21.86 | 87.33 | 327.33 |
May | 417.17 | 0.51 | 0.48 | 01-MAY-07:19 | 3277.27 | 19.23 | 73.83 | 412.33 | 1817.59 | 21.19 | 49.00 | 382.17 |
June | 410.67 | 0.50 | 0.48 | 01-JUN-06:10 | 3829.62 | 18.30 | 50.67 | 417.67 | 1684.72 | 19.59 | 3.00 | 380.00 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-06:10 | 3800.24 | 18.19 | 53.33 | 427.17 | 1711.75 | 19.54 | 5.00 | 394.17 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:30 | 3369.60 | 20.16 | 86.83 | 381.83 | 1860.40 | 21.79 | 78.83 | 349.17 |
September | 337.67 | 0.52 | 0.48 | 01-SEP-08:20 | 3269.47 | 21.84 | 96.83 | 323.33 | 1765.83 | 23.18 | 102.33 | 295.67 |
October | 234.00 | 0.52 | 0.48 | 01-OCT-07:49 | 2585.09 | 22.25 | 79.83 | 268.50 | 1132.67 | 22.23 | 93.50 | 209.83 |
November | 171.33 | 0.54 | 0.48 | 01-NOV-11:00 | 1444.90 | 20.42 | 51.67 | 196.33 | 783.39 | 22.69 | 72.17 | 132.17 |
December | 131.67 | 0.56 | 0.48 | 02-DEC-10:20 | 1053.38 | 19.99 | 37.67 | 160.17 | 547.14 | 20.80 | 40.17 | 82.17 |
Annual Sum or Average | 3515.67 | 0.52 | 2958.68 | 20.14 | 828.17 | 3678.67 | 1474.35 | 21.48 | 759.00 | 3129.33 | ||
Minimum of Months | 131.67 | 0.50 | 0.48 | 1053.38 | 18.19 | 37.67 | 160.17 | 547.14 | 19.54 | 3.00 | 82.17 | |
Maximum of Months | 429.00 | 0.56 | 0.48 | 3829.62 | 22.25 | 102.33 | 427.17 | 1860.40 | 23.18 | 102.33 | 394.17 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 94151907.86 | 26176.66 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94151907.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94151907.86 | 26176.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.445994E+10 | 10954.07 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.328359E+10 | 10954.07 | 01-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.407220E+10 | 10954.07 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120773E+10 | 10954.07 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119812E+10 | 10954.07 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.454549E+09 | 10954.07 | 07-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.179145E+09 | 9975.54 | 31-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.162811E+09 | 10030.88 | 24-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.409781E+09 | 10954.07 | 05-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161708E+10 | 10954.07 | 03-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.309369E+10 | 10954.07 | 01-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.469011E+10 | 10954.07 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.162811E+09 | 9975.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.469011E+10 | 10954.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138087E+10 | 7264.79 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.831510E+09 | 7264.79 | 02-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.693322E+09 | 7264.79 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10939191.87 | 6484.20 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 765826.56 | 1043.10 | 17-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122851E+09 | 7143.96 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.560377E+09 | 7264.79 | 03-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140554E+10 | 7264.79 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.500618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140554E+10 | 7264.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.218291E+10 | 7465.83 | 02-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132951E+10 | 7436.07 | 08-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.973788E+09 | 7416.69 | 18-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 74950951.19 | 7415.12 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1192413.31 | 1531.02 | 17-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160673E+09 | 7416.43 | 17-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.802854E+09 | 7422.26 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201931E+10 | 7415.43 | 12-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.754519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.218291E+10 | 7465.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.157482E+10 | 7224.03 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.905720E+09 | 7224.03 | 02-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.821173E+09 | 7224.03 | 03-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 50199475.74 | 7035.60 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9772859.53 | 3877.06 | 05-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183509E+09 | 7079.25 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.702979E+09 | 7224.03 | 03-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169610E+10 | 7224.03 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.594427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.169610E+10 | 7224.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.633332E+09 | 25454.80 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 58028705.19 | 25454.80 | 13-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 32489977.08 | 25454.80 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 64831129.21 | 25454.80 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.518032E+09 | 25454.80 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.633332E+09 | 25454.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137213E+10 | 10808.12 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.790738E+09 | 10808.12 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.681390E+09 | 10808.12 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42086302.61 | 10664.92 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8785500.70 | 6434.07 | 05-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.188129E+09 | 10808.12 | 21-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.729095E+09 | 10808.12 | 03-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185537E+10 | 10808.12 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.566772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.185537E+10 | 10808.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141552E+10 | 7134.06 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.878511E+09 | 7134.06 | 02-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.652401E+09 | 7134.06 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16058098.70 | 6291.62 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3117057.06 | 2616.64 | 17-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14694.96 | 97.97 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.230009E+09 | 7134.06 | 21-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.823033E+09 | 7134.06 | 03-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168309E+10 | 7134.06 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.570175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168309E+10 | 7134.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.168553E+10 | 8290.90 | 02-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.956388E+09 | 8292.57 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.577120E+09 | 8280.56 | 27-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26368400.63 | 8213.03 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155755E+09 | 8243.46 | 17-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.790907E+09 | 8303.78 | 20-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190422E+10 | 8308.27 | 11-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.609628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.190422E+10 | 8308.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144921E+10 | 7095.20 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.863639E+09 | 7095.20 | 02-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.671591E+09 | 7095.20 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 47958285.88 | 6898.28 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11091677.38 | 5408.05 | 05-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 373774.32 | 615.58 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.260864E+09 | 7095.20 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.849983E+09 | 7095.20 | 03-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177830E+10 | 7095.20 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.593301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177830E+10 | 7095.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.257623E+10 | 30750.18 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134361E+10 | 30750.18 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.895839E+09 | 30750.18 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24178077.27 | 24016.10 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229594E+09 | 30750.18 | 16-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123575E+10 | 30750.18 | 03-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.322573E+10 | 30750.18 | 01-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.953092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.322573E+10 | 30750.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.253233E+10 | 13884.69 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174813E+10 | 13884.69 | 01-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163713E+10 | 13884.69 | 01-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.264048E+09 | 12519.71 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137959E+09 | 11631.38 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6166454.44 | 6318.39 | 08-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 770066.07 | 915.73 | 01-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 110084.88 | 366.95 | 24-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38453119.89 | 10410.87 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.746588E+09 | 13884.69 | 16-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174926E+10 | 13884.69 | 03-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327571E+10 | 13884.69 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 110084.88 | 366.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.327571E+10 | 13884.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.217465E+10 | 9086.32 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149224E+10 | 9086.32 | 01-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121761E+10 | 9086.32 | 01-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101632E+09 | 8558.32 | 01-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33956093.26 | 6927.17 | 17-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11928662.17 | 6140.25 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.601156E+09 | 9086.32 | 16-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148735E+10 | 9086.32 | 03-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.256679E+10 | 9086.32 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.968731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.256679E+10 | 9086.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.307491E+10 | 9211.46 | 23-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.207284E+10 | 9211.94 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152319E+10 | 9211.24 | 20-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212456E+09 | 9121.05 | 05-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 51629548.64 | 9126.86 | 17-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8506.09 | 28.35 | 07-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29141056.87 | 9143.39 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.705932E+09 | 9192.66 | 30-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190770E+10 | 9211.80 | 24-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.349887E+10 | 9204.33 | 12-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.349887E+10 | 9211.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.240588E+10 | 9046.08 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164602E+10 | 9046.08 | 01-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140817E+10 | 9046.08 | 01-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.245057E+09 | 8119.61 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115442E+09 | 7420.85 | 05-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4600032.67 | 3925.87 | 08-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2432317.53 | 1471.57 | 01-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 896218.97 | 900.05 | 24-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 52598683.30 | 6753.36 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.775206E+09 | 9046.08 | 16-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170214E+10 | 9046.08 | 03-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.287105E+10 | 9046.08 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 896218.97 | 900.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.287105E+10 | 9046.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.469948E+10 | 15181.62 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.256734E+10 | 12069.81 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175110E+10 | 8477.12 | 08-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161717E+09 | 6662.81 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19746918.97 | 3870.12 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130521E+09 | 3991.96 | 23-OCT-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143674E+10 | 9523.16 | 29-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.401783E+10 | 10858.88 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.469948E+10 | 15181.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.592401E+10 | 15348.68 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.403834E+10 | 13189.14 | 17-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.310410E+10 | 9751.60 | 08-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.380013E+09 | 7436.74 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 65052980.38 | 4608.07 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10840587.24 | 2381.84 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.436342E+09 | 5560.91 | 23-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.253079E+10 | 10809.52 | 29-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.571490E+10 | 11955.95 | 27-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.592401E+10 | 15348.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.650783E+10 | 16835.97 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.451241E+10 | 15903.58 | 17-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.355631E+10 | 11884.30 | 08-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.678834E+09 | 9942.45 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.207811E+09 | 6785.31 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4039183.61 | 1964.69 | 08-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44761090.16 | 4488.34 | 21-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.798747E+09 | 7565.85 | 23-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304856E+10 | 12869.60 | 29-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.632094E+10 | 13940.79 | 27-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.650783E+10 | 16835.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.169697E+10 | 0.160972E+10 | 34587.31 | 30-APR-15:31 | 34587.31 | 0.00 |
May | 0.00 | 0.00 | 0.272817E+10 | 0.230597E+10 | 42887.00 | 22-MAY-15:10 | 42887.00 | 0.00 |
June | 0.00 | 0.00 | 0.929234E+10 | 0.768278E+10 | 63095.73 | 13-JUN-16:00 | 57836.77 | 0.00 |
July | 0.00 | 0.00 | 0.157367E+11 | 0.127469E+11 | 59321.42 | 21-JUL-16:00 | 59321.42 | 0.00 |
August | 0.00 | 0.00 | 0.204444E+11 | 0.160795E+11 | 56917.10 | 14-AUG-15:50 | 56029.13 | 0.00 |
September | 0.00 | 0.00 | 0.102777E+11 | 0.844142E+10 | 49804.86 | 13-SEP-15:30 | 45382.49 | 0.00 |
October | 0.00 | 0.00 | 0.360563E+09 | 0.343436E+09 | 9720.54 | 07-OCT-15:00 | 9720.54 | 0.00 |
November | 0.00 | 0.00 | 3685265.88 | 2540364.76 | 2760.89 | 24-NOV-12:00 | 1943.04 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.605405E+11 | 0.492123E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.204444E+11 | 0.160795E+11 | 63095.73 | 59321.42 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.176791E+10 | 0.170294E+10 | 37010.43 | 30-APR-16:02 | 37010.43 | 0.00 |
May | 0.00 | 0.00 | 0.261810E+10 | 0.223363E+10 | 42108.83 | 22-MAY-15:00 | 42108.83 | 0.00 |
June | 0.00 | 0.00 | 0.877174E+10 | 0.727314E+10 | 60103.99 | 13-JUN-15:40 | 54755.17 | 0.00 |
July | 0.00 | 0.00 | 0.146163E+11 | 0.118718E+11 | 54806.81 | 21-JUL-15:40 | 54806.81 | 0.00 |
August | 0.00 | 0.00 | 0.184819E+11 | 0.145619E+11 | 53538.66 | 14-AUG-15:30 | 51882.95 | 0.00 |
September | 0.00 | 0.00 | 0.935693E+10 | 0.768226E+10 | 45811.57 | 13-SEP-14:50 | 41660.34 | 0.00 |
October | 0.00 | 0.00 | 0.325315E+09 | 0.311267E+09 | 10756.74 | 07-OCT-15:00 | 10756.74 | 0.00 |
November | 0.00 | 0.00 | 3215995.54 | 2204570.42 | 2401.74 | 24-NOV-12:00 | 1679.53 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.559414E+11 | 0.456391E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.184819E+11 | 0.145619E+11 | 60103.99 | 54806.81 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.178458E+10 | 0.170897E+10 | 38238.98 | 30-APR-16:22 | 38238.98 | 0.00 |
May | 0.00 | 0.00 | 0.270300E+10 | 0.228872E+10 | 45657.02 | 22-MAY-15:00 | 45657.02 | 0.00 |
June | 0.00 | 0.00 | 0.910533E+10 | 0.752183E+10 | 69283.85 | 13-JUN-14:40 | 61330.10 | 0.00 |
July | 0.00 | 0.00 | 0.150370E+11 | 0.121932E+11 | 63122.38 | 21-JUL-15:50 | 63122.38 | 0.00 |
August | 0.00 | 0.00 | 0.183243E+11 | 0.142952E+11 | 58719.79 | 14-AUG-15:40 | 58719.79 | 0.00 |
September | 0.00 | 0.00 | 0.894594E+10 | 0.727486E+10 | 46175.71 | 13-SEP-15:00 | 42283.58 | 0.00 |
October | 0.00 | 0.00 | 0.297295E+09 | 0.280211E+09 | 10547.40 | 07-OCT-15:00 | 10547.40 | 0.00 |
November | 0.00 | 0.00 | 3316737.71 | 2247985.04 | 2493.24 | 24-NOV-12:00 | 1722.23 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.562007E+11 | 0.455653E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.183243E+11 | 0.142952E+11 | 69283.85 | 63122.38 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1869.18 | 6507.73 | 20-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1890.82 | 6534.11 | 17-FEB-12:06 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2002.18 | 6492.90 | 01-MAR-12:25 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1836.73 | 6427.88 | 03-APR-11:09 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1855.98 | 6282.20 | 01-MAY-11:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1855.90 | 6094.71 | 02-JUN-11:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1668.34 | 5959.59 | 03-JUL-11:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1821.79 | 5864.72 | 08-AUG-11:08 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1712.75 | 5931.76 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1745.38 | 6097.96 | 31-OCT-11:13 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1818.25 | 6272.01 | 29-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1788.69 | 6417.48 | 27-DEC-12:10 |
Annual Sum or Average | 0.00 | 1821.78 | ||||
Minimum of Months | 0.00 | 0.00 | 1668.34 | 5864.72 | ||
Maximum of Months | 0.00 | 0.00 | 2002.18 | 6534.11 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141979E+10 | 0.27 | 2805.95 | 02-JAN-06:01 | 0.76 |
February | 0.134042E+10 | 0.27 | 1617.38 | 10-FEB-08:20 | 0.59 |
March | 0.163012E+10 | 0.30 | 1754.22 | 23-MAR-07:07 | 0.61 |
April | 0.221019E+10 | 0.32 | 5282.03 | 28-APR-15:30 | 1.10 |
May | 0.259769E+10 | 0.34 | 4975.62 | 23-MAY-15:10 | 1.06 |
June | 0.323479E+10 | 0.39 | 6990.14 | 13-JUN-16:00 | 1.30 |
July | 0.356220E+10 | 0.39 | 7058.30 | 21-JUL-16:00 | 1.31 |
August | 0.391123E+10 | 0.43 | 6735.01 | 14-AUG-15:30 | 1.27 |
September | 0.318228E+10 | 0.38 | 6653.82 | 13-SEP-15:10 | 1.26 |
October | 0.195402E+10 | 0.30 | 4066.12 | 05-OCT-12:07 | 0.95 |
November | 0.148493E+10 | 0.27 | 1915.88 | 15-NOV-08:07 | 0.63 |
December | 0.137317E+10 | 0.27 | 1609.82 | 04-DEC-06:11 | 0.59 |
Annual Sum or Average | 0.279008E+11 | 0.33 | |||
Minimum of Months | 0.134042E+10 | 0.27 | 1609.82 | 0.59 | |
Maximum of Months | 0.391123E+10 | 0.43 | 7058.30 | 1.31 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135405E+10 | 0.27 | 2853.18 | 02-JAN-06:01 | 0.82 |
February | 0.125407E+10 | 0.28 | 2853.18 | 13-FEB-07:01 | 0.83 |
March | 0.143088E+10 | 0.29 | 2408.23 | 06-MAR-07:02 | 0.75 |
April | 0.200082E+10 | 0.32 | 5993.72 | 28-APR-15:20 | 1.28 |
May | 0.226876E+10 | 0.34 | 5380.41 | 23-MAY-15:20 | 1.19 |
June | 0.288483E+10 | 0.39 | 7160.96 | 13-JUN-15:30 | 1.42 |
July | 0.321764E+10 | 0.40 | 6879.58 | 21-JUL-15:40 | 1.39 |
August | 0.348205E+10 | 0.43 | 6680.79 | 14-AUG-15:30 | 1.36 |
September | 0.273056E+10 | 0.38 | 6546.15 | 12-SEP-15:00 | 1.35 |
October | 0.159780E+10 | 0.29 | 3389.81 | 03-OCT-14:30 | 0.91 |
November | 0.130488E+10 | 0.27 | 2853.18 | 28-NOV-07:01 | 0.83 |
December | 0.131881E+10 | 0.27 | 2853.18 | 18-DEC-07:01 | 0.83 |
Annual Sum or Average | 0.248452E+11 | 0.33 | |||
Minimum of Months | 0.125407E+10 | 0.27 | 2408.23 | 0.75 | |
Maximum of Months | 0.348205E+10 | 0.43 | 7160.96 | 1.42 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144974E+10 | 0.28 | 2682.47 | 03-JAN-06:01 | 0.75 |
February | 0.127217E+10 | 0.27 | 2682.47 | 13-FEB-06:03 | 0.75 |
March | 0.146248E+10 | 0.29 | 2682.47 | 16-MAR-06:01 | 0.75 |
April | 0.185582E+10 | 0.30 | 5819.47 | 28-APR-15:20 | 1.18 |
May | 0.209306E+10 | 0.32 | 5427.88 | 22-MAY-15:20 | 1.12 |
June | 0.264736E+10 | 0.36 | 7461.64 | 13-JUN-15:40 | 1.37 |
July | 0.294426E+10 | 0.36 | 7081.35 | 21-JUL-15:50 | 1.32 |
August | 0.308165E+10 | 0.39 | 6651.45 | 14-AUG-15:30 | 1.28 |
September | 0.234120E+10 | 0.34 | 5973.77 | 12-SEP-15:20 | 1.19 |
October | 0.150493E+10 | 0.27 | 2674.34 | 03-OCT-14:50 | 0.75 |
November | 0.133087E+10 | 0.27 | 2682.47 | 28-NOV-06:01 | 0.75 |
December | 0.140307E+10 | 0.28 | 2682.47 | 04-DEC-06:11 | 0.75 |
Annual Sum or Average | 0.233866E+11 | 0.31 | |||
Minimum of Months | 0.127217E+10 | 0.27 | 2674.34 | 0.75 | |
Maximum of Months | 0.308165E+10 | 0.39 | 7461.64 | 1.37 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:05 | 2.06 | 2.06 | 57.65 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 55.18 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 56.33 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 55.61 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.51 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.51 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 55.71 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 56.43 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 56.82 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 56.45 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 55.90 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 55.38 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.18 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.65 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.25 | 57.25 | 1869.18 | 6507.73 | 20-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 55.84 | 55.84 | 1890.82 | 6534.11 | 17-FEB-12:06 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.97 | 56.97 | 2002.18 | 6492.90 | 01-MAR-12:25 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.28 | 56.28 | 1836.73 | 6427.88 | 03-APR-11:09 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.80 | 57.80 | 1855.98 | 6282.20 | 01-MAY-11:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.96 | 56.96 | 1855.90 | 6094.71 | 02-JUN-11:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.25 | 56.25 | 1668.34 | 5959.59 | 03-JUL-11:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.89 | 56.89 | 1821.79 | 5864.72 | 08-AUG-11:08 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.35 | 57.35 | 1712.75 | 5931.76 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.65 | 55.65 | 1745.38 | 6097.96 | 31-OCT-11:13 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.46 | 56.46 | 1818.25 | 6272.01 | 29-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.13 | 56.13 | 1788.69 | 6417.48 | 27-DEC-12:10 |
Annual Sum or Average | 0.00 | 1821.78 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.65 | 55.65 | 1668.34 | 5864.72 | ||
Maximum of Months | 0.00 | 0.00 | 57.80 | 57.80 | 2002.18 | 6534.11 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.111125E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.769076E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.819061E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.399961E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.449067E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.595850E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.765965E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.914863E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.613072E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.413934E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.664590E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.111842E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.863511E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.399961E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.111842E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.790977E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.480138E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.404588E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.258926E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.294308E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.502123E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.684634E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.806052E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.503815E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.252356E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.456367E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.905782E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.634006E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.252356E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.905782E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.142137E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.957500E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.814442E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.316678E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.310844E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.488551E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.670625E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.766890E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.470320E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.464725E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.941403E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.168412E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.930748E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.310844E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.168412E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141979E+10 | 0.00 | 0.143922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134042E+10 | 0.00 | 0.891767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163012E+10 | 0.00 | 0.831158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.221019E+10 | 0.169697E+10 | 0.150554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.259769E+10 | 0.272817E+10 | 0.122960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.323479E+10 | 0.929234E+10 | 0.454549E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.356220E+10 | 0.157367E+11 | 0.179145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.391123E+10 | 0.204444E+11 | 0.162811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.318228E+10 | 0.102777E+11 | 0.409781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195402E+10 | 0.360563E+09 | 0.221463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148493E+10 | 3685265.88 | 0.659664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137317E+10 | 0.00 | 0.138289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279008E+11 | 0.605405E+11 | 0.582030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134042E+10 | 0.00 | 0.162811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.391123E+10 | 0.204444E+11 | 0.143922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135405E+10 | 0.00 | 0.124797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125407E+10 | 0.00 | 0.758565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143088E+10 | 0.00 | 0.571910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.200082E+10 | 0.176791E+10 | 0.512484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.226876E+10 | 0.261810E+10 | 88047215.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.288483E+10 | 0.877174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.321764E+10 | 0.146163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.348205E+10 | 0.184819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.273056E+10 | 0.935693E+10 | 11229056.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159780E+10 | 0.325315E+09 | 0.127110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130488E+10 | 3215995.54 | 0.578864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131881E+10 | 0.00 | 0.134539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248452E+11 | 0.559414E+11 | 0.469099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.348205E+10 | 0.184819E+11 | 0.134539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144974E+10 | 0.00 | 0.192718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127217E+10 | 0.00 | 0.128152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146248E+10 | 0.00 | 0.102383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185582E+10 | 0.178458E+10 | 0.152621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.209306E+10 | 0.270300E+10 | 0.546798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.264736E+10 | 0.910533E+10 | 14814176.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.294426E+10 | 0.150370E+11 | 3202383.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.308165E+10 | 0.183243E+11 | 1006303.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.234120E+10 | 0.894594E+10 | 0.176883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150493E+10 | 0.297295E+09 | 0.385722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133087E+10 | 3316737.71 | 0.111308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140307E+10 | 0.00 | 0.217591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233866E+11 | 0.562007E+11 | 0.813413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127217E+10 | 0.00 | 1006303.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.308165E+10 | 0.183243E+11 | 0.217591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.141979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.221019E+10 | 0.00 | 0.00 | 0.00 | 0.445594E+09 | 0.134382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.259769E+10 | 0.00 | 0.00 | 0.00 | 0.683132E+09 | 0.120985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.323479E+10 | 0.00 | 0.00 | 0.00 | 0.226916E+10 | 0.454549E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.356220E+10 | 0.00 | 0.00 | 0.00 | 0.391831E+10 | 0.179145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.391123E+10 | 0.00 | 0.00 | 0.00 | 0.507459E+10 | 0.162811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.318228E+10 | 0.00 | 0.00 | 0.00 | 0.253867E+10 | 0.409781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195402E+10 | 0.00 | 0.00 | 0.00 | 0.101199E+09 | 0.208411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148493E+10 | 0.00 | 0.00 | 0.00 | 1070842.64 | 0.515990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.981106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279008E+11 | 0.00 | 0.00 | 0.00 | 0.150317E+11 | 0.434185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.391123E+10 | 0.00 | 0.00 | 0.00 | 0.507459E+10 | 0.981106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.200082E+10 | 0.00 | 0.00 | 0.00 | 0.455971E+09 | 0.132471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.226876E+10 | 0.00 | 0.00 | 0.00 | 0.651327E+09 | 22994235.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.288483E+10 | 0.00 | 0.00 | 0.00 | 0.213640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.321764E+10 | 0.00 | 0.00 | 0.00 | 0.362870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.348205E+10 | 0.00 | 0.00 | 0.00 | 0.457847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.273056E+10 | 0.00 | 0.00 | 0.00 | 0.230720E+10 | 388469.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159780E+10 | 0.00 | 0.00 | 0.00 | 91003591.71 | 0.834757E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130488E+10 | 0.00 | 0.00 | 0.00 | 934964.43 | 0.325785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248452E+11 | 0.00 | 0.00 | 0.00 | 0.138500E+11 | 0.247055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.348205E+10 | 0.00 | 0.00 | 0.00 | 0.457847E+10 | 0.773901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.144974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185582E+10 | 0.00 | 0.00 | 0.00 | 0.463586E+09 | 0.847372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.209306E+10 | 0.00 | 0.00 | 0.00 | 0.676396E+09 | 0.338986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.264736E+10 | 0.00 | 0.00 | 0.00 | 0.222737E+10 | 10774993.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.294426E+10 | 0.00 | 0.00 | 0.00 | 0.375880E+10 | 3202383.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.308165E+10 | 0.00 | 0.00 | 0.00 | 0.458625E+10 | 1006303.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.234120E+10 | 0.00 | 0.00 | 0.00 | 0.222988E+10 | 0.132122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150493E+10 | 0.00 | 0.00 | 0.00 | 83841801.05 | 0.305848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133087E+10 | 0.00 | 0.00 | 0.00 | 965350.73 | 0.808220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233866E+11 | 0.00 | 0.00 | 0.00 | 0.140271E+11 | 0.556611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1006303.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.308165E+10 | 0.00 | 0.00 | 0.00 | 0.458625E+10 | 0.154381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.680294E+10 | 0.00 | 0.00 | 13656781.19 | 0.00 | 53662294.37 | 0.803028E+10 | 0.00 | 0.32 |
February | 0.526299E+10 | 0.00 | 0.00 | 17207683.72 | 0.00 | 0.00 | 0.861382E+10 | 0.00 | 0.33 |
March | 0.502515E+10 | 0.00 | 0.00 | 19614411.15 | 0.00 | 0.00 | 0.116743E+11 | 0.00 | 0.39 |
April | 0.135721E+10 | 0.00 | 0.00 | 38424616.58 | 0.00 | 0.00 | 0.202133E+11 | 0.00 | 0.69 |
May | 0.115900E+10 | 0.00 | 0.00 | 43749078.49 | 0.00 | 0.00 | 0.232500E+11 | 0.00 | 0.79 |
June | 0.103251E+10 | 15532934.15 | 0.00 | 47326694.56 | 34446162.12 | 0.00 | 0.237967E+11 | 0.00 | 1.08 |
July | 0.101167E+10 | 17341358.71 | 0.00 | 44583333.64 | 3386726.89 | 0.00 | 0.202918E+11 | 0.00 | 1.11 |
August | 0.110495E+10 | 0.00 | 0.00 | 48949236.67 | 0.00 | 0.00 | 0.199192E+11 | 0.00 | 1.28 |
September | 0.118638E+10 | 0.00 | 0.00 | 42891393.68 | 584127.81 | 0.00 | 0.206529E+11 | 0.00 | 1.06 |
October | 0.189583E+10 | 0.00 | 0.00 | 30548798.64 | 0.00 | 0.00 | 0.177272E+11 | 0.00 | 0.60 |
November | 0.376550E+10 | 0.00 | 0.00 | 19506294.11 | 0.00 | 0.00 | 0.114491E+11 | 0.00 | 0.39 |
December | 0.618910E+10 | 0.00 | 0.00 | 13468701.84 | 0.00 | 0.00 | 0.759233E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.357932E+11 | 32874292.86 | 0.00 | 0.379927E+09 | 38417016.82 | 53662294.37 | 0.193211E+12 | 0.00 | 0.70 |
Minimum of Months | 0.101167E+10 | 0.00 | 0.00 | 13468701.84 | 0.00 | 0.00 | 0.759233E+10 | 0.00 | 0.30 |
Maximum of Months | 0.680294E+10 | 17341358.71 | 0.00 | 48949236.67 | 34446162.12 | 53662294.37 | 0.237967E+11 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118324E+11 | 0.00 | 0.00 | 135024.05 | 0.00 | 0.387256E+09 | 0.299616E+09 | 0.00 | 0.27 |
February | 0.107106E+11 | 0.00 | 0.00 | 144755.00 | 0.00 | 12934198.34 | 0.422787E+09 | 0.00 | 0.27 |
March | 0.118207E+11 | 0.00 | 0.00 | 390134.38 | 0.00 | 12873535.70 | 0.975041E+09 | 0.00 | 0.30 |
April | 0.475371E+10 | 882128.93 | 0.00 | 13863418.66 | 0.00 | 0.00 | 0.926495E+10 | 0.00 | 0.45 |
May | 0.438160E+10 | 0.00 | 0.00 | 19369669.44 | 0.00 | 0.00 | 0.116412E+11 | 0.00 | 0.52 |
June | 0.240923E+10 | 12685328.19 | 0.00 | 25601024.96 | 30600964.48 | 0.00 | 0.141632E+11 | 0.00 | 0.73 |
July | 0.233524E+10 | 16274686.78 | 0.00 | 25436139.79 | 4006943.33 | 0.00 | 0.122077E+11 | 0.00 | 0.77 |
August | 0.199703E+10 | 0.00 | 0.00 | 27405342.32 | 0.00 | 0.00 | 0.120671E+11 | 0.00 | 0.86 |
September | 0.326320E+10 | 0.00 | 0.00 | 19762835.69 | 565781.22 | 0.00 | 0.109019E+11 | 0.00 | 0.70 |
October | 0.731331E+10 | 0.00 | 0.00 | 6173809.60 | 0.00 | 0.00 | 0.505033E+10 | 0.00 | 0.38 |
November | 0.100867E+11 | 0.00 | 0.00 | 501208.10 | 0.00 | 25096635.04 | 0.965536E+09 | 0.00 | 0.29 |
December | 0.116721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151882E+09 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.825757E+11 | 29842143.90 | 0.00 | 0.138783E+09 | 35173689.03 | 0.590042E+09 | 0.779594E+11 | 0.00 | 0.49 |
Minimum of Months | 0.199703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.118324E+11 | 16274686.78 | 0.00 | 27405342.32 | 30600964.48 | 0.387256E+09 | 0.141632E+11 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104423E+10 | 0.00 | 0.00 | 0.27 |
February | 0.100155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460291E+09 | 0.00 | 0.00 | 0.27 |
March | 0.116412E+11 | 0.00 | 0.00 | 19484.66 | 0.00 | 0.322669E+09 | 0.128843E+09 | 0.00 | 0.30 |
April | 0.656724E+10 | 1899061.88 | 0.00 | 9319016.35 | 882547.66 | 3066063.43 | 0.698475E+10 | 0.00 | 0.43 |
May | 0.581962E+10 | 0.00 | 0.00 | 14216959.07 | 0.00 | 0.00 | 0.942716E+10 | 0.00 | 0.50 |
June | 0.353975E+10 | 6181037.70 | 0.00 | 22197656.17 | 25884489.24 | 0.00 | 0.125891E+11 | 0.00 | 0.71 |
July | 0.324377E+10 | 11479875.65 | 0.00 | 22003339.65 | 7615355.89 | 0.00 | 0.111605E+11 | 0.00 | 0.75 |
August | 0.302065E+10 | 0.00 | 0.00 | 21918495.70 | 0.00 | 0.00 | 0.105708E+11 | 0.00 | 0.82 |
September | 0.460980E+10 | 0.00 | 0.00 | 13967430.03 | 0.00 | 0.00 | 0.826049E+10 | 0.00 | 0.64 |
October | 0.883654E+10 | 0.00 | 0.00 | 2242476.83 | 0.00 | 61014490.47 | 0.231424E+10 | 0.00 | 0.36 |
November | 0.978419E+10 | 0.00 | 0.00 | 37042.59 | 0.00 | 0.330235E+09 | 0.130007E+09 | 0.00 | 0.28 |
December | 0.963215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132089E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.873763E+11 | 19559975.24 | 0.00 | 0.105922E+09 | 34382392.80 | 0.354240E+10 | 0.615659E+11 | 0.00 | 0.47 |
Minimum of Months | 0.302065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.116412E+11 | 11479875.65 | 0.00 | 22197656.17 | 25884489.24 | 0.132089E+10 | 0.125891E+11 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.694087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182070E+10 | 0.00 | 0.00 | 0.27 |
February | 0.954934E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127676E+10 | 0.00 | 0.00 | 0.27 |
March | 0.167730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.888047E+09 | 0.00 | 0.00 | 0.30 |
April | 0.175351E+10 | 0.00 | 0.00 | 1104765.16 | 587597.66 | 0.117796E+09 | 0.897095E+09 | 0.00 | 0.42 |
May | 0.183054E+10 | 0.00 | 0.00 | 1971441.10 | 0.00 | 21952140.13 | 0.128514E+10 | 0.00 | 0.49 |
June | 0.984920E+09 | 2104885.38 | 0.00 | 4660974.69 | 5467936.88 | 0.00 | 0.251127E+10 | 0.00 | 0.77 |
July | 0.837686E+09 | 4128437.44 | 0.00 | 5012345.83 | 535832.98 | 0.00 | 0.242103E+10 | 0.00 | 0.83 |
August | 0.897233E+09 | 0.00 | 0.00 | 4474699.74 | 0.00 | 0.00 | 0.204534E+10 | 0.00 | 0.86 |
September | 0.146293E+10 | 0.00 | 0.00 | 1914422.57 | 0.00 | 10771797.07 | 0.109197E+10 | 0.00 | 0.61 |
October | 0.180642E+10 | 0.00 | 0.00 | 96804.23 | 0.00 | 0.363739E+09 | 0.148874E+09 | 0.00 | 0.35 |
November | 0.110853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107342E+10 | 0.00 | 0.00 | 0.28 |
December | 0.504703E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185410E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.145128E+11 | 6233322.81 | 0.00 | 19235453.32 | 6591367.53 | 0.742728E+10 | 0.104007E+11 | 0.00 | 0.48 |
Minimum of Months | 0.504703E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.183054E+10 | 4128437.44 | 0.00 | 5012345.83 | 5467936.88 | 0.185410E+10 | 0.251127E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.945802E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150657E+10 | 0.00 | 0.00 | 0.42 |
February | 0.115103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103990E+10 | 0.00 | 0.00 | 0.42 |
March | 0.176920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759159E+09 | 0.00 | 0.00 | 0.47 |
April | 0.111141E+10 | 1873264.16 | 0.00 | 3843672.47 | 0.00 | 37462196.45 | 0.228242E+10 | 0.00 | 0.84 |
May | 0.135827E+10 | 0.00 | 0.00 | 4149241.41 | 0.00 | 8783718.47 | 0.238203E+10 | 0.00 | 0.94 |
June | 0.907380E+09 | 1498226.19 | 0.00 | 5911564.76 | 5401030.87 | 0.00 | 0.304329E+10 | 0.00 | 1.37 |
July | 0.706737E+09 | 11888430.41 | 0.00 | 6569263.38 | 529276.49 | 0.00 | 0.291788E+10 | 0.00 | 1.45 |
August | 0.746919E+09 | 0.00 | 0.00 | 6455646.21 | 0.00 | 0.00 | 0.281900E+10 | 0.00 | 1.62 |
September | 0.107642E+10 | 0.00 | 0.00 | 4006649.43 | 0.00 | 3920190.94 | 0.206867E+10 | 0.00 | 1.20 |
October | 0.160204E+10 | 0.00 | 0.00 | 689968.96 | 0.00 | 0.300731E+09 | 0.460041E+09 | 0.00 | 0.57 |
November | 0.124588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.896713E+09 | 0.00 | 0.00 | 0.44 |
December | 0.711910E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158375E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.133330E+11 | 15259920.76 | 0.00 | 31626006.64 | 5930307.37 | 0.613699E+10 | 0.159733E+11 | 0.00 | 0.85 |
Minimum of Months | 0.706737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.176920E+10 | 11888430.41 | 0.00 | 6569263.38 | 5401030.87 | 0.158375E+10 | 0.304329E+10 | 0.00 | 1.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163564E+10 | 0.00 | 0.00 | 1126873.65 | 0.00 | 0.161517E+10 | 0.626069E+09 | 0.00 | 0.42 |
February | 0.162727E+10 | 0.00 | 0.00 | 1660796.25 | 0.00 | 0.113630E+10 | 0.890509E+09 | 0.00 | 0.45 |
March | 0.258134E+10 | 0.00 | 0.00 | 336376.11 | 0.00 | 0.989445E+09 | 0.250528E+09 | 0.00 | 0.45 |
April | 0.157468E+10 | 0.00 | 0.00 | 8367061.91 | 869985.09 | 0.141601E+09 | 0.459117E+10 | 0.00 | 0.99 |
May | 0.221552E+10 | 0.00 | 0.00 | 6205322.63 | 0.00 | 52513606.84 | 0.357654E+10 | 0.00 | 0.92 |
June | 0.165414E+10 | 2846233.87 | 0.00 | 7237334.30 | 8095715.58 | 1101052.76 | 0.388032E+10 | 0.00 | 1.21 |
July | 0.126887E+10 | 2758546.28 | 0.00 | 8668522.58 | 4213683.10 | 0.00 | 0.401323E+10 | 0.00 | 1.36 |
August | 0.119753E+10 | 0.00 | 0.00 | 10772093.65 | 0.00 | 0.00 | 0.450628E+10 | 0.00 | 1.70 |
September | 0.145312E+10 | 0.00 | 0.00 | 9944485.53 | 0.00 | 10435226.93 | 0.479719E+10 | 0.00 | 1.57 |
October | 0.197454E+10 | 0.00 | 0.00 | 4205266.31 | 0.00 | 0.359567E+09 | 0.260952E+10 | 0.00 | 0.77 |
November | 0.187727E+10 | 0.00 | 0.00 | 1050882.84 | 0.00 | 0.100025E+10 | 0.519446E+09 | 0.00 | 0.44 |
December | 0.120227E+10 | 0.00 | 0.00 | 527633.99 | 0.00 | 0.207268E+10 | 0.219131E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.202622E+11 | 5604780.16 | 0.00 | 60102649.76 | 13179383.78 | 0.737907E+10 | 0.304799E+11 | 0.00 | 0.89 |
Minimum of Months | 0.119753E+10 | 0.00 | 0.00 | 336376.11 | 0.00 | 0.00 | 0.219131E+09 | 0.00 | 0.39 |
Maximum of Months | 0.258134E+10 | 2846233.87 | 0.00 | 10772093.65 | 8095715.58 | 0.207268E+10 | 0.479719E+10 | 0.00 | 1.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100736E+10 | 0.00 | 0.00 | 5389.74 | 0.00 | 0.168812E+10 | 11446994.36 | 0.00 | 0.46 |
February | 0.115683E+10 | 0.00 | 0.00 | 134805.00 | 0.00 | 0.114541E+10 | 0.127300E+09 | 0.00 | 0.47 |
March | 0.184917E+10 | 0.00 | 0.00 | 98940.93 | 0.00 | 0.869582E+09 | 84319463.04 | 0.00 | 0.52 |
April | 0.175545E+10 | 0.00 | 0.00 | 3629213.94 | 641550.70 | 0.123394E+09 | 0.186455E+10 | 0.00 | 0.92 |
May | 0.185122E+10 | 0.00 | 0.00 | 3998057.01 | 0.00 | 40793691.84 | 0.223651E+10 | 0.00 | 1.05 |
June | 0.125287E+10 | 13677058.66 | 0.00 | 5850230.54 | 1035988.69 | 811946.29 | 0.295007E+10 | 0.00 | 1.48 |
July | 0.933329E+09 | 1801080.15 | 0.00 | 7011274.89 | 3389790.86 | 1562479.81 | 0.291632E+10 | 0.00 | 1.58 |
August | 0.102354E+10 | 0.00 | 0.00 | 5911616.16 | 0.00 | 0.00 | 0.241487E+10 | 0.00 | 1.59 |
September | 0.155906E+10 | 0.00 | 0.00 | 3060679.58 | 0.00 | 14420798.70 | 0.158823E+10 | 0.00 | 1.23 |
October | 0.183342E+10 | 0.00 | 0.00 | 745908.24 | 0.00 | 0.383488E+09 | 0.506771E+09 | 0.00 | 0.66 |
November | 0.127205E+10 | 0.00 | 0.00 | 13932.92 | 0.00 | 0.105965E+10 | 35228683.84 | 0.00 | 0.49 |
December | 0.593435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194058E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.160877E+11 | 15478138.82 | 0.00 | 30460048.95 | 5067330.25 | 0.726782E+10 | 0.147356E+11 | 0.00 | 0.91 |
Minimum of Months | 0.593435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.185122E+10 | 13677058.66 | 0.00 | 7011274.89 | 3389790.86 | 0.194058E+10 | 0.295007E+10 | 0.00 | 1.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.994638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178945E+10 | 0.00 | 0.00 | 0.28 |
February | 0.121535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121948E+10 | 0.00 | 0.00 | 0.27 |
March | 0.203413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750415E+09 | 0.00 | 0.00 | 0.31 |
April | 0.241913E+10 | 0.00 | 0.00 | 183948.30 | 0.00 | 34390863.59 | 0.226801E+09 | 0.00 | 0.40 |
May | 0.224255E+10 | 0.00 | 0.00 | 830390.14 | 0.00 | 619674.94 | 0.638831E+09 | 0.00 | 0.44 |
June | 0.120664E+10 | 2683628.81 | 0.00 | 3019041.53 | 7262923.45 | 0.00 | 0.174755E+10 | 0.00 | 0.63 |
July | 0.918247E+09 | 3012870.41 | 0.00 | 3873645.02 | 714086.46 | 0.00 | 0.182620E+10 | 0.00 | 0.70 |
August | 0.104798E+10 | 0.00 | 0.00 | 3300188.98 | 0.00 | 0.00 | 0.150822E+10 | 0.00 | 0.74 |
September | 0.169118E+10 | 0.00 | 0.00 | 1387442.39 | 123162.50 | 0.00 | 0.848261E+09 | 0.00 | 0.57 |
October | 0.250447E+10 | 0.00 | 0.00 | 13271.63 | 0.00 | 54261883.74 | 77176778.58 | 0.00 | 0.37 |
November | 0.192993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547213E+09 | 0.00 | 0.00 | 0.30 |
December | 0.985628E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163892E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.191899E+11 | 5696499.22 | 0.00 | 12607927.99 | 8100172.42 | 0.603475E+10 | 0.687304E+10 | 0.00 | 0.44 |
Minimum of Months | 0.918247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.250447E+10 | 3012870.41 | 0.00 | 3873645.02 | 7262923.45 | 0.178945E+10 | 0.182620E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117904E+10 | 0.00 | 0.00 | 0.36 |
February | 0.121417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768278E+09 | 0.00 | 0.00 | 0.35 |
March | 0.174791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518518E+09 | 0.00 | 0.00 | 0.39 |
April | 0.100894E+10 | 0.00 | 0.00 | 3113824.67 | 0.00 | 2004068.13 | 0.183013E+10 | 0.00 | 0.70 |
May | 0.103399E+10 | 0.00 | 0.00 | 3767256.89 | 0.00 | 222789.85 | 0.211958E+10 | 0.00 | 0.80 |
June | 0.625536E+09 | 2628985.29 | 0.00 | 5230023.70 | 5905082.11 | 0.00 | 0.265328E+10 | 0.00 | 1.16 |
July | 0.463979E+09 | 6117421.33 | 0.00 | 6027227.46 | 580584.28 | 0.00 | 0.264153E+10 | 0.00 | 1.26 |
August | 0.478539E+09 | 0.00 | 0.00 | 6287397.39 | 0.00 | 0.00 | 0.264597E+10 | 0.00 | 1.44 |
September | 0.815880E+09 | 0.00 | 0.00 | 4395610.62 | 100136.63 | 0.00 | 0.216936E+10 | 0.00 | 1.11 |
October | 0.170375E+10 | 0.00 | 0.00 | 817174.52 | 0.00 | 33828692.59 | 0.546158E+09 | 0.00 | 0.52 |
November | 0.165426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361287E+09 | 0.00 | 0.00 | 0.38 |
December | 0.951490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118492E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.127772E+11 | 8746406.62 | 0.00 | 29638515.25 | 6585803.03 | 0.404810E+10 | 0.146060E+11 | 0.00 | 0.74 |
Minimum of Months | 0.463979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.174791E+10 | 6117421.33 | 0.00 | 6287397.39 | 5905082.11 | 0.118492E+10 | 0.265328E+10 | 0.00 | 1.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118661E+10 | 0.00 | 0.00 | 139531.64 | 0.00 | 0.285724E+10 | 0.120177E+09 | 0.00 | 0.41 |
February | 0.148934E+10 | 0.00 | 0.00 | 172742.86 | 0.00 | 0.192543E+10 | 0.167227E+09 | 0.00 | 0.40 |
March | 0.173078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235066E+10 | 0.00 | 0.00 | 0.44 |
April | 0.195664E+10 | 0.00 | 0.00 | 2874194.34 | 0.00 | 0.608536E+09 | 0.161565E+10 | 0.00 | 0.66 |
May | 0.224302E+10 | 0.00 | 0.00 | 1890973.75 | 0.00 | 0.554827E+09 | 0.123958E+10 | 0.00 | 0.64 |
June | 0.199421E+10 | 4671387.53 | 0.00 | 2700187.15 | 8854333.00 | 0.226906E+09 | 0.143859E+10 | 0.00 | 0.82 |
July | 0.132990E+10 | 5200635.25 | 0.00 | 4504842.82 | 870552.94 | 0.111193E+09 | 0.209955E+10 | 0.00 | 0.94 |
August | 0.105640E+10 | 0.00 | 0.00 | 7132513.98 | 0.00 | 0.102782E+09 | 0.288475E+10 | 0.00 | 1.26 |
September | 0.122702E+10 | 225565.09 | 0.00 | 7077083.41 | 12468.17 | 0.215068E+09 | 0.335831E+10 | 0.00 | 1.23 |
October | 0.200037E+10 | 0.00 | 0.00 | 2289253.65 | 0.00 | 0.724476E+09 | 0.158807E+10 | 0.00 | 0.64 |
November | 0.183223E+10 | 0.00 | 0.00 | 154805.37 | 0.00 | 0.160427E+10 | 0.131311E+09 | 0.00 | 0.42 |
December | 0.747616E+09 | 0.00 | 0.00 | 13192.12 | 0.00 | 0.317060E+10 | 15623896.98 | 0.00 | 0.40 |
Annual Sum or Average | 0.187941E+11 | 10097587.87 | 0.00 | 28949321.10 | 9737354.11 | 0.144520E+11 | 0.146588E+11 | 0.00 | 0.69 |
Minimum of Months | 0.747616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102782E+09 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.224302E+10 | 5200635.25 | 0.00 | 7132513.98 | 8854333.00 | 0.317060E+10 | 0.335831E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.115511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138478E+10 | 0.00 | 0.00 | 0.40 |
February | 0.139212E+10 | 0.00 | 0.00 | 41984.28 | 0.00 | 0.780666E+09 | 57723562.62 | 0.00 | 0.40 |
March | 0.193957E+10 | 0.00 | 0.00 | 17781.05 | 0.00 | 0.590373E+09 | 21339469.86 | 0.00 | 0.44 |
April | 0.172631E+10 | 0.00 | 0.00 | 2232442.55 | 0.00 | 21690673.63 | 0.111659E+10 | 0.00 | 0.71 |
May | 0.154571E+10 | 0.00 | 0.00 | 3115519.56 | 0.00 | 1783754.18 | 0.173022E+10 | 0.00 | 0.84 |
June | 0.868392E+09 | 12668570.91 | 0.00 | 4859059.94 | 1909954.28 | 0.00 | 0.249468E+10 | 0.00 | 1.20 |
July | 0.654545E+09 | 3972437.40 | 0.00 | 6065086.68 | 366338.30 | 0.00 | 0.253742E+10 | 0.00 | 1.34 |
August | 0.670357E+09 | 0.00 | 0.00 | 5202628.80 | 0.00 | 0.00 | 0.216859E+10 | 0.00 | 1.33 |
September | 0.123184E+10 | 14782.28 | 0.00 | 2828438.15 | 103514.80 | 0.00 | 0.148584E+10 | 0.00 | 1.03 |
October | 0.209471E+10 | 0.00 | 0.00 | 622505.94 | 0.00 | 53705706.96 | 0.401391E+09 | 0.00 | 0.58 |
November | 0.179526E+10 | 0.00 | 0.00 | 5890.67 | 0.00 | 0.456988E+09 | 16115927.41 | 0.00 | 0.43 |
December | 0.896620E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150769E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.159706E+11 | 16655790.59 | 0.00 | 24991337.61 | 2379807.38 | 0.479768E+10 | 0.120299E+11 | 0.00 | 0.76 |
Minimum of Months | 0.654545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.209471E+10 | 12668570.91 | 0.00 | 6065086.68 | 1909954.28 | 0.150769E+10 | 0.253742E+10 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134434E+10 | 0.00 | 0.00 | 0.27 |
February | 0.155641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.798435E+09 | 0.00 | 0.00 | 0.27 |
March | 0.229310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411641E+09 | 0.00 | 0.00 | 0.30 |
April | 0.170576E+10 | 123979.83 | 0.00 | 1465368.05 | 0.00 | 13181034.49 | 0.106675E+10 | 0.00 | 0.43 |
May | 0.156404E+10 | 0.00 | 0.00 | 2557467.80 | 0.00 | 0.00 | 0.161488E+10 | 0.00 | 0.50 |
June | 0.729489E+09 | 4396538.87 | 0.00 | 5373287.66 | 6448598.73 | 0.00 | 0.280387E+10 | 0.00 | 0.78 |
July | 0.697250E+09 | 5687842.28 | 0.00 | 5454976.86 | 844390.70 | 0.00 | 0.253880E+10 | 0.00 | 0.85 |
August | 0.786061E+09 | 0.00 | 0.00 | 5123490.90 | 0.00 | 0.00 | 0.217191E+10 | 0.00 | 0.88 |
September | 0.138545E+10 | 0.00 | 0.00 | 2504474.91 | 119228.14 | 0.00 | 0.132181E+10 | 0.00 | 0.64 |
October | 0.218837E+10 | 0.00 | 0.00 | 224347.58 | 0.00 | 65479922.86 | 0.217260E+09 | 0.00 | 0.36 |
November | 0.182312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516703E+09 | 0.00 | 0.00 | 0.29 |
December | 0.106672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143893E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.171070E+11 | 10208360.98 | 0.00 | 22703413.75 | 7412217.57 | 0.458870E+10 | 0.117353E+11 | 0.00 | 0.49 |
Minimum of Months | 0.697250E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.229310E+10 | 5687842.28 | 0.00 | 5454976.86 | 6448598.73 | 0.143893E+10 | 0.280387E+10 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.151946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119569E+10 | 0.00 | 0.00 | 0.44 |
February | 0.165824E+10 | 0.00 | 0.00 | 11639.54 | 0.00 | 0.738341E+09 | 19407674.38 | 0.00 | 0.44 |
March | 0.236583E+10 | 0.00 | 0.00 | 2021.86 | 0.00 | 0.400521E+09 | 7933192.27 | 0.00 | 0.49 |
April | 0.115471E+10 | 483779.97 | 0.00 | 4369726.27 | 0.00 | 2809314.26 | 0.248274E+10 | 0.00 | 0.89 |
May | 0.133933E+10 | 0.00 | 0.00 | 4683161.62 | 0.00 | 516394.54 | 0.258493E+10 | 0.00 | 0.98 |
June | 0.812908E+09 | 3128036.78 | 0.00 | 6222290.72 | 6616441.52 | 0.00 | 0.314945E+10 | 0.00 | 1.38 |
July | 0.702134E+09 | 9954309.19 | 0.00 | 6806507.61 | 866368.32 | 0.00 | 0.290579E+10 | 0.00 | 1.45 |
August | 0.729896E+09 | 0.00 | 0.00 | 6890235.77 | 0.00 | 0.00 | 0.287041E+10 | 0.00 | 1.64 |
September | 0.116308E+10 | 0.00 | 0.00 | 4622423.71 | 122331.39 | 0.00 | 0.224697E+10 | 0.00 | 1.28 |
October | 0.199741E+10 | 0.00 | 0.00 | 947072.14 | 0.00 | 72749559.81 | 0.598880E+09 | 0.00 | 0.61 |
November | 0.191592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483763E+09 | 0.00 | 0.00 | 0.47 |
December | 0.115100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141469E+10 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.165099E+11 | 13566125.95 | 0.00 | 34555079.25 | 7605141.22 | 0.430908E+10 | 0.168665E+11 | 0.00 | 0.88 |
Minimum of Months | 0.702134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.236583E+10 | 9954309.19 | 0.00 | 6890235.77 | 6616441.52 | 0.141469E+10 | 0.314945E+10 | 0.00 | 1.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.223978E+10 | 0.00 | 0.00 | 1552025.08 | 0.00 | 0.109809E+10 | 0.788841E+09 | 0.00 | 0.43 |
February | 0.228779E+10 | 0.00 | 0.00 | 2153693.39 | 0.00 | 0.532795E+09 | 0.105436E+10 | 0.00 | 0.46 |
March | 0.317744E+10 | 0.00 | 0.00 | 532131.21 | 0.00 | 0.400697E+09 | 0.372138E+09 | 0.00 | 0.44 |
April | 0.163706E+10 | 178046.68 | 0.00 | 8968645.40 | 0.00 | 14771792.47 | 0.452368E+10 | 0.00 | 1.00 |
May | 0.200691E+10 | 0.00 | 0.00 | 6727763.51 | 0.00 | 2308121.77 | 0.369454E+10 | 0.00 | 0.92 |
June | 0.136559E+10 | 5970203.06 | 0.00 | 7681775.55 | 9260793.03 | 0.00 | 0.394014E+10 | 0.00 | 1.19 |
July | 0.113160E+10 | 8671813.28 | 0.00 | 8870987.13 | 1652651.43 | 0.00 | 0.386001E+10 | 0.00 | 1.33 |
August | 0.103162E+10 | 0.00 | 0.00 | 11291791.02 | 0.00 | 0.00 | 0.434916E+10 | 0.00 | 1.69 |
September | 0.142811E+10 | 239778.97 | 0.00 | 10734871.71 | 13483.25 | 0.00 | 0.481145E+10 | 0.00 | 1.62 |
October | 0.229950E+10 | 0.00 | 0.00 | 5009469.21 | 0.00 | 74409312.01 | 0.287253E+10 | 0.00 | 0.81 |
November | 0.244811E+10 | 0.00 | 0.00 | 1488280.28 | 0.00 | 0.475090E+09 | 0.715414E+09 | 0.00 | 0.45 |
December | 0.184423E+10 | 0.00 | 0.00 | 724343.07 | 0.00 | 0.154402E+10 | 0.306361E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.228977E+11 | 15059841.98 | 0.00 | 65735776.57 | 10926927.72 | 0.414218E+10 | 0.312886E+11 | 0.00 | 0.90 |
Minimum of Months | 0.103162E+10 | 0.00 | 0.00 | 532131.21 | 0.00 | 0.00 | 0.306361E+09 | 0.00 | 0.40 |
Maximum of Months | 0.317744E+10 | 8671813.28 | 0.00 | 11291791.02 | 9260793.03 | 0.154402E+10 | 0.481145E+10 | 0.00 | 1.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155003E+10 | 0.00 | 0.00 | 14422.06 | 0.00 | 0.123578E+10 | 19232570.80 | 0.00 | 0.46 |
February | 0.173006E+10 | 0.00 | 0.00 | 216987.81 | 0.00 | 0.616091E+09 | 0.171791E+09 | 0.00 | 0.46 |
March | 0.238482E+10 | 0.00 | 0.00 | 143419.28 | 0.00 | 0.387505E+09 | 0.111011E+09 | 0.00 | 0.51 |
April | 0.177637E+10 | 0.00 | 0.00 | 3687935.25 | 131446.44 | 18633636.40 | 0.182085E+10 | 0.00 | 0.91 |
May | 0.170792E+10 | 0.00 | 0.00 | 4275770.96 | 0.00 | 3184059.03 | 0.229770E+10 | 0.00 | 1.03 |
June | 0.100449E+10 | 19117881.11 | 0.00 | 6124989.83 | 1561845.67 | 0.00 | 0.300352E+10 | 0.00 | 1.44 |
July | 0.804454E+09 | 6887411.95 | 0.00 | 7310695.03 | 685934.64 | 0.00 | 0.282146E+10 | 0.00 | 1.55 |
August | 0.840599E+09 | 0.00 | 0.00 | 6313869.67 | 0.00 | 0.00 | 0.242414E+10 | 0.00 | 1.56 |
September | 0.145402E+10 | 141483.55 | 0.00 | 3425812.61 | 2839.34 | 0.00 | 0.168183E+10 | 0.00 | 1.23 |
October | 0.217542E+10 | 0.00 | 0.00 | 879083.54 | 0.00 | 87953867.11 | 0.569711E+09 | 0.00 | 0.66 |
November | 0.187674E+10 | 0.00 | 0.00 | 42473.33 | 0.00 | 0.550185E+09 | 52624313.66 | 0.00 | 0.48 |
December | 0.112206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152891E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.184270E+11 | 26146776.61 | 0.00 | 32435459.36 | 2382066.10 | 0.442825E+10 | 0.149739E+11 | 0.00 | 0.90 |
Minimum of Months | 0.804454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.238482E+10 | 19117881.11 | 0.00 | 7310695.03 | 1561845.67 | 0.152891E+10 | 0.300352E+10 | 0.00 | 1.56 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:45
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.877763E+11 | 0.785726E+10 | 0.00 | 0.176936E+12 | 0.428283E+10 |
February | 0.133729E+12 | 0.857711E+10 | 0.00 | 0.166813E+12 | 0.277952E+10 |
March | 0.154969E+12 | 0.738766E+10 | 0.00 | 0.197584E+12 | 0.210288E+10 |
April | 0.394882E+12 | 0.683913E+10 | 0.00 | 0.254033E+12 | 0.691975E+10 |
May | 0.471100E+12 | 0.117895E+11 | 0.00 | 0.265787E+12 | 0.101333E+11 |
June | 0.471323E+12 | 0.894797E+10 | 0.00 | 0.272970E+12 | 0.338034E+11 |
July | 0.477277E+12 | 0.784945E+10 | 0.00 | 0.273969E+12 | 0.566957E+11 |
August | 0.394587E+12 | 0.618910E+10 | 0.00 | 0.256351E+12 | 0.714899E+11 |
September | 0.300142E+12 | 0.709839E+10 | 0.00 | 0.272470E+12 | 0.356702E+11 |
October | 0.142405E+12 | 0.824108E+10 | 0.00 | 0.222992E+12 | 0.160062E+10 |
November | 0.647106E+11 | 0.992441E+10 | 0.00 | 0.185995E+12 | 0.176721E+10 |
December | 0.341713E+11 | 0.122477E+11 | 0.00 | 0.162787E+12 | 0.401342E+10 |
Annual Sum or Average | 0.312707E+13 | 0.102949E+12 | 0.00 | 0.270869E+13 | 0.231259E+12 |
Minimum of Months | 0.341713E+11 | 0.618910E+10 | 0.00 | 0.162787E+12 | 0.160062E+10 |