Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2023-10-16 08:28:46
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2456.40 | 493.04 | 493.04 |
Net Site Energy | 2456.40 | 493.04 | 493.04 |
Total Source Energy | 7545.05 | 1514.41 | 1514.41 |
Net Source Energy | 7545.05 | 1514.41 | 1514.41 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1023.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 361.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 111.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 123.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 112.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2343.89 | 112.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 1023.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 361.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 111.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 17.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 123.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 112.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1023.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 361.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 111.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 17.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 123.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 112.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 95.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 230.35 | 22.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 145.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 470.45 | 22.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 95.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 230.35 | 22.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 145.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 470.45 | 22.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2343.885 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2343.885 | 100.00 |
Total On-Site and Utility Electric Sources | 2343.885 | 100.00 |
Total Electricity End Uses | 2343.885 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 747.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2280.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.1959 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.1959 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 10.1959 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 10.1959 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.1959 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 10.1959 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.1959 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.1959 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.1959 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.1959 | 18.58 | 8.0700 | |
Total | 4982.19 | 10.1959 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 10.1959 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 10.1959 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 13-JUN-15:09 | 03-JAN-12:09 | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 102325.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 30098.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 42072.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1224.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16006.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9464.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 191734.35 | 9464.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 102325.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 30098.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 7527.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1224.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 16006.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 9464.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3242.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1145.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 354.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 54.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 391.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 121.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7423.08 | 121.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 650.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 229.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 78.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1489.93 | 24.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 650.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 229.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 78.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1489.93 | 24.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.03 | 0.247691 | 0.262000 | 0.792749 | 0.660511 | 0.500000 | 0.001538 |
CORE_MID VAV BOX COMPONENT | 2.27 | 0.329487 | 0.336000 | 0.764270 | 0.878632 | 0.500000 | 0.001156 |
CORE_TOP VAV BOX COMPONENT | 2.48 | 0.302789 | 0.322000 | 0.797006 | 0.807437 | 0.500000 | 0.001258 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.811412 | 0.194712 | 0.207000 | 0.167962 | 0.519232 | 0.500000 | 0.001957 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.723673 | 0.138214 | 0.200000 | 0.144735 | 0.368571 | 0.500000 | 0.002757 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.791347 | 0.199649 | 0.213000 | 0.168557 | 0.532398 | 0.500000 | 0.001908 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.842438 | 0.118721 | 0.200000 | 0.168488 | 0.316590 | 0.500000 | 0.003209 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.690783 | 0.228714 | 0.242000 | 0.167169 | 0.609904 | 0.500000 | 0.001666 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.652495 | 0.153291 | 0.200000 | 0.130499 | 0.408777 | 0.500000 | 0.002485 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.671481 | 0.235288 | 0.249000 | 0.167199 | 0.627436 | 0.500000 | 0.001619 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.704663 | 0.141933 | 0.200000 | 0.140933 | 0.378489 | 0.500000 | 0.002684 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.701016 | 0.225375 | 0.230000 | 0.161234 | 0.601000 | 0.500000 | 0.001691 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.697306 | 0.143440 | 0.200000 | 0.139461 | 0.382507 | 0.500000 | 0.002656 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.682782 | 0.231394 | 0.236000 | 0.161137 | 0.617050 | 0.500000 | 0.001647 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.762137 | 0.131230 | 0.200000 | 0.152427 | 0.349947 | 0.500000 | 0.002903 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 26464.42 |
CORE_MID VAV BOX REHEAT COIL | 25513.69 |
CORE_TOP VAV BOX REHEAT COIL | 26606.52 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 5607.10 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 4831.69 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 5626.95 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 5624.64 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5580.63 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4356.46 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5581.61 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4704.77 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 5382.48 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 4655.65 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 5379.24 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 5088.50 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.87 | 1.40 | 5.75 | 1.40 | 5.31 | 5.31 | 0.300000 | 0.263500 | 5.31 |
PACU_VAV_MID | 2.56 | 1.38 | 5.12 | 1.38 | 4.62 | 4.62 | 0.300000 | 0.298248 | 4.62 |
PACU_VAV_TOP | 2.82 | 1.45 | 5.64 | 1.45 | 5.42 | 5.42 | 0.300000 | 0.266825 | 5.42 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.31 |
PACU_VAV_MID_OA_CONTROLLER | 4.62 |
PACU_VAV_TOP_OA_CONTROLLER | 5.42 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.31 | 130193.75 | 0.705107 | 1.77 | 43393.58 | 0.705107 |
PACU_VAV_MID COOLING COIL | 4.62 | 114777.36 | 0.701083 | 1.54 | 38255.29 | 0.701083 |
PACU_VAV_TOP COOLING COIL | 5.42 | 132627.08 | 0.705809 | 1.81 | 44204.61 | 0.705809 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 24649.84 |
PACU_VAV_MID HEATING COIL | 21466.16 |
PACU_VAV_TOP HEATING COIL | 25181.57 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.31 |
PACU_VAV_MID FAN | 4.62 |
PACU_VAV_TOP FAN | 5.42 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 35.030 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.265 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.196 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.266 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10028.011 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10028.011 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1338.332 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.332 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2113.993 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2113.993 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1338.244 | 10.196 | 189.427 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1338.244 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 6 | 0.167 | 1.328 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 6 | 0.167 | 1.313 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.592 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5188 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5277 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3941 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
39 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
40 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
41 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
42 | 6 | 0.22034119E-07 | 0.34186667E-09 | 0.51028043E-08 | -0.99966795E-13 |
43 | 5 | -0.15575685E-03 | 0.30726149E-05 | -0.80471308E-04 | 0.50596976E-08 |
44 | 4 | 0.25098773 | 0.15612093E-02 | 0.84928613E-01 | -0.27863917E-04 |
45 | 3 | -6.4488769 | 0.50236036E-01 | -2.0965073 | 0.25009644E-01 |
46 | 2 | 38.172500 | 0.18459162 | 14.265034 | -0.30329881 |
47 | 1 | -78.474946 | 0.85697261E-01 | -28.243456 | 1.0344939 |
48 | 0 | 46.824353 | 0.17727373E-02 | 16.313943 | |
49 | 6 | 0.22220471E-07 | 0.33897870E-09 | 0.51439591E-08 | -0.10094351E-12 |
50 | 5 | -0.15674173E-03 | 0.30417725E-05 | -0.80970714E-04 | 0.51000978E-08 |
51 | 4 | 0.25219758 | 0.15433791E-02 | 0.85360851E-01 | -0.28028645E-04 |
52 | 3 | -6.4729780 | 0.49601353E-01 | -2.1036496 | 0.25127351E-01 |
53 | 2 | 38.252148 | 0.18206636 | 14.294681 | -0.30418501 |
54 | 1 | -78.536155 | 0.84448529E-01 | -28.270134 | 1.0357980 |
55 | 0 | 46.824353 | 0.17453530E-02 | 16.313230 | |
56 | 6 | 0.18845480E-07 | 0.38509844E-09 | 0.43982754E-08 | -0.83379515E-13 |
57 | 5 | -0.13867918E-03 | 0.35672754E-05 | -0.71780061E-04 | 0.43666335E-08 |
58 | 4 | 0.22968634 | 0.18605187E-02 | 0.77334699E-01 | -0.24995801E-04 |
59 | 3 | -6.0237384 | 0.61253070E-01 | -1.9705638 | 0.22935651E-01 |
60 | 2 | 36.766583 | 0.22953206 | 13.740229 | -0.28766105 |
61 | 1 | -77.393480 | 0.10834582 | -27.770672 | 1.0114547 |
62 | 0 | 46.824361 | 0.22782066E-02 | 16.327018 | |
63 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
64 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
65 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
66 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
67 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
68 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
69 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
70 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
71 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
72 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
73 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
74 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
75 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
76 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
77 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
78 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
79 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
80 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
81 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
82 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
83 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
84 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
85 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
86 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
87 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
88 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
89 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
90 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
91 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
92 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
93 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
94 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
95 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
96 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
97 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
98 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
99 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
100 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
101 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
102 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
103 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.973 | 0.1730 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1249E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1650E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1816E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2152E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4050E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4283E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9164E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9329E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.5108E-002 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7439E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7057E-002 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6802E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6964E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1097E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2073E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2006E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1241E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1623E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1807E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2122E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4042E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4257E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9162E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9327E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9104E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2532E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4694E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9650E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4178E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7095E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7685E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7749E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7868E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8002E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4636E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4735E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2507E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2543E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4038E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4095E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7357E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7698E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3605E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3872E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0113E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0263E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9162E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9327E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4689E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3453E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9651E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0571E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6449E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.9615E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2073E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2006E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7361E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7705E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3610E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3881E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0119E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0280E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9164E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9329E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1536E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3582E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7497E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0856E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6836E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8239E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7686E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7749E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9533E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9753E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6585E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6789E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4266E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4392E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4040E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4097E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.0459E-002 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.5713E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.2192E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.5185E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.2506E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.8390E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6593E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.7065E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7919E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1860E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.3728E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9107E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.3486E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.6691E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6984E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7326E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.8571E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8106E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3179E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4685E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.9823E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.0628E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6593E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7065E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.0284E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2865E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6453E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0260E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6072E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7786E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6984E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7326E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.0455E-002 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.5709E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.2186E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.5181E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.2500E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.8387E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6589E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.7063E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7918E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1859E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.3726E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9106E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.3483E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.6690E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6980E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7324E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.8571E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8105E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3180E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4684E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.9822E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.0628E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6589E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7063E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.0283E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2863E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6452E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0258E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6069E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7784E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6980E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7324E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 41967.69460 | 41967.69460 | 3.02576 | 3.02576 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 0.42469 | 00:10:00 | 20.10000 | 1.47983E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 | |
3 | CORE_MID | Cooling | 31581.99261 | 31581.99261 | 2.27461 | 2.27461 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 1541.98484 | 1541.98484 | 6.55198E-002 | 0.42469 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 34050.95003 | 34050.95003 | 2.47517 | 2.47517 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 5249.17456 | 5249.17456 | 0.22028 | 0.42469 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 11161.37818 | 11161.37818 | 0.81141 | 0.81141 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 35.03000 | 1.71578E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 1687.81503 | 1687.81503 | 7.08879E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9954.48000 | 9954.48000 | 0.72367 | 0.72367 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:40:00 | 31.48833 | 1.71511E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 1090.41177 | 1090.41177 | 4.58175E-002 | 5.66790E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 10885.36528 | 10885.36528 | 0.79135 | 0.79135 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 1716.09077 | 1716.09077 | 7.21092E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11588.21211 | 11588.21211 | 0.84244 | 0.84244 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 1090.37207 | 1090.37207 | 4.58159E-002 | 5.66753E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 9502.56460 | 9502.56460 | 0.69078 | 0.69078 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 34.94500 | 1.71577E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 268.15502 | 268.15502 | 1.14469E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8975.89632 | 8975.89632 | 0.65249 | 0.65249 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 31.72917 | 1.71515E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 185.76125 | 185.76125 | 7.92748E-003 | 5.66790E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 9237.03456 | 9237.03456 | 0.67148 | 0.67148 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 35.20000 | 1.71581E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 303.59636 | 303.59636 | 1.29525E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9693.55451 | 9693.55451 | 0.70466 | 0.70466 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:30:00 | 34.35000 | 1.71565E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 185.75707 | 185.75707 | 7.92730E-003 | 5.66753E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 9642.98936 | 9642.98936 | 0.70102 | 0.70102 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 34.94500 | 1.71577E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 945.97544 | 945.97544 | 3.99557E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9591.98372 | 9591.98372 | 0.69731 | 0.69731 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:30:00 | 31.24750 | 1.71506E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 624.64695 | 624.64695 | 2.63816E-002 | 5.66790E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 9392.16152 | 9392.16152 | 0.68278 | 0.68278 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 35.20000 | 1.71581E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 990.50630 | 990.50630 | 4.18148E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10483.79848 | 10483.79848 | 0.76214 | 0.76214 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 624.63364 | 624.63364 | 2.63810E-002 | 5.66753E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 87836.97 | 5.30759 | 5.30759 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
3 | PACU_VAV_MID | Cooling | Sensible | 78394.78 | 4.62208 | 4.62208 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
5 | PACU_VAV_TOP | Cooling | Sensible | 89321.52 | 5.42209 | 5.42209 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.02576 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24769 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79275 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66051 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.53820E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26464.41883 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.27461 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32949 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33600 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76427 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87863 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.15634E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25513.69455 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.47517 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30279 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32200 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79701 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80744 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.25830E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26606.52476 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81141 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19471 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20700 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16796 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51923 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.95674E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5607.10075 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72367 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13821 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14473 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36857 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.75659E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4831.68918 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79135 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19965 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21300 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16856 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53240 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.90835E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5626.95059 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84244 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11872 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16849 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31659 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.20920E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5624.63875 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69078 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22871 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16717 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60990 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.66584E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5580.63252 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65249 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15329 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13050 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40878 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.48546E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4356.45761 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67148 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23529 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24900 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16720 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62744 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61929E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5581.61060 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70466 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14193 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14093 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37849 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.68436E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4704.76509 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70102 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22538 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16123 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60100 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.69051E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5382.48199 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69731 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14344 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13946 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38251 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.65616E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4655.64719 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68278 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23139 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23600 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16114 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61705 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.64654E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5379.24048 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76214 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13123 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15243 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34995 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90330E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5088.49692 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.87259 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39855 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.74518 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.39855 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.30759 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.30759 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.26350 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.55893 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37853 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.11785 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.37853 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.62208 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.62208 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.29825 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.82202 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.44675 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.64404 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.44675 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.42209 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.42209 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.26682 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.30759 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.62208 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.42209 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.30759 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.30759 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 130193.74899 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70511 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.76902 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 43393.57654 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70511 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 24649.83527 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.30759 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.62208 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.62208 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 114777.36013 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.54054 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 38255.29413 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 21466.16203 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.62208 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.42209 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.42209 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 132627.08203 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70581 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.80718 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 44204.60644 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70581 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 25181.57446 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.42209 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 129931.09 | 443343.27 | 11.62 | 2.97 | 3.33 | 3.52 | 3.64 | 10.13 | 11.37 | 12.00 | 12.41 | 6.1359 | 4.8630 | 3.2750 | 1.4036 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 114589.90 | 390996.97 | 11.65 | 2.97 | 3.34 | 3.52 | 3.64 | 10.14 | 11.39 | 12.03 | 12.43 | 5.3434 | 4.2299 | 2.8465 | 1.2270 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 132347.68 | 451589.04 | 11.62 | 2.97 | 3.33 | 3.51 | 3.64 | 10.12 | 11.36 | 11.99 | 12.41 | 6.2683 | 4.9683 | 3.3460 | 1.4334 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.3970712862 | 0.3479982788 | Pass | Pass | 0.2216663838 | 0.4128566988 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.2775528579E-002 | 9.4644792353E-002 | Pass | Pass | 0.2318682437 | 0.5122470900 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.0344419572E-002 | 6.5576792026E-002 | Pass | Pass | 0.3005921218 | 0.9740143149 | Fail | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.4260547794E-002 | 6.9154270533E-002 | Pass | Pass | 0.8731715956 | 7.0627824747 | Pass | Fail |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.2268631949 | 0.2852952449 | Pass | Pass | 0.1840264918 | 0.3850234928 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.2218262117 | 0.2956838388 | Pass | Pass | 0.1889239046 | 0.3884777042 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2160984421 | 0.3036308754 | Pass | Pass | 0.1942460727 | 0.3962961179 | Pass | Fail |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2794918286 | 0.3973954287 | Pass | Pass | 0.1915124288 | 0.3901270329 | Pass | Fail |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2294562277 | 0.3431900517 | Pass | Pass | 0.2100600589 | 0.4354850911 | Pass | Fail |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3079662103 | 0.4340109789 | Pass | Pass | 0.1900799648 | 0.3882550602 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3495395853 | 0.3216030307 | Pass | Pass | 0.2190560555 | 0.4115880373 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4102562807 | 0.3824972113 | Pass | Pass | 0.2190076931 | 0.4115607714 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3461486575 | 0.3313928064 | Pass | Pass | 0.2293374034 | 0.4276568010 | Pass | Fail |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4308073943 | 0.4029982464 | Pass | Pass | 0.2190179899 | 0.4111598418 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2172783504 | 0.2891735776 | Pass | Pass | 0.1849926911 | 0.3862243718 | Pass | Fail |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2804062834 | 0.3778380996 | Pass | Pass | 0.1854985189 | 0.3860561351 | Pass | Fail |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2203134606 | 0.3096454441 | Pass | Pass | 0.1989580409 | 0.4161086911 | Pass | Fail |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2964243682 | 0.3991290794 | Pass | Pass | 0.1852389209 | 0.3857986878 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3158.80 | -184.2 | 0.00 | -2074.5 | 5062.18 | 5962.26 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 195.79 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 456.84 | 3.241 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.1959 | 983.54 | 10028.01 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.95 | 0.0000 | Y | 86.50 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.35 | 0.0000 | Y | 10.46 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.49 | 0.0000 | Y | 6.65 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.25 | 0.0000 | Y | 10.42 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.22 | 0.0000 | Y | 6.59 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.30 | 0.0000 | Y | 10.44 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.44 | 0.0000 | Y | 6.64 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.22 | 0.0000 | Y | 10.40 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.18 | 0.0000 | Y | 6.58 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.35 | 0.0000 | Y | 10.46 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.1959 | 131.26 | 1338.33 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.48 | 0.0000 | Y | 6.65 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.1959 | 207.34 | 2113.99 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.25 | 0.0000 | Y | 10.42 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.1959 | 131.25 | 1338.24 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.22 | 0.0000 | Y | 6.59 |
Interior Lighting Total | 10.1959 | 4982.19 | 50797.72 | 361.78 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.33 | 513.25 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.33 | 186.70 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 2113.99 | 810.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2113.99 | 294.90 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1338.24 | 513.22 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1338.24 | 186.69 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.28 | AstronomicalClock | - | 41.93 | 41.93 | 4.43 | |
EXTERIOR_LIGHTS_B | 8033.20 | AstronomicalClock | - | 83.83 | 71.26 | 107.46 | |
Exterior Lighting Total | 8596.48 | 111.89 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 130193.75 | 91800.54 | 38393.20 | 0.71 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 114777.36 | 80468.48 | 34308.88 | 0.70 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 132627.08 | 93609.39 | 39017.69 | 0.71 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 129931.1 | 2.97 | 10.13 | N/A | N/A | 11.62 | |
PACU_VAV_MID COOLING COIL | 114589.9 | 2.97 | 10.14 | N/A | N/A | 11.65 | |
PACU_VAV_TOP COOLING COIL | 132347.7 | 2.97 | 10.12 | N/A | N/A | 11.62 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 26464.42 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 25513.69 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 26606.52 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5607.10 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4831.69 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5626.95 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5624.64 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5580.63 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4356.46 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5581.61 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4704.77 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5382.48 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4655.65 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5379.24 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5088.50 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 24649.84 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 21466.16 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 25181.57 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.31 | 11543.42 | 2174.89 | 1.00 | 1.14 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.62 | 10117.79 | 2189.01 | 1.00 | 1.14 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.42 | 11792.43 | 2174.89 | 1.00 | 1.14 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.97 | 0.17 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 129931.09 | 2.97 | 10.13 | 11.62 | 6.1359 | 3.33 | 11.37 | 4.8630 | 3.52 | 12.00 | 3.2750 | 3.64 | 12.41 | 1.4036 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 114589.90 | 2.97 | 10.14 | 11.65 | 5.3434 | 3.34 | 11.39 | 4.2299 | 3.52 | 12.03 | 2.8465 | 3.64 | 12.43 | 1.2270 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 132347.68 | 2.97 | 10.12 | 11.62 | 6.2683 | 3.33 | 11.36 | 4.9683 | 3.51 | 11.99 | 3.3460 | 3.64 | 12.41 | 1.4334 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 41967.69 | 41967.69 | 42.67 | 3.026 | 3.026 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00879 | 28.91 | 0.01715 | 0.425 | 0.00 |
CORE_MID | 31581.99 | 31581.99 | 32.11 | 2.275 | 2.275 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 28.91 | 0.01715 | 0.425 | 0.00 |
CORE_TOP | 34050.95 | 34050.95 | 34.62 | 2.475 | 2.475 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 24.00 | 24.00 | 0.00885 | 35.20 | 0.01716 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 11161.38 | 11161.38 | 53.83 | 0.811 | 0.811 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 24.00 | 24.00 | 0.00902 | 35.03 | 0.01716 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9954.48 | 9954.48 | 75.84 | 0.724 | 0.724 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:40:00 | 24.00 | 24.00 | 0.00888 | 31.49 | 0.01715 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10885.37 | 10885.37 | 52.50 | 0.791 | 0.791 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 24.00 | 24.00 | 0.00903 | 35.20 | 0.01716 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11588.21 | 11588.21 | 88.29 | 0.842 | 0.842 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00883 | 34.58 | 0.01716 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 9502.56 | 9502.56 | 45.83 | 0.691 | 0.691 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 24.00 | 24.00 | 0.00895 | 34.95 | 0.01716 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8975.90 | 8975.90 | 68.38 | 0.652 | 0.652 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 24.00 | 24.00 | 0.00881 | 31.73 | 0.01715 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9237.03 | 9237.03 | 44.55 | 0.671 | 0.671 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 24.00 | 24.00 | 0.00896 | 35.20 | 0.01716 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9693.55 | 9693.55 | 73.85 | 0.705 | 0.705 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:30:00 | 24.00 | 24.00 | 0.00879 | 34.35 | 0.01716 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9642.99 | 9642.99 | 46.51 | 0.701 | 0.701 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 24.00 | 24.00 | 0.00904 | 34.95 | 0.01716 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9591.98 | 9591.98 | 73.07 | 0.697 | 0.697 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:30:00 | 24.00 | 24.00 | 0.00886 | 31.25 | 0.01715 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9392.16 | 9392.16 | 45.30 | 0.683 | 0.683 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 24.00 | 24.00 | 0.00906 | 35.20 | 0.01716 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10483.80 | 10483.80 | 79.87 | 0.762 | 0.762 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00883 | 34.58 | 0.01716 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 0.425 | 00:10:00 | 15.60 | 21.94 | 0.01480 | 20.10 | 0.01480 | 0.425 | 0.00 | |
CORE_MID | 1541.98 | 1541.98 | 1.57 | 0.066 | 0.425 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 20.10 | 0.01480 | 0.425 | 0.00 |
CORE_TOP | 5249.17 | 5249.17 | 5.34 | 0.220 | 0.425 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 20.10 | 0.01480 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 1687.82 | 1687.82 | 8.14 | 0.071 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01127 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 1090.41 | 1090.41 | 8.31 | 0.046 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01132 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 1716.09 | 1716.09 | 8.28 | 0.072 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01122 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 1090.37 | 1090.37 | 8.31 | 0.046 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01132 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 268.16 | 268.16 | 1.29 | 0.011 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01236 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 185.76 | 185.76 | 1.42 | 0.008 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01233 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 303.60 | 303.60 | 1.46 | 0.013 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01219 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 185.76 | 185.76 | 1.42 | 0.008 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01233 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 945.98 | 945.98 | 4.56 | 0.040 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01168 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 624.65 | 624.65 | 4.76 | 0.026 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01173 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 990.51 | 990.51 | 4.78 | 0.042 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01162 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 624.63 | 624.63 | 4.76 | 0.026 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01173 | 20.10 | 0.01480 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.31 | 5.31 | 0.00 | 0.00 | 5.3076 | 1.3985 | 5.3076 | 0.2635 | 0.3000 |
PACU_VAV_MID | 4.62 | 4.62 | 0.00 | 0.00 | 4.6221 | 1.3785 | 4.6221 | 0.2982 | 0.3000 |
PACU_VAV_TOP | 5.42 | 5.42 | 0.00 | 0.00 | 5.4221 | 1.4467 | 5.4221 | 0.2668 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 26464.419 | 26464.419 | -999.0 | -999.0 | -999.000 | 12/21 00:10:00 | 12/21 00:10:00 | 26464.42 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 25513.695 | 25513.695 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25513.69 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800241 | 51.7082 | 1541.98 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 26606.525 | 26606.525 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26606.52 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 5249.17 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 5607.101 | 5607.101 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5607.10 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01127242 | 72.4497 | 1687.82 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 4831.689 | 4831.689 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4831.69 | 1892.12 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01132478 | 72.7796 | 1090.41 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 5626.951 | 5626.951 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5626.95 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01122352 | 72.1408 | 1716.09 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 5624.639 | 5624.639 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5624.64 | 1892.00 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01132485 | 72.7801 | 1090.37 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5580.633 | 5580.633 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5580.63 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01236185 | 79.3255 | 268.16 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4356.458 | 4356.458 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4356.46 | 1892.12 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01233289 | 79.1431 | 185.76 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 5581.611 | 5581.611 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5581.61 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01218540 | 78.2148 | 303.60 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4704.765 | 4704.765 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4704.77 | 1892.00 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01233295 | 79.1435 | 185.76 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 5382.482 | 5382.482 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5382.48 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01168417 | 75.0526 | 945.98 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 4655.647 | 4655.647 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4655.65 | 1892.12 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01173036 | 75.3433 | 624.65 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 5379.240 | 5379.240 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5379.24 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01162462 | 74.6768 | 990.51 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 5088.497 | 5088.497 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5088.50 | 1892.00 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01173042 | 75.3437 | 624.63 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 130193.749 | 91800.544 | 5.307591 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 132611.99 | 96546.45 | 5.307591 | 26.53 | 19.06 | 0.01073326 | 11.04 | 11.04 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 22.5181 | 24.00 | 0.00885794 | 47.6377 | 72770.55 | 0.00 | 134247.23 | 93359.44 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 24649.835 | 24649.835 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 24649.84 | 24649.84 | 1.592277 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 75.0604 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 114777.360 | 80468.481 | 4.622084 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | 118232.76 | 83070.86 | 4.622084 | 26.86 | 19.44 | 0.01108550 | 11.03 | 11.03 | 0.00850000 | 35.03 | 0.01715783 | 25.79 | 25.8578 | 24.00 | 0.00896080 | 48.1839 | 63429.22 | 0.00 | 118350.86 | 81871.18 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 21466.162 | 21466.162 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 21466.16 | 21466.16 | 1.386625 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 86.1927 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 132627.082 | 93609.387 | 5.422085 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 135104.31 | 98166.63 | 5.422085 | 26.45 | 19.04 | 0.01073839 | 11.04 | 11.04 | 0.00850000 | 35.12 | 0.01715799 | 25.81 | 22.0426 | 24.00 | 0.00891745 | 47.9543 | 74402.66 | 0.00 | 136756.32 | 95205.55 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 25181.574 | 25181.574 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 25181.57 | 25181.57 | 1.626626 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 73.4754 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 26464.419 | 26464.419 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 26464.42 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26464.42 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 25513.695 | 25513.695 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25513.69 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25513.69 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.84 | 0.00800241 | 21.00 | 0.00800241 | 51.7082 | 1541.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 26606.525 | 26606.525 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26606.52 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26606.52 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.66 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 5249.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5607.101 | 5607.101 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5607.10 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5607.10 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.56 | 0.01127242 | 21.00 | 0.01127242 | 72.4497 | 1687.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4831.689 | 4831.689 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4831.69 | 1892.12 | 1.0000 | 0.06821858 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4831.69 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.56 | 0.01132478 | 21.00 | 0.01132478 | 72.7796 | 1090.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5626.951 | 5626.951 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5626.95 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5626.95 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.56 | 0.01122352 | 21.00 | 0.01122352 | 72.1408 | 1716.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5624.639 | 5624.639 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5624.64 | 1892.00 | 1.0000 | 0.06821410 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5624.64 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.56 | 0.01132485 | 21.00 | 0.01132485 | 72.7801 | 1090.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5580.633 | 5580.633 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5580.63 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5580.63 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.93 | 0.01236185 | 21.00 | 0.01236185 | 79.3255 | 268.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4356.458 | 4356.458 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4356.46 | 1892.12 | 1.0000 | 0.06821858 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4356.46 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.92 | 0.01233289 | 21.00 | 0.01233289 | 79.1431 | 185.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5581.611 | 5581.611 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5581.61 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5581.61 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.92 | 0.01218540 | 21.00 | 0.01218540 | 78.2148 | 303.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4704.765 | 4704.765 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4704.77 | 1892.00 | 1.0000 | 0.06821410 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4704.77 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.92 | 0.01233295 | 21.00 | 0.01233295 | 79.1435 | 185.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5382.482 | 5382.482 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5382.48 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5382.48 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.73 | 0.01168417 | 21.00 | 0.01168417 | 75.0526 | 945.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4655.647 | 4655.647 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4655.65 | 1892.12 | 1.0000 | 0.06821858 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4655.65 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.72 | 0.01173036 | 21.00 | 0.01173036 | 75.3433 | 624.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5379.240 | 5379.240 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5379.24 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5379.24 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.72 | 0.01162462 | 21.00 | 0.01162462 | 74.6768 | 990.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5088.497 | 5088.497 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5088.50 | 1892.00 | 1.0000 | 0.06821410 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5088.50 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.72 | 0.01173042 | 21.00 | 0.01173042 | 75.3437 | 624.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 130193.749 | 91800.544 | 5.307591 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7926 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.307591 | 6.38819034 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | Sensible | 132611.99 | 96546.45 | 1.0186 | 6.38819034 | 5.307591 | 26.53 | 19.06 | 0.01073326 | 54030.3 | 11.04 | 11.04 | 0.00850000 | 32522.5 | -999.0 | -999.00 | -999.00 | -999.00 | 11543.419 | 121068.57 | 35.20 | 0.01715815 | 25.83 | 1.19517000 | 22.5181 | 24.00 | 0.00885794 | 24.00 | 0.00885794 | 47.6377 | 72770.55 | 0.00 | 134247.23 | 93359.44 | 6.13590511 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.76 | 11.74 | 0.00857198 | 33443.4 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24649.835 | 24649.835 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.307591 | 6.38819034 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 24649.84 | 24649.84 | 1.0000 | 1.91645710 | 1.592277 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24649.84 | 0.00 | 0.00000000 | -6.26 | 1.19517000 | 75.0604 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | ||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 114777.360 | 80468.481 | 4.622084 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.96935 | 1025.4474 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.622084 | 5.56311746 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | Sensible | 118232.76 | 83070.86 | 1.0301 | 5.56311746 | 4.622084 | 26.86 | 19.44 | 0.01108550 | 55265.3 | 11.03 | 11.03 | 0.00850000 | 32512.0 | -999.0 | -999.00 | -999.00 | -999.00 | 10117.793 | 108114.97 | 35.03 | 0.01715783 | 25.79 | 1.19517000 | 25.8578 | 24.00 | 0.00896080 | 24.00 | 0.00896080 | 48.1839 | 63429.22 | 0.00 | 118350.86 | 81871.18 | 5.34341637 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.63 | 0.00850793 | 33173.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 21466.162 | 21466.162 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.622084 | 5.56311746 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 21466.16 | 21466.16 | 1.0000 | 1.66893524 | 1.386625 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21466.16 | 0.00 | 0.00000000 | -6.26 | 1.19517000 | 86.1927 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | ||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 132627.082 | 93609.387 | 5.422085 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8021 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.422085 | 6.52599455 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | Sensible | 135104.31 | 98166.63 | 1.0187 | 6.52599455 | 5.422085 | 26.45 | 19.04 | 0.01073839 | 53966.8 | 11.04 | 11.04 | 0.00850000 | 32522.5 | -999.0 | -999.00 | -999.00 | -999.00 | 11792.430 | 123311.88 | 35.12 | 0.01715799 | 25.81 | 1.19517000 | 22.0426 | 24.00 | 0.00891745 | 24.00 | 0.00891745 | 47.9543 | 74402.66 | 0.00 | 136756.32 | 95205.55 | 6.26826710 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.79 | 11.77 | 0.00858568 | 33505.1 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25181.574 | 25181.574 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.422085 | 6.52599455 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 25181.57 | 25181.57 | 1.0000 | 1.95779837 | 1.626626 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25181.57 | 0.00 | 0.00000000 | -6.26 | 1.19517000 | 73.4754 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 5942.67 | 0.00 | 0.00 |
CORE_MID | 5553.17 | 1.33 | 0.00 |
CORE_TOP | 5373.83 | 16.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 5771.83 | 682.00 | 660.67 |
PERIMETER_TOP_ZN_2 | 5682.50 | 754.17 | 730.67 |
PERIMETER_TOP_ZN_1 | 5861.17 | 769.50 | 767.17 |
PERIMETER_TOP_ZN_4 | 5333.00 | 728.00 | 564.83 |
PERIMETER_BOT_ZN_3 | 5934.00 | 274.67 | 274.67 |
PERIMETER_BOT_ZN_2 | 5939.67 | 474.00 | 474.00 |
PERIMETER_BOT_ZN_1 | 5942.00 | 1862.00 | 1862.00 |
PERIMETER_BOT_ZN_4 | 5928.67 | 372.17 | 372.17 |
PERIMETER_MID_ZN_3 | 5903.00 | 483.67 | 482.17 |
PERIMETER_MID_ZN_2 | 4885.00 | 581.00 | 579.00 |
PERIMETER_MID_ZN_1 | 5930.33 | 634.17 | 634.17 |
PERIMETER_MID_ZN_4 | 5638.17 | 489.17 | 470.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5942.83 | 2393.17 | 2280.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.50 | 0.00 | 0.17 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 57.33 | 0.00 | 51.67 |
PERIMETER_TOP_ZN_2 | 0.00 | 94.50 | 0.00 | 91.67 |
PERIMETER_TOP_ZN_1 | 0.00 | 86.50 | 0.00 | 82.33 |
PERIMETER_TOP_ZN_4 | 0.00 | 66.67 | 0.00 | 56.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 18.67 | 0.00 | 16.33 |
PERIMETER_BOT_ZN_2 | 0.00 | 67.17 | 0.00 | 66.67 |
PERIMETER_BOT_ZN_1 | 0.00 | 613.67 | 0.00 | 613.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 52.83 | 0.00 | 44.50 |
PERIMETER_MID_ZN_3 | 0.00 | 26.50 | 0.00 | 24.50 |
PERIMETER_MID_ZN_2 | 0.00 | 65.00 | 0.00 | 64.83 |
PERIMETER_MID_ZN_1 | 0.00 | 82.83 | 0.00 | 82.50 |
PERIMETER_MID_ZN_4 | 0.00 | 51.33 | 0.00 | 44.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 762.67 | 0.00 | 747.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.463 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.441 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.439 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.627 | 0.055 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.787 | 0.058 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.686 | 0.055 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.800 | 0.058 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.544 | 0.029 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.672 | 0.031 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.684 | 1.244 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.671 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.636 | 0.046 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.753 | 0.051 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.696 | 0.046 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.800 | 0.048 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.51 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.48 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 7736486.19 | 0.00 | 7736486.19 | 0.00 | 7736486.19 | 13393058.27 | 8223.82 | 117.86 | 418.33 | 357.42 |
CORE_MID | 7221676.93 | 0.00 | 7221676.93 | 0.00 | 7221676.93 | 13393058.27 | 8731.79 | 8.11 | 20.10 | 245.84 |
CORE_TOP | 7194344.61 | 0.00 | 7194344.61 | 0.00 | 7194344.61 | 13393058.27 | 8745.15 | 3.14 | 11.72 | 251.71 |
PERIMETER_TOP_ZN_3 | 2133475.87 | 0.00 | 2133475.87 | 330276.95 | 2463752.82 | 2823374.22 | 4762.35 | 51.79 | 3945.86 | 251.71 |
PERIMETER_TOP_ZN_2 | 1699460.42 | 0.00 | 1699460.42 | 220183.31 | 1919643.73 | 1787429.43 | 3399.59 | 1.73 | 5358.68 | 251.71 |
PERIMETER_TOP_ZN_1 | 2326975.63 | 0.00 | 2326975.63 | 330276.95 | 2657252.58 | 2823374.22 | 4542.01 | 33.29 | 4184.70 | 251.71 |
PERIMETER_TOP_ZN_4 | 1739379.12 | 0.00 | 1739379.12 | 220183.31 | 1959562.43 | 1787312.18 | 3430.05 | 17.68 | 5312.28 | 251.71 |
PERIMETER_BOT_ZN_3 | 1894871.08 | 0.00 | 1894871.08 | 175608.30 | 2070479.38 | 2823374.22 | 5725.26 | 249.38 | 2785.37 | 357.42 |
PERIMETER_BOT_ZN_2 | 1481336.13 | 0.00 | 1481336.13 | 117071.50 | 1598407.62 | 1787429.43 | 3393.94 | 46.99 | 5319.07 | 357.42 |
PERIMETER_BOT_ZN_1 | 2344260.74 | 0.00 | 2344260.74 | 4121307.75 | 6465568.50 | 2823374.22 | 4472.18 | 40.52 | 4247.30 | 357.42 |
PERIMETER_BOT_ZN_4 | 1487843.11 | 0.00 | 1487843.11 | 117071.50 | 1604914.61 | 1787312.18 | 3713.81 | 98.75 | 4947.44 | 357.42 |
PERIMETER_MID_ZN_3 | 2160284.73 | 0.00 | 2160284.73 | 274931.61 | 2435216.34 | 2823374.22 | 4633.61 | 55.67 | 4070.73 | 245.84 |
PERIMETER_MID_ZN_2 | 1697990.61 | 0.00 | 1697990.61 | 183286.64 | 1881277.25 | 1787429.43 | 3409.60 | 2.24 | 5348.16 | 1154.84 |
PERIMETER_MID_ZN_1 | 2356128.24 | 0.00 | 2356128.24 | 274931.61 | 2631059.85 | 2823374.22 | 4441.10 | 28.87 | 4290.03 | 245.84 |
PERIMETER_MID_ZN_4 | 1732759.81 | 0.00 | 1732759.81 | 183286.64 | 1916046.45 | 1787312.18 | 3462.46 | 18.18 | 5279.36 | 245.84 |
Total Facility | 45207273.21 | 0.00 | 45207273.21 | 6548416.08 | 51755689.29 | 67843644.98 | 8760.00 | 663.10 | 5641.45 | 1334.18 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3362 | 0.0000 | 0.3362 | 0.0000 | 0.3362 | 0.4247 | 5421.07 | 117.46 | 404.47 |
CORE_MID | 0.3204 | 0.0000 | 0.3204 | 0.0000 | 0.3204 | 0.4247 | 5920.97 | 7.69 | 14.34 |
CORE_TOP | 0.3189 | 0.0000 | 0.3189 | 0.0000 | 0.3189 | 0.4247 | 5931.96 | 3.00 | 8.04 |
PERIMETER_TOP_ZN_3 | 0.0960 | 0.0000 | 0.0960 | 0.0084 | 0.1043 | 0.0895 | 1961.41 | 50.82 | 3930.78 |
PERIMETER_TOP_ZN_2 | 0.0763 | 0.0000 | 0.0763 | 0.0056 | 0.0819 | 0.0567 | 831.67 | 1.16 | 5110.18 |
PERIMETER_TOP_ZN_1 | 0.1050 | 0.0000 | 0.1050 | 0.0084 | 0.1134 | 0.0895 | 1737.92 | 32.79 | 4172.29 |
PERIMETER_TOP_ZN_4 | 0.0775 | 0.0000 | 0.0775 | 0.0056 | 0.0831 | 0.0567 | 863.70 | 17.34 | 5061.95 |
PERIMETER_BOT_ZN_3 | 0.0833 | 0.0000 | 0.0833 | 0.0044 | 0.0877 | 0.0895 | 2918.12 | 248.09 | 2776.78 |
PERIMETER_BOT_ZN_2 | 0.0651 | 0.0000 | 0.0651 | 0.0030 | 0.0681 | 0.0567 | 927.66 | 45.27 | 4970.06 |
PERIMETER_BOT_ZN_1 | 0.1043 | 0.0000 | 0.1043 | 0.1889 | 0.2931 | 0.0895 | 1667.03 | 39.25 | 4236.72 |
PERIMETER_BOT_ZN_4 | 0.0650 | 0.0000 | 0.0650 | 0.0030 | 0.0680 | 0.0567 | 1250.84 | 98.37 | 4593.79 |
PERIMETER_MID_ZN_3 | 0.0973 | 0.0000 | 0.0973 | 0.0070 | 0.1043 | 0.0895 | 1828.24 | 55.30 | 4059.46 |
PERIMETER_MID_ZN_2 | 0.0729 | 0.0000 | 0.0729 | 0.0049 | 0.0779 | 0.0567 | 834.31 | 0.88 | 4198.80 |
PERIMETER_MID_ZN_1 | 0.1065 | 0.0000 | 0.1065 | 0.0070 | 0.1135 | 0.0895 | 1634.52 | 28.44 | 4280.03 |
PERIMETER_MID_ZN_4 | 0.0775 | 0.0000 | 0.0775 | 0.0046 | 0.0822 | 0.0567 | 889.82 | 17.95 | 5035.23 |
Total Facility | 2.0023 | 0.0000 | 2.0023 | 0.2507 | 2.2530 | 2.1513 | 5943.00 | 655.54 | 5216.27 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 21649650.46 | 0.00 | 21649650.46 | 22614548.33 | 3280.74 | 0.00 | 5479.26 | 357.42 |
PACU_VAV_MID | 21974210.09 | 0.00 | 21974210.09 | 22614548.33 | 3398.53 | 0.00 | 5361.47 | 245.84 |
PACU_VAV_TOP | 21865262.56 | 0.00 | 21865262.56 | 22614548.33 | 3390.51 | 0.00 | 5369.49 | 251.71 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9473 | 0.0000 | 0.9473 | 0.7171 | 821.16 | 0.00 | 5121.84 |
PACU_VAV_MID | 0.9822 | 0.0000 | 0.9822 | 0.7171 | 827.37 | 0.00 | 5115.63 |
PACU_VAV_TOP | 0.9760 | 0.0000 | 0.9760 | 0.7171 | 825.22 | 0.00 | 5117.78 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5479.26 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5361.47 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5369.49 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0994 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1412 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1335 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 829 |
Defaulted Fields | 545 |
Fields with Defaults | 2217 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2343.89 | 13177.94 | 11-JUN-17:10 | 191734.35 | 13-JUN-15:10 |
Electricity:Building | 1067.21 | 12933.60 | 11-JUN-17:10 | 78335.97 | 18-DEC-16:50 |
Electricity:Zone:CORE_BOTTOM | 322.66 | 4214.70 | 01-JAN-00:10 | 25737.69 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1067.21 | 12933.60 | 11-JUN-17:10 | 78335.97 | 18-DEC-16:50 |
InteriorLights:Electricity | 361.78 | 1672.11 | 01-JAN-08:50 | 36263.56 | 18-DEC-16:50 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 361.78 | 1672.11 | 01-JAN-08:50 | 36263.56 | 18-DEC-16:50 |
LightsWired:InteriorLights:Electricity | 361.78 | 1672.11 | 01-JAN-08:50 | 36263.56 | 18-DEC-16:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 361.78 | 1672.11 | 01-JAN-08:50 | 36263.56 | 18-DEC-16:50 |
Electricity:Zone:CORE_MID | 201.92 | 2251.11 | 01-JAN-00:10 | 14360.82 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 201.92 | 2251.11 | 01-JAN-00:10 | 14360.82 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 86.50 | 419.57 | 01-JAN-00:10 | 7552.50 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 34.79 | 428.29 | 07-MAY-17:10 | 2823.85 | 02-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.46 | 42.19 | 01-JAN-08:30 | 1388.60 | 02-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.46 | 42.19 | 01-JAN-08:30 | 1388.60 | 02-JAN-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.06 | 273.73 | 11-JUN-17:10 | 1787.68 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.65 | 26.71 | 01-JAN-07:20 | 879.10 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.65 | 26.71 | 01-JAN-07:20 | 879.10 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 34.75 | 432.40 | 12-MAR-17:10 | 2823.84 | 09-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.42 | 42.19 | 01-JAN-07:40 | 1388.60 | 09-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.42 | 42.19 | 01-JAN-07:40 | 1388.60 | 09-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 21.99 | 271.13 | 12-MAR-17:10 | 1787.61 | 18-DEC-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.59 | 26.71 | 01-JAN-08:50 | 879.04 | 18-DEC-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.59 | 26.71 | 01-JAN-08:50 | 879.04 | 18-DEC-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 34.77 | 428.29 | 07-MAY-17:10 | 2823.85 | 02-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.44 | 42.19 | 01-JAN-08:30 | 1388.60 | 02-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.44 | 42.19 | 01-JAN-08:30 | 1388.60 | 02-JAN-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.05 | 273.73 | 29-MAY-17:10 | 1787.68 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.64 | 26.71 | 01-JAN-07:20 | 879.10 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.64 | 26.71 | 01-JAN-07:20 | 879.10 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 34.74 | 432.40 | 12-MAR-17:10 | 2823.84 | 09-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.40 | 42.19 | 01-JAN-07:40 | 1388.60 | 09-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.40 | 42.19 | 01-JAN-07:40 | 1388.60 | 09-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 21.98 | 271.13 | 12-MAR-17:10 | 1787.61 | 18-DEC-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.58 | 26.71 | 01-JAN-08:40 | 879.04 | 18-DEC-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.58 | 26.71 | 01-JAN-08:40 | 879.04 | 18-DEC-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 34.79 | 428.29 | 07-MAY-17:10 | 2823.85 | 02-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 10.46 | 42.19 | 01-JAN-08:30 | 1388.60 | 02-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 10.46 | 42.19 | 01-JAN-08:30 | 1388.60 | 02-JAN-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.06 | 273.73 | 11-JUN-17:10 | 1787.68 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.65 | 26.71 | 01-JAN-07:20 | 879.10 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.65 | 26.71 | 01-JAN-07:20 | 879.10 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 34.75 | 432.40 | 12-MAR-17:10 | 2823.84 | 09-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 10.42 | 42.19 | 01-JAN-07:40 | 1388.60 | 09-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 10.42 | 42.19 | 01-JAN-07:40 | 1388.60 | 09-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 21.99 | 271.13 | 12-MAR-17:10 | 1787.61 | 18-DEC-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.59 | 26.71 | 01-JAN-08:50 | 879.04 | 18-DEC-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.59 | 26.71 | 01-JAN-08:50 | 879.04 | 18-DEC-16:50 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 1164.63 | 243.72 | 01-JAN-00:10 | 119556.25 | 13-JUN-15:10 |
ExteriorEquipment:Electricity | 17.11 | 243.72 | 01-JAN-00:10 | 1236.27 | 18-DEC-17:00 |
Transformer:ExteriorEquipment:Electricity | 17.11 | 243.72 | 01-JAN-00:10 | 1236.27 | 18-DEC-17:00 |
ElectricityPurchased:Facility | 2343.89 | 13177.94 | 11-JUN-17:10 | 191734.35 | 13-JUN-15:10 |
ElectricityPurchased:Plant | 2343.89 | 13177.94 | 11-JUN-17:10 | 191734.35 | 13-JUN-15:10 |
Cogeneration:ElectricityPurchased | 2343.89 | 13177.94 | 11-JUN-17:10 | 191734.35 | 13-JUN-15:10 |
General:Cogeneration:ElectricityPurchased | 2343.89 | 13177.94 | 11-JUN-17:10 | 191734.35 | 13-JUN-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2343.89 | 13177.94 | 11-JUN-17:10 | 191734.35 | 13-JUN-15:10 |
ElectricityNet:Plant | 2343.89 | 13177.94 | 11-JUN-17:10 | 191734.35 | 13-JUN-15:10 |
Cogeneration:ElectricityNet | 2343.89 | 13177.94 | 11-JUN-17:10 | 191734.35 | 13-JUN-15:10 |
General:Cogeneration:ElectricityNet | 2343.89 | 13177.94 | 11-JUN-17:10 | 191734.35 | 13-JUN-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity | 123.56 | 0.00 | 01-JAN-00:10 | 16274.66 | 12-JUN-15:20 |
General:Fans:Electricity | 123.56 | 0.00 | 01-JAN-00:10 | 16274.66 | 12-JUN-15:20 |
ExteriorLights:Electricity | 111.89 | 0.00 | 01-JAN-06:20 | 8596.48 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 111.89 | 0.00 | 01-JAN-06:20 | 8596.48 | 01-JAN-06:10 |
Cooling:Electricity | 1023.97 | 0.00 | 01-JAN-00:10 | 102325.78 | 13-JUN-15:10 |
General:Cooling:Electricity | 1023.97 | 0.00 | 01-JAN-00:10 | 102325.78 | 13-JUN-15:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 26-FEB-15:50 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 26-FEB-15:50 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 26-FEB-15:50 |
WIRED_LTG_ELECTRICITY | 10.17 | 0.00 | 01-JAN-00:10 | 1019.01 | 18-DEC-17:00 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 112.52 | 2003.43 | 16-JAN-12:50 | 9464.11 | 03-JAN-12:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 112.52 | 2003.43 | 16-JAN-12:50 | 9464.11 | 03-JAN-12:10 |
WaterSystems:NaturalGas | 112.52 | 2003.43 | 16-JAN-12:50 | 9464.11 | 03-JAN-12:10 |
Water Heater:WaterSystems:NaturalGas | 112.52 | 2003.43 | 16-JAN-12:50 | 9464.11 | 03-JAN-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 6205.46 | 0.00 | 01-JAN-00:10 | 531783.30 | 13-JUN-15:20 |
EnergyTransfer:Building | 2135.49 | 0.00 | 01-JAN-00:10 | 185398.38 | 12-JUN-15:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 361.88 | 0.00 | 01-JAN-00:10 | 29282.39 | 02-JAN-09:00 |
Heating:EnergyTransfer | 0.57 | 0.00 | 01-JAN-00:10 | 2108.62 | 02-AUG-04:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 0.57 | 0.00 | 01-JAN-00:10 | 2108.62 | 02-AUG-04:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 2134.92 | 0.00 | 01-JAN-00:10 | 185398.38 | 12-JUN-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 361.88 | 0.00 | 01-JAN-00:10 | 29282.39 | 02-JAN-09:00 |
General:Cooling:EnergyTransfer | 2134.92 | 0.00 | 01-JAN-00:10 | 185398.38 | 12-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 361.88 | 0.00 | 01-JAN-00:10 | 29282.39 | 02-JAN-09:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 96.98 | 0.00 | 01-JAN-00:10 | 12792.42 | 05-MAY-13:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 0.22 | 0.00 | 01-JAN-00:10 | 1711.68 | 23-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 0.22 | 0.00 | 01-JAN-00:10 | 1711.68 | 23-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 96.76 | 0.00 | 01-JAN-00:10 | 12792.42 | 05-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 96.76 | 0.00 | 01-JAN-00:10 | 12792.42 | 05-MAY-13:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 56.01 | 0.00 | 01-JAN-00:10 | 5838.98 | 21-FEB-16:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.14 | 0.00 | 01-JAN-00:10 | 646.43 | 17-DEC-09:50 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.14 | 0.00 | 01-JAN-00:10 | 646.43 | 17-DEC-09:50 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 55.88 | 0.00 | 01-JAN-00:10 | 5838.98 | 21-FEB-16:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 55.88 | 0.00 | 01-JAN-00:10 | 5838.98 | 21-FEB-16:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 63.74 | 0.00 | 01-JAN-00:10 | 6132.93 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.22 | 0.00 | 01-JAN-00:10 | 933.27 | 17-AUG-04:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.22 | 0.00 | 01-JAN-00:10 | 933.27 | 17-AUG-04:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 63.52 | 0.00 | 01-JAN-00:10 | 6132.93 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 63.52 | 0.00 | 01-JAN-00:10 | 6132.93 | 12-JUN-16:00 |
EnergyTransfer:Zone:CORE_MID | 271.29 | 0.00 | 01-JAN-00:10 | 20965.24 | 02-JAN-08:50 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 271.29 | 0.00 | 01-JAN-00:10 | 20965.24 | 02-JAN-08:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 271.29 | 0.00 | 01-JAN-00:10 | 20965.24 | 02-JAN-08:50 |
EnergyTransfer:Zone:CORE_TOP | 289.26 | 0.00 | 01-JAN-00:10 | 23390.53 | 21-FEB-14:50 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 289.26 | 0.00 | 01-JAN-00:10 | 23390.53 | 21-FEB-14:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 289.26 | 0.00 | 01-JAN-00:10 | 23390.53 | 21-FEB-14:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 90.83 | 0.00 | 01-JAN-00:10 | 10236.82 | 12-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 90.83 | 0.00 | 01-JAN-00:10 | 10236.82 | 12-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 90.83 | 0.00 | 01-JAN-00:10 | 10236.82 | 12-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 71.24 | 0.00 | 01-JAN-00:10 | 8236.34 | 05-MAY-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 71.24 | 0.00 | 01-JAN-00:10 | 8236.34 | 05-MAY-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 71.24 | 0.00 | 01-JAN-00:10 | 8236.34 | 05-MAY-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 99.98 | 0.00 | 01-JAN-00:10 | 11439.32 | 26-DEC-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 99.98 | 0.00 | 01-JAN-00:10 | 11439.32 | 26-DEC-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 99.98 | 0.00 | 01-JAN-00:10 | 11439.32 | 26-DEC-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 71.71 | 0.00 | 01-JAN-00:10 | 9042.12 | 11-APR-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 71.71 | 0.00 | 01-JAN-00:10 | 9042.12 | 11-APR-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 71.71 | 0.00 | 01-JAN-00:10 | 9042.12 | 11-APR-15:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 90.66 | 0.00 | 01-JAN-00:10 | 9552.51 | 12-JUN-15:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 90.66 | 0.00 | 01-JAN-00:10 | 9552.51 | 12-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 90.66 | 0.00 | 01-JAN-00:10 | 9552.51 | 12-JUN-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.00 | 0.00 | 01-JAN-00:10 | 7508.95 | 20-MAR-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.00 | 0.00 | 01-JAN-00:10 | 7508.95 | 20-MAR-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.00 | 0.00 | 01-JAN-00:10 | 7508.95 | 20-MAR-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 118.14 | 0.00 | 01-JAN-00:10 | 12417.67 | 05-MAY-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 118.14 | 0.00 | 01-JAN-00:10 | 12417.67 | 05-MAY-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 118.14 | 0.00 | 01-JAN-00:10 | 12417.67 | 05-MAY-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 70.16 | 0.00 | 01-JAN-00:10 | 7894.28 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 70.16 | 0.00 | 01-JAN-00:10 | 7894.28 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 70.16 | 0.00 | 01-JAN-00:10 | 7894.28 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 85.32 | 0.00 | 01-JAN-00:10 | 9295.97 | 12-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 85.32 | 0.00 | 01-JAN-00:10 | 9295.97 | 12-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 85.32 | 0.00 | 01-JAN-00:10 | 9295.97 | 12-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 66.34 | 0.00 | 01-JAN-00:10 | 7828.68 | 05-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 66.34 | 0.00 | 01-JAN-00:10 | 7828.68 | 05-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 66.34 | 0.00 | 01-JAN-00:10 | 7828.68 | 05-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 94.03 | 0.00 | 01-JAN-00:10 | 10128.49 | 26-DEC-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 94.03 | 0.00 | 01-JAN-00:10 | 10128.49 | 26-DEC-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 94.03 | 0.00 | 01-JAN-00:10 | 10128.49 | 26-DEC-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 66.91 | 0.00 | 01-JAN-00:10 | 8356.07 | 18-APR-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 66.91 | 0.00 | 01-JAN-00:10 | 8356.07 | 18-APR-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 66.91 | 0.00 | 01-JAN-00:10 | 8356.07 | 18-APR-15:30 |
PlantLoopHeatingDemand:Facility | 31.77 | 0.00 | 01-JAN-00:10 | 3781.41 | 04-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 31.77 | 0.00 | 01-JAN-00:10 | 3781.41 | 04-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 31.77 | 0.00 | 01-JAN-00:10 | 3781.41 | 04-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 31.77 | 0.00 | 01-JAN-00:10 | 3781.41 | 04-JAN-12:10 |
EnergyTransfer:HVAC | 4038.21 | 0.00 | 01-JAN-00:10 | 345013.40 | 13-JUN-15:30 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 4038.21 | 0.00 | 01-JAN-00:10 | 345013.40 | 13-JUN-15:30 |
EnergyTransfer:Plant | 31.77 | 0.00 | 01-JAN-00:10 | 3781.41 | 04-JAN-12:10 |
WaterSystems:EnergyTransfer | 31.77 | 0.00 | 01-JAN-00:10 | 3781.41 | 04-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 31.77 | 0.00 | 01-JAN-00:10 | 3781.41 | 04-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -361.882 | 0.000 | 0.000 | 32.680 | 86.497 | 236.167 | 0.000 | 0.000 | 0.000 | 6.538 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 0.000 | -271.291 | 0.000 | 0.000 | 32.730 | 86.497 | 115.425 | 0.000 | 0.000 | 0.000 | 36.638 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -289.263 | 0.000 | 0.000 | 32.749 | 86.497 | 115.425 | 0.000 | 0.000 | 0.000 | 54.592 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -90.829 | 0.000 | 0.000 | 6.889 | 10.457 | 24.333 | 42.432 | 0.000 | 1.004 | 9.985 | 0.000 | -4.103 | 0.000 | -0.168 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -71.241 | 0.000 | 0.000 | 4.362 | 6.654 | 15.404 | 42.412 | 0.000 | 0.673 | 4.460 | 0.000 | -2.609 | 0.000 | -0.114 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -99.979 | 0.000 | 0.000 | 6.882 | 10.417 | 24.332 | 54.584 | 0.000 | 0.994 | 7.042 | 0.000 | -4.091 | 0.000 | -0.181 | -0.002 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -71.708 | 0.000 | 0.000 | 4.377 | 6.585 | 15.403 | 42.595 | 0.000 | 0.680 | 5.006 | 0.000 | -2.820 | 0.000 | -0.118 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -90.657 | 0.000 | 0.000 | 6.885 | 10.439 | 24.333 | 42.660 | 0.000 | 0.554 | 10.346 | 0.000 | -4.461 | 0.000 | -0.099 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -70.994 | 0.000 | 0.000 | 4.356 | 6.642 | 15.404 | 42.529 | 0.000 | 0.360 | 4.809 | 0.000 | -3.033 | 0.000 | -0.072 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -118.133 | 0.000 | 0.000 | 6.780 | 10.404 | 24.332 | 54.418 | 0.000 | 21.800 | 5.552 | 0.000 | -4.723 | 0.000 | -0.431 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -70.155 | 0.000 | 0.000 | 4.358 | 6.576 | 15.403 | 42.632 | 0.000 | 0.355 | 4.214 | 0.000 | -3.308 | 0.000 | -0.076 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -85.318 | 0.000 | 0.000 | 6.886 | 10.457 | 24.333 | 42.811 | 0.000 | 0.852 | 4.381 | 0.000 | -4.252 | 0.000 | -0.149 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -66.336 | 0.000 | 0.000 | 3.215 | 6.654 | 15.404 | 42.689 | 0.000 | 0.570 | 0.610 | 0.000 | -2.705 | 0.000 | -0.101 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -94.026 | 0.000 | 0.000 | 6.874 | 10.417 | 24.332 | 54.965 | 0.000 | 0.841 | 0.994 | 0.000 | -4.237 | 0.000 | -0.160 | -0.000 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -66.903 | 0.000 | 0.000 | 4.367 | 6.585 | 15.403 | 42.802 | 0.000 | 0.565 | 0.243 | 0.000 | -2.957 | 0.000 | -0.106 | -0.001 |
TOPFLOOR_PLENUM | 0.216 | -96.763 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.203 | 95.531 | 0.000 | 0.000 | 0.000 | -0.187 | 0.000 |
MIDFLOOR_PLENUM | 0.135 | -55.875 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.272 | 54.694 | 0.000 | 0.000 | 0.000 | -0.227 | 0.000 |
FIRSTFLOOR_PLENUM | 0.218 | -63.520 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.985 | 62.502 | 0.000 | 0.000 | 0.000 | -0.185 | -0.000 |
Total Facility | 0.569 | -216.157 | 0.000 | -1918.716 | 0.000 | 0.000 | 164.391 | 361.779 | 705.434 | 547.528 | 0.000 | 32.708 | 368.138 | 0.000 | -43.299 | 0.000 | -2.376 | -0.007 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | -48858.47 | 0.00 | 0.00 | 283.92 | 839.14 | 4989.51 | 0.00 | 0.00 | 0.00 | 42745.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | -37132.19 | 0.00 | 0.00 | 290.40 | 839.14 | 3025.92 | 0.00 | 0.00 | 0.00 | 32976.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | -41266.24 | 0.00 | 0.00 | 297.63 | 839.14 | 3025.92 | 0.00 | 0.00 | 0.00 | 37103.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 11-JUN-15:12 | 0.00 | 0.00 | 0.00 | -14169.35 | 0.00 | 0.00 | 23.14 | 42.19 | 478.42 | 4930.47 | 0.00 | 302.26 | 8392.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 09-APR-08:42 | 0.00 | 0.00 | 0.00 | -13228.78 | 0.00 | 0.00 | 14.91 | 26.71 | 302.86 | 6796.03 | 0.00 | 28.82 | 6059.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 25-DEC-15:32 | 0.00 | 0.00 | 0.00 | -14844.56 | 0.00 | 0.00 | 22.79 | 42.19 | 478.41 | 5940.33 | 0.00 | 43.28 | 8317.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 25-DEC-15:32 | 0.00 | 0.00 | 0.00 | -15299.78 | 0.00 | 0.00 | 14.07 | 26.71 | 302.86 | 6457.24 | 0.00 | 34.66 | 8464.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 18-JUN-18:02 | 0.00 | 0.00 | 0.00 | -11990.78 | 0.00 | 0.00 | 0.00 | 77.14 | 386.10 | 1383.32 | 0.00 | 72.29 | 10071.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 09-APR-08:42 | 0.00 | 0.00 | 0.00 | -11664.75 | 0.00 | 0.00 | 15.95 | 26.71 | 302.86 | 6890.58 | 0.00 | 17.73 | 4410.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 16-JAN-12:02 | 0.00 | 0.00 | 0.00 | -12737.27 | 0.00 | 0.00 | 24.04 | 42.19 | 478.41 | 9522.44 | 0.00 | 13.92 | 2656.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 20-FEB-15:51 | 0.00 | 0.00 | 0.00 | -12997.73 | 0.00 | 0.00 | 14.70 | 26.71 | 302.86 | 6087.62 | 0.00 | 92.72 | 6473.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUN-12:32 | 0.00 | 0.00 | 0.00 | -12151.75 | 0.00 | 0.00 | 26.85 | 42.19 | 478.42 | 4938.65 | 0.00 | 114.44 | 6551.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 09-APR-08:42 | 0.00 | 0.00 | 0.00 | -12661.86 | 0.00 | 0.00 | 15.18 | 26.71 | 302.86 | 6822.78 | 0.00 | 24.96 | 5469.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 16-JAN-12:02 | 0.00 | 0.00 | 0.00 | -13030.30 | 0.00 | 0.00 | 23.56 | 42.19 | 478.41 | 9475.84 | 0.00 | 20.11 | 2990.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 20-FEB-15:51 | 0.00 | 0.00 | 0.00 | -14109.46 | 0.00 | 0.00 | 13.97 | 26.71 | 302.86 | 6026.92 | 0.00 | 136.96 | 7602.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 05-MAY-13:10 | 0.00 | -12792.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.09 | 12649.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 21-FEB-16:10 | 0.00 | -5839.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.13 | 5723.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 30-MAY-12:10 | 0.00 | -6285.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 | 6264.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 31-JUL-04:02 | 0.00 | 8614.85 | 0.00 | -223707.20 | 0.00 | 0.00 | 0.00 | 4250.75 | 14333.92 | 0.00 | 0.00 | 0.00 | 201615.94 | 0.00 | -4920.94 | 0.00 | -187.32 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 06-FEB-06:01 | 6475.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6475.94 |
MIDFLOOR_PLENUM | 02-AUG-04:02 | 2795.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.33 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2897.36 |
FIRSTFLOOR_PLENUM | 02-AUG-04:02 | 4367.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.86 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4443.98 |
Total Facility | 06-FEB-06:01 | -207342.20 | 219180.56 | 0.00 | -219180.56 | 0.00 | 0.00 | 1495.32 | 4250.75 | 17291.51 | 0.00 | 0.00 | 0.00 | 190210.33 | 0.00 | -5483.44 | 0.00 | -422.27 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.7452 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.3076 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.1179 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6221 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.6440 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.4221 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.8726 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3985 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.5589 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3785 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.8220 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4467 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0258 | 3.0258 | 0.7927 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2746 | 2.2746 | 0.7643 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4752 | 2.4752 | 0.7970 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8114 | 0.8114 | 0.1680 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7237 | 0.7237 | 0.1447 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7913 | 0.7913 | 0.1686 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8424 | 0.8424 | 0.1685 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6908 | 0.6908 | 0.1672 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6525 | 0.6525 | 0.1305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6715 | 0.6715 | 0.1672 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7047 | 0.7047 | 0.1409 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7010 | 0.7010 | 0.1612 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6973 | 0.6973 | 0.1395 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6828 | 0.6828 | 0.1611 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7621 | 0.7621 | 0.1524 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.7452 | 5.3076 | 5.7452 | 1.3985 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.1179 | 4.6221 | 5.1179 | 1.3785 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.6440 | 5.4221 | 5.6440 | 1.4467 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5129 | 1.5129 | 0.7927 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1373 | 1.1373 | 0.7643 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2376 | 1.2376 | 0.7970 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4057 | 0.4057 | 0.1680 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3618 | 0.3618 | 0.1447 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3957 | 0.3957 | 0.1686 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4212 | 0.4212 | 0.1685 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3454 | 0.3454 | 0.1672 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3262 | 0.3262 | 0.1305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3357 | 0.3357 | 0.1672 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3523 | 0.3523 | 0.1409 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3505 | 0.3505 | 0.1612 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3487 | 0.3487 | 0.1395 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3414 | 0.3414 | 0.1611 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3811 | 0.3811 | 0.1524 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.8726 | 1.3985 | 1.3985 | 1.3985 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.5589 | 1.3785 | 1.3785 | 1.3785 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.8220 | 1.4467 | 1.4467 | 1.4467 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 4982.19 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 747.17 |
Number of hours not met | 747.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1023.97 | 102325.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 361.78 | 36263.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 111.89 | 8596.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 17.11 | 1236.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 123.56 | 16274.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 112.52 | 9464.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 2343.89 |
Natural Gas | 0.00 | 112.52 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 2456.40 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 72.61 |
Space Heating | 0.00 |
Space Cooling | 205.53 |
Fans (All) | 24.80 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 470.45 |
Subtotal | 470.45 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 22.58 |
Miscellaneous (All) | 22.58 |
Subtotal | 22.58 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.73 |
Space Heating | 0.00 |
Space Cooling | 41.69 |
Fans (All) | 5.03 |
Service Water Heating | 4.58 |
Receptacle Equipment | 28.72 |
Miscellaneous | 5.26 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 7571.50 | 1188.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8648.67 | 111.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8650.33 | 109.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7790.50 | 969.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7693.83 | 1066.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7609.33 | 1150.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7526.33 | 1233.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8158.00 | 602.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7769.00 | 991.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7737.33 | 1022.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7452.67 | 1307.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7928.50 | 831.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7780.17 | 979.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7729.83 | 1030.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7505.50 | 1254.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7998.50 | 761.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8684.67 | 75.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8726.00 | 34.00 | 0.00 | 0.00 | 0.00 |
Min | 7452.67 | 34.00 | 0.00 | 0.00 | 0.00 |
Max | 8726.00 | 1307.33 | 0.00 | 0.00 | 0.00 |
Average | 7942.26 | 817.74 | 0.00 | 0.00 | 0.00 |
Sum | 142960.67 | 14719.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128038.67 | 265.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128290.00 | 14.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128292.67 | 11.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24724.00 | 185.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128292.67 | 265.33 | 0.00 | 0.00 | 0.00 |
Average | 34116.91 | 26.43 | 0.00 | 0.00 | 0.00 |
Sum | 614104.33 | 475.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 6850.50 | 1909.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8302.33 | 457.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8408.50 | 351.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 4988.50 | 3771.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 5119.00 | 3641.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 4911.83 | 3848.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 5230.33 | 3529.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 5410.83 | 3349.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 5313.33 | 3446.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 3509.83 | 5250.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 5333.00 | 3427.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 4974.00 | 3786.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 5106.83 | 3653.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 4882.50 | 3877.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 5152.00 | 3608.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 4993.33 | 3766.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 5498.67 | 3261.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 5847.83 | 2912.17 | 0.00 | 0.00 | 0.00 |
Min | 3509.83 | 351.50 | 0.00 | 0.00 | 0.00 |
Max | 8408.50 | 5250.17 | 0.00 | 0.00 | 0.00 |
Average | 5546.29 | 3213.71 | 0.00 | 0.00 | 0.00 |
Sum | 99833.17 | 57846.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127637.67 | 666.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128246.33 | 57.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128255.67 | 48.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24760.17 | 148.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24759.00 | 150.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24859.83 | 49.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 16788.17 | 8120.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24776.33 | 132.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24772.50 | 136.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128255.67 | 8120.83 | 0.00 | 0.00 | 0.00 |
Average | 33614.98 | 528.35 | 0.00 | 0.00 | 0.00 |
Sum | 605069.67 | 9510.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303049E+11 | 46123.85 | 03-JAN-05:02 | 24.93 | 22.82 | 0.199452E+10 | 2606.54 | 02-JAN-14:30 | 24.93 | 22.82 |
February | 0.276664E+11 | 48860.39 | 06-FEB-06:03 | 23.95 | 22.59 | 0.180837E+10 | 2606.54 | 21-FEB-10:20 | 23.53 | 20.42 |
March | 0.320572E+11 | 46667.28 | 08-MAR-05:02 | 24.00 | 22.62 | 0.215869E+10 | 2606.54 | 03-MAR-10:20 | 24.00 | 22.62 |
April | 0.298626E+11 | 45282.76 | 08-APR-04:02 | 26.33 | 24.54 | 0.191615E+10 | 2606.55 | 20-APR-13:09 | 33.50 | 26.37 |
May | 0.318419E+11 | 45860.22 | 25-MAY-04:02 | 25.50 | 25.27 | 0.207558E+10 | 2606.55 | 01-MAY-13:20 | 25.50 | 25.27 |
June | 0.315826E+11 | 45604.21 | 01-JUN-04:02 | 24.17 | 24.06 | 0.206954E+10 | 2606.55 | 16-JUN-13:00 | 36.00 | 27.59 |
July | 0.298097E+11 | 45990.59 | 07-JUL-04:02 | 24.17 | 23.52 | 0.192339E+10 | 2606.54 | 03-JUL-13:30 | 24.17 | 23.52 |
August | 0.314938E+11 | 46251.11 | 22-AUG-04:03 | 24.08 | 23.67 | 0.215932E+10 | 2606.55 | 03-AUG-13:00 | 24.08 | 23.67 |
September | 0.291703E+11 | 48726.59 | 19-SEP-05:03 | 24.00 | 24.00 | 0.191651E+10 | 2606.54 | 14-SEP-13:30 | 24.00 | 24.00 |
October | 0.297712E+11 | 46340.69 | 24-OCT-04:02 | 24.08 | 24.04 | 0.199361E+10 | 2606.54 | 30-OCT-13:30 | 24.25 | 24.19 |
November | 0.293171E+11 | 46205.94 | 04-NOV-04:02 | 24.17 | 23.69 | 0.197457E+10 | 2606.54 | 08-NOV-14:30 | 30.00 | 25.66 |
December | 0.290046E+11 | 46098.65 | 09-DEC-05:02 | 24.00 | 24.00 | 0.192425E+10 | 2606.54 | 04-DEC-14:30 | 24.00 | 24.00 |
Annual Sum or Average | 0.361882E+12 | 0.239145E+11 | ||||||||
Minimum of Months | 0.276664E+11 | 45282.76 | 23.95 | 22.59 | 0.180837E+10 | 2606.54 | 23.53 | 20.42 | ||
Maximum of Months | 0.320572E+11 | 48860.39 | 26.33 | 25.27 | 0.215932E+10 | 2606.55 | 36.00 | 27.59 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.775404E+10 | 11358.06 | 04-JAN-14:10 | 33.83 | 23.50 | 0.00 | 0.00 | 01-JAN-00:10 | 33.83 | 23.50 |
February | 0.776692E+10 | 12591.05 | 21-FEB-14:30 | 34.50 | 21.90 | 0.00 | 0.00 | 01-FEB-00:10 | 34.50 | 21.90 |
March | 0.943445E+10 | 12753.23 | 21-MAR-14:00 | 36.00 | 23.97 | 0.00 | 0.00 | 01-MAR-00:10 | 36.00 | 23.97 |
April | 0.907845E+10 | 11902.38 | 11-APR-14:20 | 34.87 | 26.08 | 0.00 | 0.00 | 01-APR-00:10 | 34.87 | 26.08 |
May | 0.905649E+10 | 12792.42 | 05-MAY-13:10 | 36.33 | 27.23 | 0.00 | 0.00 | 01-MAY-00:10 | 36.33 | 27.23 |
June | 0.948936E+10 | 12527.46 | 16-JUN-14:00 | 36.00 | 27.59 | 0.00 | 0.00 | 01-JUN-00:10 | 36.00 | 27.59 |
July | 0.772462E+10 | 10955.24 | 14-JUL-14:20 | 32.17 | 24.82 | 0.00 | 0.00 | 01-JUL-00:10 | 32.17 | 24.82 |
August | 0.782563E+10 | 11570.74 | 14-AUG-13:40 | 33.27 | 27.64 | 0.00 | 0.00 | 01-AUG-00:10 | 33.27 | 27.64 |
September | 0.753106E+10 | 11593.22 | 06-SEP-14:00 | 34.00 | 26.51 | 0.00 | 0.00 | 01-SEP-00:10 | 34.00 | 26.51 |
October | 0.686261E+10 | 10985.85 | 04-OCT-13:40 | 32.77 | 26.28 | 0.00 | 0.00 | 01-OCT-00:10 | 32.77 | 26.28 |
November | 0.708312E+10 | 10892.80 | 22-NOV-13:02 | 31.50 | 24.57 | 0.00 | 0.00 | 01-NOV-00:10 | 31.50 | 24.57 |
December | 0.715766E+10 | 11167.00 | 26-DEC-13:02 | 32.00 | 23.12 | 0.00 | 0.00 | 01-DEC-00:10 | 32.00 | 23.12 |
Annual Sum or Average | 0.967644E+11 | 0.00 | ||||||||
Minimum of Months | 0.686261E+10 | 10892.80 | 31.50 | 21.90 | 0.00 | 0.00 | 31.50 | 21.90 | ||
Maximum of Months | 0.948936E+10 | 12792.42 | 36.33 | 27.64 | 0.00 | 0.00 | 36.33 | 27.64 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.460151E+10 | 5354.95 | 17-JAN-16:00 | 29.90 | 22.65 | 0.00 | 0.00 | 01-JAN-00:10 | 29.90 | 22.65 |
February | 0.441270E+10 | 5838.98 | 21-FEB-16:10 | 31.80 | 23.94 | 0.00 | 0.00 | 01-FEB-00:10 | 31.80 | 23.94 |
March | 0.515903E+10 | 5579.14 | 20-MAR-15:20 | 34.77 | 24.85 | 0.00 | 0.00 | 01-MAR-00:10 | 34.77 | 24.85 |
April | 0.490733E+10 | 5184.57 | 17-APR-15:40 | 32.90 | 26.39 | 0.00 | 0.00 | 01-APR-00:10 | 32.90 | 26.39 |
May | 0.520144E+10 | 5609.39 | 30-MAY-12:02 | 33.10 | 27.55 | 0.00 | 0.00 | 01-MAY-00:10 | 33.10 | 27.55 |
June | 0.541009E+10 | 5800.88 | 12-JUN-16:00 | 35.40 | 27.71 | 0.00 | 0.00 | 01-JUN-00:10 | 35.40 | 27.71 |
July | 0.449844E+10 | 4903.65 | 05-JUL-15:20 | 32.00 | 24.92 | 0.00 | 0.00 | 01-JUL-00:10 | 32.00 | 24.92 |
August | 0.461745E+10 | 5119.82 | 14-AUG-14:30 | 32.50 | 27.94 | 0.00 | 0.00 | 01-AUG-00:10 | 32.50 | 27.94 |
September | 0.434049E+10 | 5168.05 | 05-SEP-14:10 | 32.17 | 27.21 | 0.00 | 0.00 | 01-SEP-00:10 | 32.17 | 27.21 |
October | 0.425446E+10 | 5272.46 | 10-OCT-14:30 | 30.50 | 26.20 | 0.00 | 0.00 | 01-OCT-00:10 | 30.50 | 26.20 |
November | 0.430331E+10 | 5362.16 | 13-NOV-13:02 | 31.92 | 25.57 | 0.00 | 0.00 | 01-NOV-00:10 | 31.92 | 25.57 |
December | 0.417020E+10 | 5391.88 | 26-DEC-16:20 | 29.80 | 22.57 | 0.00 | 0.00 | 01-DEC-00:10 | 29.80 | 22.57 |
Annual Sum or Average | 0.558764E+11 | 0.00 | ||||||||
Minimum of Months | 0.417020E+10 | 4903.65 | 29.80 | 22.57 | 0.00 | 0.00 | 29.80 | 22.57 | ||
Maximum of Months | 0.541009E+10 | 5838.98 | 35.40 | 27.94 | 0.00 | 0.00 | 35.40 | 27.94 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.526882E+10 | 5707.11 | 02-JAN-13:10 | 30.25 | 24.20 | 0.00 | 0.00 | 01-JAN-00:10 | 30.25 | 24.20 |
February | 0.497354E+10 | 5971.39 | 21-FEB-16:10 | 31.80 | 23.94 | 0.00 | 0.00 | 01-FEB-00:10 | 31.80 | 23.94 |
March | 0.576851E+10 | 5783.75 | 20-MAR-16:00 | 34.30 | 24.91 | 0.00 | 0.00 | 01-MAR-00:10 | 34.30 | 24.91 |
April | 0.543822E+10 | 5540.36 | 17-APR-15:50 | 32.75 | 26.32 | 0.00 | 0.00 | 01-APR-00:10 | 32.75 | 26.32 |
May | 0.579874E+10 | 6286.64 | 30-MAY-12:10 | 33.10 | 27.55 | 0.00 | 0.00 | 01-MAY-00:10 | 33.10 | 27.55 |
June | 0.604948E+10 | 6152.28 | 12-JUN-12:08 | 34.05 | 27.94 | 0.00 | 0.00 | 01-JUN-00:10 | 34.05 | 27.94 |
July | 0.517371E+10 | 5518.07 | 17-JUL-12:15 | 31.10 | 25.70 | 0.00 | 0.00 | 01-JUL-00:10 | 31.10 | 25.70 |
August | 0.535315E+10 | 5664.00 | 14-AUG-12:08 | 33.13 | 27.67 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 27.67 |
September | 0.495272E+10 | 5801.67 | 05-SEP-12:10 | 33.02 | 26.93 | 0.00 | 0.00 | 01-SEP-00:10 | 33.02 | 26.93 |
October | 0.490099E+10 | 5724.82 | 10-OCT-15:10 | 29.17 | 26.02 | 0.00 | 0.00 | 01-OCT-00:10 | 29.17 | 26.02 |
November | 0.496982E+10 | 5867.77 | 13-NOV-13:10 | 31.92 | 25.57 | 0.00 | 0.00 | 01-NOV-00:10 | 31.92 | 25.57 |
December | 0.487325E+10 | 5711.07 | 26-DEC-07:03 | 23.17 | 21.69 | 0.00 | 0.00 | 01-DEC-00:10 | 23.17 | 21.69 |
Annual Sum or Average | 0.635209E+11 | 0.00 | ||||||||
Minimum of Months | 0.487325E+10 | 5518.07 | 23.17 | 21.69 | 0.00 | 0.00 | 23.17 | 21.69 | ||
Maximum of Months | 0.604948E+10 | 6286.64 | 34.30 | 27.94 | 0.00 | 0.00 | 34.30 | 27.94 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224380E+11 | 34846.70 | 10-JAN-05:02 | 23.95 | 22.91 | 0.198987E+10 | 2606.56 | 24-JAN-10:09 | 20.83 | 18.11 |
February | 0.207608E+11 | 37133.35 | 06-FEB-06:03 | 23.95 | 22.59 | 0.180464E+10 | 2606.53 | 24-FEB-10:09 | 28.50 | 22.00 |
March | 0.241726E+11 | 34833.27 | 10-MAR-05:02 | 24.00 | 22.49 | 0.215504E+10 | 2606.54 | 03-MAR-10:09 | 24.00 | 22.49 |
April | 0.227926E+11 | 34197.53 | 05-APR-04:02 | 26.08 | 23.61 | 0.191298E+10 | 2606.54 | 20-APR-13:09 | 33.50 | 26.37 |
May | 0.242187E+11 | 34778.16 | 11-MAY-04:02 | 24.17 | 23.96 | 0.207246E+10 | 2606.54 | 01-MAY-13:09 | 24.17 | 23.96 |
June | 0.239941E+11 | 34743.71 | 01-JUN-04:02 | 24.17 | 24.06 | 0.206677E+10 | 2606.54 | 16-JUN-13:00 | 36.00 | 27.59 |
July | 0.224153E+11 | 34721.22 | 11-JUL-04:02 | 24.02 | 23.98 | 0.191901E+10 | 2606.53 | 03-JUL-13:09 | 24.02 | 23.98 |
August | 0.233795E+11 | 34524.74 | 01-AUG-04:02 | 25.25 | 24.83 | 0.215455E+10 | 2606.54 | 03-AUG-13:00 | 31.00 | 27.23 |
September | 0.218816E+11 | 34650.80 | 13-SEP-04:02 | 24.42 | 24.11 | 0.191182E+10 | 2606.54 | 14-SEP-13:09 | 32.33 | 27.93 |
October | 0.221521E+11 | 35129.17 | 11-OCT-04:02 | 24.00 | 23.26 | 0.198870E+10 | 2606.54 | 30-OCT-13:09 | 24.42 | 24.31 |
November | 0.216906E+11 | 35109.45 | 07-NOV-05:02 | 24.00 | 23.42 | 0.196997E+10 | 2606.54 | 08-NOV-14:09 | 31.00 | 25.90 |
December | 0.213946E+11 | 33422.08 | 26-DEC-06:12 | 22.33 | 21.42 | 0.191814E+10 | 2606.55 | 21-DEC-10:09 | 22.33 | 21.42 |
Annual Sum or Average | 0.271291E+12 | 0.238639E+11 | ||||||||
Minimum of Months | 0.207608E+11 | 33422.08 | 22.33 | 21.42 | 0.180464E+10 | 2606.53 | 20.83 | 18.11 | ||
Maximum of Months | 0.242187E+11 | 37133.35 | 26.08 | 24.83 | 0.215504E+10 | 2606.56 | 36.00 | 27.93 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234194E+11 | 37933.17 | 09-JAN-05:02 | 23.92 | 23.24 | 0.198640E+10 | 2606.64 | 24-JAN-10:39 | 25.13 | 19.53 |
February | 0.219692E+11 | 41267.43 | 06-FEB-06:03 | 23.95 | 22.59 | 0.180237E+10 | 2606.55 | 24-FEB-10:09 | 28.50 | 22.00 |
March | 0.260351E+11 | 37730.84 | 06-MAR-05:02 | 24.00 | 21.84 | 0.215390E+10 | 2606.55 | 03-MAR-10:09 | 24.00 | 21.84 |
April | 0.249855E+11 | 37943.92 | 10-APR-04:02 | 25.17 | 23.75 | 0.191347E+10 | 2606.55 | 20-APR-13:09 | 33.50 | 26.37 |
May | 0.262603E+11 | 38091.34 | 09-MAY-04:02 | 24.17 | 24.17 | 0.207228E+10 | 2606.54 | 25-MAY-13:09 | 31.17 | 27.76 |
June | 0.260625E+11 | 37944.22 | 26-JUN-04:02 | 24.00 | 23.59 | 0.206699E+10 | 2606.55 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.240075E+11 | 37904.96 | 17-JUL-04:02 | 24.42 | 23.35 | 0.191792E+10 | 2606.53 | 03-JUL-13:09 | 24.42 | 23.35 |
August | 0.248418E+11 | 38177.13 | 21-AUG-04:02 | 24.17 | 23.75 | 0.215276E+10 | 2606.54 | 17-AUG-13:50 | 24.17 | 23.75 |
September | 0.233938E+11 | 37482.79 | 06-SEP-04:02 | 25.52 | 24.40 | 0.191116E+10 | 2606.54 | 14-SEP-13:09 | 32.33 | 27.93 |
October | 0.232833E+11 | 38233.70 | 02-OCT-04:02 | 24.00 | 23.36 | 0.198673E+10 | 2606.55 | 13-OCT-13:09 | 31.75 | 26.46 |
November | 0.227303E+11 | 38051.12 | 13-NOV-05:02 | 25.00 | 24.24 | 0.196743E+10 | 2606.55 | 16-NOV-14:09 | 29.85 | 25.47 |
December | 0.222748E+11 | 36526.89 | 26-DEC-06:12 | 22.33 | 21.42 | 0.191330E+10 | 2606.62 | 21-DEC-10:09 | 22.33 | 21.42 |
Annual Sum or Average | 0.289263E+12 | 0.238447E+11 | ||||||||
Minimum of Months | 0.219692E+11 | 36526.89 | 22.33 | 21.42 | 0.180237E+10 | 2606.53 | 22.33 | 19.53 | ||
Maximum of Months | 0.262603E+11 | 41267.43 | 25.52 | 24.40 | 0.215390E+10 | 2606.64 | 34.17 | 27.93 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.665258E+10 | 8515.75 | 02-JAN-06:12 | 23.37 | 23.04 | 0.419432E+09 | 549.49 | 24-JAN-10:39 | 25.13 | 19.53 |
February | 0.648002E+10 | 13471.73 | 26-FEB-15:12 | 34.70 | 24.67 | 0.380949E+09 | 549.48 | 15-FEB-14:00 | 34.70 | 24.67 |
March | 0.797234E+10 | 13693.36 | 19-MAR-15:22 | 34.85 | 24.81 | 0.455136E+09 | 549.47 | 03-MAR-10:09 | 34.85 | 24.81 |
April | 0.800113E+10 | 13843.44 | 16-APR-15:02 | 31.38 | 26.47 | 0.404713E+09 | 549.47 | 20-APR-13:00 | 34.50 | 26.74 |
May | 0.918754E+10 | 14105.16 | 29-MAY-10:22 | 33.00 | 28.05 | 0.438461E+09 | 549.47 | 09-MAY-13:00 | 33.00 | 28.05 |
June | 0.988464E+10 | 14171.82 | 11-JUN-15:12 | 34.83 | 28.15 | 0.437146E+09 | 549.48 | 28-JUN-13:00 | 34.00 | 27.29 |
July | 0.815217E+10 | 13863.87 | 04-JUL-15:32 | 31.67 | 25.13 | 0.406139E+09 | 549.47 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.792374E+10 | 13646.22 | 13-AUG-14:52 | 34.00 | 28.60 | 0.455198E+09 | 549.47 | 25-AUG-13:00 | 29.00 | 26.74 |
September | 0.711514E+10 | 13518.59 | 24-SEP-16:02 | 31.08 | 27.28 | 0.404253E+09 | 549.47 | 07-SEP-13:00 | 31.08 | 27.28 |
October | 0.671871E+10 | 13575.45 | 09-OCT-13:32 | 29.20 | 26.08 | 0.420172E+09 | 549.47 | 13-OCT-13:09 | 31.75 | 26.46 |
November | 0.650954E+10 | 9875.80 | 05-NOV-15:43 | 29.83 | 24.71 | 0.415906E+09 | 549.47 | 22-NOV-14:00 | 31.50 | 24.56 |
December | 0.623518E+10 | 13236.39 | 25-DEC-15:32 | 31.00 | 22.56 | 0.404181E+09 | 549.48 | 21-DEC-10:09 | 31.00 | 22.56 |
Annual Sum or Average | 0.908327E+11 | 0.504168E+10 | ||||||||
Minimum of Months | 0.623518E+10 | 8515.75 | 23.37 | 22.56 | 0.380949E+09 | 549.47 | 25.00 | 19.53 | ||
Maximum of Months | 0.988464E+10 | 14171.82 | 34.85 | 28.60 | 0.455198E+09 | 549.49 | 34.85 | 28.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.552386E+10 | 8202.99 | 29-JAN-11:13 | 29.33 | 23.29 | 0.265893E+09 | 347.88 | 24-JAN-10:39 | 29.33 | 23.29 |
February | 0.550589E+10 | 9723.90 | 26-FEB-11:53 | 32.00 | 24.81 | 0.241434E+09 | 347.86 | 15-FEB-14:00 | 32.00 | 24.81 |
March | 0.682234E+10 | 12620.80 | 19-MAR-10:02 | 32.50 | 23.52 | 0.288204E+09 | 347.86 | 03-MAR-10:20 | 32.50 | 23.52 |
April | 0.671289E+10 | 13227.35 | 09-APR-08:42 | 30.12 | 25.80 | 0.256261E+09 | 347.86 | 20-APR-13:00 | 34.50 | 26.74 |
May | 0.666079E+10 | 12921.02 | 14-MAY-10:52 | 33.00 | 25.66 | 0.277293E+09 | 347.86 | 30-MAY-09:00 | 33.40 | 27.88 |
June | 0.678137E+10 | 13133.59 | 18-JUN-08:42 | 30.83 | 27.19 | 0.276483E+09 | 347.86 | 30-JUN-09:39 | 30.33 | 27.86 |
July | 0.572026E+10 | 12247.85 | 30-JUL-10:32 | 30.17 | 24.41 | 0.256707E+09 | 347.86 | 11-JUL-13:00 | 30.17 | 24.41 |
August | 0.612030E+10 | 13023.87 | 27-AUG-10:42 | 32.72 | 27.53 | 0.287929E+09 | 347.86 | 25-AUG-13:00 | 32.72 | 27.53 |
September | 0.570099E+10 | 11934.53 | 03-SEP-12:13 | 31.67 | 27.41 | 0.255818E+09 | 347.86 | 14-SEP-09:09 | 30.13 | 26.40 |
October | 0.536847E+10 | 12267.13 | 08-OCT-08:32 | 29.00 | 25.89 | 0.265789E+09 | 347.86 | 11-OCT-09:30 | 29.05 | 25.81 |
November | 0.519961E+10 | 11673.48 | 05-NOV-09:43 | 28.67 | 24.05 | 0.263289E+09 | 347.86 | 17-NOV-10:20 | 28.93 | 25.06 |
December | 0.512764E+10 | 11829.92 | 31-DEC-10:13 | 30.87 | 24.92 | 0.256272E+09 | 347.87 | 21-DEC-10:09 | 30.87 | 24.92 |
Annual Sum or Average | 0.712444E+11 | 0.319137E+10 | ||||||||
Minimum of Months | 0.512764E+10 | 8202.99 | 28.67 | 23.29 | 0.241434E+09 | 347.86 | 28.93 | 23.29 | ||
Maximum of Months | 0.682234E+10 | 13227.35 | 33.00 | 27.53 | 0.288204E+09 | 347.88 | 34.50 | 27.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.975593E+10 | 14326.10 | 16-JAN-13:32 | 31.27 | 21.92 | 0.421709E+09 | 573.91 | 04-JAN-14:09 | 31.27 | 21.92 |
February | 0.878611E+10 | 14082.71 | 20-FEB-13:22 | 32.80 | 24.41 | 0.381993E+09 | 568.65 | 21-FEB-14:20 | 34.67 | 21.94 |
March | 0.913004E+10 | 13721.68 | 19-MAR-14:42 | 35.17 | 24.31 | 0.455420E+09 | 549.47 | 03-MAR-10:09 | 35.17 | 24.31 |
April | 0.788113E+10 | 13478.24 | 16-APR-15:02 | 31.38 | 26.47 | 0.404654E+09 | 549.47 | 20-APR-13:00 | 34.50 | 26.74 |
May | 0.830128E+10 | 13386.29 | 07-MAY-14:32 | 34.00 | 27.03 | 0.438139E+09 | 549.47 | 09-MAY-13:00 | 33.00 | 26.97 |
June | 0.820840E+10 | 13369.38 | 11-JUN-15:12 | 34.83 | 28.15 | 0.436779E+09 | 549.47 | 28-JUN-13:00 | 34.00 | 27.29 |
July | 0.722019E+10 | 11796.32 | 04-JUL-15:32 | 31.67 | 25.13 | 0.405724E+09 | 549.47 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.749303E+10 | 12603.38 | 27-AUG-15:22 | 32.50 | 25.79 | 0.455008E+09 | 549.47 | 25-AUG-13:00 | 32.50 | 25.79 |
September | 0.743780E+10 | 13397.81 | 03-SEP-12:13 | 31.67 | 27.41 | 0.404325E+09 | 549.47 | 07-SEP-13:00 | 32.00 | 27.49 |
October | 0.787148E+10 | 14070.46 | 29-OCT-10:53 | 31.50 | 26.00 | 0.420613E+09 | 549.48 | 13-OCT-13:09 | 31.50 | 26.00 |
November | 0.862483E+10 | 14166.39 | 11-NOV-11:32 | 30.50 | 25.40 | 0.416745E+09 | 549.48 | 22-NOV-14:00 | 31.50 | 24.56 |
December | 0.927253E+10 | 14845.25 | 25-DEC-15:32 | 31.00 | 22.56 | 0.407109E+09 | 576.36 | 07-DEC-14:09 | 31.00 | 22.56 |
Annual Sum or Average | 0.999828E+11 | 0.504822E+10 | ||||||||
Minimum of Months | 0.722019E+10 | 11796.32 | 30.50 | 21.92 | 0.381993E+09 | 549.47 | 25.00 | 21.92 | ||
Maximum of Months | 0.975593E+10 | 14845.25 | 35.17 | 28.15 | 0.455420E+09 | 576.36 | 35.17 | 27.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.566912E+10 | 13830.05 | 16-JAN-16:12 | 30.53 | 22.11 | 0.263857E+09 | 347.84 | 09-JAN-14:00 | 30.53 | 22.11 |
February | 0.559537E+10 | 14664.39 | 26-FEB-15:52 | 34.10 | 25.18 | 0.239895E+09 | 347.84 | 15-FEB-14:00 | 34.10 | 25.18 |
March | 0.691864E+10 | 15081.54 | 19-MAR-15:22 | 34.85 | 24.81 | 0.287071E+09 | 347.84 | 03-MAR-10:09 | 34.85 | 24.81 |
April | 0.670090E+10 | 14935.90 | 02-APR-15:32 | 34.00 | 27.22 | 0.255491E+09 | 347.84 | 20-APR-13:00 | 34.50 | 26.74 |
May | 0.663290E+10 | 14627.83 | 14-MAY-15:32 | 34.87 | 27.32 | 0.276414E+09 | 347.83 | 09-MAY-13:00 | 34.87 | 27.32 |
June | 0.669868E+10 | 14716.95 | 11-JUN-15:52 | 34.50 | 28.11 | 0.275780E+09 | 347.84 | 30-JUN-09:00 | 31.00 | 28.03 |
July | 0.574380E+10 | 14668.12 | 04-JUL-16:12 | 30.83 | 25.29 | 0.255393E+09 | 347.84 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.605163E+10 | 14618.25 | 27-AUG-16:02 | 32.83 | 25.70 | 0.286737E+09 | 347.83 | 25-AUG-13:00 | 32.83 | 25.70 |
September | 0.568155E+10 | 14882.02 | 10-SEP-17:22 | 28.00 | 25.79 | 0.254645E+09 | 347.84 | 07-SEP-13:00 | 28.00 | 25.79 |
October | 0.542645E+10 | 14712.19 | 15-OCT-16:02 | 29.25 | 25.50 | 0.264306E+09 | 347.84 | 13-OCT-13:00 | 29.25 | 25.50 |
November | 0.530323E+10 | 12514.91 | 19-NOV-15:12 | 31.03 | 25.23 | 0.261922E+09 | 347.84 | 22-NOV-14:00 | 31.50 | 24.56 |
December | 0.528926E+10 | 15300.55 | 25-DEC-15:32 | 31.00 | 22.56 | 0.253889E+09 | 347.84 | 08-DEC-14:00 | 31.00 | 22.56 |
Annual Sum or Average | 0.717115E+11 | 0.317540E+10 | ||||||||
Minimum of Months | 0.528926E+10 | 12514.91 | 28.00 | 22.11 | 0.239895E+09 | 347.83 | 25.00 | 22.11 | ||
Maximum of Months | 0.691864E+10 | 15300.55 | 34.87 | 28.11 | 0.287071E+09 | 347.84 | 34.87 | 28.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.667154E+10 | 7623.46 | 02-JAN-07:03 | 23.85 | 23.26 | 0.420117E+09 | 549.48 | 09-JAN-14:00 | 31.00 | 24.49 |
February | 0.637871E+10 | 11589.88 | 20-FEB-15:51 | 33.10 | 24.35 | 0.381305E+09 | 549.48 | 21-FEB-10:09 | 21.92 | 19.78 |
March | 0.765102E+10 | 9359.09 | 20-MAR-04:02 | 27.08 | 23.58 | 0.455195E+09 | 549.47 | 03-MAR-10:09 | 27.08 | 23.58 |
April | 0.766184E+10 | 9582.68 | 18-APR-04:02 | 26.92 | 25.08 | 0.404547E+09 | 549.48 | 20-APR-13:09 | 33.50 | 26.37 |
May | 0.906799E+10 | 11965.81 | 29-MAY-10:22 | 33.00 | 28.05 | 0.438575E+09 | 549.47 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.983112E+10 | 11991.04 | 18-JUN-18:02 | 31.07 | 27.26 | 0.437343E+09 | 549.48 | 30-JUN-09:39 | 30.33 | 27.86 |
July | 0.835818E+10 | 11827.17 | 04-JUL-15:32 | 31.67 | 25.13 | 0.406445E+09 | 549.47 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.811566E+10 | 11692.15 | 13-AUG-14:41 | 34.00 | 28.60 | 0.455567E+09 | 549.47 | 25-AUG-13:00 | 29.00 | 26.74 |
September | 0.722069E+10 | 9998.82 | 05-SEP-04:02 | 26.75 | 26.18 | 0.404470E+09 | 549.47 | 07-SEP-13:00 | 32.00 | 27.49 |
October | 0.678699E+10 | 9598.97 | 02-OCT-04:02 | 24.00 | 23.36 | 0.420501E+09 | 549.47 | 13-OCT-13:09 | 31.75 | 26.46 |
November | 0.660210E+10 | 9130.98 | 24-NOV-05:02 | 24.42 | 21.44 | 0.416263E+09 | 549.47 | 09-NOV-14:00 | 24.42 | 21.44 |
December | 0.631342E+10 | 6708.48 | 11-DEC-13:05 | 31.33 | 26.00 | 0.405298E+09 | 549.48 | 04-DEC-14:00 | 31.33 | 26.00 |
Annual Sum or Average | 0.906593E+11 | 0.504563E+10 | ||||||||
Minimum of Months | 0.631342E+10 | 6708.48 | 23.85 | 21.44 | 0.381305E+09 | 549.47 | 21.92 | 19.78 | ||
Maximum of Months | 0.983112E+10 | 11991.04 | 34.00 | 28.60 | 0.455567E+09 | 549.48 | 33.50 | 27.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.555863E+10 | 10678.12 | 16-JAN-11:22 | 29.90 | 21.44 | 0.266392E+09 | 347.86 | 31-JAN-10:09 | 24.17 | 21.37 |
February | 0.548821E+10 | 11507.97 | 20-FEB-09:12 | 28.47 | 23.42 | 0.241814E+09 | 347.86 | 21-FEB-10:20 | 23.53 | 20.42 |
March | 0.665629E+10 | 11564.02 | 05-MAR-09:52 | 29.50 | 22.86 | 0.288541E+09 | 347.86 | 03-MAR-10:09 | 29.50 | 22.86 |
April | 0.649432E+10 | 11664.01 | 09-APR-08:42 | 30.12 | 25.80 | 0.256435E+09 | 347.86 | 24-APR-09:30 | 30.65 | 25.59 |
May | 0.654872E+10 | 11555.03 | 29-MAY-10:22 | 33.00 | 28.05 | 0.277667E+09 | 347.86 | 30-MAY-09:30 | 32.20 | 27.59 |
June | 0.670309E+10 | 11634.05 | 18-JUN-08:42 | 30.83 | 27.19 | 0.276758E+09 | 347.86 | 30-JUN-09:39 | 30.33 | 27.86 |
July | 0.578052E+10 | 10201.57 | 30-JUL-10:23 | 30.00 | 24.41 | 0.257194E+09 | 347.86 | 17-JUL-13:00 | 30.00 | 24.41 |
August | 0.621360E+10 | 11598.62 | 27-AUG-10:42 | 32.72 | 27.53 | 0.288490E+09 | 347.86 | 28-AUG-09:30 | 30.95 | 26.94 |
September | 0.575554E+10 | 11609.46 | 10-SEP-09:52 | 31.60 | 26.10 | 0.256312E+09 | 347.86 | 14-SEP-09:30 | 30.40 | 26.60 |
October | 0.536978E+10 | 11221.29 | 08-OCT-10:13 | 30.67 | 26.44 | 0.266396E+09 | 347.86 | 11-OCT-09:30 | 29.05 | 25.81 |
November | 0.524397E+10 | 9412.01 | 05-NOV-09:43 | 28.67 | 24.05 | 0.263846E+09 | 347.86 | 06-NOV-10:30 | 29.05 | 24.31 |
December | 0.518312E+10 | 10096.03 | 31-DEC-11:22 | 31.00 | 24.77 | 0.257042E+09 | 347.86 | 29-DEC-10:30 | 31.00 | 24.77 |
Annual Sum or Average | 0.709958E+11 | 0.319689E+10 | ||||||||
Minimum of Months | 0.518312E+10 | 9412.01 | 28.47 | 21.44 | 0.241814E+09 | 347.86 | 23.53 | 20.42 | ||
Maximum of Months | 0.670309E+10 | 11664.01 | 33.00 | 28.05 | 0.288541E+09 | 347.86 | 32.20 | 27.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109238E+11 | 12737.89 | 16-JAN-12:02 | 30.38 | 21.74 | 0.438113E+09 | 728.49 | 04-JAN-13:09 | 30.38 | 21.74 |
February | 0.986815E+10 | 12501.33 | 20-FEB-13:52 | 33.00 | 24.27 | 0.398393E+09 | 720.89 | 21-FEB-13:09 | 34.25 | 22.07 |
March | 0.107833E+11 | 11953.26 | 21-MAR-12:00 | 35.00 | 23.21 | 0.465738E+09 | 706.73 | 21-MAR-12:09 | 35.23 | 23.19 |
April | 0.948467E+10 | 11412.27 | 18-APR-12:00 | 34.00 | 26.52 | 0.410122E+09 | 665.52 | 18-APR-12:09 | 34.03 | 26.51 |
May | 0.101702E+11 | 12417.67 | 05-MAY-12:00 | 37.00 | 25.95 | 0.444623E+09 | 736.05 | 05-MAY-12:09 | 36.90 | 26.19 |
June | 0.101774E+11 | 11804.62 | 16-JUN-12:00 | 35.00 | 28.16 | 0.443372E+09 | 689.72 | 16-JUN-12:09 | 35.17 | 28.24 |
July | 0.867609E+10 | 10897.54 | 26-JUL-17:00 | 33.00 | 26.23 | 0.408936E+09 | 617.62 | 27-JUL-12:09 | 31.48 | 25.75 |
August | 0.939863E+10 | 11430.87 | 15-AUG-12:00 | 33.70 | 27.96 | 0.459533E+09 | 664.40 | 15-AUG-12:09 | 33.32 | 27.86 |
September | 0.900302E+10 | 11276.29 | 05-SEP-12:00 | 33.00 | 26.98 | 0.408538E+09 | 655.65 | 05-SEP-12:09 | 33.02 | 26.93 |
October | 0.927259E+10 | 11881.94 | 29-OCT-10:53 | 31.50 | 26.00 | 0.425369E+09 | 657.04 | 04-OCT-12:09 | 31.50 | 26.00 |
November | 0.100270E+11 | 12342.76 | 23-NOV-12:42 | 31.00 | 25.03 | 0.426571E+09 | 664.55 | 22-NOV-13:09 | 31.00 | 25.03 |
December | 0.103536E+11 | 12677.90 | 31-DEC-13:22 | 32.00 | 24.52 | 0.421297E+09 | 700.50 | 26-DEC-13:09 | 32.00 | 24.52 |
Annual Sum or Average | 0.118138E+12 | 0.515060E+10 | ||||||||
Minimum of Months | 0.867609E+10 | 10897.54 | 30.38 | 21.74 | 0.398393E+09 | 617.62 | 30.38 | 21.74 | ||
Maximum of Months | 0.109238E+11 | 12737.89 | 37.00 | 28.16 | 0.465738E+09 | 736.05 | 36.90 | 28.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.555487E+10 | 12885.97 | 16-JAN-17:22 | 28.30 | 21.90 | 0.266133E+09 | 347.84 | 09-JAN-14:00 | 28.30 | 21.90 |
February | 0.543708E+10 | 12998.37 | 20-FEB-15:51 | 33.10 | 24.35 | 0.241538E+09 | 347.84 | 21-FEB-10:09 | 21.92 | 19.78 |
March | 0.664449E+10 | 12642.83 | 05-MAR-15:12 | 31.40 | 24.66 | 0.288398E+09 | 347.84 | 03-MAR-10:09 | 31.40 | 24.66 |
April | 0.639380E+10 | 12446.86 | 02-APR-16:12 | 33.00 | 27.09 | 0.256267E+09 | 347.84 | 20-APR-13:00 | 34.50 | 26.74 |
May | 0.643241E+10 | 12230.10 | 07-MAY-17:52 | 31.00 | 27.23 | 0.277458E+09 | 347.84 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.657167E+10 | 12296.22 | 18-JUN-18:02 | 31.07 | 27.26 | 0.276630E+09 | 347.84 | 30-JUN-09:39 | 30.33 | 27.86 |
July | 0.570509E+10 | 12344.75 | 04-JUL-18:12 | 27.07 | 24.66 | 0.257058E+09 | 347.84 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.606428E+10 | 12271.87 | 27-AUG-16:02 | 32.83 | 25.70 | 0.288360E+09 | 347.84 | 25-AUG-13:00 | 32.83 | 25.70 |
September | 0.563544E+10 | 12529.52 | 10-SEP-17:12 | 28.00 | 25.79 | 0.256090E+09 | 347.84 | 07-SEP-13:00 | 28.00 | 25.79 |
October | 0.531740E+10 | 11312.77 | 15-OCT-16:53 | 28.50 | 25.82 | 0.266196E+09 | 347.84 | 11-OCT-09:30 | 28.50 | 25.82 |
November | 0.521921E+10 | 12084.53 | 11-NOV-14:42 | 31.57 | 26.67 | 0.263561E+09 | 347.84 | 21-NOV-14:00 | 31.50 | 24.93 |
December | 0.518112E+10 | 12386.49 | 24-DEC-16:42 | 29.33 | 23.37 | 0.256659E+09 | 347.84 | 08-DEC-14:00 | 29.33 | 23.37 |
Annual Sum or Average | 0.701569E+11 | 0.319435E+10 | ||||||||
Minimum of Months | 0.518112E+10 | 11312.77 | 27.07 | 21.90 | 0.241538E+09 | 347.84 | 21.92 | 19.78 | ||
Maximum of Months | 0.664449E+10 | 12998.37 | 33.10 | 27.26 | 0.288398E+09 | 347.84 | 34.50 | 27.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.636243E+10 | 7869.80 | 09-JAN-05:02 | 23.92 | 23.24 | 0.419986E+09 | 549.48 | 24-JAN-10:09 | 20.83 | 18.11 |
February | 0.612016E+10 | 11845.52 | 20-FEB-15:51 | 33.10 | 24.35 | 0.381297E+09 | 549.48 | 15-FEB-14:00 | 33.10 | 24.35 |
March | 0.742268E+10 | 10437.97 | 19-MAR-15:22 | 34.85 | 24.81 | 0.455267E+09 | 549.47 | 03-MAR-10:09 | 34.85 | 24.81 |
April | 0.735071E+10 | 11580.95 | 16-APR-15:02 | 31.38 | 26.47 | 0.404633E+09 | 549.47 | 20-APR-13:09 | 33.50 | 26.37 |
May | 0.853559E+10 | 12096.20 | 29-MAY-10:22 | 33.00 | 28.05 | 0.438501E+09 | 549.47 | 09-MAY-13:00 | 33.00 | 28.05 |
June | 0.918560E+10 | 12150.78 | 04-JUN-12:32 | 32.27 | 28.41 | 0.437167E+09 | 549.48 | 30-JUN-09:39 | 30.33 | 27.86 |
July | 0.763488E+10 | 11975.67 | 04-JUL-16:12 | 30.83 | 25.29 | 0.406233E+09 | 549.47 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.747179E+10 | 10424.94 | 13-AUG-14:52 | 34.00 | 28.60 | 0.455380E+09 | 549.47 | 25-AUG-13:00 | 29.00 | 26.74 |
September | 0.666581E+10 | 9692.60 | 05-SEP-04:02 | 26.75 | 26.18 | 0.404336E+09 | 549.47 | 07-SEP-13:00 | 32.00 | 27.49 |
October | 0.638447E+10 | 9710.25 | 16-OCT-04:02 | 26.00 | 25.22 | 0.420441E+09 | 549.47 | 13-OCT-13:09 | 26.00 | 25.22 |
November | 0.621610E+10 | 9641.92 | 20-NOV-05:02 | 24.00 | 22.62 | 0.416199E+09 | 549.47 | 24-NOV-14:00 | 29.00 | 22.42 |
December | 0.597163E+10 | 8664.05 | 30-DEC-06:02 | 24.07 | 24.03 | 0.404985E+09 | 549.47 | 04-DEC-14:00 | 24.07 | 24.03 |
Annual Sum or Average | 0.853219E+11 | 0.504443E+10 | ||||||||
Minimum of Months | 0.597163E+10 | 7869.80 | 23.92 | 22.62 | 0.381297E+09 | 549.47 | 20.83 | 18.11 | ||
Maximum of Months | 0.918560E+10 | 12150.78 | 34.85 | 28.60 | 0.455380E+09 | 549.48 | 34.85 | 28.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.523054E+10 | 11223.27 | 16-JAN-11:22 | 29.90 | 21.44 | 0.196969E+09 | 338.72 | 23-JAN-08:20 | 22.27 | 18.63 |
February | 0.517257E+10 | 12396.84 | 20-FEB-09:12 | 28.47 | 23.42 | 0.178812E+09 | 338.74 | 24-FEB-08:20 | 23.67 | 18.66 |
March | 0.632906E+10 | 12482.06 | 05-MAR-09:52 | 29.50 | 22.86 | 0.212891E+09 | 338.72 | 29-MAR-12:20 | 34.53 | 23.02 |
April | 0.615340E+10 | 12660.68 | 09-APR-08:42 | 30.12 | 25.80 | 0.189692E+09 | 338.72 | 27-APR-12:20 | 33.00 | 25.59 |
May | 0.613645E+10 | 12416.11 | 14-MAY-08:42 | 29.67 | 25.57 | 0.205129E+09 | 338.72 | 01-MAY-12:20 | 29.67 | 25.57 |
June | 0.624630E+10 | 12525.19 | 18-JUN-08:42 | 30.83 | 27.19 | 0.204268E+09 | 338.72 | 23-JUN-12:20 | 33.33 | 26.58 |
July | 0.529555E+10 | 11077.88 | 30-JUL-09:53 | 29.50 | 24.38 | 0.190224E+09 | 338.71 | 14-JUL-12:20 | 29.50 | 24.38 |
August | 0.570375E+10 | 12406.38 | 27-AUG-10:42 | 32.72 | 27.53 | 0.212680E+09 | 338.72 | 15-AUG-12:20 | 32.72 | 27.53 |
September | 0.528724E+10 | 12459.86 | 10-SEP-09:52 | 31.60 | 26.10 | 0.189338E+09 | 338.72 | 07-SEP-12:20 | 31.60 | 26.10 |
October | 0.503385E+10 | 12328.94 | 08-OCT-09:02 | 29.67 | 26.21 | 0.196895E+09 | 338.72 | 13-OCT-12:20 | 31.97 | 26.42 |
November | 0.489807E+10 | 10853.79 | 05-NOV-09:43 | 28.67 | 24.05 | 0.195043E+09 | 338.72 | 08-NOV-13:20 | 31.57 | 26.41 |
December | 0.485230E+10 | 11176.79 | 31-DEC-10:02 | 30.83 | 24.89 | 0.189980E+09 | 338.72 | 21-DEC-08:30 | 30.83 | 24.89 |
Annual Sum or Average | 0.663391E+11 | 0.236192E+10 | ||||||||
Minimum of Months | 0.485230E+10 | 10853.79 | 28.47 | 21.44 | 0.178812E+09 | 338.71 | 22.27 | 18.63 | ||
Maximum of Months | 0.632906E+10 | 12660.68 | 32.72 | 27.53 | 0.212891E+09 | 338.74 | 34.53 | 27.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.930400E+10 | 13031.24 | 16-JAN-12:02 | 30.38 | 21.74 | 0.424194E+09 | 588.76 | 04-JAN-14:09 | 30.38 | 21.74 |
February | 0.832470E+10 | 12648.83 | 20-FEB-13:52 | 33.00 | 24.27 | 0.383277E+09 | 582.13 | 21-FEB-14:09 | 34.83 | 21.98 |
March | 0.852039E+10 | 11828.48 | 05-MAR-15:12 | 31.40 | 24.66 | 0.455567E+09 | 549.47 | 06-MAR-14:00 | 31.00 | 24.50 |
April | 0.723908E+10 | 11241.09 | 16-APR-15:02 | 31.38 | 26.47 | 0.404581E+09 | 549.47 | 20-APR-13:09 | 33.50 | 26.37 |
May | 0.769609E+10 | 11345.33 | 07-MAY-15:12 | 33.73 | 27.56 | 0.438181E+09 | 549.47 | 09-MAY-13:00 | 33.00 | 26.97 |
June | 0.760586E+10 | 11182.10 | 11-JUN-15:12 | 34.83 | 28.15 | 0.436757E+09 | 549.47 | 30-JUN-09:00 | 31.00 | 28.03 |
July | 0.675167E+10 | 9876.75 | 17-JUL-04:02 | 24.42 | 23.35 | 0.405871E+09 | 549.47 | 11-JUL-13:00 | 24.42 | 23.35 |
August | 0.706551E+10 | 9652.32 | 28-AUG-04:02 | 25.33 | 24.05 | 0.455222E+09 | 549.47 | 25-AUG-13:00 | 25.33 | 24.05 |
September | 0.696552E+10 | 11408.85 | 10-SEP-14:31 | 32.67 | 26.74 | 0.404428E+09 | 549.47 | 07-SEP-13:00 | 32.67 | 26.74 |
October | 0.747736E+10 | 12119.30 | 29-OCT-10:53 | 31.50 | 26.00 | 0.420859E+09 | 549.47 | 13-OCT-13:09 | 31.50 | 26.00 |
November | 0.823629E+10 | 12579.70 | 23-NOV-12:42 | 31.00 | 25.03 | 0.417261E+09 | 557.56 | 20-NOV-14:09 | 31.00 | 25.03 |
December | 0.884324E+10 | 12902.24 | 03-DEC-13:42 | 31.08 | 22.40 | 0.409838E+09 | 592.40 | 07-DEC-14:09 | 33.00 | 23.12 |
Annual Sum or Average | 0.940297E+11 | 0.505603E+10 | ||||||||
Minimum of Months | 0.675167E+10 | 9652.32 | 24.42 | 21.74 | 0.383277E+09 | 549.47 | 24.42 | 21.74 | ||
Maximum of Months | 0.930400E+10 | 13031.24 | 34.83 | 28.15 | 0.455567E+09 | 592.40 | 34.83 | 28.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.535680E+10 | 13909.67 | 16-JAN-17:22 | 28.30 | 21.90 | 0.265168E+09 | 347.84 | 09-JAN-14:00 | 28.30 | 21.90 |
February | 0.524975E+10 | 14109.93 | 20-FEB-15:51 | 33.10 | 24.35 | 0.240837E+09 | 347.84 | 15-FEB-14:00 | 33.10 | 24.35 |
March | 0.643681E+10 | 13650.88 | 05-MAR-15:12 | 31.40 | 24.66 | 0.287798E+09 | 347.84 | 03-MAR-10:09 | 31.40 | 24.66 |
April | 0.615836E+10 | 13495.19 | 23-APR-15:42 | 33.25 | 24.64 | 0.255888E+09 | 347.83 | 20-APR-13:00 | 33.25 | 24.64 |
May | 0.613461E+10 | 13301.87 | 14-MAY-15:21 | 34.90 | 27.18 | 0.276914E+09 | 347.83 | 30-MAY-09:09 | 31.40 | 27.36 |
June | 0.620906E+10 | 13179.22 | 11-JUN-16:32 | 33.50 | 27.84 | 0.276181E+09 | 347.84 | 30-JUN-09:00 | 31.00 | 28.03 |
July | 0.532343E+10 | 13294.60 | 04-JUL-16:12 | 30.83 | 25.29 | 0.256231E+09 | 347.84 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.567039E+10 | 13230.46 | 27-AUG-16:02 | 32.83 | 25.70 | 0.287548E+09 | 347.83 | 25-AUG-13:00 | 32.83 | 25.70 |
September | 0.528759E+10 | 13463.54 | 10-SEP-17:12 | 28.00 | 25.79 | 0.255309E+09 | 347.84 | 07-SEP-13:00 | 28.00 | 25.79 |
October | 0.509171E+10 | 13272.90 | 15-OCT-16:02 | 29.25 | 25.50 | 0.265306E+09 | 347.83 | 13-OCT-13:00 | 29.25 | 25.50 |
November | 0.499987E+10 | 13102.06 | 11-NOV-14:42 | 31.57 | 26.67 | 0.262795E+09 | 347.84 | 21-NOV-14:00 | 31.50 | 24.93 |
December | 0.498779E+10 | 13399.22 | 24-DEC-16:32 | 29.67 | 23.46 | 0.255498E+09 | 347.84 | 08-DEC-14:00 | 29.67 | 23.46 |
Annual Sum or Average | 0.669062E+11 | 0.318547E+10 | ||||||||
Minimum of Months | 0.498779E+10 | 13102.06 | 28.00 | 21.90 | 0.240837E+09 | 347.83 | 25.00 | 21.90 | ||
Maximum of Months | 0.643681E+10 | 14109.93 | 34.90 | 27.84 | 0.287798E+09 | 347.84 | 33.25 | 28.03 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20870140.49 | 4390.39 | 11-JAN-06:02 | 24.70 |
February | 19606070.30 | 6476.70 | 06-FEB-06:01 | 23.95 |
March | 19778946.75 | 4829.47 | 20-MAR-04:02 | 27.08 |
April | 18577028.98 | 4400.33 | 10-APR-04:02 | 25.17 |
May | 15954035.04 | 4185.09 | 15-MAY-04:02 | 26.33 |
June | 15601106.55 | 4593.07 | 12-JUN-04:02 | 26.33 |
July | 17265176.70 | 4820.82 | 17-JUL-04:02 | 24.42 |
August | 17181751.81 | 4723.11 | 28-AUG-04:02 | 25.33 |
September | 16983046.75 | 4715.53 | 25-SEP-04:02 | 26.00 |
October | 16462614.32 | 4783.94 | 02-OCT-04:02 | 24.00 |
November | 16312113.68 | 5067.52 | 07-NOV-06:02 | 24.25 |
December | 21314301.77 | 3670.60 | 09-DEC-06:02 | 24.15 |
Annual Sum or Average | 0.215906E+09 | |||
Minimum of Months | 15601106.55 | 3670.60 | 23.95 | |
Maximum of Months | 21314301.77 | 6476.70 | 27.08 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11477797.27 | 1873.34 | 05-JAN-05:02 | 24.23 |
February | 9954095.73 | 2031.18 | 06-FEB-06:01 | 23.95 |
March | 13274584.63 | 2330.48 | 28-MAR-04:02 | 27.25 |
April | 12328835.26 | 2422.22 | 12-APR-04:02 | 27.08 |
May | 13287735.27 | 2714.47 | 10-MAY-04:02 | 28.33 |
June | 11630711.29 | 2482.66 | 16-JUN-04:02 | 27.33 |
July | 9332294.41 | 2304.34 | 24-JUL-04:02 | 25.67 |
August | 10196763.02 | 2795.11 | 02-AUG-04:02 | 29.25 |
September | 9879946.57 | 2459.60 | 18-SEP-04:02 | 25.42 |
October | 10896835.49 | 2154.38 | 27-OCT-05:03 | 24.00 |
November | 11660960.23 | 2165.56 | 24-NOV-05:02 | 24.42 |
December | 11441732.88 | 1767.44 | 17-DEC-09:48 | 26.00 |
Annual Sum or Average | 0.135362E+09 | |||
Minimum of Months | 9332294.41 | 1767.44 | 23.95 | |
Maximum of Months | 13287735.27 | 2795.11 | 29.25 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17576886.54 | 3682.78 | 05-JAN-05:02 | 24.23 |
February | 14028189.98 | 3574.77 | 16-FEB-05:02 | 25.00 |
March | 18812042.08 | 3803.07 | 30-MAR-04:02 | 26.83 |
April | 18388644.55 | 3908.23 | 21-APR-04:02 | 26.00 |
May | 20911028.35 | 4076.86 | 10-MAY-04:02 | 28.33 |
June | 18025265.83 | 4149.88 | 29-JUN-04:02 | 26.58 |
July | 18368883.16 | 3819.90 | 06-JUL-04:02 | 25.17 |
August | 19364717.24 | 4367.82 | 02-AUG-04:02 | 29.25 |
September | 18912119.43 | 4075.96 | 28-SEP-04:02 | 25.67 |
October | 19466409.47 | 3773.56 | 24-OCT-04:02 | 24.08 |
November | 18857658.93 | 3856.32 | 03-NOV-04:02 | 25.92 |
December | 15255433.62 | 3198.63 | 09-DEC-05:02 | 24.00 |
Annual Sum or Average | 0.217967E+09 | |||
Minimum of Months | 14028189.98 | 3198.63 | 24.00 | |
Maximum of Months | 20911028.35 | 4367.82 | 29.25 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721715E+10 | 7552.50 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.654649E+10 | 7552.50 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.777905E+10 | 7552.50 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.694828E+10 | 7552.50 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.749810E+10 | 7552.50 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.746185E+10 | 7552.50 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.698453E+10 | 7552.50 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.777905E+10 | 7552.50 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.694828E+10 | 7552.50 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.721715E+10 | 7552.50 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.713256E+10 | 7552.50 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.698453E+10 | 7552.50 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.864970E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.654649E+10 | 7552.50 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.777905E+10 | 7552.50 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.905473E+09 | 1388.60 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.810345E+09 | 907.52 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.933432E+09 | 1111.04 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.818794E+09 | 833.48 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.882124E+09 | 833.48 | 09-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.868008E+09 | 833.48 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.820562E+09 | 833.48 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.913997E+09 | 833.48 | 02-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.835360E+09 | 833.48 | 07-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.877174E+09 | 907.52 | 11-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.901208E+09 | 1388.60 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.890124E+09 | 1388.60 | 04-DEC-16:49 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.104566E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.810345E+09 | 833.48 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.933432E+09 | 1388.60 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.573318E+09 | 879.10 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.513764E+09 | 703.38 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.592713E+09 | 703.38 | 01-MAR-16:49 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.521831E+09 | 527.66 | 10-APR-15:30 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.563669E+09 | 527.66 | 02-MAY-15:39 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.555962E+09 | 527.66 | 01-JUN-15:50 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.526085E+09 | 527.66 | 06-JUL-15:50 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.582757E+09 | 527.66 | 02-AUG-15:50 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.530458E+09 | 527.66 | 01-SEP-15:50 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.555972E+09 | 703.38 | 30-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.573409E+09 | 879.10 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.563772E+09 | 879.10 | 04-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.665371E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.513764E+09 | 527.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.592713E+09 | 879.10 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.883698E+09 | 1111.04 | 02-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.799477E+09 | 884.52 | 01-FEB-17:40 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.930882E+09 | 907.52 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.823816E+09 | 833.48 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.893108E+09 | 907.52 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.881738E+09 | 907.52 | 20-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.834299E+09 | 907.52 | 11-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.922280E+09 | 907.52 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.835469E+09 | 833.48 | 07-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.868088E+09 | 833.48 | 11-OCT-15:30 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.879884E+09 | 1388.60 | 09-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.864563E+09 | 1388.60 | 18-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.104173E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.799477E+09 | 833.48 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.930882E+09 | 1388.60 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.561106E+09 | 574.49 | 02-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.505540E+09 | 559.93 | 01-FEB-17:40 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.587576E+09 | 574.49 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.520268E+09 | 574.49 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.562517E+09 | 574.49 | 09-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.553713E+09 | 574.49 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.525761E+09 | 574.49 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.582485E+09 | 574.49 | 02-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.529417E+09 | 574.49 | 07-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.552442E+09 | 703.34 | 23-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.556393E+09 | 703.34 | 07-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.548280E+09 | 879.04 | 18-DEC-16:49 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.658550E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.505540E+09 | 559.93 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.587576E+09 | 879.04 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.903296E+09 | 1388.60 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.808793E+09 | 907.52 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.932469E+09 | 1111.04 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.817388E+09 | 833.48 | 21-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.881127E+09 | 833.48 | 09-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.867372E+09 | 833.48 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.819647E+09 | 833.48 | 07-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.912791E+09 | 833.48 | 02-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.834380E+09 | 833.48 | 07-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.875179E+09 | 907.52 | 23-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.899000E+09 | 1388.60 | 07-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.887125E+09 | 1388.60 | 04-DEC-16:49 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.104386E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.808793E+09 | 833.48 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.932469E+09 | 1388.60 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.572391E+09 | 879.10 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.513100E+09 | 703.38 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.592020E+09 | 703.38 | 01-MAR-16:49 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.521233E+09 | 527.66 | 10-APR-15:30 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.562638E+09 | 527.66 | 02-MAY-15:50 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.554927E+09 | 527.66 | 01-JUN-15:50 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.524928E+09 | 527.66 | 06-JUL-15:50 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.581917E+09 | 527.66 | 02-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.529633E+09 | 527.66 | 01-SEP-15:50 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.555099E+09 | 574.53 | 11-OCT-15:39 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.571766E+09 | 879.10 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.562641E+09 | 879.10 | 04-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.664229E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.513100E+09 | 527.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.592020E+09 | 879.10 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.882900E+09 | 1111.04 | 02-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.799048E+09 | 884.52 | 01-FEB-17:40 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.929818E+09 | 907.52 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.822689E+09 | 833.48 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.891395E+09 | 907.52 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.880020E+09 | 833.48 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.833119E+09 | 907.52 | 11-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.920717E+09 | 833.48 | 02-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.834528E+09 | 833.48 | 07-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.867135E+09 | 833.48 | 11-OCT-15:39 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.879575E+09 | 1388.60 | 09-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.863471E+09 | 1388.60 | 18-DEC-16:49 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.104044E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.799048E+09 | 833.48 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.929818E+09 | 1388.60 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.560483E+09 | 574.49 | 02-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.505149E+09 | 559.93 | 01-FEB-17:40 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.587143E+09 | 574.49 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.519436E+09 | 574.49 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.561535E+09 | 574.49 | 09-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.552945E+09 | 574.49 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.524790E+09 | 574.49 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.581491E+09 | 574.49 | 02-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.528629E+09 | 574.49 | 07-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.551507E+09 | 703.34 | 23-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.555782E+09 | 703.34 | 07-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.547566E+09 | 879.04 | 18-DEC-16:49 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.657646E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.505149E+09 | 559.93 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.587143E+09 | 879.04 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.905473E+09 | 1388.60 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.810345E+09 | 907.52 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.933432E+09 | 1111.04 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.818794E+09 | 833.48 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.882124E+09 | 833.48 | 09-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.868008E+09 | 833.48 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.820562E+09 | 833.48 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.913997E+09 | 833.48 | 02-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.835360E+09 | 833.48 | 07-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.877174E+09 | 907.52 | 11-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.901208E+09 | 1388.60 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.890124E+09 | 1388.60 | 04-DEC-16:49 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.104566E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.810345E+09 | 833.48 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.933432E+09 | 1388.60 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.573318E+09 | 879.10 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.513764E+09 | 703.38 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.592713E+09 | 703.38 | 01-MAR-16:49 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.521831E+09 | 527.66 | 10-APR-15:30 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.563660E+09 | 527.66 | 02-MAY-15:39 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.555962E+09 | 527.66 | 01-JUN-15:50 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.526085E+09 | 527.66 | 06-JUL-15:50 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.582757E+09 | 527.66 | 02-AUG-15:50 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.530458E+09 | 527.66 | 01-SEP-15:50 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.555972E+09 | 703.38 | 30-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.573408E+09 | 879.10 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.563772E+09 | 879.10 | 04-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.665370E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.513764E+09 | 527.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.592713E+09 | 879.10 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.883698E+09 | 1111.04 | 02-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.799477E+09 | 884.52 | 01-FEB-17:40 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.930882E+09 | 907.52 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.823816E+09 | 833.48 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.893108E+09 | 907.52 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.881738E+09 | 907.52 | 20-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.834294E+09 | 907.52 | 11-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.922280E+09 | 907.52 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.835469E+09 | 833.48 | 07-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.868088E+09 | 833.48 | 11-OCT-15:30 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.879884E+09 | 1388.60 | 09-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.864563E+09 | 1388.60 | 18-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.104173E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.799477E+09 | 833.48 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.930882E+09 | 1388.60 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.561106E+09 | 574.49 | 02-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.505540E+09 | 559.93 | 01-FEB-17:40 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.587573E+09 | 574.49 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.520268E+09 | 574.49 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.562508E+09 | 574.49 | 09-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.553687E+09 | 574.49 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.525761E+09 | 574.49 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.582485E+09 | 574.49 | 02-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.529417E+09 | 574.49 | 07-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.552440E+09 | 703.34 | 23-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.556393E+09 | 703.34 | 07-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.548280E+09 | 879.04 | 18-DEC-16:49 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.658546E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.505540E+09 | 559.93 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.587573E+09 | 879.04 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.721715E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.694828E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.749810E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.746185E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.698453E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.694828E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.721715E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.713256E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.698453E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.864970E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.654649E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.777905E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.905473E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51534271.64 | 32896004.95 |
February | 0.901968E+09 | 0.810345E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73066566.81 | 8160911.05 |
March | 0.107774E+10 | 0.933432E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124867E+09 | 12514998.81 |
April | 0.956342E+09 | 0.818794E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123941E+09 | 2327137.84 |
May | 0.103597E+10 | 0.882124E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135446E+09 | 7026691.65 |
June | 0.103308E+10 | 0.868008E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120058E+09 | 8769075.27 |
July | 0.959235E+09 | 0.820562E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74854237.20 | 7565134.24 |
August | 0.107774E+10 | 0.913997E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91258379.63 | 13496672.90 |
September | 0.956342E+09 | 0.835360E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68536473.56 | 8298064.75 |
October | 0.994195E+09 | 0.877174E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55356216.75 | 14961645.66 |
November | 0.984487E+09 | 0.901208E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43883166.79 | 17751115.62 |
December | 0.959235E+09 | 0.890124E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41680838.29 | 34232990.32 |
Annual Sum or Average | 0.119305E+11 | 0.104566E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100448E+10 | 0.168000E+09 |
Minimum of Months | 0.901968E+09 | 0.810345E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41680838.29 | 2327137.84 |
Maximum of Months | 0.107774E+10 | 0.933432E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135446E+09 | 34232990.32 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.573318E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34302926.28 | 22815396.03 |
February | 0.571020E+09 | 0.513764E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48079702.67 | 6114955.30 |
March | 0.682301E+09 | 0.592713E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81772672.77 | 9098036.19 |
April | 0.605444E+09 | 0.521831E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82316433.97 | 1739134.20 |
May | 0.655854E+09 | 0.563669E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92534795.98 | 4427050.06 |
June | 0.654023E+09 | 0.555962E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83045124.58 | 5402852.16 |
July | 0.607275E+09 | 0.526085E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51960026.39 | 4534169.84 |
August | 0.682301E+09 | 0.582757E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61381991.64 | 8867711.83 |
September | 0.605444E+09 | 0.530458E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45155164.24 | 5628301.06 |
October | 0.629407E+09 | 0.555972E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36762152.53 | 10027535.19 |
November | 0.623262E+09 | 0.573409E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28655161.66 | 12122942.31 |
December | 0.607275E+09 | 0.563772E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27514890.55 | 23457176.59 |
Annual Sum or Average | 0.755301E+10 | 0.665371E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673481E+09 | 0.114235E+09 |
Minimum of Months | 0.571020E+09 | 0.513764E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27514890.55 | 1739134.20 |
Maximum of Months | 0.682301E+09 | 0.592713E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92534795.98 | 23457176.59 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.883698E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46633646.35 | 37682652.99 |
February | 0.901968E+09 | 0.799477E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68634478.68 | 10022365.67 |
March | 0.107774E+10 | 0.930882E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121266E+09 | 13991750.14 |
April | 0.956342E+09 | 0.823816E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124694E+09 | 2283389.20 |
May | 0.103597E+10 | 0.893108E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138698E+09 | 6673762.54 |
June | 0.103308E+10 | 0.881738E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125085E+09 | 7997784.46 |
July | 0.959235E+09 | 0.834299E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77923707.00 | 6759061.61 |
August | 0.107774E+10 | 0.922280E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93255150.51 | 12910935.94 |
September | 0.956342E+09 | 0.835469E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67878370.27 | 8485176.74 |
October | 0.994195E+09 | 0.868088E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52533313.46 | 16388954.21 |
November | 0.984487E+09 | 0.879884E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40269671.65 | 19940151.45 |
December | 0.959235E+09 | 0.864563E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36917872.62 | 38299809.80 |
Annual Sum or Average | 0.119305E+11 | 0.104173E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993788E+09 | 0.181436E+09 |
Minimum of Months | 0.901968E+09 | 0.799477E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36917872.62 | 2283389.20 |
Maximum of Months | 0.107774E+10 | 0.930882E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138698E+09 | 38299809.80 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.561106E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34447117.40 | 23086085.33 |
February | 0.570983E+09 | 0.505540E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49089862.36 | 6152777.22 |
March | 0.682256E+09 | 0.587576E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82091546.29 | 10392596.47 |
April | 0.605404E+09 | 0.520268E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81277199.69 | 1837692.53 |
May | 0.655811E+09 | 0.562517E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92752311.75 | 4679846.72 |
June | 0.653980E+09 | 0.553713E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82312962.12 | 5768196.21 |
July | 0.607235E+09 | 0.525761E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52860130.97 | 4872573.24 |
August | 0.682256E+09 | 0.582485E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62451075.53 | 9630451.16 |
September | 0.605404E+09 | 0.529417E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46180678.33 | 5937422.87 |
October | 0.629366E+09 | 0.552442E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37982386.64 | 10471030.43 |
November | 0.623221E+09 | 0.556393E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30120953.41 | 12156988.67 |
December | 0.607235E+09 | 0.548280E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28236759.35 | 23379623.63 |
Annual Sum or Average | 0.755252E+10 | 0.658550E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679803E+09 | 0.118365E+09 |
Minimum of Months | 0.570983E+09 | 0.505540E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28236759.35 | 1837692.53 |
Maximum of Months | 0.682256E+09 | 0.587576E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92752311.75 | 23379623.63 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.903296E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28761621.73 | 18233844.80 |
February | 0.901968E+09 | 0.808793E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40292433.28 | 4868020.49 |
March | 0.107774E+10 | 0.932469E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69438874.98 | 7122501.07 |
April | 0.956342E+09 | 0.817388E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69138183.72 | 1270603.96 |
May | 0.103597E+10 | 0.881127E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73846115.20 | 4294501.58 |
June | 0.103308E+10 | 0.867372E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64836388.56 | 5097448.29 |
July | 0.959235E+09 | 0.819647E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40969188.69 | 4624471.40 |
August | 0.107774E+10 | 0.912791E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49580862.94 | 8920402.62 |
September | 0.956342E+09 | 0.834380E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37822187.98 | 4884155.32 |
October | 0.994195E+09 | 0.875179E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31177117.18 | 8170656.51 |
November | 0.984487E+09 | 0.899000E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24395187.36 | 10465557.81 |
December | 0.959235E+09 | 0.887125E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23545583.36 | 20604523.35 |
Annual Sum or Average | 0.119305E+11 | 0.104386E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553804E+09 | 98556687.19 |
Minimum of Months | 0.901968E+09 | 0.808793E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23545583.36 | 1270603.96 |
Maximum of Months | 0.107774E+10 | 0.932469E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73846115.20 | 20604523.35 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.572391E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18354390.50 | 13384888.72 |
February | 0.571020E+09 | 0.513100E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25588465.37 | 4124581.20 |
March | 0.682301E+09 | 0.592020E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43379348.80 | 6183635.68 |
April | 0.605444E+09 | 0.521233E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43775737.59 | 1106195.95 |
May | 0.655854E+09 | 0.562638E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49318296.59 | 2869241.12 |
June | 0.654023E+09 | 0.554927E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44401422.89 | 3276634.23 |
July | 0.607275E+09 | 0.524928E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27990007.69 | 2985771.61 |
August | 0.682301E+09 | 0.581917E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32506435.47 | 6351819.36 |
September | 0.605444E+09 | 0.529633E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24087122.87 | 3709270.74 |
October | 0.629407E+09 | 0.555099E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19873571.88 | 6082482.65 |
November | 0.623262E+09 | 0.571766E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15445997.93 | 7690827.88 |
December | 0.607275E+09 | 0.562641E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14835364.47 | 14713393.96 |
Annual Sum or Average | 0.755301E+10 | 0.664229E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359556E+09 | 72478743.11 |
Minimum of Months | 0.571020E+09 | 0.513100E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14835364.47 | 1106195.95 |
Maximum of Months | 0.682301E+09 | 0.592020E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49318296.59 | 14713393.96 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.882900E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151394E+10 | 0.131240E+09 |
February | 0.901968E+09 | 0.799048E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158922E+10 | 72664317.56 |
March | 0.107774E+10 | 0.929818E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230527E+10 | 14399573.73 |
April | 0.956342E+09 | 0.822689E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224534E+10 | 1533747.73 |
May | 0.103597E+10 | 0.891395E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236642E+10 | 5256721.58 |
June | 0.103308E+10 | 0.880020E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244975E+10 | 8820707.42 |
July | 0.959235E+09 | 0.833119E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149644E+10 | 6671165.32 |
August | 0.107774E+10 | 0.920717E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196851E+10 | 10613844.55 |
September | 0.956342E+09 | 0.834528E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165094E+10 | 7796487.50 |
October | 0.994195E+09 | 0.867135E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146473E+10 | 21481342.25 |
November | 0.984487E+09 | 0.879575E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148955E+10 | 31007469.28 |
December | 0.959235E+09 | 0.863471E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126034E+10 | 0.119807E+09 |
Annual Sum or Average | 0.119305E+11 | 0.104044E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218005E+11 | 0.431292E+09 |
Minimum of Months | 0.901968E+09 | 0.799048E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126034E+10 | 1533747.73 |
Maximum of Months | 0.107774E+10 | 0.929818E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244975E+10 | 0.131240E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.560483E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17943464.11 | 13717643.57 |
February | 0.570983E+09 | 0.505149E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25493390.50 | 4366554.51 |
March | 0.682256E+09 | 0.587143E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42715054.63 | 7125467.25 |
April | 0.605404E+09 | 0.519436E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42491070.09 | 1231855.95 |
May | 0.655811E+09 | 0.561535E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48804095.75 | 3090513.36 |
June | 0.653980E+09 | 0.552945E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43342765.23 | 3512811.97 |
July | 0.607235E+09 | 0.524790E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27731718.81 | 3238878.27 |
August | 0.682256E+09 | 0.581491E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32346142.07 | 6843625.70 |
September | 0.605404E+09 | 0.528629E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24118454.11 | 3938724.69 |
October | 0.629366E+09 | 0.551507E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19888677.38 | 6428208.86 |
November | 0.623221E+09 | 0.555782E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15613009.33 | 7820206.79 |
December | 0.607235E+09 | 0.547566E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14687999.08 | 14912308.82 |
Annual Sum or Average | 0.755252E+10 | 0.657646E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355176E+09 | 76226799.74 |
Minimum of Months | 0.570983E+09 | 0.505149E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14687999.08 | 1231855.95 |
Maximum of Months | 0.682256E+09 | 0.587143E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48804095.75 | 14912308.82 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.905473E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43905639.36 | 29103920.39 |
February | 0.901968E+09 | 0.810345E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61210625.52 | 7737569.14 |
March | 0.107774E+10 | 0.933432E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105745E+09 | 11318089.35 |
April | 0.956342E+09 | 0.818794E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105412E+09 | 2036472.85 |
May | 0.103597E+10 | 0.882124E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113986E+09 | 5982733.33 |
June | 0.103308E+10 | 0.868008E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101689E+09 | 7263186.31 |
July | 0.959235E+09 | 0.820562E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63476617.62 | 6453580.06 |
August | 0.107774E+10 | 0.913997E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77120817.44 | 12080265.50 |
September | 0.956342E+09 | 0.835360E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58538486.32 | 6915964.09 |
October | 0.994195E+09 | 0.877174E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47471992.22 | 12813843.72 |
November | 0.984487E+09 | 0.901208E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37297939.62 | 16018029.05 |
December | 0.959235E+09 | 0.890124E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35753177.87 | 31019179.26 |
Annual Sum or Average | 0.119305E+11 | 0.104566E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851607E+09 | 0.148743E+09 |
Minimum of Months | 0.901968E+09 | 0.810345E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35753177.87 | 2036472.85 |
Maximum of Months | 0.107774E+10 | 0.933432E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113986E+09 | 31019179.26 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.573318E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29128099.52 | 20036815.74 |
February | 0.421807E+09 | 0.513764E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40192581.93 | 5710528.45 |
March | 0.502994E+09 | 0.592713E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68934871.58 | 8160722.86 |
April | 0.447140E+09 | 0.521831E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69634088.35 | 1518264.95 |
May | 0.484071E+09 | 0.563660E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77874680.75 | 3771602.54 |
June | 0.482240E+09 | 0.555962E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70612361.62 | 4468369.31 |
July | 0.448971E+09 | 0.526085E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44273482.49 | 3860073.99 |
August | 0.502994E+09 | 0.582757E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51846396.56 | 7924849.06 |
September | 0.447140E+09 | 0.530458E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38380590.88 | 4709889.31 |
October | 0.465148E+09 | 0.555972E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31429451.32 | 8624936.20 |
November | 0.460569E+09 | 0.573408E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24418401.47 | 10905022.80 |
December | 0.448971E+09 | 0.563772E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23435350.69 | 21099434.68 |
Annual Sum or Average | 0.557719E+10 | 0.665370E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570160E+09 | 0.100791E+09 |
Minimum of Months | 0.421807E+09 | 0.513764E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23435350.69 | 1518264.95 |
Maximum of Months | 0.502994E+09 | 0.592713E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77874680.75 | 21099434.68 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.883698E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39031183.09 | 33136882.04 |
February | 0.901968E+09 | 0.799477E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57096735.92 | 9420960.27 |
March | 0.107774E+10 | 0.930882E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102054E+09 | 12600584.24 |
April | 0.956342E+09 | 0.823816E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106084E+09 | 1999413.47 |
May | 0.103597E+10 | 0.893108E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117162E+09 | 5696160.99 |
June | 0.103308E+10 | 0.881738E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106676E+09 | 6591029.00 |
July | 0.959235E+09 | 0.834294E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66714489.25 | 5718664.30 |
August | 0.107774E+10 | 0.922280E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79059327.43 | 11580931.42 |
September | 0.956342E+09 | 0.835469E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57740745.06 | 7079313.54 |
October | 0.994195E+09 | 0.868088E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44479735.51 | 14036334.82 |
November | 0.984487E+09 | 0.879884E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33731091.98 | 17894837.16 |
December | 0.959235E+09 | 0.864563E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30920421.12 | 34350025.06 |
Annual Sum or Average | 0.119305E+11 | 0.104173E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840751E+09 | 0.160105E+09 |
Minimum of Months | 0.901968E+09 | 0.799477E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30920421.12 | 1999413.47 |
Maximum of Months | 0.107774E+10 | 0.930882E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117162E+09 | 34350025.06 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.561106E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28449452.81 | 20544498.01 |
February | 0.570983E+09 | 0.505540E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40172884.44 | 5969627.25 |
March | 0.682256E+09 | 0.587573E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68099455.91 | 9445667.71 |
April | 0.605404E+09 | 0.520268E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67685700.82 | 1665722.04 |
May | 0.655811E+09 | 0.562508E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77012764.67 | 4036352.10 |
June | 0.653980E+09 | 0.553687E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69165965.83 | 4848195.37 |
July | 0.607235E+09 | 0.525761E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44019615.72 | 4251617.82 |
August | 0.682256E+09 | 0.582485E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51761796.63 | 8721512.35 |
September | 0.605404E+09 | 0.529417E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38556531.05 | 5078597.04 |
October | 0.629366E+09 | 0.552440E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31679820.59 | 9181534.28 |
November | 0.623221E+09 | 0.556393E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24886332.35 | 11088498.75 |
December | 0.607235E+09 | 0.548280E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23289746.36 | 21276298.13 |
Annual Sum or Average | 0.755252E+10 | 0.658546E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564780E+09 | 0.106108E+09 |
Minimum of Months | 0.570983E+09 | 0.505540E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23289746.36 | 1665722.04 |
Maximum of Months | 0.682256E+09 | 0.587573E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77012764.67 | 21276298.13 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44223284.53 | 39406237.16 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67438687.90 | 9406758.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120119E+09 | 13536139.19 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127810E+09 | 2025950.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140115E+09 | 6810998.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125683E+09 | 8016198.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76790369.00 | 6530868.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88853399.12 | 12929340.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66763999.05 | 7634327.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52265810.03 | 15269722.18 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38921599.75 | 20550002.43 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35867882.96 | 43071776.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984852E+09 | 0.185188E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35867882.96 | 2025950.52 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140115E+09 | 43071776.76 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58109645.50 | 49373871.06 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87653488.22 | 11335403.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154854E+09 | 16536111.17 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163789E+09 | 2501761.22 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179039E+09 | 8378655.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160812E+09 | 10180385.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99567193.80 | 8136330.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115770E+09 | 14734377.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86520651.10 | 9128474.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67865387.18 | 19047069.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50977788.78 | 24629368.88 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47368747.54 | 52765988.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127233E+10 | 0.226748E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47368747.54 | 2501761.22 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179039E+09 | 52765988.37 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52755358.29 | 40754826.25 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82987046.18 | 6010520.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153843E+09 | 9926520.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162391E+09 | 1444198.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180894E+09 | 7136623.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157363E+09 | 10547673.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83449519.55 | 8231539.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111603E+09 | 12133775.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77323938.42 | 9885660.24 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56621548.62 | 18289784.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45047814.20 | 20399031.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39153085.27 | 42555606.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120343E+10 | 0.187316E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39153085.27 | 1444198.40 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180894E+09 | 42555606.95 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7552.50 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7552.50 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7552.50 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7552.50 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7552.50 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7552.50 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7552.50 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7552.50 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7552.50 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7552.50 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7552.50 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7552.50 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7552.50 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1388.60 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 199.31 | 15-JAN-13:00 | 423.72 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 907.52 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 349.33 | 26-FEB-15:55 | 53.53 | 20-FEB-06:42 |
March | 1306.65 | 01-MAR-10:09 | 1111.04 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 613.00 | 19-MAR-16:05 | 92.38 | 14-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 833.48 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 316.96 | 30-APR-15:25 | 35.16 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 833.48 | 09-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 447.28 | 07-MAY-15:00 | 180.73 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 833.48 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 410.53 | 18-JUN-14:20 | 215.12 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 833.48 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.09 | 04-JUL-14:18 | 113.46 | 02-JUL-13:40 |
August | 1306.65 | 01-AUG-09:09 | 833.48 | 02-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 428.99 | 06-AUG-12:23 | 198.18 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 833.48 | 07-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 423.90 | 10-SEP-14:46 | 106.68 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 907.52 | 11-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 398.73 | 29-OCT-12:58 | 90.26 | 22-OCT-18:00 |
November | 1306.65 | 01-NOV-09:09 | 1388.60 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.98 | 11-NOV-16:00 | 95.09 | 26-NOV-10:00 |
December | 1306.65 | 01-DEC-10:09 | 1388.60 | 04-DEC-16:49 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 154.64 | 31-DEC-13:00 | 168.97 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 154.64 | 35.16 | |||||
Maximum of Months | 1306.65 | 1388.60 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 613.00 | 423.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 879.10 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 126.25 | 15-JAN-13:00 | 281.32 | 07-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 703.38 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 240.07 | 26-FEB-15:57 | 56.33 | 19-FEB-07:00 |
March | 827.22 | 01-MAR-10:09 | 703.38 | 01-MAR-16:49 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 428.79 | 19-MAR-16:05 | 63.37 | 05-MAR-07:20 |
April | 827.22 | 03-APR-09:09 | 527.66 | 10-APR-15:30 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.98 | 30-APR-15:27 | 36.21 | 23-APR-07:00 |
May | 827.22 | 01-MAY-09:09 | 527.66 | 02-MAY-15:39 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.70 | 07-MAY-14:35 | 119.97 | 08-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 527.66 | 01-JUN-15:50 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.87 | 18-JUN-14:46 | 140.68 | 20-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 527.66 | 06-JUL-15:50 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.44 | 04-JUL-14:20 | 68.21 | 02-JUL-13:40 |
August | 827.22 | 01-AUG-09:09 | 527.66 | 02-AUG-15:50 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.25 | 06-AUG-13:00 | 140.62 | 20-AUG-10:50 |
September | 827.22 | 01-SEP-09:09 | 527.66 | 01-SEP-15:50 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.18 | 10-SEP-14:48 | 68.72 | 15-SEP-22:00 |
October | 827.22 | 02-OCT-09:09 | 703.38 | 30-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.95 | 29-OCT-13:00 | 59.69 | 22-OCT-18:00 |
November | 827.22 | 01-NOV-09:09 | 879.10 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.05 | 11-NOV-16:00 | 70.31 | 26-NOV-10:00 |
December | 827.22 | 01-DEC-10:09 | 879.10 | 04-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 108.07 | 31-DEC-13:00 | 112.18 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 527.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 108.07 | 36.21 | |||||
Maximum of Months | 827.22 | 879.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 428.79 | 281.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1111.04 | 02-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.50 | 15-JAN-12:45 | 439.68 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 884.52 | 01-FEB-17:40 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 330.71 | 26-FEB-15:55 | 60.75 | 20-FEB-06:42 |
March | 1306.65 | 01-MAR-10:09 | 907.52 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 608.89 | 19-MAR-15:50 | 94.13 | 14-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 833.48 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.33 | 30-APR-15:25 | 34.67 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 907.52 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 447.29 | 07-MAY-15:00 | 178.62 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 907.52 | 20-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 431.81 | 18-JUN-14:06 | 208.35 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 11-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 363.04 | 04-JUL-14:18 | 90.41 | 02-JUL-13:40 |
August | 1306.65 | 01-AUG-09:09 | 907.52 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 448.75 | 06-AUG-13:00 | 196.33 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 833.48 | 07-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 422.65 | 10-SEP-14:46 | 108.03 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 833.48 | 11-OCT-15:30 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 384.27 | 29-OCT-12:55 | 92.32 | 22-OCT-18:00 |
November | 1306.65 | 01-NOV-09:09 | 1388.60 | 09-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.79 | 11-NOV-15:38 | 105.56 | 26-NOV-10:00 |
December | 1306.65 | 01-DEC-10:09 | 1388.60 | 18-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 141.30 | 31-DEC-12:56 | 172.98 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 141.30 | 34.67 | |||||
Maximum of Months | 1306.65 | 1388.60 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 608.89 | 439.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 574.49 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 147.83 | 15-JAN-12:50 | 281.90 | 07-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 559.93 | 01-FEB-17:40 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 225.61 | 19-FEB-15:08 | 36.74 | 20-FEB-06:42 |
March | 827.17 | 01-MAR-10:09 | 574.49 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 405.93 | 19-MAR-15:50 | 61.29 | 03-MAR-05:40 |
April | 827.17 | 03-APR-09:09 | 574.49 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.87 | 30-APR-15:25 | 33.26 | 09-APR-16:10 |
May | 827.17 | 01-MAY-09:09 | 574.49 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.81 | 21-MAY-11:50 | 119.47 | 08-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 574.49 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.07 | 18-JUN-14:06 | 143.76 | 20-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 574.49 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.20 | 04-JUL-14:18 | 62.65 | 02-JUL-13:40 |
August | 827.17 | 01-AUG-09:09 | 574.49 | 02-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.85 | 06-AUG-12:23 | 131.13 | 20-AUG-11:00 |
September | 827.17 | 01-SEP-09:09 | 574.49 | 07-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 281.56 | 10-SEP-14:44 | 69.16 | 15-SEP-22:00 |
October | 827.17 | 02-OCT-09:09 | 703.34 | 23-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.34 | 29-OCT-13:00 | 60.84 | 22-OCT-18:00 |
November | 827.17 | 01-NOV-09:09 | 703.34 | 07-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.09 | 11-NOV-15:40 | 64.15 | 26-NOV-10:00 |
December | 827.17 | 01-DEC-10:09 | 879.04 | 18-DEC-16:49 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.73 | 31-DEC-10:00 | 112.70 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 559.93 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 114.73 | 33.26 | |||||
Maximum of Months | 827.17 | 879.04 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 405.93 | 281.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1388.60 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 117.99 | 15-JAN-13:00 | 279.85 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 907.52 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 205.00 | 20-FEB-16:00 | 30.20 | 26-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 1111.04 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.74 | 19-MAR-16:00 | 54.90 | 03-MAR-05:30 |
April | 1306.65 | 03-APR-09:09 | 833.48 | 21-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.78 | 30-APR-15:30 | 22.52 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 833.48 | 09-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.49 | 07-MAY-15:00 | 107.43 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 833.48 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.93 | 18-JUN-14:06 | 121.86 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 833.48 | 07-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.93 | 04-JUL-14:18 | 46.19 | 02-JUL-13:40 |
August | 1306.65 | 01-AUG-09:09 | 833.48 | 02-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.13 | 06-AUG-13:00 | 111.94 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 833.48 | 07-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.50 | 10-SEP-15:00 | 70.69 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 907.52 | 23-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.91 | 29-OCT-13:00 | 49.62 | 23-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1388.60 | 07-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.38 | 11-NOV-15:50 | 54.69 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1388.60 | 04-DEC-16:49 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.59 | 24-DEC-15:00 | 103.37 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 91.59 | 22.52 | |||||
Maximum of Months | 1306.65 | 1388.60 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 359.74 | 279.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 879.10 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.69 | 15-JAN-13:00 | 195.60 | 07-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 703.38 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 140.30 | 19-FEB-15:00 | 29.42 | 20-FEB-07:10 |
March | 827.22 | 01-MAR-10:09 | 703.38 | 01-MAR-16:49 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 246.27 | 19-MAR-16:00 | 39.19 | 14-MAR-22:00 |
April | 827.22 | 03-APR-09:09 | 527.66 | 10-APR-15:30 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.49 | 02-APR-15:40 | 20.69 | 23-APR-07:00 |
May | 827.22 | 01-MAY-09:09 | 527.66 | 02-MAY-15:50 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.58 | 07-MAY-14:37 | 73.46 | 08-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 527.66 | 01-JUN-15:50 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.83 | 18-JUN-14:50 | 80.33 | 20-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 527.66 | 06-JUL-15:50 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.33 | 04-JUL-14:20 | 28.69 | 02-JUL-13:40 |
August | 827.22 | 01-AUG-09:09 | 527.66 | 02-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.44 | 06-AUG-13:00 | 79.71 | 20-AUG-10:50 |
September | 827.22 | 01-SEP-09:09 | 527.66 | 01-SEP-15:50 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.85 | 10-SEP-14:55 | 49.16 | 15-SEP-22:00 |
October | 827.22 | 02-OCT-09:09 | 574.53 | 11-OCT-15:39 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.46 | 29-OCT-13:00 | 33.23 | 23-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 879.10 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.76 | 11-NOV-15:50 | 40.62 | 26-NOV-10:00 |
December | 827.22 | 01-DEC-10:09 | 879.10 | 04-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.30 | 24-DEC-15:00 | 69.99 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 527.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 59.30 | 20.69 | |||||
Maximum of Months | 827.22 | 879.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 246.27 | 195.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1111.04 | 02-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9422.14 | 04-JAN-12:02 | 5322.96 | 23-JAN-07:03 |
February | 1306.65 | 01-FEB-10:09 | 884.52 | 01-FEB-17:40 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9195.80 | 24-FEB-17:03 | 3399.23 | 02-FEB-07:03 |
March | 1306.65 | 01-MAR-10:09 | 907.52 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11399.41 | 21-MAR-11:02 | 962.66 | 15-MAR-06:05 |
April | 1306.65 | 03-APR-09:09 | 833.48 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11771.41 | 11-APR-16:02 | 201.02 | 14-APR-16:00 |
May | 1306.65 | 01-MAY-09:09 | 907.52 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13819.74 | 05-MAY-11:01 | 183.98 | 18-MAY-05:02 |
June | 1306.65 | 01-JUN-09:09 | 833.48 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12543.54 | 12-JUN-16:02 | 761.18 | 21-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 11-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9820.14 | 20-JUL-16:03 | 449.64 | 13-JUL-05:02 |
August | 1306.65 | 01-AUG-09:09 | 833.48 | 02-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11033.81 | 15-AUG-11:02 | 412.03 | 21-AUG-11:10 |
September | 1306.65 | 01-SEP-09:09 | 833.48 | 07-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9516.68 | 13-SEP-16:03 | 1252.67 | 15-SEP-17:00 |
October | 1306.65 | 02-OCT-09:09 | 833.48 | 11-OCT-15:39 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9160.53 | 04-OCT-11:02 | 1246.27 | 30-OCT-17:00 |
November | 1306.65 | 01-NOV-09:09 | 1388.60 | 09-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8767.20 | 10-NOV-12:02 | 2424.72 | 27-NOV-07:03 |
December | 1306.65 | 01-DEC-10:09 | 1388.60 | 18-DEC-16:49 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7820.97 | 11-DEC-12:02 | 5620.75 | 21-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 7820.97 | 183.98 | |||||
Maximum of Months | 1306.65 | 1388.60 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13819.74 | 5620.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 574.49 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 78.23 | 15-JAN-12:50 | 196.50 | 07-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 559.93 | 01-FEB-17:40 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 133.52 | 19-FEB-14:55 | 21.64 | 26-FEB-07:00 |
March | 827.17 | 01-MAR-10:09 | 574.49 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 229.38 | 19-MAR-15:54 | 38.89 | 03-MAR-05:30 |
April | 827.17 | 03-APR-09:09 | 574.49 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.21 | 30-APR-15:25 | 17.37 | 22-APR-03:00 |
May | 827.17 | 01-MAY-09:09 | 574.49 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.66 | 07-MAY-15:00 | 73.81 | 08-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 574.49 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.87 | 18-JUN-14:06 | 82.33 | 20-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 574.49 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.03 | 04-JUL-14:18 | 26.47 | 02-JUL-13:40 |
August | 827.17 | 01-AUG-09:09 | 574.49 | 02-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.67 | 06-AUG-12:23 | 74.88 | 20-AUG-11:00 |
September | 827.17 | 01-SEP-09:09 | 574.49 | 07-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.31 | 10-SEP-14:55 | 50.47 | 15-SEP-22:00 |
October | 827.17 | 02-OCT-09:09 | 703.34 | 23-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.56 | 29-OCT-13:00 | 33.53 | 22-OCT-18:00 |
November | 827.17 | 01-NOV-09:09 | 703.34 | 07-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.35 | 11-NOV-15:32 | 37.55 | 26-NOV-10:00 |
December | 827.17 | 01-DEC-10:09 | 879.04 | 18-DEC-16:49 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.93 | 31-DEC-12:50 | 70.25 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 559.93 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 59.93 | 17.37 | |||||
Maximum of Months | 827.17 | 879.04 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 229.38 | 196.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1388.60 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.05 | 15-JAN-13:00 | 401.76 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 907.52 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 309.08 | 19-FEB-15:00 | 47.82 | 19-FEB-06:57 |
March | 1306.65 | 01-MAR-10:09 | 1111.04 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 520.21 | 19-MAR-15:51 | 82.73 | 03-MAR-05:30 |
April | 1306.65 | 03-APR-09:09 | 833.48 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.50 | 30-APR-15:25 | 33.05 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 833.48 | 09-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.64 | 07-MAY-15:00 | 151.66 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 833.48 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 342.81 | 18-JUN-14:20 | 175.80 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 833.48 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.33 | 04-JUL-14:18 | 77.33 | 02-JUL-14:00 |
August | 1306.65 | 01-AUG-09:09 | 833.48 | 02-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 349.17 | 06-AUG-12:50 | 170.21 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 833.48 | 07-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.56 | 10-SEP-15:00 | 96.46 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 907.52 | 11-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.41 | 29-OCT-13:00 | 76.90 | 23-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1388.60 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.73 | 11-NOV-15:50 | 82.25 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1388.60 | 04-DEC-16:49 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.94 | 24-DEC-15:00 | 153.14 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 136.94 | 33.05 | |||||
Maximum of Months | 1306.65 | 1388.60 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 520.21 | 401.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 879.10 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 112.48 | 15-JAN-13:00 | 266.69 | 07-JAN-05:00 |
February | 805.43 | 01-FEB-08:09 | 703.38 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 218.91 | 19-FEB-15:00 | 49.69 | 19-FEB-06:57 |
March | 805.43 | 01-MAR-08:09 | 703.38 | 01-MAR-16:49 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 355.63 | 19-MAR-16:10 | 55.12 | 05-MAR-07:10 |
April | 805.43 | 03-APR-07:10 | 527.66 | 10-APR-15:30 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.53 | 02-APR-15:40 | 32.38 | 23-APR-07:00 |
May | 805.43 | 01-MAY-07:10 | 527.66 | 02-MAY-15:39 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.84 | 07-MAY-14:37 | 100.78 | 08-MAY-22:00 |
June | 805.43 | 01-JUN-07:10 | 527.66 | 01-JUN-15:50 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.47 | 18-JUN-14:48 | 114.93 | 20-JUN-23:00 |
July | 805.43 | 03-JUL-07:10 | 527.66 | 06-JUL-15:50 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.12 | 04-JUL-14:20 | 42.89 | 02-JUL-13:20 |
August | 805.43 | 01-AUG-07:10 | 527.66 | 02-AUG-15:50 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.04 | 06-AUG-12:50 | 121.33 | 20-AUG-10:50 |
September | 805.43 | 01-SEP-07:10 | 527.66 | 01-SEP-15:50 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.61 | 10-SEP-14:55 | 61.93 | 15-SEP-22:00 |
October | 805.43 | 02-OCT-07:10 | 703.38 | 30-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.04 | 29-OCT-13:00 | 50.62 | 23-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 879.10 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.29 | 11-NOV-15:50 | 60.09 | 26-NOV-10:00 |
December | 805.43 | 01-DEC-08:09 | 879.10 | 04-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 92.64 | 24-DEC-15:00 | 101.59 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 527.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 92.64 | 32.38 | |||||
Maximum of Months | 805.43 | 879.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 355.63 | 266.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1111.04 | 02-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 133.99 | 15-JAN-12:45 | 415.32 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 884.52 | 01-FEB-17:40 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 289.85 | 19-FEB-14:55 | 54.93 | 19-FEB-06:57 |
March | 1306.65 | 01-MAR-10:09 | 907.52 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 511.38 | 19-MAR-15:51 | 83.80 | 03-MAR-05:30 |
April | 1306.65 | 03-APR-09:09 | 833.48 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.09 | 30-APR-15:27 | 32.61 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 907.52 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.83 | 07-MAY-14:35 | 149.85 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 907.52 | 20-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.45 | 18-JUN-14:06 | 170.16 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 907.52 | 11-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.42 | 04-JUL-14:20 | 53.44 | 02-JUL-13:20 |
August | 1306.65 | 01-AUG-09:09 | 907.52 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 363.57 | 06-AUG-12:50 | 168.62 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 833.48 | 07-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.25 | 10-SEP-14:55 | 97.57 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 833.48 | 11-OCT-15:30 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.87 | 29-OCT-12:55 | 77.33 | 23-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1388.60 | 09-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.23 | 11-NOV-15:28 | 90.20 | 26-NOV-10:00 |
December | 1306.65 | 01-DEC-10:09 | 1388.60 | 18-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 117.46 | 31-DEC-12:56 | 156.43 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 833.48 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 117.46 | 32.61 | |||||
Maximum of Months | 1306.65 | 1388.60 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 511.38 | 415.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 574.49 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 126.10 | 15-JAN-12:50 | 268.31 | 07-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 559.93 | 01-FEB-17:40 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 209.16 | 19-FEB-14:55 | 33.71 | 19-FEB-06:57 |
March | 827.17 | 01-MAR-10:09 | 574.49 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 338.99 | 19-MAR-15:50 | 55.91 | 03-MAR-05:30 |
April | 827.17 | 03-APR-09:09 | 574.49 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.34 | 30-APR-15:23 | 26.58 | 09-APR-16:23 |
May | 827.17 | 01-MAY-09:09 | 574.49 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.57 | 21-MAY-12:00 | 101.33 | 08-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 574.49 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.98 | 18-JUN-14:04 | 118.11 | 20-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 574.49 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.58 | 04-JUL-14:18 | 42.06 | 02-JUL-14:00 |
August | 827.17 | 01-AUG-09:09 | 574.49 | 02-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.25 | 06-AUG-12:50 | 112.74 | 20-AUG-11:00 |
September | 827.17 | 01-SEP-09:09 | 574.49 | 07-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.20 | 10-SEP-15:00 | 63.45 | 15-SEP-22:00 |
October | 827.17 | 02-OCT-09:09 | 703.34 | 23-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.35 | 29-OCT-13:00 | 50.81 | 23-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 703.34 | 07-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.93 | 05-NOV-11:10 | 55.24 | 26-NOV-10:00 |
December | 827.17 | 01-DEC-10:09 | 879.04 | 18-DEC-16:49 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.89 | 31-DEC-12:50 | 102.22 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 559.93 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 95.89 | 26.58 | |||||
Maximum of Months | 827.17 | 879.04 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 338.99 | 268.31 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.21 | 15-JAN-13:00 | 605.43 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.14 | 19-FEB-15:00 | 61.38 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.68 | 19-MAR-16:00 | 110.35 | 03-MAR-05:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.95 | 30-APR-15:50 | 43.00 | 22-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.18 | 07-MAY-15:00 | 183.40 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.68 | 18-JUN-14:30 | 184.92 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.97 | 04-JUL-14:00 | 61.19 | 19-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.27 | 06-AUG-13:00 | 181.89 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.41 | 10-SEP-15:00 | 127.25 | 15-SEP-22:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.07 | 29-OCT-13:00 | 99.29 | 23-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.97 | 11-NOV-15:53 | 113.31 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.59 | 24-DEC-15:00 | 218.23 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.59 | 43.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.68 | 605.43 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.58 | 15-JAN-13:00 | 729.50 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.76 | 19-FEB-15:00 | 86.02 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 856.60 | 19-MAR-15:51 | 135.50 | 03-MAR-05:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.32 | 30-APR-15:50 | 52.23 | 22-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.31 | 07-MAY-15:00 | 237.87 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.87 | 18-JUN-14:30 | 233.46 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.04 | 04-JUL-14:00 | 76.10 | 19-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597.74 | 06-AUG-12:50 | 218.36 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 610.83 | 10-SEP-15:00 | 152.39 | 15-SEP-22:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.63 | 29-OCT-13:00 | 126.93 | 23-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.20 | 11-NOV-15:53 | 141.40 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.85 | 24-DEC-15:00 | 270.78 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.85 | 52.23 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 856.60 | 729.50 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.87 | 15-JAN-13:00 | 542.80 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.16 | 19-FEB-14:52 | 74.94 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 664.24 | 19-MAR-15:50 | 116.49 | 03-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.53 | 09-APR-15:00 | 33.96 | 13-APR-04:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 611.64 | 21-MAY-12:00 | 225.00 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.35 | 18-JUN-13:52 | 279.55 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.73 | 04-JUL-14:00 | 220.54 | 02-JUL-13:40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651.10 | 06-AUG-12:42 | 271.79 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.90 | 10-SEP-15:00 | 192.44 | 03-SEP-16:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.95 | 29-OCT-13:00 | 152.84 | 29-OCT-16:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.26 | 11-NOV-16:00 | 140.07 | 26-NOV-10:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.96 | 31-DEC-09:53 | 236.45 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.96 | 33.96 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 664.24 | 542.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 46123.85 | 03-JAN-05:02 | 0.00 | 4195.72 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 48860.39 | 06-FEB-06:03 | 4446.85 | 5874.01 | 34926.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 46667.28 | 08-MAR-05:02 | 0.00 | 4195.72 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45282.76 | 08-APR-04:02 | 0.00 | 2097.86 | 18975.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45860.22 | 25-MAY-04:02 | 0.00 | 4195.72 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 45604.21 | 01-JUN-04:02 | 0.00 | 4195.72 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 45990.59 | 07-JUL-04:02 | 0.00 | 4195.72 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 46251.11 | 22-AUG-04:03 | 0.00 | 3356.58 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48726.59 | 19-SEP-05:03 | 3811.58 | 5034.86 | 29937.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 46340.69 | 24-OCT-04:02 | 0.00 | 4195.72 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 46205.94 | 04-NOV-04:02 | 0.00 | 2097.86 | 18975.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 46098.65 | 09-DEC-05:02 | 0.00 | 2097.86 | 18975.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 45282.76 | 0.00 | 2097.86 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48860.39 | 4446.85 | 5874.01 | 34926.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11358.06 | 04-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 | 0.00 |
February | 12591.05 | 21-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.22 | 0.00 |
March | 12753.23 | 21-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.71 | 0.00 |
April | 11902.38 | 11-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.22 | 0.00 |
May | 12792.42 | 05-MAY-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.09 | 0.00 |
June | 12527.46 | 16-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.01 | 0.00 |
July | 10955.24 | 14-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.13 | 0.00 |
August | 11570.74 | 14-AUG-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.41 | 0.00 |
September | 11593.22 | 06-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.97 | 0.00 |
October | 10985.85 | 04-OCT-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.32 | 0.00 |
November | 10892.80 | 22-NOV-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.87 | 0.00 |
December | 11167.00 | 26-DEC-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10892.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.87 | 0.00 | |
Maximum of Months | 12792.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.01 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5354.95 | 17-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.21 | 0.00 |
February | 5838.98 | 21-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.13 | 0.00 |
March | 5579.14 | 20-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.49 | 0.00 |
April | 5184.57 | 17-APR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.59 | 0.00 |
May | 5609.39 | 30-MAY-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.25 | 0.00 |
June | 5800.88 | 12-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.36 | 0.00 |
July | 4903.65 | 05-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.32 | 0.00 |
August | 5119.82 | 14-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.76 | 0.00 |
September | 5168.05 | 05-SEP-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.80 | 0.00 |
October | 5272.46 | 10-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.63 | 0.00 |
November | 5362.16 | 13-NOV-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.07 | 0.00 |
December | 5391.88 | 26-DEC-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4903.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.11 | 0.00 | |
Maximum of Months | 5838.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.49 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5707.11 | 02-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.34 | 0.00 |
February | 5971.39 | 21-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.04 | 0.00 |
March | 5783.75 | 20-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.93 | 0.00 |
April | 5540.36 | 17-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.88 | 0.00 |
May | 6286.64 | 30-MAY-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 | 0.00 |
June | 6152.28 | 12-JUN-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.09 | 0.00 |
July | 5518.07 | 17-JUL-12:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.68 | 0.00 |
August | 5664.00 | 14-AUG-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.06 | 0.00 |
September | 5801.67 | 05-SEP-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.37 | 0.00 |
October | 5724.82 | 10-OCT-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.77 | 0.00 |
November | 5867.77 | 13-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.71 | 0.00 |
December | 5711.07 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5518.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6286.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.93 | 12.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 34846.70 | 10-JAN-05:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 37133.35 | 06-FEB-06:03 | 4446.85 | 5874.01 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34833.27 | 10-MAR-05:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34197.53 | 05-APR-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34778.16 | 11-MAY-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34743.71 | 01-JUN-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34721.22 | 11-JUL-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34524.74 | 01-AUG-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34650.80 | 13-SEP-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35129.17 | 11-OCT-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35109.45 | 07-NOV-05:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33422.08 | 26-DEC-06:12 | 2541.06 | 3356.58 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 33422.08 | 0.00 | 3356.58 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37133.35 | 4446.85 | 5874.01 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 37933.17 | 09-JAN-05:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 41267.43 | 06-FEB-06:03 | 4446.85 | 5874.01 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 37730.84 | 06-MAR-05:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37943.92 | 10-APR-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38091.34 | 09-MAY-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37944.22 | 26-JUN-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37904.96 | 17-JUL-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38177.13 | 21-AUG-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37482.79 | 06-SEP-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38233.70 | 02-OCT-04:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 38051.12 | 13-NOV-05:02 | 0.00 | 4195.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36526.89 | 26-DEC-06:12 | 2541.06 | 3356.58 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 36526.89 | 0.00 | 3356.58 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41267.43 | 4446.85 | 5874.01 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8515.75 | 02-JAN-06:12 | 535.68 | 707.60 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13471.73 | 26-FEB-15:12 | 401.76 | 253.14 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 305.86 | 0.00 |
March | 13693.36 | 19-MAR-15:22 | 401.76 | 253.14 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 552.85 | 0.00 |
April | 13843.44 | 16-APR-15:02 | 334.80 | 210.95 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 154.25 | 0.00 |
May | 14105.16 | 29-MAY-10:22 | 334.80 | 210.95 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 50.36 | 0.00 |
June | 14171.82 | 11-JUN-15:12 | 401.76 | 253.14 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 302.26 | 0.00 |
July | 13863.87 | 04-JUL-15:32 | 401.76 | 253.14 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 258.98 | 0.00 |
August | 13646.22 | 13-AUG-14:52 | 334.80 | 210.95 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 251.70 | 0.00 |
September | 13518.59 | 24-SEP-16:02 | 334.80 | 210.95 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 183.54 | 0.00 |
October | 13575.45 | 09-OCT-13:32 | 267.84 | 168.76 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 117.24 | 0.00 |
November | 9875.80 | 05-NOV-15:43 | 267.84 | 168.76 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 54.37 | 0.00 |
December | 13236.39 | 25-DEC-15:32 | 401.76 | 253.14 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 75.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8515.75 | 267.84 | 168.76 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14171.82 | 535.68 | 707.60 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 552.85 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8202.99 | 29-JAN-11:13 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 40.36 | 0.00 |
February | 9723.90 | 26-FEB-11:53 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 64.28 | 0.00 |
March | 12620.80 | 19-MAR-10:02 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 166.50 | 0.00 |
April | 13227.35 | 09-APR-08:42 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 28.82 | 0.00 |
May | 12921.02 | 14-MAY-10:52 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 126.76 | 0.00 |
June | 13133.59 | 18-JUN-08:42 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 90.50 | 0.00 |
July | 12247.85 | 30-JUL-10:32 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 106.20 | 0.00 |
August | 13023.87 | 27-AUG-10:42 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 89.96 | 0.00 |
September | 11934.53 | 03-SEP-12:13 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 122.33 | 0.00 |
October | 12267.13 | 08-OCT-08:32 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 | 0.00 |
November | 11673.48 | 05-NOV-09:43 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 22.99 | 0.00 |
December | 11829.92 | 31-DEC-10:13 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 63.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8202.99 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 | 0.00 | |
Maximum of Months | 13227.35 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 166.50 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14326.10 | 16-JAN-13:32 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 | 0.00 |
February | 14082.71 | 20-FEB-13:22 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 120.75 | 0.00 |
March | 13721.68 | 19-MAR-14:42 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 466.96 | 0.00 |
April | 13478.24 | 16-APR-15:02 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 155.14 | 0.00 |
May | 13386.29 | 07-MAY-14:32 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 409.69 | 0.00 |
June | 13369.38 | 11-JUN-15:12 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 321.85 | 0.00 |
July | 11796.32 | 04-JUL-15:32 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 275.30 | 0.00 |
August | 12603.38 | 27-AUG-15:22 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 251.93 | 0.00 |
September | 13397.81 | 03-SEP-12:13 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 183.29 | 0.00 |
October | 14070.46 | 29-OCT-10:53 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 251.38 | 0.00 |
November | 14166.39 | 11-NOV-11:32 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 58.54 | 0.00 |
December | 14845.25 | 25-DEC-15:32 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 43.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11796.32 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 43.28 | 0.00 | |
Maximum of Months | 14845.25 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 466.96 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13830.05 | 16-JAN-16:12 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 62.93 | 0.00 |
February | 14664.39 | 26-FEB-15:52 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 197.25 | 0.00 |
March | 15081.54 | 19-MAR-15:22 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 328.97 | 0.00 |
April | 14935.90 | 02-APR-15:32 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 172.59 | 0.00 |
May | 14627.83 | 14-MAY-15:32 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 87.34 | 0.00 |
June | 14716.95 | 11-JUN-15:52 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 164.93 | 0.00 |
July | 14668.12 | 04-JUL-16:12 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 129.04 | 0.00 |
August | 14618.25 | 27-AUG-16:02 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 150.74 | 0.00 |
September | 14882.02 | 10-SEP-17:22 | 0.00 | 133.54 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 | 0.00 |
October | 14712.19 | 15-OCT-16:02 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 33.37 | 0.00 |
November | 12514.91 | 19-NOV-15:12 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 72.49 | 0.00 |
December | 15300.55 | 25-DEC-15:32 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 34.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12514.91 | 0.00 | 133.54 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 | 0.00 | |
Maximum of Months | 15300.55 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 328.97 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7623.46 | 02-JAN-07:03 | 803.52 | 1111.06 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
February | 11589.88 | 20-FEB-15:51 | 468.72 | 295.33 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 177.54 | 0.00 |
March | 9359.09 | 20-MAR-04:02 | 0.00 | 884.49 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 26.61 | 0.00 |
April | 9582.68 | 18-APR-04:02 | 0.00 | 884.49 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 16.31 | 0.00 |
May | 11965.81 | 29-MAY-10:22 | 334.80 | 210.95 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 27.90 | 0.00 |
June | 11991.04 | 18-JUN-18:02 | 0.00 | 385.71 | 1930.52 | 0.00 | 0.00 | 0.00 | 0.00 | 72.29 | 0.00 |
July | 11827.17 | 04-JUL-15:32 | 401.76 | 253.14 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 145.20 | 0.00 |
August | 11692.15 | 13-AUG-14:41 | 468.72 | 295.33 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 135.01 | 0.00 |
September | 9998.82 | 05-SEP-04:02 | 0.00 | 884.49 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 5.98 | 0.00 |
October | 9598.97 | 02-OCT-04:02 | 0.00 | 884.49 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 |
November | 9130.98 | 24-NOV-05:02 | 0.00 | 884.49 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.06 |
December | 6708.48 | 11-DEC-13:05 | 5088.93 | 3037.79 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 17.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6708.48 | 0.00 | 210.95 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11991.04 | 5088.93 | 3037.79 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 177.54 | 6.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10678.12 | 16-JAN-11:22 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 11.37 | 0.00 |
February | 11507.97 | 20-FEB-09:12 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 9.61 | 0.00 |
March | 11564.02 | 05-MAR-09:52 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 29.30 | 0.00 |
April | 11664.01 | 09-APR-08:42 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 17.73 | 0.00 |
May | 11555.03 | 29-MAY-10:22 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 | 0.00 |
June | 11634.05 | 18-JUN-08:42 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 53.30 | 0.00 |
July | 10201.57 | 30-JUL-10:23 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 54.52 | 0.00 |
August | 11598.62 | 27-AUG-10:42 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 51.27 | 0.00 |
September | 11609.46 | 10-SEP-09:52 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 41.14 | 0.00 |
October | 11221.29 | 08-OCT-10:13 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 26.26 | 0.00 |
November | 9412.01 | 05-NOV-09:43 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 12.99 | 0.00 |
December | 10096.03 | 31-DEC-11:22 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 33.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9412.01 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 9.61 | 0.00 | |
Maximum of Months | 11664.01 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 54.52 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12737.89 | 16-JAN-12:02 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 13.92 | 0.00 |
February | 12501.33 | 20-FEB-13:52 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 68.77 | 0.00 |
March | 11953.26 | 21-MAR-12:00 | 687.71 | 759.45 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 9359.53 | 0.00 |
April | 11412.27 | 18-APR-12:00 | 687.71 | 759.45 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 9088.66 | 0.00 |
May | 12417.67 | 05-MAY-12:00 | 687.71 | 759.45 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 11100.11 | 0.00 |
June | 11804.62 | 16-JUN-12:00 | 687.71 | 759.45 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 9728.67 | 0.00 |
July | 10897.54 | 26-JUL-17:00 | 401.76 | 463.04 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 8639.19 | 0.00 |
August | 11430.87 | 15-AUG-12:00 | 687.71 | 759.45 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8730.08 | 0.00 |
September | 11276.29 | 05-SEP-12:00 | 687.71 | 759.45 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8124.92 | 0.00 |
October | 11881.94 | 29-OCT-10:53 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 141.30 | 0.00 |
November | 12342.76 | 23-NOV-12:42 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 32.71 | 0.00 |
December | 12677.90 | 31-DEC-13:22 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 43.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10897.54 | 267.84 | 168.76 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 13.92 | 0.00 | |
Maximum of Months | 12737.89 | 687.71 | 759.45 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 11100.11 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12885.97 | 16-JAN-17:22 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 7.28 | 0.00 |
February | 12998.37 | 20-FEB-15:51 | 296.72 | 186.96 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 92.72 | 0.00 |
March | 12642.83 | 05-MAR-15:12 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 63.58 | 0.00 |
April | 12446.86 | 02-APR-16:12 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 92.86 | 0.00 |
May | 12230.10 | 07-MAY-17:52 | 0.00 | 195.37 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.03 | 0.00 |
June | 12296.22 | 18-JUN-18:02 | 0.00 | 195.37 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.22 | 0.00 |
July | 12344.75 | 04-JUL-18:12 | 0.00 | 279.96 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 12271.87 | 27-AUG-16:02 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 84.70 | 0.00 |
September | 12529.52 | 10-SEP-17:12 | 0.00 | 133.54 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.34 | 0.00 |
October | 11312.77 | 15-OCT-16:53 | 169.55 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 0.00 |
November | 12084.53 | 11-NOV-14:42 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 44.02 | 0.00 |
December | 12386.49 | 24-DEC-16:42 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11312.77 | 0.00 | 106.83 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12998.37 | 296.72 | 279.96 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 92.86 | 0.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7869.80 | 09-JAN-05:02 | 0.00 | 884.49 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.91 |
February | 11845.52 | 20-FEB-15:51 | 468.72 | 295.33 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 263.96 | 0.00 |
March | 10437.97 | 19-MAR-15:22 | 401.76 | 253.14 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 472.62 | 0.00 |
April | 11580.95 | 16-APR-15:02 | 334.80 | 210.95 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 141.16 | 0.00 |
May | 12096.20 | 29-MAY-10:22 | 334.80 | 210.95 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 0.00 |
June | 12150.78 | 04-JUN-12:32 | 267.84 | 168.76 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 114.44 | 0.00 |
July | 11975.67 | 04-JUL-16:12 | 401.76 | 253.14 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 180.84 | 0.00 |
August | 10424.94 | 13-AUG-14:52 | 334.80 | 210.95 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 211.72 | 0.00 |
September | 9692.60 | 05-SEP-04:02 | 0.00 | 884.49 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 | 0.00 |
October | 9710.25 | 16-OCT-04:02 | 0.00 | 884.49 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 0.00 |
November | 9641.92 | 20-NOV-05:02 | 0.00 | 884.49 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 |
December | 8664.05 | 30-DEC-06:02 | 669.60 | 884.49 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7869.80 | 0.00 | 168.76 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12150.78 | 669.60 | 884.49 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 472.62 | 25.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11223.27 | 16-JAN-11:22 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 0.00 |
February | 12396.84 | 20-FEB-09:12 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 12.63 | 0.00 |
March | 12482.06 | 05-MAR-09:52 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 41.79 | 0.00 |
April | 12660.68 | 09-APR-08:42 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 24.96 | 0.00 |
May | 12416.11 | 14-MAY-08:42 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 31.06 | 0.00 |
June | 12525.19 | 18-JUN-08:42 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 78.58 | 0.00 |
July | 11077.88 | 30-JUL-09:53 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 66.85 | 0.00 |
August | 12406.38 | 27-AUG-10:42 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 78.63 | 0.00 |
September | 12459.86 | 10-SEP-09:52 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 62.69 | 0.00 |
October | 12328.94 | 08-OCT-09:02 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 0.00 |
November | 10853.79 | 05-NOV-09:43 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 19.64 | 0.00 |
December | 11176.79 | 31-DEC-10:02 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 56.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10853.79 | 169.56 | 106.84 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 12.63 | 0.00 | |
Maximum of Months | 12660.68 | 211.95 | 133.55 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 78.63 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13031.24 | 16-JAN-12:02 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 20.11 | 0.00 |
February | 12648.83 | 20-FEB-13:52 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 103.61 | 0.00 |
March | 11828.48 | 05-MAR-15:12 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 158.35 | 0.00 |
April | 11241.09 | 16-APR-15:02 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 142.58 | 0.00 |
May | 11345.33 | 07-MAY-15:12 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 323.17 | 0.00 |
June | 11182.10 | 11-JUN-15:12 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 275.00 | 0.00 |
July | 9876.75 | 17-JUL-04:02 | 0.00 | 884.49 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 |
August | 9652.32 | 28-AUG-04:02 | 0.00 | 884.49 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 11408.85 | 10-SEP-14:31 | 468.72 | 295.33 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 290.57 | 0.00 |
October | 12119.30 | 29-OCT-10:53 | 267.84 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 213.54 | 0.00 |
November | 12579.70 | 23-NOV-12:42 | 334.80 | 210.95 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 49.05 | 0.00 |
December | 12902.24 | 03-DEC-13:42 | 401.76 | 253.14 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 35.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9652.32 | 0.00 | 168.76 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13031.24 | 468.72 | 884.49 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 323.17 | 11.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13909.67 | 16-JAN-17:22 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 | 0.00 |
February | 14109.93 | 20-FEB-15:51 | 296.72 | 186.96 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 136.96 | 0.00 |
March | 13650.88 | 05-MAR-15:12 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 92.77 | 0.00 |
April | 13495.19 | 23-APR-15:42 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 119.75 | 0.00 |
May | 13301.87 | 14-MAY-15:21 | 339.11 | 213.67 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 71.90 | 0.00 |
June | 13179.22 | 11-JUN-16:32 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 121.94 | 0.00 |
July | 13294.60 | 04-JUL-16:12 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 111.18 | 0.00 |
August | 13230.46 | 27-AUG-16:02 | 254.33 | 160.25 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 129.18 | 0.00 |
September | 13463.54 | 10-SEP-17:12 | 0.00 | 133.54 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.82 | 0.00 |
October | 13272.90 | 15-OCT-16:02 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 30.24 | 0.00 |
November | 13102.06 | 11-NOV-14:42 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 65.68 | 0.00 |
December | 13399.22 | 24-DEC-16:32 | 211.94 | 133.54 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 27.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13102.06 | 0.00 | 133.54 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.82 | 0.00 | |
Maximum of Months | 14109.93 | 339.11 | 213.67 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 136.96 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.185648E+12 | 163443.79 | 04-JAN-13:00 | 0.963431E+10 | 9464.11 | 03-JAN-12:09 |
February | 0.173328E+12 | 171893.78 | 13-FEB-14:00 | 0.870220E+10 | 9458.64 | 13-FEB-12:20 |
March | 0.205360E+12 | 174625.77 | 20-MAR-15:09 | 0.982186E+10 | 9447.90 | 06-MAR-12:09 |
April | 0.199284E+12 | 174959.88 | 11-APR-15:00 | 0.918504E+10 | 9424.07 | 04-APR-11:20 |
May | 0.217454E+12 | 186841.10 | 04-MAY-12:00 | 0.954416E+10 | 9404.97 | 01-MAY-11:09 |
June | 0.217130E+12 | 191734.35 | 13-JUN-15:09 | 0.927276E+10 | 9380.97 | 14-JUN-11:09 |
July | 0.187982E+12 | 165392.95 | 17-JUL-12:00 | 0.926713E+10 | 9372.06 | 26-JUL-11:09 |
August | 0.208333E+12 | 175046.89 | 14-AUG-12:00 | 0.961450E+10 | 9380.47 | 16-AUG-11:09 |
September | 0.191680E+12 | 171371.78 | 05-SEP-12:00 | 0.912907E+10 | 9405.90 | 29-SEP-11:09 |
October | 0.191546E+12 | 167845.61 | 16-OCT-15:09 | 0.949899E+10 | 9425.82 | 27-OCT-11:09 |
November | 0.185646E+12 | 167510.72 | 13-NOV-13:00 | 0.931498E+10 | 9448.35 | 29-NOV-12:09 |
December | 0.180494E+12 | 162211.64 | 12-DEC-13:00 | 0.953068E+10 | 9456.43 | 27-DEC-12:09 |
Annual Sum or Average | 0.234389E+13 | 0.112516E+12 | ||||
Minimum of Months | 0.173328E+12 | 162211.64 | 0.870220E+10 | 9372.06 | ||
Maximum of Months | 0.217454E+12 | 191734.35 | 0.982186E+10 | 9464.11 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.304177E+11 | 0.100579E+11 | 0.593559E+11 | 0.143816E+10 | 0.102901E+11 | 12379742.02 | 0.00 | 0.740756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275238E+11 | 0.891472E+10 | 0.537310E+11 | 0.130154E+10 | 0.990350E+10 | 11196021.66 | 0.00 | 0.719422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.324678E+11 | 0.950605E+10 | 0.617796E+11 | 0.150688E+10 | 0.114798E+11 | 12675672.10 | 0.00 | 0.886069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.288950E+11 | 0.893585E+10 | 0.572952E+11 | 0.138492E+10 | 0.106339E+11 | 11960507.72 | 0.00 | 0.921275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.311938E+11 | 0.904184E+10 | 0.605677E+11 | 0.147232E+10 | 0.113389E+11 | 12527707.06 | 0.00 | 0.103827E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.309596E+11 | 0.862638E+10 | 0.594895E+11 | 0.144957E+10 | 0.120097E+11 | 12231776.97 | 0.00 | 0.104583E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.290695E+11 | 0.900058E+10 | 0.583622E+11 | 0.140745E+10 | 0.976710E+10 | 12256437.81 | 0.00 | 0.803631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.323371E+11 | 0.913984E+10 | 0.617796E+11 | 0.150679E+10 | 0.102882E+11 | 12675672.10 | 0.00 | 0.932690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.290334E+11 | 0.912154E+10 | 0.572729E+11 | 0.138468E+10 | 0.945007E+10 | 11960507.72 | 0.00 | 0.854057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.302077E+11 | 0.972268E+10 | 0.593671E+11 | 0.143813E+10 | 0.932162E+10 | 12379742.02 | 0.00 | 0.814761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.301256E+11 | 0.968728E+10 | 0.580818E+11 | 0.141184E+10 | 0.963015E+10 | 12059151.09 | 0.00 | 0.766971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295479E+11 | 0.101371E+11 | 0.583511E+11 | 0.140775E+10 | 0.944234E+10 | 12256437.81 | 0.00 | 0.715955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361779E+12 | 0.111892E+12 | 0.705434E+12 | 0.171100E+11 | 0.123555E+12 | 0.146559E+09 | 0.00 | 0.102397E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.275238E+11 | 0.862638E+10 | 0.537310E+11 | 0.130154E+10 | 0.932162E+10 | 11196021.66 | 0.00 | 0.715955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.324678E+11 | 0.101371E+11 | 0.617796E+11 | 0.150688E+10 | 0.120097E+11 | 12675672.10 | 0.00 | 0.104583E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.963431E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.870220E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.982186E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.918504E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.954416E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.927276E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.926713E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.961450E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.912907E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.949899E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.931498E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.953068E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.112516E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.870220E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.982186E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 34517.22 | 02-JAN-16:00 | 8596.48 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 1229.77 | 02-JAN-16:00 | 13883.91 | 17-JAN-15:09 | 6.85 | 01-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 31432.91 | 01-FEB-16:00 | 8596.48 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 1226.71 | 07-FEB-16:00 | 15695.72 | 21-FEB-15:09 | 6.85 | 26-FEB-15:50 | 0.00 | 01-FEB-00:10 |
March | 32359.33 | 01-MAR-16:00 | 8596.48 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 1227.66 | 28-MAR-07:19 | 15251.94 | 20-MAR-15:09 | 6.85 | 19-MAR-14:39 | 0.00 | 01-MAR-00:10 |
April | 30824.24 | 21-APR-07:10 | 8596.48 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 1227.66 | 21-APR-07:19 | 13991.53 | 11-APR-15:30 | 6.85 | 02-APR-14:50 | 0.00 | 01-APR-00:10 |
May | 31046.34 | 17-MAY-07:10 | 8596.48 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 1228.09 | 17-MAY-07:19 | 15545.41 | 05-MAY-15:20 | 6.85 | 01-MAY-12:09 | 0.00 | 01-MAY-00:10 |
June | 30972.31 | 20-JUN-07:10 | 8596.48 | 01-JUN-05:10 | 45864.70 | 01-JUN-07:10 | 1227.94 | 20-JUN-07:19 | 16274.66 | 12-JUN-15:20 | 6.85 | 11-JUN-15:50 | 0.00 | 01-JUN-00:10 |
July | 31046.34 | 11-JUL-07:10 | 8596.48 | 01-JUL-05:10 | 45864.70 | 03-JUL-07:10 | 1228.09 | 11-JUL-07:19 | 13061.35 | 14-JUL-15:39 | 6.85 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 30972.31 | 21-AUG-07:10 | 8596.48 | 01-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 1227.94 | 21-AUG-07:19 | 13459.54 | 14-AUG-14:30 | 6.85 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 30824.24 | 07-SEP-07:10 | 8596.48 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 1227.66 | 07-SEP-07:19 | 13386.29 | 05-SEP-12:00 | 6.85 | 04-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 31432.87 | 23-OCT-07:10 | 8596.48 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 1228.84 | 23-OCT-07:19 | 13733.27 | 10-OCT-14:20 | 6.85 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 35736.43 | 09-NOV-16:00 | 8596.48 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 1233.61 | 09-NOV-16:00 | 13724.31 | 13-NOV-13:30 | 6.85 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 36263.56 | 18-DEC-16:49 | 8596.48 | 01-DEC-17:30 | 45864.70 | 01-DEC-08:09 | 1236.27 | 18-DEC-16:00 | 13978.32 | 26-DEC-14:00 | 6.85 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 30824.24 | 8596.48 | 45864.70 | 1226.71 | 13061.35 | 6.85 | 0.00 | |||||||
Maximum of Months | 36263.56 | 8596.48 | 45864.70 | 1236.27 | 16274.66 | 6.85 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 76422.10 | 04-JAN-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 85633.14 | 13-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 85971.47 | 20-MAR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 87793.73 | 11-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 99380.67 | 04-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 102325.78 | 13-JUN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 78725.94 | 28-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88463.99 | 22-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84878.27 | 06-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 82675.78 | 16-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 80117.73 | 13-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 76054.98 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 76054.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 102325.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 163443.79 | 04-JAN-13:00 | 30098.83 | 42402.18 | 0.00 | 1224.43 | 13406.59 | 6.85 | 0.00 | 76304.91 | 0.00 |
February | 171893.78 | 13-FEB-14:00 | 30098.83 | 40588.47 | 0.00 | 1223.48 | 14343.00 | 6.85 | 0.00 | 85633.14 | 0.00 |
March | 174625.77 | 20-MAR-15:09 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 15251.94 | 6.85 | 0.00 | 85971.47 | 0.00 |
April | 174959.88 | 11-APR-15:00 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 13763.79 | 6.85 | 0.00 | 87793.73 | 0.00 |
May | 186841.10 | 04-MAY-12:00 | 30098.83 | 42402.18 | 0.00 | 1224.43 | 13728.14 | 6.85 | 0.00 | 99380.67 | 0.00 |
June | 191734.35 | 13-JUN-15:09 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 16006.21 | 6.85 | 0.00 | 102325.78 | 0.00 |
July | 165392.95 | 17-JUL-12:00 | 30098.83 | 42402.18 | 0.00 | 1224.43 | 12989.62 | 6.85 | 0.00 | 78671.04 | 0.00 |
August | 175046.89 | 14-AUG-12:00 | 30098.83 | 42402.18 | 0.00 | 1224.43 | 13176.15 | 6.85 | 0.00 | 88138.45 | 0.00 |
September | 171371.78 | 05-SEP-12:00 | 30098.83 | 42402.18 | 0.00 | 1224.43 | 13386.29 | 6.85 | 0.00 | 84253.20 | 0.00 |
October | 167845.61 | 16-OCT-15:09 | 30098.83 | 42072.41 | 0.00 | 1224.26 | 13066.40 | 6.85 | 0.00 | 81376.85 | 0.00 |
November | 167510.72 | 13-NOV-13:00 | 30098.83 | 42402.18 | 0.00 | 1224.43 | 13660.70 | 6.85 | 0.00 | 80117.73 | 0.00 |
December | 162211.64 | 12-DEC-13:00 | 30098.83 | 42402.18 | 0.00 | 1224.43 | 12424.37 | 6.85 | 0.00 | 76054.98 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 162211.64 | 30098.83 | 40588.47 | 0.00 | 1223.48 | 12424.37 | 6.85 | 0.00 | 76054.98 | 0.00 | |
Maximum of Months | 191734.35 | 30098.83 | 42402.18 | 0.00 | 1224.43 | 16006.21 | 6.85 | 0.00 | 102325.78 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 9464.11 | 03-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 9458.64 | 13-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 9447.90 | 06-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 9424.07 | 04-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 9404.97 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9380.97 | 14-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9372.06 | 26-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9380.47 | 16-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9405.90 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 9425.82 | 27-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 9448.35 | 29-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 9456.43 | 27-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9372.06 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9464.11 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.17 | 27.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.26 | 0.00 | 26.26 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 26.93 | 0.17 | 27.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.17 | 27.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.51 | 3.83 | 27.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.59 | 4.50 | 27.60 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.62 | 5.83 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.82 | 7.67 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.92 | 7.83 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.60 | 8.33 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.68 | 3.17 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.52 | 4.33 | 27.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.46 | 3.50 | 27.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.37 | 2.17 | 27.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.28 | 0.50 | 27.28 |
Annual Sum or Average | 0.00 | 0.00 | 57.33 | 27.66 | 51.67 | 27.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.92 | 8.33 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.42 | 2.83 | 27.42 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.65 | 9.00 | 27.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.97 | 8.67 | 27.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.97 | 11.00 | 27.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.01 | 9.67 | 28.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.90 | 8.33 | 27.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.61 | 8.00 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.94 | 5.17 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.81 | 9.00 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.71 | 7.00 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.52 | 6.67 | 27.52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.48 | 6.33 | 27.48 |
Annual Sum or Average | 0.00 | 0.00 | 94.50 | 27.79 | 91.67 | 27.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.42 | 2.83 | 27.42 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 28.01 | 11.00 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.07 | 10.00 | 28.09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.97 | 9.17 | 27.97 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.85 | 6.33 | 27.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.60 | 5.67 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.66 | 5.33 | 27.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.59 | 5.67 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.49 | 4.50 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.59 | 2.83 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.61 | 5.17 | 27.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.76 | 8.17 | 27.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.90 | 9.17 | 27.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.07 | 10.33 | 28.08 |
Annual Sum or Average | 0.00 | 0.00 | 86.50 | 27.82 | 82.33 | 27.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.49 | 2.83 | 27.49 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.07 | 10.33 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.13 | 5.50 | 28.14 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.03 | 5.83 | 28.03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.38 | 4.83 | 28.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.29 | 5.17 | 28.34 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.29 | 4.33 | 28.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.20 | 5.00 | 28.25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.83 | 4.50 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.15 | 3.33 | 28.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.08 | 3.67 | 28.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.87 | 4.33 | 27.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.83 | 4.17 | 27.83 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.11 | 5.33 | 28.11 |
Annual Sum or Average | 0.00 | 0.00 | 66.67 | 28.12 | 56.00 | 28.14 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.83 | 3.33 | 27.83 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.38 | 5.83 | 28.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.54 | 5.50 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.63 | 6.33 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.42 | 3.33 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.42 | 1.00 | 27.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 18.67 | 27.54 | 16.33 | 27.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.63 | 6.33 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.42 | 1.67 | 27.42 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.48 | 6.17 | 27.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.68 | 8.00 | 27.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.68 | 9.33 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.74 | 9.00 | 27.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.67 | 7.00 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.39 | 3.50 | 27.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.64 | 5.00 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.61 | 7.33 | 27.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.49 | 4.83 | 27.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.39 | 2.50 | 27.39 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.38 | 2.33 | 27.38 |
Annual Sum or Average | 0.00 | 0.00 | 67.17 | 27.60 | 66.67 | 27.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.38 | 1.67 | 27.38 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.74 | 9.33 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 98.17 | 25.43 | 98.00 | 25.43 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 91.83 | 25.50 | 91.50 | 25.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 54.17 | 25.66 | 54.17 | 25.66 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 37.83 | 25.50 | 37.83 | 25.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 41.33 | 25.61 | 41.33 | 25.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 39.83 | 25.70 | 39.83 | 25.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 25.09 | 28.00 | 25.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 | 25.36 | 28.50 | 25.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 25.41 | 28.33 | 25.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 | 25.49 | 32.67 | 25.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 52.50 | 25.60 | 52.50 | 25.60 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 80.50 | 25.54 | 80.50 | 25.54 |
Annual Sum or Average | 0.00 | 0.00 | 613.67 | 25.51 | 613.17 | 25.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 25.09 | 28.00 | 25.09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 98.17 | 25.70 | 98.00 | 25.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.87 | 4.67 | 27.87 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.86 | 4.17 | 27.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.98 | 4.17 | 28.02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.98 | 4.50 | 28.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.93 | 4.00 | 27.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.90 | 4.33 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.71 | 3.17 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.88 | 2.83 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.95 | 2.83 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.63 | 3.00 | 27.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.67 | 2.33 | 27.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.78 | 4.50 | 27.78 |
Annual Sum or Average | 0.00 | 0.00 | 52.83 | 27.87 | 44.50 | 27.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.63 | 2.33 | 27.64 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.98 | 4.67 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.29 | 0.67 | 27.29 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.39 | 1.67 | 27.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.43 | 1.83 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.64 | 6.33 | 27.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.72 | 6.83 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.47 | 4.17 | 27.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.45 | 2.17 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.31 | 0.83 | 27.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 26.50 | 27.57 | 24.50 | 27.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.72 | 6.83 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.55 | 1.17 | 27.55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.53 | 6.50 | 27.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.80 | 7.83 | 27.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.80 | 9.17 | 27.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.87 | 8.83 | 27.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.76 | 6.67 | 27.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.45 | 3.00 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.73 | 4.67 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.64 | 7.00 | 27.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.58 | 4.67 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.49 | 2.83 | 27.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.49 | 2.50 | 27.49 |
Annual Sum or Average | 0.00 | 0.00 | 65.00 | 27.69 | 64.83 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.45 | 1.17 | 27.45 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.87 | 9.17 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 26.29 | 18.83 | 26.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.36 | 10.00 | 27.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.63 | 5.67 | 27.64 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.42 | 1.50 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.46 | 3.33 | 27.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.48 | 2.17 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.37 | 2.33 | 27.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.59 | 6.33 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.75 | 8.17 | 27.75 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 26.08 | 23.50 | 26.08 |
Annual Sum or Average | 0.00 | 0.00 | 82.83 | 26.84 | 82.50 | 26.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.08 | 0.33 | 26.08 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 27.75 | 23.50 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.99 | 5.00 | 27.99 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.01 | 4.17 | 28.01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.19 | 4.17 | 28.23 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.15 | 4.50 | 28.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.12 | 3.83 | 28.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.11 | 4.00 | 28.13 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.80 | 2.83 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.98 | 2.83 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.15 | 2.50 | 28.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.73 | 3.17 | 27.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.74 | 2.67 | 27.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.89 | 4.83 | 27.89 |
Annual Sum or Average | 0.00 | 0.00 | 51.33 | 28.01 | 44.50 | 28.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.73 | 2.50 | 27.73 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.19 | 5.00 | 28.23 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 24.42 | 0.00 | 24.42 |
February | 0.00 | 0.00 | 454.00 | 24.38 | 0.00 | 24.38 |
March | 0.00 | 0.00 | 514.00 | 24.33 | 0.00 | 24.33 |
April | 0.00 | 0.00 | 485.00 | 24.34 | 0.00 | 24.34 |
May | 0.00 | 0.00 | 508.00 | 24.35 | 0.00 | 24.35 |
June | 0.00 | 0.00 | 496.00 | 24.34 | 0.00 | 24.34 |
July | 0.00 | 0.00 | 497.00 | 24.39 | 0.00 | 24.39 |
August | 0.00 | 0.00 | 513.83 | 24.36 | 0.00 | 24.36 |
September | 0.00 | 0.00 | 485.00 | 24.35 | 0.00 | 24.35 |
October | 0.00 | 0.00 | 502.00 | 24.41 | 0.00 | 24.41 |
November | 0.00 | 0.00 | 489.00 | 24.42 | 0.00 | 24.42 |
December | 0.00 | 0.00 | 496.83 | 24.39 | 0.00 | 24.39 |
Annual Sum or Average | 0.00 | 5942.67 | 24.37 | 0.00 | 24.37 | |
Minimum of Months | 0.00 | 0.00 | 454.00 | 24.33 | 0.00 | 24.33 |
Maximum of Months | 0.00 | 0.00 | 514.00 | 24.42 | 0.00 | 24.42 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 470.00 | 24.31 | 0.00 | 24.31 |
February | 0.00 | 0.00 | 429.00 | 24.28 | 0.00 | 24.28 |
March | 0.00 | 0.00 | 485.67 | 24.24 | 0.00 | 24.24 |
April | 0.00 | 0.00 | 458.00 | 24.25 | 0.00 | 24.25 |
May | 0.00 | 0.00 | 487.83 | 24.27 | 0.00 | 24.27 |
June | 0.00 | 0.00 | 483.17 | 24.26 | 0.00 | 24.26 |
July | 0.00 | 0.00 | 462.00 | 24.29 | 0.00 | 24.29 |
August | 0.50 | 23.23 | 472.67 | 24.26 | 0.00 | 24.26 |
September | 0.83 | 23.20 | 443.00 | 24.26 | 0.00 | 24.26 |
October | 0.00 | 0.00 | 458.50 | 24.31 | 0.00 | 24.31 |
November | 0.00 | 0.00 | 459.00 | 24.31 | 0.00 | 24.31 |
December | 0.00 | 0.00 | 444.33 | 24.28 | 0.00 | 24.28 |
Annual Sum or Average | 1.33 | 23.21 | 5553.17 | 24.28 | 0.00 | 24.28 |
Minimum of Months | 0.00 | 0.00 | 429.00 | 24.24 | 0.00 | 24.24 |
Maximum of Months | 0.83 | 23.23 | 487.83 | 24.31 | 0.00 | 24.31 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 23.37 | 430.00 | 24.32 | 0.00 | 24.32 |
February | 0.00 | 0.00 | 399.17 | 24.29 | 0.00 | 24.29 |
March | 1.00 | 23.34 | 475.33 | 24.26 | 0.00 | 24.26 |
April | 0.00 | 0.00 | 473.00 | 24.29 | 0.00 | 24.29 |
May | 0.00 | 0.00 | 487.17 | 24.30 | 0.00 | 24.30 |
June | 0.00 | 0.00 | 484.17 | 24.29 | 0.00 | 24.29 |
July | 0.00 | 0.00 | 456.67 | 24.32 | 0.00 | 24.32 |
August | 1.17 | 23.13 | 461.67 | 24.27 | 0.00 | 24.27 |
September | 1.83 | 23.14 | 440.83 | 24.28 | 0.00 | 24.28 |
October | 0.50 | 23.28 | 441.17 | 24.34 | 0.00 | 24.34 |
November | 0.00 | 0.00 | 429.50 | 24.32 | 0.00 | 24.32 |
December | 8.00 | 23.27 | 395.17 | 24.28 | 0.00 | 24.28 |
Annual Sum or Average | 16.00 | 23.27 | 5373.83 | 24.29 | 0.00 | 24.29 |
Minimum of Months | 0.00 | 0.00 | 395.17 | 24.26 | 0.00 | 24.26 |
Maximum of Months | 8.00 | 23.37 | 487.17 | 24.34 | 0.00 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.50 | 25.05 | 469.83 | 24.47 | 29.50 | 24.53 |
February | 38.33 | 26.07 | 434.50 | 24.56 | 38.33 | 24.68 |
March | 50.50 | 25.75 | 507.67 | 24.51 | 50.50 | 24.61 |
April | 61.67 | 25.98 | 485.00 | 24.66 | 61.67 | 24.80 |
May | 77.67 | 26.23 | 505.33 | 24.75 | 77.67 | 24.93 |
June | 70.67 | 26.30 | 495.00 | 24.73 | 70.67 | 24.90 |
July | 63.83 | 26.47 | 492.83 | 24.77 | 63.83 | 24.95 |
August | 67.50 | 25.70 | 509.00 | 24.54 | 67.50 | 24.66 |
September | 54.00 | 25.91 | 479.00 | 24.59 | 54.00 | 24.71 |
October | 66.33 | 26.03 | 482.00 | 24.67 | 66.33 | 24.82 |
November | 46.17 | 25.95 | 470.17 | 24.58 | 45.83 | 24.69 |
December | 46.83 | 24.99 | 441.50 | 24.47 | 34.83 | 24.55 |
Annual Sum or Average | 682.00 | 25.92 | 5771.83 | 24.61 | 660.67 | 24.74 |
Minimum of Months | 38.33 | 24.99 | 434.50 | 24.47 | 29.50 | 24.53 |
Maximum of Months | 77.67 | 26.47 | 509.00 | 24.77 | 77.67 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.33 | 26.12 | 472.00 | 24.62 | 44.67 | 24.75 |
February | 55.67 | 26.46 | 435.83 | 24.72 | 55.50 | 24.90 |
March | 58.50 | 26.25 | 502.67 | 24.61 | 58.17 | 24.77 |
April | 68.67 | 26.43 | 483.33 | 24.77 | 68.67 | 24.95 |
May | 72.00 | 26.34 | 495.50 | 24.74 | 70.83 | 24.92 |
June | 65.17 | 26.33 | 491.83 | 24.68 | 64.83 | 24.86 |
July | 64.17 | 26.46 | 473.83 | 24.76 | 64.17 | 24.94 |
August | 62.67 | 25.97 | 494.00 | 24.57 | 62.00 | 24.71 |
September | 62.67 | 26.33 | 464.67 | 24.70 | 61.83 | 24.88 |
October | 74.67 | 26.07 | 466.50 | 24.72 | 69.50 | 24.90 |
November | 61.33 | 26.09 | 456.33 | 24.68 | 56.83 | 24.84 |
December | 62.33 | 25.86 | 446.00 | 24.64 | 53.67 | 24.80 |
Annual Sum or Average | 754.17 | 26.23 | 5682.50 | 24.68 | 730.67 | 24.85 |
Minimum of Months | 46.33 | 25.86 | 435.83 | 24.57 | 44.67 | 24.71 |
Maximum of Months | 74.67 | 26.46 | 502.67 | 24.77 | 70.83 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 67.50 | 26.49 | 493.50 | 24.80 | 66.33 | 24.98 |
February | 55.00 | 26.53 | 451.67 | 24.74 | 55.00 | 24.91 |
March | 56.50 | 25.98 | 511.50 | 24.57 | 56.50 | 24.70 |
April | 61.00 | 25.94 | 485.00 | 24.65 | 61.00 | 24.78 |
May | 70.67 | 26.01 | 503.50 | 24.67 | 70.67 | 24.81 |
June | 67.33 | 26.02 | 494.67 | 24.64 | 67.33 | 24.78 |
July | 56.50 | 26.29 | 486.33 | 24.69 | 56.50 | 24.84 |
August | 66.67 | 25.59 | 508.50 | 24.51 | 66.67 | 24.62 |
September | 56.33 | 25.97 | 479.50 | 24.61 | 56.33 | 24.74 |
October | 74.50 | 26.28 | 489.00 | 24.76 | 74.50 | 24.94 |
November | 66.17 | 26.49 | 480.50 | 24.78 | 66.17 | 24.97 |
December | 71.33 | 26.50 | 477.50 | 24.81 | 70.17 | 25.01 |
Annual Sum or Average | 769.50 | 26.18 | 5861.17 | 24.68 | 767.17 | 24.84 |
Minimum of Months | 55.00 | 25.59 | 451.67 | 24.51 | 55.00 | 24.62 |
Maximum of Months | 74.50 | 26.53 | 511.50 | 24.81 | 74.50 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 67.50 | 24.84 | 427.17 | 24.49 | 41.83 | 24.61 |
February | 51.50 | 25.20 | 398.33 | 24.52 | 34.67 | 24.64 |
March | 49.17 | 25.70 | 473.67 | 24.51 | 43.83 | 24.63 |
April | 52.67 | 26.20 | 471.50 | 24.64 | 52.67 | 24.78 |
May | 61.50 | 25.92 | 482.50 | 24.61 | 57.50 | 24.76 |
June | 55.67 | 26.16 | 479.00 | 24.60 | 54.83 | 24.75 |
July | 56.67 | 25.67 | 441.33 | 24.63 | 45.50 | 24.77 |
August | 64.67 | 25.38 | 465.67 | 24.49 | 55.67 | 24.61 |
September | 47.83 | 25.65 | 439.33 | 24.53 | 42.00 | 24.65 |
October | 74.33 | 25.14 | 432.67 | 24.57 | 52.00 | 24.71 |
November | 61.00 | 25.17 | 420.83 | 24.53 | 43.50 | 24.65 |
December | 85.50 | 24.35 | 401.00 | 24.40 | 40.83 | 24.53 |
Annual Sum or Average | 728.00 | 25.38 | 5333.00 | 24.55 | 564.83 | 24.68 |
Minimum of Months | 47.83 | 24.35 | 398.33 | 24.40 | 34.67 | 24.53 |
Maximum of Months | 85.50 | 26.20 | 482.50 | 24.64 | 57.50 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.83 | 25.69 | 498.83 | 24.42 | 5.83 | 24.43 |
February | 6.50 | 25.94 | 454.00 | 24.45 | 6.50 | 24.47 |
March | 14.00 | 25.78 | 513.83 | 24.41 | 14.00 | 24.44 |
April | 19.67 | 26.09 | 485.00 | 24.53 | 19.67 | 24.59 |
May | 47.67 | 26.48 | 508.00 | 24.70 | 47.67 | 24.84 |
June | 47.50 | 26.57 | 496.00 | 24.71 | 47.50 | 24.86 |
July | 34.50 | 26.66 | 497.00 | 24.71 | 34.50 | 24.83 |
August | 38.67 | 26.19 | 514.00 | 24.55 | 38.67 | 24.66 |
September | 19.00 | 26.19 | 485.00 | 24.52 | 19.00 | 24.58 |
October | 20.17 | 26.19 | 502.00 | 24.54 | 20.17 | 24.60 |
November | 12.33 | 26.04 | 489.00 | 24.49 | 12.33 | 24.52 |
December | 8.83 | 25.72 | 491.33 | 24.41 | 8.83 | 24.43 |
Annual Sum or Average | 274.67 | 26.30 | 5934.00 | 24.54 | 274.67 | 24.61 |
Minimum of Months | 5.83 | 25.69 | 454.00 | 24.41 | 5.83 | 24.43 |
Maximum of Months | 47.67 | 26.66 | 514.00 | 24.71 | 47.67 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.50 | 26.74 | 501.83 | 24.58 | 15.50 | 24.64 |
February | 33.50 | 26.71 | 454.00 | 24.69 | 33.50 | 24.82 |
March | 42.83 | 26.69 | 514.00 | 24.64 | 42.83 | 24.79 |
April | 52.33 | 26.70 | 485.00 | 24.77 | 52.33 | 24.94 |
May | 54.17 | 26.65 | 508.00 | 24.75 | 54.17 | 24.92 |
June | 45.67 | 26.62 | 496.00 | 24.69 | 45.67 | 24.84 |
July | 37.00 | 26.67 | 497.00 | 24.70 | 37.00 | 24.83 |
August | 45.33 | 26.53 | 514.00 | 24.63 | 45.33 | 24.77 |
September | 48.50 | 26.67 | 485.00 | 24.72 | 48.50 | 24.89 |
October | 46.83 | 26.56 | 501.67 | 24.70 | 46.83 | 24.85 |
November | 28.33 | 26.64 | 488.67 | 24.65 | 28.33 | 24.75 |
December | 24.00 | 26.65 | 494.50 | 24.60 | 24.00 | 24.69 |
Annual Sum or Average | 474.00 | 26.65 | 5939.67 | 24.68 | 474.00 | 24.81 |
Minimum of Months | 15.50 | 26.53 | 454.00 | 24.58 | 15.50 | 24.64 |
Maximum of Months | 54.17 | 26.74 | 514.00 | 24.77 | 54.17 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 117.17 | 25.70 | 501.67 | 25.02 | 117.17 | 25.13 |
February | 103.67 | 25.71 | 454.00 | 25.01 | 103.67 | 25.12 |
March | 126.17 | 25.19 | 514.00 | 24.74 | 126.17 | 24.81 |
April | 131.00 | 24.82 | 485.00 | 24.64 | 131.00 | 24.67 |
May | 204.17 | 24.66 | 508.00 | 24.63 | 204.17 | 24.63 |
June | 192.50 | 24.71 | 496.00 | 24.62 | 192.50 | 24.64 |
July | 119.67 | 24.54 | 497.00 | 24.57 | 119.67 | 24.57 |
August | 230.83 | 24.50 | 514.00 | 24.49 | 230.83 | 24.49 |
September | 164.83 | 24.64 | 485.00 | 24.58 | 164.83 | 24.59 |
October | 187.00 | 24.94 | 502.00 | 24.72 | 187.00 | 24.77 |
November | 154.17 | 25.28 | 489.00 | 24.89 | 154.17 | 24.97 |
December | 130.83 | 25.60 | 496.33 | 24.98 | 130.83 | 25.09 |
Annual Sum or Average | 1862.00 | 24.95 | 5942.00 | 24.73 | 1862.00 | 24.78 |
Minimum of Months | 103.67 | 24.50 | 454.00 | 24.49 | 103.67 | 24.49 |
Maximum of Months | 230.83 | 25.71 | 514.00 | 25.02 | 230.83 | 25.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.17 | 26.64 | 498.00 | 24.58 | 26.17 | 24.68 |
February | 22.00 | 26.72 | 454.00 | 24.59 | 22.00 | 24.68 |
March | 30.50 | 26.60 | 514.00 | 24.57 | 30.50 | 24.68 |
April | 36.33 | 26.61 | 485.00 | 24.67 | 36.33 | 24.80 |
May | 38.17 | 26.58 | 507.67 | 24.65 | 38.17 | 24.78 |
June | 39.17 | 26.58 | 496.00 | 24.64 | 39.17 | 24.77 |
July | 25.50 | 26.66 | 497.00 | 24.64 | 25.50 | 24.73 |
August | 38.67 | 26.41 | 514.00 | 24.58 | 38.67 | 24.70 |
September | 26.83 | 26.59 | 485.00 | 24.59 | 26.83 | 24.69 |
October | 37.00 | 26.53 | 499.83 | 24.64 | 37.00 | 24.76 |
November | 24.00 | 26.55 | 488.17 | 24.58 | 24.00 | 24.67 |
December | 27.83 | 26.56 | 490.00 | 24.56 | 27.83 | 24.66 |
Annual Sum or Average | 372.17 | 26.58 | 5928.67 | 24.61 | 372.17 | 24.72 |
Minimum of Months | 22.00 | 26.41 | 454.00 | 24.56 | 22.00 | 24.66 |
Maximum of Months | 39.17 | 26.72 | 514.00 | 24.67 | 39.17 | 24.80 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.67 | 25.49 | 493.00 | 24.44 | 17.67 | 24.48 |
February | 22.00 | 25.94 | 453.33 | 24.50 | 22.00 | 24.56 |
March | 34.67 | 25.62 | 513.17 | 24.46 | 34.67 | 24.53 |
April | 43.00 | 25.87 | 485.00 | 24.59 | 43.00 | 24.69 |
May | 70.33 | 26.25 | 507.00 | 24.73 | 70.33 | 24.90 |
June | 62.33 | 26.30 | 496.00 | 24.70 | 62.33 | 24.86 |
July | 52.33 | 26.46 | 497.00 | 24.73 | 52.33 | 24.88 |
August | 59.33 | 25.81 | 513.67 | 24.54 | 59.33 | 24.66 |
September | 33.67 | 25.86 | 484.00 | 24.52 | 33.67 | 24.60 |
October | 43.83 | 25.99 | 497.67 | 24.59 | 43.83 | 24.70 |
November | 24.00 | 25.92 | 484.00 | 24.51 | 24.00 | 24.58 |
December | 20.50 | 25.23 | 479.17 | 24.41 | 19.00 | 24.45 |
Annual Sum or Average | 483.67 | 25.99 | 5903.00 | 24.57 | 482.17 | 24.67 |
Minimum of Months | 17.67 | 25.23 | 453.33 | 24.41 | 17.67 | 24.45 |
Maximum of Months | 70.33 | 26.46 | 513.67 | 24.73 | 70.33 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.50 | 26.30 | 416.17 | 24.64 | 26.33 | 24.74 |
February | 43.17 | 26.55 | 380.33 | 24.78 | 43.17 | 24.94 |
March | 48.67 | 26.42 | 427.67 | 24.70 | 48.67 | 24.86 |
April | 58.50 | 26.47 | 409.50 | 24.85 | 58.50 | 25.03 |
May | 65.50 | 26.40 | 422.67 | 24.84 | 65.50 | 25.02 |
June | 55.00 | 26.34 | 415.50 | 24.75 | 55.00 | 24.92 |
July | 49.00 | 26.44 | 408.00 | 24.79 | 49.00 | 24.95 |
August | 54.67 | 26.12 | 420.17 | 24.66 | 54.67 | 24.81 |
September | 51.33 | 26.47 | 395.83 | 24.78 | 51.33 | 24.96 |
October | 55.67 | 26.33 | 403.00 | 24.80 | 55.33 | 24.96 |
November | 38.50 | 26.37 | 395.17 | 24.74 | 38.00 | 24.87 |
December | 34.50 | 26.28 | 391.00 | 24.68 | 33.50 | 24.81 |
Annual Sum or Average | 581.00 | 26.38 | 4885.00 | 24.75 | 579.00 | 24.91 |
Minimum of Months | 26.50 | 26.12 | 380.33 | 24.64 | 26.33 | 24.74 |
Maximum of Months | 65.50 | 26.55 | 427.67 | 24.85 | 65.50 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 59.33 | 26.65 | 501.00 | 24.82 | 59.33 | 25.00 |
February | 50.83 | 26.61 | 454.00 | 24.76 | 50.83 | 24.93 |
March | 50.33 | 26.07 | 513.67 | 24.57 | 50.33 | 24.69 |
April | 41.67 | 25.81 | 485.00 | 24.57 | 41.67 | 24.66 |
May | 59.67 | 25.98 | 506.83 | 24.63 | 59.67 | 24.76 |
June | 52.17 | 25.92 | 495.50 | 24.58 | 52.17 | 24.69 |
July | 33.33 | 26.17 | 496.33 | 24.59 | 33.33 | 24.69 |
August | 56.50 | 25.64 | 513.17 | 24.50 | 56.50 | 24.60 |
September | 40.50 | 26.01 | 484.17 | 24.57 | 40.50 | 24.67 |
October | 67.00 | 26.35 | 499.67 | 24.75 | 67.00 | 24.92 |
November | 59.33 | 26.62 | 487.33 | 24.80 | 59.33 | 24.97 |
December | 63.50 | 26.65 | 493.67 | 24.83 | 63.50 | 25.02 |
Annual Sum or Average | 634.17 | 26.23 | 5930.33 | 24.66 | 634.17 | 24.80 |
Minimum of Months | 33.33 | 25.64 | 454.00 | 24.50 | 33.33 | 24.60 |
Maximum of Months | 67.00 | 26.65 | 513.67 | 24.83 | 67.00 | 25.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.00 | 25.83 | 466.50 | 24.54 | 36.17 | 24.65 |
February | 29.67 | 26.37 | 430.33 | 24.55 | 29.67 | 24.66 |
March | 37.33 | 26.18 | 502.67 | 24.51 | 37.33 | 24.61 |
April | 42.17 | 26.27 | 483.33 | 24.61 | 42.17 | 24.73 |
May | 51.00 | 26.09 | 495.33 | 24.60 | 50.33 | 24.73 |
June | 47.00 | 26.18 | 492.33 | 24.57 | 47.00 | 24.70 |
July | 33.50 | 26.38 | 469.50 | 24.60 | 33.50 | 24.71 |
August | 49.50 | 25.87 | 490.00 | 24.51 | 49.50 | 24.62 |
September | 32.33 | 26.13 | 460.17 | 24.52 | 32.33 | 24.62 |
October | 45.67 | 26.02 | 458.00 | 24.61 | 43.67 | 24.73 |
November | 35.17 | 26.09 | 450.83 | 24.56 | 34.00 | 24.66 |
December | 43.83 | 25.55 | 439.17 | 24.51 | 34.83 | 24.62 |
Annual Sum or Average | 489.17 | 26.06 | 5638.17 | 24.56 | 470.50 | 24.67 |
Minimum of Months | 29.67 | 25.55 | 430.33 | 24.51 | 29.67 | 24.61 |
Maximum of Months | 51.00 | 26.38 | 502.67 | 24.61 | 50.33 | 24.73 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.41921 | 46.83428 | 0.57448 | 12.17318 |
February | 454.00000 | 24.37677 | 47.12283 | 0.56886 | 12.00162 |
March | 514.00000 | 24.32863 | 47.34260 | 0.55889 | 11.74833 |
April | 485.00000 | 24.33911 | 47.49418 | 0.56039 | 11.79085 |
May | 508.00000 | 24.34934 | 47.43914 | -0.2813 | 7.06952 |
June | 496.00000 | 24.33933 | 47.38796 | -0.2786 | 7.04209 |
July | 497.00000 | 24.38947 | 47.29383 | -0.2742 | 7.04773 |
August | 514.00000 | 24.35948 | 47.55921 | -0.2819 | 7.15685 |
September | 485.00000 | 24.35368 | 47.62810 | -0.2837 | 7.10183 |
October | 502.00000 | 24.40559 | 47.45008 | 0.57132 | 12.10430 |
November | 489.00000 | 24.42317 | 47.24189 | 0.57628 | 12.22312 |
December | 497.00000 | 24.39465 | 47.10565 | 0.56747 | 11.97566 |
Annual Sum or Average | 5943.00000 | 24.37308 | 47.32621 | 0.21143 | 9.93306 |
Minimum of Months | 454.00000 | 24.32863 | 46.83428 | -0.2837 | 7.04209 |
Maximum of Months | 514.00000 | 24.42317 | 47.62810 | 0.57628 | 12.22312 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.26897 | 48.01609 | 0.53020 | 11.09075 |
February | 454.00000 | 24.24421 | 48.13790 | 0.52771 | 11.00227 |
March | 514.00000 | 24.20860 | 48.37240 | 0.52154 | 10.85379 |
April | 485.00000 | 24.22225 | 48.35623 | 0.52475 | 10.93529 |
May | 508.00000 | 24.24787 | 48.28615 | -0.3290 | 7.60613 |
June | 496.00000 | 24.24210 | 48.23707 | -0.3264 | 7.55740 |
July | 497.00000 | 24.24764 | 48.34802 | -0.3354 | 7.74968 |
August | 514.00000 | 24.21324 | 48.61708 | -0.3463 | 7.89009 |
September | 485.00000 | 24.20433 | 48.64588 | -0.3481 | 7.88757 |
October | 502.00000 | 24.25568 | 48.46304 | 0.52661 | 11.01826 |
November | 489.00000 | 24.26782 | 48.33007 | 0.52977 | 11.06998 |
December | 497.00000 | 24.21684 | 48.27083 | 0.51534 | 10.73431 |
Annual Sum or Average | 5943.00000 | 24.23654 | 48.34152 | 0.16243 | 9.60278 |
Minimum of Months | 454.00000 | 24.20433 | 48.01609 | -0.3481 | 7.55740 |
Maximum of Months | 514.00000 | 24.26897 | 48.64588 | 0.53020 | 11.09075 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.23255 | 47.57856 | 0.52704 | 11.03402 |
February | 454.00000 | 24.22306 | 47.69483 | 0.53081 | 11.09023 |
March | 514.00000 | 24.21814 | 48.01348 | 0.53543 | 11.18147 |
April | 485.00000 | 24.27050 | 48.16392 | 0.55091 | 11.54978 |
May | 508.00000 | 24.27308 | 48.17823 | -0.3007 | 7.30812 |
June | 496.00000 | 24.27584 | 48.12489 | -0.2941 | 7.20667 |
July | 497.00000 | 24.26826 | 48.11892 | -0.3139 | 7.48218 |
August | 514.00000 | 24.20607 | 48.57919 | -0.3336 | 7.71388 |
September | 485.00000 | 24.22343 | 48.53217 | -0.3246 | 7.61022 |
October | 502.00000 | 24.25303 | 48.42776 | 0.53461 | 11.23500 |
November | 489.00000 | 24.23602 | 48.23958 | 0.53096 | 11.11131 |
December | 497.00000 | 24.16545 | 48.02037 | 0.50875 | 10.62872 |
Annual Sum or Average | 5943.00000 | 24.23711 | 48.14231 | 0.17587 | 9.58109 |
Minimum of Months | 454.00000 | 24.16545 | 47.57856 | -0.3336 | 7.20667 |
Maximum of Months | 514.00000 | 24.27584 | 48.57919 | 0.55091 | 11.54978 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.36289 | 50.35143 | 0.59755 | 13.03265 |
February | 454.00000 | 24.39971 | 50.05647 | 0.61603 | 13.57040 |
March | 514.00000 | 24.37288 | 51.16119 | 0.62755 | 13.81319 |
April | 485.00000 | 24.49525 | 51.41561 | 0.67049 | 15.15205 |
May | 508.00000 | 24.52103 | 51.48208 | -0.1118 | 6.93167 |
June | 496.00000 | 24.50327 | 51.05176 | -0.0915 | 6.78828 |
July | 497.00000 | 24.54588 | 50.24595 | -0.1339 | 7.00328 |
August | 514.00000 | 24.38271 | 52.99843 | -0.1870 | 6.91317 |
September | 485.00000 | 24.42938 | 51.71084 | -0.1883 | 6.95967 |
October | 502.00000 | 24.44853 | 51.98387 | 0.63078 | 14.14556 |
November | 489.00000 | 24.41389 | 51.19400 | 0.61649 | 13.60948 |
December | 497.00000 | 24.31470 | 50.86705 | 0.58187 | 12.69605 |
Annual Sum or Average | 5943.00000 | 24.43245 | 51.22227 | 0.29926 | 10.85577 |
Minimum of Months | 454.00000 | 24.31470 | 50.05647 | -0.1883 | 6.78828 |
Maximum of Months | 514.00000 | 24.54588 | 52.99843 | 0.67049 | 15.15205 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.41701 | 49.57385 | 0.64819 | 14.52145 |
February | 454.00000 | 24.46005 | 49.23679 | 0.67480 | 15.39525 |
March | 514.00000 | 24.40321 | 50.24743 | 0.68190 | 15.57510 |
April | 485.00000 | 24.52679 | 50.51549 | 0.72216 | 16.90628 |
May | 508.00000 | 24.48378 | 51.11564 | -0.0959 | 7.12962 |
June | 496.00000 | 24.45857 | 50.92343 | -0.0909 | 6.80637 |
July | 497.00000 | 24.47989 | 50.23144 | -0.1359 | 7.07108 |
August | 514.00000 | 24.35439 | 52.45785 | -0.1555 | 7.05856 |
September | 485.00000 | 24.44089 | 51.01752 | -0.1356 | 7.22888 |
October | 502.00000 | 24.42831 | 51.41356 | 0.65687 | 15.06870 |
November | 489.00000 | 24.42261 | 50.57590 | 0.64988 | 14.71285 |
December | 497.00000 | 24.36517 | 50.05622 | 0.62855 | 14.14437 |
Annual Sum or Average | 5943.00000 | 24.43611 | 50.62806 | 0.33407 | 11.76500 |
Minimum of Months | 454.00000 | 24.35439 | 49.23679 | -0.1555 | 6.80637 |
Maximum of Months | 514.00000 | 24.52679 | 52.45785 | 0.72216 | 16.90628 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.54958 | 49.06244 | 0.70101 | 16.29875 |
February | 454.00000 | 24.51620 | 49.09738 | 0.69203 | 15.94942 |
March | 514.00000 | 24.41296 | 50.71641 | 0.65830 | 14.76593 |
April | 485.00000 | 24.48496 | 51.49614 | 0.66563 | 14.99878 |
May | 508.00000 | 24.47293 | 51.93955 | -0.1517 | 6.86743 |
June | 496.00000 | 24.44697 | 51.79246 | -0.1560 | 6.80113 |
July | 497.00000 | 24.48990 | 50.72066 | -0.1789 | 7.06950 |
August | 514.00000 | 24.35761 | 53.26335 | -0.2070 | 6.97046 |
September | 485.00000 | 24.44152 | 51.56873 | -0.1752 | 6.93852 |
October | 502.00000 | 24.51155 | 51.38076 | 0.66725 | 15.31809 |
November | 489.00000 | 24.53593 | 50.15223 | 0.68626 | 15.83817 |
December | 497.00000 | 24.52566 | 49.40856 | 0.69023 | 16.09559 |
Annual Sum or Average | 5943.00000 | 24.47808 | 50.90153 | 0.32074 | 11.95435 |
Minimum of Months | 454.00000 | 24.35761 | 49.06244 | -0.2070 | 6.80113 |
Maximum of Months | 514.00000 | 24.54958 | 53.26335 | 0.70101 | 16.29875 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.24765 | 49.98596 | 0.61233 | 13.82381 |
February | 454.00000 | 24.28642 | 49.69128 | 0.63549 | 14.39456 |
March | 514.00000 | 24.30704 | 50.54781 | 0.66014 | 15.03572 |
April | 485.00000 | 24.43072 | 50.83801 | 0.69680 | 16.13409 |
May | 508.00000 | 24.38278 | 51.36323 | -0.1338 | 7.22107 |
June | 496.00000 | 24.38315 | 51.18268 | -0.1220 | 7.06188 |
July | 497.00000 | 24.36282 | 50.50638 | -0.1755 | 7.41527 |
August | 514.00000 | 24.25829 | 52.72654 | -0.1914 | 7.40944 |
September | 485.00000 | 24.30386 | 51.38494 | -0.1834 | 7.39331 |
October | 502.00000 | 24.29815 | 51.68193 | 0.62682 | 14.27075 |
November | 489.00000 | 24.26828 | 50.91902 | 0.61640 | 13.85574 |
December | 497.00000 | 24.16776 | 50.54390 | 0.58692 | 13.24865 |
Annual Sum or Average | 5943.00000 | 24.30797 | 50.96059 | 0.29915 | 11.40882 |
Minimum of Months | 454.00000 | 24.16776 | 49.69128 | -0.1914 | 7.06188 |
Maximum of Months | 514.00000 | 24.43072 | 52.72654 | 0.69680 | 16.13409 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.39942 | 48.97512 | 0.59359 | 12.69006 |
February | 454.00000 | 24.42555 | 48.97164 | 0.60882 | 13.15938 |
March | 514.00000 | 24.37180 | 49.75068 | 0.60771 | 13.09994 |
April | 485.00000 | 24.46620 | 49.74625 | 0.64095 | 14.08816 |
May | 508.00000 | 24.53528 | 49.46346 | -0.1290 | 6.57822 |
June | 496.00000 | 24.52800 | 49.11837 | -0.1025 | 6.46030 |
July | 497.00000 | 24.57957 | 48.63195 | -0.1311 | 6.56170 |
August | 514.00000 | 24.43084 | 50.65660 | -0.1846 | 6.67288 |
September | 485.00000 | 24.45299 | 49.73716 | -0.1957 | 6.63756 |
October | 502.00000 | 24.46972 | 50.01562 | 0.62047 | 13.59094 |
November | 489.00000 | 24.44803 | 49.50705 | 0.61152 | 13.25366 |
December | 497.00000 | 24.38020 | 49.38638 | 0.58720 | 12.53605 |
Annual Sum or Average | 5943.00000 | 24.45731 | 49.50353 | 0.29087 | 10.41583 |
Minimum of Months | 454.00000 | 24.37180 | 48.63195 | -0.1957 | 6.46030 |
Maximum of Months | 514.00000 | 24.57957 | 50.65660 | 0.64095 | 14.08816 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.51064 | 48.32051 | 0.65902 | 14.60478 |
February | 454.00000 | 24.54002 | 48.23397 | 0.68275 | 15.40100 |
March | 514.00000 | 24.46971 | 48.90811 | 0.68063 | 15.34949 |
April | 485.00000 | 24.56188 | 48.96340 | 0.70980 | 16.32081 |
May | 508.00000 | 24.54509 | 49.25329 | -0.0974 | 6.66376 |
June | 496.00000 | 24.50857 | 49.14437 | -0.0940 | 6.42275 |
July | 497.00000 | 24.55739 | 48.69606 | -0.1210 | 6.49921 |
August | 514.00000 | 24.46019 | 50.28070 | -0.1343 | 6.59641 |
September | 485.00000 | 24.53030 | 49.17158 | -0.1212 | 6.66888 |
October | 502.00000 | 24.52974 | 49.53759 | 0.66534 | 14.99800 |
November | 489.00000 | 24.53211 | 48.98269 | 0.66295 | 14.82602 |
December | 497.00000 | 24.49690 | 48.71826 | 0.65020 | 14.42445 |
Annual Sum or Average | 5943.00000 | 24.51968 | 49.02663 | 0.34195 | 11.52662 |
Minimum of Months | 454.00000 | 24.46019 | 48.23397 | -0.1343 | 6.42275 |
Maximum of Months | 514.00000 | 24.56188 | 50.28070 | 0.70980 | 16.32081 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.86402 | 52.70684 | 0.79782 | 19.22262 |
February | 454.00000 | 24.85444 | 52.82079 | 0.79110 | 18.97696 |
March | 514.00000 | 24.62492 | 55.54639 | 0.73051 | 16.82191 |
April | 485.00000 | 24.59197 | 57.80416 | 0.72124 | 16.46112 |
May | 508.00000 | 24.61130 | 60.64600 | -0.0595 | 6.11820 |
June | 496.00000 | 24.59279 | 60.64468 | -0.0596 | 6.13302 |
July | 497.00000 | 24.57623 | 57.39911 | -0.1051 | 6.10276 |
August | 514.00000 | 24.48923 | 62.57341 | -0.0998 | 6.12378 |
September | 485.00000 | 24.56275 | 59.60859 | -0.0833 | 6.09654 |
October | 502.00000 | 24.64518 | 59.26003 | 0.75239 | 17.58307 |
November | 489.00000 | 24.76479 | 56.47490 | 0.78355 | 18.67780 |
December | 497.00000 | 24.81751 | 53.23119 | 0.78680 | 18.91594 |
Annual Sum or Average | 5943.00000 | 24.66456 | 57.43466 | 0.40942 | 13.04801 |
Minimum of Months | 454.00000 | 24.48923 | 52.70684 | -0.1051 | 6.09654 |
Maximum of Months | 514.00000 | 24.86402 | 62.57341 | 0.79782 | 19.22262 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.46681 | 48.48691 | 0.64745 | 14.34227 |
February | 454.00000 | 24.48322 | 48.45418 | 0.66640 | 14.90405 |
March | 514.00000 | 24.44776 | 49.06638 | 0.67401 | 15.13852 |
April | 485.00000 | 24.52821 | 49.16624 | 0.69772 | 15.90729 |
May | 508.00000 | 24.50719 | 49.42840 | -0.1165 | 6.57099 |
June | 496.00000 | 24.48825 | 49.30404 | -0.1079 | 6.48487 |
July | 497.00000 | 24.53506 | 48.81394 | -0.1332 | 6.54964 |
August | 514.00000 | 24.44174 | 50.44590 | -0.1475 | 6.62576 |
September | 485.00000 | 24.48207 | 49.39815 | -0.1437 | 6.57730 |
October | 502.00000 | 24.49789 | 49.66563 | 0.65562 | 14.68680 |
November | 489.00000 | 24.48339 | 49.14322 | 0.65009 | 14.43445 |
December | 497.00000 | 24.43475 | 48.93345 | 0.63499 | 14.00917 |
Annual Sum or Average | 5943.00000 | 24.48276 | 49.20070 | 0.32822 | 11.31779 |
Minimum of Months | 454.00000 | 24.43475 | 48.45418 | -0.1475 | 6.48487 |
Maximum of Months | 514.00000 | 24.53506 | 50.44590 | 0.69772 | 15.90729 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.39078 | 50.23139 | 0.59503 | 12.82568 |
February | 454.00000 | 24.42820 | 50.05155 | 0.61136 | 13.33502 |
March | 514.00000 | 24.37721 | 50.96447 | 0.61310 | 13.33405 |
April | 485.00000 | 24.47554 | 51.11218 | 0.64711 | 14.37950 |
May | 508.00000 | 24.52259 | 51.09593 | -0.1356 | 6.85155 |
June | 496.00000 | 24.50200 | 50.65071 | -0.1183 | 6.70021 |
July | 497.00000 | 24.54742 | 50.03856 | -0.1525 | 6.85496 |
August | 514.00000 | 24.39752 | 52.43392 | -0.2016 | 6.90470 |
September | 485.00000 | 24.42848 | 51.27142 | -0.2098 | 6.88621 |
October | 502.00000 | 24.46187 | 51.52495 | 0.62142 | 13.74956 |
November | 489.00000 | 24.43760 | 50.82007 | 0.61039 | 13.33391 |
December | 497.00000 | 24.35563 | 50.67019 | 0.58299 | 12.52868 |
Annual Sum or Average | 5943.00000 | 24.44361 | 50.91547 | 0.28549 | 10.61237 |
Minimum of Months | 454.00000 | 24.35563 | 50.03856 | -0.2098 | 6.70021 |
Maximum of Months | 514.00000 | 24.54742 | 52.43392 | 0.64711 | 14.37950 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 24.51240 | 49.55604 | 0.64683 | 14.45482 |
February | 385.00000 | 24.56680 | 49.27338 | 0.67295 | 15.34685 |
March | 433.00000 | 24.49123 | 50.24072 | 0.67018 | 15.27388 |
April | 410.00000 | 24.61352 | 50.41708 | 0.70682 | 16.47994 |
May | 430.00000 | 24.57584 | 50.93827 | -0.1117 | 7.25207 |
June | 418.00000 | 24.53898 | 50.79262 | -0.1131 | 6.92183 |
July | 422.00000 | 24.56328 | 50.13293 | -0.1487 | 7.07329 |
August | 433.00000 | 24.44356 | 52.29554 | -0.1676 | 7.22479 |
September | 410.00000 | 24.52929 | 50.71253 | -0.1503 | 7.31085 |
October | 427.00000 | 24.52379 | 51.16580 | 0.65286 | 14.92833 |
November | 417.00000 | 24.52232 | 50.32663 | 0.64804 | 14.64369 |
December | 422.00000 | 24.47067 | 49.97848 | 0.63146 | 14.15922 |
Annual Sum or Average | 5034.00000 | 24.52861 | 50.49817 | 0.32549 | 11.72617 |
Minimum of Months | 385.00000 | 24.44356 | 49.27338 | -0.1676 | 6.92183 |
Maximum of Months | 433.00000 | 24.61352 | 52.29554 | 0.70682 | 16.47994 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.60437 | 48.85891 | 0.70190 | 16.21231 |
February | 454.00000 | 24.55682 | 49.02229 | 0.68825 | 15.73948 |
March | 514.00000 | 24.42468 | 50.49318 | 0.64471 | 14.30791 |
April | 485.00000 | 24.46553 | 51.19518 | 0.64251 | 14.23739 |
May | 508.00000 | 24.47020 | 51.57830 | -0.1758 | 6.82160 |
June | 496.00000 | 24.43551 | 51.41859 | -0.1840 | 6.76813 |
July | 497.00000 | 24.48630 | 50.52004 | -0.1981 | 6.92168 |
August | 514.00000 | 24.37132 | 52.69902 | -0.2215 | 6.96079 |
September | 485.00000 | 24.44507 | 51.12523 | -0.1957 | 6.85567 |
October | 502.00000 | 24.53133 | 50.91121 | 0.65860 | 14.94363 |
November | 489.00000 | 24.57032 | 49.74858 | 0.68089 | 15.59490 |
December | 497.00000 | 24.59521 | 49.12383 | 0.69489 | 16.08765 |
Annual Sum or Average | 5943.00000 | 24.49554 | 50.57418 | 0.30775 | 11.75032 |
Minimum of Months | 454.00000 | 24.37132 | 48.85891 | -0.2215 | 6.76813 |
Maximum of Months | 514.00000 | 24.60437 | 52.69902 | 0.70190 | 16.21231 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.34755 | 49.84233 | 0.62337 | 13.86097 |
February | 454.00000 | 24.37776 | 49.65165 | 0.64255 | 14.36391 |
March | 514.00000 | 24.36119 | 50.36286 | 0.65526 | 14.71285 |
April | 485.00000 | 24.45639 | 50.54476 | 0.68264 | 15.55287 |
May | 508.00000 | 24.42331 | 51.02451 | -0.1459 | 6.94774 |
June | 496.00000 | 24.41197 | 50.82200 | -0.1390 | 6.81400 |
July | 497.00000 | 24.41619 | 50.28881 | -0.1792 | 7.03003 |
August | 514.00000 | 24.32492 | 52.19078 | -0.1914 | 7.11423 |
September | 485.00000 | 24.35980 | 50.92680 | -0.1897 | 7.07986 |
October | 502.00000 | 24.37667 | 51.21249 | 0.63035 | 14.13834 |
November | 489.00000 | 24.36093 | 50.51220 | 0.62344 | 13.84429 |
December | 497.00000 | 24.28665 | 50.31581 | 0.60288 | 13.34083 |
Annual Sum or Average | 5943.00000 | 24.37502 | 50.65232 | 0.29800 | 11.20246 |
Minimum of Months | 454.00000 | 24.28665 | 49.65165 | -0.1914 | 6.81400 |
Maximum of Months | 514.00000 | 24.45639 | 52.19078 | 0.68264 | 15.55287 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.104698E+12 | 0.266928E+11 | 451.08 | 0.723176E+11 | 0.323809E+11 | 0.00 | 1.00 | 01-JAN-00:42 | 0.00 | 01-JAN-00:10 | 138319.43 | 09-JAN-05:02 | 85150.46 | 09-JAN-05:02 | 53168.97 | 09-JAN-05:02 | 31654.92 | 09-JAN-05:02 | 0.00 |
February | 0.989879E+11 | 0.256266E+11 | 412.92 | 0.684832E+11 | 0.305047E+11 | 0.00 | 1.00 | 01-FEB-06:12 | 0.00 | 01-FEB-00:10 | 145422.62 | 06-FEB-06:03 | 91211.19 | 21-FEB-05:02 | 62065.27 | 06-FEB-06:03 | 33216.39 | 06-FEB-06:03 | 0.00 |
March | 0.120427E+12 | 0.315169E+11 | 480.36 | 0.810233E+11 | 0.394038E+11 | 0.00 | 1.00 | 01-MAR-05:02 | 0.00 | 01-MAR-00:10 | 145175.80 | 29-MAR-04:02 | 92708.37 | 20-MAR-04:02 | 59729.35 | 29-MAR-04:02 | 34860.37 | 28-MAR-04:02 | 0.00 |
April | 0.125316E+12 | 0.325789E+11 | 462.11 | 0.771282E+11 | 0.481882E+11 | 0.00 | 1.00 | 01-APR-04:02 | 0.00 | 01-APR-00:10 | 147038.29 | 01-APR-04:02 | 91091.41 | 18-APR-04:02 | 67553.99 | 01-APR-04:02 | 34986.45 | 01-APR-04:02 | 0.00 |
May | 0.143372E+12 | 0.369463E+11 | 488.68 | 0.821606E+11 | 0.612118E+11 | 0.00 | 1.00 | 01-MAY-00:42 | 0.00 | 01-MAY-00:03 | 149889.62 | 06-MAY-04:02 | 92383.59 | 08-MAY-04:02 | 74375.94 | 13-MAY-04:02 | 35719.57 | 06-MAY-04:02 | 0.00 |
June | 0.144020E+12 | 0.372877E+11 | 472.16 | 0.832739E+11 | 0.607462E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 151571.91 | 10-JUN-04:02 | 91206.51 | 05-JUN-04:02 | 75909.81 | 10-JUN-04:02 | 35594.92 | 16-JUN-12:13 | 0.00 |
July | 0.115309E+12 | 0.288974E+11 | 460.55 | 0.718530E+11 | 0.434557E+11 | 0.00 | 1.00 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 | 137044.72 | 10-JUL-04:02 | 91561.94 | 24-JUL-04:02 | 50778.46 | 21-JUL-04:02 | 32254.77 | 10-JUL-04:02 | 0.00 |
August | 0.134793E+12 | 0.337055E+11 | 473.69 | 0.761291E+11 | 0.586636E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 151283.73 | 21-AUG-04:02 | 91481.31 | 14-AUG-04:02 | 75721.19 | 21-AUG-04:02 | 36019.68 | 02-AUG-04:02 | 0.00 |
September | 0.122647E+12 | 0.306917E+11 | 451.28 | 0.705819E+11 | 0.520654E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 145440.36 | 25-SEP-04:02 | 91295.77 | 11-SEP-04:02 | 58581.34 | 25-SEP-04:02 | 34220.86 | 25-SEP-04:02 | 0.00 |
October | 0.118931E+12 | 0.293750E+11 | 451.55 | 0.691031E+11 | 0.498278E+11 | 0.00 | 1.00 | 01-OCT-06:12 | 0.00 | 01-OCT-00:10 | 145746.75 | 30-OCT-04:02 | 91432.32 | 16-OCT-04:02 | 58880.21 | 30-OCT-04:02 | 33674.48 | 30-OCT-04:02 | 0.00 |
November | 0.111341E+12 | 0.277583E+11 | 435.30 | 0.689769E+11 | 0.423639E+11 | 0.00 | 1.00 | 01-NOV-04:03 | 0.00 | 01-NOV-00:10 | 128954.51 | 14-NOV-05:02 | 89879.77 | 24-NOV-05:02 | 47720.19 | 04-NOV-04:02 | 30693.06 | 14-NOV-05:02 | 0.00 |
December | 0.102575E+12 | 0.257774E+11 | 439.58 | 0.682174E+11 | 0.343572E+11 | 0.00 | 1.00 | 01-DEC-06:13 | 0.00 | 01-DEC-00:10 | 124531.88 | 11-DEC-06:12 | 85595.94 | 26-DEC-07:03 | 47148.51 | 11-DEC-06:12 | 28474.77 | 11-DEC-06:12 | 0.00 |
Annual Sum or Average | 0.144242E+13 | 0.366855E+12 | 5479.26 | 0.889248E+12 | 0.553169E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.989879E+11 | 0.256266E+11 | 412.92 | 0.682174E+11 | 0.305047E+11 | 0.00 | 1.00 | 0.00 | 124531.88 | 85150.46 | 47148.51 | 28474.77 | 0.00 | ||||||
Maximum of Months | 0.144020E+12 | 0.372877E+11 | 488.68 | 0.832739E+11 | 0.612118E+11 | 0.00 | 1.00 | 0.00 | 151571.91 | 92708.37 | 75909.81 | 36019.68 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.905560E+11 | 0.229885E+11 | 440.04 | 0.609450E+11 | 0.296110E+11 | 0.00 | 1.00 | 01-JAN-06:22 | 0.00 | 01-JAN-00:10 | 128471.78 | 09-JAN-05:02 | 70754.56 | 09-JAN-05:02 | 57717.23 | 09-JAN-05:02 | 29213.46 | 09-JAN-05:02 | 0.00 |
February | 0.868299E+11 | 0.223693E+11 | 405.97 | 0.583719E+11 | 0.284580E+11 | 0.00 | 1.00 | 01-FEB-06:12 | 0.00 | 01-FEB-00:10 | 130311.21 | 06-FEB-06:03 | 80091.66 | 21-FEB-05:02 | 61809.16 | 06-FEB-06:03 | 29583.26 | 06-FEB-06:03 | 0.00 |
March | 0.105738E+12 | 0.274933E+11 | 472.96 | 0.690184E+11 | 0.367192E+11 | 0.00 | 1.00 | 01-MAR-05:02 | 0.00 | 01-MAR-00:10 | 130223.02 | 13-MAR-04:02 | 77030.83 | 20-MAR-04:02 | 59816.99 | 29-MAR-04:02 | 30916.75 | 28-MAR-04:02 | 0.00 |
April | 0.111172E+12 | 0.286539E+11 | 451.69 | 0.658830E+11 | 0.452890E+11 | 0.00 | 1.00 | 01-APR-04:02 | 0.00 | 01-APR-00:10 | 130841.18 | 06-APR-04:02 | 77254.56 | 28-APR-05:02 | 61052.49 | 06-APR-04:02 | 30873.54 | 12-APR-04:02 | 0.00 |
May | 0.126678E+12 | 0.323818E+11 | 477.05 | 0.696162E+11 | 0.570620E+11 | 0.00 | 1.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:33 | 133904.25 | 20-MAY-04:02 | 77622.34 | 15-MAY-04:02 | 79409.00 | 22-MAY-04:04 | 32339.31 | 14-MAY-15:21 | 0.00 |
June | 0.127058E+12 | 0.325915E+11 | 462.23 | 0.703284E+11 | 0.567297E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 133766.58 | 10-JUN-05:02 | 76516.32 | 03-JUN-05:02 | 73170.09 | 10-JUN-04:02 | 34283.27 | 11-JUN-15:12 | 0.00 |
July | 0.100060E+12 | 0.248813E+11 | 449.58 | 0.596015E+11 | 0.404584E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 127906.85 | 10-JUL-04:02 | 79252.64 | 03-JUL-04:02 | 50843.24 | 10-JUL-04:02 | 29872.84 | 10-JUL-04:02 | 0.00 |
August | 0.117105E+12 | 0.290207E+11 | 462.79 | 0.626885E+11 | 0.544162E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 134833.24 | 21-AUG-05:03 | 79292.69 | 28-AUG-04:02 | 79704.09 | 21-AUG-04:02 | 31897.23 | 02-AUG-04:02 | 0.00 |
September | 0.107189E+12 | 0.265865E+11 | 441.14 | 0.586713E+11 | 0.485182E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 130694.36 | 25-SEP-04:02 | 80892.70 | 05-SEP-04:02 | 58703.89 | 25-SEP-04:02 | 30511.06 | 08-SEP-05:02 | 0.00 |
October | 0.103685E+12 | 0.254228E+11 | 441.16 | 0.575572E+11 | 0.461275E+11 | 0.00 | 1.00 | 01-OCT-06:20 | 0.00 | 01-OCT-00:10 | 132340.83 | 30-OCT-04:02 | 78723.32 | 16-OCT-04:02 | 62878.01 | 30-OCT-04:02 | 30244.66 | 05-OCT-05:02 | 0.00 |
November | 0.963209E+11 | 0.238666E+11 | 425.47 | 0.574162E+11 | 0.389047E+11 | 0.00 | 1.00 | 01-NOV-04:03 | 0.00 | 01-NOV-00:10 | 129054.44 | 13-NOV-05:02 | 76273.79 | 20-NOV-05:02 | 53197.27 | 13-NOV-05:02 | 29829.97 | 13-NOV-05:02 | 0.00 |
December | 0.889845E+11 | 0.222584E+11 | 431.39 | 0.571280E+11 | 0.318565E+11 | 0.00 | 1.00 | 01-DEC-06:13 | 0.00 | 01-DEC-00:10 | 121899.73 | 30-DEC-06:02 | 70895.59 | 30-DEC-06:02 | 51004.14 | 30-DEC-06:02 | 27926.37 | 30-DEC-06:02 | 0.00 |
Annual Sum or Average | 0.126138E+13 | 0.318515E+12 | 5361.47 | 0.747226E+12 | 0.514150E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.868299E+11 | 0.222584E+11 | 405.97 | 0.571280E+11 | 0.284580E+11 | 0.00 | 1.00 | 0.00 | 121899.73 | 70754.56 | 50843.24 | 27926.37 | 0.00 | ||||||
Maximum of Months | 0.127058E+12 | 0.325915E+11 | 477.05 | 0.703284E+11 | 0.570620E+11 | 0.00 | 1.00 | 0.00 | 134833.24 | 80892.70 | 79704.09 | 34283.27 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.954523E+11 | 0.243944E+11 | 437.65 | 0.655553E+11 | 0.298970E+11 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:10 | 124589.49 | 09-JAN-05:02 | 75575.37 | 05-JAN-15:00 | 59214.40 | 09-JAN-05:02 | 28342.48 | 09-JAN-05:02 | 0.00 |
February | 0.923493E+11 | 0.239463E+11 | 405.68 | 0.635619E+11 | 0.287874E+11 | 0.00 | 1.00 | 01-FEB-08:50 | 0.00 | 01-FEB-00:10 | 149005.23 | 06-FEB-06:01 | 88897.91 | 26-FEB-15:12 | 66826.64 | 06-FEB-06:01 | 33965.94 | 06-FEB-06:01 | 0.00 |
March | 0.113193E+12 | 0.295967E+11 | 472.09 | 0.761873E+11 | 0.370057E+11 | 0.00 | 1.00 | 01-MAR-05:02 | 0.00 | 01-MAR-00:10 | 150573.01 | 28-MAR-04:02 | 93361.36 | 19-MAR-14:42 | 73043.47 | 28-MAR-04:02 | 35703.32 | 28-MAR-04:02 | 0.00 |
April | 0.119384E+12 | 0.308946E+11 | 455.40 | 0.735427E+11 | 0.458415E+11 | 0.00 | 1.00 | 01-APR-04:02 | 0.00 | 01-APR-00:10 | 151381.49 | 12-APR-04:02 | 90991.34 | 02-APR-14:52 | 73602.30 | 06-APR-04:02 | 37223.80 | 02-APR-14:52 | 0.00 |
May | 0.134351E+12 | 0.344987E+11 | 479.91 | 0.767651E+11 | 0.575854E+11 | 0.00 | 1.00 | 01-MAY-00:22 | 0.00 | 01-MAY-00:03 | 154844.20 | 24-MAY-04:02 | 90661.22 | 07-MAY-14:32 | 89105.37 | 22-MAY-04:02 | 37595.58 | 07-MAY-15:52 | 0.00 |
June | 0.134690E+12 | 0.347040E+11 | 463.42 | 0.776942E+11 | 0.569958E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 154569.43 | 10-JUN-05:02 | 90961.82 | 11-JUN-15:12 | 87392.78 | 10-JUN-04:02 | 40022.64 | 11-JUN-15:12 | 0.00 |
July | 0.106416E+12 | 0.265845E+11 | 454.07 | 0.653183E+11 | 0.410980E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 143950.64 | 10-JUL-04:02 | 87824.07 | 31-JUL-04:02 | 58670.99 | 10-JUL-04:02 | 33678.25 | 10-JUL-04:02 | 0.00 |
August | 0.122806E+12 | 0.305428E+11 | 461.92 | 0.681502E+11 | 0.546555E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 152502.54 | 11-AUG-05:02 | 84833.42 | 14-AUG-04:02 | 88443.75 | 21-AUG-04:02 | 37881.82 | 13-AUG-14:52 | 0.00 |
September | 0.112936E+12 | 0.281275E+11 | 441.04 | 0.641940E+11 | 0.487417E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 150759.44 | 25-SEP-04:02 | 92148.28 | 05-SEP-04:02 | 74718.13 | 02-SEP-05:02 | 35135.11 | 25-SEP-04:02 | 0.00 |
October | 0.108420E+12 | 0.266783E+11 | 442.58 | 0.619013E+11 | 0.465184E+11 | 0.00 | 1.00 | 01-OCT-06:20 | 0.00 | 01-OCT-00:10 | 152844.55 | 30-OCT-04:02 | 86679.80 | 16-OCT-04:02 | 75156.49 | 30-OCT-04:02 | 34815.10 | 30-OCT-04:02 | 0.00 |
November | 0.100758E+12 | 0.250722E+11 | 424.26 | 0.617232E+11 | 0.390348E+11 | 0.00 | 1.00 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 | 130816.93 | 13-NOV-05:02 | 73294.87 | 13-NOV-05:02 | 57522.07 | 13-NOV-05:02 | 30316.44 | 13-NOV-05:02 | 0.00 |
December | 0.936601E+11 | 0.235597E+11 | 431.47 | 0.614241E+11 | 0.322360E+11 | 0.00 | 1.00 | 01-DEC-08:15 | 0.00 | 01-DEC-00:10 | 115726.76 | 30-DEC-06:02 | 81819.45 | 25-DEC-15:32 | 50812.48 | 30-DEC-06:02 | 27221.27 | 25-DEC-15:32 | 0.00 |
Annual Sum or Average | 0.133441E+13 | 0.338600E+12 | 5369.49 | 0.816018E+12 | 0.518397E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.923493E+11 | 0.235597E+11 | 405.68 | 0.614241E+11 | 0.287874E+11 | 0.00 | 1.00 | 0.00 | 115726.76 | 73294.87 | 50812.48 | 27221.27 | 0.00 | ||||||
Maximum of Months | 0.134690E+12 | 0.347040E+11 | 479.91 | 0.776942E+11 | 0.575854E+11 | 0.00 | 1.00 | 0.00 | 154844.20 | 93361.36 | 89105.37 | 40022.64 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 494.41 | 0.00 | 494.41 | 1026.31 | 226.01 | 0.00 | 0.00 | 0.00 |
February | 527.40 | 0.00 | 527.40 | 1148.81 | 173.53 | 0.00 | 0.00 | 0.00 |
March | 541.27 | 0.00 | 541.27 | 1247.91 | 117.75 | 0.00 | 0.00 | 0.00 |
April | 589.04 | 8.35 | 580.70 | 1396.68 | 54.25 | 0.00 | 0.00 | 0.00 |
May | 755.08 | 80.44 | 674.65 | 1784.45 | 64.83 | 0.00 | 0.00 | 0.00 |
June | 922.36 | 186.40 | 735.96 | 2123.12 | 75.10 | 0.00 | 0.00 | 0.00 |
July | 793.14 | 83.14 | 710.01 | 1670.20 | 127.57 | 0.00 | 0.00 | 0.00 |
August | 653.02 | 27.85 | 625.17 | 1393.81 | 96.66 | 0.00 | 0.00 | 0.00 |
September | 555.97 | 0.27 | 555.71 | 1224.78 | 97.65 | 0.00 | 0.00 | 0.00 |
October | 535.70 | 0.00 | 535.70 | 1091.33 | 128.23 | 0.00 | 0.00 | 0.00 |
November | 506.89 | 0.00 | 506.89 | 1043.89 | 153.47 | 0.00 | 0.00 | 0.00 |
December | 480.31 | 0.00 | 480.31 | 988.92 | 245.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 613.25 | 32.29 | 580.96 | 1345.51 | 130.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 480.31 | 0.00 | 480.31 | 988.92 | 54.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 922.36 | 186.40 | 735.96 | 2123.12 | 245.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 635.57 | 214.21 | 421.37 | 1219.05 | 142.67 | 0.00 | 0.00 | 0.00 |
February | 720.73 | 264.26 | 456.48 | 1414.26 | 107.76 | 0.00 | 0.00 | 0.00 |
March | 785.74 | 307.69 | 478.05 | 1578.07 | 71.48 | 0.00 | 0.00 | 0.00 |
April | 794.11 | 303.38 | 490.73 | 1637.12 | 33.39 | 0.00 | 0.00 | 0.00 |
May | 682.61 | 206.62 | 475.98 | 1466.15 | 40.95 | 0.00 | 0.00 | 0.00 |
June | 727.03 | 239.45 | 487.59 | 1540.74 | 46.37 | 0.00 | 0.00 | 0.00 |
July | 620.99 | 139.12 | 481.87 | 1239.89 | 80.73 | 0.00 | 0.00 | 0.00 |
August | 683.41 | 200.89 | 482.51 | 1342.97 | 62.49 | 0.00 | 0.00 | 0.00 |
September | 641.80 | 174.89 | 466.91 | 1296.12 | 64.51 | 0.00 | 0.00 | 0.00 |
October | 601.51 | 153.89 | 447.62 | 1155.08 | 84.32 | 0.00 | 0.00 | 0.00 |
November | 582.14 | 160.87 | 421.27 | 1124.82 | 100.58 | 0.00 | 0.00 | 0.00 |
December | 595.73 | 191.18 | 404.55 | 1137.96 | 157.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 672.07 | 212.54 | 459.53 | 1344.87 | 82.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.14 | 139.12 | 404.55 | 1124.82 | 33.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 794.11 | 307.69 | 490.73 | 1637.12 | 157.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1309.01 | 546.13 | 762.87 | 2536.90 | 232.11 | 0.00 | 0.00 | 0.00 |
February | 1111.54 | 362.41 | 749.14 | 2315.60 | 173.23 | 0.00 | 0.00 | 0.00 |
March | 758.57 | 101.88 | 656.69 | 1742.58 | 112.63 | 0.00 | 0.00 | 0.00 |
April | 565.55 | 0.25 | 565.29 | 1358.77 | 48.57 | 0.00 | 0.00 | 0.00 |
May | 565.93 | 0.00 | 565.93 | 1395.30 | 59.38 | 0.00 | 0.00 | 0.00 |
June | 563.90 | 0.00 | 563.90 | 1385.62 | 65.95 | 0.00 | 0.00 | 0.00 |
July | 580.90 | 0.00 | 580.90 | 1239.54 | 120.58 | 0.00 | 0.00 | 0.00 |
August | 565.51 | 0.87 | 564.63 | 1213.89 | 89.43 | 0.00 | 0.00 | 0.00 |
September | 626.06 | 20.45 | 605.61 | 1372.30 | 97.91 | 0.00 | 0.00 | 0.00 |
October | 819.07 | 130.59 | 688.47 | 1649.20 | 135.38 | 0.00 | 0.00 | 0.00 |
November | 1065.06 | 324.93 | 740.12 | 2094.48 | 164.23 | 0.00 | 0.00 | 0.00 |
December | 1308.34 | 556.64 | 751.69 | 2499.45 | 257.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 818.81 | 169.69 | 649.12 | 1730.83 | 129.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 563.90 | 0.00 | 563.90 | 1213.89 | 48.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1309.01 | 556.64 | 762.87 | 2536.90 | 257.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 643.97 | 226.44 | 417.53 | 1255.42 | 157.71 | 0.00 | 0.00 | 0.00 |
February | 707.26 | 250.28 | 456.98 | 1408.91 | 120.59 | 0.00 | 0.00 | 0.00 |
March | 792.79 | 313.14 | 479.65 | 1605.26 | 87.57 | 0.00 | 0.00 | 0.00 |
April | 796.71 | 305.15 | 491.56 | 1634.09 | 41.02 | 0.00 | 0.00 | 0.00 |
May | 677.91 | 200.83 | 477.08 | 1449.90 | 41.39 | 0.00 | 0.00 | 0.00 |
June | 734.60 | 253.20 | 481.40 | 1545.27 | 47.63 | 0.00 | 0.00 | 0.00 |
July | 626.29 | 147.69 | 478.59 | 1250.71 | 82.92 | 0.00 | 0.00 | 0.00 |
August | 680.90 | 201.64 | 479.26 | 1332.10 | 64.01 | 0.00 | 0.00 | 0.00 |
September | 637.76 | 176.89 | 460.87 | 1284.59 | 67.34 | 0.00 | 0.00 | 0.00 |
October | 598.98 | 154.41 | 444.58 | 1152.67 | 88.19 | 0.00 | 0.00 | 0.00 |
November | 584.13 | 159.31 | 424.82 | 1136.06 | 105.35 | 0.00 | 0.00 | 0.00 |
December | 597.81 | 195.56 | 402.26 | 1165.05 | 169.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 672.82 | 215.00 | 457.81 | 1350.67 | 89.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 584.13 | 147.69 | 402.26 | 1136.06 | 41.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 796.71 | 313.14 | 491.56 | 1634.09 | 169.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 164.79 | 0.00 | 164.79 | 343.90 | 79.44 | 0.00 | 0.00 | 0.00 |
February | 175.79 | 0.00 | 175.79 | 385.37 | 62.17 | 0.00 | 0.00 | 0.00 |
March | 180.41 | 0.00 | 180.41 | 419.20 | 41.44 | 0.00 | 0.00 | 0.00 |
April | 196.34 | 2.78 | 193.56 | 470.12 | 18.74 | 0.00 | 0.00 | 0.00 |
May | 251.68 | 26.81 | 224.87 | 598.19 | 24.12 | 0.00 | 0.00 | 0.00 |
June | 307.44 | 62.13 | 245.31 | 710.49 | 28.13 | 0.00 | 0.00 | 0.00 |
July | 264.37 | 27.71 | 236.66 | 559.68 | 47.72 | 0.00 | 0.00 | 0.00 |
August | 217.66 | 9.28 | 208.38 | 465.22 | 37.17 | 0.00 | 0.00 | 0.00 |
September | 185.32 | 0.09 | 185.23 | 410.09 | 35.92 | 0.00 | 0.00 | 0.00 |
October | 178.56 | 0.00 | 178.56 | 366.28 | 45.88 | 0.00 | 0.00 | 0.00 |
November | 168.96 | 0.00 | 168.96 | 349.97 | 55.95 | 0.00 | 0.00 | 0.00 |
December | 160.10 | 0.00 | 160.10 | 330.41 | 88.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.41 | 10.76 | 193.65 | 450.90 | 47.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.10 | 0.00 | 160.10 | 330.41 | 18.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 307.44 | 62.13 | 245.31 | 710.49 | 88.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 164.80 | 0.00 | 164.80 | 343.91 | 79.44 | 0.00 | 0.00 | 0.00 |
February | 175.80 | 0.00 | 175.80 | 385.39 | 62.17 | 0.00 | 0.00 | 0.00 |
March | 180.42 | 0.00 | 180.42 | 419.22 | 41.44 | 0.00 | 0.00 | 0.00 |
April | 196.35 | 2.78 | 193.56 | 470.14 | 18.74 | 0.00 | 0.00 | 0.00 |
May | 251.69 | 26.81 | 224.88 | 598.22 | 24.12 | 0.00 | 0.00 | 0.00 |
June | 307.45 | 62.13 | 245.32 | 710.51 | 28.13 | 0.00 | 0.00 | 0.00 |
July | 264.38 | 27.71 | 236.67 | 559.70 | 47.72 | 0.00 | 0.00 | 0.00 |
August | 217.67 | 9.28 | 208.39 | 465.24 | 37.17 | 0.00 | 0.00 | 0.00 |
September | 185.32 | 0.09 | 185.23 | 410.11 | 35.92 | 0.00 | 0.00 | 0.00 |
October | 178.57 | 0.00 | 178.57 | 366.29 | 45.88 | 0.00 | 0.00 | 0.00 |
November | 168.96 | 0.00 | 168.96 | 349.98 | 55.95 | 0.00 | 0.00 | 0.00 |
December | 160.10 | 0.00 | 160.10 | 330.43 | 88.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.41 | 10.76 | 193.65 | 450.92 | 47.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.10 | 0.00 | 160.10 | 330.43 | 18.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 307.45 | 62.13 | 245.32 | 710.51 | 88.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 164.80 | 0.00 | 164.80 | 343.91 | 79.44 | 0.00 | 0.00 | 0.00 |
February | 175.80 | 0.00 | 175.80 | 385.39 | 62.17 | 0.00 | 0.00 | 0.00 |
March | 180.42 | 0.00 | 180.42 | 419.22 | 41.44 | 0.00 | 0.00 | 0.00 |
April | 196.35 | 2.78 | 193.56 | 470.14 | 18.74 | 0.00 | 0.00 | 0.00 |
May | 251.69 | 26.81 | 224.88 | 598.22 | 24.12 | 0.00 | 0.00 | 0.00 |
June | 307.45 | 62.13 | 245.32 | 710.51 | 28.13 | 0.00 | 0.00 | 0.00 |
July | 264.38 | 27.71 | 236.67 | 559.70 | 47.72 | 0.00 | 0.00 | 0.00 |
August | 217.67 | 9.28 | 208.39 | 465.24 | 37.17 | 0.00 | 0.00 | 0.00 |
September | 185.32 | 0.09 | 185.23 | 410.11 | 35.92 | 0.00 | 0.00 | 0.00 |
October | 178.57 | 0.00 | 178.57 | 366.29 | 45.88 | 0.00 | 0.00 | 0.00 |
November | 168.96 | 0.00 | 168.96 | 349.98 | 55.95 | 0.00 | 0.00 | 0.00 |
December | 160.10 | 0.00 | 160.10 | 330.43 | 88.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.41 | 10.76 | 193.65 | 450.92 | 47.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.10 | 0.00 | 160.10 | 330.43 | 18.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 307.45 | 62.13 | 245.32 | 710.51 | 88.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 611.39 | 206.05 | 405.33 | 1175.65 | 151.98 | 0.00 | 0.00 | 0.00 |
February | 693.31 | 254.20 | 439.11 | 1364.57 | 120.22 | 0.00 | 0.00 | 0.00 |
March | 755.84 | 295.98 | 459.86 | 1525.56 | 82.83 | 0.00 | 0.00 | 0.00 |
April | 763.89 | 291.84 | 472.05 | 1581.19 | 39.51 | 0.00 | 0.00 | 0.00 |
May | 656.63 | 198.76 | 457.87 | 1413.24 | 46.63 | 0.00 | 0.00 | 0.00 |
June | 699.37 | 230.33 | 469.04 | 1485.97 | 52.19 | 0.00 | 0.00 | 0.00 |
July | 597.36 | 133.82 | 463.54 | 1196.16 | 90.27 | 0.00 | 0.00 | 0.00 |
August | 657.40 | 193.25 | 464.16 | 1292.40 | 74.54 | 0.00 | 0.00 | 0.00 |
September | 617.38 | 168.24 | 449.14 | 1249.06 | 74.61 | 0.00 | 0.00 | 0.00 |
October | 578.63 | 148.03 | 430.59 | 1115.36 | 93.73 | 0.00 | 0.00 | 0.00 |
November | 559.99 | 154.75 | 405.24 | 1085.53 | 112.36 | 0.00 | 0.00 | 0.00 |
December | 573.06 | 183.90 | 389.16 | 1096.11 | 171.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 646.50 | 204.46 | 442.04 | 1297.29 | 92.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 559.99 | 133.82 | 389.16 | 1085.53 | 39.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 763.89 | 295.98 | 472.05 | 1581.19 | 171.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.17 | 8.15 | 16.03 | 46.48 | 6.01 | 0.00 | 0.00 | 0.00 |
February | 27.41 | 10.05 | 17.36 | 53.95 | 4.75 | 0.00 | 0.00 | 0.00 |
March | 29.89 | 11.70 | 18.18 | 60.32 | 3.28 | 0.00 | 0.00 | 0.00 |
April | 30.20 | 11.54 | 18.66 | 62.52 | 1.56 | 0.00 | 0.00 | 0.00 |
May | 25.96 | 7.86 | 18.10 | 55.88 | 1.84 | 0.00 | 0.00 | 0.00 |
June | 27.65 | 9.11 | 18.55 | 58.75 | 2.06 | 0.00 | 0.00 | 0.00 |
July | 23.62 | 5.29 | 18.33 | 47.30 | 3.57 | 0.00 | 0.00 | 0.00 |
August | 25.99 | 7.64 | 18.35 | 51.10 | 2.95 | 0.00 | 0.00 | 0.00 |
September | 24.41 | 6.65 | 17.76 | 49.39 | 2.95 | 0.00 | 0.00 | 0.00 |
October | 22.88 | 5.85 | 17.03 | 44.10 | 3.71 | 0.00 | 0.00 | 0.00 |
November | 22.14 | 6.12 | 16.02 | 42.92 | 4.44 | 0.00 | 0.00 | 0.00 |
December | 22.66 | 7.27 | 15.39 | 43.34 | 6.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.56 | 8.08 | 17.48 | 51.29 | 3.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.14 | 5.29 | 15.39 | 42.92 | 1.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.20 | 11.70 | 18.66 | 62.52 | 6.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 436.33 | 182.04 | 254.29 | 841.65 | 89.27 | 0.00 | 0.00 | 0.00 |
February | 370.51 | 120.80 | 249.71 | 767.14 | 69.07 | 0.00 | 0.00 | 0.00 |
March | 252.85 | 33.96 | 218.89 | 578.96 | 43.83 | 0.00 | 0.00 | 0.00 |
April | 188.51 | 0.08 | 188.43 | 452.76 | 17.88 | 0.00 | 0.00 | 0.00 |
May | 188.64 | 0.00 | 188.64 | 464.03 | 22.24 | 0.00 | 0.00 | 0.00 |
June | 187.96 | 0.00 | 187.96 | 459.52 | 24.09 | 0.00 | 0.00 | 0.00 |
July | 193.63 | 0.00 | 193.63 | 413.84 | 44.86 | 0.00 | 0.00 | 0.00 |
August | 188.50 | 0.29 | 188.21 | 402.43 | 35.24 | 0.00 | 0.00 | 0.00 |
September | 208.68 | 6.82 | 201.87 | 457.02 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 273.02 | 43.53 | 229.49 | 550.33 | 51.16 | 0.00 | 0.00 | 0.00 |
November | 355.01 | 108.31 | 246.70 | 696.04 | 64.57 | 0.00 | 0.00 | 0.00 |
December | 436.11 | 185.54 | 250.56 | 829.80 | 99.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.93 | 56.56 | 216.37 | 575.21 | 49.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 187.96 | 0.00 | 187.96 | 402.43 | 17.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 436.33 | 185.54 | 254.29 | 841.65 | 99.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 436.33 | 182.04 | 254.29 | 841.65 | 89.27 | 0.00 | 0.00 | 0.00 |
February | 370.51 | 120.80 | 249.71 | 767.14 | 69.07 | 0.00 | 0.00 | 0.00 |
March | 252.85 | 33.96 | 218.89 | 578.96 | 43.83 | 0.00 | 0.00 | 0.00 |
April | 188.51 | 0.08 | 188.43 | 452.76 | 17.88 | 0.00 | 0.00 | 0.00 |
May | 188.64 | 0.00 | 188.64 | 464.03 | 22.24 | 0.00 | 0.00 | 0.00 |
June | 187.96 | 0.00 | 187.96 | 459.52 | 24.09 | 0.00 | 0.00 | 0.00 |
July | 193.63 | 0.00 | 193.63 | 413.84 | 44.86 | 0.00 | 0.00 | 0.00 |
August | 188.50 | 0.29 | 188.21 | 402.43 | 35.24 | 0.00 | 0.00 | 0.00 |
September | 208.68 | 6.82 | 201.87 | 457.02 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 273.02 | 43.53 | 229.49 | 550.33 | 51.16 | 0.00 | 0.00 | 0.00 |
November | 355.01 | 108.31 | 246.70 | 696.04 | 64.57 | 0.00 | 0.00 | 0.00 |
December | 436.11 | 185.54 | 250.56 | 829.80 | 99.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.93 | 56.56 | 216.37 | 575.21 | 49.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 187.96 | 0.00 | 187.96 | 402.43 | 17.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 436.33 | 185.54 | 254.29 | 841.65 | 99.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 436.30 | 182.03 | 254.27 | 841.60 | 89.27 | 0.00 | 0.00 | 0.00 |
February | 370.49 | 120.79 | 249.69 | 767.09 | 69.06 | 0.00 | 0.00 | 0.00 |
March | 252.84 | 33.96 | 218.88 | 578.92 | 43.82 | 0.00 | 0.00 | 0.00 |
April | 188.50 | 0.08 | 188.42 | 452.73 | 17.88 | 0.00 | 0.00 | 0.00 |
May | 188.63 | 0.00 | 188.63 | 464.00 | 22.24 | 0.00 | 0.00 | 0.00 |
June | 187.95 | 0.00 | 187.95 | 459.49 | 24.09 | 0.00 | 0.00 | 0.00 |
July | 193.62 | 0.00 | 193.62 | 413.81 | 44.86 | 0.00 | 0.00 | 0.00 |
August | 188.49 | 0.29 | 188.20 | 402.40 | 35.23 | 0.00 | 0.00 | 0.00 |
September | 208.67 | 6.82 | 201.86 | 457.00 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 273.00 | 43.53 | 229.47 | 550.29 | 51.15 | 0.00 | 0.00 | 0.00 |
November | 354.99 | 108.30 | 246.69 | 695.99 | 64.56 | 0.00 | 0.00 | 0.00 |
December | 436.08 | 185.53 | 250.55 | 829.74 | 99.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.92 | 56.56 | 216.36 | 575.17 | 49.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 187.95 | 0.00 | 187.95 | 402.40 | 17.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 436.30 | 185.53 | 254.27 | 841.60 | 99.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 619.47 | 217.82 | 401.64 | 1207.99 | 168.69 | 0.00 | 0.00 | 0.00 |
February | 680.35 | 240.76 | 439.59 | 1357.27 | 134.94 | 0.00 | 0.00 | 0.00 |
March | 762.63 | 301.22 | 461.40 | 1548.82 | 99.22 | 0.00 | 0.00 | 0.00 |
April | 766.40 | 293.54 | 472.86 | 1576.19 | 48.18 | 0.00 | 0.00 | 0.00 |
May | 652.12 | 193.19 | 458.93 | 1395.45 | 48.75 | 0.00 | 0.00 | 0.00 |
June | 706.65 | 243.57 | 463.09 | 1488.50 | 55.24 | 0.00 | 0.00 | 0.00 |
July | 602.46 | 142.07 | 460.39 | 1204.89 | 94.97 | 0.00 | 0.00 | 0.00 |
August | 654.99 | 193.97 | 461.02 | 1280.21 | 78.14 | 0.00 | 0.00 | 0.00 |
September | 613.50 | 170.16 | 443.34 | 1236.14 | 78.58 | 0.00 | 0.00 | 0.00 |
October | 576.19 | 148.53 | 427.66 | 1109.70 | 99.25 | 0.00 | 0.00 | 0.00 |
November | 561.91 | 153.25 | 408.66 | 1092.74 | 118.61 | 0.00 | 0.00 | 0.00 |
December | 575.07 | 188.11 | 386.95 | 1119.04 | 186.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 647.22 | 206.82 | 440.40 | 1300.44 | 100.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 561.91 | 142.07 | 386.95 | 1092.74 | 48.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 766.40 | 301.22 | 472.86 | 1576.19 | 186.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.49 | 8.61 | 15.88 | 47.76 | 6.67 | 0.00 | 0.00 | 0.00 |
February | 26.90 | 9.52 | 17.38 | 53.66 | 5.34 | 0.00 | 0.00 | 0.00 |
March | 30.15 | 11.91 | 18.24 | 61.24 | 3.92 | 0.00 | 0.00 | 0.00 |
April | 30.30 | 11.61 | 18.70 | 62.32 | 1.90 | 0.00 | 0.00 | 0.00 |
May | 25.78 | 7.64 | 18.15 | 55.17 | 1.93 | 0.00 | 0.00 | 0.00 |
June | 27.94 | 9.63 | 18.31 | 58.85 | 2.18 | 0.00 | 0.00 | 0.00 |
July | 23.82 | 5.62 | 18.20 | 47.64 | 3.76 | 0.00 | 0.00 | 0.00 |
August | 25.90 | 7.67 | 18.23 | 50.62 | 3.09 | 0.00 | 0.00 | 0.00 |
September | 24.26 | 6.73 | 17.53 | 48.88 | 3.11 | 0.00 | 0.00 | 0.00 |
October | 22.78 | 5.87 | 16.91 | 43.88 | 3.92 | 0.00 | 0.00 | 0.00 |
November | 22.22 | 6.06 | 16.16 | 43.21 | 4.69 | 0.00 | 0.00 | 0.00 |
December | 22.74 | 7.44 | 15.30 | 44.25 | 7.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.59 | 8.18 | 17.41 | 51.42 | 3.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.22 | 5.62 | 15.30 | 43.21 | 1.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.30 | 11.91 | 18.70 | 62.32 | 7.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 494.41 | 0.00 | 494.41 | 1033.99 | 235.85 | 0.00 | 0.00 | 0.00 |
February | 527.40 | 0.00 | 527.40 | 1158.37 | 182.94 | 0.00 | 0.00 | 0.00 |
March | 541.27 | 0.00 | 541.27 | 1260.59 | 121.90 | 0.00 | 0.00 | 0.00 |
April | 589.04 | 8.35 | 580.70 | 1414.24 | 54.82 | 0.00 | 0.00 | 0.00 |
May | 755.08 | 80.44 | 674.65 | 1800.37 | 65.79 | 0.00 | 0.00 | 0.00 |
June | 922.36 | 186.40 | 735.96 | 2140.09 | 74.50 | 0.00 | 0.00 | 0.00 |
July | 793.14 | 83.14 | 710.01 | 1684.87 | 130.13 | 0.00 | 0.00 | 0.00 |
August | 653.02 | 27.85 | 625.17 | 1404.38 | 100.02 | 0.00 | 0.00 | 0.00 |
September | 555.97 | 0.27 | 555.71 | 1238.26 | 99.04 | 0.00 | 0.00 | 0.00 |
October | 535.70 | 0.00 | 535.70 | 1101.45 | 132.19 | 0.00 | 0.00 | 0.00 |
November | 506.89 | 0.00 | 506.89 | 1052.66 | 161.64 | 0.00 | 0.00 | 0.00 |
December | 480.31 | 0.00 | 480.31 | 995.08 | 258.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 613.25 | 32.29 | 580.96 | 1357.52 | 134.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 480.31 | 0.00 | 480.31 | 995.08 | 54.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 922.36 | 186.40 | 735.96 | 2140.09 | 258.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 635.57 | 214.21 | 421.37 | 1225.16 | 148.45 | 0.00 | 0.00 | 0.00 |
February | 720.73 | 264.26 | 456.48 | 1421.96 | 113.90 | 0.00 | 0.00 | 0.00 |
March | 785.74 | 307.69 | 478.05 | 1588.58 | 74.74 | 0.00 | 0.00 | 0.00 |
April | 794.11 | 303.38 | 490.73 | 1649.85 | 34.07 | 0.00 | 0.00 | 0.00 |
May | 682.61 | 206.62 | 475.98 | 1477.06 | 41.68 | 0.00 | 0.00 | 0.00 |
June | 727.03 | 239.45 | 487.59 | 1552.43 | 46.00 | 0.00 | 0.00 | 0.00 |
July | 620.99 | 139.12 | 481.87 | 1249.48 | 82.55 | 0.00 | 0.00 | 0.00 |
August | 683.41 | 200.89 | 482.51 | 1350.54 | 64.74 | 0.00 | 0.00 | 0.00 |
September | 641.80 | 174.89 | 466.91 | 1305.62 | 65.43 | 0.00 | 0.00 | 0.00 |
October | 601.51 | 153.89 | 447.62 | 1162.68 | 86.93 | 0.00 | 0.00 | 0.00 |
November | 582.14 | 160.87 | 421.27 | 1131.67 | 105.68 | 0.00 | 0.00 | 0.00 |
December | 595.73 | 191.18 | 404.55 | 1142.76 | 164.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 672.07 | 212.54 | 459.53 | 1353.66 | 85.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.14 | 139.12 | 404.55 | 1131.67 | 34.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 794.11 | 307.69 | 490.73 | 1649.85 | 164.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1309.01 | 546.13 | 762.87 | 2544.27 | 240.80 | 0.00 | 0.00 | 0.00 |
February | 1111.54 | 362.41 | 749.14 | 2326.06 | 182.29 | 0.00 | 0.00 | 0.00 |
March | 758.57 | 101.88 | 656.69 | 1756.30 | 117.43 | 0.00 | 0.00 | 0.00 |
April | 565.55 | 0.25 | 565.29 | 1375.90 | 49.52 | 0.00 | 0.00 | 0.00 |
May | 565.93 | 0.00 | 565.93 | 1410.50 | 60.69 | 0.00 | 0.00 | 0.00 |
June | 563.90 | 0.00 | 563.90 | 1401.72 | 65.82 | 0.00 | 0.00 | 0.00 |
July | 580.90 | 0.00 | 580.90 | 1253.41 | 123.45 | 0.00 | 0.00 | 0.00 |
August | 565.51 | 0.87 | 564.63 | 1224.27 | 93.40 | 0.00 | 0.00 | 0.00 |
September | 626.06 | 20.45 | 605.61 | 1386.18 | 99.45 | 0.00 | 0.00 | 0.00 |
October | 819.07 | 130.59 | 688.47 | 1660.57 | 139.13 | 0.00 | 0.00 | 0.00 |
November | 1065.06 | 324.93 | 740.12 | 2104.46 | 171.72 | 0.00 | 0.00 | 0.00 |
December | 1308.34 | 556.64 | 751.69 | 2505.04 | 268.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 818.81 | 169.69 | 649.12 | 1742.91 | 134.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 563.90 | 0.00 | 563.90 | 1224.27 | 49.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1309.01 | 556.64 | 762.87 | 2544.27 | 268.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 643.97 | 226.44 | 417.53 | 1259.09 | 165.45 | 0.00 | 0.00 | 0.00 |
February | 707.26 | 250.28 | 456.98 | 1414.49 | 128.35 | 0.00 | 0.00 | 0.00 |
March | 792.79 | 313.14 | 479.65 | 1613.19 | 91.37 | 0.00 | 0.00 | 0.00 |
April | 796.71 | 305.15 | 491.56 | 1644.13 | 42.11 | 0.00 | 0.00 | 0.00 |
May | 677.91 | 200.83 | 477.08 | 1458.40 | 42.90 | 0.00 | 0.00 | 0.00 |
June | 734.60 | 253.20 | 481.40 | 1555.23 | 48.17 | 0.00 | 0.00 | 0.00 |
July | 626.29 | 147.69 | 478.59 | 1258.52 | 86.26 | 0.00 | 0.00 | 0.00 |
August | 680.90 | 201.64 | 479.26 | 1338.07 | 67.61 | 0.00 | 0.00 | 0.00 |
September | 637.76 | 176.89 | 460.87 | 1292.26 | 69.26 | 0.00 | 0.00 | 0.00 |
October | 598.98 | 154.41 | 444.58 | 1157.79 | 92.15 | 0.00 | 0.00 | 0.00 |
November | 584.13 | 159.31 | 424.82 | 1140.38 | 112.01 | 0.00 | 0.00 | 0.00 |
December | 597.81 | 195.56 | 402.26 | 1167.62 | 179.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 672.82 | 215.00 | 457.81 | 1357.26 | 93.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 584.13 | 147.69 | 402.26 | 1140.38 | 42.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 796.71 | 313.14 | 491.56 | 1644.13 | 179.53 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132422E+10 | 0.00 | 0.132422E+10 | 0.274887E+10 | 0.605335E+09 |
February | 0.127587E+10 | 0.00 | 0.127587E+10 | 0.277920E+10 | 0.419816E+09 |
March | 0.144973E+10 | 0.00 | 0.144973E+10 | 0.334240E+10 | 0.315388E+09 |
April | 0.152680E+10 | 21637656.65 | 0.150517E+10 | 0.362021E+10 | 0.140612E+09 |
May | 0.202242E+10 | 0.215448E+09 | 0.180697E+10 | 0.477948E+10 | 0.173653E+09 |
June | 0.239076E+10 | 0.483154E+09 | 0.190761E+10 | 0.550314E+10 | 0.194654E+09 |
July | 0.212436E+10 | 0.222671E+09 | 0.190169E+10 | 0.447347E+10 | 0.341680E+09 |
August | 0.174904E+10 | 74580343.55 | 0.167446E+10 | 0.373318E+10 | 0.258883E+09 |
September | 0.144108E+10 | 690066.21 | 0.144039E+10 | 0.317462E+10 | 0.253098E+09 |
October | 0.143482E+10 | 0.00 | 0.143482E+10 | 0.292303E+10 | 0.343443E+09 |
November | 0.131386E+10 | 0.00 | 0.131386E+10 | 0.270576E+10 | 0.397797E+09 |
December | 0.128646E+10 | 0.00 | 0.128646E+10 | 0.264872E+10 | 0.658367E+09 |
Annual Sum or Average | 0.193394E+11 | 0.101818E+10 | 0.183212E+11 | 0.424321E+11 | 0.410273E+10 |
Minimum of Months | 0.127587E+10 | 0.00 | 0.127587E+10 | 0.264872E+10 | 0.140612E+09 |
Maximum of Months | 0.239076E+10 | 0.483154E+09 | 0.190761E+10 | 0.550314E+10 | 0.658367E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170231E+10 | 0.573729E+09 | 0.112859E+10 | 0.326511E+10 | 0.382114E+09 |
February | 0.174360E+10 | 0.639290E+09 | 0.110431E+10 | 0.342139E+10 | 0.260705E+09 |
March | 0.210452E+10 | 0.824120E+09 | 0.128040E+10 | 0.422670E+10 | 0.191448E+09 |
April | 0.205833E+10 | 0.786368E+09 | 0.127196E+10 | 0.424342E+10 | 86554402.38 |
May | 0.182829E+10 | 0.553421E+09 | 0.127487E+10 | 0.392694E+10 | 0.109689E+09 |
June | 0.188447E+10 | 0.620645E+09 | 0.126383E+10 | 0.399360E+10 | 0.120194E+09 |
July | 0.166325E+10 | 0.372609E+09 | 0.129064E+10 | 0.332091E+10 | 0.216238E+09 |
August | 0.183044E+10 | 0.538071E+09 | 0.129237E+10 | 0.359701E+10 | 0.167367E+09 |
September | 0.166356E+10 | 0.453326E+09 | 0.121023E+10 | 0.335955E+10 | 0.167215E+09 |
October | 0.161109E+10 | 0.412175E+09 | 0.119892E+10 | 0.309376E+10 | 0.225855E+09 |
November | 0.150892E+10 | 0.416983E+09 | 0.109193E+10 | 0.291554E+10 | 0.260703E+09 |
December | 0.159560E+10 | 0.512044E+09 | 0.108356E+10 | 0.304791E+10 | 0.420976E+09 |
Annual Sum or Average | 0.211944E+11 | 0.670278E+10 | 0.144916E+11 | 0.424118E+11 | 0.260906E+10 |
Minimum of Months | 0.150892E+10 | 0.372609E+09 | 0.108356E+10 | 0.291554E+10 | 86554402.38 |
Maximum of Months | 0.210452E+10 | 0.824120E+09 | 0.129237E+10 | 0.424342E+10 | 0.420976E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.350604E+10 | 0.146276E+10 | 0.204328E+10 | 0.679483E+10 | 0.621688E+09 |
February | 0.268905E+10 | 0.876730E+09 | 0.181232E+10 | 0.560189E+10 | 0.419068E+09 |
March | 0.203174E+10 | 0.272864E+09 | 0.175888E+10 | 0.466732E+10 | 0.301659E+09 |
April | 0.146590E+10 | 658052.64 | 0.146524E+10 | 0.352194E+10 | 0.125891E+09 |
May | 0.151580E+10 | 0.00 | 0.151580E+10 | 0.373716E+10 | 0.159034E+09 |
June | 0.146162E+10 | 0.00 | 0.146162E+10 | 0.359153E+10 | 0.170937E+09 |
July | 0.155588E+10 | 0.00 | 0.155588E+10 | 0.331998E+10 | 0.322965E+09 |
August | 0.151466E+10 | 2340935.21 | 0.151232E+10 | 0.325128E+10 | 0.239542E+09 |
September | 0.162274E+10 | 52999972.44 | 0.156974E+10 | 0.355701E+10 | 0.253795E+09 |
October | 0.219379E+10 | 0.349782E+09 | 0.184401E+10 | 0.441721E+10 | 0.362612E+09 |
November | 0.276063E+10 | 0.842230E+09 | 0.191840E+10 | 0.542890E+10 | 0.425692E+09 |
December | 0.350425E+10 | 0.149091E+10 | 0.201333E+10 | 0.669453E+10 | 0.688488E+09 |
Annual Sum or Average | 0.258221E+11 | 0.535128E+10 | 0.204708E+11 | 0.545836E+11 | 0.409137E+10 |
Minimum of Months | 0.146162E+10 | 0.00 | 0.146162E+10 | 0.325128E+10 | 0.125891E+09 |
Maximum of Months | 0.350604E+10 | 0.149091E+10 | 0.204328E+10 | 0.679483E+10 | 0.688488E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172481E+10 | 0.606498E+09 | 0.111831E+10 | 0.336251E+10 | 0.422413E+09 |
February | 0.171101E+10 | 0.605487E+09 | 0.110552E+10 | 0.340842E+10 | 0.291730E+09 |
March | 0.212341E+10 | 0.838705E+09 | 0.128470E+10 | 0.429953E+10 | 0.234554E+09 |
April | 0.206507E+10 | 0.790953E+09 | 0.127412E+10 | 0.423555E+10 | 0.106335E+09 |
May | 0.181572E+10 | 0.537914E+09 | 0.127781E+10 | 0.388342E+10 | 0.110849E+09 |
June | 0.190409E+10 | 0.656295E+09 | 0.124780E+10 | 0.400533E+10 | 0.123462E+09 |
July | 0.167745E+10 | 0.395580E+09 | 0.128187E+10 | 0.334990E+10 | 0.222088E+09 |
August | 0.182372E+10 | 0.540083E+09 | 0.128364E+10 | 0.356790E+10 | 0.171457E+09 |
September | 0.165308E+10 | 0.458491E+09 | 0.119459E+10 | 0.332967E+10 | 0.174551E+09 |
October | 0.160432E+10 | 0.413558E+09 | 0.119076E+10 | 0.308731E+10 | 0.236215E+09 |
November | 0.151406E+10 | 0.412932E+09 | 0.110113E+10 | 0.294466E+10 | 0.273066E+09 |
December | 0.160118E+10 | 0.523775E+09 | 0.107740E+10 | 0.312046E+10 | 0.453648E+09 |
Annual Sum or Average | 0.212179E+11 | 0.678027E+10 | 0.144376E+11 | 0.425947E+11 | 0.282037E+10 |
Minimum of Months | 0.151406E+10 | 0.395580E+09 | 0.107740E+10 | 0.294466E+10 | 0.106335E+09 |
Maximum of Months | 0.212341E+10 | 0.838705E+09 | 0.128470E+10 | 0.429953E+10 | 0.453648E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.441385E+09 | 0.00 | 0.441385E+09 | 0.921096E+09 | 0.212772E+09 |
February | 0.425271E+09 | 0.00 | 0.425271E+09 | 0.932280E+09 | 0.150397E+09 |
March | 0.483222E+09 | 0.00 | 0.483222E+09 | 0.112278E+10 | 0.110985E+09 |
April | 0.508910E+09 | 7212210.98 | 0.501698E+09 | 0.121855E+10 | 48566802.87 |
May | 0.674107E+09 | 71812679.45 | 0.602295E+09 | 0.160220E+10 | 64598451.00 |
June | 0.796883E+09 | 0.161044E+09 | 0.635839E+09 | 0.184158E+10 | 72919382.84 |
July | 0.708085E+09 | 74220008.14 | 0.633865E+09 | 0.149904E+10 | 0.127816E+09 |
August | 0.582985E+09 | 24858938.33 | 0.558126E+09 | 0.124604E+10 | 99553924.81 |
September | 0.480337E+09 | 230011.19 | 0.480107E+09 | 0.106297E+10 | 93110443.41 |
October | 0.478251E+09 | 0.00 | 0.478251E+09 | 0.981032E+09 | 0.122878E+09 |
November | 0.437933E+09 | 0.00 | 0.437933E+09 | 0.907113E+09 | 0.145027E+09 |
December | 0.428799E+09 | 0.00 | 0.428799E+09 | 0.884982E+09 | 0.238193E+09 |
Annual Sum or Average | 0.644617E+10 | 0.339378E+09 | 0.610679E+10 | 0.142197E+11 | 0.148682E+10 |
Minimum of Months | 0.425271E+09 | 0.00 | 0.425271E+09 | 0.884982E+09 | 48566802.87 |
Maximum of Months | 0.796883E+09 | 0.161044E+09 | 0.635839E+09 | 0.184158E+10 | 0.238193E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.441402E+09 | 0.00 | 0.441402E+09 | 0.921140E+09 | 0.212782E+09 |
February | 0.425288E+09 | 0.00 | 0.425288E+09 | 0.932325E+09 | 0.150402E+09 |
March | 0.483242E+09 | 0.00 | 0.483242E+09 | 0.112284E+10 | 0.110988E+09 |
April | 0.508931E+09 | 7212404.84 | 0.501718E+09 | 0.121861E+10 | 48567311.82 |
May | 0.674132E+09 | 71814609.79 | 0.602317E+09 | 0.160227E+10 | 64600612.52 |
June | 0.796911E+09 | 0.161048E+09 | 0.635863E+09 | 0.184165E+10 | 72922014.32 |
July | 0.708110E+09 | 74222003.19 | 0.633888E+09 | 0.149910E+10 | 0.127820E+09 |
August | 0.583007E+09 | 24859606.55 | 0.558147E+09 | 0.124609E+10 | 99557475.19 |
September | 0.480355E+09 | 230017.37 | 0.480125E+09 | 0.106301E+10 | 93113952.50 |
October | 0.478269E+09 | 0.00 | 0.478269E+09 | 0.981076E+09 | 0.122883E+09 |
November | 0.437950E+09 | 0.00 | 0.437950E+09 | 0.907154E+09 | 0.145034E+09 |
December | 0.428816E+09 | 0.00 | 0.428816E+09 | 0.885023E+09 | 0.238204E+09 |
Annual Sum or Average | 0.644641E+10 | 0.339387E+09 | 0.610703E+10 | 0.142203E+11 | 0.148687E+10 |
Minimum of Months | 0.425288E+09 | 0.00 | 0.425288E+09 | 0.885023E+09 | 48567311.82 |
Maximum of Months | 0.796911E+09 | 0.161048E+09 | 0.635863E+09 | 0.184165E+10 | 0.238204E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.441402E+09 | 0.00 | 0.441402E+09 | 0.921140E+09 | 0.212782E+09 |
February | 0.425288E+09 | 0.00 | 0.425288E+09 | 0.932325E+09 | 0.150402E+09 |
March | 0.483242E+09 | 0.00 | 0.483242E+09 | 0.112284E+10 | 0.110988E+09 |
April | 0.508931E+09 | 7212404.84 | 0.501718E+09 | 0.121861E+10 | 48567311.82 |
May | 0.674132E+09 | 71814609.79 | 0.602317E+09 | 0.160227E+10 | 64600612.52 |
June | 0.796911E+09 | 0.161048E+09 | 0.635863E+09 | 0.184165E+10 | 72922014.32 |
July | 0.708110E+09 | 74222003.19 | 0.633888E+09 | 0.149910E+10 | 0.127820E+09 |
August | 0.583007E+09 | 24859606.55 | 0.558147E+09 | 0.124609E+10 | 99557475.19 |
September | 0.480355E+09 | 230017.37 | 0.480125E+09 | 0.106301E+10 | 93113952.50 |
October | 0.478269E+09 | 0.00 | 0.478269E+09 | 0.981076E+09 | 0.122883E+09 |
November | 0.437950E+09 | 0.00 | 0.437950E+09 | 0.907154E+09 | 0.145034E+09 |
December | 0.428816E+09 | 0.00 | 0.428816E+09 | 0.885023E+09 | 0.238204E+09 |
Annual Sum or Average | 0.644641E+10 | 0.339387E+09 | 0.610703E+10 | 0.142203E+11 | 0.148687E+10 |
Minimum of Months | 0.425288E+09 | 0.00 | 0.425288E+09 | 0.885023E+09 | 48567311.82 |
Maximum of Months | 0.796911E+09 | 0.161048E+09 | 0.635863E+09 | 0.184165E+10 | 0.238204E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163754E+10 | 0.551896E+09 | 0.108564E+10 | 0.314885E+10 | 0.407055E+09 |
February | 0.167726E+10 | 0.614963E+09 | 0.106229E+10 | 0.330116E+10 | 0.290845E+09 |
March | 0.202444E+10 | 0.792759E+09 | 0.123168E+10 | 0.408606E+10 | 0.221856E+09 |
April | 0.198001E+10 | 0.756443E+09 | 0.122357E+10 | 0.409845E+10 | 0.102400E+09 |
May | 0.175873E+10 | 0.532361E+09 | 0.122637E+10 | 0.378522E+10 | 0.124903E+09 |
June | 0.181277E+10 | 0.597027E+09 | 0.121574E+10 | 0.385162E+10 | 0.135274E+09 |
July | 0.159996E+10 | 0.358430E+09 | 0.124153E+10 | 0.320379E+10 | 0.241778E+09 |
August | 0.176079E+10 | 0.517596E+09 | 0.124320E+10 | 0.346157E+10 | 0.199655E+09 |
September | 0.160026E+10 | 0.436075E+09 | 0.116418E+10 | 0.323756E+10 | 0.193394E+09 |
October | 0.154979E+10 | 0.396490E+09 | 0.115330E+10 | 0.298738E+10 | 0.251051E+09 |
November | 0.145150E+10 | 0.401115E+09 | 0.105039E+10 | 0.281369E+10 | 0.291238E+09 |
December | 0.153489E+10 | 0.492559E+09 | 0.104233E+10 | 0.293582E+10 | 0.458487E+09 |
Annual Sum or Average | 0.203879E+11 | 0.644771E+10 | 0.139402E+11 | 0.409112E+11 | 0.291794E+10 |
Minimum of Months | 0.145150E+10 | 0.358430E+09 | 0.104233E+10 | 0.281369E+10 | 0.102400E+09 |
Maximum of Months | 0.202444E+10 | 0.792759E+09 | 0.124320E+10 | 0.409845E+10 | 0.458487E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64746892.57 | 21821468.99 | 42925423.58 | 0.124503E+09 | 16094568.89 |
February | 66317249.44 | 24315073.31 | 42002176.13 | 0.130525E+09 | 11499736.78 |
March | 80044645.63 | 31344960.81 | 48699684.82 | 0.161559E+09 | 8772006.14 |
April | 78287746.08 | 29909079.22 | 48378666.86 | 0.162049E+09 | 4048823.41 |
May | 69538447.44 | 21049070.23 | 48489377.21 | 0.149664E+09 | 4938562.47 |
June | 71675168.53 | 23605901.32 | 48069267.21 | 0.152290E+09 | 5348630.18 |
July | 63261157.87 | 14171994.25 | 49089163.62 | 0.126675E+09 | 9559666.32 |
August | 69620078.60 | 20465265.39 | 49154813.21 | 0.136867E+09 | 7894198.56 |
September | 63272738.40 | 17242011.22 | 46030727.18 | 0.128010E+09 | 7646643.95 |
October | 61277318.03 | 15676850.18 | 45600467.85 | 0.118118E+09 | 9926342.38 |
November | 57391086.81 | 15859729.53 | 41531357.28 | 0.111251E+09 | 11515303.97 |
December | 60688209.70 | 19475337.43 | 41212872.27 | 0.116080E+09 | 18128171.80 |
Annual Sum or Average | 0.806121E+09 | 0.254937E+09 | 0.551184E+09 | 0.161759E+10 | 0.115373E+09 |
Minimum of Months | 57391086.81 | 14171994.25 | 41212872.27 | 0.111251E+09 | 4048823.41 |
Maximum of Months | 80044645.63 | 31344960.81 | 49154813.21 | 0.162049E+09 | 18128171.80 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116866E+10 | 0.487577E+09 | 0.681086E+09 | 0.225428E+10 | 0.239107E+09 |
February | 0.896336E+09 | 0.292238E+09 | 0.604099E+09 | 0.185587E+10 | 0.167084E+09 |
March | 0.677240E+09 | 90952923.61 | 0.586287E+09 | 0.155068E+10 | 0.117387E+09 |
April | 0.488630E+09 | 219346.40 | 0.488410E+09 | 0.117356E+10 | 46357489.01 |
May | 0.505261E+09 | 0.00 | 0.505261E+09 | 0.124285E+10 | 59566340.43 |
June | 0.487202E+09 | 0.00 | 0.487202E+09 | 0.119107E+10 | 62437603.12 |
July | 0.518621E+09 | 0.00 | 0.518621E+09 | 0.110842E+10 | 0.120164E+09 |
August | 0.504882E+09 | 780295.79 | 0.504101E+09 | 0.107786E+10 | 94373652.73 |
September | 0.540909E+09 | 17666296.50 | 0.523242E+09 | 0.118461E+10 | 96392029.49 |
October | 0.731253E+09 | 0.116592E+09 | 0.614662E+09 | 0.147399E+10 | 0.137019E+09 |
November | 0.920195E+09 | 0.280738E+09 | 0.639457E+09 | 0.180413E+10 | 0.167354E+09 |
December | 0.116806E+10 | 0.496961E+09 | 0.671103E+09 | 0.222253E+10 | 0.267259E+09 |
Annual Sum or Average | 0.860726E+10 | 0.178372E+10 | 0.682353E+10 | 0.181398E+11 | 0.157450E+10 |
Minimum of Months | 0.487202E+09 | 0.00 | 0.487202E+09 | 0.107786E+10 | 46357489.01 |
Maximum of Months | 0.116866E+10 | 0.496961E+09 | 0.681086E+09 | 0.225428E+10 | 0.267259E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116866E+10 | 0.487577E+09 | 0.681086E+09 | 0.225428E+10 | 0.239107E+09 |
February | 0.896336E+09 | 0.292238E+09 | 0.604099E+09 | 0.185587E+10 | 0.167084E+09 |
March | 0.677240E+09 | 90952923.61 | 0.586287E+09 | 0.155068E+10 | 0.117387E+09 |
April | 0.488630E+09 | 219346.40 | 0.488410E+09 | 0.117356E+10 | 46357489.01 |
May | 0.505261E+09 | 0.00 | 0.505261E+09 | 0.124285E+10 | 59566340.43 |
June | 0.487202E+09 | 0.00 | 0.487202E+09 | 0.119107E+10 | 62437603.12 |
July | 0.518621E+09 | 0.00 | 0.518621E+09 | 0.110842E+10 | 0.120164E+09 |
August | 0.504882E+09 | 780295.79 | 0.504101E+09 | 0.107786E+10 | 94373652.73 |
September | 0.540909E+09 | 17666296.50 | 0.523242E+09 | 0.118461E+10 | 96392029.49 |
October | 0.731253E+09 | 0.116592E+09 | 0.614662E+09 | 0.147399E+10 | 0.137019E+09 |
November | 0.920195E+09 | 0.280738E+09 | 0.639457E+09 | 0.180413E+10 | 0.167354E+09 |
December | 0.116806E+10 | 0.496961E+09 | 0.671103E+09 | 0.222253E+10 | 0.267259E+09 |
Annual Sum or Average | 0.860726E+10 | 0.178372E+10 | 0.682353E+10 | 0.181398E+11 | 0.157450E+10 |
Minimum of Months | 0.487202E+09 | 0.00 | 0.487202E+09 | 0.107786E+10 | 46357489.01 |
Maximum of Months | 0.116866E+10 | 0.496961E+09 | 0.681086E+09 | 0.225428E+10 | 0.267259E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116859E+10 | 0.487546E+09 | 0.681043E+09 | 0.225414E+10 | 0.239092E+09 |
February | 0.896280E+09 | 0.292219E+09 | 0.604061E+09 | 0.185575E+10 | 0.167073E+09 |
March | 0.677198E+09 | 90947175.90 | 0.586250E+09 | 0.155058E+10 | 0.117379E+09 |
April | 0.488599E+09 | 219332.54 | 0.488379E+09 | 0.117348E+10 | 46354559.48 |
May | 0.505229E+09 | 0.00 | 0.505229E+09 | 0.124278E+10 | 59562576.17 |
June | 0.487172E+09 | 0.00 | 0.487172E+09 | 0.119099E+10 | 62433657.42 |
July | 0.518588E+09 | 0.00 | 0.518588E+09 | 0.110835E+10 | 0.120156E+09 |
August | 0.504850E+09 | 780246.48 | 0.504070E+09 | 0.107779E+10 | 94367688.85 |
September | 0.540875E+09 | 17665180.09 | 0.523209E+09 | 0.118453E+10 | 96385938.05 |
October | 0.731207E+09 | 0.116584E+09 | 0.614623E+09 | 0.147390E+10 | 0.137011E+09 |
November | 0.920137E+09 | 0.280720E+09 | 0.639417E+09 | 0.180402E+10 | 0.167344E+09 |
December | 0.116799E+10 | 0.496930E+09 | 0.671061E+09 | 0.222239E+10 | 0.267242E+09 |
Annual Sum or Average | 0.860671E+10 | 0.178361E+10 | 0.682310E+10 | 0.181387E+11 | 0.157440E+10 |
Minimum of Months | 0.487172E+09 | 0.00 | 0.487172E+09 | 0.107779E+10 | 46354559.48 |
Maximum of Months | 0.116859E+10 | 0.496930E+09 | 0.681043E+09 | 0.225414E+10 | 0.267242E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.165918E+10 | 0.583420E+09 | 0.107576E+10 | 0.323548E+10 | 0.451810E+09 |
February | 0.164591E+10 | 0.582448E+09 | 0.106346E+10 | 0.328350E+10 | 0.326458E+09 |
March | 0.204262E+10 | 0.806792E+09 | 0.123583E+10 | 0.414837E+10 | 0.265751E+09 |
April | 0.198650E+10 | 0.760857E+09 | 0.122565E+10 | 0.408548E+10 | 0.124883E+09 |
May | 0.174664E+10 | 0.517446E+09 | 0.122919E+10 | 0.373758E+10 | 0.130579E+09 |
June | 0.183165E+10 | 0.631323E+09 | 0.120032E+10 | 0.385819E+10 | 0.143177E+09 |
July | 0.161362E+10 | 0.380528E+09 | 0.123310E+10 | 0.322719E+10 | 0.254366E+09 |
August | 0.175433E+10 | 0.519532E+09 | 0.123480E+10 | 0.342892E+10 | 0.209281E+09 |
September | 0.159018E+10 | 0.441045E+09 | 0.114914E+10 | 0.320408E+10 | 0.203666E+09 |
October | 0.154328E+10 | 0.397822E+09 | 0.114546E+10 | 0.297221E+10 | 0.265840E+09 |
November | 0.145646E+10 | 0.397219E+09 | 0.105924E+10 | 0.283238E+10 | 0.307446E+09 |
December | 0.154026E+10 | 0.503844E+09 | 0.103641E+10 | 0.299723E+10 | 0.498655E+09 |
Annual Sum or Average | 0.204106E+11 | 0.652228E+10 | 0.138884E+11 | 0.410106E+11 | 0.318191E+10 |
Minimum of Months | 0.145646E+10 | 0.380528E+09 | 0.103641E+10 | 0.283238E+10 | 0.124883E+09 |
Maximum of Months | 0.204262E+10 | 0.806792E+09 | 0.123583E+10 | 0.414837E+10 | 0.498655E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 65602437.25 | 23067840.61 | 42534596.64 | 0.127928E+09 | 17864149.43 |
February | 65077741.83 | 23029397.11 | 42048344.73 | 0.129826E+09 | 12907832.50 |
March | 80763047.15 | 31899713.23 | 48863333.93 | 0.164022E+09 | 10507506.48 |
April | 78544297.43 | 30083496.02 | 48460801.40 | 0.161536E+09 | 4937746.02 |
May | 69060294.15 | 20459295.66 | 48600998.49 | 0.147780E+09 | 5162977.88 |
June | 72421419.08 | 24961851.65 | 47459567.43 | 0.152549E+09 | 5661066.52 |
July | 63801069.82 | 15045695.60 | 48755374.22 | 0.127600E+09 | 10057400.17 |
August | 69364522.02 | 20541760.57 | 48822761.44 | 0.135576E+09 | 8274759.07 |
September | 62874269.26 | 17438479.37 | 45435789.89 | 0.126686E+09 | 8052772.76 |
October | 61019654.69 | 15729478.62 | 45290176.07 | 0.117518E+09 | 10511060.74 |
November | 57586918.36 | 15705636.81 | 41881281.54 | 0.111990E+09 | 12156109.93 |
December | 60900262.54 | 19921492.63 | 40978769.91 | 0.118507E+09 | 19716322.75 |
Annual Sum or Average | 0.807016E+09 | 0.257884E+09 | 0.549132E+09 | 0.162152E+10 | 0.125810E+09 |
Minimum of Months | 57586918.36 | 15045695.60 | 40978769.91 | 0.111990E+09 | 4937746.02 |
Maximum of Months | 80763047.15 | 31899713.23 | 48863333.93 | 0.164022E+09 | 19716322.75 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132422E+10 | 0.00 | 0.132422E+10 | 0.276945E+10 | 0.631691E+09 |
February | 0.127587E+10 | 0.00 | 0.127587E+10 | 0.280233E+10 | 0.442575E+09 |
March | 0.144973E+10 | 0.00 | 0.144973E+10 | 0.337636E+10 | 0.326510E+09 |
April | 0.152680E+10 | 21637656.65 | 0.150517E+10 | 0.366571E+10 | 0.142089E+09 |
May | 0.202242E+10 | 0.215448E+09 | 0.180697E+10 | 0.482211E+10 | 0.176202E+09 |
June | 0.239076E+10 | 0.483154E+09 | 0.190761E+10 | 0.554710E+10 | 0.193113E+09 |
July | 0.212436E+10 | 0.222671E+09 | 0.190169E+10 | 0.451277E+10 | 0.348550E+09 |
August | 0.174904E+10 | 74580343.55 | 0.167446E+10 | 0.376150E+10 | 0.267904E+09 |
September | 0.144108E+10 | 690066.21 | 0.144039E+10 | 0.320956E+10 | 0.256715E+09 |
October | 0.143482E+10 | 0.00 | 0.143482E+10 | 0.295014E+10 | 0.354057E+09 |
November | 0.131386E+10 | 0.00 | 0.131386E+10 | 0.272849E+10 | 0.418959E+09 |
December | 0.128646E+10 | 0.00 | 0.128646E+10 | 0.266521E+10 | 0.693373E+09 |
Annual Sum or Average | 0.193394E+11 | 0.101818E+10 | 0.183212E+11 | 0.428107E+11 | 0.425174E+10 |
Minimum of Months | 0.127587E+10 | 0.00 | 0.127587E+10 | 0.266521E+10 | 0.142089E+09 |
Maximum of Months | 0.239076E+10 | 0.483154E+09 | 0.190761E+10 | 0.554710E+10 | 0.693373E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170231E+10 | 0.573729E+09 | 0.112859E+10 | 0.328148E+10 | 0.397610E+09 |
February | 0.174360E+10 | 0.639290E+09 | 0.110431E+10 | 0.344001E+10 | 0.275536E+09 |
March | 0.210452E+10 | 0.824120E+09 | 0.128040E+10 | 0.425486E+10 | 0.200192E+09 |
April | 0.205833E+10 | 0.786368E+09 | 0.127196E+10 | 0.427641E+10 | 88314305.54 |
May | 0.182829E+10 | 0.553421E+09 | 0.127487E+10 | 0.395615E+10 | 0.111627E+09 |
June | 0.188447E+10 | 0.620645E+09 | 0.126383E+10 | 0.402390E+10 | 0.119242E+09 |
July | 0.166325E+10 | 0.372609E+09 | 0.129064E+10 | 0.334660E+10 | 0.221095E+09 |
August | 0.183044E+10 | 0.538071E+09 | 0.129237E+10 | 0.361729E+10 | 0.173393E+09 |
September | 0.166356E+10 | 0.453326E+09 | 0.121023E+10 | 0.338418E+10 | 0.169603E+09 |
October | 0.161109E+10 | 0.412175E+09 | 0.119892E+10 | 0.311411E+10 | 0.232835E+09 |
November | 0.150892E+10 | 0.416983E+09 | 0.109193E+10 | 0.293328E+10 | 0.273926E+09 |
December | 0.159560E+10 | 0.512044E+09 | 0.108356E+10 | 0.306076E+10 | 0.441527E+09 |
Annual Sum or Average | 0.211944E+11 | 0.670278E+10 | 0.144916E+11 | 0.426890E+11 | 0.270490E+10 |
Minimum of Months | 0.150892E+10 | 0.372609E+09 | 0.108356E+10 | 0.293328E+10 | 88314305.54 |
Maximum of Months | 0.210452E+10 | 0.824120E+09 | 0.129237E+10 | 0.427641E+10 | 0.441527E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.350604E+10 | 0.146276E+10 | 0.204328E+10 | 0.681457E+10 | 0.644963E+09 |
February | 0.268905E+10 | 0.876730E+09 | 0.181232E+10 | 0.562722E+10 | 0.440986E+09 |
March | 0.203174E+10 | 0.272864E+09 | 0.175888E+10 | 0.470407E+10 | 0.314523E+09 |
April | 0.146590E+10 | 658052.64 | 0.146524E+10 | 0.356634E+10 | 0.128366E+09 |
May | 0.151580E+10 | 0.00 | 0.151580E+10 | 0.377789E+10 | 0.162555E+09 |
June | 0.146162E+10 | 0.00 | 0.146162E+10 | 0.363325E+10 | 0.170616E+09 |
July | 0.155588E+10 | 0.00 | 0.155588E+10 | 0.335713E+10 | 0.330639E+09 |
August | 0.151466E+10 | 2340935.21 | 0.151232E+10 | 0.327909E+10 | 0.250149E+09 |
September | 0.162274E+10 | 52999972.44 | 0.156974E+10 | 0.359299E+10 | 0.257777E+09 |
October | 0.219379E+10 | 0.349782E+09 | 0.184401E+10 | 0.444767E+10 | 0.372639E+09 |
November | 0.276063E+10 | 0.842230E+09 | 0.191840E+10 | 0.545477E+10 | 0.445087E+09 |
December | 0.350425E+10 | 0.149091E+10 | 0.201333E+10 | 0.670951E+10 | 0.718581E+09 |
Annual Sum or Average | 0.258221E+11 | 0.535128E+10 | 0.204708E+11 | 0.549645E+11 | 0.423688E+10 |
Minimum of Months | 0.146162E+10 | 0.00 | 0.146162E+10 | 0.327909E+10 | 0.128366E+09 |
Maximum of Months | 0.350604E+10 | 0.149091E+10 | 0.204328E+10 | 0.681457E+10 | 0.718581E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172481E+10 | 0.606498E+09 | 0.111831E+10 | 0.337236E+10 | 0.443149E+09 |
February | 0.171101E+10 | 0.605487E+09 | 0.110552E+10 | 0.342193E+10 | 0.310493E+09 |
March | 0.212341E+10 | 0.838705E+09 | 0.128470E+10 | 0.432077E+10 | 0.244731E+09 |
April | 0.206507E+10 | 0.790953E+09 | 0.127412E+10 | 0.426159E+10 | 0.109160E+09 |
May | 0.181572E+10 | 0.537914E+09 | 0.127781E+10 | 0.390618E+10 | 0.114904E+09 |
June | 0.190409E+10 | 0.656295E+09 | 0.124780E+10 | 0.403116E+10 | 0.124865E+09 |
July | 0.167745E+10 | 0.395580E+09 | 0.128187E+10 | 0.337081E+10 | 0.231049E+09 |
August | 0.182372E+10 | 0.540083E+09 | 0.128364E+10 | 0.358389E+10 | 0.181086E+09 |
September | 0.165308E+10 | 0.458491E+09 | 0.119459E+10 | 0.334954E+10 | 0.179511E+09 |
October | 0.160432E+10 | 0.413558E+09 | 0.119076E+10 | 0.310103E+10 | 0.246804E+09 |
November | 0.151406E+10 | 0.412932E+09 | 0.110113E+10 | 0.295586E+10 | 0.290338E+09 |
December | 0.160118E+10 | 0.523775E+09 | 0.107740E+10 | 0.312735E+10 | 0.480842E+09 |
Annual Sum or Average | 0.212179E+11 | 0.678027E+10 | 0.144376E+11 | 0.428025E+11 | 0.295693E+10 |
Minimum of Months | 0.151406E+10 | 0.395580E+09 | 0.107740E+10 | 0.295586E+10 | 0.109160E+09 |
Maximum of Months | 0.212341E+10 | 0.838705E+09 | 0.128470E+10 | 0.432077E+10 | 0.480842E+09 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1026.31 | 226.01 | 494.41 | 0.00 | 494.41 | 0.00 | 0.00 |
February | 1148.81 | 173.53 | 527.40 | 0.00 | 527.40 | 0.00 | 0.00 |
March | 1247.91 | 117.75 | 541.27 | 0.00 | 541.27 | 0.00 | 0.00 |
April | 1396.68 | 54.25 | 589.04 | 8.35 | 580.70 | 0.00 | 0.00 |
May | 1784.45 | 64.83 | 755.08 | 80.44 | 674.65 | 0.00 | 0.00 |
June | 2123.12 | 75.10 | 922.36 | 186.40 | 735.96 | 0.00 | 0.00 |
July | 1670.20 | 127.57 | 793.14 | 83.14 | 710.01 | 0.00 | 0.00 |
August | 1393.81 | 96.66 | 653.02 | 27.85 | 625.17 | 0.00 | 0.00 |
September | 1224.78 | 97.65 | 555.97 | 0.27 | 555.71 | 0.00 | 0.00 |
October | 1091.33 | 128.23 | 535.70 | 0.00 | 535.70 | 0.00 | 0.00 |
November | 1043.89 | 153.47 | 506.89 | 0.00 | 506.89 | 0.00 | 0.00 |
December | 988.92 | 245.81 | 480.31 | 0.00 | 480.31 | 0.00 | 0.00 |
Annual Sum or Average | 1345.51 | 130.10 | 613.25 | 32.29 | 580.96 | 0.00 | 0.00 |
Minimum of Months | 988.92 | 54.25 | 480.31 | 0.00 | 480.31 | 0.00 | 0.00 |
Maximum of Months | 2123.12 | 245.81 | 922.36 | 186.40 | 735.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1219.05 | 142.67 | 635.57 | 214.21 | 421.37 | 0.00 | 0.00 |
February | 1414.26 | 107.76 | 720.73 | 264.26 | 456.48 | 0.00 | 0.00 |
March | 1578.07 | 71.48 | 785.74 | 307.69 | 478.05 | 0.00 | 0.00 |
April | 1637.12 | 33.39 | 794.11 | 303.38 | 490.73 | 0.00 | 0.00 |
May | 1466.15 | 40.95 | 682.61 | 206.62 | 475.98 | 0.00 | 0.00 |
June | 1540.74 | 46.37 | 727.03 | 239.45 | 487.59 | 0.00 | 0.00 |
July | 1239.89 | 80.73 | 620.99 | 139.12 | 481.87 | 0.00 | 0.00 |
August | 1342.97 | 62.49 | 683.41 | 200.89 | 482.51 | 0.00 | 0.00 |
September | 1296.12 | 64.51 | 641.80 | 174.89 | 466.91 | 0.00 | 0.00 |
October | 1155.08 | 84.32 | 601.51 | 153.89 | 447.62 | 0.00 | 0.00 |
November | 1124.82 | 100.58 | 582.14 | 160.87 | 421.27 | 0.00 | 0.00 |
December | 1137.96 | 157.17 | 595.73 | 191.18 | 404.55 | 0.00 | 0.00 |
Annual Sum or Average | 1344.87 | 82.73 | 672.07 | 212.54 | 459.53 | 0.00 | 0.00 |
Minimum of Months | 1124.82 | 33.39 | 582.14 | 139.12 | 404.55 | 0.00 | 0.00 |
Maximum of Months | 1637.12 | 157.17 | 794.11 | 307.69 | 490.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2536.90 | 232.11 | 1309.01 | 546.13 | 762.87 | 0.00 | 0.00 |
February | 2315.60 | 173.23 | 1111.54 | 362.41 | 749.14 | 0.00 | 0.00 |
March | 1742.58 | 112.63 | 758.57 | 101.88 | 656.69 | 0.00 | 0.00 |
April | 1358.77 | 48.57 | 565.55 | 0.25 | 565.29 | 0.00 | 0.00 |
May | 1395.30 | 59.38 | 565.93 | 0.00 | 565.93 | 0.00 | 0.00 |
June | 1385.62 | 65.95 | 563.90 | 0.00 | 563.90 | 0.00 | 0.00 |
July | 1239.54 | 120.58 | 580.90 | 0.00 | 580.90 | 0.00 | 0.00 |
August | 1213.89 | 89.43 | 565.51 | 0.87 | 564.63 | 0.00 | 0.00 |
September | 1372.30 | 97.91 | 626.06 | 20.45 | 605.61 | 0.00 | 0.00 |
October | 1649.20 | 135.38 | 819.07 | 130.59 | 688.47 | 0.00 | 0.00 |
November | 2094.48 | 164.23 | 1065.06 | 324.93 | 740.12 | 0.00 | 0.00 |
December | 2499.45 | 257.05 | 1308.34 | 556.64 | 751.69 | 0.00 | 0.00 |
Annual Sum or Average | 1730.83 | 129.74 | 818.81 | 169.69 | 649.12 | 0.00 | 0.00 |
Minimum of Months | 1213.89 | 48.57 | 563.90 | 0.00 | 563.90 | 0.00 | 0.00 |
Maximum of Months | 2536.90 | 257.05 | 1309.01 | 556.64 | 762.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1255.42 | 157.71 | 643.97 | 226.44 | 417.53 | 0.00 | 0.00 |
February | 1408.91 | 120.59 | 707.26 | 250.28 | 456.98 | 0.00 | 0.00 |
March | 1605.26 | 87.57 | 792.79 | 313.14 | 479.65 | 0.00 | 0.00 |
April | 1634.09 | 41.02 | 796.71 | 305.15 | 491.56 | 0.00 | 0.00 |
May | 1449.90 | 41.39 | 677.91 | 200.83 | 477.08 | 0.00 | 0.00 |
June | 1545.27 | 47.63 | 734.60 | 253.20 | 481.40 | 0.00 | 0.00 |
July | 1250.71 | 82.92 | 626.29 | 147.69 | 478.59 | 0.00 | 0.00 |
August | 1332.10 | 64.01 | 680.90 | 201.64 | 479.26 | 0.00 | 0.00 |
September | 1284.59 | 67.34 | 637.76 | 176.89 | 460.87 | 0.00 | 0.00 |
October | 1152.67 | 88.19 | 598.98 | 154.41 | 444.58 | 0.00 | 0.00 |
November | 1136.06 | 105.35 | 584.13 | 159.31 | 424.82 | 0.00 | 0.00 |
December | 1165.05 | 169.37 | 597.81 | 195.56 | 402.26 | 0.00 | 0.00 |
Annual Sum or Average | 1350.67 | 89.43 | 672.82 | 215.00 | 457.81 | 0.00 | 0.00 |
Minimum of Months | 1136.06 | 41.02 | 584.13 | 147.69 | 402.26 | 0.00 | 0.00 |
Maximum of Months | 1634.09 | 169.37 | 796.71 | 313.14 | 491.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1031.73 | 238.33 | 494.40 | 0.00 | 494.40 | 0.00 | 0.00 |
February | 1156.14 | 186.51 | 527.38 | 0.00 | 527.38 | 0.00 | 0.00 |
March | 1257.63 | 124.31 | 541.26 | 0.00 | 541.26 | 0.00 | 0.00 |
April | 1410.40 | 56.21 | 589.03 | 8.35 | 580.68 | 0.00 | 0.00 |
May | 1794.63 | 72.36 | 755.07 | 80.44 | 674.63 | 0.00 | 0.00 |
June | 2131.51 | 84.40 | 922.34 | 186.40 | 735.94 | 0.00 | 0.00 |
July | 1679.08 | 143.17 | 793.12 | 83.13 | 709.99 | 0.00 | 0.00 |
August | 1395.69 | 111.51 | 653.00 | 27.84 | 625.16 | 0.00 | 0.00 |
September | 1230.32 | 107.77 | 555.96 | 0.27 | 555.69 | 0.00 | 0.00 |
October | 1098.86 | 137.64 | 535.69 | 0.00 | 535.69 | 0.00 | 0.00 |
November | 1049.93 | 167.86 | 506.88 | 0.00 | 506.88 | 0.00 | 0.00 |
December | 991.27 | 266.80 | 480.30 | 0.00 | 480.30 | 0.00 | 0.00 |
Annual Sum or Average | 1352.75 | 141.44 | 613.24 | 32.29 | 580.95 | 0.00 | 0.00 |
Minimum of Months | 991.27 | 56.21 | 480.30 | 0.00 | 480.30 | 0.00 | 0.00 |
Maximum of Months | 2131.51 | 266.80 | 922.34 | 186.40 | 735.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1222.13 | 157.99 | 635.56 | 214.20 | 421.36 | 0.00 | 0.00 |
February | 1418.52 | 124.98 | 720.72 | 264.25 | 456.47 | 0.00 | 0.00 |
March | 1585.88 | 86.11 | 785.73 | 307.69 | 478.04 | 0.00 | 0.00 |
April | 1643.71 | 41.07 | 794.10 | 303.38 | 490.72 | 0.00 | 0.00 |
May | 1469.12 | 48.48 | 682.60 | 206.62 | 475.98 | 0.00 | 0.00 |
June | 1544.72 | 54.25 | 727.02 | 239.44 | 487.58 | 0.00 | 0.00 |
July | 1243.45 | 93.84 | 620.98 | 139.11 | 481.86 | 0.00 | 0.00 |
August | 1343.50 | 77.49 | 683.40 | 200.89 | 482.51 | 0.00 | 0.00 |
September | 1298.45 | 77.56 | 641.79 | 174.89 | 466.90 | 0.00 | 0.00 |
October | 1159.46 | 97.44 | 601.50 | 153.89 | 447.62 | 0.00 | 0.00 |
November | 1128.45 | 116.80 | 582.13 | 160.87 | 421.26 | 0.00 | 0.00 |
December | 1139.45 | 177.95 | 595.72 | 191.17 | 404.55 | 0.00 | 0.00 |
Annual Sum or Average | 1348.58 | 96.19 | 672.06 | 212.54 | 459.52 | 0.00 | 0.00 |
Minimum of Months | 1128.45 | 41.07 | 582.13 | 139.11 | 404.55 | 0.00 | 0.00 |
Maximum of Months | 1643.71 | 177.95 | 794.10 | 307.69 | 490.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2524.90 | 267.81 | 1308.96 | 546.11 | 762.85 | 0.00 | 0.00 |
February | 2301.37 | 207.19 | 1111.50 | 362.39 | 749.11 | 0.00 | 0.00 |
March | 1736.84 | 131.48 | 758.54 | 101.87 | 656.67 | 0.00 | 0.00 |
April | 1358.25 | 53.65 | 565.53 | 0.25 | 565.28 | 0.00 | 0.00 |
May | 1392.06 | 66.72 | 565.92 | 0.00 | 565.92 | 0.00 | 0.00 |
June | 1378.52 | 72.26 | 563.88 | 0.00 | 563.88 | 0.00 | 0.00 |
July | 1241.49 | 134.59 | 580.88 | 0.00 | 580.88 | 0.00 | 0.00 |
August | 1207.26 | 105.70 | 565.49 | 0.87 | 564.62 | 0.00 | 0.00 |
September | 1371.04 | 111.56 | 626.04 | 20.45 | 605.59 | 0.00 | 0.00 |
October | 1650.94 | 153.47 | 819.04 | 130.59 | 688.45 | 0.00 | 0.00 |
November | 2088.07 | 193.69 | 1065.02 | 324.92 | 740.10 | 0.00 | 0.00 |
December | 2489.34 | 299.34 | 1308.29 | 556.62 | 751.67 | 0.00 | 0.00 |
Annual Sum or Average | 1725.60 | 149.78 | 818.79 | 169.68 | 649.10 | 0.00 | 0.00 |
Minimum of Months | 1207.26 | 53.65 | 563.88 | 0.00 | 563.88 | 0.00 | 0.00 |
Maximum of Months | 2524.90 | 299.34 | 1308.96 | 556.62 | 762.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1255.75 | 175.36 | 643.96 | 226.44 | 417.52 | 0.00 | 0.00 |
February | 1410.93 | 140.28 | 707.25 | 250.28 | 456.97 | 0.00 | 0.00 |
March | 1610.06 | 103.14 | 792.78 | 313.13 | 479.65 | 0.00 | 0.00 |
April | 1638.51 | 50.09 | 796.70 | 305.15 | 491.55 | 0.00 | 0.00 |
May | 1450.63 | 50.68 | 677.90 | 200.83 | 477.07 | 0.00 | 0.00 |
June | 1547.35 | 57.42 | 734.59 | 253.20 | 481.40 | 0.00 | 0.00 |
July | 1252.54 | 98.72 | 626.28 | 147.69 | 478.59 | 0.00 | 0.00 |
August | 1330.83 | 81.23 | 680.89 | 201.64 | 479.25 | 0.00 | 0.00 |
September | 1285.02 | 81.68 | 637.75 | 176.88 | 460.87 | 0.00 | 0.00 |
October | 1153.57 | 103.18 | 598.98 | 154.40 | 444.57 | 0.00 | 0.00 |
November | 1135.95 | 123.30 | 584.12 | 159.31 | 424.82 | 0.00 | 0.00 |
December | 1163.28 | 193.54 | 597.80 | 195.55 | 402.25 | 0.00 | 0.00 |
Annual Sum or Average | 1351.86 | 104.89 | 672.81 | 215.00 | 457.81 | 0.00 | 0.00 |
Minimum of Months | 1135.95 | 50.09 | 584.12 | 147.69 | 402.25 | 0.00 | 0.00 |
Maximum of Months | 1638.51 | 193.54 | 796.70 | 313.13 | 491.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1033.99 | 235.85 | 494.41 | 0.00 | 494.41 | 0.00 | 0.00 |
February | 1158.37 | 182.94 | 527.40 | 0.00 | 527.40 | 0.00 | 0.00 |
March | 1260.59 | 121.90 | 541.27 | 0.00 | 541.27 | 0.00 | 0.00 |
April | 1414.24 | 54.82 | 589.04 | 8.35 | 580.70 | 0.00 | 0.00 |
May | 1800.37 | 65.79 | 755.08 | 80.44 | 674.65 | 0.00 | 0.00 |
June | 2140.09 | 74.50 | 922.36 | 186.40 | 735.96 | 0.00 | 0.00 |
July | 1684.87 | 130.13 | 793.14 | 83.14 | 710.01 | 0.00 | 0.00 |
August | 1404.38 | 100.02 | 653.02 | 27.85 | 625.17 | 0.00 | 0.00 |
September | 1238.26 | 99.04 | 555.97 | 0.27 | 555.71 | 0.00 | 0.00 |
October | 1101.45 | 132.19 | 535.70 | 0.00 | 535.70 | 0.00 | 0.00 |
November | 1052.66 | 161.64 | 506.89 | 0.00 | 506.89 | 0.00 | 0.00 |
December | 995.08 | 258.88 | 480.31 | 0.00 | 480.31 | 0.00 | 0.00 |
Annual Sum or Average | 1357.52 | 134.82 | 613.25 | 32.29 | 580.96 | 0.00 | 0.00 |
Minimum of Months | 995.08 | 54.82 | 480.31 | 0.00 | 480.31 | 0.00 | 0.00 |
Maximum of Months | 2140.09 | 258.88 | 922.36 | 186.40 | 735.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1225.16 | 148.45 | 635.57 | 214.21 | 421.37 | 0.00 | 0.00 |
February | 1421.96 | 113.90 | 720.73 | 264.26 | 456.48 | 0.00 | 0.00 |
March | 1588.58 | 74.74 | 785.74 | 307.69 | 478.05 | 0.00 | 0.00 |
April | 1649.85 | 34.07 | 794.11 | 303.38 | 490.73 | 0.00 | 0.00 |
May | 1477.06 | 41.68 | 682.61 | 206.62 | 475.98 | 0.00 | 0.00 |
June | 1552.43 | 46.00 | 727.03 | 239.45 | 487.59 | 0.00 | 0.00 |
July | 1249.48 | 82.55 | 620.99 | 139.12 | 481.87 | 0.00 | 0.00 |
August | 1350.54 | 64.74 | 683.41 | 200.89 | 482.51 | 0.00 | 0.00 |
September | 1305.62 | 65.43 | 641.80 | 174.89 | 466.91 | 0.00 | 0.00 |
October | 1162.68 | 86.93 | 601.51 | 153.89 | 447.62 | 0.00 | 0.00 |
November | 1131.67 | 105.68 | 582.14 | 160.87 | 421.27 | 0.00 | 0.00 |
December | 1142.76 | 164.85 | 595.73 | 191.18 | 404.55 | 0.00 | 0.00 |
Annual Sum or Average | 1353.66 | 85.77 | 672.07 | 212.54 | 459.53 | 0.00 | 0.00 |
Minimum of Months | 1131.67 | 34.07 | 582.14 | 139.12 | 404.55 | 0.00 | 0.00 |
Maximum of Months | 1649.85 | 164.85 | 794.11 | 307.69 | 490.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2544.27 | 240.80 | 1309.01 | 546.13 | 762.87 | 0.00 | 0.00 |
February | 2326.06 | 182.29 | 1111.54 | 362.41 | 749.14 | 0.00 | 0.00 |
March | 1756.30 | 117.43 | 758.57 | 101.88 | 656.69 | 0.00 | 0.00 |
April | 1375.90 | 49.52 | 565.55 | 0.25 | 565.29 | 0.00 | 0.00 |
May | 1410.50 | 60.69 | 565.93 | 0.00 | 565.93 | 0.00 | 0.00 |
June | 1401.72 | 65.82 | 563.90 | 0.00 | 563.90 | 0.00 | 0.00 |
July | 1253.41 | 123.45 | 580.90 | 0.00 | 580.90 | 0.00 | 0.00 |
August | 1224.27 | 93.40 | 565.51 | 0.87 | 564.63 | 0.00 | 0.00 |
September | 1386.18 | 99.45 | 626.06 | 20.45 | 605.61 | 0.00 | 0.00 |
October | 1660.57 | 139.13 | 819.07 | 130.59 | 688.47 | 0.00 | 0.00 |
November | 2104.46 | 171.72 | 1065.06 | 324.93 | 740.12 | 0.00 | 0.00 |
December | 2505.04 | 268.29 | 1308.34 | 556.64 | 751.69 | 0.00 | 0.00 |
Annual Sum or Average | 1742.91 | 134.35 | 818.81 | 169.69 | 649.12 | 0.00 | 0.00 |
Minimum of Months | 1224.27 | 49.52 | 563.90 | 0.00 | 563.90 | 0.00 | 0.00 |
Maximum of Months | 2544.27 | 268.29 | 1309.01 | 556.64 | 762.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1259.09 | 165.45 | 643.97 | 226.44 | 417.53 | 0.00 | 0.00 |
February | 1414.49 | 128.35 | 707.26 | 250.28 | 456.98 | 0.00 | 0.00 |
March | 1613.19 | 91.37 | 792.79 | 313.14 | 479.65 | 0.00 | 0.00 |
April | 1644.13 | 42.11 | 796.71 | 305.15 | 491.56 | 0.00 | 0.00 |
May | 1458.40 | 42.90 | 677.91 | 200.83 | 477.08 | 0.00 | 0.00 |
June | 1555.23 | 48.17 | 734.60 | 253.20 | 481.40 | 0.00 | 0.00 |
July | 1258.52 | 86.26 | 626.29 | 147.69 | 478.59 | 0.00 | 0.00 |
August | 1338.07 | 67.61 | 680.90 | 201.64 | 479.26 | 0.00 | 0.00 |
September | 1292.26 | 69.26 | 637.76 | 176.89 | 460.87 | 0.00 | 0.00 |
October | 1157.79 | 92.15 | 598.98 | 154.41 | 444.58 | 0.00 | 0.00 |
November | 1140.38 | 112.01 | 584.13 | 159.31 | 424.82 | 0.00 | 0.00 |
December | 1167.62 | 179.53 | 597.81 | 195.56 | 402.26 | 0.00 | 0.00 |
Annual Sum or Average | 1357.26 | 93.76 | 672.82 | 215.00 | 457.81 | 0.00 | 0.00 |
Minimum of Months | 1140.38 | 42.11 | 584.13 | 147.69 | 402.26 | 0.00 | 0.00 |
Maximum of Months | 1644.13 | 179.53 | 796.71 | 313.14 | 491.56 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.274887E+10 | 0.605335E+09 | 0.132422E+10 | 0.00 | 0.132422E+10 | 0.00 | 0.00 |
February | 0.277920E+10 | 0.419816E+09 | 0.127587E+10 | 0.00 | 0.127587E+10 | 0.00 | 0.00 |
March | 0.334240E+10 | 0.315388E+09 | 0.144973E+10 | 0.00 | 0.144973E+10 | 0.00 | 0.00 |
April | 0.362021E+10 | 0.140612E+09 | 0.152680E+10 | 21637656.65 | 0.150517E+10 | 0.00 | 0.00 |
May | 0.477948E+10 | 0.173653E+09 | 0.202242E+10 | 0.215448E+09 | 0.180697E+10 | 0.00 | 0.00 |
June | 0.550314E+10 | 0.194654E+09 | 0.239076E+10 | 0.483154E+09 | 0.190761E+10 | 0.00 | 0.00 |
July | 0.447347E+10 | 0.341680E+09 | 0.212436E+10 | 0.222671E+09 | 0.190169E+10 | 0.00 | 0.00 |
August | 0.373318E+10 | 0.258883E+09 | 0.174904E+10 | 74580343.55 | 0.167446E+10 | 0.00 | 0.00 |
September | 0.317462E+10 | 0.253098E+09 | 0.144108E+10 | 690066.21 | 0.144039E+10 | 0.00 | 0.00 |
October | 0.292303E+10 | 0.343443E+09 | 0.143482E+10 | 0.00 | 0.143482E+10 | 0.00 | 0.00 |
November | 0.270576E+10 | 0.397797E+09 | 0.131386E+10 | 0.00 | 0.131386E+10 | 0.00 | 0.00 |
December | 0.264872E+10 | 0.658367E+09 | 0.128646E+10 | 0.00 | 0.128646E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.424321E+11 | 0.410273E+10 | 0.193394E+11 | 0.101818E+10 | 0.183212E+11 | 0.00 | 0.00 |
Minimum of Months | 0.264872E+10 | 0.140612E+09 | 0.127587E+10 | 0.00 | 0.127587E+10 | 0.00 | 0.00 |
Maximum of Months | 0.550314E+10 | 0.658367E+09 | 0.239076E+10 | 0.483154E+09 | 0.190761E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.326511E+10 | 0.382114E+09 | 0.170231E+10 | 0.573729E+09 | 0.112859E+10 | 0.00 | 0.00 |
February | 0.342139E+10 | 0.260705E+09 | 0.174360E+10 | 0.639290E+09 | 0.110431E+10 | 0.00 | 0.00 |
March | 0.422670E+10 | 0.191448E+09 | 0.210452E+10 | 0.824120E+09 | 0.128040E+10 | 0.00 | 0.00 |
April | 0.424342E+10 | 86554402.38 | 0.205833E+10 | 0.786368E+09 | 0.127196E+10 | 0.00 | 0.00 |
May | 0.392694E+10 | 0.109689E+09 | 0.182829E+10 | 0.553421E+09 | 0.127487E+10 | 0.00 | 0.00 |
June | 0.399360E+10 | 0.120194E+09 | 0.188447E+10 | 0.620645E+09 | 0.126383E+10 | 0.00 | 0.00 |
July | 0.332091E+10 | 0.216238E+09 | 0.166325E+10 | 0.372609E+09 | 0.129064E+10 | 0.00 | 0.00 |
August | 0.359701E+10 | 0.167367E+09 | 0.183044E+10 | 0.538071E+09 | 0.129237E+10 | 0.00 | 0.00 |
September | 0.335955E+10 | 0.167215E+09 | 0.166356E+10 | 0.453326E+09 | 0.121023E+10 | 0.00 | 0.00 |
October | 0.309376E+10 | 0.225855E+09 | 0.161109E+10 | 0.412175E+09 | 0.119892E+10 | 0.00 | 0.00 |
November | 0.291554E+10 | 0.260703E+09 | 0.150892E+10 | 0.416983E+09 | 0.109193E+10 | 0.00 | 0.00 |
December | 0.304791E+10 | 0.420976E+09 | 0.159560E+10 | 0.512044E+09 | 0.108356E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.424118E+11 | 0.260906E+10 | 0.211944E+11 | 0.670278E+10 | 0.144916E+11 | 0.00 | 0.00 |
Minimum of Months | 0.291554E+10 | 86554402.38 | 0.150892E+10 | 0.372609E+09 | 0.108356E+10 | 0.00 | 0.00 |
Maximum of Months | 0.424342E+10 | 0.420976E+09 | 0.210452E+10 | 0.824120E+09 | 0.129237E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.679483E+10 | 0.621688E+09 | 0.350604E+10 | 0.146276E+10 | 0.204328E+10 | 0.00 | 0.00 |
February | 0.560189E+10 | 0.419068E+09 | 0.268905E+10 | 0.876730E+09 | 0.181232E+10 | 0.00 | 0.00 |
March | 0.466732E+10 | 0.301659E+09 | 0.203174E+10 | 0.272864E+09 | 0.175888E+10 | 0.00 | 0.00 |
April | 0.352194E+10 | 0.125891E+09 | 0.146590E+10 | 658052.64 | 0.146524E+10 | 0.00 | 0.00 |
May | 0.373716E+10 | 0.159034E+09 | 0.151580E+10 | 0.00 | 0.151580E+10 | 0.00 | 0.00 |
June | 0.359153E+10 | 0.170937E+09 | 0.146162E+10 | 0.00 | 0.146162E+10 | 0.00 | 0.00 |
July | 0.331998E+10 | 0.322965E+09 | 0.155588E+10 | 0.00 | 0.155588E+10 | 0.00 | 0.00 |
August | 0.325128E+10 | 0.239542E+09 | 0.151466E+10 | 2340935.21 | 0.151232E+10 | 0.00 | 0.00 |
September | 0.355701E+10 | 0.253795E+09 | 0.162274E+10 | 52999972.44 | 0.156974E+10 | 0.00 | 0.00 |
October | 0.441721E+10 | 0.362612E+09 | 0.219379E+10 | 0.349782E+09 | 0.184401E+10 | 0.00 | 0.00 |
November | 0.542890E+10 | 0.425692E+09 | 0.276063E+10 | 0.842230E+09 | 0.191840E+10 | 0.00 | 0.00 |
December | 0.669453E+10 | 0.688488E+09 | 0.350425E+10 | 0.149091E+10 | 0.201333E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.545836E+11 | 0.409137E+10 | 0.258221E+11 | 0.535128E+10 | 0.204708E+11 | 0.00 | 0.00 |
Minimum of Months | 0.325128E+10 | 0.125891E+09 | 0.146162E+10 | 0.00 | 0.146162E+10 | 0.00 | 0.00 |
Maximum of Months | 0.679483E+10 | 0.688488E+09 | 0.350604E+10 | 0.149091E+10 | 0.204328E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.336251E+10 | 0.422413E+09 | 0.172481E+10 | 0.606498E+09 | 0.111831E+10 | 0.00 | 0.00 |
February | 0.340842E+10 | 0.291730E+09 | 0.171101E+10 | 0.605487E+09 | 0.110552E+10 | 0.00 | 0.00 |
March | 0.429953E+10 | 0.234554E+09 | 0.212341E+10 | 0.838705E+09 | 0.128470E+10 | 0.00 | 0.00 |
April | 0.423555E+10 | 0.106335E+09 | 0.206507E+10 | 0.790953E+09 | 0.127412E+10 | 0.00 | 0.00 |
May | 0.388342E+10 | 0.110849E+09 | 0.181572E+10 | 0.537914E+09 | 0.127781E+10 | 0.00 | 0.00 |
June | 0.400533E+10 | 0.123462E+09 | 0.190409E+10 | 0.656295E+09 | 0.124780E+10 | 0.00 | 0.00 |
July | 0.334990E+10 | 0.222088E+09 | 0.167745E+10 | 0.395580E+09 | 0.128187E+10 | 0.00 | 0.00 |
August | 0.356790E+10 | 0.171457E+09 | 0.182372E+10 | 0.540083E+09 | 0.128364E+10 | 0.00 | 0.00 |
September | 0.332967E+10 | 0.174551E+09 | 0.165308E+10 | 0.458491E+09 | 0.119459E+10 | 0.00 | 0.00 |
October | 0.308731E+10 | 0.236215E+09 | 0.160432E+10 | 0.413558E+09 | 0.119076E+10 | 0.00 | 0.00 |
November | 0.294466E+10 | 0.273066E+09 | 0.151406E+10 | 0.412932E+09 | 0.110113E+10 | 0.00 | 0.00 |
December | 0.312046E+10 | 0.453648E+09 | 0.160118E+10 | 0.523775E+09 | 0.107740E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.425947E+11 | 0.282037E+10 | 0.212179E+11 | 0.678027E+10 | 0.144376E+11 | 0.00 | 0.00 |
Minimum of Months | 0.294466E+10 | 0.106335E+09 | 0.151406E+10 | 0.395580E+09 | 0.107740E+10 | 0.00 | 0.00 |
Maximum of Months | 0.429953E+10 | 0.453648E+09 | 0.212341E+10 | 0.838705E+09 | 0.128470E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.276338E+10 | 0.638336E+09 | 0.132419E+10 | 0.00 | 0.132419E+10 | 0.00 | 0.00 |
February | 0.279693E+10 | 0.451202E+09 | 0.127585E+10 | 0.00 | 0.127585E+10 | 0.00 | 0.00 |
March | 0.336845E+10 | 0.332962E+09 | 0.144971E+10 | 0.00 | 0.144971E+10 | 0.00 | 0.00 |
April | 0.365576E+10 | 0.145701E+09 | 0.152677E+10 | 21637020.66 | 0.150513E+10 | 0.00 | 0.00 |
May | 0.480673E+10 | 0.193800E+09 | 0.202237E+10 | 0.215442E+09 | 0.180693E+10 | 0.00 | 0.00 |
June | 0.552488E+10 | 0.218763E+09 | 0.239070E+10 | 0.483140E+09 | 0.190756E+10 | 0.00 | 0.00 |
July | 0.449725E+10 | 0.383457E+09 | 0.212431E+10 | 0.222664E+09 | 0.190164E+10 | 0.00 | 0.00 |
August | 0.373823E+10 | 0.298669E+09 | 0.174900E+10 | 74578151.43 | 0.167442E+10 | 0.00 | 0.00 |
September | 0.318899E+10 | 0.279338E+09 | 0.144105E+10 | 690045.93 | 0.144036E+10 | 0.00 | 0.00 |
October | 0.294318E+10 | 0.368643E+09 | 0.143479E+10 | 0.00 | 0.143479E+10 | 0.00 | 0.00 |
November | 0.272142E+10 | 0.435095E+09 | 0.131383E+10 | 0.00 | 0.131383E+10 | 0.00 | 0.00 |
December | 0.265503E+10 | 0.714600E+09 | 0.128643E+10 | 0.00 | 0.128643E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.426602E+11 | 0.446057E+10 | 0.193390E+11 | 0.101815E+10 | 0.183208E+11 | 0.00 | 0.00 |
Minimum of Months | 0.265503E+10 | 0.145701E+09 | 0.127585E+10 | 0.00 | 0.127585E+10 | 0.00 | 0.00 |
Maximum of Months | 0.552488E+10 | 0.714600E+09 | 0.239070E+10 | 0.483140E+09 | 0.190756E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.327336E+10 | 0.423149E+09 | 0.170229E+10 | 0.573717E+09 | 0.112857E+10 | 0.00 | 0.00 |
February | 0.343169E+10 | 0.302344E+09 | 0.174357E+10 | 0.639278E+09 | 0.110430E+10 | 0.00 | 0.00 |
March | 0.424762E+10 | 0.230629E+09 | 0.210449E+10 | 0.824104E+09 | 0.128038E+10 | 0.00 | 0.00 |
April | 0.426050E+10 | 0.106449E+09 | 0.205830E+10 | 0.786352E+09 | 0.127194E+10 | 0.00 | 0.00 |
May | 0.393489E+10 | 0.129842E+09 | 0.182826E+10 | 0.553410E+09 | 0.127485E+10 | 0.00 | 0.00 |
June | 0.400391E+10 | 0.140623E+09 | 0.188444E+10 | 0.620633E+09 | 0.126381E+10 | 0.00 | 0.00 |
July | 0.333046E+10 | 0.251337E+09 | 0.166323E+10 | 0.372602E+09 | 0.129062E+10 | 0.00 | 0.00 |
August | 0.359844E+10 | 0.207550E+09 | 0.183041E+10 | 0.538061E+09 | 0.129235E+10 | 0.00 | 0.00 |
September | 0.336557E+10 | 0.201041E+09 | 0.166353E+10 | 0.453317E+09 | 0.121021E+10 | 0.00 | 0.00 |
October | 0.310550E+10 | 0.260978E+09 | 0.161107E+10 | 0.412167E+09 | 0.119890E+10 | 0.00 | 0.00 |
November | 0.292494E+10 | 0.302754E+09 | 0.150889E+10 | 0.416975E+09 | 0.109192E+10 | 0.00 | 0.00 |
December | 0.305190E+10 | 0.476615E+09 | 0.159558E+10 | 0.512034E+09 | 0.108354E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.425288E+11 | 0.303331E+10 | 0.211941E+11 | 0.670265E+10 | 0.144914E+11 | 0.00 | 0.00 |
Minimum of Months | 0.292494E+10 | 0.106449E+09 | 0.150889E+10 | 0.372602E+09 | 0.108354E+10 | 0.00 | 0.00 |
Maximum of Months | 0.426050E+10 | 0.476615E+09 | 0.210449E+10 | 0.824104E+09 | 0.129235E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.676269E+10 | 0.717306E+09 | 0.350591E+10 | 0.146270E+10 | 0.204321E+10 | 0.00 | 0.00 |
February | 0.556748E+10 | 0.501241E+09 | 0.268895E+10 | 0.876694E+09 | 0.181226E+10 | 0.00 | 0.00 |
March | 0.465194E+10 | 0.352153E+09 | 0.203168E+10 | 0.272853E+09 | 0.175883E+10 | 0.00 | 0.00 |
April | 0.352059E+10 | 0.139070E+09 | 0.146586E+10 | 658025.33 | 0.146520E+10 | 0.00 | 0.00 |
May | 0.372849E+10 | 0.178695E+09 | 0.151575E+10 | 0.00 | 0.151575E+10 | 0.00 | 0.00 |
June | 0.357313E+10 | 0.187309E+09 | 0.146158E+10 | 0.00 | 0.146158E+10 | 0.00 | 0.00 |
July | 0.332520E+10 | 0.360484E+09 | 0.155583E+10 | 0.00 | 0.155583E+10 | 0.00 | 0.00 |
August | 0.323352E+10 | 0.283115E+09 | 0.151461E+10 | 2340838.06 | 0.151227E+10 | 0.00 | 0.00 |
September | 0.355375E+10 | 0.289170E+09 | 0.162269E+10 | 52997773.08 | 0.156969E+10 | 0.00 | 0.00 |
October | 0.442188E+10 | 0.411050E+09 | 0.219371E+10 | 0.349768E+09 | 0.184395E+10 | 0.00 | 0.00 |
November | 0.541228E+10 | 0.502052E+09 | 0.276053E+10 | 0.842195E+09 | 0.191833E+10 | 0.00 | 0.00 |
December | 0.666744E+10 | 0.801760E+09 | 0.350412E+10 | 0.149085E+10 | 0.201327E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.544184E+11 | 0.472340E+10 | 0.258212E+11 | 0.535106E+10 | 0.204702E+11 | 0.00 | 0.00 |
Minimum of Months | 0.323352E+10 | 0.139070E+09 | 0.146158E+10 | 0.00 | 0.146158E+10 | 0.00 | 0.00 |
Maximum of Months | 0.676269E+10 | 0.801760E+09 | 0.350591E+10 | 0.149085E+10 | 0.204321E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.336341E+10 | 0.469675E+09 | 0.172479E+10 | 0.606488E+09 | 0.111830E+10 | 0.00 | 0.00 |
February | 0.341333E+10 | 0.339366E+09 | 0.171099E+10 | 0.605477E+09 | 0.110551E+10 | 0.00 | 0.00 |
March | 0.431239E+10 | 0.276258E+09 | 0.212338E+10 | 0.838691E+09 | 0.128469E+10 | 0.00 | 0.00 |
April | 0.424702E+10 | 0.129821E+09 | 0.206505E+10 | 0.790940E+09 | 0.127411E+10 | 0.00 | 0.00 |
May | 0.388536E+10 | 0.135742E+09 | 0.181570E+10 | 0.537906E+09 | 0.127779E+10 | 0.00 | 0.00 |
June | 0.401074E+10 | 0.148838E+09 | 0.190407E+10 | 0.656285E+09 | 0.124778E+10 | 0.00 | 0.00 |
July | 0.335479E+10 | 0.264424E+09 | 0.167743E+10 | 0.395574E+09 | 0.128185E+10 | 0.00 | 0.00 |
August | 0.356449E+10 | 0.217556E+09 | 0.182370E+10 | 0.540074E+09 | 0.128362E+10 | 0.00 | 0.00 |
September | 0.333077E+10 | 0.211719E+09 | 0.165306E+10 | 0.458484E+09 | 0.119457E+10 | 0.00 | 0.00 |
October | 0.308973E+10 | 0.276351E+09 | 0.160430E+10 | 0.413552E+09 | 0.119075E+10 | 0.00 | 0.00 |
November | 0.294437E+10 | 0.319602E+09 | 0.151405E+10 | 0.412925E+09 | 0.110112E+10 | 0.00 | 0.00 |
December | 0.311573E+10 | 0.518371E+09 | 0.160116E+10 | 0.523766E+09 | 0.107739E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.426321E+11 | 0.330772E+10 | 0.212176E+11 | 0.678016E+10 | 0.144375E+11 | 0.00 | 0.00 |
Minimum of Months | 0.294437E+10 | 0.129821E+09 | 0.151405E+10 | 0.395574E+09 | 0.107739E+10 | 0.00 | 0.00 |
Maximum of Months | 0.431239E+10 | 0.518371E+09 | 0.212338E+10 | 0.838691E+09 | 0.128469E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.276945E+10 | 0.631691E+09 | 0.132422E+10 | 0.00 | 0.132422E+10 | 0.00 | 0.00 |
February | 0.280233E+10 | 0.442575E+09 | 0.127587E+10 | 0.00 | 0.127587E+10 | 0.00 | 0.00 |
March | 0.337636E+10 | 0.326510E+09 | 0.144973E+10 | 0.00 | 0.144973E+10 | 0.00 | 0.00 |
April | 0.366571E+10 | 0.142089E+09 | 0.152680E+10 | 21637656.65 | 0.150517E+10 | 0.00 | 0.00 |
May | 0.482211E+10 | 0.176202E+09 | 0.202242E+10 | 0.215448E+09 | 0.180697E+10 | 0.00 | 0.00 |
June | 0.554710E+10 | 0.193113E+09 | 0.239076E+10 | 0.483154E+09 | 0.190761E+10 | 0.00 | 0.00 |
July | 0.451277E+10 | 0.348550E+09 | 0.212436E+10 | 0.222671E+09 | 0.190169E+10 | 0.00 | 0.00 |
August | 0.376150E+10 | 0.267904E+09 | 0.174904E+10 | 74580343.55 | 0.167446E+10 | 0.00 | 0.00 |
September | 0.320956E+10 | 0.256715E+09 | 0.144108E+10 | 690066.21 | 0.144039E+10 | 0.00 | 0.00 |
October | 0.295014E+10 | 0.354057E+09 | 0.143482E+10 | 0.00 | 0.143482E+10 | 0.00 | 0.00 |
November | 0.272849E+10 | 0.418959E+09 | 0.131386E+10 | 0.00 | 0.131386E+10 | 0.00 | 0.00 |
December | 0.266521E+10 | 0.693373E+09 | 0.128646E+10 | 0.00 | 0.128646E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.428107E+11 | 0.425174E+10 | 0.193394E+11 | 0.101818E+10 | 0.183212E+11 | 0.00 | 0.00 |
Minimum of Months | 0.266521E+10 | 0.142089E+09 | 0.127587E+10 | 0.00 | 0.127587E+10 | 0.00 | 0.00 |
Maximum of Months | 0.554710E+10 | 0.693373E+09 | 0.239076E+10 | 0.483154E+09 | 0.190761E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.328148E+10 | 0.397610E+09 | 0.170231E+10 | 0.573729E+09 | 0.112859E+10 | 0.00 | 0.00 |
February | 0.344001E+10 | 0.275536E+09 | 0.174360E+10 | 0.639290E+09 | 0.110431E+10 | 0.00 | 0.00 |
March | 0.425486E+10 | 0.200192E+09 | 0.210452E+10 | 0.824120E+09 | 0.128040E+10 | 0.00 | 0.00 |
April | 0.427641E+10 | 88314305.54 | 0.205833E+10 | 0.786368E+09 | 0.127196E+10 | 0.00 | 0.00 |
May | 0.395615E+10 | 0.111627E+09 | 0.182829E+10 | 0.553421E+09 | 0.127487E+10 | 0.00 | 0.00 |
June | 0.402390E+10 | 0.119242E+09 | 0.188447E+10 | 0.620645E+09 | 0.126383E+10 | 0.00 | 0.00 |
July | 0.334660E+10 | 0.221095E+09 | 0.166325E+10 | 0.372609E+09 | 0.129064E+10 | 0.00 | 0.00 |
August | 0.361729E+10 | 0.173393E+09 | 0.183044E+10 | 0.538071E+09 | 0.129237E+10 | 0.00 | 0.00 |
September | 0.338418E+10 | 0.169603E+09 | 0.166356E+10 | 0.453326E+09 | 0.121023E+10 | 0.00 | 0.00 |
October | 0.311411E+10 | 0.232835E+09 | 0.161109E+10 | 0.412175E+09 | 0.119892E+10 | 0.00 | 0.00 |
November | 0.293328E+10 | 0.273926E+09 | 0.150892E+10 | 0.416983E+09 | 0.109193E+10 | 0.00 | 0.00 |
December | 0.306076E+10 | 0.441527E+09 | 0.159560E+10 | 0.512044E+09 | 0.108356E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.426890E+11 | 0.270490E+10 | 0.211944E+11 | 0.670278E+10 | 0.144916E+11 | 0.00 | 0.00 |
Minimum of Months | 0.293328E+10 | 88314305.54 | 0.150892E+10 | 0.372609E+09 | 0.108356E+10 | 0.00 | 0.00 |
Maximum of Months | 0.427641E+10 | 0.441527E+09 | 0.210452E+10 | 0.824120E+09 | 0.129237E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.681457E+10 | 0.644963E+09 | 0.350604E+10 | 0.146276E+10 | 0.204328E+10 | 0.00 | 0.00 |
February | 0.562722E+10 | 0.440986E+09 | 0.268905E+10 | 0.876730E+09 | 0.181232E+10 | 0.00 | 0.00 |
March | 0.470407E+10 | 0.314523E+09 | 0.203174E+10 | 0.272864E+09 | 0.175888E+10 | 0.00 | 0.00 |
April | 0.356634E+10 | 0.128366E+09 | 0.146590E+10 | 658052.64 | 0.146524E+10 | 0.00 | 0.00 |
May | 0.377789E+10 | 0.162555E+09 | 0.151580E+10 | 0.00 | 0.151580E+10 | 0.00 | 0.00 |
June | 0.363325E+10 | 0.170616E+09 | 0.146162E+10 | 0.00 | 0.146162E+10 | 0.00 | 0.00 |
July | 0.335713E+10 | 0.330639E+09 | 0.155588E+10 | 0.00 | 0.155588E+10 | 0.00 | 0.00 |
August | 0.327909E+10 | 0.250149E+09 | 0.151466E+10 | 2340935.21 | 0.151232E+10 | 0.00 | 0.00 |
September | 0.359299E+10 | 0.257777E+09 | 0.162274E+10 | 52999972.44 | 0.156974E+10 | 0.00 | 0.00 |
October | 0.444767E+10 | 0.372639E+09 | 0.219379E+10 | 0.349782E+09 | 0.184401E+10 | 0.00 | 0.00 |
November | 0.545477E+10 | 0.445087E+09 | 0.276063E+10 | 0.842230E+09 | 0.191840E+10 | 0.00 | 0.00 |
December | 0.670951E+10 | 0.718581E+09 | 0.350425E+10 | 0.149091E+10 | 0.201333E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.549645E+11 | 0.423688E+10 | 0.258221E+11 | 0.535128E+10 | 0.204708E+11 | 0.00 | 0.00 |
Minimum of Months | 0.327909E+10 | 0.128366E+09 | 0.146162E+10 | 0.00 | 0.146162E+10 | 0.00 | 0.00 |
Maximum of Months | 0.681457E+10 | 0.718581E+09 | 0.350604E+10 | 0.149091E+10 | 0.204328E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.337236E+10 | 0.443149E+09 | 0.172481E+10 | 0.606498E+09 | 0.111831E+10 | 0.00 | 0.00 |
February | 0.342193E+10 | 0.310493E+09 | 0.171101E+10 | 0.605487E+09 | 0.110552E+10 | 0.00 | 0.00 |
March | 0.432077E+10 | 0.244731E+09 | 0.212341E+10 | 0.838705E+09 | 0.128470E+10 | 0.00 | 0.00 |
April | 0.426159E+10 | 0.109160E+09 | 0.206507E+10 | 0.790953E+09 | 0.127412E+10 | 0.00 | 0.00 |
May | 0.390618E+10 | 0.114904E+09 | 0.181572E+10 | 0.537914E+09 | 0.127781E+10 | 0.00 | 0.00 |
June | 0.403116E+10 | 0.124865E+09 | 0.190409E+10 | 0.656295E+09 | 0.124780E+10 | 0.00 | 0.00 |
July | 0.337081E+10 | 0.231049E+09 | 0.167745E+10 | 0.395580E+09 | 0.128187E+10 | 0.00 | 0.00 |
August | 0.358389E+10 | 0.181086E+09 | 0.182372E+10 | 0.540083E+09 | 0.128364E+10 | 0.00 | 0.00 |
September | 0.334954E+10 | 0.179511E+09 | 0.165308E+10 | 0.458491E+09 | 0.119459E+10 | 0.00 | 0.00 |
October | 0.310103E+10 | 0.246804E+09 | 0.160432E+10 | 0.413558E+09 | 0.119076E+10 | 0.00 | 0.00 |
November | 0.295586E+10 | 0.290338E+09 | 0.151406E+10 | 0.412932E+09 | 0.110113E+10 | 0.00 | 0.00 |
December | 0.312735E+10 | 0.480842E+09 | 0.160118E+10 | 0.523775E+09 | 0.107740E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.428025E+11 | 0.295693E+10 | 0.212179E+11 | 0.678027E+10 | 0.144376E+11 | 0.00 | 0.00 |
Minimum of Months | 0.295586E+10 | 0.109160E+09 | 0.151406E+10 | 0.395580E+09 | 0.107740E+10 | 0.00 | 0.00 |
Maximum of Months | 0.432077E+10 | 0.480842E+09 | 0.212341E+10 | 0.838705E+09 | 0.128470E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.344983E+10 | -0.276320E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -686629356.1 | 58.98 | 0.00 | 0.00 |
February | 0.311599E+10 | -0.249531E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -620675120.7 | 58.98 | 0.00 | 0.00 |
March | 0.359687E+10 | -0.290742E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689450936.5 | 58.98 | 0.00 | 0.00 |
April | 0.322648E+10 | -0.255952E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666957175.5 | 58.98 | 0.00 | 0.00 |
May | 0.337532E+10 | -0.268559E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689728029.0 | 58.98 | 0.00 | 0.00 |
June | 0.329551E+10 | -0.262840E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667115802.0 | 58.98 | 0.00 | 0.00 |
July | 0.315088E+10 | -0.246322E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687664724.0 | 58.98 | 0.00 | 0.00 |
August | 0.343271E+10 | -0.274361E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689094823.6 | 58.98 | 0.00 | 0.00 |
September | 0.317902E+10 | -0.251269E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666323960.1 | 58.98 | 0.00 | 0.00 |
October | 0.334057E+10 | -0.265353E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687037148.6 | 58.98 | 0.00 | 0.00 |
November | 0.333030E+10 | -0.266591E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -664382079.0 | 58.98 | 0.00 | 0.00 |
December | 0.336325E+10 | -0.267663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -686615863.6 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.398567E+11 | -0.317550E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.810168E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.311599E+10 | -0.290742E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -689728029.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.359687E+10 | -0.246322E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -620675120.7 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-07:40 | 2518.93 | 25.51 | 148.33 | 325.33 | 1242.50 | 25.20 | 320.50 | 314.67 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-07:10 | 1987.15 | 19.42 | 0.00 | 295.67 | 1050.49 | 21.61 | 234.50 | 278.00 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:40 | 1501.81 | 19.23 | 0.00 | 328.83 | 836.92 | 21.34 | 219.50 | 308.17 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:10 | 1231.53 | 18.91 | 0.00 | 328.17 | 699.68 | 21.05 | 149.17 | 297.00 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-06:00 | 1054.14 | 17.88 | 0.00 | 336.50 | 586.80 | 19.98 | 56.17 | 294.33 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-07:40 | 1029.43 | 18.03 | 0.00 | 329.83 | 591.91 | 20.20 | 31.33 | 289.17 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-07:10 | 997.36 | 17.47 | 0.00 | 333.67 | 542.02 | 19.53 | 2.50 | 288.17 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-07:10 | 1179.29 | 18.35 | 0.00 | 335.00 | 645.73 | 20.45 | 98.83 | 296.67 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:49 | 1333.03 | 18.19 | 0.00 | 317.33 | 701.82 | 20.24 | 123.67 | 284.67 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-06:30 | 1726.84 | 19.61 | 15.00 | 330.17 | 878.58 | 21.19 | 202.17 | 294.83 |
November | 337.67 | 0.50 | 0.48 | 01-NOV-06:00 | 2182.57 | 23.92 | 115.33 | 316.33 | 1069.83 | 22.14 | 254.33 | 288.17 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:40 | 2529.52 | 25.54 | 149.50 | 322.17 | 1242.47 | 25.15 | 318.33 | 308.67 |
Annual Sum or Average | 4292.33 | 0.51 | 1587.68 | 20.10 | 428.17 | 3899.00 | 832.25 | 21.46 | 2011.00 | 3542.50 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 997.36 | 17.47 | 0.00 | 295.67 | 542.02 | 19.53 | 2.50 | 278.00 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2529.52 | 25.54 | 149.50 | 336.50 | 1242.50 | 25.20 | 320.50 | 314.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-07:19 | 2117.23 | 22.04 | 108.50 | 314.50 | 1110.90 | 22.97 | 77.50 | 284.00 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-06:40 | 2349.27 | 22.15 | 99.17 | 290.50 | 1237.34 | 23.07 | 71.17 | 268.17 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-06:00 | 2666.23 | 22.19 | 113.00 | 326.83 | 1106.81 | 21.70 | 52.33 | 304.33 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:10 | 2198.31 | 20.43 | 84.17 | 333.17 | 1152.52 | 21.67 | 54.50 | 305.67 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-05:00 | 1884.48 | 19.67 | 87.67 | 344.00 | 985.88 | 21.85 | 67.83 | 310.17 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-06:40 | 2022.00 | 20.08 | 84.50 | 340.33 | 1064.79 | 22.12 | 63.50 | 311.50 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-06:19 | 1681.47 | 19.38 | 87.17 | 342.50 | 864.06 | 21.36 | 64.33 | 305.17 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-05:00 | 1917.62 | 20.01 | 86.00 | 341.00 | 993.28 | 21.24 | 55.17 | 310.33 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:10 | 1810.22 | 19.42 | 84.33 | 319.83 | 926.59 | 20.59 | 54.50 | 286.67 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-05:00 | 1807.88 | 19.99 | 86.17 | 321.50 | 922.51 | 21.13 | 55.17 | 289.33 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-06:40 | 1823.31 | 20.63 | 85.00 | 304.67 | 915.54 | 21.50 | 51.50 | 270.67 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-06:40 | 2058.42 | 22.13 | 112.67 | 307.50 | 943.80 | 21.87 | 56.17 | 277.50 |
Annual Sum or Average | 4292.33 | 0.52 | 2023.63 | 20.65 | 1118.33 | 3886.33 | 1016.40 | 21.74 | 723.67 | 3523.50 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 1681.47 | 19.38 | 84.17 | 290.50 | 864.06 | 20.59 | 51.50 | 268.17 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2666.23 | 22.19 | 113.00 | 344.00 | 1237.34 | 23.07 | 77.50 | 311.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.54 | 0.48 | 01-JAN-08:30 | 841.23 | 17.07 | 0.00 | 304.83 | 496.67 | 19.25 | 0.00 | 258.33 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-07:40 | 925.96 | 17.56 | 0.00 | 283.50 | 548.78 | 19.71 | 0.00 | 253.00 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-07:00 | 1057.67 | 18.43 | 0.00 | 327.17 | 626.01 | 20.55 | 79.83 | 299.83 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:40 | 1293.15 | 19.36 | 0.00 | 338.17 | 732.45 | 21.47 | 178.83 | 312.00 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1502.42 | 19.18 | 3.83 | 352.67 | 788.86 | 21.24 | 178.67 | 325.50 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:19 | 1799.77 | 23.49 | 113.17 | 351.00 | 918.58 | 23.05 | 280.00 | 331.17 |
July | 383.17 | 0.50 | 0.48 | 01-JUL-06:40 | 1557.13 | 23.01 | 116.83 | 356.00 | 781.38 | 23.22 | 219.17 | 328.33 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-06:19 | 1394.58 | 19.10 | 0.00 | 348.50 | 747.86 | 21.19 | 165.33 | 317.83 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:49 | 1132.01 | 17.94 | 0.00 | 317.67 | 612.59 | 19.97 | 82.83 | 283.83 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-07:30 | 1000.54 | 17.77 | 0.00 | 319.67 | 549.44 | 19.81 | 18.83 | 271.50 |
November | 337.67 | 0.53 | 0.48 | 01-NOV-07:40 | 895.53 | 17.42 | 0.00 | 294.83 | 504.42 | 19.51 | 0.00 | 250.67 |
December | 349.33 | 0.54 | 0.48 | 01-DEC-07:30 | 819.13 | 16.84 | 0.00 | 299.17 | 477.73 | 19.01 | 0.00 | 250.83 |
Annual Sum or Average | 4292.33 | 0.52 | 1195.69 | 19.00 | 233.83 | 3893.17 | 653.32 | 20.71 | 1203.50 | 3482.83 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 819.13 | 16.84 | 0.00 | 283.50 | 477.73 | 19.01 | 0.00 | 250.67 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 1799.77 | 23.49 | 116.83 | 356.00 | 918.58 | 23.22 | 280.00 | 331.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-08:39 | 2185.87 | 22.20 | 109.33 | 312.83 | 1144.18 | 23.05 | 77.83 | 285.83 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-07:00 | 2449.82 | 22.11 | 102.33 | 288.33 | 1030.55 | 21.50 | 46.83 | 262.67 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-08:20 | 2719.07 | 21.92 | 112.67 | 335.00 | 1126.84 | 21.37 | 51.83 | 309.67 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 2649.43 | 15.71 | 0.00 | 333.00 | 1114.04 | 19.04 | 0.00 | 306.17 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-07:10 | 2085.97 | 15.47 | 0.00 | 344.17 | 937.57 | 18.57 | 0.00 | 308.50 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-08:09 | 1966.50 | 15.89 | 0.00 | 337.67 | 1029.28 | 19.11 | 0.00 | 310.17 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-07:40 | 1681.62 | 15.28 | 0.00 | 342.33 | 857.47 | 18.29 | 0.00 | 303.67 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-07:19 | 1927.21 | 16.05 | 8.50 | 340.00 | 973.40 | 18.75 | 0.00 | 308.00 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-07:30 | 1986.11 | 19.24 | 87.00 | 317.33 | 901.30 | 18.51 | 7.67 | 286.50 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-07:00 | 1886.52 | 21.11 | 101.83 | 321.50 | 972.50 | 22.32 | 72.83 | 289.17 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-07:00 | 1863.75 | 20.40 | 85.00 | 305.50 | 965.51 | 22.45 | 66.00 | 274.83 |
December | 349.33 | 0.52 | 0.48 | 01-DEC-07:40 | 1935.35 | 20.50 | 90.00 | 311.50 | 1025.27 | 22.52 | 72.00 | 281.50 |
Annual Sum or Average | 4292.33 | 0.52 | 2106.95 | 18.73 | 696.67 | 3889.17 | 1005.13 | 20.40 | 395.00 | 3526.67 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1681.62 | 15.28 | 0.00 | 288.33 | 857.47 | 18.29 | 0.00 | 262.67 | |
Maximum of Months | 383.17 | 0.52 | 0.48 | 2719.07 | 22.20 | 112.67 | 344.17 | 1144.18 | 23.05 | 77.83 | 310.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-07:40 | 2415.52 | 23.06 | 148.33 | 324.50 | 1170.44 | 23.01 | 89.00 | 313.83 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-07:10 | 1900.74 | 15.59 | 0.00 | 295.33 | 991.74 | 19.16 | 0.33 | 276.67 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:49 | 1441.36 | 15.79 | 0.00 | 328.67 | 799.25 | 19.24 | 0.00 | 305.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:10 | 1185.29 | 15.56 | 0.00 | 327.00 | 672.87 | 19.01 | 0.00 | 293.17 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-06:00 | 1015.86 | 14.27 | 0.00 | 334.33 | 564.44 | 17.67 | 0.00 | 288.83 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-07:49 | 991.38 | 14.58 | 0.00 | 327.17 | 570.12 | 18.05 | 0.00 | 284.67 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-07:19 | 962.21 | 13.72 | 0.00 | 331.67 | 521.16 | 17.10 | 0.00 | 285.00 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-07:10 | 1135.84 | 14.80 | 0.00 | 333.00 | 620.01 | 18.18 | 0.00 | 291.50 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 1282.76 | 14.52 | 0.00 | 316.83 | 671.07 | 17.84 | 0.00 | 282.17 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-06:40 | 1657.84 | 15.90 | 15.00 | 329.00 | 835.36 | 18.82 | 5.67 | 291.83 |
November | 337.67 | 0.50 | 0.48 | 01-NOV-07:10 | 2092.73 | 21.22 | 115.00 | 314.67 | 1016.76 | 20.80 | 40.00 | 289.67 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:40 | 2425.01 | 23.11 | 149.00 | 321.50 | 1169.69 | 22.91 | 88.50 | 307.50 |
Annual Sum or Average | 4292.33 | 0.52 | 1524.80 | 16.77 | 427.33 | 3883.67 | 792.39 | 19.27 | 223.50 | 3510.33 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 962.21 | 13.72 | 0.00 | 295.33 | 521.16 | 17.10 | 0.00 | 276.67 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2425.01 | 23.11 | 149.00 | 334.33 | 1170.44 | 23.01 | 89.00 | 313.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-07:19 | 2053.05 | 21.59 | 108.50 | 313.33 | 1066.40 | 22.77 | 77.50 | 281.83 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-06:40 | 2289.17 | 21.70 | 99.17 | 290.17 | 1187.28 | 22.88 | 71.17 | 265.33 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:10 | 2594.23 | 21.75 | 113.00 | 326.00 | 1054.55 | 21.52 | 52.33 | 302.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:10 | 2118.37 | 19.97 | 84.17 | 330.83 | 1099.56 | 21.51 | 54.50 | 303.50 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-05:00 | 1839.71 | 19.22 | 87.50 | 342.17 | 942.22 | 21.70 | 67.83 | 307.67 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-06:49 | 1963.45 | 19.64 | 84.50 | 337.33 | 1018.19 | 21.96 | 63.17 | 307.50 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-06:19 | 1635.50 | 18.93 | 87.17 | 339.00 | 819.30 | 20.48 | 56.33 | 300.67 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-05:00 | 1862.51 | 19.56 | 86.00 | 339.17 | 948.12 | 21.08 | 55.17 | 307.83 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:10 | 1742.67 | 18.97 | 84.33 | 318.50 | 884.45 | 20.42 | 54.50 | 282.50 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-05:00 | 1758.91 | 19.51 | 86.17 | 320.83 | 881.27 | 20.93 | 55.17 | 285.50 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-06:40 | 1766.30 | 20.15 | 85.00 | 302.50 | 874.84 | 21.29 | 51.50 | 268.33 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-06:40 | 1999.67 | 21.68 | 112.67 | 305.83 | 902.13 | 21.66 | 56.17 | 275.33 |
Annual Sum or Average | 4292.33 | 0.52 | 1964.37 | 20.19 | 1118.17 | 3865.67 | 970.93 | 21.50 | 715.33 | 3488.50 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1635.50 | 18.93 | 84.17 | 290.17 | 819.30 | 20.42 | 51.50 | 265.33 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2594.23 | 21.75 | 113.00 | 342.17 | 1187.28 | 22.88 | 77.50 | 307.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.54 | 0.48 | 01-JAN-08:30 | 810.63 | 13.66 | 0.00 | 303.00 | 479.63 | 17.13 | 0.00 | 254.00 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-07:49 | 892.42 | 14.25 | 0.00 | 281.67 | 530.09 | 17.70 | 0.00 | 248.67 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:09 | 1018.71 | 15.20 | 0.00 | 326.33 | 604.22 | 18.64 | 0.00 | 297.00 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 1244.28 | 16.00 | 0.00 | 335.83 | 703.96 | 19.49 | 0.00 | 308.17 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-06:19 | 1444.79 | 15.40 | 3.83 | 351.17 | 752.93 | 18.77 | 1.83 | 322.67 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:19 | 1729.74 | 20.83 | 112.83 | 350.00 | 873.74 | 20.77 | 34.17 | 329.50 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:40 | 1498.87 | 20.29 | 116.17 | 354.50 | 744.37 | 20.99 | 59.50 | 325.17 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-06:19 | 1341.62 | 15.44 | 0.00 | 346.83 | 715.67 | 18.89 | 0.00 | 314.17 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:49 | 1090.83 | 14.34 | 0.00 | 316.67 | 588.14 | 17.66 | 0.00 | 281.50 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-07:40 | 964.96 | 14.13 | 0.00 | 315.67 | 528.59 | 17.50 | 0.00 | 269.50 |
November | 337.67 | 0.53 | 0.48 | 01-NOV-07:40 | 863.76 | 13.83 | 0.00 | 293.67 | 486.15 | 17.23 | 0.00 | 245.67 |
December | 349.33 | 0.54 | 0.48 | 01-DEC-07:30 | 789.42 | 13.35 | 0.00 | 296.50 | 461.07 | 16.79 | 0.00 | 245.17 |
Annual Sum or Average | 4292.33 | 0.52 | 1151.16 | 15.63 | 232.83 | 3871.83 | 626.66 | 18.51 | 95.50 | 3441.17 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 789.42 | 13.35 | 0.00 | 281.67 | 461.07 | 16.79 | 0.00 | 245.17 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 1729.74 | 20.83 | 116.17 | 354.50 | 873.74 | 20.99 | 59.50 | 329.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-08:50 | 2122.25 | 21.80 | 109.33 | 312.17 | 1099.21 | 22.94 | 77.83 | 282.50 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-08:09 | 2388.36 | 21.72 | 102.33 | 287.33 | 982.35 | 21.37 | 46.83 | 260.67 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-08:30 | 2654.54 | 21.51 | 112.67 | 334.83 | 1074.27 | 21.23 | 52.00 | 306.67 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 2560.75 | 15.15 | 0.00 | 331.33 | 1062.09 | 18.84 | 0.00 | 303.17 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-07:19 | 2041.54 | 14.91 | 0.00 | 341.50 | 894.71 | 18.35 | 0.00 | 306.33 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-08:09 | 1913.06 | 15.32 | 0.00 | 336.67 | 982.84 | 18.88 | 0.00 | 307.33 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-07:49 | 1636.98 | 14.71 | 0.00 | 340.17 | 819.08 | 18.07 | 0.00 | 300.67 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-07:19 | 1868.82 | 15.51 | 8.50 | 337.00 | 929.23 | 18.54 | 0.00 | 306.00 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-07:30 | 1918.93 | 18.59 | 85.00 | 315.67 | 859.76 | 18.32 | 7.67 | 284.00 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-08:09 | 1819.13 | 19.42 | 87.50 | 318.33 | 931.34 | 22.19 | 73.00 | 286.33 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-08:09 | 1804.85 | 19.97 | 85.00 | 304.33 | 924.34 | 22.34 | 66.00 | 272.00 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-07:49 | 1870.50 | 19.85 | 87.33 | 310.33 | 982.04 | 22.41 | 72.00 | 278.33 |
Annual Sum or Average | 4292.33 | 0.52 | 2045.69 | 18.11 | 677.67 | 3869.67 | 960.45 | 20.23 | 395.33 | 3494.00 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1636.98 | 14.71 | 0.00 | 287.33 | 819.08 | 18.07 | 0.00 | 260.67 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2654.54 | 21.80 | 112.67 | 341.50 | 1099.21 | 22.94 | 77.83 | 307.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-07:40 | 2415.39 | 23.06 | 148.33 | 324.50 | 1170.35 | 23.02 | 89.00 | 313.83 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-07:10 | 1900.62 | 15.59 | 0.00 | 295.33 | 991.66 | 19.17 | 0.33 | 276.67 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:49 | 1441.28 | 15.79 | 0.00 | 328.67 | 799.19 | 19.24 | 0.00 | 305.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:10 | 1185.24 | 15.56 | 0.00 | 327.00 | 672.82 | 19.01 | 0.00 | 293.17 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-06:00 | 1015.80 | 14.27 | 0.00 | 334.33 | 564.39 | 17.67 | 0.00 | 288.83 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-07:49 | 991.34 | 14.59 | 0.00 | 327.17 | 570.08 | 18.05 | 0.00 | 284.67 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-07:19 | 962.14 | 13.72 | 0.00 | 331.67 | 521.12 | 17.10 | 0.00 | 285.00 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-07:10 | 1135.77 | 14.81 | 0.00 | 333.00 | 619.96 | 18.19 | 0.00 | 291.50 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 1282.67 | 14.52 | 0.00 | 316.83 | 671.01 | 17.84 | 0.00 | 282.17 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-06:40 | 1657.71 | 15.90 | 15.00 | 329.00 | 835.28 | 18.82 | 5.67 | 291.83 |
November | 337.67 | 0.50 | 0.48 | 01-NOV-07:10 | 2092.58 | 21.22 | 115.00 | 314.67 | 1016.66 | 20.80 | 40.00 | 289.67 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:40 | 2424.87 | 23.12 | 149.00 | 321.50 | 1169.59 | 22.91 | 88.50 | 307.50 |
Annual Sum or Average | 4292.33 | 0.52 | 1524.71 | 16.77 | 427.33 | 3883.67 | 792.32 | 19.27 | 223.50 | 3510.33 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 962.14 | 13.72 | 0.00 | 295.33 | 521.12 | 17.10 | 0.00 | 276.67 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2424.87 | 23.12 | 149.00 | 334.33 | 1170.35 | 23.02 | 89.00 | 313.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-07:19 | 2052.99 | 21.59 | 108.50 | 313.33 | 1066.34 | 22.77 | 77.50 | 281.83 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-06:40 | 2289.10 | 21.71 | 99.17 | 290.17 | 1187.21 | 22.88 | 71.17 | 265.33 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:10 | 2594.17 | 21.75 | 113.00 | 326.00 | 1054.48 | 21.52 | 52.33 | 302.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:10 | 2118.30 | 19.97 | 84.17 | 330.83 | 1099.49 | 21.51 | 54.50 | 303.50 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-05:00 | 1839.63 | 19.22 | 87.50 | 342.17 | 942.16 | 21.70 | 67.83 | 307.67 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-06:49 | 1963.37 | 19.64 | 84.50 | 337.33 | 1018.12 | 21.96 | 63.17 | 307.50 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-06:19 | 1635.41 | 18.93 | 87.17 | 339.00 | 819.23 | 20.48 | 56.33 | 300.67 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-05:00 | 1862.42 | 19.56 | 86.00 | 339.17 | 948.05 | 21.08 | 55.17 | 307.83 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:10 | 1742.58 | 18.97 | 84.33 | 318.50 | 884.38 | 20.42 | 54.50 | 282.50 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-05:00 | 1758.83 | 19.52 | 86.17 | 320.83 | 881.20 | 20.93 | 55.17 | 285.50 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-06:40 | 1766.22 | 20.15 | 85.00 | 302.50 | 874.77 | 21.29 | 51.50 | 268.17 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-06:40 | 1999.61 | 21.68 | 112.67 | 305.83 | 902.06 | 21.66 | 56.17 | 275.33 |
Annual Sum or Average | 4292.33 | 0.52 | 1964.29 | 20.19 | 1118.17 | 3865.67 | 970.87 | 21.50 | 715.33 | 3488.33 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1635.41 | 18.93 | 84.17 | 290.17 | 819.23 | 20.42 | 51.50 | 265.33 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2594.17 | 21.75 | 113.00 | 342.17 | 1187.21 | 22.88 | 77.50 | 307.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.54 | 0.48 | 01-JAN-08:30 | 810.61 | 13.67 | 0.00 | 303.00 | 479.60 | 17.13 | 0.00 | 254.00 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-07:49 | 892.39 | 14.25 | 0.00 | 281.67 | 530.06 | 17.70 | 0.00 | 248.67 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:09 | 1018.67 | 15.20 | 0.00 | 326.33 | 604.18 | 18.64 | 0.00 | 297.00 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 1244.22 | 16.00 | 0.00 | 335.83 | 703.91 | 19.49 | 0.00 | 308.17 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-06:19 | 1444.69 | 15.40 | 3.83 | 351.17 | 752.87 | 18.77 | 1.83 | 322.67 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:19 | 1729.64 | 20.83 | 112.83 | 350.00 | 873.67 | 20.77 | 34.33 | 329.50 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:40 | 1498.76 | 20.29 | 116.17 | 354.50 | 744.30 | 20.99 | 59.50 | 325.17 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-06:19 | 1341.53 | 15.45 | 0.00 | 346.83 | 715.61 | 18.89 | 0.00 | 314.17 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:49 | 1090.76 | 14.34 | 0.00 | 316.67 | 588.09 | 17.66 | 0.00 | 281.50 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-07:40 | 964.91 | 14.13 | 0.00 | 315.67 | 528.55 | 17.50 | 0.00 | 269.50 |
November | 337.67 | 0.53 | 0.48 | 01-NOV-07:40 | 863.72 | 13.83 | 0.00 | 293.67 | 486.12 | 17.23 | 0.00 | 245.67 |
December | 349.33 | 0.54 | 0.48 | 01-DEC-07:30 | 789.39 | 13.36 | 0.00 | 296.50 | 461.04 | 16.80 | 0.00 | 245.17 |
Annual Sum or Average | 4292.33 | 0.52 | 1151.10 | 15.63 | 232.83 | 3871.83 | 626.61 | 18.51 | 95.67 | 3441.17 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 789.39 | 13.36 | 0.00 | 281.67 | 461.04 | 16.80 | 0.00 | 245.17 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 1729.64 | 20.83 | 116.17 | 354.50 | 873.67 | 20.99 | 59.50 | 329.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-08:50 | 2122.19 | 21.80 | 109.33 | 312.17 | 1099.14 | 22.94 | 77.83 | 282.50 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-08:09 | 2388.30 | 21.72 | 102.33 | 287.33 | 982.28 | 21.37 | 46.83 | 260.67 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-08:30 | 2654.48 | 21.51 | 112.67 | 334.83 | 1074.20 | 21.23 | 52.00 | 306.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 2560.68 | 15.15 | 0.00 | 331.33 | 1062.02 | 18.84 | 0.00 | 303.17 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-07:19 | 2041.46 | 14.91 | 0.00 | 341.50 | 894.65 | 18.35 | 0.00 | 306.33 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-08:09 | 1912.99 | 15.33 | 0.00 | 336.50 | 982.78 | 18.88 | 0.00 | 307.33 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-07:49 | 1636.89 | 14.71 | 0.00 | 340.17 | 819.01 | 18.07 | 0.00 | 300.67 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-07:19 | 1868.73 | 15.51 | 8.50 | 337.00 | 929.16 | 18.54 | 0.00 | 306.00 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-07:30 | 1918.84 | 18.59 | 85.00 | 315.67 | 859.70 | 18.32 | 7.67 | 284.00 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-08:09 | 1819.04 | 19.42 | 87.50 | 318.33 | 931.27 | 22.20 | 73.00 | 286.33 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-08:09 | 1804.77 | 19.97 | 85.00 | 304.33 | 924.27 | 22.34 | 66.00 | 272.00 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-07:49 | 1870.44 | 19.85 | 87.33 | 310.33 | 981.98 | 22.41 | 72.00 | 278.33 |
Annual Sum or Average | 4292.33 | 0.52 | 2045.62 | 18.11 | 677.67 | 3869.50 | 960.39 | 20.23 | 395.33 | 3493.83 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1636.89 | 14.71 | 0.00 | 287.33 | 819.01 | 18.07 | 0.00 | 260.67 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2654.48 | 21.80 | 112.67 | 341.50 | 1099.14 | 22.94 | 77.83 | 307.33 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.104698E+12 | 0.723176E+11 | 138319.43 | 09-JAN-05:02 | 85150.46 | 0.00 |
February | 0.00 | 0.00 | 0.989879E+11 | 0.684832E+11 | 145422.62 | 06-FEB-06:03 | 83357.35 | 0.00 |
March | 0.00 | 0.00 | 0.120427E+12 | 0.810233E+11 | 145175.80 | 29-MAR-04:02 | 85446.45 | 0.00 |
April | 0.00 | 0.00 | 0.125316E+12 | 0.771282E+11 | 147038.29 | 01-APR-04:02 | 79484.31 | 0.00 |
May | 0.00 | 0.00 | 0.143372E+12 | 0.821606E+11 | 149889.62 | 06-MAY-04:02 | 78676.80 | 0.00 |
June | 0.00 | 0.00 | 0.144020E+12 | 0.832739E+11 | 151571.91 | 10-JUN-04:02 | 75662.10 | 0.00 |
July | 0.00 | 0.00 | 0.115309E+12 | 0.718530E+11 | 137044.72 | 10-JUL-04:02 | 91054.45 | 0.00 |
August | 0.00 | 0.00 | 0.134793E+12 | 0.761291E+11 | 151283.73 | 21-AUG-04:02 | 75562.54 | 0.00 |
September | 0.00 | 0.00 | 0.122647E+12 | 0.705819E+11 | 145440.36 | 25-SEP-04:02 | 86859.01 | 0.00 |
October | 0.00 | 0.00 | 0.118931E+12 | 0.691031E+11 | 145746.75 | 30-OCT-04:02 | 86866.54 | 0.00 |
November | 0.00 | 0.00 | 0.111341E+12 | 0.689769E+11 | 128954.51 | 14-NOV-05:02 | 86108.99 | 0.00 |
December | 0.00 | 0.00 | 0.102575E+12 | 0.682174E+11 | 124531.88 | 11-DEC-06:12 | 77383.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.144242E+13 | 0.889248E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.989879E+11 | 0.682174E+11 | 124531.88 | 75562.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.144020E+12 | 0.832739E+11 | 151571.91 | 91054.45 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.905560E+11 | 0.609450E+11 | 128471.78 | 09-JAN-05:02 | 70754.56 | 0.00 |
February | 0.00 | 0.00 | 0.868299E+11 | 0.583719E+11 | 130311.21 | 06-FEB-06:03 | 68502.05 | 0.00 |
March | 0.00 | 0.00 | 0.105738E+12 | 0.690184E+11 | 130223.02 | 13-MAR-04:02 | 73094.72 | 0.00 |
April | 0.00 | 0.00 | 0.111172E+12 | 0.658830E+11 | 130841.18 | 06-APR-04:02 | 69788.69 | 0.00 |
May | 0.00 | 0.00 | 0.126678E+12 | 0.696162E+11 | 133904.25 | 20-MAY-04:02 | 62327.24 | 0.00 |
June | 0.00 | 0.00 | 0.127058E+12 | 0.703284E+11 | 133766.58 | 10-JUN-05:02 | 62427.89 | 0.00 |
July | 0.00 | 0.00 | 0.100060E+12 | 0.596015E+11 | 127906.85 | 10-JUL-04:02 | 77063.61 | 0.00 |
August | 0.00 | 0.00 | 0.117105E+12 | 0.626885E+11 | 134833.24 | 21-AUG-05:03 | 58142.53 | 0.00 |
September | 0.00 | 0.00 | 0.107189E+12 | 0.586713E+11 | 130694.36 | 25-SEP-04:02 | 71990.47 | 0.00 |
October | 0.00 | 0.00 | 0.103685E+12 | 0.575572E+11 | 132340.83 | 30-OCT-04:02 | 69462.82 | 0.00 |
November | 0.00 | 0.00 | 0.963209E+11 | 0.574162E+11 | 129054.44 | 13-NOV-05:02 | 75857.17 | 0.00 |
December | 0.00 | 0.00 | 0.889845E+11 | 0.571280E+11 | 121899.73 | 30-DEC-06:02 | 70895.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126138E+13 | 0.747226E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.868299E+11 | 0.571280E+11 | 121899.73 | 58142.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.127058E+12 | 0.703284E+11 | 134833.24 | 77063.61 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.954523E+11 | 0.655553E+11 | 124589.49 | 09-JAN-05:02 | 65375.09 | 0.00 |
February | 0.00 | 0.00 | 0.923493E+11 | 0.635619E+11 | 149005.23 | 06-FEB-06:01 | 82178.59 | 0.00 |
March | 0.00 | 0.00 | 0.113193E+12 | 0.761873E+11 | 150573.01 | 28-MAR-04:02 | 77529.55 | 0.00 |
April | 0.00 | 0.00 | 0.119384E+12 | 0.735427E+11 | 151381.49 | 12-APR-04:02 | 79074.59 | 0.00 |
May | 0.00 | 0.00 | 0.134351E+12 | 0.767651E+11 | 154844.20 | 24-MAY-04:02 | 69267.08 | 0.00 |
June | 0.00 | 0.00 | 0.134690E+12 | 0.776942E+11 | 154569.43 | 10-JUN-05:02 | 69956.64 | 0.00 |
July | 0.00 | 0.00 | 0.106416E+12 | 0.653183E+11 | 143950.64 | 10-JUL-04:02 | 85279.65 | 0.00 |
August | 0.00 | 0.00 | 0.122806E+12 | 0.681502E+11 | 152502.54 | 11-AUG-05:02 | 73063.80 | 0.00 |
September | 0.00 | 0.00 | 0.112936E+12 | 0.641940E+11 | 150759.44 | 25-SEP-04:02 | 79912.93 | 0.00 |
October | 0.00 | 0.00 | 0.108420E+12 | 0.619013E+11 | 152844.55 | 30-OCT-04:02 | 77688.06 | 0.00 |
November | 0.00 | 0.00 | 0.100758E+12 | 0.617232E+11 | 130816.93 | 13-NOV-05:02 | 73294.87 | 0.00 |
December | 0.00 | 0.00 | 0.936601E+11 | 0.614241E+11 | 115726.76 | 30-DEC-06:02 | 64914.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.133441E+13 | 0.816018E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.923493E+11 | 0.614241E+11 | 115726.76 | 64914.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.134690E+12 | 0.776942E+11 | 154844.20 | 85279.65 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1186.38 | 4020.92 | 05-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1185.98 | 4003.25 | 07-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1243.95 | 3960.19 | 02-MAR-12:17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1141.39 | 3888.55 | 03-APR-11:17 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 1159.16 | 3819.36 | 02-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1172.03 | 3737.75 | 06-JUN-11:13 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1072.85 | 3698.57 | 05-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1183.02 | 3744.57 | 30-AUG-11:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1123.67 | 3817.44 | 26-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1145.10 | 3900.25 | 27-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1184.02 | 3964.39 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1152.79 | 4005.15 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 1162.42 | ||||
Minimum of Months | 0.00 | 0.00 | 1072.85 | 3698.57 | ||
Maximum of Months | 0.00 | 0.00 | 1243.95 | 4020.92 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.397854E+10 | 0.43 | 10398.16 | 30-JAN-07:03 | 1.66 |
February | 0.378492E+10 | 0.44 | 11538.80 | 06-FEB-06:01 | 1.77 |
March | 0.440210E+10 | 0.46 | 11538.80 | 20-MAR-04:02 | 1.77 |
April | 0.407574E+10 | 0.45 | 11538.80 | 07-APR-04:02 | 1.77 |
May | 0.440263E+10 | 0.47 | 11538.80 | 04-MAY-04:02 | 1.77 |
June | 0.468792E+10 | 0.49 | 11538.80 | 05-JUN-04:02 | 1.77 |
July | 0.387775E+10 | 0.43 | 11538.80 | 03-JUL-04:02 | 1.77 |
August | 0.411282E+10 | 0.45 | 11538.80 | 07-AUG-04:02 | 1.77 |
September | 0.373274E+10 | 0.43 | 11538.80 | 07-SEP-04:02 | 1.77 |
October | 0.367998E+10 | 0.41 | 11538.80 | 02-OCT-04:02 | 1.77 |
November | 0.378905E+10 | 0.42 | 11538.80 | 24-NOV-05:02 | 1.77 |
December | 0.368750E+10 | 0.41 | 11253.94 | 26-DEC-07:03 | 1.74 |
Annual Sum or Average | 0.482117E+11 | 0.44 | |||
Minimum of Months | 0.367998E+10 | 0.41 | 10398.16 | 1.66 | |
Maximum of Months | 0.468792E+10 | 0.49 | 11538.80 | 1.77 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.321187E+10 | 0.41 | 8051.33 | 09-JAN-05:02 | 1.54 |
February | 0.309144E+10 | 0.42 | 10113.75 | 06-FEB-06:01 | 1.78 |
March | 0.352823E+10 | 0.44 | 10113.75 | 13-MAR-04:02 | 1.78 |
April | 0.324163E+10 | 0.43 | 10113.75 | 06-APR-05:02 | 1.78 |
May | 0.345735E+10 | 0.44 | 10113.75 | 02-MAY-04:02 | 1.78 |
June | 0.365379E+10 | 0.46 | 10113.75 | 09-JUN-04:02 | 1.78 |
July | 0.296019E+10 | 0.40 | 10113.75 | 03-JUL-04:02 | 1.78 |
August | 0.310754E+10 | 0.41 | 10113.75 | 02-AUG-04:02 | 1.78 |
September | 0.285932E+10 | 0.40 | 10113.75 | 11-SEP-04:02 | 1.78 |
October | 0.286389E+10 | 0.39 | 10113.75 | 16-OCT-04:02 | 1.78 |
November | 0.297578E+10 | 0.40 | 10113.75 | 13-NOV-05:02 | 1.78 |
December | 0.293106E+10 | 0.39 | 8840.82 | 30-DEC-06:02 | 1.63 |
Annual Sum or Average | 0.378821E+11 | 0.41 | |||
Minimum of Months | 0.285932E+10 | 0.39 | 8051.33 | 1.54 | |
Maximum of Months | 0.365379E+10 | 0.46 | 10113.75 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.309969E+10 | 0.37 | 6366.11 | 11-JAN-06:02 | 1.20 |
February | 0.302714E+10 | 0.39 | 11787.71 | 06-FEB-06:01 | 1.77 |
March | 0.354949E+10 | 0.41 | 11710.21 | 20-MAR-04:02 | 1.76 |
April | 0.331652E+10 | 0.41 | 11787.71 | 17-APR-04:02 | 1.77 |
May | 0.347889E+10 | 0.41 | 11787.71 | 01-MAY-04:02 | 1.77 |
June | 0.366803E+10 | 0.43 | 11787.71 | 10-JUN-05:02 | 1.76 |
July | 0.292916E+10 | 0.37 | 10615.94 | 31-JUL-04:02 | 1.65 |
August | 0.306781E+10 | 0.38 | 11787.71 | 14-AUG-04:02 | 1.77 |
September | 0.285802E+10 | 0.38 | 11637.42 | 05-SEP-04:02 | 1.75 |
October | 0.277775E+10 | 0.36 | 10244.00 | 16-OCT-04:02 | 1.62 |
November | 0.286532E+10 | 0.37 | 7102.36 | 13-NOV-05:02 | 1.28 |
December | 0.282379E+10 | 0.36 | 5768.01 | 30-DEC-06:02 | 1.13 |
Annual Sum or Average | 0.374616E+11 | 0.39 | |||
Minimum of Months | 0.277775E+10 | 0.36 | 5768.01 | 1.13 | |
Maximum of Months | 0.366803E+10 | 0.43 | 11787.71 | 1.77 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 57.30 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:02 | 2.06 | 2.06 | 57.41 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 56.61 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 56.95 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:10 | 2.06 | 2.06 | 57.49 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.30 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.48 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 56.74 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.47 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.62 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:02 | 2.06 | 2.06 | 57.60 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 56.87 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.61 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.62 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.11 | 57.11 | 1186.38 | 4020.92 | 05-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.60 | 57.60 | 1185.98 | 4003.25 | 07-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.80 | 56.80 | 1243.95 | 3960.19 | 02-MAR-12:17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.14 | 57.14 | 1141.39 | 3888.55 | 03-APR-11:17 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 58.01 | 58.01 | 1159.16 | 3819.36 | 02-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.22 | 58.22 | 1172.03 | 3737.75 | 06-JUN-11:13 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.33 | 58.33 | 1072.85 | 3698.57 | 05-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.90 | 56.90 | 1183.02 | 3744.57 | 30-AUG-11:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.31 | 58.31 | 1123.67 | 3817.44 | 26-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.16 | 57.16 | 1145.10 | 3900.25 | 27-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.79 | 57.79 | 1184.02 | 3964.39 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.06 | 57.06 | 1152.79 | 4005.15 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 1162.42 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.80 | 56.80 | 1072.85 | 3698.57 | ||
Maximum of Months | 0.00 | 0.00 | 58.33 | 58.33 | 1243.95 | 4020.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.306713E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.294116E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.359190E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.366547E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.413489E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.419756E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.327751E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.378183E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.344244E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.330549E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.315473E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.294649E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.415066E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.294116E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.419756E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.262003E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.254607E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.310216E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.318955E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.358392E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.362453E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.278415E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.321282E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.294459E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.282867E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.268424E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.251895E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.356397E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.251895E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.362453E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.274941E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.269734E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.331462E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.342111E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.379776E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.383720E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.295136E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.336106E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.309855E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.294561E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.279375E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.263835E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.376061E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.263835E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.383720E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.397854E+10 | 0.104698E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.378492E+10 | 0.989879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.440210E+10 | 0.120427E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.407574E+10 | 0.125316E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.440263E+10 | 0.143372E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.468792E+10 | 0.144020E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.387775E+10 | 0.115309E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.411282E+10 | 0.134793E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.373274E+10 | 0.122647E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.367998E+10 | 0.118931E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.378905E+10 | 0.111341E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.368750E+10 | 0.102575E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.482117E+11 | 0.144242E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.367998E+10 | 0.989879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.468792E+10 | 0.144020E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.321187E+10 | 0.905560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.309144E+10 | 0.868299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352823E+10 | 0.105738E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.324163E+10 | 0.111172E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.345735E+10 | 0.126678E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.365379E+10 | 0.127058E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.296019E+10 | 0.100060E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.310754E+10 | 0.117105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.285932E+10 | 0.107189E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.286389E+10 | 0.103685E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.297578E+10 | 0.963209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.293106E+10 | 0.889845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378821E+11 | 0.126138E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.285932E+10 | 0.868299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.365379E+10 | 0.127058E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.309969E+10 | 0.954523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302714E+10 | 0.923493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.354949E+10 | 0.113193E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.331652E+10 | 0.119384E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.347889E+10 | 0.134351E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.366803E+10 | 0.134690E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.292916E+10 | 0.106416E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.306781E+10 | 0.122806E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.285802E+10 | 0.112936E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277775E+10 | 0.108420E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286532E+10 | 0.100758E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.282379E+10 | 0.936601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.374616E+11 | 0.133441E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.277775E+10 | 0.923493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.366803E+10 | 0.134690E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.397854E+10 | 0.00 | 0.00 | 0.00 | 0.266928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.378492E+10 | 0.00 | 0.00 | 0.00 | 0.256266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.440210E+10 | 0.00 | 0.00 | 0.00 | 0.315169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.407574E+10 | 0.00 | 0.00 | 0.00 | 0.325789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.440263E+10 | 0.00 | 0.00 | 0.00 | 0.369463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.468792E+10 | 0.00 | 0.00 | 0.00 | 0.372877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.387775E+10 | 0.00 | 0.00 | 0.00 | 0.288974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.411282E+10 | 0.00 | 0.00 | 0.00 | 0.337055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.373274E+10 | 0.00 | 0.00 | 0.00 | 0.306917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.367998E+10 | 0.00 | 0.00 | 0.00 | 0.293750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.378905E+10 | 0.00 | 0.00 | 0.00 | 0.277583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.368750E+10 | 0.00 | 0.00 | 0.00 | 0.257774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.482117E+11 | 0.00 | 0.00 | 0.00 | 0.366855E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.367998E+10 | 0.00 | 0.00 | 0.00 | 0.256266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.468792E+10 | 0.00 | 0.00 | 0.00 | 0.372877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.321187E+10 | 0.00 | 0.00 | 0.00 | 0.229885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.309144E+10 | 0.00 | 0.00 | 0.00 | 0.223693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352823E+10 | 0.00 | 0.00 | 0.00 | 0.274933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.324163E+10 | 0.00 | 0.00 | 0.00 | 0.286539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.345735E+10 | 0.00 | 0.00 | 0.00 | 0.323818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.365379E+10 | 0.00 | 0.00 | 0.00 | 0.325915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.296019E+10 | 0.00 | 0.00 | 0.00 | 0.248813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.310754E+10 | 0.00 | 0.00 | 0.00 | 0.290207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.285932E+10 | 0.00 | 0.00 | 0.00 | 0.265865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.286389E+10 | 0.00 | 0.00 | 0.00 | 0.254228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.297578E+10 | 0.00 | 0.00 | 0.00 | 0.238666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.293106E+10 | 0.00 | 0.00 | 0.00 | 0.222584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378821E+11 | 0.00 | 0.00 | 0.00 | 0.318515E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.285932E+10 | 0.00 | 0.00 | 0.00 | 0.222584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.365379E+10 | 0.00 | 0.00 | 0.00 | 0.325915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.309969E+10 | 0.00 | 0.00 | 0.00 | 0.243944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302714E+10 | 0.00 | 0.00 | 0.00 | 0.239463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.354949E+10 | 0.00 | 0.00 | 0.00 | 0.295967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.331652E+10 | 0.00 | 0.00 | 0.00 | 0.308946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.347889E+10 | 0.00 | 0.00 | 0.00 | 0.344987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.366803E+10 | 0.00 | 0.00 | 0.00 | 0.347040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.292916E+10 | 0.00 | 0.00 | 0.00 | 0.265845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.306781E+10 | 0.00 | 0.00 | 0.00 | 0.305428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.285802E+10 | 0.00 | 0.00 | 0.00 | 0.281275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277775E+10 | 0.00 | 0.00 | 0.00 | 0.266783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286532E+10 | 0.00 | 0.00 | 0.00 | 0.250722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.282379E+10 | 0.00 | 0.00 | 0.00 | 0.235597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.374616E+11 | 0.00 | 0.00 | 0.00 | 0.338600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.277775E+10 | 0.00 | 0.00 | 0.00 | 0.235597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.366803E+10 | 0.00 | 0.00 | 0.00 | 0.347040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 652623.27 | 0.117949E+11 | 0.00 | 74710.13 | 0.217848E+10 | 0.00 | 818772.55 | 0.00 | 0.33 |
February | 0.00 | 0.113223E+11 | 0.00 | 0.00 | 0.230564E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
March | 0.00 | 0.151544E+11 | 0.00 | 0.00 | 0.241257E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
April | 0.00 | 0.178423E+11 | 0.00 | 0.00 | 0.422910E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
May | 0.00 | 0.219992E+11 | 0.00 | 0.00 | 0.528582E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.221665E+11 | 0.00 | 0.00 | 0.420867E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.156114E+11 | 0.00 | 0.00 | 0.359270E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
August | 0.00 | 0.221844E+11 | 0.00 | 0.00 | 0.323820E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
September | 0.00 | 0.192607E+11 | 0.00 | 0.00 | 0.405103E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
October | 0.00 | 0.185979E+11 | 0.00 | 0.00 | 0.343602E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
November | 0.00 | 0.155683E+11 | 0.00 | 0.00 | 0.289469E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
December | 0.00 | 0.123724E+11 | 0.00 | 0.00 | 0.263225E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 652623.27 | 0.203875E+12 | 0.00 | 74710.13 | 0.404652E+11 | 0.00 | 818772.55 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.113223E+11 | 0.00 | 0.00 | 0.217848E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 652623.27 | 0.221844E+11 | 0.00 | 74710.13 | 0.528582E+10 | 0.00 | 818772.55 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1623099.32 | 0.109572E+11 | 0.00 | 31017.01 | 0.193547E+10 | 0.00 | 2638954.41 | 0.00 | 0.30 |
February | 0.00 | 0.105785E+11 | 0.00 | 0.00 | 0.220364E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
March | 0.00 | 0.140966E+11 | 0.00 | 0.00 | 0.242366E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
April | 0.00 | 0.168726E+11 | 0.00 | 0.00 | 0.405784E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
May | 0.00 | 0.208303E+11 | 0.00 | 0.00 | 0.511607E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.210969E+11 | 0.00 | 0.00 | 0.415826E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.147782E+11 | 0.00 | 0.00 | 0.348417E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.210007E+11 | 0.00 | 0.00 | 0.327302E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.182358E+11 | 0.00 | 0.00 | 0.402768E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.173696E+11 | 0.00 | 0.00 | 0.338865E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
November | 0.00 | 0.145948E+11 | 0.00 | 0.00 | 0.276631E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
December | 98835.96 | 0.115210E+11 | 0.00 | 12787.58 | 0.244140E+10 | 0.00 | 2934.63 | 0.00 | 0.30 |
Annual Sum or Average | 1721935.28 | 0.191932E+12 | 0.00 | 43804.59 | 0.392762E+11 | 0.00 | 2641889.04 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.105785E+11 | 0.00 | 0.00 | 0.193547E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 1623099.32 | 0.210969E+11 | 0.00 | 31017.01 | 0.511607E+10 | 0.00 | 2638954.41 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1219690.33 | 0.105964E+11 | 0.00 | 0.00 | 0.192929E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
February | 0.00 | 0.102128E+11 | 0.00 | 0.00 | 0.227791E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
March | 0.00 | 0.135688E+11 | 0.00 | 0.00 | 0.241430E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
April | 0.00 | 0.162695E+11 | 0.00 | 0.00 | 0.415880E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
May | 0.00 | 0.203396E+11 | 0.00 | 0.00 | 0.514390E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.205330E+11 | 0.00 | 0.00 | 0.412467E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.142396E+11 | 0.00 | 0.00 | 0.368330E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.203813E+11 | 0.00 | 0.00 | 0.331945E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.176594E+11 | 0.00 | 0.00 | 0.403383E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.168386E+11 | 0.00 | 0.00 | 0.350508E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
November | 0.00 | 0.141399E+11 | 0.00 | 0.00 | 0.278506E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
December | 0.00 | 0.109927E+11 | 0.00 | 0.00 | 0.264749E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 1219690.33 | 0.185772E+12 | 0.00 | 0.00 | 0.400231E+11 | 0.00 | 0.00 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.102128E+11 | 0.00 | 0.00 | 0.192929E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 1219690.33 | 0.205330E+11 | 0.00 | 0.00 | 0.514390E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 257039.45 | 0.307055E+10 | 0.00 | 0.00 | 0.393823E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
February | 0.00 | 0.318614E+10 | 0.00 | 0.00 | 0.392558E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
March | 0.00 | 0.435479E+10 | 0.00 | 0.00 | 0.394257E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
April | 0.00 | 0.572211E+10 | 0.00 | 0.00 | 0.618441E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
May | 0.00 | 0.790511E+10 | 0.00 | 0.00 | 0.631524E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 0.00 | 0.862716E+10 | 0.00 | 0.00 | 0.425793E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.534550E+10 | 0.00 | 0.00 | 0.505249E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.683869E+10 | 0.00 | 0.00 | 0.534914E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.573477E+10 | 0.00 | 0.00 | 0.672154E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.00 | 0.511666E+10 | 0.00 | 0.00 | 0.579636E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
November | 0.00 | 0.420645E+10 | 0.00 | 0.00 | 0.472392E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
December | 0.00 | 0.317724E+10 | 0.00 | 0.00 | 0.523840E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 257039.45 | 0.632852E+11 | 0.00 | 0.00 | 0.614458E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.307055E+10 | 0.00 | 0.00 | 0.392558E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 257039.45 | 0.862716E+10 | 0.00 | 0.00 | 0.672154E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 221493.21 | 0.258110E+10 | 0.00 | 0.00 | 0.284565E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
February | 0.00 | 0.273700E+10 | 0.00 | 0.00 | 0.254433E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
March | 0.00 | 0.375748E+10 | 0.00 | 0.00 | 0.305156E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
April | 0.00 | 0.483869E+10 | 0.00 | 0.00 | 0.492946E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
May | 0.00 | 0.564819E+10 | 0.00 | 0.00 | 0.624041E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
June | 0.00 | 0.581307E+10 | 0.00 | 0.00 | 0.477410E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.366300E+10 | 0.00 | 0.00 | 0.501815E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.527188E+10 | 0.00 | 0.00 | 0.466664E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.466436E+10 | 0.00 | 0.00 | 0.513467E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
October | 0.00 | 0.409693E+10 | 0.00 | 0.00 | 0.499417E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 0.00 | 0.339170E+10 | 0.00 | 0.00 | 0.352089E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
December | 0.00 | 0.268205E+10 | 0.00 | 0.00 | 0.358222E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 221493.21 | 0.491454E+11 | 0.00 | 0.00 | 0.513022E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.258110E+10 | 0.00 | 0.00 | 0.254433E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 221493.21 | 0.581307E+10 | 0.00 | 0.00 | 0.624041E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 257949.40 | 0.467332E+10 | 0.00 | 0.00 | 0.215039E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
February | 0.00 | 0.445325E+10 | 0.00 | 0.00 | 0.265536E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
March | 0.00 | 0.503664E+10 | 0.00 | 0.00 | 0.341797E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
April | 0.00 | 0.559831E+10 | 0.00 | 0.00 | 0.642567E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 0.00 | 0.697279E+10 | 0.00 | 0.00 | 0.775286E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.697028E+10 | 0.00 | 0.00 | 0.589703E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.461590E+10 | 0.00 | 0.00 | 0.597150E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.639973E+10 | 0.00 | 0.00 | 0.573416E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.603079E+10 | 0.00 | 0.00 | 0.650742E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.614124E+10 | 0.00 | 0.00 | 0.475855E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
November | 0.00 | 0.571949E+10 | 0.00 | 0.00 | 0.315606E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
December | 0.00 | 0.498433E+10 | 0.00 | 0.00 | 0.275902E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 257949.40 | 0.675961E+11 | 0.00 | 0.00 | 0.571860E+10 | 0.00 | 0.00 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.445325E+10 | 0.00 | 0.00 | 0.215039E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 257949.40 | 0.697279E+10 | 0.00 | 0.00 | 0.775286E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 257843.43 | 0.255221E+10 | 0.00 | 0.00 | 0.422821E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
February | 0.00 | 0.269883E+10 | 0.00 | 0.00 | 0.447129E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
March | 0.00 | 0.376838E+10 | 0.00 | 0.00 | 0.420509E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
April | 0.00 | 0.472910E+10 | 0.00 | 0.00 | 0.653012E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
May | 0.00 | 0.542026E+10 | 0.00 | 0.00 | 0.890591E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
June | 0.00 | 0.557352E+10 | 0.00 | 0.00 | 0.680511E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.351480E+10 | 0.00 | 0.00 | 0.743524E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
August | 0.00 | 0.508002E+10 | 0.00 | 0.00 | 0.661684E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.444647E+10 | 0.00 | 0.00 | 0.782597E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.389036E+10 | 0.00 | 0.00 | 0.843619E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
November | 0.00 | 0.330659E+10 | 0.00 | 0.00 | 0.612686E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
December | 0.00 | 0.257771E+10 | 0.00 | 0.00 | 0.620154E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 257843.43 | 0.475583E+11 | 0.00 | 0.00 | 0.777884E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.255221E+10 | 0.00 | 0.00 | 0.420509E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 257843.43 | 0.557352E+10 | 0.00 | 0.00 | 0.890591E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 305462.50 | 0.258527E+10 | 0.00 | 0.00 | 0.517969E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
February | 0.00 | 0.264609E+10 | 0.00 | 0.00 | 0.518988E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
March | 0.00 | 0.363235E+10 | 0.00 | 0.00 | 0.563856E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
April | 0.00 | 0.480905E+10 | 0.00 | 0.00 | 0.818632E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
May | 0.00 | 0.679417E+10 | 0.00 | 0.00 | 0.816168E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.759839E+10 | 0.00 | 0.00 | 0.492135E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.475067E+10 | 0.00 | 0.00 | 0.562263E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.593440E+10 | 0.00 | 0.00 | 0.627545E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.491676E+10 | 0.00 | 0.00 | 0.855944E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
October | 0.00 | 0.422771E+10 | 0.00 | 0.00 | 0.809611E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
November | 0.00 | 0.347949E+10 | 0.00 | 0.00 | 0.669314E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
December | 0.00 | 0.269511E+10 | 0.00 | 0.00 | 0.623808E+09 | 0.00 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 305462.50 | 0.540695E+11 | 0.00 | 0.00 | 0.787623E+10 | 0.00 | 0.00 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.258527E+10 | 0.00 | 0.00 | 0.492135E+09 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 305462.50 | 0.759839E+10 | 0.00 | 0.00 | 0.855944E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 218116.01 | 0.218015E+10 | 0.00 | 2008.30 | 0.344305E+09 | 0.00 | 18331.53 | 0.00 | 0.45 |
February | 0.00 | 0.235092E+10 | 0.00 | 0.00 | 0.285230E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
March | 0.00 | 0.329220E+10 | 0.00 | 0.00 | 0.301404E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
April | 0.00 | 0.425888E+10 | 0.00 | 0.00 | 0.457997E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
May | 0.00 | 0.491327E+10 | 0.00 | 0.00 | 0.619302E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 0.00 | 0.506308E+10 | 0.00 | 0.00 | 0.479557E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
July | 0.00 | 0.321286E+10 | 0.00 | 0.00 | 0.480956E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.456793E+10 | 0.00 | 0.00 | 0.439324E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.408491E+10 | 0.00 | 0.00 | 0.500970E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.346157E+10 | 0.00 | 0.00 | 0.511389E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
November | 0.00 | 0.285789E+10 | 0.00 | 0.00 | 0.391736E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
December | 0.00 | 0.229224E+10 | 0.00 | 0.00 | 0.375364E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 218116.01 | 0.425359E+11 | 0.00 | 2008.30 | 0.518753E+10 | 0.00 | 18331.53 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.218015E+10 | 0.00 | 0.00 | 0.285230E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 218116.01 | 0.506308E+10 | 0.00 | 2008.30 | 0.619302E+09 | 0.00 | 18331.53 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 279456.09 | 0.449917E+10 | 0.00 | 1067.54 | 0.269641E+09 | 0.00 | 24992.40 | 0.00 | 0.53 |
February | 0.00 | 0.432458E+10 | 0.00 | 0.00 | 0.275547E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
March | 0.00 | 0.521087E+10 | 0.00 | 0.00 | 0.385002E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
April | 0.00 | 0.579338E+10 | 0.00 | 0.00 | 0.797310E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
May | 0.00 | 0.719320E+10 | 0.00 | 0.00 | 0.982093E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.724878E+10 | 0.00 | 0.00 | 0.775253E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.461021E+10 | 0.00 | 0.00 | 0.742053E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.661635E+10 | 0.00 | 0.00 | 0.685752E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.611110E+10 | 0.00 | 0.00 | 0.776205E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.606118E+10 | 0.00 | 0.00 | 0.546683E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
November | 0.00 | 0.563608E+10 | 0.00 | 0.00 | 0.349544E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
December | 0.00 | 0.480034E+10 | 0.00 | 0.00 | 0.292471E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 279456.09 | 0.681052E+11 | 0.00 | 1067.54 | 0.687755E+10 | 0.00 | 24992.40 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.432458E+10 | 0.00 | 0.00 | 0.269641E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 279456.09 | 0.724878E+10 | 0.00 | 1067.54 | 0.982093E+09 | 0.00 | 24992.40 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 237526.44 | 0.220502E+10 | 0.00 | 34.53 | 0.369143E+09 | 0.00 | 19959.89 | 0.00 | 0.45 |
February | 0.00 | 0.235628E+10 | 0.00 | 0.00 | 0.360694E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
March | 0.00 | 0.334727E+10 | 0.00 | 0.00 | 0.338503E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
April | 0.00 | 0.420714E+10 | 0.00 | 0.00 | 0.540752E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
May | 0.00 | 0.476641E+10 | 0.00 | 0.00 | 0.744123E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 0.00 | 0.498666E+10 | 0.00 | 0.00 | 0.530988E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
July | 0.00 | 0.315399E+10 | 0.00 | 0.00 | 0.559554E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.446177E+10 | 0.00 | 0.00 | 0.509894E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.394974E+10 | 0.00 | 0.00 | 0.616992E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.341803E+10 | 0.00 | 0.00 | 0.584594E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
November | 0.00 | 0.282915E+10 | 0.00 | 0.00 | 0.489334E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
December | 0.00 | 0.228432E+10 | 0.00 | 0.00 | 0.443323E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 237526.44 | 0.419658E+11 | 0.00 | 34.53 | 0.608789E+10 | 0.00 | 19959.89 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.220502E+10 | 0.00 | 0.00 | 0.338503E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 237526.44 | 0.498666E+10 | 0.00 | 34.53 | 0.744123E+09 | 0.00 | 19959.89 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 905685.22 | 0.320084E+10 | 0.00 | 0.00 | 0.414956E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
February | 0.00 | 0.329399E+10 | 0.00 | 0.00 | 0.419197E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
March | 0.00 | 0.455438E+10 | 0.00 | 0.00 | 0.429446E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
April | 0.00 | 0.593057E+10 | 0.00 | 0.00 | 0.647432E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
May | 0.00 | 0.819910E+10 | 0.00 | 0.00 | 0.652070E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 0.00 | 0.900607E+10 | 0.00 | 0.00 | 0.429190E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.552893E+10 | 0.00 | 0.00 | 0.515036E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.706860E+10 | 0.00 | 0.00 | 0.563301E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.587717E+10 | 0.00 | 0.00 | 0.756840E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.00 | 0.519778E+10 | 0.00 | 0.00 | 0.660143E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
November | 0.00 | 0.431533E+10 | 0.00 | 0.00 | 0.535927E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
December | 23852.31 | 0.329585E+10 | 0.00 | 0.00 | 0.532546E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 929537.52 | 0.654686E+11 | 0.00 | 0.00 | 0.655608E+10 | 0.00 | 0.00 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.320084E+10 | 0.00 | 0.00 | 0.414956E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 905685.22 | 0.900607E+10 | 0.00 | 0.00 | 0.756840E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 647814.11 | 0.260393E+10 | 0.00 | 311.64 | 0.320493E+09 | 0.00 | 135258.35 | 0.00 | 0.51 |
February | 0.00 | 0.276896E+10 | 0.00 | 0.00 | 0.279128E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
March | 0.00 | 0.388830E+10 | 0.00 | 0.00 | 0.316853E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
April | 0.00 | 0.498713E+10 | 0.00 | 0.00 | 0.492614E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
May | 0.00 | 0.579715E+10 | 0.00 | 0.00 | 0.621085E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
June | 0.00 | 0.594646E+10 | 0.00 | 0.00 | 0.509069E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.371983E+10 | 0.00 | 0.00 | 0.508615E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.537183E+10 | 0.00 | 0.00 | 0.467619E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.473695E+10 | 0.00 | 0.00 | 0.548649E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
October | 0.00 | 0.413905E+10 | 0.00 | 0.00 | 0.511165E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 0.00 | 0.343512E+10 | 0.00 | 0.00 | 0.373606E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
December | 20631.36 | 0.271285E+10 | 0.00 | 0.00 | 0.367642E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 668445.47 | 0.501076E+11 | 0.00 | 311.64 | 0.531654E+10 | 0.00 | 135258.35 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.260393E+10 | 0.00 | 0.00 | 0.279128E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 647814.11 | 0.594646E+10 | 0.00 | 311.64 | 0.621085E+09 | 0.00 | 135258.35 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 620097.44 | 0.489437E+10 | 0.00 | 304.54 | 0.215558E+09 | 0.00 | 284737.80 | 0.00 | 0.55 |
February | 0.00 | 0.469021E+10 | 0.00 | 0.00 | 0.251611E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
March | 0.00 | 0.532538E+10 | 0.00 | 0.00 | 0.352717E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
April | 0.00 | 0.580890E+10 | 0.00 | 0.00 | 0.668307E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 0.00 | 0.717900E+10 | 0.00 | 0.00 | 0.824443E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.719326E+10 | 0.00 | 0.00 | 0.654787E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.472439E+10 | 0.00 | 0.00 | 0.644392E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.660675E+10 | 0.00 | 0.00 | 0.607998E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.621681E+10 | 0.00 | 0.00 | 0.708456E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.635099E+10 | 0.00 | 0.00 | 0.478508E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
November | 0.00 | 0.598591E+10 | 0.00 | 0.00 | 0.299180E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
December | 23837.94 | 0.519918E+10 | 0.00 | 0.00 | 0.259693E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 643935.38 | 0.701751E+11 | 0.00 | 304.54 | 0.596565E+10 | 0.00 | 284737.80 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.469021E+10 | 0.00 | 0.00 | 0.215558E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 620097.44 | 0.719326E+10 | 0.00 | 304.54 | 0.824443E+09 | 0.00 | 284737.80 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 856217.71 | 0.269456E+10 | 0.00 | 0.00 | 0.352591E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
February | 0.00 | 0.284762E+10 | 0.00 | 0.00 | 0.381023E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
March | 0.00 | 0.401840E+10 | 0.00 | 0.00 | 0.376884E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
April | 0.00 | 0.498385E+10 | 0.00 | 0.00 | 0.603207E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
May | 0.00 | 0.570036E+10 | 0.00 | 0.00 | 0.786830E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
June | 0.00 | 0.586491E+10 | 0.00 | 0.00 | 0.624538E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.369917E+10 | 0.00 | 0.00 | 0.625363E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.534394E+10 | 0.00 | 0.00 | 0.542999E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.465872E+10 | 0.00 | 0.00 | 0.695840E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.414580E+10 | 0.00 | 0.00 | 0.635320E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
November | 0.00 | 0.347595E+10 | 0.00 | 0.00 | 0.501275E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
December | 22549.52 | 0.275818E+10 | 0.00 | 0.00 | 0.465708E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 878767.23 | 0.501915E+11 | 0.00 | 0.00 | 0.659158E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.269456E+10 | 0.00 | 0.00 | 0.352591E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 856217.71 | 0.586491E+10 | 0.00 | 0.00 | 0.786830E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.234645E+12 | -0.984787E+10 | 0.00 | -0.117569E+12 | 0.364782E+12 |
February | 0.228448E+12 | -0.101108E+11 | 0.00 | -0.117938E+12 | 0.350109E+12 |
March | 0.292308E+12 | -0.162962E+11 | 0.00 | -0.146081E+12 | 0.427965E+12 |
April | 0.287882E+12 | -0.179846E+11 | 0.00 | -0.188443E+12 | 0.448000E+12 |
May | 0.289400E+12 | -0.224854E+11 | 0.00 | -0.230701E+12 | 0.508228E+12 |
June | 0.300050E+12 | -0.219085E+11 | 0.00 | -0.224184E+12 | 0.510351E+12 |
July | 0.250048E+12 | -0.133940E+11 | 0.00 | -0.167713E+12 | 0.402148E+12 |
August | 0.311034E+12 | -0.201648E+11 | 0.00 | -0.207452E+12 | 0.467972E+12 |
September | 0.245819E+12 | -0.155403E+11 | 0.00 | -0.197823E+12 | 0.428178E+12 |
October | 0.272071E+12 | -0.148487E+11 | 0.00 | -0.187430E+12 | 0.412511E+12 |
November | 0.225408E+12 | -0.121920E+11 | 0.00 | -0.158497E+12 | 0.385117E+12 |
December | 0.221691E+12 | -0.941945E+10 | 0.00 | -0.130671E+12 | 0.356815E+12 |
Annual Sum or Average | 0.315880E+13 | -0.184192E+12 | 0.00 | -0.207450E+13 | 0.506218E+13 |
Minimum of Months | 0.221691E+12 | -0.224854E+11 | 0.00 | -0.230701E+12 | 0.350109E+12 |
Maximum of Months | 0.311034E+12 | -0.941945E+10 | 0.00 | -0.117569E+12 | 0.510351E+12 |